mibs/MIBS/liebert/LIEBERT-GP-ENV-MIB
2023-12-05 12:25:34 +01:00

3258 lines
111 KiB
Plaintext

LIEBERT-GP-ENVIRONMENTAL-MIB DEFINITIONS ::= BEGIN
IMPORTS
MODULE-IDENTITY,
OBJECT-IDENTITY,
OBJECT-TYPE,
Unsigned32,
Integer32
FROM SNMPv2-SMI
DisplayString
FROM SNMPv2-TC
lgpEnvironmental,
liebertEnvironmentalModuleReg
FROM LIEBERT-GP-REGISTRATION-MIB
;
-- =============================================================================
-- Module Identification and Registration
-- =============================================================================
liebertGlobalProductsEnvironmentalModule MODULE-IDENTITY
LAST-UPDATED "201507210000Z"
ORGANIZATION "Liebert Corporation"
CONTACT-INFO
"Contact: Technical Support
Postal:
Liebert Corporation
1050 Dearborn Drive
P.O. Box 29186
Columbus OH, 43229
US
Tel: +1 (800) 222-5877
E-mail: liebert.monitoring@vertivco.com
Web: www.vertivco.com
Author: Gregory M. Hoge"
DESCRIPTION
"The MIB module used to register Liebert SNMP OIDs.
Copyright 2000-2015 Liebert Corporation. All rights reserved.
Reproduction of this document is authorized on the condition
that the forgoing copyright notice is included.
This Specification is supplied 'AS IS' and Liebert Corporation
makes no warranty, either express or implied, as to the use,
operation, condition, or performance of the Specification."
REVISION "200811170000Z"
DESCRIPTION
"Added support for NXL unit."
REVISION "200807020000Z"
DESCRIPTION
"SMIv2 changes (INTEGER to Integer32.
Corrected spelling errors."
REVISION "200801100000Z"
DESCRIPTION
"Modified contact email address."
REVISION "200705290000Z"
DESCRIPTION
"Added support for XDF Unit."
REVISION "200608150000Z"
DESCRIPTION
"Added support for HP release."
REVISION "200602220000Z"
DESCRIPTION
"Added support for Liebert DS Unit."
::= { liebertEnvironmentalModuleReg 1 }
-- =============================================================================
-- lgpEnvironmental - Liebert Environmental Registrations
-- =============================================================================
lgpEnvTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree is used to register Liebert temperature object
identifiers."
REFERENCE
"The registrations for the objects in this sub-tree are
defined below in the sub-section titled Liebert Environmental
Temperature Group."
::= { lgpEnvironmental 1 }
lgpEnvHumidity OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree is used to register Liebert humidity object
identifiers."
REFERENCE
"The registrations for the objects in this sub-tree are
defined below in the sub-section titled Liebert Environmental
Humidity Group."
::= { lgpEnvironmental 2 }
lgpEnvState OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree is used to register Liebert environmental state object
identifiers."
REFERENCE
"The registrations for the objects in this sub-tree are
defined below in the sub-section titled Liebert Environmental
State Group."
::= { lgpEnvironmental 3 }
lgpEnvConfig OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree is used to register Liebert environmental configuration
object identifiers."
REFERENCE
"The registrations for the objects in this sub-tree are
defined below in the sub-section titled Liebert Environmental
Configuration Group."
::= { lgpEnvironmental 4 }
lgpEnvControl OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree is used to register Liebert environmental control
object identifiers."
REFERENCE
"The registrations for the objects in this sub-tree are
defined below in the sub-section titled Liebert Environmental
Control Group."
::= { lgpEnvironmental 5 }
lgpEnvStatistics OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree is used to register Liebert environmental statistic
object identifiers."
REFERENCE
"The registrations for the objects in this sub-tree are
defined below in the sub-section titled Liebert Environmental
Statistics Group."
::= { lgpEnvironmental 6 }
lgpEnvPoints OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree is used to register Liebert environmental point
object identifiers."
REFERENCE
"The registrations for the objects in this sub-tree are
defined below in the sub-section titled Liebert Environmental
point Group."
::= { lgpEnvironmental 7 }
lgpEnvUnits OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree is used to register Liebert environmental unit
object identifiers."
REFERENCE
"The registrations for the objects in this sub-tree are
defined below in the sub-section titled Liebert Environmental
units Group."
::= { lgpEnvironmental 8 }
lgpEnvRemoteSensors OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree is used to register Liebert environmental remote
sensor object identifiers."
REFERENCE
"The registrations for the objects in this sub-tree are
defined below in the sub-section titled Liebert Environmental
Remote Sensor Group."
::= { lgpEnvironmental 9 }
-- =============================================================================
-- lgpEnvTemperature - Liebert Environmental Temperature Group
-- =============================================================================
lgpEnvTemperatureWellKnown OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Liebert well known temperature objects are identified by OIDs that
reside in this sub-tree."
::= { lgpEnvTemperature 1 }
lgpEnvTemperatureFahrenheit OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree contains OIDs that are used to control and monitor
temperature using the Fahrenheit temperature scale."
REFERENCE
"The registrations for the objects in this sub-tree are defined below
in the sub-section titled Liebert Environmental Fahrenheit Temperature
Group."
::= { lgpEnvTemperature 2 }
lgpEnvTemperatureCelsius OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree contains OIDs that are used to control and monitor
temperature using the Celsius temperature scale."
REFERENCE
"The registrations for the objects in this sub-tree are defined below
in the sub-section titled Liebert Environmental Celsius Temperature
Group."
::= { lgpEnvTemperature 3 }
lgpEnvTemperatureControlMode OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A reference to a temperature description object. The object
referenced should not be accessible, but rather be used to provide
a unique description of the temperature object that is used for
control."
::= { lgpEnvTemperature 4 }
-- =============================================================================
-- lgpEnvHumidity - Liebert Environmental Humidity Group
-- =============================================================================
lgpEnvHumidityWellKnown OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Liebert well known humidity objects are defined by OIDs that reside
in this sub-tree."
::= { lgpEnvHumidity 1 }
lgpEnvHumidityRelative OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree contains OIDs that are used to control and monitor
relative humidity."
REFERENCE
"The registrations for the objects in this sub-tree are defined below
in the sub-section titled Liebert Environmental Relative Humidity
Group."
::= { lgpEnvHumidity 2 }
-- =============================================================================
-- lgpEnvState - Liebert Environmental State Group
-- =============================================================================
lgpEnvStateSystem OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2),
standby(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present state of the system."
::= { lgpEnvState 1 }
lgpEnvStateCooling OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present state of the cooling subsystem."
::= { lgpEnvState 2 }
lgpEnvStateHeating OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present state of the heating subsystem."
::= { lgpEnvState 3 }
lgpEnvStateHumidifying OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present state of the humidifier subsystem."
::= { lgpEnvState 4 }
lgpEnvStateDehumidifying OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present state of the dehumidifier subsystem"
::= { lgpEnvState 5 }
lgpEnvStateEconoCycle OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present state of the Econ-o-cycle subsystem."
::= { lgpEnvState 6 }
lgpEnvStateFan OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present state of the system fan."
::= { lgpEnvState 7 }
lgpEnvStateGeneralAlarmOutput OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present state of the general alarm output. This indicates if
an alarm is active in the system."
::= { lgpEnvState 8 }
lgpEnvStateCoolingCapacity OBJECT-TYPE
SYNTAX Unsigned32
UNITS "percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The percentage of the cooling capacity presently in use."
::= { lgpEnvState 9 }
lgpEnvStateHeatingCapacity OBJECT-TYPE
SYNTAX Unsigned32
UNITS "percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The percentage of the heating capacity presently in use."
::= { lgpEnvState 10 }
lgpEnvStateAudibleAlarm OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present state of the audible alarm output."
::= { lgpEnvState 11 }
lgpEnvStateCoolingUnits OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree contains OIDs that are used to indicate the status
of cooling units."
::= { lgpEnvState 12 }
lgpEnvStateCoolingUnit1 OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present state of cooling unit 1."
::= { lgpEnvStateCoolingUnits 2 }
lgpEnvStateCoolingUnit2 OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present state of cooling unit 2."
::= { lgpEnvStateCoolingUnits 3 }
lgpEnvStateCoolingUnit3 OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present state of cooling unit 3."
::= { lgpEnvStateCoolingUnits 4 }
lgpEnvStateCoolingUnit4 OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present state of cooling unit 4."
::= { lgpEnvStateCoolingUnits 5 }
lgpEnvStateHeatingUnits OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree contains OIDs that are used to indicate the status
of heating units."
::= { lgpEnvState 13 }
lgpEnvStateHeatingUnit1 OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present state of heating unit 1."
::= { lgpEnvStateHeatingUnits 2 }
lgpEnvStateHeatingUnit2 OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present state of heating unit 2."
::= { lgpEnvStateHeatingUnits 3 }
lgpEnvStateHeatingUnit3 OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present state of heating unit 3."
::= { lgpEnvStateHeatingUnits 4 }
lgpEnvStateHeatingUnit4 OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present state of heating unit 4."
::= { lgpEnvStateHeatingUnits 5 }
lgpEnvStateOperatingReason OBJECT-TYPE
SYNTAX INTEGER
{
none(1),
localUser(2),
alarm(3),
schedule(4),
remoteUser(5),
externalDevice(6),
localDisplay(7)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The reason for the current operating state of the system."
::= { lgpEnvState 14 }
lgpEnvStateOperatingMode OBJECT-TYPE
SYNTAX INTEGER
{
auto(1),
manual(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present operating mode of the system."
::= { lgpEnvState 15 }
lgpEnvStateFanCapacity OBJECT-TYPE
SYNTAX Unsigned32
UNITS "percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The percentage of the fan capacity presently in use."
::= { lgpEnvState 16 }
lgpEnvStateFreeCoolingCapacity OBJECT-TYPE
SYNTAX Unsigned32
UNITS "percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The percentage of the free cooling capacity presently in use."
::= { lgpEnvState 17 }
lgpEnvStateDehumidifyingCapacity OBJECT-TYPE
SYNTAX Unsigned32
UNITS "percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The percentage of the dehumidifying capacity presently in use."
::= { lgpEnvState 18 }
lgpEnvStateHumidifyingCapacity OBJECT-TYPE
SYNTAX Unsigned32
UNITS "percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The percentage of the humidifying capacity presently in use."
