PDU-MIB DEFINITIONS ::= BEGIN
IMPORTS
MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE FROM SNMPv2-SMI
enterprises, Integer32, IpAddress, Opaque FROM SNMPv2-SMI
MODULE-COMPLIANCE, OBJECT-GROUP, NOTIFICATION-GROUP FROM SNMPv2-CONF
TEXTUAL-CONVENTION, DisplayString, MacAddress FROM SNMPv2-TC;
eaton MODULE-IDENTITY
LAST-UPDATED "200803140000Z" -- March 14, 2008
ORGANIZATION "Eaton Corporation"
CONTACT-INFO "
Author: Eaton Corporation
postal: Eaton Corporation
Eaton Center
1111 Superior Avenue
Cleveland, OH 44114-2584
phone: +1 (216) 523-5000
"
DESCRIPTION "This mib describes the SNMP functions of the
Power Distribution Unit by Eaton Corporation."
REVISION "200803140000z"
DESCRIPTION "Modified MIB in effort to better support HP Openview
and other SNMP managers."
REVISION "200702140000Z"
DESCRIPTION "Updated version for remote access to pdu."
::= { enterprises 534 }
product OBJECT IDENTIFIER ::= { eaton 6 }
pduagent OBJECT IDENTIFIER ::= { product 6 }
pdu OBJECT IDENTIFIER ::= { pduagent 6 }
traps OBJECT IDENTIFIER ::= { pdu 0 }
board OBJECT IDENTIFIER ::= { pdu 1 }
environmental OBJECT IDENTIFIER ::= { pdu 2 }
conformance OBJECT IDENTIFIER ::= { pdu 9 }
info OBJECT IDENTIFIER ::= { board 1 }
outlets OBJECT IDENTIFIER ::= { board 2 }
unit OBJECT IDENTIFIER ::= { board 3 }
unitReadings OBJECT IDENTIFIER ::= { unit 1 }
compliances OBJECT IDENTIFIER ::= { conformance 1 }
groups OBJECT IDENTIFIER ::= { conformance 2 }
-- Conformance Information
compliance MODULE-COMPLIANCE
STATUS current
DESCRIPTION
"The requirements for conformance to the PDU-MIB."
MODULE -- this module
GROUP infoGroup
DESCRIPTION
"The info group."
GROUP outletsGroup
DESCRIPTION
"The outlets group."
GROUP unitSensorsGroup
DESCRIPTION
"The unit sensor readings association group."
GROUP externalTemperatureGroup
DESCRIPTION
"The external temperature sensor association group."
GROUP externalHumidityGroup
DESCRIPTION
"The external humidity sensor association group."
GROUP trapsGroup
DESCRIPTION
"The traps group."
::= { compliances 1 }
infoGroup OBJECT-GROUP
OBJECTS { firmwareVersion,
serialNumber,
ipAddress,
netmask,
gateway,
mac,
hardwareRev,
userName,
objectName,
objectInstance,
targetUser,
groupName,
imageVersion,
sensorDescr,
thresholdDescr,
thresholdSeverity,
thresholdEventType,
status,
slaveIpAddress }
STATUS current
DESCRIPTION
"A collection of objects providing basic information
about the pdu."
::= { groups 1 }
outletsGroup OBJECT-GROUP
OBJECTS { outletCount,
outletLabel,
outletOperationalState,
outletCurrent,
outletMaxCurrent,
outletVoltage,
outletActivePower,
outletApparentPower,
outletPowerFactor,
outletCurrentUpperWarning,
outletCurrentUpperCritical }
STATUS current
DESCRIPTION
"A collection of objects providing basic information
about the outlets, including sensor readings."
