-- Data Aire-dap4_al.MIB
|
|
-- MIB generated by Data Aire
|
|
-- Tuesday, 12 July 2011
|
|
--
|
|
|
|
DataAire-dap4-al-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
OBJECT-GROUP
|
|
FROM SNMPv2-CONF
|
|
sysContact, sysName, sysLocation
|
|
FROM SNMPv2-MIB
|
|
enterprises, MODULE-IDENTITY, OBJECT-TYPE, Integer32
|
|
FROM SNMPv2-SMI;
|
|
|
|
dap4-alMIB MODULE-IDENTITY
|
|
LAST-UPDATED "201107120850Z" -- July 12, 2011 at 08:50 GMT
|
|
ORGANIZATION "Data Aire"
|
|
CONTACT-INFO
|
|
"
|
|
Data Aire
|
|
230 West Blueridge Ave
|
|
Orange, CA
|
|
Tel: 1-800-347-2473
|
|
E-mail: sales@dataaire.com
|
|
"
|
|
DESCRIPTION
|
|
"This is the MIB module for the dap4_al device."
|
|
REVISION "201107120850Z"
|
|
DESCRIPTION
|
|
"version 1.0"
|
|
::= { instruments 1 }
|
|
|
|
|
|
--
|
|
-- Node definitions
|
|
--
|
|
|
|
-- 1.3.6.1.4.1.9839
|
|
carel OBJECT IDENTIFIER ::= { enterprises 9839 }
|
|
|
|
-- 1.3.6.1.4.1.9839.1
|
|
systm OBJECT IDENTIFIER ::= { carel 1 }
|
|
|
|
-- 1.3.6.1.4.1.9839.1.1
|
|
agentRelease OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Release of the Agent."
|
|
::= { systm 1 }
|
|
|
|
-- 1.3.6.1.4.1.9839.1.2
|
|
agentCode OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Code of the Agent. 2=pCOWeb."
|
|
::= { systm 2 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2
|
|
instruments OBJECT IDENTIFIER ::= { carel 2 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.0
|
|
pCOWebInfo OBJECT IDENTIFIER ::= { instruments 0 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.9839.2.0.10
|
|
pCOStatusgroup OBJECT IDENTIFIER ::= { pCOWebInfo 10 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.0.10.1
|
|
pCOId1-Status OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Status of pCOId1. 0=Offline, 1=Init, 2=Online"
|
|
::= { pCOStatusgroup 1 }
|
|
|
|
-- ... You will have how many pCOIdX-Status objects as the pCOs connected to pCOWeb.
|
|
|
|
-- 1.3.6.1.4.1.9839.2.0.11
|
|
pCOErrorsNumbergroup OBJECT IDENTIFIER ::= { pCOWebInfo 11 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.0.11.1
|
|
pCOId1-ErrorsNumber OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Number of Communication Errors from pCOId1 to pCOWeb."
|
|
::= { pCOErrorsNumbergroup 1 }
|
|
|
|
-- ... You will have how many pCOIdX-ErrorsNumber objects as the pCOs connected to pCOWeb.
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1
|
|
digitalObjects OBJECT IDENTIFIER ::= { dap4-alMIB 1 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.1
|
|
dehum-on OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Dehumidify mode is running"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 1 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.2
|
|
hum-on OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Humidifier is running"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 2 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.3
|
|
engy-on OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Energy saver is running"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 3 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.4
|
|
cool-inhibit OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Cooling inhibit from Zone Master"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 4 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.5
|
|
heat-held OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Heat inhibited due to alarm condition"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 5 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.6
|
|
humidifier-inhibit OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Humidifier stopped due to alarm"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 6 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.7
|
|
dehum-inhibit OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Dehum is inhibited"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 7 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.8
|
|
rht-during-dehum OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "reheat during dehum"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 8 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.9
|
|
floor-wtr-alm OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Water under floor alarm"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 9 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.10
|
|
air-flow-alm OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "No air flow alarm"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 10 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.11
|
|
filter-alm OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Dirty filter from digital input"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 11 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.12
|
|
humidifier-alm OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Alarm from humidifier digital input"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 12 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.13
|
|
firestat-alm OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Temperature of return air above firestat alarm set point"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 13 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.14
|
|
shortcycle-alm OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "One or more comps has short cycled"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 14 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.15
|
|
humidity-fail OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Sensor is out of range"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 15 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.16
|
|
ret-air-fail OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Sensor is out of range"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 16 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.17
|
|
maint-alm OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Maintenance Schedule Due alarm"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 17 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.18
|
|
c1-hp-alm OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "High pressure alarm"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 18 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.19
|
|
c1-lp-alm OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Low pressure alarm"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 19 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.20
|
|
c2-hp-alm OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "High pressure alarm"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 20 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.21
|
|
c2-lp-alm OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Low pressure alarm"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 21 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.22
|
|
smoke-alm OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Smoke detected from digital input"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 22 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.23
|
|
