mibs/MIBS/liebert/LIEBERT-GP-PDU-MIB
2023-12-05 12:25:34 +01:00

3658 lines
146 KiB
Plaintext
Raw Blame History

LIEBERT-GP-PDU-MIB DEFINITIONS ::= BEGIN
IMPORTS
DisplayString
FROM SNMPv2-TC
MODULE-IDENTITY,
OBJECT-IDENTITY,
OBJECT-TYPE,
Integer32,
Unsigned32
FROM SNMPv2-SMI
lgpPdu,
liebertPduModuleReg
FROM LIEBERT-GP-REGISTRATION-MIB
;
-- =============================================================================
-- Module Identification and Registration
-- =============================================================================
liebertGlobalProductsPduModule MODULE-IDENTITY
LAST-UPDATED "200807020000Z"
ORGANIZATION "Liebert Corporation"
CONTACT-INFO
"Contact: Technical Support
Postal:
Liebert Corporation
1050 Dearborn Drive
P.O. Box 29186
Columbus OH, 43229
US
Tel: +1 (800) 222-5877
E-mail: liebert.monitoring@vertivco.com
Web: www.vertivco.com
Author: Keith Sarbaugh"
DESCRIPTION
"The MIB module used to register Liebert POWER related SNMP OIDs.
Copyright 2008-2008 Liebert Corporation. All rights reserved.
Reproduction of this document is authorized on the condition
that the forgoing copyright notice is included.
This Specification is supplied 'AS IS' and Liebert Corporation
makes no warranty, either express or implied, as to the use,
operation, condition, or performance of the Specification."
REVISION "200807020000Z"
DESCRIPTION
"Initial Version"
::= { liebertPduModuleReg 1 }
-- =============================================================================
-- lgpPdu - Liebert Power Distribution Registrations
-- =============================================================================
-- -----------------------------------------------------------------------------
-- PDU Global Data and Control Information
-- -----------------------------------------------------------------------------
lgpPduGlobalData OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree contains data and control associated with PDU's controlled
by this agent. Data in this sub-tree will affect the behavior of all
PDU's controlled by this agent."
REFERENCE
"The registrations for the objects in this sub-tree are
defined below."
::= { lgpPdu 5 }
lgpPduEntrySWOverTemperatureProtectionConfig OBJECT-TYPE
SYNTAX INTEGER
{
local(0),
array(1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This configures the scope of behavior for the PDU Software Over
Temperature Protection feature.
See lgpPduRcpEntrySwOverTemperatureProtection to enable this feature
and get further information about what actions will be performed.
local (0)
Only receptacles on the PDU with the alarming temperature sensor
will be affected.
array (1)
All receptacles in the PDU array will be affected, regardless of
which PDU the alarming temperature sensor is connected to.
"
::= { lgpPduGlobalData 5 }
lgpPduEntrySWOverTemperatureProtectionDelay OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This sets the delay for the PDU Software Over Temperature Protection
feature. This value determines the amount of time to delay, after the
high temperature alarm becomes active, before taking action on the
enabled receptacles. If the high temperature alarm becomes inactive
before the expiration of the delay time, no action will be taken on
the enabled receptacles.
See lgpPduRcpEntrySwOverTemperatureProtection to enable this feature
and get further information about what actions will be performed.
"
::= { lgpPduGlobalData 10 }
-- -----------------------------------------------------------------------------
-- PDU Group Information
-- -----------------------------------------------------------------------------
lgpPduCluster OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree contains information about PDU clusters. Clusters are
groups of PDU's under a single monitoring or control domain."
REFERENCE
"The registrations for the objects in this sub-tree are
defined below."
::= { lgpPdu 10 }
lgpPduGrpSysStatus OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This value represents a bit-field of the various operational
states of the PDUs that are part of the cluster of PDUs
being monitored by this agent.
This value is the bit-wise logical OR of all of the
'lgpPduEntrySysStatus' columns in the 'lgpPduTable'
which represents the combined statuses of all PDUs for this agent.
Note the bit-position is given parenthetically next to the operational
state in the description below. The bit position is big-endian
(least significant digit is the right-most digit). The state is
present in the PDU when the bit is on (value = 1).
The value is a logical OR of all of the following potential states of
each PDU in the cluster.
normalOperation(1)
One or more PDUs in the cluster are operating normally with no
active warnings or alarms.
startUp(2)
One or more PDUs are in the startup state (initializing). Control
and monitoring operations may be inhibited or unavailable
while the PDU is in this state. This state will clear
automatically when the PDU(s) are fully initialized and ready to
accept control and monitoring commands.
unknownNoSupport(4)
The state of one or more PDUs are not known at this time or
there is no support for this piece of information from 1 or more
PDUs in the cluster/group.
normalWithWarning(8)
One or more PDUs are operating normally with one or more active
warnings. Appropriate personnel should investigate the
warning(s) as soon as possible and take appropriate action.
normalWithAlarm(16)
One or more PDUs are operating normally with one or more active
alarms. Appropriate personnel should investigate the alarm(s)
as soon as possible and take appropriate action.
abnormalOperation(32)
One ore more PDUs are operating abnormally. There is a
failure within the system that is unexpected under normal
operating conditions. Appropriate personnel should investigate
the cause as soon as possible. The normal functioning of
the system is likely inhibited.
unknownCommFailure(64)
The state of one or more PDUs are not known due to a communications
failure between the PDU hardware and the communications
module. This state is usually indicative of a hardware
problem.
"
::= { lgpPduCluster 5 }
-- -----------------------------------------------------------------------------
-- Power Distribution (PDU) Table.
-- -----------------------------------------------------------------------------
lgpPduTableCount OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Count"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of PDUs being monitored by this agent. This is the
number of entries in the lgpPduTable."
::= { lgpPdu 19 }
lgpPduTable OBJECT-TYPE
SYNTAX SEQUENCE OF LgpPduEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains a list of PDU entries.
The table contains zero, one, or many rows, depending upon the number
of PDUs being monitored. The Network Management System (NMS)
cannot create or delete rows in the table. The rows are created by
the agent based upon the number of PDUs being managed.
Each row in the table represents a PDU in the system."
::= { lgpPdu 20 }
lgpPduEntry OBJECT-TYPE
SYNTAX LgpPduEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This entry defines the columns to be populated in the
'lgpPduTable'. Each column represents an attribute of a PDU.
This table is indexed by the PDU identifier that is unique
within the agent.
"
INDEX
{
lgpPduEntryIndex
}
::= { lgpPduTable 1 }
LgpPduEntry ::= SEQUENCE
{
lgpPduEntryIndex Unsigned32,
lgpPduEntryId Unsigned32,
lgpPduEntryUsrLabel DisplayString,
lgpPduEntrySysAssignLabel DisplayString,
lgpPduEntryPositionRelative Unsigned32,
lgpPduEntrySysStatus Unsigned32,
lgpPduEntryUsrTag1 DisplayString,
lgpPduEntryUsrTag2 DisplayString,
lgpPduEntrySerialNumber DisplayString,
lgpPduEntryRbCount Unsigned32,
lgpPduEntrySWOverCurrentProtection INTEGER
}
lgpPduEntryIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This is the index that indicates the row of the 'lgpPduTable'."
::= { lgpPduEntry 1 }
lgpPduEntryId OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This is an internal index representing a unique identifier for
each PDU represented by this agent. The value is assigned
by the agent."
::= { lgpPduEntry 5 }
lgpPduEntryUsrLabel OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This is a user assigned label representing the PDU."
::= { lgpPduEntry 10 }
lgpPduEntrySysAssignLabel OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"System assigned identifier representing the PDU. The value
is independent of any user assigned label or tag. The exact format
of this label is system dependent and is subject to change,
therefore, it should not be referenced for programmatic use."
::= { lgpPduEntry 15 }
lgpPduEntryPositionRelative OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Count"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This is a one-based value that indicates the PDU's relative
position within a rack or other enclosing entity."
::= { lgpPduEntry 20 }
lgpPduEntrySysStatus OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This value represents a bit-field of the various operational
states of the PDU. The value is a logical OR of all of the
following potential states of the PDU. Note the bit-position
is given parenthetically next to the operational state in the
description below. The bit position is assumed to be a big-endian
format (least significant digit is the right-most digit). The
state is present in the PDU when the bit is on (value = 1).
normalOperation(1)
The PDU is operating normally with no active warnings or alarms.
startUp(2)
The PDU is in the startup state (initializing). Control
and monitoring operations maybe inhibited or unavailable
while the PDU is in this state. This state will clear
automatically when the PDU(s) are fully initialized and
ready to accept control and monitoring commands.
normalWithWarning(8)
The PDU is operating normally with one or more active
warnings. Appropriate personnel should investigate the
warning(s) as soon as possible and take appropriate action.
normalWithAlarm(16)
The PDU is operating normally with one or more active
alarms. Appropriate personnel should investigate the alarm(s)
as soon as possible and take appropriate action.
abnormalOperation(32)
The PDU is operating abnormally. That is there is some
failure within the system that is unexpected under normal
operating conditions. Appropriate personnel should investigate
the cause as soon as possible. The normal functioning of
the system is likely inhibited.
"
::= { lgpPduEntry 25 }
lgpPduEntryUsrTag1 OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This is a user assigned Tag for the PDU. This value may be
useful for end-user grouping or asset tracking purposes.
The value for this tag does not need to be unique for this
unit or across other units."
::= { lgpPduEntry 35 }
lgpPduEntryUsrTag2 OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This is a user assigned Tag for the PDU. This value may be
useful for end-user grouping or asset tracking purposes.
The value for this tag does not need to be unique for this
unit or across other units."
::= { lgpPduEntry 40 }
lgpPduEntrySerialNumber OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"System assigned serial number for this PDU. This number is
assigned at time of manufacture, is globally unique with respect
to all PDU units."
::= { lgpPduEntry 45 }
lgpPduEntryRbCount OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Count"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of receptacle branches (Rb) within this PDU."
::= { lgpPduEntry 50 }
lgpPduEntrySWOverCurrentProtection OBJECT-TYPE
SYNTAX INTEGER
{
disabled(0),
enable(1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This is the PDU Software Over Current Protection feature which will
prevent unused receptacles from turning on when the
'PDU Over Current Warning' or 'PDU Over Current Alarm' threshold
is violated. Such receptacles shall get locked to prevent any user
from switching them ON. Only device-admin shall have the authorization
to unlock such receptacles.
If the feature is enabled, in case of PDU Over Current Warning or Alarm condition,
following action will be taken on the receptacles:
a. Locked & OFF <20> No change
b. Locked & ON - No change
c. UnLocked & OFF <20> Receptacle shall be locked
d. Unlocked & ON <20> If the receptacle is being used (current>0), no change.
If that outlet is being unused(current=0), turn it off and lock it in that position.
No action will be taken if the feature is disabled.
Note: Only applicable to PDU models where receptacle measurement and control is supported.
Not applicable for PDU models that support only branch monitoring.
disabled
This function is disabled.
enable
This function is enabled."
::= { lgpPduEntry 55 }
-- -----------------------------------------------------------------------------
-- PDU Power Source.
-- -----------------------------------------------------------------------------
lgpPduPowerSource OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree contains information about PDU power sources."
REFERENCE
"The registrations for the objects in this sub-tree are
defined below."
::= { lgpPdu 30 }
lgpPduPsTableCount OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Count"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of power sources in the lgpPduPsTable."
::= { lgpPduPowerSource 19 }
lgpPduPsTable OBJECT-TYPE
SYNTAX SEQUENCE OF LgpPduPsEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains a list of the PDU's power source(s).
The table contains zero, one, or more rows, depending
upon the number of PDUs being monitored and the number of
power sources installed for each PDU.
The NMS cannot create or delete rows in the table. The rows are
created by the agent based upon the capabilities of the PDUs
being monitored. Each row in the table represents a PDU's
Power Source."
::= { lgpPduPowerSource 20 }
lgpPduPsEntry OBJECT-TYPE
SYNTAX LgpPduPsEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This entry defines the attributes to be populated in the
various columns of the 'lgpPduPsTable' (Power Source Table).
This table is indexed by both the 'lgpPduEntryIndex' which is
the sole index into the 'lgpPduTable' and the 'lgpPduPsEntryIndex'
which is a unique identifier for the Power Source within a
given PDU. Taken together these two indexes uniquely identify
a Power Source within this agent.
