commit98a672123c7872f6b9b75a9a2b6bb3aea504de6a (patch)
tree9b13bd7f563c3198047bd359195327cf28b3caf0 /MIBS/alpha/Argus-Power-System-MIB
downloadmibs-main.tar.gz
mibs-main.zip
Initial commitHEADmain
Diffstat (limited to 'MIBS/alpha/Argus-Power-System-MIB')
-rw-r--r--MIBS/alpha/Argus-Power-System-MIB799
1 files changed, 799 insertions, 0 deletions
diff --git a/MIBS/alpha/Argus-Power-System-MIB b/MIBS/alpha/Argus-Power-System-MIB
new file mode 100644
index 0000000..b3776cd
--- /dev/null
+++ b/MIBS/alpha/Argus-Power-System-MIB
@@ -0,0 +1,799 @@
+ Argus-Power-System-MIB DEFINITIONS ::= BEGIN
+
+ --==========================================================================
+ -- NOTE: Refer to RFC1628 for the formal definition of the SNMPv2-SMI MIB.
+ --==========================================================================
+
+ IMPORTS
+ MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE, enterprises
+ FROM SNMPv2-SMI;
+
+ argus MODULE-IDENTITY
+ LAST-UPDATED "201612090000Z"
+ ORGANIZATION "Alpha Technologies Ltd."
+ CONTACT-INFO
+ "Alpha Technologies Ltd.
+ 7700 Riverfront Gate
+ Burnaby, BC V5J 5M4
+ Canada
+
+ Tel: 1-604-436-5900
+ Fax: 1-604-436-1233"
+ DESCRIPTION
+ "This MIB defines the information block(s) available in CXC RMU
+ as defined by the following list:
+ - upsDevice: the CXC-series of controllers"
+
+ REVISION "201612090000Z" -- December 9, 2016
+ DESCRIPTION
+ "
+ Updated upsSecondsOnBattery to upsMinutesOnBattery to match unit value of the data.
+ "
+
+
+ ::= { enterprises 7309 }
+
+ PositiveInteger ::= TEXTUAL-CONVENTION
+ DISPLAY-HINT "d"
+ STATUS current
+ DESCRIPTION
+ "This data type is a non-zero and non-negative value."
+ SYNTAX INTEGER (1..2147483647)
+
+ NonNegativeInteger ::= TEXTUAL-CONVENTION
+ DISPLAY-HINT "d"
+ STATUS current
+ DESCRIPTION
+ "This data type is a non-negative value."
+ SYNTAX INTEGER (0..2147483647)
+
+ DisplayString ::=
+ OCTET STRING
+ -- This data type is used to model textual information taken
+ -- from the NVT ASCII character set. By convention, objects
+ -- with this syntax are declared as having
+ --
+ -- SIZE (0..255)
+
+ PhysAddress ::=
+ OCTET STRING
+ -- This data type is used to model media addresses. For many
+ -- types of media, this will be in a binary representation.
+ -- For example, an ethernet address would be represented as
+ -- a string of 6 octets.
