PDU-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE FROM SNMPv2-SMI
|
|
enterprises, Integer32, IpAddress, Opaque FROM SNMPv2-SMI
|
|
MODULE-COMPLIANCE, OBJECT-GROUP, NOTIFICATION-GROUP FROM SNMPv2-CONF
|
|
TEXTUAL-CONVENTION, DisplayString, MacAddress FROM SNMPv2-TC;
|
|
|
|
eaton MODULE-IDENTITY
|
|
LAST-UPDATED "200803140000Z" -- March 14, 2008
|
|
ORGANIZATION "Eaton Corporation"
|
|
CONTACT-INFO "
|
|
Author: Eaton Corporation
|
|
postal: Eaton Corporation
|
|
Eaton Center
|
|
1111 Superior Avenue
|
|
Cleveland, OH 44114-2584
|
|
phone: +1 (216) 523-5000
|
|
"
|
|
DESCRIPTION "This mib describes the SNMP functions of the
|
|
Power Distribution Unit by Eaton Corporation."
|
|
REVISION "200803140000z"
|
|
DESCRIPTION "Modified MIB in effort to better support HP Openview
|
|
and other SNMP managers."
|
|
|
|
REVISION "200702140000Z"
|
|
DESCRIPTION "Updated version for remote access to pdu."
|
|
::= { enterprises 534 }
|
|
|
|
product OBJECT IDENTIFIER ::= { eaton 6 }
|
|
pduagent OBJECT IDENTIFIER ::= { product 6 }
|
|
pdu OBJECT IDENTIFIER ::= { pduagent 6 }
|
|
|
|
traps OBJECT IDENTIFIER ::= { pdu 0 }
|
|
board OBJECT IDENTIFIER ::= { pdu 1 }
|
|
environmental OBJECT IDENTIFIER ::= { pdu 2 }
|
|
conformance OBJECT IDENTIFIER ::= { pdu 9 }
|
|
info OBJECT IDENTIFIER ::= { board 1 }
|
|
outlets OBJECT IDENTIFIER ::= { board 2 }
|
|
unit OBJECT IDENTIFIER ::= { board 3 }
|
|
|
|
unitReadings OBJECT IDENTIFIER ::= { unit 1 }
|
|
|
|
compliances OBJECT IDENTIFIER ::= { conformance 1 }
|
|
groups OBJECT IDENTIFIER ::= { conformance 2 }
|
|
|
|
-- Conformance Information
|
|
|
|
compliance MODULE-COMPLIANCE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The requirements for conformance to the PDU-MIB."
|
|
MODULE -- this module
|
|
|
|
GROUP infoGroup
|
|
DESCRIPTION
|
|
"The info group."
|
|
|
|
GROUP outletsGroup
|
|
DESCRIPTION
|
|
"The outlets group."
|
|
|
|
GROUP unitSensorsGroup
|
|
DESCRIPTION
|
|
"The unit sensor readings association group."
|
|
|
|
GROUP externalTemperatureGroup
|
|
DESCRIPTION
|
|
"The external temperature sensor association group."
|
|
|
|
GROUP externalHumidityGroup
|
|
DESCRIPTION
|
|
"The external humidity sensor association group."
|
|
|
|
GROUP trapsGroup
|
|
DESCRIPTION
|
|
"The traps group."
|
|
::= { compliances 1 }
|
|
|
|
infoGroup OBJECT-GROUP
|
|
OBJECTS { firmwareVersion,
|
|
serialNumber,
|
|
ipAddress,
|
|
netmask,
|
|
gateway,
|
|
mac,
|
|
hardwareRev,
|
|
userName,
|
|
objectName,
|
|
objectInstance,
|
|
targetUser,
|
|
groupName,
|
|
imageVersion,
|
|
sensorDescr,
|
|
thresholdDescr,
|
|
thresholdSeverity,
|
|
thresholdEventType,
|
|
status,
|
|
slaveIpAddress }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A collection of objects providing basic information
|
|
about the pdu."
|
|
::= { groups 1 }
|
|
|
|
outletsGroup OBJECT-GROUP
|
|
OBJECTS { outletCount,
|
|
outletLabel,
|
|
outletOperationalState,
|
|
outletCurrent,
|
|
outletMaxCurrent,
|
|
outletVoltage,
|
|
outletActivePower,
|
|
outletApparentPower,
|
|
outletPowerFactor,
|
|
outletCurrentUpperWarning,
|
|
outletCurrentUpperCritical }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A collection of objects providing basic information
|
|
about the outlets, including sensor readings."
