3580 lines
105 KiB
Plaintext
3580 lines
105 KiB
Plaintext
-- ============================================================================
|
||
-- Copyright (C)2013 by HUAWEI TECHNOLOGIES. All rights reserved.
|
||
-- Description: This MIB is used for defining Power Monitor management
|
||
-- MIB objects.
|
||
-- Reference:
|
||
-- Version: V3.35
|
||
-- ============================================================================
|
||
HUAWEI-POWER-MIB DEFINITIONS ::= BEGIN
|
||
|
||
IMPORTS
|
||
hwEnvEmuIndex,hwEnvEmuType,hwDigChannelIndex
|
||
FROM HUAWEI-ENVIRONMENT-MIB
|
||
huaweiUtility
|
||
FROM HUAWEI-MIB
|
||
Integer32, OBJECT-TYPE, MODULE-IDENTITY, NOTIFICATION-TYPE
|
||
FROM SNMPv2-SMI
|
||
DisplayString, RowStatus, TruthValue, DateAndTime, TEXTUAL-CONVENTION
|
||
FROM SNMPv2-TC
|
||
hwFrameIndex
|
||
FROM HUAWEI-DEVICE-MIB;
|
||
|
||
hwPower MODULE-IDENTITY
|
||
LAST-UPDATED "201312280000Z"
|
||
ORGANIZATION "Huawei Technologies Co.,Ltd."
|
||
CONTACT-INFO
|
||
"Huawei Industrial Base
|
||
Bantian, Longgang
|
||
Shenzhen 518129
|
||
People's Republic of China
|
||
Website: http://www.huawei.com
|
||
Email: support@huawei.com
|
||
"
|
||
DESCRIPTION
|
||
"
|
||
This MIB is used for defining Power Monitor management MIB objects.
|
||
"
|
||
|
||
-- Revision history
|
||
REVISION "201312280000Z"
|
||
DESCRIPTION "V3.35, modify the leaf of hwRectifierOperState."
|
||
|
||
REVISION "201311160000Z"
|
||
DESCRIPTION "V3.34, modify the leaf of hwRectifierOperState."
|
||
|
||
REVISION "201212280000Z"
|
||
DESCRIPTION "V3.33, added enumerate etp48150(128) in hwPowerType leaf for smu EMU,
|
||
added enumerate h801pmu(127) in hwPowerType leaf for H801PMU."
|
||
|
||
REVISION "201212140000Z"
|
||
DESCRIPTION "V3.32, add the leaf of hwBatteryLogTestBatteryTemperature, hwBatteryLogTestBatteryCurrent
|
||
and hwBatteryGroupBomCode for battery smart manage.
|
||
add enumerate sleep(6) in hwChargeOperStatus leaf.
|
||
add enumerate supplyRecoverAutotestTerminated(7) in hwBatteryTestResult leaf."
|
||
|
||
REVISION "201207240000Z"
|
||
DESCRIPTION "V3.31, add the leaf of hwPowerModuleRestoreTrap and hwPowerModuleMismatchTrap for SMU digital alarm."
|
||
|
||
REVISION "201206250000Z"
|
||
DESCRIPTION "V3.30, add enumerate smu(124) in hwPowerType leaf for smu EMU,
|
||
modified the name of hwBatteryTestPrealarmThreshold to hwBatteryTestAlarmThreshold,
|
||
modified description of hwBatteryTestDuration,hwBatteryTestTerminateVoltage and hwBatteryTestAlarmThreshold,
|
||
delete enumerate smu(124),
|
||
add enumerate etp4830(125) and enumerate etp4890(126) in hwPowerType leaf for smu EMU"
|
||
|
||
REVISION "201201090000Z"
|
||
DESCRIPTION "V3.29, add the leafs of hwEmmBatt1TempFaultTrap, hwEmmBatt1TempRestoreTrap, hwEmmEnviHumFaultTrap,
|
||
hwEmmEnviHumRestoreTrap, hwEmmEnvi1TempFaultTrap, hwEmmEnvi1TempRestoreTrap, hwEmmBattTemFaultTrap,
|
||
hwEmmBattTemRecoverTrap and hwEmmPowerBatteryOffRecoverTrap"
|
||
|
||
REVISION "201112170000Z"
|
||
DESCRIPTION "V3.28, added hwBatteryLogTestEfficiency the objects of hwEmmPowerBattaryTestStopTrap.
|
||
add the leaf of hwEmmPowerBatteryUnDetectTrap and ch_hwEmmPowerBatteryDetectRecoverTrap for SMU digital alarm."
|
||
|
||
REVISION "201112080000Z"
|
||
DESCRIPTION "V3.27, added hwBatteryTestPrealarmThreshold leaf node for getting and setting battery test prealarm threshold.
|
||
added hwBatteryLogTestEfficiency leaf node for inquiry efficiency setting. "
|
||
|
||
REVISION "201108170000Z"
|
||
DESCRIPTION "V3.25, add the leaf of hwEmmPowerBatteryOffTrap for battary power-off."
|
||
|
||
REVISION "201103160000Z"
|
||
DESCRIPTION "V3.25, added enumerate discharge(5) in hwChargeOperStatus leaf for discharge.
|
||
add enumerate LiFeBattery(123) in hwPowerType leaf for LiFeBattery EMU"
|
||
|
||
REVISION "201012170000Z"
|
||
DESCRIPTION "V3.24, added Objects hwBatteryLogTestBatteryStatus of hwEmmPowerBattaryTestStopTrap node."
|
||
|
||
REVISION "201011100000Z"
|
||
DESCRIPTION "V3.23, added enumerate power3000(122) in hwPowerType leaf for Power3000 EMU.
|
||
Modified the objects of hwEmmPowerBattloopFaultTrap and hwEmmPowerBattloopRecoverTrap.
|
||
Added hwEmmDigMainsupplyFaultTrap and hwEmmDigMainsupplyRecoverTrap."
|
||
|
||
REVISION "201007180900Z"
|
||
DESCRIPTION "V3.22, added enumerate power3000(122) in hwPowerType leaf for Power3000 EMU.
|
||
Modified the objects of hwEmmPowerBattloopFaultTrap and hwEmmPowerBattloopRecoverTrap.
|
||
Added hwEmmDigMainsupplyFaultTrap and hwEmmDigMainsupplyRecoverTrap."
|
||
|
||
REVISION "201006120900Z"
|
||
DESCRIPTION "V3.21, modified description of hwBatteryGroupOperStatus node."
|
||
|
||
REVISION "201004210900Z"
|
||
DESCRIPTION "V3.20, modified node name to avoid conflict."
|
||
|
||
REVISION "201004080900Z"
|
||
DESCRIPTION "V3.19, modified this MIB for clearing simple tester errors and warnings."
|
||
|
||
REVISION "201003090900Z"
|
||
DESCRIPTION "V3.18, added hwBatteryInstallTime leaf node for getting the battery installation time"
|
||
|
||
REVISION "201002060900Z"
|
||
DESCRIPTION "V3.17,Modified the description."
|
||
|
||
REVISION "201001290900Z"
|
||
DESCRIPTION "V3.16,Deleted simple tester MIB compile errors and warnings."
|
||
|
||
REVISION "200611100900Z"
|
||
DESCRIPTION "V3.09,Added hwBatteryHardwareState."
|
||
|
||
REVISION "200610250900Z"
|
||
DESCRIPTION "V3.08,Added hwBatteryVoltageState."
|
||
|
||
::= { huaweiUtility 2 }
|
||
|
||
|
||
MeasuresRange ::= TEXTUAL-CONVENTION
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Basic unit of measure:
|
||
1.pressure:indicated by mV, 1V = 1000 mV
|
||
2.current:indicated by mA, 1A = 1000 mA
|
||
3.temperature: indicated by 1% degree centigrade
|
||
"
|
||
SYNTAX Integer32
|
||
|
||
|
||
|
||
hwPowerMonObjects OBJECT IDENTIFIER ::= { hwPower 1 }
|
||
hwPowerSysInfoTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwPowerSysInfoEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Power basic information table. The indexes of this table are hwEnvEmuIndex
|
||
and hwPowerIndex. hwEnvEmuIndex comes from hwEnvironmentInfoTable and is
|
||
the index of the monitoring unit. hwPowerIndex is the index of the power
|
||
supply monitored by the monitoring unit.
|
||
"
|
||
::= { hwPowerMonObjects 1 }
|
||
|
||
hwPowerSysInfoEntry OBJECT-TYPE
|
||
SYNTAX HwPowerSysInfoEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Power basic information table. The indexes of this entry are hwEnvEmuIndex
|
||
and hwPowerIndex. hwEnvEmuIndex comes from hwEnvironmentInfoTable and is
|
||
the index of the monitoring unit. hwPowerIndex is the index of the power
|
||
supply monitored by the monitoring unit.
|
||
"
|
||
INDEX { hwEnvEmuIndex, hwPowerIndex }
|
||
::= { hwPowerSysInfoTable 1 }
|
||
|
||
HwPowerSysInfoEntry ::=
|
||
SEQUENCE {
|
||
hwPowerIndex
|
||
Integer32,
|
||
hwPowerType
|
||
INTEGER,
|
||
hwPowerName
|
||
DisplayString,
|
||
hwPowerState
|
||
INTEGER,
|
||
hwPowerRowStatus
|
||
RowStatus,
|
||
hwPowerControlMode
|
||
INTEGER,
|
||
hwPowerRemoteFrameID
|
||
Integer32,
|
||
hwPowerProtect
|
||
INTEGER,
|
||
hwPowerVersion
|
||
DisplayString,
|
||
hwPowerSupplyState
|
||
INTEGER
|
||
}
|
||
|
||
hwPowerIndex OBJECT-TYPE
|
||
SYNTAX Integer32 (0..255)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Index of the power supply monitored by the monitoring unit"
|
||
::= { hwPowerSysInfoEntry 1 }
|
||
|
||
hwPowerType OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
power4875(1),
|
||
power4810(2),
|
||
power48100(3),
|
||
power4850(4),
|
||
power48240(5),
|
||
power48120(6),
|
||
power48300(7),
|
||
power48240SinglePhase(8),
|
||
universalPower(9),
|
||
power4845(10),
|
||
rpower(11),
|
||
power4805(15),
|
||
power4820(16),
|
||
onps(17),
|
||
power4875l(18),
|
||
psma(100),
|
||
perm-al175nt(101),
|
||
mcs1800(102),
|
||
mcs1800A(103),
|
||
mcs3000(104),
|
||
sm40sm60(105),
|
||
scu(106),
|
||
eltek(107),
|
||
dk04(108),
|
||
dk04C(109),
|
||
dpc(110),
|
||
power4830(120),
|
||
h831pmua(121),
|
||
power3000(122),
|
||
liFeBattery(123),
|
||
etp4830(125),
|
||
etp4890(126),
|
||
h801pmu(127),
|
||
etp48150(128),
|
||
other(255)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Type of the Power emu device.
|
||
Options:
|
||
1.power4875(1) - Type of the Power emu device is power4875
|
||
2.power4810(2) - Type of the Power emu device is power4810
|
||
3.power48100(3) - Type of the Power emu device is power48100
|
||
4.power4850(4) - Type of the Power emu device is power4850
|
||
5.power48240(5) - Type of the Power emu device is power48240
|
||
6.power48120(6) - Type of the Power emu device is power48120
|
||
7.power48300(7) - Type of the Power emu device is power48300
|
||
8.power48240SinglePhase(8) - Type of the Power emu device is power48240SinglePhase
|
||
9.universalPower(9) - Type of the Power emu device is universalPower
|
||
10.power4845(10) - Type of the Power emu device is power4845
|
||
11.rpower(11) - Type of the Power emu device is rpower
|
||
12.power4805(15) - Type of the Power emu device is power4805
|
||
13.power4820(16) - Type of the Power emu device is power4820
|
||
14.onps(17) - Type of the Power emu device is onps
|
||
15.power4875l(18) - Type of the Power emu device is power4875l
|
||
16.psma(100) - Type of the Power emu device is psma
|
||
17.perm-al175nt(101) - Type of the Power emu device is perm-al175nt
|
||
18.mcs1800(102) - Type of the Power emu device is mcs1800
|
||
19.mcs1800A(103) - Type of the Power emu device is mcs1800A
|
||
20.mcs3000(104) - Type of the Power emu device is mcs3000
|
||
21.sm40sm60(105) - Type of the Power emu device is sm40sm60
|
||
22.scu(106) - Type of the Power emu device is scu
|
||
23.eltek(107) - Type of the Power emu device is eltek
|
||
24.dk04(108) - Type of the Power emu device is dk04
|
||
25.dk04C(109) - Type of the Power emu device is dk04C
|
||
26.dpc(110) - Type of the Power emu device is dpc
|
||
27.power4830(120) - Type of the Power emu device is power4830
|
||
28.h831pmua(121) - Type of the Power emu device is h831pmua
|
||
29.power3000(122) - Type of the Power emu device is power3000
|
||
30.liFeBattery(123) - Type of the Power emu device is LiFeBattery
|
||
31.etp4830(125), - Type of SMU Power emu device is etp4830
|
||
32.etp4890(126), - Type of SMU Power emu device is etp4890
|
||
33.h801pmu(127), - Type of the Power emu device is h801pmua
|
||
34.etp48150(128), - Type of SMU Power emu device is etp48150
|
||
35.other(255) - other Power Type
|
||
"
|
||
::= { hwPowerSysInfoEntry 2 }
|
||
|
||
hwPowerName OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"
|
||
Power name.
