+-- Copyright(C) 2019 Panduit
+-- G5 PDU SNMP MIB DEFINITIONS
+-- ****************************************************************************
+
+-- ====================================================================================
+PANDUIT-MIB DEFINITIONS ::= BEGIN
+
+IMPORTS
+ enterprises FROM RFC1155-SMI
+ Counter FROM RFC1155-SMI
+ DisplayString FROM RFC1213-MIB
+ ifIndex FROM RFC1213-MIB
+ ifDescr FROM RFC1213-MIB
+ sysName FROM RFC1213-MIB
+ sysDescr FROM RFC1213-MIB
+ sysContact FROM RFC1213-MIB
+ sysLocation FROM RFC1213-MIB
+ OBJECT-TYPE FROM RFC-1212
+ NOTIFICATION-TYPE FROM RFC-1215;
+
+panduit OBJECT IDENTIFIER ::= { enterprises 19536 }
+
+g5 MODULE-IDENTITY
+ LAST-UPDATED "201902021200Z" -- 2 February 2019
+ ORGANIZATION "Panduit"
+ CONTACT-INFO "Panduit
+
+ Postal: Panduit
+ 18900 Panduit Drive
+ Tinley Park, IL 60487
+ USA
+
+ Tel: +1 708 532-1800/888-506-5400
+
+ E-mail: techsupport@panduit.com"
+ DESCRIPTION
+ "SmartZone G5 iPDU"
+ REVISION "201902021200Z" -- 12 February 2019
+ DESCRIPTION
+ "Fix the index and access hub and added the Energy Thresholds"
+ REVISION "201801121200Z" -- 12 January 2018
+ DESCRIPTION
+ "First Major Release"
+ ::= { panduit 10 }
+
+--
+-- pdug5 Monitored Managed PDU object identifiers
+--
+pdug5 OBJECT IDENTIFIER ::= {g5 1}
+
+pdug5Ident OBJECT IDENTIFIER ::= { pdug5 1 }
+pdug5Input OBJECT IDENTIFIER ::= { pdug5 2 }
+pdug5Group OBJECT IDENTIFIER ::= { pdug5 3 }
+pdug5Environment OBJECT IDENTIFIER ::= { pdug5 4 }
+pdug5Outlet OBJECT IDENTIFIER ::= { pdug5 5 }
+pdug5Traps OBJECT IDENTIFIER ::= { pdug5 6 }
+pdug5TrapInfo OBJECT IDENTIFIER ::= { pdug5 7 }
+
+-- ====================================================================================
+-- ====================================================================================
+-- pdug5 - monitored and managed PDU line
+-- pdug5 (Panduit PDU) - Metered PDU - Switched PDU - Metered+Switched PDU
+-- ====================================================================================
+--
+-- g5 OBJECT IDENTIFIER ::= { panduit 10}
+-- pdug5 OBJECT IDENTIFIER ::= { g5 1}
+-- pdug5Ident OBJECT IDENTIFIER ::= { pdug5 1 }
+-- PDU identification group
+-- OID= .1.3.6.1.4.1.19536.10.1.1
+
+pdug5NumberPDU OBJECT-TYPE
+ SYNTAX INTEGER (1..4)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of PDUs detected (in its daisy chain)."
+ ::= { pdug5Ident 1 }
+
+-- ======= pdug5 Identification ===========
+
+pdug5IdentTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF pdug5IdentEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "Aggregate Object with number of entries equal to pdug5NumberPDU ."
+ ::= { pdug5Ident 2 }
+
+pdug5IdentEntry OBJECT-TYPE
+ SYNTAX pdug5IdentEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "The Identity table entry containing the name, model, manufacturer,
+ firmware version, part number, etc."
+ INDEX { pdug5IdentIndex }
+ ::= { pdug5IdentTable 1 }
+
+pdug5IdentEntry ::= SEQUENCE {
+ pdug5IdentIndex INTEGER,
+ pdug5Name DisplayString,
+ pdug5Model DisplayString,
+ pdug5Manufacturer DisplayString,
+ pdug5FirmwareVersion DisplayString,
+ pdug5FirmwareVersionTimeStamp DisplayString,
+ pdug5PartNumber DisplayString,
+ pdug5SerialNumber DisplayString,
+ pdug5Status INTEGER,
+ pdug5Controllable INTEGER,
+ pdug5InputPhaseCount INTEGER,
+ pdug5GroupCount INTEGER,
+ pdug5OutletCount INTEGER,
+ pdug5MACAddress DisplayString,
+ pdug5IPv4Address DisplayString,
+ pdug5IPv6Address DisplayString
+ }
+
+pdug5IdentIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..4)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index for the pdug5IdentEntry table."
+ ::= { pdug5IdentEntry 1 }
+
+pdug5Name OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..63))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The string identify the device in daisy chain. Example PDU A."
+ ::= { pdug5IdentEntry 2 }
+
+pdug5Model OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..63))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Device Model."
+ ::= { pdug5IdentEntry 3 }
+
+pdug5Manufacturer OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..63))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Device Manufacturer Name."
+ ::= { pdug5IdentEntry 4 }
+
+pdug5FirmwareVersion OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..63))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The firmware revision level of the device."
+ ::= { pdug5IdentEntry 5 }
+
+pdug5FirmwareVersionTimeStamp OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Timestamp of when the PDU firmware was last updated"
+ ::= { pdug5IdentEntry 6 }
+
+pdug5PartNumber OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..63))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The device part number. Example P36E09M."
+ ::= { pdug5IdentEntry 7 }
+
+pdug5SerialNumber OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..63))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The device serial number, 10-digit."
+ ::= { pdug5IdentEntry 8 }
+
+pdug5Status OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ other(1),
+ ok(2),
+ degraded(3),
+ failed(4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The overall status of the device. A value of OK(2) indicates the device is operating normally.
+ A value of degraded(3) indicates the device is operating with warning indicators. A value of
+ failed(4) indicates the device is operating with critical indicators."
+ ::= { pdug5IdentEntry 9 }
+
+pdug5Controllable OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ yes(1),
+ no(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This object indicates whether or not the device is controllable."
+ ::= { pdug5IdentEntry 10 }
+
+pdug5InputPhaseCount OBJECT-TYPE
+ SYNTAX INTEGER (1..3)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of input phase on this pdu 1 or 3."
+ ::= { pdug5IdentEntry 11 }
+
+pdug5GroupCount OBJECT-TYPE
+ SYNTAX INTEGER (0..12)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of groups (breakers) on this pdu."
+ ::= { pdug5IdentEntry 12 }
+
+pdug5OutletCount OBJECT-TYPE
+ SYNTAX INTEGER (1..48)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of outlets in this PDU."
+ ::= { pdug5IdentEntry 13 }
+
+pdug5MACAddress OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The assigned MAC address for this PDU."
+ ::={ pdug5IdentEntry 14 }
+
+pdug5IPv4Address OBJECT-TYPE
+ SYNTAX IpAddress
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current IPv4 Address.
+ A value of 0.0.0.0 indicates an error or an unset option."
+ ::={ pdug5IdentEntry 15 }
+
+pdug5IPv6Address OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current IPv6 Address.
+ A vale of 0.0.0.0.0.0 indicates an error or an unset option."
+ ::={ pdug5IdentEntry 16 }
+
+-- ============ pdug5 Configuration =======
+
+pdug5ConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF pdug5ConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "Aggregate Object with number of entries equal to pdug5NumberPDU."
+ ::= { pdug5Ident 3 }
+
+pdug5ConfigEntry OBJECT-TYPE
+ SYNTAX pdug5ConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Read Configuration data from the PDU being queried."
+ INDEX {pdug5ConfigIndex}
+ ::= {pdug5ConfigTable 1}
+
+pdug5ConfigEntry ::= SEQUENCE{
+ pdug5ConfigIndex INTEGER,
+ pdug5ConfigSsh INTEGER,
+ pdug5ConfigFtps INTEGER,
+ pdug5ConfigHttp INTEGER,
+ pdug5ConfigHttps INTEGER,
+ pdug5ConfigIPv4IPv6Switch INTEGER,
+ pdug5ConfigRedfishAPI INTEGER,
+ pdug5ConfigOledDispalyOrientation INTEGER,
+ pdug5ConfigEnergyReset INTEGER,
+ pdug5ConfigNetworkManagementCardReset INTEGER,
+ pdug5ConfigDaisyChainStatus INTEGER
+ }
+
+pdug5ConfigIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..4)
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The index of PDU configuration entry."
+ ::={pdug5ConfigEntry 1}
+
+pdug5ConfigSsh OBJECT-TYPE
+ SYNTAX INTEGER{
+ off(0),
+ on(1)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to off(0) will disable the SSH conneciton.
+ Setting this OID to on(1) will enable the SSH connection. iNC reboot will be required for the settings to take effect."
+ ::={pdug5ConfigEntry 2}
+
+pdug5ConfigFtps OBJECT-TYPE
+ SYNTAX INTEGER{
+ off(0),
+ on(1)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to off(0) will disable the FTPS connection.
+ Setting this OID to on(1) will enable the FTPS connection. iNC reboot will be required for the settings to take effect"
+ ::={pdug5ConfigEntry 3}
+
+pdug5ConfigHttp OBJECT-TYPE
+ SYNTAX INTEGER{
+ off(0),
+ on(1)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to off(0) will disable the HTTP connection.
+ Setting this OID to on(1) will enable the HTTP connection.iNC reboot will be required for the settings to take effect"
+ ::={pdug5ConfigEntry 4}
+
+pdug5ConfigHttps OBJECT-TYPE
+ SYNTAX INTEGER{
+ off(0),
+ on(1)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to off(0) will disable the HTTPS connection.
+ Setting this OID to on(1) will enable the HTTPS connection.iNC reboot will be required for the settings to take effect"
+ ::={pdug5ConfigEntry 5}
+
+pdug5ConfigIPv4IPv6Switch OBJECT-TYPE
+ SYNTAX INTEGER{
+ iPv4(1),
+ iPv6(2),
+ iPv4IPv6(3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to IPv4(1) will enable the IPv4 configuration.
+ Setting this OID to IPv6(2) will enable the IPv6 configuration.
+ Setting this OID to IPv4&IPv6(3) will enable both IPv4 and IPv6 configuration.iNC reboot will be required for the settings to take effect"
+ ::={pdug5ConfigEntry 6}
+
+pdug5ConfigRedfishAPI OBJECT-TYPE
+ SYNTAX INTEGER{
+ off(0),
+ on(1)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to off(0) will disable the Redfish API.