|
|
::= { groups 2 }
|
|
|
|
unitSensorsGroup OBJECT-GROUP
|
|
OBJECTS { unitCurrent,
|
|
unitVoltage,
|
|
unitActivePower,
|
|
unitApparentPower,
|
|
unitCpuTemp,
|
|
unitCircuitBreak0State,
|
|
unitCircuitBreak1State,
|
|
unitCircuitBreak2State,
|
|
unitCircuitBreak0Current,
|
|
unitCircuitBreak1Current,
|
|
unitCircuitBreak2Current,
|
|
unitVoltageLowerWarning,
|
|
unitVoltageUpperWarning,
|
|
unitVoltageLowerCritical,
|
|
unitVoltageUpperCritical,
|
|
unitCurrentUpperWarning,
|
|
unitCurrentUpperCritical,
|
|
unitTempLowerWarning,
|
|
unitTempUpperWarning,
|
|
unitTempLowerCritical,
|
|
unitTempUpperCritical }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A collection of objects providing unit level sensor readings."
|
|
::= { groups 4 }
|
|
|
|
externalTemperatureGroup OBJECT-GROUP
|
|
OBJECTS { tempSensorCount,
|
|
tempSensorLabel,
|
|
temperature,
|
|
tempLowerWarning,
|
|
tempUpperWarning,
|
|
tempLowerCritical,
|
|
tempUpperCritical,
|
|
tempLowerWarningReset,
|
|
tempUpperWarningReset,
|
|
tempLowerCriticalReset,
|
|
tempUpperCriticalReset }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A collection of objects providing external temperature sensor readings and threshold settings."
|
|
::= { groups 6 }
|
|
|
|
externalHumidityGroup OBJECT-GROUP
|
|
OBJECTS { humiditySensorCount,
|
|
humiditySensorLabel,
|
|
humidity,
|
|
humidityLowerWarning,
|
|
humidityUpperWarning,
|
|
humidityLowerCritical,
|
|
humidityUpperCritical,
|
|
humidityLowerWarningReset,
|
|
humidityUpperWarningReset,
|
|
humidityLowerCriticalReset,
|
|
humidityUpperCriticalReset }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A collection of objects providing external humidity sensor readings and threshold settings."
|
|
::= { groups 7 }
|
|
|
|
trapsGroup NOTIFICATION-GROUP
|
|
NOTIFICATIONS { rebootStarted,
|
|
rebootCompleted,
|
|
userLogin,
|
|
userLogout,
|
|
userAuthenticationFailure,
|
|
userSessionTimeout,
|
|
userAdded,
|
|
userModified,
|
|
userDeleted,
|
|
groupAdded,
|
|
groupModified,
|
|
groupDeleted,
|
|
deviceUpdateStarted,
|
|
userBlocked,
|
|
powerControl,
|
|
userPasswordChanged,
|
|
passwordSettingsChanged,
|
|
firmwareFileDiscarded,
|
|
firmwareValidationFailed,
|
|
securityViolation,
|
|
logFileCleared,
|
|
thresholdAlarm,
|
|
outletGroupingConnectivityLost }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A collection of traps."
|
|
::= { groups 9 }
|
|
|
|
|
|
-- Textual Conventions
|
|
|
|
MilliAmps ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Data type for reporting sensor readings and thresholds
|
|
associated with current sensors. If the underlying hardware
|
|
sensor indicates 1 amp, then the SNMP agent will report
|
|
a value of 1000 milliamps. The value is scaled in this
|
|
manner as a way to deal with floating point types
|
|
that SNMP does not currently support."
|
|
SYNTAX Unsigned32
|
|
|
|
MilliVolts ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Data type for reporting sensor readings and thresholds
|
|
associated with voltage sensors. If the underlying hardware
|
|
sensor indicates 1 volts, then the SNMP agent will report
|
|
a value of 1000 millivolts. The value is scaled in this
|
|
manner as a way to deal with floating point types
|
|
that SNMP does not currently support."
|
|
SYNTAX Unsigned32
|
|
|
|
Watts ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Data type for reporting sensor readings and thresholds
|
|
associated with active power sensors. If the underlying hardware
|
|
sensor indicates 1 watt, then the SNMP agent will report
|
|
a value of 1 watt. No scaling is performed for this type."