|
||
"
|
||
::= { hwPowerSysInfoEntry 3 }
|
||
|
||
hwPowerState OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
fault(2),
|
||
protecting(3),
|
||
switched(4),
|
||
invalid(-1)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Power board status:
|
||
Refers to the status of communication between the internal monitor board
|
||
of the power device and the external upper board.
|
||
Options:
|
||
1.normal(1) - indicates the normal state
|
||
2.fault(2) - indicates the faulty state
|
||
3.protecting(3)- indicates that the backup power supply works in the protection state
|
||
4.switched(4) - indicates that the main power supply is faulty, and is protected by backup power supply
|
||
5.invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
|
||
"
|
||
::= { hwPowerSysInfoEntry 4 }
|
||
|
||
hwPowerRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus standard operation. The values 1 and 2 are supported currently.
|
||
1 indicates the activation status, and 2 indicates the non-activation status."
|
||
::= { hwPowerSysInfoEntry 5 }
|
||
|
||
hwPowerControlMode OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
manualControl(1),
|
||
autoControl(2),
|
||
invalid(-1)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Control mode of the power monitor module.
|
||
Options:
|
||
1.manualControl(1) - control by manual, the remote mode
|
||
2.autoControl(2) - auto control mode, the default is auto control mode
|
||
3.invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
|
||
"
|
||
DEFVAL { 1 }
|
||
::= { hwPowerSysInfoEntry 6 }
|
||
|
||
hwPowerRemoteFrameID OBJECT-TYPE
|
||
SYNTAX Integer32 (0..255)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Apply for remote power system.
|
||
It is the frame ID that the remote unit exists in"
|
||
::= { hwPowerSysInfoEntry 7 }
|
||
|
||
hwPowerProtect OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
protect(1),
|
||
undoProtect(2)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Apply for remote power system.
|
||
It is used to enable or disable N+1 protection function.
|
||
Options:
|
||
1.protect(1) - enables the N+1 protection function
|
||
2.undoProtect(2) - disables the N+1 protection function"
|
||
::= { hwPowerSysInfoEntry 8 }
|
||
|
||
hwPowerVersion OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Version of power"
|
||
::= { hwPowerSysInfoEntry 9 }
|
||
|
||
hwPowerSupplyState OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
ac(1),
|
||
battery(2)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"
|
||
Power supply modes.
|
||
Options:
|
||
1.ac(1) - indicates the AC power supply
|
||
2.battery(2) - indicates power supply by the batteries
|
||
"
|
||
::= { hwPowerSysInfoEntry 10 }
|
||
|
||
hwACInputTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwACInputEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"AC input table. Through this table,
|
||
AC input monitoring parameters of 4875 power supply, 4845 power supply,
|
||
4810 power supply, 48100 power supply, and 48240 power supply can
|
||
be set and queried.
|
||
The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwACLoopIndex.
|
||
hwEnvEmuIndex is the index of the monitoring unit.
|
||
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
|
||
hwACLoopIndex is the index of the AC input power supply monitored by the monitoring unit.
|
||
"
|
||
::= { hwPowerMonObjects 2 }
|
||
|
||
hwACInputEntry OBJECT-TYPE
|
||
SYNTAX HwACInputEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"AC input table. Through this table,
|
||
AC input monitoring parameters of 4875 power supply, 4845 power supply,
|
||
4810 power supply, 48100 power supply, and 48240 power supply can
|
||
be set and queried.
|
||
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwACLoopIndex.
|
||
hwEnvEmuIndex is the index of the monitoring unit.
|
||
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
|
||
hwACLoopIndex is the index of the AC input power supply monitored by the monitoring unit."
|
||
INDEX { hwEnvEmuIndex, hwPowerIndex, hwACLoopIndex }
|
||
::= { hwACInputTable 1 }
|
||
|
||
HwACInputEntry ::=
|
||
SEQUENCE {
|
||
hwACLoopIndex
|
||
Integer32,
|
||
hwACPowerState
|
||
INTEGER,
|
||
hwACVoltA
|
||
MeasuresRange,
|
||
hwACCurrentA
|
||
MeasuresRange,
|
||
hwACVoltB
|
||
MeasuresRange,
|
||
hwACCurrentB
|
||
MeasuresRange,
|
||
hwACVoltC
|
||
MeasuresRange,
|
||
hwACCurrentC
|
||
MeasuresRange,
|
||
hwACVoltageHigh
|
||
MeasuresRange,
|
||
hwACVoltageLow
|
||
MeasuresRange,
|
||
hwACRowStatus
|
||
RowStatus,
|
||
hwACVoltageAState
|
||
INTEGER,
|
||
hwACVoltageBState
|
||
INTEGER,
|
||
hwACVoltageCState
|
||
INTEGER
|
||
}
|
||
|
||
hwACLoopIndex OBJECT-TYPE
|
||
SYNTAX Integer32 (0..255)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Input loop index. There are two channels of AC current input,
|
||
which are the backup for each other."
|
||
::= { hwACInputEntry 1 }
|
||
|
||
hwACPowerState OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
offline(2),
|
||
exceedVoltage(3),
|
||
belowVoltage(4),
|
||
backup(5),
|
||
invalid(-1)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Status of power supply.
|
||
Options:
|
||
1.normal(1) - indicates that the power supply is normal
|
||
2.offline(2) - indicates that the power supply is offline
|
||
3.exceedVoltage(3) - indicates that the power supply is overvoltage
|
||
4.belowVoltage(4) - indicates that the power supply is undervoltage
|
||
5.backup(5) - indicates that the power supply is not supported currently
|
||
6.invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
|
||
"
|
||
::= { hwACInputEntry 2 }
|
||
|
||
hwACVoltA OBJECT-TYPE
|
||
SYNTAX MeasuresRange
|
||
UNITS "mV"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"AC Inuput voltage A.
|
||
Unit: mV"
|
||
::= { hwACInputEntry 3 }
|
||
|
||
hwACCurrentA OBJECT-TYPE
|
||
SYNTAX MeasuresRange
|
||
UNITS "mA"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"AC input Current A.
|
||
Unit: mA"
|
||
::= { hwACInputEntry 4 }
|
||
|
||
hwACVoltB OBJECT-TYPE
|
||
SYNTAX MeasuresRange
|
||
UNITS "mV"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"AC input voltage B.
|
||
Unit: mv"
|
||
::= { hwACInputEntry 5 }
|
||
|
||
hwACCurrentB OBJECT-TYPE
|
||
SYNTAX MeasuresRange
|
||
UNITS "mA"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"AC input current B.
|
||
Unit: mA"
|
||
::= { hwACInputEntry 6 }
|
||
|
||
hwACVoltC OBJECT-TYPE
|
||
SYNTAX MeasuresRange
|
||
UNITS "mV"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"AC input voltage C.
|
||
Unit: mV"
|
||
::= { hwACInputEntry 7 }
|
||
|
||
hwACCurrentC OBJECT-TYPE
|
||
SYNTAX MeasuresRange
|
||
UNITS "mA"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"AC input current C.
|
||
Unit: mA"
|
||
::= { hwACInputEntry 8 }
|
||
|
||
hwACVoltageHigh OBJECT-TYPE
|
||
SYNTAX MeasuresRange
|
||
UNITS "mV"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"AC input over-voltage alarm threshold.
|
||
Unit: mV"
|
||
DEFVAL { 280000 }
|
||
::= { hwACInputEntry 9 }
|
||
|
||
hwACVoltageLow OBJECT-TYPE
|
||
SYNTAX MeasuresRange
|
||
UNITS "mV"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"AC input under-voltage alarm threshold.
|
||
Unit: mV"
|
||
DEFVAL { 180000 }
|
||
::= { hwACInputEntry 10 }
|
||
|
||
hwACRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Only the add operation, delete operation, and status query operation are supported."
|
||
::= { hwACInputEntry 11 }
|
||
|
||
hwACVoltageAState OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(0),
|
||
belowVoltage(1) ,
|
||
exceedVoltage(2),
|
||
missing-phase(3)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Phase AB/A of AC input state.
|
||
Options:
|
||
1. normal(0) - indicates that the Phase AB/A of AC input state is normal
|
||
2. belowVoltage(1) - indicates that the Phase AB/A of AC input state is belowVoltage
|
||
3. exceedVoltage(2) - indicates that the Phase AB/A of AC input state is exceedVoltage
|
||
4. missing-phase(3) - indicates that the Phase AB/A of AC input state is missing-phase
|
||
"
|
||
::= { hwACInputEntry 12 }
|
||
|
||
hwACVoltageBState OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(0),
|
||
belowVoltage(1) ,
|
||
exceedVoltage(2),
|
||
missing-phase(3)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Phase BC/B of AC input state.
|
||
Options:
|
||
1. normal(0) - indicates that the Phase BC/B of AC input state is normal
|
||
2. belowVoltage(1) - indicates that the Phase BC/B of AC input state is belowVoltage
|
||
3. exceedVoltage(2) - indicates that the Phase BC/B of AC input state is exceedVoltage
|
||
4. missing-phase(3) - indicates that the Phase BC/B of AC input state is missing-phase
|
||
"
|
||
::= { hwACInputEntry 13 }
|
||
|
||
hwACVoltageCState OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(0),
|
||
belowVoltage(1) ,
|
||
exceedVoltage(2),
|
||
missing-phase(3)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Phase CA/C of AC input state.
|
||
Options:
|
||
1. normal(0) - indicates that the Phase CA/C of AC input state is normal
|
||
2. belowVoltage(1) - indicates that the Phase CA/C of AC input state is belowVoltage
|
||
3. exceedVoltage(2) - indicates that the Phase CA/C of AC input state is exceedVoltage
|
||
4. missing-phase(3) - indicates that the Phase CA/C of AC input state is missing-phase
|
||
"
|
||
::= { hwACInputEntry 14 }
|
||
|
||
hwDCOutTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwDCOutEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"DC output table. Through this table,
|
||
DC output monitoring parameters of 4875 power supply, 4845 power supply,
|
||
4810 power supply, 482400 power supply, and 48100 power supply can
|
||
be set and queried.
|
||
The indexes of this table are hwEnvEmuIndex and hwPowerIndex.
|
||
hwEnvEmuIndex, which comes from hwEnvironmentInfoTable,
|
||
is the index of the monitored unit.
|
||
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
|
||
"
|
||
::= { hwPowerMonObjects 3 }
|
||
|
||
hwDCOutEntry OBJECT-TYPE
|
||
SYNTAX HwDCOutEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"DC output table. Through this table,
|
||
DC output monitoring parameters of 4875 power supply, 4845 power supply,
|
||
4810 power supply, 482400 power supply, and 48100 power supply can
|
||
be set and queried.
|
||
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
|
||
hwEnvEmuIndex, which comes from hwEnvironmentInfoTable,
|
||
is the index of the monitored unit.
|
||
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
|
||
"
|
||
INDEX { hwEnvEmuIndex, hwPowerIndex }
|
||
::= { hwDCOutTable 1 }
|
||
|
||
HwDCOutEntry ::=
|
||
SEQUENCE {
|
||
hwDCVoltageOut
|
||
MeasuresRange,
|
||
hwDCCurrentOut
|
||
MeasuresRange,
|
||
hwDCVoltageOutHigh
|
||
MeasuresRange,
|
||
hwDCVoltageOutLow
|
||
MeasuresRange,
|
||
hwDCVoltageOutState
|
||
INTEGER,
|
||
hwDCCurrentOutHigh
|
||
MeasuresRange,
|
||
hwDCCurrentOutLow
|
||
MeasuresRange,
|
||
hwDCCurrentOutState
|
||
INTEGER,
|
||
hwDCOutRowStatus
|
||
RowStatus,
|
||
hwDCOutLoadCurrent
|
||
MeasuresRange,
|
||
hwDCOutLoadTmpHigh
|
||
MeasuresRange,
|
||
hwDCOutRunState
|
||
BITS ,
|
||
hwDCCommunicationState
|
||
INTEGER
|
||
}
|
||
|
||
hwDCVoltageOut OBJECT-TYPE
|
||
SYNTAX MeasuresRange
|
||
UNITS "mV"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"DC voltage output.
|
||
Unit: mV"
|
||
::= { hwDCOutEntry 1 }
|
||
|
||
hwDCCurrentOut OBJECT-TYPE
|
||
SYNTAX MeasuresRange
|
||
UNITS "mA"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"DC current output.
