mibs/MIBS/liebert/LIEBERT-GP-NOTIFY-MIB
2023-12-05 12:25:34 +01:00

398 lines
14 KiB
Plaintext

LIEBERT-GP-NOTIFICATIONS-MIB DEFINITIONS ::= BEGIN
IMPORTS
sysUpTime
FROM RFC1213-MIB
MODULE-IDENTITY,
OBJECT-IDENTITY,
OBJECT-TYPE,
NOTIFICATION-TYPE
FROM SNMPv2-SMI
lgpNotifications,
liebertNotificationsModuleReg
FROM LIEBERT-GP-REGISTRATION-MIB
lgpConditionId,
lgpConditionDescr,
lgpConditionTime,
lgpConditionTableRef,
lgpConditionTableRowRef
FROM LIEBERT-GP-CONDITIONS-MIB
;
-- =============================================================================
-- Module Identification and Registration
-- =============================================================================
liebertGlobalProductsNotificationsModule MODULE-IDENTITY
LAST-UPDATED "200807020000Z"
ORGANIZATION "Liebert Corporation"
CONTACT-INFO
"Contact: Technical Support
Postal:
Liebert Corporation
1050 Dearborn Drive
P.O. Box 29186
Columbus OH, 43229
US
Tel: +1 (800) 222-5877
E-mail: liebert.monitoring@vertivco.com
Web: www.vertivco.com
Author: Craig S. Ward"
DESCRIPTION
"The MIB module used to register Liebert SNMP OIDs.
Copyright 2000-2008 Liebert Corporation. All rights reserved.
Reproduction of this document is authorized on the condition
that the forgoing copyright notice is included.
This Specification is supplied 'AS IS' and Liebert Corporation
makes no warranty, either express or implied, as to the use,
operation, condition, or performance of the Specification."
REVISION "200807020000Z"
DESCRIPTION
" o Added Notifications for PDU devices (power on/off).
o Added lgpEventParameters branch for defining notification payload
that specifically identifies objects that are contained in tables.
o Added new varbind to the lgpEventConditionEntryAdded and
lgpEventConditionEntryRemoved notifications.
o Fixed minor SMIv2 warnings and issues
"
REVISION "200805150000Z"
DESCRIPTION
" o Added Notifications for PDU devices (power on/off).
o Added lgpEventParameters branch for defining notification payload
that specifically identifies objects that are contained in tables.
o Added new varbind to the lgpEventConditionEntryAdded and
lgpEventConditionEntryRemoved notifications.
o Fixed minor SMIv2 warnings and issues
"
REVISION "200801100000Z"
DESCRIPTION
"Modified contact email address and deprecated both:
o lgpEventAgentFirmwareUpdateSuccessful
o lgpEventAgentFirmwareCorrupt
which were moved to the LIEBERT-GP-AGENT-MIB document."
REVISION "200608150000Z"
DESCRIPTION
"Added events for firmware update successful and for firmware corrupt."
REVISION "200602220000Z"
DESCRIPTION
"Added support for Liebert DS Unit."
::= { liebertNotificationsModuleReg 1 }
-- =============================================================================
-- lgpNotifications - Liebert Notifications Registrations
-- =============================================================================
lgpEventNotifications OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Notifications for Liebert Global Products."
::= { lgpNotifications 0 }
lgpEventParameters OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub tree describes various parameters/data that are carried
in the payload of some notifications."
::= { lgpNotifications 10 }
lgpEventParmTableRef OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This object will be included as a varbind in some
lgpEventNotifications. It is a reference to a table object in
the MIB. The value of this object will be the OID of a table
that the object that the notification applies to is defined.
The notification containing this object will also contain
a varbind 'lgpEventParmTableRowRef' that will specify which
instance (row) in the table the object is defined in.
Example:
NOTIFICATION: lgpEventConditionEntryAdded
varbind: lgpConditionId 6
varbind: lgpConditionDescr lgpConditionRcpBranchBreakerOpen
varbind: lgpConditionTime 393884848
varbind: lgpEventParmTableRef lgpPduRbTable
varbind: lgpEventParmTableRowRef lgpPduRbEntryId.1.4
In the above example the breaker opened for a Receptacle branch.