|
|
SYNTAX Unsigned32
|
|
|
|
VoltAmps ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Data type for reporting sensor readings and thresholds
|
|
associated with apparent power sensors. If the underlying hardware
|
|
sensor indicates 1 volt-amp, then the SNMP agent will report
|
|
a value of 1 volt-amp. No scaling is performed for this type."
|
|
SYNTAX Unsigned32
|
|
|
|
DegreesCelsius ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Data type for reporting sensor readings and thresholds
|
|
associated with temperature sensors. If the underlying hardware
|
|
sensor indicates 1 degree Celsius, then the SNMP agent will report
|
|
a value of 1 degree Celsius. No scaling is performed for this type."
|
|
SYNTAX Unsigned32
|
|
|
|
Hertz ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Data type for reporting sensor readings and thresholds
|
|
associated with frequency sensors. If the underlying hardware
|
|
sensor indicates 1 Hertz, then the SNMP agent will report
|
|
a value of 1 Hertz. No scaling is performed for this type."
|
|
SYNTAX Unsigned32
|
|
|
|
RelativeHumidity ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Data type for reporting sensor readings and thresholds
|
|
associated with humidity sensors. Relative humidity is
|
|
expressed as percentage and is defined as the ratio of the
|
|
partial pressure of water vapor in a gaseous mixture of
|
|
air and water vapor to the saturated vapor pressure of water
|
|
at a given temperature."
|
|
SYNTAX Unsigned32 (0..100)
|
|
|
|
PowerFactorPercentage ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Data type for reporting sensor readings and thresholds
|
|
associated with power factor sensors. The power factor of
|
|
an AC power system is defined as the ratio of the real
|
|
or active power to the apparent power and is a number
|
|
between 0 and 1. A PowerFactorPercentage value is calculated
|
|
by taking this ratio and multiplying by 100. The power factor
|
|
is used to indicate how efficiently a particular load is
|
|
utilizing energy."
|
|
SYNTAX Unsigned32 (0..100)
|
|
|
|
SensorTypeEnumeration ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The types a sensor can be."
|
|
SYNTAX INTEGER { outletCurrent(0),
|
|
outletMaxCurrent(1),
|
|
outletVoltage(2),
|
|
outletActivePower(3),
|
|
outletApparentPower(4),
|
|
outletMaxActivePower(5),
|
|
outletAverageActivePower(6),
|
|
outletPowerFactor(7),
|
|
powerBranchVoltage(200),
|
|
powerBranchFrequency(201),
|
|
powerBranchTemperature(202),
|
|
powerBranchCurrent(203),
|
|
environmentalTemp1(300),
|
|
environmentalTemp2(301),
|
|
environmentalTemp3(302),
|
|
environmentalTemp4(303),
|
|
environmentalTemp5(304),
|
|
environmentalTemp6(305),
|
|
environmentalTemp7(306),
|
|
environmentalTemp8(307),
|
|
environmentalHumidity1(400),
|
|
environmentalHumidity2(401),
|
|
environmentalHumidity3(402),
|
|
environmentalHumidity4(403),
|
|
environmentalHumidity5(404),
|
|
environmentalHumidity6(405),
|
|
environmentalHumidity7(406),
|
|
environmentalHumidity8(407),
|
|
unitRmsCurrent(500),
|
|
unitMaxRmsCurrent(501),
|
|
unitVoltage(502),
|
|
unitCpuTemp(503),
|
|
unitActivePower(504),
|
|
unitApparentPower(505),
|
|
unitCircuitBreak0State(550),
|
|
unitCircuitBreak1State(551),
|
|
unitCircuitBreak2State(552),
|
|
unitCircuitBreak0Current(600),
|
|
unitCircuitBreak1Current(601),
|
|
unitCircuitBreak2Current(602) }
|
|
|
|
SensorStateEnumeration ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The states a sensor can be in."
|
|
SYNTAX INTEGER { unavailable(-1),
|
|
ok(0),
|
|
belowLowerWarning(1),
|
|
aboveUpperWarning(2),
|
|
belowLowerCritical(3),
|
|
aboveUpperCritical(4) }
|
|
|
|
|
|
-- the info group
|
|
|
|
firmwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current firmware version"
|
|
::= { info 1 }
|
|
|
|
serialNumber OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The serial number."
|
|
::= { info 2 }
|
|
|
|
ipAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current IP address. A value of 0.0.0.0 indicates an error
|
|
or an unset option."
|
|
::= { info 3 }
|
|
|
|
netmask OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current Netmask. A value of 0.0.0.0 indicates an error
|
|
or an unset option."
