mibs/MIBS/ingrasys/IPOMANII-MIB
2023-12-05 12:25:34 +01:00

4571 lines
134 KiB
Plaintext

-- Ingrasys iPoManII MIB
-- MIB for Intelligent Power Management
--
-- { iso org(3) dod(6) internet(1) private(4) enterprises(1) ingrasys(2468)
-- product(1) pduAgent(4) iPoManII(1)
-- ==============================================================================================
---
--- Revision History
---
--- v0.80 20-Apr-2005 Ming Lu/Ingrasys
--- Created
---
--- v0.81 04-Aug-2007 Ming Lu/Ingrasys
--- Modify Some error from Web check issue
--- Add Slave mib data and control
---
--- v0.82 04-Oct-2007 Ming Lu/Ingrasys
--- Modify Some error from Web check issue
---
--- v1.00 06-Dec-2007 Ming Lu/Ingrasys
--- Add Slave trap 26-150
---
--- v1.01 25-Jan-2008 Ming Lu/Ingrasys
--- Modify Some mib wording error
---
--- v1.02 30-Jan-2008 Ming Lu/Ingrasys
--- Modify Some mib wording error
---
--- v1.03 09-Apr-2010 Ming Lu/Ingrasys
--- Add reset WattItem
---
IPOMANII-MIB DEFINITIONS ::= BEGIN
IMPORTS
enterprises
FROM RFC1155-SMI
OBJECT-TYPE
FROM RFC-1212
DisplayString
FROM RFC1213-MIB
TRAP-TYPE
FROM RFC-1215;
ingrasys OBJECT IDENTIFIER ::= { enterprises 2468 }
product OBJECT IDENTIFIER ::= { ingrasys 1 }
pduAgent OBJECT IDENTIFIER ::= { product 4 }
iPoManII OBJECT IDENTIFIER ::= { pduAgent 2 }
ipmObjects OBJECT IDENTIFIER ::= { iPoManII 1 }
ipmTraps OBJECT IDENTIFIER ::= { iPoManII 2 }
ipmIdent OBJECT IDENTIFIER ::= { ipmObjects 1 }
ipmAgent OBJECT IDENTIFIER ::= { ipmObjects 2 }
ipmDevice OBJECT IDENTIFIER ::= { ipmObjects 3 }
ipmSlave OBJECT IDENTIFIER ::= { ipmObjects 4 }
ipmEnv OBJECT IDENTIFIER ::= { ipmObjects 5 }
-- ===========================================================================
--
-- ipmIdent
--
-- iPoManII Identification Group
--
-- ===========================================================================
ipmIdentManufacturer OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The name of manufacturer."
::= { ipmIdent 1 }
ipmIdentModel OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Model designation of device."
::= { ipmIdent 2 }
ipmIdentAgentSoftwareVersion OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The firmware version of the device."
::= { ipmIdent 3 }
ipmIdentName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A description of this device."
::= { ipmIdent 4 }
ipmAgentConfig OBJECT IDENTIFIER ::= { ipmAgent 1 }
-- ===========================================================================
--
-- ipmConfig
--
-- iPoManII Configuration Group, configure the secific features of iPoManII
--
-- ===========================================================================
ipmAgentMibVersion OBJECT-TYPE
SYNTAX INTEGER (1..65500) --
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Mib Version implemented on this device."
::= { ipmAgentConfig 1 }
ipmAgentTime OBJECT IDENTIFIER ::= { ipmAgent 2 }
-- ===========================================================================
--
-- ipmConfigTime
--
-- Date/Time Configuration Group of the device.
--
-- ===========================================================================
ipmAgentTimeDate OBJECT-TYPE
SYNTAX DisplayString (SIZE (10..10))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The date in agent, format is (dd/mm/yyyy)"
::= { ipmAgentTime 1 }
ipmAgentTimeTime OBJECT-TYPE
SYNTAX DisplayString (SIZE (8..8))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The time in agent, format is (hh:mm:ss)"
::= { ipmAgentTime 2 }
ipmAgentTimerFromNtp OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable or disable the agent to synchronize date/time with NTP server."
::= { ipmAgentTime 3 }
ipmAgentNtpIpAddress OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The ip address of NTP server."
::= { ipmAgentTime 4 }
ipmAgentNtpTimeZone OBJECT-TYPE
SYNTAX INTEGER {
gMT-1200(1),
gMT-1100(2),
gMT-1000(3),
gMT-0900(4),
gMT-0800(5),
gMT-0700(6),
gMT-0600(7),
gMT-0500(8),
gMT-0400(9),
gMT-0330(10),
gMT-0300(11),
gMT-0200(12),
gMT-0100(13),
gMT-0000(14),
gMT0100(15),
gMT0200(16),
gMT0300(17),
gMT0330(18),
gMT0400(19),
gMT0500(20),
gMT0530(21),
gMT0600(22),
gMT0700(23),
gMT0800(24),
gMT0900(25),
gMT1000(26),
gMT1100(27),
gMT1200(28)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Time Zone to use when synchronize with NTP server."
::= { ipmAgentTime 5 }
ipmAgentDayLightSaving OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable the Day Light Saving when synchronize with NTP server."
::= { ipmAgentTime 6 }
ipmAgentNetwork OBJECT IDENTIFIER ::= { ipmAgent 3 }
-- ===========================================================================
--
-- ipmConfigNetwork
--
-- Network Configuration Group of the device.
--
-- ===========================================================================
ipmAgentNetworkIp OBJECT IDENTIFIER ::= { ipmAgentNetwork 1 }
-- ===========================================================================
--
-- ipmAgentNetworkIp
--
-- Ip address Configuration Group of the device.
--
-- ===========================================================================
ipmAgentNetworkIpAdress OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The ip address that NMS can identify the managed device."
::= { ipmAgentNetworkIp 1}
ipmAgentNetworkIpGateway OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The default gateway that allow device managed through routers."
::= { ipmAgentNetworkIp 2}
ipmAgentNetworkIpSubnet OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Internet address subnet mask"
::= { ipmAgentNetworkIp 3}
ipmAgentNetworkDhcpControl OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable DHCP protocol"
::= { ipmAgentNetwork 2 }
ipmAgentNetworkPingControl OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable to response to PING request."
::= { ipmAgentNetwork 3 }
ipmAgentNetworkTftpControl OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable TFTP protocol"
::= { ipmAgentNetwork 4 }
ipmAgentNetworkTelnet OBJECT IDENTIFIER ::= { ipmAgentNetwork 5 }
-- ===========================================================================
--
-- ipmConfigNetworkTelnet
--
-- Telnet Configuration Group of the device.
--
-- ===========================================================================
ipmAgentTelnetControl OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable Telnet protocol."
::= { ipmAgentNetworkTelnet 1 }
ipmAgentTelnetPort OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The TCP port for telnet"
::= { ipmAgentNetworkTelnet 2}
ipmAgentNetworkHttp OBJECT IDENTIFIER ::= { ipmAgentNetwork 6 }
-- ===========================================================================
--
-- ipmConfigNetworkHttp
--
-- HTTP Configuration Group of the device.
--
-- ===========================================================================
ipmAgentHttpControl OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable HTTP protocol."
::= { ipmAgentNetworkHttp 1 }
ipmAgentHttpPort OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The TCP port for HTTP."
::= { ipmAgentNetworkHttp 2}
ipmAgentNetworkSnmp OBJECT IDENTIFIER ::= { ipmAgentNetwork 7 }
-- ===========================================================================
--
-- ipmAgentNetworkSnmp
--
-- SNMP Configuration Group of the device.
--
-- ===========================================================================
ipmAgentSnmpControl OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable SNMP protocol."
::= { ipmAgentNetworkSnmp 1 }
ipmAgentSnmpPort OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The UDP port for SNMP."
::= { ipmAgentNetworkSnmp 2}
ipmAgentLog OBJECT IDENTIFIER ::= { ipmAgentConfig 4 }
-- ===========================================================================
--
-- ipmConfigLog
--
-- Log Configuration Group of the device.
--
-- ===========================================================================
pduAgentDataLogInterval OBJECT-TYPE
SYNTAX INTEGER (60..28800) -- in seconds
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The interval of the updation of the data log. The value
is in seconds"
::= { ipmAgentLog 1 }
ipmAgentControl OBJECT IDENTIFIER ::= { ipmAgentConfig 5 }
-- ===========================================================================
--
-- ipmAgentAgentControl
--
-- Agent Control Configuration Group of the device.
--
-- ===========================================================================
ipmAgentControlDefault OBJECT-TYPE
SYNTAX INTEGER {
reset(1),
nothing(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Reset all parameters of the agent to default value."
::= { ipmAgentControl 1}
ipmAgentControlRestart OBJECT-TYPE
SYNTAX INTEGER {
restart(1),
nothing(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Restart the agent."
::= { ipmAgentControl 2}
ipmAgentTrap OBJECT IDENTIFIER ::= { ipmAgentConfig 6 }
-- ===========================================================================
--
-- ipmAgentTrap
--
-- Trap Configuration Group of the agent.
--
-- ===========================================================================
ipmAgentTrapRetryCount OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The count of repeat traps send to NMS before trap
acknowledgement received."
::= { ipmAgentTrap 1}
ipmAgentTrapRetryTime OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The time interval in seconds between retry traps sned to NMS."
::= { ipmAgentTrap 2}
ipmAgentTrapAckSignature OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The signature of trap acknowledgement."
::= { ipmAgentTrap 3}
-- ===========================================================================
--
-- ipmAgentTrapsReceiversTable
--
-- ===========================================================================
ipmAgentTrapsReceiversTable OBJECT-TYPE
SYNTAX SEQUENCE OF IpmAgentTrapsReceiversEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of managers to send traps to. The number of
entries is given by the value of agentConfigNumTrapReceivers"
::= { ipmAgentConfig 7}
ipmAgentTrapsReceiversEntry OBJECT-TYPE
SYNTAX IpmAgentTrapsReceiversEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The managers to send traps to."
INDEX { trapsIndex }
::= { ipmAgentTrapsReceiversTable 1 }
IpmAgentTrapsReceiversEntry ::=
SEQUENCE {
trapsIndex INTEGER,
trapsReceiverAddr IpAddress,
receiverCommunityString DisplayString,
receiverNmsType INTEGER,
receiverSeverityLevel INTEGER,
receiverDescription DisplayString
}
trapsIndex OBJECT-TYPE
SYNTAX INTEGER (0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a trap receiver entry."
::= { ipmAgentTrapsReceiversEntry 1 }
trapsReceiverAddr OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The IP address of the manager to send a trap to."
::= { ipmAgentTrapsReceiversEntry 2 }
receiverCommunityString OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..15))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The community name to use in the trap when
sent to the manager."
::= { ipmAgentTrapsReceiversEntry 3 }
receiverNmsType OBJECT-TYPE
SYNTAX INTEGER {
none(1),
iPoManII-trap(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The trap group that NMS desired."
::= { ipmAgentTrapsReceiversEntry 4 }
receiverSeverityLevel OBJECT-TYPE
SYNTAX INTEGER {
informational(1),
warning(2),
severe(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The severity level of traps to be received by this manager."
::= { ipmAgentTrapsReceiversEntry 5 }
receiverDescription OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Description of trap receivers"
::= { ipmAgentTrapsReceiversEntry 6 }
-- ===========================================================================
--
-- ipmAgentAccessControlTable
--
-- ===========================================================================
ipmAgentAccessControlTable OBJECT-TYPE
SYNTAX SEQUENCE OF IpmAgentAccessControlEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of managers which can access the device with private
community string."
::= { ipmAgentConfig 8}
ipmAgentAccessControlEntry OBJECT-TYPE
SYNTAX IpmAgentAccessControlEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The managers."
INDEX { accessIndex}
::= { ipmAgentAccessControlTable 1 }
IpmAgentAccessControlEntry ::=
SEQUENCE {
accessIndex
INTEGER,
accessControlAddr
IpAddress,
accessControlMode
INTEGER
}
accessIndex OBJECT-TYPE
SYNTAX INTEGER (0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a access control entry."
::= { ipmAgentAccessControlEntry 1 }
accessControlAddr OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The IP address of the manager to access the device."
::= { ipmAgentAccessControlEntry 2 }
accessControlMode OBJECT-TYPE
SYNTAX INTEGER {
permitted (1),
denied (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Access type, only read/Write access type can change parameter
of the device."