"
INDEX
{
lgpPduEntryIndex,
lgpPduPsEntryIndex
}
::= { lgpPduPsTable 1 }
LgpPduPsEntry ::= SEQUENCE
{
lgpPduPsEntryIndex Unsigned32,
lgpPduPsEntryId Unsigned32,
lgpPduPsEntrySysAssignLabel DisplayString,
lgpPduPsEntryModel DisplayString,
lgpPduPsEntryWiringType INTEGER,
lgpPduPsEntryEpInputRated Unsigned32,
lgpPduPsEntryEcInputRated Unsigned32,
lgpPduPsEntryFreqRated Unsigned32,
lgpPduPsEntryEnergyAccum Unsigned32,
lgpPduPsEntrySerialNum DisplayString,
lgpPduPsEntryFirmwareVersion DisplayString,
lgpPduPsEntryPwrTotal Unsigned32,
lgpPduPsEntryEcNeutral Unsigned32,
lgpPduPsEntryEcNeutralThrshldOvrWarn Unsigned32,
lgpPduPsEntryEcNeutralThrshldOvrAlarm Unsigned32,
lgpPduPsEntryUnbalancedLoadThrshldAlarm Unsigned32,
lgpPduPsEntryApTotal Unsigned32,
lgpPduPsEntryPfTotal Integer32,
lgpPduPsEntryEcResidual Unsigned32,
lgpPduPsEntryEcResidualThrshldOvrAlarm Unsigned32
}
lgpPduPsEntryIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This is a unique identifier for the Power Source within a
given PDU. This is one of two indexes used to indicate the row of
the 'lgpPduTable'."
::= { lgpPduPsEntry 5 }
lgpPduPsEntryId OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This is a unique entry id representing a given PDU power source
for the PDU."
::= { lgpPduPsEntry 10 }
lgpPduPsEntrySysAssignLabel OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"System assigned identifier for this power source. The value
is independent of any user assigned label or tag. The exact format
of this label is system dependent and is subject to change,
therefore, it should not be referenced for programmatic use."
::= { lgpPduPsEntry 15 }
lgpPduPsEntryModel OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This is the model name (identifier) of the power supply."
::= { lgpPduPsEntry 20 }
lgpPduPsEntryWiringType OBJECT-TYPE
SYNTAX INTEGER
{
not-specified(0),
single-phase-3-wire-L1-N-PE(1),
two-phase-3-wire-L1-L2-PE(2),
three-phase-4-wire-L1-L2-L3-PE(3),
three-phase-5-wire-L1-L2-L3-N-PE(4),
two-phase-4-wire-L1-L2-N-PE(5)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The PDU's power supply physical wiring type.
not-specified
The type has not been specified/configured. The end_user
must configure this object to specify the physical wiring
type.
single-phase-3-wire-L1-N-PE
Single Phase input with 3 wires (Line 1, Neutral and
Protective Earth).
two-phase-3-wire-L1-L2-PE
Two Phase input with 3 wires (Line 1, Line 2, and
Protective Earth).
three-phase-4-wire-L1-L2-L3-PE
Three Phase input with 4 wires (Line 1, Line 2, Line 3,
and Protective Earth).
three-phase-5-wire-L1-L2-L3-N-PE
Three Phase input with 5 wires (Line 1, Line 2, Line 3,
Neutral and Protective Earth).
two-phase-4-wire-L1-L2-N-PE
Two Phase input with 4 wires (Line 1, Line 2, Neutral,
and Protective Earth)."
::= { lgpPduPsEntry 25 }
lgpPduPsEntryEpInputRated OBJECT-TYPE
SYNTAX Unsigned32
UNITS "VoltRMS"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rated Input Line Voltage for the power source (i.e. this is the
nominal line input voltage; it is NOT a measured voltage).
The value is defined to be the rated line voltage
(either line-to-neutral or line-to-line depending upon the
power source's type)."
::= { lgpPduPsEntry 30 }
lgpPduPsEntryEcInputRated OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Amp-AC-RMS"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This is the rated input line current for the module
(it is NOT the measured current)."
::= { lgpPduPsEntry 35 }
lgpPduPsEntryFreqRated OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Hertz"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rated input line frequency for this power source
(i.e. This is the expected line frequency; it is NOT a
measured frequency; it is typically 50 Hz or 60 Hz)."
::= { lgpPduPsEntry 40 }
lgpPduPsEntryEnergyAccum OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Kilowatt-Hour"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Total accumulated energy, measured at the power source input, since
the last energy reset. Writing a value of 0 (zero) to this
causes the accumulated energy to be reset. Writing a non-zero
value is invalid and shall result in a write error and the
total energy value remains unchanged.
If the energy has not been reset and has not wrapped,
then this is the total energy since installation.
This value persists across boot events."
::= { lgpPduPsEntry 50 }
lgpPduPsEntrySerialNum OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This is a unique serial number of the power supply. This number
is assigned to the power supply at the time of manufacture."
::= { lgpPduPsEntry 55 }
lgpPduPsEntryFirmwareVersion OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This is the version of the firmware installed on the PDU's
power supply."
::= { lgpPduPsEntry 60 }
lgpPduPsEntryPwrTotal OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Watt"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Total input power for this power supply. This is the sum of the
power for all phases"
::= { lgpPduPsEntry 65 }
lgpPduPsEntryEcNeutral OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Amp-AC-RMS"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The neutral current measured at the PDU's power source."
::= { lgpPduPsEntry 70 }
lgpPduPsEntryEcNeutralThrshldOvrWarn OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Percent"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The threshold at which an over current warning is activated. If the
measured neutral current (lgpPduPsEntryEcNeutral) is above this
percentage of the full scale rated value
(lgpPduPsEntryEcInputRated), an over neutral current warning
(lgpConditionSource1NeutralOverCurrent) is activated."
::= { lgpPduPsEntry 75 }
lgpPduPsEntryEcNeutralThrshldOvrAlarm OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Percent"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The threshold at which an over current alarm is activated. If the
measured neutral current (lgpPduPsEntryEcNeutral) is above this
percentage of the full scale rated value
(lgpPduPsEntryEcInputRated), an over neutral current alarm
(lgpConditionSource1NeutralOverCurrent) is activated."
::= { lgpPduPsEntry 80 }
lgpPduPsEntryUnbalancedLoadThrshldAlarm OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Percent"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The parameter is for setting the maximum acceptable percentage of
'Unbalanced Load' between any two phases. This setting shall
trigger an alarm when the % load between any two phases varies by
a percentage higher than this configurable value. If this value is
0% then the alarm would be deactivated."
::= { lgpPduPsEntry 85 }
lgpPduPsEntryApTotal OBJECT-TYPE
SYNTAX Unsigned32
UNITS "VoltAmp"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Total Apparent power for this power supply. This is the sum of the
apparent power for all phases"
::= { lgpPduPsEntry 90 }
lgpPduPsEntryPfTotal OBJECT-TYPE
SYNTAX Integer32
UNITS "0.01 Power Factor"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Total power factor, which is real power/apparent power for all
phases combined. This is the sum of the real power for all phases
divided by the sum of the apparent power for all phases."
::= { lgpPduPsEntry 95 }
lgpPduPsEntryEcResidual OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.001 Amp-AC-RMS"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The measured residual current."
::= { lgpPduPsEntry 100 }
lgpPduPsEntryEcResidualThrshldOvrAlarm OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.001 Amp-AC-RMS"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The threshold at which an over current alarm is activated. If the
measured residual current (lgpPduPsEntryEcResidual) is above this
value, an over current alarm is activated. Setting this to 0mA
disables the alarm."
::= { lgpPduPsEntry 105 }
-- -----------------------------------------------------------------------------
-- PDU - Power Source Line/Phase Table.
-- -----------------------------------------------------------------------------
lgpPduPsLineTable OBJECT-TYPE
SYNTAX SEQUENCE OF LgpPduPsLineEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains a list of PDU's power source line/phase
measurements. The table contains zero, one, or many rows, depending
upon the number of PDU's Power Sources being monitored.
The NMS cannot create or delete rows in the table.
The rows are created by the agent based upon the capabilities of the
managed PDU's power supply(s). Each row in the table represents a
particular phase/line measurement of a power supply for a
given PDU."
::= { lgpPduPowerSource 40 }
lgpPduPsLineEntry OBJECT-TYPE
SYNTAX LgpPduPsLineEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This entry defines the attributes to be populated in the
various columns of the 'lgpPduPsLineTable'.
The table is index by three indexes which taken together
uniquely identify line/phase information for a given power source
within a PDU. The 'lgpPduEntryIndex' is an index into the
'lgpPduTable'. This identifies the PDU that the power source
is on. The 'lgpPduPsEntryIndex' is an index that together with
the 'lgpPduEntryIndex' uniquely identifies the power source
within the PDU that the row in this table represents. The final
index 'lgpPduPsLineEntryIndex' identifies the particular
line/phase that the measurement applies to within the identified
power source."
INDEX
{
lgpPduEntryIndex,
lgpPduPsEntryIndex,
lgpPduPsLineEntryIndex
}
::= { lgpPduPsLineTable 1 }
LgpPduPsLineEntry ::= SEQUENCE
{
lgpPduPsLineEntryIndex Unsigned32,
lgpPduPsLineEntryId Unsigned32,
lgpPduPsLineEntryLine INTEGER,
lgpPduPsLineEntryEpLNTenths Unsigned32,
lgpPduPsLineEntryEpLN Unsigned32,
lgpPduPsLineEntryEc Unsigned32,
lgpPduPsLineEntryEcHundredths Unsigned32,
lgpPduPsLineEntryEcThrshldUndrAlarm Unsigned32,
lgpPduPsLineEntryEcThrshldOvrWarn Unsigned32,
lgpPduPsLineEntryEcThrshldOvrAlarm Unsigned32,
lgpPduPsLineEntryEcAvailBeforeAlarm Unsigned32,
lgpPduPsLineEntryEcUsedBeforeAlarm Unsigned32,
lgpPduPsLineEntryEpLL Unsigned32,
lgpPduPsLineEntryEpLLTenths Unsigned32,
lgpPduPsLineEntryEcAvailBeforeAlarmHundredths Unsigned32,
lgpPduPsLineEntryPwrLN Unsigned32,
lgpPduPsLineEntryPwrLL Unsigned32,
lgpPduPsLineEntryApLN Unsigned32,
lgpPduPsLineEntryApLL Unsigned32,
lgpPduPsLineEntryPfLN Integer32,
lgpPduPsLineEntryPfLL Integer32
}
lgpPduPsLineEntryIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This is the index that indicates the line/phase of the measurements
in the given row of the 'lgpPduPsLineTable'."
::= { lgpPduPsLineEntry 5 }
lgpPduPsLineEntryId OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Unique identifier (within a PDU) for the PDU's power source.
The object may not be available in non-modular systems."
::= { lgpPduPsLineEntry 10 }
lgpPduPsLineEntryLine OBJECT-TYPE
SYNTAX INTEGER
{
phase1(1),
phase2(2),
phase3(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The line number (phase) that the measurement represents for all
measurements in a given row of the table. Note that this always
matches the lgpPduPsLineEntryIndex of the same row in the table.
The line/phases are as follows:
Line# Description
----- ---------------------------------------------------
1 Line 1-N (A) for Line-to-Neutral measurements
2 Line 2-N (B) for Line-to-Neutral measurements
3 Line 3-N (C) for Line-to-Neutral measurements
1 Line 1-2 (A-B) for Line-to-Line measurements
2 Line 2-3 (B-C) for Line-to-Line measurements
3 Line 3-1 (C-A) for Line-to-Line measurements
"
::= { lgpPduPsLineEntry 15 }
lgpPduPsLineEntryEpLNTenths OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts-AC-RMS"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Alternating Current RMS Line to Neutral Electrical Potential
measurement.
The line/phase being measured is indicated by the corresponding
lgpPduPsLineEntryLine value of this row in the table."
::= { lgpPduPsLineEntry 19 }
lgpPduPsLineEntryEpLN OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Volts-AC-RMS"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Alternating Current RMS Line to Neutral Electrical Potential
measurement.
The line/phase being measured is indicated by the corresponding
lgpPduPsLineEntryLine value of this row in the table."
::= { lgpPduPsLineEntry 20 }
lgpPduPsLineEntryEc OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Amps-AC-RMS"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Total input line-to-neutral electrical current.
The line/phase being measured is indicated by the corresponding
lgpPduPsLineEntryLine value of this row in the table."