|
|
::= { info 4 }
|
|
|
|
gateway OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current Gateway. A value of 0.0.0.0 indicates an error
|
|
or an unset option."
|
|
::= { info 5 }
|
|
|
|
mac OBJECT-TYPE
|
|
SYNTAX MacAddress
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current MAC address."
|
|
::= { info 6 }
|
|
|
|
hardwareRev OBJECT-TYPE
|
|
SYNTAX Integer32(0..255)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The hardware revision number."
|
|
::= { info 7 }
|
|
|
|
userName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The login of a user."
|
|
::= { info 10 }
|
|
|
|
objectName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The model type of the device"
|
|
::= { info 12 }
|
|
|
|
objectInstance OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The device name"
|
|
::= { info 13}
|
|
|
|
targetUser OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The user record being operated on"
|
|
::= { info 14}
|
|
|
|
groupName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The group record being operated on"
|
|
::= { info 15 }
|
|
|
|
imageVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The version of the Upgrade image"
|
|
::= { info 18 }
|
|
|
|
sensorDescr OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sensor description indicating which sensor experienced a threshold exceeded
|
|
event. When applicable the description will indicate the sensor number."
|
|
::= { info 19 }
|
|
|
|
thresholdDescr OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Threshold description indicating which configured threshold has been triggered (or cleared)."
|
|
::= { info 20 }
|
|
|
|
thresholdSeverity OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"String (Warning, Critical, etc...) indicating the severity of the threshold which has been triggered (or cleared)."
|
|
::= { info 21 }
|
|
|
|
thresholdEventType OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"String (triggered, cleared) indicating if the threshold event indicates that a configured threshold
|
|
has been triggered or cleared."
|
|
::= { info 22 }
|
|
|
|
status OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The success status of an operation"
|
|
::= { info 23 }
|
|
|
|
slaveIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"In a shepherding configuration, this is the IP address of slave PDU. A value of 0.0.0.0 indicates an error
|
|
or an unset option."
|
|
::= { info 24}
|
|
|
|
-- the outlets group
|
|
|
|
-- Implementation for managing the outlets
|
|
|
|
outletCount OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of outlets (regardless of
|
|
their current state) present on this pdu."
|
|
::= { outlets 1 }
|
|
|
|
|
|
-- the outlets table
|
|
|
|
-- The outlets table contains information on the pdu's outlets.
|
|
-- It further provides functions for managing them.
|
|
|
|
outletTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF OutletEntryStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of outlet entries. The number of
|
|
entries is given by the value of outletCount."
|
|
::= { outlets 2 }
|
|
|
|
outletEntry OBJECT-TYPE
|
|
SYNTAX OutletEntryStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An outlet entry containing objects at the
|
|
for a particular outlet."
|
|
INDEX { outletIndex }
|
|
::= { outletTable 1 }
|
|
|
|
OutletEntryStruct ::= SEQUENCE { outletIndex Integer32,
|
|
outletLabel DisplayString,
|
|
outletOperationalState INTEGER,
|
|
outletCurrent MilliAmps,
|
|
outletMaxCurrent MilliAmps,
|
|
outletVoltage MilliVolts,
|
|
outletActivePower Watts,
|
|
outletApparentPower VoltAmps,
|
|
outletPowerFactor PowerFactorPercentage,
|
|
outletCurrentUpperWarning MilliAmps,
|
|
outletCurrentUpperCritical MilliAmps }
|
|
|
|
outletIndex OBJECT-TYPE
|
|
SYNTAX Integer32(0..255)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value for each outlet. Its value
|
|
ranges between 1 and the value of outletCount."
|
|
::= { outletEntry 1 }
|
|
|
|
outletLabel OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A textual string containing information
|
|
about the outlet."
|
|
::= { outletEntry 2 }
|
|
|
|
outletOperationalState OBJECT-TYPE
|
|
SYNTAX INTEGER { error(-1),
|
|
off(0),
|
|
on(1),
|
|
cycling(2) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A value for each outlet which describes the
|
|
operational state of the outlet. It is also
|
|
used to set the operational state of the outlet"
|
|
::= { outletEntry 3 }
|
|
|
|
outletCurrent OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value for the current sensor
|
|
attached to the outlet. This value is
|
|
reported in milliamps (1/1000th of an amp)"
|
|
::= { outletEntry 4 }
|
|
|
|
outletMaxCurrent OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value for the max. current sensor
|
|
attached to the outlet. This value is
|
|
reported in milliamps (1/1000th of an amp)"
|
|
::= { outletEntry 5 }
|
|
|
|
outletVoltage OBJECT-TYPE
|
|
SYNTAX MilliVolts
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value for the voltage sensor
|
|
attached to the outlet.This value is
|
|
reported in millivolts (1/1000th of a volt)"
|
|
::= { outletEntry 6 }
|
|
|
|
outletActivePower OBJECT-TYPE
|
|
SYNTAX Watts
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value for the active power sensor
|
|
attached to the outlet. This value is
|
|
reported in Watts."
