diff --git a/MIBS/apc/PowerNet-MIB b/MIBS/apc/PowerNet-MIB new file mode 100644 index 0000000..39f9498 --- /dev/null +++ b/MIBS/apc/PowerNet-MIB @@ -0,0 +1,86003 @@ +-- ************************************************************************* +-- AMERICAN POWER CONVERSION PowerNet-MIB +-- ************************************************************************* +-- Copyright (c) 2020 American Power Conversion, Inc. +-- PowerNet is a Trademark of American Power Conversion Corp. +-- +-- Title: APC TOP LEVEL PowerNet MIB +-- +-- Version : 4.3.6 +-- +-- Generated by script: tomib.awk +-- +-- Input File: powernetPS.mib +-- +-- Created: Saturday, September, 19, 2020 +-- +-- Revision History: +-- ************************************************************************* + +-- - v3.2.0 Added functionality for MasterSwitch Plus
+-- - v3.3.0 Added functionality for MX28B (dcDM3) and 3-phase UPS
+-- - v3.3.2 New traps for Symmetra PX UPS
+-- 07/15/01 - v3.4.0 Added transfer switch
+-- - v3.4.3 Added functionality for External and Integrated Environmental Monitor
+-- 06/14/02 - v3.4.4 Added dcmim2(Siemens) branch, Battery Manager(Reading) traps, and
+-- Psx Traps for PDU and RM-PDU and Netlock branch/traps
+-- 12/13/02 - v3.5.0 netlock - Initial support for netlock (nl). Traps 261-265 added.
+-- rPDU - Initial support for rPDU. Traps 266-283 added.
+-- rARU - Initial support for rARU.
+-- gateway - Initial support for gateway (gw). Traps 230-260, 284-297 added.
+-- ups - upsSyncCtrlGroup and upsState sections added.
+-- 02/19/03 - v3.6.0 ups - UpsOutletGroups section added. Traps 298-299 added.
+-- smw - Traps 300-305 added.
+-- rPDU - General OID description cleanups.
+-- gw - Updated SNMP support for gw.
+-- 05/21/03 - v3.6.1 ups - Updated SNMP support for ups.
+-- ems - Environmental Management System OIDs renamed from gateway (gw).
+-- raru - Updated SNMP support for raru.
+-- 06/13/03 - v3.6.3 airFM - Initial support for airFM. Traps 306-311 added.
+-- nl - Traps 261-265 removed.
+-- 11/26/03 - v3.6.4 xPDU - Initial support for xPDU. Traps 312-344 added.
+-- airPA - Initial support for airPA. Traps 306-311 modified for airPA use.
+-- airFM - AirFMStatus OIDs cleaned up.
+-- 03/19/04 - v3.6.5 rPDU - Updated SNMP support for rPDU.
+-- airFM - AirFMGroup section added.
+-- 05/13/04 - v3.6.6 ups - Added several upsAdvBattery OIDs.
+-- ems - Added emsStatusHardwareStatus and emsHardwareState traps 345-346.
+-- aru - Trap 228 redefined to aruDeviceConfigChange.
+-- 08/04/04 - v3.6.7 ups - Added upsAdvConfigNumExternalBatteries and
+-- upsAdvConfigSimpleSignalShutdowns.
+-- ce - Custom Event traps 347-352 added.
+-- 11/22/04 - v3.6.8 ems - Many emsProbeConfig and emsProbeStatus OIDs added.
+-- ups - Traps 353-358 added.
+-- env - Traps 359-374 added.
+-- 01/26/05 - v3.6.9 battman - Initial support for battman, traps 375-380 added.
+-- xATS - Initial support for xATS, traps 381-478 added.
+-- generator - Initial support for generator.
+-- rPDU - Trap edits.
+-- xPDU - Trap edits.
+-- 05/26/05 - v3.7.0 consolePortServer - Initial support for consolePortServer (cpsAP930x).
+-- xPDU - Cleaned up many descriptions.
+-- xATS - Cleaned up many descriptions.
+-- ups - Added several upsAdvConfig OIDs.
+-- 09/28/05 - v3.8.0 modEnvMgr - Initial support for modEnvMgr (mem).
+-- rARU - Added functionality for Gen 2 ARU.
+-- ups/aru/mem - Traps 500-569 added.
+-- all - General cleanup on typos and spelling errors.
+-- 01/04/06 - v3.8.1 rARU - Added functionality for Gen 2 ARU
+-- 02/22/06 - v3.8.2 accessControl - Initial support for accessControl.
+-- Traps 570-592 added.
+-- accessPX - Initial support for accessPX.
+-- airIR - Initial support for airIR and airIRAlarms.
+-- airIRRC - Initial support for airIRRC.
+-- 05/24/06 - v3.8.4 apcLocalDisplay - Initial support for apcLocalDisplay.
+-- ups - UpsAdvOutputRedundancy, upsAdvOutputKVACapacity,
+-- upsAdvConfigBasicSignalLowBatteryDuration, and
+-- upsAdvConfigBypassPhaseLockRequired OIDs added.
+-- UpsAdvConfigMinReturnRuntime SYNTAX changed.
+-- UPS trap numbers 600-623 added.
+-- em - New emConfigProbe, emConfigContact, emStatusProbe OIDs added.
+-- iem - New iemConfigProbe, iemConfigContact, iemStatusProbe OIDs added.
+-- 08/31/06 - v3.8.5 airIRSC - Initial support for airIRSC.
+-- XPDU - XPDUBranchBreaker OIDs and xPDUBranchCurrent traps added.
+-- 11/03/06 - v3.8.6 rPDU - Updated SNMP support for rPDU.
+-- accessPX - accessPXConfigCardFormat OID added.
+-- airIRSC - airIRSCUnitStatusCompressor added.
+-- 01/03/07 - v3.8.7 airIRRP - Initial support for airIRRP100 and airIRRP500.
+-- 04/06/07 - v3.8.8 battMan - Updated SNMP support for Battery Manager,
+-- battManConfigApplication OID deprecated.
+-- airIRRP - Added HeatAssistEnable to airIRRP100 and airIRRP500.
+-- ups - Added several upsDiagSubSys OIDs.
+-- iem - Added iemStatusProbeLocation OID.
+-- all - Cleaned up version history section.
+-- 12/19/07 - v3.9.1 airFM - Added full SNMP support, deprecating some existing OIDs in
+-- favor of new structure.
+-- 12/19/07 - v3.9.2 Added new OIDs for isxModularDistribution, isxModularPdu, airInRoomPerimeter
+-- airIRGen2, symmetraPX IDs, isxServers IDs, upsAdvConfig, upsDiagSubSysNetworkComCard,
+-- memInputsCommStatus, airIRRP100GroupSetpoints. Added new SNMP Traps for
+-- ISX Modular Distribution, and xATS.
+-- 08/13/08 - v3.9.3 Added new OIDs for UPS HighPrec OIDs:
+-- upsHighPrecBattery, upsHighPrecInput, and upsHighPrecOutput.
+-- Added new OIDs for the 10kW the AIR IR Gen2:
+-- airIRG2RDT2ConfigUnitRoleOverride, airIRG2RDT2RunHoursUnit,
+-- airIRG2GroupConfigNumberofBackupUnits, airIRG2GroupConfigRuntimeBalancingEnable,
+-- and airIRG2GroupConfigLoadAssistEnable for use by 10kW application.
+-- Added new traps apcInternalCommunicationFault and apcInternalCommunicationFaultCleared
+-- for use by the SUMX application.
+-- Updated descriptions in existing OIDs.
+-- 09/25/08 - v3.9.4 Added new OIDs for Symmetra PX:
+-- upsParallelSystem, upsPhysicalLayout, upsAdvConfigMainsSetting, upsAdvConfigACWiringSetting,
+-- upsAdvConfigUpperOutputVoltTolerance, upsAdvConfigLowerOutputVoltTolerance, upsAdvConfigUpperBypassVoltTolerance
+-- upsAdvConfigLowerBypassVoltTolerance, upsAdvConfigOutofSyncBypassTransferDelay, upsAdvTestDiagnosticTime
+-- upsAdvTestDiagnosticDay, upsDiagSwitchGearBypassInputSwitchStatus, upsDiagSubFeedBreakerTable,
+-- upsDiagSubFeedBreakerTable, upsSideCarFrameLayoutTable, upsPowerFrameLayoutTable
+-- Added new OIDs for UPSs:
+-- upsBasicSystemStatus, upsAdvControlFlashAndBeep (appended new list options)
+-- Added new OIDs for the AC RP10kW:
+-- airIRG2RDT2ConfigUnitIdleOnCoolFail
+-- Added new OID for isxModularPDU device:
+-- isxModularPduDeviceTransformerPresent (appended new list option)
+-- 02/24/09 - v3.9.5 Added new OIDs for the UPS Integrated ATS product, Air IRSC product, added new Traps for UPS support
+-- and fixed MIB compilier warnings.
+-- 02/24/09 - v3.9.6 Added new Traps and mtrapargs for the ISXC Trap Notification support.
+-- 09/18/09 - v3.9.8 Added new OIDs for the InRoom C7000 Air product.
+-- 04/14/10 - v3.9.9 Added new rPDU2 device and modified some rPDU OIDs.
+-- 06/22/10 - v4.0.0 Added traps 638 through 651 to support ATS.
+-- Updated control OIDs for rPDU2g
+-- Updates to support PX100kW UPS.
+-- Added traps 756 and 757 to support PX100kW UPS.
+-- Added upsAdvBattery, upsHighPrecBattery, and upsDiagBattery OIDs to support PX250kW/PX500kW UPS.
+-- 06/30/10 - v4.0.1 Added new OID's upsAdvBatteryFullCapacity, upsAdvInputNominalFrequency, upsAdvInputNominalVoltage,
+-- upsAdvInputBypassNominalFrequency, upsAdvInputBypassNominalVoltage, upsBasicSystemInternalTemperature,
+-- upsAdvOutputNominalFrequency, upsAdvOutputActivePower and upsAdvOutputApparentPower.
+-- Added traps 734 to 739 to support Galaxy 300 and Galaxy 7000 UPS.
+-- Added SyOid's galaxy300UPS10kVA33, galaxy300UPS15kVA33, galaxy300UPS20kVA33,
+-- galaxy300UPS30kVA33, galaxy300UPS40kVA33, galaxy300UPS10kVA31, galaxy300UPS15kVA31,
+-- galaxy300UPS20kVA31 and galaxy300UPS30kVA31,galaxy7000UPS200kVA,galaxy7000UPS250kVA,
+-- galaxy7000UPS300kVA,galaxy7000UPS400kVA,galaxy7000UPS500kVA,galaxy7000SSC800kVA,
+-- galaxy7000SSC1200kVA and galaxy7000SSC2000kVA.
+-- 10/27/10 - v4.0.2 Added Idle on Cool Fail and Fan Speed Control OIDs for the InRow ACRC.
+-- Added new OID's for Odin UPS upsAdvInputStatisticsTable, upsAdvInputApparentPower,
+-- upsAdvInputVoltageTHD, upsAdvInputBypassVoltageTHD, upsAdvInputPeakCurrent, upsAdvInputBypassPeakCurrent,
+-- upsAdvOutputStatisticsTable, upsAdvOutputPeakCurrent, upsAdvOutputCurrentTHD, upsAdvOutputCrestFactor,
+-- upsAdvStateTotaltimeonbattery, upsAdvStateTotaltimeonbypass, upsAdvStateTotaltimeonNormal,
+-- upsAdvStateNumberoftimesonbattery, upsAdvStateNumberoftimesbypass, upsAdvStateNumberoftimesNormal,
+-- subfeedBreakerUpperAcceptPowerCritical, upsParallelInputMaximumCurrent, upsParallelTotalOutputPower,
+-- upsParallelTotalOutputApparentPower, upsParallelInputCurrent, upsParallelInputActivePower,
+-- upsParallelInputApparentPower, upsParallelInputVoltage, upsParallelInputMaxVoltage,
+-- upsParallelInputMaxCurrent, upsParallelInputTotalActivePower, upsParallelInputTotalApparentPower,
+-- upsParallelOutputCurrent, upsParallelOutputLoad, upsParallelOutputPercentLoad, upsParallelOutputPower,
+-- upsParallelOutputApparentPower, upsParallelDiagSubSysBreakerStatus, upsParallelDiagSubSysBreakerName
+-- and upsParallelOutputTotalPercentLoad.
+-- Modified the OID upsAdvConfigOutputFreqRange and upsParallelSysRedundancy.
+-- 01/13/11 - v4.0.3 Added new oids, upsHighPrecOutputEfficiency and upsHighPrecOutputEnergyUsage.
+-- Added green mode for bit 51 of upsBasicStateOutputState.
+-- Added traps 758 to 763 to support UPS firmware update.
+-- Deprecated all OIDs off branch mfiletransfer
+-- Added rPDU2 Metered Outlet Data
+-- 08/17/11 - v4.0.4 Updated several rPDU2 and rPDU OIDs.
+-- 12/07/11 - v4.0.5 Added new OID's for SYPX upsPhaseOutputPowerFactor and symmetraPxDisplay.
+-- Added SYS OID's for different Caphorn models galaxy5000UPS20KVA, galaxy5000UPS30KVA, galaxy5000UPS40KVA
+-- galaxy5000UPS50KVA, galaxy5000UPS60KVA , galaxy5000UPS80KVA, galaxy5000UPS100KVA, galaxy5000UPS120KVA
+-- galaxy5000UPS130KVA, galaxy5500UPS20KVA, galaxy5500UPS30KVA, galaxy5500UPS40KVA, galaxy5500UPS50KVA
+-- galaxy5500UPS60KVA, galaxy5500UPS80KVA, galaxy5500UPS100KVA, galaxy5500UPS120KVA, galaxy5500UPS130KVA
+-- and new OID upsAdvStateEcomode
+-- 06/05/12 - v4.0.6 Added new OID rPDUIdentDeviceLineToNeutralVoltage for AP7823 Rack PDU.
+-- 06/20/12 - v4.0.6 Added new rPDU2Group OID table for AP84xx, AP86xx, AP88xx, AP89xx Rack PDUs.
+-- 08/10/12 - v4.0.6 Added new OIDs for SYPX 250/500 upsAdvConfigWarningAlarmDelay, upsAdvConfigInformationalAlarmDelay, upsDiagSwitchGearInstallationLoadPct,
+-- upsParallelOutputActivePowerTable,upsParallelSysSwitchGearInstallationLoadPct, upsParallelSysRedundancyStatus and upsParallelSysName.
+-- Modified the description for upsBasicBatteryLastReplaceDate and bit 51 of upsBasicStateOutputState.
+-- Updated upsBasicOutputStatus and upsBasicSystemStatus.
+-- 08/10/12 - v4.0.6 Added SYS OIDs for different Caphorn models galaxy9000UPS, galaxy9000SSC, galaxy9000UPSWithSSC, galaxy9000FreqConverter, eps6000UPS,
+-- eps6000SSC, eps6000UPSWithSSC, eps6000FreqConverter, eps7000UPS, eps7000SSC, eps7000UPSWithSSC,
+-- eps7000FreqConverter, eps8000UPS, eps8000SSC, eps8000UPSWithSSC, eps8000FreqConverter.
+-- Modified the description for bits 53 to 56 of upsBasicStateOutputState.
+-- 02/22/13 -v4.0.8 Added OIDs upsAdvBatteryInternalSKU, upsAdvBatteryExternalSKU, upsAdvBatteryRecommendedReplaceDate,
+-- upsAdvConfigGreenMode, upsAdvConfigLCDLocalLanguage, upsAdvConfigLCDLockOut,
+-- upsAdvConfigChargerRate, and upsAdvConfigBatterySelection for the SUMX application.
+-- 04/10/13 -v4.0.9 Added new SYS OID for sPDU masterSwitchsPDU
+-- 10/18/13 -v4.1.0 Added new cooling section of OIDs for second generation cooling products.
+-- 02/17/14 -v4.1.1 Added the OIDs for Valhal(Galaxy VM)UPS.
+-- 08/11/14 -v4.1.2 Added upsHighPrecBatteryPacks category.
+-- Added upsHighPrecInputBypassVoltage and upsHighPrecInputBypassFrequency OIDs.
+-- Added traps upsLocalDisplayButtonFault, upsLocalDisplayButtonFaultCleared, upsNeedsFactorySetupFault,
+-- upsNeedsFactorySetupFaultCleared, upsEPOActive, upsEPOActiveCleared, upsFirmwareMismatch, upsFirmwareMismatchCleared,
+-- upsOscillatorFailed, and upsOscillatorFailedCleared
+-- Updated the description for upsHighPrecOutputEfficiency to display all currently defined error conditions.
+-- 11/25/14 -v4.1.4 Changes for IRRP100 and IRRP500:
+-- 1.New OIDs added to support Active Flow Controller:
+-- airIRRP100GroupStatusActiveFlowControlStatus, airIRRP100GroupSetpointsActiveFlowControlBias, airIRRP100GroupConfigNumberOfActiveFlowControllers,
+-- airIRRP100GroupConfigActiveFlowControllerLampTest, airIRRP100GroupConfigAltitudeUS, airIRRP100GroupConfigAltitudeMetric,
+-- airIRRP500GroupStatusActiveFlowControlStatus, airIRRP500GroupSetpointsActiveFlowControlBias, airIRRP500GroupConfigNumberOfActiveFlowControllers,
+-- airIRRP500GroupConfigActiveFlowControllerLampTest, airIRRP500GroupConfigAltitudeUS, airIRRP500GroupConfigAltitudeMetric.
+-- 2.Updated OIDs airIRRP100GroupConfigConfigurationType and airIRRP500GroupConfigConfigurationType to support CACS strategy.
+-- 3.Added OIDs airIRRP100UnitConfigSecondaryPowerFeedCapability and airIRRP500UnitConfigSecondaryPowerFeedCapability
+-- to support secondary power feed capability.
+-- 4.Added OIDs airIRRP100UnitConfigIdleOnCoolFail and airIRRP500UnitConfigIdleOnCoolFail to support Idle on Cool Fail setting.
+-- 5.Added OIDs airIRRP100GroupStatusDewPointTempUS, airIRRP100GroupStatusDewPointTempMetric, airIRRP500GroupStatusDewPointTempUS
+-- and airIRRP500GroupStatusDewPointTempMetric to support the group dew point temperature.
+-- 6.Added OIDs airIRRP100UnitStatusLeakSensor and airIRRP500UnitStatusLeakSensor to support leak sensor status.
+-- 05/06/15 -v4.1.5 Added configurable contact OID rPDU2DeviceConfigContact.
+-- Added enums for the chargerSpotmode, inverterSpotmode state in upsBasicOutputStatus OID and StaticBypassStandby state in the upsBasicSystemStatus OID.
+-- Added new OIDs to support Active Flow Controller for airIRSC:
+-- airIRSCGroupConfigNumberOfActiveFlowControllers, airIRSCGroupConfigActiveFlowControllerLampTest,
+-- airIRSCGroupStatusActiveFlowControlStatus, airIRSCGroupSetpointsActiveFlowControlBias, airIRSCUnitStatusLeakSensor
+-- 07/13/15 -v4.1.6 Changes for airIR Gen2 RD:
+-- 1. Updated airIRG2GroupConfigConfigurationType to support CACS strategy.
+-- 2. Added airIRG2RDT2StatusLeakSensor to support leak sensor status.
+-- 3. Added OIDs to support Active Flow Controller:
+-- airIRG2GroupStatusActiveFlowControlStatus,airIRG2GroupSetpointsActiveFlowControlBias,airIRG2GroupConfigNumberOfActiveFlowControllers,
+-- airIRG2GroupConfigActiveFlowControllerLampTest,airIRG2GroupConfigAltitudeUS,airIRG2GroupConfigAltitudeMetric.
+-- 08/05/15 -v4.1.7 Changes for SUMX and SY:
+-- 1. Added upsAdvConfigBatteryHealthAlarmWarningTime and upsAdvConfigBatteryHealthAlarmSleepTime OIDs.
+-- 2. Added upsDCOutput OIDs to support UPSes with DC outputs
+-- 3. Added upsOnBatteryDueToFault and upsOnBatteryDueToFaultCleared for Symmetra UPSes.
+-- 04/27/16 -v4.1.8 Changes for Galaxy VX:
+-- 1. Added SYSOIDs for various models of Galaxy VX galaxyVXUPS500kVA, galaxyVXUPS625kVA, galaxyVXUPS750kVA, galaxyVXUPS1000kVA,
+-- galaxyVXUPS1250kVA and galaxyVXUPS1500kVA
+-- 2. Added New OIDs upsAdvInputEnergyUsage, upsAdvOutputEnergyUsage, upsDiagnosticPowerCabinet and upsDiagSwitchgearAmbientTemperature.
+-- 3. Replaced the options "batteryBreaker1" and "batteryBreaker2" from "switchgearBreakerType" in OID upsDiagSwitchGearBreakerTable with
+-- "batteryBreaker" and "bypassBackFeedBreaker".
+-- 05/11/16 -v4.1.8 Added SYSOID for Air Economizer.
+-- 07/01/16 -v4.1.9 Added support for PowerChute Network Shutdown.
+-- 08/18/16 -v4.2.0 Added description "Minor or Environment Alarm" for bit 60 of OID upsBasicStateOutputState.
+-- 09/08/16 -v4.2.0 Added support for AP7xxxB series Rack PDUs
+-- 09/08/16 -v4.2.0 Added the following tables for NB250:
+-- 1.emsInputStateSensorConfig, emsInputStateSensorStatus, memInputStateSensors
+-- 2.Added wireless entry under environmentalMonitor.
+-- 09/30/16 -v4.2.1 Changes for SUMX:
+-- Added upsAdvConfigSignalFlashVoltage and upsAdvConfigBatteryTemperatureCompensation.
+-- Added upsIntegratedUIO and subtree upsOutputRelays.
+-- Added configuration oids for universal input / output ports and associated sensors.
+-- Added upsHighPrecBatteryHealth.
+-- Added upsOutletGroupStatusGroupFullState in upsOutletGroupStatusTable.
+-- Added trap for temporary bypass.
+-- Updated fault list for upsDCOutputStatusAbnormalConditions.
+-- 01/24/17 -v4.2.2 Changes for G300: Added Oids upsAdvConfigBatteryChargerType, upsAdvConfigAutomaticRestart, upsAdvConfigDeepDischargeProtection,
+-- upsAdvConfigFreqBypassTransferRange, upsAdvConfigUpsPowerconverterType, upsAdvConfigFrequencyConverterMode,upsEcoModeSetting,
+-- upsEcoModeFreqTransferRange, upsEcoModeHighVoltThreshold, upsEcoModeLowVoltThreshold,upsParallelNumOfUpsPoweringLoad,
+-- upsParallelMinNumOfRequiredUps.
+-- 08/03/2017 Changed the range value for xPDUSystemOutputOverCurrentThreshold and xPDUSystemOutputOverCurrentNeutralThreshold
+-- from 100 to 110 to maintain consistency across all interfaces.
+-- 03/24/17 Changes for Galaxy VX and Galaxy VM
+-- Added the options NiCd and Li-Ion to upsAdvConfigBatterySelection.
+-- 03/31/2017 -v4.2.3 Changes for NB250:
+-- Added new card option to accessPXConfigCardFormat.
+-- 08/02/2017 -v4.2.4 Changes for G7000: Added new oid's to support EBM and ECO modes and upsAdvBatteryNominalBackupTime.
+-- 11/13/2017 Changes for NB250: Added oid's memSensorsTemperatureHighPrec, memOutputStatusAlarmState, memOutletStatusAlarmState, memBeaconStatusAlarmState,
+-- wirelessSensorStatusLocation, wirelessSensorStatusAlarmStatus, wirelessSensorPodStatusLocation, wirelessSensorPodStatusAlarmStatus,
+-- wirelessSensorConfigLocation, wirelessSensorPodConfigLocation.
+-- 3/2/2018 -v4.2.7 Corrected OBJECT-TYPE and DESCRIPTION for airIRRP500UnitThresholdsSupplyHumidityHigh and airIRRP500UnitThresholdsSupplyHumidityLow to
+-- airIRRP500UnitThresholdsReturnHumidityHigh and airIRRP500UnitThresholdsReturnHumidityLow.
+-- 9/11/2018 -v4.2.8 Added oid's upsHighPrecBatteryPackOnlyTableSize, upsHighPrecBatteryPackOnlyIndex, upsHighPrecBatteryPackOnlyFirmwareRevision,
+-- upsHighPrecBatteryPackOnlySerialNumber, upsHighPrecBatteryPackOnlyTemperature, upsHighPrecBatteryPackOnlyStatus, upsHighPrecBatteryPackOnlyHealth,
+-- upsHighPrecBatteryPackOnlyReplaceDate, upsHighPrecBatteryPackOnlyInstallDate.
+-- 01/31/2019 -v4.2.9 Added a new SYSOID for galaxyVXUPS1100kVA for Galaxy VX.
+-- 02/15/2019 -v4.3.0 Added oid's rPDU2IdentBootMonitorRev,rPDU2IdentLongDescription,rPDU2IdentNMCSerialNumber,rPDU2DevicePropertiesDevicePowerRating
+-- rPDU2OutletSwitchedConfigExternalLink,rPDU2OutletSwitchedStatusExternalLink,rPDU2OutletMeteredConfigExternalLink,rPDU2OutletMeteredStatusReceptacleType,
+-- rPDU2OutletMeteredStatusExternalLink.
+-- 03/11/2019 Added oid upsAdvConfigACQualificationTime.
+-- 10/29/2019 Added oid upsHighPrecExtdBatteryTemperature.
+-- Added traps upsInputContactOutputRelayFault, upsInputContactOutputRelayFaultCleared, upsAirFilterWarning, upsAirFilterWarningCleared
+-- upsBatteryPackIncompatible, upsBatteryPackIncompatibleCleared, upsInputContactAbnormal, upsInputContactAbnormalCleared,
+-- upsOutputRelayAbnormal, upsOutputRelayAbnormalCleared.
+-- 05/12/2020 Modified the description for atsOutputPower and atsOutputBankPower OIDs.
+-- 08/27/2020 Changed oid upsEnergyEfficiencyStatsTimeSinceReset to upsEnergyEfficiencyStatsOutputEnergyTimeSinceReset and modified the description
+-- Modified the descriptions for oids upsEnergyEfficiencyStatsTimeInECOmode and upsEnergyEfficiencyStatsTimeInECOnversion
+-- Added oids upsEnergyEfficiencyStatsInputEnergyTimeSinceReset, upsEnergyEfficiencyStatsECOmodeTimeSinceReset
+-- and upsEnergyEfficiencyStatsECOnversionTimeSinceReset
+-- Modified the description for oid upsBasicIdentName
+
+-- ********************************************************************************************
+-- ********************************************************************************************
+-- PowerNet-MIB { iso org(3) dod(6) internet(1) private(4)
+-- enterprises(1) apc(318) }
+
+PowerNet-MIB DEFINITIONS ::= BEGIN
+
+IMPORTS
+ enterprises, IpAddress, Gauge, TimeTicks FROM RFC1155-SMI
+ DisplayString FROM RFC1213-MIB
+ SnmpAdminString FROM SNMP-FRAMEWORK-MIB
+ OBJECT-TYPE FROM RFC-1212
+ TRAP-TYPE FROM RFC-1215;
+-- IMPORTS End
+
+apc OBJECT IDENTIFIER ::= { enterprises 318 }
+
+products OBJECT IDENTIFIER ::= { apc 1 }
+apcmgmt OBJECT IDENTIFIER ::= { apc 2 }
+
+hardware OBJECT IDENTIFIER ::= { products 1 }
+software OBJECT IDENTIFIER ::= { products 2 }
+system OBJECT IDENTIFIER ::= { products 3 }
+experimental OBJECT IDENTIFIER ::= { products 4 }
+
+mconfig OBJECT IDENTIFIER ::= { apcmgmt 1 }
+mcontrol OBJECT IDENTIFIER ::= { apcmgmt 2 }
+mtrapargs OBJECT IDENTIFIER ::= { apcmgmt 3 }
+mfiletransfer OBJECT IDENTIFIER ::= { apcmgmt 4 }
+
+mconfigClock OBJECT IDENTIFIER ::= { mconfig 6 }
+
+mfiletransferStatus OBJECT IDENTIFIER ::= { mfiletransfer 1 }
+mfiletransferConfig OBJECT IDENTIFIER ::= { mfiletransfer 2 }
+mfiletransferControl OBJECT IDENTIFIER ::= { mfiletransfer 3 }
+
+mfiletransferConfigSettings OBJECT IDENTIFIER ::= { mfiletransferConfig 1 }
+mfiletransferConfigTFTP OBJECT IDENTIFIER ::= { mfiletransferConfig 2 }
+mfiletransferConfigFTP OBJECT IDENTIFIER ::= { mfiletransferConfig 3 }
+
+ups OBJECT IDENTIFIER ::= { hardware 1 }
+measureUps OBJECT IDENTIFIER ::= { hardware 2 }
+miniSNMPadapter OBJECT IDENTIFIER ::= { hardware 3 }
+masterswitch OBJECT IDENTIFIER ::= { hardware 4 }
+masterswitchVM OBJECT IDENTIFIER ::= { hardware 5 }
+masterswitchMSP OBJECT IDENTIFIER ::= { hardware 6 }
+dcDM3 OBJECT IDENTIFIER ::= { hardware 7 }
+automaticTransferSwitch OBJECT IDENTIFIER ::= { hardware 8 }
+dc2 OBJECT IDENTIFIER ::= { hardware 9 }
+environmentalMonitor OBJECT IDENTIFIER ::= { hardware 10 }
+netlock OBJECT IDENTIFIER ::= { hardware 11 }
+rPDU OBJECT IDENTIFIER ::= { hardware 12 }
+airConditioners OBJECT IDENTIFIER ::= { hardware 13 }
+rARU OBJECT IDENTIFIER ::= { hardware 14 }
+xPDU OBJECT IDENTIFIER ::= { hardware 15 }
+battMan OBJECT IDENTIFIER ::= { hardware 16 }
+xATS OBJECT IDENTIFIER ::= { hardware 17 }
+generator OBJECT IDENTIFIER ::= { hardware 18 }
+consolePortServer OBJECT IDENTIFIER ::= { hardware 19 }
+accessControl OBJECT IDENTIFIER ::= { hardware 20 }
+apcLocalDisplay OBJECT IDENTIFIER ::= { hardware 21 }
+isxModularDistribution OBJECT IDENTIFIER ::= { hardware 22 }
+isxModularPdu OBJECT IDENTIFIER ::= { hardware 23 }
+
+
+universalInputOutput OBJECT IDENTIFIER ::= { hardware 25 }
+
+rPDU2 OBJECT IDENTIFIER ::= { hardware 26 }
+
+
+cooling OBJECT IDENTIFIER ::= { hardware 27 }
+
+powerManagementModule OBJECT IDENTIFIER ::= { hardware 28 }
+
+charger OBJECT IDENTIFIER ::= { hardware 29 }
+
+ePDU OBJECT IDENTIFIER ::= { hardware 30 }
+
+
+powerNetSubAgent OBJECT IDENTIFIER ::= { software 1 }
+
+struxureWareOperations OBJECT IDENTIFIER ::= { software 2 }
+
+powerChuteNetworkShutdown OBJECT IDENTIFIER ::= { software 3 }
+
+powerChuteBusinessEdition OBJECT IDENTIFIER ::= { software 4 }
+
+
+struxureWareOperationsStatus OBJECT IDENTIFIER ::= { struxureWareOperations 1 }
+
+powerNetSoftwareSystem OBJECT IDENTIFIER ::= { powerNetSubAgent 1 }
+powerNetSoftwareConfig OBJECT IDENTIFIER ::= { powerNetSubAgent 2 }
+
+backUPS OBJECT IDENTIFIER ::= { system 1 }
+smartUPS OBJECT IDENTIFIER ::= { system 2 }
+matrixUPS OBJECT IDENTIFIER ::= { system 3 }
+masterSwitch OBJECT IDENTIFIER ::= { system 4 }
+symmetraUPS OBJECT IDENTIFIER ::= { system 5 }
+dp100E OBJECT IDENTIFIER ::= { system 6 }
+dp300E OBJECT IDENTIFIER ::= { system 7 }
+monitors OBJECT IDENTIFIER ::= { system 8 }
+redundantSwitch OBJECT IDENTIFIER ::= { system 9 }
+dcPower OBJECT IDENTIFIER ::= { system 10 }
+automaticXferSwitch OBJECT IDENTIFIER ::= { system 11 }
+netLock OBJECT IDENTIFIER ::= { system 12 }
+symmetra3PhaseUPS OBJECT IDENTIFIER ::= { system 13 }
+networkAir OBJECT IDENTIFIER ::= { system 14 }
+infraStruXurePDU OBJECT IDENTIFIER ::= { system 15 }
+ais5000UPS OBJECT IDENTIFIER ::= { system 16 }
+smartUPS3Phase OBJECT IDENTIFIER ::= { system 17 }
+battManager OBJECT IDENTIFIER ::= { system 18 }
+infraStruXureATS OBJECT IDENTIFIER ::= { system 19 }
+conPortServ OBJECT IDENTIFIER ::= { system 20 }
+gutor OBJECT IDENTIFIER ::= { system 21 }
+accControl OBJECT IDENTIFIER ::= { system 22 }
+symmetraPX OBJECT IDENTIFIER ::= { system 23 }
+isxModDistribution OBJECT IDENTIFIER ::= { system 24 }
+isxServers OBJECT IDENTIFIER ::= { system 25 }
+smartUPS2 OBJECT IDENTIFIER ::= { system 27 }
+galaxy OBJECT IDENTIFIER ::= { system 28 }
+
+eps OBJECT IDENTIFIER ::= { system 30 }
+
+pcns OBJECT IDENTIFIER ::= { system 31 }
+
+
+
+pcbe OBJECT IDENTIFIER ::= { system 33 }
+
+pmm OBJECT IDENTIFIER ::= { system 34 }
+
+
+rpp OBJECT IDENTIFIER ::= { system 35 }
+
+
+battManIdent OBJECT IDENTIFIER ::= { battMan 1 }
+battManSystemCalib OBJECT IDENTIFIER ::= { battMan 2 }
+battManUnitCalib OBJECT IDENTIFIER ::= { battMan 3 }
+battManStringCalib OBJECT IDENTIFIER ::= { battMan 4 }
+battManBatteryCalib OBJECT IDENTIFIER ::= { battMan 5 }
+battManConfig OBJECT IDENTIFIER ::= { battMan 6 }
+battManAlarm OBJECT IDENTIFIER ::= { battMan 7 }
+battManSystemStatus OBJECT IDENTIFIER ::= { battMan 8 }
+battManStringStatus OBJECT IDENTIFIER ::= { battMan 9 }
+battManBatteryStatus OBJECT IDENTIFIER ::= { battMan 10 }
+battManInputContactStatus OBJECT IDENTIFIER ::= { battMan 11 }
+battManControl OBJECT IDENTIFIER ::= { battMan 12 }
+battManTestResults OBJECT IDENTIFIER ::= { battMan 13 }
+battManUnitStatus OBJECT IDENTIFIER ::= { battMan 14 }
+
+xPDUIdent OBJECT IDENTIFIER ::= { xPDU 1 }
+xPDUDevice OBJECT IDENTIFIER ::= { xPDU 2 }
+xPDUACMonitoringPoint OBJECT IDENTIFIER ::= { xPDU 3 }
+xPDUCircuitBreakers OBJECT IDENTIFIER ::= { xPDU 4 }
+xPDUInputContacts OBJECT IDENTIFIER ::= { xPDU 5 }
+xPDUOutputRelays OBJECT IDENTIFIER ::= { xPDU 6 }
+xPDUMiscGroup OBJECT IDENTIFIER ::= { xPDU 7 }
+
+xPDUMainInput OBJECT IDENTIFIER ::= { xPDUACMonitoringPoint 1 }
+xPDUBypassInput OBJECT IDENTIFIER ::= { xPDUACMonitoringPoint 2 }
+xPDUUPSInput OBJECT IDENTIFIER ::= { xPDUACMonitoringPoint 3 }
+xPDUSystemOutput OBJECT IDENTIFIER ::= { xPDUACMonitoringPoint 4 }
+xPDUGroundMonitorPoint OBJECT IDENTIFIER ::= { xPDUACMonitoringPoint 5 }
+
+xPDUSystemBreakers OBJECT IDENTIFIER ::= { xPDUCircuitBreakers 1 }
+xPDUBranchBreakers OBJECT IDENTIFIER ::= { xPDUCircuitBreakers 2 }
+
+pmmIdent OBJECT IDENTIFIER ::= { powerManagementModule 1 }
+pmmDevice OBJECT IDENTIFIER ::= { powerManagementModule 2 }
+pmmMonitoring OBJECT IDENTIFIER ::= { powerManagementModule 3 }
+pmmInput OBJECT IDENTIFIER ::= { pmmMonitoring 1 }
+pmmOutput OBJECT IDENTIFIER ::= { pmmMonitoring 2 }
+pmmBranch OBJECT IDENTIFIER ::= { pmmMonitoring 3 }
+
+pmmSiteConfig OBJECT IDENTIFIER ::= { pmmMonitoring 4 }
+
+
+chargerIdent OBJECT IDENTIFIER ::= { charger 1 }
+chargerInput OBJECT IDENTIFIER ::= { charger 2 }
+chargerOutput OBJECT IDENTIFIER ::= { charger 3 }
+
+
+xATSIdent OBJECT IDENTIFIER ::= { xATS 1 }
+xATSDevice OBJECT IDENTIFIER ::= { xATS 2 }
+xATSSwitch OBJECT IDENTIFIER ::= { xATS 3 }
+xATSACMonitoringPoint OBJECT IDENTIFIER ::= { xATS 4 }
+xATSTesting OBJECT IDENTIFIER ::= { xATS 5 }
+xATSInputContacts OBJECT IDENTIFIER ::= { xATS 6 }
+xATSOutputRelays OBJECT IDENTIFIER ::= { xATS 7 }
+xATSMisc OBJECT IDENTIFIER ::= { xATS 8 }
+
+xATSSwitchStatus OBJECT IDENTIFIER ::= { xATSSwitch 1 }
+xATSSwitchSettings OBJECT IDENTIFIER ::= { xATSSwitch 2 }
+xATSSwitchTimers OBJECT IDENTIFIER ::= { xATSSwitch 3 }
+xATSSwitchBlockMap OBJECT IDENTIFIER ::= { xATSSwitch 4 }
+xATSSwitchStatistics OBJECT IDENTIFIER ::= { xATSSwitch 5 }
+
+xATSSource1 OBJECT IDENTIFIER ::= { xATSACMonitoringPoint 1 }
+xATSSource2 OBJECT IDENTIFIER ::= { xATSACMonitoringPoint 2 }
+xATSSystemOutput OBJECT IDENTIFIER ::= { xATSACMonitoringPoint 3 }
+
+xATSTestingStatus OBJECT IDENTIFIER ::= { xATSTesting 1 }
+xATSTestingResults OBJECT IDENTIFIER ::= { xATSTesting 2 }
+xATSTestingSchedule OBJECT IDENTIFIER ::= { xATSTesting 3 }
+xATSTestingSimulatePowerFail OBJECT IDENTIFIER ::= { xATSTesting 4 }
+
+xATSGenerator OBJECT IDENTIFIER ::= { generator 1 }
+
+xATSGeneratorIdent OBJECT IDENTIFIER ::= { xATSGenerator 1 }
+xATSGeneratorStatus OBJECT IDENTIFIER ::= { xATSGenerator 2 }
+xATSGeneratorAdvStatus OBJECT IDENTIFIER ::= { xATSGenerator 3 }
+xATSGeneratorOutput OBJECT IDENTIFIER ::= { xATSGenerator 4 }
+xATSGeneratorSettings OBJECT IDENTIFIER ::= { xATSGenerator 5 }
+xATSGeneratorService OBJECT IDENTIFIER ::= { xATSGenerator 6 }
+xATSGeneratorFuelSystem OBJECT IDENTIFIER ::= { xATSGenerator 7 }
+
+cpsAP930x OBJECT IDENTIFIER ::= { consolePortServer 1 }
+
+cpsAP930xSys OBJECT IDENTIFIER ::= { cpsAP930x 1 }
+cpsAP930xConf OBJECT IDENTIFIER ::= { cpsAP930x 2 }
+cpsAP930xInfo OBJECT IDENTIFIER ::= { cpsAP930x 3 }
+cpsAP930xAdm OBJECT IDENTIFIER ::= { cpsAP930x 4 }
+
+
+
+smartUPS250 OBJECT IDENTIFIER ::= { smartUPS 1 }
+smartUPS400 OBJECT IDENTIFIER ::= { smartUPS 2 }
+smartUPS600 OBJECT IDENTIFIER ::= { smartUPS 3 }
+smartUPS900 OBJECT IDENTIFIER ::= { smartUPS 4 }
+smartUPS1250 OBJECT IDENTIFIER ::= { smartUPS 5 }
+smartUPS2000 OBJECT IDENTIFIER ::= { smartUPS 6 }
+
+smartUPS450 OBJECT IDENTIFIER ::= { smartUPS 7 }
+smartUPS700 OBJECT IDENTIFIER ::= { smartUPS 8 }
+smartUPS1000 OBJECT IDENTIFIER ::= { smartUPS 9 }
+smartUPS1400 OBJECT IDENTIFIER ::= { smartUPS 10 }
+smartUPS2200 OBJECT IDENTIFIER ::= { smartUPS 11 }
+smartUPS3000 OBJECT IDENTIFIER ::= { smartUPS 12 }
+smartUPS5000 OBJECT IDENTIFIER ::= { smartUPS 13 }
+smartUPS7500 OBJECT IDENTIFIER ::= { smartUPS 14 }
+smartUPS10000 OBJECT IDENTIFIER ::= { smartUPS 15 }
+smartUPS1500 OBJECT IDENTIFIER ::= { smartUPS 16 }
+smartUPS3000DSP OBJECT IDENTIFIER ::= { smartUPS 17 }
+smartUPS5000DSP OBJECT IDENTIFIER ::= { smartUPS 18 }
+smartUPS8000 OBJECT IDENTIFIER ::= { smartUPS 19 }
+
+matrixUPS3000 OBJECT IDENTIFIER ::= { matrixUPS 1 }
+matrixUPS5000 OBJECT IDENTIFIER ::= { matrixUPS 2 }
+
+masterSwitchV1 OBJECT IDENTIFIER ::= { masterSwitch 1}
+masterSwitchV2 OBJECT IDENTIFIER ::= { masterSwitch 2}
+masterSwitchVM OBJECT IDENTIFIER ::= { masterSwitch 3}
+masterSwitchMSP OBJECT IDENTIFIER ::= { masterSwitch 4}
+masterSwitchrPDU OBJECT IDENTIFIER ::= { masterSwitch 5}
+masterSwitchrPDU2 OBJECT IDENTIFIER ::= { masterSwitch 6}
+masterSwitchsPDU OBJECT IDENTIFIER ::= { masterSwitch 7}
+masterSwitchrPDUB OBJECT IDENTIFIER ::= { masterSwitch 8}
+masterSwitchePDU OBJECT IDENTIFIER ::= { masterSwitch 9}
+
+symmetraUPS4kVA OBJECT IDENTIFIER ::= { symmetraUPS 1 }
+symmetraUPS8kVA OBJECT IDENTIFIER ::= { symmetraUPS 2 }
+symmetraUPS12kVA OBJECT IDENTIFIER ::= { symmetraUPS 3 }
+symmetraUPS16kVA OBJECT IDENTIFIER ::= { symmetraUPS 4 }
+
+environmental OBJECT IDENTIFIER ::= { monitors 1 }
+environmentalMgtSystem OBJECT IDENTIFIER ::= { monitors 2 }
+emu2 OBJECT IDENTIFIER ::= { monitors 3 }
+mem OBJECT IDENTIFIER ::= { monitors 4 }
+
+dm3 OBJECT IDENTIFIER ::= { dcPower 1 }
+dcmim2 OBJECT IDENTIFIER ::= { dcPower 2 }
+
+symmetra3PhaseUPS40kVA OBJECT IDENTIFIER ::= { symmetra3PhaseUPS 1 }
+symmetra3PhaseUPS60kVA OBJECT IDENTIFIER ::= { symmetra3PhaseUPS 2 }
+symmetra3PhaseUPS80kVA OBJECT IDENTIFIER ::= { symmetra3PhaseUPS 3 }
+symmetra3PhaseUPS20kVA OBJECT IDENTIFIER ::= { symmetra3PhaseUPS 4 }
+
+airFMSeries OBJECT IDENTIFIER ::= { networkAir 1 }
+rackAirRemovalUnit OBJECT IDENTIFIER ::= { networkAir 2 }
+airPASeries OBJECT IDENTIFIER ::= { networkAir 3 }
+airIRSC100Series OBJECT IDENTIFIER ::= { networkAir 4 }
+airIRRC100Series OBJECT IDENTIFIER ::= { networkAir 5 }
+airIRRP100Series OBJECT IDENTIFIER ::= { networkAir 6 }
+airIRRP500Series OBJECT IDENTIFIER ::= { networkAir 7 }
+airIRRD100Series OBJECT IDENTIFIER ::= { networkAir 8 }
+airInRoomPerimeter OBJECT IDENTIFIER ::= { networkAir 9 }
+airACRC300Series OBJECT IDENTIFIER ::= { networkAir 10 }
+airLESeries OBJECT IDENTIFIER ::= { networkAir 11 }
+airIRRDU OBJECT IDENTIFIER ::= { networkAir 12 }
+airEcoBreeze OBJECT IDENTIFIER ::= { networkAir 13 }
+airLELSeries OBJECT IDENTIFIER ::= { networkAir 14 }
+airACRC600Series OBJECT IDENTIFIER ::= { networkAir 15 }
+airACRD600Series OBJECT IDENTIFIER ::= { networkAir 16 }
+airEconomizer OBJECT IDENTIFIER ::= { networkAir 17 }
+airTSAChillers OBJECT IDENTIFIER ::= { networkAir 18 }
+airLEG2Series OBJECT IDENTIFIER ::= { networkAir 19 }
+airAmico OBJECT IDENTIFIER ::= { networkAir 20 }
+airUniflarSP OBJECT IDENTIFIER ::= { networkAir 21 }
+airTrimChiller OBJECT IDENTIFIER ::= { networkAir 22 }
+airACRD300Series OBJECT IDENTIFIER ::= { networkAir 23 }
+
+ais5000UPS10kVA OBJECT IDENTIFIER ::= { ais5000UPS 1 }
+ais5000UPS20kVA OBJECT IDENTIFIER ::= { ais5000UPS 2 }
+ais5000UPS30kVA OBJECT IDENTIFIER ::= { ais5000UPS 3 }
+ais5000UPS40kVA OBJECT IDENTIFIER ::= { ais5000UPS 4 }
+ais5000UPS60kVA OBJECT IDENTIFIER ::= { ais5000UPS 5 }
+ais5000UPS80kVA OBJECT IDENTIFIER ::= { ais5000UPS 6 }
+ais5000UPS100kVA OBJECT IDENTIFIER ::= { ais5000UPS 7 }
+
+smartUPS3Phase10kVA OBJECT IDENTIFIER ::= { smartUPS3Phase 1 }
+smartUPS3Phase15kVA OBJECT IDENTIFIER ::= { smartUPS3Phase 2 }
+smartUPS3Phase20kVA OBJECT IDENTIFIER ::= { smartUPS3Phase 3 }
+smartUPS3Phase30kVA OBJECT IDENTIFIER ::= { smartUPS3Phase 4 }
+smartUPS3Phase40kVA OBJECT IDENTIFIER ::= { smartUPS3Phase 5 }
+
+galaxy7000UPS200kVA OBJECT IDENTIFIER ::= { galaxy 1 }
+galaxy7000UPS250kVA OBJECT IDENTIFIER ::= { galaxy 2 }
+galaxy7000UPS300kVA OBJECT IDENTIFIER ::= { galaxy 3 }
+galaxy7000UPS400kVA OBJECT IDENTIFIER ::= { galaxy 4 }
+galaxy7000UPS500kVA OBJECT IDENTIFIER ::= { galaxy 5 }
+galaxy7000SSC800kVA OBJECT IDENTIFIER ::= { galaxy 6 }
+galaxy7000SSC1200kVA OBJECT IDENTIFIER ::= { galaxy 7 }
+galaxy7000SSC2000kVA OBJECT IDENTIFIER ::= { galaxy 8 }
+galaxy300UPS10kVA33 OBJECT IDENTIFIER ::= { galaxy 9 }
+galaxy300UPS15kVA33 OBJECT IDENTIFIER ::= { galaxy 10 }
+galaxy300UPS20kVA33 OBJECT IDENTIFIER ::= { galaxy 11 }
+galaxy300UPS30kVA33 OBJECT IDENTIFIER ::= { galaxy 12 }
+galaxy300UPS40kVA33 OBJECT IDENTIFIER ::= { galaxy 13 }
+galaxy300UPS10kVA31 OBJECT IDENTIFIER ::= { galaxy 14 }
+galaxy300UPS15kVA31 OBJECT IDENTIFIER ::= { galaxy 15 }
+galaxy300UPS20kVA31 OBJECT IDENTIFIER ::= { galaxy 16 }
+galaxy300UPS30kVA31 OBJECT IDENTIFIER ::= { galaxy 17 }
+
+galaxy5000UPS20KVA OBJECT IDENTIFIER ::= { galaxy 18 }
+galaxy5000UPS30KVA OBJECT IDENTIFIER ::= { galaxy 19 }
+galaxy5000UPS40KVA OBJECT IDENTIFIER ::= { galaxy 20 }
+galaxy5000UPS50KVA OBJECT IDENTIFIER ::= { galaxy 21 }
+galaxy5000UPS60KVA OBJECT IDENTIFIER ::= { galaxy 22 }
+galaxy5000UPS80KVA OBJECT IDENTIFIER ::= { galaxy 23 }
+galaxy5000UPS100KVA OBJECT IDENTIFIER ::= { galaxy 24 }
+galaxy5000UPS120KVA OBJECT IDENTIFIER ::= { galaxy 25 }
+galaxy5000UPS130KVA OBJECT IDENTIFIER ::= { galaxy 26 }
+galaxy5500UPS20KVA OBJECT IDENTIFIER ::= { galaxy 27 }
+galaxy5500UPS30KVA OBJECT IDENTIFIER ::= { galaxy 28 }
+galaxy5500UPS40KVA OBJECT IDENTIFIER ::= { galaxy 29 }
+galaxy5500UPS50KVA OBJECT IDENTIFIER ::= { galaxy 30 }
+galaxy5500UPS60KVA OBJECT IDENTIFIER ::= { galaxy 31 }
+galaxy5500UPS80KVA OBJECT IDENTIFIER ::= { galaxy 32 }
+galaxy5500UPS100KVA OBJECT IDENTIFIER ::= { galaxy 33 }
+galaxy5500UPS120KVA OBJECT IDENTIFIER ::= { galaxy 34 }
+galaxy5500UPS130KVA OBJECT IDENTIFIER ::= { galaxy 35 }
+
+
+
+galaxyVMUPS50kVA OBJECT IDENTIFIER ::= { galaxy 36 }
+galaxyVMUPS60kVA OBJECT IDENTIFIER ::= { galaxy 37 }
+galaxyVMUPS80kVA OBJECT IDENTIFIER ::= { galaxy 38 }
+galaxyVMUPS90kVA OBJECT IDENTIFIER ::= { galaxy 39 }
+galaxyVMUPS100kVA OBJECT IDENTIFIER ::= { galaxy 40 }
+galaxyVMUPS110kVA OBJECT IDENTIFIER ::= { galaxy 41 }
+galaxyVMUPS120kVA OBJECT IDENTIFIER ::= { galaxy 42 }
+galaxyVMUPS130kVA OBJECT IDENTIFIER ::= { galaxy 43 }
+galaxyVMUPS160kVA OBJECT IDENTIFIER ::= { galaxy 44 }
+galaxyVMUPS180kVA OBJECT IDENTIFIER ::= { galaxy 45 }
+galaxyVMUPS200kVA OBJECT IDENTIFIER ::= { galaxy 46 }
+galaxyVMUPS225kVA OBJECT IDENTIFIER ::= { galaxy 47 }
+
+
+galaxy9000UPS OBJECT IDENTIFIER ::= { galaxy 48 }
+galaxy9000SSC OBJECT IDENTIFIER ::= { galaxy 49 }
+galaxy9000UPSWithSSC OBJECT IDENTIFIER ::= { galaxy 50 }
+galaxy9000FreqConverter OBJECT IDENTIFIER ::= { galaxy 51 }
+
+
+galaxyVXUPS625kVA OBJECT IDENTIFIER ::= { galaxy 56 }
+galaxyVXUPS750kVA OBJECT IDENTIFIER ::= { galaxy 57 }
+galaxyVXUPS1000kVA OBJECT IDENTIFIER ::= { galaxy 58 }
+galaxyVXUPS1250kVA OBJECT IDENTIFIER ::= { galaxy 59 }
+galaxyVXUPS1500kVA OBJECT IDENTIFIER ::= { galaxy 60 }
+
+galaxy300UPS60kVA33 OBJECT IDENTIFIER ::= { galaxy 61 }
+galaxy300UPS80kVA33 OBJECT IDENTIFIER ::= { galaxy 62 }
+
+galaxyVXUPS500kVA OBJECT IDENTIFIER ::= { galaxy 63 }
+galaxyVXUPS250kVA OBJECT IDENTIFIER ::= { galaxy 64 }
+galaxyVXUPS400kVA OBJECT IDENTIFIER ::= { galaxy 65 }
+
+galaxyVSUPS100kW OBJECT IDENTIFIER ::= { galaxy 66 }
+
+galaxy7000UPS160kVA OBJECT IDENTIFIER ::= { galaxy 67 }
+galaxyVXUPS300kVA OBJECT IDENTIFIER ::= { galaxy 68 }
+galaxyVXUPS1100kVA OBJECT IDENTIFIER ::= { galaxy 69 }
+
+
+galaxyVSUPS10kW OBJECT IDENTIFIER ::= { galaxy 70 }
+galaxyVSUPS15kW OBJECT IDENTIFIER ::= { galaxy 71 }
+galaxyVSUPS20kW OBJECT IDENTIFIER ::= { galaxy 72 }
+galaxyVSUPS25kW OBJECT IDENTIFIER ::= { galaxy 73 }
+galaxyVSUPS30kW OBJECT IDENTIFIER ::= { galaxy 74 }
+galaxyVSUPS40kW OBJECT IDENTIFIER ::= { galaxy 75 }
+galaxyVSUPS50kW OBJECT IDENTIFIER ::= { galaxy 76 }
+galaxyVSUPS60kW OBJECT IDENTIFIER ::= { galaxy 77 }
+galaxyVSUPS75kW OBJECT IDENTIFIER ::= { galaxy 78 }
+galaxyVSUPS80kW OBJECT IDENTIFIER ::= { galaxy 79 }
+galaxyVSUPS120kW OBJECT IDENTIFIER ::= { galaxy 80 }
+galaxyVSUPS150kW OBJECT IDENTIFIER ::= { galaxy 81 }
+galaxyVXUPS800kVA OBJECT IDENTIFIER ::= { galaxy 82 }
+galaxyPXUPS60kW OBJECT IDENTIFIER ::= { galaxy 83 }
+galaxyPXUPS80kW OBJECT IDENTIFIER ::= { galaxy 84 }
+galaxyPXUPS100kW OBJECT IDENTIFIER ::= { galaxy 85 }
+galaxyVLUPS500kW OBJECT IDENTIFIER ::= { galaxy 86 }
+
+eps6000UPS OBJECT IDENTIFIER ::= { eps 1 }
+eps6000SSC OBJECT IDENTIFIER ::= { eps 2 }
+eps6000UPSWithSSC OBJECT IDENTIFIER ::= { eps 3 }
+eps6000FreqConverter OBJECT IDENTIFIER ::= { eps 4 }
+eps7000UPS OBJECT IDENTIFIER ::= { eps 5 }
+eps7000SSC OBJECT IDENTIFIER ::= { eps 6 }
+eps7000UPSWithSSC OBJECT IDENTIFIER ::= { eps 7 }
+eps7000FreqConverter OBJECT IDENTIFIER ::= { eps 8 }
+eps8000UPS OBJECT IDENTIFIER ::= { eps 9 }
+eps8000SSC OBJECT IDENTIFIER ::= { eps 10 }
+eps8000UPSWithSSC OBJECT IDENTIFIER ::= { eps 11 }
+eps8000FreqConverter OBJECT IDENTIFIER ::= { eps 12 }
+
+
+
+pcns4 OBJECT IDENTIFIER ::= { pcns 1 }
+
+pcnsIdent OBJECT IDENTIFIER ::= { powerChuteNetworkShutdown 1 }
+pcnsNetworking OBJECT IDENTIFIER ::= { powerChuteNetworkShutdown 2 }
+pcnsNMC OBJECT IDENTIFIER ::= { powerChuteNetworkShutdown 3 }
+pcnsEvents OBJECT IDENTIFIER ::= { powerChuteNetworkShutdown 4 }
+pcnsShutdown OBJECT IDENTIFIER ::= { powerChuteNetworkShutdown 5 }
+pcnsAlarms OBJECT IDENTIFIER ::= { powerChuteNetworkShutdown 6 }
+
+pcnsLoggingLevel OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..6))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Override the Root Logging level for PCNS. Possible Values: CLEAR, DEBUG"
+ ::= { powerChuteNetworkShutdown 7 }
+
+
+pcbe9 OBJECT IDENTIFIER ::= { pcbe 1 }
+
+pmm400kVA OBJECT IDENTIFIER ::= { pmm 1 }
+pmm500kVA OBJECT IDENTIFIER ::= { pmm 2 }
+
+
+rpp400kVA OBJECT IDENTIFIER ::= { rpp 1 }
+rpp250kVA OBJECT IDENTIFIER ::= { rpp 2 }
+
+
+pcbeIdent OBJECT IDENTIFIER ::= { powerChuteBusinessEdition 1 }
+-- Deliberately leaving gap in the numbers so they are consistant with PCNS
+pcbeAlarms OBJECT IDENTIFIER ::= { powerChuteBusinessEdition 6 }
+
+
+
+conPortServAP930x OBJECT IDENTIFIER ::= { conPortServ 1 }
+
+gutorPEW OBJECT IDENTIFIER ::= { gutor 1 }
+gutorPDW OBJECT IDENTIFIER ::= { gutor 2 }
+gutorWEW OBJECT IDENTIFIER ::= { gutor 3 }
+gutorWDW OBJECT IDENTIFIER ::= { gutor 4 }
+gutorSDC OBJECT IDENTIFIER ::= { gutor 5 }
+gutorPXP OBJECT IDENTIFIER ::= { gutor 6 }
+gutorPXC OBJECT IDENTIFIER ::= { gutor 7 }
+
+upsIdent OBJECT IDENTIFIER ::= { ups 1 }
+upsBattery OBJECT IDENTIFIER ::= { ups 2 }
+upsInput OBJECT IDENTIFIER ::= { ups 3 }
+upsOutput OBJECT IDENTIFIER ::= { ups 4 }
+upsConfig OBJECT IDENTIFIER ::= { ups 5 }
+upsControl OBJECT IDENTIFIER ::= { ups 6 }
+upsTest OBJECT IDENTIFIER ::= { ups 7 }
+upsComm OBJECT IDENTIFIER ::= { ups 8 }
+upsPhase OBJECT IDENTIFIER ::= { ups 9 }
+upsSyncCtrlGroup OBJECT IDENTIFIER ::= { ups 10 }
+upsState OBJECT IDENTIFIER ::= { ups 11 }
+upsOutletGroups OBJECT IDENTIFIER ::= { ups 12 }
+upsDiagnostics OBJECT IDENTIFIER ::= { ups 13 }
+upsParallelSystem OBJECT IDENTIFIER ::= { ups 14 }
+upsPhysicalLayout OBJECT IDENTIFIER ::= { ups 15 }
+upsIntegratedATS OBJECT IDENTIFIER ::= { ups 16 }
+upsDCOutput OBJECT IDENTIFIER ::= { ups 17 }
+upsIntegratedUIO OBJECT IDENTIFIER ::= { ups 18 }
+upsEnergyEfficiency OBJECT IDENTIFIER ::= { ups 20 }
+
+
+upsStatistics OBJECT IDENTIFIER ::= { ups 22 }
+
+upsBasicIdent OBJECT IDENTIFIER ::= { upsIdent 1 }
+upsAdvIdent OBJECT IDENTIFIER ::= { upsIdent 2 }
+
+upsBasicBattery OBJECT IDENTIFIER ::= { upsBattery 1 }
+upsAdvBattery OBJECT IDENTIFIER ::= { upsBattery 2 }
+upsHighPrecBattery OBJECT IDENTIFIER ::= { upsBattery 3 }
+
+upsBasicInput OBJECT IDENTIFIER ::= { upsInput 1 }
+upsAdvInput OBJECT IDENTIFIER ::= { upsInput 2 }
+upsHighPrecInput OBJECT IDENTIFIER ::= { upsInput 3 }
+
+upsBasicOutput OBJECT IDENTIFIER ::= { upsOutput 1 }
+upsAdvOutput OBJECT IDENTIFIER ::= { upsOutput 2 }
+upsHighPrecOutput OBJECT IDENTIFIER ::= { upsOutput 3 }
+
+upsBasicConfig OBJECT IDENTIFIER ::= { upsConfig 1 }
+upsAdvConfig OBJECT IDENTIFIER ::= { upsConfig 2 }
+
+
+upsBasicControl OBJECT IDENTIFIER ::= { upsControl 1 }
+upsAdvControl OBJECT IDENTIFIER ::= { upsControl 2 }
+
+upsBasicTest OBJECT IDENTIFIER ::= { upsTest 1 }
+upsAdvTest OBJECT IDENTIFIER ::= { upsTest 2 }
+
+upsPhaseResetValues OBJECT IDENTIFIER ::= { upsPhase 1 }
+upsPhaseInput OBJECT IDENTIFIER ::= { upsPhase 2 }
+upsPhaseOutput OBJECT IDENTIFIER ::= { upsPhase 3 }
+
+upsSyncCtrlGroupConfig OBJECT IDENTIFIER ::= { upsSyncCtrlGroup 1 }
+upsSyncCtrlGroupStatus OBJECT IDENTIFIER ::= { upsSyncCtrlGroup 2 }
+
+upsBasicState OBJECT IDENTIFIER ::= { upsState 1 }
+upsAdvState OBJECT IDENTIFIER ::= { upsState 2 }
+
+upsOutletGroupStatus OBJECT IDENTIFIER ::= { upsOutletGroups 1 }
+upsOutletGroupConfig OBJECT IDENTIFIER ::= { upsOutletGroups 2 }
+upsOutletGroupControl OBJECT IDENTIFIER ::= { upsOutletGroups 3 }
+
+upsDiagnosticIM OBJECT IDENTIFIER ::= { upsDiagnostics 1 }
+upsDiagnosticPowerModules OBJECT IDENTIFIER ::= { upsDiagnostics 2 }
+upsDiagnosticBatteries OBJECT IDENTIFIER ::= { upsDiagnostics 3 }
+upsDiagnosticSubsystem OBJECT IDENTIFIER ::= { upsDiagnostics 4 }
+upsDiagnosticExternalDevices OBJECT IDENTIFIER ::= { upsDiagnostics 5 }
+upsDiagnosticComBus OBJECT IDENTIFIER ::= { upsDiagnostics 6 }
+upsDiagnosticPowerCabinet OBJECT IDENTIFIER ::= { upsDiagnostics 7 }
+upsDiagnosticDisplay OBJECT IDENTIFIER ::= { upsDiagnostics 8 }
+upsDiagnosticUnitController OBJECT IDENTIFIER ::= { upsDiagnostics 9 }
+upsDiagnosticSLC OBJECT IDENTIFIER ::= { upsDiagnostics 10 }
+upsDiagnosticTemperature OBJECT IDENTIFIER ::= { upsDiagnostics 11 }
+
+upsDiagSwitchGear OBJECT IDENTIFIER ::= { upsDiagnosticExternalDevices 1 }
+upsDiagMCCBBox OBJECT IDENTIFIER ::= { upsDiagnosticExternalDevices 2 }
+upsDiagTransformer OBJECT IDENTIFIER ::= { upsDiagnosticExternalDevices 3 }
+
+upsDiagFlyWheel OBJECT IDENTIFIER ::= { upsDiagnosticExternalDevices 4 }
+
+upsOutputRelays OBJECT IDENTIFIER ::= { upsIntegratedUIO 1 }
+upsInputContacts OBJECT IDENTIFIER ::= { upsIntegratedUIO 2 }
+
+
+upsECOmode OBJECT IDENTIFIER ::= { upsEnergyEfficiency 1 }
+upsEBMmode OBJECT IDENTIFIER ::= { upsEnergyEfficiency 2 }
+
+
+upsBatteryStats OBJECT IDENTIFIER ::= { upsStatistics 1 }
+upsOperationalStats OBJECT IDENTIFIER ::= { upsStatistics 2 }
+upsEnergyEfficiencyStats OBJECT IDENTIFIER ::= { upsStatistics 3 }
+
+mUpsEnviron OBJECT IDENTIFIER ::= { measureUps 1 }
+mUpsContact OBJECT IDENTIFIER ::= { measureUps 2 }
+
+serialPort OBJECT IDENTIFIER ::= { miniSNMPadapter 1}
+
+serialPort1 OBJECT IDENTIFIER ::= { serialPort 1}
+serialPort2 OBJECT IDENTIFIER ::= { serialPort 2}
+
+serialPort2Config OBJECT IDENTIFIER ::= { serialPort2 1}
+serialPort2Control OBJECT IDENTIFIER ::= { serialPort2 2}
+
+sPDUIdent OBJECT IDENTIFIER ::= { masterswitch 1 }
+sPDUMasterControl OBJECT IDENTIFIER ::= { masterswitch 2 }
+sPDUMasterConfig OBJECT IDENTIFIER ::= { masterswitch 3 }
+sPDUOutletControl OBJECT IDENTIFIER ::= { masterswitch 4 }
+sPDUOutletConfig OBJECT IDENTIFIER ::= { masterswitch 5 }
+
+sPDUIdentVM OBJECT IDENTIFIER ::= { masterswitchVM 1 }
+sPDUMasterControlVM OBJECT IDENTIFIER ::= { masterswitchVM 2 }
+sPDUMasterConfigVM OBJECT IDENTIFIER ::= { masterswitchVM 3 }
+sPDUMasterStatusVM OBJECT IDENTIFIER ::= { masterswitchVM 4 }
+sPDUOutletControlVM OBJECT IDENTIFIER ::= { masterswitchVM 5 }
+sPDUOutletConfigVM OBJECT IDENTIFIER ::= { masterswitchVM 6 }
+sPDUOutletStatusVM OBJECT IDENTIFIER ::= { masterswitchVM 7 }
+
+sPDUIdentMSP OBJECT IDENTIFIER ::= { masterswitchMSP 1 }
+sPDUMasterControlMSP OBJECT IDENTIFIER ::= { masterswitchMSP 2 }
+sPDUMasterConfigMSP OBJECT IDENTIFIER ::= { masterswitchMSP 3 }
+sPDUMasterStatusMSP OBJECT IDENTIFIER ::= { masterswitchMSP 4 }
+sPDUOutletControlMSP OBJECT IDENTIFIER ::= { masterswitchMSP 5 }
+sPDUOutletConfigMSP OBJECT IDENTIFIER ::= { masterswitchMSP 6 }
+sPDUOutletStatusMSP OBJECT IDENTIFIER ::= { masterswitchMSP 7 }
+
+sPDUOutletConfigMSPall OBJECT IDENTIFIER ::= { sPDUOutletConfigMSP 1 }
+sPDUOutletConfigMSPgs OBJECT IDENTIFIER ::= { sPDUOutletConfigMSP 2 }
+sPDUOutletConfigMSPannun OBJECT IDENTIFIER ::= { sPDUOutletConfigMSP 3 }
+sPDUOutletConfigMSPmups OBJECT IDENTIFIER ::= { sPDUOutletConfigMSP 4 }
+
+rPDUIdent OBJECT IDENTIFIER ::= { rPDU 1 }
+rPDULoad OBJECT IDENTIFIER ::= { rPDU 2 }
+rPDUOutlet OBJECT IDENTIFIER ::= { rPDU 3 }
+rPDUPowerSupply OBJECT IDENTIFIER ::= { rPDU 4 }
+rPDUStatus OBJECT IDENTIFIER ::= { rPDU 5 }
+
+rPDULoadDevice OBJECT IDENTIFIER ::= { rPDULoad 1 }
+rPDULoadPhaseConfig OBJECT IDENTIFIER ::= { rPDULoad 2 }
+rPDULoadStatus OBJECT IDENTIFIER ::= { rPDULoad 3 }
+rPDULoadBankConfig OBJECT IDENTIFIER ::= { rPDULoad 4 }
+
+rPDUOutletDevice OBJECT IDENTIFIER ::= { rPDUOutlet 1 }
+rPDUOutletPhase OBJECT IDENTIFIER ::= { rPDUOutlet 2 }
+rPDUOutletControl OBJECT IDENTIFIER ::= { rPDUOutlet 3 }
+rPDUOutletConfig OBJECT IDENTIFIER ::= { rPDUOutlet 4 }
+rPDUOutletStatus OBJECT IDENTIFIER ::= { rPDUOutlet 5 }
+rPDUOutletBank OBJECT IDENTIFIER ::= { rPDUOutlet 6 }
+
+rPDUPowerSupplyDevice OBJECT IDENTIFIER ::= { rPDUPowerSupply 1 }
+
+dm3Ident OBJECT IDENTIFIER ::= { dcDM3 1 }
+dm3Config OBJECT IDENTIFIER ::= { dcDM3 2 }
+dm3Status OBJECT IDENTIFIER ::= { dcDM3 3 }
+
+dm3IdentSystem OBJECT IDENTIFIER ::= { dm3Ident 1}
+
+dm3ConfigSystem OBJECT IDENTIFIER ::= { dm3Config 1 }
+dm3ConfigLVD OBJECT IDENTIFIER ::= { dm3Config 2 }
+dm3ConfigBattery OBJECT IDENTIFIER ::= { dm3Config 3 }
+dm3ConfigPowerModules OBJECT IDENTIFIER ::= { dm3Config 4 }
+dm3ConfigRelays OBJECT IDENTIFIER ::= { dm3Config 5 }
+dm3ConfigDistribution OBJECT IDENTIFIER ::= { dm3Config 6 }
+
+dm3ConfigRectifier OBJECT IDENTIFIER ::= { dm3ConfigPowerModules 1 }
+dm3ConfigConverter OBJECT IDENTIFIER ::= { dm3ConfigPowerModules 2 }
+
+dm3ConfigRectThresh OBJECT IDENTIFIER ::= { dm3ConfigRectifier 1 }
+dm3ConfigRectAlarms OBJECT IDENTIFIER ::= { dm3ConfigRectifier 2 }
+
+dm3ConfigConvThresh OBJECT IDENTIFIER ::= { dm3ConfigConverter 1 }
+dm3ConfigConvAlarms OBJECT IDENTIFIER ::= { dm3ConfigConverter 2 }
+
+dm3ConfigOutputRelays OBJECT IDENTIFIER ::= { dm3ConfigRelays 1 }
+dm3ConfigInputRelays OBJECT IDENTIFIER ::= { dm3ConfigRelays 2 }
+
+dm3ConfigBreakers OBJECT IDENTIFIER ::= { dm3ConfigDistribution 1 }
+dm3ConfigFuses OBJECT IDENTIFIER ::= { dm3ConfigDistribution 2 }
+
+dm3StatusSystem OBJECT IDENTIFIER ::= { dm3Status 1 }
+dm3StatusAlarms OBJECT IDENTIFIER ::= { dm3Status 2 }
+dm3StatusBattery OBJECT IDENTIFIER ::= { dm3Status 3 }
+dm3StatusOEM OBJECT IDENTIFIER ::= { dm3Status 4 }
+dm3StatusLVD OBJECT IDENTIFIER ::= { dm3Status 5 }
+dm3StatusPowerModules OBJECT IDENTIFIER ::= { dm3Status 6 }
+dm3StatusRelays OBJECT IDENTIFIER ::= { dm3Status 7 }
+dm3StatusDistribution OBJECT IDENTIFIER ::= { dm3Status 8 }
+
+dm3StatusRectifier OBJECT IDENTIFIER ::= { dm3StatusPowerModules 1 }
+dm3StatusConverter OBJECT IDENTIFIER ::= { dm3StatusPowerModules 2 }
+
+dm3StatusOutputRelays OBJECT IDENTIFIER ::= { dm3StatusRelays 1 }
+dm3StatusInputRelays OBJECT IDENTIFIER ::= { dm3StatusRelays 2 }
+
+dm3StatusBreakers OBJECT IDENTIFIER ::= { dm3StatusDistribution 1 }
+dm3StatusFuses OBJECT IDENTIFIER ::= { dm3StatusDistribution 2 }
+
+atsIdent OBJECT IDENTIFIER ::= { automaticTransferSwitch 1 }
+atsCalibration OBJECT IDENTIFIER ::= { automaticTransferSwitch 2 }
+atsControl OBJECT IDENTIFIER ::= { automaticTransferSwitch 3 }
+atsConfig OBJECT IDENTIFIER ::= { automaticTransferSwitch 4 }
+atsStatus OBJECT IDENTIFIER ::= { automaticTransferSwitch 5 }
+
+atsCalibrationInput OBJECT IDENTIFIER ::= { atsCalibration 1 }
+atsCalibrationPowerSupply OBJECT IDENTIFIER ::= { atsCalibration 2 }
+atsCalibrationOutput OBJECT IDENTIFIER ::= { atsCalibration 3 }
+
+atsStatusDeviceStatus OBJECT IDENTIFIER ::= { atsStatus 1 }
+atsStatusResetValues OBJECT IDENTIFIER ::= { atsStatus 2 }
+atsStatusInput OBJECT IDENTIFIER ::= { atsStatus 3 }
+atsStatusOutput OBJECT IDENTIFIER ::= { atsStatus 4 }
+
+dcmim2Ident OBJECT IDENTIFIER ::= { dc2 1 }
+dcmim2Control OBJECT IDENTIFIER ::= { dc2 2 }
+dcmim2Config OBJECT IDENTIFIER ::= { dc2 3 }
+dcmim2Status OBJECT IDENTIFIER ::= { dc2 4 }
+
+dcmim2IdentSystem OBJECT IDENTIFIER ::= { dcmim2Ident 1 }
+
+dcmim2ControlSystem OBJECT IDENTIFIER ::= { dcmim2Control 1 }
+
+dcmim2ConfigSystem OBJECT IDENTIFIER ::= { dcmim2Config 1 }
+dcmim2ConfigBattery OBJECT IDENTIFIER ::= { dcmim2Config 2 }
+dcmim2ConfigLVD OBJECT IDENTIFIER ::= { dcmim2Config 3 }
+
+dcmim2StatusSystem OBJECT IDENTIFIER ::= { dcmim2Status 1 }
+dcmim2StatusRectifier OBJECT IDENTIFIER ::= { dcmim2Status 2 }
+dcmim2StatusBattery OBJECT IDENTIFIER ::= { dcmim2Status 3 }
+dcmim2StatusLVD OBJECT IDENTIFIER ::= { dcmim2Status 4 }
+dcmim2StatusAlarms OBJECT IDENTIFIER ::= { dcmim2Status 5 }
+
+external OBJECT IDENTIFIER ::= { environmentalMonitor 1 }
+integrated OBJECT IDENTIFIER ::= { environmentalMonitor 2 }
+envMgtSystem OBJECT IDENTIFIER ::= { environmentalMonitor 3 }
+modEnvMgr OBJECT IDENTIFIER ::= { environmentalMonitor 4 }
+envWireless OBJECT IDENTIFIER ::= { environmentalMonitor 5 }
+
+emIdent OBJECT IDENTIFIER ::= { external 1 }
+emConfig OBJECT IDENTIFIER ::= { external 2 }
+emStatus OBJECT IDENTIFIER ::= { external 3 }
+
+iemIdent OBJECT IDENTIFIER ::= { integrated 1 }
+iemConfig OBJECT IDENTIFIER ::= { integrated 2 }
+iemStatus OBJECT IDENTIFIER ::= { integrated 3 }
+
+emsIdent OBJECT IDENTIFIER ::= { envMgtSystem 1 }
+
+emsOutputRelayControl OBJECT IDENTIFIER ::= { envMgtSystem 2 }
+emsOutletControl OBJECT IDENTIFIER ::= { envMgtSystem 3 }
+emsSensorControl OBJECT IDENTIFIER ::= { envMgtSystem 4 }
+emsAlarmDeviceControl OBJECT IDENTIFIER ::= { envMgtSystem 5 }
+
+emsConfig OBJECT IDENTIFIER ::= { envMgtSystem 6 }
+emsProbeConfig OBJECT IDENTIFIER ::= { envMgtSystem 7 }
+emsInputContactConfig OBJECT IDENTIFIER ::= { envMgtSystem 8 }
+emsOutputRelayConfig OBJECT IDENTIFIER ::= { envMgtSystem 9 }
+emsOutletConfig OBJECT IDENTIFIER ::= { envMgtSystem 10 }
+emsSensorConfig OBJECT IDENTIFIER ::= { envMgtSystem 11 }
+
+emsStatus OBJECT IDENTIFIER ::= { envMgtSystem 12 }
+emsProbeStatus OBJECT IDENTIFIER ::= { envMgtSystem 13 }
+emsInputContactStatus OBJECT IDENTIFIER ::= { envMgtSystem 14 }
+emsOutputRelayStatus OBJECT IDENTIFIER ::= { envMgtSystem 15 }
+emsOutletStatus OBJECT IDENTIFIER ::= { envMgtSystem 16 }
+emsAlarmDeviceStatus OBJECT IDENTIFIER ::= { envMgtSystem 17 }
+emsSensorStatus OBJECT IDENTIFIER ::= { envMgtSystem 18 }
+emsInputStateSensorConfig OBJECT IDENTIFIER ::= { envMgtSystem 19 }
+emsInputStateSensorStatus OBJECT IDENTIFIER ::= { envMgtSystem 20 }
+
+memModules OBJECT IDENTIFIER ::= { modEnvMgr 1 }
+memSensors OBJECT IDENTIFIER ::= { modEnvMgr 2 }
+memInputs OBJECT IDENTIFIER ::= { modEnvMgr 3 }
+memOutputs OBJECT IDENTIFIER ::= { modEnvMgr 4 }
+memOutlets OBJECT IDENTIFIER ::= { modEnvMgr 5 }
+memBeacons OBJECT IDENTIFIER ::= { modEnvMgr 6 }
+memInputStateSensors OBJECT IDENTIFIER ::= { modEnvMgr 7 }
+
+wirelessSensorStatus OBJECT IDENTIFIER ::= { envWireless 1 }
+wirelessSensorPodStatus OBJECT IDENTIFIER ::= { envWireless 2 }
+wirelessSensorConfig OBJECT IDENTIFIER ::= { envWireless 3 }
+wirelessSensorPodConfig OBJECT IDENTIFIER ::= { envWireless 4 }
+
+nlIdent OBJECT IDENTIFIER ::= { netlock 1 }
+nlStatus OBJECT IDENTIFIER ::= { netlock 2 }
+
+airFM OBJECT IDENTIFIER ::= { airConditioners 1 }
+airFMIdent OBJECT IDENTIFIER ::= { airFM 1 }
+airFMStatus OBJECT IDENTIFIER ::= { airFM 2 }
+airFMGroup OBJECT IDENTIFIER ::= { airFM 3 }
+airFMSystem OBJECT IDENTIFIER ::= { airFM 4 }
+airFMModule OBJECT IDENTIFIER ::= { airFM 5 }
+airFMAlarms OBJECT IDENTIFIER ::= { airFM 6 }
+
+airFMGroupSysRoles OBJECT IDENTIFIER ::= { airFMGroup 4 }
+airFMGroupCfg OBJECT IDENTIFIER ::= { airFMGroup 5 }
+airFMGroupLoadShare OBJECT IDENTIFIER ::= { airFMGroup 6 }
+airFMGroupFailover OBJECT IDENTIFIER ::= { airFMGroup 7 }
+
+airFMGroupFailoverSys OBJECT IDENTIFIER ::= { airFMGroupFailover 1 }
+airFMGroupFailoverMod OBJECT IDENTIFIER ::= { airFMGroupFailover 2 }
+
+airFMSysStatus OBJECT IDENTIFIER ::= { airFMSystem 1 }
+airFMSysDemands OBJECT IDENTIFIER ::= { airFMSystem 2 }
+airFMSysSetup OBJECT IDENTIFIER ::= { airFMSystem 3 }
+airFMSysConfig OBJECT IDENTIFIER ::= { airFMSystem 4 }
+airFMSysCooling OBJECT IDENTIFIER ::= { airFMSystem 5 }
+airFMSysHumidify OBJECT IDENTIFIER ::= { airFMSystem 6 }
+airFMSysDehumidify OBJECT IDENTIFIER ::= { airFMSystem 7 }
+airFMSysReheat OBJECT IDENTIFIER ::= { airFMSystem 8 }
+airFMSysThresholds OBJECT IDENTIFIER ::= { airFMSystem 9 }
+airFMSysInputs OBJECT IDENTIFIER ::= { airFMSystem 10 }
+airFMSysOutputs OBJECT IDENTIFIER ::= { airFMSystem 11 }
+airFMSysAlarmMap OBJECT IDENTIFIER ::= { airFMSystem 12 }
+
+airFMSysAlarmMapSys OBJECT IDENTIFIER ::= { airFMSysAlarmMap 1 }
+airFMSysAlarmMapMainMod OBJECT IDENTIFIER ::= { airFMSysAlarmMap 2 }
+airFMSysAlarmMapExpMod1 OBJECT IDENTIFIER ::= { airFMSysAlarmMap 3 }
+airFMSysAlarmMapExpMod2 OBJECT IDENTIFIER ::= { airFMSysAlarmMap 4 }
+airFMSysAlarmMapInput OBJECT IDENTIFIER ::= { airFMSysAlarmMap 5 }
+airFMSysAlarmMapOutput OBJECT IDENTIFIER ::= { airFMSysAlarmMap 6 }
+
+airFMModIdent OBJECT IDENTIFIER ::= { airFMModule 1 }
+airFMModStatus OBJECT IDENTIFIER ::= { airFMModule 2 }
+airFMModProperties OBJECT IDENTIFIER ::= { airFMModule 3 }
+airFMModCooling OBJECT IDENTIFIER ::= { airFMModule 4 }
+airFMModHumidity OBJECT IDENTIFIER ::= { airFMModule 5 }
+airFMModBlower1 OBJECT IDENTIFIER ::= { airFMModule 6 }
+airFMModBlower2 OBJECT IDENTIFIER ::= { airFMModule 7 }
+airFMModRunHours OBJECT IDENTIFIER ::= { airFMModule 8 }
+airFMModServIntervals OBJECT IDENTIFIER ::= { airFMModule 9 }
+airFMModServIntResets OBJECT IDENTIFIER ::= { airFMModule 10 }
+
+
+airPA OBJECT IDENTIFIER ::= { airConditioners 2 }
+airPAIdent OBJECT IDENTIFIER ::= { airPA 1 }
+airPAStatus OBJECT IDENTIFIER ::= { airPA 2 }
+
+airIR OBJECT IDENTIFIER ::= { airConditioners 3 }
+airIRAlarms OBJECT IDENTIFIER ::= { airIR 1 }
+airIRRC OBJECT IDENTIFIER ::= { airIR 2 }
+airIRRP OBJECT IDENTIFIER ::= { airIR 3 }
+airIRSC OBJECT IDENTIFIER ::= { airIR 4 }
+
+airIRRCGroup OBJECT IDENTIFIER ::= { airIRRC 1 }
+airIRRCUnit OBJECT IDENTIFIER ::= { airIRRC 2 }
+
+airIRRCGroupStatus OBJECT IDENTIFIER ::= { airIRRCGroup 1 }
+airIRRCGroupSetpoints OBJECT IDENTIFIER ::= { airIRRCGroup 2 }
+airIRRCGroupConfig OBJECT IDENTIFIER ::= { airIRRCGroup 3 }
+
+airIRRCUnitIdent OBJECT IDENTIFIER ::= { airIRRCUnit 1 }
+airIRRCUnitStatus OBJECT IDENTIFIER ::= { airIRRCUnit 2 }
+airIRRCUnitRunHours OBJECT IDENTIFIER ::= { airIRRCUnit 3 }
+airIRRCUnitServiceIntervals OBJECT IDENTIFIER ::= { airIRRCUnit 4 }
+airIRRCUnitThresholds OBJECT IDENTIFIER ::= { airIRRCUnit 5 }
+airIRRCUnitConfig OBJECT IDENTIFIER ::= { airIRRCUnit 6 }
+
+-- Series 100 DX Air Conditioners
+airIRRP100 OBJECT IDENTIFIER ::= { airIRRP 1 }
+-- Series 500 CW Air Conditioners
+airIRRP500 OBJECT IDENTIFIER ::= { airIRRP 2 }
+
+airIRRP100Group OBJECT IDENTIFIER ::= { airIRRP100 1 }
+airIRRP100Unit OBJECT IDENTIFIER ::= { airIRRP100 2 }
+
+airIRRP100GroupStatus OBJECT IDENTIFIER ::= { airIRRP100Group 1 }
+airIRRP100GroupSetpoints OBJECT IDENTIFIER ::= { airIRRP100Group 2 }
+airIRRP100GroupConfig OBJECT IDENTIFIER ::= { airIRRP100Group 3 }
+
+airIRRP100UnitIdent OBJECT IDENTIFIER ::= { airIRRP100Unit 1 }
+airIRRP100UnitStatus OBJECT IDENTIFIER ::= { airIRRP100Unit 2 }
+airIRRP100UnitRunHours OBJECT IDENTIFIER ::= { airIRRP100Unit 3 }
+airIRRP100UnitServiceIntervals OBJECT IDENTIFIER ::= { airIRRP100Unit 4 }
+airIRRP100UnitThresholds OBJECT IDENTIFIER ::= { airIRRP100Unit 5 }
+airIRRP100UnitConfig OBJECT IDENTIFIER ::= { airIRRP100Unit 6 }
+
+airIRRP500Group OBJECT IDENTIFIER ::= { airIRRP500 1 }
+airIRRP500Unit OBJECT IDENTIFIER ::= { airIRRP500 2 }
+
+airIRRP500GroupStatus OBJECT IDENTIFIER ::= { airIRRP500Group 1 }
+airIRRP500GroupSetpoints OBJECT IDENTIFIER ::= { airIRRP500Group 2 }
+airIRRP500GroupConfig OBJECT IDENTIFIER ::= { airIRRP500Group 3 }
+
+airIRRP500UnitIdent OBJECT IDENTIFIER ::= { airIRRP500Unit 1 }
+airIRRP500UnitStatus OBJECT IDENTIFIER ::= { airIRRP500Unit 2 }
+airIRRP500UnitRunHours OBJECT IDENTIFIER ::= { airIRRP500Unit 3 }
+airIRRP500UnitServiceIntervals OBJECT IDENTIFIER ::= { airIRRP500Unit 4 }
+airIRRP500UnitThresholds OBJECT IDENTIFIER ::= { airIRRP500Unit 5 }
+airIRRP500UnitConfig OBJECT IDENTIFIER ::= { airIRRP500Unit 6 }
+
+
+airIRSCUnit OBJECT IDENTIFIER ::= { airIRSC 1 }
+
+airIRSCUnitIdent OBJECT IDENTIFIER ::= { airIRSCUnit 1 }
+airIRSCUnitStatus OBJECT IDENTIFIER ::= { airIRSCUnit 2 }
+airIRSCUnitRunHours OBJECT IDENTIFIER ::= { airIRSCUnit 3 }
+airIRSCUnitServiceIntervals OBJECT IDENTIFIER ::= { airIRSCUnit 4 }
+airIRSCUnitThresholds OBJECT IDENTIFIER ::= { airIRSCUnit 5 }
+airIRSCUnitSetpoints OBJECT IDENTIFIER ::= { airIRSCUnit 6 }
+airIRSCUnitConfig OBJECT IDENTIFIER ::= { airIRSCUnit 7 }
+
+airIRSCGroup OBJECT IDENTIFIER ::= { airIRSC 2 }
+
+airIRSCGroupStatus OBJECT IDENTIFIER ::= { airIRSCGroup 1 }
+airIRSCGroupSetpoints OBJECT IDENTIFIER ::= { airIRSCGroup 2 }
+airIRSCGroupConfig OBJECT IDENTIFIER ::= { airIRSCGroup 3 }
+
+
+airIRGen2 OBJECT IDENTIFIER ::= { airConditioners 4 }
+
+airIRG2Ident OBJECT IDENTIFIER ::= { airIRGen2 1 }
+airIRG2Group OBJECT IDENTIFIER ::= { airIRGen2 2 }
+airIRG2Alarms OBJECT IDENTIFIER ::= { airIRGen2 3 }
+airIRG2RC OBJECT IDENTIFIER ::= { airIRGen2 4 }
+airIRG2RD OBJECT IDENTIFIER ::= { airIRGen2 5 }
+airIRG2SC OBJECT IDENTIFIER ::= { airIRGen2 6 }
+airIRG2RA OBJECT IDENTIFIER ::= { airIRGen2 7 }
+
+-- airIR Gen2 Group data
+airIRG2GroupStatus OBJECT IDENTIFIER ::= { airIRG2Group 1 }
+airIRG2GroupSetpoints OBJECT IDENTIFIER ::= { airIRG2Group 2 }
+airIRG2GroupConfig OBJECT IDENTIFIER ::= { airIRG2Group 3 }
+
+-- airIR Gen2 RD Unit data
+airIRG2RDType1 OBJECT IDENTIFIER ::= { airIRG2RD 1 }
+airIRG2RDType2 OBJECT IDENTIFIER ::= { airIRG2RD 2 }
+airIRG2RDT2Status OBJECT IDENTIFIER ::= { airIRG2RDType2 1 }
+airIRG2RDT2RunHours OBJECT IDENTIFIER ::= { airIRG2RDType2 2 }
+airIRG2RDT2ServiceIntervals OBJECT IDENTIFIER ::= { airIRG2RDType2 3 }
+airIRG2RDT2Thresholds OBJECT IDENTIFIER ::= { airIRG2RDType2 4 }
+airIRG2RDT2Setpoints OBJECT IDENTIFIER ::= { airIRG2RDType2 5 }
+airIRG2RDT2Config OBJECT IDENTIFIER ::= { airIRG2RDType2 6 }
+
+airInRoom OBJECT IDENTIFIER ::= { airConditioners 5 }
+
+airIRmIdent OBJECT IDENTIFIER ::= { airInRoom 1 }
+airIRmAlarms OBJECT IDENTIFIER ::= { airInRoom 2 }
+airIRmPerimeter OBJECT IDENTIFIER ::= { airInRoom 3 }
+
+airIRmPmCommon1 OBJECT IDENTIFIER ::= { airIRmPerimeter 2 }
+airIRmPmCommon2 OBJECT IDENTIFIER ::= { airIRmPerimeter 3 }
+airIRmPmCommon3 OBJECT IDENTIFIER ::= { airIRmPerimeter 4 }
+airIRmPmCommon4 OBJECT IDENTIFIER ::= { airIRmPerimeter 5 }
+airIRmPmCommon5 OBJECT IDENTIFIER ::= { airIRmPerimeter 6 }
+airIRmPmCompressor1 OBJECT IDENTIFIER ::= { airIRmPerimeter 7 }
+airIRmPmCompressor2 OBJECT IDENTIFIER ::= { airIRmPerimeter 8 }
+airIRmPmSuctionValve1 OBJECT IDENTIFIER ::= { airIRmPerimeter 9 }
+airIRmPmSuctionValve2 OBJECT IDENTIFIER ::= { airIRmPerimeter 10 }
+airIRmPmEheating1 OBJECT IDENTIFIER ::= { airIRmPerimeter 11 }
+airIRmPmEheating2 OBJECT IDENTIFIER ::= { airIRmPerimeter 12 }
+airIRmPmEheating3 OBJECT IDENTIFIER ::= { airIRmPerimeter 13 }
+airIRmPmEheating4 OBJECT IDENTIFIER ::= { airIRmPerimeter 14 }
+airIRmPmGECWvalve OBJECT IDENTIFIER ::= { airIRmPerimeter 15 }
+airIRmPmGvalve OBJECT IDENTIFIER ::= { airIRmPerimeter 16 }
+airIRmPmDrycooler1 OBJECT IDENTIFIER ::= { airIRmPerimeter 17 }
+airIRmPmDrycooler2 OBJECT IDENTIFIER ::= { airIRmPerimeter 18 }
+airIRmPmDrycooler3 OBJECT IDENTIFIER ::= { airIRmPerimeter 19 }
+airIRmPmDrycooler4 OBJECT IDENTIFIER ::= { airIRmPerimeter 20 }
+airIRmPmPump1 OBJECT IDENTIFIER ::= { airIRmPerimeter 21 }
+airIRmPmPump2 OBJECT IDENTIFIER ::= { airIRmPerimeter 22 }
+airIRmPmPump3 OBJECT IDENTIFIER ::= { airIRmPerimeter 23 }
+airIRmPmPump4 OBJECT IDENTIFIER ::= { airIRmPerimeter 24 }
+airIRmPmHotgasHeating OBJECT IDENTIFIER ::= { airIRmPerimeter 25 }
+airIRmPmPWWHeating OBJECT IDENTIFIER ::= { airIRmPerimeter 26 }
+airIRmPmHumidifier1 OBJECT IDENTIFIER ::= { airIRmPerimeter 27 }
+airIRmPmHumidifier2 OBJECT IDENTIFIER ::= { airIRmPerimeter 28 }
+-- Skipping 29 and 30.
+airIRmPmDehumidification OBJECT IDENTIFIER ::= { airIRmPerimeter 31 }
+airIRmPmFan1 OBJECT IDENTIFIER ::= { airIRmPerimeter 32 }
+airIRmPmFan2 OBJECT IDENTIFIER ::= { airIRmPerimeter 33 }
+airIRmPmFan3 OBJECT IDENTIFIER ::= { airIRmPerimeter 34 }
+airIRmPmLouver1 OBJECT IDENTIFIER ::= { airIRmPerimeter 35 }
+airIRmPmLouver2 OBJECT IDENTIFIER ::= { airIRmPerimeter 36 }
+airIRmPmLouver3 OBJECT IDENTIFIER ::= { airIRmPerimeter 37 }
+airIRmPmAuxAlarm1 OBJECT IDENTIFIER ::= { airIRmPerimeter 38 }
+airIRmPmAuxAlarm2 OBJECT IDENTIFIER ::= { airIRmPerimeter 39 }
+airIRmPmAuxAlarm3 OBJECT IDENTIFIER ::= { airIRmPerimeter 40 }
+airIRmPmAuxAlarm4 OBJECT IDENTIFIER ::= { airIRmPerimeter 41 }
+airIRmPmAuxAlarm5 OBJECT IDENTIFIER ::= { airIRmPerimeter 42 }
+airIRmPmAlarmBits OBJECT IDENTIFIER ::= { airIRmPerimeter 43 }
+airIRmPmMyZone OBJECT IDENTIFIER ::= { airIRmPerimeter 44 }
+airIRmPmGlobalZoneData OBJECT IDENTIFIER ::= { airIRmPerimeter 45 }
+
+airIRGen3 OBJECT IDENTIFIER ::= { airConditioners 6 }
+
+airIRG3Ident OBJECT IDENTIFIER ::= { airIRGen3 1 }
+airIRG3Group OBJECT IDENTIFIER ::= { airIRGen3 2 }
+airIRG3Alarms OBJECT IDENTIFIER ::= { airIRGen3 3 }
+airIRG3RDU OBJECT IDENTIFIER ::= { airIRGen3 4 }
+airIRG3CM OBJECT IDENTIFIER ::= { airIRGen3 5 }
+
+
+rARUIdent OBJECT IDENTIFIER ::= { rARU 1 }
+rARUConfig OBJECT IDENTIFIER ::= { rARU 2 }
+rARUStatus OBJECT IDENTIFIER ::= { rARU 3 }
+rARUFanStatus OBJECT IDENTIFIER ::= { rARU 4 }
+rARUPower OBJECT IDENTIFIER ::= { rARU 5 }
+rARUSensors OBJECT IDENTIFIER ::= { rARU 6 }
+
+
+accessPX OBJECT IDENTIFIER ::= { accessControl 1 }
+
+accessPXIdent OBJECT IDENTIFIER ::= { accessPX 1 }
+accessPXConfig OBJECT IDENTIFIER ::= { accessPX 2 }
+accessPXConfigFront OBJECT IDENTIFIER ::= { accessPX 3 }
+accessPXStatusFront OBJECT IDENTIFIER ::= { accessPX 4 }
+accessPXConfigRear OBJECT IDENTIFIER ::= { accessPX 5 }
+accessPXStatusRear OBJECT IDENTIFIER ::= { accessPX 6 }
+accessPXConfigBeacon OBJECT IDENTIFIER ::= { accessPX 7 }
+accessPXStatusBeacon OBJECT IDENTIFIER ::= { accessPX 8 }
+
+apcLocalDisplayIdent OBJECT IDENTIFIER ::= { apcLocalDisplay 1 }
+apcLocalDisplayConfig OBJECT IDENTIFIER ::= { apcLocalDisplay 2 }
+
+accPX OBJECT IDENTIFIER ::= { accControl 1 }
+
+isxModularPduIdent OBJECT IDENTIFIER ::= { isxModularPdu 1 }
+isxModularPduDevice OBJECT IDENTIFIER ::= { isxModularPdu 2 }
+isxModularPduStatus OBJECT IDENTIFIER ::= { isxModularPdu 3 }
+
+symmetraPx48kVA OBJECT IDENTIFIER ::= { symmetraPX 1 }
+symmetraPx160kVA OBJECT IDENTIFIER ::= { symmetraPX 2 }
+symmetraPx250kVA OBJECT IDENTIFIER ::= { symmetraPX 3 }
+symmetraPx500kVA OBJECT IDENTIFIER ::= { symmetraPX 4 }
+symmetraPx100kVA OBJECT IDENTIFIER ::= { symmetraPX 5 }
+symmetraPxDisplay OBJECT IDENTIFIER ::= { symmetraPX 6 }
+
+isx24ModuleHalfRackPdu OBJECT IDENTIFIER ::= { isxModDistribution 1 }
+isx6ModuleRackPdu OBJECT IDENTIFIER ::= { isxModDistribution 2 }
+
+isxModularDistInfo OBJECT IDENTIFIER ::= { isxModularDistribution 1 }
+isxModularDistModules OBJECT IDENTIFIER ::= { isxModularDistribution 2 }
+isxModularDistSubFeeds OBJECT IDENTIFIER ::= { isxModularDistribution 3 }
+isxModularDistTotals OBJECT IDENTIFIER ::= { isxModularDistribution 4 }
+
+isxModularDistSysVoltage OBJECT IDENTIFIER ::= { isxModularDistTotals 1 }
+isxModularDistSysCurrent OBJECT IDENTIFIER ::= { isxModularDistTotals 2 }
+isxModularDistSysPower OBJECT IDENTIFIER ::= { isxModularDistTotals 3 }
+
+isxcBasic OBJECT IDENTIFIER ::= { isxServers 1 }
+isxcStandard OBJECT IDENTIFIER ::= { isxServers 2 }
+isxcEnterprise OBJECT IDENTIFIER ::= { isxServers 3 }
+isxcVirtual OBJECT IDENTIFIER ::= { isxServers 4 }
+
+uioSensor OBJECT IDENTIFIER ::= { universalInputOutput 1 }
+uioInputContact OBJECT IDENTIFIER ::= { universalInputOutput 2 }
+uioOutputRelay OBJECT IDENTIFIER ::= { universalInputOutput 3 }
+
+
+-- object types
+
+-- the products group
+-- the experimental group
+
+
+
+-- the apcmgmt group
+-- the mconfig group
+
+mconfigNumTrapReceivers OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of managers to send traps to."
+ ::= { mconfig 1 }
+
+mconfigTrapReceiverTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF MconfigTrapReceiverEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of managers to send traps to. The number of
+ entries is given by the value of mconfigNumTrapReceivers."
+ ::= { mconfig 2 }
+
+mconfigTrapReceiverEntry OBJECT-TYPE
+ SYNTAX MconfigTrapReceiverEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The managers to send traps to."
+ INDEX { trapIndex}
+ ::= { mconfigTrapReceiverTable 1 }
+
+MconfigTrapReceiverEntry ::=
+ SEQUENCE {
+ trapIndex
+ INTEGER,
+ receiverAddr
+ IpAddress,
+ communityString
+ DisplayString,
+ severity
+ INTEGER,
+ acceptThisReceiver
+ INTEGER,
+ receiveTrapType
+ INTEGER
+ }
+
+trapIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to a trap receiver entry."
+ ::= { mconfigTrapReceiverEntry 1 }
+
+receiverAddr OBJECT-TYPE
+ SYNTAX IpAddress
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The IP address of the manager to send a trap to."
+ ::= { mconfigTrapReceiverEntry 2 }
+
+communityString OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The community name to use in the trap when
+ sent to the manager."
+ ::= { mconfigTrapReceiverEntry 3 }
+
+severity OBJECT-TYPE
+ SYNTAX INTEGER {
+ information(1),
+ warning(2),
+ severe(3)
+ }
+ ACCESS read-only
+ STATUS obsolete
+ DESCRIPTION
+ "The severity threshold of traps to send to the manager.
+ traps are labeled in severity as informational(1), warning(2),
+ severe(3). Only traps of equal or greater severity than
+ this value are sent to the manager."
+ ::= { mconfigTrapReceiverEntry 4 }
+
+acceptThisReceiver OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The value of yes(1) indicates that trap generation for this manager is enabled.
+ The value of no(2) indicates that trap generation for this manager is disabled"
+ ::= { mconfigTrapReceiverEntry 5 }
+
+
+receiveTrapType OBJECT-TYPE
+ SYNTAX INTEGER {
+ powernet (1),
+ ietf (2),
+ both (3)
+ }
+ ACCESS read-only
+ STATUS obsolete
+ DESCRIPTION
+ "Type of trap."
+ ::= { mconfigTrapReceiverEntry 6 }
+
+mconfigBOOTPEnabled OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The value of yes(1) indicates the PowerNet Adapter is configured to
+ obtain its IP configuration parameters from a BOOTP server.
+
+ The value of no(2) indicates adapter will assume IP configuration parameters
+ values saved in adapter's eeprom, which was originally configured at local
+ console."
+ ::= { mconfig 3 }
+
+mconfigTFTPServerIP OBJECT-TYPE
+ SYNTAX IpAddress
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The IP address of TFTP server. If mconfigBOOTPEnabled is yes(1), then this IP address
+ is provided by BOOTP server and not allowed to be modified; otherwise, this IP address
+ can be modified.
+
+ Before using TFTP to load new code image, the image file should be placed in proper
+ directory of the specified TFTP server. This OID is only supported by APC Network
+ Management Cards."
+ ::= { mconfig 4 }
+
+newCodeAuthentViaTFTP OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ validNewAgentCodeImage (2),
+ sameAgentCodeImage (3),
+ invalidAgentCodeImage (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Once mcontrolRestartAgent is set to loadAndExecuteNewAgent (3), PowerNet adapter will
+ start to load the remote image file, for authentication only, instead of saving the code
+ into flash memory. Only if a validNewAgentCodeImage (1) is found will the agent reboot
+ the PowerNet adapter and invoke the loader to load and save new code into the flash memory.
+ Otherwise, the current agent code will continue to run.
+
+ This OID shows the result of the above authentication process.
+ validNewAgentCodeImage (1) means the code image on TFTP server
+ is a valid APC agent code and is different version from the current agent.
+ Once agent identifies this, loader will start to update flash memory with
+ the new agent code.
+
+ sameAgentCodeImage (2) means the code image on TFTP server is exactly the
+ same as the currently running agent. Currently running agent will not invoke
+ loader to load the same again.
+
+ invalidAgentCodeImage (3) means the code image on TFTP server is NOT a valid
+ APC agent code. Thus, current agent will not load it into the flash memory.
+
+ The value of this OID will be associated with TRAP codeImageAuthentDone.
+ This OID is only supported by APC Network Management Cards."
+
+ ::= { mconfig 5 }
+
+mconfigClockDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The current date in the mm/dd/yyyy format. Example: 01/01/2000."
+ ::= { mconfigClock 1 }
+
+mconfigClockTime OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The current time in the hh:mm:ss am/pm format. Example: 12:00:00 am."
+ ::= { mconfigClock 2 }
+
+mcontrolRestartAgent OBJECT-TYPE
+ SYNTAX INTEGER {
+ restartCurrentAgent (1),
+ continueCurrentAgent (2),
+ loadAndExecuteNewAgent (3),
+ restartWithoutAgent (4),
+ resetNetworkAndRestart (5),
+ resetNetworkLeaveModeAndRestart (6)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to restartCurrentAgent (1) will restart the same SNMP
+ agent code currently saved in flash memory. Setting this OID to
+ loadAndExecuteNewAgent (3) will enable adapter to load a new agent code
+ into the flash memory and start to execute this new agent code.
+ Bootp/tftp is the default protocol. loadAndExecuteNewAgent is only
+ supported by APC Network Management Cards. Setting
+ this OID to restartWithoutAgent (4) will restart the system and not
+ start the agent. The subsequent time the system restarts the agent will
+ also automatically restart. Setting this OID to
+ resetNetworkAndRestart (5) will set the Boot Mode, IP Address, Subnet
+ Mask, and Default Gateway to defaults, expire any existing DHCP lease
+ and then restart the system. Setting this OID to
+ resetNetworkLeaveModeAndRestart (6) will leave the Boot Mode at the
+ current setting, set the IP Address, Subnet Mask, and Default Gateway to
+ defaults, expire any existing DHCP lease and then restart the system."
+
+ ::= { mcontrol 1 }
+
+-- The mtrapargs group
+-- These OIDs allows APC traps to be sent with additional arguments
+-- which may not be defined in the APC MIB.
+
+mtrapargsInteger OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID allows APC traps to be sent with an integer argument
+ that my not be defined in the APC MIB.
+
+ A get of this OID will return 0."
+ ::= { mtrapargs 1 }
+
+mtrapargsIpAddress OBJECT-TYPE
+ SYNTAX IpAddress
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID allows APC traps to be sent with an IP address argument
+ that my not be defined in the APC MIB.
+
+ A get of this OID will return 0.0.0.0."
+ ::= { mtrapargs 2 }
+
+mtrapargsString OBJECT-TYPE
+ SYNTAX SnmpAdminString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID allows APC traps to be sent with an octet string argument
+ that my not be defined in the APC MIB.
+
+ A get of this OID will return a NULL string."
+ ::= { mtrapargs 3 }
+
+mtrapargsGauge OBJECT-TYPE
+ SYNTAX Gauge
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID allows APC traps to be sent with a Gauge argument
+ that my not be defined in the APC MIB.
+
+ A get of this OID will return 0."
+ ::= { mtrapargs 4 }
+
+mtrapargsTimeTicks OBJECT-TYPE
+ SYNTAX TimeTicks
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID allows APC traps to be sent with a TimeTicks argument
+ that my not be defined in the APC MIB.
+
+ A get of this OID will return 0."
+ ::= { mtrapargs 5 }
+
+mtrapargsInteger02 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID allows APC traps to be sent with an integer argument
+ that my not be defined in the APC MIB.
+
+ A get of this OID will return 0."
+ ::= { mtrapargs 6 }
+
+mtrapargsInteger03 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID allows APC traps to be sent with an integer argument
+ that my not be defined in the APC MIB.
+
+ A get of this OID will return 0."
+ ::= { mtrapargs 7 }
+
+mtrapargsIpAddress02 OBJECT-TYPE
+ SYNTAX IpAddress
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID allows APC traps to be sent with an IP address argument
+ that my not be defined in the APC MIB.
+
+ A get of this OID will return 0.0.0.0."
+ ::= { mtrapargs 8 }
+
+mtrapargsIpAddress03 OBJECT-TYPE
+ SYNTAX IpAddress
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID allows APC traps to be sent with an IP address argument
+ that my not be defined in the APC MIB.
+
+ A get of this OID will return 0.0.0.0."
+ ::= { mtrapargs 9 }
+
+mtrapargsString02 OBJECT-TYPE
+ SYNTAX SnmpAdminString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID allows APC traps to be sent with an octet string argument
+ that my not be defined in the APC MIB.
+
+ A get of this OID will return a NULL string."
+ ::= { mtrapargs 10 }
+
+mtrapargsString03 OBJECT-TYPE
+ SYNTAX SnmpAdminString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID allows APC traps to be sent with an octet string argument
+ that my not be defined in the APC MIB.
+
+ A get of this OID will return a NULL string."
+ ::= { mtrapargs 11 }
+
+mtrapargsGauge02 OBJECT-TYPE
+ SYNTAX Gauge
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID allows APC traps to be sent with a Gauge argument
+ that my not be defined in the APC MIB.
+
+ A get of this OID will return 0."
+ ::= { mtrapargs 12 }
+
+mtrapargsGauge03 OBJECT-TYPE
+ SYNTAX Gauge
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID allows APC traps to be sent with a Gauge argument
+ that my not be defined in the APC MIB.
+
+ A get of this OID will return 0."
+ ::= { mtrapargs 13 }
+
+mtrapargsTimeTicks02 OBJECT-TYPE
+ SYNTAX TimeTicks
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID allows APC traps to be sent with a TimeTicks argument
+ that my not be defined in the APC MIB.
+
+ A get of this OID will return 0."
+ ::= { mtrapargs 14 }
+
+mtrapargsTimeTicks03 OBJECT-TYPE
+ SYNTAX TimeTicks
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID allows APC traps to be sent with a TimeTicks argument
+ that my not be defined in the APC MIB.
+
+ A get of this OID will return 0."
+ ::= { mtrapargs 15 }
+
+mtrapargsString04 OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID allows APC traps to be sent with an octet string argument
+ that my not be defined in the APC MIB.
+
+ A get of this OID will return a NULL string."
+ ::= { mtrapargs 16 }
+
+mtrapargsString05 OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID allows APC traps to be sent with an octet string argument
+ that my not be defined in the APC MIB.
+
+ A get of this OID will return a NULL string."
+ ::= { mtrapargs 17 }
+
+mtrapargsInteger04 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID allows APC traps to be sent with an integer argument
+ that my not be defined in the APC MIB.
+
+ A get of this OID will return 0."
+ ::= { mtrapargs 18 }
+
+mtrapargsInteger05 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID allows APC traps to be sent with an integer argument
+ that my not be defined in the APC MIB.
+
+ A get of this OID will return 0."
+ ::= { mtrapargs 19 }
+
+mtrapargsString06 OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID allows APC traps to be sent with an octet string argument
+ that my not be defined in the APC MIB.
+
+ A get of this OID will return a NULL string."
+ ::= { mtrapargs 20 }
+
+mtrapargsString07 OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID allows APC traps to be sent with an octet string argument
+ that my not be defined in the APC MIB.
+
+ A get of this OID will return a NULL string."
+ ::= { mtrapargs 21 }
+
+mtrapargsString08 OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID allows APC traps to be sent with an octet string argument
+ that my not be defined in the APC MIB.
+
+ A get of this OID will return a NULL string."
+ ::= { mtrapargs 22 }
+
+mtrapargsOctetString OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID allows APC traps to be sent with an octet string argument
+ that my not be defined in the APC MIB.
+
+ A get of this OID will return a NULL string."
+ ::= { mtrapargs 23 }
+
+mtrapargsOctetString02 OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID allows APC traps to be sent with an octet string argument
+ that my not be defined in the APC MIB.
+
+ A get of this OID will return a NULL string."
+ ::= { mtrapargs 24 }
+
+mtrapargsOctetString03 OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID allows APC traps to be sent with an octet string argument
+ that my not be defined in the APC MIB.
+
+ A get of this OID will return a NULL string."
+ ::= { mtrapargs 25 }
+
+mtrapargsOctetString04 OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID allows APC traps to be sent with an octet string argument
+ that my not be defined in the APC MIB.
+
+ A get of this OID will return a NULL string."
+ ::= { mtrapargs 26 }
+
+mtrapargsOctetString05 OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID allows APC traps to be sent with an octet string argument
+ that my not be defined in the APC MIB.
+
+ A get of this OID will return a NULL string."
+ ::= { mtrapargs 27 }
+
+mtrapargsOctetString06 OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID allows APC traps to be sent with an octet string argument
+ that my not be defined in the APC MIB.
+
+ A get of this OID will return a NULL string."
+ ::= { mtrapargs 28 }
+
+mtrapargsOctetString07 OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID allows APC traps to be sent with an octet string argument
+ that my not be defined in the APC MIB.
+
+ A get of this OID will return a NULL string."
+ ::= { mtrapargs 29 }
+
+mtrapargsOctetString08 OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID allows APC traps to be sent with an octet string argument
+ that my not be defined in the APC MIB.
+
+ A get of this OID will return a NULL string."
+ ::= { mtrapargs 30 }
+
+-- the mfiletransfer group
+-- the mfiletransferStatus group
+mfiletransferStatusLastTransferResult OBJECT-TYPE
+ SYNTAX INTEGER {
+ lastFileTransferResultSuccessful (1),
+ lastFileTransferResultNotAvailable (2),
+ lastFileTransferResultFailureUnknown (3),
+ lastFileTransferResultFailureServerInaccessible (4),
+ lastFileTransferResultFailureServerAccessDenied (5),
+ lastFileTransferResultFailureFileNotFound (6),
+ lastFileTransferResultFailureFileTypeUnknown (7),
+ lastFileTransferResultFailureFileCorrupted (8)
+ }
+ ACCESS read-only
+ STATUS deprecated
+ DESCRIPTION
+ "This OID has been deprecated.
+
+ Once mfiletransferControlInitiateFileTransfer is set to a value other than doNotInitiateFileTransfer
+ a file transfer of mfiletransferConfigSettingsFilename will be attempted from either a TFTP or FTP
+ server.
+
+ This OID shows the last attempted file transfer result.
+ lastFileTransferResultSuccessful (1) means the file transfer was successful.
+ lastFileTransferResultNotAvailable (2) means that there have been no previous file transfers.
+ lastFileTransferResultFailureUnknown (3) means that the last file transfer failed for an unknown reason.
+ lastFileTransferResultFailureServerInaccessible (4) means that the TFTP or FTP server could not be found on the network.
+ lastFileTransferResultFailureServerAccessDenied (5) means that the TFTP or FTP server denied access.
+ lastFileTransferResultFailureFileNotFound (6) means that the file could not be located.
+ lastFileTransferResultFailureFileTypeUnknown (7) means the file was examined, but the contents were unknown.
+ lastFileTransferResultFailureFileCorrupt (8) means the transferred file was corrupt."
+
+ ::= { mfiletransferStatus 1 }
+
+-- the mfiletransferConfig group
+-- the mfiletransferConfigSettings group
+
+mfiletransferConfigSettingsFilename OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS deprecated
+ DESCRIPTION
+ "This OID has been deprecated.
+
+ The path and name of the file to transfer using the mfiletransferControlInitiateFileTransfer OID.
+ If the file to transfer exists in the default server directory then the path may be omitted."
+
+ ::= { mfiletransferConfigSettings 1 }
+
+-- the mfiletransferConfigTFTP group
+
+mfiletransferConfigTFTPServerAddress OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS deprecated
+ DESCRIPTION
+ "This OID has been deprecated.
+
+ The IP Address in dotted decimal notation of the TFTP server involved in the file transfer."
+
+ ::= { mfiletransferConfigTFTP 1 }
+
+-- the mfiletransferConfigFTP group
+
+mfiletransferConfigFTPServerAddress OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS deprecated
+ DESCRIPTION
+ "This OID has been deprecated.
+
+ The IP Address in dotted decimal notation of the FTP server involved in the file transfer."
+
+ ::= { mfiletransferConfigFTP 1 }
+
+mfiletransferConfigFTPServerUser OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS deprecated
+ DESCRIPTION
+ "This OID has been deprecated.
+
+ The user identification for logging into the FTP server specified with mfiletransferConfigFTPServerAddress."
+
+ ::= { mfiletransferConfigFTP 2 }
+
+mfiletransferConfigFTPServerPassword OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS deprecated
+ DESCRIPTION
+ "This OID has been deprecated.
+
+ The password for logging into the FTP server specified with mfiletransferConfigFTPServerAddress."
+
+ ::= { mfiletransferConfigFTP 3 }
+
+-- the mfiletransferControl group
+
+mfiletransferControlInitiateFileTransfer OBJECT-TYPE
+ SYNTAX INTEGER {
+ doNotInitiateFileTransfer (1),
+ initiateFileTransferDownloadViaTFTP (2),
+ initiateFileTransferDownloadViaFTP (3)
+ }
+ ACCESS read-write
+ STATUS deprecated
+ DESCRIPTION
+ "This OID has been deprecated.
+
+ Setting this OID to doNotInitiateFileTransfer (1) will do nothing.
+
+ Setting this OID to initiateFileTransferDownloadViaTFTP (2) will attempt to transfer the file named in
+ mfiletransferConfigSettingsFilename from the TFTP Server identified in mfiletransferConfigTFTPAddress.
+
+ Setting this OID to initiateFileTransferDownloadViaFTP (3) will attempt to transfer the file named in
+ mfiletransferConfigSettingsFilename from the FTP Server identified in mfiletransferConfigFTPAddress
+ using mfiletransferConfigFTPUser and mfiletransferConfigFTPPassword for the FTP Server login process."
+
+ ::= { mfiletransferControl 1 }
+-- the battManIdent group
+
+battManIdentProductName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the battery manager."
+ ::= { battManIdent 1 }
+
+battManIdentHardwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery manager network interface hardware revision.
+ This value is set at the factory."
+ ::= { battManIdent 2 }
+
+battManIdentFirmwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery manager network interface firmware revision.
+ This value is set at the factory and can change with firmware update."
+ ::= { battManIdent 3 }
+
+battManIdentDateOfManufacture OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The date the battery manager was manufactured in mm/dd/yyyy format.
+ This value is set at the factory."
+ ::= { battManIdent 4 }
+
+battManIdentModelNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery manager model number character string.
+ This value is set at the factory."
+ ::= { battManIdent 5 }
+
+battManIdentSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery manager serial number character string.
+ This value is set at the factory."
+ ::= { battManIdent 6 }
+
+-- the battManCalib group
+-- system calibration
+
+battManOhmicValueCorrectionFactor OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The system ohmic value correction factor in percent."
+ ::= { battManSystemCalib 1 }
+
+-- unit calibration
+
+battManUnitCalibTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the battManUnitCalibTable."
+ ::= { battManUnitCalib 1 }
+
+battManUnitCalibTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF BattManUnitCalibEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting calibration information from each unit in the system."
+ ::= { battManUnitCalib 2 }
+
+battManUnitCalibEntry OBJECT-TYPE
+ SYNTAX BattManUnitCalibEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The unit to get data from."
+ INDEX { battManUnitCalibIndex }
+ ::= { battManUnitCalibTable 1 }
+
+BattManUnitCalibEntry ::=
+ SEQUENCE {
+ battManUnitCalibIndex INTEGER,
+ battManUnitSerialNumber DisplayString,
+ battManBatteryVoltageZeroCalib INTEGER,
+ battManBatteryVoltageSpanCalib INTEGER
+ }
+
+battManUnitCalibIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index of unit calibration entries in the table."
+ ::= { battManUnitCalibEntry 1 }
+
+battManUnitSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The serial number of the unit."
+ ::= { battManUnitCalibEntry 2 }
+
+battManBatteryVoltageZeroCalib OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The unit battery voltage zero calibration in millivolts."
+ ::= { battManUnitCalibEntry 3 }
+
+battManBatteryVoltageSpanCalib OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The unit battery voltage span calibration in hundredths of percent."
+ ::= { battManUnitCalibEntry 4 }
+
+-- string calibration table
+
+battManStringCalibTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the battManStringCalibTable."
+ ::= { battManStringCalib 1 }
+
+battManStringCalibTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF BattManStringCalibEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting calibration information from each string in the system."
+ ::= { battManStringCalib 2 }
+
+battManStringCalibEntry OBJECT-TYPE
+ SYNTAX BattManStringCalibEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The string to get data from."
+ INDEX { battManStringCalibIndex }
+ ::= { battManStringCalibTable 1 }
+
+BattManStringCalibEntry ::=
+ SEQUENCE {
+ battManStringCalibIndex INTEGER,
+ battManDCCurrentZeroCalib INTEGER,
+ battManACCurrentZeroCalib INTEGER,
+ battManProbeRange INTEGER
+ }
+
+battManStringCalibIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index of string calibration entries in the table."
+ ::= { battManStringCalibEntry 1 }
+
+battManDCCurrentZeroCalib OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The string DC current zero calibration in tenths of amps."
+ ::= { battManStringCalibEntry 2 }
+
+battManACCurrentZeroCalib OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The string AC current zero calibration in tenths of amps."
+ ::= { battManStringCalibEntry 3 }
+
+battManProbeRange OBJECT-TYPE
+ SYNTAX INTEGER {
+ amps1000 (1),
+ amps500 (2),
+ amps100 (3),
+ amps200 (4),
+ amps2000 (5)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The string probe range in amps."
+ ::= { battManStringCalibEntry 4 }
+
+--string 1 battery calibration table
+
+battManString1BatteryCalibTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the battManString1BatteryCalibTable."
+ ::= { battManBatteryCalib 1 }
+
+battManString1BatteryCalibTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF BattManString1BatteryCalibEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting calibration information from each battery in String 1."
+ ::= { battManBatteryCalib 2 }
+
+battManString1BatteryCalibEntry OBJECT-TYPE
+ SYNTAX BattManString1BatteryCalibEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The string to get data from."
+ INDEX { battManString1BatteryCalibIndex }
+ ::= { battManString1BatteryCalibTable 1 }
+
+BattManString1BatteryCalibEntry ::=
+ SEQUENCE {
+ battManString1BatteryCalibIndex INTEGER,
+ battManString1BatteryInterTierOhmicValue INTEGER
+ }
+
+battManString1BatteryCalibIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index of battery calibration entries in the table."
+ ::= { battManString1BatteryCalibEntry 1 }
+
+battManString1BatteryInterTierOhmicValue OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The battery inter-tier ohmic value in ohms. This corresponds to the ohmic
+ value for the positive terminal of the battery."
+ ::= { battManString1BatteryCalibEntry 2 }
+
+--string 2 battery calibration table
+
+battManString2BatteryCalibTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the battManString2BatteryCalibTable."
+ ::= { battManBatteryCalib 3 }
+
+battManString2BatteryCalibTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF BattManString2BatteryCalibEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting calibration information from each battery in String 2."
+ ::= { battManBatteryCalib 4 }
+
+battManString2BatteryCalibEntry OBJECT-TYPE
+ SYNTAX BattManString2BatteryCalibEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The string to get data from."
+ INDEX { battManString2BatteryCalibIndex }
+ ::= { battManString2BatteryCalibTable 1 }
+
+BattManString2BatteryCalibEntry ::=
+ SEQUENCE {
+ battManString2BatteryCalibIndex INTEGER,
+ battManString2BatteryInterTierOhmicValue INTEGER
+ }
+
+battManString2BatteryCalibIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index of battery calibration entries in the table."
+ ::= { battManString2BatteryCalibEntry 1 }
+
+battManString2BatteryInterTierOhmicValue OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The battery inter-tier ohmic value in ohms."
+ ::= { battManString2BatteryCalibEntry 2 }
+
+-- the battManConfig group
+
+battManConfigApplication OBJECT-TYPE
+ SYNTAX INTEGER {
+ silcon (1),
+ other (2)
+ }
+ ACCESS read-write
+ STATUS deprecated
+ DESCRIPTION
+ "This OID has been deprecated."
+ ::= { battManConfig 1 }
+
+battManConfigBatteryChemistry OBJECT-TYPE
+ SYNTAX INTEGER {
+ leadAcid (1),
+ nickel-Cadmium (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The battery chemistry of the monitored batteries:
+ LeadAcid(1) Lead Acid or
+ Nickel-Cadmium(2) Nickel-Cadmium."
+ ::= { battManConfig 2 }
+
+battManConfigBatteryAHCapacity OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The amp hour capacity of the monitored batteries 5-4000 AH."
+ ::= { battManConfig 3 }
+
+battManConfigNumberofStrings OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The number of strings in the battery manager system."
+ ::= { battManConfig 4 }
+
+battManConfigBatteriesperString OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The number of batteries per string."
+ ::= { battManConfig 5 }
+
+
+battManConfigCellsperBattery OBJECT-TYPE
+ SYNTAX INTEGER {
+ oneCell (1),
+ twoCells (2),
+ fourCells (4),
+ sixCells (6)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The number of cells per battery (1, 2, 4 or 6 for lead-acid, 1 or 2 for NiCd."
+ ::= { battManConfig 6 }
+
+
+battManConfigMinCellVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum battery cell voltage alarm limit in millivolts DC."
+ ::= { battManConfig 7 }
+
+battManConfigMaxCellVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum battery cell voltage alarm limit in millivolts DC."
+ ::= { battManConfig 8 }
+
+battManConfigMaxPilotTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum pilot battery temperature alarm limit in tenths of degrees Fahrenheit."
+ ::= { battManConfig 9 }
+
+battManConfigMaxPilotTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum pilot battery temperature alarm limit in tenths of degrees Celsius."
+ ::= { battManConfig 10 }
+
+battManConfigMaxAmbientTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum ambient temperature alarm limit in tenths of degrees Fahrenheit."
+ ::= { battManConfig 11 }
+
+battManConfigMaxAmbientTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum ambient temperature alarm limit in tenths of degrees Celsius."
+ ::= { battManConfig 12 }
+
+battManConfigMinAmbientTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The Minimum Ambient Temperature alarm limit in tenths of degrees Fahrenheit."
+ ::= { battManConfig 13 }
+
+battManConfigMinAmbientTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The Minimum Ambient Temperature alarm limit in tenths of degrees Celsius."
+ ::= { battManConfig 14 }
+
+battManConfigMaxRippleCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum ripple current alarm limit for the monitored battery
+ strings in percent of AH capacity."
+ ::= { battManConfig 15 }
+
+battManConfigMaxCurrentAcceptanceDeviation OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum current acceptance deviation alarm limit in percent."
+ ::= { battManConfig 16 }
+
+battManConfigMonitorWireLength OBJECT-TYPE
+ SYNTAX INTEGER {
+ fiftyFeetOrLess (1),
+ moreThanFiftyFeet (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The monitor wire length:
+ fiftyFeetOrLess (1) indicates that the wire length is less than or equal to 50 feet.
+ moreThanFiftyFeet (2) indicates that the wire length is greater than 50 feet."
+ ::= { battManConfig 17 }
+
+battManConfigDischargeVoltageAlarmLevel OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The discharge voltage alarm level in percent."
+ ::= { battManConfig 18 }
+
+battManConfigAutoAnnunciatorReset OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled (1),
+ enabled (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The annunciator output signal reset method:
+ disabled(1) means the annunciator signal output will be reset when the reset button is pressed.
+ enabled(2) means the annunciator will stop signaling when all alarm conditions clear."
+ ::= { battManConfig 19 }
+
+battManConfigSuspendCellVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "This is used along with the number of cells per battery
+ and the number of batteries per string to determine if
+ a battery string has violated the low voltage limit. If
+ so, the Battery Management System will enter suspend mode.
+ Measured in millivolts DC"
+ ::= { battManConfig 20 }
+
+battManConfigOhmicTestWaitTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The amount of time in seconds after a discharge event before
+ data will be collected for the ohmic value calculation."
+ ::= { battManConfig 21 }
+
+battManConfigNumberOfBoosts OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The number of consecutive times the Battery Management
+ System applies a charge to each battery during a boost
+ cycle. Batteries with a Rated Battery AH Capacity
+ less than or equal to 120 AH will always have a value
+ of one for Number of Boosts."
+ ::= { battManConfig 22 }
+
+-- the battManAlarm group
+
+battManAlarmManagementController OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Management Controller Alarm is :
+ normal(1) no alarm conditions identified
+ alarm(2) an alarm condition exists."
+ ::= { battManAlarm 1 }
+
+battManAlarmBatteries OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Batteries Alarm is :
+ normal(1) no alarm conditions identified
+ alarm(2) an alarm condition exists."
+ ::= { battManAlarm 2 }
+
+battManAlarmCharger OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Charger Alarm is :
+ normal(1) no alarm conditions identified
+ alarm(2) an alarm condition exists."
+ ::= { battManAlarm 3 }
+
+battManAlarmEnvironment OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Environment Alarm is :
+ normal(1) no alarm conditions identified
+ alarm(2) an alarm condition exists."
+ ::= { battManAlarm 4 }
+
+-- the battManSystemStatus group
+
+-- These are system wide parameters
+
+battManSystemAmbientTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The system ambient temperature in tenths of degrees Celsius."
+ ::= { battManSystemStatus 1 }
+
+battManSystemAmbientTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The system ambient temperature in tenths of degrees Fahrenheit."
+ ::= { battManSystemStatus 2 }
+
+battManSystemPilotTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The system pilot temperature in tenths of degrees Celsius."
+ ::= { battManSystemStatus 3 }
+
+battManSystemPilotTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The system pilot temperature in tenths of degrees Fahrenheit."
+ ::= { battManSystemStatus 4 }
+
+battManSystemAmbientHighTempAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "When set to alarm(2), indicates that the system has a high temperature alarm."
+ ::= { battManSystemStatus 5 }
+
+battManSystemAmbientLowTempAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "When set to alarm(2), indicates that the system has a low temperature alarm."
+ ::= { battManSystemStatus 6 }
+
+battManSystemPilotBatteryHighTempAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "When set to alarm(2), indicates that the system has a pilot battery high temperature alarm."
+ ::= { battManSystemStatus 7 }
+
+battManSystemPilotProbeDisconnected OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "When set to alarm(2), indicates that the system pilot probe is disconnected."
+ ::= { battManSystemStatus 8 }
+
+battManSystemAmbientProbeDisconnected OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "When set to alarm(2), indicates that the system ambient probe is disconnected."
+ ::= { battManSystemStatus 9 }
+
+battManSystemConfigurationInvalid OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "When set to alarm(2), indicates that the system is not configured correctly."
+ ::= { battManSystemStatus 10 }
+
+battManSystemSuspendVoltage OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "When set to alarm(2), indicates that the system has suspended voltage scans."
+ ::= { battManSystemStatus 11 }
+
+-- This is a table of input contact parameters
+
+battManInputContactTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the battManInputContactTable."
+ ::= { battManInputContactStatus 1 }
+
+battManInputContactTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF BattManInputContactEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting information from each contact
+ in the system. "
+ ::= { battManInputContactStatus 2 }
+
+battManInputContactEntry OBJECT-TYPE
+ SYNTAX BattManInputContactEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The contact to get data from."
+ INDEX { battManInputContactIndex }
+ ::= { battManInputContactTable 1 }
+
+BattManInputContactEntry ::=
+ SEQUENCE {
+ battManInputContactIndex INTEGER,
+ battManInputContactName DisplayString,
+ battManInputContactAlarmState INTEGER,
+ battManInputContactState INTEGER,
+ battManInputContactNormalState INTEGER,
+ battManInputContactAlarmDelay INTEGER
+ }
+
+battManInputContactIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index of contact entries in the table."
+ ::= { battManInputContactEntry 1 }
+
+battManInputContactName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the input contact."
+ ::= { battManInputContactEntry 2 }
+
+battManInputContactAlarmState OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "When set to alarm(2), indicates that the alarm condition is active for this contact."
+ ::= { battManInputContactEntry 3 }
+
+battManInputContactState OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "When set to open(1), the input contact is in the open state.
+ When set to closed(2), the input contact is in the closed state."
+ ::= { battManInputContactEntry 4 }
+
+battManInputContactNormalState OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "When set to open(1), the input contact is normally open.
+ When set to closed(2), the input contact is normally closed."
+ ::= { battManInputContactEntry 5 }
+
+battManInputContactAlarmDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The input contact alarm delay time in seconds."
+ ::= { battManInputContactEntry 6 }
+
+-- This is a table of battery string parameters
+
+battManStringTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the battManStringTable."
+ ::= { battManStringStatus 1 }
+
+battManStringTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF BattManStringEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting information from each string
+ in the system. "
+ ::= { battManStringStatus 2 }
+
+battManStringEntry OBJECT-TYPE
+ SYNTAX BattManStringEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The string to get data from."
+ INDEX { battManStringIndex }
+ ::= { battManStringTable 1 }
+
+BattManStringEntry ::=
+ SEQUENCE {
+ battManStringIndex INTEGER,
+ battManStringCurrent INTEGER,
+ battManStringRippleCurrent INTEGER,
+ battManStringChargerHighVoltageAlarm INTEGER,
+ battManStringChargerLowVoltageAlarm INTEGER,
+ battManStringCurrentProbeDisconnected INTEGER,
+ battManStringOnBattery INTEGER,
+ battManStringHighRippleCurrent INTEGER,
+ battManStringVoltage INTEGER,
+ battManStringDischargeLess5Seconds INTEGER,
+ battManStringDischarge5to10Seconds INTEGER,
+ battManStringDischarge10to60Seconds INTEGER,
+ battManStringDischargeMore60Seconds INTEGER
+ }
+
+battManStringIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index of string entries in the table."
+ ::= { battManStringEntry 1 }
+
+battManStringCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The string current in tenths of amps."
+ ::= { battManStringEntry 2 }
+
+battManStringRippleCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The string ripple current in tenths of amps."
+ ::= { battManStringEntry 3 }
+
+battManStringChargerHighVoltageAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "When set to alarm(2), indicates that the string charger has a high voltage alarm."
+ ::= { battManStringEntry 4 }
+
+battManStringChargerLowVoltageAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "When set to alarm(2), indicates that the string charger has a low voltage alarm."
+ ::= { battManStringEntry 5 }
+
+battManStringCurrentProbeDisconnected OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "When set to alarm(2), indicates that the string charger probe is disconnected."
+ ::= { battManStringEntry 6 }
+
+battManStringOnBattery OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "When set to alarm(2), indicates that the string is in the on-battery state."
+ ::= { battManStringEntry 7 }
+
+battManStringHighRippleCurrent OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "When set to alarm(2), indicates that the string has a high ripple current."
+ ::= { battManStringEntry 8 }
+
+battManStringVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The sum of the voltages for all of the batteries on a
+ string in millivolts DC."
+ ::= { battManStringEntry 9 }
+
+battManStringDischargeLess5Seconds OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of recorded discharges lasting less than
+ 5 seconds."
+ ::= { battManStringEntry 10 }
+
+battManStringDischarge5to10Seconds OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of recorded discharges lasting between 5
+ and 10 seconds."
+ ::= { battManStringEntry 11 }
+
+battManStringDischarge10to60Seconds OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of recorded discharges lasting between 10
+ and 60 seconds."
+ ::= { battManStringEntry 12 }
+
+battManStringDischargeMore60Seconds OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of recorded discharges lasting more than
+ 60 seconds (1 minute)."
+ ::= { battManStringEntry 13 }
+
+-- the battManString1BatteryStatus group
+
+battManString1BatteryTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the battManString1BatteryTable."
+ ::= { battManBatteryStatus 1 }
+
+battManString1BatteryTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF BattManString1BatteryEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting information from each string
+ in the system. "
+ ::= { battManBatteryStatus 2 }
+
+battManString1BatteryEntry OBJECT-TYPE
+ SYNTAX BattManString1BatteryEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The string to get data from."
+ INDEX { battManString1BatteryIndex }
+ ::= { battManString1BatteryTable 1 }
+
+BattManString1BatteryEntry ::=
+ SEQUENCE {
+ battManString1BatteryIndex INTEGER,
+ battManString1BatteryVoltage INTEGER,
+ battManString1BatteryLowestVoltage INTEGER,
+ battManString1BatteryCellShorted INTEGER,
+ battManString1BatteryOpenFuseOrConnection INTEGER,
+ battManString1BatteryLowCapacity INTEGER,
+ battManString1BatteryHighOhmicValue INTEGER,
+ battManString1BatteryThermalRunaway INTEGER,
+ battManString1BatteryDryout INTEGER,
+ battManString1BatteryUserHighVoltageAlarm INTEGER,
+ battManString1BatteryUserLowVoltageAlarm INTEGER,
+ battManString1BatteryChemHighVoltageAlarm INTEGER,
+ battManString1BatteryChemLowVoltageAlarm INTEGER,
+ battManString1BatteryOpenCell INTEGER
+ }
+
+battManString1BatteryIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index of string entries in the table."
+ ::= { battManString1BatteryEntry 1 }
+
+battManString1BatteryVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery voltage in millivolts DC."
+ ::= { battManString1BatteryEntry 2 }
+
+battManString1BatteryLowestVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The lowest battery discharge voltage during the last power event in millivolts DC."
+ ::= { battManString1BatteryEntry 3 }
+
+battManString1BatteryCellShorted OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "When set to alarm(2), indicates that a battery cell is shorted."
+ ::= { battManString1BatteryEntry 4 }
+
+battManString1BatteryOpenFuseOrConnection OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "When set to alarm(2), indicates that a fuse or connection is open."
+ ::= { battManString1BatteryEntry 5 }
+
+battManString1BatteryLowCapacity OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "When set to alarm(2), indicates a battery has low capacity."
+ ::= { battManString1BatteryEntry 6 }
+
+battManString1BatteryHighOhmicValue OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "When set to alarm(2), indicates a battery has a high ohmic value."
+ ::= { battManString1BatteryEntry 7 }
+
+battManString1BatteryThermalRunaway OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "When set to alarm(2), indicates a battery has a thermal runaway condition."
+ ::= { battManString1BatteryEntry 8 }
+
+battManString1BatteryDryout OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "When set to alarm(2), indicates a battery has a dryout condition."
+ ::= { battManString1BatteryEntry 9 }
+
+battManString1BatteryUserHighVoltageAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "When set to alarm(2), indicates a battery has violated
+ the user level high voltage limit."
+ ::= { battManString1BatteryEntry 10 }
+
+battManString1BatteryUserLowVoltageAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "When set to alarm(2), indicates a battery has violated
+ the user level low voltage limit."
+ ::= { battManString1BatteryEntry 11 }
+
+battManString1BatteryChemHighVoltageAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "When set to alarm(2), indicates a battery has violated
+ the chemistry level high voltage limit."
+ ::= { battManString1BatteryEntry 12 }
+
+battManString1BatteryChemLowVoltageAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "When set to alarm(2), indicates a battery has violated
+ the chemistry level low voltage limit."
+ ::= { battManString1BatteryEntry 13 }
+
+battManString1BatteryOpenCell OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "When set to alarm(2), indicates the battery has an open
+ cell or an inter-connection is abnormal."
+ ::= { battManString1BatteryEntry 14 }
+
+
+-- the battManString2BatteryStatus group
+
+battManString2BatteryTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the battManString2BatteryTable."
+ ::= { battManBatteryStatus 3 }
+
+battManString2BatteryTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF BattManString2BatteryEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting information from each string
+ in the system. "
+ ::= { battManBatteryStatus 4 }
+
+battManString2BatteryEntry OBJECT-TYPE
+ SYNTAX BattManString2BatteryEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The string to get data from."
+ INDEX { battManString2BatteryIndex }
+ ::= { battManString2BatteryTable 1 }
+
+BattManString2BatteryEntry ::=
+ SEQUENCE {
+ battManString2BatteryIndex INTEGER,
+ battManString2BatteryVoltage INTEGER,
+ battManString2BatteryLowestVoltage INTEGER,
+ battManString2BatteryCellShorted INTEGER,
+ battManString2BatteryOpenFuseOrConnection INTEGER,
+ battManString2BatteryLowCapacity INTEGER,
+ battManString2BatteryHighOhmicValue INTEGER,
+ battManString2BatteryThermalRunaway INTEGER,
+ battManString2BatteryDryout INTEGER,
+ battManString2BatteryUserHighVoltageAlarm INTEGER,
+ battManString2BatteryUserLowVoltageAlarm INTEGER,
+ battManString2BatteryChemHighVoltageAlarm INTEGER,
+ battManString2BatteryChemLowVoltageAlarm INTEGER,
+ battManString2BatteryOpenCell INTEGER
+ }
+
+battManString2BatteryIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index of string entries in the table."
+ ::= { battManString2BatteryEntry 1 }
+
+battManString2BatteryVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery voltage in millivolts DC."
+ ::= { battManString2BatteryEntry 2 }
+
+battManString2BatteryLowestVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The lowest battery discharge voltage during the last power event in millivolts DC."
+ ::= { battManString2BatteryEntry 3 }
+
+battManString2BatteryCellShorted OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "When set to alarm(2), indicates that a battery cell is shorted."
+ ::= { battManString2BatteryEntry 4 }
+
+battManString2BatteryOpenFuseOrConnection OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "When set to alarm(2), indicates that a fuse or connection is open."
+ ::= { battManString2BatteryEntry 5 }
+
+battManString2BatteryLowCapacity OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "When set to alarm(2), indicates a battery has low capacity."
+ ::= { battManString2BatteryEntry 6 }
+
+battManString2BatteryHighOhmicValue OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "When set to alarm(2), indicates a battery has a high ohmic value."
+ ::= { battManString2BatteryEntry 7 }
+
+battManString2BatteryThermalRunaway OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "When set to alarm(2), indicates a battery has a thermal runaway condition."
+ ::= { battManString2BatteryEntry 8 }
+
+battManString2BatteryDryout OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "When set to alarm(2), indicates a battery has a dryout condition."
+ ::= { battManString2BatteryEntry 9 }
+
+battManString2BatteryUserHighVoltageAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "When set to alarm(2), indicates a battery has violated
+ the user level high voltage limit."
+ ::= { battManString2BatteryEntry 10 }
+
+battManString2BatteryUserLowVoltageAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "When set to alarm(2), indicates a battery has violated
+ the user level low voltage limit."
+ ::= { battManString2BatteryEntry 11 }
+
+battManString2BatteryChemHighVoltageAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "When set to alarm(2), indicates a battery has violated
+ the chemistry level high voltage limit."
+ ::= { battManString2BatteryEntry 12 }
+
+battManString2BatteryChemLowVoltageAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "When set to alarm(2), indicates a battery has violated
+ the chemistry level low voltage limit."
+ ::= { battManString2BatteryEntry 13 }
+
+battManString2BatteryOpenCell OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "When set to alarm(2), indicates the battery has an open
+ cell or an inter-connection is abnormal."
+ ::= { battManString2BatteryEntry 14 }
+
+-- battery manager control group
+battManRemoteAnnunciatorReset OBJECT-TYPE
+ SYNTAX INTEGER {
+ noOperation (1),
+ reset (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to reset(2) will reset the user interface annunciator.
+ Getting this OID will do nothing and return the noOperation(1) value."
+ ::= { battManControl 1 }
+
+battManResetChargeCurrentDeviationBenchmark OBJECT-TYPE
+ SYNTAX INTEGER {
+ noOperation (1),
+ reset (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to reset(2) will reset the charge current deviation benchmark.
+ Getting this OID will do nothing and return the noOperation(1) value."
+ ::= { battManControl 2 }
+
+battManResetLowestDischargeVoltages OBJECT-TYPE
+ SYNTAX INTEGER {
+ noOperation (1),
+ reset (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to reset(2) will reset the lowest discharge voltages.
+ Getting this OID will do nothing and return the noOperation(1) value."
+ ::= { battManControl 3 }
+
+battManResetDischargeCounters OBJECT-TYPE
+ SYNTAX INTEGER {
+ noOperation (1),
+ reset (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to reset(2) will reset all discharge event counters.
+ Getting this OID will do nothing and return the noOperation(1) value."
+ ::= { battManControl 4 }
+
+-- the battManTestResults group
+
+--string 1 test results table
+
+battManString1OhmicValueLastDischargeInfo OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Informational text showing the date/time, load, and pilot temperature for the string
+ during the last discharge when ohmic values were recorded."
+ ::= { battManTestResults 1 }
+
+battManString1OhmicValueTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the battManString1OhmicValueTable."
+ ::= { battManTestResults 2 }
+
+battManString1OhmicValueTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF BattManString1OhmicValueEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting ohmic value information from each battery in String 1."
+ ::= { battManTestResults 3 }
+
+battManString1OhmicValueEntry OBJECT-TYPE
+ SYNTAX BattManString1OhmicValueEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The string to get data from."
+ INDEX { battManString1OhmicValueIndex }
+ ::= { battManString1OhmicValueTable 1 }
+
+BattManString1OhmicValueEntry ::=
+ SEQUENCE {
+ battManString1OhmicValueIndex INTEGER,
+ battManString1OhmicValueData INTEGER
+ }
+
+battManString1OhmicValueIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery number."
+ ::= { battManString1OhmicValueEntry 1 }
+
+battManString1OhmicValueData OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery inter-tier ohmic value in tenths of milli-Ohms.