|
||
Unit: mA"
|
||
::= { hwDCOutEntry 2 }
|
||
|
||
hwDCVoltageOutHigh OBJECT-TYPE
|
||
SYNTAX MeasuresRange
|
||
UNITS "mV"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Output DC exceed-voltage alarm point.
|
||
Default: 58000
|
||
Unit: mV"
|
||
DEFVAL { 58000 }
|
||
::= { hwDCOutEntry 3 }
|
||
|
||
hwDCVoltageOutLow OBJECT-TYPE
|
||
SYNTAX MeasuresRange
|
||
UNITS "mV"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Output DC below-voltage alarm point . Default value is 45V.
|
||
Unit: mV"
|
||
DEFVAL { 45000 }
|
||
::= { hwDCOutEntry 4 }
|
||
|
||
hwDCVoltageOutState OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
exceedVoltage(2),
|
||
belowVoltage(3),
|
||
invalid(-1)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS deprecated
|
||
DESCRIPTION
|
||
"DC output voltage status.
|
||
Options:
|
||
1. normal(1) - indicates that the DC output voltage state is normal
|
||
2. exceedVoltage(2) - indicates that the DC output voltage state is exceedVoltage
|
||
3. belowVoltage(3) - indicates that the DC output voltage state is belowVoltage
|
||
4.invalid(-1) - indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
|
||
"
|
||
::= { hwDCOutEntry 5 }
|
||
|
||
hwDCCurrentOutHigh OBJECT-TYPE
|
||
SYNTAX MeasuresRange
|
||
UNITS "mA"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Output DC exceed-current alarm point .
|
||
Unit: mA"
|
||
::= { hwDCOutEntry 6 }
|
||
|
||
hwDCCurrentOutLow OBJECT-TYPE
|
||
SYNTAX MeasuresRange
|
||
UNITS "mA"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Output below-current alarm point .
|
||
Unit: mA"
|
||
::= { hwDCOutEntry 7 }
|
||
|
||
hwDCCurrentOutState OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
exceedVoltage(2),
|
||
belowVoltage(3),
|
||
invalid(-1)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS deprecated
|
||
DESCRIPTION
|
||
"DC output current status.
|
||
Options:
|
||
1.normal(1) - indicates that the DC output current state is normal
|
||
2.exceedVoltage(2) - indicates that the DC output current state is exceedVoltage
|
||
3.belowVoltage(3) - indicates that the DC output current state is belowVoltage
|
||
4.invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
|
||
"
|
||
::= { hwDCOutEntry 8 }
|
||
|
||
hwDCOutRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus standard operation"
|
||
::= { hwDCOutEntry 9 }
|
||
|
||
hwDCOutLoadCurrent OBJECT-TYPE
|
||
SYNTAX MeasuresRange
|
||
UNITS "mA"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Total load current of DC output .
|
||
Unit: mA"
|
||
::= { hwDCOutEntry 10 }
|
||
|
||
hwDCOutLoadTmpHigh OBJECT-TYPE
|
||
SYNTAX MeasuresRange
|
||
UNITS "0.01 degree"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The off protection point under the load temperature, by default,
|
||
it is 65 degrees centigrade.
|
||
Unit: 0.01 degree"
|
||
DEFVAL { 6500 }
|
||
::= { hwDCOutEntry 11 }
|
||
|
||
hwDCOutRunState OBJECT-TYPE
|
||
SYNTAX BITS
|
||
{
|
||
battery1ChargeCurOver(0),
|
||
battery2ChargeCurOver(1),
|
||
batteryVoltageOver(2),
|
||
batteryVoltageLack(3),
|
||
loadOff(4),
|
||
batteryOff(5),
|
||
communicationFailure(6),
|
||
dcOutManual(7)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"DC output running status.
|
||
Options:
|
||
1.battery1ChargeCurOver(0) - indicates battery 1 charge over-current
|
||
2.battery2ChargeCurOver(1) - indicates battery 2 charge over-current
|
||
3.batteryVoltageOver(2) - indicates output over-voltage
|
||
4.batteryVoltageLack(3) - indicates battery lack-voltage
|
||
5.loadOff(4) - indicates load off twice
|
||
6.batteryOff(5) - indictes battery protection (off once)
|
||
7.communicationFailure(6) - indicates that the communication fails
|
||
8.dcOutManual(7) - indicates DC by manual"
|
||
::= { hwDCOutEntry 12 }
|
||
|
||
hwDCCommunicationState OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(0),
|
||
fault(1)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"DC communication status.
|
||
Options:
|
||
1.normal(0) - indicates that the DC communication state is normal
|
||
2.fault(1) - indicates that the DC communication state is fault
|
||
"
|
||
::= { hwDCOutEntry 13 }
|
||
|
||
hwLoadinfoTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwLoadinfoEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Load information table. Through this table, the load parameter can be set and queried.
|
||
The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwLoadIndex.
|
||
hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, is the index of the monitored unit.
|
||
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
|
||
hwLoadIndex is the index of the monitored load.
|
||
"
|
||
::= { hwPowerMonObjects 4 }
|
||
|
||
hwLoadinfoEntry OBJECT-TYPE
|
||
SYNTAX HwLoadinfoEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Load information table. Through this table, the load parameter can be set and queried.
|
||
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwLoadIndex.
|
||
hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, is the index of the monitored unit.
|
||
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
|
||
hwLoadIndex is the index of the monitored load.
|
||
"
|
||
INDEX { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
|
||
::= { hwLoadinfoTable 1 }
|
||
|
||
HwLoadinfoEntry ::=
|
||
SEQUENCE {
|
||
hwLoadIndex
|
||
Integer32,
|
||
hwLoadInfoAdminState
|
||
INTEGER,
|
||
hwLoadInfoOperStatus
|
||
INTEGER,
|
||
hwLoadCurrent
|
||
MeasuresRange,
|
||
hwLoadVoltage
|
||
MeasuresRange,
|
||
hwLoadVoltageHigh
|
||
MeasuresRange,
|
||
hwLoadLoadName
|
||
DisplayString,
|
||
hwLoadInfoRowStatus
|
||
RowStatus,
|
||
hwLoadFuseState
|
||
INTEGER,
|
||
hwLoadHoreIndex
|
||
Integer32
|
||
}
|
||
|
||
hwLoadIndex OBJECT-TYPE
|
||
SYNTAX Integer32 (0..255)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Loop index: usually each DC output loop corresponds to a load."
|
||
::= { hwLoadinfoEntry 1 }
|
||
|
||
hwLoadInfoAdminState OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
on(1),
|
||
off(2),
|
||
invalid(-1)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Load operation.
|
||
Options:
|
||
1. on(1) - indicates that the Load is enabled
|
||
2. off(2) - indicates that the Load is disabled
|
||
3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
|
||
"
|
||
DEFVAL { 1 }
|
||
::= { hwLoadinfoEntry 2 }
|
||
|
||
hwLoadInfoOperStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
abnormal(2),
|
||
stop(3),
|
||
invalid(-1)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Status of power supply.
|
||
Options:
|
||
1. normal(1) - indicates that the state of power supply is normal
|
||
2. abnormal(2) - indicates that the state of power supply is abnormal
|
||
3. stop(3) - indicates that the state of power supply is stopping power supply
|
||
4. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
|
||
"
|
||
::= { hwLoadinfoEntry 3 }
|
||
|
||
hwLoadCurrent OBJECT-TYPE
|
||
SYNTAX MeasuresRange
|
||
UNITS "mA"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Present current .
|
||
Unit: mA"
|
||
::= { hwLoadinfoEntry 4 }
|
||
|
||
hwLoadVoltage OBJECT-TYPE
|
||
SYNTAX MeasuresRange
|
||
UNITS "mV"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Present voltage .
|
||
Unit: mV"
|
||
::= { hwLoadinfoEntry 5 }
|
||
|
||
hwLoadVoltageHigh OBJECT-TYPE
|
||
SYNTAX MeasuresRange
|
||
UNITS "mV"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Off voltage (Stop external voltage), in unit of mV,
|
||
When DC output voltage exceeds the value, the load will be automatically cut off.
|
||
Default: 43500
|
||
Unit: mV
|
||
"
|
||
DEFVAL { 43500 }
|
||
::= { hwLoadinfoEntry 6 }
|
||
|
||
hwLoadLoadName OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Load name: usually each DC output loop corresponds to a load."
|
||
::= { hwLoadinfoEntry 7 }
|
||
|
||
hwLoadInfoRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus standard operation"
|
||
::= { hwLoadinfoEntry 8 }
|
||
|
||
hwLoadFuseState OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
on(1),
|
||
off(2),
|
||
invalid(-1)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Load fuse state, including the auxiliary load fuse.
|
||
Options:
|
||
1. on(1) - indicates that the fuse is connected
|
||
2. off(2) - indicates that the fuse is disconnected
|
||
3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
|
||
"
|
||
::= { hwLoadinfoEntry 9 }
|
||
|
||
hwLoadHoreIndex OBJECT-TYPE
|
||
SYNTAX Integer32 (0..255)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"
|
||
load hore index
|
||
"
|
||
::= { hwLoadinfoEntry 10 }
|
||
|
||
|
||
hwRectifierTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwRectifierEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rectifier module table.
|
||
Through this table, the status information of the rectifier module
|
||
can be set and queried.
|
||
The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwRectifierIndex.
|
||
hwEnvEmuIndex, which comes from hwEnvironmentInfoTable,
|
||
is the index of the monitored unit.
|
||
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
|
||
hwRectifierIndex is the index of the monitored rectifier module under the power supply.
|
||
"
|
||
::= { hwPowerMonObjects 5 }
|
||
|
||
hwRectifierEntry OBJECT-TYPE
|
||
SYNTAX HwRectifierEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rectifier module table.
|
||
Through this table, the status information of the rectifier module
|
||
can be set and queried.
|
||
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwRectifierIndex.
|
||
hwEnvEmuIndex, which comes from hwEnvironmentInfoTable,
|
||
is the index of the monitored unit.
|
||
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
|
||
hwRectifierIndex is the index of the monitored rectifier module under the power supply.
|
||
"
|
||
INDEX { hwEnvEmuIndex, hwPowerIndex, hwRectifierIndex }
|
||
::= { hwRectifierTable 1 }
|
||
|
||
HwRectifierEntry ::=
|
||
SEQUENCE {
|
||
hwRectifierIndex
|
||
Integer32,
|
||
hwRectifierAdminState
|
||
INTEGER,
|
||
hwRectifierOperState
|
||
INTEGER,
|
||
hwRectifierVoltage
|
||
MeasuresRange,
|
||
hwRectifierCurrent
|
||
MeasuresRange,
|
||
hwRectifierRowStatus
|
||
RowStatus,
|
||
hwRectifierCurrentLimit
|
||
TruthValue,
|
||
hwRectifierRunState
|
||
BITS,
|
||
hwRectifierChargeState
|
||
INTEGER
|
||
}
|
||
|
||
hwRectifierIndex OBJECT-TYPE
|
||
SYNTAX Integer32 (0..255)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rectifier Module index. There are multiple rectifier
|
||
modules to a power source.
|
||
"
|
||
::= { hwRectifierEntry 1 }
|
||
|
||
hwRectifierAdminState OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
on(1),
|
||
off(2),
|
||
invalid(-1)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Switch operation of rectifier module.
|
||
Options:
|
||
1.on(1) - indicates that the Rectifier module is enabled
|
||
2.off(2) - indicates that the Rectifier module is disabled
|
||
3.invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
|
||
"
|
||
DEFVAL { 1 }
|
||
::= { hwRectifierEntry 2 }
|
||
|
||
hwRectifierOperState OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
fault(2),
|
||
protect(3),
|
||
communicationFailure(4),
|
||
on(5),
|
||
noConfig(6),
|
||
offline(7),
|
||
close(8),
|
||
invalid(-1)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Present state, 5 and 6 respectively indicates the on/off state of the 48100 power device.
|
||
Options:
|
||
1. normal(1) - indicates that the Rectifier operation state is normal
|
||
2. fault(2) - indicates that the Rectifier operation state is fault
|
||
3. protect(3) - indicates that the Rectifier operation state is protect
|
||
4. communicationFailure(4) - indicates that the Rectifier operation state is communicationFailure
|
||
5. on(5) - indicates that the Rectifier operation state is on
|
||
6. noConfig(6) - indicates that the Rectifier operation state is not Configured
|
||
7. offline(7) - indicates that the Rectifier operation state is offline
|
||
8. close(8) - indicates that the Rectifier operation state is closed
|
||
9. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
|
||
"
|
||
::= { hwRectifierEntry 3 }
|
||
|
||
hwRectifierVoltage OBJECT-TYPE
|
||
SYNTAX MeasuresRange
|
||
UNITS "mV"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Output voltage .
