-rw-r--r--MIBS/avtech/ROOMALERT12E-MIB553
1 files changed, 553 insertions, 0 deletions
diff --git a/MIBS/avtech/ROOMALERT12E-MIB b/MIBS/avtech/ROOMALERT12E-MIB
new file mode 100644
index 0000000..30f2cdc
--- /dev/null
+++ b/MIBS/avtech/ROOMALERT12E-MIB
@@ -0,0 +1,553 @@
+--
+--defines ROOMALERT12E-MIB for SNMP agent extension of Room Alert 12E
+--Contents: Global Registration Module
+-- Room Alert OIDs - Enterprise 20916
+--Version: 3.3.0
+--Date: 28 May 2021
+--Developed By: AVTECH Software, Inc.
+
+--
+--Copyright (c) 2021 AVTECH Software, Inc.
+--
+
+ROOMALERT12E-MIB DEFINITIONS ::= BEGIN
+
+
+IMPORTS
+ enterprises, IpAddress, Counter, TimeTicks
+ FROM RFC1155-SMI
+ OBJECT-TYPE
+ FROM RFC-1212
+ TRAP-TYPE
+ FROM RFC-1215;
+
+
+avtech OBJECT IDENTIFIER ::= { enterprises 20916 }
+products OBJECT IDENTIFIER ::= { avtech 1 }
+roomalert12E OBJECT IDENTIFIER ::= { products 10 }
+sensors OBJECT IDENTIFIER ::= { roomalert12E 1 }
+lightTower OBJECT IDENTIFIER ::= { roomalert12E 2 }
+internal-sen OBJECT IDENTIFIER ::= { sensors 1 }
+digital-sen1 OBJECT IDENTIFIER ::= { sensors 2 }
+digital-sen2 OBJECT IDENTIFIER ::= { sensors 3 }
+digital-sen3 OBJECT IDENTIFIER ::= { sensors 4 }
+switch1 OBJECT IDENTIFIER ::= { sensors 5 }
+switch2 OBJECT IDENTIFIER ::= { sensors 6 }
+switch3 OBJECT IDENTIFIER ::= { sensors 7 }
+switch4 OBJECT IDENTIFIER ::= { sensors 8 }
+analog OBJECT IDENTIFIER ::= { sensors 9 }
+relay OBJECT IDENTIFIER ::= { sensors 10 }
+traps OBJECT IDENTIFIER ::= { roomalert12E 3 }
+
+-- Room Alert 12E MIB
+-- Parameters
+
+
+
+
+internal-sen-1 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "This value represents the current internal temperature in Celsius"
+::= { internal-sen 1 }
+
+internal-sen-2 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "This value represents the current internal temperature in Fahrenheit."
+::= { internal-sen 2 }
+
+internal-sen-3 OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The internal sensor's label"
+::= { internal-sen 3 }
+
+analog-1 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The current status of the Room Alert 12E analog input (0-5VDC)."
+::= { analog 1 }
+
+analog-2 OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The analog sensor's label."
+::= { analog 2 }
+
+analog-3 OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The current status of the Room Alert 12E analog input (user-defined scale)."
+::= { analog 3 }
+
+relay-1 OBJECT-TYPE
+ SYNTAX INTEGER(0..1)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "The current status of the Room Alert 12E relay output."
+::= { relay 1 }
+
+relay-2 OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The relay output's label."
+::= { relay 2 }
+
+digital-sen1-1 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "If this sensor is a Temperature, Temp/Humidity, Temp/Analog, or Temp/Active Power sensor, this value represents the current temperature in Celsius."
+::= { digital-sen1 1 }
+
+digital-sen1-2 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "If this sensor is a Temperature, Temp/Humidity, Temp/Analog, or Temp/Active Power sensor, this value represents the current temperature in Fahrenheit."
+::= { digital-sen1 2 }
+
+digital-sen1-3 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Temp/Analog sensor, this value represents the current Voltage reading. If this is a Temp/Active Power sensor, this value represents the current power state (1=Power Detected, 0=No Power Detected)."