::= { lgpEnvState 19 }
lgpEnvStateFreeCooling OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2),
start(3),
unavailable(4)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present state of the system free cooling process of heat
exchange. When 'off', free cooling is not in use. When 'on'
free cooling is in use. When 'start', free cooling is preparing
to turn on. When 'unavailable', the state information is
unavailable."
::= { lgpEnvState 20 }
lgpEnvStateElectricHeater OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present state of the electric heaters."
::= { lgpEnvState 21 }
lgpEnvStateHotWater OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present state of hot water system."
::= { lgpEnvState 22 }
lgpEnvStateOperatingEfficiency OBJECT-TYPE
SYNTAX Unsigned32
UNITS "percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The ratio of cooling energy provided to the amount of total energy
being used."
::= { lgpEnvState 23 }
lgpEnvComponentStateTable OBJECT-TYPE
SYNTAX SEQUENCE OF LgpEnvComponentStateEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains a list of the units components that have
a state associated with them.
The table contains zero, one, or more rows, depending
upon the number of components associated with the unit.
The NMS cannot create or delete rows in the table. The rows are
created by the agent based upon the capabilities of the units
being monitored."
::= { lgpEnvState 50 }
lgpEnvComponentStateEntry OBJECT-TYPE
SYNTAX LgpEnvComponentStateEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This entry defines the attributes to be populated in the
various columns of the 'lgpEnvComponentStateTable'."
INDEX
{
lgpEnvComponentStateIndex
}
::= { lgpEnvComponentStateTable 1 }
LgpEnvComponentStateEntry ::= SEQUENCE
{
lgpEnvComponentStateIndex Unsigned32,
lgpEnvComponentStateDescr OBJECT IDENTIFIER,
lgpEnvComponentState INTEGER
}
lgpEnvComponentStateIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This is the index indicating the nth element of the table."
::= { lgpEnvComponentStateEntry 1 }
lgpEnvComponentStateDescr OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A reference to a component description object. The object
referenced should not be accessible, but rather be used
to provide a unique description of the component being
described in the row of the table."
::= { lgpEnvComponentStateEntry 2 }
lgpEnvComponentState OBJECT-TYPE
SYNTAX INTEGER
{
not-specified(0),
on(1),
off(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"not-specified
The state of the component is unknown.
on
The component is on.
off
The component is off."
::= { lgpEnvComponentStateEntry 3 }
lgpEnvValveTable OBJECT-TYPE
SYNTAX SEQUENCE OF LgpEnvValveEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains a list of the unit valves that have
information associated with them.
The table contains zero, one, or more rows, depending
upon the number of valves associated with the unit.
The NMS cannot create or delete rows in the table. The rows are
created by the agent based upon the capabilities of the units
being monitored."
::= { lgpEnvState 70 }
lgpEnvValveEntry OBJECT-TYPE
SYNTAX LgpEnvValveEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This entry defines the attributes to be populated in the
various columns of the 'lgpEnvValveTable'."
INDEX
{
lgpEnvValveIndex
}
::= { lgpEnvValveTable 1 }
LgpEnvValveEntry ::= SEQUENCE
{
lgpEnvValveIndex Unsigned32,
lgpEnvValveDescr OBJECT IDENTIFIER,
lgpEnvValveState INTEGER,
lgpEnvValvePositionTenths Unsigned32
}
lgpEnvValveIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This is the index indicating the nth element of the table."
::= { lgpEnvValveEntry 1 }
lgpEnvValveDescr OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A reference to a valve description object. The object
referenced should not be accessible, but rather be used
to provide a unique description of the valve being
described in the row of the table."
::= { lgpEnvValveEntry 2 }
lgpEnvValveState OBJECT-TYPE
SYNTAX INTEGER
{
not-specified(0),
open(1),
closed(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"not-specified
The state of the component is unknown.
open
The valve is open.
off
The valve is closed."
::= { lgpEnvValveEntry 3 }
lgpEnvValvePositionTenths OBJECT-TYPE
SYNTAX Unsigned32
UNITS ".1 percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This gives a value describing the position of the valve."
::= { lgpEnvValveEntry 20 }
-- =============================================================================
-- lgpEnvConfig - Liebert Environmental Configuration Group
-- =============================================================================
lgpEnvConfigReheatLockout OBJECT-TYPE
SYNTAX INTEGER
{
lockedOut(1),
notLockedOut(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"If locked-out the reheats will not operate even if controller calls
for its operation."
::= { lgpEnvConfig 1 }
lgpEnvConfigHumLockout OBJECT-TYPE
SYNTAX INTEGER
{
lockedOut(1),
notLockedOut(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"If locked-out the humidifier will not operate even if controller
calls for its operation."
::= { lgpEnvConfig 2 }
lgpEnvConfigRestartDelay OBJECT-TYPE
SYNTAX Unsigned32
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"When utility power is disrupted, this is the delay interval to wait
before restarting the system after the utility power is restored.
A Restart Delay of zero denotes a manual restart, the unit will NOT
automatically restart."
::= { lgpEnvConfig 4 }
lgpEnvConfigRemoteShutdown OBJECT-TYPE
SYNTAX INTEGER
{
disabled(1),
enabled(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"When in the disabled state, the remote shutdown feature should
be locked out. The enabled state is self-describing."
::= { lgpEnvConfig 7 }
lgpEnvConfigCoolingServiceInterval OBJECT-TYPE
SYNTAX Unsigned32
UNITS "hours"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The amount of time, in hours, between scheduled maintenance
of the cooling system. When the cooling service timer reaches
this value an lgpConditionServiceCooling will be activated.
Once service has been completed the cooling service timer
should be reset to 0."
::= { lgpEnvConfig 8 }
lgpEnvConfigHumidifierServiceInterval OBJECT-TYPE
SYNTAX Unsigned32
UNITS "hours"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The amount of time, in hours, between scheduled maintenance
of the humidifier. When the humidifier service timer reaches
this value an lgpConditionServiceHumidifier will be activated.
Once service has been completed humidifier service timer
should be reset to 0."
::= { lgpEnvConfig 9 }
lgpEnvConfigFilterServiceInterval OBJECT-TYPE
SYNTAX Unsigned32
UNITS "hours"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The amount of time, in hours, between scheduled maintenance
of the system filter. When the filter service timer reaches this
value an lgpConditionChangeFilter will be activated. Once service
has been completed the filter service timer should be reset to 0."
::= { lgpEnvConfig 10 }
lgpEnvConfigSleepModeDeadbandRangeDegC OBJECT-TYPE
SYNTAX Integer32
UNITS ".1 degrees Celsius"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The allowable deviation above and below the temperature set point used
to create a no control region, a dead-band, where heating and
cooling control are disabled. This dead-band is applied only
when the system's sleep mode function is in operation."
::= { lgpEnvConfig 11 }
lgpEnvConfigSleepModeDeadbandRangeDegF OBJECT-TYPE
SYNTAX Integer32
UNITS ".1 degrees Fahrenheit"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The allowable deviation above and below the temperature set point used
to create a no control region, a dead-band, where heating and
cooling control are disabled. This dead-band is applied only
when the system's sleep mode function is in operation."
::= { lgpEnvConfig 12 }
lgpEnvConfigSupplyTempLowLimitDegF OBJECT-TYPE
SYNTAX Integer32
UNITS "degrees Fahrenheit"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The minimum allowable supply temperature."
::= { lgpEnvConfig 13 }
lgpEnvConfigSupplyTempLowLimitDegC OBJECT-TYPE
SYNTAX Integer32
UNITS "degrees Celsius"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The minimum allowable supply temperature."
::= { lgpEnvConfig 14 }
lgpEnvConfigTemperatureIntegTime OBJECT-TYPE
SYNTAX Integer32
UNITS "minutes"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value used as the integration factor in the proportional
integral derivative (PID) temperature calculation."
::= { lgpEnvConfig 15 }
lgpEnvConfigLocalTemperatureUnit OBJECT-TYPE
SYNTAX INTEGER
{
degC(1),
degF(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The local temperature unit of the system."
::= { lgpEnvConfig 16 }
lgpEnvConfigSleepMode OBJECT-TYPE
SYNTAX INTEGER
{
enabled(1),
disabled(2),
auto(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The configured mode of the device's sleep function. If 'enabled',
the device will sleep, or not operate, for each 'lgpEnvSleepDay' that
is enabled and also during the periods defined in the
'lgpEnvSleepTimeTable' each day. If 'disabled', the device will
operate continually and not sleep at all. If 'auto', the device will
sleep, or not operate, for each 'lgpEnvSleepDay' that is enabled and
also during the periods defined in the 'lgpEnvSleepTimeTable' each
day unless the environmental conditions fall outside the desired
operation ranges."
::= { lgpEnvConfig 17 }
lgpEnvConfigHumidityIntegTime OBJECT-TYPE
SYNTAX Integer32
UNITS "minutes"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value used as the integration factor in the proportional
integral derivative (PID) humidity calculation."
::= { lgpEnvConfig 18 }
lgpEnvConfigFreecoolingDeltaDegF OBJECT-TYPE
SYNTAX Integer32
UNITS "degrees Fahrenheit"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The minimum temperature differential between the control
temperature measurement and the coolant required to utilize
free-cooling."
::= { lgpEnvConfig 19 }
lgpEnvConfigFreecoolingDeltaDegC OBJECT-TYPE
SYNTAX Integer32
UNITS "degrees Celsius"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The minimum temperature differential between the control
temperature measurement and the coolant required to utilize
free-cooling."
::= { lgpEnvConfig 20 }
lgpEnvConfigSupplyTempLowLimit OBJECT-TYPE
SYNTAX INTEGER
{
disabled(1),
enabled(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The system configuration parameter to enable or disable the supply
air low temperature limit."
::= { lgpEnvConfig 21 }
lgpEnvConfigSensorEventsStandard OBJECT-TYPE
SYNTAX INTEGER
{
disabled(1),
enabled(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The system configuration parameter to enable or disable the standard
sensor events."
::= { lgpEnvConfig 22 }
lgpEnvConfigSensorEvents1 OBJECT-TYPE
SYNTAX INTEGER
{
disabled(1),
enabled(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The system configuration parameter to enable or disable sensor 1 events."
::= { lgpEnvConfig 23 }
lgpEnvConfigSleepModeDeadbandRange OBJECT-TYPE
SYNTAX INTEGER
{
disabled(1),
enabled(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The system configuration parameter to enable or disable the use of
the sleep interval dead-band range in the sleep mode temperature
calculations and control algorithm."
