+XUPS-MIB DEFINITIONS ::= BEGIN
+
+IMPORTS
+ TimeTicks, Gauge32, Counter32, Integer32
+ FROM SNMPv2-SMI
+ DisplayString
+ FROM SNMPv2-TC
+ MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE
+ FROM SNMPv2-SMI
+ MODULE-COMPLIANCE, OBJECT-GROUP, NOTIFICATION-GROUP
+ FROM SNMPv2-CONF
+ sysName
+ FROM RFC1213-MIB
+ eaton, xupsEnvironment
+ FROM EATON-OIDS
+ -- Need to import these EMP objects to support PowerMIB-style traps for EMP
+ xupsContactIndex, xupsContactType, xupsContactState, xupsContactDescr,
+ xupsEnvRemoteTemp, xupsEnvRemoteTempLowerLimit, xupsEnvRemoteTempUpperLimit,
+ xupsEnvRemoteHumidity, xupsEnvRemoteHumidityLowerLimit,
+ xupsEnvRemoteHumidityUpperLimit
+ FROM EATON-EMP-MIB;
+
+xupsMIB MODULE-IDENTITY
+ LAST-UPDATED "201909270000Z"
+ ORGANIZATION "Eaton Corporation"
+ CONTACT-INFO
+ "Eaton Power Quality Technical Support (PQTS) group
+ www.eaton.com/powerxpert
+ Technical Resource Center phone numbers
+ United States: 1.800.843.9433 or 919.870.3028
+ Canada: 1.800.461.9166 ext. 260
+ All other countries: Call your local service representative."
+ DESCRIPTION
+ "Defines Eaton's proprietary PowerMIB for UPS and
+ related device data.
+
+ Copyright (C) Exide Electronics 1992-98
+ Copyright (C) Powerware Corporation 1999-2004
+ Copyright (C) Eaton Corporation (2005-)."
+
+ REVISION "201909270000Z"
+ DESCRIPTION
+ "xupsOutputSource data can monitor the ESS mode."
+
+ REVISION "201909120000Z"
+ DESCRIPTION
+ "Provide new data that reflects some battery alarm : xupsBatteryFailure,
+ xupsBatteryNotPresent, xupsBatteryAged, xupsBatteryLowCapacity."
+
+ REVISION "201909100000Z"
+ DESCRIPTION
+ "Change the data xupsBatteryLastReplacedDate to read-only because the card
+ sets it automatically when the battery replacement is detected."
+
+ REVISION "201904120000Z"
+ DESCRIPTION
+ "Provide the status of the main AC Input in xupsInputStatus.
+ Provide the status of the AC Output in xupsOutputStatus and a new trap
+ and alarm 'load not protected' in xupsOutputNotProtected."
+
+ REVISION "201903050000Z"
+ DESCRIPTION
+ "Provide more UPS identification data as xupsIdentPartNumber and xupsIdentSerialNumber.
+ Provide a collection xupsAgent that contains identification data of the card :
+ xupsAgentManufacturer, xupsAgentModel, xupsAgentSoftwareVersion, xupsAgentPartNumber,
+ xupsAgentSerialNumber"
+
+ REVISION "201902190000Z"
+ DESCRIPTION
+ "To ensure consistency whith the measures done on the UPS, the data following are renamed :
+ xupsInputAverageCurrent to xupsInputTotalCurrent,
+ xupsOutputAverageCurrent to xupsOutputTotalCurrent,
+ xupsBypassAverageCurrent to xupsBypassTotalCurrent."
+
+ REVISION "201809120000Z"
+ DESCRIPTION
+ "Add new data xupsInputId, xupsInputName, xupsInputCurrentHighPrecision in the table xupsInputTable.
+ Add new sub collection xupsInputTotal with xupsInputAverageVoltage, xupsInputAverageCurrent,
+ xupsInputTotalWatts, xupsInputTotalVA, xupsInputAveragePowerFactor inside.
+ Add new data xupsOutputId, xupsOutputName, xupsOutputCurrentHighPrecision,
+ xupsOutputPercentLoad, xupsOutputVA in the table xupsOutputTable.
+ Add new sub collection xupsOutputTotal with xupsOutputAverageVoltage, xupsOutputAverageCurrent,
+ xupsOutputTotalWatts, xupsOutputTotalVA, xupsOutputAveragePowerFactor inside.
+ Add new data xupsBypassId, xupsBypassName, xupsBypassCurrentHighPrecision,
+ xupsBypassWatts in the table xupsBypassTable.
+ Add new sub collection xupsBypassTotal with xupsBypassTotalAverageVoltage, xupsBypassAverageCurrent,
+ xupsBypassTotalWatts, xupsBypassTotalVA, xupsBypassTotalAverageFactor inside."
+
+ REVISION "201804230000Z"
+ DESCRIPTION
+ "Add new data xupsTestTrap, xupstdTestTrap that will allow to initiate a
+ test trap sent out from the agent to the trap receivers."
+
+ REVISION "201211261513Z"
+ DESCRIPTION
+ "Add the identifier of measures xupsInputId, xupsOutputId and xupsBypassId,
+ respectively in the table xupsInputTable, xupsOutputTable and xupsBypassTable."
+
+ REVISION "201204030000Z"
+ DESCRIPTION
+ "Add new data xupsOutputHourlyPowerUsage, xupsOutputCumulativePowerUsage,
+ and xupsOutputCumulativePowerUsageTimer into the collection xupsOutput.
+ Add new data xupsRecepHourlyPowerUsage, xupsRecepCumulativePowerUsage,
+ and xupsRecepCumulativePowerUsageTimer into the collection xupsRecepTable."
+
+ REVISION "201102250000Z"
+ DESCRIPTION
+ "Add new data xupsSwitchable"
+
+ REVISION "200810020000Z"
+ DESCRIPTION
+ "Added new values of batteryDisconnected(6), batteryUnderTest(7),
+ and checkBattery(8) to xupsBatteryAbmStatus."
+
+ REVISION "200705030000Z"
+ DESCRIPTION
+ "Added new value of pxg(5) to xupsSendTrapType
+ for Power Xpert Gateway implementations."
+
+ REVISION "200703130000Z"
+ DESCRIPTION
+ "Initial SNMPv2-SMI-compliant Version of PowerMIB.
+ Incorporates all revisions of the original xups
+ MIB file through Version 3.13 21-May-04."
+
+ ::= { eaton 1 }
+
+-- xupsMIB { iso org(3) dod(6) internet(1) private(4)
+-- enterprises(1) eaton(534) xupsMIB(1) }
+
+
+xupsIdent OBJECT IDENTIFIER ::= { xupsMIB 1 }
+xupsBattery OBJECT IDENTIFIER ::= { xupsMIB 2 }
+xupsInput OBJECT IDENTIFIER ::= { xupsMIB 3 }
+xupsOutput OBJECT IDENTIFIER ::= { xupsMIB 4 }
+xupsBypass OBJECT IDENTIFIER ::= { xupsMIB 5 }
+-- xupsEnvironment OBJECT IDENTIFIER ::= { xupsMIB 6 } - defined in EATON-OIDS
+xupsAlarm OBJECT IDENTIFIER ::= { xupsMIB 7 }
+xupsTest OBJECT IDENTIFIER ::= { xupsMIB 8 }
+xupsControl OBJECT IDENTIFIER ::= { xupsMIB 9 }
+xupsConfig OBJECT IDENTIFIER ::= { xupsMIB 10 }
+xupsTrapControl OBJECT IDENTIFIER ::= { xupsMIB 11 }
+xupsRecep OBJECT IDENTIFIER ::= { xupsMIB 12 }
+xupsTopology OBJECT IDENTIFIER ::= { xupsMIB 13 }
+xupsAgent OBJECT IDENTIFIER ::= { xupsMIB 14 }
+
+xupsInputTotal OBJECT IDENTIFIER ::= { xupsInput 8 }
+xupsOutputTotal OBJECT IDENTIFIER ::= { xupsOutput 9 }
+xupsBypassTotal OBJECT IDENTIFIER ::= { xupsBypass 4 }
+
+--
+-- xupsIdent group:
+--
+xupsIdentManufacturer OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..31))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The UPS Manufacturer Name (e.g. Eaton Corporation)."
+ ::= { xupsIdent 1}
+
+xupsIdentModel OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..63))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The UPS Model (e.g. Powerware Plus Model 18)."
+ ::= {xupsIdent 2}
+
+xupsIdentSoftwareVersion OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..63))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The firmware revision level(s) of the UPS microcontroller(s)."
+ ::= {xupsIdent 3}
+
+xupsIdentOemCode OBJECT-TYPE
+ SYNTAX Integer32 (0..255)
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "A binary code indicating who the UPS was manufactured or labeled for.
+ 0 or 255 indicates Eaton itself."
+ ::= {xupsIdent 4}
+
+xupsIdentPartNumber OBJECT-TYPE
+ SYNTAX OCTET STRING (SIZE(1..31))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The catalog part number of the UPS device."
+ ::= { xupsIdent 5 }
+
+xupsIdentSerialNumber OBJECT-TYPE
+ SYNTAX OCTET STRING (SIZE(1..31))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The serial number of the UPS device."
+ ::= { xupsIdent 6 }
+
+
+--
+-- xupsBattery group:
+--
+xupsBatTimeRemaining OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "seconds"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Battery run time in seconds before UPS turns off due
+ to low battery."
+ ::= { xupsBattery 1}
+
+xupsBatVoltage OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "Volts DC"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Battery voltage as reported by the UPS meters."
+ ::= {xupsBattery 2}
+
+xupsBatCurrent OBJECT-TYPE
+ SYNTAX Integer32 (-2147483648..2147483647)
+ UNITS "Amps DC"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Battery Current as reported by the UPS metering.
+ Current is positive when discharging, negative
+ when recharging the battery."
+ ::= {xupsBattery 3}
+
+xupsBatCapacity OBJECT-TYPE
+ SYNTAX Integer32 (0..100)
+ UNITS "percent"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Battery percent charge."
+ ::= { xupsBattery 4}
+
+xupsBatteryAbmStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ batteryCharging(1),
+ batteryDischarging(2),
+ batteryFloating(3),
+ batteryResting(4),
+ unknown(5),
+ batteryDisconnected(6),
+ batteryUnderTest(7),
+ checkBattery(8)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Gives the status of the Advanced Battery Management and Battery state;
+ batteryFloating(3) status means that the charger is temporarily
+ charging the battery to its float voltage; batteryResting(4) is the
+ state when the battery is fully charged and none of the other actions
+ (charging/discharging/floating) is being done.
+ checkBattery(8) indicates that the Battery state is uncertain
+ following a poor battery test result."
+ ::= { xupsBattery 5}
+
+xupsBatteryLastReplacedDate OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..16))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The date when the Batteries in this UPS were last replaced. Free text format,
+ so the preferred local date format may be used (MM/DD/YYYY, DD-Mon-YYYY, etc)."
+ ::= { xupsBattery 6}
+
+xupsBatteryFailure OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes(1),
+ no(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Indicates if a battery fault detected or battery tests failed."
+ ::= { xupsBattery 7}
+
+xupsBatteryNotPresent OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes(1),
+ no(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Indicates if the UPS has no battery either internal or external."
+ ::= { xupsBattery 8}
+
+xupsBatteryAged OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes(1),
+ no(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Indicates if the battery is over aged."
+ ::= { xupsBattery 9}
+
+xupsBatteryLowCapacity OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes(1),
+ no(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Indicates if the battery capacity is below the threshold set in the UPS."