+
+
+
+
+
+ upsPower OBJECT IDENTIFIER ::= { argus 6}
+ upsDevice OBJECT IDENTIFIER ::= { upsPower 1}
+ upsIdent OBJECT IDENTIFIER ::= { upsDevice 1}
+ upsBattery OBJECT IDENTIFIER ::= { upsDevice 2}
+ upsInput OBJECT IDENTIFIER ::= { upsDevice 3}
+ upsOutput OBJECT IDENTIFIER ::= { upsDevice 4}
+ upsAlarm OBJECT IDENTIFIER ::= { upsDevice 5}
+ upsConfig OBJECT IDENTIFIER ::= { upsDevice 6}
+ upsTraps OBJECT IDENTIFIER ::= { upsDevice 7}
+ upsExtra OBJECT IDENTIFIER ::= { upsDevice 8}
+
+
+ --==========================================================================
+ -- Start of Extra Information
+ -- Power upstem specified variables and alarm status are maintained in the extra
+ -- table. CXC RMU will populate realtime live data to these variables and
+ -- status entries in the table. Table entries' string value are configured by
+ -- CXC RMU web interface and support unicode string
+ --==========================================================================
+
+ upsExtraCount OBJECT-TYPE
+ SYNTAX INTEGER (0..65535)
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION "Number of extra variables"
+ ::= { upsExtra 1 }
+
+ upsExtraTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsExtraEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION "A table of CXC upstem controller extra variables"
+ ::= { upsExtra 2 }
+
+ upsExtraEntry OBJECT-TYPE
+ SYNTAX UpsExtraEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION "An entry into the CXC upstem controller extra variable table"
+ INDEX { upsExtraIndex }
+ ::= { upsExtraTable 1 }
+
+ UpsExtraEntry
+ ::= SEQUENCE {
+ upsExtraIndex INTEGER,
+ upsExtraName DisplayString ,
+ upsExtraIntegerValue INTEGER,
+ upsExtraStringValue DisplayString
+ }
+
+ upsExtraIndex OBJECT-TYPE
+ SYNTAX INTEGER (0..65535)
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION "The index of the extra variable in the CXC upstem controller table"
+ ::= { upsExtraEntry 1 }
+
+ upsExtraName OBJECT-TYPE
+ SYNTAX DisplayString (SIZE(0..30))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION "The description of the extra variable as reported by the CXC upstem controller"
+ ::= { upsExtraEntry 2 }
+
+ upsExtraIntegerValue OBJECT-TYPE
+ SYNTAX INTEGER (-1000000000..1000000000)
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION "The integer value of the extra variable as reported by the CXC upstem controller"
+ ::= { upsExtraEntry 3 }
+
+ upsExtraStringValue OBJECT-TYPE
+ SYNTAX DisplayString (SIZE(0..255))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION "The string value of the extra variable as reported by the CXC upstem controller"
+ ::= { upsExtraEntry 4 }
+
+ --==========================================================================
+ -- The OBJECT IDENTIFIERs for the traps must be defined in this manner to
+ -- satisfy the NetSight MIB compiler; in particular, nodes cannot be defined
+ -- concatenated in a single line, but must be defined explicitly node by node
+ -- (hence, the upsDevice.upsTraps.upsTrap definition)
+ -- In addition, forward references to extra upstem variables are needed for
+ -- upsTrap by CastleRock SNMPc for event filter and match features.
+ --==========================================================================
+ upsTrap OBJECT IDENTIFIER ::= { upsTraps 0 }
+
+ --==========================================================================
+ -- Start of Traps
+ --==========================================================================
+
+ upsAlarmTrap NOTIFICATION-TYPE
+ OBJECTS {
+ upsExtraIntegerValue,
+ upsExtraStringValue,
+ upsExtraIndex,
+ upsExtraName
+ }
+ STATUS current
+ DESCRIPTION "A trap issued from a change in state in one of the Alarms on the Novus controller"
+ ::= { upsTrap 1 }
+
+ upsAgentStartupTrap NOTIFICATION-TYPE
+ OBJECTS {
+ upsIdentSiteName
+ }
+ STATUS current
+ DESCRIPTION "A trap to indicate that the agent software has started up."
+ ::= { upsTrap 2 }
+
+ upsAgentShutdownTrap NOTIFICATION-TYPE
+ OBJECTS {
+ upsIdentSiteName
+ }
+ STATUS current
+ DESCRIPTION "A trap to indicate that the agent software has shutdown."
+ ::= { upsTrap 3 }
+
+ upsAgentFaultTrap NOTIFICATION-TYPE
+ OBJECTS {
+ upsExtraIntegerValue,
+ upsExtraStringValue,
+ upsExtraIndex,
+ upsExtraName
+ }
+ STATUS current
+ DESCRIPTION "A trap issued from a change in state in one of the Faults on the Novus controller"
+ ::= { upsTrap 4 }
+
+ upsAgentEventTrap NOTIFICATION-TYPE
+ OBJECTS {
+ upsExtraIntegerValue,
+ upsExtraStringValue,
+ upsExtraIndex,
+ upsExtraName
+ }
+ STATUS current
+ DESCRIPTION "A trap issued from a change in state in one of the Events on the Novus controller"
+ ::= { upsTrap 5 }
+
+
+
+
+ --
+ -- The Device Identification group.