::= { lgpPduPsLineEntry 21 }
lgpPduPsLineEntryEcHundredths OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 Amps-AC-RMS"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Total input line-to-neutral electrical current.
The line/phase being measured is indicated by the corresponding
lgpPduPsLineEntryLine value of this row in the table."
::= { lgpPduPsLineEntry 22 }
lgpPduPsLineEntryEcThrshldUndrAlarm OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Percent"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The threshold at which an under current alarm is activated. If
the measured current (lgpPduPsLineEntryEc) is equal to or below
this percentage of the full scale rated value
(lgpPduPsEntryEcInputRated), an under current alarm
is activated."
::= { lgpPduPsLineEntry 35 }
lgpPduPsLineEntryEcThrshldOvrWarn OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Percent"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The threshold at which an over current warning is activated. If
the measured current (lgpPduPsLineEntryEc) is equal to or over
this percentage of the full scale rated value
(lgpPduPsEntryEcInputRated), an over current warning
is activated."
::= { lgpPduPsLineEntry 36 }
lgpPduPsLineEntryEcThrshldOvrAlarm OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Percent"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The threshold at which an over current alarm is activated. If
the measured current (lgpPduPsLineEntryEc) is equal to or over
this percentage of the full scale rated value
(lgpPduPsEntryEcInputRated), an over current alarm
is activated."
::= { lgpPduPsLineEntry 37 }
lgpPduPsLineEntryEcAvailBeforeAlarm OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Amps-AC-RMS"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The amount that the current/amperage may increase from its present
value before an over current alarm occurs."
::= { lgpPduPsLineEntry 38 }
lgpPduPsLineEntryEcUsedBeforeAlarm OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The percent of current utilization relative to the over current
alarm threshold."
::= { lgpPduPsLineEntry 39 }
lgpPduPsLineEntryEpLL OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Volts-AC-RMS"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Line to Line Electrical Potential.
The line/phase being measured is indicated by the corresponding
lgpPduPsLineEntryLine value of this row in the table."
::= { lgpPduPsLineEntry 60 }
lgpPduPsLineEntryEpLLTenths OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts-AC-RMS"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Line to Line Electrical Potential.
The line/phase being measured is indicated by the corresponding
lgpPduPsLineEntryLine value of this row in the table."
::= { lgpPduPsLineEntry 61 }
lgpPduPsLineEntryEcAvailBeforeAlarmHundredths OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 Amps-AC-RMS"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The amount that the current/amperage may increase from its present
value before an over current alarm occurs."
::= { lgpPduPsLineEntry 62 }
lgpPduPsLineEntryPwrLN OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Watt"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The line-to-neutral measurement of the Real Power (Watts).
The line/phase being measured is indicated by the corresponding
lgpPduPsLineEntryLine value of this row in the table."
::= { lgpPduPsLineEntry 63 }
lgpPduPsLineEntryPwrLL OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Watt"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The line-to-line measurement of the Real Power (Watts).
The line/phase being measured is indicated by the corresponding
lgpPduPsLineEntryLine value of this row in the table."
::= { lgpPduPsLineEntry 64 }
lgpPduPsLineEntryApLN OBJECT-TYPE
SYNTAX Unsigned32
UNITS "VoltAmp"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The line-to-neutral measurement of the Apparent Power (VA).
The line/phase being measured is indicated by the corresponding
lgpPduPsLineEntryLine value of this row in the table."
::= { lgpPduPsLineEntry 65 }
lgpPduPsLineEntryApLL OBJECT-TYPE
SYNTAX Unsigned32
UNITS "VoltAmp"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The line-to-line measurement of the Apparent Power (VA).
The line/phase being measured is indicated by the corresponding
lgpPduPsLineEntryLine value of this row in the table."
::= { lgpPduPsLineEntry 66 }
lgpPduPsLineEntryPfLN OBJECT-TYPE
SYNTAX Integer32
UNITS "0.01 Power Factor"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The line-to-neutral measurement of the Power Factor of the
power source.
The line/phase being measured is indicated by the corresponding
lgpPduPsLineEntryLine value of this row in the table."
::= { lgpPduPsLineEntry 67 }
lgpPduPsLineEntryPfLL OBJECT-TYPE
SYNTAX Integer32
UNITS "0.01 Power Factor"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The line-to-line measurement of the Power Factor of the
power source.
The line/phase being measured is indicated by the corresponding
lgpPduPsLineEntryLine value of this row in the table."
::= { lgpPduPsLineEntry 68 }
-- -----------------------------------------------------------------------------
-- PDU Receptacle Branch
-- -----------------------------------------------------------------------------
lgpPduReceptacleBranch OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree contains information about PDU receptacle branches."
REFERENCE
"The registrations for the objects in this sub-tree are
defined below."
::= { lgpPdu 40 }
lgpPduRbTableCount OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Count"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of receptacle branches in the lgpPduRbTable."
::= { lgpPduReceptacleBranch 19 }
lgpPduRbTable OBJECT-TYPE
SYNTAX SEQUENCE OF LgpPduRbEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains a list of PDU Receptacle branches.
The table contains zero, one, or many rows, depending
upon the number of PDUs being managed and how many
receptacle branches each PDU has installed.
The NMS cannot create or delete rows in the table. The rows are
created by the agent based upon the capabilities of the PDUs
being managed. Each row in the table represents a receptacle branch
for a given PDU. The PDU that a branch is installed
on is indicated by the column lgpPduEntryIndex. The branch
within the lgpPduEntryIndex PDU is indicated by the column
lgpPduRbEntryIndex."
::= { lgpPduReceptacleBranch 20 }
lgpPduRbEntry OBJECT-TYPE
SYNTAX LgpPduRbEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This entry defines the attributes to be populated in the
various columns of the 'lgpPduRbTable'. The table is indexed
by both the 'lgpPduEntryIndex' and 'lgpPduRbEntryIndex'. The
lgpPduEntryIndex specifies the PDU, defined in the lgpPduTable
that the branch is on. The lgpPduRbEntryIndex uniquely identifies
the branch within that PDU. Taken together the two indexes
uniquely identify a branch being monitored by this agent.
"
INDEX
{
lgpPduEntryIndex,
lgpPduRbEntryIndex
}
::= { lgpPduRbTable 1 }
LgpPduRbEntry ::= SEQUENCE
{
lgpPduRbEntryIndex Unsigned32,
lgpPduRbEntryId Unsigned32,
lgpPduRbEntryUsrLabel DisplayString,
lgpPduRbEntrySysAssignLabel DisplayString,
lgpPduRbEntryPositionRelative Unsigned32,
lgpPduRbEntrySerialNum DisplayString,
lgpPduRbEntryModel DisplayString,
lgpPduRbEntryFirmwareVersion DisplayString,
lgpPduRbEntryUsrTag1 DisplayString,
lgpPduRbEntryUsrTag2 DisplayString,
lgpPduRbEntryReceptacleType INTEGER,
lgpPduRbEntryCapabilities INTEGER,
lgpPduRbEntryLineSource INTEGER,
lgpPduRbEntryRcpCount Unsigned32,
lgpPduRbEntryEpRated Unsigned32,
lgpPduRbEntryEcRated Unsigned32,
lgpPduRbEntryFreqRated Unsigned32,
lgpPduRbEntryEnergyAccum Unsigned32,
lgpPduRbEntryEpLNTenths Unsigned32,
lgpPduRbEntryPwr Unsigned32,
lgpPduRbEntryAp Unsigned32,
lgpPduRbEntryPf Integer32,
lgpPduRbEntryEcHundredths Unsigned32,
lgpPduRbEntryEcThrshldUndrAlm Unsigned32,
lgpPduRbEntryEcThrshldOvrWarn Unsigned32,
lgpPduRbEntryEcThrshldOvrAlm Unsigned32,
lgpPduRbEntryEcAvailBeforeAlarmHundredths Unsigned32,
lgpPduRbEntryEcUsedBeforeAlarm Unsigned32,
lgpPduRbEntryEpLLTenths Unsigned32,
lgpPduRbEntrySwOverCurrentProtection INTEGER
}
lgpPduRbEntryIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This is the index that indicates the row of the
'lgpPduRbTable'"
::= { lgpPduRbEntry 1 }
lgpPduRbEntryId OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A unique id representing the receptacle branch within the
collection of branches being monitored by this agent. The
uniqueness of this id is within the PDUs being managed by
a single agent."
::= { lgpPduRbEntry 5 }
lgpPduRbEntryUsrLabel OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A user assigned label representing the receptacle branch."
::= { lgpPduRbEntry 8 }
lgpPduRbEntrySysAssignLabel OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"System assigned identifier for this receptacle branch. The value
is independent of any user assigned label or tag. The exact format
of this label is system dependent and is subject to change,
therefore, it should not be referenced for programmatic use."
::= { lgpPduRbEntry 20 }
lgpPduRbEntryPositionRelative OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Count"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This is a one-based value that indicates the relative
position of the branch within the PDU."
::= { lgpPduRbEntry 25 }
lgpPduRbEntrySerialNum OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A globally unique serial number for this branch. This number
is assigned to the branch at the time of manufacture and can not
be modified. NOTE: Generally only PDUs with replaceable
receptacle branches will have serial numbers."
::= { lgpPduRbEntry 30 }
lgpPduRbEntryModel OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This is the model designation for this receptacle branch."
::= { lgpPduRbEntry 35 }
lgpPduRbEntryFirmwareVersion OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This is the firmware version number of the control software
running on the receptacle branch. Only PDUs with
replaceable receptacle branches will typically support this
object."
::= { lgpPduRbEntry 40 }
lgpPduRbEntryUsrTag1 OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This is a user assigned Tag for the receptacle branch. This
value may be useful for end-user grouping or asset tracking
purposes. The value for this tag does not need to be unique
for this unit or across other units."
::= { lgpPduRbEntry 41 }
lgpPduRbEntryUsrTag2 OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This is a user assigned Tag for the receptacle branch. This
value may be useful for end-user grouping or asset tracking
purposes. The value for this tag does not need to be unique
for this unit or across other units."
::= { lgpPduRbEntry 42 }
lgpPduRbEntryReceptacleType OBJECT-TYPE
SYNTAX INTEGER
{
not-specified(0),
nema-5-20R-20-Amp(1),
iec-C13-sheet-F-10-Amp(2),
iec-C19-sheet-J-16-Amp(3),
iec-C13-sheet-F-10-Amp-and-iec-C19-sheet-J-16-Amp(4),
nema-5-20R-20-Amp-and-iec-C13-sheet-F-10-Amp(5),
nema-5-20R-20-Amp-and-iec-C19-sheet-J-16-Amp(6),
cee-7-type-E-schuko(7),
nema-L6-30R-30-Amp(8)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This enumeration represents the type of receptacles installed
on this receptacle branch. All receptacles on this branch are
of this type/style.
not-specified
If this value is returned, either the receptacle type has
not been specified/configured or the agent monitoring this
PDU does not have a SNMP enumeration defined to the type.
"
::= { lgpPduRbEntry 45 }
lgpPduRbEntryCapabilities OBJECT-TYPE
SYNTAX INTEGER
{
not-specified(0),
no-optional-capabilities(1),
measurement-only(2),
measurement-and-control(3),
control-only(4),
current-measurement-only(5),
current-measurement-and-control(6)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Receptacle branch capabilities describes what an individual branch
is capable of.
no-optional-capabilities
The branch is unable to report measurements and lacks
control capabilities.
measurement-only
The branch is capable of reporting multiple measurements.
measurement-and-control
The branch is capable of reporting multiple measurements
and controlling the state.
control-only
The branch is capable of controlling the state.
current-measurement-only
The branch is capable of reporting the current/amperage only.
current-measurement-and-control
The branch is capable of reporting the current/amperage and
has the ability to control the state."