|
|
::= { outletEntry 7 }
|
|
|
|
outletApparentPower OBJECT-TYPE
|
|
SYNTAX VoltAmps
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value for the apparent power sensor
|
|
attached to the outlet. This value is
|
|
reported in Volt-Amps"
|
|
::= { outletEntry 8 }
|
|
|
|
outletPowerFactor OBJECT-TYPE
|
|
SYNTAX PowerFactorPercentage
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value for the power factor
|
|
of the outlet. The reading represents a
|
|
percentage in the range of 0% to 100%."
|
|
::= { outletEntry 9 }
|
|
|
|
outletCurrentUpperWarning OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the upper warning (non-critical)
|
|
current threshold for the outlet. This value is
|
|
reported in milliamps (1/1000th of an amp)"
|
|
::= { outletEntry 21 }
|
|
|
|
outletCurrentUpperCritical OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the upper critical current
|
|
threshold for the outlet. This value is
|
|
reported in milliamps (1/1000th of an amp)"
|
|
::= { outletEntry 23 }
|
|
|
|
|
|
|
|
-- the unitReadings group
|
|
|
|
-- The unitReadings group contains sensor reading values
|
|
-- for the PDU unit as a whole
|
|
|
|
unitCurrent OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value for the unit's current sensor in millamps."
|
|
::= { unitReadings 1 }
|
|
|
|
unitVoltage OBJECT-TYPE
|
|
SYNTAX MilliVolts
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value for the unit's voltage sensor in millivolts."
|
|
::= { unitReadings 2 }
|
|
|
|
unitActivePower OBJECT-TYPE
|
|
SYNTAX Watts
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value for the unit's voltage sensor in volt-amps."
|
|
::= { unitReadings 3 }
|
|
|
|
unitApparentPower OBJECT-TYPE
|
|
SYNTAX Watts
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value for the unit's voltage sensor in volt-amps."
|
|
::= { unitReadings 4 }
|
|
|
|
unitCpuTemp OBJECT-TYPE
|
|
SYNTAX DegreesCelsius
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value for the unit's CPU temperature sensor in degrees Celsius."
|
|
::= { unitReadings 5 }
|
|
|
|
|
|
unitCircuitBreak0State OBJECT-TYPE
|
|
SYNTAX INTEGER { unavailable(-1),
|
|
ok(0),
|
|
tripped(1) }
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value for the unit's circuit breaker state sensor 0."
|
|
::= { unitReadings 20 }
|
|
|
|
unitCircuitBreak1State OBJECT-TYPE
|
|
SYNTAX INTEGER { unavailable(-1),
|
|
ok(0),
|
|
tripped(1) }
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value for the unit's circuit breaker state sensor 1."
|
|
::= { unitReadings 21 }
|
|
|
|
unitCircuitBreak2State OBJECT-TYPE
|
|
SYNTAX INTEGER { unavailable(-1),
|
|
ok(0),
|
|
tripped(1) }
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value for the unit's circuit breaker state sensor 2."
|
|
::= { unitReadings 22 }
|
|
|
|
unitCircuitBreak0Current OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value for the unit's circuit breaker current sensor 0."
|
|
::= { unitReadings 40 }
|
|
|
|
unitCircuitBreak1Current OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value for the unit's circuit breaker current sensor 1."
|
|
::= { unitReadings 41 }
|
|
|
|
unitCircuitBreak2Current OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value for the unit's circuit breaker current sensor 2."
|
|
::= { unitReadings 42 }
|
|
|
|
unitVoltageLowerWarning OBJECT-TYPE
|
|
SYNTAX MilliVolts
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the lower warning (non-critical) unit level voltage threshold."
|
|
::= { unitReadings 60 }
|
|
|
|
unitVoltageLowerCritical OBJECT-TYPE
|
|
SYNTAX MilliVolts
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the lower critical unit level voltage threshold."
