@@ -0,0 +1,1385 @@
+PDU-MIB DEFINITIONS ::= BEGIN
+
+IMPORTS
+ MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE FROM SNMPv2-SMI
+ enterprises, Integer32, IpAddress, Opaque FROM SNMPv2-SMI
+ MODULE-COMPLIANCE, OBJECT-GROUP, NOTIFICATION-GROUP FROM SNMPv2-CONF
+ TEXTUAL-CONVENTION, DisplayString, MacAddress FROM SNMPv2-TC;
+
+eaton MODULE-IDENTITY
+ LAST-UPDATED "200803140000Z" -- March 14, 2008
+ ORGANIZATION "Eaton Corporation"
+ CONTACT-INFO "
+ Author: Eaton Corporation
+ postal: Eaton Corporation
+ Eaton Center
+ 1111 Superior Avenue
+ Cleveland, OH 44114-2584
+ phone: +1 (216) 523-5000
+ "
+ DESCRIPTION "This mib describes the SNMP functions of the
+ Power Distribution Unit by Eaton Corporation."
+ REVISION "200803140000z"
+ DESCRIPTION "Modified MIB in effort to better support HP Openview
+ and other SNMP managers."
+
+ REVISION "200702140000Z"
+ DESCRIPTION "Updated version for remote access to pdu."
+ ::= { enterprises 534 }
+
+product OBJECT IDENTIFIER ::= { eaton 6 }
+pduagent OBJECT IDENTIFIER ::= { product 6 }
+pdu OBJECT IDENTIFIER ::= { pduagent 6 }
+
+traps OBJECT IDENTIFIER ::= { pdu 0 }
+board OBJECT IDENTIFIER ::= { pdu 1 }
+environmental OBJECT IDENTIFIER ::= { pdu 2 }
+conformance OBJECT IDENTIFIER ::= { pdu 9 }
+info OBJECT IDENTIFIER ::= { board 1 }
+outlets OBJECT IDENTIFIER ::= { board 2 }
+unit OBJECT IDENTIFIER ::= { board 3 }
+
+unitReadings OBJECT IDENTIFIER ::= { unit 1 }
+
+compliances OBJECT IDENTIFIER ::= { conformance 1 }
+groups OBJECT IDENTIFIER ::= { conformance 2 }
+
+-- Conformance Information
+
+compliance MODULE-COMPLIANCE
+ STATUS current
+ DESCRIPTION
+ "The requirements for conformance to the PDU-MIB."
+ MODULE -- this module
+
+ GROUP infoGroup
+ DESCRIPTION
+ "The info group."
+
+ GROUP outletsGroup
+ DESCRIPTION
+ "The outlets group."
+
+ GROUP unitSensorsGroup
+ DESCRIPTION
+ "The unit sensor readings association group."
+
+ GROUP externalTemperatureGroup
+ DESCRIPTION
+ "The external temperature sensor association group."
+
+ GROUP externalHumidityGroup
+ DESCRIPTION
+ "The external humidity sensor association group."
+
+ GROUP trapsGroup
+ DESCRIPTION
+ "The traps group."
+ ::= { compliances 1 }
+
+infoGroup OBJECT-GROUP
+ OBJECTS { firmwareVersion,
+ serialNumber,
+ ipAddress,
+ netmask,
+ gateway,
+ mac,
+ hardwareRev,
+ userName,
+ objectName,
+ objectInstance,
+ targetUser,
+ groupName,
+ imageVersion,
+ sensorDescr,
+ thresholdDescr,
+ thresholdSeverity,
+ thresholdEventType,
+ status,
+ slaveIpAddress }
+ STATUS current
+ DESCRIPTION
+ "A collection of objects providing basic information
+ about the pdu."
+ ::= { groups 1 }
+
+outletsGroup OBJECT-GROUP
+ OBJECTS { outletCount,
+ outletLabel,
+ outletOperationalState,
+ outletCurrent,
+ outletMaxCurrent,
+ outletVoltage,
+ outletActivePower,
+ outletApparentPower,
+ outletPowerFactor,
+ outletCurrentUpperWarning,
+ outletCurrentUpperCritical }
+ STATUS current
+ DESCRIPTION
+ "A collection of objects providing basic information
+ about the outlets, including sensor readings."
+ ::= { groups 2 }
+
+unitSensorsGroup OBJECT-GROUP
+ OBJECTS { unitCurrent,
+ unitVoltage,
+ unitActivePower,
+ unitApparentPower,
+ unitCpuTemp,
+ unitCircuitBreak0State,
+ unitCircuitBreak1State,
+ unitCircuitBreak2State,
+ unitCircuitBreak0Current,
+ unitCircuitBreak1Current,
+ unitCircuitBreak2Current,
+ unitVoltageLowerWarning,
+ unitVoltageUpperWarning,
+ unitVoltageLowerCritical,
+ unitVoltageUpperCritical,
+ unitCurrentUpperWarning,
+ unitCurrentUpperCritical,
+ unitTempLowerWarning,
+ unitTempUpperWarning,
+ unitTempLowerCritical,
+ unitTempUpperCritical }
+ STATUS current
+ DESCRIPTION
+ "A collection of objects providing unit level sensor readings."