::= { lgpPduRbEntry 50 }
lgpPduRbEntryLineSource OBJECT-TYPE
SYNTAX INTEGER
{
not-specified(0),
line-1-neutral(1),
line-2-neutral(2),
line-3-neutral(3),
line-1-line-2(4),
line-2-line-3(5),
line-3-line-1(6),
line-1-line-2-and-line-1-neutral(7),
line-2-line-3-and-line-2-neutral(8),
line-3-line-1-and-line-3-neutral(9),
unknown-line-neutral(10),
unknown-line-line(11)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This represents the line source that is supplying power to this
receptacle branch.
not-specified
The line source supplying power to the load for this
receptacle branch has not been specified/configured.
line-1-N
The load for this receptacle branch is supplied by
a line-to-neutral configuration. (line 1 to neutral).
line-2-N
The load for this receptacle branch is supplied by
a line-to-neutral configuration. (line 2 to neutral).
line-3-N
The load for this receptacle branch is supplied by
a line-to-neutral configuration. (line 3 to neutral).
line-1-line-2
The load for this receptacle branch is supplied by
a line-to-line configuration (line 1 to line 2).
line-2-line-3
The load for this receptacle branch is supplied by
a line-to-line configuration (line 2 to line 3).
line-3-line-1
The load for this receptacle branch is supplied by
a line-to-line configuration (line 3 to line 1).
line-1-line-2-and-line-1-neutral
The load for this mixed receptacle branch is supplied by
a line-to-line and line-to-neutral configuration
(line 1 to line 2 and line 1 to neutral).
line-2-line-3-and-line-2-neutral
The load for this mixed receptacle branch is supplied by
a line-to-line and line-to-neutral configuration
(line 2 to line 3 and line 2 to neutral).
line-3-line-1-and-line-3-neutral
The load for this mixed receptacle branch is supplied by
a line-to-line and line-to-neutral configuration
(line 3 to line 1 and line 3 to neutral).
unknown-line-neutral
The load for this branch is supplied by
a line-to-neutral configuration. The system is unable to
determine which lines are supporting the load.
unknown-line-line
The load for this branch is supplied by
a line-to-line configuration. The system is unable to
determine which lines are supporting the load.
"
::= { lgpPduRbEntry 55 }
lgpPduRbEntryRcpCount OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Count"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of receptacles on this receptacle branch."
::= { lgpPduRbEntry 60 }
lgpPduRbEntryEpRated OBJECT-TYPE
SYNTAX Unsigned32
UNITS "VoltRMS"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rated Line Voltage for the receptacle branch and its associated
receptacles (i.e. This is the nominal line voltage that is
available to the connected load; it is NOT a measured voltage.)"
::= { lgpPduRbEntry 70 }
lgpPduRbEntryEcRated OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Amp-AC-RMS"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This is the rated input line current for the module
(it is NOT the measured current)."
::= { lgpPduRbEntry 75 }
lgpPduRbEntryFreqRated OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Hertz"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This is the rated electrical frequency for the receptacle branch
and its associated receptacles"
::= { lgpPduRbEntry 80 }
lgpPduRbEntryEnergyAccum OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Kilowatt-Hour"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Total accumulated energy, measured at the receptacle branch input,
since the last energy reset. Writing a value of 0 (zero) to this
causes the accumulated energy to be reset. Writing a non-zero
value is invalid and shall result in a write error and the
total energy value remains unchanged.
If the energy has not been reset and has not wrapped, then this
is the total energy since installation.
This value persists across boot events.
NOTE: Resetting this value does not reset the values for the
individual receptacles."
::= { lgpPduRbEntry 85 }
lgpPduRbEntryEpLNTenths OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 VoltRMS"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The line-to-neutral measurement of the Electrical Potential
measured in Volts RMS (Root Mean Squared)."
::= { lgpPduRbEntry 100 }
lgpPduRbEntryPwr OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Watt"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The line-to-neutral measurement of the Real Power (Wattage)"
::= { lgpPduRbEntry 115 }
lgpPduRbEntryAp OBJECT-TYPE
SYNTAX Unsigned32
UNITS "VoltAmp"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The line-to-neutral measurement of the Apparent Power (VA)"
::= { lgpPduRbEntry 120 }
lgpPduRbEntryPf OBJECT-TYPE
SYNTAX Integer32
UNITS "0.01 Power Factor"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The line-to-neutral measurement of the Power Factor of the
receptacle branches' input."
::= { lgpPduRbEntry 125 }
lgpPduRbEntryEcHundredths OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 Amp-AC-RMS"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The line-to-neutral measurement of the Electrical Current
measured in Amperes RMS (Root Mean Squared)."
::= { lgpPduRbEntry 130 }
lgpPduRbEntryEcThrshldUndrAlm OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Percent"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The threshold at which an under current alarm is activated. If
the measured current (lgpPduRbEntryEc) is equal to or below
this percentage of the full scale rated value
(lgpPduRbEntryEcRated), an under current alarm
is activated"
::= { lgpPduRbEntry 135 }
lgpPduRbEntryEcThrshldOvrWarn OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Percent"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The threshold at which an over current warning is activated. If
the measured current (lgpPduRbEntryEc) is equal to or over
this percentage of the full scale rated value
(lgpPduRbEntryEcRated), an over current warning
is activated"
::= { lgpPduRbEntry 140 }
lgpPduRbEntryEcThrshldOvrAlm OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Percent"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The threshold at which an over current alarm is activated. If
the measured current (lgpPduRbEntryEcLN) is equal to or over
this percentage of the full scale rated value
(lgpPduRbEntryEcRated), an over current alarm
is activated"
::= { lgpPduRbEntry 145 }
lgpPduRbEntryEcAvailBeforeAlarmHundredths OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 Amps-AC-RMS"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The amount that the current/amperage may increase from its present
value before an over current alarm occurs."
::= { lgpPduRbEntry 150 }
lgpPduRbEntryEcUsedBeforeAlarm OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The percent of current utilization relative to the over current
alarm threshold."
::= { lgpPduRbEntry 160 }
lgpPduRbEntryEpLLTenths OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 VoltRMS"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The line-to-line measurement of the Electrical Potential
measured in Volts RMS (Root Mean Squared)."
::= { lgpPduRbEntry 170 }
lgpPduRbEntrySwOverCurrentProtection OBJECT-TYPE
SYNTAX INTEGER
{
disable(0),
enable(1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The configuration parameter to enable or disable the Branch
SW Over Current Protection feature.If the feature is enabled, in case of Over Current Warning or Alarm condition, following action will be taken on the receptacles:
Locked & On - No Change
Locked & Off - No Change
Unlocked & Off - Turn it Off and Lock it
Unlocked & On - If load present, No Change. If no load, turn it Off and Lock it.
No action will be taken if the feature is disabled.
Note: Only applicable to PDU models where receptacle measurement and control is possible. Not applicable to branch monoitoring models
disabled
This function is disabled.
enable
This function is enabled."
::= { lgpPduRbEntry 175 }
-- -----------------------------------------------------------------------------
-- PDU Receptacle Branch - Line/Phase Measurements.
-- -----------------------------------------------------------------------------
lgpPduRbLineTable OBJECT-TYPE
SYNTAX SEQUENCE OF LgpPduRbLineEntry
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION
"This table contains a list of PDU receptacle branch line/phase
measurements. The table contains zero, one, or many rows, depending
upon the number of PDUs and the number of receptacle branches
on each PDU that are being monitored.
The NMS cannot create or delete rows in the table.
The rows are created by the agent based upon the capabilities of the
PDU(s) being monitored. Each row in the table represents a
particular phase/line measurement of a PDU Receptacle
Branch.
Rows in the table are uniquely identified by three indexes representing
respectively the PDU (lgpPduEntryIndex), the receptacle
branch (lgpPduRbEntryIndex) and the line/phase being
measured (lgpPduRbLineEntryIndex).
"
::= { lgpPduReceptacleBranch 40 }
lgpPduRbLineEntry OBJECT-TYPE
SYNTAX LgpPduRbLineEntry
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION
"This entry defines the attributes to be populated in the
various columns of the 'lgpPduRbLineTable'. The table is
indexed by three indexes. The 'lgpPduEntryIndex' references
a PDU in the 'lgpPduTable' to which this receptacle branch
line/phase measurement belongs. The 'lgpPduRbEntryIndex' together
with the 'lgpPduEntryIndex' references the receptacle branch
in the 'lgpPduRbTable'. The 'lgpPduRbLineEntryIndex' represents
the line/phase of the measurements in the row of this table.
Together these three indexes uniquely identify a phase/line
measurement on a receptacle branch within a PDU being monitored
by this agent.
"
INDEX
{
lgpPduEntryIndex,
lgpPduRbEntryIndex,
lgpPduRbLineEntryIndex
}
::= { lgpPduRbLineTable 1 }
LgpPduRbLineEntry ::= SEQUENCE
{
lgpPduRbLineEntryIndex Unsigned32,
lgpPduRbLineEntryId Unsigned32,
lgpPduRbLineEntryLine INTEGER,
lgpPduRbLineEntryEpLNTenths Unsigned32,
lgpPduRbLineEntryEpLN Unsigned32,
lgpPduRbLineEntryEc Unsigned32,
lgpPduRbLineEntryPwr Unsigned32,
lgpPduRbLineEntryAp Unsigned32,
lgpPduRbLineEntryPf Integer32,
lgpPduRbLineEntryEcHundredths Unsigned32,
lgpPduRbLineEntryEcThrshldUndrAlm Unsigned32,
lgpPduRbLineEntryEcThrshldOvrWarn Unsigned32,
lgpPduRbLineEntryEcThrshldOvrAlm Unsigned32,
lgpPduRbLineEntryEcAvailBeforeAlarmHundredths Unsigned32,
lgpPduRbLineEntryEcAvailBeforeAlarm Unsigned32,
lgpPduRbLineEntryEcUsedBeforeAlarm Unsigned32,
lgpPduRbLineEntryEpLL Unsigned32,
lgpPduRbLineEntryEpLLTenths Unsigned32
}
lgpPduRbLineEntryIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION
"This is the index that indicates the row of the
'lgpPduRbLineTable'"
::= { lgpPduRbLineEntry 1 }
lgpPduRbLineEntryId OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Runtime assigned branch identifier."
::= { lgpPduRbLineEntry 5 }
lgpPduRbLineEntryLine OBJECT-TYPE
SYNTAX INTEGER
{
phase1(1),
phase2(2),
phase3(3)
}
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"The line number or phase that the measurement for this
receptacle branch represents for each measurement in this row of
the table. The phases are as follows:
Line# Description
----- ---------------------------------------------------
1 Line 1-N (A) for Line-to-Neutral measurements
2 Line 2-N (B) for Line-to-Neutral measurements
3 Line 3-N (C) for Line-to-Neutral measurements
1 Line 1-2 (A-B) for Line-to-Line measurements
2 Line 2-3 (B-C) for Line-to-Line measurements
3 Line 3-1 (C-A) for Line-to-Line measurements
"
::= { lgpPduRbLineEntry 10 }
lgpPduRbLineEntryEpLNTenths OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 VoltRMS"
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"The line-to-neutral measurement of the Electrical Potential
measured in Volts RMS (Root Mean Squared)."
::= { lgpPduRbLineEntry 19 }
lgpPduRbLineEntryEpLN OBJECT-TYPE
SYNTAX Unsigned32
UNITS "VoltRMS"
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"The line-to-neutral measurement of the Electrical Potential
measured in Volts RMS (Root Mean Squared)."
::= { lgpPduRbLineEntry 20 }
lgpPduRbLineEntryEc OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Amp-AC-RMS"
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"The line-to-neutral measurement of the Electrical Current
measured in Amperes RMS (Root Mean Squared)."
::= { lgpPduRbLineEntry 21 }
lgpPduRbLineEntryPwr OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Watt"
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"The line-to-neutral measurement of the Real Power (Wattage)"
::= { lgpPduRbLineEntry 22 }
lgpPduRbLineEntryAp OBJECT-TYPE
SYNTAX Unsigned32
UNITS "VoltAmp"
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"The line-to-neutral measurement of the Apparent Power (VA)"
::= { lgpPduRbLineEntry 23 }
lgpPduRbLineEntryPf OBJECT-TYPE
SYNTAX Integer32
UNITS "0.01 Power Factor"
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"The line-to-neutral measurement of the Power Factor of the
receptacle branches' input."
::= { lgpPduRbLineEntry 24 }
lgpPduRbLineEntryEcHundredths OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 Amp-AC-RMS"
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"The line-to-neutral measurement of the Electrical Current
measured in Amperes RMS (Root Mean Squared)."