+ Setting this OID to on(1) will enable the Redfish API.iNC reboot will be required for the settings to take effect"
+ ::={pdug5ConfigEntry 7}
+
+pdug5ConfigOledDispalyOrientation OBJECT-TYPE
+ SYNTAX INTEGER{
+ displayNormal(1),
+ displayReverse(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the intended physical orientation of OLED display.
+ displayNormal(1) indicates normal orientation.
+ displayReverse(2) indicates upside down orientation."
+ ::={pdug5ConfigEntry 8}
+
+pdug5ConfigEnergyReset OBJECT-TYPE
+ SYNTAX INTEGER{
+ noOperation(1),
+ reset(2),
+ notSupported(3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to reset(2) will cause the device energy meter value
+ to be reset to zero. Getting this OID in models that support this feature
+ will do nothing and return the noOperation(1) value. Models that do not
+ supported this feature will respond to this OID with a value of notSupported(3).
+ Attempts to set this OID in these models will fail."
+ ::={pdug5ConfigEntry 9}
+
+pdug5ConfigNetworkManagementCardReset OBJECT-TYPE
+ SYNTAX INTEGER{
+ noOperation(0),
+ reset(1)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return noOperation(0).
+ Getting this OID to reset(1) will reset iNC."
+ ::={pdug5ConfigEntry 10}
+
+pdug5ConfigDaisyChainStatus OBJECT-TYPE
+ SYNTAX INTEGER{
+ daisychain(0),
+ rna(1)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID will change daisychain mode. 0:QNA,1:DNA."
+ ::={pdug5ConfigEntry 11}
+
+-- ====================================================================================--
+-- g5 OBJECT IDENTIFIER ::= { panduit 10}
+-- pdug5 OBJECT IDENTIFIER ::= { g5 1}
+-- pdug5Ident OBJECT IDENTIFIER ::= { pdug5 2 }
+-- PDU input group
+-- OID= .1.3.6.1.4.1.19536.10.1.2
+
+pdug5InputTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF pdug5InputEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Aggregate Object with number of entries equal to pdug5NumberPDU ."
+ ::= { pdug5Input 1 }
+
+pdug5InputEntry OBJECT-TYPE
+ SYNTAX pdug5InputEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The ident table entry containing the VA, Watts, WH, etc."
+ INDEX { pdug5IdentIndex }
+ ::= { pdug5InputTable 1 }
+
+pdug5InputEntry ::= SEQUENCE {
+ pdug5InputType INTEGER,
+ pdug5InputFrequency INTEGER,
+ pdug5InputFrequencyStatus INTEGER,
+ pdug5InputPowerVA INTEGER,
+ pdug5InputPowerWatts INTEGER,
+ pdug5InputTotalEnergy INTEGER,
+ pdug5InputPowerWattHourTimer DisplayString,
+ pdug5InputResettableEnergy INTEGER,
+ pdug5InputPowerFactor INTEGER,
+ pdug5InputPowerVAR INTEGER,
+ pdug5InputTotalCurrent INTEGER
+ }
+
+pdug5InputType OBJECT-TYPE
+ SYNTAX INTEGER {
+ singlePhase (1),
+ splitPhase (2),
+ threePhaseDelta (3),
+ threePhaseWye (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Type of input - single phase, split phase, three phase delta, or three
+ phase wye."
+ ::= { pdug5InputEntry 1 }
+
+pdug5InputFrequency OBJECT-TYPE
+ SYNTAX INTEGER (0..2147483647) -- UNITS RMS 0.001 Hz
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The measured input frequency from the PDU meters in tenths of Hz."
+ ::= { pdug5InputEntry 2 }
+
+pdug5InputFrequencyStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ good (1),
+ outOfRange (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Status of the measured input frequency relative to the nominal frequency and the admitted tolerance."
+ ::= { pdug5InputEntry 3 }
+
+pdug5InputPowerVA OBJECT-TYPE
+ SYNTAX INTEGER -- Units in VA
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A total input VA of all phases. Units are VA. A negative value indicates
+ that this object is not available."
+ ::= { pdug5InputEntry 4 }
+
+pdug5InputPowerWatts OBJECT-TYPE
+ SYNTAX INTEGER -- Units in Watts
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A total input Watts of all phases. Units are Watts. A negative value indicates
+ that this object is not available."
+ ::= { pdug5InputEntry 5 }
+
+pdug5InputTotalEnergy OBJECT-TYPE
+ SYNTAX INTEGER -- Units in KWh
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A total input Watt-Hour value for all phases. Units are KWh. This value is accumulated since PDU in service.
+ A negative value indicates that this object is not available."
+ ::= { pdug5InputEntry 6 }
+
+pdug5InputPowerWattHourTimer OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..22)) -- display Date Time Since Last Reset
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A Timestamp of when the Total Input WH was last reset."
+ ::= { pdug5InputEntry 7 }
+
+pdug5InputResettableEnergy OBJECT-TYPE
+ SYNTAX INTEGER -- Units in Wh
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A total input Watt-Hour value for all phases. Units are Wh. This value can be reset to 0
+ using GUI. In that case, the pdug5InputPowerWattHourTimer will be reset as well
+ A negative value indicates that this object is not available."
+ ::= { pdug5InputEntry 8 }
+
+pdug5InputPowerFactor OBJECT-TYPE
+ SYNTAX INTEGER -- units 0.01
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An input PF value. Units are in thousandths, for example a power factor
+ of 0.95 would be returned as 95, and 0.92 would be returned as 92.
+ A negative value indicates that this object is not available."
+ ::= { pdug5InputEntry 9 }
+
+pdug5InputPowerVAR OBJECT-TYPE
+ SYNTAX INTEGER -- Units in VAR
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An input VAR value. Units are VAR. A negative value indicates
+ that this object is not available."
+ ::= { pdug5InputEntry 10 }
+
+pdug5InputTotalCurrent OBJECT-TYPE
+ SYNTAX INTEGER -- Units are 0.01 A
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "All phases total current value. Units are 0.01 amps.
+ For 3 phase, mathematically add totally 3 phase current together."
+ ::= { pdug5InputEntry 11 }
+
+-- ==========Input per Phase =============
+
+pdug5InputPhaseTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF pdug5InputPhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Aggregate Object with number of entries equal to number of PDUs (pdug5NumberPDU) and
+ number of input phase (pdug5InputPhaseCount)."
+ ::= {pdug5Input 2}
+
+pdug5InputPhaseEntry OBJECT-TYPE
+ SYNTAX pdug5InputPhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The input table entry containing the voltage, current, frequency, power for each phase.
+ Entries are given with number of pdu and number of input phase 1, 2, or 3."
+ INDEX { pdug5IdentIndex, pdug5InputPhaseIndex }
+ ::= { pdug5InputPhaseTable 1 }
+
+pdug5InputPhaseEntry ::= SEQUENCE {
+ pdug5InputPhaseIndex INTEGER,
+ pdug5InputPhaseVoltageMeasType INTEGER,
+ pdug5InputPhaseVoltage INTEGER,
+ pdug5InputPhaseVoltageThStatus INTEGER,
+ pdug5InputPhaseVoltageThLowerWarning INTEGER,
+ pdug5InputPhaseVoltageThLowerCritical INTEGER,
+ pdug5InputPhaseVoltageThUpperWarning INTEGER,
+ pdug5InputPhaseVoltageThUpperCritical INTEGER,
+ pdug5InputPhaseCurrentMeasType INTEGER,
+ pdug5InputPhaseCurrentRating INTEGER,
+ pdug5InputPhaseCurrent INTEGER,
+ pdug5InputPhaseCurrentThStatus INTEGER,
+ pdug5InputPhaseCurrentThLowerWarning INTEGER,
+ pdug5InputPhaseCurrentThLowerCritical INTEGER,
+ pdug5InputPhaseCurrentThUpperWarning INTEGER,
+ pdug5InputPhaseCurrentThUpperCritical INTEGER,
+ pdug5InputPhaseCurrentPercentLoad INTEGER,
+ pdug5InputPhasePowerMeasType INTEGER,
+ pdug5InputPhasePowerVA INTEGER,
+ pdug5InputPhasePowerWatts INTEGER,
+ pdug5InputPhasePowerWattHour INTEGER,
+ pdug5InputPhasePowerWattHourTimer DisplayString,
+ pdug5InputPhasePowerFactor INTEGER,
+ pdug5InputPhasePowerVAR INTEGER,
+ pdug5InputPhaseVoltageThResetThld INTEGER,
+ pdug5InputPhaseVoltageThChangeDelay INTEGER,
+ pdug5InputPhaseVoltageThCtrl INTEGER,
+ pdug5InputPhaseCurrentThResetThld INTEGER,
+ pdug5InputPhaseCurrentThChangeDelay INTEGER,
+ pdug5InputPhaseCurrentThCtrl INTEGER,
+ pdug5InputPowerThresholdThLowerWarning INTEGER,
+ pdug5InputPowerThresholdThLowerCritical INTEGER,
+ pdug5InputPowerThresholdThUpperWarning INTEGER,
+ pdug5InputPowerThresholdThUpperCritical INTEGER,
+ pdug5InputPowerThresholdThResetThld INTEGER,
+ pdug5InputPowerThresholdThChangeDelay INTEGER,
+ pdug5InputPowerThresholdThCtrl INTEGER,
+ pdug5InputEnergyThresholdThUpperWarning INTEGER,
+ pdug5InputEnergyThresholdThUpperCritical INTEGER,
+ pdug5InputEnergyThresholdThResetThld INTEGER,
+ pdug5InputEnergyThresholdThChangeDelay INTEGER,
+ pdug5InputEnergyThresholdThCtrl INTEGER
+ }
+
+pdug5InputPhaseIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..3)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index for the pdug5InputEntry table."
+ ::= { pdug5InputPhaseEntry 1}
+
+pdug5InputPhaseVoltageMeasType OBJECT-TYPE
+ SYNTAX INTEGER {
+ singlePhase (1),
+ phase1toN (2),
+ phase2toN (3),
+ phase3toN (4),
+ phase1to2 (5),
+ phase2to3 (6),
+ phase3to1 (7)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Value indicates what input voltage is being measured in this table row - single phase
+ voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phase 1 to phase 2,
+ phase 2 to phase 3, or phase 3 to phase 1."
+ ::= { pdug5InputPhaseEntry 2 }
+
+pdug5InputPhaseVoltage OBJECT-TYPE
+ SYNTAX INTEGER -- UNITS RMS 0.1 V
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An input voltage measurement value. Values is in 0.1 V."
