summaryrefslogtreecommitdiff
path: root/MIBS/avocent/ACS-MIB
diff options
context:
space:
mode:
authorDavid Leutgeb <david.leutgeb@mannundmouse.com>2023-12-05 12:25:34 +0100
committerDavid Leutgeb <david.leutgeb@mannundmouse.com>2023-12-05 12:25:34 +0100
commit98a672123c7872f6b9b75a9a2b6bb3aea504de6a (patch)
tree9b13bd7f563c3198047bd359195327cf28b3caf0 /MIBS/avocent/ACS-MIB
downloadmibs-98a672123c7872f6b9b75a9a2b6bb3aea504de6a.tar.gz
mibs-98a672123c7872f6b9b75a9a2b6bb3aea504de6a.zip
Initial commitHEADmain
Diffstat (limited to 'MIBS/avocent/ACS-MIB')
-rw-r--r--MIBS/avocent/ACS-MIB2572
1 files changed, 2572 insertions, 0 deletions
diff --git a/MIBS/avocent/ACS-MIB b/MIBS/avocent/ACS-MIB
new file mode 100644
index 0000000..9587a10
--- /dev/null
+++ b/MIBS/avocent/ACS-MIB
@@ -0,0 +1,2572 @@
+--------------------------------------------------------------------------------
+-- Avocent ACS MIB
+-- Copyright 2009 Avocent Corporation
+-- Revision: 2.0.1
+-- Last Modified: October 10, 2010
+--------------------------------------------------------------------------------
+
+ACS-MIB DEFINITIONS ::= BEGIN
+
+IMPORTS
+ Gauge,TimeTicks,IpAddress,Counter,NetworkAddress
+ FROM RFC1155-SMI
+ PhysAddress
+ FROM RFC1213-MIB
+ enterprises, MODULE-IDENTITY
+ FROM SNMPv2-SMI
+ OBJECT-TYPE, MODULE-IDENTITY, OBJECT-IDENTITY, Integer32
+ FROM SNMPv2-SMI
+ DisplayString
+ FROM SNMPv2-TC
+ InterfaceIndex, InterfaceIndexOrZero
+ FROM IF-MIB
+ TRAP-TYPE
+ FROM RFC-1215;
+
+--------------------------------------------------------------------------------
+-- Object Groupings
+--------------------------------------------------------------------------------
+
+--@ Note: every product type should be uniquely identified underneath the
+--@ acsProducts object group. Each product should report its unique acsProducts
+--@ OBJECT IDENTIFIER in mib-2.system.sysObjectID. Please see the file
+--@ "_Avocent Enterprise Object Identifier Assignment.txt" for a list of the
+--@ IDs that have been assigned.
+
+-- enterprises .1.3.6.1.4.1
+
+-- avocent OBJECT IDENTIFIER ::= { enterprises 10418 }
+
+acs MODULE-IDENTITY
+ LAST-UPDATED "201010100000Z"
+ ORGANIZATION "Avocent Corporation"
+ CONTACT-INFO "postal : Avocent Corporation
+ 47281 Bayside Parkway
+ Fremont, CA 94538, USA
+ e-mail : Technical Support
+ techsupport@avocent.com"
+ DESCRIPTION
+ "This module defines the Avocent MIB extensions to
+ ACS60xx products."
+ REVISION "201010100000Z"
+ DESCRIPTION "Add products acs6004 and acs6008"
+ REVISION "200912110000Z"
+ DESCRIPTION "Extended acsPowerMgmt to support data monitoring
+ and Avocent PM-PDUs"
+ REVISION "200709170000Z"
+ DESCRIPTION "First Draft"
+::= { enterprises 10418 16 }
+
+acsProducts OBJECT IDENTIFIER ::= { acs 1 }
+acsManagement OBJECT IDENTIFIER ::= { acs 2 }
+--
+acs6016 OBJECT IDENTIFIER ::= { acsProducts 1 } -- 10418.16.1.1
+acs6032 OBJECT IDENTIFIER ::= { acsProducts 2 } -- 10418.16.1.2
+acs6048 OBJECT IDENTIFIER ::= { acsProducts 3 } -- 10418.16.1.3
+acs6004 OBJECT IDENTIFIER ::= { acsProducts 4 } -- 10418.16.1.4
+acs6008 OBJECT IDENTIFIER ::= { acsProducts 5 } -- 10418.16.1.5
+
+acsAppliance OBJECT IDENTIFIER ::= { acsManagement 1 } -- 10418.16.2.1
+acsSessions OBJECT IDENTIFIER ::= { acsManagement 2 } -- 10418.16.2.2
+acsSerialPort OBJECT IDENTIFIER ::= { acsManagement 3 } -- 10418.16.2.3
+acsPowerMgmt OBJECT IDENTIFIER ::= { acsManagement 5 } -- 10418.16.2.5
+
+-- objects under acsPowerMgmt
+-- acsPowerMgmtNumSerialPorts ::= { acsPowerMgmt 1 }
+-- acsPowerMgmtSerialTable ::= { acsPowerMgmt 2 }
+-- acsPowerMgmtPDUTable ::= { acsPowerMgmt 3 }
+-- acsPowerMgmtTotalNumberOfOutlets ::= { acsPowerMgmt 4 }
+-- acsPowerMgmtOutletsTable ::= { acsPowerMgmt 5 }
+-- acsPowerMgmtNumberOfOutletGroup ::= { acsPowerMgmt 6 }
+-- acsPowerMgmtGroupTable ::= { acsPowerMgmt 7 }
+-- acsPowerMgmtPhasesTable ::= { acsPowerMgmt 8 }
+-- acsPowerMgmtBanksTable ::= { acsPowerMgmt 9 }
+-- acsPowerMgmtEnvMonTable ::= { acsPowerMgmt 10 }
+-- acsPowerMgmtOutElecMonTable ::= { acsPowerMgmt 11 }
+
+
+--
+-- Note that traps are defined in a separate trap MIB
+--
+acsTrapObject OBJECT IDENTIFIER ::= { acsManagement 6 } -- 10418.16.2.6
+
+--
+-- Type Definitions
+--
+
+--
+-- Each enumeration represents the states of the appliance power supplies.
+PowerSupplyState ::= INTEGER
+{
+ statePowerOn(1),
+ statePowerOff(2),
+ powerNotInstaled(9999)
+}
+
+--
+-- Each enumeration represents the speed of the serial port.
+SerialPortSpeed ::= INTEGER
+{
+ speed300bps(300),
+ speed600bps(600),
+ speed1200bps(1200),
+ speed2400bps(2400),
+ speed4800bps(4800),
+ speed9600bps(9600),
+ speed19200bps(19200),
+ speed38400bps(38400),
+ speed57600bps(57600),
+ speed115200bps(115200),
+ speed230400bps(230400),
+ speed460800bps(460800)
+}
+
+--
+-- Each enumeration represents the state of the RS-232C signal.
+SerialPortSignalState ::=INTEGER
+{
+ up(1),
+ down(2)
+}
+
+--
+-- Each enumeration represents the RJ-45 pin-out
+SerialPortPinOut ::=INTEGER
+{
+ cyclades(1),
+ cisco(2)
+}
+
+--
+-- acsAppliance
+-- OBJECT IDENTIFIER ::= { acsManagement 1 } 10418.16.2.1
+--
+acsHostName OBJECT-TYPE
+ SYNTAX DisplayString ( SIZE (0..32) )
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The appliance name"
+::= { acsAppliance 1 }
+
+acsProductModel OBJECT-TYPE
+ SYNTAX DisplayString ( SIZE (0..50) )
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The appliance product model"
+::= { acsAppliance 2 }
+
+acsPartNumber OBJECT-TYPE
+ SYNTAX DisplayString ( SIZE (0..32) )
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The part number of this appliance as shown on the label
+ attached or imprinted on the appliance."
+::= { acsAppliance 3 }
+
+acsSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString ( SIZE (0..32) )
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The serial number of this appliance as shown on the label
+ attached or imprinted on the appliance."
+::= { acsAppliance 4 }
+
+acsEIDNumber OBJECT-TYPE
+ SYNTAX DisplayString ( SIZE (0..32) )
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The electronic ID number (EID) of this appliance as shown on the label
+ attached or imprinted on the appliance."
+::= { acsAppliance 5 }
+
+acsBootcodeVersion OBJECT-TYPE
+ SYNTAX DisplayString ( SIZE (0..32) )
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The version of the bootcode of this appliance."
+::= { acsAppliance 6 }
+
+acsFirmwareVersion OBJECT-TYPE
+ SYNTAX DisplayString ( SIZE (0..32) )
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The version of the firmware of this appliance."
+::= { acsAppliance 7 }
+
+acsPowerSupply OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "It gives information about Power Supply of this appliance"
+::= { acsAppliance 8 }
+
+acsPowerSupplyNumber OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Number of the power supplies of this appliance"
+::= { acsPowerSupply 1 }
+
+acsPowerSupplyStatePw1 OBJECT-TYPE
+ SYNTAX PowerSupplyState
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "State of the first power supply"
+::= { acsPowerSupply 2 }
+
+acsPowerSupplyStatePw2 OBJECT-TYPE
+ SYNTAX PowerSupplyState
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "State of the second power supply"
+::= { acsPowerSupply 3 }
+
+acsReboot OBJECT-TYPE
+ SYNTAX INTEGER {
+ noAction(1),
+ reboot(2)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "A set value of reboot(2) will reboot the appliance.
+ noAction(1) = always returned in a GET. Does nothing if SET.
+ reboot(2) = when SET the appliance immediately reboots."
+::= { acsAppliance 9 }
+
+--
+-- acsSessions
+-- OBJECT IDENTIFIER ::= { acsManagement 2 } 10418.16.2.2
+--
+acsActiveSessionsNumberOfSession OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Number of active sessions."
+::= { acsSessions 1 }
+
+acsActiveSessionsTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AcsActiveSessionsTableEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "This table contains the list of active sessions."
+::= { acsSessions 2 }
+
+acsActiveSessionsTableEntry OBJECT-TYPE
+ SYNTAX AcsActiveSessionsTableEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "each entry has the information about the active session"
+ INDEX { acsActiveSessionsTableIndex }
+::= { acsActiveSessionsTable 1 }
+
+AcsActiveSessionsTableEntry ::= SEQUENCE {
+ acsActiveSessionsTableIndex InterfaceIndexOrZero,
+ acsActiveSessionsTableUser DisplayString, -- user name
+ acsActiveSessionsTableGroup DisplayString, -- group name
+ acsActiveSessionsTableType DisplayString, -- RO/RW-ssh,telnet or web
+ acsActiveSessionsTableConnection DisplayString, -- type + target name
+ acsActiveSessionsTableSessionTime DisplayString, -- time of session
+ acsActiveSessionsTableFrom DisplayString, -- source of the session
+ acsActiveSessionsTableKill INTEGER
+}
+
+acsActiveSessionsTableIndex OBJECT-TYPE
+ SYNTAX InterfaceIndexOrZero
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "A unique index representing an entry in this table."
