397 lines
14 KiB
Plaintext
397 lines
14 KiB
Plaintext
-- ----------------------------------------------------------------------------
|
|
--
|
|
-- SIAE MICROELETTRONICA s.p.a.
|
|
--
|
|
-- Via Michelangelo Buonarroti, 21
|
|
-- 20093 - Cologno Monzese
|
|
-- Milano
|
|
-- ITALY
|
|
--
|
|
-- ----------------------------------------------------------------------------
|
|
-- ----------------------------------------------------------------------------
|
|
|
|
SIAE-SENSOR-TEMP-MIB
|
|
DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
MODULE-IDENTITY, OBJECT-TYPE,
|
|
Integer32
|
|
FROM SNMPv2-SMI
|
|
DisplayString
|
|
FROM SNMPv2-TC
|
|
siaeMib
|
|
FROM SIAE-TREE-MIB
|
|
AlarmStatus, AlarmSeverityCode
|
|
FROM SIAE-ALARM-MIB;
|
|
|
|
sensorTemp MODULE-IDENTITY
|
|
LAST-UPDATED "201605030000Z"
|
|
ORGANIZATION "SIAE MICROELETTRONICA spa"
|
|
CONTACT-INFO
|
|
"SIAE MICROELETTONICA s.p.a.
|
|
Via Michelangelo Buonarroti, 21
|
|
20093 - Cologno Monzese
|
|
Milano - ITALY
|
|
Phone : +39-02-27325-1
|
|
E-mail: tbd@siaemic.com
|
|
"
|
|
DESCRIPTION
|
|
"Management information for equipment heat.
|
|
"
|
|
REVISION "201605030000Z"
|
|
DESCRIPTION
|
|
"MIB version 01.00.01
|
|
- Added sensorTempMonitorTable and sensorTempMonitorSystemControl
|
|
- Added DEFVAL clause to sensorTempAlarmThreshold1Severity and
|
|
sensorTempAlarmThreshold2Severity
|
|
"
|
|
REVISION "201403310000Z"
|
|
DESCRIPTION
|
|
"Initial version 01.00.00
|
|
"
|
|
::= { siaeMib 77 }
|
|
|
|
----------------------------------------------------------------------------------
|
|
-- Temperature Sensors Management information
|
|
----------------------------------------------------------------------------------
|
|
--
|
|
-- This MIB is used to describe the temperature devices available on the equipment.
|
|
-- Each device represents a temperature sensor. It displays the current temperature.
|
|
-- Each records has got 2 thresholds passing one of them an indication is generated.
|
|
-- When at least one device has got a pass indication an alarm rises.
|
|
-- The alarm drops when the temperature is 5°C under the threshold which generates the
|
|
-- indication.
|
|
--
|
|
----------------------------------------------------------------------------------
|
|
|
|
------ Beginning --------------------------------------------------------------
|
|
|
|
sensorTempMibVersion OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Numerical version of this module.
|
|
The string version of this MIB have the following format:
|
|
XX.YY.ZZ
|
|
so, for example, the value 1 should be interpreted as 00.00.01
|
|
and the value 10001 should be interpreted as 01.00.01."
|
|
::= {sensorTemp 1}
|
|
|
|
------- Begin of sensorTempTable
|
|
--
|
|
|
|
sensorTempTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF SensorTempEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table with sensorTemp device entries"
|
|
::= {sensorTemp 2}
|
|
|
|
sensorTempEntry OBJECT-TYPE
|
|
SYNTAX SensorTempEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature Sensor entry"
|
|
INDEX {sensorTempIndex}
|
|
::= {sensorTempTable 1}
|
|
|
|
SensorTempEntry ::=
|
|
SEQUENCE {
|
|
sensorTempIndex Integer32,
|
|
sensorTempValue Integer32,
|
|
sensorTempThreshold1 Integer32,
|
|
sensorTempThreshold2 Integer32,
|
|
sensorTempHysteresis1 Integer32,
|
|
sensorTempHysteresis2 Integer32,
|
|
sensorTempStatus1 INTEGER,
|
|
sensorTempStatus2 INTEGER,
|
|
sensorTempLabel DisplayString
|
|
}
|
|
|
|
sensorTempIndex OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature Sensor index.