::= { groups 2 }
unitSensorsGroup OBJECT-GROUP
OBJECTS { unitCurrent,
unitVoltage,
unitActivePower,
unitApparentPower,
unitCpuTemp,
unitCircuitBreak0State,
unitCircuitBreak1State,
unitCircuitBreak2State,
unitCircuitBreak0Current,
unitCircuitBreak1Current,
unitCircuitBreak2Current,
unitVoltageLowerWarning,
unitVoltageUpperWarning,
unitVoltageLowerCritical,
unitVoltageUpperCritical,
unitCurrentUpperWarning,
unitCurrentUpperCritical,
unitTempLowerWarning,
unitTempUpperWarning,
unitTempLowerCritical,
unitTempUpperCritical }
STATUS current
DESCRIPTION
"A collection of objects providing unit level sensor readings."
::= { groups 4 }
externalTemperatureGroup OBJECT-GROUP
OBJECTS { tempSensorCount,
tempSensorLabel,
temperature,
tempLowerWarning,
tempUpperWarning,
tempLowerCritical,
tempUpperCritical,
tempLowerWarningReset,
tempUpperWarningReset,
tempLowerCriticalReset,
tempUpperCriticalReset }
STATUS current
DESCRIPTION
"A collection of objects providing external temperature sensor readings and threshold settings."
::= { groups 6 }
externalHumidityGroup OBJECT-GROUP
OBJECTS { humiditySensorCount,
humiditySensorLabel,
humidity,
humidityLowerWarning,
humidityUpperWarning,
humidityLowerCritical,
humidityUpperCritical,
humidityLowerWarningReset,
humidityUpperWarningReset,
humidityLowerCriticalReset,
humidityUpperCriticalReset }
STATUS current
DESCRIPTION
"A collection of objects providing external humidity sensor readings and threshold settings."
::= { groups 7 }
trapsGroup NOTIFICATION-GROUP
NOTIFICATIONS { rebootStarted,
rebootCompleted,
userLogin,
userLogout,
userAuthenticationFailure,
userSessionTimeout,
userAdded,
userModified,
userDeleted,
groupAdded,
groupModified,
groupDeleted,
deviceUpdateStarted,
userBlocked,
powerControl,
userPasswordChanged,
passwordSettingsChanged,
firmwareFileDiscarded,
firmwareValidationFailed,
securityViolation,
logFileCleared,
thresholdAlarm,
outletGroupingConnectivityLost }
STATUS current
DESCRIPTION
"A collection of traps."
::= { groups 9 }
-- Textual Conventions
MilliAmps ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Data type for reporting sensor readings and thresholds
associated with current sensors. If the underlying hardware
sensor indicates 1 amp, then the SNMP agent will report
a value of 1000 milliamps. The value is scaled in this
manner as a way to deal with floating point types
that SNMP does not currently support."
SYNTAX Unsigned32
MilliVolts ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Data type for reporting sensor readings and thresholds
associated with voltage sensors. If the underlying hardware
sensor indicates 1 volts, then the SNMP agent will report
a value of 1000 millivolts. The value is scaled in this
manner as a way to deal with floating point types
that SNMP does not currently support."
SYNTAX Unsigned32
Watts ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Data type for reporting sensor readings and thresholds
associated with active power sensors. If the underlying hardware
sensor indicates 1 watt, then the SNMP agent will report
a value of 1 watt. No scaling is performed for this type."
SYNTAX Unsigned32
VoltAmps ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Data type for reporting sensor readings and thresholds
associated with apparent power sensors. If the underlying hardware
sensor indicates 1 volt-amp, then the SNMP agent will report
a value of 1 volt-amp. No scaling is performed for this type."
SYNTAX Unsigned32
DegreesCelsius ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Data type for reporting sensor readings and thresholds
associated with temperature sensors. If the underlying hardware
sensor indicates 1 degree Celsius, then the SNMP agent will report
a value of 1 degree Celsius. No scaling is performed for this type."
SYNTAX Unsigned32
Hertz ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Data type for reporting sensor readings and thresholds
associated with frequency sensors. If the underlying hardware
sensor indicates 1 Hertz, then the SNMP agent will report
a value of 1 Hertz. No scaling is performed for this type."