The specific receptacle branch is specified by the additional
varbind (lgpEventParmTableRowRef). In this case the notification
is for the 4th receptacle branch on the 1st PDU in the PDU cluster.
"
::= { lgpEventParameters 5 }
lgpEventParmTableRowRef OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This is a reference to the intersection of a row and column (cell)
in the table specified by the companion varbind
(lgpEventParmTableRef) in this notification. The row in the
table where this cell exists represents the object that this
notification applies to.
Example:
NOTIFICATION: lgpEventRcpPowerStateChangeOff
varbind: sysUpTime 393885975
varbind: lgpEventParmTableRef lgpPduRcpTable
varbind: lgpEventParmTableRowRef lgpPduRcpEntryId.2.4.5
In the above example the power state changed for a Receptacle.
The table containing the definition of the receptacle
(lgpPduRcpTable) is given by the varbind (lgpEventParmTableRef)
The specific receptacle is specified by the varbind
(lgpEventParmTableRowRef). In this case the notification
is for the 5th receptacle on the 4th receptacle branch on the
2nd PDU in the PDU cluster.
If one wanted to retrieve the user assigned label for this
receptacle the OID would be: lgpPduRcpEntryUsrLabel.2.4.5
"
::= { lgpEventParameters 6 }
lgpEventConditionEntryAdded NOTIFICATION-TYPE
OBJECTS { lgpConditionId,
lgpConditionDescr,
lgpConditionTime,
lgpConditionTableRef,
lgpConditionTableRowRef
}
STATUS current
DESCRIPTION
"This notification is sent each time a condition is inserted into the
conditions table."
::= { lgpEventNotifications 1 }
lgpEventConditionEntryRemoved NOTIFICATION-TYPE
OBJECTS { lgpConditionId,
lgpConditionDescr,
lgpConditionTime,
lgpConditionTableRef,
lgpConditionTableRowRef
}
STATUS current
DESCRIPTION
"This notification is sent each time a condition is removed from the
conditions table."
::= { lgpEventNotifications 2 }
lgpEventLowBatteryWarning NOTIFICATION-TYPE
OBJECTS { sysUpTime }
STATUS current
DESCRIPTION
"The battery's remaining charge is less than or equal to the agent's
configured low threshold 'lgpPwrConfigLowBatteryWarningTime'."
::= { lgpEventNotifications 3 }
lgpEventLoadTransferedToBypass NOTIFICATION-TYPE
OBJECTS { sysUpTime }
STATUS current
DESCRIPTION
"The device has transferred the load to the bypass source."
::= { lgpEventNotifications 4 }
lgpEventInternalFault NOTIFICATION-TYPE
OBJECTS { sysUpTime }
STATUS current
DESCRIPTION
"The device has reported an internal fault."
::= { lgpEventNotifications 5 }
lgpEventBatteryTestFailed NOTIFICATION-TYPE
OBJECTS { sysUpTime }
STATUS current
DESCRIPTION
"The device has reported a battery self-test failure."
::= { lgpEventNotifications 6 }
lgpEventOutputOverload NOTIFICATION-TYPE
OBJECTS { sysUpTime }
STATUS current
DESCRIPTION
"The device has reported an output overload condition."
::= { lgpEventNotifications 7 }
lgpEventEstablishedPowerRedundancy NOTIFICATION-TYPE
OBJECTS { sysUpTime }
STATUS current
DESCRIPTION
"The device has transitioned to the user defined redundant state."
::= { lgpEventNotifications 8 }
lgpEventLostPowerRedundancy NOTIFICATION-TYPE
OBJECTS { sysUpTime }
STATUS current
DESCRIPTION
"The device as transitioned to a non-redundant power state as defined
by the user configured threshold."
::= { lgpEventNotifications 9 }
lgpEventPowerModuleFailure NOTIFICATION-TYPE
OBJECTS { sysUpTime }
STATUS current
DESCRIPTION
"Device power module failure."
::= { lgpEventNotifications 10 }
lgpEventBatteryModuleFailure NOTIFICATION-TYPE
OBJECTS { sysUpTime }
STATUS current
DESCRIPTION
"Device battery module failure."
::= { lgpEventNotifications 11 }
lgpEventControlModuleFailure NOTIFICATION-TYPE
OBJECTS { sysUpTime }
STATUS current
DESCRIPTION
"Device control module failure."