::= { ipmAgentAccessControlEntry 3 }
ipmDeviceInlet OBJECT IDENTIFIER ::= { ipmDevice 1 }
-- ===========================================================================
--
-- ipmDeviceInlet
--
-- Inlet Group
--
-- ===========================================================================
ipmDeviceInletNumber OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The inlet number on this device."
::= { ipmDeviceInlet 1}
ipmDeviceInletConfigTable OBJECT-TYPE
SYNTAX SEQUENCE OF IpmDeviceInletConfigEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of inlet on this device."
::= { ipmDeviceInlet 2}
ipmDeviceInletConfigEntry OBJECT-TYPE
SYNTAX IpmDeviceInletConfigEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The inlet number of device."
INDEX { inletConfigIndex}
::= { ipmDeviceInletConfigTable 1 }
IpmDeviceInletConfigEntry ::=
SEQUENCE {
inletConfigIndex
INTEGER,
inletConfigDesc
DisplayString,
inletConfigVoltageHigh
INTEGER,
inletConfigVoltageHighAction
INTEGER,
inletConfigVoltageLow
INTEGER,
inletConfigVoltageLowAction
INTEGER,
inletConfigCurrentHigh
INTEGER,
inletConfigCurrentHighAction
INTEGER,
inletConfigFrequencyHigh
INTEGER,
inletConfigfrequencyHighAction
INTEGER,
inletConfigFrequencyLow
INTEGER,
inletConfigfrequencyLowAction
INTEGER
}
inletConfigIndex OBJECT-TYPE
SYNTAX INTEGER (0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a access inlet configuration table."
::= { ipmDeviceInletConfigEntry 1 }
inletConfigDesc OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A Description of inlet of device."
::= { ipmDeviceInletConfigEntry 2 }
inletConfigVoltageHigh OBJECT-TYPE
SYNTAX INTEGER (1..65500) --
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Inlet high voltage threshold, in volts."
::= { ipmDeviceInletConfigEntry 3 }
inletConfigVoltageHighAction OBJECT-TYPE
SYNTAX INTEGER {
outletsOff (1),
nothing (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Reaction of the device when inlet voltage higher than set point."
::= { ipmDeviceInletConfigEntry 4 }
inletConfigVoltageLow OBJECT-TYPE
SYNTAX INTEGER (1..65500) --
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Inlet low voltage threshold, in volts."
::= { ipmDeviceInletConfigEntry 5 }
inletConfigVoltageLowAction OBJECT-TYPE
SYNTAX INTEGER {
outletsOff (1),
nothing (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Reaction of the device when inlet voltage lower than set point."
::= { ipmDeviceInletConfigEntry 6 }
inletConfigCurrentHigh OBJECT-TYPE
SYNTAX INTEGER (1..160) --
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Inlet low voltage threshold, in 0.1 amps."
::= { ipmDeviceInletConfigEntry 7 }
inletConfigCurrentHighAction OBJECT-TYPE
SYNTAX INTEGER {
outletsOff (1),
nothing (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Reaction of the device when inlet current higher than set point."
::= { ipmDeviceInletConfigEntry 8 }
inletConfigFrequencyHigh OBJECT-TYPE
SYNTAX INTEGER (1..65500) --
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Inlet high frequency threshold, in hz."
::= { ipmDeviceInletConfigEntry 9 }
inletConfigfrequencyHighAction OBJECT-TYPE
SYNTAX INTEGER {
outletsOff (1),
nothing (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Reaction of the device when inlet frequency higher than set point."
::= { ipmDeviceInletConfigEntry 10 }
inletConfigFrequencyLow OBJECT-TYPE
SYNTAX INTEGER (1..65500) --
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Inlet low frequency threshold, in hz."
::= { ipmDeviceInletConfigEntry 11 }
inletConfigfrequencyLowAction OBJECT-TYPE
SYNTAX INTEGER {
outletsOff (1),
nothing (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Reaction of the device when inlet frequency lower than set point."
::= { ipmDeviceInletConfigEntry 12 }
ipmDeviceInletStatusTable OBJECT-TYPE
SYNTAX SEQUENCE OF IpmDeviceInletStatusEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of inlet on this device."
::= { ipmDeviceInlet 3}
ipmDeviceInletStatusEntry OBJECT-TYPE
SYNTAX IpmDeviceInletStatusEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The inlet number of device."
INDEX { inletStatusIndex}
::= { ipmDeviceInletStatusTable 1 }
IpmDeviceInletStatusEntry ::=
SEQUENCE {
inletStatusIndex
INTEGER,
inletStatusVoltage
INTEGER,
inletStatusCurrent
INTEGER,
inletStatusFrequency
INTEGER,
inletStatusKwatt
INTEGER,
inletStatusWH
INTEGER
}
inletStatusIndex OBJECT-TYPE
SYNTAX INTEGER (0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a access inlet configuration table."
::= { ipmDeviceInletStatusEntry 1 }
inletStatusVoltage OBJECT-TYPE
SYNTAX INTEGER (1..65500) --
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Inlet Voltage in 0.1 volts"
::= { ipmDeviceInletStatusEntry 2 }
inletStatusCurrent OBJECT-TYPE
SYNTAX INTEGER (0..65500) --
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Inlet Current in 0.001 Amp."
::= { ipmDeviceInletStatusEntry 3 }
inletStatusFrequency OBJECT-TYPE
SYNTAX INTEGER (1..65500) --
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Inlet Frequency in 0.1 Hz"
::= { ipmDeviceInletStatusEntry 4 }
inletStatusKwatt OBJECT-TYPE
SYNTAX INTEGER (0..65500) --
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Inlet Kwatt in 0.1 KW/H"
::= { ipmDeviceInletStatusEntry 5 }
inletStatusWH OBJECT-TYPE
SYNTAX INTEGER (1..65500) --
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Inlet Kwatt in 0.1 W/H"
::= { ipmDeviceInletStatusEntry 6 }
inletWattReset OBJECT-TYPE
SYNTAX INTEGER {
none(1),
inlet1(2),
inlet2(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Reset inlet kw."
::= { ipmDeviceInlet 4}
ipmDeviceOutlet OBJECT IDENTIFIER ::= { ipmDevice 2 }
-- ===========================================================================
--
-- ipmDeviceOutlet
--
-- Inlet Group
--
-- ===========================================================================
ipmDeviceOutletNumber OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The outlet number on this device."
::= { ipmDeviceOutlet 1}
ipmDeviceOutletConfigTable OBJECT-TYPE
SYNTAX SEQUENCE OF IpmDeviceOutletConfigEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of outlet on this device."
::= { ipmDeviceOutlet 2}
ipmDeviceOutletConfigEntry OBJECT-TYPE
SYNTAX IpmDeviceOutletConfigEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The inlet number of device."
INDEX { inletConfigIndex}
::= { ipmDeviceOutletConfigTable 1 }
IpmDeviceOutletConfigEntry ::=
SEQUENCE {
outletConfigIndex
INTEGER,
outletConfigDesc
DisplayString,
outletConfigLocation
DisplayString,
outletConfigOnDelay
INTEGER,
outletConfigOffDelay
INTEGER,
outletConfigCurrentHigh
INTEGER,
outletConfigCurrentHighAction
INTEGER
}
outletConfigIndex OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a access inlet configuration table."
::= { ipmDeviceOutletConfigEntry 1 }
outletConfigDesc OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A Description of outlet of device."
::= { ipmDeviceOutletConfigEntry 2 }
outletConfigLocation OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Location of device connectted to this outlet."
::= { ipmDeviceOutletConfigEntry 3 }
outletConfigOnDelay OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The delay time before turn on tis outlet, in seconds."
::= { ipmDeviceOutletConfigEntry 4 }
outletConfigOffDelay OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The delay time before turn off tis outlet, in seconds."
::= { ipmDeviceOutletConfigEntry 5 }
outletConfigCurrentHigh OBJECT-TYPE
SYNTAX INTEGER (1..65500) --
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The outlet high current threshold, in amp."
::= { ipmDeviceOutletConfigEntry 6 }
outletConfigCurrentHighAction OBJECT-TYPE
SYNTAX INTEGER {
outletOff (1),
nothing (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Reaction of the device when outlet current higher than set point."
::= { ipmDeviceOutletConfigEntry 7 }
ipmDeviceOutletStatusTable OBJECT-TYPE
SYNTAX SEQUENCE OF IpmDeviceOutletStatusEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of outlet on this device."
::= { ipmDeviceOutlet 3}
ipmDeviceOutletStatusEntry OBJECT-TYPE
SYNTAX IpmDeviceOutletStatusEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The outlet number of device."
INDEX { outletStatusIndex}
::= { ipmDeviceOutletStatusTable 1 }
IpmDeviceOutletStatusEntry ::=
SEQUENCE {
outletStatusIndex
INTEGER,
outletStatusStatus
INTEGER,
outletStatusCurrent
INTEGER,
outletStatusKwatt
INTEGER,
outletStatusWH
INTEGER,
outletStatusStateTime
INTEGER,
outletStatusTimeToGo
INTEGER
}
outletStatusIndex OBJECT-TYPE
SYNTAX INTEGER (0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a access outlet configuration table."
::= { ipmDeviceOutletStatusEntry 1 }
outletStatusStatus OBJECT-TYPE
SYNTAX INTEGER {
unknow (1),
outletOff (2),
outletOn (3),
outletOffToOn (4),
outletOnToOff (5),
outletCycling (6)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Outlet state"
::= { ipmDeviceOutletStatusEntry 2 }
outletStatusCurrent OBJECT-TYPE
SYNTAX INTEGER (0..65500) --
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The outlet Current in 0.001 Amp."
::= { ipmDeviceOutletStatusEntry 3 }
outletStatusKwatt OBJECT-TYPE
SYNTAX INTEGER (0..65500) --
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The outlet Kwatt in 0.001 KW/H."
::= { ipmDeviceOutletStatusEntry 4 }
outletStatusWH OBJECT-TYPE
SYNTAX INTEGER (0..65500) --
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The outlet Watt in 0.1 W/H."
::= { ipmDeviceOutletStatusEntry 5 }
outletStatusStateTime OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Time in seconds since the outlet changed to current state."
::= { ipmDeviceOutletStatusEntry 6 }
outletStatusTimeToGo OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Remain time the outlet state will be changed by agent, in seconds"
::= { ipmDeviceOutletStatusEntry 7 }
ipmDeviceOutletControlTable OBJECT-TYPE
SYNTAX SEQUENCE OF IpmDeviceOutletControlEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of outlet on this device."
::= { ipmDeviceOutlet 4}
ipmDeviceOutletControlEntry OBJECT-TYPE
SYNTAX IpmDeviceOutletControlEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The outlet number of device."
INDEX { outletControlIndex}
::= { ipmDeviceOutletControlTable 1 }
IpmDeviceOutletControlEntry ::=
SEQUENCE {
outletControlIndex
INTEGER,
outletControlControl
INTEGER
}
outletControlIndex OBJECT-TYPE
SYNTAX INTEGER (0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a access outlet configuration table."
::= { ipmDeviceOutletControlEntry 1 }
outletControlControl OBJECT-TYPE
SYNTAX INTEGER {
none(1),
cancelAction(2),
onImmediately(3),
offImmediately(4),
cycleImmediately(5),
onByActionTimer(6),
offByActionTimer(7),
cycleByActionTimer(8),
onThenOffByActionTimers(9),
offThenOnByActionTimers(10)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Set to control the outlet perform action as requested."
::= { ipmDeviceOutletControlEntry 2 }
ipmDeviceOutletControlAll OBJECT-TYPE
SYNTAX INTEGER {
none(1),
cancelAction(2),
onImmediately(3),
offImmediately(4),
cycleImmediately(5),
onByActionTimers(6),
offByActionTimers(7),
cycleByActionTimers(8),
onThenOffByActionTimers(9),
offThenOnByActionTimers(10)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Set to control all outlets perform action as requested."
::= { ipmDeviceOutlet 5}
ipmDeviceOutletWattReset OBJECT-TYPE
SYNTAX INTEGER {
none(1),
outleta(2),
outletb(3),
outletc(4),
outletd(5),
outlete(6),
outletf(7),
outletg(8),
outleth(9),
outleti(10),
outletj(11),
outletk(12),
outletl(13)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Reset outlet kw."
::= { ipmDeviceOutlet 6}
ipmDeviceCcOut OBJECT IDENTIFIER ::= { ipmDevice 3 }
-- ===========================================================================
--
-- ipmDeviceCCOut
--
-- Contact Closure Output Group
--
-- ===========================================================================
ipmDeviceCcOutNumber OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The contact closure output number on this device."