|
||
Unit: mV"
|
||
::= { hwRectifierEntry 4 }
|
||
|
||
hwRectifierCurrent OBJECT-TYPE
|
||
SYNTAX MeasuresRange
|
||
UNITS "mA"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Output current .
|
||
Unit: mA"
|
||
::= { hwRectifierEntry 5 }
|
||
|
||
hwRectifierRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus standard operation"
|
||
::= { hwRectifierEntry 6 }
|
||
|
||
hwRectifierCurrentLimit OBJECT-TYPE
|
||
SYNTAX TruthValue
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"current limit switch"
|
||
DEFVAL { 1 }
|
||
::= { hwRectifierEntry 7 }
|
||
|
||
hwRectifierRunState OBJECT-TYPE
|
||
SYNTAX BITS
|
||
{
|
||
rectifierOn(0),
|
||
averageCharge(1),
|
||
output(2),
|
||
isLimit(3)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Running state of rectifier module.
|
||
Options:
|
||
1.rectifierOn(0) - indicates that the module is on
|
||
2.averageCharge(1) - indicates that the module is being averagely charged.
|
||
3.output(2) - indicates that the module has output
|
||
4. isLimit(3) - indicates the current limit switch
|
||
"
|
||
::= { hwRectifierEntry 8 }
|
||
|
||
hwRectifierChargeState OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
float(0),
|
||
average(1),
|
||
test(2)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Charging state of rectifier.
|
||
Options:
|
||
1. float(0) - indicates that the Charge state of Rectifier is float
|
||
2. average(1) - indicates that the Charge state of Rectifier is average
|
||
3. test(2) - indicates that the Charge state of Rectifier is test
|
||
"
|
||
::= { hwRectifierEntry 9 }
|
||
|
||
hwBatteryGroup OBJECT IDENTIFIER ::= { hwPowerMonObjects 6 }
|
||
hwBatteryGroupTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwBatteryGroupEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Basic information table of battery group.
|
||
The indexes of this table are hwEnvEmuIndex and hwPowerIndex.
|
||
hwEnvEmuIndex is the index of the monitored unit,
|
||
and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
|
||
"
|
||
::= { hwBatteryGroup 1 }
|
||
|
||
hwBatteryGroupEntry OBJECT-TYPE
|
||
SYNTAX HwBatteryGroupEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Basic information table of battery group.
|
||
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
|
||
hwEnvEmuIndex is the index of the monitored unit,
|
||
and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
|
||
"
|
||
INDEX { hwEnvEmuIndex, hwPowerIndex }
|
||
::= { hwBatteryGroupTable 1 }
|
||
|
||
HwBatteryGroupEntry ::=
|
||
SEQUENCE {
|
||
hwBatteryGroupCapacity
|
||
Integer32,
|
||
hwBatteryGroupCapcaityRemain
|
||
Integer32,
|
||
hwBatteryGroups
|
||
Integer32,
|
||
hwBatteryGroupVoltageLow
|
||
MeasuresRange,
|
||
hwBatteryGroupChargeLimit
|
||
MeasuresRange,
|
||
hwBatteryGroupRowStatus
|
||
RowStatus,
|
||
hwBatteryGroupOperStatus
|
||
INTEGER,
|
||
hwBatteryGroupVoltageHigh
|
||
MeasuresRange,
|
||
hwBatteryGroupTwiceOffVoltage
|
||
MeasuresRange,
|
||
hwBatteryGroupProtectVoltage
|
||
MeasuresRange,
|
||
hwBatteryGroupTmpOffHigh
|
||
MeasuresRange,
|
||
hwBatteryInstallTime
|
||
DisplayString,
|
||
hwBatteryGroupBomCode
|
||
DisplayString
|
||
}
|
||
|
||
hwBatteryGroupCapacity OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Total capacity of the present battery group.
|
||
Unit: Ah"
|
||
::= { hwBatteryGroupEntry 1 }
|
||
|
||
hwBatteryGroupCapcaityRemain OBJECT-TYPE
|
||
SYNTAX Integer32 (-1..100)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Total remain capacity of the present battery group .
|
||
invalid(-1) indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal.
|
||
Unit: Ah"
|
||
::= { hwBatteryGroupEntry 2 }
|
||
|
||
hwBatteryGroups OBJECT-TYPE
|
||
SYNTAX Integer32 (0..255)
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Number of battery group"
|
||
DEFVAL { 2 }
|
||
::= { hwBatteryGroupEntry 3 }
|
||
|
||
hwBatteryGroupVoltageLow OBJECT-TYPE
|
||
SYNTAX MeasuresRange
|
||
UNITS "mV"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"When the voltage of the battery group is lower than the value set,
|
||
the battery group will no longer supply power. Its unit is mV.
|
||
Default: 43000
|
||
Unit: mV
|
||
"
|
||
DEFVAL { 43000 }
|
||
::= { hwBatteryGroupEntry 4 }
|
||
|
||
hwBatteryGroupChargeLimit OBJECT-TYPE
|
||
SYNTAX MeasuresRange
|
||
UNITS "percent"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Charge limit point quotient, the product of which and the max capacity
|
||
of the battery group is the max charge current allowed.
|
||
Default: 15
|
||
Unit: percent
|
||
"
|
||
DEFVAL { 15 }
|
||
::= { hwBatteryGroupEntry 5 }
|
||
|
||
hwBatteryGroupRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus standard operation"
|
||
::= { hwBatteryGroupEntry 6 }
|
||
|
||
hwBatteryGroupOperStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
on(1),
|
||
off(2),
|
||
invalid(-1)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The State of the battery supply which was connected with Power EMU.
|
||
To use this function,please confirm that the battery group was connected with Power EMU and the Power EMU state is Normal.
|
||
When the mains supply is abnormal, the battery group usually supplies power in an emergency.
|
||
Options:
|
||
1.on(1) - indicates that the state of the battery power supply is on
|
||
2.off(2) - indicates that the state of the battery power supply is off
|
||
3.invalid(-1) - indicates that the device can not get the value,e.g. the EMU does not support this operation, or the EMU state is abnormal"
|
||
::= { hwBatteryGroupEntry 7 }
|
||
|
||
hwBatteryGroupVoltageHigh OBJECT-TYPE
|
||
SYNTAX MeasuresRange
|
||
UNITS "mV"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"When the voltage of the battery group is higher than the value set, the battery group
|
||
will no longer supply power. Its unit is mV.
|
||
Default: 43000
|
||
Unit: mV
|
||
"
|
||
DEFVAL { 43000 }
|
||
::= { hwBatteryGroupEntry 8 }
|
||
|
||
hwBatteryGroupTwiceOffVoltage OBJECT-TYPE
|
||
SYNTAX MeasuresRange
|
||
UNITS "mV"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The twice off protection voltage of the battery group. Its unit is mV.
|
||
Default: 44000
|
||
Unit: mV
|
||
"
|
||
DEFVAL { 44000 }
|
||
::= { hwBatteryGroupEntry 9 }
|
||
|
||
hwBatteryGroupProtectVoltage OBJECT-TYPE
|
||
SYNTAX MeasuresRange
|
||
UNITS "mV"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The first off protection voltage of the battery,
|
||
whose default is 43V.
|
||
Default: 43000
|
||
Unit: mV
|
||
"
|
||
DEFVAL { 43000 }
|
||
::= { hwBatteryGroupEntry 10 }
|
||
|
||
hwBatteryGroupTmpOffHigh OBJECT-TYPE
|
||
SYNTAX MeasuresRange
|
||
UNITS "0.01 degree"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The high temperature off protection point of the battery group,
|
||
whose default is 50 degrees centigrade.
|
||
Unit: 0.01 degree
|
||
"
|
||
DEFVAL { 5000 }
|
||
::= { hwBatteryGroupEntry 11 }
|
||
|
||
hwBatteryInstallTime OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"
|
||
The installing date of battery group.
|
||
"
|
||
::= { hwBatteryGroupEntry 12 }
|
||
|
||
hwBatteryGroupBomCode OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..32))
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"
|
||
The BOM code of battery.
|
||
"
|
||
::= { hwBatteryGroupEntry 13 }
|
||
|
||
hwChargeTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwChargeEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Charge management table.
|
||
Through this table, the charging parameter of the battery can be set and queried.
|
||
The indexes of this table are hwEnvEmuIndex and hwPowerIndex.
|
||
hwEnvEmuIndex is the index of the monitored unit,
|
||
and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
|
||
"
|
||
::= { hwBatteryGroup 2 }
|
||
|
||
hwChargeEntry OBJECT-TYPE
|
||
SYNTAX HwChargeEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Charge management table.
|
||
Through this table, the charging parameter of the battery can be set and queried.
|
||
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
|
||
hwEnvEmuIndex is the index of the monitored unit,
|
||
and hwPowerIndex is the index of the power supply monitored by the monitoring unit."
|
||
INDEX { hwEnvEmuIndex, hwPowerIndex }
|
||
::= { hwChargeTable 1 }
|
||
|
||
HwChargeEntry ::=
|
||
SEQUENCE {
|
||
hwChargeAdminStatus
|
||
INTEGER,
|
||
hwChargeOperStatus
|
||
INTEGER,
|
||
hwAverageChargeVoltage
|
||
MeasuresRange,
|
||
hwFloatChargeVoltage
|
||
MeasuresRange,
|
||
hwChargeControlRowStatus
|
||
RowStatus,
|
||
hwAverageChargeTime
|
||
Integer32,
|
||
hwBatteryTmpRedeemingQuotiety
|
||
Integer32
|
||
}
|
||
|
||
hwChargeAdminStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
average(1),
|
||
float(2),
|
||
auto(3),
|
||
invalid(-1)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Charge management mode.
|
||
Options:
|
||
1. average(1) - indicates that the charge management mode is average charge
|
||
2. float(2) - indicates that the charge management mode is float charge
|
||
3. auto(3) - indicates that the charge management mode is auto-control charge
|
||
4. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
|
||
"
|
||
DEFVAL { 2 }
|
||
::= { hwChargeEntry 1 }
|
||
|
||
hwChargeOperStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
average(1),
|
||
float(2),
|
||
full(3),
|
||
noCharge(4),
|
||
discharge(5),
|
||
sleep(6),
|
||
invalid(-1)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Charge operation status.
|
||
Options:
|
||
1. average(1) - indicates that the charge operation state is average charge
|
||
2. float(2) - indicates that the charge operation state is float charge
|
||
3. full(3) - indicates that the charge operation state is full
|
||
4. noCharge(4) - indicates that there is no charge in operation
|
||
5. discharge(5) - indicates that there is discharge in operation
|
||
6. sleep(6) - indicates that the charge operation state is sleep
|
||
7. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
|
||
"
|
||
::= { hwChargeEntry 2 }
|
||
|
||
hwAverageChargeVoltage OBJECT-TYPE
|
||
SYNTAX MeasuresRange
|
||
UNITS "mV"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Voltage value of average charge, in unit of mV.
|
||
Default: 56500
|
||
Unit: mV
|
||
"
|
||
DEFVAL { 56500 }
|
||
::= { hwChargeEntry 3 }
|
||
|
||
hwFloatChargeVoltage OBJECT-TYPE
|
||
SYNTAX MeasuresRange
|
||
UNITS "mV"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Voltage value of float charge .
|
||
Default: 53500
|
||
Unit: mV
|
||
"
|
||
DEFVAL { 53500 }
|
||
::= { hwChargeEntry 4 }
|
||
|
||
hwChargeControlRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus standard operation"
|
||
::= { hwChargeEntry 5 }
|
||
|
||
hwAverageChargeTime OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "day"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Timing average charge time interval, effective range is 190 days.
|
||
Default :value is 60 days
|
||
Unit: day"
|
||
DEFVAL { 60 }
|
||
::= { hwChargeEntry 6 }
|
||
|
||
hwBatteryTmpRedeemingQuotiety OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Temperature redeeming quotient, used to set the co-relation
|
||
between the float charge voltage and the battery temperature.
|
||
It means How much will the float charge voltage decrease
|
||
with the increasing of every degree centigrade of the battery
|
||
temperature. The unit is mV.
|
||
Specific value is determined by the redeem feature curve of
|
||
floating charge for the battery group used.
|
||
Default value is 100mV
|
||
"
|
||
DEFVAL { 100 }
|
||
::= { hwChargeEntry 7 }
|
||
|
||
hwBatteryTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwBatteryEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery group state table.
|
||
Through this table, the status parameter of a battery group can be set and queried.
|
||
The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwBatteryIndex.
|
||
hwEnvEmuIndex is the index of the monitored unit.
|
||
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
|
||
hwBatteryIndex is the index of the monitored battery group.
|
||
"
|
||
::= { hwBatteryGroup 3 }
|
||
|
||
hwBatteryEntry OBJECT-TYPE
|
||
SYNTAX HwBatteryEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery group state table.
|
||
Through this table, the status parameter of a battery group can be set and queried.
|
||
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryIndex.
|
||
hwEnvEmuIndex is the index of the monitored unit.
