-- Title: DPS_V41.MIB
|
|
-- Version: v4.1
|
|
--
|
|
-- Copyright @ 1997-2004 DPS Inc. All Rights Reserved
|
|
--
|
|
-- This MIB defines objects for the DPS products.
|
|
--
|
|
--
|
|
|
|
DPS-MIB-V38 DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
DisplayString,
|
|
sysDescr,
|
|
sysLocation
|
|
FROM RFC1213-MIB
|
|
OBJECT-TYPE
|
|
FROM RFC1212-MIB
|
|
enterprises
|
|
FROM RFC1155-SMI
|
|
TRAP-TYPE
|
|
FROM RFC-1215;
|
|
|
|
dpsInc OBJECT IDENTIFIER ::= {enterprises 2682}
|
|
|
|
dpsAlarmControl OBJECT IDENTIFIER ::= {dpsInc 1}
|
|
|
|
tmonXM OBJECT IDENTIFIER ::= {dpsAlarmControl 1}
|
|
|
|
tmonIdent OBJECT IDENTIFIER ::= {tmonXM 1}
|
|
|
|
tmonIdentManufacturer OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The TMON/XM Unit manufacturer."
|
|
::= {tmonIdent 1}
|
|
|
|
tmonIdentModel OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The TMON/XM model designation."
|
|
::= {tmonIdent 2}
|
|
|
|
tmonIdentSoftwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The TMON/XM SNMP Agent software version."
|
|
::= {tmonIdent 3}
|
|
|
|
tmonAlarmTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF TMonAlarmEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "A table of TMon Alarm-specific information."
|
|
::= {tmonXM 2}
|
|
|
|
tmonAlarmEntry OBJECT-TYPE
|
|
SYNTAX TMonAlarmEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Information about a particular TMon alarm."
|
|
INDEX {tmonAIndex}
|
|
::= {tmonAlarmTable 1}
|
|
|
|
TMonAlarmEntry ::= SEQUENCE { tmonAIndex INTEGER,
|
|
tmonASite DisplayString,
|
|
tmonADesc DisplayString,
|
|
tmonAState DisplayString,
|
|
tmonASeverity DisplayString,
|
|
tmonAChgDate DisplayString,
|
|
tmonAChgTime DisplayString,
|
|
tmonAAuxDesc DisplayString,
|
|
tmonADispDesc DisplayString,
|
|
tmonAPntType INTEGER,
|
|
tmonAPort INTEGER,
|
|
tmonAAddress INTEGER,
|
|
tmonADisplay INTEGER,
|
|
tmonAPoint INTEGER,
|
|
tmonAIPAddr DisplayString,
|
|
tmonADevDesc DisplayString
|
|
}
|
|
|
|
tmonAIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..2147483647)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Tmon alarm table index (1..NumberOfAlarms)."
|
|
::={tmonAlarmEntry 1}
|
|
|
|
tmonASite OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The site of the alarm (i.e. Atlanta Hub, Sub-Station H32)."
|
|
::= {tmonAlarmEntry 2}
|
|
|
|
tmonADesc OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "A user-defined text string associated with the alarm
|
|
(i.e. South Door, Generator, Power Grid 1)."
|
|
::= {tmonAlarmEntry 3}
|
|
|
|
tmonAState OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The current alarm state."
|
|
::= {tmonAlarmEntry 4}
|
|
|
|
tmonASeverity OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The severity of the last alarm event."
|
|
::= {tmonAlarmEntry 5}
|
|
|
|
tmonAChgDate OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The date (mm/dd/yy) of the last alarm event."
|
|
::= {tmonAlarmEntry 6}
|
|
|
|
tmonAChgTime OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The time (hh:mm:ss) of the last alarm event."
|
|
::= {tmonAlarmEntry 7}
|
|
|
|
tmonAAuxDesc OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "An auxiliary user-defined text string associated with the
|
|
alarm (i.e. This remote needs servicing)."
|
|
::= {tmonAlarmEntry 8}
|
|
|
|
tmonADispDesc OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "A description of the display on which this point appears."