+ ::= {pdug5InputPhaseEntry 3}
+
+pdug5InputPhaseVoltageThStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ good (1),
+ lowWarning (2),
+ lowCritical (3),
+ highWarning (4),
+ highCritical (5)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Status of the measured input voltage relative to the configured thresholds."
+ ::= { pdug5InputPhaseEntry 4 }
+
+pdug5InputPhaseVoltageThLowerWarning OBJECT-TYPE
+ SYNTAX INTEGER (-1..500000) -- Units in 0.1 V
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Lower warning threshold. Units are 0.1 volts. A negative value indicates
+ that this object is not available."
+ ::= { pdug5InputPhaseEntry 5 }
+
+pdug5InputPhaseVoltageThLowerCritical OBJECT-TYPE
+ SYNTAX INTEGER (-1..500000) -- Units in 0.1 V
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Lower critical threshold. Units are 0.1 volts. A negative value indicates
+ that this object is not available."
+ ::= { pdug5InputPhaseEntry 6 }
+
+pdug5InputPhaseVoltageThUpperWarning OBJECT-TYPE
+ SYNTAX INTEGER (-1..500000) -- Units in 0.1 V
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Upper warning threshold. Units are 0.1 volts. A negative value indicates
+ that this object is not available."
+ ::= { pdug5InputPhaseEntry 7 }
+
+pdug5InputPhaseVoltageThUpperCritical OBJECT-TYPE
+ SYNTAX INTEGER (-1..500000) -- Units in 0.1 V
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Upper critical threshold. Units are 0.1 volts. A negative value indicates
+ that this object is not available."
+ ::= { pdug5InputPhaseEntry 8 }
+
+pdug5InputPhaseCurrentMeasType OBJECT-TYPE
+ SYNTAX INTEGER {
+ singlePhase (1),
+ neutral (2),
+ phase1 (3),
+ phase2 (4),
+ phase3 (5)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Which input wire is being measured in this table row - single phase, neutral, phase 1,
+ phase 2, or phase 3."
+ ::= { pdug5InputPhaseEntry 9 }
+
+pdug5InputPhaseCurrentRating OBJECT-TYPE
+ SYNTAX INTEGER -- Units in 0.01 A
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Rated current capacity of the input. A negative value indicates that
+ the hardware current capacity is unknown. Units are 0.01 amps."
+ ::= { pdug5InputPhaseEntry 10 }
+
+pdug5InputPhaseCurrent OBJECT-TYPE
+ SYNTAX INTEGER -- Units in 0.01 A
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An input current measurement value. Units are 0.01 amps."
+ ::= { pdug5InputPhaseEntry 11 }
+
+pdug5InputPhaseCurrentThStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ good (1),
+ lowWarning (2),
+ lowCritical (3),
+ highWarning (4),
+ highCritical (5)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Status of the measured input current relative to the configured thresholds."
+ ::= { pdug5InputPhaseEntry 12 }
+
+pdug5InputPhaseCurrentThLowerWarning OBJECT-TYPE
+ SYNTAX INTEGER (-1..100000) -- Units in 0.01 A
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Lower warning threshold. Units are 0.01 amps. A negative value indicates
+ that this object is not available."
+ ::= { pdug5InputPhaseEntry 13 }
+
+pdug5InputPhaseCurrentThLowerCritical OBJECT-TYPE
+ SYNTAX INTEGER (-1..100000) -- Units in 0.01 A
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Lower critical threshold. Units are 0.01 amps. A negative value indicates
+ that this object is not available."
+ ::= { pdug5InputPhaseEntry 14 }
+
+pdug5InputPhaseCurrentThUpperWarning OBJECT-TYPE
+ SYNTAX INTEGER (-1..100000) -- Units in 0.01 A
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Upper warning threshold. Units are 0.01 amps. A negative value indicates
+ that this object is not available."
+ ::= { pdug5InputPhaseEntry 15 }
+
+pdug5InputPhaseCurrentThUpperCritical OBJECT-TYPE
+ SYNTAX INTEGER (-1..100000) -- Units in 0.01 A
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Upper critical threshold. Units are 0.01 amps. A negative value indicates
+ that this object is not available."
+ ::= { pdug5InputPhaseEntry 16 }
+
+pdug5InputPhaseCurrentPercentLoad OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Current percent load, based on the rated current capacity. Units are
+ percentage, for example 80% will be returned as 80. A negative
+ value indicates that this object is not available."
+ ::= { pdug5InputPhaseEntry 17 }
+
+pdug5InputPhasePowerMeasType OBJECT-TYPE
+ SYNTAX INTEGER {
+ singlePhase (1),
+ neutral (2),
+ phase1 (3),
+ phase2 (4),
+ phase3 (5)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Which input wire is being measured in this table row - single phase, neutral, phase 1,
+ phase 2, or phase 3."
+ ::= { pdug5InputPhaseEntry 18 }
+
+pdug5InputPhasePowerVA OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An input VA value. Units are VA. A negative value indicates
+ that this object is not available."
+ ::= { pdug5InputPhaseEntry 19 }
+
+pdug5InputPhasePowerWatts OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An input Watts value. Units are Watts. A negative value indicates
+ that this object is not available."
+ ::= { pdug5InputPhaseEntry 20 }
+
+pdug5InputPhasePowerWattHour OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A Watt-Hour value for each Input phase. Units are WH. This value can be reset to 0
+ using GUI. In that case, the pdug5InputPhasePowerWattHourTimer will be reset as well
+ A negative value indicates that this object is not available."
+ ::= { pdug5InputPhaseEntry 21 }
+
+pdug5InputPhasePowerWattHourTimer OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..22)) -- display Date Time
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Timestamp of when input Watt-hours (inputWh) was last reset."
+ ::= { pdug5InputPhaseEntry 22 }
+
+pdug5InputPhasePowerFactor OBJECT-TYPE
+ SYNTAX INTEGER -- units 0.01
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An input PF value. Units are in thousandths, for example a power factor
+ of 0.95 would be returned as 95, and 0.92 would be returned
+ as 92. A negative value indicates that this object is not available."
+ ::= { pdug5InputPhaseEntry 23 }
+
+pdug5InputPhasePowerVAR OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An input VAR value. Units are VAR. A negative value indicates
+ that this object is not available."
+ ::= { pdug5InputPhaseEntry 24 }
+
+-- 1.3.6.1.4.1.19536.10.1.2.2.1.25
+pdug5InputPhaseVoltageThResetThld OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Input phase voltage alarm reset threshold. Units are 0.1 volts.
+ A negative value indicates that this object is not available."
+ DEFVAL { 0 }
+ ::= { pdug5InputPhaseEntry 25 }
+
+-- 1.3.6.1.4.1.19536.10.1.2.2.1.26
+pdug5InputPhaseVoltageThChangeDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Input phase voltage alarm change delay. Units are 0.1 volts.
+ A negative value indicates that this object is not available."
+ DEFVAL { 0 }
+ ::= { pdug5InputPhaseEntry 26 }
+
+-- 1.3.6.1.4.1.19536.10.1.2.2.1.27
+pdug5InputPhaseVoltageThCtrl OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Input phase voltage alarm threshold control:
+ bit 0: up critical alarm control bit, 0 - enable, 1 - disable
+ bit 1: up warning alarm control bit, 0 - enable, 1 - disable
+ bit 2: low warning alarm control bit, 0 - enable, 1 - disable
+ bit 3: low critical alarm control bit, 0 - enable, 1 - disable"
+ DEFVAL { 0 }
+ ::= { pdug5InputPhaseEntry 27 }
+
+-- 1.3.6.1.4.1.19536.10.1.2.2.1.28
+pdug5InputPhaseCurrentThResetThld OBJECT-TYPE
+ SYNTAX INTEGER (-1..100000) -- Units in 0.01 A
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Input phase current alarm reset threshold. Units are 0.01 amps.
+ A negative value indicates that this object is not available."
+ ::= { pdug5InputPhaseEntry 28 }
+
+-- 1.3.6.1.4.1.19536.10.1.2.2.1.29
+pdug5InputPhaseCurrentThChangeDelay OBJECT-TYPE
+ SYNTAX INTEGER (-1..100000) -- Units in 0.01 A
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Input phase current alarm change delay. Units are 0.01 amps.
+ A negative value indicates that this object is not available."
+ ::= { pdug5InputPhaseEntry 29 }
+
+-- 1.3.6.1.4.1.19536.10.1.2.2.1.30
+pdug5InputPhaseCurrentThCtrl OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Input phase current alarm threshold control:
+ bit 0: up critical alarm control bit, 0 - enable, 1 - disable
+ bit 1: up warning alarm control bit, 0 - enable, 1 - disable
+ bit 2: low warning alarm control bit, 0 - enable, 1 - disable
+ bit 3: low critical alarm control bit, 0 - enable, 1 - disable"
+ DEFVAL { 0 }
+ ::= { pdug5InputPhaseEntry 30 }
+
+pdug5InputPowerThresholdThLowerWarning OBJECT-TYPE
+ SYNTAX INTEGER (-1..500000) -- Units in W
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Lower warning Power threshold. Units are in Watts. A negative value indicates
+ that this object is not available."
+ ::= { pdug5InputPhaseEntry 31 }
+
+pdug5InputPowerThresholdThLowerCritical OBJECT-TYPE
+ SYNTAX INTEGER (-1..500000) -- Units in W
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Lower critical Power threshold. Units are in Watts. A negative value indicates
+ that this object is not available."
+ ::= { pdug5InputPhaseEntry 32 }
+
+pdug5InputPowerThresholdThUpperWarning OBJECT-TYPE
+ SYNTAX INTEGER (-1..500000) -- Units in W
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Upper warning Power threshold. Units are in Watts. A negative value indicates
+ that this object is not available."
+ ::= { pdug5InputPhaseEntry 33 }
+
+pdug5InputPowerThresholdThUpperCritical OBJECT-TYPE
+ SYNTAX INTEGER (-1..500000) -- Units in W
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Upper critical Power threshold. Units are in Watts. A negative value indicates
+ that this object is not available."
+ ::= { pdug5InputPhaseEntry 34 }
+
+pdug5InputPowerThresholdThResetThld OBJECT-TYPE
+ SYNTAX INTEGER (-1..100000) -- Units in W
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Power alarm reset threshold. Units are in Watts.
+ A negative value indicates that this object is not available."
+ ::= { pdug5InputPhaseEntry 35 }
+
+pdug5InputPowerThresholdThChangeDelay OBJECT-TYPE
+ SYNTAX INTEGER (-1..100000) -- Units in W
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Power alarm change delay. Units are in Watts.
+ A negative value indicates that this object is not available."