+ ::= { xupsBattery 10}
+
+
+--
+-- xupsInput group:
+--
+xupsInputFrequency OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "0.1 Hertz"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The utility line frequency in tenths of Hz."
+ ::= {xupsInput 1}
+
+xupsInputLineBads OBJECT-TYPE
+ SYNTAX Counter32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of times the Input was out of tolerance
+ in voltage or frequency."
+ ::= {xupsInput 2}
+
+xupsInputNumPhases OBJECT-TYPE
+ SYNTAX Integer32 (0..6)
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of input phases (normally 1 to 3)."
+ ::= {xupsInput 3}
+
+xupsInputTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF XupsInputEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A list of input table entries. The number of entries
+ is given by the value of xupsInputNumPhases."
+ ::= {xupsInput 4}
+
+xupsInputEntry OBJECT-TYPE
+ SYNTAX XupsInputEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "The input table entry containing the current,
+ voltage, etc. readings for one phase."
+ INDEX { xupsInputPhase }
+ ::= { xupsInputTable 1 }
+
+XupsInputEntry ::= SEQUENCE {
+ xupsInputPhase Integer32,
+ xupsInputVoltage Integer32,
+ xupsInputCurrent Integer32,
+ xupsInputWatts Integer32,
+ xupsInputId INTEGER,
+ xupsInputName OCTET STRING,
+ xupsInputCurrentHighPrecision Integer32
+ }
+
+xupsInputPhase OBJECT-TYPE
+ SYNTAX Integer32 (0..6)
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of the phase. Serves as index for input table."
+ ::= {xupsInputEntry 1}
+
+xupsInputVoltage OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "RMS Volts"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The measured input voltage from the UPS meters in volts."
+ ::= {xupsInputEntry 2}
+
+xupsInputCurrent OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "RMS Amps"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The measured input current from the UPS meters in amps."
+ ::= {xupsInputEntry 3}
+
+xupsInputWatts OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "Watts"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The measured input real power in watts."
+ ::= {xupsInputEntry 4}
+
+xupsInputId OBJECT-TYPE
+ SYNTAX INTEGER {
+ phase1toN (1),
+ phase2toN (2),
+ phase3toN (3),
+ phase1to2 (4),
+ phase2to3 (5),
+ phase3to1 (6)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "value indicates what measurement is being stored in this table row :
+ phase1 to neutral, phase2 to neutral, phase3 to neutral,
+ phase1 to phase2, phase2 to phase3, phase3 to phase1."
+ ::= { xupsInputEntry 5 }
+
+xupsInputName OBJECT-TYPE
+ SYNTAX OCTET STRING (SIZE(1..31))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "A descriptive name for the phase, example : L1/A for the phase 1."
+ ::= { xupsInputEntry 6 }
+
+xupsInputCurrentHighPrecision OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "RMS tenth of Amps"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The measured input current from the UPS meters in tenth of amps."
+ ::= {xupsInputEntry 7}
+
+xupsInputSource OBJECT-TYPE
+ SYNTAX INTEGER {
+ other(1),
+ none(2),
+ primaryUtility(3),
+ bypassFeed(4),
+ secondaryUtility(5),
+ generator(6),
+ flywheel(7),
+ fuelcell(8)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present external source of input power. The enumeration
+ 'none(2)' indicates that there is no external source of
+ power, for example, the UPS is On Battery (an internal source).
+ 'primaryUtility' indicates the normal case of utility input power.
+ The 'bypassFeed' can only be used when the Bypass source is known
+ to be a separate utility feed than the primaryUtility(3).
+ 'secondaryUtility' indicates that a secondary utility feed is supplying
+ power (on a dual AC input UPS).
+ 'generator' indicates that input power is provided by a generator.
+ Note that the alternate energy sources of 'flywheel' and 'fuelcell' are
+ not necessarily AC input sources."
+ ::= { xupsInput 5 }
+
+-- xupsDualInputStatus and xupsSecondaryInputWatch would only be present
+-- for UPSs with a secondary input source.
+
+xupsDualInputStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ bothSourcesBad(1),
+ primarySourceGood(2),
+ secondarySourceGood(3),
+ bothSourcesGood(4)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present status of the sources of input power in a dual source UPS.
+ The enumeration primarySourceGood(2) indicates that the primary source
+ of power is present and within 'normal' ranges for voltage and
+ frequency, but the secondary source is either not present or not in an
+ acceptable range.
+ 'secondarySourceGood' indicates that only the Secondary power feed is
+ available and within its limits.
+ The enumeration bothSourcesGood(4) indicates that both sources are present
+ and within their respective 'normal' ranges;
+ bothSourcesBad(1) indicates that neither source is present, or, if present,
+ is not within acceptable ranges.
+ This object will only be implemented for UPSs with two sources of input
+ power, e.g., redundant AC feeds or a separate Bypass or Generator source.
+ The secondary source will not be an AC power source in all cases."
+ ::= { xupsInput 6 }
+
+xupsSecondaryInputWatch OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(1),
+ enabled(2)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "This object enables(2) or disables(1) the alarms and traps related to the
+ availability and use of the secondary input of a dual-input UPS
+ (i.e., OnAlternatePowerSource and AltPowerNotAvailable).
+ To avoid nuisance alarms and traps, this object should be set to
+ disabled(1) when the UPS is not wired to a secondary source of power.
+ This object will only be implemented for UPSs with two sources of input
+ power, i.e., redundant AC feeds or a separate Bypass or Generator source."
+ ::= { xupsInput 7 }
+
+--
+-- xupsInputTotal group:
+--
+xupsInputAverageVoltage OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "RMS Volts"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The measured input voltage from the UPS meters in volts.
+ Related to the phase 1 if the UPS is single phase,
+ either it is average of all the simple phase voltage."
+ ::= {xupsInputTotal 1}
+
+xupsInputTotalCurrent OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "RMS tenth of Amps"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The measured input current from the UPS meters in tenth of amps.
+ Related to the phase 1 if the UPS is single phase,
+ either it is average of all the simple phase current."
+ ::= {xupsInputTotal 2}
+
+xupsInputTotalWatts OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "Watts"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The measured input active power in watts.
+ Sum of all the simple phase watts."
+ ::= {xupsInputTotal 3}
+
+xupsInputTotalVA OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "VA"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The measured input apparent power in VA.
+ Sum of all the simple phase VA."
+ ::= {xupsInputTotal 4}
+
+xupsInputAveragePowerFactor OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Indicates the total power factor of the input in hundredths.
+ 0.92 would be returned as 92."
+ ::= { xupsInputTotal 5 }
+
+xupsInputStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ inputBad(1),
+ inputGood(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present status of the primary AC input of the UPS.
+ The enumeration inputGood(2) indicates that the primary source
+ of power is present and within 'normal' ranges for voltage and
+ frequency.
+ inputBad(1) indicates that neither source is present, or, if present,
+ is not within acceptable ranges."
+ ::= { xupsInput 9 }
+
+--
+-- xupsOutput group:
+--
+xupsOutputLoad OBJECT-TYPE
+ SYNTAX Integer32 (0..200)
+ UNITS "percent"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The UPS output load in percent of rated capacity."
+ ::= {xupsOutput 1}
+
+xupsOutputFrequency OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "0.1 Hertz"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The measured UPS output frequency in tenths of Hz."
+ ::= {xupsOutput 2}
+
+xupsOutputNumPhases OBJECT-TYPE
+ SYNTAX Integer32 (0..6)
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of metered output phases."
+ ::= {xupsOutput 3}
+
+xupsOutputTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF XupsOutputEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A list of output table entries. The number of entries
+ is given by the value of xupsOutputNumPhases."
+ ::= {xupsOutput 4}
+
+xupsOutputEntry OBJECT-TYPE
+ SYNTAX XupsOutputEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "Output Table Entry containing voltage, current, etc."
+ INDEX { xupsOutputPhase }
+ ::= {xupsOutputTable 1}
+
+XupsOutputEntry ::= SEQUENCE {
+ xupsOutputPhase Integer32,
+ xupsOutputVoltage Integer32,
+ xupsOutputCurrent Integer32,
+ xupsOutputWatts Integer32,
+ xupsOutputId INTEGER,
+ xupsOutputName OCTET STRING,
+ xupsOutputCurrentHighPrecision Integer32,
+ xupsOutputPercentLoad Integer32,
+ xupsOutputVA Integer32
+ }
+
+xupsOutputPhase OBJECT-TYPE
+ SYNTAX Integer32 (0..6)
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of the phase. Serves as index for output table."
+ ::= {xupsOutputEntry 1}
+
+xupsOutputVoltage OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "RMS Volts"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The measured output voltage from the UPS metering in volts."
+ ::= {xupsOutputEntry 2}
+
+xupsOutputCurrent OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "RMS Amps"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The measured UPS output current in amps."
+ ::= {xupsOutputEntry 3}
+
+xupsOutputWatts OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "Watts"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The measured real output power in watts."
+ ::= {xupsOutputEntry 4}
+
+xupsOutputId OBJECT-TYPE
+ SYNTAX INTEGER {
+ phase1toN (1),
+ phase2toN (2),
+ phase3toN (3),
+ phase1to2 (4),
+ phase2to3 (5),
+ phase3to1 (6)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "value indicates what measurement is being stored in this table row :
+ phase1 to neutral, phase2 to neutral, phase3 to neutral,
+ phase1 to phase2, phase2 to phase3, phase3 to phase1. "
+ ::= { xupsOutputEntry 5 }
+
+xupsOutputName OBJECT-TYPE
+ SYNTAX OCTET STRING (SIZE(1..31))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "A descriptive name for the phase."
+ ::= { xupsOutputEntry 6 }
+
+xupsOutputCurrentHighPrecision OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "RMS tenth of Amps"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The measured output current from the UPS meters in tenth of amps."
+ ::= {xupsOutputEntry 7}
+
+xupsOutputPercentLoad OBJECT-TYPE
+ SYNTAX Integer32 (0..200)
+ UNITS "percent"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The percentage of the UPS power capacity presently
+ being used on this output line"
+ ::= { xupsOutputEntry 8 }
+
+xupsOutputVA OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "VA"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The measured apparent output power in VA."
+ ::= {xupsOutputEntry 9}
+
+xupsOutputSource OBJECT-TYPE
+ SYNTAX INTEGER {
+ other(1),
+ none(2),
+ normal(3),
+ bypass(4),
+ battery(5),
+ booster(6),
+ reducer(7),
+ parallelCapacity(8),
+ parallelRedundant(9),
+ highEfficiencyMode(10),
+ maintenanceBypass(11),
+ essMode(12)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present source of output power. The enumeration
+ none(2) indicates that there is no source of output
+ power (and therefore no output power), for example,
+ the system has opened the output breaker.
+ 'normal', 'bypass', and 'battery' indicate those common UPS statuses.
+ 'booster' and 'reducer' indicate boost or buck operation, for
+ line-interactive UPSs only.
+ 'parallelCapacity' and 'parallelRedundant' indicate a normal parallel
+ UPS system, in either Parallel for Capacity or Redundancy configuration.
+ 'highEfficiencyMode' is normal but enhanced by High Efficiency mode.
+ 'maintenanceBypass' indicates that the UPS is in Maintenance/Manual
+ Bypass mode.
+ 'essMode' is normal but enhanced by Energy Saver System.
+ 'other' covers any other, unusual conditions."
+ ::= { xupsOutput 5 }
+
+xupsOutputHourlyPowerUsage OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "Wh"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Units are Watt-hours.This is the energy consumed during the last hour."