+ Note: Zero or negative values are invalid and may indicate
+ faulty calibration of ohmic value correction factors."
+ ::= { battManString1OhmicValueEntry 2 }
+
+battManString1ResponseTestChangeTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the battManString1ResponseTestChangeTable."
+ ::= { battManTestResults 4 }
+
+battManString1ResponseTestChangeTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF BattManString1ResponseTestChangeEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting response test change information from each battery in String 1."
+ ::= { battManTestResults 5 }
+
+battManString1ResponseTestChangeEntry OBJECT-TYPE
+ SYNTAX BattManString1ResponseTestChangeEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The string to get data from."
+ INDEX { battManString1ResponseTestChangeIndex }
+ ::= { battManString1ResponseTestChangeTable 1 }
+
+BattManString1ResponseTestChangeEntry ::=
+ SEQUENCE {
+ battManString1ResponseTestChangeIndex INTEGER,
+ battManString1ResponseTestChangeData INTEGER
+ }
+
+battManString1ResponseTestChangeIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index of the entries in the table."
+ ::= { battManString1ResponseTestChangeEntry 1 }
+
+battManString1ResponseTestChangeData OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery response test change in percent."
+ ::= { battManString1ResponseTestChangeEntry 2 }
+
+battManString2OhmicValueLastDischargeInfo OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Informational text showing the date/time, load, and pilot temperature for the string
+ during the last discharge when ohmic values were recorded."
+ ::= { battManTestResults 6 }
+
+battManString2OhmicValueTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the battManString2OhmicValueTable."
+ ::= { battManTestResults 7 }
+
+battManString2OhmicValueTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF BattManString2OhmicValueEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting ohmic value information from each battery in String 2."
+ ::= { battManTestResults 8 }
+
+battManString2OhmicValueEntry OBJECT-TYPE
+ SYNTAX BattManString2OhmicValueEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The string to get data from."
+ INDEX { battManString2OhmicValueIndex }
+ ::= { battManString2OhmicValueTable 1 }
+
+BattManString2OhmicValueEntry ::=
+ SEQUENCE {
+ battManString2OhmicValueIndex INTEGER,
+ battManString2OhmicValueData INTEGER
+ }
+
+battManString2OhmicValueIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index of battery calibration entries in the table."
+ ::= { battManString2OhmicValueEntry 1 }
+
+battManString2OhmicValueData OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery inter-tier ohmic value in ohms.
+ Note: Zero or negative values are invalid and may indicate
+ faulty calibration of ohmic value correction factors."
+ ::= { battManString2OhmicValueEntry 2 }
+
+battManString2ResponseTestChangeTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the battManString2ResponseTestChangeTable."
+ ::= { battManTestResults 9 }
+
+battManString2ResponseTestChangeTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF BattManString2ResponseTestChangeEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting response test change information from each battery in String 2."
+ ::= { battManTestResults 10 }
+
+battManString2ResponseTestChangeEntry OBJECT-TYPE
+ SYNTAX BattManString2ResponseTestChangeEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The string to get data from."
+ INDEX { battManString2ResponseTestChangeIndex }
+ ::= { battManString2ResponseTestChangeTable 1 }
+
+BattManString2ResponseTestChangeEntry ::=
+ SEQUENCE {
+ battManString2ResponseTestChangeIndex INTEGER,
+ battManString2ResponseTestChangeData INTEGER
+ }
+
+battManString2ResponseTestChangeIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index of the entries in the table."
+ ::= { battManString2ResponseTestChangeEntry 1 }
+
+battManString2ResponseTestChangeData OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery response test change in percent."
+ ::= { battManString2ResponseTestChangeEntry 2 }
+
+battManString1ResponseTestCurrentTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the battManString1ResponseTestCurrentTable."
+ ::= { battManTestResults 11 }
+
+battManString1ResponseTestCurrentTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF BattManString1ResponseTestCurrentEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting response test current information from each battery
+ in String 1."
+ ::= { battManTestResults 12 }
+
+battManString1ResponseTestCurrentEntry OBJECT-TYPE
+ SYNTAX BattManString1ResponseTestCurrentEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The string to get data from."
+ INDEX { battManString1ResponseTestCurrentIndex }
+ ::= { battManString1ResponseTestCurrentTable 1 }
+
+BattManString1ResponseTestCurrentEntry ::=
+ SEQUENCE {
+ battManString1ResponseTestCurrentIndex INTEGER,
+ battManString1ResponseTestCurrentData INTEGER
+ }
+
+battManString1ResponseTestCurrentIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index of the entries in the table."
+ ::= { battManString1ResponseTestCurrentEntry 1 }
+
+battManString1ResponseTestCurrentData OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery response test current in milliamps."
+ ::= { battManString1ResponseTestCurrentEntry 2 }
+
+battManString2ResponseTestCurrentTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the battManString2ResponseTestCurrentTable."
+ ::= { battManTestResults 13 }
+
+battManString2ResponseTestCurrentTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF BattManString2ResponseTestCurrentEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting response test current information from each battery
+ in String 2."
+ ::= { battManTestResults 14 }
+
+battManString2ResponseTestCurrentEntry OBJECT-TYPE
+ SYNTAX BattManString2ResponseTestCurrentEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The string to get data from."
+ INDEX { battManString2ResponseTestCurrentIndex }
+ ::= { battManString2ResponseTestCurrentTable 1 }
+
+BattManString2ResponseTestCurrentEntry ::=
+ SEQUENCE {
+ battManString2ResponseTestCurrentIndex INTEGER,
+ battManString2ResponseTestCurrentData INTEGER
+ }
+
+battManString2ResponseTestCurrentIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index of the entries in the table."
+ ::= { battManString2ResponseTestCurrentEntry 1 }
+
+battManString2ResponseTestCurrentData OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery response test current in milliamps."
+ ::= { battManString2ResponseTestCurrentEntry 2 }
+
+battManString1ResponseTestCurrentBenchmarkTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the battManString1ResponseTestCurrentBenchmarkTable."
+ ::= { battManTestResults 15 }
+
+battManString1ResponseTestCurrentBenchmarkTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF BattManString1ResponseTestCurrentBenchmarkEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting response test current benchmark information from
+ each battery in String 1."
+ ::= { battManTestResults 16 }
+
+battManString1ResponseTestCurrentBenchmarkEntry OBJECT-TYPE
+ SYNTAX BattManString1ResponseTestCurrentBenchmarkEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The string to get data from."
+ INDEX { battManString1ResponseTestCurrentBenchmarkIndex }
+ ::= { battManString1ResponseTestCurrentBenchmarkTable 1 }
+
+BattManString1ResponseTestCurrentBenchmarkEntry ::=
+ SEQUENCE {
+ battManString1ResponseTestCurrentBenchmarkIndex INTEGER,
+ battManString1ResponseTestCurrentBenchmarkData INTEGER
+ }
+
+battManString1ResponseTestCurrentBenchmarkIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index of the entries in the table."
+ ::= { battManString1ResponseTestCurrentBenchmarkEntry 1 }
+
+battManString1ResponseTestCurrentBenchmarkData OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery response test current benchmark in milliamps."
+ ::= { battManString1ResponseTestCurrentBenchmarkEntry 2 }
+
+battManString2ResponseTestCurrentBenchmarkTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the battManString2ResponseTestCurrentBenchmarkTable."
+ ::= { battManTestResults 17 }
+
+battManString2ResponseTestCurrentBenchmarkTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF BattManString2ResponseTestCurrentBenchmarkEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting response test current benchmark information from
+ each battery in String 2."
+ ::= { battManTestResults 18 }
+
+battManString2ResponseTestCurrentBenchmarkEntry OBJECT-TYPE
+ SYNTAX BattManString2ResponseTestCurrentBenchmarkEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The string to get data from."
+ INDEX { battManString2ResponseTestCurrentBenchmarkIndex }
+ ::= { battManString2ResponseTestCurrentBenchmarkTable 1 }
+
+BattManString2ResponseTestCurrentBenchmarkEntry ::=
+ SEQUENCE {
+ battManString2ResponseTestCurrentBenchmarkIndex INTEGER,
+ battManString2ResponseTestCurrentBenchmarkData INTEGER
+ }
+
+battManString2ResponseTestCurrentBenchmarkIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index of the entries in the table."
+ ::= { battManString2ResponseTestCurrentBenchmarkEntry 1 }
+
+battManString2ResponseTestCurrentBenchmarkData OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery response test current benchmark in milliamps."
+ ::= { battManString2ResponseTestCurrentBenchmarkEntry 2 }
+
+-- battManUnitStatus
+
+battManUnitStatusTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the battManUnitStatusTable."
+ ::= { battManUnitStatus 1 }
+
+battManUnitStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF BattManUnitStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting status information from each unit in the system."
+ ::= { battManUnitStatus 2 }
+
+battManUnitStatusEntry OBJECT-TYPE
+ SYNTAX BattManUnitStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The unit to get data from."
+ INDEX { battManUnitStatusIndex }
+ ::= { battManUnitStatusTable 1 }
+
+BattManUnitStatusEntry ::=
+ SEQUENCE {
+ battManUnitStatusIndex INTEGER,
+ battManUnitStatusSerialNumber DisplayString,
+ battManUnitHardwareRev INTEGER,
+ battManUnitFirmwareRev INTEGER,
+ battManUnitCommLoss INTEGER,
+ battManUnitRelayStuck INTEGER
+ }
+
+battManUnitStatusIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index of unit status entries in the table."
+ ::= { battManUnitStatusEntry 1 }
+
+battManUnitStatusSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery manager unit serial number character string.
+ This value is set at the factory."
+ ::= { battManUnitStatusEntry 2 }
+
+battManUnitHardwareRev OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery manager unit hardware revision.
+ This value is set at the factory."
+ ::= { battManUnitStatusEntry 3 }
+
+battManUnitFirmwareRev OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery manager unit firmware revision.
+ This value is set at the factory and can change with firmware update."
+ ::= { battManUnitStatusEntry 4 }
+
+battManUnitCommLoss OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "When set to alarm(2), indicates the system has lost
+ communication with the unit."
+ ::= { battManUnitStatusEntry 5 }
+
+battManUnitRelayStuck OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "When set to alarm(2), indicates the unit monitor relay
+ is stuck."
+ ::= { battManUnitStatusEntry 6 }
+
+
+-- the xPDUIdent group
+
+xPDUIdentProductName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the PDU."
+ ::= { xPDUIdent 1 }
+
+xPDUIdentHardwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The hardware revision of the PDU.
+ This value is set at the factory."
+ ::= { xPDUIdent 2 }
+
+xPDUIdentFirmwareAppRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An ID string identifying the application firmware revision of the PDU."
+ ::= { xPDUIdent 3 }
+
+xPDUIdentFirmwareAppOSRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An ID string identifying the application operating system firmware revision of the PDU."
+ ::= { xPDUIdent 4 }
+
+xPDUIdentFirmwareControllerRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An ID string identifying the PDU controller firmware revision."
+ ::= { xPDUIdent 5 }
+
+xPDUIdentDateOfManufacture OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The date when the PDU was manufactured in mm/dd/yyyy format.
+ This value is set at the factory."
+ ::= { xPDUIdent 6 }
+
+xPDUIdentModelNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the model number of
+ the PDU. This value is set at the factory."
+ ::= { xPDUIdent 7 }
+
+xPDUIdentSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the serial number of
+ the PDU. This value is set at the factory."
+ ::= { xPDUIdent 8 }
+
+-- the xPDUDevice group
+
+xPDUDeviceNominalMainInputVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The nominal main input voltage to the PDU. Measured in Volts,
+ line-to-line for a 3-wire (delta) service or line-to-neutral for a
+ 4-wire (wye) service."
+ ::= { xPDUDevice 1 }
+
+xPDUDeviceServiceType OBJECT-TYPE
+ SYNTAX INTEGER {
+ threeWire (1),
+ fourWire (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The type of utility input to the PDU. Either 3 wires (delta), or 4 wires (wye)."
+ ::= { xPDUDevice 2 }
+
+xPDUDeviceNominalOutputVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The nominal line-to-neutral output voltage to the load measured in Volts."
+ ::= { xPDUDevice 3 }
+
+xPDUDeviceMainInputBreakerRating OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The rating of the main input breaker measured in Amps."
+ ::= { xPDUDevice 4 }
+
+xPDUDevicePanelBreakerRating OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The rating of the panel breaker measured in Amps."
+ ::= { xPDUDevice 5 }
+
+xPDUDeviceTransformerPresent OBJECT-TYPE
+ SYNTAX INTEGER {
+ notPresent (1),
+ present (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates whether or not a transformer is installed in the PDU."
+ ::= { xPDUDevice 6 }
+
+xPDUDeviceLoadTieBreakerPresent OBJECT-TYPE
+ SYNTAX INTEGER {
+ notPresent (1),
+ present (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates whether or not a load tie breaker is installed in the PDU."
+ ::= { xPDUDevice 7 }
+
+xPDUDeviceLoadTestPortPresent OBJECT-TYPE
+ SYNTAX INTEGER {
+ notPresent (1),
+ present (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates whether or not a load test port is installed in the PDU."
+ ::= { xPDUDevice 8 }
+
+xPDUDeviceFusesPresent OBJECT-TYPE
+ SYNTAX INTEGER {
+ notPresent (1),
+ present (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates whether or not the UPS feed from the PDU includes fuses."
+ ::= { xPDUDevice 9 }
+
+xPDUDeviceFansPresent OBJECT-TYPE
+ SYNTAX INTEGER {
+ notPresent (1),
+ present (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates whether or not cooling fans are installed in the PDU."
+ ::= { xPDUDevice 10 }
+
+xPDUDeviceBypassInputPresent OBJECT-TYPE
+ SYNTAX INTEGER {
+ notPresent (1),
+ present (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates whether or not the PDU is equipped with a second feed for
+ the UPS's bypass input."
+ ::= { xPDUDevice 11 }
+
+xPDUDeviceCrossTieOutputPresent OBJECT-TYPE
+ SYNTAX INTEGER {
+ notPresent (1),
+ present (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates whether or not the PDU is equipped with a cross-tie output."
+ ::= { xPDUDevice 12 }
+
+xPDUDeviceEarthGroundMonitorPresent OBJECT-TYPE
+ SYNTAX INTEGER {
+ notPresent (1),
+ present (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates whether or not the PDU can provide ground current measurements."
+ ::= { xPDUDevice 13 }
+
+xPDUDeviceInfraStruXureType OBJECT-TYPE
+ SYNTAX INTEGER {
+ typeB (1),
+ typeC (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the configuration of this PDU system.
+ Type-B PDU is in a distributed UPS system and has bypass capabilities.
+ Type-C PDU receives power from a larger central UPS."
+ ::= { xPDUDevice 14 }
+
+-- Main Input
+
+xPDUMainInputOverVoltThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..30)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold above which an input over voltage condition will be generated.
+ Specified as percent deviation from nominal."
+ ::= { xPDUMainInput 1 }
+
+xPDUMainInputUnderVoltThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..30)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold below which an input under voltage condition will be generated.
+ Specified as percent deviation from nominal.
+ A value of zero indicates that the threshold is disabled."
+ ::= { xPDUMainInput 2 }
+
+-- Main Input Voltage Table
+
+xPDUMainInputVoltageTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of Main input voltage entries."
+ ::= { xPDUMainInput 3 }
+
+xPDUMainInputVoltagePhaseTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF XPDUMainInputVoltagePhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of input voltage table entries. The number of
+ entries are the phase entries.
+ The number of entries is contained in the
+ xPDUMainInputVoltageTableSize OID."
+ ::= { xPDUMainInput 4 }
+
+ xPDUMainInputVoltagePhaseEntry OBJECT-TYPE
+ SYNTAX XPDUMainInputVoltagePhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular main input voltage phase."
+ INDEX { xPDUMainInputVoltagePhaseIndex }
+ ::= { xPDUMainInputVoltagePhaseTable 1 }
+
+ XPDUMainInputVoltagePhaseEntry ::= SEQUENCE {
+ xPDUMainInputVoltagePhaseIndex INTEGER,
+ xPDUMainInputVoltageLtoL INTEGER,
+ xPDUMainInputVoltageLtoN INTEGER
+ }
+
+ xPDUMainInputVoltagePhaseIndex OBJECT-TYPE
+ SYNTAX INTEGER{
+ phase1(1),
+ phase2(2),
+ phase3(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Description of each input phase entry in the table."
+ ::= { xPDUMainInputVoltagePhaseEntry 1 }
+
+ xPDUMainInputVoltageLtoL OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Line-to-line PDU input voltage when an isolation transformer is present,
+ or -1 if no transformer present in this PDU. Measured in tenths of Volts."
+ ::= { xPDUMainInputVoltagePhaseEntry 2 }
+
+ xPDUMainInputVoltageLtoN OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Line-to-neutral PDU input voltage when an isolation transformer is not present,
+ or -1 if a transformer is present in this PDU. Measured in tenths of Volts."
+ ::= { xPDUMainInputVoltagePhaseEntry 3 }
+
+
+xPDUBypassInputOverVoltThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..30)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold above which a bypass input over voltage condition will be generated.
+ Specified as percent deviation from nominal."
+ ::= { xPDUBypassInput 1 }
+
+xPDUBypassInputUnderVoltThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..30)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold below which an bypass input under voltage condition will be generated.
+ Specified as percent deviation from nominal.
+ A value of zero indicates that the threshold is disabled."
+ ::= { xPDUBypassInput 2 }
+
+-- Bypass Input Voltage Table
+
+xPDUBypassInputVoltagePhaseTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of bypass input voltage entries."
+ ::= { xPDUBypassInput 3 }
+
+xPDUBypassInputVoltagePhaseTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF XPDUBypassInputVoltagePhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of output table entries. The number of
+ entries are the phase entries.
+ The number of entries is contained in the
+ xPDUBypassInputVoltagePhaseTableSize OID."
+ ::= { xPDUBypassInput 4 }
+
+ xPDUBypassInputVoltagePhaseEntry OBJECT-TYPE
+ SYNTAX XPDUBypassInputVoltagePhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular bypass input voltage phase."
+ INDEX { xPDUBypassInputVoltagePhaseIndex }
+ ::= { xPDUBypassInputVoltagePhaseTable 1 }
+
+ XPDUBypassInputVoltagePhaseEntry ::= SEQUENCE {
+ xPDUBypassInputVoltagePhaseIndex INTEGER,
+ xPDUBypassInputVoltageLtoL INTEGER,
+ xPDUBypassInputVoltageLtoN INTEGER
+ }
+
+ xPDUBypassInputVoltagePhaseIndex OBJECT-TYPE
+ SYNTAX INTEGER{
+ phase1(1),
+ phase2(2),
+ phase3(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index of each bypass input phase entry in the table."
+ ::= { xPDUBypassInputVoltagePhaseEntry 1 }
+
+ xPDUBypassInputVoltageLtoL OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Line-to-line bypass input voltage, or -1 if no bypass
+ feed is present in this PDU. Measured in tenths of Volts."
+ ::= { xPDUBypassInputVoltagePhaseEntry 2 }
+
+ xPDUBypassInputVoltageLtoN OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Line-to-neutral bypass input voltage, or -1 if no bypass
+ feed is present in this PDU. Measured in tenths of Volts."
+ ::= { xPDUBypassInputVoltagePhaseEntry 3 }
+
+-- UPS Input Table
+
+xPDUUPSInputVoltagePhaseTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of UPS input voltage entries."
+ ::= { xPDUUPSInput 1 }
+
+xPDUUPSInputVoltagePhaseTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF XPDUUPSInputVoltagePhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of UPS input table entries. The number of
+ entries are the phase entries.
+ The number of entries is contained in the
+ xPDUUPSInputVoltagePhaseTableSize OID."
+ ::= { xPDUUPSInput 2 }
+
+ xPDUUPSInputVoltagePhaseEntry OBJECT-TYPE
+ SYNTAX XPDUUPSInputVoltagePhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular UPS input voltage phase."
+ INDEX { xPDUUPSInputVoltagePhaseIndex }
+ ::= { xPDUUPSInputVoltagePhaseTable 1 }
+
+ XPDUUPSInputVoltagePhaseEntry ::= SEQUENCE {
+ xPDUUPSInputVoltagePhaseIndex INTEGER,
+ xPDUUPSInputVoltageLtoNPresent INTEGER
+ }
+
+ xPDUUPSInputVoltagePhaseIndex OBJECT-TYPE
+ SYNTAX INTEGER{
+ phase1(1),
+ phase2(2),
+ phase3(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Description of each UPS input phase entry in the table."
+ ::= { xPDUUPSInputVoltagePhaseEntry 1 }
+
+ xPDUUPSInputVoltageLtoNPresent OBJECT-TYPE
+ SYNTAX INTEGER {
+ notPresent (1),
+ present (2),
+ unknown (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates whether or not voltage is present at the UPS feed."
+ ::= { xPDUUPSInputVoltagePhaseEntry 2 }
+
+-- System Output
+
+xPDUSystemOutputFrequency OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The system output frequency in tenths of Hertz."
+ ::= { xPDUSystemOutput 1 }
+
+xPDUSystemOutputNeutralCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Shows the neutral current measured at the system output in tenths of Amps."
+ ::= { xPDUSystemOutput 2 }
+
+xPDUSystemOutputTotalPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Shows the total system output power in tenths of kW."
+ ::= { xPDUSystemOutput 3 }
+
+xPDUSystemOutputTotalApparentPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Shows the total system output power in tenths of kVA."
+ ::= { xPDUSystemOutput 4 }
+
+xPDUSystemOutputTotalPowerFactor OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the total power factor of the system output.
+ A value of 100 representing a unity power factor (1.00).
+ Measured in hundredths."
+ ::= { xPDUSystemOutput 5 }
+
+xPDUSystemOutputFrequencyTolerance OBJECT-TYPE
+ SYNTAX INTEGER{
+ freqToleranceOff (1),
+ freqTolerancePointTwo (2),
+ freqTolerancePointFive (3),
+ freqToleranceOne (4),
+ freqToleranceOnePointFive (5),
+ freqToleranceTwo (6),
+ freqToleranceThree (7),
+ freqToleranceFour (8),
+ freqToleranceFive (9),
+ freqToleranceNine (10)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Shows the circuit panel output frequency tolerance in Hertz."
+ ::= { xPDUSystemOutput 6 }
+
+xPDUSystemOutputMaxKWPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Defines 100% load in kW.
+ Purpose is to set to match UPS capabilities."
+ ::= { xPDUSystemOutput 7 }
+
+xPDUSystemOutputOverVoltThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..30)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold above which an output over voltage condition will be generated.
+ Specified as percent deviation from nominal."
+ ::= { xPDUSystemOutput 8 }
+
+xPDUSystemOutputUnderVoltThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..30)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold below which an output under voltage condition will be generated.
+ Specified as percent deviation from nominal.
+ A value of zero indicates that the threshold is disabled."
+ ::= { xPDUSystemOutput 9 }
+
+
+xPDUSystemOutputOverCurrentThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..110)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold above which an over current condition will be generated.
+ Specified as a percent of the panel breaker rating.
+ A value of zero indicates that the threshold is disabled."
+ ::= { xPDUSystemOutput 10 }
+
+xPDUSystemOutputOverCurrentNeutralThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..110)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold above which an Over current neutral condition will be generated.
+ Specified as a percent of the panel breaker rating.
+ A value of zero indicates that the threshold is disabled."
+ ::= { xPDUSystemOutput 11 }
+
+xPDUSystemOutputUnderCurrentThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold below which an under current condition will be generated.
+ Specified as a percent of the panel breaker rating.
+ A value of zero indicates that the threshold is disabled."
+ ::= { xPDUSystemOutput 12 }
+
+xPDUSystemOutputTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of System Output phase entries."
+ ::= { xPDUSystemOutput 13 }
+
+xPDUSystemOutputPhaseTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF XPDUSystemOutputPhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of system output table entries.
+ The number of entries is contained in the
+ xPDUSystemOutputTableSize OID."
+ ::= { xPDUSystemOutput 14 }
+
+ xPDUSystemOutputPhaseEntry OBJECT-TYPE
+ SYNTAX XPDUSystemOutputPhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular system output phase."
+ INDEX { xPDUSystemOutputPhaseIndex }
+ ::= { xPDUSystemOutputPhaseTable 1 }
+
+ XPDUSystemOutputPhaseEntry ::= SEQUENCE {
+ xPDUSystemOutputPhaseIndex INTEGER,
+ xPDUSystemOutputVoltageLtoL INTEGER,
+ xPDUSystemOutputVoltageLtoN INTEGER,
+ xPDUSystemOutputPhaseCurrent INTEGER,
+ xPDUSystemOutputPower INTEGER,
+ xPDUSystemOutputApparentPower INTEGER,
+ xPDUSystemOutputPowerFactor INTEGER
+ }
+
+ xPDUSystemOutputPhaseIndex OBJECT-TYPE
+ SYNTAX INTEGER{
+ phase1(1),
+ phase2(2),
+ phase3(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Description of each output phase entry in the table."
+ ::= { xPDUSystemOutputPhaseEntry 1 }
+
+ xPDUSystemOutputVoltageLtoL OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Line-to-line system output voltage available at the circuit panel.
+ Measured in tenths of Volts."
+ ::= { xPDUSystemOutputPhaseEntry 2 }
+
+ xPDUSystemOutputVoltageLtoN OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Line-to-neutral system output voltage available at the circuit panel.
+ Measured in tenths of Volts."
+ ::= { xPDUSystemOutputPhaseEntry 3 }
+
+
+ xPDUSystemOutputPhaseCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "System load current per phase. Measured in tenths of Amps."
+ ::= { xPDUSystemOutputPhaseEntry 4 }
+
+ xPDUSystemOutputPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "System output power per phase. Measured in tenths of kW."
+ ::= { xPDUSystemOutputPhaseEntry 5 }
+
+ xPDUSystemOutputApparentPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "System output power per phase. Measured in tenths of kVA."
+ ::= { xPDUSystemOutputPhaseEntry 6 }
+
+ xPDUSystemOutputPowerFactor OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the Power Factor of the system output per phase.
+ A value of 100 representing a unity Power Factor (1.00).
+ Measured in hundredths."
+ ::= { xPDUSystemOutputPhaseEntry 7 }
+
+xPDUGroundCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Shows the current measured in the earth ground conductor.
+ Measured in tenths of Amps, or -1 if not available."
+ ::= { xPDUGroundMonitorPoint 1 }
+
+xPDUGroundCurrentThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..50)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold above which a ground current over current
+ condition will be generated. Specified in tenths of Amps."
+ ::= { xPDUGroundMonitorPoint 2 }
+
+-- System Breakers
+
+xPDUSystemBreakerTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of system breaker entries."
+ ::= { xPDUSystemBreakers 1 }
+
+xPDUSystemBreakerTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF XPDUSystemBreakerEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of system breaker entries.
+ The number of entries is contained in the
+ xPDUSystemBreakerTableSize OID."
+ ::= { xPDUSystemBreakers 2 }
+
+ xPDUSystemBreakerEntry OBJECT-TYPE
+ SYNTAX XPDUSystemBreakerEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular system breaker."
+ INDEX { xPDUSystemBreakerTableIndex }
+ ::= { xPDUSystemBreakerTable 1 }
+
+ XPDUSystemBreakerEntry ::= SEQUENCE {
+ xPDUSystemBreakerTableIndex INTEGER,
+ xPDUSystemBreakerDescription DisplayString,
+ xPDUSystemBreakerPosition INTEGER
+ }
+
+ xPDUSystemBreakerTableIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index of system breaker entries in the table."
+ ::= { xPDUSystemBreakerEntry 1 }
+
+xPDUSystemBreakerDescription OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..79))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A brief description of the system breakers."
+ ::= { xPDUSystemBreakerEntry 2 }
+
+ xPDUSystemBreakerPosition OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2),
+ unknown (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates whether this breaker is open(1) or closed(2)."
+ ::= { xPDUSystemBreakerEntry 3 }
+
+-- Branch Breakers (Breaker Panel)
+
+xPDUNumOfBranchBreakers OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of branch breakers (panel positions) in the Panel.
+ returns 42 for a 1-panel or 84 for a 2-panel system."
+ ::= { xPDUBranchBreakers 1 }
+
+-- Branch Breakers Table
+
+xPDUBranchBreakerTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of branch breaker entries determined by the xPDUNumOfBranchBreakers OID."
+ ::= { xPDUBranchBreakers 2 }
+
+xPDUBranchBreakerTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF XPDUBranchBreakerEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of branch breaker table entries. The
+ number of entries is given by the value of xPDUBranchBreakerTableSize
+ The number of entries is contained in the xPDUBranchBreakerTableSize OID."
+ ::= { xPDUBranchBreakers 3 }
+
+ xPDUBranchBreakerEntry OBJECT-TYPE
+ SYNTAX XPDUBranchBreakerEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular branch breaker (panel position)."
+ INDEX { xPDUBranchBreakerTableIndex }
+ ::= { xPDUBranchBreakerTable 1 }
+
+ XPDUBranchBreakerEntry ::= SEQUENCE {
+ xPDUBranchBreakerTableIndex INTEGER,
+ xPDUBranchBreakerRating INTEGER,
+ xPDUBranchBreakerRDPFeed INTEGER,
+ xPDUBranchBreakerTieIndicator INTEGER,
+ xPDUBranchBreakerCurrent INTEGER,
+ xPDUBranchBreakerOverCurrentThreshold INTEGER,
+ xPDUBranchBreakerUnderCurrentThreshold INTEGER,
+ xPDUBranchBreakerMaxCurrentThreshold INTEGER,
+ xPDUBranchBreakerMinCurrentThreshold INTEGER,
+ xPDUBranchBreakerName DisplayString,
+ xPDUBranchBreakerLocation DisplayString
+
+ }
+
+ xPDUBranchBreakerTableIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index of branch breaker entries in the table."
+ ::= { xPDUBranchBreakerEntry 1 }
+
+ xPDUBranchBreakerRating OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates current rating of this breaker.
+ 0=Breaker is not present.
+ 1=Earth leakage connection.
+ 2=Neutral connection.
+ A value greater than 2 indicates breaker current rating in Amps.
+ A value above 60 Amp will signify a remote feed.
+ The xPDUBranchBreakerRDPFeed OID will indicate which breakers are
+ configured as a remote drop.
+ Note: When setting branch circuit thresholds/ratings for an entry,
+ all positions tied (see the xPDUBranchBreakerTieIndicator OID)
+ to this entry will inherit the new threshold/rating."
+ ::= { xPDUBranchBreakerEntry 2 }
+
+ xPDUBranchBreakerRDPFeed OBJECT-TYPE
+ SYNTAX INTEGER {
+ remoteDistribution (1),
+ noRemoteDistribution (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates that a breaker position is feeding a remote
+ distribution panel."
+ ::= { xPDUBranchBreakerEntry 3 }
+
+ xPDUBranchBreakerTieIndicator OBJECT-TYPE
+ SYNTAX INTEGER {
+ breakerUnTied (1),
+ breakerTied (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates whether or not the breaker in this position
+ is logically associated with the breaker immediately below it.
+ This setting is used grouping the breakers feeding
+ a multi-pole branch circuit.
+ Note: When setting an entry's branch breaker tie indicator to breakerTied,
+ all the positions that are tied to this breaker will take on the rating
+ and thresholds for this entry of the table."
+ ::= { xPDUBranchBreakerEntry 4 }
+
+ xPDUBranchBreakerCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the branch current in tenths of Amps or -1 when not available."
+ ::= { xPDUBranchBreakerEntry 5 }
+
+ xPDUBranchBreakerOverCurrentThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold above which a branch circuit high current
+ condition will be generated.
+ Specified as a percent of the branch breaker rating.
+ A value of zero indicates that the threshold is disabled.
+ Note: When setting branch circuit thresholds/ratings for an entry,
+ all positions tied (see the xPDUBranchBreakerTieIndicator OID)
+ to this entry will inherit the new threshold/rating."
+ ::= { xPDUBranchBreakerEntry 6 }
+
+ xPDUBranchBreakerUnderCurrentThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold below which a branch circuit low current
+ condition will be generated.
+ Specified as a percent of the branch breaker rating.
+ A value of zero indicates that the threshold is disabled.
+ Note: When setting branch circuit thresholds/ratings for an entry,
+ all positions tied (see the xPDUBranchBreakerTieIndicator OID)
+ to this entry will inherit the new threshold/rating."
+ ::= { xPDUBranchBreakerEntry 7 }
+
+ xPDUBranchBreakerMaxCurrentThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold above which a branch circuit maximum current
+ condition will be generated.
+ Specified as a percent of the branch breaker rating.
+ A value of zero indicates that the threshold is disabled.
+ Note: When setting branch circuit thresholds/ratings for an entry,
+ all positions tied (see the xPDUBranchBreakerTieIndicator OID)
+ to this entry will inherit the new threshold/rating."
+ ::= { xPDUBranchBreakerEntry 8 }
+
+ xPDUBranchBreakerMinCurrentThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold below which a branch circuit minimum current
+ condition will be generated.
+ Specified as a percent of the branch breaker rating.
+ A value of zero indicates that the threshold is disabled.
+ Note: When setting branch circuit thresholds/ratings for an entry,
+ all positions tied (see the xPDUBranchBreakerTieIndicator OID)
+ to this entry will inherit the new threshold/rating."
+ ::= { xPDUBranchBreakerEntry 9 }
+
+ xPDUBranchBreakerName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The description of the purpose/use of the breaker."
+ ::= { xPDUBranchBreakerEntry 10 }
+
+ xPDUBranchBreakerLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The description of the location of the breaker."
+ ::= { xPDUBranchBreakerEntry 11 }
+
+
+-- the xPDUInputContacts group
+
+xPDUInputContactNumContacts OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of contacts supported by the PDU."
+ ::= { xPDUInputContacts 1 }
+
+xPDUInputContactTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of input contact entries."
+ ::= { xPDUInputContacts 2 }
+
+xPDUInputContactTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF XPDUInputContactEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of contacts supported by the PDU.
+ The number of entries is contained in the
+ xPDUInputContactTableSize OID."
+ ::= { xPDUInputContacts 3 }
+
+xPDUInputContactEntry OBJECT-TYPE
+ SYNTAX XPDUInputContactEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A contact entry containing information for a given contact."
+ INDEX { xPDUInputContactNumber }
+ ::= { xPDUInputContactTable 1 }
+
+XPDUInputContactEntry ::=
+ SEQUENCE {
+ xPDUInputContactNumber INTEGER,
+ xPDUInputContactName DisplayString,
+ xPDUInputContactNormalState INTEGER,
+ xPDUInputContactCurrentState INTEGER
+ }
+
+xPDUInputContactNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An index identifying the contact on the PDU."
+ ::= { xPDUInputContactEntry 1 }
+
+xPDUInputContactName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The description of the purpose/use of the contact."
+ ::= { xPDUInputContactEntry 2 }
+
+xPDUInputContactNormalState OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The normal operating position of the contact."
+ ::= { xPDUInputContactEntry 3 }
+
+xPDUInputContactCurrentState OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2),
+ unknown (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This value indicates the current state of the contact."
+ ::= { xPDUInputContactEntry 4 }
+
+-- the xPDUOutputRelays group
+
+xPDUOutputRelaysNumRelays OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of output relays supported by the PDU."
+ ::= { xPDUOutputRelays 1 }
+
+xPDUOutputRelaysTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of output relay entries."
+ ::= { xPDUOutputRelays 2 }
+
+xPDUOutputRelayTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF XPDUOutputRelayEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of output relays supported by the PDU.
+ The number of entries is contained in the
+ xPDUOutputRelayTableSize OID."
+ ::= { xPDUOutputRelays 3 }
+
+xPDUOutputRelayEntry OBJECT-TYPE
+ SYNTAX XPDUOutputRelayEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A output relay entry containing information for a given contact."
+ INDEX { xPDUOutputRelayNumber }
+ ::= { xPDUOutputRelayTable 1 }
+
+XPDUOutputRelayEntry ::=
+ SEQUENCE {
+ xPDUOutputRelayNumber INTEGER,
+ xPDUOutputRelayName DisplayString,
+ xPDUOutputRelayNormalState INTEGER,
+ xPDUOutputRelayCurrentState INTEGER
+ }
+
+xPDUOutputRelayNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An index identifying the output relay on the PDU."
+ ::= { xPDUOutputRelayEntry 1 }
+
+xPDUOutputRelayName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The description of the purpose/use of the output relay."
+ ::= { xPDUOutputRelayEntry 2 }
+
+xPDUOutputRelayNormalState OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The normal operating position of the output relay."
+ ::= { xPDUOutputRelayEntry 3 }
+
+xPDUOutputRelayCurrentState OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2),
+ unknown (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This value indicates the current state of the output relay."
+ ::= { xPDUOutputRelayEntry 4 }
+
+-- the xPDUMiscGroup
+
+xPDUEPOMode OBJECT-TYPE
+ SYNTAX INTEGER {
+ armed (1),
+ disarmed (2),
+ unknown (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates whether the EPO System is armed(1) or disarmed(2)."
+ ::= { xPDUMiscGroup 1 }
+
+xPDUTransformTempStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ overtemp (2),
+ noTransformerPresent (3),
+ unknown (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates if the PDU's isolation transformer is over temperature."
+ ::= { xPDUMiscGroup 2 }
+
+xPDUCoolingFanStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ failed (2),
+ noCoolingFansPresent (3),
+ unknown (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates if one or more of the PDU's cooling fans have failed."
+ ::= { xPDUMiscGroup 3 }
+
+-- The pmmIdent group
+
+pmmIdentModelNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the model number of the PMM.
+ This value is set at the factory."
+ ::= { pmmIdent 1 }
+
+pmmIdentSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the serial number of the PMM.
+ This value is set at the factory."
+ ::= { pmmIdent 2 }
+
+pmmIdentDateOfManufacture OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The date when the PMM was manufactured in mm/dd/yyyy format.
+ This value is set at the factory."
+ ::= { pmmIdent 3 }
+
+pmmIdentHMISerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the serial number of the HMI.
+ This value is set at the factory."
+ ::= { pmmIdent 4 }
+
+pmmIdentHMIHardwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The hardware revision of the HMI.
+ This value is set at the factory."
+ ::= { pmmIdent 5 }
+
+pmmIdentHMIFirmwareAppRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An ID string identifying the application firmware revision of the
+ HMI."
+ ::= { pmmIdent 6 }
+
+pmmIdentHMIFirmwareAppOSRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An ID string identifying the application operating system firmware revision of the
+ HMI."
+ ::= { pmmIdent 7 }
+
+-- The pmmDevice group
+
+pmmDeviceNominalInputVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The nominal input voltage to the PMM. Measured in Volts,
+ line-to-line for a 3-wire (delta) service or line-to-neutral for a
+ 4-wire (wye) service."
+ ::= { pmmDevice 1 }
+
+pmmDeviceServiceType OBJECT-TYPE
+ SYNTAX INTEGER{
+ threeWire (1),
+ fourWire (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The type of utility input to the PMM. Either 3 wires (delta), or 4 wires (wye)."
+ ::= { pmmDevice 2 }
+
+pmmDeviceNominalOutputVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The nominal line-to-neutral output voltage to the load measured in Volts."
+ ::= { pmmDevice 3 }
+-- The pmmInput group
+pmmInputMeterTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of input meters attached to the system."
+ ::= { pmmInput 1 }
+
+pmmInputTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF PMMInputEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of input meter entries."
+ ::= { pmmInput 2}
+
+pmmInputEntry OBJECT-TYPE
+ SYNTAX PMMInputEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular input meter."
+ INDEX { pmmInputMeterIndex }
+ ::= { pmmInputTable 1 }
+
+ PMMInputEntry ::= SEQUENCE {
+ pmmInputMeterIndex INTEGER,
+ pmmInputFrequency INTEGER,
+ pmmInputTotalActivePower INTEGER,
+ pmmInputTotalApparentPower INTEGER,
+ pmmInputTotalPowerFactor INTEGER,
+ pmmInputActiveEnergyDelivered Integer32,
+ pmmInputActiveEnergyReceived Integer32,
+ pmmInputApparentEnergyDelivered Integer32,
+ pmmInputApparentEnergyReceived Integer32,
+ pmmInputFrequencyDeviation INTEGER,
+ pmmInputPowerFactorDeviation INTEGER,
+ pmmInputMinVoltThreshold INTEGER,
+ pmmInputLowVoltThreshold INTEGER,
+ pmmInputHighVoltThreshold INTEGER,
+ pmmInputMaxVoltThreshold INTEGER,
+ pmmInputMinCurrentThreshold INTEGER,
+ pmmInputLowCurrentThreshold INTEGER,
+ pmmInputHighCurrentThreshold INTEGER,
+ pmmInputMaxCurrentThreshold INTEGER,
+ pmmInputMinApparentPowerThreshold INTEGER,
+ pmmInputMaxApparentPowerThreshold INTEGER,
+ pmmInputOverActivePowerThreshold INTEGER,
+ pmmInputBreakerState INTEGER,
+ pmmInputBreakerOpenAlarm INTEGER,
+ pmmInputAverageCurrent INTEGER,
+ pmmInputNeturalCurrent INTEGER,
+ pmmInputMaxInstantaneousNeutralCurrent INTEGER,
+ pmmInputAverageCurrentTHD INTEGER,
+ pmmInputAverageVoltageLtoL INTEGER,
+ pmmInputAverageVoltageLtoN INTEGER,
+ pmmInputLoad INTEGER,
+ pmmInputMeterFirmwareVersion INTEGER,
+ pmmInputMeterSerialNumber DisplayString,
+ pmmInputEnergyUsageAccumulatedTotal INTEGER,
+ pmmInputPhaseLoss INTEGER,
+ pmmInputBreakerCTSize INTEGER,
+ pmmInputBreakerRating INTEGER,
+ pmmInputKWHResetDate DisplayString,
+ pmmInputAlarmGeneration INTEGER,
+ pmmInputVoltageMaximumAlarm INTEGER,
+ pmmInputVoltageHighAlarm INTEGER,
+ pmmInputVoltageLowAlarm INTEGER,
+ pmmInputVoltageMinimumAlarm INTEGER,
+ pmmInputCurrentMaximumAlarm INTEGER,
+ pmmInputCurrentHighAlarm INTEGER,
+ pmmInputCurrentLowAlarm INTEGER,
+ pmmInputCurrentMinimumAlarm INTEGER,
+ pmmInputApparentPowerMaximumAlarm INTEGER,
+ pmmInputApparentPowerMinimumAlarm INTEGER,
+ pmmInputKWOverAlarm INTEGER,
+ pmmInputPhaseLossAlarm INTEGER,
+ pmmInputPowerFactorTotalAlarm INTEGER,
+ pmmInputFrequencyDeviationAlarm INTEGER
+ }
+
+pmmInputMeterIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input meter identifier."
+ ::= { pmmInputEntry 1 }
+
+pmmInputFrequency OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input frequency in tenths of Hertz."
+ ::= { pmmInputEntry 2 }
+
+pmmInputTotalActivePower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Shows the total input active power in tenths of kW."
+ ::= { pmmInputEntry 3 }
+
+pmmInputTotalApparentPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Shows the total input apparent power in tenths of kVA."
+ ::= { pmmInputEntry 4 }
+
+pmmInputTotalPowerFactor OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the total power factor. A value of 100 representing
+ a unity power factor (1.00). Specified in hundredths."
+ ::= { pmmInputEntry 5 }
+
+pmmInputActiveEnergyDelivered OBJECT-TYPE
+ SYNTAX Integer32
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Shows the input active energy delivered in tenths of kWh."
+ ::= { pmmInputEntry 6 }
+
+pmmInputActiveEnergyReceived OBJECT-TYPE
+ SYNTAX Integer32
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Shows the input active energy received in tenths of kWh."
+ ::= { pmmInputEntry 7 }
+
+pmmInputApparentEnergyDelivered OBJECT-TYPE
+ SYNTAX Integer32
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Shows the input apparent energy delivered in tenths of kVAh."
+ ::= { pmmInputEntry 8 }
+
+pmmInputApparentEnergyReceived OBJECT-TYPE
+ SYNTAX Integer32
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Shows the input apparent energy received in tenths of kVAh."
+ ::= { pmmInputEntry 9 }
+
+pmmInputFrequencyDeviation OBJECT-TYPE
+ SYNTAX INTEGER{
+ freqDeviationOff (1),
+ freqDeviationPointTwo (2),
+ freqDeviationPointFive (3),
+ freqDeviationOne (4),
+ freqDeviationOnePointFive (5),
+ freqDeviationTwo (6),
+ freqDeviationThree (7),
+ freqDeviationFour (8),
+ freqDeviationFive (9),
+ freqDeviationNine (10)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Shows the input frequency deviation in Hertz."
+ ::= { pmmInputEntry 10 }
+
+pmmInputPowerFactorDeviation OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Shows the input power factor deviation. Specified in tenths.
+ A value of zero indicates that the threshold is disabled."
+ ::= { pmmInputEntry 11 }
+
+pmmInputMinVoltThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold below which an input minimum voltage condition
+ will be generated. Specified as percent deviation from
+ nominal voltage represented in the OID pmmDeviceNominalInputVoltage.
+ A value of zero indicates that the threshold is disabled."
+ ::= { pmmInputEntry 12 }
+
+pmmInputLowVoltThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold below which an input low voltage condition
+ will be generated. Specified as percent deviation from
+ nominal voltage represented in the OID pmmDeviceNominalInputVoltage.
+ A value of zero indicates that the threshold is disabled."
+ ::= { pmmInputEntry 13 }
+
+pmmInputHighVoltThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..120)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold above which an input high voltage condition
+ will be generated. Specified as percent deviation from
+ nominal voltage represented in the OID pmmDeviceNominalInputVoltage.
+ A value of zero indicates that the threshold is disabled."
+ ::= { pmmInputEntry 14 }
+
+pmmInputMaxVoltThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..120)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold above which an input maximum voltage condition
+ will be generated. Specified as percent deviation from
+ nominal voltage represented in the OID pmmDeviceNominalInputVoltage.
+ A value of zero indicates that the threshold is disabled."
+ ::= { pmmInputEntry 15 }
+
+pmmInputMinCurrentThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold below which an input minimum current condition will be generated.
+ Specified as a percent of the panel breaker rating.
+ A value of zero indicates that the threshold is disabled."
+ ::= { pmmInputEntry 16 }
+
+pmmInputLowCurrentThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold below which an input low current condition will be generated.
+ Specified as a percent of the panel breaker rating.
+ A value of zero indicates that the threshold is disabled."
+ ::= { pmmInputEntry 17 }
+
+pmmInputHighCurrentThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..110)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold above which an input high current condition will be generated.
+ Specified as a percent of the panel breaker rating.
+ A value of zero indicates that the threshold is disabled."
+ ::= { pmmInputEntry 18 }
+
+pmmInputMaxCurrentThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold above which an input maximum current condition will be generated.
+ Specified as a percent of the panel breaker rating.
+ A value of zero indicates that the threshold is disabled."
+ ::= { pmmInputEntry 19 }
+
+pmmInputMinApparentPowerThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold below which an input minimum apparent power condition will be generated.
+ Specified as a percent deviation from nominal power rating.
+ A value of zero indicates that the threshold is disabled."
+ ::= { pmmInputEntry 20 }
+
+pmmInputMaxApparentPowerThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..110)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold above which an input maximum apparent power condition will be generated.
+ Specified as a percent deviation from nominal power rating.
+ A value of zero indicates that the threshold is disabled."
+ ::= { pmmInputEntry 21 }
+
+pmmInputOverActivePowerThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold above which an input over active power condition will be generated.
+ Specified as a percent deviation from nominal power rating.
+ A value of zero indicates that the threshold is disabled."
+ ::= { pmmInputEntry 22 }
+
+pmmInputBreakerState OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2),
+ unknown(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This value indicates the current state of input breaker.
+ 1 will indicate open,
+ 2 will indicate closed,
+ 3 will indicate unknown."
+ ::= { pmmInputEntry 23 }
+
+pmmInputBreakerOpenAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ enabled (1),
+ disabled (2),
+ unknown (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Breaker open alarm status.
+ 1 will indicate enabled,
+ 2 will indicate disabled,
+ 3 will indicate unknown."
+ ::= { pmmInputEntry 24 }
+
+pmmInputAverageCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Input Average current. Measured in tenths of Amps."
+ ::= { pmmInputEntry 25 }
+
+pmmInputNeturalCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Input Netural current. Measured in tenths of Amps."
+ ::= { pmmInputEntry 26 }
+
+pmmInputMaxInstantaneousNeutralCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Input maximum instantaneous neutral current. Measured in tenths of Amps."
+ ::= { pmmInputEntry 27 }
+
+pmmInputAverageCurrentTHD OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Input average harmonic distortions.
+ Returns -1 if unsupported or failed."
+ ::= { pmmInputEntry 28 }
+
+pmmInputAverageVoltageLtoL OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Input Average Line to Line voltage. Measured in tenths of Volts.
+ Returns -1 if unsupported or failed."
+ ::= { pmmInputEntry 29 }
+
+pmmInputAverageVoltageLtoN OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Input Average Line to Neutral voltage. Measured in tenths of Volts.
+ Returns -1 if unsupported or failed."
+ ::= { pmmInputEntry 30 }
+
+pmmInputLoad OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Total load of input breaker in percentage.
+ Returns -1 if unsupported or failed."
+ ::= { pmmInputEntry 31 }
+
+pmmInputMeterFirmwareVersion OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Shows the input meter firmware revision.
+ Returns -1 if unsupported or failed."
+ ::= { pmmInputEntry 32 }
+
+pmmInputMeterSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Shows the input meter serial number.
+ Returns -1 if unsupported or failed."
+ ::= { pmmInputEntry 33 }
+
+pmmInputEnergyUsageAccumulatedTotal OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Shows the total accumulated input energy usage in kwh.
+ Returns -1 if unsupported or failed."
+ ::= { pmmInputEntry 34 }
+
+pmmInputPhaseLoss OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold below which an input phase loss condition will be generated.
+ Specified as a percent deviation from phase to neutral nominal voltage.
+ A value of zero indicates that the threshold is disabled.
+ Returns -1 if unsupported or failed."
+ ::= { pmmInputEntry 35 }
+
+pmmInputBreakerCTSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Shows the input breaker CT size.
+ Returns -1 if unsupported or failed."
+ ::= { pmmInputEntry 36 }
+
+pmmInputBreakerRating OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Shows the input breaker rating in Amps(A).
+ Returns -1 if unsupported or failed."
+ ::= { pmmInputEntry 37 }
+
+pmmInputKWHResetDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The date that the kWh usage was reset, in the format mm/dd/yyyy."
+ ::= { pmmInputEntry 38 }
+
+pmmInputAlarmGeneration OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Alarm generation status.
+ 1 - enabled
+ 2 - disabled
+ 3 - unknown "
+ ::= { pmmInputEntry 39 }
+
+pmmInputVoltageMaximumAlarm OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Voltage maximum alarm generation status.
+ 1 - enabled
+ 2 - disabled
+ 3 - unknown "
+ ::= { pmmInputEntry 40 }
+
+pmmInputVoltageHighAlarm OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Voltage high alarm generation status.
+ 1 - enabled
+ 2 - disabled
+ 3 - unknown "
+ ::= { pmmInputEntry 41 }
+
+pmmInputVoltageLowAlarm OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Voltage low alarm generation status.
+ 1 - enabled
+ 2 - disabled
+ 3 - unknown "
+ ::= { pmmInputEntry 42 }
+
+pmmInputVoltageMinimumAlarm OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Voltage minimum alarm generation status.
+ 1 - enabled
+ 2 - disabled
+ 3 - unknown "
+ ::= { pmmInputEntry 43 }
+
+pmmInputCurrentMaximumAlarm OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Current maximum alarm generation status.
+ 1 - enabled
+ 2 - disabled
+ 3 - unknown "
+ ::= { pmmInputEntry 44 }
+
+pmmInputCurrentHighAlarm OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Current high alarm generation status.
+ 1 - enabled
+ 2 - disabled
+ 3 - unknown "
+ ::= { pmmInputEntry 45 }
+
+pmmInputCurrentLowAlarm OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Current low alarm generation status.
+ 1 - enabled
+ 2 - disabled
+ 3 - unknown "
+ ::= { pmmInputEntry 46 }
+
+pmmInputCurrentMinimumAlarm OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Current minimum alarm generation status.
+ 1 - enabled
+ 2 - disabled
+ 3 - unknown "
+ ::= { pmmInputEntry 47 }
+
+pmmInputApparentPowerMaximumAlarm OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Apparent Power maximum alarm generation status.
+ 1 - enabled
+ 2 - disabled
+ 3 - unknown "
+ ::= { pmmInputEntry 48 }
+
+pmmInputApparentPowerMinimumAlarm OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Apparent Power minimum alarm generation status.
+ 1 - enabled
+ 2 - disabled
+ 3 - unknown "
+ ::= { pmmInputEntry 49 }
+
+pmmInputKWOverAlarm OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Over active power alarm generation status.
+ 1 - enabled
+ 2 - disabled
+ 3 - unknown "
+ ::= { pmmInputEntry 50 }
+
+pmmInputPhaseLossAlarm OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Phase loss alarm generation status.
+ 1 - enabled
+ 2 - disabled
+ 3 - unknown "
+ ::= { pmmInputEntry 51 }
+
+pmmInputPowerFactorTotalAlarm OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Total power factor alarm generation status.
+ 1 - enabled
+ 2 - disabled
+ 3 - unknown "
+ ::= { pmmInputEntry 52 }
+
+pmmInputFrequencyDeviationAlarm OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Frequency deviation alarm generation status.
+ 1 - enabled
+ 2 - disabled
+ 3 - unknown "
+ ::= { pmmInputEntry 53 }
+
+
+pmmInputPhaseTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF PMMInputPhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of input table entries.
+ The number of entries is given by the value of
+ pmmInputMeterTableSize OID."
+ ::= { pmmInput 3 }
+
+pmmInputPhaseEntry OBJECT-TYPE
+ SYNTAX PMMInputPhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular input phase."
+ INDEX { pmmInputMeterNum, pmmInputPhase }
+ ::= { pmmInputPhaseTable 1 }
+
+ PMMInputPhaseEntry ::= SEQUENCE {
+ pmmInputMeterNum INTEGER,
+ pmmInputPhase INTEGER,
+ pmmInputVoltageLtoL INTEGER,
+ pmmInputVoltageLtoN INTEGER,
+ pmmInputPhaseCurrent INTEGER,
+ pmmInputActivePower INTEGER,
+ pmmInputApparentPower INTEGER,
+ pmmInputPowerFactor INTEGER,
+ pmmInputMaxInstantaneousCurrent INTEGER,
+ pmmInputPhaseAngle INTEGER,
+ pmmInputTHDLtoL INTEGER,
+ pmmInputTHDLtoN INTEGER,
+ pmmInputCurrentTHD INTEGER
+ }
+
+pmmInputMeterNum OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input meter identifier."
+ ::= { pmmInputPhaseEntry 1 }
+
+pmmInputPhase OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Input phase index."
+ ::= { pmmInputPhaseEntry 2 }
+
+pmmInputVoltageLtoL OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Line-to-line input voltage available.
+ Measured in tenths of Volts."
+ ::= { pmmInputPhaseEntry 3 }
+
+pmmInputVoltageLtoN OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Line-to-neutral input voltage available.
+ Measured in tenths of Volts."
+ ::= { pmmInputPhaseEntry 4 }
+
+pmmInputPhaseCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Input current per phase. Measured in tenths of Amps."
+ ::= { pmmInputPhaseEntry 5 }
+
+pmmInputActivePower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Input power per phase. Measured in tenths of kW."
+ ::= { pmmInputPhaseEntry 6 }
+
+pmmInputApparentPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Input power per phase. Measured in tenths of kVA."
+ ::= { pmmInputPhaseEntry 7 }
+
+pmmInputPowerFactor OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the power factor of the input per phase.
+ A value of 100 representing a unity power factor (1.00).
+ Specified in hundredths."
+ ::= { pmmInputPhaseEntry 8 }
+
+pmmInputMaxInstantaneousCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Input maximum phase instantaneous current. Measured in tenths of Amps."
+ ::= { pmmInputPhaseEntry 9 }
+
+pmmInputPhaseAngle OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Current phase Angle. Measured in tenths of decimal"
+ ::= { pmmInputPhaseEntry 10 }
+
+pmmInputTHDLtoL OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Input harmonic distortions line to line."
+ ::= { pmmInputPhaseEntry 11 }
+
+pmmInputTHDLtoN OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Input harmonic distortions line to netural."
+ ::= { pmmInputPhaseEntry 12 }
+
+pmmInputCurrentTHD OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Input harmonic distortions.
+ Returns -1 if unsupported or failed.
+ Specified in tenths."
+ ::= { pmmInputPhaseEntry 13 }
+
+-- The pmmOutput group
+pmmOutputMeterTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of output meters attached to the system."
+ ::= { pmmOutput 1 }
+
+pmmOutputTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF PMMOutputEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of output meter entries."
+ ::= { pmmOutput 2}
+
+pmmOutputEntry OBJECT-TYPE
+ SYNTAX PMMOutputEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular output meter."
+ INDEX { pmmOutputMeterIndex }
+ ::= { pmmOutputTable 1 }
+
+ PMMOutputEntry ::= SEQUENCE {
+ pmmOutputMeterIndex INTEGER,
+ pmmOutputFrequency INTEGER,
+ pmmOutputTotalActivePower INTEGER,
+ pmmOutputTotalApparentPower INTEGER,
+ pmmOutputTotalPowerFactor INTEGER,
+ pmmOutputActiveEnergyDelivered Integer32,
+ pmmOutputActiveEnergyReceived Integer32,
+ pmmOutputApparentEnergyDelivered Integer32,
+ pmmOutputApparentEnergyReceived Integer32,
+ pmmOutputFrequencyDeviation INTEGER,
+ pmmOutputPowerFactorDeviation INTEGER,
+ pmmOutputMinVoltThreshold INTEGER,
+ pmmOutputLowVoltThreshold INTEGER,
+ pmmOutputHighVoltThreshold INTEGER,
+ pmmOutputMaxVoltThreshold INTEGER,
+ pmmOutputMinCurrentThreshold INTEGER,
+ pmmOutputLowCurrentThreshold INTEGER,
+ pmmOutputHighCurrentThreshold INTEGER,
+ pmmOutputMaxCurrentThreshold INTEGER,
+ pmmOutputMinApparentPowerThreshold INTEGER,
+ pmmOutputMaxApparentPowerThreshold INTEGER,
+ pmmOutputOverActivePowerThreshold INTEGER,
+ pmmOutputPhaseLossThreshold INTEGER,
+ pmmOutputBreakerState INTEGER,
+ pmmOutputBreakerOpenAlarm INTEGER
+ }
+
+pmmOutputMeterIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output meter identifier."
+ ::= { pmmOutputEntry 1 }
+
+pmmOutputFrequency OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output frequency in tenths of Hertz."
+ ::= { pmmOutputEntry 2 }
+
+pmmOutputTotalActivePower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Shows the total output active power in tenths of kW."
+ ::= { pmmOutputEntry 3 }
+
+pmmOutputTotalApparentPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Shows the total output apparent power in tenths of kVA."
+ ::= { pmmOutputEntry 4 }
+
+pmmOutputTotalPowerFactor OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the total power factor. A value of 100 representing
+ a unity power factor (1.00). Specified in hundredths."
+ ::= { pmmOutputEntry 5 }
+
+pmmOutputActiveEnergyDelivered OBJECT-TYPE
+ SYNTAX Integer32
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Shows the output active energy delivered in tenths of kWh."
+ ::= { pmmOutputEntry 6 }
+
+pmmOutputActiveEnergyReceived OBJECT-TYPE
+ SYNTAX Integer32
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Shows the output active energy received in tenths of kWh."
+ ::= { pmmOutputEntry 7 }
+
+pmmOutputApparentEnergyDelivered OBJECT-TYPE
+ SYNTAX Integer32
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Shows the output apparent energy delivered in tenths of kVAh."
+ ::= { pmmOutputEntry 8 }
+
+pmmOutputApparentEnergyReceived OBJECT-TYPE
+ SYNTAX Integer32
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Shows the output apparent energy received in tenths of kVAh."
+ ::= { pmmOutputEntry 9 }
+
+pmmOutputFrequencyDeviation OBJECT-TYPE
+ SYNTAX INTEGER{
+ freqDeviationOff (1),
+ freqDeviationPointTwo (2),
+ freqDeviationPointFive (3),
+ freqDeviationOne (4),
+ freqDeviationOnePointFive (5),
+ freqDeviationTwo (6),
+ freqDeviationThree (7),
+ freqDeviationFour (8),
+ freqDeviationFive (9),
+ freqDeviationNine (10)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Shows the output frequency deviation in Hertz."
+ ::= { pmmOutputEntry 10 }
+
+pmmOutputPowerFactorDeviation OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Shows the output power factor deviation. Specified in tenths.
+ A value of zero indicates that the threshold is disabled."
+ ::= { pmmOutputEntry 11 }
+
+pmmOutputMinVoltThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold below which an output minimum voltage condition
+ will be generated. Specified as percent deviation from
+ nominal voltage represented in the OID pmmDeviceNominalOutputVoltage.
+ A value of zero indicates that the threshold is disabled."
+ ::= { pmmOutputEntry 12 }
+
+pmmOutputLowVoltThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold below which an output low voltage condition
+ will be generated. Specified as percent deviation from
+ nominal voltage represented in the OID pmmDeviceNominalOutputVoltage.
+ A value of zero indicates that the threshold is disabled."
+ ::= { pmmOutputEntry 13 }
+
+pmmOutputHighVoltThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..120)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold above which an output high voltage condition
+ will be generated. Specified as percent deviation from
+ nominal voltage represented in the OID pmmDeviceNominalOutputVoltage.
+ A value of zero indicates that the threshold is disabled."
+ ::= { pmmOutputEntry 14 }
+
+pmmOutputMaxVoltThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..120)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold above which an output maximum voltage condition
+ will be generated. Specified as percent deviation from
+ nominal voltage represented in the OID pmmDeviceNominalOutputVoltage.
+ A value of zero indicates that the threshold is disabled."
+ ::= { pmmOutputEntry 15 }
+
+pmmOutputMinCurrentThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold below which an output minimum current condition will be generated.
+ Specified as a percent of the panel breaker rating.
+ A value of zero indicates that the threshold is disabled."
+ ::= { pmmOutputEntry 16 }
+
+pmmOutputLowCurrentThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold below which an output low current condition will be generated.
+ Specified as a percent of the panel breaker rating.
+ A value of zero indicates that the threshold is disabled."
+ ::= { pmmOutputEntry 17 }
+
+pmmOutputHighCurrentThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..110)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold above which an output high current condition will be generated.
+ Specified as a percent of the panel breaker rating.
+ A value of zero indicates that the threshold is disabled."
+ ::= { pmmOutputEntry 18 }
+
+pmmOutputMaxCurrentThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold above which an output maximum current condition will be generated.
+ Specified as a percent of the panel breaker rating.
+ A value of zero indicates that the threshold is disabled."
+ ::= { pmmOutputEntry 19 }
+
+pmmOutputMinApparentPowerThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold below which an output minimum apparent power condition will be generated.
+ Specified as a percent deviation from nominal power rating.
+ A value of zero indicates that the threshold is disabled."
+ ::= { pmmOutputEntry 20 }
+
+pmmOutputMaxApparentPowerThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..110)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold above which an output maximum apparent power condition will be generated.
+ Specified as a percent deviation from nominal power rating.
+ A value of zero indicates that the threshold is disabled."
+ ::= { pmmOutputEntry 21 }
+
+pmmOutputOverActivePowerThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold above which an output over active power condition will be generated.
+ Specified as a percent deviation from nominal power rating.
+ A value of zero indicates that the threshold is disabled."
+ ::= { pmmOutputEntry 22 }
+
+pmmOutputPhaseLossThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold below which an output phase loss condition will be generated.
+ Specified as a percent deviation from nominal voltage represented
+ in the OID pmmDeviceNominalOutputVoltage.
+ A value of zero indicates that the threshold is disabled."
+ ::= { pmmOutputEntry 23 }
+
+pmmOutputBreakerState OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2),
+ unknown(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This value indicates the current state of output breaker.
+ 1 will indicate open,
+ 2 will indicate closed,
+ 3 will indicate unknown."
+ ::= { pmmOutputEntry 24 }
+
+pmmOutputBreakerOpenAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ enabled (1),
+ disabled (2),
+ unknown (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Breaker open alarm status.
+ 1 will indicate enabled,
+ 2 will indicate disabled,
+ 3 will indicate unknown."
+ ::= { pmmOutputEntry 25 }
+
+pmmOutputPhaseTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF PMMOutputPhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of output table entries.
+ The number of entries is given by the value of
+ pmmOutputMeterTableSize OID."
+ ::= { pmmOutput 3 }
+
+pmmOutputPhaseEntry OBJECT-TYPE
+ SYNTAX PMMOutputPhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular output phase."
+ INDEX { pmmOutputMeterNum, pmmOutputPhase }
+ ::= { pmmOutputPhaseTable 1 }
+
+ PMMOutputPhaseEntry ::= SEQUENCE {
+ pmmOutputMeterNum INTEGER,
+ pmmOutputPhase INTEGER,
+ pmmOutputVoltageLtoL INTEGER,
+ pmmOutputVoltageLtoN INTEGER,
+ pmmOutputPhaseCurrent INTEGER,
+ pmmOutputActivePower INTEGER,
+ pmmOutputApparentPower INTEGER,
+ pmmOutputPowerFactor INTEGER
+ }
+
+pmmOutputMeterNum OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output meter identifier."
+ ::= { pmmOutputPhaseEntry 1 }
+
+pmmOutputPhase OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Output phase index."
+ ::= { pmmOutputPhaseEntry 2 }
+
+pmmOutputVoltageLtoL OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Line-to-line output voltage available.
+ Measured in tenths of Volts."
+ ::= { pmmOutputPhaseEntry 3 }
+
+pmmOutputVoltageLtoN OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Line-to-neutral output voltage available.
+ Measured in tenths of Volts."
+ ::= { pmmOutputPhaseEntry 4 }
+
+pmmOutputPhaseCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Load current per phase. Measured in tenths of Amps."
+ ::= { pmmOutputPhaseEntry 5 }
+
+pmmOutputActivePower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Output power per phase. Measured in tenths of kW."
+ ::= { pmmOutputPhaseEntry 6 }
+
+pmmOutputApparentPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Output power per phase. Measured in tenths of kVA."
+ ::= { pmmOutputPhaseEntry 7 }
+
+pmmOutputPowerFactor OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the power factor of the output per phase.
+ A value of 100 representing a unity power factor (1.00).
+ Specified in hundredths."
+ ::= { pmmOutputPhaseEntry 8 }
+
+-- The pmmBranch group
+
+pmmnumofBranchMeters OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of branch meters attached to the system."
+ ::= { pmmBranch 1 }
+
+pmmBranchBreakerTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of branch breaker entries."
+ ::= { pmmBranch 2 }
+
+pmmBranchBreakerTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF PMMBranchBreakerEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of branch breaker table entries.
+ The number of entries is contained in the pmmBranchBreakerTableSize OID."
+ ::= { pmmBranch 3 }
+
+pmmBranchBreakerEntry OBJECT-TYPE
+ SYNTAX PMMBranchBreakerEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular branch breaker (panel/circuit position)."
+ INDEX {pmmBranchCircuitMeterIndex, pmmBranchCircuitIndex }
+ ::= { pmmBranchBreakerTable 1 }
+
+ PMMBranchBreakerEntry ::= SEQUENCE {
+ pmmBranchCircuitMeterIndex INTEGER,
+ pmmBranchCircuitIndex INTEGER,
+ pmmBranchCircuitNumberOfPoles INTEGER,
+ pmmBranchCircuitPhase DisplayString,
+ pmmBranchCircuitBreakerIdentifier DisplayString,
+ pmmBranchCircuitLoadIdentifier DisplayString,
+ pmmBranchCircuitCurrent INTEGER,
+ pmmBranchCircuitBreakerRating INTEGER,
+ pmmBranchCircuitTotalActivePower INTEGER,
+ pmmBranchCircuitTotalApparentPower INTEGER,
+ pmmBranchCircuitEnergyUsage Gauge,
+ pmmBranchCircuitEnergyUsageResetDate DisplayString,
+ pmmBranchCircuitTotalPowerFactor INTEGER,
+ pmmBranchCircuitBreakerState INTEGER,
+ pmmBranchCircuitMinCurrentThreshold INTEGER,
+ pmmBranchCircuitLowCurrentThreshold INTEGER,
+ pmmBranchCircuitHighCurrentThreshold INTEGER,
+ pmmBranchCircuitMaxCurrentThreshold INTEGER,
+ pmmBranchCircuitMinApparentPowerThreshold INTEGER,
+ pmmBranchCircuitMaxApparentPowerThreshold INTEGER,
+ pmmBranchCircuitAlaramGeneration INTEGER,
+ pmmBranchCircuitBreakerOpenAlarm INTEGER,
+ pmmBranchCircuitBreakerAverageCurrent INTEGER,
+ pmmBranchCircuitMaxInstantaneousCurrentPhase INTEGER,
+ pmmBranchCircuitBreakerMaxInstantaneousAverageCurrent INTEGER,
+ pmmBranchCircuitAngle INTEGER,
+ pmmBranchCircuitActivePower INTEGER,
+ pmmBranchCircuitApparentPower INTEGER,
+ pmmBranchCircuitBreakerEnergyTotalUsage Gauge,
+ pmmBranchCircuitPowerFactor INTEGER,
+ pmmBranchCircuitTHD INTEGER,
+ pmmBranchCircuitBreakerTHD INTEGER,
+ pmmBranchCircuitBreakerLoad INTEGER,
+ pmmBranchCircuitBranchNumber INTEGER,
+ pmmBranchCircuitChannelCTSize INTEGER,
+ pmmBranchcircuitCurrentMaxAlarm INTEGER,
+ pmmBranchcircuitCurrentHighAlarm INTEGER,
+ pmmBranchcircuitCurrentLowAlarm INTEGER,
+ pmmBranchcircuitCurrentMinAlarm INTEGER,
+ pmmBranchcircuitApparentPowerMaxAlarm INTEGER,
+ pmmBranchcircuitApparentPowerMinAlarm INTEGER
+ }
+
+pmmBranchCircuitMeterIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index of branch circuit meter in the table."
+ ::= { pmmBranchBreakerEntry 1 }
+
+pmmBranchCircuitIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The branch circuit index."
+ ::= { pmmBranchBreakerEntry 2 }
+
+pmmBranchCircuitNumberOfPoles OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of poles."
+ ::= { pmmBranchBreakerEntry 3 }
+
+pmmBranchCircuitPhase OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The phase associated with branch circuit."
+ ::= { pmmBranchBreakerEntry 4 }
+
+pmmBranchCircuitBreakerIdentifier OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The branch circuit identifier."
+ ::= { pmmBranchBreakerEntry 5 }
+
+pmmBranchCircuitLoadIdentifier OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Identifies the name or location of the branch circuit load."
+ ::= { pmmBranchBreakerEntry 6 }
+
+pmmBranchCircuitCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The branch circuit current Measured in tenths of Amps."
+ ::= { pmmBranchBreakerEntry 7 }
+
+pmmBranchCircuitBreakerRating OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The rating of the branch circuit breaker in Amps."
+ ::= { pmmBranchBreakerEntry 8 }
+
+pmmBranchCircuitTotalActivePower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Branch circuit total power. Measured in tenths
+ of kW."
+ ::= { pmmBranchBreakerEntry 9 }
+
+pmmBranchCircuitTotalApparentPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Branch circuit total apparent power. Measured in
+ tenths of kVA."
+ ::= { pmmBranchBreakerEntry 10 }
+
+pmmBranchCircuitEnergyUsage OBJECT-TYPE
+ SYNTAX Gauge
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the accumulated energy usage in tenths of kWh.
+ Displayed as 0 when not available or no energy used."
+ ::= { pmmBranchBreakerEntry 11 }
+
+pmmBranchCircuitEnergyUsageResetDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The date that the kWh usage was reset, in the format mm/dd/yyyy."
+ ::= { pmmBranchBreakerEntry 12 }
+
+pmmBranchCircuitTotalPowerFactor OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the total power factor of the branch circuit output.
+ A value of 100 representing a unity power factor (1.00)
+ Specified in hundredths."
+ ::= { pmmBranchBreakerEntry 13 }
+
+pmmBranchCircuitBreakerState OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2),
+ unknown (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This value indicates the current state of branch
+ circuit breaker.
+ 1 will indicate open,
+ 2 will indicate closed,
+ 3 will indicate unknown."
+ ::= { pmmBranchBreakerEntry 14 }
+
+pmmBranchCircuitMinCurrentThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold below which a branch circuit minimum current
+ condition will be generated.
+ Specified as a percent of the branch breaker rating
+ represented in the OID pmmBranchCircuitBreakerRating
+ A value of zero indicates that the threshold is disabled."
+ ::= { pmmBranchBreakerEntry 15 }
+
+pmmBranchCircuitLowCurrentThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold below which a branch circuit low current
+ condition will be generated.
+ Specified as a percent of the branch breaker rating
+ represented in the OID pmmBranchCircuitBreakerRating
+ A value of zero indicates that the threshold is disabled."
+ ::= { pmmBranchBreakerEntry 16 }
+
+pmmBranchCircuitHighCurrentThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold above which a branch circuit high current
+ condition will be generated.
+ Specified as a percent of the branch breaker rating
+ represented in the OID pmmBranchCircuitBreakerRating
+ A value of zero indicates that the threshold is disabled."
+ ::= { pmmBranchBreakerEntry 17 }
+
+pmmBranchCircuitMaxCurrentThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold above which a branch circuit maximum current
+ condition will be generated.
+ Specified as a percent of the branch breaker rating
+ represented in the OID pmmBranchCircuitBreakerRating
+ A value of zero indicates that the threshold is disabled."
+ ::= { pmmBranchBreakerEntry 18 }
+
+pmmBranchCircuitMinApparentPowerThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold below which a branch circuit minimum apparent
+ power condition will be generated.
+ Specified as a percent of the branch breaker apparent power rating.
+ A value of zero indicates that the threshold is disabled."
+ ::= { pmmBranchBreakerEntry 19 }
+
+pmmBranchCircuitMaxApparentPowerThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold above which a branch circuit maximum apparent
+ power condition will be generated.
+ Specified as a percent of the branch breaker apparent power rating.
+ A value of zero indicates that the threshold is disabled."
+ ::= { pmmBranchBreakerEntry 20 }
+
+pmmBranchCircuitAlaramGeneration OBJECT-TYPE
+ SYNTAX INTEGER {
+ enabled (1),
+ disabled (2),
+ unknown (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Alarm generation status.
+ 1 will indicate enabled,
+ 2 will indicate disabled,
+ 3 will indicate unknown."
+ ::= { pmmBranchBreakerEntry 21 }
+
+pmmBranchCircuitBreakerOpenAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ enabled (1),
+ disabled (2),
+ unknown (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Breaker open alarm status.
+ 1 will indicate enabled,
+ 2 will indicate disabled,
+ 3 will indicate unknown."
+ ::= { pmmBranchBreakerEntry 22 }
+
+pmmBranchCircuitBreakerAverageCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Branch breaker current. Measured in tenths of Amps."
+ ::= { pmmBranchBreakerEntry 23 }
+
+pmmBranchCircuitMaxInstantaneousCurrentPhase OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Branch circuit maximum instantaneous current. Measured in tenths of Amps."
+ ::= { pmmBranchBreakerEntry 24 }
+
+pmmBranchCircuitBreakerMaxInstantaneousAverageCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Branch breaker maximum instantaneous current. Measured in tenths of Amps."
+ ::= { pmmBranchBreakerEntry 25 }
+
+pmmBranchCircuitAngle OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Branch circuit phase angle. Measured in tenths of Decimal."
+ ::= { pmmBranchBreakerEntry 26 }
+
+pmmBranchCircuitActivePower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Branch circuit Active power. Measured in tenths of kW."
+ ::= { pmmBranchBreakerEntry 27 }
+
+pmmBranchCircuitApparentPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Branch circuit apparent power. Measured in tenths of kVA."
+ ::= { pmmBranchBreakerEntry 28 }
+
+pmmBranchCircuitBreakerEnergyTotalUsage OBJECT-TYPE
+ SYNTAX Gauge
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the circuit Breaker total accumulated energy usage in tenths of kWh.
+ Displayed as 0 when not available or no energy used."
+ ::= { pmmBranchBreakerEntry 29 }
+
+pmmBranchCircuitPowerFactor OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the power factor of the branch circuit.
+ A value of 100 representing a unity power factor (1.00)
+ Specified in hundredths."
+ ::= { pmmBranchBreakerEntry 30 }
+
+pmmBranchCircuitTHD OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Branch circuit harmonic distortion."
+ ::= { pmmBranchBreakerEntry 31 }
+
+pmmBranchCircuitBreakerTHD OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Branch Breaker harmonic distortion."
+ ::= { pmmBranchBreakerEntry 32 }
+
+pmmBranchCircuitBreakerLoad OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Total load on the Breaker.
+ Measured in tenths of Amps."
+ ::= { pmmBranchBreakerEntry 33 }
+
+pmmBranchCircuitBranchNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The branch number.
+ Returns -1 if unsupported or failed."
+ ::= { pmmBranchBreakerEntry 34 }
+
+pmmBranchCircuitChannelCTSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The branch CT Size.
+ Returns -1 if unsupported or failed."
+ ::= { pmmBranchBreakerEntry 35 }
+
+pmmBranchcircuitCurrentMaxAlarm OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Current maximum alarm generation status.
+ 1 - enabled
+ 2 - disabled
+ 3 - unknown "
+ ::= { pmmBranchBreakerEntry 36 }
+
+pmmBranchcircuitCurrentHighAlarm OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Current high alarm generation status.
+ 1 - enabled
+ 2 - disabled
+ 3 - unknown "
+ ::= { pmmBranchBreakerEntry 37 }
+
+pmmBranchcircuitCurrentLowAlarm OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Current low alarm generation status.
+ 1 - enabled
+ 2 - disabled
+ 3 - unknown "
+ ::= { pmmBranchBreakerEntry 38 }
+
+pmmBranchcircuitCurrentMinAlarm OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Current minimum alarm generation status.
+ 1 - enabled
+ 2 - disabled
+ 3 - unknown "
+ ::= { pmmBranchBreakerEntry 39 }
+
+pmmBranchcircuitApparentPowerMaxAlarm OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Apparent power maximum alarm generation status.
+ 1 - enabled
+ 2 - disabled
+ 3 - unknown "
+ ::= { pmmBranchBreakerEntry 40 }
+
+pmmBranchcircuitApparentPowerMinAlarm OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Apparent power minimum alarm generation status.
+ 1 - enabled
+ 2 - disabled
+ 3 - unknown "
+ ::= { pmmBranchBreakerEntry 41 }
+
+-- pmmsite Configuration begins
+pmmSiteConfigTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of site configuration set supported by system."
+ ::= { pmmSiteConfig 1 }
+
+pmmSiteConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF PmmSiteConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of PMM site configurable entries."
+ ::= { pmmSiteConfig 2}
+
+pmmSiteConfigEntry OBJECT-TYPE
+ SYNTAX PmmSiteConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular site configuration."
+ INDEX { pmmSiteConfigIndex}
+ ::= { pmmSiteConfigTable 1 }
+
+PmmSiteConfigEntry ::=
+ SEQUENCE {
+ pmmSiteConfigIndex INTEGER,
+ pmmSiteConfigNominalPtoPVoltage INTEGER,
+ pmmSiteConfigNominalPtoNVoltage INTEGER,
+ pmmSiteConfigNominalCurrent INTEGER,
+ pmmSiteConfigNominalFrequency INTEGER,
+ pmmSiteConfigNominalApparentPower INTEGER,
+ pmmSiteConfigServiceType INTEGER
+ }
+
+pmmSiteConfigIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "PMM site configuration identifier."
+ ::= { pmmSiteConfigEntry 1 }
+
+pmmSiteConfigNominalPtoPVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The nominal input phase to phase voltage to the PMM. Measured in Volts,
+ line-to-line for a 3-wire (delta) service or line-to-neutral for a
+ 4-wire (wye) service."
+ ::= { pmmSiteConfigEntry 2 }
+
+pmmSiteConfigNominalPtoNVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The nominal input phase to neutral voltage to the PMM. Measured in Volts,
+ line-to-line for a 3-wire (delta) service or line-to-neutral for a
+ 4-wire (wye) service."
+ ::= { pmmSiteConfigEntry 3 }
+
+pmmSiteConfigNominalCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The nominal input current to the PMM. Measured in tenths of Amps."
+ ::= { pmmSiteConfigEntry 4 }
+
+pmmSiteConfigNominalFrequency OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The nominal input frequency to the PMM. Measured in tenths of Hertz."
+ ::= { pmmSiteConfigEntry 5 }
+
+pmmSiteConfigNominalApparentPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The nominal input apparent power to the PMM. Measured in tenths of kVA."
+ ::= { pmmSiteConfigEntry 6 }
+
+pmmSiteConfigServiceType OBJECT-TYPE
+ SYNTAX INTEGER{
+ threeWire (1),
+ fourWire (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The type of utility input to the PMM. Either 3 wires (delta), or 4 wires (wye)."
+ ::= { pmmSiteConfigEntry 7 }
+
+
+pmmSiteConfigNumberofPanel OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of panels present.
+ Returns -1 if unsupported or failed."
+ ::= { pmmSiteConfig 3 }
+
+pmmSiteConfigNumberofChannel OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of channels present.
+ Returns -1 if unsupported or failed."
+ ::= { pmmSiteConfig 4 }
+
+pmmSiteConfigNumberofsources OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of input sources present.
+ Returns -1 if unsupported or failed."
+ ::= { pmmSiteConfig 5 }
+
+pmmSiteConfigProductModelNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ " A character string identifying the model number of the RPP.
+ This value is set at the factory.
+ Returns -1 if unsupported or failed."
+ ::= { pmmSiteConfig 6 }
+
+pmmSiteConfigProductSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the serial number of the RPP.
+ This value is set at the factory.
+ Returns -1 if unsupported or failed."
+ ::= { pmmSiteConfig 7 }
+-- pmm site config end
+-- pmm end
+
+-- charger group
+
+chargerIdentModel OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the model name of the Charger.
+ This value is set at the factory."
+ ::= { chargerIdent 1 }
+
+chargerBasicIdentName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "An 8 byte ID string identifying the Charger. This object
+ can be set by the administrator."
+ ::= { chargerIdent 2 }
+
+chargerIdentSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the serial number of the Charger.
+ This value is set at the factory."
+ ::= { chargerIdent 3 }
+
+chargerIdentModelType OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The detailed model information of the Charger."
+ ::= { chargerIdent 4 }
+
+-- Input Phase Table
+
+chargerInputPhaseTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF ChargerInputPhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of input table entries. The number of entries
+ is given by the sum of the Charger input phases."
+ ::= { chargerInput 1 }
+
+chargerInputPhaseEntry OBJECT-TYPE
+ SYNTAX ChargerInputPhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular input phase."
+ INDEX { chargerInputPhaseTableIndex}
+ ::= { chargerInputPhaseTable 1 }
+
+ChargerInputPhaseEntry ::= SEQUENCE {
+ chargerInputPhaseTableIndex INTEGER,
+ chargerInputPhaseVoltage INTEGER,
+ chargerInputPhaseMinVoltage INTEGER,
+ chargerInputPhaseMaxVoltage INTEGER,
+ chargerInputPhaseCurrent INTEGER
+}
+
+chargerInputPhaseTableIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input identifier."
+ ::= { chargerInputPhaseEntry 1 }
+
+chargerInputPhaseVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input voltage in VAC, or -1 if it's unsupported
+ by this Charger."
+ ::= { chargerInputPhaseEntry 2 }
+
+chargerInputPhaseMinVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The lowest input voltage to the Charger during the previous minute of operation, or -1 if it's unsupported
+ by this Charger."
+ ::= { chargerInputPhaseEntry 3 }
+
+chargerInputPhaseMaxVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The highest input voltage to the Charger during the previous minute of operation, or -1 if it's unsupported
+ by this Charger."
+ ::= { chargerInputPhaseEntry 4 }
+
+chargerInputPhaseCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input current in 0.1 amperes, or -1 if it's
+ unsupported by this Charger."
+ ::= { chargerInputPhaseEntry 5 }
+
+ -- end of Input table
+
+ -- the charger output group
+chargerOutputStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(1),
+ initialising(2),
+ standby(3),
+ onBattery(4),
+ floatCharging(5),
+ boostCharging(6),
+ initialCharging(7)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current state of the Charger. If the Charger is unable to
+ determine the state of the Charger this variable is set
+ to unknown(1)."
+ ::= { chargerOutput 1 }
+
+chargerOutputVauxVoltage OBJECT-TYPE
+ SYNTAX Gauge
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Load output voltage, measured in VDC."
+ ::= { chargerOutput 2 }
+
+chargerOutputTotalCurrent OBJECT-TYPE
+ SYNTAX Gauge
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current in amperes drawn by the load on the Charger."
+ ::= { chargerOutput 3 }
+
+chargerOutputLoad OBJECT-TYPE
+ SYNTAX Gauge
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current Charger load expressed in percent
+ of the total rated current of the charger."
+ ::= { chargerOutput 4 }
+-- charger end
+-- The xATSIdent group
+
+xATSIdentProductName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the transfer switch unit."
+ ::= { xATSIdent 1 }
+
+xATSIdentHardwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The hardware revision of the transfer switch.
+ This value is set at the factory."
+ ::= { xATSIdent 2 }
+
+xATSIdentFirmwareAppRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An ID string identifying the application firmware revision of the transfer switch."
+ ::= { xATSIdent 3 }
+
+xATSIdentFirmwareAppOSRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An ID string identifying the application operating system firmware revision of the transfer switch."
+ ::= { xATSIdent 4 }
+
+xATSIdentFirmwareControllerRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An ID string identifying the transfer switch controller firmware revision."
+ ::= { xATSIdent 5 }
+
+xATSIdentDateOfManufacture OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The date when the transfer switch was manufactured in mm/dd/yyyy format.
+ This value is set at the factory."
+ ::= { xATSIdent 6 }
+
+xATSIdentModelNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the model number of the transfer switch.
+ This value is set at the factory."
+ ::= { xATSIdent 7 }
+
+xATSIdentSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the serial number of the transfer switch.
+ This value is set at the factory."
+ ::= { xATSIdent 8 }
+
+-- The xATSDevice group
+
+xATSDeviceServiceType OBJECT-TYPE
+ SYNTAX INTEGER {
+ threeWire (1),
+ fourWire (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The type of utility input to the transfer switch.
+ Either 3 wires (delta), or 4 wires (wye)."
+ ::= { xATSDevice 1 }
+
+xATSDeviceNominalVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The nominal line-to-neutral system voltage.
+ Measured in Volts, line-to-line for a 3-wire service or
+ line-to-neutral for a 4-wire service. -1 if not available."
+ ::= { xATSDevice 2 }
+
+xATSDeviceNominalFrequency OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The nominal system frequency. Measured in tenths of Hertz.
+ -1 if not available."
+ ::= { xATSDevice 3 }
+
+xATSDeviceTransferSwitchRating OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The rating of the transfer switch.
+ Measured in Amps."
+ ::= { xATSDevice 4 }
+
+xATSDeviceDCBackUpPresent OBJECT-TYPE
+ SYNTAX INTEGER{
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates if a DC backup is present or not."
+ ::= { xATSDevice 5 }
+
+-- The xATS Switch Status group
+
+xATSSwitchStatusSelectedSource OBJECT-TYPE
+ SYNTAX INTEGER{
+ none (1),
+ source1 (2),
+ source2 (3),
+ fault (4),
+ unknown (5)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The source which is currently selected, i.e. supplying power to the load."
+ ::= { xATSSwitchStatus 1 }
+
+xATSSwitchStatusOperationalMode OBJECT-TYPE
+ SYNTAX INTEGER{
+ automatic (1),
+ notInAutoAbnormal (2),
+ notInAuto (3),
+ unknown (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current operating mode of the transfer switch. When the ATS is in
+ automatic mode, generator starting and ATS transferring is all done automatically
+ as needed based on the state of source 1. Automatic operation is halted when the
+ ATS is in either of the notInAuto modes.
+ A mode of notInAuto indicates that the automatic operation switch is in the
+ disabled position, as indicated by the xATSSwitchStatusAutomaticOperationSwitch OID.
+ The notInAutoAbnormal condition indicates that an abnormal
+ condition has caused the transfer switch to halt automatic operation.
+ In this case, traps can indicate the exact problem. In the case of
+ notInAutoAbnormal, refer to the operation manual for details
+ on how debug the condition and restore automatic operation."
+ ::= { xATSSwitchStatus 2 }
+
+xATSSwitchStatusAutomaticOperationSwitch OBJECT-TYPE
+ SYNTAX INTEGER{
+ disabled (1),
+ enabled (2),
+ unknown (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The position of the automatic operation switch on the front of the transfer switch."
+ ::= { xATSSwitchStatus 3 }
+
+xATSSwitchStatusEngineStartSignal OBJECT-TYPE
+ SYNTAX INTEGER{
+ run (1),
+ stop (2),
+ unknown (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The position of the Start/Stop contact which signals the generator
+ engine to start/run. When the ATS is in automatic mode,
+ generator starting/stopping is under ATS control."
+ ::= { xATSSwitchStatus 4 }
+
+-- The xATS Switch Setting group
+
+xATSSwitchSettingsLowVoltageTransferPoint OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The lowest acceptable voltage condition at source 1.
+ When any phase of source 1 is lower than this voltage,
+ source quality is considered bad and the generator run signal
+ is asserted to begin generator operation.
+ Specified in volts, line-to-line for a 3-wire service or
+ line-to-neutral for a 4-wire service.
+ -1 if not available."
+ ::= { xATSSwitchSettings 1 }
+
+xATSSwitchSettingsHighVoltageTransferPoint OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The highest acceptable voltage condition at source 1.
+ When any phase of source 1 is greater than this voltage,
+ source quality is considered bad and the generator run signal
+ is asserted to begin generator operation.
+ Specified in volts, line-to-line for a 3-wire service or
+ line-to-neutral for a 4-wire service.
+ -1 if not available."
+ ::= { xATSSwitchSettings 2 }
+
+xATSSwitchSettingsMaxFrequencyDeviation OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum acceptable frequency deviation condition from nominal at source 1.
+ When source 1 frequency is outside the specified range,
+ source quality is considered bad and the generator run signal
+ is asserted to begin generator operation.
+ Specified in tenths of Hertz above or below nominal.
+ A value of zero indicates that frequency is ignored when
+ determining source quality.
+ -1 if not available."
+ ::= { xATSSwitchSettings 3 }
+
+xATSSwitchSettingsMinPhaseBalance OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum required phase balance at source 1.
+ When the percentage difference between the minimum and maximum
+ phase voltage measurements at source 1 is greater than this value,
+ source quality is considered bad and the generator run signal
+ is asserted to begin generator operation.
+ Specified as a percentage. A value of zero indicates that phase balance
+ is ignored when determining source quality. -1 if not available."
+ ::= { xATSSwitchSettings 4 }
+
+xATSSwitchSettingsNominalRotation OBJECT-TYPE
+ SYNTAX INTEGER{
+ abc (1),
+ cba (2),
+ any (3),
+ unknown (4)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The nominal phase rotation (or phase sequence) required by the load.
+ For certain types of equipment, such as rotating machinery, phase rotation
+ is critical for proper operation as it determines the direction which motors
+ will rotate (clockwise or counterclockwise).
+ Source quality will be seen as bad if the rotation measured at that
+ ATS input does not match this setting.
+ If this setting is set to any, phase rotation is ignored."
+ ::= { xATSSwitchSettings 5 }
+
+xATSSwitchSettingsAllowClosedTransfer OBJECT-TYPE
+ SYNTAX INTEGER{
+ yes (1),
+ no (2),
+ unknown (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "This setting enables seamless (closed) transfers between sources.
+ When possible, both source 1 and source 2 are closed to the output
+ for a brief time. If closed transfer is not possible within the amount
+ of time specified by the xATSSwitchSettingsMaxSyncTime OID,
+ an open transfer will be executed."
+ ::= { xATSSwitchSettings 6 }
+
+xATSSwitchSettingsMaxSyncTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "When attempting/seeking to perform a closed transfer, this setting defines
+ the maximum time allowed before the transfer switch will give up and perform
+ an open transfer. Specified in seconds.
+ -1 if not available."
+ ::= { xATSSwitchSettings 7 }
+
+xATSSwitchSettingsNeutralTransferTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "This setting defines how long both source 1 and source 2 will be
+ disconnected from the output, during an open transfer.
+ Specified in seconds.
+ -1 if not available."
+ ::= { xATSSwitchSettings 8 }
+
+xATSSwitchSettingsClearLatchedAlarms OBJECT-TYPE
+ SYNTAX INTEGER{
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Clears any latched alarm conditions."
+ ::= { xATSSwitchSettings 9 }
+
+xATSSwitchSettingsSetToFactoryDefaults OBJECT-TYPE
+ SYNTAX INTEGER{
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Sets all transfer switch settings to factory default values."
+ ::= { xATSSwitchSettings 10 }
+
+
+-- The xATSSwitchTimers group
+
+ xATSSwitchTimersTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of transfer switch timer entries."
+ ::= { xATSSwitchTimers 1 }
+
+ xATSSwitchTimersTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF XATSSwitchTimersEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of timers supported by ATS.
+ The number of entries is contained in the xATSSwitchTimersTableSize OID."
+ ::= { xATSSwitchTimers 2 }
+
+ xATSSwitchTimersEntry OBJECT-TYPE
+ SYNTAX XATSSwitchTimersEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information about an individual ATS timer."
+ INDEX { xATSSwitchTimersIndex }
+ ::= { xATSSwitchTimersTable 1 }
+
+ XATSSwitchTimersEntry ::=
+ SEQUENCE {
+ xATSSwitchTimersIndex INTEGER,
+ xATSSwitchTimersName DisplayString,
+ xATSSwitchTimersAbort INTEGER,
+ xATSSwitchTimersStatus INTEGER,
+ xATSSwitchTimersRemainingTime INTEGER,
+ xATSSwitchTimersDelaySetting INTEGER
+ }
+
+xATSSwitchTimersIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index of timer entries in the table."
+ ::= { xATSSwitchTimersEntry 1 }
+
+xATSSwitchTimersName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Name of the individual timer.Refer to ATS operation manual,
+ or on-line help, for detailed descriptions of ATS timers."
+ ::= { xATSSwitchTimersEntry 2 }
+
+xATSSwitchTimersAbort OBJECT-TYPE
+ SYNTAX INTEGER{
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "This aborts the individual timer."
+ ::= { xATSSwitchTimersEntry 3 }
+
+xATSSwitchTimersStatus OBJECT-TYPE
+ SYNTAX INTEGER{
+ inactive (1),
+ active (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the individual timer. Designates whether this timer
+ entry is currently running or inactive."
+ ::= { xATSSwitchTimersEntry 4 }
+
+xATSSwitchTimersRemainingTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The time remaining for this timer entry.
+ Specified in seconds."
+ ::= { xATSSwitchTimersEntry 5 }
+
+xATSSwitchTimersDelaySetting OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The delay settings associated with this timer entry.
+ When this timer entry is active, the timer value must exceed this setting
+ before the ATS behavior associated with this timer is executed.
+ Refer to ATS operation manual, or on-line help, for detailed
+ descriptions of ATS timers."
+ ::= { xATSSwitchTimersEntry 6 }
+
+-- The xATSSwitchBlockMap group
+
+ xATSSwitchBlockMapTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of blocking map entries, or how many ATS actions can be blocked."
+ ::= { xATSSwitchBlockMap 1 }
+
+ xATSSwitchBlockMapTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF XATSSwitchBlockMapEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of blocking maps supported by the ATS.
+ The number of entries is contained in the xATSSwitchBlockMapTableSize OID."
+ ::= { xATSSwitchBlockMap 2 }
+
+ xATSSwitchBlockMapEntry OBJECT-TYPE
+ SYNTAX XATSSwitchBlockMapEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information about a specific ATS blocking map."
+ INDEX { xATSSwitchBlockMapIndex }
+ ::= { xATSSwitchBlockMapTable 1 }
+
+ XATSSwitchBlockMapEntry ::=
+ SEQUENCE {
+ xATSSwitchBlockMapIndex INTEGER,
+ xATSSwitchBlockMapName DisplayString,
+ xATSSwitchBlockMapStatus INTEGER,
+ xATSSwitchBlockMapSetting INTEGER
+ }
+
+ xATSSwitchBlockMapIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index of blocking map entries in the table."
+ ::= { xATSSwitchBlockMapEntry 1 }
+
+ xATSSwitchBlockMapName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A string describing the ATS action to be blocked."
+ ::= { xATSSwitchBlockMapEntry 2 }
+
+ xATSSwitchBlockMapStatus OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Represents the status of this blocking map entry, in bit-mapped format.
+ A non-zero value indicates that this entry's ATS action is currently being blocked.
+ The bit(s) set indicate which input(s) are causing the blocking (bit0, bit1, etc).
+
+ bit 0 - Contact 1
+ bit 1 - Contact 2
+ bit 2 - Contact 3
+ bit 3 - Contact 4."
+ ::= { xATSSwitchBlockMapEntry 3 }
+
+ xATSSwitchBlockMapSetting OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "This setting designates the inputs that block the ATS action
+ The mapping is specified as a bit-field, where each bit set indicates
+ the input that blocks the ATS action associated with the entry.
+
+ bit 0 - Contact 1
+ bit 1 - Contact 2
+ bit 2 - Contact 3
+ bit 3 - Contact 4."
+ ::= { xATSSwitchBlockMapEntry 4 }
+
+-- The xATSSwitchStatistics group
+
+ xATSSwitchStatisticsTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of transfer switch statistics entries."
+ ::= { xATSSwitchStatistics 1 }
+
+ xATSSwitchStatisticsTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF XATSSwitchStatisticsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of statistics supported by ATS.
+ The number of entries is contained in the xATSSwitchStatisticsTableSize OID."
+ ::= { xATSSwitchStatistics 2 }
+
+ xATSSwitchStatisticsEntry OBJECT-TYPE
+ SYNTAX XATSSwitchStatisticsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information about an individual ATS statistic."
+ INDEX { xATSSwitchStatisticsIndex }
+ ::= { xATSSwitchStatisticsTable 1 }
+
+ XATSSwitchStatisticsEntry ::=
+ SEQUENCE {
+ xATSSwitchStatisticsIndex INTEGER,
+ xATSSwitchStatisticsName DisplayString,
+ xATSSwitchStatisticsValue DisplayString,
+ xATSSwitchStatisticsReset INTEGER
+ }
+
+ xATSSwitchStatisticsIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index of ATS statistics entries in the table."
+ ::= { xATSSwitchStatisticsEntry 1 }
+
+ xATSSwitchStatisticsName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This is the name of the ATS statistic associated with this entry."
+ ::= { xATSSwitchStatisticsEntry 2 }
+
+ xATSSwitchStatisticsValue OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This is the value of the ATS statistic associated with this entry."
+ ::= { xATSSwitchStatisticsEntry 3 }
+
+ xATSSwitchStatisticsReset OBJECT-TYPE
+ SYNTAX INTEGER{
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "This will reset the individual ATS statistic associated with this entry."
+ ::= { xATSSwitchStatisticsEntry 4 }
+
+-- The xATS Source 1 group
+
+xATSSource1Name OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "String used to identify source 1."
+ ::= { xATSSource1 1 }
+
+xATSSource1Position OBJECT-TYPE
+ SYNTAX INTEGER{
+ open (1),
+ closed (2),
+ tripped (3),
+ unknown (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current position of the switch at source 1."
+ ::= { xATSSource1 2 }
+
+xATSSource1Frequency OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The frequency at source 1 in tenths of Hertz.
+ -1 if unavailable."
+ ::= { xATSSource1 3 }
+
+xATSSource1Quality OBJECT-TYPE
+ SYNTAX INTEGER{
+ sourceGood (1),
+ lowVoltage (2),
+ highVoltage (3),
+ phaseImbalance (4),
+ freqOutOfRange (5),
+ badRotation (6),
+ unknown (7)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current line quality of source 1."
+ ::= { xATSSource1 4 }
+
+xATSSource1Rotation OBJECT-TYPE
+ SYNTAX INTEGER{
+ abc (1),
+ cba (2),
+ unknown (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The phase rotation measured at the source 1 input of the ATS.
+ The sequence is a reference to the order in which the three phases
+ pass the zero-crossing boundary in time."
+ ::= { xATSSource1 5 }
+
+xATSSource1TableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of input voltage entries at the source 1 input of the ATS."
+ ::= { xATSSource1 6 }
+
+ xATSSource1PhaseTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF XATSSource1PhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of voltage table entries for source 1. The number of
+ entries are the phase entries. The number of entries is contained in the
+ xATSSource1TableSize OID."
+ ::= { xATSSource1 7 }
+
+ xATSSource1PhaseEntry OBJECT-TYPE
+ SYNTAX XATSSource1PhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular input voltage phase at the source 1 input of the ATS."
+ INDEX { xATSSource1Index }
+ ::= { xATSSource1PhaseTable 1 }
+
+ XATSSource1PhaseEntry ::= SEQUENCE {
+ xATSSource1Index INTEGER,
+ xATSSource1VoltageLtoL INTEGER,
+ xATSSource1VoltageLtoN INTEGER
+ }
+
+ xATSSource1Index OBJECT-TYPE
+ SYNTAX INTEGER{
+ phase1(1),
+ phase2(2),
+ phase3(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Description of each phase utilized at source 1."
+ ::= { xATSSource1PhaseEntry 1 }
+
+ xATSSource1VoltageLtoL OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Source 1 line-to-line input voltage.
+ Measured in tenths of Volts."
+ ::= { xATSSource1PhaseEntry 2 }
+
+ xATSSource1VoltageLtoN OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Source 1 line-to-neutral input voltage.
+ Measured in tenths of Volts. -1 for a 3-wire service type."
+ ::= { xATSSource1PhaseEntry 3 }
+
+-- The xATS Source 2 group
+
+xATSSource2Name OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "String used to identify source 2."
+ ::= { xATSSource2 1 }
+
+xATSSource2Position OBJECT-TYPE
+ SYNTAX INTEGER{
+ open (1),
+ closed (2),
+ tripped (3),
+ unknown (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current position of the switch at source 2."
+ ::= { xATSSource2 2 }
+
+xATSSource2Frequency OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The frequency at source 2 in tenths of Hertz.
+ -1 if not available."
+ ::= { xATSSource2 3 }
+
+xATSSource2Quality OBJECT-TYPE
+ SYNTAX INTEGER{
+ sourceGood (1),
+ lowVoltage (2),
+ highVoltage (3),
+ phaseImbalance (4),
+ freqOutOfRange (5),
+ badRotation (6),
+ unknown (7)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current line quality of source 2."
+ ::= { xATSSource2 4 }
+
+xATSSource2Rotation OBJECT-TYPE
+ SYNTAX INTEGER{
+ abc (1),
+ cba (2),
+ unknown (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The phase rotation measured at the source 2 input of the ATS.
+ -1 if not available."
+ ::= { xATSSource2 5 }
+
+xATSSource2TableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of input voltage entries at the source 2 input of the ATS."
+ ::= { xATSSource2 6 }
+
+ xATSSource2PhaseTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF XATSSource2PhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of voltage table entries for the source 2. The number of
+ entries are the phase entries. The number of entries is contained in the
+ xATSSource2TableSize OID."
+ ::= { xATSSource2 7 }
+
+ xATSSource2PhaseEntry OBJECT-TYPE
+ SYNTAX XATSSource2PhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular input voltage phase at the source 2 input of the ATS."
+ INDEX { xATSSource2Index }
+ ::= { xATSSource2PhaseTable 1 }
+
+ XATSSource2PhaseEntry ::= SEQUENCE {
+ xATSSource2Index INTEGER,
+ xATSSource2VoltageLtoL INTEGER,
+ xATSSource2VoltageLtoN INTEGER
+ }
+
+ xATSSource2Index OBJECT-TYPE
+ SYNTAX INTEGER{
+ phase1(1),
+ phase2(2),
+ phase3(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Description of each phase utilized at the source 2."
+ ::= { xATSSource2PhaseEntry 1 }
+
+ xATSSource2VoltageLtoL OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Source 2 line-to-line input voltage.
+ Measured in tenths of Volts."
+ ::= { xATSSource2PhaseEntry 2 }
+
+ xATSSource2VoltageLtoN OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Source 2 line-to-neutral input voltage.
+ Measured in tenths of Volts. -1 for a 3-wire service type."
+ ::= { xATSSource2PhaseEntry 3 }
+
+-- The xATSSystemOutput
+
+xATSSystemOutputFrequency OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The system output frequency in tenths of Hertz."
+ ::= { xATSSystemOutput 1 }
+
+xATSSystemOutputTotalPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Shows the total system output power in tenths of kW."
+ ::= { xATSSystemOutput 2 }
+
+xATSSystemOutputTotalApparentPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Shows the total system output power in tenths of kVA."
+ ::= { xATSSystemOutput 3 }
+
+xATSSystemOutputTotalPowerFactor OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the total power factor of the system output.
+ A value of 100 representing a unity power factor (1.00)
+ Specified in hundredths."
+ ::= { xATSSystemOutput 4 }
+
+xATSSystemOutputFrequencyTolerance OBJECT-TYPE
+ SYNTAX INTEGER{
+ freqToleranceOff (1),
+ freqTolerancePointTwo (2),
+ freqTolerancePointFive (3),
+ freqToleranceOne (4),
+ freqToleranceOnePointFive (5),
+ freqToleranceTwo (6),
+ freqToleranceThree (7),
+ freqToleranceFour (8),
+ freqToleranceFive (9),
+ freqToleranceNine (10)
+
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Shows the panel output frequency tolerance in +/- Hertz."
+ ::= { xATSSystemOutput 5 }
+
+xATSSystemOutputOverVoltThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold above which an output over voltage condition will be generated.
+ Specified as tenths of percent deviation from nominal.
+ A value of zero indicates that the threshold is disabled."
+ ::= { xATSSystemOutput 6 }
+
+xATSSystemOutputUnderVoltThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold below which an output under voltage condition will be generated.
+ Specified as tenths of percent deviation from nominal.
+ A value of zero indicates that the threshold is disabled."
+ ::= { xATSSystemOutput 7 }
+
+xATSSystemOutputOverCurrentThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold above which an over current condition will be generated.
+ Specified as a percent of the transfer switch rating (xATSDeviceTransferSwitchRating OID).
+ A value of zero indicates that the threshold is disabled."
+ ::= { xATSSystemOutput 8 }
+
+xATSSystemOutputUnderCurrentThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold below which an under current condition will be generated.
+ Specified as a percent of the transfer switch rating (xATSDeviceTransferSwitchRating OID).
+ A value of zero indicates that the threshold is disabled."
+ ::= { xATSSystemOutput 9 }
+
+xATSSystemOutputAlarmDelayThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Delay the generation of an output alarm.
+ Specified in seconds."
+ ::= { xATSSystemOutput 10 }
+
+xATSSystemOutputTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of system output phase entries."
+ ::= { xATSSystemOutput 11 }
+
+xATSSystemOutputPhaseTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF XATSSystemOutputPhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of system output table entries.
+ The number of entries is contained in the xATSSystemOutputTableSize OID."
+ ::= { xATSSystemOutput 12 }
+
+ xATSSystemOutputPhaseEntry OBJECT-TYPE
+ SYNTAX XATSSystemOutputPhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular system output phase."
+ INDEX { xATSSystemOutputPhaseIndex }
+ ::= { xATSSystemOutputPhaseTable 1 }
+
+ XATSSystemOutputPhaseEntry ::= SEQUENCE {
+ xATSSystemOutputPhaseIndex INTEGER,
+ xATSSystemOutputVoltageLtoL INTEGER,
+ xATSSystemOutputVoltageLtoN INTEGER,
+ xATSSystemOutputPhaseCurrent INTEGER,
+ xATSSystemOutputPower INTEGER,
+ xATSSystemOutputApparentPower INTEGER,
+ xATSSystemOutputPowerFactor INTEGER
+ }
+
+ xATSSystemOutputPhaseIndex OBJECT-TYPE
+ SYNTAX INTEGER{
+ phase1(1),
+ phase2(2),
+ phase3(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Description of each system output phase utilized in this device."
+ ::= { xATSSystemOutputPhaseEntry 1 }
+
+ xATSSystemOutputVoltageLtoL OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Line-to-line system output voltage available at the circuit panel.
+ Measured in tenths of Volts. -1 if not available."
+ ::= { xATSSystemOutputPhaseEntry 2 }
+
+ xATSSystemOutputVoltageLtoN OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Line-to-neutral system output voltage available at the circuit panel.
+ Measured in tenths of Volts. -1 for a 3-wire service type or if not available."
+ ::= { xATSSystemOutputPhaseEntry 3 }
+
+ xATSSystemOutputPhaseCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "System load current per phase. Measured in Amps.
+ -1 if not available."
+ ::= { xATSSystemOutputPhaseEntry 4 }
+
+ xATSSystemOutputPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "System output power per phase. Measured in tenths of kW."
+ ::= { xATSSystemOutputPhaseEntry 5 }
+
+ xATSSystemOutputApparentPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "system output power per phase. Measured in tenths of kVA."
+ ::= { xATSSystemOutputPhaseEntry 6 }
+
+ xATSSystemOutputPowerFactor OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "indicates the power factor of the system output per phase.
+ A value of 100 representing a unity power factor (1.00).
+ Measured in hundredths."
+ ::= { xATSSystemOutputPhaseEntry 7 }
+
+-- xATS TestingStatus group
+
+xATSTestingStatusSelectTestProcess OBJECT-TYPE
+ SYNTAX INTEGER {
+ engineStartTest (1),
+ systemLoadTest (2),
+ generatorHoldTest (3),
+ cancelTest (4)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Type of tests that can be selected when no test has been scheduled.
+ engineStartTest and systemLoadTest may be selected when no tests
+ are running. Tests that are selected may be canceled manually."
+ ::= { xATSTestingStatus 1 }
+
+xATSTestingStatusTestStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ noTestInProcess (1),
+ testPending (2),
+ startingEngine (3),
+ engineWarmingUp (4),
+ awaitingTransferToS2 (5),
+ testingWithLoad (6),
+ awaitingRetransferToS1 (7),
+ testingWithoutLoad (8),
+ stoppingEngine (9),
+ holdingOnGenerator (10)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The present system test status/state."
+ ::= { xATSTestingStatus 2 }
+
+xATSTestingStatusProfileWarmupTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The amount of time that the generator will warm up during a test.
+ This is portion of the test when the xATSTestingStatusTestStatus
+ OID returns the value engineWarmingUp.
+ Specified in seconds."
+ ::= { xATSTestingStatus 3 }
+
+xATSTestingStatusProfileLoadedTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The amount of time that ATS will apply the system load to the generator
+ during a system load test.
+ This is portion of the test when the xATSTestingStatusTestStatus
+ OID returns the value testingWithLoad.
+ Specified in minutes."
+ ::= { xATSTestingStatus 4 }
+
+xATSTestingStatusProfileUnloadedTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The amount of time that the generator will run following the warm up
+ portion of a start test, or the loaded portion of a load test.
+ This is portion of the test when the xATSTestingStatusTestStatus
+ OID returns the value testingWithoutLoad.
+ Specified in seconds."
+ ::= { xATSTestingStatus 5 }
+
+-- xATS TestingResults group
+
+xATSTestingResultsLastDateOfTest OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Date of the last test that was performed, either scheduled or manual.
+ Test results are available in the xATSTestingResultsLastResult OID.
+ Specified in the dd/mm/yyyy format, or 'none' if not available."
+ ::= { xATSTestingResults 1 }
+
+xATSTestingResultsLastResult OBJECT-TYPE
+ SYNTAX INTEGER {
+ noResultsAvailable (1),
+ startTestPassed (2),
+ loadTestPassed (3),
+ startSignalFailure (4),
+ failedGenNotInAuto (5),
+ failedGenEmerStop (6),
+ failedGenShutdown (7),
+ failedGenDidNotStart (8),
+ failedS2NeverGood (9),
+ genFailedDuringWarmup (10),
+ failureOnXferToS1 (11),
+ genFailedLoaded (12),
+ failureOnRexferToS2 (13),
+ failedOnCooldown (14),
+ genFailedToStop (15),
+ failedAtsInternalFault (16),
+ failedAtsNotInAuto (17),
+ canceledManualTest (18),
+ canceledScheduledTest (19)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The result of the last ATS/generator system test."
+ ::= { xATSTestingResults 2 }
+
+xATSTestingResultsTestLastTestTime OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Time of day at which the last test was performed, either scheduled or manual.
+ Test results are available in the xATSTestingResultsLastResult OID.
+ Specified in the hh:mm:ss format, or 'none' if not available."
+ ::= { xATSTestingResults 3 }
+
+xATSTestingResultsLastCrankDuration OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The time spent cranking the generator before it started during the last test.
+ Specified in seconds, or -1 if not available."
+ ::= { xATSTestingResults 4 }
+
+xATSTestingResultsLastWarmupDuration OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The time spent in the engineWarmingUp state during the last system test.
+ Specified in seconds, or -1 if not available."
+ ::= { xATSTestingResults 5 }
+
+xATSTestingResultsLastLoadedDuration OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The time spent in the testingWithLoad state during the last system test.
+ Specified in seconds, or -1 if not available."
+ ::= { xATSTestingResults 6 }
+
+xATSTestingResultsLastUnloadedDuration OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The time spent in the testingWithoutLoad state during the last system test.
+ Specified in seconds, or -1 if not available."
+ ::= { xATSTestingResults 7 }
+
+-- xATS TestingSchedule group
+
+xATSTestingScheduleFrequency OBJECT-TYPE
+ SYNTAX INTEGER {
+ never (1),
+ daily (2),
+ weekly (3),
+ monthly (4)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The frequency of running scheduled tests."
+ ::= { xATSTestingSchedule 1 }
+
+xATSTestingScheduleTestDay OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The desired day for the scheduled test. This object applies only
+ when the xATSTestingScheduleFrequency OID is set to weekly or monthly.
+ For weekly test frequency, the string is the day the test will be run.
+ For monthly test frequency, the string indicates the day,
+ and the instance within the month.
+ For example, for monthly frequency: 2nd Sunday, 3rd Monday, 4th Tuesday,
+ for weekly frequency: Sunday, Monday, Tuesday."
+ ::= { xATSTestingSchedule 2 }
+
+xATSTestingScheduleTestTime OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The time of day that the scheduled test will occur.
+ Specified in the format hh:mm."
+ ::= { xATSTestingSchedule 3 }
+
+xATSTestingScheduleTestWithLoadInterval OBJECT-TYPE
+ SYNTAX INTEGER {
+ applyLoadEveryTest (1),
+ neverApplyLoad (2),
+ applyLoadMonthly (3),
+ applyLoadMonthlyDetailed (4)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "This setting specifies which system tests should include applying the
+ load to the generator. The applyLoadMonthlyDetailed entry
+ in the list will apply load once, for each month represented in the
+ xATSTestingScheduleTestWithLoadSelectMonth OID."
+ ::= { xATSTestingSchedule 4 }
+
+xATSTestingScheduleTestWithLoadSelectMonth OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The detailed selection for testing with load on a month-by-month basis.
+ This object is applicable when the xATSTestingScheduleTestWithLoadInterval
+ is set to applyLoadMonthlyDetailed. Otherwise this selection will be ignored.
+ Format for this string is a comma-separated entry of months.
+ For example: Jan,Mar,Dec.
+ The string will return 'No Months Scheduled' if no months have been selected."
+ ::= { xATSTestingSchedule 5 }
+
+xATSTestingScheduleNextTestDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The date of the next scheduled test, in the format dd-mmm-yyyy."
+ ::= { xATSTestingSchedule 6 }
+
+-- xATSTestingSimulatePowerFail group
+
+xATSTestingSimulatePowerFailTest OBJECT-TYPE
+ SYNTAX INTEGER{
+ cancelSimulation (1),
+ fiveSecondsSimulation (2),
+ tenSecondsSimulation (3),
+ thirtySecondsSimulation (4),
+ oneMinuteSimulation (5),
+ threeMinutesSimulation (6),
+ fiveMinutesSimulation (7),
+ tenMinutesSimulation (8)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "This object executes a simulated power failure for the duration indicated.
+ Simulation can be aborted by selecting cancelSimulation."
+ ::= { xATSTestingSimulatePowerFail 1 }
+
+xATSTestingSimulatePowerFailTimeRemaining OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the time remaining in seconds, for a simulated power failure.
+ a value of zero indicates that simulated power failure is not active."
+ ::= { xATSTestingSimulatePowerFail 2 }
+
+-- The xATS Input Contact group
+
+xATSInputContactNumContacts OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of contacts supported by the ATS."
+ ::= { xATSInputContacts 1 }
+
+xATSInputContactTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of input contact entries."
+ ::= { xATSInputContacts 2 }
+
+xATSInputContactTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF XATSInputContactEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of contacts supported by the ATS.
+ The number of entries is contained in the
+ xATSInputContactTableSize OID."
+ ::= { xATSInputContacts 3 }
+
+ xATSInputContactEntry OBJECT-TYPE
+ SYNTAX XATSInputContactEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A contact entry containing information for a given contact."
+ INDEX { xATSInputContactNumber }
+ ::= { xATSInputContactTable 1 }
+
+ XATSInputContactEntry ::=
+ SEQUENCE {
+ xATSInputContactNumber INTEGER,
+ xATSInputContactName DisplayString,
+ xATSInputContactNormalState INTEGER,
+ xATSInputContactCurrentState INTEGER
+ }
+
+ xATSInputContactNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An index identifying the contact on the ATS."
+ ::= { xATSInputContactEntry 1 }
+
+ xATSInputContactName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The description of the purpose/use of the contact."
+ ::= { xATSInputContactEntry 2 }
+
+ xATSInputContactNormalState OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The normal operating position of the contact."
+ ::= { xATSInputContactEntry 3 }
+
+ xATSInputContactCurrentState OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This value indicates the current state of the contact."
+ ::= { xATSInputContactEntry 4 }
+
+-- the xATS OutputRelays group
+
+ xATSOutputRelayNumRelays OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of output relays supported by the ATS."
+ ::= { xATSOutputRelays 1 }
+
+ xATSOutputRelayTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of output relay entries."
+ ::= { xATSOutputRelays 2 }
+
+ xATSOutputRelayTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF XATSOutputRelayEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of output relays supported by the ATS.
+ The number of entries is contained in the
+ xATSOutputRelayTableSize OID."
+ ::= { xATSOutputRelays 3 }
+
+ xATSOutputRelayEntry OBJECT-TYPE
+ SYNTAX XATSOutputRelayEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A output relay entry containing information for a given contact."
+ INDEX { xATSOutputRelayNumber }
+ ::= { xATSOutputRelayTable 1 }
+
+ XATSOutputRelayEntry ::=
+ SEQUENCE {
+ xATSOutputRelayNumber INTEGER,
+ xATSOutputRelayName DisplayString,
+ xATSOutputRelayNormalState INTEGER,
+ xATSOutputRelayCurrentState INTEGER
+ }
+
+ xATSOutputRelayNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An index identifying the output relay on the ATS."
+ ::= { xATSOutputRelayEntry 1 }
+
+ xATSOutputRelayName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The description of the purpose/use of the output relay."
+ ::= { xATSOutputRelayEntry 2 }
+
+ xATSOutputRelayNormalState OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The normal operating position of the output relay."
+ ::= { xATSOutputRelayEntry 3 }
+
+ xATSOutputRelayCurrentState OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This value indicates the current state of the output relay."
+ ::= { xATSOutputRelayEntry 4 }
+
+-- The xATS Generator Ident group
+
+xATSGeneratorIdentModelNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the model number of the generator.
+ This value is set at the factory."
+ ::= { xATSGeneratorIdent 1 }
+
+xATSGeneratorIdentSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the serial number of the generator.
+ This value is set at the factory."
+ ::= { xATSGeneratorIdent 2 }
+
+xATSGeneratorIdentDateofManufacture OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying when the generator was manufactured in mm/dd/yyyy format.
+ This value is set at the factory."
+ ::= { xATSGeneratorIdent 3 }
+
+xATSGeneratorIdentVoltageConfiguration OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The voltage for which the generator's alternator is designed.
+ Specified in Volts line-to-line."
+ ::= { xATSGeneratorIdent 4 }
+
+xATSGeneratorIdentMaxPowerRating OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The max power rating of the generator. Specified in kW."
+ ::= { xATSGeneratorIdent 5 }
+
+xATSGeneratorIdentAlternatorFrequency OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The frequency for which the generator's alternator is designed.
+ Specified in Hertz."
+ ::= { xATSGeneratorIdent 6 }
+
+-- The xATS Generator Status group
+
+xATSGeneratorStatusGeneratorName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The name or label for the generator connected to the source 2 of the ATS."
+ ::= { xATSGeneratorStatus 1 }
+
+xATSGeneratorStatusOperational OBJECT-TYPE
+ SYNTAX INTEGER{
+ nocomm (1),
+ off (2),
+ ready (3),
+ starting (4),
+ idle (5),
+ running (6),
+ normalStop (7),
+ emergencyStop (8),
+ notInAuto (9),
+ shutdown (10),
+ unknown (11)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The operational status of the generator. unavailable when unrecognized status is received."
+ ::= { xATSGeneratorStatus 2 }
+
+xATSGeneratorStatusModeSwitchPosition OBJECT-TYPE
+ SYNTAX INTEGER{
+ off (1),
+ manual (2),
+ automatic (3),
+ unknown (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The position of the generator's auto-mode switch.
+ In automatic mode, the generator is started and stopped via the
+ remote start contact, which has state indicated in the
+ xATSGeneratorStatusRemoteStart OID.
+ In manual mode generator start/stop control is via local command only.
+ Off prevents the generator from running."
+ ::= { xATSGeneratorStatus 3 }
+
+xATSGeneratorStatusRemoteStart OBJECT-TYPE
+ SYNTAX INTEGER{
+ stop (1),
+ run (2),
+ unknown (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the generator's remote start contact, which is
+ provided as an output from the transfer switch to start/stop the
+ generator when in automatic mode."
+ ::= { xATSGeneratorStatus 4 }
+
+-- The xATS Generator Advanced Status group
+
+xATSGeneratorAdvStatusBatteryVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The voltage of the generator's starting battery.
+ Measured in tenths of VDC, or -1 if not available."
+ ::= { xATSGeneratorAdvStatus 1 }
+
+xATSGeneratorAdvStatusOilPressure OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The generator's engine oil pressure.
+ Measured in tenths of Psi or kPa, based on the
+ value of the xATSGeneratorSettingsMetricUnit OID,
+ or -1 if not available."
+ ::= { xATSGeneratorAdvStatus 2 }
+
+xATSGeneratorAdvStatusCoolantTemperature OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Current coolant temperature in the generator.
+ Measured in degrees Celsius or Fahrenheit, based on the
+ value of the xATSGeneratorSettingsMetricUnit OID,
+ or -1 if not available."
+ ::= { xATSGeneratorAdvStatus 3 }
+
+xATSGeneratorAdvStatusEngineRPM OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Current engine speed of the generator.
+ Measured in RPM, or -1 if not available."
+ ::= { xATSGeneratorAdvStatus 4 }
+
+xATSGeneratorAdvStatusOilLevel OBJECT-TYPE
+ SYNTAX INTEGER{
+ ok (1),
+ low (2),
+ unknown (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates adequate oil level in the generator."
+ ::= { xATSGeneratorAdvStatus 5 }
+
+xATSGeneratorAdvStatusCoolantLevel OBJECT-TYPE
+ SYNTAX INTEGER{
+ ok (1),
+ low (2),
+ unknown (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates adequate coolant level in the generator."
+ ::= { xATSGeneratorAdvStatus 6 }
+
+-- The xATS Generator Output group
+
+xATSGeneratorOutputFrequency OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output frequency of the generator.
+ Measured in tenths of Hertz, or -1 if not available."
+ ::= { xATSGeneratorOutput 1 }
+
+xATSGeneratorOutputTotalPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The total output power of the generator.
+ Measured in tenths of tenths of kW, or -1 if not available."
+ ::= { xATSGeneratorOutput 2 }
+
+xATSGeneratorOutputTotalApparentPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The total output power of the generator.
+ Measured in tenths of kVA, or -1 if not available."
+ ::= { xATSGeneratorOutput 3 }
+
+xATSGeneratorOutputTotalPowerFactor OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the total load power factor of the generator.
+ A value of 100 representing a unity power factor (1.00),
+ or -1 when if not available."
+ ::= { xATSGeneratorOutput 4 }
+
+xATSGeneratorOutputTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of generator output phase entries."
+ ::= { xATSGeneratorOutput 5 }
+
+ xATSGeneratorOutputPhaseTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF XATSGeneratorOutputPhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of generator output table entries.
+ The number of entries is contained in the xATSGeneratorOutputTableSize OID."
+ ::= { xATSGeneratorOutput 6 }
+
+ xATSGeneratorOutputPhaseEntry OBJECT-TYPE
+ SYNTAX XATSGeneratorOutputPhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular generator output phase."
+ INDEX { xATSGeneratorOutputPhaseIndex }
+ ::= { xATSGeneratorOutputPhaseTable 1 }
+
+ XATSGeneratorOutputPhaseEntry ::= SEQUENCE {
+ xATSGeneratorOutputPhaseIndex INTEGER,
+ xATSGeneratorOutputVoltageLtoL INTEGER,
+ xATSGeneratorOutputVoltageLtoN INTEGER,
+ xATSGeneratorOutputPhaseCurrent INTEGER,
+ xATSGeneratorOutputPower INTEGER,
+ xATSGeneratorOutputApparentPower INTEGER,
+ xATSGeneratorOutputPowerFactor INTEGER
+ }
+
+ xATSGeneratorOutputPhaseIndex OBJECT-TYPE
+ SYNTAX INTEGER{
+ phase1(1),
+ phase2(2),
+ phase3(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Description of each generator output phase utilized in this device."
+ ::= { xATSGeneratorOutputPhaseEntry 1 }
+
+ xATSGeneratorOutputVoltageLtoL OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Line-to-line generator output voltage.
+ Measured in Volts, or -1 if not available."
+ ::= { xATSGeneratorOutputPhaseEntry 2 }
+
+ xATSGeneratorOutputVoltageLtoN OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Line-to-neutral generator output voltage.
+ Measured in volts, or -1 if not available."
+ ::= { xATSGeneratorOutputPhaseEntry 3 }
+
+ xATSGeneratorOutputPhaseCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Generator load current per phase.
+ Measured in Amps, or -1 if not available."
+ ::= { xATSGeneratorOutputPhaseEntry 4 }
+
+ xATSGeneratorOutputPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Generator output power per phase.
+ Measured in tenths of kW, or -1 if not available."
+ ::= { xATSGeneratorOutputPhaseEntry 5 }
+
+ xATSGeneratorOutputApparentPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Generator output power per phase.
+ Measured in tenths of kVA, or -1 if not available."
+ ::= { xATSGeneratorOutputPhaseEntry 6 }
+
+ xATSGeneratorOutputPowerFactor OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the load power factor of the generator output per phase.
+ A value of 100 representing a unity power factor (1.00),
+ or -1 if not available."
+ ::= { xATSGeneratorOutputPhaseEntry 7 }
+
+-- xATS Generator Settings group
+
+xATSGeneratorSettingsVoltageAdjust OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The voltage adjust of the generator.
+ Specified in volts line-to-line,
+ or -1 if not available."
+ ::= { xATSGeneratorSettings 1 }
+
+xATSGeneratorSettingsFrequencyAdjust OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The frequency adjust of the generator.
+ Specified in tenths of Hertz."
+ ::= { xATSGeneratorSettings 2 }
+
+xATSGeneratorSettingsStartDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The delay, in seconds, after the remote run signal is activated
+ before the generator's engine will be cranked to start,
+ or -1 if not available."
+ ::= { xATSGeneratorSettings 3 }
+
+xATSGeneratorSettingsStopDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The delay, in seconds, before the generator will stop
+ after the remote run signal is deactivated,
+ or -1 if not available."
+ ::= { xATSGeneratorSettings 4 }
+
+xATSGeneratorSettingsCrankCycleEnable OBJECT-TYPE
+ SYNTAX INTEGER{
+ disabled (1),
+ enabled (2),
+ unknown (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "When Crank Cycle is enabled, the engine will be cranked up to the time
+ specified by the xATSGeneratorSettingsCrankTime OID.
+ If the generator's engine does not start, there will be a pause as
+ specified by the xATSGeneratorSettingsCrankRestTime OID before the
+ engine will be cranked again. This cycle is repeated as specified by
+ the xATSGeneratorSettingsNumberCrank OID.
+ When crank cycle is disabled, the generator's engine will be
+ cranked continuously until it starts."
+ ::= { xATSGeneratorSettings 5 }
+
+xATSGeneratorSettingsCrankTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The duration of engine cranking, in seconds, when starting the generator.
+ Applicable when the xATSGeneratorSettingsCrankCycleEnable OID is enabled.
+ -1 if not available."
+ ::= { xATSGeneratorSettings 6 }
+
+xATSGeneratorSettingsCrankRestTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The pause duration, in seconds, following an unsuccessful attempt to start the generator.
+ Applicable when the xATSGeneratorSettingsCrankCycleEnable OID is enabled.
+ -1 if not available."
+ ::= { xATSGeneratorSettings 7 }
+
+xATSGeneratorSettingsNumberCrank OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of failed crank attempts before giving up on starting the generator.
+ Applicable when the xATSGeneratorSettingsCrankCycleEnable OID is enabled.
+ -1 if not available."
+ ::= { xATSGeneratorSettings 8 }
+
+xATSGeneratorSettingsMetricUnit OBJECT-TYPE
+ SYNTAX INTEGER{
+ disabled (1),
+ enabled (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Specifies the use of metric units in generator related OIDs, as well
+ as on all other interfaces including the generator's local interface."
+ ::= { xATSGeneratorSettings 9 }
+
+-- xATS generator service group
+
+xATSGeneratorServiceTotalRunHoursLifetime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Total time that the generator engine has been run,
+ over the life of the generator. Measured in hours.
+ -1 if not available."
+ ::= { xATSGeneratorService 1 }
+
+xATSGeneratorServiceEngineStartsLifetime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Number of engine starts over the life of the generator.
+ -1 if not available."
+ ::= { xATSGeneratorService 2 }
+
+xATSGeneratorServiceTotalkWhLifetime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Total kWh of operation over the life of the generator.
+ -1 if not available."
+ ::= { xATSGeneratorService 3 }
+
+xATSGeneratorServiceTotalRunHoursSinceMaintenance OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Total time that the generator engine has been run,
+ since last service maintenance. Measured in tenths of hours.
+ -1 if not available."
+ ::= { xATSGeneratorService 4 }
+
+xATSGeneratorServiceEngineStartsSinceMaintenance OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Number of engine starts since last service maintenance.
+ -1 if not available."
+ ::= { xATSGeneratorService 5 }
+
+xATSGeneratorServiceTotalkWhMaintenance OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Total kWh of operation since last service maintenance.
+ -1 if not available."
+ ::= { xATSGeneratorService 6 }
+
+xATSGeneratorServiceResetRecord OBJECT-TYPE
+ SYNTAX INTEGER{
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Resets the engine start counter, engine run-hours, and kWh values that have
+ accumulated in the generator since last maintenance.
+ Also, the last service date will be reset to the current system date, and
+ any service alarms will be cleared."
+ ::= { xATSGeneratorService 7 }
+
+xATSGeneratorServiceRecordResetDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Date at which the generator's service record was reset, in dd-mmm-yyyy format."
+ ::= { xATSGeneratorService 8 }
+
+xATSGeneratorServiceNextServiceDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Date at which the next generator service is due in dd-mmm-yyyy format.
+ Based on the xATSGeneratorServiceCalendarIntervalThreshold OID
+ or '' if the calendar-based threshold is set to off."
+ ::= { xATSGeneratorService 9 }
+
+xATSGeneratorServiceRunHoursUntilServiceDate OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Run hours until the next generator service is due, in hours.
+ Based on the xATSGeneratorServiceRunHoursThreshold OID
+ or -1 if the run hour-based threshold is set to off."
+ ::= { xATSGeneratorService 10 }
+
+xATSGeneratorServiceRunHoursThreshold OBJECT-TYPE
+ SYNTAX INTEGER{
+ disabled (1),
+ runThreshold100Hours (2),
+ runThreshold150Hours (3),
+ runThreshold200Hours (4),
+ runThreshold250Hours (5),
+ runThreshold300Hours (6),
+ runThreshold400Hours (7),
+ runThreshold500Hours (8)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Run hour-based service interval. When the run-hours since
+ service surpasses this threshold, generator service is due."
+ ::= { xATSGeneratorService 11 }
+
+xATSGeneratorServiceCalendarIntervalThreshold OBJECT-TYPE
+ SYNTAX INTEGER{
+ disabled (1),
+ interval1month (2),
+ interval2month (3),
+ interval3month (4),
+ interval6month (5),
+ intervalyearly (6)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Calendar-based service interval. When the next service date,
+ as indicated by the xATSGeneratorServiceNextServiceDate OID
+ is in the past, generator is due for service."
+ ::= { xATSGeneratorService 12 }
+
+-- The xATS Generator Fuel system group
+
+xATSGeneratorFuelSystemType OBJECT-TYPE
+ SYNTAX INTEGER{
+ diesel (1),
+ propane (2),
+ naturalGas (3),
+ unknown (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The type of fuel used by the generator."
+ ::= { xATSGeneratorFuelSystem 1 }
+
+xATSGeneratorFuelSystemTankSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Size of the generator's fuel tank.
+ Specified in gallons or liters, based on the value of the
+ xATSGeneratorSettingsMetricUnit OID, or -1 if not available."
+ ::= { xATSGeneratorFuelSystem 2 }
+
+xATSGeneratorFuelSystemFuelLevel OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Fuel remaining in the generator tank.
+ Measured in percent of tank fill, or -1 if not available."
+ ::= { xATSGeneratorFuelSystem 3 }
+
+xATSGeneratorFuelSystemRuntimePower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The power value used in the runtime remaining calculation.
+ Measured in tenths of kW, or -1 if not available."
+ ::= { xATSGeneratorFuelSystem 4 }
+
+xATSGeneratorFuelSystemEstimatedRunTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An estimate of available runtime for the generator, based on
+ available fuel as specified in the xATSGeneratorFuelSystemFuelLevel OID
+ and kW load as specified in the xATSGeneratorFuelSystemRuntimePower OID.
+ Measured in tenths of hours, or -1 if not available."
+ ::= { xATSGeneratorFuelSystem 5 }
+
+xATSGeneratorFuelSystemLowRunTimeThreshold OBJECT-TYPE
+ SYNTAX INTEGER{
+ disabled (1),
+ oneHour (2),
+ twoHours (3),
+ threeHours (4),
+ fourHours (5),
+ fiveHours (6),
+ sixHours (7),
+ twelveHours (8),
+ oneDay (9),
+ twoDays (10),
+ threeDays (11),
+ fourDays (12),
+ fiveDays (13),
+ sixDays (14),
+ sevenDays (15)
+
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold below which a low runtime alarm will exist."
+ ::= { xATSGeneratorFuelSystem 6 }
+
+xATSGeneratorFuelSystemVeryLowRunTimeThreshold OBJECT-TYPE
+ SYNTAX INTEGER{
+ disabled (1),
+ oneHour (2),
+ twoHours (3),
+ threeHours (4),
+ fourHours (5),
+ fiveHours (6),
+ sixHours (7),
+ twelveHours (8),
+ oneDay (9),
+ twoDays (10),
+ threeDays (11),
+ fourDays (12),
+ fiveDays (13),
+ sixDays (14),
+ sevenDays (15)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold below which a very low runtime alarm will exist."
+ ::= { xATSGeneratorFuelSystem 7 }
+
+xATSGeneratorFuelSystemLowFuelLevelThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold below which a low fuel alarm will exist, with a value of 0 indicating disabled.
+ Specified as percent of tank fill."
+ ::= { xATSGeneratorFuelSystem 8 }
+
+xATSGeneratorFuelSystemVeryLowFuelLevelThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold below which a very low fuel alarm will exist, with a value of 0 indicating disabled.
+ Specified as percent of tank fill."
+ ::= { xATSGeneratorFuelSystem 9 }
+
+-- The console Port Server AP930x system group
+
+apCPSpname OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The product's name."
+::= { cpsAP930xSys 1 }
+
+apCPSversion OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The firmware's version."
+::= {cpsAP930xSys 2}
+
+apCPSPower OBJECT IDENTIFIER ::= { cpsAP930xSys 3 }
+
+apCPSPwNum OBJECT-TYPE
+ SYNTAX Integer32
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The number of the power supplies."
+::= { apCPSPower 1 }
+
+apCPSPw1 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "State of the first power supply.
+ 0 will indicate not installed,
+ 1 will indicate power ON,
+ 2 will indicate power OFF."
+::= { apCPSPower 2 }
+
+apCPSPw2 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "State of the second power supply.
+ 0 will indicate not installed,
+ 1 will indicate power ON,
+ 2 will indicate power OFF."
+::= { apCPSPower 3 }
+
+apCPSPcmcia OBJECT IDENTIFIER ::= {cpsAP930xSys 4}
+
+apCPSNPcmcia OBJECT-TYPE
+ SYNTAX Integer32
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Number of PCMCIA cards available."
+::= { apCPSPcmcia 1 }
+
+cpsCardIdentTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF CpsCardIdentEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "A table of PCMCIA card identifications."
+::= { apCPSPcmcia 2 }
+
+cpsCardIdentEntry OBJECT-TYPE
+ SYNTAX CpsCardIdentEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "Identification information for a PCMCIA card."
+ INDEX { cpsCardIdentIndex }
+::= { cpsCardIdentTable 1 }
+
+CpsCardIdentEntry ::= SEQUENCE {
+ cpsCardIdentIndex Integer32,
+ cpsCardIdentProd DisplayString,
+ cpsCardIdentMan DisplayString ,
+ cpsCardIdentFunc DisplayString,
+ cpsCardIdentPCI DisplayString
+}
+
+cpsCardIdentIndex OBJECT-TYPE
+ SYNTAX Integer32
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Number to identify the socket Card."
+::= { cpsCardIdentEntry 1 }
+
+cpsCardIdentProd OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Product identification string."
+::= { cpsCardIdentEntry 2 }
+
+cpsCardIdentMan OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Manufacturer ID code."
+::= { cpsCardIdentEntry 3 }
+
+cpsCardIdentFunc OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Function ID code."
+::= { cpsCardIdentEntry 4 }
+
+cpsCardIdentPCI OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "PCI ID"
+::= { cpsCardIdentEntry 5 }
+
+cpsCardConfTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF CpsCardConfEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "A table of socket configuration information."
+::= { apCPSPcmcia 3 }
+
+cpsCardConfEntry OBJECT-TYPE
+ SYNTAX CpsCardConfEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "Configuration information for a socket."
+ INDEX { cpsCardConfIndex }
+::= { cpsCardConfTable 1 }
+
+CpsCardConfEntry ::= SEQUENCE {
+ cpsCardConfIndex Integer32,
+ cpsCardConfPower DisplayString,
+ cpsCardConfType DisplayString,
+ cpsCardConfInter DisplayString,
+ cpsCardConfFunc DisplayString,
+ cpsCardConfCardv DisplayString,
+ cpsCardConfPort1 DisplayString,
+ cpsCardConfPort2 DisplayString
+}
+
+cpsCardConfIndex OBJECT-TYPE
+ SYNTAX Integer32
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Number to identify the socket PCMCIA."
+::= { cpsCardConfEntry 1 }
+
+cpsCardConfPower OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Power Settings."
+::= { cpsCardConfEntry 2 }
+
+cpsCardConfType OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Interface Type."
+::= { cpsCardConfEntry 3 }
+
+cpsCardConfInter OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Interrupt number."
+::= { cpsCardConfEntry 4 }
+
+cpsCardConfFunc OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Function."
+::= { cpsCardConfEntry 5 }
+
+cpsCardConfCardv OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Card values."
+::= { cpsCardConfEntry 6 }
+
+cpsCardConfPort1 OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "I/O Port 1."
+::= { cpsCardConfEntry 7 }
+
+cpsCardConfPort2 OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "I/O Port 2."
+::= { cpsCardConfEntry 8 }
+
+cpsCardStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF CpsCardStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "A table of current socket status information."
+::= { apCPSPcmcia 4 }
+
+cpsCardStatusEntry OBJECT-TYPE
+ SYNTAX CpsCardStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "Current status information for a socket."
+ INDEX { cpsCardStatusIndex }
+::= { cpsCardStatusTable 1 }
+
+CpsCardStatusEntry ::= SEQUENCE {
+ cpsCardStatusIndex Integer32,
+ cpsCardStatusCard DisplayString,
+ cpsCardStatusFunc DisplayString
+}
+
+cpsCardStatusIndex OBJECT-TYPE
+ SYNTAX Integer32(0..2)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Number to identify the socket PCMCIA."
+::= { cpsCardStatusEntry 1 }
+
+cpsCardStatusCard OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Current Card State."
+::= { cpsCardStatusEntry 2 }
+
+cpsCardStatusFunc OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Current Function."
+::= { cpsCardStatusEntry 3 }
+
+apCPSFlashSize OBJECT-TYPE
+ SYNTAX Integer32
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Total amount of flash memory in Mbytes."
+::= {cpsAP930xSys 5}
+
+apCPSRAMSize OBJECT-TYPE
+ SYNTAX Integer32
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Total amount of RAM in Mbytes."
+::= {cpsAP930xSys 6}
+
+apCPSCPUfreq OBJECT-TYPE
+ SYNTAX Integer32
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "CPU clock in MHz."
+::= {cpsAP930xSys 7}
+
+apCPSDevId OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The product's identifier."
+::= { cpsAP930xSys 8 }
+
+
+-- The console Port Server AP930x configuration group
+
+cpsHostName OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..40))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "The Host Name."
+::= { cpsAP930xConf 1 }
+
+cpsConsoleBanner OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..255))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "The console banner."
+::= { cpsAP930xConf 2 }
+
+cpsMotd OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..255))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "The motd message."
+::= { cpsAP930xConf 3 }
+
+cpsEthItf OBJECT IDENTIFIER ::= { cpsAP930xConf 4 }
+
+cpsEthDhcpc OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "0 will indicate DHCP inactive,
+ 1 will indicate DHCP active,
+ 2 will indicate DHCP active and the last parameter is saved."
+::= { cpsEthItf 1 }
+
+cpsEthIPaddr OBJECT-TYPE
+ SYNTAX IpAddress
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "This is the IP address of the Ethernet Interface."
+::= { cpsEthItf 2 }
+
+cpsEthIPmask OBJECT-TYPE
+ SYNTAX IpAddress
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "The mask for the Ethernet network."
+::= { cpsEthItf 3 }
+
+cpsEthMTU OBJECT-TYPE
+ SYNTAX Integer32
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "The Maximum Transmission Unit size, which determines
+ whether packets should be broken up."
+::= { cpsEthItf 4 }
+
+cpsEthIPaddr2 OBJECT-TYPE
+ SYNTAX IpAddress
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "The Ethernet secondary IP address."
+::= { cpsEthItf 5 }
+
+cpsEthIPmask2 OBJECT-TYPE
+ SYNTAX IpAddress
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "The Ethernet secondary IP mask."
+::= { cpsEthItf 6 }
+
+cpsNameService OBJECT IDENTIFIER ::= { cpsAP930xConf 5 }
+
+cpsResolverOrder OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..15))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "Specifies how host lookups are to be performed.
+ Valid values : empty, 'hosts', 'bind', 'hosts, bind',
+ 'bind, hosts' "
+::= { cpsNameService 1 }
+
+cpsMultipleIP OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..3))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "Valid values are ON or OFF. If set to ON, the resolve
+ library will return all valid addresses for a host
+ that appears in the /etc/hosts file, instead of only
+ the first. "
+::= { cpsNameService 2 }
+
+cpsDNSserv OBJECT IDENTIFIER ::= { cpsNameService 3 }
+
+cpsDNSpriserv OBJECT-TYPE
+ SYNTAX IpAddress
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "Internet Address (in dot notation) of primary name
+ server that the resolver should query."
+::= { cpsDNSserv 1 }
+
+cpsDNSsecserv OBJECT-TYPE
+ SYNTAX IpAddress
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "Internet Address (in dot notation) of secondary name
+ server that the resolver should query."
+::= { cpsDNSserv 2 }
+
+cpsDNSdomain OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..40))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "Local domain name."