|
|
::= { unitReadings 61 }
|
|
|
|
unitVoltageUpperWarning OBJECT-TYPE
|
|
SYNTAX MilliVolts
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the upper warning (non-critical) unit level voltage threshold."
|
|
::= { unitReadings 62 }
|
|
|
|
unitVoltageUpperCritical OBJECT-TYPE
|
|
SYNTAX MilliVolts
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the upper critical unit level voltage threshold."
|
|
::= { unitReadings 63 }
|
|
|
|
unitCurrentUpperWarning OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the upper warning (non-critical) unit level current threshold."
|
|
::= { unitReadings 70 }
|
|
|
|
unitCurrentUpperCritical OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the upper critical unit level current threshold. NOTE: This
|
|
particular threshold is NOT settable "
|
|
::= { unitReadings 71 }
|
|
|
|
unitTempLowerWarning OBJECT-TYPE
|
|
SYNTAX DegreesCelsius
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the lower warning (non-critical) unit level temperature threshold."
|
|
::= { unitReadings 80 }
|
|
|
|
unitTempLowerCritical OBJECT-TYPE
|
|
SYNTAX DegreesCelsius
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the lower critical unit level temperature threshold."
|
|
::= { unitReadings 81 }
|
|
|
|
unitTempUpperWarning OBJECT-TYPE
|
|
SYNTAX DegreesCelsius
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the upper warning (non-critical) unit level temperature threshold."
|
|
::= { unitReadings 82 }
|
|
|
|
unitTempUpperCritical OBJECT-TYPE
|
|
SYNTAX DegreesCelsius
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the upper critical unit level temperature threshold."
|
|
::= { unitReadings 83 }
|
|
|
|
|
|
-- the externalTemperature group
|
|
|
|
-- Implementation for managing external temperature sensors
|
|
|
|
tempSensorCount OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of external temperature sensors (regardless of
|
|
their current state) present on this pdu."
|
|
::= { environmental 1 }
|
|
|
|
|
|
-- the temperature sensors table
|
|
|
|
-- The tempSensorTable table contains information on the pdu's external temperature sensors.
|
|
|
|
tempSensorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF TempSensorEntryStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of temperature sensor entries. The number of
|
|
entries is given by the value of tempSensorCount."
|
|
::= { environmental 2 }
|
|
|
|
tempSensorEntry OBJECT-TYPE
|
|
SYNTAX TempSensorEntryStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing sensor reading and threshold
|
|
settings for a particular temperature sensor."
|
|
INDEX { tempSensorIndex }
|
|
::= { tempSensorTable 1 }
|
|
|
|
TempSensorEntryStruct ::= SEQUENCE { tempSensorIndex Integer32,
|
|
tempSensorLabel DisplayString,
|
|
temperature DegreesCelsius,
|
|
tempLowerWarning DegreesCelsius,
|
|
tempUpperWarning DegreesCelsius,
|
|
tempLowerCritical DegreesCelsius,
|
|
tempUpperCritical DegreesCelsius,
|
|
tempLowerWarningReset DegreesCelsius,
|
|
tempUpperWarningReset DegreesCelsius,
|
|
tempLowerCriticalReset DegreesCelsius,
|
|
tempUpperCriticalReset DegreesCelsius }
|
|
|
|
tempSensorIndex OBJECT-TYPE
|
|
SYNTAX Integer32(0..255)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value for each temperature sensor. Its value
|
|
ranges between 1 and tempSensorCount."
|
|
::= { tempSensorEntry 1 }
|
|
|
|
tempSensorLabel OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A settable human-readable label for the external temperature
|
|
sensor. One possible use for this label is to convey sensor
|
|
location."
|
|
::= { tempSensorEntry 2 }
|
|
|
|
temperature OBJECT-TYPE
|
|
SYNTAX DegreesCelsius
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the external temperature sensor reported
|
|
in degrees celsius."
|
|
::= { tempSensorEntry 3 }
|
|
|
|
tempLowerWarning OBJECT-TYPE
|
|
SYNTAX DegreesCelsius
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the lower warning (non-critical) threshold."
|
|
::= { tempSensorEntry 4 }
|
|
|
|
tempUpperWarning OBJECT-TYPE
|
|
SYNTAX DegreesCelsius
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the upper warning (non-critical) threshold."
|
|
::= { tempSensorEntry 5 }
|
|
|
|
tempLowerCritical OBJECT-TYPE
|
|
SYNTAX DegreesCelsius
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the lower critical threshold."