+ ::= { pdug5InputPhaseEntry 36 }
+
+pdug5InputPowerThresholdThCtrl OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Power alarm threshold control:
+ bit 0: up critical alarm control bit, 0 - enable, 1 - disable
+ bit 1: up warning alarm control bit, 0 - enable, 1 - disable
+ bit 2: low warning alarm control bit, 0 - enable, 1 - disable
+ bit 3: low critical alarm control bit, 0 - enable, 1 - disable"
+ DEFVAL { 0 }
+ ::= { pdug5InputPhaseEntry 37 }
+
+pdug5InputEnergyThresholdThUpperWarning OBJECT-TYPE
+ SYNTAX INTEGER (-1..500000) -- Units in W
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Upper warning Energy threshold. Units are in Watts. A negative value indicates
+ that this object is not available."
+ ::= { pdug5InputPhaseEntry 38 }
+
+pdug5InputEnergyThresholdThUpperCritical OBJECT-TYPE
+ SYNTAX INTEGER (-1..500000) -- Units in W
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Upper critical Energy threshold. Units are in Watts. A negative value indicates
+ that this object is not available."
+ ::= { pdug5InputPhaseEntry 39 }
+
+pdug5InputEnergyThresholdThResetThld OBJECT-TYPE
+ SYNTAX INTEGER (-1..100000) -- Units in W
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Energy alarm reset threshold. Units are in Watts.
+ A negative value indicates that this object is not available."
+ ::= { pdug5InputPhaseEntry 40 }
+
+pdug5InputEnergyThresholdThChangeDelay OBJECT-TYPE
+ SYNTAX INTEGER (-1..100000) -- Units in W
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Energy alarm change delay. Units are in Watts.
+ A negative value indicates that this object is not available."
+ ::= { pdug5InputPhaseEntry 41 }
+
+pdug5InputEnergyThresholdThCtrl OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Energy alarm threshold control:
+ bit 0: up critical alarm control bit, 0 - enable, 1 - disable
+ bit 1: up warning alarm control bit, 0 - enable, 1 - disable
+ bit 2: low warning alarm control bit, 0 - enable, 1 - disable
+ bit 3: low critical alarm control bit, 0 - enable, 1 - disable"
+ DEFVAL { 0 }
+ ::= { pdug5InputPhaseEntry 42 }
+
+-- ====================================================================================
+-- g5 OBJECT IDENTIFIER ::= { panduit 10}
+-- pdug5 OBJECT IDENTIFIER ::= { g5 1}
+-- pdug5Group OBJECT IDENTIFIER ::= { pdug5 3 }
+-- pdug5 Output groups of outlets
+-- OID= .1.3.6.1.4.1.19536.10.1.3
+
+pdug5GroupTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF pdug5GroupEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "Aggregate Object with number of entries equal to number of PDUs
+ and number of breakers (pdug5GroupCount)."
+ ::= { pdug5Group 1 }
+
+pdug5GroupEntry OBJECT-TYPE
+ SYNTAX pdug5GroupEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The input table entry containing the name, voltages, currents, power, etc."
+ INDEX { pdug5IdentIndex, pdug5GroupIndex }
+ ::= { pdug5GroupTable 1 }
+
+pdug5GroupEntry ::= SEQUENCE {
+ pdug5GroupIndex INTEGER,
+ pdug5GroupName DisplayString,
+ pdug5GroupType INTEGER,
+ pdug5GroupVoltageMeasType INTEGER,
+ pdug5GroupVoltage INTEGER,
+ pdug5GroupVoltageThStatus INTEGER,
+ pdug5GroupVoltageThLowerWarning INTEGER,
+ pdug5GroupVoltageThLowerCritical INTEGER,
+ pdug5GroupVoltageThUpperWarning INTEGER,
+ pdug5GroupVoltageThUpperCritical INTEGER,
+ pdug5groupCurrentRating INTEGER,
+ pdug5GroupCurrent INTEGER,
+ pdug5GroupCurrentThStatus INTEGER,
+ pdug5GroupCurrentThLowerWarning INTEGER,
+ pdug5GroupCurrentThLowerCritical INTEGER,
+ pdug5GroupCurrentThUpperWarning INTEGER,
+ pdug5GroupCurrentThUpperCritical INTEGER,
+ pdug5GroupCurrentPercentLoad INTEGER,
+ pdug5GroupPowerVA INTEGER,
+ pdug5GroupPowerWatts INTEGER,
+ pdug5GroupPowerWattHour INTEGER,
+ pdug5GroupPowerWattHourTimer DisplayString,
+ pdug5GroupPowerFactor INTEGER,
+ pdug5GroupPowerVAR INTEGER,
+ pdug5GroupOutletCount INTEGER,
+ pdug5GroupBreakerStatus INTEGER,
+ pdug5GroupVoltageThCtrl INTEGER,
+ pdug5GroupCurrentThCtrl INTEGER
+ }
+
+pdug5GroupIndex OBJECT-TYPE
+ SYNTAX INTEGER (0..12)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index for the pdug5GroupEntry table."
+ ::= { pdug5GroupEntry 1 }
+
+pdug5GroupName OBJECT-TYPE
+ SYNTAX DisplayString (SIZE(1..31))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A descriptive name for the group."
+ ::= { pdug5GroupEntry 2 }
+
+pdug5GroupType OBJECT-TYPE
+ SYNTAX INTEGER {
+ breaker1pole (2),
+ breaker2pole (3),
+ breaker3pole (4),
+ outletSection (5)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The type of the group. (5) has no breaker"
+ ::= { pdug5GroupEntry 3 }
+
+pdug5GroupVoltageMeasType OBJECT-TYPE
+ SYNTAX INTEGER {
+ singlePhase (1),
+ phase1toN (2),
+ phase2toN (3),
+ phase3toN (4),
+ phase1to2 (5),
+ phase2to3 (6),
+ phase3to1 (7)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Value indicates what input voltage is being measured in this table row - single phase
+ voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phase 1 to phase 2,
+ phase 2 to phase 3, or phase 3 to phase 1."
+ ::= { pdug5GroupEntry 4 }
+
+pdug5GroupVoltage OBJECT-TYPE
+ SYNTAX INTEGER -- Units 0.1 V
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Units are 0.1 volts."
+ ::= { pdug5GroupEntry 5 }
+
+pdug5GroupVoltageThStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ good (1),
+ lowWarning (2),
+ lowCritical (3),
+ highWarning (4),
+ highCritical (5)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Status of the measured group voltage relative to the configured thresholds."
+ ::= { pdug5GroupEntry 6 }
+
+pdug5GroupVoltageThLowerWarning OBJECT-TYPE
+ SYNTAX INTEGER (-1..500000) -- Units 0.1 V
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Lower warning threshold. Units are 0.1 volts. A negative value indicates
+ that this object is not available."
+ ::= { pdug5GroupEntry 7 }
+
+pdug5GroupVoltageThLowerCritical OBJECT-TYPE
+ SYNTAX INTEGER (-1..500000) -- Units 0.1 V
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Lower critical threshold. Units are 0.1 volts. A negative value indicates
+ that this object is not available."
+ ::= { pdug5GroupEntry 8 }
+
+pdug5GroupVoltageThUpperWarning OBJECT-TYPE
+ SYNTAX INTEGER (-1..500000) -- Units 0.1 V
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Upper warning threshold. Units are 0.1 volts. A negative value indicates
+ that this object is not available."
+ ::= { pdug5GroupEntry 9 }
+
+pdug5GroupVoltageThUpperCritical OBJECT-TYPE
+ SYNTAX INTEGER (-1..500000) -- Units 0.1 V
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Upper critical threshold. Units are 0.1 volts. A negative value indicates
+ that this object is not available."
+ ::= { pdug5GroupEntry 10 }
+
+pdug5groupCurrentRating OBJECT-TYPE
+ SYNTAX INTEGER -- Units 0.01 A
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Rated current capacity of the group. Units are 0.01 amps. A negative
+ value indicates that the hardware current capacity is unknown (it
+ will always be unknown for custom groups)."
+ ::= { pdug5GroupEntry 11 }
+
+pdug5GroupCurrent OBJECT-TYPE
+ SYNTAX INTEGER -- Units 0.01 A
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A group current measurement value. Units are 0.01 amps."
+ ::= { pdug5GroupEntry 12 }
+
+pdug5GroupCurrentThStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ good (1),
+ lowWarning (2),
+ lowCritical (3),
+ highWarning (4),
+ highCritical (5)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Status of the measured group current relative to the configured thresholds."
+ ::= { pdug5GroupEntry 13 }
+
+pdug5GroupCurrentThLowerWarning OBJECT-TYPE
+ SYNTAX INTEGER (-1..100000) -- Units 0.01 A
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Lower warning threshold. Units are 0.01 amps. A negative value indicates
+ that this object is not available."
+ ::= { pdug5GroupEntry 14 }
+
+pdug5GroupCurrentThLowerCritical OBJECT-TYPE
+ SYNTAX INTEGER (-1..100000) -- Units 0.01 A
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Lower critical threshold. Units are 0.01 amps. A negative value indicates
+ that this object is not available."
+ ::= { pdug5GroupEntry 15 }
+
+pdug5GroupCurrentThUpperWarning OBJECT-TYPE
+ SYNTAX INTEGER (-1..100000) -- Units 0.01 A
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Upper warning threshold. Units are 0.01 amps. A negative value indicates
+ that this object is not available."
+ ::= { pdug5GroupEntry 16 }
+
+pdug5GroupCurrentThUpperCritical OBJECT-TYPE
+ SYNTAX INTEGER (-1..100000) -- Units 0.01 A
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Upper critical threshold. Units are 0.01 amps. A negative value indicates
+ that this object is not available."
+ ::= { pdug5GroupEntry 17 }
+
+
+pdug5GroupCurrentPercentLoad OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Current percent load, based on the rated current capacity. Units are
+ percentage, for example 80% will be returned as 80. A negative
+ value indicates that this object is not available."
+ ::= { pdug5GroupEntry 18 }
+
+pdug5GroupPowerVA OBJECT-TYPE
+ SYNTAX INTEGER -- units in VA
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A group VA value. Units are VA. A negative value indicates
+ that this object is not available."
+ ::= { pdug5GroupEntry 19 }
+
+pdug5GroupPowerWatts OBJECT-TYPE
+ SYNTAX INTEGER -- units in Watt
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A group power value. Units are Watts. A negative value indicates
+ that this object is not available."
+ ::= { pdug5GroupEntry 20 }
+
+pdug5GroupPowerWattHour OBJECT-TYPE
+ SYNTAX INTEGER -- Units in Watt-Hour
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A Watt-Hour value for each section. Units are WH. This value can be reset to 0
+ using GUI. In that case, the pdug5GroupPowerWattHourTimer will be reset as well.