+ ::= { groups 4 }
+
+externalTemperatureGroup OBJECT-GROUP
+ OBJECTS { tempSensorCount,
+ tempSensorLabel,
+ temperature,
+ tempLowerWarning,
+ tempUpperWarning,
+ tempLowerCritical,
+ tempUpperCritical,
+ tempLowerWarningReset,
+ tempUpperWarningReset,
+ tempLowerCriticalReset,
+ tempUpperCriticalReset }
+ STATUS current
+ DESCRIPTION
+ "A collection of objects providing external temperature sensor readings and threshold settings."
+ ::= { groups 6 }
+
+externalHumidityGroup OBJECT-GROUP
+ OBJECTS { humiditySensorCount,
+ humiditySensorLabel,
+ humidity,
+ humidityLowerWarning,
+ humidityUpperWarning,
+ humidityLowerCritical,
+ humidityUpperCritical,
+ humidityLowerWarningReset,
+ humidityUpperWarningReset,
+ humidityLowerCriticalReset,
+ humidityUpperCriticalReset }
+ STATUS current
+ DESCRIPTION
+ "A collection of objects providing external humidity sensor readings and threshold settings."
+ ::= { groups 7 }
+
+trapsGroup NOTIFICATION-GROUP
+ NOTIFICATIONS { rebootStarted,
+ rebootCompleted,
+ userLogin,
+ userLogout,
+ userAuthenticationFailure,
+ userSessionTimeout,
+ userAdded,
+ userModified,
+ userDeleted,
+ groupAdded,
+ groupModified,
+ groupDeleted,
+ deviceUpdateStarted,
+ userBlocked,
+ powerControl,
+ userPasswordChanged,
+ passwordSettingsChanged,
+ firmwareFileDiscarded,
+ firmwareValidationFailed,
+ securityViolation,
+ logFileCleared,
+ thresholdAlarm,
+ outletGroupingConnectivityLost }
+ STATUS current
+ DESCRIPTION
+ "A collection of traps."
+ ::= { groups 9 }
+
+
+-- Textual Conventions
+
+MilliAmps ::= TEXTUAL-CONVENTION
+ STATUS current
+ DESCRIPTION
+ "Data type for reporting sensor readings and thresholds
+ associated with current sensors. If the underlying hardware
+ sensor indicates 1 amp, then the SNMP agent will report
+ a value of 1000 milliamps. The value is scaled in this
+ manner as a way to deal with floating point types
+ that SNMP does not currently support."
+ SYNTAX Unsigned32
+
+MilliVolts ::= TEXTUAL-CONVENTION
+ STATUS current
+ DESCRIPTION
+ "Data type for reporting sensor readings and thresholds
+ associated with voltage sensors. If the underlying hardware
+ sensor indicates 1 volts, then the SNMP agent will report
+ a value of 1000 millivolts. The value is scaled in this
+ manner as a way to deal with floating point types
+ that SNMP does not currently support."
+ SYNTAX Unsigned32
+
+Watts ::= TEXTUAL-CONVENTION
+ STATUS current
+ DESCRIPTION
+ "Data type for reporting sensor readings and thresholds
+ associated with active power sensors. If the underlying hardware
+ sensor indicates 1 watt, then the SNMP agent will report
+ a value of 1 watt. No scaling is performed for this type."
+ SYNTAX Unsigned32
+
+VoltAmps ::= TEXTUAL-CONVENTION
+ STATUS current
+ DESCRIPTION
+ "Data type for reporting sensor readings and thresholds
+ associated with apparent power sensors. If the underlying hardware
+ sensor indicates 1 volt-amp, then the SNMP agent will report
+ a value of 1 volt-amp. No scaling is performed for this type."
+ SYNTAX Unsigned32
+
+DegreesCelsius ::= TEXTUAL-CONVENTION
+ STATUS current
+ DESCRIPTION
+ "Data type for reporting sensor readings and thresholds
+ associated with temperature sensors. If the underlying hardware
+ sensor indicates 1 degree Celsius, then the SNMP agent will report
+ a value of 1 degree Celsius. No scaling is performed for this type."
+ SYNTAX Unsigned32
+
+Hertz ::= TEXTUAL-CONVENTION
+ STATUS current
+ DESCRIPTION
+ "Data type for reporting sensor readings and thresholds
+ associated with frequency sensors. If the underlying hardware
+ sensor indicates 1 Hertz, then the SNMP agent will report
+ a value of 1 Hertz. No scaling is performed for this type."