+ -- All objects in this group are set at device initialization
+ -- and remain static.
+ --
+
+
+
+ upsIdentManufacturer OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..255))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The name of the UPS manufacturer."
+ ::= { upsIdent 1 }
+
+ upsIdentProductCode OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..255))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The UPS Model designation."
+ ::= { upsIdent 2 }
+
+ upsIdentModel OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..255))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The UPS Product code designation."
+ ::= { upsIdent 3 }
+
+ upsIdentUPSSoftwareVersion OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..255))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The UPS firmware/software version(s). This variable
+ may or may not have the same value as
+ upsIdentAgentSoftwareVersion in some implementations."
+ ::= { upsIdent 4 }
+
+ upsIdentAgentSoftwareVersion OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..255))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The UPS agent software version. This variable may or
+ may not have the same value as
+ upsIdentUPSSoftwareVersion in some implementations."
+ ::= { upsIdent 5 }
+
+ upsIdentName OBJECT-TYPE
+ SYNTAX DisplayString (SIZE(0..255))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "A string identifying the UPS. This object should be
+ set by the administrator."
+ ::= { upsIdent 6 }
+
+ upsIdentAttachedDevices OBJECT-TYPE
+ SYNTAX DisplayString (SIZE(0..255))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "A string identifying the devices attached to the
+ output(s) of the UPS. This object should be set by
+ the administrator."
+ ::= { upsIdent 7 }
+
+ upsIdentSiteName OBJECT-TYPE
+ SYNTAX DisplayString (SIZE(0..255))
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION "Site Name"
+ ::= { upsIdent 8 }
+
+ upsIdentSiteCity OBJECT-TYPE
+ SYNTAX DisplayString (SIZE(0..255))
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION "Site City"
+ ::= { upsIdent 9 }
+
+ upsIdentSiteRegion OBJECT-TYPE
+ SYNTAX DisplayString (SIZE(0..255))
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION "Site Region"
+ ::= { upsIdent 10 }
+
+ upsIdentSiteCountry OBJECT-TYPE
+ SYNTAX DisplayString (SIZE(0..255))
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION "Site Country"
+ ::= { upsIdent 11 }
+
+ upsIdentContactName OBJECT-TYPE
+ SYNTAX DisplayString (SIZE(0..255))
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION "Contact Name"
+ ::= { upsIdent 12 }
+
+ upsIdentPhoneNumber OBJECT-TYPE
+ SYNTAX DisplayString (SIZE(0..255))
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION "Phone Number"
+ ::= { upsIdent 13 }
+
+ upsIdentDate OBJECT-TYPE
+ SYNTAX DisplayString (SIZE(0..255))
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION "Date of the RMU-Novus"
+ ::= { upsIdent 14 }
+
+ upsIdentTime OBJECT-TYPE
+ SYNTAX DisplayString (SIZE(0..255))
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION "Time of the RMU-Novus"
+ ::= { upsIdent 15 }
+
+
+
+ --
+ -- Battery Group
+ --
+
+
+
+ upsBatteryStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(1),
+ batteryNormal(2),
+ batteryLow(3),
+ batteryDepleted(4)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The indication of the capacity remaining in the UPS
+ system's batteries. A value of batteryNormal
+ indicates that the remaining run-time is greater than
+ upsConfigLowBattTime. A value of batteryLow indicates
+ that the remaining battery run-time is less than or
+ equal to upsConfigLowBattTime. A value of
+ batteryDepleted indicates that the UPS will be unable
+ to sustain the present load when and if the utility
+ power is lost (including the possibility that the
+ utility power is currently absent and the UPS is
+ unable to sustain the output)."