|
|
::= { tempSensorEntry 6 }
|
|
|
|
tempUpperCritical OBJECT-TYPE
|
|
SYNTAX DegreesCelsius
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the upper critical threshold."
|
|
::= { tempSensorEntry 7 }
|
|
|
|
tempLowerWarningReset OBJECT-TYPE
|
|
SYNTAX DegreesCelsius
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the lower warning (non-critical) reset/hysteresis value."
|
|
::= { tempSensorEntry 8 }
|
|
|
|
tempUpperWarningReset OBJECT-TYPE
|
|
SYNTAX DegreesCelsius
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the upper warning (non-critical) reset/hysteresis value."
|
|
::= { tempSensorEntry 9 }
|
|
|
|
tempLowerCriticalReset OBJECT-TYPE
|
|
SYNTAX DegreesCelsius
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the lower critical reset/hysteresis value."
|
|
::= { tempSensorEntry 10 }
|
|
|
|
tempUpperCriticalReset OBJECT-TYPE
|
|
SYNTAX DegreesCelsius
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the upper critical reset/hysteresis value."
|
|
::= { tempSensorEntry 11 }
|
|
|
|
-- the externalHumidity group
|
|
|
|
-- Implementation for managing external humidity sensors
|
|
|
|
humiditySensorCount OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of external humidity sensors (regardless of
|
|
their current state) present on this pdu."
|
|
::= { environmental 3 }
|
|
|
|
|
|
-- the humidity sensors table
|
|
|
|
-- The humiditySensorTable table contains information on the pdu's external humidity sensors.
|
|
|
|
humiditySensorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF HumiditySensorEntryStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of humidity sensor entries. The number of
|
|
entries is given by the value of humiditySensorCount."
|
|
::= { environmental 4 }
|
|
|
|
humiditySensorEntry OBJECT-TYPE
|
|
SYNTAX HumiditySensorEntryStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing sensor reading and threshold
|
|
settings for a particular humidity sensor."
|
|
INDEX { humiditySensorIndex }
|
|
::= { humiditySensorTable 1 }
|
|
|
|
HumiditySensorEntryStruct ::= SEQUENCE { humiditySensorIndex Integer32,
|
|
humiditySensorLabel DisplayString,
|
|
humidity RelativeHumidity,
|
|
humidityLowerWarning RelativeHumidity,
|
|
humidityUpperWarning RelativeHumidity,
|
|
humidityLowerCritical RelativeHumidity,
|
|
humidityUpperCritical RelativeHumidity,
|
|
humidityLowerWarningReset RelativeHumidity,
|
|
humidityUpperWarningReset RelativeHumidity,
|
|
humidityLowerCriticalReset RelativeHumidity,
|
|
humidityUpperCriticalReset RelativeHumidity }
|
|
|
|
humiditySensorIndex OBJECT-TYPE
|
|
SYNTAX Integer32(0..255)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value for each humidity sensor. Its value
|
|
ranges between 1 and humiditySensorCount."
|
|
::= { humiditySensorEntry 1 }
|
|
|
|
humiditySensorLabel OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A settable human-readable label for the external humidity
|
|
sensor. One possible use for this label is to convey sensor
|
|
location."
|
|
::= { humiditySensorEntry 2 }
|
|
|
|
humidity OBJECT-TYPE
|
|
SYNTAX RelativeHumidity
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the external humidity sensor reported
|
|
as relative humidity (a percentage)."
|
|
::= { humiditySensorEntry 3 }
|
|
|
|
humidityLowerWarning OBJECT-TYPE
|
|
SYNTAX RelativeHumidity
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the lower warning (non-critical) threshold."
|
|
::= { humiditySensorEntry 4 }
|
|
|
|
humidityUpperWarning OBJECT-TYPE
|
|
SYNTAX RelativeHumidity
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the upper warning (non-critical) threshold."
|
|
::= { humiditySensorEntry 5 }
|
|
|
|
humidityLowerCritical OBJECT-TYPE
|
|
SYNTAX RelativeHumidity
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the lower critical threshold."
|
|
::= { humiditySensorEntry 6 }
|
|
|
|
humidityUpperCritical OBJECT-TYPE
|
|
SYNTAX RelativeHumidity
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the upper critical threshold."