|
||
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
|
||
hwBatteryIndex is the index of the monitored battery group.
|
||
"
|
||
INDEX { hwEnvEmuIndex, hwPowerIndex, hwBatteryIndex }
|
||
::= { hwBatteryTable 1 }
|
||
|
||
HwBatteryEntry ::=
|
||
SEQUENCE {
|
||
hwBatteryIndex
|
||
Integer32,
|
||
hwBatteryCapacity
|
||
Integer32,
|
||
hwBatteryLoopState
|
||
INTEGER,
|
||
hwBatteryVoltage
|
||
MeasuresRange,
|
||
hwBatteryState
|
||
INTEGER,
|
||
hwBatteryCurrent
|
||
MeasuresRange,
|
||
hwBatteryTemperature
|
||
Integer32,
|
||
hwBatteryRowStatus
|
||
RowStatus,
|
||
hwBatteryCurrentHigh
|
||
MeasuresRange,
|
||
hwBatteryFuseState
|
||
INTEGER,
|
||
hwBatteryContactState
|
||
INTEGER,
|
||
hwBatteryRemainCapacity
|
||
Integer32,
|
||
hwBatteryProtectState
|
||
INTEGER,
|
||
hwBatteryVoltageState
|
||
INTEGER,
|
||
hwBatteryHardwareState
|
||
INTEGER
|
||
}
|
||
|
||
hwBatteryIndex OBJECT-TYPE
|
||
SYNTAX Integer32 (0..255)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery group loop index"
|
||
::= { hwBatteryEntry 1 }
|
||
|
||
hwBatteryCapacity OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The permitted max battery capacity of the battery group loop charge.
|
||
Unit: Ah"
|
||
DEFVAL { 100 }
|
||
::= { hwBatteryEntry 2 }
|
||
|
||
hwBatteryLoopState OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
on(1),
|
||
off(2),
|
||
invalid(-1)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The battery group present status.
|
||
Options:
|
||
1. on(1) - indicates that the present state of battery group is on
|
||
2. off(2) - indicates that the present state of battery group is off
|
||
3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
|
||
"
|
||
::= { hwBatteryEntry 3 }
|
||
|
||
hwBatteryVoltage OBJECT-TYPE
|
||
SYNTAX MeasuresRange
|
||
UNITS "mV"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The loop voltage of the battery group.
|
||
Unit: mV"
|
||
::= { hwBatteryEntry 4 }
|
||
|
||
hwBatteryState OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
charge(1),
|
||
discharge(2),
|
||
invalid(-1)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The present state of the battery group loop.
|
||
Options:
|
||
1. charge(1) - indicates that the present state of the battery group loop is charge
|
||
2. discharge(2) - indicates that the present state of the battery group loop is discharge
|
||
3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
|
||
"
|
||
::= { hwBatteryEntry 5 }
|
||
|
||
hwBatteryCurrent OBJECT-TYPE
|
||
SYNTAX MeasuresRange
|
||
UNITS "mA"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Present current .
|
||
Unit: mA"
|
||
::= { hwBatteryEntry 6 }
|
||
|
||
hwBatteryTemperature OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "degree"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The loop temperature of the battery group.
|
||
Unit: degree"
|
||
::= { hwBatteryEntry 7 }
|
||
|
||
hwBatteryRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus standard operation"
|
||
::= { hwBatteryEntry 8 }
|
||
|
||
hwBatteryCurrentHigh OBJECT-TYPE
|
||
SYNTAX MeasuresRange
|
||
UNITS "mA"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The over-current alarm point of the battery group.
|
||
Unit: mA"
|
||
::= { hwBatteryEntry 9 }
|
||
|
||
hwBatteryFuseState OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
on(1),
|
||
off(2),
|
||
invalid(-1)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery fuse state.
|
||
Options:
|
||
1. on(1) - indicates that the fuse is connected
|
||
2. off(2) - indicates that the fuse is disconnected
|
||
3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
|
||
"
|
||
::= { hwBatteryEntry 10 }
|
||
|
||
hwBatteryContactState OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
on(1),
|
||
off(2),
|
||
invalid(-1)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The state of the battery contactor.
|
||
Options:
|
||
1. on(1) - indicates that the contactor is connected
|
||
2. off(2) - indicates that the contactor is disconnected
|
||
3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal"
|
||
::= { hwBatteryEntry 11 }
|
||
|
||
hwBatteryRemainCapacity OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Remain capacity of the battery
|
||
"
|
||
::= { hwBatteryEntry 12 }
|
||
|
||
hwBatteryProtectState OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
overtemperature(2),
|
||
overCurrent(3)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Protection status of the battery.
|
||
Options:
|
||
1. normal(1) - indicates that the Protection status of the battery is normal
|
||
2. overtemperature(2) - indicates that the Protection status of the battery is overtemperature
|
||
3. overCurrent(3) - indicates that the Protection status of the battery is overCurrent
|
||
"
|
||
::= { hwBatteryEntry 13 }
|
||
|
||
hwBatteryVoltageState OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
exceedVoltage(2),
|
||
belowVoltage(3)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Voltage state of Battery.
|
||
Options:
|
||
1. normal(1) - indicates that Voltage state of Battery is normal
|
||
2. exceedVoltage(2) - indicates that Voltage state of Battery is exceedVoltage
|
||
3. belowVoltage(3) - indicates that Voltage state of Battery is belowVoltage
|
||
"
|
||
::= { hwBatteryEntry 14 }
|
||
|
||
hwBatteryHardwareState OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
fault(2)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Hardware State of Battery.
|
||
Options:
|
||
1. normal(1) - indicates that the hardware state of Battery is normal
|
||
2. fault(2) - indicates that the hardware state of Battery is fault
|
||
"
|
||
::= { hwBatteryEntry 15 }
|
||
|
||
hwBatteryTestTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwBatteryTestEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery test table.
|
||
The indexes of this table are hwEnvEmuIndex and hwPowerIndex.
|
||
hwEnvEmuIndex is the index of the monitored unit,
|
||
and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
|
||
"
|
||
::= { hwBatteryGroup 4 }
|
||
|
||
hwBatteryTestEntry OBJECT-TYPE
|
||
SYNTAX HwBatteryTestEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery test table.
|
||
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
|
||
hwEnvEmuIndex is the index of the monitored unit,
|
||
and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
|
||
"
|
||
INDEX { hwEnvEmuIndex, hwPowerIndex }
|
||
::= { hwBatteryTestTable 1 }
|
||
|
||
HwBatteryTestEntry ::=
|
||
SEQUENCE {
|
||
hwBatteryTestAdminStatus
|
||
INTEGER,
|
||
hwBatteryTestAutoDischargePeriod
|
||
Integer32,
|
||
hwBatteryTestResult
|
||
INTEGER,
|
||
hwBatteryTestStartTime
|
||
DateAndTime,
|
||
hwBatteryTestDuration
|
||
Integer32,
|
||
hwBatteryTestTerminateVoltage
|
||
Integer32,
|
||
hwBatteryTestTotalDischargeAH
|
||
Integer32,
|
||
hwBatteryTestOperStatus
|
||
INTEGER,
|
||
hwBatteryTestPhase
|
||
INTEGER,
|
||
hwBatteryTestStartHour
|
||
Integer32,
|
||
hwBatteryTestAlarmThreshold
|
||
Integer32
|
||
}
|
||
|
||
hwBatteryTestAdminStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
start(1),
|
||
terminate(2),
|
||
enableAutoTest(3),
|
||
disableAutoTest(4),
|
||
timeautoTest(5),
|
||
offautoTest(6),
|
||
timeoffautoTest(7)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery test admin status.
|
||
Options:
|
||
1. start(1) - indicates that the Battery starts testing
|
||
2. terminate(2) - indicates that the Battery terminates testing
|
||
3. enableAutoTest(3) - indicates that the Battery enables auto test function
|
||
4. disableAutoTest(4) - indicates that the Battery disables auto test function
|
||
5. timeautoTest(5) - indicates that the Battery enable timing auto test function
|
||
6. offautoTest(6) - indicates that the Battery enable off auto test function
|
||
7. timeoffautoTest(7) - indicates that the Battery enable timing+off auto test
|
||
"
|
||
::= { hwBatteryTestEntry 1 }
|
||
|
||
hwBatteryTestAutoDischargePeriod OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "day"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Auto discharge test period.
|
||
Effective range is 30 -240 days.
|
||
Default: 120
|
||
Unit: day
|
||
"
|
||
DEFVAL { 120 }
|
||
::= { hwBatteryTestEntry 2 }
|
||
|
||
hwBatteryTestResult OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
testing(1),
|
||
complete(2),
|
||
alarmTerminated(3),
|
||
hostTerminated(4),
|
||
overtimeTerminated(5),
|
||
normal(6),
|
||
supplyRecoverAutotestTerminated(7)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS obsolete
|
||
DESCRIPTION
|
||
"Test result:
|
||
Options:
|
||
1. testing(1) - indicates that the Battery test is in operation
|
||
2. complete(2) - indicates that the Battery test is completed normally
|
||
3. alarmTerminated(3) - indicates that the Battery test is stopped by alarms
|
||
4. hostTerminated(4) - indicates that the Battery test is stopped by the host
|
||
5. overtimeTerminated(5) - indicates that the Battery test is stopped because of over time
|
||
6. normal(6) - indicates that the Battery test is not started
|
||
7. supplyRecoverAutotestTerminated(7) - indicates that the Battery test is stopped because of supply recover
|
||
"
|
||
::= { hwBatteryTestEntry 3 }
|
||
|
||
hwBatteryTestStartTime OBJECT-TYPE
|
||
SYNTAX DateAndTime
|
||
MAX-ACCESS read-only
|
||
STATUS obsolete
|
||
DESCRIPTION
|
||
"Time of starting test"
|
||
::= { hwBatteryTestEntry 4 }
|
||
|
||
hwBatteryTestDuration OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "hour"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery discharge test duration .
|
||
Effective range is 1<>C100 hours.
|
||
Default :value is 10 hours
|
||
Unit: hour
|
||
"
|
||
::= { hwBatteryTestEntry 5 }
|
||
|
||
hwBatteryTestTerminateVoltage OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "mV"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery discharge test end voltage.
|
||
Effective range (DC lack alarm voltage+0.5V<EFBFBD>Cvoltage of floating charge).
|
||
Default: 45600
|
||
Unit: mV
|
||
"
|
||
::= { hwBatteryTestEntry 6 }
|
||
|
||
hwBatteryTestTotalDischargeAH OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "mAH"
|
||
MAX-ACCESS read-only
|
||
STATUS obsolete
|
||
DESCRIPTION
|
||
"
|
||
Total discharge AH.
|
||
Unit: mAH
|
||
"
|
||
::= { hwBatteryTestEntry 7 }
|
||
|
||
hwBatteryTestOperStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
autoTestPermit(1),
|
||
autoTestForbid(2),
|
||
timeautoTestPermit(3),
|
||
offautoTestPermit(4),
|
||
timeoffautoTestPermit(5)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"
|
||
Battery discharge test operate status.
|
||
Options:
|
||
1. autoTestPermit(1) - indicates that auto discharge test is enabled
|
||
2. autoTestForbid(2) - indicates that auto discharge test is disabled
|
||
3. timeautoTestPermit(3) - indicates that timing auto discharge test is enabled
|
||
4. offautoTestPermit(4) - indicates that off auto discharge test is enabled
|
||
5. timeoffautoTestPermit(5) - indicates that timing-off auto discharge test is enabled"
|
||
::= { hwBatteryTestEntry 8 }
|
||
|
||
hwBatteryTestPhase OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
charge(1),
|
||
discharge(2),
|
||
record(3),
|
||
finish(4),
|
||
waitingfordischarge(5)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery test phase.
|
||
Options:
|
||
1. charge(1) - indicates the batter test phase is charge
|
||
2. discharge(2) - indicates the batter test phase is discharge
|
||
3. record(3) - indicates the power equipment recording test result
|
||
4. finish(4) - indicates that the discharge is complete
|
||
5.waitingfordischarge(5) - indicates that preparation is ready for discharge command
|
||
"
|
||
::= { hwBatteryTestEntry 9 }
|
||
|
||
hwBatteryTestStartHour OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "hour"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Discharge start time.
|
||
Effective range is 0 23
|
||
Default: 0
|
||
Unit: hour
|
||
"
|
||
DEFVAL { '0'b }
|
||
::= { hwBatteryTestEntry 10 }
|
||
|
||
hwBatteryTestAlarmThreshold OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "percent"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The battery discharge test alarm threshold in ratio of the range:1~79."
|
||
DEFVAL { 70 }
|
||
::= { hwBatteryTestEntry 11 }
|
||
|
||
hwBatteryLogTestTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwBatteryLogTestEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery test result table,
|
||
Through this table, the discharging test result of the battery group can be saved and queried.
|
||
The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwBatteryLogTestIndex.
|
||
hwEnvEmuIndex is the index of the monitored unit.
