diff options
| author | David Leutgeb <david.leutgeb@mannundmouse.com> | 2023-12-05 12:25:34 +0100 |
|---|---|---|
| committer | David Leutgeb <david.leutgeb@mannundmouse.com> | 2023-12-05 12:25:34 +0100 |
| commit | 98a672123c7872f6b9b75a9a2b6bb3aea504de6a (patch) | |
| tree | 9b13bd7f563c3198047bd359195327cf28b3caf0 /MIBS/dpstelecom/DPS-TEXT-RTU-MIB | |
| download | mibs-main.tar.gz mibs-main.zip | |
Diffstat (limited to 'MIBS/dpstelecom/DPS-TEXT-RTU-MIB')
| -rw-r--r-- | MIBS/dpstelecom/DPS-TEXT-RTU-MIB | 171 |
1 files changed, 171 insertions, 0 deletions
diff --git a/MIBS/dpstelecom/DPS-TEXT-RTU-MIB b/MIBS/dpstelecom/DPS-TEXT-RTU-MIB new file mode 100644 index 0000000..4ef113b --- /dev/null +++ b/MIBS/dpstelecom/DPS-TEXT-RTU-MIB @@ -0,0 +1,171 @@ +-- Title: DPS-TEXT-RTU.MIB
+-- Version: v1.0 for SNMPv2c
+--
+-- Copyright @ 2011 DPS Inc. All Rights Reserved
+--
+-- This MIB defines objects for the DPS TEXT RTU products.
+--
+-- DPS CBH 8/2011
+--
+
+DPS-TEXT-RTU-MIB DEFINITIONS ::= BEGIN
+
+IMPORTS
+ DisplayString
+ FROM SNMPv2-TC
+ OBJECT-TYPE
+ FROM SNMPv2-SMI
+ NOTIFICATION-TYPE
+ FROM SNMPv2-SMI
+ Integer32
+ FROM SNMPv2-SMI
+ dpsAlarmControl
+ FROM DPS-MIB-V38;
+
+dpsTEXTRTUv2 OBJECT IDENTIFIER ::= {dpsAlarmControl 5}
+
+dpsTEXTRTUv2Ident OBJECT IDENTIFIER ::= {dpsTEXTRTUv2 1}
+
+--Textual Conventions
+
+AnalogThresholds ::= TEXTUAL-CONVENTION
+ STATUS current
+ DESCRIPTION "Highest threshold level crossed, if MJ, MN is assumed. Will be blank if alarm is not from an analog sources"
+ SYNTAX INTEGER {
+ noAlarms (0),
+ minorUnder (1),
+ minorOver (2),
+ majorUnder (3),
+ majorOver (4),
+ notDetected (5)
+ }
+
+RTUCAction ::= TEXTUAL-CONVENTION
+ STATUS current
+ DESCRIPTION "Requested action. Latch, release, and momentary will affect relays. Sync(s) will resend traps for currently active alarms(TEXT RTU will ignore if invalid)."
+ SYNTAX INTEGER {
+ latch(1),
+ release(2),
+ momentary(3),
+ syncStanding(4),
+ syncAnalogs(5)
+ }
+
+--Device identifying objects
+
+dpsTEXTRTUv2DateTime OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION "The RTU system date and time."
+ ::= {dpsTEXTRTUv2Ident 1}
+
+dpsTEXTRTUv2DeviceType OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION "Device type of far end SMS device as received in SMS messages to SMS receiver. ie NG216_G3"
+ ::= {dpsTEXTRTUv2Ident 2}
+
+dpsTEXTRTUv2Phone OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION "The phone number of the far end or originating SMS RTU, only SMS RTUs will have/respond to this variable"
+ ::= {dpsTEXTRTUv2Ident 3}
+
+
+-- Alarm identifying objects
+
+dpsTEXTRTUv2AlarmGrid OBJECT IDENTIFIER ::= {dpsTEXTRTUv2 2}
+
+dpsTEXTRTUv2ADisplay OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION "TEXT RTU display number. See the usermanual for display mapping information"
+ ::= {dpsTEXTRTUv2AlarmGrid 1}
+
+dpsTEXTRTUv2APoint OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION "TEXT RTU point number. See the usermanual for point mapping information"
+ ::= {dpsTEXTRTUv2AlarmGrid 2}
+
+dpsTEXTRTUv2APntDesc OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION "A description of this point."
+ ::= {dpsTEXTRTUv2AlarmGrid 3}
+
+dpsTEXTRTUv2AState OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION "The current state of this point."
+ ::= {dpsTEXTRTUv2AlarmGrid 4}
+
+dpsTEXTRTUAnalogvalue OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION "The current value of the channel. Will be blank if alarm is not from an analog source"
+ ::= {dpsTEXTRTUv2AlarmGrid 5}
+
+dpsTEXTRTUAnalogthresholds OBJECT-TYPE
+ SYNTAX AnalogThresholds
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION "Highest threshold level crossed, if MJ, MN is assumed. Will be blank if alarm is not from an analog sources"
+ ::= {dpsTEXTRTUv2AlarmGrid 6}
+
+-- TEXT RTU Control Commands
+
+dpsTEXTRTUv2ControlGrid OBJECT IDENTIFIER ::= {dpsTEXTRTUv2 3}
+
+dpsTEXTRTUv2CDisplay OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION "RTU_port_address display number."
+ ::= {dpsTEXTRTUv2ControlGrid 1}
+
+dpsTEXTRTUv2CPoint OBJECT-TYPE
+ SYNTAX Integer32 (1..64)
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION "RTU_port_display point number (1-64)."
+ ::= {dpsTEXTRTUv2ControlGrid 2}
+
+dpsTEXTRTUv2CMOMTime OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION "Momentary latch time (in milliseconds). If value is blank, the default of 600ms will be used"
+ ::= {dpsTEXTRTUv2ControlGrid 3}
+
+dpsTEXTRTUv2CAction OBJECT-TYPE
+ SYNTAX RTUCAction
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION "Requested action. Latch, release, and momentary will affect relays. Sync(s) will resend traps for currently active alarms(TEXT RTU will ignore if invalid)."
+ ::= {dpsTEXTRTUv2ControlGrid 4}
+
+
+-- DPS SMS RTU traps. Traps generated from SMS receiver indicating event on far end SMS RTU
+
+dpsTEXTRTUv2AlarmSet NOTIFICATION-TYPE
+ OBJECTS { sysDescr, sysLocation, dpsTEXTRTUv2DateTime, dpsTEXTRTUv2DeviceType, dpsTEXTRTUv2Phone, dpsTEXTRTUv2ADisplay, dpsTEXTRTUv2APoint, dpsTEXTRTUv2APntDesc, dpsTEXTRTUv2AState, dpsTEXTRTUAnalogvalue }
+ STATUS current
+ DESCRIPTION "Generated when alarm is received from far end SMS device to SMS receiver."
+ ::= { dpsTEXTRTUv2 100 }
+
+dpsTEXTRTUv2AlarmClear NOTIFICATION-TYPE
+ OBJECTS { sysDescr, sysLocation, dpsTEXTRTUv2DateTime, dpsTEXTRTUv2DeviceType, dpsTEXTRTUv2Phone, dpsTEXTRTUv2ADisplay, dpsTEXTRTUv2APoint, dpsTEXTRTUv2APntDesc, dpsTEXTRTUv2AState, dpsTEXTRTUAnalogvalue }
+ STATUS current
+ DESCRIPTION "Generated when clear is received from far end SMS device to SMS receiver."
+ ::= { dpsTEXTRTUv2 200 }
+
+END
|