::= { lgpEnvConfig 24 }
lgpEnvConfigAutoConfiguration OBJECT-TYPE
SYNTAX INTEGER
{
disabled(1),
enabled(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The system configuration parameter to enable or disable the auto
configuration feature. This feature configures temperature and
humidity control parameters."
::= { lgpEnvConfig 25 }
lgpEnvConfigDeltaGlycolType OBJECT-TYPE
SYNTAX INTEGER
{
disabled(1),
contact(2),
value(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The system configuration parameter that specifies how the system
will determine if there is enough capacity to initiate free
cooling. If 'disabled', the system will use the valve temperature
to initiate free cooling. If 'contact', a input to the system
will initiate free cooling. If 'valve', the system compares the
room and glycol temperature differential with the valve temperature
to initiate free cooling. If the temperature differential is
greater than or equal to the valve temperature, free cooling will
be initiated."
::= { lgpEnvConfig 26 }
lgpEnvConfigChillWaterControl OBJECT-TYPE
SYNTAX INTEGER
{
disabled(1),
enabled(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The system configuration parameter to enable or disable the minimum
chill water temperature control."
::= { lgpEnvConfig 27 }
lgpEnvConfigInfaredFlushRate OBJECT-TYPE
SYNTAX Unsigned32
UNITS "percent"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The Infrared humidifier pan overfill rate. This parameter configures
the amount of water that flows into the humidifier pan when the
'humidifier is in operation."
::= { lgpEnvConfig 28 }
lgpEnvConfigHumidityControl OBJECT-TYPE
SYNTAX INTEGER
{
relative(1),
compensated(2),
predictive(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The present configured state of the automatic humidity compensation
algorithm."
::= { lgpEnvConfig 29 }
lgpEnvConfigCompressorLockout OBJECT-TYPE
SYNTAX INTEGER
{
lockedOut(1),
notLockedOut(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The system as locked out the compressor(s). If locked-out, the
compressor(s) will not operate even if the controller calls for their
operation."
::= { lgpEnvConfig 30 }
lgpEnvConfigReheatAndHumidifierLockout OBJECT-TYPE
SYNTAX INTEGER
{
lockedOut(1),
notLockedOut(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The system as locked out the compressor(s). If locked-out, the
electrical reheats and humidifier will not operate even if the
controller calls for their operation."
::= { lgpEnvConfig 31 }
-- -----------------------------------------------------------------------------
-- Operational Time Table
-- -----------------------------------------------------------------------------
lgpEnvOperationalTimeTable OBJECT-TYPE
SYNTAX SEQUENCE OF LgpEnvOperationalTimeEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of environmental operational time ranges for a given
environmental unit. The entries in this table may be duplicated from
values in the 'lgpEnvStatistics' group.
This table contains zero, one, or many rows, depending upon the number
of 'lgpEnvOperationTimePoint' and 'lgpEnvOperationTimeSubID' available
in the table.
The NMS cannot create or delete rows from the table.
The rows are created by the agent based upon the capabilities of
the managed device."
::= { lgpEnvConfig 32 }
lgpEnvOperationalTimeEntry OBJECT-TYPE
SYNTAX LgpEnvOperationalTimeEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This entry defines the contents of the columns for the table
'lgpEnvOperationalTimeTable'."
REFERENCE
"The 'lgpEnvOperationTimePoint' in this table corresponds to what
the operation time applies to."
INDEX { lgpEnvOperationTimeIndex }
::= { lgpEnvOperationalTimeTable 1 }
LgpEnvOperationalTimeEntry ::= SEQUENCE
{
lgpEnvOperationTimeIndex Unsigned32,
lgpEnvOperationTimePoint OBJECT IDENTIFIER,
lgpEnvOperationTimeSubID Integer32,
lgpEnvOperationTimeUnit OBJECT IDENTIFIER,
lgpEnvOperationTimeValue Integer32,
lgpEnvOperationTimeHighWarning Integer32
}
lgpEnvOperationTimeIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This is the index indicating the nth element of the table."
::= { lgpEnvOperationalTimeEntry 1 }
lgpEnvOperationTimePoint OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"An OID representing a well known operation point.
These object identifiers can indicate a point, location, or mode
of an operation for which a measurement is recorded. The OID's
name usually implies a location of the measurement point such as
'fan', 'compressor', etc."
REFERENCE
"The object identifiers in this column can be found in the sub-tree
'lgpEnvWellKnownPoints' and correspond to the entry in the table
'lgpEnvOperationalTimeTable'."
::= { lgpEnvOperationalTimeEntry 2 }
lgpEnvOperationTimeSubID OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This is a sub identifier for the 'lgpEnvOperationPoint'.
It indicates the instance number of the well known operation
point. For example, a system could have two fans installed.
This variable would identify fan 1 with a lgpEnvOperationSubID
equal to 1 and fan 2 with a lgpEnvOperationSubID equal to 2."
::= { lgpEnvOperationalTimeEntry 3 }
lgpEnvOperationTimeUnit OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"An OID representing a well known operation time unit type.
These object identifiers indicate the units of the operation time.
The OID's name usually implies a measurement type such as
'lgpEnvHours', etc."
REFERENCE
"The object identifiers in this column can be found in the sub-tree
'lgpEnvWellKnownUnits' and correspond to the
entry in the table lgpEnvOperationalTimeTable."
::= { lgpEnvOperationalTimeEntry 4 }
lgpEnvOperationTimeValue OBJECT-TYPE
SYNTAX Integer32
UNITS "hours"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The actual operation time value of the
'lgpEnvOperationTimePoint'.
If multiple operation times are available for a
'lgpEnvOperationTimePoint' the 'lgpEnvOperationTimeSubID' will
differentiate between them."
::= { lgpEnvOperationalTimeEntry 5 }
lgpEnvOperationTimeHighWarning OBJECT-TYPE
SYNTAX Integer32
UNITS "hours"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The high warning time of the operation designated by the
'lgpEnvOperationTimePoint'. If operation times are available at
a single 'lgpEnvOperationTimePoint' the 'lgpEnvOperationTimeSubID'
will differentiate between them."
::= { lgpEnvOperationalTimeEntry 6 }
lgpEnvConfigTempControlAlgorithm OBJECT-TYPE
SYNTAX INTEGER
{
pi(1),
pid(2),
intelligent(3),
proportional(4)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Selects the algorithm for controlling temperature."
::= { lgpEnvConfig 33 }
lgpEnvConfigFanSpeedMode OBJECT-TYPE
SYNTAX INTEGER
{
manual(1),
auto(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Changes the function of the fan speed output. If auto, then the fan
speed is modulated. If manual, the fan speed output follows
lgpEnvConfigFanSpeedCapacity."
::= { lgpEnvConfig 34 }
lgpEnvConfigFanSpeedCapacity OBJECT-TYPE
SYNTAX Unsigned32
UNITS "percent"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Sets the fan speed output if lgpEnvConfigFanSpeedMode is set to
'manual'. Typical values range from 0 to 100% (actual valid ranges may
differ from unit to unit)."
::= { lgpEnvConfig 35 }
lgpEnvConfigBmsResetTimer OBJECT-TYPE
SYNTAX Unsigned32
UNITS "minutes"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The current count-down time for a BMS to continue controlling the fan
speed. If this value reaches 0, then the condition
lgpConditionBmsResetTimerExpired will be generated. If a BMS wants to
continue controlling the fan speed, it must reset this timer. Typical
values range from 0 to 120 minutes (actual valid ranges may differ from
unit to unit)."
::= { lgpEnvConfig 36 }
lgpEnvConfigDisableSensorOffsetDegC OBJECT-TYPE
SYNTAX Integer32
UNITS "degrees Celsius"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"If any of the enclosure temperature sensors
(lgpEnvEnclosureTemperatureSensors) are outside the average reading by
this amount, that sensor's readings will not be used."
::= { lgpEnvConfig 37 }
lgpEnvConfigDisableSensorOffsetDegF OBJECT-TYPE
SYNTAX Integer32
UNITS "degrees Fahrenheit"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"If any of the enclosure temperature sensors
(lgpEnvEnclosureTemperatureSensors) are outside the average reading by
this amount, that sensor's readings will not be used."
::= { lgpEnvConfig 38 }
lgpEnvConfigCabinetSensorAlarms OBJECT-TYPE
SYNTAX INTEGER
{
disabled(0),
enabled(1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enable or Disable Cabinet Sensor Alarms."
::= { lgpEnvConfig 39 }
lgpEnvConfigAirTemperatureControlSensor OBJECT-TYPE
SYNTAX INTEGER
{
supply(1),
remote(2),
return(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Sensor from which air temperature measurements will be used for
cooling and heating control."
::= { lgpEnvConfig 42 }
lgpEnvConfigFanSpeedControlSensor OBJECT-TYPE
SYNTAX INTEGER
{
supply(1),
remote(2),
return(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Sensor from which air temperature measurements will be used for fan
speed control."
::= { lgpEnvConfig 43 }
lgpEnvConfigMinFanSpeed OBJECT-TYPE
SYNTAX Unsigned32
UNITS "percent"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Sets the minimum fan speed output if lgpEnvConfigFanSpeedMode is set
to 'Auto'."
::= { lgpEnvConfig 44 }
lgpEnvConfigMaxFanSpeed OBJECT-TYPE
SYNTAX Unsigned32
UNITS "percent"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Sets the maximum fan speed output if lgpEnvConfigFanSpeedMode is set
to 'Auto'."
::= { lgpEnvConfig 45 }
lgpEnvConfigFanSpeedPropBandDegC OBJECT-TYPE
SYNTAX Integer32
UNITS "degrees Celsius"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Temperature control band above the temperature set point calculated
for proportional fan speed control. If measured air temperature is
within this band, fan speed operations are proportionally controlled."
::= { lgpEnvConfig 46 }
lgpEnvConfigFanSpeedPropBandDegF OBJECT-TYPE
SYNTAX Integer32
UNITS "degrees Fahrenheit"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Temperature control band above the temperature set point calculated
for proportional fan speed control. If measured air temperature is
within this band, fan speed operations are proportionally controlled."