+::= { acsActiveSessionsTableEntry 1 }
+
+acsActiveSessionsTableUser OBJECT-TYPE
+ SYNTAX DisplayString ( SIZE (0..32) )
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The name of the user that opens this session."
+::= { acsActiveSessionsTableEntry 2 }
+
+acsActiveSessionsTableGroup OBJECT-TYPE
+ SYNTAX DisplayString ( SIZE (0..32) )
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The name of the group that the user belongs to."
+::= { acsActiveSessionsTableEntry 3 }
+
+acsActiveSessionsTableType OBJECT-TYPE
+ SYNTAX DisplayString ( SIZE (0..32) )
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The session type."
+::= { acsActiveSessionsTableEntry 4 }
+
+acsActiveSessionsTableConnection OBJECT-TYPE
+ SYNTAX DisplayString ( SIZE (0..32) )
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Connection type."
+::= { acsActiveSessionsTableEntry 5 }
+
+acsActiveSessionsTableSessionTime OBJECT-TYPE
+ SYNTAX DisplayString ( SIZE (0..32) )
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Time of the session"
+::= { acsActiveSessionsTableEntry 6 }
+
+acsActiveSessionsTableFrom OBJECT-TYPE
+ SYNTAX DisplayString ( SIZE (0..32) )
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The source IP address of the session."
+::= { acsActiveSessionsTableEntry 7 }
+
+acsActiveSessionsTableKill OBJECT-TYPE
+ SYNTAX INTEGER {
+ noAction(1),
+ killSession(2)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "A set value of killSession(2) will kill the session.
+ noAction(1) = always returned in a GET. Does nothing if SET.
+ killSession(2)= when SET the appliance immediately kills the session."
+::= { acsActiveSessionsTableEntry 8 }
+
+--
+-- acsSerialPort
+-- OBJECT IDENTIFIER ::= { acsManagement 3 } 10418.16.2.3
+--
+
+acsSerialPortNumberOfPorts OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Number of Serial Ports (physical serial port plus Aux Port."
+::= { acsSerialPort 1 }
+
+acsSerialPortTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AcsSerialPortTableEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "This table contains information about serial ports."
+::= { acsSerialPort 2 }
+
+acsSerialPortTableEntry OBJECT-TYPE
+ SYNTAX AcsSerialPortTableEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "each entry has the information about specific serial port."
+ INDEX { acsSerialPortTableNumber }
+::= { acsSerialPortTable 1 }
+
+AcsSerialPortTableEntry ::= SEQUENCE {
+ acsSerialPortTableNumber Integer32, -- serial port number
+ acsSerialPortTableDeviceName DisplayString, -- associated device name
+ acsSerialPortTableStatus INTEGER, -- status of serial port
+ acsSerialPortTableName DisplayString, -- associated name
+ acsSerialPortTableProfile INTEGER, -- configured profile
+ acsSerialPortTablePinOut SerialPortPinOut, -- configure RJ45 pin-out
+ acsSerialPortTableComSpeed SerialPortSpeed, -- configured speed
+ acsSerialPortTableComParity INTEGER, -- configured parity
+ acsSerialPortTableComDataSize Integer32, -- configured data size
+ acsSerialPortTableComStopBits Integer32, -- configured stop bits
+ acsSerialPortTableComFlowControl INTEGER, -- configured flow control
+ acsSerialPortTableSignalStateDTR SerialPortSignalState, -- state of DTR RS-232C signal
+ acsSerialPortTableSignalStateDCD SerialPortSignalState, -- state of DCD RS-232C signal
+ acsSerialPortTableSignalStateRTS SerialPortSignalState, -- state of RTS RS-232C signal
+ acsSerialPortTableSignalStateCTS SerialPortSignalState, -- state of CTS RS-232C signal
+ acsSerialPortTableTxBytes Integer32, -- number of transmitted bytes
+ acsSerialPortTableRxBytes Integer32, -- number of received bytes
+ acsSerialPortTableFrameError Integer32, -- number of detected frame errors
+ acsSerialPortTableParityError Integer32, -- number of detected parity errors
+ acsSerialPortTableBreak Integer32, -- number of detected break
+ acsSerialPortTableOverrun Integer32 -- number of detected overrun errors
+}
+
+acsSerialPortTableNumber OBJECT-TYPE
+ SYNTAX Integer32 (1..49)
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "A unique index representing an entry in this table.
+ It is the number of the serial port. For AUX port,
+ the number will be the number of physical serial ports plus 1."
+::= { acsSerialPortTableEntry 1 }
+
+acsSerialPortTableDeviceName OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..25))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The associated device name for the serial port."
+::= { acsSerialPortTableEntry 2 }
+
+acsSerialPortTableStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(1),
+ idle(2),
+ inUse(3)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The status of the serial port:
+ disabled(1) = it was configured as disable.
+ idle(2) = there is not any session opened in this port.
+ inUse(3) = there is session(s) opened in this port."
+::= { acsSerialPortTableEntry 3 }
+
+acsSerialPortTableName OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..25))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Name associated with this serial port."
+::= { acsSerialPortTableEntry 4 }
+
+acsSerialPortTableProfile OBJECT-TYPE
+ SYNTAX INTEGER {
+ casProfile(1),
+ tsProfile(2),
+ dialInProfile(3),
+ powerProfile(4)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Configured profile for this serial port."
+::= { acsSerialPortTableEntry 5 }
+
+acsSerialPortTablePinOut OBJECT-TYPE
+ SYNTAX SerialPortPinOut
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "RJ45 Pin-out configured for this serial port."
+::= { acsSerialPortTableEntry 6 }
+
+acsSerialPortTableComSpeed OBJECT-TYPE
+ SYNTAX SerialPortSpeed
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Speed configured for this serial port."
+::= { acsSerialPortTableEntry 7 }
+
+acsSerialPortTableComParity OBJECT-TYPE
+ SYNTAX INTEGER {
+ none(1),
+ odd(2),
+ even(3)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Parity configured for this serial port."
+::= { acsSerialPortTableEntry 8 }
+
+acsSerialPortTableComDataSize OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Data Size configured for this serial port."
+::= { acsSerialPortTableEntry 9 }
+
+acsSerialPortTableComStopBits OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Number of Stop Bits configured for this serial port."
+::= { acsSerialPortTableEntry 10 }
+
+acsSerialPortTableComFlowControl OBJECT-TYPE
+ SYNTAX INTEGER {
+ none(1),
+ hardware(2),
+ software(3)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Flow Control configured for this serial port."
+::= { acsSerialPortTableEntry 11 }
+
+acsSerialPortTableSignalStateDTR OBJECT-TYPE
+ SYNTAX SerialPortSignalState
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "State of the DTR RS-232C signal."
+::= { acsSerialPortTableEntry 12 }
+
+acsSerialPortTableSignalStateDCD OBJECT-TYPE
+ SYNTAX SerialPortSignalState
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "State of the DCD RS-232C signal."
+::= { acsSerialPortTableEntry 13 }
+
+acsSerialPortTableSignalStateRTS OBJECT-TYPE
+ SYNTAX SerialPortSignalState
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "State of the RTS RS-232C signal."
+::= { acsSerialPortTableEntry 14 }
+
+acsSerialPortTableSignalStateCTS OBJECT-TYPE
+ SYNTAX SerialPortSignalState
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "State of the CTS RS-232C signal."
+::= { acsSerialPortTableEntry 15 }
+
+acsSerialPortTableTxBytes OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of transmited bytes by the serial port."
+::= { acsSerialPortTableEntry 16 }
+
+acsSerialPortTableRxBytes OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of received bytes by the serial port."
+::= { acsSerialPortTableEntry 17 }
+
+acsSerialPortTableFrameError OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of frame error detected in the serial port."
+::= { acsSerialPortTableEntry 18 }
+
+acsSerialPortTableParityError OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of parity error detected in the serial port."
+::= { acsSerialPortTableEntry 19 }
+
+acsSerialPortTableBreak OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of break detected in the serial port."
+::= { acsSerialPortTableEntry 20 }
+
+acsSerialPortTableOverrun OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of overrun error detected in the serial port."
+::= { acsSerialPortTableEntry 21 }
+
+--
+-- acsPowerMgmt
+-- OBJECT IDENTIFIER ::= { acsManagement 5 } 10418.16.2.5
+--
+acsPowerMgmtNumSerialPorts OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of Serial Ports that has PDU connected on the appliance."
+::= { acsPowerMgmt 1 }
+
+acsPowerMgmtSerialTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AcsPowerMgmtSerialTableEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "Information about each serial port thas has PDU connect."
+::= { acsPowerMgmt 2 }
+
+acsPowerMgmtSerialTableEntry OBJECT-TYPE
+ SYNTAX AcsPowerMgmtSerialTableEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "Information about each serial port thas has PDU connect."
+ INDEX { acsPowerMgmtSerialTableIndex }
+::= { acsPowerMgmtSerialTable 1 }
+
+AcsPowerMgmtSerialTableEntry ::= SEQUENCE {
+ acsPowerMgmtSerialTableIndex InterfaceIndex,
+ acsPowerMgmtSerialTablePortNumber Integer32,
+ acsPowerMgmtSerialTableDeviceName DisplayString,
+ acsPowerMgmtSerialTableNumberPDUs Integer32
+}
+
+acsPowerMgmtSerialTableIndex OBJECT-TYPE
+ SYNTAX InterfaceIndex
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The index of the register."
+::= { acsPowerMgmtSerialTableEntry 1 }
+
+acsPowerMgmtSerialTablePortNumber OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of the serial port when the PDU is connected."
+::= { acsPowerMgmtSerialTableEntry 2 }
+
+acsPowerMgmtSerialTableDeviceName OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The device name of this serial port."
+::= { acsPowerMgmtSerialTableEntry 3 }
+
+acsPowerMgmtSerialTableNumberPDUs OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Total number of units connected in this serial port."
+::= { acsPowerMgmtSerialTableEntry 4 }
+
+acsPowerMgmtPDUTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AcsPowerMgmtPDUTableEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "This table contains the list of detected PDUs."