+ SYNTAX Unsigned32
+
+RelativeHumidity ::= TEXTUAL-CONVENTION
+ STATUS current
+ DESCRIPTION
+ "Data type for reporting sensor readings and thresholds
+ associated with humidity sensors. Relative humidity is
+ expressed as percentage and is defined as the ratio of the
+ partial pressure of water vapor in a gaseous mixture of
+ air and water vapor to the saturated vapor pressure of water
+ at a given temperature."
+ SYNTAX Unsigned32 (0..100)
+
+PowerFactorPercentage ::= TEXTUAL-CONVENTION
+ STATUS current
+ DESCRIPTION
+ "Data type for reporting sensor readings and thresholds
+ associated with power factor sensors. The power factor of
+ an AC power system is defined as the ratio of the real
+ or active power to the apparent power and is a number
+ between 0 and 1. A PowerFactorPercentage value is calculated
+ by taking this ratio and multiplying by 100. The power factor
+ is used to indicate how efficiently a particular load is
+ utilizing energy."
+ SYNTAX Unsigned32 (0..100)
+
+SensorTypeEnumeration ::= TEXTUAL-CONVENTION
+ STATUS current
+ DESCRIPTION
+ "The types a sensor can be."
+ SYNTAX INTEGER { outletCurrent(0),
+ outletMaxCurrent(1),
+ outletVoltage(2),
+ outletActivePower(3),
+ outletApparentPower(4),
+ outletMaxActivePower(5),
+ outletAverageActivePower(6),
+ outletPowerFactor(7),
+ powerBranchVoltage(200),
+ powerBranchFrequency(201),
+ powerBranchTemperature(202),
+ powerBranchCurrent(203),
+ environmentalTemp1(300),
+ environmentalTemp2(301),
+ environmentalTemp3(302),
+ environmentalTemp4(303),
+ environmentalTemp5(304),
+ environmentalTemp6(305),
+ environmentalTemp7(306),
+ environmentalTemp8(307),
+ environmentalHumidity1(400),
+ environmentalHumidity2(401),
+ environmentalHumidity3(402),
+ environmentalHumidity4(403),
+ environmentalHumidity5(404),
+ environmentalHumidity6(405),
+ environmentalHumidity7(406),
+ environmentalHumidity8(407),
+ unitRmsCurrent(500),
+ unitMaxRmsCurrent(501),
+ unitVoltage(502),
+ unitCpuTemp(503),
+ unitActivePower(504),
+ unitApparentPower(505),
+ unitCircuitBreak0State(550),
+ unitCircuitBreak1State(551),
+ unitCircuitBreak2State(552),
+ unitCircuitBreak0Current(600),
+ unitCircuitBreak1Current(601),
+ unitCircuitBreak2Current(602) }
+
+SensorStateEnumeration ::= TEXTUAL-CONVENTION
+ STATUS current
+ DESCRIPTION
+ "The states a sensor can be in."
+ SYNTAX INTEGER { unavailable(-1),
+ ok(0),
+ belowLowerWarning(1),
+ aboveUpperWarning(2),
+ belowLowerCritical(3),
+ aboveUpperCritical(4) }
+
+
+-- the info group
+
+firmwareVersion OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The current firmware version"
+ ::= { info 1 }
+
+serialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The serial number."
+ ::= { info 2 }
+
+ipAddress OBJECT-TYPE
+ SYNTAX IpAddress
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The current IP address. A value of 0.0.0.0 indicates an error
+ or an unset option."
+ ::= { info 3 }
+
+netmask OBJECT-TYPE
+ SYNTAX IpAddress
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The current Netmask. A value of 0.0.0.0 indicates an error
+ or an unset option."
+ ::= { info 4 }
+
+gateway OBJECT-TYPE
+ SYNTAX IpAddress
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The current Gateway. A value of 0.0.0.0 indicates an error
+ or an unset option."
+ ::= { info 5 }
+
+mac OBJECT-TYPE
+ SYNTAX MacAddress
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The current MAC address."
+ ::= { info 6 }
+
+hardwareRev OBJECT-TYPE
+ SYNTAX Integer32(0..255)
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The hardware revision number."
+ ::= { info 7 }
+
+userName OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS accessible-for-notify
+ STATUS current
+ DESCRIPTION
+ "The login of a user."