+ ::= { xupsOutput 6 }
+
+xupsOutputCumulativePowerUsage OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "Wh"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Units are Watt-hours.This is the energy consumed since the last reset.
+ This object is writable so that it can be reset to 0.
+ When it is written to 0, the xupsOutputCumulativeWhTimer will be reset to 0 as well."
+ ::= { xupsOutput 7 }
+
+xupsOutputCumulativePowerUsageTimer OBJECT-TYPE
+ SYNTAX Counter32
+ UNITS "Seconds"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Time in seconds since the cumulative power usage was last reset."
+ ::= { xupsOutput 8 }
+
+--
+-- xupsOutputTotal group:
+--
+xupsOutputAverageVoltage OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "RMS Volts"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The measured output voltage from the UPS meters in volts.
+ Related to the phase 1 if the UPS is single phase,
+ either it is average of all the simple phase voltage."
+ ::= {xupsOutputTotal 1}
+
+xupsOutputTotalCurrent OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "RMS tenth of Amps"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The measured output current from the UPS meters in tenth of amps.
+ Related to the phase 1 if the UPS is single phase,
+ either it is average of all the simple phase current."
+ ::= {xupsOutputTotal 2}
+
+xupsOutputTotalWatts OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "Watts"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The measured output active power in watts.
+ Sum of all the simple phase watts."
+ ::= {xupsOutputTotal 3}
+
+xupsOutputTotalVA OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "VA"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The measured output apparent power in VA.
+ Sum of all the simple phase VA."
+ ::= {xupsOutputTotal 4}
+
+xupsOutputAveragePowerFactor OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Indicates the total power factor of the output in hundredths.
+ 0.92 would be returned as 92."
+ ::= { xupsOutputTotal 5 }
+
+xupsOutputStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ outputNotPowered(1),
+ outputNotProtected(2),
+ outputProtected(3)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present status of the AC output of the UPS.
+ The enumeration outputNotPowered(1) indicates that the output is not powered.
+ outputNotProtected(2) indicates that the output is powered but not protected,
+ due to following reasons : On bypass, battery fault, or UPS internal failure
+ that makes the ups will be inoperant in case of AC input failure.
+ outputProtected(3) indicates that the output is powered and protected."
+ ::= { xupsOutput 10 }
+
+
+--
+-- xupsBypass group:
+--
+xupsBypassFrequency OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "0.1 Hertz"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The bypass frequency in tenths of Hz."
+ ::= {xupsBypass 1}
+
+xupsBypassNumPhases OBJECT-TYPE
+ SYNTAX Integer32 (0..6)
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of lines in the UPS bypass table."
+ ::= {xupsBypass 2}
+
+xupsBypassTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF XupsBypassEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A list of bypass table entries. The number of entries
+ is given by the value of xupsBypassNumPhases."
+ ::= {xupsBypass 3}
+
+xupsBypassEntry OBJECT-TYPE
+ SYNTAX XupsBypassEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "Bypass Table Entry containing voltage for each phase."
+ INDEX { xupsBypassPhase }
+ ::= {xupsBypassTable 1}
+
+XupsBypassEntry ::= SEQUENCE {
+ xupsBypassPhase Integer32,
+ xupsBypassVoltage Integer32,
+ xupsBypassId INTEGER,
+ xupsBypassName OCTET STRING,
+ xupsBypassCurrentHighPrecision Integer32,
+ xupsBypassWatts Integer32
+ }
+
+xupsBypassPhase OBJECT-TYPE
+ SYNTAX Integer32 (0..6)
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The Bypass Phase, index for the table."
+ ::= {xupsBypassEntry 1}
+
+xupsBypassVoltage OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "RMS Volts"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The measured UPS bypass voltage in volts."
+ ::= {xupsBypassEntry 2}
+
+xupsBypassId OBJECT-TYPE
+ SYNTAX INTEGER {
+ phase1toN (1),
+ phase2toN (2),
+ phase3toN (3),
+ phase1to2 (4),
+ phase2to3 (5),
+ phase3to1 (6)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "value indicates what measurement is being stored in this table row :
+ phase1 to neutral, phase2 to neutral, phase3 to neutral,
+ phase1 to phase2, phase2 to phase3, phase3 to phase1. "
+ ::= { xupsBypassEntry 3 }
+
+xupsBypassName OBJECT-TYPE
+ SYNTAX OCTET STRING (SIZE(1..31))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "A descriptive name for the phase."
+ ::= { xupsBypassEntry 4 }
+
+xupsBypassCurrentHighPrecision OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "RMS tenth of Amps"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The measured bypass current from the UPS meters in tenth of amps."
+ ::= {xupsBypassEntry 5}
+
+xupsBypassWatts OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "Watts"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The measured real bypass power in watts."
+ ::= {xupsBypassEntry 6}
+
+--
+-- xupsBypassTotal group:
+--
+xupsBypassAverageVoltage OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "RMS Volts"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The measured bypass voltage from the UPS meters in volts.
+ Related to the phase 1 if the UPS is single phase,
+ either it is average of all the simple phase voltage."
+ ::= {xupsBypassTotal 1}
+
+xupsBypassTotalCurrent OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "RMS tenth of Amps"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The measured bypass current from the UPS meters in tenth of amps.
+ Related to the phase 1 if the UPS is single phase,
+ either it is average of all the simple phase current."
+ ::= {xupsBypassTotal 2}
+
+xupsBypassTotalWatts OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "Watts"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The measured bypass active power in watts.
+ Sum of all the simple phase watts."
+ ::= {xupsBypassTotal 3}
+
+xupsBypassTotalVA OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "VA"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The measured output apparent power in VA.
+ Sum of all the simple phase VA."
+ ::= {xupsBypassTotal 4}
+
+xupsBypassAveragePowerFactor OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Indicates the total power factor of the input in hundredths.
+ 0.92 would be returned as 92."
+ ::= { xupsBypassTotal 5 }
+
+
+--
+-- xupsEnvironment group:
+--
+
+xupsEnvAmbientTemp OBJECT-TYPE
+ SYNTAX Integer32 (-100..200)
+ UNITS "degrees Centigrade"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The reading of the ambient temperature in the vicinity of the
+ UPS or SNMP agent."
+ ::= { xupsEnvironment 1 }
+
+xupsEnvAmbientLowerLimit OBJECT-TYPE
+ SYNTAX Integer32 (-100..200)
+ UNITS "degrees Centigrade"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The Lower Limit of the ambient temperature; if xupsEnvAmbientTemp
+ falls below this value, the xupsAmbientTempBad alarm will occur."
+ ::= { xupsEnvironment 2 }
+
+xupsEnvAmbientUpperLimit OBJECT-TYPE
+ SYNTAX Integer32 (-100..200)
+ UNITS "degrees Centigrade"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The Upper Limit of the ambient temperature; if xupsEnvAmbientTemp
+ rises above this value, the xupsAmbientTempBad alarm will occur.
+ This value should be greater than xupsEnvAmbientLowerLimit."
+ ::= { xupsEnvironment 3 }
+
+xupsEnvAmbientHumidity OBJECT-TYPE
+ SYNTAX Integer32 (0..100)
+ UNITS "percent"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The reading of the ambient humidity in the vicinity of the
+ UPS or SNMP agent."
+ ::= { xupsEnvironment 4 }
+
+--
+-- Moved the EMP-based objects,
+-- from xupsEnvRemoteTemp to xupsEnvRemoteHumidityUpperLimit
+-- ( { xupsEnvironment 5 to 12 }, including xupsContactSenseTable,
+-- to separate file Eaton-EMP-MIB.txt
+--
+
+
+
+--
+-- xupsAlarm group:
+--
+xupsAlarms OBJECT-TYPE
+ SYNTAX Gauge32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The current number of alarm conditions."
+ ::= {xupsAlarm 1}
+
+xupsAlarmTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF XupsAlarmEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A list of alarm table entries. The number of entries
+ is given by the value of xupsAlarms.
+ Note that this table is sparsely (non-consecutively)
+ numbered and will be empty if there are no active alarms."
+ ::= {xupsAlarm 2}
+
+xupsAlarmEntry OBJECT-TYPE
+ SYNTAX XupsAlarmEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "Alarm Table Entry containing descriptive information
+ for one alarm entry."
+ INDEX { xupsAlarmID }
+ ::= {xupsAlarmTable 1}
+
+XupsAlarmEntry ::= SEQUENCE {
+ xupsAlarmID Integer32,
+ xupsAlarmDescr OBJECT IDENTIFIER,
+ xupsAlarmTime TimeTicks
+ }
+
+xupsAlarmID OBJECT-TYPE
+ SYNTAX Integer32 (1..2147483647)
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "A unique identifier for an alarm condition."
+ ::= {xupsAlarmEntry 1}
+
+xupsAlarmDescr OBJECT-TYPE
+ SYNTAX OBJECT IDENTIFIER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "A reference to an alarm description object. The object
+ referenced should not be accessible, but rather be used to
+ provide a unique description of the alarm condition."
+ ::= {xupsAlarmEntry 2}
+
+xupsAlarmTime OBJECT-TYPE
+ SYNTAX TimeTicks
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The value of the MIB-II variable sysUpTime when the alarm
+ condition occurred."
+ ::= {xupsAlarmEntry 3}
+
+--
+-- Well known alarm conditions.
+--
+xupsOnBattery OBJECT IDENTIFIER ::= {xupsAlarm 3}
+xupsLowBattery OBJECT IDENTIFIER ::= {xupsAlarm 4}
+xupsUtilityPowerRestored OBJECT IDENTIFIER ::= {xupsAlarm 5}
+xupsReturnFromLowBattery OBJECT IDENTIFIER ::= {xupsAlarm 6}
+xupsOutputOverload OBJECT IDENTIFIER ::= {xupsAlarm 7}
+xupsInternalFailure OBJECT IDENTIFIER ::= {xupsAlarm 8}
+xupsBatteryDischarged OBJECT IDENTIFIER ::= {xupsAlarm 9}
+xupsInverterFailure OBJECT IDENTIFIER ::= {xupsAlarm 10}
+xupsOnBypass OBJECT IDENTIFIER ::= {xupsAlarm 11}
+xupsBypassNotAvailable OBJECT IDENTIFIER ::= {xupsAlarm 12}
+xupsOutputOff OBJECT IDENTIFIER ::= {xupsAlarm 13}
+xupsInputFailure OBJECT IDENTIFIER ::= {xupsAlarm 14}
+xupsBuildingAlarm OBJECT IDENTIFIER ::= {xupsAlarm 15}
+xupsShutdownImminent OBJECT IDENTIFIER ::= {xupsAlarm 16}
+xupsOnInverter OBJECT IDENTIFIER ::= {xupsAlarm 17}
+
+
+xupsAlarmNumEvents OBJECT-TYPE
+ SYNTAX Gauge32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of entries in the UPS event history queue."
+ ::= { xupsAlarm 18 }
+
+xupsAlarmEventTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF XupsAlarmEventEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A table of the UPS internal event history queue."
+ ::= { xupsAlarm 19 }
+
+xupsAlarmEventEntry OBJECT-TYPE
+ SYNTAX XupsAlarmEventEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "One of the entries in the UPS event history queue."
+ INDEX { xupsAlarmEventID }
+ ::= { xupsAlarmEventTable 1 }
+
+-- The first 4 vars in the xAEEntry have been deprecated, since they resulted in
+-- a flood of difficult to interpret data. They have been replaced by the single
+-- entry, xupsAlarmEventMsg, which gives a human-readable description of the event.