wtr-flow-alm OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "No water flow alarm"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 23 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.24
|
|
disch-air-fail OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Sensor is out of range"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 24 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.25
|
|
ra-tmp-hi-alm OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Temperature of return air above alarm set point"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 25 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.26
|
|
ra-tmp-lo-alm OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Temperature of return air below alarm set point"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 26 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.27
|
|
hum-hi-alm OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Humidity above alarm set point"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 27 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.28
|
|
hum-lo-alm OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Humidity below alarm set point"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 28 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.29
|
|
fan-overload OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Fan overload"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 29 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.30
|
|
stdby-pump-on OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Standby pump on: Check primary pump -Optional alarm. Pump failure input signal required"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 30 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.31
|
|
cust-msg-sw1 OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Custom alarm #1 -Optional alarm. External alarm input required. Factory programmed custom message required"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 31 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.32
|
|
cust-msg-sw2 OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Custom alarm #2 -Optional alarm. External alarm input required. Factory programmed custom message required"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 32 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.33
|
|
cust-msg-sw3 OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Custom alarm #3 -Optional alarm. External alarm input required. Factory programmed custom message required"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 33 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.34
|
|
cust-msg-sw4 OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Custom alarm #4 -Optional alarm. External alarm input required. Factory programmed custom message required"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 34 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.35
|
|
humsw-inhibit OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Humidifier stopped due to custom alarm switch"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 35 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.36
|
|
heat-inhibit OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Heat inhibited due to custom switch alarm condition"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 36 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.37
|
|
rht-hum-inhibit OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Reheat and humidification inhibited from operation"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 37 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.38
|
|
disch-tmp-lo-alm OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Temperature of discharge air below alarm set point"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 38 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.39
|
|
override-alm OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Manual override: Check bypass switches - Standard alarm. Manual override switch is on"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 39 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.40
|
|
condensation-alm OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "High condensation from digital input"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 40 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.41
|
|
unit-in-standby OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Unit in standby, all functions held off - Optional alarm. Control input signal required Factory setting required "
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 41 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.42
|
|
cw-sns-fail OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Sensor is out of range"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 42 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.43
|
|
humsw-chk-cyl OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Humidifier stopped due to custom alarm switch"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 43 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.44
|
|
bms-cooling-inhibit OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Cooling operation inhibited by BMS"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 44 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.45
|
|
bms-heat-inhibit OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Heat inhibited due to bms"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 45 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.46
|
|
bms-humidifier-inhibit OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Humidifier operation inhibited by BMS"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 46 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.47
|
|
bms-dehum-inhibit OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Dehumidify mode inhibited by bms"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 47 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.48
|
|
fan-inhibit-bms OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Inhibit fan by bms"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 48 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.49
|
|
hum-expect OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Reduces control humidity cycling"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 49 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.50
|
|
usashr-f-c OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Temperature Mode 0=_C 1=_F"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 50 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.52
|
|
lead-comp OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Lead compressor select 0= C1, 1= C2"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 52 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.53
|
|
wtrvlv-dir OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Water valve direct or reverse acting"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 53 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.54
|
|
ups-on-alm OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Alarm: UPS power on: Check main power -Optional alarm. External alarm input required"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 54 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.55