+ ::= { info 10 }
+
+objectName OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS accessible-for-notify
+ STATUS current
+ DESCRIPTION
+ "The model type of the device"
+ ::= { info 12 }
+
+objectInstance OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS accessible-for-notify
+ STATUS current
+ DESCRIPTION
+ "The device name"
+ ::= { info 13}
+
+targetUser OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS accessible-for-notify
+ STATUS current
+ DESCRIPTION
+ "The user record being operated on"
+ ::= { info 14}
+
+groupName OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS accessible-for-notify
+ STATUS current
+ DESCRIPTION
+ "The group record being operated on"
+ ::= { info 15 }
+
+imageVersion OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS accessible-for-notify
+ STATUS current
+ DESCRIPTION
+ "The version of the Upgrade image"
+ ::= { info 18 }
+
+sensorDescr OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS accessible-for-notify
+ STATUS current
+ DESCRIPTION
+ "Sensor description indicating which sensor experienced a threshold exceeded
+ event. When applicable the description will indicate the sensor number."
+ ::= { info 19 }
+
+thresholdDescr OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS accessible-for-notify
+ STATUS current
+ DESCRIPTION
+ "Threshold description indicating which configured threshold has been triggered (or cleared)."
+ ::= { info 20 }
+
+thresholdSeverity OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS accessible-for-notify
+ STATUS current
+ DESCRIPTION
+ "String (Warning, Critical, etc...) indicating the severity of the threshold which has been triggered (or cleared)."
+ ::= { info 21 }
+
+thresholdEventType OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS accessible-for-notify
+ STATUS current
+ DESCRIPTION
+ "String (triggered, cleared) indicating if the threshold event indicates that a configured threshold
+ has been triggered or cleared."
+ ::= { info 22 }
+
+status OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS accessible-for-notify
+ STATUS current
+ DESCRIPTION
+ "The success status of an operation"
+ ::= { info 23 }
+
+slaveIpAddress OBJECT-TYPE
+ SYNTAX IpAddress
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "In a shepherding configuration, this is the IP address of slave PDU. A value of 0.0.0.0 indicates an error
+ or an unset option."
+ ::= { info 24}
+
+-- the outlets group
+
+-- Implementation for managing the outlets
+
+outletCount OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of outlets (regardless of
+ their current state) present on this pdu."
+ ::= { outlets 1 }
+
+
+-- the outlets table
+
+-- The outlets table contains information on the pdu's outlets.
+-- It further provides functions for managing them.
+
+outletTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF OutletEntryStruct
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A list of outlet entries. The number of
+ entries is given by the value of outletCount."
+ ::= { outlets 2 }
+
+outletEntry OBJECT-TYPE
+ SYNTAX OutletEntryStruct
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An outlet entry containing objects at the
+ for a particular outlet."
+ INDEX { outletIndex }
+ ::= { outletTable 1 }
+
+OutletEntryStruct ::= SEQUENCE { outletIndex Integer32,
+ outletLabel DisplayString,
+ outletOperationalState INTEGER,
+ outletCurrent MilliAmps,
+ outletMaxCurrent MilliAmps,
+ outletVoltage MilliVolts,
+ outletActivePower Watts,
+ outletApparentPower VoltAmps,
+ outletPowerFactor PowerFactorPercentage,
+ outletCurrentUpperWarning MilliAmps,
+ outletCurrentUpperCritical MilliAmps }
+
+outletIndex OBJECT-TYPE
+ SYNTAX Integer32(0..255)
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "A unique value for each outlet. Its value
+ ranges between 1 and the value of outletCount."
+ ::= { outletEntry 1 }
+
+outletLabel OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "A textual string containing information
+ about the outlet."
+ ::= { outletEntry 2 }
+
+outletOperationalState OBJECT-TYPE
+ SYNTAX INTEGER { error(-1),
+ off(0),
+ on(1),
+ cycling(2) }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "A value for each outlet which describes the
+ operational state of the outlet. It is also
+ used to set the operational state of the outlet"
+ ::= { outletEntry 3 }
+
+outletCurrent OBJECT-TYPE
+ SYNTAX MilliAmps
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "A unique value for the current sensor
+ attached to the outlet. This value is
+ reported in milliamps (1/1000th of an amp)"
+ ::= { outletEntry 4 }
+
+outletMaxCurrent OBJECT-TYPE
+ SYNTAX MilliAmps
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "A unique value for the max. current sensor
+ attached to the outlet. This value is
+ reported in milliamps (1/1000th of an amp)"
+ ::= { outletEntry 5 }
+
+outletVoltage OBJECT-TYPE
+ SYNTAX MilliVolts
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "A unique value for the voltage sensor
+ attached to the outlet.This value is
+ reported in millivolts (1/1000th of a volt)"
+ ::= { outletEntry 6 }
+
+outletActivePower OBJECT-TYPE
+ SYNTAX Watts
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "A unique value for the active power sensor
+ attached to the outlet. This value is
+ reported in Watts."