|
|
"
|
|
::= {sensorTempEntry 1}
|
|
|
|
sensorTempValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Value of the temperature (in Celsius).
|
|
"
|
|
::= {sensorTempEntry 2}
|
|
|
|
sensorTempThreshold1 OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This object can not be modified. It reports the temperature threshold 1.
|
|
When sensorTempValue exceeds this value sensorTempStatus1 becomes Active.
|
|
When threshold has been exceed status returns stand-by only when sensorTempValue
|
|
goes under sensorTempHysteresis1.
|
|
"
|
|
::= {sensorTempEntry 3}
|
|
|
|
sensorTempThreshold2 OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This object can not be modified. It reports the temperature threshold 2.
|
|
When sensorTempValue exceeds this value sensorTempStatus2 becomes Active.
|
|
When threshold has been exceed status returns stand-by only when sensorTempValue
|
|
goes under sensorTempHysteresis2.
|
|
"
|
|
::= {sensorTempEntry 4}
|
|
|
|
sensorTempHysteresis1 OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This object can not be modified. It reports the temperature hysteresis 1.
|
|
When sensorTempStatus1 is Active it represents the value under which returns
|
|
cleared.
|
|
"
|
|
::= {sensorTempEntry 5}
|
|
|
|
sensorTempHysteresis2 OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This object can not be modified. It reports the temperature hysteresis 2.
|
|
When sensorTempStatus1 is Active it represents the value under which returns
|
|
cleared.
|
|
"
|
|
::= {sensorTempEntry 6}
|
|
|
|
sensorTempStatus1 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
cleared (1),
|
|
alarmed (2),
|
|
hysteresis (3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This object is used to manage temperature related to sensorTempThreshold1.
|
|
Values mean:
|
|
cleared: sensorTempValue is lower than threshold1
|
|
active: sensorTempValue is greater than threshold1
|
|
hysteresis: sensorTempValue is between threshold1 and hysteresis1 but
|
|
previuosly greater than thresold1.
|
|
"
|
|
::= {sensorTempEntry 7}
|
|
|
|
sensorTempStatus2 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
cleared (1),
|
|
alarmed (2),
|
|
hysteresis (3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This object is used to manage temperature related to sensorTempThreshold2.
|
|
Values mean:
|
|
cleared: sensorTempValue is lower than threshold2
|
|
active: sensorTempValue is greater than threshold2
|
|
hysteresis: sensorTempValue is between threshold2 and hysteresis2 but
|
|
previuosly greater than thresold2.
|
|
"
|
|
::= {sensorTempEntry 8}
|
|
|
|
sensorTempLabel OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..32))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A textual string containing information on sensorTemp sensor.
|
|
"
|
|
::= {sensorTempEntry 9}
|
|
|
|
--
|
|
------- End of sensorTempTable
|
|
|
|
sensorTempAlarmThreshold1 OBJECT-TYPE
|
|
SYNTAX AlarmStatus
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This object is used to notiy alarm if at least one entry in the
|
|
sensorTemp table has got sensorTempStatus1 alarmed."
|
|
::= {sensorTemp 3}
|
|
|
|
sensorTempAlarmThreshold2 OBJECT-TYPE
|
|
SYNTAX AlarmStatus
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This object is used to notiy alarm if at least one entry in the
|
|
sensorTemp table has got sensorTempStatus2 alarmed."
|
|
::= {sensorTemp 4}
|
|
|
|
sensorTempAlarmThreshold1Severity OBJECT-TYPE
|
|
SYNTAX AlarmSeverityCode
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This object is used to change severity of sensorTempAlarmThreshold1."
|
|
DEFVAL { warningTrapEnable }
|
|
::= {sensorTemp 5}
|
|
|
|
sensorTempAlarmThreshold2Severity OBJECT-TYPE
|
|
SYNTAX AlarmSeverityCode
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This object is used to change severity of sensorTempAlarmThreshold2."