+XupsAlarmEventEntry ::= SEQUENCE {
+ xupsAlarmEventID Integer32,
+ xupsAlarmEventDateAndTime DisplayString,
+ xupsAlarmEventKind INTEGER,
+ xupsAlarmEventDescr Integer32,
+ xupsAlarmEventMsg DisplayString
+ }
+
+xupsAlarmEventID OBJECT-TYPE
+ SYNTAX Integer32 (1..400)
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A unique number that reflects the order in which the event
+ occurred. The oldest event in the queue will be number 1.
+ Subsequent events will be numbered 2, 3, 4, etc."
+ ::= { xupsAlarmEventEntry 1 }
+
+xupsAlarmEventDateAndTime OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..22))
+ MAX-ACCESS read-only
+ STATUS deprecated
+ DESCRIPTION
+ "The time and date that an event occurred as recorded in the UPS
+ internal event queue. This string will reflect the time and
+ date as set in the UPS itself and will not be referenced to sysUpTime.
+ The format is MM/DD/YYYY:HH:MM:SS. Time is 24 hour standard."
+ ::= { xupsAlarmEventEntry 2 }
+
+xupsAlarmEventKind OBJECT-TYPE
+ SYNTAX INTEGER {
+ occurred (1),
+ cleared (2),
+ unknown (3)
+ }
+ MAX-ACCESS read-only
+ STATUS deprecated
+ DESCRIPTION
+ "Enumerated value that tells whether the event is an
+ occurrence of an alarm condition or a clearing of an
+ alarm condition."
+ ::= { xupsAlarmEventEntry 3 }
+
+xupsAlarmEventDescr OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ MAX-ACCESS read-only
+ STATUS deprecated
+ DESCRIPTION
+ "A description of the event stored in the UPS event queue.
+ This description will be a sixteen bit integer value
+ representing one of the defined alarms in the Powerware Binary
+ Computer Mode communication specification; for example,
+ a value of 0 represents the 'Inverter AC Over Voltage'
+ alarm (byte 1, bit 0 in the BCM Alarm Map)."
+ ::= { xupsAlarmEventEntry 4 }
+
+xupsAlarmEventMsg OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..80))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "A text string describing each entry in the Event Log. The format of this
+ text message is free (not fixed) for the operator to read; good contents
+ would be a time & date stamp, the event type, and a description of the event."
+ ::= { xupsAlarmEventEntry 5 }
+
+--
+-- More Well known alarm conditions.
+--
+xupsBreakerOpen OBJECT IDENTIFIER ::= {xupsAlarm 20}
+xupsAlarmEntryAdded OBJECT IDENTIFIER ::= {xupsAlarm 21}
+xupsAlarmEntryRemoved OBJECT IDENTIFIER ::= {xupsAlarm 22}
+
+-- Same as RFC 1628 Well Known Alarms:
+xupsAlarmBatteryBad OBJECT IDENTIFIER ::= {xupsAlarm 23}
+xupsOutputOffAsRequested OBJECT IDENTIFIER ::= {xupsAlarm 24}
+xupsDiagnosticTestFailed OBJECT IDENTIFIER ::= {xupsAlarm 25}
+xupsCommunicationsLost OBJECT IDENTIFIER ::= {xupsAlarm 26}
+xupsUpsShutdownPending OBJECT IDENTIFIER ::= {xupsAlarm 27}
+xupsAlarmTestInProgress OBJECT IDENTIFIER ::= {xupsAlarm 28}
+
+-- Alarm for the Ambient Temperature, when outside of lo/hi limits
+xupsAmbientTempBad OBJECT IDENTIFIER ::= {xupsAlarm 29}
+
+-- For Loss of Redundancy in parallel systems
+xupsLossOfRedundancy OBJECT IDENTIFIER ::= {xupsAlarm 30}
+
+-- More Same as RFC 1628 Well Known Alarms:
+xupsAlarmTempBad OBJECT IDENTIFIER ::= {xupsAlarm 31}
+xupsAlarmChargerFailed OBJECT IDENTIFIER ::= {xupsAlarm 32}
+xupsAlarmFanFailure OBJECT IDENTIFIER ::= {xupsAlarm 33}
+xupsAlarmFuseFailure OBJECT IDENTIFIER ::= {xupsAlarm 34}
+
+-- A Relay, Contactor, or Breaker has failed
+xupsPowerSwitchBad OBJECT IDENTIFIER ::= {xupsAlarm 35}
+
+-- One module in a parallel or composite system has failed
+xupsModuleFailure OBJECT IDENTIFIER ::= {xupsAlarm 36}
+
+-- Two Alarms for systems with an Alternate Power Source, such as
+-- Secondary utility feed (on a dual AC input UPS), generator,
+-- flywheel, or fuelcell. Enabled by xupsSecondaryInputWatch.
+xupsOnAlternatePowerSource OBJECT IDENTIFIER ::= {xupsAlarm 37}
+xupsAltPowerNotAvailable OBJECT IDENTIFIER ::= {xupsAlarm 38}
+
+-- Some Notice condition exists which is not covered by the other WKA
+-- (like an xupsInternalFailure, but at a lower level of urgency)
+xupsNoticeCondition OBJECT IDENTIFIER ::= {xupsAlarm 39}
+
+-- Alarms for the Remote Temperature & Humidity, when outside of lo/hi limits
+xupsRemoteTempBad OBJECT IDENTIFIER ::= {xupsAlarm 40}
+xupsRemoteHumidityBad OBJECT IDENTIFIER ::= {xupsAlarm 41}
+
+-- Last of the RFC1628 Well Known Alarms:
+xupsAlarmOutputBad OBJECT IDENTIFIER ::= {xupsAlarm 42}
+xupsAlarmAwaitingPower OBJECT IDENTIFIER ::= {xupsAlarm 43}
+
+-- Alarm for this important UPS mode
+xupsOnMaintenanceBypass OBJECT IDENTIFIER ::= {xupsAlarm 44}
+
+-- New alarms now managed by the Network-M2 card
+xupsOutputNotProtected OBJECT IDENTIFIER ::= {xupsAlarm 51}
+
+
+--
+-- xupsTest group:
+--
+
+xupsTestStart OBJECT-TYPE
+ SYNTAX INTEGER {
+ testBattery (1),
+ noTestStarted (2),
+ testSystem (3),
+ testSecondarySource (4),
+ flashLightsTest (5),
+ cancelTest (6)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Setting this object initiates the requested Test.
+ The test types which a UPS might support are 'testBattery',
+ 'testSystem' (a UPS General Systems test, however defined by the UPS),
+ 'testSecondarySource' (test if the Secondary power source is good on a
+ dual input UPS), and
+ 'flashLightsTest' (start a test which flashes the UPS lights, and if
+ available, sounds the horn to help locate the UPS).
+ If a UPS does not support the requested test, the set operation may
+ succeed but the xupsTestBatteryStatus will end up as notSupported.
+ When read, this object indicates the last test requested via this object,
+ if any; 'noTestStarted' could be the initial value.
+ Currently only the 'flashLightsTest' can be canceled with 'cancelTest'."
+ ::= {xupsTest 1}
+
+xupsTestBatteryStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ passed (2),
+ failed (3),
+ inProgress (4),
+ notSupported (5),
+ inhibited (6),
+ scheduled (7)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Reading this enumerated value gives an indication of the (last)
+ UPS Battery test status.
+ 'inhibited' means that the battery test could not be run.
+ 'scheduled' means that the battery test could not be run at the time
+ of request, but will be run at some later (UPS-determined) time."
+ ::= {xupsTest 2}
+
+xupsLastGeneralTest OBJECT-TYPE
+ SYNTAX INTEGER {
+ noTestStarted (2),
+ testSystem (3),
+ testSecondarySource (4),
+ flashLightsTest (5)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Indicates the last UPS test requested via xupsTestStart or by other
+ non-SNMP means, other than for the testBattery (1) case.
+ The results of the test indicated by this object are reported in
+ xupsLastGeneralTestResult."
+ ::= {xupsTest 3}
+
+xupsLastGeneralTestResult OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ passed (2),
+ failed (3),
+ inProgress (4),
+ notSupported (5),
+ inhibited (6),
+ scheduled (7)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Reading this enumerated value gives the result of the test indicated
+ in xupsLastGeneralTest."
+ ::= {xupsTest 4}
+
+xupsTestTrap OBJECT-TYPE
+ SYNTAX INTEGER { startTestTrap (1) }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Setting startTestTrap to 1 will initiate a test trap
+ to be sent out from the agent. All other set values are invalid."
+ ::= {xupsTest 5}
+
+
+--
+-- xupsControl group:
+--
+xupsControlOutputOffDelay OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "seconds"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Setting this value to other than zero will cause the UPS
+ output to turn off after the number of seconds.
+ Setting it to 0 will cause an attempt to abort a pending
+ shutdown."
+ ::= {xupsControl 1}
+
+xupsControlOutputOnDelay OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "seconds"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Setting this value to other than zero will cause the UPS
+ output to turn on after the number of seconds.
+ Setting it to 0 will cause an attempt to abort a pending
+ startup."
+ ::= {xupsControl 2}
+
+xupsControlOutputOffTrapDelay OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "seconds"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "When xupsControlOutputOffDelay reaches this value, a trap will
+ be sent."
+ ::= {xupsControl 3}
+
+xupsControlOutputOnTrapDelay OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "seconds"
+ MAX-ACCESS read-write
+ STATUS deprecated
+ DESCRIPTION
+ "When xupsControlOutputOnDelay reaches this value, a
+ xupsOutputOff trap will be sent."
+ ::= {xupsControl 4}
+
+xupsControlToBypassDelay OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "seconds"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Setting this value to other than zero will cause the UPS
+ output to go to Bypass after the number of seconds.
+ If the Bypass is unavailable, this may cause the UPS
+ to not supply power to the load.
+ Setting it to 0 will cause an attempt to abort a pending
+ shutdown."
+ ::= {xupsControl 5}
+
+xupsLoadShedSecsWithRestart OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "seconds"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Setting this value will cause the UPS output to turn off
+ after the set number of seconds, then restart (after a UPS-defined
+ 'down time') when the utility is again available.
+ Unlike xupsControlOutputOffDelay, which might or might not,
+ this object always maps to the XCP 0x8A Load Dump & Restart command,
+ so the desired shutdown and restart behavior is guaranteed to happen.
+ Once set, this command cannot be aborted.
+ This is the preferred Control object to use when performing
+ an On Battery OS Shutdown."
+ ::= {xupsControl 6}
+
+xupsSwitchable OBJECT-TYPE
+ SYNTAX INTEGER {
+ switchable (1),
+ notSwitchable (2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Parameter which indicates whether UPS commands received via any
+ communication path (aside from manual controls) are able (switchable)
+ or not able (notSwitchable) to control the UPS."
+ ::= { xupsControl 7 }
+
+--
+-- xupsConfig group:
+--
+xupsConfigOutputVoltage OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "RMS Volts"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The nominal UPS Output voltage per phase in volts."
+ ::= {xupsConfig 1}
+
+xupsConfigInputVoltage OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "RMS Volts"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The nominal UPS Input voltage per phase in volts."
+ ::= {xupsConfig 2}
+
+xupsConfigOutputWatts OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "Watts"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The nominal UPS available real power output in watts."
+ ::= {xupsConfig 3}
+
+xupsConfigOutputFreq OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "0.1 Hertz"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The nominal output frequency in tenths of Hz."
