-- HUAWEI-SITE-MONITOR-MIB.mib
|
|
-- MIB generated by MG-SOFT Visual MIB Builder Version 4.0 Build 347
|
|
-- Wednesday, March 30, 2011 at 11:17:42
|
|
--
|
|
|
|
-- HUAWEI-NGPOWER-MIB.mib
|
|
-- MIB generated by MG-SOFT Visual MIB Builder Version 3.0 Build 253
|
|
-- Sunday, June 14, 2009 at 11:04:12
|
|
--
|
|
|
|
HUAWEI-SITE-MONITOR-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
huaweiUtility
|
|
FROM HUAWEI-MIB
|
|
OBJECT-GROUP, NOTIFICATION-GROUP
|
|
FROM SNMPv2-CONF
|
|
Integer32, Unsigned32, OBJECT-TYPE, MODULE-IDENTITY, NOTIFICATION-TYPE
|
|
FROM SNMPv2-SMI
|
|
TEXTUAL-CONVENTION
|
|
FROM SNMPv2-TC;
|
|
|
|
|
|
-- September 15, 2010 at 11:00 GMT
|
|
hwSiteMonitorMIB MODULE-IDENTITY
|
|
LAST-UPDATED "201103040000Z" -- March 04, 2011 at 00:00 GMT
|
|
ORGANIZATION
|
|
"Huawei Technologies Co.,Ltd."
|
|
CONTACT-INFO
|
|
"Floor 5, Block 4, R&D Building,
|
|
Huawei Longgang Production Base,
|
|
Shenzhen, P.R.C.
|
|
http://www.huawei.com
|
|
Zip: 518129."
|
|
DESCRIPTION
|
|
"Site Monitor MIB defines MIB objects which provides load and backup management, patch management NMS interfaces.
|
|
The current version is V1.01"
|
|
REVISION "201103040000Z" -- March 04, 2011 at 00:00 GMT
|
|
DESCRIPTION
|
|
"Add hwAcOffLongTimeAlarmTraps, hwAcOffLongTimeAlarmResumeTraps"
|
|
REVISION "201010310000Z" -- October 31, 2010 at 00:00 GMT
|
|
DESCRIPTION
|
|
"Huawei site monitor mib V1.00"
|
|
::= { huaweiUtility 164 }
|
|
|
|
|
|
|
|
--
|
|
-- Textual conventions
|
|
--
|
|
|
|
DisplayString ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
SYNTAX OCTET STRING (SIZE (1..64))
|
|
|
|
RowStatus ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
SYNTAX INTEGER
|
|
{
|
|
active(1),
|
|
notInService(2),
|
|
notReady(3),
|
|
createAndGo(4),
|
|
createAndWait(5),
|
|
destroy(6)
|
|
}
|
|
|
|
-- Textual conventions
|
|
--
|
|
DateAndTime ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
SYNTAX OCTET STRING (SIZE (8..11))
|
|
|
|
RunStatus ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This integer value represents running status of the system.
|
|
Depending on situation there may be limits on allowed values.
|
|
Operational values:
|
|
(1) unknown - status has not yet been defined
|
|
(2) normal - there are no activated alarms
|
|
(3) alarm - alarm status
|
|
"
|
|
SYNTAX INTEGER
|
|
{
|
|
unknow(1),
|
|
normal(2),
|
|
alarm(3)
|
|
}
|
|
|
|
MeasuresRange ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
SYNTAX Integer32
|
|
|
|
TruthValue ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
SYNTAX INTEGER
|
|
{
|
|
true(1),
|
|
flase(2)
|
|
}
|
|
|
|
|
|
--
|
|
-- Node definitions
|
|
--
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1
|
|
hwSiteMonitorMIBObjects OBJECT IDENTIFIER ::= { hwSiteMonitorMIB 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.1
|
|
hwSiteInfo OBJECT IDENTIFIER ::= { hwSiteMonitorMIBObjects 1 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.1.1
|
|
hwSiteSummary OBJECT IDENTIFIER ::= { hwSiteInfo 1 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.1.1.1
|
|
hwSiteId OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Site ID, default value: 000,000.
|
|
Naming rule of the site device ID (six digits): The first three digits indicate the device name and the last three digits indicate the serial number (SN) of the device. If the last three digits are 000, it indicates a virtual device. "
|
|
::= { hwSiteSummary 1 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.1.1.2
|
|
hwSiteName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (0..63))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Site name, which users can configure, is used to specify a site.
|
|
Otherwise, the configured character can not be any other languages except English."
|
|
::= { hwSiteSummary 2 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.1.1.3
|
|
hwSiteAdminAddr OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..65535)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Site administrant address, which users can assigned, is the unique ID of a site. It is used for device management by NMS, and value range is 0 to 65535. "
|
|
::= { hwSiteSummary 3 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.1.1.4
|
|
hwSiteDescription OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (0..127))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Site description. It is of the character string type. It is used to describe the site information such as the site location, which users can configure.
|
|
Otherwise, the configured character can not be any other languages except English."
|
|
::= { hwSiteSummary 4 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.1.1.5
|
|
hwNetIdentifier OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (0..63))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"NE ID. It is of the character string type. It is the unique ID of the site (an independent network element (NE)) on the network.
|
|
Otherwise, the configured character can not be any other languages except English. "
|
|
::= { hwSiteSummary 5 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.1.1.6
|
|
hwSiteIp OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (8..16))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Site IP address, default value is 192.168.0.10. Users need to configure the site IP address."
|
|
::= { hwSiteSummary 6 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.1.1.7
|
|
hwSiteNetmask OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (8..16))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Site netmask, default value is 255.255.0.0. Users need to configure the site netmask. "
|
|
::= { hwSiteSummary 7 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.1.1.8
|
|
hwSiteGateway OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (8..16))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Site gateway, default value: 192.168.0.1. Users need to configure the site gateway. "
|
|
::= { hwSiteSummary 8 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.1.1.9
|
|
hwSiteDGWorkStatus OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
idle(1),
|
|
working(2),
|
|
unknown(255)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of the diesel working state. It is an enumeration type:
|
|
If the enumeration value is 1, it indicates that the diesel is in the idle state;
|
|
If the enumeration value is 2, it indicates that the diesel is in the working state;
|
|
If the enumeration value is 255, it indicates diesel operation status unknown. "
|
|
::= { hwSiteSummary 9 }
|
|
-- 1.3.6.1.4.1.2011.6.164.1.1.2
|
|
hwSiteAlarms OBJECT IDENTIFIER ::= { hwSiteInfo 2 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.1.2.1
|
|
hwDeviceTrapOrdinalNumber OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Site device event trap serial number (SN) is the unique ID of the device event trap. It is used to resend and synchronize event traps. Its value range is 0 to 4294967296.
|
|
When the value exceeds the maximum value, the system automatically clears the value and numbers the alarm from 0 to 4294967296.
|
|
If the network management system (NMS) recieve the alarm number is not consequential, in such case that it notifies the SNMP agent the event trap number required.
|
|
So the monitor send the 50 event trap messages in maximum, after consequencial number required by NMS again.
|
|
Specially, if NMS set the value to 0, the agent would clear the alarm queue automatically."
|
|
::= { hwSiteAlarms 1 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.1.2.2
|
|
hwAlarmTrapOrdinalNumber OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Site alarm serial number (SN) is the unique ID of the alarm Trap. It is used to resend and synchronize alarms. Its value range is 0 to 4294967296.
|
|
When the value exceeds the maximum value, the system automatically clears the value and numbers the alarm from 0 to 4294967296.
|
|
If the network management system (NMS) recieve the alarm number is not consequential, in such case that it notifies the SNMP agent the alarm number required.
|
|
So the monitor send the 50 alarm messages in maximum, after consequencial number required by NMS again.
|
|
Specially, if NMS set the value to 0, the agent would clear the alarm queue automatically."
|
|
::= { hwSiteAlarms 2 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.1.2.3
|
|
hwAlarmQuantity OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Alarm number in site alarm list which are support. It is used for alarm list management by NMS, and value range is 0 to 65535. "
|
|
::= { hwSiteAlarms 3 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.1.5.10.7
|
|
-- 1.3.6.1.4.1.2011.6.164.1.1.2.100
|
|
hwSiteAlarmTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF HwSiteAlarmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Site alarms table. The table containing alarm information on the site management. Use this table to get site alarm name, alarm level, alarm signal description, and alarm port description, which can be used as VB of alarm traps. This table's index is hwAlarmIndex, clone site alarms table."
|
|
::= { hwSiteAlarms 100 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.1.5.10.7.1
|
|
-- 1.3.6.1.4.1.2011.6.164.1.1.2.100.1
|
|
hwSiteAlarmEntry OBJECT-TYPE
|
|
SYNTAX HwSiteAlarmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Site alarms table entry."
|
|
INDEX { hwAlarmIndex }
|
|
::= { hwSiteAlarmTable 1 }
|
|
|
|
|
|
HwSiteAlarmEntry ::=
|
|
SEQUENCE {
|
|
hwAlarmIndex
|
|
Integer32,
|
|
hwAlarmText
|
|
OCTET STRING,
|
|
hwAlarmLevel
|
|
INTEGER,
|
|
hwAlarmSigDesc
|
|
OCTET STRING,
|
|
hwAlarmRowStatus
|
|
RowStatus
|
|
}
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.1.2.100.1.1
|
|
hwAlarmIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..65535)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Site alarm table index. It is the unique ID of the site alarm."
|
|
::= { hwSiteAlarmEntry 1 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.1.2.100.1.2
|
|
hwAlarmText OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (0..63))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Alarm name. It is of the character string type, and used to specify the content of a specific alarm. "
|
|
::= { hwSiteAlarmEntry 2 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.1.2.100.1.3
|
|
hwAlarmLevel OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
critical(1),
|
|
major(2),
|
|
minor(3),
|
|
warning(4),
|
|
cleared(5),
|
|
unknown(255)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Alarm level, which users can configure the alarm severity, is an enumeration type:
|
|
If the enumeration value is 1, it indicates a critical alarm;
|
|
If the enumeration value is 2, it indicates a major alarm;
|
|
If the enumeration value is 3, it indicates a minor alarm;
|
|
If the enumeration value is 4, it indicates a warning;
|
|
If the enumeration value is 5, it indicates the alarm is cleared."
|
|
::= { hwSiteAlarmEntry 3 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.1.2.100.1.4
|
|
hwAlarmSigDesc OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (0..127))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Alarm signal description. It is used to add and describe alarm content. Users can define the description of the alarm.
|
|
Otherwise, the configured character can not be any other languages except English."
|
|
::= { hwSiteAlarmEntry 4 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.1.2.100.1.100
|
|
hwAlarmRowStatus OBJECT-TYPE
|
|
SYNTAX RowStatus
|
|
MAX-ACCESS read-create
|
|
STATUS current
|
|
DESCRIPTION
|
|
"RowStatus of site alarms table."
|
|
::= { hwSiteAlarmEntry 100 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.2
|
|
hwSiteMonitors OBJECT IDENTIFIER ::= { hwSiteMonitorMIBObjects 2 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.2.1
|
|
hwMonitorsGroup OBJECT IDENTIFIER ::= { hwSiteMonitors 1 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.2.1.1
|
|
hwMonsGroupId OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Site monitor group ID, is the unique ID of the site monitors."
|
|
::= { hwMonitorsGroup 1 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.2.1.2
|
|
hwMonsGroupName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (0..63))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Site monitor group name is of the character string type, used to specify the monitor group. Users can configure it.
|
|
Otherwise, the configured character can not be any other languages except English. "
|
|
::= { hwMonitorsGroup 2 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.2.1.3
|
|
hwMonsQuantity OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..100)
|
|
UNITS "pcs"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total site intelligent monitors. "
|
|
::= { hwMonitorsGroup 3 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.2.2
|
|
hwMonitor OBJECT IDENTIFIER ::= { hwSiteMonitors 2 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.2.2.1
|
|
hwMonitorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF HwMonitorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Site monitors table. Use this table to get site monitor equipment ID, site monitor equipment name, equipment software version, equipment PCB version, manufacturer, manufacture date, equipment serial No, equipment description, total runing time, and equipment controlled status, as well as to control monitor reset. This table's index is hwMonIndex, clone site monitors table."
|
|
::= { hwMonitor 1 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.2.2.1.1
|
|
hwMonitorEntry OBJECT-TYPE
|
|
SYNTAX HwMonitorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Site monitors table entry."
|
|
INDEX { hwMonIndex }
|
|
::= { hwMonitorTable 1 }
|
|
|
|
|
|
HwMonitorEntry ::=
|
|
SEQUENCE {
|
|
hwMonIndex
|
|
Integer32,
|
|
hwMonEquipId
|
|
Unsigned32,
|
|
hwMonEquipName
|
|
OCTET STRING,
|
|
hwMonEquipDescription
|
|
OCTET STRING,
|
|
hwMonEquipSoftwareVersion
|
|
OCTET STRING,
|
|
hwMonEquipPcbVersion
|
|
OCTET STRING,
|
|
hwMonEquipManufacturer
|
|
OCTET STRING,
|
|
hwMonEquipManuDate
|
|
OCTET STRING,
|
|
hwMonEquipSerialNo
|
|
OCTET STRING,
|
|
hwMonEquipOperTotalTime
|
|
Unsigned32,
|
|
hwSetMonEquipCtrlState
|
|
INTEGER,
|
|
hwCtrlMonEquipReset
|
|
INTEGER,
|
|
hwMonitorOperStatus
|
|
INTEGER,
|
|
hwMonRowStatus
|
|
RowStatus
|
|
}
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.2.2.1.1.1
|
|
hwMonIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..100)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table index of the site monitors (hwSiteMonsTab) is restricted by the quantity of the site monitors (hwMonsQuantity). Value range: 1 to 100"
|
|
::= { hwMonitorEntry 1 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.2.2.1.1.2
|
|
hwMonEquipId OBJECT-TYPE
|
|
SYNTAX Unsigned32 (1001..1100)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Site monitor ID. Value range: 001,001 to 001,100, in which the first three digits indicate the device type and the last three digits indicate the device SN. "
|
|
::= { hwMonitorEntry 2 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.2.2.1.1.3
|
|
hwMonEquipName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (0..63))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Monitor name. It is of the character string type, and users can set the name of the monitor.
|
|
Otherwise, the configured character can not be any other languages except English. "
|
|
::= { hwMonitorEntry 3 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.2.2.1.1.4
|
|
hwMonEquipDescription OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (0..127))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Monitor description. It is of the character string type. Users can set the description of the monitor.
|
|
Otherwise, the configured character can not be any other languages except English."
|
|
::= { hwMonitorEntry 4 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.2.2.1.1.5
|
|
hwMonEquipSoftwareVersion OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (0..63))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Monitor software version. It is of the character string type."
|
|
::= { hwMonitorEntry 5 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.2.2.1.1.6
|
|
hwMonEquipPcbVersion OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (0..63))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Monitor printed circuit board (PCB) hardware version. It is of the character string type."
|
|
::= { hwMonitorEntry 6 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.2.2.1.1.7
|
|
hwMonEquipManufacturer OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (0..63))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Monitor manufacture. It is of the character string type, and is an inherent attribute of the device."
|
|
::= { hwMonitorEntry 7 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.2.2.1.1.8
|
|
hwMonEquipManuDate OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (0..127))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Monitor production date. It is of the character string type, and is an inherent attribute of the device. "
|
|
::= { hwMonitorEntry 8 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.2.2.1.1.9
|
|
hwMonEquipSerialNo OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (0..127))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Production SN of the monitor. It is the electronic tag of the products."
|
|
::= { hwMonitorEntry 9 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.2.2.1.1.10
|
|
hwMonEquipOperTotalTime OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..65536)
|
|
UNITS "hours"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total monitor runtime. The monitor counts the data in real time. The value is an integer (.0), and unit is hour (h). It is used for performance measurement and evaluation of the monitor."
|
|
::= { hwMonitorEntry 10 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.2.2.1.1.11
|
|
hwSetMonEquipCtrlState OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
manualMode(1),
|
|
autoMode(2),
|
|
unknown(255)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Monitor control status. It is an enumeration type:
|
|
If the enumeration value is 1, it indicates the background control;
|
|
If the enumeration value is 2, it indicates the automatic control.
|
|
In manual state, monitor works under background commands; while monitors runs well automatically in auto state.
|
|
For details, see the corresponding user manual of the monitor."
|
|
::= { hwMonitorEntry 11 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.2.2.1.1.12
|
|
hwCtrlMonEquipReset OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
normal(1),
|
|
reset(2),
|
|
nullOper(255)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Warm-reset control of the monitor. It is an enumeration type:
|
|
If the network management system (NMS) notifies the SNMP agent that this node is set to 1, it indicates that the reset of the monitor is not triggered;
|
|
If the NMS notifies the SNMP agent that this node is set to 2, it indicates that the background starts the reset of the monitor. "
|
|
::= { hwMonitorEntry 12 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.2.2.1.1.99
|
|
hwMonitorOperStatus OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
normal(1),
|
|
commRs485Fail(2),
|
|
commNetFail(3),
|
|
fault(4),
|
|
alarmResume(254),
|
|
other(255)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of the site monitor module. It is an enumeration type:
|
|
If the enumeration value is 1, it indicates that the site monitor module is in the normal state;
|
|
If the enumeration value is 2, it indicates that the monitor module RS485 port communication failed;
|
|
If the enumeration value is 3, it indicates that the monitor module net port communication failed;
|
|
If the enumeration value is 4, it indicates that a fault occurs on the monitor module;
|
|
If the enumeration value is 254, it indicates monitor module alarm resume;
|
|
If the enumeration value is 255, it indicates monitor module operation status unknown. "
|
|
::= { hwMonitorEntry 99 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.2.2.1.1.100
|
|
hwMonRowStatus OBJECT-TYPE
|
|
SYNTAX RowStatus
|
|
MAX-ACCESS read-create
|
|
STATUS current
|
|
DESCRIPTION
|
|
"RowStatus of site monitor."
|
|
::= { hwMonitorEntry 100 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.3
|
|
hwSiteRectifiers OBJECT IDENTIFIER ::= { hwSiteMonitorMIBObjects 3 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.3.1
|
|
hwRectsGroup OBJECT IDENTIFIER ::= { hwSiteRectifiers 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.3.1.1
|
|
hwRectsGroupId OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Device group ID of the rectifier module. It is the unique ID of the rectifier module group, and its default value: 002,000.
|
|
The first digits indicate the device type and the last three digits indicate the device SN. If the last three digits are 000, it indicates a virtual device. "
|
|
::= { hwRectsGroup 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.3.1.2
|
|
hwRectsGroupName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (0..63))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Name of the rectifier module group, character string type, is used to specify the rectifier module group. Users can configure it.
|
|
Otherwise, the configured character can not be any other languages except English."
|
|
::= { hwRectsGroup 2 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.3.1.3
|
|
hwRectsTotalCurrent OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..500000)
|
|
UNITS "A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total current of the rectifier module group on the site. It indicates the real-time statistics of the rectifier module group on the site. unit: A, and the value is accurate to one decimal place (.1). "
|
|
::= { hwRectsGroup 3 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.3.1.4
|
|
hwRectsTotalQuantity OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..256)
|
|
UNITS "pcs"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total quantity of the rectifier modules. Value range: 0 to 256. "
|
|
::= { hwRectsGroup 4 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.3.1.5
|
|
hwRectsRatedVoltage OBJECT-TYPE
|
|
SYNTAX Unsigned32 (420..580)
|
|
UNITS "V"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Rated voltage of the rectifier module group. It is an inherent attribute. Value range: 42 to 58, Unit: V, and the value is accurate to one decimal place (.1). "
|
|
::= { hwRectsGroup 5 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.3.1.6
|
|
hwModifyRectsOutputVoltage OBJECT-TYPE
|
|
SYNTAX Unsigned32 (420..580)
|
|
UNITS "V"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Voltage adjustment of the rectifier module, which users can configure it. Value range: 42 to 58, Unit: V, and the value is accurate to one decimal space (.1). Based on the actual requirements, users can modify the output voltage of the rectifier module by modifying the value of the node.
|
|
NOTES: Be cautious about changing the value of the node. "
|
|
::= { hwRectsGroup 6 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.3.1.7
|
|
hwSetRectsRedundEnable OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
disable(1),
|
|
enable(2),
|
|
funcNotSupport(3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sleep function of the rectifier module group on the site. It is an enumeration value:
|
|
If the NMS notifies the SNMP agent that this node is set to 1, it means to disable the sleep function of the rectifier module group;
|
|
If the NMS notifies the SNMP agent that this node is set to 2, it means to enable the sleep function of the rectifier module group.
|
|
If NMS get the node value is 3, it indicates that this function is not support, and in such case the value set to the agent is invalid.
|
|
Default value: to disable the sleep function of the rectifier module group. For details, see the corresponding user manual of the monitor."