+::= { acsPowerMgmt 3 }
+
+acsPowerMgmtPDUTableEntry OBJECT-TYPE
+ SYNTAX AcsPowerMgmtPDUTableEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "each entry has the information about the PDU."
+ INDEX { acsPowerMgmtPDUTablePortNumber, acsPowerMgmtPDUTablePduIndex }
+::= { acsPowerMgmtPDUTable 1 }
+
+AcsPowerMgmtPDUTableEntry ::= SEQUENCE {
+ acsPowerMgmtPDUTablePortNumber InterfaceIndex, -- number of serial port
+ acsPowerMgmtPDUTablePduIndex InterfaceIndexOrZero,
+ acsPowerMgmtPDUTablePduId DisplayString, -- PDU identification
+ acsPowerMgmtPDUTablePortName DisplayString, -- Serial Port Name
+ acsPowerMgmtPDUTableModel DisplayString, -- PDU model
+ acsPowerMgmtPDUTableVendor DisplayString, -- Vendor
+ acsPowerMgmtPDUTableFirmwareVersion DisplayString, -- Firmware Version
+ acsPowerMgmtPDUTableNumberOfOutlets Integer32,
+ acsPowerMgmtPDUTableCurrentNOS Integer32, -- OBSOLETED number of current sensors
+ acsPowerMgmtPDUTableCurrent1Value Integer32, -- OBSOLETED actual value for current of the sensor 1
+ acsPowerMgmtPDUTableCurrent1Max Integer32, -- OBSOLETED max value for current of the sensor 1
+ acsPowerMgmtPDUTableCurrent2Value Integer32, -- OBSOLETED actual value for current of the sensor 2
+ acsPowerMgmtPDUTableCurrent2Max Integer32, -- OBSOLETED max value for current of the sensor 2
+ acsPowerMgmtPDUTableCurrent3Value Integer32, -- OBSOLETED actual value for current of the sensor 3
+ acsPowerMgmtPDUTableCurrent3Max Integer32, -- OBSOLETED max value for current of the sensor 3
+ acsPowerMgmtPDUTableTemperatureNOS Integer32, -- OBSOLETED number of temperature sensors
+ acsPowerMgmtPDUTableTemperature1Value Integer32, -- OBSOLETED actual value for Temperature 1
+ acsPowerMgmtPDUTableTemperature1Max Integer32, -- OBSOLETED max value for Temperature 1
+ acsPowerMgmtPDUTableTemperature2Value Integer32, -- OBSOLETED actual value for Temperaturet 2
+ acsPowerMgmtPDUTableTemperature2Max Integer32, -- OBSOLETED max value for Temperature 2
+ acsPowerMgmtPDUTableTemperature3Value Integer32, -- OBSOLETED actual value for Temperature 3
+ acsPowerMgmtPDUTableTemperature3Max Integer32, -- OBSOLETED max value for Temperature 3
+ acsPowerMgmtPDUTableHumidityNOS Integer32, -- OBSOLETED humidity number of humidity sensors
+ acsPowerMgmtPDUTableHumidity1Value Integer32, -- OBSOLETED actual value for Humidity of the sensor 1
+ acsPowerMgmtPDUTableHumidity1Max Integer32, -- OBSOLETED max value for Humidityof the sensor 1
+ acsPowerMgmtPDUTableHumidity2Value Integer32, -- OBSOLETED actual value for Humidity of the sensor 2
+ acsPowerMgmtPDUTableHumidity2Max Integer32, -- OBSOLETED max value for Humidity of the sensor 2
+ acsPowerMgmtPDUTableHumidity3Value Integer32, -- OBSOLETED actual value for Humidity of the sensor 3
+ acsPowerMgmtPDUTableHumidity3Max Integer32, -- OBSOLETED max value for Humidity of the sensor 3
+ acsPowerMgmtPDUTableVoltageNOS Integer32, -- OBSOLETED number of voltage sensor
+ acsPowerMgmtPDUTableVoltage1Value Integer32, -- OBSOLETED actual value for Voltage of the sensor 1
+ acsPowerMgmtPDUTableVoltage1Max Integer32, -- OBSOLETED max value for Voltage of the sensor 1
+ acsPowerMgmtPDUTableVoltage2Value Integer32, -- OBSOLETED actual value for Voltage of the sensor 2
+ acsPowerMgmtPDUTableVoltage2Max Integer32, -- OBSOLETED max value for Voltaget of the sensor 2
+ acsPowerMgmtPDUTableVoltage3Value Integer32, -- OBSOLETED actual value for Voltage of the sensor 3
+ acsPowerMgmtPDUTableVoltage3Max Integer32, -- OBSOLETED max value for Voltage of the sensor 3
+ acsPowerMgmtPDUTableNumberOfPhases Integer32, -- number of phases (single or 3-phases)
+ acsPowerMgmtPDUTableNumberOfBanks Integer32, -- number of banks
+ acsPowerMgmtPDUTableCurrentValue Integer32, -- actual value of PDU current sensor
+ acsPowerMgmtPDUTableCurrentMax Integer32, -- max detected value of current sensor
+ acsPowerMgmtPDUTableCurrentMin Integer32, -- min detected value of current sensor
+ acsPowerMgmtPDUTableCurrentAvg Integer32, -- average value for current sensor
+ acsPowerMgmtPDUTableCurrentReset INTEGER, -- reset max, min and avg values
+ acsPowerMgmtPDUTableVoltageType INTEGER, -- type of PDU voltage
+ acsPowerMgmtPDUTableVoltageValue Integer32, -- actual value of PDU voltage
+ acsPowerMgmtPDUTableVoltageMax Integer32, -- max value of voltage sensor
+ acsPowerMgmtPDUTableVoltageMin Integer32, -- min value of voltage sensor
+ acsPowerMgmtPDUTableVoltageAvg Integer32, -- avg value of voltage sensor
+ acsPowerMgmtPDUTableVoltageReset INTEGER, -- reset max, min and avg values
+ acsPowerMgmtPDUTablePowerType INTEGER, -- type of PDU power consumption
+ acsPowerMgmtPDUTablePowerValue Integer32, -- actual value of PDU power consumption
+ acsPowerMgmtPDUTablePowerMax Integer32, -- max value
+ acsPowerMgmtPDUTablePowerMin Integer32, -- min value
+ acsPowerMgmtPDUTablePowerAvg Integer32, -- average value
+ acsPowerMgmtPDUTablePowerReset INTEGER, -- reset max, min and avg values
+ acsPowerMgmtPDUTablePowerFactorType INTEGER, -- type of PDU power factor
+ acsPowerMgmtPDUTablePowerFactorValue Integer32, -- actual value of PDU power factor
+ acsPowerMgmtPDUTablePowerFactorMax Integer32, -- max value for power factor
+ acsPowerMgmtPDUTablePowerFactorMin Integer32, -- min value for power factor
+ acsPowerMgmtPDUTablePowerFactorAvg Integer32, -- avg value for power factor
+ acsPowerMgmtPDUTablePowerFactorReset INTEGER, -- reset max, min and avg values
+ acsPowerMgmtPDUTableAlarm INTEGER, -- status of PDU alarm
+ acsPowerMgmtPDUTableEnvSensors Integer32 -- number of environmental sensors
+}
+
+acsPowerMgmtPDUTablePortNumber OBJECT-TYPE
+ SYNTAX InterfaceIndex
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Number of serial port when the PDU is connected."
+::= { acsPowerMgmtPDUTableEntry 1 }
+
+acsPowerMgmtPDUTablePduIndex OBJECT-TYPE
+ SYNTAX InterfaceIndexOrZero
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "A PDU position in the chain."
+::= { acsPowerMgmtPDUTableEntry 2 }
+
+acsPowerMgmtPDUTablePduId OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "PDU identification."
+::= { acsPowerMgmtPDUTableEntry 3 }
+
+acsPowerMgmtPDUTablePortName OBJECT-TYPE
+ SYNTAX DisplayString
+
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Name of serial port when the PDU is connected."
+::= { acsPowerMgmtPDUTableEntry 4 }
+
+acsPowerMgmtPDUTableModel OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Model of the PDU."
+::= { acsPowerMgmtPDUTableEntry 5 }
+
+acsPowerMgmtPDUTableVendor OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Vendor of the PDU."
+::= { acsPowerMgmtPDUTableEntry 6 }
+
+acsPowerMgmtPDUTableFirmwareVersion OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Version of the PDU firmware."
+::= { acsPowerMgmtPDUTableEntry 7 }
+
+acsPowerMgmtPDUTableNumberOfOutlets OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Number of outlets of the PDU."
+::= { acsPowerMgmtPDUTableEntry 8 }
+
+acsPowerMgmtPDUTableCurrentNOS OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS obsolete
+ DESCRIPTION
+ "Number of current sensors in the PDU."
+::= { acsPowerMgmtPDUTableEntry 9 }
+
+acsPowerMgmtPDUTableCurrent1Value OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS obsolete
+ DESCRIPTION
+ "Current of the sensor 1 in this PDU unit in AMP.
+ The value of this object is the actual current in
+ AMP * 10. You need to translate the readed value
+ (Ex. : value is 5, the current is 0.5 AMP.)"
+::= { acsPowerMgmtPDUTableEntry 10 }
+
+acsPowerMgmtPDUTableCurrent1Max OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS obsolete
+ DESCRIPTION
+ "Maximum current of the sensor 1 in this PDU unit in AMP.
+ When the PDU does not have support for maximum value,
+ the value will be 0.
+ The value of this object is the actual current in
+ AMP * 10. You need to translate the readed value
+ (Ex. : value is 5, the current is 0.5 AMP.)
+ Clear this value, set it with Zero value."
+::= { acsPowerMgmtPDUTableEntry 11 }
+
+acsPowerMgmtPDUTableCurrent2Value OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS obsolete
+ DESCRIPTION
+ "Current of the sensor 2 in this PDU unit in AMP.
+ The value of this object is the actual current in
+ AMP * 10. You need to translate the readed value
+ (Ex. : value is 5, the current is 0.5 AMP.)"
+::= { acsPowerMgmtPDUTableEntry 12 }
+
+acsPowerMgmtPDUTableCurrent2Max OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS obsolete
+ DESCRIPTION
+ "Maximum current of the sensor 2 in this PDU unit in AMP.
+ When the PDU does not have support for maximum value,
+ the value will be 0.
+ The value of this object is the actual current in
+ AMP * 10. You need to translate the readed value
+ (Ex. : value is 5, the current is 0.5 AMP.)