+ ::= { outletEntry 7 }
+
+outletApparentPower OBJECT-TYPE
+ SYNTAX VoltAmps
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "A unique value for the apparent power sensor
+ attached to the outlet. This value is
+ reported in Volt-Amps"
+ ::= { outletEntry 8 }
+
+outletPowerFactor OBJECT-TYPE
+ SYNTAX PowerFactorPercentage
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "A unique value for the power factor
+ of the outlet. The reading represents a
+ percentage in the range of 0% to 100%."
+ ::= { outletEntry 9 }
+
+outletCurrentUpperWarning OBJECT-TYPE
+ SYNTAX MilliAmps
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The value of the upper warning (non-critical)
+ current threshold for the outlet. This value is
+ reported in milliamps (1/1000th of an amp)"
+ ::= { outletEntry 21 }
+
+outletCurrentUpperCritical OBJECT-TYPE
+ SYNTAX MilliAmps
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The value of the upper critical current
+ threshold for the outlet. This value is
+ reported in milliamps (1/1000th of an amp)"
+ ::= { outletEntry 23 }
+
+
+
+-- the unitReadings group
+
+-- The unitReadings group contains sensor reading values
+-- for the PDU unit as a whole
+
+unitCurrent OBJECT-TYPE
+ SYNTAX MilliAmps
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The value for the unit's current sensor in millamps."
+ ::= { unitReadings 1 }
+
+unitVoltage OBJECT-TYPE
+ SYNTAX MilliVolts
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The value for the unit's voltage sensor in millivolts."
+ ::= { unitReadings 2 }
+
+unitActivePower OBJECT-TYPE
+ SYNTAX Watts
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The value for the unit's voltage sensor in volt-amps."
+ ::= { unitReadings 3 }
+
+unitApparentPower OBJECT-TYPE
+ SYNTAX Watts
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The value for the unit's voltage sensor in volt-amps."
+ ::= { unitReadings 4 }
+
+unitCpuTemp OBJECT-TYPE
+ SYNTAX DegreesCelsius
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The value for the unit's CPU temperature sensor in degrees Celsius."
+ ::= { unitReadings 5 }
+
+
+unitCircuitBreak0State OBJECT-TYPE
+ SYNTAX INTEGER { unavailable(-1),
+ ok(0),
+ tripped(1) }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The value for the unit's circuit breaker state sensor 0."
+ ::= { unitReadings 20 }
+
+unitCircuitBreak1State OBJECT-TYPE
+ SYNTAX INTEGER { unavailable(-1),
+ ok(0),
+ tripped(1) }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The value for the unit's circuit breaker state sensor 1."
+ ::= { unitReadings 21 }
+
+unitCircuitBreak2State OBJECT-TYPE
+ SYNTAX INTEGER { unavailable(-1),
+ ok(0),
+ tripped(1) }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The value for the unit's circuit breaker state sensor 2."
+ ::= { unitReadings 22 }
+
+unitCircuitBreak0Current OBJECT-TYPE
+ SYNTAX MilliAmps
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The value for the unit's circuit breaker current sensor 0."
+ ::= { unitReadings 40 }
+
+unitCircuitBreak1Current OBJECT-TYPE
+ SYNTAX MilliAmps
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The value for the unit's circuit breaker current sensor 1."
+ ::= { unitReadings 41 }
+
+unitCircuitBreak2Current OBJECT-TYPE
+ SYNTAX MilliAmps
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The value for the unit's circuit breaker current sensor 2."
+ ::= { unitReadings 42 }
+
+unitVoltageLowerWarning OBJECT-TYPE
+ SYNTAX MilliVolts
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The value of the lower warning (non-critical) unit level voltage threshold."
+ ::= { unitReadings 60 }
+
+unitVoltageLowerCritical OBJECT-TYPE
+ SYNTAX MilliVolts
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The value of the lower critical unit level voltage threshold."
+ ::= { unitReadings 61 }
+
+unitVoltageUpperWarning OBJECT-TYPE
+ SYNTAX MilliVolts
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The value of the upper warning (non-critical) unit level voltage threshold."
+ ::= { unitReadings 62 }
+
+unitVoltageUpperCritical OBJECT-TYPE
+ SYNTAX MilliVolts
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The value of the upper critical unit level voltage threshold."
+ ::= { unitReadings 63 }
+
+unitCurrentUpperWarning OBJECT-TYPE
+ SYNTAX MilliAmps
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The value of the upper warning (non-critical) unit level current threshold."
+ ::= { unitReadings 70 }
+
+unitCurrentUpperCritical OBJECT-TYPE
+ SYNTAX MilliAmps
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The value of the upper critical unit level current threshold. NOTE: This
+ particular threshold is NOT settable "
+ ::= { unitReadings 71 }
+
+unitTempLowerWarning OBJECT-TYPE
+ SYNTAX DegreesCelsius
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The value of the lower warning (non-critical) unit level temperature threshold."
+ ::= { unitReadings 80 }
+
+unitTempLowerCritical OBJECT-TYPE
+ SYNTAX DegreesCelsius
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The value of the lower critical unit level temperature threshold."