|
|
pwrup-alm OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Loss of power requires manual reset of alarm"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 55 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.56
|
|
seetag-cust-alm1 OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Local alarm #1: See tag inside door =Optional alarm. External alarm input required"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 56 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.57
|
|
seetag-cust-alm2 OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Local alarm #2: See tag inside door =Optional alarm. External alarm input required"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 57 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.58
|
|
seetag-cust-alm3 OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Local alarm #3: See tag inside door =Optional alarm. External alarm input required"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 58 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.59
|
|
seetag-cust-alm4 OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Local alarm #4: See tag inside door =Optional alarm. External alarm input required"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 59 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.60
|
|
shortcycle-alm-en OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Enable short cycle alarm of the compressors"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 60 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.61
|
|
superv-off OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Supervisor (BMS) On-Off. Show the state OFFbyBMS in main mask (1: Off; 0: On"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 61 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.1.62
|
|
BMS-heartbeat OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Bms heartbeat - pCO looks for update every 10 minutes"
|
|
DEFVAL { 0 }
|
|
::= { digitalObjects 62 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.2
|
|
analogObjects OBJECT IDENTIFIER ::= { dap4-alMIB 2 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.2.1
|
|
ret-air-tmp OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Temperature of return air"
|
|
DEFVAL { 0 }
|
|
::= { analogObjects 1 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.2.2
|
|
minmax-24hr-retair-maximum OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Maximum Return air temp in last 24hrs"
|
|
DEFVAL { 0 }
|
|
::= { analogObjects 2 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.2.3
|
|
minmax-24hr-retair-minumum OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Minimum Return air temp in last 24hrs"
|
|
DEFVAL { 0 }
|
|
::= { analogObjects 3 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.2.4
|
|
temp-setpoint OBJECT-TYPE
|
|
SYNTAX Integer32 (-9999..9999)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Temperature setpoint"
|
|
DEFVAL { 0 }
|
|
::= { analogObjects 4 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.2.5
|
|
temp-deadband OBJECT-TYPE
|
|
SYNTAX Integer32 (0..99)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Amount from setpoint before a comp is staged on"
|
|
DEFVAL { 0 }
|
|
::= { analogObjects 5 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.2.6
|
|
humidity-ain-offs OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Humidity Sensor Calibration"
|
|
DEFVAL { 0 }
|
|
::= { analogObjects 6 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.2.7
|
|
return-ain-offs OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Return Temperature Sensor Calibration"
|
|
DEFVAL { 0 }
|
|
::= { analogObjects 7 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.2.8
|
|
cw-tmp OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Temperature of chilled water"
|
|
DEFVAL { 0 }
|
|
::= { analogObjects 8 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.2.9
|
|
disch-air-tmp OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Temperature of discharge air"
|
|
DEFVAL { 0 }
|
|
::= { analogObjects 9 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.2.10
|
|
discharge-ain-offs OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Discharge Temperature Sensor Calibration - Optional discharge air temperature sensor required (B9)"
|
|
DEFVAL { 0 }
|
|
::= { analogObjects 10 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.2.11
|
|
cw-ain-offs OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Chilled Water Temperature Sensor Calibration - Optional chilled water temperature sensor required (B10)"
|
|
DEFVAL { 0 }
|
|
::= { analogObjects 11 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.2.12
|
|
engsaver-setpoint OBJECT-TYPE
|
|
SYNTAX Integer32 (-9999..9999)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Temperature setpoint where chilled water will is requested"
|
|
DEFVAL { 0 }
|
|
::= { analogObjects 12 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.2.13
|
|
opt1-analog OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Value of the analog input"
|
|
DEFVAL { 0 }
|
|
::= { analogObjects 13 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.2.14
|
|
opt2-analog OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Value of the analog input"
|
|
DEFVAL { 0 }
|
|
::= { analogObjects 14 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.2.15
|
|
opt3-analog OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Value of the analog input"
|
|
DEFVAL { 0 }
|
|
::= { analogObjects 15 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.2.16
|
|
opt4-analog OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Value of the analog input"
|
|
DEFVAL { 0 }
|
|
::= { analogObjects 16 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.2.17
|
|
opt-sns-1-y1 OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Analog Sensor 1 Minimum Value"
|
|
DEFVAL { 0 }
|
|
::= { analogObjects 17 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.2.18
|
|
opt-sns-1-y2 OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Analog Sensor 1 Maximum Value"
|
|
DEFVAL { 1000 }
|
|
::= { analogObjects 18 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.2.19
|
|
opt-sns-1-ain-offs OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Analog Sensor 1 Calibration"
|
|
DEFVAL { 0 }
|
|
::= { analogObjects 19 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.2.20
|
|
opt-sns-2-y1 OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Analog Sensor 2 Minimum Value"
|
|
DEFVAL { 0 }
|
|
::= { analogObjects 20 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.2.21
|
|
opt-sns-2-y2 OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Analog Sensor 2 Maximum Value"
|
|
DEFVAL { 1000 }
|
|
::= { analogObjects 21 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.2.22
|
|
opt-sns-2-ain-offs OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Analog Sensor 2 Calibration"
|
|
DEFVAL { 0 }
|
|
::= { analogObjects 22 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.2.23
|
|
opt-sns-3-y1 OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Analog Sensor 3 Minimum Value"
|
|
DEFVAL { 0 }
|
|