+ Clear this value, set it with Zero value."
+::= { acsPowerMgmtPDUTableEntry 13}
+
+acsPowerMgmtPDUTableCurrent3Value OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS obsolete
+ DESCRIPTION
+ "Current of the sensor 3 in this PDU unit in AMP.
+ The value of this object is the actual current in
+ AMP * 10. You need to translate the readed value
+ (Ex. : value is 5, the current is 0.5 AMP.)"
+::= { acsPowerMgmtPDUTableEntry 14 }
+
+acsPowerMgmtPDUTableCurrent3Max OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS obsolete
+ DESCRIPTION
+ "Maximum current of the sensor 3 in this PDU unit in AMP.
+ When the PDU does not have support for maximum value,
+ the value will be 0.
+ The value of this object is the actual current in
+ AMP * 10. You need to translate the readed value
+ (Ex. : value is 5, the current is 0.5 AMP.)
+ Clear this value, set it with Zero value."
+::= { acsPowerMgmtPDUTableEntry 15 }
+
+acsPowerMgmtPDUTableTemperatureNOS OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS obsolete
+ DESCRIPTION
+ "Number of temperature sensors in the PDU."
+::= { acsPowerMgmtPDUTableEntry 16 }
+
+acsPowerMgmtPDUTableTemperature1Value OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS obsolete
+ DESCRIPTION
+ "Temperature of this PM unit in Celsius degrees.
+ The value of this object is the actual temperature in
+ degrees C * 10. You need to translate the readed value
+ (Ex. : value is 240, the temperature is 24 Celsius.)
+ If the temperature measurement is not installed this
+ value will be 0.
+ Valid values are 5 to 999 ( 0.5 to 99.9 Celsius)."
+::= { acsPowerMgmtPDUTableEntry 17 }
+
+acsPowerMgmtPDUTableTemperature1Max OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS obsolete
+ DESCRIPTION
+ "Maximum temperature detected in this PM unit in Celsius degrees.
+ The value will be Zero when the PDU does not have support for maximum value.
+ The value of this object is the actual temperature in
+ degrees C * 10. You need to translate the readed value
+ (Ex. : value is 240, the temperature is 24 Celsius.)
+ If the temperature measurement is not installed this
+ value will be 0.
+ Valid values are 5 to 999 ( 0.5 to 99.9 Celsius).
+ Set with Zero value to clear the max. temperature."
+::= { acsPowerMgmtPDUTableEntry 18 }
+
+acsPowerMgmtPDUTableTemperature2Value OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS obsolete
+ DESCRIPTION
+ "Temperature of this PM unit in Celsius degrees.
+ The value of this object is the actual temperature in
+ degrees C * 10. You need to translate the readed value
+ (Ex. : value is 240, the temperature is 24 Celsius.)
+ If the temperature measurement is not installed this
+ value will be 0.
+ Valid values are 5 to 999 ( 0.5 to 99.9 Celsius)."
+::= { acsPowerMgmtPDUTableEntry 19 }
+
+acsPowerMgmtPDUTableTemperature2Max OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS obsolete
+ DESCRIPTION
+ "Maximum temperature detected in this PM unit in Celsius degrees.
+ The value will be Zero when the PDU does not have support for maximum value.
+ The value of this object is the actual temperature in
+ degrees C * 10. You need to translate the readed value
+ (Ex. : value is 240, the temperature is 24 Celsius.)
+ If the temperature measurement is not installed this
+ value will be 0.
+ Valid values are 5 to 999 ( 0.5 to 99.9 Celsius).
+ Set with Zero value to clear the max. temperature."
+::= { acsPowerMgmtPDUTableEntry 20 }
+
+acsPowerMgmtPDUTableTemperature3Value OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS obsolete
+ DESCRIPTION
+ "Temperature of this PM unit in Celsius degrees.
+ The value of this object is the actual temperature in
+ degrees C * 10. You need to translate the readed value
+ (Ex. : value is 240, the temperature is 24 Celsius.)
+ If the temperature measurement is not installed this
+ value will be 0.
+ Valid values are 5 to 999 ( 0.5 to 99.9 Celsius)."
+::= { acsPowerMgmtPDUTableEntry 21 }
+
+acsPowerMgmtPDUTableTemperature3Max OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS obsolete
+ DESCRIPTION
+ "Maximum temperature detected in this PM unit in Celsius degrees.
+ The value will be Zero when the PDU does not have support for maximum value.
+ The value of this object is the actual temperature in
+ degrees C * 10. You need to translate the readed value
+ (Ex. : value is 240, the temperature is 24 Celsius.)
+ If the temperature measurement is not installed this
+ value will be 0.
+ Valid values are 5 to 999 ( 0.5 to 99.9 Celsius).
+ Set with Zero value to clear the max. temperature."
+::= { acsPowerMgmtPDUTableEntry 22 }
+
+acsPowerMgmtPDUTableHumidityNOS OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS obsolete
+ DESCRIPTION
+ "Number of humidity sensors in the PDU."
+::= { acsPowerMgmtPDUTableEntry 23 }
+
+acsPowerMgmtPDUTableHumidity1Value OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS obsolete
+ DESCRIPTION
+ "Humidity of this PM unit .
+ If the humidity measurement is not installed this
+ value will be 0."
+::= { acsPowerMgmtPDUTableEntry 24 }
+
+acsPowerMgmtPDUTableHumidity1Max OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS obsolete
+ DESCRIPTION
+ "Maximum humidity detected in this PM unit.
+ If the humidity measurement is not installed or the PDU does not have support for maximum value this
+ value will be 0.
+ Set with Zero value to clear the max. temperature."
+::= { acsPowerMgmtPDUTableEntry 25 }
+
+acsPowerMgmtPDUTableHumidity2Value OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS obsolete
+ DESCRIPTION
+ "Humidity of this PM unit .
+ If the humidity measurement is not installed this
+ value will be 0."
+::= { acsPowerMgmtPDUTableEntry 26 }
+
+acsPowerMgmtPDUTableHumidity2Max OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS obsolete
+ DESCRIPTION
+ "Maximum humidity detected in this PM unit.
+ If the humidity measurement is not installed or the PDU does not have support for maximum value this
+ value will be 0.
+ Set with Zero value to clear the max. temperature."
+::= { acsPowerMgmtPDUTableEntry 27 }
+
+acsPowerMgmtPDUTableHumidity3Value OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS obsolete
+ DESCRIPTION
+ "Humidity of this PM unit .
+ If the humidity measurement is not installed this
+ value will be 0."
+::= { acsPowerMgmtPDUTableEntry 28 }
+
+acsPowerMgmtPDUTableHumidity3Max OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS obsolete
+ DESCRIPTION
+ "Maximum humidity detected in this PM unit.
+ If the humidity measurement is not installed or the PDU does not have support for maximum value this
+ value will be 0.
+ Set with Zero value to clear the max. temperature."
+::= { acsPowerMgmtPDUTableEntry 29 }
+
+acsPowerMgmtPDUTableVoltageNOS OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS obsolete
+ DESCRIPTION
+ "Number of voltage sensors in the PDU."
+::= { acsPowerMgmtPDUTableEntry 30 }
+
+acsPowerMgmtPDUTableVoltage1Value OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS obsolete
+ DESCRIPTION
+ "Voltage of this sensor in this PDU unit."
+::= { acsPowerMgmtPDUTableEntry 31 }
+
+acsPowerMgmtPDUTableVoltage1Max OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS obsolete
+ DESCRIPTION
+ "Maximum voltage of this sensor in this PDU unit.
+ Set with Zero value to clear the maximum voltage."
+::= { acsPowerMgmtPDUTableEntry 32 }
+
+acsPowerMgmtPDUTableVoltage2Value OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS obsolete
+ DESCRIPTION
+ "Voltage of this sensor in this PDU unit."
+::= { acsPowerMgmtPDUTableEntry 33 }
+
+acsPowerMgmtPDUTableVoltage2Max OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS obsolete
+ DESCRIPTION
+ "Maximum voltage of this sensor in this PDU unit.
+ Set with Zero value to clear the maximum voltage."
+::= { acsPowerMgmtPDUTableEntry 34 }
+
+acsPowerMgmtPDUTableVoltage3Value OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS obsolete
+ DESCRIPTION
+ "Voltage of this sensor in this PDU unit."
+::= { acsPowerMgmtPDUTableEntry 35 }
+
+acsPowerMgmtPDUTableVoltage3Max OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS obsolete
+ DESCRIPTION
+ "Maximum voltage of this sensor in this PDU unit.
+ Set with Zero value to clear the maximum voltage."
+::= { acsPowerMgmtPDUTableEntry 36 }
+
+acsPowerMgmtPDUTableNumberOfPhases OBJECT-TYPE
+ SYNTAX INTEGER {
+ single-phase (0),
+ three-phase (3)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION "Number of phases of this PDU unit."
+::= { acsPowerMgmtPDUTableEntry 37 }
+
+acsPowerMgmtPDUTableNumberOfBanks OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION "Number of banks of this PDU unit."
+::= { acsPowerMgmtPDUTableEntry 38 }
+
+acsPowerMgmtPDUTableCurrentValue OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Actual value of current sensor in this PDU.( A x 10 )"
+::= { acsPowerMgmtPDUTableEntry 39 }
+
+acsPowerMgmtPDUTableCurrentMax OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Max detected value of current sensor in this PDU.( A x 10 )"
+::= { acsPowerMgmtPDUTableEntry 40 }
+
+acsPowerMgmtPDUTableCurrentMin OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Min detected value of current sensor in this PDU.( A x 10 )"
+::= { acsPowerMgmtPDUTableEntry 41 }
+
+acsPowerMgmtPDUTableCurrentAvg OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Average value for current sensor in this PDU.( A x 10 )"
+::= { acsPowerMgmtPDUTableEntry 42 }
+
+acsPowerMgmtPDUTableCurrentReset OBJECT-TYPE
+ SYNTAX INTEGER {
+ no-action (1),
+ reset (2)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION "Reset max, min and avg values of current."
+::= { acsPowerMgmtPDUTableEntry 43 }
+
+acsPowerMgmtPDUTableVoltageType OBJECT-TYPE
+ SYNTAX INTEGER {
+ none-sensor (0),
+ estimated (1),
+ read (2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION "Type of voltage values."
