3258 lines
111 KiB
Plaintext
3258 lines
111 KiB
Plaintext
LIEBERT-GP-ENVIRONMENTAL-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
MODULE-IDENTITY,
|
|
OBJECT-IDENTITY,
|
|
OBJECT-TYPE,
|
|
Unsigned32,
|
|
Integer32
|
|
FROM SNMPv2-SMI
|
|
DisplayString
|
|
FROM SNMPv2-TC
|
|
lgpEnvironmental,
|
|
liebertEnvironmentalModuleReg
|
|
FROM LIEBERT-GP-REGISTRATION-MIB
|
|
;
|
|
|
|
-- =============================================================================
|
|
-- Module Identification and Registration
|
|
-- =============================================================================
|
|
|
|
liebertGlobalProductsEnvironmentalModule MODULE-IDENTITY
|
|
LAST-UPDATED "201507210000Z"
|
|
ORGANIZATION "Liebert Corporation"
|
|
CONTACT-INFO
|
|
"Contact: Technical Support
|
|
|
|
Postal:
|
|
Liebert Corporation
|
|
1050 Dearborn Drive
|
|
P.O. Box 29186
|
|
Columbus OH, 43229
|
|
US
|
|
|
|
Tel: +1 (800) 222-5877
|
|
|
|
E-mail: liebert.monitoring@vertivco.com
|
|
Web: www.vertivco.com
|
|
|
|
Author: Gregory M. Hoge"
|
|
|
|
DESCRIPTION
|
|
"The MIB module used to register Liebert SNMP OIDs.
|
|
|
|
Copyright 2000-2015 Liebert Corporation. All rights reserved.
|
|
Reproduction of this document is authorized on the condition
|
|
that the forgoing copyright notice is included.
|
|
|
|
This Specification is supplied 'AS IS' and Liebert Corporation
|
|
makes no warranty, either express or implied, as to the use,
|
|
operation, condition, or performance of the Specification."
|
|
|
|
REVISION "200811170000Z"
|
|
DESCRIPTION
|
|
"Added support for NXL unit."
|
|
|
|
REVISION "200807020000Z"
|
|
DESCRIPTION
|
|
"SMIv2 changes (INTEGER to Integer32.
|
|
Corrected spelling errors."
|
|
|
|
REVISION "200801100000Z"
|
|
DESCRIPTION
|
|
"Modified contact email address."
|
|
|
|
REVISION "200705290000Z"
|
|
DESCRIPTION
|
|
"Added support for XDF Unit."
|
|
|
|
REVISION "200608150000Z"
|
|
DESCRIPTION
|
|
"Added support for HP release."
|
|
|
|
REVISION "200602220000Z"
|
|
DESCRIPTION
|
|
"Added support for Liebert DS Unit."
|
|
|
|
::= { liebertEnvironmentalModuleReg 1 }
|
|
|
|
-- =============================================================================
|
|
-- lgpEnvironmental - Liebert Environmental Registrations
|
|
-- =============================================================================
|
|
|
|
lgpEnvTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree is used to register Liebert temperature object
|
|
identifiers."
|
|
REFERENCE
|
|
"The registrations for the objects in this sub-tree are
|
|
defined below in the sub-section titled Liebert Environmental
|
|
Temperature Group."
|
|
::= { lgpEnvironmental 1 }
|
|
|
|
lgpEnvHumidity OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree is used to register Liebert humidity object
|
|
identifiers."
|
|
REFERENCE
|
|
"The registrations for the objects in this sub-tree are
|
|
defined below in the sub-section titled Liebert Environmental
|
|
Humidity Group."
|
|
::= { lgpEnvironmental 2 }
|
|
|
|
lgpEnvState OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree is used to register Liebert environmental state object
|
|
identifiers."
|
|
REFERENCE
|
|
"The registrations for the objects in this sub-tree are
|
|
defined below in the sub-section titled Liebert Environmental
|
|
State Group."
|
|
::= { lgpEnvironmental 3 }
|
|
|
|
lgpEnvConfig OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree is used to register Liebert environmental configuration
|
|
object identifiers."
|
|
REFERENCE
|
|
"The registrations for the objects in this sub-tree are
|
|
defined below in the sub-section titled Liebert Environmental
|
|
Configuration Group."
|
|
::= { lgpEnvironmental 4 }
|
|
|
|
lgpEnvControl OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree is used to register Liebert environmental control
|
|
object identifiers."
|
|
REFERENCE
|
|
"The registrations for the objects in this sub-tree are
|
|
defined below in the sub-section titled Liebert Environmental
|
|
Control Group."
|
|
::= { lgpEnvironmental 5 }
|
|
|
|
lgpEnvStatistics OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree is used to register Liebert environmental statistic
|
|
object identifiers."
|
|
REFERENCE
|
|
"The registrations for the objects in this sub-tree are
|
|
defined below in the sub-section titled Liebert Environmental
|
|
Statistics Group."
|
|
::= { lgpEnvironmental 6 }
|
|
|
|
lgpEnvPoints OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree is used to register Liebert environmental point
|
|
object identifiers."
|
|
REFERENCE
|
|
"The registrations for the objects in this sub-tree are
|
|
defined below in the sub-section titled Liebert Environmental
|
|
point Group."
|
|
::= { lgpEnvironmental 7 }
|
|
|
|
lgpEnvUnits OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree is used to register Liebert environmental unit
|
|
object identifiers."
|
|
REFERENCE
|
|
"The registrations for the objects in this sub-tree are
|
|
defined below in the sub-section titled Liebert Environmental
|
|
units Group."
|
|
::= { lgpEnvironmental 8 }
|
|
|
|
lgpEnvRemoteSensors OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree is used to register Liebert environmental remote
|
|
sensor object identifiers."
|
|
REFERENCE
|
|
"The registrations for the objects in this sub-tree are
|
|
defined below in the sub-section titled Liebert Environmental
|
|
Remote Sensor Group."
|
|
::= { lgpEnvironmental 9 }
|
|
|
|
-- =============================================================================
|
|
-- lgpEnvTemperature - Liebert Environmental Temperature Group
|
|
-- =============================================================================
|
|
|
|
lgpEnvTemperatureWellKnown OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Liebert well known temperature objects are identified by OIDs that
|
|
reside in this sub-tree."
|
|
::= { lgpEnvTemperature 1 }
|
|
|
|
lgpEnvTemperatureFahrenheit OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree contains OIDs that are used to control and monitor
|
|
temperature using the Fahrenheit temperature scale."
|
|
REFERENCE
|
|
"The registrations for the objects in this sub-tree are defined below
|
|
in the sub-section titled Liebert Environmental Fahrenheit Temperature
|
|
Group."
|
|
::= { lgpEnvTemperature 2 }
|
|
|
|
lgpEnvTemperatureCelsius OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree contains OIDs that are used to control and monitor
|
|
temperature using the Celsius temperature scale."
|
|
REFERENCE
|
|
"The registrations for the objects in this sub-tree are defined below
|
|
in the sub-section titled Liebert Environmental Celsius Temperature
|
|
Group."
|
|
::= { lgpEnvTemperature 3 }
|
|
|
|
lgpEnvTemperatureControlMode OBJECT-TYPE
|
|
SYNTAX OBJECT IDENTIFIER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A reference to a temperature description object. The object
|
|
referenced should not be accessible, but rather be used to provide
|
|
a unique description of the temperature object that is used for
|
|
control."
|
|
::= { lgpEnvTemperature 4 }
|
|
|
|
-- =============================================================================
|
|
-- lgpEnvHumidity - Liebert Environmental Humidity Group
|
|
-- =============================================================================
|
|
|
|
lgpEnvHumidityWellKnown OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Liebert well known humidity objects are defined by OIDs that reside
|
|
in this sub-tree."
|
|
::= { lgpEnvHumidity 1 }
|
|
|
|
lgpEnvHumidityRelative OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree contains OIDs that are used to control and monitor
|
|
relative humidity."
|
|
REFERENCE
|
|
"The registrations for the objects in this sub-tree are defined below
|
|
in the sub-section titled Liebert Environmental Relative Humidity
|
|
Group."
|
|
::= { lgpEnvHumidity 2 }
|
|
|
|
-- =============================================================================
|
|
-- lgpEnvState - Liebert Environmental State Group
|
|
-- =============================================================================
|
|
|
|
lgpEnvStateSystem OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
on(1),
|
|
off(2),
|
|
standby(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present state of the system."
|
|
::= { lgpEnvState 1 }
|
|
|
|
lgpEnvStateCooling OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present state of the cooling subsystem."
|
|
::= { lgpEnvState 2 }
|
|
|
|
lgpEnvStateHeating OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present state of the heating subsystem."
|
|
::= { lgpEnvState 3 }
|
|
|
|
lgpEnvStateHumidifying OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present state of the humidifier subsystem."
|
|
::= { lgpEnvState 4 }
|
|
|
|
lgpEnvStateDehumidifying OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present state of the dehumidifier subsystem"
|
|
::= { lgpEnvState 5 }
|
|
|
|
lgpEnvStateEconoCycle OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present state of the Econ-o-cycle subsystem."
|
|
::= { lgpEnvState 6 }
|
|
|
|
lgpEnvStateFan OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present state of the system fan."
|
|
::= { lgpEnvState 7 }
|
|
|
|
lgpEnvStateGeneralAlarmOutput OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present state of the general alarm output. This indicates if
|
|
an alarm is active in the system."
|
|
::= { lgpEnvState 8 }
|
|
|
|
lgpEnvStateCoolingCapacity OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "percent"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The percentage of the cooling capacity presently in use."
|
|
::= { lgpEnvState 9 }
|
|
|
|
lgpEnvStateHeatingCapacity OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "percent"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The percentage of the heating capacity presently in use."
|
|
::= { lgpEnvState 10 }
|
|
|
|
lgpEnvStateAudibleAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present state of the audible alarm output."
|
|
::= { lgpEnvState 11 }
|
|
|
|
lgpEnvStateCoolingUnits OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree contains OIDs that are used to indicate the status
|
|
of cooling units."
|
|
::= { lgpEnvState 12 }
|
|
|
|
lgpEnvStateCoolingUnit1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present state of cooling unit 1."
|
|
::= { lgpEnvStateCoolingUnits 2 }
|
|
|
|
lgpEnvStateCoolingUnit2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present state of cooling unit 2."
|
|
::= { lgpEnvStateCoolingUnits 3 }
|
|
|
|
lgpEnvStateCoolingUnit3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present state of cooling unit 3."
|
|
::= { lgpEnvStateCoolingUnits 4 }
|
|
|
|
lgpEnvStateCoolingUnit4 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present state of cooling unit 4."
|
|
::= { lgpEnvStateCoolingUnits 5 }
|
|
|
|
lgpEnvStateHeatingUnits OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree contains OIDs that are used to indicate the status
|
|
of heating units."
|
|
::= { lgpEnvState 13 }
|
|
|
|
lgpEnvStateHeatingUnit1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present state of heating unit 1."
|
|
::= { lgpEnvStateHeatingUnits 2 }
|
|
|
|
lgpEnvStateHeatingUnit2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present state of heating unit 2."
|
|
::= { lgpEnvStateHeatingUnits 3 }
|
|
|
|
lgpEnvStateHeatingUnit3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present state of heating unit 3."
|
|
::= { lgpEnvStateHeatingUnits 4 }
|
|
|
|
lgpEnvStateHeatingUnit4 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present state of heating unit 4."
