diff --git a/MIBS/POWER-ETHERNET-MIB b/MIBS/POWER-ETHERNET-MIB
new file mode 100644
index 0000000..dfb0673
--- /dev/null
+++ b/MIBS/POWER-ETHERNET-MIB
@@ -0,0 +1,629 @@
+-- *****************************************************************
+-- POWER-ETHERNET-MIB
+--
+-- This mib was extracted from RFC 3621
+--
+-- Copyright (c) 2006, 2009 by Cisco Systems, Inc.
+-- All rights reserved.
+-- *****************************************************************
+POWER-ETHERNET-MIB DEFINITIONS ::= BEGIN
+
+IMPORTS
+ MODULE-IDENTITY, mib-2, OBJECT-TYPE, Integer32,
+ Gauge32, Counter32, NOTIFICATION-TYPE
+ FROM SNMPv2-SMI
+ TruthValue
+ FROM SNMPv2-TC
+ MODULE-COMPLIANCE, OBJECT-GROUP, NOTIFICATION-GROUP
+ FROM SNMPv2-CONF
+
+ SnmpAdminString
+ FROM SNMP-FRAMEWORK-MIB;
+
+ powerEthernetMIB MODULE-IDENTITY
+
+ LAST-UPDATED "200311240000Z" -- November 24, 2003
+ ORGANIZATION "IETF Ethernet Interfaces and Hub MIB
+ Working Group"
+
+ CONTACT-INFO
+ "
+ WG Charter:
+ http://www.ietf.org/html.charters/hubmib-charter.html
+
+ Mailing lists:
+ General Discussion: hubmib@ietf.org
+ To Subscribe: hubmib-requests@ietf.org
+ In Body: subscribe your_email_address
+
+ Chair: Dan Romascanu
+ Avaya
+ Tel: +972-3-645-8414
+ Email: dromasca@avaya.com
+
+ Editor: Avi Berger
+ PowerDsine Inc.
+ Tel: 972-9-7755100 Ext 307
+ Fax: 972-9-7755120
+ E-mail: avib@PowerDsine.com
+ "
+
+ DESCRIPTION
+ "The MIB module for managing Power Source Equipment
+ (PSE) working according to the IEEE 802.af Powered
+ Ethernet (DTE Power via MDI) standard.
+
+ The following terms are used throughout this
+ MIB module. For complete formal definitions,
+ the IEEE 802.3 standards should be consulted
+ wherever possible:
+
+ Group - A recommended, but optional, entity
+ defined by the IEEE 802.3 management standard,
+ in order to support a modular numbering scheme.
+ The classical example allows an implementor to
+ represent field-replaceable units as groups of
+ ports, with the port numbering matching the
+ modular hardware implementation.
+
+ Port - This entity identifies the port within the group
+ for which this entry contains information. The numbering
+ scheme for ports is implementation specific.
+
+ Copyright (c) The Internet Society (2003). This version
+ of this MIB module is part of RFC 3621; See the RFC
+ itself for full legal notices."
+
+ REVISION "200311240000Z" -- November 24, 2003
+ DESCRIPTION "Initial version, published as RFC 3621."
+ ::= { mib-2 105 }
+
+pethNotifications OBJECT IDENTIFIER ::= { powerEthernetMIB 0 }
+pethObjects OBJECT IDENTIFIER ::= { powerEthernetMIB 1 }
+pethConformance OBJECT IDENTIFIER ::= { powerEthernetMIB 2 }
+
+-- PSE Objects
+
+ pethPsePortTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF PethPsePortEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A table of objects that display and control the power
+ characteristics of power Ethernet ports on a Power Source
+ Entity (PSE) device. This group will be implemented in
+ managed power Ethernet switches and mid-span devices.
+ Values of all read-write objects in this table are
+ persistent at restart/reboot."
+ ::= { pethObjects 1 }
+
+ pethPsePortEntry OBJECT-TYPE
+ SYNTAX PethPsePortEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A set of objects that display and control the power
+ characteristics of a power Ethernet PSE port."