::= { lgpEnvConfig 47 }
-- =============================================================================
-- lgpEnvControl - Liebert Environmental Control Group
-- =============================================================================
lgpEnvControlShutdownAfterDelay OBJECT-TYPE
SYNTAX Integer32 (-1..2147483647)
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Setting this object will shutdown (i.e., turn off)
the system after the indicated number of seconds. Setting
this object to 0 will cause the shutdown to occur
immediately. Setting this object to -1 will abort the
countdown. If the system is already in the desired
state at the time the countdown reaches 0, then
nothing will happen. When read, lgpEnvControlShutdownAfterDelay
will return the number of seconds remaining until shutdown,
or -1 if no shutdown countdown is in effect. On some systems,
if the agent is restarted while a shutdown countdown is in effect,
the countdown may be aborted. Sets to this object
override any lgpEnvControlShutdownAfterDelay already in effect."
::= { lgpEnvControl 1 }
lgpEnvControlStartupAfterDelay OBJECT-TYPE
SYNTAX Integer32 (-1..2147483647)
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Setting this object will start the system after the
indicated number of seconds. Setting this object to 0 will
cause the startup to occur immediately. Setting this
object to -1 will abort the countdown. If the system
is already on at the time the countdown reaches 0,
then nothing will happen. Sets to this object
override the effect of any lgpEnvControlStartupAfterDelay
countdown in progress. When read, lgpEnvControlStartupAfterDelay
will return the number of seconds until startup, or -1 if no
startup countdown is in effect. On some systems, if the agent
is restarted while a startup countdown is in effect, the
countdown is aborted."
::= { lgpEnvControl 2 }
lgpEnvSleepIntervalTimeTable OBJECT-TYPE
SYNTAX SEQUENCE OF LgpEnvSleepIntervalTimeEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A sleep time interval table containing a list of the start and stop
times to be used to take a device online or offline.
The NMS cannot create or delete rows from the table.
The rows are created by the agent based upon the capabilities of
the managed device."
::= { lgpEnvControl 3 }
lgpEnvSleepIntervalTimeEntry OBJECT-TYPE
SYNTAX LgpEnvSleepIntervalTimeEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This entry defines the contents of the columns for the table
'lgpEnvSleepIntervalTimeTable'."
INDEX { lgpEnvSleepTimeIndex }
::= { lgpEnvSleepIntervalTimeTable 1 }
LgpEnvSleepIntervalTimeEntry ::= SEQUENCE
{
lgpEnvSleepTimeIndex Unsigned32,
lgpEnvSleepTimeSubID Integer32,
lgpEnvSleepTimeStartHour Integer32,
lgpEnvSleepTimeStartMinute Integer32,
lgpEnvSleepTimeStopHour Integer32,
lgpEnvSleepTimeStopMinute Integer32
}
lgpEnvSleepTimeIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This is the index indicating the row of the table
'lgpEnvSleepIntervalTimeTable'."
::= { lgpEnvSleepIntervalTimeEntry 1 }
lgpEnvSleepTimeSubID OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This is a sub identifier for each 'lgpEnvSleepIntervalTimeEntry'.
It indicates the instance number of the
'lgpEnvSleepIntervalTimeEntry'.
For example, a system could have two sleep intervals and the first
interval's sub ID would be 1 and the second interval's sub ID
would be 2."
::= { lgpEnvSleepIntervalTimeEntry 2 }
lgpEnvSleepTimeStartHour OBJECT-TYPE
SYNTAX Integer32(0..23)
UNITS "hour"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This is the hours digit of the time when the system will be put
online."
::= { lgpEnvSleepIntervalTimeEntry 3 }
lgpEnvSleepTimeStartMinute OBJECT-TYPE
SYNTAX Integer32(0..59)
UNITS "minute"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This is the minutes digit of the time when the system will be put
online."
::= { lgpEnvSleepIntervalTimeEntry 4 }
lgpEnvSleepTimeStopHour OBJECT-TYPE
SYNTAX Integer32(0..23)
UNITS "hour"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This is the hours digit containing the time when the system will
be taken offline."
::= { lgpEnvSleepIntervalTimeEntry 5 }
lgpEnvSleepTimeStopMinute OBJECT-TYPE
SYNTAX Integer32(0..59)
UNITS "minute"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This is the minutes digit containing the time when the system
will be taken offline."
::= { lgpEnvSleepIntervalTimeEntry 6 }
lgpEnvSleepDayTable OBJECT-TYPE
SYNTAX SEQUENCE OF LgpEnvSleepDayEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A sleep table containing a list of the days of the week the system
will be offline.
The NMS cannot create or delete rows from the table.
The rows are created by the agent based upon the capabilities of
the managed device."
::= { lgpEnvControl 4 }
lgpEnvSleepDayEntry OBJECT-TYPE
SYNTAX LgpEnvSleepDayEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This entry defines the contents of the columns for the table
'lgpEnvSleepDayTable'."
INDEX { lgpEnvSleepDayIndex }
::= { lgpEnvSleepDayTable 1 }
LgpEnvSleepDayEntry ::= SEQUENCE
{
lgpEnvSleepDayIndex Unsigned32,
lgpEnvSleepDay INTEGER,
lgpEnvSleepAllDayEnabled INTEGER
}
lgpEnvSleepDayIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This is the index indicating the row of the table
'lgpEnvSleepDayTable'."
::= { lgpEnvSleepDayEntry 1 }
lgpEnvSleepDay OBJECT-TYPE
SYNTAX INTEGER
{
sunday(1),
monday(2),
tuesday(3),
wednesday(4),
thursday(5),
friday(6),
saturday(7)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This is a sub identifier for the day of the week within
'lgpEnvSleepDayTable'."
::= { lgpEnvSleepDayEntry 2 }
lgpEnvSleepAllDayEnabled OBJECT-TYPE
SYNTAX INTEGER
{
yes(1),
no(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The all day sleep functionality has been enabled for the
corresponding 'lgpEnvSleepDay' in the 'lgpEnvSleepDayTable'."
::= { lgpEnvSleepDayEntry 3 }
-- =============================================================================
-- lgpEnvStatistics - Liebert Environmental Statistics Group
-- =============================================================================
lgpEnvStatisticsComp1RunHr OBJECT-TYPE
SYNTAX Unsigned32
UNITS "hours"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Accumulated run hours of compressor 1. This value may be duplicated
in the 'lgpEnvOperationalTimeTable'."
::= { lgpEnvStatistics 1 }
lgpEnvStatisticsComp2RunHr OBJECT-TYPE
SYNTAX Unsigned32
UNITS "hours"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Accumulated run hours of compressor 2. This value may be duplicated
in the 'lgpEnvOperationalTimeTable'."
::= { lgpEnvStatistics 2 }
lgpEnvStatisticsFanRunHr OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
" Accumulated run hours of the main fan. This value may be duplicated
in the 'lgpEnvOperationalTimeTable'."
::= { lgpEnvStatistics 3 }
lgpEnvStatisticsHumRunHr OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
" Accumulated run hours of the humidifier. This value may be
duplicated in the 'lgpEnvOperationalTimeTable'."
::= { lgpEnvStatistics 4 }
lgpEnvStatisticsReheat1RunHr OBJECT-TYPE
SYNTAX Unsigned32
UNITS "hours"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Accumulated run hours of reheat element 1. This value may be
duplicated in the 'lgpEnvOperationalTimeTable'."
::= { lgpEnvStatistics 7 }
lgpEnvStatisticsReheat2RunHr OBJECT-TYPE
SYNTAX Unsigned32
UNITS "hours"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Accumulated run hours of reheat element 2. This value may be
duplicated in the 'lgpEnvOperationalTimeTable'."
::= { lgpEnvStatistics 8 }
lgpEnvStatisticsReheat3RunHr OBJECT-TYPE
SYNTAX Unsigned32
UNITS "hours"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Accumulated run hours of reheat element 3. This value may be
duplicated in the 'lgpEnvOperationalTimeTable'."
::= { lgpEnvStatistics 9 }
lgpEnvStatisticsCoolingModeHrs OBJECT-TYPE
SYNTAX Unsigned32
UNITS "hours"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Accumulated run hours while lgpEnvStateCooling is on(1).
This value may be duplicated in the 'lgpEnvOperationalTimeTable'."
::= { lgpEnvStatistics 10 }
lgpEnvStatisticsHeatingModeHrs OBJECT-TYPE
SYNTAX Unsigned32
UNITS "hours"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Accumulated run hours while lgpEnvStateHeating is on(1).
This value may be duplicated in the 'lgpEnvOperationalTimeTable'."
::= { lgpEnvStatistics 11 }
lgpEnvStatisticsHumidifyModeHrs OBJECT-TYPE
SYNTAX Unsigned32
UNITS "hours"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Accumulated run hours of the humidifying process of the system.
This value may be duplicated in the 'lgpEnvOperationalTimeTable'."
::= { lgpEnvStatistics 12 }
lgpEnvStatisticsDehumidifyModeHrs OBJECT-TYPE
SYNTAX Unsigned32
UNITS "hours"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Accumulated run hours of the dehumidifying process of the system.
This value may be duplicated in the 'lgpEnvOperationalTimeTable'."
::= { lgpEnvStatistics 13 }
lgpEnvStatisticsHotGasRunHr OBJECT-TYPE
SYNTAX Unsigned32
UNITS "hours"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Accumulated run hours of the hot gas system. This value may be
duplicated in the 'lgpEnvOperationalTimeTable'."
::= { lgpEnvStatistics 14 }
lgpEnvStatisticsHotWaterRunHr OBJECT-TYPE
SYNTAX Unsigned32
UNITS "hours"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Accumulated run hours of the hot water system. This value may be
duplicated in the 'lgpEnvOperationalTimeTable'."
::= { lgpEnvStatistics 15 }
lgpEnvStatisticsFreeCoolRunHr OBJECT-TYPE
SYNTAX Unsigned32
UNITS "hours"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Accumulated run hours of the free cooling process. This value may
be duplicated in the 'lgpEnvOperationalTimeTable'."
::= { lgpEnvStatistics 16 }
lgpEnvStatisticsComp3RunHr OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
" Accumulated run hours of compressor 3."
::= { lgpEnvStatistics 17 }
lgpEnvStatisticsComp4RunHr OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
" Accumulated run hours of compressor 4."
::= { lgpEnvStatistics 18 }
-- =============================================================================
-- lgpEnvWellKnownPoints - Liebert "well-known" points
-- =============================================================================
lgpEnvWellKnownPoints OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree registers well known Liebert Environmental Points.
The object identifier names usually encompass a process, or location,
where measurements are recorded or where values are applied."