|
|
::= { lgpEnvStateHeatingUnits 5 }
|
|
|
|
lgpEnvStateOperatingReason OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
none(1),
|
|
localUser(2),
|
|
alarm(3),
|
|
schedule(4),
|
|
remoteUser(5),
|
|
externalDevice(6),
|
|
localDisplay(7)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The reason for the current operating state of the system."
|
|
::= { lgpEnvState 14 }
|
|
|
|
lgpEnvStateOperatingMode OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
auto(1),
|
|
manual(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present operating mode of the system."
|
|
::= { lgpEnvState 15 }
|
|
|
|
lgpEnvStateFanCapacity OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "percent"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The percentage of the fan capacity presently in use."
|
|
::= { lgpEnvState 16 }
|
|
|
|
lgpEnvStateFreeCoolingCapacity OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "percent"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The percentage of the free cooling capacity presently in use."
|
|
::= { lgpEnvState 17 }
|
|
|
|
lgpEnvStateDehumidifyingCapacity OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "percent"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The percentage of the dehumidifying capacity presently in use."
|
|
::= { lgpEnvState 18 }
|
|
|
|
lgpEnvStateHumidifyingCapacity OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "percent"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The percentage of the humidifying capacity presently in use."
|
|
::= { lgpEnvState 19 }
|
|
|
|
lgpEnvStateFreeCooling OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
on(1),
|
|
off(2),
|
|
start(3),
|
|
unavailable(4)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present state of the system free cooling process of heat
|
|
exchange. When 'off', free cooling is not in use. When 'on'
|
|
free cooling is in use. When 'start', free cooling is preparing
|
|
to turn on. When 'unavailable', the state information is
|
|
unavailable."
|
|
::= { lgpEnvState 20 }
|
|
|
|
lgpEnvStateElectricHeater OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present state of the electric heaters."
|
|
::= { lgpEnvState 21 }
|
|
|
|
lgpEnvStateHotWater OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present state of hot water system."
|
|
::= { lgpEnvState 22 }
|
|
|
|
lgpEnvStateOperatingEfficiency OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "percent"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The ratio of cooling energy provided to the amount of total energy
|
|
being used."
|
|
::= { lgpEnvState 23 }
|
|
|
|
lgpEnvComponentStateTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF LgpEnvComponentStateEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table contains a list of the units components that have
|
|
a state associated with them.
|
|
The table contains zero, one, or more rows, depending
|
|
upon the number of components associated with the unit.
|
|
The NMS cannot create or delete rows in the table. The rows are
|
|
created by the agent based upon the capabilities of the units
|
|
being monitored."
|
|
::= { lgpEnvState 50 }
|
|
|
|
lgpEnvComponentStateEntry OBJECT-TYPE
|
|
SYNTAX LgpEnvComponentStateEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This entry defines the attributes to be populated in the
|
|
various columns of the 'lgpEnvComponentStateTable'."
|
|
INDEX
|
|
{
|
|
lgpEnvComponentStateIndex
|
|
}
|
|
::= { lgpEnvComponentStateTable 1 }
|
|
|
|
LgpEnvComponentStateEntry ::= SEQUENCE
|
|
{
|
|
lgpEnvComponentStateIndex Unsigned32,
|
|
lgpEnvComponentStateDescr OBJECT IDENTIFIER,
|
|
lgpEnvComponentState INTEGER
|
|
}
|
|
|
|
lgpEnvComponentStateIndex OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is the index indicating the nth element of the table."
|
|
::= { lgpEnvComponentStateEntry 1 }
|
|
|
|
lgpEnvComponentStateDescr OBJECT-TYPE
|
|
SYNTAX OBJECT IDENTIFIER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A reference to a component description object. The object
|
|
referenced should not be accessible, but rather be used
|
|
to provide a unique description of the component being
|
|
described in the row of the table."
|
|
::= { lgpEnvComponentStateEntry 2 }
|
|
|
|
lgpEnvComponentState OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
not-specified(0),
|
|
on(1),
|
|
off(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"not-specified
|
|
The state of the component is unknown.
|
|
on
|
|
The component is on.
|
|
off
|
|
The component is off."
|
|
::= { lgpEnvComponentStateEntry 3 }
|
|
|
|
lgpEnvValveTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF LgpEnvValveEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table contains a list of the unit valves that have
|
|
information associated with them.
|
|
The table contains zero, one, or more rows, depending
|
|
upon the number of valves associated with the unit.
|
|
The NMS cannot create or delete rows in the table. The rows are
|
|
created by the agent based upon the capabilities of the units
|
|
being monitored."
|
|
::= { lgpEnvState 70 }
|
|
|
|
lgpEnvValveEntry OBJECT-TYPE
|
|
SYNTAX LgpEnvValveEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This entry defines the attributes to be populated in the
|
|
various columns of the 'lgpEnvValveTable'."
|
|
INDEX
|
|
{
|
|
lgpEnvValveIndex
|
|
}
|
|
::= { lgpEnvValveTable 1 }
|
|
|
|
LgpEnvValveEntry ::= SEQUENCE
|
|
{
|
|
lgpEnvValveIndex Unsigned32,
|
|
lgpEnvValveDescr OBJECT IDENTIFIER,
|
|
lgpEnvValveState INTEGER,
|
|
lgpEnvValvePositionTenths Unsigned32
|
|
}
|
|
|
|
lgpEnvValveIndex OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is the index indicating the nth element of the table."
|
|
::= { lgpEnvValveEntry 1 }
|
|
|
|
lgpEnvValveDescr OBJECT-TYPE
|
|
SYNTAX OBJECT IDENTIFIER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A reference to a valve description object. The object
|
|
referenced should not be accessible, but rather be used
|
|
to provide a unique description of the valve being
|
|
described in the row of the table."
|
|
::= { lgpEnvValveEntry 2 }
|
|
|
|
lgpEnvValveState OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
not-specified(0),
|
|
open(1),
|
|
closed(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"not-specified
|
|
The state of the component is unknown.
|
|
open
|
|
The valve is open.
|
|
off
|
|
The valve is closed."
|
|
::= { lgpEnvValveEntry 3 }
|
|
|
|
lgpEnvValvePositionTenths OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS ".1 percent"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This gives a value describing the position of the valve."
|
|
::= { lgpEnvValveEntry 20 }
|
|
|
|
-- =============================================================================
|
|
-- lgpEnvConfig - Liebert Environmental Configuration Group
|
|
-- =============================================================================
|
|
|
|
lgpEnvConfigReheatLockout OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
lockedOut(1),
|
|
notLockedOut(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"If locked-out the reheats will not operate even if controller calls
|
|
for its operation."
|
|
::= { lgpEnvConfig 1 }
|
|
|
|
lgpEnvConfigHumLockout OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
lockedOut(1),
|
|
notLockedOut(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"If locked-out the humidifier will not operate even if controller
|
|
calls for its operation."
|
|
::= { lgpEnvConfig 2 }
|
|
|
|
lgpEnvConfigRestartDelay OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When utility power is disrupted, this is the delay interval to wait
|
|
before restarting the system after the utility power is restored.
|
|
A Restart Delay of zero denotes a manual restart, the unit will NOT
|
|
automatically restart."
|
|
::= { lgpEnvConfig 4 }
|
|
|
|
lgpEnvConfigRemoteShutdown OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
disabled(1),
|
|
enabled(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When in the disabled state, the remote shutdown feature should
|
|
be locked out. The enabled state is self-describing."
|
|
::= { lgpEnvConfig 7 }
|
|
|
|
lgpEnvConfigCoolingServiceInterval OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "hours"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The amount of time, in hours, between scheduled maintenance
|
|
of the cooling system. When the cooling service timer reaches
|
|
this value an lgpConditionServiceCooling will be activated.
|
|
Once service has been completed the cooling service timer
|
|
should be reset to 0."
|
|
::= { lgpEnvConfig 8 }
|
|
|
|
lgpEnvConfigHumidifierServiceInterval OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "hours"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The amount of time, in hours, between scheduled maintenance
|
|
of the humidifier. When the humidifier service timer reaches
|
|
this value an lgpConditionServiceHumidifier will be activated.
|
|
Once service has been completed humidifier service timer
|
|
should be reset to 0."
|
|
::= { lgpEnvConfig 9 }
|
|
|
|
lgpEnvConfigFilterServiceInterval OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "hours"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The amount of time, in hours, between scheduled maintenance
|
|
of the system filter. When the filter service timer reaches this
|
|
value an lgpConditionChangeFilter will be activated. Once service
|
|
has been completed the filter service timer should be reset to 0."
|
|
::= { lgpEnvConfig 10 }
|
|
|
|
lgpEnvConfigSleepModeDeadbandRangeDegC OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS ".1 degrees Celsius"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The allowable deviation above and below the temperature set point used
|
|
to create a no control region, a dead-band, where heating and
|
|
cooling control are disabled. This dead-band is applied only
|
|
when the system's sleep mode function is in operation."
|
|
::= { lgpEnvConfig 11 }
|
|
|
|
lgpEnvConfigSleepModeDeadbandRangeDegF OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS ".1 degrees Fahrenheit"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The allowable deviation above and below the temperature set point used
|
|
to create a no control region, a dead-band, where heating and
|
|
cooling control are disabled. This dead-band is applied only
|
|
when the system's sleep mode function is in operation."
|
|
::= { lgpEnvConfig 12 }
|
|
|
|
lgpEnvConfigSupplyTempLowLimitDegF OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "degrees Fahrenheit"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The minimum allowable supply temperature."
|
|
::= { lgpEnvConfig 13 }
|
|
|
|
lgpEnvConfigSupplyTempLowLimitDegC OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "degrees Celsius"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The minimum allowable supply temperature."
|
|
::= { lgpEnvConfig 14 }
|
|
|
|
lgpEnvConfigTemperatureIntegTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "minutes"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value used as the integration factor in the proportional
|
|
integral derivative (PID) temperature calculation."
|
|
::= { lgpEnvConfig 15 }
|
|
|
|
lgpEnvConfigLocalTemperatureUnit OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
degC(1),
|
|
degF(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The local temperature unit of the system."
|
|
::= { lgpEnvConfig 16 }
|
|
|
|
lgpEnvConfigSleepMode OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
enabled(1),
|
|
disabled(2),
|
|
auto(3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The configured mode of the device's sleep function. If 'enabled',
|
|
the device will sleep, or not operate, for each 'lgpEnvSleepDay' that
|
|
is enabled and also during the periods defined in the
|
|
'lgpEnvSleepTimeTable' each day. If 'disabled', the device will
|
|
operate continually and not sleep at all. If 'auto', the device will
|
|
sleep, or not operate, for each 'lgpEnvSleepDay' that is enabled and
|
|
also during the periods defined in the 'lgpEnvSleepTimeTable' each
|
|
day unless the environmental conditions fall outside the desired
|
|
operation ranges."
|
|
::= { lgpEnvConfig 17 }
|
|
|
|
lgpEnvConfigHumidityIntegTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "minutes"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value used as the integration factor in the proportional
|
|
integral derivative (PID) humidity calculation."
|
|
::= { lgpEnvConfig 18 }
|
|
|
|
lgpEnvConfigFreecoolingDeltaDegF OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "degrees Fahrenheit"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The minimum temperature differential between the control
|
|
temperature measurement and the coolant required to utilize
|
|
free-cooling."
|
|
::= { lgpEnvConfig 19 }
|
|
|
|
lgpEnvConfigFreecoolingDeltaDegC OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "degrees Celsius"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The minimum temperature differential between the control
|
|
temperature measurement and the coolant required to utilize
|
|
free-cooling."
|
|
::= { lgpEnvConfig 20 }
|
|
|
|
lgpEnvConfigSupplyTempLowLimit OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
disabled(1),
|
|
enabled(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system configuration parameter to enable or disable the supply
|
|
air low temperature limit."