+ INDEX { pethPsePortGroupIndex , pethPsePortIndex }
+ ::= { pethPsePortTable 1 }
+
+ PethPsePortEntry ::= SEQUENCE {
+ pethPsePortGroupIndex
+ Integer32,
+ pethPsePortIndex
+ Integer32,
+ pethPsePortAdminEnable
+ TruthValue,
+ pethPsePortPowerPairsControlAbility
+ TruthValue,
+ pethPsePortPowerPairs
+ INTEGER,
+ pethPsePortDetectionStatus
+ INTEGER,
+ pethPsePortPowerPriority
+ INTEGER,
+ pethPsePortMPSAbsentCounter
+ Counter32,
+ pethPsePortType
+ SnmpAdminString,
+ pethPsePortPowerClassifications
+ INTEGER,
+ pethPsePortInvalidSignatureCounter
+ Counter32,
+ pethPsePortPowerDeniedCounter
+ Counter32,
+ pethPsePortOverLoadCounter
+ Counter32,
+ pethPsePortShortCounter
+ Counter32
+ }
+
+ pethPsePortGroupIndex OBJECT-TYPE
+ SYNTAX Integer32 (1..2147483647)
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "This variable uniquely identifies the group
+ containing the port to which a power Ethernet PSE is
+ connected. Group means box in the stack, module in a
+ rack and the value 1 MUST be used for non-modular devices.
+ Furthermore, the same value MUST be used in this variable,
+ pethMainPseGroupIndex, and pethNotificationControlGroupIndex
+ to refer to a given box in a stack or module in the rack."
+ ::= { pethPsePortEntry 1 }
+
+ pethPsePortIndex OBJECT-TYPE
+ SYNTAX Integer32 (1..2147483647)
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "This variable uniquely identifies the power Ethernet PSE
+ port within group pethPsePortGroupIndex to which the
+ power Ethernet PSE entry is connected."
+ ::= { pethPsePortEntry 2 }
+
+ pethPsePortAdminEnable OBJECT-TYPE
+ SYNTAX TruthValue
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "true (1) An interface which can provide the PSE functions.
+ false(2) The interface will act as it would if it had no PSE
+ function."
+ REFERENCE
+ "IEEE Std 802.3af Section 30.9.1.1.2 aPSEAdminState"
+ ::= { pethPsePortEntry 3 }
+
+ pethPsePortPowerPairsControlAbility OBJECT-TYPE
+ SYNTAX TruthValue
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Describes the capability of controlling the power pairs
+ functionality to switch pins for sourcing power.
+ The value true indicate that the device has the capability
+ to control the power pairs. When false the PSE Pinout
+ Alternative used cannot be controlled through the
+ PethPsePortAdminEnable attribute."
+ REFERENCE
+ "IEEE Std 802.3af Section 30.9.1.1.3
+ aPSEPowerPairsControlAbility"
+ ::= { pethPsePortEntry 4 }
+
+ pethPsePortPowerPairs OBJECT-TYPE
+ SYNTAX INTEGER {
+ signal(1),
+ spare(2)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Describes or controls the pairs in use. If the value of
+ pethPsePortPowerPairsControl is true, this object is
+ writable.
+ A value of signal(1) means that the signal pairs
+ only are in use.
+ A value of spare(2) means that the spare pairs
+ only are in use."
+ REFERENCE
+ "IEEE Std 802.3af Section 30.9.1.1.4 aPSEPowerPairs"
+ ::= { pethPsePortEntry 5 }
+
+ pethPsePortDetectionStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(1),
+ searching(2),
+ deliveringPower(3),
+ fault(4),
+ test(5),
+ otherFault(6)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Describes the operational status of the port PD detection.
+ A value of disabled(1)- indicates that the PSE State diagram
+ is in the state DISABLED.
+ A value of deliveringPower(3) - indicates that the PSE State
+ diagram is in the state POWER_ON for a duration greater than
+ tlim max (see IEEE Std 802.3af Table 33-5 tlim).
+ A value of fault(4) - indicates that the PSE State diagram is
+ in the state TEST_ERROR.
+ A value of test(5) - indicates that the PSE State diagram is
+ in the state TEST_MODE.
+ A value of otherFault(6) - indicates that the PSE State
+ diagram is in the state IDLE due to the variable
+ error_conditions.