::= { ipmDeviceCcOut 1}
ipmDeviceCcOutConfigTable OBJECT-TYPE
SYNTAX SEQUENCE OF IpmDeviceCcOutConfigEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of contact closure output on this device."
::= { ipmDeviceCcOut 2}
ipmDeviceCcOutConfigEntry OBJECT-TYPE
SYNTAX IpmDeviceCcOutConfigEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The CC number of device."
INDEX { ccOutConfigIndex}
::= { ipmDeviceCcOutConfigTable 1 }
IpmDeviceCcOutConfigEntry ::=
SEQUENCE {
ccOutConfigIndex
INTEGER,
ccOutConfigDesc
DisplayString,
ccOutConfigEventAction
INTEGER,
ccOutConfigCloseDelay
INTEGER,
ccOutConfigOpenDelay
INTEGER
}
ccOutConfigIndex OBJECT-TYPE
SYNTAX INTEGER (0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to access contact closure output configuration table."
::= { ipmDeviceCcOutConfigEntry 1 }
ccOutConfigDesc OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A Description of a contact closure output of device."
::= { ipmDeviceCcOutConfigEntry 2 }
ccOutConfigEventAction OBJECT-TYPE
SYNTAX INTEGER {
yes (1),
no (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disble the contact closure output to react to events."
::= { ipmDeviceCcOutConfigEntry 3 }
ccOutConfigCloseDelay OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The delay time in seconds when the contact closure output set to close."
::= { ipmDeviceCcOutConfigEntry 4 }
ccOutConfigOpenDelay OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The delay time in seconds when the contact closure output set to open."
::= { ipmDeviceCcOutConfigEntry 5 }
ipmDeviceCcOutStatusTable OBJECT-TYPE
SYNTAX SEQUENCE OF IpmDeviceCcOutStatusEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of contact closure output on this device."
::= { ipmDeviceCcOut 3}
ipmDeviceCcOutStatusEntry OBJECT-TYPE
SYNTAX IpmDeviceCcOutStatusEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The CC number of device."
INDEX { ccOutStatusIndex}
::= { ipmDeviceCcOutStatusTable 1 }
IpmDeviceCcOutStatusEntry ::=
SEQUENCE {
ccOutStatusIndex
INTEGER,
ccOutStatusStatus
INTEGER,
ccOutStatusTimeOnState
INTEGER
}
ccOutStatusIndex OBJECT-TYPE
SYNTAX INTEGER (0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to access contact closure output configuration table."
::= { ipmDeviceCcOutStatusEntry 1 }
ccOutStatusStatus OBJECT-TYPE
SYNTAX INTEGER {
closed (1),
open (2)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"State of a contact closure output of device."
::= { ipmDeviceCcOutStatusEntry 2 }
ccOutStatusTimeOnState OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Time in seconds since the contact closure output changed to current state."
::= { ipmDeviceCcOutStatusEntry 3 }
ipmDeviceCcOutControlTable OBJECT-TYPE
SYNTAX SEQUENCE OF IpmDeviceCcOutControlEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of contact closure output on this device."
::= { ipmDeviceCcOut 4}
ipmDeviceCcOutControlEntry OBJECT-TYPE
SYNTAX IpmDeviceCcOutControlEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The outlet number of device."
INDEX { ccOutControlIndex}
::= { ipmDeviceCcOutControlTable 1 }
IpmDeviceCcOutControlEntry ::=
SEQUENCE {
ccOutControlIndex
INTEGER,
ccOutControlControl
INTEGER
}
ccOutControlIndex OBJECT-TYPE
SYNTAX INTEGER (0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a access contact closure output configuration table."
::= { ipmDeviceCcOutControlEntry 1 }
ccOutControlControl OBJECT-TYPE
SYNTAX INTEGER {
none(1),
cancelAction(2),
closeImmediately(3),
openImmediately(4),
cycleImmediately(5),
closeByCloseTimer(6),
openByOpenTimer(7),
cycleByActionTimer(8),
closeThenOpenByActionTimers(9),
openThenCloseByActionTimers(10)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Set to control the contact closure output perform action as requested."
::= { ipmDeviceCcOutControlEntry 2 }
ipmSlaveState OBJECT IDENTIFIER ::= { ipmSlave 1 }
-- ===========================================================================
--
-- ipmSlaveState
--
-- Daisy Chain Device Group
--
-- ===========================================================================
--
ipmSlaveStateTable OBJECT-TYPE
SYNTAX SEQUENCE OF IpmSlaveStateEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of outlet on this device."
::= { ipmSlaveState 1}
ipmSlaveStateEntry OBJECT-TYPE
SYNTAX IpmSlaveStateEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The outlet number of device."
INDEX { slaveStateIndex}
::= { ipmSlaveStateTable 1 }
IpmSlaveStateEntry ::=
SEQUENCE {
slaveStateIndex
INTEGER,
slaveStateControl01
INTEGER
}
slaveStateIndex OBJECT-TYPE
SYNTAX INTEGER (0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a access outlet configuration table."
::= { ipmSlaveStateEntry 1 }
slaveStateControl01 OBJECT-TYPE
SYNTAX INTEGER {
disconnected(1),
connected(2)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Set to control the outlet perform action as requested to slave outlet A"
::= { ipmSlaveStateEntry 2 }
ipmSlaveInlet OBJECT IDENTIFIER ::= { ipmSlave 2 }
-- ===========================================================================
--
-- ipmSlaveAllDevice
--
-- Daisy Chain Device Group
--
-- ===========================================================================
ipmSlaveInletStatus OBJECT IDENTIFIER ::= { ipmSlaveInlet 1 }
-- ===========================================================================
--
-- ipmSlaveAllDevice
--
-- Daisy Chain Device Group
--
-- ===========================================================================
ipmDeviceSlaveInletStatusTable OBJECT-TYPE
SYNTAX SEQUENCE OF IpmDeviceSlaveInletStatusEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of inlet on this device."
::= { ipmSlaveInletStatus 1}
ipmDeviceSlaveInletStatusEntry OBJECT-TYPE
SYNTAX IpmDeviceSlaveInletStatusEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The inlet number of device."
INDEX { inletStatusIndex}
::= { ipmDeviceSlaveInletStatusTable 1 }
IpmDeviceSlaveInletStatusEntry ::=
SEQUENCE {
inletSlaveStatusIndex
INTEGER,
inletSlaveStatusVoltage
INTEGER,
inletSlaveStatusCurrent
INTEGER,
inletSlaveStatusFrequency
INTEGER,
inletSlaveStatusKwatt
INTEGER,
inletSlaveStatusWH
INTEGER,
inletSlaveStatusVoltage2
INTEGER,
inletSlaveStatusCurrent2
INTEGER,
inletSlaveStatusFrequency2
INTEGER,
inletSlaveStatusKwatt2
INTEGER,
inletSlaveStatusWH2
INTEGER
}
inletSlaveStatusIndex OBJECT-TYPE
SYNTAX INTEGER (0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a access inlet configuration table."
::= { ipmDeviceSlaveInletStatusEntry 1 }
inletSlaveStatusVoltage OBJECT-TYPE
SYNTAX INTEGER (1..65500) --
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Inlet Voltage in 0.1 volts"
::= { ipmDeviceSlaveInletStatusEntry 2 }
inletSlaveStatusCurrent OBJECT-TYPE
SYNTAX INTEGER (0..65500) --
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Inlet Current in 0.001 Amp."
::= { ipmDeviceSlaveInletStatusEntry 3 }
inletSlaveStatusFrequency OBJECT-TYPE
SYNTAX INTEGER (1..65500) --
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Inlet Frequency in 0.1 Hz"
::= { ipmDeviceSlaveInletStatusEntry 4 }
inletSlaveStatusKwatt OBJECT-TYPE
SYNTAX INTEGER (0..65500) --
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Inlet Kwatt in 0.001 KW/H"
::= { ipmDeviceSlaveInletStatusEntry 5 }
inletSlaveStatusWH OBJECT-TYPE
SYNTAX INTEGER (1..65500) --
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Inlet Kwatt in 0.001 KW/H"
::= { ipmDeviceSlaveInletStatusEntry 6 }
inletSlaveStatusVoltage2 OBJECT-TYPE
SYNTAX INTEGER (1..65500) --
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Inlet Voltage in 0.1 volts"
::= { ipmDeviceSlaveInletStatusEntry 7 }
inletSlaveStatusCurrent2 OBJECT-TYPE
SYNTAX INTEGER (0..65500) --
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Inlet Current in 0.001 Amp."
::= { ipmDeviceSlaveInletStatusEntry 8 }
inletSlaveStatusFrequency2 OBJECT-TYPE
SYNTAX INTEGER (1..65500) --
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Inlet Frequency in 0.1 Hz"
::= { ipmDeviceSlaveInletStatusEntry 9 }
inletSlaveStatusKwatt2 OBJECT-TYPE
SYNTAX INTEGER (0..65500) --
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Inlet Kwatt in 0.001 KW/H"
::= { ipmDeviceSlaveInletStatusEntry 10 }
inletSlaveStatusWH2 OBJECT-TYPE
SYNTAX INTEGER (1..65500) --
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Inlet Kwatt in 0.001 KW/H"
::= { ipmDeviceSlaveInletStatusEntry 11 }
ipmSlaveInletConfig OBJECT IDENTIFIER ::= { ipmSlaveInlet 2 }
-- ===========================================================================
--
-- ipmSlaveAllDevice
--
-- Daisy Chain Device Group
--
-- ===========================================================================
ipmDeviceslaveInletConfigTable OBJECT-TYPE
SYNTAX SEQUENCE OF IpmDeviceslaveInletConfigEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of inlet on this device."
::= { ipmSlaveInletConfig 1}
ipmDeviceslaveInletConfigEntry OBJECT-TYPE
SYNTAX IpmDeviceslaveInletConfigEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The inlet number of device."
INDEX { slaveInletConfigIndex}
::= { ipmDeviceslaveInletConfigTable 1 }
IpmDeviceslaveInletConfigEntry ::=
SEQUENCE {
slaveInletConfigIndex
INTEGER,
slaveInletConfigVoltageHigh
INTEGER,
slaveInletConfigVoltageLow
INTEGER,
slaveInlet2ConfigVoltageHigh
INTEGER,
slaveInlet2ConfigVoltageLow
INTEGER
}
slaveInletConfigIndex OBJECT-TYPE
SYNTAX INTEGER (0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a access inlet configuration table."
::= { ipmDeviceslaveInletConfigEntry 1 }
slaveInletConfigVoltageHigh OBJECT-TYPE
SYNTAX INTEGER (1..65500) --
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Inlet high voltage threshold, in volts."
::= { ipmDeviceslaveInletConfigEntry 2 }
slaveInletConfigVoltageLow OBJECT-TYPE
SYNTAX INTEGER (1..65500) --
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Inlet low voltage threshold, in volts."
::= { ipmDeviceslaveInletConfigEntry 3 }
slaveInlet2ConfigVoltageHigh OBJECT-TYPE
SYNTAX INTEGER (1..65500) --
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Inlet 2 high voltage threshold, in volts."
::= { ipmDeviceslaveInletConfigEntry 4 }
slaveInlet2ConfigVoltageLow OBJECT-TYPE
SYNTAX INTEGER (1..65500) --
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Inlet low voltage threshold, in volts."
::= { ipmDeviceslaveInletConfigEntry 5 }
ipmSlaveOutlet OBJECT IDENTIFIER ::= { ipmSlave 3 }
-- ===========================================================================
--
-- ipmSlaveAllDevice
--
-- Daisy Chain Device Group
--
-- ===========================================================================
ipmSlaveOutletConfig OBJECT IDENTIFIER ::= { ipmSlaveOutlet 1 }
-- ===========================================================================
--
-- ipmOutletConfig
--
-- Outlet Config Group
--
-- ===========================================================================
--
-- Outlet Name Description
--
ipmSlaveDeviceOutletNameTable OBJECT-TYPE
SYNTAX SEQUENCE OF IpmSlaveDeviceOutletNameEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of outlet on this device."
::= { ipmSlaveOutletConfig 1}
ipmSlaveDeviceOutletNameEntry OBJECT-TYPE
SYNTAX IpmSlaveDeviceOutletNameEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The outlet number of device."