|
|
::= { lgpEnvConfig 21 }
|
|
|
|
lgpEnvConfigSensorEventsStandard OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
disabled(1),
|
|
enabled(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system configuration parameter to enable or disable the standard
|
|
sensor events."
|
|
::= { lgpEnvConfig 22 }
|
|
|
|
lgpEnvConfigSensorEvents1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
disabled(1),
|
|
enabled(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system configuration parameter to enable or disable sensor 1 events."
|
|
::= { lgpEnvConfig 23 }
|
|
|
|
lgpEnvConfigSleepModeDeadbandRange OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
disabled(1),
|
|
enabled(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system configuration parameter to enable or disable the use of
|
|
the sleep interval dead-band range in the sleep mode temperature
|
|
calculations and control algorithm."
|
|
::= { lgpEnvConfig 24 }
|
|
|
|
lgpEnvConfigAutoConfiguration OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
disabled(1),
|
|
enabled(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system configuration parameter to enable or disable the auto
|
|
configuration feature. This feature configures temperature and
|
|
humidity control parameters."
|
|
::= { lgpEnvConfig 25 }
|
|
|
|
lgpEnvConfigDeltaGlycolType OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
disabled(1),
|
|
contact(2),
|
|
value(3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system configuration parameter that specifies how the system
|
|
will determine if there is enough capacity to initiate free
|
|
cooling. If 'disabled', the system will use the valve temperature
|
|
to initiate free cooling. If 'contact', a input to the system
|
|
will initiate free cooling. If 'valve', the system compares the
|
|
room and glycol temperature differential with the valve temperature
|
|
to initiate free cooling. If the temperature differential is
|
|
greater than or equal to the valve temperature, free cooling will
|
|
be initiated."
|
|
|
|
::= { lgpEnvConfig 26 }
|
|
|
|
lgpEnvConfigChillWaterControl OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
disabled(1),
|
|
enabled(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system configuration parameter to enable or disable the minimum
|
|
chill water temperature control."
|
|
|
|
::= { lgpEnvConfig 27 }
|
|
|
|
lgpEnvConfigInfaredFlushRate OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "percent"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Infrared humidifier pan overfill rate. This parameter configures
|
|
the amount of water that flows into the humidifier pan when the
|
|
'humidifier is in operation."
|
|
|
|
::= { lgpEnvConfig 28 }
|
|
|
|
lgpEnvConfigHumidityControl OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
relative(1),
|
|
compensated(2),
|
|
predictive(3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present configured state of the automatic humidity compensation
|
|
algorithm."
|
|
::= { lgpEnvConfig 29 }
|
|
|
|
lgpEnvConfigCompressorLockout OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
lockedOut(1),
|
|
notLockedOut(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system as locked out the compressor(s). If locked-out, the
|
|
compressor(s) will not operate even if the controller calls for their
|
|
operation."
|
|
|
|
::= { lgpEnvConfig 30 }
|
|
|
|
lgpEnvConfigReheatAndHumidifierLockout OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
lockedOut(1),
|
|
notLockedOut(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system as locked out the compressor(s). If locked-out, the
|
|
electrical reheats and humidifier will not operate even if the
|
|
controller calls for their operation."
|
|
|
|
::= { lgpEnvConfig 31 }
|
|
|
|
-- -----------------------------------------------------------------------------
|
|
-- Operational Time Table
|
|
-- -----------------------------------------------------------------------------
|
|
|
|
lgpEnvOperationalTimeTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF LgpEnvOperationalTimeEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of environmental operational time ranges for a given
|
|
environmental unit. The entries in this table may be duplicated from
|
|
values in the 'lgpEnvStatistics' group.
|
|
|
|
This table contains zero, one, or many rows, depending upon the number
|
|
of 'lgpEnvOperationTimePoint' and 'lgpEnvOperationTimeSubID' available
|
|
in the table.
|
|
|
|
The NMS cannot create or delete rows from the table.
|
|
The rows are created by the agent based upon the capabilities of
|
|
the managed device."
|
|
::= { lgpEnvConfig 32 }
|
|
|
|
lgpEnvOperationalTimeEntry OBJECT-TYPE
|
|
SYNTAX LgpEnvOperationalTimeEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This entry defines the contents of the columns for the table
|
|
'lgpEnvOperationalTimeTable'."
|
|
REFERENCE
|
|
"The 'lgpEnvOperationTimePoint' in this table corresponds to what
|
|
the operation time applies to."
|
|
INDEX { lgpEnvOperationTimeIndex }
|
|
::= { lgpEnvOperationalTimeTable 1 }
|
|
|
|
LgpEnvOperationalTimeEntry ::= SEQUENCE
|
|
{
|
|
lgpEnvOperationTimeIndex Unsigned32,
|
|
lgpEnvOperationTimePoint OBJECT IDENTIFIER,
|
|
lgpEnvOperationTimeSubID Integer32,
|
|
lgpEnvOperationTimeUnit OBJECT IDENTIFIER,
|
|
lgpEnvOperationTimeValue Integer32,
|
|
lgpEnvOperationTimeHighWarning Integer32
|
|
}
|
|
|
|
lgpEnvOperationTimeIndex OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is the index indicating the nth element of the table."
|
|
::= { lgpEnvOperationalTimeEntry 1 }
|
|
|
|
lgpEnvOperationTimePoint OBJECT-TYPE
|
|
SYNTAX OBJECT IDENTIFIER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An OID representing a well known operation point.
|
|
These object identifiers can indicate a point, location, or mode
|
|
of an operation for which a measurement is recorded. The OID's
|
|
name usually implies a location of the measurement point such as
|
|
'fan', 'compressor', etc."
|
|
REFERENCE
|
|
"The object identifiers in this column can be found in the sub-tree
|
|
'lgpEnvWellKnownPoints' and correspond to the entry in the table
|
|
'lgpEnvOperationalTimeTable'."
|
|
::= { lgpEnvOperationalTimeEntry 2 }
|
|
|
|
lgpEnvOperationTimeSubID OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is a sub identifier for the 'lgpEnvOperationPoint'.
|
|
It indicates the instance number of the well known operation
|
|
point. For example, a system could have two fans installed.
|
|
This variable would identify fan 1 with a lgpEnvOperationSubID
|
|
equal to 1 and fan 2 with a lgpEnvOperationSubID equal to 2."
|
|
::= { lgpEnvOperationalTimeEntry 3 }
|
|
|
|
lgpEnvOperationTimeUnit OBJECT-TYPE
|
|
SYNTAX OBJECT IDENTIFIER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An OID representing a well known operation time unit type.
|
|
These object identifiers indicate the units of the operation time.
|
|
The OID's name usually implies a measurement type such as
|
|
'lgpEnvHours', etc."
|
|
REFERENCE
|
|
"The object identifiers in this column can be found in the sub-tree
|
|
'lgpEnvWellKnownUnits' and correspond to the
|
|
entry in the table lgpEnvOperationalTimeTable."
|
|
::= { lgpEnvOperationalTimeEntry 4 }
|
|
|
|
lgpEnvOperationTimeValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "hours"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The actual operation time value of the
|
|
'lgpEnvOperationTimePoint'.
|
|
If multiple operation times are available for a
|
|
'lgpEnvOperationTimePoint' the 'lgpEnvOperationTimeSubID' will
|
|
differentiate between them."
|
|
::= { lgpEnvOperationalTimeEntry 5 }
|
|
|
|
lgpEnvOperationTimeHighWarning OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "hours"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The high warning time of the operation designated by the
|
|
'lgpEnvOperationTimePoint'. If operation times are available at
|
|
a single 'lgpEnvOperationTimePoint' the 'lgpEnvOperationTimeSubID'
|
|
will differentiate between them."
|
|
::= { lgpEnvOperationalTimeEntry 6 }
|
|
|
|
lgpEnvConfigTempControlAlgorithm OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
pi(1),
|
|
pid(2),
|
|
intelligent(3),
|
|
proportional(4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Selects the algorithm for controlling temperature."
|
|
::= { lgpEnvConfig 33 }
|
|
|
|
lgpEnvConfigFanSpeedMode OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
manual(1),
|
|
auto(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Changes the function of the fan speed output. If auto, then the fan
|
|
speed is modulated. If manual, the fan speed output follows
|
|
lgpEnvConfigFanSpeedCapacity."
|
|
::= { lgpEnvConfig 34 }
|
|
|
|
lgpEnvConfigFanSpeedCapacity OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "percent"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sets the fan speed output if lgpEnvConfigFanSpeedMode is set to
|
|
'manual'. Typical values range from 0 to 100% (actual valid ranges may
|
|
differ from unit to unit)."
|
|
::= { lgpEnvConfig 35 }
|
|
|
|
lgpEnvConfigBmsResetTimer OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "minutes"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current count-down time for a BMS to continue controlling the fan
|
|
speed. If this value reaches 0, then the condition
|
|
lgpConditionBmsResetTimerExpired will be generated. If a BMS wants to
|
|
continue controlling the fan speed, it must reset this timer. Typical
|
|
values range from 0 to 120 minutes (actual valid ranges may differ from
|
|
unit to unit)."
|
|
::= { lgpEnvConfig 36 }
|
|
|
|
lgpEnvConfigDisableSensorOffsetDegC OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "degrees Celsius"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"If any of the enclosure temperature sensors
|
|
(lgpEnvEnclosureTemperatureSensors) are outside the average reading by
|
|
this amount, that sensor's readings will not be used."
|
|
::= { lgpEnvConfig 37 }
|
|
|
|
lgpEnvConfigDisableSensorOffsetDegF OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "degrees Fahrenheit"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"If any of the enclosure temperature sensors
|
|
(lgpEnvEnclosureTemperatureSensors) are outside the average reading by
|
|
this amount, that sensor's readings will not be used."
|
|
::= { lgpEnvConfig 38 }
|
|
|
|
lgpEnvConfigCabinetSensorAlarms OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
disabled(0),
|
|
enabled(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enable or Disable Cabinet Sensor Alarms."
|
|
::= { lgpEnvConfig 39 }
|
|
|
|
lgpEnvConfigAirTemperatureControlSensor OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
supply(1),
|
|
remote(2),
|
|
return(3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sensor from which air temperature measurements will be used for
|
|
cooling and heating control."
|
|
::= { lgpEnvConfig 42 }
|
|
|
|
lgpEnvConfigFanSpeedControlSensor OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
supply(1),
|
|
remote(2),
|
|
return(3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sensor from which air temperature measurements will be used for fan
|
|
speed control."
|
|
::= { lgpEnvConfig 43 }
|
|
|
|
lgpEnvConfigMinFanSpeed OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "percent"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sets the minimum fan speed output if lgpEnvConfigFanSpeedMode is set
|
|
to 'Auto'."
|
|
::= { lgpEnvConfig 44 }
|
|
|
|
lgpEnvConfigMaxFanSpeed OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "percent"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sets the maximum fan speed output if lgpEnvConfigFanSpeedMode is set
|
|
to 'Auto'."
|
|
::= { lgpEnvConfig 45 }
|
|
|
|
lgpEnvConfigFanSpeedPropBandDegC OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "degrees Celsius"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature control band above the temperature set point calculated
|
|
for proportional fan speed control. If measured air temperature is
|
|
within this band, fan speed operations are proportionally controlled."
|
|
::= { lgpEnvConfig 46 }
|
|
|
|
lgpEnvConfigFanSpeedPropBandDegF OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "degrees Fahrenheit"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature control band above the temperature set point calculated
|
|
for proportional fan speed control. If measured air temperature is
|
|
within this band, fan speed operations are proportionally controlled."