+ ::= {xupsConfig 4}
+
+xupsConfigDateAndTime OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..22))
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Date and time information for the UPS. Setting this variable
+ will initiate a set UPS date and time to this value. Reading
+ this variable will return the UPS time and date. This value
+ is not referenced to sysUpTime. It is simply the clock value
+ from the UPS real time clock.
+ Format is as follows: MM/DD/YYYY:HH:MM:SS."
+ ::= { xupsConfig 5 }
+
+xupsConfigLowOutputVoltageLimit OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "RMS Volts"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The Lower limit for acceptable Output Voltage, per the UPS
+ specifications."
+ ::= {xupsConfig 6}
+
+xupsConfigHighOutputVoltageLimit OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "RMS Volts"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The Upper limit for acceptable Output Voltage, per the UPS
+ specifications."
+ ::= {xupsConfig 7}
+
+xupsConfigInstallDate OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..16))
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The date when this UPS was installed. Free text format, so the
+ preferred local date format may be used (MM/DD/YYYY, DD-Mon-YYYY, etc)."
+ ::= {xupsConfig 8}
+
+
+
+--
+-- xupsTrapControl group:
+--
+xupsMaxTrapLevel OBJECT-TYPE
+ SYNTAX INTEGER {
+ none (1),
+ critical (2),
+ major (3),
+ minor (4),
+ allTraps (5)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The level of severity of traps which will be sent to the
+ requesting host; individual trap receivers will have
+ individual values for this variable. Values are:
+ (1) none: no traps will be sent to this host;
+ (2) critical: only traps for Critical alarm conditions will
+ be sent to this host;
+ (3) major: Critical and Major traps will be sent;
+ (4) minor: All levels of alarming traps will be sent: Critical,
+ Major, and Minor
+ (This level was added in PowerMIB v3.11)
+ (5) allTraps: all Traps will be sent to this host
+ (Critical, Major, Minor, Informational)."
+ ::= {xupsTrapControl 1}
+
+xupsSendTrapType OBJECT-TYPE
+ SYNTAX INTEGER {
+ stnd (1),
+ xups (2),
+ stndPlus (3),
+ xupsPlus (4),
+ pxg (5)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The type of traps which will be sent to the
+ requesting host; individual trap receivers will have
+ individual values for this variable. The additional
+ variables in types (3) and (4) are useful for determining
+ which UPS is the source on multi-port network adapters,
+ and for getting additional descriptive information.
+ Types (1) through (4) are all SNMP version 1 trap PDUs.
+ Values are:
+ (1) stnd: Traps as defined in the Standard UPS MIB (RFC1628)
+ and Generic (MIB II) traps as defined in RFC 1215.
+ (2) xups: xupsTrapDefined Traps as defined in the PowerMIB
+ and Generic (MIB II) traps as defined in RFC 1215.
+ (3 Deprecated) stndPlus: same as stnd plus variables from the interface
+ group and, where appropriate, xupsTrapMessage.
+ (4 Deprecated) xupsPlus: xupsTrapPortN Traps (same as xups plus
+ variables from the interface group) and,
+ for authFail, xupsTrapMessage.
+ (5 pxg: Traps as defined in the Power Xpert Gateway MIB
+ (PXG-MIB)."
+ ::= {xupsTrapControl 2}
+
+xupsTrapMessage OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..79))
+ MAX-ACCESS read-only -- actually not-accessible
+ STATUS current
+ DESCRIPTION
+ "A descriptive text message which may be sent with traps to
+ further explain the reason for the trap.
+ This object is not-accessible to MIB browsers, but had to be changed to
+ read-only to satisfy SMIv2 syntax checkers since it is included in traps."
+ ::= {xupsTrapControl 3}
+
+-- An Identifier for the PowerMIB traps
+-- Used below in the section where the traps are defined
+xupsTrapSource OBJECT IDENTIFIER ::= {xupsTrapControl 4}
+
+xupsHeartbeatMinsInterval OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "Minutes"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "How often to send the xupstdHeartbeat trap, in units of minutes.
+ A setting of 0 disables the Heartbeat function."
+ ::= {xupsTrapControl 5}
+
+
+
+--
+-- xupsRecep group:
+--
+-- (Note that the terms Receptacle, Outlet, and Load Group are used interchangeably
+-- here and all mean "one of a group of controllable, power-switched outputs")
+--
+xupsNumReceptacles OBJECT-TYPE
+ SYNTAX Integer32 (0..64)
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of independently controllable Receptacles, as described in the
+ xupsRecepTable."
+ ::= {xupsRecep 1}
+
+xupsRecepTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF XupsRecepEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A list of receptacle table entries. The number of entries
+ is given by the value of xupsNumReceptacles."
+ ::={xupsRecep 2}
+
+xupsRecepEntry OBJECT-TYPE
+ SYNTAX XupsRecepEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A receptacle table entry containing the status and
+ control values for one receptacle."
+ INDEX { xupsRecepIndex }
+ ::= { xupsRecepTable 1 }
+
+XupsRecepEntry ::= SEQUENCE {
+ xupsRecepIndex Integer32,
+ xupsRecepStatus INTEGER,
+ xupsRecepOffDelaySecs Integer32,
+ xupsRecepOnDelaySecs Integer32,
+ xupsRecepAutoOffDelay Integer32,
+ xupsRecepAutoOnDelay Integer32,
+ xupsRecepShedSecsWithRestart Integer32,
+ xupsRecepHourlyPowerUsage Integer32,
+ xupsRecepCumulativePowerUsage Integer32,
+ xupsRecepCumulativePowerUsageTimer Counter32
+ }
+
+xupsRecepIndex OBJECT-TYPE
+ SYNTAX Integer32 (1..64)
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of the Receptacle. Serves as index for Receptacle table."
+ ::= {xupsRecepEntry 1}
+
+
+xupsRecepStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ on(1), off(2), pendingOff(3), pendingOn(4), unknown(5),
+ reserved(6), failedClosed(7), failedOpen(8) }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The Recep Status 1=On/Close, 2=Off/Open, 3=On w/Pending Off,
+ 4=Off w/Pending ON, 5=Unknown, 6=Reserved for future,
+ 7=Failed in Closed position, 8=Failed in Open position."
+ ::={xupsRecepEntry 2}
+
+
+xupsRecepOffDelaySecs OBJECT-TYPE
+ SYNTAX Integer32 (-1..2147483647)
+ UNITS "seconds"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The Delay until the Receptacle is turned Off. Setting
+ this value to other than -1 will cause the UPS output to
+ turn off after the number of seconds (0 is immediately).
+ Setting it to -1 will cause an attempt to abort a pending shutdown.
+ When this object is set while the UPS is On Battery, it is not necessary
+ to set xupsRecepOnDelaySecs, since the outlet will turn back on
+ automatically when power is available again."
+ ::= {xupsRecepEntry 3}
+
+xupsRecepOnDelaySecs OBJECT-TYPE
+ SYNTAX Integer32 (-1..2147483647)
+ UNITS "seconds"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The Delay until the Receptacle is turned On. Setting
+ this value to other than -1 will cause the UPS output to
+ turn on after the number of seconds (0 is immediately).
+ Setting it to -1 will cause an attempt to abort a pending restart."
+ ::={xupsRecepEntry 4}
+
+
+xupsRecepAutoOffDelay OBJECT-TYPE
+ SYNTAX Integer32 (-1..32767)
+ UNITS "seconds"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The delay after going On Battery until the Receptacle is
+ automatically turned Off. A value of -1 means that this Output should
+ never be turned Off automatically, but must be turned Off only by command.
+ Values from 0 to 30 are valid, but probably innappropriate.
+ The AutoOffDelay can be used to prioritize loads in the event of a prolonged
+ power outage; less critical loads will turn off earlier to extend battery
+ time for the more critical loads. If the utility power is restored before the
+ AutoOff delay counts down to 0 on an outlet, that outlet will not turn Off."
+ ::= {xupsRecepEntry 5}
+
+xupsRecepAutoOnDelay OBJECT-TYPE
+ SYNTAX Integer32 (-1..32767)
+ UNITS "seconds"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Seconds delay after the Outlet is signaled to turn On before the Output is
+ Automatically turned ON. A value of -1 means that this Output should never
+ be turned On automatically, but only when specifically commanded to do so.
+ A value of 0 means that the Receptacle should come On immediately
+ at power-up or for an On command."
+ ::= {xupsRecepEntry 6}
+
+-- xupsRecepAutoOnDelay has three purposes:
+-- 1. To coordinate the automatic startup of various outlets, when the normal
+-- auto-sequencing of 1 second per outlet is not adequate. For example, they may
+-- be used to power up hard disk arrays before CPU units are started.
+-- 2. To force additional 'Down Time' during xupsRecepOffDelaySecs commands, for
+-- equipment to be reset, when the standard 'Down Time' is not long enough.
+-- 3. For the -1 value, to ensure that loads won't be powered until commanded,
+-- following power-up or a xupsRecepOffDelaySecs command.
+
+xupsRecepShedSecsWithRestart OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "seconds"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Setting this value will cause the UPS output to turn off
+ after the set number of seconds, then restart (after a UPS-defined
+ 'down time') when the utility is again available.
+ Unlike xupsRecepOffDelaySecs, which might or might not,
+ this object always maps to the XCP 0x8A Load Dump & Restart command,
+ so the desired shutdown and restart behavior is guaranteed to happen.
+ Once set, this command cannot be aborted."
+ ::= {xupsRecepEntry 7}
+
+xupsRecepHourlyPowerUsage OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "Wh"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Units are Watt-hours.This is the energy consumed during the last hour."
+ ::= { xupsRecepEntry 8 }
+
+xupsRecepCumulativePowerUsage OBJECT-TYPE
+ SYNTAX Integer32 (0..2147483647)
+ UNITS "Wh"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Units are Watt-hours.This is the energy consumed since the last reset.
+ This object is writable so that it can be reset to 0.
+ When it is written to 0, the xupsRecepCumulativePowerUsageTimer will be reset to 0 as well."
+ ::= { xupsRecepEntry 9 }
+
+xupsRecepCumulativePowerUsageTimer OBJECT-TYPE
+ SYNTAX Counter32
+ UNITS "Seconds"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Time in seconds since the cumulative power usage was last reset."
+ ::= { xupsRecepEntry 10 }
+
+
+--
+-- xupsTopology group:
+--
+xupsTopologyType OBJECT-TYPE
+ SYNTAX Integer32 (0..32767)
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Value which denotes the type of UPS by its power topology. Values are the
+ same as those described in the XCP Topology block's Overall Topology field."
+ ::= {xupsTopology 1}
+
+xupsTopoMachineCode OBJECT-TYPE
+ SYNTAX Integer32 (0..32767)
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "ID Value which denotes the Powerware model of the UPS for software.
+ Values are the same as those described in the XCP Configuration
+ block's Machine Code field."
+ ::= {xupsTopology 2}
+
+xupsTopoUnitNumber OBJECT-TYPE
+ SYNTAX Integer32 (0..64)
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Identifies which unit and what type of data is being reported.
+ A value of 0 means that this MIB information comes from the top-level system
+ view (eg, manifold module or system bypass cabinet reporting total system
+ output). Standalone units also use a value of 0, since they are the 'full
+ system' view.
+ A value of 1 or higher indicates the number of the module in the system
+ which is reporting only its own data in the PowerMIB objects."
+ ::= {xupsTopology 3}
+
+xupsTopoPowerStrategy OBJECT-TYPE
+ SYNTAX INTEGER {
+ highAlert(1), standard(2), enableHighEfficiency(3),
+ immediateHighEfficiency(4) }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Value which denotes which Power Strategy is currently set for the UPS.