+::= { cpsDNSserv 3 }
+
+cpsSerialPortConf OBJECT IDENTIFIER ::= { cpsAP930xConf 6 }
+
+cpsSerialGlobal OBJECT IDENTIFIER ::= { cpsSerialPortConf 1 }
+
+cpsSerialInclude OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..40))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "File used in centralized management."
+::= { cpsSerialGlobal 1 }
+
+cpsSerialNFS OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..50))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "Remote Network File System where data buffering will be
+ written instead of the default directory '/var/run/DB'."
+::= { cpsSerialGlobal 2 }
+
+cpsSerialLockDir OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..50))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "The lock directory."
+::= { cpsSerialGlobal 3 }
+
+cpsSerialRlogin OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..50))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "Location of the rlogin binary that accepts the -i flag."
+::= { cpsSerialGlobal 4 }
+
+cpsSerialPppd OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..50))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "Location of the pppd binary."
+::= { cpsSerialGlobal 5 }
+
+cpsSerialTelnet OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..50))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "Location of the telnet application."
+::= { cpsSerialGlobal 6 }
+
+cpsSerialSsh OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..50))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "Location of the ssh application."
+::= { cpsSerialGlobal 7 }
+
+cpsSerialLocalLogins OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "This parameter is only necessary when authentication is
+ being performed for a port.
+ This is useful if the Radius authentication server is down.
+ 0 indicates OFF,
+ 1 indicates ON."
+::= { cpsSerialGlobal 8 }
+
+cpsSerialFacility OBJECT-TYPE
+ SYNTAX Integer32
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "This value (0-7) is the Local facility sent to the syslog daemon."
+::= { cpsSerialGlobal 9 }
+
+cpsSerialDBFacility OBJECT-TYPE
+ SYNTAX Integer32
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "This value (0-7) is the Local facility sent to the syslog daemon."
+::= { cpsSerialGlobal 10 }
+
+cpsSerialGroupTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF CpsSerialGroupEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION ""
+::= { cpsSerialGlobal 11 }
+
+cpsSerialGroupEntry OBJECT-TYPE
+ SYNTAX CpsSerialGroupEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION ""
+ INDEX { cpsSerialGroupIndex }
+::= { cpsSerialGroupTable 1 }
+
+CpsSerialGroupEntry ::= SEQUENCE {
+ cpsSerialGroupIndex INTEGER,
+ cpsSerialGroupName DisplayString,
+ cpsSerialGroupUsers DisplayString
+}
+
+cpsSerialGroupIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Number to identify the group."
+::= { cpsSerialGroupEntry 1 }
+
+cpsSerialGroupName OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..20))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "The group name."
+::= { cpsSerialGroupEntry 2 }
+
+cpsSerialGroupUsers OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..80))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "The user's names."
+::= { cpsSerialGroupEntry 3 }
+
+cpsSerialSpec OBJECT IDENTIFIER ::= { cpsSerialPortConf 2 }
+
+cpsSerialPortTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF CpsSerialPortEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "This is the specific configuration per serial port."
+::= { cpsSerialSpec 1 }
+
+cpsSerialPortEntry OBJECT-TYPE
+ SYNTAX CpsSerialPortEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "One particular serial port configuration."
+ INDEX { cpsSerialPortNumber }
+::= { cpsSerialPortTable 1 }
+
+CpsSerialPortEntry ::= SEQUENCE {
+ cpsSerialPortNumber INTEGER, -- 0 == all. X == ttyX sX.
+ cpsSerialPortTty DisplayString, -- associate device
+ cpsSerialPortName DisplayString, -- alias name
+ cpsSerialPortSpeed Integer32, -- physical port configuration
+ cpsSerialPortDataSize Integer32,
+ cpsSerialPortStopBits Integer32,
+ cpsSerialPortParity DisplayString,
+ cpsSerialPortFlowCtrl DisplayString,
+ cpsSerialPortDTRdelay Integer32,
+ cpsSerialPortDCDCtrl INTEGER,
+ cpsSerialPortLogUtmp INTEGER, -- log into UTMP
+ cpsSerialPortLogWtmp INTEGER, -- log into WTMP
+ cpsSerialPortLogform DisplayString,
+ cpsSerialPortAuthtype DisplayString, -- authentication type
+ cpsSerialPortAuthSrv1 IpAddress, -- IP address of the primary authentication server
+ cpsSerialPortAccSrv1 IpAddress, -- IP address of the primary accounting server
+ cpsSerialPortAuthTmo Integer32, -- time out per authentication query
+ cpsSerialPortAuthRetr Integer32, -- authentication number of retries
+ cpsSerialPortAuthSrv2 IpAddress, -- IP address of the secondary authentication server
+ cpsSerialPortAccSrv2 IpAddress, -- IP address of the secondary accounting server
+ cpsSerialPortAuthSecret DisplayString, -- secret used in authentication
+ cpsSerialPortAuthRadP INTEGER, -- accept RADIUS' user without password
+ cpsSerialPortAuthAcc DisplayString, -- access restriction on Users
+ cpsSerialPortProtocol DisplayString, -- Profile
+ cpsSerialPortRemoteIP DisplayString, -- remote IP address
+ cpsSerialPortSocketPort DisplayString, -- number of socket port
+ cpsSerialPortRemHost IpAddress, -- IP address of the remote Host
+ cpsSerialPortBanner DisplayString, -- Banner
+ cpsSerialPortPrompt DisplayString, -- Login prompt
+ cpsSerialPortTermType DisplayString, -- terminal type
+ cpsSerialPortAutomUsr DisplayString, -- automatic user
+ cpsSerialPortNetMask IpAddress, -- net mask
+ cpsSerialPortPppMtu Integer32,
+ cpsSerialPortPppMru Integer32,
+ cpsSerialPortPppOptions DisplayString,
+ cpsSerialPortPppFoption DisplayString,
+ cpsSerialPortModemChat DisplayString, -- initchat send to modem
+ cpsSerialPortSttyCmd DisplayString,
+ cpsSerialPortSockTx Integer32, -- socket transmission interval
+ cpsSerialPortSockPoll Integer32, -- socket polling interval
+ cpsSerialPortSockIdle Integer32, -- socket idle timeout
+ cpsSerialPortDBsize Integer32, -- maximum size of the data buffering file
+ cpsSerialPortDBtime INTEGER, -- data buffering with/without timestamp
+ cpsSerialPortDBmode DisplayString, -- data bufferinf mode circ or line
+ cpsSerialPortDBsyslog Integer32, -- size of the data send to syslog
+ cpsSerialPortDBmenu INTEGER, -- menu of the data buffering
+ cpsSerialPortDBalarm INTEGER, -- use alarm generating feature
+ cpsSerialPortSSHbreak DisplayString, -- break sequence (SSH)
+ cpsSerialPortSniffSess DisplayString, -- sniff session type
+ cpsSerialPortSniffAdm DisplayString, -- admin users to sniff
+ cpsSerialPortSniffEsc DisplayString, -- escape char to sniff session
+ cpsSerialPortSniffMsess DisplayString, -- multiple session
+ cpsSerialPortTelnetMode INTEGER, -- telnet client mode
+ cpsSerialPortSysBufSess INTEGER, -- syslog buffering at all times
+ cpsSerialPortLFSuppress INTEGER, -- LF suppression in socket_server session
+ cpsSerialPortAutoInput DisplayString, -- Input string to auto answer
+ cpsSerialPortAutoOutput DisplayString, -- Output string to auto answer
+ cpsSerialPortBreakInterval Integer32 -- Break interval (in ms)
+}
+
+cpsSerialPortNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Number to identify the serial port. Value 0 is ALL."
+::= { cpsSerialPortEntry 1 }
+
+cpsSerialPortTty OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..25))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "The device name for the serial port."
+::= { cpsSerialPortEntry 2 }
+
+cpsSerialPortName OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..40))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "Alias name given to the server connected to the serial port."
+::= { cpsSerialPortEntry 3 }
+
+cpsSerialPortSpeed OBJECT-TYPE
+ SYNTAX Integer32
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "The speed of the serial port.
+ Supported values are:
+ 50, 75, 110, 134, 150, 200, 300, 600,
+ 1200, 1800, 2400, 4800, 9600, 14400, 19200,
+ 28800, 38400, 57600, 115200, 230400, and 460800"
+::= { cpsSerialPortEntry 4 }
+
+cpsSerialPortDataSize OBJECT-TYPE
+ SYNTAX Integer32 (4..8)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "The data size for the serial port."
+::= { cpsSerialPortEntry 5 }
+
+cpsSerialPortStopBits OBJECT-TYPE
+ SYNTAX Integer32 (0..2)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "The number of stop bits for the serial port."
+::= { cpsSerialPortEntry 6 }
+
+cpsSerialPortParity OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..5))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "The parity for the serial port."
+::= { cpsSerialPortEntry 7 }
+
+cpsSerialPortFlowCtrl OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..5))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "The flow control for the serial port."
+::= { cpsSerialPortEntry 8 }
+
+cpsSerialPortDTRdelay OBJECT-TYPE
+ SYNTAX Integer32
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "This specifies how long (in milliseconds) a DTR signal
+ will be turned off before it is turned on again."
+::= { cpsSerialPortEntry 9 }
+
+cpsSerialPortDCDCtrl OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "DCD signal controls the connection request.
+ 0 will indicate nocontrol,
+ 1 will indicate control."
+::= { cpsSerialPortEntry 10 }
+
+cpsSerialPortLogUtmp OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "Update the login records in /var/run/utmp file.
+ 0 will indicate inactive,
+ 1 will indicate active."
+::= { cpsSerialPortEntry 11 }
+
+cpsSerialPortLogWtmp OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "Update the login records in /var/run/wtmp file.
+ 0 will indicate inactive,
+ 1 will indicate active."
+::= { cpsSerialPortEntry 12 }
+
+cpsSerialPortLogform OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..40))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "This is the format to write the login record."
+::= { cpsSerialPortEntry 13 }
+
+cpsSerialPortAuthtype OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..25))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "Authentication type."
+::= { cpsSerialPortEntry 14 }
+
+cpsSerialPortAuthSrv1 OBJECT-TYPE
+ SYNTAX IpAddress
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "IP address of the primary authentication server."
+::= { cpsSerialPortEntry 15 }
+
+cpsSerialPortAccSrv1 OBJECT-TYPE
+ SYNTAX IpAddress
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "IP address of the primary accounting server."
+::= { cpsSerialPortEntry 16 }
+
+cpsSerialPortAuthTmo OBJECT-TYPE
+ SYNTAX Integer32
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "This is the timeout (in seconds) for the authentication
+ query to be answered."
+::= { cpsSerialPortEntry 17 }
+
+cpsSerialPortAuthRetr OBJECT-TYPE
+ SYNTAX Integer32
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "This defines the number of times each server is tried
+ before another is contacted."
+::= { cpsSerialPortEntry 18 }
+
+cpsSerialPortAuthSrv2 OBJECT-TYPE
+ SYNTAX IpAddress
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "IP address of the secondary authentication server."
+::= { cpsSerialPortEntry 19 }
+
+cpsSerialPortAccSrv2 OBJECT-TYPE
+ SYNTAX IpAddress
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "IP address of the secondary accounting server."
+::= { cpsSerialPortEntry 20 }
+
+cpsSerialPortAuthSecret OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..40))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "This is the shared secret with authentication servers."
+::= { cpsSerialPortEntry 21 }
+
+cpsSerialPortAuthRadP OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "Radius state.
+ 0 will indicate inactive,
+ 1 will indicate active."
+::= { cpsSerialPortEntry 22 }
+
+cpsSerialPortAuthAcc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..40))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "Access restriction."
+::= { cpsSerialPortEntry 23 }
+
+cpsSerialPortProtocol OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..40))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "Defines the serial port's protocol."
+::= { cpsSerialPortEntry 24 }
+
+cpsSerialPortRemoteIP OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..20))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "This is the default IP address of the serial port."
+::= { cpsSerialPortEntry 25 }
+
+cpsSerialPortSocketPort OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..10))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "This defines an alternative labeling system for the serial port."
+::= { cpsSerialPortEntry 26 }
+
+cpsSerialPortRemHost OBJECT-TYPE
+ SYNTAX IpAddress
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "The IP address of the host to which the serial port will connect."
+::= { cpsSerialPortEntry 27 }
+
+cpsSerialPortBanner OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..250))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "This defines the banner."
+::= { cpsSerialPortEntry 28 }
+
+cpsSerialPortPrompt OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..250))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "This defines the login prompt to the serial port."
+::= { cpsSerialPortEntry 29 }
+
+cpsSerialPortTermType OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..20))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "This defines the terminal type."
+::= { cpsSerialPortEntry 30 }
+
+cpsSerialPortAutomUsr OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..40))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "This defines the automatic user."
+::= { cpsSerialPortEntry 31 }
+
+cpsSerialPortNetMask OBJECT-TYPE
+ SYNTAX IpAddress
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "The network mask used in dial in connection."
+::= { cpsSerialPortEntry 32 }
+
+cpsSerialPortPppMtu OBJECT-TYPE
+ SYNTAX Integer32
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "The PPP MTU - dial in connection."
+::= { cpsSerialPortEntry 33 }
+
+cpsSerialPortPppMru OBJECT-TYPE
+ SYNTAX Integer32
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "The PPP MRU - dial in connection."
+::= { cpsSerialPortEntry 34 }
+
+cpsSerialPortPppOptions OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "The PPP options when the PPP session is autodetected."
+::= { cpsSerialPortEntry 35 }
+
+cpsSerialPortPppFoption OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "The PPP forced options when the user has already been authenticated."
+::= { cpsSerialPortEntry 36 }
+
+cpsSerialPortModemChat OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "The initchat send to modem connected."
+::= { cpsSerialPortEntry 37 }
+
+cpsSerialPortSttyCmd OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..180))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "The tty settings after socket connection is established."
+::= { cpsSerialPortEntry 38 }
+
+cpsSerialPortSockTx OBJECT-TYPE
+ SYNTAX Integer32
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "Defines the delay (in milliseconds) before transmission to
+ the Ethernet of data received through a serial port."
+::= { cpsSerialPortEntry 39 }
+
+cpsSerialPortSockPoll OBJECT-TYPE
+ SYNTAX Integer32
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "Keep-alive timer (milliseconds) for the TCP connection."
+::= { cpsSerialPortEntry 40 }
+
+cpsSerialPortSockIdle OBJECT-TYPE
+ SYNTAX Integer32
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "The idle timeout in seconds."
+::= { cpsSerialPortEntry 41 }
+
+cpsSerialPortDBsize OBJECT-TYPE
+ SYNTAX Integer32
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "Maximum size of the data buffering file."
+::= { cpsSerialPortEntry 42 }
+
+cpsSerialPortDBtime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "Timestamp in data buffering.
+ 0 will indicate inactive,
+ 1 will indicate active."
+::= { cpsSerialPortEntry 43 }
+
+cpsSerialPortDBmode OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..5))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "Data buffering mode : circ or line."
+::= { cpsSerialPortEntry 44 }
+
+cpsSerialPortDBsyslog OBJECT-TYPE
+ SYNTAX Integer32
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "Size of the data buffer sent to syslog."
+::= { cpsSerialPortEntry 45 }
+
+cpsSerialPortDBmenu OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "Menu type for data buffering.
+ 0 will indicate display Menu,
+ 1 will indicate inactive,
+ 2 will indicate DB,
+ 3 will indicate Parc."
+::= { cpsSerialPortEntry 46 }
+
+cpsSerialPortDBalarm OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "Alarm generation status.
+ 0 will indicate inactive,
+ 1 will indicate active."
+::= { cpsSerialPortEntry 47 }
+
+cpsSerialPortSSHbreak OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..16))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "Break sequence - ssh session."
+::= { cpsSerialPortEntry 48 }
+
+cpsSerialPortSniffSess OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..5))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "Sniff session type."
+::= { cpsSerialPortEntry 49 }
+
+cpsSerialPortSniffAdm OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..40))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "List of admin users allowed to sniff session."
+::= { cpsSerialPortEntry 50 }
+
+cpsSerialPortSniffEsc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..6))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "Escape sequence used in sniff session."
+::= { cpsSerialPortEntry 51 }
+
+cpsSerialPortSniffMsess OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..20))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION ""
+::= { cpsSerialPortEntry 52 }
+
+cpsSerialPortTelnetMode OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "Mode negotiated by client telnet with the server.
+ 0 will indicate text,
+ 1 will indicate binary."
+::= { cpsSerialPortEntry 53 }
+
+cpsSerialPortSysBufSess OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "Syslog Buffering at all times.
+ 0 will indicate yes,
+ 1 will indicate no."
+::= { cpsSerialPortEntry 54 }
+
+cpsSerialPortLFSuppress OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "LF suppression in socket_server session.
+ 0 will indicate inactive,
+ 1 will indicate active."
+::= { cpsSerialPortEntry 55 }
+
+cpsSerialPortAutoInput OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..40))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "Input string used for auto answer."
+::= { cpsSerialPortEntry 56 }
+
+cpsSerialPortAutoOutput OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..40))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "Output string used for auto answer."
+::= { cpsSerialPortEntry 57 }
+
+cpsSerialPortBreakInterval OBJECT-TYPE
+ SYNTAX Integer32
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "The break interval in milliseconds."
+::= { cpsSerialPortEntry 58 }
+
+-- The console Port Server AP930x information group
+
+cpsInfoSerialPortTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF CpsInfoSerialPortEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "This is the information of the specific serial port."
+::= { cpsAP930xInfo 1 }
+
+cpsInfoSerialPortEntry OBJECT-TYPE
+ SYNTAX CpsInfoSerialPortEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "One particular serial port."
+ INDEX { cpsInfoSerialPortNumber }
+::= { cpsInfoSerialPortTable 1 }
+
+CpsInfoSerialPortEntry ::= SEQUENCE {
+ cpsInfoSerialPortNumber INTEGER, -- X == ttyX sX.
+ cpsInfoSerialPortTty DisplayString, -- associate device
+ cpsInfoSerialPortName DisplayString, -- alias name
+ cpsInfoSerialPortSpeed Integer32,
+ cpsInfoSerialPortTxBytes Integer32,
+ cpsInfoSerialPortRXBytes Integer32,
+ cpsInfoSerialPortErrFrame Integer32,
+ cpsInfoSerialPortErrParity Integer32,
+ cpsInfoSerialPortErrBreaks Integer32,
+ cpsInfoSerialPortErrOverrun Integer32,
+ cpsInfoSerialPortSigDTR INTEGER,
+ cpsInfoSerialPortSigCD INTEGER,
+ cpsInfoSerialPortSigDSR INTEGER,
+ cpsInfoSerialPortSigRTS INTEGER,
+ cpsInfoSerialPortSigCTS INTEGER,
+ cpsInfoSerialPortSigRI INTEGER
+ }
+
+cpsInfoSerialPortNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Number to identify the serial port."
+::= { cpsInfoSerialPortEntry 1 }
+
+cpsInfoSerialPortTty OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The device name for the serial port."
+::= { cpsInfoSerialPortEntry 2 }
+
+cpsInfoSerialPortName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Alias name given to the server connected to the serial port."
+::= { cpsInfoSerialPortEntry 3 }
+
+cpsInfoSerialPortSpeed OBJECT-TYPE
+ SYNTAX Integer32
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The speed for serial port."
+::= { cpsInfoSerialPortEntry 4 }
+
+cpsInfoSerialPortTxBytes OBJECT-TYPE
+ SYNTAX Integer32
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The number of transmitted bytes by the serial port."
+::= { cpsInfoSerialPortEntry 5 }
+
+cpsInfoSerialPortRXBytes OBJECT-TYPE
+ SYNTAX Integer32
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The number of received bytes by the serial port."
+::= { cpsInfoSerialPortEntry 6 }
+
+cpsInfoSerialPortErrFrame OBJECT-TYPE
+ SYNTAX Integer32
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The number of frame errors."
+::= { cpsInfoSerialPortEntry 7 }
+
+cpsInfoSerialPortErrParity OBJECT-TYPE
+ SYNTAX Integer32
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The number of parity errors."
+::= { cpsInfoSerialPortEntry 8 }
+
+cpsInfoSerialPortErrBreaks OBJECT-TYPE
+ SYNTAX Integer32
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The number of breaks errors."
+::= { cpsInfoSerialPortEntry 9 }
+
+cpsInfoSerialPortErrOverrun OBJECT-TYPE
+ SYNTAX Integer32
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The number of overrun errors."
+::= { cpsInfoSerialPortEntry 10 }
+
+cpsInfoSerialPortSigDTR OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The state of the DTR signal.
+ 0 will indicate down,
+ 1 will indicate up."
+::= { cpsInfoSerialPortEntry 11 }
+
+cpsInfoSerialPortSigCD OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The state of the DCD signal.
+ 0 will indicate down,
+ 1 will indicate up."
+::= { cpsInfoSerialPortEntry 12 }
+
+cpsInfoSerialPortSigDSR OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The state of the DSR signal.
+ 0 will indicate down,
+ 1 will indicate up."
+::= { cpsInfoSerialPortEntry 13 }
+
+cpsInfoSerialPortSigRTS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The state of the RTS signal.
+ 0 will indicate down,
+ 1 will indicate up."
+::= { cpsInfoSerialPortEntry 14 }
+
+cpsInfoSerialPortSigCTS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The state of the CTS signal.
+ 0 will indicate down,
+ 1 will indicate up."
+::= { cpsInfoSerialPortEntry 15 }
+
+cpsInfoSerialPortSigRI OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The state of the RI signal.
+ 0 will indicate down,
+ 1 will indicate up."
+::= { cpsInfoSerialPortEntry 16 }
+
+-- The console Port Server AP930x administrative group
+
+apCPSSave OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "Exec saveconf command.
+ 0 will indicate don't save,
+ 1 will indicate save."
+::= { cpsAP930xAdm 1 }
+
+apCPSSerialHUP OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION "Exec signal_ras hup command.
+ 0 will indicate no restart,
+ 1 will indicate restart."
+::= { cpsAP930xAdm 2 }
+
+-- the access PX group
+
+accessPXIdentAlarmStatus OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Access PX alarm status
+ 1 = Normal
+ 2 = Warning
+ 3 = Critical."
+ ::= { accessPXIdent 1 }
+
+
+accessPXIdentProductNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The product number of the Access PX."
+ ::= { accessPXIdent 2 }
+
+accessPXIdentHardwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The hardware revision number of the Access PX."
+ ::= { accessPXIdent 3 }
+
+accessPXIdentDateOfManufacture OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The date of manufacture of the Access PX."
+ ::= { accessPXIdent 4 }
+
+accessPXIdentSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The serial number of the Access PX."
+ ::= { accessPXIdent 5 }
+
+accessPXConfigCardReaderEnableDisableAction OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Action to disable/enable the card reader."
+ ::= { accessPXConfig 1 }
+
+accessPXConfigAutoRelockTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Time (10 - 60) in seconds when the door will automatically relock
+ after it has been unlocked and the handle has not been opened."
+ ::= { accessPXConfig 2 }
+
+accessPXConfigCardFormat OBJECT-TYPE
+ SYNTAX INTEGER {
+ hidStd26 (1),
+ hid37Bit (2),
+ hid37BitWithFacility (3),
+ hidCorp1000 (4),
+ mifareclassic4b (5),
+ mifareclassic7b (6),
+ mifaredesfire (7),
+ mifareplus (8),
+ iCLASS8b (9)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates and controls the various card format."
+ ::= { accessPXConfig 3 }
+
+accessPXConfigFrontDoorLockControl OBJECT-TYPE
+ SYNTAX INTEGER {
+ unlock (1),
+ lock (2),
+ notInstalledReadOnly (3),
+ disconnectedReadOnly (4)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Control action (unlock, lock) for the front door. Setting this OID
+ will unlock or lock the front door. Getting this OID will respond
+ with the current state of the front door lock which could be
+ 1 = unlocked,
+ 2 = locked,
+ 3 = not installed,
+ 4 = disconnected."
+ ::= { accessPXConfigFront 1 }
+
+accessPXConfigFrontDoorMaxOpenTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Time in minutes, (1 - 120), that the front door can be
+ allowed to remain open without generating an alarm condition."
+ ::= { accessPXConfigFront 2 }
+
+accessPXStatusFrontDoorLock OBJECT-TYPE
+ SYNTAX INTEGER {
+ unlocked (1),
+ locked (2),
+ notInstalled (3),
+ disconnected (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Present state of the front door lock: unlocked, locked,
+ not installed, or disconnected."
+ ::= { accessPXStatusFront 1 }
+
+accessPXStatusFrontDoor OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2),
+ notInstalled (3),
+ disconnected (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Present state of the front door: open, closed,
+ not installed, or disconnected."
+ ::= { accessPXStatusFront 2 }
+
+accessPXStatusFrontDoorHandle OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2),
+ notInstalled (3),
+ disconnected (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Present state of the front door handle: open, closed,
+ not installed, or disconnected."
+ ::= { accessPXStatusFront 3 }
+
+accessPXStatusFrontDoorMaxOpenTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Time in minutes, (1 - 120), that the front door can be
+ allowed to remain open without generating an alarm condition."
+ ::= { accessPXStatusFront 4 }
+
+accessPXStatusFrontDoorAlarmStatus OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Front door alarm status
+ 1 = Normal
+ 2 = Warning
+ 3 = Critical
+ 4 = Front door not installed."
+ ::= { accessPXStatusFront 5 }
+
+accessPXConfigRearDoorLockControl OBJECT-TYPE
+ SYNTAX INTEGER {
+ unlock (1),
+ lock (2),
+ notInstalledReadOnly (3),
+ disconnectedReadOnly (4)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Control action (unlock, lock) for the rear door. Setting this OID
+ will unlock or lock the rear door. Getting this OID will respond
+ with the current state of the rear door lock which could be
+ 1 = unlocked,
+ 2 = locked,
+ 3 = not installed,
+ 4 = disconnected."
+ ::= { accessPXConfigRear 1 }
+
+accessPXConfigRearDoorMaxOpenTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Time in minutes, (1 - 120), that the rear door can be
+ allowed to remain open without generating an alarm condition."
+ ::= { accessPXConfigRear 2 }
+
+accessPXStatusRearDoorLock OBJECT-TYPE
+ SYNTAX INTEGER {
+ unlocked (1),
+ locked (2),
+ notInstalled (3),
+ disconnected (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Present state of the rear door lock: unlocked, locked,
+ not installed, or disconnected."
+ ::= { accessPXStatusRear 1 }
+
+accessPXStatusRearDoor OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2),
+ notInstalled (3),
+ disconnected (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Present state of the rear door: open, closed,
+ not installed, or disconnected."
+ ::= { accessPXStatusRear 2 }
+
+accessPXStatusRearDoorHandle OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2),
+ notInstalled (3),
+ disconnected (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Present state of the rear door handle: open, closed,
+ not installed, or disconnected."
+ ::= { accessPXStatusRear 3 }
+
+accessPXStatusRearDoorMaxOpenTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Time in minutes, (1 - 120), that the rear door can be
+ allowed to remain open without generating an alarm condition."
+ ::= { accessPXStatusRear 4 }
+
+accessPXStatusRearDoorAlarmStatus OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Rear door alarm status
+ 1 = Normal
+ 2 = Warning
+ 3 = Critical
+ 4 = Rear door not installed."
+ ::= { accessPXStatusRear 5 }
+
+accessPXConfigBeaconName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A descriptive name for the Beacon."
+ ::= { accessPXConfigBeacon 1 }
+
+accessPXConfigBeaconLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A descriptive name for the location of the Beacon."
+ ::= { accessPXConfigBeacon 2 }
+
+accessPXConfigBeaconAction OBJECT-TYPE
+ SYNTAX INTEGER {
+ turnOff (1),
+ turnOn (2),
+ notInstalledReadOnly (3),
+ disconnectedReadOnly (4)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Control action (turnOff, turnOn) for the beacon. Setting this OID
+ will turn the beacon off or on. Getting this OID will respond
+ with the current state which could be
+ 1 = off,
+ 2 = on,
+ 3 = not installed,
+ 4 = disconnected."
+ ::= { accessPXConfigBeacon 3 }
+
+accessPXStatusBeaconName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the beacon."
+ ::= { accessPXStatusBeacon 1 }
+
+accessPXStatusBeaconLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the location of the beacon."
+ ::= { accessPXStatusBeacon 2 }
+
+accessPXStatusBeaconCurrentState OBJECT-TYPE
+ SYNTAX INTEGER {
+ off (1),
+ on (2),
+ notInstalled (3),
+ disconnected (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current state of the beacon: off, on,
+ not installed, or disconnected."
+ ::= { accessPXStatusBeacon 3 }
+
+-- the apcLocalDisplay group
+
+apcLocalDisplayIdentDisplayType OBJECT-TYPE
+ SYNTAX INTEGER {
+ noDisplayFound (1),
+ powerviewRM (2),
+ powerviewWW (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Numeric value used to identify the type of display in use."
+ ::= { apcLocalDisplayIdent 1 }
+
+apcLocalDisplayIdentModelNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The model number of the local display."
+ ::= { apcLocalDisplayIdent 2 }
+
+apcLocalDisplayIdentFirmwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The firmware revision number of the local display."
+ ::= { apcLocalDisplayIdent 3 }
+
+apcLocalDisplayIdentOptions OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A display-specific string identifying options in the local display."
+ ::= { apcLocalDisplayIdent 4 }
+
+apcLocalDisplayIdentDateOfManufacture OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The date of manufacture of the local display, if available."
+ ::= { apcLocalDisplayIdent 5 }
+
+apcLocalDisplayIdentSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The serial number of the local display, if available."
+ ::= { apcLocalDisplayIdent 6 }
+
+apcLocalDisplayConfigAlarmBeeper OBJECT-TYPE
+ SYNTAX INTEGER {
+ beeperDisabled (1),
+ beeperEnabled (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The alarm beeper setting for the local display.
+ When enabled, the alarm beeper will begin to sound whenever
+ there a new alarm becomes active. The alarm beeper will continue to
+ periodically sound until a key is pressed on the display."
+ ::= { apcLocalDisplayConfig 1 }
+
+apcLocalDisplayConfigBeeperVolume OBJECT-TYPE
+ SYNTAX INTEGER {
+ beeperDisabled (1),
+ beeperLow (2),
+ beeperMedium (3),
+ beeperHigh (4)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The volume setting of the beeper on the local display."
+ ::= { apcLocalDisplayConfig 2 }
+
+apcLocalDisplayConfigCheckLogIndicator OBJECT-TYPE
+ SYNTAX INTEGER {
+ checklogNotPresent (1),
+ checklogDisabled (2),
+ checklogInformational (3),
+ checklogWarning (4),
+ checklogCritical (5)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum level event severity level required to illuminate
+ the check log light on the local display.
+ notPresent (1) indicates that the display does not have a check log light."
+ ::= { apcLocalDisplayConfig 3 }
+
+apcLocalDisplayConfigKeyClick OBJECT-TYPE
+ SYNTAX INTEGER {
+ keyclickDisabled (1),
+ keyclickEnabled (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The key click setting of the local display."
+ ::= { apcLocalDisplayConfig 4 }
+
+apcLocalDisplayConfigContrast OBJECT-TYPE
+ SYNTAX INTEGER {
+ contrast1 (1),
+ contrast2 (2),
+ contrast3 (3),
+ contrast4 (4),
+ contrast5 (5),
+ contrast6 (6),
+ contrast7 (7),
+ contrast8 (8)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The contrast level of the local display."
+ ::= { apcLocalDisplayConfig 5 }
+
+-- the software group
+-- the powerNetSubAgent group
+-- the powerNetSoftwareSystem group
+
+powerNetSoftwareSystemDescription OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..79))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A brief description of the PowerNet sub-agent."
+ ::= { powerNetSoftwareSystem 1 }
+
+powerNetSoftwareOid OBJECT-TYPE
+ SYNTAX OBJECT IDENTIFIER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The object identifier of the PowerNet sub-agent."
+ ::= { powerNetSoftwareSystem 2 }
+
+-- powerNetSmuxPeer OBJECT IDENTIFIER ::= { powerNetSoftwareOid 1 }
+-- powerNetDPIPeer OBJECT IDENTIFIER ::= { powerNetSoftwareOid 2 }
+
+powerNetSoftwareSystemUpTime OBJECT-TYPE
+ SYNTAX TimeTicks
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The time that the sub-agent has been running."
+ ::= { powerNetSoftwareSystem 3 }
+
+
+-- powerNetSoftwareConfig group
+
+powerNetSoftwareTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of software modules supporting the UPS."
+ ::= { powerNetSoftwareConfig 1 }
+
+powerNetSoftwareTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF PowerNetSoftwareEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of the software monitoring the UPS."
+ ::= { powerNetSoftwareConfig 2 }
+
+powerNetSoftwareEntry OBJECT-TYPE
+ SYNTAX PowerNetSoftwareEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information on a software module."
+ INDEX { moduleNumber }
+ ::= { powerNetSoftwareTable 1 }
+
+PowerNetSoftwareEntry ::=
+ SEQUENCE {
+ moduleNumber
+ INTEGER,
+ moduleName
+ DisplayString,
+ moduleVersion
+ DisplayString,
+ moduleDate
+ DisplayString
+ }
+
+moduleNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index into the Software Entry Table"
+ ::= { powerNetSoftwareEntry 1 }
+
+moduleName OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..79))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the software module."
+ ::= { powerNetSoftwareEntry 2 }
+
+moduleVersion OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..8))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The version of the software module."
+ ::= { powerNetSoftwareEntry 3 }
+
+moduleDate OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..9))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The date of the software module represented as mm-dd-yy."
+ ::= { powerNetSoftwareEntry 4 }
+
+-- the StruxureWare Operations group
+
+serverStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(1),
+ stopped(2),
+ running(3),
+ running-missing(4),
+ initializing(5),
+ starting(6),
+ disaster-recovery(7),
+ postoffice-inconsistent(8),
+ missing-jgroups(9)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the StruxureWare Operations server:
+ 1: The status of the application server is unknown. Check Webmin and if
+ the problem persists, contact Technical Support.
+ 2: Restart the StruxureWare DC Operation server. If the server was part of
+ a cluster, see the StruxureWare DC Operation User Assistance about
+ rejoining the cluster. If the problem persists, contact Technical Support.
+ 3: No problem.
+ 4: High availability is lost. The StruxureWare DC Operation Application
+ server is running but one or more nodes are not available. If the
+ StruxureWare DC Operation server is part of a cluster, ensure all nodes
+ are running and there is a network connection between the nodes. If the
+ problem persists, contact Technical Support.
+ 5: Wait for the StruxureWare DC Operation Application server to initialize.
+ If the problem persists, contact Technical Support.
+ 6: Wait for the StruxureWare DC Operation Application server to finish
+ starting.
+ If the problem persists, contact Technical Support.
+ 7: This node is running in Disaster Recovery mode.
+ 8: The JBoss postoffice is currently inconsistent. This may be a temporary
+ issue. If the problem persists for more than 10 minutes,
+ contact Technical Support.
+ 9: The JBoss is missing jgroups. This may be a temporary issue. If the
+ problem persists for more than 10 minutes, contact Technical Support."
+ ::= { struxureWareOperationsStatus 1 }
+
+databaseStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(1),
+ stopped(2),
+ running(3),
+ detached(4),
+ catching-up(5),
+ attaching(6),
+ running-master(7),
+ running-primary-slave(8),
+ running-slave(9),
+ running-alone(10)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the StruxureWare Operations database:
+ 1: The status of the database is unknown. Check Webmin and if the problem
+ persists, contact Technical Support.
+ 2: Restart the StruxureWare DC Operation server. If the server was part of
+ a cluster, see the StruxureWare DC Operation User Assistance about
+ rejoining the cluster. If the problem persists, contact Technical Support.
+ 3: No problem.
+ 4: High availability is lost. The database is detached from the cluster
+ and does not receive updates. See the StruxureWare DC Operation User
+ Assistance about reattaching the database node to the StruxureWare DC
+ Operation cluster.
+ If the problem persists, contact Technical Support.
+ 5: The database is catching up with the cluster. Wait for the StruxureWare
+ DC Operation database to retrieve all updates from the master node.
+ If the problem persists, contact Technical Support.
+ 6: The database is attaching to the cluster. Wait for the StruxureWare
+ Operation database to attach to the cluster. If the problem persists,
+ contact Technical Support.
+ 7: The database is the master in a cluster.
+ 8: The database is the primary slave in the cluster. All changes on master
+ are synchronously replicated to this node.
+ 9: The database is a secondary slave in the cluster. All changes on
+ master are asynchronously replicated to this node.
+ 10: The database does not replicate its changes to other nodes."
+ ::= { struxureWareOperationsStatus 2 }
+
+loadBalancerStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(1),
+ stopped(2),
+ running(3),
+ running-missing(4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the StruxureWare Operations load balancer:
+ 1: Load Balancer status is unknown. Check Webmin and if the problem
+ persists, contact Technical Support.
+ 2: Load Balancer stopped. Restart the StruxureWare DC Operation server.
+ If the problem persists, contact Technical Support.
+ 3: Normal status
+ 4: High availability is lost. The StruxureWare DC Operation Load Balancer
+ is running but one or more nodes are not available. If the StruxureWare DC
+ Operation server is part of a cluster, ensure all nodes are running and
+ there is a network connection between the nodes. If the problem persists,
+ contact Technical Support."
+ ::= { struxureWareOperationsStatus 3 }
+
+essentialServicesStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(1),
+ stopped(2),
+ running(3),
+ time-sync-problems(4),
+ backup-problems(5)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the StruxureWare Operations essential services:
+ 1: Unknown status. Check Webmin and if the problem persists, contact
+ Technical Support.
+ 2: Essential services are not running on the StruxureWare DC Operation
+ server. Reboot the node and monitor the status page in Webmin. If the
+ problem persists, contact Technical Support.
+ 3: Normal status
+ 4: The time difference between the StruxureWare DC Operation slave and the
+ master node is too big. Correct the time on the slave to match the time on
+ the master. Consider using an NTP server. If the problem persists,
+ contact Technical Support.
+ 5: The last backup that was attempted on the StruxureWare DC Operation
+ server has failed. Make certain that the system can write to the location
+ specified as backup location. This is particularly relevant for network
+ attached storage. If the problem persists, contact Technical Support."
+ ::= { struxureWareOperationsStatus 4 }
+
+etlStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(1),
+ running(2),
+ failed(3),
+ paused(4),
+ stopped(5)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the StruxureWare Operations ETL services:
+ 1: Unknown status. Check the network configuration and the server
+ network settings. If the problem persists, contact
+ Technical Support (http://www.apc.com/go/direct/index.cfm?tag=support).
+ 2: Normal status,
+ 3: ETL Transformations have failed and are subsequently stopped.
+ Investigate the cause of the failure. If the problem persists, contact
+ Technical Support (http://www.apc.com/go/direct/index.cfm?tag=support).
+ 4: ETL Transformations are currently paused.
+ 5: ETL Transformations are currently stopped."
+ ::= { struxureWareOperationsStatus 5 }
+
+
+-- the software group
+-- the powerChuteNetworkShutdown group
+-- the pcnsIdent group
+
+pcnshostname OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The hostname of the PCNS instance."
+ ::= { pcnsIdent 1 }
+
+pcnsVersion OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..9))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The version of PCNS installed. x.x.x"
+ ::= { pcnsIdent 2 }
+
+pcnsOS OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The version of OS PCNS is Installed on."
+ ::= { pcnsIdent 3 }
+
+pcnsJavaVersion OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The version of Java PCNS is running on."
+ ::= { pcnsIdent 4 }
+
+-- the software group
+-- the powerChuteNetworkShutdown group
+-- the pcnsNetworking group
+
+pcnsUIProtocol OBJECT-TYPE
+ SYNTAX INTEGER {
+ http(1),
+ https(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Web Protocol used to connect to the PCNS UI."
+ ::= { pcnsNetworking 1 }
+
+pcnsHttpPort OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Port used for PCNS http UI."
+ ::= { pcnsNetworking 2 }
+
+pcnsHttpsPort OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Port used for PCNS https UI."
+ ::= { pcnsNetworking 3 }
+
+pcnsNetworkConfig OBJECT-TYPE
+ SYNTAX INTEGER {
+ ipV4(1),
+ ipV6(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Configuration of the TCP Network."
+ ::= { pcnsNetworking 4 }
+
+pcnsVirtualInstall OBJECT-TYPE
+ SYNTAX INTEGER {
+ none(1),
+ hyper-V(2),
+ vmWare(3),
+ nutanixAHV(4),
+ nutanixESXi(5),
+ simpliVity(6),
+ hyperFlex(7)
+
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Virtualization technology in use by PCNS."
+ ::= { pcnsNetworking 5 }
+
+-- the software group
+-- the powerChuteNetworkShutdown group
+-- the pcnsNMC group
+
+pcnsMode OBJECT-TYPE
+ SYNTAX INTEGER {
+ single(1),
+ redundant(2),
+ parallel(3),
+ advanced(4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Configuration mode of the UPS(s) which PCNS is monitoring."
+ ::= { pcnsNMC 1 }
+
+pcnsNMCPort OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Port used to connect to all of the Network Management Card(s)."
+ ::= { pcnsNMC 2 }
+
+pcnsNMCProtocol OBJECT-TYPE
+ SYNTAX INTEGER {
+ http(1),
+ https(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Web Protocol used to connect to all of the Network Management Card(s)."
+ ::= { pcnsNMC 3 }
+
+pcnsNmcTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF PCNSNMCEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The Network Management Cards in the UPS's which PCNS is monitoring to provide safe shutdown."
+ ::= { pcnsNMC 4 }
+
+pcnsNmcEntry OBJECT-TYPE
+ SYNTAX PCNSNMCEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Details of the NMC."
+ INDEX { pcnsNmcIndex }
+ ::= { pcnsNmcTable 1 }
+
+PCNSNMCEntry ::=
+ SEQUENCE {
+ pcnsNmcIndex
+ Gauge,
+ pcnsNmcAddr
+ IpAddress,
+ pcnsNmcOutlet
+ Gauge
+ }
+
+pcnsNmcIndex OBJECT-TYPE
+ SYNTAX Gauge
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index of the NMC within PCNS setup."
+ ::= { pcnsNmcEntry 1 }
+
+pcnsNmcAddr OBJECT-TYPE
+ SYNTAX IpAddress
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The IP address of the NMC."
+ ::= { pcnsNmcEntry 2 }
+
+pcnsNmcOutlet OBJECT-TYPE
+ SYNTAX Gauge
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Outlet Group which PCNS is enrolled with on the NMC."
+ ::= { pcnsNmcEntry 3 }
+
+-- the software group
+-- the powerChuteNetworkShutdown group
+-- the pcnsEvents group
+
+
+
+pcnsPowerFailed OBJECT IDENTIFIER ::= { pcnsEvents 1 }
+
+pcnsPowerFailedDesc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsPowerFailed 1 }
+
+pcnsPowerFailedEnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsPowerFailed 2 }
+
+pcnsPowerFailedEnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsPowerFailed 3 }
+
+pcnsPowerFailedCommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsPowerFailed 4 }
+
+pcnsPowerFailedCommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsPowerFailed 5 }
+
+pcnsPowerFailedEnableShutdown OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Perform a graceful shutdown of the server when this event occurs."
+ ::= { pcnsPowerFailed 6 }
+
+pcnsPowerFailedShutdownDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)."
+ ::= { pcnsPowerFailed 7 }
+
+pcnsPowerRestored OBJECT IDENTIFIER ::= { pcnsEvents 2 }
+
+pcnsPowerRestoredDesc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsPowerRestored 1 }
+
+pcnsPowerRestoredEnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsPowerRestored 2 }
+
+pcnsPowerRestoredEnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsPowerRestored 3 }
+
+pcnsPowerRestoredCommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsPowerRestored 4 }
+
+pcnsPowerRestoredCommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsPowerRestored 5 }
+
+
+pcnsOverload OBJECT IDENTIFIER ::= { pcnsEvents 3 }
+
+pcnsOverloadDesc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsOverload 1 }
+
+pcnsOverloadEnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsOverload 2 }
+
+pcnsOverloadEnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsOverload 3 }
+
+pcnsOverloadCommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsOverload 4 }
+
+pcnsOverloadCommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsOverload 5 }
+
+pcnsOverloadEnableShutdown OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Perform a graceful shutdown of the server when this event occurs."
+ ::= { pcnsOverload 6 }
+
+pcnsOverloadShutdownDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)."
+ ::= { pcnsOverload 7 }
+
+pcnsOverloadSolved OBJECT IDENTIFIER ::= { pcnsEvents 4 }
+
+pcnsOverloadSolvedDesc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsOverloadSolved 1 }
+
+pcnsOverloadSolvedEnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsOverloadSolved 2 }
+
+pcnsOverloadSolvedEnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsOverloadSolved 3 }
+
+pcnsOverloadSolvedCommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsOverloadSolved 4 }
+
+pcnsOverloadSolvedCommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsOverloadSolved 5 }
+
+
+pcnsRunTimeExceeded OBJECT IDENTIFIER ::= { pcnsEvents 5 }
+
+pcnsRunTimeExceededDesc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsRunTimeExceeded 1 }
+
+pcnsRunTimeExceededEnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsRunTimeExceeded 2 }
+
+pcnsRunTimeExceededEnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsRunTimeExceeded 3 }
+
+pcnsRunTimeExceededCommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsRunTimeExceeded 4 }
+
+pcnsRunTimeExceededCommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsRunTimeExceeded 5 }
+
+pcnsRunTimeExceededEnableShutdown OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Perform a graceful shutdown of the server when this event occurs."
+ ::= { pcnsRunTimeExceeded 6 }
+
+pcnsRunTimeExceededShutdownDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)."
+ ::= { pcnsRunTimeExceeded 7 }
+
+
+pcnsRunTimeWithinRange OBJECT IDENTIFIER ::= { pcnsEvents 6 }
+
+pcnsRunTimeWithinRangeDesc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsRunTimeWithinRange 1 }
+
+pcnsRunTimeWithinRangeEnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsRunTimeWithinRange 2 }
+
+pcnsRunTimeWithinRangeEnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsRunTimeWithinRange 3 }
+
+pcnsRunTimeWithinRangeCommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsRunTimeWithinRange 4 }
+
+pcnsRunTimeWithinRangeCommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsRunTimeWithinRange 5 }
+
+
+
+pcnsRunTimeBelowThreshold OBJECT IDENTIFIER ::= { pcnsEvents 7 }
+
+pcnsRunTimeBelowThresholdDesc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsRunTimeBelowThreshold 1 }
+
+pcnspcnsRunTimeBelowThresholdEnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsRunTimeBelowThreshold 2 }
+
+pcnsRunTimeBelowThresholdEnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsRunTimeBelowThreshold 3 }
+
+pcnsRunTimeBelowThresholdCommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsRunTimeBelowThreshold 4 }
+
+
+pcnsRunTimeBelowThresholdEnableShutdown OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Perform a graceful shutdown of the server when this event occurs."
+ ::= { pcnsRunTimeBelowThreshold 6 }
+
+
+pcnsRunTimeBelowThresholdCommandFileThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "If the Runtime Remaining falls below this (seconds), the command file will run."
+ ::= { pcnsRunTimeBelowThreshold 8 }
+
+pcnsRunTimeBelowThresholdShutdownThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "If the Runtime Remaining falls below this (seconds), the shutdown will begin."
+ ::= { pcnsRunTimeBelowThreshold 9 }
+
+
+
+
+pcnsRunTimeAboveThreshold OBJECT IDENTIFIER ::= { pcnsEvents 8 }
+
+pcnsRunTimeAboveThresholdDesc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsRunTimeAboveThreshold 1 }
+
+pcnsRunTimeAboveThresholdEnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsRunTimeAboveThreshold 2 }
+
+pcnsRunTimeAboveThresholdEnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsRunTimeAboveThreshold 3 }
+
+pcnsRunTimeAboveThresholdCommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsRunTimeAboveThreshold 4 }
+
+pcnsRunTimeAboveThresholdCommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsRunTimeAboveThreshold 5 }
+
+
+
+
+pcnsBatteryDischarged OBJECT IDENTIFIER ::= { pcnsEvents 10 }
+
+pcnsBatteryDischargedDesc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsBatteryDischarged 1 }
+
+pcnsBatteryDischargedEnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsBatteryDischarged 2 }
+
+pcnsBatteryDischargedEnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsBatteryDischarged 3 }
+
+pcnsBatteryDischargedCommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsBatteryDischarged 4 }
+
+pcnsBatteryDischargedCommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsBatteryDischarged 5 }
+
+pcnsBatteryDischargedEnableShutdown OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Perform a graceful shutdown of the server when this event occurs."
+ ::= { pcnsBatteryDischarged 6 }
+
+pcnsBatteryDischargedShutdownDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)."
+ ::= { pcnsBatteryDischarged 7 }
+
+
+pcnsBatteryChargeInRange OBJECT IDENTIFIER ::= { pcnsEvents 11 }
+
+pcnsBatteryChargeInRangeDesc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsBatteryChargeInRange 1 }
+
+pcnsBatteryChargeInRangeEnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsBatteryChargeInRange 2 }
+
+pcnsBatteryChargeInRangeEnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsBatteryChargeInRange 3 }
+
+pcnsBatteryChargeInRangeCommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsBatteryChargeInRange 4 }
+
+pcnsBatteryChargeInRangeCommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsBatteryChargeInRange 5 }
+
+
+
+pcnsFaultBypassEnabled OBJECT IDENTIFIER ::= { pcnsEvents 12 }
+
+pcnsFaultBypassEnabledDesc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsFaultBypassEnabled 1 }
+
+pcnsFaultBypassEnabledEnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsFaultBypassEnabled 2 }
+
+pcnsFaultBypassEnabledEnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsFaultBypassEnabled 3 }
+
+pcnsFaultBypassEnabledCommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsFaultBypassEnabled 4 }
+
+pcnsFaultBypassEnabledCommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsFaultBypassEnabled 5 }
+
+pcnsFaultBypassEnabledEnableShutdown OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Perform a graceful shutdown of the server when this event occurs."
+ ::= { pcnsFaultBypassEnabled 6 }
+
+pcnsFaultBypassEnabledShutdownDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)."
+ ::= { pcnsFaultBypassEnabled 7 }
+
+
+pcnsBypassEnabled OBJECT IDENTIFIER ::= { pcnsEvents 13 }
+
+pcnsBypassEnabledDesc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsBypassEnabled 1 }
+
+pcnsBypassEnabledEnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsBypassEnabled 2 }
+
+pcnsBypassEnabledEnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsBypassEnabled 3 }
+
+pcnsBypassEnabledCommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsBypassEnabled 4 }
+
+pcnsBypassEnabledCommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsBypassEnabled 5 }
+
+pcnsBypassEnabledEnableShutdown OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Perform a graceful shutdown of the server when this event occurs."
+ ::= { pcnsBypassEnabled 6 }
+
+pcnsBypassEnabledShutdownDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)."
+ ::= { pcnsBypassEnabled 7 }
+
+
+pcnsBypassManualEnabled OBJECT IDENTIFIER ::= { pcnsEvents 14 }
+
+pcnsBypassManualEnabledDesc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsBypassManualEnabled 1 }
+
+pcnsBypassManualEnabledEnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsBypassManualEnabled 2 }
+
+pcnsBypassManualEnabledEnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsBypassManualEnabled 3 }
+
+pcnsBypassManualEnabledCommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsBypassManualEnabled 4 }
+
+pcnsBypassManualEnabledCommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsBypassManualEnabled 5 }
+
+pcnsBypassManualEnabledEnableShutdown OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Perform a graceful shutdown of the server when this event occurs."
+ ::= { pcnsBypassManualEnabled 6 }
+
+pcnsBypassManualEnabledShutdownDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)."
+ ::= { pcnsBypassManualEnabled 7 }
+
+pcnsBypassDisabled OBJECT IDENTIFIER ::= { pcnsEvents 15 }
+
+pcnsBypassDisabledDesc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsBypassDisabled 1 }
+
+pcnsBypassDisabledEnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsBypassDisabled 2 }
+
+pcnsBypassDisabledEnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsBypassDisabled 3 }
+
+pcnsBypassDisabledCommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsBypassDisabled 4 }
+
+pcnsBypassDisabledCommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsBypassDisabled 5 }
+
+
+pcnsBypassContactorFailed OBJECT IDENTIFIER ::= { pcnsEvents 16 }
+
+pcnsBypassContactorFailedDesc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsBypassContactorFailed 1 }
+
+pcnsBypassContactorFailedEnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsBypassContactorFailed 2 }
+
+pcnsBypassContactorFailedEnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsBypassContactorFailed 3 }
+
+pcnsBypassContactorFailedCommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsBypassContactorFailed 4 }
+
+pcnsBypassContactorFailedCommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsBypassContactorFailed 5 }
+
+pcnsBypassContactorFailedEnableShutdown OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Perform a graceful shutdown of the server when this event occurs."
+ ::= { pcnsBypassContactorFailed 6 }
+
+pcnsBypassContactorFailedShutdownDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)."
+ ::= { pcnsBypassContactorFailed 7 }
+
+pcnsBypassContactorOk OBJECT IDENTIFIER ::= { pcnsEvents 17 }
+
+pcnsBypassContactorOkDesc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsBypassContactorOk 1 }
+
+pcnsBypassContactorOkEnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsBypassContactorOk 2 }
+
+pcnsBypassContactorOkEnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsBypassContactorOk 3 }
+
+pcnsBypassContactorOkCommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsBypassContactorOk 4 }
+
+pcnsBypassContactorOkCommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsBypassContactorOk 5 }
+
+
+pcnsCommunicationLostOnBattery OBJECT IDENTIFIER ::= { pcnsEvents 18 }
+
+pcnsCommunicationLostOnBatteryDesc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsCommunicationLostOnBattery 1 }
+
+pcnsCommunicationLostOnBatteryEnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsCommunicationLostOnBattery 2 }
+
+pcnsCommunicationLostOnBatteryEnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsCommunicationLostOnBattery 3 }
+
+pcnsCommunicationLostOnBatteryCommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsCommunicationLostOnBattery 4 }
+
+pcnsCommunicationLostOnBatteryCommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsCommunicationLostOnBattery 5 }
+
+pcnsCommunicationLostOnBatteryEnableShutdown OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Perform a graceful shutdown of the server when this event occurs."
+ ::= { pcnsCommunicationLostOnBattery 6 }
+
+pcnsCommunicationLostOnBatteryShutdownDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)."
+ ::= { pcnsCommunicationLostOnBattery 7 }
+
+pcnsCommunicationLost OBJECT IDENTIFIER ::= { pcnsEvents 19 }
+
+pcnsCommunicationLostDesc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsCommunicationLost 1 }
+
+pcnsCommunicationLostEnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsCommunicationLost 2 }
+
+pcnsCommunicationLostEnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsCommunicationLost 3 }
+
+pcnsCommunicationLostCommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsCommunicationLost 4 }
+
+pcnsCommunicationLostCommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsCommunicationLost 5 }
+
+pcnsCommunicationLostEnableShutdown OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Perform a graceful shutdown of the server when this event occurs."
+ ::= { pcnsCommunicationLost 6 }
+
+pcnsCommunicationLostShutdownDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)."
+ ::= { pcnsCommunicationLost 7 }
+
+pcnsNetCommunicationLost OBJECT IDENTIFIER ::= { pcnsEvents 20 }
+
+pcnsNetCommunicationLostDesc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsNetCommunicationLost 1 }
+
+pcnsNetCommunicationLostEnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsNetCommunicationLost 2 }
+
+pcnsNetCommunicationLostEnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsNetCommunicationLost 3 }
+
+pcnsNetCommunicationLostCommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsNetCommunicationLost 4 }
+
+pcnsNetCommunicationLostCommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsNetCommunicationLost 5 }
+
+pcnsNetCommunicationLostEnableShutdown OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Perform a graceful shutdown of the server when this event occurs."
+ ::= { pcnsNetCommunicationLost 6 }
+
+pcnsNetCommunicationLostShutdownDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)."
+ ::= { pcnsNetCommunicationLost 7 }
+
+pcnsCommunicationEstablished OBJECT IDENTIFIER ::= { pcnsEvents 21 }
+
+pcnsCommunicationEstablishedDesc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsCommunicationEstablished 1 }
+
+pcnsCommunicationEstablishedEnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsCommunicationEstablished 2 }
+
+pcnsCommunicationEstablishedEnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsCommunicationEstablished 3 }
+
+pcnsCommunicationEstablishedCommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsCommunicationEstablished 4 }
+
+pcnsCommunicationEstablishedCommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsCommunicationEstablished 5 }
+
+
+pcnsMinRedundancyLost OBJECT IDENTIFIER ::= { pcnsEvents 22 }
+
+pcnsMinRedundancyLostDesc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsMinRedundancyLost 1 }
+
+pcnsMinRedundancyLostEnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsMinRedundancyLost 2 }
+
+pcnsMinRedundancyLostEnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsMinRedundancyLost 3 }
+
+pcnsMinRedundancyLostCommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsMinRedundancyLost 4 }
+
+pcnsMinRedundancyLostCommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsMinRedundancyLost 5 }
+
+pcnsMinRedundancyLostEnableShutdown OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Perform a graceful shutdown of the server when this event occurs."
+ ::= { pcnsMinRedundancyLost 6 }
+
+pcnsMinRedundancyLostShutdownDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)."
+ ::= { pcnsMinRedundancyLost 7 }
+
+pcnsMinRedundancyRegained OBJECT IDENTIFIER ::= { pcnsEvents 23 }
+
+pcnsMinRedundancyRegainedDesc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsMinRedundancyRegained 1 }
+
+pcnsMinRedundancyRegainedEnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsMinRedundancyRegained 2 }
+
+pcnsMinRedundancyRegainedEnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsMinRedundancyRegained 3 }
+
+pcnsMinRedundancyRegainedCommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsMinRedundancyRegained 4 }
+
+pcnsMinRedundancyRegainedCommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsMinRedundancyRegained 5 }
+
+
+pcnsParallelRedundancyLost OBJECT IDENTIFIER ::= { pcnsEvents 24 }
+
+pcnsParallelRedundancyLostDesc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsParallelRedundancyLost 1 }
+
+pcnsParallelRedundancyLostEnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsParallelRedundancyLost 2 }
+
+pcnsParallelRedundancyLostEnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsParallelRedundancyLost 3 }
+
+pcnsParallelRedundancyLostCommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsParallelRedundancyLost 4 }
+
+pcnsParallelRedundancyLostCommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsParallelRedundancyLost 5 }
+
+pcnsParallelRedundancyLostEnableShutdown OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Perform a graceful shutdown of the server when this event occurs."
+ ::= { pcnsParallelRedundancyLost 6 }
+
+pcnsParallelRedundancyLostShutdownDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)."
+ ::= { pcnsParallelRedundancyLost 7 }
+
+pcnsParallelRedundancyRegained OBJECT IDENTIFIER ::= { pcnsEvents 25 }
+
+pcnsParallelRedundancyRegainedDesc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsParallelRedundancyRegained 1 }
+
+pcnsParallelRedundancyRegainedEnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsParallelRedundancyRegained 2 }
+
+pcnsParallelRedundancyRegainedEnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsParallelRedundancyRegained 3 }
+
+pcnsParallelRedundancyRegainedCommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsParallelRedundancyRegained 4 }
+
+pcnsParallelRedundancyRegainedCommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsParallelRedundancyRegained 5 }
+
+pcnsMaxInternalTempExceeded OBJECT IDENTIFIER ::= { pcnsEvents 26 }
+
+pcnsMaxInternalTempExceededDesc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsMaxInternalTempExceeded 1 }
+
+pcnsMaxInternalTempExceededEnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsMaxInternalTempExceeded 2 }
+
+pcnsMaxInternalTempExceededEnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsMaxInternalTempExceeded 3 }
+
+pcnsMaxInternalTempExceededCommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsMaxInternalTempExceeded 4 }
+
+pcnsMaxInternalTempExceededCommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsMaxInternalTempExceeded 5 }
+
+pcnsMaxInternalTempExceededEnableShutdown OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Perform a graceful shutdown of the server when this event occurs."
+ ::= { pcnsMaxInternalTempExceeded 6 }
+
+pcnsMaxInternalTempExceededShutdownDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)."
+ ::= { pcnsMaxInternalTempExceeded 7 }
+
+pcnsMaxInternalTempInRange OBJECT IDENTIFIER ::= { pcnsEvents 27 }
+
+pcnsMaxInternalTempInRangeDesc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsMaxInternalTempInRange 1 }
+
+pcnsMaxInternalTempInRangeEnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsMaxInternalTempInRange 2 }
+
+pcnsMaxInternalTempInRangeEnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsMaxInternalTempInRange 3 }
+
+pcnsMaxInternalTempInRangeCommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsMaxInternalTempInRange 4 }
+
+pcnsMaxInternalTempInRangeCommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsMaxInternalTempInRange 5 }
+
+
+pcnsMinLoadCapabilityLost OBJECT IDENTIFIER ::= { pcnsEvents 28 }
+
+pcnsMinLoadCapabilityLostDesc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsMinLoadCapabilityLost 1 }
+
+pcnsMinLoadCapabilityLostEnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsMinLoadCapabilityLost 2 }
+
+pcnsMinLoadCapabilityLostEnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsMinLoadCapabilityLost 3 }
+
+pcnsMinLoadCapabilityLostCommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsMinLoadCapabilityLost 4 }
+
+pcnsMinLoadCapabilityLostCommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsMinLoadCapabilityLost 5 }
+
+pcnsMinLoadCapabilityLostEnableShutdown OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Perform a graceful shutdown of the server when this event occurs."
+ ::= { pcnsMinLoadCapabilityLost 6 }
+
+pcnsMinLoadCapabilityLostShutdownDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)."
+ ::= { pcnsMinLoadCapabilityLost 7 }
+
+pcnsMinLoadCapabilityRegained OBJECT IDENTIFIER ::= { pcnsEvents 29 }
+
+pcnsMinLoadCapabilityRegainedDesc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsMinLoadCapabilityRegained 1 }
+
+pcnsMinLoadCapabilityRegainedEnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsMinLoadCapabilityRegained 2 }
+
+pcnsMinLoadCapabilityRegainedEnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsMinLoadCapabilityRegained 3 }
+
+pcnsMinLoadCapabilityRegainedCommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsMinLoadCapabilityRegained 4 }
+
+pcnsMinLoadCapabilityRegainedCommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsMinLoadCapabilityRegained 5 }
+
+
+
+-- PCNS Environmental Monitoring Card Events
+pcnsEnvironmentCommunicationEstablished OBJECT IDENTIFIER ::= { pcnsEvents 30 }
+
+pcnsEnvironmentCommunicationEstablishedDesc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsEnvironmentCommunicationEstablished 1 }
+
+pcnsEnvironmentCommunicationEstablishedEnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsEnvironmentCommunicationEstablished 2 }
+
+pcnsEnvironmentCommunicationEstablishedEnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsEnvironmentCommunicationEstablished 3 }
+
+pcnsEnvironmentCommunicationEstablishedCommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsEnvironmentCommunicationEstablished 4 }
+
+pcnsEnvironmentCommunicationEstablishedCommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsEnvironmentCommunicationEstablished 5 }
+
+
+
+pcnsEnvironmentCommunicationLost OBJECT IDENTIFIER ::= { pcnsEvents 31 }
+
+pcnsEnvironmentCommunicationLostDesc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsEnvironmentCommunicationLost 1 }
+
+pcnsEnvironmentCommunicationLostEnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsEnvironmentCommunicationLost 2 }
+
+pcnsEnvironmentCommunicationLostEnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsEnvironmentCommunicationLost 3 }
+
+pcnsEnvironmentCommunicationLostCommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsEnvironmentCommunicationLost 4 }
+
+pcnsEnvironmentCommunicationLostCommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsEnvironmentCommunicationLost 5 }
+
+pcnsTempInRangeProbe1 OBJECT IDENTIFIER ::= { pcnsEvents 32 }
+
+pcnsTempInRangeProbe1Desc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsTempInRangeProbe1 1 }
+
+pcnsTempInRangeProbe1EnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsTempInRangeProbe1 2 }
+
+pcnsTempInRangeProbe1EnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsTempInRangeProbe1 3 }
+
+pcnsTempInRangeProbe1CommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsTempInRangeProbe1 4 }
+
+pcnsTempInRangeProbe1CommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsTempInRangeProbe1 5 }
+
+
+
+pcnsTempOutOfRangeProbe1 OBJECT IDENTIFIER ::= { pcnsEvents 33 }
+
+pcnsTempOutOfRangeProbe1Desc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsTempOutOfRangeProbe1 1 }
+
+pcnsTempOutOfRangeProbe1EnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsTempOutOfRangeProbe1 2 }
+
+pcnsTempOutOfRangeProbe1EnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsTempOutOfRangeProbe1 3 }
+
+pcnsTempOutOfRangeProbe1CommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsTempOutOfRangeProbe1 4 }
+
+pcnsTempOutOfRangeProbe1CommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsTempOutOfRangeProbe1 5 }
+
+pcnsTempOutOfRangeProbe1EnableShutdown OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Perform a graceful shutdown of the server when this event occurs."
+ ::= { pcnsTempOutOfRangeProbe1 6 }
+
+pcnsTempOutOfRangeProbe1ShutdownDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)."
+ ::= { pcnsTempOutOfRangeProbe1 7 }
+
+
+pcnsHumidityInRangeProbe1 OBJECT IDENTIFIER ::= { pcnsEvents 34 }
+pcnsHumidityInRangeProbe1Desc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsHumidityInRangeProbe1 1 }
+
+pcnsHumidityInRangeProbe1EnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsHumidityInRangeProbe1 2 }
+
+pcnsHumidityInRangeProbe1EnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsHumidityInRangeProbe1 3 }
+
+pcnsHumidityInRangeProbe1CommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsHumidityInRangeProbe1 4 }
+
+pcnsHumidityInRangeProbe1CommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsHumidityInRangeProbe1 5 }
+
+
+
+pcnsHumidityOutOfRangeProbe1 OBJECT IDENTIFIER ::= { pcnsEvents 35 }
+
+pcnsHumidityOutOfRangeProbe1Desc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsHumidityOutOfRangeProbe1 1 }
+
+pcnsHumidityOutOfRangeProbe1EnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsHumidityOutOfRangeProbe1 2 }
+
+pcnsHumidityOutOfRangeProbe1EnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsHumidityOutOfRangeProbe1 3 }
+
+pcnsHumidityOutOfRangeProbe1CommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsHumidityOutOfRangeProbe1 4 }
+
+pcnsHumidityOutOfRangeProbe1CommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsHumidityOutOfRangeProbe1 5 }
+
+pcnsHumidityOutOfRangeProbe1EnableShutdown OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Perform a graceful shutdown of the server when this event occurs."
+ ::= { pcnsHumidityOutOfRangeProbe1 6 }
+
+pcnsHumidityOutOfRangeProbe1ShutdownDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)."
+ ::= { pcnsHumidityOutOfRangeProbe1 7 }
+
+pcnsTempInRangeProbe2 OBJECT IDENTIFIER ::= { pcnsEvents 36 }
+
+pcnsTempInRangeProbe2Desc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsTempInRangeProbe2 1 }
+
+pcnsTempInRangeProbe2EnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsTempInRangeProbe2 2 }
+
+pcnsTempInRangeProbe2EnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsTempInRangeProbe2 3 }
+
+pcnsTempInRangeProbe2CommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsTempInRangeProbe2 4 }
+
+pcnsTempInRangeProbe2CommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsTempInRangeProbe2 5 }
+
+
+
+pcnsTempOutOfRangeProbe2 OBJECT IDENTIFIER ::= { pcnsEvents 37 }
+
+pcnsTempOutOfRangeProbe2Desc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsTempOutOfRangeProbe2 1 }
+
+pcnsTempOutOfRangeProbe2EnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsTempOutOfRangeProbe2 2 }
+
+pcnsTempOutOfRangeProbe2EnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsTempOutOfRangeProbe2 3 }
+
+pcnsTempOutOfRangeProbe2CommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsTempOutOfRangeProbe2 4 }
+
+pcnsTempOutOfRangeProbe2CommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsTempOutOfRangeProbe2 5 }
+
+pcnsTempOutOfRangeProbe2EnableShutdown OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Perform a graceful shutdown of the server when this event occurs."
+ ::= { pcnsTempOutOfRangeProbe2 6 }
+
+pcnsTempOutOfRangeProbe2ShutdownDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)."
+ ::= { pcnsTempOutOfRangeProbe2 7 }
+
+
+pcnsHumidityInRangeProbe2 OBJECT IDENTIFIER ::= { pcnsEvents 38 }
+
+pcnsHumidityInRangeProbe2Desc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsHumidityInRangeProbe2 1 }
+
+pcnsHumidityInRangeProbe2EnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsHumidityInRangeProbe2 2 }
+
+pcnsHumidityInRangeProbe2EnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsHumidityInRangeProbe2 3 }
+
+pcnsHumidityInRangeProbe2CommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsHumidityInRangeProbe2 4 }
+
+pcnsHumidityInRangeProbe2CommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsHumidityInRangeProbe2 5 }
+
+
+
+pcnsHumidityOutOfRangeProbe2 OBJECT IDENTIFIER ::= { pcnsEvents 39 }
+
+pcnsHumidityOutOfRangeProbe2Desc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsHumidityOutOfRangeProbe2 1 }
+
+pcnsHumidityOutOfRangeProbe2EnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsHumidityOutOfRangeProbe2 2 }
+
+pcnsHumidityOutOfRangeProbe2EnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsHumidityOutOfRangeProbe2 3 }
+
+pcnsHumidityOutOfRangeProbe2CommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsHumidityOutOfRangeProbe2 4 }
+
+pcnsHumidityOutOfRangeProbe2CommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsHumidityOutOfRangeProbe2 5 }
+
+pcnsHumidityOutOfRangeProbe2EnableShutdown OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Perform a graceful shutdown of the server when this event occurs."
+ ::= { pcnsHumidityOutOfRangeProbe2 6 }
+
+pcnsHumidityOutOfRangeProbe2ShutdownDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)."
+ ::= { pcnsHumidityOutOfRangeProbe2 7 }
+
+pcnsContactFault1 OBJECT IDENTIFIER ::= { pcnsEvents 40 }
+
+pcnsContactFault1Desc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsContactFault1 1 }
+
+pcnsContactFault1EnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsContactFault1 2 }
+
+pcnsContactFault1EnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsContactFault1 3 }
+
+pcnsContactFault1CommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsContactFault1 4 }
+
+pcnsContactFault1CommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsContactFault1 5 }
+
+pcnsContactFault1EnableShutdown OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Perform a graceful shutdown of the server when this event occurs."
+ ::= { pcnsContactFault1 6 }
+
+pcnsContactFault1ShutdownDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)."
+ ::= { pcnsContactFault1 7 }
+
+
+pcnsContactFault2 OBJECT IDENTIFIER ::= { pcnsEvents 41 }
+
+pcnsContactFault2Desc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsContactFault2 1 }
+
+pcnsContactFault2EnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsContactFault2 2 }
+
+pcnsContactFault2EnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsContactFault2 3 }
+
+pcnsContactFault2CommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsContactFault2 4 }
+
+pcnsContactFault2CommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsContactFault2 5 }
+
+pcnsContactFault2EnableShutdown OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Perform a graceful shutdown of the server when this event occurs."
+ ::= { pcnsContactFault2 6 }
+
+pcnsContactFault2ShutdownDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)."
+ ::= { pcnsContactFault2 7 }
+
+pcnsContactFault3 OBJECT IDENTIFIER ::= { pcnsEvents 42 }
+
+pcnsContactFault3Desc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsContactFault3 1 }
+
+pcnsContactFault3EnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsContactFault3 2 }
+
+pcnsContactFault3EnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsContactFault3 3 }
+
+pcnsContactFault3CommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsContactFault3 4 }
+
+pcnsContactFault3CommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsContactFault3 5 }
+
+pcnsContactFault3EnableShutdown OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Perform a graceful shutdown of the server when this event occurs."
+ ::= { pcnsContactFault3 6 }
+
+pcnsContactFault3ShutdownDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)."
+ ::= { pcnsContactFault3 7 }
+
+pcnsContactFault4 OBJECT IDENTIFIER ::= { pcnsEvents 43 }
+
+pcnsContactFault4Desc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsContactFault4 1 }
+
+pcnsContactFault4EnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsContactFault4 2 }
+
+pcnsContactFault4EnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsContactFault4 3 }
+
+pcnsContactFault4CommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsContactFault4 4 }
+
+pcnsContactFault4CommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsContactFault4 5 }
+
+pcnsContactFault4EnableShutdown OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Perform a graceful shutdown of the server when this event occurs."
+ ::= { pcnsContactFault4 6 }
+
+pcnsContactFault4ShutdownDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)."
+ ::= { pcnsContactFault4 7 }
+
+pcnsContactNormal1 OBJECT IDENTIFIER ::= { pcnsEvents 44 }
+
+pcnsContactNormal1Desc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsContactNormal1 1 }
+
+pcnsContactNormal1EnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsContactNormal1 2 }
+
+pcnsContactNormal1EnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsContactNormal1 3 }
+
+pcnsContactNormal1CommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsContactNormal1 4 }
+
+pcnsContactNormal1CommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsContactNormal1 5 }
+
+
+pcnsContactNormal2 OBJECT IDENTIFIER ::= { pcnsEvents 45 }
+
+pcnsContactNormal2Desc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsContactNormal2 1 }
+
+pcnsContactNormal2EnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsContactNormal2 2 }
+
+pcnsContactNormal2EnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsContactNormal2 3 }
+
+pcnsContactNormal2CommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsContactNormal2 4 }
+
+pcnsContactNormal2CommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsContactNormal2 5 }
+
+
+pcnsContactNormal3 OBJECT IDENTIFIER ::= { pcnsEvents 46 }
+
+pcnsContactNormal3Desc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsContactNormal3 1 }
+
+pcnsContactNormal3EnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsContactNormal3 2 }
+
+pcnsContactNormal3EnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsContactNormal3 3 }
+
+pcnsContactNormal3CommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsContactNormal3 4 }
+
+pcnsContactNormal3CommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsContactNormal3 5 }
+
+
+
+pcnsContactNormal4 OBJECT IDENTIFIER ::= { pcnsEvents 47 }
+
+pcnsContactNormal4Desc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Description of the event."
+ ::= { pcnsContactNormal4 1 }
+
+pcnsContactNormal4EnableLogging OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Log occurrences of this event in PCNS log."
+ ::= { pcnsContactNormal4 2 }
+
+pcnsContactNormal4EnableCommandFile OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Execute a command file when this event occurs."
+ ::= { pcnsContactNormal4 3 }
+
+pcnsContactNormal4CommandFilePath OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Path of command file to execute when this event occurs."
+ ::= { pcnsContactNormal4 4 }
+
+pcnsContactNormal4CommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long to wait after event occurs before executing command file (seconds)."
+ ::= { pcnsContactNormal4 5 }
+
+
+
+
+
+
+-- the software group
+-- the powerChuteNetworkShutdown group
+-- the pcnsShutdown group
+
+pcnsShutdownCommandFileEnabled OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Run a shutdown command file before performing graceful shutdown."
+ ::= { pcnsShutdown 1 }
+
+pcnsShutdownCommandFileDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long in seconds to wait before running a shutdown command file before graceful shutdown."
+ ::= { pcnsShutdown 2 }
+
+pcnsShutdownCommandFile OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Full name of the shutdown command file to run before graceful shutdown."
+ ::= { pcnsShutdown 3 }
+
+pcnsShutdownCommandFileDuration OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long in seconds shutdown command file takes to run."
+ ::= { pcnsShutdown 4 }
+
+pcnsTurnOffUps OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Turn off the UPS when performing a graceful shutdown."
+ ::= { pcnsShutdown 5 }
+
+pcnsTurnOffSOG OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Turn off the Outlet Group on the UPS when performing a graceful shutdown."
+ ::= { pcnsShutdown 6 }
+
+pcnsRuntimeRemainingThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "This defines a threshold for runtime remaining. When the
+ UPS is running on battery power and the runtime remaining
+ on the UPS drops below the threshold, PowerChute will trigger
+ a shutdown sequence."
+ ::= { pcnsShutdown 7 }
+
+pcnsRuntimeRemainingCmdFileThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "This defines a threshold for runtime remaining. When
+ runtime remaining drops below this threshold, PowerChute
+ will execute the command file."
+ ::= { pcnsShutdown 8 }
+
+pcnsAdvancedShutdownTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF PCNSAdvancedShutdownEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The Network Management Cards in the UPS's which PCNS is monitoring to provide safe shutdown."
+ ::= { pcnsShutdown 9 }
+
+pcnsAdvancedShutdownEntry OBJECT-TYPE
+ SYNTAX PCNSAdvancedShutdownEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Details of the NMC."
+ INDEX { pcnsAdvancedGroupNo }
+ ::= { pcnsAdvancedShutdownTable 1 }
+
+PCNSAdvancedShutdownEntry ::=
+ SEQUENCE {
+ pcnsAdvancedGroupNo Gauge,
+ pcnsAdvancedGroupName DisplayString,
+ pcnsAdvancedGroupNMC DisplayString,
+ pcnsAdvancedShutdownUPSRequiredForLoad INTEGER,
+ pcnsAdvancedShutdownCommandFileEnabled INTEGER,
+ pcnsAdvancedShutdownCommandFile DisplayString,
+ pcnsAdvancedShutdownCommandFileDuration INTEGER,
+ pcnsAdvancedShutdownPowerchuteServer INTEGER,
+ pcnsAdvancedShutdownOnLostRedundancy INTEGER,
+ pcnsAdvancedTurnOffUps INTEGER,
+ pcnsAdvancedTurnOffSOG INTEGER
+ }
+
+pcnsAdvancedGroupNo OBJECT-TYPE
+ SYNTAX Gauge
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index of the Advanced Shutdown Group."
+ ::= { pcnsAdvancedShutdownEntry 1 }
+
+pcnsAdvancedGroupName OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Name of the Advanced Shutdown Group."
+ ::= { pcnsAdvancedShutdownEntry 2 }
+
+pcnsAdvancedGroupNMC OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "List of NMCs in the Advanced Shutdown Group."
+ ::= { pcnsAdvancedShutdownEntry 3 }
+
+pcnsAdvancedShutdownUPSRequiredForLoad OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Number of UPS's required to power load."
+ ::= { pcnsAdvancedShutdownEntry 4 }
+
+pcnsAdvancedShutdownCommandFileEnabled OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Run a shutdown command file before performing graceful shutdown."
+ ::= { pcnsAdvancedShutdownEntry 5 }
+
+pcnsAdvancedShutdownCommandFile OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Full name of the shutdown command file to run before graceful shutdown."
+ ::= { pcnsAdvancedShutdownEntry 6 }
+
+pcnsAdvancedShutdownCommandFileDuration OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long in seconds shutdown command file takes to run."
+ ::= { pcnsAdvancedShutdownEntry 7 }
+
+pcnsAdvancedShutdownPowerchuteServer OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Shut down PowerChute Server."
+ ::= { pcnsAdvancedShutdownEntry 8 }
+
+pcnsAdvancedShutdownOnLostRedundancy OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Shut down if Redundancy lost."
+ ::= { pcnsAdvancedShutdownEntry 9 }
+
+pcnsAdvancedTurnOffUps OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Turn off the UPS when performing a graceful shutdown."
+ ::= { pcnsAdvancedShutdownEntry 10 }
+
+pcnsAdvancedTurnOffSOG OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Turn off the Outlet Group on the UPS when performing a graceful shutdown."
+ ::= { pcnsAdvancedShutdownEntry 11 }
+
+
+-- the software group
+-- the powerChuteNetworkShutdown group
+-- the pcnsAlarms group
+
+pcnsCriticalFlag OBJECT-TYPE
+ SYNTAX INTEGER {
+ active (1),
+ clear (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "PowerChute Network Shutdown has begun a safe shutdown of the host."
+ ::= { pcnsAlarms 1 }
+
+pcnsCriticalCause OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..255))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The reason PowerChute Network Shutdown has begun a safe shutdown."
+ ::= { pcnsAlarms 2 }
+
+pcnsNetComsLostFlag OBJECT-TYPE
+ SYNTAX INTEGER {
+ active (1),
+ clear (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "PowerChute cannot communicate with NMC."
+ ::= { pcnsAlarms 3 }
+
+pcnsNMCComsLostFlag OBJECT-TYPE
+ SYNTAX INTEGER {
+ active (1),
+ clear (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "NMC cannot communicate with UPS."
+ ::= { pcnsAlarms 4 }
+
+pcnsUpdateAvailableFlag OBJECT-TYPE
+ SYNTAX INTEGER {
+ active (1),
+ clear (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "PowerChute has detected that a newer version is available."
+ ::= { pcnsAlarms 5 }
+
+pcnsUpdateDesc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..255))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Details of the newer version of PowerChute."
+ ::= { pcnsAlarms 6 }
+
+-- the software group
+-- the powerChuteBusinessEdition group
+-- the pcbeIdent group
+
+pcbeHostname OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The hostname of the PCBE instance."
+ ::= { pcbeIdent 1 }
+
+pcbeVersion OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The version of PCBE installed. x.x.x"
+ ::= { pcbeIdent 2 }
+
+pcbeOS OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The version of OS PCBE is installed on."
+ ::= { pcbeIdent 3 }
+
+pcbeJavaVersion OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The version of Java PCBE is running on."
+ ::= { pcbeIdent 4 }
+
+pcbeUIProtocol OBJECT-TYPE
+ SYNTAX INTEGER {
+ http(1),
+ https(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Web Protocol used to connect to the PCBE UI."
+ ::= { pcbeIdent 5 }
+
+pcbeHttpPort OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Port used for PCBE http UI."
+ ::= { pcbeIdent 6 }
+
+pcbeHttpsPort OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Port used for PCBE https UI."
+ ::= { pcbeIdent 7 }
+
+
+
+-- the software group
+-- the powerChuteBusinessEdition group
+-- the pcbeAlarms group
+
+pcbeCriticalFlag OBJECT-TYPE
+ SYNTAX INTEGER {
+ active (1),
+ clear (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "PowerChute Business Edition has begun a safe shutdown of the host."
+ ::= { pcbeAlarms 1 }
+
+pcbeCriticalCause OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..255))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The reason PowerChute Business Edition has begun a safe shutdown."
+ ::= { pcbeAlarms 2 }
+
+pcbeComsLostFlag OBJECT-TYPE
+ SYNTAX INTEGER {
+ active (1),
+ clear (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "If active (1), PowerChute cannot communicate with UPS"
+ ::= { pcbeAlarms 3 }
+
+-- pcbeAlarms 4 is deliberately skipped to make this consistent with PCNS
+
+pcbeUpdateAvailableFlag OBJECT-TYPE
+ SYNTAX INTEGER {
+ active (1),
+ clear (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "PowerChute has detected that a newer version is available."
+ ::= { pcbeAlarms 5 }
+
+pcbeUpdateDesc OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..255))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Details of the newer version of PowerChute."
+ ::= { pcbeAlarms 6 }
+
+-- the ups group
+-- the upsIdent group
+-- the upsBasicIdent
+
+upsBasicIdentModel OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The UPS model name (e.g. 'APC Smart-UPS 600')."
+ ::= { upsBasicIdent 1 }
+
+upsBasicIdentName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "An 8 byte ID string identifying the UPS. This object
+ can be set by the administrator. For GVS, GPX and GVL products, this string can be up to 32 bytes."
+ ::= { upsBasicIdent 2 }
+
+upsBasicIdentFamilyName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The UPS model family name for the product."
+ ::= { upsBasicIdent 3 }
+
+upsBasicIdentModelType OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The detailed model information of the system."
+ ::= { upsBasicIdent 4 }
+
+-- the upsAdvIdent group
+
+upsAdvIdentFirmwareRevision OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The firmware revision of the UPS system's microprocessor."
+ ::= { upsAdvIdent 1 }
+
+upsAdvIdentDateOfManufacture OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The date when the UPS was manufactured in mm/dd/yy (or yyyy) format."
+ ::= { upsAdvIdent 2 }
+
+upsAdvIdentSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An 8-character string (12-character in case of
+ 3 phase UPS) identifying the serial number of
+ the UPS internal microprocessor. This number is set at
+ the factory. NOTE: This number does NOT correspond to
+ the serial number on the rear of the UPS."
+ ::= { upsAdvIdent 3 }
+
+upsAdvIdentFirmwareRevision2 OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The firmware revision of a UPS system co-microprocessor."
+ ::= { upsAdvIdent 4 }
+
+upsAdvIdentSkuNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The SKU number of a UPS system."
+ ::= { upsAdvIdent 5 }
+
+upsAdvIdentHardwareRevision OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The hardware revision of a UPS system."
+ ::= { upsAdvIdent 6 }
+
+upsAdvIdentUpsPhaseConfigType OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(1),
+ threePhaseInOut(2),
+ onePhaseInOut(3),
+ threePhaseInOneOut(4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The type definition, based on phase configuration.
+ 1 - Unknown
+ 2 - 3 phase in/out
+ 3 - 1 phase in/out
+ 4 - 3 phase in/1 phase out"
+ ::= { upsAdvIdent 7 }
+
+upsAdvEnergyStorageType OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(1),
+ vrlaOrWetCells(2),
+ niCdBatteries(3),
+ liIonBatteries(4),
+ noEnergyStorage(5),
+ flywheel(6),
+ ultracaps(7)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The energy storage type connected to the UPS. It states battery type and battery chemistry.
+ 1 - Unknown
+ 2 - VRLA or wet cells
+ 3 - NiCd batteries
+ 4 - Lithium-ion batteries
+ 5 - No energy storage
+ 6 - Flywheel
+ 7 - Ultracaps"
+ ::= { upsAdvIdent 8 }
+
+-- the upsBattery group
+-- the upsBasicBattery group
+
+upsBasicBatteryStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(1),
+ batteryNormal(2),
+ batteryLow(3),
+ batteryInFaultCondition(4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the UPS batteries. A batteryLow(3) value
+ indicates the UPS will be unable to sustain the current
+ load, and its services will be lost if power is not restored.
+ The amount of run time in reserve at the time of low battery
+ can be configured by the upsAdvConfigLowBatteryRunTime.
+ A batteryInFaultCondition(4)value indicates that a battery
+ installed has an internal error condition."
+ ::= { upsBasicBattery 1 }
+
+upsBasicBatteryTimeOnBattery OBJECT-TYPE
+ SYNTAX TimeTicks
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The elapsed time since the UPS has switched to battery
+ power."
+ ::= { upsBasicBattery 2 }
+
+upsBasicBatteryLastReplaceDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The date when the UPS system's batteries were last replaced
+ in mm/dd/yy (or yyyy) format. For Smart-UPS models, this value
+ is originally set in the factory. When the UPS batteries
+ are replaced, this value should be reset by the administrator.
+ For Symmetra PX 250/500 this OID is read only and is configurable in the local display only."
+ ::= { upsBasicBattery 3 }
+
+-- the upsAdvBattery group
+
+upsAdvBatteryCapacity OBJECT-TYPE
+ SYNTAX Gauge
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The remaining battery capacity expressed in
+ percent of full capacity."
+ ::= { upsAdvBattery 1 }
+
+upsAdvBatteryTemperature OBJECT-TYPE
+ SYNTAX Gauge
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current internal UPS temperature expressed in
+ Celsius. Temperatures below zero read as 0.
+
+ Consider using upsHighPrecExtdBatteryTemperature instead."
+ ::= { upsAdvBattery 2 }
+
+upsAdvBatteryRunTimeRemaining OBJECT-TYPE
+ SYNTAX TimeTicks
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The UPS battery run time remaining before battery
+ exhaustion."
+ ::= { upsAdvBattery 3 }
+
+upsAdvBatteryReplaceIndicator OBJECT-TYPE
+ SYNTAX INTEGER {
+ noBatteryNeedsReplacing(1),
+ batteryNeedsReplacing(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates whether the UPS batteries need replacing."
+ ::= { upsAdvBattery 4 }
+
+upsAdvBatteryNumOfBattPacks OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of external battery packs connected to the UPS. If
+ the UPS does not use smart cells then the agent reports
+ ERROR_NO_SUCH_NAME."
+ ::= { upsAdvBattery 5 }
+
+upsAdvBatteryNumOfBadBattPacks OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of external battery packs connected to the UPS that
+ are defective. If the UPS does not use smart cells then the
+ agent reports ERROR_NO_SUCH_NAME."
+ ::= { upsAdvBattery 6 }
+
+upsAdvBatteryNominalVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The nominal battery voltage in Volts."
+ ::= { upsAdvBattery 7 }
+
+upsAdvBatteryActualVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The actual battery bus voltage in Volts."
+ ::= { upsAdvBattery 8 }
+
+upsAdvBatteryCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery current in Amps."
+ ::= { upsAdvBattery 9 }
+
+upsAdvTotalDCCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The total DC current in Amps."
+ ::= { upsAdvBattery 10 }
+
+upsAdvBatteryFullCapacity OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The full chargeable capacity of the battery which is
+ expressed in percentage."
+ ::= { upsAdvBattery 11 }
+
+-- Advanced Battery Voltage Table
+
+ upsAdvBatteryActualVoltageTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UPSAdvBatteryActualVoltageEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of battery table entries. The number of battery
+ frames present in UPS."
+ ::= { upsAdvBattery 12 }
+
+
+ upsAdvBatteryActualVoltageEntry OBJECT-TYPE
+ SYNTAX UPSAdvBatteryActualVoltageEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Information applicable to
+ each of the Battery frames."
+ INDEX { upsAdvBatteryActualVoltageTableIndex }
+ ::= { upsAdvBatteryActualVoltageTable 1 }
+
+ UPSAdvBatteryActualVoltageEntry ::= SEQUENCE {
+ upsAdvBatteryActualVoltageTableIndex INTEGER,
+ upsAdvBatteryActualVoltagePolarity INTEGER,
+ upsAdvBatteryFrameActualVoltage INTEGER
+ }
+
+ upsAdvBatteryActualVoltageTableIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Battery Frame identifier. Battery Frame index."
+ ::= { upsAdvBatteryActualVoltageEntry 1 }
+
+ upsAdvBatteryActualVoltagePolarity OBJECT-TYPE
+ SYNTAX INTEGER {
+ positive (0),
+ negative (1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The selected Battery Voltage Polarity.
+ 0 indicates positive polarity.
+ 1 indicates negative polarity."
+ ::= { upsAdvBatteryActualVoltageEntry 2 }
+
+ upsAdvBatteryFrameActualVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The actual battery bus voltage in Volts."
+ ::= { upsAdvBatteryActualVoltageEntry 3 }
+
+-- Advanced TotalDC Current Table
+
+ upsAdvTotalDCCurrentTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UPSAdvTotalDCCurrentEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of Battery Frame table entries. The number of entries
+ is given by the value of Number of Battery Frames."
+ ::= { upsAdvBattery 13 }
+
+
+ upsAdvTotalDCCurrentEntry OBJECT-TYPE
+ SYNTAX UPSAdvTotalDCCurrentEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular Battery Frame."
+ INDEX { upsAdvTotalDCCurrentTableIndex }
+ ::= { upsAdvTotalDCCurrentTable 1 }
+
+ UPSAdvTotalDCCurrentEntry ::= SEQUENCE {
+ upsAdvTotalDCCurrentTableIndex INTEGER,
+ upsAdvTotalDCCurrentPolarity INTEGER,
+ upsAdvTotalFrameDCCurrent INTEGER
+ }
+
+ upsAdvTotalDCCurrentTableIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Battery Frame identifier. Total DC Current
+ Table Index."
+ ::= { upsAdvTotalDCCurrentEntry 1 }
+
+ upsAdvTotalDCCurrentPolarity OBJECT-TYPE
+ SYNTAX INTEGER {
+ positive (0),
+ negative (1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The selected Battery Current Polarity.
+ 0 indicates positive polarity.
+ 1 indicates negative polarity."
+ ::= { upsAdvTotalDCCurrentEntry 2 }
+
+ upsAdvTotalFrameDCCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ " The Total DC Current of battery in Amperes."
+ ::= { upsAdvTotalDCCurrentEntry 3 }
+
+
+
+-- Advanced Battery Current Table
+
+ upsAdvBatteryCurrentTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UPSAdvBatteryCurrentEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of Battery Frame table entries. The number of entries
+ is given by number of Battery frames present."
+ ::= { upsAdvBattery 14 }
+
+ upsAdvBatteryCurrentEntry OBJECT-TYPE
+ SYNTAX UPSAdvBatteryCurrentEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular battery frame."
+ INDEX { upsAdvBatteryCurrentTableIndex, upsAdvBatteryCurrentIndex }
+ ::= { upsAdvBatteryCurrentTable 1 }
+
+ UPSAdvBatteryCurrentEntry ::= SEQUENCE {
+ upsAdvBatteryCurrentTableIndex INTEGER,
+ upsAdvBatteryCurrentIndex INTEGER,
+ upsAdvBatteryCurrentPolarity INTEGER,
+ upsAdvBatteryFrameCurrent INTEGER
+ }
+
+ upsAdvBatteryCurrentTableIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Battery Frame identifier. Battery Current
+ Table Index."
+ ::= { upsAdvBatteryCurrentEntry 1 }
+
+ upsAdvBatteryCurrentIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery frame identifier."
+ ::= { upsAdvBatteryCurrentEntry 2 }
+
+ upsAdvBatteryCurrentPolarity OBJECT-TYPE
+ SYNTAX INTEGER {
+ positive (0),
+ negative (1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The selected Battery current polarity.
+ 0 indicates positive polarity.
+ 1 indicates negative polarity"
+ ::= { upsAdvBatteryCurrentEntry 3 }
+
+ upsAdvBatteryFrameCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Battery current measured in Amperes"
+ ::= { upsAdvBatteryCurrentEntry 4 }
+
+
+ upsAdvBatteryEstimatedChargeTime OBJECT-TYPE
+ SYNTAX TimeTicks
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The estimated remaining time required to charge the UPS to a full state of charge."
+ ::= { upsAdvBattery 15 }
+
+ upsAdvBatteryPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The measured battery power in kW."
+ ::= { upsAdvBattery 16 }
+
+ upsAdvBatteryChargerStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(1),
+ ok(2),
+ inFaultCondition(3),
+ floatCharging(4),
+ boostCharging(5),
+ resting(6),
+ notCharging(7),
+ equalizationCharging(8),
+ testInProgress(9),
+ cyclicFloatCharging(10)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the battery charger. If the UPS is unable
+ to find the state of charger, this variable is set to unknown(1)."
+ ::= { upsAdvBattery 17 }
+
+
+ upsAdvBatteryInternalSKU OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The SKU of the internal battery."
+ ::= { upsAdvBattery 19 }
+
+ upsAdvBatteryExternalSKU OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The SKU of the external battery."
+ ::= { upsAdvBattery 20 }
+
+ upsAdvBatteryRecommendedReplaceDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The recommended replacement date for the battery based on the UPS internal battery life algorithm."
+ ::= { upsAdvBattery 21 }
+
+ upsAdvBatteryNominalBackupTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Defines the runtime of the user supplied battery in minutes, when battery is new."
+ ::= { upsAdvBattery 22 }
+
+ upsAdvBatteryCondition OBJECT-TYPE
+ SYNTAX INTEGER{
+ unknown(1),
+ ok(2),
+ weak(3),
+ poor(4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Health of the battries based on the battery test."
+ ::= { upsAdvBattery 23 }
+
+ upsAdvBatteryChargingCurrentRestricted OBJECT-TYPE
+ SYNTAX INTEGER{
+ yes (1),
+ no (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates whether battery charging current is restricted or not.
+ The value of yes(1) indicates that battery charging current is restricted .
+ The value of no(2) indicates that battery charging current is not restricted."
+ ::= { upsAdvBattery 24 }
+
+upsAdvBatteryTotalCapacity OBJECT-TYPE
+ SYNTAX Gauge
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The actual available battery capacity of the system expressed in ampere hours (Ah).
+ The value is updated continuously, for example when battery breakers are opened or closed,
+ or when battery strings/battery blocks are added or removed."
+ ::= { upsAdvBattery 25 }
+
+upsAdvBatteryFuseStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ fuseOpen(1),
+ fuseOk(2),
+ notPresent(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "If battery system has one common fuse for the battery system, the status is given by this value.
+ 1 = Fuse Open
+ 2 = Fuse Ok
+ 3 = Not present"
+ ::= { upsAdvBattery 26 }
+
+upsAdvBatteryBreakerStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ disconnected(1),
+ closed(2),
+ notPresent(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The value indicates the aggregated status of the battery breakers in the system.
+ disconnected(1) indicates none of the battery breakers are closed, and the battery system is disconnected
+ closed(2) indicates at least one of the battery breakers in the system is closed
+ notPresent(3) if not present"
+ ::= { upsAdvBattery 27 }
+
+upsAdvBatteryWiringConfiguration OBJECT-TYPE
+ SYNTAX INTEGER {
+ twoWire(1),
+ threeWire(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The value indicates the wiring configuration, whether the battery is 2-wire or 3-wire.
+ If it's a 3-wire battery system, the system can have 2 voltages and currents per cabinet.
+ 1 = 2-wire (a non-split battery)
+ 2 = 3-wire (a split battery)"
+ ::= { upsAdvBattery 28 }
+
+
+-- the upsHighPrecBattery group
+
+upsHighPrecBatteryCapacity OBJECT-TYPE
+ SYNTAX Gauge
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The remaining battery capacity expressed in
+ tenths of percent of full capacity."
+ ::= { upsHighPrecBattery 1 }
+
+upsHighPrecBatteryTemperature OBJECT-TYPE
+ SYNTAX Gauge
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current internal UPS temperature expressed in
+ tenths of degrees Celsius. Temperatures below zero
+ read as 0.
+
+ Consider using upsHighPrecExtdBatteryTemperature instead."
+ ::= { upsHighPrecBattery 2 }
+
+upsHighPrecBatteryNominalVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The nominal battery voltage in tenths of Volts."
+ ::= { upsHighPrecBattery 3 }
+
+upsHighPrecBatteryActualVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The actual battery bus voltage in tenths of Volts."
+ ::= { upsHighPrecBattery 4 }
+
+upsHighPrecBatteryCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery current in tenths of Amps."
+ ::= { upsHighPrecBattery 5 }
+
+upsHighPrecTotalDCCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The total DC current in tenths of Amps."
+ ::= { upsHighPrecBattery 6 }
+
+-- High Precision Actual Battery Voltage Table
+
+ upsHighPrecBatteryActualVoltageTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UPSHighPrecBatteryActualVoltageEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of Battery frame table entries. The number of entries
+ is given by the number of Battery frames."
+ ::= { upsHighPrecBattery 7 }
+
+
+ upsHighPrecBatteryActualVoltageEntry OBJECT-TYPE
+ SYNTAX UPSHighPrecBatteryActualVoltageEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular battery frame."
+ INDEX { upsHighPrecBatteryActualVoltageTableIndex }
+ ::= { upsHighPrecBatteryActualVoltageTable 1 }
+
+ UPSHighPrecBatteryActualVoltageEntry ::= SEQUENCE {
+ upsHighPrecBatteryActualVoltageTableIndex INTEGER,
+ upsHighPrecBatteryActualVoltagePolarity INTEGER,
+ upsHighPrecBatteryVoltage INTEGER
+ }
+
+ upsHighPrecBatteryActualVoltageTableIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Battery Frame identifier. High Precision
+ Actual Voltage Table Index."
+ ::= { upsHighPrecBatteryActualVoltageEntry 1 }
+
+ upsHighPrecBatteryActualVoltagePolarity OBJECT-TYPE
+ SYNTAX INTEGER {
+ positive (0),
+ negative (1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The selected Battery Voltage polarity.
+ 0 indicates positive polarity.
+ 1 indicates negative polarity."
+ ::= { upsHighPrecBatteryActualVoltageEntry 2 }
+
+ upsHighPrecBatteryVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The actual battery bus voltage expressed
+ as tenths of Volts. "
+ ::= { upsHighPrecBatteryActualVoltageEntry 3 }
+
+-- High Precision Total DC Current Table
+
+ upsHighPrecTotalDCCurrentTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UPSHighPrecTotalDCCurrentEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of Battery Frame table entries. The number of entries
+ is given by the number of battery frames."
+ ::= { upsHighPrecBattery 8 }
+
+
+ upsHighPrecTotalDCCurrentEntry OBJECT-TYPE
+ SYNTAX UPSHighPrecTotalDCCurrentEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular battery frame."
+ INDEX { upsHighPrecTotalDCCurrentTableIndex }
+ ::= { upsHighPrecTotalDCCurrentTable 1 }
+
+ UPSHighPrecTotalDCCurrentEntry ::= SEQUENCE {
+ upsHighPrecTotalDCCurrentTableIndex INTEGER,
+ upsHighPrecTotalDCCurrentPolarity INTEGER,
+ upsHighPrecTotalDCFrameCurrent INTEGER
+ }
+
+ upsHighPrecTotalDCCurrentTableIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Battery Frame identifier.
+ High precision Total DC Current index."
+ ::= { upsHighPrecTotalDCCurrentEntry 1 }
+
+ upsHighPrecTotalDCCurrentPolarity OBJECT-TYPE
+ SYNTAX INTEGER {
+ positive (0),
+ negative (1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The selected Battery Current polarity.
+ 0 indicates positive polarity.
+ 1 indicates negative polarity."
+ ::= { upsHighPrecTotalDCCurrentEntry 2 }
+
+ upsHighPrecTotalDCFrameCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The total DC current in tenths of Amperes. "
+ ::= { upsHighPrecTotalDCCurrentEntry 3 }
+
+
+-- HighPrec Battery Current Table
+
+ upsHighPrecBatteryCurrentTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UPSHighPrecBatteryCurrentEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of Battery Frame table entries. The number of entries
+ is given by the number of battery frames."
+ ::= { upsHighPrecBattery 9 }
+
+ upsHighPrecBatteryCurrentEntry OBJECT-TYPE
+ SYNTAX UPSHighPrecBatteryCurrentEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular battery frame."
+ INDEX { upsHighPrecBatteryCurrentTableIndex, upsHighPrecBatteryCurrentIndex }
+ ::= { upsHighPrecBatteryCurrentTable 1 }
+
+ UPSHighPrecBatteryCurrentEntry ::= SEQUENCE {
+ upsHighPrecBatteryCurrentTableIndex INTEGER,
+ upsHighPrecBatteryCurrentIndex INTEGER,
+ upsHighPrecBatteryCurrentPolarity INTEGER,
+ upsHighPrecBatteryFrameCurrent INTEGER
+ }
+
+ upsHighPrecBatteryCurrentTableIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Battery frame identifier.
+ Battery Frame index."
+ ::= { upsHighPrecBatteryCurrentEntry 1 }
+
+ upsHighPrecBatteryCurrentIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Battery frame identifier.
+ Battery Index for each frame."
+ ::= { upsHighPrecBatteryCurrentEntry 2 }
+
+ upsHighPrecBatteryCurrentPolarity OBJECT-TYPE
+ SYNTAX INTEGER {
+ positive (0),
+ negative (1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The selected Battery Current polarity.
+ 0 indicates positive polarity.
+ 1 indicates negative polarity."
+ ::= { upsHighPrecBatteryCurrentEntry 3 }
+
+ upsHighPrecBatteryFrameCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Battery current in tenths of Amperes."
+ ::= { upsHighPrecBatteryCurrentEntry 4 }
+
+-- High Precision Battery Packs
+
+upsHighPrecBatteryPacks OBJECT IDENTIFIER ::= { upsHighPrecBattery 10 }
+
+upsHighPrecBatteryPackTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the upsHighPrecBatteryPacks."
+ ::= { upsHighPrecBatteryPacks 1 }
+
+ upsHighPrecBatteryPackTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UPSHighPrecBatteryPackEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of Battery Pack table entries. The number of entries
+ is given by number of Battery Packs present."
+ ::= { upsHighPrecBatteryPacks 2 }
+
+ upsHighPrecBatteryPackEntry OBJECT-TYPE
+ SYNTAX UPSHighPrecBatteryPackEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular battery pack."
+ INDEX { upsHighPrecBatteryPackIndex, upsHighPrecBatteryCartridgeIndex }
+ ::= { upsHighPrecBatteryPackTable 1 }
+
+ UPSHighPrecBatteryPackEntry ::= SEQUENCE {
+ upsHighPrecBatteryPackIndex INTEGER,
+ upsHighPrecBatteryCartridgeIndex INTEGER,
+ upsHighPrecBatteryPackFirmwareRevision DisplayString,
+ upsHighPrecBatteryPackSerialNumber DisplayString,
+ upsHighPrecBatteryPackTemperature INTEGER,
+ upsHighPrecBatteryPackStatus OCTET STRING,
+ upsHighPrecBatteryPackCartridgeHealth OCTET STRING,
+ upsHighPrecBatteryPackCartridgeReplaceDate DisplayString,
+ upsHighPrecBatteryPackCartridgeInstallDate DisplayString,
+ upsHighPrecBatteryPackCartridgeStatus OCTET STRING
+ }
+
+ upsHighPrecBatteryPackIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery pack identifier."
+ ::= { upsHighPrecBatteryPackEntry 1 }
+
+ upsHighPrecBatteryCartridgeIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery cartridge identifier."
+ ::= { upsHighPrecBatteryPackEntry 2 }
+
+ upsHighPrecBatteryPackFirmwareRevision OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery pack firmware revision."
+ ::= { upsHighPrecBatteryPackEntry 3}
+
+ upsHighPrecBatteryPackSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery pack serial number."
+ ::= { upsHighPrecBatteryPackEntry 4}
+
+ upsHighPrecBatteryPackTemperature OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery pack temperature measured in 10ths of degree Celcius"
+ ::= { upsHighPrecBatteryPackEntry 5 }
+
+ upsHighPrecBatteryPackStatus OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery status for the pack only.
+ bit 0 Disconnected
+ bit 1 Overvoltage
+ bit 2 NeedsReplacement
+ bit 3 OvertemperatureCritical
+ bit 4 Charger
+ bit 5 TemperatureSensor
+ bit 6 BusSoftStart
+ bit 7 OvertemperatureWarning
+ bit 8 GeneralError
+ bit 9 Communication
+ bit 10 DisconnectedFrame
+ bit 11 FirmwareMismatch
+ "
+ ::= { upsHighPrecBatteryPackEntry 6 }
+
+ upsHighPrecBatteryPackCartridgeHealth OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery cartridge health.
+ bit 0 Battery lifetime okay
+ bit 1 Battery lifetime near end, order replacement cartridge
+ bit 2 Battery lifetime exceeded, replace battery
+ bit 3 Battery lifetime near end acknowledged, order replacement cartridge
+ bit 4 Battery lifetime exceeded acknowledged, replace battery
+ bit 5 Battery measured lifetime near end, order replacement cartridge
+ bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge
+ "
+ ::= { upsHighPrecBatteryPackEntry 7}
+
+ upsHighPrecBatteryPackCartridgeReplaceDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery cartridge estimated battery replace date."
+ ::= { upsHighPrecBatteryPackEntry 8 }
+
+ upsHighPrecBatteryPackCartridgeInstallDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The battery cartridge install date."
+ ::= { upsHighPrecBatteryPackEntry 9 }
+
+ upsHighPrecBatteryPackCartridgeStatus OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery cartridge status.
+ bit 0 Disconnected
+ bit 1 Overvoltage
+ bit 2 NeedsReplacement
+ bit 3 OvertemperatureCritical
+ bit 4 Charger
+ bit 5 TemperatureSensor
+ bit 6 BusSoftStart
+ bit 7 OvertemperatureWarning
+ bit 8 GeneralError
+ bit 9 Communication
+ bit 10 DisconnectedFrame
+ bit 11 FirmwareMismatch
+ "
+ ::= { upsHighPrecBatteryPackEntry 10 }
+
+upsHighPrecBatteryPackOnlyTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the upsHighPrecBatteryPacks."
+ ::= { upsHighPrecBatteryPacks 3 }
+
+ upsHighPrecBatteryPackOnlyTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UPSHighPrecBatteryPackOnlyEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of Battery Pack table entries. The number of entries
+ is given by number of Battery Packs present."
+ ::= { upsHighPrecBatteryPacks 4 }
+
+ upsHighPrecBatteryPackOnlyEntry OBJECT-TYPE
+ SYNTAX UPSHighPrecBatteryPackOnlyEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular battery pack."
+ INDEX { upsHighPrecBatteryPackOnlyIndex }
+ ::= { upsHighPrecBatteryPackOnlyTable 1 }
+
+ UPSHighPrecBatteryPackOnlyEntry ::= SEQUENCE {
+ upsHighPrecBatteryPackOnlyIndex INTEGER,
+ upsHighPrecBatteryPackOnlyFirmwareRevision DisplayString,
+ upsHighPrecBatteryPackOnlySerialNumber DisplayString,
+ upsHighPrecBatteryPackOnlyTemperature INTEGER,
+ upsHighPrecBatteryPackOnlyStatus OCTET STRING,
+ upsHighPrecBatteryPackOnlyHealth OCTET STRING,
+ upsHighPrecBatteryPackOnlyReplaceDate DisplayString,
+ upsHighPrecBatteryPackOnlyInstallDate DisplayString
+ }
+
+ upsHighPrecBatteryPackOnlyIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery pack identifier."
+ ::= { upsHighPrecBatteryPackOnlyEntry 1 }
+
+ upsHighPrecBatteryPackOnlyFirmwareRevision OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery pack firmware revision."
+ ::= { upsHighPrecBatteryPackOnlyEntry 2}
+
+ upsHighPrecBatteryPackOnlySerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery pack serial number."
+ ::= { upsHighPrecBatteryPackOnlyEntry 3}
+
+ upsHighPrecBatteryPackOnlyTemperature OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery pack temperature measured in 10ths of degree Celcius"
+ ::= { upsHighPrecBatteryPackOnlyEntry 4 }
+
+ upsHighPrecBatteryPackOnlyStatus OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery status for the pack only.
+ bit 0 Disconnected
+ bit 1 Overvoltage
+ bit 2 NeedsReplacement
+ bit 3 OvertemperatureCritical
+ bit 4 Charger
+ bit 5 TemperatureSensor
+ bit 6 BusSoftStart
+ bit 7 OvertemperatureWarning
+ bit 8 GeneralError
+ bit 9 Communication
+ bit 10 DisconnectedFrame
+ bit 11 FirmwareMismatch
+ "
+ ::= { upsHighPrecBatteryPackOnlyEntry 5 }
+
+ upsHighPrecBatteryPackOnlyHealth OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery pack health.
+ bit 0 Battery lifetime okay
+ bit 1 Battery lifetime near end, order replacement pack
+ bit 2 Battery lifetime exceeded, replace battery
+ bit 3 Battery lifetime near end acknowledged, order replacement pack
+ bit 4 Battery lifetime exceeded acknowledged, replace battery
+ bit 5 Battery measured lifetime near end, order replacement pack
+ bit 6 Battery measured lifetime near end acknowledged, order replacement pack
+ "
+ ::= { upsHighPrecBatteryPackOnlyEntry 6 }
+
+ upsHighPrecBatteryPackOnlyReplaceDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery pack estimated battery replace date."
+ ::= { upsHighPrecBatteryPackOnlyEntry 7 }
+
+ upsHighPrecBatteryPackOnlyInstallDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The battery pack install date."
+ ::= { upsHighPrecBatteryPackOnlyEntry 8 }
+
+-- end of High Precision Battery Packs
+
+upsHighPrecBatteryHealth OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery health.
+ Bit 0 Battery life okay
+ Bit 1 Battery life near end, order battery cartridge
+ Bit 2 Battery life exceeded, replace battery cartridge
+ Bit 3 Battery life near end acknowledged, order battery
+ cartridge
+ Bit 4 Battery life exceeded acknowledged, replace battery
+ cartridge
+ Bit 5 Battery measured life near end, order battery cartridge
+ Bit 6 Battery measured life near end acknowledged, order
+ battery cartridge"
+ ::= { upsHighPrecBattery 11}
+
+upsHighPrecActivePower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Active Power of Battery in tenths of kW"
+ ::= { upsHighPrecBattery 12 }
+
+upsHighPrecExtdBatteryTemperature OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current internal UPS temperature expressed in
+ tenths of degrees Celsius. Can be negative."
+ ::= { upsHighPrecBattery 13 }
+
+ upsBatteryNumberOfCabinets OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The value indicates the number of battery cabinets in total, internal and external.
+ If the UPS only has internal batteries, that number should be 1.
+ If the UPS has external and internal, the number is 1 + number of external cabinets."
+ ::= { upsBattery 4 }
+
+-- Battery Cabinet Table
+
+ upsBatteryCabinetTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UPSBatteryCabinetEntry
+ ACCESS not-accessible
+ STATUS optional
+ DESCRIPTION
+ "Table of battery cabinets"
+ ::= { upsBattery 5 }
+
+ upsBatteryCabinetEntry OBJECT-TYPE
+ SYNTAX UPSBatteryCabinetEntry
+ ACCESS not-accessible
+ STATUS optional
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular battery cabinet."
+ INDEX { upsBatteryCabinetIndex }
+ ::= { upsBatteryCabinetTable 1 }
+
+ UPSBatteryCabinetEntry ::= SEQUENCE {
+ upsBatteryCabinetIndex INTEGER,
+ upsBatteryCabinetLocalIndex INTEGER,
+ upsBatteryCabinetWiringConfiguration INTEGER,
+ upsBatteryCabinetVoltagePolarity1 INTEGER,
+ upsBatteryCabinetVoltagePolarity2 INTEGER,
+ upsBatteryCabinetCurrentPolarity1 INTEGER,
+ upsBatteryCabinetCurrentPolarity2 INTEGER,
+ upsBatteryCabinetTemperature INTEGER,
+ upsBatteryCabinetMaxTemperature INTEGER,
+ upsBatteryCabinetMinTemperature INTEGER,
+ upsBatteryCabinetAverageTemperature INTEGER,
+ upsBatteryCabinetFuse INTEGER,
+ upsBatteryCabinetBreaker INTEGER,
+ upsBatteryCabinetNumberOfStrings INTEGER,
+ upsBatteryCabinetNumberOfVerticalPositions INTEGER,
+ upsBatteryCabinetNumberOfHorizontalPositions INTEGER
+ }
+
+ upsBatteryCabinetIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "The Battery Cabinet identifier. Battery Cabinet
+ Table Index."
+ ::= { upsBatteryCabinetEntry 1 }
+
+ upsBatteryCabinetLocalIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "The identification number for the actual battery cabinet in the system.
+ 0 corresponds to the internal batteries
+ 1 and higher corresponds to external battery cabinets"
+ ::= { upsBatteryCabinetEntry 2 }
+
+ upsBatteryCabinetWiringConfiguration OBJECT-TYPE
+ SYNTAX INTEGER {
+ twoWire(1),
+ threeWire(2)
+ }
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "The value indicates the wiring configuration, whether the battery is 2-wire or 3-wire.
+ If it's a 3-wire battery system, the system can have two voltages and currents per cabinet.
+ 1 = 2-wire (a non-split battery)
+ 2 = 3-wire (a split battery)"
+ ::= { upsBatteryCabinetEntry 3 }
+
+ upsBatteryCabinetVoltagePolarity1 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "The battery voltage. For a non-split battery, it is the full voltage.
+ For a split battery, the value is the voltage for one side/half of the battery"
+ ::= { upsBatteryCabinetEntry 4 }
+
+ upsBatteryCabinetVoltagePolarity2 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "The voltage for the second side/half of the battery in a split battery system.
+ If it is not a split battery, this reports -1"
+ ::= { upsBatteryCabinetEntry 5 }
+
+ upsBatteryCabinetCurrentPolarity1 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "The battery current. For a non-split battery, it is the full current.
+ For a split battery, the value is the current for one side/half of the battery"
+ ::= { upsBatteryCabinetEntry 6 }
+
+ upsBatteryCabinetCurrentPolarity2 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "The current for the second side/half of the battery in a split battery system.
+ If it is not a split battery, this reports -1"
+ ::= { upsBatteryCabinetEntry 7 }
+
+ upsBatteryCabinetTemperature OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "The measured temperature of the battery cabinet in tenths of degrees Celcius"
+ ::= { upsBatteryCabinetEntry 8 }
+
+ upsBatteryCabinetMaxTemperature OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "The highest temperature measured for the battery in the battery cabinet in tenths of degrees Celcius.
+ If there are multiple sensors in the battery cabinet, it is the selected highest actual value
+ of measured temperatures.
+ If there is battery string information, it is the highest actual battery string temperature value."
+ ::= { upsBatteryCabinetEntry 9 }
+
+ upsBatteryCabinetMinTemperature OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "The lowest temperature measured for the battery in the battery cabinet in tenths of degrees Celcius.
+ If there are multiple sensors in the battery cabinet, it is the selected lowest actual value
+ of measured temperatures.
+ If there is string information, it is the lowest actual battery string temperature value."
+ ::= { upsBatteryCabinetEntry 10 }
+
+ upsBatteryCabinetAverageTemperature OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "The average temperature for all the battery sensors in the battery cabinet and
+ for the battery strings, if battery strings are present.
+ Measured in tenths of degrees Celcius."
+ ::= { upsBatteryCabinetEntry 11 }
+
+ upsBatteryCabinetFuse OBJECT-TYPE
+ SYNTAX INTEGER {
+ fuseOpen(1),
+ fuseOk(2),
+ notPresent(3)
+ }
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "If the battery cabinet has a common fuse, the status is given by this value.
+ 1 = Fuse open
+ 2 = Fuse OK
+ 3 = Not present"
+ ::= { upsBatteryCabinetEntry 12 }
+
+ upsBatteryCabinetBreaker OBJECT-TYPE
+ SYNTAX INTEGER {
+ noBreaker(1),
+ unknown(2),
+ breakerOpen(3),
+ breakerClosed(4)
+ }
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "The value indicates the battery cabinet breaker status. Reports 1 if no breaker is present.
+ 1 = No breaker
+ 2 = Unknown
+ 3 = Breaker open
+ 4 = Breaker closed"
+ ::= { upsBatteryCabinetEntry 13 }
+
+ upsBatteryCabinetNumberOfStrings OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "The number of battery strings in the battery cabinet. The value can be 0,
+ meaning that no additional information on the battery string is available.
+ 1 and higher means data in the table is provided."
+ ::= { upsBatteryCabinetEntry 14 }
+
+ upsBatteryCabinetNumberOfVerticalPositions OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "The number of vertical levels or shelves for battery blocks/modules.
+ The levels are indexed from the bottom up"
+ ::= { upsBatteryCabinetEntry 15 }
+
+ upsBatteryCabinetNumberOfHorizontalPositions OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "The number of horizontal positions for battery blocks/modules.
+ The levels are indexed from left to right"
+ ::= { upsBatteryCabinetEntry 16 }
+
+-- Battery Cabinet String Table
+
+ upsBatteryCabStringTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UPSBatteryCabStringEntry
+ ACCESS not-accessible
+ STATUS optional
+ DESCRIPTION
+ "Table of battery strings in the complete battery solution"
+ ::= { upsBattery 6 }
+
+ upsBatteryCabStringEntry OBJECT-TYPE
+ SYNTAX UPSBatteryCabStringEntry
+ ACCESS not-accessible
+ STATUS optional
+ DESCRIPTION
+ "An entry containing information applicable to a particular battery string
+ in the battery cabinet."
+ INDEX { upsBatteryCabStringIndex }
+ ::= { upsBatteryCabStringTable 1 }
+
+ UPSBatteryCabStringEntry ::= SEQUENCE {
+ upsBatteryCabStringIndex INTEGER,
+ upsBatteryCabStringCabReference INTEGER,
+ upsBatteryCabStringLocalIndex INTEGER,
+ upsBatteryCabStringCurrent INTEGER,
+ upsBatteryCabStringAverageTemperature INTEGER,
+ upsBatteryCabStringMaxTemperature INTEGER,
+ upsBatteryCabStringMinTemperature INTEGER,
+ upsBatteryCabStringFuseStatus INTEGER,
+ upsBatteryCabStringNumberOfBlocks INTEGER
+ }
+
+ upsBatteryCabStringIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "The battery cabinet string identifier. Battery cabinet string or halfstring
+ table index."
+ ::= { upsBatteryCabStringEntry 1 }
+
+ upsBatteryCabStringCabReference OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "Reference to the global battery cabinet index where the battery string is placed."
+ ::= { upsBatteryCabStringEntry 2 }
+
+ upsBatteryCabStringLocalIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "Local battery string identification index in the actual battery cabinet (E.g. String 2 in cabinet)"
+ ::= { upsBatteryCabStringEntry 3 }
+
+ upsBatteryCabStringCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "The current in a battery string or battery halfstring, in tenths of Amps."
+ ::= { upsBatteryCabStringEntry 4 }
+
+ upsBatteryCabStringAverageTemperature OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "Temperature of the battery string or the average of the aggregated temperature of each
+ battery block/module (in tenths of degrees Celcius). "
+ ::= { upsBatteryCabStringEntry 5 }
+
+ upsBatteryCabStringMaxTemperature OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "The actual highest battery temperature measurement for the battery blocks/modules (in tenths of degrees Celcius)."
+ ::= { upsBatteryCabStringEntry 6 }
+
+ upsBatteryCabStringMinTemperature OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "The actual lowest battery temperature measurement for the battery blocks/modules (in tenths of degrees Celcius)."
+ ::= { upsBatteryCabStringEntry 7 }
+
+ upsBatteryCabStringFuseStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ fuseOpen(1),
+ fuseOk(2),
+ notPresent(3)
+ }
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "If the battery string has a common fuse, the status is given by this value.
+ 1 = Fuse open
+ 2 = Fuse OK
+ 3 = Not present"
+ ::= { upsBatteryCabStringEntry 8 }
+
+ upsBatteryCabStringNumberOfBlocks OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "The number of battery blocks/modules in a battery string.
+ Can be 0, if no data is available in the table of individual battery blocks/cartridges"
+ ::= { upsBatteryCabStringEntry 9 }
+
+-- Battery Cabinet Block Table
+
+ upsBatteryCabBlockTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UPSBatteryCabBlockEntry
+ ACCESS not-accessible
+ STATUS optional
+ DESCRIPTION
+ "Table of battery blocks/modules in the complete battery solution."
+ ::= { upsBattery 7 }
+
+ upsBatteryCabBlockEntry OBJECT-TYPE
+ SYNTAX UPSBatteryCabBlockEntry
+ ACCESS not-accessible
+ STATUS optional
+ DESCRIPTION
+ "An entry containing information applicable to a particular battery block
+ in the battery cabinet."
+ INDEX { upsBatteryCabBlockIndex }
+ ::= { upsBatteryCabBlockTable 1 }
+
+ UPSBatteryCabBlockEntry ::= SEQUENCE {
+ upsBatteryCabBlockIndex INTEGER,
+ upsBatteryCabBlockStringReference INTEGER,
+ upsBatteryCabBlockLocalIndex INTEGER,
+ upsBatteryCabBlockPresent INTEGER,
+ upsBatteryCabBlockType DisplayString,
+ upsBatteryCabBlockTemperature INTEGER,
+ upsBatteryCabBlockFuseStatus INTEGER,
+ upsBatteryCabBlockVoltage INTEGER,
+ upsBatteryCabBlockNumberOfCells INTEGER,
+ upsBatteryCabBlockVerticalPosition INTEGER,
+ upsBatteryCabBlockHorizontalPosition INTEGER
+ }
+
+ upsBatteryCabBlockIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "The battery cabinet block identifier. Global battery cabinet block
+ table index."
+ ::= { upsBatteryCabBlockEntry 1 }
+
+ upsBatteryCabBlockStringReference OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "Reference to the specific global battery string index"
+ ::= { upsBatteryCabBlockEntry 2 }
+
+ upsBatteryCabBlockLocalIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "Local battery block/module identification index in the actual battery string (E.g. Battery block 3 in the battery string)"
+ ::= { upsBatteryCabBlockEntry 3 }
+
+ upsBatteryCabBlockPresent OBJECT-TYPE
+ SYNTAX INTEGER {
+ present(1),
+ notPresent(2),
+ notAvailable(3)
+ }
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "Value indicates if battery block/module is present in the system.
+ Typically battery modules are removable and battery blocks are static. Reports notAvailable(3) if data is not available"
+ ::= { upsBatteryCabBlockEntry 4 }
+
+ upsBatteryCabBlockType OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "Text string value, showing the vendor and model of the battery in the battery block/module"
+ ::= { upsBatteryCabBlockEntry 5 }
+
+ upsBatteryCabBlockTemperature OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "The temperature for the battery block/module in tenths of degrees Celcius.
+ If multiple sensors are available it is the highest temperature in the battery block/module"
+ ::= { upsBatteryCabBlockEntry 6 }
+
+ upsBatteryCabBlockFuseStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ fuseOpen(1),
+ fuseOk(2),
+ notPresent(3)
+ }
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "If the battery module has a fuse, the status is given by this value.
+ 1 = Fuse open
+ 2 = Fuse OK
+ 3 = Not present"
+ ::= { upsBatteryCabBlockEntry 7 }
+
+ upsBatteryCabBlockVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "The voltage of the battery block/module"
+ ::= { upsBatteryCabBlockEntry 8 }
+
+ upsBatteryCabBlockNumberOfCells OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "The number of cells in the battery block/module"
+ ::= { upsBatteryCabBlockEntry 9 }
+
+ upsBatteryCabBlockVerticalPosition OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "The vertical position of the battery block/module in the actual battery cabinet
+ (E.g. 4, if it is the 4th shelf counting from the bottom)"
+ ::= { upsBatteryCabBlockEntry 10 }
+
+ upsBatteryCabBlockHorizontalPosition OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "The horizontal position of the battery block/module in the actual battery cabinet
+ (E.g. 3, if it is the 3rd position counting from the left)"
+ ::= { upsBatteryCabBlockEntry 11 }
+
+-- Battery Block Cell Table
+
+ upsBatteryCabBlockCellTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UPSBatteryCabBlockCellEntry
+ ACCESS not-accessible
+ STATUS optional
+ DESCRIPTION
+ "Table of battery cells in a battery block/module in the complete battery solution"
+ ::= { upsBattery 8 }
+
+ upsBatteryCabBlockCellEntry OBJECT-TYPE
+ SYNTAX UPSBatteryCabBlockCellEntry
+ ACCESS not-accessible
+ STATUS optional
+ DESCRIPTION
+ "An entry containing information applicable to a particular battery cell
+ inside the battery block."
+ INDEX { upsBatteryCabBlockCellIndex }
+ ::= { upsBatteryCabBlockCellTable 1 }
+
+ UPSBatteryCabBlockCellEntry ::= SEQUENCE {
+ upsBatteryCabBlockCellIndex INTEGER,
+ upsBatteryCabBlockCellReference INTEGER,
+ upsBatteryCabBlockCellLocalIndex INTEGER,
+ upsBatteryCabBlockCellVoltage INTEGER,
+ upsBatteryCabBlockCellTemperature INTEGER
+ }
+
+ upsBatteryCabBlockCellIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "The battery block cell identifier. Global battery block cell
+ table index."
+ ::= { upsBatteryCabBlockCellEntry 1 }
+
+ upsBatteryCabBlockCellReference OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "Reference to the specific global battery block/module index."
+ ::= { upsBatteryCabBlockCellEntry 2 }
+
+ upsBatteryCabBlockCellLocalIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "Local battery block/module identification index in the actual battery block (E.g. battery cell 5 in the battery block)"
+ ::= { upsBatteryCabBlockCellEntry 3 }
+
+ upsBatteryCabBlockCellVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "The measured battery cell voltage"
+ ::= { upsBatteryCabBlockCellEntry 4 }
+
+ upsBatteryCabBlockCellTemperature OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "The temperature for the battery cell in tenths of degrees Celcius.
+ If there is not a temperature sensor for each battery cell, then report -1 for those, which are not present."
+ ::= { upsBatteryCabBlockCellEntry 5 }
+
+-- the upsBasicInput group
+
+upsBasicInputPhase OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current AC input phase."
+ ::= { upsBasicInput 1 }
+
+
+-- the upsAdvInput group
+
+upsAdvInputLineVoltage OBJECT-TYPE
+ SYNTAX Gauge
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current utility line voltage in VAC."
+ ::= { upsAdvInput 1 }
+
+upsAdvInputMaxLineVoltage OBJECT-TYPE
+ SYNTAX Gauge
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum utility line voltage in VAC over the
+ previous 1 minute period."
+ ::= { upsAdvInput 2 }
+
+upsAdvInputMinLineVoltage OBJECT-TYPE
+ SYNTAX Gauge
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum utility line voltage in VAC over the
+ previous 1 minute period."
+ ::= { upsAdvInput 3 }
+
+upsAdvInputFrequency OBJECT-TYPE
+ SYNTAX Gauge
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current input frequency to the UPS system in Hz."
+ ::= { upsAdvInput 4 }
+
+
+upsAdvInputLineFailCause OBJECT-TYPE
+ SYNTAX INTEGER {
+ noTransfer(1),
+ highLineVoltage(2),
+ brownout(3),
+ blackout(4),
+ smallMomentarySag(5),
+ deepMomentarySag(6),
+ smallMomentarySpike(7),
+ largeMomentarySpike(8),
+ selfTest(9),
+ rateOfVoltageChange(10)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The reason for the occurrence of the last transfer to UPS
+ battery power. The variable is set to:
+ - noTransfer(1) -- if there is no transfer yet.
+ - highLineVoltage(2) -- if the transfer to battery is caused
+ by an over voltage greater than the high transfer voltage.
+ - brownout(3) -- if the duration of the outage is greater than
+ five seconds and the line voltage is between 40% of the
+ rated output voltage and the low transfer voltage.
+ - blackout(4) -- if the duration of the outage is greater than five
+ seconds and the line voltage is between 40% of the rated
+ output voltage and ground.
+ - smallMomentarySag(5) -- if the duration of the outage is less
+ than five seconds and the line voltage is between 40% of the
+ rated output voltage and the low transfer voltage.
+ - deepMomentarySag(6) -- if the duration of the outage is less
+ than five seconds and the line voltage is between 40% of the
+ rated output voltage and ground. The variable is set to
+ - smallMomentarySpike(7) -- if the line failure is caused by a
+ rate of change of input voltage less than ten volts per cycle.
+ - largeMomentarySpike(8) -- if the line failure is caused by
+ a rate of change of input voltage greater than ten volts per cycle.
+ - selfTest(9) -- if the UPS was commanded to do a self test.
+ - rateOfVoltageChange(10) -- if the failure is due to the rate of change of
+ the line voltage."
+ ::= { upsAdvInput 5 }
+
+
+upsAdvInputNominalFrequency OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The nominal input frequency of the UPS system in Hz."
+ ::= { upsAdvInput 6 }
+
+upsAdvInputNominalVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The nominal input voltage of the UPS system in VAC."
+ ::= { upsAdvInput 7 }
+
+upsAdvInputBypassNominalFrequency OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The nominal bypass input frequency of the UPS system in Hz."
+ ::= { upsAdvInput 8 }
+
+upsAdvInputBypassNominalVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The nominal bypass input voltage of the UPS system in VAC."
+ ::= { upsAdvInput 9 }
+
+ upsAdvInputStatisticsTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsAdvInputStatisticsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of input table entries. The number of entries
+ is given by the value of upsPhaseNumInputs."
+ ::= { upsAdvInput 10 }
+
+ upsAdvInputStatisticsEntry OBJECT-TYPE
+ SYNTAX UpsAdvInputStatisticsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular input."
+ INDEX { upsAdvInputStatisticsIndex }
+ ::= { upsAdvInputStatisticsTable 1 }
+
+UpsAdvInputStatisticsEntry ::= SEQUENCE {
+ upsAdvInputStatisticsIndex INTEGER,
+ upsAdvInputApparentPower INTEGER,
+ upsAdvInputVoltageTHD INTEGER,
+ upsAdvInputBypassVoltageTHD INTEGER,
+ upsAdvInputPeakCurrent INTEGER,
+ upsAdvInputBypassPeakCurrent INTEGER,
+ upsAdvInputActivePower INTEGER
+ }
+
+ upsAdvInputStatisticsIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input identifier."
+ ::= { upsAdvInputStatisticsEntry 1 }
+
+upsAdvInputApparentPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input apparent power(sum of all of the three phases) measured in kVA."
+ ::= { upsAdvInputStatisticsEntry 2 }
+
+upsAdvInputVoltageTHD OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input voltage Total Harmonic Distortion in percent."
+ ::= { upsAdvInputStatisticsEntry 3 }
+
+upsAdvInputBypassVoltageTHD OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The bypass input voltage Total Harmonic Distortion in percent."
+ ::= { upsAdvInputStatisticsEntry 4 }
+
+upsAdvInputPeakCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input peak current in Amperes."
+ ::= { upsAdvInputStatisticsEntry 5 }
+
+upsAdvInputBypassPeakCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The bypass input peak current in Amperes."
+ ::= { upsAdvInputStatisticsEntry 6 }
+
+
+upsAdvInputActivePower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input active power measured in kW."
+ ::= { upsAdvInputStatisticsEntry 7 }
+
+
+
+
+upsAdvInputTotalApparentPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input total apparent power(sum of all three phases)
+ of the UPS system in kVA."
+ ::= { upsAdvInput 11 }
+
+upsAdvInputTotalActivePower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input total active power(sum of all three phases)
+ of the UPS system in kW."
+ ::= { upsAdvInput 12 }
+
+upsAdvInputBypassTotalApparentPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input bypass total apparent power(sum of all three phases)
+ of the UPS system in kVA."
+ ::= { upsAdvInput 13 }
+
+upsAdvInputBypassTotalActivePower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input bypass total active power(sum of all three phases)
+ of the UPS system in kW."
+ ::= { upsAdvInput 14 }
+
+upsAdvInputEnergyUsage OBJECT-TYPE
+ SYNTAX Unsigned32
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input energy usage of the UPS in kWh."
+ ::= { upsAdvInput 15 }
+
+upsAdvInputDCVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The DC input voltage in Volts."
+ ::= { upsAdvInput 16 }
+
+upsAdvInputDCCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The DC input current in Amps."
+ ::= { upsAdvInput 17 }
+
+-- the upsHighPrecInput group
+
+upsHighPrecInputLineVoltage OBJECT-TYPE
+ SYNTAX Gauge
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current utility line voltage in tenths of VAC."
+ ::= { upsHighPrecInput 1 }
+
+upsHighPrecInputMaxLineVoltage OBJECT-TYPE
+ SYNTAX Gauge
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum utility line voltage in tenths of VAC over the
+ previous 1 minute period."
+ ::= { upsHighPrecInput 2 }
+
+upsHighPrecInputMinLineVoltage OBJECT-TYPE
+ SYNTAX Gauge
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum utility line voltage in tenths of VAC over the
+ previous 1 minute period."
+ ::= { upsHighPrecInput 3 }
+
+upsHighPrecInputFrequency OBJECT-TYPE
+ SYNTAX Gauge
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current input frequency to the UPS system in tenths of Hz."
+ ::= { upsHighPrecInput 4 }
+
+
+upsHighPrecInputEnergyUsage OBJECT-TYPE
+ SYNTAX Unsigned32
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input energy usage of the UPS in hundredths of kWh."
+ ::= { upsHighPrecInput 5 }
+
+upsHighPrecInputBypassVoltage OBJECT-TYPE
+ SYNTAX Unsigned32
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current bypass line voltage in tenths of VAC."
+ ::= { upsHighPrecInput 6 }
+
+upsHighPrecInputBypassFrequency OBJECT-TYPE
+ SYNTAX Unsigned32
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current input bypass frequency to the UPS system in tenths of Hz."
+ ::= { upsHighPrecInput 7 }
+
+-- the upsBasicOutput group
+upsBasicOutputStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(1),
+ onLine(2),
+ onBattery(3),
+ onSmartBoost(4),
+ timedSleeping(5),
+ softwareBypass(6),
+ off(7),
+ rebooting(8),
+ switchedBypass(9),
+ hardwareFailureBypass(10),
+ sleepingUntilPowerReturn(11),
+ onSmartTrim(12),
+ ecoMode(13),
+ hotStandby(14),
+ onBatteryTest(15),
+ emergencyStaticBypass(16),
+ staticBypassStandby(17),
+ powerSavingMode(18),
+ spotMode(19),
+ eConversion(20),
+ chargerSpotmode(21),
+ inverterSpotmode(22),
+ activeLoad(23),
+ batteryDischargeSpotmode(24),
+ inverterStandby (25),
+ chargerOnly(26)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current state of the UPS. If the UPS is unable to
+ determine the state of the UPS this variable is set
+ to unknown(1).
+
+ During self-test most UPSes report onBattery(3) but
+ some that support it will report onBatteryTest(15).
+ To determine self-test status across all UPSes, refer
+ to the upsBasicStateOutputState OID."
+ ::= { upsBasicOutput 1 }
+
+upsBasicOutputPhase OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The actual number of output phases in a UPS"
+ ::= { upsBasicOutput 2 }
+
+upsBasicSystemStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(1),
+ onLine(2),
+ onBattery(3),
+ onSmartBoost(4),
+ timedSleeping(5),
+ softwareBypass(6),
+ off(7),
+ rebooting(8),
+ switchedBypass(9),
+ hardwareFailureBypass(10),
+ sleepingUntilPowerReturn(11),
+ onSmartTrim(12),
+ ecoMode(13),
+ inverter(14),
+ eConversion(15),
+ staticBypassStandby(16),
+ efficiencyBoosterMode(17)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Current state for the whole system (UPS and surrounding breakers).
+ If the UPS is unable to determine the state of the system, this
+ variable is set to unknown(1)."
+ ::= { upsBasicOutput 3 }
+
+upsBasicSystemInternalTemperature OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The actual internal temperature of the UPS system in Celsius."
+ ::= { upsBasicOutput 4 }
+
+
+ upsBasicSystemInverterStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(1),
+ ok(2),
+ inFaultCondition(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current state of the UPS inverter. If the UPS is unable
+ to determine the state of the inverter, this variable is set
+ to unknown(1)."
+ ::= { upsBasicOutput 5 }
+
+ upsBasicSystemPFCStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(1),
+ ok(2),
+ inFaultCondition(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The general status of the power factor correction (AC input stage
+ of the UPS). If the UPS is unable to determine the state of PFC,
+ this variable is set to unknown(1)."
+ ::= { upsBasicOutput 6 }
+
+ upsBasicOutputACwiringConfiguration OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(1),
+ noNeutralWiredonSystem(2),
+ neutralUsedforSupplyingLoad(3)
+
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates if neutral wire on output side of the UPS is
+ used (load wired line to neutral). If the UPS is unable to
+ determine the state of neutral, this variable is set to
+ unknown(1)."
+ ::= { upsBasicOutput 7 }
+
+
+
+-- the upsAdvOutput group
+
+upsAdvOutputVoltage OBJECT-TYPE
+ SYNTAX Gauge
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output voltage of the UPS system in VAC."
+ ::= { upsAdvOutput 1 }
+
+upsAdvOutputFrequency OBJECT-TYPE
+ SYNTAX Gauge
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current output frequency of the UPS system in Hz."
+ ::= { upsAdvOutput 2 }
+
+upsAdvOutputLoad OBJECT-TYPE
+ SYNTAX Gauge
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current UPS load expressed in percent
+ of rated capacity."
+ ::= { upsAdvOutput 3 }
+
+upsAdvOutputCurrent OBJECT-TYPE
+ SYNTAX Gauge
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current in amperes drawn by the load on the UPS."
+ ::= { upsAdvOutput 4 }
+
+upsAdvOutputRedundancy OBJECT-TYPE
+ SYNTAX Gauge
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of power modules which can fail or be
+ removed without causing the UPS to generate a Minimum
+ Redundancy Lost event."
+ ::= { upsAdvOutput 5 }
+
+upsAdvOutputKVACapacity OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum load that this UPS can support.
+ This value is dynamic for scalable 3-phase UPSs where power modules can be added for increased capacity.
+ The value indicates the actual available output capacity. For non-scalable 3-phase UPSs the value is
+ fixed to the UPS rating."
+ ::= { upsAdvOutput 6 }
+
+upsAdvOutputNominalFrequency OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The nominal output frequency of the UPS system in Hz."
+ ::= { upsAdvOutput 7 }
+
+upsAdvOutputActivePower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The total output active power of the UPS system in W.
+ The total active power is the sum of phase 1, phase 2 and
+ phase 3 power."
+ ::= { upsAdvOutput 8 }
+
+upsAdvOutputApparentPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The total output apparent power of all phases of the UPS system in VA."
+ ::= { upsAdvOutput 9 }
+
+
+ upsAdvOutputStatisticsTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsAdvOutputStatisticsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of input table entries. The number of entries
+ is given by the value of upsPhaseNumOutputs."
+ ::= { upsAdvOutput 10 }
+
+ upsAdvOutputStatisticsEntry OBJECT-TYPE
+ SYNTAX UpsAdvOutputStatisticsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular output."
+ INDEX { upsAdvOutputStatisticsIndex }
+ ::= { upsAdvOutputStatisticsTable 1 }
+
+ UpsAdvOutputStatisticsEntry ::= SEQUENCE {
+ upsAdvOutputStatisticsIndex INTEGER,
+ upsAdvOutputPeakCurrent INTEGER,
+ upsAdvOutputCurrentTHD INTEGER,
+ upsAdvOutputCrestFactor INTEGER
+
+ }
+
+ upsAdvOutputStatisticsIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output identifier."
+ ::= { upsAdvOutputStatisticsEntry 1 }
+
+ upsAdvOutputPeakCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output peak current in Amperes."
+ ::= { upsAdvOutputStatisticsEntry 2 }
+
+ upsAdvOutputCurrentTHD OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output current Total Harmonic Distortion in percent."
+ ::= { upsAdvOutputStatisticsEntry 3 }
+
+ upsAdvOutputCrestFactor OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output current crest factor expressed in tenths."
+ ::= { upsAdvOutputStatisticsEntry 4 }
+
+ upsAdvOutputNeutralCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The neutral current in amperes."
+ ::= { upsAdvOutput 11 }
+
+ upsAdvOutputEnergyUsage OBJECT-TYPE
+ SYNTAX Unsigned32
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ " The output energy usage of the UPS in kWh."
+ ::= { upsAdvOutput 12 }
+
+upsAdvOutputSourceSynchronization OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the synchronization source for the inverter output frequency.
+ 1. Main
+ 2. Internal
+ 3. External
+ 4. On AC Bypass.
+ 5. External / On Bypass
+ For other values it is unknown"
+ ::= { upsAdvOutput 13 }
+
+upsAdvOutputInverterFrequency OBJECT-TYPE
+ SYNTAX Gauge
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Output frequency in Hz measured at the output of inverter."
+ ::= { upsAdvOutput 14 }
+
+-- the upsHighPrecOutput group
+
+upsHighPrecOutputVoltage OBJECT-TYPE
+ SYNTAX Gauge
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output voltage of the UPS system in tenths of VAC."
+ ::= { upsHighPrecOutput 1 }
+
+upsHighPrecOutputFrequency OBJECT-TYPE
+ SYNTAX Gauge
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current output frequency of the UPS system in tenths of Hz."
+ ::= { upsHighPrecOutput 2 }
+
+upsHighPrecOutputLoad OBJECT-TYPE
+ SYNTAX Gauge
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current UPS load expressed in tenths of percent
+ of rated capacity."
+ ::= { upsHighPrecOutput 3 }
+
+upsHighPrecOutputCurrent OBJECT-TYPE
+ SYNTAX Gauge
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current in tenths of amperes drawn by the load on the UPS."
+ ::= { upsHighPrecOutput 4 }
+
+upsHighPrecOutputEfficiency OBJECT-TYPE
+ SYNTAX Integer32
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The positive values represent efficiency of the UPS in tenths of percent.
+ -1 If UPS supports this OID but the result is not available
+ -2 Load is too low to report efficiency
+ -3 Output off and efficiency is 0
+ -4 On battery, efficiency is not measured or calculated in this mode
+ -5 In Bypass, efficiency is not measured or calculated in this mode
+ -6 Battery charging, battery is charging and adversely affecting efficiency
+ -7 Poor AC input, the main input is outside the optimum efficiency range"
+ ::= { upsHighPrecOutput 5 }
+
+upsHighPrecOutputEnergyUsage OBJECT-TYPE
+ SYNTAX Unsigned32
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output energy usage of the UPS in hundredths of kWh."
+ ::= { upsHighPrecOutput 6 }
+
+-- the upsBasicConfig group
+
+upsBasicConfigNumDevices OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of devices that are plugged into the UPS.
+ This value is customer configurable from the device entry table"
+ ::= { upsBasicConfig 1 }
+
+upsBasicConfigDeviceTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsBasicConfigDeviceEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of devices that are plugged into the UPS.
+ The number of entries is given by the value of
+ upsBasicConfigNumDevices."
+ ::= { upsBasicConfig 2 }
+
+upsBasicConfigDeviceEntry OBJECT-TYPE
+ SYNTAX UpsBasicConfigDeviceEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The devices plugged in to the UPS."