::= { analogObjects 23 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.2.24
|
|
opt-sns-3-y2 OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Analog Sensor 3 Maximum Value"
|
|
DEFVAL { 1000 }
|
|
::= { analogObjects 24 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.2.25
|
|
opt-sns-3-ain-offs OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Analog Sensor 3 Calibration"
|
|
DEFVAL { 0 }
|
|
::= { analogObjects 25 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.2.26
|
|
opt-sns-4-y1 OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Analog Sensor 4 Minimum Value"
|
|
DEFVAL { 0 }
|
|
::= { analogObjects 26 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.2.27
|
|
opt-sns-4-y2 OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Analog Sensor 4 Maximum Value"
|
|
DEFVAL { 1000 }
|
|
::= { analogObjects 27 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.2.28
|
|
opt-sns-4-ain-offs OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Analog Sensor 4 Calibration"
|
|
DEFVAL { 0 }
|
|
::= { analogObjects 28 }
|
|
|
|
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3
|
|
integerObjects OBJECT IDENTIFIER ::= { dap4-alMIB 3 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.1
|
|
disch-air-lo-sp OBJECT-TYPE
|
|
SYNTAX Integer32 (-32767..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Lower Limit alarm of discharge air temp"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 1 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.2
|
|
humidity-dis OBJECT-TYPE
|
|
SYNTAX Integer32 (-999..999)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Relative humidity displayed as xx%"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 2 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.3
|
|
stages-on OBJECT-TYPE
|
|
SYNTAX Integer32 (-32767..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Cooling Stages On, DX only"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 3 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.4
|
|
heaters-on OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Number of heat stages running"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 4 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.5
|
|
minmax-24hr-hum-maximum OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Maximum humidity in last 24hrs"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 5 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.6
|
|
minmax-24hr-hum-minumum OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Minimum humidity in last 24hrs"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 6 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.7
|
|
comp-duty OBJECT-TYPE
|
|
SYNTAX Integer32 (0..999)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Cooling Utilization Over Last Hour -Percentage of cooling is used in the last hour of operation; this point applies to DX unit."
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 7 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.8
|
|
heat-duty OBJECT-TYPE
|
|
SYNTAX Integer32 (0..999)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Heating Utilization Over Last Hour -Percentage of heating is used in the last hour of operation"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 8 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.9
|
|
hum-duty OBJECT-TYPE
|
|
SYNTAX Integer32 (0..999)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Humidifier Utilization Over Last Hour -Percentage of humidifier is used in the last hour of operation"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 9 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.10
|
|
c1-hours-h OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Compressor 1 Runtime -This point applies to DX unit with one compressor -high"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 10 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.11
|
|
c1-hours-l OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "hour"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Compressor 1 Runtime -This point applies to DX unit with one compressor -low"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 11 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.12
|
|
c2-hours-h OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Compressor 2 Runtime -This point applies to DX unit with dual compressor - high"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 12 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.13
|
|
c2-hours-l OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "hour"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Compressor 2 Runtime -This point applies to DX unit with dual compressor - low"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 13 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.14
|
|
ht1-hours-h OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Heater 1 Runtime - high"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 14 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.15
|
|
ht1-hours-l OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "hour"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Heater 1 Runtime - low"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 15 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.16
|
|
current-second OBJECT-TYPE
|
|
SYNTAX Integer32 (0..59)
|
|
UNITS "sec"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Current second"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 16 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.17
|
|
current-minute OBJECT-TYPE
|
|
SYNTAX Integer32 (0..59)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Current minute"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 17 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.18
|
|
current-hour OBJECT-TYPE
|
|
SYNTAX Integer32 (0..23)
|
|
UNITS "hour"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Current hour"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 18 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.19
|
|
current-day OBJECT-TYPE
|
|
SYNTAX Integer32 (1..31)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Current day"
|
|
DEFVAL { 1 }
|
|
::= { integerObjects 19 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.20
|
|
current-month OBJECT-TYPE
|
|
SYNTAX Integer32 (1..12)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Current month"
|
|
DEFVAL { 1 }
|
|
::= { integerObjects 20 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.21
|
|
current-year OBJECT-TYPE
|
|
SYNTAX Integer32 (0..99)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Current year"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 21 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.22
|
|
firestat-sp OBJECT-TYPE
|
|
SYNTAX Integer32 (0..999)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Alarm settting of return air temp to determine there is a fire"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 22 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.23
|
|
hum-hi-sp OBJECT-TYPE
|
|
SYNTAX Integer32 (0..99)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Humidity upper limit alarm"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 23 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.24