|
|
::= { humiditySensorEntry 7 }
|
|
|
|
humidityLowerWarningReset OBJECT-TYPE
|
|
SYNTAX RelativeHumidity
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the lower warning (non-critical) reset/hysteresis value."
|
|
::= { humiditySensorEntry 8 }
|
|
|
|
humidityUpperWarningReset OBJECT-TYPE
|
|
SYNTAX RelativeHumidity
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the upper warning (non-critical) reset/hysteresis value."
|
|
::= { humiditySensorEntry 9 }
|
|
|
|
humidityLowerCriticalReset OBJECT-TYPE
|
|
SYNTAX RelativeHumidity
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the lower critical reset/hysteresis value."
|
|
::= { humiditySensorEntry 10 }
|
|
|
|
humidityUpperCriticalReset OBJECT-TYPE
|
|
SYNTAX RelativeHumidity
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the upper critical reset/hysteresis value."
|
|
::= { humiditySensorEntry 11 }
|
|
|
|
|
|
-- Start the traps
|
|
|
|
rebootStarted NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The reboot process has started"
|
|
::= { traps 1 }
|
|
|
|
rebootCompleted NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The reboot process is complete"
|
|
::= { traps 2 }
|
|
|
|
userLogin NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName,
|
|
ipAddress }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A user logged in"
|
|
::= { traps 3 }
|
|
|
|
userLogout NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName,
|
|
ipAddress }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A user logged out"
|
|
::= { traps 4 }
|
|
|
|
userAuthenticationFailure NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName,
|
|
ipAddress }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A user authentication attempt failed"
|
|
::= { traps 5 }
|
|
|
|
userSessionTimeout NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName,
|
|
ipAddress }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A user timed out from the device"
|
|
::= { traps 8 }
|
|
|
|
userAdded NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName,
|
|
targetUser }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A user was added to the system"
|
|
::= { traps 11 }
|
|
|
|
userModified NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName,
|
|
targetUser }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A user account was modified"
|
|
::= { traps 12 }
|
|
|
|
userDeleted NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName,
|
|
targetUser }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A user was deleted from the system"
|
|
::= { traps 13 }
|
|
|
|
groupAdded NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName,
|
|
groupName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A group was added to the system"
|
|
::= { traps 14 }
|
|
|
|
groupModified NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName,
|
|
groupName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A group was modified"
|
|
::= { traps 15 }
|
|
|
|
|
|
groupDeleted NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName,
|
|
groupName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A group was deleted from the system"
|
|
::= { traps 16 }
|
|
|
|
deviceUpdateStarted NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName,
|
|
ipAddress,
|
|
imageVersion }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The device update has started"
|
|
::= { traps 20 }
|
|
|
|
userBlocked NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName,
|
|
ipAddress }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A blocked user tried to log in"
|
|
::= { traps 22 }
|
|
|
|
powerControl NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName,
|
|
ipAddress,
|
|
outletLabel,
|
|
outletOperationalState }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An outlet has been switched"
|
|
::= { traps 23 }
|
|
|
|
userPasswordChanged NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName,
|
|
targetUser,
|
|
ipAddress }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A user password was changed"
|
|
::= { traps 24 }
|
|
|
|
passwordSettingsChanged NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName,
|
|
status }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Strong password settings changed "
|
|
::= { traps 28 }
|
|
|
|
-- Start new event to support RP products
|
|
|
|
firmwareFileDiscarded NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A firmware file discarded "
|
|
::= { traps 36 }
|
|
|
|
firmwareValidationFailed NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A firmware validation failed "
|
|
::= { traps 38 }
|
|
|
|
securityViolation NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName,
|
|
ipAddress }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Security violation."
|
|
::= { traps 39 }
|
|
|
|
logFileCleared NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The log file has been cleared."
|
|
::= { traps 41 }
|
|
|
|
--sensor threshold exceeded traps
|
|
|
|
thresholdAlarm NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
ipAddress,
|
|
sensorDescr,
|
|
thresholdDescr,
|
|
thresholdSeverity,
|
|
thresholdEventType }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Configured sensor theshold event. The 'thresholdType' variable will indicate whether or not
|
|
the threshold triggered or cleared"
|
|
::= { traps 45 }
|
|
|
|
-- Shepherd Application traps
|
|
outletGroupingConnectivityLost NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
ipAddress,
|
|
slaveIpAddress }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Master PDU lost contact with the slave PDU in an outlet grouping configuration."
|
|
::= { traps 50 }
|
|
|
|
|
|
END
|