|
|
::= { hwRectsGroup 7 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.3.1.8
|
|
hwCtrlRectsAllOnOff OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
on(1),
|
|
off(2),
|
|
nullOper(255)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Power-on or power-off of the rectifier module group (all the rectifier modules) on the site. It is an enumeration value:
|
|
If the NMS notifies the SNMP agent that this node is set to 1, it indicates power-on of all rectifier modules;
|
|
If the NMS notifies the SNMP agent that this node is set to 2, it indicates power-off of all the rectifier modules. "
|
|
::= { hwRectsGroup 8 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.3.2
|
|
hwRectifier OBJECT IDENTIFIER ::= { hwSiteRectifiers 2 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.1.5.6
|
|
-- 1.3.6.1.4.1.2011.6.164.1.3.2.1
|
|
hwRectConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF HwRectConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Rectifier config information table. Use this table to get rectifiers equipment ID, software version, manufacturer, rated current, efficency, AC input type, and to control equipment on or off. This table's index is hwRectConfigIndex, clone Rectifier config information table."
|
|
::= { hwRectifier 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.1.5.6.1
|
|
-- 1.3.6.1.4.1.2011.6.164.1.3.2.1.1
|
|
hwRectConfigEntry OBJECT-TYPE
|
|
SYNTAX HwRectConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Rectifier config table entry."
|
|
INDEX { hwRectConfigIndex }
|
|
::= { hwRectConfigTable 1 }
|
|
|
|
|
|
HwRectConfigEntry ::=
|
|
SEQUENCE {
|
|
hwRectConfigIndex
|
|
Integer32,
|
|
hwRectEquipId
|
|
Unsigned32,
|
|
hwRectEquipName
|
|
OCTET STRING,
|
|
hwRectType
|
|
INTEGER,
|
|
hwRectSoftwareVersion
|
|
OCTET STRING,
|
|
hwRectManufacturer
|
|
OCTET STRING,
|
|
hwRectManuDate
|
|
OCTET STRING,
|
|
hwRectSerialNo
|
|
OCTET STRING,
|
|
hwRectRatedCurrent
|
|
Unsigned32,
|
|
hwRectEfficency
|
|
Unsigned32,
|
|
hwRectInputAcType
|
|
INTEGER,
|
|
hwCtrlRectOnOff
|
|
INTEGER,
|
|
hwRectConfigRowStatus
|
|
RowStatus
|
|
}
|
|
|
|
-- 1.3.6.1.4.1.2011.6.1.5.6.1.2
|
|
-- 1.3.6.1.4.1.2011.6.164.1.3.2.1.1.1
|
|
hwRectConfigIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Index of the device configuration list for the rectifier modules, which value range: 1 to 256. Lines of the device list are restricted by the total quantity of the rectifier modules (hwRectTotleQuantity).
|
|
"
|
|
::= { hwRectConfigEntry 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.3.2.1.1.2
|
|
hwRectEquipId OBJECT-TYPE
|
|
SYNTAX Unsigned32 (2001..2255)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Rectifier module ID. Value range: 002'001 to 002'255. The first digits indicate the device type and last three digits indicate the device SN. "
|
|
::= { hwRectConfigEntry 2 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.3.2.1.1.3
|
|
hwRectEquipName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (0..63))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Device name of the rectifier module, character string type, is used to specify the rectifier module. Users can configure it.
|
|
Otherwise, the configured character can not be any other languages except English."
|
|
::= { hwRectConfigEntry 3 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.1.5.6.1.3
|
|
-- 1.3.6.1.4.1.2011.6.164.1.3.2.1.1.4
|
|
hwRectType OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
eps5(1),
|
|
eps15(2),
|
|
eps30(3),
|
|
eps50(4),
|
|
eps100(5),
|
|
unknown(255)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Specific type of the rectifier module. It is an enumeration type:
|
|
If the enumeration value is 1, it indicates a 5A rectifier module;
|
|
If the enumeration value is 2, it indicates a 15A rectifier module;
|
|
If the enumeration value is 3, it indicates a 30A rectifier module;
|
|
If the enumeration value is 4, it indicates a 50A rectifier module;
|
|
If the enumeration value is 5, it indicates a 100A rectifier module.
|
|
|
|
"
|
|
::= { hwRectConfigEntry 4 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.3.2.1.1.5
|
|
hwRectSoftwareVersion OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (0..63))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Software version of the rectifier module. It indicates the software version ID of the module. "
|
|
::= { hwRectConfigEntry 5 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.3.2.1.1.6
|
|
hwRectManufacturer OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (0..63))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Manufacture of the rectifier module."
|
|
::= { hwRectConfigEntry 6 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.3.2.1.1.7
|
|
hwRectManuDate OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (0..127))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Manufacture date of rectifiers is of string type."
|
|
::= { hwRectConfigEntry 7 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.3.2.1.1.8
|
|
hwRectSerialNo OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (0..127))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Rectifier module SN. It indicates the electronic tag of the product."
|
|
::= { hwRectConfigEntry 8 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.3.2.1.1.9
|
|
hwRectRatedCurrent OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..1000)
|
|
UNITS "A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Rated voltage of the rectifier module, is an inherent attribute. Value range: 0 to 100, Unit: A, and the value is accurate to one decimal place (.1). "
|
|
::= { hwRectConfigEntry 9 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.3.2.1.1.10
|
|
hwRectEfficency OBJECT-TYPE
|
|
SYNTAX Unsigned32 (800..1000)
|
|
UNITS "%"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Efficiency of the rectifier module, is an inherent attribute. Value range: 80 to 100, Unit: %, and the value is accurate to one decimal place (.1)."
|
|
::= { hwRectConfigEntry 10 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.3.2.1.1.11
|
|
hwRectInputAcType OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
single(1),
|
|
triple(2),
|
|
unknown(255)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Input AC type of the rectifier module. It is an enumeration value:
|
|
If the value of the node is 1, it indicates single-phase AC input;
|
|
If the value of the node is 2, it indicates three-phase AC input. "
|
|
::= { hwRectConfigEntry 11 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.1.5.6.1.8
|
|
-- 1.3.6.1.4.1.2011.6.164.1.3.2.1.1.12
|
|
hwCtrlRectOnOff OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
on(1),
|
|
off(2),
|
|
nullOper(255)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Power-on or power-off of the rectifier module, is an enumeration value. Users can modify the enumeration value of this node, thus controlling of the power-on or power-off of the rectifier module:
|
|
If the NMS notifies the SNMP agent that this node is set to 1, it indicates power-on of the rectifier module;
|
|
If the NMS notifies the SNMP agent that this node is set to 2, it indicates power-off of the rectifier module. "
|
|
::= { hwRectConfigEntry 12 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.1.5.6.1.11
|
|
-- 1.3.6.1.4.1.2011.6.164.1.3.2.1.1.100
|
|
hwRectConfigRowStatus OBJECT-TYPE
|
|
SYNTAX RowStatus
|
|
MAX-ACCESS read-create
|
|
STATUS current
|
|
DESCRIPTION
|
|
"RowStatus of rectifier config table."
|
|
::= { hwRectConfigEntry 100 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.3.2.2
|
|
hwRectOperTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF HwRectOperEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Rectifier runing information table. Use this table to get rectifiers output current, output voltage, totle runing time, and current run status. This table's index is hwRectRunIndex, clone rectifier runing information table."
|
|
::= { hwRectifier 2 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.3.2.2.1
|
|
hwRectOperEntry OBJECT-TYPE
|
|
SYNTAX HwRectOperEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Rectifier runing table entry."
|
|
INDEX { hwRectOperIndex }
|
|
::= { hwRectOperTable 1 }
|
|
|
|
|
|
HwRectOperEntry ::=
|
|
SEQUENCE {
|
|
hwRectOperIndex
|
|
Integer32,
|
|
hwRectOutputCurrent
|
|
Unsigned32,
|
|
hwRectOutputVoltage
|
|
Unsigned32,
|
|
hwRectTotalOperTime
|
|
Unsigned32,
|
|
hwRectOperStatus
|
|
INTEGER,
|
|
hwRectOperRowStatus
|
|
RowStatus
|
|
}
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.3.2.2.1.1
|
|
hwRectOperIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table index of the running rectifier modules, which value range: 1 to 256. Lines of the device list are restricted by the total quantity of the rectifier modules (hwRectTotleQuantity)."
|
|
::= { hwRectOperEntry 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.1.5.6.1.5
|
|
-- 1.3.6.1.4.1.2011.6.164.1.3.2.2.1.2
|
|
hwRectOutputCurrent OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..2000)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Output current of the rectifier module. It is a real-time analog parameter. Value range: 0 to 200, Unit: A, and the value is accurate to one decimal place (.1). "
|
|
::= { hwRectOperEntry 2 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.1.5.6.1.4
|
|
-- 1.3.6.1.4.1.2011.6.164.1.3.2.2.1.3
|
|
hwRectOutputVoltage OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..600)
|
|
UNITS "V"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Output voltage of the rectifier module. It is a real-time analog parameter. Value range: 0 to 60, Unit: V, the value is accurate to one decimal place (.1).
|
|
"
|
|
::= { hwRectOperEntry 3 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.3.2.2.1.4
|
|
hwRectTotalOperTime OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "minutes"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total runtime of the rectifier module. Value unit: minute (m), and the value is an integer (.0). "
|
|
::= { hwRectOperEntry 4 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.3.2.2.1.99
|
|
hwRectOperStatus OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
normal(1),
|
|
fault(2),
|
|
protect(3),
|
|
commFail(4),
|
|
switchOff(5),
|
|
invalid(6),
|
|
noConfig(7),
|
|
alarmResume(254),
|
|
other(255)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of the rectifier module. It is an enumeration type:
|
|
If the enumeration value is 1, it indicates that the rectifier module is in the normal state;
|
|
If the enumeration value is 2, it indicates that a fault occurs on the rectifier module;
|
|
If the enumeration value is 3, it indicates the automatic protection of the rectifier module;
|
|
If the enumeration value is 4, it indicates that communication of the rectifier module fails;
|
|
If the enumeration value is 5, it indicates that the rectifier module is shut down;
|
|
If the enumeration value is 6, it indicates that the rectifier module is invalid;
|
|
If the enumeration value is 7, it indicates that this rectifier is not configured;
|
|
If the enumeration value is 254, it indicates rectifier alarm resume;
|
|
If the enumeration value is 255, it indicates rectifier operation status unknown.
|
|
|
|
"
|
|
::= { hwRectOperEntry 99 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.3.2.2.1.100
|
|
hwRectOperRowStatus OBJECT-TYPE
|
|
SYNTAX RowStatus
|
|
MAX-ACCESS read-create
|
|
STATUS current
|
|
DESCRIPTION
|
|
"RowStatus of rectifier runing table."
|
|
::= { hwRectOperEntry 100 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4
|
|
hwSiteBatterys OBJECT IDENTIFIER ::= { hwSiteMonitorMIBObjects 4 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.1
|
|
hwBattsConfig OBJECT IDENTIFIER ::= { hwSiteBatterys 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.1.1
|
|
hwBattsGroupId OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery group ID. It is the unique ID of the battery group device. The first digits indicate the device type and the last three digits indicate the device SN. If the last three digits are 000, it indicates a virtual device. "
|
|
::= { hwBattsConfig 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.1.2
|
|
hwBattsGroupName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (0..63))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Device name of the battery group. It is of the character string type, which can be configured by users.
|
|
Otherwise, the configured character can not be any other languages except English."
|
|
::= { hwBattsConfig 2 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.1.3
|
|
hwBattsTotalQuantity OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..100)
|
|
UNITS "strings"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total quantity of battery strings, which value range: 0 to 100."
|
|
::= { hwBattsConfig 3 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.1.4
|
|
hwSetBattsHighTempAction OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
blvd(1),
|
|
lowerDcOutput(2),
|
|
unknown(255)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery high-temperature protection mode. It is an enumeration value, and can be configured.
|
|
If the enumeration value is 1, it indicates the power-off protection mode;
|
|
If the enumeration value is 2, it indicates the protection mode of lowering the output voltage of the rectifier module.
|
|
unknown(255) it is do nothing "
|
|
::= { hwBattsConfig 4 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.1.5
|
|
hwSetBattsHighTempVoltLimit OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..600)
|
|
UNITS "V"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery protection voltage under high temperature. It works with the low-voltage power-off protection in battery high-temperature protection mode, which can be configured by users. If the low-voltage power-off protection mode (that is, the enumeration value is 1) is selected, the node is a low-voltage power-off node. Value range: 0 to 60, unit: V, and the value is accurate to one decimal place (.1). "
|
|
::= { hwBattsConfig 5 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.1.6
|
|
hwSetBattsHTDLimit OBJECT-TYPE
|
|
SYNTAX Integer32 (0..100)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Upper threshold of the battery high temperature disconnection(HTD), can be configured by users. Value range: 0 to 100, Unit: centigrade (°„C), and the value is an integer (.0)."
|
|
::= { hwBattsConfig 6 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.1.7
|
|
hwSetBattsHTDEnable OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
enable(1),
|
|
disable(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery high temperature disconnection enable. It is an enumeration type:
|
|
If the enumeration value is 1, enable the operation of the battery disconnection in high temperature;
|
|
If the enumeration value is 2, disable the operation of the battery disconnection in high temperature.
|
|
The operation of the battery disconnection in high temperature is disabled by default. "
|
|
::= { hwBattsConfig 7 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.1.8
|
|
hwSetBattsFloatVoltage OBJECT-TYPE
|
|
SYNTAX Unsigned32 (420..580)
|
|
UNITS "V"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Float charge voltage of the batteries, can be configured by users. Value range: 42 to 58, unit: V, and the value is accurate to one decimal place (.1)"
|
|
::= { hwBattsConfig 8 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.1.9
|
|
hwSetBattsBoostVoltage OBJECT-TYPE
|
|
SYNTAX Unsigned32 (420..580)
|
|
UNITS "V"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Boostcharge voltage of the batteries, can be configured by users. Value range: 42 to 58, unit: V, and the value is accurate to one decimal place (.1)."
|
|
::= { hwBattsConfig 9 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.1.10
|
|
hwSetBattsCurrLimitCoefficient OBJECT-TYPE
|
|
SYNTAX Unsigned32 (5..25)
|
|
UNITS "C10"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Current-limiting point coefficient of the batteries, can be configured by users. Value range: 0.05 to 0.25, unit: C10, and the value is accurate to two decimal places (.2)."
|
|
::= { hwBattsConfig 10 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.1.11
|
|
hwSetBattsCompFactor OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..500)
|
|
UNITS "mV per centigrades"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature compensated coefficient of the batteries, can be configured by user. Value range: 0 to 500, unit: mv per centigrade, and the value is an integer (.0)."
|
|
::= { hwBattsConfig 11 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.1.12
|
|
hwCtrlBattsBoostFloat OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
floatCharge(1),
|
|
boostCharge(2),
|
|
nullOper(255)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Control batteries charge mode between boost and float. It is an enumeration value.
|
|
Users actively control the conversion.
|
|
If the NMS notifies the SNMP agent that this node is set to 1, it means to start the float charge mode of the batteries;
|
|
If the NMS notifies the SNMP agent that this node is set to 2, it means to start the boost charge mode of the batteries.
|
|
"
|
|
::= { hwBattsConfig 12 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.2
|
|
hwBattsOperate OBJECT IDENTIFIER ::= { hwSiteBatterys 2 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.2.1
|
|
hwBattsTotalCurrent OBJECT-TYPE
|
|
SYNTAX Integer32 (-10000..10000)
|
|
UNITS "A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total current of the battery group. It indicates the real-time statistics of the battery group on the site. Value range: -1000 to +1000, unit: A, and the value is accurate to one decimal place (.1). "
|
|
::= { hwBattsOperate 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.2.2
|
|
hwBattsPreDischargeTime OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..65536)
|
|
UNITS "minutes"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery group backup time. It indicates the real-time statistics of the battery group. Value range: 0 to 65536, Unit: minute (m), and the value is an integer (.0). "
|
|
::= { hwBattsOperate 2 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.2.3
|
|
hwBattsChargeStatus OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
floatCharge(1),
|
|
boostCharge(2),
|
|
disCharge(3),
|
|
unknown(255)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery charging state, indicates the charging and discharging information about the battery group. It is an enumeration type.
|
|
If the enumeration value is 1, it indicates a battery group in the float charging state.
|
|
If the enumeration value is 2, it indicates a battery group in the boost charging state.
|
|
If the enumeration value is 3, it indicates a battery group in the discharging state.
|
|
"
|
|
::= { hwBattsOperate 3 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.2.4
|
|
hwBattsCurrLimitStatus OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
unlimit(1),
|
|
limit(2),
|
|
unknown(255)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery group current-limiting state, indicates the state information about the battery group. It is an enumeration value.
|
|
If the enumeration value is 1, it indicates that the current of the battery group is not limited.
|
|
If the enumeration value is 2, it indicates the current of the battery group is limited.
|
|
"
|
|
::= { hwBattsOperate 4 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.3
|
|
hwBattsTest OBJECT IDENTIFIER ::= { hwSiteBatterys 3 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.3.1
|
|
hwBattsTestRecordCount OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..100)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery test records number."
|
|
::= { hwBattsTest 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.3.2
|
|
hwSetBattsManuStdTestTime OBJECT-TYPE
|
|
SYNTAX Unsigned32 (1..100)
|
|
UNITS "hours"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery standard test time, It can be configured by users, and its value is an integer (.0).
|
|
Here, if battery manual test is standard mode, value range defines between 1 to 6000, unit: minutes(m)"
|
|
::= { hwBattsTest 2 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.3.3
|
|
hwSetBattsManuStdTestEndVolt OBJECT-TYPE
|
|
SYNTAX Unsigned32 (170..220)
|
|
UNITS "V per cell"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Voltage when the battery test is ended, can be configured by users. Unit: V/cell, and the value is accurate to two decimal place (.2).
|
|
Here, if battery manual test is standard mode, value range defines between 1.7 to 2.2"
|
|
::= { hwBattsTest 3 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.3.4
|
|
hwSetBattsManuStdTestCellNum OBJECT-TYPE
|
|
SYNTAX Unsigned32 (1..50)
|
|
UNITS "cell"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery cell number in each Group, which is used in the battery standard manual test, can be configured by users. Unit: psc or cell, value range defines between 1 to 50. and the value is accurate to one decimal place (.0)."
|
|
::= { hwBattsTest 4 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.3.5
|
|
hwSetBattsManuShortTestTime OBJECT-TYPE
|
|
SYNTAX Unsigned32 (1..240)
|
|
UNITS "minutes"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery short test time, It can be configured by users, and its value is an integer (.0).
|
|
If battery manual test is simple mode, value range defines between 1 to 240, unit: minutes(m)"
|
|
::= { hwBattsTest 5 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.3.6
|
|
hwSetBattsManuShortTestEndVolt OBJECT-TYPE
|
|
SYNTAX Unsigned32 (400..540)
|
|
UNITS "V"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Voltage when the battery short test is ended, can be configured by users. Unit: V, and the value is accurate to one decimal place (.1).
|
|
Here, if battery manual test is standard mode, value range defines between 40 to 54.
|
|
"
|
|
::= { hwBattsTest 6 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.3.7
|
|
hwCtrlBattsTestStartStop OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
stdTestStart(1),
|
|
shortTestStart(2),
|
|
testStop(3),
|
|
nullOper(255)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery manualtest start and stop. It is an enumeration value.
|
|
If the NMS notifies the SNMP agent that the node is set to 1, it means to start a standard manual test;
|
|
If the NMS notifies the SNMP agent that the node is set to 2, it means to start a short manual test;
|
|
If the NMS notifies the SNMP agent that the node is set to 3, it means to stop the battery test.
|
|
Set the parameters, such as battery test time, and voltage when the battery test stops before the node controls the start of the battery test. If the parameters are not set this time, the system uses the configuration parameters by default; and if the battery test is started at the first time, the system uses the default value.
|
|
Battery test can only start up in some conditions, so that the reason of Start of battery short test failed may be as follow:
|
|
1. Interval between this test and the latest AC outage or test is longer than the preset duration.
|
|
2. No major alarm is raised.
|
|
3. The number of healthy modules is greater than 0.
|
|
4. The number of battery strings is greater than 0."
|
|
::= { hwBattsTest 7 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.3.100
|
|
hwBattsTestResultTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF HwBattsTestResultEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery test result record table. Use this table to get battery test inital time, test result, battery efficiency, battery discharge time, terminated voltage, average current, discharge AH value, test temperature and test terminated course. This table's index is hwBattsTestResultIndex, clone Battery test result record table."
|
|
::= { hwBattsTest 100 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.3.100.1
|
|
hwBattsTestResultEntry OBJECT-TYPE
|
|
SYNTAX HwBattsTestResultEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery test result table entry."