+::= { acsPowerMgmtPDUTableEntry 44 }
+
+acsPowerMgmtPDUTableVoltageValue OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Actual value of voltage sensor in this PDU unit.( V )"
+::= { acsPowerMgmtPDUTableEntry 45 }
+
+acsPowerMgmtPDUTableVoltageMax OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Max detected value of voltage sensor in this PDU unit.( V )"
+::= { acsPowerMgmtPDUTableEntry 46 }
+
+acsPowerMgmtPDUTableVoltageMin OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Min detected value of voltage sensor in this PDU unit.( V )"
+::= { acsPowerMgmtPDUTableEntry 47 }
+
+acsPowerMgmtPDUTableVoltageAvg OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Average value for voltage sensor in this PDU unit.( V )"
+::= { acsPowerMgmtPDUTableEntry 48 }
+
+acsPowerMgmtPDUTableVoltageReset OBJECT-TYPE
+ SYNTAX INTEGER {
+ no-action (1),
+ reset (2)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION "Reset max, min and avg values of voltage."
+::= { acsPowerMgmtPDUTableEntry 49 }
+
+acsPowerMgmtPDUTablePowerType OBJECT-TYPE
+ SYNTAX INTEGER {
+ none-sensor (0),
+ estimated (1),
+ read (2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION "Type of power consumption values.( W x 10 )"
+::= { acsPowerMgmtPDUTableEntry 50 }
+
+acsPowerMgmtPDUTablePowerValue OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Actual value of power consumption in this PDU unit.( W x 10 )"
+::= { acsPowerMgmtPDUTableEntry 51 }
+
+acsPowerMgmtPDUTablePowerMax OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Max detected value of power consumption in this PDU unit.( W x 10 )"
+::= { acsPowerMgmtPDUTableEntry 52 }
+
+acsPowerMgmtPDUTablePowerMin OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Min detected value of power consumption in this PDU unit.( W x 10 )"
+::= { acsPowerMgmtPDUTableEntry 53 }
+
+acsPowerMgmtPDUTablePowerAvg OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Average value for power consumption in this PDU unit.( W x 10 )"
+::= { acsPowerMgmtPDUTableEntry 54 }
+
+acsPowerMgmtPDUTablePowerReset OBJECT-TYPE
+ SYNTAX INTEGER {
+ no-action (1),
+ reset (2)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION "Reset max, min and avg values of power consumption."
+::= { acsPowerMgmtPDUTableEntry 55 }
+
+acsPowerMgmtPDUTablePowerFactorType OBJECT-TYPE
+ SYNTAX INTEGER {
+ none-sensor (0),
+ estimated (1),
+ read (2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION "Type of power factor values."
+::= { acsPowerMgmtPDUTableEntry 56 }
+
+acsPowerMgmtPDUTablePowerFactorValue OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Actual value of power factor in this PDU unit.( PF x 100 )"
+::= { acsPowerMgmtPDUTableEntry 57 }
+
+acsPowerMgmtPDUTablePowerFactorMax OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Max detected value of power factor in this PDU unit.( PF x 100 )"
+::= { acsPowerMgmtPDUTableEntry 58 }
+
+acsPowerMgmtPDUTablePowerFactorMin OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Min detected value of power factor in this PDU unit.( PF x 100 )"
+::= { acsPowerMgmtPDUTableEntry 59 }
+
+acsPowerMgmtPDUTablePowerFactorAvg OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Average value for power factor in this PDU unit.( PF x 100 )"
+::= { acsPowerMgmtPDUTableEntry 60 }
+
+acsPowerMgmtPDUTablePowerFactorReset OBJECT-TYPE
+ SYNTAX INTEGER {
+ no-action (1),
+ reset (2)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION "Reset max, min and avg values of power factor."
+::= { acsPowerMgmtPDUTableEntry 61 }
+
+acsPowerMgmtPDUTableAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ blow-fuse (2),
+ hw-ocp (3),
+ high-critical (4),
+ high-warning (5),
+ low-warning (6),
+ low-critical (7)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION "Show the PDU alarm status."
+::= { acsPowerMgmtPDUTableEntry 62 }
+
+acsPowerMgmtPDUTableEnvSensors OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Number of environmental sensor in this PDU."
+::= { acsPowerMgmtPDUTableEntry 63 }
+
+
+acsPowerMgmtTotalNumberOfOutlets OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Number of outlets managed by the appliance."
+::= { acsPowerMgmt 4 }
+
+acsPowerMgmtOutletsTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AcsPowerMgmtOutletsTableEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "This table contains the information about outlets."
+::= { acsPowerMgmt 5 }
+
+acsPowerMgmtOutletsTableEntry OBJECT-TYPE
+ SYNTAX AcsPowerMgmtOutletsTableEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "each entry has the information about the outlet."
+ INDEX { acsPowerMgmtOutletsTablePortNumber,
+ acsPowerMgmtOutletsTablePduNumber,
+ acsPowerMgmtOutletsTableNumber }
+::= { acsPowerMgmtOutletsTable 1 }
+
+AcsPowerMgmtOutletsTableEntry ::= SEQUENCE {
+ acsPowerMgmtOutletsTablePortNumber InterfaceIndex, -- serial port #
+ acsPowerMgmtOutletsTablePduNumber InterfaceIndex,
+ acsPowerMgmtOutletsTableNumber InterfaceIndex, -- outlet number in PDU
+ acsPowerMgmtOutletsTableName DisplayString, -- outlet name
+ acsPowerMgmtOutletsTableStatus INTEGER, -- outlet status
+ acsPowerMgmtOutletsTablePowerControl INTEGER, -- manage the outlet
+ acsPowerMgmtOutletsTablePortName DisplayString, -- serial port name
+ acsPowerMgmtOutletsTablePduId DisplayString -- PDU ID
+}
+
+acsPowerMgmtOutletsTablePortNumber OBJECT-TYPE
+ SYNTAX InterfaceIndex
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Serial Port number."
+::= { acsPowerMgmtOutletsTableEntry 1 }
+
+acsPowerMgmtOutletsTablePduNumber OBJECT-TYPE
+ SYNTAX InterfaceIndex
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Index."
+::= { acsPowerMgmtOutletsTableEntry 2 }
+
+acsPowerMgmtOutletsTableNumber OBJECT-TYPE
+ SYNTAX InterfaceIndex
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Number of the outlet in the PDU."
+::= { acsPowerMgmtOutletsTableEntry 3 }
+
+acsPowerMgmtOutletsTableName OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Name of the outlet."
+::= { acsPowerMgmtOutletsTableEntry 4 }
+
+acsPowerMgmtOutletsTableStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ off(1),
+ on(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Status of the outlet."
+::= { acsPowerMgmtOutletsTableEntry 5 }
+
+acsPowerMgmtOutletsTablePowerControl OBJECT-TYPE
+ SYNTAX INTEGER {
+ noAction(1),
+ powerOn(2),
+ powerOff(3),
+ powerCycle(4),
+ powerLock(5),
+ powerUnlock(6)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "A set value of power*(2-6) will send command to PDU.
+ noAction(1) = always returned in a GET. Does nothing if SET.
+ powerOn(2) = when SET the power On command is sent to PDU.
+ powerOff(3) = when SET the power Off command is sent to PDU.
+ powerCycle(4)=when SET the power cycle command is sent to PDU.
+ powerLock(5)= when SET the power lock command is sent to PDU.
+ powerUnlock(6)=when SET the power unlock command is sent to PDU.
+ The powerLock and powerUnlock are valid only for Cyclades-PM PDUs"
+::= { acsPowerMgmtOutletsTableEntry 6 }
+
+acsPowerMgmtOutletsTablePortName OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Serial Port Name where the PDU is connected."
+::= { acsPowerMgmtOutletsTableEntry 7 }
+
+acsPowerMgmtOutletsTablePduId OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "PDU identification."
+::= { acsPowerMgmtOutletsTableEntry 8 }
+
+acsPowerMgmtNumberOfOutletGroup OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Number of configured group of outlets."
+::= { acsPowerMgmt 6 }
+
+acsPowerMgmtGroupTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AcsPowerMgmtGroupTableEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "This table contains the information about group of outlets."
+::= { acsPowerMgmt 7 }
+
+acsPowerMgmtGroupTableEntry OBJECT-TYPE
+ SYNTAX AcsPowerMgmtGroupTableEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "each entry has the information about group of outlets."
+ INDEX { acsPowerMgmtGroupTableIndex }
+::= { acsPowerMgmtGroupTable 1 }
+
+AcsPowerMgmtGroupTableEntry ::= SEQUENCE {
+ acsPowerMgmtGroupTableIndex InterfaceIndexOrZero,
+ acsPowerMgmtGroupTableName DisplayString, -- group name
+ acsPowerMgmtGroupTableStatus INTEGER, -- group status
+ acsPowerMgmtGroupTablePowerControl INTEGER -- manage the group
+}
+
+acsPowerMgmtGroupTableIndex OBJECT-TYPE
+ SYNTAX InterfaceIndexOrZero
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Index of the group."
+::= { acsPowerMgmtGroupTableEntry 1 }
+
+acsPowerMgmtGroupTableName OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Name of the group of outlets."
+::= { acsPowerMgmtGroupTableEntry 2 }
+
+acsPowerMgmtGroupTableStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ off(1),
+ on(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Status of the group of outlet."
+::= { acsPowerMgmtGroupTableEntry 3 }
+
+acsPowerMgmtGroupTablePowerControl OBJECT-TYPE
+ SYNTAX INTEGER {
+ noAction(1),
+ powerOn(2),
+ powerOff(3),
+ powerCycle(4)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "A set value of power*(2-6) will send command to PDU.
+ noAction(1) = always returned in a GET. Does nothing if SET.
+ powerOn(2) = when SET the power On command is sent to PDU.
+ powerOff(3) = when SET the power Off command is sent to PDU.
+ powerCycle(4)=when SET the power cycle command is sent to PDU."
+::= { acsPowerMgmtGroupTableEntry 4 }
+
+acsPowerMgmtPhasesTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AcsPowerMgmtPhasesTableEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "This table contains data monitoring of each detected phase."
+::= { acsPowerMgmt 8 }
+
+acsPowerMgmtPhasesTableEntry OBJECT-TYPE
+ SYNTAX AcsPowerMgmtPhasesTableEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "each entry has the data monitoring about phases."