|
|
::= {tmonAlarmEntry 9}
|
|
|
|
tmonAPntType OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Type of this point."
|
|
::={tmonAlarmEntry 10}
|
|
|
|
tmonAPort OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Port on which this point is reported."
|
|
::={tmonAlarmEntry 11}
|
|
|
|
tmonAAddress OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Address of unit reporting this point."
|
|
::={tmonAlarmEntry 12}
|
|
|
|
tmonADisplay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Display on which this point appears."
|
|
::={tmonAlarmEntry 13}
|
|
|
|
tmonAPoint OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Index into display of this point."
|
|
::={tmonAlarmEntry 14}
|
|
|
|
tmonAIPAddr OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The IP Address of the device on which this point appears."
|
|
::= {tmonAlarmEntry 16}
|
|
|
|
tmonADevDesc OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "A description of the device on which this point appears."
|
|
::= {tmonAlarmEntry 17}
|
|
|
|
-- structure used to issue a command to tmonXM element
|
|
|
|
tmonCommandGrid OBJECT IDENTIFIER ::= {tmonXM 3}
|
|
|
|
tmonCPType OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Tmon point type."
|
|
::= {tmonCommandGrid 1}
|
|
|
|
tmonCPort OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Tmon port number."
|
|
::= {tmonCommandGrid 2}
|
|
|
|
tmonCAddress OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Tmon_port address number."
|
|
::= {tmonCommandGrid 3}
|
|
|
|
tmonCDisplay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Tmon_port_address display number."
|
|
::= {tmonCommandGrid 4}
|
|
|
|
tmonCPoint OBJECT-TYPE
|
|
SYNTAX INTEGER (1..64)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Tmon_port_display point number (1-64)."
|
|
::= {tmonCommandGrid 5}
|
|
|
|
tmonCEvent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Tmon event ID."
|
|
::= {tmonCommandGrid 6}
|
|
|
|
tmonCAction OBJECT-TYPE
|
|
SYNTAX INTEGER { latch(1),
|
|
release(2),
|
|
momentary(3),
|
|
ack(17),
|
|
tag(18),
|
|
untag(19)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Requested command action (tmonXM will ignore if invalid)."
|
|
::= {tmonCommandGrid 7}
|
|
|
|
tmonCAuxText OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "An auxiliary user-defined text string associated with the
|
|
command (i.e. User_initials)."
|
|
::= {tmonCommandGrid 8}
|
|
|
|
tmonCResult OBJECT-TYPE
|
|
SYNTAX INTEGER { success(1),
|
|
failure(2),
|
|
pending(3)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Command result."
|
|
::= {tmonCommandGrid 9}
|
|
|
|
|
|
|
|
dpsRTU OBJECT IDENTIFIER ::= {dpsAlarmControl 2}
|
|
|
|
dpsRTUIdent OBJECT IDENTIFIER ::= {dpsRTU 1}
|
|
|
|
dpsRTUManufacturer OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The Remote Telemetry Unit manufacturer."
|
|
::= {dpsRTUIdent 1}
|
|
|
|
dpsRTUModel OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The RTU model designation."
|
|
::= {dpsRTUIdent 2}
|
|
|
|
dpsRTUFirmwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The RTU firmware version."
|
|
::= {dpsRTUIdent 3}
|
|
|
|
dpsRTUDateTime OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "The RTU system date and time."
|
|
::= {dpsRTUIdent 4}
|
|
|
|
dpsRTUSyncReq OBJECT-TYPE
|
|
SYNTAX INTEGER { sync(1)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Caution: SETting this object initiates traps for all
|
|
standing alarms."
|
|
::= {dpsRTUIdent 5}
|
|
|
|
|
|
-- structure used to access displays managed by this RTU
|
|
|
|
dpsRTUDisplayGrid OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF DPSrtuDispEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Holds information on displays managed by the RTU."