+ INDEX { deviceIndex }
+ ::= { upsBasicConfigDeviceTable 1 }
+
+UpsBasicConfigDeviceEntry ::=
+ SEQUENCE {
+ deviceIndex
+ INTEGER,
+ deviceName
+ DisplayString,
+ vaRating
+ INTEGER,
+ acceptThisDevice
+ INTEGER
+ }
+
+deviceIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of the device that is plugged into the UPS."
+ ::= { upsBasicConfigDeviceEntry 1 }
+
+deviceName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The name/description of the device plugged into the UPS."
+ ::= { upsBasicConfigDeviceEntry 2 }
+
+vaRating OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The volt-amp rating of the device plugged into the UPS."
+ ::= { upsBasicConfigDeviceEntry 3 }
+
+acceptThisDevice OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes(1),
+ no(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "An entry is added if yes, the entry is deleted if no."
+ ::= { upsBasicConfigDeviceEntry 4 }
+
+
+
+
+-- the upsAdvConfig group
+
+upsAdvConfigRatedOutputVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The nominal output voltage from the UPS in VAC.
+
+ For a list of allowed values supported by your UPS model,
+ see the UPS User's Manual.
+
+ If a value other than a supported value is provided in a
+ set request, the UPS interprets it as the next lower
+ acceptable value. If the provided value is lower than
+ the lowest acceptable value, the lowest acceptable
+ value is used."
+ ::= { upsAdvConfig 1 }
+
+upsAdvConfigHighTransferVolt OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum line voltage in VAC allowed before the
+ UPS system transfers to battery backup.
+
+ For a list of allowed values supported by your UPS model,
+ see the UPS User's Manual.
+
+ If a value other than a supported value is provided in a
+ set request, the UPS interprets it as a the next higher
+ acceptable value. If the provided value is higher than
+ the highest acceptable value, the highest acceptable
+ value is used."
+ ::= { upsAdvConfig 2 }
+
+upsAdvConfigLowTransferVolt OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum line voltage in VAC allowed before the
+ UPS system transfers to battery backup.
+
+ For a list of allowed values supported by your UPS model,
+ see the UPS User's Manual.
+
+ If a value other than a supported value is provided in a
+ set request, the UPS interprets it as the next lower
+ acceptable value. If the provided value is lower than
+ the lowest acceptable value, the lowest acceptable
+ value is used."
+ ::= { upsAdvConfig 3 }
+
+upsAdvConfigAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ timed(1),
+ atLowBattery(2),
+ never(3),
+ mute(4)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A flag indicating how the UPS should handle audible
+ line fail alarms:
+ timed(1): UPS alarm will sound after a preset timed duration starting
+ from the line fail condition (see OID upsAdvConfigAlarmTimer for the
+ alarm timer value)
+ atLowBattery(2): UPS alarm will sound when the UPS has reached a Low
+ Battery condition during a line fail
+ never(3): Disables the UPS audible alarm
+ mute(4): Mutes the current alarm for some UPSs only when it is in an
+ alarm state and will return to the previously configured option when
+ the UPS recovers from the alarm condition"
+ ::= { upsAdvConfig 4 }
+
+upsAdvConfigAlarmTimer OBJECT-TYPE
+ SYNTAX TimeTicks
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The time after initial line failure at which the UPS
+ begins emitting audible alarms (beeping). This timer is
+ observed only if the value of extControlAlarm is timed(2).
+ Allowed values are 0 or 30 seconds.
+
+ If a value other than a supported value is provided in a
+ set request, the UPS interprets it as a the next lower
+ acceptable value. If the provided value is lower than
+ the lowest acceptable value, the lowest acceptable
+ value is used."
+ ::= { upsAdvConfig 5 }
+
+upsAdvConfigMinReturnCapacity OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum battery capacity required before the UPS will
+ return from a low battery shutdown condition. The capacity is
+ measured from 0% battery capacity (or Low Battery) as a percent
+ of full capacity (100%). In other words, the UPS will not re-energize
+ the output until the battery has charged so that its' capacity is equal
+ to this value.
+
+ For a list of allowed values supported by your UPS model,
+ see the UPS User's Manual.
+
+ If a value other than a supported value is provided in a
+ set request, the UPS interprets it as a the next higher
+ acceptable value. If the provided value is higher than
+ the highest acceptable value, the highest acceptable
+ value is used."
+ ::= { upsAdvConfig 6 }
+
+upsAdvConfigSensitivity OBJECT-TYPE
+ SYNTAX INTEGER {
+ auto(1),
+ low(2),
+ medium(3),
+ high(4)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The sensitivity of the UPS to utility line abnormalities
+ or noises."
+ ::= { upsAdvConfig 7 }
+
+upsAdvConfigLowBatteryRunTime OBJECT-TYPE
+ SYNTAX TimeTicks
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The desired run time of the UPS, in seconds, once the
+ low battery condition is reached. During this time the UPS will
+ produce a constant warning tone which can not be disabled.
+
+ For a list of allowed values supported by your UPS model,
+ see the UPS User's Manual.
+
+ If a value other than a supported value is provided in a set
+ request, the UPS interprets the value as the next higher
+ acceptable value. If the provided value is higher than the
+ highest acceptable value, the highest acceptable value is used."
+ ::= { upsAdvConfig 8 }
+
+upsAdvConfigReturnDelay OBJECT-TYPE
+ SYNTAX TimeTicks
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The delay in seconds after utility line power returns
+ before the UPS will turn on. This value is also used
+ when the UPS comes out of a reboot and before the UPS
+ wakes up from 'sleep' mode.
+
+ For a list of allowed values supported by your UPS model,
+ see the UPS User's Manual.
+
+ If a value other than a supported value is provided in a
+ set request, the UPS interprets it as a the next higher
+ acceptable value. If the provided value is higher than
+ the highest acceptable value, the highest acceptable
+ value is used."
+ ::= { upsAdvConfig 9 }
+
+upsAdvConfigShutoffDelay OBJECT-TYPE
+ SYNTAX TimeTicks
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The delay in seconds the UPS remains on after being told
+ to turn off.
+
+ For a list of allowed values supported by your UPS model,
+ see the UPS User's Manual.
+
+ If a value other than a supported value is provided in a
+ set request, the UPS interprets it as a the next higher
+ acceptable value. If the provided value is higher than
+ the highest acceptable value, the highest acceptable
+ value is used."
+ ::= { upsAdvConfig 10 }
+
+upsAdvConfigUpsSleepTime OBJECT-TYPE
+ SYNTAX TimeTicks
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The time in seconds for the UPS to go to 'sleep' when
+ instructed. When in sleep mode, the UPS will not provide
+ output power regardless of the input line state. Once the
+ specified time has elapsed, output power will be restored.
+
+ This is a configuration setting. The UPS will not go to
+ sleep until told to do so by the manager from a management
+ station.
+
+ Any input value is allowed, however the UPS only recognizes
+ 1/10 of an hour increments. The provided value will be
+ rounded to the closest 1/10 of an hour with one exception:
+ Any value entered between 1 and 540 seconds will be rounded
+ to 360 seconds (or 6 minutes)."
+ ::= { upsAdvConfig 11 }
+
+
+upsAdvConfigSetEEPROMDefaults OBJECT-TYPE
+ SYNTAX INTEGER {
+ noSetEEPROMDefaults(1),
+ setEEPROMDefaults(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "WRITE: Resets the UPS EEPROM variables to default values.
+ READ: returns 1"
+ ::= { upsAdvConfig 12 }
+
+upsAdvConfigDipSwitchTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsAdvConfigDipSwitchEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Current settings of UPS dip switches."
+ ::= { upsAdvConfig 13 }
+
+upsAdvConfigDipSwitchEntry OBJECT-TYPE
+ SYNTAX UpsAdvConfigDipSwitchEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The current setting of one dip switch."
+ INDEX { dipSwitchIndex }
+ ::= { upsAdvConfigDipSwitchTable 1 }
+
+UpsAdvConfigDipSwitchEntry ::=
+ SEQUENCE {
+ dipSwitchIndex
+ INTEGER,
+ dipSwitchStatus
+ INTEGER
+ }
+
+dipSwitchIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of a UPS dip switch."
+ ::= { upsAdvConfigDipSwitchEntry 1 }
+
+dipSwitchStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ on(1),
+ off(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The setting of a UPS dip switch."
+ ::= { upsAdvConfigDipSwitchEntry 2 }
+
+upsAdvConfigBattExhaustThresh OBJECT-TYPE
+ SYNTAX TimeTicks
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The number of seconds prior to battery exhaustion when the
+ UPS will switch off power to its load."
+ ::= { upsAdvConfig 14 }
+
+upsAdvConfigPassword OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The password entered at the UPS front panel to enable local
+ configuration of the EEProm. If the password is disabled or
+ is not supported, then the agent returns a null string."
+ ::= { upsAdvConfig 15 }
+
+upsAdvConfigAllowedSetTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsAdvConfigAllowedSetEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The table listing the allowed values for all discrete
+ configurable UPS variables."
+ ::= { upsAdvConfig 16 }
+
+upsAdvConfigAllowedSetEntry OBJECT-TYPE
+ SYNTAX UpsAdvConfigAllowedSetEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The table entry for a configurable UPS variable."
+ INDEX { apcUpsConfigFieldIndex }
+ ::= { upsAdvConfigAllowedSetTable 1 }
+
+UpsAdvConfigAllowedSetEntry ::= SEQUENCE {
+ apcUpsConfigFieldIndex INTEGER,
+ apcUpsConfigFieldOID OBJECT IDENTIFIER,
+ apcUpsConfigFieldValueRange DisplayString
+ }
+
+apcUpsConfigFieldIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to an eeprom field entry."
+ ::= { upsAdvConfigAllowedSetEntry 1 }
+
+apcUpsConfigFieldOID OBJECT-TYPE
+ SYNTAX OBJECT IDENTIFIER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The OID of the current configurable value."
+ ::= { upsAdvConfigAllowedSetEntry 2 }
+
+apcUpsConfigFieldValueRange OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The discrete set of allowed values of a configurable
+ register. Individual values are delimited by a comma."
+ ::= { upsAdvConfigAllowedSetEntry 3 }
+
+upsAdvConfigBattCabAmpHour OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Configure the amp-hour setting of the UPS battery solution.
+ The value shows the maximum battery capacity configured for the UPS when using a third party battery solution
+ regardless of the breaker positions. The actual available battery capacity based on breaker positions or
+ connected/disconnected battery strings, is presented in OID upsAdvBatteryTotalCapacity"
+ ::= { upsAdvConfig 17 }
+
+upsAdvConfigPositionSelector OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ rack (2),
+ tower (3)
+ }
+
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Configure UPS position selector. If the UPS doesn't
+ support this configuration it will report unknown (1).
+ The positions are either rack (2) for rack mounted or
+ tower (3) for tower unit."
+ ::= { upsAdvConfig 18 }
+
+upsAdvConfigOutputFreqRange OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ freqRangeAUTO (2),
+ freqRange60Var1 (3),
+ freqRange60Var3 (4),
+ freqRange50Var1 (5),
+ freqRange50Var3 (6),
+ freqRange60Var10 (7),
+ freqRange50Var10 (8),
+ freqRange60Var1dot0 (9),
+ freqRange50Var1dot0 (10),
+ freqRange50Pct0dot5 (11),
+ freqRange50Pct1 (12),
+ freqRange50Pct2 (13),
+ freqRange50Pct4 (14),
+ freqRange50Pct6 (15),
+ freqRange50Pct8 (16),
+ freqRange60Pct0dot5 (17),
+ freqRange60Pct1 (18),
+ freqRange60Pct2 (19),
+ freqRange60Pct4 (20),
+ freqRange60Pct6 (21),
+ freqRange60Pct8 (22)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Configure the output frequency tolerance range.
+ unknown(1) indicates the output frequency is unknown.
+ freqRangeAUTO(2) configure the output frequency range for automatic.
+ freqRange60Var1(3) configure the output frequency range for 60 +/- 0.1 Hz
+ freqRange60Var3(4) configure the output frequency range for 60 +/- 3.0 Hz
+ freqRange50Var1(5) configure the output frequency range for 50 +/- 0.1 Hz
+ freqRange50Var3(6) configure the output frequency range for 50 +/- 3.0 Hz
+ freqRange60Var10(7) configure the output frequency range for 60 +/- 10 Hz
+ freqRange50Var10(8) configure the output frequency range for 50 +/- 10 Hz
+ freqRange60Var1dot0(9) configure the output frequency range for 60 +/- 1.0 Hz
+ freqRange50Var1dot0(10) configure the output frequency range for 50 +/- 1.0 Hz
+ freqRange50Pct0dot5(11) configure the output frequency range for 50 Hz +/- 0.5 %
+ freqRange50Pct1(12) configure the output frequency range for 50 Hz +/- 1.0 %
+ freqRange50Pct2(13) configure the output frequency range for 50 Hz +/- 2.0 %
+ freqRange50Pct4(14) configure the output frequency range for 50 Hz +/- 4.0 %
+ freqRange50Pct6(15) configure the output frequency range for 50 Hz +/- 6.0 %
+ freqRange50Pct8(16) configure the output frequency range for 50 Hz +/- 8.0 %
+ freqRange60Pct0dot5(17) configure the output frequency range for 60 Hz +/- 0.5 %
+ freqRange60Pct1(18) configure the output frequency range for 60 Hz +/- 1.0 %
+ freqRange60Pct2(19) configure the output frequency range for 60 Hz +/- 2.0 %
+ freqRange60Pct4(20) configure the output frequency range for 60 Hz +/- 4.0 %
+ freqRange60Pct6(21) configure the output frequency range for 60 Hz +/- 6.0 %
+ freqRange60Pct8(22) configure the output frequency range for 60 Hz +/- 8.0 %
+ For a list of allowed values and conditions when variable can be set by your UPS model,
+ see the UPS User's Manual."
+ ::= { upsAdvConfig 19 }
+
+upsAdvConfigUPSFail OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ gotoBypass (2),
+ dropLoad (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Configure the UPS fail action. If UPS fails,
+ and frequency or voltage is out of range it will either
+ GotoBypass (2) or DropLoad (3). This OID will report
+ unknown (1) if it is not supported feature or option."
+ ::= { upsAdvConfig 20 }
+
+upsAdvConfigAlarmRedundancy OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Configure settings of UPS alarm if the redundancy is
+ under the current redundancy. Use 0 for never."
+ ::= { upsAdvConfig 21 }
+
+upsAdvConfigAlarmLoadOver OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Configure settings of UPS alarm if the load is
+ over the current load in kVA. Use -1 for never."
+ ::= { upsAdvConfig 22 }
+
+upsAdvConfigAlarmRuntimeUnder OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Configure settings of UPS alarm if the runtime is
+ under the current time of minutes. Use -1 for never."
+ ::= { upsAdvConfig 23 }
+
+upsAdvConfigVoutReporting OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ voutAUTO (2),
+ vout208 (3),
+ vout240 (4)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Configure the way the UPS scales its output voltage readings.
+ unknown(1) indicates the Vout Reporting is unknown.
+ voutAUTO(2) configure the Vout Reporting for automatic scaling.
+ vout208(3) configure the Vout Reporting for 208 Volts.
+ vout240(4) configure the Vout Reporting for 240 Volts."
+ ::= { upsAdvConfig 24 }
+
+upsAdvConfigNumExternalBatteries OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Configure the number of external batteries connected to the UPS."
+ ::= { upsAdvConfig 25 }
+
+upsAdvConfigSimpleSignalShutdowns OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Configure Simple Signal shutdown commands from the Simple Signal
+ port to be issued to the UPS.
+ unknown(1) indicates the Simple Signal Shutdown setting is unknown.
+ disabled(2) configure to disable Simple Signal Shutdowns.
+ enabled(3) configure to enable Simple Signal Shutdowns."
+ ::= { upsAdvConfig 26 }
+
+upsAdvConfigMaxShutdownTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum amount of time for server shutdown to complete before a
+ UPS shutdown occurs."
+ ::= { upsAdvConfig 27 }
+
+upsAsiUpsControlServerRequestShutdown OBJECT-TYPE
+ SYNTAX INTEGER {
+ serverShutdownOff (1),
+ serverShutdownReboot (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Start a server shutdown sequence:
+ serverShutdownOff: Shutdown server and turn off UPS
+ serverShutdownReboot: Shutdown server and turn reboot UPS."
+ ::= { upsAdvConfig 28 }
+
+upsAdvConfigMinReturnRuntime OBJECT-TYPE
+ SYNTAX TimeTicks
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum amount of run time in seconds required before the output will be
+ turned on, using power calculation captured at start of last shutdown."
+ ::= { upsAdvConfig 29 }
+
+upsAdvConfigBasicSignalLowBatteryDuration OBJECT-TYPE
+ SYNTAX TimeTicks
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The duration of runtime in seconds during an on-battery condition at which
+ the UPS will signal the basic low battery shutdown condition."
+ ::= { upsAdvConfig 30 }
+
+upsAdvConfigBypassPhaseLockRequired OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Sets the condition for when bypass is an acceptable mode of operation as a
+ requirement."
+ ::= { upsAdvConfig 31 }
+
+upsAdvConfigOutputFreqSlewRate OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ slewRateQuarterHzPerSec (2),
+ slewRateHalfHzPerSec (3),
+ slewRate1HzPerSec (4),
+ slewRate2HzPerSec (5),
+ slewRate4HzPerSec (6),
+ slewRate6HzPerSec (7)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The rate at which the UPS will change its output frequency
+ in response to utility frequency changes."
+ ::= { upsAdvConfig 32 }
+
+upsAdvConfigChargerLevel OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ low (2),
+ high (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Sets the rate at which the UPS charges its batteries."
+ ::= { upsAdvConfig 33 }
+
+upsAdvConfigBypassToleranceSetting OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ wide (2),
+ medium (3),
+ narrow (4),
+ custom (5)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "This setting allows selecting from standard bypass tolerance configurations to suit their situation."
+ ::= { upsAdvConfig 34 }
+
+upsAdvConfigMainsSetting OBJECT-TYPE
+ SYNTAX INTEGER {
+ singleInput (1),
+ dualInput (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Configure the type of mains supply system.
+ singleInput (1) indicates a single supply system.
+ dualInput (2) indicates a dual supply system. "
+ ::= { upsAdvConfig 35 }
+
+upsAdvConfigACWiringSetting OBJECT-TYPE
+ SYNTAX INTEGER {
+ threeWire (1),
+ fourWire (2),
+ fourWireHRG (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Configure the AC wiring of the system.
+ threeWire (1) indicates 3-wire system configuration.
+ fourWire (2) indicates 4-wire system configuration.
+ fourWireHRG (3) indicates a 4-wire High resistive Grounding system."
+ ::= { upsAdvConfig 36 }
+
+upsAdvConfigUpperOutputVoltTolerance OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Upper tolerance of the output RMS voltage before transferring to bypass.
+ Expressed as percent of nominal voltage."
+ ::= { upsAdvConfig 37 }
+
+upsAdvConfigLowerOutputVoltTolerance OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Lower tolerance of the output RMS voltage before transferring to bypass.
+ Expressed as percent of nominal voltage."
+ ::= { upsAdvConfig 38 }
+
+upsAdvConfigUpperBypassVoltTolerance OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Upper tolerance of the bypass voltage that allows transfer to bypass by user.
+ Expressed as percent of nominal voltage."
+ ::= { upsAdvConfig 39 }
+
+upsAdvConfigLowerBypassVoltTolerance OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Lower tolerance of the bypass voltage that allows transfer to bypass by user.
+ Expressed as percent of nominal voltage."
+ ::= { upsAdvConfig 40 }
+
+upsAdvConfigOutofSyncBypassTransferDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Configure the time (in milliseconds), indicating the gap in output voltage
+ if an asynchronous transfer to bypass needs to occur."
+ ::= { upsAdvConfig 41 }
+
+
+
+
+upsAdvConfigWarningAlarmDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Configure the time delay for reporting warning alarms
+ (in seconds)."
+ ::= { upsAdvConfig 43 }
+
+upsAdvConfigInformationalAlarmDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Configure the time delay for reporting informational alarms
+ (in seconds)."
+ ::= { upsAdvConfig 44 }
+
+upsAdvConfigGreenMode OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable/Disable UPS green mode feature."
+ ::= { upsAdvConfig 45 }
+
+upsAdvConfigLCDLocalLanguage OBJECT-TYPE
+ SYNTAX INTEGER {
+ english (1),
+ french (2),
+ italian (3),
+ german (4),
+ spanish (5),
+ portuguese (6),
+ japanese (7)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Configure the language setting of the UPS LCD display information."
+ ::= { upsAdvConfig 46 }
+
+upsAdvConfigLCDLockOut OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable/Disable the control function of the UPS via the LCD Display."
+ ::= { upsAdvConfig 47 }
+
+upsAdvConfigChargerRate OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Change the maximum allowed UPS charge rate on select products where 100% represents
+ the manufacturer's recommended rate. A charge/discharge rate of C/10 for a 10 Ah
+ battery would be 1 where C is defined as the charge or discharge rate equal to the
+ capacity of a battery divided by 1 hour. To increase the charge rate by a factor of
+ 2 to C/5, this oid would be set to 200%. This number would not change when external
+ packs are added or removed. Charging at too high a rate can result in boiling and/or
+ venting of electrolyte and/or high gas pressure."
+ ::= { upsAdvConfig 48 }
+
+upsAdvConfigBatterySelection OBJECT-TYPE
+ SYNTAX INTEGER {
+ vrla (1),
+ ventedcell (2),
+ nicd (3),
+ li-ion(4)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Configure the installed battery type; VRLA is a Valve Regulated
+ Lead Acid type battery, Vented Cell is a wet cell type (car) battery, NiCd is a
+ Nickel-Cadmium type battery, and Li-Ion is Lithium Ion type battery.
+ Please use the OID defined under upsIdent: upsAdvEnergyStorageType"
+ ::= { upsAdvConfig 49 }
+
+upsAdvConfigBatteryHealthAlarmWarningTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Configure the number of days before the battery health is depleted that the battery
+ health alarm is activated. Setting this to -1, if supported by the UPS, will suppress
+ the battery health alarm."
+ ::= { upsAdvConfig 50 }
+
+upsAdvConfigBatteryHealthAlarmSleepTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Configure the number of days that the UPS's battery health alarm should sleep before
+ being activated again after being acknowledged. Setting this to -1, if supported by the
+ UPS, displays no other alarms after the first alarm is acknowledged."
+ ::= { upsAdvConfig 51 }
+
+upsAdvConfigSignalFlashVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Configure the signal flash voltage in tenths of volts."
+ ::= { upsAdvConfig 52 }
+
+upsAdvConfigBatteryTemperatureCompensation OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Configure the battery temperature compensation voltage in
+ hundreds of volts per degree C. On products which support this
+ field, the charger voltage is reduced for each degree C rise
+ by the value configured in this setting multiplied by the
+ number of battery cells attached to the UPS."
+ ::= { upsAdvConfig 53 }
+
+upsAdvConfigBatteryChargerType OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "This OID describes type of battery charger used: standard or extended.
+ 1 - Internal charger,
+ 2 - Extended (CLA),
+ 3 - Large extension (other cases),
+ 4 - Extra large extension (XL),
+ 5 - Double extra large extension (XXL)
+ For other numbers charger type is unknown"
+ ::= { upsAdvConfig 54 }
+
+upsAdvConfigAutomaticRestart OBJECT-TYPE
+ SYNTAX INTEGER {
+ enabled (1),
+ disabled (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates whether Automatic Restart is enabled or disabled."
+ ::= { upsAdvConfig 55 }
+
+upsAdvConfigDeepDischargeProtection OBJECT-TYPE
+ SYNTAX INTEGER {
+ enabled (1),
+ disabled (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates whether protection against deep discharge is enabled or disabled."
+ ::= { upsAdvConfig 56 }
+
+upsAdvConfigFreqBypassTransferRange OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Tolerance of bypass AC frequency to switch on bypass. The frequency must be in
+ range of -X% to +X% around the nominal value."
+ ::= { upsAdvConfig 57 }
+
+upsAdvConfigUpsPowerconverterType OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "This value indicates the type of UPS in terms of output phase and redundancy.
+ 2 - Galaxy 7000 Unitary 3:3
+ 3 - Galaxy 7000 Redundant 3:3
+ 4 - Galaxy 7000 Parallel SSC 3:3
+ 6 - Galaxy 7000 SSC 3:3
+ 10 - Galaxy 300 Unitary 3:3
+ 11 - Galaxy 300 Unitary 3:1
+ 12 - Galaxy 300 Redundant 3:3
+ 13 - Galaxy 300 Redundant 3:1
+ 14 - Galaxy 5000/5500 Unitary
+ 15 - Galaxy 5000/5500 Parallel
+ 16 - Galaxy 5000/5500 Unitary Frequency Converter
+ 17 - Galaxy 5000/5500 Parallel Frequency Converter
+ For other values UPS is unknown. "
+ ::= { upsAdvConfig 58 }
+
+upsAdvConfigFrequencyConverterMode OBJECT-TYPE
+ SYNTAX INTEGER {
+ autoRanging (1),
+ frequencyConverter (2),
+ unknown (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates whether the output frequency is in Auto Ranging or Frequency converter mode.
+ In Auto Ranging mode the inverter provides output frequency in the same range as the input.
+ In Frequency converter mode it is possible to have 50Hz input and 60 Hz output and vice versa."
+ ::= { upsAdvConfig 59 }
+
+upsAdvConfigACQualificationTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The time in seconds that the voltage is required to be in the acceptable range before being declared to be acceptable."
+ ::= { upsAdvConfig 60 }
+
+ -- the upsSyncCtrlGroupConfig group
+
+upsSCGMembershipGroupNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The SCG Membership Group number (MGN) is a 16-bit number allowing
+ up to 65534 separate groups that can be identified and distinguished
+ per IP subnet. Zero and 65535 are not used. The MGN is used in all
+ communication between members of the SCG and a Network Management Card
+ (NMC) will listen and only respond to commands sent to it using its
+ configured SCG ID."
+ ::= { upsSyncCtrlGroupConfig 1 }
+
+upsSCGActiveMembershipStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ enabledSCG (1),
+ disabledSCG (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Membership in the configured SCG can be enabled and
+ disabled. If an NMC is configured for an SCG, but
+ has its membership disabled, all synchronized control commands
+ received will be ignored."
+ ::= { upsSyncCtrlGroupConfig 2 }
+
+upsSCGPowerSynchronizationDelayTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The Power Synchronization Delay Time (PSD) setting is the maximum
+ number of seconds an SCG Initiator will wait for all SCG members to
+ recover utility power before completing the reboot sequence of a
+ reboot or sleep command. If all SCG members are ready to proceed,
+ no additional delay is introduced."
+ ::= { upsSyncCtrlGroupConfig 3 }
+
+upsSCGReturnBatteryCapacityOffset OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A reboot command uses the Initiator's Return battery Capacity (RBC) to control
+ when the SCG completes this operation. In a Normal Control Operation (NCC) the
+ UPS will only complete the reboot if RBC is reached. Due to normal battery
+ charge rate variations it may be desirable for the Followers to complete the
+ reboot if they are within some range of the Initiator's RBC when the Initiator
+ is prepared (charged to RBC) to complete the reboot. The Return Battery
+ Capacity Offset (RBCO) defines a percent battery capacity subtracted from an
+ RBC above which a Follower's battery must be charged for it to complete a
+ reboot. For example, if the Initiator's RBC is 50% and the Initiator's RBCO is
+ 5% then a Follower's battery capacity is within range if it is greater or equal
+ to 45% (50% - 5%) at the time when the Initiator tries to complete the reboot
+ command. The default RBCO is 10%. "
+ ::= { upsSyncCtrlGroupConfig 4 }
+
+upsSCGMultiCastIP OBJECT-TYPE
+ SYNTAX IpAddress
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The MultiCast IP address of the SCG Group."
+ ::= { upsSyncCtrlGroupConfig 5 }
+
+
+-- the upsSyncCtrlGroupStatus group
+
+upsSCGNumOfGroupMembers OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of active, communicating members in the Sync Control Group (SCG).
+ This variable indicates the number of rows in the SCG Status Table."
+ ::= { upsSyncCtrlGroupStatus 1 }
+
+-- Sync Control Group Status Table
+
+upsSCGStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsSCGStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of SCG status table entries. The number of entries
+ is given by the value of upsSCGNumOfGroupMembers."
+ ::= { upsSyncCtrlGroupStatus 2 }
+
+ upsSCGStatusEntry OBJECT-TYPE
+ SYNTAX UpsSCGStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular SCG Member."
+ INDEX { upsSCGStatusTableIndex }
+ ::= { upsSCGStatusTable 1 }
+
+ UpsSCGStatusEntry ::= SEQUENCE {
+ upsSCGStatusTableIndex INTEGER,
+ upsSCGMemberIP IpAddress,
+ upsSCGACInputStatus INTEGER,
+ upsSCGACOutputStatus INTEGER
+ }
+
+ upsSCGStatusTableIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of a status entry for an active, communicating SCG member."
+ ::= { upsSCGStatusEntry 1 }
+
+ upsSCGMemberIP OBJECT-TYPE
+ SYNTAX IpAddress
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The IP address of an active, communicating SCG Member."
+ ::= { upsSCGStatusEntry 2 }
+
+ upsSCGACInputStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ acInGood(1),
+ acInBad(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID indicates the AC Input Status of the SCG Member.
+ acInGood(1) indicates the AC Input is within tolerance.
+ acInBad(2) indicates the AC Input is not within tolerance."
+ ::= { upsSCGStatusEntry 3 }
+
+ upsSCGACOutputStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ acOutOn(1),
+ acOutOff(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID indicates the AC Output Status of the SCG Member.
+ acOutOn(1) indicates the UPS output is providing power to the load.
+ acOutOff(2) indicates the UPS output is not providing power to the load. "
+ ::= { upsSCGStatusEntry 4 }
+
+-- the upsBasicState group
+
+
+upsBasicStateOutputState OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An ASCII string containing the 64 flags representing
+ the current state(s) of the UPS. If the Network Card
+ is unable to determine the state of the UPS, this
+ variable is set to 'UNKNOWN'.
+
+ The flags are numbered 1 to 64, read from left to
+ right. The flags are defined as follows:
+
+ Flag 1: Abnormal Condition Present
+ Flag 2: On Battery
+ Flag 3: Low Battery
+ Flag 4: On Line
+
+ Flag 5: Replace Battery
+ Flag 6: Serial Communication Established
+ Flag 7: AVR Boost Active
+ Flag 8: AVR Trim Active
+
+ Flag 9: Overload
+ Flag 10: Runtime Calibration
+ Flag 11: Batteries Discharged
+ Flag 12: Manual Bypass
+
+ Flag 13: Software Bypass
+ Flag 14: In Bypass due to Internal Fault
+ Flag 15: In Bypass due to Supply Failure
+ Flag 16: In Bypass due to Fan Failure
+
+ Flag 17: Sleeping on a Timer
+ Flag 18: Sleeping until Utility Power Returns
+ Flag 19: On
+ Flag 20: Rebooting
+
+ Flag 21: Battery Communication Lost
+ Flag 22: Graceful Shutdown Initiated
+ Flag 23: Smart Boost or Smart Trim Fault
+ Flag 24: Bad Output Voltage
+
+ Flag 25: Battery Charger Failure
+ Flag 26: High Battery Temperature
+ Flag 27: Warning Battery Temperature
+ Flag 28: Critical Battery Temperature
+
+ Flag 29: Self Test In Progress
+ Flag 30: Low Battery / On Battery
+ Flag 31: Graceful Shutdown Issued by Upstream Device
+ Flag 32: Graceful Shutdown Issued by Downstream Device
+
+ Flag 33: No Batteries Attached
+ Flag 34: Synchronized Command is in Progress
+ Flag 35: Synchronized Sleeping Command is in Progress
+ Flag 36: Synchronized Rebooting Command is in Progress
+
+ Flag 37: Inverter DC Imbalance
+ Flag 38: Transfer Relay Failure
+ Flag 39: Shutdown or Unable to Transfer
+ Flag 40: Low Battery Shutdown
+
+ Flag 41: Electronic Unit Fan Failure
+ Flag 42: Main Relay Failure
+ Flag 43: Bypass Relay Failure
+ Flag 44: Temporary Bypass
+
+ Flag 45: High Internal Temperature
+ Flag 46: Battery Temperature Sensor Fault
+ Flag 47: Input Out of Range for Bypass
+ Flag 48: DC Bus Overvoltage
+
+ Flag 49: PFC Failure
+ Flag 50: Critical Hardware Fault
+ Flag 51: Green Mode/ECO Mode
+ Flag 52: Hot Standby
+
+ Flag 53: Emergency Power Off (EPO) Activated
+ Flag 54: Load Alarm Violation
+ Flag 55: Bypass Phase Fault
+ Flag 56: UPS Internal Communication Failure
+
+ Flag 57: Efficiency Booster Mode
+ Flag 58: Off
+ Flag 59: Standby
+ Flag 60: Minor or Environment Alarm
+
+ Flag 61: <Not Used>
+ Flag 62: <Not Used>
+ Flag 63: <Not Used>
+ Flag 64: <Not Used>"
+ ::= { upsBasicState 1 }
+
+upsBasicStateAlarmStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ noAlarms (1),
+ infoAlarm (2),
+ warningAlarm (3),
+ criticalAlarm (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The alarm status of the Power Module.
+ noAlarms(1) indicates the device has no alarms present.
+ infoAlarm (2) indicates the device has alarms and the
+ highest severity of the alarms present is infomational.
+ warningAlarm (3) indicates the device has alarms and the
+ highest severity of the alarms present is warning.
+ criticalAlarm (4) indicates the device has alarms and the
+ highest severity of the alarms present is critical."
+ ::= { upsBasicState 2 }
+
+
+-- the upsAdvState group
+
+upsAdvStateAbnormalConditions OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An ASCII string containing the 32 flags representing
+ the current active UPS faults. If the Network Card
+ is unable to determine the values of the flags, this
+ variable is set to 'UNKNOWN'. If this variable is not
+ supported by the connected UPS, this variable is set to
+ 'NOT SUPPORTED'.
+
+ The flags are numbered from 1 to 32, and read from left to
+ right. The flags are defined as follows:
+
+ Flag 1: Power Module Failure
+ Flag 2: Main Intelligence Module Failure
+ Flag 3: Redundant Intelligence Module Failure
+ Flag 4: Battery Failure
+
+ Flag 5: Load(kVA) Alarm Threshold Violation
+ Flag 6: Redundancy Lost
+ Flag 7: Redundancy Below Alarm Threshold
+ Flag 8: Bypass not in Range; Either Frequency or Voltage
+
+ Flag 9: Bypass Contactor Stuck in Bypass Condition
+ Flag 10: Bypass Contactor Stuck in On-Line Condition
+ Flag 11: In Bypass due to an Internal Fault
+ Flag 12: In Bypass due to an Overload
+
+ Flag 13: In Maintenance Bypass
+ Flag 14: Input Circuit Braker Tripped Open
+ Flag 15: System Level Fan Failure
+ Flag 16: Redundant Intelligent Module in Control
+
+ Flag 17: IIC Inter-Module Communication Failure
+ Flag 18: No Working Power Modules
+ Flag 19: Load Shutdown From Bypass; Input Frequency
+ Flag 20: Runtime Below Alarm Threshold
+
+ Flag 21: Extended Run Frame Fault
+ Flag 22: Output Voltage out of Range
+ Flag 23: UPS Not Synchronized
+ Flag 24: No Batteries Installed
+
+ Flag 25: Battery Voltage High
+ Flag 26: UPS Specific Fault Detected
+ Flag 27: Site Wiring Fault
+ Flag 28: Backfeed Protection Relay Opened
+
+ Flag 29: <Not Used>
+ Flag 30: <Not Used>
+ Flag 31: <Not Used>
+ Flag 32: <Not Used>"
+ ::= { upsAdvState 1 }
+
+upsAdvStateSymmetra3PhaseSpecificFaults OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An ASCII string containing the 64 flags representing
+ the current active UPS specific faults for the Symmetra
+ 3-Phase UPS models. If the Network Card is unable to
+ determine the values of the flags, this variable is set
+ to 'UNKNOWN'. If the connected UPS does not use this
+ variable, it is set to 'NOT SUPPORTED'.
+
+ The flags are numbered from 1 to 64, and read from left
+ to right. The bits are defined as follows:
+
+ Flag 1: External Switch Gear Failure
+ Flag 2: External Transformer Over Temperature
+ Flag 3: External DC Circuit Breaker Tripped
+ Flag 4: System Power Supply Failure
+
+ Flag 5: Battery Monitor Card Failure
+ Flag 6: Battery Monitor Card Removed
+ Flag 7: XR Communication Card Failure
+ Flag 8: XR Communication Card Removed
+
+ Flag 9: External Switch Gear Monitoring Card Failure
+ Flag 10: External Switch Gear Monitoring Card Removed
+ Flag 11: Internal DC Circuit Breaker Tripped
+ Flag 12: Static Bypass Switch Failure
+
+ Flag 13: System EEPROM Removed
+ Flag 14: System EEPROM Failure
+ Flag 15: UPS in Forced Bypass
+ Flag 16: Static Bypass Switch Module Removed
+
+ Flag 17: System Start-Up Configuration Fault
+ Flag 18: Battery Charger Shutdown Externally
+ Flag 19: <Not Used>
+ Flag 20: <Not Used>
+
+ Flag 21: <Not Used>
+ Flag 22: <Not Used>
+ Flag 23: <Not Used>
+ Flag 24: <Not Used>
+
+ Flag 25: <Not Used>
+ Flag 26: <Not Used>
+ Flag 27: <Not Used>
+ Flag 28: <Not Used>
+
+ Flag 29: <Not Used>
+ Flag 30: <Not Used>
+ Flag 31: <Not Used>
+ Flag 32: <Not Used>
+
+ Flag 33: <Not Used>
+ Flag 34: <Not Used>
+ Flag 35: <Not Used>
+ Flag 36: <Not Used>
+
+ Flag 37: <Not Used>
+ Flag 38: <Not Used>
+ Flag 39: <Not Used>
+ Flag 40: <Not Used>
+
+ Flag 41: <Not Used>
+ Flag 42: <Not Used>
+ Flag 43: <Not Used>
+ Flag 44: <Not Used>
+
+ Flag 45: <Not Used>
+ Flag 46: <Not Used>
+ Flag 47: <Not Used>
+ Flag 48: <Not Used>
+
+ Flag 49: <Not Used>
+ Flag 50: <Not Used>
+ Flag 51: <Not Used>
+ Flag 52: <Not Used>
+
+ Flag 53: <Not Used>
+ Flag 54: <Not Used>
+ Flag 55: <Not Used>
+ Flag 56: <Not Used>
+
+ Flag 57: <Not Used>
+ Flag 58: <Not Used>
+ Flag 59: <Not Used>
+ Flag 60: <Not Used>
+
+ Flag 61: <Not Used>
+ Flag 62: <Not Used>
+ Flag 63: <Not Used>
+ Flag 64: <Not Used>"
+ ::= { upsAdvState 2 }
+
+upsAdvStateDP300ESpecificFaults OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An ASCII string containing the 64 flags representing
+ the current active UPS specific faults for the Silcon
+ DP300E UPS models. If the Network Card is unable to
+ determine the values of the flags, this variable is set
+ to 'UNKNOWN'. If the connected UPS does not use this
+ variable, it is set to 'NOT SUPPORTED'.
+
+ The flags are numbered from 1 to 64, and read from left
+ to right. The bits are defined as follows:
+
+ Flag 1: Peak Current Limiter Active
+ Flag 2: Bypass Power Supply Fault
+ Flag 3: Delta Current Limiter Active
+ Flag 4: Fan Fault
+
+ Flag 5: High DC warning
+ Flag 6: Inverter Voltage Error
+ Flag 7: Parallel Synchronization Error
+ Flag 8: Second Power Supply Fault
+
+ Flag 9: Internal Power Supply Fault
+ Flag 10: <Not Used>
+ Flag 11: <Not Used>
+ Flag 12: <Not Used>
+
+ Flag 13: <Not Used>
+ Flag 14: Bypass Static Switch High Temperature
+ Flag 15: High Battery Temperature
+ Flag 16: Battery Weak
+
+ Flag 17: <Not Used>
+ Flag 18: System Locked in Operation Mode
+ Flag 19: RAM1 Memory Write Error
+ Flag 20: Memory Write Error
+
+ Flag 21: Communication to VQ Bypass Lost
+ Flag 22: Communication to VQ Output Lost
+ Flag 23: Communication to DMU Lost
+ Flag 24: Communication to Controller Lost
+
+ Flag 25: Communication to Parallel IF Lost
+ Flag 26: External Shutdown Accepted
+ Flag 27: DC Capacitor Charge Error
+ Flag 28: Communication to VQ Mains Lost
+
+ Flag 29: Bypass Synchronization Error
+ Flag 30: Charge Error
+ Flag 31: SII Aux Input Activiated
+ Flag 32: <Not Used>
+
+ Flag 33: Blown Inverter Fuse
+ Flag 34: Blown Rectifier Fuse
+ Flag 35: Auxilliary 1 Fault
+ Flag 36: <Not Used>
+
+ Flag 37: <Not Used>
+ Flag 38: <Not Used>
+ Flag 39: <Not Used>
+ Flag 40: <Not Used>
+
+ Flag 41: <Not Used>
+ Flag 42: <Not Used>
+ Flag 43: <Not Used>
+ Flag 44: <Not Used>
+
+ Flag 45: <Not Used>
+ Flag 46: High Temperature Charger Magnetic
+ Flag 47: <Not Used>
+ Flag 48: Battery Monitor Warning
+
+ Flag 49: Battery Monitor Alarm
+ Flag 50: <Not Used>
+ Flag 51: <Not Used>
+ Flag 52: <Not Used>
+
+ Flag 53: TSM 1/2/3 Temperature Shutdown
+ Flag 54: Charger 0/30 Temperature Warning
+ Flag 55: Charger 0/30 Temperature Shutdown
+ Flag 56: High Output Voltage
+
+ Flag 57: SSW Temperature Over 90
+ Flag 58: <Not Used>
+ Flag 59: Low Current Failure In AC Capacitors
+ Flag 60: <Not Used>
+
+ Flag 61: Advanced Battery Management Not Installed
+ Flag 62: <Not Used>
+ Flag 63: <Not Used>
+ Flag 64: <Not Used>"
+ ::= { upsAdvState 3 }
+
+upsAdvStateSymmetraSpecificFaults OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An ASCII string containing the 64 flags representing
+ the current active UPS specific faults for the Symmetra
+ UPS models. If the Network Card is unable to determine
+ the values of the flags, this variable is set to 'UNKNOWN'.
+ If the connected UPS does not use this variable, it is
+ set to 'NOT SUPPORTED'.
+
+ The flags are numbered from 1 to 64, and read from left
+ to right. The bits are defined as follows:
+
+ Flag 1: System Fault
+ Flag 2: Bypass Relay Fault
+ Flag 3: Power Module Turn Off Failure
+ Flag 4: Frame Identification Fault
+
+ Flag 5: <Not Used>
+ Flag 6: <Not Used>
+ Flag 7: <Not Used>
+ Flag 8: <Not Used>
+
+ Flag 9: <Not Used>
+ Flag 10: <Not Used>
+ Flag 11: <Not Used>
+ Flag 12: <Not Used>
+
+ Flag 13: <Not Used>
+ Flag 14: <Not Used>
+ Flag 15: <Not Used>
+ Flag 16: <Not Used>
+
+ Flag 17: <Not Used>
+ Flag 18: <Not Used>
+ Flag 19: <Not Used>
+ Flag 20: <Not Used>
+
+ Flag 21: <Not Used>
+ Flag 22: <Not Used>
+ Flag 23: <Not Used>
+ Flag 24: <Not Used>
+
+ Flag 25: <Not Used>
+ Flag 26: <Not Used>
+ Flag 27: <Not Used>
+ Flag 28: <Not Used>
+
+ Flag 29: <Not Used>
+ Flag 30: <Not Used>
+ Flag 31: <Not Used>
+ Flag 32: <Not Used>
+
+ Flag 33: <Not Used>
+ Flag 34: <Not Used>
+ Flag 35: <Not Used>
+ Flag 36: <Not Used>
+
+ Flag 37: <Not Used>
+ Flag 38: <Not Used>
+ Flag 39: <Not Used>
+ Flag 40: <Not Used>
+
+ Flag 41: <Not Used>
+ Flag 42: <Not Used>
+ Flag 43: <Not Used>
+ Flag 44: <Not Used>
+
+ Flag 45: <Not Used>
+ Flag 46: <Not Used>
+ Flag 47: <Not Used>
+ Flag 48: <Not Used>
+
+ Flag 49: <Not Used>
+ Flag 50: <Not Used>
+ Flag 51: <Not Used>
+ Flag 52: <Not Used>
+
+ Flag 53: <Not Used>
+ Flag 54: <Not Used>
+ Flag 55: <Not Used>
+ Flag 56: <Not Used>
+
+ Flag 57: <Not Used>
+ Flag 58: <Not Used>
+ Flag 59: <Not Used>
+ Flag 60: <Not Used>
+
+ Flag 61: <Not Used>
+ Flag 62: <Not Used>
+ Flag 63: <Not Used>
+ Flag 64: <Not Used>"
+ ::= { upsAdvState 4 }
+
+upsAdvStateSmartUPSSpecificFaults OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An ASCII string containing the 64 flags representing
+ the current active UPS specific faults for the Smart-UPS
+ UPS models. If the Network Card is unable to determine
+ the values of the flags, this variable is set to
+ 'UNKNOWN'. If the connected UPS does not use this
+ variable, it is set to 'NOT SUPPORTED'.
+
+ The flags are numbered from 1 to 64, and read from left
+ to right. The bits are defined as follows:
+
+ Flag 1: EPO Switch Activated
+ Flag 2: Static Bypass Switch Fault
+ Flag 3: System Configuration Fault
+ Flag 4: Power Supply Unit Fault
+
+ Flag 5: Weak Battery
+ Flag 6: High Battery Temperature
+ Flag 7: Internal Mechanical Bypass
+ Flag 8: Loss Of Parallel Redundancy
+
+ Flag 9: Parallel Bus Communication Fault on Cable 1
+ Flag 10: Parallel Bus Communication Fault on Cable 2
+ Flag 11: Auxiliary Bus Communication Fault
+ Flag 12: Parallel Bus Termination Fault on Cable 1
+
+ Flag 13: Parallel Bus Termination Fault on Cable 2
+ Flag 14: Auxiliary Bus Termination Fault
+ Flag 15: No Master Present In The Parallel System
+ Flag 16: Overload on a Parallel Unit
+
+ Flag 17: Parallel Configuration Fault
+ Flag 18: <Not Used>
+ Flag 19: <Not Used>
+ Flag 20: <Not Used>
+
+ Flag 21: <Not Used>
+ Flag 22: <Not Used>
+ Flag 23: <Not Used>
+ Flag 24: <Not Used>
+
+ Flag 25: <Not Used>
+ Flag 26: <Not Used>
+ Flag 27: <Not Used>
+ Flag 28: <Not Used>
+
+ Flag 29: <Not Used>
+ Flag 30: <Not Used>
+ Flag 31: <Not Used>
+ Flag 32: <Not Used>
+
+ Flag 33: <Not Used>
+ Flag 34: <Not Used>
+ Flag 35: <Not Used>
+ Flag 36: <Not Used>
+
+ Flag 37: <Not Used>
+ Flag 38: <Not Used>
+ Flag 39: <Not Used>
+ Flag 40: <Not Used>
+
+ Flag 41: <Not Used>
+ Flag 42: <Not Used>
+ Flag 43: <Not Used>
+ Flag 44: <Not Used>
+
+ Flag 45: <Not Used>
+ Flag 46: <Not Used>
+ Flag 47: <Not Used>
+ Flag 48: <Not Used>
+
+ Flag 49: <Not Used>
+ Flag 50: <Not Used>
+ Flag 51: <Not Used>
+ Flag 52: <Not Used>
+
+ Flag 53: <Not Used>
+ Flag 54: <Not Used>
+ Flag 55: <Not Used>
+ Flag 56: <Not Used>
+
+ Flag 57: <Not Used>
+ Flag 58: <Not Used>
+ Flag 59: <Not Used>
+ Flag 60: <Not Used>
+
+ Flag 61: <Not Used>
+ Flag 62: <Not Used>
+ Flag 63: <Not Used>
+ Flag 64: <Not Used>"
+ ::= { upsAdvState 5 }
+
+
+upsAdvStateSystemMessages OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An ASCII string containing the 3 digit Decimal code
+ representing the current active message from the
+ System Message Register. Each code should remain active
+ for a minimum of 15 seconds. However, in the worst case
+ scenario, a code could be cleared after only 5 seconds.
+ It is recommended that this object be polled at least
+ once every 4 seconds in order to get the most accurate
+ representation of the current UPS System Message. If the
+ Network Card is unable to determine the value of the
+ System Message Register, this variable is set to
+ 'UNKNOWN'."
+ ::= { upsAdvState 6 }
+
+
+upsAdvStateTotaltimeonbattery OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Total time the UPS has been in battery operation."
+ ::= { upsAdvState 7 }
+
+upsAdvStateTotaltimeonbypass OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Total time the UPS has been in bypass operation."
+ ::= { upsAdvState 8 }
+
+upsAdvStateTotaltimeonNormal OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Total time the UPS has been in normal operation."
+ ::= { upsAdvState 9 }
+
+upsAdvStateNumberoftimesonbattery OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Number of times the UPS was on battery.
+ Since the last reset of statistical data."
+ ::= { upsAdvState 10 }
+
+upsAdvStateNumberoftimesbypass OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Number of times the UPS was in bypass.
+ Since the last reset of statistical data."
+ ::= { upsAdvState 11 }
+
+upsAdvStateNumberoftimesNormal OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Number of times the UPS was in normal operation.
+ Since the last reset of statistical data."
+ ::= { upsAdvState 12 }
+
+upsAdvStateEcomode OBJECT-TYPE
+ SYNTAX INTEGER {
+ upsOnEcoMode(1),
+ upsNotOnEcoMode(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Eco mode status.
+ 1: UPS is on Eco-mode
+ 2: UPS is not on Eco-mode."
+ ::= { upsAdvState 13 }
+
+upsAdvStateLifeCycleManagement OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An ASCII string containing the 16 flags representing the life cycle management alerts
+ for the device. If the Network Card is unable to determine the values of the flags,
+ this variable is set to 'UNKNOWN'. If the connected UPS does not use this variable,
+ it is set to 'NOT SUPPORTED'.
+
+ The flags are numbered from 1 to 16, and read from left
+ to right. The bits are defined as follows:
+
+ Flag 1: End of Warranty Soon
+ Flag 2: Battery Check Recommended
+ Flag 3: Service Period On Wearing Parts Expired
+ Flag 4: Secure Start-up Recommended
+
+ Flag 5: Fan Life Expired
+ Flag 6: DC Capacitor Life Expired
+ Flag 7: AC Capacitor Life Expired
+ Flag 8: Supply Service Life Expired
+
+ Flag 9: Ups Out Of Limits Warning
+ Flag 10: Air Filter Life Expired
+ Flag 11: <Not Used>
+ Flag 12: <Not Used>
+
+ Flag 13: <Not Used>
+ Flag 14: <Not Used>
+ Flag 15: <Not Used>
+ Flag 16: <Not Used>"
+ ::= { upsAdvState 14 }
+
+-- the upsBasicControl group
+
+upsBasicControlConserveBattery OBJECT-TYPE
+ SYNTAX INTEGER {
+ noTurnOffUps(1),
+ turnOffUpsToConserveBattery(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this variable to turnUpsOffToConserveBattery(2)
+ causes a UPS on battery to be put into 'sleep' mode. The
+ UPS will turn back on when utility power is restored.
+ Attempting to turn off a UPS that is not on battery will
+ result in a badValue error.
+
+ Setting this value to noTurnOffUps(1) has no
+ effect.
+
+ The value noTurnOffUps(1) will always be returned
+ when the variable is read."
+::= { upsBasicControl 1 }
+
+
+
+-- the upsAdvControl group
+
+upsAdvControlUpsOff OBJECT-TYPE
+ SYNTAX INTEGER {
+ noTurnUpsOff(1),
+ turnUpsOff(2),
+ turnUpsOffGracefully(3),
+ turnUpsSyncGroupOff(4),
+ turnUpsSyncGroupOffAfterDelay(5),
+ turnUpsSyncGroupOffGracefully(6)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this variable to turnUpsOff(2) causes
+ the UPS to shut off. When in this state, the UPS
+ will not provide output power regardless of the input
+ line state.
+
+ Setting this variable to turnUpsOffGracefully(3) causes
+ the UPS to shut off after a delay period. This allows the
+ host to shut down in a graceful manner. When in this state,
+ the UPS will not provide output power regardless of the
+ input line state.
+
+ If this UPS is an active member of a Synchronized
+ Control Group (SCG) the turnUpsSyncGroupOff(4) command
+ will perform a Synchronized Turn Off of all active Group
+ members regardless of their current AC output status.
+
+ If this UPS is an active member of a Synchronized
+ Control Group (SCG) the turnUpsSyncGroupOffAfterDelay(5)
+ command will perform a Synchronized Turn Off After Delay
+ of all active Group members regardless of their current
+ AC output status. This unit's Shutdown Delay will be used
+ to execute the Turn Off After Delay command.
+
+ If this UPS is an active member of an SCG, the
+ turnUpsSyncGroupOffGracefully(6) command will perform a
+ Synchronized Turn Off Gracefully of all active Group
+ members regardless of their current AC output status.
+ This unit's Maximum Shutdown Time and Shutdown Delay will
+ be used to execute the Turn Off Gracefully command.
+
+ Setting this value to noTurnUpsOff(1) has no
+ effect.
+
+ The value noTurnUpsOff(1) will always be returned
+ when the variable is read."
+ ::= { upsAdvControl 1 }
+
+upsAdvControlRebootShutdownUps OBJECT-TYPE
+ SYNTAX INTEGER {
+ noRebootShutdownUps(1),
+ rebootShutdownUps(2),
+ rebootShutdownUpsGracefully(3),
+ rebootShutdownSyncGroupUps(4),
+ rebootShutdownSyncGroupUpsGracefully(5)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this variable to rebootShutdownUps(2) causes the UPS
+ to shut off and turn back on (as long as good AC input power
+ is available, otherwise the UPS will remain off until good AC
+ input power is available).
+
+ Setting this variable to rebootShutdownUpsGracefully(3) causes
+ the UPS to shut off after a delay period and then turn back
+ on. This allows the host to shut down in a graceful manner.
+
+ If this UPS is an active member of a Synchronized Control
+ Group (SCG) the rebootShutdownSyncGroupUps(4) command will
+ perform a Synchronized Reboot of all active Group members
+ regardless of their current AC output status. If applicable,
+ this unit's Power Synchronization Delay, Shutdown Delay,
+ Return Delay, Return Battery Capacity, and Return Battery
+ Capacity Offset will be used to execute the Reboot command.
+
+ If this UPS is an active member of a SCG the
+ rebootShutdownSyncGroupUpsGracefully(5) command will perform
+ a Synchronized Reboot of all active Group members regardless
+ of their current AC output status. If applicable, this unit's
+ Power Synchronization Delay, Maximum Shutdown Time, Shutdown
+ Delay, Return Delay, Return Battery Capacity, and Return
+ Battery Capacity Offset will be used to execute the Reboot
+ command.
+
+ Setting this value to noRebootShutdownUps(1) has no effect.
+
+ The value noRebootShutdownUps(1) will always be returned when
+ the variable is read."
+ ::= { upsAdvControl 2 }
+
+upsAdvControlUpsSleep OBJECT-TYPE
+ SYNTAX INTEGER {
+ noPutUpsToSleep(1),
+ putUpsToSleep(2),
+ putUpsToSleepGracefully(3),
+ putUpsSyncGroupToSleep(4),
+ putUpsSyncGroupToSleepGracefully(5)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this variable to putUpsToSleep(2) causes
+ the UPS to go to sleep for the time specified by
+ upsAdvConfigUpsSleepTime.
+
+ Setting this variable to putUpsToSleepGracefully(3)
+ causes the UPS to go to sleep for the time specified
+ by upsAdvConfigUpsSleepTime after a delay period.
+ This allows the host to shut down in a graceful manner.
+
+ If this UPS is an active member of a Synchronized Control
+ Group (SCG), the putUpsSyncGroupToSleep(4) command will perform
+ a Synchronized Sleep of all active Group members regardless
+ of their current AC output status. This unit's Power
+ Synchronization Delay, Shutdown Delay, Sleep Time,
+ and Return Delay will be used to execute the sleep command.
+
+ If this UPS is an active member of a SCG the
+ putUpsSyncGroupToSleepGracefully(5) command will perform a
+ Synchronized Sleep Gracefully of all active Group members
+ regardless of their current AC output status. This unit's
+ Power Synchronization Delay, Maximum Shutdown Time, Shutdown
+ Delay, Sleep Time, and Return Delay to execute the sleep
+ command.
+
+ When in sleep mode, the UPS will not provide output
+ power regardless of the input line state. Once the
+ specified time has elapsed, output power will be
+ restored.
+
+ Setting this value to noPutUpsToSleep(1) has no
+ effect.
+
+ The value noPutUpsToSleep(1) will always be returned
+ when the variable is read."
+ ::= { upsAdvControl 3 }
+
+
+upsAdvControlSimulatePowerFail OBJECT-TYPE
+ SYNTAX INTEGER {
+ noSimulatePowerFailure(1),
+ simulatePowerFailure(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this variable to simulatePowerFailure(2) causes
+ the UPS switch to battery power.
+
+ Setting this value to noSimulatePowerFailure(1) has no
+ effect.
+
+ The value noSimulatePowerFailure(1) will always be returned
+ when the variable is read."
+ ::= { upsAdvControl 4 }
+
+
+upsAdvControlFlashAndBeep OBJECT-TYPE
+ SYNTAX INTEGER {
+ noFlashAndBeep(1),
+ flashAndBeep(2),
+ flashAndBeepSyncGroup(3),
+ flashAndBeepCont(4),
+ flashAndBeepCancel(5)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this variable to flashAndBeep(2) causes the
+ UPS to beep and simultaneously turn on the UPS front
+ panel lights (Smart-UPS only).
+
+ If this UPS is an active member of a Synchronized Control
+ Group (SCG), the flashAndBeepSyncGroup(3) command will
+ Flash and Beep all active Group members regardless of
+ current AC output status.
+
+ Setting this value to noFlashAndBeep(1) has no
+ effect.
+
+ Setting this value to flashAndBeepCont (4) commandcauses
+ the UPS to beep and light the front panel lights until
+ the flashAndBeepCancel (5) command is received.
+
+ The value noFlashAndBeep(1) will always be returned
+ when the variable is read."
+ ::= { upsAdvControl 5 }
+
+
+upsAdvControlTurnOnUPS OBJECT-TYPE
+ SYNTAX INTEGER {
+ noTurnOnUPS(1),
+ turnOnUPS(2),
+ turnOnUPSSyncGroup(3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this variable to turnOnUPS(2) causes the
+ UPS to be turned on immediately.
+
+ If this UPS is an active member of a Synchronized Control
+ Group (SCG), the turnOnUPSSyncGroup(3) command will perform
+ a Synchronized Turn On of all active Group members
+ regardless of their current AC output status.
+
+ Setting this value to noTurnOnUPS(1) has no
+ effect.
+
+ The value noTurnOnUPS(1) will always be returned
+ when the variable is read."
+ ::= { upsAdvControl 6 }
+
+upsAdvControlBypassSwitch OBJECT-TYPE
+ SYNTAX INTEGER {
+ noBypassSwitch (1),
+ switchToBypass (2),
+ switchOutOfBypass(3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "This switch puts the UPS in or out of bypass mode."
+ ::= { upsAdvControl 7 }
+
+upsAdvControlRebootUpsWithOrWithoutAC OBJECT-TYPE
+ SYNTAX INTEGER {
+ noRebootUpsWithOrWithoutAC (1),
+ rebootUpsImmediatelyWithOrWithoutAC (2),
+ rebootUpsDelayedWithOrWithoutAC (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this variable to rebootUpsImmediatelyWithOrWithoutAC (2)
+ causes the UPS to turn off immediately, wait for a minimum time
+ (typically 8 seconds), and then turn back on regardless of the
+ AC input power on the UPS. Any supported switched outlet
+ groups will be turned off immediately but will turn on based
+ on their individual settings (to allow on sequencing).
+
+ Setting this variable to rebootUpsDelayedWithOrWithoutAC (3)
+ causes the UPS to turn off after a delay period, wait for a
+ minimum time (typically 8 seconds), and then turn back on
+ regardless of the AC input power on the UPS. Any supported
+ switched outlet groups will be turned off and on based on their
+ individual settings (to allow off and/or on sequencing).
+
+ Setting this value to noRebootUpsWithOrWithoutAC (1) has no
+ effect.
+
+ The value noRebootUpsWithOrWithoutAC (1) will always be
+ returned when the variable is read."
+ ::= { upsAdvControl 8 }
+
+upsAdvControlFirmwareUpdate OBJECT-TYPE
+ SYNTAX INTEGER {
+ noFirmwareUpdate (1),
+ firmwareUpdate (2),
+ updateInProcess (3),
+ updateSuccessful (4),
+ updateFailed (5)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this variable to firmwareUpdate(2) causes the
+ UPS to begin a firmware update if possible.
+
+ Setting this value to noFirmwareUpdate(1) will clear the
+ previous results, if any, or otherwise has no effect.
+
+ Reading this variable will return noFirmwareUpdate(1) when
+ the UPS firmware has not been updated (or previous results
+ have been cleared), updateInProcess(3) when the UPS firmware
+ is being updated, updateSuccessful(4) when the UPS firmware
+ has been successfully updated, or updateFailed(5) if the UPS
+ firmware update failed."
+ ::= { upsAdvControl 9 }
+
+
+-- the upsTest group
+
+-- the upsBasicTest group
+
+-- the upsAdvTest group
+
+upsAdvTestDiagnosticSchedule OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(1),
+ biweekly(2),
+ weekly(3),
+ atTurnOn(4),
+ never(5),
+ fourWeeks(6),
+ twelveWeeks(7),
+ biweeklySinceLastTest(8),
+ weeklySinceLastTest(9),
+ eightWeeks(10),
+ twentysixWeeks(11),
+ fiftytwoWeeks(12)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The UPS system's automatic battery test schedule."
+ ::= { upsAdvTest 1 }
+
+
+upsAdvTestDiagnostics OBJECT-TYPE
+ SYNTAX INTEGER {
+ noTestDiagnostics(1),
+ testDiagnostics(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this variable to testDiagnostics(2) causes
+ the UPS to perform a diagnostic self test.
+
+ Setting this value to noTestDiagnostics(1) has no
+ effect.
+
+ The value noTestDiagnostics(1) will always be returned
+ when the variable is read."
+ ::= { upsAdvTest 2 }
+
+upsAdvTestDiagnosticsResults OBJECT-TYPE
+ SYNTAX INTEGER {
+ ok(1),
+ failed(2),
+ invalidTest(3),
+ testInProgress(4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The results of the last UPS diagnostics test performed."
+ ::= { upsAdvTest 3 }
+
+upsAdvTestLastDiagnosticsDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The date the last UPS diagnostics test was performed in
+ mm/dd/yy format."
+ ::= { upsAdvTest 4 }
+
+upsAdvTestRuntimeCalibration OBJECT-TYPE
+ SYNTAX INTEGER {
+ noPerformCalibration(1),
+ performCalibration(2),
+ cancelCurrentCalibration(3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this variable to performCalibration(2) causes
+ the UPS to discharge to calibrate the UPS.
+ The test will only start if the battery capacity is 100%.
+ The test runs until capacity is less than 25%.
+
+ Setting this variable to cancelCurrentCalibration(3)
+ after setting performCalibration(2) will cancel the
+ current discharge.
+
+ Setting this variable to noPerformCalibration(1)
+ will have no effect.
+
+ The value noPerformCalibration(1) will always be returned
+ when the variable is read.
+
+ The result of the calibration will be saved in
+ upsAdvTestCalibrationResult."
+ ::= { upsAdvTest 5 }
+
+upsAdvTestCalibrationResults OBJECT-TYPE
+ SYNTAX INTEGER {
+ ok(1),
+ invalidCalibration(2),
+ calibrationInProgress(3),
+ refused(4),
+ aborted(5),
+ pending(6),
+ unknown(7)
+ }
+ ACCESS read-only
+ STATUS mandatory
+
+ DESCRIPTION
+ "The results of the last runtime calibration.
+
+ Value ok(1) means a successful runtime calibration.
+
+ Value invalidCalibration(2) indicates last calibration did
+ not take place since the battery capacity was below
+ 100%.
+ Value calibrationInProgress(3) means a calibration
+ is occurring now.
+
+ Value refused(4) means the test was refused, it did not take place.
+
+ Value aborted(5) indicates the test started but either someone cancelled it or
+ the system encountered an error.
+
+ Value pending(6) the test will commence shortly. "
+ ::= { upsAdvTest 6 }
+
+upsAdvTestCalibrationDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The date the last UPS runtime calibration was
+ performed in mm/dd/yy format."
+ ::= { upsAdvTest 7 }
+
+upsAdvTestDiagnosticTime OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The time of the day to perform automatic battery test.
+ Expressed in 24 hour notation - hh:mm."
+ ::= { upsAdvTest 8 }
+
+upsAdvTestDiagnosticDay OBJECT-TYPE
+ SYNTAX INTEGER {
+ monday (1),
+ tuesday (2),
+ wednesday (3),
+ thursday (4),
+ friday (5),
+ saturday (6),
+ sunday (7)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The day of the week to perform automatic battery test."
+ ::= { upsAdvTest 9 }
+
+upsAdvTestBatteryInterval OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The UPS system's automatic battery test period."
+ ::= { upsAdvTest 10 }
+
+upsAdvTestCalibrationLastSuccessfulDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The latest date when the UPS performed a successful runtime calibration test.
+ The format is YYYY-MM-DD"
+ ::= { upsAdvTest 11 }
+
+upsAdvTestBatteryLastSuccessfulDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The latest date when the UPS performed a successful battery diagnostic test (battery monitoring test).
+ The format is YYYY-MM-DD"
+ ::= { upsAdvTest 12 }
+
+upsAdvTestBatteryLastDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "The latest date when the UPS performed a battery diagnostic test (battery monitoring test),
+ regardless of the test result.
+ The format is YYYY-MM-DD"
+ ::= { upsAdvTest 13 }
+
+upsAdvTestBatteryProcessStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ ok(1),
+ preconditionNotMeet(2),
+ batteryTestInProgress(3),
+ refused(4),
+ aborted(5),
+ pending(6),
+ unknown(7)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The results of the latest battery diagnostic test (battery monitoring test).
+ ok(1) indicates a successful completion of the test.
+ preconditionNotMeet(2) indicates that the test did not start, due to low capacity or low load.
+ batteryTestInProgress(3) indicates that a test is in progress.
+ refused(4) indicates that the test was refused and did not take place.
+ aborted(5) indicates that the test started but it was either cancelled or the system encountered an error.
+ pending(6) the test will commence shortly."
+ ::= { upsAdvTest 14 }
+
+upsAdvTestBatteryConditionStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(1),
+ batteryOK(2),
+ batteryCapacityDecreased(3),
+ batteryDefect(4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Result of the latest successful test
+ 1 = unknown
+ 2 = battery OK
+ 3 = battery capacity decreased
+ 4 = battery defect"
+ ::= { upsAdvTest 15 }
+
+upsAdvTestDiagnosticsBatteryInterval OBJECT-TYPE
+ SYNTAX INTEGER {
+ never(1),
+ weekly(2),
+ biweekly(3),
+ every4weeks(4),
+ every8weeks(5),
+ every12weeks(6),
+ every26weeks(7),
+ every52weeks(8)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery test is a diagnostic test (also referred to as battery monitoring test).
+ The test will be performed on the day stated in upsAdvTestDiagnosticDay
+ and at the time stated in upsAdvTestDiagnosticTime.
+ The result can be read in upsAdvTestBatteryConditionStatus.
+ 1 = Never
+ 2 = Weekly
+ 3 = biweekly
+ 4 = Every 4 weeks
+ 5 = Every 8 weeks
+ 6 = Every 12 weeks
+ 7 = Every 26 weeks
+ 8 = Every 52 weeks"
+ ::= { upsAdvTest 16 }
+
+-- the upsComm group
+
+upsCommStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ ok(1),
+ noComm(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of agent's communication with UPS. "
+ ::= { upsComm 1 }
+
+-- ups (integrated) output relay table
+
+upsOutputRelayStatusTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of integrated output relays on the UPS."
+ ::= { upsOutputRelays 1 }
+
+upsOutputRelayStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UPSOutputRelayStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for access of individual relays."
+ ::= { upsOutputRelays 2 }
+
+upsOutputRelayStatusEntry OBJECT-TYPE
+ SYNTAX UPSOutputRelayStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The output relays to access."
+ INDEX { upsOutputRelayIndex }
+ ::= { upsOutputRelayStatusTable 1 }
+
+UPSOutputRelayStatusEntry ::=
+ SEQUENCE {
+ upsOutputRelayIndex INTEGER,
+ upsOutputRelayState INTEGER,
+ upsOutputRelayDetailedStatus DisplayString
+ }
+
+upsOutputRelayIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the output relay entry."
+ ::= { upsOutputRelayStatusEntry 1 }
+
+upsOutputRelayState OBJECT-TYPE
+ SYNTAX INTEGER {
+ outputRelayNormalState (1),
+ outputRelayAbnormalState (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this variable will return the output relay state.
+ 1 - normal state
+ 2 - abnormal state"
+ ::= { upsOutputRelayStatusEntry 2 }
+
+upsOutputRelayDetailedStatus OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An ASCII string containing the 16 flags representing
+ the status of the output relay.
+
+ The flags are numbered from 1 to 16, and read from left
+ to right. The bits are defined as follows:
+
+ Flag 1: Cause is true which makes the output relay active if not pending a condition
+ Flag 2: Pending delay
+ Flag 3: Pending peak period
+ Flag 4: <Not Used>
+
+ Flag 5: <Not Used>
+ Flag 6: <Not Used>
+ Flag 7: <Not Used>
+ Flag 8: <Not Used>
+
+ Flag 9: <Not Used>
+ Flag 10: <Not Used>
+ Flag 11: <Not Used>
+ Flag 12: <Not Used>
+
+ Flag 13: <Not Used>
+ Flag 14: <Not Used>
+ Flag 15: <Not Used>
+ Flag 16: <Not Used>"
+ ::= { upsOutputRelayStatusEntry 3 }
+
+upsOutputRelayConfigTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of integrated output relays on the UPS."
+ ::= { upsOutputRelays 3 }
+
+upsOutputRelayConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UPSOutputRelayConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for access of individual relays."
+ ::= { upsOutputRelays 4 }
+
+upsOutputRelayConfigEntry OBJECT-TYPE
+ SYNTAX UPSOutputRelayConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The output relays to access."
+ INDEX { upsOutputRelayConfigIndex }
+ ::= { upsOutputRelayConfigTable 1 }
+
+UPSOutputRelayConfigEntry ::=
+ SEQUENCE {
+ upsOutputRelayConfigIndex INTEGER,
+ upsOutputRelayConfigDelay INTEGER,
+ upsOutputRelayConfigCause INTEGER
+ }
+
+upsOutputRelayConfigIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the output relay entry."
+ ::= { upsOutputRelayConfigEntry 1 }
+
+upsOutputRelayConfigDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Output relay delay 0 - 86400 seconds."
+ ::= { upsOutputRelayConfigEntry 2 }
+
+upsOutputRelayConfigCause OBJECT-TYPE
+ SYNTAX INTEGER {
+ outputRelayConfigCauseNone (1),
+ outputRelayConfigCauseOnBatPwrFail (2),
+ outputRelayConfigCauseOnBatPwrFailExceptPeakPeriod (3),
+ outputRelayConfigCauseLoBatWhileOnBat (4),
+ outputRelayConfigCauseAlarm (5),
+ outputRelayConfigCauseFault (6),
+ outputRelayConfigCauseOutputOn (7),
+ outputRelayConfigCauseOutputOff (8),
+ outputRelayConfigCauseOnline (9),
+ outputRelayConfigCauseInBypass (10)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "This variable sets what causes the output relay state to change.
+ 1 - none
+ 2 - on battery power failure
+ 3 - on battery power failure expect during peak period
+ 4 - low battery while on battery
+ 5 - alarm
+ 6 - fault
+ 7 - output on
+ 8 - output off
+ 9 - online
+ 10 - in bypass"
+ ::= { upsOutputRelayConfigEntry 3 }
+
+upsOutputRelayConfigPolarity OBJECT-TYPE
+ SYNTAX INTEGER{
+ upsOutputRelayAllRelaysEnergizedWhenTrue (1),
+ upsOutputRelayAllRelaysNotEnergizedWhenTrue (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Configures all output relays with one setting.
+ 1 - all relays act normally open, when logic condition is true, relays are energized
+ 2 - all relays act normally close, when logic condition is true relays are deenergized"
+ ::= { upsOutputRelays 5 }
+
+
+upsOutputRelayConfigPeakPeriod OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "An ASCII string containing the 64 flags representing
+ the peak period setting of the UPS. Flags are numbered 1-64
+ starting from the left. Each flag is either a '1',
+ representing a flag that is set, or a '0', representing
+ a flag that is /not/ set.
+
+ The peak period intervals are times that are both:
+ - on the days of the week set by the first 7 flags AND
+ - within the time periods set by the remaining flags.
+
+ UPS output relays triggered by 'On battery except peak period'
+ will not signal when the UPS is on battery during a peak period.
+
+ The flags are defined as follows:
+
+ Flag 1: Sunday
+ Flag 2: Monday
+ Flag 3: Tuesday
+ Flag 4: Wednesday
+
+ Flag 5: Thursday
+ Flag 6: Friday
+ Flag 7: Saturday
+ Flag 8: 00:00-00:29
+
+ Flag 9: 00:30-00:59
+ Flag 10: 01:00-01:29
+ Flag 11: 01:30-01:59
+ Flag 12: 02:00-02:29
+
+ Flag 13: 02:30-02:59
+ Flag 14: 03:00-03:29
+ Flag 15: 03:30-03:59
+ Flag 16: 04:00-04:29
+
+ Flag 17: 04:30-04:59
+ Flag 18: 05:00-05:29
+ Flag 19: 05:30-05:59
+ Flag 20: 06:00-06:29
+
+ Flag 21: 06:30-06:59
+ Flag 22: 07:00-07:29
+ Flag 23: 07:30-07:59
+ Flag 24: 08:00-08:29
+
+ Flag 25: 08:30-08:59
+ Flag 26: 09:00-09:29
+ Flag 27: 09:30-09:59
+ Flag 28: 10:00-00:29
+
+ Flag 29: 10:30-10:59
+ Flag 30: 11:00-11:29
+ Flag 31: 11:30-11:59
+ Flag 32: 12:00-12:29
+
+ Flag 33: 12:30-12:59
+ Flag 34: 13:00-13:29
+ Flag 35: 13:30-13:59
+ Flag 36: 14:00-14:29
+
+ Flag 37: 14:30-14:59
+ Flag 38: 15:00-15:29
+ Flag 39: 15:30-15:59
+ Flag 40: 16:00-16:29
+
+ Flag 41: 16:30-16:59
+ Flag 42: 17:00-17:29
+ Flag 43: 17:30-17:59
+ Flag 44: 18:00-18:29
+
+ Flag 45: 18:30-18:59
+ Flag 46: 19:00-19:29
+ Flag 47: 19:30-19:59
+ Flag 48: 20:00-20:29
+
+ Flag 49: 20:30-20:59
+ Flag 50: 21:00-21:29
+ Flag 51: 21:30-21:59
+ Flag 52: 22:00-22:29
+
+ Flag 53: 22:30-22:59
+ Flag 54: 23:00-23:29
+ Flag 55: 23:30-23:59
+ Flag 56: <Not Used>
+
+ Flag 57: <Not Used>
+ Flag 58: <Not Used>
+ Flag 59: <Not Used>
+ Flag 60: <Not Used>
+
+ Flag 61: <Not Used>
+ Flag 62: <Not Used>
+ Flag 63: <Not Used>
+ Flag 64: <Not Used>
+
+ To set this OID you can either:
+ - set the 64 flag bits as an ASCII string of '1's and '0's
+ as described above. The same format is used when this OID
+ is read.
+ - or turn on/off an individual flags.
+
+ Examples:
+
+ Set for Sundays and Tuesdays from 00:00-01:29:
+ 1010000111000000000000000000000000000000000000000000000000000000
+
+ Set Mondays to be part of the peak periods:
+ +2
+
+ Set Tuesdays to not be part of the peak periods:
+ -3
+
+ Include interval 23:30-23:59 in the peak period:
+ +55"
+ ::= { upsOutputRelays 6 }
+
+upsInputContactStatusTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of integrated input contacts on the UPS."
+ ::= { upsInputContacts 1 }
+
+upsInputContactStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsInputContactStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for access of individual contacts."
+ ::= { upsInputContacts 2 }
+
+upsInputContactStatusEntry OBJECT-TYPE
+ SYNTAX UpsInputContactStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The input contacts to access."
+ INDEX { upsInputContactIndex }
+ ::= { upsInputContactStatusTable 1 }
+
+UpsInputContactStatusEntry ::=
+ SEQUENCE {
+ upsInputContactIndex INTEGER,
+ upsInputContactState INTEGER
+ }
+
+upsInputContactIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the input contact entry."
+ ::= { upsInputContactStatusEntry 1 }
+
+upsInputContactState OBJECT-TYPE
+ SYNTAX INTEGER {
+ upsInputContactNormalState (1),
+ upsInputContactAbnormalState (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this variable will return the input contact state.
+ 1 - normal state
+ 2 - abnormal state"
+ ::= { upsInputContactStatusEntry 2 }
+
+upsInputContactConfigTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of integrated input contacts on the UPS."
+ ::= { upsInputContacts 3 }
+
+upsInputContactConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsInputContactConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for access of individual contacts."
+ ::= { upsInputContacts 4 }
+
+upsInputContactConfigEntry OBJECT-TYPE
+ SYNTAX UpsInputContactConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The input contacts to access."
+ INDEX { upsInputContactConfigIndex }
+ ::= { upsInputContactConfigTable 1 }
+
+UpsInputContactConfigEntry ::=
+ SEQUENCE {
+ upsInputContactConfigIndex INTEGER,
+ upsInputContactConfigAction INTEGER
+ }
+
+upsInputContactConfigIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the input contact entry."
+ ::= { upsInputContactConfigEntry 1 }
+
+upsInputContactConfigAction OBJECT-TYPE
+ SYNTAX INTEGER {
+ upsInputContactConfigActionNone (1),
+ upsInputContactConfigActionSelfTest (2),
+ upsInputContactConfigActionExternalAlarmOn (3),
+ upsInputContactConfigActionExternalAlarmOff (4),
+ upsInputContactConfigActionOutputOffNoDelay (5),
+ upsInputContactConfigActionOutputOn (6)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "When the input contact changes state, this action occurs.
+ 1 - none
+ 2 - self test
+ 3 - external alarm on
+ 4 - external alarm off
+ 5 - output off no delay
+ 6 - output on"
+ ::= { upsInputContactConfigEntry 2 }
+
+upsInputContactConfigPolarity OBJECT-TYPE
+ SYNTAX INTEGER{
+ upsInputContactAllContactsClosedEqualsTrue (1),
+ upsInputContactAllContactsOpenEqualsTrue (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Configures all input contacts with one setting.
+ 1 - all contacts act as normally open
+ 2 - all contacts act as normally closed"
+ ::= { upsInputContacts 5 }
+
+-- upsServiceInfo subgroup
+-- the upsServiceBatteryInfo subgroup
+-- Don't want to expose Ups Service information data to customer.
+-- Always be in experimental.
+
+-- upsECOmode subgroup
+upsEcoModeFreqTransferRange OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates tolerance of bypass AC frequency in Hz to switch on ECO mode."
+ ::= { upsECOmode 1 }
+
+upsEcoModeHighVoltThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates high threshold on AC voltage in volts to switch on ECO mode."
+ ::= { upsECOmode 2 }
+
+upsEcoModeLowVoltThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates low threshold on AC voltage in volts to switch on ECO mode."
+ ::= { upsECOmode 3 }
+
+upsEcoModeSetting OBJECT-TYPE
+ SYNTAX INTEGER {
+ enabled (1),
+ disabled (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates whether ECO feature is avaiable to this UPS or not."
+ ::= { upsECOmode 4 }
+
+upsEcoModeStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ active (1),
+ inactive (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates whether UPS is running in ECO mode or not."
+ ::= { upsECOmode 5 }
+
+upsEcoModeCountSinceReset OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Number of times UPS entered into ECO mode since maintenance reset."
+ ::= { upsECOmode 6 }
+
+upsEcoModeOnlineSinceCommission OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Total runtime in online mode with ECO feature enabled once product is authorized to use (in minutes)."
+ ::= { upsECOmode 7 }
+
+upsEcoModeOnlineSinceReset OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Total runtime in online mode with ECO feature enabled since maintenance reset (in minutes)."
+ ::= { upsECOmode 8 }
+
+upsEcoModeTotalPercentTimeSinceReset OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates percentage of runtime in ECO mode since maintenance reset."
+ ::= { upsECOmode 9 }
+
+upsEcoModePercentTimeSinceCommission OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates percentage of operation time in ECO mode once product is authorized to use."
+ ::= { upsECOmode 10 }
+
+upsEcoModeTotalTimeSinceReset OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Total runtime of UPS in ECO mode since maintenance reset (in minutes)."
+ ::= { upsECOmode 11 }
+
+upsEcoModeTotalTimeSinceCommission OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Total runtime in ECO mode once product is authorized to use (in minutes)."
+ ::= { upsECOmode 12 }
+
+upsEcoModeTotalTimeInMonth OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Total runtime of UPS in ECO mode since beginning of month (in minutes)."
+ ::= { upsECOmode 13 }
+
+-- upsEBMmode subgroup
+upsEbmModeSetting OBJECT-TYPE
+ SYNTAX INTEGER {
+ enabled (1),
+ disabled (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates whether efficiency booster mode feature is avaiable to this UPS or not."
+ ::= { upsEBMmode 1 }
+
+upsEbmModeStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ active (1),
+ inactive (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates whether UPS is running on EBM mode or not."
+ ::= { upsEBMmode 2 }
+
+upsEbmModeCountSinceReset OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Number of times UPS entered into efficiency booster mode since maintenance reset."
+ ::= { upsEBMmode 3 }
+
+upsEbmModeTotalTimeInMonth OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Total runtime of UPS in efficiency booster mode since beginning of month (in minutes)."
+ ::= { upsEBMmode 4 }
+
+upsEbmModeTotalTimeSinceReset OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Total runtime of UPS in efficiency booster mode since maintenance reset (in minutes)."
+ ::= { upsEBMmode 5 }
+
+upsEbmModeTotalPercentTimeSinceReset OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates percentage of runtime in efficiency booster mode since maintenance reset."
+ ::= { upsEBMmode 6 }
+
+upsEbmModeOnlineSinceCommission OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates runtime in online mode with EBM feature enabled once product is authorized to use (in minutes)."
+ ::= { upsEBMmode 7 }
+
+upsEbmModePercentTimeSinceCommission OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates percentage of operation time in efficiency booster mode once product is authorized to use."
+ ::= { upsEBMmode 8 }
+
+upsEbmModeRuntimeSinceCommission OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Total runtime in efficiency booster mode once product is authorized to use (in minutes)."
+ ::= { upsEBMmode 9 }
+
+upsEbmModeOnlineSinceReset OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Total runtime in online mode with EBM feature enabled since maintenance reset (in minutes)."
+ ::= { upsEBMmode 10 }
+
+upsEbmModeUpsCount OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Number of UPS's running in efficiency booster mode."
+ ::= { upsEBMmode 11 }
+
+-- upsBatteryStats group
+
+upsBatteryStatsReset OBJECT-TYPE
+ SYNTAX INTEGER {
+ notSupported (1),
+ noOperation (2),
+ reset (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to reset(3) will reset the Battery Stats timer.
+ Getting this OID will return:
+ notSupported(1) - reset feature is not supported.
+ noOperation(2) - indicates reset is supported, does nothing."
+ ::= { upsBatteryStats 1 }
+
+upsBatteryStatsTimeSinceReset OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Time since battery timer reset (in minutes)."
+ ::= { upsBatteryStats 2 }
+
+upsBatteryStatsTimeOnBattery OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Total time for UPS in battery operation (in minutes)."
+ ::= { upsBatteryStats 3 }
+
+-- upsOperationalStats group
+
+upsOpStatsReset OBJECT-TYPE
+ SYNTAX INTEGER {
+ notSupported (1),
+ noOperation (2),
+ reset (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to reset(3) will reset the Operational Stats timer.
+ Getting this OID will return:
+ notSupported(1) - reset feature is not supported.
+ noOperation(2) - indicates reset is supported, does nothing."
+ ::= { upsOperationalStats 1 }
+
+upsOpStatsTimeSinceReset OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Time since timer reset (in minutes)."
+ ::= { upsOperationalStats 2 }
+
+upsOpStatsTimeInNormalOperation OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Total time for UPS in normal operation since timer reset via upsOpStatsReset (in minutes)."
+ ::= { upsOperationalStats 3 }
+
+upsOpStatsTimeInBypassOperation OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Total time for UPS in bypass operation since timer reset via upsOpStatsReset (in minutes)."
+ ::= { upsOperationalStats 4 }
+
+upsOpStatsTimeInECOmodeOperation OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Total time for UPS in ECO mode since timer reset via upsOpStatsReset (in minutes)."
+ ::= { upsOperationalStats 5 }
+
+upsOpStatsTimeInECOnversionOperation OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Total time for UPS in ECOnversion since timer reset via upsOpStatsReset (in minutes)."
+ ::= { upsOperationalStats 6 }
+
+-- upsEnergyEfficiencyStats group
+
+upsEnergyEfficiencyStatsReset OBJECT-TYPE
+ SYNTAX INTEGER {
+ notSupported (1),
+ noOperation (2),
+ reset (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to reset(3) will reset the Energy Efficiency Stats timer.
+ Getting this OID will return:
+ notSupported(1) - reset feature is not supported.
+ noOperation(2) - indicates reset is supported, does nothing."
+ ::= { upsEnergyEfficiencyStats 1 }
+
+upsEnergyEfficiencyStatsOutputEnergyTimeSinceReset OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Time (in minutes) since last timer reset of the OID upsEnergyEfficiencyStatsOutputEnergyUsage"
+ ::= { upsEnergyEfficiencyStats 2 }
+
+upsEnergyEfficiencyStatsTimeInECOmode OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "Total time (in minutes) for UPS in ECO mode since last timer reset via upsEnergyEfficiencyStatsReset"
+ ::= { upsEnergyEfficiencyStats 3 }
+
+upsEnergyEfficiencyStatsTimeInECOnversion OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "Total time (in minutes) for UPS in ECOnversion since last timer reset via upsEnergyEfficiencyStatsReset"
+ ::= { upsEnergyEfficiencyStats 4 }
+
+upsEnergyEfficiencyStatsInputEnergyUsage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input energy usage of the UPS in kWh since timer reset."
+ ::= { upsEnergyEfficiencyStats 5 }
+
+upsEnergyEfficiencyStatsOutputEnergyUsage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output energy usage of the UPS in kWh since timer reset."
+ ::= { upsEnergyEfficiencyStats 6 }
+
+upsEnergyEfficiencyStatsInputEnergyTimeSinceReset OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Time (in minutes) since last timer reset of the OID upsEnergyEfficiencyStatsInputEnergyUsage"
+ ::= { upsEnergyEfficiencyStats 7 }
+
+upsEnergyEfficiencyStatsECOmodeTimeSinceReset OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "Time (in minutes) since last timer reset of the OID upsEnergyEfficiencyStatsTimeInECOmode"
+ ::= { upsEnergyEfficiencyStats 8 }
+
+upsEnergyEfficiencyStatsECOnversionTimeSinceReset OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS optional
+ DESCRIPTION
+ "Time (in minutes) since last timer reset of the OID upsEnergyEfficiencyStatsTimeInECOnversion"
+ ::= { upsEnergyEfficiencyStats 9 }
+
+-- the measureUps group
+-- the Environ group
+
+mUpsEnvironAmbientTemperature OBJECT-TYPE
+ SYNTAX Gauge
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The ambient temperature in Celsius for Probe 1."
+ ::= { mUpsEnviron 1 }
+
+mUpsEnvironRelativeHumidity OBJECT-TYPE
+ SYNTAX Gauge
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The relative humidity as a percentage for Probe 1."
+ ::= { mUpsEnviron 2 }
+
+
+mUpsEnvironAmbientTemperature2 OBJECT-TYPE
+ SYNTAX Gauge
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The ambient temperature in Celsius for Probe 2."
+ ::= { mUpsEnviron 3 }
+
+mUpsEnvironRelativeHumidity2 OBJECT-TYPE
+ SYNTAX Gauge
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The relative humidity as a percentage for Probe 2."
+ ::= { mUpsEnviron 4 }
+
+-- the mUpsContact group
+
+mUpsContactNumContacts OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of contacts supported by the Measure-UPS."
+ ::= { mUpsContact 1 }
+
+mUpsContactTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF MUpsContactEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of contacts supported by the Measure-UPS."
+ ::= { mUpsContact 2 }
+
+mUpsContactEntry OBJECT-TYPE
+ SYNTAX MUpsContactEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A contact entry containing information for a given contact."
+ INDEX { contactNumber }
+ ::= { mUpsContactTable 1 }
+
+MUpsContactEntry ::=
+ SEQUENCE {
+ contactNumber
+ INTEGER,
+ normalState
+ INTEGER,
+ description
+ DisplayString,
+ monitoringStatus
+ INTEGER,
+ currentStatus
+ INTEGER
+ }
+
+contactNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An index identifying the contact on the Measure-UPS."
+ ::= { mUpsContactEntry 1 }
+
+normalState OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(1),
+ open(2),
+ closed(3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The normal operating position of the contact. If the normal
+ operating position cannot be set then it is controlled via the
+ dip switch on the Measure-UPS and is therefore read-only."
+ ::= { mUpsContactEntry 2 }
+
+description OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The description of the purpose/use of the contact."
+ ::= { mUpsContactEntry 3 }
+
+monitoringStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(1),
+ enabled(2),
+ disabled(3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A flag indicating whether this contact is
+ monitored, or not."
+ ::= { mUpsContactEntry 4 }
+
+currentStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(1),
+ noFault(2),
+ fault(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This value indicates the current state of the contact.
+ If the contact is not in its normal state. This value
+ is set to fault(2)."
+ ::= { mUpsContactEntry 5 }
+
+-- Three Phase Group
+
+--
+-- Reset Max/Min Values Group
+--
+
+ upsPhaseResetMaxMinValues OBJECT-TYPE
+ SYNTAX INTEGER {
+ none (1),
+ reset (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Reset the maximum and minimum UPS values:
+ upsPhaseInputMaxVoltage, upsPhaseInputMinVoltage,
+ upsPhaseInputMaxCurrent, upsPhaseInputMinCurrent,
+ upsPhaseInputMaxPower, upsPhaseInputMinPower,
+ upsPhaseOutputMaxCurrent, upsPhaseOutputMinCurrent,
+ upsPhaseOutputMaxLoad, upsPhaseOutputMinLoad,
+ upsPhaseOutputMaxPercentLoad, upsPhaseOutputMinPercentLoad,
+ upsPhaseOutputMaxPower, upsPhaseOutputMinPower,
+ upsPhaseOutputMaxPercentPower, upsPhaseOutputMinPercentPower."
+ ::= { upsPhaseResetValues 1 }
+
+--
+-- Input Group
+--
+
+-- Number of Inputs
+
+ upsPhaseNumInputs OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of input feeds to this device.
+ This variable indicates the number of rows in the
+ input table."
+ ::= { upsPhaseInput 1 }
+
+-- Input Table
+
+ upsPhaseInputTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsPhaseInputEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of input table entries. The number of entries
+ is given by the value of upsPhaseNumInputs."
+ ::= { upsPhaseInput 2 }
+
+ upsPhaseInputEntry OBJECT-TYPE
+ SYNTAX UpsPhaseInputEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular input."
+ INDEX { upsPhaseInputTableIndex }
+ ::= { upsPhaseInputTable 1 }
+
+ UpsPhaseInputEntry ::= SEQUENCE {
+ upsPhaseInputTableIndex INTEGER,
+ upsPhaseNumInputPhases INTEGER,
+ upsPhaseInputVoltageOrientation INTEGER,
+ upsPhaseInputFrequency INTEGER,
+ upsPhaseInputType INTEGER,
+ upsPhaseInputName DisplayString
+ }
+
+ upsPhaseInputTableIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input identifier."
+ ::= { upsPhaseInputEntry 1 }
+
+ upsPhaseNumInputPhases OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of input phases utilized in this
+ device. The sum of all the upsPhaseNumInputPhases
+ variable indicates the number of rows in the
+ input phase table."
+ ::= { upsPhaseInputEntry 2 }
+
+ upsPhaseInputVoltageOrientation OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(1),
+ singlePhase(2),
+ splitPhase(3),
+ threePhasePhaseToNeutral(4),
+ threePhasePhaseToPhase(5)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input voltage orientation:
+ 1: unknown for this UPS
+ 2: singlePhase - phase 1 voltage is between Phase 1
+ and Neutral.
+ 3: splitPhase - phase 1 voltage is between Phase 1 and
+ Neutral; phase 2 voltage is between Phase 2 and Neutral;
+ phase 3 voltage is between Phase 1 and Phase 2.
+ 4: threePhasePhaseToNeutral - phase 1 voltage is between
+ Phase 1 and Neutral; phase 2 voltage is between Phase 2
+ and Neutral; phase 3 voltage is between Phase 3 and
+ Neutral.
+ 5: threePhasePhaseToPhase - phase 1 voltage is between
+ Phase 1 and Phase 2; phase 2 voltage is between Phase 2
+ and Phase 3; phase 3 voltage is between Phase 3 and
+ Phase 1."
+ ::= { upsPhaseInputEntry 3 }
+
+ upsPhaseInputFrequency OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input frequency in 0.1 Hertz, or -1 if it's unsupported
+ by this UPS."
+ ::= { upsPhaseInputEntry 4 }
+
+ upsPhaseInputType OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(1),
+ main(2),
+ bypass(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input type."
+ ::= { upsPhaseInputEntry 5 }
+
+ upsPhaseInputName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A name given to a particular input."
+ ::= { upsPhaseInputEntry 6 }
+
+-- Input Phase Table
+
+ upsPhaseInputPhaseTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsPhaseInputPhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of input table entries. The number of entries
+ is given by the sum of the upsPhaseNumInputPhases."
+ ::= { upsPhaseInput 3 }
+
+ upsPhaseInputPhaseEntry OBJECT-TYPE
+ SYNTAX UpsPhaseInputPhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular input phase."
+ INDEX { upsPhaseInputPhaseTableIndex, upsPhaseInputPhaseIndex }
+ ::= { upsPhaseInputPhaseTable 1 }
+
+ UpsPhaseInputPhaseEntry ::= SEQUENCE {
+ upsPhaseInputPhaseTableIndex INTEGER,
+ upsPhaseInputPhaseIndex INTEGER,
+ upsPhaseInputVoltage INTEGER,
+ upsPhaseInputMaxVoltage INTEGER,
+ upsPhaseInputMinVoltage INTEGER,
+ upsPhaseInputCurrent INTEGER,
+ upsPhaseInputMaxCurrent INTEGER,
+ upsPhaseInputMinCurrent INTEGER,
+ upsPhaseInputPower INTEGER,
+ upsPhaseInputMaxPower INTEGER,
+ upsPhaseInputMinPower INTEGER,
+ upsPhaseInputApparentPower INTEGER,
+ upsPhaseInputPowerFactor INTEGER,
+ upsPhaseInputVoltagePN INTEGER
+ }
+
+ upsPhaseInputPhaseTableIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input identifier."
+ ::= { upsPhaseInputPhaseEntry 1 }
+
+ upsPhaseInputPhaseIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input phase identifier."
+ ::= { upsPhaseInputPhaseEntry 2 }
+
+ upsPhaseInputVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input voltage in VAC, or -1 if it's unsupported
+ by this UPS."
+ ::= { upsPhaseInputPhaseEntry 3 }
+
+ upsPhaseInputMaxVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum input voltage in VAC measured
+ since the last reset (upsPhaseResetMaxMinValues), or
+ -1 if it's unsupported by this UPS.
+ Sampled every 30 seconds."
+ ::= { upsPhaseInputPhaseEntry 4 }
+
+ upsPhaseInputMinVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum input voltage in VAC measured
+ since the last reset (upsPhaseResetMaxMinValues), or
+ -1 if it's unsupported by this UPS.
+ Sampled every 30 seconds."
+ ::= { upsPhaseInputPhaseEntry 5 }
+
+ upsPhaseInputCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input current in 0.1 amperes, or -1 if it's
+ unsupported by this UPS."
+ ::= { upsPhaseInputPhaseEntry 6 }
+
+ upsPhaseInputMaxCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum input current in 0.1 amperes measured
+ since the last reset (upsPhaseResetMaxMinValues), or
+ -1 if it's unsupported by this UPS.
+ Sampled every 30 seconds."
+ ::= { upsPhaseInputPhaseEntry 7 }
+
+ upsPhaseInputMinCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum input current in 0.1 amperes measured
+ since the last reset (upsPhaseResetMaxMinValues), or
+ -1 if it's unsupported by this UPS.
+ Sampled every 30 seconds."
+ ::= { upsPhaseInputPhaseEntry 8 }
+
+ upsPhaseInputPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input power in Watts, or -1 if it's unsupported
+ by this UPS."
+ ::= { upsPhaseInputPhaseEntry 9 }
+
+ upsPhaseInputMaxPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum input power in Watts measured
+ since the last reset (upsPhaseResetMaxMinValues), or
+ -1 if it's unsupported by this UPS.
+ Sampled every 30 seconds."
+ ::= { upsPhaseInputPhaseEntry 10 }
+
+ upsPhaseInputMinPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum input power in Watts measured
+ since the last reset (upsPhaseResetMaxMinValues), or
+ -1 if it's unsupported by this UPS.
+ Sampled every 30 seconds."
+ ::= { upsPhaseInputPhaseEntry 11 }
+
+
+ upsPhaseInputApparentPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input apparent power of the UPS in kVA."
+ ::= { upsPhaseInputPhaseEntry 12 }
+
+ upsPhaseInputPowerFactor OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input power factor measured in hundredth."
+ ::= { upsPhaseInputPhaseEntry 13 }
+
+ upsPhaseInputVoltagePN OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input voltage measured across Phase to Neutral in VAC, or -1 if it's unsupported
+ by this UPS."
+ ::= { upsPhaseInputPhaseEntry 14 }
+ --
+ -- The Output group.
+ --
+
+ -- Number of Outputs
+
+ upsPhaseNumOutputs OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of output feeds to this device.
+ This variable indicates the number of rows in the
+ output table."
+ ::= { upsPhaseOutput 1 }
+
+ -- Output Table
+
+ upsPhaseOutputTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsPhaseOutputEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of output table entries. The number of entries
+ is given by the value of upsOutputNumPhases."
+ ::= { upsPhaseOutput 2 }
+
+ upsPhaseOutputEntry OBJECT-TYPE
+ SYNTAX UpsPhaseOutputEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular output."
+ INDEX { upsPhaseOutputTableIndex }
+ ::= { upsPhaseOutputTable 1 }
+
+ UpsPhaseOutputEntry ::= SEQUENCE {
+ upsPhaseOutputTableIndex INTEGER,
+ upsPhaseNumOutputPhases INTEGER,
+ upsPhaseOutputVoltageOrientation INTEGER,
+ upsPhaseOutputFrequency INTEGER
+ }
+
+ upsPhaseOutputTableIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output identifier."
+ ::= { upsPhaseOutputEntry 1 }
+
+ upsPhaseNumOutputPhases OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of output phases utilized in this
+ device. The sum of all the upsPhaseNumOutputPhases
+ variable indicates the number of rows in the
+ output phase table."
+ ::= { upsPhaseOutputEntry 2 }
+
+ upsPhaseOutputVoltageOrientation OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(1),
+ singlePhase(2),
+ splitPhase(3),
+ threePhasePhaseToNeutral(4),
+ threePhasePhaseToPhase(5)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output voltage orientation:
+ 1: unknown for this UPS
+ 2: singlePhase - phase 1 voltage is between Phase 1
+ and Neutral.
+ 3: splitPhase - phase 1 voltage is between Phase 1 and
+ Neutral; phase 2 voltage is between Phase 2 and Neutral;
+ phase 3 voltage is between Phase 1 and Phase 2.
+ 4: threePhasePhaseToNeutral - phase 1 voltage is between
+ Phase 1 and Neutral; phase 2 voltage is between Phase 2
+ and Neutral; phase 3 voltage is between Phase 3 and
+ Neutral.
+ 5: threePhasePhaseToPhase - phase 1 voltage is between
+ Phase 1 and Phase 2; phase 2 voltage is between Phase 2
+ and Phase 3; phase 3 voltage is between Phase 3 and
+ Phase 1."
+ ::= { upsPhaseOutputEntry 3 }
+
+ upsPhaseOutputFrequency OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output frequency in 0.1 Hertz, or -1 if it's
+ unsupported by this UPS."
+ ::= { upsPhaseOutputEntry 4 }
+
+ -- Output Phase Table
+
+ upsPhaseOutputPhaseTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsPhaseOutputPhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of output table entries. The number of
+ entries is given by the sum of the upsPhaseNumOutputPhases."
+ ::= { upsPhaseOutput 3 }
+
+ upsPhaseOutputPhaseEntry OBJECT-TYPE
+ SYNTAX UpsPhaseOutputPhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular output phase."
+ INDEX { upsPhaseOutputPhaseTableIndex, upsPhaseOutputPhaseIndex }
+ ::= { upsPhaseOutputPhaseTable 1 }
+
+ UpsPhaseOutputPhaseEntry ::= SEQUENCE {
+ upsPhaseOutputPhaseTableIndex INTEGER,
+ upsPhaseOutputPhaseIndex INTEGER,
+ upsPhaseOutputVoltage INTEGER,
+ upsPhaseOutputCurrent INTEGER,
+ upsPhaseOutputMaxCurrent INTEGER,
+ upsPhaseOutputMinCurrent INTEGER,
+ upsPhaseOutputLoad INTEGER,
+ upsPhaseOutputMaxLoad INTEGER,
+ upsPhaseOutputMinLoad INTEGER,
+ upsPhaseOutputPercentLoad INTEGER,
+ upsPhaseOutputMaxPercentLoad INTEGER,
+ upsPhaseOutputMinPercentLoad INTEGER,
+ upsPhaseOutputPower INTEGER,
+ upsPhaseOutputMaxPower INTEGER,
+ upsPhaseOutputMinPower INTEGER,
+ upsPhaseOutputPercentPower INTEGER,
+ upsPhaseOutputMaxPercentPower INTEGER,
+ upsPhaseOutputMinPercentPower INTEGER,
+ upsPhaseOutputPowerFactor INTEGER,
+ upsPhaseOutputApparentPower INTEGER,
+ upsPhaseOutputInverterVoltage INTEGER,
+ upsPhaseOutputVoltagePN INTEGER
+ }
+
+ upsPhaseOutputPhaseTableIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output identifier."
+ ::= { upsPhaseOutputPhaseEntry 1 }
+
+ upsPhaseOutputPhaseIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output phase identifier."
+ ::= { upsPhaseOutputPhaseEntry 2 }
+
+ upsPhaseOutputVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output voltage in VAC, or -1 if it's unsupported
+ by this UPS."
+ ::= { upsPhaseOutputPhaseEntry 3 }
+
+ upsPhaseOutputCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output current in 0.1 amperes drawn
+ by the load on the UPS, or -1 if it's unsupported
+ by this UPS."
+ ::= { upsPhaseOutputPhaseEntry 4 }
+
+ upsPhaseOutputMaxCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum output current in 0.1 amperes measured
+ since the last reset (upsPhaseResetMaxMinValues), or
+ -1 if it's unsupported by this UPS.
+ Sampled every 30 seconds."
+ ::= { upsPhaseOutputPhaseEntry 5 }
+
+ upsPhaseOutputMinCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum output current in 0.1 amperes measured
+ since the last reset (upsPhaseResetMaxMinValues), or
+ -1 if it's unsupported by this UPS.
+ Sampled every 30 seconds."
+ ::= { upsPhaseOutputPhaseEntry 6 }
+
+ upsPhaseOutputLoad OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output load in VA, or -1 if it's unsupported
+ by this UPS."
+ ::= { upsPhaseOutputPhaseEntry 7 }
+
+ upsPhaseOutputMaxLoad OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum output load in VA measured
+ since the last reset (upsPhaseResetMaxMinValues), or
+ -1 if it's unsupported by this UPS.
+ Sampled every 30 seconds."
+ ::= { upsPhaseOutputPhaseEntry 8 }
+
+ upsPhaseOutputMinLoad OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum output load in VA measured
+ since the last reset (upsPhaseResetMaxMinValues), or
+ -1 if it's unsupported by this UPS.
+ Sampled every 30 seconds."
+ ::= { upsPhaseOutputPhaseEntry 9 }
+
+ upsPhaseOutputPercentLoad OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The percentage of the UPS load capacity in VA at
+ redundancy @ (n + x) presently being used on this
+ output phase, or -1 if it's unsupported by this UPS."
+ ::= { upsPhaseOutputPhaseEntry 10 }
+
+ upsPhaseOutputMaxPercentLoad OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum percentage of the UPS load capacity in
+ VA measured at redundancy @ (n + x) presently
+ being used on this output phase since the last reset
+ (upsPhaseResetMaxMinValues), or -1 if it's unsupported
+ by this UPS. Sampled every 30 seconds."
+ ::= { upsPhaseOutputPhaseEntry 11 }
+
+ upsPhaseOutputMinPercentLoad OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum percentage of the UPS load capacity in
+ VA measured at redundancy @ (n + x) presently
+ being used on this output phase since the last reset
+ (upsPhaseResetMaxMinValues), or -1 if it's unsupported
+ by this UPS. Sampled every 30 seconds."
+ ::= { upsPhaseOutputPhaseEntry 12 }
+
+ upsPhaseOutputPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output power in Watts, or -1 if it's
+ unsupported by this UPS."
+ ::= { upsPhaseOutputPhaseEntry 13 }
+
+ upsPhaseOutputMaxPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum output power in Watts measured
+ since the last reset (upsPhaseResetMaxMinValues), or
+ -1 if it's unsupported by this UPS.
+ Sampled every 30 seconds."
+ ::= { upsPhaseOutputPhaseEntry 14 }
+
+ upsPhaseOutputMinPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum output power in Watts measured
+ since the last reset (upsPhaseResetMaxMinValues), or
+ -1 if it's unsupported by this UPS.
+ Sampled every 30 seconds."
+ ::= { upsPhaseOutputPhaseEntry 15 }
+
+ upsPhaseOutputPercentPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The percentage of the UPS power capacity in Watts at
+ redundancy @ (n + x) presently being used on this
+ output phase, or -1 if it's unsupported by this UPS."
+ ::= { upsPhaseOutputPhaseEntry 16 }
+
+ upsPhaseOutputMaxPercentPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum percentage of the UPS power capacity
+ in Watts measured at redundancy @ (n + x) presently
+ being used on this output phase since the last
+ reset (upsPhaseResetMaxMinValues), or -1 if it's
+ unsupported by this UPS. Sampled every 30 seconds."
+ ::= { upsPhaseOutputPhaseEntry 17 }
+
+ upsPhaseOutputMinPercentPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum percentage of the UPS power capacity
+ in Watts measured at redundancy @ (n + x) presently
+ being used on this output phase since the last
+ reset (upsPhaseResetMaxMinValues), or -1 if it's
+ unsupported by this UPS. Sampled every 30 seconds."
+ ::= { upsPhaseOutputPhaseEntry 18 }
+
+ upsPhaseOutputPowerFactor OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Output power factor of the UPS in hundredth."
+ ::= { upsPhaseOutputPhaseEntry 19 }
+ upsPhaseOutputApparentPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Apparent power in kVA"
+ ::= { upsPhaseOutputPhaseEntry 20 }
+
+ upsPhaseOutputInverterVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Output voltage in VAC measured at the output of inverter."
+ ::= { upsPhaseOutputPhaseEntry 21 }
+
+ upsPhaseOutputVoltagePN OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output voltage measured across Phase to Neutral in VAC, or -1 if it's unsupported
+ by this UPS."
+ ::= { upsPhaseOutputPhaseEntry 22 }
+
+-- the upsOutletGroupStatus group
+
+upsOutletGroupStatusTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of outlet groups for the UPS."
+ ::= { upsOutletGroupStatus 1 }
+
+upsOutletGroupStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsOutletGroupStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting status of the outlet groups. The number of
+ entries is contained in the upsOutletGroupStatusTableSize OID."
+ ::= { upsOutletGroupStatus 2 }
+
+upsOutletGroupStatusEntry OBJECT-TYPE
+ SYNTAX UpsOutletGroupStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The outlet group status to get."
+ INDEX { upsOutletGroupStatusIndex}
+ ::= { upsOutletGroupStatusTable 1 }
+
+UpsOutletGroupStatusEntry ::=
+ SEQUENCE {
+ upsOutletGroupStatusIndex INTEGER,
+ upsOutletGroupStatusName DisplayString,
+ upsOutletGroupStatusGroupState INTEGER,
+ upsOutletGroupStatusCommandPending INTEGER,
+ upsOutletGroupStatusOutletType INTEGER,
+ upsOutletGroupStatusGroupFullState DisplayString
+ }
+
+upsOutletGroupStatusIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the outlet group entry."
+ ::= { upsOutletGroupStatusEntry 1 }
+
+upsOutletGroupStatusName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the outlet group. This OID is provided
+ for informational purposes only. This value is set
+ by the upsOutletGroupConfigName OID."
+ ::= { upsOutletGroupStatusEntry 2 }
+
+upsOutletGroupStatusGroupState OBJECT-TYPE
+ SYNTAX INTEGER {
+ upsOutletGroupStatusOn (1),
+ upsOutletGroupStatusOff (2),
+ upsOutletGroupStatusUnknown (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this variable will return the outlet group state. If the outlet
+ group is on, the upsOutletGroupStatusOn (1) value will be returned. If
+ the outlet group is off, the upsOutletGroupStatusOff (2) value will be
+ returned. If the state of the outlet group cannot be determined, the
+ upsOutletGroupStatusUnknown (3) value will be returned."
+
+ ::= { upsOutletGroupStatusEntry 3 }
+
+upsOutletGroupStatusCommandPending OBJECT-TYPE
+ SYNTAX INTEGER {
+ upsOutletGroupCommandPending (1),
+ upsOutletGroupNoCommandPending (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this variable will return the command pending
+ state of the outlet group. If a command is pending on the
+ outlet group, the upsOutletGroupCommandPending (1) value
+ will be returned. If there is not a command pending
+ on the outlet group, the upsOutletGroupNoCommandPending (2)
+ will be returned."
+ ::= { upsOutletGroupStatusEntry 4 }
+
+upsOutletGroupStatusOutletType OBJECT-TYPE
+ SYNTAX INTEGER {
+ upsSwitchedOutletGroup (1),
+ upsMainOutletGroup (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this variable will return the type of outlet group.
+ If present in the system, the main outlet group is
+ 'unswitched' and must be on in order for any of the switched
+ outlet groups to be on. Conversely, if the main outlet group
+ is off, all the switched outlet groups must also be off.
+ Therefore, any commands made to the main outlet group that
+ turn it off will also be applied to all switched outlet
+ groups that are on, unless the state of a switched outlet
+ group prevents it, in which case the command will fail."
+ ::= { upsOutletGroupStatusEntry 5 }
+
+upsOutletGroupStatusGroupFullState OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An ASCII string containing the 32 flags representing the
+ current state(s) of the outlet group. If the Network Card
+ is unable to determine the state of the outlet group, this
+ variable is set to 'UNKNOWN'.
+
+ The flags are numbered from 1 to 32, and read from left to
+ right. The flags are defined as follows:
+
+ Flag 1: On
+ Flag 2: Off
+ Flag 3: Reboot in Progress
+ Flag 4: Shutdown in Progress
+
+ Flag 5: Sleep in Progress
+ Flag 6: <Not Used>
+ Flag 7: <Not Used>
+ Flag 8: Pending Load Shed
+
+ Flag 9: Pending On Delay
+ Flag 10: Pending Off Delay
+ Flag 11: Pending AC Presence
+ Flag 12: Pending On Minimum Runtime
+
+ Flag 13: Member Group Process 1
+ Flag 14: Member Group Process 2
+ Flag 15: Runtime Below Turn On Setting
+ Flag 16: <Not Used>
+
+ Flag 17: <Not Used>
+ Flag 18: <Not Used>
+ Flag 19: <Not Used>
+ Flag 20: <Not Used>
+
+ Flag 21: <Not Used>
+ Flag 22: <Not Used>
+ Flag 23: <Not Used>
+ Flag 24: <Not Used>
+
+ Flag 25: <Not Used>
+ Flag 26: <Not Used>
+ Flag 27: <Not Used>
+ Flag 28: <Not Used>
+
+ Flag 29: <Not Used>
+ Flag 30: <Not Used>
+ Flag 31: <Not Used>
+ Flag 32: <Not Used>"
+ ::= { upsOutletGroupStatusEntry 6 }
+
+-- the upsOutletGroupConfig group
+
+upsOutletGroupConfigTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of outlet groups for the UPS."
+ ::= { upsOutletGroupConfig 1 }
+
+upsOutletGroupConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsOutletGroupConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The list of outlet groups to configure. The number of entries
+ is defined by the upsOutletGroupConfigTableSize OID."
+ ::= { upsOutletGroupConfig 2 }
+
+upsOutletGroupConfigEntry OBJECT-TYPE
+ SYNTAX UpsOutletGroupConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The outlet groups to configure."
+ INDEX { upsOutletGroupConfigIndex}
+ ::= { upsOutletGroupConfigTable 1 }
+
+UpsOutletGroupConfigEntry ::=
+ SEQUENCE {
+ upsOutletGroupConfigIndex INTEGER,
+ upsOutletGroupConfigName DisplayString,
+ upsOutletGroupConfigPowerOnDelay INTEGER,
+ upsOutletGroupConfigPowerOffDelay INTEGER,
+ upsOutletGroupConfigRebootDuration INTEGER,
+ upsOutletGroupConfigMinReturnRuntime INTEGER,
+ upsOutletGroupConfigOutletType INTEGER,
+ upsOutletGroupConfigLoadShedControlSkipOffDelay INTEGER,
+ upsOutletGroupConfigLoadShedControlAutoRestart INTEGER,
+ upsOutletGroupConfigLoadShedControlTimeOnBattery INTEGER,
+ upsOutletGroupConfigLoadShedControlRuntimeRemaining INTEGER,
+ upsOutletGroupConfigLoadShedControlInOverload INTEGER,
+ upsOutletGroupConfigLoadShedTimeOnBattery INTEGER,
+ upsOutletGroupConfigLoadShedRuntimeRemaining INTEGER
+ }
+
+upsOutletGroupConfigIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the outlet group entry."
+ ::= { upsOutletGroupConfigEntry 1 }
+
+upsOutletGroupConfigName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the outlet group."
+ ::= { upsOutletGroupConfigEntry 2 }
+
+upsOutletGroupConfigPowerOnDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The amount of time (seconds) the outlet group will delay
+ powering on when the delayed on, reboot, or shutdown command is
+ applied. Allowed values vary by UPS model. The value of -1 is
+ used for Never if supported by the UPS and the outlet group."
+ ::= { upsOutletGroupConfigEntry 3 }
+
+upsOutletGroupConfigPowerOffDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The amount of time (seconds) the outlet group will delay
+ powering off when the delayed off, reboot, or shutdown command is
+ applied. Allowed values vary by UPS model. The value of -1 is
+ used for Never if supported by the UPS and the outlet group."
+ ::= { upsOutletGroupConfigEntry 4 }
+
+upsOutletGroupConfigRebootDuration OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "During a reboot sequence, power is turned off and then
+ back on. This OID defines the amount of time to wait
+ (seconds) after turning the power off, at the start
+ of the sequence, before initiating the power on sequence.
+ Allowed values vary by UPS model."
+ ::= { upsOutletGroupConfigEntry 5 }
+
+upsOutletGroupConfigMinReturnRuntime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "In an Outlet Group shutdown sequence, the Outlet Group cycles
+ power off then on. This OID defines the minimum amount of UPS
+ runtime (seconds) that is required in order to power the
+ Outlet Group on. Allowed values vary by UPS model."
+ ::= { upsOutletGroupConfigEntry 6 }
+
+upsOutletGroupConfigOutletType OBJECT-TYPE
+ SYNTAX INTEGER {
+ upsSwitchedOutletGroup (1),
+ upsMainOutletGroup (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this variable will return the type of outlet group.
+ If present in the system, the main outlet group is
+ 'unswitched' and must be on in order for any of the switched
+ outlet groups to be on. Conversely, if the main outlet group
+ is off, all the switched outlet groups must also be off.
+ Therefore, any commands made to the main outlet group that
+ turn it off will also be applied to all switched outlet
+ groups that are on, unless the state of a switched outlet
+ group prevents it, in which case the command will fail."
+ ::= { upsOutletGroupConfigEntry 7 }
+
+upsOutletGroupConfigLoadShedControlSkipOffDelay OBJECT-TYPE
+ SYNTAX INTEGER {
+ upsOutletGroupConfigSkipOffDelay (1),
+ upsOutletGroupConfigUseOffDelay (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Configures whether the outlet group's off delay setting
+ (upsOutletGroupConfigPowerOffDelay) will be used in a load
+ shedding situation, where applicable."
+ ::= { upsOutletGroupConfigEntry 8 }
+
+upsOutletGroupConfigLoadShedControlAutoRestart OBJECT-TYPE
+ SYNTAX INTEGER {
+ upsOutletGroupConfigAutoRestart (1),
+ upsOutletGroupConfigManualRestart (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Configures whether the outlet group will automatically restart
+ after a load shedding situation, where applicable."
+ ::= { upsOutletGroupConfigEntry 9 }
+
+upsOutletGroupConfigLoadShedControlTimeOnBattery OBJECT-TYPE
+ SYNTAX INTEGER {
+ upsOutletGroupConfigDisableTimeOnBatteryLoadShed (1),
+ upsOutletGroupConfigEnableTimeOnBatteryLoadShed (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Configures whether the outlet group will load shed (turn off)
+ after the UPS's time on battery has exceeded the
+ upsOutletGroupConfigLoadShedTimeOnBattery OID setting. The
+ settings for upsOutletGroupConfigLoadShedControlSkipOffDelay
+ and upsOutletGroupConfigLoadShedControlAutoRestart are valid
+ for this load shed condition."
+ ::= { upsOutletGroupConfigEntry 10 }
+
+upsOutletGroupConfigLoadShedControlRuntimeRemaining OBJECT-TYPE
+ SYNTAX INTEGER {
+ upsOutletGroupConfigDisableRuntimeRemainingLoadShed (1),
+ upsOutletGroupConfigEnableRuntimeRemainingLoadShed (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Configures whether the outlet group will load shed (turn off)
+ when the UPS is on battery and the remaining runtime is less
+ than the upsOutletGroupConfigLoadShedRuntimeRemaining OID
+ setting. The settings for
+ upsOutletGroupConfigLoadShedControlSkipOffDelay and
+ upsOutletGroupConfigLoadShedControlAutoRestart are valid for
+ this load shed condition."
+ ::= { upsOutletGroupConfigEntry 11 }
+
+upsOutletGroupConfigLoadShedControlInOverload OBJECT-TYPE
+ SYNTAX INTEGER {
+ upsOutletGroupConfigDisableInOverloadLoadShed (1),
+ upsOutletGroupConfigEnableInOverloadLoadShed (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Configures whether the outlet group will load shed (turn off)
+ when the UPS is in an overload condition. The setting for
+ upsOutletGroupConfigLoadShedControlSkipOffDelay is valid for
+ this load shed condition. Returns -1 if not supported by this
+ outlet group."
+ ::= { upsOutletGroupConfigEntry 12 }
+
+upsOutletGroupConfigLoadShedTimeOnBattery OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "When the UPS has been on battery for more time than this
+ value, the outlet group will turn off if this condition is
+ enabled by the upsOutletGroupConfigLoadShedControlTimeOnBattery
+ OID. Allowed values vary by UPS model."
+ ::= { upsOutletGroupConfigEntry 13 }
+
+upsOutletGroupConfigLoadShedRuntimeRemaining OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "When the runtime remaining is less than this value, the outlet
+ group will turn off if this condition is enabled by the
+ upsOutletGroupConfigLoadShedControlRuntimeRemaining OID.
+ Allowed values vary by UPS model."
+ ::= { upsOutletGroupConfigEntry 14 }
+
+-- the upsOutletGroupControl group
+
+upsOutletGroupControlTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of outlet groups for the UPS."
+ ::= { upsOutletGroupControl 1 }
+
+upsOutletGroupControlTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsOutletGroupControlEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for control of individual outlet groups. The number of
+ entries is contained in the upsOutletGroupControlTableSize OID."
+ ::= { upsOutletGroupControl 2 }
+
+upsOutletGroupControlEntry OBJECT-TYPE
+ SYNTAX UpsOutletGroupControlEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The outlet group to control."
+ INDEX { upsOutletGroupControlIndex}
+ ::= { upsOutletGroupControlTable 1 }
+
+UpsOutletGroupControlEntry ::=
+ SEQUENCE {
+ upsOutletGroupControlIndex INTEGER,
+ upsOutletGroupControlName DisplayString,
+ upsOutletGroupControlCommand INTEGER,
+ upsOutletGroupControlOutletType INTEGER
+ }
+
+upsOutletGroupControlIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the outlet group entry."
+ ::= { upsOutletGroupControlEntry 1 }
+
+upsOutletGroupControlName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the outlet group. This OID is provided
+ for informational purposes only. This value is set
+ by the upsOutletGroupConfigName OID."
+ ::= { upsOutletGroupControlEntry 2 }
+
+upsOutletGroupControlCommand OBJECT-TYPE
+ SYNTAX INTEGER {
+ upsOutletGroupImmediateOn (1),
+ upsOutletGroupImmediateOff (2),
+ upsOutletGroupImmediateRebootWithOrWithoutAC (3),
+ upsOutletGroupDelayedOn (4),
+ upsOutletGroupDelayedOff (5),
+ upsOutletGroupDelayedRebootWithOrWithoutAC (6),
+ upsOutletGroupCancelPendingCommand (7),
+ upsOutletGroupControlUnknown (8),
+ upsOutletGroupImmediateRebootShutdown (9),
+ upsOutletGroupDelayedRebootShutdown (10)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this variable will return the outlet group state. If the outlet
+ group is on, the upsOutletGroupImmediateOn (1) value will be returned. If
+ the outlet group is off, the upsOutletGroupImmediateOff (2) value will be
+ returned.
+
+ If the state of the outlet group cannot be determined, the
+ upsOutletGroupControlUnknown (8) value will be returned.
+
+ Setting this variable to upsOutletGroupImmediateOn (1) will turn the
+ outlet group on immediately.
+
+ Setting this variable to upsOutletGroupImmediateOff (2) will turn the
+ outlet group off immediately.
+
+ Setting this variable to upsOutletGroupImmediateRebootWithOrWithoutAC (3)
+ will turn the outlet group off immediately, wait the
+ upsOutletGroupConfigRebootDuration OID time, wait the
+ upsOutletGroupConfigPowerOnDelay OID, and then turn the outlet group on
+ regardless of the AC input power on the UPS.
+
+ Setting this variable to upsOutletGroupDelayedOn (4) will turn the outlet
+ group on after the upsOutletGroupConfigPowerOnDelay OID has elapsed.
+
+ Setting this variable to upsOutletGroupDelayedOff (5) will turn the outlet
+ group off after the upsOutletGroupConfigPowerOffDelay OID has elapsed.
+
+ Setting this variable to upsOutletGroupDelayedRebootWithOrWithoutAC (6)
+ will turn the outlet group off after the upsOutletGroupConfigPowerOffDelay
+ OID has elapsed, wait the upsOutletGroupConfigRebootDuration OID time, wait
+ the upsOutletGroupConfigPowerOnDelay OID, and then turn the outlet group
+ on regardless of the AC input power on the UPS.
+
+ Setting this variable to upsOutletGroupCancelPendingCommand (7) will
+ cause any pending command to this outlet group to be canceled.
+
+ Setting this variable to upsOutletGroupImmediateRebootShutdown (9) will
+ turn the outlet group off immediately, wait for the AC power to return to normal
+ (a minimum of the upsOutletGroupConfigRebootDuration OID time), wait the
+ upsOutletGroupConfigPowerOnDelay OID time, and then turn the outlet
+ group on.
+
+ Setting this variable to upsOutletGroupDelayedRebootShutdown (10) will
+ turn the outlet group off after the upsOutletGroupConfigPowerOffDelay OID
+ has elapsed, wait for the AC power to return to normal (a minimum of the
+ upsOutletGroupConfigRebootDuration OID time), wait the
+ upsOutletGroupConfigPowerOnDelay OID time, and then turn the outlet
+ group on.
+
+ In systems with a main outlet group, commands to the main outlet group must
+ be performed with caution. It may be clearer to use the ups control commands
+ available from upsAdvControl... OIDs. If any command is made to the main
+ outlet group that will turn it off, one of two things will happen:
+ 1) If any switched outlet group is in a state that prevents this command
+ from occurring on the main outlet group, the command will be rejected. Note
+ that a switched outlet group being on without a command in progress is not a
+ state that normally prevents the command.
+ 2) The command will be accepted and applied to the main outlet group and all
+ switched outlet groups that are on.
+
+ There is one additional special case for systems with a main outlet group.
+ If the main outlet group is off and a switched outlet group is commanded to
+ turn on, the on command will be applied to both the main outlet group and
+ that switched outlet group."
+ ::= { upsOutletGroupControlEntry 3 }
+
+upsOutletGroupControlOutletType OBJECT-TYPE
+ SYNTAX INTEGER {
+ upsSwitchedOutletGroup (1),
+ upsMainOutletGroup (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this variable will return the type of outlet group.
+ If present in the system, the main outlet group is
+ 'unswitched' and must be on in order for any of the switched
+ outlet groups to be on. Conversely, if the main outlet group
+ is off, all the switched outlet groups must also be off.
+ Therefore, any commands made to the main outlet group that
+ turn it off will also be applied to all switched outlet
+ groups that are on, unless the state of a switched outlet
+ group prevents it, in which case the command will fail."
+ ::= { upsOutletGroupControlEntry 4 }
+
+-- the upsDiagnosticIM group
+
+upsDiagIMTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of Intelligence Modules in or attached to the UPS."
+ ::= { upsDiagnosticIM 1 }
+
+upsDiagIMTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsDiagIMEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for diagnostics of individual Intelligence Modules. The number of
+ entries is contained in the upsDiagIMTableSize OID."
+ ::= { upsDiagnosticIM 2 }
+
+upsDiagIMEntry OBJECT-TYPE
+ SYNTAX UpsDiagIMEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The diagnostics and information of an Intelligence Module."
+ INDEX { upsDiagIMIndex}
+ ::= { upsDiagIMTable 1 }
+
+UpsDiagIMEntry ::=
+ SEQUENCE {
+ upsDiagIMIndex INTEGER,
+ upsDiagIMType INTEGER,
+ upsDiagIMStatus INTEGER,
+ upsDiagIMFirmwareRev DisplayString,
+ upsDiagIMSlaveFirmwareRev DisplayString,
+ upsDiagIMHardwareRev DisplayString,
+ upsDiagIMSerialNum DisplayString,
+ upsDiagIMManufactureDate DisplayString,
+ upsDiagIMInControl INTEGER
+ }
+
+upsDiagIMIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the Intelligence Module entry."
+ ::= { upsDiagIMEntry 1 }
+
+upsDiagIMType OBJECT-TYPE
+ SYNTAX INTEGER {
+ imUnknown (1),
+ imMIM (2),
+ imRIM (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The type of the Intelligence Module.
+ imUnknown(1) indicates the IM type is unknown.
+ imMIM(2) indicates the IM type is a Main Intelligence Module.
+ imRIM(3) indicates the IM type is Redundant Intelligence Module."
+ ::= { upsDiagIMEntry 2 }
+
+upsDiagIMStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ notInstalled (2),
+ offOk (3),
+ onOk (4),
+ offFail (5),
+ onFail (6),
+ lostComm (7)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the Intelligence Module.
+ unknown(1) indicates the device status is unknown.
+ notInstalled(2) indicates the device is not installed.
+ offOk(3) indicates the device status is off and OK.
+ onOk(4) indicates the device status is on and OK.
+ offFail(5) indicates the device status is off and failed.
+ onFail(6) indicates the device status is on and failed.
+ lostComm(7) indicates the device has lost communication."
+ ::= { upsDiagIMEntry 3 }
+
+upsDiagIMFirmwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The firmware revision of the Intelligence Module."
+ ::= { upsDiagIMEntry 4 }
+
+upsDiagIMSlaveFirmwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The slave firmware revision of the Intelligence Module."
+ ::= { upsDiagIMEntry 5 }
+
+upsDiagIMHardwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The hardware revision of the Intelligence Module."
+ ::= { upsDiagIMEntry 6 }
+
+upsDiagIMSerialNum OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The serial number of the Intelligence Module."
+ ::= { upsDiagIMEntry 7 }
+
+upsDiagIMManufactureDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The manufacture date of the Intelligence Module."
+ ::= { upsDiagIMEntry 8 }
+upsDiagIMInControl OBJECT-TYPE
+ SYNTAX INTEGER {
+ activeInControl (1),
+ passive (2),
+ unknown (3),
+ fault (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Intelligence Module state.
+ activeInControl(1) indicates the IM is active and in control.
+ passive(2) indicates the IM is in passive state.
+ unknown(3) indicates the IM is in unknown state.
+ fault(4) indicates the IM is in fault state."
+ ::= { upsDiagIMEntry 9 }
+
+-- the upsDiagnosticPowerModules group
+
+upsDiagPMTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum number of Power Modules supported by the UPS."
+ ::= { upsDiagnosticPowerModules 1 }
+
+upsDiagPMTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsDiagPMEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for diagnostics of Individual Power modules. The number of
+ entries is contained in the upsDiagPMTableSize OID."
+ ::= { upsDiagnosticPowerModules 2 }
+
+upsDiagPMEntry OBJECT-TYPE
+ SYNTAX UpsDiagPMEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The diagnostics of an Power Module."
+ INDEX { upsDiagPMIndex}
+ ::= { upsDiagPMTable 1 }
+
+UpsDiagPMEntry ::=
+ SEQUENCE {
+ upsDiagPMIndex INTEGER,
+ upsDiagPMStatus INTEGER,
+ upsDiagPMFirmwareRev DisplayString,
+ upsDiagPMHardwareRev DisplayString,
+ upsDiagPMSerialNum DisplayString,
+ upsDiagPMManufactureDate DisplayString,
+ upsDiagPMModelNum DisplayString
+ }
+
+upsDiagPMIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the Power Module entry."
+ ::= { upsDiagPMEntry 1 }
+
+upsDiagPMStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ notInstalled (2),
+ offOk (3),
+ onOk (4),
+ offFail (5),
+ onFail (6),
+ lostComm (7)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the Power Module.
+ unknown(1) indicates the device status is unknown.
+ notInstalled(2) indicates the device is not installed.
+ offOk(3) indicates the device status is off and OK.
+ onOk(4) indicates the device status is on and OK.
+ offFail(5) indicates the device status is off and failed.
+ onFail(6) indicates the device status is on and failed.
+ lostComm(7) indicates the device has lost communication."
+ ::= { upsDiagPMEntry 2 }
+
+upsDiagPMFirmwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The firmware revision of the Power Module."
+ ::= { upsDiagPMEntry 3 }
+
+upsDiagPMHardwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The hardware revision of the Power Module."
+ ::= { upsDiagPMEntry 4 }
+
+upsDiagPMSerialNum OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The serial number of the Power Module."
+ ::= { upsDiagPMEntry 5 }
+
+upsDiagPMManufactureDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The manufacture date of the Power Module."
+ ::= { upsDiagPMEntry 6 }
+
+upsDiagPMModelNum OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The model number of the Power Module."
+ ::= { upsDiagPMEntry 7 }
+
+upsDiagPMLifetimeInfoTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsDiagPMLifetimeInfoEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for diagnostics of individual power module's lifetime information.
+ The number of entries is contained in the upsDiagPMTableSize OID."
+ ::= { upsDiagnosticPowerModules 3 }
+
+upsDiagPMLifetimeInfoEntry OBJECT-TYPE
+ SYNTAX UpsDiagPMLifetimeInfoEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The diagnostics of a Power Module lifetime information."
+ INDEX { upsDiagPMLifetimeInfoIndex}
+ ::= { upsDiagPMLifetimeInfoTable 1 }
+
+UpsDiagPMLifetimeInfoEntry ::=
+ SEQUENCE {
+ upsDiagPMLifetimeInfoIndex INTEGER,
+ upsDiagPMLifetimeStatus INTEGER,
+ upsDiagPMEstmtdLifetimeRmng INTEGER,
+ upsDiagPMEstmtdLifetimeRmngPct INTEGER,
+ upsDiagPMFanLifetimeStatus INTEGER,
+ upsDiagPMFanEstmtdLifetimeRmng INTEGER,
+ upsDiagPMFanEstmtdLifetimeRmngPct INTEGER
+
+ }
+
+upsDiagPMLifetimeInfoIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the Power Module lifetime information entry."
+ ::= { upsDiagPMLifetimeInfoEntry 1 }
+
+upsDiagPMLifetimeStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ ok (1),
+ nearEnd (2),
+ exceeded (3),
+ unknown (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the Power Module lifetime information.
+ ok(1) indicates the device lifetime status is OK.
+ nearEnd(2) indicates the device lifetime status is near end.
+ exceeded(3) indicates the device lifetime status is exceeded.
+ unknown(4) indicates the device lifetime status is unknown."
+
+ ::= { upsDiagPMLifetimeInfoEntry 2 }
+
+upsDiagPMEstmtdLifetimeRmng OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Displays the time remaining for the module before it should be replaced.
+ Measured in months. This value is set when you originally install the module."
+ ::= { upsDiagPMLifetimeInfoEntry 3 }
+
+upsDiagPMEstmtdLifetimeRmngPct OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Displays the percentage of the total lifetime remaining for the module
+ before it should be replaced."
+ ::= { upsDiagPMLifetimeInfoEntry 4 }
+
+upsDiagPMFanLifetimeStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ ok (1),
+ nearEnd (2),
+ exceeded (3),
+ unknown (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the Power Module Fan lifetime information.
+ ok(1) indicates the device lifetime status is OK.
+ nearEnd(2) indicates the device lifetime status is near end.
+ exceeded(3) indicates the device lifetime status is exceeded.
+ unknown(4) indicates the device lifetime status is unknown."
+ ::= { upsDiagPMLifetimeInfoEntry 5 }
+
+upsDiagPMFanEstmtdLifetimeRmng OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Displays the time remaining, measured in months, before the module's
+ fan should be replaced. It is reset by the field service engineer when
+ a new fan is installed."
+ ::= { upsDiagPMLifetimeInfoEntry 6 }
+
+upsDiagPMFanEstmtdLifetimeRmngPct OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Displays the percentage of the total lifetime remaining
+ before the module's fan should be replaced."
+ ::= { upsDiagPMLifetimeInfoEntry 7 }
+
+upsDiagPMEnclDoorFltrTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum number of power module enclosures attached to the UPS."
+ ::= { upsDiagnosticPowerModules 4 }
+
+upsDiagPMEnclDoorFltrTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsDiagPMEnclDoorFltrEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for the diagnostics of individual power module enclosure door filters.
+ The number of entries is contained in the upsDiagPMEnclDoorFltrTableSize OID."
+ ::= { upsDiagnosticPowerModules 5 }
+
+upsDiagPMEnclDoorFltrEntry OBJECT-TYPE
+ SYNTAX UpsDiagPMEnclDoorFltrEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Power module door filter diagnostics info."
+ INDEX { upsDiagPMEnclIndex}
+ ::= { upsDiagPMEnclDoorFltrTable 1 }
+
+UpsDiagPMEnclDoorFltrEntry ::=
+ SEQUENCE {
+ upsDiagPMEnclIndex INTEGER,
+ upsDiagPMEnclDoorFltrLifetime INTEGER,
+ upsDiagPMEnclDoorFltrStatus INTEGER,
+ upsDiagPMEnclDoorFltrEstmtdLifetimeRmng INTEGER,
+ upsDiagPMEnclDoorFltrEstmtdLifetimeRmngPct INTEGER
+ }
+upsDiagPMEnclIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the power module enclosure entry.
+ Enclosure 0 indicates the Power enclosure 1.
+ Enclosure 1 indicates the Power enclosure 2."
+ ::= { upsDiagPMEnclDoorFltrEntry 1 }
+
+upsDiagPMEnclDoorFltrLifetime OBJECT-TYPE
+ SYNTAX INTEGER {
+ heavyFiltration15days (1),
+ normalFiltration30days(2),
+ lightFiltration60days (3),
+ notPresent (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Door filter replacement time interval, based on the installation enivironment.
+ heavyFiltration15days (1) indicates door filter needs to be replaced within 15 days.
+ normalFiltration30days (2) indicates door filter needs to be replaced within 30 days.
+ lightFiltration60days (3) indicates door filter needs to be replaced within 60 days.
+ notPresent(4) indicates that the door filter is not present."
+ ::= { upsDiagPMEnclDoorFltrEntry 2 }
+
+upsDiagPMEnclDoorFltrStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ ok (1),
+ nearEnd (2),
+ exceeded (3),
+ unknown (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the current status of the door filter.
+ ok(1) indicates the device lifetime status is OK.
+ nearEnd(2) indicates the device lifetime status is near end.
+ exceeded(3) indicates the device lifetime status is exceeded.
+ unknown(4) indicates the device lifetime status is unknown."
+ ::= { upsDiagPMEnclDoorFltrEntry 3 }
+
+upsDiagPMEnclDoorFltrEstmtdLifetimeRmng OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Displays the time remaining, measured in days, before the module door filter should be replaced.
+ This value is set when you originally install the module."
+ ::= { upsDiagPMEnclDoorFltrEntry 4 }
+
+upsDiagPMEnclDoorFltrEstmtdLifetimeRmngPct OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Displays the percentage of the total lifetime remaining for the module
+ door filter before it should be replaced."
+ ::= { upsDiagPMEnclDoorFltrEntry 5 }
+
+
+
+-- the upsDiagnosticBatteries group
+
+upsDiagBatteryTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum number of batteries supported by the UPS."
+ ::= { upsDiagnosticBatteries 1 }
+
+upsDiagBatteryTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsDiagBatteryEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for diagnostics of individual batteries. The number of
+ entries is contained in the upsDiagBattTableSize OID."
+ ::= { upsDiagnosticBatteries 2 }
+
+upsDiagBatteryEntry OBJECT-TYPE
+ SYNTAX UpsDiagBatteryEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The diagnostics of a battery."
+ INDEX { upsDiagBatteryIndex}
+ ::= { upsDiagBatteryTable 1 }
+
+UpsDiagBatteryEntry ::=
+ SEQUENCE {
+ upsDiagBatteryFrameIndex INTEGER,
+ upsDiagBatteryIndex INTEGER,
+ upsDiagBatteryStatus INTEGER,
+ upsDiagBatterySerialNumber DisplayString,
+ upsDiagBatteryFirmwareRev DisplayString,
+ upsDiagBatteryManufactureDate DisplayString,
+ upsDiagBatteryType DisplayString,
+ upsDiagBatteryFramePresent INTEGER,
+ upsDiagBatteryFrameTemperature INTEGER
+ }
+
+upsDiagBatteryFrameIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the battery frame entry.
+ Frame 0 indicates the Main frame. Extended Run (XR) frames
+ start from index 1."
+ ::= { upsDiagBatteryEntry 1 }
+
+upsDiagBatteryIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the battery entry."
+ ::= { upsDiagBatteryEntry 2 }
+
+upsDiagBatteryStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ notInstalled (2),
+ ok (3),
+ failed (4),
+ highTemperature (5),
+ replaceImmediately (6),
+ lowCapacity (7)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the battery.
+ unknown(1) indicates the device status is unknown.
+ notInstalled(2) indicates the device is not installed.
+ ok(3) indicates the battery status is OK.
+ failed(4) indicates the battery status is failed.
+ highTemperature(5) indicates the battery has a high temperature condition.
+ replaceImmediately(6) indicates the battery must be replaced immediately.
+ lowCapacity(7) indicates the battery has a low capacity."
+ ::= { upsDiagBatteryEntry 3 }
+
+upsDiagBatterySerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The serial number of the battery."
+ ::= { upsDiagBatteryEntry 4 }
+
+upsDiagBatteryFirmwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The firmware revision of the battery."
+ ::= { upsDiagBatteryEntry 5 }
+
+upsDiagBatteryManufactureDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The manufacture date of the battery."
+ ::= { upsDiagBatteryEntry 6 }
+
+upsDiagBatteryType OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery type or rating for the battery."
+ ::= { upsDiagBatteryEntry 7 }
+
+
+ upsDiagBatteryFramePresent OBJECT-TYPE
+ SYNTAX INTEGER {
+ notPresent(0),
+ present(1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery frame/cabinet status.
+ 0 indicates frame/cabinet is not present.
+ 1 indicates frame/cabinet is present."
+ ::= { upsDiagBatteryEntry 8 }
+
+ upsDiagBatteryFrameTemperature OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery frame/cabinet temperature in tenths of degrees celsius.
+ If the frame/cabinet is not present, this variable is set to (-1)."
+ ::= { upsDiagBatteryEntry 9 }
+
+upsDiagBatteryFrameTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum number of battery frames supported by the UPS."
+ ::= { upsDiagnosticBatteries 3 }
+
+upsDiagBatteryFrameTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsDiagBatteryFrameEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for diagnostics of individual battery frame. The number of
+ entries is contained in the upsDiagBatteryFrameTableSize OID."
+ ::= { upsDiagnosticBatteries 4 }
+
+upsDiagBatteryFrameEntry OBJECT-TYPE
+ SYNTAX UpsDiagBatteryFrameEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The diagnostics of a battery frame."
+ INDEX { upsDiagBatteryFrameTableIndex}
+ ::= { upsDiagBatteryFrameTable 1 }
+
+UpsDiagBatteryFrameEntry ::=
+ SEQUENCE {
+ upsDiagBatteryFrameTableIndex INTEGER,
+ upsDiagBatteryModuleStatusPerFrame DisplayString,
+ upsDiagBatteryPositiveVoltage INTEGER,
+ upsDiagBatteryNegativeVoltage INTEGER,
+ upsDiagBatteryTemperature INTEGER
+
+ }
+
+upsDiagBatteryFrameTableIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the battery frame entry."
+ ::= { upsDiagBatteryFrameEntry 1 }
+
+upsDiagBatteryModuleStatusPerFrame OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An ASCII string containing the 64 flags representing
+ the status of battery modules. 1 indicates battery module installed,
+ 0 indicates battery module not installed.
+
+ The flags are numbered from 1 to 64, and read from left
+ to right. The flags are defined as follows:
+
+ Flag 1: Battery Module Level 1 A
+ Flag 2: Battery Module Level 1 B
+ Flag 3: Battery Module Level 1 C
+ Flag 4: Battery Module Level 1 D
+ Flag 5: Battery Module Level 1 E
+ Flag 6: Battery Module Level 1 F
+
+ Flag 7: Battery Module Level 2 A
+ Flag 8: Battery Module Level 2 B
+ Flag 9: Battery Module Level 2 C
+ Flag 10: Battery Module Level 2 D
+ Flag 11: Battery Module Level 2 E
+ Flag 12: Battery Module Level 2 F
+
+ Flag 13: Battery Module Level 3 A
+ Flag 14: Battery Module Level 3 B
+ Flag 15: Battery Module Level 3 C
+ Flag 16: Battery Module Level 3 D
+ Flag 17: Battery Module Level 3 E
+ Flag 18: Battery Module Level 3 F
+
+ Flag 19: Battery Module Level 4 A
+ Flag 20: Battery Module Level 4 B
+ Flag 21: Battery Module Level 4 C
+ Flag 22: Battery Module Level 4 D
+ Flag 23: Battery Module Level 4 E
+ Flag 24: Battery Module Level 4 F
+
+ Flag 25: Battery Module Level 7 A
+ Flag 26: Battery Module Level 7 B
+ Flag 27: Battery Module Level 7 C
+ Flag 28: Battery Module Level 7 D
+ Flag 29: Battery Module Level 7 E
+ Flag 30: Battery Module Level 7 F
+
+ Flag 31: Battery Module Level 8 A
+ Flag 32: Battery Module Level 8 B
+ Flag 33: Battery Module Level 8 C
+ Flag 34: Battery Module Level 8 D
+ Flag 35: Battery Module Level 8 E
+ Flag 36: Battery Module Level 8 F
+
+ Flag 37: Battery Module Level 9 A
+ Flag 38: Battery Module Level 9 B
+ Flag 39: Battery Module Level 9 C
+ Flag 40: Battery Module Level 9 D
+ Flag 41: Battery Module Level 9 E
+ Flag 42: Battery Module Level 9 F
+
+ Flag 43: Battery Module Level 10 A
+ Flag 44: Battery Module Level 10 B
+ Flag 45: Battery Module Level 10 C
+ Flag 46: Battery Module Level 10 D
+ Flag 47: Battery Module Level 10 E
+ Flag 48: Battery Module Level 10 F
+
+ Flag 49: <Not Used>
+ Flag 50: <Not Used>
+ Flag 51: <Not Used>
+ Flag 52: <Not Used>
+ Flag 53: <Not Used>
+ Flag 54: <Not Used>
+
+ Flag 55: <Not Used>
+ Flag 56: <Not Used>
+ Flag 57: <Not Used>
+ Flag 58: <Not Used>
+ Flag 59: <Not Used>
+ Flag 60: <Not Used>
+
+ Flag 61: <Not Used>
+ Flag 62: <Not Used>
+ Flag 63: <Not Used>
+ Flag 64: <Not Used>"
+ ::= { upsDiagBatteryFrameEntry 2 }
+
+upsDiagBatteryPositiveVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery positive voltage, in Volts."