SYNTAX Unsigned32
RelativeHumidity ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Data type for reporting sensor readings and thresholds
associated with humidity sensors. Relative humidity is
expressed as percentage and is defined as the ratio of the
partial pressure of water vapor in a gaseous mixture of
air and water vapor to the saturated vapor pressure of water
at a given temperature."
SYNTAX Unsigned32 (0..100)
PowerFactorPercentage ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Data type for reporting sensor readings and thresholds
associated with power factor sensors. The power factor of
an AC power system is defined as the ratio of the real
or active power to the apparent power and is a number
between 0 and 1. A PowerFactorPercentage value is calculated
by taking this ratio and multiplying by 100. The power factor
is used to indicate how efficiently a particular load is
utilizing energy."
SYNTAX Unsigned32 (0..100)
SensorTypeEnumeration ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"The types a sensor can be."
SYNTAX INTEGER { outletCurrent(0),
outletMaxCurrent(1),
outletVoltage(2),
outletActivePower(3),
outletApparentPower(4),
outletMaxActivePower(5),
outletAverageActivePower(6),
outletPowerFactor(7),
powerBranchVoltage(200),
powerBranchFrequency(201),
powerBranchTemperature(202),
powerBranchCurrent(203),
environmentalTemp1(300),
environmentalTemp2(301),
environmentalTemp3(302),
environmentalTemp4(303),
environmentalTemp5(304),
environmentalTemp6(305),
environmentalTemp7(306),
environmentalTemp8(307),
environmentalHumidity1(400),
environmentalHumidity2(401),
environmentalHumidity3(402),
environmentalHumidity4(403),
environmentalHumidity5(404),
environmentalHumidity6(405),
environmentalHumidity7(406),
environmentalHumidity8(407),
unitRmsCurrent(500),
unitMaxRmsCurrent(501),
unitVoltage(502),
unitCpuTemp(503),
unitActivePower(504),
unitApparentPower(505),
unitCircuitBreak0State(550),
unitCircuitBreak1State(551),
unitCircuitBreak2State(552),
unitCircuitBreak0Current(600),
unitCircuitBreak1Current(601),
unitCircuitBreak2Current(602) }
SensorStateEnumeration ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"The states a sensor can be in."
SYNTAX INTEGER { unavailable(-1),
ok(0),
belowLowerWarning(1),
aboveUpperWarning(2),
belowLowerCritical(3),
aboveUpperCritical(4) }
-- the info group
firmwareVersion OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current firmware version"
::= { info 1 }
serialNumber OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The serial number."
::= { info 2 }
ipAddress OBJECT-TYPE
SYNTAX IpAddress
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current IP address. A value of 0.0.0.0 indicates an error
or an unset option."
::= { info 3 }
netmask OBJECT-TYPE
SYNTAX IpAddress
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current Netmask. A value of 0.0.0.0 indicates an error
or an unset option."
::= { info 4 }
gateway OBJECT-TYPE
SYNTAX IpAddress
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current Gateway. A value of 0.0.0.0 indicates an error
or an unset option."
::= { info 5 }
mac OBJECT-TYPE
SYNTAX MacAddress
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current MAC address."
::= { info 6 }
hardwareRev OBJECT-TYPE
SYNTAX Integer32(0..255)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The hardware revision number."
::= { info 7 }
userName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"The login of a user."
::= { info 10 }
objectName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"The model type of the device"
::= { info 12 }
objectInstance OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"The device name"
::= { info 13}
targetUser OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"The user record being operated on"
::= { info 14}
groupName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"The group record being operated on"
::= { info 15 }
imageVersion OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"The version of the Upgrade image"
::= { info 18 }
sensorDescr OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"Sensor description indicating which sensor experienced a threshold exceeded
event. When applicable the description will indicate the sensor number."
::= { info 19 }
thresholdDescr OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"Threshold description indicating which configured threshold has been triggered (or cleared)."