+ A negative value indicates that this object is not available."
+ ::= { pdug5GroupEntry 21 }
+
+pdug5GroupPowerWattHourTimer OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..22)) -- display Date and Time
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Timestamp of when group Watt-hours (groupWh) was last reset."
+ ::= { pdug5GroupEntry 22 }
+
+pdug5GroupPowerFactor OBJECT-TYPE
+ SYNTAX INTEGER -- Value is in 0.01
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A group PF value. Units are in thousandths, for example a power factor
+ of 0.95 would be returned as 95, and 0.92 would be returned as 92.
+ A negative value indicates that this object is not available."
+ ::= { pdug5GroupEntry 23 }
+
+pdug5GroupPowerVAR OBJECT-TYPE
+ SYNTAX INTEGER -- Units in VAR
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A group VAR value. Units are VAR. A negative value indicates
+ that this object is not available."
+ ::= { pdug5GroupEntry 24 }
+
+pdug5GroupOutletCount OBJECT-TYPE
+ SYNTAX INTEGER (0..48)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of outlets in each group (breaker)."
+ ::= { pdug5GroupEntry 25 }
+
+pdug5GroupBreakerStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ breakerOn (2),
+ breakerOff (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Only applicable to groups with breaker. Indicates whether a breaker is turned
+ off or on."
+ ::= { pdug5GroupEntry 26 }
+
+-- 1.3.6.1.4.1.19536.10.1.3.1.1.27
+pdug5GroupVoltageThCtrl OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Circuit Breaker voltage alarm threshold control:
+ bit 0: up critical alarm control bit, 0 - enable, 1 - disable
+ bit 1: up warning alarm control bit, 0 - enable, 1 - disable
+ bit 2: low warning alarm control bit, 0 - enable, 1 - disable
+ bit 3: low critical alarm control bit, 0 - enable, 1 - disable"
+ DEFVAL { 0 }
+ ::= { pdug5GroupEntry 27 }
+
+-- 1.3.6.1.4.1.19536.10.1.3.1.1.28
+pdug5GroupCurrentThCtrl OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Circuit Breaker current alarm threshold control:
+ bit 0: up critical alarm control bit, 0 - enable, 1 - disable
+ bit 1: up warning alarm control bit, 0 - enable, 1 - disable
+ bit 2: low warning alarm control bit, 0 - enable, 1 - disable
+ bit 3: low critical alarm control bit, 0 - enable, 1 - disable"
+ ::= { pdug5GroupEntry 28 }
+
+-- ====================================================================================
+-- g5 OBJECT IDENTIFIER ::= { panduit 10}
+-- pdug5 OBJECT IDENTIFIER ::= { g5 1}
+-- pdug5Environment OBJECT IDENTIFIER ::= { pdug5 4 }
+-- pdug5 Environment group
+-- PDU identification group
+-- OID= .1.3.6.1.4.1.19536.10.1.4
+
+pdug5EnvProbeTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF pdug5EnvProbeEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of environment probe (1 per PDU) for temperature, humidity, and contacts.
+ The number of entries is given by number of PDUs in daisy chain."
+ ::= { pdug5Environment 1 }
+
+pdug5EnvProbeEntry OBJECT-TYPE
+ SYNTAX pdug5EnvProbeEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Aggregate entries equal to number of PDUs."
+ INDEX { pdug5IdentIndex }
+ ::= { pdug5EnvProbeTable 1 }
+
+pdug5EnvProbeEntry ::= SEQUENCE {
+ pdug5TemperatureScale INTEGER,
+ pdug5TemperatureCount INTEGER,
+ pdug5HumidityCount INTEGER,
+ pdug5DoorCount INTEGER,
+ pdug5DryCount INTEGER,
+ pdug5SpotCount INTEGER,
+ pdug5RopeCount INTEGER,
+ pdug5HidCount INTEGER
+}
+
+pdug5TemperatureScale OBJECT-TYPE
+ SYNTAX INTEGER {
+ celsius (1),
+ fahrenheit (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Scale used to return temperature objects."
+ ::= { pdug5EnvProbeEntry 1 }
+
+pdug5TemperatureCount OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of temperature measurements.The MAX is 6 (1 per probe)."
+ ::= { pdug5EnvProbeEntry 2 }
+
+pdug5HumidityCount OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of humidity measurements.The MAX is 6(1 per probe)."
+ ::= { pdug5EnvProbeEntry 3 }
+
+pdug5DoorCount OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of door sensors.The MAX is 6(1 per probe)."
+ ::= { pdug5EnvProbeEntry 4 }
+
+pdug5DryCount OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of dry sensors.The MAX is 2(1 per probe)."
+ ::= { pdug5EnvProbeEntry 5 }
+
+pdug5SpotCount OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of spot sensors.The MAX is 2(1 per probe)."
+ ::= { pdug5EnvProbeEntry 6 }
+
+pdug5RopeCount OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of rope sensors.The MAX is 2(1 per probe)."
+ ::= { pdug5EnvProbeEntry 7 }
+
+pdug5HidCount OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of hid sensors. The MAX is 2(1 per probe)."
+ ::= { pdug5EnvProbeEntry 10 }
+
+-- ========Temperature Measurements ============
+
+pdug5TemperatureTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF pdug5TemperatureEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of temperature probe measurements. The number of entries are
+ given by number of pdu and pdug5TemperatureCount."
+ ::= { pdug5Environment 2 }
+
+pdug5TemperatureEntry OBJECT-TYPE
+ SYNTAX pdug5TemperatureEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry for a temperature measurement."
+ INDEX { pdug5IdentIndex, pdug5TemperatureIndex }
+ ::= { pdug5TemperatureTable 1 }
+
+pdug5TemperatureEntry ::= SEQUENCE {
+ pdug5TemperatureIndex INTEGER,
+ pdug5TemperatureName DisplayString,
+ pdug5TemperatureProbeStatus INTEGER,
+ pdug5TemperatureValue INTEGER,
+ pdug5TemperatureThStatus INTEGER,
+ pdug5TemperatureThLowerWarning INTEGER,
+ pdug5TemperatureThLowerCritical INTEGER,
+ pdug5TemperatureThUpperWarning INTEGER,
+ pdug5TemperatureThUpperCritical INTEGER,
+ pdug5TemperatureThCtrl INTEGER
+}
+
+pdug5TemperatureIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..6)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A unique value for each temperature probe measurement. Its value
+ ranges from 1 to temperatureCount."
+ ::= { pdug5TemperatureEntry 1 }
+
+pdug5TemperatureName OBJECT-TYPE
+ SYNTAX DisplayString (SIZE(1..31))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A descriptive name for the temperature probe."
+ ::= { pdug5TemperatureEntry 2 }
+
+pdug5TemperatureProbeStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ disconnected (1),
+ connected (2),
+ bad (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates whether a probe is connected or not."
+ ::= { pdug5TemperatureEntry 3 }
+
+pdug5TemperatureValue OBJECT-TYPE
+ SYNTAX INTEGER --0.1 Fahrenheit or Celsius
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Units are degree(either Fahrenheit or Celsius)."
+ ::= { pdug5TemperatureEntry 4 }
+
+
+pdug5TemperatureThStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ good (1),
+ lowWarning (2),
+ lowCritical (3),
+ highWarning (4),
+ highCritical (5)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Status of the measured temperature relative to the configured thresholds."
+ ::= { pdug5TemperatureEntry 5 }
+
+pdug5TemperatureThLowerWarning OBJECT-TYPE
+ SYNTAX INTEGER (-1..150000)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Lower warning threshold. Units are degrees. A negative value
+ indicates that this object is not available."
+ ::= { pdug5TemperatureEntry 6 }
+
+pdug5TemperatureThLowerCritical OBJECT-TYPE
+ SYNTAX INTEGER (-1..150000)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Lower critical threshold. Units are degrees. A negative value
+ indicates that this object is not available."
+ ::= { pdug5TemperatureEntry 7 }
+
+pdug5TemperatureThUpperWarning OBJECT-TYPE
+ SYNTAX INTEGER (-1..150000)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Upper warning threshold. Units are degrees. A negative value
+ indicates that this object is not available."
+ ::= { pdug5TemperatureEntry 8 }
+
+pdug5TemperatureThUpperCritical OBJECT-TYPE
+ SYNTAX INTEGER (-1..150000)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Upper critical threshold. Units are degrees. A negative value
+ indicates that this object is not available."
+ ::= { pdug5TemperatureEntry 9 }
+
+-- 1.3.6.1.4.1.19536.10.1.4.2.1.10
+pdug5TemperatureThCtrl OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Temperature alarm threshold control:
+ bit 0: up critical alarm control bit, 0 - enable, 1 - disable
+ bit 1: up warning alarm control bit, 0 - enable, 1 - disable
+ bit 2: low warning alarm control bit, 0 - enable, 1 - disable
+ bit 3: low critical alarm control bit, 0 - enable, 1 - disable"
+ DEFVAL { 0 }
+ ::= { pdug5TemperatureEntry 10 }
+
+-- ==========Humidity Measurements ==========
+
+pdug5HumidityTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF pdug5HumidityEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of humidity probe measurements. The number of entries are
+ given by number of pdu and pdug5HumidityCount."
+ ::= { pdug5Environment 3 }
+
+pdug5HumidityEntry OBJECT-TYPE
+ SYNTAX pdug5HumidityEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry for a humidity measurement."
+ INDEX { pdug5IdentIndex, pdug5HumidityIndex }
+ ::= { pdug5HumidityTable 1 }
+
+pdug5HumidityEntry ::= SEQUENCE {
+ pdug5HumidityIndex INTEGER,
+ pdug5HumidityName DisplayString,
+ pdug5HumidityProbeStatus INTEGER,
+ pdug5HumidityValue INTEGER,
+ pdug5HumidityThStatus INTEGER,
+ pdug5HumidityThLowerWarning INTEGER,
+ pdug5HumidityThLowerCritical INTEGER,
+ pdug5HumidityThUpperWarning INTEGER,
+ pdug5HumidityThUpperCritical INTEGER,
+ pdug5HumidityThCtrl INTEGER
+}
+
+pdug5HumidityIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..6)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A unique value for each humidity probe measurement. Its value
+ ranges from 1 to pdug5HumidityCount per PDU."
+ ::= { pdug5HumidityEntry 1 }
+
+pdug5HumidityName OBJECT-TYPE
+ SYNTAX DisplayString (SIZE(1..31))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A descriptive name for the humidity probe."