|
||
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
|
||
hwBatteryLogTestIndex is the index of the monitored battery.
|
||
"
|
||
::= { hwBatteryGroup 5 }
|
||
|
||
hwBatteryLogTestEntry OBJECT-TYPE
|
||
SYNTAX HwBatteryLogTestEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery test result table,
|
||
Through this table, the discharging test result of the battery group can be saved and queried.
|
||
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryLogTestIndex.
|
||
hwEnvEmuIndex is the index of the monitored unit.
|
||
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
|
||
hwBatteryLogTestIndex is the index of the monitored battery.
|
||
"
|
||
INDEX { hwEnvEmuIndex, hwPowerIndex, hwBatteryLogTestIndex }
|
||
::= { hwBatteryLogTestTable 1 }
|
||
|
||
HwBatteryLogTestEntry ::=
|
||
SEQUENCE {
|
||
hwBatteryLogTestIndex
|
||
Integer32,
|
||
hwBatteryLogTestStartTime
|
||
DateAndTime,
|
||
hwBatteryLogTestDischargeDuration
|
||
Integer32,
|
||
hwBatteryLogTestTerminateVoltage
|
||
Integer32,
|
||
hwBatteryLogTestBatteryStatus
|
||
INTEGER,
|
||
hwBatteryLogTestTotalDischargeAH
|
||
Integer32,
|
||
hwBatteryLogTestFinish
|
||
INTEGER,
|
||
hwBatteryLogTestEfficiency
|
||
Integer32,
|
||
hwBatteryLogTestBatteryTemperature
|
||
Integer32,
|
||
hwBatteryLogTestBatteryCurrent
|
||
Integer32
|
||
}
|
||
|
||
hwBatteryLogTestIndex OBJECT-TYPE
|
||
SYNTAX Integer32 (0..255)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery discharge test result index"
|
||
::= { hwBatteryLogTestEntry 1 }
|
||
|
||
hwBatteryLogTestStartTime OBJECT-TYPE
|
||
SYNTAX DateAndTime
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery discharge test start time"
|
||
::= { hwBatteryLogTestEntry 2 }
|
||
|
||
hwBatteryLogTestDischargeDuration OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "minute"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Duration of discharge.
|
||
Unit: minute"
|
||
::= { hwBatteryLogTestEntry 3 }
|
||
|
||
hwBatteryLogTestTerminateVoltage OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "mV"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"End voltage of battery discharge test .
|
||
Unit: mV"
|
||
::= { hwBatteryLogTestEntry 4 }
|
||
|
||
hwBatteryLogTestBatteryStatus OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
expectant(1),
|
||
unexpected(2),
|
||
unknown(3)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery status.
|
||
Options:
|
||
1. expectant(1) - indicates the batter test state is expectant
|
||
2. unexpected(2) - indicates the batter test state is unexpected
|
||
3. unknown(3) - indicates the batter test state is unknown
|
||
"
|
||
::= { hwBatteryLogTestEntry 5 }
|
||
|
||
hwBatteryLogTestTotalDischargeAH OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "mAH"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"
|
||
Discharge cumulate AH.
|
||
Unit: mAH
|
||
"
|
||
::= { hwBatteryLogTestEntry 6 }
|
||
|
||
hwBatteryLogTestFinish OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
testing(1),
|
||
completed(2),
|
||
alarmTerminated (3),
|
||
hostTerminated(4),
|
||
overtimeTerminated(5),
|
||
notTest(6)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery Test result.
|
||
Options:
|
||
1. testing(1) - indicates that it is during testing
|
||
2. completed(2) - indicates that the test is completed normally
|
||
3. alarmTerminated(3) - indicates that the test is stopped by alarms
|
||
4. hostTerminated(4) - indicates that the test is stopped by the host
|
||
5. overtimeTerminated(5) - indicates that the test is stopped because of over 100 hours
|
||
6. notTest(6) - indicates that the test is not started
|
||
"
|
||
::= { hwBatteryLogTestEntry 7 }
|
||
|
||
hwBatteryLogTestEfficiency OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "percent"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"
|
||
The information of battery test efficiency.
|
||
"
|
||
::= { hwBatteryLogTestEntry 8 }
|
||
|
||
hwBatteryLogTestBatteryTemperature OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "0.01 Degree"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery discharge test end Temperature.
|
||
Unit: 0.01 Degree
|
||
"
|
||
::= { hwBatteryLogTestEntry 9 }
|
||
|
||
hwBatteryLogTestBatteryCurrent OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "mA"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery discharge test average Current.
|
||
Unit: mA
|
||
"
|
||
::= { hwBatteryLogTestEntry 10 }
|
||
|
||
hwRemoteProvidePowerInfoTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwRemoteProvidePowerInfoEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Remote provide power basic information table.
|
||
The indexes of this table are hwEnvEmuIndex and hwPowerIndex.
|
||
hwEnvEmuIndex is the index of the monitored unit,
|
||
and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
|
||
"
|
||
::= { hwPowerMonObjects 7 }
|
||
|
||
hwRemoteProvidePowerInfoEntry OBJECT-TYPE
|
||
SYNTAX HwRemoteProvidePowerInfoEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Remote provide power basic information table.
|
||
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
|
||
hwEnvEmuIndex is the index of the monitored unit,
|
||
and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
|
||
"
|
||
INDEX { hwEnvEmuIndex,hwPowerIndex }
|
||
::= { hwRemoteProvidePowerInfoTable 1 }
|
||
|
||
HwRemoteProvidePowerInfoEntry ::=
|
||
SEQUENCE {
|
||
hwPowerCentralState
|
||
INTEGER,
|
||
hwPowerCentralDCInPutState
|
||
INTEGER,
|
||
hwPowerCentralDCOutputState
|
||
INTEGER,
|
||
hwPowerCentralDCOutputMode
|
||
INTEGER,
|
||
hwPowerRemoteCommState
|
||
INTEGER,
|
||
hwPowerRemoteDCInputState
|
||
INTEGER,
|
||
hwPowerRemoteLineCurState
|
||
INTEGER,
|
||
hwPowerRemotePowerState
|
||
INTEGER,
|
||
hwPowerRemoteLineState
|
||
BITS,
|
||
hwPowerCentralLoadState
|
||
INTEGER
|
||
}
|
||
|
||
hwPowerCentralState OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
temOver(2)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of the central module.
|
||
Options:
|
||
1. normal(1) - indicates the normal state
|
||
2. temOver(2) - indicates the over-temperature
|
||
"
|
||
::= { hwRemoteProvidePowerInfoEntry 1 }
|
||
|
||
hwPowerCentralDCInPutState OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
lack(2),
|
||
over(3)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of central module DC input:
|
||
Options:
|
||
1.normal(1) - indicates the normal state
|
||
2.lack(2) - indicates the voltage underflow
|
||
3.over(3) - indicates the voltage overflow
|
||
"
|
||
::= { hwRemoteProvidePowerInfoEntry 2}
|
||
|
||
hwPowerCentralDCOutputState OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
volLack(2),
|
||
volOver(3),
|
||
loadOver(4),
|
||
shortCircuit(5),
|
||
noLoad(6)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of central module DC output.
|
||
Options:
|
||
1. normal(1) - indicates the normal state
|
||
2. volLack(2) - indicates the voltage underflow
|
||
3. volOver(3) - indicates the voltage overflow
|
||
4. loadOver(4) - indicates the over-loading
|
||
5. shortCircuit(5) - indicates the short circuit
|
||
6. noLoad(6) - indicates no load
|
||
"
|
||
::= { hwRemoteProvidePowerInfoEntry 3 }
|
||
|
||
hwPowerCentralDCOutputMode OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
highVolMode(1),
|
||
lowVolMode(2)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Mode of central module DC output.
|
||
Options:
|
||
1. highVolMode(1) - indicates the high voltage output mode
|
||
2. lowVolMode(2) - indicates the low voltage output mode
|
||
"
|
||
::= { hwRemoteProvidePowerInfoEntry 4 }
|
||
|
||
hwPowerRemoteCommState OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
revfault(2),
|
||
sendfault(3)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Remote power module communications state.
|
||
Options:
|
||
1. normal(1) - indicates the normal state
|
||
2. revfault(2) - indicates the receiving of fault
|
||
3. sendfault(3) - indicates the sending of fault"
|
||
::= { hwRemoteProvidePowerInfoEntry 5 }
|
||
|
||
hwPowerRemoteDCInputState OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
lack(2)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of remote module DC input.
|
||
Options:
|
||
1. normal(1) - indicates the normal state
|
||
2. lack(2) - indicates that the voltage is underflow
|
||
"
|
||
::= { hwRemoteProvidePowerInfoEntry 6 }
|
||
|
||
hwPowerRemoteLineCurState OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
cablejoining(2),
|
||
curLeakage(3),
|
||
curOver(4)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"state of line between central and remote module.
|
||
Options:
|
||
1.normal(1) - indicates the normal state
|
||
2.cablejoining(2) - indicates the cable joining
|
||
3.curLeakage(3) - indicates the cur Leakage
|
||
4.curOver(4) - indicates the cur Over
|
||
"
|
||
::= { hwRemoteProvidePowerInfoEntry 7 }
|
||
|
||
hwPowerRemotePowerState OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
fault(2)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"state of remote UA60 power.
|
||
Options:
|
||
1. normal(1) - indicates the normal state
|
||
2. fault(2) - indicates the faulty state
|
||
"
|
||
::= { hwRemoteProvidePowerInfoEntry 8 }
|
||
|
||
hwPowerRemoteLineState OBJECT-TYPE
|
||
SYNTAX BITS
|
||
{
|
||
u1state(0),
|
||
u2state(1),
|
||
u3state(2),
|
||
u4state(3),
|
||
a1state(4),
|
||
a2state(5),
|
||
a3state(6),
|
||
a4state(7)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"State of line U1.
|
||
Options:
|
||
1. u1state(0) - indicates the power remote line state is u1 state
|
||
2. u2state(1) - indicates the power remote line state is u2 state
|
||
3. u3state(2) - indicates the power remote line state is u3 state
|
||
4. u4state(3) - indicates the power remote line state is u4 state
|
||
5. a1state(4) - indicates the power remote line state is a1 state
|
||
6. a2state(5) - indicates the power remote line state is a2 state
|
||
7. a3state(6) - indicates the power remote line state is a3 state
|
||
8. a4state(7) - indicates the power remote line state is a4 state
|
||
"
|
||
::= { hwRemoteProvidePowerInfoEntry 9 }
|
||
|
||
hwPowerCentralLoadState OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(1),
|
||
overload(2),
|
||
nonload(3)
|
||
}
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"state of central load.
|
||
Options:
|
||
1. normal(1) - indicates the normal state
|
||
2. overload(2) - indicates overload
|
||
3. nonload(3) - indicates non-load
|
||
"
|
||
::= { hwRemoteProvidePowerInfoEntry 10 }
|
||
|
||
|
||
hwPowerMibTrap OBJECT IDENTIFIER ::= { hwPower 2 }
|
||
|
||
hwPowerTrapOid OBJECT IDENTIFIER ::= { hwPowerMibTrap 1 }
|
||
|
||
hwPowerTrapsDefine OBJECT IDENTIFIER ::= { hwPowerMibTrap 2 }
|
||
|
||
hwPowerTraps OBJECT IDENTIFIER ::= { hwPowerTrapsDefine 0 }
|
||
|
||
powerConnFaultAlarm NOTIFICATION-TYPE
|
||
OBJECTS {hwEnvEmuIndex, hwPowerIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
" This trap message is reported when the communication between
|
||
the power module and the monitoring board is fault."
|
||
::= { hwPowerTraps 1 }
|
||
|
||
powerConnFaultAlarmResume NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the communication between
|
||
the power module and the monitoring board resumes."
|
||
::= { hwPowerTraps 2 }
|
||
|
||
acInputVoltageAlarm NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwACLoopIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when there is a exception of AC input voltage."
|
||
::= { hwPowerTraps 3 }
|
||
|
||
acInputVoltageAlarmResume NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwACLoopIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the state of AC input voltage resumes."
|
||
::= { hwPowerTraps 4 }
|
||
|
||
acInputVoltageHighAlarm NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwACLoopIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the input voltage is too high."
|
||
::= { hwPowerTraps 5 }
|
||
|
||
acInputVoltageHighAlarmResume NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwACLoopIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the input voltage
|
||
resumes to the normal range from a high value."
|
||
::= { hwPowerTraps 6 }
|
||
|
||
acInputVoltageLowAlarm NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwACLoopIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the input voltage is too low."
|
||
::= { hwPowerTraps 7 }
|
||
|
||
acInputVoltageLowAlarmResume NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwACLoopIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the input voltage
|
||
resumes to the normal range from a low value."
|
||
::= { hwPowerTraps 8 }
|
||
|
||
dcOutputVoltageHighAlarm NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the output voltage is too high."