::= { lgpEnvPoints 1 }
lgpEnvFanPoint OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This identifier represents a well known fan measurement point."
::= { lgpEnvWellKnownPoints 1 }
lgpEnvCompressorPoint OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This identifier represents a well known compressor measurement
point."
::= { lgpEnvWellKnownPoints 2 }
lgpEnvElectricHeaterPoint OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This identifier represents a well known electric heater measurement
point."
::= { lgpEnvWellKnownPoints 3 }
lgpEnvChilledWaterPoint OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This identifier represents a well known chilled water measurement
point."
::= { lgpEnvWellKnownPoints 4 }
lgpEnvHumidifierPoint OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This identifier represents a well known humidifier measurement
point."
::= { lgpEnvWellKnownPoints 5 }
lgpEnvDehumidifierPoint OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This identifier represents a well known dehumidifier measurement
point."
::= { lgpEnvWellKnownPoints 6 }
lgpEnvFreeCoolingPoint OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This identifier represents a well known free-cooling measurement
process."
::= { lgpEnvWellKnownPoints 7 }
lgpEnvHotWaterPoint OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This identifier represents a well known hot water measurement
point."
::= { lgpEnvWellKnownPoints 8 }
lgpEnvHotGasPoint OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This identifier represents a well known hot gas measurement
point."
::= { lgpEnvWellKnownPoints 9 }
lgpEnvBatteryCabinetPoint OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This identifier represents a well known cabinet point.
To determine the cabinet being described in a multi-cabinet system,
this point implements two additional indexes. The first index
describes the module being supplied with battery power. The second
index identifies the number of the battery cabinet, which is
typically a sequential number.
Example: lgpPwrMeasBatteryCabinet.2.4
'lgpEnvBatteryCabinetPoint' = Point is a battery cabinet.
'.2' = Cabinet is in the second module.
'.4' = Cabinet number 4"
::= { lgpEnvWellKnownPoints 10 }
lgpEnvPumpPoints OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree identifies well-known pumps in the system."
::= { lgpEnvWellKnownPoints 11 }
lgpEnvPump1Point OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This identifier represents pump 1."
::= { lgpEnvPumpPoints 1 }
lgpEnvPump2Point OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This identifier represents pump 2."
::= { lgpEnvPumpPoints 2 }
lgpEnvCompressorPoints OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree identifies well-known compressors in the system."
::= { lgpEnvWellKnownPoints 12 }
lgpEnvCompressor1Point OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This identifier represents compressor 1."
::= { lgpEnvCompressorPoints 1 }
lgpEnvCompressor1APoint OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This identifier represents compressor 1A."
::= { lgpEnvCompressor1Point 1 }
lgpEnvCompressor1BPoint OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This identifier represents compressor 1B."
::= { lgpEnvCompressor1Point 2 }
lgpEnvCompressor2Point OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This identifier represents compressor 2."
::= { lgpEnvCompressorPoints 2 }
lgpEnvCompressor2APoint OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This identifier represents compressor 2A."
::= { lgpEnvCompressor2Point 1 }
lgpEnvCompressor2BPoint OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This identifier represents compressor 2B."
::= { lgpEnvCompressor2Point 2 }
lgpEnvValvePoints OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree identifies well-known valves in the system."
::= { lgpEnvWellKnownPoints 13 }
lgpEnvHotGasValve1Point OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This identifier represents hot gas valve 1."
::= { lgpEnvValvePoints 1 }
lgpEnvHotGasValve2Point OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This identifier represents hot gas valve 2."
::= { lgpEnvValvePoints 2 }
lgpEnvRemoteSensorStatisticPoints OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree identifies well-known remote sensor statistics in the
system."
::= { lgpEnvWellKnownPoints 14 }
lgpEnvRemoteSensorMinimumPoint OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This identifier represents the minimum value for remote sensor
readings."
::= { lgpEnvRemoteSensorStatisticPoints 1 }
lgpEnvRemoteSensorMaximumPoint OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This identifier represents the maximum value for remote sensor
readings."
::= { lgpEnvRemoteSensorStatisticPoints 2 }
lgpEnvRemoteSensorAveragePoint OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This identifier represents the average value for remote sensor
readings."
::= { lgpEnvRemoteSensorStatisticPoints 3 }
-- =============================================================================
-- lgpEnvWellKnownUnits - Liebert "well-known" units
-- =============================================================================
lgpEnvWellKnownUnits OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree registers well known Liebert Environmental Units.
The object identifier names usually encompass a process, or location,
where measurements are recorded or where values are applied."
::= { lgpEnvUnits 1 }
lgpEnvHours OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This identifier represents well known time unit of hours."
::= { lgpEnvWellKnownUnits 1 }
-- =============================================================================
-- lgpEnvTemperatureMeasurements - Liebert "well-known" temperature objects
-- =============================================================================
lgpEnvControlTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Temperature measurement used as control feedback."
::= { lgpEnvTemperatureWellKnown 1 }
lgpEnvReturnAirTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Temperature measurement of return air."
::= { lgpEnvTemperatureWellKnown 2 }
lgpEnvSupplyAirTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Temperature measurement of supply air."
::= { lgpEnvTemperatureWellKnown 3 }
lgpAmbientTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Ambient temperature measurement."
::= { lgpEnvTemperatureWellKnown 4 }
lgpInverterTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Temperature measurement of the inverter."
::= { lgpEnvTemperatureWellKnown 5 }
lgpBatteryTempterature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Temperature measurement of the battery."
::= { lgpEnvTemperatureWellKnown 6 }
lgpAcDcConverterTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Temperature measurement of the AC-to-DC Converter."
::= { lgpEnvTemperatureWellKnown 7 }
lgpPfcTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Temperature measurement of the power factor correction circuitry."
::= { lgpEnvTemperatureWellKnown 8 }
lgpTransformerTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Temperature measurement of the transformer."
::= { lgpEnvTemperatureWellKnown 9 }
lgpLocalTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Temperature measurement of local temperature sensor."
::= { lgpEnvTemperatureWellKnown 10 }
lgpLocal1Temperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Temperature and humidity measurements of Local Sensor 1."
::= { lgpLocalTemperature 1 }
lgpLocal2Temperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Temperature and humidity measurements of Local Sensor 2."
::= { lgpLocalTemperature 2 }
lgpLocal3Temperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Temperature and humidity measurements of Local Sensor 3."
::= { lgpLocalTemperature 3 }
lgpDigitalScrollCompressorTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Temperature and humidity measurements of a digital Scroll Compressor."
::= { lgpEnvTemperatureWellKnown 11 }
lgpDigitalScrollCompressor1Temperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Temperature and humidity measurements of a digital Scroll
Compressor 1."
::= { lgpDigitalScrollCompressorTemperature 1 }
lgpDigitalScrollCompressor2Temperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Temperature and humidity measurements of a digital Scroll
Compressor 2."
::= { lgpDigitalScrollCompressorTemperature 2 }
lgpChillWaterTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Temperature measurements of a chill water system."
::= { lgpEnvTemperatureWellKnown 12 }
lgpCoolantTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Temperature measurements of an environmental system's coolant."
::= { lgpEnvTemperatureWellKnown 13 }
lgpEnvEnclosureTemperatureSensors OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Enclosure temperature sensors"
::= { lgpEnvTemperatureWellKnown 14 }
lgpEnvEnclosureTemperatureSensor1 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Enclosure temperature sensor 1"
::= { lgpEnvEnclosureTemperatureSensors 1 }
lgpEnvEnclosureTemperatureSensor2 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Enclosure temperature sensor 2"
::= { lgpEnvEnclosureTemperatureSensors 2 }
lgpEnvEnclosureTemperatureSensor3 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Enclosure temperature sensor 3"
::= { lgpEnvEnclosureTemperatureSensors 3 }
lgpEnvEnclosureTemperatureSensor4 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Enclosure temperature sensor 4"
::= { lgpEnvEnclosureTemperatureSensors 4 }
lgpEnvValueAmbientRoomTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Temperature outside enclosure."
::= { lgpEnvTemperatureWellKnown 15 }
lgpEnvDewPointTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The calculated temperature outside of the enclosure at which
condensation is likely to occur."
::= { lgpEnvTemperatureWellKnown 16 }
lgpEnvEnclosureTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Temperature inside of enclosure."
::= { lgpEnvTemperatureWellKnown 17 }
lgpEnvAdjustedTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The current temperature set-point which is computed by the system and
may be temporarily different from the user set-point because of
external factors."
::= { lgpEnvTemperatureWellKnown 18 }
lgpEnvExternalSensors OBJECT-IDENTITY
STATUS current
DESCRIPTION
"External sensors to monitor environmental variables such as
temperature and humidity"
::= { lgpEnvTemperatureWellKnown 19 }
lgpEnvExternalAirSensorA OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Temperature and humidity measurements from external air
sensor A."
::= { lgpEnvExternalSensors 1 }
lgpEnvExternalAirSensorADewPoint OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Dewpoint temperature for External Air Sensor A."
::= { lgpEnvExternalSensors 2 }
lgpEnvExternalAirSensorB OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Temperature and humidity measurements from external air
sensor B."
::= { lgpEnvExternalSensors 3 }
lgpEnvExternalAirSensorBDewPoint OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Dewpoint temperature for External Air Sensor B."
::= { lgpEnvExternalSensors 4 }
lgpEnvSupplyFluidTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The current temperature of the fluid being supplied."
::= { lgpEnvTemperatureWellKnown 20 }
lgpEnvSupplyRefrigerantTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The current temperature of the refrigerant being supplied."
::= { lgpEnvTemperatureWellKnown 21 }
lgpEnvMinDesiredRoomAirTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The minimum desired room air temperature. If the room air temperature
falls below this set point, the unit will reduce the cooling."
::= { lgpEnvTemperatureWellKnown 22 }
lgpEnvDewPointTemperatures OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree identifies well-known dew point temperatures in the
system."
::= { lgpEnvTemperatureWellKnown 23 }
lgpEnvInletDewPointTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Dew point temperature measured at the inlet of the unit."
::= { lgpEnvDewPointTemperatures 1 }
-- =============================================================================
-- lgpEnvTemperatureFahrenheit - Liebert Environmental Fahrenheit
-- Temperature Group
-- =============================================================================
lgpEnvTemperatureSettingDegF OBJECT-TYPE
SYNTAX Integer32
UNITS "degrees Fahrenheit"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The temperature setting used to control the well known temperature
object 'lgpEnvControlTemperature'. This setting is cloned in
'lgpEnvTemperatureSettingDegC' with the value converted to Celsius."