+ ::= { pdug5HumidityEntry 2 }
+
+pdug5HumidityProbeStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ disconnected (1),
+ connected (2),
+ bad (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates whether a probe is connected or not."
+ ::= { pdug5HumidityEntry 3 }
+
+pdug5HumidityValue OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Units are %RH."
+ ::= { pdug5HumidityEntry 4 }
+
+pdug5HumidityThStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ good (1),
+ lowWarning (2),
+ lowCritical (3),
+ highWarning (4),
+ highCritical (5)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Status of the measured humidity relative to the configured thresholds."
+ ::= { pdug5HumidityEntry 5 }
+
+pdug5HumidityThLowerWarning OBJECT-TYPE
+ SYNTAX INTEGER (-1..1000)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Lower warning threshold. Units are %RH. A negative value
+ indicates that this object is not available."
+ ::= { pdug5HumidityEntry 6 }
+
+pdug5HumidityThLowerCritical OBJECT-TYPE
+ SYNTAX INTEGER (-1..1000)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Lower critical threshold. Units are %RH. A negative value
+ indicates that this object is not available."
+ ::= { pdug5HumidityEntry 7 }
+
+pdug5HumidityThUpperWarning OBJECT-TYPE
+ SYNTAX INTEGER (-1..1000)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Upper warning threshold. Units are %RH. A negative value
+ indicates that this object is not available."
+ ::= { pdug5HumidityEntry 8 }
+
+pdug5HumidityThUpperCritical OBJECT-TYPE
+ SYNTAX INTEGER (-1..1000)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Upper critical threshold. Units are %RH. A negative value
+ indicates that this object is not available."
+ ::= { pdug5HumidityEntry 9 }
+
+-- 1.3.6.1.4.1.19536.10.1.4.3.1.10
+pdug5HumidityThCtrl OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Humidity alarm threshold control:
+ bit 0: up critical alarm control bit, 0 - enable, 1 - disable
+ bit 1: up warning alarm control bit, 0 - enable, 1 - disable
+ bit 2: low warning alarm control bit, 0 - enable, 1 - disable
+ bit 3: low critical alarm control bit, 0 - enable, 1 - disable"
+ DEFVAL { 0 }
+ ::= { pdug5HumidityEntry 10 }
+
+-- ======Door sensor Status==========
+
+pdug5DoorTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF pdug5DoorEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of door sensors. The number of entries are
+ given by number of PDU and pdug5DoorCount."
+ ::= { pdug5Environment 4 }
+
+pdug5DoorEntry OBJECT-TYPE
+ SYNTAX pdug5DoorEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry for a door sensor"
+ INDEX { pdug5IdentIndex, pdug5DoorIndex }
+ ::= { pdug5DoorTable 1 }
+
+pdug5DoorEntry ::= SEQUENCE {
+ pdug5DoorIndex INTEGER,
+ pdug5DoorName DisplayString,
+ pdug5DoorProbeStatus INTEGER,
+ pdug5DoorState INTEGER
+}
+
+pdug5DoorIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..2)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A unique value for each door sensor. Its value ranges from 1 to
+ doorCount."
+ ::= { pdug5DoorEntry 1 }
+
+pdug5DoorName OBJECT-TYPE
+ SYNTAX DisplayString (SIZE(1..31))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A descriptive name for the door sensor."
+ ::= { pdug5DoorEntry 2 }
+
+pdug5DoorProbeStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ disconnected (1),
+ connected (2),
+ bad (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates whether a probe is connected or not.
+ Will not be returned if the door sensor is internal to the ePDU,
+ in that case only doorState should be read."
+ ::= { pdug5DoorEntry 3 }
+
+pdug5DoorState OBJECT-TYPE
+ SYNTAX INTEGER {
+ doorOpen (1),
+ doorClosed (2),
+ BaddoorSensor (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The state of the door sensor."
+ ::= { pdug5DoorEntry 4 }
+
+
+-- ======Dry Sensor Status==========
+ -- 1.3.6.1.4.1.19536.10.1.4.5
+ pdug5DryTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF pdug5DryEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of dry sensors. The number of entries are
+ given by number of pdu and pdug5DryCount."
+ ::= { pdug5Environment 5 }
+
+
+
+ -- 1.3.6.1.4.1.19536.10.1.4.5.1
+ pdug5DryEntry OBJECT-TYPE
+ SYNTAX pdug5DryEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry for a contact sensor"
+ INDEX { pdug5IdentIndex, pdug5DryIndex }
+ ::= { pdug5DryTable 1 }
+
+
+ pdug5DryEntry ::=
+ SEQUENCE {
+ pdug5DryIndex
+ INTEGER,
+ pdug5DryName
+ DisplayString,
+ pdug5DryProbeStatus
+ INTEGER,
+ pdug5DryState
+ INTEGER
+ }
+
+
+ -- 1.3.6.1.4.1.19536.10.1.4.5.1.1
+ pdug5DryIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..2)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A unique value for each dry sensor. Its value ranges from 1 to
+ dryCount."
+ ::= { pdug5DryEntry 1 }
+
+
+
+ -- 1.3.6.1.4.1.19536.10.1.4.5.1.2
+ pdug5DryName OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (1..31))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A descriptive name for the dry sensor."
+ ::= { pdug5DryEntry 2 }
+
+
+
+ -- 1.3.6.1.4.1.19536.10.1.4.5.1.3
+ pdug5DryProbeStatus OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ disconnected(1),
+ connected(2),
+ bad(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates whether a probe is connected or not."
+ ::= { pdug5DryEntry 3 }
+
+
+
+ -- 1.3.6.1.4.1.19536.10.1.4.5.1.4
+ pdug5DryState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ good(1),
+ alarmed(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The state of the dry sensor."
+ ::= { pdug5DryEntry 4 }
+
+
+-- ====== Water Spot Sensor Status==========
+
+ -- 1.3.6.1.4.1.19536.10.1.4.6
+ pdug5SpotTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF pdug5SpotEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of contact sensors. The number of entries are
+ given by number of pdu and pdug5SpotCount."
+ ::= { pdug5Environment 6 }
+
+
+
+ -- 1.3.6.1.4.1.19536.10.1.4.6.1
+ pdug5SpotEntry OBJECT-TYPE
+ SYNTAX pdug5SpotEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry for a contact sensor"
+ INDEX { pdug5IdentIndex, pdug5SpotIndex }
+ ::= { pdug5SpotTable 1 }
+
+
+ pdug5SpotEntry ::=
+ SEQUENCE {
+ pdug5SpotIndex
+ INTEGER,
+ pdug5SpotName
+ DisplayString,
+ pdug5SpotProbeStatus
+ INTEGER,
+ pdug5SpotState
+ INTEGER
+ }
+
+
+ -- 1.3.6.1.4.1.19536.10.1.4.6.1.1
+ pdug5SpotIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..3)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A unique value for each spot sensor. Its value ranges from 1 to
+ spotCount."
+ ::= { pdug5SpotEntry 1 }
+
+
+
+ -- 1.3.6.1.4.1.19536.10.1.4.6.1.2
+ pdug5SpotName OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (1..31))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A descriptive name for the spot sensor."
+ ::= { pdug5SpotEntry 2 }
+
+
+ -- 1.3.6.1.4.1.19536.10.1.4.6.1.3
+ pdug5SpotProbeStatus OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ disconnected(1),
+ connected(2),
+ bad(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates whether a probe is connected or not."
+ ::= { pdug5SpotEntry 3 }
+
+
+ -- 1.3.6.1.4.1.19536.10.1.4.6.1.4
+ pdug5SpotState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ noleak(1),
+ leak(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The state of the spot sensor."
+ ::= { pdug5SpotEntry 4 }
+
+
+-- ======Water Rope Sensor Status==========
+ -- 1.3.6.1.4.1.19536.10.1.4.7
+ pdug5RopeTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF pdug5RopeEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of rope sensors. The number of entries are
+ given by number of pdu and pdug5RopeCount."
+ ::= { pdug5Environment 7 }
+
+
+ -- 1.3.6.1.4.1.19536.10.1.4.7.1
+ pdug5RopeEntry OBJECT-TYPE
+ SYNTAX pdug5RopeEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry for a contact sensor"
+ INDEX { pdug5IdentIndex, pdug5RopeIndex }
+ ::= { pdug5RopeTable 1 }
+
+
+ pdug5RopeEntry ::=
+ SEQUENCE {
+ pdug5RopeIndex
+ INTEGER,
+ pdug5RopeName
+ DisplayString,
+ pdug5RopeProbeStatus
+ INTEGER,
+ pdug5RopeState
+ INTEGER
+ }
+
+ -- 1.3.6.1.4.1.19536.10.1.4.7.1.1
+ pdug5RopeIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..3)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A unique value for each rope sensor. Its value ranges from 1 to
+ ropeCount."
+ ::= { pdug5RopeEntry 1 }
+
+
+ -- 1.3.6.1.4.1.19536.10.1.4.7.1.2
+ pdug5RopeName OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (1..31))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A descriptive name for the rope sensor."
+ ::= { pdug5RopeEntry 2 }
+
+
+ -- 1.3.6.1.4.1.19536.10.1.4.7.1.3
+ pdug5RopeProbeStatus OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ disconnected(1),
+ connected(2),
+ bad(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates whether a probe is connected or not."
+ ::= { pdug5RopeEntry 3 }
+
+
+ -- 1.3.6.1.4.1.19536.10.1.4.7.1.4
+ pdug5RopeState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ noleak(1),
+ leak(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The state of the rope sensor."
+ ::= { pdug5RopeEntry 4 }
+
+ -- 1.3.6.1.4.1.19536.10.1.4.10
+ pdug5EnvHID OBJECT IDENTIFIER ::= { pdug5Environment 10 }
+
+
+-- ======Hid Sensor Status==========
+ -- 1.3.6.1.4.1.19536.10.1.4.10.1
+ pdug5EnvHidTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF pdug5EnvHidEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of contact sensors. The number of entries are
+ given by number of pdu and pdug5HidCount."