INDEX { slaveOutletNameIndex}
::= { ipmSlaveDeviceOutletNameTable 1 }
IpmSlaveDeviceOutletNameEntry ::=
SEQUENCE {
slaveOutletNameIndex
INTEGER,
slaveOutletName01
DisplayString,
slaveOutletName02
DisplayString,
slaveOutletName03
DisplayString,
slaveOutletName04
DisplayString,
slaveOutletName05
DisplayString,
slaveOutletName06
DisplayString,
slaveOutletName07
DisplayString,
slaveOutletName08
DisplayString,
slaveOutletName09
DisplayString,
slaveOutletName10
DisplayString,
slaveOutletName11
DisplayString,
slaveOutletName12
DisplayString
}
slaveOutletNameIndex OBJECT-TYPE
SYNTAX INTEGER (0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a access outlet configuration table."
::= { ipmSlaveDeviceOutletNameEntry 1 }
slaveOutletName01 OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A Description of a outlet name of device."
::= { ipmSlaveDeviceOutletNameEntry 2 }
slaveOutletName02 OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A Description of a outlet name of device."
::= { ipmSlaveDeviceOutletNameEntry 3 }
slaveOutletName03 OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A Description of a outlet name of device."
::= { ipmSlaveDeviceOutletNameEntry 4 }
slaveOutletName04 OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A Description of a outlet name of device."
::= { ipmSlaveDeviceOutletNameEntry 5 }
slaveOutletName05 OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A Description of a outlet name of device."
::= { ipmSlaveDeviceOutletNameEntry 6 }
slaveOutletName06 OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A Description of a outlet name of device."
::= { ipmSlaveDeviceOutletNameEntry 7 }
slaveOutletName07 OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A Description of a outlet name of device."
::= { ipmSlaveDeviceOutletNameEntry 8 }
slaveOutletName08 OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A Description of a outlet name of device."
::= { ipmSlaveDeviceOutletNameEntry 9 }
slaveOutletName09 OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A Description of a outlet name of device."
::= { ipmSlaveDeviceOutletNameEntry 10 }
slaveOutletName10 OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A Description of a outlet name of device."
::= { ipmSlaveDeviceOutletNameEntry 11 }
slaveOutletName11 OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A Description of a outlet name of device."
::= { ipmSlaveDeviceOutletNameEntry 12 }
slaveOutletName12 OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A Description of a outlet name of device."
::= { ipmSlaveDeviceOutletNameEntry 13 }
-- ===============================
-- Outlet Location Description
-- ===============================
ipmSlaveDeviceOutletLocationTable OBJECT-TYPE
SYNTAX SEQUENCE OF IpmSlaveDeviceOutletLocationEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of outlet on this device."
::= { ipmSlaveOutletConfig 2}
ipmSlaveDeviceOutletLocationEntry OBJECT-TYPE
SYNTAX IpmSlaveDeviceOutletLocationEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The outlet number of device."
INDEX { slaveOutletLocationIndex}
::= { ipmSlaveDeviceOutletLocationTable 1 }
IpmSlaveDeviceOutletLocationEntry ::=
SEQUENCE {
slaveOutletLocationIndex
INTEGER,
slaveOutletLocation01
DisplayString,
slaveOutletLocation02
DisplayString,
slaveOutletLocation03
DisplayString,
slaveOutletLocation04
DisplayString,
slaveOutletLocation05
DisplayString,
slaveOutletLocation06
DisplayString,
slaveOutletLocation07
DisplayString,
slaveOutletLocation08
DisplayString,
slaveOutletLocation09
DisplayString,
slaveOutletLocation10
DisplayString,
slaveOutletLocation11
DisplayString,
slaveOutletLocation12
DisplayString
}
slaveOutletLocationIndex OBJECT-TYPE
SYNTAX INTEGER (0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a access outlet configuration table."
::= { ipmSlaveDeviceOutletLocationEntry 1 }
slaveOutletLocation01 OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A Description of a outlet name of device."
::= { ipmSlaveDeviceOutletLocationEntry 2 }
slaveOutletLocation02 OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A Description of a outlet name of device."
::= { ipmSlaveDeviceOutletLocationEntry 3 }
slaveOutletLocation03 OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A Description of a outlet name of device."
::= { ipmSlaveDeviceOutletLocationEntry 4 }
slaveOutletLocation04 OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A Description of a outlet name of device."
::= { ipmSlaveDeviceOutletLocationEntry 5 }
slaveOutletLocation05 OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A Description of a outlet name of device."
::= { ipmSlaveDeviceOutletLocationEntry 6 }
slaveOutletLocation06 OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A Description of a outlet name of device."
::= { ipmSlaveDeviceOutletLocationEntry 7 }
slaveOutletLocation07 OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A Description of a outlet name of device."
::= { ipmSlaveDeviceOutletLocationEntry 8 }
slaveOutletLocation08 OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A Description of a outlet name of device."
::= { ipmSlaveDeviceOutletLocationEntry 9 }
slaveOutletLocation09 OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A Description of a outlet name of device."
::= { ipmSlaveDeviceOutletLocationEntry 10 }
slaveOutletLocation10 OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A Description of a outlet name of device."
::= { ipmSlaveDeviceOutletLocationEntry 11 }
slaveOutletLocation11 OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A Description of a outlet name of device."
::= { ipmSlaveDeviceOutletLocationEntry 12 }
slaveOutletLocation12 OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A Description of a outlet name of device."
::= { ipmSlaveDeviceOutletLocationEntry 13 }
-- ==========================================
-- Outlet On Delay Time
-- ==========================================
ipmSlaveDeviceOutletOnTimeTable OBJECT-TYPE
SYNTAX SEQUENCE OF IpmSlaveDeviceOutletOnTimeEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of outlet on this device."
::= { ipmSlaveOutletConfig 3}
ipmSlaveDeviceOutletOnTimeEntry OBJECT-TYPE
SYNTAX IpmSlaveDeviceOutletOnTimeEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The outlet number of device."
INDEX { slaveOutletOnTimeIndex}
::= { ipmSlaveDeviceOutletOnTimeTable 1 }
IpmSlaveDeviceOutletOnTimeEntry ::=
SEQUENCE {
slaveOutletOnTimeIndex
INTEGER,
slaveOutletOnTime01
INTEGER,
slaveOutletOnTime02
INTEGER,
slaveOutletOnTime03
INTEGER,
slaveOutletOnTime04
INTEGER,
slaveOutletOnTime05
INTEGER,
slaveOutletOnTime06
INTEGER,
slaveOutletOnTime07
INTEGER,
slaveOutletOnTime08
INTEGER,
slaveOutletOnTime09
INTEGER,
slaveOutletOnTime10
INTEGER,
slaveOutletOnTime11
INTEGER,
slaveOutletOnTime12
INTEGER
}
slaveOutletOnTimeIndex OBJECT-TYPE
SYNTAX INTEGER (0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a access outlet configuration table."
::= { ipmSlaveDeviceOutletOnTimeEntry 1 }
slaveOutletOnTime01 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The delay time before turn on tis outlet, in seconds."
::= { ipmSlaveDeviceOutletOnTimeEntry 2 }
slaveOutletOnTime02 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The delay time before turn on tis outlet, in seconds."
::= { ipmSlaveDeviceOutletOnTimeEntry 3 }
slaveOutletOnTime03 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The delay time before turn on tis outlet, in seconds."
::= { ipmSlaveDeviceOutletOnTimeEntry 4 }
slaveOutletOnTime04 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The delay time before turn on tis outlet, in seconds."
::= { ipmSlaveDeviceOutletOnTimeEntry 5 }
slaveOutletOnTime05 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The delay time before turn on tis outlet, in seconds."
::= { ipmSlaveDeviceOutletOnTimeEntry 6 }
slaveOutletOnTime06 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The delay time before turn on tis outlet, in seconds."
::= { ipmSlaveDeviceOutletOnTimeEntry 7 }
slaveOutletOnTime07 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The delay time before turn on tis outlet, in seconds."
::= { ipmSlaveDeviceOutletOnTimeEntry 8 }
slaveOutletOnTime08 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The delay time before turn on tis outlet, in seconds."
::= { ipmSlaveDeviceOutletOnTimeEntry 9 }
slaveOutletOnTime09 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The delay time before turn on tis outlet, in seconds."
::= { ipmSlaveDeviceOutletOnTimeEntry 10 }
slaveOutletOnTime10 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The delay time before turn on tis outlet, in seconds."
::= { ipmSlaveDeviceOutletOnTimeEntry 11 }
slaveOutletOnTime11 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The delay time before turn on tis outlet, in seconds."
::= { ipmSlaveDeviceOutletOnTimeEntry 12 }
slaveOutletOnTime12 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The delay time before turn on tis outlet, in seconds."
::= { ipmSlaveDeviceOutletOnTimeEntry 13 }
-- ==========================================
-- Outlet Off Delay Time
-- ==========================================
ipmSlaveDeviceOutletOffTimeTable OBJECT-TYPE
SYNTAX SEQUENCE OF IpmSlaveDeviceOutletOffTimeEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of outlet on this device."
::= { ipmSlaveOutletConfig 4}
ipmSlaveDeviceOutletOffTimeEntry OBJECT-TYPE
SYNTAX IpmSlaveDeviceOutletOffTimeEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The outlet number of device."
INDEX { slaveOutletOffTimeIndex}
::= { ipmSlaveDeviceOutletOffTimeTable 1 }
IpmSlaveDeviceOutletOffTimeEntry ::=
SEQUENCE {
slaveOutletOffTimeIndex
INTEGER,
slaveOutletOffTime01
INTEGER,
slaveOutletOffTime02
INTEGER,
slaveOutletOffTime03
INTEGER,
slaveOutletOffTime04
INTEGER,
slaveOutletOffTime05
INTEGER,
slaveOutletOffTime06
INTEGER,
slaveOutletOffTime07
INTEGER,
slaveOutletOffTime08
INTEGER,
slaveOutletOffTime09
INTEGER,
slaveOutletOffTime10
INTEGER,
slaveOutletOffTime11
INTEGER,
slaveOutletOffTime12
INTEGER
}
slaveOutletOffTimeIndex OBJECT-TYPE
SYNTAX INTEGER (0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a access outlet configuration table."
::= { ipmSlaveDeviceOutletOffTimeEntry 1 }
slaveOutletOffTime01 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The delay time before turn on tis outlet, in seconds."
::= { ipmSlaveDeviceOutletOffTimeEntry 2 }
slaveOutletOffTime02 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The delay time before turn on tis outlet, in seconds."
::= { ipmSlaveDeviceOutletOffTimeEntry 3 }
slaveOutletOffTime03 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The delay time before turn on tis outlet, in seconds."
::= { ipmSlaveDeviceOutletOffTimeEntry 4 }
slaveOutletOffTime04 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The delay time before turn on tis outlet, in seconds."
::= { ipmSlaveDeviceOutletOffTimeEntry 5 }
slaveOutletOffTime05 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The delay time before turn on tis outlet, in seconds."
::= { ipmSlaveDeviceOutletOffTimeEntry 6 }
slaveOutletOffTime06 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The delay time before turn on tis outlet, in seconds."
::= { ipmSlaveDeviceOutletOffTimeEntry 7 }
slaveOutletOffTime07 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The delay time before turn on tis outlet, in seconds."
::= { ipmSlaveDeviceOutletOffTimeEntry 8 }
slaveOutletOffTime08 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The delay time before turn on tis outlet, in seconds."
::= { ipmSlaveDeviceOutletOffTimeEntry 9 }
slaveOutletOffTime09 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The delay time before turn on tis outlet, in seconds."
::= { ipmSlaveDeviceOutletOffTimeEntry 10 }
slaveOutletOffTime10 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The delay time before turn on tis outlet, in seconds."
::= { ipmSlaveDeviceOutletOffTimeEntry 11 }
slaveOutletOffTime11 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The delay time before turn on tis outlet, in seconds."
::= { ipmSlaveDeviceOutletOffTimeEntry 12 }
slaveOutletOffTime12 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The delay time before turn on tis outlet, in seconds."
::= { ipmSlaveDeviceOutletOffTimeEntry 13 }
-- ==========================================
-- Outlet Current TH
-- ==========================================
ipmSlaveDeviceOutletCurrThTable OBJECT-TYPE
SYNTAX SEQUENCE OF IpmSlaveDeviceOutletCurrThEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of outlet on this device."
::= { ipmSlaveOutletConfig 5}
ipmSlaveDeviceOutletCurrThEntry OBJECT-TYPE
SYNTAX IpmSlaveDeviceOutletCurrThEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The outlet number of device."