::= { info 20 }
thresholdSeverity OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"String (Warning, Critical, etc...) indicating the severity of the threshold which has been triggered (or cleared)."
::= { info 21 }
thresholdEventType OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"String (triggered, cleared) indicating if the threshold event indicates that a configured threshold
has been triggered or cleared."
::= { info 22 }
status OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"The success status of an operation"
::= { info 23 }
slaveIpAddress OBJECT-TYPE
SYNTAX IpAddress
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"In a shepherding configuration, this is the IP address of slave PDU. A value of 0.0.0.0 indicates an error
or an unset option."
::= { info 24}
-- the outlets group
-- Implementation for managing the outlets
outletCount OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of outlets (regardless of
their current state) present on this pdu."
::= { outlets 1 }
-- the outlets table
-- The outlets table contains information on the pdu's outlets.
-- It further provides functions for managing them.
outletTable OBJECT-TYPE
SYNTAX SEQUENCE OF OutletEntryStruct
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of outlet entries. The number of
entries is given by the value of outletCount."
::= { outlets 2 }
outletEntry OBJECT-TYPE
SYNTAX OutletEntryStruct
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An outlet entry containing objects at the
for a particular outlet."
INDEX { outletIndex }
::= { outletTable 1 }
OutletEntryStruct ::= SEQUENCE { outletIndex Integer32,
outletLabel DisplayString,
outletOperationalState INTEGER,
outletCurrent MilliAmps,
outletMaxCurrent MilliAmps,
outletVoltage MilliVolts,
outletActivePower Watts,
outletApparentPower VoltAmps,
outletPowerFactor PowerFactorPercentage,
outletCurrentUpperWarning MilliAmps,
outletCurrentUpperCritical MilliAmps }
outletIndex OBJECT-TYPE
SYNTAX Integer32(0..255)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A unique value for each outlet. Its value
ranges between 1 and the value of outletCount."
::= { outletEntry 1 }
outletLabel OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A textual string containing information
about the outlet."
::= { outletEntry 2 }
outletOperationalState OBJECT-TYPE
SYNTAX INTEGER { error(-1),
off(0),
on(1),
cycling(2) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A value for each outlet which describes the
operational state of the outlet. It is also
used to set the operational state of the outlet"
::= { outletEntry 3 }
outletCurrent OBJECT-TYPE
SYNTAX MilliAmps
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A unique value for the current sensor
attached to the outlet. This value is
reported in milliamps (1/1000th of an amp)"
::= { outletEntry 4 }
outletMaxCurrent OBJECT-TYPE
SYNTAX MilliAmps
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A unique value for the max. current sensor
attached to the outlet. This value is
reported in milliamps (1/1000th of an amp)"
::= { outletEntry 5 }
outletVoltage OBJECT-TYPE
SYNTAX MilliVolts
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A unique value for the voltage sensor
attached to the outlet.This value is
reported in millivolts (1/1000th of a volt)"
::= { outletEntry 6 }
outletActivePower OBJECT-TYPE
SYNTAX Watts
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A unique value for the active power sensor
attached to the outlet. This value is
reported in Watts."
::= { outletEntry 7 }
outletApparentPower OBJECT-TYPE
SYNTAX VoltAmps
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A unique value for the apparent power sensor
attached to the outlet. This value is
reported in Volt-Amps"
::= { outletEntry 8 }
outletPowerFactor OBJECT-TYPE
SYNTAX PowerFactorPercentage
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A unique value for the power factor
of the outlet. The reading represents a
percentage in the range of 0% to 100%."
::= { outletEntry 9 }
outletCurrentUpperWarning OBJECT-TYPE
SYNTAX MilliAmps
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value of the upper warning (non-critical)
current threshold for the outlet. This value is
reported in milliamps (1/1000th of an amp)"
::= { outletEntry 21 }
outletCurrentUpperCritical OBJECT-TYPE
SYNTAX MilliAmps
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value of the upper critical current
threshold for the outlet. This value is
reported in milliamps (1/1000th of an amp)"
::= { outletEntry 23 }
-- the unitReadings group
-- The unitReadings group contains sensor reading values
-- for the PDU unit as a whole
unitCurrent OBJECT-TYPE
SYNTAX MilliAmps
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The value for the unit's current sensor in millamps."