+ A value of searching(2)- indicates the PSE State diagram is
+ in a state other than those listed above."
+ REFERENCE
+ "IEEE Std 802.3af Section 30.9.1.1.5
+ aPSEPowerDetectionStatus"
+ ::= { pethPsePortEntry 6 }
+
+ pethPsePortPowerPriority OBJECT-TYPE
+ SYNTAX INTEGER {
+ critical(1),
+ high(2),
+ low(3)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "This object controls the priority of the port from the point
+ of view of a power management algorithm. The priority that
+ is set by this variable could be used by a control mechanism
+ that prevents over current situations by disconnecting first
+ ports with lower power priority. Ports that connect devices
+ critical to the operation of the network - like the E911
+ telephones ports - should be set to higher priority."
+ ::= { pethPsePortEntry 7 }
+
+ pethPsePortMPSAbsentCounter OBJECT-TYPE
+ SYNTAX Counter32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "This counter is incremented when the PSE state diagram
+ transitions directly from the state POWER_ON to the
+ state IDLE due to tmpdo_timer_done being asserted."
+ REFERENCE
+ "IEEE Std 802.3af Section 30.9.1.1.11
+ aPSEMPSAbsentCounter"
+ ::= { pethPsePortEntry 8 }
+
+ pethPsePortType OBJECT-TYPE
+ SYNTAX SnmpAdminString
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "A manager will set the value of this variable to indicate
+ the type of powered device that is connected to the port.
+ The default value supplied by the agent if no value has
+ ever been set should be a zero-length octet string."
+ ::= { pethPsePortEntry 9 }
+
+ pethPsePortPowerClassifications OBJECT-TYPE
+ SYNTAX INTEGER {
+ class0(1),
+ class1(2),
+ class2(3),
+ class3(4),
+ class4(5)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Classification is a way to tag different terminals on the
+ Power over LAN network according to their power consumption.
+ Devices such as IP telephones, WLAN access points and others,
+ will be classified according to their power requirements.
+
+ The meaning of the classification labels is defined in the
+ IEEE specification.
+
+ This variable is valid only while a PD is being powered,
+ that is, while the attribute pethPsePortDetectionStatus
+ is reporting the enumeration deliveringPower."
+ REFERENCE
+ "IEEE Std 802.3af Section 30.9.1.1.6
+ aPSEPowerClassification"
+ ::= { pethPsePortEntry 10 }
+
+ pethPsePortInvalidSignatureCounter OBJECT-TYPE
+ SYNTAX Counter32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "This counter is incremented when the PSE state diagram
+ enters the state SIGNATURE_INVALID."
+ REFERENCE
+ "IEEE Std 802.3af Section 30.9.1.1.7
+ aPSEInvalidSignatureCounter"
+ ::= { pethPsePortEntry 11 }
+
+ pethPsePortPowerDeniedCounter OBJECT-TYPE
+ SYNTAX Counter32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "This counter is incremented when the PSE state diagram
+ enters the state POWER_DENIED."
+ REFERENCE
+ "IEEE Std 802.3af Section 30.9.1.1.8
+ aPSEPowerDeniedCounter"
+ ::= { pethPsePortEntry 12 }
+
+ pethPsePortOverLoadCounter OBJECT-TYPE
+ SYNTAX Counter32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "This counter is incremented when the PSE state diagram
+ enters the state ERROR_DELAY_OVER."
+ REFERENCE
+ "IEEE Std 802.3af Section 30.9.1.1.9
+ aPSEOverLoadCounter"
+ ::= { pethPsePortEntry 13 }
+
+ pethPsePortShortCounter OBJECT-TYPE
+ SYNTAX Counter32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "This counter is incremented when the PSE state diagram
+ enters the state ERROR_DELAY_SHORT."
+ REFERENCE
+ "IEEE Std 802.3af Section 30.9.1.1.10
+ aPSEShortCounter"
+ ::= { pethPsePortEntry 14 }
+
+-- Main PSE Objects
+
+pethMainPseObjects OBJECT IDENTIFIER ::= { pethObjects 3 }
+
+pethMainPseTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF PethMainPseEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A table of objects that display and control attributes
+ of the main power source in a PSE device. Ethernet
+ switches are one example of boxes that would support
+ these objects.