|
||
::= { hwPowerTraps 9 }
|
||
|
||
dcOutputVoltageHighAlarmResume NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the output voltage
|
||
resumes to the normal range from a high value."
|
||
::= { hwPowerTraps 10 }
|
||
|
||
dcOutputCurrentHighAlarm NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the output current is too high."
|
||
::= { hwPowerTraps 11 }
|
||
|
||
dcOutputCurrentHighAlarmResume NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the output current
|
||
resumes to the normal range from a high value."
|
||
::= { hwPowerTraps 12 }
|
||
|
||
dcOutputVoltageLowAlarm NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the output voltage is too low."
|
||
::= { hwPowerTraps 13 }
|
||
|
||
dcOutputVoltageLowAlarmResume NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the output voltage
|
||
resumes to the normal range from a low value."
|
||
::= { hwPowerTraps 14 }
|
||
|
||
dcOutputCurrentLowAlarm NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the output current is too low."
|
||
::= { hwPowerTraps 15 }
|
||
|
||
dcOutputCurrentLowAlarmResume NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the output current
|
||
resumes to the normal range from a low value."
|
||
::= { hwPowerTraps 16 }
|
||
|
||
overLoadPowerAbnormalAlarm NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the state of load power is abnormal."
|
||
::= { hwPowerTraps 17 }
|
||
|
||
overLoadPowerAbnormalAlarmResume NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the state of load power recovers to normal."
|
||
::= { hwPowerTraps 18 }
|
||
|
||
overBattPowerOffAlarm NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the battery is powered off."
|
||
::= { hwPowerTraps 19 }
|
||
|
||
overBattPowerOffAlarmResume NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the battery is powered on."
|
||
::= { hwPowerTraps 20 }
|
||
|
||
overLoadPowerOffAlarm NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the loadpower is powered off."
|
||
::= { hwPowerTraps 21 }
|
||
|
||
overLoadPowerOffAlarmResume NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the loadpower is powered on."
|
||
::= { hwPowerTraps 22 }
|
||
|
||
acMainsSupplyAlarm NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwACLoopIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the AC mains supply is abnormal."
|
||
::= { hwPowerTraps 23 }
|
||
|
||
acMainsSupplyAlarmResume NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwACLoopIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the AC mains supply recovers to normal."
|
||
::= { hwPowerTraps 24 }
|
||
|
||
batteryLoopAlarm NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwBatteryIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the loop of battery group disconnects."
|
||
::= { hwPowerTraps 25 }
|
||
|
||
batteryLoopAlarmResume NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwBatteryIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the loop of battery group connects."
|
||
::= { hwPowerTraps 26 }
|
||
|
||
batteryFuseAlarm NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwBatteryIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the fuse of battery group disconnects."
|
||
::= { hwPowerTraps 27 }
|
||
|
||
batteryFuseAlarmResume NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwBatteryIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the fuse of battery group connects. "
|
||
::= { hwPowerTraps 28 }
|
||
|
||
batteryContachAlarm NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwBatteryIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the contactor of battery group disconnects."
|
||
::= { hwPowerTraps 29 }
|
||
|
||
batteryContachAlarmResume NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwBatteryIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the contactor of battery group connects."
|
||
::= { hwPowerTraps 30 }
|
||
|
||
userModuleOffAlarm NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the user module is powered off."
|
||
::= { hwPowerTraps 31 }
|
||
|
||
userModuleOffAlarmResume NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the user module is powered on."
|
||
::= { hwPowerTraps 32 }
|
||
|
||
transferModuleOffAlarm NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the transfer module is powered off."
|
||
::= { hwPowerTraps 33 }
|
||
|
||
transferModuleOffAlarmResume NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the transfer module is powered on."
|
||
::= { hwPowerTraps 34 }
|
||
|
||
userModuleSwitchAlarm NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the user module is switched off."
|
||
::= { hwPowerTraps 35 }
|
||
|
||
transferModuleSwitchAlarm NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the transfer module is switched off."
|
||
::= { hwPowerTraps 37 }
|
||
|
||
loadFuseAlarm NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the load fuse is abnormal."
|
||
::= { hwPowerTraps 39 }
|
||
|
||
loadFuseAlarmResume NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the load fuse resumes."
|
||
::= { hwPowerTraps 40 }
|
||
|
||
chargeCtrlStateAlarm NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the control state of average or floating charge converts."
|
||
::= { hwPowerTraps 41 }
|
||
|
||
chargeModeAlarm NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the charge state converts."
|
||
::= { hwPowerTraps 42 }
|
||
|
||
acCommFailAlarm NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the AC panel communication fails."
|
||
::= { hwPowerTraps 43 }
|
||
|
||
acCommFailAlarmResume NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the AC panel communication resumes."
|
||
::= { hwPowerTraps 44 }
|
||
|
||
batteryChargeOverAlarm NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwBatteryIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the Over-current of battery group happens."
|
||
::= { hwPowerTraps 45 }
|
||
|
||
batteryChargeOverAlarmResume NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwBatteryIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"OThis trap message is reported when the Over-current of battery group resumes."
|
||
::= { hwPowerTraps 46 }
|
||
|
||
batteryVoltageLackAlarm NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwBatteryIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the voltage of battery group lacks."
|
||
::= { hwPowerTraps 47 }
|
||
|
||
batteryVoltageLackAlarmResume NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwBatteryIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the voltage of battery group recovers from lack."
|
||
::= { hwPowerTraps 48 }
|
||
|
||
loadTwiceOffAlarm NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the load is powered off twice."
|
||
::= { hwPowerTraps 49 }
|
||
|
||
loadTwiceOffAlarmResume NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the load recovers from powering off twice."
|
||
::= { hwPowerTraps 50 }
|
||
|
||
loadOnceOffAlarm NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwBatteryIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the load is powered off once."
|
||
::= { hwPowerTraps 51 }
|
||
|
||
loadOnceOffAlarmResume NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwBatteryIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the load recovers from powering off once."
|
||
::= { hwPowerTraps 52 }
|
||
|
||
acInputPowerOffAlarm NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the AC input is powered off."
|
||
::= { hwPowerTraps 53 }
|
||
|
||
acInputPowerOffAlarmResume NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the AC input power is powered off."
|
||
::= { hwPowerTraps 54 }
|
||
|
||
acInputLoopSwtichAlarm NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the AC input loop switches to another one."
|
||
::= { hwPowerTraps 55 }
|
||
|
||
batteryDischargeTestStartAlarm NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the battery discharge test starts."
|
||
::= { hwPowerTraps 56 }
|
||
|
||
batteryDischargeTestStopAlarm NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the battery discharge test stops."
|
||
::= { hwPowerTraps 57 }
|
||
|
||
powerProtectAlarm NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the power protection function is enbaled."
|
||
::= { hwPowerTraps 58 }
|
||
|
||
powerUndoProtectAlarm NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the power protection function is disabled."
|
||
::= { hwPowerTraps 59 }
|
||
|
||
powerCentralOutputModeSwtichAlarm NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the central output mode swtiches to another one."
|
||
::= { hwPowerTraps 60 }
|
||
|
||
powerCentralTempretaureAlarm NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the central tempretaure is abnormal."
|
||
::= { hwPowerTraps 61 }
|
||
|
||
powerCentralInputAlarm NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the central input voltage is abnormal."
|
||
::= { hwPowerTraps 62 }
|
||
|
||
powerCentralOutputAlarm NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the central output voltage is abnormal."
|
||
::= { hwPowerTraps 63 }
|
||
|
||
powerRemoteCommFaultAlarm NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the communiction between the remote and central fails."
|
||
::= { hwPowerTraps 64 }
|
||
|
||
powerRemoteVoltageAlarm NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the remote voltage is abnormal."
|
||
::= { hwPowerTraps 65}
|
||
|
||
powerLineAlarm NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the power line is abnormal."
|
||
::= { hwPowerTraps 66 }
|
||
|
||
powerRemotePowerAlarm1 NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the remote power is abnormal."
|
||
::= { hwPowerTraps 67 }
|
||
|
||
powerRemotePowerAlarm2 NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the Line UA is abnormal."
|
||
::= { hwPowerTraps 68 }
|
||
|
||
powerRemotePowerAlarm3 NOTIFICATION-TYPE
|
||
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This trap message is reported when the Central load is abnormal."
|
||
::= { hwPowerTraps 69 }
|
||
|
||
hwACInfomationTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF HwACInfomationEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"AC infomation table. The table is not supported.
|
||
The indexes of this table are hwEnvEmuIndex and hwPowerIndex."
|
||
::= { hwPowerMonObjects 8 }
|
||
|
||
hwACInfomationEntry OBJECT-TYPE
|
||
SYNTAX HwACInfomationEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"AC infomation table. The table is not supported.
|
||
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex."
|
||
INDEX { hwEnvEmuIndex, hwPowerIndex }
|
||
::= { hwACInfomationTable 1 }
|
||
|
||
HwACInfomationEntry ::=
|
||
SEQUENCE {
|
||
hwACInfoCommState
|
||
INTEGER,
|
||
hwACInfoThunderState
|
||
INTEGER,
|
||
hwACInfoCurrentLoop
|
||
Integer32,
|
||
hwACInfoMCBTrigger
|
||
INTEGER,
|
||
hwACInfoFrequency
|
||
Integer32,
|
||
hwACInfoRowStatus
|
||
RowStatus
|
||
}
|
||
|
||
hwACInfoCommState OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(0),
|
||
fault(1)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"communication state of AC input module.
|
||
The node is not supported.
|
||
Options:
|
||
1. normal(0) - indicates the communication state of AC is normal
|
||
2. fault(1) - indicates the communication state of AC is fault
|
||
"
|
||
::= { hwACInfomationEntry 1 }
|
||
|
||
hwACInfoThunderState OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(0),
|
||
fault(1)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Thunder's state.
|
||
The node is not supported.
|
||
Options:
|
||
1. normal(0) - indicates the state of Thunder is normal
|
||
2. fault(1) - indicates the state of Thunder is fault
|
||
"
|
||
::= { hwACInfomationEntry 2 }
|
||
|
||
hwACInfoCurrentLoop OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Current AC input working loop.
|
||
The leaf is not supported.
|
||
"
|
||
::= { hwACInfomationEntry 3 }
|
||
|
||
hwACInfoMCBTrigger OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
{
|
||
normal(0),
|
||
break-down(1)
|
||
}
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"AC input MCB trigger state.
|
||
The leaf is not supported.
|
||
Options:
|
||
1. normal(0) - indicates the AC input MCB trigger state is normal
|
||
2. break-down(1)- indicates the AC input MCB trigger state is break-down
|
||
"
|
||
::= { hwACInfomationEntry 4 }
|
||
|
||
hwACInfoFrequency OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "HZ"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The infomation of AC input frequency.
|
||
This leaf is not supported.
|
||
Unit: HZ
|
||
"
|
||
::= { hwACInfomationEntry 5 }
|
||
|
||
hwACInfoRowStatus OBJECT-TYPE
|
||
SYNTAX RowStatus
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"RowStatus standard operation
|
||
The leaf is not supported.
|
||
"
|
||
::= { hwACInfomationEntry 6 }
|
||
|
||
powerConformance OBJECT IDENTIFIER ::= { hwPower 3 }
|
||
|
||
powerCompliances OBJECT IDENTIFIER ::= { powerConformance 1 }
|
||
|
||
powerGroups OBJECT IDENTIFIER ::= { powerConformance 2 }
|
||
|
||
hwEnvironPowerTraps OBJECT IDENTIFIER ::= { hwPower 4 }
|
||
|
||
hwEnvironPowerCommonTraps OBJECT IDENTIFIER ::= { hwEnvironPowerTraps 1 }
|
||
|
||
hwEnvironPowerAlarmTraps OBJECT IDENTIFIER ::= { hwEnvironPowerTraps 2 }
|
||
|
||
hwEnvironPowerAlarmTrapsPrefix OBJECT IDENTIFIER ::= { hwEnvironPowerAlarmTraps 0 }
|
||
|
||
hwEmmPowerBattaryTestStartTrap NOTIFICATION-TYPE
|
||
OBJECTS {
|
||
hwFrameIndex,
|
||
hwEnvEmuIndex,
|
||
hwPowerIndex,
|
||
hwEnvEmuType,
|
||
hwPowerType
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The agent generates this trap when the power
|
||
device battary discharge test starts.
|
||
"
|
||
::= { hwEnvironPowerAlarmTrapsPrefix 1 }
|
||
|
||
hwEmmPowerBattaryTestStopTrap NOTIFICATION-TYPE
|
||
OBJECTS {
|
||
hwFrameIndex,
|
||
hwEnvEmuIndex,
|
||
hwPowerIndex,
|
||
hwEnvEmuType,
|
||
hwPowerType,
|
||
hwBatteryLogTestBatteryStatus,
|
||
hwBatteryLogTestEfficiency
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The agent generates this trap when the power
|
||
device battary discharge test ends.