+ INDEX { acsPowerMgmtPhasesTablePortNumber, acsPowerMgmtPhasesTablePduIndex, acsPowerMgmtPhasesTablePhaseIndex }
+::= { acsPowerMgmtPhasesTable 1 }
+
+AcsPowerMgmtPhasesTableEntry ::= SEQUENCE {
+ acsPowerMgmtPhasesTablePortNumber InterfaceIndex, -- number of serial port
+ acsPowerMgmtPhasesTablePduIndex InterfaceIndexOrZero, -- number of PDU
+ acsPowerMgmtPhasesTablePhaseIndex InterfaceIndexOrZero, -- phase index
+ acsPowerMgmtPhasesTablePhaseName DisplayString, -- Phase Name
+ acsPowerMgmtPhasesTablePduId DisplayString, -- PDU identification
+ acsPowerMgmtPhasesTablePortName DisplayString, -- Serial Port Name
+ acsPowerMgmtPhasesTableCurrentValue Integer32, -- actual value of Phase current sensor
+ acsPowerMgmtPhasesTableCurrentMax Integer32, -- max detected value of current sensor
+ acsPowerMgmtPhasesTableCurrentMin Integer32, -- min detected value of current sensor
+ acsPowerMgmtPhasesTableCurrentAvg Integer32, -- average value for current sensor
+ acsPowerMgmtPhasesTableCurrentReset INTEGER, -- reset max, min and avg values
+ acsPowerMgmtPhasesTableVoltageType INTEGER, -- type of phase voltage
+ acsPowerMgmtPhasesTableVoltageValue Integer32, -- actual value of phase voltage
+ acsPowerMgmtPhasesTableVoltageMax Integer32, -- max value of voltage sensor
+ acsPowerMgmtPhasesTableVoltageMin Integer32, -- min value of voltage sensor
+ acsPowerMgmtPhasesTableVoltageAvg Integer32, -- avg value of voltage sensor
+ acsPowerMgmtPhasesTableVoltageReset INTEGER, -- reset max, min and avg values
+ acsPowerMgmtPhasesTablePowerType INTEGER, -- type of phase power consumption
+ acsPowerMgmtPhasesTablePowerValue Integer32, -- actual value of phase power consumption
+ acsPowerMgmtPhasesTablePowerMax Integer32, -- max value
+ acsPowerMgmtPhasesTablePowerMin Integer32, -- min value
+ acsPowerMgmtPhasesTablePowerAvg Integer32, -- average value
+ acsPowerMgmtPhasesTablePowerReset INTEGER, -- reset max, min and avg values
+ acsPowerMgmtPhasesTablePowerFactorType INTEGER, -- type of phase power factor
+ acsPowerMgmtPhasesTablePowerFactorValue Integer32, -- actual value of phase power factor
+ acsPowerMgmtPhasesTablePowerFactorMax Integer32, -- max value for power factor
+ acsPowerMgmtPhasesTablePowerFactorMin Integer32, -- min value for power factor
+ acsPowerMgmtPhasesTablePowerFactorAvg Integer32, -- avg value for power factor
+ acsPowerMgmtPhasesTablePowerFactorReset INTEGER, -- reset max, min and avg values
+ acsPowerMgmtPhasesTableAlarm INTEGER -- phase alarm status
+}
+
+acsPowerMgmtPhasesTablePortNumber OBJECT-TYPE
+ SYNTAX InterfaceIndex
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Number of serial port when the PDU is connected."
+::= { acsPowerMgmtPhasesTableEntry 1 }
+
+acsPowerMgmtPhasesTablePduIndex OBJECT-TYPE
+ SYNTAX InterfaceIndexOrZero
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "A PDU position in the chain."
+::= { acsPowerMgmtPhasesTableEntry 2 }
+
+acsPowerMgmtPhasesTablePhaseIndex OBJECT-TYPE
+ SYNTAX InterfaceIndexOrZero
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "phase index in the PDU."
+::= { acsPowerMgmtPhasesTableEntry 3 }
+
+acsPowerMgmtPhasesTablePhaseName OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "phase name in the PDU."
+::= { acsPowerMgmtPhasesTableEntry 4 }
+
+acsPowerMgmtPhasesTablePduId OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "PDU identification."
+::= { acsPowerMgmtPhasesTableEntry 5 }
+
+acsPowerMgmtPhasesTablePortName OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Name of serial port when the PDU is connected."
+::= { acsPowerMgmtPhasesTableEntry 6 }
+
+acsPowerMgmtPhasesTableCurrentValue OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Actual value of current sensor in this phase.( A x 10 )"
+::= { acsPowerMgmtPhasesTableEntry 7 }
+
+acsPowerMgmtPhasesTableCurrentMax OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Max detected value of current sensor in this phase.( A x 10 )"
+::= { acsPowerMgmtPhasesTableEntry 8 }
+
+acsPowerMgmtPhasesTableCurrentMin OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Min detected value of current sensor in this phase.( A x 10 )"
+::= { acsPowerMgmtPhasesTableEntry 9 }
+
+acsPowerMgmtPhasesTableCurrentAvg OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Average value for current sensor in this phase.( A x 10 )"
+::= { acsPowerMgmtPhasesTableEntry 10 }
+
+acsPowerMgmtPhasesTableCurrentReset OBJECT-TYPE
+ SYNTAX INTEGER {
+ no-action (1),
+ reset (2)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION "Reset max, min and avg values of current."
+::= { acsPowerMgmtPhasesTableEntry 11 }
+
+acsPowerMgmtPhasesTableVoltageType OBJECT-TYPE
+ SYNTAX INTEGER {
+ none-sensor (0),
+ estimated (1),
+ read (2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION "Type of voltage values."
+::= { acsPowerMgmtPhasesTableEntry 12 }
+
+acsPowerMgmtPhasesTableVoltageValue OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Actual value of voltage sensor in this phase.( V )"
+::= { acsPowerMgmtPhasesTableEntry 13 }
+
+acsPowerMgmtPhasesTableVoltageMax OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Max detected value of voltage sensor in this phase.( V )"
+::= { acsPowerMgmtPhasesTableEntry 14 }
+
+acsPowerMgmtPhasesTableVoltageMin OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Min detected value of voltage sensor in this phase.( V )"
+::= { acsPowerMgmtPhasesTableEntry 15 }
+
+acsPowerMgmtPhasesTableVoltageAvg OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Average value for voltage sensor in this phase.( V )"
+::= { acsPowerMgmtPhasesTableEntry 16 }
+
+acsPowerMgmtPhasesTableVoltageReset OBJECT-TYPE
+ SYNTAX INTEGER {
+ no-action (1),
+ reset (2)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION "Reset max, min and avg values of voltage."
+::= { acsPowerMgmtPhasesTableEntry 17 }
+
+acsPowerMgmtPhasesTablePowerType OBJECT-TYPE
+ SYNTAX INTEGER {
+ none-sensor (0),
+ estimated (1),
+ read (2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION "Type of power consumption values."
+::= { acsPowerMgmtPhasesTableEntry 18 }
+
+acsPowerMgmtPhasesTablePowerValue OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Actual value of power consumption in this phase.( W x 10 )"
+::= { acsPowerMgmtPhasesTableEntry 19 }
+
+acsPowerMgmtPhasesTablePowerMax OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Max detected value of power consumption in this phase.( W x 10 )"
+::= { acsPowerMgmtPhasesTableEntry 20 }
+
+acsPowerMgmtPhasesTablePowerMin OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Min detected value of power consumption in this phase.( W x 10 )"
+::= { acsPowerMgmtPhasesTableEntry 21 }
+
+acsPowerMgmtPhasesTablePowerAvg OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Average value for power consumption in this phase.( W x 10 )"
+::= { acsPowerMgmtPhasesTableEntry 22 }
+
+acsPowerMgmtPhasesTablePowerReset OBJECT-TYPE
+ SYNTAX INTEGER {
+ no-action (1),
+ reset (2)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION "Reset max, min and avg values of power consumption."
+::= { acsPowerMgmtPhasesTableEntry 23 }
+
+acsPowerMgmtPhasesTablePowerFactorType OBJECT-TYPE
+ SYNTAX INTEGER {
+ none-sensor (0),
+ estimated (1),
+ read (2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION "Type of power factor values."
+::= { acsPowerMgmtPhasesTableEntry 24 }
+
+acsPowerMgmtPhasesTablePowerFactorValue OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Actual value of power factor in this phase.( PF x 100 )"
+::= { acsPowerMgmtPhasesTableEntry 25 }
+
+acsPowerMgmtPhasesTablePowerFactorMax OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Max detected value of power factor in this phase.( PF x 100 )"
+::= { acsPowerMgmtPhasesTableEntry 26 }
+
+acsPowerMgmtPhasesTablePowerFactorMin OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Min detected value of power factor in this phase.( PF x 100 )"
+::= { acsPowerMgmtPhasesTableEntry 27 }
+
+acsPowerMgmtPhasesTablePowerFactorAvg OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Average value for power factor in this phase.( PF x 100 )"
+::= { acsPowerMgmtPhasesTableEntry 28 }
+
+acsPowerMgmtPhasesTablePowerFactorReset OBJECT-TYPE
+ SYNTAX INTEGER {
+ no-action (1),
+ reset (2)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION "Reset max, min and avg values of power factor."
+::= { acsPowerMgmtPhasesTableEntry 29 }
+
+acsPowerMgmtPhasesTableAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ blow-fuse (2),
+ hw-ocp (3),
+ high-critical (4),
+ high-warning (5),
+ low-warning (6),
+ low-critical (7)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION "Show the phase alarm status."
+::= { acsPowerMgmtPhasesTableEntry 30 }
+
+acsPowerMgmtBanksTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AcsPowerMgmtBanksTableEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "This table contains data monitoring of each detected bank."
+::= { acsPowerMgmt 9 }
+
+acsPowerMgmtBanksTableEntry OBJECT-TYPE
+ SYNTAX AcsPowerMgmtBanksTableEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "each entry has the data monitoring about bank."