+ Values of all read-write objects in this table are
+ persistent at restart/reboot."
+ ::= { pethMainPseObjects 1 }
+
+ pethMainPseEntry OBJECT-TYPE
+ SYNTAX PethMainPseEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A set of objects that display and control the Main
+ power of a PSE. "
+ INDEX { pethMainPseGroupIndex }
+ ::= { pethMainPseTable 1 }
+
+ PethMainPseEntry ::= SEQUENCE {
+ pethMainPseGroupIndex
+ Integer32,
+ pethMainPsePower
+ Gauge32 ,
+ pethMainPseOperStatus
+ INTEGER,
+ pethMainPseConsumptionPower
+ Gauge32,
+ pethMainPseUsageThreshold
+ Integer32
+ }
+ pethMainPseGroupIndex OBJECT-TYPE
+ SYNTAX Integer32 (1..2147483647)
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "This variable uniquely identifies the group to which
+ power Ethernet PSE is connected. Group means (box in
+ the stack, module in a rack) and the value 1 MUST be
+ used for non-modular devices. Furthermore, the same
+ value MUST be used in this variable, pethPsePortGroupIndex,
+ and pethNotificationControlGroupIndex to refer to a
+ given box in a stack or module in a rack."
+ ::= { pethMainPseEntry 1 }
+
+ pethMainPsePower OBJECT-TYPE
+ SYNTAX Gauge32 (1..65535)
+ UNITS "Watts"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The nominal power of the PSE expressed in Watts."
+ ::= { pethMainPseEntry 2 }
+
+ pethMainPseOperStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ on(1),
+ off(2),
+ faulty(3)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The operational status of the main PSE."
+ ::= { pethMainPseEntry 3 }
+
+ pethMainPseConsumptionPower OBJECT-TYPE
+ SYNTAX Gauge32
+ UNITS "Watts"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Measured usage power expressed in Watts."
+ ::= { pethMainPseEntry 4 }
+
+ pethMainPseUsageThreshold OBJECT-TYPE
+ SYNTAX Integer32 (1..99)
+ UNITS "%"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The usage threshold expressed in percents for
+ comparing the measured power and initiating
+ an alarm if the threshold is exceeded."
+ ::= { pethMainPseEntry 5 }
+
+-- Notification Control Objects
+
+pethNotificationControl OBJECT IDENTIFIER ::= { pethObjects 4 }
+
+pethNotificationControlTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF PethNotificationControlEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A table of objects that display and control the
+ Notification on a PSE device.
+ Values of all read-write objects in this table are
+ persistent at restart/reboot."
+ ::= { pethNotificationControl 1 }
+
+ pethNotificationControlEntry OBJECT-TYPE
+ SYNTAX PethNotificationControlEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A set of objects that control the Notification events."
+ INDEX { pethNotificationControlGroupIndex }
+ ::= { pethNotificationControlTable 1 }
+
+ PethNotificationControlEntry ::= SEQUENCE {
+ pethNotificationControlGroupIndex
+ Integer32,
+ pethNotificationControlEnable
+ TruthValue
+ }
+ pethNotificationControlGroupIndex OBJECT-TYPE
+ SYNTAX Integer32 (1..2147483647)
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "This variable uniquely identifies the group. Group
+ means box in the stack, module in a rack and the value
+ 1 MUST be used for non-modular devices. Furthermore,
+ the same value MUST be used in this variable,
+ pethPsePortGroupIndex, and
+ pethMainPseGroupIndex to refer to a given box in a
+ stack or module in a rack. "
+ ::= { pethNotificationControlEntry 1 }
+
+ pethNotificationControlEnable OBJECT-TYPE
+ SYNTAX TruthValue
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "This object controls, on a per-group basis, whether
+ or not notifications from the agent are enabled. The
+ value true(1) means that notifications are enabled; the
+ value false(2) means that they are not."