|
|
INDEX { hwBattsTestResultIndex }
|
|
::= { hwBattsTestResultTable 1 }
|
|
|
|
|
|
HwBattsTestResultEntry ::=
|
|
SEQUENCE {
|
|
hwBattsTestResultIndex
|
|
Integer32,
|
|
hwBattsTestType
|
|
INTEGER,
|
|
hwBattsTestStartTime
|
|
OCTET STRING,
|
|
hwBattsTestResult
|
|
INTEGER,
|
|
hwBattsEfficiency
|
|
Integer32,
|
|
hwBattsDischargeTime
|
|
Unsigned32,
|
|
hwBattsDischargeEndVoltage
|
|
Unsigned32,
|
|
hwBattsDischargeAvCurrent
|
|
Integer32,
|
|
hwBattsDischargeAhValue
|
|
Unsigned32,
|
|
hwBattsTestTemprature
|
|
Integer32,
|
|
hwBattsTestEndCourse
|
|
INTEGER,
|
|
hwBattsTestResultRowStatus
|
|
RowStatus
|
|
}
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.3.100.1.1
|
|
hwBattsTestResultIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..100)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table index of the battery test results. Currently up to 10 times of the battery test results are saved by default. "
|
|
::= { hwBattsTestResultEntry 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.3.100.1.2
|
|
hwBattsTestType OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
manualTest(1),
|
|
acOffAutoTest(2),
|
|
timedTest(3),
|
|
shortTest(4),
|
|
other(255)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Record test type of the battery test. It is an enumeration value:
|
|
If the NMS notifies the SNMP agent that this node is set to 1, it indicates a manual test;
|
|
If the NMS notifies the SNMP agent that this node is set to 2, it indicates a simplified test;
|
|
If the NMS notifies the SNMP agent that this node is set to 3, it indicates a timed test;
|
|
If the NMS notifies the SNMP agent that this node is set to 4, it indicates a short test;
|
|
If the NMS notifies the SNMP agent that this node is set to 255, it indicates a other test."
|
|
::= { hwBattsTestResultEntry 2 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.3.100.1.3
|
|
hwBattsTestStartTime OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (0..127))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Test start time of the record in the battery test. It is of the character string type."
|
|
::= { hwBattsTestResultEntry 3 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.3.100.1.4
|
|
hwBattsTestResult OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
battNoResult(1),
|
|
battNormal(2),
|
|
battPreAlarm(3),
|
|
battAlarm(4),
|
|
unknown(255)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery test result. It is an enumeration value.
|
|
If the enumeration value of the node is 1, it indicates that the battery test has no result:
|
|
If the enumeration value of the node is 2, it indicates that the battery is in the normal state:
|
|
If the enumeration value of the node is 3, it indicates that the battery is in the minor abnormal state,
|
|
If the enumeration value of the node is 4, it indicates that the battery is in the alarm state,
|
|
If the enumeration value of the node is 255, it indicates that the battery state is unknown,"
|
|
::= { hwBattsTestResultEntry 4 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.3.100.1.5
|
|
hwBattsEfficiency OBJECT-TYPE
|
|
SYNTAX Integer32 (0..100)
|
|
UNITS "%"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery efficiency test. Value range: 0 to 100, Unit: %, and the value is an integer (.0).
|
|
If the value is -1, it indicates that the test value is inefficient."
|
|
::= { hwBattsTestResultEntry 5 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.3.100.1.6
|
|
hwBattsDischargeTime OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..10000)
|
|
UNITS "hours"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Discharge time of the battery test records. Value range: 0 to 100, unit: hour (h), and the value is accurate to two decimal places (.2)."
|
|
::= { hwBattsTestResultEntry 6 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.3.100.1.7
|
|
hwBattsDischargeEndVoltage OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..600)
|
|
UNITS "V"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Discharge termination voltage of the battery test. Value range: 0 to 60, unit: V, and the value is accurate to one decimal place (.1)."
|
|
::= { hwBattsTestResultEntry 7 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.3.100.1.8
|
|
hwBattsDischargeAvCurrent OBJECT-TYPE
|
|
SYNTAX Integer32 (-10000..10000)
|
|
UNITS "A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average discharge current of the battery test. Value range: -10000 to 10000, unit: A, and the value is accurate to one decimal place (.1)."
|
|
::= { hwBattsTestResultEntry 8 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.3.100.1.9
|
|
hwBattsDischargeAhValue OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..5000)
|
|
UNITS "Ah"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Discharge ampere per hour the battery test. Value range: 0 to 5000, Unit: Ah, and the value is an integer (.0). "
|
|
::= { hwBattsTestResultEntry 9 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.3.100.1.10
|
|
hwBattsTestTemprature OBJECT-TYPE
|
|
SYNTAX Integer32 (-50..100)
|
|
UNITS "centigrades"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery temperature of the battery test termination. Value range: -50 to +100, Unit: centigrade (°„C), and the value is an integer (.0).
|
|
If the value is -1024, it indicates that no battery temperature value sensor is detected."
|
|
::= { hwBattsTestResultEntry 10 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.3.100.1.11
|
|
hwBattsTestEndCourse OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
voltageToEnd(1),
|
|
timeToEnd(2),
|
|
acOnToEnd(3),
|
|
manulToEnd(4),
|
|
faultAlarmToEnd(5),
|
|
other(255)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Termination factors of the battery test. It is an enumeration value.
|
|
If the enumeration value is 1, it indicates that the voltage value of the battery test reaches the set termination voltage;
|
|
If the enumeration value is 2, it indicates that the voltage value of the battery test reaches the timing limit;
|
|
If the enumeration value is 3, it indicates that an alarm related to the battery leads to the stop of the battery test;
|
|
If the enumeration value is 4, it indicates that a battery test is stopped manually,
|
|
If the enumeration value is 5, it indicates that battery fault alarm happened,
|
|
If the enumeration value is 255, it indicates that battery test end for other courses."
|
|
::= { hwBattsTestResultEntry 11 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.3.100.1.100
|
|
hwBattsTestResultRowStatus OBJECT-TYPE
|
|
SYNTAX RowStatus
|
|
MAX-ACCESS read-create
|
|
STATUS current
|
|
DESCRIPTION
|
|
"RowStatus of battery test table."
|
|
::= { hwBattsTestResultEntry 100 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.4
|
|
hwBattString OBJECT IDENTIFIER ::= { hwSiteBatterys 4 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.4.1
|
|
hwBattStringConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF HwBattStringConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery string config table. Use this table to get battery string equipment ID and equipment name, to set battery standard capacity and battery install time as well. This table's index is hwBattStringConfigIndex, clone battery string config table."
|
|
::= { hwBattString 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.4.1.1
|
|
hwBattStringConfigEntry OBJECT-TYPE
|
|
SYNTAX HwBattStringConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery string config table entry."
|
|
INDEX { hwBattStringConfigIndex }
|
|
::= { hwBattStringConfigTable 1 }
|
|
|
|
|
|
HwBattStringConfigEntry ::=
|
|
SEQUENCE {
|
|
hwBattStringConfigIndex
|
|
Integer32,
|
|
hwBattStringEquipId
|
|
Unsigned32,
|
|
hwBattStringEquipName
|
|
OCTET STRING,
|
|
hwSetBattsTempUpperLimit
|
|
Integer32,
|
|
hwSetBattsTempLowerLimit
|
|
Integer32,
|
|
hwSetBattsTempMeasureUpperLimit
|
|
Integer32,
|
|
hwSetBattsTempMeasureLowerLimit
|
|
Integer32,
|
|
hwSetBattStdCapacity
|
|
Integer32,
|
|
hwSetBattInstallTime
|
|
OCTET STRING,
|
|
hwBattStringConfigRowStatus
|
|
RowStatus
|
|
}
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.4.1.1.1
|
|
hwBattStringConfigIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..100)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Device table index of the battery string, which value range: 1 to 100."
|
|
::= { hwBattStringConfigEntry 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.4.1.1.2
|
|
hwBattStringEquipId OBJECT-TYPE
|
|
SYNTAX Unsigned32 (3001..3100)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Batteries device ID, can be configured by users. Value range: 003,001 to 003,100, in which the first three digits specify the device type and the last three specify the device SN."
|
|
::= { hwBattStringConfigEntry 2 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.4.1.1.3
|
|
hwBattStringEquipName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (0..63))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Batteries device name, of the character string type, is used to specify the batteries. Users can configure it.
|
|
Otherwise, the configured character can not be any other languages except English."
|
|
::= { hwBattStringConfigEntry 3 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.4.1.1.4
|
|
hwSetBattsTempUpperLimit OBJECT-TYPE
|
|
SYNTAX Integer32 (-50..100)
|
|
UNITS "centigrades"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Upper threshold of the battery temperature alarm, can be configured by users. Value range: -50 to 100, Unit: centigrade (°„C), and the value is an integer (.0)."
|
|
::= { hwBattStringConfigEntry 4 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.4.1.1.5
|
|
hwSetBattsTempLowerLimit OBJECT-TYPE
|
|
SYNTAX Integer32 (-50..100)
|
|
UNITS "centigrades"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Lower threshold of the battery temperature alarm, can be configured by users. Value range: -50 to 100, Unit: centigrade (°„C), and the value is an integer (.0)."
|
|
::= { hwBattStringConfigEntry 5 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.4.1.1.6
|
|
hwSetBattsTempMeasureUpperLimit OBJECT-TYPE
|
|
SYNTAX Integer32 (0..100)
|
|
UNITS "centigrades"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Upper threshold of the battery temperature measurement, can be configured by users. Value range: 0 to 100, Unit: centigrade (°„C), and the value is an integer (.0)."
|
|
::= { hwBattStringConfigEntry 6 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.4.1.1.7
|
|
hwSetBattsTempMeasureLowerLimit OBJECT-TYPE
|
|
SYNTAX Integer32 (-50..0)
|
|
UNITS "centigrades"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Lower threshold of the battery temperature measurement, can be configured by users. Value range: -50 to 0, Unit: centigrade (°„C), and the value is an integer (.0)."
|
|
::= { hwBattStringConfigEntry 7 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.4.1.1.8
|
|
hwSetBattStdCapacity OBJECT-TYPE
|
|
SYNTAX Integer32 (0..10000)
|
|
UNITS "Ah"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Set battery standard capacity, is an inherent attribute of the device. Value range: 0 to 10000, unit: Ah, the value is an integer (.0). "
|
|
::= { hwBattStringConfigEntry 8 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.4.1.1.9
|
|
hwSetBattInstallTime OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (0..128))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Set battery install time, of the character string type, can be configured by users.
|
|
Otherwise, the configured character can not be any other languages except English. "
|
|
::= { hwBattStringConfigEntry 9 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.4.1.1.100
|
|
hwBattStringConfigRowStatus OBJECT-TYPE
|
|
SYNTAX RowStatus
|
|
MAX-ACCESS read-create
|
|
STATUS current
|
|
DESCRIPTION
|
|
"RowStatus of battery string config table."
|
|
::= { hwBattStringConfigEntry 100 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.4.2
|
|
hwBattStringOperTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF HwBattStringOperEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery string runing table. Use this table to get battery string current, persent of remain capacity, battery remain capacity, battery actual capacity, as well as battery temperature. This table's index is hwBattStringRunIndex, clone battery string runing table."
|
|
::= { hwBattString 2 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.4.2.1
|
|
hwBattStringOperEntry OBJECT-TYPE
|
|
SYNTAX HwBattStringOperEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery string runing table entry."
|
|
INDEX { hwBattStringOperIndex }
|
|
::= { hwBattStringOperTable 1 }
|
|
|
|
|
|
HwBattStringOperEntry ::=
|
|
SEQUENCE {
|
|
hwBattStringOperIndex
|
|
Integer32,
|
|
hwBattStringCurrent
|
|
Integer32,
|
|
hwBattStringRemainCapacityPercent
|
|
Unsigned32,
|
|
hwBattStringRemainCapacity
|
|
Unsigned32,
|
|
hwBattStringActualCapacity
|
|
Unsigned32,
|
|
hwBattStringTemprature
|
|
Integer32,
|
|
hwBattStringOperStatus
|
|
INTEGER,
|
|
hwBattStringOperRowStatus
|
|
RowStatus
|
|
}
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.4.2.1.1
|
|
hwBattStringOperIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..100)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Device table index of the battery string, which value range: 1 to 100."
|
|
::= { hwBattStringOperEntry 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.4.2.1.2
|
|
hwBattStringCurrent OBJECT-TYPE
|
|
SYNTAX Integer32 (-10000..10000)
|
|
UNITS "A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Batteries current. It is an analog parameter collected by the battery string in real time. Value range: -1000 to +1000, unit: A, and the value is accurate to one decimal place (.1)."
|
|
::= { hwBattStringOperEntry 2 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.4.2.1.3
|
|
hwBattStringRemainCapacityPercent OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..1000)
|
|
UNITS "%"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Remaining capacity percentage of the battery string. Value range: 0 to 100, unit: %, and the value is accurate to one decimal place (.1)."
|
|
::= { hwBattStringOperEntry 3 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.4.2.1.4
|
|
hwBattStringRemainCapacity OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..5000)
|
|
UNITS "Ah"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Remaining capacity of the battery string. It is an analog parameter collected by the battery string in real time. Value range: 0 to 5000, unit: Ah, and the value is an integer (.0)."
|
|
::= { hwBattStringOperEntry 4 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.4.2.1.5
|
|
hwBattStringActualCapacity OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..5000)
|
|
UNITS "Ah"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Batteries actual capacity. It is an analog parameter collected by the battery string in real time.Value range: 0 to 5000, unit: Ah, the value is an integer (.0)."
|
|
::= { hwBattStringOperEntry 5 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.4.2.1.6
|
|
hwBattStringTemprature OBJECT-TYPE
|
|
SYNTAX Integer32 (-500..1000)
|
|
UNITS "centigrades"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery temperature. It is a battery parameter collected in real time. Value range: -50 to +100, unit: centigrade (°„C), and the value is an integer (.1).
|
|
If the value is -99999, it indicates that battery temperature sensor is not configured."
|
|
::= { hwBattStringOperEntry 6 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.4.2.1.99
|
|
hwBattStringOperStatus OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
normal(1),
|
|
tempHigh(2),
|
|
tempLow(3),
|
|
loopBreak(4),
|
|
overCurrent(5),
|
|
unbalance(6),
|
|
alarmResume(254),
|
|
other(255)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of the site battery string module. It is an enumeration type:
|
|
If the enumeration value is 1, it indicates that the site battery string is in the normal state;
|
|
If the enumeration value is 2, it indicates that the battery string is over upper alarm threshold of temperature;
|
|
If the enumeration value is 3, it indicates that the battery string is under lower alarm threshold of temperature;
|
|
If the enumeration value is 4, it indicates that battery string loop has disconnected;
|
|
If the enumeration value is 5, it indicates that the current of batery is over upper charging threshold;
|
|
If the enumeration value is 254, it indicates battery string alarm resume;
|
|
If the enumeration value is 255, it indicates battery string operation status unknown. "
|
|
::= { hwBattStringOperEntry 99 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.4.4.2.1.100
|
|
hwBattStringOperRowStatus OBJECT-TYPE
|
|
SYNTAX RowStatus
|
|
MAX-ACCESS read-create
|
|
STATUS current
|
|
DESCRIPTION
|
|
"RowStatus of battery string runing table."
|
|
::= { hwBattStringOperEntry 100 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.5
|
|
hwSiteAcDistributions OBJECT IDENTIFIER ::= { hwSiteMonitorMIBObjects 5 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.5.1
|
|
hwAcDistributionsGroup OBJECT IDENTIFIER ::= { hwSiteAcDistributions 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.5.1.1
|
|
hwAcsGroupId OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"AC group ID, is the unique ID of the AC group. The first three digits indicate the device type and the last three indicate the device SN. If the last three digits are 000, it indicates a virtual device. "
|
|
::= { hwAcDistributionsGroup 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.5.1.2
|
|
hwAcsGroupName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (0..63))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Device name of the AC group. It is of the character string type, and can be configured by users.
|
|
Otherwise, the configured character can not be any other languages except English."
|
|
::= { hwAcDistributionsGroup 2 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.5.1.3
|
|
hwAcsTotalCurrent OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..10000)
|
|
UNITS "A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total current of the AC group. It indicates the real-time statistics of the AC group. Value range: 0 to 1000, unit: A, and the value is accurate to one decimal place (.1)."
|
|
::= { hwAcDistributionsGroup 3 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.5.1.4
|
|
hwAcsTotalQuantity OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..100)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total quantity of the site ACUs. Value range: 0 to 100. "
|
|
::= { hwAcDistributionsGroup 4 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.5.1.5
|
|
hwSetAcsUpperVoltLimit OBJECT-TYPE
|
|
SYNTAX Unsigned32 (60..500)
|
|
UNITS "V"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Upper threshold of the AC voltage alarm, can be configured by users. Value range: 60 to 500, unit: V, and the value is an integer (.0)."
|
|
::= { hwAcDistributionsGroup 5 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.5.1.6
|
|
hwSetAcsLowerVoltLimit OBJECT-TYPE
|
|
SYNTAX Unsigned32 (60..500)
|
|
UNITS "V"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Lower threshold of the AC voltage alarm, can be configured by users. Value range: 60 to 500, unit: V, and the value is an integer (.0)."
|
|
::= { hwAcDistributionsGroup 6 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.5.2
|
|
hwAcDistribution OBJECT IDENTIFIER ::= { hwSiteAcDistributions 2 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.1.5.5
|
|
-- 1.3.6.1.4.1.2011.6.164.1.5.2.1
|
|
hwAcInputTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF HwAcInputEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"AC input table. Use this table to get AC distribution unit ID, AC distribution unit name, A phase or AB line voltage, B phase or BC line voltage, C phase or CA line voltage, AC input breaker status, as well as AC output breakers quantity, which defines hwAcOutputBreakerTable row number. This table's index is hwAcInputIndex, clone AC input table."
|
|
::= { hwAcDistribution 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.1.5.5.1
|
|
-- 1.3.6.1.4.1.2011.6.164.1.5.2.1.1
|
|
hwAcInputEntry OBJECT-TYPE
|
|
SYNTAX HwAcInputEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"AC input table entry."
|
|
INDEX { hwAcInputIndex }
|
|
::= { hwAcInputTable 1 }
|
|
|
|
|
|
HwAcInputEntry ::=
|
|
SEQUENCE {
|
|
hwAcInputIndex
|
|
Integer32,
|
|
hwAcEquipId
|
|
Unsigned32,
|
|
hwAcEquipName
|
|
OCTET STRING,
|
|
hwApOrAblVoltage
|
|
Unsigned32,
|
|
hwBpOrBclVoltage
|
|
Unsigned32,
|
|
hwCpOrCalVoltage
|
|
Unsigned32,
|
|
hwAphaseCurrent
|
|
Integer32,
|
|
hwBphaseCurrent
|
|
Integer32,
|
|
hwCphaseCurrent
|
|
Integer32,
|
|
hwAcInputBreakersQuantity
|
|
Unsigned32,
|
|
hwAcInputOperStatus
|
|
INTEGER,
|
|
hwAcRowStatus
|
|
RowStatus
|
|
}
|
|
|
|
-- 1.3.6.1.4.1.2011.6.1.5.5.1.1
|
|
-- 1.3.6.1.4.1.2011.6.164.1.5.2.1.1.1
|
|
hwAcInputIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..100)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"ACU device table index, which value range: 1 to 100. Lines of the device list are restricted by the total quantity of ACUs (hwAcsInputQuantity)."
|
|
::= { hwAcInputEntry 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.5.2.1.1.2
|
|
hwAcEquipId OBJECT-TYPE
|
|
SYNTAX Unsigned32 (4001..4100)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"ACU device ID, which users can configure. Value range: 004,001 to 004,100, in which The first digits indicate the device type and the last three digits indicate the device SN."
|
|
::= { hwAcInputEntry 2 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.5.2.1.1.3
|
|
hwAcEquipName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (0..63))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"ACU device name, of the character string type, is used to specify the alternating current unit (ACU). Users can configure it.
|
|
Otherwise, the configured character can not be any other languages except English."
|
|
::= { hwAcInputEntry 3 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.1.5.5.1.5
|
|
-- 1.3.6.1.4.1.2011.6.164.1.5.2.1.1.4
|
|
hwApOrAblVoltage OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..5000)
|
|
UNITS "V"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"ACU A-phase or AB-line voltage. Value range: 0 to 500, unit: V, and the value is accurate to one decimal place (.1)."
|
|
::= { hwAcInputEntry 4 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.1.5.5.1.6
|
|
-- 1.3.6.1.4.1.2011.6.164.1.5.2.1.1.5
|
|
hwBpOrBclVoltage OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..5000)
|
|
UNITS "V"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"ACU B-phase or BC-line voltage. Value range: 0 to 500, unit: V, and the value is accurate to one decimal place (.1)."
|
|
::= { hwAcInputEntry 5 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.1.5.5.1.7
|
|
-- 1.3.6.1.4.1.2011.6.164.1.5.2.1.1.6
|
|
hwCpOrCalVoltage OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..5000)
|
|
UNITS "V"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"ACU C-phase or CA-line voltage. Value range: 0 to 500, unit: V, and the value is accurate to one decimal place (.1)."
|
|
::= { hwAcInputEntry 6 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.1.5.5.1.11
|
|
-- 1.3.6.1.4.1.2011.6.164.1.5.2.1.1.7
|
|
hwAphaseCurrent OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1000)
|
|
UNITS "A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"ACU A-phase current. It is an analog parameter collected by the ACU in real time. Value range: 0 to 100, unit: A, and the value is accurate to one decimal place (.1)."
|
|
::= { hwAcInputEntry 7 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.1.5.5.1.12
|
|
-- 1.3.6.1.4.1.2011.6.164.1.5.2.1.1.8
|
|
hwBphaseCurrent OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1000)
|
|
UNITS "A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"ACU B-phase current. It is an analog parameter collected by the ACU in real time. Value range: 0 to 100, unit: A, and the value is accurate to one decimal place (.1)."