::= { unitReadings 1 }
unitVoltage OBJECT-TYPE
SYNTAX MilliVolts
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The value for the unit's voltage sensor in millivolts."
::= { unitReadings 2 }
unitActivePower OBJECT-TYPE
SYNTAX Watts
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The value for the unit's voltage sensor in volt-amps."
::= { unitReadings 3 }
unitApparentPower OBJECT-TYPE
SYNTAX Watts
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The value for the unit's voltage sensor in volt-amps."
::= { unitReadings 4 }
unitCpuTemp OBJECT-TYPE
SYNTAX DegreesCelsius
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The value for the unit's CPU temperature sensor in degrees Celsius."
::= { unitReadings 5 }
unitCircuitBreak0State OBJECT-TYPE
SYNTAX INTEGER { unavailable(-1),
ok(0),
tripped(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The value for the unit's circuit breaker state sensor 0."
::= { unitReadings 20 }
unitCircuitBreak1State OBJECT-TYPE
SYNTAX INTEGER { unavailable(-1),
ok(0),
tripped(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The value for the unit's circuit breaker state sensor 1."
::= { unitReadings 21 }
unitCircuitBreak2State OBJECT-TYPE
SYNTAX INTEGER { unavailable(-1),
ok(0),
tripped(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The value for the unit's circuit breaker state sensor 2."
::= { unitReadings 22 }
unitCircuitBreak0Current OBJECT-TYPE
SYNTAX MilliAmps
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The value for the unit's circuit breaker current sensor 0."
::= { unitReadings 40 }
unitCircuitBreak1Current OBJECT-TYPE
SYNTAX MilliAmps
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The value for the unit's circuit breaker current sensor 1."
::= { unitReadings 41 }
unitCircuitBreak2Current OBJECT-TYPE
SYNTAX MilliAmps
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The value for the unit's circuit breaker current sensor 2."
::= { unitReadings 42 }
unitVoltageLowerWarning OBJECT-TYPE
SYNTAX MilliVolts
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value of the lower warning (non-critical) unit level voltage threshold."
::= { unitReadings 60 }
unitVoltageLowerCritical OBJECT-TYPE
SYNTAX MilliVolts
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value of the lower critical unit level voltage threshold."
::= { unitReadings 61 }
unitVoltageUpperWarning OBJECT-TYPE
SYNTAX MilliVolts
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value of the upper warning (non-critical) unit level voltage threshold."
::= { unitReadings 62 }
unitVoltageUpperCritical OBJECT-TYPE
SYNTAX MilliVolts
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value of the upper critical unit level voltage threshold."
::= { unitReadings 63 }
unitCurrentUpperWarning OBJECT-TYPE
SYNTAX MilliAmps
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value of the upper warning (non-critical) unit level current threshold."
::= { unitReadings 70 }
unitCurrentUpperCritical OBJECT-TYPE
SYNTAX MilliAmps
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The value of the upper critical unit level current threshold. NOTE: This
particular threshold is NOT settable "
::= { unitReadings 71 }
unitTempLowerWarning OBJECT-TYPE
SYNTAX DegreesCelsius
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value of the lower warning (non-critical) unit level temperature threshold."
::= { unitReadings 80 }
unitTempLowerCritical OBJECT-TYPE
SYNTAX DegreesCelsius
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value of the lower critical unit level temperature threshold."
::= { unitReadings 81 }
unitTempUpperWarning OBJECT-TYPE
SYNTAX DegreesCelsius
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value of the upper warning (non-critical) unit level temperature threshold."
::= { unitReadings 82 }
unitTempUpperCritical OBJECT-TYPE
SYNTAX DegreesCelsius
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value of the upper critical unit level temperature threshold."