+ ::= { pethNotificationControlEntry 2 }
+
+--
+-- Notifications Section
+--
+--
+
+ pethPsePortOnOffNotification NOTIFICATION-TYPE
+ OBJECTS { pethPsePortDetectionStatus }
+ STATUS current
+ DESCRIPTION
+ " This Notification indicates if Pse Port is delivering or
+ not power to the PD. This Notification SHOULD be sent on
+ every status change except in the searching mode.
+ At least 500 msec must elapse between notifications
+ being emitted by the same object instance."
+ ::= { pethNotifications 1 }
+
+ pethMainPowerUsageOnNotification NOTIFICATION-TYPE
+ OBJECTS { pethMainPseConsumptionPower }
+ STATUS current
+ DESCRIPTION
+ " This Notification indicate PSE Threshold usage
+ indication is on, the usage power is above the
+ threshold. At least 500 msec must elapse between
+ notifications being emitted by the same object
+ instance."
+ ::= { pethNotifications 2 }
+
+ pethMainPowerUsageOffNotification NOTIFICATION-TYPE
+ OBJECTS { pethMainPseConsumptionPower }
+ STATUS current
+ DESCRIPTION
+ " This Notification indicates PSE Threshold usage indication
+ off, the usage power is below the threshold.
+ At least 500 msec must elapse between notifications being
+ emitted by the same object instance."
+ ::= { pethNotifications 3 }
+
+--
+-- Conformance Section
+--
+pethCompliances OBJECT IDENTIFIER ::= { pethConformance 1 }
+pethGroups OBJECT IDENTIFIER ::= { pethConformance 2 }
+
+pethCompliance MODULE-COMPLIANCE
+ STATUS current
+ DESCRIPTION
+ "Describes the requirements for conformance to the
+ Power Ethernet MIB."
+
+ MODULE -- this module
+ MANDATORY-GROUPS { pethPsePortGroup,
+ pethPsePortNotificationGroup,
+ pethNotificationControlGroup
+ }
+ GROUP pethMainPseGroup
+ DESCRIPTION
+ "The pethMainPseGroup is mandatory for PSE systems
+ that implement a main power supply."
+ GROUP pethMainPowerNotificationGroup
+ DESCRIPTION
+ "The pethMainPowerNotificationGroup is mandatory for
+ PSE systems that implement a main power supply."
+ ::= { pethCompliances 1 }
+
+pethPsePortGroup OBJECT-GROUP
+ OBJECTS {
+ pethPsePortAdminEnable,
+ pethPsePortPowerPairsControlAbility,
+ pethPsePortPowerPairs,
+ pethPsePortDetectionStatus,
+ pethPsePortPowerPriority,
+ pethPsePortMPSAbsentCounter,
+ pethPsePortInvalidSignatureCounter,
+ pethPsePortPowerDeniedCounter,
+ pethPsePortOverLoadCounter,
+ pethPsePortShortCounter,
+ pethPsePortType,
+ pethPsePortPowerClassifications
+ }
+ STATUS current
+ DESCRIPTION
+ "PSE Port objects."
+ ::= { pethGroups 1 }
+
+pethMainPseGroup OBJECT-GROUP
+ OBJECTS {
+ pethMainPsePower,
+ pethMainPseOperStatus,
+ pethMainPseConsumptionPower,
+ pethMainPseUsageThreshold
+ }
+ STATUS current
+ DESCRIPTION
+ "Main PSE Objects. "
+ ::= { pethGroups 2 }
+
+pethNotificationControlGroup OBJECT-GROUP
+ OBJECTS {
+ pethNotificationControlEnable
+ }
+ STATUS current
+ DESCRIPTION
+ "Notification Control Objects. "
+ ::= { pethGroups 3 }
+
+pethPsePortNotificationGroup NOTIFICATION-GROUP
+ NOTIFICATIONS { pethPsePortOnOffNotification}
+ STATUS current
+ DESCRIPTION "Pse Port Notifications."
+ ::= { pethGroups 4 }
+
+ pethMainPowerNotificationGroup NOTIFICATION-GROUP
+ NOTIFICATIONS { pethMainPowerUsageOnNotification,
+ pethMainPowerUsageOffNotification}
+ STATUS current
+ DESCRIPTION "Main PSE Notifications."
+ ::= { pethGroups 5 }
+
+END
+