|
|
::= { lgpEnvConfig 47 }
|
|
|
|
-- =============================================================================
|
|
-- lgpEnvControl - Liebert Environmental Control Group
|
|
-- =============================================================================
|
|
|
|
lgpEnvControlShutdownAfterDelay OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..2147483647)
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this object will shutdown (i.e., turn off)
|
|
the system after the indicated number of seconds. Setting
|
|
this object to 0 will cause the shutdown to occur
|
|
immediately. Setting this object to -1 will abort the
|
|
countdown. If the system is already in the desired
|
|
state at the time the countdown reaches 0, then
|
|
nothing will happen. When read, lgpEnvControlShutdownAfterDelay
|
|
will return the number of seconds remaining until shutdown,
|
|
or -1 if no shutdown countdown is in effect. On some systems,
|
|
if the agent is restarted while a shutdown countdown is in effect,
|
|
the countdown may be aborted. Sets to this object
|
|
override any lgpEnvControlShutdownAfterDelay already in effect."
|
|
::= { lgpEnvControl 1 }
|
|
|
|
lgpEnvControlStartupAfterDelay OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..2147483647)
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this object will start the system after the
|
|
indicated number of seconds. Setting this object to 0 will
|
|
cause the startup to occur immediately. Setting this
|
|
object to -1 will abort the countdown. If the system
|
|
is already on at the time the countdown reaches 0,
|
|
then nothing will happen. Sets to this object
|
|
override the effect of any lgpEnvControlStartupAfterDelay
|
|
countdown in progress. When read, lgpEnvControlStartupAfterDelay
|
|
will return the number of seconds until startup, or -1 if no
|
|
startup countdown is in effect. On some systems, if the agent
|
|
is restarted while a startup countdown is in effect, the
|
|
countdown is aborted."
|
|
::= { lgpEnvControl 2 }
|
|
|
|
lgpEnvSleepIntervalTimeTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF LgpEnvSleepIntervalTimeEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A sleep time interval table containing a list of the start and stop
|
|
times to be used to take a device online or offline.
|
|
|
|
The NMS cannot create or delete rows from the table.
|
|
The rows are created by the agent based upon the capabilities of
|
|
the managed device."
|
|
::= { lgpEnvControl 3 }
|
|
|
|
lgpEnvSleepIntervalTimeEntry OBJECT-TYPE
|
|
SYNTAX LgpEnvSleepIntervalTimeEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This entry defines the contents of the columns for the table
|
|
'lgpEnvSleepIntervalTimeTable'."
|
|
INDEX { lgpEnvSleepTimeIndex }
|
|
::= { lgpEnvSleepIntervalTimeTable 1 }
|
|
|
|
LgpEnvSleepIntervalTimeEntry ::= SEQUENCE
|
|
{
|
|
lgpEnvSleepTimeIndex Unsigned32,
|
|
lgpEnvSleepTimeSubID Integer32,
|
|
lgpEnvSleepTimeStartHour Integer32,
|
|
lgpEnvSleepTimeStartMinute Integer32,
|
|
lgpEnvSleepTimeStopHour Integer32,
|
|
lgpEnvSleepTimeStopMinute Integer32
|
|
}
|
|
|
|
lgpEnvSleepTimeIndex OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is the index indicating the row of the table
|
|
'lgpEnvSleepIntervalTimeTable'."
|
|
::= { lgpEnvSleepIntervalTimeEntry 1 }
|
|
|
|
lgpEnvSleepTimeSubID OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is a sub identifier for each 'lgpEnvSleepIntervalTimeEntry'.
|
|
It indicates the instance number of the
|
|
'lgpEnvSleepIntervalTimeEntry'.
|
|
For example, a system could have two sleep intervals and the first
|
|
interval's sub ID would be 1 and the second interval's sub ID
|
|
would be 2."
|
|
::= { lgpEnvSleepIntervalTimeEntry 2 }
|
|
|
|
lgpEnvSleepTimeStartHour OBJECT-TYPE
|
|
SYNTAX Integer32(0..23)
|
|
UNITS "hour"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is the hours digit of the time when the system will be put
|
|
online."
|
|
::= { lgpEnvSleepIntervalTimeEntry 3 }
|
|
|
|
lgpEnvSleepTimeStartMinute OBJECT-TYPE
|
|
SYNTAX Integer32(0..59)
|
|
UNITS "minute"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is the minutes digit of the time when the system will be put
|
|
online."
|
|
::= { lgpEnvSleepIntervalTimeEntry 4 }
|
|
|
|
lgpEnvSleepTimeStopHour OBJECT-TYPE
|
|
SYNTAX Integer32(0..23)
|
|
UNITS "hour"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is the hours digit containing the time when the system will
|
|
be taken offline."
|
|
::= { lgpEnvSleepIntervalTimeEntry 5 }
|
|
|
|
lgpEnvSleepTimeStopMinute OBJECT-TYPE
|
|
SYNTAX Integer32(0..59)
|
|
UNITS "minute"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is the minutes digit containing the time when the system
|
|
will be taken offline."
|
|
::= { lgpEnvSleepIntervalTimeEntry 6 }
|
|
|
|
lgpEnvSleepDayTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF LgpEnvSleepDayEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A sleep table containing a list of the days of the week the system
|
|
will be offline.
|
|
|
|
The NMS cannot create or delete rows from the table.
|
|
The rows are created by the agent based upon the capabilities of
|
|
the managed device."
|
|
::= { lgpEnvControl 4 }
|
|
|
|
lgpEnvSleepDayEntry OBJECT-TYPE
|
|
SYNTAX LgpEnvSleepDayEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This entry defines the contents of the columns for the table
|
|
'lgpEnvSleepDayTable'."
|
|
INDEX { lgpEnvSleepDayIndex }
|
|
::= { lgpEnvSleepDayTable 1 }
|
|
|
|
LgpEnvSleepDayEntry ::= SEQUENCE
|
|
{
|
|
lgpEnvSleepDayIndex Unsigned32,
|
|
lgpEnvSleepDay INTEGER,
|
|
lgpEnvSleepAllDayEnabled INTEGER
|
|
}
|
|
|
|
lgpEnvSleepDayIndex OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is the index indicating the row of the table
|
|
'lgpEnvSleepDayTable'."
|
|
::= { lgpEnvSleepDayEntry 1 }
|
|
|
|
lgpEnvSleepDay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
sunday(1),
|
|
monday(2),
|
|
tuesday(3),
|
|
wednesday(4),
|
|
thursday(5),
|
|
friday(6),
|
|
saturday(7)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is a sub identifier for the day of the week within
|
|
'lgpEnvSleepDayTable'."
|
|
::= { lgpEnvSleepDayEntry 2 }
|
|
|
|
lgpEnvSleepAllDayEnabled OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
yes(1),
|
|
no(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The all day sleep functionality has been enabled for the
|
|
corresponding 'lgpEnvSleepDay' in the 'lgpEnvSleepDayTable'."
|
|
::= { lgpEnvSleepDayEntry 3 }
|
|
|
|
-- =============================================================================
|
|
-- lgpEnvStatistics - Liebert Environmental Statistics Group
|
|
-- =============================================================================
|
|
|
|
lgpEnvStatisticsComp1RunHr OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "hours"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Accumulated run hours of compressor 1. This value may be duplicated
|
|
in the 'lgpEnvOperationalTimeTable'."
|
|
::= { lgpEnvStatistics 1 }
|
|
|
|
lgpEnvStatisticsComp2RunHr OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "hours"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Accumulated run hours of compressor 2. This value may be duplicated
|
|
in the 'lgpEnvOperationalTimeTable'."
|
|
::= { lgpEnvStatistics 2 }
|
|
|
|
lgpEnvStatisticsFanRunHr OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" Accumulated run hours of the main fan. This value may be duplicated
|
|
in the 'lgpEnvOperationalTimeTable'."
|
|
::= { lgpEnvStatistics 3 }
|
|
|
|
lgpEnvStatisticsHumRunHr OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" Accumulated run hours of the humidifier. This value may be
|
|
duplicated in the 'lgpEnvOperationalTimeTable'."
|
|
::= { lgpEnvStatistics 4 }
|
|
|
|
lgpEnvStatisticsReheat1RunHr OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "hours"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Accumulated run hours of reheat element 1. This value may be
|
|
duplicated in the 'lgpEnvOperationalTimeTable'."
|
|
::= { lgpEnvStatistics 7 }
|
|
|
|
lgpEnvStatisticsReheat2RunHr OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "hours"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Accumulated run hours of reheat element 2. This value may be
|
|
duplicated in the 'lgpEnvOperationalTimeTable'."
|
|
::= { lgpEnvStatistics 8 }
|
|
|
|
lgpEnvStatisticsReheat3RunHr OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "hours"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Accumulated run hours of reheat element 3. This value may be
|
|
duplicated in the 'lgpEnvOperationalTimeTable'."
|
|
::= { lgpEnvStatistics 9 }
|
|
|
|
lgpEnvStatisticsCoolingModeHrs OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "hours"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Accumulated run hours while lgpEnvStateCooling is on(1).
|
|
This value may be duplicated in the 'lgpEnvOperationalTimeTable'."
|
|
::= { lgpEnvStatistics 10 }
|
|
|
|
lgpEnvStatisticsHeatingModeHrs OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "hours"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Accumulated run hours while lgpEnvStateHeating is on(1).
|
|
This value may be duplicated in the 'lgpEnvOperationalTimeTable'."
|
|
::= { lgpEnvStatistics 11 }
|
|
|
|
lgpEnvStatisticsHumidifyModeHrs OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "hours"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Accumulated run hours of the humidifying process of the system.
|
|
This value may be duplicated in the 'lgpEnvOperationalTimeTable'."
|
|
::= { lgpEnvStatistics 12 }
|
|
|
|
lgpEnvStatisticsDehumidifyModeHrs OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "hours"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Accumulated run hours of the dehumidifying process of the system.
|
|
This value may be duplicated in the 'lgpEnvOperationalTimeTable'."
|
|
::= { lgpEnvStatistics 13 }
|
|
|
|
lgpEnvStatisticsHotGasRunHr OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "hours"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Accumulated run hours of the hot gas system. This value may be
|
|
duplicated in the 'lgpEnvOperationalTimeTable'."
|
|
::= { lgpEnvStatistics 14 }
|
|
|
|
lgpEnvStatisticsHotWaterRunHr OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "hours"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Accumulated run hours of the hot water system. This value may be
|
|
duplicated in the 'lgpEnvOperationalTimeTable'."
|
|
::= { lgpEnvStatistics 15 }
|
|
|
|
lgpEnvStatisticsFreeCoolRunHr OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "hours"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Accumulated run hours of the free cooling process. This value may
|
|
be duplicated in the 'lgpEnvOperationalTimeTable'."
|
|
::= { lgpEnvStatistics 16 }
|
|
|
|
lgpEnvStatisticsComp3RunHr OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" Accumulated run hours of compressor 3."
|
|
::= { lgpEnvStatistics 17 }
|
|
|
|
lgpEnvStatisticsComp4RunHr OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" Accumulated run hours of compressor 4."
|
|
::= { lgpEnvStatistics 18 }
|
|
|
|
-- =============================================================================
|
|
-- lgpEnvWellKnownPoints - Liebert "well-known" points
|
|
-- =============================================================================
|
|
|
|
lgpEnvWellKnownPoints OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree registers well known Liebert Environmental Points.
|
|
The object identifier names usually encompass a process, or location,
|
|
where measurements are recorded or where values are applied."