INDEX { slaveOutletCurrThIndex}
::= { ipmSlaveDeviceOutletCurrThTable 1 }
IpmSlaveDeviceOutletCurrThEntry ::=
SEQUENCE {
slaveOutletCurrThIndex
INTEGER,
slaveOutletCurrTh01
INTEGER,
slaveOutletCurrTh02
INTEGER,
slaveOutletCurrTh03
INTEGER,
slaveOutletCurrTh04
INTEGER,
slaveOutletCurrTh05
INTEGER,
slaveOutletCurrTh06
INTEGER,
slaveOutletCurrTh07
INTEGER,
slaveOutletCurrTh08
INTEGER,
slaveOutletCurrTh09
INTEGER,
slaveOutletCurrTh10
INTEGER,
slaveOutletCurrTh11
INTEGER,
slaveOutletCurrTh12
INTEGER
}
slaveOutletCurrThIndex OBJECT-TYPE
SYNTAX INTEGER (0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a access outlet configuration table."
::= { ipmSlaveDeviceOutletCurrThEntry 1 }
slaveOutletCurrTh01 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Outlet Current Threshold ,in 0.1 Amp."
::= { ipmSlaveDeviceOutletCurrThEntry 2 }
slaveOutletCurrTh02 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Outlet Current Threshold ,in 0.1 Amp."
::= { ipmSlaveDeviceOutletCurrThEntry 3 }
slaveOutletCurrTh03 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Outlet Current Threshold ,in 0.1 Amp."
::= { ipmSlaveDeviceOutletCurrThEntry 4 }
slaveOutletCurrTh04 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Outlet Current Threshold ,in 0.1 Amp."
::= { ipmSlaveDeviceOutletCurrThEntry 5 }
slaveOutletCurrTh05 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Outlet Current Threshold ,in 0.1 Amp."
::= { ipmSlaveDeviceOutletCurrThEntry 6 }
slaveOutletCurrTh06 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Outlet Current Threshold ,in 0.1 Amp."
::= { ipmSlaveDeviceOutletCurrThEntry 7 }
slaveOutletCurrTh07 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Outlet Current Threshold ,in 0.1 Amp."
::= { ipmSlaveDeviceOutletCurrThEntry 8 }
slaveOutletCurrTh08 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Outlet Current Threshold ,in 0.1 Amp."
::= { ipmSlaveDeviceOutletCurrThEntry 9 }
slaveOutletCurrTh09 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Outlet Current Threshold ,in 0.1 Amp."
::= { ipmSlaveDeviceOutletCurrThEntry 10 }
slaveOutletCurrTh10 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Outlet Current Threshold ,in 0.1 Amp."
::= { ipmSlaveDeviceOutletCurrThEntry 11 }
slaveOutletCurrTh11 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Outlet Current Threshold ,in 0.1 Amp."
::= { ipmSlaveDeviceOutletCurrThEntry 12 }
slaveOutletCurrTh12 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Outlet Current Threshold ,in 0.1 Amp."
::= { ipmSlaveDeviceOutletCurrThEntry 13 }
ipmSlaveOutletStatus OBJECT IDENTIFIER ::= { ipmSlaveOutlet 2 }
-- ===========================================================================
--
-- ipmOutletStatus
--
-- Outlet Status Group
--
-- ===========================================================================
-- ==========================================
-- Outlet Current
-- ==========================================
ipmSlaveDeviceOutletCurrentTable OBJECT-TYPE
SYNTAX SEQUENCE OF IpmSlaveDeviceOutletCurrentEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of outlet on this device."
::= { ipmSlaveOutletStatus 1}
ipmSlaveDeviceOutletCurrentEntry OBJECT-TYPE
SYNTAX IpmSlaveDeviceOutletCurrentEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The outlet number of device."
INDEX { slaveOutletCurrentIndex}
::= { ipmSlaveDeviceOutletCurrentTable 1 }
IpmSlaveDeviceOutletCurrentEntry ::=
SEQUENCE {
slaveOutletCurrentIndex
INTEGER,
slaveOutletCurrent01
INTEGER,
slaveOutletCurrent02
INTEGER,
slaveOutletCurrent03
INTEGER,
slaveOutletCurrent04
INTEGER,
slaveOutletCurrent05
INTEGER,
slaveOutletCurrent06
INTEGER,
slaveOutletCurrent07
INTEGER,
slaveOutletCurrent08
INTEGER,
slaveOutletCurrent09
INTEGER,
slaveOutletCurrent10
INTEGER,
slaveOutletCurrent11
INTEGER,
slaveOutletCurrent12
INTEGER
}
slaveOutletCurrentIndex OBJECT-TYPE
SYNTAX INTEGER (0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a access outlet configuration table."
::= { ipmSlaveDeviceOutletCurrentEntry 1 }
slaveOutletCurrent01 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The outlet A Current in 0.001 Amp."
::= { ipmSlaveDeviceOutletCurrentEntry 2 }
slaveOutletCurrent02 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The outlet B Current in 0.001 Amp."
::= { ipmSlaveDeviceOutletCurrentEntry 3 }
slaveOutletCurrent03 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The outlet C Current in 0.001 Amp."
::= { ipmSlaveDeviceOutletCurrentEntry 4 }
slaveOutletCurrent04 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The outlet D Current in 0.001 Amp."
::= { ipmSlaveDeviceOutletCurrentEntry 5 }
slaveOutletCurrent05 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The outlet E Current in 0.001 Amp."
::= { ipmSlaveDeviceOutletCurrentEntry 6 }
slaveOutletCurrent06 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The outlet F Current in 0.001 Amp."
::= { ipmSlaveDeviceOutletCurrentEntry 7 }
slaveOutletCurrent07 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The outlet G Current in 0.001 Amp."
::= { ipmSlaveDeviceOutletCurrentEntry 8 }
slaveOutletCurrent08 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The outlet H Current in 0.001 Amp."
::= { ipmSlaveDeviceOutletCurrentEntry 9 }
slaveOutletCurrent09 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The outlet I Current in 0.001 Amp."
::= { ipmSlaveDeviceOutletCurrentEntry 10 }
slaveOutletCurrent10 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The outlet J Current in 0.001 Amp."
::= { ipmSlaveDeviceOutletCurrentEntry 11 }
slaveOutletCurrent11 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The outlet K Current in 0.001 Amp."
::= { ipmSlaveDeviceOutletCurrentEntry 12 }
slaveOutletCurrent12 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The outlet L Current in 0.001 Amp."
::= { ipmSlaveDeviceOutletCurrentEntry 13 }
-- ==========================================
-- Outlet W/H
-- ==========================================
ipmSlaveDeviceOutletWattTable OBJECT-TYPE
SYNTAX SEQUENCE OF IpmSlaveDeviceOutletWattEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of outlet on this device."
::= { ipmSlaveOutletStatus 2}
ipmSlaveDeviceOutletWattEntry OBJECT-TYPE
SYNTAX IpmSlaveDeviceOutletWattEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The outlet number of device."
INDEX { slaveOutletWattIndex}
::= { ipmSlaveDeviceOutletWattTable 1 }
IpmSlaveDeviceOutletWattEntry ::=
SEQUENCE {
slaveOutletWattIndex
INTEGER,
slaveOutletWatt01
INTEGER,
slaveOutletWatt02
INTEGER,
slaveOutletWatt03
INTEGER,
slaveOutletWatt04
INTEGER,
slaveOutletWatt05
INTEGER,
slaveOutletWatt06
INTEGER,
slaveOutletWatt07
INTEGER,
slaveOutletWatt08
INTEGER,
slaveOutletWatt09
INTEGER,
slaveOutletWatt10
INTEGER,
slaveOutletWatt11
INTEGER,
slaveOutletWatt12
INTEGER
}
slaveOutletWattIndex OBJECT-TYPE
SYNTAX INTEGER (0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a access outlet configuration table."
::= { ipmSlaveDeviceOutletWattEntry 1 }
slaveOutletWatt01 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The outlet A Watt in 0.1 W/H."
::= { ipmSlaveDeviceOutletWattEntry 2 }
slaveOutletWatt02 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The outlet B Watt in 0.1 W/H."
::= { ipmSlaveDeviceOutletWattEntry 3 }
slaveOutletWatt03 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The outlet C Watt in 0.1 W/H."
::= { ipmSlaveDeviceOutletWattEntry 4 }
slaveOutletWatt04 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The outlet D Watt in 0.1 W/H."
::= { ipmSlaveDeviceOutletWattEntry 5 }
slaveOutletWatt05 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The outlet E Watt in 0.1 W/H."
::= { ipmSlaveDeviceOutletWattEntry 6 }
slaveOutletWatt06 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The outlet F Watt in 0.1 W/H."
::= { ipmSlaveDeviceOutletWattEntry 7 }
slaveOutletWatt07 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The outlet G Watt in 0.1 W/H."
::= { ipmSlaveDeviceOutletWattEntry 8 }
slaveOutletWatt08 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The outlet H Watt in 0.1 W/H."
::= { ipmSlaveDeviceOutletWattEntry 9 }
slaveOutletWatt09 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The outlet I Watt in 0.1 W/H."
::= { ipmSlaveDeviceOutletWattEntry 10 }
slaveOutletWatt10 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The outlet J Watt in 0.1 W/H."
::= { ipmSlaveDeviceOutletWattEntry 11 }
slaveOutletWatt11 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The outlet K Watt in 0.1 W/H."
::= { ipmSlaveDeviceOutletWattEntry 12 }
slaveOutletWatt12 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The outlet L Watt in 0.1 W/H."
::= { ipmSlaveDeviceOutletWattEntry 13 }
-- ==========================================
-- Outlet W/H
-- ==========================================
ipmSlaveDeviceOutletKwattTable OBJECT-TYPE
SYNTAX SEQUENCE OF IpmSlaveDeviceOutletKwattEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of outlet on this device."
::= { ipmSlaveOutletStatus 3}
ipmSlaveDeviceOutletKwattEntry OBJECT-TYPE
SYNTAX IpmSlaveDeviceOutletKwattEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The outlet number of device."
INDEX { slaveOutletKwattIndex}
::= { ipmSlaveDeviceOutletKwattTable 1 }
IpmSlaveDeviceOutletKwattEntry ::=
SEQUENCE {
slaveOutletKwattIndex
INTEGER,
slaveOutletKwatt01
INTEGER,
slaveOutletKwatt02
INTEGER,
slaveOutletKwatt03
INTEGER,
slaveOutletKwatt04
INTEGER,
slaveOutletKwatt05
INTEGER,
slaveOutletKwatt06
INTEGER,
slaveOutletKwatt07
INTEGER,
slaveOutletKwatt08
INTEGER,
slaveOutletKwatt09
INTEGER,
slaveOutletKwatt10
INTEGER,
slaveOutletKwatt11
INTEGER,
slaveOutletKwatt12
INTEGER
}
slaveOutletKwattIndex OBJECT-TYPE
SYNTAX INTEGER (0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a access outlet configuration table."
::= { ipmSlaveDeviceOutletKwattEntry 1 }
slaveOutletKwatt01 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The outlet A Kwatt in 0.001 KW/H."
::= { ipmSlaveDeviceOutletKwattEntry 2 }
slaveOutletKwatt02 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The outlet B Kwatt in 0.001 KW/H."
::= { ipmSlaveDeviceOutletKwattEntry 3 }
slaveOutletKwatt03 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The outlet C Kwatt in 0.001 KW/H."
::= { ipmSlaveDeviceOutletKwattEntry 4 }
slaveOutletKwatt04 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The outlet D Kwatt in 0.001 KW/H."
::= { ipmSlaveDeviceOutletKwattEntry 5 }
slaveOutletKwatt05 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The outlet E Kwatt in 0.001 KW/H."
::= { ipmSlaveDeviceOutletKwattEntry 6 }
slaveOutletKwatt06 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The outlet F Kwatt in 0.001 KW/H."
::= { ipmSlaveDeviceOutletKwattEntry 7 }
slaveOutletKwatt07 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The outlet G Kwatt in 0.001 KW/H."
::= { ipmSlaveDeviceOutletKwattEntry 8 }
slaveOutletKwatt08 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The outlet H Kwatt in 0.001 KW/H."
::= { ipmSlaveDeviceOutletKwattEntry 9 }
slaveOutletKwatt09 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The outlet I Kwatt in 0.001 KW/H."