+ The values are:
+ highAlert(1) - The UPS shall optimize its operating state to maximize its
+ power-protection levels. This mode will be held for at most 24 hours.
+ standard(2) - Balanced, normal power protection strategy. UPS will not enter
+ HE operating mode from this setting.
+ enableHighEfficiency(3) - The UPS is enabled to enter HE operating mode to
+ optimize its operating state to maximize its efficiency, when
+ conditions change to permit it (as determined by the UPS).
+ forceHighEfficiency(4) - If this value is permitted to be Set for this UPS,
+ and if conditions permit, requires the UPS to enter High Efficiency
+ mode now, without delay (for as long as utility conditions permit).
+ After successfully set to forceHighEfficiency(4),
+ xupsTopoPowerStrategy changes to value enableHighEfficiency(3).
+ xupsOutputSource will indicate if the UPS status is actually operating in
+ High Efficiency mode."
+ ::= {xupsTopology 4}
+
+
+--
+-- xupsAgent group:
+--
+xupsAgentManufacturer OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..31))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The card agent Manufacturer Name (e.g. Eaton Corporation)."
+ ::= { xupsAgent 1}
+
+xupsAgentModel OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..63))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The card agent model"
+ ::= {xupsAgent 2}
+
+xupsAgentSoftwareVersion OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..63))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The agent firmware version."
+ ::= {xupsAgent 3}
+
+xupsAgentPartNumber OBJECT-TYPE
+ SYNTAX OCTET STRING (SIZE(1..31))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The card agent catalog part number."
+ ::= { xupsAgent 4 }
+
+xupsAgentSerialNumber OBJECT-TYPE
+ SYNTAX OCTET STRING (SIZE(1..31))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The card agent catalog serial number."
+ ::= { xupsAgent 5 }
+
+
+-- *************************************************************************
+-- *************************************************************************
+
+--
+-- Traps (xupst)
+--
+-- 1) Eaton's traps have been defined in this MIB for three different sources.
+-- The trap definitions for the three sources are very similar,
+-- and use the same alarms as their triggers; their names are prefaced
+-- by xupstb, xupstd, and xupstp to distinguish the three types
+-- However, the products that the "Basic" and "Port Defined" trap types were
+-- created for have been obsoleted, so the only trap types in active use
+-- are the "Defined" (xupstd) traps listed below
+-- The Obsolete types have been moved to file XUPS_Obsolete.mib
+--
+-- a) OBSOLETE - Basic Agents for which the trap variables have not been
+-- defined, though trap variables are included with the trap PDU
+-- xupsNull OBJECT IDENTIFIER ::= { xupsMIB 0 }
+-- xupsTrapBasic OBJECT IDENTIFIER ::= { xupsNull 0 }
+--
+
+-- b) Agents with exactly Defined trap variables, which may be
+-- used as input to trap response macros on management stations
+-- This trap type is selected by setting xupsSendTrapType to xups(2)
+xupsTrapDefined OBJECT IDENTIFIER ::= {xupsTrapSource 1}
+-- Following the recommendations for coexistence between v1 traps
+-- and v2 notifications, define the snmpTrapOID base with a 0
+xupsTrapOidDefined OBJECT IDENTIFIER ::= { xupsTrapDefined 0 }
+
+--
+-- c) OBSOLETE - Agents with Defined traps including ifIndex and ifDescr,
+-- which can be used to determine which UPS of a multi-port
+-- agent (eg, Eaton Network SNMP Adapter) sent the trap
+-- This trap type was selected by setting xupsSendTrapType to xupsPlus(4)
+-- xupsTrapPortN OBJECT IDENTIFIER ::= {xupsTrapSource 2}
+--
+-- 2) Trap Severity Level is given as a comment to indicate which
+-- xupsMaxTrapLevel will result in this trap being sent;
+-- levels are (in order): Critical, Major, Minor, Informational
+--
+
+
+-- ****************************************************************************
+-- ****************************************************************************
+--
+-- Traps from xupsTrapDefined source (xupstd):
+--
+
+xupstdControlOff NOTIFICATION-TYPE
+ OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
+ STATUS current
+ DESCRIPTION
+ "The UPS output power will turn off in a number of
+ seconds equal to upsControlOutputOffTrapDelay."
+ --#SEVERITY CRITICAL
+ ::= { xupsTrapOidDefined 1 }
+
+xupstdControlOn NOTIFICATION-TYPE
+ OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
+ STATUS current
+ DESCRIPTION
+ "The UPS output power will turn on in a number of
+ seconds equal to upsControlOutputOnTrapDelay."
+ --#SEVERITY INFORMATIONAL
+ ::= { xupsTrapOidDefined 2 }
+
+xupstdOnBattery NOTIFICATION-TYPE
+ OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
+ STATUS current
+ DESCRIPTION
+ "The UPS has no AC input power and is running on
+ battery."
+ --#SEVERITY MAJOR
+ ::= { xupsTrapOidDefined 3 }
+
+xupstdLowBattery NOTIFICATION-TYPE
+ OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
+ STATUS current
+ DESCRIPTION
+ "The UPS batteries are low. Tied to low battery
+ alarm condition."
+ --#SEVERITY CRITICAL
+ ::= { xupsTrapOidDefined 4 }
+
+xupstdUtilityPowerRestored NOTIFICATION-TYPE
+ OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
+ STATUS current
+ DESCRIPTION
+ "Input power has been restored after running on battery."
+ --#SEVERITY INFORMATIONAL
+ ::= { xupsTrapOidDefined 5 }
+
+xupstdReturnFromLowBattery NOTIFICATION-TYPE
+ OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
+ STATUS current
+ DESCRIPTION
+ "The battery has recovered from a low battery condition."
+ --#SEVERITY INFORMATIONAL
+ ::= { xupsTrapOidDefined 6 }
+
+xupstdOutputOverload NOTIFICATION-TYPE
+ OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
+ STATUS current
+ DESCRIPTION
+ "The ups has sensed an overload of greater than
+ 106 percent. Tied to the 106% overload alarm."
+ --#SEVERITY MINOR
+ ::= { xupsTrapOidDefined 7 }
+
+xupstdInternalFailure NOTIFICATION-TYPE
+ OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
+ STATUS current
+ DESCRIPTION
+ "Some component of the ups - rectifier, inverter,
+ control panel has failed. Tied to alarms indi-
+ cating failure."
+ --#SEVERITY CRITICAL
+ ::= { xupsTrapOidDefined 8 }
+
+xupstdBatteryDischarged NOTIFICATION-TYPE
+ OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
+ STATUS current
+ DESCRIPTION
+ "The Battery Totally Discharged Alarm has occurred."
+ --#SEVERITY CRITICAL
+ ::= { xupsTrapOidDefined 9 }
+
+xupstdInverterFailure NOTIFICATION-TYPE
+ OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
+ STATUS current
+ DESCRIPTION
+ "The ups inverter is unavailable or malfunctioning due to an internal failure."
+ --#SEVERITY CRITICAL
+ ::= { xupsTrapOidDefined 10 }
+
+xupstdOnBypass NOTIFICATION-TYPE
+ OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
+ STATUS current
+ DESCRIPTION
+ "The ups has gone on bypass for some reason."
+ --#SEVERITY CRITICAL
+ ::= { xupsTrapOidDefined 11 }
+
+xupstdBypassNotAvailable NOTIFICATION-TYPE
+ OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
+ STATUS current
+ DESCRIPTION
+ "The ups bypass is unavailable"
+ --#SEVERITY MAJOR
+ ::= { xupsTrapOidDefined 12 }
+
+xupstdOutputOff NOTIFICATION-TYPE
+ OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
+ STATUS current
+ DESCRIPTION
+ "The ups output is switched off."
+ --#SEVERITY CRITICAL
+ ::= { xupsTrapOidDefined 13 }
+
+xupstdInputFailure NOTIFICATION-TYPE
+ OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
+ STATUS current
+ DESCRIPTION
+ "The ups input power is incorrect in voltage,
+ frequency, or phase rotation."
+ --#SEVERITY MINOR
+ ::= { xupsTrapOidDefined 14 }
+
+xupstdBuildingAlarm NOTIFICATION-TYPE
+ OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
+ STATUS current
+ DESCRIPTION
+ "One of the defined building alarms has occurred."
+ --#SEVERITY MAJOR
+ ::= { xupsTrapOidDefined 15 }
+
+xupstdShutdownImminent NOTIFICATION-TYPE
+ OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
+ STATUS current
+ DESCRIPTION
+ "The ups shutdown imminent alarm has occurred."
+ --#SEVERITY CRITICAL
+ ::= { xupsTrapOidDefined 16 }
+
+xupstdOnInverter NOTIFICATION-TYPE
+ OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
+ STATUS current
+ DESCRIPTION
+ "The ups is returned to utility power running the inverter
+ after either a transfer to bypass or a run on battery."
+ --#SEVERITY INFORMATIONAL
+ ::= { xupsTrapOidDefined 17 }
+
+xupstdBreakerOpen NOTIFICATION-TYPE
+ OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
+ STATUS current
+ DESCRIPTION
+ "One of the UPS breakers or contactors has been opened."
+ --#SEVERITY MAJOR
+ ::= { xupsTrapOidDefined 20 }
+
+xupstdAlarmEntryAdded NOTIFICATION-TYPE
+ OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
+ STATUS current
+ DESCRIPTION
+ "An alarm not defined in the xups Well Known Alarms
+ (eg, an alarm defined in RFC1628)
+ has been added to the Alarm Table."
+ --#SEVERITY MAJOR
+ ::= { xupsTrapOidDefined 21 }
+
+xupstdAlarmEntryRemoved NOTIFICATION-TYPE
+ OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
+ STATUS current
+ DESCRIPTION
+ "An alarm not defined in the xups Well Known Alarms
+ has been removed from the Alarm Table."
+ --#SEVERITY INFORMATIONAL
+ ::= { xupsTrapOidDefined 22 }
+
+xupstdAlarmBatteryBad NOTIFICATION-TYPE
+ OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
+ STATUS current
+ DESCRIPTION
+ "One or more batteries have been determined to require replacement."
+ --#SEVERITY MAJOR
+ ::= { xupsTrapOidDefined 23 }
+
+xupstdOutputOffAsRequested NOTIFICATION-TYPE
+ OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
+ STATUS current
+ DESCRIPTION
+ "The UPS has shutdown as requested, i.e., the output is off."
+ --#SEVERITY INFORMATIONAL
+ ::= { xupsTrapOidDefined 24 }
+
+xupstdDiagnosticTestFailed NOTIFICATION-TYPE
+ OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
+ STATUS current
+ DESCRIPTION
+ "The result of the last diagnostic test indicates a failure."
+ --#SEVERITY MINOR
+ ::= { xupsTrapOidDefined 25 }
+
+xupstdCommunicationsLost NOTIFICATION-TYPE
+ OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
+ STATUS current
+ DESCRIPTION
+ "A problem has been encountered in the communications
+ between the agent and the UPS."
+ --#SEVERITY MAJOR
+ ::= { xupsTrapOidDefined 26 }
+
+xupstdUpsShutdownPending NOTIFICATION-TYPE
+ OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
+ STATUS current
+ DESCRIPTION
+ "An xupsControlOutputOffDelay countdown is underway."