+ ::= { upsBattery 1 }
+
+ upsMinutesOnBattery OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "minutes"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "
+ The accumulated elapsed time that the UPS system have been on battery.
+ "
+ ::= { upsBattery 2 }
+
+ upsBatteryVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "0.1 Volt DC"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The magnitude of the present battery voltage."
+ ::= { upsBattery 3 }
+
+ upsBatteryChargingCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "0.1 Amp DC"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present battery charging current."
+ ::= { upsBattery 4 }
+
+ upsBatteryCapacity OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "0.1 Amp DC"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present battery capacity."
+ ::= { upsBattery 5 }
+
+
+ upsBatteryTemperature OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "degrees Centigrade"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The ambient temperature at or near the UPS Battery
+ casing."
+ ::= { upsBattery 6 }
+ upsBatteryLowWarning OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "percentage"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The set battery capacity percentage at which the unit will raise an alarm."
+ ::= { upsBattery 7 }
+
+
+ --
+ -- Input Group
+ --
+
+
+
+ upsInputNumLines OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of input lines utilized in this device.
+ This variable indicates the number of rows in the
+ input table."
+ ::= { upsInput 1 }
+
+ upsInputTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsInputEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A list of input table entries. The number of entries
+ is given by the value of upsInputNumLines."
+ ::= { upsInput 2 }
+
+ upsInputEntry OBJECT-TYPE
+ SYNTAX UpsInputEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular input line."
+ INDEX { upsInputLineIndex }
+ ::= { upsInputTable 1 }
+
+ UpsInputEntry ::= SEQUENCE {
+ upsInputLineIndex INTEGER ,
+ upsInputFrequency INTEGER ,
+ upsInputVoltage INTEGER
+ }
+
+ upsInputLineIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "The input line identifier."
+ ::= { upsInputEntry 1 }
+
+ upsInputFrequency OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "Hertz"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present input frequency."
+ ::= { upsInputEntry 2 }
+
+ upsInputVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "0.1 RMS Volts"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The magnitude of the present input voltage."
+ ::= { upsInputEntry 3 }
+
+ --
+ -- The Output group.
+ --
+
+
+
+ upsOutputSource OBJECT-TYPE
+ SYNTAX INTEGER {
+ standby(1),
+ line(2),
+ boost2(3),
+ boost1(4),
+ buck1(5),
+ buck2(6),
+ inverter(7),
+ retransfer(8),
+ transfer(9),
+ shutdown(10),
+ bypass(11)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present source of output power. The enumeration
+ line(2) indicates that the Novus is in line mode."
+ ::= { upsOutput 1 }
+
+ upsOutputFrequency OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "0.1 Hertz"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present output frequency."
+ ::= { upsOutput 2 }
+
+ upsOutputNumLines OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of output lines utilized in this device.
+ This variable indicates the number of rows in the
+ output table."
+ ::= { upsOutput 3 }
+
+ upsOutputTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsOutputEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A list of output table entries. The number of
+ entries is given by the value of upsOutputNumLines."
+ ::= { upsOutput 4 }
+
+ upsOutputEntry OBJECT-TYPE
+ SYNTAX UpsOutputEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular output line."
+ INDEX { upsOutputLineIndex }
+ ::= { upsOutputTable 1 }
+
+ UpsOutputEntry ::= SEQUENCE {
+ upsOutputLineIndex INTEGER ,
+ upsOutputVoltage INTEGER ,
+ upsOutputCurrent INTEGER ,
+ upsOutputPowerVA INTEGER ,
+ upsOutputPowerWatt INTEGER ,
+ upsPowerFactor INTEGER ,
+ upsOutputPercentLoad INTEGER
+ }
+
+ upsOutputLineIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "The output line identifier."
+ ::= { upsOutputEntry 1 }
+
+ upsOutputVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "0.1 RMS Volts"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present output voltage."
+ ::= { upsOutputEntry 2 }
+
+ upsOutputCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "0.1 RMS Amp"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present output current."