::= { lgpEventNotifications 12 }
lgpEventPowerModuleWarning NOTIFICATION-TYPE
OBJECTS { sysUpTime }
STATUS current
DESCRIPTION
"Device power module warning."
::= { lgpEventNotifications 13 }
lgpEventBatteryModuleWarning NOTIFICATION-TYPE
OBJECTS { sysUpTime }
STATUS current
DESCRIPTION
"Device battery module warning."
::= { lgpEventNotifications 14 }
lgpEventControlModuleWarning NOTIFICATION-TYPE
OBJECTS { sysUpTime }
STATUS current
DESCRIPTION
"Device control module warning."
::= { lgpEventNotifications 15 }
lgpEventAgentFirmwareUpdateSuccessful NOTIFICATION-TYPE
OBJECTS { sysUpTime }
STATUS deprecated
DESCRIPTION
"The firmware update to the agent card has completed successfully.
This element has been relocated to lgpAgentFirmwareUpdateSuccessful
in the LIEBERT-GP-AGENT-MIB document."
::= { lgpEventNotifications 16 }
lgpEventAgentFirmwareCorrupt NOTIFICATION-TYPE
OBJECTS { sysUpTime }
STATUS deprecated
DESCRIPTION
"The firmware update to the agent card has failed and the firmware is
now corrupt.
This element has been relocated to lgpAgentFirmwareCorrupt
in the LIEBERT-GP-AGENT-MIB document."
::= { lgpEventNotifications 17 }
lgpEventConfigModified NOTIFICATION-TYPE
OBJECTS {
sysUpTime,
lgpEventParmTableRef,
lgpEventParmTableRowRef
}
STATUS current
DESCRIPTION
"Configuration for the referenced PDU has been modified."
::= { lgpEventNotifications 18 }
lgpEventModuleAdded NOTIFICATION-TYPE
OBJECTS {
sysUpTime,
lgpEventParmTableRef,
lgpEventParmTableRowRef
}
STATUS current
DESCRIPTION
"A hot-swappable module has been added to the object specified by the
lgpEventParmTableRef and lgpEventParmTableRowRef."
::= { lgpEventNotifications 19 }
lgpEventModuleRemoved NOTIFICATION-TYPE
OBJECTS {
sysUpTime,
lgpEventParmTableRef,
lgpEventParmTableRowRef
}
STATUS current
DESCRIPTION
"A hot-swappable module has been removed from the object specified by
the lgpEventParmTableRef and lgpEventParmTableRowRef."
::= { lgpEventNotifications 20 }
lgpEventRcpPowerStateChangeOn NOTIFICATION-TYPE
OBJECTS {
sysUpTime,
lgpEventParmTableRef,
lgpEventParmTableRowRef
}
STATUS current
DESCRIPTION
"Receptacle's power state has been changed from OFF to ON."
::= { lgpEventNotifications 21 }
lgpEventRcpPowerStateChangeOff NOTIFICATION-TYPE
OBJECTS {
sysUpTime,
lgpEventParmTableRef,
lgpEventParmTableRowRef
}
STATUS current
DESCRIPTION
"Receptacle's power state has been changed from ON to OFF."
::= { lgpEventNotifications 22 }
lgpEventRcpLoadAdded NOTIFICATION-TYPE
OBJECTS {
sysUpTime,
lgpEventParmTableRef,
lgpEventParmTableRowRef
}
STATUS current
DESCRIPTION
"The receptacle's load started drawing power. This notification
is asserted when the receptacle power is ON and the associated load
was previously not drawing power but is now drawing power.
This event is not asserted as a result of turning the
receptacle power ON."
::= { lgpEventNotifications 23 }
lgpEventRcpLoadRemoved NOTIFICATION-TYPE
OBJECTS {
sysUpTime,
lgpEventParmTableRef,
lgpEventParmTableRowRef
}
STATUS current
DESCRIPTION
"The receptacle's load stopped drawing power. This notification
is asserted when the receptacle power is ON and the associated load
was previously drawing power but is now no longer drawing power.
This event is not asserted as a result of turning the
receptacle power OFF."
::= { lgpEventNotifications 24 }
END