|
|
::= {dpsRTU 2}
|
|
|
|
dpsRTUDisplayEntry OBJECT-TYPE
|
|
SYNTAX DPSrtuDispEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Information about a particular RTU display."
|
|
INDEX {dpsRTUPort, dpsRTUAddress, dpsRTUDisplay}
|
|
::= {dpsRTUDisplayGrid 1}
|
|
|
|
DPSrtuDispEntry ::= SEQUENCE { dpsRTUPort INTEGER,
|
|
dpsRTUAddress INTEGER,
|
|
dpsRTUDisplay INTEGER,
|
|
dpsRTUDispDesc DisplayString,
|
|
dpsRTUPntMap DisplayString
|
|
}
|
|
|
|
dpsRTUPort OBJECT-TYPE
|
|
SYNTAX INTEGER (0..999)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "RTU port number."
|
|
::= {dpsRTUDisplayEntry 1}
|
|
|
|
dpsRTUAddress OBJECT-TYPE
|
|
SYNTAX INTEGER (0..999)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "RTU_port address number."
|
|
::= {dpsRTUDisplayEntry 2}
|
|
|
|
dpsRTUDisplay OBJECT-TYPE
|
|
SYNTAX INTEGER (0..999)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "RTU_port_address display number."
|
|
::= {dpsRTUDisplayEntry 3}
|
|
|
|
dpsRTUDispDesc OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "A description of the associated display."
|
|
::= {dpsRTUDisplayEntry 4}
|
|
|
|
dpsRTUPntMap OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "A map of the points appearing in this display."
|
|
::= {dpsRTUDisplayEntry 5}
|
|
|
|
|
|
-- structure used to issue a control to a managed point
|
|
|
|
dpsRTUControlGrid OBJECT IDENTIFIER ::= {dpsRTU 3}
|
|
|
|
dpsRTUCPort OBJECT-TYPE
|
|
SYNTAX INTEGER (0..999)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "RTU port number."
|
|
::= {dpsRTUControlGrid 1}
|
|
|
|
dpsRTUCAddress OBJECT-TYPE
|
|
SYNTAX INTEGER (0..999)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "RTU_port address number."
|
|
::= {dpsRTUControlGrid 2}
|
|
|
|
dpsRTUCDisplay OBJECT-TYPE
|
|
SYNTAX INTEGER (0..999)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "RTU_port_address display number."
|
|
::= {dpsRTUControlGrid 3}
|
|
|
|
dpsRTUCPoint OBJECT-TYPE
|
|
SYNTAX INTEGER (1..64)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "RTU_port_display point number (1-64)."
|
|
::= {dpsRTUControlGrid 4}
|
|
|
|
dpsRTUCAction OBJECT-TYPE
|
|
SYNTAX INTEGER { latch(1),
|
|
release(2),
|
|
momentary(3)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Requested action on point (RTU will ignore if invalid)."
|
|
::= {dpsRTUControlGrid 5}
|
|
|
|
dpsRTUAlarmGrid OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF DPSrtuAlarmEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Holds individual alarm point information."
|
|
::= {dpsRTU 5}
|
|
|
|
dpsRTUAlarmEntry OBJECT-TYPE
|
|
SYNTAX DPSrtuAlarmEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Detailed information about a particular RTU display."
|
|
INDEX {dpsRTUAPort, dpsRTUAAddress, dpsRTUADisplay, dpsRTUAPoint}
|
|
::= {dpsRTUAlarmGrid 1}
|
|
|
|
DPSrtuAlarmEntry ::= SEQUENCE { dpsRTUAPort INTEGER,
|
|
dpsRTUAAddress INTEGER,
|
|
dpsRTUADisplay INTEGER,
|
|
dpsRTUAPoint INTEGER,
|
|
dpsRTUAPntDesc DisplayString,
|
|
dpsRTUAState DisplayString
|
|
}
|
|
|
|
dpsRTUAPort OBJECT-TYPE
|
|
SYNTAX INTEGER (0..999)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "RTU port number."