::= { ipmSlaveDeviceOutletKwattEntry 10 }
slaveOutletKwatt10 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The outlet J Kwatt in 0.001 KW/H."
::= { ipmSlaveDeviceOutletKwattEntry 11 }
slaveOutletKwatt11 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The outlet K Kwatt in 0.001 KW/H."
::= { ipmSlaveDeviceOutletKwattEntry 12 }
slaveOutletKwatt12 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The outlet L Kwatt in 0.001 KW/H."
::= { ipmSlaveDeviceOutletKwattEntry 13 }
ipmSlaveOutletAction OBJECT IDENTIFIER ::= { ipmSlaveOutlet 3 }
-- ===========================================================================
--
-- ipmOutletStatus
--
-- Outlet Action Group
--
-- ===========================================================================
ipmSlaveDeviceOutletActionTable OBJECT-TYPE
SYNTAX SEQUENCE OF IpmSlaveDeviceOutletActionEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of outlet on this device."
::= { ipmSlaveOutletAction 1}
ipmSlaveDeviceOutletActionEntry OBJECT-TYPE
SYNTAX IpmSlaveDeviceOutletActionEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The outlet number of device."
INDEX { slaveOutletActionIndex}
::= { ipmSlaveDeviceOutletActionTable 1 }
IpmSlaveDeviceOutletActionEntry ::=
SEQUENCE {
slaveOutletActionIndex
INTEGER,
slaveOutletAction01
INTEGER,
slaveOutletAction02
INTEGER,
slaveOutletAction03
INTEGER,
slaveOutletAction04
INTEGER,
slaveOutletAction05
INTEGER,
slaveOutletAction06
INTEGER,
slaveOutletAction07
INTEGER,
slaveOutletAction08
INTEGER,
slaveOutletAction09
INTEGER,
slaveOutletAction10
INTEGER,
slaveOutletAction11
INTEGER,
slaveOutletAction12
INTEGER
}
slaveOutletActionIndex OBJECT-TYPE
SYNTAX INTEGER (0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a access outlet configuration table."
::= { ipmSlaveDeviceOutletActionEntry 1 }
slaveOutletAction01 OBJECT-TYPE
SYNTAX INTEGER {
none(1),
cancelAction(2),
onImmediately(3),
offImmediately(4),
cycleImmediately(5),
onByActionTimer(6),
offByActionTimer(7),
cycleByActionTimer(8),
onThenOffByActionTimers(9),
offThenOnByActionTimers(10)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Set to control the outlet perform action as requested."
::= { ipmSlaveDeviceOutletActionEntry 2 }
slaveOutletAction02 OBJECT-TYPE
SYNTAX INTEGER {
none(1),
cancelAction(2),
onImmediately(3),
offImmediately(4),
cycleImmediately(5),
onByActionTimer(6),
offByActionTimer(7),
cycleByActionTimer(8),
onThenOffByActionTimers(9),
offThenOnByActionTimers(10)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Set to control the outlet perform action as requested."
::= { ipmSlaveDeviceOutletActionEntry 3 }
slaveOutletAction03 OBJECT-TYPE
SYNTAX INTEGER {
none(1),
cancelAction(2),
onImmediately(3),
offImmediately(4),
cycleImmediately(5),
onByActionTimer(6),
offByActionTimer(7),
cycleByActionTimer(8),
onThenOffByActionTimers(9),
offThenOnByActionTimers(10)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Set to control the outlet perform action as requested."
::= { ipmSlaveDeviceOutletActionEntry 4 }
slaveOutletAction04 OBJECT-TYPE
SYNTAX INTEGER {
none(1),
cancelAction(2),
onImmediately(3),
offImmediately(4),
cycleImmediately(5),
onByActionTimer(6),
offByActionTimer(7),
cycleByActionTimer(8),
onThenOffByActionTimers(9),
offThenOnByActionTimers(10)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Set to control the outlet perform action as requested."
::= { ipmSlaveDeviceOutletActionEntry 5 }
slaveOutletAction05 OBJECT-TYPE
SYNTAX INTEGER {
none(1),
cancelAction(2),
onImmediately(3),
offImmediately(4),
cycleImmediately(5),
onByActionTimer(6),
offByActionTimer(7),
cycleByActionTimer(8),
onThenOffByActionTimers(9),
offThenOnByActionTimers(10)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Set to control the outlet perform action as requested."
::= { ipmSlaveDeviceOutletActionEntry 6 }
slaveOutletAction06 OBJECT-TYPE
SYNTAX INTEGER {
none(1),
cancelAction(2),
onImmediately(3),
offImmediately(4),
cycleImmediately(5),
onByActionTimer(6),
offByActionTimer(7),
cycleByActionTimer(8),
onThenOffByActionTimers(9),
offThenOnByActionTimers(10)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Set to control the outlet perform action as requested."
::= { ipmSlaveDeviceOutletActionEntry 7 }
slaveOutletAction07 OBJECT-TYPE
SYNTAX INTEGER {
none(1),
cancelAction(2),
onImmediately(3),
offImmediately(4),
cycleImmediately(5),
onByActionTimer(6),
offByActionTimer(7),
cycleByActionTimer(8),
onThenOffByActionTimers(9),
offThenOnByActionTimers(10)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Set to control the outlet perform action as requested."
::= { ipmSlaveDeviceOutletActionEntry 8 }
slaveOutletAction08 OBJECT-TYPE
SYNTAX INTEGER {
none(1),
cancelAction(2),
onImmediately(3),
offImmediately(4),
cycleImmediately(5),
onByActionTimer(6),
offByActionTimer(7),
cycleByActionTimer(8),
onThenOffByActionTimers(9),
offThenOnByActionTimers(10)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Set to control the outlet perform action as requested."
::= { ipmSlaveDeviceOutletActionEntry 9 }
slaveOutletAction09 OBJECT-TYPE
SYNTAX INTEGER {
none(1),
cancelAction(2),
onImmediately(3),
offImmediately(4),
cycleImmediately(5),
onByActionTimer(6),
offByActionTimer(7),
cycleByActionTimer(8),
onThenOffByActionTimers(9),
offThenOnByActionTimers(10)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Set to control the outlet perform action as requested."
::= { ipmSlaveDeviceOutletActionEntry 10 }
slaveOutletAction10 OBJECT-TYPE
SYNTAX INTEGER {
none(1),
cancelAction(2),
onImmediately(3),
offImmediately(4),
cycleImmediately(5),
onByActionTimer(6),
offByActionTimer(7),
cycleByActionTimer(8),
onThenOffByActionTimers(9),
offThenOnByActionTimers(10)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Set to control the outlet perform action as requested."
::= { ipmSlaveDeviceOutletActionEntry 11 }
slaveOutletAction11 OBJECT-TYPE
SYNTAX INTEGER {
none(1),
cancelAction(2),
onImmediately(3),
offImmediately(4),
cycleImmediately(5),
onByActionTimer(6),
offByActionTimer(7),
cycleByActionTimer(8),
onThenOffByActionTimers(9),
offThenOnByActionTimers(10)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Set to control the outlet perform action as requested."
::= { ipmSlaveDeviceOutletActionEntry 12 }
slaveOutletAction12 OBJECT-TYPE
SYNTAX INTEGER {
none(1),
cancelAction(2),
onImmediately(3),
offImmediately(4),
cycleImmediately(5),
onByActionTimer(6),
offByActionTimer(7),
cycleByActionTimer(8),
onThenOffByActionTimers(9),
offThenOnByActionTimers(10)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Set to control the outlet perform action as requested."
::= { ipmSlaveDeviceOutletActionEntry 13 }
ipmEnvEmd OBJECT IDENTIFIER ::= { ipmEnv 1 }
-- ===========================================================================
--
-- ipmEnvEmd
--
-- Environmental Monitor Device Group
--
-- ===========================================================================
ipmEnvEmdStatus OBJECT IDENTIFIER ::= { ipmEnvEmd 1 }
-- ===========================================================================
--
-- ipmEnvEmd
--
-- Environmental Monitor Device Status Group
--
-- ===========================================================================
ipmEnvEmdStatusEmdType OBJECT-TYPE
SYNTAX INTEGER {
unknown(1),
disabled(2),
eMD-HT(3),
eMD-T(4)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"EMD Type."
::= { ipmEnvEmdStatus 1 }
ipmEnvEmdStatusTemperature OBJECT-TYPE
SYNTAX INTEGER (1..10000) --
ACCESS read-only
STATUS mandatory
DESCRIPTION
"EMD Temperature in 0.1 degree C."
::= { ipmEnvEmdStatus 2 }
ipmEnvEmdStatusHumidity OBJECT-TYPE
SYNTAX INTEGER (1..10000) --
ACCESS read-only
STATUS mandatory
DESCRIPTION
"EMD Humidity in 0.1%."
::= { ipmEnvEmdStatus 3 }
ipmEnvEmdStatusAlarm1 OBJECT-TYPE
SYNTAX INTEGER {
unknown(1),
disabled(2),
alarm(3),
normal(4)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"EMD Alarm-1 state."
::= { ipmEnvEmdStatus 4 }
ipmEnvEmdStatusAlarm2 OBJECT-TYPE
SYNTAX INTEGER {
unknown(1),
disabled(2),
alarm(3),
normal(4)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"EMD Alarm-2 state."
::= { ipmEnvEmdStatus 5 }
ipmEnvEmdConfig OBJECT IDENTIFIER ::= { ipmEnvEmd 2 }
-- ===========================================================================
--
-- ipmEnvEmd
--
-- Environmental Monitor Device Configuration Group
--
-- ===========================================================================
ipmEnvEmdConfigEmdPresence OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
autoDetect(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Configure the EMD presence by auto-detect or not exist (disabled)."
::= { ipmEnvEmdConfig 1 }
ipmEnvEmdConfigEmdName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The name of Emd."
::= { ipmEnvEmdConfig 2 }
ipmEnvEmdConfigTemp OBJECT IDENTIFIER ::= { ipmEnvEmdConfig 3 }
-- ===========================================================================
--
-- ipmEnvEmdConfigTemp
--
-- Environmental Monitor Device Temperature Configuration Group
--
-- ===========================================================================
ipmEnvEmdConfigTempName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The name of EMD Temperature sensor."
::= { ipmEnvEmdConfigTemp 1 }
ipmEnvEmdConfigTempHighSetPoint OBJECT-TYPE
SYNTAX INTEGER (5..65) --
ACCESS read-write
STATUS mandatory
DESCRIPTION
"EMD Temperature set point high, alarm will active when temperature
over this value, in degree C."
::= { ipmEnvEmdConfigTemp 2 }
ipmEnvEmdConfigTempHighStatus OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enabled/disabled the high setpoint be applied or not"
::= { ipmEnvEmdConfigTemp 3 }
ipmEnvEmdConfigTempLowSetPoint OBJECT-TYPE
SYNTAX INTEGER (5..65) --
ACCESS read-write
STATUS mandatory
DESCRIPTION
"EMD Temperature set point high, alarm will active when temperature
under this value, in degree C."
::= { ipmEnvEmdConfigTemp 4 }
ipmEnvEmdConfigTempLowStatus OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enabled/disabled the low setpoint be applied or not"
::= { ipmEnvEmdConfigTemp 5 }
ipmEnvEmdConfigTempOffset OBJECT-TYPE
SYNTAX INTEGER {
t0p0(1),
t0p5(2),
t1p0(3),
t1p5(4),
t2p0(5),
t2p5(6),
t3p0(7),
t-0p5(8),
t-1p0(9),
t-1p5(10),
t-2p0(11),
t-2p5(12),
t-3p0(13)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Offset of temperature in degree C to adjust EMD temperature measurement."
::= { ipmEnvEmdConfigTemp 6 }
ipmEnvEmdConfigHumi OBJECT IDENTIFIER ::= { ipmEnvEmdConfig 4 }
-- ===========================================================================
--
-- ipmEnvEmdConfigHumi
--
-- Environmental Monitor Device Humidity Configuration Group
--
-- ===========================================================================
ipmEnvEmdConfigHumiName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The name of EMD Humidity."
::= { ipmEnvEmdConfigHumi 1 }
ipmEnvEmdConfigHumiHighSetPoint OBJECT-TYPE
SYNTAX INTEGER (5..95) --
ACCESS read-write
STATUS mandatory
DESCRIPTION
"EMD humidity set point high, alarm will active when humidity
over this value, in %."