::= { unitReadings 83 }
-- the externalTemperature group
-- Implementation for managing external temperature sensors
tempSensorCount OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of external temperature sensors (regardless of
their current state) present on this pdu."
::= { environmental 1 }
-- the temperature sensors table
-- The tempSensorTable table contains information on the pdu's external temperature sensors.
tempSensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF TempSensorEntryStruct
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of temperature sensor entries. The number of
entries is given by the value of tempSensorCount."
::= { environmental 2 }
tempSensorEntry OBJECT-TYPE
SYNTAX TempSensorEntryStruct
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing sensor reading and threshold
settings for a particular temperature sensor."
INDEX { tempSensorIndex }
::= { tempSensorTable 1 }
TempSensorEntryStruct ::= SEQUENCE { tempSensorIndex Integer32,
tempSensorLabel DisplayString,
temperature DegreesCelsius,
tempLowerWarning DegreesCelsius,
tempUpperWarning DegreesCelsius,
tempLowerCritical DegreesCelsius,
tempUpperCritical DegreesCelsius,
tempLowerWarningReset DegreesCelsius,
tempUpperWarningReset DegreesCelsius,
tempLowerCriticalReset DegreesCelsius,
tempUpperCriticalReset DegreesCelsius }
tempSensorIndex OBJECT-TYPE
SYNTAX Integer32(0..255)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A unique value for each temperature sensor. Its value
ranges between 1 and tempSensorCount."
::= { tempSensorEntry 1 }
tempSensorLabel OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A settable human-readable label for the external temperature
sensor. One possible use for this label is to convey sensor
location."
::= { tempSensorEntry 2 }
temperature OBJECT-TYPE
SYNTAX DegreesCelsius
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The value of the external temperature sensor reported
in degrees celsius."
::= { tempSensorEntry 3 }
tempLowerWarning OBJECT-TYPE
SYNTAX DegreesCelsius
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value of the lower warning (non-critical) threshold."
::= { tempSensorEntry 4 }
tempUpperWarning OBJECT-TYPE
SYNTAX DegreesCelsius
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value of the upper warning (non-critical) threshold."
::= { tempSensorEntry 5 }
tempLowerCritical OBJECT-TYPE
SYNTAX DegreesCelsius
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value of the lower critical threshold."
::= { tempSensorEntry 6 }
tempUpperCritical OBJECT-TYPE
SYNTAX DegreesCelsius
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value of the upper critical threshold."
::= { tempSensorEntry 7 }
tempLowerWarningReset OBJECT-TYPE
SYNTAX DegreesCelsius
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value of the lower warning (non-critical) reset/hysteresis value."
::= { tempSensorEntry 8 }
tempUpperWarningReset OBJECT-TYPE
SYNTAX DegreesCelsius
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value of the upper warning (non-critical) reset/hysteresis value."
::= { tempSensorEntry 9 }
tempLowerCriticalReset OBJECT-TYPE
SYNTAX DegreesCelsius
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value of the lower critical reset/hysteresis value."
::= { tempSensorEntry 10 }
tempUpperCriticalReset OBJECT-TYPE
SYNTAX DegreesCelsius
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value of the upper critical reset/hysteresis value."
::= { tempSensorEntry 11 }
-- the externalHumidity group
-- Implementation for managing external humidity sensors
humiditySensorCount OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of external humidity sensors (regardless of
their current state) present on this pdu."
::= { environmental 3 }
-- the humidity sensors table
-- The humiditySensorTable table contains information on the pdu's external humidity sensors.
humiditySensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF HumiditySensorEntryStruct
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of humidity sensor entries. The number of
entries is given by the value of humiditySensorCount."
::= { environmental 4 }
humiditySensorEntry OBJECT-TYPE
SYNTAX HumiditySensorEntryStruct
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing sensor reading and threshold
settings for a particular humidity sensor."