|
|
::= {dpsRTUAlarmEntry 1}
|
|
|
|
dpsRTUAAddress OBJECT-TYPE
|
|
SYNTAX INTEGER (0..999)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "RTU_port address number."
|
|
::= {dpsRTUAlarmEntry 2}
|
|
|
|
dpsRTUADisplay OBJECT-TYPE
|
|
SYNTAX INTEGER (0..999)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "RTU_port_address display number."
|
|
::= {dpsRTUAlarmEntry 3}
|
|
|
|
dpsRTUAPoint OBJECT-TYPE
|
|
SYNTAX INTEGER (0..999)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "RTU_port_address_display point number."
|
|
::= {dpsRTUAlarmEntry 4}
|
|
|
|
dpsRTUAPntDesc OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "A description of this point."
|
|
::= {dpsRTUAlarmEntry 5}
|
|
|
|
dpsRTUAState OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The current state of this point."
|
|
::= {dpsRTUAlarmEntry 6}
|
|
|
|
--Table for accessing analog channel value
|
|
|
|
analogChannels OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF ChannelEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Holds information on analog channels"
|
|
::= {dpsRTU 6}
|
|
|
|
channelEntry OBJECT-TYPE
|
|
SYNTAX ChannelEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Information about a particular channel"
|
|
INDEX {channelNumber}
|
|
::= {analogChannels 1}
|
|
|
|
ChannelEntry ::= SEQUENCE { channelNumber INTEGER,
|
|
enabled INTEGER,
|
|
description DisplayString,
|
|
value DisplayString,
|
|
thresholds INTEGER
|
|
}
|
|
|
|
channelNumber OBJECT-TYPE
|
|
SYNTAX INTEGER (0..999)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Input channel number"
|
|
::= {channelEntry 1}
|
|
|
|
enabled OBJECT-TYPE
|
|
SYNTAX INTEGER { disabled (0),
|
|
enabled (1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Enable status of channel"
|
|
::= {channelEntry 2}
|
|
|
|
description OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The user defined description of the channel"
|
|
::= {channelEntry 3}
|
|
|
|
value OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The current value of the channel"
|
|
::= {channelEntry 4}
|
|
|
|
thresholds OBJECT-TYPE
|
|
SYNTAX INTEGER { noAlarms (0),
|
|
minorUnder (1),
|
|
minorOver (2),
|
|
majorUnder (3),
|
|
majorOver (4),
|
|
notDetected (5)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Highest threshold level crossed, if MJ, MN is assumed"
|
|
::= {channelEntry 5}
|
|
|
|
-- TRAP definitions
|
|
|
|
tmonCRalarmSet TRAP-TYPE
|
|
ENTERPRISE tmonXM
|
|
VARIABLES { tmonASite, tmonADesc, tmonAState, tmonASeverity, tmonAChgDate,
|
|
tmonAChgTime, tmonAAuxDesc, tmonADispDesc, tmonAPntType,
|
|
tmonAPort, tmonAAddress, tmonADisplay, tmonAPoint, tmonCEvent,
|
|
tmonAIPAddr, tmonADevDesc }
|
|
DESCRIPTION "Generated when a critical alarm is set."
|
|
::= 10
|
|
|
|
tmonCRalarmClr TRAP-TYPE
|
|
ENTERPRISE tmonXM
|
|
VARIABLES { tmonASite, tmonADesc, tmonAState, tmonASeverity, tmonAChgDate,
|
|
tmonAChgTime, tmonAAuxDesc, tmonADispDesc, tmonAPntType,
|
|
tmonAPort, tmonAAddress, tmonADisplay, tmonAPoint, tmonCEvent,
|
|
tmonAIPAddr, tmonADevDesc }
|
|
DESCRIPTION "Generated when a critical alarm clears."
|
|
::= 11
|
|
|
|
tmonMJalarmSet TRAP-TYPE
|
|
ENTERPRISE tmonXM
|
|
VARIABLES { tmonASite, tmonADesc, tmonAState, tmonASeverity, tmonAChgDate,
|
|
tmonAChgTime, tmonAAuxDesc, tmonADispDesc, tmonAPntType,
|
|
tmonAPort, tmonAAddress, tmonADisplay, tmonAPoint, tmonCEvent,
|
|
tmonAIPAddr, tmonADevDesc }
|
|
DESCRIPTION "Generated when a major alarm is set."