+ ::= { unitReadings 81 }
+
+unitTempUpperWarning OBJECT-TYPE
+ SYNTAX DegreesCelsius
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The value of the upper warning (non-critical) unit level temperature threshold."
+ ::= { unitReadings 82 }
+
+unitTempUpperCritical OBJECT-TYPE
+ SYNTAX DegreesCelsius
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The value of the upper critical unit level temperature threshold."
+ ::= { unitReadings 83 }
+
+
+-- the externalTemperature group
+
+-- Implementation for managing external temperature sensors
+
+tempSensorCount OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of external temperature sensors (regardless of
+ their current state) present on this pdu."
+ ::= { environmental 1 }
+
+
+-- the temperature sensors table
+
+-- The tempSensorTable table contains information on the pdu's external temperature sensors.
+
+tempSensorTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF TempSensorEntryStruct
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A list of temperature sensor entries. The number of
+ entries is given by the value of tempSensorCount."
+ ::= { environmental 2 }
+
+tempSensorEntry OBJECT-TYPE
+ SYNTAX TempSensorEntryStruct
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry containing sensor reading and threshold
+ settings for a particular temperature sensor."
+ INDEX { tempSensorIndex }
+ ::= { tempSensorTable 1 }
+
+TempSensorEntryStruct ::= SEQUENCE { tempSensorIndex Integer32,
+ tempSensorLabel DisplayString,
+ temperature DegreesCelsius,
+ tempLowerWarning DegreesCelsius,
+ tempUpperWarning DegreesCelsius,
+ tempLowerCritical DegreesCelsius,
+ tempUpperCritical DegreesCelsius,
+ tempLowerWarningReset DegreesCelsius,
+ tempUpperWarningReset DegreesCelsius,
+ tempLowerCriticalReset DegreesCelsius,
+ tempUpperCriticalReset DegreesCelsius }
+
+tempSensorIndex OBJECT-TYPE
+ SYNTAX Integer32(0..255)
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "A unique value for each temperature sensor. Its value
+ ranges between 1 and tempSensorCount."
+ ::= { tempSensorEntry 1 }
+
+tempSensorLabel OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "A settable human-readable label for the external temperature
+ sensor. One possible use for this label is to convey sensor
+ location."
+ ::= { tempSensorEntry 2 }
+
+temperature OBJECT-TYPE
+ SYNTAX DegreesCelsius
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The value of the external temperature sensor reported
+ in degrees celsius."
+ ::= { tempSensorEntry 3 }
+
+tempLowerWarning OBJECT-TYPE
+ SYNTAX DegreesCelsius
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The value of the lower warning (non-critical) threshold."
+ ::= { tempSensorEntry 4 }
+
+tempUpperWarning OBJECT-TYPE
+ SYNTAX DegreesCelsius
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The value of the upper warning (non-critical) threshold."
+ ::= { tempSensorEntry 5 }
+
+tempLowerCritical OBJECT-TYPE
+ SYNTAX DegreesCelsius
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The value of the lower critical threshold."
+ ::= { tempSensorEntry 6 }
+
+tempUpperCritical OBJECT-TYPE
+ SYNTAX DegreesCelsius
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The value of the upper critical threshold."
+ ::= { tempSensorEntry 7 }
+
+tempLowerWarningReset OBJECT-TYPE
+ SYNTAX DegreesCelsius
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The value of the lower warning (non-critical) reset/hysteresis value."
+ ::= { tempSensorEntry 8 }
+
+tempUpperWarningReset OBJECT-TYPE
+ SYNTAX DegreesCelsius
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The value of the upper warning (non-critical) reset/hysteresis value."
+ ::= { tempSensorEntry 9 }
+
+tempLowerCriticalReset OBJECT-TYPE
+ SYNTAX DegreesCelsius
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The value of the lower critical reset/hysteresis value."
+ ::= { tempSensorEntry 10 }
+
+tempUpperCriticalReset OBJECT-TYPE
+ SYNTAX DegreesCelsius
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The value of the upper critical reset/hysteresis value."
+ ::= { tempSensorEntry 11 }
+
+-- the externalHumidity group
+
+-- Implementation for managing external humidity sensors
+
+humiditySensorCount OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of external humidity sensors (regardless of
+ their current state) present on this pdu."
+ ::= { environmental 3 }
+
+
+-- the humidity sensors table
+
+-- The humiditySensorTable table contains information on the pdu's external humidity sensors.
+
+humiditySensorTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF HumiditySensorEntryStruct
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A list of humidity sensor entries. The number of
+ entries is given by the value of humiditySensorCount."
+ ::= { environmental 4 }
+
+humiditySensorEntry OBJECT-TYPE
+ SYNTAX HumiditySensorEntryStruct
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry containing sensor reading and threshold
+ settings for a particular humidity sensor."