|
|
::= { lgpEnvPoints 1 }
|
|
|
|
lgpEnvFanPoint OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This identifier represents a well known fan measurement point."
|
|
::= { lgpEnvWellKnownPoints 1 }
|
|
|
|
lgpEnvCompressorPoint OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This identifier represents a well known compressor measurement
|
|
point."
|
|
::= { lgpEnvWellKnownPoints 2 }
|
|
|
|
lgpEnvElectricHeaterPoint OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This identifier represents a well known electric heater measurement
|
|
point."
|
|
::= { lgpEnvWellKnownPoints 3 }
|
|
|
|
lgpEnvChilledWaterPoint OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This identifier represents a well known chilled water measurement
|
|
point."
|
|
::= { lgpEnvWellKnownPoints 4 }
|
|
|
|
lgpEnvHumidifierPoint OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This identifier represents a well known humidifier measurement
|
|
point."
|
|
::= { lgpEnvWellKnownPoints 5 }
|
|
|
|
lgpEnvDehumidifierPoint OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This identifier represents a well known dehumidifier measurement
|
|
point."
|
|
::= { lgpEnvWellKnownPoints 6 }
|
|
|
|
lgpEnvFreeCoolingPoint OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This identifier represents a well known free-cooling measurement
|
|
process."
|
|
::= { lgpEnvWellKnownPoints 7 }
|
|
|
|
lgpEnvHotWaterPoint OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This identifier represents a well known hot water measurement
|
|
point."
|
|
::= { lgpEnvWellKnownPoints 8 }
|
|
|
|
lgpEnvHotGasPoint OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This identifier represents a well known hot gas measurement
|
|
point."
|
|
::= { lgpEnvWellKnownPoints 9 }
|
|
|
|
lgpEnvBatteryCabinetPoint OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This identifier represents a well known cabinet point.
|
|
To determine the cabinet being described in a multi-cabinet system,
|
|
this point implements two additional indexes. The first index
|
|
describes the module being supplied with battery power. The second
|
|
index identifies the number of the battery cabinet, which is
|
|
typically a sequential number.
|
|
|
|
Example: lgpPwrMeasBatteryCabinet.2.4
|
|
|
|
'lgpEnvBatteryCabinetPoint' = Point is a battery cabinet.
|
|
'.2' = Cabinet is in the second module.
|
|
'.4' = Cabinet number 4"
|
|
::= { lgpEnvWellKnownPoints 10 }
|
|
|
|
lgpEnvPumpPoints OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree identifies well-known pumps in the system."
|
|
::= { lgpEnvWellKnownPoints 11 }
|
|
|
|
lgpEnvPump1Point OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This identifier represents pump 1."
|
|
::= { lgpEnvPumpPoints 1 }
|
|
|
|
lgpEnvPump2Point OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This identifier represents pump 2."
|
|
::= { lgpEnvPumpPoints 2 }
|
|
|
|
lgpEnvCompressorPoints OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree identifies well-known compressors in the system."
|
|
::= { lgpEnvWellKnownPoints 12 }
|
|
|
|
lgpEnvCompressor1Point OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This identifier represents compressor 1."
|
|
::= { lgpEnvCompressorPoints 1 }
|
|
|
|
lgpEnvCompressor1APoint OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This identifier represents compressor 1A."
|
|
::= { lgpEnvCompressor1Point 1 }
|
|
|
|
lgpEnvCompressor1BPoint OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This identifier represents compressor 1B."
|
|
::= { lgpEnvCompressor1Point 2 }
|
|
|
|
lgpEnvCompressor2Point OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This identifier represents compressor 2."
|
|
::= { lgpEnvCompressorPoints 2 }
|
|
|
|
lgpEnvCompressor2APoint OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This identifier represents compressor 2A."
|
|
::= { lgpEnvCompressor2Point 1 }
|
|
|
|
lgpEnvCompressor2BPoint OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This identifier represents compressor 2B."
|
|
::= { lgpEnvCompressor2Point 2 }
|
|
|
|
lgpEnvValvePoints OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree identifies well-known valves in the system."
|
|
::= { lgpEnvWellKnownPoints 13 }
|
|
|
|
lgpEnvHotGasValve1Point OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This identifier represents hot gas valve 1."
|
|
::= { lgpEnvValvePoints 1 }
|
|
|
|
lgpEnvHotGasValve2Point OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This identifier represents hot gas valve 2."
|
|
::= { lgpEnvValvePoints 2 }
|
|
|
|
lgpEnvRemoteSensorStatisticPoints OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree identifies well-known remote sensor statistics in the
|
|
system."
|
|
::= { lgpEnvWellKnownPoints 14 }
|
|
|
|
lgpEnvRemoteSensorMinimumPoint OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This identifier represents the minimum value for remote sensor
|
|
readings."
|
|
::= { lgpEnvRemoteSensorStatisticPoints 1 }
|
|
|
|
lgpEnvRemoteSensorMaximumPoint OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This identifier represents the maximum value for remote sensor
|
|
readings."
|
|
::= { lgpEnvRemoteSensorStatisticPoints 2 }
|
|
|
|
lgpEnvRemoteSensorAveragePoint OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This identifier represents the average value for remote sensor
|
|
readings."
|
|
::= { lgpEnvRemoteSensorStatisticPoints 3 }
|
|
|
|
-- =============================================================================
|
|
-- lgpEnvWellKnownUnits - Liebert "well-known" units
|
|
-- =============================================================================
|
|
|
|
lgpEnvWellKnownUnits OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree registers well known Liebert Environmental Units.
|
|
The object identifier names usually encompass a process, or location,
|
|
where measurements are recorded or where values are applied."
|
|
::= { lgpEnvUnits 1 }
|
|
|
|
lgpEnvHours OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This identifier represents well known time unit of hours."
|
|
::= { lgpEnvWellKnownUnits 1 }
|
|
|
|
-- =============================================================================
|
|
-- lgpEnvTemperatureMeasurements - Liebert "well-known" temperature objects
|
|
-- =============================================================================
|
|
|
|
lgpEnvControlTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature measurement used as control feedback."
|
|
::= { lgpEnvTemperatureWellKnown 1 }
|
|
|
|
lgpEnvReturnAirTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature measurement of return air."
|
|
::= { lgpEnvTemperatureWellKnown 2 }
|
|
|
|
lgpEnvSupplyAirTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature measurement of supply air."
|
|
::= { lgpEnvTemperatureWellKnown 3 }
|
|
|
|
lgpAmbientTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ambient temperature measurement."
|
|
::= { lgpEnvTemperatureWellKnown 4 }
|
|
|
|
lgpInverterTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature measurement of the inverter."
|
|
::= { lgpEnvTemperatureWellKnown 5 }
|
|
|
|
lgpBatteryTempterature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature measurement of the battery."
|
|
::= { lgpEnvTemperatureWellKnown 6 }
|
|
|
|
lgpAcDcConverterTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature measurement of the AC-to-DC Converter."
|
|
::= { lgpEnvTemperatureWellKnown 7 }
|
|
|
|
lgpPfcTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature measurement of the power factor correction circuitry."
|
|
::= { lgpEnvTemperatureWellKnown 8 }
|
|
|
|
lgpTransformerTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature measurement of the transformer."
|
|
::= { lgpEnvTemperatureWellKnown 9 }
|
|
|
|
lgpLocalTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature measurement of local temperature sensor."
|
|
::= { lgpEnvTemperatureWellKnown 10 }
|
|
|
|
lgpLocal1Temperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature and humidity measurements of Local Sensor 1."
|
|
::= { lgpLocalTemperature 1 }
|
|
|
|
lgpLocal2Temperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature and humidity measurements of Local Sensor 2."
|
|
::= { lgpLocalTemperature 2 }
|
|
|
|
lgpLocal3Temperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature and humidity measurements of Local Sensor 3."
|
|
::= { lgpLocalTemperature 3 }
|
|
|
|
lgpDigitalScrollCompressorTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature and humidity measurements of a digital Scroll Compressor."
|
|
::= { lgpEnvTemperatureWellKnown 11 }
|
|
|
|
lgpDigitalScrollCompressor1Temperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature and humidity measurements of a digital Scroll
|
|
Compressor 1."
|
|
::= { lgpDigitalScrollCompressorTemperature 1 }
|
|
|
|
lgpDigitalScrollCompressor2Temperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature and humidity measurements of a digital Scroll
|
|
Compressor 2."
|
|
::= { lgpDigitalScrollCompressorTemperature 2 }
|
|
|
|
lgpChillWaterTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature measurements of a chill water system."
|
|
::= { lgpEnvTemperatureWellKnown 12 }
|
|
|
|
lgpCoolantTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature measurements of an environmental system's coolant."
|
|
::= { lgpEnvTemperatureWellKnown 13 }
|
|
|
|
lgpEnvEnclosureTemperatureSensors OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enclosure temperature sensors"
|
|
::= { lgpEnvTemperatureWellKnown 14 }
|
|
|
|
lgpEnvEnclosureTemperatureSensor1 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enclosure temperature sensor 1"
|
|
::= { lgpEnvEnclosureTemperatureSensors 1 }
|
|
|
|
lgpEnvEnclosureTemperatureSensor2 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enclosure temperature sensor 2"
|
|
::= { lgpEnvEnclosureTemperatureSensors 2 }
|
|
|
|
lgpEnvEnclosureTemperatureSensor3 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enclosure temperature sensor 3"
|
|
::= { lgpEnvEnclosureTemperatureSensors 3 }
|
|
|
|
lgpEnvEnclosureTemperatureSensor4 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enclosure temperature sensor 4"
|
|
::= { lgpEnvEnclosureTemperatureSensors 4 }
|
|
|
|
lgpEnvValueAmbientRoomTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature outside enclosure."
|
|
::= { lgpEnvTemperatureWellKnown 15 }
|
|
|
|
lgpEnvDewPointTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The calculated temperature outside of the enclosure at which
|
|
condensation is likely to occur."
|
|
::= { lgpEnvTemperatureWellKnown 16 }
|
|
|
|
lgpEnvEnclosureTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature inside of enclosure."
|
|
::= { lgpEnvTemperatureWellKnown 17 }
|
|
|
|
lgpEnvAdjustedTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current temperature set-point which is computed by the system and
|
|
may be temporarily different from the user set-point because of
|
|
external factors."
|
|
::= { lgpEnvTemperatureWellKnown 18 }
|
|
|
|
lgpEnvExternalSensors OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"External sensors to monitor environmental variables such as
|
|
temperature and humidity"
|
|
::= { lgpEnvTemperatureWellKnown 19 }
|
|
|
|
lgpEnvExternalAirSensorA OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature and humidity measurements from external air
|
|
sensor A."
|
|
::= { lgpEnvExternalSensors 1 }
|
|
|
|
lgpEnvExternalAirSensorADewPoint OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Dewpoint temperature for External Air Sensor A."
|
|
::= { lgpEnvExternalSensors 2 }
|
|
|
|
lgpEnvExternalAirSensorB OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature and humidity measurements from external air
|
|
sensor B."
|
|
::= { lgpEnvExternalSensors 3 }
|
|
|
|
lgpEnvExternalAirSensorBDewPoint OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Dewpoint temperature for External Air Sensor B."
|
|
::= { lgpEnvExternalSensors 4 }
|
|
|
|
lgpEnvSupplyFluidTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current temperature of the fluid being supplied."
|
|
::= { lgpEnvTemperatureWellKnown 20 }
|
|
|
|
lgpEnvSupplyRefrigerantTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current temperature of the refrigerant being supplied."