|
|
::= { hwAcInputEntry 8 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.1.5.5.1.13
|
|
-- 1.3.6.1.4.1.2011.6.164.1.5.2.1.1.9
|
|
hwCphaseCurrent OBJECT-TYPE
|
|
SYNTAX Integer32 (0..1000)
|
|
UNITS "A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"ACU C-phase current. It is an analog parameter collected by the ACU in real time. Value range: 0 to 100, unit: A, and the value is accurate to one decimal place (.1)."
|
|
::= { hwAcInputEntry 9 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.5.2.1.1.10
|
|
hwAcInputBreakersQuantity OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..100)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Quantity of the AC air circuit breakers.
|
|
As the ACU lower-level subset, the node indicates the quantity of the output air circuit breakers contained by each ACU lower-level subset. Value range: 0 to 100.
|
|
"
|
|
::= { hwAcInputEntry 10 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.5.2.1.1.99
|
|
hwAcInputOperStatus OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
normal(1),
|
|
acOff(2),
|
|
acAbsent(3),
|
|
voltHigh(4),
|
|
voltLow(5),
|
|
alarmResume(254),
|
|
other(255)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of the site AC distribution uint. It is an enumeration type:
|
|
If the enumeration value is 1, it indicates that the site AC distribution uint is in the normal state;
|
|
If the enumeration value is 2, it indicates that AC distribution uint power off;
|
|
If the enumeration value is 3, it indicates that AC input phase absent;
|
|
If the enumeration value is 4, it indicates that AC voltage is over upper alarm threshold;
|
|
If the enumeration value is 5, it indicates that AC voltage is under lower alarm threshold;
|
|
If the enumeration value is 254, it indicates AC distribution uint alarm resume;
|
|
If the enumeration value is 255, it indicates AC distribution uint operation status unknown.
|
|
"
|
|
::= { hwAcInputEntry 99 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.1.5.5.1.16
|
|
-- 1.3.6.1.4.1.2011.6.164.1.5.2.1.1.100
|
|
hwAcRowStatus OBJECT-TYPE
|
|
SYNTAX RowStatus
|
|
MAX-ACCESS read-create
|
|
STATUS current
|
|
DESCRIPTION
|
|
"RowStatus of ACU."
|
|
::= { hwAcInputEntry 100 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.5.2.2
|
|
hwAcInputBreakerTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF HwAcInputBreakerEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ac input breaker table. Use this table to get AC input breaker equipment ID, AC input breaker equipment name, and AC input breaker status. This table's index is hwAcInputBreakerIndex, which qualificated by hwAcInputBreakersQuantity in hwAcInputTable, clone Ac input breaker table."
|
|
::= { hwAcDistribution 2 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.5.2.2.1
|
|
hwAcInputBreakerEntry OBJECT-TYPE
|
|
SYNTAX HwAcInputBreakerEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ac input breaker table entry."
|
|
INDEX { hwAcInputIndex, hwAcInputBreakerIndex }
|
|
::= { hwAcInputBreakerTable 1 }
|
|
|
|
|
|
HwAcInputBreakerEntry ::=
|
|
SEQUENCE {
|
|
hwAcInputBreakerIndex
|
|
Integer32,
|
|
hwAcInputBreakerEquipId
|
|
Unsigned32,
|
|
hwAcInputBreakerEquipName
|
|
OCTET STRING,
|
|
hwAcInputBreakerOperStatus
|
|
INTEGER,
|
|
hwAcInputBreakerRowStatus
|
|
RowStatus
|
|
}
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.5.2.2.1.1
|
|
hwAcInputBreakerIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..100)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Device table index of the AC air circuit breaker. Value range: 1 to 100.
|
|
An input air circuit breaker device can be uniquely identified through the ACU table index and device index of the AC air circuit breaker. "
|
|
::= { hwAcInputBreakerEntry 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.5.2.2.1.2
|
|
hwAcInputBreakerEquipId OBJECT-TYPE
|
|
SYNTAX Unsigned32 (5001..5100)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"AC input air circuit breaker ID. Value range: 005,001 to 005,100. The first digits indicate the device type and the last three digits indicate the device SN."
|
|
::= { hwAcInputBreakerEntry 2 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.5.2.2.1.3
|
|
hwAcInputBreakerEquipName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (0..63))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"AC input air circuit breaker name, of the character string type, can configured by users.
|
|
Otherwise, the configured character can not be any other languages except English."
|
|
::= { hwAcInputBreakerEntry 3 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.5.2.2.1.99
|
|
hwAcInputBreakerOperStatus OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
normal(1),
|
|
disconnect(2),
|
|
alarmResume(254),
|
|
other(255)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Operation state of the site AC input breaker. It is an enumeration type:
|
|
If the enumeration value is 1, it indicates that the site AC input breaker is in the normal state;
|
|
If the enumeration value is 2, it indicates that the AC input breaker disconnect;
|
|
If the enumeration value is 254, it indicates AC input breaker alarm resume;
|
|
If the enumeration value is 255, it indicates AC input breaker operation status unknown.
|
|
"
|
|
::= { hwAcInputBreakerEntry 99 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.5.2.2.1.100
|
|
hwAcInputBreakerRowStatus OBJECT-TYPE
|
|
SYNTAX RowStatus
|
|
MAX-ACCESS read-create
|
|
STATUS current
|
|
DESCRIPTION
|
|
"RowStatus of AC input breaker."
|
|
::= { hwAcInputBreakerEntry 100 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.6
|
|
hwSiteDcDistributions OBJECT IDENTIFIER ::= { hwSiteMonitorMIBObjects 6 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.6.1
|
|
hwDcDistributionsGroup OBJECT IDENTIFIER ::= { hwSiteDcDistributions 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.6.1.1
|
|
hwDcsGroupId OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"DC group ID: unique ID of the DC group. in which The first digits indicate the device type and the last three digits indicate the device SN. If the last three digits are 000, it indicates a virtual device."
|
|
::= { hwDcDistributionsGroup 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.6.1.2
|
|
hwDcsGroupName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (0..63))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Device name of the DC group, of the character string type, can be configured by users.
|
|
Otherwise, the configured character can not be any other languages except English."
|
|
::= { hwDcDistributionsGroup 2 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.6.1.3
|
|
hwDcsTotalVoltage OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..600)
|
|
UNITS "V"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total voltage of the DC group. Value range: 0 to 60, unit: V, and the value is accurate to one decimal place (.1)."
|
|
::= { hwDcDistributionsGroup 3 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.6.1.4
|
|
hwDcsTotalCurrent OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..1000000)
|
|
UNITS "A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total current of the DC group. Value range: 0 to 10000, unit: A, and the value is accurate to one decimal place (.1). "
|
|
::= { hwDcDistributionsGroup 4 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.6.1.5
|
|
hwDcsTotalPower OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..600000)
|
|
UNITS "W"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total power of the DC group. Value range: 0 to 10000, unit: W, and the value is an integer (.0)."
|
|
::= { hwDcDistributionsGroup 5 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.6.1.6
|
|
hwDcsTotalQuantity OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..100)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total quantity of the DC units, and its Value range: 0 to 100."
|
|
::= { hwDcDistributionsGroup 6 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.6.1.7
|
|
hwSetDcsUpperVoltLimit OBJECT-TYPE
|
|
SYNTAX Unsigned32 (300..600)
|
|
UNITS "V"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Upper threshold of the DC voltage alarm, can be configued by users. Value range: 30 to 60, unit: V, and the value is accurate to one decimal space (.1)."
|
|
::= { hwDcDistributionsGroup 7 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.6.1.8
|
|
hwSetDcsLowerVoltLimit OBJECT-TYPE
|
|
SYNTAX Unsigned32 (300..600)
|
|
UNITS "V"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Lower threshold of the DC voltage alarm, can be configued by users. Value range: 30 to 60, unit: V, and the value is accurate to one decimal space (.1)."
|
|
::= { hwDcDistributionsGroup 8 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.6.2
|
|
hwDcDistribution OBJECT IDENTIFIER ::= { hwSiteDcDistributions 2 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.6.2.1
|
|
hwDcOutputTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF HwDcOutputEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"DC output table. Use this table to get DC distribution unit ID, DC distribution unit name, DC output voltage, DC output power, and loads quantity in each DC distribution unit, which defines hwLoadsOutputTable row number. This table's index is hwDcOutputIndex, clone Dc output table."
|
|
::= { hwDcDistribution 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.6.2.1.1
|
|
hwDcOutputEntry OBJECT-TYPE
|
|
SYNTAX HwDcOutputEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Dc output table entry."
|
|
INDEX { hwDcOutputIndex }
|
|
::= { hwDcOutputTable 1 }
|
|
|
|
|
|
HwDcOutputEntry ::=
|
|
SEQUENCE {
|
|
hwDcOutputIndex
|
|
Integer32,
|
|
hwDcOutputEquipId
|
|
Unsigned32,
|
|
hwDcOutputEquipName
|
|
OCTET STRING,
|
|
hwDcOutputVoltage
|
|
Unsigned32,
|
|
hwDcOutputCurrent
|
|
Unsigned32,
|
|
hwDcOutputPower
|
|
Unsigned32,
|
|
hwLoadsQuantity
|
|
Unsigned32,
|
|
hwDcOutputOperStatus
|
|
INTEGER,
|
|
hwDcOutputRowStatus
|
|
RowStatus
|
|
}
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.6.2.1.1.1
|
|
hwDcOutputIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..100)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Device table index of the DC units, which value range: 1 to 100. Lines of the device list are restricted by the total quantity of DC units (hwDcsQuantity)."
|
|
::= { hwDcOutputEntry 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.6.2.1.1.2
|
|
hwDcOutputEquipId OBJECT-TYPE
|
|
SYNTAX Unsigned32 (6001..6100)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"DC unit device ID, which value range: 006,001 to 006,100. The first digits indicate the device type and the last three digits indicate the device SN. "
|
|
::= { hwDcOutputEntry 2 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.6.2.1.1.3
|
|
hwDcOutputEquipName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (0..63))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"DC unit device name, of the character string type, can be configued by users.
|
|
Otherwise, the configured character can not be any other languages except English."
|
|
::= { hwDcOutputEntry 3 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.6.2.1.1.4
|
|
hwDcOutputVoltage OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..600)
|
|
UNITS "V"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"DC output voltage. It is an analog parameter collected by the DC power in real time. Value range: 0 to 60, unit: V, and the value is accurate to one decimal space (.1)."
|
|
::= { hwDcOutputEntry 4 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.6.2.1.1.5
|
|
hwDcOutputCurrent OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..100000)
|
|
UNITS "A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"DC output current. It is an analog parameter collected by the DC power in real time. Value range: 0 to 10000, unit: A, and the value is accurate to one decimal space (.1)."
|
|
::= { hwDcOutputEntry 5 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.6.2.1.1.6
|
|
hwDcOutputPower OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..600000)
|
|
UNITS "W"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"DC output power. It is an analog parameter collected by the DC power in real time. Value range: 0 to 600000, unit: W, and the value is an integer (.0)."
|
|
::= { hwDcOutputEntry 6 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.6.2.1.1.7
|
|
hwLoadsQuantity OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..100)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Quantity of the DC load output branches, which value range: 0 to 100.
|
|
As the DC unit lower-level subset, the node indicates the quantity of the DC load output branches contained by each DC unit lower-level subset."
|
|
::= { hwDcOutputEntry 7 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.6.2.1.1.99
|
|
hwDcOutputOperStatus OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
normal(1),
|
|
voltHigh(2),
|
|
voltLow(3),
|
|
alarmResume(254),
|
|
other(255)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of the site DC distribution uint. It is an enumeration type:
|
|
If the enumeration value is 1, it indicates that the site DC distribution uint is in the normal state;
|
|
If the enumeration value is 2, it indicates that DC voltage is over the upper alarm threshold;
|
|
If the enumeration value is 3, it indicates that DC voltage is under the lower alarm threshold;
|
|
If the enumeration value is 254, it indicates DC distribution uint alarm resume;
|
|
If the enumeration value is 255, it indicates DC distribution uint operation status unknown.
|
|
"
|
|
::= { hwDcOutputEntry 99 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.6.2.1.1.100
|
|
hwDcOutputRowStatus OBJECT-TYPE
|
|
SYNTAX RowStatus
|
|
MAX-ACCESS read-create
|
|
STATUS current
|
|
DESCRIPTION
|
|
"RowStatus of Dc output equipments."
|
|
::= { hwDcOutputEntry 100 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.6.2.2
|
|
hwLoadBranchTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF HwLoadBranchEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Loads output table. Use this table to get load branch equipment ID, load branch equipment name, load branch current, and load branch power. This table's index is hwLoadBranchIndex, which qualificated by hwloadsQuantity in hwDcOutputTable, clone loads output table."
|
|
::= { hwDcDistribution 2 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.6.2.2.1
|
|
hwLoadBranchEntry OBJECT-TYPE
|
|
SYNTAX HwLoadBranchEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Loads output table entry."
|
|
INDEX { hwDcOutputIndex, hwLoadBranchIndex }
|
|
::= { hwLoadBranchTable 1 }
|
|
|
|
|
|
HwLoadBranchEntry ::=
|
|
SEQUENCE {
|
|
hwLoadBranchIndex
|
|
Integer32,
|
|
hwLoadBranchEquipId
|
|
Unsigned32,
|
|
hwLoadBranchEquipName
|
|
OCTET STRING,
|
|
hwLoadBranchCurrent
|
|
Unsigned32,
|
|
hwLoadBranchPower
|
|
Unsigned32,
|
|
hwLoadBranchOperStatus
|
|
INTEGER,
|
|
hwLoadBranchRowStatus
|
|
RowStatus
|
|
}
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.6.2.2.1.1
|
|
hwLoadBranchIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..100)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Device table index of the DC load output branch, which value range: 1 to 100.
|
|
A DC load output branch can be uniquely identified through the DC unit table index and device index of the DC load output branch."
|
|
::= { hwLoadBranchEntry 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.6.2.2.1.2
|
|
hwLoadBranchEquipId OBJECT-TYPE
|
|
SYNTAX Unsigned32 (7001..7100)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Device ID of the DC load output branch. Value range: 007,001 to 007,100. The first digits indicate the device type and the last three digits indicate the SN of the device. "
|
|
::= { hwLoadBranchEntry 2 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.6.2.2.1.3
|
|
hwLoadBranchEquipName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (0..63))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Device name of the DC load output branch, of the character string type, can be configured by users.
|
|
Otherwise, the configured character can not be any other languages except English."
|
|
::= { hwLoadBranchEntry 3 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.6.2.2.1.4
|
|
hwLoadBranchCurrent OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..100000)
|
|
UNITS "A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"DC load output branch current. It is an analog parameter collected by the load branch in real time. Value range: 0 to 10000, unit: A, and the value is accurate to one decimal space (.1)."
|
|
::= { hwLoadBranchEntry 4 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.6.2.2.1.5
|
|
hwLoadBranchPower OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..600000)
|
|
UNITS "W"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"DC load branch power. It is an analog parameter collected by the DC power in real time. Value range: 0 to 600000, unit: W, and the value is an integer (.0)."
|
|
::= { hwLoadBranchEntry 5 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.6.2.2.1.99
|
|
hwLoadBranchOperStatus OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
normal(1),
|
|
disconnect(2),
|
|
alarmResume(254),
|
|
other(255)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of the site load output branch. It is an enumeration type:
|
|
If the enumeration value is 1, it indicates that the site load output branch is in the normal state;
|
|
If the enumeration value is 2, it indicates that the load output branch disconnect;
|
|
If the enumeration value is 254, it indicates load output branch alarm resume;
|
|
If the enumeration value is 255, it indicates load output branch operation status unknown.
|
|
"
|
|
::= { hwLoadBranchEntry 99 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.6.2.2.1.100
|
|
hwLoadBranchRowStatus OBJECT-TYPE
|
|
SYNTAX RowStatus
|
|
MAX-ACCESS read-create
|
|
STATUS current
|
|
DESCRIPTION
|
|
"RowStatus of loads output branch."
|
|
::= { hwLoadBranchEntry 100 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.7
|
|
hwLvdUnits OBJECT IDENTIFIER ::= { hwSiteMonitorMIBObjects 7 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.7.1
|
|
hwLvdsGroup OBJECT IDENTIFIER ::= { hwLvdUnits 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.7.1.1
|
|
hwLvdsGroupId OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"LVD unit group ID. It is the unique ID of the LVD unit group. The first digits indicate the device type. The last three digits indicate the device SN. If the last three digits are 000, it indicates a virtual device."
|
|
::= { hwLvdsGroup 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.7.1.2
|
|
hwLvdsGroupName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (0..63))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Low-voltage power-off unit group name, of the character string type, can be configured by users.
|
|
Otherwise, the configured character can not be any other languages except English."
|
|
::= { hwLvdsGroup 2 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.7.1.3
|
|
hwLvdsTotalQuantity OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..100)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total quantity of power-off units. Value range: 0 to 100."
|
|
::= { hwLvdsGroup 3 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.7.2
|
|
hwLvdUnit OBJECT IDENTIFIER ::= { hwLvdUnits 2 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.7.2.1
|
|
hwLvdBranchTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF HwLvdBranchEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Power-off unit table. Use this table to get Lvd unit equipment ID and power-off unit equipment name, set power-off enable and power-off voltage, as well as control power-off unit disconnected. This table's index is hwLvdBranchIndex, which qualificated by hwLvdsQuantity, clone power-off unit table."
|
|
::= { hwLvdUnit 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.7.2.1.1
|
|
hwLvdBranchEntry OBJECT-TYPE
|
|
SYNTAX HwLvdBranchEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Power-off table entry."
|
|
INDEX { hwLvdBranchIndex }
|
|
::= { hwLvdBranchTable 1 }
|
|
|
|
|
|
HwLvdBranchEntry ::=
|
|
SEQUENCE {
|
|
hwLvdBranchIndex
|
|
Integer32,
|
|
hwLvdUnitEquipId
|
|
Unsigned32,
|
|
hwLvdUnitEquipName
|
|
OCTET STRING,
|
|
hwSetLvdEnable
|
|
INTEGER,
|
|
hwSetLvdVoltage
|
|
Integer32,
|
|
hwCtrlLvd
|
|
INTEGER,
|
|
hwLvdBranchOperStatus
|
|
INTEGER,
|
|
hwLvdBranchRowStatus
|
|
RowStatus
|
|
}
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.7.2.1.1.1
|
|
hwLvdBranchIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..100)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Device table index of a power-off unit. Value range: 1 to 100. Lines of the device list are restricted by the total quantity of the power-off units (hwLvdsTotalQuantity). "
|
|
::= { hwLvdBranchEntry 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.7.2.1.1.2
|
|
hwLvdUnitEquipId OBJECT-TYPE
|
|
SYNTAX Unsigned32 (8001..8100)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Device ID of a power-off unit. Value range: 8001 to 8100. The first digits indicate the device type and the last three digits indicate the device SN. "
|
|
::= { hwLvdBranchEntry 2 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.7.2.1.1.3
|
|
hwLvdUnitEquipName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (0..63))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Device name of a power-off unit, of the character string type, is used to specify the low-voltage power-off unit. Users can configure it.
|
|
Otherwise, the configured character can not be any other languages except English. "
|
|
::= { hwLvdBranchEntry 3 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.7.2.1.1.4
|
|
hwSetLvdEnable OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
enabled(1),
|
|
disabled(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Control power-off unit enabling. It is an enumeration value, and users actively set it.
|
|
If the enumeration value is 1, it means to enable the power-off unit;
|
|
If the enumeration value is 2, it means to disable the power-off unit.
|
|
When the power-off unit control is not configured, the power-off unit is enabled by default."
|
|
::= { hwLvdBranchEntry 4 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.7.2.1.1.5
|
|
hwSetLvdVoltage OBJECT-TYPE
|
|
SYNTAX Integer32 (350..600)
|
|
UNITS "V"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Low-voltage power-off voltage of a power-off unit can be configured by users. Its value range: 35 to 60, unit: V, and the value is accurate to one decimal space (.1)."
|
|
::= { hwLvdBranchEntry 5 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.7.2.1.1.6
|
|
hwCtrlLvd OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
powerOff(1),
|
|
powerOn(2),
|
|
nullOper(255)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Control of the power-off unit. It is an enumeration value, users control it manually.
|
|
If the NMS notifies the SNMP agent that the node is set to 1, it means to power off the power-off unit;
|
|
If the NMS notifies the SNMP agent that the node is set to 2, it means that the background controls the power-on of the LVD unit.
|
|
"
|
|
::= { hwLvdBranchEntry 6 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.7.2.1.1.99
|
|
hwLvdBranchOperStatus OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
normal(1),
|
|
lowVoltOff(2),
|
|
backgroundOff(3),
|
|
localManualOff(4),
|
|
lowTempOff(5),
|
|
highTempOff(6),
|
|
alarmResume(254),
|
|
other(255)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of the site LVD uint. It is an enumeration type:
|
|
If the enumeration value is 1, it indicates that the site LVD uint is in the normal state;
|
|
If the enumeration value is 2, it indicates that the power-off uint disconnect for low voltage;
|
|
If the enumeration value is 3, it indicates that the power-off uint disconnect bakeground;
|
|
If the enumeration value is 4, it indicates that the power-off uint local disconnect manually;
|
|
If the enumeration value is 5, it indicates that the power-off uint disconnect for under temperature;
|
|
If the enumeration value is 6, it indicates that the power-off uint disconnect for over temperature;
|
|
If the enumeration value is 254, it indicates that the power-off uint alarm resume;
|
|
If the enumeration value is 255, it indicates LVD uint operation status unknown. "
|
|
::= { hwLvdBranchEntry 99 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.7.2.1.1.100
|
|
hwLvdBranchRowStatus OBJECT-TYPE
|
|
SYNTAX RowStatus
|
|
MAX-ACCESS read-create
|
|
STATUS current
|
|
DESCRIPTION
|
|
"RowStatus of lvd table."