|
|
::= 12
|
|
|
|
tmonMJalarmClr TRAP-TYPE
|
|
ENTERPRISE tmonXM
|
|
VARIABLES { tmonASite, tmonADesc, tmonAState, tmonASeverity, tmonAChgDate,
|
|
tmonAChgTime, tmonAAuxDesc, tmonADispDesc, tmonAPntType,
|
|
tmonAPort, tmonAAddress, tmonADisplay, tmonAPoint, tmonCEvent,
|
|
tmonAIPAddr, tmonADevDesc }
|
|
DESCRIPTION "Generated when a major alarm clears."
|
|
::= 13
|
|
|
|
tmonMNalarmSet TRAP-TYPE
|
|
ENTERPRISE tmonXM
|
|
VARIABLES { tmonASite, tmonADesc, tmonAState, tmonASeverity, tmonAChgDate,
|
|
tmonAChgTime, tmonAAuxDesc, tmonADispDesc, tmonAPntType,
|
|
tmonAPort, tmonAAddress, tmonADisplay, tmonAPoint, tmonCEvent,
|
|
tmonAIPAddr, tmonADevDesc }
|
|
DESCRIPTION "Generated when a minor alarm is set."
|
|
::= 14
|
|
|
|
tmonMNalarmClr TRAP-TYPE
|
|
ENTERPRISE tmonXM
|
|
VARIABLES { tmonASite, tmonADesc, tmonAState, tmonASeverity, tmonAChgDate,
|
|
tmonAChgTime, tmonAAuxDesc, tmonADispDesc, tmonAPntType,
|
|
tmonAPort, tmonAAddress, tmonADisplay, tmonAPoint, tmonCEvent,
|
|
tmonAIPAddr, tmonADevDesc }
|
|
DESCRIPTION "Generated when a minor alarm clears."
|
|
::= 15
|
|
|
|
tmonSTalarmSet TRAP-TYPE
|
|
ENTERPRISE tmonXM
|
|
VARIABLES { tmonASite, tmonADesc, tmonAState, tmonASeverity, tmonAChgDate,
|
|
tmonAChgTime, tmonAAuxDesc, tmonADispDesc, tmonAPntType,
|
|
tmonAPort, tmonAAddress, tmonADisplay, tmonAPoint, tmonCEvent,
|
|
tmonAIPAddr, tmonADevDesc }
|
|
DESCRIPTION "Generated when a status alarm is set."
|
|
::= 16
|
|
|
|
tmonSTalarmClr TRAP-TYPE
|
|
ENTERPRISE tmonXM
|
|
VARIABLES { tmonASite, tmonADesc, tmonAState, tmonASeverity, tmonAChgDate,
|
|
tmonAChgTime, tmonAAuxDesc, tmonADispDesc, tmonAPntType,
|
|
tmonAPort, tmonAAddress, tmonADisplay, tmonAPoint, tmonCEvent,
|
|
tmonAIPAddr, tmonADevDesc }
|
|
DESCRIPTION "Generated when a status alarm clears."
|
|
::= 17
|
|
|
|
dpsRTUPointSet TRAP-TYPE
|
|
ENTERPRISE dpsRTU
|
|
VARIABLES { sysDescr, sysLocation, dpsRTUDateTime,
|
|
dpsRTUAPort, dpsRTUAAddress, dpsRTUADisplay, dpsRTUAPoint,
|
|
dpsRTUAPntDesc, dpsRTUAState }
|
|
DESCRIPTION "Generated when a point is set."