|
|
DEFVAL { criticalTrapEnable }
|
|
::= {sensorTemp 6}
|
|
|
|
----------------------------------------------------------------------------------
|
|
-- TEMP-MONITOR feature
|
|
----------------------------------------------------------------------------------
|
|
--
|
|
-- For each temperature sensor shown in sensorTempMonitorTable it is possible
|
|
-- to register a record every 15 min. Each record includes, along with some
|
|
-- auxiliary information, the min, max and average temperature observed in
|
|
-- the period of time. The registered data can be exported to the SNMP manager
|
|
-- by using SIAE-PMFTP-MIB.
|
|
--
|
|
----------------------------------------------------------------------------------
|
|
|
|
------- Begin of sensorTempMonitorTable
|
|
--
|
|
|
|
sensorTempMonitorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF SensorTempMonitorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table with sensorTempMonitor entries"
|
|
::= {sensorTemp 7}
|
|
|
|
sensorTempMonitorEntry OBJECT-TYPE
|
|
SYNTAX SensorTempMonitorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature Sensor Monitor entry"
|
|
INDEX {sensorTempIndex}
|
|
::= {sensorTempMonitorTable 1}
|
|
|
|
SensorTempMonitorEntry ::=
|
|
SEQUENCE {
|
|
sensorTempMonitorAdminStatus INTEGER,
|
|
sensorTempMonitorOperStatus INTEGER,
|
|
sensorTempMonitorMinTemp Integer32,
|
|
sensorTempMonitorMaxTemp Integer32,
|
|
sensorTempMonitorAverageTemp Integer32
|
|
}
|
|
|
|
sensorTempMonitorAdminStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
up (1),
|
|
down (2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The desired state of the temperatuure monitor.
|
|
|
|
When a managed system initializes, all the temperature
|
|
monitors start with sensorTempMonitorAdminStatus in the
|
|
down(2) state, it's a default state also. As a result
|
|
of either explicit management action or per configuration
|
|
information retained by the managed system,
|
|
sensorTempMonitorAdminStatus is then changed to the up(1)
|
|
state (or remains in the down(2) state).
|
|
"
|
|
DEFVAL { down }
|
|
::= {sensorTempMonitorEntry 1}
|
|
|
|
|
|
sensorTempMonitorOperStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
up (1),
|
|
down (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current state of the temperatuure monitor. Usually
|
|
this object report the same value of sensorTempMonitorAdminStatus.
|
|
When there is some problem related to the temperature sensor,
|
|
this object shown the down(2) value even if sensorTempMonitorAdminStatus
|
|
is set to up(1).
|
|
"
|
|
::= {sensorTempMonitorEntry 2}
|
|
|
|
sensorTempMonitorMinTemp OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The minimum value of the temperature measured in the last actual
|
|
900 seconds. The value is expressed in degrees Celsius.
|
|
"
|
|
::= {sensorTempMonitorEntry 3}
|
|
|
|
sensorTempMonitorMaxTemp OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The maximum value of the temperature measured in the last actual
|
|
900 seconds. The value is expressed in degrees Celsius.
|
|
"
|
|
::= {sensorTempMonitorEntry 4}
|
|
|
|
sensorTempMonitorAverageTemp OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The average value of the temperature measured in the last actual
|
|
900 seconds. The value is expressed in tenth of degrees Celsius.
|
|
"
|
|
::= {sensorTempMonitorEntry 5}
|
|
|
|
--
|
|
------- End of sensorTempMonitorTable
|
|
|
|
sensorTempMonitorSystemControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
start(1),
|
|
shutdown(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The administrative system control status requested by management
|
|
for the TEMP-MONITOR feature. The value 'start'(1) indicates that
|
|
TEMP-MONITOR should be supported in the device on all temperature
|
|
sensors that have this capability (Those shown in
|
|
sensorTempMonitorTable). The value shutdown(2) indicates
|
|
that TEMP-MONITOR should be shutdown in the device on all
|
|
temperature sensors.
|
|
"
|
|
DEFVAL { shutdown }
|
|
::= { sensorTemp 8 }
|
|
|
|
------ End group -----------------------------------------------------------------
|
|
|
|
END
|
|
|