+ ::= { upsOutputEntry 3 }
+
+ upsOutputPowerVA OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "VA"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present output VA."
+ ::= { upsOutputEntry 4 }
+
+ upsOutputPowerWatt OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "Watts"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present output true power."
+ ::= { upsOutputEntry 5 }
+
+ upsPowerFactor OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "percent"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present power factor."
+ ::= { upsOutputEntry 6 }
+
+ upsOutputPercentLoad OBJECT-TYPE
+ SYNTAX INTEGER (0..200)
+ UNITS "percent"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The percentage of the UPS power capacity presently
+ being used on this output line, i.e., the greater of
+ the percent load of true power capacity and the
+ percent load of VA."
+ ::= { upsOutputEntry 7 }
+
+ --
+ -- The Alarms group.
+ --
+
+
+
+ upsAlarmsPresent OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present number of active alarm conditions."
+ ::= { upsAlarm 1 }
+
+ upsAlarmTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsAlarmEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A list of alarm table entries. "
+ ::= { upsAlarm 2 }
+
+ upsAlarmEntry OBJECT-TYPE
+ SYNTAX UpsAlarmEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular alarm."
+ INDEX { upsAlarmId }
+ ::= { upsAlarmTable 1 }
+
+ UpsAlarmEntry ::= SEQUENCE {
+ upsAlarmId INTEGER ,
+ upsAlarmDescr DisplayString,
+ upsAlarmStatus INTEGER
+ }
+
+ upsAlarmId OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A unique identifier for an alarm condition. This
+ value must remain constant."
+ ::= { upsAlarmEntry 1 }
+
+ upsAlarmDescr OBJECT-TYPE
+ SYNTAX DisplayString (SIZE(0..255))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "A unique description of the alarm. "
+ ::= { upsAlarmEntry 2 }
+
+ upsAlarmStatus OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "1 - ON or 0 - OFF. "
+ ::= { upsAlarmEntry 3 }
+
+ --
+ -- The Config group.
+ --
+
+
+
+ upsConfigLineQualifyTime OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "seconds"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "This objects displays the line qualify time."
+ ::= { upsConfig 1 }
+
+ upsConfigLineOutputVoltageHighLimit OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "volttenth"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "This object represents the Line output High Voltage Limit."
+ ::= { upsConfig 2 }
+
+ upsConfigLineOutputVoltageLowLimit OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "volttenth"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "This object represents the Line output Low Voltage Limit."
+ ::= { upsConfig 3 }
+
+ upsConfigFanOnTemperature OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "degreeC"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "This object represents the Fan on temperature."
+ ::= { upsConfig 4 }
+
+
+ upsShutdownStatus OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS ""
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "This object tells us if output is disabled or enabled."
+ ::= { upsConfig 5 }
+ upsInverterOffDelayTime OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "seconds"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "This object represents the inverter off delay time."
+ ::= { upsConfig 6 }
+
+ upsConfigIPAddress OBJECT-TYPE
+ SYNTAX DisplayString (SIZE(0..255))
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "This objects displays the IP address of the RMU."
+ ::= { upsConfig 7 }
+
+ upsConfigNetMask OBJECT-TYPE
+ SYNTAX DisplayString (SIZE(0..255))
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "This object displays the Net Mask of the RMU."
+ ::= { upsConfig 8 }
+
+ upsConfigGateway OBJECT-TYPE
+ SYNTAX DisplayString (SIZE(0..255))
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "This object displays the Gateway of the RMU."
+ ::= { upsConfig 9 }
+
+ upsConfigSnmpCommunity OBJECT-TYPE
+ SYNTAX DisplayString (SIZE(0..255))
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "This object displays the SNMP community"
+ ::= { upsConfig 10 }
+
+ upsConfigSnmpTrapIPDestination OBJECT-TYPE
+ SYNTAX DisplayString (SIZE(0..255))
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "This object displays the SNMP Trap IP destination."
+ ::= { upsConfig 11 }
+
+END