|
|
::= { hwLvdBranchEntry 100 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8
|
|
hwSiteEnvUnits OBJECT IDENTIFIER ::= { hwSiteMonitorMIBObjects 8 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.1
|
|
hwEnvUnitsGroup OBJECT IDENTIFIER ::= { hwSiteEnvUnits 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.1.1
|
|
hwEnvUnitsGroupId OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unit group ID of the site environment. It is the unique ID of the unit group on the site. The first digits indicate the device type. The last three digits indicate the device SN. If the last three digits are 000, it indicates a virtual device. "
|
|
::= { hwEnvUnitsGroup 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.1.2
|
|
hwEnvUnitsGroupName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (0..63))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unit group name of the site environment, of the character string type, can be configured by users.
|
|
Otherwise, the configured character can not be any other languages except English."
|
|
::= { hwEnvUnitsGroup 2 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.1.3
|
|
hwCtrlSmokeReset OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
normal(1),
|
|
reset(2),
|
|
nullOper(255)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Smoke sensor reset. It manually controls clearance of the smoke sensor alarm, and this node is of the enumeration type.
|
|
If the enumeration value is 1, it indicates that the reset of the smoke sensor is not required.
|
|
If the enumeration value of the node is 2, it indicates that the background controls the reset of the smoke sensor.
|
|
"
|
|
::= { hwEnvUnitsGroup 3 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.1.4
|
|
hwCtrlDoorReset OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
normal(1),
|
|
reset(2),
|
|
nullOper(255)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Door actuator reset control. It manually controls clearance of the door actuator alarm. This node is of the enumeration type.
|
|
If the enumeration value is 1, it indicates that clearance of the door actuator is not required;
|
|
If the enumeration value is 2, it indicates that the background controls clearance of the door actuator. "
|
|
::= { hwEnvUnitsGroup 4 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.1.5
|
|
hwCtrlBuzzerEnable OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
enable(1),
|
|
disable(2),
|
|
nullOper(255)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Buzzer enabling. It manually controls the enabling of the buzzer alarm. This node is of the enumeration type.
|
|
When the enumeration value is 1, it means to enable the buzzer;
|
|
When the enumeration value is 2, it means to disable the buzzer.
|
|
"
|
|
::= { hwEnvUnitsGroup 5 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.1.6
|
|
hwEnvTempSensorsTotalQuantity OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..256)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Quantity of the environment temperature sensors, and its value range: 0 to 256."
|
|
::= { hwEnvUnitsGroup 6 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.1.7
|
|
hwEnvHumiSensorsTotalQuantity OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..256)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Quantity of the environment humidity sensors, and its value range: 0 to 256."
|
|
::= { hwEnvUnitsGroup 7 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.1.8
|
|
hwSpareDigitalsTotalQuantity OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..256)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Quantity of the Spare digitals, and its value range: 0 to 256."
|
|
::= { hwEnvUnitsGroup 8 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.2
|
|
hwEnvSensor OBJECT IDENTIFIER ::= { hwSiteEnvUnits 2 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.2.1
|
|
hwEnvTempSensorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF HwEnvTempSensorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Site environment temperature table. Use this table to get environment temperature equipment ID, environment temperature equipment name, and environment temperature, set environment temperature upper limit, environment temperature lower limit, and environment temperature alarm enable. This table's index is hwEnvTempSensorIndex, which qualificated by hwEnvTempSensorsQuantity, clone site environment temperature table."
|
|
::= { hwEnvSensor 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.2.1.1
|
|
hwEnvTempSensorEntry OBJECT-TYPE
|
|
SYNTAX HwEnvTempSensorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Site environment temperature table entry."
|
|
INDEX { hwEnvTempSensorIndex }
|
|
::= { hwEnvTempSensorTable 1 }
|
|
|
|
|
|
HwEnvTempSensorEntry ::=
|
|
SEQUENCE {
|
|
hwEnvTempSensorIndex
|
|
Integer32,
|
|
hwEnvTempEquipId
|
|
Unsigned32,
|
|
hwEnvTempEquipName
|
|
OCTET STRING,
|
|
hwEnvTemperature
|
|
Integer32,
|
|
hwSetEnvTempUpperLimit
|
|
Integer32,
|
|
hwSetEnvTempLowerLimit
|
|
Integer32,
|
|
hwSetEnvTempMeasureUpperLimit
|
|
Integer32,
|
|
hwSetEnvTempMeasureLowerLimit
|
|
Integer32,
|
|
hwSetEnvTempAlarmEnable
|
|
INTEGER,
|
|
hwEnvTempSensorOperStatus
|
|
INTEGER,
|
|
hwEnvTempSensorRowStatus
|
|
RowStatus
|
|
}
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.2.1.1.1
|
|
hwEnvTempSensorIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table index of the environment temperature sensors. Value range: 1 to 256. Lines of the device table are restricted by the quantity of environment temperature sensors (hwEnvTempSensorsTotalQuantity). "
|
|
::= { hwEnvTempSensorEntry 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.2.1.1.2
|
|
hwEnvTempEquipId OBJECT-TYPE
|
|
SYNTAX Unsigned32 (9001..9255)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Environment temperature sensor ID. Value range: 009'001 to 009'255, in which the first digits indicate the device type and the last three digits indicate the device SN. "
|
|
::= { hwEnvTempSensorEntry 2 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.2.1.1.3
|
|
hwEnvTempEquipName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (0..63))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Environment temperature sensor name, of the character string type, is used to specify an environment temperature sensor. Users can configure it.
|
|
Otherwise, the configured character can not be any other languages except English. "
|
|
::= { hwEnvTempSensorEntry 3 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.2.1.1.4
|
|
hwEnvTemperature OBJECT-TYPE
|
|
SYNTAX Integer32 (-50..100)
|
|
UNITS "centigrades"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Environment temperature. It is an environment parameter collected in real time. Value range: -50 to +100, unit: centigrade (°„C), and the value is an integer (.0).
|
|
If the value is -1024, it indicates that the temperature sensor is not configured."
|
|
::= { hwEnvTempSensorEntry 4 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.2.1.1.5
|
|
hwSetEnvTempUpperLimit OBJECT-TYPE
|
|
SYNTAX Integer32 (-50..100)
|
|
UNITS "centigrades"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Upper threshold of the environment temperature alarm, can be configured by users. Value range: -50 to 100, unit: centigrade (°„C), and the value is an integer (.0)."
|
|
::= { hwEnvTempSensorEntry 5 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.2.1.1.6
|
|
hwSetEnvTempLowerLimit OBJECT-TYPE
|
|
SYNTAX Integer32 (-50..100)
|
|
UNITS "centigrades"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Lower threshold of the environment temperature alarm, can be configured by users. Value range: -50 to 100, unit: centigrade (°„C), and the value is an integer (.0)."
|
|
::= { hwEnvTempSensorEntry 6 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.2.1.1.7
|
|
hwSetEnvTempMeasureUpperLimit OBJECT-TYPE
|
|
SYNTAX Integer32 (0..100)
|
|
UNITS "centigrades"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Upper threshold of the environment temperature measurement, can be configured by users. Value range: 0 to 100, unit: centigrade (°„C), and the value is an integer (.0)."
|
|
::= { hwEnvTempSensorEntry 7 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.2.1.1.8
|
|
hwSetEnvTempMeasureLowerLimit OBJECT-TYPE
|
|
SYNTAX Integer32 (-50..0)
|
|
UNITS "centigrades"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Lower threshold of the environment temperature measurement, can be configured by users. Value range: -50 to 0, unit: centigrade (°„C), and the value is an integer (.0)."
|
|
::= { hwEnvTempSensorEntry 8 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.2.1.1.9
|
|
hwSetEnvTempAlarmEnable OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
enable(1),
|
|
disable(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Environment temperature alarm. It is an enumeration type:
|
|
If the enumeration value is 1, enable the alarm of the environment temperature;
|
|
If the enumeration value is 2, disable the alarm of the environment temperature. "
|
|
::= { hwEnvTempSensorEntry 9 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.2.1.1.99
|
|
hwEnvTempSensorOperStatus OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
normal(1),
|
|
tempHigh(2),
|
|
tempLow(3),
|
|
notInslot(4),
|
|
alarmResume(254),
|
|
other(255)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of the site environment temperature sensor. It is an enumeration type:
|
|
If the enumeration value is 1, it indicates that the site environment temperature sensor is in the normal state;
|
|
If the enumeration value is 2, it indicates that the environment temperature sensor is over temperature;
|
|
If the enumeration value is 3, it indicates that the environment temperature sensor is under temperature;
|
|
If the enumeration value is 4, it indicates that the environment temperature sensor is not in slot;
|
|
If the enumeration value is 254, it indicates that environment temperature alarm resume;
|
|
If the enumeration value is 255, it indicates environment temperature sensor operation status unknown.
|
|
|
|
"
|
|
::= { hwEnvTempSensorEntry 99 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.2.1.1.100
|
|
hwEnvTempSensorRowStatus OBJECT-TYPE
|
|
SYNTAX RowStatus
|
|
MAX-ACCESS read-create
|
|
STATUS current
|
|
DESCRIPTION
|
|
"RowStatus of Environment temperature table."
|
|
::= { hwEnvTempSensorEntry 100 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.2.2
|
|
hwEnvHumiSensorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF HwEnvHumiSensorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Environment humidity table. Use this table to get environment humidity equipment ID , environment humidity equipment name, and environment humidity, set environment humidity upper limit, environment humidity lower limit, and environment humidity alarm enable. This table's index is hwEnvHumiSensorIndex, which qualificated by hwEnvHumiSensorIndex, clone site environment humidity table."
|
|
::= { hwEnvSensor 2 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.2.2.1
|
|
hwEnvHumiSensorEntry OBJECT-TYPE
|
|
SYNTAX HwEnvHumiSensorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Environment humidity table entry."
|
|
INDEX { hwEnvHumiSensorIndex }
|
|
::= { hwEnvHumiSensorTable 1 }
|
|
|
|
|
|
HwEnvHumiSensorEntry ::=
|
|
SEQUENCE {
|
|
hwEnvHumiSensorIndex
|
|
Integer32,
|
|
hwEnvHumiEquipId
|
|
Unsigned32,
|
|
hwEnvHumiEquipName
|
|
OCTET STRING,
|
|
hwEnvHumidity
|
|
Integer32,
|
|
hwSetEnvHumidityUpperLimit
|
|
Integer32,
|
|
hwSetEnvHumidityLowerLimit
|
|
Integer32,
|
|
hwSetEnvHumidityMeasureUpperLimit
|
|
Integer32,
|
|
hwSetEnvHumidityMeasureLowerLimit
|
|
Integer32,
|
|
hwSetEnvHumiAlarmEnable
|
|
INTEGER,
|
|
hwEnvHumiSensorOperStatus
|
|
INTEGER,
|
|
hwEnvHumiSensorRowStatus
|
|
RowStatus
|
|
}
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.2.2.1.1
|
|
hwEnvHumiSensorIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table index of the environment humility sensors. Value range: 1 to 256. Lines of the device list are restricted by the quantity of environment humility sensors (hwEnvHumiSensorsTotalQuantity). "
|
|
::= { hwEnvHumiSensorEntry 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.2.2.1.2
|
|
hwEnvHumiEquipId OBJECT-TYPE
|
|
SYNTAX Unsigned32 (10001..10255)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Environment humility sensor ID, can be configured by users. Value range: 010'001 to 010'255, in which the first digits indicate the device type and the last three digits indicate the device SN."
|
|
::= { hwEnvHumiSensorEntry 2 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.2.2.1.3
|
|
hwEnvHumiEquipName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (0..63))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Environment humility sensor name, of the character string type, is used to specify an environment humility sensor. Users can configure it.
|
|
Otherwise, the configured character can not be any other languages except English. "
|
|
::= { hwEnvHumiSensorEntry 3 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.2.2.1.4
|
|
hwEnvHumidity OBJECT-TYPE
|
|
SYNTAX Integer32 (0..100)
|
|
UNITS "%RH"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Environment humility. It is an environment parameter collected in real time. Value range: 0 to 100, unit: %RH, and the value is an integer (.0).
|
|
If the value is 255, it indicates that the humidity sensor is not configured."
|
|
::= { hwEnvHumiSensorEntry 4 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.2.2.1.5
|
|
hwSetEnvHumidityUpperLimit OBJECT-TYPE
|
|
SYNTAX Integer32 (0..100)
|
|
UNITS "%RH"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Upper threshold of the environment humility alarm, can be configured by users. Value range: 0 to 100, unit: %RH, and the value is an integer (.0)."
|
|
::= { hwEnvHumiSensorEntry 5 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.2.2.1.6
|
|
hwSetEnvHumidityLowerLimit OBJECT-TYPE
|
|
SYNTAX Integer32 (0..100)
|
|
UNITS "%RH"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Lower threshold of the environment humility alarm, can be configured by users. Value range: 0 to 100, unit: %RH, and the value is an integer (.0)."
|
|
::= { hwEnvHumiSensorEntry 6 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.2.2.1.7
|
|
hwSetEnvHumidityMeasureUpperLimit OBJECT-TYPE
|
|
SYNTAX Integer32 (0..100)
|
|
UNITS "%RH"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Upper threshold of the environment humility measurement, can be configured by users. Value range: 0 to 100, unit: %RH, and the value is an integer (.0)."
|
|
::= { hwEnvHumiSensorEntry 7 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.2.2.1.8
|
|
hwSetEnvHumidityMeasureLowerLimit OBJECT-TYPE
|
|
SYNTAX Integer32 (0..100)
|
|
UNITS "%RH"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Lower threshold of the environment humility measurement, can be configured by users. Value range: 0 to 100, unit: %RH, and the value is an integer (.0)."
|
|
::= { hwEnvHumiSensorEntry 8 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.2.2.1.9
|
|
hwSetEnvHumiAlarmEnable OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
enable(1),
|
|
disable(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Environment humility alarm. It is an enumeration type:
|
|
If the enumeration value is 1, enable the alarm of the environment humility;
|
|
If the enumeration value is 2, disable the alarm of the environment humility.
|
|
The environment humility alarm is enabled by default. "
|
|
::= { hwEnvHumiSensorEntry 9 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.2.2.1.99
|
|
hwEnvHumiSensorOperStatus OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
normal(1),
|
|
humidityHigh(2),
|
|
humidityLow(3),
|
|
notInslot(4),
|
|
alarmResume(254),
|
|
other(255)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of the site environment humidity sensor. It is an enumeration type:
|
|
If the enumeration value is 1, it indicates that the site environment humidity sensor is in the normal state;
|
|
If the enumeration value is 2, it indicates that the environment humidity sensor is over humidity;
|
|
If the enumeration value is 3, it indicates that the environment humidity sensor is under humidity;
|
|
If the enumeration value is 4, it indicates that the environment humidity sensor is not in slot;
|
|
If the enumeration value is 254, it indicates that environment humidity alarm resume;
|
|
If the enumeration value is 255, it indicates environment humidity sensor operation status unknown. "
|
|
::= { hwEnvHumiSensorEntry 99 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.2.2.1.100
|
|
hwEnvHumiSensorRowStatus OBJECT-TYPE
|
|
SYNTAX RowStatus
|
|
MAX-ACCESS read-create
|
|
STATUS current
|
|
DESCRIPTION
|
|
"RowStatus of Environment humidity table."
|
|
::= { hwEnvHumiSensorEntry 100 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.2.3
|
|
hwSpareDigitalTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF HwSpareDigitalEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Spare digital table. Use this table to get Spare digital equipment ID , Spare digital equipment name, and current Spare digital alarm tension, ae well as to set Spare digital alarm enable. This table's index is hwSpareDigitalIndex, which qualificated by hwSpareDigitalsTotalQuantity, clone switch input table."
|
|
::= { hwEnvSensor 3 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.2.3.1
|
|
hwSpareDigitalEntry OBJECT-TYPE
|
|
SYNTAX HwSpareDigitalEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Spare digital table entry."
|
|
INDEX { hwSpareDigitalIndex }
|
|
::= { hwSpareDigitalTable 1 }
|
|
|
|
|
|
HwSpareDigitalEntry ::=
|
|
SEQUENCE {
|
|
hwSpareDigitalIndex
|
|
Integer32,
|
|
hwSpareDigitalEquipId
|
|
Unsigned32,
|
|
hwSpareDigitalEquipName
|
|
OCTET STRING,
|
|
hwSetSpareDigitalAlarmTension
|
|
INTEGER,
|
|
hwSetSpareDigitalAlarmEnable
|
|
INTEGER,
|
|
hwSpareDigitalOperStatus
|
|
INTEGER,
|
|
hwSpareDigitalRowStatus
|
|
RowStatus
|
|
}
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.2.3.1.1
|
|
hwSpareDigitalIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Spare digital table index, which value range: 1 to 256. Lines of the device list are restricted by the quantity of Spare digitals (hwSpareDigitalsTotalQuantity). "
|
|
::= { hwSpareDigitalEntry 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.2.3.1.2
|
|
hwSpareDigitalEquipId OBJECT-TYPE
|
|
SYNTAX Unsigned32 (11001..11255)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Spare digital device ID. Value range: 011'001 to 011'255, in which the first digits indicate the device type and the last three digits indicate the device SN. "
|
|
::= { hwSpareDigitalEntry 2 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.2.3.1.3
|
|
hwSpareDigitalEquipName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (0..63))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Spare digital name, of the character string type, is used to specify Spare digitals. Users can configure it.
|
|
Otherwise, the configured character can not be any other languages except English. "
|
|
::= { hwSpareDigitalEntry 3 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.2.3.1.4
|
|
hwSetSpareDigitalAlarmTension OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
low(0),
|
|
high(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Spare digital alarm state. It is an enumeration value.
|
|
If the value of the node is 0, it indicates a low-tension alarm;
|
|
If the value of the node is 1, it indicates a high-tension alarm. "
|
|
::= { hwSpareDigitalEntry 4 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.2.3.1.5
|
|
hwSetSpareDigitalAlarmEnable OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
enable(1),
|
|
disable(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Spare digital alarm enabling. It is an enumeration type:
|
|
If the enumeration value is 1, it means to enable the alarm;
|
|
If the enumeration value is 2, it means to disable the alarm. "
|
|
::= { hwSpareDigitalEntry 5 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.2.3.1.99
|
|
hwSpareDigitalOperStatus OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
normal(1),
|
|
alarm(2),
|
|
alarmResume(254),
|
|
other(255)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of the site Spare digital. It is an enumeration type:
|
|
If the enumeration value is 1, it indicates that the Spare digital operation state is normal;
|
|
If the enumeration value is 2, it indicates that a alarm occurs on the Spare digital;
|
|
If the enumeration value is 254, it indicates that spare digital alarm resume;
|
|
If the enumeration value is 255, it indicates Spare digital operation status unknown."
|
|
::= { hwSpareDigitalEntry 99 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.8.2.3.1.100
|
|
hwSpareDigitalRowStatus OBJECT-TYPE
|
|
SYNTAX RowStatus
|
|
MAX-ACCESS read-create
|
|
STATUS current
|
|
DESCRIPTION
|
|
"RowStatus of Spare digital device table."
|
|
::= { hwSpareDigitalEntry 100 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9
|
|
hwSitePDEs OBJECT IDENTIFIER ::= { hwSiteMonitorMIBObjects 9 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.1
|
|
hwPDEGroup OBJECT IDENTIFIER ::= { hwSitePDEs 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.1.1
|
|
hwPDEGroupId OBJECT-TYPE
|
|
SYNTAX Unsigned32 (12000..12255)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE unit group ID. It is the unique ID of the PDE unit group. The first digits indicate the device type. The last three digits indicate the device SN. If the last three digits are 000, it indicates a virtual device."
|
|
::= { hwPDEGroup 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.1.2
|
|
hwPDEGroupName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (0..64))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE unit group name, of the character string type, can be configured by users.
|
|
Otherwise, the configured character can not be any other languages except English."
|
|
::= { hwPDEGroup 2 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.1.3
|
|
hwPDEGroupNum OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..100)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE Num,Value range: 0 to 100."
|
|
::= { hwPDEGroup 3 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.1.4
|
|
hwPDEGroupCommNum OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..100)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Communication PDE Num,Value range: 0 to 100."
|
|
::= { hwPDEGroup 4 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.1.5
|
|
hwPDEGroupTotalPower OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..100000)
|
|
UNITS "W"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE Total Power,Value range: 0.0 to 10000.0.Unit: W.and the value is accurate to one decimal space (.1)."
|
|
::= { hwPDEGroup 5 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.1.6
|
|
hwPDEGroupTotalCurrent OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..3000)
|
|
UNITS "A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE Total Current,Value range: 0.0 to 300.0.Unit: A.and the value is accurate to one decimal space (.1)."