|
|
ret-air-hi-sp OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Upper limit alarm of return air temp"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 24 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.25
|
|
hum-lo-sp OBJECT-TYPE
|
|
SYNTAX Integer32 (0..99)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Humidity lower limit alarm"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 25 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.26
|
|
ret-air-lo-sp OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Lower limit alarm of return air temp"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 26 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.27
|
|
hum-deadband OBJECT-TYPE
|
|
SYNTAX Integer32 (0..999)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "amount hum must change from setpoint before acting"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 27 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.28
|
|
hum-setpoint OBJECT-TYPE
|
|
SYNTAX Integer32 (0..999)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "humidity setpoint"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 28 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.29
|
|
start-dly OBJECT-TYPE
|
|
SYNTAX Integer32 (1..600)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Time before the system starts up"
|
|
DEFVAL { 10 }
|
|
::= { integerObjects 29 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.30
|
|
alm1-del OBJECT-TYPE
|
|
SYNTAX Integer32 (0..32000)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Optional Alarm 1 Delay"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 30 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.31
|
|
alm2-del OBJECT-TYPE
|
|
SYNTAX Integer32 (0..32000)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Optional Alarm 2 Delay"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 31 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.32
|
|
alm3-del OBJECT-TYPE
|
|
SYNTAX Integer32 (0..32000)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Optional Alarm 3 Delay"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 32 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.33
|
|
alarm1-txt OBJECT-TYPE
|
|
SYNTAX Integer32 (0..16)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Message on optional alarm screen, some also add function"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 33 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.34
|
|
alarm2-txt OBJECT-TYPE
|
|
SYNTAX Integer32 (0..16)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Message on optional alarm screen, some also add function"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 34 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.35
|
|
alarm3-txt OBJECT-TYPE
|
|
SYNTAX Integer32 (0..16)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Message on optional alarm screen, some also add function"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 35 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.36
|
|
alarm4-txt OBJECT-TYPE
|
|
SYNTAX Integer32 (0..16)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Message on optional alarm screen, some also add function"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 36 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.37
|
|
comp-sel OBJECT-TYPE
|
|
SYNTAX Integer32 (0..5)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Comps 0=none, 1=one, 2=one+UL, 3=two, 4=two+UL, 5=Four/two circuit"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 37 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.38
|
|
dehum-mode OBJECT-TYPE
|
|
SYNTAX Integer32 (0..4)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "0=none, 1= comp limited, 2=twocomp limited, 3= comp unlimited, 4=twocomp unlimited"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 38 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.39
|
|
reheat-sel OBJECT-TYPE
|
|
SYNTAX Integer32 (0..3)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Number of heat stages"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 39 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.40
|
|
hum-sel OBJECT-TYPE
|
|
SYNTAX Integer32 (0..4)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "0=none, 1=comp mod, 2=comp non, 3= comf mod, 4= conf non mod"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 40 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.41
|
|
alm-contact-msg OBJECT-TYPE
|
|
SYNTAX Integer32 (0..4)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Text displayed on all alarm screens"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 41 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.42
|
|
powerup-sel OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "0= start wo/alarm, 1= start w/alarm, 2= requires reset of alarm"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 42 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.43
|
|
buzzer-select OBJECT-TYPE
|
|
SYNTAX Integer32 (0..3)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "0=None, 1=short beeps, 2=long beep, 3=Constant"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 43 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.44
|
|
cw-disp OBJECT-TYPE
|
|
SYNTAX Integer32 (0..999)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "% of 10volts of analog output #1"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 44 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.45
|
|
wtrvlv-duty OBJECT-TYPE
|
|
SYNTAX Integer32 (0..999)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Chilled Water Utilization Over Last Hour - This applies to Chilled water or Energy saver units. "
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 45 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.46
|
|
hum-hours-h OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Humidifier Runtime - high"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 46 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.47
|
|
hum-hours-l OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "hour"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Humidifier Runtime - low"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 47 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.48
|
|
blower-hours-h OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Blower Runtime - high"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 48 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.49
|
|
blower-hours-l OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "hour"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Blower Runtime - low"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 49 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.50
|
|
alm4-del OBJECT-TYPE
|
|
SYNTAX Integer32 (0..32000)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Optional Alarm 4 Delay"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 50 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.51
|
|
assist-sel OBJECT-TYPE
|
|
SYNTAX Integer32 (0..5)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "0= no comp assist, 1=one comp assist, 2= two comp assist, 3... 4..."