+ ::= { upsDiagBatteryFrameEntry 3 }
+
+upsDiagBatteryNegativeVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery negative voltage, in Volts."
+ ::= { upsDiagBatteryFrameEntry 4 }
+
+upsDiagBatteryTemperature OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The battery frame/cabinet temperature in tenths of degrees celsius.
+ If the frame/cabinet is not present, this variable is set to (-1)."
+ ::= { upsDiagBatteryFrameEntry 5 }
+
+
+-- the upsDiagnosticSubsystem group
+
+upsDiagSubSysFrameTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of frames attached to the UPS including the Main frame."
+ ::= { upsDiagnosticSubsystem 1 }
+
+upsDiagSubSysFrameTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsDiagSubSysFrameEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for diagnostics of individual XR Frames."
+ ::= { upsDiagnosticSubsystem 2 }
+
+upsDiagSubSysFrameEntry OBJECT-TYPE
+ SYNTAX UpsDiagSubSysFrameEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The diagnostics of an XR Frame."
+ INDEX { upsDiagSubSysFrameIndex}
+ ::= { upsDiagSubSysFrameTable 1 }
+
+UpsDiagSubSysFrameEntry ::=
+ SEQUENCE {
+ upsDiagSubSysFrameIndex INTEGER,
+ upsDiagSubSysFrameType INTEGER,
+ upsDiagSubSysFrameFirmwareRev DisplayString,
+ upsDiagSubSysFrameHardwareRev DisplayString,
+ upsDiagSubSysFrameSerialNum DisplayString,
+ upsDiagSubSysFrameManufactureDate DisplayString
+ }
+
+upsDiagSubSysFrameIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The frame index entry."
+ ::= { upsDiagSubSysFrameEntry 1 }
+
+upsDiagSubSysFrameType OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ notInstalled (2),
+ frameTypeMain (3),
+ frameTypeXR (4),
+ frameTypeLXR (5)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The type of Frame.
+ unknown(1) indicates the device status is unknown.
+ notInstalled(2) indicates the device is not installed.
+ frameTypeMain(3) indicates the frame type is the Main Frame.
+ frameTypeXR(4) indicates the frame type is an XR Frame.
+ frameTypeLXR(5) indicates the frame type is an LXR Frame."
+ ::= { upsDiagSubSysFrameEntry 2 }
+
+upsDiagSubSysFrameFirmwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The firmware revision of the frame."
+ ::= { upsDiagSubSysFrameEntry 3 }
+
+upsDiagSubSysFrameHardwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The hardware revision of the frame."
+ ::= { upsDiagSubSysFrameEntry 4 }
+
+upsDiagSubSysFrameSerialNum OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The serial number of the frame."
+ ::= { upsDiagSubSysFrameEntry 5 }
+
+upsDiagSubSysFrameManufactureDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The manufacture date of the frame."
+ ::= { upsDiagSubSysFrameEntry 6 }
+
+upsDiagSubSysIntBypSwitchTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of Internal Bypass switches attached to the UPS."
+ ::= { upsDiagnosticSubsystem 3 }
+
+upsDiagSubSysIntBypSwitchTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsDiagSubSysIntBypSwitchEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for diagnostics of the Internal Bypass Switch."
+ ::= { upsDiagnosticSubsystem 4 }
+
+upsDiagSubSysIntBypSwitchEntry OBJECT-TYPE
+ SYNTAX UpsDiagSubSysIntBypSwitchEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The diagnostics of the Internal Bypass Switch."
+ INDEX { upsDiagSubSysIntBypSwitchIndex}
+ ::= { upsDiagSubSysIntBypSwitchTable 1 }
+
+UpsDiagSubSysIntBypSwitchEntry ::=
+ SEQUENCE {
+ upsDiagSubSysIntBypSwitchFrameIndex INTEGER,
+ upsDiagSubSysIntBypSwitchIndex INTEGER,
+ upsDiagSubSysIntBypSwitchStatus INTEGER,
+ upsDiagSubSysIntBypSwitchFirmwareRev DisplayString,
+ upsDiagSubSysIntBypSwitchHardwareRev DisplayString,
+ upsDiagSubSysIntBypSwitchSerialNum DisplayString,
+ upsDiagSubSysIntBypSwitchManufactureDate DisplayString,
+ upsDiagSubSysIntBypSwitchModelNum DisplayString
+ }
+
+upsDiagSubSysIntBypSwitchFrameIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The frame index entry."
+ ::= { upsDiagSubSysIntBypSwitchEntry 1 }
+
+upsDiagSubSysIntBypSwitchIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Internal Bypass Switch index entry."
+ ::= { upsDiagSubSysIntBypSwitchEntry 2 }
+
+upsDiagSubSysIntBypSwitchStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ notInstalled (2),
+ offOk (3),
+ onOk (4),
+ offFail (5),
+ onFail (6),
+ lostComm (7)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Internal Bypass Switch status.
+ unknown(1) indicates the device status is unknown.
+ notInstalled(2) indicates the device is not installed.
+ offOk(3) indicates the device status is off and OK.
+ onOk(4) indicates the device status is on and OK.
+ offFail(5) indicates the device status is off and failed.
+ onFail(6) indicates the device status is on and failed.
+ lostComm(7) indicates the device has lost communication."
+ ::= { upsDiagSubSysIntBypSwitchEntry 3 }
+
+upsDiagSubSysIntBypSwitchFirmwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The firmware revision of the Internal Bypass Switch."
+ ::= { upsDiagSubSysIntBypSwitchEntry 4 }
+
+upsDiagSubSysIntBypSwitchHardwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The hardware revision of the Internal Bypass Switch."
+ ::= { upsDiagSubSysIntBypSwitchEntry 5 }
+
+upsDiagSubSysIntBypSwitchSerialNum OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The serial number of the Internal Bypass Switch."
+ ::= { upsDiagSubSysIntBypSwitchEntry 6 }
+
+upsDiagSubSysIntBypSwitchManufactureDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The manufacture date of the Internal Bypass Switch."
+ ::= { upsDiagSubSysIntBypSwitchEntry 7 }
+
+ upsDiagSubSysIntBypSwitchModelNum OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The model number of the Internal Bypass Switch."
+ ::= { upsDiagSubSysIntBypSwitchEntry 8 }
+
+upsDiagSubSysBattMonitorTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of Battery Monitor Boards attached to the UPS."
+ ::= { upsDiagnosticSubsystem 5 }
+
+upsDiagSubSysBattMonitorTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsDiagSubSysBattMonitorEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for diagnostics of the Battery Monitor Board."
+ ::= { upsDiagnosticSubsystem 6 }
+
+upsDiagSubSysBattMonitorEntry OBJECT-TYPE
+ SYNTAX UpsDiagSubSysBattMonitorEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The diagnostics of the Battery Monitor Board."
+ INDEX { upsDiagSubSysBattMonitorIndex}
+ ::= { upsDiagSubSysBattMonitorTable 1 }
+
+UpsDiagSubSysBattMonitorEntry ::=
+ SEQUENCE {
+ upsDiagSubSysBattMonitorFrameIndex INTEGER,
+ upsDiagSubSysBattMonitorIndex INTEGER,
+ upsDiagSubSysBattMonitorStatus INTEGER,
+ upsDiagSubSysBattMonitorFirmwareRev DisplayString,
+ upsDiagSubSysBattMonitorHardwareRev DisplayString,
+ upsDiagSubSysBattMonitorSerialNum DisplayString,
+ upsDiagSubSysBattMonitorManufactureDate DisplayString
+ }
+
+upsDiagSubSysBattMonitorFrameIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The frame index entry."
+ ::= { upsDiagSubSysBattMonitorEntry 1 }
+
+upsDiagSubSysBattMonitorIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of the Battery Monitor Board."
+ ::= { upsDiagSubSysBattMonitorEntry 2 }
+
+upsDiagSubSysBattMonitorStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ notInstalled (2),
+ offOk (3),
+ onOk (4),
+ offFail (5),
+ onFail (6),
+ lostComm (7)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the Battery Monitor Board.
+ unknown(1) indicates the device status is unknown.
+ notInstalled(2) indicates the device is not installed.
+ offOk(3) indicates the device status is off and OK.
+ onOk(4) indicates the device status is on and OK.
+ offFail(5) indicates the device status is off and failed.
+ onFail(6) indicates the device status is on and failed.
+ lostComm(7) indicates the device has lost communication."
+ ::= { upsDiagSubSysBattMonitorEntry 3 }
+
+upsDiagSubSysBattMonitorFirmwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The firmware revision of the Battery Monitor Board."
+ ::= { upsDiagSubSysBattMonitorEntry 4 }
+
+upsDiagSubSysBattMonitorHardwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The hardware revision of the Battery Monitor Board."
+ ::= { upsDiagSubSysBattMonitorEntry 5 }
+
+upsDiagSubSysBattMonitorSerialNum OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The serial number of the Battery Monitor Board."
+ ::= { upsDiagSubSysBattMonitorEntry 6 }
+
+upsDiagSubSysBattMonitorManufactureDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The date of the manufacture for the Battery Monitor Board."
+ ::= { upsDiagSubSysBattMonitorEntry 7 }
+
+upsDiagSubSysExternalSwitchGearTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of External Switch Gears attached to the UPS."
+ ::= { upsDiagnosticSubsystem 7 }
+
+upsDiagSubSysExternalSwitchGearTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsDiagSubSysExternalSwitchGearEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for diagnostics of the individual External Switch Gear."
+ ::= { upsDiagnosticSubsystem 8 }
+
+upsDiagSubSysExternalSwitchGearEntry OBJECT-TYPE
+ SYNTAX UpsDiagSubSysExternalSwitchGearEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The diagnostics of an individual External Switch Gear."
+ INDEX { upsDiagSubSysExternalSwitchGearIndex}
+ ::= { upsDiagSubSysExternalSwitchGearTable 1 }
+
+UpsDiagSubSysExternalSwitchGearEntry ::=
+ SEQUENCE {
+ upsDiagSubSysExternalSwitchGearFrameIndex INTEGER,
+ upsDiagSubSysExternalSwitchGearIndex INTEGER,
+ upsDiagSubSysExternalSwitchGearStatus INTEGER,
+ upsDiagSubSysExternalSwitchGearFirmwareRev DisplayString,
+ upsDiagSubSysExternalSwitchGearHardwareRev DisplayString,
+ upsDiagSubSysExternalSwitchGearSerialNum DisplayString,
+ upsDiagSubSysExternalSwitchGearManufactureDate DisplayString,
+ upsDiagSubSysExternalSwitchGearTemperature INTEGER
+
+ }
+
+upsDiagSubSysExternalSwitchGearFrameIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The frame index entry."
+ ::= { upsDiagSubSysExternalSwitchGearEntry 1 }
+
+upsDiagSubSysExternalSwitchGearIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of the External Switch Gear."
+ ::= { upsDiagSubSysExternalSwitchGearEntry 2 }
+
+upsDiagSubSysExternalSwitchGearStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ notInstalled (2),
+ offOk (3),
+ onOk (4),
+ offFail (5),
+ onFail (6),
+ lostComm (7)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the External Switch Gear.
+ unknown(1) indicates the device status is unknown.
+ notInstalled(2) indicates the device is not installed.
+ offOk(3) indicates the device status is off and OK.
+ onOk(4) indicates the device status is on and OK.
+ offFail(5) indicates the device status is off and failed.
+ onFail(6) indicates the device status is on and failed.
+ lostComm(7) indicates the device has lost communication."
+ ::= { upsDiagSubSysExternalSwitchGearEntry 3 }
+
+upsDiagSubSysExternalSwitchGearFirmwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The firmware revision of the External Switch Gear monitor card."
+ ::= { upsDiagSubSysExternalSwitchGearEntry 4 }
+
+upsDiagSubSysExternalSwitchGearHardwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The hardware revision of the External Switch Gear monitor card."
+ ::= { upsDiagSubSysExternalSwitchGearEntry 5 }
+
+upsDiagSubSysExternalSwitchGearSerialNum OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The serial number of the External Switch Gear monitor card."
+ ::= { upsDiagSubSysExternalSwitchGearEntry 6 }
+
+upsDiagSubSysExternalSwitchGearManufactureDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The date of the manufacture for the External Switch Gear monitor card."
+ ::= { upsDiagSubSysExternalSwitchGearEntry 7 }
+
+ upsDiagSubSysExternalSwitchGearTemperature OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+
+ "The temperature of the air around the External Switch
+ Gear monitor card in tenths of degrees Celsius."
+ ::= { upsDiagSubSysExternalSwitchGearEntry 8 }
+
+upsDiagSubSysDisplayInterfaceCardTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of Display Interface Cards attached to the UPS."
+ ::= { upsDiagnosticSubsystem 9 }
+
+upsDiagSubSysDisplayInterfaceCardTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsDiagSubSysDisplayInterfaceCardEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for diagnostics of individual Display Interface Cards."
+ ::= { upsDiagnosticSubsystem 10 }
+
+upsDiagSubSysDisplayInterfaceCardEntry OBJECT-TYPE
+ SYNTAX UpsDiagSubSysDisplayInterfaceCardEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The diagnostics of a Display Interface Card."
+ INDEX { upsDiagSubSysDisplayInterfaceCardIndex}
+ ::= { upsDiagSubSysDisplayInterfaceCardTable 1 }
+
+UpsDiagSubSysDisplayInterfaceCardEntry ::=
+ SEQUENCE {
+ upsDiagSubSysDisplayInterfaceCardFrameIndex INTEGER,
+ upsDiagSubSysDisplayInterfaceCardIndex INTEGER,
+ upsDiagSubSysDisplayInterfaceCardStatus INTEGER
+ }
+
+upsDiagSubSysDisplayInterfaceCardFrameIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The frame index entry."
+ ::= { upsDiagSubSysDisplayInterfaceCardEntry 1 }
+
+upsDiagSubSysDisplayInterfaceCardIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of the Display Interface Card."
+ ::= { upsDiagSubSysDisplayInterfaceCardEntry 2 }
+
+upsDiagSubSysDisplayInterfaceCardStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ notInstalled (2),
+ offOk (3),
+ onOk (4),
+ offFail (5),
+ onFail (6),
+ lostComm (7)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the Display Interface Card.
+ unknown(1) indicates the device status is unknown.
+ notInstalled(2) indicates the device is not installed.
+ offOk(3) indicates the device status is off and OK.
+ onOk(4) indicates the device status is on and OK.
+ offFail(5) indicates the device status is off and failed.
+ onFail(6) indicates the device status is on and failed.
+ lostComm(7) indicates the device has lost communication."
+ ::= { upsDiagSubSysDisplayInterfaceCardEntry 3 }
+
+upsDiagSubSysDCCircuitBreakerTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of DC Circuit Breakers attached to the UPS."
+ ::= { upsDiagnosticSubsystem 11 }
+
+upsDiagSubSysDCCircuitBreakerTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsDiagSubSysDCCircuitBreakerEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for diagnostics of individual DC Circuit Breakers."
+ ::= { upsDiagnosticSubsystem 12 }
+
+upsDiagSubSysDCCircuitBreakerEntry OBJECT-TYPE
+ SYNTAX UpsDiagSubSysDCCircuitBreakerEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The diagnostics of a DC Circuit Breaker."
+ INDEX { upsDiagSubSysDCCircuitBreakerIndex}
+ ::= { upsDiagSubSysDCCircuitBreakerTable 1 }
+
+UpsDiagSubSysDCCircuitBreakerEntry ::=
+ SEQUENCE {
+ upsDiagSubSysDCCircuitBreakerFrameIndex INTEGER,
+ upsDiagSubSysDCCircuitBreakerIndex INTEGER,
+ upsDiagSubSysDCCircuitBreakerStatus INTEGER
+ }
+
+upsDiagSubSysDCCircuitBreakerFrameIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The frame index entry."
+ ::= { upsDiagSubSysDCCircuitBreakerEntry 1 }
+
+upsDiagSubSysDCCircuitBreakerIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of the DC Circuit Breaker."
+ ::= { upsDiagSubSysDCCircuitBreakerEntry 2 }
+
+upsDiagSubSysDCCircuitBreakerStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ notInstalled (2),
+ opened (3),
+ closed (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the DC Circuit Breaker.
+ unknown(1) indicates the circuit breaker status is unknown.
+ notInstalled(2) indicates the circuit breaker is not installed.
+ opened(3) indicates the circuit breaker is opened.
+ closed(4) indicates the circuit breaker is closed."
+ ::= { upsDiagSubSysDCCircuitBreakerEntry 3 }
+
+upsDiagSubSysSystemPowerSupplyTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of System Power Supplies attached to the UPS."
+ ::= { upsDiagnosticSubsystem 13 }
+
+upsDiagSubSysSystemPowerSupplyTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsDiagSubSysSystemPowerSupplyEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for diagnostics of individual System Power Supplies."
+ ::= { upsDiagnosticSubsystem 14 }
+
+upsDiagSubSysSystemPowerSupplyEntry OBJECT-TYPE
+ SYNTAX UpsDiagSubSysSystemPowerSupplyEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The diagnostics of a System Power Supply."
+ INDEX { upsDiagSubSysSystemPowerSupplyIndex}
+ ::= { upsDiagSubSysSystemPowerSupplyTable 1 }
+
+UpsDiagSubSysSystemPowerSupplyEntry ::=
+ SEQUENCE {
+ upsDiagSubSysSystemPowerSupplyFrameIndex INTEGER,
+ upsDiagSubSysSystemPowerSupplyIndex INTEGER,
+ upsDiagSubSysSystemPowerSupplyStatus INTEGER,
+ upsDiagSubSysSystemPowerSupplyFirmwareRev DisplayString,
+ upsDiagSubSysSystemPowerSupplyHardwareRev DisplayString,
+ upsDiagSubSysSystemPowerSupplySerialNum DisplayString,
+ upsDiagSubSysSystemPowerSupplyManufactureDate DisplayString
+ }
+
+upsDiagSubSysSystemPowerSupplyFrameIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The frame index entry."
+ ::= { upsDiagSubSysSystemPowerSupplyEntry 1 }
+
+upsDiagSubSysSystemPowerSupplyIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of a System Power Supply."
+ ::= { upsDiagSubSysSystemPowerSupplyEntry 2 }
+
+upsDiagSubSysSystemPowerSupplyStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ notInstalled (2),
+ offOk (3),
+ onOk (4),
+ offFail (5),
+ onFail (6),
+ lostComm (7)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the System Power Supply.
+ unknown(1) indicates the device status is unknown.
+ notInstalled(2) indicates the device is not installed.
+ offOk(3) indicates the device status is off and OK.
+ onOk(4) indicates the device status is on and OK.
+ offFail(5) indicates the device status is off and failed.
+ onFail(6) indicates the device status is on and failed.
+ lostComm(7) indicates the device has lost communication."
+ ::= { upsDiagSubSysSystemPowerSupplyEntry 3 }
+
+upsDiagSubSysSystemPowerSupplyFirmwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The firmware revision of the System Power Supply monitor card."
+ ::= { upsDiagSubSysSystemPowerSupplyEntry 4 }
+
+upsDiagSubSysSystemPowerSupplyHardwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The hardware revision of the System Power Supply monitor card."
+ ::= { upsDiagSubSysSystemPowerSupplyEntry 5 }
+
+upsDiagSubSysSystemPowerSupplySerialNum OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The serial number of the System Power Supply monitor card."
+ ::= { upsDiagSubSysSystemPowerSupplyEntry 6 }
+
+upsDiagSubSysSystemPowerSupplyManufactureDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The date of the manufacture for the System Power Supply monitor card."
+ ::= { upsDiagSubSysSystemPowerSupplyEntry 7 }
+
+upsDiagSubSysXRCommunicationCardTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of XR Communication Cards attached to the UPS."
+ ::= { upsDiagnosticSubsystem 15 }
+
+upsDiagSubSysXRCommunicationCardTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsDiagSubSysXRCommunicationCardEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for diagnostics of individual XR Communication Cards."
+ ::= { upsDiagnosticSubsystem 16 }
+
+upsDiagSubSysXRCommunicationCardEntry OBJECT-TYPE
+ SYNTAX UpsDiagSubSysXRCommunicationCardEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The diagnostics of an XR Communication Card."
+ INDEX { upsDiagSubSysXRCommunicationCardIndex}
+ ::= { upsDiagSubSysXRCommunicationCardTable 1 }
+
+UpsDiagSubSysXRCommunicationCardEntry ::=
+ SEQUENCE {
+ upsDiagSubSysXRCommunicationCardFrameIndex INTEGER,
+ upsDiagSubSysXRCommunicationCardIndex INTEGER,
+ upsDiagSubSysXRCommunicationCardStatus INTEGER,
+ upsDiagSubSysXRCommunicationCardFirmwareRev DisplayString,
+ upsDiagSubSysXRCommunicationCardSerialNum DisplayString
+
+ }
+
+upsDiagSubSysXRCommunicationCardFrameIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The frame index entry."
+ ::= { upsDiagSubSysXRCommunicationCardEntry 1 }
+
+upsDiagSubSysXRCommunicationCardIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of an XR Communication Card."
+ ::= { upsDiagSubSysXRCommunicationCardEntry 2 }
+
+upsDiagSubSysXRCommunicationCardStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ notInstalled (2),
+ offOk (3),
+ onOk (4),
+ offFail (5),
+ onFail (6),
+ lostComm (7)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the XR Communication Card.
+ unknown(1) indicates the device status is unknown.
+ notInstalled(2) indicates the device is not installed.
+ offOk(3) indicates the device status is off and OK.
+ onOk(4) indicates the device status is on and OK.
+ offFail(5) indicates the device status is off and failed.
+ onFail(6) indicates the device status is on and failed.
+ lostComm(7) indicates the device has lost communication."
+ ::= { upsDiagSubSysXRCommunicationCardEntry 3 }
+
+upsDiagSubSysXRCommunicationCardFirmwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The firmware revision of the XR Communication card."
+ ::= { upsDiagSubSysXRCommunicationCardEntry 4 }
+
+upsDiagSubSysXRCommunicationCardSerialNum OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The serial number of the XR Communication card."
+ ::= { upsDiagSubSysXRCommunicationCardEntry 5 }
+
+upsDiagSubSysExternalPowerFrameBoardTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of External Power Frame Boards attached to the UPS."
+ ::= { upsDiagnosticSubsystem 17 }
+
+upsDiagSubSysExternalPowerFrameBoardTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsDiagSubSysExternalPowerFrameBoardEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for diagnostics of individual External Power Frame Boards."
+ ::= { upsDiagnosticSubsystem 18 }
+
+upsDiagSubSysExternalPowerFrameBoardEntry OBJECT-TYPE
+ SYNTAX UpsDiagSubSysExternalPowerFrameBoardEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The diagnostics of an External Power Frame Board."
+ INDEX { upsDiagSubSysExternalPowerFrameBoardIndex}
+ ::= { upsDiagSubSysExternalPowerFrameBoardTable 1 }
+
+UpsDiagSubSysExternalPowerFrameBoardEntry ::=
+ SEQUENCE {
+ upsDiagSubSysExternalPowerFrameBoardFrameIndex INTEGER,
+ upsDiagSubSysExternalPowerFrameBoardIndex INTEGER,
+ upsDiagSubSysExternalPowerFrameBoardStatus INTEGER
+ }
+
+upsDiagSubSysExternalPowerFrameBoardFrameIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The frame index entry."
+ ::= { upsDiagSubSysExternalPowerFrameBoardEntry 1 }
+
+upsDiagSubSysExternalPowerFrameBoardIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of an External Power Frame Board."
+ ::= { upsDiagSubSysExternalPowerFrameBoardEntry 2 }
+
+upsDiagSubSysExternalPowerFrameBoardStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ notInstalled (2),
+ offOk (3),
+ onOk (4),
+ offFail (5),
+ onFail (6),
+ lostComm (7)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the External Power Frame Board.
+ unknown(1) indicates the device status is unknown.
+ notInstalled(2) indicates the device is not installed.
+ offOk(3) indicates the device status is off and OK.
+ onOk(4) indicates the device status is on and OK.
+ offFail(5) indicates the device status is off and failed.
+ onFail(6) indicates the device status is on and failed.
+ lostComm(7) indicates the device has lost communication."
+ ::= { upsDiagSubSysExternalPowerFrameBoardEntry 3 }
+
+upsDiagSubSysChargerTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of Chargers attached to the UPS."
+ ::= { upsDiagnosticSubsystem 19 }
+
+ upsDiagSubSysChargerTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsDiagSubSysChargerEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for diagnostics of individual chargers."
+ ::= { upsDiagnosticSubsystem 20 }
+
+upsDiagSubSysChargerEntry OBJECT-TYPE
+ SYNTAX UpsDiagSubSysChargerEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The diagnostics of a charger."
+ INDEX { upsDiagSubSysChargerIndex}
+ ::= { upsDiagSubSysChargerTable 1 }
+
+UpsDiagSubSysChargerEntry ::=
+ SEQUENCE {
+ upsDiagSubSysChargerFrameIndex INTEGER,
+ upsDiagSubSysChargerIndex INTEGER,
+ upsDiagSubSysChargerStatus INTEGER
+ }
+
+upsDiagSubSysChargerFrameIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The frame index entry."
+ ::= { upsDiagSubSysChargerEntry 1 }
+
+upsDiagSubSysChargerIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of a charger."
+ ::= { upsDiagSubSysChargerEntry 2 }
+
+upsDiagSubSysChargerStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ notInstalled (2),
+ offOk (3),
+ onOk (4),
+ offFail (5),
+ onFail (6),
+ lostComm (7)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the Charger.
+ unknown(1) indicates the device status is unknown.
+ notInstalled(2) indicates the device is not installed.
+ offOk(3) indicates the device status is off and OK.
+ onOk(4) indicates the device status is on and OK.
+ offFail(5) indicates the device status is off and failed.
+ onFail(6) indicates the device status is on and failed.
+ lostComm(7) indicates the device has lost communication."
+ ::= { upsDiagSubSysChargerEntry 3 }
+
+upsDiagSubSysInverterTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of Inverters attached to the UPS."
+ ::= { upsDiagnosticSubsystem 21 }
+
+upsDiagSubSysInverterTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsDiagSubSysInverterEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for diagnostics of individual Inverters."
+ ::= { upsDiagnosticSubsystem 22 }
+
+upsDiagSubSysInverterEntry OBJECT-TYPE
+ SYNTAX UpsDiagSubSysInverterEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The diagnostics of an Inverter."
+ INDEX { upsDiagSubSysInverterIndex}
+ ::= { upsDiagSubSysInverterTable 1 }
+
+UpsDiagSubSysInverterEntry ::=
+ SEQUENCE {
+ upsDiagSubSysInverterFrameIndex INTEGER,
+ upsDiagSubSysInverterIndex INTEGER,
+ upsDiagSubSysInverterStatus INTEGER,
+ upsDiagSubSysInverterFirmwareRev DisplayString,
+ upsDiagSubSysInverterHardwareRev DisplayString,
+ upsDiagSubSysInverterSerialNum DisplayString,
+ upsDiagSubSysInverterManufactureDate DisplayString
+ }
+
+upsDiagSubSysInverterFrameIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The frame index entry."
+ ::= { upsDiagSubSysInverterEntry 1 }
+
+upsDiagSubSysInverterIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of an Inverter."
+ ::= { upsDiagSubSysInverterEntry 2 }
+
+upsDiagSubSysInverterStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ notInstalled (2),
+ offOk (3),
+ onOk (4),
+ offFail (5),
+ onFail (6),
+ lostComm (7)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the Inverter.
+ unknown(1) indicates the device status is unknown.
+ notInstalled(2) indicates the device is not installed.
+ offOk(3) indicates the device status is off and OK.
+ onOk(4) indicates the device status is on and OK.
+ offFail(5) indicates the device status is off and failed.
+ onFail(6) indicates the device status is on and failed.
+ lostComm(7) indicates the device has lost communication."
+ ::= { upsDiagSubSysInverterEntry 3 }
+
+upsDiagSubSysInverterFirmwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The firmware revision of the Inverter monitor."
+ ::= { upsDiagSubSysInverterEntry 4 }
+
+upsDiagSubSysInverterHardwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The hardware revision of the Inverter monitor."
+ ::= { upsDiagSubSysInverterEntry 5 }
+
+upsDiagSubSysInverterSerialNum OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The serial number of the Inverter monitor."
+ ::= { upsDiagSubSysInverterEntry 6 }
+
+upsDiagSubSysInverterManufactureDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The date of manufacture for the Inverter monitor."
+ ::= { upsDiagSubSysInverterEntry 7 }
+
+upsDiagSubSysPowerFactorCorrectionTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of Power Factor Correction devices attached to the UPS."
+ ::= { upsDiagnosticSubsystem 23 }
+
+upsDiagSubSysPowerFactorCorrectionTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsDiagSubSysPowerFactorCorrectionEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for diagnostics of individual PowerFactorCorrections."
+ ::= { upsDiagnosticSubsystem 24 }
+
+upsDiagSubSysPowerFactorCorrectionEntry OBJECT-TYPE
+ SYNTAX UpsDiagSubSysPowerFactorCorrectionEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The diagnostics of a Power Factor Correction."
+ INDEX { upsDiagSubSysPowerFactorCorrectionIndex}
+ ::= { upsDiagSubSysPowerFactorCorrectionTable 1 }
+
+UpsDiagSubSysPowerFactorCorrectionEntry ::=
+ SEQUENCE {
+ upsDiagSubSysPowerFactorCorrectionFrameIndex INTEGER,
+ upsDiagSubSysPowerFactorCorrectionIndex INTEGER,
+ upsDiagSubSysPowerFactorCorrectionStatus INTEGER,
+ upsDiagSubSysPowerFactorCorrectionFirmwareRev DisplayString,
+ upsDiagSubSysPowerFactorCorrectionHardwareRev DisplayString,
+ upsDiagSubSysPowerFactorCorrectionSerialNum DisplayString,
+ upsDiagSubSysPowerFactorCorrectionManufactureDate DisplayString
+ }
+
+upsDiagSubSysPowerFactorCorrectionFrameIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The frame index entry."
+ ::= { upsDiagSubSysPowerFactorCorrectionEntry 1 }
+
+upsDiagSubSysPowerFactorCorrectionIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of a Power Factor Correction."
+ ::= { upsDiagSubSysPowerFactorCorrectionEntry 2 }
+
+upsDiagSubSysPowerFactorCorrectionStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ notInstalled (2),
+ offOk (3),
+ onOk (4),
+ offFail (5),
+ onFail (6),
+ lostComm (7)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the Power Factor Correction.
+ unknown(1) indicates the device status is unknown.
+ notInstalled(2) indicates the device is not installed.
+ offOk(3) indicates the device status is off and OK.
+ onOk(4) indicates the device status is on and OK.
+ offFail(5) indicates the device status is off and failed.
+ onFail(6) indicates the device status is on and failed.
+ lostComm(7) indicates the device has lost communication."
+ ::= { upsDiagSubSysPowerFactorCorrectionEntry 3 }
+
+upsDiagSubSysPowerFactorCorrectionFirmwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The firmware revision of the Power Factor Correction monitor."
+ ::= { upsDiagSubSysPowerFactorCorrectionEntry 4 }
+
+upsDiagSubSysPowerFactorCorrectionHardwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The hardware revision of the Power Factor Correction monitor."
+ ::= { upsDiagSubSysPowerFactorCorrectionEntry 5 }
+
+upsDiagSubSysPowerFactorCorrectionSerialNum OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The serial number of the Power Factor Correction monitor."
+ ::= { upsDiagSubSysPowerFactorCorrectionEntry 6 }
+
+upsDiagSubSysPowerFactorCorrectionManufactureDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The date of the manufacture for the Power Factor Correction monitor."
+ ::= { upsDiagSubSysPowerFactorCorrectionEntry 7 }
+
+upsDiagSubSysNetworkComCardTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of Network Communication Cards attached to the UPS."
+ ::= { upsDiagnosticSubsystem 25 }
+
+upsDiagSubSysNetworkComCardTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsDiagSubSysNetworkComCardEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting diagnostics information of an individual Network Communication Card."
+ ::= { upsDiagnosticSubsystem 26 }
+
+upsDiagSubSysNetworkComCardEntry OBJECT-TYPE
+ SYNTAX UpsDiagSubSysNetworkComCardEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The diagnostics of a Network Communication Card."
+ INDEX { upsDiagSubSysNetworkComCardIndex}
+ ::= { upsDiagSubSysNetworkComCardTable 1 }
+
+UpsDiagSubSysNetworkComCardEntry ::=
+ SEQUENCE {
+ upsDiagSubSysNetworkComCardIndex INTEGER,
+ upsDiagSubSysNetworkComCardModelNumber DisplayString,
+ upsDiagSubSysNetworkComCardSerialNumber DisplayString,
+ upsDiagSubSysNetworkComCardDateOfManufacture DisplayString,
+ upsDiagSubSysNetworkComCardHardwareRev DisplayString,
+ upsDiagSubSysNetworkComCardFirmwareAppRev DisplayString,
+ upsDiagSubSysNetworkComCardFirmwareAppOSRev DisplayString
+ }
+
+upsDiagSubSysNetworkComCardIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The UPS network and display interface communication card index entry."
+ ::= { upsDiagSubSysNetworkComCardEntry 1 }
+
+upsDiagSubSysNetworkComCardModelNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the model number of the UPS network and display interface communication card.
+ This value is set at the factory."
+ ::= { upsDiagSubSysNetworkComCardEntry 2 }
+
+upsDiagSubSysNetworkComCardSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the serial number of the UPS network and display interface communication card.
+ This value is set at the factory."
+ ::= { upsDiagSubSysNetworkComCardEntry 3 }
+
+upsDiagSubSysNetworkComCardDateOfManufacture OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The date when the UPS network and display interface communication card was manufactured in mm/dd/yyyy format.
+ This value is set at the factory."
+ ::= { upsDiagSubSysNetworkComCardEntry 4 }
+
+upsDiagSubSysNetworkComCardHardwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The hardware revision of the UPS network and display interface communication card.
+ This value is set at the factory."
+ ::= { upsDiagSubSysNetworkComCardEntry 5 }
+
+upsDiagSubSysNetworkComCardFirmwareAppRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An ID string identifying the application firmware revision of the
+ UPS network and display interface communication card."
+ ::= { upsDiagSubSysNetworkComCardEntry 6 }
+
+upsDiagSubSysNetworkComCardFirmwareAppOSRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An ID string identifying the application operating system firmware revision of the
+ UPS network and display interface communication card."
+ ::= { upsDiagSubSysNetworkComCardEntry 7 }
+
+upsDiagSubSysUsrSuppBattMonitorTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of user supplied Battery Monitor Boards attached to the UPS."
+ ::= { upsDiagnosticSubsystem 27 }
+
+upsDiagSubSysUsrSuppBattMonitorTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsDiagSubSysUsrSuppBattMonitorEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for diagnostics of the user supplied Battery Monitor Board."
+ ::= { upsDiagnosticSubsystem 28 }
+
+upsDiagSubSysUsrSuppBattMonitorEntry OBJECT-TYPE
+ SYNTAX UpsDiagSubSysUsrSuppBattMonitorEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The diagnostics of the user supplied Battery Monitor Board."
+ INDEX { upsDiagSubSysUsrSuppBattMonitorIndex}
+ ::= { upsDiagSubSysUsrSuppBattMonitorTable 1 }
+
+UpsDiagSubSysUsrSuppBattMonitorEntry ::=
+ SEQUENCE {
+ upsDiagSubSysUsrSuppBattMonitorIndex INTEGER,
+ upsDiagSubSysUsrSuppBattMonitorStatus INTEGER,
+ upsDiagSubSysUsrSuppBattMonitorFirmwareRev DisplayString,
+ upsDiagSubSysUsrSuppBattMonitorHardwareRev DisplayString,
+ upsDiagSubSysUsrSuppBattMonitorSerialNum DisplayString,
+ upsDiagSubSysUsrSuppBattMonitorTemperature INTEGER
+ }
+
+upsDiagSubSysUsrSuppBattMonitorIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of the user supplied Battery Monitor Board."
+ ::= { upsDiagSubSysUsrSuppBattMonitorEntry 1 }
+
+upsDiagSubSysUsrSuppBattMonitorStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ notInstalled (2),
+ offOk (3),
+ onOk (4),
+ offFail (5),
+ onFail (6),
+ lostComm (7)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the user supplied Battery Monitor Board.
+ unknown(1) indicates the device status is unknown.
+ notInstalled(2) indicates the device is not installed.
+ offOk(3) indicates the device status is off and OK.
+ onOk(4) indicates the device status is on and OK.
+ offFail(5) indicates the device status is off and failed.
+ onFail(6) indicates the device status is on and failed.
+ lostComm(7) indicates the device has lost communication."
+ ::= { upsDiagSubSysUsrSuppBattMonitorEntry 2 }
+
+upsDiagSubSysUsrSuppBattMonitorFirmwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The firmware revision of the user supplied Battery Monitor Board."
+ ::= { upsDiagSubSysUsrSuppBattMonitorEntry 3 }
+
+upsDiagSubSysUsrSuppBattMonitorHardwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The hardware revision of the user supplied
+ Battery Monitor Board."
+ ::= { upsDiagSubSysUsrSuppBattMonitorEntry 4 }
+
+upsDiagSubSysUsrSuppBattMonitorSerialNum OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The serial number of the user supplied
+ Battery Monitor Board."
+ ::= { upsDiagSubSysUsrSuppBattMonitorEntry 5 }
+
+upsDiagSubSysUsrSuppBattMonitorTemperature OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+
+ "The temperature of the air around the user supplied
+ Battery Monitor Board in tenths of degrees Celsius."
+ ::= { upsDiagSubSysUsrSuppBattMonitorEntry 6 }
+
+upsDiagSubSysUsrSuppBattBreakerStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ notInstalled (2),
+ opened (3),
+ closed (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the user supplied Battery Breaker.
+ unknown(1) indicates the circuit breaker status is unknown.
+ notInstalled(2) indicates the circuit breaker is not installed.
+ opened(3) indicates the circuit breaker is opened.
+ closed(4) indicates the circuit breaker is closed."
+ ::= { upsDiagnosticSubsystem 29 }
+
+upsDiagSubSysPSUTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of Power Supply Units in the UPS."
+ ::= { upsDiagnosticSubsystem 30 }
+
+upsDiagSubSysPSUTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsDiagSubSysPSUEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for diagnostics of individual Power Supply Units. The number of
+ entries is contained in the upsDiagSubSysPSUTableSize OID."
+ ::= { upsDiagnosticSubsystem 31 }
+
+upsDiagSubSysPSUEntry OBJECT-TYPE
+ SYNTAX UpsDiagSubSysPSUEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The diagnostics information of a Power Supply Unit."
+ INDEX { upsDiagSubSysPSUIndex}
+ ::= { upsDiagSubSysPSUTable 1 }
+
+UpsDiagSubSysPSUEntry ::=
+ SEQUENCE {
+ upsDiagSubSysPSUIndex INTEGER,
+ upsDiagSubSysPSUStatus INTEGER
+ }
+
+upsDiagSubSysPSUIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the Power Supply Unit entry."
+ ::= { upsDiagSubSysPSUEntry 1 }
+
+upsDiagSubSysPSUStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ notInstalled (2),
+ offOk (3),
+ onOk (4),
+ offFail (5),
+ onFail (6),
+ lostComm (7)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the Power Supply Unit.
+ unknown(1) indicates the device status is unknown.
+ notInstalled(2) indicates the device is not installed.
+ offOk(3) indicates the device status is off and OK.
+ onOk(4) indicates the device status is on and OK.
+ offFail(5) indicates the device status is off and failed.
+ onFail(6) indicates the device status is on and failed.
+ lostComm(7) indicates the device has lost communication."
+ ::= { upsDiagSubSysPSUEntry 2 }
+
+upsDiagSubSysIDRCTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of ID and Relay Controller Cards attached to the UPS."
+ ::= { upsDiagnosticSubsystem 32 }
+
+upsDiagSubSysIDRCTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsDiagSubSysIDRCEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for diagnostics of the ID and Relay Controller Card."
+ ::= { upsDiagnosticSubsystem 33 }
+
+upsDiagSubSysIDRCEntry OBJECT-TYPE
+ SYNTAX UpsDiagSubSysIDRCEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The diagnostics of the ID and Relay Controller Card."
+ INDEX { upsDiagSubSysIDRCIndex}
+ ::= { upsDiagSubSysIDRCTable 1 }
+
+UpsDiagSubSysIDRCEntry ::=
+ SEQUENCE {
+ upsDiagSubSysIDRCIndex INTEGER,
+ upsDiagSubSysIDRCStatus INTEGER,
+ upsDiagSubSysIDRCFirmwareRev DisplayString,
+ upsDiagSubSysIDRCHardwareRev DisplayString,
+ upsDiagSubSysIDRCSerialNum DisplayString
+ }
+
+upsDiagSubSysIDRCIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of the ID and Relay Controller Card."
+ ::= { upsDiagSubSysIDRCEntry 1 }
+
+upsDiagSubSysIDRCStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ notInstalled (2),
+ offOk (3),
+ onOk (4),
+ offFail (5),
+ onFail (6),
+ lostComm (7)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the ID and Relay Controller Card.
+ unknown(1) indicates the device status is unknown.
+ notInstalled(2) indicates the device is not installed.
+ offOk(3) indicates the device status is off and OK.
+ onOk(4) indicates the device status is on and OK.
+ offFail(5) indicates the device status is off and failed.
+ onFail(6) indicates the device status is on and failed.
+ lostComm(7) indicates the device has lost communication."
+ ::= { upsDiagSubSysIDRCEntry 2 }
+
+upsDiagSubSysIDRCFirmwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The firmware revision of the ID and Relay Controller Card."
+ ::= { upsDiagSubSysIDRCEntry 3 }
+
+upsDiagSubSysIDRCHardwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The hardware revision of the ID and Relay Controller Card."
+ ::= { upsDiagSubSysIDRCEntry 4 }
+
+upsDiagSubSysIDRCSerialNum OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The serial number of the ID
+ and Relay Controller Card."
+ ::= { upsDiagSubSysIDRCEntry 5 }
+
+upsDiagSubSysExternalConnectorStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ notInstalled (2),
+ offOk (3),
+ onOk (4),
+ offFail (5),
+ onFail (6),
+ lostComm (7)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the external connector board.
+ unknown(1) indicates the device status is unknown.
+ notInstalled(2) indicates the device is not installed.
+ offOk(3) indicates the device status is off and OK.
+ onOk(4) indicates the device status is on and OK.
+ offFail(5) indicates the device status is off and failed.
+ onFail(6) indicates the device status is on and failed.
+ lostComm(7) indicates the device has lost communication."
+ ::= { upsDiagnosticSubsystem 34 }
+
+
+upsDiagSubSysBackfeedContactorTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of backfeed protection contactor attached to the UPS."
+ ::= { upsDiagnosticSubsystem 35 }
+
+upsDiagSubSysBackfeedContactorTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsDiagSubSysBackfeedContactorEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Backfeed protection contactor table."
+ ::= { upsDiagnosticSubsystem 36 }
+ upsDiagSubSysBackfeedContactorEntry OBJECT-TYPE
+ SYNTAX UpsDiagSubSysBackfeedContactorEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of backfeed protection contactors."
+ INDEX { upsDiagSubSysbackfeedContactorIndex }
+ ::= { upsDiagSubSysBackfeedContactorTable 1 }
+
+ UpsDiagSubSysBackfeedContactorEntry ::=
+ SEQUENCE {
+ upsDiagSubSysbackfeedContactorIndex
+ INTEGER,
+ upsDiagSubSysbackfeedContactorName
+ DisplayString,
+ upsDiagSubSysbackfeedContactorType
+ INTEGER,
+ upsDiagSubSysbackfeedContactorStatus
+ INTEGER
+ }
+
+ upsDiagSubSysbackfeedContactorIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of the backfeed protection contactor."
+ ::= { upsDiagSubSysBackfeedContactorEntry 1 }
+
+ upsDiagSubSysbackfeedContactorName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the backfeed protection contactor."
+ ::= { upsDiagSubSysBackfeedContactorEntry 2 }
+
+ upsDiagSubSysbackfeedContactorType OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(1),
+ normalAC(2),
+ bypassAC(3)
+
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the backfeed protection contactor types available in the UPS system.
+ If the UPS is unable to find any attached contactors, this variable
+ is set to unknown(1)."
+ ::= { upsDiagSubSysBackfeedContactorEntry 3 }
+
+ upsDiagSubSysbackfeedContactorStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(1),
+ opened(2),
+ closed(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of backfeed protection contactor.
+ unknown(1) indicates the contactor status is unknown.
+ opened (2) indicates the contactor is opened.
+ closed (3) indicates the contactor is closed."
+ ::= { upsDiagSubSysBackfeedContactorEntry 4 }
+
+upsDiagSubSysIntBypSwitchFanLifetimeInfoTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of backfeed protection contactor attached to the UPS."
+ ::= { upsDiagnosticSubsystem 37 }
+
+upsDiagSubSysIntBypSwitchFanLifetimeInfoTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsDiagSubSysIntBypSwitchFanLifetimeInfoEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for diagnostics of the Internal Bypass Switch life time infomation."
+ ::= { upsDiagnosticSubsystem 38 }
+
+ upsDiagSubSysIntBypSwitchFanLifetimeInfoEntry OBJECT-TYPE
+ SYNTAX UpsDiagSubSysIntBypSwitchFanLifetimeInfoEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The diagnostics of the Internal Bypass Switch."
+ INDEX { upsDiagSubSysIntBypSwitchFanLifetimeInfoIndex }
+ ::= { upsDiagSubSysIntBypSwitchFanLifetimeInfoTable 1 }
+
+ UpsDiagSubSysIntBypSwitchFanLifetimeInfoEntry ::=
+ SEQUENCE {
+ upsDiagSubSysIntBypSwitchFanLifetimeInfoIndex INTEGER,
+ upsDiagSubSysIntBypSwitchFanLifetimeStatus INTEGER,
+ upsDiagSubSysIntBypSwitchFanEstmtdLifetimeRmng INTEGER,
+ upsDiagSubSysIntBypSwitchFanEstmtdLifetimeRmngPct INTEGER
+ }
+
+ upsDiagSubSysIntBypSwitchFanLifetimeInfoIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the Internal Bypass Switch Fan liftime information entry"
+ ::= { upsDiagSubSysIntBypSwitchFanLifetimeInfoEntry 1 }
+
+ upsDiagSubSysIntBypSwitchFanLifetimeStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ ok (1),
+ nearEnd (2),
+ exceeded (3),
+ unknown (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the Internal Bypass Switch Fan lifetime information.
+ ok(1) indicates the device lifetime status is OK.
+ nearEnd(2) indicates the device lifetime status is near end.
+ exceeded(3) indicates the device lifetime status is exceeded.
+ unknown(4) indicates the device lifetime status is unknown."
+ ::= { upsDiagSubSysIntBypSwitchFanLifetimeInfoEntry 2 }
+
+ upsDiagSubSysIntBypSwitchFanEstmtdLifetimeRmng OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Displays the time remaining for the module before it should be replaced.
+ Measured in months. This value is set when you originally install the module."
+ ::= { upsDiagSubSysIntBypSwitchFanLifetimeInfoEntry 3 }
+
+ upsDiagSubSysIntBypSwitchFanEstmtdLifetimeRmngPct OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Displays the percentage of the total lifetime remaining for the module
+ before it should be replaced."
+ ::= { upsDiagSubSysIntBypSwitchFanLifetimeInfoEntry 4 }
+
+-- the upsDiagnosticExternalDevices group
+
+upsDiagSwitchGearStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ notInstalled (2),
+ ok (3),
+ fail (4),
+ lostComm (5),
+ overtemp (6)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the Switch Gear.
+ unknown(1) indicates the device status is unknown.
+ notInstalled(2) indicates the device is not installed.
+ ok(3) indicates the device status is OK.
+ fail(4) indicates the device status has failed.
+ lostComm(5) indicates the device has lost communication.
+ overtemp(6) indicates the device has an over temperature condition."
+ ::= { upsDiagSwitchGear 1 }
+
+upsDiagSwitchGearInputSwitchStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ notInstalled (2),
+ opened (3),
+ closed (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the Switch Gear Input Switch.
+ unknown(1) indicates the switch status is unknown.
+ notInstalled(2) indicates the switch is not installed.
+ opened(3) indicates the switch is opened.
+ closed(4) indicates the switch is closed."
+ ::= { upsDiagSwitchGear 2 }
+
+upsDiagSwitchGearOutputSwitchStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ notInstalled (2),
+ opened (3),
+ closed (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the Switch Gear Output Switch.
+ unknown(1) indicates the switch status is unknown.
+ notInstalled(2) indicates the switch is not installed.
+ opened(3) indicates the switch is opened.
+ closed(4) indicates the switch is closed."
+ ::= { upsDiagSwitchGear 3 }
+
+upsDiagSwitchGearBypassSwitchStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ notInstalled (2),
+ opened (3),
+ closed (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the Switch Gear Bypass Switch.
+ unknown(1) indicates the switch status is unknown.
+ notInstalled(2) indicates the switch is not installed.
+ opened(3) indicates the switch is opened.
+ closed(4) indicates the switch is closed."
+ ::= { upsDiagSwitchGear 4 }
+
+upsDiagSwitchGearBypassInputSwitchStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ notInstalled (2),
+ opened (3),
+ closed (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the Switch Gear Bypass Input Switch.
+ unknown(1) indicates the switch status is unknown.
+ notInstalled(2) indicates the switch is not installed.
+ opened(3) indicates the switch is opened.
+ closed(4) indicates the switch is closed."
+ ::= { upsDiagSwitchGear 5 }
+
+upsDiagSwitchGearBreakerTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of switchgear breakers attached to the UPS."
+ ::= { upsDiagSwitchGear 6 }
+
+upsDiagSwitchGearBreakerTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsDiagSwitchGearBreakerEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Switchgear breaker table."
+ ::= { upsDiagSwitchGear 7 }
+
+ upsDiagSwitchGearBreakerEntry OBJECT-TYPE
+ SYNTAX UpsDiagSwitchGearBreakerEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of switchgear breakers."
+ INDEX { switchgearBreakerIndex }
+ ::= { upsDiagSwitchGearBreakerTable 1 }
+
+ UpsDiagSwitchGearBreakerEntry ::=
+ SEQUENCE {
+ switchgearBreakerIndex
+ INTEGER,
+ switchgearBreakerPresent
+ INTEGER,
+ switchgearBreakerName
+ DisplayString,
+ switchgearBreakerType
+ INTEGER,
+ switchgearBreakerStatus
+ INTEGER
+ }
+
+ switchgearBreakerIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of the switchgear breaker."
+ ::= { upsDiagSwitchGearBreakerEntry 1 }
+
+ switchgearBreakerPresent OBJECT-TYPE
+ SYNTAX INTEGER {
+ notPresent(1),
+ present(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates if the switchgear breaker is present.
+ notPresent(1) indicates that the breaker is not present.
+ present(2) indicates that the breaker is present."
+ ::= { upsDiagSwitchGearBreakerEntry 2 }
+
+ switchgearBreakerName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the switchgear breaker."
+ ::= { upsDiagSwitchGearBreakerEntry 3 }
+
+
+ switchgearBreakerType OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(1),
+ unitInputBreaker(2),
+ staticSwitchInputBreaker(3),
+ maintenanceBypassBreaker(4),
+ unitOutputBreaker(5),
+ systemIsolationBreaker(6),
+ batteryBreaker(7),
+ bypassBackFeedBreaker(8),
+ internalMaintenanceBypassBreaker(9),
+ redundantInternalMaintenanceBypassBreaker(10)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the switchgear breaker types available in the UPS system.
+ If the UPS is unable to find any attached breakers, this variable
+ is set to unknown(1). If the system has multiple breakers of the same
+ type (eg. multiple battery breakers) the status shown in OID
+ switchgearBreakerStatus will be the aggregated status."
+ ::= { upsDiagSwitchGearBreakerEntry 4 }
+
+ switchgearBreakerStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(1),
+ opened(2),
+ closed(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of switchgear breaker.
+ unknown(1) indicates the breaker status is unknown.
+ opened (2) indicates the breaker is opened.
+ closed (3) indicates the breaker is closed.
+ NOTE: If there are more than one breaker of the same type, the status reflects the aggregated value.
+ For battery breakers as example, closed would mean that at least one breaker is closed."
+ ::= { upsDiagSwitchGearBreakerEntry 5 }
+
+
+
+upsDiagSubFeedBreakerTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of subfeed breakers attached to the UPS."
+ ::= { upsDiagSwitchGear 8 }
+
+upsDiagSubFeedBreakerTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsDiagSubFeedBreakerEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Subfeed breaker table."
+ ::= { upsDiagSwitchGear 9 }
+
+ upsDiagSubFeedBreakerEntry OBJECT-TYPE
+ SYNTAX UpsDiagSubFeedBreakerEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of subfeed breakers."
+ INDEX { subfeedBreakerIndex }
+ ::= { upsDiagSubFeedBreakerTable 1 }
+
+ UpsDiagSubFeedBreakerEntry ::=
+ SEQUENCE {
+ subfeedBreakerIndex
+ INTEGER,
+ subfeedBreakerPresent
+ INTEGER,
+ subfeedBreakerRating
+ INTEGER,
+ subfeedBreakerUpperAcceptPowerWarning
+ INTEGER,
+ subfeedBreakerUpperAcceptPowerCritical
+ INTEGER,
+ subfeedBreakerStatus
+ INTEGER,
+ subfeedBreakerName
+ DisplayString,
+ subfeedBreakerCurrent
+ INTEGER
+ }
+
+ subfeedBreakerIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of the subfeed breakers."
+ ::= { upsDiagSubFeedBreakerEntry 1 }
+
+ subfeedBreakerPresent OBJECT-TYPE
+ SYNTAX INTEGER {
+ notPresent (1),
+ present (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates if the subfeed breaker is present.
+ notPresent (1) indicates that the breaker is not present.
+ present (2) indicates that the breaker is present."
+ ::= { upsDiagSubFeedBreakerEntry 2 }
+
+ subfeedBreakerRating OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current rating of the installed subfeed breaker."
+ ::= { upsDiagSubFeedBreakerEntry 3 }
+
+ subfeedBreakerUpperAcceptPowerWarning OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum acceptable load before warning is issued.
+ Expressed as percent of the subfeed breaker rating."
+ ::= { upsDiagSubFeedBreakerEntry 4 }
+
+
+
+ subfeedBreakerUpperAcceptPowerCritical OBJECT-TYPE
+ SYNTAX INTEGER (0..125)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum load before a critical alarm occurs.
+ Expressed as percent of the subfeed breaker rating."
+ ::= { upsDiagSubFeedBreakerEntry 5 }
+
+ subfeedBreakerStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ notInstalled (2),
+ opened (3),
+ closed (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the Circuit Breaker.
+ unknown(1) indicates the circuit breaker status is unknown.
+ notInstalled(2) indicates the circuit breaker is not installed.
+ opened(3) indicates the circuit breaker is opened.
+ closed(4) indicates the circuit breaker is closed."
+ ::= { upsDiagSubFeedBreakerEntry 6 }
+
+ subfeedBreakerName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the subfeed breaker."
+ ::= { upsDiagSubFeedBreakerEntry 7}
+
+ subfeedBreakerCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The subfeed current in tenths of Amps."
+ ::= { upsDiagSubFeedBreakerEntry 8 }
+
+
+upsDiagSwitchGearInstallationLoadPct OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The actual output load expressed as a percentage of the rating of the UPS."
+ ::= { upsDiagSwitchGear 10 }
+
+
+ upsDiagSubFeedPhaseTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UPSDiagSubFeedPhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of subfeed phase table."
+ ::= { upsDiagSwitchGear 11 }
+
+ upsDiagSubFeedPhaseEntry OBJECT-TYPE
+ SYNTAX UPSDiagSubFeedPhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular phase."
+ INDEX { upsDiagSubFeedPhaseIndex }
+ ::= { upsDiagSubFeedPhaseTable 1 }
+
+ UPSDiagSubFeedPhaseEntry ::= SEQUENCE {
+ upsDiagSubFeedBreakerIndex INTEGER,
+ upsDiagSubFeedPhaseIndex INTEGER,
+ upsDiagSubFeedPhaseCurrent INTEGER,
+ upsDiagSubFeedPhaseCurrentAlternate INTEGER
+ }
+
+ upsDiagSubFeedBreakerIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The subfeed breaker index."
+ ::= { upsDiagSubFeedPhaseEntry 1 }
+
+ upsDiagSubFeedPhaseIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The subfeed phase index."
+ ::= { upsDiagSubFeedPhaseEntry 2 }
+
+ upsDiagSubFeedPhaseCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The subfeed phase current in Amps."
+ ::= { upsDiagSubFeedPhaseEntry 3 }
+
+ upsDiagSubFeedPhaseCurrentAlternate OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The subfeed phase current in tenths of Amps."
+ ::= { upsDiagSubFeedPhaseEntry 4 }
+
+
+upsDiagSwitchgearSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The serial number of the UPS I/O Cabinet."
+ ::= { upsDiagSwitchGear 12 }
+
+upsDiagSwitchgearAmbientTemperature OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The ambient temperature of I/O Cabinet in tenths of degrees Celsius."
+ ::= { upsDiagSwitchGear 13 }
+
+upsDiagUsrSuppSwitchgearMonitorTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of user supplied Switch Gear Monitor Boards attached to the UPS."
+ ::= { upsDiagSwitchGear 14 }
+
+upsDiagUsrSuppSwitchgearMonitorTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsDiagUsrSuppSwitchgearMonitorEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for diagnostics of the user supplied Switch Gear Monitor Board."
+ ::= { upsDiagSwitchGear 15 }
+
+upsDiagUsrSuppSwitchgearMonitorEntry OBJECT-TYPE
+ SYNTAX UpsDiagUsrSuppSwitchgearMonitorEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The diagnostics of the user supplied Switch Gear Monitor Board."
+ INDEX { upsDiagUsrSuppSwitchgearMonitorIndex}
+ ::= { upsDiagUsrSuppSwitchgearMonitorTable 1 }
+
+UpsDiagUsrSuppSwitchgearMonitorEntry ::=
+ SEQUENCE {
+ upsDiagUsrSuppSwitchgearMonitorIndex INTEGER,
+ upsDiagUsrSuppSwitchgearMonitorStatus INTEGER,
+ upsDiagUsrSuppSwitchgearMonitorFirmwareRev DisplayString,
+ upsDiagUsrSuppSwitchgearMonitorHardwareRev DisplayString,
+ upsDiagUsrSuppSwitchgearMonitorSerialNum DisplayString,
+ upsDiagUsrSuppSwitchgearMonitorTemperature INTEGER
+
+ }
+
+upsDiagUsrSuppSwitchgearMonitorIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of the user supplied Switch Gear Monitor Board."
+ ::= { upsDiagUsrSuppSwitchgearMonitorEntry 1 }
+
+upsDiagUsrSuppSwitchgearMonitorStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ notInstalled (2),
+ offOk (3),
+ onOk (4),
+ offFail (5),
+ onFail (6),
+ lostComm (7)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the user supplied Switch Gear Monitor Board.
+ unknown(1) indicates the device status is unknown.
+ notInstalled(2) indicates the device is not installed.
+ offOk(3) indicates the device status is off and OK.
+ onOk(4) indicates the device status is on and OK.
+ offFail(5) indicates the device status is off and failed.
+ onFail(6) indicates the device status is on and failed.
+ lostComm(7) indicates the device has lost communication."
+ ::= { upsDiagUsrSuppSwitchgearMonitorEntry 2 }
+
+upsDiagUsrSuppSwitchgearMonitorFirmwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The firmware revision of the user supplied Switch Gear Monitor Board."
+ ::= { upsDiagUsrSuppSwitchgearMonitorEntry 3 }
+
+upsDiagUsrSuppSwitchgearMonitorHardwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The hardware revision of the user supplied Switch Gear Monitor Board."
+ ::= { upsDiagUsrSuppSwitchgearMonitorEntry 4 }
+
+upsDiagUsrSuppSwitchgearMonitorSerialNum OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The serial number of the user supplied
+ Switch Gear Monitor Board."
+ ::= { upsDiagUsrSuppSwitchgearMonitorEntry 5 }
+
+upsDiagUsrSuppSwitchgearMonitorTemperature OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+
+ "The temperature of the air around the user supplied
+ Switch Gear Monitor Board in tenths of degrees Celsius."
+ ::= { upsDiagUsrSuppSwitchgearMonitorEntry 6 }
+
+upsDiagMCCBBoxStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ notInstalled (2),
+ opened (3),
+ closed (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the MCCB Box (Molded Case Circuit Breaker Box) external device.
+ unknown(1) indicates the device status is unknown.
+ notInstalled(2) indicates the device is not installed.
+ opened(3) indicates the circuit is opened.
+ closed(4) indicates the circuit is closed."
+ ::= { upsDiagMCCBBox 1 }
+
+upsDiagTransformerStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ notInstalled (2),
+ ok (3),
+ fail (4),
+ lostComm (5),
+ overtemp (6),
+ opened (7),
+ closed (8)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the External Transformer.
+ unknown(1) indicates the device status is unknown.
+ notInstalled(2) indicates the device is not installed.
+ ok(3) indicates the device status is OK.
+ fail(4) indicates the device status has failed.
+ lostComm(5) indicates the device has lost communication.
+ overtemp(6) indicates the device has an over temperature condition.
+ opened(7) indicates the circuit is opened.
+ closed(8) indicates the circuit is closed."
+ ::= { upsDiagTransformer 1 }
+
+
+ upsDiagFlyWheelStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(1),
+ present(2),
+ notPresent(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the status of flywheel connected to UPS. If the UPS
+ is unable to determine the state of flywheel, this variable is
+ set to unknown(1)."
+ ::= { upsDiagFlyWheel 1 }
+
+
+
+
+-- the upsDiagnosticComBus group
+
+upsDiagComBusInternalMIMStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ notInstalled (2),
+ ok (3),
+ lostComm (4),
+ rxFailure (5),
+ txFailure (6)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the internal MIM communication bus.
+ unknown(1) indicates the device status is unknown.
+ notInstalled(2) indicates the device is not installed.
+ ok(3) indicates the device status is OK.
+ lostComm(4) indicates the device has lost communication.
+ rxFailure(5) indicates the device has a receive failure.
+ txFailure(6) indicates the device has a transmit failure."
+ ::= { upsDiagnosticComBus 1 }
+
+upsDiagComBusInternalRIMStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ notInstalled (2),
+ ok (3),
+ lostComm (4),
+ rxFailure (5),
+ txFailure (6)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the internal RIM communication bus.
+ unknown(1) indicates the device status is unknown.
+ notInstalled(2) indicates the device is not installed.
+ ok(3) indicates the device status is OK.
+ lostComm(4) indicates the device has lost communication.
+ rxFailure(5) indicates the device has a receive failure.
+ txFailure(6) indicates the device has a transmit failure."
+ ::= { upsDiagnosticComBus 2 }
+
+upsDiagComBusMIMtoRIMStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ notInstalled (2),
+ ok (3),
+ lostComm (4),
+ rxFailure (5),
+ txFailure (6)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the MIM to RIM communication bus.
+ unknown(1) indicates the device status is unknown.
+ notInstalled(2) indicates the device is not installed.
+ ok(3) indicates the device status is OK.
+ lostComm(4) indicates the device has lost communication.
+ rxFailure(5) indicates the device has a receive failure.
+ txFailure(6) indicates the device has a transmit failure."
+ ::= { upsDiagnosticComBus 3 }
+
+upsDiagComBusExternalMIMStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ notInstalled (2),
+ ok (3),
+ lostComm (4),
+ rxFailure (5),
+ txFailure (6)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the external MIM communication bus.
+ unknown(1) indicates the device status is unknown.
+ notInstalled(2) indicates the device is not installed.
+ ok(3) indicates the device status is OK.
+ lostComm(4) indicates the device has lost communication.
+ rxFailure(5) indicates the device has a receive failure.
+ txFailure(6) indicates the device has a transmit failure."
+ ::= { upsDiagnosticComBus 4 }
+
+upsDiagComBusExternalRIMStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ notInstalled (2),
+ ok (3),
+ lostComm (4),
+ rxFailure (5),
+ txFailure (6)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the external RIM communication bus.
+ unknown(1) indicates the device status is unknown.
+ notInstalled(2) indicates the device is not installed.
+ ok(3) indicates the device status is OK.
+ lostComm(4) indicates the device has lost communication.
+ rxFailure(5) indicates the device has a receive failure.
+ txFailure(6) indicates the device has a transmit failure."
+ ::= { upsDiagnosticComBus 5 }
+
+-- the upsDiagnosticPowerCabinet group
+upsDiagnosticPowerCabinetTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum number of Power Cabinets supported by the UPS."
+ ::= { upsDiagnosticPowerCabinet 1 }
+
+upsDiagnosticPowerCabinetTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsDiagnosticPowerCabinetEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for diagnostics of individual Power Cabinets.
+ The number of entries is contained in the upsDiagnosticPowerCabinetTableSize OID."
+ ::= { upsDiagnosticPowerCabinet 2 }
+
+upsDiagnosticPowerCabinetEntry OBJECT-TYPE
+ SYNTAX UpsDiagnosticPowerCabinetEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The diagnostics of a Power Cabinet."
+ INDEX { upsDiagnosticPowerCabinetIndex}
+ ::= { upsDiagnosticPowerCabinetTable 1 }
+
+UpsDiagnosticPowerCabinetEntry ::=
+ SEQUENCE {
+ upsDiagnosticPowerCabinetIndex INTEGER,
+ upsDiagnosticPowerCabinetAmbientTemperature INTEGER
+ }
+
+upsDiagnosticPowerCabinetIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the Power Cabinet."
+ ::= { upsDiagnosticPowerCabinetEntry 1 }
+
+upsDiagnosticPowerCabinetAmbientTemperature OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The ambient temperature of Power Cabinet in tenths of degrees Celsius.
+ If the Power Cabinet is not present, this variable is set to (-1)."
+ ::= { upsDiagnosticPowerCabinetEntry 2 }
+
+-- the upsDiagnosticDisplay group
+upsDiagnosticDisplayHardwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The hardware revision of the Display."
+ ::= { upsDiagnosticDisplay 1 }
+
+upsDiagnosticDisplaySerialNum OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The serial number of the Display."
+ ::= { upsDiagnosticDisplay 2 }
+
+upsDiagnosticDisplayFirmwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The firmware revision of the Display."
+ ::= { upsDiagnosticDisplay 3 }
+
+ upsDiagnosticDisplayModelNum OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The model number of the Display."
+ ::= { upsDiagnosticDisplay 4 }
+
+ upsDiagnosticDisplayStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ notInstalled (2),
+ offOk (3),
+ onOk (4),
+ offFail (5),
+ onFail (6),
+ lostComm (7)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The System Level Controller Status.
+ unknown(1) indicates the device status is unknown.
+ notInstalled(2) indicates the device is not installed.
+ offOk(3) indicates the device status is off and OK.
+ onOk(4) indicates the device status is on and OK.
+ offFail(5) indicates the device status is off and failed.
+ onFail(6) indicates the device status is on and failed.
+ lostComm(7) indicates the device has lost communication."
+ ::= { upsDiagnosticDisplay 5 }
+
+ -- the upsDiagnosticSLC group
+upsDiagnosticSLCHardwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The hardware revision of the System Level Controller."
+ ::= { upsDiagnosticSLC 1 }
+
+upsDiagnosticSLCSerialNum OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The serial number of the System Level Controller."
+ ::= { upsDiagnosticSLC 2 }
+
+upsDiagnosticSLCFirmwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The firmware revision of the System Level Controller."
+ ::= { upsDiagnosticSLC 3 }
+
+upsDiagnosticSLCModelNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Model number of the System Level Controller."
+ ::= { upsDiagnosticSLC 4 }
+
+ upsDiagSLCStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ notInstalled (2),
+ offOk (3),
+ onOk (4),
+ offFail (5),
+ onFail (6),
+ lostComm (7)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The System Level Controller Status.
+ unknown(1) indicates the device status is unknown.
+ notInstalled(2) indicates the device is not installed.
+ offOk(3) indicates the device status is off and OK.
+ onOk(4) indicates the device status is on and OK.
+ offFail(5) indicates the device status is off and failed.
+ onFail(6) indicates the device status is on and failed.
+ lostComm(7) indicates the device has lost communication."
+ ::= { upsDiagnosticSLC 5 }
+
+-- upsDiagnosticTemperature
+upsDiagnosticTemperatureAmbientTemperature OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The ambient temperature in tenths of degrees Celsius.
+ If not available, this variable is set to (-1999)."
+ ::= { upsDiagnosticTemperature 1 }
+
+
+-- upsDiagnosticUnitContoller group
+
+ upsDiagUnitControllerTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of Unit Controllers in or attached to the UPS."
+ ::= { upsDiagnosticUnitController 1 }
+
+upsDiagUnitControllerTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsDiagUnitControllerEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for diagnostics of individual Intelligence Modules. The number of
+ entries is contained in the upsDiagUnitControllerTableSize OID."
+ ::= { upsDiagnosticUnitController 2 }
+
+upsDiagUnitControllerEntry OBJECT-TYPE
+ SYNTAX UpsDiagUnitControllerEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The diagnostics and information of an Intelligence Module."
+ INDEX { upsDiagUnitControllerIndex}
+ ::= { upsDiagUnitControllerTable 1 }
+
+UpsDiagUnitControllerEntry ::=
+ SEQUENCE {
+ upsDiagUnitControllerIndex INTEGER,
+ upsDiagUnitControllerStatus INTEGER,
+ upsDiagUnitControllerFirmwareRev DisplayString,
+ upsDiagUnitControllerHardwareRev DisplayString,
+ upsDiagUnitControllerSerialNum DisplayString,
+ upsDiagUnitControllerModelNum DisplayString
+ }
+
+upsDiagUnitControllerIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the Unit Controller entry."
+ ::= { upsDiagUnitControllerEntry 1 }
+
+
+upsDiagUnitControllerStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ notInstalled (2),
+ offOk (3),
+ onOk (4),
+ offFail (5),
+ onFail (6),
+ lostComm (7)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the Unit Controller.
+ unknown(1) indicates the device status is unknown.
+ notInstalled(2) indicates the device is not installed.
+ offOk(3) indicates the device status is off and OK.
+ onOk(4) indicates the device status is on and OK.
+ offFail(5) indicates the device status is off and failed.
+ onFail(6) indicates the device status is on and failed.
+ lostComm(7) indicates the device has lost communication."
+ ::= { upsDiagUnitControllerEntry 2 }
+
+upsDiagUnitControllerFirmwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The firmware revision of the Unit Controller."
+ ::= { upsDiagUnitControllerEntry 3 }
+
+upsDiagUnitControllerHardwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The hardware revision of the Unit Controller."
+ ::= { upsDiagUnitControllerEntry 4 }
+
+upsDiagUnitControllerSerialNum OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The serial number of the Unit Controller."
+ ::= { upsDiagUnitControllerEntry 5 }
+
+upsDiagUnitControllerModelNum OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The model number of the Unit Controller."
+ ::= { upsDiagUnitControllerEntry 6 }
+
+-- the upsParallelSystem group
+
+upsParallelSysLocalAddress OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Defines the UPS ID number in the parallel system."
+ ::= { upsParallelSystem 1 }
+
+upsParallelSysRemoteAddress OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Defines the total number of UPSs in parallel."
+ ::= { upsParallelSystem 2 }
+
+upsParallelSysRedundancy OBJECT-TYPE
+ SYNTAX INTEGER {
+ nplus0 (1),
+ nplus1 (2),
+ nplus2 (3),
+ nplus3 (4),
+ nplus4 (5),
+ nplus5 (6)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The redundancy warning level for paralleled UPS
+ nplus0 (1) indicates that there are no redundant units.
+ nplus1 (2) indicates that there is one redundant unit.
+ nplus2 (3) indicates that there are two redundant units.
+ nplus3 (4) indicates that there are three redundant units.
+ nplus4 (5) indicates that there are four redundant unit.
+ nplus5 (6) indicates that there are five redundant units."
+ ::= { upsParallelSystem 3 }
+
+
+upsParallelInputMaximumCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Maximum input RMS current of the parallel system
+ measured in Amperes."
+ ::= { upsParallelSystem 4 }
+
+upsParallelTotalOutputPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Total Output power of UPS in kW
+ when UPS are configured in parallel
+ or -1 if it's unsupported by this UPS."
+ ::= { upsParallelSystem 5 }
+
+upsParallelTotalOutputApparentPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Total Output Apparent power of UPS in kVA
+ when UPS are configured in parallel
+ or -1 if it's unsupported by this UPS."
+ ::= { upsParallelSystem 6 }
+
+-- Parallel Input Phase Table
+
+ upsParallelInputPhaseTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsParallelInputPhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of input table entries."
+ ::= { upsParallelSystem 7 }
+
+ upsParallelInputPhaseEntry OBJECT-TYPE
+ SYNTAX UpsParallelInputPhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular input phase."
+ INDEX { upsParallelInputPhaseTableIndex, upsParallelInputPhaseIndex }
+ ::= { upsParallelInputPhaseTable 1 }
+
+ UpsParallelInputPhaseEntry ::= SEQUENCE {
+ upsParallelInputPhaseTableIndex INTEGER,
+ upsParallelInputPhaseIndex INTEGER,
+ upsParallelInputCurrent INTEGER,
+ upsParallelInputActivePower INTEGER,
+ upsParallelInputApparentPower INTEGER,
+ upsParallelInputVoltage INTEGER,
+ upsParallelInputMaxVoltage INTEGER,
+ upsParallelInputMaxCurrent INTEGER,
+ upsParallelInputTotalActivePower INTEGER,
+ upsParallelInputTotalApparentPower INTEGER
+ }
+
+ upsParallelInputPhaseTableIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The parallel unit identifier."
+ ::= { upsParallelInputPhaseEntry 1 }
+
+ upsParallelInputPhaseIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input phase identifier."
+ ::= { upsParallelInputPhaseEntry 2 }
+
+
+ upsParallelInputCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input current in amperes, or -1 if it's
+ unsupported by this UPS."
+ ::= { upsParallelInputPhaseEntry 3 }
+
+ upsParallelInputActivePower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input power in kW, or -1 if it's
+ unsupported by this UPS."
+ ::= { upsParallelInputPhaseEntry 4 }
+
+ upsParallelInputApparentPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input apparent power in kVA, or -1 if it's
+ unsupported by this UPS."
+ ::= { upsParallelInputPhaseEntry 5 }
+
+ upsParallelInputVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input voltage of UPS in volts, or -1 if it's
+ unsupported by this UPS."
+ ::= { upsParallelInputPhaseEntry 6 }
+
+ upsParallelInputMaxVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The peak input voltage in VAC measured since the last reset,
+ or -1 if it's unsupported by this UPS."
+ ::= { upsParallelInputPhaseEntry 7 }
+
+ upsParallelInputMaxCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The peak input current in amperes measured since last reset,
+ or -1 if it's unsupported by this UPS."
+ ::= { upsParallelInputPhaseEntry 8 }
+
+ upsParallelInputTotalActivePower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Total active input power of the parallel system in kW."
+ ::= { upsParallelInputPhaseEntry 9 }
+
+ upsParallelInputTotalApparentPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Total apparent input power of the parallel system in kVA."
+ ::= { upsParallelInputPhaseEntry 10 }
+
+
+-- Parallel Output Phase Table
+
+ upsParallelOutputPhaseTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsParallelOutputPhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of output table entries. The number of
+ entries is given by the sum of the upsPhaseNumOutputPhases."
+ ::= { upsParallelSystem 8 }
+
+ upsParallelOutputPhaseEntry OBJECT-TYPE
+ SYNTAX UpsParallelOutputPhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular output phase."
+ INDEX { upsParallelOutputPhaseTableIndex, upsParallelOutputPhaseIndex }
+ ::= { upsParallelOutputPhaseTable 1 }
+
+ UpsParallelOutputPhaseEntry ::= SEQUENCE {
+ upsParallelOutputPhaseTableIndex INTEGER,
+ upsParallelOutputPhaseIndex INTEGER,
+ upsParallelOutputCurrent INTEGER,
+ upsParallelOutputLoad INTEGER,
+ upsParallelOutputPercentLoad INTEGER,
+ upsParallelOutputPower INTEGER
+ }
+
+ upsParallelOutputPhaseTableIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output identifier."
+ ::= { upsParallelOutputPhaseEntry 1 }
+
+ upsParallelOutputPhaseIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output phase identifier."
+ ::= { upsParallelOutputPhaseEntry 2 }
+
+ upsParallelOutputCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output current in amperes drawn
+ by the load on the UPS, or -1 if it's unsupported
+ by this UPS."
+ ::= { upsParallelOutputPhaseEntry 3 }
+
+ upsParallelOutputLoad OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output load in VA, or -1 if it's unsupported
+ by this UPS."
+ ::= { upsParallelOutputPhaseEntry 4 }
+
+ upsParallelOutputPercentLoad OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The percentage of the UPS load capacity in VA at
+ present redundancy being used on this output phase,
+ or -1 if it's unsupported by this UPS."
+ ::= { upsParallelOutputPhaseEntry 5 }
+
+ upsParallelOutputPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output power in Watts, or -1 if it's
+ unsupported by this UPS."
+ ::= { upsParallelOutputPhaseEntry 6 }
+
+ -- Parallel Output Apparent Power Table
+
+ upsParallelOutputApparentPowerTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsParallelOutputApparentPowerEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of output table entries. The number of entries
+ is given by the value of upsOutputNumPhases."
+ ::= { upsParallelSystem 9 }
+
+ upsParallelOutputApparentPowerEntry OBJECT-TYPE
+ SYNTAX UpsParallelOutputApparentPowerEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular output."
+ INDEX { upsParallelOutputApparentPowerTableIndex }
+ ::= { upsParallelOutputApparentPowerTable 1 }
+
+ UpsParallelOutputApparentPowerEntry ::= SEQUENCE {
+ upsParallelOutputApparentPowerTableIndex INTEGER,
+ upsParallelOutputApparentPower INTEGER
+ }
+
+ upsParallelOutputApparentPowerTableIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The UPS parallel output identifier."
+ ::= { upsParallelOutputApparentPowerEntry 1 }
+
+ upsParallelOutputApparentPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The apparent power of each of UPS in kVA
+ when UPS are configured in parallel."
+ ::= { upsParallelOutputApparentPowerEntry 2 }
+
+
+upsParallelDiagSubSysBreakerTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsParallelDiagSubSysBreakerEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for diagnostics of parallel Circuit Breakers."
+ ::= { upsParallelSystem 10 }
+
+upsParallelDiagSubSysBreakerEntry OBJECT-TYPE
+ SYNTAX UpsParallelDiagSubSysBreakerEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The diagnostics of Circuit Breaker."
+ INDEX { upsParallelDiagSubSysBreakerFrameIndex, upsParallelDiagSubSysBreakerIndex}
+ ::= { upsParallelDiagSubSysBreakerTable 1 }
+
+UpsParallelDiagSubSysBreakerEntry ::=
+ SEQUENCE {
+ upsParallelDiagSubSysBreakerFrameIndex INTEGER,
+ upsParallelDiagSubSysBreakerIndex INTEGER,
+ upsParallelDiagSubSysBreakerStatus INTEGER,
+ upsParallelDiagSubSysBreakerName DisplayString
+ }
+
+upsParallelDiagSubSysBreakerFrameIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Parallel UPS index entry."
+ ::= { upsParallelDiagSubSysBreakerEntry 1 }
+
+upsParallelDiagSubSysBreakerIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of the Circuit Breaker."
+ ::= { upsParallelDiagSubSysBreakerEntry 2 }
+
+upsParallelDiagSubSysBreakerStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ notInstalled (2),
+ opened (3),
+ closed (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the Circuit Breaker.
+ unknown(1) indicates the circuit breaker status is unknown.
+ notInstalled(2) indicates the circuit breaker is not installed.
+ opened(3) indicates the circuit breaker is opened.
+ closed(4) indicates the circuit breaker is closed."
+ ::= { upsParallelDiagSubSysBreakerEntry 3 }
+
+upsParallelDiagSubSysBreakerName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of Circuit Breaker."
+ ::= { upsParallelDiagSubSysBreakerEntry 4 }
+
+upsParallelOutputTotalPercentLoad OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+
+DESCRIPTION
+ "The percentage of the UPS total load capacity in kVA
+ or -1 if it's unsupported by this UPS."
+ ::= { upsParallelSystem 11 }
+-- Parallel Output Active Power Table
+
+upsParallelOutputActivePowerTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsParallelOutputActivePowerEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of output table entries. The number of entries
+ is given by the value of upsParallelSysRemoteAddress."
+ ::= { upsParallelSystem 12 }
+
+upsParallelOutputActivePowerEntry OBJECT-TYPE
+ SYNTAX UpsParallelOutputActivePowerEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular output."
+ INDEX { upsParallelOutputActivePowerTableIndex }
+ ::= { upsParallelOutputActivePowerTable 1 }
+
+UpsParallelOutputActivePowerEntry ::= SEQUENCE {
+ upsParallelOutputActivePowerTableIndex INTEGER,
+ upsParallelOutputActivePower INTEGER
+ }
+
+upsParallelOutputActivePowerTableIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The UPS parallel output identifier."
+ ::= { upsParallelOutputActivePowerEntry 1 }
+
+upsParallelOutputActivePower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The active power of each UPS in kW
+ when UPSs are configured in parallel."
+ ::= { upsParallelOutputActivePowerEntry 2 }
+
+upsParallelSysSwitchGearInstallationLoadPct OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The actual output load expressed as a percentage of the rating of the
+ Parallel UPS system."
+ ::= { upsParallelSystem 13 }
+
+
+
+upsParallelSysRedundancyStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ nplus0 (1),
+ nplus1 (2),
+ nplus2 (3),
+ nplus3 (4),
+ nplus4 (5),
+ nplus5 (6)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Displays the number of backup or redundant UPSs set up on the parallel system.
+ nplus0 (1) no redundant units.
+ nplus1 (2) one redundant unit.
+ nplus2 (3) two redundant units.
+ nplus3 (4) three redundant units.
+ nplus4 (5) four redundant units.
+ nplus5 (6) five redundant units."
+ ::= { upsParallelSystem 14 }
+
+upsParallelSysName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "An ID string for the group of UPS units in the same parallel system.
+ Some products do not allow write operations for this OID."
+ ::= { upsParallelSystem 15 }
+
+upsParallelSysUpsTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of UPSs in parallel."
+ ::= { upsParallelSystem 16 }
+
+upsParallelSysUpsTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsParallelSysUpsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of UPS table entries. The number of entries
+ is given by the value of upsParallelSysUpsTableize."
+ ::= { upsParallelSystem 17 }
+
+upsParallelSysUpsEntry OBJECT-TYPE
+ SYNTAX UpsParallelSysUpsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular UPS in parallel."
+ INDEX { upsParallelSysUpsIndex}
+ ::= { upsParallelSysUpsTable 1 }
+
+UpsParallelSysUpsEntry ::=
+ SEQUENCE {
+ upsParallelSysUpsIndex INTEGER,
+ upsParallelSysUpsName DisplayString,
+ upsParallelSysUpsAlarmStatus INTEGER,
+ upsParallelSysUpsMode INTEGER,
+ upsParallelSysUpsSerialNumber DisplayString
+ }
+
+upsParallelSysUpsIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the Parallel System UPS table entry."
+ ::= { upsParallelSysUpsEntry 1 }
+
+upsParallelSysUpsName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The UPS id as assigned by the system."
+ ::= { upsParallelSysUpsEntry 2 }
+
+upsParallelSysUpsAlarmStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ normal (2),
+ informational (3),
+ warning (4),
+ critical (5)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The alarm status of the UPS.
+ unknown(1) indicates the UPS status is unknown.
+ normal(2) indicates UPS is functioning normally.
+ informational(3) indicates informational alarm present in the UPS.
+ warning(4) indicates warning alarm present in the UPS.
+ critical(5) indicates critical alarm present in the UPS."
+ ::= { upsParallelSysUpsEntry 3 }
+
+upsParallelSysUpsMode OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(1),
+ onLine(2),
+ onBattery(3),
+ onBatteryTest(4),
+ requestedStaticBypass(5),
+ forcedBypass(6),
+ maintenanceBypass(7),
+ off(8),
+ ecoMode(9),
+ hotStandby(10),
+ inquiring(11)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current operating mode of the UPS. If the UPS is unable to
+ determine the state of the UPS, this variable is set
+ to unknown(1)."
+ ::= { upsParallelSysUpsEntry 4 }
+
+upsParallelSysUpsSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Serial number of the UPS in parallel.
+ Equivalent to OID 1.3.6.1.4.1.318.1.1.1.1.2.3 (upsAdvIdentSerialNumber)."
+ ::= { upsParallelSysUpsEntry 5 }
+
+upsParallelNumOfUpsPoweringLoad OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Number of UPS powered and protecting the load which are not defective
+ (no battery fault, no internal fault)."
+ ::= { upsParallelSystem 18 }
+
+upsParallelMinNumOfRequiredUps OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Minimal number of UPS required to guarantee the availability of power."
+ ::= { upsParallelSystem 19 }
+
+-- the upsPhysicalLayout group
+upsIOFrameLayoutPositionID OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Defines the position ID of UPS frame."
+ ::= { upsPhysicalLayout 1 }
+
+upsBottomFeedFrameLayoutPositionID OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Defines the position ID of bottom feed frame."
+ ::= { upsPhysicalLayout 2 }
+
+upsSwitchGearLayoutPositionID OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Defines the position ID of switchgear."
+ ::= { upsPhysicalLayout 3 }
+
+-- the upsBatteryFrameLayoutTable subgroup
+upsBatteryFrameLayoutTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of battery frames."
+ ::= { upsPhysicalLayout 4 }
+
+upsBatteryFrameLayoutTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsBatteryFrameLayoutEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Battery frame layout position ID table."
+ ::= { upsPhysicalLayout 5 }
+
+ upsBatteryFrameLayoutEntry OBJECT-TYPE
+ SYNTAX UpsBatteryFrameLayoutEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of layout position IDs of battery frames."
+ INDEX { batteryFrameIndex }
+ ::= { upsBatteryFrameLayoutTable 1 }
+
+ UpsBatteryFrameLayoutEntry ::=
+ SEQUENCE {
+ batteryFrameIndex
+ INTEGER,
+ batteryFramePositionID
+ INTEGER
+ }
+
+ batteryFrameIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of the battery frame."
+ ::= { upsBatteryFrameLayoutEntry 1 }
+
+ batteryFramePositionID OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Defines the position ID of each of the battery frames in the row."
+ ::= { upsBatteryFrameLayoutEntry 2 }
+
+-- the upsSideCarFrameLayoutTable subgroup
+upsSideCarFrameLayoutTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of sidecar frames."
+ ::= { upsPhysicalLayout 6 }
+
+upsSideCarFrameLayoutTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsSideCarFrameLayoutEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Sidecar frame layout position ID table."
+ ::= { upsPhysicalLayout 7 }
+
+ upsSideCarFrameLayoutEntry OBJECT-TYPE
+ SYNTAX UpsSideCarFrameLayoutEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of sidecar frame layout position IDs."
+ INDEX { sideCarFrameIndex }
+ ::= { upsSideCarFrameLayoutTable 1 }
+
+ UpsSideCarFrameLayoutEntry ::=
+ SEQUENCE {
+ sideCarFrameIndex
+ INTEGER,
+ sideCarFramePositionID
+ INTEGER
+ }
+
+ sideCarFrameIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of the sidecar frame."
+ ::= { upsSideCarFrameLayoutEntry 1 }
+
+ sideCarFramePositionID OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Defines the position ID of each of the sidecar frames in the row."
+ ::= { upsSideCarFrameLayoutEntry 2 }
+
+-- the upsPowerFrameLayoutTable subgroup
+upsPowerFrameLayoutTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of power frames."
+ ::= { upsPhysicalLayout 8 }
+
+upsPowerFrameLayoutTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsPowerFrameLayoutEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Power frame layout position ID table."
+ ::= { upsPhysicalLayout 9 }
+
+ upsPowerFrameLayoutEntry OBJECT-TYPE
+ SYNTAX UpsPowerFrameLayoutEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of power frame layout position IDs."
+ INDEX { powerFrameIndex }
+ ::= { upsPowerFrameLayoutTable 1 }
+
+ UpsPowerFrameLayoutEntry ::=
+ SEQUENCE {
+ powerFrameIndex
+ INTEGER,
+ powerFramePositionID
+ INTEGER
+ }
+
+ powerFrameIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of the power frame."
+ ::= { upsPowerFrameLayoutEntry 1 }
+
+ powerFramePositionID OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Defines the position ID of each of the power frames in the row."
+ ::= { upsPowerFrameLayoutEntry 2 }
+
+-- the upsIntegratedATS group
+
+upsIntegratedATSSelectedSource OBJECT-TYPE
+ SYNTAX INTEGER {
+ noSourceSelected (1),
+ unknown (2),
+ sourceA (3),
+ sourceB (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The source which is currently selected by the ATS to supply the UPS."
+ ::= { upsIntegratedATS 1 }
+
+
+upsIntegratedATSPreferredSource OBJECT-TYPE
+ SYNTAX INTEGER {
+ upsIntegratedATSNoSourcePreference (1),
+ upsIntegratedATSPreferSourceA (2),
+ upsIntegratedATSPreferSourceB (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The preferred source of power when both sources are OK."
+ ::= { upsIntegratedATS 2 }
+
+upsIntegratedATSUpsReturnStaggering OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "This is a delay factor applied to the retransfer of this UPS with integrated ATS.
+ When multiple UPSs are in use from a single source, each UPS can have a unique delay value,
+ which will reduce inrush by preventing all UPSs from transferring at the same time."
+ ::= { upsIntegratedATS 3 }
+
+upsIntegratedATSSourceTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of input sources for this integrated ATS."
+ ::= { upsIntegratedATS 4 }
+
+upsIntegratedATSSourceTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsIntegratedATSSourceEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting status and settings for the ATS input sources.
+ The number of entries is contained in the upsIntegratedATSSourceTableSize OID."
+ ::= { upsIntegratedATS 5 }
+
+upsIntegratedATSSourceEntry OBJECT-TYPE
+ SYNTAX UpsIntegratedATSSourceEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The input source status to get."
+ INDEX { upsIntegratedATSSourceIndex}
+ ::= { upsIntegratedATSSourceTable 1 }
+
+UpsIntegratedATSSourceEntry ::=
+ SEQUENCE {
+ upsIntegratedATSSourceIndex INTEGER,
+ upsIntegratedATSSourceName DisplayString,
+ upsIntegratedATSSourceStatus INTEGER,
+ upsIntegratedATSLineFailDelay INTEGER,
+ upsIntegratedATSLineStabilityDelay INTEGER
+ }
+
+upsIntegratedATSSourceIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the input source entry."
+ ::= { upsIntegratedATSSourceEntry 1 }
+
+upsIntegratedATSSourceName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the input source. This OID is provided
+ for informational purposes only."
+ ::= { upsIntegratedATSSourceEntry 2 }
+
+upsIntegratedATSSourceStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ upsIntegratedATSSourceGood (1),
+ upsIntegratedATSSourceBad (2),
+ upsIntegratedATSSourceUnknown (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this variable will return the input source status."
+ ::= { upsIntegratedATSSourceEntry 3 }
+
+upsIntegratedATSLineFailDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The delay between a selected input source becoming bad, and the ATS switching away from that source.
+ This delay is used to make sure that the line has truly failed before the ATS will be switched.
+ Specified in seconds."
+ ::= { upsIntegratedATSSourceEntry 4 }
+
+upsIntegratedATSLineStabilityDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The delay between an unselected input source becoming good, and the ATS switching to that source.
+ This delay is used to make sure that the line has truly returned before the ATS will be switched.
+ Specified in seconds."
+ ::= { upsIntegratedATSSourceEntry 5 }
+
+-- the upsDCOutput group
+
+upsDCOutputStatus OBJECT IDENTIFIER ::= { upsDCOutput 1 }
+
+upsDCOutputStatusTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of DC outputs on the UPS."
+ ::= { upsDCOutputStatus 1 }
+
+upsDCOutputStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsDCOutputStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Provides status information on UPS DC outputs.
+ The number of entries is contained in the upsDCOutputStatusTableSize OID."
+ ::= { upsDCOutputStatus 2 }
+
+upsDCOutputStatusEntry OBJECT-TYPE
+ SYNTAX UpsDCOutputStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The DC output."
+ INDEX { upsDCOutputStatusTableIndex}
+ ::= { upsDCOutputStatusTable 1 }
+
+UpsDCOutputStatusEntry ::=
+ SEQUENCE {
+ upsDCOutputStatusTableIndex INTEGER,
+ upsDCOutputStatusVoltageNominal INTEGER,
+ upsDCOutputStatusCurrentRating INTEGER,
+ upsDCOutputStatusVoltage INTEGER,
+ upsDCOutputStatusCurrent INTEGER,
+ upsDCOutputStatusAbnormalConditions DisplayString
+ }
+
+upsDCOutputStatusTableIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the DC output status entry."
+ ::= { upsDCOutputStatusEntry 1 }
+
+upsDCOutputStatusVoltageNominal OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The desired voltage for this output in tenths of VDC.
+ When the output is on and there are no fault conditions,
+ the actual voltage should be near the nominal."
+ ::= { upsDCOutputStatusEntry 2 }
+
+upsDCOutputStatusCurrentRating OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The amount of current this output is able to supply in
+ tenths of amperes."
+ ::= { upsDCOutputStatusEntry 3 }
+
+upsDCOutputStatusVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The voltage measured on this output in tenths of VDC."
+ ::= { upsDCOutputStatusEntry 4 }
+
+upsDCOutputStatusCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current drawn by the load measured on this output
+ in tenths of amperes."
+ ::= { upsDCOutputStatusEntry 5 }
+
+upsDCOutputStatusAbnormalConditions OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An ASCII string containing flags representing active
+ output faults. If the Network Card is unable to determine
+ the state of the faults, this variable is set to 'UNKNOWN'.
+
+ The flags are numbered 1 onward, read from left to
+ right. The flags are defined as follows starting from 1:
+
+ Flag 1: Output Overload
+ Flag 2: Output Short Circuit
+ Flag 3: Output Over Voltage
+ Flag 4: <Not Used>
+ Flag 5: Overtemperature
+ Flag 6: Backfeed Relay Fault
+ Flag 7: <Not Used>
+ Flag 8: PFC Input Relay Fault
+ Flag 9: <Not Used>
+ Flag 10: Bypass Relay Fault
+ Flag 11: <Not Used>
+ Flag 12: <Not Used>
+ Flag 13: <Not Used>
+ Flag 14: <Not Used>
+ Flag 15: <Not Used>
+ Flag 16: <Not Used>
+ Flag 17: <Not Used>
+ Flag 18: <Not Used>
+ Flag 19: Output Fault (over or undervoltage)
+ Flag 20: Bus Converter Fault
+ Flag 21: Sensor Fault
+ Flag 21: <Not Used>
+ Flag 22: <Not Used>
+ Flag 23: <Not Used>
+ Flag 24: <Not Used>
+ Flag 25: <Not Used>
+ Flag 26: <Not Used>
+ Flag 27: <Not Used>
+ Flag 28: <Not Used>
+ Flag 29: <Not Used>
+ Flag 30: <Not Used>
+ Flag 31: <Not Used>
+ Flag 32: <Not Used>"
+ ::= { upsDCOutputStatusEntry 6 }
+
+-- the serialPort2Config group
+
+serialPort2Mode OBJECT-TYPE
+ SYNTAX INTEGER {
+ localConsole(1),
+ passthrough(2)
+ }
+ ACCESS read-write
+ STATUS obsolete
+ DESCRIPTION
+ "Setting this variable to passthrough will enable mini's port2
+ behave like a UPS port. Choosing localConsole will enable the port
+ to be used as local console."
+ ::= { serialPort2Config 1 }
+-- the serialPort2Control group
+
+setPulseOnTXD OBJECT-TYPE
+ SYNTAX INTEGER {
+ noSetPulseOnTXD(1),
+ setPulseOnTXD(2),
+ setTXDLow(3),
+ setTXDHigh(4)
+
+ }
+ ACCESS read-write
+ STATUS obsolete
+ DESCRIPTION
+ "Setting this variable to setPulseOnTXD(2)
+ causes adapter to generate a PULSE on TXD pin of serial port 2.
+ The duration in the prototype implementation will be 1 second.
+
+ Setting this value to noSetPulseOnTXD(1) has no
+ effect.
+
+ The value noSetPulseOnTXD(1) will always be returned
+ when the variable is read.
+
+ Setting this value to setTXDLow(3), or setTXDHigh(4) will keep TXD
+ always low or high respectively."
+ ::= { serialPort2Control 1 }
+
+-- the sPDUIdent group
+
+sPDUIdentHardwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The hardware revision of the PDU. This value
+ is set at the factory."
+ ::= { sPDUIdent 1 }
+
+sPDUIdentFirmwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An 8 byte ID string identifying the PDU firmware revision.
+ This value is set at the factory."
+ ::= { sPDUIdent 2 }
+
+
+sPDUIdentDateOfManufacture OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The date when the PDU was manufactured in mm/dd/yy format.
+ This value is set at the factory. The year 2000 will be
+ represented by 00."
+ ::= { sPDUIdent 3 }
+
+sPDUIdentModelNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A 10-character string identifying the model number of
+ the PDU internal. This value is set at the factory."
+ ::= { sPDUIdent 4 }
+
+sPDUIdentSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A 12-character string identifying the serial number of
+ the PDU internal microprocessor. This value is set at
+ the factory."
+ ::= { sPDUIdent 5 }
+
+
+-- the sPDUMasterControl group
+
+sPDUMasterControlSwitch OBJECT-TYPE
+ SYNTAX INTEGER {
+ turnAllOnNow (1),
+ turnAllOnSequence (2),
+ turnAllOffNow (3),
+ rebootAllNow (4),
+ rebootAllSequence (5),
+ noCommand (6),
+ turnAllOffSequence (7)
+ }
+
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to turnAllOnNow (1) will turn all outlets
+ on immediately.
+
+ Setting this OID to turnAllOnSequence (2) will turn all outlets
+ on as defined by each outlet's sPDUOutletPowerOnTime OID value.
+
+ Setting this OID to turnAllOff (3) will turn all outlets
+ off immediately.
+
+ Setting this OID to rebootAllNow (4) will reboot all outlets
+ immediately.
+
+ For MasterSwitch firmware version 1.X, setting this OID to
+ rebootAllSequence (5) reboots all outlets, with power returned
+ to the outlets in the sequence defined by each outlet's
+ sPDUOutletPowerOnTime OID value.
+
+ For MasterSwitch firmware version 2.X, setting this OID to
+ rebootAllSequence (5) will cause a turnAllOffSequence to be performed.
+ Once all outlets are off, the MasterSwitch will then delay the
+ sPDUMasterConfigReboot OID time, and then perform a turnAllOnSequence.
+
+ For MasterSwitch firmware version 2.X, setting this OID to
+ turnAllOffSequence (7) will turn all outlets off as defined by
+ each outlet's sPDUOutletPowerOffTime OID value.
+
+ For MasterSwitch firmware version 1.X, setting this OID to
+ turnAllOffSequence (7) will have no effect.
+
+ Getting this OID will return the noCommand (6) value."
+
+ ::= { sPDUMasterControl 1 }
+
+
+sPDUMasterState OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will cause the status of all outlets to be
+ returned. This OID is provided for informational purposes only.
+ To change the outlet state, the user should use the sPDUOutletCtl
+ OID in the sPDUOutletControlTable.
+
+ The format of the data returned is a character string consisting
+ of the word 'On' if the outlet is on or 'Off' if the outlet is
+ off. At least one space will delimit each outlet entry in the
+ string.
+
+ If the outlet states are unknown, the character string 'Unknown'
+ will be returned. This signifies that there is an inconsistency
+ in the PDU. In the rare case that this should happen, the user
+ is advised to shut down all equipment powered by the PDU and
+ then cycle the PDU's power. This will put the PDU in a consistent
+ state."
+
+ ::= { sPDUMasterControl 2 }
+
+sPDUMasterPending OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will cause the command pending status of all outlets to be returned.
+
+ The format of the data returned is a character string consisting
+ of the word 'Yes' if a command is pending for the outlet or 'No'
+ if there is no command pending for the outlet. At least one
+ space will delimit each outlet entry in the string.
+
+ If the pending states are unknown, the character string 'Unknown'
+ will be returned. This signifies that there is an inconsistency
+ in the PDU. In the rare case that this should happen, the user
+ is advised to shut down all equipment powered by the PDU and then
+ cycle the PDU's power. This will put the PDU in a consistent state."
+ ::= { sPDUMasterControl 3 }
+
+
+-- the sPDUMasterConfig group
+
+sPDUMasterConfigPowerOn OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ " The amount of delay, in seconds, between when
+ power is provided to the PDU and when the PDU
+ provides basic master power to the outlets.
+
+ Allowed values are:
+
+ -1 never apply power automatically.
+ 0 apply power immediately.
+ 15 apply power in 15 seconds.
+ 30 apply power in 30 seconds.
+ 45 apply power in 45 seconds.
+ 60 apply power in 60 seconds (1 minute).
+ 120 apply power in 120 seconds (2 minutes).
+ 300 apply power in 300 seconds (5 minutes).
+
+ If a value other than a supported value is provided in a
+ set request, the PDU interprets it as the next lower
+ acceptable value. If the provided value is lower than
+ the lowest acceptable value, the lowest acceptable
+ value is used."
+
+ ::= { sPDUMasterConfig 1 }
+
+sPDUMasterConfigReboot OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "During a reboot sequence, power is turned off and then
+ back on. This OID defines the amount of time to wait,
+ in seconds, after turning the power off, at the start
+ of the sequence, before turning power back on, at the
+ end of the reboot sequence.
+
+ Allowed values are:
+
+ 5 wait 5 seconds between off/on.
+ 10 wait 10 seconds between off/on.
+ 15 wait 15 seconds between off/on.
+ 20 wait 20 seconds between off/on.
+ 30 wait 30 seconds between off/on.
+ 45 wait 45 seconds between off/on.
+ 60 wait 60 seconds (1 minute) between off/on.
+
+ If a value other than a supported value is provided in a
+ set request, the PDU interprets it as the next lower
+ acceptable value. If the provided value is lower than
+ the lowest acceptable value, the lowest acceptable
+ value is used.
+
+ This OID is read-only for the MasterSwitch version 2.X and is the
+ maximum sPDUOutletRebootDuration OID of the individual outlets."
+
+ ::= { sPDUMasterConfig 2 }
+
+sPDUMasterConfigPDUName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the PDU."
+ ::= { sPDUMasterConfig 3 }
+
+
+
+-- the sPDUOutletControl group
+sPDUOutletControlTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of outlets for the PDU."
+ ::= { sPDUOutletControl 1 }
+
+
+sPDUOutletControlTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF SPDUOutletControlEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for control of individual outlet switches. The number of
+ entries is contained in the sPDUOutletControlTableSize OID."
+ ::= { sPDUOutletControl 2 }
+
+sPDUOutletControlEntry OBJECT-TYPE
+ SYNTAX SPDUOutletControlEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The outlets to control."
+ INDEX { sPDUOutletControlIndex}
+ ::= { sPDUOutletControlTable 1 }
+
+SPDUOutletControlEntry ::=
+ SEQUENCE {
+ sPDUOutletControlIndex INTEGER,
+ sPDUOutletPending INTEGER,
+ sPDUOutletCtl INTEGER,
+ sPDUOutletCtlName DisplayString
+ }
+
+sPDUOutletControlIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the outlet entry."
+ ::= { sPDUOutletControlEntry 1 }
+
+sPDUOutletPending OBJECT-TYPE
+ SYNTAX INTEGER{
+ commandPending (1),
+ noCommandPending (2),
+ commandPendingUnknown (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Reports whether the current outlet has a pending command.
+
+ If the commandPendingUnknown (3) value is returned, all
+ devices powered by the PDU should be shut down. The PDU's
+ power should then be cycled to clear this condition."
+
+ ::= { sPDUOutletControlEntry 2 }
+
+sPDUOutletCtl OBJECT-TYPE
+ SYNTAX INTEGER {
+ outletOn (1),
+ outletOff (2),
+ outletReboot (3),
+ outletUnknown (4),
+ outletOnWithDelay (5),
+ outletOffWithDelay (6),
+ outletRebootWithDelay (7)
+ }
+
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this variable will return the outlet state. If
+ the outlet is on, the outletOn (1) value will be returned.
+ If the outlet is off, the outletOff (2) value will be
+ returned.
+
+ If the state of the outlet cannot be determined, the
+ outletUnknown (4) value will be returned. If the
+ outletUnknown condition should occur, all devices
+ powered by the PDU should be shut down. The PDU's power
+ should then be cycled to clear this condition.
+
+ Setting this variable to outletOn (1) will turn the outlet on.
+
+ Setting this variable to outletOff (2) will turn the outlet off.
+
+ Setting this variable to outletReboot (3) will reboot the outlet.
+
+ Setting this variable to outletOnWithDelay (5) will turn the outlet on
+ after the sPDUOutletPowerOnTime OID has elapsed. This option is not
+ valid for MasterSwitch firmware version 1.X.
+
+ Setting this variable to outletOffWithDelay (6) will turn the outlet off
+ after the sPDUOutletPowerOffTime OID has elapsed. This option is not valid
+ for MasterSwitch firmware version 1.X.
+
+ Setting this variable to outletRebootWithDelay (7) will turn the outlet off
+ after the sPDUOutletPowerOffTime OID has elapsed, wait the sPDUOutletRebootDuration
+ OID time, then turn the outlet back on.
+ This option is not valid for MasterSwitch firmware version 1.X."
+
+ ::= { sPDUOutletControlEntry 3 }
+
+sPDUOutletCtlName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the outlet. Maximum size is 20 characters.
+ This OID is provided for informational purposes only.
+ This value is set by the sPDUOutletName OID."
+
+ ::= { sPDUOutletControlEntry 4 }
+
+-- the sPDUOutletConfig group
+sPDUOutletConfigTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of outlets for the PDU."
+ ::= { sPDUOutletConfig 1 }
+
+sPDUOutletConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF SPDUOutletConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The list of outlets to configure. The number of
+ entries is defined by the sPDUOutletConfigTableSize
+ OID."
+
+ ::= { sPDUOutletConfig 2 }
+
+sPDUOutletConfigEntry OBJECT-TYPE
+ SYNTAX SPDUOutletConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The outlets to control."
+ INDEX { sPDUOutletConfigIndex}
+ ::= { sPDUOutletConfigTable 1 }
+
+SPDUOutletConfigEntry ::=
+ SEQUENCE {
+ sPDUOutletConfigIndex INTEGER,
+ sPDUOutletPowerOnTime INTEGER,
+ sPDUOutletName DisplayString,
+ sPDUOutletPowerOffTime INTEGER,
+ sPDUOutletRebootDuration INTEGER
+ }
+
+sPDUOutletConfigIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the outlet entry."
+ ::= { sPDUOutletConfigEntry 1 }
+
+sPDUOutletPowerOnTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The amount of time (in seconds) the outlet will delay
+ powering on when the MasterSwitch is powered on.
+
+ Allowed values are:
+
+ -1 never power on automatically.
+ 0 power on with the Master Switch.
+ 15 power on 15 seconds after the MasterSwitch has power applied.
+ 30 power on 30 seconds after the MasterSwitch has power applied.
+ 45 power on 45 seconds after the MasterSwitch has power applied.
+ 60 power on 60 seconds (1 minute) after the MasterSwitch has power applied.
+ 120 power on 120 seconds (2 minutes) after the MasterSwitch has power applied.
+ 300 power on 300 seconds (5 minutes) after the MasterSwitch has power applied.
+
+ If a value other than a supported value is provided in a
+ set request, the PDU interprets it as the next lower
+ acceptable value. If the provided value is lower than
+ the lowest acceptable value, the lowest acceptable
+ value is used."
+
+ ::= { sPDUOutletConfigEntry 2 }
+
+sPDUOutletName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the outlet. Maximum size is 20 characters."
+
+ ::= { sPDUOutletConfigEntry 3 }
+
+sPDUOutletPowerOffTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The amount of time (in seconds) the outlet will delay
+ powering off.
+
+ Allowed values are:
+
+ -1 never power off automatically.
+ 0 power off with the MasterSwitch.
+ 15 power off 15 seconds after being commanded.
+ 30 power off 30 seconds after being commanded.
+ 45 power off 45 seconds after being commanded.
+ 60 power off 60 seconds (1 minute) after being commanded.
+ 120 power off 120 seconds (2 minutes) after being commanded.
+ 300 power off 300 seconds (5 minutes) after being commanded.
+
+ If a value other than a supported value is provided in a
+ set request, the PDU interprets it as the next lower
+ acceptable value. If the provided value is lower than
+ the lowest acceptable value, the lowest acceptable
+ value is used.
+
+ This OID is not available for MasterSwitch firmware version 1.X."
+
+ ::= { sPDUOutletConfigEntry 4 }
+
+sPDUOutletRebootDuration OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "During a reboot sequence, power is turned off and then
+ back on. This OID defines the amount of time to wait,
+ in seconds, after turning the power off, at the start
+ of the sequence, before turning power back on, at the
+ end of the reboot sequence.
+
+ Allowed values are:
+
+ 5 wait 5 seconds between off/on.
+ 10 wait 10 seconds between off/on.
+ 15 wait 15 seconds between off/on.
+ 20 wait 20 seconds between off/on.
+ 30 wait 30 seconds between off/on.
+ 45 wait 45 seconds between off/on.
+ 60 wait 60 seconds (1 minute) between off/on.
+
+ If a value other than a supported value is provided in a
+ set request, the PDU interprets it as the next lower
+ acceptable value. If the provided value is lower than
+ the lowest acceptable value, the lowest acceptable
+ value is used.
+
+ This OID is not available for MasterSwitch firmware version 1.X."
+
+ ::= { sPDUOutletConfigEntry 5 }
+
+
+-- the sPDUIdentVM group
+
+sPDUIdentVMTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of MasterSwitch VMs controllable
+ by this IP address."
+ ::= { sPDUIdentVM 1 }
+
+
+sPDUIdentVMTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF SPDUIdentVMEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for query of the individual MasterSwitch VMs.
+ The number of entries is contained in the
+ sPDUIdentVMTableSize OID."
+ ::= { sPDUIdentVM 2 }
+
+sPDUIdentVMEntry OBJECT-TYPE
+ SYNTAX SPDUIdentVMEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The MasterSwitch VMs to query."
+ INDEX { sPDUIdentVMIndex}
+ ::= { sPDUIdentVMTable 1 }
+
+SPDUIdentVMEntry ::=
+ SEQUENCE {
+ sPDUIdentVMIndex INTEGER,
+ sPDUIdentNameVM DisplayString,
+ sPDUIdentHardwareRevVM DisplayString,
+ sPDUIdentFirmwareRevVM DisplayString,
+ sPDUIdentDateOfManufactureVM DisplayString,
+ sPDUIdentModelNumberVM DisplayString,
+ sPDUIdentSerialNumberVM DisplayString
+ }
+
+sPDUIdentVMIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the MasterSwitch VM entry."
+ ::= { sPDUIdentVMEntry 1 }
+
+sPDUIdentNameVM OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A 23-character string identifying the
+ MasterSwitch VM. "
+ ::= { sPDUIdentVMEntry 2 }
+
+sPDUIdentHardwareRevVM OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The hardware version of the MasterSwitch VM.
+ This value is set at the factory."
+ ::= { sPDUIdentVMEntry 3 }
+
+sPDUIdentFirmwareRevVM OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An 6-character ID string identifying the MasterSwitch VM
+ firmware version. This value is set at the factory."
+ ::= { sPDUIdentVMEntry 4 }
+
+
+sPDUIdentDateOfManufactureVM OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The date when the MasterSwitch VM was manufactured in mm/dd/yyyy format.
+ This value is set at the factory. "
+ ::= { sPDUIdentVMEntry 5 }
+
+sPDUIdentModelNumberVM OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A 17-character string identifying the model number of
+ the MasterSwitch VM. This value is set at the factory."
+ ::= { sPDUIdentVMEntry 6 }
+
+sPDUIdentSerialNumberVM OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A 17-character string identifying the serial number of
+ the MasterSwitch VM. This value is set at the factory."
+ ::= { sPDUIdentVMEntry 7 }
+
+
+-- the sPDUMasterControlVM group
+
+sPDUMasterControlVMTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of MasterSwitch VMs controllable
+ by this IP address."
+ ::= { sPDUMasterControlVM 1 }
+
+
+sPDUMasterControlVMTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF SPDUMasterControlVMEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for control of the individual MasterSwitch VMs.
+ The number of entries is contained in the
+ sPDUMasterControlVMTableSize OID."
+ ::= { sPDUMasterControlVM 2 }
+
+sPDUMasterControlVMEntry OBJECT-TYPE
+ SYNTAX SPDUMasterControlVMEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The MasterSwitch VMs to control."
+ INDEX { sPDUMasterControlVMIndex}
+ ::= { sPDUMasterControlVMTable 1 }
+
+SPDUMasterControlVMEntry ::=
+ SEQUENCE {
+ sPDUMasterControlVMIndex INTEGER,
+ sPDUMasterControlVMName DisplayString,
+ sPDUMasterControlVMCommand INTEGER
+ }
+
+sPDUMasterControlVMIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the MasterSwitch VM entry."
+ ::= { sPDUMasterControlVMEntry 1 }
+
+sPDUMasterControlVMName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the MasterSwitch VM. The maximum
+ value is 23 characters. The name is set by
+ using the sPDUMasterConfigVMName OID."
+ ::= { sPDUMasterControlVMEntry 2 }
+
+sPDUMasterControlVMCommand OBJECT-TYPE
+ SYNTAX INTEGER {
+ noCommandAllVM (1),
+ immediateAllOnVM (2),
+ immediateAllOffVM (3),
+ immediateAllRebootVM (4),
+ delayedAllOnVM (5),
+ delayedAllOffVM (6),
+ sequencedAllRebootVM (7),
+ delayedAllRebootVM (8),
+ delayedSequenceAllRebootVM (9),
+ cancelAllPendingCommandsVM (10),
+ audioAlarmMute (11)
+ }
+
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to immediateAllOnVM (2) will turn all outlets
+ on immediately.
+
+ Setting this OID to immediateAllOffVM (3) will turn all outlets
+ off immediately.
+
+ Setting this OID to immediateAllRebootVM (4) will reboot all outlets
+ immediately.
+
+ Setting this OID to delayedAllOnVM (5) will turn all outlets on as
+ defined by each outlet's sPDUOutletConfigVMPowerOnTime OID value.
+
+ Setting this OID to delayedAllOffVM (6) will turn all outlets
+ off as defined by each outlet's sPDUOutletConfigVMPowerOffTime OID value.
+
+ Setting this OID to sequencedAllRebootVM (7) will cause a
+ immediateAllOffVM command to be performed. The MasterSwitch VM will
+ then delay the sPDUMasterStatusVMRebootDuration OID time, and then
+ perform a delayedAllOnVM command.
+
+ Setting this OID to delayedAllRebootVM (8) will cause a delayedAllOffVM
+ command to be performed. Each outlet will then wait its
+ sPDUOutletConfigVMRebootDuration before returning power to the outlet.
+
+ Setting this OID to delayedSequenceAllRebootVM (9) will cause a
+ delayedAllOffVM command to be performed. Once all outlets are off,
+ the MasterSwitch VM will then delay the sPDUMasterStatusVMRebootDuration
+ OID time, and then perform a delayedAllOnVM command.
+
+ Setting this OID to cancelAllPendingCommandsVM (10) will cause all pending
+ commands on the MasterSwitch VM to be canceled.
+
+
+ Setting this OID to audioAlarmMute (11) will temporarily silence the audible
+ alarm for the duration of the current overload condition. The audible alarm
+ will be activated on subsequent overload alarms.
+
+ Getting this OID will return the noCommandAllVM (1) value."
+ ::= { sPDUMasterControlVMEntry 3 }
+
+
+-- the sPDUMasterConfigVM group
+
+sPDUMasterConfigVMTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of MasterSwitch VMs configurable
+ by this IP address."
+ ::= { sPDUMasterConfigVM 1 }
+
+
+sPDUMasterConfigVMTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF SPDUMasterConfigVMEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for configuration of the individual MasterSwitch VMs.
+ The number of entries is contained in the
+ sPDUMasterConfigVMTableSize OID."
+ ::= { sPDUMasterConfigVM 2 }
+
+sPDUMasterConfigVMEntry OBJECT-TYPE
+ SYNTAX SPDUMasterConfigVMEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The MasterSwitch VMs to configure."
+ INDEX { sPDUMasterConfigVMIndex}
+ ::= { sPDUMasterConfigVMTable 1 }
+
+SPDUMasterConfigVMEntry ::=
+ SEQUENCE {
+ sPDUMasterConfigVMIndex INTEGER,
+ sPDUMasterConfigVMName DisplayString,
+ sPDUMasterConfigVMColdstartDelay INTEGER,
+ sPDUMasterConfigVMAudioAlarmActivated INTEGER,
+ sPDUMasterConfigVMHighLoadWarningThreshold INTEGER,
+ sPDUMasterConfigVMLowLoadWarningThreshold INTEGER,
+ sPDUMasterConfigVMOverloadRestriction INTEGER
+ }
+
+sPDUMasterConfigVMIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the MasterSwitch VM entry."
+ ::= { sPDUMasterConfigVMEntry 1 }
+
+
+sPDUMasterConfigVMName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the MasterSwitch VM. Maximum size is 23 characters."
+ ::= { sPDUMasterConfigVMEntry 2 }
+
+sPDUMasterConfigVMColdstartDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ " The amount of delay, in seconds, between when
+ power is provided to the MasterSwitch VM and
+ when the MasterSwitch VM provides basic master
+ power to the outlets.
+
+ Allowed values are:
+
+ -1 never apply power automatically.
+ 0 apply power immediately.
+ 15 apply power in 15 seconds.
+ 30 apply power in 30 seconds.
+ 45 apply power in 45 seconds.
+ 60 apply power in 60 seconds (1 minute).
+ 120 apply power in 120 seconds (2 minutes).
+ 300 apply power in 300 seconds (5 minutes).
+
+ If a value other than a supported value is provided in a
+ set request, the MasterSwitch VM interprets it as the next lower
+ acceptable value. If the provided value is lower than
+ the lowest acceptable value, the lowest acceptable
+ value is used."
+ ::= { sPDUMasterConfigVMEntry 3 }
+
+sPDUMasterConfigVMAudioAlarmActivated OBJECT-TYPE
+ SYNTAX INTEGER {
+ audioAlarmActiveNever (1),
+ audioAlarmActiveOnOverload (2),
+ audioAlarmActiveOnOverloadImminent (3)
+ }
+
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to audioAlarmActiveNever (1) will disable
+ the audio alarm on the MasterSwitch VM.
+
+ Setting this OID to audioAlarmActiveOnOverload (2) will
+ activate the audio alarm on the MasterSwitch VM when an
+ overload condition is present.
+
+ Setting this OID to audioAlarmActiveOnOverloadImminent (3)
+ will activate the audio alarm on the MasterSwitch VM when
+ the load on the MasterSwitch VM has surpassed the
+ sPDUMasterConfigVMHighLoadWarningThreshold OID value."
+ ::= { sPDUMasterConfigVMEntry 4 }
+
+sPDUMasterConfigVMHighLoadWarningThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A threshold that indicates the power consumption of
+ the load is nearing an overload condition. It is
+ represented as a percentage of full load."
+ ::= { sPDUMasterConfigVMEntry 5 }
+
+sPDUMasterConfigVMLowLoadWarningThreshold OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A threshold that indicates the power consumption of
+ the load is nearing a low consumption condition. It is
+ represented as a percentage of full load."
+ ::= { sPDUMasterConfigVMEntry 6 }
+
+sPDUMasterConfigVMOverloadRestriction OBJECT-TYPE
+ SYNTAX INTEGER {
+ alwaysAllowTurnON (1),
+ restrictOnWarning (2),
+ restrictOnOverload (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "This OID controls the behavior of the MasterSwitch VM
+ when an overload condition is possible and additional
+ outlets are requested to be turned on.
+
+ Setting this OID to alwaysAllowTurnON (1) will always allow
+ the outlets to turn on.
+
+ Setting this OID to restrictOnWarning (2) will not allow
+ outlets to turn on if the sPDUMasterConfigVMHighLoadWarningThreshold
+ OID is exceeded.
+
+ Setting this OID to restrictOnOverload (3) will not allow
+ outlets to turn on if the MasterSwitch Vm is in an
+ overload condition."
+ ::= { sPDUMasterConfigVMEntry 7 }
+
+-- the sPDUMasterStatusVM group
+
+sPDUMasterStatusVMTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of MasterSwitch VMs at
+ this IP address."
+ ::= { sPDUMasterStatusVM 1 }
+
+
+sPDUMasterStatusVMTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF SPDUMasterStatusVMEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for gathering of status from the individual
+ MasterSwitch VMs. The number of entries is contained
+ in the sPDUMasterStatusVMTableSize OID."
+ ::= { sPDUMasterStatusVM 2 }
+
+sPDUMasterStatusVMEntry OBJECT-TYPE
+ SYNTAX SPDUMasterStatusVMEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The MasterSwitch VMs to gather status from."
+ INDEX { sPDUMasterStatusVMIndex}
+ ::= { sPDUMasterStatusVMTable 1 }
+
+SPDUMasterStatusVMEntry ::=
+ SEQUENCE {
+ sPDUMasterStatusVMIndex INTEGER,
+ sPDUMasterStatusVMName DisplayString,
+ sPDUMasterStatusVMCommandPending INTEGER,
+ sPDUMasterStatusVMOverloadCondition INTEGER,
+ sPDUMasterStatusVMLowLoadCondition INTEGER,
+ sPDUMasterStatusVMCurrentLoad INTEGER,
+ sPDUMasterStatusVMMaxLoad INTEGER,
+ sPDUMasterStatusVMOutletCount INTEGER,
+ sPDUMasterStatusVMRebootDuration INTEGER
+ }
+
+sPDUMasterStatusVMIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the MasterSwitch VM entry."
+ ::= { sPDUMasterStatusVMEntry 1 }
+
+sPDUMasterStatusVMName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the MasterSwitch VM. Maximum size is 23 characters."
+ ::= { sPDUMasterStatusVMEntry 2 }
+
+sPDUMasterStatusVMCommandPending OBJECT-TYPE
+ SYNTAX INTEGER {
+ commandPendingMasterTrueVM (1),
+ commandPendingMasterFalseVM (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return commandPendingMasterTrueVM (1)
+ if the MasterSwitch VM has a pending command on any of its
+ outlets.
+
+ commandPendingMasterFalseVM (2) will be returned if there are
+ no pending commands."
+ ::= { sPDUMasterStatusVMEntry 3 }
+
+sPDUMasterStatusVMOverloadCondition OBJECT-TYPE
+ SYNTAX INTEGER {
+ overloadConditionTrueVM (1),
+ overloadConditionFalseVM (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return overloadConditionTrueVM (1)
+ if the sPDUMasterConfigVMHighLoadWarningThreshold OID is
+ violated.
+
+ overloadConditionFalseVM (2) will be returned if the
+ sPDUMasterConfigVMHighLoadWarningThreshold OID is not
+ violated."
+ ::= { sPDUMasterStatusVMEntry 4 }
+
+sPDUMasterStatusVMLowLoadCondition OBJECT-TYPE
+ SYNTAX INTEGER {
+ lowLoadConditionTrueVM (1),
+ lowLoadConditionFalseVM (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return lowLoadConditionTrueVM (1)
+ if the sPDUMasterConfigVMLowLoadWarningThreshold OID is
+ violated.
+
+ lowLoadConditionFalseVM (2) will be returned if the
+ sPDUMasterConfigVMHighLoadWarningThreshold OID is not
+ violated. "
+ ::= { sPDUMasterStatusVMEntry 5 }
+
+sPDUMasterStatusVMCurrentLoad OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return the total amount of power
+ being consumed by the load. It is represented as a
+ percentage of full load."
+ ::= { sPDUMasterStatusVMEntry 6 }
+
+sPDUMasterStatusVMMaxLoad OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return the total amount of power
+ that this MasterSwitch VM can provide. It is represented
+ in Amps."
+ ::= { sPDUMasterStatusVMEntry 7 }
+
+sPDUMasterStatusVMOutletCount OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return the number of controllable
+ outlets for this MasterSwitch VM."
+ ::= { sPDUMasterStatusVMEntry 8 }
+
+sPDUMasterStatusVMRebootDuration OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return the largest
+ sPDUOutletConfigVMRebootDuration OID time
+ for this MasterSwitch VM."
+ ::= { sPDUMasterStatusVMEntry 9 }
+
+-- the sPDUOutletControlVM group
+
+
+sPDUOutletControlVMTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF SPDUOutletControlVMEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for control of individual outlet switches. The number of
+ entries is contained in the sPDUMasterStatusOutletCount OID."
+ ::= { sPDUOutletControlVM 1 }
+
+sPDUOutletControlVMEntry OBJECT-TYPE
+ SYNTAX SPDUOutletControlVMEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The outlets to control."
+ INDEX { sPDUOutletControlVMIndex, sPDUOutletControlVMOutletIndex }
+ ::= { sPDUOutletControlVMTable 1 }
+
+SPDUOutletControlVMEntry ::=
+ SEQUENCE {
+ sPDUOutletControlVMIndex INTEGER,
+ sPDUOutletControlVMName DisplayString,
+ sPDUOutletControlVMOutletIndex INTEGER,
+ sPDUOutletControlVMOutletName DisplayString,
+ sPDUOutletControlVMOutletCommand INTEGER
+ }
+
+sPDUOutletControlVMIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the MasterSwitch VM."
+ ::= { sPDUOutletControlVMEntry 1 }
+
+sPDUOutletControlVMName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the MasterSwitch VM. Maximum size is 23 characters.
+ This OID is provided for informational purposes only."
+ ::= { sPDUOutletControlVMEntry 2 }
+
+sPDUOutletControlVMOutletIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the outlet entry."
+ ::= { sPDUOutletControlVMEntry 3 }
+
+sPDUOutletControlVMOutletName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the outlet. Maximum size is 23 characters.
+ This OID is provided for informational purposes only."
+ ::= { sPDUOutletControlVMEntry 4 }
+
+sPDUOutletControlVMOutletCommand OBJECT-TYPE
+ SYNTAX INTEGER {
+ immediateOnVM (1),
+ immediateOffVM (2),
+ immediateRebootVM (3),
+ delayedOnVM (4),
+ delayedOffVM (5),
+ delayedRebootVM (6),
+ cancelPendingCommandVM (7)
+
+ }
+
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this variable will return the outlet state. If
+ the outlet is on, the immediateOnVM (1) value will be returned.
+ If the outlet is off, the immediateOffVM (2) value will be
+ returned.
+
+
+ Setting this variable to immediateOnVM (1) will immediately turn the outlet on.
+
+ Setting this variable to immediateOffVM (2) will immediately turn the outlet off.
+
+ Setting this variable to immediateRebootVM (3) will immediately reboot the outlet.
+
+ Setting this variable to delayedOnVM (4) will turn the outlet on
+ after the sPDUOutletConfigVMPowerOnTime OID time has elapsed.
+
+ Setting this variable to delayedOffVM (5) will turn the outlet off
+ after the sPDUOutletConfigVMPowerOffTime OID time has elapsed.
+
+ Setting this variable to delayedRebootVM (6) will cause the
+ MasterSwitch VM to perform a delayedOffVM command, wait the
+ sPDUOutletConfigVMRebootDuration OID time, and then perform the
+ immediateOnVM command.
+
+ Setting this variable to cancelPendingCommandVM (7) will cause any
+ pending command to this outlet to be canceled."
+ ::= { sPDUOutletControlVMEntry 5 }
+
+-- the sPDUOutletConfigVM group
+
+sPDUOutletConfigVMTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF SPDUOutletConfigVMEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for configuration of individual outlets. The number of
+ entries is contained in the sPDUMasterStatusOutletCount OID."
+ ::= { sPDUOutletConfigVM 1 }
+
+sPDUOutletConfigVMEntry OBJECT-TYPE
+ SYNTAX SPDUOutletConfigVMEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The outlets to configure."
+ INDEX { sPDUOutletConfigVMIndex, sPDUOutletConfigVMOutletIndex }
+ ::= { sPDUOutletConfigVMTable 1 }
+
+SPDUOutletConfigVMEntry ::=
+ SEQUENCE {
+ sPDUOutletConfigVMIndex INTEGER,
+ sPDUOutletConfigVMName DisplayString,
+ sPDUOutletConfigVMOutletIndex INTEGER,
+ sPDUOutletConfigVMOutletName DisplayString,
+ sPDUOutletConfigVMPowerOnTime INTEGER,
+ sPDUOutletConfigVMPowerOffTime INTEGER,
+ sPDUOutletConfigVMRebootDuration INTEGER
+ }
+
+sPDUOutletConfigVMIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the MasterSwitch VM."
+ ::= { sPDUOutletConfigVMEntry 1 }
+
+sPDUOutletConfigVMName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the MasterSwitch VM. Maximum size is 23 characters."
+ ::= { sPDUOutletConfigVMEntry 2 }
+
+sPDUOutletConfigVMOutletIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the outlet entry."
+ ::= { sPDUOutletConfigVMEntry 3 }
+
+
+sPDUOutletConfigVMOutletName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the outlet. Maximum size is 23 characters."
+ ::= { sPDUOutletConfigVMEntry 4 }
+
+sPDUOutletConfigVMPowerOnTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The amount of time (in seconds) the outlet will delay
+ powering on at coldstart or when a command that requires
+ a turn-on delay is issued.
+
+ Allowed values are:
+
+ -1 never power on.
+ 0 power on immediately.
+ 15 power on 15 seconds after being commanded.
+ 30 power on 30 seconds after being commanded.
+ 45 power on 45 seconds after being commanded.
+ 60 power on 60 seconds (1 minute) after being commanded.
+ 120 power on 120 seconds (2 minutes) after being commanded.
+ 300 power on 300 seconds (5 minutes) after being commanded.
+
+ If a value other than a supported value is provided in a
+ set request, the MasterSwitch VM interprets it as the next lower
+ acceptable value. If the provided value is lower than
+ the lowest acceptable value, the lowest acceptable
+ value is used."
+ ::= { sPDUOutletConfigVMEntry 5 }
+
+
+sPDUOutletConfigVMPowerOffTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The amount of time (in seconds) the outlet will delay
+ powering off when a command that requires
+ a turn-off delay is issued.
+
+
+ Allowed values are:
+
+ -1 never power off automatically.
+ 0 power off immediately.
+ 15 power off 15 seconds after being commanded.
+ 30 power off 30 seconds after being commanded.
+ 45 power off 45 seconds after being commanded.
+ 60 power off 60 seconds (1 minute) after being commanded.
+ 120 power off 120 seconds (2 minutes) after being commanded.
+ 300 power off 300 seconds (5 minutes) after being commanded.
+
+ If a value other than a supported value is provided in a
+ set request, the MasterSwitch VM interprets it as the next lower
+ acceptable value. If the provided value is lower than
+ the lowest acceptable value, the lowest acceptable
+ value is used."
+ ::= { sPDUOutletConfigVMEntry 6 }
+
+sPDUOutletConfigVMRebootDuration OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "During a reboot sequence, power is turned off and then
+ back on. This OID defines the amount of time to wait,
+ in seconds, after turning the power off, at the start
+ of the sequence, before turning power back on, at the
+ end of the reboot sequence.
+
+ Allowed values are:
+
+ 5 wait 5 seconds between off/on.
+ 10 wait 10 seconds between off/on.
+ 15 wait 15 seconds between off/on.
+ 20 wait 20 seconds between off/on.
+ 30 wait 30 seconds between off/on.
+ 45 wait 45 seconds between off/on.
+ 60 wait 60 seconds (1 minute) between off/on.
+
+ If a value other than a supported value is provided in a
+ set request, the MasterSwitch VM interprets it as the next lower
+ acceptable value. If the provided value is lower than
+ the lowest acceptable value, the lowest acceptable
+ value is used."
+ ::= { sPDUOutletConfigVMEntry 7 }
+
+-- the sPDUOutletStatusVM group
+
+sPDUOutletStatusVMTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF SPDUOutletStatusVMEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting of status of individual outlets. The number of
+ entries is contained in the sPDUMasterStatusOutletCount OID."
+ ::= { sPDUOutletStatusVM 1 }
+
+sPDUOutletStatusVMEntry OBJECT-TYPE
+ SYNTAX SPDUOutletStatusVMEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The outlets to gather status from."
+ INDEX { sPDUOutletStatusVMIndex, sPDUOutletStatusVMOutletIndex }
+ ::= { sPDUOutletStatusVMTable 1 }
+
+SPDUOutletStatusVMEntry ::=
+ SEQUENCE {
+ sPDUOutletStatusVMIndex INTEGER,
+ sPDUOutletStatusVMName DisplayString,
+ sPDUOutletStatusVMOutletIndex INTEGER,
+ sPDUOutletStatusVMOutletName DisplayString,
+ sPDUOutletStatusVMOutletState INTEGER,
+ sPDUOutletStatusVMCommandPending INTEGER
+ }
+
+sPDUOutletStatusVMIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the MasterSwitch VM."
+ ::= { sPDUOutletStatusVMEntry 1 }
+
+sPDUOutletStatusVMName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the MasterSwitch VM. Maximum size is 23 characters."
+ ::= { sPDUOutletStatusVMEntry 2 }
+
+sPDUOutletStatusVMOutletIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the outlet entry."
+ ::= { sPDUOutletStatusVMEntry 3 }
+
+sPDUOutletStatusVMOutletName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the outlet. Maximum size is 23 characters."
+ ::= { sPDUOutletStatusVMEntry 4 }
+
+sPDUOutletStatusVMOutletState OBJECT-TYPE
+ SYNTAX INTEGER {
+ outletStatusVMOn (1),
+ outletStatusVMOff (2)
+ }
+
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this variable will return the outlet state. If
+ the outlet is on, the outletStatusOnVM (1) value will be returned.
+ If the outlet is off, the outletStatusOffVM (2) value will be
+ returned. "
+ ::= { sPDUOutletStatusVMEntry 5 }
+
+sPDUOutletStatusVMCommandPending OBJECT-TYPE
+ SYNTAX INTEGER {
+ outletStatusVMCommandPending (1),
+ outletStatusVMNoCommandPending (2)
+ }
+
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this variable will return the command pending
+ state of the outlet. If a command is pending on the
+ outlet, the outletStatusVMCommandPending (1) value
+ will be returned. If there is not a command pending
+ on the outlet, the outletStatusVMNoCommandPending (2)
+ will be returned."
+ ::= { sPDUOutletStatusVMEntry 6 }
+
+-- the sPDUIdentMSP group
+
+sPDUIdentMSPTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of MasterSwitch pluses controllable
+ by this IP address."
+ ::= { sPDUIdentMSP 1 }
+
+
+sPDUIdentMSPTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF SPDUIdentMSPEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for query of the individual MasterSwitch pluses.
+ The number of entries is contained in the
+ sPDUIdentMSPTableSize OID."
+ ::= { sPDUIdentMSP 2 }
+
+sPDUIdentMSPEntry OBJECT-TYPE
+ SYNTAX SPDUIdentMSPEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The MasterSwitch pluses to query."
+ INDEX { sPDUIdentMSPIndex}
+ ::= { sPDUIdentMSPTable 1 }
+
+SPDUIdentMSPEntry ::=
+ SEQUENCE {
+ sPDUIdentMSPIndex INTEGER,
+ sPDUIdentNameMSP DisplayString,
+ sPDUIdentHardwareRevMSP DisplayString,
+ sPDUIdentFirmwareRevMSP DisplayString,
+ sPDUIdentDateOfManufactureMSP DisplayString,
+ sPDUIdentModelNumberMSP DisplayString,
+ sPDUIdentSerialNumberMSP DisplayString
+ }
+
+sPDUIdentMSPIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the MasterSwitch plus entry."
+ ::= { sPDUIdentMSPEntry 1 }
+
+sPDUIdentNameMSP OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the MasterSwitch plus. The maximum
+ value is 23 characters. The name is set by
+ using the sPDUMasterConfigMSPName OID."
+ ::= { sPDUIdentMSPEntry 2 }
+
+sPDUIdentHardwareRevMSP OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The hardware version of the MasterSwitch plus.
+ This value is set at the factory."
+ ::= { sPDUIdentMSPEntry 3 }
+
+sPDUIdentFirmwareRevMSP OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An 6-character ID string identifying the MasterSwitch plus
+ firmware version. This value is set at the factory."
+ ::= { sPDUIdentMSPEntry 4 }
+
+sPDUIdentDateOfManufactureMSP OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The date when the MasterSwitch plus was manufactured in mm/dd/yyyy format.
+ This value is set at the factory. "
+ ::= { sPDUIdentMSPEntry 5 }
+
+sPDUIdentModelNumberMSP OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A 17-character string identifying the model number of
+ the MasterSwitch plus. This value is set at the factory."
+ ::= { sPDUIdentMSPEntry 6 }
+
+sPDUIdentSerialNumberMSP OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A 17-character string identifying the serial number of
+ the MasterSwitch plus. This value is set at the factory."
+ ::= { sPDUIdentMSPEntry 7 }
+
+
+-- the sPDUMasterControlMSP group
+
+sPDUMasterControlMSPTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of MasterSwitch pluses controllable
+ by this IP address."
+ ::= { sPDUMasterControlMSP 1 }
+
+sPDUMasterControlMSPTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF SPDUMasterControlMSPEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for control of the individual MasterSwitch pluses.
+ The number of entries is contained in the
+ sPDUMasterControlMSPTableSize OID."
+ ::= { sPDUMasterControlMSP 2 }
+
+sPDUMasterControlMSPEntry OBJECT-TYPE
+ SYNTAX SPDUMasterControlMSPEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The MasterSwitch pluses to control."
+ INDEX { sPDUMasterControlMSPIndex}
+ ::= { sPDUMasterControlMSPTable 1 }
+
+SPDUMasterControlMSPEntry ::=
+ SEQUENCE {
+ sPDUMasterControlMSPIndex INTEGER,
+ sPDUMasterControlMSPName DisplayString,
+ sPDUMasterControlMSPCommand INTEGER
+ }
+
+sPDUMasterControlMSPIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the MasterSwitch plus entry."
+ ::= { sPDUMasterControlMSPEntry 1 }
+
+sPDUMasterControlMSPName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the MasterSwitch plus. The maximum
+ value is 23 characters. The name is set by
+ using the sPDUMasterConfigMSPName OID."
+ ::= { sPDUMasterControlMSPEntry 2 }
+
+sPDUMasterControlMSPCommand OBJECT-TYPE
+ SYNTAX INTEGER {
+ noCommandAllMSP (1),
+ immediateAllOnMSP (2),
+ sequencedAllOnMSP (3),
+ immediateAllOffMSP (4),
+ gracefulAllRebootMSP (5),
+ immediateAllRebootMSP (6),
+ gracefulAllShutdownMSP (7),
+ overrideAllBatCapThreshMSP (8),
+ cancelAllPendingCommandsMSP (9),
+ restoreFactoryDefaultsMSP (10)
+ }
+
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to immediateAllOnMSP (2) will turn all outlets
+ on immediately.
+
+ Setting this OID to sequencedAllOnMSP (3) will turn all outlets
+ on as defined by each outlet's sPDUOutletConfigMSPPowerOnDelay OID value.
+
+ Setting this OID to immediateAllOffMSP (4) will turn all outlets
+ off immediately.
+
+ Setting this OID to gracefulAllRebootMSP (5) will reboot all outlets
+ (after the device running PowerChute confirms shutdown) as defined
+ by each outlet's sPDUOutletConfigMSPRebootDuration OID time value.
+
+ Setting this OID to immediateAllRebootMSP (6) will reboot all outlets
+ immediately.
+
+ Setting this OID to gracefulAllShutdownMSP (7) will shutdown all outlets
+ (after the device running PowerChute confirms shutdown) as defined
+ by each outlet's sPDUOutletConfigMSPPowerOffDelay OID time value. Each
+ outlet will then turn on after the sum of its
+ sPDUOutletConfigMSPRestartDelay and sPDUOutletConfigMSPPowerOnDelay OID
+ values.
+
+ Setting this OID to overrideAllBatCapThreshMSP (8) will cause the
+ outlet to ignore the Battery Capacity Threshold and proceed turning on
+ the outlets as defined by each outlet's sPDUOutletConfigMSPPowerOnDelay
+ OID value.
+
+ Setting this OID to cancelAllPendingCommandsMSP (9) will cause all pending
+ commands on the MasterSwitch plus to be canceled.
+
+ Setting this OID to restoreFactoryDefaultsMSP (10) will cause the settings of
+ the MasterSwitch plus to be restored to the factory defaults.
+
+ Getting this OID will return the noCommandAllMSP (1) value."
+ ::= { sPDUMasterControlMSPEntry 3 }
+
+
+-- the sPDUMasterConfigMSP group
+
+sPDUMasterConfigMSPTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of MasterSwitch pluses configurable
+ by this IP address."
+ ::= { sPDUMasterConfigMSP 1 }
+
+sPDUMasterConfigMSPTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF SPDUMasterConfigMSPEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for configuration of the individual MasterSwitch pluses.
+ The number of entries is contained in the
+ sPDUMasterConfigMSPTableSize OID."
+ ::= { sPDUMasterConfigMSP 2 }
+
+sPDUMasterConfigMSPEntry OBJECT-TYPE
+ SYNTAX SPDUMasterConfigMSPEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The MasterSwitch pluses to configure."
+ INDEX { sPDUMasterConfigMSPIndex}
+ ::= { sPDUMasterConfigMSPTable 1 }
+
+SPDUMasterConfigMSPEntry ::=
+ SEQUENCE {
+ sPDUMasterConfigMSPIndex INTEGER,
+ sPDUMasterConfigMSPName DisplayString,
+ sPDUMasterConfigMSPPowerOnTimeDelay INTEGER,
+ sPDUMasterConfigMSPManualButton INTEGER
+ }
+
+sPDUMasterConfigMSPIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the MasterSwitch plus entry."
+ ::= { sPDUMasterConfigMSPEntry 1 }
+
+sPDUMasterConfigMSPName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the MasterSwitch plus. Maximum size is 23 characters."
+ ::= { sPDUMasterConfigMSPEntry 2 }
+
+sPDUMasterConfigMSPPowerOnTimeDelay OBJECT-TYPE
+ SYNTAX INTEGER (0..9999)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ " The amount of delay, in seconds, between when
+ power is provided to the MasterSwitch plus and
+ when the MasterSwitch plus provides basic master
+ power to the outlets.
+
+ Allowed values are:
+
+ 0 - 9999 seconds (0 - 2hrs, 46 mins, 39 secs).
+ 0 indicates to apply power immediately."
+ ::= { sPDUMasterConfigMSPEntry 3 }
+
+
+sPDUMasterConfigMSPManualButton OBJECT-TYPE
+ SYNTAX INTEGER {
+ manualButtonDisabled (1),
+ manualButtonEnabled (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to manualButtonDisabled (1) will disable
+ the manual button on the MasterSwitch plus.
+
+ Setting this OID to manualButtonEnabled (2) will enable
+ the manual button on the MasterSwitch plus."