+ INDEX { humiditySensorIndex }
+ ::= { humiditySensorTable 1 }
+
+HumiditySensorEntryStruct ::= SEQUENCE { humiditySensorIndex Integer32,
+ humiditySensorLabel DisplayString,
+ humidity RelativeHumidity,
+ humidityLowerWarning RelativeHumidity,
+ humidityUpperWarning RelativeHumidity,
+ humidityLowerCritical RelativeHumidity,
+ humidityUpperCritical RelativeHumidity,
+ humidityLowerWarningReset RelativeHumidity,
+ humidityUpperWarningReset RelativeHumidity,
+ humidityLowerCriticalReset RelativeHumidity,
+ humidityUpperCriticalReset RelativeHumidity }
+
+humiditySensorIndex OBJECT-TYPE
+ SYNTAX Integer32(0..255)
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "A unique value for each humidity sensor. Its value
+ ranges between 1 and humiditySensorCount."
+ ::= { humiditySensorEntry 1 }
+
+humiditySensorLabel OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "A settable human-readable label for the external humidity
+ sensor. One possible use for this label is to convey sensor
+ location."
+ ::= { humiditySensorEntry 2 }
+
+humidity OBJECT-TYPE
+ SYNTAX RelativeHumidity
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The value of the external humidity sensor reported
+ as relative humidity (a percentage)."
+ ::= { humiditySensorEntry 3 }
+
+humidityLowerWarning OBJECT-TYPE
+ SYNTAX RelativeHumidity
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The value of the lower warning (non-critical) threshold."
+ ::= { humiditySensorEntry 4 }
+
+humidityUpperWarning OBJECT-TYPE
+ SYNTAX RelativeHumidity
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The value of the upper warning (non-critical) threshold."
+ ::= { humiditySensorEntry 5 }
+
+humidityLowerCritical OBJECT-TYPE
+ SYNTAX RelativeHumidity
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The value of the lower critical threshold."
+ ::= { humiditySensorEntry 6 }
+
+humidityUpperCritical OBJECT-TYPE
+ SYNTAX RelativeHumidity
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The value of the upper critical threshold."
+ ::= { humiditySensorEntry 7 }
+
+humidityLowerWarningReset OBJECT-TYPE
+ SYNTAX RelativeHumidity
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The value of the lower warning (non-critical) reset/hysteresis value."
+ ::= { humiditySensorEntry 8 }
+
+humidityUpperWarningReset OBJECT-TYPE
+ SYNTAX RelativeHumidity
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The value of the upper warning (non-critical) reset/hysteresis value."
+ ::= { humiditySensorEntry 9 }
+
+humidityLowerCriticalReset OBJECT-TYPE
+ SYNTAX RelativeHumidity
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The value of the lower critical reset/hysteresis value."
+ ::= { humiditySensorEntry 10 }
+
+humidityUpperCriticalReset OBJECT-TYPE
+ SYNTAX RelativeHumidity
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The value of the upper critical reset/hysteresis value."
+ ::= { humiditySensorEntry 11 }
+
+
+-- Start the traps
+
+rebootStarted NOTIFICATION-TYPE
+ OBJECTS { objectName,
+ objectInstance,
+ userName }
+ STATUS current
+ DESCRIPTION
+ "The reboot process has started"
+ ::= { traps 1 }
+
+rebootCompleted NOTIFICATION-TYPE
+ OBJECTS { objectName,
+ objectInstance }
+ STATUS current
+ DESCRIPTION
+ "The reboot process is complete"
+ ::= { traps 2 }
+
+userLogin NOTIFICATION-TYPE
+ OBJECTS { objectName,
+ objectInstance,
+ userName,
+ ipAddress }
+ STATUS current
+ DESCRIPTION
+ "A user logged in"
+ ::= { traps 3 }
+
+userLogout NOTIFICATION-TYPE
+ OBJECTS { objectName,
+ objectInstance,
+ userName,
+ ipAddress }
+ STATUS current
+ DESCRIPTION
+ "A user logged out"
+ ::= { traps 4 }
+
+userAuthenticationFailure NOTIFICATION-TYPE
+ OBJECTS { objectName,
+ objectInstance,
+ userName,
+ ipAddress }
+ STATUS current
+ DESCRIPTION
+ "A user authentication attempt failed"