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 51 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.52
|
|
wtrvlv-sel OBJECT-TYPE
|
|
SYNTAX Integer32 (0..4)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Water valve type 0=none, 1=chill, 2=Engy, 3=Aux chill, 4=Disc Reg"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 52 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.53
|
|
wtrvlv-volts-sel OBJECT-TYPE
|
|
SYNTAX Integer32 (0..4)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Water valve voltage 0= 0-10, 1=2-10, 2=7-10, 3=6-9, 4=4-7"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 53 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.54
|
|
hum-volts OBJECT-TYPE
|
|
SYNTAX Integer32 (0..999)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "% of 10volts of analog output #2"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 54 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.55
|
|
dehum-hours-h OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Dehumidifier Runtime - High"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 55 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.56
|
|
dehum-hours-l OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "hour"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Dehumidifier Runtime - Low"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 56 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.58
|
|
autoflush-dly OBJECT-TYPE
|
|
SYNTAX Integer32 (0..99)
|
|
UNITS "hour"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Time between drain cycles 0=12hr, 1=24hr, 2=48hr, 3=96hr, 4=None"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 58 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.59
|
|
y4-out OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Value sent to optional analog output#1"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 59 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.60
|
|
y5-out OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Value sent to optional analog output#2"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 60 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.61
|
|
air-flow OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Current Fan Airflow - Based on calculated Pressure Diff formula"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 61 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.62
|
|
opt-snsr1-name OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Name of the sensor"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 62 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.63
|
|
opt-sns-1-ain-type OBJECT-TYPE
|
|
SYNTAX Integer32 (0..9)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Analog Sensor 1 Type {0=NTC 1=PT1000 2=0-1VDC 3=0-10VDC 4=4-20mA 5=ON/OFF 6=0-5VDC 7=NTC HT 8=-50T90 9=10T170}"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 63 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.64
|
|
opt-snsr2-name OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Name of the sensor"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 64 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.65
|
|
opt-sns-2-ain-type OBJECT-TYPE
|
|
SYNTAX Integer32 (0..9)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Analog Sensor 2 Type {0=NTC 1=PT1000 2=0-1VDC 3=0-10VDC 4=4-20mA 5=ON/OFF 6=0-5VDC 7=NTC HT 8=-50T90 9=10T170}"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 65 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.66
|
|
opt-snsr3-name OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Name of the sensor"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 66 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.67
|
|
opt-sns-3-ain-type OBJECT-TYPE
|
|
SYNTAX Integer32 (0..9)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Analog Sensor 3 Type {0=NTC 1=PT1000 2=0-1VDC 3=0-10VDC 4=4-20mA 5=ON/OFF 6=0-5VDC 7=NTC HT 8=-50T90 9=10T170}"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 67 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.68
|
|
opt-snsr4-name OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Name of the sensor"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 68 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.69
|
|
opt-sns-4-ain-type OBJECT-TYPE
|
|
SYNTAX Integer32 (0..9)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Analog Sensor 4 Type {0=NTC 1=PT1000 2=0-1VDC 3=0-10VDC 4=4-20mA 5=ON/OFF 6=0-5VDC 7=NTC HT 8=-50T90 9=10T170}"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 69 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.70
|
|
cw-fan-speed-bms OBJECT-TYPE
|
|
SYNTAX Integer32 (0..100)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "CW Fan speed (%) sent via BMS"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 70 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.71
|
|
dx-fan-speed-bms OBJECT-TYPE
|
|
SYNTAX Integer32 (0..100)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "DX Fan speed (%) sent via BMS"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 71 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.72
|
|
fan-speed-max OBJECT-TYPE
|
|
SYNTAX Integer32 (70..100)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Maximum Fan speed (% of output) modulation."
|
|
DEFVAL { 100 }
|
|
::= { integerObjects 72 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.73
|
|
fan-speed-min OBJECT-TYPE
|
|
SYNTAX Integer32 (40..100)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Minimum Fan speed (% of output) modulation from pressure."