+ ::= { sPDUMasterConfigMSPEntry 4 }
+
+-- the sPDUMasterStatusMSP group
+
+sPDUMasterStatusMSPTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of MasterSwitch pluses at
+ this IP address."
+ ::= { sPDUMasterStatusMSP 1 }
+
+
+sPDUMasterStatusMSPTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF SPDUMasterStatusMSPEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for gathering of status from the individual
+ MasterSwitch pluses. The number of entries is contained
+ in the sPDUMasterStatusMSPTableSize OID."
+ ::= { sPDUMasterStatusMSP 2 }
+
+sPDUMasterStatusMSPEntry OBJECT-TYPE
+ SYNTAX SPDUMasterStatusMSPEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The MasterSwitch pluses to gather status from."
+ INDEX { sPDUMasterStatusMSPIndex}
+ ::= { sPDUMasterStatusMSPTable 1 }
+
+SPDUMasterStatusMSPEntry ::=
+ SEQUENCE {
+ sPDUMasterStatusMSPIndex INTEGER,
+ sPDUMasterStatusMSPName DisplayString,
+ sPDUMasterStatusMSPOutletCount INTEGER
+ }
+
+sPDUMasterStatusMSPIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the MasterSwitch plus entry."
+ ::= { sPDUMasterStatusMSPEntry 1 }
+
+sPDUMasterStatusMSPName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the MasterSwitch plus. The maximum
+ value is 23 characters. The name is set by
+ using the sPDUMasterConfigMSPName OID."
+ ::= { sPDUMasterStatusMSPEntry 2 }
+
+sPDUMasterStatusMSPOutletCount OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return the number of controllable
+ outlets for this MasterSwitch plus."
+ ::= { sPDUMasterStatusMSPEntry 3 }
+
+-- the sPDUOutletControlMSP group
+
+sPDUOutletControlMSPTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF SPDUOutletControlMSPEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for control of individual outlet switches. The number of
+ entries is contained in the sPDUMasterStatusMSPOutletCount OID."
+ ::= { sPDUOutletControlMSP 1 }
+
+sPDUOutletControlMSPEntry OBJECT-TYPE
+ SYNTAX SPDUOutletControlMSPEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The outlets to control."
+ INDEX { sPDUOutletControlMSPIndex, sPDUOutletControlMSPOutletIndex }
+ ::= { sPDUOutletControlMSPTable 1 }
+
+SPDUOutletControlMSPEntry ::=
+ SEQUENCE {
+ sPDUOutletControlMSPIndex INTEGER,
+ sPDUOutletControlMSPName DisplayString,
+ sPDUOutletControlMSPOutletIndex INTEGER,
+ sPDUOutletControlMSPOutletName DisplayString,
+ sPDUOutletControlMSPOutletCommand INTEGER
+ }
+
+sPDUOutletControlMSPIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the MasterSwitch plus."
+ ::= { sPDUOutletControlMSPEntry 1 }
+
+sPDUOutletControlMSPName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the MasterSwitch plus. The maximum
+ value is 23 characters. The name is set by
+ using the sPDUMasterConfigMSPName OID."
+ ::= { sPDUOutletControlMSPEntry 2 }
+
+sPDUOutletControlMSPOutletIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the outlet entry."
+ ::= { sPDUOutletControlMSPEntry 3 }
+
+sPDUOutletControlMSPOutletName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the outlet. The maximum size is
+ 23 characters. The name is set by using the
+ sPDUOutletConfigMSPallOutletName OID.
+ This OID is provided for informational purposes only."
+ ::= { sPDUOutletControlMSPEntry 4 }
+
+sPDUOutletControlMSPOutletCommand OBJECT-TYPE
+ SYNTAX INTEGER {
+ immediateOnMSP (1),
+ delayedOnMSP (2),
+ immediateOffMSP (3),
+ gracefulRebootMSP (4),
+ immediateRebootMSP (5),
+ gracefulshutdownMSP (6),
+ overrideBatCapThreshMSP (7),
+ cancelPendingCommandMSP (8)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this variable will return the outlet state. If
+ the outlet is on, the immediateOnMSP (1) value will be returned.
+ If the outlet is off, the immediateOffMSP (3) value will be
+ returned.
+
+ Setting this variable to immediateOnMSP (1) will immediately turn the outlet on.
+
+ Setting this variable to delayedOnMSP (2) will turn the outlet on
+ after the sPDUOutletConfigMSPPowerOnDelay OID time has elapsed.
+
+ Setting this variable to immediateOffMSP (3) will immediately turn the outlet off.
+
+ Setting this variable to gracefulRebootMSP (4) will cause the outlet to wait for
+ device confirmation (if applicable) and then turn the outlet off after the
+ sPDUOutletConfigMSPPowerOffDelay OID time has elapsed. The outlet will then turn
+ on after the sPDUOutletConfigMSPRebootDuration OID time has elapsed.
+
+ Setting this variable to immediateRebootMSP (5) will immediately reboot the outlet.
+
+ Setting this variable to gracefulshutdownMSP (6) will cause the outlet to wait for
+ device confirmation (if applicable) and then turn the outlet off after the
+ sPDUOutletConfigMSPPowerOffDelay OID time has elapsed. The outlet will then turn
+ on after the sum of the sPDUOutletConfigMSPRestartTime OID time and the
+ sPDUOutletConfigMSPPowerOnDelay OID time has elapsed.
+
+ Setting this variable to overrideBatCapThreshMSP (7) will cause the outlet to
+ ignore the Battery Capacity Threshold and proceed waiting on the
+ sPDUOutletConfigMSPPowerOnDelay OID time before turning the outlet on.
+
+ Setting this variable to cancelPendingCommandMSP (8) will cause any
+ pending command to this outlet to be canceled."
+ ::= { sPDUOutletControlMSPEntry 5 }
+
+-- the sPDUOutletConfigMSPall group
+
+sPDUOutletConfigMSPallTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF SPDUOutletConfigMSPallEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for configuration of individual outlets. The number of
+ entries is contained in the sPDUMasterStatusMSPOutletCount OID."
+ ::= { sPDUOutletConfigMSPall 1 }
+
+sPDUOutletConfigMSPallEntry OBJECT-TYPE
+ SYNTAX SPDUOutletConfigMSPallEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The outlets to configure."
+ INDEX { sPDUOutletConfigMSPallIndex, sPDUOutletConfigMSPallOutletIndex }
+ ::= { sPDUOutletConfigMSPallTable 1 }
+
+SPDUOutletConfigMSPallEntry ::=
+ SEQUENCE {
+ sPDUOutletConfigMSPallIndex INTEGER,
+ sPDUOutletConfigMSPallName DisplayString,
+ sPDUOutletConfigMSPallOutletIndex INTEGER,
+ sPDUOutletConfigMSPallOutletName DisplayString,
+ sPDUOutletConfigMSPallOutletCtrlMode INTEGER
+ }
+
+sPDUOutletConfigMSPallIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the MasterSwitch plus."
+ ::= { sPDUOutletConfigMSPallEntry 1 }
+
+sPDUOutletConfigMSPallName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the MasterSwitch plus. The maximum
+ value is 23 characters. The name is set by
+ using the sPDUMasterConfigMSPName OID."
+ ::= { sPDUOutletConfigMSPallEntry 2 }
+
+sPDUOutletConfigMSPallOutletIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the outlet entry."
+ ::= { sPDUOutletConfigMSPallEntry 3 }
+
+sPDUOutletConfigMSPallOutletName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the outlet. Maximum size is 23 characters."
+ ::= { sPDUOutletConfigMSPallEntry 4 }
+
+sPDUOutletConfigMSPallOutletCtrlMode OBJECT-TYPE
+ SYNTAX INTEGER {
+ modeGracefulShutdown (1),
+ modeAnnunciator (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to modeGracefulShutdown (1) will put this
+ outlet into the Graceful Shutdown control mode.
+
+ Setting this OID to modeAnnunciator (2) will put this outlet
+ into the Annunciator control mode."
+ ::= { sPDUOutletConfigMSPallEntry 5 }
+
+
+-- the sPDUOutConfigMSPgs group
+
+sPDUOutletConfigMSPgsTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF SPDUOutletConfigMSPgsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for configuration of individual outlets. The number of
+ entries is contained in the sPDUMasterStatusMSPOutletCount OID."
+ ::= { sPDUOutletConfigMSPgs 1 }
+
+sPDUOutletConfigMSPgsEntry OBJECT-TYPE
+ SYNTAX SPDUOutletConfigMSPgsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The outlets to configure."
+ INDEX { sPDUOutletConfigMSPgsIndex, sPDUOutletConfigMSPgsOutletIndex }
+ ::= { sPDUOutletConfigMSPgsTable 1 }
+
+SPDUOutletConfigMSPgsEntry ::=
+ SEQUENCE {
+ sPDUOutletConfigMSPgsIndex INTEGER,
+ sPDUOutletConfigMSPgsName DisplayString,
+ sPDUOutletConfigMSPgsOutletIndex INTEGER,
+ sPDUOutletConfigMSPgsOutletName DisplayString,
+ sPDUOutletConfigMSPgsOutletCtrlMode INTEGER,
+ sPDUOutletConfigMSPgsDeviceConfirm INTEGER,
+ sPDUOutletConfigMSPgsLowBattWarning INTEGER,
+ sPDUOutletConfigMSPgsLowBattMult INTEGER,
+ sPDUOutletConfigMSPgsRestartDelay INTEGER,
+ sPDUOutletConfigMSPgsPowerOnDelay INTEGER,
+ sPDUOutletConfigMSPgsPowerOffDelay INTEGER,
+ sPDUOutletConfigMSPgsBattCapThresh INTEGER,
+ sPDUOutletConfigMSPgsRebootDuration INTEGER
+ }
+
+sPDUOutletConfigMSPgsIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the MasterSwitch plus."
+ ::= { sPDUOutletConfigMSPgsEntry 1 }
+
+sPDUOutletConfigMSPgsName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the MasterSwitch plus. The maximum
+ value is 23 characters. The name is set by
+ using the sPDUMasterConfigMSPName OID."
+ ::= { sPDUOutletConfigMSPgsEntry 2 }
+
+sPDUOutletConfigMSPgsOutletIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the outlet entry."
+ ::= { sPDUOutletConfigMSPgsEntry 3 }
+
+sPDUOutletConfigMSPgsOutletName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the outlet. The maximum size is
+ 23 characters. The name is set by using the
+ sPDUOutletConfigMSPallOutletName OID.
+ This OID is provided for informational purposes only."
+ ::= { sPDUOutletConfigMSPgsEntry 4 }
+
+sPDUOutletConfigMSPgsOutletCtrlMode OBJECT-TYPE
+ SYNTAX INTEGER {
+ modeGracefulShutdown (1),
+ modeAnnunciator (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Control Mode of the outlet.
+ This OID is provided for informational purposes only."
+ ::= { sPDUOutletConfigMSPgsEntry 5 }
+
+sPDUOutletConfigMSPgsDeviceConfirm OBJECT-TYPE
+ SYNTAX INTEGER {
+ deviceConfirmNo (1),
+ deviceConfirmYes (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to deviceConfirmNo (1) cause the outlet to
+ NOT wait for device confirmation while performing graceful
+ operations.
+
+ Setting this OID to deviceConfirmYes (2) cause the outlet to
+ wait for device confirmation while performing graceful
+ operations."
+ ::= { sPDUOutletConfigMSPgsEntry 6 }
+
+sPDUOutletConfigMSPgsLowBattWarning OBJECT-TYPE
+ SYNTAX INTEGER (-2..9999)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ " The amount of delay, in 6 second intervals, between
+ when the UPS goes on battery and the power down sequence for
+ the outlet is initiated.
+
+ Allowed values are:
+
+ -2 - Never initiate the power down sequence on low battery warning.
+ -1 - Initiate power down sequence based on remaining runtime.
+ 1 - 9999 six second intervals (6 secs - 16hrs, 39 mins, 54 secs).
+ 0 indicates to immediately initiate power down sequence on low
+ battery warning."
+ ::= { sPDUOutletConfigMSPgsEntry 7 }
+
+sPDUOutletConfigMSPgsLowBattMult OBJECT-TYPE
+ SYNTAX INTEGER (1..7)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ " Only applicable if sPDUOutletConfigMSPgsLowBattWarning OID is
+ set to -1 (On Runtime Remaining).
+
+ Allows you to set the value to stagger the shutdown sequence of the outlets.
+ 1 provides the longest delay (the outlet to shutoff first), and 7 would
+ provide the shortest delay (the outlet to shut off last).
+
+ Allowed values are:
+ 1 - 7."
+ ::= { sPDUOutletConfigMSPgsEntry 8 }
+
+sPDUOutletConfigMSPgsRestartDelay OBJECT-TYPE
+ SYNTAX INTEGER (-1..9999)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ " The amount of delay, in 6 minute intervals, between
+ when the outlet is turned off and the outlet is turned back on
+ when performing a Graceful Shutdown.
+
+ Allowed values are:
+
+ -1 - Never turn outlet back on after a Graceful shutdown.
+ 0 - 9999 six minute intervals (0 - 999hrs, 54 mins)."
+ ::= { sPDUOutletConfigMSPgsEntry 9 }
+
+sPDUOutletConfigMSPgsPowerOnDelay OBJECT-TYPE
+ SYNTAX INTEGER (-1..9999)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ " The amount of delay, in seconds, between the UPS entering
+ normal (on-line) state and the outlet being powered on.
+
+ Allowed values are:
+
+ -1 - Remain Off when the UPS enters the on-line state.
+ 0 - 9999 seconds (0 - 2 hrs, 46 mins, 39 secs)."
+ ::= { sPDUOutletConfigMSPgsEntry 10 }
+
+
+sPDUOutletConfigMSPgsPowerOffDelay OBJECT-TYPE
+ SYNTAX INTEGER (0..9999)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ " The amount of delay, in seconds, between when the server
+ shuts down and the outlet is powered off.
+
+ Allowed values are:
+
+ 0 - 9999 seconds (0 - 2 hrs, 46 mins, 39 secs)."
+ ::= { sPDUOutletConfigMSPgsEntry 11 }
+
+sPDUOutletConfigMSPgsBattCapThresh OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ " The minimum battery capacity, as a percent (0-100%), required
+ of the UPS before an outlet will be allowed to power on.
+
+ Allowed values are:
+
+ 0 - 100 percent."
+ ::= { sPDUOutletConfigMSPgsEntry 12 }
+
+sPDUOutletConfigMSPgsRebootDuration OBJECT-TYPE
+ SYNTAX INTEGER (0..9999)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ " The amount of delay, in seconds, from outlet off until
+ outlet on during a reboot.
+
+ Allowed values are:
+
+ 0 - 9999 seconds (0 - 2 hrs, 46 mins, 39 secs)."
+ ::= { sPDUOutletConfigMSPgsEntry 13 }
+
+
+-- the sPDUOutConfigMSPannun group
+
+sPDUOutletConfigMSPannunTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF SPDUOutletConfigMSPannunEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for configuration of individual outlets. The number of
+ entries is contained in the sPDUMasterStatusMSPOutletCount OID."
+ ::= { sPDUOutletConfigMSPannun 1 }
+
+sPDUOutletConfigMSPannunEntry OBJECT-TYPE
+ SYNTAX SPDUOutletConfigMSPannunEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The outlets to configure."
+ INDEX { sPDUOutletConfigMSPannunIndex, sPDUOutletConfigMSPannunOutletIndex }
+ ::= { sPDUOutletConfigMSPannunTable 1 }
+
+SPDUOutletConfigMSPannunEntry ::=
+ SEQUENCE {
+ sPDUOutletConfigMSPannunIndex INTEGER,
+ sPDUOutletConfigMSPannunName DisplayString,
+ sPDUOutletConfigMSPannunOutletIndex INTEGER,
+ sPDUOutletConfigMSPannunOutletName DisplayString,
+ sPDUOutletConfigMSPannunOutletCtrlMode INTEGER,
+ sPDUOutletConfigMSPannunInitialState INTEGER,
+ sPDUOutletConfigMSPannunAlarmActionDly INTEGER
+ }
+
+sPDUOutletConfigMSPannunIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the MasterSwitch plus."
+ ::= { sPDUOutletConfigMSPannunEntry 1 }
+
+sPDUOutletConfigMSPannunName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the MasterSwitch plus. The maximum
+ value is 23 characters. The name is set by
+ using the sPDUMasterConfigMSPName OID."
+ ::= { sPDUOutletConfigMSPannunEntry 2 }
+
+sPDUOutletConfigMSPannunOutletIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the outlet entry."
+ ::= { sPDUOutletConfigMSPannunEntry 3 }
+
+sPDUOutletConfigMSPannunOutletName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the outlet. The maximum size is
+ 23 characters. The name is set by using the
+ sPDUOutletConfigMSPallOutletName OID.
+ This OID is provided for informational purposes only."
+ ::= { sPDUOutletConfigMSPannunEntry 4 }
+
+sPDUOutletConfigMSPannunOutletCtrlMode OBJECT-TYPE
+ SYNTAX INTEGER {
+ modeGracefulShutdown (1),
+ modeAnnunciator (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Control Mode of the outlet.
+ This OID is provided for informational purposes only."
+ ::= { sPDUOutletConfigMSPannunEntry 5 }
+
+sPDUOutletConfigMSPannunInitialState OBJECT-TYPE
+ SYNTAX INTEGER {
+ initialStateOff (1),
+ initialStateOn (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to initialStateOff (1) causes the outlet
+ to default to off when in the non-alarmed condition.
+
+ Setting this OID to initialStateOn (2) causes the outlet
+ to default to on when in the non-alarmed condition."
+ ::= { sPDUOutletConfigMSPannunEntry 6 }
+
+sPDUOutletConfigMSPannunAlarmActionDly OBJECT-TYPE
+ SYNTAX INTEGER (0..9999)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ " The amount of time, in seconds, that an enabled Measure-UPS
+ alarm must be asserted before an alarm condition is recognized.
+
+ Allowed values are:
+
+ 0 - 9999 seconds (0 - 2 hrs, 46 mins, 39 secs)."
+ ::= { sPDUOutletConfigMSPannunEntry 7 }
+
+
+-- the sPDUOutConfigMSPmups group
+
+sPDUOutletConfigMSPmupsTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF SPDUOutletConfigMSPmupsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for configuration of individual outlets. The number of
+ entries is contained in the sPDUMasterStatusMSPOutletCount OID."
+ ::= { sPDUOutletConfigMSPmups 1 }
+
+sPDUOutletConfigMSPmupsEntry OBJECT-TYPE
+ SYNTAX SPDUOutletConfigMSPmupsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The outlets to configure."
+ INDEX { sPDUOutletConfigMSPmupsIndex, sPDUOutletConfigMSPmupsOutletIndex }
+ ::= { sPDUOutletConfigMSPmupsTable 1 }
+
+SPDUOutletConfigMSPmupsEntry ::=
+ SEQUENCE {
+ sPDUOutletConfigMSPmupsIndex INTEGER,
+ sPDUOutletConfigMSPmupsName DisplayString,
+ sPDUOutletConfigMSPmupsOutletIndex INTEGER,
+ sPDUOutletConfigMSPmupsOutletName DisplayString,
+ sPDUOutletConfigMSPmupsZone1 INTEGER,
+ sPDUOutletConfigMSPmupsZone2 INTEGER,
+ sPDUOutletConfigMSPmupsZone3 INTEGER,
+ sPDUOutletConfigMSPmupsZone4 INTEGER,
+ sPDUOutletConfigMSPmupsP1LowHum INTEGER,
+ sPDUOutletConfigMSPmupsP1HiHum INTEGER,
+ sPDUOutletConfigMSPmupsP1LowTemp INTEGER,
+ sPDUOutletConfigMSPmupsP1HiTemp INTEGER,
+ sPDUOutletConfigMSPmupsP2LowHum INTEGER,
+ sPDUOutletConfigMSPmupsP2HiHum INTEGER,
+ sPDUOutletConfigMSPmupsP2LowTemp INTEGER,
+ sPDUOutletConfigMSPmupsP2HiTemp INTEGER
+ }
+
+sPDUOutletConfigMSPmupsIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the MasterSwitch plus."
+ ::= { sPDUOutletConfigMSPmupsEntry 1 }
+
+sPDUOutletConfigMSPmupsName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the MasterSwitch plus. The maximum
+ value is 23 characters. The name is set by
+ using the sPDUMasterConfigMSPName OID."
+ ::= { sPDUOutletConfigMSPmupsEntry 2 }
+
+sPDUOutletConfigMSPmupsOutletIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the outlet entry."
+ ::= { sPDUOutletConfigMSPmupsEntry 3 }
+
+sPDUOutletConfigMSPmupsOutletName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the outlet. The maximum size is
+ 23 characters. The name is set by using the
+ sPDUOutletConfigMSPallOutletName OID.
+ This OID is provided for informational purposes only."
+ ::= { sPDUOutletConfigMSPmupsEntry 4 }
+
+sPDUOutletConfigMSPmupsZone1 OBJECT-TYPE
+ SYNTAX INTEGER {
+ disableAlarm (1),
+ enableAlarm (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to disableAlarm (1) disables the
+ Zone 1 alarm for this outlet.
+
+ Setting this OID to enableAlarm (2) enables the
+ Zone 1 alarm for this outlet."
+ ::= { sPDUOutletConfigMSPmupsEntry 5 }
+
+sPDUOutletConfigMSPmupsZone2 OBJECT-TYPE
+ SYNTAX INTEGER {
+ disableAlarm (1),
+ enableAlarm (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to disableAlarm (1) disables the
+ Zone 2 alarm for this outlet.
+
+ Setting this OID to enableAlarm (2) enables the
+ Zone 2 alarm for this outlet."
+ ::= { sPDUOutletConfigMSPmupsEntry 6 }
+
+sPDUOutletConfigMSPmupsZone3 OBJECT-TYPE
+ SYNTAX INTEGER {
+ disableAlarm (1),
+ enableAlarm (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to disableAlarm (1) disables the
+ Zone 3 alarm for this outlet.
+
+ Setting this OID to enableAlarm (2) enables the
+ Zone 3 alarm for this outlet."
+ ::= { sPDUOutletConfigMSPmupsEntry 7 }
+
+sPDUOutletConfigMSPmupsZone4 OBJECT-TYPE
+ SYNTAX INTEGER {
+ disableAlarm (1),
+ enableAlarm (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to disableAlarm (1) disables the
+ Zone 4 alarm for this outlet.
+
+ Setting this OID to enableAlarm (2) enables the
+ Zone 4 alarm for this outlet."
+ ::= { sPDUOutletConfigMSPmupsEntry 8 }
+
+sPDUOutletConfigMSPmupsP1LowHum OBJECT-TYPE
+ SYNTAX INTEGER {
+ disableAlarm (1),
+ enableAlarm (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to disableAlarm (1) disables the
+ Probe 1 low humidity alarm for this outlet.
+
+ Setting this OID to enableAlarm (2) enables the
+ Probe 1 low humidity alarm for this outlet."
+ ::= { sPDUOutletConfigMSPmupsEntry 9 }
+
+sPDUOutletConfigMSPmupsP1HiHum OBJECT-TYPE
+ SYNTAX INTEGER {
+ disableAlarm (1),
+ enableAlarm (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to disableAlarm (1) disables the
+ Probe 1 high humidity alarm for this outlet.
+
+ Setting this OID to enableAlarm (2) enables the
+ Probe 1 high humidity alarm for this outlet."
+ ::= { sPDUOutletConfigMSPmupsEntry 10 }
+
+sPDUOutletConfigMSPmupsP1LowTemp OBJECT-TYPE
+ SYNTAX INTEGER {
+ disableAlarm (1),
+ enableAlarm (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to disableAlarm (1) disables the
+ Probe 1 low temperature alarm for this outlet.
+
+ Setting this OID to enableAlarm (2) enables the
+ Probe 1 low temperature alarm for this outlet."
+ ::= { sPDUOutletConfigMSPmupsEntry 11 }
+
+sPDUOutletConfigMSPmupsP1HiTemp OBJECT-TYPE
+ SYNTAX INTEGER {
+ disableAlarm (1),
+ enableAlarm (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to disableAlarm (1) disables the
+ Probe 1 high temperature alarm for this outlet.
+
+ Setting this OID to enableAlarm (2) enables the
+ Probe 1 high temperature alarm for this outlet."
+ ::= { sPDUOutletConfigMSPmupsEntry 12 }
+
+sPDUOutletConfigMSPmupsP2LowHum OBJECT-TYPE
+ SYNTAX INTEGER {
+ disableAlarm (1),
+ enableAlarm (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to disableAlarm (1) disables the
+ Probe 2 low humidity alarm for this outlet.
+
+ Setting this OID to enableAlarm (2) enables the
+ Probe 2 low humidity alarm for this outlet."
+ ::= { sPDUOutletConfigMSPmupsEntry 13 }
+
+sPDUOutletConfigMSPmupsP2HiHum OBJECT-TYPE
+ SYNTAX INTEGER {
+ disableAlarm (1),
+ enableAlarm (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to disableAlarm (1) disables the
+ Probe 2 high humidity alarm for this outlet.
+
+ Setting this OID to enableAlarm (2) enables the
+ Probe 2 high humidity alarm for this outlet."
+ ::= { sPDUOutletConfigMSPmupsEntry 14 }
+
+sPDUOutletConfigMSPmupsP2LowTemp OBJECT-TYPE
+ SYNTAX INTEGER {
+ disableAlarm (1),
+ enableAlarm (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to disableAlarm (1) disables the
+ Probe 2 low temperature alarm for this outlet.
+
+ Setting this OID to enableAlarm (2) enables the
+ Probe 2 low temperature alarm for this outlet."
+ ::= { sPDUOutletConfigMSPmupsEntry 15 }
+
+sPDUOutletConfigMSPmupsP2HiTemp OBJECT-TYPE
+ SYNTAX INTEGER {
+ disableAlarm (1),
+ enableAlarm (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to disableAlarm (1) disables the
+ Probe 2 high temperature alarm for this outlet.
+
+ Setting this OID to enableAlarm (2) enables the
+ Probe 2 high temperature alarm for this outlet."
+ ::= { sPDUOutletConfigMSPmupsEntry 16 }
+
+-- the sPDUOutletStatusMSP group
+
+sPDUOutletStatusMSPTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF SPDUOutletStatusMSPEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting of status of individual outlets. The number of
+ entries is contained in the sPDUMasterStatusOutletCount OID."
+ ::= { sPDUOutletStatusMSP 1 }
+
+sPDUOutletStatusMSPEntry OBJECT-TYPE
+ SYNTAX SPDUOutletStatusMSPEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The outlets to gather status from."
+ INDEX { sPDUOutletStatusMSPIndex, sPDUOutletStatusMSPOutletIndex }
+ ::= { sPDUOutletStatusMSPTable 1 }
+
+SPDUOutletStatusMSPEntry ::=
+ SEQUENCE {
+ sPDUOutletStatusMSPIndex INTEGER,
+ sPDUOutletStatusMSPName DisplayString,
+ sPDUOutletStatusMSPOutletIndex INTEGER,
+ sPDUOutletStatusMSPOutletName DisplayString,
+ sPDUOutletStatusMSPOutletState INTEGER,
+ sPDUOutletStatusMSPCommandPending INTEGER,
+ sPDUOutletStatusMSPOutletCtrlMode INTEGER
+ }
+
+sPDUOutletStatusMSPIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the MasterSwitch MSP."
+ ::= { sPDUOutletStatusMSPEntry 1 }
+
+sPDUOutletStatusMSPName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the MasterSwitch plus. The maximum
+ value is 23 characters. The name is set by
+ using the sPDUMasterConfigMSPName OID."
+ ::= { sPDUOutletStatusMSPEntry 2 }
+
+sPDUOutletStatusMSPOutletIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the outlet entry."
+ ::= { sPDUOutletStatusMSPEntry 3 }
+
+sPDUOutletStatusMSPOutletName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the outlet. The maximum size is
+ 23 characters. The name is set by using the
+ sPDUOutletConfigMSPallOutletName OID.
+ This OID is provided for informational purposes only."
+ ::= { sPDUOutletStatusMSPEntry 4 }
+
+sPDUOutletStatusMSPOutletState OBJECT-TYPE
+ SYNTAX INTEGER {
+ outletStatusMSPOn (1),
+ outletStatusMSPOff (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this variable will return the outlet state. If
+ the outlet is on, the outletStatusMSPOn (1) value will be returned.
+ If the outlet is off, the outletStatusMSPOff (2) value will be
+ returned. "
+ ::= { sPDUOutletStatusMSPEntry 5 }
+
+sPDUOutletStatusMSPCommandPending OBJECT-TYPE
+ SYNTAX INTEGER {
+ outletStatusMSPCommandPending (1),
+ outletStatusMSPNoCommandPending (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this variable will return the command pending
+ state of the outlet. If a command is pending on the
+ outlet, the outletStatusMSPCommandPending (1) value
+ will be returned. If there is not a command pending
+ on the outlet, the outletStatusMSPNoCommandPending (2)
+ will be returned."
+ ::= { sPDUOutletStatusMSPEntry 6 }
+
+sPDUOutletStatusMSPOutletCtrlMode OBJECT-TYPE
+ SYNTAX INTEGER {
+ modeGracefulShutdown (1),
+ modeAnnunciator (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Control Mode of the outlet.
+ This OID is provided for informational purposes only."
+ ::= { sPDUOutletStatusMSPEntry 7 }
+
+
+-- the rPDUIdent group
+
+rPDUIdentName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the Rack PDU.
+ The maximum string size is device dependent."
+ ::= { rPDUIdent 1 }
+
+rPDUIdentHardwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The hardware revision of the Rack PDU.
+ This value is set at the factory."
+ ::= { rPDUIdent 2 }
+
+rPDUIdentFirmwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An 8-byte ID string identifying the Rack PDU firmware revision.
+ This value is set at the factory."
+ ::= { rPDUIdent 3 }
+
+
+rPDUIdentDateOfManufacture OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The date when the Rack PDU was manufactured in mm/dd/yyyy format.
+ This value is set at the factory. The year 2000 will be
+ represented by 00."
+ ::= { rPDUIdent 4 }
+
+rPDUIdentModelNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A 10-character string identifying the model number of
+ the Rack PDU. This value is set at the factory."
+ ::= { rPDUIdent 5 }
+
+rPDUIdentSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A 12-character string identifying the serial number of
+ the Rack PDU. This value is set at the factory."
+ ::= { rPDUIdent 6 }
+
+rPDUIdentDeviceRating OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return the electrical rating of the device in Amps."
+
+ ::= { rPDUIdent 7 }
+
+rPDUIdentDeviceNumOutlets OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return the number of outlets contained in the device."
+
+ ::= { rPDUIdent 8 }
+
+rPDUIdentDeviceNumPhases OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return the number of phases supported by the device."
+
+ ::= { rPDUIdent 9 }
+
+rPDUIdentDeviceNumBreakers OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return the number of circuit breakers supported by the device.
+ This is the same as the number of banks of outlets.
+ 0 will be returned if the unit has no phase breakers. "
+
+ ::= { rPDUIdent 10 }
+
+rPDUIdentDeviceBreakerRating OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return rating of the circuit breakers
+ on the device in Amps if it has any."
+
+ ::= { rPDUIdent 11 }
+
+rPDUIdentDeviceOrientation OBJECT-TYPE
+ SYNTAX INTEGER {
+ orientHorizontal (1),
+ orientVertical (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return the intended physical orientation of the device.
+
+ OrientHorizonatal(1) indicates Horizontal.
+ OrientVertical(2) indicates Vertical."
+
+ ::= { rPDUIdent 12 }
+
+rPDUIdentDeviceOutletLayout OBJECT-TYPE
+ SYNTAX INTEGER {
+ seqPhaseToNeutral (1),
+ seqPhaseToPhase (2),
+ seqPhToNeu21PhToPh (3),
+ seqPhToPhGrouped (4),
+ seqPhToNGrouped (5),
+ seqPToN1516PToPGrouped (6),
+ seqPhToPh2xGrouped (7),
+ seqPhToN2xGrouped (8),
+ seqNotApplicable (9)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return outlet layout for the device.
+
+ seqPhaseToNeutral(1) indicates outlet layout as follows:
+ 1:1-N,2:2-N,3:3-N,4:1-N,5:2-N,...
+
+ seqPhaseToPhase(2) indicates outlet layout as follows:
+ 1:1-2,2:2-3,3:3-1,4:1-2,5:2-3,...
+
+ seqPhToNeu21PhToPh(3) indicates outlet layout as follows:
+ 1:1-N,2:2-N...21:3-N,22:1-2,23:2-3,24:3-1,...
+
+ seqPhToPhGrouped(4) indicates outlet layout as follows:
+ For AP8xxx SKU's Group 1:1-2, Group 2:2-3, Group 3:3-1.
+ For AP7xxx SKU's Group 1:3-1. Group 2:2-3, Group 3:1-2.
+
+ seqPhToNGrouped(5) indicates outlet layout as follows:
+ This unit has 3 outlet groups. Group 1:1-N, Group 2:2-N, Group 3:3-N.
+
+ seqPToN1516PToPGrouped(6) indicates outlet layout as follows:
+ This unit has 4 outlet groups. Group 1 (Outlets 1-14):1-2,
+ Group 2 (Outlets 15-16):1-N, Group 3:2-3, Group 4:3-1.
+
+ seqPhToPh2xGrouped(7) indicates outlet layout as follows:
+ This unit has 6 outlet groups. Group 1:1-2, Group 2:1-2, Group 3:2-3,
+ Group 4:2-3, Group 5:3-1, Group 6:3-1.
+
+ seqPhToN2xGrouped(8) indicates outlet layout as follows:
+ This unit has 6 outlet groups. Group 1:1-N, Group 2:1-N, Group 3:2-N,
+ Group 4:2-N, Group 5:3-N, Group 6:3-N.
+
+ seqNotApplicable(9):
+ Outlet layout does not affect any of the user interfaces.
+ These SKUs may report seqNotApplicable(9) if there is
+ not an exact outlet layout match available."
+
+ ::= { rPDUIdent 13 }
+
+rPDUIdentDeviceDisplayOrientation OBJECT-TYPE
+ SYNTAX INTEGER {
+ displayNormal (1),
+ displayReverse (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return the intended physical orientation of the Seven-Segment Display.
+
+ Normal(1) indicates Normal.
+ Reverse(2)indicates Upside-Down."
+ ::= { rPDUIdent 14 }
+
+
+rPDUIdentDeviceLinetoLineVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Getting/Setting this OID will return/set the Line to Line Voltage.
+ This OID defaults to the nominal input line voltage in volts AC.
+ This setting is used to calculate total power and must be configured for best accuracy.
+ This OID does not apply to AP86XX, AP88XX, or AP89XX SKUs.
+
+ The valid range is between 0V to 440V"
+ ::= { rPDUIdent 15 }
+
+rPDUIdentDevicePowerWatts OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return the Power in Watts."
+
+ ::= { rPDUIdent 16 }
+
+rPDUIdentDevicePowerFactor OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Getting/setting this OID will return/set the
+ Power Factor in thousandths (1000 is power factor of 1).
+ For AP8XXX SKUs, this OID is read-only
+
+ Valid range is from 0 to 1000."
+ ::= { rPDUIdent 17 }
+
+rPDUIdentDevicePowerVA OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return the Power in VA."
+
+ ::= { rPDUIdent 18 }
+
+rPDUIdentDeviceLinetoNeutralVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Getting/Setting this OID will return/set the Line to Neutral Voltage.
+ This OID defaults to the nominal line to neutral voltage in volts AC.
+ This setting is used to calculate total power and must be configured for best accuracy.
+ This OID applies only to AP7823. For all other models, the OID is fixed at 0.
+
+ The valid range is between 0V to 440V."
+
+ ::= { rPDUIdent 19 }
+
+-- the rPDULoadDevice group
+
+rPDULoadDevMaxPhaseLoad OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return the maximum rated power
+ that each phase of the Rack PDU can provide. It is
+ represented in Amps.
+
+ 0 will be returned if the unit is banked."
+ ::= { rPDULoadDevice 1 }
+
+rPDULoadDevNumPhases OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of phases available with this Rack PDU."
+ ::= { rPDULoadDevice 2 }
+
+rPDULoadDevMaxBankLoad OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return the maximum rated power
+ that a bank of the Rack PDU can provide. It is
+ represented in Amps.
+
+ 0 will be returned if the device does not have any banks."
+
+ ::= { rPDULoadDevice 3 }
+
+rPDULoadDevNumBanks OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of banks of outlets available with this Rack PDU.
+ A bank of outlets has a unique circuit breaker for a subset
+ of the total number of outlets on the rPDU.
+
+ 0 will be returned if the unit has no banks."
+ ::= { rPDULoadDevice 4 }
+
+rPDULoadDevBankTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The size of the Bank Table."
+ ::= { rPDULoadDevice 5 }
+
+
+rPDULoadDevBankTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RPDULoadDevBankEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting the Bank Max Load in the Rack PDU."
+
+ ::= { rPDULoadDevice 6 }
+
+rPDULoadDevBankEntry OBJECT-TYPE
+ SYNTAX RPDULoadDevBankEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The Rack PDU Banks Access."
+ INDEX { rPDULoadDevBankIndex}
+ ::= { rPDULoadDevBankTable 1 }
+
+RPDULoadDevBankEntry ::=
+ SEQUENCE {
+ rPDULoadDevBankIndex INTEGER,
+ rPDULoadDevBankNumber INTEGER,
+ rPDULoadDevBankMaxLoad INTEGER
+ }
+
+rPDULoadDevBankIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the Rack PDU bank entry."
+ ::= { rPDULoadDevBankEntry 1 }
+
+rPDULoadDevBankNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return the bank number."
+
+ ::= { rPDULoadDevBankEntry 2 }
+
+rPDULoadDevBankMaxLoad OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return the maximum rated power
+ that each bank of the Rack PDU can provide. It is
+ represented in Amps."
+
+ ::= { rPDULoadDevBankEntry 3 }
+
+rPDULoadDevMaxOutletTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The size of the Outlet Table."
+ ::= { rPDULoadDevice 7 }
+
+
+rPDULoadDevMaxOutletTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RPDULoadDevMaxOutletEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting the Max Outlet Load in an Outlet Monitored Rack PDU."
+ ::= { rPDULoadDevice 8 }
+
+rPDULoadDevMaxOutletEntry OBJECT-TYPE
+ SYNTAX RPDULoadDevMaxOutletEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "This gives access to Max Outlet Load of an Outlet Monitored Rack PDU"
+ INDEX { rPDULoadDevOutletIndex}
+ ::= { rPDULoadDevMaxOutletTable 1 }
+
+RPDULoadDevMaxOutletEntry ::=
+ SEQUENCE {
+ rPDULoadDevOutletIndex INTEGER,
+ rPDULoadDevOutletNumber INTEGER,
+ rPDULoadDevMaxOutletLoad INTEGER
+ }
+
+rPDULoadDevOutletIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the Outlet Monitored Rack PDU Max Outlet Load entry."
+ ::= { rPDULoadDevMaxOutletEntry 1 }
+
+rPDULoadDevOutletNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return the Outlet number."
+ ::= { rPDULoadDevMaxOutletEntry 2 }
+
+
+rPDULoadDevMaxOutletLoad OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return the maximum rated power
+ that each Outlet of an Outlet Monitored Rack PDU can provide. It is
+ represented in Amps. "
+ ::= { rPDULoadDevMaxOutletEntry 3 }
+
+
+
+-- the rPDULoadPhaseConfig group
+
+rPDULoadPhaseConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RPDULoadPhaseConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for configuration of each Rack PDU phase.
+ The number of entries is contained in the
+ rPDULoadDevNumPhases OID."
+ ::= { rPDULoadPhaseConfig 1 }
+
+rPDULoadPhaseConfigEntry OBJECT-TYPE
+ SYNTAX RPDULoadPhaseConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The Rack PDU phase to configure."
+ INDEX { rPDULoadPhaseConfigIndex}
+ ::= { rPDULoadPhaseConfigTable 1 }
+
+RPDULoadPhaseConfigEntry ::=
+ SEQUENCE {
+ rPDULoadPhaseConfigIndex INTEGER,
+ rPDULoadPhaseConfigLowLoadThreshold INTEGER,
+ rPDULoadPhaseConfigNearOverloadThreshold INTEGER,
+ rPDULoadPhaseConfigOverloadThreshold INTEGER,
+ rPDULoadPhaseConfigAlarm INTEGER
+ }
+
+rPDULoadPhaseConfigIndex OBJECT-TYPE
+ SYNTAX INTEGER {
+ phase1 (1),
+ phase2 (2),
+ phase3 (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the Rack PDU phase entry."
+ ::= { rPDULoadPhaseConfigEntry 1 }
+
+rPDULoadPhaseConfigLowLoadThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A threshold that indicates the power consumption of
+ the load is nearing a low consumption condition. It is
+ represented in Amps. A warning will be issued when the
+ load is less than the threshold value.
+
+ A threshold value of 0 Amps effectively disables this
+ warning.
+
+ Maximum value must be less than the value returned
+ by the rPDULoadPhaseConfigNearOverloadThreshold OID."
+ ::= { rPDULoadPhaseConfigEntry 2 }
+
+rPDULoadPhaseConfigNearOverloadThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A threshold that indicates the power consumption of
+ the load is nearing an overload condition. It is
+ represented in Amps. A warning will be issued when the
+ load is greater than or equal to the threshold value.
+
+ Minimum value must be greater than the value returned by
+ the rPDULoadPhaseConfigLowLoadThreshold OID.
+
+ Maximum value must be less than or equal to the value
+ returned by the rPDULoadPhaseConfigOverloadThreshold OID."
+ ::= { rPDULoadPhaseConfigEntry 3 }
+
+rPDULoadPhaseConfigOverloadThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A threshold that indicates the power consumption of
+ the load has entered an overload condition. It is
+ represented in Amps. A warning will be issued when the
+ load is greater than or equal to the threshold value.
+
+ Minimum value must be greater than or equal to the value
+ returned by the rPDULoadPhaseConfigNearOverloadThreshold OID.
+
+ Maximum value must be less than or equal to the value
+ returned by the rPDULoadDevMaxPhaseLoad OID."
+ ::= { rPDULoadPhaseConfigEntry 4 }
+
+
+rPDULoadPhaseConfigAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ noLoadAlarm (1),
+ underCurrentAlarm (2),
+ nearOverCurrentAlarm (3),
+ overCurrentAlarm (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return the current Phase Alarm."
+ ::= { rPDULoadPhaseConfigEntry 5 }
+
+
+
+
+
+-- the rPDULoadStatus group
+
+rPDULoadStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RPDULoadStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting of status of each Rack PDU phase/bank.
+ The number of entries is calculated by adding
+ the number of phases (rPDULoadDevNumPhases OID) and
+ the number of banks of outlets (rPDULoadDevNumBanks)
+ Number of entries = #phases + #banks.
+ NOTE: If a device has phase and bank information, all phase information
+ shall precede the bank information. If a device has total information,
+ it shall precede both the bank and the phase information."
+ ::= { rPDULoadStatus 1 }
+
+rPDULoadStatusEntry OBJECT-TYPE
+ SYNTAX RPDULoadStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The Rack PDU phase/bank to gather status from."
+ INDEX { rPDULoadStatusIndex}
+ ::= { rPDULoadStatusTable 1 }
+
+RPDULoadStatusEntry ::=
+ SEQUENCE {
+ rPDULoadStatusIndex INTEGER,
+ rPDULoadStatusLoad Gauge,
+ rPDULoadStatusLoadState INTEGER,
+ rPDULoadStatusPhaseNumber INTEGER,
+ rPDULoadStatusBankNumber INTEGER
+ }
+
+rPDULoadStatusIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the Rack PDU phase/bank entry. All phase information will precede
+ any bank information"
+ ::= { rPDULoadStatusEntry 1 }
+
+rPDULoadStatusLoad OBJECT-TYPE
+ SYNTAX Gauge
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return the phase/bank load measured
+ in tenths of Amps."
+ ::= { rPDULoadStatusEntry 2 }
+
+rPDULoadStatusLoadState OBJECT-TYPE
+ SYNTAX INTEGER {
+ phaseLoadNormal (1),
+ phaseLoadLow (2),
+ phaseLoadNearOverload (3),
+ phaseLoadOverload (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return the phase/bank load state.
+
+ phaseLoadNormal(1) indicates that the phase/bank is
+ operating properly within the rPDULoadConfigLowLoadThreshold
+ and rPDULoadConfigNearOverloadThreshold OID values.
+
+ phaseLoadLow(2) indicates that the phase/bank load has
+ dropped below the rPDULoadConfigLowLoadThreshold OID value.
+ An SNMP trap will occur when this state is entered or cleared.
+
+ phaseLoadNearOverload(3) indicates that the phase/bank load
+ is greater than or equal to the
+ rPDULoadConfigNearOverloadThreshold OID value.
+ An SNMP trap will occur when this state is entered or cleared.
+
+ phaseLoadOverload(4) indicates that the phase/bank load is
+ greater than or equal to the rPDULoadConfigOverloadThreshold
+ OID value.
+ An SNMP trap will occur when this state is entered or cleared."
+ ::= { rPDULoadStatusEntry 3 }
+
+rPDULoadStatusPhaseNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The phase number to which this record refers."
+ ::= { rPDULoadStatusEntry 4 }
+
+rPDULoadStatusBankNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The bank number to which this record refers. A value of 0 will be returned if
+ any bank is not present or if it is phase related."
+ ::= { rPDULoadStatusEntry 5 }
+
+
+-- the rPDULoadBankConfig group
+
+rPDULoadBankConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RPDULoadBankConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for configuration of each Rack PDU bank.
+ The number of entries is contained in the
+ rPDULoadDevNumBanks OID."
+ ::= { rPDULoadBankConfig 1 }
+
+rPDULoadBankConfigEntry OBJECT-TYPE
+ SYNTAX RPDULoadBankConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The Rack PDU bank to configure."
+ INDEX { rPDULoadBankConfigIndex}
+ ::= { rPDULoadBankConfigTable 1 }
+
+RPDULoadBankConfigEntry ::=
+ SEQUENCE {
+ rPDULoadBankConfigIndex INTEGER,
+ rPDULoadBankConfigLowLoadThreshold INTEGER,
+ rPDULoadBankConfigNearOverloadThreshold INTEGER,
+ rPDULoadBankConfigOverloadThreshold INTEGER,
+ rPDULoadBankConfigAlarm INTEGER
+ }
+
+rPDULoadBankConfigIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the Rack PDU bank entry."
+ ::= { rPDULoadBankConfigEntry 1 }
+
+rPDULoadBankConfigLowLoadThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A threshold that indicates the power consumption of
+ the load is nearing a low consumption condition. It is
+ represented in Amps. A warning will be issued when the
+ load is less than the threshold value.
+
+ A threshold value of 0 Amps effectively disables this
+ warning.
+
+ Maximum value must be less than the value returned
+ by the rPDULoadBankConfigNearOverloadThreshold OID."
+
+ ::= { rPDULoadBankConfigEntry 2 }
+
+rPDULoadBankConfigNearOverloadThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A threshold that indicates the power consumption of
+ the load is nearing an overload condition. It is
+ represented in Amps. A warning will be issued when the
+ load is greater than or equal to the threshold value.
+
+ Minimum value must be greater than the value returned by
+ the rPDULoadBankConfigLowLoadThreshold OID.
+
+ Maximum value must be less than or equal to the value
+ returned by the rPDULoadBankConfigOverloadThreshold OID."
+
+ ::= { rPDULoadBankConfigEntry 3 }
+
+rPDULoadBankConfigOverloadThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A threshold that indicates the power consumption of
+ the load has entered an overload condition. It is
+ represented in Amps. A warning will be issued when the
+ load is greater than or equal to the threshold value.
+
+ Minimum value must be greater than or equal to the value
+ returned by the rPDULoadBankConfigNearOverloadThreshold OID.
+
+ Maximum value must be less than or equal to the value
+ returned by the rPDULoadDevMaxBankLoad OID."
+
+ ::= { rPDULoadBankConfigEntry 4 }
+
+rPDULoadBankConfigAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ noLoadAlarm (1),
+ underCurrentAlarm (2),
+ nearOverCurrentAlarm (3),
+ overCurrentAlarm (4)
+
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ " Getting this OID will return the current Bank Alarm."
+ ::= { rPDULoadBankConfigEntry 5 }
+
+
+-- the rPDUOutletDevice group
+
+rPDUOutletDevCommand OBJECT-TYPE
+ SYNTAX INTEGER {
+ noCommandAll (1),
+ immediateAllOn (2),
+ immediateAllOff (3),
+ immediateAllReboot (4),
+ delayedAllOn (5),
+ delayedAllOff (6),
+ delayedAllReboot (7),
+ cancelAllPendingCommands (8)
+ }
+
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to immediateAllOn (2) will turn all outlets
+ on immediately.
+
+ Setting this OID to immediateAllOff (3) will turn all outlets
+ off immediately.
+
+ Setting this OID to immediateAllReboot (4) will reboot all outlets
+ immediately.
+
+ Setting this OID to delayedAllOn (5) will turn all outlets on as
+ defined by each outlet's rPDUOutletConfigPowerOnTime OID value.
+
+ Setting this OID to delayedAllOff (6) will turn all outlets
+ off as defined by each outlet's rPDUOutletConfigPowerOffTime OID value.
+
+ Setting this OID to delayedAllReboot (7) will cause a
+ delayedAllOff command to be performed. Once all outlets are off,
+ the Switched Rack PDU will then delay the largest
+ rPDUOutletConfigRebootDuration OID time, and then perform a
+ delayedAllOn command.
+
+ Setting this OID to cancelAllPendingCommands (8) will cause all pending
+ commands on the Switched Rack PDU to be canceled.
+
+ Getting this OID will return the noCommandAll (1) value."
+ ::= { rPDUOutletDevice 1 }
+
+rPDUOutletDevColdstartDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The amount of delay, in seconds, between when
+ power is provided to the Switched Rack PDU and
+ when the Switched Rack PDU provides basic master
+ power to the outlets.
+
+ Allowed values are:
+
+ -1 - never apply power automatically.
+ 0 - apply power immediately.
+ 1 to 300 - delay up to 300 seconds (5 minutes)."
+ ::= { rPDUOutletDevice 2 }
+
+rPDUOutletDevNumCntrlOutlets OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of controlled outlets on this Switched Rack PDU."
+ ::= { rPDUOutletDevice 3 }
+
+rPDUOutletDevNumTotalOutlets OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The total number of outlets on this Rack PDU."
+ ::= { rPDUOutletDevice 4 }
+
+rPDUOutletDevMonitoredOutlets OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The total number of monitored outlets on this Rack PDU."
+ ::= { rPDUOutletDevice 5 }
+
+
+-- the rPDUOutletPhase group
+
+rPDUOutletPhaseTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RPDUOutletPhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for management of outlets on a per phase basis."
+ ::= { rPDUOutletPhase 1 }
+
+rPDUOutletPhaseEntry OBJECT-TYPE
+ SYNTAX RPDUOutletPhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The phase to manage."
+ INDEX { rPDUOutletPhaseIndex}
+ ::= { rPDUOutletPhaseTable 1 }
+
+RPDUOutletPhaseEntry ::=
+ SEQUENCE {
+ rPDUOutletPhaseIndex INTEGER,
+ rPDUOutletPhaseOverloadRestriction INTEGER
+ }
+
+rPDUOutletPhaseIndex OBJECT-TYPE
+ SYNTAX INTEGER {
+ phase1 (1),
+ phase2 (2),
+ phase3 (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the Switched Rack PDU phase entry."
+ ::= { rPDUOutletPhaseEntry 1 }
+
+rPDUOutletPhaseOverloadRestriction OBJECT-TYPE
+ SYNTAX INTEGER {
+ alwaysAllowTurnON (1),
+ restrictOnNearOverload (2),
+ restrictOnOverload (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "This OID controls the behavior of a Switched Rack PDU
+ phase when an overload condition is possible and
+ additional outlets are requested to be turned on.
+
+ Setting this OID to alwaysAllowTurnON (1) will always allow
+ the outlets on the corresponding phase to turn on.
+
+ Setting this OID to restrictOnNearOverload (2) will not allow
+ outlets on the corresponding phase to turn on if the
+ rPDULoadConfigNearOverloadThreshold OID is exceeded.
+
+ Setting this OID to restrictOnOverload (3) will not allow
+ outlets on the corresponding phase to turn on if the
+ rPDULoadConfigOverloadThreshold OID is exceeded."
+ ::= { rPDUOutletPhaseEntry 2 }
+
+
+-- the rPDUOutletControl group
+
+rPDUOutletControlTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RPDUOutletControlEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for control of the individual outlets.
+ The number of entries is contained in the
+ rPDUOutletDevNumCntrlOutlets OID."
+ ::= { rPDUOutletControl 1 }
+
+rPDUOutletControlEntry OBJECT-TYPE
+ SYNTAX RPDUOutletControlEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The outlet to control."
+ INDEX { rPDUOutletControlIndex}
+ ::= { rPDUOutletControlTable 1 }
+
+RPDUOutletControlEntry ::=
+ SEQUENCE {
+ rPDUOutletControlIndex INTEGER,
+ rPDUOutletControlOutletName DisplayString,
+ rPDUOutletControlOutletPhase INTEGER,
+ rPDUOutletControlOutletCommand INTEGER,
+ rPDUOutletControlOutletBank INTEGER
+ }
+
+rPDUOutletControlIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the outlet entry."
+ ::= { rPDUOutletControlEntry 1 }
+
+rPDUOutletControlOutletName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the outlet. The maximum string size is device dependent.
+ An error will be returned if the set request exceeds the max size.
+ This OID is provided for informational purposes only."
+ ::= { rPDUOutletControlEntry 2 }
+
+rPDUOutletControlOutletPhase OBJECT-TYPE
+ SYNTAX INTEGER {
+ phase1 (1),
+ phase2 (2),
+ phase3 (3),
+ phase1-2 (4),
+ phase2-3 (5),
+ phase3-1 (6)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The phase/s associated with this outlet.
+
+ For single phase devices, this object will always
+ return phase1(1).
+
+ For 3-phase devices, this object will return phase1 (1),
+ phase2 (2), or phase3 (3) for outlets tied to a single
+ phase. For outlets tied to two phases, this object will
+ return phase1-2 (4) for phases 1 and 2, phase2-3 (5) for
+ phases 2 and 3, and phase3-1 (6) for phases 3 and 1."
+ ::= { rPDUOutletControlEntry 3 }
+
+rPDUOutletControlOutletCommand OBJECT-TYPE
+ SYNTAX INTEGER {
+ immediateOn (1),
+ immediateOff (2),
+ immediateReboot (3),
+ delayedOn (4),
+ delayedOff (5),
+ delayedReboot (6),
+ cancelPendingCommand (7)
+ }
+
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this variable will return the outlet state. If
+ the outlet is on, the immediateOn (1) value will be returned.
+ If the outlet is off, the immediateOff (2) value will be
+ returned.
+
+
+ Setting this variable to immediateOn (1) will immediately turn
+ the outlet on.
+
+ Setting this variable to immediateOff (2) will immediately turn
+ the outlet off.
+
+ Setting this variable to immediateReboot (3) will immediately
+ reboot the outlet.
+
+ Setting this variable to delayedOn (4) will turn the outlet on
+ after the rPDUOutletConfigPowerOnTime OID time has elapsed.
+
+ Setting this variable to delayedOff (5) will turn the outlet off
+ after the rPDUOutletConfigPowerOffTime OID time has elapsed.
+
+ Setting this variable to delayedReboot (6) will cause the
+ Switched Rack PDU to perform a delayedOff command, wait the
+ rPDUOutletConfigRebootDuration OID time, and then perform a
+ delayedOn command.
+
+ Setting this variable to cancelPendingCommand (7) will cause any
+ pending command to this outlet to be canceled."
+
+ ::= { rPDUOutletControlEntry 4 }
+
+rPDUOutletControlOutletBank OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The bank associated with this outlet."
+ ::= { rPDUOutletControlEntry 5 }
+
+
+-- the rPDUOutletConfig group
+
+rPDUOutletConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RPDUOutletConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for configuration of individual outlets. The number of
+ entries is contained in the rPDUOutletDevNumCntrlOutlets OID."
+ ::= { rPDUOutletConfig 1 }
+
+rPDUOutletConfigEntry OBJECT-TYPE
+ SYNTAX RPDUOutletConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The outlet to configure."
+ INDEX { rPDUOutletConfigIndex}
+ ::= { rPDUOutletConfigTable 1 }
+
+RPDUOutletConfigEntry ::=
+ SEQUENCE {
+ rPDUOutletConfigIndex INTEGER,
+ rPDUOutletConfigOutletName DisplayString,
+ rPDUOutletConfigOutletPhase INTEGER,
+ rPDUOutletConfigPowerOnTime INTEGER,
+ rPDUOutletConfigPowerOffTime INTEGER,
+ rPDUOutletConfigRebootDuration INTEGER,
+ rPDUOutletConfigOutletBank INTEGER
+ }
+
+rPDUOutletConfigIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the outlet entry."
+ ::= { rPDUOutletConfigEntry 1 }
+
+rPDUOutletConfigOutletName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the outlet. The maximum string size is device dependent.
+ An error will be returned if the set request exceeds the max size."
+ ::= { rPDUOutletConfigEntry 2 }
+
+rPDUOutletConfigOutletPhase OBJECT-TYPE
+ SYNTAX INTEGER {
+ phase1 (1),
+ phase2 (2),
+ phase3 (3),
+ phase1-2 (4),
+ phase2-3 (5),
+ phase3-1 (6)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The phase/s associated with this outlet.
+
+ For single phase devices, this object will always
+ return phase1(1).
+
+ For 3-phase devices, this object will return phase1 (1),
+ phase2 (2), or phase3 (3) for outlets tied to a single
+ phase. For outlets tied to two phases, this object will
+ return phase1-2 (4) for phases 1 and 2, phase2-3 (5) for
+ phases 2 and 3, and phase3-1 (6) for phases 3 and 1."
+ ::= { rPDUOutletConfigEntry 3 }
+
+rPDUOutletConfigPowerOnTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The amount of time (in seconds) the outlet will delay
+ powering on at coldstart or when a command that requires
+ a turn-on delay is issued.
+
+ Allowed values are:
+
+ -1 - never power on.
+ 0 - power on immediately.
+ 1 to 7200 - power on up to 7200 seconds after being
+ commanded."
+ ::= { rPDUOutletConfigEntry 4 }
+
+rPDUOutletConfigPowerOffTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The amount of time (in seconds) the outlet will delay
+ powering off when a command that requires
+ a turn-off delay is issued.
+
+ Allowed values are:
+
+ -1 - never power off.
+ 0 - power off immediately.
+ 1 to 7200 - power off up to 7200 seconds after being
+ commanded."
+ ::= { rPDUOutletConfigEntry 5 }
+
+rPDUOutletConfigRebootDuration OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "During a reboot sequence, power is turned off and then
+ back on. This OID defines the amount of time to wait,
+ in seconds, after turning the power off, at the start
+ of the sequence, before turning power back on, at the
+ end of the reboot sequence.
+
+ Allowed range is any value between 5 and 60 seconds (1 minute)."
+ ::= { rPDUOutletConfigEntry 6 }
+
+rPDUOutletConfigOutletBank OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The bank associated with this outlet."
+ ::= { rPDUOutletConfigEntry 7 }
+
+-- Monitored Outlets table
+
+rPDUOutletConfigMonitoredTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The size of the Outlet Config Monitored Table"
+ ::= { rPDUOutletConfig 2 }
+
+
+rPDUOutletConfigMonitoredTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RPDUOutletConfigMonitoredEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting/setting of outlet thresholds of an Outlet Monitored Rack PDU."
+ ::= { rPDUOutletConfig 3 }
+
+rPDUOutletConfigMonitoredEntry OBJECT-TYPE
+ SYNTAX RPDUOutletConfigMonitoredEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "This gives access to Monitored Outlet entries"
+ INDEX { rPDUOutletConfigMonitoredIndex }
+ ::= { rPDUOutletConfigMonitoredTable 1 }
+
+RPDUOutletConfigMonitoredEntry ::=
+ SEQUENCE {
+ rPDUOutletConfigMonitoredIndex INTEGER,
+ rPDUOutletConfigMonitoredName DisplayString,
+ rPDUOutletConfigMonitoredNumber INTEGER,
+ rPDUOutletConfigMonitoredLowLoadThreshold INTEGER,
+ rPDUOutletConfigMonitoredNearOverloadThreshold INTEGER,
+ rPDUOutletConfigMonitoredOverloadThreshold INTEGER
+ }
+
+rPDUOutletConfigMonitoredIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the RACK PDU Phase entry."
+ ::= { rPDUOutletConfigMonitoredEntry 1 }
+
+rPDUOutletConfigMonitoredName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the Monitored Outlet. The maximum string size is device dependent.
+ An error will be returned if the set request exceeds the max size."
+ ::= { rPDUOutletConfigMonitoredEntry 2 }
+
+rPDUOutletConfigMonitoredNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The outlet number of an Outlet Monitored RACK PDU."
+ ::= { rPDUOutletConfigMonitoredEntry 3 }
+
+
+rPDUOutletConfigMonitoredLowLoadThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A threshold that indicates the power consumption of
+ the load is nearing a low consumption condition. It is
+ represented in Amps. A warning will be issued when the
+ load is less than the threshold value.
+
+ A threshold value of 0 Amps effectively disables this
+ warning.
+
+ Maximum value must be less than the value returned
+ by the rPDUOutletConfigMonitoredNearOverloadThreshold OID.
+
+ 0 will be returned if the unit is not Outlet Monitored Rack PDU."
+ ::= { rPDUOutletConfigMonitoredEntry 4 }
+
+rPDUOutletConfigMonitoredNearOverloadThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A threshold that indicates the power consumption of
+ the load is nearing an overload condition. It is
+ represented in Amps. A warning will be issued when the
+ load is greater than or equal to the threshold value.
+
+ Minimum value must be greater than the value returned by
+ the rPDUOutletConfigMonitoredLowLoadThreshold OID.
+
+ Maximum value must be less than or equal to the value
+ returned by the rPDUOutletConfigMonitoredOverloadThreshold OID.
+
+ 0 will be returned if the unit is not Outlet Monitored Rack PDU."
+ ::= { rPDUOutletConfigMonitoredEntry 5 }
+
+rPDUOutletConfigMonitoredOverloadThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A threshold that indicates the power consumption of
+ the load has entered an overload condition. It is
+ represented in Amps. A warning will be issued when the
+ load is greater than or equal to the threshold value.
+
+ Minimum value must be greater than or equal to the value
+ returned by the rPDUOutletConfigMonitoredNearOverloadThreshold OID.
+
+ Maximum value must be less than or equal to the value
+ returned by the rPDULoadDevMaxOutletLoad OID.
+
+ 0 will be returned if the unit is not Outlet Monitored Rack PDU."
+ ::= { rPDUOutletConfigMonitoredEntry 6 }
+
+
+
+
+-- the rPDUOutletStatus group
+
+rPDUOutletStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RPDUOutletStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting of status of individual outlets. The number of
+ entries is contained in the rPDUOutletDevNumCntrlOutlets OID or
+ rPDUOutletDevMonitoredOutlets OID."
+ ::= { rPDUOutletStatus 1 }
+
+rPDUOutletStatusEntry OBJECT-TYPE
+ SYNTAX RPDUOutletStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The outlet to gather status from."
+ INDEX { rPDUOutletStatusIndex}
+ ::= { rPDUOutletStatusTable 1 }
+
+RPDUOutletStatusEntry ::=
+ SEQUENCE {
+ rPDUOutletStatusIndex INTEGER,
+ rPDUOutletStatusOutletName DisplayString,
+ rPDUOutletStatusOutletPhase INTEGER,
+ rPDUOutletStatusOutletState INTEGER,
+ rPDUOutletStatusCommandPending INTEGER,
+ rPDUOutletStatusOutletBank INTEGER,
+ rPDUOutletStatusLoad Gauge
+ }
+
+rPDUOutletStatusIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the outlet entry."
+ ::= { rPDUOutletStatusEntry 1 }
+
+rPDUOutletStatusOutletName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the outlet. The maximum string size is device dependent.
+ This OID is provided for informational purposes only."
+ ::= { rPDUOutletStatusEntry 2 }
+
+rPDUOutletStatusOutletPhase OBJECT-TYPE
+ SYNTAX INTEGER {
+ phase1 (1),
+ phase2 (2),
+ phase3 (3),
+ phase1-2 (4),
+ phase2-3 (5),
+ phase3-1 (6)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The phase/s associated with this outlet.
+
+ For single phase devices, this object will always
+ return phase1(1).
+
+ For 3-phase devices, this object will return phase1 (1),
+ phase2 (2), or phase3 (3) for outlets tied to a single
+ phase. For outlets tied to two phases, this object will
+ return phase1-2 (4) for phases 1 and 2, phase2-3 (5) for
+ phases 2 and 3, and phase3-1 (6) for phases 3 and 1."
+ ::= { rPDUOutletStatusEntry 3 }
+
+rPDUOutletStatusOutletState OBJECT-TYPE
+ SYNTAX INTEGER {
+ outletStatusOn (1),
+ outletStatusOff (2)
+ }
+
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this variable will return the outlet state. If
+ the outlet is on, the outletStatusOn (1) value will be returned.
+ If the outlet is off, the outletStatusOff (2) value will be
+ returned."
+ ::= { rPDUOutletStatusEntry 4 }
+
+rPDUOutletStatusCommandPending OBJECT-TYPE
+ SYNTAX INTEGER {
+ outletStatusCommandPending (1),
+ outletStatusNoCommandPending (2)
+ }
+
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this variable will return the command pending
+ state of the outlet. If a command is pending on the
+ outlet, the outletStatusCommandPending (1) value
+ will be returned. If there is not a command pending
+ on the outlet, the outletStatusNoCommandPending (2)
+ will be returned."
+ ::= { rPDUOutletStatusEntry 5 }
+
+rPDUOutletStatusOutletBank OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The bank associated with this outlet."
+ ::= { rPDUOutletStatusEntry 6 }
+
+rPDUOutletStatusLoad OBJECT-TYPE
+ SYNTAX Gauge
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return the measured Outlet load for
+ an Outlet Monitored Rack PDU in tenths of Amps. For other
+ models this OID is not supported."
+ ::= { rPDUOutletStatusEntry 7 }
+
+
+-- the rPDUOutletBank group
+
+rPDUOutletBankTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RPDUOutletBankEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for management of outlets on a per bank basis."
+ ::= { rPDUOutletBank 1 }
+
+rPDUOutletBankEntry OBJECT-TYPE
+ SYNTAX RPDUOutletBankEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The bank to manage."
+ INDEX { rPDUOutletBankIndex}
+ ::= { rPDUOutletBankTable 1 }
+
+RPDUOutletBankEntry ::=
+ SEQUENCE {
+ rPDUOutletBankIndex INTEGER,
+ rPDUOutletBankOverloadRestriction INTEGER
+ }
+
+rPDUOutletBankIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the Switched Rack PDU bank entry."
+ ::= { rPDUOutletBankEntry 1 }
+
+rPDUOutletBankOverloadRestriction OBJECT-TYPE
+ SYNTAX INTEGER {
+ alwaysAllowTurnON (1),
+ restrictOnNearOverload (2),
+ restrictOnOverload (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "This OID controls the behavior of a Switched Rack PDU
+ bank when an overload condition is possible and
+ additional outlets are requested to be turned on.
+
+ Setting this OID to alwaysAllowTurnON (1) will always allow
+ the outlets on the corresponding bank to turn on.
+
+ Setting this OID to restrictOnNearOverload (2) will not allow
+ outlets on the corresponding bank to turn on if the
+ rPDULoadBankConfigNearOverloadThreshold OID is exceeded.
+
+ Setting this OID to restrictOnOverload (3) will not allow
+ outlets on the corresponding bank to turn on if the
+ rPDULoadBankConfigOverloadThreshold OID is exceeded."
+ ::= { rPDUOutletBankEntry 2 }
+
+-- the rPDUPowerSupplyDevice group
+
+rPDUPowerSupply1Status OBJECT-TYPE
+ SYNTAX INTEGER {
+ powerSupplyOneOk (1),
+ powerSupplyOneFailed (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return powerSupply1Ok(1) if power
+ supply 1 is functioning normally. If not functioning normally,
+ this OID will return powerSupply1Failed(2)."
+ ::= { rPDUPowerSupplyDevice 1 }
+
+rPDUPowerSupply2Status OBJECT-TYPE
+ SYNTAX INTEGER {
+ powerSupplyTwoOk (1),
+ powerSupplyTwoFailed (2),
+ powerSupplyTwoNotPresent (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return powerSupply2Ok(1) if power
+ supply 2 is functioning normally. If not functioning normally,
+ this OID will return powerSupply2Failed(2).
+
+ Metered Rack PDUs do not have a redundant powersupply."
+
+ ::= { rPDUPowerSupplyDevice 2 }
+
+
+
+rPDUPowerSupplyAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ allAvailablePowerSuppliesOK (1),
+ powerSupplyOneFailed (2),
+ powerSupplyTwoFailed (3),
+ powerSupplyOneandTwoFailed (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return powerSupply Alarm"
+ ::= { rPDUPowerSupplyDevice 3 }
+
+-- the rPDUStatus group
+
+rPDUStatusBankTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The size of the Status Bank Table"
+ ::= { rPDUStatus 1 }
+
+
+rPDUStatusBankTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RPDUStatusBankEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting of status of each Rack PDU Bank"
+ ::= { rPDUStatus 2 }
+
+rPDUStatusBankEntry OBJECT-TYPE
+ SYNTAX RPDUStatusBankEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "This gives access to Bank entries"
+ INDEX { rPDUStatusBankIndex }
+ ::= { rPDUStatusBankTable 1 }
+
+RPDUStatusBankEntry ::=
+ SEQUENCE {
+ rPDUStatusBankIndex INTEGER,
+ rPDUStatusBankNumber INTEGER,
+ rPDUStatusBankState INTEGER
+ }
+
+rPDUStatusBankIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the RACK PDU Bank entry."
+ ::= { rPDUStatusBankEntry 1 }
+
+rPDUStatusBankNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return the bank number."
+ ::= { rPDUStatusBankEntry 2 }
+
+rPDUStatusBankState OBJECT-TYPE
+ SYNTAX INTEGER {
+ bankLoadNormal (1),
+ bankLoadLow (2),
+ bankLoadNearOverload (3),
+ bankLoadOverload (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return the bank load state.
+
+ bankLoadNormal(1) indicates that the bank is
+ operating properly within the rPDULoadBankConfigLowLoadThreshold
+ and rPDULoadBankConfigNearOverloadThreshold OID values.
+
+ bankLoadLow(2) indicates that the bank load has
+ dropped below the rPDULoadBankConfigLowLoadThreshold OID value.
+ An SNMP trap will occur when this state is entered or cleared.
+
+ bankLoadNearOverload(3) indicates that the bank load
+ is greater than or equal to the
+ rPDULoadBankConfigNearOverloadThreshold OID value.
+ An SNMP trap will occur when this state is entered or cleared.
+
+ bankLoadOverload(4) indicates that the bank load is
+ greater than or equal to the rPDULoadBankConfigOverloadThreshold
+ OID value.
+ An SNMP trap will occur when this state is entered or cleared."
+ ::= { rPDUStatusBankEntry 3 }
+
+-- Phase status table
+
+rPDUStatusPhaseTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The size of the Status Phase Table"
+ ::= { rPDUStatus 3 }
+
+
+rPDUStatusPhaseTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RPDUStatusPhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting of status of each Rack PDU Phase"
+ ::= { rPDUStatus 4 }
+
+rPDUStatusPhaseEntry OBJECT-TYPE
+ SYNTAX RPDUStatusPhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "This gives access to Phase entries"
+ INDEX { rPDUStatusPhaseIndex }
+ ::= { rPDUStatusPhaseTable 1 }
+
+RPDUStatusPhaseEntry ::=
+ SEQUENCE {
+ rPDUStatusPhaseIndex INTEGER,
+ rPDUStatusPhaseNumber INTEGER,
+ rPDUStatusPhaseState INTEGER
+ }
+
+rPDUStatusPhaseIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the RACK PDU Phase entry."
+ ::= { rPDUStatusPhaseEntry 1 }
+
+rPDUStatusPhaseNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return the phase number."
+ ::= { rPDUStatusPhaseEntry 2 }
+
+rPDUStatusPhaseState OBJECT-TYPE
+ SYNTAX INTEGER {
+ phaseLoadNormal (1),
+ phaseLoadLow (2),
+ phaseLoadNearOverload (3),
+ phaseLoadOverload (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return the Phase load state.
+
+ phaseLoadNormal(1) indicates that the Phase is
+ operating properly within the rPDULoadPhaseConfigLowLoadThreshold
+ and rPDULoadPhaseConfigNearOverloadThreshold OID values.
+
+ phaseLoadLow(2) indicates that the Phase load has
+ dropped below the rPDULoadPhaseConfigLowLoadThreshold OID value.
+ An SNMP trap will occur when this state is entered or cleared.
+
+ phaseLoadNearOverload(3) indicates that the Phase load
+ is greater than or equal to the
+ rPDULoadPhaseConfigNearOverloadThreshold OID value.
+ An SNMP trap will occur when this state is entered or cleared.
+
+ phaseLoadOverload(4) indicates that the Phase load is
+ greater than or equal to the rPDULoadPhaseConfigOverloadThreshold
+ OID value.
+ An SNMP trap will occur when this state is entered or cleared."
+ ::= { rPDUStatusPhaseEntry 3 }
+
+-- Outlet status table
+
+rPDUStatusOutletTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The size of the Status Outlet Table"
+ ::= { rPDUStatus 5 }
+
+
+rPDUStatusOutletTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RPDUStatusOutletEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting of status of each Outlet of an Outlet Monitored Rack PDU."
+ ::= { rPDUStatus 6 }
+
+rPDUStatusOutletEntry OBJECT-TYPE
+ SYNTAX RPDUStatusOutletEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "This gives access to Outlet entries"
+ INDEX { rPDUStatusOutletIndex }
+ ::= { rPDUStatusOutletTable 1 }
+
+RPDUStatusOutletEntry ::=
+ SEQUENCE {
+ rPDUStatusOutletIndex INTEGER,
+ rPDUStatusOutletNumber INTEGER,
+ rPDUStatusOutletState INTEGER
+ }
+
+rPDUStatusOutletIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the RACK PDU Outlet entry."
+ ::= { rPDUStatusOutletEntry 1 }
+
+rPDUStatusOutletNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return the Outlet number."
+ ::= { rPDUStatusOutletEntry 2 }
+
+rPDUStatusOutletState OBJECT-TYPE
+ SYNTAX INTEGER {
+ outletLoadNormal (1),
+ outletLoadLow (2),
+ outletLoadNearOverload (3),
+ outletLoadOverload (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return the Outlet load state.
+
+ outletLoadNormal(1) indicates that the Outlet is
+ operating properly within the rPDUOutletConfigMonitoredLowLoadThreshold
+ and rPDUOutletConfigMonitoredNearOverloadThreshold OID values.
+
+ outletLoadLow(2) indicates that the Outlet load has
+ dropped below the rPDUOutletConfigMonitoredLowLoadThreshold OID value.
+ An SNMP trap will occur when this state is entered or cleared.
+
+ outletLoadNearOverload(3) indicates that the Outlet load
+ is greater than or equal to the
+ rPDUOutletConfigMonitoredNearOverloadThreshold OID value.
+ An SNMP trap will occur when this state is entered or cleared.
+
+ outletLoadOverload(4) indicates that the Outlet load is
+ greater than or equal to the rPDUOutletConfigMonitoredOverloadThreshold
+ OID value.
+ An SNMP trap will occur when this state is entered or cleared."
+ ::= { rPDUStatusOutletEntry 3 }
+
+-- Common rPDU2 values
+
+Rpdu2OutletPhaseLayoutType ::= INTEGER {
+ seqPhase1ToNeutral (1),
+ seqPhase2ToNeutral (2),
+ seqPhase3ToNeutral (3),
+ seqPhase1ToPhase2 (4),
+ seqPhase2ToPhase3 (5),
+ seqPhase3ToPhase1 (6)
+ }
+
+-- rPDU2 Ident Table
+
+rPDU2IdentTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The total number of Rack PDUs"
+ ::= { rPDU2 1 }
+
+rPDU2IdentTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RPDU2IdentEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A table of Rack PDU identification data"
+ ::= { rPDU2 2 }
+
+rPDU2IdentEntry OBJECT-TYPE
+ SYNTAX RPDU2IdentEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Identification data from Rack PDU being queried"
+ INDEX { rPDU2IdentIndex }
+ ::= { rPDU2IdentTable 1 }
+
+RPDU2IdentEntry ::=
+ SEQUENCE {
+ rPDU2IdentIndex INTEGER,
+ rPDU2IdentModule INTEGER,
+ rPDU2IdentName DisplayString,
+ rPDU2IdentLocation DisplayString,
+ rPDU2IdentHardwareRev DisplayString,
+ rPDU2IdentFirmwareRev DisplayString,
+ rPDU2IdentDateOfManufacture DisplayString,
+ rPDU2IdentModelNumber DisplayString,
+ rPDU2IdentSerialNumber DisplayString,
+ rPDU2IdentContact DisplayString,
+ rPDU2IdentBootMonitorRev DisplayString,
+ rPDU2IdentLongDescription DisplayString,
+ rPDU2IdentNMCSerialNumber DisplayString,
+ rPDU2IndentAppBuildDate DisplayString,
+ rPDU2IndentAOSBuildDate DisplayString,
+ rPDU2IndentBootMonBuildDate DisplayString
+ }
+
+rPDU2IdentIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the Rack PDU identification table
+ entry"
+ ::= { rPDU2IdentEntry 1 }
+
+rPDU2IdentModule OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user-defined Rack PDU numeric ID"
+ ::= { rPDU2IdentEntry 2 }
+
+rPDU2IdentName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A user-defined string identifying the Rack PDU"
+ ::= { rPDU2IdentEntry 3 }
+
+rPDU2IdentLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A user-defined string identifying the location
+ of the Rack PDU"
+ ::= { rPDU2IdentEntry 4 }
+
+rPDU2IdentHardwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Rack PDU hardware version"
+ ::= { rPDU2IdentEntry 5 }
+
+rPDU2IdentFirmwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Rack PDU firmware version"
+ ::= { rPDU2IdentEntry 6 }
+
+rPDU2IdentDateOfManufacture OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The date the Rack PDU was manufactured
+ in mm/dd/yyyy format"
+ ::= { rPDU2IdentEntry 7 }
+
+rPDU2IdentModelNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Rack PDU model number"
+ ::= { rPDU2IdentEntry 8 }
+
+rPDU2IdentSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Rack PDU serial number"
+ ::= { rPDU2IdentEntry 9 }
+
+rPDU2IdentContact OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A user-defined string identifying the
+ person to contact regarding the Rack PDU"
+ ::= { rPDU2IdentEntry 10 }
+
+rPDU2IdentBootMonitorRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Rack PDU Boot Monitor version"
+ ::= { rPDU2IdentEntry 11 }
+
+ rPDU2IdentLongDescription OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Rack PDU Long Description name"
+ ::= { rPDU2IdentEntry 12 }
+
+ rPDU2IdentNMCSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Rack PDU Network Management Card (NMC) serial number"
+ ::= { rPDU2IdentEntry 13 }
+
+ rPDU2IndentAppBuildDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Rack PDU Application build date"
+ ::= { rPDU2IdentEntry 14 }
+
+ rPDU2IndentAOSBuildDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Rack PDU AOS build date"
+ ::= { rPDU2IdentEntry 15 }
+
+ rPDU2IndentBootMonBuildDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Rack PDU Boot Monitor build date"
+ ::= { rPDU2IdentEntry 16 }
+
+-- rPDU2 Device Data
+
+rPDU2DeviceTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The total number of Rack PDUs"
+ ::= { rPDU2 3 }
+
+rPDU2Device OBJECT IDENTIFIER ::= { rPDU2 4 }
+
+-- rPDU2 Device Config
+
+rPDU2DeviceConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RPDU2DeviceConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A table of Rack PDU configuration data"
+ ::= { rPDU2Device 1 }
+
+rPDU2DeviceConfigEntry OBJECT-TYPE
+ SYNTAX RPDU2DeviceConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Configuration data from Rack PDU being queried"
+ INDEX { rPDU2DeviceConfigIndex }
+ ::= { rPDU2DeviceConfigTable 1 }
+
+RPDU2DeviceConfigEntry ::=
+ SEQUENCE {
+ rPDU2DeviceConfigIndex INTEGER,
+ rPDU2DeviceConfigModule INTEGER,
+ rPDU2DeviceConfigName DisplayString,
+ rPDU2DeviceConfigLocation DisplayString,
+ rPDU2DeviceConfigDisplayOrientation INTEGER,
+ rPDU2DeviceConfigColdstartDelay INTEGER,
+ rPDU2DeviceConfigLowLoadPowerThreshold INTEGER,
+ rPDU2DeviceConfigNearOverloadPowerThreshold INTEGER,
+ rPDU2DeviceConfigOverloadPowerThreshold INTEGER,
+ rPDU2DeviceConfigDevicePeakPowerReset INTEGER,
+ rPDU2DeviceConfigDeviceEnergyReset INTEGER,
+ rPDU2DeviceConfigOutletsEnergyReset INTEGER,
+ rPDU2DeviceConfigOutletsPeakLoadReset INTEGER,
+ rPDU2DeviceConfigContact DisplayString
+
+ }
+
+rPDU2DeviceConfigIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the Rack PDU table entry"
+ ::= { rPDU2DeviceConfigEntry 1 }
+
+rPDU2DeviceConfigModule OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The user-defined Rack PDU numeric ID"
+ ::= { rPDU2DeviceConfigEntry 2 }
+
+rPDU2DeviceConfigName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A user-defined string identifying the Rack PDU"
+ ::= { rPDU2DeviceConfigEntry 3 }
+
+rPDU2DeviceConfigLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A user-defined string identifying the location
+ of the Rack PDU"
+ ::= { rPDU2DeviceConfigEntry 4 }
+
+rPDU2DeviceConfigDisplayOrientation OBJECT-TYPE
+ SYNTAX INTEGER {
+ displayNormal (1),
+ displayReverse (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the intended physical orientation
+ of the display.
+
+ displayNormal(1) indicates normal orientation
+ displayReverse(2) indicates upside down orientation"
+ ::= { rPDU2DeviceConfigEntry 5 }
+
+rPDU2DeviceConfigColdstartDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The amount of delay, measured in seconds, between
+ when power is provided to the Rack PDU and when
+ the Rack PDU provides basic master power to the
+ outlets.
+ Allowed values are:
+ -1 - never apply power automatically.
+ 0 - apply power immediately.
+ 1 to 300 - delay up to 300 seconds (5 minutes)."
+ ::= { rPDU2DeviceConfigEntry 6 }
+
+rPDU2DeviceConfigLowLoadPowerThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "User-defined low power draw alarm threshold,
+ measured in tenths of kilowatts. Models that do
+ not support this feature will respond to this OID
+ with a value of -1."
+ ::= { rPDU2DeviceConfigEntry 7 }
+
+rPDU2DeviceConfigNearOverloadPowerThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "User-defined near power overload threshold,
+ measured in tenths of kilowatts. Models that do
+ not support this feature will respond to this OID
+ with a value of -1."
+ ::= { rPDU2DeviceConfigEntry 8 }
+
+rPDU2DeviceConfigOverloadPowerThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "User-defined power overload threshold,
+ measured in tenths of kilowatts. Models that do
+ not support this feature will respond to this OID
+ with a value of -1."
+ ::= { rPDU2DeviceConfigEntry 9 }
+
+rPDU2DeviceConfigDevicePeakPowerReset OBJECT-TYPE
+ SYNTAX INTEGER {
+ noOperation (1),
+ reset (2),
+ notSupported (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to reset (2) will cause the existing peak power value
+ to be replaced by the current load power value.
+
+ Getting this OID will do nothing and return the noOperation(1) value.
+ Models that do not support this feature will respond to this OID
+ with a value of not supported (3). Attempts to set this OID
+ in these models will fail."
+ ::= { rPDU2DeviceConfigEntry 10 }
+
+rPDU2DeviceConfigDeviceEnergyReset OBJECT-TYPE
+ SYNTAX INTEGER {
+ noOperation (1),
+ reset (2),
+ notSupported (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to reset (2) will cause the device energy meter value
+ to be reset to zero.
+
+ Getting this OID in models that support this feature will do nothing
+ and return the noOperation(1) value.
+
+ Models that do not support this feature will respond to this OID
+ with a value of notSupported (3). Attempts to set this OID
+ in these models will fail."
+ ::= { rPDU2DeviceConfigEntry 11 }
+
+rPDU2DeviceConfigOutletsEnergyReset OBJECT-TYPE
+ SYNTAX INTEGER {
+ noOperation (1),
+ reset (2),
+ notSupported (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to reset (2) will cause the all outlet energy meter values
+ to be reset to zero.
+
+ Getting this OID will do nothing and return the noOperation(1) value.
+
+ Models that do not support this feature will respond to this OID
+ with a value of notSupported (3). Attempts to set this OID
+ in these models will fail."
+ ::= { rPDU2DeviceConfigEntry 12 }
+
+rPDU2DeviceConfigOutletsPeakLoadReset OBJECT-TYPE
+ SYNTAX INTEGER {
+ noOperation (1),
+ reset (2),
+ notSupported (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to reset (2) will cause the all outlet peak load values
+ to be reset to zero.
+
+ Getting this OID will do nothing and return the noOperation(1) value.
+
+ Models that do not support this feature will respond to this OID
+ with a value of notSupported (3). Attempts to set this OID
+ in these models will fail."
+ ::= { rPDU2DeviceConfigEntry 13 }
+
+rPDU2DeviceConfigContact OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A user-defined string identifying the
+ person to contact regarding the Rack PDU"
+ ::= { rPDU2DeviceConfigEntry 14 }
+
+-- rPDU2 Device Properties
+
+rPDU2DevicePropertiesTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RPDU2DevicePropertiesEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A table of Rack PDU properties"
+ ::= { rPDU2Device 2 }
+
+rPDU2DevicePropertiesEntry OBJECT-TYPE
+ SYNTAX RPDU2DevicePropertiesEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Properties of the Rack PDU being queried"
+ INDEX { rPDU2DevicePropertiesIndex }
+ ::= { rPDU2DevicePropertiesTable 1 }
+
+RPDU2DevicePropertiesEntry ::=
+ SEQUENCE {
+ rPDU2DevicePropertiesIndex INTEGER,
+ rPDU2DevicePropertiesModule INTEGER,
+ rPDU2DevicePropertiesName DisplayString,
+ rPDU2DevicePropertiesNumOutlets INTEGER,
+ rPDU2DevicePropertiesNumSwitchedOutlets INTEGER,
+ rPDU2DevicePropertiesNumMeteredOutlets INTEGER,
+ rPDU2DevicePropertiesNumPhases INTEGER,
+ rPDU2DevicePropertiesNumMeteredBanks INTEGER,
+ rPDU2DevicePropertiesMaxCurrentRating INTEGER,
+ rPDU2DevicePropertiesOrientation INTEGER,
+ rPDU2DevicePropertiesOutletLayout INTEGER,
+ rPDU2DevicePropertiesMaxPhaseCurrentRating INTEGER,
+ rPDU2DevicePropertiesDevicePowerRating INTEGER
+ }
+
+rPDU2DevicePropertiesIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the Rack PDU properties table entry"
+ ::= { rPDU2DevicePropertiesEntry 1 }
+
+rPDU2DevicePropertiesModule OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user-defined Rack PDU numeric ID"
+ ::= { rPDU2DevicePropertiesEntry 2 }
+
+rPDU2DevicePropertiesName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A user-defined string identifying the Rack PDU"
+ ::= { rPDU2DevicePropertiesEntry 3 }
+
+rPDU2DevicePropertiesNumOutlets OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of outlets on the Rack PDU"
+ ::= { rPDU2DevicePropertiesEntry 4 }
+
+rPDU2DevicePropertiesNumSwitchedOutlets OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of switched outlets on the Rack PDU"
+ ::= { rPDU2DevicePropertiesEntry 5 }
+
+rPDU2DevicePropertiesNumMeteredOutlets OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of metered outlets on the Rack PDU"
+ ::= { rPDU2DevicePropertiesEntry 6 }
+
+rPDU2DevicePropertiesNumPhases OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of phases present in the Rack PDU"
+ ::= { rPDU2DevicePropertiesEntry 7 }
+
+rPDU2DevicePropertiesNumMeteredBanks OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of metered banks present in the Rack PDU"
+ ::= { rPDU2DevicePropertiesEntry 8 }
+
+rPDU2DevicePropertiesMaxCurrentRating OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum current rating, measured in Amps, for
+ the Rack PDU"
+ ::= { rPDU2DevicePropertiesEntry 9 }
+
+rPDU2DevicePropertiesOrientation OBJECT-TYPE
+ SYNTAX INTEGER {
+ horizontal (1),
+ vertical (2),
+ verticalISXv2 (3),
+ verticalISXv3 (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Rack PDU orientation"
+ ::= { rPDU2DevicePropertiesEntry 10 }
+
+rPDU2DevicePropertiesOutletLayout OBJECT-TYPE
+ SYNTAX INTEGER {
+ seqPhaseToNeutral (1),
+ seqPhaseToPhase (2),
+ seqPhToNeu21PhToPh (3),
+ seqPhToPhGrouped (4),
+ seqPhToNGrouped (5),
+ seqPToN1516PToPGrouped (6),
+ seqPhToPh2xGrouped (7),
+ seqPhToN2xGrouped (8),
+ seqNotApplicable (9),
+ seqPhToNPhToPhPhToN (10)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return outlet layout for the device.
+
+ seqPhaseToNeutral(1) indicates outlet layout as follows:
+ 1:1-N,2:2-N,3:3-N,4:1-N,5:2-N,...
+ or for single phase SKUs, all outlets 1-N
+
+ seqPhaseToPhase(2) indicates outlet layout as follows:
+ 1:1-2,2:2-3,3:3-1,4:1-2,5:2-3,...
+
+ seqPhToNeu21PhToPh(3) indicates outlet layout as follows:
+ 1:1-N,2:2-N...21:3-N,22:1-2,23:2-3,24:3-1,...
+
+ seqPhToPhGrouped(4) indicates outlet layout as follows:
+ For AP8xxx SKU's Group 1:1-2, Group 2:2-3, Group 3:3-1.
+
+ seqPhToNGrouped(5) indicates outlet layout as follows:
+ This unit has 3 outlet groups. Group 1:1-N, Group 2:2-N, Group 3:3-N.
+
+ seqPToN1516PToPGrouped(6) indicates outlet layout as follows:
+ This unit has 4 outlet groups. Group 1 (Outlets 1-14):1-2,
+ Group 2 (Outlets 15-16):1-N, Group 3:2-3, Group 4:3-1.
+
+ seqPhToPh2xGrouped(7) indicates outlet layout as follows:
+ This unit has 6 outlet groups. Group 1:1-2, Group 2:1-2, Group 3:2-3,
+ Group 4:2-3, Group 5:3-1, Group 6:3-1.
+
+ seqPhToN2xGrouped(8) indicates outlet layout as follows:
+ This unit has 6 outlet groups. Group 1:1-N, Group 2:1-N, Group 3:2-N,
+ Group 4:2-N, Group 5:3-N, Group 6:3-N.
+
+ seqNotApplicable(9):
+ Outlet layout does not affect any of the user interfaces for
+ AP88XX SKUs. These SKUs may report seqNotApplicable(9) if there is
+ not an exact outlet layout match available.
+
+ seqPhToNPhToPhPhToN(10) indicates outlet layout as follows:
+ Group 1:1-N, Group 2:1-2, Group 3:2-N."
+ ::= { rPDU2DevicePropertiesEntry 11 }
+
+rPDU2DevicePropertiesMaxPhaseCurrentRating OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum current rating, measured in Amps, for
+ the Rack PDU"
+ ::= { rPDU2DevicePropertiesEntry 12 }
+
+
+rPDU2DevicePropertiesDevicePowerRating OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum power rating, measured in Watts, for
+ the Rack PDU"
+ ::= { rPDU2DevicePropertiesEntry 13 }
+
+
+-- rPDU2 Device Status
+
+rPDU2DeviceStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RPDU2DeviceStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A table of Rack PDU status information"
+ ::= { rPDU2Device 3 }
+
+rPDU2DeviceStatusEntry OBJECT-TYPE
+ SYNTAX RPDU2DeviceStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Status information from the Rack PDU being queried"
+ INDEX { rPDU2DeviceStatusIndex }
+ ::= { rPDU2DeviceStatusTable 1 }
+
+RPDU2DeviceStatusEntry ::=
+ SEQUENCE {
+ rPDU2DeviceStatusIndex INTEGER,
+ rPDU2DeviceStatusModule INTEGER,
+ rPDU2DeviceStatusName DisplayString,
+ rPDU2DeviceStatusLoadState INTEGER,
+ rPDU2DeviceStatusPower INTEGER,
+ rPDU2DeviceStatusPeakPower INTEGER,
+ rPDU2DeviceStatusPeakPowerTimestamp DisplayString,
+ rPDU2DeviceStatusPeakPowerStartTime DisplayString,
+ rPDU2DeviceStatusEnergy INTEGER,
+ rPDU2DeviceStatusEnergyStartTime DisplayString,
+ rPDU2DeviceStatusCommandPending INTEGER,
+ rPDU2DeviceStatusPowerSupplyAlarm INTEGER,
+ rPDU2DeviceStatusPowerSupply1Status INTEGER,
+ rPDU2DeviceStatusPowerSupply2Status INTEGER,
+ rPDU2DeviceStatusOutletsEnergyStartTime DisplayString,
+ rPDU2DeviceStatusApparentPower INTEGER,
+ rPDU2DeviceStatusPowerFactor INTEGER,
+ rPDU2DeviceStatusNPSType INTEGER
+ }
+
+rPDU2DeviceStatusIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the Rack PDU status table entry"
+ ::= { rPDU2DeviceStatusEntry 1 }
+
+rPDU2DeviceStatusModule OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user-defined Rack PDU numeric ID"
+ ::= { rPDU2DeviceStatusEntry 2 }
+
+rPDU2DeviceStatusName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A user-defined string identifying the Rack PDU"
+ ::= { rPDU2DeviceStatusEntry 3 }
+
+rPDU2DeviceStatusLoadState OBJECT-TYPE
+ SYNTAX INTEGER {
+ lowLoad (1),
+ normal (2),
+ nearOverload (3),
+ overload (4),
+ notsupported (5)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the present load status of the Rack PDU.
+ Models that do not support this feature will respond to this OID
+ with a value of notsupported (5)."
+ ::= { rPDU2DeviceStatusEntry 4 }
+
+rPDU2DeviceStatusPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The power consumption of the Rack PDU load in hundredths of kilowatts.
+ Models that do not support this feature will respond to this OID
+ with a value of -1."
+ ::= { rPDU2DeviceStatusEntry 5 }
+
+rPDU2DeviceStatusPeakPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The peak power consumption of the Rack PDU load in hundredths of kilowatts.
+ Models that do not support this feature will respond to this OID with a value
+ of -1."
+ ::= { rPDU2DeviceStatusEntry 6 }
+
+rPDU2DeviceStatusPeakPowerTimestamp OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the date and time that peak power consumption occurred.
+ Models that do not support this feature will respond to this OID with string
+ 'notsupported'."
+ ::= { rPDU2DeviceStatusEntry 7 }
+
+rPDU2DeviceStatusPeakPowerStartTime OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the date and time of the last device peak power reset.
+ Models that do not support this feature will respond to this OID with string
+ 'notsupported'."
+ ::= { rPDU2DeviceStatusEntry 8 }
+
+rPDU2DeviceStatusEnergy OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A user resettable energy meter measuring Rack PDU load
+ energy consumption in tenths of kilowatt-hours. Models that do not
+ support this feature will respond to this OID
+ with a value of -1."
+ ::= { rPDU2DeviceStatusEntry 9 }
+
+rPDU2DeviceStatusEnergyStartTime OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the date and time of the last device energy
+ meter reset. Models that do not support this feature will
+ respond to this OID with string 'notsupported'."
+ ::= { rPDU2DeviceStatusEntry 10 }
+
+
+rPDU2DeviceStatusCommandPending OBJECT-TYPE
+ SYNTAX INTEGER {
+ commandPending (1),
+ noCommandPending (2),
+ commandPendingUnknown (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates whether or not the device
+ is processing a pending command. If
+ the commandPendingUnknown (3) value is
+ returned, all devices powered by the
+ Rack PDU should be shut down. The
+ Rack PDU's power should then be cycled
+ to clear this condition."
+ ::= { rPDU2DeviceStatusEntry 11 }
+
+rPDU2DeviceStatusPowerSupplyAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates a power supply alarm is active when value
+ equals alarm (2)"
+ ::= { rPDU2DeviceStatusEntry 12 }
+
+rPDU2DeviceStatusPowerSupply1Status OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2),
+ notInstalled (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates whether or not an alarm is active in Power
+ Supply 1"
+ ::= { rPDU2DeviceStatusEntry 13 }
+
+rPDU2DeviceStatusPowerSupply2Status OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2),
+ notInstalled (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates whether or not an alarm is active in Power
+ Supply 2"
+ ::= { rPDU2DeviceStatusEntry 14 }
+
+rPDU2DeviceStatusOutletsEnergyStartTime OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the date and time of the last outlets energy
+ meter reset. Models that do not support this feature will
+ respond to this OID with string 'notsupported'."
+ ::= { rPDU2DeviceStatusEntry 15 }
+
+rPDU2DeviceStatusApparentPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The apparent power consumption of the Rack PDU load in hundredths of kiloVoltAmps (kVA).
+ Models that do not support this feature will respond to this OID
+ with a value of -1."
+ ::= { rPDU2DeviceStatusEntry 16 }
+
+rPDU2DeviceStatusPowerFactor OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The power factor of the Rack PDU load in hundredths. Models that do not support this feature
+ will respond to this OID with a value of -1."
+ ::= { rPDU2DeviceStatusEntry 17 }
+
+rPDU2DeviceStatusNPSType OBJECT-TYPE
+ SYNTAX INTEGER {
+ notNPS (1),
+ host (2),
+ guest (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The device NPS status:
+ notNPS (1) indicates the Rack PDU is not in an NPS group.
+ host (2) indicates the Rack PDU has been designated as a host in an NPS group.
+ Only one Rack PDU in an NPS group is allowed to be the host.
+ guest (3) indicates the Rack PDU has been designated as a guest in an NPS group."
+ ::= { rPDU2DeviceStatusEntry 18 }
+
+-- rPDU2 Device Control
+
+rPDU2DeviceControlTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RPDU2DeviceControlEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A table of Rack PDU control data"
+ ::= { rPDU2Device 4 }
+
+rPDU2DeviceControlEntry OBJECT-TYPE
+ SYNTAX RPDU2DeviceControlEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Control data from Rack PDU being queried"
+ INDEX { rPDU2DeviceControlIndex }
+ ::= { rPDU2DeviceControlTable 1 }
+
+RPDU2DeviceControlEntry ::=
+ SEQUENCE {
+ rPDU2DeviceControlIndex INTEGER,
+ rPDU2DeviceControlModule INTEGER,
+ rPDU2DeviceControlName DisplayString,
+ rPDU2DeviceControlCommand INTEGER
+ }
+
+rPDU2DeviceControlIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the Rack PDU control table entry"
+ ::= { rPDU2DeviceControlEntry 1 }
+
+rPDU2DeviceControlModule OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user-defined Rack PDU numeric ID"
+ ::= { rPDU2DeviceControlEntry 2 }
+
+rPDU2DeviceControlName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A user-defined string identifying the Rack PDU"
+ ::= { rPDU2DeviceControlEntry 3 }
+
+rPDU2DeviceControlCommand OBJECT-TYPE
+ SYNTAX INTEGER {
+ immediateAllOn (1),
+ delayedAllOn (2),
+ immediateAllOff (3),
+ immediateAllReboot (4),
+ delayedAllReboot (5),
+ noCommandAll (6),
+ delayedAllOff (7),
+ cancelAllPendingCommands (8)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to immediateAllOn (1) will turn all outlets
+ on immediately.
+
+ Setting this OID to delayedAllOn (2) will turn all outlets on as
+ defined by each outlet's rPDU2OutletSwitchedConfigPowerOnTime
+ OID value.
+
+ Setting this OID to immediateAllOff (3) will turn all outlets
+ off immediately.
+
+ Setting this OID to immediateAllReboot (4) will cause an immediateAllOff
+ command to be performed. Once all outlets are off, the
+ Switched Rack PDU will then delay the
+ rPDU2OutletSwitchedConfigRebootDuration OID time, and then perform an
+ immediateAllOn command.
+
+ Setting this OID to delayedAllReboot (5) will cause a
+ delayedAllOff command to be performed. Once all outlets are off,
+ the Switched Rack PDU will then delay the largest
+ rPDU2OutletSwitchedConfigRebootDuration OID time, and then perform a
+ delayedAllOn command.
+
+ Setting this OID to noCommandAll (6) will have no effect.
+
+ Setting this OID to delayedAllOff (7) will turn all outlets off
+ as defined by each outlet's rPDU2OutletSwitchedConfigPowerOffTime
+ OID value.
+
+ Setting this OID to cancelAllPendingCommands (8) will cause all pending
+ commands on the Switched Rack PDU to be cancelled.
+
+ Getting this OID will return the noCommandAll (6)
+ value."
+ ::= { rPDU2DeviceControlEntry 4 }
+
+-- rPDU2 Phase Data
+
+rPDU2PhaseTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of connected Rack PDU phases"
+ ::= { rPDU2 5}
+
+rPDU2Phase OBJECT IDENTIFIER ::= { rPDU2 6 }
+
+-- rPDU2 Phase Config
+
+rPDU2PhaseConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RPDU2PhaseConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A table of Rack PDU phase configuration data"
+ ::= { rPDU2Phase 1 }
+
+rPDU2PhaseConfigEntry OBJECT-TYPE
+ SYNTAX RPDU2PhaseConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Configuration data from currently queried Rack
+ PDU phase"
+ INDEX { rPDU2PhaseConfigIndex }
+ ::= { rPDU2PhaseConfigTable 1 }
+
+RPDU2PhaseConfigEntry ::=
+ SEQUENCE {
+ rPDU2PhaseConfigIndex INTEGER,
+ rPDU2PhaseConfigModule INTEGER,
+ rPDU2PhaseConfigNumber INTEGER,
+ rPDU2PhaseConfigOverloadRestriction INTEGER,
+ rPDU2PhaseConfigLowLoadCurrentThreshold INTEGER,
+ rPDU2PhaseConfigNearOverloadCurrentThreshold INTEGER,
+ rPDU2PhaseConfigOverloadCurrentThreshold INTEGER,
+ rPDU2PhaseConfigPhasePeakCurrentReset INTEGER
+ }
+
+rPDU2PhaseConfigIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the Rack PDU phase configuration
+ table entry"
+ ::= { rPDU2PhaseConfigEntry 1 }
+
+rPDU2PhaseConfigModule OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user-defined Rack PDU numeric ID"
+ ::= { rPDU2PhaseConfigEntry 2 }
+
+rPDU2PhaseConfigNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The numeric phase ID"
+ ::= { rPDU2PhaseConfigEntry 3 }
+
+rPDU2PhaseConfigOverloadRestriction OBJECT-TYPE
+ SYNTAX INTEGER {
+ alwaysAllowTurnON (1),
+ restrictOnNearOverload (2),
+ restrictOnOverload (3),
+ notSupported (4)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "This OID controls the behavior of a Switched Rack PDU
+ phase when an overload condition is possible and
+ additional outlets are requested to be turned on.
+
+ Setting this OID to alwaysAllowTurnON (1) will always allow
+ the outlets on the corresponding phase to turn on.
+
+ Setting this OID to restrictOnNearOverload (2) will not allow
+ outlets on the corresponding phase to turn on if the
+ rPDULoadConfigNearOverloadThreshold OID is exceeded.
+
+ Setting this OID to restrictOnOverload (3) will not allow
+ outlets on the corresponding phase to turn on if the
+ rPDULoadConfigOverloadThreshold OID is exceeded.
+
+ Models that do not support this feature will respond to this OID
+ with a value of notSupported (4). Attempts to set this OID
+ in these models will fail."
+ ::= { rPDU2PhaseConfigEntry 4 }
+
+rPDU2PhaseConfigLowLoadCurrentThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "User-defined low load phase current
+ threshold in Amps"
+ ::= { rPDU2PhaseConfigEntry 5 }
+
+rPDU2PhaseConfigNearOverloadCurrentThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "User-defined near phase overload warning
+ threshold in Amps"
+ ::= { rPDU2PhaseConfigEntry 6 }
+
+rPDU2PhaseConfigOverloadCurrentThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "User-defined phase overload current
+ threshold in Amps"
+ ::= { rPDU2PhaseConfigEntry 7 }
+
+rPDU2PhaseConfigPhasePeakCurrentReset OBJECT-TYPE
+ SYNTAX INTEGER {
+ noOperation (1),
+ reset (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to reset (2) will cause the existing peak current value
+ to be replaced by the present load current value.
+
+ Getting this OID will do nothing and return the noOperation(1) value."
+ ::= { rPDU2PhaseConfigEntry 8 }
+
+
+-- rPDU2 Phase Properties
+
+rPDU2PhasePropertiesTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RPDU2PhasePropertiesEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A table of Rack PDU phase properties"
+ ::= { rPDU2Phase 2 }
+
+rPDU2PhasePropertiesEntry OBJECT-TYPE
+ SYNTAX RPDU2PhasePropertiesEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Properties of the currently queried Rack
+ PDU phase"
+ INDEX { rPDU2PhasePropertiesIndex }
+ ::= { rPDU2PhasePropertiesTable 1 }
+
+RPDU2PhasePropertiesEntry ::=
+ SEQUENCE {
+ rPDU2PhasePropertiesIndex INTEGER,
+ rPDU2PhasePropertiesModule INTEGER,
+ rPDU2PhasePropertiesNumber INTEGER
+ }
+
+rPDU2PhasePropertiesIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the Rack PDU phase properties
+ table entry"
+ ::= { rPDU2PhasePropertiesEntry 1 }
+
+rPDU2PhasePropertiesModule OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user-defined Rack PDU numeric ID"
+ ::= { rPDU2PhasePropertiesEntry 2 }
+
+rPDU2PhasePropertiesNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The numeric phase ID"
+ ::= { rPDU2PhasePropertiesEntry 3 }
+
+-- rPDU2 Phase Status
+
+rPDU2PhaseStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RPDU2PhaseStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A table of Rack PDU phase status data"
+ ::= { rPDU2Phase 3 }
+
+rPDU2PhaseStatusEntry OBJECT-TYPE
+ SYNTAX RPDU2PhaseStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Status data from currently queried Rack PDU
+ phase"
+ INDEX { rPDU2PhaseStatusIndex }
+ ::= { rPDU2PhaseStatusTable 1 }
+
+RPDU2PhaseStatusEntry ::=
+ SEQUENCE {
+ rPDU2PhaseStatusIndex INTEGER,
+ rPDU2PhaseStatusModule INTEGER,
+ rPDU2PhaseStatusNumber INTEGER,
+ rPDU2PhaseStatusLoadState INTEGER,
+ rPDU2PhaseStatusCurrent INTEGER,
+ rPDU2PhaseStatusVoltage INTEGER,
+ rPDU2PhaseStatusPower INTEGER,
+ rPDU2PhaseStatusApparentPower INTEGER,
+ rPDU2PhaseStatusPowerFactor INTEGER,
+ rPDU2PhaseStatusPeakCurrent INTEGER,
+ rPDU2PhaseStatusPeakCurrentTimestamp DisplayString,
+ rPDU2PhaseStatusPeakCurrentStartTime DisplayString
+ }
+
+rPDU2PhaseStatusIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the Rack PDU phase status table
+ entry"
+ ::= { rPDU2PhaseStatusEntry 1 }
+
+rPDU2PhaseStatusModule OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user-defined Rack PDU numeric ID"
+ ::= { rPDU2PhaseStatusEntry 2 }
+
+rPDU2PhaseStatusNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The numeric phase ID"
+ ::= { rPDU2PhaseStatusEntry 3 }
+
+rPDU2PhaseStatusLoadState OBJECT-TYPE
+ SYNTAX INTEGER {
+ lowLoad (1),
+ normal (2),
+ nearOverload (3),
+ overload (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the present load status of the Rack PDU
+ phase being queried"
+ ::= { rPDU2PhaseStatusEntry 4 }
+
+rPDU2PhaseStatusCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the current draw, in tenths of Amps, of the load
+ on the Rack PDU phase being queried"
+ ::= { rPDU2PhaseStatusEntry 5 }
+
+rPDU2PhaseStatusVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the Voltage, in Volts, of the Rack
+ PDU phase being queried. Models that do not support this
+ feature will respond to this OID with a value of -1."
+ ::= { rPDU2PhaseStatusEntry 6 }
+
+rPDU2PhaseStatusPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the load power, in hundredths of kilowatts (kW),
+ consumed on the Rack PDU phase being queried.
+ Models that do not support this feature will respond to this
+ OID with a value of -1."
+ ::= { rPDU2PhaseStatusEntry 7 }
+
+rPDU2PhaseStatusApparentPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the load apparent power, in hundredths of kiloVoltAmps (kVA),
+ consumed on the Rack PDU phase being queried.
+ Models that do not support this feature will respond to this
+ OID with a value of -1."
+ ::= { rPDU2PhaseStatusEntry 8 }
+
+rPDU2PhaseStatusPowerFactor OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the load power factor, in hundredths,
+ of the Rack PDU phase being queried.
+ Models that do not support this feature will respond to
+ this OID with a value of -1."
+ ::= { rPDU2PhaseStatusEntry 9 }
+
+
+rPDU2PhaseStatusPeakCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The peak current of the Rack PDU phase load in tenths of Amps"
+ ::= { rPDU2PhaseStatusEntry 10 }
+
+rPDU2PhaseStatusPeakCurrentTimestamp OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the date and time that the peak current occurred"
+ ::= { rPDU2PhaseStatusEntry 11 }
+
+rPDU2PhaseStatusPeakCurrentStartTime OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the date and time of the last phase peak current reset"
+ ::= { rPDU2PhaseStatusEntry 12 }
+
+-- rPDU2 Bank Data
+
+rPDU2BankTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of connected Rack PDU banks"
+ ::= { rPDU2 7}
+
+rPDU2Bank OBJECT IDENTIFIER ::= { rPDU2 8 }
+
+-- rPDU2 Bank Config
+
+rPDU2BankConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RPDU2BankConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A table of Rack PDU bank configuration data"
+ ::= { rPDU2Bank 1 }
+
+rPDU2BankConfigEntry OBJECT-TYPE
+ SYNTAX RPDU2BankConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Configuration data from currently queried
+ Rack PDU bank"
+ INDEX { rPDU2BankConfigIndex }
+ ::= { rPDU2BankConfigTable 1 }
+
+RPDU2BankConfigEntry ::=
+ SEQUENCE {
+ rPDU2BankConfigIndex INTEGER,
+ rPDU2BankConfigModule INTEGER,
+ rPDU2BankConfigNumber INTEGER,
+ rPDU2BankConfigOverloadRestriction INTEGER,
+ rPDU2BankConfigLowLoadCurrentThreshold INTEGER,
+ rPDU2BankConfigNearOverloadCurrentThreshold INTEGER,
+ rPDU2BankConfigOverloadCurrentThreshold INTEGER,
+ rPDU2BankConfigBankPeakCurrentReset INTEGER
+ }
+
+rPDU2BankConfigIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the Rack PDU bank configuration
+ table entry"
+ ::= { rPDU2BankConfigEntry 1 }
+
+rPDU2BankConfigModule OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user-defined Rack PDU numeric ID"
+ ::= { rPDU2BankConfigEntry 2 }
+
+rPDU2BankConfigNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The numeric bank ID"
+ ::= { rPDU2BankConfigEntry 3 }
+
+rPDU2BankConfigOverloadRestriction OBJECT-TYPE
+ SYNTAX INTEGER {
+ alwaysAllowTurnON (1),
+ restrictOnNearOverload (2),
+ restrictOnOverload (3),
+ notSupported (4)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "This OID controls the behavior of a Switched Rack PDU
+ bank when an overload condition is possible and
+ additional outlets are requested to be turned on.
+
+ Setting this OID to alwaysAllowTurnON (1) will always allow
+ the outlets on the corresponding bank to turn on.
+
+ Setting this OID to restrictOnNearOverload (2) will not allow
+ outlets on the corresponding bank to turn on if the
+ rPDU2BankConfigNearOverloadCurrentThreshold OID is exceeded.
+
+ Setting this OID to restrictOnOverload (3) will not allow
+ outlets on the corresponding bank to turn on if the
+ rPDU2BankConfigOverloadCurrentThreshold OID is exceeded.
+
+ Models that do not support this feature will respond to this OID
+ with a value of notSupported (4). Attempts to set this OID
+ in these models will fail."
+ ::= { rPDU2BankConfigEntry 4 }
+
+rPDU2BankConfigLowLoadCurrentThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "User-defined low load bank current
+ threshold in Amps"
+ ::= { rPDU2BankConfigEntry 5 }
+
+rPDU2BankConfigNearOverloadCurrentThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "User-defined near bank overload current warning
+ threshold in Amps"
+ ::= { rPDU2BankConfigEntry 6 }
+
+rPDU2BankConfigOverloadCurrentThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "User-defined bank overload current threshold
+ in Amps"
+ ::= { rPDU2BankConfigEntry 7 }
+
+ rPDU2BankConfigBankPeakCurrentReset OBJECT-TYPE
+ SYNTAX INTEGER {
+ noOperation (1),
+ reset (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to reset (2) will cause the existing peak current value
+ to be replaced by the present load current value.
+
+ Getting this OID will do nothing and return the noOperation(1) value."
+ ::= { rPDU2BankConfigEntry 8 }
+
+-- rPDU2 Bank Properties
+
+rPDU2BankPropertiesTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RPDU2BankPropertiesEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A table of Rack PDU bank properties"
+ ::= { rPDU2Bank 2 }
+
+rPDU2BankPropertiesEntry OBJECT-TYPE
+ SYNTAX RPDU2BankPropertiesEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Properties of the currently queried
+ Rack PDU bank"
+ INDEX { rPDU2BankPropertiesIndex }
+ ::= { rPDU2BankPropertiesTable 1 }
+
+RPDU2BankPropertiesEntry ::=
+ SEQUENCE {
+ rPDU2BankPropertiesIndex INTEGER,
+ rPDU2BankPropertiesModule INTEGER,
+ rPDU2BankPropertiesNumber INTEGER,
+ rPDU2BankPropertiesPhaseLayout Rpdu2OutletPhaseLayoutType,
+ rPDU2BankPropertiesBreakerRating INTEGER
+ }
+
+rPDU2BankPropertiesIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the Rack PDU bank properties
+ table entry"
+ ::= { rPDU2BankPropertiesEntry 1 }
+
+rPDU2BankPropertiesModule OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user-defined Rack PDU numeric ID"
+ ::= { rPDU2BankPropertiesEntry 2 }
+
+rPDU2BankPropertiesNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The numeric bank ID"
+ ::= { rPDU2BankPropertiesEntry 3 }
+
+rPDU2BankPropertiesPhaseLayout OBJECT-TYPE
+ SYNTAX Rpdu2OutletPhaseLayoutType
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID describes the outlet phase connections on
+ the referenced bank as follows:
+
+ seqPhase1ToNeutral(1) indicates that bank outlets are
+ wired from Phase 1 to Neutral.
+
+ seqPhase2ToNeutral(2) indicates that bank outlets are
+ wired from Phase 2 to Neutral.
+
+ seqPhase3ToNeutral(3) indicates that bank outlets are
+ wired from Phase 3 to Neutral.
+
+ seqPhase1ToPhase2(4) indicates that bank outlets are
+ wired from Phase 1 to Phase 2.
+
+ seqPhase2ToPhase3(5) indicates that bank outlets are
+ wired from Phase 2 to Phase 3.
+
+ seqPhase3ToPhase1(6) indicates that bank outlets are
+ wired from Phase 3 to Phase 1."
+ ::= { rPDU2BankPropertiesEntry 4 }
+
+
+rPDU2BankPropertiesBreakerRating OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "If bank circuit breakers are present on the device, this OID will return
+ the rating of the breaker in Amps."
+ ::= { rPDU2BankPropertiesEntry 5 }
+
+-- rPDU2 Bank Status
+
+rPDU2BankStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RPDU2BankStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A table of Rack PDU bank status data"
+ ::= { rPDU2Bank 3 }
+
+rPDU2BankStatusEntry OBJECT-TYPE
+ SYNTAX RPDU2BankStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Status data from currently queried Rack PDU
+ bank"
+ INDEX { rPDU2BankStatusIndex }
+ ::= { rPDU2BankStatusTable 1 }
+
+RPDU2BankStatusEntry ::=
+ SEQUENCE {
+ rPDU2BankStatusIndex INTEGER,
+ rPDU2BankStatusModule INTEGER,
+ rPDU2BankStatusNumber INTEGER,
+ rPDU2BankStatusLoadState INTEGER,
+ rPDU2BankStatusCurrent INTEGER,
+ rPDU2BankStatusPeakCurrent INTEGER,
+ rPDU2BankStatusPeakCurrentTimestamp DisplayString,
+ rPDU2BankStatusPeakCurrentStartTime DisplayString
+ }
+
+rPDU2BankStatusIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the Rack PDU bank status
+ table entry"
+ ::= { rPDU2BankStatusEntry 1 }
+
+rPDU2BankStatusModule OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user-defined Rack PDU numeric ID"
+ ::= { rPDU2BankStatusEntry 2 }
+
+rPDU2BankStatusNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The numeric bank ID"
+ ::= { rPDU2BankStatusEntry 3 }
+
+rPDU2BankStatusLoadState OBJECT-TYPE
+ SYNTAX INTEGER {
+ lowLoad (1),
+ normal (2),
+ nearOverload (3),
+ overload (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the present load status of the Rack PDU
+ bank being queried"
+ ::= { rPDU2BankStatusEntry 4 }
+
+rPDU2BankStatusCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the current draw, in tenths of Amps, of the load
+ on the Rack PDU bank being queried"
+ ::= { rPDU2BankStatusEntry 5 }
+
+rPDU2BankStatusPeakCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The peak current of the Rack PDU bank load in tenths of Amps"
+ ::= { rPDU2BankStatusEntry 6 }
+
+rPDU2BankStatusPeakCurrentTimestamp OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the date and time the bank peak current occurred"
+ ::= { rPDU2BankStatusEntry 7 }
+
+rPDU2BankStatusPeakCurrentStartTime OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the date and time of the last bank peak current reset"
+ ::= { rPDU2BankStatusEntry 8 }
+
+
+-- rPDU2 Outlet Data
+
+rPDU2Outlet OBJECT IDENTIFIER ::= { rPDU2 9 }
+
+-- rPDU2 Switched Outlet Data
+
+rPDU2OutletSwitchedTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of switched outlets on connected Rack PDUs"
+ ::= { rPDU2Outlet 1}
+
+rPDU2OutletSwitched OBJECT IDENTIFIER ::= { rPDU2Outlet 2 }
+
+-- rPDU2 Switched Outlet Config
+
+rPDU2OutletSwitchedConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RPDU2OutletSwitchedConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A table of Rack PDU switched outlet configuration data"
+ ::= { rPDU2OutletSwitched 1 }
+
+rPDU2OutletSwitchedConfigEntry OBJECT-TYPE
+ SYNTAX RPDU2OutletSwitchedConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Configuration data from currently queried
+ Rack PDU switched outlet"
+ INDEX { rPDU2OutletSwitchedConfigIndex }
+ ::= { rPDU2OutletSwitchedConfigTable 1 }
+
+RPDU2OutletSwitchedConfigEntry ::=
+ SEQUENCE {
+ rPDU2OutletSwitchedConfigIndex INTEGER,
+ rPDU2OutletSwitchedConfigModule INTEGER,
+ rPDU2OutletSwitchedConfigName DisplayString,
+ rPDU2OutletSwitchedConfigNumber INTEGER,
+ rPDU2OutletSwitchedConfigPowerOnTime INTEGER,
+ rPDU2OutletSwitchedConfigPowerOffTime INTEGER,
+ rPDU2OutletSwitchedConfigRebootDuration INTEGER,
+ rPDU2OutletSwitchedConfigExternalLink DisplayString
+ }
+
+rPDU2OutletSwitchedConfigIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the Rack PDU switched outlet
+ configuration table entry"
+ ::= { rPDU2OutletSwitchedConfigEntry 1 }
+
+rPDU2OutletSwitchedConfigModule OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user-defined Rack PDU numeric ID"
+ ::= { rPDU2OutletSwitchedConfigEntry 2 }
+
+rPDU2OutletSwitchedConfigName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The user-defined switched outlet ID string"
+ ::= { rPDU2OutletSwitchedConfigEntry 3 }
+
+rPDU2OutletSwitchedConfigNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The numeric switched outlet ID"
+ ::= { rPDU2OutletSwitchedConfigEntry 4 }
+
+rPDU2OutletSwitchedConfigPowerOnTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The amount of delay, in seconds, between when
+ power is provided to the Rack PDU and when
+ this switched outlet starts providing power.
+ Range -1...300 where -1 = Never power on,
+ 0 = immediate power on, and 1-300 = seconds to
+ delay."
+ ::= { rPDU2OutletSwitchedConfigEntry 5 }
+
+rPDU2OutletSwitchedConfigPowerOffTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The amount of time, in seconds, this outlet will
+ delay powering off.
+ Range -1...360 where -1 = Never power off,
+ 0 = immediate power off, and 1-360 = seconds to
+ delay."
+ ::= { rPDU2OutletSwitchedConfigEntry 6 }
+
+rPDU2OutletSwitchedConfigRebootDuration OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "After turning power off during a reboot sequence,
+ the amount of time to wait before turning power
+ to this outlet back on.
+ Range 5-60 seconds delay."
+ ::= { rPDU2OutletSwitchedConfigEntry 7 }
+
+
+rPDU2OutletSwitchedConfigExternalLink OBJECT-TYPE
+SYNTAX DisplayString
+ACCESS read-write
+STATUS mandatory
+DESCRIPTION
+ "User-defined external device web link.
+ Possible use cases could be the IP address of the external device
+ plugged into the outlet or its manufacturer web page for convenient
+ support such as user manuals, specifications, drivers, etc."
+::= { rPDU2OutletSwitchedConfigEntry 8 }
+
+
+-- rPDU2 Switched Outlet Config
+
+rPDU2OutletSwitchedPropertiesTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RPDU2OutletSwitchedPropertiesEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A table of Rack PDU switched outlet properties"
+ ::= { rPDU2OutletSwitched 2 }
+
+rPDU2OutletSwitchedPropertiesEntry OBJECT-TYPE
+ SYNTAX RPDU2OutletSwitchedPropertiesEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Properties of the currently queried Rack PDU
+ switched outlet"
+ INDEX { rPDU2OutletSwitchedPropertiesIndex }
+ ::= { rPDU2OutletSwitchedPropertiesTable 1 }
+
+RPDU2OutletSwitchedPropertiesEntry ::=
+ SEQUENCE {
+ rPDU2OutletSwitchedPropertiesIndex INTEGER,
+ rPDU2OutletSwitchedPropertiesModule INTEGER,
+ rPDU2OutletSwitchedPropertiesName DisplayString,
+ rPDU2OutletSwitchedPropertiesNumber INTEGER,
+ rPDU2OutletSwitchedPropertiesPhaseLayout Rpdu2OutletPhaseLayoutType,
+ rPDU2OutletSwitchedPropertiesBank INTEGER
+ }
+
+rPDU2OutletSwitchedPropertiesIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the Rack PDU switched outlet
+ properties table entry"
+ ::= { rPDU2OutletSwitchedPropertiesEntry 1 }
+
+rPDU2OutletSwitchedPropertiesModule OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user-defined Rack PDU numeric ID"
+ ::= { rPDU2OutletSwitchedPropertiesEntry 2 }
+
+rPDU2OutletSwitchedPropertiesName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user-defined switched outlet ID string"
+ ::= { rPDU2OutletSwitchedPropertiesEntry 3 }
+
+rPDU2OutletSwitchedPropertiesNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The numeric switched outlet ID"
+ ::= { rPDU2OutletSwitchedPropertiesEntry 4 }
+
+rPDU2OutletSwitchedPropertiesPhaseLayout OBJECT-TYPE
+ SYNTAX Rpdu2OutletPhaseLayoutType
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID describes the phase connections of
+ the referenced outlet as follows:
+
+ seqPhase1ToNeutral(1) indicates that the outlet is
+ wired from Phase 1 to Neutral.
+
+ seqPhase2ToNeutral(2) indicates that the outlet is
+ wired from Phase 2 to Neutral.
+
+ seqPhase3ToNeutral(3) indicates that the outlet is
+ wired from Phase 3 to Neutral.
+
+ seqPhase1ToPhase2(4) indicates that the outlet is
+ wired from Phase 1 to Phase 2.
+
+ seqPhase2ToPhase3(5) indicates that the outlet is
+ wired from Phase 2 to Phase 3.
+
+ seqPhase3ToPhase1(6) indicates that the outlet is
+ wired from Phase 3 to Phase 1."
+ ::= { rPDU2OutletSwitchedPropertiesEntry 5 }
+
+rPDU2OutletSwitchedPropertiesBank OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The numeric bank ID"
+ ::= { rPDU2OutletSwitchedPropertiesEntry 6 }
+
+-- rPDU2 Switched Outlet Status
+
+rPDU2OutletSwitchedStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RPDU2OutletSwitchedStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A table of Rack PDU switched outlet status
+ information"
+ ::= { rPDU2OutletSwitched 3 }
+
+rPDU2OutletSwitchedStatusEntry OBJECT-TYPE
+ SYNTAX RPDU2OutletSwitchedStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Status information for currently queried
+ Rack PDU switched outlet"
+ INDEX { rPDU2OutletSwitchedStatusIndex }
+ ::= { rPDU2OutletSwitchedStatusTable 1 }
+
+RPDU2OutletSwitchedStatusEntry ::=
+ SEQUENCE {
+ rPDU2OutletSwitchedStatusIndex INTEGER,
+ rPDU2OutletSwitchedStatusModule INTEGER,
+ rPDU2OutletSwitchedStatusName DisplayString,
+ rPDU2OutletSwitchedStatusNumber INTEGER,
+ rPDU2OutletSwitchedStatusState INTEGER,
+ rPDU2OutletSwitchedStatusCommandPending INTEGER,
+ rPDU2OutletSwitchedStatusExternalLink DisplayString
+ }
+
+rPDU2OutletSwitchedStatusIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the Rack PDU switched outlet
+ status information table entry"
+ ::= { rPDU2OutletSwitchedStatusEntry 1 }
+
+rPDU2OutletSwitchedStatusModule OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user-defined Rack PDU numeric ID"
+ ::= { rPDU2OutletSwitchedStatusEntry 2 }
+
+rPDU2OutletSwitchedStatusName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user-defined switched outlet ID string"
+ ::= { rPDU2OutletSwitchedStatusEntry 3 }
+
+rPDU2OutletSwitchedStatusNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The numeric switched outlet ID"
+ ::= { rPDU2OutletSwitchedStatusEntry 4 }
+
+rPDU2OutletSwitchedStatusState OBJECT-TYPE
+ SYNTAX INTEGER {
+ off (1),
+ on (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the present switch state of the Rack
+ PDU switched outlet being queried"
+ ::= { rPDU2OutletSwitchedStatusEntry 5 }
+
+rPDU2OutletSwitchedStatusCommandPending OBJECT-TYPE
+ SYNTAX INTEGER {
+ commandPending (1),
+ noCommandPending (2),
+ commandPendingUnknown (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates whether or not the device is
+ processing a command for this outlet.
+
+ If the commandPendingUnknown (3) value is
+ returned, all devices powered by the Rack PDU
+ should be shut down. The Rack PDU's power
+ should then be cycled to clear this condition."
+ ::= { rPDU2OutletSwitchedStatusEntry 6 }
+
+
+rPDU2OutletSwitchedStatusExternalLink OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Each RPDU outlet can have its own external web URL link.
+ This can be configured in the rPDU2OutletSwitchedConfigExternalLink OID.
+ When this link is clicked in the web interface, the linked URL will
+ open in the web browser."
+ ::= { rPDU2OutletSwitchedStatusEntry 7 }
+
+
+-- rPDU2 Switched Outlet Control
+
+rPDU2OutletSwitchedControlTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RPDU2OutletSwitchedControlEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A table of Rack PDU switched outlet control
+ data"
+ ::= { rPDU2OutletSwitched 4 }
+
+rPDU2OutletSwitchedControlEntry OBJECT-TYPE
+ SYNTAX RPDU2OutletSwitchedControlEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Control data for currently queried Rack
+ PDU switched outlet"
+ INDEX { rPDU2OutletSwitchedControlIndex }
+ ::= { rPDU2OutletSwitchedControlTable 1 }
+
+RPDU2OutletSwitchedControlEntry ::=
+ SEQUENCE {
+ rPDU2OutletSwitchedControlIndex INTEGER,
+ rPDU2OutletSwitchedControlModule INTEGER,
+ rPDU2OutletSwitchedControlName DisplayString,
+ rPDU2OutletSwitchedControlNumber INTEGER,
+ rPDU2OutletSwitchedControlCommand INTEGER
+ }
+
+rPDU2OutletSwitchedControlIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the Rack PDU switched outlet
+ control data table entry"
+ ::= { rPDU2OutletSwitchedControlEntry 1 }
+
+rPDU2OutletSwitchedControlModule OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user-defined Rack PDU numeric ID"
+ ::= { rPDU2OutletSwitchedControlEntry 2 }
+
+rPDU2OutletSwitchedControlName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user-defined switched outlet ID string"
+ ::= { rPDU2OutletSwitchedControlEntry 3 }
+
+rPDU2OutletSwitchedControlNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The numeric switched outlet ID"
+ ::= { rPDU2OutletSwitchedControlEntry 4 }
+
+rPDU2OutletSwitchedControlCommand OBJECT-TYPE
+ SYNTAX INTEGER {
+ immediateOn (1),
+ immediateOff (2),
+ immediateReboot (3),
+ outletUnknown (4),
+ delayedOn (5),
+ delayedOff (6),
+ delayedReboot (7),
+ cancelPendingCommand (8)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this variable will return the outlet state. If
+ the outlet is on, the immediateOn (1) value will be returned.
+ If the outlet is off, the immediateOff (2) value will be
+ returned. If the state of the outlet cannot be
+ determined, the outletUnknown (4) value will be returned.
+ If the outletUnknown condition should occur, all devices
+ powered by the PDU should be shut down. The PDU's power
+ should then be cycled to clear this condition.
+
+ Setting this variable to immediateOn (1) will immediately turn
+ the outlet on.
+
+ Setting this variable to immediateOff (2) will immediately turn
+ the outlet off.
+
+ Setting this variable to immediateReboot (3) will cause the
+ Switched Rack PDU to perform an immediateOff command, wait the
+ rPDU2OutletSwitchedConfigRebootDuration OID time, and then perform an
+ immediateOn command.
+
+ Setting this variable to delayedOn (5) will turn the outlet on
+ after the rPDU2OutletSwitchedConfigPowerOnTime OID time has elapsed.
+
+ Setting this variable to delayedOff (6) will turn the outlet off
+ after the rPDU2OutletSwitchedConfigPowerOffTime OID time has elapsed.
+
+ Setting this variable to delayedReboot (7) will cause the
+ Switched Rack PDU to perform a delayedOff command, wait the
+ rPDU2OutletSwitchedConfigRebootDuration OID time, and then perform a
+ delayedOn command.
+
+ Setting this variable to cancelPendingCommand (8) will cause any
+ pending command to this outlet to be cancelled."
+ ::= { rPDU2OutletSwitchedControlEntry 5 }
+
+-- rPDU2 Metered Outlet Data
+
+rPDU2OutletMeteredTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of metered outlets on connect Rack PDUs"
+ ::= { rPDU2Outlet 3}
+
+rPDU2OutletMetered OBJECT IDENTIFIER ::= { rPDU2Outlet 4 }
+
+-- rPDU2 Metered Outlet Config
+
+rPDU2OutletMeteredConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RPDU2OutletMeteredConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A table of Rack PDU metered outlet configuration data"
+ ::= { rPDU2OutletMetered 1 }
+
+rPDU2OutletMeteredConfigEntry OBJECT-TYPE
+ SYNTAX RPDU2OutletMeteredConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Configuration data from currently queried
+ Rack PDU metered outlet"
+ INDEX { rPDU2OutletMeteredConfigIndex }
+ ::= { rPDU2OutletMeteredConfigTable 1 }
+
+RPDU2OutletMeteredConfigEntry ::=
+ SEQUENCE {
+ rPDU2OutletMeteredConfigIndex INTEGER,
+ rPDU2OutletMeteredConfigModule INTEGER,
+ rPDU2OutletMeteredConfigName DisplayString,
+ rPDU2OutletMeteredConfigNumber INTEGER,
+ rPDU2OutletMeteredConfigLowLoadCurrentThreshold INTEGER,
+ rPDU2OutletMeteredConfigNearOverloadCurrentThreshold INTEGER,
+ rPDU2OutletMeteredConfigOverloadCurrentThreshold INTEGER,
+ rPDU2OutletMeteredConfigExternalLink DisplayString
+ }
+
+rPDU2OutletMeteredConfigIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the Rack PDU metered outlet
+ configuration table entry"
+ ::= { rPDU2OutletMeteredConfigEntry 1 }
+
+rPDU2OutletMeteredConfigModule OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user-defined Rack PDU numeric ID"
+ ::= { rPDU2OutletMeteredConfigEntry 2 }
+
+rPDU2OutletMeteredConfigName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The user-defined metered outlet ID string"
+ ::= { rPDU2OutletMeteredConfigEntry 3 }
+
+rPDU2OutletMeteredConfigNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The numeric switched outlet ID"
+ ::= { rPDU2OutletMeteredConfigEntry 4 }
+
+rPDU2OutletMeteredConfigLowLoadCurrentThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "User-defined low load outlet current threshold in Watts"
+ ::= { rPDU2OutletMeteredConfigEntry 5 }
+
+rPDU2OutletMeteredConfigNearOverloadCurrentThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "User-defined near outlet overload warning threshold
+ in Watts"
+ ::= { rPDU2OutletMeteredConfigEntry 6 }
+
+rPDU2OutletMeteredConfigOverloadCurrentThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "User-defined outlet overload current threshold in Watts"
+ ::= { rPDU2OutletMeteredConfigEntry 7 }
+
+
+rPDU2OutletMeteredConfigExternalLink OBJECT-TYPE
+SYNTAX DisplayString
+ACCESS read-write
+STATUS mandatory
+DESCRIPTION
+ "User-defined external device web link.
+ Possible use cases could be the IP address of the external device
+ plugged into the outlet or its manufacturer web page for convenient
+ support such as user manuals, specifications, drivers, etc."
+::= { rPDU2OutletMeteredConfigEntry 8 }
+
+-- rPDU2 Metered Outlet Properties
+
+rPDU2OutletMeteredPropertiesTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RPDU2OutletMeteredPropertiesEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A table of Rack PDU metered outlet properties"
+ ::= { rPDU2OutletMetered 2 }
+
+rPDU2OutletMeteredPropertiesEntry OBJECT-TYPE
+ SYNTAX RPDU2OutletMeteredPropertiesEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Properties of currently queried Rack PDU
+ metered outlet"
+ INDEX { rPDU2OutletMeteredPropertiesIndex }
+ ::= { rPDU2OutletMeteredPropertiesTable 1 }
+
+RPDU2OutletMeteredPropertiesEntry ::=
+ SEQUENCE {
+ rPDU2OutletMeteredPropertiesIndex INTEGER,
+ rPDU2OutletMeteredPropertiesModule INTEGER,
+ rPDU2OutletMeteredPropertiesName DisplayString,
+ rPDU2OutletMeteredPropertiesNumber INTEGER,
+ rPDU2OutletMeteredPropertiesLayout Rpdu2OutletPhaseLayoutType,
+ rPDU2OutletMeteredPropertiesPowerRating INTEGER,
+ rPDU2OutletMeteredPropertiesBank INTEGER
+ }
+
+rPDU2OutletMeteredPropertiesIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the Rack PDU metered properties table
+ entry"
+ ::= { rPDU2OutletMeteredPropertiesEntry 1 }
+
+rPDU2OutletMeteredPropertiesModule OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user-defined Rack PDU numeric ID"
+ ::= { rPDU2OutletMeteredPropertiesEntry 2 }
+
+rPDU2OutletMeteredPropertiesName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user-defined metered outlet ID string"
+ ::= { rPDU2OutletMeteredPropertiesEntry 3 }
+
+rPDU2OutletMeteredPropertiesNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The numeric metered outlet ID"
+ ::= { rPDU2OutletMeteredPropertiesEntry 4 }
+
+rPDU2OutletMeteredPropertiesLayout OBJECT-TYPE
+ SYNTAX Rpdu2OutletPhaseLayoutType
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID describes the phase connections of
+ the referenced outlet as follows:
+
+ seqPhase1ToNeutral(1) indicates that the outlet is
+ wired from Phase 1 to Neutral.
+
+ seqPhase2ToNeutral(2) indicates that the outlet is
+ wired from Phase 2 to Neutral.
+
+ seqPhase3ToNeutral(3) indicates that the outlet is
+ wired from Phase 3 to Neutral.
+
+ seqPhase1ToPhase2(4) indicates that the outlet is
+ wired from Phase 1 to Phase 2.
+
+ seqPhase2ToPhase3(5) indicates that the outlet is
+ wired from Phase 2 to Phase 3.
+
+ seqPhase3ToPhase1(6) indicates that the outlet is
+ wired from Phase 3 to Phase 1."
+ ::= { rPDU2OutletMeteredPropertiesEntry 5 }
+
+rPDU2OutletMeteredPropertiesPowerRating OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Maximum power rating of Rack PDU metered outlet"
+ ::= { rPDU2OutletMeteredPropertiesEntry 6 }
+
+rPDU2OutletMeteredPropertiesBank OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This outlet's numeric bank ID"
+ ::= { rPDU2OutletMeteredPropertiesEntry 7 }
+
+-- rPDU2 Metered Outlet Status
+
+rPDU2OutletMeteredStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RPDU2OutletMeteredStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A table of Rack PDU metered outlet status data"
+ ::= { rPDU2OutletMetered 3 }
+
+rPDU2OutletMeteredStatusEntry OBJECT-TYPE
+ SYNTAX RPDU2OutletMeteredStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Status data from currently queried Rack PDU
+ metered outlet"
+ INDEX { rPDU2OutletMeteredStatusIndex }
+ ::= { rPDU2OutletMeteredStatusTable 1 }
+
+RPDU2OutletMeteredStatusEntry ::=
+ SEQUENCE {
+ rPDU2OutletMeteredStatusIndex INTEGER,
+ rPDU2OutletMeteredStatusModule INTEGER,
+ rPDU2OutletMeteredStatusName DisplayString,
+ rPDU2OutletMeteredStatusNumber INTEGER,
+ rPDU2OutletMeteredStatusState INTEGER,
+ rPDU2OutletMeteredStatusCurrent INTEGER,
+ rPDU2OutletMeteredStatusPower INTEGER,
+ rPDU2OutletMeteredStatusPeakPower INTEGER,
+ rPDU2OutletMeteredStatusPeakPowerTimestamp DisplayString,
+ rPDU2OutletMeteredStatusPeakPowerStartTime DisplayString,
+ rPDU2OutletMeteredStatusEnergy INTEGER,
+ rPDU2OutletMeteredStatusReceptacleType DisplayString,
+ rPDU2OutletMeteredStatusExternalLink DisplayString
+ }
+
+rPDU2OutletMeteredStatusIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the Rack PDU metered status table
+ entry"
+ ::= { rPDU2OutletMeteredStatusEntry 1 }
+
+rPDU2OutletMeteredStatusModule OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user-defined Rack PDU numeric ID"
+ ::= { rPDU2OutletMeteredStatusEntry 2 }
+
+rPDU2OutletMeteredStatusName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user-defined metered outlet ID string"
+ ::= { rPDU2OutletMeteredStatusEntry 3 }
+
+rPDU2OutletMeteredStatusNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The numeric metered outlet ID"
+ ::= { rPDU2OutletMeteredStatusEntry 4 }
+
+rPDU2OutletMeteredStatusState OBJECT-TYPE
+ SYNTAX INTEGER {
+ lowLoad (1),
+ normal (2),
+ nearOverload (3),
+ overload (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the present load status of the Rack
+ PDU metered outlet being queried"
+ ::= { rPDU2OutletMeteredStatusEntry 5 }
+
+rPDU2OutletMeteredStatusCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the current draw, in tenths
+ of Amps, of the load on the Rack PDU
+ outlet being queried"
+ ::= { rPDU2OutletMeteredStatusEntry 6 }
+
+rPDU2OutletMeteredStatusPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the power draw of the load
+ on the Rack PDU outlet being queried"
+ ::= { rPDU2OutletMeteredStatusEntry 7 }
+
+rPDU2OutletMeteredStatusPeakPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the peak power load draw
+ on the Rack PDU outlet being queried"
+ ::= { rPDU2OutletMeteredStatusEntry 8 }
+
+rPDU2OutletMeteredStatusPeakPowerTimestamp OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the date and time that this metered
+ outlet's peak power consumption occurred"
+ ::= { rPDU2OutletMeteredStatusEntry 9 }
+
+rPDU2OutletMeteredStatusPeakPowerStartTime OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the start date and time that this metered
+ outlet began recording peak power observations"
+ ::= { rPDU2OutletMeteredStatusEntry 10 }
+
+rPDU2OutletMeteredStatusEnergy OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A user resettable energy meter measuring Rack PDU load
+ energy consumption in tenths of kilowatt-hours"
+ ::= { rPDU2OutletMeteredStatusEntry 11 }
+
+
+rPDU2OutletMeteredStatusReceptacleType OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates receptacle type for the outlet."
+ ::= { rPDU2OutletMeteredStatusEntry 12 }
+
+
+rPDU2OutletMeteredStatusExternalLink OBJECT-TYPE
+SYNTAX DisplayString
+ACCESS read-only
+STATUS mandatory
+DESCRIPTION
+ "Each RPDU outlet can have its own external web URL link.
+ This can be configured in the rPDU2OutletMeteredConfigExternalLink OID.
+ When this link is clicked in the web interface, the linked URL will
+ open in the web browser."
+::= { rPDU2OutletMeteredStatusEntry 13 }
+
+-- rPDU2 Sensor Data
+
+rPDU2Sensor OBJECT IDENTIFIER ::= { rPDU2 10 }
+
+-- rPDU2 Temperature and Humidity Sensor Data
+
+rPDU2SensorTempHumidityTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of connected temperature-humidity sensors"
+ ::= { rPDU2Sensor 1}
+
+rPDU2SensorTempHumidity OBJECT IDENTIFIER ::= { rPDU2Sensor 2 }
+
+-- rPDU2 Temperature and Humidity Sensor Config
+
+rPDU2SensorTempHumidityConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RPDU2SensorTempHumidityConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A table of temperature-humidity sensor
+ configuration data"
+ ::= { rPDU2SensorTempHumidity 1 }
+
+rPDU2SensorTempHumidityConfigEntry OBJECT-TYPE
+ SYNTAX RPDU2SensorTempHumidityConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Configuration data from temperature-humidity sensor
+ being queried"
+ INDEX { rPDU2SensorTempHumidityConfigIndex }
+ ::= { rPDU2SensorTempHumidityConfigTable 1 }
+
+RPDU2SensorTempHumidityConfigEntry ::=
+ SEQUENCE {
+ rPDU2SensorTempHumidityConfigIndex INTEGER,
+ rPDU2SensorTempHumidityConfigModule INTEGER,
+ rPDU2SensorTempHumidityConfigName DisplayString,
+ rPDU2SensorTempHumidityConfigNumber INTEGER,
+ rPDU2SensorTempHumidityConfigTemperatureAlarmEnable INTEGER,
+ rPDU2SensorTempHumidityConfigHumidityAlarmEnable INTEGER,
+ rPDU2SensorTempHumidityConfigTempMaxThreshF INTEGER,
+ rPDU2SensorTempHumidityConfigTempHighThreshF INTEGER,
+ rPDU2SensorTempHumidityConfigTempHysteresisF INTEGER,
+ rPDU2SensorTempHumidityConfigTempMaxThreshC INTEGER,
+ rPDU2SensorTempHumidityConfigTempHighThreshC INTEGER,
+ rPDU2SensorTempHumidityConfigTempHysteresisC INTEGER,
+ rPDU2SensorTempHumidityConfigHumidityLowThresh INTEGER,
+ rPDU2SensorTempHumidityConfigHumidityMinThresh INTEGER,
+ rPDU2SensorTempHumidityConfigHumidityHysteresis INTEGER,
+ rPDU2SensorTempHumidityConfigTempPeakReset INTEGER
+ }
+
+rPDU2SensorTempHumidityConfigIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the temperature-humidity sensor
+ configuration data table entry"
+ ::= { rPDU2SensorTempHumidityConfigEntry 1 }
+
+rPDU2SensorTempHumidityConfigModule OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user-defined Rack PDU numeric ID"
+ ::= { rPDU2SensorTempHumidityConfigEntry 2 }
+
+rPDU2SensorTempHumidityConfigName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The user-defined temperature-humidity
+ sensor ID string"
+ ::= { rPDU2SensorTempHumidityConfigEntry 3 }
+
+rPDU2SensorTempHumidityConfigNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature-humidity sensor numeric ID"
+ ::= { rPDU2SensorTempHumidityConfigEntry 4 }
+
+rPDU2SensorTempHumidityConfigTemperatureAlarmEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled (1),
+ enabled (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID enables or disables generation
+ of sensor temperature alarm.