+ ::= { traps 5 }
+
+userSessionTimeout NOTIFICATION-TYPE
+ OBJECTS { objectName,
+ objectInstance,
+ userName,
+ ipAddress }
+ STATUS current
+ DESCRIPTION
+ "A user timed out from the device"
+ ::= { traps 8 }
+
+userAdded NOTIFICATION-TYPE
+ OBJECTS { objectName,
+ objectInstance,
+ userName,
+ targetUser }
+ STATUS current
+ DESCRIPTION
+ "A user was added to the system"
+ ::= { traps 11 }
+
+userModified NOTIFICATION-TYPE
+ OBJECTS { objectName,
+ objectInstance,
+ userName,
+ targetUser }
+ STATUS current
+ DESCRIPTION
+ "A user account was modified"
+ ::= { traps 12 }
+
+userDeleted NOTIFICATION-TYPE
+ OBJECTS { objectName,
+ objectInstance,
+ userName,
+ targetUser }
+ STATUS current
+ DESCRIPTION
+ "A user was deleted from the system"
+ ::= { traps 13 }
+
+groupAdded NOTIFICATION-TYPE
+ OBJECTS { objectName,
+ objectInstance,
+ userName,
+ groupName }
+ STATUS current
+ DESCRIPTION
+ "A group was added to the system"
+ ::= { traps 14 }
+
+groupModified NOTIFICATION-TYPE
+ OBJECTS { objectName,
+ objectInstance,
+ userName,
+ groupName }
+ STATUS current
+ DESCRIPTION
+ "A group was modified"
+ ::= { traps 15 }
+
+
+groupDeleted NOTIFICATION-TYPE
+ OBJECTS { objectName,
+ objectInstance,
+ userName,
+ groupName }
+ STATUS current
+ DESCRIPTION
+ "A group was deleted from the system"
+ ::= { traps 16 }
+
+deviceUpdateStarted NOTIFICATION-TYPE
+ OBJECTS { objectName,
+ objectInstance,
+ userName,
+ ipAddress,
+ imageVersion }
+ STATUS current
+ DESCRIPTION
+ "The device update has started"
+ ::= { traps 20 }
+
+userBlocked NOTIFICATION-TYPE
+ OBJECTS { objectName,
+ objectInstance,
+ userName,
+ ipAddress }
+ STATUS current
+ DESCRIPTION
+ "A blocked user tried to log in"
+ ::= { traps 22 }
+
+powerControl NOTIFICATION-TYPE
+ OBJECTS { objectName,
+ objectInstance,
+ userName,
+ ipAddress,
+ outletLabel,
+ outletOperationalState }
+ STATUS current
+ DESCRIPTION
+ "An outlet has been switched"
+ ::= { traps 23 }
+
+userPasswordChanged NOTIFICATION-TYPE
+ OBJECTS { objectName,
+ objectInstance,
+ userName,
+ targetUser,
+ ipAddress }
+ STATUS current
+ DESCRIPTION
+ "A user password was changed"
+ ::= { traps 24 }
+
+passwordSettingsChanged NOTIFICATION-TYPE
+ OBJECTS { objectName,
+ objectInstance,
+ userName,
+ status }
+ STATUS current
+ DESCRIPTION
+ "Strong password settings changed "
+ ::= { traps 28 }
+
+-- Start new event to support RP products
+
+firmwareFileDiscarded NOTIFICATION-TYPE
+ OBJECTS { objectName,
+ objectInstance,
+ userName }
+ STATUS current
+ DESCRIPTION
+ "A firmware file discarded "
+ ::= { traps 36 }
+
+firmwareValidationFailed NOTIFICATION-TYPE
+ OBJECTS { objectName,
+ objectInstance,
+ userName }
+ STATUS current
+ DESCRIPTION
+ "A firmware validation failed "
+ ::= { traps 38 }
+
+securityViolation NOTIFICATION-TYPE
+ OBJECTS { objectName,
+ objectInstance,
+ userName,
+ ipAddress }
+ STATUS current
+ DESCRIPTION
+ "Security violation."
+ ::= { traps 39 }
+
+logFileCleared NOTIFICATION-TYPE
+ OBJECTS { objectName,
+ objectInstance,
+ userName }
+ STATUS current
+ DESCRIPTION
+ "The log file has been cleared."
+ ::= { traps 41 }
+
+--sensor threshold exceeded traps
+
+thresholdAlarm NOTIFICATION-TYPE
+ OBJECTS { objectName,
+ objectInstance,
+ ipAddress,
+ sensorDescr,
+ thresholdDescr,
+ thresholdSeverity,
+ thresholdEventType }
+ STATUS current
+ DESCRIPTION
+ "Configured sensor theshold event. The 'thresholdType' variable will indicate whether or not
+ the threshold triggered or cleared"
+ ::= { traps 45 }
+
+-- Shepherd Application traps
+outletGroupingConnectivityLost NOTIFICATION-TYPE
+ OBJECTS { objectName,
+ objectInstance,
+ ipAddress,
+ slaveIpAddress }
+ STATUS current
+ DESCRIPTION
+ "Master PDU lost contact with the slave PDU in an outlet grouping configuration."
+ ::= { traps 50 }
+
+
+END