|
|
::= { hwPDEGroup 6 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.1.7
|
|
hwPDEGroupCommStatus OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
commOk(1),
|
|
commFail(2),
|
|
unknown(255)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE Communication Status. It is an enumeration type:
|
|
If the enumeration value is 1, it indicates that communication is normal;
|
|
If the enumeration value is 2, it indicates that communication is abnormal.
|
|
If the enumeration value is 255, it indicates that communication is unknown."
|
|
::= { hwPDEGroup 7 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3
|
|
hwPDE OBJECT IDENTIFIER ::= { hwSitePDEs 3 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.1
|
|
hwPDETable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF HwPDEEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE table. Use this table to get PDE equipment ID , PDE equipment name, and current PDE status. This table's index is hwPDEIndex."
|
|
::= { hwPDE 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.1.1
|
|
hwPDEEntry OBJECT-TYPE
|
|
SYNTAX HwPDEEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE table entry."
|
|
INDEX { hwPDEIndex }
|
|
::= { hwPDETable 1 }
|
|
|
|
HwPDEEntry ::=
|
|
SEQUENCE {
|
|
hwPDEIndex
|
|
Integer32,
|
|
hwPDEEquipId
|
|
Unsigned32,
|
|
hwPDEEquipName
|
|
OCTET STRING,
|
|
hwPDETotalRunningTime
|
|
Unsigned32,
|
|
hwPDEBranchNum
|
|
Unsigned32,
|
|
hwPDETotalPower
|
|
Unsigned32,
|
|
hwPDETotalCurrent
|
|
Unsigned32,
|
|
hwPDEBranch1Power
|
|
Unsigned32,
|
|
hwPDEBranch2Power
|
|
Unsigned32,
|
|
hwPDEBranch3Power
|
|
Unsigned32,
|
|
hwPDEBranch4Power
|
|
Unsigned32,
|
|
hwPDEBranch1Current
|
|
Unsigned32,
|
|
hwPDEBranch2Current
|
|
Unsigned32,
|
|
hwPDEBranch3Current
|
|
Unsigned32,
|
|
hwPDEBranch4Current
|
|
Unsigned32,
|
|
hwPDEBranch1Voltage
|
|
Unsigned32,
|
|
hwPDEBranch2Voltage
|
|
Unsigned32,
|
|
hwPDEBranch3Voltage
|
|
Unsigned32,
|
|
hwPDEBranch4Voltage
|
|
Unsigned32,
|
|
hwPDEBranch1Temperature
|
|
Unsigned32,
|
|
hwPDEBranch2Temperature
|
|
Unsigned32,
|
|
hwPDEBranch3Temperature
|
|
Unsigned32,
|
|
hwPDEBranch4Temperature
|
|
Unsigned32,
|
|
hwPDEOperStatus
|
|
INTEGER,
|
|
hwPDERowStatus
|
|
RowStatus
|
|
}
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.1
|
|
hwPDEIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..10)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE table index, which value range: 1 to 10. Lines of the device list are restricted by the quantity of PDE. "
|
|
::= { hwPDEEntry 1 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.2
|
|
hwPDEEquipId OBJECT-TYPE
|
|
SYNTAX Unsigned32 (12001..12255)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE device ID. Value range: 012'001 to 012'255, in which the first digits indicate the device type and the last three digits indicate the device SN. "
|
|
::= { hwPDEEntry 2 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.3
|
|
hwPDEEquipName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (0..64))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE name, of the character string type, is used to specify PDEs. Users can configure it.
|
|
Otherwise, the configured character can not be any other languages except English. "
|
|
::= { hwPDEEntry 3 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.4
|
|
hwPDETotalRunningTime OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..876000)
|
|
UNITS "H"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE Total Running Time,Value range: 0 to 876000.Unit: H."
|
|
::= { hwPDEEntry 4 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.5
|
|
hwPDEBranchNum OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..6)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE Branch Number,Value range: 0 to 6."
|
|
::= { hwPDEEntry 5 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.6
|
|
hwPDETotalPower OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..100000)
|
|
UNITS "W"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE Total Power,Value range: 0.0 to 10000.0.Unit: W.and the value is accurate to one decimal space (.1)."
|
|
::= { hwPDEEntry 6 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.7
|
|
hwPDETotalCurrent OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..300000)
|
|
UNITS "A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE Total Current,Value range: 0.0 to 30000.0.Unit: A.and the value is accurate to one decimal space (.1)."
|
|
::= { hwPDEEntry 7 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.8
|
|
hwPDEBranch1Power OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..1000000)
|
|
UNITS "W"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE Branch1 Power,Value range: 0.0 to 100000.0.Unit: W.and the value is accurate to one decimal space (.1)."
|
|
::= { hwPDEEntry 8 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.9
|
|
hwPDEBranch2Power OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..1000000)
|
|
UNITS "W"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE Branch2 Power,Value range: 0.0 to 100000.0.Unit: W.and the value is accurate to one decimal space (.1)."
|
|
::= { hwPDEEntry 9 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.10
|
|
hwPDEBranch3Power OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..1000000)
|
|
UNITS "W"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE Branch3 Power,Value range: 0.0 to 100000.0.Unit: W.and the value is accurate to one decimal space (.1)."
|
|
::= { hwPDEEntry 10 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.11
|
|
hwPDEBranch4Power OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..1000000)
|
|
UNITS "W"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE Branch4 Power,Value range: 0.0 to 100000.0.Unit: W.and the value is accurate to one decimal space (.1)."
|
|
::= { hwPDEEntry 11 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.12
|
|
hwPDEBranch1Current OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..10000)
|
|
UNITS "A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE Branch1 Current,Value range: 0.0 to 1000.0.Unit: A.and the value is accurate to one decimal space (.1)."
|
|
::= { hwPDEEntry 12 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.13
|
|
hwPDEBranch2Current OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..10000)
|
|
UNITS "A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE Branch2 Current,Value range: 0.0 to 1000.0.Unit: A.and the value is accurate to one decimal space (.1)."
|
|
::= { hwPDEEntry 13 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.14
|
|
hwPDEBranch3Current OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..10000)
|
|
UNITS "A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE Branch3 Current,Value range: 0.0 to 1000.0.Unit: A.and the value is accurate to one decimal space (.1)."
|
|
::= { hwPDEEntry 14 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.15
|
|
hwPDEBranch4Current OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..10000)
|
|
UNITS "A"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE Branch4 Current,Value range: 0.0 to 1000.0.Unit: A.and the value is accurate to one decimal space (.1)."
|
|
::= { hwPDEEntry 15 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.16
|
|
hwPDEBranch1Voltage OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..650)
|
|
UNITS "V"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE Branch1 Voltage,Value range: 0.0 to 65.0.Unit: V.and the value is accurate to one decimal space (.1)."
|
|
::= { hwPDEEntry 16 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.17
|
|
hwPDEBranch2Voltage OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..650)
|
|
UNITS "V"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE Branch2 Voltage,Value range: 0.0 to 65.0.Unit: V.and the value is accurate to one decimal space (.1)."
|
|
::= { hwPDEEntry 17 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.18
|
|
hwPDEBranch3Voltage OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..650)
|
|
UNITS "V"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE Branch3 Voltage,Value range: 0.0 to 65.0.Unit: V.and the value is accurate to one decimal space (.1)."
|
|
::= { hwPDEEntry 18 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.19
|
|
hwPDEBranch4Voltage OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..650)
|
|
UNITS "V"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE Branch4 Voltage,Value range: 0.0 to 65.0.Unit: V.and the value is accurate to one decimal space (.1)."
|
|
::= { hwPDEEntry 19 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.20
|
|
hwPDEBranch1Temperature OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..300)
|
|
UNITS "deg"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE Branch1 Temperature,Value range: 0 to 300.Unit: deg."
|
|
::= { hwPDEEntry 20 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.21
|
|
hwPDEBranch2Temperature OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..300)
|
|
UNITS "deg"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE Branch2 Temperature,Value range: 0 to 300.Unit: deg."
|
|
::= { hwPDEEntry 21 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.22
|
|
hwPDEBranch3Temperature OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..300)
|
|
UNITS "deg"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE Branch3 Temperature,Value range: 0 to 300.Unit: deg."
|
|
::= { hwPDEEntry 22 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.23
|
|
hwPDEBranch4Temperature OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..300)
|
|
UNITS "deg"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE Branch4 Temperature,Value range: 0 to 300.Unit: deg."
|
|
::= { hwPDEEntry 23 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.24
|
|
hwPDEOperStatus OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
normal(1),
|
|
alarm(2),
|
|
alarmResume(254),
|
|
unknown(255)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of the PDE. It is an enumeration type:
|
|
If the enumeration value is 1, it indicates that the PDE is in the normal state;
|
|
If the enumeration value is 2, it indicates that the PDE is in the alarm state;
|
|
If the enumeration value is 254, it indicates that the PDE is in the resume state;
|
|
If the enumeration value is 255, it indicates PDE operation status unknown. "
|
|
::= { hwPDEEntry 24 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.100
|
|
hwPDERowStatus OBJECT-TYPE
|
|
SYNTAX RowStatus
|
|
MAX-ACCESS read-create
|
|
STATUS current
|
|
DESCRIPTION
|
|
"RowStatus of PDE table."
|
|
::= { hwPDEEntry 100 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.2
|
|
hwPDEConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF HwPDEConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE Config table. Use this table to get PDE equipment ID , PDE equipment name, and current PDE config parameter. This table's index is hwPDEConfigIndex."
|
|
::= { hwPDE 2 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.2.1
|
|
hwPDEConfigEntry OBJECT-TYPE
|
|
SYNTAX HwPDEConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE Config table entry."
|
|
INDEX { hwPDEConfigIndex }
|
|
::= { hwPDEConfigTable 1 }
|
|
|
|
HwPDEConfigEntry ::=
|
|
SEQUENCE {
|
|
hwPDEConfigIndex
|
|
Integer32,
|
|
hwPDEConfigEquipId
|
|
Unsigned32,
|
|
hwPDEConfigEquipName
|
|
OCTET STRING,
|
|
hwPDEOverTempProtect
|
|
Unsigned32,
|
|
hwPDEVolProtectEnable
|
|
INTEGER,
|
|
hwPDEOverVoltageProtect
|
|
Unsigned32,
|
|
hwPDEUnderVoltageProtect
|
|
Unsigned32,
|
|
hwPDEHysteresis
|
|
Unsigned32,
|
|
hwPDEReset
|
|
INTEGER,
|
|
hwPDEBranch1Control
|
|
INTEGER,
|
|
hwPDEBranch2Control
|
|
INTEGER,
|
|
hwPDEBranch3Control
|
|
INTEGER,
|
|
hwPDEBranch4Control
|
|
INTEGER,
|
|
hwPDEBranch1CurrentLimit
|
|
Unsigned32,
|
|
hwPDEBranch2CurrentLimit
|
|
Unsigned32,
|
|
hwPDEBranch3CurrentLimit
|
|
Unsigned32,
|
|
hwPDEBranch4CurrentLimit
|
|
Unsigned32,
|
|
hwPDEConfigRowStatus
|
|
RowStatus
|
|
}
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.1
|
|
hwPDEConfigIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..10)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE Config table index, which value range: 1 to 10. Lines of the device list are restricted by the quantity of PDE. "
|
|
::= { hwPDEConfigEntry 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.2
|
|
hwPDEConfigEquipId OBJECT-TYPE
|
|
SYNTAX Unsigned32 (12001..12255)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE device ID. Value range: 012'001 to 012'255, in which the first digits indicate the device type and the last three digits indicate the device SN. "
|
|
::= { hwPDEConfigEntry 2 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.3
|
|
hwPDEConfigEquipName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (0..64))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE name, of the character string type, is used to specify PDEs. Users can configure it.
|
|
Otherwise, the configured character can not be any other languages except English. "
|
|
::= { hwPDEConfigEntry 3 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.4
|
|
hwPDEOverTempProtect OBJECT-TYPE
|
|
SYNTAX Unsigned32 (100..120)
|
|
UNITS "deg"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE Over Temperature Protect,Value range: 100 to 120.Unit: deg."
|
|
::= { hwPDEConfigEntry 4 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.5
|
|
hwPDEVolProtectEnable OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
enable(1),
|
|
disable(2),
|
|
unknown(255)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE Over Protect Enable,It is an enumeration value, and users actively set it.
|
|
If the enumeration value is 1, it means to enable the PDE voltage protect;
|
|
If the enumeration value is 2, it means to disable the PDE voltage protect. "
|
|
::= { hwPDEConfigEntry 5 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.6
|
|
hwPDEOverVoltageProtect OBJECT-TYPE
|
|
SYNTAX Unsigned32 (58..60)
|
|
UNITS "V"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE Over Voltage Protect,Value range: 58 to 60.Unit: V."
|
|
::= { hwPDEConfigEntry 6 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.7
|
|
hwPDEUnderVoltageProtect OBJECT-TYPE
|
|
SYNTAX Unsigned32 (40..48)
|
|
UNITS "V"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE Under Voltage Protect,Value range: 40 to 48.Unit: V."
|
|
::= { hwPDEConfigEntry 7 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.8
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.8
|
|
hwPDEHysteresis OBJECT-TYPE
|
|
SYNTAX Unsigned32 (1..3)
|
|
UNITS "V"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE Hysteresis,Value range: 1 to 3.Unit: V."
|
|
::= { hwPDEConfigEntry 8 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.9
|
|
hwPDEReset OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
reset(1),
|
|
unknown(255)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE Reset Control,It is an enumeration value, and users actively set it.
|
|
If the enumeration value is 1, it means to reset the PDE; "
|
|
::= { hwPDEConfigEntry 9 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.10
|
|
hwPDEBranch1Control OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
open(1),
|
|
close(2),
|
|
unknown(255)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE Branch1 Control,It is an enumeration value, and users actively set it.
|
|
If the enumeration value is 1, it means to open the branch1;
|
|
If the enumeration value is 2, it means to close the branch1; "
|
|
::= { hwPDEConfigEntry 10 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.11
|
|
hwPDEBranch2Control OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
open(1),
|
|
close(2),
|
|
unknown(255)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE Branch2 Control,It is an enumeration value, and users actively set it.
|
|
If the enumeration value is 1, it means to open the branch2;
|
|
If the enumeration value is 2, it means to close the branch2; "
|
|
::= { hwPDEConfigEntry 11 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.12
|
|
hwPDEBranch3Control OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
open(1),
|
|
close(2),
|
|
unknown(255)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE Branch3 Control,It is an enumeration value, and users actively set it.
|
|
If the enumeration value is 1, it means to open the branch3;
|
|
If the enumeration value is 2, it means to close the branch3; "
|
|
::= { hwPDEConfigEntry 12 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.13
|
|
hwPDEBranch4Control OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
open(1),
|
|
close(2),
|
|
unknown(255)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE Branch4 Control,It is an enumeration value, and users actively set it.
|
|
If the enumeration value is 1, it means to open the branch4;
|
|
If the enumeration value is 2, it means to close the branch4; "
|
|
::= { hwPDEConfigEntry 13 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.14
|
|
hwPDEBranch1CurrentLimit OBJECT-TYPE
|
|
SYNTAX Unsigned32 (1..20)
|
|
UNITS "A"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE Branch1 Current Limit,Value range: 1 to 20.Unit: A."
|
|
::= { hwPDEConfigEntry 14 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.15
|
|
hwPDEBranch2CurrentLimit OBJECT-TYPE
|
|
SYNTAX Unsigned32 (1..30)
|
|
UNITS "A"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE Branch2 Current Limit,Value range: 1 to 30.Unit: A."
|
|
::= { hwPDEConfigEntry 15 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.16
|
|
hwPDEBranch3CurrentLimit OBJECT-TYPE
|
|
SYNTAX Unsigned32 (1..30)
|
|
UNITS "A"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE Branch3 Current Limit,Value range: 1 to 30.Unit: A."
|
|
::= { hwPDEConfigEntry 16 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.17
|
|
hwPDEBranch4CurrentLimit OBJECT-TYPE
|
|
SYNTAX Unsigned32 (1..20)
|
|
UNITS "A"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDE Branch4 Current Limit,Value range: 1 to 20.Unit: A."
|
|
::= { hwPDEConfigEntry 17 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.100
|
|
hwPDEConfigRowStatus OBJECT-TYPE
|
|
SYNTAX RowStatus
|
|
MAX-ACCESS read-create
|
|
STATUS current
|
|
DESCRIPTION
|
|
"RowStatus of PDE config table."