+ ::= { pdug5EnvHID 1 }
+
+
+ -- 1.3.6.1.4.1.19536.10.1.4.10.1.1
+ pdug5EnvHidEntry OBJECT-TYPE
+ SYNTAX pdug5EnvHidEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry for a contact sensor"
+ INDEX { pdug5IdentIndex, pdug5HIDIndex }
+ ::= { pdug5EnvHidTable 1 }
+
+
+ pdug5EnvHidEntry ::=
+ SEQUENCE {
+ pdug5HIDIndex
+ INTEGER,
+ pdug5HidAisle
+ INTEGER,
+ pdug5HidHandleOperation
+ INTEGER
+ }
+
+ -- 1.3.6.1.4.1.19536.10.1.4.10.1.1.1
+ pdug5HIDIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..2)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of the PDU HID table entry"
+ ::= { pdug5EnvHidEntry 1 }
+
+
+
+ -- 1.3.6.1.4.1.19536.10.1.4.10.1.1.2
+ pdug5HidAisle OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ COLD(1),
+ HOT(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Aisle of HID handle. "
+ ::= { pdug5EnvHidEntry 2 }
+ -- 1.3.6.1.4.1.19536.10.1.4.10.1.1.3
+ pdug5HidHandleOperation OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ unlock(1),
+ lock(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "HID handle control opterations "
+ ::= { pdug5EnvHidEntry 3 }
+ -- 1.3.6.1.4.1.19536.10.1.4.10.1.1.4
+ pduHIDVer OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..63))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The firmware revision level of the HID"
+ ::= { pdug5EnvHidEntry 4 }
+ -- 1.3.6.1.4.1.19536.10.1.4.10.1.1.5
+ pdug5MechanicalLock OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ unlock(1),
+ lock(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "HID Mechanical opterations "
+ ::= { pdug5EnvHidEntry 5 }
+-- ======Hid hid control table==========
+ -- 1.3.6.1.4.1.19536.10.1.4.10.2
+ pdug5EnvHidControlTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF pdug5EnvHidControlEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of smartcard. The number of entries are
+ given by number of pdu and pdug5HidCount."
+ ::= { pdug5EnvHID 2 }
+
+
+ -- 1.3.6.1.4.1.19536.10.1.4.10.2.1
+ pdug5EnvHidControlEntry OBJECT-TYPE
+ SYNTAX pdug5EnvHidControlEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The smartcard table entry containing the usrname, cardid, cardaisle etc."
+ INDEX { pdug5IdentIndex, pdug5HidControlIndex }
+ ::= { pdug5EnvHidControlTable 1 }
+
+
+ pdug5EnvHidControlEntry ::=
+ SEQUENCE {
+ pdug5HidControlIndex INTEGER,
+ pdug5HidControlUserName DisplayString,
+ pdug5HidControlCardID INTEGER,
+ pdug5HidControlTimestamp DisplayString,
+ pdug5HidControlCardAisle INTEGER
+ }
+ -- 1.3.6.1.4.1.19536.10.1.4.10.2.1.1
+ pdug5HidControlIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..2)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of the PDU smartcard table entry"
+ ::= { pdug5EnvHidControlEntry 1 }
+ -- 1.3.6.1.4.1.19536.10.1.4.10.2.1.2
+ pdug5HidControlUserName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "User name of smartcard"
+ ::= { pdug5EnvHidControlEntry 2 }
+
+ -- 1.3.6.1.4.19536.10.1.4.10.2.1.3
+ pdug5HidControlCardID OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "HID smartcard ID."
+ ::= { pdug5EnvHidControlEntry 3 }
+
+ -- 1.3.6.1.4.19536.10.1.4.10.2.1.4
+ pdug5HidControlTimestamp OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the date and time of accessing"
+ ::= { pdug5EnvHidControlEntry 4 }
+
+
+ -- 1.3.6.1.4.19536.10.1.4.10.2.1.5
+ pdug5HidControlCardAisle OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ COLD(1),
+ HOT(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Aisle of authorized card. "
+ ::= { pdug5EnvHidControlEntry 5 }
+
+-- ====================================================================================
+-- g5 OBJECT IDENTIFIER ::= { panduit 10}
+-- pdug5 OBJECT IDENTIFIER ::= { g5 1}
+-- pdug5Outlet OBJECT IDENTIFIER ::= { pdug5 5 }
+-- OID= .1.3.6.1.4.1.19536.10.1.5
+
+pdug5OutletTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF pdug5OutletEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Aggregate Object with number of entries equal to Number of PDU (pdug5IdentIndex)
+ and Number of outlet per PDU (pdug5OutletIndex)."
+ ::= { pdug5Outlet 1 }
+
+pdug5OutletEntry OBJECT-TYPE
+ SYNTAX pdug5OutletEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The Outlet table entry containing the type, voltage, current etc."
+ INDEX { pdug5IdentIndex, pdug5OutletIndex }
+ ::= { pdug5OutletTable 1 }
+
+pdug5OutletEntry ::= SEQUENCE {
+ pdug5OutletIndex INTEGER,
+ pdug5OutletName DisplayString,
+ pdug5OutletType INTEGER,
+ pdug5OutletCurrentRating INTEGER,
+ pdug5OutletCurrent INTEGER,
+ pdug5OutletActivePowerThStatus INTEGER,
+ pdug5OutletActivePowerThLowerWarning INTEGER,
+ pdug5OutletActivePowerThLowerCritical INTEGER,
+ pdug5OutletActivePowerThUpperWarning INTEGER,
+ pdug5OutletActivePowerThUpperCritical INTEGER,
+ pdug5OutletCurrentPercentLoad INTEGER,
+ pdug5OutletVA INTEGER,
+ pdug5OutletWatts INTEGER,
+ pdug5OutletWh INTEGER,
+ pdug5OutletWhTimer DisplayString,
+ pdug5OutletPowerFactor INTEGER,
+ pdug5OutletVAR INTEGER,
+ pdug5OutletBranch INTEGER,
+ pdug5OutletActivePowerThResetThld INTEGER,
+ pdug5OutletActivePowerThChangeDelay INTEGER,
+ pdug5OutletActivePowerThCtrl INTEGER
+}
+
+pdug5OutletIndex OBJECT-TYPE
+ SYNTAX INTEGER (0..48)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index for each outlet, value from 1 to the number of outlets per PDU."
+ ::= { pdug5OutletEntry 1 }
+
+pdug5OutletName OBJECT-TYPE
+ SYNTAX DisplayString (SIZE(1..31))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A descriptive name for the outlet."
+ ::= { pdug5OutletEntry 2 }
+
+pdug5OutletType OBJECT-TYPE
+ SYNTAX INTEGER {
+ iecC13 (1),
+ iecC19 (2),
+ i5-20R (3),
+ uk (10),
+ french (11),
+ schuko (12),
+ nema515 (20),
+ nema51520 (21),
+ nema520 (22),
+ nemaL520 (23),
+ nemaL530 (24),
+ nema615 (25),
+ nema620 (26),
+ nemaL620 (27),
+ nemaL630 (28),
+ nemaL715 (29),
+ rf203p277 (30)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Type of this outlet - C13, C19 ,5-20R."
+ ::= { pdug5OutletEntry 3 }
+
+pdug5OutletCurrentRating OBJECT-TYPE
+ SYNTAX INTEGER -- Units 0.01 A
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Rated current capacity of this outlet. Units are 0.01 amps. A negative
+ value indicates that the hardware current capacity is unknown."
+ ::= { pdug5OutletEntry 4 }
+
+pdug5OutletCurrent OBJECT-TYPE
+ SYNTAX INTEGER -- Units 0.01 A
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A outlet current measurement value. Units are 0.01 amps."
+ ::= { pdug5OutletEntry 5 }
+
+pdug5OutletActivePowerThStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ good (1),
+ lowWarning (2),
+ lowCritical (3),
+ highWarning (4),
+ highCritical (5)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Status of the measured outlet active power relative to the configured thresholds."
+ ::= { pdug5OutletEntry 6 }
+
+pdug5OutletActivePowerThLowerWarning OBJECT-TYPE
+ SYNTAX INTEGER (-1..10000)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Lower warning threshold. Units are Watts(W). A negative value indicates
+ that this object is not available."
+ ::= { pdug5OutletEntry 7 }
+
+pdug5OutletActivePowerThLowerCritical OBJECT-TYPE
+ SYNTAX INTEGER (-1..10000)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Lower critical threshold. Units are Watts(W). A negative value indicates
+ that this object is not available."
+ ::= { pdug5OutletEntry 8 }
+
+pdug5OutletActivePowerThUpperWarning OBJECT-TYPE
+ SYNTAX INTEGER (-1..10000)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Upper warning threshold. Units are Watts(W). A negative value indicates
+ that this object is not available."
+ ::= { pdug5OutletEntry 9 }
+
+pdug5OutletActivePowerThUpperCritical OBJECT-TYPE
+ SYNTAX INTEGER (-1..10000)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Upper critical threshold. Units are Watts(W). A negative value indicates
+ that this object is not available."
+ ::= { pdug5OutletEntry 10 }
+
+
+pdug5OutletCurrentPercentLoad OBJECT-TYPE
+ SYNTAX INTEGER -- unit in percentage
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Current percent load, based on the rated current capacity. Units are
+ percentage, for example 80% will be returned as 80. A negative
+ value indicates that this object is not available."
+ ::= { pdug5OutletEntry 11 }
+
+pdug5OutletVA OBJECT-TYPE
+ SYNTAX INTEGER -- units in VA
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A outlet VA value. Units are VA. A negative value indicates
+ that this object is not available."
+ ::= { pdug5OutletEntry 12 }
+
+pdug5OutletWatts OBJECT-TYPE
+ SYNTAX INTEGER -- units in Watt
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A outlet Watts value. Units are Watts. A negative value indicates
+ that this object is not available."
+ ::= { pdug5OutletEntry 13 }
+
+pdug5OutletWh OBJECT-TYPE
+ SYNTAX INTEGER -- Units in Watt-Hour
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A Watt-Hour value for each outlet. Units are WH.
+This object is writable so that it can be reset to 0. When it is
+ written to, the pdug5OutletWhTimer will be reset updated as well
+ A negative value indicates that this object is not available."
+ ::= { pdug5OutletEntry 14 }
+
+pdug5OutletWhTimer OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..22)) -- display Date and Time
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Timestamp (date and time) of outlet Watt-hours was last reset."
+ ::= { pdug5OutletEntry 15 }
+
+pdug5OutletPowerFactor OBJECT-TYPE
+ SYNTAX INTEGER -- units are in 0.01
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An outlet PF value. Units are in thousandths, for example a power factor
+ of 0.95 would be returned as 95, and 0.92 would be returned
+ as 92. A negative value indicates that this object is not available."
+ ::= { pdug5OutletEntry 16 }
+
+pdug5OutletVAR OBJECT-TYPE
+ SYNTAX INTEGER -- Units in VAR
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An outlet VAR value. Units are VAR. A negative value indicates
+ that this object is not available."
+ ::= { pdug5OutletEntry 17 }
+
+pdug5OutletBranch OBJECT-TYPE
+ SYNTAX INTEGER -- Units in VAR
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The branch number outlet located."