INDEX { humiditySensorIndex }
::= { humiditySensorTable 1 }
HumiditySensorEntryStruct ::= SEQUENCE { humiditySensorIndex Integer32,
humiditySensorLabel DisplayString,
humidity RelativeHumidity,
humidityLowerWarning RelativeHumidity,
humidityUpperWarning RelativeHumidity,
humidityLowerCritical RelativeHumidity,
humidityUpperCritical RelativeHumidity,
humidityLowerWarningReset RelativeHumidity,
humidityUpperWarningReset RelativeHumidity,
humidityLowerCriticalReset RelativeHumidity,
humidityUpperCriticalReset RelativeHumidity }
humiditySensorIndex OBJECT-TYPE
SYNTAX Integer32(0..255)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A unique value for each humidity sensor. Its value
ranges between 1 and humiditySensorCount."
::= { humiditySensorEntry 1 }
humiditySensorLabel OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A settable human-readable label for the external humidity
sensor. One possible use for this label is to convey sensor
location."
::= { humiditySensorEntry 2 }
humidity OBJECT-TYPE
SYNTAX RelativeHumidity
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The value of the external humidity sensor reported
as relative humidity (a percentage)."
::= { humiditySensorEntry 3 }
humidityLowerWarning OBJECT-TYPE
SYNTAX RelativeHumidity
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value of the lower warning (non-critical) threshold."
::= { humiditySensorEntry 4 }
humidityUpperWarning OBJECT-TYPE
SYNTAX RelativeHumidity
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value of the upper warning (non-critical) threshold."
::= { humiditySensorEntry 5 }
humidityLowerCritical OBJECT-TYPE
SYNTAX RelativeHumidity
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value of the lower critical threshold."
::= { humiditySensorEntry 6 }
humidityUpperCritical OBJECT-TYPE
SYNTAX RelativeHumidity
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value of the upper critical threshold."
::= { humiditySensorEntry 7 }
humidityLowerWarningReset OBJECT-TYPE
SYNTAX RelativeHumidity
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value of the lower warning (non-critical) reset/hysteresis value."
::= { humiditySensorEntry 8 }
humidityUpperWarningReset OBJECT-TYPE
SYNTAX RelativeHumidity
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value of the upper warning (non-critical) reset/hysteresis value."
::= { humiditySensorEntry 9 }
humidityLowerCriticalReset OBJECT-TYPE
SYNTAX RelativeHumidity
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value of the lower critical reset/hysteresis value."
::= { humiditySensorEntry 10 }
humidityUpperCriticalReset OBJECT-TYPE
SYNTAX RelativeHumidity
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value of the upper critical reset/hysteresis value."
::= { humiditySensorEntry 11 }
-- Start the traps
rebootStarted NOTIFICATION-TYPE
OBJECTS { objectName,
objectInstance,
userName }
STATUS current
DESCRIPTION
"The reboot process has started"
::= { traps 1 }
rebootCompleted NOTIFICATION-TYPE
OBJECTS { objectName,
objectInstance }
STATUS current
DESCRIPTION
"The reboot process is complete"
::= { traps 2 }
userLogin NOTIFICATION-TYPE
OBJECTS { objectName,
objectInstance,
userName,
ipAddress }
STATUS current
DESCRIPTION
"A user logged in"
::= { traps 3 }
userLogout NOTIFICATION-TYPE
OBJECTS { objectName,
objectInstance,
userName,
ipAddress }
STATUS current
DESCRIPTION
"A user logged out"
::= { traps 4 }
userAuthenticationFailure NOTIFICATION-TYPE
OBJECTS { objectName,
objectInstance,
userName,