+ INDEX { acsPowerMgmtBanksTablePortNumber, acsPowerMgmtBanksTablePduIndex, acsPowerMgmtBanksTableBankIndex }
+::= { acsPowerMgmtBanksTable 1 }
+
+AcsPowerMgmtBanksTableEntry ::= SEQUENCE {
+ acsPowerMgmtBanksTablePortNumber InterfaceIndex, -- number of serial port
+ acsPowerMgmtBanksTablePduIndex InterfaceIndexOrZero, -- number of PDU
+ acsPowerMgmtBanksTableBankIndex InterfaceIndexOrZero, -- bank index
+ acsPowerMgmtBanksTableBankName DisplayString, -- Bank Name
+ acsPowerMgmtBanksTablePduId DisplayString, -- PDU identification
+ acsPowerMgmtBanksTablePortName DisplayString, -- Serial Port Name
+ acsPowerMgmtBanksTableCurrentValue Integer32, -- actual value of bank current sensor
+ acsPowerMgmtBanksTableCurrentMax Integer32, -- max detected value of current sensor
+ acsPowerMgmtBanksTableCurrentMin Integer32, -- min detected value of current sensor
+ acsPowerMgmtBanksTableCurrentAvg Integer32, -- average value for current sensor
+ acsPowerMgmtBanksTableCurrentReset INTEGER, -- reset max, min and avg values
+ acsPowerMgmtBanksTableVoltageType INTEGER, -- type of bank voltage
+ acsPowerMgmtBanksTableVoltageValue Integer32, -- actual value of bank voltage
+ acsPowerMgmtBanksTableVoltageMax Integer32, -- max value of voltage sensor
+ acsPowerMgmtBanksTableVoltageMin Integer32, -- min value of voltage sensor
+ acsPowerMgmtBanksTableVoltageAvg Integer32, -- avg value of voltage sensor
+ acsPowerMgmtBanksTableVoltageReset INTEGER, -- reset max, min and avg values
+ acsPowerMgmtBanksTablePowerType INTEGER, -- type of bank power consumption
+ acsPowerMgmtBanksTablePowerValue Integer32, -- actual value of bank power consumption
+ acsPowerMgmtBanksTablePowerMax Integer32, -- max value
+ acsPowerMgmtBanksTablePowerMin Integer32, -- min value
+ acsPowerMgmtBanksTablePowerAvg Integer32, -- average value
+ acsPowerMgmtBanksTablePowerReset INTEGER, -- reset max, min and avg values
+ acsPowerMgmtBanksTablePowerFactorType INTEGER, -- type of bank power factor
+ acsPowerMgmtBanksTablePowerFactorValue Integer32, -- actual value of bank power factor
+ acsPowerMgmtBanksTablePowerFactorMax Integer32, -- max value for power factor
+ acsPowerMgmtBanksTablePowerFactorMin Integer32, -- min value for power factor
+ acsPowerMgmtBanksTablePowerFactorAvg Integer32, -- avg value for power factor
+ acsPowerMgmtBanksTablePowerFactorReset INTEGER, -- reset max, min and avg values
+ acsPowerMgmtBanksTableAlarm INTEGER -- status of bank alarm
+}
+
+acsPowerMgmtBanksTablePortNumber OBJECT-TYPE
+ SYNTAX InterfaceIndex
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Number of serial port when the PDU is connected."
+::= { acsPowerMgmtBanksTableEntry 1 }
+
+acsPowerMgmtBanksTablePduIndex OBJECT-TYPE
+ SYNTAX InterfaceIndexOrZero
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "A PDU position in the chain."
+::= { acsPowerMgmtBanksTableEntry 2 }
+
+acsPowerMgmtBanksTableBankIndex OBJECT-TYPE
+ SYNTAX InterfaceIndexOrZero
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Bank index in the PDU."
+::= { acsPowerMgmtBanksTableEntry 3 }
+
+acsPowerMgmtBanksTableBankName OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Bank name in the PDU."
+::= { acsPowerMgmtBanksTableEntry 4 }
+
+acsPowerMgmtBanksTablePduId OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "PDU identification."
+::= { acsPowerMgmtBanksTableEntry 5 }
+
+acsPowerMgmtBanksTablePortName OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Name of serial port when the PDU is connected."
+::= { acsPowerMgmtBanksTableEntry 6 }
+
+acsPowerMgmtBanksTableCurrentValue OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Actual value of current sensor in this bank.( A x 10 )"
+::= { acsPowerMgmtBanksTableEntry 7 }
+
+acsPowerMgmtBanksTableCurrentMax OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Max detected value of current sensor in this bank.( A x 10 )"
+::= { acsPowerMgmtBanksTableEntry 8 }
+
+acsPowerMgmtBanksTableCurrentMin OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Min detected value of current sensor in this bank.( A x 10 )"
+::= { acsPowerMgmtBanksTableEntry 9 }
+
+acsPowerMgmtBanksTableCurrentAvg OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Average value for current sensor in this bank.( A x 10 )"
+::= { acsPowerMgmtBanksTableEntry 10 }
+
+acsPowerMgmtBanksTableCurrentReset OBJECT-TYPE
+ SYNTAX INTEGER {
+ no-action (1),
+ reset (2)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION "Reset max, min and avg values of current."
+::= { acsPowerMgmtBanksTableEntry 11 }
+
+acsPowerMgmtBanksTableVoltageType OBJECT-TYPE
+ SYNTAX INTEGER {
+ none-sensor (0),
+ estimated (1),
+ read (2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION "Type of voltage values."
+::= { acsPowerMgmtBanksTableEntry 12 }
+
+acsPowerMgmtBanksTableVoltageValue OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Actual value of voltage sensor in this bank.( V )"
+::= { acsPowerMgmtBanksTableEntry 13 }
+
+acsPowerMgmtBanksTableVoltageMax OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Max detected value of voltage sensor in this bank.( V )"
+::= { acsPowerMgmtBanksTableEntry 14 }
+
+acsPowerMgmtBanksTableVoltageMin OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Min detected value of voltage sensor in this bank.( V )"
+::= { acsPowerMgmtBanksTableEntry 15 }
+
+acsPowerMgmtBanksTableVoltageAvg OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Average value for voltage sensor in this bank.( V )"
+::= { acsPowerMgmtBanksTableEntry 16 }
+
+acsPowerMgmtBanksTableVoltageReset OBJECT-TYPE
+ SYNTAX INTEGER {
+ no-action (1),
+ reset (2)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION "Reset max, min and avg values of voltage."
+::= { acsPowerMgmtBanksTableEntry 17 }
+
+acsPowerMgmtBanksTablePowerType OBJECT-TYPE
+ SYNTAX INTEGER {
+ none-sensor (0),
+ estimated (1),
+ read (2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION "Type of power consumption values."
+::= { acsPowerMgmtBanksTableEntry 18 }
+
+acsPowerMgmtBanksTablePowerValue OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Actual value of power consumption in this bank.( W x 10 )"
+::= { acsPowerMgmtBanksTableEntry 19 }
+
+acsPowerMgmtBanksTablePowerMax OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Max detected value of power consumption in this bank.( W x 10 )"
+::= { acsPowerMgmtBanksTableEntry 20 }
+
+acsPowerMgmtBanksTablePowerMin OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Min detected value of power consumption in this bank.( W x 10 )"
+::= { acsPowerMgmtBanksTableEntry 21 }
+
+acsPowerMgmtBanksTablePowerAvg OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Average value for power consumption in this bank.( W x 10 )"
+::= { acsPowerMgmtBanksTableEntry 22 }
+
+acsPowerMgmtBanksTablePowerReset OBJECT-TYPE
+ SYNTAX INTEGER {
+ no-action (1),
+ reset (2)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION "Reset max, min and avg values of power consumption."
+::= { acsPowerMgmtBanksTableEntry 23 }
+
+acsPowerMgmtBanksTablePowerFactorType OBJECT-TYPE
+ SYNTAX INTEGER {
+ none-sensor (0),
+ estimated (1),
+ read (2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION "Type of power factor values."
+::= { acsPowerMgmtBanksTableEntry 24 }
+
+acsPowerMgmtBanksTablePowerFactorValue OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Actual value of power factor in this bank.( PF x 100 )"
+::= { acsPowerMgmtBanksTableEntry 25 }
+
+acsPowerMgmtBanksTablePowerFactorMax OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Max detected value of power factor in this bank.( PF x 100 )"
+::= { acsPowerMgmtBanksTableEntry 26 }
+
+acsPowerMgmtBanksTablePowerFactorMin OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Min detected value of power factor in this bank.( PF x 100 )"
+::= { acsPowerMgmtBanksTableEntry 27 }
+
+acsPowerMgmtBanksTablePowerFactorAvg OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Average value for power factor in this bank.( PF x 100 )"
+::= { acsPowerMgmtBanksTableEntry 28 }
+
+acsPowerMgmtBanksTablePowerFactorReset OBJECT-TYPE
+ SYNTAX INTEGER {
+ no-action (1),
+ reset (2)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION "Reset max, min and avg values of power factor."
+::= { acsPowerMgmtBanksTableEntry 29 }
+
+acsPowerMgmtBanksTableAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ blow-fuse (2),
+ hw-ocp (3),
+ high-critical (4),
+ high-warning (5),
+ low-warning (6),
+ low-critical (7)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION "Show the bank alarm status."
+::= { acsPowerMgmtBanksTableEntry 30 }
+
+acsPowerMgmtEnvMonTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AcsPowerMgmtEnvMonTableEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "This table contains data monitoring of each detected environmental sensor."
+::= { acsPowerMgmt 10 }
+
+acsPowerMgmtEnvMonTableEntry OBJECT-TYPE
+ SYNTAX AcsPowerMgmtEnvMonTableEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "each entry has the data monitoring about environmental sensors."
+ INDEX { acsPowerMgmtEnvMonTablePortNumber, acsPowerMgmtEnvMonTablePduIndex, acsPowerMgmtEnvMonTableIndex }
+::= { acsPowerMgmtEnvMonTable 1 }
+
+AcsPowerMgmtEnvMonTableEntry ::= SEQUENCE {
+ acsPowerMgmtEnvMonTablePortNumber InterfaceIndex, -- number of serial port
+ acsPowerMgmtEnvMonTablePduIndex InterfaceIndexOrZero, -- number of PDU
+ acsPowerMgmtEnvMonTableIndex InterfaceIndexOrZero, -- index
+ acsPowerMgmtEnvMonTableName DisplayString, -- sensor name
+ acsPowerMgmtEnvMonTablePduId DisplayString, -- PDU identification
+ acsPowerMgmtEnvMonTablePortName DisplayString, -- Serial Port Name
+ acsPowerMgmtEnvMonTableType INTEGER, -- environmental sensor type
+ acsPowerMgmtEnvMonTableStatus INTEGER, -- state of digital sensor
+ acsPowerMgmtEnvMonTableValue Integer32, -- value
+ acsPowerMgmtEnvMonTableMaxValue Integer32 -- max value
+}
+
+acsPowerMgmtEnvMonTablePortNumber OBJECT-TYPE
+ SYNTAX InterfaceIndex
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Number of serial port when the PDU is connected."
+::= { acsPowerMgmtEnvMonTableEntry 1 }
+
+acsPowerMgmtEnvMonTablePduIndex OBJECT-TYPE
+ SYNTAX InterfaceIndexOrZero
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "A PDU position in the chain."