+
+ Getting this OID returns the current value of
+ the temperature alarm enable."
+ ::= { rPDU2SensorTempHumidityConfigEntry 5 }
+
+rPDU2SensorTempHumidityConfigHumidityAlarmEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled (1),
+ enabled (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID enables or disables generation
+ of sensor humidity alarm.
+
+ Getting this OID returns the current value of
+ the humidity alarm enable."
+ ::= { rPDU2SensorTempHumidityConfigEntry 6 }
+
+rPDU2SensorTempHumidityConfigTempMaxThreshF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor maximum temperature alarm threshold in
+ Fahrenheit. Attempting to set this OID to a
+ value less than or equal to that of
+ rPDU2SensorTempHumidityConfigTempHighThreshF
+ will result in an error."
+ ::= { rPDU2SensorTempHumidityConfigEntry 7 }
+
+rPDU2SensorTempHumidityConfigTempHighThreshF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor high temperature warning alarm threshold
+ in Fahrenheit. Attempting to set this OID to a
+ value greater than or equal to that of
+ rPDU2SensorTempHumidityConfigTempMaxThreshF
+ will result in an error."
+ ::= { rPDU2SensorTempHumidityConfigEntry 8 }
+
+rPDU2SensorTempHumidityConfigTempHysteresisF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor temperature hysteresis setting in Fahrenheit"
+ ::= { rPDU2SensorTempHumidityConfigEntry 9 }
+
+rPDU2SensorTempHumidityConfigTempMaxThreshC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor maximum temperature alarm threshold
+ in Celsius. Attempting to set this OID to a
+ value less than or equal to that of
+ rPDU2SensorTempHumidityConfigTempHighThreshC
+ will result in an error."
+ ::= { rPDU2SensorTempHumidityConfigEntry 10 }
+
+rPDU2SensorTempHumidityConfigTempHighThreshC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor high temperature warning alarm threshold
+ in Celsius. Attempting to set this OID to a
+ value greater than or equal to that of
+ rPDU2SensorTempHumidityConfigTempMaxThreshC
+ will result in an error."
+ ::= { rPDU2SensorTempHumidityConfigEntry 11 }
+
+rPDU2SensorTempHumidityConfigTempHysteresisC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor temperature hysteresis setting in Celsius"
+ ::= { rPDU2SensorTempHumidityConfigEntry 12 }
+
+rPDU2SensorTempHumidityConfigHumidityLowThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor low humidity warning alarm threshold in percent
+ relative humidity. Attempting to set this OID to a
+ value less than or equal to that of
+ rPDU2SensorTempHumidityConfigHumidityMinThresh
+ will result in an error. Must be between 15% and 90%"
+ ::= { rPDU2SensorTempHumidityConfigEntry 13 }
+
+rPDU2SensorTempHumidityConfigHumidityMinThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor minimum humidity alarm threshold in percent
+ relative humidity. Attempting to set this OID to a
+ value greater than or equal to that of
+ rPDU2SensorTempHumidityConfigHumidityLowThresh
+ will result in an error. Must be between 15% and 90%"
+ ::= { rPDU2SensorTempHumidityConfigEntry 14 }
+
+rPDU2SensorTempHumidityConfigHumidityHysteresis OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor humidity hysteresis setting in percent relative
+ humidity"
+ ::= { rPDU2SensorTempHumidityConfigEntry 15 }
+
+rPDU2SensorTempHumidityConfigTempPeakReset OBJECT-TYPE
+ SYNTAX INTEGER {
+ noOperation (1),
+ reset (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to reset (2) will cause the existing peak temperature
+ to be replaced by the present temperature reading.
+
+ Getting this OID will do nothing and return the noOperation(1) value."
+ ::= { rPDU2SensorTempHumidityConfigEntry 16}
+
+
+-- rPDU2 Temperature and Humidity Sensor Status
+
+rPDU2SensorTempHumidityStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RPDU2SensorTempHumidityStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A table of temperature-humidity sensor status data"
+ ::= { rPDU2SensorTempHumidity 2 }
+
+rPDU2SensorTempHumidityStatusEntry OBJECT-TYPE
+ SYNTAX RPDU2SensorTempHumidityStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Status information from temperature-humidity sensor
+ being queried"
+ INDEX { rPDU2SensorTempHumidityStatusIndex }
+ ::= { rPDU2SensorTempHumidityStatusTable 1 }
+
+RPDU2SensorTempHumidityStatusEntry ::=
+ SEQUENCE {
+ rPDU2SensorTempHumidityStatusIndex INTEGER,
+ rPDU2SensorTempHumidityStatusModule INTEGER,
+ rPDU2SensorTempHumidityStatusName DisplayString,
+ rPDU2SensorTempHumidityStatusNumber INTEGER,
+ rPDU2SensorTempHumidityStatusType INTEGER,
+ rPDU2SensorTempHumidityStatusCommStatus INTEGER,
+ rPDU2SensorTempHumidityStatusTempF INTEGER,
+ rPDU2SensorTempHumidityStatusTempC INTEGER,
+ rPDU2SensorTempHumidityStatusTempStatus INTEGER,
+ rPDU2SensorTempHumidityStatusRelativeHumidity INTEGER,
+ rPDU2SensorTempHumidityStatusHumidityStatus INTEGER,
+ rPDU2SensorTempHumidityStatusTempPeakF INTEGER,
+ rPDU2SensorTempHumidityStatusTempPeakC INTEGER,
+ rPDU2SensorTempHumidityStatusTempPeakStartTime DisplayString,
+ rPDU2SensorTempHumidityStatusTempPeakTimestamp DisplayString
+ }
+
+rPDU2SensorTempHumidityStatusIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the temperature-humidity
+ status data table entry"
+ ::= { rPDU2SensorTempHumidityStatusEntry 1 }
+
+rPDU2SensorTempHumidityStatusModule OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user-defined Rack PDU numeric ID"
+ ::= { rPDU2SensorTempHumidityStatusEntry 2 }
+
+rPDU2SensorTempHumidityStatusName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user-defined temperature-humidity
+ sensor ID string"
+ ::= { rPDU2SensorTempHumidityStatusEntry 3 }
+
+rPDU2SensorTempHumidityStatusNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature-humidity sensor numeric ID"
+ ::= { rPDU2SensorTempHumidityStatusEntry 4 }
+
+rPDU2SensorTempHumidityStatusType OBJECT-TYPE
+ SYNTAX INTEGER {
+ temperatureOnly (1),
+ temperatureHumidity (2),
+ commsLost (3),
+ notInstalled (4)
+
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The type of the sensor"
+ ::= { rPDU2SensorTempHumidityStatusEntry 5 }
+
+rPDU2SensorTempHumidityStatusCommStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ notInstalled (1),
+ commsOK (2),
+ commsLost (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The communications status of the sensor"
+ ::= { rPDU2SensorTempHumidityStatusEntry 6 }
+
+rPDU2SensorTempHumidityStatusTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor temperature reading in tenths of degrees Fahrenheit"
+ ::= { rPDU2SensorTempHumidityStatusEntry 7 }
+
+rPDU2SensorTempHumidityStatusTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor temperature reading in tenths of degrees Celsius"
+ ::= { rPDU2SensorTempHumidityStatusEntry 8 }
+
+rPDU2SensorTempHumidityStatusTempStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ notPresent (1),
+ belowMin (2),
+ belowLow (3),
+ normal (4),
+ aboveHigh (5),
+ aboveMax (6)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID reports the current state of the temperature probe.
+
+ A notPresent (1) response indicates that no probe is attached.
+ A belowMin (2) response indicates that the probe is present and
+ its measured temperature lies below the minimum threshold.
+ A belowLow (3) response indicates that the probe is present and
+ its measured temperature lies below the low threshold.
+ A normal (4) response indicates that the probe is present
+ and its measured temperature lies within all temperature thresholds.
+ An aboveHigh (5) response indicates that the probe is present
+ and is measuring a temperature above the high threshold.
+ An aboveMax (6) response indicates that the probe is present
+ and is measuring a temperature above the max threshold."
+ ::= { rPDU2SensorTempHumidityStatusEntry 9 }
+
+rPDU2SensorTempHumidityStatusRelativeHumidity OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor humidity reading in percent relative humidity"
+ ::= { rPDU2SensorTempHumidityStatusEntry 10 }
+
+rPDU2SensorTempHumidityStatusHumidityStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ notPresent (1),
+ belowMin (2),
+ belowLow (3),
+ normal (4),
+ aboveHigh (5),
+ aboveMax (6)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID reports the current state of the humidity probe.
+
+ A notPresent (1) response indicates that no probe is attached.
+ A belowMin (2) response indicates that the probe is present and
+ its measured humidity lies below the minimum threshold.
+ A belowLow (3) response indicates that the probe is present and
+ its measured humidity lies below the low threshold.
+ A normal (4) response indicates that the probe is present
+ and its measured humidity lies within all humidity thresholds.
+ An aboveHigh (5) response indicates that the probe is present
+ and is measuring a humidity above the high threshold.
+ An aboveMax (6) response indicates that the probe is present
+ and is measuring a humidity above the max threshold."
+ ::= { rPDU2SensorTempHumidityStatusEntry 11 }
+
+rPDU2SensorTempHumidityStatusTempPeakF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor peak temperature in tenths of degrees Fahrenheit"
+ ::= { rPDU2SensorTempHumidityStatusEntry 12 }
+
+rPDU2SensorTempHumidityStatusTempPeakC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor peak temperature in tenths of degrees Celsius"
+ ::= { rPDU2SensorTempHumidityStatusEntry 13 }
+
+
+rPDU2SensorTempHumidityStatusTempPeakTimestamp OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the date and time that the peak temperature occurred"
+ ::= { rPDU2SensorTempHumidityStatusEntry 14 }
+
+rPDU2SensorTempHumidityStatusTempPeakStartTime OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the date and time of the last temperature peak reset"
+ ::= { rPDU2SensorTempHumidityStatusEntry 15 }
+
+-- rPDU2 Discrete Sensor Data
+
+rPDU2SensorDiscreteTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of connected discrete sensors"
+ ::= { rPDU2Sensor 3}
+
+rPDU2SensorDiscrete OBJECT IDENTIFIER ::= { rPDU2Sensor 4 }
+
+-- rPDU2 Discrete Sensor Config
+
+rPDU2SensorDiscreteConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RPDU2SensorDiscreteConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A table of discrete sensor configuration
+ data"
+ ::= { rPDU2SensorDiscrete 1 }
+
+rPDU2SensorDiscreteConfigEntry OBJECT-TYPE
+ SYNTAX RPDU2SensorDiscreteConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Configuration data from discreste sensor
+ being queried"
+ INDEX { rPDU2SensorDiscreteConfigIndex }
+ ::= { rPDU2SensorDiscreteConfigTable 1 }
+
+RPDU2SensorDiscreteConfigEntry ::=
+ SEQUENCE {
+ rPDU2SensorDiscreteConfigIndex INTEGER,
+ rPDU2SensorDiscreteConfigModule INTEGER,
+ rPDU2SensorDiscreteConfigName DisplayString,
+ rPDU2SensorDiscreteConfigNumber INTEGER,
+ rPDU2SensorDiscreteConfigNormalState INTEGER,
+ rPDU2SensorDiscreteConfigAbnormalSeverity INTEGER
+ }
+
+rPDU2SensorDiscreteConfigIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the discrete sensor configuration
+ data table entry"
+ ::= { rPDU2SensorDiscreteConfigEntry 1 }
+
+rPDU2SensorDiscreteConfigModule OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user-defined Rack PDU numeric ID"
+ ::= { rPDU2SensorDiscreteConfigEntry 2 }
+
+rPDU2SensorDiscreteConfigName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The user-defined discrete sensor ID string"
+ ::= { rPDU2SensorDiscreteConfigEntry 3 }
+
+rPDU2SensorDiscreteConfigNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The discrete sensor numeric ID"
+ ::= { rPDU2SensorDiscreteConfigEntry 4 }
+
+rPDU2SensorDiscreteConfigNormalState OBJECT-TYPE
+ SYNTAX INTEGER {
+ normallyOpen (1),
+ normallyClosed (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the normal state of the discrete input
+ contact"
+ ::= { rPDU2SensorDiscreteConfigEntry 5 }
+
+rPDU2SensorDiscreteConfigAbnormalSeverity OBJECT-TYPE
+ SYNTAX INTEGER {
+ informational (1),
+ warning (2),
+ critical (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the severity of alarm triggered by
+ abnormal discrete input contact state"
+ ::= { rPDU2SensorDiscreteConfigEntry 6 }
+
+-- rPDU2 Discrete Sensor Status
+
+rPDU2SensorDiscreteStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RPDU2SensorDiscreteStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A table of discrete sensor status data"
+ ::= { rPDU2SensorDiscrete 2 }
+
+rPDU2SensorDiscreteStatusEntry OBJECT-TYPE
+ SYNTAX RPDU2SensorDiscreteStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Status information from discrete sensor
+ being queried"
+ INDEX { rPDU2SensorDiscreteStatusIndex }
+ ::= { rPDU2SensorDiscreteStatusTable 1 }
+
+RPDU2SensorDiscreteStatusEntry ::=
+ SEQUENCE {
+ rPDU2SensorDiscreteStatusIndex INTEGER,
+ rPDU2SensorDiscreteStatusModule INTEGER,
+ rPDU2SensorDiscreteStatusName DisplayString,
+ rPDU2SensorDiscreteStatusNumber INTEGER,
+ rPDU2SensorDiscreteStatusType INTEGER,
+ rPDU2SensorDiscreteStatusCommStatus INTEGER,
+ rPDU2SensorDiscreteStatusCurrentState INTEGER,
+ rPDU2SensorDiscreteStatusAlarmState INTEGER
+ }
+
+rPDU2SensorDiscreteStatusIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the discrete sensor status data
+ table entry"
+ ::= { rPDU2SensorDiscreteStatusEntry 1 }
+
+rPDU2SensorDiscreteStatusModule OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user-defined Rack PDU numeric ID"
+ ::= { rPDU2SensorDiscreteStatusEntry 2 }
+
+rPDU2SensorDiscreteStatusName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user-defined discrete sensor ID string"
+ ::= { rPDU2SensorDiscreteStatusEntry 3 }
+
+rPDU2SensorDiscreteStatusNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The discrete sensor numeric ID"
+ ::= { rPDU2SensorDiscreteStatusEntry 4 }
+
+rPDU2SensorDiscreteStatusType OBJECT-TYPE
+ SYNTAX INTEGER {
+ notConnected (1),
+ doorContactSensor (2),
+ smokeSensor (3),
+ motionDetector (4),
+ vibrationSensor (5),
+ dryContactSensor (6),
+ spotLeakSensor (7)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The type of discrete sensor currently being queried"
+ ::= { rPDU2SensorDiscreteStatusEntry 5 }
+
+rPDU2SensorDiscreteStatusCommStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ notInstalled(1),
+ commsOK(2),
+ commsLost(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The communications status of the sensor"
+ ::= { rPDU2SensorDiscreteStatusEntry 6 }
+
+rPDU2SensorDiscreteStatusCurrentState OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2),
+ unknown (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current open/close state of the discrete
+ sensor"
+ ::= { rPDU2SensorDiscreteStatusEntry 7 }
+
+rPDU2SensorDiscreteStatusAlarmState OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ alarm (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates alarm status of discrete sensor input"
+ ::= { rPDU2SensorDiscreteStatusEntry 8 }
+
+rPDU2Group OBJECT IDENTIFIER ::= { rPDU2 11 }
+
+-- rPDU2 Total Rack PDU Network Port Sharing (NPS) group power and energy
+
+rPDU2GroupNumberOfDevices OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return the number of Rack PDU devices contributing
+ to the Network Port Sharing (NPS) group power and energy values.
+ Queries to guest units in an NPS group are not applicable and will
+ return 0."
+
+ ::= { rPDU2Group 1 }
+
+rPDU2GroupTotalPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return the total power consumption of the Rack PDU
+ Network Port Sharing (NPS) group devices in hundredths of kilowatts.
+ Queries to guest units in an NPS group are not applicable and will
+ return 0."
+
+ ::= { rPDU2Group 2 }
+
+rPDU2GroupTotalEnergy OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return the total energy consumption of the Rack PDU
+ Network Port Sharing (NPS) group devices in tenths of kilowatt-hours.
+
+ To reset the energy meters for each of the Rack PDU devices that contribute
+ to this value, see the rPDU2GroupEnergyReset OID.
+
+ To view the start time for each of the Rack PDU device energy meters that
+ contribute to this value, see the rPDU2DeviceStatusEnergyStartTime OID.
+
+ Queries to guest units in an NPS group are not applicable and will
+ return 0."
+
+ ::= { rPDU2Group 3 }
+
+rPDU2GroupEnergyReset OBJECT-TYPE
+ SYNTAX INTEGER {
+ noOperation (1),
+ reset (2),
+ notSupported (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to reset (2) will cause the device energy meter value
+ on each device in the Rack PDU Network Port Sharing (NPS) group to be
+ reset to zero.
+
+ Each device in the Rack PDU group will also have its corresponding
+ rPDU2DeviceStatusEnergyStartTime OID value updated.
+
+ Getting this OID in models that support this feature will do nothing
+ and return the noOperation(1) value.
+
+ Models that do not support this feature, as well as guest units in an
+ NPS group, will respond to this OID with a value of notSupported (3).
+ Attempts to set this OID in these units will fail."
+
+ ::= { rPDU2Group 4 }
+
+
+-- rPDU2 Phase To Phase Status
+rPDU2PhaseToPhaseStatusTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of connected Rack PDU banks"
+ ::= { rPDU2 12}
+
+rPDU2PhaseToPhase OBJECT IDENTIFIER ::= { rPDU2 13 }
+
+rPDU2PhaseToPhaseStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RPDU2PhaseToPhaseStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A table of Rack PDU phase to phase status data.
+ This table is only applicable to SKUs that have
+ phase to phase outputs."
+ ::= { rPDU2PhaseToPhase 1 }
+
+rPDU2PhaseToPhaseStatusEntry OBJECT-TYPE
+ SYNTAX RPDU2PhaseToPhaseStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Status data from currently queried Rack PDU
+ phase to phase outputs"
+ INDEX { rPDU2PhaseToPhaseStatusIndex }
+ ::= { rPDU2PhaseToPhaseStatusTable 1 }
+
+RPDU2PhaseToPhaseStatusEntry ::=
+ SEQUENCE {
+ rPDU2PhaseToPhaseStatusIndex INTEGER,
+ rPDU2PhaseToPhaseStatusModule INTEGER,
+ rPDU2PhaseToPhaseStatusVoltage1to2 INTEGER,
+ rPDU2PhaseToPhaseStatusVoltage2to3 INTEGER,
+ rPDU2PhaseToPhaseStatusVoltage3to1 INTEGER
+ }
+
+rPDU2PhaseToPhaseStatusIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the Rack PDU phase to phase status table
+ entry"
+ ::= { rPDU2PhaseToPhaseStatusEntry 1 }
+
+rPDU2PhaseToPhaseStatusModule OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user-defined Rack PDU numeric ID"
+ ::= { rPDU2PhaseToPhaseStatusEntry 2 }
+
+
+rPDU2PhaseToPhaseStatusVoltage1to2 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the Voltage, in Volts, of the Rack
+ PDU phase 1 to phase 2 output being queried"
+ ::= { rPDU2PhaseToPhaseStatusEntry 3 }
+
+rPDU2PhaseToPhaseStatusVoltage2to3 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the Voltage, in Volts, of the Rack
+ PDU phase 2 to phase 3 output being queried"
+ ::= { rPDU2PhaseToPhaseStatusEntry 4 }
+
+rPDU2PhaseToPhaseStatusVoltage3to1 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the Voltage, in Volts, of the Rack
+ PDU phase 3 to phase 2 output being queried"
+ ::= { rPDU2PhaseToPhaseStatusEntry 5 }
+
+-- ePDU Ident Table
+
+ePDUDeviceStatusTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The total number of Easy PDUs"
+ ::= { ePDU 1 }
+
+ePDUDevice OBJECT IDENTIFIER ::= { ePDU 2 }
+
+-- ePDU Device Status
+
+ePDUDeviceStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF EPDUDeviceStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A table of Easy PDU status information"
+ ::= { ePDUDevice 1 }
+
+ePDUDeviceStatusEntry OBJECT-TYPE
+ SYNTAX EPDUDeviceStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Status information from the Easy PDU being queried"
+ INDEX { ePDUDeviceStatusIndex }
+ ::= { ePDUDeviceStatusTable 1 }
+
+EPDUDeviceStatusEntry ::=
+ SEQUENCE {
+ ePDUDeviceStatusIndex INTEGER,
+ ePDUDeviceStatusModule INTEGER,
+ ePDUDeviceStatusVersion DisplayString,
+ ePDUDeviceStatusModelNumber DisplayString,
+ ePDUDeviceStatusSerialNumber DisplayString,
+ ePDUDeviceStatusNumPhases INTEGER,
+ ePDUDeviceStatusActivePower INTEGER,
+ ePDUDeviceStatusReactivePower INTEGER,
+ ePDUDeviceStatusApparentPower INTEGER,
+ ePDUDeviceStatusPowerFactor INTEGER,
+ ePDUDeviceStatusEnergy INTEGER,
+ ePDUDeviceStatusFrequency INTEGER
+ }
+
+ePDUDeviceStatusIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the Easy PDU status table entry"
+ ::= { ePDUDeviceStatusEntry 1 }
+
+ePDUDeviceStatusModule OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user-defined Rack PDU numeric ID"
+ ::= { ePDUDeviceStatusEntry 2 }
+
+ePDUDeviceStatusVersion OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Easy PDU firmware and hardware version"
+ ::= { ePDUDeviceStatusEntry 3 }
+
+ePDUDeviceStatusModelNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Easy PDU model number"
+ ::= { ePDUDeviceStatusEntry 4 }
+
+ePDUDeviceStatusSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Easy PDU serial number"
+ ::= { ePDUDeviceStatusEntry 5 }
+
+ePDUDeviceStatusNumPhases OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of phases present in the Easy PDU"
+ ::= { ePDUDeviceStatusEntry 6 }
+
+ePDUDeviceStatusActivePower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the PDU Active Power. Units:1 Watt.
+ Models that do not support this feature, will respond to this OID
+ with a value of notSupported (-1)."
+ ::= { ePDUDeviceStatusEntry 7 }
+
+ePDUDeviceStatusReactivePower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the PDU Reactive Power. Units:1 Var.
+ Models that do not support this feature, will respond to this OID
+ with a value of notSupported (-1)."
+ ::= { ePDUDeviceStatusEntry 8 }
+
+ePDUDeviceStatusApparentPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the PDU Apparent Power. Units:1 VA.
+ Models that do not support this feature, will respond to this OID
+ with a value of notSupported (-1)."
+ ::= { ePDUDeviceStatusEntry 9 }
+
+ePDUDeviceStatusPowerFactor OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the PDU Power Factor. Units:0.1%.
+ Models that do not support this feature, will respond to this OID
+ with a value of notSupported (-1)."
+ ::= { ePDUDeviceStatusEntry 10 }
+
+ePDUDeviceStatusEnergy OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the PDU Energy. Units:1 Wh.
+ Models that do not support this feature, will respond to this OID
+ with a value of notSupported (-1)."
+ ::= { ePDUDeviceStatusEntry 11 }
+
+ePDUDeviceStatusFrequency OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the PDU Frequency. Units:0.001 Hz.
+ Models that do not support this feature, will respond to this OID
+ with a value of notSupported (-1)."
+ ::= { ePDUDeviceStatusEntry 12 }
+
+-- ePDU Device Control
+
+ePDUDeviceControlTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF EPDUDeviceControlEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A table of Easy PDU control data"
+ ::= { ePDUDevice 2 }
+
+ePDUDeviceControlEntry OBJECT-TYPE
+ SYNTAX EPDUDeviceControlEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Control data from Easy PDU being queried"
+ INDEX { ePDUDeviceControlIndex }
+ ::= { ePDUDeviceControlTable 1 }
+
+EPDUDeviceControlEntry ::=
+ SEQUENCE {
+ ePDUDeviceControlIndex INTEGER,
+ ePDUDeviceControlModule INTEGER,
+ ePDUDeviceControlReboot INTEGER,
+ ePDUDeviceControlEngeryReset INTEGER,
+ ePDUDeviceControlBeepAlarm INTEGER
+ }
+
+ePDUDeviceControlIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the Easy PDU control table entry"
+ ::= { ePDUDeviceControlEntry 1 }
+
+ePDUDeviceControlModule OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user-defined Easy PDU numeric ID"
+ ::= { ePDUDeviceControlEntry 2 }
+
+ePDUDeviceControlReboot OBJECT-TYPE
+ SYNTAX INTEGER {
+ noOperation(0),
+ reboot(1)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to reboot (1) will cause the device reboot immediately.
+ Getting this OID in models that support this feature will do nothing and
+ return the noOperation(0) value."
+ ::= { ePDUDeviceControlEntry 3 }
+
+ePDUDeviceControlEngeryReset OBJECT-TYPE
+ SYNTAX INTEGER {
+ noOperation(0),
+ reset(1)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to reboot (1) will cause the device reboot immediately.
+ Getting this OID in models that support this feature will do nothing and
+ return the noOperation(0) value."
+ ::= { ePDUDeviceControlEntry 4 }
+
+
+ePDUDeviceControlBeepAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ off(1),
+ on(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "User-defined Beep alarm, 1 for turn off Beep, 2 for turn on Beep.
+ Models that do not support this feature will respond to this OID
+ with a value of -1."
+ ::= { ePDUDeviceControlEntry 5 }
+
+-- ePDU Phase Data
+
+ePDUPhaseTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of connected Easy PDU phases"
+ ::= { ePDU 3 }
+
+ePDUPhase OBJECT IDENTIFIER ::= { ePDU 4 }
+
+-- ePDU2 Phase Config
+
+ePDUPhaseConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF EPDUPhaseConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A table of Easy PDU phase configuration data"
+ ::= { ePDUPhase 1 }
+
+ePDUPhaseConfigEntry OBJECT-TYPE
+ SYNTAX EPDUPhaseConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Configuration data from currently queried Easy PDU phase"
+ INDEX { ePDUPhaseConfigIndex }
+ ::= { ePDUPhaseConfigTable 1 }
+
+EPDUPhaseConfigEntry ::=
+ SEQUENCE {
+ ePDUPhaseConfigIndex INTEGER,
+ ePDUPhaseConfigModule INTEGER,
+ ePDUPhaseConfigNumber INTEGER,
+ ePDUPhaseConfigOverVoltageThreshold INTEGER,
+ ePDUPhaseConfigLowVoltageThreshold INTEGER,
+ ePDUPhaseConfigOverCurrentThreshold INTEGER,
+ ePDUPhaseConfigLowCurrentThreshold INTEGER
+ }
+
+ePDUPhaseConfigIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the Easy PDU phase configuration table entry"
+ ::= { ePDUPhaseConfigEntry 1 }
+
+ePDUPhaseConfigModule OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user-defined Easy PDU numeric ID"
+ ::= { ePDUPhaseConfigEntry 2 }
+
+ePDUPhaseConfigNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The numeric phase ID"
+ ::= { ePDUPhaseConfigEntry 3 }
+
+ePDUPhaseConfigOverVoltageThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "User-defined Phase Over Voltage alarm threshold. Units:0.1 V.
+ Models that do not support this feature will respond to this OID
+ with a value of -1."
+ ::= { ePDUPhaseConfigEntry 4 }
+
+ePDUPhaseConfigLowVoltageThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "User-defined Phase Low Voltage alarm threshold. Units:0.1 V.
+ Models that do not support this feature will
+ respond to this OID with a value of -1."
+ ::= { ePDUPhaseConfigEntry 5 }
+
+ePDUPhaseConfigOverCurrentThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "User-defined Phase Over Current alarm threshold. Units:0.01 A.
+ Models that do not support this feature will respond to this OID
+ with a value of -1."
+ ::= { ePDUPhaseConfigEntry 6 }
+
+ePDUPhaseConfigLowCurrentThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "User-defined Phase Low Current alarm threshold. Units:0.01 A.
+ Models that do not support this feature will respond to this OID
+ with a value of -1."
+ ::= { ePDUPhaseConfigEntry 7 }
+
+-- ePDU Phase Status
+
+ePDUPhaseStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF EPDUPhaseStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A table of Rack PDU phase status data"
+ ::= { ePDUPhase 2 }
+
+ePDUPhaseStatusEntry OBJECT-TYPE
+ SYNTAX EPDUPhaseStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Status data from currently queried Easy PDU phase"
+ INDEX { ePDUPhaseStatusIndex }
+ ::= { ePDUPhaseStatusTable 1 }
+
+EPDUPhaseStatusEntry ::=
+ SEQUENCE {
+ ePDUPhaseStatusIndex INTEGER,
+ ePDUPhaseStatusModule INTEGER,
+ ePDUPhaseStatusNumber INTEGER,
+ ePDUPhaseStatusVoltage INTEGER,
+ ePDUPhaseStatusCurrent INTEGER,
+ ePDUPhaseStatusActivePower INTEGER,
+ ePDUPhaseStatusReactivePower INTEGER,
+ ePDUPhaseStatusApparentPower INTEGER,
+ ePDUPhaseStatusPowerFactor INTEGER,
+ ePDUPhaseStatusEnergy INTEGER
+ }
+
+ePDUPhaseStatusIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..12)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the Easy PDU phase configuration table entry"
+ ::= { ePDUPhaseStatusEntry 1 }
+
+ePDUPhaseStatusModule OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user-defined Easy PDU numeric ID"
+ ::= { ePDUPhaseStatusEntry 2 }
+
+ePDUPhaseStatusNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The numeric phase ID"
+ ::= { ePDUPhaseStatusEntry 3 }
+
+ePDUPhaseStatusVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the Phase Voltage. Units:0.1 V"
+ ::= { ePDUPhaseStatusEntry 4 }
+
+ePDUPhaseStatusCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the Phase Current. Units:0.01 A"
+ ::= { ePDUPhaseStatusEntry 5 }
+
+ePDUPhaseStatusActivePower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the Phase Active Power. Units:1 Watt"
+ ::= { ePDUPhaseStatusEntry 6 }
+
+ePDUPhaseStatusReactivePower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the Phase Reactive Power. Units:1 Var.
+ Models that do not support this feature, will respond to this OID
+ with a value of notSupported (-1)."
+ ::= { ePDUPhaseStatusEntry 7 }
+
+ePDUPhaseStatusApparentPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the Phase Apparent Power. Units:1 VA.
+ Models that do not support this feature, will respond to this OID
+ with a value of notSupported (-1)."
+ ::= { ePDUPhaseStatusEntry 8 }
+
+ePDUPhaseStatusPowerFactor OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the Phase Power Factor. Units:0.1%"
+ ::= { ePDUPhaseStatusEntry 9 }
+
+ePDUPhaseStatusEnergy OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the Phase Energy. Units:1 Wh"
+ ::= { ePDUPhaseStatusEntry 10 }
+
+-- ePDU Switched Outlet Data
+
+ePDUOutletTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of switched outlets on connected Easy PDUs."
+ ::= { ePDU 5 }
+
+ePDUOutlet OBJECT IDENTIFIER ::= { ePDU 6 }
+
+-- ePDU Switched Outlet Status
+
+ePDUOutletStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF EPDUOutletStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The number of switched outlets on connected Rack PDUs"
+ ::= { ePDUOutlet 1 }
+
+ePDUOutletStatusEntry OBJECT-TYPE
+ SYNTAX EPDUOutletStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Switched Outlet status from currently queried
+ Easy PDU switched outlet"
+ INDEX { ePDUOutletStatusIndex }
+ ::= { ePDUOutletStatusTable 1 }
+
+EPDUOutletStatusEntry ::=
+ SEQUENCE {
+ ePDUOutletStatusIndex INTEGER,
+ ePDUOutletStatusModule INTEGER,
+ ePDUOutletStatusNumber INTEGER,
+ ePDUOutletStatusState INTEGER
+ }
+
+ePDUOutletStatusIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..128)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the Easy PDU switched outlet status information table entry.
+ Models that do not support this feature, will respond to this OID
+ with a value of notSupported (-1)."
+ ::= { ePDUOutletStatusEntry 1 }
+
+ePDUOutletStatusModule OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user-defined Easy PDU numeric ID.
+ Models that do not support this feature, will respond to this OID
+ with a value of notSupported (-1)."
+ ::= { ePDUOutletStatusEntry 2 }
+
+ePDUOutletStatusNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The numeric switched outlet ID.
+ Models that do not support this feature, will respond to this OID
+ with a value of notSupported (-1)."
+ ::= { ePDUOutletStatusEntry 3 }
+
+ePDUOutletStatusState OBJECT-TYPE
+ SYNTAX INTEGER {
+ off(1),
+ on(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the present switch state of the Easy PDU switched outlet being queried.
+ Models that do not support this feature, will respond to this OID
+ with a value of notSupported (-1)."
+ ::= { ePDUOutletStatusEntry 4 }
+
+-- ePDU Switched Outlet Control
+
+ePDUOutletControlTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF EPDUOutletControlEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A table of Easy PDU switched outlet control data"
+ ::= { ePDUOutlet 2 }
+
+ePDUOutletControlEntry OBJECT-TYPE
+ SYNTAX EPDUOutletControlEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Control data for currently queried Easy PDU switched outlet"
+ INDEX { ePDUOutletControlIndex }
+ ::= { ePDUOutletControlTable 1 }
+
+EPDUOutletControlEntry ::=
+ SEQUENCE {
+ ePDUOutletControlIndex INTEGER,
+ ePDUOutletControlModule INTEGER,
+ ePDUOutletControlNumber INTEGER,
+ ePDUOutletControlCommand INTEGER
+ }
+
+ePDUOutletControlIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..128)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the Easy PDU switched outlet configuration table entry.
+ Models that do not support this feature, will respond to this OID
+ with a value of notSupported (-1)."
+ ::= { ePDUOutletControlEntry 1 }
+
+ePDUOutletControlModule OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user-defined Easy PDU numeric ID.
+ Models that do not support this feature, will respond to this OID
+ with a value of notSupported (-1)."
+ ::= { ePDUOutletControlEntry 2 }
+
+ePDUOutletControlNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The numeric switched outlet ID.
+ Models that do not support this feature, will respond to this OID
+ with a value of notSupported (-1)."
+ ::= { ePDUOutletControlEntry 3 }
+
+ePDUOutletControlCommand OBJECT-TYPE
+ SYNTAX INTEGER {
+ immediateOn(1),
+ immediateOff(2),
+ outletUnknown(3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this variable will return the outlet state. If
+ the outlet is on, the immediateOn (1) value will be returned.
+ If the outlet is off, the immediateOff (2) value will be
+ returned. If the state of the outlet cannot be
+ determined, the outletUnknown (3) value will be returned.
+ If the outletUnknown condition should occur, all devices
+ powered by the PDU should be shut down. The PDU's power
+ should then be cycled to clear this condition.
+ Models that do not support this feature,
+ will respond to this OID with a value of notSupported (-1).
+ Setting this variable to immediateOn (1) will immediately turn the outlet on.
+ Setting this variable to immediateOff (2) will immediately turn the outlet off."
+ ::= { ePDUOutletControlEntry 4 }
+
+-- ePDU Temperature and Humidity Sensor Data
+
+ePDUSensorTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of connected temperature-humidity sensors"
+ ::= { ePDU 7 }
+
+ePDUSensor OBJECT IDENTIFIER ::= { ePDU 8 }
+
+-- ePDU Temperature and Humidity Sensor Config
+
+ePDUSensorConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF EPDUSensorConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A table of temperature-humidity sensor configuration data"
+ ::= { ePDUSensor 1 }
+
+ePDUSensorConfigEntry OBJECT-TYPE
+ SYNTAX EPDUSensorConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Configuration data from temperature-humidity sensor being queried"
+ INDEX { ePDUSensorConfigIndex }
+ ::= { ePDUSensorConfigTable 1 }
+
+EPDUSensorConfigEntry ::=
+ SEQUENCE {
+ ePDUSensorConfigIndex INTEGER,
+ ePDUSensorConfigModule INTEGER,
+ ePDUSensorConfigTempMaxThreshold INTEGER,
+ ePDUSensorConfigTempMinThreshold INTEGER,
+ ePDUSensorConfigHumidityMaxThreshold INTEGER,
+ ePDUSensorConfigHumidityMinThreshold INTEGER
+ }
+
+ePDUSensorConfigIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the temperature-humidity sensor configuration data table entry"
+ ::= { ePDUSensorConfigEntry 1 }
+
+ePDUSensorConfigModule OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user-defined Easy PDU numeric ID"
+ ::= { ePDUSensorConfigEntry 2 }
+
+ePDUSensorConfigTempMaxThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "User-defined Max Temperature alarm threshold. Units: 0.1 degrees Celsius.
+ Models that do not support this feature will respond to this OID
+ with a value of -1."
+ ::= { ePDUSensorConfigEntry 3 }
+
+
+ePDUSensorConfigTempMinThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "User-defined Min Temperature alarm threshold. Units: 0.1 degrees Celsius.
+ Models that do not support this feature will
+ respond to this OID with a value of -1."
+ ::= { ePDUSensorConfigEntry 4 }
+
+ePDUSensorConfigHumidityMaxThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "User-defined Max Humidity alarm threshold. Units: 0.1% relative humidity.
+ Models that do not support this feature will respond to this OID
+ with a value of -1."
+ ::= { ePDUSensorConfigEntry 5 }
+
+ePDUSensorConfigHumidityMinThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "User-defined Min Humidity alarm threshold. Units: 0.1% relative humidity.
+ Models that do not support this feature will respond to this OID
+ with a value of -1."
+ ::= { ePDUSensorConfigEntry 6 }
+
+-- ePDU Temperature and Humidity Sensor Status
+
+ePDUSensorStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF EPDUSensorStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A table of temperature-humidity sensor status data"
+ ::= { ePDUSensor 2 }
+
+ePDUSensorStatusEntry OBJECT-TYPE
+ SYNTAX EPDUSensorStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Status information from temperature-humidity sensor being queried"
+ INDEX { ePDUSensorStatusIndex }
+ ::= { ePDUSensorStatusTable 1 }
+
+EPDUSensorStatusEntry ::=
+ SEQUENCE {
+ ePDUSensorStatusIndex INTEGER,
+ ePDUSensorStatusModule INTEGER,
+ ePDUSensorStatusTemperature INTEGER,
+ ePDUSensorStatusHumidity INTEGER
+ }
+
+ePDUSensorStatusIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..4)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the temperature-humidity status data table entry"
+ ::= { ePDUSensorStatusEntry 1 }
+
+ePDUSensorStatusModule OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user-defined Easy PDU numeric ID"
+ ::= { ePDUSensorStatusEntry 2 }
+
+ePDUSensorStatusTemperature OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor temperature reading in tenths of degrees Celsius."
+ ::= { ePDUSensorStatusEntry 3 }
+
+ePDUSensorStatusHumidity OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor humidity reading in 0.1 percent relative humidity."
+ ::= { ePDUSensorStatusEntry 4 }
+
+-- the cooling group
+
+coolingUnit OBJECT IDENTIFIER ::= { cooling 1 }
+
+coolingUnitTableSize OBJECT-TYPE
+ SYNTAX INTEGER (0..2147483647)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of cooling units accessible via this agent."
+ ::= { coolingUnit 1 }
+
+coolingUnitTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF CoolingUnitEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A table of cooling unit level data."
+ ::= { coolingUnit 2}
+
+coolingUnitEntry OBJECT-TYPE
+ SYNTAX CoolingUnitEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An element of coolingUnitTable."
+ INDEX { coolingUnitTableIndex }
+ ::= { coolingUnitTable 1 }
+
+CoolingUnitEntry ::= SEQUENCE {
+ coolingUnitTableIndex INTEGER
+}
+
+coolingUnitTableIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..2147483647)
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The unit reference identifier for this table and all other table entries subordinate to coolingUnits."
+ ::= { coolingUnitEntry 1 }
+
+coolingUnitAbout OBJECT IDENTIFIER ::= { coolingUnit 3 }
+
+coolingUnitAboutTableSize OBJECT-TYPE
+ SYNTAX INTEGER (0..2147483647)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The potential number of entries available in coolingUnitAboutTable."
+ ::= { coolingUnitAbout 1 }
+
+coolingUnitAboutTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF CoolingUnitAboutEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A table of unit reference information."
+ ::= { coolingUnitAbout 2}
+
+coolingUnitAboutEntry OBJECT-TYPE
+ SYNTAX CoolingUnitAboutEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An element of coolingUnitAboutTable."
+ INDEX { coolingUnitTableIndex,
+ coolingUnitAboutTableIndex }
+ ::= { coolingUnitAboutTable 1 }
+
+CoolingUnitAboutEntry ::= SEQUENCE {
+ coolingUnitAboutTableIndex INTEGER,
+ coolingUnitAboutDescription DisplayString,
+ coolingUnitAboutValue DisplayString
+}
+
+coolingUnitAboutTableIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..2147483647)
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The static reference identifier for each table entry."
+ ::= { coolingUnitAboutEntry 1 }
+
+coolingUnitAboutDescription OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A text description of the information presented in coolingUnitAboutValue."
+ ::= { coolingUnitAboutEntry 2 }
+
+coolingUnitAboutValue OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The actual value of the current table entry."
+ ::= { coolingUnitAboutEntry 3 }
+
+coolingUnitStatus OBJECT IDENTIFIER ::= { coolingUnit 4 }
+coolingUnitStatusAnalog OBJECT IDENTIFIER ::= { coolingUnitStatus 1 }
+
+coolingUnitStatusAnalogTableSize OBJECT-TYPE
+ SYNTAX INTEGER (0..2147483647)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The potential number of entries available in coolingUnitStatusAnalogTable."
+ ::= { coolingUnitStatusAnalog 1 }
+
+coolingUnitStatusAnalogTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF CoolingUnitStatusAnalogEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A table of analog unit status data."
+ ::= { coolingUnitStatusAnalog 2}
+
+coolingUnitStatusAnalogEntry OBJECT-TYPE
+ SYNTAX CoolingUnitStatusAnalogEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An element of coolingUnitStatusAnalogTable."
+ INDEX { coolingUnitTableIndex,
+ coolingUnitStatusAnalogTableIndex }
+ ::= { coolingUnitStatusAnalogTable 1 }
+
+CoolingUnitStatusAnalogEntry ::= SEQUENCE {
+ coolingUnitStatusAnalogTableIndex INTEGER,
+ coolingUnitStatusAnalogDescription DisplayString,
+ coolingUnitStatusAnalogValue INTEGER,
+ coolingUnitStatusAnalogUnits DisplayString,
+ coolingUnitStatusAnalogScale INTEGER
+}
+
+coolingUnitStatusAnalogTableIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..2147483647)
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The static reference identifier for each table entry."
+ ::= { coolingUnitStatusAnalogEntry 1 }
+
+coolingUnitStatusAnalogDescription OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A text description of the information presented in coolingUnitStatusAnalogValue."
+ ::= { coolingUnitStatusAnalogEntry 2 }
+
+coolingUnitStatusAnalogValue OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The scaled value of the current table entry (multiplied by coolingUnitStatusAnalogScale for integer presentation)."
+ ::= { coolingUnitStatusAnalogEntry 3 }
+
+coolingUnitStatusAnalogUnits OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit of measure by which coolingUnitStatusAnalogValue is expressed."
+ ::= { coolingUnitStatusAnalogEntry 4 }
+
+coolingUnitStatusAnalogScale OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The factor by which coolingUnitStatusAnalogValue is expressed."
+ ::= { coolingUnitStatusAnalogEntry 5 }
+
+coolingUnitStatusDiscrete OBJECT IDENTIFIER ::= { coolingUnitStatus 2 }
+
+coolingUnitStatusDiscreteTableSize OBJECT-TYPE
+ SYNTAX INTEGER (0..2147483647)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The potential number of entries available in coolingUnitStatusDiscreteTable."
+ ::= { coolingUnitStatusDiscrete 1 }
+
+coolingUnitStatusDiscreteTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF CoolingUnitStatusDiscreteEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A table of discrete unit status data."
+ ::= { coolingUnitStatusDiscrete 2}
+
+coolingUnitStatusDiscreteEntry OBJECT-TYPE
+ SYNTAX CoolingUnitStatusDiscreteEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An element of coolingUnitStatusDiscreteTable."
+ INDEX { coolingUnitTableIndex,
+ coolingUnitStatusDiscreteTableIndex }
+ ::= { coolingUnitStatusDiscreteTable 1 }
+
+CoolingUnitStatusDiscreteEntry ::= SEQUENCE {
+ coolingUnitStatusDiscreteTableIndex INTEGER,
+ coolingUnitStatusDiscreteDescription DisplayString,
+ coolingUnitStatusDiscreteValueAsString DisplayString,
+ coolingUnitStatusDiscreteValueAsInteger INTEGER,
+ coolingUnitStatusDiscreteIntegerReferenceKey DisplayString
+}
+
+coolingUnitStatusDiscreteTableIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..2147483647)
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The static reference identifier for each table entry."
+ ::= { coolingUnitStatusDiscreteEntry 1 }
+
+coolingUnitStatusDiscreteDescription OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A text description of the information presented in this table's 'value' OIDs."
+ ::= { coolingUnitStatusDiscreteEntry 2 }
+
+coolingUnitStatusDiscreteValueAsString OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The actual value of the current table entry expressed as a string."
+ ::= { coolingUnitStatusDiscreteEntry 3 }
+
+coolingUnitStatusDiscreteValueAsInteger OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The actual value of the current table entry expressed as an integer value."
+ ::= { coolingUnitStatusDiscreteEntry 4 }
+
+coolingUnitStatusDiscreteIntegerReferenceKey OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A complete listing of all possible coolingUnitStatusDiscreteValueAsInteger values paired with their identifying strings."
+ ::= { coolingUnitStatusDiscreteEntry 5 }
+
+coolingUnitConfiguration OBJECT IDENTIFIER ::= { coolingUnit 5 }
+coolingUnitConfigurationAnalog OBJECT IDENTIFIER ::= { coolingUnitConfiguration 1 }
+
+coolingUnitConfigurationAnalogTableSize OBJECT-TYPE
+ SYNTAX INTEGER (0..2147483647)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The potential number of entries available in coolingUnitConfigurationAnalogTable."
+ ::= { coolingUnitConfigurationAnalog 1 }
+
+coolingUnitConfigurationAnalogTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF CoolingUnitConfigurationAnalogEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A table of analog unit configuration data."
+ ::= { coolingUnitConfigurationAnalog 2}
+
+coolingUnitConfigurationAnalogEntry OBJECT-TYPE
+ SYNTAX CoolingUnitConfigurationAnalogEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An element of coolingUnitConfigurationAnalogTable."
+ INDEX { coolingUnitTableIndex,
+ coolingUnitConfigurationAnalogTableIndex }
+ ::= { coolingUnitConfigurationAnalogTable 1 }
+
+CoolingUnitConfigurationAnalogEntry ::= SEQUENCE {
+ coolingUnitConfigurationAnalogTableIndex INTEGER,
+ coolingUnitConfigurationAnalogDescription DisplayString,
+ coolingUnitConfigurationAnalogValue INTEGER,
+ coolingUnitConfigurationAnalogUnits DisplayString,
+ coolingUnitConfigurationAnalogScale INTEGER,
+ coolingUnitConfigurationAnalogAccess INTEGER,
+ coolingUnitConfigurationAnalogMinimum INTEGER,
+ coolingUnitConfigurationAnalogMaximum INTEGER
+}
+
+coolingUnitConfigurationAnalogTableIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..2147483647)
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The static reference identifier for each table entry."
+ ::= { coolingUnitConfigurationAnalogEntry 1 }
+
+coolingUnitConfigurationAnalogDescription OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A text description of the information presented in coolingUnitConfigurationAnalogValue."
+ ::= { coolingUnitConfigurationAnalogEntry 2 }
+
+coolingUnitConfigurationAnalogValue OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The scaled value of the current table entry (multiplied by coolingUnitConfigurationAnalogScale for integer presentation)."
+ ::= { coolingUnitConfigurationAnalogEntry 3 }
+
+coolingUnitConfigurationAnalogUnits OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit of measure by which coolingUnitConfigurationAnalogValue is expressed."
+ ::= { coolingUnitConfigurationAnalogEntry 4 }
+
+coolingUnitConfigurationAnalogScale OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The factor by which coolingUnitConfigurationAnalogValue is expressed."
+ ::= { coolingUnitConfigurationAnalogEntry 5 }
+
+coolingUnitConfigurationAnalogAccess OBJECT-TYPE
+ SYNTAX INTEGER {
+ readOnly (1),
+ readWrite (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A description of available access to coolingUnitConfigurationAnalogValue via SNMP client."
+ ::= { coolingUnitConfigurationAnalogEntry 6 }
+
+coolingUnitConfigurationAnalogMinimum OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum possible value of coolingUnitConfigurationAnalogValue."
+ ::= { coolingUnitConfigurationAnalogEntry 7 }
+
+coolingUnitConfigurationAnalogMaximum OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum possible value of coolingUnitConfigurationAnalogValue."
+ ::= { coolingUnitConfigurationAnalogEntry 8 }
+
+coolingUnitConfigurationDiscrete OBJECT IDENTIFIER ::= { coolingUnitConfiguration 2 }
+
+coolingUnitConfigurationDiscreteTableSize OBJECT-TYPE
+ SYNTAX INTEGER (0..2147483647)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The potential number of entries available in coolingUnitConfigurationDiscreteTable."
+ ::= { coolingUnitConfigurationDiscrete 1 }
+
+coolingUnitConfigurationDiscreteTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF CoolingUnitConfigurationDiscreteEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A table of discrete unit configuration data."
+ ::= { coolingUnitConfigurationDiscrete 2}
+
+coolingUnitConfigurationDiscreteEntry OBJECT-TYPE
+ SYNTAX CoolingUnitConfigurationDiscreteEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An element of coolingUnitConfigurationDiscreteTable."
+ INDEX { coolingUnitTableIndex,
+ coolingUnitConfigurationDiscreteTableIndex }
+ ::= { coolingUnitConfigurationDiscreteTable 1 }
+
+CoolingUnitConfigurationDiscreteEntry ::= SEQUENCE {
+ coolingUnitConfigurationDiscreteTableIndex INTEGER,
+ coolingUnitConfigurationDiscreteDescription DisplayString,
+ coolingUnitConfigurationDiscreteValueAsString DisplayString,
+ coolingUnitConfigurationDiscreteValueAsInteger INTEGER,
+ coolingUnitConfigurationDiscreteIntegerReferenceKey DisplayString,
+ coolingUnitConfigurationDiscreteAccess INTEGER
+}
+
+coolingUnitConfigurationDiscreteTableIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..2147483647)
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The static reference identifier for each table entry."
+ ::= { coolingUnitConfigurationDiscreteEntry 1 }
+
+coolingUnitConfigurationDiscreteDescription OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A text description of the information presented in this table's 'value' OIDs."
+ ::= { coolingUnitConfigurationDiscreteEntry 2 }
+
+coolingUnitConfigurationDiscreteValueAsString OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The actual value of the current table entry expressed as a string."
+ ::= { coolingUnitConfigurationDiscreteEntry 3 }
+
+coolingUnitConfigurationDiscreteValueAsInteger OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The actual value of the current table entry expressed as an integer value."
+ ::= { coolingUnitConfigurationDiscreteEntry 4 }
+
+coolingUnitConfigurationDiscreteIntegerReferenceKey OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A complete listing of all possible coolingUnitConfigurationDiscreteValueAsInteger values paired with their identifying strings."
+ ::= { coolingUnitConfigurationDiscreteEntry 5 }
+
+coolingUnitConfigurationDiscreteAccess OBJECT-TYPE
+ SYNTAX INTEGER {
+ readOnly (1),
+ readWrite (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A description of available access to coolingUnitConfigurationDiscreteValueAsInteger via SNMP client."
+ ::= { coolingUnitConfigurationDiscreteEntry 6 }
+
+coolingUnitConfigurationString OBJECT IDENTIFIER ::= { coolingUnitConfiguration 3 }
+
+coolingUnitConfigurationStringTableSize OBJECT-TYPE
+ SYNTAX INTEGER (0..2147483647)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The potential number of entries available in coolingUnitConfigurationStringTable."
+ ::= { coolingUnitConfigurationString 1 }
+
+coolingUnitConfigurationStringTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF CoolingUnitConfigurationStringEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A table of unit configuration strings."
+ ::= { coolingUnitConfigurationString 2}
+
+coolingUnitConfigurationStringEntry OBJECT-TYPE
+ SYNTAX CoolingUnitConfigurationStringEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An element of coolingUnitConfigurationStringTable."
+ INDEX { coolingUnitTableIndex,
+ coolingUnitConfigurationStringTableIndex }
+ ::= { coolingUnitConfigurationStringTable 1 }
+
+CoolingUnitConfigurationStringEntry ::= SEQUENCE {
+ coolingUnitConfigurationStringTableIndex INTEGER,
+ coolingUnitConfigurationStringDescription DisplayString,
+ coolingUnitConfigurationStringValue DisplayString,
+ coolingUnitConfigurationStringMaxLength INTEGER,
+ coolingUnitConfigurationStringAccess INTEGER
+}
+
+coolingUnitConfigurationStringTableIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..2147483647)
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The static reference identifier for each table entry."
+ ::= { coolingUnitConfigurationStringEntry 1 }
+
+coolingUnitConfigurationStringDescription OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A text description of the information presented in coolingUnitConfigurationStringValue."
+ ::= { coolingUnitConfigurationStringEntry 2 }
+
+coolingUnitConfigurationStringValue OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The actual value of the current table entry."
+ ::= { coolingUnitConfigurationStringEntry 3 }
+
+coolingUnitConfigurationStringMaxLength OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum string length supported by coolingUnitConfigurationStringValue."
+ ::= { coolingUnitConfigurationStringEntry 4 }
+
+coolingUnitConfigurationStringAccess OBJECT-TYPE
+ SYNTAX INTEGER {
+ readOnly (1),
+ readWrite (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A description of available access to coolingUnitConfigurationStringValue via SNMP client."
+ ::= { coolingUnitConfigurationStringEntry 5 }
+
+coolingUnitExtended OBJECT IDENTIFIER ::= { coolingUnit 6 }
+coolingUnitExtendedAnalog OBJECT IDENTIFIER ::= { coolingUnitExtended 1 }
+
+coolingUnitExtendedAnalogTableSize OBJECT-TYPE
+ SYNTAX INTEGER (0..2147483647)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The potential number of entries available in coolingUnitExtendedAnalogTable."
+ ::= { coolingUnitExtendedAnalog 1 }
+
+coolingUnitExtendedAnalogTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF CoolingUnitExtendedAnalogEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A table of secondary analog data for the cooling unit or one of its components."
+ ::= { coolingUnitExtendedAnalog 2}
+
+coolingUnitExtendedAnalogEntry OBJECT-TYPE
+ SYNTAX CoolingUnitExtendedAnalogEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An element of coolingUnitExtendedAnalogTable."
+ INDEX { coolingUnitTableIndex,
+ coolingUnitExtendedAnalogTableIndex }
+ ::= { coolingUnitExtendedAnalogTable 1 }
+
+CoolingUnitExtendedAnalogEntry ::= SEQUENCE {
+ coolingUnitExtendedAnalogTableIndex INTEGER,
+ coolingUnitExtendedAnalogDescription DisplayString,
+ coolingUnitExtendedAnalogValue INTEGER,
+ coolingUnitExtendedAnalogUnits DisplayString,
+ coolingUnitExtendedAnalogScale INTEGER
+}
+
+coolingUnitExtendedAnalogTableIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..2147483647)
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The static reference identifier for each table entry. This identifier may reference different table entries in different unit models."
+ ::= { coolingUnitExtendedAnalogEntry 1 }
+
+coolingUnitExtendedAnalogDescription OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A text description of the information presented in coolingUnitExtendedAnalogValue."
+ ::= { coolingUnitExtendedAnalogEntry 2 }
+
+coolingUnitExtendedAnalogValue OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The scaled value of the current table entry (multiplied by coolingUnitExtendedAnalogScale for integer presentation)."
+ ::= { coolingUnitExtendedAnalogEntry 3 }
+
+coolingUnitExtendedAnalogUnits OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit of measure by which coolingUnitExtendedAnalogValue is expressed."
+ ::= { coolingUnitExtendedAnalogEntry 4 }
+
+coolingUnitExtendedAnalogScale OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The factor by which coolingUnitExtendedAnalogValue is expressed."
+ ::= { coolingUnitExtendedAnalogEntry 5 }
+
+coolingUnitExtendedDiscrete OBJECT IDENTIFIER ::= { coolingUnitExtended 2 }
+
+coolingUnitExtendedDiscreteTableSize OBJECT-TYPE
+ SYNTAX INTEGER (0..2147483647)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The potential number of entries available in coolingUnitExtendedDiscreteTable."
+ ::= { coolingUnitExtendedDiscrete 1 }
+
+coolingUnitExtendedDiscreteTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF CoolingUnitExtendedDiscreteEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A table of secondary discrete cooling unit data."
+ ::= { coolingUnitExtendedDiscrete 2}
+
+coolingUnitExtendedDiscreteEntry OBJECT-TYPE
+ SYNTAX CoolingUnitExtendedDiscreteEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An element of coolingUnitExtendedDiscreteTable."
+ INDEX { coolingUnitTableIndex,
+ coolingUnitExtendedDiscreteTableIndex }
+ ::= { coolingUnitExtendedDiscreteTable 1 }
+
+CoolingUnitExtendedDiscreteEntry ::= SEQUENCE {
+ coolingUnitExtendedDiscreteTableIndex INTEGER,
+ coolingUnitExtendedDiscreteDescription DisplayString,
+ coolingUnitExtendedDiscreteValueAsString DisplayString,
+ coolingUnitExtendedDiscreteValueAsInteger INTEGER,
+ coolingUnitExtendedDiscreteIntegerReferenceKey DisplayString
+}
+
+coolingUnitExtendedDiscreteTableIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..2147483647)
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The static reference identifier for each table entry. This identifier may reference different table entries in different unit models."
+ ::= { coolingUnitExtendedDiscreteEntry 1 }
+
+coolingUnitExtendedDiscreteDescription OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A text description of the information presented in this table's 'value' OIDs."
+ ::= { coolingUnitExtendedDiscreteEntry 2 }
+
+coolingUnitExtendedDiscreteValueAsString OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The actual value of the current table entry expressed as a string."
+ ::= { coolingUnitExtendedDiscreteEntry 3 }
+
+coolingUnitExtendedDiscreteValueAsInteger OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The actual value of the current table entry expressed as an integer value."
+ ::= { coolingUnitExtendedDiscreteEntry 4 }
+
+coolingUnitExtendedDiscreteIntegerReferenceKey OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A complete listing of all possible coolingUnitExtendedDiscreteValueAsInteger values paired with their identifying strings."
+ ::= { coolingUnitExtendedDiscreteEntry 5 }
+
+coolingUnitExtendedString OBJECT IDENTIFIER ::= { coolingUnitExtended 3 }
+
+coolingUnitExtendedStringTableSize OBJECT-TYPE
+ SYNTAX INTEGER (0..2147483647)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The potential number of entries available in coolingUnitExtendedStringTable."
+ ::= { coolingUnitExtendedString 1 }
+
+coolingUnitExtendedStringTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF CoolingUnitExtendedStringEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A table of secondary unit reference data."
+ ::= { coolingUnitExtendedString 2}
+
+coolingUnitExtendedStringEntry OBJECT-TYPE
+ SYNTAX CoolingUnitExtendedStringEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An element of coolingUnitExtendedStringTable."
+ INDEX { coolingUnitTableIndex,
+ coolingUnitExtendedStringTableIndex }
+ ::= { coolingUnitExtendedStringTable 1 }
+
+CoolingUnitExtendedStringEntry ::= SEQUENCE {
+ coolingUnitExtendedStringTableIndex INTEGER,
+ coolingUnitExtendedStringDescription DisplayString,
+ coolingUnitExtendedStringValue DisplayString
+}
+
+coolingUnitExtendedStringTableIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..2147483647)
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The static reference identifier for each table entry. This identifier may reference different table entries in different unit models."
+ ::= { coolingUnitExtendedStringEntry 1 }
+
+coolingUnitExtendedStringDescription OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A text description of the information presented in coolingUnitExtendedStringValue."
+ ::= { coolingUnitExtendedStringEntry 2 }
+
+coolingUnitExtendedStringValue OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The actual value of the current table entry."
+ ::= { coolingUnitExtendedStringEntry 3 }
+
+
+
+-- the dm3IdentSystem group
+
+dm3IdentSysDescriptionTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of DC description records."
+ ::= { dm3IdentSystem 1 }
+
+dm3IdentSysDescriptionTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF Dm3IdentSysDescriptionEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for accessing description records of the powerplant. The number of
+ entries is contained in the dm3IdentSysDescriptionTableSize OID."
+ ::= { dm3IdentSystem 2 }
+
+dm3IdentSysDescriptionEntry OBJECT-TYPE
+ SYNTAX Dm3IdentSysDescriptionEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The powerplant description record to reference."
+ INDEX { dm3IdentSysDescriptionIndex }
+ ::= { dm3IdentSysDescriptionTable 1 }
+
+Dm3IdentSysDescriptionEntry ::=
+ SEQUENCE {
+ dm3IdentSysDescriptionIndex INTEGER,
+ dm3IdentSysDescriptionText DisplayString
+ }
+
+dm3IdentSysDescriptionIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the DC powerplant description record."
+ ::= { dm3IdentSysDescriptionEntry 1 }
+
+dm3IdentSysDescriptionText OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A 16 character text field describing the DC power plant device.
+ This field can be configured from the dm3ConfigSysDescriptionText OID."
+ ::= { dm3IdentSysDescriptionEntry 2 }
+
+dm3IdentSysModel OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Model type of the DC power plant."
+ ::= { dm3IdentSystem 3 }
+
+dm3IdentSysCntrlRev OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Integer representation of the hardware revision of the Master Controller board."
+ ::= { dm3IdentSystem 4 }
+
+dm3IdentSysFWVersion OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Integer representation of the power plant Master Controller firmware revision."
+ ::= { dm3IdentSystem 5 }
+
+-- the dm3ConfigSystem group
+
+dm3ConfigSysDescriptionTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of DC description records."
+ ::= { dm3ConfigSystem 1 }
+
+dm3ConfigSysDescriptionTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF Dm3ConfigSysDescriptionEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for accessing description records of the powerplant. The number of
+ entries is contained in the dm3ConfigSysDescriptionTableSize OID."
+ ::= { dm3ConfigSystem 2 }
+
+dm3ConfigSysDescriptionEntry OBJECT-TYPE
+ SYNTAX Dm3ConfigSysDescriptionEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The powerplant description record to reference."
+ INDEX { dm3ConfigSysDescriptionIndex }
+ ::= { dm3ConfigSysDescriptionTable 1 }
+
+Dm3ConfigSysDescriptionEntry ::=
+ SEQUENCE {
+ dm3ConfigSysDescriptionIndex INTEGER,
+ dm3ConfigSysDescriptionText DisplayString
+ }
+
+dm3ConfigSysDescriptionIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the DC powerplant description record."
+
+ ::= { dm3ConfigSysDescriptionEntry 1 }
+
+dm3ConfigSysDescriptionText OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "16 character text field describing the DC power plant device."
+
+ ::= { dm3ConfigSysDescriptionEntry 2 }
+
+dm3ConfigSysHighTempThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Ambient high temperature threshold. Temperature sensor located on Master
+ Controller board.
+
+ Values are represented in thousandths of a degree.
+ Units are displayed in the scale shown in
+ the 'dm3StatusSysTempUnits' OID (Celsius or Fahrenheit).
+
+ Attempts to set the value above or below the acceptable range of the powerplant
+ will cause the value to be set at the high or low point of the range respectively."
+ ::= { dm3ConfigSystem 3 }
+
+dm3ConfigSysHighTempAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ alarmIgnore (1),
+ alarmRelay1 (2),
+ alarmRelay2 (3),
+ alarmRelay3 (4),
+ alarmRelay4 (5),
+ alarmRelay5 (6),
+ alarmRelay6 (7),
+ alarmMinor (8),
+ alarmMajor (9)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "For the System High Temperature Alarm;
+ Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
+ Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
+ alarm condition.
+ Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
+ alarm condition."
+ ::= { dm3ConfigSystem 4 }
+
+dm3ConfigSysLowTempThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Ambient low temperature threshold. Temperature sensor located on Master
+ Controller board.
+
+ Values are represented in thousandths of a degree.
+ Units are displayed in the scale shown in
+ the 'dm3StatusSysTempUnits' OID (Celsius or Fahrenheit).
+
+ Attempts to set the value above or below the acceptable range of the powerplant
+ will cause the value to be set at the high or low point of the range respectively."
+ ::= { dm3ConfigSystem 5 }
+
+dm3ConfigSysLowTempAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ alarmIgnore (1),
+ alarmRelay1 (2),
+ alarmRelay2 (3),
+ alarmRelay3 (4),
+ alarmRelay4 (5),
+ alarmRelay5 (6),
+ alarmRelay6 (7),
+ alarmMinor (8),
+ alarmMajor (9)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "For the System Low Temperature Alarm;
+ Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
+ Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
+ alarm condition.
+ Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
+ alarm condition."
+ ::= { dm3ConfigSystem 6 }
+
+dm3ConfigSysHardwareTempAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ alarmIgnore (1),
+ alarmRelay1 (2),
+ alarmRelay2 (3),
+ alarmRelay3 (4),
+ alarmRelay4 (5),
+ alarmRelay5 (6),
+ alarmRelay6 (7),
+ alarmMinor (8),
+ alarmMajor (9)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "For the System Hardware Temperature Alarm;
+ Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
+ Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
+ alarm condition.
+ Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
+ alarm condition."
+ ::= { dm3ConfigSystem 7 }
+
+dm3ConfigSysRemoteAccess OBJECT-TYPE
+ SYNTAX INTEGER {
+ accessEnabled (1),
+ accessDisabled (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "
+ This OID is used to disable remote write access to the power plant.
+ Setting this OID to accessEnabled (1) will have no affect.
+ Setting this OID to accessDisabled (2) will disable the ability to
+ remotely configure the DC powerplant.
+
+ Once remote access is disabled, it can only be restored from the front
+ panel of the DC power plant."
+ ::= { dm3ConfigSystem 8 }
+
+
+-- the dm3ConfigLVD group
+
+dm3ConfigLVDTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of DC powerplant LVDs controllable
+ by this IP address."
+ ::= { dm3ConfigLVD 1 }
+
+dm3ConfigLVDTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF Dm3ConfigLVDEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for accessing settings of the LVDs. The number of
+ entries is contained in the dm3ConfigLVDTableSize OID."
+ ::= { dm3ConfigLVD 2 }
+
+dm3ConfigLVDEntry OBJECT-TYPE
+ SYNTAX Dm3ConfigLVDEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The LVD to configure."
+ INDEX { dm3ConfigLVDIndex }
+ ::= { dm3ConfigLVDTable 1 }
+
+Dm3ConfigLVDEntry ::=
+ SEQUENCE {
+ dm3ConfigLVDIndex INTEGER,
+ dm3ConfigLVDName DisplayString,
+ dm3ConfigLVDEnable INTEGER,
+ dm3ConfigLVDTripThresh INTEGER,
+ dm3ConfigLVDResetThresh INTEGER,
+ dm3ConfigLVDOpenAlarm INTEGER,
+ dm3ConfigLVDHWAlarm INTEGER
+ }
+
+dm3ConfigLVDIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the DC powerplant LVD."
+ ::= { dm3ConfigLVDEntry 1 }
+
+dm3ConfigLVDName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the LVD. The maximum value is 16 characters."
+ ::= { dm3ConfigLVDEntry 2 }
+
+dm3ConfigLVDEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ enabledYes (1),
+ enabledNo (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "This OID is used to control and indicate if the LVD is on or off.
+ Setting this OID to enabledYes (1) will enable (turn on) the LVD.
+ Setting this OID to enabledNo (2) will disable (turn off) the LVD."
+ ::= { dm3ConfigLVDEntry 3 }
+
+dm3ConfigLVDTripThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "LVD Trip threshold. If voltage exceeds threshold, the LVD will trip.
+
+ Values are represented in thousandths of Volts (mV).
+ Attempts to set the value above or below the acceptable range of the powerplant
+ will cause the value to be set at the high or low point of the range respectively."
+ ::= { dm3ConfigLVDEntry 4 }
+
+dm3ConfigLVDResetThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "LVD Reset threshold. If voltage exceeds threshold, the LVD will reset.
+
+ Values are represented in thousandths of Volts (mV).
+ Attempts to set the value above or below the acceptable range of the powerplant
+ will cause the value to be set at the high or low point of the range respectively."
+ ::= { dm3ConfigLVDEntry 5 }
+
+dm3ConfigLVDOpenAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ alarmIgnore (1),
+ alarmRelay1 (2),
+ alarmRelay2 (3),
+ alarmRelay3 (4),
+ alarmRelay4 (5),
+ alarmRelay5 (6),
+ alarmRelay6 (7),
+ alarmMinor (8),
+ alarmMajor (9)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "For the LVD Open Alarm;
+ Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
+ Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
+ alarm condition.
+ Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
+ alarm condition."
+ ::= { dm3ConfigLVDEntry 6 }
+
+dm3ConfigLVDHWAlarm OBJECT-TYPE
+SYNTAX INTEGER {
+ alarmIgnore (1),
+ alarmRelay1 (2),
+ alarmRelay2 (3),
+ alarmRelay3 (4),
+ alarmRelay4 (5),
+ alarmRelay5 (6),
+ alarmRelay6 (7),
+ alarmMinor (8),
+ alarmMajor (9)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "For the LVD Hardware Alarm;
+ Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
+ Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
+ alarm condition.
+ Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
+ alarm condition."
+ ::= { dm3ConfigLVDEntry 7 }
+
+
+-- the dm3ConfigBattery group
+
+dm3ConfigBattFloatVolt OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Battery Float Voltage. This setting controls the power plant voltage.
+
+ Values are represented in thousandths of Volts (mV).
+ Attempts to set the value above or below the acceptable range of the powerplant
+ will cause the value to be set at the high or low point of the range respectively."
+ ::= { dm3ConfigBattery 1 }
+
+dm3ConfigBattMaxRecharge OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Battery Maximum Recharge Rate. This setting controls the battery max
+ recharge rate. The value is based on C/20 for 240 AHr battery string.
+
+ Values are represented in thousandths of Amps (mA).
+ Attempts to set the value above or below the acceptable range of the powerplant
+ will cause the value to be set at the high or low point of the range respectively."
+ ::= { dm3ConfigBattery 2 }
+
+dm3ConfigBattDischargeThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Battery discharge threshold. If battery output current exceeds threshold
+ a battery discharge alarm will occur.
+
+ Values are represented in thousandths of Amps (mA).
+ Attempts to set the value above or below the acceptable range of the powerplant
+ will cause the value to be set at the high or low point of the range respectively."
+ ::= { dm3ConfigBattery 3 }
+
+dm3ConfigBattDischargeAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ alarmIgnore (1),
+ alarmRelay1 (2),
+ alarmRelay2 (3),
+ alarmRelay3 (4),
+ alarmRelay4 (5),
+ alarmRelay5 (6),
+ alarmRelay6 (7),
+ alarmMinor (8),
+ alarmMajor (9)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "For the Battery Discharge Alarm;
+ Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
+ Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
+ alarm condition.
+ Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
+ alarm condition."
+
+ ::= { dm3ConfigBattery 4 }
+
+dm3ConfigBattHighVoltThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Battery high voltage threshold. If system battery voltage exceeds threshold
+ a battery high voltage alarm will occur.
+
+ Values are represented in thousandths of Volts (mV).
+ Attempts to set the value above or below the acceptable range of the powerplant
+ will cause the value to be set at the high or low point of the range respectively."
+ ::= { dm3ConfigBattery 5 }
+
+dm3ConfigBattHighVoltAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ alarmIgnore (1),
+ alarmRelay1 (2),
+ alarmRelay2 (3),
+ alarmRelay3 (4),
+ alarmRelay4 (5),
+ alarmRelay5 (6),
+ alarmRelay6 (7),
+ alarmMinor (8),
+ alarmMajor (9)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "For the Battery High Voltage Alarm;
+ Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
+ Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
+ alarm condition.
+ Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
+ alarm condition."
+
+ ::= { dm3ConfigBattery 6 }
+
+dm3ConfigBattLowVoltThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Battery low voltage threshold. If system battery voltage is under threshold
+ a battery low voltage alarm will occur.
+
+ Values are represented in thousandths of Volts (mV).
+ Attempts to set the value above or below the acceptable range of the powerplant
+ will cause the value to be set at the high or low point of the range respectively."
+ ::= { dm3ConfigBattery 7 }
+
+dm3ConfigBattLowVoltAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ alarmIgnore (1),
+ alarmRelay1 (2),
+ alarmRelay2 (3),
+ alarmRelay3 (4),
+ alarmRelay4 (5),
+ alarmRelay5 (6),
+ alarmRelay6 (7),
+ alarmMinor (8),
+ alarmMajor (9)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "For the Battery Low Voltage Alarm;
+ Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
+ Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
+ alarm condition.
+ Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
+ alarm condition."
+
+ ::= { dm3ConfigBattery 8 }
+
+dm3ConfigBattHighTempThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Battery high temperature threshold. If system battery temperature exceeds threshold
+ a battery high temperature alarm will occur.
+
+ Values are represented in thousandths of a degree.
+ Units are displayed in the scale shown in
+ the 'dm3StatusSysTempUnits' OID (Celsius or Fahrenheit).
+
+ Attempts to set the value above or below the acceptable range of the powerplant
+ will cause the value to be set at the high or low point of the range respectively."
+
+ ::= { dm3ConfigBattery 9 }
+
+dm3ConfigBattHighTempAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ alarmIgnore (1),
+ alarmRelay1 (2),
+ alarmRelay2 (3),
+ alarmRelay3 (4),
+ alarmRelay4 (5),
+ alarmRelay5 (6),
+ alarmRelay6 (7),
+ alarmMinor (8),
+ alarmMajor (9)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "For the Battery High Temperature Alarm;
+ Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
+ Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
+ alarm condition.
+ Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
+ alarm condition."
+
+ ::= { dm3ConfigBattery 10 }
+
+dm3ConfigBattLowTempThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Battery low temperature threshold. If system battery temperature is under threshold
+ a battery low temperature alarm will occur.
+
+ Values are represented in thousandths of a degree.
+ Units are displayed in the scale shown in
+ the 'dm3StatusSysTempUnits' OID (Celsius or Fahrenheit).
+
+ Attempts to set the value above or below the acceptable range of the powerplant
+ will cause the value to be set at the high or low point of the range respectively."
+
+ ::= { dm3ConfigBattery 11 }
+
+dm3ConfigBattLowTempAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ alarmIgnore (1),
+ alarmRelay1 (2),
+ alarmRelay2 (3),
+ alarmRelay3 (4),
+ alarmRelay4 (5),
+ alarmRelay5 (6),
+ alarmRelay6 (7),
+ alarmMinor (8),
+ alarmMajor (9)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "For the Battery Low Temperature Alarm;
+ Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
+ Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
+ alarm condition.
+ Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
+ alarm condition."
+
+ ::= { dm3ConfigBattery 12 }
+
+dm3ConfigBattAmpHour OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Battery Amp-Hour Size. Units are thousandths of Amp hours (mAHr).
+
+ Attempts to set the value above or below the acceptable range of the powerplant
+ will cause the value to be set at the high or low point of the range respectively."
+ ::= { dm3ConfigBattery 13 }
+
+dm3ConfigCompMethod OBJECT-TYPE
+ SYNTAX INTEGER {
+ tempcompOn (1),
+ tempcompOff (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "This OID is used to configure and get the state of the battery
+ temperature compensation.
+
+ Setting this OID to tempcompOn (1) will enable/turn on the battery temperature compensation.
+ Setting this OID to tempcompOff (2) will disable/turn off the battery temperature compensation."
+ ::= { dm3ConfigBattery 14 }
+
+dm3ConfigCompTempCoeff OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Compensation Temperature Coefficient. (uV/degC/cell).
+
+ Units are presented in microvolts.
+ Attempts to set the value above or below the acceptable range of the powerplant
+ will cause the value to be set at the high or low point of the range respectively."
+ ::= { dm3ConfigBattery 15 }
+
+dm3ConfigHighKneeTemp OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "High Knee for temperature compensation: Compensation temperature coefficient
+ becomes 0mV/degC/cell.
+
+ Values are represented in thousandths of degrees Celsius.
+ Attempts to set the value above or below the acceptable range of the powerplant
+ will cause the value to be set at the high or low point of the range respectively."
+ ::= { dm3ConfigBattery 16 }
+
+dm3ConfigLowKneeTemp OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Low Knee for temperature compensation: Compensation temperature coefficient
+ becomes 0mV/degC/cell.
+
+ Values are represented in thousandths of degrees Celsius.
+ Attempts to set the value above or below the acceptable range of the powerplant
+ will cause the value to be set at the high or low point of the range respectively."
+ ::= { dm3ConfigBattery 17 }
+
+dm3ConfigBattHwCurrentAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ alarmIgnore (1),
+ alarmRelay1 (2),
+ alarmRelay2 (3),
+ alarmRelay3 (4),
+ alarmRelay4 (5),
+ alarmRelay5 (6),
+ alarmRelay6 (7),
+ alarmMinor (8),
+ alarmMajor (9)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "For the Battery Current Hardware Alarm (indicating current is outside realistic
+ limits, or a possible measurement fault;
+ Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
+ Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
+ alarm condition.
+ Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
+ alarm condition."
+
+ ::= { dm3ConfigBattery 18 }
+
+dm3ConfigBattHwTempAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ alarmIgnore (1),
+ alarmRelay1 (2),
+ alarmRelay2 (3),
+ alarmRelay3 (4),
+ alarmRelay4 (5),
+ alarmRelay5 (6),
+ alarmRelay6 (7),
+ alarmMinor (8),
+ alarmMajor (9)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "For the Battery Temperature Hardware Alarm (indicating temperature is outside realistic
+ limits, or a possible measurement fault;
+ Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
+ Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
+ alarm condition.
+ Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
+ alarm condition."
+
+ ::= { dm3ConfigBattery 19 }
+
+
+-- the dm3ConfigRectThresh group
+dm3ConfigRectHighVoltThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Rectifier high voltage threshold. If rectifier voltage exceeds threshold
+ a rectifier high voltage alarm will occur.
+
+ Values are represented in thousandths of Volts (mV).
+ Attempts to set the value above or below the acceptable range of the powerplant
+ will cause the value to be set at the high or low point of the range respectively."
+ ::= { dm3ConfigRectThresh 1 }
+
+
+dm3ConfigRectLowVoltThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Rectifier low voltage threshold. If rectifier voltage is under threshold
+ a rectifier low voltage alarm will occur.
+
+ Values are represented in thousandths of Volts (mV).
+ Attempts to set the value above or below the acceptable range of the powerplant
+ will cause the value to be set at the high or low point of the range respectively."
+ ::= { dm3ConfigRectThresh 2 }
+
+dm3ConfigRectFailSafe OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Rectifier Fail Safe point. This OID represents the value sent to rectifier controllers
+ to use in the event of communications loss with the Master Controller or Master Controller
+ board failure.
+
+ Values are represented in thousandths of Volts (mV).
+ Attempts to set the value above or below the acceptable range of the powerplant
+ will cause the value to be set at the high or low point of the range respectively."
+ ::= { dm3ConfigRectThresh 3 }
+
+dm3ConfigRectFailComm OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Rectifier Communication Fail timeout. This OID represents the time interval in which there is no
+ communication between the rectifier and the master controller at which the rectifier will reset
+ all its values to default.
+
+ Values are represented in hundredths of Seconds.
+ Attempts to set the value above or below the acceptable range of the powerplant
+ will cause the value to be set at the high or low point of the range respectively."
+ ::= { dm3ConfigRectThresh 4 }
+
+-- the dm3ConfigRectAlarms group
+
+dm3ConfigRectHighVoltAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ alarmIgnore (1),
+ alarmRelay1 (2),
+ alarmRelay2 (3),
+ alarmRelay3 (4),
+ alarmRelay4 (5),
+ alarmRelay5 (6),
+ alarmRelay6 (7),
+ alarmMinor (8),
+ alarmMajor (9)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "For the Rectifier High Voltage Alarm;
+ Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
+ Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
+ alarm condition.
+ Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
+ alarm condition."
+
+ ::= { dm3ConfigRectAlarms 1 }
+
+dm3ConfigRectLowVoltAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ alarmIgnore (1),
+ alarmRelay1 (2),
+ alarmRelay2 (3),
+ alarmRelay3 (4),
+ alarmRelay4 (5),
+ alarmRelay5 (6),
+ alarmRelay6 (7),
+ alarmMinor (8),
+ alarmMajor (9)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "For the Rectifier Low Voltage Alarm;
+ Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
+ Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
+ alarm condition.
+ Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
+ alarm condition."
+
+ ::= { dm3ConfigRectAlarms 2 }
+
+dm3ConfigRectConfigAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ alarmIgnore (1),
+ alarmRelay1 (2),
+ alarmRelay2 (3),
+ alarmRelay3 (4),
+ alarmRelay4 (5),
+ alarmRelay5 (6),
+ alarmRelay6 (7),
+ alarmMinor (8),
+ alarmMajor (9)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "This alarm is activated when a new rectifier is detected;
+ Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
+ Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
+ alarm condition.
+ Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
+ alarm condition."
+
+ ::= { dm3ConfigRectAlarms 3 }
+
+dm3ConfigRect1ofNAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ alarmIgnore (1),
+ alarmRelay1 (2),
+ alarmRelay2 (3),
+ alarmRelay3 (4),
+ alarmRelay4 (5),
+ alarmRelay5 (6),
+ alarmRelay6 (7),
+ alarmMinor (8),
+ alarmMajor (9)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "This setting indicates the action if ONE rectifier of a N+1 system has failed;
+ Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
+ Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
+ alarm condition.
+ Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
+ alarm condition."
+
+ ::= { dm3ConfigRectAlarms 4 }
+
+dm3ConfigRect2ofNAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ alarmIgnore (1),
+ alarmRelay1 (2),
+ alarmRelay2 (3),
+ alarmRelay3 (4),
+ alarmRelay4 (5),
+ alarmRelay5 (6),
+ alarmRelay6 (7),
+ alarmMinor (8),
+ alarmMajor (9)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "This setting indicates the action if TWO OR MORE rectifiers of a N+1 system have failed;
+ Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
+ Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
+ alarm condition.
+ Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
+ alarm condition."
+
+ ::= { dm3ConfigRectAlarms 5 }
+
+dm3ConfigRectDiagAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ alarmIgnore (1),
+ alarmRelay1 (2),
+ alarmRelay2 (3),
+ alarmRelay3 (4),
+ alarmRelay4 (5),
+ alarmRelay5 (6),
+ alarmRelay6 (7),
+ alarmMinor (8),
+ alarmMajor (9),
+ alarmNofN (10)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "For the Rectifier Controller Diagnostics Alarm;
+ Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
+ Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
+ alarm condition.
+ Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigRect1ofNAlarm OID
+ to be activated if ONE rectifier fails in an N+1 system. It causes the alarm specified in the
+ dm3ConfigRect2ofNAlarm OID to be activated if TWO OR MORE rectifiers fail in an N+1 system."
+
+ ::= { dm3ConfigRectAlarms 6 }
+
+dm3ConfigRectImbalanceAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ alarmIgnore (1),
+ alarmRelay1 (2),
+ alarmRelay2 (3),
+ alarmRelay3 (4),
+ alarmRelay4 (5),
+ alarmRelay5 (6),
+ alarmRelay6 (7),
+ alarmMinor (8),
+ alarmMajor (9)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "For the Rectifier Imbalance Alarm;
+ Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
+ Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
+ alarm condition.
+ Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
+ alarm condition."
+
+ ::= { dm3ConfigRectAlarms 7 }
+
+dm3ConfigRectCurrLimitAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ alarmIgnore (1),
+ alarmRelay1 (2),
+ alarmRelay2 (3),
+ alarmRelay3 (4),
+ alarmRelay4 (5),
+ alarmRelay5 (6),
+ alarmRelay6 (7),
+ alarmMinor (8),
+ alarmMajor (9),
+ alarmNofN (10)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "For the Rectifier Current Limit Alarm (indicating rectifier in the Current Limit state);
+ Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
+ Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
+ alarm condition.
+ Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigRect1ofNAlarm OID
+ to be activated if ONE rectifier fails in an N+1 system. It causes the alarm specified in the
+ dm3ConfigRect2ofNAlarm OID to be activated if TWO OR MORE rectifiers fail in an N+1 system."
+
+ ::= { dm3ConfigRectAlarms 8 }
+
+dm3ConfigRectStandbyAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ alarmIgnore (1),
+ alarmRelay1 (2),
+ alarmRelay2 (3),
+ alarmRelay3 (4),
+ alarmRelay4 (5),
+ alarmRelay5 (6),
+ alarmRelay6 (7),
+ alarmMinor (8),
+ alarmMajor (9),
+ alarmNofN (10)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "For the Rectifier Standby Alarm (indicating output DC has been turned off);
+ Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
+ Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
+ alarm condition.
+ Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigRect1ofNAlarm OID
+ to be activated if ONE rectifier fails in an N+1 system. It causes the alarm specified in the
+ dm3ConfigRect2ofNAlarm OID to be activated if TWO OR MORE rectifiers fail in an N+1 system."
+
+ ::= { dm3ConfigRectAlarms 9 }
+
+dm3ConfigRectFanFailAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ alarmIgnore (1),
+ alarmRelay1 (2),
+ alarmRelay2 (3),
+ alarmRelay3 (4),
+ alarmRelay4 (5),
+ alarmRelay5 (6),
+ alarmRelay6 (7),
+ alarmMinor (8),
+ alarmMajor (9),
+ alarmNofN (10)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "For the Rectifier Fan Fail Alarm;
+ Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
+ Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
+ alarm condition.
+ Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigRect1ofNAlarm OID
+ to be activated if ONE rectifier fails in an N+1 system. It causes the alarm specified in the
+ dm3ConfigRect2ofNAlarm OID to be activated if TWO OR MORE rectifiers fail in an N+1 system."
+
+ ::= { dm3ConfigRectAlarms 10 }
+
+dm3ConfigRectFailAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ alarmIgnore (1),
+ alarmRelay1 (2),
+ alarmRelay2 (3),
+ alarmRelay3 (4),
+ alarmRelay4 (5),
+ alarmRelay5 (6),
+ alarmRelay6 (7),
+ alarmMinor (8),
+ alarmMajor (9),
+ alarmNofN (10)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "For the Rectifier Fail Alarm;
+ Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
+ Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
+ alarm condition.
+ Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigRect1ofNAlarm OID
+ to be activated if ONE rectifier fails in an N+1 system. It causes the alarm specified in the
+ dm3ConfigRect2ofNAlarm OID to be activated if TWO OR MORE rectifiers fail in an N+1 system."
+
+ ::= { dm3ConfigRectAlarms 11 }
+
+dm3ConfigRectHwVoltAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ alarmIgnore (1),
+ alarmRelay1 (2),
+ alarmRelay2 (3),
+ alarmRelay3 (4),
+ alarmRelay4 (5),
+ alarmRelay5 (6),
+ alarmRelay6 (7),
+ alarmMinor (8),
+ alarmMajor (9)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "For the Rectifier Hardware Voltage Alarm (indicating voltage outside realistic limits,
+ or a possible measurement fault);
+ Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
+ Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
+ alarm condition.
+ Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
+ alarm condition."
+
+ ::= { dm3ConfigRectAlarms 12 }
+
+
+-- the dm3ConfigConvThresh group
+
+dm3ConfigConvHighVoltThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Converter high voltage threshold. If converter voltage exceeds threshold
+ a converter high voltage alarm will occur.
+
+ Values are represented in thousandths of Volts (mV).
+ Attempts to set the value above or below the acceptable range of the powerplant
+ will cause the value to be set at the high or low point of the range respectively."
+
+ ::= { dm3ConfigConvThresh 1 }
+
+dm3ConfigConvLowVoltThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Converter low voltage threshold. If converter voltage exceeds threshold
+ a converter low voltage alarm will occur.
+
+ Values are represented in thousandths of Volts (mV).
+ Attempts to set the value above or below the acceptable range of the powerplant
+ will cause the value to be set at the high or low point of the range respectively."
+ ::= { dm3ConfigConvThresh 2 }
+
+dm3ConfigConvFailSafe OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Converter Fail Safe point. This OID represents the value sent to converter controllers
+ to use in the event of communications loss with the Master Controller or Master Controller
+ board failure.
+
+ Values are represented in thousandths of Volts (mV).
+ Attempts to set the value above or below the acceptable range of the powerplant
+ will cause the value to be set at the high or low point of the range respectively."
+ ::= { dm3ConfigConvThresh 3 }
+
+dm3ConfigConvSetPoint OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Converter Set point. This OID represents the initial set point used in the
+ voltage control loop.
+
+ Units are thousandths of Volts (mV).
+ Attempts to set the value above or below the acceptable range of the powerplant
+ will cause the value to be set at the high or low point of the range respectively."
+ ::= { dm3ConfigConvThresh 4 }
+
+dm3ConfigConvFailMax OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Converter Fail Maximum limit. This OID represents the value sent to the converter
+ controllers to define the maximum set point allowed.
+
+ Units are thousandths of Volts (mV).
+ Attempts to set the value above or below the acceptable range of the powerplant
+ will cause the value to be set at the high or low point of the range respectively."
+ ::= { dm3ConfigConvThresh 5 }
+
+dm3ConfigConvFailMin OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Converter Fail Minimum limit. This OID represents the value sent to the converter
+ controllers to define the minimum set point allowed.
+
+ Units are thousandths of Volts (mV).
+ Attempts to set the value above or below the acceptable range of the powerplant
+ will cause the value to be set at the high or low point of the range respectively."
+ ::= { dm3ConfigConvThresh 6 }
+
+dm3ConfigConvFailComm OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Converter Communication Fail timeout. This OID represents the time interval in which there is no
+ communication between the converter and the master controller at which the converter will reset
+ all its values to default.
+
+ Values are represented in hundredths of Seconds.
+ Attempts to set the value above or below the acceptable range of the powerplant
+ will cause the value to be set at the high or low point of the range respectively."
+ ::= { dm3ConfigConvThresh 7 }
+
+-- the dm3ConfigConvAlarms group
+dm3ConfigConvHighVoltAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ alarmIgnore (1),
+ alarmRelay1 (2),
+ alarmRelay2 (3),
+ alarmRelay3 (4),
+ alarmRelay4 (5),
+ alarmRelay5 (6),
+ alarmRelay6 (7),
+ alarmMinor (8),
+ alarmMajor (9)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "For the Converter High Voltage Alarm;
+ Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
+ Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
+ alarm condition.
+ Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
+ alarm condition."
+
+ ::= { dm3ConfigConvAlarms 1 }
+
+dm3ConfigConvLowVoltAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ alarmIgnore (1),
+ alarmRelay1 (2),
+ alarmRelay2 (3),
+ alarmRelay3 (4),
+ alarmRelay4 (5),
+ alarmRelay5 (6),
+ alarmRelay6 (7),
+ alarmMinor (8),
+ alarmMajor (9)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "For the Converter Low Voltage Alarm;
+ Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
+ Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
+ alarm condition.
+ Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
+ alarm condition."
+
+ ::= { dm3ConfigConvAlarms 2 }
+
+dm3ConfigConvConfigAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ alarmIgnore (1),
+ alarmRelay1 (2),
+ alarmRelay2 (3),
+ alarmRelay3 (4),
+ alarmRelay4 (5),
+ alarmRelay5 (6),
+ alarmRelay6 (7),
+ alarmMinor (8),
+ alarmMajor (9)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "For the Converter Configuration Alarm (indicating a new converter has been detected);
+ Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
+ Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
+ alarm condition.
+ Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
+ alarm condition."
+
+ ::= { dm3ConfigConvAlarms 3 }
+
+dm3ConfigConv1ofNAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ alarmIgnore (1),
+ alarmRelay1 (2),
+ alarmRelay2 (3),
+ alarmRelay3 (4),
+ alarmRelay4 (5),
+ alarmRelay5 (6),
+ alarmRelay6 (7),
+ alarmMinor (8),
+ alarmMajor (9)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "For the Converter 1ofN Alarm (indicating action if ONE converter of a N+1 system has failed);
+ Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
+ Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
+ alarm condition.
+ Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
+ alarm condition."
+
+ ::= { dm3ConfigConvAlarms 4 }
+
+dm3ConfigConv2ofNAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ alarmIgnore (1),
+ alarmRelay1 (2),
+ alarmRelay2 (3),
+ alarmRelay3 (4),
+ alarmRelay4 (5),
+ alarmRelay5 (6),
+ alarmRelay6 (7),
+ alarmMinor (8),
+ alarmMajor (9)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "For the Converter 2ofN Alarm (indicating action if TWO OR MORE converters of a N+1 system has failed);
+ Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
+ Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
+ alarm condition.
+ Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
+ alarm condition."
+
+ ::= { dm3ConfigConvAlarms 5 }
+
+dm3ConfigConvDiagAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ alarmIgnore (1),
+ alarmRelay1 (2),
+ alarmRelay2 (3),
+ alarmRelay3 (4),
+ alarmRelay4 (5),
+ alarmRelay5 (6),
+ alarmRelay6 (7),
+ alarmMinor (8),
+ alarmMajor (9),
+ alarmNofN (10)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "For the Converter Diagnostics Alarm;
+ Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
+ Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
+ alarm condition.
+ Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigConv1ofNAlarm OID
+ to be activated if ONE converter fails in an N+1 system. It causes the alarm specified in the
+ dm3ConfigConv2ofNAlarm OID to be activated if TWO OR MORE converters fail in an N+1 system."
+
+ ::= { dm3ConfigConvAlarms 6 }
+
+dm3ConfigConvImbalanceAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ alarmIgnore (1),
+ alarmRelay1 (2),
+ alarmRelay2 (3),
+ alarmRelay3 (4),
+ alarmRelay4 (5),
+ alarmRelay5 (6),
+ alarmRelay6 (7),
+ alarmMinor (8),
+ alarmMajor (9),
+ alarmNofN (10)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "For the Converter Imbalance Alarm;
+ Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
+ Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
+ alarm condition.
+ Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigConv1ofNAlarm OID
+ to be activated if ONE converter fails in an N+1 system. It causes the alarm specified in the
+ dm3ConfigConv2ofNAlarm OID to be activated if TWO OR MORE converters fail in an N+1 system."
+
+ ::= { dm3ConfigConvAlarms 7 }
+
+dm3ConfigConvCurrLimitAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ alarmIgnore (1),
+ alarmRelay1 (2),
+ alarmRelay2 (3),
+ alarmRelay3 (4),
+ alarmRelay4 (5),
+ alarmRelay5 (6),
+ alarmRelay6 (7),
+ alarmMinor (8),
+ alarmMajor (9),
+ alarmNofN (10)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "For the Converter Current Limit Alarm (indicating the converter is in the Current Limit state);
+ Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
+ Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
+ alarm condition.
+ Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigConv1ofNAlarm OID
+ to be activated if ONE converter fails in an N+1 system. It causes the alarm specified in the
+ dm3ConfigConv2ofNAlarm OID to be activated if TWO OR MORE converters fail in an N+1 system."
+
+ ::= { dm3ConfigConvAlarms 8 }
+
+dm3ConfigConvStandbyAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ alarmIgnore (1),
+ alarmRelay1 (2),
+ alarmRelay2 (3),
+ alarmRelay3 (4),
+ alarmRelay4 (5),
+ alarmRelay5 (6),
+ alarmRelay6 (7),
+ alarmMinor (8),
+ alarmMajor (9),
+ alarmNofN (10)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "For the Converter Standby Alarm (indicating the converter is in the Standby state);
+ Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
+ Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
+ alarm condition.
+ Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigConv1ofNAlarm OID
+ to be activated if ONE converter fails in an N+1 system. It causes the alarm specified in the
+ dm3ConfigConv2ofNAlarm OID to be activated if TWO OR MORE converters fail in an N+1 system."
+
+ ::= { dm3ConfigConvAlarms 9 }
+
+dm3ConfigConvFanFailAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ alarmIgnore (1),
+ alarmRelay1 (2),
+ alarmRelay2 (3),
+ alarmRelay3 (4),
+ alarmRelay4 (5),
+ alarmRelay5 (6),
+ alarmRelay6 (7),
+ alarmMinor (8),
+ alarmMajor (9),
+ alarmNofN (10)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "For the Converter Fan Fail Alarm;
+ Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
+ Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
+ alarm condition.
+ Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigConv1ofNAlarm OID
+ to be activated if ONE converter fails in an N+1 system. It causes the alarm specified in the
+ dm3ConfigConv2ofNAlarm OID to be activated if TWO OR MORE converters fail in an N+1 system."
+
+ ::= { dm3ConfigConvAlarms 10 }
+
+dm3ConfigConvFailAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ alarmIgnore (1),
+ alarmRelay1 (2),
+ alarmRelay2 (3),
+ alarmRelay3 (4),
+ alarmRelay4 (5),
+ alarmRelay5 (6),
+ alarmRelay6 (7),
+ alarmMinor (8),
+ alarmMajor (9),
+ alarmNofN (10)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "For the Converter Fail Alarm;
+ Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
+ Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
+ alarm condition.
+ Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigConv1ofNAlarm OID
+ to be activated if ONE converter fails in an N+1 system. It causes the alarm specified in the
+ dm3ConfigConv2ofNAlarm OID to be activated if TWO OR MORE converters fail in an N+1 system."
+
+ ::= { dm3ConfigConvAlarms 11 }
+
+dm3ConfigConvHwVoltAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ alarmIgnore (1),
+ alarmRelay1 (2),
+ alarmRelay2 (3),
+ alarmRelay3 (4),
+ alarmRelay4 (5),
+ alarmRelay5 (6),
+ alarmRelay6 (7),
+ alarmMinor (8),
+ alarmMajor (9),
+ alarmNofN (10)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "For the Converter Voltage Alarm (indicating voltage outside realistic limits, or a
+ possible measurement fault);
+ Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
+ Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
+ alarm condition.
+ Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigConv1ofNAlarm OID
+ to be activated if ONE converter fails in an N+1 system. It causes the alarm specified in the
+ dm3ConfigConv2ofNAlarm OID to be activated if TWO OR MORE converters fail in an N+1 system."
+
+ ::= { dm3ConfigConvAlarms 12 }
+
+
+-- the dm3ConfigOutputRelays group
+
+dm3ConfigOutRlyTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of DC powerplant Output Relays controllable
+ by this IP address."
+ ::= { dm3ConfigOutputRelays 1 }
+
+dm3ConfigOutRlyTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF Dm3ConfigOutRlyEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for accessing settings of the Output Relays. The number of
+ entries is contained in the dm3ConfigOutRlyTableSize OID."
+ ::= { dm3ConfigOutputRelays 2 }
+
+dm3ConfigOutRlyEntry OBJECT-TYPE
+ SYNTAX Dm3ConfigOutRlyEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The output relay to configure."
+ INDEX { dm3ConfigOutRlyIndex }
+ ::= { dm3ConfigOutRlyTable 1 }
+
+Dm3ConfigOutRlyEntry ::=
+ SEQUENCE {
+ dm3ConfigOutRlyIndex INTEGER,
+ dm3ConfigOutRlyName DisplayString,
+ dm3ConfigOutRlyDelay INTEGER,
+ dm3ConfigOutRlyAlarm INTEGER
+ }
+
+dm3ConfigOutRlyIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the DC powerplant output relay."
+ ::= { dm3ConfigOutRlyEntry 1 }
+
+dm3ConfigOutRlyName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the output relay. The maximum value is 16 characters."
+ ::= { dm3ConfigOutRlyEntry 2 }
+
+dm3ConfigOutRlyDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Output Relay Delay. This OID represents the time delay from the initiation of an
+ output relay action to when the output relay action does occur. If the alarm condition
+ disappears before the end of the delay, no action will occur. Delay for Major
+ and Minor alarms is not configurable and is always set to 0.
+
+ Values are represented in hundredths of seconds.
+ Attempts to set the value above or below the acceptable range of the powerplant
+ will cause the value to be set at the high or low point of the range respectively."
+ ::= { dm3ConfigOutRlyEntry 3 }
+
+dm3ConfigOutRlyAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ alarmIgnore (1),
+ alarmRelay1 (2),
+ alarmRelay2 (3),
+ alarmRelay3 (4),
+ alarmRelay4 (5),
+ alarmRelay5 (6),
+ alarmRelay6 (7),
+ alarmMinor (8),
+ alarmMajor (9)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Output Relay Alarm. This setting indicates what action to perform in the event of
+ an output relay alarm condition;
+ Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
+ Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
+ alarm condition.
+ Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
+ alarm condition.
+
+ Relay Alarm for Major and Minor alarms is not configurable and is always set to
+ alarmMajor and alarmMinor respectively."
+
+ ::= { dm3ConfigOutRlyEntry 4 }
+
+
+-- the dm3ConfigInputRelays group
+
+dm3ConfigInRlyTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of DC powerplant Input Relays controllable
+ by this IP address."
+ ::= { dm3ConfigInputRelays 1 }
+
+dm3ConfigInRlyTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF Dm3ConfigInRlyEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for accessing settings of the Input Relays. The number of
+ entries is contained in the dm3ConfigInRlyTableSize OID."
+ ::= { dm3ConfigInputRelays 2 }
+
+dm3ConfigInRlyEntry OBJECT-TYPE
+ SYNTAX Dm3ConfigInRlyEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The input relay to configure."
+ INDEX { dm3ConfigInRlyIndex }
+ ::= { dm3ConfigInRlyTable 1 }
+
+Dm3ConfigInRlyEntry ::=
+ SEQUENCE {
+ dm3ConfigInRlyIndex INTEGER,
+ dm3ConfigInRlyName DisplayString,
+ dm3ConfigInRlyDelay INTEGER,
+ dm3ConfigInRlyAlarm INTEGER
+ }
+
+dm3ConfigInRlyIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the DC powerplant input relay."
+ ::= { dm3ConfigInRlyEntry 1 }
+
+dm3ConfigInRlyName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the input relay. The maximum value is 16 characters."
+
+ ::= { dm3ConfigInRlyEntry 2 }
+
+dm3ConfigInRlyDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Input Relay Delay. This OID represents the time delay from the initiation of an
+ input relay action to when the input relay action does occur. If the alarm condition
+ disappears before the end of the delay, no action will occur.
+
+ Values are represented in hundredths of seconds.
+
+ Attempts to set the value above or below the acceptable range of the powerplant
+ will cause the value to be set at the high or low point of the range respectively."
+ ::= { dm3ConfigInRlyEntry 3 }
+
+dm3ConfigInRlyAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ alarmIgnore (1),
+ alarmRelay1 (2),
+ alarmRelay2 (3),
+ alarmRelay3 (4),
+ alarmRelay4 (5),
+ alarmRelay5 (6),
+ alarmRelay6 (7),
+ alarmMinor (8),
+ alarmMajor (9)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Input Relay Alarm. This setting indicates what action to perform in the event of
+ an input relay alarm condition;
+ Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
+ Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
+ alarm condition.
+ Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
+ alarm condition."
+
+ ::= { dm3ConfigInRlyEntry 4 }
+
+-- the dm3ConfigBreakers group
+
+dm3ConfigBreakersTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of DC powerplant circuit breakers controllable
+ by this IP address."
+ ::= { dm3ConfigBreakers 1 }
+
+dm3ConfigBreakersTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF Dm3ConfigBreakersEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for accessing settings of the circuit breakers. The number of
+ entries is contained in the dm3ConfigBreakersTableSize OID."
+ ::= { dm3ConfigBreakers 2 }
+
+dm3ConfigBreakersEntry OBJECT-TYPE
+ SYNTAX Dm3ConfigBreakersEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The circuit breaker to configure."
+ INDEX { dm3ConfigBreakersIndex }
+ ::= { dm3ConfigBreakersTable 1 }
+
+Dm3ConfigBreakersEntry ::=
+ SEQUENCE {
+ dm3ConfigBreakersIndex INTEGER,
+ dm3ConfigBreakersName DisplayString,
+ dm3ConfigBreakersAlarm INTEGER
+ }
+
+dm3ConfigBreakersIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the DC powerplant circuit breaker."
+ ::= { dm3ConfigBreakersEntry 1 }
+
+dm3ConfigBreakersName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the circuit breaker. The maximum value is 16 characters."
+ ::= { dm3ConfigBreakersEntry 2 }
+
+dm3ConfigBreakersAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ alarmIgnore (1),
+ alarmRelay1 (2),
+ alarmRelay2 (3),
+ alarmRelay3 (4),
+ alarmRelay4 (5),
+ alarmRelay5 (6),
+ alarmRelay6 (7),
+ alarmMinor (8),
+ alarmMajor (9)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Circuit Breaker Alarm. This setting indicates what action to perform in the event of
+ a circuit breaker alarm condition;
+ Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
+ Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
+ alarm condition.
+ Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
+ alarm condition."
+
+ ::= { dm3ConfigBreakersEntry 3 }
+
+-- the dm3ConfigFuses group
+
+dm3ConfigFusesTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of DC powerplant Fuses controllable
+ by this IP address."
+ ::= { dm3ConfigFuses 1 }
+
+dm3ConfigFusesTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF Dm3ConfigFusesEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for accessing settings of the Fuses. The number of
+ entries is contained in the dm3ConfigFusesTableSize OID."
+ ::= { dm3ConfigFuses 2 }
+
+dm3ConfigFusesEntry OBJECT-TYPE
+ SYNTAX Dm3ConfigFusesEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The fuse to configure."
+ INDEX { dm3ConfigFusesIndex }
+ ::= { dm3ConfigFusesTable 1 }
+
+Dm3ConfigFusesEntry ::=
+ SEQUENCE {
+ dm3ConfigFusesIndex INTEGER,
+ dm3ConfigFusesName DisplayString,
+ dm3ConfigFusesAlarm INTEGER
+ }
+
+dm3ConfigFusesIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the DC powerplant fuse."
+ ::= { dm3ConfigFusesEntry 1 }
+
+dm3ConfigFusesName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the fuse. The maximum value is 16 characters."
+ ::= { dm3ConfigFusesEntry 2 }
+
+dm3ConfigFusesAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ alarmIgnore (1),
+ alarmRelay1 (2),
+ alarmRelay2 (3),
+ alarmRelay3 (4),
+ alarmRelay4 (5),
+ alarmRelay5 (6),
+ alarmRelay6 (7),
+ alarmMinor (8),
+ alarmMajor (9)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Fuses Alarm. This setting indicates what action to perform in the event of
+ a Fuse alarm condition;
+ Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
+ Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an
+ alarm condition.
+ Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an
+ alarm condition.
+ Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an
+ alarm condition.
+ Setting this OID to alarmMajor (9) causes the Major relay to be activated for an
+ alarm condition."
+
+ ::= { dm3ConfigFusesEntry 3 }
+
+-- the dm3StatusSystem group
+
+dm3StatusSystemTemp OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "System temperature based on sensor on Master Controller PCB.
+
+ Values are represented in thousandths of a degree.
+ Units are displayed in the scale shown in
+ the 'dm3StatusSysTempUnits' OID (Celsius or Fahrenheit)."
+
+ ::= { dm3StatusSystem 1 }
+
+dm3StatusSystemStart OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Time stamp at DC powerplant initialization.
+ The time is represented as MMM,DD,YYYY,HH:MM:SS."
+ ::= { dm3StatusSystem 2 }
+
+dm3StatusSysRemoteAccess OBJECT-TYPE
+ SYNTAX INTEGER {
+ accessEnabled (1),
+ accessDisabled (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Remote Access indicator
+ This setting indicates if configuration (write) access to the powerplant is enabled or
+ disabled at the powerplant level.
+ This value will be accessEnabled (1) if remote configuration is enabled, and
+ accessDisabled (2) if remote configuration is disabled."
+ ::= { dm3StatusSystem 3 }
+
+dm3StatusSysSecurityLevel OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This variable shows the current active security access level of controller. This
+ can only be changed directly from the front panel."
+ ::= { dm3StatusSystem 4 }
+
+dm3StatusSysTempSanity OBJECT-TYPE
+ SYNTAX INTEGER{
+ saneYES (1),
+ saneNO (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "System temperature sanity indicator. Indicates if the system temperature is
+ reasonable. Reasonable is defined based on powerplant type. A value of saneYes (1)
+ indicates temperature is reasonable, a value of saneNo (2) indicates it is not."
+ ::= { dm3StatusSystem 5 }
+
+dm3StatusSysAlarmState OBJECT-TYPE
+ SYNTAX INTEGER{
+ alarmMinor (1),
+ alarmMajor (2),
+ alarmBoth (3),
+ alarmNone (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "System Alarm State. Reflects the alarm status of the overall DC system.
+ If a minor alarm is present, the value will be alarmMinor(1).
+ If a major alarm is present, the value will be alarmMajor(2).
+ If both minor and a major alarm is present, the value will be alarmBoth(3).
+ If no alarm is present, the value will be alarmNone(4)."
+ ::= { dm3StatusSystem 6 }
+
+dm3StatusSysTempUnits OBJECT-TYPE
+ SYNTAX INTEGER {
+ celsius(1),
+ fahrenheit(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature scale used to display the temperature
+ in the DC system, Celsius(1) or Fahrenheit(2).
+ This setting is based on the system preferences
+ configuration in the agent."
+ ::= { dm3StatusSystem 7 }
+
+
+-- the dm3StatusAlarms group
+
+dm3StatusAlarmsTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of DC powerplant alarms viewable
+ by this IP address."
+ ::= { dm3StatusAlarms 1 }
+
+dm3StatusAlarmsTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF Dm3StatusAlarmsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for accessing system alarms. The number of
+ entries is contained in the dm3StatusAlarmsTableSize OID."
+ ::= { dm3StatusAlarms 2 }
+
+dm3StatusAlarmsEntry OBJECT-TYPE
+ SYNTAX Dm3StatusAlarmsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The alarm to display."
+ INDEX { dm3StatusAlarmsIndex }
+ ::= { dm3StatusAlarmsTable 1 }
+
+Dm3StatusAlarmsEntry ::=
+ SEQUENCE {
+ dm3StatusAlarmsIndex INTEGER,
+ dm3StatusAlarmsText DisplayString
+ }
+
+dm3StatusAlarmsIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of the system alarm."
+ ::= { dm3StatusAlarmsEntry 1 }
+
+dm3StatusAlarmsText OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The 16 character text describing the active alarm condition."
+ ::= { dm3StatusAlarmsEntry 2 }
+
+-- the dm3StatusBattery group
+
+dm3StatusBattCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Battery Current: This OID shows the battery current in thousandths of Amps (mA)."
+ ::= { dm3StatusBattery 1 }
+
+dm3StatusBattTemp OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Battery Temperature:
+
+ Values are represented in thousandths of a degree.
+ Units are displayed in the scale shown in
+ the 'dm3StatusSysTempUnits' OID (Celsius or Fahrenheit)."
+
+ ::= { dm3StatusBattery 2 }
+
+dm3StatusBattCurrentSanity OBJECT-TYPE
+ SYNTAX INTEGER{
+ saneYES (1),
+ saneNO (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Battery current sanity indicator. Indicates if the battery current is
+ reasonable. Reasonable is defined based on powerplant type. A value of saneYes (1)
+ indicates current is reasonable, a value of saneNo (2) indicates it is not."
+ ::= { dm3StatusBattery 3 }
+
+dm3StatusBattTempSanity OBJECT-TYPE
+ SYNTAX INTEGER{
+ saneYES (1),
+ saneNO (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Battery temperature sanity indicator. Indicates if the battery temperature is
+ reasonable. Reasonable is defined based on powerplant type. A value of saneYes (1)
+ indicates temperature is reasonable, a value of saneNo (2) indicates it is not."
+ ::= { dm3StatusBattery 4 }
+
+-- the dm3StatusOEM group
+
+dm3StatusOEMrectOffset OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID shows the rectifier offset value in thousandths of Volts (mV)."
+ ::= { dm3StatusOEM 1 }
+
+dm3StatusOEMrectGain OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID shows the rectifier gain value in thousandths of Volts (mV/V)."
+ ::= { dm3StatusOEM 2 }
+
+dm3StatusOEMconvOffset OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID shows the converter offset value in thousandths of Volts (mV)."
+ ::= { dm3StatusOEM 3 }
+
+dm3StatusOEMconvGain OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID shows the converter gain value in thousandths of Volts (mV/V)."
+ ::= { dm3StatusOEM 4 }
+
+dm3StatusOEMshuntOffset OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID shows the shunt offset value in thousandths of Amps (mA)."
+ ::= { dm3StatusOEM 5 }
+
+dm3StatusOEMshuntGain OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID shows the shunt gain value in thousandths of Amps (mA/A)."
+ ::= { dm3StatusOEM 6 }
+
+-- the dm3StatusLVD group
+
+dm3StatusLVDTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of DC powerplant LVDs viewable
+ by this IP address."
+ ::= { dm3StatusLVD 1 }
+
+dm3StatusLVDTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF Dm3StatusLVDEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for accessing settings of the LVDs. The number of
+ entries is contained in the dm3StatusLVDTableSize OID."
+ ::= { dm3StatusLVD 2 }
+
+dm3StatusLVDEntry OBJECT-TYPE
+ SYNTAX Dm3StatusLVDEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The LVD to gather status from."
+ INDEX { dm3StatusLVDIndex }
+ ::= { dm3StatusLVDTable 1 }
+
+Dm3StatusLVDEntry ::=
+ SEQUENCE {
+ dm3StatusLVDIndex INTEGER,
+ dm3StatusLVDName DisplayString,
+ dm3StatusLVDState INTEGER,
+ dm3StatusLVDHwFault INTEGER
+ }
+
+dm3StatusLVDIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the DC powerplant LVD."
+ ::= { dm3StatusLVDEntry 1 }
+
+dm3StatusLVDName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the LVD. The maximum size is
+ 16 characters. The name is set by using the
+ dm3ConfigLVDName OID.
+ This OID is provided for informational purposes only."
+ ::= { dm3StatusLVDEntry 2 }
+
+dm3StatusLVDState OBJECT-TYPE
+ SYNTAX INTEGER {
+ statusClosed (1),
+ statusOpened (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return statusClosed (1) if the LVD is closed.
+ statusOpened (2) will be returned if the LVD is opened."
+ ::= { dm3StatusLVDEntry 3 }
+
+dm3StatusLVDHwFault OBJECT-TYPE
+ SYNTAX INTEGER {
+ statusFault (1),
+ statusNofault (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return statusFault (1) if the LVD is faulted.
+ statusNofault (2) will be returned if the LVD is not faulted."
+ ::= { dm3StatusLVDEntry 4 }
+
+-- the dm3StatusRectifier group
+
+dm3StatusRectTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of DC powerplant rectifiers viewable
+ by this IP address."
+ ::= { dm3StatusRectifier 1 }
+
+dm3StatusRectTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF Dm3StatusRectEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for accessing settings of the rectifiers. The number of
+ entries is contained in the dm3StatusRectTableSize OID."
+ ::= { dm3StatusRectifier 2 }
+
+dm3StatusRectEntry OBJECT-TYPE
+ SYNTAX Dm3StatusRectEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The rectifier to gather status from."
+ INDEX { dm3StatusRectIndex }
+ ::= { dm3StatusRectTable 1 }
+
+Dm3StatusRectEntry ::=
+ SEQUENCE {
+ dm3StatusRectIndex INTEGER,
+ dm3StatusRectID INTEGER,
+ dm3StatusRectDesc DisplayString,
+ dm3StatusRectCurrent INTEGER,
+ dm3StatusRectCurrentLimit INTEGER,
+ dm3StatusRectStandby INTEGER,
+ dm3StatusRectFanFail INTEGER,
+ dm3StatusRectFail INTEGER,
+ dm3StatusRectDevType INTEGER,
+ dm3StatusRectPhyAddr INTEGER,
+ dm3StatusRectCfg INTEGER,
+ dm3StatusRectPcbRev INTEGER,
+ dm3StatusRectFwVer INTEGER,
+ dm3StatusRectPresent INTEGER,
+ dm3StatusRectDiagPass INTEGER,
+ dm3StatusRectState INTEGER
+ }
+
+dm3StatusRectIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the DC powerplant rectifier."
+ ::= { dm3StatusRectEntry 1 }
+
+dm3StatusRectID OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID shows the rectifier ID. This enumerates the number of the rectifier within
+ a group of rectifiers."
+ ::= { dm3StatusRectEntry 2 }
+
+dm3StatusRectDesc OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID shows the 16-character rectifier description."
+ ::= { dm3StatusRectEntry 3 }
+
+dm3StatusRectCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID shows the rectifier current in thousandths of Amps (mA)."
+ ::= { dm3StatusRectEntry 4 }
+
+dm3StatusRectCurrentLimit OBJECT-TYPE
+ SYNTAX INTEGER {
+ statusTrue (1),
+ statusFalse (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return statusTrue (1) if the rectifier is in the Current Limit state.
+ statusFalse (2) will be returned if the rectifier is not in the Current Limit state."
+ ::= { dm3StatusRectEntry 5 }
+
+dm3StatusRectStandby OBJECT-TYPE
+ SYNTAX INTEGER {
+ statusTrue (1),
+ statusFalse (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return statusTrue (1) if the rectifier is in the Standby state.
+ statusFalse (2) will be returned if the rectifier is not in the Standby state."
+ ::= { dm3StatusRectEntry 6 }
+
+dm3StatusRectFanFail OBJECT-TYPE
+ SYNTAX INTEGER {
+ statusTrue (1),
+ statusFalse (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return statusTrue (1) if the rectifier Fan has failed.
+ statusFalse (2) will be returned if the rectifier Fan has not failed."
+ ::= { dm3StatusRectEntry 7 }
+
+dm3StatusRectFail OBJECT-TYPE
+ SYNTAX INTEGER {
+ statusTrue (1),
+ statusFalse (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return statusTrue (1) if the rectifier has failed.
+ statusFalse (2) will be returned if the rectifier has not failed."
+ ::= { dm3StatusRectEntry 8 }
+
+dm3StatusRectDevType OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID shows the rectifier device type."
+ ::= { dm3StatusRectEntry 9 }
+
+dm3StatusRectPhyAddr OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID shows the rectifier physical address (the address on the bus)."
+ ::= { dm3StatusRectEntry 10 }
+
+dm3StatusRectCfg OBJECT-TYPE
+ SYNTAX INTEGER {
+ statusTrue (1),
+ statusFalse (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return statusTrue (1) if the rectifier is present after
+ power-up or set-configuration.
+ statusFalse (2) will be returned if the rectifier is not configured."
+ ::= { dm3StatusRectEntry 11 }
+
+dm3StatusRectPcbRev OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID shows the rectifier device PCB serial number."
+ ::= { dm3StatusRectEntry 12 }
+
+dm3StatusRectFwVer OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID shows the rectifier device firmware revision."
+ ::= { dm3StatusRectEntry 13 }
+
+dm3StatusRectPresent OBJECT-TYPE
+ SYNTAX INTEGER {
+ statusTrue (1),
+ statusFalse (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return statusTrue (1) if the rectifier is present.
+ statusFalse (2) will be returned if the rectifier is not present."
+ ::= { dm3StatusRectEntry 14 }
+
+dm3StatusRectDiagPass OBJECT-TYPE
+ SYNTAX INTEGER {
+ statusTrue (1),
+ statusFalse (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return statusTrue (1) if the rectifier diagnostics have passed.
+ statusFalse (2) will be returned if the rectifier diagnostics have not passed."
+ ::= { dm3StatusRectEntry 15 }
+
+dm3StatusRectState OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID shows the rectifier device state as defined by the device status register."
+ ::= { dm3StatusRectEntry 16 }
+
+dm3StatusSysRectVoltSanity OBJECT-TYPE
+ SYNTAX INTEGER {
+ saneYES (1),
+ saneNO (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Rectifier voltage sanity indicator. Indicates if the rectifier voltage is
+ reasonable. Reasonable is defined based on powerplant type. A value of saneYes (1)
+ indicates voltage is reasonable, a value of saneNo (2) indicates it is not."
+ ::= { dm3StatusRectifier 3 }
+
+dm3StatusSysRectAvailable OBJECT-TYPE
+ SYNTAX INTEGER {
+ statusTrue (1),
+ statusFalse (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return statusTrue (1) if the rectifier is available.
+ statusFalse (2) will be returned if the rectifier is not available."
+ ::= { dm3StatusRectifier 4 }
+
+dm3StatusSysRectType OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID shows the type of rectifier the system has. There can only be a single type of
+ rectifier in the power plant"
+ ::= { dm3StatusRectifier 5 }
+
+dm3StatusSysRectVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID shows the system level rectifier voltage in thousandths of Volts (mV)."
+ ::= { dm3StatusRectifier 6 }
+
+dm3StatusSysRectCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID shows the system level rectifier current in thousandths of Amps (mA)."
+ ::= { dm3StatusRectifier 7 }
+
+
+-- the dm3StatusConverter group
+
+dm3StatusConvTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of DC powerplant converters viewable
+ by this IP address."
+ ::= { dm3StatusConverter 1 }
+
+dm3StatusConvTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF Dm3StatusConvEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for viewing status of the converters. The number of
+ entries is contained in the dm3StatusConvTableSize OID."
+ ::= { dm3StatusConverter 2 }
+
+dm3StatusConvEntry OBJECT-TYPE
+ SYNTAX Dm3StatusConvEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The converter to gather status from."
+ INDEX { dm3StatusConvIndex }
+ ::= { dm3StatusConvTable 1 }
+
+Dm3StatusConvEntry ::=
+ SEQUENCE {
+ dm3StatusConvIndex INTEGER,
+ dm3StatusConvID INTEGER,
+ dm3StatusConvDesc DisplayString,
+ dm3StatusConvCurrent INTEGER,
+ dm3StatusConvCurrentLimit INTEGER,
+ dm3StatusConvStandby INTEGER,
+ dm3StatusConvFanFail INTEGER,
+ dm3StatusConvFail INTEGER,
+ dm3StatusConvDevType INTEGER,
+ dm3StatusConvPhyAddr INTEGER,
+ dm3StatusConvCfg INTEGER,
+ dm3StatusConvPcbRev INTEGER,
+ dm3StatusConvFwVer INTEGER,
+ dm3StatusConvPresent INTEGER,
+ dm3StatusConvDiagPass INTEGER,
+ dm3StatusConvState INTEGER
+ }
+
+dm3StatusConvIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the DC powerplant converter."
+ ::= { dm3StatusConvEntry 1 }
+
+dm3StatusConvID OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID shows the converter ID. This enumerates the number of the converter within
+ a group of converters."
+ ::= { dm3StatusConvEntry 2 }
+
+dm3StatusConvDesc OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID shows the 16 character converter description."
+ ::= { dm3StatusConvEntry 3 }
+
+dm3StatusConvCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID shows the converter current in thousandths of Amps (mA)."
+ ::= { dm3StatusConvEntry 4 }
+
+dm3StatusConvCurrentLimit OBJECT-TYPE
+ SYNTAX INTEGER {
+ statusTrue (1),
+ statusFalse (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return statusTrue (1) if the converter is in the Current Limit state.
+ statusFalse (2) will be returned if the converter is not in the Current Limit state."
+ ::= { dm3StatusConvEntry 5 }
+
+dm3StatusConvStandby OBJECT-TYPE
+ SYNTAX INTEGER {
+ statusTrue (1),
+ statusFalse (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return statusTrue (1) if the converter is in the Standby state.
+ statusFalse (2) will be returned if the converter is not in the Standby state."
+ ::= { dm3StatusConvEntry 6 }
+
+dm3StatusConvFanFail OBJECT-TYPE
+ SYNTAX INTEGER {
+ statusTrue (1),
+ statusFalse (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return statusTrue (1) if the converter Fan has failed.
+ statusFalse (2) will be returned if the converter Fan has not failed."
+ ::= { dm3StatusConvEntry 7 }
+
+dm3StatusConvFail OBJECT-TYPE
+ SYNTAX INTEGER {
+ statusTrue (1),
+ statusFalse (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return statusTrue (1) if the converter has failed.
+ statusFalse (2) will be returned if the converter has not failed."
+ ::= { dm3StatusConvEntry 8 }
+
+dm3StatusConvDevType OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID shows the converter device type."
+ ::= { dm3StatusConvEntry 9 }
+
+dm3StatusConvPhyAddr OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID shows the converter physical address (the address on the bus)."
+ ::= { dm3StatusConvEntry 10 }
+
+dm3StatusConvCfg OBJECT-TYPE
+ SYNTAX INTEGER {
+ statusTrue (1),
+ statusFalse (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return statusTrue (1) if the converter is present after
+ power-up or set-configuration.
+ statusFalse (2) will be returned if the converter is not configured."
+ ::= { dm3StatusConvEntry 11 }
+
+dm3StatusConvPcbRev OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID shows the converter device PCB serial number."
+ ::= { dm3StatusConvEntry 12 }
+
+dm3StatusConvFwVer OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID shows the converter device firmware version."
+ ::= { dm3StatusConvEntry 13 }
+
+dm3StatusConvPresent OBJECT-TYPE
+ SYNTAX INTEGER {
+ statusTrue (1),
+ statusFalse (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return statusTrue (1) if the converter is present.
+ statusFalse (2) will be returned if the converter is not present."
+ ::= { dm3StatusConvEntry 14 }
+
+dm3StatusConvDiagPass OBJECT-TYPE
+ SYNTAX INTEGER {
+ statusTrue (1),
+ statusFalse (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return statusTrue (1) if the converter diagnostics have passed.
+ statusFalse (2) will be returned if the converter diagnostics have not passed."
+ ::= { dm3StatusConvEntry 15 }
+
+dm3StatusConvState OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID shows the converter state as defined by the device status register."
+ ::= { dm3StatusConvEntry 16 }
+
+dm3StatusSysConvVoltSanity OBJECT-TYPE
+ SYNTAX INTEGER{
+ saneYES (1),
+ saneNO (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Converter voltage sanity indicator. Indicates if the converter voltage is
+ reasonable. Reasonable is defined based on powerplant type. A value of saneYes (1)
+ indicates voltage is reasonable, a value of saneNo (2) indicates it is not."
+ ::= { dm3StatusConverter 3 }
+
+dm3StatusSysConvAvailable OBJECT-TYPE
+ SYNTAX INTEGER {
+ statusTrue (1),
+ statusFalse (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return statusTrue (1) if the converter is available.
+ statusFalse (2) will be returned if the converter is not available."
+ ::= { dm3StatusConverter 4 }
+
+dm3StatusSysConvType OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID shows the converter type."
+ ::= { dm3StatusConverter 5 }
+
+dm3StatusSysConvVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID shows the system level converter voltage in thousandths of volts (mV)."
+ ::= { dm3StatusConverter 6 }
+
+dm3StatusSysConvCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID shows the system level converter current in thousandths of Amps (mA)."
+ ::= { dm3StatusConverter 7 }
+
+-- the dm3StatusOutputRelays group
+
+dm3StatusOutRlyTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of DC powerplant output relays viewable
+ by this IP address."
+ ::= { dm3StatusOutputRelays 1 }
+
+dm3StatusOutRlyTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF Dm3StatusOutRlyEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for viewing status of the output relays. The number of
+ entries is contained in the dm3StatusOutRlyTableSize OID."
+ ::= { dm3StatusOutputRelays 2 }
+
+dm3StatusOutRlyEntry OBJECT-TYPE
+ SYNTAX Dm3StatusOutRlyEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The output relay to gather status from."
+ INDEX { dm3StatusOutRlyIndex }
+ ::= { dm3StatusOutRlyTable 1 }
+
+Dm3StatusOutRlyEntry ::=
+ SEQUENCE {
+ dm3StatusOutRlyIndex INTEGER,
+ dm3StatusOutRlyName DisplayString,
+ dm3StatusOutRlyStatus INTEGER
+ }
+
+dm3StatusOutRlyIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the DC powerplant output relay."
+ ::= { dm3StatusOutRlyEntry 1 }
+
+dm3StatusOutRlyName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the output relay. The maximum size is
+ 16 characters. The name is set by using the
+ dm3ConfigOutRlyName OID.
+ This OID is provided for informational purposes only."
+ ::= { dm3StatusOutRlyEntry 2 }
+
+dm3StatusOutRlyStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ statusOn (1),
+ statusOff (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return statusOn (1) if the output relay is enabled/on.
+ statusOff (2) will be returned if the output relay is disabled/off."
+ ::= { dm3StatusOutRlyEntry 3 }
+
+
+-- the dm3StatusInputRelays group
+
+dm3StatusInRlyTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of DC powerplant input relays viewable
+ by this IP address."
+ ::= { dm3StatusInputRelays 1 }
+
+dm3StatusInRlyTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF Dm3StatusInRlyEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for viewing status of the input relays. The number of
+ entries is contained in the dm3StatusInRlyTableSize OID."
+ ::= { dm3StatusInputRelays 2 }
+
+
+dm3StatusInRlyEntry OBJECT-TYPE
+ SYNTAX Dm3StatusInRlyEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The input relays to gather status from."
+ INDEX { dm3StatusInRlyIndex }
+ ::= { dm3StatusInRlyTable 1 }
+
+Dm3StatusInRlyEntry ::=
+ SEQUENCE {
+ dm3StatusInRlyIndex INTEGER,
+ dm3StatusInRlyName DisplayString,
+ dm3StatusInRlyStatus INTEGER
+ }
+
+dm3StatusInRlyIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the DC powerplant input relay."
+ ::= { dm3StatusInRlyEntry 1 }
+
+dm3StatusInRlyName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the input relay. The maximum size is
+ 16 characters. The name is set by using the
+ dm3ConfigInRlyName OID.
+ This OID is provided for informational purposes only."
+ ::= { dm3StatusInRlyEntry 2 }
+
+dm3StatusInRlyStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ statusOn (1),
+ statusOff (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return statusOn (1) if the input relay is enabled/on.
+ statusOff (2) will be returned if the input relay is disabled/off."
+ ::= { dm3StatusInRlyEntry 3 }
+
+-- the dm3StatusBreakers group
+
+dm3StatusBreakersTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of DC powerplant circuit breakers viewable
+ by this IP address."
+ ::= { dm3StatusBreakers 1 }
+
+dm3StatusBreakersTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF Dm3StatusBreakersEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for viewing status of the circuit breakers. The number of
+ entries is contained in the dm3StatusBreakersTableSize OID."
+ ::= { dm3StatusBreakers 2 }
+
+dm3StatusBreakersEntry OBJECT-TYPE
+ SYNTAX Dm3StatusBreakersEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The circuit breaker to gather status from."
+ INDEX { dm3StatusBreakersIndex }
+ ::= { dm3StatusBreakersTable 1 }
+
+Dm3StatusBreakersEntry ::=
+ SEQUENCE {
+ dm3StatusBreakersIndex INTEGER,
+ dm3StatusBreakersName DisplayString,
+ dm3StatusBreakersStatus INTEGER
+ }
+
+dm3StatusBreakersIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the DC powerplant circuit breaker."
+ ::= { dm3StatusBreakersEntry 1 }
+
+dm3StatusBreakersName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the circuit breaker. The maximum size is
+ 16 characters. The name is set by using the
+ dm3ConfigBreakersName OID.
+ This OID is provided for informational purposes only."
+ ::= { dm3StatusBreakersEntry 2 }
+
+dm3StatusBreakersStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ statusClosed (1),
+ statusOpen (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return statusClosed (1) if the circuit breaker is closed.
+ statusOpen (2) will be returned if the circuit breaker is open."
+ ::= { dm3StatusBreakersEntry 3 }
+
+-- the dm3StatusFuses group
+
+dm3StatusFusesTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of DC powerplant fuses controllable
+ by this IP address."
+ ::= { dm3StatusFuses 1 }
+
+dm3StatusFusesTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF Dm3StatusFusesEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for viewing status of the fuses. The number of
+ entries is contained in the dm3StatusFusesTableSize OID."
+ ::= { dm3StatusFuses 2 }
+
+dm3StatusFusesEntry OBJECT-TYPE
+ SYNTAX Dm3StatusFusesEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The fuse to gather status from."
+ INDEX { dm3StatusFusesIndex }
+ ::= { dm3StatusFusesTable 1 }
+
+Dm3StatusFusesEntry ::=
+ SEQUENCE {
+ dm3StatusFusesIndex INTEGER,
+ dm3StatusFusesName DisplayString,
+ dm3StatusFusesStatus INTEGER
+ }
+
+dm3StatusFusesIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the DC powerplant fuse."
+ ::= { dm3StatusFusesEntry 1 }
+
+dm3StatusFusesName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the fuse. The maximum size is
+ 16 characters. The name is set by using the
+ dm3ConfigFuseName OID.
+ This OID is provided for informational purposes only."
+ ::= { dm3StatusFusesEntry 2 }
+
+dm3StatusFusesStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ statusClosed (1),
+ statusOpen (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return statusClosed (1) if the fuse is closed.
+ statusOpen (2) will be returned if the fuse is open."
+ ::= { dm3StatusFusesEntry 3 }
+
+-- the atsIdent group
+
+atsIdentHardwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The hardware revision of the Automatic Transfer Switch.
+ This value is set at the factory."
+ ::= { atsIdent 1 }
+
+atsIdentFirmwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A string identifying the Automatic Transfer Switch
+ firmware revision."
+ ::= { atsIdent 2 }
+
+atsIdentFirmwareDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The date of release for this Automatic Transfer Switch
+ firmware revision. "
+ ::= { atsIdent 3 }
+
+atsIdentDateOfManufacture OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The date when the Automatic Transfer Switch was manufactured in mm/dd/yyyy format.
+ This value is set at the factory. "
+ ::= { atsIdent 4 }
+
+atsIdentModelNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A string identifying the model number of the Automatic Transfer Switch.
+ This value is set at the factory."
+ ::= { atsIdent 5 }
+
+atsIdentSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A string identifying the serial number of
+ the Automatic Transfer Switch. This value is set at the factory."
+ ::= { atsIdent 6 }
+
+atsIdentNominalLineVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "RMS Utility Voltage measured in Volts."
+ ::= { atsIdent 7 }
+
+atsIdentNominalLineFrequency OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Utility Power Frequency measured in Hertz."
+ ::= { atsIdent 8 }
+
+atsIdentDeviceRating OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This gives the device rating in Amps"
+ ::= { atsIdent 9 }
+
+
+-- the atsCalibration group
+
+-- Input Voltage Calibration Factor table
+
+ atsCalibrationNumInputs OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of inputs to this device."
+ ::= { atsCalibrationInput 1 }
+
+ atsCalibrationNumInputPhases OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of phases per input for this device."
+ ::= { atsCalibrationInput 2 }
+
+ atsCalibrationInputPhaseTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF ATSCalibrationInputPhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The number of phases per input line to this device."
+ ::= { atsCalibrationInput 3 }
+
+ atsCalibrationInputPhaseEntry OBJECT-TYPE
+ SYNTAX ATSCalibrationInputPhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing calibration information applicable to a
+ particular input phase."
+ INDEX { atsCalibrationInputTableIndex, atsCalibrationInputPhaseTableIndex }
+ ::= { atsCalibrationInputPhaseTable 1 }
+
+ ATSCalibrationInputPhaseEntry ::= SEQUENCE {
+ atsCalibrationInputTableIndex INTEGER,
+ atsCalibrationInputPhaseTableIndex INTEGER,
+ atsLineVoltageCalibrationFactor INTEGER
+ }
+
+ atsCalibrationInputTableIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input identifier."
+ ::= { atsCalibrationInputPhaseEntry 1 }
+
+ atsCalibrationInputPhaseTableIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input phase identifier."
+ ::= { atsCalibrationInputPhaseEntry 2 }
+
+ atsLineVoltageCalibrationFactor OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Line Voltage Calibration factor.
+ This value is set at the factory."
+ ::= { atsCalibrationInputPhaseEntry 3 }
+
+-- Power Supply Voltage Calibration table
+
+ atsCalibrationPowerSupplyVoltages OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of power supply voltages supported by this device.
+ This variable indicates the number of rows in the
+ atsCalibrationPowerSupplyTable."
+ ::= { atsCalibrationPowerSupply 1 }
+
+ atsCalibrationPowerSupplyVoltageTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF ATSCalibrationPowerSupplyVoltageEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of Power Supply table entries."
+ ::= { atsCalibrationPowerSupply 2 }
+
+ atsCalibrationPowerSupplyVoltageEntry OBJECT-TYPE
+ SYNTAX ATSCalibrationPowerSupplyVoltageEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular Power Supply Voltage."
+ INDEX { atsCalibrationPowerSupplyVoltageTableIndex }
+ ::= { atsCalibrationPowerSupplyVoltageTable 1 }
+
+ ATSCalibrationPowerSupplyVoltageEntry ::= SEQUENCE {
+ atsCalibrationPowerSupplyVoltageTableIndex INTEGER,
+ atsCalibrationPowerSupplyVoltage INTEGER,
+ atsPowerSupplyVoltageCalibrationFactor INTEGER
+ }
+
+ atsCalibrationPowerSupplyVoltageTableIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The power supply voltage identifier."
+ ::= { atsCalibrationPowerSupplyVoltageEntry 1 }
+
+ atsCalibrationPowerSupplyVoltage OBJECT-TYPE
+ SYNTAX INTEGER {
+ powerSupply24V(1),
+ powerSupply12V(2),
+ powerSupply(3),
+ powerSupply24VSourceB(4),
+ powerSupplyMinus12V(5)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This value describes the power supply voltage of
+ 24V Source A, 24V Source B, +12V, -12V and 5V."
+ ::= { atsCalibrationPowerSupplyVoltageEntry 2 }
+
+ atsPowerSupplyVoltageCalibrationFactor OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Line Voltage Calibration factor.
+ This value is set at the factory."
+ ::= { atsCalibrationPowerSupplyVoltageEntry 3 }
+
+-- ATS4G Power Supply Calibration
+ats4gCalibrationPowerSupplyVoltageTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF ATS4GCalibrationPowerSupplyVoltageEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of Power Supply table entries. It is not applicable to
+ AP77xx ATS units."
+ ::= { atsCalibrationPowerSupply 3 }
+
+ ats4gCalibrationPowerSupplyVoltageEntry OBJECT-TYPE
+ SYNTAX ATS4GCalibrationPowerSupplyVoltageEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular Power Supply Voltage. It is not applicable to
+ AP77xx ATS units."
+ INDEX { ats4gCalibrationPowerSupplyVoltageTableIndex }
+ ::= { ats4gCalibrationPowerSupplyVoltageTable 1 }
+
+ ATS4GCalibrationPowerSupplyVoltageEntry ::= SEQUENCE {
+ ats4gCalibrationPowerSupplyVoltageTableIndex INTEGER,
+ ats4gCalibrationPowerSupplyVoltage INTEGER,
+ ats4gPowerSupplyVoltageCalibrationFactor INTEGER
+ }
+
+ ats4gCalibrationPowerSupplyVoltageTableIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The power supply voltage identifier. It is not applicable to
+ AP77xx ATS units."
+ ::= { ats4gCalibrationPowerSupplyVoltageEntry 1 }
+
+ ats4gCalibrationPowerSupplyVoltage OBJECT-TYPE
+ SYNTAX INTEGER {
+ powerSupply24VA(1),
+ powerSupply24VB(2),
+ powerSupplyVBoostA(3),
+ powerSupplyVBoostB(4),
+ powerSupply3Dot3V(5),
+ powerSupply1Dot0V(6)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This value describes the power supply voltage of
+ 24V Source A, 24V Source B, VBoost Source A, VBoost Source B, 3.3V, 1.0V.
+ It is not applicable to AP77xx ATS units."
+ ::= { ats4gCalibrationPowerSupplyVoltageEntry 2 }
+
+ ats4gPowerSupplyVoltageCalibrationFactor OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Line Voltage Calibration factor. This value is set at the factory.
+ It is not applicable to AP77xx ATS units."
+ ::= { ats4gCalibrationPowerSupplyVoltageEntry 3 }
+
+-- Output Current Calibration table
+
+ atsCalibrationNumOutputs OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of output lines from this device.
+ This variable indicates the number of rows in the
+ atsCalibrationOutputTable."
+ ::= { atsCalibrationOutput 1 }
+
+ atsCalibrationNumOutputPhases OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of output phases utilized in this
+ device."
+ ::= { atsCalibrationOutput 2 }
+
+ atsCalibrationOutputTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF ATSCalibrationOutputEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of output table entries."
+ ::= { atsCalibrationOutput 3 }
+
+ atsCalibrationOutputEntry OBJECT-TYPE
+ SYNTAX ATSCalibrationOutputEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular output."
+ INDEX { atsCalibrationOutputTableIndex, atsCalibrationOutputPhasesTableIndex }
+ ::= { atsCalibrationOutputTable 1 }
+
+ ATSCalibrationOutputEntry ::= SEQUENCE {
+ atsCalibrationOutputTableIndex INTEGER,
+ atsCalibrationOutputPhasesTableIndex INTEGER,
+ atsOutputCurrentCalibrationFactor INTEGER
+ }
+
+ atsCalibrationOutputTableIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output identifier."
+ ::= { atsCalibrationOutputEntry 1 }
+
+ atsCalibrationOutputPhasesTableIndex OBJECT-TYPE
+ SYNTAX INTEGER{
+ phase1(1),
+ phase2(2),
+ phase3(3),
+ neutral(4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Description of each calibration factor for each
+ output phase utilized in this device and one for neutral. "
+ ::= { atsCalibrationOutputEntry 2 }
+
+ atsOutputCurrentCalibrationFactor OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output current calibration factor measured in Amps."
+ ::= { atsCalibrationOutputEntry 3 }
+
+-- Exp Begin
+-- ATS4G output current calibration
+ ats4gCalibrationOutputTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF ATS4GCalibrationOutputEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of output table entries. It is not applicable to
+ AP77xx ATS units."
+ ::= { atsCalibrationOutput 4 }
+
+ ats4gCalibrationOutputEntry OBJECT-TYPE
+ SYNTAX ATS4GCalibrationOutputEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular output."
+ INDEX { ats4gCalibrationOutputTableIndex, ats4gCalibrationOutputPhasesTableIndex}
+ ::= { ats4gCalibrationOutputTable 1 }
+
+ ATS4GCalibrationOutputEntry ::= SEQUENCE {
+ ats4gCalibrationOutputTableIndex INTEGER,
+ ats4gCalibrationOutputPhasesTableIndex INTEGER,
+ ats4gOutputCurrentCalibrationFactor INTEGER
+ }
+
+ ats4gCalibrationOutputTableIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output identifier."
+ ::= { ats4gCalibrationOutputEntry 1 }
+
+ ats4gCalibrationOutputPhasesTableIndex OBJECT-TYPE
+ SYNTAX INTEGER{
+ sourceALine(1),
+ sourneBLine(2),
+ bank1(3),
+ bank2(4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Description of each calibration factor for each output phase utilized
+ in this device and one for neutral. Bank 1 and Bank 2 are for units
+ with two circuit breakers. It is not applicable to AP77xx ATS units."
+ ::= { ats4gCalibrationOutputEntry 2 }
+
+ ats4gOutputCurrentCalibrationFactor OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output current calibration factor measured in Amps.
+ It is not applicable to AP7xxx ATS units."
+ ::= { ats4gCalibrationOutputEntry 3 }
+-- Exp End
+
+-- the atsControl group
+
+atsControlResetATS OBJECT-TYPE
+ SYNTAX INTEGER {
+ none(1),
+ reset(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this variable will cause the Automatic Transfer Switch to
+ perform a power-on reset. It is not applicable to AP44xx units."
+ ::= { atsControl 1 }
+
+atsControlClearAllAlarms OBJECT-TYPE
+ SYNTAX INTEGER {
+ none(1),
+ clear(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this variable will clear all alarms in the Automatic Transfer Switch.
+ Returns (-1) if unsupported."
+ ::= { atsControl 2 }
+
+
+-- the atsConfig group
+
+atsConfigProductName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A configurable character string."
+ ::= { atsConfig 1 }
+
+atsConfigPreferredSource OBJECT-TYPE
+ SYNTAX INTEGER {
+ sourceA(1),
+ sourceB(2),
+ none(3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "This variable returns the preferred source of power when both sources are OK."