ipAddress }
STATUS current
DESCRIPTION
"A user authentication attempt failed"
::= { traps 5 }
userSessionTimeout NOTIFICATION-TYPE
OBJECTS { objectName,
objectInstance,
userName,
ipAddress }
STATUS current
DESCRIPTION
"A user timed out from the device"
::= { traps 8 }
userAdded NOTIFICATION-TYPE
OBJECTS { objectName,
objectInstance,
userName,
targetUser }
STATUS current
DESCRIPTION
"A user was added to the system"
::= { traps 11 }
userModified NOTIFICATION-TYPE
OBJECTS { objectName,
objectInstance,
userName,
targetUser }
STATUS current
DESCRIPTION
"A user account was modified"
::= { traps 12 }
userDeleted NOTIFICATION-TYPE
OBJECTS { objectName,
objectInstance,
userName,
targetUser }
STATUS current
DESCRIPTION
"A user was deleted from the system"
::= { traps 13 }
groupAdded NOTIFICATION-TYPE
OBJECTS { objectName,
objectInstance,
userName,
groupName }
STATUS current
DESCRIPTION
"A group was added to the system"
::= { traps 14 }
groupModified NOTIFICATION-TYPE
OBJECTS { objectName,
objectInstance,
userName,
groupName }
STATUS current
DESCRIPTION
"A group was modified"
::= { traps 15 }
groupDeleted NOTIFICATION-TYPE
OBJECTS { objectName,
objectInstance,
userName,
groupName }
STATUS current
DESCRIPTION
"A group was deleted from the system"
::= { traps 16 }
deviceUpdateStarted NOTIFICATION-TYPE
OBJECTS { objectName,
objectInstance,
userName,
ipAddress,
imageVersion }
STATUS current
DESCRIPTION
"The device update has started"
::= { traps 20 }
userBlocked NOTIFICATION-TYPE
OBJECTS { objectName,
objectInstance,
userName,
ipAddress }
STATUS current
DESCRIPTION
"A blocked user tried to log in"
::= { traps 22 }
powerControl NOTIFICATION-TYPE
OBJECTS { objectName,
objectInstance,
userName,
ipAddress,
outletLabel,
outletOperationalState }
STATUS current
DESCRIPTION
"An outlet has been switched"
::= { traps 23 }
userPasswordChanged NOTIFICATION-TYPE
OBJECTS { objectName,
objectInstance,
userName,
targetUser,
ipAddress }
STATUS current
DESCRIPTION
"A user password was changed"
::= { traps 24 }
passwordSettingsChanged NOTIFICATION-TYPE
OBJECTS { objectName,
objectInstance,
userName,
status }
STATUS current
DESCRIPTION
"Strong password settings changed "
::= { traps 28 }
-- Start new event to support RP products
firmwareFileDiscarded NOTIFICATION-TYPE
OBJECTS { objectName,
objectInstance,
userName }
STATUS current
DESCRIPTION
"A firmware file discarded "
::= { traps 36 }
firmwareValidationFailed NOTIFICATION-TYPE
OBJECTS { objectName,
objectInstance,
userName }
STATUS current
DESCRIPTION
"A firmware validation failed "
::= { traps 38 }
securityViolation NOTIFICATION-TYPE
OBJECTS { objectName,
objectInstance,
userName,
ipAddress }
STATUS current
DESCRIPTION
"Security violation."
::= { traps 39 }
logFileCleared NOTIFICATION-TYPE
OBJECTS { objectName,
objectInstance,
userName }
STATUS current
DESCRIPTION
"The log file has been cleared."
::= { traps 41 }
--sensor threshold exceeded traps
thresholdAlarm NOTIFICATION-TYPE
OBJECTS { objectName,
objectInstance,
ipAddress,
sensorDescr,
thresholdDescr,
thresholdSeverity,
thresholdEventType }
STATUS current
DESCRIPTION
"Configured sensor theshold event. The 'thresholdType' variable will indicate whether or not
the threshold triggered or cleared"
::= { traps 45 }
-- Shepherd Application traps
outletGroupingConnectivityLost NOTIFICATION-TYPE
OBJECTS { objectName,
objectInstance,
ipAddress,
slaveIpAddress }
STATUS current
DESCRIPTION
"Master PDU lost contact with the slave PDU in an outlet grouping configuration."
::= { traps 50 }
END