|
||
"
|
||
::= { hwEnvironPowerAlarmTrapsPrefix 2 }
|
||
|
||
hwEmmPowerAcvolFaultTrap NOTIFICATION-TYPE
|
||
OBJECTS {
|
||
hwFrameIndex,
|
||
hwEnvEmuIndex,
|
||
hwPowerIndex,
|
||
hwACLoopIndex,
|
||
hwEnvEmuType,
|
||
hwPowerType
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The agent generates this trap when the power
|
||
device AC input voltage is abnormal.
|
||
"
|
||
::= { hwEnvironPowerAlarmTrapsPrefix 3 }
|
||
|
||
hwEmmPowerAcvolRecoverTrap NOTIFICATION-TYPE
|
||
OBJECTS {
|
||
hwFrameIndex,
|
||
hwEnvEmuIndex,
|
||
hwPowerIndex,
|
||
hwACLoopIndex,
|
||
hwEnvEmuType,
|
||
hwPowerType
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The agent generates this trap when the power
|
||
device AC input voltage recovers.
|
||
"
|
||
::= { hwEnvironPowerAlarmTrapsPrefix 4 }
|
||
|
||
hwEmmPowerDcvolFaultTrap NOTIFICATION-TYPE
|
||
OBJECTS {
|
||
hwFrameIndex,
|
||
hwEnvEmuIndex,
|
||
hwPowerIndex,
|
||
hwEnvEmuType,
|
||
hwPowerType
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The agent generates this trap when the power
|
||
device DC output voltage is abnormal.
|
||
"
|
||
::= { hwEnvironPowerAlarmTrapsPrefix 5 }
|
||
|
||
hwEmmPowerDcvolRecoverTrap NOTIFICATION-TYPE
|
||
OBJECTS {
|
||
hwFrameIndex,
|
||
hwEnvEmuIndex,
|
||
hwPowerIndex,
|
||
hwEnvEmuType,
|
||
hwPowerType
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The agent generates this trap when the power
|
||
device DC output voltage recovers.
|
||
"
|
||
::= { hwEnvironPowerAlarmTrapsPrefix 6 }
|
||
|
||
hwEmmPowerBattloopFaultTrap NOTIFICATION-TYPE
|
||
OBJECTS {
|
||
hwFrameIndex,
|
||
hwEnvEmuIndex,
|
||
hwPowerIndex,
|
||
hwBatteryIndex,
|
||
hwEnvEmuType,
|
||
hwPowerType
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The agent generates this trap when the power
|
||
device the battery loop is broken.
|
||
In this case, the function of he backup power is lost.
|
||
"
|
||
::= { hwEnvironPowerAlarmTrapsPrefix 7 }
|
||
|
||
hwEmmPowerBattloopRecoverTrap NOTIFICATION-TYPE
|
||
OBJECTS {
|
||
hwFrameIndex,
|
||
hwEnvEmuIndex,
|
||
hwPowerIndex,
|
||
hwBatteryIndex,
|
||
hwEnvEmuType,
|
||
hwPowerType
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The agent generates this trap when the power
|
||
device battery loop recovers.
|
||
"
|
||
::= { hwEnvironPowerAlarmTrapsPrefix 8 }
|
||
|
||
hwEmmPowerLoadfuseFaultTrap NOTIFICATION-TYPE
|
||
OBJECTS {
|
||
hwFrameIndex,
|
||
hwEnvEmuIndex,
|
||
hwPowerIndex,
|
||
hwLoadIndex,
|
||
hwEnvEmuType,
|
||
hwPowerType
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The agent generates this trap when the fuse of the power device
|
||
is broken. In this case, the device is powered off.
|
||
"
|
||
::= { hwEnvironPowerAlarmTrapsPrefix 9 }
|
||
|
||
hwEmmPowerLoadfuseRecoverTrap NOTIFICATION-TYPE
|
||
OBJECTS {
|
||
hwFrameIndex,
|
||
hwEnvEmuIndex,
|
||
hwPowerIndex,
|
||
hwLoadIndex,
|
||
hwEnvEmuType,
|
||
hwPowerType
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The agent generates this trap when the fuse of the power
|
||
device recovers.
|
||
"
|
||
::= { hwEnvironPowerAlarmTrapsPrefix 10 }
|
||
|
||
hwEmmPowerRectifierFaultTrap NOTIFICATION-TYPE
|
||
OBJECTS {
|
||
hwFrameIndex,
|
||
hwEnvEmuIndex,
|
||
hwPowerIndex,
|
||
hwRectifierIndex,
|
||
hwEnvEmuType,
|
||
hwPowerType
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The agent generates this trap when the rectifier
|
||
module of the power device is abnormal and the spully power may decrease.
|
||
"
|
||
::= { hwEnvironPowerAlarmTrapsPrefix 11 }
|
||
|
||
hwEmmPowerRectifierRecoverTrap NOTIFICATION-TYPE
|
||
OBJECTS {
|
||
hwFrameIndex,
|
||
hwEnvEmuIndex,
|
||
hwPowerIndex,
|
||
hwRectifierIndex,
|
||
hwEnvEmuType,
|
||
hwPowerType
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The agent generates this trap when the rectifier module of the
|
||
power device recovers.
|
||
"
|
||
::= { hwEnvironPowerAlarmTrapsPrefix 12 }
|
||
|
||
hwEmmDigMainsupplyFaultTrap NOTIFICATION-TYPE
|
||
OBJECTS
|
||
{
|
||
hwFrameIndex,
|
||
hwEnvEmuIndex,
|
||
hwDigChannelIndex,
|
||
hwEnvEmuType,
|
||
hwPowerType
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The agent generates this trap when the
|
||
main supply digital is faulty.
|
||
"
|
||
::= { hwEnvironPowerAlarmTrapsPrefix 13 }
|
||
|
||
hwEmmDigMainsupplyRecoverTrap NOTIFICATION-TYPE
|
||
OBJECTS
|
||
{
|
||
hwFrameIndex,
|
||
hwEnvEmuIndex,
|
||
hwDigChannelIndex,
|
||
hwEnvEmuType,
|
||
hwPowerType
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The agent generates this trap when the
|
||
main supply digital recovers.
|
||
"
|
||
::= { hwEnvironPowerAlarmTrapsPrefix 14 }
|
||
|
||
hwEmmPowerBatteryOffTrap NOTIFICATION-TYPE
|
||
OBJECTS {
|
||
hwFrameIndex,
|
||
hwEnvEmuIndex,
|
||
hwPowerIndex,
|
||
hwEnvEmuType,
|
||
hwPowerType
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The agent generates this trap when the power
|
||
of battary is off.
|
||
"
|
||
::= { hwEnvironPowerAlarmTrapsPrefix 15 }
|
||
|
||
hwEmmBatt1TempFaultTrap NOTIFICATION-TYPE
|
||
OBJECTS
|
||
{
|
||
hwFrameIndex,
|
||
hwEnvEmuIndex,
|
||
hwPowerIndex,
|
||
hwEnvEmuType,
|
||
hwPowerType
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The agent generates this trap when the
|
||
battery group 1 temperature sensor fault
|
||
occurs.
|
||
"
|
||
::= { hwEnvironPowerAlarmTrapsPrefix 16 }
|
||
|
||
hwEmmBatt1TempRestoreTrap NOTIFICATION-TYPE
|
||
OBJECTS
|
||
{
|
||
hwFrameIndex,
|
||
hwEnvEmuIndex,
|
||
hwPowerIndex,
|
||
hwEnvEmuType,
|
||
hwPowerType
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The agent generates this trap when the
|
||
battery group 1 temperature sensor fault
|
||
recovers.
|
||
"
|
||
::= { hwEnvironPowerAlarmTrapsPrefix 17 }
|
||
|
||
hwEmmEnviHumFaultTrap NOTIFICATION-TYPE
|
||
OBJECTS
|
||
{
|
||
hwFrameIndex,
|
||
hwEnvEmuIndex,
|
||
hwPowerIndex,
|
||
hwEnvEmuType,
|
||
hwPowerType
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The agent generates this trap when the
|
||
environment humidity sensor fault occurs.
|
||
"
|
||
::= { hwEnvironPowerAlarmTrapsPrefix 18 }
|
||
|
||
hwEmmEnviHumRestoreTrap NOTIFICATION-TYPE
|
||
OBJECTS
|
||
{
|
||
hwFrameIndex,
|
||
hwEnvEmuIndex,
|
||
hwPowerIndex,
|
||
hwEnvEmuType,
|
||
hwPowerType
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The agent generates this trap when the
|
||
environment humidity sensor fault recovers.
|
||
"
|
||
::= { hwEnvironPowerAlarmTrapsPrefix 19 }
|
||
|
||
hwEmmEnvi1TempFaultTrap NOTIFICATION-TYPE
|
||
OBJECTS
|
||
{
|
||
hwFrameIndex,
|
||
hwEnvEmuIndex,
|
||
hwPowerIndex,
|
||
hwEnvEmuType,
|
||
hwPowerType
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The agent generates this trap when the
|
||
environment 1 temperature sensor fault
|
||
occurs.
|
||
"
|
||
::= { hwEnvironPowerAlarmTrapsPrefix 20 }
|
||
|
||
hwEmmEnvi1TempRestoreTrap NOTIFICATION-TYPE
|
||
OBJECTS
|
||
{
|
||
hwFrameIndex,
|
||
hwEnvEmuIndex,
|
||
hwPowerIndex,
|
||
hwEnvEmuType,
|
||
hwPowerType
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The agent generates this trap when the
|
||
environment 1 temperature sensor fault
|
||
recovers.
|
||
"
|
||
::= { hwEnvironPowerAlarmTrapsPrefix 21 }
|
||
|
||
hwEmmBattTemFaultTrap NOTIFICATION-TYPE
|
||
OBJECTS
|
||
{
|
||
hwFrameIndex,
|
||
hwEnvEmuIndex,
|
||
hwPowerIndex,
|
||
hwEnvEmuType,
|
||
hwPowerType
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The agent generates this trap when the battery
|
||
temperature out of normal range.
|
||
"
|
||
::= { hwEnvironPowerAlarmTrapsPrefix 22 }
|
||
|
||
hwEmmBattTemRecoverTrap NOTIFICATION-TYPE
|
||
OBJECTS
|
||
{
|
||
hwFrameIndex,
|
||
hwEnvEmuIndex,
|
||
hwPowerIndex,
|
||
hwEnvEmuType,
|
||
hwPowerType
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The agent generates this trap when the battery
|
||
temperature recovers to normal range.
|
||
"
|
||
::= { hwEnvironPowerAlarmTrapsPrefix 23 }
|
||
|
||
hwEmmPowerBatteryOffRecoverTrap NOTIFICATION-TYPE
|
||
OBJECTS {
|
||
hwFrameIndex,
|
||
hwEnvEmuIndex,
|
||
hwPowerIndex,
|
||
hwEnvEmuType,
|
||
hwPowerType
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The agent generates this trap when the power
|
||
of battary recovers to on state.
|
||
"
|
||
::= { hwEnvironPowerAlarmTrapsPrefix 24 }
|
||
|
||
hwEmmPowerBatteryUnDetectTrap NOTIFICATION-TYPE
|
||
OBJECTS
|
||
{
|
||
hwFrameIndex,
|
||
hwEnvEmuIndex,
|
||
hwPowerIndex,
|
||
hwEnvEmuType,
|
||
hwPowerType
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The agent generates this trap when the
|
||
one or more batteries are not detected.
|
||
"
|
||
::= { hwEnvironPowerAlarmTrapsPrefix 25 }
|
||
|
||
hwEmmPowerBatteryDetectRecoverTrap NOTIFICATION-TYPE
|
||
OBJECTS
|
||
{
|
||
hwFrameIndex,
|
||
hwEnvEmuIndex,
|
||
hwPowerIndex,
|
||
hwEnvEmuType,
|
||
hwPowerType
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The agent generates this trap when the
|
||
batteries recover.
|
||
"
|
||
::= { hwEnvironPowerAlarmTrapsPrefix 26 }
|
||
|
||
hwPowerModuleMismatchTrap NOTIFICATION-TYPE
|
||
OBJECTS
|
||
{
|
||
hwFrameIndex,
|
||
hwEnvEmuIndex,
|
||
hwPowerIndex,
|
||
hwEnvEmuType,
|
||
hwPowerType
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The agent generates this trap when the
|
||
the power supply system detects mismatched power module .
|
||
"
|
||
::= { hwEnvironPowerAlarmTrapsPrefix 27 }
|
||
|
||
hwPowerModuleRestoreTrap NOTIFICATION-TYPE
|
||
OBJECTS
|
||
{
|
||
hwFrameIndex,
|
||
hwEnvEmuIndex,
|
||
hwPowerIndex,
|
||
hwEnvEmuType,
|
||
hwPowerType
|
||
}
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The agent generates this trap when the power module recovers.
|
||
"
|
||
::= { hwEnvironPowerAlarmTrapsPrefix 28 }
|
||
END
|