::= { lgpEnvTemperatureFahrenheit 1 }
lgpEnvTemperatureToleranceDegF OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Fahrenheit"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The acceptable variance from 'lgpEnvTemperatureSettingDegF', without
initiating a control action. This setting is cloned in
'lgpEnvTemperatureToleranceDegC' with the value converted to Celsius."
::= { lgpEnvTemperatureFahrenheit 2 }
lgpEnvTemperatureTableDegF OBJECT-TYPE
SYNTAX SEQUENCE OF LgpEnvTemperatureEntryDegF
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of temperature table entries. The table contains zero, one,
or many rows, depending upon the number of temperature objects
available. The NMS cannot create or delete rows from the table. The
rows are created by the agent based upon the capabilities of the
managed device. The entries in this table are cloned in
'lgpEnvTemperatureTableDegC' where Fahrenheit values are converted to
Celsius."
::= { lgpEnvTemperatureFahrenheit 3 }
lgpEnvTemperatureDeadbandRangeDegF OBJECT-TYPE
SYNTAX Integer32
UNITS ".1 degrees Fahrenheit"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The allowable deviation above and below the temperature set point
used to create a no control region, a dead-band, where heating
and cooling control are disabled."
::= { lgpEnvTemperatureFahrenheit 4 }
lgpEnvTemperatureEntryDegF OBJECT-TYPE
SYNTAX LgpEnvTemperatureEntryDegF
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This entry defines the contents of the rows for the table
'lgpEnvTemperatureTableDegF'."
INDEX { lgpEnvTemperatureIdDegF }
::= { lgpEnvTemperatureTableDegF 1 }
LgpEnvTemperatureEntryDegF ::= SEQUENCE
{
lgpEnvTemperatureIdDegF Unsigned32,
lgpEnvTemperatureDescrDegF OBJECT IDENTIFIER,
lgpEnvTemperatureMeasurementDegF Integer32,
lgpEnvTemperatureHighThresholdDegF Integer32,
lgpEnvTemperatureLowThresholdDegF Integer32,
lgpEnvTemperatureSetPointDegF Integer32,
lgpEnvTemperatureDailyHighDegF Integer32,
lgpEnvTemperatureDailyLowDegF Integer32,
lgpEnvTempDailyHighTimeHourDegF Integer32,
lgpEnvTempDailyHighTimeMinuteDegF Integer32,
lgpEnvTempDailyHighTimeSecondDegF Integer32,
lgpEnvTempDailyLowTimeHourDegF Integer32,
lgpEnvTempDailyLowTimeMinuteDegF Integer32,
lgpEnvTempDailyLowTimeSecondDegF Integer32,
lgpEnvTemperatureMeasurementTenthsDegF Integer32,
lgpEnvTemperatureHighThresholdTenthsDegF Integer32,
lgpEnvTemperatureLowThresholdTenthsDegF Integer32,
lgpEnvTemperatureSetPointTenthsDegF Integer32,
lgpEnvTemperatureDeadBandTenthsDegF Integer32,
lgpEnvTempHeatingPropBandTenthsDegF Integer32,
lgpEnvTempCoolingPropBandTenthsDegF Integer32
}
lgpEnvTemperatureIdDegF OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This OID is used as an index to identify a row in the table
'lgpEnvTemperatureTableDegF'."
::= { lgpEnvTemperatureEntryDegF 1 }
lgpEnvTemperatureDescrDegF OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A reference to a temperature description object. The object
referenced should not be accessible, but rather be used to provide
a unique description of the temperature."
::= { lgpEnvTemperatureEntryDegF 2 }
lgpEnvTemperatureMeasurementDegF OBJECT-TYPE
SYNTAX Integer32
UNITS "degrees Fahrenheit"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The measured temperature value."
::= { lgpEnvTemperatureEntryDegF 3 }
lgpEnvTemperatureHighThresholdDegF OBJECT-TYPE
SYNTAX Integer32
UNITS "degrees Fahrenheit"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The high temperature notification threshold. This is the maximum
value of 'lgpEnvTemperatureMeasurementDegF' before the agent sends a
notification."
::= { lgpEnvTemperatureEntryDegF 4 }
lgpEnvTemperatureLowThresholdDegF OBJECT-TYPE
SYNTAX Integer32
UNITS "degrees Fahrenheit"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The low temperature notification threshold. This is the minimum
value of 'lgpEnvTemperatureMeasurementDegF' before the agent sends a
notification."
::= { lgpEnvTemperatureEntryDegF 5 }
lgpEnvTemperatureSetPointDegF OBJECT-TYPE
SYNTAX Integer32
UNITS "degrees Fahrenheit"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The temperature setting for the well known
'lgpEnvTemperatureDescrDegF' point. This setting may or may not be
the setting used from control. Some systems have the capability to
dynamically change the control setting based on environmental
conditions and/or user configuration."
::= { lgpEnvTemperatureEntryDegF 6 }
lgpEnvTemperatureDailyHighDegF OBJECT-TYPE
SYNTAX Integer32
UNITS "degrees Fahrenheit"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The daily high temperature measurement."
::= { lgpEnvTemperatureEntryDegF 7 }
lgpEnvTemperatureDailyLowDegF OBJECT-TYPE
SYNTAX Integer32
UNITS "degrees Fahrenheit"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The daily low temperature measurement."
::= { lgpEnvTemperatureEntryDegF 8 }
lgpEnvTempDailyHighTimeHourDegF OBJECT-TYPE
SYNTAX Integer32(0..23)
UNITS "hours"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The hours digit of the time corresponding to the daily high
temperature measurement."
::= { lgpEnvTemperatureEntryDegF 9 }
lgpEnvTempDailyHighTimeMinuteDegF OBJECT-TYPE
SYNTAX Integer32(0..59)
UNITS "minutes"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The minutes digit of the time corresponding to the daily high
temperature measurement."
::= { lgpEnvTemperatureEntryDegF 10 }
lgpEnvTempDailyHighTimeSecondDegF OBJECT-TYPE
SYNTAX Integer32(0..59)
UNITS "seconds"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The seconds digit of the time corresponding to the daily high
temperature measurement."
::= { lgpEnvTemperatureEntryDegF 11 }
lgpEnvTempDailyLowTimeHourDegF OBJECT-TYPE
SYNTAX Integer32(0..23)
UNITS "hours"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The hours digit of the time corresponding to the daily low
temperature measurement."
::= { lgpEnvTemperatureEntryDegF 12 }
lgpEnvTempDailyLowTimeMinuteDegF OBJECT-TYPE
SYNTAX Integer32(0..59)
UNITS "minutes"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The minutes digit of the time corresponding to the daily low
temperature measurement."
::= { lgpEnvTemperatureEntryDegF 13 }
lgpEnvTempDailyLowTimeSecondDegF OBJECT-TYPE
SYNTAX Integer32(0..59)
UNITS "seconds"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The seconds digit of the time corresponding to the daily low
temperature measurement."
::= { lgpEnvTemperatureEntryDegF 14 }
lgpEnvTemperatureMeasurementTenthsDegF OBJECT-TYPE
SYNTAX Integer32
UNITS ".1 degrees Fahrenheit"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The measured temperature value."
::= { lgpEnvTemperatureEntryDegF 50 }
lgpEnvTemperatureHighThresholdTenthsDegF OBJECT-TYPE
SYNTAX Integer32
UNITS ".1 degrees Fahrenheit"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The high temperature notification threshold. This is the maximum
value of 'lgpEnvTemperatureMeasurementTenthsDegF' before the agent sends a
notification."
::= { lgpEnvTemperatureEntryDegF 51 }
lgpEnvTemperatureLowThresholdTenthsDegF OBJECT-TYPE
SYNTAX Integer32
UNITS ".1 degrees Fahrenheit"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The low temperature notification threshold. This is the minimum
value of 'lgpEnvTemperatureMeasurementTenthsDegF' before the agent sends a
notification."
::= { lgpEnvTemperatureEntryDegF 52 }
lgpEnvTemperatureSetPointTenthsDegF OBJECT-TYPE
SYNTAX Integer32
UNITS ".1 degrees Fahrenheit"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The temperature setting for the well known
'lgpEnvTemperatureDescrDegF' point. This setting may or may not be
the setting used from control. Some systems have the capability to
dynamically change the control setting based on environmental
conditions and/or user configuration."
::= { lgpEnvTemperatureEntryDegF 53 }
lgpEnvTemperatureDeadBandTenthsDegF OBJECT-TYPE
SYNTAX Integer32
UNITS ".1 degrees Fahrenheit"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The deadband region around the setpoint value
(lgpEnvTemperatureSetPointTenthsDegF) where no heating or cooling will occur."
::= { lgpEnvTemperatureEntryDegF 60 }
lgpEnvTempHeatingPropBandTenthsDegF OBJECT-TYPE
SYNTAX Integer32
UNITS ".1 degrees Fahrenheit"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The proportional region below the setpoint value
(lgpEnvTemperatureSetPointTenthsDegF) where heating will be
proportionally controlled."
::= { lgpEnvTemperatureEntryDegF 61 }
lgpEnvTempCoolingPropBandTenthsDegF OBJECT-TYPE
SYNTAX Integer32
UNITS ".1 degrees Fahrenheit"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The proportional region above the setpoint value
(lgpEnvTemperatureSetPointTenthsDegF) where cooling will be
proportionally controlled."
::= { lgpEnvTemperatureEntryDegF 62 }
-- =============================================================================
-- lgpEnvTemperatureCelsius - Liebert Environmental Celsius
-- Temperature Group
-- =============================================================================
lgpEnvTemperatureSettingDegC OBJECT-TYPE
SYNTAX Integer32
UNITS "degrees Celsius"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The temperature setting used to control the well known temperature
object 'lgpEnvControlTemperature'. This setting is cloned in
'lgpEnvTemperatureSettingDegF' with the value converted to Fahrenheit."
::= { lgpEnvTemperatureCelsius 1 }
lgpEnvTemperatureToleranceDegC OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Celsius"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The acceptable variance from 'lgpEnvTemperatureSettingDegC', without
initiating a control action. This setting is cloned in
'lgpEnvTemperatureToleranceDegF' with the value converted to Fahrenheit."