+ --#SEVERITY MAJOR
+ ::= { xupsTrapOidDefined 27 }
+
+xupstdAlarmTestInProgress NOTIFICATION-TYPE
+ OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
+ STATUS current
+ DESCRIPTION
+ "A test is in progress, as initiated and indicated by the xupsTest Group.
+ When the test is complete, one of the following traps will be sent:
+ - xupstdDiagnosticTestFailed if the test fails,
+ - xupstdDiagnosticTestPassed on success, or
+ - xupstdAlarmEntryRemoved in other cases (e.g., Test Canceled)."
+ --#SEVERITY INFORMATIONAL
+ ::= { xupsTrapOidDefined 28 }
+
+-- Provide additional information with the AmbientTemp trap
+xupstdAmbientTempBad NOTIFICATION-TYPE
+ OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage,
+ xupsEnvAmbientTemp, xupsEnvAmbientLowerLimit,
+ xupsEnvAmbientUpperLimit }
+ STATUS current
+ DESCRIPTION
+ "The ambient temperature, xupsEnvAmbientTemp, has fallen below
+ the set lower limit, xupsEnvAmbientLowerLimit, or has risen above
+ the set upper limit, xupsEnvAmbientUpperLimit."
+ --#SEVERITY MAJOR
+ ::= { xupsTrapOidDefined 29 }
+
+-- Added to support the ConnectUPS Web/SNMP card's ability to monitor contact(s)
+xupstdContactActiveNotice NOTIFICATION-TYPE
+ OBJECTS { xupsContactIndex, xupsContactType, xupsContactState, xupsContactDescr }
+ STATUS current
+ DESCRIPTION
+ "The Contact indicated by xupsContactIndex is in its Active state.
+ The following are the situations that generate this trap:
+ For xupsContactType: and xupsContactState:
+ normallyOpen(1) and closedWithNotice(4)
+ normallyClosed(2) and openWithNotice(3)
+ anyChange(3) and openWithNotice(3) or closedWithNotice(4)"
+ --#SEVERITY MAJOR
+ ::= { xupsTrapOidDefined 30 }
+
+xupstdContactInactiveNotice NOTIFICATION-TYPE
+ OBJECTS { xupsContactIndex, xupsContactType, xupsContactState, xupsContactDescr }
+ STATUS current
+ DESCRIPTION
+ "The Contact indicated by xupsContactIndex has changed to its Inactive state."
+ --#SEVERITY INFORMATIONAL
+ ::= { xupsTrapOidDefined 31 }
+
+
+xupstdLossOfRedundancy NOTIFICATION-TYPE
+ OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
+ STATUS current
+ DESCRIPTION
+ "A parallel UPS system is no longer operating in N+1 redundant mode;
+ this may be due to module failure or removal, or due to overloading."
+ --#SEVERITY MINOR
+ ::= { xupsTrapOidDefined 32 }
+
+xupstdAlarmTempBad NOTIFICATION-TYPE
+ OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
+ STATUS current
+ DESCRIPTION
+ "An internal temperature is out of tolerance."
+ --#SEVERITY MAJOR
+ ::= { xupsTrapOidDefined 33 }
+
+xupstdAlarmChargerFailed NOTIFICATION-TYPE
+ OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
+ STATUS current
+ DESCRIPTION
+ "An uncorrected problem has been detected within the UPS charger subsystem."
+ --#SEVERITY MAJOR
+ ::= { xupsTrapOidDefined 34 }
+
+xupstdAlarmFanFailure NOTIFICATION-TYPE
+ OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
+ STATUS current
+ DESCRIPTION
+ "The failure of one or more fans in the UPS has been detected."
+ --#SEVERITY MAJOR
+ ::= { xupsTrapOidDefined 35 }
+
+xupstdAlarmFuseFailure NOTIFICATION-TYPE
+ OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
+ STATUS current
+ DESCRIPTION
+ "The failure of one or more fuses has been detected."
+ --#SEVERITY CRITICAL
+ ::= { xupsTrapOidDefined 36 }
+
+xupstdPowerSwitchBad NOTIFICATION-TYPE
+ OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
+ STATUS current
+ DESCRIPTION
+ "A Relay, Contactor, or Breaker has failed."
+ --#SEVERITY CRITICAL
+ ::= { xupsTrapOidDefined 37 }
+
+xupstdModuleFailure NOTIFICATION-TYPE
+ OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
+ STATUS current
+ DESCRIPTION
+ "One module in a parallel or composite system has failed."
+ --#SEVERITY MAJOR
+ ::= { xupsTrapOidDefined 38 }
+
+-- xupsInputSource added to this trap's var list
+xupstdOnAlternatePowerSource NOTIFICATION-TYPE
+ OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage, xupsInputSource }
+ STATUS current
+ DESCRIPTION
+ "The system is being powered by its Alternate Power Source, such as a
+ Secondary utility feed (on a dual AC input UPS), generator, flywheel,
+ or fuel cell."
+ --#SEVERITY MINOR
+ ::= { xupsTrapOidDefined 39 }
+
+xupstdAltPowerNotAvailable NOTIFICATION-TYPE
+ OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
+ STATUS current
+ DESCRIPTION
+ "On systems with a separate alternate power source (eg, dual AC inputs),
+ that alternate power source is currently not available. This could be
+ a problem if the primary power source (eg, utility) fails for a period
+ of time longer than that for which the internal batteries can supply power."
+ --#SEVERITY MINOR
+ ::= { xupsTrapOidDefined 40 }
+
+xupstdNoticeCondition NOTIFICATION-TYPE
+ OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
+ STATUS current
+ DESCRIPTION
+ "Some Notice condition exists which is not covered by the other traps.
+ This is like an xupstdInternalFailure, but at a lower severity level."
+ --#SEVERITY MINOR
+ ::= { xupsTrapOidDefined 41 }
+
+
+-- Added to provide additional information with the RemoteTemp and RemoteHumidity
+xupstdRemoteTempBad NOTIFICATION-TYPE
+ OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage,
+ xupsEnvRemoteTemp, xupsEnvRemoteTempLowerLimit,
+ xupsEnvRemoteTempUpperLimit }
+ STATUS current
+ DESCRIPTION
+ "The remote temperature, xupsEnvRemoteTemp, has fallen below
+ the set lower limit, xupsEnvRemoteTempLowerLimit, or has risen above
+ the set upper limit, xupsEnvRemoteTempUpperLimit."
+ --#SEVERITY MAJOR
+ ::= { xupsTrapOidDefined 42 }
+
+xupstdRemoteHumidityBad NOTIFICATION-TYPE
+ OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage,
+ xupsEnvRemoteHumidity, xupsEnvRemoteHumidityLowerLimit,
+ xupsEnvRemoteHumidityUpperLimit }
+ STATUS current
+ DESCRIPTION
+ "The remote temperature, xupsEnvRemoteHumidity, has fallen below
+ the set lower limit, xupsEnvRemoteHumidityLowerLimit, or has risen above
+ the set upper limit, xupsEnvRemoteHumidityUpperLimit."
+ --#SEVERITY MINOR
+ ::= { xupsTrapOidDefined 43 }
+
+
+xupstdHeartbeat NOTIFICATION-TYPE
+ OBJECTS { xupsInputSource, xupsOutputSource, xupsAlarms }
+ STATUS current
+ DESCRIPTION
+ "A periodic status trap message. It is sent at an interval
+ set by object xupsHeartbeatMinsInterval.
+ The included variables provide a brief statement of the UPS status."
+ --#SEVERITY INFORMATIONAL
+ ::= { xupsTrapOidDefined 44 }
+
+xupstdDiagnosticTestPassed NOTIFICATION-TYPE
+ OBJECTS { xupsTestBatteryStatus, xupsLastGeneralTest, xupsLastGeneralTestResult }
+ STATUS current
+ DESCRIPTION
+ "A diagnostic test just completed, and its result is Passed.
+ The included variables provide additional information on the test."
+ --#SEVERITY INFORMATIONAL
+ ::= { xupsTrapOidDefined 45 }
+
+xupstdOutputBad NOTIFICATION-TYPE
+ OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
+ STATUS current
+ DESCRIPTION
+ "The output condition (other than OutputOverload) is out of tolerance."
+ --#SEVERITY CRITICAL
+ ::= { xupsTrapOidDefined 46 }
+
+xupstdAwaitingPower NOTIFICATION-TYPE
+ OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
+ STATUS current
+ DESCRIPTION
+ "The UPS output is off and the UPS is awaiting the return of input power."
+ --#SEVERITY MINOR
+ ::= { xupsTrapOidDefined 47 }
+
+xupstdOnMaintenanceBypass NOTIFICATION-TYPE
+ OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
+ STATUS current
+ DESCRIPTION
+ "The UPS has been placed on Maintenance / Manual Bypass by an operator."
+ --#SEVERITY MAJOR
+ ::= { xupsTrapOidDefined 48 }
+
+xupstdCommEstablished NOTIFICATION-TYPE
+ OBJECTS { xupsIdentModel, xupsOutputSource }
+ STATUS current
+ DESCRIPTION
+ "This trap is sent when the SNMP agent first establishes a communication
+ link with the UPS.
+ The included variables provide identification and UPS status information."
+ --#SEVERITY INFORMATIONAL
+ ::= { xupsTrapOidDefined 49 }
+
+xupstdAgentDown NOTIFICATION-TYPE
+ -- OBJECTS { (none) }
+ STATUS current
+ DESCRIPTION
+ "This trap is sent when the SNMP agent is exiting or closing down gracefully.
+ This may be triggered by a signal from the OS to stop this process. In many
+ implementations, it will be followed quickly by a restart of this vital process."
+ --#SEVERITY MINOR
+ ::= { xupsTrapOidDefined 50 }
+
+-- New traps now managed by the Network-M2 card
+xupstdOutputNotProtected NOTIFICATION-TYPE
+ OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
+ STATUS current
+ DESCRIPTION
+ "The ups output is not protectet for any reason in the UPS."
+ --#SEVERITY CRITICAL
+ ::= { xupsTrapOidDefined 51 }
+
+xupstdTestTrap NOTIFICATION-TYPE
+ OBJECTS { sysName, xupsTrapMessage }
+ STATUS current
+ DESCRIPTION
+ "This trap is sent to the trap receivers to check proper reception of traps."
+ --#SEVERITY INFORMATIONAL
+ ::= { xupsTrapOidDefined 100 }
+
+--
+-- Conformance-related definitions
+-- (Defined mostly to satisfy the MIB checkers.)
+--
+xupsConformance OBJECT IDENTIFIER ::= { xupsMIB 100 }
+
+xupsIdentFullGroup OBJECT-GROUP
+ OBJECTS { xupsIdentManufacturer, xupsIdentModel,
+ xupsIdentSoftwareVersion, xupsIdentOemCode,
+ xupsIdentPartNumber, xupsIdentSerialNumber }
+ STATUS current
+ DESCRIPTION
+ "The Full set of xupsIdent subgroup objects."
+ ::= { xupsConformance 2 }
+
+xupsBatteryFullGroup OBJECT-GROUP
+ OBJECTS { xupsBatTimeRemaining, xupsBatVoltage, xupsBatCurrent,
+ xupsBatCapacity, xupsBatteryAbmStatus, xupsBatteryLastReplacedDate,
+ xupsBatteryFailure, xupsBatteryNotPresent, xupsBatteryAged, xupsBatteryLowCapacity }
+ STATUS current
+ DESCRIPTION
+ "The Full set of xupsBattery subgroup objects."