+::= { digital-sen1 3 }
+
+digital-sen1-4 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Temp/Analog sensor, this value represents the current custom reading."
+::= { digital-sen1 4 }
+
+digital-sen1-5 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius."
+::= { digital-sen1 5 }
+
+digital-sen1-6 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current dew point in Celsius."
+::= { digital-sen1 6 }
+
+digital-sen1-7 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current dew point in Fahrenheit."
+::= { digital-sen1 7 }
+
+digital-sen1-8 OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The sensor's label"
+::= { digital-sen1 8 }
+
+digital-sen2-1 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "If this sensor is a Temperature, Temp/Humidity, Temp/Analog, or Temp/Active Power sensor, this value represents the current temperature in Celsius."
+::= { digital-sen2 1 }
+
+digital-sen2-2 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "If this sensor is a Temperature, Temp/Humidity, Temp/Analog, or Temp/Active Power sensor, this value represents the current temperature in Fahrenheit."
+::= { digital-sen2 2 }
+
+digital-sen2-3 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Temp/Analog sensor, this value represents the current Voltage reading. If this is a Temp/Active Power sensor, this value represents the current power state (1=Power Detected, 0=No Power Detected)."
+::= { digital-sen2 3 }
+
+digital-sen2-4 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Temp/Analog sensor, this value represents the current custom reading."
+::= { digital-sen2 4 }
+
+digital-sen2-5 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius."
+::= { digital-sen2 5 }
+
+digital-sen2-6 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current dew point in Celsius."
+::= { digital-sen2 6 }
+
+digital-sen2-7 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current dew point in Fahrenheit."
+::= { digital-sen2 7 }
+
+digital-sen2-8 OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The sensor's label"
+::= { digital-sen2 8 }
+
+digital-sen3-1 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "If this sensor is a Temperature, Temp/Humidity, Temp/Analog, or Temp/Active Power sensor, this value represents the current temperature in Celsius."
+::= { digital-sen3 1 }
+
+digital-sen3-2 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "If this sensor is a Temperature, Temp/Humidity, Temp/Analog, or Temp/Active Power sensor, this value represents the current temperature in Fahrenheit."
+::= { digital-sen3 2 }
+
+digital-sen3-3 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Temp/Analog sensor, this value represents the current Voltage reading. If this is a Temp/Active Power sensor, this value represents the current power state (1=Power Detected, 0=No Power Detected)."
+::= { digital-sen3 3 }
+
+digital-sen3-4 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Temp/Analog sensor, this value represents the current custom reading."
+::= { digital-sen3 4 }
+
+digital-sen3-5 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius."
+::= { digital-sen3 5 }
+
+digital-sen3-6 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current dew point in Celsius."
+::= { digital-sen3 6 }
+
+digital-sen3-7 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current dew point in Fahrenheit."
+::= { digital-sen3 7 }
+
+digital-sen3-8 OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The sensor's label"
+::= { digital-sen3 8 }
+
+switch-sen1-1 OBJECT-TYPE
+ SYNTAX INTEGER(0..1)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The reading for switch sensor 1 (0 = OPEN, 1 = CLOSED)."
+::= { switch1 1 }
+
+switch-sen1-2 OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The label for switch sensor 1."
+::= { switch1 2 }
+
+switch-sen2 OBJECT-TYPE
+ SYNTAX INTEGER(0..1)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The reading for switch sensor 2 (0 = OPEN, 1 = CLOSED)."
+::= { switch2 1 }
+
+switch-sen2-2 OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The label for switch sensor 2."
+::= { switch2 2 }
+
+switch-sen3 OBJECT-TYPE
+ SYNTAX INTEGER(0..1)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The reading for switch sensor 3 (0 = OPEN, 1 = CLOSED)."
+::= { switch3 1 }
+
+switch-sen3-2 OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The label for switch sensor 3."