::= { lgpPduRbLineEntry 25 }
lgpPduRbLineEntryEcThrshldUndrAlm OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Percent"
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"The threshold at which an under current alarm is activated. If
the measured current (lgpPduRbLineEntryEc) is equal to or below
this percentage of the full scale rated value
(lgpPduRbEntryEcRated), an under current alarm
is activated"
::= { lgpPduRbLineEntry 35 }
lgpPduRbLineEntryEcThrshldOvrWarn OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Percent"
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"The threshold at which an over current warning is activated. If
the measured current (lgpPduRbLineEntryEc) is equal to or over
this percentage of the full scale rated value
(lgpPduRbEntryEcRated), an over current warning
is activated"
::= { lgpPduRbLineEntry 36 }
lgpPduRbLineEntryEcThrshldOvrAlm OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Percent"
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"The threshold at which an over current alarm is activated. If
the measured current (lgpPduRbLineEntryEcLN) is equal to or over
this percentage of the full scale rated value
(lgpPduRbEntryEcRated), an over current alarm
is activated"
::= { lgpPduRbLineEntry 37 }
lgpPduRbLineEntryEcAvailBeforeAlarmHundredths OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 Amps-AC-RMS"
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"The amount that the current/amperage may increase from its present
value before an over current alarm occurs."
::= { lgpPduRbLineEntry 39 }
lgpPduRbLineEntryEcAvailBeforeAlarm OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Amps-AC-RMS"
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"The amount that the current/amperage may increase from its present
value before an over current alarm occurs."
::= { lgpPduRbLineEntry 40 }
lgpPduRbLineEntryEcUsedBeforeAlarm OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Percent"
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"The percent of current utilization relative to the over current
alarm threshold."
::= { lgpPduRbLineEntry 41 }
lgpPduRbLineEntryEpLL OBJECT-TYPE
SYNTAX Unsigned32
UNITS "VoltRMS"
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"The line-to-line measurement of the Electrical Potential
measured in Volts RMS (Root Mean Squared)."
::= { lgpPduRbLineEntry 60 }
lgpPduRbLineEntryEpLLTenths OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 VoltRMS"
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"The line-to-line measurement of the Electrical Potential
measured in Volts RMS (Root Mean Squared)."
::= { lgpPduRbLineEntry 61 }
-- -----------------------------------------------------------------------------
-- PDU Receptacle (RCP) - Table
-- -----------------------------------------------------------------------------
lgpPduReceptacle OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree contains information about PDU receptacles."
REFERENCE
"The registrations for the objects in this sub-tree are
defined below."
::= { lgpPdu 50 }
lgpPduRcpTableCount OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Count"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of receptacles in the lgpPduRcpTable."
::= { lgpPduReceptacle 19 }
lgpPduRcpTable OBJECT-TYPE
SYNTAX SEQUENCE OF LgpPduRcpEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains a list of PDU receptacle entries.
The table contains numerous rows representing an individual
receptacle, depending upon the number and configuration of
the PDU(s) being monitored by the agent.
The NMS cannot create or delete rows in the table. The rows are
created by the agent based upon the capabilities of the managed
PDU(s). Each row in the table represents a receptacle in
the system.
"
::= { lgpPduReceptacle 20 }
lgpPduRcpEntry OBJECT-TYPE
SYNTAX LgpPduRcpEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This entry defines the attributes to be populated in the
various columns of the 'lgpPduRcpTable'. This table is indexed
by three indexes. The 'lgpPduEntryIndex' references a PDU in
the 'lgpPduTable' that a given row in this table represents.
The 'lgpPduRbEntryIndex' together with the 'lgpPduEntryIndex'
specifies a row in the 'lgpPduRbTable' that the receptacle
belongs. The 'lgpPduRcpEntryIndex' identifies the particular
receptacle within the branch.
"
INDEX
{
lgpPduEntryIndex,
lgpPduRbEntryIndex,
lgpPduRcpEntryIndex
}
::= { lgpPduRcpTable 1 }
LgpPduRcpEntry ::= SEQUENCE
{
lgpPduRcpEntryIndex Unsigned32,
lgpPduRcpEntryId Unsigned32,
lgpPduRcpEntryUsrLabel DisplayString,
lgpPduRcpEntryUsrTag1 DisplayString,
lgpPduRcpEntryUsrTag2 DisplayString,
lgpPduRcpEntrySysAssignLabel DisplayString,
lgpPduRcpEntryPosition Unsigned32,
lgpPduRcpEntryType INTEGER,
lgpPduRcpEntryLineSource INTEGER,
lgpPduRcpEntryCapabilities INTEGER,
lgpPduRcpEntryEp Unsigned32,
lgpPduRcpEntryEpTenths Unsigned32,
lgpPduRcpEntryEc Unsigned32,
lgpPduRcpEntryEcHundredths Unsigned32,
lgpPduRcpEntryPwrOut Unsigned32,
lgpPduRcpEntryApOut Unsigned32,
lgpPduRcpEntryPf Unsigned32,
lgpPduRcpEntryFreq Unsigned32,
lgpPduRcpEntryEnergyAccum Unsigned32,
lgpPduRcpEntryPwrOnDelay Unsigned32,
lgpPduRcpEntryPwrState INTEGER,
lgpPduRcpEntryPwrUpState INTEGER,
lgpPduRcpEntryControl INTEGER,
lgpPduRcpEntryControlLock INTEGER,
lgpPduRcpEntryEcThrshldUnderAlarm Unsigned32,
lgpPduRcpEntryEcThrshldOverWarn Unsigned32,
lgpPduRcpEntryEcThrshldOverAlarm Unsigned32,
lgpPduRcpEntryEcAvailBeforeAlarmHundredths Unsigned32,
lgpPduRcpEntryEcAvailBeforeAlarm Unsigned32,
lgpPduRcpEntryEcUsedBeforeAlarm Unsigned32,
lgpPduRcpEntryEcCrestFactor Unsigned32,
lgpPduRcpEntryBlinkLED INTEGER,
lgpPduRcpEntrySwOverTemperatureProtection INTEGER,
lgpPduRcpEntryOperationCondition INTEGER,
lgpPduRcpEntryCriticality INTEGER,
lgpPduRcpEntryPostOnDelay Unsigned32,
lgpPduRcpEntryPostOffDelay Unsigned32,
lgpPduRcpEntryAddReceptacleToGroup OBJECT IDENTIFIER,
lgpPduRcpEntryRemoveReceptacleFromGroup OBJECT IDENTIFIER
}
lgpPduRcpEntryIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This is the index that indicates the receptacle position on the
receptacle branch. This along with the other two indexes on the
lgpPduRcpTable uniquely identify the receptacle in this table."
::= { lgpPduRcpEntry 1 }
lgpPduRcpEntryId OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A runtime assigned receptacle identification number."
::= { lgpPduRcpEntry 5 }
lgpPduRcpEntryUsrLabel OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User assigned label for this receptacle."
::= { lgpPduRcpEntry 10 }
lgpPduRcpEntryUsrTag1 OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User assigned Tag to assist in identifying or grouping this
receptacle within the end-users domain."
::= { lgpPduRcpEntry 15 }
lgpPduRcpEntryUsrTag2 OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User assigned Tag to assist in identifying or grouping this
receptacle within the end-users domain."
::= { lgpPduRcpEntry 20 }
lgpPduRcpEntrySysAssignLabel OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"System assigned identifier representing the receptacle. The value
is independent of any user assigned label or tag. The exact format
of this label is system dependent and is subject to change,
therefore, it should not be referenced for programmatic use."
::= { lgpPduRcpEntry 25 }
lgpPduRcpEntryPosition OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A number representing the position of the receptacle within the
receptacle branch."
::= { lgpPduRcpEntry 30 }
lgpPduRcpEntryType OBJECT-TYPE
SYNTAX INTEGER
{
not-specified(0),
nema-5-20R-20-Amp(1),
iec-C13-sheet-F-10-Amp(2),
iec-C19-sheet-J-16-Amp(3),
cee-7-type-E-schuko(7),
nema-L6-30R-30-Amp(8)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The type or form of receptacle. The enumerations are specified
in well-known industry standard terms and abbreviations."
::= { lgpPduRcpEntry 40 }
lgpPduRcpEntryLineSource OBJECT-TYPE
SYNTAX INTEGER
{
not-specified(0),
line-1-N(1),
line-2-N(2),
line-3-N(3),
line-1-line-2(4),
line-2-line-3(5),
line-3-line-1(6),
unknown-line-neutral(7),
unknown-line-line(8)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This represents the line source that is supplying power to this
receptacle.
not-specified
The line source supplying power to the load for this
receptacle has not been specified/configured.
line-1-N
The load for this receptacle is supplied by
a line-to-neutral configuration. (line 1 to neutral).
line-2-N
The load for this receptacle is supplied by
a line-to-neutral configuration. (line 2 to neutral).
line-3-N
The load for this receptacle is supplied by
a line-to-neutral configuration. (line 3 to neutral).
line-1-line-2
The load for this receptacle is supplied by
a line-to-line configuration (line 1 to line 2).
line-2-line-3
The load for this receptacle is supplied by
a line-to-line configuration (line 2 to line 3).
line-3-line-1
The load for this receptacle is supplied by
a line-to-line configuration (line 3 to line 1).
unknown-line-neutral
The load for this receptacle is supplied by
a line-to-neutral configuration. The system is unable to
determine which lines are supporting the load.
unknown-line-line
The load for this receptacle is supplied by
a line-to-line configuration. The system is unable to
determine which lines are supporting the load.
"
::= { lgpPduRcpEntry 45 }
lgpPduRcpEntryCapabilities OBJECT-TYPE
SYNTAX INTEGER
{
not-specified(0),
no-optional-capabilities(1),
measurement-only(2),
measurement-and-control(3),
control-only(4),
current-measurement-only(5),
current-measurement-and-control(6)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Receptacle capabilities describes what an individual receptacle is
capable of.
no-optional-capabilities
The receptacle is unable to report measurements and lacks
control capabilities.
measurement-only
The receptacle is capable of reporting multiple measurements.
measurement-and-control
The receptacle is capable of reporting multiple measurements
and controlling the state.
control-only
The receptacle is capable of controlling the state.
current-measurement-only
The receptacle is capable of reporting the current/amperage
only.
current-measurement-and-control
The receptacle is capable of reporting the current/amperage and
has the ability to control the state."
::= { lgpPduRcpEntry 50 }
lgpPduRcpEntryEp OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Volts-AC-RMS"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Voltage being delivered to the load attached to the receptacle.
Alternating Current RMS Electrical Potential measurement."
::= { lgpPduRcpEntry 55 }
lgpPduRcpEntryEpTenths OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts-AC-RMS"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Voltage being delivered to the load attached to the receptacle.
Alternating Current RMS Electrical Potential measurement."
::= { lgpPduRcpEntry 56 }
lgpPduRcpEntryEc OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Amp-AC-RMS"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Current (amperage) being delivered to the load attached to
the receptacle. Electrical Current is measured in
Amperes RMS (Root Mean Squared)."
::= { lgpPduRcpEntry 60 }
lgpPduRcpEntryEcHundredths OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 Amp-AC-RMS"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Current (amperage) being delivered to the load attached to
the receptacle. Electrical Current is measured in
Amperes RMS (Root Mean Squared)."
::= { lgpPduRcpEntry 61 }
lgpPduRcpEntryPwrOut OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Watt"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Real Power (watts) being delivered to the load attached to
the receptacle."
::= { lgpPduRcpEntry 65 }
lgpPduRcpEntryApOut OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Volt-Amp-RMS"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Apparent Power (volt-amps) being delivered to the load
attached to the receptacle."
::= { lgpPduRcpEntry 70 }
lgpPduRcpEntryPf OBJECT-TYPE
SYNTAX Unsigned32
UNITS ".01 Power Factor"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Receptacle Power Factor, which is the ratio of real power
to apparent power (i.e. ratio of watts to volts-amps)."
::= { lgpPduRcpEntry 75 }
lgpPduRcpEntryFreq OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Hertz"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The measured line frequency being delivered to the load
attached to the receptacle."
::= { lgpPduRcpEntry 80 }
lgpPduRcpEntryEnergyAccum OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Kilowatt-Hour"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Total accumulated energy, measured at the module input, since
the last energy reset. Writing a value of 0 (zero) to this
causes the accumulated energy to be reset. Writing a non-zero
value is invalid and shall result in a write error and the
total energy value remains unchanged.
If the energy has not been reset and has not wrapped,
then this is the total energy since installation.
This value persists across boot events."
::= { lgpPduRcpEntry 85 }
lgpPduRcpEntryPwrOnDelay OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The amount of time to wait before power is applied to the
receptacle after a power strip is turned on or rebooted.
This can be used to stagger the powering of multiple
receptacles in order to prevent a large initial current
draw."