::= { ipmEnvEmdConfigHumi 2 }
ipmEnvEmdConfigHumiHighStatus OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enabled/disabled the high setpoint be applied or not"
::= { ipmEnvEmdConfigHumi 3 }
ipmEnvEmdConfigHumiLowSetPoint OBJECT-TYPE
SYNTAX INTEGER (5..95) --
ACCESS read-write
STATUS mandatory
DESCRIPTION
"EMD humidity set point low, alarm will active when humidity
under this value, in %."
::= { ipmEnvEmdConfigHumi 4 }
ipmEnvEmdConfigHumiLowStatus OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enabled/disabled the high setpoint be applied or not"
::= { ipmEnvEmdConfigHumi 5 }
ipmEnvEmdConfigHumiOffset OBJECT-TYPE
SYNTAX INTEGER {
h0p0(1),
h1p0(2),
h2p0(3),
h3p0(4),
h4p0(5),
h5p0(6),
h6p0(7),
h-1p0(8),
h-2p0(9),
h-3p0(10),
h-4p0(11),
h-5p0(12),
h-6p0(13)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Emd Hum Offset;"
::= { ipmEnvEmdConfigHumi 6 }
ipmEnvEmdConfigAlarm1 OBJECT IDENTIFIER ::= { ipmEnvEmdConfig 5 }
-- ===========================================================================
--
-- ipmEnvEmdConfigAlarm1
--
-- Environmental Monitor Device Alarm-1 Configuration Group
--
-- ===========================================================================
ipmEnvEmdConfigAlarm1Name OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The name of EMD Alarm-1."
::= { ipmEnvEmdConfigAlarm1 1 }
ipmEnvEmdConfigAlarm1Type OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
normalOpen(2),
normalClose(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"EMD Alarm-1 type"
::= { ipmEnvEmdConfigAlarm1 2 }
ipmEnvEmdConfigAlarm2 OBJECT IDENTIFIER ::= { ipmEnvEmdConfig 6 }
-- ===========================================================================
--
-- ipmEnvEmdConfigAlarm2
--
-- Environmental Monitor Device Alarm-2 Configuration Group
--
-- ===========================================================================
ipmEnvEmdConfigAlarm2Name OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The name of EMD Alarm-2."
::= { ipmEnvEmdConfigAlarm2 1 }
ipmEnvEmdConfigAlarm2Type OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
normalOpen(2),
normalClose(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"EMD Alarm-2 type"
::= { ipmEnvEmdConfigAlarm2 2 }
-- ===========================================================================
-- ipmTraps
--
-- iPoManII Trap group
-- ===========================================================================
-- This section defines the well-known notifications sent by
-- iPoManII agents.
ipmInletVoltageTooHigh TRAP-TYPE
ENTERPRISE ipmTraps
VARIABLES {
inletConfigIndex,
inletStatusVoltage,
inletConfigVoltageHigh,
inletConfigDesc
}
DESCRIPTION
"CRITICAL: The input voltage over high threshold."
::= 1
ipmInletVoltageNotTooHigh TRAP-TYPE
ENTERPRISE ipmTraps
VARIABLES {
inletConfigIndex,
inletStatusVoltage,
inletConfigVoltageHigh,
inletConfigDesc
}
DESCRIPTION
"WARNING: The input voltage return from over high threshold."
::= 2
ipmInletVoltageTooLow TRAP-TYPE
ENTERPRISE ipmTraps
VARIABLES {
inletConfigIndex,
inletStatusVoltage,
inletConfigVoltageLow,
inletConfigDesc
}
DESCRIPTION
"CRITICAL: The input voltage under low threshold."
::= 3
ipmInletVoltageNotTooLow TRAP-TYPE
ENTERPRISE ipmTraps
VARIABLES {
inletConfigIndex,
inletStatusVoltage,
inletConfigVoltageLow,
inletConfigDesc
}
DESCRIPTION
"WARNING: The input voltage return from under low threshold."
::= 4
ipmInletCurrentTooHigh TRAP-TYPE
ENTERPRISE ipmTraps
VARIABLES {
inletConfigIndex,
inletStatusCurrent,
inletConfigCurrentHigh,
inletConfigDesc
}
DESCRIPTION
"CRITICAL: The input current over high threshold."
::= 5
ipmInletCurrentNotTooHigh TRAP-TYPE
ENTERPRISE ipmTraps
VARIABLES {
inletConfigIndex,
inletStatusCurrent,
inletConfigCurrentHigh,
inletConfigDesc
}
DESCRIPTION
"WARNING: The input current return from over high threshold."
::= 6
ipmInletFrequencyTooHigh TRAP-TYPE
ENTERPRISE ipmTraps
VARIABLES {
inletConfigIndex,
inletStatusFrequency,
inletConfigFrequencyHigh,
inletConfigDesc
}
DESCRIPTION
"CRITICAL: The input frequency over high threshold."
::= 7
ipmInletFrequencyNotTooHigh TRAP-TYPE
ENTERPRISE ipmTraps
VARIABLES {
inletConfigIndex,
inletStatusFrequency,
inletConfigFrequencyHigh,
inletConfigDesc
}
DESCRIPTION
"WARNING: The input frequency return from over high threshold."
::= 8
ipmInletFrequencyTooLow TRAP-TYPE
ENTERPRISE ipmTraps
VARIABLES {
inletConfigIndex,
inletStatusFrequency,
inletConfigFrequencyLow,
inletConfigDesc
}
DESCRIPTION
"CRITICAL: The input frequency under low threshold."
::= 9
ipmInletFrequencyNotTooLow TRAP-TYPE
ENTERPRISE ipmTraps
VARIABLES {
inletConfigIndex,
inletStatusFrequency,
inletConfigFrequencyLow,
inletConfigDesc
}
DESCRIPTION
"WARNING: The input frequency return from under low threshold."
::= 10
ipmOutletCurrentTooHigh TRAP-TYPE
ENTERPRISE ipmTraps
VARIABLES {
outletConfigIndex,
outletStatusCurrent,
outletConfigCurrentHigh,
outletConfigDesc
}
DESCRIPTION
"CRITICAL: The output current of outlet over high threshold."
::= 11
ipmOutletCurrentNotTooHigh TRAP-TYPE
ENTERPRISE ipmTraps
VARIABLES {
outletConfigIndex,
outletStatusCurrent,
outletConfigCurrentHigh,
outletConfigDesc
}
DESCRIPTION
"WARNING: The output current of outlet return from over high threshold."
::= 12
ipmOutletStateChanged TRAP-TYPE
ENTERPRISE ipmTraps
VARIABLES {
outletConfigIndex,
outletStatusStatus,
outletConfigDesc
}
DESCRIPTION
"INFORMATION: The outlet state had changed from on to off, or from off to on."
::= 13
ipmEmdTemperatureNotHigh TRAP-TYPE
ENTERPRISE ipmTraps
VARIABLES {
ipmEnvEmdStatusTemperature,
ipmEnvEmdConfigTempHighSetPoint,
ipmEnvEmdConfigTempName
}
DESCRIPTION
"INFORMATION: emd Temperature Not High."
::= 14
ipmEmdTemperatureTooHigh TRAP-TYPE
ENTERPRISE ipmTraps
VARIABLES {
ipmEnvEmdStatusTemperature,
ipmEnvEmdConfigTempHighSetPoint,
ipmEnvEmdConfigTempName
}
DESCRIPTION
"WARNING: emd Temperature Too High."
::= 15
ipmEmdTemperatureNotLow TRAP-TYPE
ENTERPRISE ipmTraps
VARIABLES {
ipmEnvEmdStatusTemperature,
ipmEnvEmdConfigTempLowSetPoint,
ipmEnvEmdConfigTempName
}
DESCRIPTION
"INFORMATION: emd Temperature Not Low."
::= 16
ipmEmdTemperatureTooLow TRAP-TYPE
ENTERPRISE ipmTraps
VARIABLES {
ipmEnvEmdStatusTemperature,
ipmEnvEmdConfigTempLowSetPoint,
ipmEnvEmdConfigTempName
}
DESCRIPTION
"WARNING: emd Temperature Too Low."
::= 17
ipmEmdHumidityNotHigh TRAP-TYPE
ENTERPRISE ipmTraps
VARIABLES {
ipmEnvEmdStatusHumidity,
ipmEnvEmdConfigHumiHighSetPoint,
ipmEnvEmdConfigHumiName
}
DESCRIPTION
"INFORMATION: emd Humidity Not High."
::= 18
ipmEmdHumidityTooHigh TRAP-TYPE
ENTERPRISE ipmTraps
VARIABLES {
ipmEnvEmdStatusHumidity,
ipmEnvEmdConfigHumiHighSetPoint,
ipmEnvEmdConfigHumiName
}
DESCRIPTION
"WARNING: emd Humidity Too High."
::= 19
ipmEmdHumidityNotLow TRAP-TYPE
ENTERPRISE ipmTraps
VARIABLES {
ipmEnvEmdStatusHumidity,
ipmEnvEmdConfigHumiLowSetPoint,
ipmEnvEmdConfigHumiName
}
DESCRIPTION
"INFORMATION: emd Humidity Not Low."
::= 20
ipmEmdHumidityTooLow TRAP-TYPE
ENTERPRISE ipmTraps
VARIABLES {
ipmEnvEmdStatusHumidity,
ipmEnvEmdConfigHumiLowSetPoint,
ipmEnvEmdConfigHumiName
}
DESCRIPTION
"WARNING: emd Humidity Too Low."
::= 21
ipmEmdAlarm1Normal TRAP-TYPE
ENTERPRISE ipmTraps
VARIABLES {
ipmEnvEmdConfigAlarm1Type,
ipmEnvEmdConfigAlarm1Name
}
DESCRIPTION
"INFORMATION: emd Alarm1 Normal."
::= 22
ipmEmdAlarm1Active TRAP-TYPE
ENTERPRISE ipmTraps
VARIABLES {
ipmEnvEmdConfigAlarm1Type,
ipmEnvEmdConfigAlarm1Name
}
DESCRIPTION
"WARNING: emd Alarm1 Active."
::= 23
ipmEmdAlarm2Normal TRAP-TYPE
ENTERPRISE ipmTraps
VARIABLES {
ipmEnvEmdConfigAlarm2Type,
ipmEnvEmdConfigAlarm2Name
}
DESCRIPTION
"INFORMATION: emd Alarm2 Normal."
::= 24
ipmEmdAlarm2Active TRAP-TYPE
ENTERPRISE ipmTraps
VARIABLES {
ipmEnvEmdConfigAlarm2Type,
ipmEnvEmdConfigAlarm2Name
}
DESCRIPTION
"WARNING: emd Alarm2 Active."
::= 25
ipmSlave01Inlet01OverHigh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave01 input01 voltage over high threshold."
::= 26
ipmSlave01Inlet01NotOverHigh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave01 input01 voltage Not over high threshold."
::= 27
ipmSlave01Inlet02OverHigh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave01 input02 voltage over high threshold."
::= 28
ipmSlave01Inlet02NotOverHigh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave01 input02 voltage Not over high threshold."
::= 29
ipmSlave01Inlet01UnderLow TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave01 input01 voltage under low threshold."
::= 30
ipmSlave01Inlet01NotUnderLow TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave01 input01 voltage Not under low threshold."
::= 31
ipmSlave01Inlet02UnderLow TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave01 input02 voltage under low threshold."
::= 32
ipmSlave01Inlet02NotUnderLow TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave01 input02 voltage Not under low threshold."
::= 33
ipmSlave01Inlet01CurrentOverTh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave01 input01 current over high threshold."
::= 34
ipmSlave01Inlet01NotCurrentOverTh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave01 input01 current not over high threshold."
::= 35
ipmSlave01Inlet02CurrentOverTh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave01 input02 current over high threshold."
::= 36
ipmSlave01Inlet02NotCurrentOverTh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave01 input02 current not over high threshold."
::= 37
ipmSlave01EmdTemperatureNotHigh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"INFORMATION: The Slave01 emd Temperature Not High."
::= 38
ipmSlave01EmdTemperatureTooHigh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"WARNING: The Slave01 emd Temperature Too High."
::= 39
ipmSlave01EmdTemperatureNotLow TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"INFORMATION: The Slave01 emd Temperature Not Low."
::= 40
ipmSlave01EmdTemperatureTooLow TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"WARNING: The Slave01 emd Temperature Too Low."
::= 41
ipmSlave01EmdHumidityNotHigh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"INFORMATION: The Slave01 emd Humidity Not High."