::= { lgpEnvTemperatureCelsius 2 }
lgpEnvTemperatureTableDegC OBJECT-TYPE
SYNTAX SEQUENCE OF LgpEnvTemperatureEntryDegC
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of temperature table entries. The table contains zero, one,
or many rows, depending upon the number of temperature objects
available. The NMS cannot create or delete rows from the table. The
rows are created by the agent based upon the capabilities of the
managed device. The entries in this table are cloned in
'lgpEnvTemperatureTableDegF' where Celsius values are converted to
Fahrenheit."
::= { lgpEnvTemperatureCelsius 3 }
lgpEnvTemperatureDeadbandRangeDegC OBJECT-TYPE
SYNTAX Integer32
UNITS ".1 degrees Celsius"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The allowable deviation above and below the temperature set point
used to create a no control region, a dead-band, where heating
and cooling control are disabled."
::= { lgpEnvTemperatureCelsius 4 }
lgpEnvTemperatureEntryDegC OBJECT-TYPE
SYNTAX LgpEnvTemperatureEntryDegC
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This entry defines the contents of the rows for the table
'lgpEnvTemperatureTableDegC'."
INDEX { lgpEnvTemperatureIdDegC }
::= { lgpEnvTemperatureTableDegC 1 }
LgpEnvTemperatureEntryDegC ::= SEQUENCE
{
lgpEnvTemperatureIdDegC Unsigned32,
lgpEnvTemperatureDescrDegC OBJECT IDENTIFIER,
lgpEnvTemperatureMeasurementDegC Integer32,
lgpEnvTemperatureHighThresholdDegC Integer32,
lgpEnvTemperatureLowThresholdDegC Integer32,
lgpEnvTemperatureSetPointDegC Integer32,
lgpEnvTemperatureDailyHighDegC Integer32,
lgpEnvTemperatureDailyLowDegC Integer32,
lgpEnvTempDailyHighTimeHourDegC Integer32,
lgpEnvTempDailyHighTimeMinuteDegC Integer32,
lgpEnvTempDailyHighTimeSecondDegC Integer32,
lgpEnvTempDailyLowTimeHourDegC Integer32,
lgpEnvTempDailyLowTimeMinuteDegC Integer32,
lgpEnvTempDailyLowTimeSecondDegC Integer32,
lgpEnvTemperatureMeasurementTenthsDegC Integer32,
lgpEnvTemperatureHighThresholdTenthsDegC Integer32,
lgpEnvTemperatureLowThresholdTenthsDegC Integer32,
lgpEnvTemperatureSetPointTenthsDegC Integer32,
lgpEnvTemperatureDeadBandTenthsDegC Integer32,
lgpEnvTempHeatingPropBandTenthsDegC Integer32,
lgpEnvTempCoolingPropBandTenthsDegC Integer32
}
lgpEnvTemperatureIdDegC OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This OID is used as an index to identify a row in the table
'lgpEnvTemperatureTableDegC'."
::= { lgpEnvTemperatureEntryDegC 1 }
lgpEnvTemperatureDescrDegC OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A reference to a temperature description object. The object
referenced should not be accessible, but rather be used to provide
a unique description of the temperature."
::= { lgpEnvTemperatureEntryDegC 2 }
lgpEnvTemperatureMeasurementDegC OBJECT-TYPE
SYNTAX Integer32
UNITS "degrees Celsius"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The measured temperature value."
::= { lgpEnvTemperatureEntryDegC 3 }
lgpEnvTemperatureHighThresholdDegC OBJECT-TYPE
SYNTAX Integer32
UNITS "degrees Celsius"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The high temperature notification threshold. This is the maximum
value of 'lgpEnvTemperatureMeasurementDegC' before the agent sends a
notification."
::= { lgpEnvTemperatureEntryDegC 4 }
lgpEnvTemperatureLowThresholdDegC OBJECT-TYPE
SYNTAX Integer32
UNITS "degrees Celsius"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The low temperature notification threshold. This is the minimum
value of 'lgpEnvTemperatureMeasurementDegC' before the agent sends a
notification."
::= { lgpEnvTemperatureEntryDegC 5 }
lgpEnvTemperatureSetPointDegC OBJECT-TYPE
SYNTAX Integer32
UNITS "degrees Celsius"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The temperature setting for the well known
'lgpEnvTemperatureDescrDegC' point. This setting may or may not be
the setting used from control. Some systems have the capability to
dynamically change the control setting based on environmental
conditions and/or user configuration."
::= { lgpEnvTemperatureEntryDegC 6 }
lgpEnvTemperatureDailyHighDegC OBJECT-TYPE
SYNTAX Integer32
UNITS "degrees Celsius"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The daily high temperature measurement."
::= { lgpEnvTemperatureEntryDegC 7 }
lgpEnvTemperatureDailyLowDegC OBJECT-TYPE
SYNTAX Integer32
UNITS "degrees Celsius"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The daily low temperature measurement."
::= { lgpEnvTemperatureEntryDegC 8 }
lgpEnvTempDailyHighTimeHourDegC OBJECT-TYPE
SYNTAX Integer32(0..23)
UNITS "hours"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The hours digit of the time corresponding to the daily high
temperature measurement."
::= { lgpEnvTemperatureEntryDegC 9 }
lgpEnvTempDailyHighTimeMinuteDegC OBJECT-TYPE
SYNTAX Integer32(0..59)
UNITS "minutes"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The minutes digit of the time corresponding to the daily high
temperature measurement."
::= { lgpEnvTemperatureEntryDegC 10 }
lgpEnvTempDailyHighTimeSecondDegC OBJECT-TYPE
SYNTAX Integer32(0..59)
UNITS "seconds"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The seconds digit of the time corresponding to the daily high
temperature measurement."
::= { lgpEnvTemperatureEntryDegC 11 }
lgpEnvTempDailyLowTimeHourDegC OBJECT-TYPE
SYNTAX Integer32(0..23)
UNITS "hours"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The hours digit of the time corresponding to the daily low
temperature measurement."
::= { lgpEnvTemperatureEntryDegC 12 }
lgpEnvTempDailyLowTimeMinuteDegC OBJECT-TYPE
SYNTAX Integer32(0..59)
UNITS "minutes"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The minutes digit of the time corresponding to the daily low
temperature measurement."
::= { lgpEnvTemperatureEntryDegC 13 }
lgpEnvTempDailyLowTimeSecondDegC OBJECT-TYPE
SYNTAX Integer32(0..59)
UNITS "seconds"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The seconds digit of the time corresponding to the daily low
temperature measurement."
::= { lgpEnvTemperatureEntryDegC 14 }
lgpEnvTemperatureMeasurementTenthsDegC OBJECT-TYPE
SYNTAX Integer32
UNITS ".1 degrees Celsius"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The measured temperature value."
::= { lgpEnvTemperatureEntryDegC 50 }
lgpEnvTemperatureHighThresholdTenthsDegC OBJECT-TYPE
SYNTAX Integer32
UNITS ".1 degrees Celsius"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The high temperature notification threshold. This is the maximum
value of 'lgpEnvTemperatureMeasurementTenthsDegC' before the agent sends a
notification."
::= { lgpEnvTemperatureEntryDegC 51 }
lgpEnvTemperatureLowThresholdTenthsDegC OBJECT-TYPE
SYNTAX Integer32
UNITS ".1 degrees Celsius"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The low temperature notification threshold. This is the minimum
value of 'lgpEnvTemperatureMeasurementTenthsDegC' before the agent sends a
notification."
::= { lgpEnvTemperatureEntryDegC 52 }
lgpEnvTemperatureSetPointTenthsDegC OBJECT-TYPE
SYNTAX Integer32
UNITS ".1 degrees Celsius"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The temperature setting for the well known
'lgpEnvTemperatureDescrDegC' point. This setting may or may not be
the setting used from control. Some systems have the capability to
dynamically change the control setting based on environmental
conditions and/or user configuration."
::= { lgpEnvTemperatureEntryDegC 53 }
lgpEnvTemperatureDeadBandTenthsDegC OBJECT-TYPE
SYNTAX Integer32
UNITS ".1 degrees Celsius"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The deadband region around the setpoint value
(lgpEnvTemperatureSetPointTenthsDegC) where no heating or cooling will occur."
::= { lgpEnvTemperatureEntryDegC 60 }
lgpEnvTempHeatingPropBandTenthsDegC OBJECT-TYPE
SYNTAX Integer32
UNITS ".1 degrees Celsius"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The proportional region below the setpoint value
(lgpEnvTemperatureSetPointTenthsDegC) where heating will be
proportionally controlled."
::= { lgpEnvTemperatureEntryDegC 61 }
lgpEnvTempCoolingPropBandTenthsDegC OBJECT-TYPE
SYNTAX Integer32
UNITS ".1 degrees Celsius"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The proportional region above the setpoint value
(lgpEnvTemperatureSetPointTenthsDegC) where cooling will be
proportionally controlled."
::= { lgpEnvTemperatureEntryDegC 62 }
-- =============================================================================
-- lgpEnvHumidityMeasurements - Liebert "well-known" Humidity objects
-- =============================================================================
lgpEnvControlHumidity OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Humidity measurement used as control feedback."
::= { lgpEnvHumidityWellKnown 1 }
lgpEnvReturnAirHumidity OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Humidity measurement of return air."
::= { lgpEnvHumidityWellKnown 2 }
lgpEnvSupplyAirHumidity OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Humidity measurement of supply air."
::= { lgpEnvHumidityWellKnown 3 }
lgpEnvValueAmbientHumidity OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Humidity outside enclosure."
::= { lgpEnvHumidityWellKnown 4 }
-- =============================================================================
-- lgpEnvRelativeHumidity - Liebert Environmental Relative Humidity Group
-- =============================================================================
lgpEnvHumiditySettingRel OBJECT-TYPE
SYNTAX Integer32
UNITS "percent Relative Humidity"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The humidity setting used to control the well known humidity
point."
::= { lgpEnvHumidityRelative 1 }
lgpEnvHumidityToleranceRel OBJECT-TYPE
SYNTAX Integer32
UNITS "percent Relative Humidity"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Acceptable variance from lgpEnvHumiditySettingRel, without
initiating a control action."
::= { lgpEnvHumidityRelative 2 }
lgpEnvHumidityTableRel OBJECT-TYPE
SYNTAX SEQUENCE OF LgpEnvHumidityEntryRel
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of humidity table entries. The table contains zero, one,
or many rows, depending upon the number of humidity objects available.