::= { lgpPduRcpEntry 90 }
lgpPduRcpEntryPwrState OBJECT-TYPE
SYNTAX INTEGER
{
unknown(0),
off(1),
on(2),
off-pending-on-delay(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"unknown
The current power state is unknown.
off
The current power state of the receptacle is OFF.
on
The current power state of the receptacle is ON.
off-pending-on-delay
The current power state of the receptacle is OFF. The power
will be ON at the expiration of the ON delay of this
receptacle."
::= { lgpPduRcpEntry 95 }
lgpPduRcpEntryPwrUpState OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2),
last-state(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The 'Power Up State' defines the state to which the receptacle shall return
after a power cycle of the PDU.
on
The receptacle shall be switched to the ON state after the power on delay
timer (lgpPduRcpEntryPwrOnDelay).
off
The receptacle shall be in the OFF state upon power cycle.
last-state
The receptacle shall be put to the previous state. Again, on state will be
effective only after the power on delay (lgpPduRcpEntryPwrOnDelay)."
::= { lgpPduRcpEntry 96 }
lgpPduRcpEntryControl OBJECT-TYPE
SYNTAX INTEGER
{
off(0),
on(1),
cycle-power(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This object represents the current and persistent (configured)
power state of the receptacle. The receptacle can also be
controlled by writing to this object.
off
The current and persisted (configured) power state of the
receptacle is 'off'. When writing 'off' to this object the
receptacle, if ON, will be turned OFF and its persistent
(configured) power state will be set to 'off'.
on
The current and persisted (configured) power state of the
receptacle is 'on'. When writing 'on' to this object the
receptacle, if 'off', will be turned 'on' and its persistent
(configured) power state will be set to 'on'.
cycle-power
The receptacle is currently in a power-cycle state. The
power to the receptacle is being turned off momentarily and
will then revert to being 'on'.
When writing 'cycle-power' to this OBJECT if the receptacle is
'on' it will be momentarily turned 'off' and then revert to the
'on' state. The receptacle's persistent (configured) power
state will be left unchanged ('on').
If the receptacle is OFF writing cycle-power has no
affect on the receptacle.
"
::= { lgpPduRcpEntry 100 }
lgpPduRcpEntryControlLock OBJECT-TYPE
SYNTAX INTEGER
{
unknown(0),
unlocked(1),
locked(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This object represents the locked state of the receptacle.
unknown
The lock state of the receptacle is not known at this time.
locked
If the receptacle is 'locked' then its current persisted
(configured) state can not be changed.
unlocked
If the receptacle is 'unlocked', then a user with proper
permissions may change the receptacles state."
::= { lgpPduRcpEntry 105 }
lgpPduRcpEntryEcThrshldUnderAlarm OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Percent"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The threshold at which an under current alarm is activated. If
the measured current (lgpPduRbLineEntryEcLL) is equal to or below
this percentage of the full scale rated value
(lgpPduRbEntryEcRated), an under current alarm
is activated"
::= { lgpPduRcpEntry 150 }
lgpPduRcpEntryEcThrshldOverWarn OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Percent"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The threshold at which an over current warning is activated. If
the measured current (lgpPduRbLineEntryEcLL) is equal to or over
this percentage of the full scale rated value
(lgpPduRbEntryEcRated), an over current warning
is activated"
::= { lgpPduRcpEntry 151 }
lgpPduRcpEntryEcThrshldOverAlarm OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Percent"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The threshold at which an over current alarm is activated. If
the measured current (lgpPduRbLineEntryEcLL) is equal to or over
this percentage of the full scale rated value
(lgpPduRbEntryEcRated), an over current alarm
is activated"
::= { lgpPduRcpEntry 152 }
lgpPduRcpEntryEcAvailBeforeAlarmHundredths OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 Amps-AC-RMS"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The amount that the current/amperage may increase from its present
value before an over current alarm occurs."
::= { lgpPduRcpEntry 159 }
lgpPduRcpEntryEcAvailBeforeAlarm OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Amps-AC-RMS"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The amount that the current/amperage may increase from its present
value before an over current alarm occurs."
::= { lgpPduRcpEntry 160 }
lgpPduRcpEntryEcUsedBeforeAlarm OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The percent of current utilization relative to the over current
alarm threshold."
::= { lgpPduRcpEntry 161 }
lgpPduRcpEntryEcCrestFactor OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Receptacle current crest factor, which is the peak amplitude of the
current waveform divided by the RMS value of the waveform."
::= { lgpPduRcpEntry 162 }
lgpPduRcpEntryBlinkLED OBJECT-TYPE
SYNTAX INTEGER
{
noAction(1),
blinkLED(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Blink the receptacle LED. Writing blinkLED(2) will cause the LED
to blink for a predefined duration of time. Reading this object
will always return noAction(1)."
::= { lgpPduRcpEntry 200 }
lgpPduRcpEntrySwOverTemperatureProtection OBJECT-TYPE
SYNTAX INTEGER
{
disable(0),
enable(1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The configuration parameter to enable or disable the Receptacle
SW Over Temperature Protection feature
If the feature is enabled, in case of Over Temperature Alarm condition,
following action will be taken on the receptacles:
Locked & Off - No Change
Unlocked & Off - No Change
Unlocked & On - Turn it Off.
Locked & On - Turn it Off and keep it Locked.
No action will be taken if the feature is disabled."
::= { lgpPduRcpEntry 205 }
lgpPduRcpEntryOperationCondition OBJECT-TYPE
SYNTAX INTEGER
{
normalOperation(1),
normalWithWarning(2),
normalWithAlarm(3),
abnormal(4)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Receptacle Operating Condition - indicates the condition of the receptacle.
The operating condition has the following:
Normal
Normal operation without any alarm or warning.
Alarm
An Alarm condition due to over/under current.
Warning
A Warning condition due to over/under current
Abnormal
A condition in which the outlet is in 'Power Off State' but still drawing current."
::= { lgpPduRcpEntry 210 }
lgpPduRcpEntryCriticality OBJECT-TYPE
SYNTAX INTEGER
{
critical(0),
notCritical(1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The configuration parameter can be used by the user to mark a receptacle as
critical or non-critical."
::= { lgpPduRcpEntry 215 }
lgpPduRcpEntryPostOnDelay OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The 'Post On Delay' is the time interval (in seconds) that the PDU waits after
a command is issued to switch ON a receptacle before applying power to the receptacle
A value of zero implies that there is no delay (i.e. the receptacle is turned on
immediately on command issue)."
::= { lgpPduRcpEntry 220 }
lgpPduRcpEntryPostOffDelay OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The 'Post Off Delay' is the time interval (in seconds) that the PDU waits after
a command is issued to switch OFF a receptacle before removing power from the receptacle
A value of zero implies that there is no delay (i.e. the receptacle is turned off
immediately on command issue)."
::= { lgpPduRcpEntry 225 }
lgpPduRcpEntryAddReceptacleToGroup OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This receptacle can be added to a group by writing a corresponding
OID to this column. The OID must be a pointer to the
lgpPduRcpGroupUsrLabel from the lgpPduRcpGroupTable.
For example, to add this receptacle to group 1, the oid
.1.3.6.1.4.1.476.1.42.3.8.50.30.10.1.1 would be written to
this column."
::= { lgpPduRcpEntry 230 }
lgpPduRcpEntryRemoveReceptacleFromGroup OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This receptacle can be removed from a group by writing a corresponding
OID to this column. The OID must be a pointer to the
lgpPduRcpGroupUsrLabel from the lgpPduRcpGroupTable.
For example, to remove this receptacle from group 1, the oid
.1.3.6.1.4.1.476.1.42.3.8.50.30.10.1.1 would be written to
this column."
::= { lgpPduRcpEntry 235 }
-- -----------------------------------------------------------------------------
-- PDU Receptacle Group Table
-- -----------------------------------------------------------------------------
lgpPduRcpGroup OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree contains information about receptacle groups.
Receptacle groups are supported by some PDU's and allow control of
multiple receptacles at a time by issuing commands to an associated
receptacle group."
REFERENCE
"The registrations for the objects in this sub-tree are
defined below."
::= { lgpPduReceptacle 30 }
lgpPduRcpGroupTableCount OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Count"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of receptacle groups (rows) in the lgpPduRcpGroupTable."
::= { lgpPduRcpGroup 9 }
lgpPduRcpGroupTable OBJECT-TYPE
SYNTAX SEQUENCE OF LgpPduRcpGroupEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains a list of the possible receptacle groups
that can be created. The table contains a fixed number of rows, which
is the maximum number of receptacle groups that can be used."
::= { lgpPduRcpGroup 10 }
lgpPduRcpGroupEntry OBJECT-TYPE
SYNTAX LgpPduRcpGroupEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This entry defines the attributes to be populated in the
various columns of the 'lgpPduRcpGroupTable'.
This table is indexed by lgpPduRcpGroupIndex.
"
INDEX
{
lgpPduRcpGroupIndex
}
::= { lgpPduRcpGroupTable 1 }
LgpPduRcpGroupEntry ::= SEQUENCE
{
lgpPduRcpGroupIndex Unsigned32,
lgpPduRcpGroupUsrLabel DisplayString,
lgpPduRcpGroupDeleteGroup INTEGER,
lgpPduRcpGroupControlPower INTEGER,
lgpPduRcpGroupControlLock INTEGER,
lgpPduRcpGroupBlinkLED INTEGER
}
lgpPduRcpGroupIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This is an index into the table. There will always be 64 rows,
each representing a separate receptacle group.
"
::= { lgpPduRcpGroupEntry 1 }
lgpPduRcpGroupUsrLabel OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User assigned identifier for this receptacle group."
::= { lgpPduRcpGroupEntry 10 }
lgpPduRcpGroupDeleteGroup OBJECT-TYPE
SYNTAX INTEGER
{
no-action(0),
delete-receptacle-group(1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This column will delete the receptacles from the group when written to."
::= { lgpPduRcpGroupEntry 20 }
lgpPduRcpGroupControlPower OBJECT-TYPE
SYNTAX INTEGER
{
no-action(0),
off(1),
on(2),
cycle-power(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This column controls the power to the group of receptacles. The corresponding
operation will be performed on all receptacles that have been added to the group.
"
::= { lgpPduRcpGroupEntry 30 }
lgpPduRcpGroupControlLock OBJECT-TYPE
SYNTAX INTEGER
{
no-action(0),
unlock(1),
lock(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This column controls the locking of the group of receptacles. The corresponding
operation will be performed on all receptacles that have been added to the group.
"
::= { lgpPduRcpGroupEntry 40 }
lgpPduRcpGroupBlinkLED OBJECT-TYPE
SYNTAX INTEGER
{
no-action(0),
blinkLED(1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This column will blink the LED's associated with all receptacles that are part of
the group.
"
::= { lgpPduRcpGroupEntry 50 }
-- -----------------------------------------------------------------------------
-- PDU Receptacle Group Display Table
-- -----------------------------------------------------------------------------
lgpPduRcpGroupDisplayTableCount OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Count"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of rows currently in the lgpPduRcpGroupDisplayTable."
::= { lgpPduRcpGroup 19 }
lgpPduRcpGroupDisplayTable OBJECT-TYPE
SYNTAX SEQUENCE OF LgpPduRcpGroupDisplayEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table is used to display which receptacle groups are currently
defined and which receptacles are associated with each group.
The table will have 0 rows when no receptacles have been added to any receptacle
groups. If a single receptacle has been added to 2 different groups,
there will be 2 rows in the table.
"
::= { lgpPduRcpGroup 20 }
lgpPduRcpGroupDisplayEntry OBJECT-TYPE
SYNTAX LgpPduRcpGroupDisplayEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This entry defines the attributes to be populated in the
various columns of the 'lgpPduRcpGroupDisplayTable'.
This table is indexed by two indexes.
The 'lgpPduRcpGroupIndex' references a receptacle group in
the 'lgpPduRcpGroupTable' that a given row in this table represents.
The 'lgpPduEntryIndex' references a PDU in the 'lgpPduTable'
that identifies the particular PDU receptacle list
within the receptacle group.
"
INDEX
{
lgpPduRcpGroupIndex,
lgpPduEntryIndex
}
::= { lgpPduRcpGroupDisplayTable 1 }
LgpPduRcpGroupDisplayEntry ::= SEQUENCE
{
lgpPduRcpGroupDisplayIndex Unsigned32,
lgpPduRcpGroupDisplayGroup DisplayString
}
lgpPduRcpGroupDisplayIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This is an index into the table. There can be zero or more rows
in this table."