|
|
::= { lgpEnvTemperatureWellKnown 21 }
|
|
|
|
lgpEnvMinDesiredRoomAirTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The minimum desired room air temperature. If the room air temperature
|
|
falls below this set point, the unit will reduce the cooling."
|
|
::= { lgpEnvTemperatureWellKnown 22 }
|
|
|
|
lgpEnvDewPointTemperatures OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree identifies well-known dew point temperatures in the
|
|
system."
|
|
::= { lgpEnvTemperatureWellKnown 23 }
|
|
|
|
lgpEnvInletDewPointTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Dew point temperature measured at the inlet of the unit."
|
|
::= { lgpEnvDewPointTemperatures 1 }
|
|
|
|
-- =============================================================================
|
|
-- lgpEnvTemperatureFahrenheit - Liebert Environmental Fahrenheit
|
|
-- Temperature Group
|
|
-- =============================================================================
|
|
|
|
lgpEnvTemperatureSettingDegF OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "degrees Fahrenheit"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The temperature setting used to control the well known temperature
|
|
object 'lgpEnvControlTemperature'. This setting is cloned in
|
|
'lgpEnvTemperatureSettingDegC' with the value converted to Celsius."
|
|
::= { lgpEnvTemperatureFahrenheit 1 }
|
|
|
|
lgpEnvTemperatureToleranceDegF OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "0.1 degrees Fahrenheit"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The acceptable variance from 'lgpEnvTemperatureSettingDegF', without
|
|
initiating a control action. This setting is cloned in
|
|
'lgpEnvTemperatureToleranceDegC' with the value converted to Celsius."
|
|
::= { lgpEnvTemperatureFahrenheit 2 }
|
|
|
|
lgpEnvTemperatureTableDegF OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF LgpEnvTemperatureEntryDegF
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of temperature table entries. The table contains zero, one,
|
|
or many rows, depending upon the number of temperature objects
|
|
available. The NMS cannot create or delete rows from the table. The
|
|
rows are created by the agent based upon the capabilities of the
|
|
managed device. The entries in this table are cloned in
|
|
'lgpEnvTemperatureTableDegC' where Fahrenheit values are converted to
|
|
Celsius."
|
|
::= { lgpEnvTemperatureFahrenheit 3 }
|
|
|
|
lgpEnvTemperatureDeadbandRangeDegF OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS ".1 degrees Fahrenheit"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The allowable deviation above and below the temperature set point
|
|
used to create a no control region, a dead-band, where heating
|
|
and cooling control are disabled."
|
|
|
|
::= { lgpEnvTemperatureFahrenheit 4 }
|
|
|
|
lgpEnvTemperatureEntryDegF OBJECT-TYPE
|
|
SYNTAX LgpEnvTemperatureEntryDegF
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This entry defines the contents of the rows for the table
|
|
'lgpEnvTemperatureTableDegF'."
|
|
INDEX { lgpEnvTemperatureIdDegF }
|
|
::= { lgpEnvTemperatureTableDegF 1 }
|
|
|
|
LgpEnvTemperatureEntryDegF ::= SEQUENCE
|
|
{
|
|
lgpEnvTemperatureIdDegF Unsigned32,
|
|
lgpEnvTemperatureDescrDegF OBJECT IDENTIFIER,
|
|
lgpEnvTemperatureMeasurementDegF Integer32,
|
|
lgpEnvTemperatureHighThresholdDegF Integer32,
|
|
lgpEnvTemperatureLowThresholdDegF Integer32,
|
|
lgpEnvTemperatureSetPointDegF Integer32,
|
|
lgpEnvTemperatureDailyHighDegF Integer32,
|
|
lgpEnvTemperatureDailyLowDegF Integer32,
|
|
lgpEnvTempDailyHighTimeHourDegF Integer32,
|
|
lgpEnvTempDailyHighTimeMinuteDegF Integer32,
|
|
lgpEnvTempDailyHighTimeSecondDegF Integer32,
|
|
lgpEnvTempDailyLowTimeHourDegF Integer32,
|
|
lgpEnvTempDailyLowTimeMinuteDegF Integer32,
|
|
lgpEnvTempDailyLowTimeSecondDegF Integer32,
|
|
lgpEnvTemperatureMeasurementTenthsDegF Integer32,
|
|
lgpEnvTemperatureHighThresholdTenthsDegF Integer32,
|
|
lgpEnvTemperatureLowThresholdTenthsDegF Integer32,
|
|
lgpEnvTemperatureSetPointTenthsDegF Integer32,
|
|
lgpEnvTemperatureDeadBandTenthsDegF Integer32,
|
|
lgpEnvTempHeatingPropBandTenthsDegF Integer32,
|
|
lgpEnvTempCoolingPropBandTenthsDegF Integer32
|
|
|
|
}
|
|
|
|
lgpEnvTemperatureIdDegF OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This OID is used as an index to identify a row in the table
|
|
'lgpEnvTemperatureTableDegF'."
|
|
::= { lgpEnvTemperatureEntryDegF 1 }
|
|
|
|
lgpEnvTemperatureDescrDegF OBJECT-TYPE
|
|
SYNTAX OBJECT IDENTIFIER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A reference to a temperature description object. The object
|
|
referenced should not be accessible, but rather be used to provide
|
|
a unique description of the temperature."
|
|
::= { lgpEnvTemperatureEntryDegF 2 }
|
|
|
|
lgpEnvTemperatureMeasurementDegF OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "degrees Fahrenheit"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured temperature value."
|
|
::= { lgpEnvTemperatureEntryDegF 3 }
|
|
|
|
lgpEnvTemperatureHighThresholdDegF OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "degrees Fahrenheit"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The high temperature notification threshold. This is the maximum
|
|
value of 'lgpEnvTemperatureMeasurementDegF' before the agent sends a
|
|
notification."
|
|
::= { lgpEnvTemperatureEntryDegF 4 }
|
|
|
|
lgpEnvTemperatureLowThresholdDegF OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "degrees Fahrenheit"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The low temperature notification threshold. This is the minimum
|
|
value of 'lgpEnvTemperatureMeasurementDegF' before the agent sends a
|
|
notification."
|
|
::= { lgpEnvTemperatureEntryDegF 5 }
|
|
|
|
lgpEnvTemperatureSetPointDegF OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "degrees Fahrenheit"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The temperature setting for the well known
|
|
'lgpEnvTemperatureDescrDegF' point. This setting may or may not be
|
|
the setting used from control. Some systems have the capability to
|
|
dynamically change the control setting based on environmental
|
|
conditions and/or user configuration."
|
|
::= { lgpEnvTemperatureEntryDegF 6 }
|
|
|
|
lgpEnvTemperatureDailyHighDegF OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "degrees Fahrenheit"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The daily high temperature measurement."
|
|
::= { lgpEnvTemperatureEntryDegF 7 }
|
|
|
|
lgpEnvTemperatureDailyLowDegF OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "degrees Fahrenheit"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The daily low temperature measurement."
|
|
::= { lgpEnvTemperatureEntryDegF 8 }
|
|
|
|
lgpEnvTempDailyHighTimeHourDegF OBJECT-TYPE
|
|
SYNTAX Integer32(0..23)
|
|
UNITS "hours"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The hours digit of the time corresponding to the daily high
|
|
temperature measurement."
|
|
::= { lgpEnvTemperatureEntryDegF 9 }
|
|
|
|
lgpEnvTempDailyHighTimeMinuteDegF OBJECT-TYPE
|
|
SYNTAX Integer32(0..59)
|
|
UNITS "minutes"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The minutes digit of the time corresponding to the daily high
|
|
temperature measurement."
|
|
::= { lgpEnvTemperatureEntryDegF 10 }
|
|
|
|
lgpEnvTempDailyHighTimeSecondDegF OBJECT-TYPE
|
|
SYNTAX Integer32(0..59)
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The seconds digit of the time corresponding to the daily high
|
|
temperature measurement."
|
|
::= { lgpEnvTemperatureEntryDegF 11 }
|
|
|
|
lgpEnvTempDailyLowTimeHourDegF OBJECT-TYPE
|
|
SYNTAX Integer32(0..23)
|
|
UNITS "hours"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The hours digit of the time corresponding to the daily low
|
|
temperature measurement."
|
|
::= { lgpEnvTemperatureEntryDegF 12 }
|
|
|
|
lgpEnvTempDailyLowTimeMinuteDegF OBJECT-TYPE
|
|
SYNTAX Integer32(0..59)
|
|
UNITS "minutes"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The minutes digit of the time corresponding to the daily low
|
|
temperature measurement."
|
|
::= { lgpEnvTemperatureEntryDegF 13 }
|
|
|
|
lgpEnvTempDailyLowTimeSecondDegF OBJECT-TYPE
|
|
SYNTAX Integer32(0..59)
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The seconds digit of the time corresponding to the daily low
|
|
temperature measurement."
|
|
::= { lgpEnvTemperatureEntryDegF 14 }
|
|
|
|
lgpEnvTemperatureMeasurementTenthsDegF OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS ".1 degrees Fahrenheit"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured temperature value."
|
|
::= { lgpEnvTemperatureEntryDegF 50 }
|
|
|
|
lgpEnvTemperatureHighThresholdTenthsDegF OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS ".1 degrees Fahrenheit"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The high temperature notification threshold. This is the maximum
|
|
value of 'lgpEnvTemperatureMeasurementTenthsDegF' before the agent sends a
|
|
notification."
|
|
::= { lgpEnvTemperatureEntryDegF 51 }
|
|
|
|
lgpEnvTemperatureLowThresholdTenthsDegF OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS ".1 degrees Fahrenheit"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The low temperature notification threshold. This is the minimum
|
|
value of 'lgpEnvTemperatureMeasurementTenthsDegF' before the agent sends a
|
|
notification."
|
|
::= { lgpEnvTemperatureEntryDegF 52 }
|
|
|
|
lgpEnvTemperatureSetPointTenthsDegF OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS ".1 degrees Fahrenheit"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The temperature setting for the well known
|
|
'lgpEnvTemperatureDescrDegF' point. This setting may or may not be
|
|
the setting used from control. Some systems have the capability to
|
|
dynamically change the control setting based on environmental
|
|
conditions and/or user configuration."
|
|
::= { lgpEnvTemperatureEntryDegF 53 }
|
|
|
|
lgpEnvTemperatureDeadBandTenthsDegF OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS ".1 degrees Fahrenheit"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The deadband region around the setpoint value
|
|
(lgpEnvTemperatureSetPointTenthsDegF) where no heating or cooling will occur."
|
|
::= { lgpEnvTemperatureEntryDegF 60 }
|
|
|
|
lgpEnvTempHeatingPropBandTenthsDegF OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS ".1 degrees Fahrenheit"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The proportional region below the setpoint value
|
|
(lgpEnvTemperatureSetPointTenthsDegF) where heating will be
|
|
proportionally controlled."
|
|
::= { lgpEnvTemperatureEntryDegF 61 }
|
|
|
|
lgpEnvTempCoolingPropBandTenthsDegF OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS ".1 degrees Fahrenheit"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The proportional region above the setpoint value
|
|
(lgpEnvTemperatureSetPointTenthsDegF) where cooling will be
|
|
proportionally controlled."
|
|
::= { lgpEnvTemperatureEntryDegF 62 }
|
|
|
|
-- =============================================================================
|
|
-- lgpEnvTemperatureCelsius - Liebert Environmental Celsius
|
|
-- Temperature Group
|
|
-- =============================================================================
|
|
|
|
lgpEnvTemperatureSettingDegC OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "degrees Celsius"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The temperature setting used to control the well known temperature
|
|
object 'lgpEnvControlTemperature'. This setting is cloned in
|
|
'lgpEnvTemperatureSettingDegF' with the value converted to Fahrenheit."