|
|
::= 20
|
|
|
|
dpsRTUPointClr TRAP-TYPE
|
|
ENTERPRISE dpsRTU
|
|
VARIABLES { sysDescr, sysLocation, dpsRTUDateTime,
|
|
dpsRTUAPort, dpsRTUCAddress, dpsRTUADisplay, dpsRTUAPoint,
|
|
dpsRTUAPntDesc, dpsRTUAState }
|
|
DESCRIPTION "Generated when a point clears."
|
|
::= 21
|
|
|
|
dpsRTUsumPSet TRAP-TYPE
|
|
ENTERPRISE dpsRTU
|
|
VARIABLES { sysDescr, sysLocation, dpsRTUDateTime }
|
|
DESCRIPTION "Generated when any point is set."
|
|
::= 101
|
|
|
|
dpsRTUsumPClr TRAP-TYPE
|
|
ENTERPRISE dpsRTU
|
|
VARIABLES { sysDescr, sysLocation, dpsRTUDateTime }
|
|
DESCRIPTION "Generated when all points clear."
|
|
::= 102
|
|
|
|
dpsRTUcomFailed TRAP-TYPE
|
|
ENTERPRISE dpsRTU
|
|
VARIABLES { sysDescr, sysLocation, dpsRTUDateTime }
|
|
DESCRIPTION "Generated when polled unit fails to respond."
|
|
::= 103
|
|
|
|
dpsRTUcomRestored TRAP-TYPE
|
|
ENTERPRISE dpsRTU
|
|
VARIABLES { sysDescr, sysLocation, dpsRTUDateTime }
|
|
DESCRIPTION "Generated when failed unit resumes responding."
|
|
::= 104
|
|
|
|
-- **************************************************************************
|
|
-- Granular TRAP definitions
|
|
--
|
|
-- The following section supports granular trapping available on selected
|
|
-- DPS remote telemetry units. This software selectable facility changes the
|
|
-- trap sent by a remote so equipped. The standard trap identifies a SET or
|
|
-- CLR event in the trap ID and binds variables identifying the specific
|
|
-- remote point associated with the event. A granular trap identifies a SET
|
|
-- or CLR event and the specific point associated with the event all in the
|
|
-- trap ID. This is accomplished by mapping all SET event/points into the
|
|
-- trap ID range 10001-19999 and all CLR event/points into the trap ID range
|
|
-- 20001-29999.
|
|
-- If the unit manages multiple displays, the displays are mapped
|
|
-- sequentially with each display occupying a 64 point range. For example, a
|
|
-- standalone standard or timestamp KDA which manages two displays, reports
|
|
-- SET event/points in the first display (discrete alarm points) in the range
|
|
-- 10001-10064. The CLR event/points for the same display would be reported
|
|
-- in the range 20001-20064. The second display (controls & housekeeping
|
|
-- alarm points) would have its SET event/points reported in the range 10065-
|
|
-- 10128 and its CLR event/points reported in the range 20065-20128.
|
|
-- SET and CLR definitions for the first 64 points have been included and
|
|
-- can be used as is for driving most SNMP manager mechanisms designed to key
|
|
-- on the trap ID for distinguishing and managing events. Additional events
|
|
-- can be added simply by editing the following trap definitions prior to
|
|
-- compiling this file into your SNMP manager. We recommend managing the SET
|
|
-- and CLR event definitions for a specific point as a single unit and using
|
|
-- the following simple rules:
|
|
-- + Adjust the numeric portion of the label preceeding TRAP-TYPE.
|
|
-- + Adjust the numeric reference in the DESCRIPTION text.
|
|
-- + Adjust the number on the last line of the definition.
|
|
--
|
|
-- Using these rules a definition for the 65th point would be:
|
|
--
|
|
-- dpsRTUp0065Set TRAP-TYPE
|
|
-- ENTERPRISE dpsRTU
|
|
-- VARIABLES { sysDescr, sysLocation, dpsRTUDateTime,
|
|
-- dpsRTUAPort, dpsRTUCAddress, dpsRTUADisplay, dpsRTUAPoint,
|
|
-- dpsRTUAPntDesc, dpsRTUAState }
|
|
-- DESCRIPTION "Generated when granular point 65 is set."