+ ::= { pdug5OutletEntry 18 }
+
+-- 1.3.6.1.4.1.19536.10.1.5.1.1.19
+pdug5OutletActivePowerThResetThld OBJECT-TYPE
+ SYNTAX INTEGER (-1..10000)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Outlet Active Power alarm reset threshold. Units are Watts(W).
+ A negative value indicates that this object is not available."
+ ::= { pdug5OutletEntry 19 }
+
+-- 1.3.6.1.4.1.19536.10.1.5.1.1.20
+pdug5OutletActivePowerThChangeDelay OBJECT-TYPE
+ SYNTAX INTEGER (-1..10000)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Outlet Active Power generates alarm every outlet alarm times.
+ A negative value indicates that this object is not available."
+ ::= { pdug5OutletEntry 20 }
+
+-- 1.3.6.1.4.1.19536.10.1.5.1.1.21
+pdug5OutletActivePowerThCtrl OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Outlet Active Power alarm threshold control:
+ bit 0: up critical alarm control bit, 0 - enable, 1 - disable
+ bit 1: up warning alarm control bit, 0 - enable, 1 - disable
+ bit 2: low warning alarm control bit, 0 - enable, 1 - disable
+ bit 3: low critical alarm control bit, 0 - enable, 1 - disable"
+ DEFVAL { 0 }
+ ::= { pdug5OutletEntry 21 }
+
+-- ====================== PDU Outlet Control=====================
+
+pdug5OutletControlTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF pdug5OutletControlEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Aggregate Object with number of entries equal to Number of PDU (pdug5IdentIndex)
+ and Number of outlets per PDU (pdug5OutletIndex)."
+ ::= { pdug5Outlet 2 }
+
+pdug5OutletControlEntry OBJECT-TYPE
+ SYNTAX pdug5OutletControlEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The Outlet table entry containing the type, voltage, current etc."
+ INDEX { pdug5IdentIndex, pdug5OutletIndex }
+ ::= { pdug5OutletControlTable 1 }
+
+pdug5OutletControlEntry ::= SEQUENCE {
+
+ pdug5OutletControlStatus INTEGER,
+ pdug5OutletControlOffCmd INTEGER,
+ pdug5OutletControlOnCmd INTEGER,
+ pdug5OutletControlRebootCmd INTEGER,
+ pdug5OutletControlPowerOnState INTEGER,
+ pdug5OutletControlSequenceDelay INTEGER,
+ pdug5OutletControlRebootOffTime INTEGER,
+ pdug5OutletControlSwitchable INTEGER,
+ pdug5OutletControlShutoffDelay INTEGER,
+ pdug5OutletControlCommand INTEGER
+}
+
+pdug5OutletControlStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ off (1),
+ on (2),
+ pendingOff (3),
+ pendingOn (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "current state of a control outlet."
+ ::= { pdug5OutletControlEntry 1 }
+
+pdug5OutletControlOffCmd OBJECT-TYPE
+ SYNTAX INTEGER (-1..99999)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "When write, once issued, the outlet will turn Off immediately.
+ 0-n: Time in seconds until the outlet command is issued
+ -1: Cancel a pending outlet Off command
+ When read, returns -1 if no command is pending, or the current downcount in
+ seconds of a pending command."
+ ::= { pdug5OutletControlEntry 2 }
+
+pdug5OutletControlOnCmd OBJECT-TYPE
+ SYNTAX INTEGER (-1..99999)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "When write, once issued, the outlet will turn On immediately.
+ 0-n: Time in seconds until the outlet command is issued
+ -1: Cancel a pending outlet On command
+ When read, returns -1 if no command is pending, or the current downcount in
+ seconds of a pending command."
+ ::= { pdug5OutletControlEntry 3 }
+
+pdug5OutletControlRebootCmd OBJECT-TYPE
+ SYNTAX INTEGER (-1..99999)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "When write, for outlets that are On prior to this Reboot command, they will
+ switch Off immediately when the command is issued, remain Off for
+ outletControlRebootOffTime seconds, and then turn back On.
+ For outlets that are Off prior to the Reboot command, they will turn On after
+ a delay of outletControlRebootOffTime seconds from when the command is issued.
+ 0-n : Time in seconds until the Reboot command is issued
+ -1 : Cancel a pending outlet Reboot command
+
+ When read, returns -1 if no command is pending, or the current downcount in
+ seconds of a pending command."
+ ::= { pdug5OutletControlEntry 4 }
+
+pdug5OutletControlPowerOnState OBJECT-TYPE
+ SYNTAX INTEGER {
+ off (1),
+ on (2),
+ lastState (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Determines the outlet state when power is applied to the unit.
+ 1 : not restart at device startup
+ 2 : should sequence back ON in line with outletControlSequenceTime
+ 3 : should take the state the outlet had when power was lost.
+ If the state was ON, should sequence back ON in line with outletControlSequenceTime."
+ ::= { pdug5OutletControlEntry 5 }
+
+pdug5OutletControlSequenceDelay OBJECT-TYPE
+ SYNTAX INTEGER (-1..7200)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Time delay in seconds from when a Global Sequence On command is issued to
+ when the command is executed on this outlet. This delay is also used as a power-on
+ delay. Set to -1 to exclude this outlet from Global Sequence On commands."
+ ::= { pdug5OutletControlEntry 6 }
+
+pdug5OutletControlRebootOffTime OBJECT-TYPE
+ SYNTAX INTEGER (-1..7200)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Time delay in seconds that the outlet should remain in the Off state when executing a Reboot command."
+ ::= { pdug5OutletControlEntry 7 }
+
+pdug5OutletControlSwitchable OBJECT-TYPE
+ SYNTAX INTEGER {
+ switchable (1),
+ notSwitchable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Determines the outlet capability to be controlled On/Off from the communication channels.
+ 1 : control On/Off enabled
+ 2 : control On/Off disabled."
+ ::= { pdug5OutletControlEntry 8 }
+
+pdug5OutletControlShutoffDelay OBJECT-TYPE
+ SYNTAX INTEGER (-1..7200)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Time delay in seconds that could be taken in account before shutting of the outlet.
+ An application which need to shutoff properly an outlet will read this parameter first
+ then write it to the command pdug5OutletControlOffCmd."
+ ::= { pdug5OutletControlEntry 9 }
+
+
+pdug5OutletControlCommand OBJECT-TYPE
+ SYNTAX INTEGER {
+ immediateOff (1),
+ immediateOn (2),
+ delayedOff (3),
+ delayedOn (4),
+ immediateReboot (5),
+ delayedReboot (6),
+ outletUnknown (7)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Getting this variable will return the outlet state.
+ If the outlet is on, the immediateOn (2)
+ value will be returned. If the outlet is off,
+ the immediateOff (1) value will be returned.
+ If the state of the outlet cannot be determined, the
+ outletUnknown (7) value will be returned. If the
+ outletUnknown condition should occur, all devices
+ powered by the PDU should be shut down. The PDU's
+ power should then be cycled to clear this condition.
+ Setting this variable to immediateOn (2) will immediately
+ turn the outlet on. Setting this variable to
+ immediateOff (1) will immediately turn the outlet off.
+ Setting this variable to immediateReboot (5)
+ will cause the Switched PDU to perform an immediateOff
+ command, wait the pdug5OutletControlRebootOffTime
+ OID time, and then perform an immediateOn command.
+ Setting this variable to delayedOn (4) will turn the
+ outlet on after the pdug5OutletControlSequenceDelay
+ OID time has elapsed. Setting this variable to
+ delayedOff (3) will turn the outlet off after the
+ pdug5OutletControlShutoffDelay OID time has elapsed.
+ Setting this variable to delayedReboot (6) will cause
+ the Switched PDU to perform a delayedOff command, wait
+ the pdug5OutletControlRebootOffTime OID time, and
+ then perform a delayedOn command."
+ ::= { pdug5OutletControlEntry 10 }
+
+-- ====================================================================================
+-- g5 OBJECT IDENTIFIER ::= { panduit 10}
+-- pdug5 OBJECT IDENTIFIER ::= { g5 1}
+-- pdug5Traps OBJECT IDENTIFIER ::= { pdug5 6 }
+-- PDU identification group
+-- OID= .1.3.6.1.4.1.19536.10.1.6
+
+trapCritical NOTIFICATION-TYPE
+ OBJECTS {
+ trapCode,
+ trapDescription,
+ sysDescr,
+ pdug5IPv4Address}
+ STATUS current
+ DESCRIPTION
+ "A critical alarm has occurred."
+ ::= {pdug5Traps 1}
+
+trapWarning NOTIFICATION-TYPE
+ OBJECTS {
+ trapCode,
+ trapDescription,
+ sysDescr,
+ pdug5IPv4Address }
+ STATUS current
+ DESCRIPTION
+ "A warning alarm has occurred."
+ ::= {pdug5Traps 2}
+
+trapInformation NOTIFICATION-TYPE
+ OBJECTS {
+ trapCode,
+ trapDescription,
+ sysDescr,
+ pdug5IPv4Address }
+ STATUS current
+ DESCRIPTION
+ "An informational alarm has occurred."
+ ::= {pdug5Traps 3}
+
+trapCleared NOTIFICATION-TYPE
+ OBJECTS {
+ trapCode,
+ trapDescription,
+ sysDescr,
+ pdug5IPv4Address }
+ STATUS current
+ DESCRIPTION
+ "An alarm has cleared."
+ ::= {pdug5Traps 4}
+
+trapTest NOTIFICATION-TYPE
+ OBJECTS {
+ trapCode,
+ trapDescription,
+ sysDescr,
+ pdug5IPv4Address }
+ STATUS current
+ DESCRIPTION
+ "Test trap sent to a trap receiver to check proper reception of traps"
+ ::= {pdug5Traps 5}
+
+-- ====================================================================================
+-- g5 OBJECT IDENTIFIER ::= { panduit 10}
+-- pdug5 OBJECT IDENTIFIER ::= { g5 1}
+-- pdug5TrapInfo OBJECT IDENTIFIER ::= { pdug5 7 }
+-- PDU identification group
+-- OID= .1.3.6.1.4.1.19536.10.1.7
+
+pdug5TrapInfoEntry OBJECT IDENTIFIER ::= { pdug5TrapInfo 1 }
+
+trapCode OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A number identifying the event for the trap that was sent."
+ ::= { pdug5TrapInfoEntry 1 }
+
+trapDescription OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..255))
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A string identifying the event for that last trap that was sent."
+ ::= { pdug5TrapInfoEntry 2 }