|
|
::= { hwPDEConfigEntry 100 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2
|
|
hwSiteMonitorMIBTraps OBJECT IDENTIFIER ::= { hwSiteMonitorMIB 2 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1
|
|
hwSiteAlarmTraps OBJECT IDENTIFIER ::= { hwSiteMonitorMIBTraps 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.1.7.1
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0
|
|
hwSiteAlarmTrapsPrefix OBJECT IDENTIFIER ::= { hwSiteAlarmTraps 0 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.1.7.1.9
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.1
|
|
hwRectifierFaultAlarmTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber, hwAlarmText, hwAlarmLevel, hwAlarmSigDesc, hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier, hwSiteDescription, hwRectEquipId, hwRectEquipName,hwRectOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When rectifiers fault alarms happen, a alarm trap will be send. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.1.7.1.10
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.2
|
|
hwRectifierFaultAlarmResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber, hwAlarmText, hwAlarmLevel, hwAlarmSigDesc, hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier, hwSiteDescription, hwRectEquipId, hwRectEquipName, hwRectOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Rectifier Fault alarm resolved.Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 2 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.3
|
|
hwRectifierAbnormalAlarmTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber, hwAlarmText, hwAlarmLevel,hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription,hwRectEquipId, hwRectEquipName, hwRectOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Rectifier abnormal alarm, because of communication failure, module protection, or turnoff. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 3 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.4
|
|
hwRectifierAbnormalAlarmResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel, hwAlarmSigDesc,hwSiteName ,hwSiteAdminAddr ,
|
|
hwNetIdentifier,hwSiteDescription,hwRectEquipId, hwRectEquipName, hwRectOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Rectifier abnormal alarm resume. Description.Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 4 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.5
|
|
hwBattLoopBreakAlarmTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwBattStringEquipId, hwBattStringEquipName, hwBattStringOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery loop disconnect. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery string equipment ID and equipment name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 5 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.6
|
|
hwBattLoopBreakAlarmResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwBattStringEquipId,hwBattStringEquipName, hwBattStringOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery loop break alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery string equipment ID and equipment name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 6 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.7
|
|
hwBattLvdAlarmTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription,hwLvdUnitEquipId, hwLvdUnitEquipName,hwLvdBranchOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery disconnect for low voltage. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery LVD unit equipment ID and equipment name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 7 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.8
|
|
hwBattLvdAlarmResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber, hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription,hwLvdUnitEquipId, hwLvdUnitEquipName, hwLvdBranchOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery LVD alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery LVD unit equipment ID and equipment name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 8 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.9
|
|
hwBattOverCurrAlarmTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription,hwBattStringEquipId, hwBattStringEquipName, hwBattStringOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Batterys charge in over current. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery string equipment ID and equipment name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 9 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.10
|
|
hwBattOverCurrAlarmResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel, hwAlarmSigDesc, hwSiteName,hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwBattStringEquipId,hwBattStringEquipName, hwBattStringOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Batterys over current alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery string equipment ID and equipment name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 10 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.11
|
|
hwBattStringTempAlarmTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwBattStringEquipId, hwBattStringEquipName,hwBattStringOperStatus}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery string temperature is too high or too low. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery group ID and group name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 11 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.12
|
|
hwBattStringTempAlarmResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc, hwSiteName,hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwBattStringEquipId, hwBattStringEquipName, hwBattStringOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery string temperature alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery group ID and group name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 12 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.13
|
|
hwBattDischargeAlarmTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription,hwBattsGroupId, hwBattsGroupName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery group discharge alarm. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery group ID and group name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 13 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.14
|
|
hwBattDischargeAlarmResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwBattsGroupId, hwBattsGroupName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery group discharge alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery group ID and group name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 14 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.1.7.1.32
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.15
|
|
hwAcInputAlarmTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel, hwAlarmSigDesc, hwSiteName,hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwAcEquipId, hwAcEquipName, hwAcInputOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"AC absent or AC power off alarms happened. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, AC equipment ID and equipment name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 15 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.1.7.1.31
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.16
|
|
hwAcInputAlarmResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwAcEquipId,hwAcEquipName, hwAcInputOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"AC input alarm resumed. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, AC equipment ID and equipment name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 16 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.17
|
|
hwAcVoltAlarmTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwAcEquipId, hwAcEquipName, hwAcInputOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"AC voltage too high or too low. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, AC equipment ID and equipment name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 17 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.18
|
|
hwAcVoltAlarmResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier, hwSiteDescription,hwAcEquipId, hwAcEquipName, hwAcInputOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"AC voltage alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, AC equipment ID and equipment name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 18 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.19
|
|
hwDcVoltAlarmTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel, hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwDcOutputEquipId, hwDcOutputEquipName, hwDcOutputOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"DC voltage too high or too low. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, DC equipment ID and equipment name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 19 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.20
|
|
hwDcVoltAlarmResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber, hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwDcOutputEquipId, hwDcOutputEquipName, hwDcOutputOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"DC voltage alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, DC equipment ID and equipment name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 20 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.21
|
|
hwLoadLvdAlarmTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel, hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,
|
|
hwNetIdentifier, hwSiteDescription,hwLvdUnitEquipId,hwLvdUnitEquipName,hwLvdBranchOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Loads disconnect for low voltage. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, load LVD unit equipment ID and equipment name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 21 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.22
|
|
hwLoadLvdAlarmResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwLvdUnitEquipId, hwLvdUnitEquipName, hwLvdBranchOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Load LVD alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, load LVD unit equipment ID and equipment name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 22 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.23
|
|
hwLoadFuseAlarmTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel, hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription,hwLoadBranchEquipId, hwLoadBranchEquipName,hwLoadBranchOperStatus}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Load fuse broken down. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery string equipment ID and equipment name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 23 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.24
|
|
hwLoadFuseAlarmResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwLoadBranchEquipId, hwLoadBranchEquipName, hwLoadBranchOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Load fuse alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery string equipment ID and equipment name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 24 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.25
|
|
hwEnvTempAlarmTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwEnvTempEquipId,hwEnvTempEquipName, hwEnvTempSensorOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Environment temperature is too high or too low. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment temperature sensor equipment ID and equipment name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 25 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.26
|
|
hwEnvTempAlarmResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwEnvTempEquipId,hwEnvTempEquipName, hwEnvTempSensorOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Environment temperature alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment temperature sensor equipment ID and equipment name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 26 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.27
|
|
hwEnvHumiAlarmTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber, hwAlarmText, hwAlarmLevel, hwAlarmSigDesc, hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier, hwSiteDescription, hwEnvHumiEquipId, hwEnvHumiEquipName, hwEnvHumiSensorOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Environment humidity is too high or too low. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment humidity sensor equipment ID and equipment name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 27 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.28
|
|
hwEnvHumiAlarmResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber, hwAlarmText, hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwEnvHumiEquipId, hwEnvHumiEquipName, hwEnvHumiSensorOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Environment humidity alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment humidity sensor equipment ID and equipment name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 28 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.29
|
|
hwSpareDigitalAlarmTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel,hwAlarmSigDesc, hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwSpareDigitalEquipId, hwSpareDigitalEquipName, hwSpareDigitalOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Spare digital fault. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, Spare digital equipment ID and equipment name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 29 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.30
|
|
hwSpareDigitalAlarmResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber, hwAlarmText,hwAlarmLevel,hwAlarmSigDesc, hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier, hwSiteDescription,hwSpareDigitalEquipId, hwSpareDigitalEquipName, hwSpareDigitalOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Spare digital alarm resume.Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, Spare digital equipment ID and equipment name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 30 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.31
|
|
hwDoorAlarmTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwEnvUnitsGroupId, hwEnvUnitsGroupName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Door open. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment unit group ID and group name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 31 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.32
|
|
hwDoorAlarmResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber, hwAlarmText,hwAlarmLevel,hwAlarmSigDesc, hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwEnvUnitsGroupId, hwEnvUnitsGroupName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Door alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment unit group ID and group name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 32 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.33
|
|
hwWaterAlarmTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber, hwAlarmText, hwAlarmLevel, hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwEnvUnitsGroupId, hwEnvUnitsGroupName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Water alarm. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment unit group ID and group name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 33 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.34
|
|
hwWaterAlarmResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber, hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwEnvUnitsGroupId, hwEnvUnitsGroupName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Water alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment unit group ID and group name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 34 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.35
|
|
hwSmokeAlarmTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber, hwAlarmText,hwAlarmLevel, hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,
|
|
hwNetIdentifier, hwSiteDescription, hwEnvUnitsGroupId,hwEnvUnitsGroupName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Site is on fire, which is detected by smoke sensors. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment unit group ID and group name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 35 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.36
|
|
hwSmokeAlarmResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber, hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription,hwEnvUnitsGroupId,hwEnvUnitsGroupName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Smoke alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment unit group ID and group name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 36 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.37
|
|
hwWireAlarmTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier, hwSiteDescription, hwEnvUnitsGroupId, hwEnvUnitsGroupName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Wire alarm.Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment unit group ID and group name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 37 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.38
|
|
hwWireAlarmResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwEnvUnitsGroupId, hwEnvUnitsGroupName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Wire alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment unit group ID and group name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 38 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.39
|
|
hwAcBreakerAlarmTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel,hwAlarmSigDesc, hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwAcInputBreakerEquipId, hwAcInputBreakerEquipName, hwAcInputBreakerOperStatus}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"AC breaker alarm.Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, AC distribution unit ID and its name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 39 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.40
|
|
hwAcBreakerAlarmResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel,hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwAcInputBreakerEquipId, hwAcInputBreakerEquipName, hwAcInputBreakerOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"AC breaker alarm resume.Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, AC distribution unit ID and its name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 40 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.41
|
|
hwMultiRectFailureAlarmTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwRectsGroupId, hwRectsGroupName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"More than one rectifier reported fault alarms in the same time. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, rectifier group ID and group name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 41 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.42
|
|
hwMultiRectFailureAlarmResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc, hwSiteName,hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwRectsGroupId, hwRectsGroupName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Multi-rectifiers fault alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, rectifier group ID and group name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 42 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.43
|
|
hwRectRedundAlarmTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription,hwRectsGroupId,hwRectsGroupName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Rectifiers work redundantly, in this case that some of rectifiers will going to sleep. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, rectifier group ID and group name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 43 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.44
|
|
hwRectRedundAlarmResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber, hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwRectsGroupId, hwRectsGroupName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Rectifiers redundant alarm resume, when the power supply and requirement were in balance. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, rectifier group ID and group name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 44 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.45
|
|
hwBattUnbalanceAlarmTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel,hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwBattStringEquipId, hwBattStringEquipName,hwBattStringOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery works in unbalance state. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery string equipment ID and equipment name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 45 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.46
|
|
hwBattUnbalanceAlarmResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber, hwAlarmText,hwAlarmLevel, hwAlarmSigDesc, hwSiteName,hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwBattStringEquipId, hwBattStringEquipName,hwBattStringOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery unbalance alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery string equipment ID and equipment name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 46 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.47
|
|
hwAcFreqFaultAlarmTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwAcEquipId,hwAcEquipName, hwAcInputOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"AC frequency is fault. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, AC equipment ID and equipment name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 47 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.48
|
|
hwAcFreqFaultAlarmResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwAcEquipId, hwAcEquipName,hwAcInputOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"AC frequency alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, AC equipment ID and equipment name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 48 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.49
|
|
hwXmuSelfFaultAlarmTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription,hwMonEquipId,hwMonEquipName,hwMonitorOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"There are some fault in XMU itself. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, monitor equipment ID and equipment name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 49 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.50
|
|
hwXmuSelfFaultAlarmResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber, hwAlarmText,hwAlarmLevel, hwAlarmSigDesc, hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwMonEquipId, hwMonEquipName, hwMonitorOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"XMU fault alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, monitor equipment ID and equipment name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 50 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.51
|
|
hwRs485CommAlarmTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwMonEquipId, hwMonEquipName,hwMonitorOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"RS485 communication of monitors disconnect. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, monitor equipment ID and equipment name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 51 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.52
|
|
hwRs485CommAlarmResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwMonEquipId, hwMonEquipName, hwMonitorOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"RS485 communication alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, monitor equipment ID and equipment name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 52 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.53
|
|
hwNetCommAlarmTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber, hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwMonEquipId, hwMonEquipName,hwMonitorOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Network communication of monitors disconnect. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, monitor equipment ID and equipment name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 53 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.54
|
|
hwNetCommAlarmResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc, hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwMonEquipId, hwMonEquipName, hwMonitorOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Network communication alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, monitor equipment ID and equipment name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 54 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.55
|
|
hwAcOffLongTimeAlarmTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel, hwAlarmSigDesc, hwSiteName,hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwAcEquipId, hwAcEquipName, hwAcInputOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"AC power off for a long time alarms happened. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, AC equipment ID and equipment name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 55 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.56
|
|
hwAcOffLongTimeAlarmResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel, hwAlarmSigDesc, hwSiteName,hwSiteAdminAddr,
|
|
hwNetIdentifier, hwSiteDescription, hwAcEquipId, hwAcEquipName,hwAcInputOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"AC power off for a long time alarms resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, AC equipment ID and equipment name are also include in VB(variable bondings). "
|
|
::= { hwSiteAlarmTrapsPrefix 56 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.57
|
|
hwSpdAlarmTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwEnvUnitsGroupId, hwEnvUnitsGroupName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 57 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.58
|
|
hwSpdAlarmResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwEnvUnitsGroupId, hwEnvUnitsGroupName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 58 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.59
|
|
hwBadBatteryTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwBattsGroupId, hwBattsGroupName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 59 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.60
|
|
hwBadBatteryResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel,hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwBattsGroupId, hwBattsGroupName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 60 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.61
|
|
hwLvd2DisconnectingTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwLvdUnitEquipId, hwLvdUnitEquipName, hwLvdBranchOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 61 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.62
|
|
hwLvd2DisconnectingResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwLvdUnitEquipId, hwLvdUnitEquipName, hwLvdBranchOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 62 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.63
|
|
hwBattHighTempTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel, hwAlarmSigDesc,hwSiteName,hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwBattStringEquipId, hwBattStringEquipName,hwBattStringOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 63 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.64
|
|
hwBattHighTempResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier, hwSiteDescription, hwBattStringEquipId, hwBattStringEquipName,hwBattStringOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 64 }
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.65
|
|
hwBattLowTempTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel, hwAlarmSigDesc, hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwBattStringEquipId,hwBattStringEquipName, hwBattStringOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 65 }
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.66
|
|
hwBattLowTempResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwBattStringEquipId, hwBattStringEquipName, hwBattStringOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 66 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.67
|
|
hwDcUltraOverVoltageTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel,hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwDcOutputEquipId, hwDcOutputEquipName, hwDcOutputOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 67 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.68
|
|
hwDcUltraOverVoltageResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel,hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier, hwSiteDescription, hwDcOutputEquipId, hwDcOutputEquipName, hwDcOutputOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 68 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.69
|
|
hwDcUltraUnderVoltageTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwDcOutputEquipId, hwDcOutputEquipName, hwDcOutputOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 69 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.70
|
|
hwDcUltraUnderVoltageResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText,hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwDcOutputEquipId, hwDcOutputEquipName, hwDcOutputOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 70 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.71
|
|
hwUmiCommFailTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel, hwAlarmSigDesc, hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwEnvUnitsGroupId, hwEnvUnitsGroupName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 71 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.72
|
|
hwUmiCommFailResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier, hwSiteDescription,hwEnvUnitsGroupId, hwEnvUnitsGroupName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 72 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.73
|
|
hwShortTestFailTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwRectsGroupId, hwRectsGroupName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 73 }
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.74
|
|
hwShortTestFailResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwBattsGroupId, hwBattsGroupName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 74 }
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.75
|
|
hwMissingBattTempSensorTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwBattsGroupId, hwBattsGroupName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 75 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.76
|
|
hwMissingBattTempSensorResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel, hwAlarmSigDesc, hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwBattsGroupId, hwBattsGroupName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 76 }
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.77
|
|
hwBattTempSensorFaultTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwBattsGroupId, hwBattsGroupName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 77 }
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.78
|
|
hwBattTempSensorFaultResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber, hwAlarmText, hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription,hwBattsGroupId, hwBattsGroupName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 78 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.79
|
|
hwAcOverVoltageTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwAcEquipId, hwAcEquipName, hwAcInputOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 79 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.80
|
|
hwAcOverVoltageResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS {hwAlarmTrapOrdinalNumber, hwAlarmText, hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier, hwSiteDescription, hwAcEquipId, hwAcEquipName, hwAcInputOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 80 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.81
|
|
hwAcUnderVoltageTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwAcEquipId, hwAcEquipName, hwAcInputOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 81 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.82
|
|
hwAcUnderVoltageResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription,hwAcEquipId, hwAcEquipName, hwAcInputOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 82 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.83
|
|
hwPDELoadFaultTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwPDEGroupId, hwPDEGroupName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 83 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.84
|
|
hwPDELoadFaultResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel, hwAlarmSigDesc, hwSiteName,hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwPDEGroupId, hwPDEGroupName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 84 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.85
|
|
hwPDENoResponseTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwPDEEquipId, hwPDEEquipName, hwPDEOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 85 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.86
|
|
hwPDENoResponseResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwPDEEquipId, hwPDEEquipName, hwPDEOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 86 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.87
|
|
hwPDEFailureTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription,hwPDEEquipId, hwPDEEquipName, hwPDEOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 87 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.88
|
|
hwPDEFailureResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwPDEEquipId, hwPDEEquipName, hwPDEOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 88 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.89
|
|
hwPDEBr1FailureTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwPDEEquipId, hwPDEEquipName, hwPDEOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 89 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.90
|
|
hwPDEBr1FailureResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwPDEEquipId, hwPDEEquipName, hwPDEOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 90 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.91
|
|
hwPDEBr2FailureTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwPDEEquipId, hwPDEEquipName, hwPDEOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 91 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.92
|
|
hwPDEBr2FailureResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwPDEEquipId, hwPDEEquipName, hwPDEOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 92 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.93
|
|
hwPDEBr3FailureTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier, hwSiteDescription, hwPDEEquipId, hwPDEEquipName, hwPDEOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 93 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.94
|
|
hwPDEBr3FailureResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier, hwSiteDescription, hwPDEEquipId, hwPDEEquipName, hwPDEOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 94 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.95
|
|
hwPDEBr4FailureTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwPDEEquipId, hwPDEEquipName, hwPDEOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 95 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.96
|
|
hwPDEBr4FailureResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier, hwSiteDescription, hwPDEEquipId, hwPDEEquipName, hwPDEOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 96 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.97
|
|
hwPDEBr1ProtectTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier, hwSiteDescription, hwPDEEquipId, hwPDEEquipName, hwPDEOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 97 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.98
|
|
hwPDEBr1ProtectResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber, hwAlarmText, hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwPDEEquipId, hwPDEEquipName, hwPDEOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 98 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.99
|
|
hwPDEBr2ProtectTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwPDEEquipId, hwPDEEquipName, hwPDEOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 99 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.100
|
|
hwPDEBr2ProtectResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwPDEEquipId, hwPDEEquipName, hwPDEOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 100 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.101
|
|
hwPDEBr3ProtectTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwPDEEquipId, hwPDEEquipName, hwPDEOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 101 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.102
|
|
hwPDEBr3ProtectResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber, hwAlarmText, hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwPDEEquipId, hwPDEEquipName, hwPDEOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 102 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.103
|
|
hwPDEBr4ProtectTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwPDEEquipId, hwPDEEquipName, hwPDEOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 103 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.104
|
|
hwPDEBr4ProtectResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS {hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel, hwAlarmSigDesc, hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription,hwPDEEquipId, hwPDEEquipName,hwPDEOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 104 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.105
|
|
hwPDELostTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwPDEGroupId, hwPDEGroupName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 105 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.1.0.106
|
|
hwPDELostResumeTraps NOTIFICATION-TYPE
|
|
OBJECTS { hwAlarmTrapOrdinalNumber,hwAlarmText, hwAlarmLevel, hwAlarmSigDesc,hwSiteName, hwSiteAdminAddr,
|
|
hwNetIdentifier,hwSiteDescription, hwPDEGroupId, hwPDEGroupName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteAlarmTrapsPrefix 106 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.2
|
|
hwSiteDevicesTraps OBJECT IDENTIFIER ::= { hwSiteMonitorMIBTraps 2 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.2.0
|
|
hwDevicesTrapsPrefix OBJECT IDENTIFIER ::= { hwSiteDevicesTraps 0 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.2.0.1
|
|
hwRectifiersInslotChange NOTIFICATION-TYPE
|
|
OBJECTS { hwDeviceTrapOrdinalNumber, hwSiteName, hwSiteAdminAddr, hwNetIdentifier, hwSiteDescription,
|
|
hwRectEquipId, hwRectEquipName, hwRectOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When the presence status of a rectifier changes, the node reports an event. Then the NMS adds or deletes the corresponding entry to or from hwRectConfigTable or hwRectOperTable. The bound information includes the site address, site name, site description, and NE identifier. In addition, the ID, name, and status of the rectifier are bound to identify the specific rectifier and its operation type. When an entry is added, the device status is reported as normal (1); when an entry is deleted, the device status is reported as commFail (4).
|
|
This trap is the unique trigger condition that causes the NMS to add or delete entries to or from hwRectConfigTable or hwRectOperTable."
|
|
::= { hwDevicesTrapsPrefix 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.2.0.2
|
|
hwBatterysInslotChange NOTIFICATION-TYPE
|
|
OBJECTS { hwDeviceTrapOrdinalNumber, hwSiteName, hwSiteAdminAddr, hwNetIdentifier, hwSiteDescription,
|
|
hwBattStringEquipId, hwBattStringEquipName, hwBattStringOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When the presence status of a battery string changes, the node reports an event. Then the NMS adds or deletes the corresponding entry to or from hwBatttConfigTable or hwBatttOperTable. The bound information includes the site address, site name, site description, and NE identifier. In addition, the ID, name, and status of the battery string are bound to identify the specific battery string and its operation type. When an entry is added, the device status is reported as normal (1); when an entry is deleted, the device status is reported as loopBreak (4).
|
|
This trap is the unique trigger condition that causes the NMS to add or delete entries to or from hwBatttConfigTable or hwBatttOperTable."
|
|
::= { hwDevicesTrapsPrefix 2 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.2.0.3
|
|
hwBattTestRecordsAdd NOTIFICATION-TYPE
|
|
OBJECTS { hwDeviceTrapOrdinalNumber, hwSiteName, hwSiteDescription, hwNetIdentifier, hwSiteAdminAddr }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"After a new discharge test is conducted on a battery group, the node reports an event. The bound information includes the site address, site name, site description, and NE identifier. The NMS needs to add the corresponding entry to the battery test table. The test records are sorted by time in descending order. The battery test table holds a maximum of 10 test records. If the number of test records exceeds 10, the earlier records starting from the last but one record are deleted at a time because the last record is saved permanently.
|
|
This trap is the unique trigger condition that causes the NMS to add entries from hwBattsTestResultTable.
|
|
The battery test table allows you only to add entries."
|
|
::= { hwDevicesTrapsPrefix 3 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.2.0.4
|
|
hwEnvTempSensInslotChange NOTIFICATION-TYPE
|
|
OBJECTS { hwDeviceTrapOrdinalNumber, hwSiteName,hwSiteAdminAddr, hwNetIdentifier,hwSiteDescription,
|
|
hwEnvTempEquipId, hwEnvTempEquipName, hwEnvTempSensorOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When the presence status of an environment temperature sensor changes, the node reports an event. Then the NMS adds or deletes the corresponding entry to or from hwEvnTempSensorTable. The bound information includes the site address, site name, site description, and NE identifier. In addition, the ID, name, and status of the environment temperature sensor are bound to identify the specific environment temperature sensor and its operation type. When an entry is added, the device status is reported as normal (1); when an entry is deleted, the device status is reported as notInslot (4).
|
|
This trap is the unique trigger condition that causes the NMS to add or delete entries to or from hwEnvTempSensorTable."
|
|
::= { hwDevicesTrapsPrefix 4 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.2.0.5
|
|
hwEnvHumiSensInslotChange NOTIFICATION-TYPE
|
|
OBJECTS { hwDeviceTrapOrdinalNumber, hwSiteName, hwSiteAdminAddr, hwNetIdentifier,hwSiteDescription,
|
|
hwEnvHumiEquipId, hwEnvHumiEquipName, hwEnvHumiSensorOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When the presence status of an environment humidity sensor changes, the trap reports an event. Then the NMS adds or deletes the corresponding entry to or from hwEvnHumiSensorTable. The bound information includes the site address, site name, site description, and NE identifier. In addition, the ID, name, and status of the environment humidity sensor are bound to identify the specific environment humidity sensor and its operation type. When an entry is added, the device status is reported as normal (1); when an entry is deleted, the device status is reported as notInslot (4).
|
|
This trap is the unique trigger condition that causes the NMS to add or delete entries to or from hwEnvHumiSensorTable."
|
|
::= { hwDevicesTrapsPrefix 5 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.2.0.6
|
|
hwPDEsInslotChange NOTIFICATION-TYPE
|
|
OBJECTS { hwDeviceTrapOrdinalNumber,hwSiteName, hwSiteAdminAddr, hwNetIdentifier,hwSiteDescription,
|
|
hwPDEEquipId, hwPDEEquipName, hwPDEOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwDevicesTrapsPrefix 6 }
|
|
|
|
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.3
|
|
hwV101SiteDevicesTraps OBJECT IDENTIFIER ::= { hwSiteMonitorMIBTraps 3 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.3.0
|
|
hwV101DevicesTrapsPrefix OBJECT IDENTIFIER ::= { hwV101SiteDevicesTraps 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.3.0.1
|
|
hwRectifiersInslotChange NOTIFICATION-TYPE
|
|
OBJECTS { hwDeviceTrapOrdinalNumber, hwSiteName, hwSiteAdminAddr, hwNetIdentifier, hwSiteDescription,
|
|
hwRectEquipId, hwRectEquipName, hwRectOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When the presence status of a rectifier changes, the node reports an event. Then the NMS adds or deletes the corresponding entry to or from hwRectConfigTable or hwRectOperTable. The bound information includes the site address, site name, site description, and NE identifier. In addition, the ID, name, and status of the rectifier are bound to identify the specific rectifier and its operation type. When an entry is added, the device status is reported as normal (1); when an entry is deleted, the device status is reported as commFail (4).