The NMS cannot create or delete rows from the table. The rows are
created by the agent based upon the capabilities of the managed device."
::= { lgpEnvHumidityRelative 3 }
lgpEnvHumidityDeadbandRange OBJECT-TYPE
SYNTAX Integer32
UNITS ".1 percent RH"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The allowable deviation above and below the humidity set point used
to create a no control region, a dead-band, where humidifying and
dehumidifying control are disabled."
::= { lgpEnvHumidityRelative 4 }
lgpEnvHumidityEntryRel OBJECT-TYPE
SYNTAX LgpEnvHumidityEntryRel
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This entry defines the contents of the rows for the table
'lgpEnvHumidityTableRel'."
INDEX { lgpEnvHumidityIdRel }
::= { lgpEnvHumidityTableRel 1 }
LgpEnvHumidityEntryRel ::= SEQUENCE
{
lgpEnvHumidityIdRel Unsigned32,
lgpEnvHumidityDescrRel OBJECT IDENTIFIER,
lgpEnvHumidityMeasurementRel Integer32,
lgpEnvHumidityHighThresholdRel Integer32,
lgpEnvHumidityLowThresholdRel Integer32,
lgpEnvHumiditySetPoint Integer32,
lgpEnvHumidityDailyHigh Integer32,
lgpEnvHumidityDailyLow Integer32,
lgpEnvHumidityDailyHighTimeHour Integer32,
lgpEnvHumidityDailyHighTimeMinute Integer32,
lgpEnvHumidityDailyHighTimeSecond Integer32,
lgpEnvHumidityDailyLowTimeHour Integer32,
lgpEnvHumidityDailyLowTimeMinute Integer32,
lgpEnvHumidityDailyLowTimeSecond Integer32,
lgpEnvHumidityDeadBand Integer32,
lgpEnvHumidifyPropBand Integer32,
lgpEnvDehumidifyPropBand Integer32,
lgpEnvHumidityMeasurementRelTenths Integer32,
lgpEnvHumidityHighThresholdRelTenths Integer32,
lgpEnvHumidityLowThresholdRelTenths Integer32
}
lgpEnvHumidityIdRel OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This OID is used as an index to identify a row in the table
'lgpEnvHumidityTableRel'."
::= { lgpEnvHumidityEntryRel 1 }
lgpEnvHumidityDescrRel OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A reference to a humidity description object. The object
referenced should not be accessible, but rather be used
to provide a unique description of the humidity."
::= { lgpEnvHumidityEntryRel 2 }
lgpEnvHumidityMeasurementRel OBJECT-TYPE
SYNTAX Integer32
UNITS "percent Relative Humidity"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The measured humidity value."
::= { lgpEnvHumidityEntryRel 3 }
lgpEnvHumidityHighThresholdRel OBJECT-TYPE
SYNTAX Integer32
UNITS "percent Relative Humidity"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The high humidity notification threshold. This is the maximum
value of 'lgpEnvHumidityMeasurementRel' before the agent sends a
notification."
::= { lgpEnvHumidityEntryRel 4 }
lgpEnvHumidityLowThresholdRel OBJECT-TYPE
SYNTAX Integer32
UNITS "percent Relative Humidity"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The low humidity notification threshold. This is the minimum
value of 'lgpEnvHumidityMeasurementRel' before the agent sends a
notification."
::= { lgpEnvHumidityEntryRel 5 }
lgpEnvHumiditySetPoint OBJECT-TYPE
SYNTAX Integer32
UNITS "percent Relative Humidity"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The humidity setting used to control the well known humidity
object 'lgpEnvHumidityDescrRel'. This setting may or may not be
the setting used from control. Some systems have the capability to
dynamically change the control setting based on environmental
conditions and/or user configuration."
::= { lgpEnvHumidityEntryRel 6 }
lgpEnvHumidityDailyHigh OBJECT-TYPE
SYNTAX Integer32
UNITS "percent Relative Humidity"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The daily high relative humidity measurement."
::= { lgpEnvHumidityEntryRel 7 }
lgpEnvHumidityDailyLow OBJECT-TYPE
SYNTAX Integer32
UNITS "percent Relative Humidity"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The daily low relative humidity measurement."
::= { lgpEnvHumidityEntryRel 8 }
lgpEnvHumidityDailyHighTimeHour OBJECT-TYPE
SYNTAX Integer32(0..23)
UNITS "hours"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The hours digit of the time corresponding to the daily high
humidity measurement."
::= { lgpEnvHumidityEntryRel 9 }
lgpEnvHumidityDailyHighTimeMinute OBJECT-TYPE
SYNTAX Integer32(0..59)
UNITS "minutes"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The minutes digit of the time corresponding to the daily high
humidity measurement."
::= { lgpEnvHumidityEntryRel 10 }
lgpEnvHumidityDailyHighTimeSecond OBJECT-TYPE
SYNTAX Integer32(0..59)
UNITS "seconds"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The seconds digit of the time corresponding to the daily high
humidity measurement."
::= { lgpEnvHumidityEntryRel 11 }
lgpEnvHumidityDailyLowTimeHour OBJECT-TYPE
SYNTAX Integer32(0..23)
UNITS "hours"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The hours digit of the time corresponding to the daily low humidity measurement."
::= { lgpEnvHumidityEntryRel 12 }
lgpEnvHumidityDailyLowTimeMinute OBJECT-TYPE
SYNTAX Integer32(0..59)
UNITS "minutes"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The minutes digit of the time corresponding to the daily low
humidity measurement."
::= { lgpEnvHumidityEntryRel 13 }
lgpEnvHumidityDailyLowTimeSecond OBJECT-TYPE
SYNTAX Integer32(0..59)
UNITS "seconds"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The seconds digit of the time corresponding to the daily low humidity measurement."
::= { lgpEnvHumidityEntryRel 14 }
lgpEnvHumidityDeadBand OBJECT-TYPE
SYNTAX Integer32
UNITS "percent Relative Humidity"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The deadband region around the setpoint value
(lgpEnvHumiditySetPoint) where no humidifying or dehumidifying will occur."
::= { lgpEnvHumidityEntryRel 15 }
lgpEnvHumidifyPropBand OBJECT-TYPE
SYNTAX Integer32
UNITS "percent Relative Humidity"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The proportional region below the setpoint value
(lgpEnvHumiditySetPoint) where humidifying will be
proportionally controlled."
::= { lgpEnvHumidityEntryRel 16 }
lgpEnvDehumidifyPropBand OBJECT-TYPE
SYNTAX Integer32
UNITS "percent Relative Humidity"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The proportional region above the setpoint value
(lgpEnvHumiditySetPoint) where dehumidifying will be
proportionally controlled."
::= { lgpEnvHumidityEntryRel 17 }
lgpEnvHumidityMeasurementRelTenths OBJECT-TYPE
SYNTAX Integer32
UNITS ".1 percent Relative Humidity"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The measured humidity value."
::= { lgpEnvHumidityEntryRel 50 }
lgpEnvHumidityHighThresholdRelTenths OBJECT-TYPE
SYNTAX Integer32
UNITS ".1 percent Relative Humidity"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The high humidity notification threshold. This is the maximum
value of 'lgpEnvHumidityMeasurementRelTenths' before the agent sends a
notification."
::= { lgpEnvHumidityEntryRel 51 }
lgpEnvHumidityLowThresholdRelTenths OBJECT-TYPE
SYNTAX Integer32
UNITS ".1 percent Relative Humidity"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The low humidity notification threshold. This is the minimum
value of 'lgpEnvHumidityMeasurementRelTenths' before the agent sends a
notification."
::= { lgpEnvHumidityEntryRel 52 }
-- =============================================================================
-- lgpEnvRemoteSensors - Liebert Environmental Remote Sensor Group
-- =============================================================================
lgpEnvRemoteSensorCalc OBJECT-TYPE
SYNTAX INTEGER
{
average(1),
maximum(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Calculation method applied to temperature readings from the remote
sensors to determine a single temperature measurement value for
cooling and heating control."
::= { lgpEnvRemoteSensors 1 }
lgpEnvRemoteSensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF LgpEnvRemoteSensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains a list of remote sensors attached to the
environmental unit. The table contains zero, one, or more rows,
depending upon the number of sensors attached to the unit."
::= { lgpEnvRemoteSensors 10 }
lgpEnvRemoteSensorEntry OBJECT-TYPE
SYNTAX LgpEnvRemoteSensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This entry defines the attributes to be populated in the
various columns of the 'lgpEnvRemoteSensorTable'."
INDEX
{
lgpEnvRemoteSensorIndex
}
::= { lgpEnvRemoteSensorTable 1 }
LgpEnvRemoteSensorEntry ::= SEQUENCE
{
lgpEnvRemoteSensorIndex Unsigned32,
lgpEnvRemoteSensorId Unsigned32,
lgpEnvRemoteSensorMode Integer32,
lgpEnvRemoteSensorUsrLabel DisplayString,
lgpEnvRemoteSensorTempMeasurementDegF Integer32,
lgpEnvRemoteSensorTempMeasurementDegC Integer32
}
lgpEnvRemoteSensorIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This is the index indicating the nth element of the table."
::= { lgpEnvRemoteSensorEntry 1 }
lgpEnvRemoteSensorId OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This is the sensor number identifying the sensor."
::= { lgpEnvRemoteSensorEntry 2 }
lgpEnvRemoteSensorMode OBJECT-TYPE
SYNTAX INTEGER
{
disable(0),
reference(1),
control(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Function assigned to remote sensor. When set to control(2) the
sensor will be used in calculation of remote sensor temperature which
may be used for heating and cooling control. When set to disable(0)
the remote sensor reading is not available. When set to reference(1)
the remote sensor reading is available but not used for control."
::= { lgpEnvRemoteSensorEntry 3 }
lgpEnvRemoteSensorUsrLabel OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User assigned remote sensor label."
::= { lgpEnvRemoteSensorEntry 4 }
lgpEnvRemoteSensorTempMeasurementDegF OBJECT-TYPE
SYNTAX Integer32
UNITS "degrees Fahrenheit"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Temperature measured at the temperature sensor reported in
degrees Fahrenheit."
::= { lgpEnvRemoteSensorEntry 5 }
lgpEnvRemoteSensorTempMeasurementDegC OBJECT-TYPE
SYNTAX Integer32
UNITS "degrees Celsius"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Temperature measured at the temperature sensor reported in
degrees Celsius."
::= { lgpEnvRemoteSensorEntry 6 }
END