|
|
::= { lgpEnvTemperatureCelsius 1 }
|
|
|
|
lgpEnvTemperatureToleranceDegC OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "0.1 degrees Celsius"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The acceptable variance from 'lgpEnvTemperatureSettingDegC', without
|
|
initiating a control action. This setting is cloned in
|
|
'lgpEnvTemperatureToleranceDegF' with the value converted to Fahrenheit."
|
|
::= { lgpEnvTemperatureCelsius 2 }
|
|
|
|
lgpEnvTemperatureTableDegC OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF LgpEnvTemperatureEntryDegC
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of temperature table entries. The table contains zero, one,
|
|
or many rows, depending upon the number of temperature objects
|
|
available. The NMS cannot create or delete rows from the table. The
|
|
rows are created by the agent based upon the capabilities of the
|
|
managed device. The entries in this table are cloned in
|
|
'lgpEnvTemperatureTableDegF' where Celsius values are converted to
|
|
Fahrenheit."
|
|
::= { lgpEnvTemperatureCelsius 3 }
|
|
|
|
lgpEnvTemperatureDeadbandRangeDegC OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS ".1 degrees Celsius"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The allowable deviation above and below the temperature set point
|
|
used to create a no control region, a dead-band, where heating
|
|
and cooling control are disabled."
|
|
::= { lgpEnvTemperatureCelsius 4 }
|
|
|
|
lgpEnvTemperatureEntryDegC OBJECT-TYPE
|
|
SYNTAX LgpEnvTemperatureEntryDegC
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This entry defines the contents of the rows for the table
|
|
'lgpEnvTemperatureTableDegC'."
|
|
INDEX { lgpEnvTemperatureIdDegC }
|
|
::= { lgpEnvTemperatureTableDegC 1 }
|
|
|
|
LgpEnvTemperatureEntryDegC ::= SEQUENCE
|
|
{
|
|
lgpEnvTemperatureIdDegC Unsigned32,
|
|
lgpEnvTemperatureDescrDegC OBJECT IDENTIFIER,
|
|
lgpEnvTemperatureMeasurementDegC Integer32,
|
|
lgpEnvTemperatureHighThresholdDegC Integer32,
|
|
lgpEnvTemperatureLowThresholdDegC Integer32,
|
|
lgpEnvTemperatureSetPointDegC Integer32,
|
|
lgpEnvTemperatureDailyHighDegC Integer32,
|
|
lgpEnvTemperatureDailyLowDegC Integer32,
|
|
lgpEnvTempDailyHighTimeHourDegC Integer32,
|
|
lgpEnvTempDailyHighTimeMinuteDegC Integer32,
|
|
lgpEnvTempDailyHighTimeSecondDegC Integer32,
|
|
lgpEnvTempDailyLowTimeHourDegC Integer32,
|
|
lgpEnvTempDailyLowTimeMinuteDegC Integer32,
|
|
lgpEnvTempDailyLowTimeSecondDegC Integer32,
|
|
lgpEnvTemperatureMeasurementTenthsDegC Integer32,
|
|
lgpEnvTemperatureHighThresholdTenthsDegC Integer32,
|
|
lgpEnvTemperatureLowThresholdTenthsDegC Integer32,
|
|
lgpEnvTemperatureSetPointTenthsDegC Integer32,
|
|
lgpEnvTemperatureDeadBandTenthsDegC Integer32,
|
|
lgpEnvTempHeatingPropBandTenthsDegC Integer32,
|
|
lgpEnvTempCoolingPropBandTenthsDegC Integer32
|
|
|
|
}
|
|
|
|
lgpEnvTemperatureIdDegC OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This OID is used as an index to identify a row in the table
|
|
'lgpEnvTemperatureTableDegC'."
|
|
::= { lgpEnvTemperatureEntryDegC 1 }
|
|
|
|
lgpEnvTemperatureDescrDegC OBJECT-TYPE
|
|
SYNTAX OBJECT IDENTIFIER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A reference to a temperature description object. The object
|
|
referenced should not be accessible, but rather be used to provide
|
|
a unique description of the temperature."
|
|
::= { lgpEnvTemperatureEntryDegC 2 }
|
|
|
|
lgpEnvTemperatureMeasurementDegC OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "degrees Celsius"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured temperature value."
|
|
::= { lgpEnvTemperatureEntryDegC 3 }
|
|
|
|
lgpEnvTemperatureHighThresholdDegC OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "degrees Celsius"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The high temperature notification threshold. This is the maximum
|
|
value of 'lgpEnvTemperatureMeasurementDegC' before the agent sends a
|
|
notification."
|
|
::= { lgpEnvTemperatureEntryDegC 4 }
|
|
|
|
lgpEnvTemperatureLowThresholdDegC OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "degrees Celsius"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The low temperature notification threshold. This is the minimum
|
|
value of 'lgpEnvTemperatureMeasurementDegC' before the agent sends a
|
|
notification."
|
|
::= { lgpEnvTemperatureEntryDegC 5 }
|
|
|
|
lgpEnvTemperatureSetPointDegC OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "degrees Celsius"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The temperature setting for the well known
|
|
'lgpEnvTemperatureDescrDegC' point. This setting may or may not be
|
|
the setting used from control. Some systems have the capability to
|
|
dynamically change the control setting based on environmental
|
|
conditions and/or user configuration."
|
|
::= { lgpEnvTemperatureEntryDegC 6 }
|
|
|
|
lgpEnvTemperatureDailyHighDegC OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "degrees Celsius"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The daily high temperature measurement."
|
|
::= { lgpEnvTemperatureEntryDegC 7 }
|
|
|
|
lgpEnvTemperatureDailyLowDegC OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "degrees Celsius"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The daily low temperature measurement."
|
|
::= { lgpEnvTemperatureEntryDegC 8 }
|
|
|
|
lgpEnvTempDailyHighTimeHourDegC OBJECT-TYPE
|
|
SYNTAX Integer32(0..23)
|
|
UNITS "hours"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The hours digit of the time corresponding to the daily high
|
|
temperature measurement."
|
|
::= { lgpEnvTemperatureEntryDegC 9 }
|
|
|
|
lgpEnvTempDailyHighTimeMinuteDegC OBJECT-TYPE
|
|
SYNTAX Integer32(0..59)
|
|
UNITS "minutes"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The minutes digit of the time corresponding to the daily high
|
|
temperature measurement."
|
|
::= { lgpEnvTemperatureEntryDegC 10 }
|
|
|
|
lgpEnvTempDailyHighTimeSecondDegC OBJECT-TYPE
|
|
SYNTAX Integer32(0..59)
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The seconds digit of the time corresponding to the daily high
|
|
temperature measurement."
|
|
::= { lgpEnvTemperatureEntryDegC 11 }
|
|
|
|
lgpEnvTempDailyLowTimeHourDegC OBJECT-TYPE
|
|
SYNTAX Integer32(0..23)
|
|
UNITS "hours"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The hours digit of the time corresponding to the daily low
|
|
temperature measurement."
|
|
::= { lgpEnvTemperatureEntryDegC 12 }
|
|
|
|
lgpEnvTempDailyLowTimeMinuteDegC OBJECT-TYPE
|
|
SYNTAX Integer32(0..59)
|
|
UNITS "minutes"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The minutes digit of the time corresponding to the daily low
|
|
temperature measurement."
|
|
::= { lgpEnvTemperatureEntryDegC 13 }
|
|
|
|
lgpEnvTempDailyLowTimeSecondDegC OBJECT-TYPE
|
|
SYNTAX Integer32(0..59)
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The seconds digit of the time corresponding to the daily low
|
|
temperature measurement."
|
|
::= { lgpEnvTemperatureEntryDegC 14 }
|
|
|
|
lgpEnvTemperatureMeasurementTenthsDegC OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS ".1 degrees Celsius"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured temperature value."
|
|
::= { lgpEnvTemperatureEntryDegC 50 }
|
|
|
|
lgpEnvTemperatureHighThresholdTenthsDegC OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS ".1 degrees Celsius"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The high temperature notification threshold. This is the maximum
|
|
value of 'lgpEnvTemperatureMeasurementTenthsDegC' before the agent sends a
|
|
notification."
|
|
::= { lgpEnvTemperatureEntryDegC 51 }
|
|
|
|
lgpEnvTemperatureLowThresholdTenthsDegC OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS ".1 degrees Celsius"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The low temperature notification threshold. This is the minimum
|
|
value of 'lgpEnvTemperatureMeasurementTenthsDegC' before the agent sends a
|
|
notification."
|
|
::= { lgpEnvTemperatureEntryDegC 52 }
|
|
|
|
lgpEnvTemperatureSetPointTenthsDegC OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS ".1 degrees Celsius"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The temperature setting for the well known
|
|
'lgpEnvTemperatureDescrDegC' point. This setting may or may not be
|
|
the setting used from control. Some systems have the capability to
|
|
dynamically change the control setting based on environmental
|
|
conditions and/or user configuration."
|
|
::= { lgpEnvTemperatureEntryDegC 53 }
|
|
|
|
lgpEnvTemperatureDeadBandTenthsDegC OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS ".1 degrees Celsius"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The deadband region around the setpoint value
|
|
(lgpEnvTemperatureSetPointTenthsDegC) where no heating or cooling will occur."
|
|
::= { lgpEnvTemperatureEntryDegC 60 }
|
|
|
|
lgpEnvTempHeatingPropBandTenthsDegC OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS ".1 degrees Celsius"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The proportional region below the setpoint value
|
|
(lgpEnvTemperatureSetPointTenthsDegC) where heating will be
|
|
proportionally controlled."
|
|
::= { lgpEnvTemperatureEntryDegC 61 }
|
|
|
|
lgpEnvTempCoolingPropBandTenthsDegC OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS ".1 degrees Celsius"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The proportional region above the setpoint value
|
|
(lgpEnvTemperatureSetPointTenthsDegC) where cooling will be
|
|
proportionally controlled."
|
|
::= { lgpEnvTemperatureEntryDegC 62 }
|
|
|
|
-- =============================================================================
|
|
-- lgpEnvHumidityMeasurements - Liebert "well-known" Humidity objects
|
|
-- =============================================================================
|
|
|
|
lgpEnvControlHumidity OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Humidity measurement used as control feedback."
|
|
::= { lgpEnvHumidityWellKnown 1 }
|
|
|
|
lgpEnvReturnAirHumidity OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Humidity measurement of return air."
|
|
::= { lgpEnvHumidityWellKnown 2 }
|
|
|
|
lgpEnvSupplyAirHumidity OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Humidity measurement of supply air."
|
|
::= { lgpEnvHumidityWellKnown 3 }
|
|
|
|
lgpEnvValueAmbientHumidity OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Humidity outside enclosure."
|
|
::= { lgpEnvHumidityWellKnown 4 }
|
|
|
|
-- =============================================================================
|
|
-- lgpEnvRelativeHumidity - Liebert Environmental Relative Humidity Group
|
|
-- =============================================================================
|
|
|
|
lgpEnvHumiditySettingRel OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "percent Relative Humidity"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The humidity setting used to control the well known humidity
|
|
point."
|
|
::= { lgpEnvHumidityRelative 1 }
|
|
|
|
lgpEnvHumidityToleranceRel OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "percent Relative Humidity"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Acceptable variance from lgpEnvHumiditySettingRel, without
|
|
initiating a control action."