|
|
This trap is the unique trigger condition that causes the NMS to add or delete entries to or from hwRectConfigTable or hwRectOperTable."
|
|
::= { hwV101DevicesTrapsPrefix 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.3.0.2
|
|
hwBatterysInslotChange NOTIFICATION-TYPE
|
|
OBJECTS { hwDeviceTrapOrdinalNumber, hwSiteName, hwSiteAdminAddr, hwNetIdentifier, hwSiteDescription,
|
|
hwBattStringEquipId, hwBattStringEquipName, hwBattStringOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When the presence status of a battery string changes, the node reports an event. Then the NMS adds or deletes the corresponding entry to or from hwBatttConfigTable or hwBatttOperTable. The bound information includes the site address, site name, site description, and NE identifier. In addition, the ID, name, and status of the battery string are bound to identify the specific battery string and its operation type. When an entry is added, the device status is reported as normal (1); when an entry is deleted, the device status is reported as loopBreak (4).
|
|
This trap is the unique trigger condition that causes the NMS to add or delete entries to or from hwBatttConfigTable or hwBatttOperTable."
|
|
::= { hwV101DevicesTrapsPrefix 2 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.3.0.3
|
|
hwBattTestRecordsAdd NOTIFICATION-TYPE
|
|
OBJECTS { hwDeviceTrapOrdinalNumber, hwSiteName, hwSiteDescription, hwNetIdentifier, hwSiteAdminAddr }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"After a new discharge test is conducted on a battery group, the node reports an event. The bound information includes the site address, site name, site description, and NE identifier. The NMS needs to add the corresponding entry to the battery test table. The test records are sorted by time in descending order. The battery test table holds a maximum of 10 test records. If the number of test records exceeds 10, the earlier records starting from the last but one record are deleted at a time because the last record is saved permanently.
|
|
This trap is the unique trigger condition that causes the NMS to add entries from hwBattsTestResultTable.
|
|
The battery test table allows you only to add entries."
|
|
::= { hwV101DevicesTrapsPrefix 3 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.3.0.4
|
|
hwEnvTempSensInslotChange NOTIFICATION-TYPE
|
|
OBJECTS { hwDeviceTrapOrdinalNumber, hwSiteName,hwSiteAdminAddr, hwNetIdentifier,hwSiteDescription,
|
|
hwEnvTempEquipId, hwEnvTempEquipName, hwEnvTempSensorOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When the presence status of an environment temperature sensor changes, the node reports an event. Then the NMS adds or deletes the corresponding entry to or from hwEvnTempSensorTable. The bound information includes the site address, site name, site description, and NE identifier. In addition, the ID, name, and status of the environment temperature sensor are bound to identify the specific environment temperature sensor and its operation type. When an entry is added, the device status is reported as normal (1); when an entry is deleted, the device status is reported as notInslot (4).
|
|
This trap is the unique trigger condition that causes the NMS to add or delete entries to or from hwEnvTempSensorTable."
|
|
::= { hwV101DevicesTrapsPrefix 4 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.3.0.5
|
|
hwEnvHumiSensInslotChange NOTIFICATION-TYPE
|
|
OBJECTS { hwDeviceTrapOrdinalNumber, hwSiteName, hwSiteAdminAddr, hwNetIdentifier,hwSiteDescription,
|
|
hwEnvHumiEquipId, hwEnvHumiEquipName, hwEnvHumiSensorOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When the presence status of an environment humidity sensor changes, the trap reports an event. Then the NMS adds or deletes the corresponding entry to or from hwEvnHumiSensorTable. The bound information includes the site address, site name, site description, and NE identifier. In addition, the ID, name, and status of the environment humidity sensor are bound to identify the specific environment humidity sensor and its operation type. When an entry is added, the device status is reported as normal (1); when an entry is deleted, the device status is reported as notInslot (4).
|
|
This trap is the unique trigger condition that causes the NMS to add or delete entries to or from hwEnvHumiSensorTable."
|
|
::= { hwV101DevicesTrapsPrefix 5 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.2.3.0.6
|
|
hwPDEsInslotChange NOTIFICATION-TYPE
|
|
OBJECTS { hwDeviceTrapOrdinalNumber,hwSiteName, hwSiteAdminAddr, hwNetIdentifier,hwSiteDescription,
|
|
hwPDEEquipId, hwPDEEquipName, hwPDEOperStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwV101DevicesTrapsPrefix 6 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.3
|
|
hwSiteMonitorMIBConformance OBJECT IDENTIFIER ::= { hwSiteMonitorMIB 3 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.3.1
|
|
hwSiteMonitorGroups OBJECT IDENTIFIER ::= { hwSiteMonitorMIBConformance 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.1.6
|
|
-- 1.3.6.1.4.1.2011.6.164.3.1.1
|
|
hwSiteInfoGroup OBJECT-GROUP
|
|
OBJECTS { hwSiteName, hwSiteDescription, hwSiteId, hwSiteIp, hwSiteNetmask,
|
|
hwAlarmIndex, hwAlarmLevel, hwAlarmSigDesc, hwAlarmQuantity, hwAlarmRowStatus,
|
|
hwSiteGateway, hwNetIdentifier, hwAlarmText, hwDeviceTrapOrdinalNumber, hwAlarmTrapOrdinalNumber,
|
|
hwSiteAdminAddr }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Site information group."
|
|
::= { hwSiteMonitorGroups 1 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.3.1.2
|
|
hwSiteMonitorsGroup OBJECT-GROUP
|
|
OBJECTS { hwMonsGroupId, hwMonsGroupName, hwMonIndex, hwMonEquipId, hwMonEquipName,
|
|
hwMonEquipPcbVersion, hwMonEquipManufacturer, hwMonEquipManuDate, hwMonEquipSerialNo, hwMonEquipDescription,
|
|
hwCtrlMonEquipReset, hwMonRowStatus, hwMonitorOperStatus, hwMonsQuantity, hwMonEquipOperTotalTime,
|
|
hwMonEquipSoftwareVersion, hwSetMonEquipCtrlState }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Site monitor group."
|
|
::= { hwSiteMonitorGroups 2 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.3.1.3
|
|
hwSiteRectifiersGroup OBJECT-GROUP
|
|
OBJECTS { hwRectSerialNo, hwRectType, hwRectManufacturer, hwRectOutputCurrent, hwRectOutputVoltage,
|
|
hwCtrlRectOnOff, hwRectEquipId, hwRectEquipName, hwRectRatedCurrent, hwRectInputAcType,
|
|
hwRectEfficency, hwRectConfigIndex, hwRectConfigRowStatus, hwRectsGroupId, hwRectsGroupName,
|
|
hwRectsTotalQuantity, hwRectsRatedVoltage, hwModifyRectsOutputVoltage, hwSetRectsRedundEnable, hwRectManuDate,
|
|
hwCtrlRectsAllOnOff, hwRectsTotalCurrent, hwRectOperStatus, hwRectOperIndex, hwRectTotalOperTime,
|
|
hwRectSoftwareVersion, hwRectOperRowStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Site rectifier group."
|
|
::= { hwSiteMonitorGroups 3 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.3.1.4
|
|
hwSiteBatterysGroup OBJECT-GROUP
|
|
OBJECTS { hwBattStringCurrent, hwBattStringRemainCapacity, hwSetBattInstallTime, hwBattStringEquipId, hwBattStringEquipName,
|
|
hwBattStringRemainCapacityPercent, hwBattStringActualCapacity, hwSetBattStdCapacity, hwBattStringTemprature, hwBattsGroupId,
|
|
hwBattsGroupName, hwSetBattsHighTempAction, hwSetBattsHighTempVoltLimit, hwSetBattsFloatVoltage, hwSetBattsBoostVoltage,
|
|
hwSetBattsCompFactor, hwBattsChargeStatus, hwBattsCurrLimitStatus, hwCtrlBattsTestStartStop, hwBattsTestResultIndex,
|
|
hwBattsTestType, hwBattsTestStartTime, hwBattsTestResult, hwBattsEfficiency, hwBattsDischargeTime,
|
|
hwBattsDischargeEndVoltage, hwBattsDischargeAvCurrent, hwBattsDischargeAhValue, hwBattsTestTemprature, hwBattsTestEndCourse,
|
|
hwBattsTestResultRowStatus, hwBattStringConfigIndex, hwBattStringConfigRowStatus, hwSetBattsTempUpperLimit, hwSetBattsTempLowerLimit,
|
|
hwSetBattsCurrLimitCoefficient, hwBattsTotalCurrent, hwSetBattsHTDLimit, hwBattsTestRecordCount, hwBattStringOperStatus,
|
|
hwSetBattsTempMeasureUpperLimit, hwSetBattsTempMeasureLowerLimit, hwBattsPreDischargeTime, hwBattsTotalQuantity, hwSetBattsManuStdTestTime,
|
|
hwSetBattsManuStdTestEndVolt, hwSetBattsManuStdTestCellNum, hwSetBattsManuShortTestTime, hwSetBattsManuShortTestEndVolt, hwBattStringOperIndex,
|
|
hwSetBattsHTDEnable, hwBattStringOperRowStatus, hwCtrlBattsBoostFloat }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Site battery group."
|
|
::= { hwSiteMonitorGroups 4 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.3.1.5
|
|
hwSiteAcDistributionsGroup OBJECT-GROUP
|
|
OBJECTS { hwSetAcsUpperVoltLimit, hwSetAcsLowerVoltLimit, hwApOrAblVoltage, hwBpOrBclVoltage, hwCpOrCalVoltage,
|
|
hwAphaseCurrent, hwBphaseCurrent, hwCphaseCurrent, hwAcsGroupId, hwAcsGroupName,
|
|
hwAcInputIndex, hwAcRowStatus, hwAcEquipId, hwAcInputOperStatus, hwAcEquipName,
|
|
hwAcsTotalCurrent, hwAcsTotalQuantity, hwSiteDescription, hwAcInputBreakerIndex, hwAcInputBreakerEquipId,
|
|
hwAcInputBreakerEquipName, hwAcInputBreakerOperStatus, hwAcInputBreakerRowStatus, hwAcInputBreakersQuantity }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Site AC distribution group."
|
|
::= { hwSiteMonitorGroups 5 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.3.1.6
|
|
hwSiteDcDistributionsGroup OBJECT-GROUP
|
|
OBJECTS { hwSetDcsUpperVoltLimit, hwSetDcsLowerVoltLimit, hwDcOutputIndex, hwDcOutputVoltage, hwDcOutputCurrent,
|
|
hwDcOutputPower, hwDcOutputRowStatus, hwLoadBranchIndex, hwLoadBranchPower, hwDcOutputEquipId,
|
|
hwDcOutputEquipName, hwLoadBranchEquipId, hwDcOutputOperStatus, hwLoadBranchOperStatus, hwLoadBranchRowStatus,
|
|
hwLvdUnitEquipName, hwLoadBranchEquipName, hwDcsGroupId, hwDcsGroupName, hwDcsTotalVoltage,
|
|
hwDcsTotalCurrent, hwDcsTotalPower, hwDcsTotalQuantity, hwLoadsQuantity, hwLoadBranchCurrent
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Site DC distribution group."
|
|
::= { hwSiteMonitorGroups 6 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.3.1.7
|
|
hwSiteLvdUnitsGroup OBJECT-GROUP
|
|
OBJECTS { hwLvdBranchIndex, hwLvdBranchRowStatus, hwLvdUnitEquipId, hwLvdsGroupId, hwLvdUnitEquipName,
|
|
hwLvdsGroupName, hwSetLvdVoltage, hwCtrlLvd, hwLvdsTotalQuantity, hwLvdBranchOperStatus,
|
|
hwSetLvdEnable }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Site low voltage disconnection unit group."
|
|
::= { hwSiteMonitorGroups 7 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.3.1.8
|
|
hwSiteEnvUnitsGroup OBJECT-GROUP
|
|
OBJECTS { hwCtrlSmokeReset, hwCtrlDoorReset, hwEnvTempSensorIndex, hwEnvTemperature, hwEnvHumiSensorIndex,
|
|
hwEnvHumidity, hwEnvHumiEquipId, hwEnvHumiEquipName, hwEnvTempEquipId, hwEnvTempEquipName,
|
|
hwEnvUnitsGroupId, hwEnvUnitsGroupName, hwSetEnvTempAlarmEnable, hwSetEnvHumiAlarmEnable, hwCtrlBuzzerEnable,
|
|
hwSetEnvTempUpperLimit, hwSetEnvTempLowerLimit, hwEnvTempSensorRowStatus, hwSetEnvHumidityUpperLimit, hwSetEnvHumidityLowerLimit,
|
|
hwEnvHumiSensorRowStatus, hwEnvTempSensorOperStatus, hwEnvHumiSensorOperStatus, hwSetEnvTempMeasureUpperLimit, hwSetEnvTempMeasureLowerLimit,
|
|
hwSetEnvHumidityMeasureUpperLimit, hwSetEnvHumidityMeasureLowerLimit, hwEnvTempSensorsTotalQuantity, hwEnvHumiSensorsTotalQuantity, hwSpareDigitalIndex,
|
|
hwSpareDigitalEquipId, hwSpareDigitalEquipName, hwSetSpareDigitalAlarmTension, hwSetSpareDigitalAlarmEnable, hwSpareDigitalOperStatus,
|
|
hwSpareDigitalRowStatus, hwSpareDigitalsTotalQuantity }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Site envirenment unit group."
|
|
::= { hwSiteMonitorGroups 8 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.1.7.3
|
|
-- 1.3.6.1.4.1.2011.6.164.3.1.9
|
|
hwSiteAlarmTrapsGroup NOTIFICATION-GROUP
|
|
NOTIFICATIONS { hwAcInputAlarmTraps, hwAcInputAlarmResumeTraps, hwAcVoltAlarmTraps, hwAcVoltAlarmResumeTraps, hwDcVoltAlarmTraps,
|
|
hwDcVoltAlarmResumeTraps, hwLoadLvdAlarmTraps, hwLoadLvdAlarmResumeTraps, hwBattLvdAlarmTraps, hwBattLvdAlarmResumeTraps,
|
|
hwBattLoopBreakAlarmTraps, hwBattLoopBreakAlarmResumeTraps, hwEnvTempAlarmTraps, hwEnvTempAlarmResumeTraps, hwEnvHumiAlarmTraps,
|
|
hwEnvHumiAlarmResumeTraps, hwDoorAlarmTraps, hwDoorAlarmResumeTraps, hwWaterAlarmTraps, hwWaterAlarmResumeTraps,
|
|
hwSmokeAlarmTraps, hwSmokeAlarmResumeTraps, hwRectifierFaultAlarmTraps, hwRectifierFaultAlarmResumeTraps, hwRectifierAbnormalAlarmTraps,
|
|
hwRectifierAbnormalAlarmResumeTraps, hwBattOverCurrAlarmTraps, hwBattOverCurrAlarmResumeTraps, hwLoadFuseAlarmTraps, hwLoadFuseAlarmResumeTraps,
|
|
hwRs485CommAlarmTraps, hwRs485CommAlarmResumeTraps, hwNetCommAlarmTraps, hwNetCommAlarmResumeTraps, hwMultiRectFailureAlarmTraps,
|
|
hwMultiRectFailureAlarmResumeTraps, hwRectRedundAlarmTraps, hwRectRedundAlarmResumeTraps, hwBattUnbalanceAlarmTraps, hwBattUnbalanceAlarmResumeTraps,
|
|
hwAcFreqFaultAlarmTraps, hwWireAlarmTraps, hwWireAlarmResumeTraps, hwAcFreqFaultAlarmResumeTraps, hwXmuSelfFaultAlarmTraps,
|
|
hwAcBreakerAlarmTraps, hwAcBreakerAlarmResumeTraps, hwBattDischargeAlarmTraps, hwBattDischargeAlarmResumeTraps, hwXmuSelfFaultAlarmResumeTraps,
|
|
hwBattStringTempAlarmTraps, hwBattStringTempAlarmResumeTraps, hwSpareDigitalAlarmTraps, hwSpareDigitalAlarmResumeTraps, hwAcOffLongTimeAlarmTraps,
|
|
hwAcOffLongTimeAlarmResumeTraps, hwSpdAlarmTraps, hwSpdAlarmResumeTraps, hwBadBatteryTraps, hwBadBatteryResumeTraps,
|
|
hwLvd2DisconnectingTraps, hwLvd2DisconnectingResumeTraps, hwBattHighTempTraps, hwBattHighTempResumeTraps, hwBattLowTempTraps,
|
|
hwBattLowTempResumeTraps, hwDcUltraOverVoltageTraps, hwDcUltraOverVoltageResumeTraps, hwDcUltraUnderVoltageTraps, hwDcUltraUnderVoltageResumeTraps,
|
|
hwUmiCommFailTraps, hwUmiCommFailResumeTraps, hwShortTestFailTraps, hwShortTestFailResumeTraps, hwMissingBattTempSensorTraps,
|
|
hwMissingBattTempSensorResumeTraps, hwBattTempSensorFaultTraps, hwBattTempSensorFaultResumeTraps, hwAcOverVoltageTraps, hwAcOverVoltageResumeTraps,
|
|
hwAcUnderVoltageTraps, hwAcUnderVoltageResumeTraps, hwBattTestRecordsAdd, hwPDENoResponseTraps, hwPDENoResponseResumeTraps,
|
|
hwPDELostTraps, hwPDELostResumeTraps, hwPDELoadFaultTraps, hwPDELoadFaultResumeTraps, hwPDEFailureTraps,
|
|
hwPDEFailureResumeTraps, hwPDEBr1FailureTraps, hwPDEBr1FailureResumeTraps, hwPDEBr2FailureTraps, hwPDEBr2FailureResumeTraps,
|
|
hwPDEBr3FailureTraps, hwPDEBr3FailureResumeTraps, hwPDEBr4FailureTraps, hwPDEBr4FailureResumeTraps, hwPDEBr1ProtectTraps,
|
|
hwPDEBr1ProtectResumeTraps, hwPDEBr2ProtectTraps, hwPDEBr2ProtectResumeTraps, hwPDEBr3ProtectTraps, hwPDEBr3ProtectResumeTraps,
|
|
hwPDEBr4ProtectTraps, hwPDEBr4ProtectResumeTraps }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Site alarm trap group."
|
|
::= { hwSiteMonitorGroups 9 }
|
|
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.3.1.10
|
|
hwSiteDeviceTrapsGroup NOTIFICATION-GROUP
|
|
NOTIFICATIONS { hwRectifiersInslotChange, hwBatterysInslotChange, hwBattTestRecordsAdd, hwEnvTempSensInslotChange, hwEnvHumiSensInslotChange,
|
|
hwPDEsInslotChange }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteMonitorGroups 10 }
|
|
|
|
-- 1.3.6.1.4.1.2011.6.164.3.1.11
|
|
hwSiteEfusesGroup OBJECT-GROUP
|
|
OBJECTS { hwPDEGroupId, hwPDEGroupName, hwPDEGroupNum, hwPDEGroupCommNum, hwPDEGroupTotalPower,
|
|
hwPDEGroupTotalCurrent, hwPDEGroupCommStatus, hwPDEIndex, hwPDEEquipId, hwPDEEquipName,
|
|
hwPDETotalRunningTime, hwPDEBranchNum, hwPDETotalPower, hwPDETotalCurrent, hwPDEBranch1Power,
|
|
hwPDEBranch2Power, hwPDEBranch3Power, hwPDEBranch4Power, hwPDEBranch1Current, hwPDEBranch2Current,
|
|
hwPDEBranch3Current, hwPDEBranch4Current, hwPDEBranch1Voltage, hwPDEBranch2Voltage, hwPDEBranch3Voltage,
|
|
hwPDEBranch4Voltage, hwPDEBranch1Temperature, hwPDEBranch2Temperature, hwPDEBranch3Temperature, hwPDEBranch4Temperature,
|
|
hwPDEOperStatus, hwPDERowStatus, hwPDEConfigIndex, hwPDEConfigEquipId, hwPDEConfigEquipName,
|
|
hwPDEOverTempProtect, hwPDEVolProtectEnable, hwPDEOverVoltageProtect, hwPDEUnderVoltageProtect, hwPDEHysteresis,
|
|
hwPDEReset, hwPDEBranch1Control, hwPDEBranch2Control, hwPDEBranch3Control, hwPDEBranch4Control,
|
|
hwPDEBranch1CurrentLimit, hwPDEBranch2CurrentLimit, hwPDEBranch3CurrentLimit, hwPDEBranch4CurrentLimit, hwPDEConfigRowStatus
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description."
|
|
::= { hwSiteMonitorGroups 11 }
|
|
|
|
|
|
END
|
|
|
|
--
|
|
-- HUAWEI-SITE-MONITOR-MIB.mib
|
|
--
|