+ ::= { xupsConformance 3 }
+
+xupsInputFullGroup OBJECT-GROUP
+ OBJECTS { xupsInputFrequency, xupsInputLineBads, xupsInputNumPhases,
+ xupsInputSource, xupsDualInputStatus, xupsSecondaryInputWatch, xupsInputStatus }
+ STATUS current
+ DESCRIPTION
+ "The Full set of xupsInput subgroup objects."
+ ::= { xupsConformance 4 }
+
+xupsInputTableFullGroup OBJECT-GROUP
+ OBJECTS { xupsInputPhase, xupsInputVoltage, xupsInputCurrent, xupsInputWatts,
+ xupsInputId, xupsInputName, xupsInputCurrentHighPrecision }
+ STATUS current
+ DESCRIPTION
+ "The Full set of xupsInputTable subgroup objects."
+ ::= { xupsConformance 5 }
+
+xupsOutputFullGroup OBJECT-GROUP
+ OBJECTS { xupsOutputLoad, xupsOutputFrequency, xupsOutputNumPhases, xupsOutputSource,
+ xupsOutputHourlyPowerUsage, xupsOutputCumulativePowerUsage, xupsOutputCumulativePowerUsageTimer, xupsOutputStatus }
+ STATUS current
+ DESCRIPTION
+ "The Full set of xupsOutput subgroup objects."
+ ::= { xupsConformance 6 }
+
+xupsOutputTableFullGroup OBJECT-GROUP
+ OBJECTS { xupsOutputPhase, xupsOutputVoltage, xupsOutputCurrent, xupsOutputWatts,
+ xupsOutputId, xupsOutputName, xupsOutputCurrentHighPrecision, xupsOutputPercentLoad, xupsOutputVA }
+ STATUS current
+ DESCRIPTION
+ "The Full set of xupsOutputTable subgroup objects."
+ ::= { xupsConformance 7 }
+
+xupsBypassFullGroup OBJECT-GROUP
+ OBJECTS { xupsBypassFrequency, xupsBypassNumPhases, xupsBypassPhase, xupsBypassVoltage }
+ STATUS current
+ DESCRIPTION
+ "The Full set of xupsBypass subgroup objects."
+ ::= { xupsConformance 8 }
+
+xupsEnvironmentFullGroup OBJECT-GROUP
+ OBJECTS { xupsEnvAmbientTemp, xupsEnvAmbientLowerLimit,
+ xupsEnvAmbientUpperLimit, xupsEnvAmbientHumidity }
+ STATUS current
+ DESCRIPTION
+ "The Full set of xupsEnvironment subgroup objects."
+ ::= { xupsConformance 9 }
+
+xupsAlarmFullGroup OBJECT-GROUP
+ OBJECTS { xupsAlarms, xupsAlarmID, xupsAlarmDescr, xupsAlarmTime }
+ STATUS current
+ DESCRIPTION
+ "The Full set of xupsAlarm subgroup objects."
+ ::= { xupsConformance 10 }
+
+xupsAlarmEventsFullGroup OBJECT-GROUP
+ OBJECTS { xupsAlarmNumEvents, xupsAlarmEventMsg }
+ STATUS current
+ DESCRIPTION
+ "The Full set of Alarm/Event history subgroup objects."
+ ::= { xupsConformance 11 }
+
+xupsTestFullGroup OBJECT-GROUP
+ OBJECTS { xupsTestStart, xupsTestBatteryStatus, xupsLastGeneralTest,
+ xupsLastGeneralTestResult, xupsTestTrap }
+ STATUS current
+ DESCRIPTION
+ "The Full set of xupsTest subgroup objects."
+ ::= { xupsConformance 12 }
+
+xupsControlFullGroup OBJECT-GROUP
+ OBJECTS { xupsControlOutputOffDelay, xupsControlOutputOnDelay,
+ xupsControlOutputOffTrapDelay, xupsControlToBypassDelay,
+ xupsLoadShedSecsWithRestart, xupsSwitchable }
+ STATUS current
+ DESCRIPTION
+ "The Full set of xupsControl subgroup objects."
+ ::= { xupsConformance 13 }
+
+xupsConfigFullGroup OBJECT-GROUP
+ OBJECTS { xupsConfigOutputVoltage, xupsConfigInputVoltage, xupsConfigOutputWatts,
+ xupsConfigOutputFreq, xupsConfigDateAndTime, xupsConfigLowOutputVoltageLimit,
+ xupsConfigHighOutputVoltageLimit, xupsConfigInstallDate }
+ STATUS current
+ DESCRIPTION
+ "The Full set of xupsConfig subgroup objects."
+ ::= { xupsConformance 14 }
+
+xupsTrapControlFullGroup OBJECT-GROUP
+ OBJECTS { xupsMaxTrapLevel, xupsSendTrapType, xupsTrapMessage,
+ xupsHeartbeatMinsInterval }
+ STATUS current
+ DESCRIPTION
+ "The Full set of xupsTrapControl subgroup objects."
+ ::= { xupsConformance 15 }
+
+xupsRecepFullGroup OBJECT-GROUP
+ OBJECTS { xupsNumReceptacles, xupsRecepIndex, xupsRecepStatus,
+ xupsRecepOffDelaySecs, xupsRecepOnDelaySecs,
+ xupsRecepAutoOffDelay, xupsRecepAutoOnDelay, xupsRecepShedSecsWithRestart,
+ xupsRecepHourlyPowerUsage, xupsRecepCumulativePowerUsage, xupsRecepCumulativePowerUsageTimer }
+ STATUS current
+ DESCRIPTION
+ "The Full set of xupsRecep subgroup objects."
+ ::= { xupsConformance 16 }
+
+xupsTopologyFullGroup OBJECT-GROUP
+ OBJECTS { xupsTopologyType, xupsTopoMachineCode,
+ xupsTopoUnitNumber, xupsTopoPowerStrategy }
+ STATUS current
+ DESCRIPTION
+ "The Full set of xupsTopology subgroup objects."
+ ::= { xupsConformance 17 }
+
+xupstdNotifyGroup NOTIFICATION-GROUP
+ NOTIFICATIONS { xupstdControlOff, xupstdControlOn, xupstdOnBattery, xupstdLowBattery,
+ xupstdUtilityPowerRestored, xupstdReturnFromLowBattery,
+ xupstdOutputOverload, xupstdInternalFailure, xupstdBatteryDischarged,
+ xupstdInverterFailure, xupstdOnBypass, xupstdBypassNotAvailable,
+ xupstdOutputOff, xupstdInputFailure, xupstdBuildingAlarm,
+ xupstdShutdownImminent, xupstdOnInverter, xupstdBreakerOpen,
+ xupstdAlarmEntryAdded, xupstdAlarmEntryRemoved, xupstdAlarmBatteryBad,
+ xupstdOutputOffAsRequested, xupstdDiagnosticTestFailed,
+ xupstdCommunicationsLost, xupstdUpsShutdownPending, xupstdAlarmTempBad,
+ xupstdAlarmTestInProgress, xupstdAmbientTempBad, xupstdLossOfRedundancy,
+ xupstdAlarmChargerFailed, xupstdAlarmFanFailure, xupstdAlarmFuseFailure,
+ xupstdPowerSwitchBad, xupstdModuleFailure, xupstdOnAlternatePowerSource,
+ xupstdAltPowerNotAvailable, xupstdNoticeCondition, xupstdHeartbeat,
+ xupstdDiagnosticTestPassed, xupstdOutputBad, xupstdAwaitingPower,
+ xupstdOnMaintenanceBypass, xupstdCommEstablished, xupstdAgentDown,
+ xupstdOutputNotProtected, xupstdTestTrap }
+ STATUS current
+ DESCRIPTION
+ "The Alarm and Event notifications from the xupsTrapDefined source (xupstd)."
+ ::= { xupsConformance 18 }
+
+xupstdEMPNotifyGroup NOTIFICATION-GROUP
+ NOTIFICATIONS { xupstdContactActiveNotice, xupstdContactInactiveNotice,
+ xupstdRemoteTempBad, xupstdRemoteHumidityBad }
+ STATUS current
+ DESCRIPTION
+ "The EMP's Alarm and Event notifications from the xupsTrapDefined source (xupstd)."
+ ::= { xupsConformance 19 }
+
+
+xupsMibFullCompliance MODULE-COMPLIANCE
+ STATUS current
+ DESCRIPTION
+ "A compliance statement for all of everything in this MIB."
+ MODULE -- this module
+ MANDATORY-GROUPS { xupsIdentFullGroup, xupsBatteryFullGroup, xupsInputFullGroup,
+ xupsInputTableFullGroup, xupsOutputFullGroup, xupsOutputTableFullGroup,
+ xupsBypassFullGroup, xupsEnvironmentFullGroup, xupsAlarmFullGroup,
+ xupsAlarmEventsFullGroup, xupsTestFullGroup, xupsControlFullGroup,
+ xupsConfigFullGroup, xupsTrapControlFullGroup, xupsRecepFullGroup,
+ xupsTopologyFullGroup, xupstdNotifyGroup, xupstdEMPNotifyGroup,
+ xupsBypassTableFullGroup, xupsInputTotalFullGroup, xupsOutputTotalFullGroup,
+ xupsBypassTotalFullGroup }
+ ::= { xupsConformance 20 }
+
+xupsDeprecatedGroup OBJECT-GROUP
+ OBJECTS { xupsAlarmEventDateAndTime, xupsAlarmEventKind,
+ xupsAlarmEventDescr, xupsControlOutputOnTrapDelay }
+ STATUS deprecated
+ DESCRIPTION
+ "Contains objects which are now deprecated."
+ ::= { xupsConformance 21 }
+
+xupsBypassTableFullGroup OBJECT-GROUP
+ OBJECTS { xupsBypassId, xupsBypassName, xupsBypassCurrentHighPrecision, xupsBypassWatts }
+ STATUS current
+ DESCRIPTION
+ "The Full set of xupsBypassTable subgroup objects."
+ ::= { xupsConformance 22 }
+
+xupsInputTotalFullGroup OBJECT-GROUP
+ OBJECTS { xupsInputAverageVoltage, xupsInputTotalCurrent, xupsInputTotalWatts,
+ xupsInputTotalVA, xupsInputAveragePowerFactor }
+ STATUS current
+ DESCRIPTION
+ "The Full set of xupsInputTotal subgroup objects."
+ ::= { xupsConformance 23 }
+
+xupsOutputTotalFullGroup OBJECT-GROUP
+ OBJECTS { xupsOutputAverageVoltage, xupsOutputTotalCurrent, xupsOutputTotalWatts,
+ xupsOutputTotalVA, xupsOutputAveragePowerFactor }
+ STATUS current
+ DESCRIPTION
+ "The Full set of xupsOutputTotal subgroup objects."
+ ::= { xupsConformance 24 }
+
+xupsBypassTotalFullGroup OBJECT-GROUP
+ OBJECTS { xupsBypassAverageVoltage, xupsBypassTotalCurrent, xupsBypassTotalWatts,
+ xupsBypassTotalVA, xupsBypassAveragePowerFactor }
+ STATUS current
+ DESCRIPTION
+ "The Full set of xupsOutputTotal subgroup objects."
+ ::= { xupsConformance 25 }
+
+xupsAgentFullGroup OBJECT-GROUP
+ OBJECTS { xupsAgentManufacturer, xupsAgentModel,
+ xupsAgentSoftwareVersion, xupsAgentPartNumber, xupsAgentSerialNumber }
+ STATUS current
+ DESCRIPTION
+ "The Full set of xupsAgent subgroup objects."
+ ::= { xupsConformance 26 }
+
+ END
+