+::= { acsPowerMgmtEnvMonTableEntry 2 }
+
+acsPowerMgmtEnvMonTableIndex OBJECT-TYPE
+ SYNTAX InterfaceIndexOrZero
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "envmon sensor index."
+::= { acsPowerMgmtEnvMonTableEntry 3 }
+
+acsPowerMgmtEnvMonTableName OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "envmon sensor name."
+::= { acsPowerMgmtEnvMonTableEntry 4 }
+
+acsPowerMgmtEnvMonTablePduId OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "PDU identification."
+::= { acsPowerMgmtEnvMonTableEntry 5 }
+
+acsPowerMgmtEnvMonTablePortName OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Name of serial port when the PDU is connected."
+::= { acsPowerMgmtEnvMonTableEntry 6 }
+
+acsPowerMgmtEnvMonTableType OBJECT-TYPE
+ SYNTAX INTEGER {
+ temp-internal (1),
+ temperature (2),
+ humidity (3),
+ air-flow (4),
+ smoke (5),
+ dry-concact (6),
+ water-level (7),
+ motion (8),
+ unplugged (9),
+ unknown (10)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION "The type of environmental monitor."
+::= { acsPowerMgmtEnvMonTableEntry 7 }
+
+acsPowerMgmtEnvMonTableStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal(1),
+ triggered(2),
+ not-applicable(3)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION "Status of digital sensors:
+ Dry-Contact, Water level, Smoke sensor, Motion sensor."
+::= { acsPowerMgmtEnvMonTableEntry 8 }
+
+acsPowerMgmtEnvMonTableValue OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Detected value for envmon sensors. Temperature: C x 10. Humidity: %. Air flow: afu."
+::= { acsPowerMgmtEnvMonTableEntry 9 }
+
+acsPowerMgmtEnvMonTableMaxValue OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Max detected value for envmon sensors. Temperature: C x 10. Humidity: %. Air flow: afu."
+::= { acsPowerMgmtEnvMonTableEntry 10 }
+
+acsPowerMgmtOutElecMonTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AcsPowerMgmtOutElecMonTableEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "This table contains the information about data monitoring of outlets."
+::= { acsPowerMgmt 11 }
+
+acsPowerMgmtOutElecMonTableEntry OBJECT-TYPE
+ SYNTAX AcsPowerMgmtOutElecMonTableEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "each entry has the information about the outlet."
+ INDEX { acsPowerMgmtOutElecMonTablePortNumber,
+ acsPowerMgmtOutElecMonTablePduNumber,
+ acsPowerMgmtOutElecMonTableNumber }
+::= { acsPowerMgmtOutElecMonTable 1 }
+
+AcsPowerMgmtOutElecMonTableEntry ::= SEQUENCE {
+ acsPowerMgmtOutElecMonTablePortNumber InterfaceIndex, -- serial port #
+ acsPowerMgmtOutElecMonTablePduNumber InterfaceIndex,
+ acsPowerMgmtOutElecMonTableNumber InterfaceIndex, -- outlet number in PDU
+ acsPowerMgmtOutElecMonTableCurrentValue Integer32, -- actual value for current
+ acsPowerMgmtOutElecMonTableCurrentMax Integer32, -- max detected value for current
+ acsPowerMgmtOutElecMonTableCurrentMin Integer32, -- min detected value for current
+ acsPowerMgmtOutElecMonTableCurrentAvg Integer32, -- average value for current
+ acsPowerMgmtOutElecMonTableCurrentReset INTEGER, -- reset max, min and avg values of current
+ acsPowerMgmtOutElecMonTablePowerValue Integer32, -- actual value for power
+ acsPowerMgmtOutElecMonTablePowerMax Integer32, -- max detected value for power
+ acsPowerMgmtOutElecMonTablePowerMin Integer32, -- min detected value for power
+ acsPowerMgmtOutElecMonTablePowerAvg Integer32, -- average value for power
+ acsPowerMgmtOutElecMonTablePowerReset INTEGER, -- reset max, min and avg values of power
+ acsPowerMgmtOutElecMonTableVoltageValue Integer32, -- actual value for voltage
+ acsPowerMgmtOutElecMonTableVoltageMax Integer32, -- max detected value for voltage
+ acsPowerMgmtOutElecMonTableVoltageMin Integer32, -- min detected value for voltage
+ acsPowerMgmtOutElecMonTableVoltageAvg Integer32, -- average value for voltage
+ acsPowerMgmtOutElecMonTableVoltageReset INTEGER, -- reset max, min and avg values of voltage
+ acsPowerMgmtOutElecMonTablePowerFactorValue Integer32, -- actual value for power factor
+ acsPowerMgmtOutElecMonTablePowerFactorMax Integer32, -- max detected value for power factor
+ acsPowerMgmtOutElecMonTablePowerFactorMin Integer32, -- min detected value for power factor
+ acsPowerMgmtOutElecMonTablePowerFactorAvg Integer32, -- avg value for power factor
+ acsPowerMgmtOutElecMonTablePowerFactorReset INTEGER, -- reset max, min and avg values of power factor
+ acsPowerMgmtOutElecMonTableAlarm INTEGER -- outlet alarm status
+}
+
+acsPowerMgmtOutElecMonTablePortNumber OBJECT-TYPE
+ SYNTAX InterfaceIndex
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Serial Port number."
+::= { acsPowerMgmtOutElecMonTableEntry 1 }
+
+acsPowerMgmtOutElecMonTablePduNumber OBJECT-TYPE
+ SYNTAX InterfaceIndex
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Index."
+::= { acsPowerMgmtOutElecMonTableEntry 2 }
+
+acsPowerMgmtOutElecMonTableNumber OBJECT-TYPE
+ SYNTAX InterfaceIndex
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Number of the outlet in the PDU."
+::= { acsPowerMgmtOutElecMonTableEntry 3 }
+
+acsPowerMgmtOutElecMonTableCurrentValue OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Actual value of outlet current sensor.( A x 10 )"
+::= { acsPowerMgmtOutElecMonTableEntry 4 }
+
+acsPowerMgmtOutElecMonTableCurrentMax OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Max detected value of outlet current sensor.( A x 10 )"
+::= { acsPowerMgmtOutElecMonTableEntry 5 }
+
+acsPowerMgmtOutElecMonTableCurrentMin OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Min detected value of outlet current sensor.( A x 10 )"
+::= { acsPowerMgmtOutElecMonTableEntry 6 }
+
+acsPowerMgmtOutElecMonTableCurrentAvg OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Average value for outlet current sensor.( A x 10 )"
+::= { acsPowerMgmtOutElecMonTableEntry 7 }
+
+acsPowerMgmtOutElecMonTableCurrentReset OBJECT-TYPE
+ SYNTAX INTEGER {
+ noAction(1),
+ reset(2)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Reset max, min and avertage values of outlet current."
+::= { acsPowerMgmtOutElecMonTableEntry 8 }
+
+acsPowerMgmtOutElecMonTablePowerValue OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Actual value of outlet power comsumption sensor.( W x 10 )"
+::= { acsPowerMgmtOutElecMonTableEntry 9 }
+
+acsPowerMgmtOutElecMonTablePowerMax OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Max detected value of outlet power comsumption sensor.( W x 10 )"
+::= { acsPowerMgmtOutElecMonTableEntry 10 }
+
+acsPowerMgmtOutElecMonTablePowerMin OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Min detected value of outlet power comsumption sensor.( W x 10 )"
+::= { acsPowerMgmtOutElecMonTableEntry 11 }
+
+acsPowerMgmtOutElecMonTablePowerAvg OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Average value for outlet power comsumption sensor.( W x 10 )"
+::= { acsPowerMgmtOutElecMonTableEntry 12 }
+
+acsPowerMgmtOutElecMonTablePowerReset OBJECT-TYPE
+ SYNTAX INTEGER {
+ noAction(1),
+ reset(2)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Reset max, min and avertage values of outlet power comsumption."
+::= { acsPowerMgmtOutElecMonTableEntry 13 }
+
+acsPowerMgmtOutElecMonTableVoltageValue OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Actual value of outlet voltage sensor.( V )"
+::= { acsPowerMgmtOutElecMonTableEntry 14 }
+
+acsPowerMgmtOutElecMonTableVoltageMax OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Max detected value of outlet voltage sensor.( V )"
+::= { acsPowerMgmtOutElecMonTableEntry 15 }
+
+acsPowerMgmtOutElecMonTableVoltageMin OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Min detected value of outlet voltage sensor.( V )"
+::= { acsPowerMgmtOutElecMonTableEntry 16 }
+
+acsPowerMgmtOutElecMonTableVoltageAvg OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Average value for outlet voltage sensor.( V )"
+::= { acsPowerMgmtOutElecMonTableEntry 17 }
+
+acsPowerMgmtOutElecMonTableVoltageReset OBJECT-TYPE
+ SYNTAX INTEGER {
+ noAction(1),
+ reset(2)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Reset max, min and avertage values of outlet voltage."
+::= { acsPowerMgmtOutElecMonTableEntry 18 }
+
+acsPowerMgmtOutElecMonTablePowerFactorValue OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Actual value of outlet power-factor sensor.( PF x 100 )"
+::= { acsPowerMgmtOutElecMonTableEntry 19 }
+
+acsPowerMgmtOutElecMonTablePowerFactorMax OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Max detected value of outlet power-factor sensor.( PF x 100 )"
+::= { acsPowerMgmtOutElecMonTableEntry 20 }
+
+acsPowerMgmtOutElecMonTablePowerFactorMin OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Min detected value of outlet power-factor sensor.( PF x 100 )"
+::= { acsPowerMgmtOutElecMonTableEntry 21 }
+
+acsPowerMgmtOutElecMonTablePowerFactorAvg OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Average value for outlet power-factor sensor.( PF x 100 )"
+::= { acsPowerMgmtOutElecMonTableEntry 22 }
+
+acsPowerMgmtOutElecMonTablePowerFactorReset OBJECT-TYPE
+ SYNTAX INTEGER {
+ noAction(1),
+ reset(2)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Reset max, min and avertage values of outlet power-factor."
+::= { acsPowerMgmtOutElecMonTableEntry 23 }
+
+acsPowerMgmtOutElecMonTableAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ blow-fuse (2),
+ hw-ocp (3),
+ high-critical (4),
+ high-warning (5),
+ low-warning (6),
+ low-critical (7)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION "Show the outlet alarm status."
+::= { acsPowerMgmtOutElecMonTableEntry 24 }
+
+END