|
|
DEFVAL { 40 }
|
|
::= { integerObjects 73 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.74
|
|
fan-pr-sp OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1001)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Fan pressure setpoint (0.01 inches of water)"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 74 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.75
|
|
fan-pr-band OBJECT-TYPE
|
|
SYNTAX Integer32 (1..100)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Fan pressure band (0.01 inches of water)"
|
|
DEFVAL { 5 }
|
|
::= { integerObjects 75 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.76
|
|
fan-af-max OBJECT-TYPE
|
|
SYNTAX Integer32 (0..32000)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Maximum air flow limit of setpoint from BMS or valve modulation."
|
|
DEFVAL { 1000 }
|
|
::= { integerObjects 76 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.77
|
|
fan-af-min OBJECT-TYPE
|
|
SYNTAX Integer32 (0..32000)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Minimum air flow limit of setpoint from BMS or valve modulation."
|
|
DEFVAL { 1000 }
|
|
::= { integerObjects 77 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.78
|
|
fan-kfactor OBJECT-TYPE
|
|
SYNTAX Integer32 (100..500)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Fan K Factor"
|
|
DEFVAL { 200 }
|
|
::= { integerObjects 78 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.79
|
|
num-fans OBJECT-TYPE
|
|
SYNTAX Integer32 (1..3)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Number of fans installed in this unit"
|
|
DEFVAL { 1 }
|
|
::= { integerObjects 79 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.81
|
|
ht2-hours-h OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Heater 2 Runtime - high"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 81 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.82
|
|
ht2-hours-l OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "hour"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Heater 2 Runtime - low"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 82 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.83
|
|
ht3-hours-h OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Heater 3 Runtime - high"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 83 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.84
|
|
ht3-hours-l OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "hour"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Heater 3 Runtime - low"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 84 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.85
|
|
engy-hours-h OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Energy Saver Runtime - This optional point applies to energy saver units only -high"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 85 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.86
|
|
engy-hours-l OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "hour"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Energy Saver Runtime - This optional point applies to energy saver units only - low"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 86 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.87
|
|
cw-hours-h OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Chilled Water Runtime - This applies to chilled water units only - high"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 87 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.88
|
|
cw-hours-l OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "hour"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Chilled Water Runtime - This applies to chilled water units only - low"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 88 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.89
|
|
c3-hours-h OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Compressor 3 Runtime - This applies when unit has four stages tandem compressors - high"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 89 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.90
|
|
c3-hours-l OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "hour"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Compressor 3 Runtime - This applies when unit has four stages tandem compressors - low"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 90 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.91
|
|
c4-hours-l OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "hour"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Compressor 4 Runtime - This applies when unit has four stages tandem compressors. - high"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 91 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.92
|
|
c4-hours-h OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Compressor 4 Runtime - This applies when unit has four stages tandem compressors. - low"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 92 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.93
|
|
cond-hours-h OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Condenser Runtime - high"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 93 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.94
|
|
cond-hours-l OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "hour"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Condenser Runtime - low"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 94 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.95
|
|
dx-fan-speed OBJECT-TYPE
|
|
SYNTAX Integer32 (60..100)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Fan speed (% of output) when compressor cooling."
|
|
DEFVAL { 85 }
|
|
::= { integerObjects 95 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.96
|
|
cw-fan-speed OBJECT-TYPE
|
|
SYNTAX Integer32 (60..100)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Fan speed (% of output) when cold water cooling."
|
|
DEFVAL { 85 }
|
|
::= { integerObjects 96 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.97
|
|
fan-af-dx-sp OBJECT-TYPE
|
|
SYNTAX Integer32 (0..32000)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Fan air flow setpoint for DX unit (cfm)"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 97 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.98
|
|
fan-af-cw-sp OBJECT-TYPE
|
|
SYNTAX Integer32 (0..32000)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Fan air flow setpoint for CW unit (cfm)"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 98 }
|
|
|
|
-- 1.3.6.1.4.1.9839.2.1.3.99
|
|
zm-airflow-sp OBJECT-TYPE
|
|
SYNTAX Integer32 (-32768..32767)
|
|
UNITS "N/A"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Zone Airflow Setpoint kcfm"
|
|
DEFVAL { 0 }
|
|
::= { integerObjects 99 }
|
|
|
|
|
|
|
|
END
|
|
|
|
--
|
|
-- DataAire-dap4-al.MIB
|
|
--
|