|
|
::= { lgpEnvHumidityRelative 2 }
|
|
|
|
lgpEnvHumidityTableRel OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF LgpEnvHumidityEntryRel
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of humidity table entries. The table contains zero, one,
|
|
or many rows, depending upon the number of humidity objects available.
|
|
The NMS cannot create or delete rows from the table. The rows are
|
|
created by the agent based upon the capabilities of the managed device."
|
|
::= { lgpEnvHumidityRelative 3 }
|
|
|
|
lgpEnvHumidityDeadbandRange OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS ".1 percent RH"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The allowable deviation above and below the humidity set point used
|
|
to create a no control region, a dead-band, where humidifying and
|
|
dehumidifying control are disabled."
|
|
::= { lgpEnvHumidityRelative 4 }
|
|
|
|
lgpEnvHumidityEntryRel OBJECT-TYPE
|
|
SYNTAX LgpEnvHumidityEntryRel
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This entry defines the contents of the rows for the table
|
|
'lgpEnvHumidityTableRel'."
|
|
INDEX { lgpEnvHumidityIdRel }
|
|
::= { lgpEnvHumidityTableRel 1 }
|
|
|
|
LgpEnvHumidityEntryRel ::= SEQUENCE
|
|
{
|
|
lgpEnvHumidityIdRel Unsigned32,
|
|
lgpEnvHumidityDescrRel OBJECT IDENTIFIER,
|
|
lgpEnvHumidityMeasurementRel Integer32,
|
|
lgpEnvHumidityHighThresholdRel Integer32,
|
|
lgpEnvHumidityLowThresholdRel Integer32,
|
|
lgpEnvHumiditySetPoint Integer32,
|
|
lgpEnvHumidityDailyHigh Integer32,
|
|
lgpEnvHumidityDailyLow Integer32,
|
|
lgpEnvHumidityDailyHighTimeHour Integer32,
|
|
lgpEnvHumidityDailyHighTimeMinute Integer32,
|
|
lgpEnvHumidityDailyHighTimeSecond Integer32,
|
|
lgpEnvHumidityDailyLowTimeHour Integer32,
|
|
lgpEnvHumidityDailyLowTimeMinute Integer32,
|
|
lgpEnvHumidityDailyLowTimeSecond Integer32,
|
|
lgpEnvHumidityDeadBand Integer32,
|
|
lgpEnvHumidifyPropBand Integer32,
|
|
lgpEnvDehumidifyPropBand Integer32,
|
|
lgpEnvHumidityMeasurementRelTenths Integer32,
|
|
lgpEnvHumidityHighThresholdRelTenths Integer32,
|
|
lgpEnvHumidityLowThresholdRelTenths Integer32
|
|
}
|
|
|
|
lgpEnvHumidityIdRel OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This OID is used as an index to identify a row in the table
|
|
'lgpEnvHumidityTableRel'."
|
|
::= { lgpEnvHumidityEntryRel 1 }
|
|
|
|
lgpEnvHumidityDescrRel OBJECT-TYPE
|
|
SYNTAX OBJECT IDENTIFIER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A reference to a humidity description object. The object
|
|
referenced should not be accessible, but rather be used
|
|
to provide a unique description of the humidity."
|
|
::= { lgpEnvHumidityEntryRel 2 }
|
|
|
|
lgpEnvHumidityMeasurementRel OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "percent Relative Humidity"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured humidity value."
|
|
::= { lgpEnvHumidityEntryRel 3 }
|
|
|
|
lgpEnvHumidityHighThresholdRel OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "percent Relative Humidity"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The high humidity notification threshold. This is the maximum
|
|
value of 'lgpEnvHumidityMeasurementRel' before the agent sends a
|
|
notification."
|
|
::= { lgpEnvHumidityEntryRel 4 }
|
|
|
|
lgpEnvHumidityLowThresholdRel OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "percent Relative Humidity"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The low humidity notification threshold. This is the minimum
|
|
value of 'lgpEnvHumidityMeasurementRel' before the agent sends a
|
|
notification."
|
|
::= { lgpEnvHumidityEntryRel 5 }
|
|
|
|
lgpEnvHumiditySetPoint OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "percent Relative Humidity"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The humidity setting used to control the well known humidity
|
|
object 'lgpEnvHumidityDescrRel'. This setting may or may not be
|
|
the setting used from control. Some systems have the capability to
|
|
dynamically change the control setting based on environmental
|
|
conditions and/or user configuration."
|
|
::= { lgpEnvHumidityEntryRel 6 }
|
|
|
|
lgpEnvHumidityDailyHigh OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "percent Relative Humidity"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The daily high relative humidity measurement."
|
|
::= { lgpEnvHumidityEntryRel 7 }
|
|
|
|
lgpEnvHumidityDailyLow OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "percent Relative Humidity"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The daily low relative humidity measurement."
|
|
::= { lgpEnvHumidityEntryRel 8 }
|
|
|
|
lgpEnvHumidityDailyHighTimeHour OBJECT-TYPE
|
|
SYNTAX Integer32(0..23)
|
|
UNITS "hours"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The hours digit of the time corresponding to the daily high
|
|
humidity measurement."
|
|
::= { lgpEnvHumidityEntryRel 9 }
|
|
|
|
lgpEnvHumidityDailyHighTimeMinute OBJECT-TYPE
|
|
SYNTAX Integer32(0..59)
|
|
UNITS "minutes"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The minutes digit of the time corresponding to the daily high
|
|
humidity measurement."
|
|
::= { lgpEnvHumidityEntryRel 10 }
|
|
|
|
lgpEnvHumidityDailyHighTimeSecond OBJECT-TYPE
|
|
SYNTAX Integer32(0..59)
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The seconds digit of the time corresponding to the daily high
|
|
humidity measurement."
|
|
::= { lgpEnvHumidityEntryRel 11 }
|
|
|
|
lgpEnvHumidityDailyLowTimeHour OBJECT-TYPE
|
|
SYNTAX Integer32(0..23)
|
|
UNITS "hours"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The hours digit of the time corresponding to the daily low humidity measurement."
|
|
::= { lgpEnvHumidityEntryRel 12 }
|
|
|
|
lgpEnvHumidityDailyLowTimeMinute OBJECT-TYPE
|
|
SYNTAX Integer32(0..59)
|
|
UNITS "minutes"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The minutes digit of the time corresponding to the daily low
|
|
humidity measurement."
|
|
::= { lgpEnvHumidityEntryRel 13 }
|
|
|
|
lgpEnvHumidityDailyLowTimeSecond OBJECT-TYPE
|
|
SYNTAX Integer32(0..59)
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The seconds digit of the time corresponding to the daily low humidity measurement."
|
|
::= { lgpEnvHumidityEntryRel 14 }
|
|
|
|
lgpEnvHumidityDeadBand OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "percent Relative Humidity"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The deadband region around the setpoint value
|
|
(lgpEnvHumiditySetPoint) where no humidifying or dehumidifying will occur."
|
|
::= { lgpEnvHumidityEntryRel 15 }
|
|
|
|
lgpEnvHumidifyPropBand OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "percent Relative Humidity"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The proportional region below the setpoint value
|
|
(lgpEnvHumiditySetPoint) where humidifying will be
|
|
proportionally controlled."
|
|
::= { lgpEnvHumidityEntryRel 16 }
|
|
|
|
lgpEnvDehumidifyPropBand OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "percent Relative Humidity"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The proportional region above the setpoint value
|
|
(lgpEnvHumiditySetPoint) where dehumidifying will be
|
|
proportionally controlled."
|
|
::= { lgpEnvHumidityEntryRel 17 }
|
|
|
|
lgpEnvHumidityMeasurementRelTenths OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS ".1 percent Relative Humidity"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured humidity value."
|
|
::= { lgpEnvHumidityEntryRel 50 }
|
|
|
|
lgpEnvHumidityHighThresholdRelTenths OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS ".1 percent Relative Humidity"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The high humidity notification threshold. This is the maximum
|
|
value of 'lgpEnvHumidityMeasurementRelTenths' before the agent sends a
|
|
notification."
|
|
::= { lgpEnvHumidityEntryRel 51 }
|
|
|
|
lgpEnvHumidityLowThresholdRelTenths OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS ".1 percent Relative Humidity"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The low humidity notification threshold. This is the minimum
|
|
value of 'lgpEnvHumidityMeasurementRelTenths' before the agent sends a
|
|
notification."
|
|
::= { lgpEnvHumidityEntryRel 52 }
|
|
|
|
-- =============================================================================
|
|
-- lgpEnvRemoteSensors - Liebert Environmental Remote Sensor Group
|
|
-- =============================================================================
|
|
|
|
lgpEnvRemoteSensorCalc OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
average(1),
|
|
maximum(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Calculation method applied to temperature readings from the remote
|
|
sensors to determine a single temperature measurement value for
|
|
cooling and heating control."
|
|
::= { lgpEnvRemoteSensors 1 }
|
|
|
|
lgpEnvRemoteSensorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF LgpEnvRemoteSensorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table contains a list of remote sensors attached to the
|
|
environmental unit. The table contains zero, one, or more rows,
|
|
depending upon the number of sensors attached to the unit."
|
|
::= { lgpEnvRemoteSensors 10 }
|
|
|
|
lgpEnvRemoteSensorEntry OBJECT-TYPE
|
|
SYNTAX LgpEnvRemoteSensorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This entry defines the attributes to be populated in the
|
|
various columns of the 'lgpEnvRemoteSensorTable'."
|
|
INDEX
|
|
{
|
|
lgpEnvRemoteSensorIndex
|
|
}
|
|
::= { lgpEnvRemoteSensorTable 1 }
|
|
|
|
LgpEnvRemoteSensorEntry ::= SEQUENCE
|
|
{
|
|
lgpEnvRemoteSensorIndex Unsigned32,
|
|
lgpEnvRemoteSensorId Unsigned32,
|
|
lgpEnvRemoteSensorMode Integer32,
|
|
lgpEnvRemoteSensorUsrLabel DisplayString,
|
|
lgpEnvRemoteSensorTempMeasurementDegF Integer32,
|
|
lgpEnvRemoteSensorTempMeasurementDegC Integer32
|
|
}
|
|
|
|
lgpEnvRemoteSensorIndex OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is the index indicating the nth element of the table."
|
|
::= { lgpEnvRemoteSensorEntry 1 }
|
|
|
|
lgpEnvRemoteSensorId OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is the sensor number identifying the sensor."
|
|
::= { lgpEnvRemoteSensorEntry 2 }
|
|
|
|
lgpEnvRemoteSensorMode OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
disable(0),
|
|
reference(1),
|
|
control(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Function assigned to remote sensor. When set to control(2) the
|
|
sensor will be used in calculation of remote sensor temperature which
|
|
may be used for heating and cooling control. When set to disable(0)
|
|
the remote sensor reading is not available. When set to reference(1)
|
|
the remote sensor reading is available but not used for control."
|
|
::= { lgpEnvRemoteSensorEntry 3 }
|
|
|
|
lgpEnvRemoteSensorUsrLabel OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User assigned remote sensor label."
|
|
::= { lgpEnvRemoteSensorEntry 4 }
|
|
|
|
lgpEnvRemoteSensorTempMeasurementDegF OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "degrees Fahrenheit"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature measured at the temperature sensor reported in
|
|
degrees Fahrenheit."
|
|
::= { lgpEnvRemoteSensorEntry 5 }
|
|
|
|
lgpEnvRemoteSensorTempMeasurementDegC OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "degrees Celsius"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature measured at the temperature sensor reported in
|
|
degrees Celsius."
|
|
::= { lgpEnvRemoteSensorEntry 6 }
|
|
|
|
END
|
|
|