::= { lgpPduRcpGroupDisplayEntry 10 }
lgpPduRcpGroupDisplayGroup OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This column displays the PDU receptacle list of the specified
receptacle group. The value in this column is a comma delimted string that decribes
the list of receptacles of a PDU that are members of the receptacle group.
For example, if receptacles 1 and 3 of branch A and receptacles 2 and 4
of branch B are members of the receptacle group, this column
would show: A-1,A-3,B-2,B-4"
::= { lgpPduRcpGroupDisplayEntry 20 }
-- -----------------------------------------------------------------------------
-- PDU Auxiliary Sensors
-- -----------------------------------------------------------------------------
lgpPduAuxiliarySensors OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree contains information about PDU Auxiliary Sensors."
REFERENCE
"The registrations for the objects in this sub-tree are
defined below."
::= { lgpPdu 60 }
lgpPduAuxSensorCount OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Count"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of auxiliary sensors in the lgpPduAuxSensorTable."
::= { lgpPduAuxiliarySensors 5 }
lgpPduAuxSensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF LgpPduAuxSensorEntry
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION
"This table contains a list of the PDU's Auxiliary Sensors.
The table contains zero, one, or more rows, depending
upon the number of PDUs being monitored and the number of
auxiliary sensors installed for each PDU.
The NMS cannot create or delete rows in the table. The rows are
created by the agent based upon the capabilities of the PDUs
being monitored. Each row in the table represents an auxiliary
sensor in a PDU."
::= { lgpPduAuxiliarySensors 10 }
lgpPduAuxSensorEntry OBJECT-TYPE
SYNTAX LgpPduAuxSensorEntry
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION
"This entry defines the attributes to be populated in the
various columns of the 'lgpPduAuxSensorTable'.
This table is indexed by both the 'lgpPduEntryIndex' which is
the sole index into the 'lgpPduTable' and the
'lgpPduAuxSensorIndex'which is a unique identifier for the
auxiliary sensor attached to the given PDU. Taken together these
two indexes uniquely identify an Auxiliary Sensor within this
agent."
INDEX
{
lgpPduEntryIndex,
lgpPduAuxSensorIndex
}
::= { lgpPduAuxSensorTable 1 }
LgpPduAuxSensorEntry ::= SEQUENCE
{
lgpPduAuxSensorIndex Unsigned32,
lgpPduAuxSensorMeasType INTEGER,
lgpPduAuxSensorId Unsigned32,
lgpPduAuxSensorSysAssignLabel DisplayString,
lgpPduAuxSensorPositionRelative Unsigned32,
lgpPduAuxSensorUsrLabel DisplayString,
lgpPduAuxSensorUsrTag1 DisplayString,
lgpPduAuxSensorUsrTag2 DisplayString,
lgpPduAuxSensorTempSerialNum DisplayString,
lgpPduAuxSensorHumSerialNum DisplayString,
lgpPduAuxSensorTempMeasurementDegF Integer32,
lgpPduAuxSensorTempThrshldUndrAlmDegF Integer32,
lgpPduAuxSensorTempThrshldOvrAlmDegF Integer32,
lgpPduAuxSensorTempThrshldUndrWarnDegF Integer32,
lgpPduAuxSensorTempThrshldOvrWarnDegF Integer32,
lgpPduAuxSensorTempMeasurementDegC Integer32,
lgpPduAuxSensorTempThrshldUndrAlmDegC Integer32,
lgpPduAuxSensorTempThrshldOvrAlmDegC Integer32,
lgpPduAuxSensorTempThrshldUndrWarnDegC Integer32,
lgpPduAuxSensorTempThrshldOvrWarnDegC Integer32,
lgpPduAuxSensorHumMeasurement Unsigned32,
lgpPduAuxSensorHumThrshldUndrAlm Unsigned32,
lgpPduAuxSensorHumThrshldOvrAlm Unsigned32,
lgpPduAuxSensorHumThrshldUndrWarn Unsigned32,
lgpPduAuxSensorHumThrshldOvrWarn Unsigned32
}
lgpPduAuxSensorIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION
"This is the index indicating the nth element of the table."
::= { lgpPduAuxSensorEntry 1 }
lgpPduAuxSensorMeasType OBJECT-TYPE
SYNTAX INTEGER
{
not-specified(0),
temperature(1),
humidity(2),
temperature-and-humidity(3)
}
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"not-specified
The type of sensor is unknown.
temperature
The sensor in this row of the table measures temperature.
humidity
The sensor in this row of the table measures relative humidity.
temperature-and-humidity
The sensor in this row of the table measures both temperature
and relative humidity."
::= { lgpPduAuxSensorEntry 5 }
lgpPduAuxSensorId OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"System assigned auxiliary sensor identification number. The value
assigned is product specific."
::= { lgpPduAuxSensorEntry 10 }
lgpPduAuxSensorSysAssignLabel OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Label assigned to the auxiliary sensor at runtime by the system.
The value is independent of any user assigned label or asset tag."
::= { lgpPduAuxSensorEntry 15 }
lgpPduAuxSensorPositionRelative OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Auxiliary sensor relative position. This is a one-based value
that indicates the sensor's position relative to the sensor string
connector."
::= { lgpPduAuxSensorEntry 20 }
lgpPduAuxSensorUsrLabel OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"User assigned auxiliary sensor label."
::= { lgpPduAuxSensorEntry 25 }
lgpPduAuxSensorUsrTag1 OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"User assigned Tag to assist in identifying or grouping this
auxiliary sensor within the end-users domain."
::= { lgpPduAuxSensorEntry 30 }
lgpPduAuxSensorUsrTag2 OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"User assigned Tag to assist in identifying or grouping this
auxiliary sensor within the end-users domain."
::= { lgpPduAuxSensorEntry 35 }
lgpPduAuxSensorTempSerialNum OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"The temperature sensor's globally unique serial number assigned at
the time of manufacture."
::= { lgpPduAuxSensorEntry 40 }
lgpPduAuxSensorHumSerialNum OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"The humidity sensor's globally unique serial number assigned at
the time of manufacture."
::= { lgpPduAuxSensorEntry 45 }
lgpPduAuxSensorTempMeasurementDegF OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Fahrenheit"
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Temperature measured at the temperature sensor reported in
degrees Fahrenheit."
::= { lgpPduAuxSensorEntry 50 }
lgpPduAuxSensorTempThrshldUndrAlmDegF OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Fahrenheit"
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"Under temperature alarm threshold. An alarm is activated if the
temperature is equal to or below this value."
::= { lgpPduAuxSensorEntry 55 }
lgpPduAuxSensorTempThrshldOvrAlmDegF OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Fahrenheit"
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"Over temperature alarm threshold. An alarm is activated if the
temperature is equal to or above this value."
::= { lgpPduAuxSensorEntry 60 }
lgpPduAuxSensorTempThrshldUndrWarnDegF OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Fahrenheit"
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"Under temperature warning threshold. A warning is activated if
the temperature is equal to or below this value."
::= { lgpPduAuxSensorEntry 65 }
lgpPduAuxSensorTempThrshldOvrWarnDegF OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Fahrenheit"
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"Over temperature warning threshold. A warning is activated if the
temperature is equal to or above this value."
::= { lgpPduAuxSensorEntry 70 }
lgpPduAuxSensorTempMeasurementDegC OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Celsius"
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Temperature measured at the temperature sensor reported in
degrees Celsius."
::= { lgpPduAuxSensorEntry 75 }
lgpPduAuxSensorTempThrshldUndrAlmDegC OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Celsius"
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"Under temperature alarm threshold. An alarm is activated if the
temperature is equal to or below this value."
::= { lgpPduAuxSensorEntry 80 }
lgpPduAuxSensorTempThrshldOvrAlmDegC OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Celsius"
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"Over temperature alarm threshold. An alarm is activated if the
temperature is equal to or above this value."
::= { lgpPduAuxSensorEntry 85 }
lgpPduAuxSensorTempThrshldUndrWarnDegC OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Celsius"
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"Under temperature warning threshold. A warning is activated if
the temperature is equal to or below this value."
::= { lgpPduAuxSensorEntry 90 }
lgpPduAuxSensorTempThrshldOvrWarnDegC OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Celsius"
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"Over temperature warning threshold. A warning is activated if the
temperature is equal to or above this value."
::= { lgpPduAuxSensorEntry 95 }
lgpPduAuxSensorHumMeasurement OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 percent Relative Humidity"
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Relative Humidity measured at the humidity sensor."
::= { lgpPduAuxSensorEntry 100 }
lgpPduAuxSensorHumThrshldUndrAlm OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 percent Relative Humidity"
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"Under relative humidity alarm threshold. An alarm is activated
if the relative humidity is equal to or below this value."
::= { lgpPduAuxSensorEntry 105 }
lgpPduAuxSensorHumThrshldOvrAlm OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 percent Relative Humidity"
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"Over relative humidity alarm threshold. An alarm is activated
if the relative humidity is equal to or above this value."
::= { lgpPduAuxSensorEntry 110 }
lgpPduAuxSensorHumThrshldUndrWarn OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 percent Relative Humidity"
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"Under relative humidity warning threshold. A warning is activated
if the relative humidity is equal to or below this value."
::= { lgpPduAuxSensorEntry 115 }
lgpPduAuxSensorHumThrshldOvrWarn OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 percent Relative Humidity"
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"Over relative humidity warning threshold. A warning is activated
if the relative humidity is equal to or above this value."
::= { lgpPduAuxSensorEntry 120 }
lgpPduAuxMeasTable OBJECT-TYPE
SYNTAX SEQUENCE OF LgpPduAuxMeasEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains a list of the PDU's Auxiliary Sensor Measurements.
The table contains zero, one, or more rows, depending
upon the number of PDUs being monitored, the number of auxiliary
sensors installed for each PDU, and the number of measurements within
each sensor. The NMS cannot create or delete rows in the table. The
rows are created by the agent based upon the capabilities of the PDUs
being monitored. Each row in the table represents an auxiliary
sensor measurement in a PDU."
::= { lgpPduAuxiliarySensors 15 }
lgpPduAuxMeasEntry OBJECT-TYPE
SYNTAX LgpPduAuxMeasEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This entry defines the attributes to be populated in the
various columns of the 'lgpPduAuxMeasTable'.
This table is indexed by 'lgpPduEntryIndex' which is
the sole index into the 'lgpPduTable', 'lgpPduAuxSensorIndex' which
is a unique identifier for the auxiliary sensor attached to the
given PDU, and 'lgpPduAuxMeasSensorMeasurementIndex' which is the
measurement's index identified on the sensor. Taken together these
three indexes uniquely identify an Auxiliary Sensor Measurement
within this agent."
INDEX
{
lgpPduEntryIndex,
lgpPduAuxMeasSensorIndex,
lgpPduAuxMeasSensorMeasurementIndex
}
::= { lgpPduAuxMeasTable 1 }
LgpPduAuxMeasEntry ::= SEQUENCE
{
lgpPduAuxMeasSensorIndex Unsigned32,
lgpPduAuxMeasSensorMeasurementIndex Unsigned32,
lgpPduAuxMeasType INTEGER,
lgpPduAuxMeasSensorSysAssignLabel DisplayString,
lgpPduAuxMeasUsrLabel DisplayString,
lgpPduAuxMeasUsrTag1 DisplayString,
lgpPduAuxMeasUsrTag2 DisplayString,
lgpPduAuxMeasSensorSerialNum DisplayString,
lgpPduAuxMeasTempDegF Integer32,
lgpPduAuxMeasTempThrshldUndrAlmDegF Integer32,
lgpPduAuxMeasTempThrshldOvrAlmDegF Integer32,
lgpPduAuxMeasTempThrshldUndrWarnDegF Integer32,
lgpPduAuxMeasTempThrshldOvrWarnDegF Integer32,
lgpPduAuxMeasTempDegC Integer32,
lgpPduAuxMeasTempThrshldUndrAlmDegC Integer32,
lgpPduAuxMeasTempThrshldOvrAlmDegC Integer32,
lgpPduAuxMeasTempThrshldUndrWarnDegC Integer32,
lgpPduAuxMeasTempThrshldOvrWarnDegC Integer32,
lgpPduAuxMeasHum Unsigned32,
lgpPduAuxMeasHumThrshldUndrAlm Unsigned32,
lgpPduAuxMeasHumThrshldOvrAlm Unsigned32,
lgpPduAuxMeasHumThrshldUndrWarn Unsigned32,
lgpPduAuxMeasHumThrshldOvrWarn Unsigned32,
lgpPduAuxMeasDrClosureState INTEGER,
lgpPduAuxMeasDrClosureConfig INTEGER,
lgpPduAuxMeasCntctClosureState INTEGER,
lgpPduAuxMeasCntctClosureConfig INTEGER,
lgpPduAuxMeasDiffPressure Integer32,
lgpPduAuxMeasDiffPressureThrshldUndrAlm Integer32,
lgpPduAuxMeasDiffPressureThrshldOvrAlm Integer32,
lgpPduAuxMeasDiffPressureThrshldUndrWarn Integer32,
lgpPduAuxMeasDiffPressureThrshldOvrWarn Integer32,
lgpPduAuxMeasLeakDetectState INTEGER
}
lgpPduAuxMeasSensorIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This is the index indicating the sensor the measurement is accessed
from."