::= 42
ipmSlave01EmdHumidityTooHigh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"WARNING: The Slave01 emd Humidity Too High."
::= 43
ipmSlave01EmdHumidityNotLow TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"INFORMATION: The Slave01 emd Humidity Not Low."
::= 44
ipmSlave01EmdHumidityTooLow TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"WARNING: The Slave01 emd Humidity Too Low."
::= 45
ipmSlave01EmdAlarm1Normal TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"INFORMATION: The Slave01 emd Alarm1 Normal."
::= 46
ipmSlave01EmdAlarm1Active TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"WARNING: The Slave01 emd Alarm1 Active."
::= 47
ipmSlave01EmdAlarm2Normal TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"INFORMATION: The Slave01 emd Alarm2 Normal."
::= 48
ipmSlave01EmdAlarm2Active TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"WARNING: The Slave01 emd Alarm2 Active."
::= 49
ipmSlave01OutletCurrentOverTh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"WARNING: The Slave01 Outlet Current over threshold."
::= 50
ipmSlave02Inlet01OverHigh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave02 input01 voltage over high threshold."
::= 51
ipmSlave02Inlet01NotOverHigh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave02 input01 voltage Not over high threshold."
::= 52
ipmSlave02Inlet02OverHigh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave02 input02 voltage over high threshold."
::= 53
ipmSlave02Inlet02NotOverHigh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave02 input02 voltage Not over high threshold."
::= 54
ipmSlave02Inlet01UnderLow TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave02 input01 voltage under low threshold."
::= 55
ipmSlave02Inlet01NotUnderLow TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave02 input01 voltage Not under low threshold."
::= 56
ipmSlave02Inlet02UnderLow TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave02 input02 voltage under low threshold."
::= 57
ipmSlave02Inlet02NotUnderLow TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave02 input02 voltage Not under low threshold."
::= 58
ipmSlave02Inlet01CurrentOverTh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave02 input01 current over high threshold."
::= 59
ipmSlave02Inlet01NotCurrentOverTh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave02 input01 current not over high threshold."
::= 60
ipmSlave02Inlet02CurrentOverTh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave02 input02 current over high threshold."
::= 61
ipmSlave02Inlet02NotCurrentOverTh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave02 input02 current not over high threshold."
::= 62
ipmSlave02EmdTemperatureNotHigh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"INFORMATION: The Slave02 emd Temperature Not High."
::= 63
ipmSlave02EmdTemperatureTooHigh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"WARNING: The Slave02 emd Temperature Too High."
::= 64
ipmSlave02EmdTemperatureNotLow TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"INFORMATION: The Slave02 emd Temperature Not Low."
::= 65
ipmSlave02EmdTemperatureTooLow TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"WARNING: The Slave02 emd Temperature Too Low."
::= 66
ipmSlave02EmdHumidityNotHigh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"INFORMATION: The Slave02 emd Humidity Not High."
::= 67
ipmSlave02EmdHumidityTooHigh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"WARNING: The Slave02 emd Humidity Too High."
::= 68
ipmSlave02EmdHumidityNotLow TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"INFORMATION: The Slave02 emd Humidity Not Low."
::= 69
ipmSlave02EmdHumidityTooLow TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"WARNING: The Slave02 emd Humidity Too Low."
::= 70
ipmSlave02EmdAlarm1Normal TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"INFORMATION: The Slave02 emd Alarm1 Normal."
::= 71
ipmSlave02EmdAlarm1Active TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"WARNING: The Slave02 emd Alarm1 Active."
::= 72
ipmSlave02EmdAlarm2Normal TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"INFORMATION: The Slave02 emd Alarm2 Normal."
::= 73
ipmSlave02EmdAlarm2Active TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"WARNING: The Slave02 emd Alarm2 Active."
::= 74
ipmSlave02OutletCurrentOverTh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"WARNING: The Slave02 Outlet Current over threshold."
::= 75
ipmSlave03Inlet01OverHigh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave03 input01 voltage over high threshold."
::= 76
ipmSlave03Inlet01NotOverHigh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave03 input01 voltage Not over high threshold."
::= 77
ipmSlave03Inlet02OverHigh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave03 input02 voltage over high threshold."
::= 78
ipmSlave03Inlet02NotOverHigh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave03 input02 voltage Not over high threshold."
::= 79
ipmSlave03Inlet01UnderLow TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave03 input01 voltage under low threshold."
::= 80
ipmSlave03Inlet01NotUnderLow TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave03 input01 voltage Not under low threshold."
::= 81
ipmSlave03Inlet02UnderLow TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave03 input02 voltage under low threshold."
::= 82
ipmSlave03Inlet02NotUnderLow TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave03 input02 voltage Not under low threshold."
::= 83
ipmSlave03Inlet01CurrentOverTh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave03 input01 current over high threshold."
::= 84
ipmSlave03Inlet01NotCurrentOverTh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave03 input01 current not over high threshold."
::= 85
ipmSlave03Inlet02CurrentOverTh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave03 input02 current over high threshold."
::= 86
ipmSlave03Inlet02NotCurrentOverTh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave03 input02 current not over high threshold."
::= 87
ipmSlave03EmdTemperatureNotHigh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"INFORMATION: The Slave03 emd Temperature Not High."
::= 88
ipmSlave03EmdTemperatureTooHigh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"WARNING: The Slave03 emd Temperature Too High."
::= 89
ipmSlave03EmdTemperatureNotLow TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"INFORMATION: The Slave03 emd Temperature Not Low."
::= 90
ipmSlave03EmdTemperatureTooLow TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"WARNING: The Slave03 emd Temperature Too Low."
::= 91
ipmSlave03EmdHumidityNotHigh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"INFORMATION: The Slave03 emd Humidity Not High."
::= 92
ipmSlave03EmdHumidityTooHigh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"WARNING: The Slave03 emd Humidity Too High."
::= 93
ipmSlave03EmdHumidityNotLow TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"INFORMATION: The Slave03 emd Humidity Not Low."
::= 94
ipmSlave03EmdHumidityTooLow TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"WARNING: The Slave03 emd Humidity Too Low."
::= 95
ipmSlave03EmdAlarm1Normal TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"INFORMATION: The Slave03 emd Alarm1 Normal."
::= 96
ipmSlave03EmdAlarm1Active TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"WARNING: The Slave03 emd Alarm1 Active."
::= 97
ipmSlave03EmdAlarm2Normal TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"INFORMATION: The Slave03 emd Alarm2 Normal."
::= 98
ipmSlave03EmdAlarm2Active TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"WARNING: The Slave03 emd Alarm2 Active."
::= 99
ipmSlave03OutletCurrentOverTh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"WARNING: The Slave03 Outlet Current over threshold."
::= 100
ipmSlave04Inlet01OverHigh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave04 input01 voltage over high threshold."
::= 101
ipmSlave04Inlet01NotOverHigh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave04 input01 voltage Not over high threshold."
::= 102
ipmSlave04Inlet02OverHigh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave04 input02 voltage over high threshold."
::= 103
ipmSlave04Inlet02NotOverHigh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave04 input02 voltage Not over high threshold."
::= 104
ipmSlave04Inlet01UnderLow TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave04 input01 voltage under low threshold."
::= 105
ipmSlave04Inlet01NotUnderLow TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave04 input01 voltage Not under low threshold."
::= 106
ipmSlave04Inlet02UnderLow TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave04 input02 voltage under low threshold."
::= 107
ipmSlave04Inlet02NotUnderLow TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave04 input02 voltage Not under low threshold."
::= 108
ipmSlave04Inlet01CurrentOverTh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave04 input01 current over high threshold."
::= 109
ipmSlave04Inlet01NotCurrentOverTh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave04 input01 current not over high threshold."
::= 110
ipmSlave04Inlet02CurrentOverTh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave04 input02 current over high threshold."
::= 111
ipmSlave04Inlet02NotCurrentOverTh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave04 input02 current not over high threshold."
::= 112
ipmSlave04EmdTemperatureNotHigh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"INFORMATION: The Slave04 emd Temperature Not High."
::= 113
ipmSlave04EmdTemperatureTooHigh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"WARNING: The Slave04 emd Temperature Too High."
::= 114
ipmSlave04EmdTemperatureNotLow TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"INFORMATION: The Slave04 emd Temperature Not Low."
::= 115
ipmSlave04EmdTemperatureTooLow TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"WARNING: The Slave04 emd Temperature Too Low."
::= 116
ipmSlave04EmdHumidityNotHigh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"INFORMATION: The Slave04 emd Humidity Not High."
::= 117
ipmSlave04EmdHumidityTooHigh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"WARNING: The Slave04 emd Humidity Too High."
::= 118
ipmSlave04EmdHumidityNotLow TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"INFORMATION: The Slave04 emd Humidity Not Low."
::= 119
ipmSlave04EmdHumidityTooLow TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"WARNING: The Slave04 emd Humidity Too Low."
::= 120
ipmSlave04EmdAlarm1Normal TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"INFORMATION: The Slave04 emd Alarm1 Normal."
::= 121
ipmSlave04EmdAlarm1Active TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"WARNING: The Slave04 emd Alarm1 Active."
::= 122
ipmSlave04EmdAlarm2Normal TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"INFORMATION: The Slave04 emd Alarm2 Normal."
::= 123
ipmSlave04EmdAlarm2Active TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"WARNING: The Slave04 emd Alarm2 Active."
::= 124
ipmSlave04OutletCurrentOverTh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"WARNING: The Slave04 Outlet Current over threshold."
::= 125
ipmSlave05Inlet01OverHigh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave05 input01 voltage over high threshold."
::= 126
ipmSlave05Inlet01NotOverHigh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave05 input01 voltage Not over high threshold."
::= 127
ipmSlave05Inlet02OverHigh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave05 input02 voltage over high threshold."
::= 128
ipmSlave05Inlet02NotOverHigh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave05 input02 voltage Not over high threshold."
::= 129
ipmSlave05Inlet01UnderLow TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave05 input01 voltage under low threshold."
::= 130
ipmSlave05Inlet01NotUnderLow TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave05 input01 voltage Not under low threshold."
::= 131
ipmSlave05Inlet02UnderLow TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave05 input02 voltage under low threshold."
::= 132
ipmSlave05Inlet02NotUnderLow TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave05 input02 voltage Not under low threshold."
::= 133
ipmSlave05Inlet01CurrentOverTh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave05 input01 current over high threshold."
::= 134
ipmSlave05Inlet01NotCurrentOverTh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave05 input01 current not over high threshold."
::= 135
ipmSlave05Inlet02CurrentOverTh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave05 input02 current over high threshold."
::= 136
ipmSlave05Inlet02NotCurrentOverTh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"CRITICAL: The Slave05 input02 current not over high threshold."
::= 137
ipmSlave05EmdTemperatureNotHigh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"INFORMATION: The Slave05 emd Temperature Not High."
::= 138
ipmSlave05EmdTemperatureTooHigh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"WARNING: The Slave05 emd Temperature Too High."
::= 139
ipmSlave05EmdTemperatureNotLow TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"INFORMATION: The Slave05 emd Temperature Not Low."
::= 140
ipmSlave05EmdTemperatureTooLow TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"WARNING: The Slave05 emd Temperature Too Low."
::= 141
ipmSlave05EmdHumidityNotHigh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"INFORMATION: The Slave05 emd Humidity Not High."
::= 142
ipmSlave05EmdHumidityTooHigh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"WARNING: The Slave05 emd Humidity Too High."
::= 143
ipmSlave05EmdHumidityNotLow TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"INFORMATION: The Slave05 emd Humidity Not Low."
::= 144
ipmSlave05EmdHumidityTooLow TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"WARNING: The Slave05 emd Humidity Too Low."
::= 145
ipmSlave05EmdAlarm1Normal TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"INFORMATION: The Slave05 emd Alarm1 Normal."
::= 146
ipmSlave05EmdAlarm1Active TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"WARNING: The Slave05 emd Alarm1 Active."
::= 147
ipmSlave05EmdAlarm2Normal TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"INFORMATION: The Slave05 emd Alarm2 Normal."
::= 148
ipmSlave05EmdAlarm2Active TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"WARNING: The Slave05 emd Alarm2 Active."
::= 149
ipmSlave05OutletCurrentOverTh TRAP-TYPE
ENTERPRISE ipmTraps
DESCRIPTION
"WARNING: The Slave05 Outlet Current over threshold."
::= 150
END