|
|
-- ::= 10065
|
|
--
|
|
-- dpsRTUp0065Clr TRAP-TYPE
|
|
-- ENTERPRISE dpsRTU
|
|
-- VARIABLES { sysDescr, sysLocation, dpsRTUDateTime,
|
|
-- dpsRTUAPort, dpsRTUCAddress, dpsRTUADisplay, dpsRTUAPoint,
|
|
-- dpsRTUAPntDesc, dpsRTUAState }
|
|
-- DESCRIPTION "Generated when granular point 65 clears."
|
|
-- ::= 20065
|
|
--
|
|
-- This editing can can be accomplished quite easily using a plain ASCII
|
|
-- file editor. The repetitive structure of the definitions also makes for
|
|
-- rapid scripted or programmed generation if any such tools are available.
|
|
-- A compressed file containing event/point definitions for 144 displays is
|
|
-- available (DPS_G36.zip 150K) which uncompressed (DPS_G36.mib 6.2M) can be
|
|
-- used for cut-and-paste editing if desired.
|
|
-- The definitions can be further customized if desired by similar editing
|
|
-- prior to compiling carefully observing the following conventions:
|
|
-- + The label preceeding the TRAP-TYPE designator can be edited with some
|
|
-- freedom but the label must be utterly unique among all trap definitions.
|
|
-- + The ENTERPRISE and VARIABLES sections must not be changed.
|
|
-- + The DESCRIPTION can be edited with complete freedom and is typically
|
|
-- ignored within the context of standard SNMP manager trap handling. The
|
|
-- quote mark before and after the text of the description are required.
|
|
-- + The number on the last line of the definition is the actual trap ID
|
|
-- defined and must also be utterly unique.
|
|
--
|
|
-- For example:
|
|
--
|
|
-- dpsRTUp0001Set TRAP-TYPE
|
|
-- ENTERPRISE dpsRTU
|
|
-- VARIABLES { sysDescr, sysLocation, dpsRTUDateTime,
|
|
-- dpsRTUAPort, dpsRTUCAddress, dpsRTUADisplay, dpsRTUAPoint,
|
|
-- dpsRTUAPntDesc, dpsRTUAState }
|
|
-- DESCRIPTION "Generated when granular point 1 is set."
|
|
-- ::= 10001
|
|
--
|
|
-- dpsRTUp0001Clr TRAP-TYPE
|
|
-- ENTERPRISE dpsRTU
|
|
-- VARIABLES { sysDescr, sysLocation, dpsRTUDateTime,
|
|
-- dpsRTUAPort, dpsRTUCAddress, dpsRTUADisplay, dpsRTUAPoint,
|
|
-- dpsRTUAPntDesc, dpsRTUAState }
|
|
-- DESCRIPTION "Generated when granular point 1 clears."
|
|
-- ::= 20001
|
|
--
|
|
-- Could be customized as:
|
|
--
|
|
-- dpsRTUFireAlarm TRAP-TYPE
|
|
-- ENTERPRISE dpsRTU
|
|
-- VARIABLES { sysDescr, sysLocation, dpsRTUDateTime,
|
|
-- dpsRTUAPort, dpsRTUCAddress, dpsRTUADisplay, dpsRTUAPoint,
|
|
-- dpsRTUAPntDesc, dpsRTUAState }
|
|
-- DESCRIPTION "Generated when smoke detector activates."
|
|
-- ::= 10001
|
|
--
|
|
-- dpsRTUFireOut TRAP-TYPE
|
|
-- ENTERPRISE dpsRTU
|
|
-- VARIABLES { sysDescr, sysLocation, dpsRTUDateTime,
|
|
-- dpsRTUAPort, dpsRTUCAddress, dpsRTUADisplay, dpsRTUAPoint,
|
|
-- dpsRTUAPntDesc, dpsRTUAState }
|
|
-- DESCRIPTION "Generated when smoke detector deactivates."
|
|
-- ::= 20001
|
|
-- **************************************************************************
|
|
|
|
|
|
END
|