+::= { switch3 2 }
+
+switch-sen4 OBJECT-TYPE
+ SYNTAX INTEGER(0..1)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The reading for switch sensor 4 (0 = OPEN, 1 = CLOSED)."
+::= { switch4 1 }
+
+switch-sen4-2 OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The label for switch sensor 4."
+::= { switch4 2 }
+
+alarmmessage OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Last Alarm Message"
+::= { traps 1 }
+
+
+-- Light Tower
+
+lightTower-RE OBJECT-TYPE
+ SYNTAX INTEGER(0..1)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "The status of the red LED on the Light Tower."
+::= { lightTower 1 }
+
+lightTower-OR OBJECT-TYPE
+ SYNTAX INTEGER(0..1)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "The status of the orange LED on the Light Tower."
+::= { lightTower 2 }
+
+lightTower-GR OBJECT-TYPE
+ SYNTAX INTEGER(0..1)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "The status of the green LED on the Light Tower."
+::= { lightTower 3 }
+
+lightTower-WH OBJECT-TYPE
+ SYNTAX INTEGER(0..1)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "The status of the white LED on the Light Tower."
+::= { lightTower 4 }
+
+lightTower-BL OBJECT-TYPE
+ SYNTAX INTEGER(0..1)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "The status of the blue LED on the Light Tower."
+::= { lightTower 5 }
+
+lightTower-A1 OBJECT-TYPE
+ SYNTAX INTEGER(0..1)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "The status of the 1st audio alarm on the Light Tower."
+::= { lightTower 6 }
+
+lightTower-A2 OBJECT-TYPE
+ SYNTAX INTEGER(0..1)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "The status of the 2nd audio alarm on the Light Tower."
+::= { lightTower 7 }
+
+lightTower-RL OBJECT-TYPE
+ SYNTAX INTEGER(0..1)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "The status of the LTA's on-board relay output"
+::= { lightTower 8 }
+
+
+-- ROOMALERT12E TRAPS
+
+tempalarm1-12E TRAP-TYPE
+ ENTERPRISE roomalert12E
+ VARIABLES { alarmmessage }
+ DESCRIPTION "A tempalarm1 trap signifies that the current
+ temperature on external sensor 1 is outside the
+ defined high or low threshold."
+::= 1
+
+room-alert-12E-snmp-trap TRAP-TYPE
+ ENTERPRISE roomalert12E
+ VARIABLES { alarmmessage }
+ DESCRIPTION "A room-alert-12E-snmp-trap indicates that an alarm
+ condition has occurred on the sensor inidcated
+ by the alarmMessage variable."
+::= 2
+
+tempalarm2-12E TRAP-TYPE
+ ENTERPRISE roomalert12E
+ VARIABLES { alarmmessage }
+ DESCRIPTION "A tempalarm2 trap signifies that the current
+ temperature on external sensor 2 is outside the
+ defined high or low threshold."
+::= 3
+
+tempclear2-12E TRAP-TYPE
+ ENTERPRISE roomalert12E
+ VARIABLES { alarmmessage }
+ DESCRIPTION "A tempclear2 trap signifies that the current
+ temperature on external sensor 2 has returned to
+ a normal condition and is within the defined
+ high or low threshold."
+::= 4
+
+tempalarm3-12E TRAP-TYPE
+ ENTERPRISE roomalert12E
+ VARIABLES { alarmmessage }
+ DESCRIPTION "A tempalarm3 trap signifies that the current
+ temperature on external sensor 3 is outside the
+ defined high or low threshold."
+::= 5
+
+tempclear3-12E TRAP-TYPE
+ ENTERPRISE roomalert12E
+ VARIABLES { alarmmessage }
+ DESCRIPTION "A tempclear3 trap signifies that the current
+ temperature on external sensor 3 has returned to
+ a normal condition and is within the defined
+ high or low threshold."