::= { lgpPduAuxMeasEntry 1 }
lgpPduAuxMeasSensorMeasurementIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This is the measurement's index identified on the sensor."
::= { lgpPduAuxMeasEntry 5 }
lgpPduAuxMeasType OBJECT-TYPE
SYNTAX INTEGER
{
not-specified(0),
temperature(1),
humidity(2),
door-closure(3),
contact-closure(4),
differential-pressure(5),
leak-detection(6)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"not-specified
The type of measurement is unknown.
temperature
The measurement in this row of the table measures temperature.
humidity
The measurement in this row of the table measures relative
humidity.
door-closure
The measurement in this row of the table measures the state of a
door.
contact-closure
The measurement in this row of the table measures the state of a
contact closure.
differential-pressure
The measurement in this row of the table measures differential pressure.
leak-detection
The measurement in this row of the table measures the state of a
leak detection sensor."
::= { lgpPduAuxMeasEntry 10 }
lgpPduAuxMeasSensorSysAssignLabel OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Label assigned to the auxiliary sensor at runtime by the system.
The value is independent of any user assigned label or asset tag."
::= { lgpPduAuxMeasEntry 15 }
lgpPduAuxMeasUsrLabel OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User assigned auxiliary sensor measurement label."
::= { lgpPduAuxMeasEntry 20 }
lgpPduAuxMeasUsrTag1 OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User assigned Tag to assist in identifying or grouping this
auxiliary sensor measurement within the end-users domain."
::= { lgpPduAuxMeasEntry 25 }
lgpPduAuxMeasUsrTag2 OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User assigned Tag to assist in identifying or grouping this
auxiliary sensor measurement within the end-users domain."
::= { lgpPduAuxMeasEntry 30 }
lgpPduAuxMeasSensorSerialNum OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The sensor's globally unique serial number assigned at
the time of manufacture."
::= { lgpPduAuxMeasEntry 35 }
lgpPduAuxMeasTempDegF OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Fahrenheit"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Temperature measured at the temperature sensor reported in
degrees Fahrenheit."
::= { lgpPduAuxMeasEntry 40 }
lgpPduAuxMeasTempThrshldUndrAlmDegF OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Fahrenheit"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Under temperature alarm threshold. An alarm is activated if the
temperature is equal to or below this value."
::= { lgpPduAuxMeasEntry 50 }
lgpPduAuxMeasTempThrshldOvrAlmDegF OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Fahrenheit"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Over temperature alarm threshold. An alarm is activated if the
temperature is equal to or above this value."
::= { lgpPduAuxMeasEntry 55 }
lgpPduAuxMeasTempThrshldUndrWarnDegF OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Fahrenheit"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Under temperature warning threshold. A warning is activated if
the temperature is equal to or below this value."
::= { lgpPduAuxMeasEntry 60 }
lgpPduAuxMeasTempThrshldOvrWarnDegF OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Fahrenheit"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Over temperature warning threshold. A warning is activated if the
temperature is equal to or above this value."
::= { lgpPduAuxMeasEntry 65 }
lgpPduAuxMeasTempDegC OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Celsius"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Temperature measured at the temperature sensor reported in
degrees Celsius."
::= { lgpPduAuxMeasEntry 70 }
lgpPduAuxMeasTempThrshldUndrAlmDegC OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Celsius"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Under temperature alarm threshold. An alarm is activated if the
temperature is equal to or below this value."
::= { lgpPduAuxMeasEntry 75 }
lgpPduAuxMeasTempThrshldOvrAlmDegC OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Celsius"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Over temperature alarm threshold. An alarm is activated if the
temperature is equal to or above this value."
::= { lgpPduAuxMeasEntry 80 }
lgpPduAuxMeasTempThrshldUndrWarnDegC OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Celsius"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Under temperature warning threshold. A warning is activated if
the temperature is equal to or below this value."
::= { lgpPduAuxMeasEntry 85 }
lgpPduAuxMeasTempThrshldOvrWarnDegC OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Celsius"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Over temperature warning threshold. A warning is activated if the
temperature is equal to or above this value."
::= { lgpPduAuxMeasEntry 90 }
lgpPduAuxMeasHum OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 percent Relative Humidity"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Relative Humidity measured at the humidity sensor."
::= { lgpPduAuxMeasEntry 95 }
lgpPduAuxMeasHumThrshldUndrAlm OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 percent Relative Humidity"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Under relative humidity alarm threshold. An alarm is activated
if the relative humidity is equal to or below this value."
::= { lgpPduAuxMeasEntry 100 }
lgpPduAuxMeasHumThrshldOvrAlm OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 percent Relative Humidity"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Over relative humidity alarm threshold. An alarm is activated
if the relative humidity is equal to or above this value."
::= { lgpPduAuxMeasEntry 105 }
lgpPduAuxMeasHumThrshldUndrWarn OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 percent Relative Humidity"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Under relative humidity warning threshold. A warning is activated
if the relative humidity is equal to or below this value."
::= { lgpPduAuxMeasEntry 110 }
lgpPduAuxMeasHumThrshldOvrWarn OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 percent Relative Humidity"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Over relative humidity warning threshold. A warning is activated
if the relative humidity is equal to or above this value."
::= { lgpPduAuxMeasEntry 115 }
lgpPduAuxMeasDrClosureState OBJECT-TYPE
SYNTAX INTEGER
{
not-specified(0),
open(1),
closed(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The state of a door sensor measurement.
not-specified
The door state is unknown.
open
The door is in the open state.
closed
The door is in the closed state."
::= { lgpPduAuxMeasEntry 120 }
lgpPduAuxMeasDrClosureConfig OBJECT-TYPE
SYNTAX INTEGER
{
disabled(0),
alarm-when-open(1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Configure door state alarms. This object provides the ability to
select when a door closure measurement should cause an alarm.
disabled
The door state will never result in alarm.
alarm-when-open
Activate an alarm when the door state becomes open."
::= { lgpPduAuxMeasEntry 125 }
lgpPduAuxMeasCntctClosureState OBJECT-TYPE
SYNTAX INTEGER
{
not-specified(0),
open(1),
closed(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The state of a contact closure sensor measurement.
not-specified
The contact closure state is unknown.
open
The contact closure is in the open state.
closed
The contact closure is in the closed state."
::= { lgpPduAuxMeasEntry 130 }
lgpPduAuxMeasCntctClosureConfig OBJECT-TYPE
SYNTAX INTEGER
{
disabled(0),
alarm-when-open(1),
alarm-when-closed(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Configure contact closure state alarms. This object provides the
ability to select when a contact closure measurement should
activate an alarm.
disabled
The contact closure state will never result in alarm.
alarm-when-open
Activate an alarm when the contact closure state becomes
open.
alarm-when-closed
Activate an alarm when the contact closure state becomes
closed."
::= { lgpPduAuxMeasEntry 135 }
lgpPduAuxMeasDiffPressure OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 Pascal"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Pressure difference measured at the differential pressure sensor."
::= { lgpPduAuxMeasEntry 140 }
lgpPduAuxMeasDiffPressureThrshldUndrAlm OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 Pascal"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Under differential pressure alarm threshold. An alarm is activated
if the differential pressure is equal to or below this value."
::= { lgpPduAuxMeasEntry 145 }
lgpPduAuxMeasDiffPressureThrshldOvrAlm OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 Pascal"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Over differential pressure alarm threshold. An alarm is activated
if the differential pressure is equal to or above this value."
::= { lgpPduAuxMeasEntry 150 }
lgpPduAuxMeasDiffPressureThrshldUndrWarn OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 Pascal"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Under differential pressure warning threshold. A warning is activated
if the differential pressure is equal to or below this value."
::= { lgpPduAuxMeasEntry 155 }
lgpPduAuxMeasDiffPressureThrshldOvrWarn OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 Pascal"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Over differential pressure warning threshold. A warning is activated
if the differential pressure is equal to or above this value."
::= { lgpPduAuxMeasEntry 160 }
lgpPduAuxMeasLeakDetectState OBJECT-TYPE
SYNTAX INTEGER
{
not-specified(0),
no-leak-detected(1),
leak-detected(2),
leak-detection-pending(3),
cable-fault(4)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"not-specified
The leak detection state is unknown.
no-leak-detected
No leak has been detected.
leak-detected
A leak has been detected.
leak-detection-pending
Characterization of possible leak is pending further analysis
based on new data received from the sensor.
This state may not occur at all, but if it does, it should occur
only for a small amount of time before transitioning to
no-leak-detected or leak-detected.
cable-fault
A fault in the cable has been detected (for example, a
disconnected cable). The sensor will not be able to detect
a leak.
"
::= { lgpPduAuxMeasEntry 165 }
lgpPduAuxMeasOrderTable OBJECT-TYPE
SYNTAX SEQUENCE OF LgpPduAuxMeasOrderEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains a list of the PDU's Auxiliary Sensors
and their respective 'location' in the lgpPduAuxMeasTable table.
This table contains 1 row, for potential sensor for each PDU.
The rows in this table are created by the agent based on the maximum
number of sensor's supported for each PDU.
Each row in the table represents an auxiliary sensor, identified by its
factory assigned serial number and its placement in the lgpPduAuxMeasTable.
If all serial numbers in this table are empty strings then the
location of the sensors in the lgpPduAuxMeasTable will default to the
agent's default placement algorithm. If sensors in the
lgpPduAuxMeasTable and are not represented by an entry in this table then
the location of the unrepresented sensor(s) in the lgpPduAuxMeasTable,
and other display mediums, will be determined by the agent, but in no
case will an unrepresented sensor occupy a position reserved for a sensor
present in this table. Those unrepresented sensor's display location is
not guaranteed to be consistent across reboots or rediscovery actions
on the sensor bus. Only sensors represented in this table are guarantted
consistent placement as specified by their index entries (position) in
this table.
Note that it is possible to have entries in this table representing sensors
that may not exist on the given PDU at runtime. These allocated by not present
sensors will reduce the total number of sensors that can be displayed for
the given PDU."
::= { lgpPduAuxiliarySensors 20 }
lgpPduAuxMeasOrderEntry OBJECT-TYPE
SYNTAX LgpPduAuxMeasOrderEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This entry defines the attributes to be populated in the
various columns of the 'lgpPduAuxMeasOrderTable'.
This table is indexed by 'lgpPduEntryIndex' which is
the sole index into the 'lgpPduTable' and 'lgpPduAuxMeasSensorIndex'
which is a unique identifier for the auxiliary sensor attached to the
given PDU. Taken together these two indexes uniquely
identify a Auxiliary Sensor within this agent."
INDEX
{
lgpPduEntryIndex,
lgpPduAuxSensorOrderIndex
}
::= { lgpPduAuxMeasOrderTable 1 }
LgpPduAuxMeasOrderEntry ::= SEQUENCE
{
lgpPduEntryIndex Unsigned32,
lgpPduAuxSensorOrderIndex Unsigned32,
lgpPduAuxMeasOrderSensorSerialNum DisplayString
}
lgpPduAuxSensorOrderIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Index representing the position within the sensor string on the given PDU"
::= { lgpPduAuxMeasOrderEntry 5 }
lgpPduAuxMeasOrderSensorSerialNum OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The sensor's globally unique serial number assigned at
the time of manufacture. The sensor represented by this
serial number will be, if discovered, by the agent placed
in the lgpPduAuxMeasTable at the location specified by the
index entries herein. A empty string in this object indicates
an open display position that can be occupied by any sensor not
given a specific display position in this table."
::= { lgpPduAuxMeasOrderEntry 15 }
END