+::= 6
+
+humidityalarm1-12E TRAP-TYPE
+ ENTERPRISE roomalert12E
+ VARIABLES { alarmmessage }
+ DESCRIPTION "A humidityalarm1 trap signifies that the current
+ humidity on external sensor 1 is outside the
+ defined high or low threshold."
+::= 7
+
+humidityclear1-12E TRAP-TYPE
+ ENTERPRISE roomalert12E
+ VARIABLES { alarmmessage }
+ DESCRIPTION "A humidityclear1 trap signifies that the current
+ humidity on external sensor 1 has returned to
+ a normal condition and is within the defined
+ high or low threshold."
+::= 8
+
+humidityalarm2-12E TRAP-TYPE
+ ENTERPRISE roomalert12E
+ VARIABLES { alarmmessage }
+ DESCRIPTION "A humidityalarm2 trap signifies that the current
+ humidity on external sensor 2 is outside the
+ defined high or low threshold."
+::= 9
+
+humidityclear2-12E TRAP-TYPE
+ ENTERPRISE roomalert12E
+ VARIABLES { alarmmessage }
+ DESCRIPTION "A humidityclear2 trap signifies that the current
+ humidity on external sensor 2 has returned to
+ a normal condition and is within the defined
+ high or low threshold."
+::= 10
+
+humidityalarm3-12E TRAP-TYPE
+ ENTERPRISE roomalert12E
+ VARIABLES { alarmmessage }
+ DESCRIPTION "A humidityalarm3 trap signifies that the current
+ humidity on external sensor 3 is outside the
+ defined high or low threshold."
+::= 11
+
+humidityclear3-12E TRAP-TYPE
+ ENTERPRISE roomalert12E
+ VARIABLES { alarmmessage }
+ DESCRIPTION "A humidityclear3 trap signifies that the current
+ humidity on external sensor 3 has returned to
+ a normal condition and is within the defined
+ high or low threshold."
+::= 12
+
+switchalarm1-12E TRAP-TYPE
+ ENTERPRISE roomalert12E
+ VARIABLES { alarmmessage }
+ DESCRIPTION "A switchalarm1 trap signifies that switch sensor 1
+ is in an alarm state."
+::= 13
+
+switchclear1-12E TRAP-TYPE
+ ENTERPRISE roomalert12E
+ VARIABLES { alarmmessage }
+ DESCRIPTION "A switchclear1 trap signifies that the switch sensor 1
+ has returned to a normal state."
+::= 14
+
+switchalarm2-12E TRAP-TYPE
+ ENTERPRISE roomalert12E
+ VARIABLES { alarmmessage }
+ DESCRIPTION "A switchalarm2 trap signifies that switch sensor 2
+ is in an alarm state."
+::= 15
+
+switchclear2-12E TRAP-TYPE
+ ENTERPRISE roomalert12E
+ VARIABLES { alarmmessage }
+ DESCRIPTION "A switchclear2 trap signifies that the switch sensor 2
+ has returned to a normal state."
+::= 16
+
+switchalarm3-12E TRAP-TYPE
+ ENTERPRISE roomalert12E
+ VARIABLES { alarmmessage }
+ DESCRIPTION "A switchalarm3 trap signifies that switch sensor 3
+ is in an alarm state."
+::= 17
+
+switchclear3-12E TRAP-TYPE
+ ENTERPRISE roomalert12E
+ VARIABLES { alarmmessage }
+ DESCRIPTION "A switchclear3 trap signifies that the switch sensor 3
+ has returned to a normal state."
+::= 18
+
+switchalarm4-12E TRAP-TYPE
+ ENTERPRISE roomalert12E
+ VARIABLES { alarmmessage }
+ DESCRIPTION "A switchalarm4 trap signifies that switch sensor 4
+ is in an alarm state."
+::= 19
+
+switchclear4-12E TRAP-TYPE
+ ENTERPRISE roomalert12E
+ VARIABLES { alarmmessage }
+ DESCRIPTION "A switchclear4 trap signifies that the switch sensor 4
+ has returned to a normal state."
+::= 20
+END \ No newline at end of file