+ ::= { atsConfig 2 }
+
+atsConfigFrontPanelLockout OBJECT-TYPE
+ SYNTAX INTEGER {
+ disableFrontPanel(1),
+ enableFrontPanel(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this variable to disableFrontPanel(1), prevents source
+ preference configuration of the Automatic Transfer Switch via the
+ Front Panel.
+ Setting this variable to enableFrontPanel(2)allows, source preference
+ configuration of the Automatic Transfer Switch via the Front Panel."
+ ::= { atsConfig 3 }
+
+atsConfigVoltageSensitivity OBJECT-TYPE
+ SYNTAX INTEGER {
+ high(1),
+ low(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "This variable defines the sensitivity to changes in voltage:
+ high(1) for best protection, low(2) for frequent small line
+ voltage changes."
+ ::= { atsConfig 4 }
+
+atsConfigTransferVoltageRange OBJECT-TYPE
+ SYNTAX INTEGER {
+ wide(1),
+ medium(2),
+ narrow(3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "This variable defines the range of acceptable voltage from a power source.
+ If the voltage measured from the selected input source is not within this
+ range, the Automatic Transfer Switch will switch over (transfer) to the
+ alternate power source."
+
+ ::= { atsConfig 5 }
+
+atsConfigCurrentLimit OBJECT-TYPE
+ SYNTAX INTEGER (0..20)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The threshold (in Amps) at which an Over Current Alarm will be generated.
+ This OID returns the overload threshold value of the
+ OID atsConfigPhaseOverLoadThreshold for the 1U ATS and
+ OID atsConfigBankOverLoadThreshold of total for the 2U ATS.
+ Setting this OID does not have any impact on the device."
+ ::= { atsConfig 6 }
+
+
+atsConfigResetValues OBJECT-TYPE
+ SYNTAX INTEGER {
+ none(1),
+ reset(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Resets the ATS configuration to its default values.
+ Returns (-1) if not supported."
+
+ ::= { atsConfig 7 }
+
+atsConfigLineVRMS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "To configure the input RMS voltage."
+
+ ::= { atsConfig 8 }
+
+atsConfigLineVRMSNarrowLimit OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "To configure the Line VRMS Narrow Limit."
+
+ ::= { atsConfig 9 }
+
+atsConfigLineVRMSMediumLimit OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "To configure the Line VRMS Medium Limit."
+
+ ::= { atsConfig 10 }
+
+atsConfigLineVRMSWideLimit OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "To configure the Line VRMS Wide Limit."
+
+ ::= { atsConfig 11 }
+
+atsConfigFrequencyDeviation OBJECT-TYPE
+ SYNTAX INTEGER {
+ one(1),
+ two(2),
+ three(3),
+ five(5),
+ ten(10)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "To configure the frequency deviation.
+ AP77xx units uses the options of 1, 2, or 3.
+ AP44xx units uses the options of 3, 5, or 10."
+ ::= { atsConfig 12 }
+
+-- Bank table
+
+atsConfigBankTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The size of the bank table."
+ ::= { atsConfig 13 }
+
+
+atsConfigBankTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF ATSConfigBankEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for configuration of each ATS bank."
+ ::= { atsConfig 14 }
+
+atsConfigBankEntry OBJECT-TYPE
+ SYNTAX ATSConfigBankEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "This gives access to bank current threshold"
+ INDEX { atsConfigBankTableIndex }
+ ::= { atsConfigBankTable 1 }
+
+ATSConfigBankEntry ::=
+ SEQUENCE {
+ atsConfigBankTableIndex INTEGER,
+ atsConfigBank INTEGER,
+ atsConfigBankLowLoadThreshold INTEGER,
+ atsConfigBankNearOverLoadThreshold INTEGER,
+ atsConfigBankOverLoadThreshold INTEGER
+ }
+
+atsConfigBankTableIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An index to the bank table entry."
+ ::= { atsConfigBankEntry 1 }
+
+atsConfigBank OBJECT-TYPE
+ SYNTAX INTEGER {
+ total (1),
+ bank1 (2),
+ bank2 (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The bank number of an ATS"
+ ::= { atsConfigBankEntry 2 }
+
+atsConfigBankLowLoadThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A threshold that indicates the current drawn is nearing
+ a low consumption condition. It is represented in Amps.
+ A warning will be issued when the load is less than the
+ threshold value.
+
+ A threshold value of 0 Amps disables this warning.
+
+ Maximum value must be less than the value returned
+ by the atsConfigBankNearOverLoadThreshold OID."
+ ::= { atsConfigBankEntry 3 }
+
+atsConfigBankNearOverLoadThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A threshold that indicates the current drawn is nearing
+ an overload condition. It is represented in Amps.
+ A warning will be issued when the load is greater than
+ or equal to the threshold value.
+
+ Minimum value must be greater than the value returned by
+ the atsConfigBankLowLoadThreshold OID.
+
+ Maximum value must be less than or equal to the value
+ returned by the atsConfigBankOverLoadThreshold OID."
+ ::= { atsConfigBankEntry 4 }
+
+atsConfigBankOverLoadThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A threshold that indicates the current drawn has entered
+ an overload condition. It is represented in Amps.
+ A warning will be issued when the load is greater than or
+ equal to the threshold value.
+
+ Minimum value must be greater than or equal to the value
+ returned by the atsConfigBankNearOverLoadThreshold OID.
+
+ Maximum value must be less than or equal to the value returned by
+ atsIdentDeviceRating OID."
+ ::= { atsConfigBankEntry 5 }
+
+-- Phase table
+
+atsConfigPhaseTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The size of the phase table."
+ ::= { atsConfig 15 }
+
+
+atsConfigPhaseTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF ATSConfigPhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for configuration of each ATS phase."
+ ::= { atsConfig 16 }
+
+atsConfigPhaseEntry OBJECT-TYPE
+ SYNTAX ATSConfigPhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "This gives access to phase threshold"
+ INDEX { atsConfigPhaseTableIndex }
+ ::= { atsConfigPhaseTable 1 }
+
+ATSConfigPhaseEntry ::=
+ SEQUENCE {
+ atsConfigPhaseTableIndex INTEGER,
+ atsConfigPhase INTEGER,
+ atsConfigPhaseLowLoadThreshold INTEGER,
+ atsConfigPhaseNearOverLoadThreshold INTEGER,
+ atsConfigPhaseOverLoadThreshold INTEGER
+ }
+
+atsConfigPhaseTableIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the phase table entry."
+ ::= { atsConfigPhaseEntry 1 }
+
+atsConfigPhase OBJECT-TYPE
+ SYNTAX INTEGER {
+ phase1 (1),
+ phase2 (2),
+ phase3 (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The phase number of an ATS"
+ ::= { atsConfigPhaseEntry 2 }
+
+atsConfigPhaseLowLoadThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A threshold that indicates the current drawn is nearing
+ a low consumption condition. It is represented in Amps.
+ A warning will be issued when the load is less than the
+ threshold value.
+
+ A threshold value of 0 Amps disables this warning.
+
+ Maximum value must be less than the value returned
+ by the atsConfigPhaseNearOverLoadThreshold OID."
+ ::= { atsConfigPhaseEntry 3 }
+
+atsConfigPhaseNearOverLoadThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A threshold that indicates the current drawn is nearing
+ an overload condition. It is represented in Amps.
+ A warning will be issued when the load is greater than
+ or equal to the threshold value.
+
+ Minimum value must be greater than the value returned by
+ the atsConfigPhaseLowLoadThreshold OID.
+
+ Maximum value must be less than or equal to the value
+ returned by the atsConfigPhaseOverLoadThreshold OID."
+ ::= { atsConfigPhaseEntry 4 }
+
+atsConfigPhaseOverLoadThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A threshold that indicates the current drawn has entered
+ an overload condition. It is represented in Amps.
+ A warning will be issued when the load is greater than or
+ equal to the threshold value.
+
+ Minimum value must be greater than or equal to the value
+ returned by the atsConfigPhaseNearOverLoadThreshold OID.
+
+ Maximum value must be less than or equal to the value
+ returned by atsIdentDeviceRating OID."
+ ::= { atsConfigPhaseEntry 5 }
+
+
+-- the atsStatus group
+
+ atsStatusCommStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ atsNeverDiscovered(1),
+ atsCommEstablished(2),
+ atsCommLost(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This variable returns the current communication status
+ of the Automatic Transfer Switch. "
+ ::= { atsStatusDeviceStatus 1 }
+
+
+ atsStatusSelectedSource OBJECT-TYPE
+ SYNTAX INTEGER {
+ sourceA(1),
+ sourceB(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This variable returns the current source of power. "
+ ::= { atsStatusDeviceStatus 2 }
+
+
+ atsStatusRedundancyState OBJECT-TYPE
+ SYNTAX INTEGER {
+ atsRedundancyLost(1),
+ atsFullyRedundant(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This variable returns the current redundancy state of the ATS.
+ atsRedundancyLost(1) indicates that the ATS is unable to
+ switch over to the alternate power source if the current source fails.
+ atsFullyRedundant(2) indicates that the ATS will switch over to
+ the alternate power source if the current source fails."
+ ::= { atsStatusDeviceStatus 3 }
+
+
+ atsStatusOverCurrentState OBJECT-TYPE
+ SYNTAX INTEGER {
+ atsOverCurrent(1),
+ atsCurrentOK(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This variable returns the output current state of the ATS.
+ atsOverCurrent(1) indicates that the ATS has exceeded the output
+ current threshold and will not allow a switch over to the alternate power
+ source if the current source fails.
+ atsCurrentOK(2) indicates that the output current is below the
+ output current threshold.
+ This OID returns the value of the OID atsOutputPhaseState for the 1U ATS and
+ OID atsOutputBankState for the 2U ATS."
+ ::= { atsStatusDeviceStatus 4 }
+
+
+ atsStatus5VPowerSupply OBJECT-TYPE
+ SYNTAX INTEGER {
+ atsPowerSupplyFailure(1),
+ atsPowerSupplyOK(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This variable returns the present state of the ATS 5V power supply.
+ atsPowerSupplyFailure(1) indicates the 5V power supply has failed
+ and that the ATS serial port Configuration Menu is not accessible .
+ atsPowerSupplyOK(2) indicates that the ATS 5V power supply
+ is operating within tolerance. This is only supported by AP77xx SKUs."
+ ::= { atsStatusDeviceStatus 5 }
+
+ atsStatus24VPowerSupply OBJECT-TYPE
+ SYNTAX INTEGER {
+ atsPowerSupplyFailure(1),
+ atsPowerSupplyOK(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This variable returns the present state of the ATS 24V power supply for Source A.
+ atsPowerSupplyFailure(1) indicates the 24V power supply has failed
+ and the ATS is unable to switch over to the alternate power source if
+ the current source fails.
+ atsPowerSupplyOK(2) indicates that the ATS 24V power supply
+ is operating within tolerance."
+ ::= { atsStatusDeviceStatus 6 }
+
+
+ atsStatus24VSourceBPowerSupply OBJECT-TYPE
+ SYNTAX INTEGER {
+ atsPowerSupplyFailure(1),
+ atsPowerSupplyOK(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This variable returns the present state of the ATS 24V power supply for Source B.
+ atsPowerSupplyFailure(1) indicates the 24V power supply has failed
+ and the ATS is unable to switch over to the alternate power source if
+ the current source fails.
+ atsPowerSupplyOK(2) indicates that the ATS 24V power supply
+ is operating within tolerance."
+ ::= { atsStatusDeviceStatus 7 }
+
+ atsStatusPlus12VPowerSupply OBJECT-TYPE
+ SYNTAX INTEGER {
+ atsPowerSupplyFailure(1),
+ atsPowerSupplyOK(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This variable returns the present state of the ATS 12V power supply.
+ atsPowerSupplyFailure(1) indicates the 12V power supply has failed
+ and the ATS is unable to monitor the current sensors.
+ atsPowerSupplyOK(2) indicates that the ATS 12V power supply
+ is operating within tolerance. This is only supported by AP77xx SKUs."
+ ::= { atsStatusDeviceStatus 8 }
+
+
+ atsStatusMinus12VPowerSupply OBJECT-TYPE
+ SYNTAX INTEGER {
+ atsPowerSupplyFailure(1),
+ atsPowerSupplyOK(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This variable returns the present state of the ATS -12V power supply.
+ atsPowerSupplyFailure(1) indicates the -12V power supply has failed
+ and the ATS is unable to monitor the current sensors.
+ atsPowerSupplyOK(2) indicates that the ATS -12V power supply
+ is operating within tolerance. This is only supported by AP77xx SKUs."
+ ::= { atsStatusDeviceStatus 9 }
+
+
+ atsStatusSwitchStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ fail(1),
+ ok(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This variable returns the status of the ATS."
+ ::= { atsStatusDeviceStatus 10 }
+
+ atsStatusFrontPanel OBJECT-TYPE
+ SYNTAX INTEGER {
+ locked(1),
+ unlocked(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This variable returns the present state of the ATS front panel.
+ locked(1): Front panel button cannot be used to change the sources.
+ unlocked(2): Front panel button can be used to change the sources. "
+
+ ::= { atsStatusDeviceStatus 11 }
+
+
+ atsStatusSourceAStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ fail(1),
+ ok(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This variable returns the status of the Source A."
+ ::= { atsStatusDeviceStatus 12 }
+
+
+ atsStatusSourceBStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ fail(1),
+ ok(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This variable returns the status of the Source B."
+ ::= { atsStatusDeviceStatus 13 }
+
+
+ atsStatusPhaseSyncStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ inSync(1),
+ outOfSync(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This variable returns the status of the phase synch."
+ ::= { atsStatusDeviceStatus 14 }
+
+
+ atsStatusVoltageOutStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ fail(1),
+ ok(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This variable returns the output voltage status."
+ ::= { atsStatusDeviceStatus 15 }
+
+
+ atsStatusHardwareStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ fail(1),
+ ok(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This variable returns the status of display board hardware."
+ ::= { atsStatusDeviceStatus 16 }
+
+ atsStatus3dot3VPowerSupply OBJECT-TYPE
+ SYNTAX INTEGER {
+ atsPowerSupplyFailure(1),
+ atsPowerSupplyOK(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This variable returns the present state of the ATS 3.3V power supply.
+ atsPowerSupplyFailure(1) indicates the 3.3V power supply has failed.
+ atsPowerSupplyOK(2) indicates that the ATS 3.3V power supply
+ is operating within tolerance. This is only supported by AP44xx units."
+ ::= {atsStatusDeviceStatus 17 }
+
+ atsStatus1Dot0VPowerSupply OBJECT-TYPE
+ SYNTAX INTEGER {
+ atsPowerSupplyFailure(1),
+ atsPowerSupplyOK(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This variable returns the present state of the ATS 1.0V power supply.
+ atsPowerSupplyFailure(1) indicates the 1V power supply has failed.
+ atsPowerSupplyOK(2) indicates that the ATS 1.0V power supply
+ is operating within tolerance. This is only supported by AP44xx units."
+ ::= {atsStatusDeviceStatus 18 }
+
+ atsStatusVBoostSourceA OBJECT-TYPE
+ SYNTAX INTEGER {
+ atsPowerSupplyFailure(1),
+ atsPowerSupplyOK(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This variable returns the present state of the ATS Source A Boost 48V voltage.
+ atsPowerSupplyFailure(1) indicates the ATS Source A Boost 48V voltage has failed.
+ atsPowerSupplyOK(2) indicates that the ATS Source A Boost 48V voltage
+ is operating within tolerance. This is only supported by AP44xx units."
+ ::= {atsStatusDeviceStatus 19 }
+
+ atsStatusVBoostSourceB OBJECT-TYPE
+ SYNTAX INTEGER {
+ atsPowerSupplyFailure(1),
+ atsPowerSupplyOK(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This variable returns the present state of the ATS Source B Boost 48V voltage.
+ atsPowerSupplyFailure(1) indicates the ATS Source B Boost 48V voltage has failed.
+ atsPowerSupplyOK(2) indicates that the ATS Source B Boost 48V voltage
+ is operating within tolerance. This is only supported by AP44xx units."
+ ::= {atsStatusDeviceStatus 20 }
+
+ atsStatusResetMaxMinValues OBJECT-TYPE
+ SYNTAX INTEGER {
+ none(1),
+ reset(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Resets the maximum and minimum ATS values:
+ atsInputMaxVoltage, atsInputMinVoltage,
+ atsInputMaxCurrent, atsInputMinCurrent,
+ atsInputMaxPower, atsInputMinPower,
+ atsOutputMaxCurrent, atsOutputMinCurrent,
+ atsOutputMaxLoad, atsOutputMinLoad,
+ atsOutputMaxPercentLoad, atsOutputMinPercentLoad,
+ atsOutputMaxPower, atsOutputMinPower,
+ atsOutputMaxPercentPower, atsOutputMinPercentPower.
+ These variables represent the maximum and minimum ATS values
+ since the last time they were read or reset by this OID.
+ Values unsupported by this ATS will return (-1)."
+ ::= { atsStatusResetValues 1 }
+
+--
+-- Input Group
+--
+-- Number of Inputs
+ atsNumInputs OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of input feeds to this device.
+ This variable indicates the number of rows in the
+ input table."
+ ::= { atsStatusInput 1 }
+
+-- Input Table
+
+ atsInputTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AtsInputEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of input table entries. The number of entries
+ is given by the value of atsNumInputs."
+ ::= { atsStatusInput 2 }
+
+ atsInputEntry OBJECT-TYPE
+ SYNTAX AtsInputEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular input."
+ INDEX { atsInputTableIndex }
+ ::= { atsInputTable 1 }
+
+ AtsInputEntry ::= SEQUENCE {
+ atsInputTableIndex INTEGER,
+ atsNumInputPhases INTEGER,
+ atsInputVoltageOrientation INTEGER,
+ atsInputFrequency INTEGER,
+ atsInputType INTEGER,
+ atsInputName DisplayString
+ }
+
+ atsInputTableIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input identifier."
+ ::= { atsInputEntry 1 }
+
+ atsNumInputPhases OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of input phases utilized in this
+ device. The sum of all the atsNumInputPhases
+ variable indicates the number of rows in the
+ input phase table."
+ ::= { atsInputEntry 2 }
+
+ atsInputVoltageOrientation OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(1),
+ singlePhase(2),
+ splitPhase(3),
+ threePhasePhaseToNeutral(4),
+ threePhasePhaseToPhase(5)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input voltage orientation:
+ 1: unknown for this Source
+ 2: singlePhase - phase 1 voltage is between Phase 1
+ and Neutral.
+ 3: splitPhase - phase 1 voltage is between Phase 1 and
+ Neutral; phase 2 voltage is between Phase 2 and Neutral;
+ phase 3 voltage is between Phase 1 and Phase 2.
+ 4: threePhasePhaseToNeutral - phase 1 voltage is between
+ Phase 1 and Neutral; phase 2 voltage is between Phase 2
+ and Neutral; phase 3 voltage is between Phase 3 and
+ Neutral.
+ 5: threePhasePhaseToPhase - phase 1 voltage is between
+ Phase 1 and Phase 2; phase 2 voltage is between Phase 2
+ and Phase 3; phase 3 voltage is between Phase 3 and
+ Phase 1."
+ ::= { atsInputEntry 3 }
+
+ atsInputFrequency OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input frequency in Hertz, or -1 if it's unsupported
+ by this Source."
+ ::= { atsInputEntry 4 }
+
+ atsInputType OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(1),
+ main(2),
+ bypass(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input type."
+ ::= { atsInputEntry 5 }
+
+ atsInputName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A name given to a particular input."
+ ::= { atsInputEntry 6 }
+
+-- Input Phase Table
+
+ atsInputPhaseTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AtsInputPhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of input table entries. The number of entries
+ is given by the sum of the atsNumInputPhases."
+ ::= { atsStatusInput 3 }
+
+ atsInputPhaseEntry OBJECT-TYPE
+ SYNTAX AtsInputPhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular input phase."
+ INDEX { atsInputPhaseTableIndex, atsInputPhaseIndex }
+ ::= { atsInputPhaseTable 1 }
+
+ AtsInputPhaseEntry ::= SEQUENCE {
+ atsInputPhaseTableIndex INTEGER,
+ atsInputPhaseIndex INTEGER,
+ atsInputVoltage INTEGER,
+ atsInputMaxVoltage INTEGER,
+ atsInputMinVoltage INTEGER,
+ atsInputCurrent INTEGER,
+ atsInputMaxCurrent INTEGER,
+ atsInputMinCurrent INTEGER,
+ atsInputPower INTEGER,
+ atsInputMaxPower INTEGER,
+ atsInputMinPower INTEGER
+ }
+
+ atsInputPhaseTableIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input identifier."
+ ::= { atsInputPhaseEntry 1 }
+
+ atsInputPhaseIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input phase identifier."
+ ::= { atsInputPhaseEntry 2 }
+
+ atsInputVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input voltage in VAC, or -1 if it's unsupported
+ by this Source."
+ ::= { atsInputPhaseEntry 3 }
+
+ atsInputMaxVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum input voltage in VAC measured
+ since the last time this variable was read
+ or reset (atsStatusResetMaxMinValues).
+ Returns (-1) if unsupported."
+ ::= { atsInputPhaseEntry 4 }
+
+ atsInputMinVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum input voltage in VAC measured
+ since the last time this variable was read
+ or reset (atsStatusResetMaxMinValues).
+ Returns (-1) if unsupported."
+ ::= { atsInputPhaseEntry 5 }
+
+ atsInputCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input current in amperes, or -1 if it's
+ unsupported by this Source."
+ ::= { atsInputPhaseEntry 6 }
+
+ atsInputMaxCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum input current in amperes measured
+ since the last time this variable was read
+ or reset (atsStatusResetMaxMinValues).
+ Returns (-1) if unsupported."
+ ::= { atsInputPhaseEntry 7 }
+
+ atsInputMinCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum input current in amperes measured
+ since the last time this variable was read
+ or reset (atsStatusResetMaxMinValues).
+ Returns (-1) if unsupported."
+ ::= { atsInputPhaseEntry 8 }
+
+ atsInputPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input power in Watts, or -1 if it's unsupported
+ by this Source."
+ ::= { atsInputPhaseEntry 9 }
+
+ atsInputMaxPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum input power in Watts measured
+ since the last time this variable was read
+ or reset (atsStatusResetMaxMinValues).
+ Returns (-1) if unsupported."
+ ::= { atsInputPhaseEntry 10 }
+
+ atsInputMinPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum input power in Watts measured
+ since the last time this variable was read
+ or reset (atsStatusResetMaxMinValues).
+ Returns (-1) if unsupported."
+ ::= { atsInputPhaseEntry 11 }
+
+ --
+ -- The Output group.
+ --
+
+ -- Number of Outputs
+
+ atsNumOutputs OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of output feeds to this device.
+ This variable indicates the number of rows in the
+ output table."
+ ::= { atsStatusOutput 1 }
+
+ -- Output Table
+
+ atsOutputTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AtsOutputEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of output table entries. The number of entries
+ is given by the value of atsOutputNumPhases."
+ ::= { atsStatusOutput 2 }
+
+ atsOutputEntry OBJECT-TYPE
+ SYNTAX AtsOutputEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular output."
+ INDEX { atsOutputTableIndex }
+ ::= { atsOutputTable 1 }
+
+ AtsOutputEntry ::= SEQUENCE {
+ atsOutputTableIndex INTEGER,
+ atsNumOutputPhases INTEGER,
+ atsOutputVoltageOrientation INTEGER,
+ atsOutputFrequency INTEGER
+ }
+
+ atsOutputTableIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output identifier."
+ ::= { atsOutputEntry 1 }
+
+ atsNumOutputPhases OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of output phases utilized in this
+ device. The sum of all the atsNumOutputPhases
+ variable indicates the number of rows in the
+ output phase table."
+ ::= { atsOutputEntry 2 }
+
+ atsOutputVoltageOrientation OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(1),
+ singlePhase(2),
+ splitPhase(3),
+ threePhasePhaseToNeutral(4),
+ threePhasePhaseToPhase(5)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output voltage orientation:
+ 1: unknown for this ATS
+ 2: singlePhase - phase 1 voltage is between Phase 1
+ and Neutral.
+ 3: splitPhase - phase 1 voltage is between Phase 1 and
+ Neutral; phase 2 voltage is between Phase 2 and Neutral;
+ phase 3 voltage is between Phase 1 and Phase 2.
+ 4: threePhasePhaseToNeutral - phase 1 voltage is between
+ Phase 1 and Neutral; phase 2 voltage is between Phase 2
+ and Neutral; phase 3 voltage is between Phase 3 and
+ Neutral.
+ 5: threePhasePhaseToPhase - phase 1 voltage is between
+ Phase 1 and Phase 2; phase 2 voltage is between Phase 2
+ and Phase 3; phase 3 voltage is between Phase 3 and
+ Phase 1."
+ ::= { atsOutputEntry 3 }
+
+ atsOutputFrequency OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output frequency in Hertz, or -1 if it's
+ unsupported by this ATS."
+ ::= { atsOutputEntry 4 }
+
+ -- Output Phase Table
+
+ atsOutputPhaseTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AtsOutputPhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of output table entries. The number of
+ entries is given by the sum of the atsNumOutputPhases."
+ ::= { atsStatusOutput 3 }
+
+ atsOutputPhaseEntry OBJECT-TYPE
+ SYNTAX AtsOutputPhaseEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular output phase."
+ INDEX { atsOutputPhaseTableIndex, atsOutputPhaseIndex }
+ ::= { atsOutputPhaseTable 1 }
+
+ AtsOutputPhaseEntry ::= SEQUENCE {
+ atsOutputPhaseTableIndex INTEGER,
+ atsOutputPhaseIndex INTEGER,
+ atsOutputVoltage INTEGER,
+ atsOutputCurrent INTEGER,
+ atsOutputMaxCurrent INTEGER,
+ atsOutputMinCurrent INTEGER,
+ atsOutputLoad INTEGER,
+ atsOutputMaxLoad INTEGER,
+ atsOutputMinLoad INTEGER,
+ atsOutputPercentLoad INTEGER,
+ atsOutputMaxPercentLoad INTEGER,
+ atsOutputMinPercentLoad INTEGER,
+ atsOutputPower INTEGER,
+ atsOutputMaxPower INTEGER,
+ atsOutputMinPower INTEGER,
+ atsOutputPercentPower INTEGER,
+ atsOutputMaxPercentPower INTEGER,
+ atsOutputMinPercentPower INTEGER,
+ atsOutputPhaseState INTEGER
+ }
+
+ atsOutputPhaseTableIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output identifier."
+ ::= { atsOutputPhaseEntry 1 }
+
+ atsOutputPhaseIndex OBJECT-TYPE
+ SYNTAX INTEGER{
+ phase1(1),
+ phase2(2),
+ phase3(3),
+ neutral(4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Description of each output phase utilized in
+ this device and one for neutral. "
+ ::= { atsOutputPhaseEntry 2 }
+
+ atsOutputVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output voltage in VAC, or -1 if it's unsupported
+ by this ATS."
+ ::= { atsOutputPhaseEntry 3 }
+
+ atsOutputCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output current in 0.1 amperes drawn
+ by the load on the ATS, or -1 if it's unsupported
+ by this ATS."
+ ::= { atsOutputPhaseEntry 4 }
+
+ atsOutputMaxCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum output current in 0.1 amperes measured
+ since the last time this variable was read
+ or reset (atsStatusResetMaxMinValues).
+ Returns (-1) if unsupported."
+ ::= { atsOutputPhaseEntry 5 }
+
+ atsOutputMinCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum output current in 0.1 amperes measured
+ since the last time this variable was read
+ or reset (atsStatusResetMaxMinValues).
+ Returns (-1) if unsupported."
+ ::= { atsOutputPhaseEntry 6 }
+
+ atsOutputLoad OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output load in VA, or -1 if it's unsupported
+ by this ATS."
+ ::= { atsOutputPhaseEntry 7 }
+
+ atsOutputMaxLoad OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum output load in VA measured
+ since the last time this variable was read
+ or reset (atsStatusResetMaxMinValues).
+ Returns (-1) if unsupported."
+ ::= { atsOutputPhaseEntry 8 }
+
+ atsOutputMinLoad OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum output load in VA measured
+ since the last time this variable was read
+ or reset (atsStatusResetMaxMinValues).
+ Returns (-1) if unsupported."
+ ::= { atsOutputPhaseEntry 9 }
+
+ atsOutputPercentLoad OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The percentage of the ATS load capacity in VA at
+ redundancy @ (n + x) presently being used on this
+ output phase, or -1 if it's unsupported by this ATS."
+ ::= { atsOutputPhaseEntry 10 }
+
+ atsOutputMaxPercentLoad OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum percentage of the ATS load capacity in
+ VA measured at redundancy @ (n + x) presently
+ being used on this output phase since the last time
+ this variable was read or reset (atsStatusResetMaxMinValues).
+ Returns (-1) if unsupported."
+ ::= { atsOutputPhaseEntry 11 }
+
+ atsOutputMinPercentLoad OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum percentage of the ATS load capacity in
+ VA measured at redundancy @ (n + x) presently
+ being used on this output phase since the last time
+ this variable was read or reset (atsStatusResetMaxMinValues).
+ Returns (-1) if unsupported."
+ ::= { atsOutputPhaseEntry 12 }
+
+ atsOutputPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output apparent power in VA, or
+ -1 if it's unsupported by this ATS."
+
+ ::= { atsOutputPhaseEntry 13 }
+
+ atsOutputMaxPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum output power in VAs measured
+ since the last time this variable was read
+ or reset (atsStatusResetMaxMinValues).
+ Returns (-1) if unsupported."
+ ::= { atsOutputPhaseEntry 14 }
+
+ atsOutputMinPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum output power in VA measured
+ since the last time this variable was read
+ or reset (atsStatusResetMaxMinValues).
+ Returns (-1) if unsupported."
+ ::= { atsOutputPhaseEntry 15 }
+
+ atsOutputPercentPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The percentage of the ATSpower capacity in VA at
+ redundancy @ (n + x) presently being used on this
+ output phase, or -1 if it's unsupported by this ATS."
+ ::= { atsOutputPhaseEntry 16 }
+
+ atsOutputMaxPercentPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum percentage of the ATSpower capacity
+ in VA measured at redundancy @ (n + x) presently
+ being used on this output phase since the last time
+ this variable was read or reset (atsStatusResetMaxMinValues).
+ Returns (-1) if unsupported."
+ ::= { atsOutputPhaseEntry 17 }
+
+ atsOutputMinPercentPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum percentage of the ATSpower capacity
+ in VA measured at redundancy @ (n + x) presently
+ being used on this output phase since the last time
+ this variable was read or reset (atsStatusResetMaxMinValues).
+ Returns (-1) if unsupported."
+ ::= { atsOutputPhaseEntry 18 }
+
+
+ atsOutputPhaseState OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ lowload (2),
+ nearoverload (3),
+ overload (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return the phase load state.
+
+ normal(1) indicates that the bank is operating properly
+ within the atsConfigPhaseLowLoadThreshold and
+ atsConfigPhaseNearOverLoadThreshold OID values.
+
+ lowload(2) indicates that the bank load has dropped below
+ the atsConfigPhaseLowLoadThreshold OID value. An SNMP trap
+ will occur when this state is entered or cleared.
+
+ nearoverload(3) indicates that the bank load is greater than
+ or equal to the atsConfigPhaseNearOverLoadThreshold OID value.
+ An SNMP trap will occur when this state is entered or cleared.
+
+ overload(4) indicates that the bank load is greater than or
+ equal to the atsConfigPhaseOverLoadThreshold OID value.
+ An SNMP trap will occur when this state is entered or cleared."
+ ::= { atsOutputPhaseEntry 19 }
+
+
+ atsOutputBankTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The size of the bank table."
+ ::= { atsStatusOutput 4 }
+
+
+ atsOutputBankTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF ATSOutputBankEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting table entries."
+ ::= { atsStatusOutput 5 }
+
+ atsOutputBankEntry OBJECT-TYPE
+ SYNTAX ATSOutputBankEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "This gives access to bank table entries"
+ INDEX { atsOutputBankTableIndex }
+ ::= { atsOutputBankTable 1 }
+
+ ATSOutputBankEntry ::=
+ SEQUENCE {
+ atsOutputBankTableIndex INTEGER,
+ atsOutputPhase INTEGER,
+ atsOutputBank INTEGER,
+ atsOutputBankCurrent Gauge,
+ atsOutputBankState INTEGER,
+ atsOutputBankOutputVoltage INTEGER,
+ atsOutputBankMaxCurrent INTEGER,
+ atsOutputBankMinCurrent INTEGER,
+ atsOutputBankLoad INTEGER,
+ atsOutputBankMaxLoad INTEGER,
+ atsOutputBankMinLoad INTEGER,
+ atsOutputBankPercentLoad INTEGER,
+ atsOutputBankMaxPercentLoad INTEGER,
+ atsOutputBankMinPercentLoad INTEGER,
+ atsOutputBankPower INTEGER,
+ atsOutputBankMaxPower INTEGER,
+ atsOutputBankMinPower INTEGER,
+ atsOutputBankPercentPower INTEGER,
+ atsOutputBankMaxPercentPower INTEGER,
+ atsOutputBankMinPercentPower INTEGER
+ }
+
+ atsOutputBankTableIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the bank table entry."
+ ::= { atsOutputBankEntry 1 }
+
+ atsOutputPhase OBJECT-TYPE
+ SYNTAX INTEGER {
+ phase1 (1),
+ phase2 (2),
+ phase3 (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The phase number of an ATS"
+ ::= { atsOutputBankEntry 2 }
+
+ atsOutputBank OBJECT-TYPE
+ SYNTAX INTEGER {
+ total (1),
+ bank1 (2),
+ bank2 (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The bank number of an ATS"
+ ::= { atsOutputBankEntry 3 }
+
+ atsOutputBankCurrent OBJECT-TYPE
+ SYNTAX Gauge
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return the bank current measured
+ in tenths of Amps."
+ ::= { atsOutputBankEntry 4 }
+
+ atsOutputBankState OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ lowload (2),
+ nearoverload (3),
+ overload (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return the bank load state.
+
+ normal(1) indicates that the bank is
+ operating properly within the atsConfigBankLowLoadThreshold
+ and atsConfigBankNearOverLoadThreshold OID values.
+
+ lowload(2) indicates that the bank load has dropped below the
+ atsConfigBankLowLoadThreshold OID value. An SNMP trap will
+ occur when this state is entered or cleared.
+
+ nearoverload(3) indicates that the bank load is greater than
+ or equal to the atsConfigBankNearOverLoadThreshold OID value.
+ An SNMP trap will occur when this state is entered or cleared.
+
+ overload(4) indicates that the bank load is greater than or
+ equal to the atsConfigBankOverLoadThreshold OID value.
+ An SNMP trap will occur when this state is entered or cleared."
+ ::= { atsOutputBankEntry 5 }
+
+ atsOutputBankOutputVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output voltage in VAC, or -1 if it's unsupported
+ by this ATS."
+ ::= { atsOutputBankEntry 6 }
+
+
+ atsOutputBankMaxCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum output current, on the bank represented by
+ OID atsOutputBank, in 0.1 amperes measured since the
+ last time this variable was read
+ or reset (atsStatusResetMaxMinValues).
+ Returns (-1) if unsupported."
+ ::= { atsOutputBankEntry 7 }
+
+ atsOutputBankMinCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum output current, on the bank represented by
+ OID atsOutputBank, in 0.1 amperes measured since the
+ last time this variable was read
+ or reset (atsStatusResetMaxMinValues).
+ Returns (-1) if unsupported."
+ ::= { atsOutputBankEntry 8 }
+
+ atsOutputBankLoad OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output load, on the bank represented by
+ OID atsOutputBank, in VA, or -1 if it's
+ unsupported by this ATS."
+ ::= { atsOutputBankEntry 9 }
+
+ atsOutputBankMaxLoad OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum output load, on the bank represented by
+ OID atsOutputBank, in VA measured since the last
+ time this variable was read
+ or reset (atsStatusResetMaxMinValues).
+ Returns (-1) if unsupported."
+ ::= { atsOutputBankEntry 10 }
+
+ atsOutputBankMinLoad OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum output load, on the bank represented by
+ OID atsOutputBank, in VA measured since the last
+ time this variable was read
+ or reset (atsStatusResetMaxMinValues).
+ Returns (-1) if unsupported."
+ ::= { atsOutputBankEntry 11 }
+
+ atsOutputBankPercentLoad OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The percentage of the ATS load capacity in VA at
+ redundancy @ (n + x) presently being used on this
+ bank, represented by OID atsOutputBank.
+ Returns (-1) if unsupported."
+ ::= { atsOutputBankEntry 12 }
+
+ atsOutputBankMaxPercentLoad OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum percentage of the ATS load capacity in
+ VA measured at redundancy @ (n + x) presently
+ being used on this bank, represented by OID atsOutputBank,
+ since the last time this variable was read or
+ reset (atsStatusResetMaxMinValues).
+ Returns (-1) if unsupported."
+ ::= { atsOutputBankEntry 13 }
+
+ atsOutputBankMinPercentLoad OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum percentage of the ATS load capacity in
+ VA measured at redundancy @ (n + x) presently
+ being used on this bank, represented by OID
+ atsOutputBank, since the last time this variable was
+ read or reset (atsStatusResetMaxMinValues).
+ Returns (-1) if unsupported."
+ ::= { atsOutputBankEntry 14 }
+
+ atsOutputBankPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output apparent power in VA on the bank represented by
+ OID atsOutputBank or -1 if it's unsupported by this ATS."
+ ::= { atsOutputBankEntry 15 }
+
+ atsOutputBankMaxPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum output power in VA measured on the bank
+ represented by OID atsOutputBank since the last
+ time this variable was read
+ or reset (atsStatusResetMaxMinValues).
+ Returns (-1) if unsupported."
+ ::= { atsOutputBankEntry 16 }
+
+ atsOutputBankMinPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum output power in VA measured on the bank
+ represented by OID atsOutputBank since the last time
+ this variable was read
+ or reset (atsStatusResetMaxMinValues).
+ Returns (-1) if unsupported."
+ ::= { atsOutputBankEntry 17 }
+
+ atsOutputBankPercentPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The percentage of the ATSpower capacity in Watts at
+ redundancy @ (n + x) presently being used on this
+ bank, represented by OID atsOutputBank, or
+ -1 if it's unsupported by this ATS."
+ ::= { atsOutputBankEntry 18 }
+
+ atsOutputBankMaxPercentPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum percentage of the ATSpower capacity
+ in VA measured at redundancy @ (n + x) presently
+ being used on this bank, represented by OID
+ atsOutputBank, since the last time this variable
+ was read or reset (atsStatusResetMaxMinValues).
+ Returns (-1) if unsupported."
+ ::= { atsOutputBankEntry 19 }
+
+ atsOutputBankMinPercentPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum percentage of the ATSpower capacity
+ in VA measured at redundancy @ (n + x) presently
+ being used on this bank, represented by OID atsOutputBank
+ since the last time this variable was read or
+ reset (atsStatusResetMaxMinValues).
+ Returns (-1) if unsupported."
+ ::= { atsOutputBankEntry 20 }
+
+
+-- the dcmim2IdentSystem group
+
+dcmim2IdentSysFWVersion OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Integer representation of the power plant Master Controller firmware revision."
+ ::= { dcmim2IdentSystem 1 }
+
+
+-- the dcmim2ControlSystem group
+
+dcmim2ControlRunFunctBatteryTest OBJECT-TYPE
+ SYNTAX INTEGER {
+ battTestOff (1),
+ battTestOn (2)
+}
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return the battery functional test state. If
+ the test is off, the battTestOff (1) value will be returned.
+ If the test is on, the battTestOn (2) value will be
+ returned.
+
+ Setting this OID to battTestOff (1) will turn the battery functional test off.
+ Setting this OID to battTestOn (2) will turn the battery functional test on."
+
+ ::= { dcmim2ControlSystem 1 }
+
+dcmim2ControlRunCapacityBatteryTest OBJECT-TYPE
+ SYNTAX INTEGER {
+ battTestOff (1),
+ battTestOn (2)
+}
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return the battery capacity test state. If
+ the test is off, the battTestOff (1) value will be returned.
+ If the test is on, the battTestOn (2) value will be
+ returned.
+
+ Setting this OID to battTestOff (1) will turn the battery capacity test off.
+ Setting this OID to battTestOn (2) will turn the battery capacity test on."
+
+ ::= { dcmim2ControlSystem 2 }
+
+
+-- the dcmim2ConfigSystem group
+
+dcmim2ConfigSysHighTempTrip OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Trip level (threshold) at which System High Temp alarm condition is created.
+ Range 28 to 100 (degC).
+
+ Values are represented in thousandths of a degree.
+ Units are displayed in the scale shown in
+ the 'dcmim2StatusSysTempUnits' OID (Celsius or Fahrenheit)."
+
+
+ ::= { dcmim2ConfigSystem 1 }
+
+dcmim2ConfigSysHighTempReset OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Level at which System High Temp alarm condition is reset (cleared).
+ Range 25 to (upper temp - 3) (degC).
+
+ Values are represented in thousandths of a degree.
+ Units are displayed in the scale shown in
+ the 'dcmim2StatusSysTempUnits' OID (Celsius or Fahrenheit)."
+
+ ::= { dcmim2ConfigSystem 2 }
+
+dcmim2ConfigSysLowTempTrip OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Trip level (threshold) at which System Low Temp alarm condition is created.
+ Range -100 to 10 (degC).
+ Values are represented in thousandths of a degree.
+ Units are displayed in the scale shown in
+ the 'dcmim2StatusSysTempUnits' OID (Celsius or Fahrenheit)."
+
+ ::= { dcmim2ConfigSystem 3 }
+
+dcmim2ConfigSysLowTempReset OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Level at which System Low Temp alarm condition is reset (cleared).
+ Range (lower temp + 3) to 13 (degC).
+ Values are represented in thousandths of a degree.
+ Units are displayed in the scale shown in
+ the 'dcmim2StatusSysTempUnits' OID (Celsius or Fahrenheit)."
+
+ ::= { dcmim2ConfigSystem 4 }
+
+-- the dcmim2ConfigBattery group
+
+dcmim2ConfigBattFloatVolt OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Battery Float Voltage defined at 25 degrees Celsius.
+
+ Values are represented in thousandths of Volts (mV)."
+
+ ::= { dcmim2ConfigBattery 1 }
+
+dcmim2ConfigBattMaxRecharge OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Battery Maximum Recharge Rate. This is the maximum current used
+ during battery charging.
+
+ Values are represented in thousandths of Amps (mA)."
+
+ ::= { dcmim2ConfigBattery 2 }
+
+dcmim2ConfigBattMfgCapacity OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Battery capacity (Amp-Hour Size) as specified by the battery manufacturer.
+
+ Values are represented in thousandths of Amp hours (mAHr)."
+
+ ::= { dcmim2ConfigBattery 3 }
+
+dcmim2ConfigBattType OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Type of battery in the powerplant
+
+ Valid values range from 0 to 254."
+
+ ::= { dcmim2ConfigBattery 4 }
+
+dcmim2ConfigBattFunctTestDuration OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Duration of the battery functional test.
+
+ Values are represented in thousandths of seconds (mSecs)."
+
+ ::= { dcmim2ConfigBattery 5 }
+
+dcmim2ConfigBattFunctTestThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold the battery voltage of the system must remain above
+ in order to pass the battery functional test.
+
+ Values are represented in thousandths of Volts (mV)."
+
+ ::= { dcmim2ConfigBattery 6 }
+
+dcmim2ConfigBattCapacityTestPercent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold for good battery capacity test results.
+
+ Values range from 0 to 100 percent."
+
+ ::= { dcmim2ConfigBattery 7 }
+
+dcmim2ConfigBattCapacityTestEndThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Safeguard voltage at which battery capacity test will end
+ if there is a battery problem.
+
+ Values are represented in thousandths of Volts (mV)."
+
+ ::= { dcmim2ConfigBattery 8 }
+
+dcmim2ConfigBattCapacityTestCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Constant current value used during battery capacity testing.
+
+ Values are represented in thousandths of Amps (mA)."
+
+ ::= { dcmim2ConfigBattery 9 }
+
+
+-- the dcmim2ConfigLVD group
+
+dcmim2ConfigLVDTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of DC powerplant LVDs controllable
+ by this IP address."
+ ::= { dcmim2ConfigLVD 1 }
+
+dcmim2ConfigLVDTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF Dcmim2ConfigLVDEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for accessing settings of the LVDs. The number of
+ entries is contained in the dcmim2ConfigLVDTableSize OID."
+ ::= { dcmim2ConfigLVD 2 }
+
+dcmim2ConfigLVDEntry OBJECT-TYPE
+ SYNTAX Dcmim2ConfigLVDEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The LVD to configure."
+ INDEX { dcmim2ConfigLVDIndex }
+ ::= { dcmim2ConfigLVDTable 1 }
+
+Dcmim2ConfigLVDEntry ::=
+ SEQUENCE {
+ dcmim2ConfigLVDIndex INTEGER,
+ dcmim2ConfigLVDTrip INTEGER,
+ dcmim2ConfigLVDReset INTEGER,
+ dcmim2ConfigLVDState INTEGER
+ }
+
+dcmim2ConfigLVDIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the DC powerplant LVD."
+ ::= { dcmim2ConfigLVDEntry 1 }
+
+dcmim2ConfigLVDTrip OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "LVD Trip threshold. System bus voltage at which LVD will trip (open)
+ during a battery backup operation.
+
+ Values are represented in thousandths of Volts (mV)."
+ ::= { dcmim2ConfigLVDEntry 2 }
+
+dcmim2ConfigLVDReset OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "LVD Reset threshold. System bus voltage at which LVD will reset (close)
+ after AC power has been restored.
+
+ Values are represented in thousandths of Volts (mV)."
+ ::= { dcmim2ConfigLVDEntry 3 }
+
+dcmim2ConfigLVDState OBJECT-TYPE
+ SYNTAX INTEGER {
+ statusClosed (1),
+ statusOpened (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return statusClosed (1) if the LVD is closed.
+ statusOpened (2) will be returned if the LVD is opened."
+ ::= { dcmim2ConfigLVDEntry 4 }
+
+
+-- the dcmim2StatusSystem group
+
+dcmim2StatusSysRectCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "System (Total Rectifier) current in thousandths of Amps (mA)."
+ ::= { dcmim2StatusSystem 1 }
+
+dcmim2StatusSysLoadCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Load current in thousandths of Amps (mA)."
+ ::= { dcmim2StatusSystem 2 }
+
+dcmim2StatusSysBusVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "System bus voltage in thousandths of Volts (mV)."
+ ::= { dcmim2StatusSystem 3 }
+
+dcmim2StatusSysAmbientTemp OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "System temperature based on sensor on Master Controller PCB.
+
+ Values are represented in thousandths of a degree.
+ Units are displayed in the scale shown in
+ the 'dcmim2StatusSysTempUnits' OID (Celsius or Fahrenheit)."
+ ::= { dcmim2StatusSystem 4 }
+
+dcmim2StatusSysUpTime OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Length of time since the DC Powerplant controller has been powered up."
+ ::= { dcmim2StatusSystem 5 }
+
+dcmim2StatusSysTempUnits OBJECT-TYPE
+ SYNTAX INTEGER {
+ celsius(1),
+ fahrenheit(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature scale used to display the temperature
+ in the DC system, Celsius(1) or Fahrenheit(2).
+ This setting is based on the system preferences
+ configuration in the agent."
+ ::= { dcmim2StatusSystem 6 }
+
+
+-- the dcmim2StatusRectifier group
+
+dcmim2StatusRectTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of DC powerplant rectifiers viewable
+ by this IP address."
+ ::= { dcmim2StatusRectifier 1 }
+
+dcmim2StatusRectTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF Dcmim2StatusRectEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for accessing settings of the rectifiers. The number of
+ entries is contained in the dcmim2StatusRectTableSize OID."
+ ::= { dcmim2StatusRectifier 2 }
+
+dcmim2StatusRectEntry OBJECT-TYPE
+ SYNTAX Dcmim2StatusRectEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The rectifier to gather status from."
+ INDEX { dcmim2StatusRectIndex }
+ ::= { dcmim2StatusRectTable 1 }
+
+Dcmim2StatusRectEntry ::=
+ SEQUENCE {
+ dcmim2StatusRectIndex INTEGER,
+ dcmim2StatusRectDevType INTEGER,
+ dcmim2StatusRectID INTEGER,
+ dcmim2StatusRectPhyAddr INTEGER,
+ dcmim2StatusRectFail INTEGER,
+ dcmim2StatusRectCurrent INTEGER
+ }
+
+dcmim2StatusRectIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the DC powerplant rectifier."
+ ::= { dcmim2StatusRectEntry 1 }
+
+dcmim2StatusRectDevType OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID shows the rectifier device type."
+ ::= { dcmim2StatusRectEntry 2 }
+
+dcmim2StatusRectID OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID shows the rectifier ID. This enumerates the number of the rectifier within
+ a group of rectifiers."
+ ::= { dcmim2StatusRectEntry 3 }
+
+dcmim2StatusRectPhyAddr OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID shows the rectifier physical address (the address on the bus)."
+ ::= { dcmim2StatusRectEntry 4 }
+
+dcmim2StatusRectFail OBJECT-TYPE
+ SYNTAX INTEGER {
+ statusTrue (1),
+ statusFalse (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return statusTrue (1) if the rectifier has failed.
+ statusFalse (2) will be returned if the rectifier has not failed."
+ ::= { dcmim2StatusRectEntry 5 }
+
+dcmim2StatusRectCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID shows the individual rectifier current in thousandths of Amps (mA)."
+ ::= { dcmim2StatusRectEntry 6 }
+
+
+-- the dcmim2StatusBattery group
+
+dcmim2StatusBattFloatVolt OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Battery Float Voltage represented in thousandths of Volts (mV)."
+ ::= { dcmim2StatusBattery 1 }
+
+dcmim2StatusBattCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Battery Current: This OID shows the battery current in thousandths of Amps (mA)."
+ ::= { dcmim2StatusBattery 2 }
+
+dcmim2StatusBattTemp OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Battery Temperature:
+
+ Values are represented in thousandths of a degree.
+ Units are displayed in the scale shown in
+ the 'dcmim2StatusSysTempUnits' OID (Celsius or Fahrenheit)."
+ ::= { dcmim2StatusBattery 3 }
+
+dcmim2StatusBattMfgCapacity OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Battery capacity (Amp-Hour Size) as specified by the battery manufacturer.
+ Values are represented in thousandths of Amp hours (mAHr)."
+ ::= { dcmim2StatusBattery 4 }
+
+dcmim2StatusBattTestCapacity OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Battery capacity (Amp-Hour Size) as determined by the battery capacity test.
+ Values are represented in thousandths of Amp hours (mAHr)."
+ ::= { dcmim2StatusBattery 5 }
+
+dcmim2StatusBattFunctTestResult OBJECT-TYPE
+ SYNTAX INTEGER{
+ functTestNotPerformed (1),
+ functTestInProcess (2),
+ functTestInterrupted (3),
+ functTestPass (4),
+ functTestFail (5)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Results of the last battery functional test that was run."
+ ::= { dcmim2StatusBattery 6 }
+
+dcmim2StatusBattCapacityTestResult OBJECT-TYPE
+ SYNTAX INTEGER{
+ capacityTestNotPerformed (1),
+ capacityTestInProcess (2),
+ capacityTestInterrupted (3),
+ capacityTestPass (4),
+ capacityTestFail (5)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Results of the last battery capacity test that was run."
+ ::= { dcmim2StatusBattery 7 }
+
+
+-- the dcmim2StatusLVD group
+
+dcmim2StatusLVDTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of DC powerplant LVDs accessible
+ by this IP address."
+ ::= { dcmim2StatusLVD 1 }
+
+dcmim2StatusLVDTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF Dcmim2StatusLVDEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for accessing the LVDs. The number of
+ entries is contained in the dcmim2StatusLVDTableSize OID."
+ ::= { dcmim2StatusLVD 2 }
+
+dcmim2StatusLVDEntry OBJECT-TYPE
+ SYNTAX Dcmim2StatusLVDEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The LVD to access."
+ INDEX { dcmim2StatusLVDIndex }
+ ::= { dcmim2StatusLVDTable 1 }
+
+Dcmim2StatusLVDEntry ::=
+ SEQUENCE {
+ dcmim2StatusLVDIndex INTEGER,
+ dcmim2StatusLVDState INTEGER
+ }
+
+dcmim2StatusLVDIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the DC powerplant LVD."
+ ::= { dcmim2StatusLVDEntry 1 }
+
+dcmim2StatusLVDState OBJECT-TYPE
+ SYNTAX INTEGER {
+ statusClosed (1),
+ statusOpened (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this OID will return statusClosed (1) if the LVD is closed.
+ statusOpened (2) will be returned if the LVD is opened."
+ ::= { dcmim2StatusLVDEntry 2 }
+
+
+-- the dcmim2StatusAlarms group
+
+dcmim2StatusAlarmsTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of DC powerplant alarms viewable
+ by this IP address."
+ ::= { dcmim2StatusAlarms 1 }
+
+dcmim2StatusAlarmsTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF Dcmim2StatusAlarmsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for accessing system alarms. The number of
+ entries is contained in the dcmim2StatusAlarmsTableSize OID."
+ ::= { dcmim2StatusAlarms 2 }
+
+dcmim2StatusAlarmsEntry OBJECT-TYPE
+ SYNTAX Dcmim2StatusAlarmsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The alarm to display."
+ INDEX { dcmim2StatusAlarmsIndex }
+ ::= { dcmim2StatusAlarmsTable 1 }
+
+Dcmim2StatusAlarmsEntry ::=
+ SEQUENCE {
+ dcmim2StatusAlarmsIndex INTEGER,
+ dcmim2StatusAlarmsText DisplayString
+ }
+
+dcmim2StatusAlarmsIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of the system alarm."
+ ::= { dcmim2StatusAlarmsEntry 1 }
+
+dcmim2StatusAlarmsText OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The 16 character text describing the active alarm condition."
+ ::= { dcmim2StatusAlarmsEntry 2 }
+
+-- External Environmental Monitor
+
+emIdentFirmwareRevision OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The firmware revision of the Environmental Monitor."
+ ::= { emIdent 1 }
+
+emConfigProbesNumProbes OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of temperature and humidity probes available."
+ ::= { emConfig 1 }
+
+emConfigProbesTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF EmConfigProbesEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of probes supported by the Environmental Monitor
+ and their configurations."
+ ::= { emConfig 2 }
+
+emConfigProbesEntry OBJECT-TYPE
+ SYNTAX EmConfigProbesEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The Environmental Monitor probe configurations."
+ INDEX { emConfigProbeNumber }
+ ::= { emConfigProbesTable 1 }
+
+EmConfigProbesEntry ::=
+ SEQUENCE {
+ emConfigProbeNumber
+ INTEGER,
+ emConfigProbeName
+ DisplayString,
+ emConfigProbeHighTempThreshold
+ INTEGER,
+ emConfigProbeLowTempThreshold
+ INTEGER,
+ emConfigProbeTempUnits
+ INTEGER,
+ emConfigProbeHighHumidThreshold
+ INTEGER,
+ emConfigProbeLowHumidThreshold
+ INTEGER,
+ emConfigProbeHighTempEnable
+ INTEGER,
+ emConfigProbeLowTempEnable
+ INTEGER,
+ emConfigProbeHighHumidEnable
+ INTEGER,
+ emConfigProbeLowHumidEnable
+ INTEGER,
+ emConfigProbeMaxTempThreshold
+ INTEGER,
+ emConfigProbeMinTempThreshold
+ INTEGER,
+ emConfigProbeMaxHumidThreshold
+ INTEGER,
+ emConfigProbeMinHumidThreshold
+ INTEGER,
+ emConfigProbeMaxTempEnable
+ INTEGER,
+ emConfigProbeMinTempEnable
+ INTEGER,
+ emConfigProbeMaxHumidEnable
+ INTEGER,
+ emConfigProbeMinHumidEnable
+ INTEGER,
+ emConfigProbeTempHysteresis
+ INTEGER,
+ emConfigProbeHumidHysteresis
+ INTEGER,
+ emConfigProbeLocation
+ DisplayString
+ }
+
+emConfigProbeNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index into an Environmental Monitor probe entry."
+ ::= { emConfigProbesEntry 1 }
+
+emConfigProbeName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A descriptive name of the probe set by the user,
+ possibly denoting its location or purpose."
+ ::= { emConfigProbesEntry 2 }
+
+emConfigProbeHighTempThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The high temperature alarm threshold for the probe.
+ Units are displayed in the scale selected in
+ the 'emConfigProbeTempUnits' OID (Celsius or Fahrenheit)."
+ ::= { emConfigProbesEntry 3 }
+
+emConfigProbeLowTempThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The low temperature alarm threshold for the probe.
+ Units are displayed in the scale selected in
+ the 'emConfigProbeTempUnits' OID (Celsius or Fahrenheit)."
+ ::= { emConfigProbesEntry 4 }
+
+emConfigProbeTempUnits OBJECT-TYPE
+ SYNTAX INTEGER {
+ celsius(1),
+ fahrenheit(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature scale used to display the temperature
+ thresholds of the probe, Celsius(1) or Fahrenheit(2).
+ This setting is based on the system preferences
+ configuration in the agent."
+ ::= { emConfigProbesEntry 5 }
+
+emConfigProbeHighHumidThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The high humidity alarm threshold for the probe in
+ percent relative humidity."
+ ::= { emConfigProbesEntry 6 }
+
+emConfigProbeLowHumidThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The low humidity alarm threshold for the probe in
+ percent relative humidity."
+ ::= { emConfigProbesEntry 7 }
+
+emConfigProbeHighTempEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(1),
+ enabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The high temperature alarm enable/disable for the
+ probe. No alarm will be generated if this value
+ is set to disabled(1). The alarm will be
+ generated if this value is set to enabled(2) and
+ the threshold has been violated."
+ ::= { emConfigProbesEntry 8 }
+
+emConfigProbeLowTempEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(1),
+ enabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The low temperature alarm enable/disable for the
+ probe. No alarm will be generated if this value
+ is set to disabled(1). The alarm will be
+ generated if this value is set to enabled(2) and
+ the threshold has been violated."
+ ::= { emConfigProbesEntry 9 }
+
+emConfigProbeHighHumidEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(1),
+ enabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The high humidity alarm enable/disable for the
+ probe. No alarm will be generated if this value
+ is set to disabled(1). The alarm will be
+ generated if this value is set to enabled(2) and
+ the threshold has been violated."
+ ::= { emConfigProbesEntry 10 }
+
+emConfigProbeLowHumidEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(1),
+ enabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The low humidity alarm enable/disable for the
+ probe. No alarm will be generated if this value
+ is set to disabled(1). The alarm will be
+ generated if this value is set to enabled(2) and
+ the threshold has been violated."
+ ::= { emConfigProbesEntry 11 }
+
+emConfigProbeMaxTempThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum temperature alarm threshold for the probe.
+ Units are displayed in the scale selected in
+ the 'emConfigProbeTempUnits' OID (Celsius or Fahrenheit)."
+ ::= { emConfigProbesEntry 12 }
+
+emConfigProbeMinTempThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum temperature alarm threshold for the probe.
+ Units are displayed in the scale selected in
+ the 'emConfigProbeTempUnits' OID (Celsius or Fahrenheit)."
+ ::= { emConfigProbesEntry 13 }
+
+emConfigProbeMaxHumidThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The maximun humidity alarm threshold for the probe in
+ percent relative humidity."
+ ::= { emConfigProbesEntry 14 }
+
+emConfigProbeMinHumidThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum humidity alarm threshold for the probe in
+ percent relative humidity."
+ ::= { emConfigProbesEntry 15 }
+
+emConfigProbeMaxTempEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(1),
+ enabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum temperature alarm enable/disable for the
+ probe. No alarm will be generated if this value
+ is set to disabled(1). The alarm will be
+ generated if this value is set to enabled(2) and
+ the threshold has been violated."
+ ::= { emConfigProbesEntry 16 }
+
+emConfigProbeMinTempEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(1),
+ enabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum temperature alarm enable/disable for the
+ probe. No alarm will be generated if this value
+ is set to disabled(1). The alarm will be
+ generated if this value is set to enabled(2) and
+ the threshold has been violated."
+ ::= { emConfigProbesEntry 17 }
+
+emConfigProbeMaxHumidEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(1),
+ enabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum humidity alarm enable/disable for the
+ probe. No alarm will be generated if this value
+ is set to disabled(1). The alarm will be
+ generated if this value is set to enabled(2) and
+ the threshold has been violated."
+ ::= { emConfigProbesEntry 18 }
+
+emConfigProbeMinHumidEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(1),
+ enabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum humidity alarm enable/disable for the
+ probe. No alarm will be generated if this value
+ is set to disabled(1). The alarm will be
+ generated if this value is set to enabled(2) and
+ the threshold has been violated."
+ ::= { emConfigProbesEntry 19 }
+
+emConfigProbeTempHysteresis OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The number of degrees beyond the temperature thresholds
+ at which an active temperature alarm will be cleared.
+ This configuration setting applies to all temperature
+ thresholds.
+ Units are displayed in the scale selected in
+ the 'emConfigProbeTempUnits' OID (Celsius or Fahrenheit)."
+ ::= { emConfigProbesEntry 20 }
+
+emConfigProbeHumidHysteresis OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The number of percent RH points beyond the humidity
+ thresholds at which an active humidity alarm will be
+ cleared. This configuration setting applies to all
+ humidity thresholds.
+ Units are displayed in the scale selected in
+ the 'emConfigProbeTempUnits' OID (Celsius or Fahrenheit)."
+ ::= { emConfigProbesEntry 21 }
+
+emConfigProbeLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A string describing the location of the probe."
+ ::= { emConfigProbesEntry 22 }
+
+emConfigContactsNumContacts OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of contacts supported by the Environmental
+ Monitor."
+ ::= { emConfig 3 }
+
+emConfigContactsTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF EmConfigContactsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of contacts supported by the Environmental Monitor
+ and their configurations."
+ ::= { emConfig 4 }
+
+emConfigContactsEntry OBJECT-TYPE
+ SYNTAX EmConfigContactsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The Environmental Monitor contact configurations."
+ INDEX { emConfigContactNumber }
+ ::= { emConfigContactsTable 1 }
+
+EmConfigContactsEntry ::=
+ SEQUENCE {
+ emConfigContactNumber
+ INTEGER,
+ emConfigContactName
+ DisplayString,
+ emConfigContactEnable
+ INTEGER,
+ emConfigContactSeverity
+ INTEGER,
+ emConfigContactNormalState
+ INTEGER,
+ emConfigContactLocation
+ DisplayString
+ }
+
+emConfigContactNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of an Environmental Monitor contact."
+ ::= { emConfigContactsEntry 1 }
+
+emConfigContactName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A descriptive name for an Environmental Monitor
+ contact set by the user, possibly denoting its
+ location or purpose."
+ ::= { emConfigContactsEntry 2 }
+
+emConfigContactEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(1),
+ enabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "An Environmental Monitor contact alarm enable/disable.
+ No alarm will be generated if the contact is disabled(1).
+ An alarm will be generated if the contact is enabled(2)
+ and the contact has been faulted."
+ ::= { emConfigContactsEntry 3 }
+
+emConfigContactSeverity OBJECT-TYPE
+ SYNTAX INTEGER {
+ critical(1),
+ warning(2),
+ informational(3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The severity of the alarm that will be triggered when
+ the input contact is activated. The alarms can be
+ critical(1), warning(2) or informational(3)."
+ ::= { emConfigContactsEntry 4 }
+
+emConfigContactNormalState OBJECT-TYPE
+ SYNTAX INTEGER {
+ open(1),
+ closed(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The contact state that will be considered normal, i.e.
+ will not trigger an alarm. The states are open(1) or
+ closed(2)."
+ ::= { emConfigContactsEntry 5 }
+
+emConfigContactLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A descriptive label for the contact denoting its
+ location or purpose."
+ ::= { emConfigContactsEntry 6 }
+
+emStatusCommStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ noComm(1),
+ comm(2),
+ commLost(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The communication status between the agent
+ and the Environmental Monitor.
+
+ noComm(1), Communication has never been established.
+ comm(2), Communication has been established.
+ commLost(3), Communication was established, but was lost."
+ ::= { emStatus 1 }
+
+emStatusProbesNumProbes OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of available probes on the Environmental
+ Monitor."
+ ::= { emStatus 2 }
+
+emStatusProbesTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF EmStatusProbesEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of probes supported by the Environmental Monitor
+ and their status."
+ ::= { emStatus 3 }
+
+emStatusProbesEntry OBJECT-TYPE
+ SYNTAX EmStatusProbesEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the probe."
+ INDEX { emStatusProbeNumber }
+ ::= { emStatusProbesTable 1 }
+
+EmStatusProbesEntry ::=
+ SEQUENCE {
+ emStatusProbeNumber
+ INTEGER,
+ emStatusProbeName
+ DisplayString,
+ emStatusProbeStatus
+ INTEGER,
+ emStatusProbeCurrentTemp
+ INTEGER,
+ emStatusProbeTempUnits
+ INTEGER,
+ emStatusProbeCurrentHumid
+ INTEGER,
+ emStatusProbeHighTempViolation
+ INTEGER,
+ emStatusProbeLowTempViolation
+ INTEGER,
+ emStatusProbeHighHumidViolation
+ INTEGER,
+ emStatusProbeLowHumidViolation
+ INTEGER,
+ emStatusProbeMaxTempViolation
+ INTEGER,
+ emStatusProbeMinTempViolation
+ INTEGER,
+ emStatusProbeMaxHumidViolation
+ INTEGER,
+ emStatusProbeMinHumidViolation
+ INTEGER
+ }
+
+emStatusProbeNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of the probe."
+ ::= { emStatusProbesEntry 1 }
+
+emStatusProbeName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A descriptive name for the probe set by the user,
+ possibly denoting its location or purpose."
+ ::= { emStatusProbesEntry 2 }
+
+emStatusProbeStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ disconnected(1),
+ connected(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The connected status of the probe, either
+ disconnected(1) or connected(2)."
+ ::= { emStatusProbesEntry 3 }
+
+emStatusProbeCurrentTemp OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current temperature reading from the probe displayed
+ in the units shown in the 'emStatusProbeTempUnits' OID
+ (Celsius or Fahrenheit)."
+ ::= { emStatusProbesEntry 4 }
+
+emStatusProbeTempUnits OBJECT-TYPE
+ SYNTAX INTEGER {
+ celsius(1),
+ fahrenheit(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature scale used to display the temperature
+ thresholds of the probe, Celsius(1) or Fahrenheit(2).
+ This setting is based on the system preferences
+ configuration in the agent."
+ ::= { emStatusProbesEntry 5 }
+
+emStatusProbeCurrentHumid OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current humidity reading from the probe in
+ percent relative humidity."
+ ::= { emStatusProbesEntry 6 }
+
+emStatusProbeHighTempViolation OBJECT-TYPE
+ SYNTAX INTEGER {
+ noViolation(1),
+ highTempViolation(2),
+ disabled(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The high temperature violation status of the probe
+ temperature reading. This OID will show a highTempViolation(2)
+ if the current temperature reading shown in the
+ 'emStatusProbeCurrentTemp' OID is greater than or equal to
+ the high temperature threshold value, the
+ 'emConfigProbeHighTempThreshold' OID, and the value of the
+ 'emConfigProbeHighTempEnable' OID is enabled. Otherwise it will show
+ noViolation(1). If the 'emConfigProbeHighTempEnable' OID is disabled,
+ this OID will show disabled(3)."
+ ::= { emStatusProbesEntry 7 }
+
+emStatusProbeLowTempViolation OBJECT-TYPE
+ SYNTAX INTEGER {
+ noViolation(1),
+ lowTempViolation(2),
+ disabled(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The high temperature violation status of the probe
+ temperature reading. This OID will show a lowTempViolation(2)
+ if the current temperature reading shown in the
+ 'emStatusProbeCurrentTemp' OID is less than or equal to
+ the low temperature threshold value, the
+ 'emConfigProbeLowTempThreshold' OID, and the value of the
+ 'emConfigProbeLowTempEnable' OID is enabled. Otherwise it will show
+ noViolation(1). If the 'emConfigProbeLowTempEnable' OID is disabled,
+ this OID will show disabled(3)."
+ ::= { emStatusProbesEntry 8 }
+
+emStatusProbeHighHumidViolation OBJECT-TYPE
+ SYNTAX INTEGER {
+ noViolation(1),
+ highHumidViolation(2),
+ disabled(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The high humidity violation status of the probe humidity
+ reading. This OID will show a highTempViolation(2)
+ if the current humidity reading shown in the
+ 'emStatusProbeCurrentHumid' OID is greater than or equal to
+ the high humidity threshold value, the
+ 'emConfigProbeHighHumidThreshold' OID, and the value of the
+ 'emConfigProbeHighHumidEnable' OID is enabled. Otherwise it will
+ show noViolation(1). If the 'emConfigProbeHighHumidEnable' OID is
+ disabled, this OID will show disabled(3)"
+ ::= { emStatusProbesEntry 9 }
+
+emStatusProbeLowHumidViolation OBJECT-TYPE
+ SYNTAX INTEGER {
+ noViolation(1),
+ lowHumidViolation(2),
+ disabled(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The low humidity violation status of the probe humidity
+ reading. This OID will show a lowTempViolation(2)
+ if the current humidity reading shown in the
+ 'emStatusProbeCurrentHumid' OID is less than or equal to
+ the low humidity threshold value, the
+ 'emConfigProbeLowHumidThreshold' OID, and the value of the
+ 'emConfigProbeLowHumidEnable' OID is enabled. Otherwise it will
+ show noViolation(1). If the 'emConfigProbeLowHumidEnable' OID is
+ disabled, this OID will show disabled(3)."
+ ::= { emStatusProbesEntry 10 }
+
+emStatusProbeMaxTempViolation OBJECT-TYPE
+ SYNTAX INTEGER {
+ noViolation(1),
+ maxTempViolation(2),
+ disabled(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The max temperature violation status of the probe
+ temperature reading. This OID will show a maxTempViolation(2)
+ if the current temperature reading shown in the
+ 'emStatusProbeCurrentTemp' OID is greater than or equal to
+ the maximun temperature threshold value, the
+ 'emConfigProbeMaxTempThreshold' OID, and the value of the
+ 'emConfigProbeMaxTempEnable' OID is enabled. Otherwise it will show
+ noViolation(1). If the 'emConfigProbeMaxTempEnable' OID is disabled,
+ this OID will show disabled(3)."
+ ::= { emStatusProbesEntry 11 }
+
+emStatusProbeMinTempViolation OBJECT-TYPE
+ SYNTAX INTEGER {
+ noViolation(1),
+ minTempViolation(2),
+ disabled(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum temperature violation status of the probe
+ temperature reading. This OID will show a minTempViolation(2)
+ if the current temperature reading shown in the
+ 'emStatusProbeCurrentTemp' OID is less than or equal to
+ the minimum temperature threshold value, the
+ 'emConfigProbeMinTempThreshold' OID, and the value of the
+ 'emConfigProbeMinTempEnable' OID is enabled. Otherwise it will show
+ noViolation(1). If the 'emConfigProbeMinTempEnable' OID is disabled,
+ this OID will show disabled(3)."
+ ::= { emStatusProbesEntry 12 }
+
+emStatusProbeMaxHumidViolation OBJECT-TYPE
+ SYNTAX INTEGER {
+ noViolation(1),
+ maxHumidViolation(2),
+ disabled(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum humidity violation status of the probe humidity
+ reading. This OID will show a maxTempViolation(2)
+ if the current humidity reading shown in the
+ 'emStatusProbeCurrentHumid' OID is greater than or equal to
+ the maximum humidity threshold value, the
+ 'emConfigProbeMaxHumidThreshold' OID, and the value of the
+ 'emConfigProbeMaxHumidEnable' OID is enabled. Otherwise it will
+ show noViolation(1). If the 'emConfigProbeMaxHumidEnable' OID is
+ disabled, this OID will show disabled(3)"
+ ::= { emStatusProbesEntry 13 }
+
+emStatusProbeMinHumidViolation OBJECT-TYPE
+ SYNTAX INTEGER {
+ noViolation(1),
+ minHumidViolation(2),
+ disabled(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum humidity violation status of the probe humidity
+ reading. This OID will show a minTempViolation(2)
+ if the current humidity reading shown in the
+ 'emStatusProbeCurrentHumid' OID is less than or equal to
+ the minimum humidity threshold value, the
+ 'emConfigProbeMinHumidThreshold' OID, and the value of the
+ 'emConfigProbeMinHumidEnable' OID is enabled. Otherwise it will
+ show noViolation(1). If the 'emConfigProbeMinHumidEnable' OID is
+ disabled, this OID will show disabled(3)."
+ ::= { emStatusProbesEntry 14 }
+
+emStatusContactsNumContacts OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of contacts supported by the
+ Environmental Monitor."
+ ::= { emStatus 4 }
+
+emStatusContactsTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF EmStatusContactsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of contacts supported by the Environmental Monitor
+ and their status."
+ ::= { emStatus 5 }
+
+emStatusContactsEntry OBJECT-TYPE
+ SYNTAX EmStatusContactsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the contact."
+ INDEX { emStatusContactNumber }
+ ::= { emStatusContactsTable 1 }
+
+EmStatusContactsEntry ::=
+ SEQUENCE {
+ emStatusContactNumber
+ INTEGER,
+ emStatusContactName
+ DisplayString,
+ emStatusContactStatus
+ INTEGER
+ }
+
+emStatusContactNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of the Environmental Monitor contact."
+ ::= { emStatusContactsEntry 1 }
+
+emStatusContactName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A descriptive name for the Environmental Monitor contact
+ set by the user, possibly denoting its location or purpose."
+ ::= { emStatusContactsEntry 2 }
+
+emStatusContactStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ noFault(1),
+ fault(2),
+ disabled(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the Environmental Monitor contact. The status
+ will show noFault(1) if the contact is in the normal state
+ and the 'emConfigContactEnable' OID is enabled. The status will
+ show a fault(2) if the contact is faulted and the
+ 'emContactEnable' OID is enabled. If the 'emConfigContactEnable'
+ OID is disabled, the status will show disabled(3)."
+ ::= { emStatusContactsEntry 3 }
+
+-- Modular Environmental Manager (MEM)
+
+-- MEM Modules Status table
+
+memModulesStatusTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the memModulesStatusTable."
+ ::= { memModules 1 }
+
+memModulesStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF MemModulesStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting status information from the modules
+ attached to the system."
+ ::= { memModules 2 }
+
+memModulesStatusEntry OBJECT-TYPE
+ SYNTAX MemModulesStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The unit to get data from."
+ INDEX { memModulesStatusModuleNumber }
+ ::= { memModulesStatusTable 1 }
+
+MemModulesStatusEntry ::=
+ SEQUENCE {
+ memModulesStatusModuleNumber INTEGER,
+ memModulesStatusModuleName DisplayString,
+ memModulesStatusModuleLocation DisplayString,
+ memModulesStatusModelNumber DisplayString,
+ memModulesStatusSerialNumber DisplayString,
+ memModulesStatusFirmwareRev DisplayString,
+ memModulesStatusHardwareRev DisplayString
+ }
+
+memModulesStatusModuleNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The module number."
+ ::= { memModulesStatusEntry 1 }
+
+memModulesStatusModuleName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The module name."
+ ::= { memModulesStatusEntry 2 }
+
+memModulesStatusModuleLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The location of the module."
+ ::= { memModulesStatusEntry 3 }
+
+memModulesStatusModelNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The model number of the module."
+ ::= { memModulesStatusEntry 4 }
+
+memModulesStatusSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The serial number of the module."
+ ::= { memModulesStatusEntry 5 }
+
+memModulesStatusFirmwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The firmware revision of the module."
+ ::= { memModulesStatusEntry 6 }
+
+memModulesStatusHardwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The hardware revision."
+ ::= { memModulesStatusEntry 7 }
+
+-- MEM Modules Config table
+
+memModulesConfigTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the memModulesConfigTable."
+ ::= { memModules 3 }
+
+memModulesConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF MemModulesConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting status information from the modules
+ attached to the system."
+ ::= { memModules 4 }
+
+memModulesConfigEntry OBJECT-TYPE
+ SYNTAX MemModulesConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The unit to get data from."
+ INDEX { memModulesConfigModuleNumber }
+ ::= { memModulesConfigTable 1 }
+
+MemModulesConfigEntry ::=
+ SEQUENCE {
+ memModulesConfigModuleNumber INTEGER,
+ memModulesConfigModuleName DisplayString,
+ memModulesConfigModuleLocation DisplayString
+ }
+
+memModulesConfigModuleNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The module number."
+ ::= { memModulesConfigEntry 1 }
+
+memModulesConfigModuleName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The module name."
+ ::= { memModulesConfigEntry 2 }
+
+memModulesConfigModuleLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The location of the module."
+ ::= { memModulesConfigEntry 3 }
+
+
+-- MEM Sensor Status Table
+
+memSensorsStatusSysTempUnits OBJECT-TYPE
+ SYNTAX INTEGER {
+ celsius(1),
+ fahrenheit(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature scale used to display the temperature
+ in the system, Celsius(1) or Fahrenheit(2).
+ This setting is based on the system preferences
+ configuration in the agent."
+ ::= { memSensors 1 }
+
+memSensorsStatusTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the memSensorsStatusTable."
+ ::= { memSensors 2 }
+
+memSensorsStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF MemSensorsStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting sensor status information."
+ ::= { memSensors 3 }
+
+memSensorsStatusEntry OBJECT-TYPE
+ SYNTAX MemSensorsStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The unit to get data from."
+ INDEX { memSensorsStatusModuleNumber, memSensorsStatusSensorNumber }
+ ::= { memSensorsStatusTable 1 }
+
+MemSensorsStatusEntry ::=
+ SEQUENCE {
+ memSensorsStatusModuleNumber INTEGER,
+ memSensorsStatusSensorNumber INTEGER,
+ memSensorsStatusSensorName DisplayString,
+ memSensorsStatusSensorLocation DisplayString,
+ memSensorsTemperature INTEGER,
+ memSensorsHumidity INTEGER,
+ memSensorsCommStatus INTEGER,
+ memSensorsAlarmStatus INTEGER,
+ memSensorsTemperatureHighPrec INTEGER,
+ memSensorsVoltage INTEGER
+ }
+
+memSensorsStatusModuleNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of the module that the sensor is attached to."
+ ::= { memSensorsStatusEntry 1 }
+
+memSensorsStatusSensorNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of this sensor on the module."
+ ::= { memSensorsStatusEntry 2 }
+
+memSensorsStatusSensorName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The sensor name."
+ ::= { memSensorsStatusEntry 3 }
+
+memSensorsStatusSensorLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The location of the sensor."
+ ::= { memSensorsStatusEntry 4 }
+
+memSensorsTemperature OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The sensor's current temperature reading.
+ Units are displayed in the scale shown in
+ the memSensorsStatusSysTempUnits OID (Celsius or Fahrenheit)."
+ ::= { memSensorsStatusEntry 5 }
+
+memSensorsHumidity OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current humidity reading from the sensor."
+ ::= { memSensorsStatusEntry 6 }
+
+memSensorsCommStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ notInstalled(1),
+ commsOK(2),
+ commsLost(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The communications status of the sensor."
+ ::= { memSensorsStatusEntry 7 }
+
+memSensorsAlarmStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ memNormal(1),
+ memWarning(2),
+ memCritical(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The alarm status of the sensor.
+ memWarning is not applicable to voltage sensor."
+ ::= { memSensorsStatusEntry 8 }
+
+memSensorsTemperatureHighPrec OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current temperature is displayed in tenths of degrees in the scale
+ shown in the memSensorsStatusSysTempUnits OID (Celsius or Fahrenheit)."
+ ::= { memSensorsStatusEntry 9 }
+
+memSensorsVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The sensor's current voltage reading.
+
+ Values are displayed in tenths of Volts DC."
+ ::= { memSensorsStatusEntry 10 }
+
+-- MEM Sensor Config Table
+
+memSensorsConfigTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the memSensorsConfigTable."
+ ::= { memSensors 4 }
+
+memSensorsConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF MemSensorsConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting configuration information from
+ sensors attached to the system."
+ ::= { memSensors 5 }
+
+memSensorsConfigEntry OBJECT-TYPE
+ SYNTAX MemSensorsConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The unit to get data from."
+ INDEX { memSensorsConfigModuleNumber, memSensorsConfigSensorNumber }
+ ::= { memSensorsConfigTable 1 }
+
+MemSensorsConfigEntry ::=
+ SEQUENCE {
+ memSensorsConfigModuleNumber INTEGER,
+ memSensorsConfigSensorNumber INTEGER,
+ memSensorsName DisplayString,
+ memSensorsLocation DisplayString,
+ memSensorsAlarmGeneration INTEGER,
+ memSensorsTempMaxThresh INTEGER,
+ memSensorsTempHighThresh INTEGER,
+ memSensorsTempLowThresh INTEGER,
+ memSensorsTempMinThresh INTEGER,
+ memSensorsTempThreshHysteresis INTEGER,
+ memSensorsTempShortDecRateThreshValue INTEGER,
+ memSensorsTempShortDecRateThreshTime INTEGER,
+ memSensorsTempShortIncRateThreshValue INTEGER,
+ memSensorsTempShortIncRateThreshTime INTEGER,
+ memSensorsTempLongDecRateThreshValue INTEGER,
+ memSensorsTempLongDecRateThreshTime INTEGER,
+ memSensorsTempLongIncRateThreshValue INTEGER,
+ memSensorsTempLongIncRateThreshTime INTEGER,
+ memSensorsHumidityMaxThresh INTEGER,
+ memSensorsHumidityHighThresh INTEGER,
+ memSensorsHumidityLowThresh INTEGER,
+ memSensorsHumidityMinThresh INTEGER,
+ memSensorsHumidityThreshHysteresis INTEGER,
+ memSensorsVoltMaxThresh INTEGER,
+ memSensorsVoltMinThresh INTEGER
+ }
+
+memSensorsConfigModuleNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of the module that the sensor is attached to."
+ ::= { memSensorsConfigEntry 1 }
+
+memSensorsConfigSensorNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of this sensor on the module."
+ ::= { memSensorsConfigEntry 2 }
+
+memSensorsName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A descriptive name for the sensor."
+ ::= { memSensorsConfigEntry 3 }
+
+memSensorsLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The location of the sensor."
+ ::= { memSensorsConfigEntry 4 }
+
+memSensorsAlarmGeneration OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled (1),
+ enabled (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable alarm generation on this sensor."
+ ::= { memSensorsConfigEntry 5 }
+
+memSensorsTempMaxThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature at which the MEM will generate a maximum
+ temperature threshold violation alarm on this sensor.
+ The temperature scale is based on the memSensorsStatusSysTempUnits OID."
+
+ ::= { memSensorsConfigEntry 6 }
+
+memSensorsTempHighThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature at which the MEM will generate a high
+ temperature threshold violation alarm on this sensor.
+ The temperature scale is based on the memSensorsStatusSysTempUnits OID."
+ ::= { memSensorsConfigEntry 7 }
+
+memSensorsTempLowThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature at which the MEM will generate a low
+ temperature threshold violation alarm on this sensor.
+ The temperature scale is based on the memSensorsStatusSysTempUnits OID."
+ ::= { memSensorsConfigEntry 8 }
+
+memSensorsTempMinThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature at which the MEM will generate a minimum
+ temperature threshold violation alarm on this sensor.
+ The temperature scale is based on the memSensorsStatusSysTempUnits OID."
+ ::= { memSensorsConfigEntry 9 }
+
+memSensorsTempThreshHysteresis OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The change in temperature required to cause a
+ temperature alarm to change from an active to an inactive state.
+ The temperature scale is based on the memSensorsStatusSysTempUnits OID."
+
+ ::= { memSensorsConfigEntry 10 }
+
+memSensorsTempShortDecRateThreshValue OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The value of the temperature short-term decreasing rate
+ time that will cause an alarm to be generated.
+ The temperature scale is based on the memSensorsStatusSysTempUnits OID."
+ ::= { memSensorsConfigEntry 11 }
+
+memSensorsTempShortDecRateThreshTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The time over which the temperature may not decrease
+ beyond the value specified by the temperature short-term
+ decreasing rate threshold value."
+ ::= { memSensorsConfigEntry 12 }
+
+memSensorsTempShortIncRateThreshValue OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The value of the temperature short-term increasing rate
+ time that will cause an alarm to be generated.
+ The temperature scale is based on the memSensorsStatusSysTempUnits OID."
+ ::= { memSensorsConfigEntry 13 }
+
+memSensorsTempShortIncRateThreshTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The time over which the temperature may not increase
+ beyond the value specified by the temperature short-term
+ increasing rate threshold value."
+ ::= { memSensorsConfigEntry 14 }
+
+memSensorsTempLongDecRateThreshValue OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The value of the temperature long-term decreasing rate
+ time that will cause an alarm to be generated.
+ The temperature scale is based on the memSensorsStatusSysTempUnits OID."
+ ::= { memSensorsConfigEntry 15 }
+
+memSensorsTempLongDecRateThreshTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The time over which the temperature may not decrease
+ beyond the value specified by the temperature long-term
+ decreasing rate threshold value."
+ ::= { memSensorsConfigEntry 16 }
+
+memSensorsTempLongIncRateThreshValue OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The value of the temperature long-term increasing rate
+ time that will cause an alarm to be generated.
+ The temperature scale is based on the memSensorsStatusSysTempUnits OID."
+ ::= { memSensorsConfigEntry 17 }
+
+memSensorsTempLongIncRateThreshTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The time over which the temperature may not increase
+ beyond the value specified by the temperature long-term
+ increasing rate threshold value."
+ ::= { memSensorsConfigEntry 18 }
+
+memSensorsHumidityMaxThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The humidity at which the maximum humidity threshold alarm
+ will be generated."
+ ::= { memSensorsConfigEntry 19 }
+
+memSensorsHumidityHighThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The humidity at which the high humidity threshold alarm
+ will be generated."
+ ::= { memSensorsConfigEntry 20 }
+
+memSensorsHumidityLowThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The humidity at which the low humidity threshold alarm
+ will be generated."
+ ::= { memSensorsConfigEntry 21 }
+
+memSensorsHumidityMinThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The humidity at which the minimum humidity threshold alarm
+ will be generated."
+ ::= { memSensorsConfigEntry 22 }
+
+memSensorsHumidityThreshHysteresis OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The change in humidity required to cause an active humidity
+ alarm to change to the inactive state."
+ ::= { memSensorsConfigEntry 23 }
+
+memSensorsVoltMaxThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The voltage at which the MEM will generate a maximum
+ voltage threshold violation alarm on this sensor."
+ ::= { memSensorsConfigEntry 24 }
+
+memSensorsVoltMinThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The voltage at which the MEM will generate a minimum
+ voltage threshold violation alarm on this sensor."
+ ::= { memSensorsConfigEntry 25 }
+
+-- MEM Input Status Table
+
+memInputsStatusTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the memInputsStatusTable."
+ ::= { memInputs 1 }
+
+memInputsStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF MemInputsStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting input status information."
+ ::= { memInputs 2 }
+
+memInputsStatusEntry OBJECT-TYPE
+ SYNTAX MemInputsStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The unit to get data from."
+ INDEX { memInputsStatusModuleNumber, memInputsStatusInputNumber }
+ ::= { memInputsStatusTable 1 }
+
+MemInputsStatusEntry ::=
+ SEQUENCE {
+ memInputsStatusModuleNumber INTEGER,
+ memInputsStatusInputNumber INTEGER,
+ memInputsStatusInputName DisplayString,
+ memInputsStatusInputLocation DisplayString,
+ memInputsStatusCurrentState INTEGER,
+ memInputsStatusCurrentAnalogValue DisplayString,
+ memInputsStatusAlarmStatus INTEGER,
+ memInputsCommStatus INTEGER
+ }
+
+memInputsStatusModuleNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of the module that the input is attached to."
+ ::= { memInputsStatusEntry 1 }
+
+memInputsStatusInputNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of this input on the module."
+ ::= { memInputsStatusEntry 2 }
+
+memInputsStatusInputName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input name."
+ ::= { memInputsStatusEntry 3 }
+
+memInputsStatusInputLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The location of the input."
+ ::= { memInputsStatusEntry 4 }
+
+memInputsStatusCurrentState OBJECT-TYPE
+ SYNTAX INTEGER {
+ inputClosedHighMEM (1),
+ inputOpenLowMEM (2),
+ inputDisabled (3),
+ inputStateNotApplicable (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current state of the input. This OID will return
+ inputStateNotAplicable(4) for analog input types. "
+ ::= { memInputsStatusEntry 5 }
+
+memInputsStatusCurrentAnalogValue OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current analog value of the input in the units defined
+ by the user."
+ ::= { memInputsStatusEntry 6 }
+
+memInputsStatusAlarmStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ memNormal(1),
+ memWarning(2),
+ memCritical(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The alarm status of the input."
+ ::= { memInputsStatusEntry 7 }
+
+memInputsCommStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ notInstalled(1),
+ commsOK(2),
+ commsLost(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The communications status of the input. This OID is only supported by NBRK0200."
+ ::= { memInputsStatusEntry 8 }
+
+-- MEM Input Config Table
+
+memInputsConfigTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the memInputsConfigTable."
+ ::= { memInputs 3 }
+
+memInputsConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF MemInputsConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting input configuration information."
+ ::= { memInputs 4 }
+
+memInputsConfigEntry OBJECT-TYPE
+ SYNTAX MemInputsConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The unit to get data from."
+ INDEX { memInputsConfigModuleNumber, memInputsConfigInputNumber }
+ ::= { memInputsConfigTable 1 }
+
+MemInputsConfigEntry ::=
+ SEQUENCE {
+ memInputsConfigModuleNumber INTEGER,
+ memInputsConfigInputNumber INTEGER,
+ memInputName DisplayString,
+ memInputLocation DisplayString,
+ memInputType INTEGER,
+ memInputAlarmGeneration INTEGER,
+ memInputNormalState INTEGER,
+ memInputAbnormalSeverity INTEGER,
+ memInputNumberCalibrationPoints INTEGER,
+ memInputAnalogCalibrationPoint1 DisplayString,
+ memInputAnalogCalibrationPoint2 DisplayString,
+ memInputAnalogCalibrationPoint3 DisplayString,
+ memInputAnalogCalibrationPoint4 DisplayString,
+ memInputAnalogCalibrationPoint5 DisplayString,
+ memInputAnalogCalibrationPoint1Value DisplayString,
+ memInputAnalogCalibrationPoint2Value DisplayString,
+ memInputAnalogCalibrationPoint3Value DisplayString,
+ memInputAnalogCalibrationPoint4Value DisplayString,
+ memInputAnalogCalibrationPoint5Value DisplayString,
+ memInputAnalogMeasurementUnits DisplayString,
+ memInputAnalogMaxThresh DisplayString,
+ memInputAnalogHighThresh DisplayString,
+ memInputAnalogLowThresh DisplayString,
+ memInputAnalogMinThresh DisplayString,
+ memInputAnalogThreshHysteresis DisplayString
+ }
+
+memInputsConfigModuleNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of the module that the input is attached to."
+ ::= { memInputsConfigEntry 1 }
+
+memInputsConfigInputNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of this input on the module."
+ ::= { memInputsConfigEntry 2 }
+
+memInputName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the input."
+ ::= { memInputsConfigEntry 3 }
+
+memInputLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The location of the input."
+ ::= { memInputsConfigEntry 4 }
+
+memInputType OBJECT-TYPE
+ SYNTAX INTEGER {
+ noConnection (1),
+ dryContact (2),
+ digital (3),
+ analogmAmps (4),
+ analogVolts (5)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The type of input this contact will take."
+ ::= { memInputsConfigEntry 5 }
+
+memInputAlarmGeneration OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled (1),
+ enabled (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable alarm generation on this input."
+ ::= { memInputsConfigEntry 6 }
+
+memInputNormalState OBJECT-TYPE
+ SYNTAX INTEGER {
+ inputClosedHighMEM (1),
+ inputOpenLowMEM (2),
+ inputDisabled (3),
+ inputStateNotApplicable (4)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Defines the normal (no alarm) state of the input."
+ ::= { memInputsConfigEntry 7 }
+
+memInputAbnormalSeverity OBJECT-TYPE
+ SYNTAX INTEGER {
+ inputSeverityinformational (1),
+ inputSeveritywarning (2),
+ inputSeveritysevere (3),
+ inputSeverityNotApplicable (4)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Defines the severity of the event that is associated
+ with the abnormal state of the input. This OID will return
+ inputSeverityNotApplicable(4) for analog input types. "
+ ::= { memInputsConfigEntry 8 }
+
+memInputNumberCalibrationPoints OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The number of calibration points that are required for
+ this input."
+ ::= { memInputsConfigEntry 9 }
+
+memInputAnalogCalibrationPoint1 OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The electrical value that the input sensor will measure at the
+ first calibration point.
+ This OID is relevant only for inputs configured as analog type (ma or V)."
+ ::= { memInputsConfigEntry 10 }
+
+memInputAnalogCalibrationPoint2 OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The electrical value that the input sensor will measure at the
+ second calibration point.
+ This OID is relevant only for inputs configured as analog type (ma or V)."
+ ::= { memInputsConfigEntry 11 }
+
+memInputAnalogCalibrationPoint3 OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The electrical value that the input sensor will measure at the
+ third calibration point.
+ This OID is relevant only for inputs configured as analog type (ma or V)."
+ ::= { memInputsConfigEntry 12 }
+
+memInputAnalogCalibrationPoint4 OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The electrical value that the input sensor will measure at the
+ fourth calibration point.
+ This OID is relevant only for inputs configured as analog type (ma or V)."
+ ::= { memInputsConfigEntry 13 }
+
+memInputAnalogCalibrationPoint5 OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The electrical value that the input sensor will measure at the
+ fifth calibration point.
+ This OID is relevant only for inputs configured as analog type (ma or V)."
+ ::= { memInputsConfigEntry 14 }
+
+memInputAnalogCalibrationPoint1Value OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The value of the input, in units of measure defined by
+ the user, that corresponds to the current setting at the
+ first calibration point."
+ ::= { memInputsConfigEntry 15 }
+
+memInputAnalogCalibrationPoint2Value OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The value of the input, in units of measure defined by
+ the user, that corresponds to the current setting at the
+ second calibration point."
+ ::= { memInputsConfigEntry 16 }
+
+memInputAnalogCalibrationPoint3Value OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The value of the input, in units of measure defined by
+ the user, that corresponds to the current setting at the
+ third calibration point."
+ ::= { memInputsConfigEntry 17 }
+
+memInputAnalogCalibrationPoint4Value OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The value of the input, in units of measure defined by
+ the user, that corresponds to the current setting at the
+ fourth calibration point."
+ ::= { memInputsConfigEntry 18 }
+
+memInputAnalogCalibrationPoint5Value OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The value of the input, in units of measure defined by
+ the user, that corresponds to the current setting at the
+ fifth calibration point."
+ ::= { memInputsConfigEntry 19 }
+
+memInputAnalogMeasurementUnits OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The units of measure to be used for this input."
+ ::= { memInputsConfigEntry 20 }
+
+memInputAnalogMaxThresh OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The input value at which a maximum threshold violation
+ alarm will be generated on this input."
+ ::= { memInputsConfigEntry 21 }
+
+memInputAnalogHighThresh OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The input value at which a high threshold violation
+ alarm will be generated on this input."
+ ::= { memInputsConfigEntry 22 }
+
+memInputAnalogLowThresh OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The input value at which a low threshold violation
+ alarm will be generated on this input."
+ ::= { memInputsConfigEntry 23 }
+
+memInputAnalogMinThresh OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The input value at which a minimum threshold violation
+ alarm will be generated on this input."
+ ::= { memInputsConfigEntry 24 }
+
+
+memInputAnalogThreshHysteresis OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The change in value required to cause an alarm on this input
+ to change from active to inactive."
+ ::= { memInputsConfigEntry 25 }
+
+
+-- MEM Output Status Table
+
+memOutputStatusTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the memOutputStatusTable."
+ ::= { memOutputs 1 }
+
+memOutputStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF MemOutputStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting output status information."
+ ::= { memOutputs 2 }
+
+memOutputStatusEntry OBJECT-TYPE
+ SYNTAX MemOutputStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The unit to get data from."
+ INDEX { memOutputStatusModuleNumber, memOutputStatusOutputNumber }
+ ::= { memOutputStatusTable 1 }
+
+MemOutputStatusEntry ::=
+ SEQUENCE {
+ memOutputStatusModuleNumber INTEGER,
+ memOutputStatusOutputNumber INTEGER,
+ memOutputStatusOutputName DisplayString,
+ memOutputStatusOutputLocation DisplayString,
+ memOutputStatusCurrentState INTEGER,
+ memOutputStatusAlarmState INTEGER
+ }
+
+memOutputStatusModuleNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of the module that the output is attached to."
+ ::= { memOutputStatusEntry 1 }
+
+memOutputStatusOutputNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of this output on the module."
+ ::= { memOutputStatusEntry 2 }
+
+memOutputStatusOutputName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output name."
+ ::= { memOutputStatusEntry 3 }
+
+memOutputStatusOutputLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The location of the output."
+ ::= { memOutputStatusEntry 4 }
+
+memOutputStatusCurrentState OBJECT-TYPE
+ SYNTAX INTEGER {
+ memOutputClosed (1),
+ memOutputOpen (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The state of the output."
+ ::= { memOutputStatusEntry 5 }
+
+memOutputStatusAlarmState OBJECT-TYPE
+ SYNTAX INTEGER {
+ memOutputNormal (1),
+ memOutputAbnormal (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The alarm state of the output."
+ ::= { memOutputStatusEntry 6 }
+
+-- MEM Output Config Table
+
+memOutputConfigTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the memOutputConfigTable."
+ ::= { memOutputs 3 }
+
+memOutputConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF MemOutputConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting output configuration information."
+ ::= { memOutputs 4 }
+
+memOutputConfigEntry OBJECT-TYPE
+ SYNTAX MemOutputConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The unit to get data from."
+ INDEX { memOutputConfigModuleNumber, memOutputConfigOutputNumber }
+ ::= { memOutputConfigTable 1 }
+
+MemOutputConfigEntry ::=
+ SEQUENCE {
+ memOutputConfigModuleNumber INTEGER,
+ memOutputConfigOutputNumber INTEGER,
+ memOutputName DisplayString,
+ memOutputLocation DisplayString,
+ memOutputNormalState INTEGER,
+ memOutputAction INTEGER
+ }
+
+memOutputConfigModuleNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of the module that the output is attached to."
+ ::= { memOutputConfigEntry 1 }
+
+memOutputConfigOutputNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of this output on the module."
+ ::= { memOutputConfigEntry 2 }
+
+memOutputName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the output."
+ ::= { memOutputConfigEntry 3 }
+
+memOutputLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The location of the output."
+ ::= { memOutputConfigEntry 4 }
+
+memOutputNormalState OBJECT-TYPE
+ SYNTAX INTEGER {
+ memOutputClosed (1),
+ memOutputOpen (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The state of the output that will not generate an alarm."
+ ::= { memOutputConfigEntry 5 }
+
+memOutputAction OBJECT-TYPE
+ SYNTAX INTEGER {
+ memActionClose (1),
+ memActionOpen (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Manual control actions for the output. SNMP get command will return the state
+ of the output, SNMP set of this OID controls the output."
+ ::= { memOutputConfigEntry 6 }
+
+
+-- MEM Outlet Status Table
+
+memOutletStatusTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the memOutletStatusTable."
+ ::= { memOutlets 1 }
+
+memOutletStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF MemOutletStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting outlet status information."
+ ::= { memOutlets 2 }
+
+memOutletStatusEntry OBJECT-TYPE
+ SYNTAX MemOutletStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The unit to get data from."
+ INDEX { memOutletStatusModuleNumber, memOutletStatusOutletNumber }
+ ::= { memOutletStatusTable 1 }
+
+MemOutletStatusEntry ::=
+ SEQUENCE {
+ memOutletStatusModuleNumber INTEGER,
+ memOutletStatusOutletNumber INTEGER,
+ memOutletStatusOutletName DisplayString,
+ memOutletStatusOutletLocation DisplayString,
+ memOutletStatusCurrentState INTEGER,
+ memOutletStatusAlarmState INTEGER
+ }
+
+memOutletStatusModuleNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of the module that the outlet is attached to."
+ ::= { memOutletStatusEntry 1 }
+
+memOutletStatusOutletNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of this outlet on the module."
+ ::= { memOutletStatusEntry 2 }
+
+memOutletStatusOutletName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The outlet name."
+ ::= { memOutletStatusEntry 3 }
+
+memOutletStatusOutletLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The location of the outlet."
+ ::= { memOutletStatusEntry 4 }
+
+memOutletStatusCurrentState OBJECT-TYPE
+ SYNTAX INTEGER {
+ off (1),
+ on (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The state of the outlet."
+ ::= { memOutletStatusEntry 5 }
+
+memOutletStatusAlarmState OBJECT-TYPE
+ SYNTAX INTEGER {
+ memOutletNormal (1),
+ memOutletAbnormal (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The alarm state of the outlet."
+ ::= { memOutletStatusEntry 6 }
+
+-- MEM Outlet Config Table
+
+memOutletConfigTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the memOutletConfigTable."
+ ::= { memOutlets 3 }
+
+memOutletConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF MemOutletConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting outlet configuration information."
+ ::= { memOutlets 4 }
+
+memOutletConfigEntry OBJECT-TYPE
+ SYNTAX MemOutletConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The unit to get data from."
+ INDEX { memOutletConfigModuleNumber, memOutletConfigOutletNumber }
+ ::= { memOutletConfigTable 1 }
+
+MemOutletConfigEntry ::=
+ SEQUENCE {
+ memOutletConfigModuleNumber INTEGER,
+ memOutletConfigOutletNumber INTEGER,
+ memOutletName DisplayString,
+ memOutletLocation DisplayString,
+ memOutletNormalState INTEGER,
+ memOutletAction INTEGER
+ }
+
+memOutletConfigModuleNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of the module that the Outlet is attached to."
+ ::= { memOutletConfigEntry 1 }
+
+memOutletConfigOutletNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of this Outlet on the module."
+ ::= { memOutletConfigEntry 2 }
+
+memOutletName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the Outlet."
+ ::= { memOutletConfigEntry 3 }
+
+memOutletLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The location of the Outlet."
+ ::= { memOutletConfigEntry 4 }
+
+memOutletNormalState OBJECT-TYPE
+ SYNTAX INTEGER {
+ off (1),
+ on (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The state of the Outlet that will not generate an alarm."
+ ::= { memOutletConfigEntry 5 }
+
+memOutletAction OBJECT-TYPE
+ SYNTAX INTEGER {
+ turnOff (1),
+ turnOn (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Manual control actions for the Outlet. Get displays state
+ of outlet, set controls outlet."
+ ::= { memOutletConfigEntry 6 }
+
+
+-- MEM Beacon Status Table
+
+memBeaconStatusTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the memBeaconStatusTable."
+ ::= { memBeacons 1 }
+
+memBeaconStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF MemBeaconStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting beacon status information."
+ ::= { memBeacons 2 }
+
+memBeaconStatusEntry OBJECT-TYPE
+ SYNTAX MemBeaconStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The unit to get data from."
+ INDEX { memBeaconStatusModuleNumber, memBeaconStatusBeaconNumber }
+ ::= { memBeaconStatusTable 1 }
+
+MemBeaconStatusEntry ::=
+ SEQUENCE {
+ memBeaconStatusModuleNumber INTEGER,
+ memBeaconStatusBeaconNumber INTEGER,
+ memBeaconStatusBeaconName DisplayString,
+ memBeaconStatusBeaconLocation DisplayString,
+ memBeaconStatusCurrentState INTEGER,
+ memBeaconStatusAlarmState INTEGER
+ }
+
+memBeaconStatusModuleNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of the module that the beacon is attached to."
+ ::= { memBeaconStatusEntry 1 }
+
+memBeaconStatusBeaconNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of this beacon on the module."
+ ::= { memBeaconStatusEntry 2 }
+
+memBeaconStatusBeaconName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The beacon name."
+ ::= { memBeaconStatusEntry 3 }
+
+memBeaconStatusBeaconLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The location of the beacon."
+ ::= { memBeaconStatusEntry 4 }
+
+memBeaconStatusCurrentState OBJECT-TYPE
+ SYNTAX INTEGER {
+ off (1),
+ on (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The state of the beacon."
+ ::= { memBeaconStatusEntry 5 }
+
+memBeaconStatusAlarmState OBJECT-TYPE
+ SYNTAX INTEGER {
+ memBeaconNormal (1),
+ memBeaconAbnormal (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The alarm state of the beacon."
+ ::= { memBeaconStatusEntry 6 }
+
+-- MEM Beacon Config Table
+
+memBeaconConfigTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the memBeaconConfigTable."
+ ::= { memBeacons 3 }
+
+memBeaconConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF MemBeaconConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting beacon configuration information."
+ ::= { memBeacons 4 }
+
+memBeaconConfigEntry OBJECT-TYPE
+ SYNTAX MemBeaconConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The unit to get data from."
+ INDEX { memBeaconConfigModuleNumber, memBeaconConfigBeaconNumber }
+ ::= { memBeaconConfigTable 1 }
+
+MemBeaconConfigEntry ::=
+ SEQUENCE {
+ memBeaconConfigModuleNumber INTEGER,
+ memBeaconConfigBeaconNumber INTEGER,
+ memBeaconConfigName DisplayString,
+ memBeaconConfigLocation DisplayString,
+ memBeaconAction INTEGER
+ }
+
+memBeaconConfigModuleNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of the module that the beacon is attached to."
+ ::= { memBeaconConfigEntry 1 }
+
+memBeaconConfigBeaconNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of this beacon on the module."
+ ::= { memBeaconConfigEntry 2 }
+
+memBeaconConfigName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the beacon."
+ ::= { memBeaconConfigEntry 3 }
+
+memBeaconConfigLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The location of the beacon."
+ ::= { memBeaconConfigEntry 4 }
+
+memBeaconAction OBJECT-TYPE
+ SYNTAX INTEGER {
+ turnOff (1),
+ turnOn (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Control action (on/off) for the beacon. Setting this OID will turn the
+ beacon on/off. Getting this OID will respond with the current state."
+ ::= { memBeaconConfigEntry 5 }
+
+-- MEM INPUT STATE SENSOR TABLE
+
+memSmokeSensorStatusTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the memSmokeSensorStatusTable."
+ ::= { memInputStateSensors 1 }
+
+memSmokeSensorStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF MemSmokeSensorStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for the access of individual sensors."
+ ::= { memInputStateSensors 2 }
+
+memSmokeSensorStatusEntry OBJECT-TYPE
+ SYNTAX MemSmokeSensorStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The sensor to access."
+ INDEX { memSmokeSensorStatusModuleIndex }
+ ::= { memSmokeSensorStatusTable 1 }
+
+MemSmokeSensorStatusEntry ::=
+ SEQUENCE {
+ memSmokeSensorStatusModuleIndex INTEGER,
+ memSmokeSensorStatusSensorIndex INTEGER,
+ memSmokeSensorStatusSensorName DisplayString,
+ memSmokeSensorStatusSensorLocation DisplayString,
+ memSmokeSensorStatusSensorState INTEGER,
+ memSmokeSensorStatusSensorSeverity INTEGER,
+ memSmokeStatusAlarmStatus INTEGER,
+ memSmokeSensorCommStatus INTEGER
+ }
+
+memSmokeSensorStatusModuleIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the module entry."
+ ::= { memSmokeSensorStatusEntry 1 }
+
+memSmokeSensorStatusSensorIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the sensor entry."
+ ::= { memSmokeSensorStatusEntry 2 }
+
+memSmokeSensorStatusSensorName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user defined name of the smoke sensor."
+ ::= { memSmokeSensorStatusEntry 3 }
+
+memSmokeSensorStatusSensorLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user defined location of the smoke sensor."
+ ::= { memSmokeSensorStatusEntry 4 }
+
+memSmokeSensorStatusSensorState OBJECT-TYPE
+ SYNTAX INTEGER {
+ smokeDetected (1),
+ noSmoke (2),
+ unknown (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The state of the smoke sensor.
+ smokeDetected (1) indicates there is smoke.
+ noSmoke (2) indicates there is no smoke.
+ unknown (3) indicates the state is unknown."
+ ::= { memSmokeSensorStatusEntry 5}
+
+memSmokeSensorStatusSensorSeverity OBJECT-TYPE
+ SYNTAX INTEGER {
+ critical(1),
+ warning(2),
+ informational(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The severity of the alarm that will be triggered when
+ the smoke sensor is activated. The alarms can be
+ critical(1), warning(2) or informational(3)."
+ ::= { memSmokeSensorStatusEntry 6 }
+
+memSmokeStatusAlarmStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ memNormal(1),
+ memWarning(2),
+ memCritical(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The alarm status of the smoke sensor."
+ ::= { memSmokeSensorStatusEntry 7 }
+
+memSmokeSensorCommStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ commOK(1),
+ commLost(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The communication status of the smoke sensor."
+ ::= { memSmokeSensorStatusEntry 8 }
+
+memVibrationSensorStatusTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the memVibrationSensorStatusTable."
+ ::= { memInputStateSensors 3}
+
+memVibrationSensorStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF MemVibrationSensorStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for the access of individual sensors."
+ ::= { memInputStateSensors 4 }
+
+memVibrationSensorStatusEntry OBJECT-TYPE
+ SYNTAX MemVibrationSensorStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The sensors to access."
+ INDEX { memVibrationSensorStatusModuleIndex }
+ ::= { memVibrationSensorStatusTable 1 }
+
+MemVibrationSensorStatusEntry ::=
+ SEQUENCE {
+ memVibrationSensorStatusModuleIndex INTEGER,
+ memVibrationSensorStatusSensorIndex INTEGER,
+ memVibrationSensorStatusSensorName DisplayString,
+ memVibrationSensorStatusSensorLocation DisplayString,
+ memVibrationSensorStatusSensorState INTEGER,
+ memVibrationSensorStatusSensorSeverity INTEGER,
+ memVibrationStatusAlarmStatus INTEGER,
+ memVibrationSensorCommStatus INTEGER
+ }
+
+memVibrationSensorStatusModuleIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the sensor module entry."
+ ::= { memVibrationSensorStatusEntry 1 }
+
+memVibrationSensorStatusSensorIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the sensor entry."
+ ::= { memVibrationSensorStatusEntry 2 }
+
+memVibrationSensorStatusSensorName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user defined name of the vibration sensor."
+ ::= { memVibrationSensorStatusEntry 3 }
+
+memVibrationSensorStatusSensorLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user defined location of the vibration sensor."
+ ::= { memVibrationSensorStatusEntry 4 }
+
+memVibrationSensorStatusSensorState OBJECT-TYPE
+ SYNTAX INTEGER {
+ vibrationDetected (1),
+ noVibration (2),
+ unknown (3)
+ }
+
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The state of the vibration sensor.
+ vibrationDetected (1) indicates there is vibration.
+ noVibration (2) indicates there is no vibration.
+ unknown (3) indicates the state is unknown."
+ ::= { memVibrationSensorStatusEntry 5 }
+
+memVibrationSensorStatusSensorSeverity OBJECT-TYPE
+ SYNTAX INTEGER {
+ critical(1),
+ warning(2),
+ informational(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The severity of the alarm that will be triggered when
+ the vibration sensor is activated. The alarms can be
+ critical(1), warning(2) or informational(3)."
+ ::= { memVibrationSensorStatusEntry 6 }
+
+memVibrationStatusAlarmStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ memNormal(1),
+ memWarning(2),
+ memCritical(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The alarm status of the vibration sensor."
+ ::= { memVibrationSensorStatusEntry 7 }
+
+memVibrationSensorCommStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ commOK(1),
+ commLost(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The communication status of the vibration sensor."
+ ::= { memVibrationSensorStatusEntry 8 }
+
+
+memFluidSensorStatusTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the memFluidSensorStatusTable."
+ ::= { memInputStateSensors 5}
+
+memFluidSensorStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF MemFluidSensorStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for access of individual sensors."
+ ::= { memInputStateSensors 6 }
+
+memFluidSensorStatusEntry OBJECT-TYPE
+ SYNTAX MemFluidSensorStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The sensor to access."
+ INDEX { memFluidSensorStatusModuleIndex }
+ ::= { memFluidSensorStatusTable 1 }
+
+MemFluidSensorStatusEntry ::=
+ SEQUENCE {
+ memFluidSensorStatusModuleIndex INTEGER,
+ memFluidSensorStatusSensorIndex INTEGER,
+ memFluidSensorStatusSensorName DisplayString,
+ memFluidSensorStatusSensorLocation DisplayString,
+ memFluidSensorStatusSensorState INTEGER,
+ memFluidSensorStatusSensorSeverity INTEGER,
+ memFluidStatusAlarmStatus INTEGER,
+ memFluidSensorCommStatus INTEGER
+ }
+
+memFluidSensorStatusModuleIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the sensor module entry."
+ ::= { memFluidSensorStatusEntry 1 }
+
+memFluidSensorStatusSensorIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the sensor entry."
+ ::= { memFluidSensorStatusEntry 2 }
+
+memFluidSensorStatusSensorName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user defined name of the fluid sensor."
+ ::= { memFluidSensorStatusEntry 3 }
+
+memFluidSensorStatusSensorLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user defined location of the fluid sensor."
+ ::= { memFluidSensorStatusEntry 4 }
+
+memFluidSensorStatusSensorState OBJECT-TYPE
+ SYNTAX INTEGER {
+ fluidDetected (1),
+ noFluid (2),
+ unknown (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The state of the fluid sensor.
+ fluidDetected (1) indicates there is fluid leak.
+ noFluid (2) indicates there is no fluid leak.
+ unknown (3) indicates the state is unknown."
+ ::= { memFluidSensorStatusEntry 5 }
+
+memFluidSensorStatusSensorSeverity OBJECT-TYPE
+ SYNTAX INTEGER {
+ critical(1),
+ warning(2),
+ informational(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The severity of the alarm that will be triggered when
+ the fluid sensor is activated. The alarms can be
+ critical(1), warning(2) or informational(3)."
+ ::= { memFluidSensorStatusEntry 6 }
+
+memFluidStatusAlarmStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ memNormal(1),
+ memWarning(2),
+ memCritical(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The alarm status of the fluid sensor."
+ ::= { memFluidSensorStatusEntry 7 }
+
+memFluidSensorCommStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ commOK(1),
+ commLost(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The communication status of the fluid sensor."
+ ::= { memFluidSensorStatusEntry 8 }
+
+memDoorSensorStatusTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the memDoorSensorStatusTable."
+ ::= { memInputStateSensors 7}
+
+memDoorSensorStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF MemDoorSensorStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for the access of individual sensors."
+ ::= { memInputStateSensors 8}
+
+memDoorSensorStatusEntry OBJECT-TYPE
+ SYNTAX MemDoorSensorStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The sensor to access."
+ INDEX { memDoorSensorStatusModuleIndex }
+ ::= { memDoorSensorStatusTable 1 }
+
+MemDoorSensorStatusEntry ::=
+ SEQUENCE {
+ memDoorSensorStatusModuleIndex INTEGER,
+ memDoorSensorStatusSensorIndex INTEGER,
+ memDoorSensorStatusSensorName DisplayString,
+ memDoorSensorStatusSensorLocation DisplayString,
+ memDoorSensorStatusSensorState INTEGER,
+ memDoorSensorStatusSensorSeverity INTEGER,
+ memDoorStatusAlarmStatus INTEGER,
+ memDoorSensorCommStatus INTEGER
+ }
+
+memDoorSensorStatusModuleIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the sensor module entry."
+ ::= { memDoorSensorStatusEntry 1 }
+
+memDoorSensorStatusSensorIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the sensor entry."
+ ::= { memDoorSensorStatusEntry 2 }
+
+memDoorSensorStatusSensorName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user defined name of the door sensor."
+ ::= { memDoorSensorStatusEntry 3 }
+
+memDoorSensorStatusSensorLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user defined location of the door sensor."
+ ::= { memDoorSensorStatusEntry 4 }
+
+memDoorSensorStatusSensorState OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2),
+ unknown (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The state of the door sensor.
+ open (1) indicates door open.
+ closed (2) indicates door closed.
+ unknown (3) indicates the state is unknown."
+ ::= { memDoorSensorStatusEntry 5 }
+
+memDoorSensorStatusSensorSeverity OBJECT-TYPE
+ SYNTAX INTEGER {
+ critical(1),
+ warning(2),
+ informational(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The severity of the alarm that will be triggered when
+ the door sensor is activated. The alarms can be
+ critical(1), warning(2) or informational(3)."
+ ::= { memDoorSensorStatusEntry 6 }
+
+memDoorStatusAlarmStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ memNormal(1),
+ memWarning(2),
+ memCritical(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The alarm status of the door sensor."
+ ::= { memDoorSensorStatusEntry 7 }
+
+memDoorSensorCommStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ commOK(1),
+ commLost(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The communication status of the door sensor."
+ ::= { memDoorSensorStatusEntry 8 }
+
+-- MEM Input State sensor config
+memSmokeSensorConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF MemSmokeSensorConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for the configuration of individual sensors."
+ ::= { memInputStateSensors 9 }
+
+memSmokeSensorConfigEntry OBJECT-TYPE
+ SYNTAX MemSmokeSensorConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The sensors to configure."
+ INDEX { memSmokeSensorConfigSensorModuleIndex }
+ ::= { memSmokeSensorConfigTable 1 }
+
+MemSmokeSensorConfigEntry ::=
+ SEQUENCE {
+ memSmokeSensorConfigSensorModuleIndex INTEGER,
+ memSmokeSensorConfigSensorIndex INTEGER,
+ memSmokeSensorConfigSensorName DisplayString,
+ memSmokeSensorConfigSensorLocation DisplayString,
+ memSmokeSensorConfigSensorSeverity INTEGER,
+ memSmokeSensorConfigAlarmGeneration INTEGER
+ }
+
+memSmokeSensorConfigSensorModuleIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the sensor module entry."
+ ::= { memSmokeSensorConfigEntry 1 }
+
+memSmokeSensorConfigSensorIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the sensor entry."
+ ::= { memSmokeSensorConfigEntry 2 }
+
+memSmokeSensorConfigSensorName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The user defined name of the smoke sensor."
+ ::= { memSmokeSensorConfigEntry 3 }
+
+memSmokeSensorConfigSensorLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The user defined location of the smoke sensor."
+ ::= { memSmokeSensorConfigEntry 4 }
+
+memSmokeSensorConfigSensorSeverity OBJECT-TYPE
+ SYNTAX INTEGER {
+ critical(1),
+ warning(2),
+ informational(3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The severity of the alarm that will be triggered when
+ the smoke sensor is activated. The alarms can be
+ critical(1), warning(2) or informational(3)."
+ ::= { memSmokeSensorConfigEntry 5 }
+
+memSmokeSensorConfigAlarmGeneration OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled (1),
+ enabled (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable alarm generation on this input."
+ ::= { memSmokeSensorConfigEntry 6 }
+
+memVibrationSensorConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF MemVibrationSensorConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for the configuration of individual sensors."
+ ::= { memInputStateSensors 10 }
+
+memVibrationSensorConfigEntry OBJECT-TYPE
+ SYNTAX MemVibrationSensorConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The sensor to configure."
+ INDEX { memVibrationSensorModuleConfigIndex }
+ ::= { memVibrationSensorConfigTable 1 }
+
+MemVibrationSensorConfigEntry ::=
+ SEQUENCE {
+ memVibrationSensorModuleConfigIndex INTEGER,
+ memVibrationSensorConfigSensorIndex INTEGER,
+ memVibrationSensorConfigSensorName DisplayString,
+ memVibrationSensorConfigSensorLocation DisplayString,
+ memVibrationSensorConfigSensorSeverity INTEGER,
+ memVibrationSensorConfigAlarmGeneration INTEGER
+ }
+
+memVibrationSensorModuleConfigIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the sensor module entry."
+ ::= { memVibrationSensorConfigEntry 1 }
+
+memVibrationSensorConfigSensorIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the sensor entry."
+ ::= { memVibrationSensorConfigEntry 2 }
+
+memVibrationSensorConfigSensorName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The user defined name of the vibration sensor."
+ ::= { memVibrationSensorConfigEntry 3 }
+
+memVibrationSensorConfigSensorLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The user defined location of the vibration sensor."
+ ::= { memVibrationSensorConfigEntry 4 }
+
+memVibrationSensorConfigSensorSeverity OBJECT-TYPE
+ SYNTAX INTEGER {
+ critical(1),
+ warning(2),
+ informational(3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The severity of the alarm that will be triggered when
+ the vibration sensor is activated. The alarms can be
+ critical(1), warning(2) or informational(3)."
+ ::= { memVibrationSensorConfigEntry 5 }
+
+memVibrationSensorConfigAlarmGeneration OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled (1),
+ enabled (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable alarm generation on this input."
+ ::= { memVibrationSensorConfigEntry 6 }
+
+memFluidSensorConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF MemFluidSensorConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for the configuration of individual sensors."
+ ::= { memInputStateSensors 11 }
+
+memFluidSensorConfigEntry OBJECT-TYPE
+ SYNTAX MemFluidSensorConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The sensor to configure."
+ INDEX { memFluidSensorModuleConfigIndex }
+ ::= { memFluidSensorConfigTable 1 }
+
+MemFluidSensorConfigEntry ::=
+ SEQUENCE {
+ memFluidSensorModuleConfigIndex INTEGER,
+ memFluidSensorConfigSensorIndex INTEGER,
+ memFluidSensorConfigSensorName DisplayString,
+ memFluidSensorConfigSensorLocation DisplayString,
+ memFluidSensorConfigSensorSeverity INTEGER,
+ memFluidSensorConfigAlarmGeneration INTEGER
+ }
+
+memFluidSensorModuleConfigIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the sensor module entry."
+ ::= { memFluidSensorConfigEntry 1 }
+
+memFluidSensorConfigSensorIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the sensor entry."
+ ::= { memFluidSensorConfigEntry 2 }
+
+memFluidSensorConfigSensorName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The user defined name of the fluid sensor."
+ ::= { memFluidSensorConfigEntry 3 }
+
+memFluidSensorConfigSensorLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The user defined location of the fluid sensor."
+ ::= { memFluidSensorConfigEntry 4 }
+
+memFluidSensorConfigSensorSeverity OBJECT-TYPE
+ SYNTAX INTEGER {
+ critical(1),
+ warning(2),
+ informational(3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The severity of the alarm that will be triggered when
+ the fluid sensor is activated. The alarms can be
+ critical(1), warning(2) or informational(3)."
+ ::= { memFluidSensorConfigEntry 5 }
+
+memFluidSensorConfigAlarmGeneration OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled (1),
+ enabled (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable alarm generation on this input."
+ ::= { memFluidSensorConfigEntry 6 }
+
+memDoorSensorConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF MemDoorSensorConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for the configuration of individual sensors."
+ ::= { memInputStateSensors 12 }
+
+memDoorSensorConfigEntry OBJECT-TYPE
+ SYNTAX MemDoorSensorConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The sensors to configure."
+ INDEX { memDoorSensorModuleConfigIndex }
+ ::= { memDoorSensorConfigTable 1 }
+
+MemDoorSensorConfigEntry ::=
+ SEQUENCE {
+ memDoorSensorModuleConfigIndex INTEGER,
+ memDoorSensorConfigSensorIndex INTEGER,
+ memDoorSensorConfigSensorName DisplayString,
+ memDoorSensorConfigSensorLocation DisplayString,
+ memDoorSensorConfigSensorSeverity INTEGER,
+ memDoorSensorConfigAlarmGeneration INTEGER
+ }
+
+memDoorSensorModuleConfigIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the sensor module entry."
+ ::= { memDoorSensorConfigEntry 1 }
+
+memDoorSensorConfigSensorIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the sensor entry."
+ ::= { memDoorSensorConfigEntry 2 }
+
+memDoorSensorConfigSensorName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The user defined name of the door sensor."
+ ::= { memDoorSensorConfigEntry 3 }
+
+memDoorSensorConfigSensorLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The user defined location of the door sensor."
+ ::= { memDoorSensorConfigEntry 4 }
+
+memDoorSensorConfigSensorSeverity OBJECT-TYPE
+ SYNTAX INTEGER {
+ critical(1),
+ warning(2),
+ informational(3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The severity of the alarm that will be triggered when
+ the door sensor is activated. The alarms can be
+ critical(1), warning(2) or informational(3)."
+ ::= { memDoorSensorConfigEntry 5 }
+
+memDoorSensorConfigAlarmGeneration OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled (1),
+ enabled (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable alarm generation on this input."
+ ::= { memDoorSensorConfigEntry 6 }
+
+-- WIRELESS Table
+
+wirelessSensorStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF WirelessSensorStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for the access of individual sensors."
+ ::= { wirelessSensorStatus 1 }
+
+wirelessSensorStatusEntry OBJECT-TYPE
+ SYNTAX WirelessSensorStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of wireless sensor status table entries."
+ INDEX { wirelessSensorStatusIndex }
+ ::= { wirelessSensorStatusTable 1 }
+
+WirelessSensorStatusEntry ::=
+ SEQUENCE {
+ wirelessSensorStatusIndex INTEGER,
+ wirelessSensorStatusExtAddr DisplayString,
+ wirelessSensorStatusName DisplayString,
+ wirelessSensorStatusAlarmGeneration INTEGER,
+ wirelessSensorStatusTemperature INTEGER,
+ wirelessSensorStatusHighTempThresh INTEGER,
+ wirelessSensorStatusLowTempThresh INTEGER,
+ wirelessSensorStatusHumidity INTEGER,
+ wirelessSensorStatusHighHumidityThresh INTEGER,
+ wirelessSensorStatusLowHumidityThresh INTEGER,
+ wirelessSensorStatusCommStatus INTEGER,
+ wirelessSensorStatusMaxTempThresh INTEGER,
+ wirelessSensorStatusMinTempThresh INTEGER,
+ wirelessSensorStatusMaxHumidityThresh INTEGER,
+ wirelessSensorStatusMinHumidityThresh INTEGER,
+ wirelessSensorStatusBattery INTEGER,
+ wirelessSensorStatusLowBatteryThresh INTEGER,
+ wirelessSensorStatusMinBatteryThresh INTEGER,
+ wirelessSensorStatusRssi INTEGER,
+ wirelessSensorStatusLowRssiThresh INTEGER,
+ wirelessSensorStatusMinRssiThresh INTEGER,
+ wirelessSensorStatusLocation DisplayString,
+ wirelessSensorStatusAlarmStatus INTEGER
+ }
+
+wirelessSensorStatusIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the sensor entry."
+ ::= { wirelessSensorStatusEntry 1 }
+
+wirelessSensorStatusExtAddr OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The extended address is the combination of the unique 10 byte
+ MAC address of the sensor concatenated with its short address."
+ ::= { wirelessSensorStatusEntry 2 }
+
+wirelessSensorStatusName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the wireless sensor."
+ ::= { wirelessSensorStatusEntry 3 }
+
+wirelessSensorStatusAlarmGeneration OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled (0),
+ enabled (1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates whether alarm generation is enabled or disabled for the sensor."
+ ::= { wirelessSensorStatusEntry 4 }
+
+wirelessSensorStatusTemperature OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current temperature are displayed in tenths of degrees in the scale
+ shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
+ ::= { wirelessSensorStatusEntry 5 }
+
+wirelessSensorStatusHighTempThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Values are displayed in tenths of degrees in the scale
+ shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
+ ::= { wirelessSensorStatusEntry 6 }
+
+wirelessSensorStatusLowTempThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Values are displayed in tenths of degrees in the scale
+ shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
+ ::= { wirelessSensorStatusEntry 7 }
+
+wirelessSensorStatusHumidity OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Values are represented in whole number percentage."
+ ::= { wirelessSensorStatusEntry 8 }
+
+wirelessSensorStatusHighHumidityThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Values are represented in whole number percentage."
+ ::= { wirelessSensorStatusEntry 9 }
+
+wirelessSensorStatusLowHumidityThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Values are represented in whole number percentage."
+ ::= { wirelessSensorStatusEntry 10 }
+
+
+wirelessSensorStatusCommStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ inactive(0),
+ active(1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The communication status of the wireless sensor.
+ inactive(0) indicates sensor is in the wireless network but not sending information.
+ active(1) indicates wireless sensor is live and sending information."
+ ::= { wirelessSensorStatusEntry 11 }
+
+wirelessSensorStatusMaxTempThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Values are displayed in tenths of degrees in the scale
+ shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
+ ::= { wirelessSensorStatusEntry 12 }
+
+wirelessSensorStatusMinTempThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Values are displayed in tenths of degrees in the scale
+ shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
+ ::= { wirelessSensorStatusEntry 13 }
+
+wirelessSensorStatusMaxHumidityThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Values are represented in whole number percentage."
+ ::= { wirelessSensorStatusEntry 14 }
+
+wirelessSensorStatusMinHumidityThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Values are represented in whole number percentage."
+ ::= { wirelessSensorStatusEntry 15 }
+
+wirelessSensorStatusBattery OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Values are displayed in tenths of Volts DC."
+ ::= { wirelessSensorStatusEntry 16 }
+
+wirelessSensorStatusLowBatteryThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Values are displayed in tenths of Volts DC."
+ ::= { wirelessSensorStatusEntry 17 }
+
+wirelessSensorStatusMinBatteryThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Values are displayed in tenths of Volts DC."
+ ::= { wirelessSensorStatusEntry 18 }
+
+wirelessSensorStatusRssi OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Values are represented in whole number percentage."
+ ::= { wirelessSensorStatusEntry 19 }
+
+wirelessSensorStatusLowRssiThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Values are represented in whole number percentage."
+ ::= { wirelessSensorStatusEntry 20 }
+
+wirelessSensorStatusMinRssiThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Values are represented in whole number percentage."
+ ::= { wirelessSensorStatusEntry 21 }
+
+wirelessSensorStatusLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A user-defined string identifying the location
+ of the wireless sensor."
+ ::= { wirelessSensorStatusEntry 22 }
+
+wirelessSensorStatusAlarmStatus OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The alarm status of the wireless sensor. This integer should be interpreted
+ as a bit map, with each bit representing the presence or absence of
+ the specific alarm conditions listed below. The bit will be '1' if
+ the condition is present, and '0' if the condition is not present.
+
+ Bit Hex. Value Description
+ 1 0x0001 Maximum temperature exceeded.
+ 2 0x0002 High temperature exceeded.
+ 3 0x0004 Low temperature exceeded.
+ 4 0x0008 Minimum temperature exceeded.
+ 5 0x0010 Maximum humidity exceeded.
+ 6 0x0020 High humidity exceeded.
+ 7 0x0040 Low humidity exceeded.
+ 8 0x0080 Minimum humidity exceeded.
+ 9 0x0100 Low battery exceeded.
+ 10 0x0200 Minimum battery exceeded.
+ 11 0x0400 Low signal strength exceeded.
+ 12 0x0800 Minimum signal strength exceeded.
+ 13 0x1000 Sensor inactive."
+ ::= { wirelessSensorStatusEntry 23 }
+
+-- Sensor pod Status
+
+wirelessSensorPodStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF WirelessSensorPodStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for the access of individual pod sensors."
+ ::= { wirelessSensorPodStatus 1 }
+
+wirelessSensorPodStatusEntry OBJECT-TYPE
+ SYNTAX WirelessSensorPodStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The sensor pod to access."
+ INDEX { wirelessSensorPodStatusIndex }
+ ::= { wirelessSensorPodStatusTable 1 }
+
+WirelessSensorPodStatusEntry ::=
+ SEQUENCE {
+ wirelessSensorPodStatusIndex INTEGER,
+ wirelessSensorPodPortIndex INTEGER,
+ wirelessSensorPodStatusExtAddr DisplayString,
+ wirelessSensorPodStatusName DisplayString,
+ wirelessSensorPodStatusAlarmGeneration INTEGER,
+ wirelessSensorPodStatusTemperature INTEGER,
+ wirelessSensorPodStatusHighTempThresh INTEGER,
+ wirelessSensorPodStatusLowTempThresh INTEGER,
+ wirelessSensorPodStatusHumidity INTEGER,
+ wirelessSensorPodStatusHighHumidityThresh INTEGER,
+ wirelessSensorPodStatusLowHumidityThresh INTEGER,
+ wirelessSensorPodStatusCommStatus INTEGER,
+ wirelessSensorPodStatusMaxTempThresh INTEGER,
+ wirelessSensorPodStatusMinTempThresh INTEGER,
+ wirelessSensorPodStatusMaxHumidityThresh INTEGER,
+ wirelessSensorPodStatusMinHumidityThresh INTEGER,
+ wirelessSensorPodStatusDryContactState INTEGER,
+ wirelessSensorPodStatusDryContactNormalState INTEGER,
+ wirelessSensorPodStatusBattery INTEGER,
+ wirelessSensorPodStatusLowBatteryThresh INTEGER,
+ wirelessSensorPodStatusMinBatteryThresh INTEGER,
+ wirelessSensorPodStatusRssi INTEGER,
+ wirelessSensorPodStatusLowRssiThresh INTEGER,
+ wirelessSensorPodStatusMinRssiThresh INTEGER,
+ wirelessSensorPodStatusLocation DisplayString,
+ wirelessSensorPodStatusAlarmStatus INTEGER
+ }
+
+wirelessSensorPodStatusIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the pod sensor entry."
+ ::= { wirelessSensorPodStatusEntry 1 }
+
+ wirelessSensorPodPortIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The pod sensor port index."
+ ::= { wirelessSensorPodStatusEntry 2 }
+
+wirelessSensorPodStatusExtAddr OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The extended address is the combination of the unique 10 byte MAC address
+ of the sensor concatenated with its short address."
+ ::= { wirelessSensorPodStatusEntry 3 }
+
+
+wirelessSensorPodStatusName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the sensor pod."
+ ::= { wirelessSensorPodStatusEntry 4 }
+
+wirelessSensorPodStatusAlarmGeneration OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled (0),
+ enabled (1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Status of whether alarm generation is enabled or disabled."
+ ::= { wirelessSensorPodStatusEntry 5 }
+
+wirelessSensorPodStatusTemperature OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Values are displayed in tenths of degrees in the scale
+ shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
+ ::= { wirelessSensorPodStatusEntry 6 }
+
+wirelessSensorPodStatusHighTempThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Values are displayed in tenths of degrees in the scale
+ shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
+ ::= { wirelessSensorPodStatusEntry 7 }
+
+wirelessSensorPodStatusLowTempThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Values are displayed in tenths of degrees in the scale
+ shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
+ ::= { wirelessSensorPodStatusEntry 8 }
+
+wirelessSensorPodStatusHumidity OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Values are represented in whole number percentage."
+ ::= { wirelessSensorPodStatusEntry 9 }
+
+wirelessSensorPodStatusHighHumidityThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Values are represented in whole number percentage."
+ ::= { wirelessSensorPodStatusEntry 10 }
+
+wirelessSensorPodStatusLowHumidityThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Values are represented in whole number percentage."
+ ::= { wirelessSensorPodStatusEntry 11}
+
+
+wirelessSensorPodStatusCommStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ inactive(0),
+ active(1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The communication status of the wireless sensor.
+ inactive(0) indicates pod sensor is in the wireless network but not sending information.
+ active(1) indicates wireless sensor is live and sending information."
+ ::= { wirelessSensorPodStatusEntry 12 }
+
+wirelessSensorPodStatusMaxTempThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Values are displayed in tenths of degrees in the scale
+ shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
+ ::= { wirelessSensorPodStatusEntry 13 }
+
+wirelessSensorPodStatusMinTempThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Values are displayed in tenths of degrees in the scale
+ shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
+ ::= { wirelessSensorPodStatusEntry 14 }
+
+wirelessSensorPodStatusMaxHumidityThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Values are represented in whole number percentage."
+ ::= { wirelessSensorPodStatusEntry 15 }
+
+wirelessSensorPodStatusMinHumidityThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Values are represented in whole number percentage."
+ ::= { wirelessSensorPodStatusEntry 16 }
+
+wirelessSensorPodStatusDryContactState OBJECT-TYPE
+ SYNTAX INTEGER {
+ drycontactOpen (0),
+ drycontactClosed (1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "State of the dry contact. If the dry contact is closed,
+ the drycontactClosed (1) value will be returned. If the dry contact
+ state is open, the drycontactOpen (0) value will be returned."
+ ::= { wirelessSensorPodStatusEntry 17 }
+
+wirelessSensorPodStatusDryContactNormalState OBJECT-TYPE
+ SYNTAX INTEGER {
+ normallyOpen (0),
+ normallyClosed (1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The normal state of the dry contact. If the normal state is closed,
+ the normallyClosed (1) value will be returned. If the normal state is
+ open, the normallyOpen (0) value will be returned."
+ ::= { wirelessSensorPodStatusEntry 18 }
+
+wirelessSensorPodStatusBattery OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Values are displayed in tenths of Volts DC."
+ ::= { wirelessSensorPodStatusEntry 19 }
+
+wirelessSensorPodStatusLowBatteryThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Values are displayed in tenths of Volts DC."
+ ::= { wirelessSensorPodStatusEntry 20 }
+
+wirelessSensorPodStatusMinBatteryThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Values are displayed in tenths of Volts DC."
+ ::= { wirelessSensorPodStatusEntry 21 }
+
+wirelessSensorPodStatusRssi OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Values are represented in whole number percentage."
+ ::= { wirelessSensorPodStatusEntry 22 }
+
+wirelessSensorPodStatusLowRssiThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Values are represented in whole number percentage."
+ ::= { wirelessSensorPodStatusEntry 23 }
+
+wirelessSensorPodStatusMinRssiThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Values are represented in whole number percentage."
+ ::= { wirelessSensorPodStatusEntry 24 }
+
+wirelessSensorPodStatusLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The location of the wireless sensor pod."
+ ::= { wirelessSensorPodStatusEntry 25 }
+
+wirelessSensorPodStatusAlarmStatus OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The alarm status of the wireless pod sensor. This integer should be interpreted
+ as a bit map, with each bit representing the presence or absence of
+ the specific alarm conditions listed below. The bit will be '1' if
+ the condition is present, and '0' if the condition is not present.
+
+ Bit Hex. Value Description
+ 1 0x0001 Maximum temperature exceeded.
+ 2 0x0002 High temperature exceeded.
+ 3 0x0004 Low temperature exceeded.
+ 4 0x0008 Minimum temperature exceeded.
+ 5 0x0010 Maximum humidity exceeded.
+ 6 0x0020 High humidity exceeded.
+ 7 0x0040 Low humidity exceeded.
+ 8 0x0080 Minimum humidity exceeded.
+ 9 0x0100 Low battery exceeded.
+ 10 0x0200 Minimum battery exceeded.
+ 11 0x0400 Low signal strength exceeded.
+ 12 0x0800 Minimum signal strength exceeded.
+ 13 0x1000 Sensor inactive.
+ 14 0x2000 Dry contact in Critical state.
+ 15 0x4000 Dry contact in warning state."
+ ::= { wirelessSensorPodStatusEntry 26 }
+
+-- Sensor Config Table
+wirelessSensorConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF WirelessSensorConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for the configuration of individual sensors."
+ ::= { wirelessSensorConfig 1 }
+
+wirelessSensorConfigEntry OBJECT-TYPE
+ SYNTAX WirelessSensorConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The sensor to configure."
+ INDEX { wirelessSensorConfigIndex }
+ ::= { wirelessSensorConfigTable 1 }
+
+WirelessSensorConfigEntry ::=
+ SEQUENCE {
+ wirelessSensorConfigIndex INTEGER,
+ wirelessSensorConfigName DisplayString,
+ wirelessSensorConfigAlarmGeneration INTEGER,
+ wirelessSensorConfigHighTempThresh INTEGER,
+ wirelessSensorConfigLowTempThresh INTEGER,
+ wirelessSensorConfigHighHumidityThresh INTEGER,
+ wirelessSensorConfigLowHumidityThresh INTEGER,
+ wirelessSensorConfigMaxTempThresh INTEGER,
+ wirelessSensorConfigMinTempThresh INTEGER,
+ wirelessSensorConfigMaxHumidityThresh INTEGER,
+ wirelessSensorConfigMinHumidityThresh INTEGER,
+ wirelessSensorConfigLowBatteryThresh INTEGER,
+ wirelessSensorConfigMinBatteryThresh INTEGER,
+ wirelessSensorConfigLowRssiThresh INTEGER,
+ wirelessSensorConfigMinRssiThresh INTEGER,
+ wirelessSensorConfigLocation DisplayString
+ }
+
+wirelessSensorConfigIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the entry."
+ ::= { wirelessSensorConfigEntry 1 }
+
+wirelessSensorConfigName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The user-defined wireless sensor ID string."
+ ::= { wirelessSensorConfigEntry 2 }
+
+wirelessSensorConfigAlarmGeneration OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled (0),
+ enabled (1)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable alarm generation for this sensor."
+ ::= { wirelessSensorConfigEntry 3 }
+
+wirelessSensorConfigHighTempThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Values are displayed in tenths of degrees in the scale
+ shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
+ ::= { wirelessSensorConfigEntry 4 }
+
+wirelessSensorConfigLowTempThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Values are displayed in tenths of degrees in the scale
+ shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
+ ::= { wirelessSensorConfigEntry 5 }
+
+wirelessSensorConfigHighHumidityThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Values are represented in whole number percentage."
+ ::= { wirelessSensorConfigEntry 6 }
+
+wirelessSensorConfigLowHumidityThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Values are represented in whole number percentage."
+ ::= { wirelessSensorConfigEntry 7 }
+
+wirelessSensorConfigMaxTempThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Values are displayed in tenths of degrees in the scale
+ shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
+ ::= { wirelessSensorConfigEntry 8 }
+
+wirelessSensorConfigMinTempThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Values are displayed in tenths of degrees in the scale
+ shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
+ ::= { wirelessSensorConfigEntry 9 }
+
+wirelessSensorConfigMaxHumidityThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Values are represented in whole number percentage."
+ ::= { wirelessSensorConfigEntry 10 }
+
+wirelessSensorConfigMinHumidityThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Values are represented in whole number percentage."
+ ::= { wirelessSensorConfigEntry 11 }
+
+wirelessSensorConfigLowBatteryThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Values are displayed in tenths of Volts DC."
+ ::= { wirelessSensorConfigEntry 12 }
+
+wirelessSensorConfigMinBatteryThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Values are displayed in tenths of Volts DC."
+ ::= { wirelessSensorConfigEntry 13 }
+
+wirelessSensorConfigLowRssiThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Values are represented in whole number percentage."
+ ::= { wirelessSensorConfigEntry 14 }
+
+wirelessSensorConfigMinRssiThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Values are represented in whole number percentage."
+ ::= { wirelessSensorConfigEntry 15 }
+
+wirelessSensorConfigLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A user-defined string identifying the location of the
+ wireless sensor. Maximum text input is 20 characters."
+ ::= { wirelessSensorConfigEntry 16 }
+
+-- Sensor pod config Table
+wirelessSensorPodConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF WirelessSensorPodConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for the configuration of individual sensors."
+ ::= { wirelessSensorPodConfig 1 }
+
+wirelessSensorPodConfigEntry OBJECT-TYPE
+ SYNTAX WirelessSensorPodConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The sensor to configure."
+ INDEX { wirelessSensorPodConfigIndex, wirelessSensorPodConfigPortIndex }
+ ::= { wirelessSensorPodConfigTable 1 }
+
+WirelessSensorPodConfigEntry ::=
+ SEQUENCE {
+ wirelessSensorPodConfigIndex INTEGER,
+ wirelessSensorPodConfigPortIndex INTEGER,
+ wirelessSensorPodConfigName DisplayString,
+ wirelessSensorPodConfigAlarmGeneration INTEGER,
+ wirelessSensorPodConfigDryContactNormalState INTEGER,
+ wirelessSensorPodConfigHighTempThresh INTEGER,
+ wirelessSensorPodConfigLowTempThresh INTEGER,
+ wirelessSensorPodConfigHighHumidityThresh INTEGER,
+ wirelessSensorPodConfigLowHumidityThresh INTEGER,
+ wirelessSensorPodConfigMaxTempThresh INTEGER,
+ wirelessSensorPodConfigMinTempThresh INTEGER,
+ wirelessSensorPodConfigMaxHumidityThresh INTEGER,
+ wirelessSensorPodConfigMinHumidityThresh INTEGER,
+ wirelessSensorPodConfigLowBatteryThresh INTEGER,
+ wirelessSensorPodConfigMinBatteryThresh INTEGER,
+ wirelessSensorPodConfigLowRssiThresh INTEGER,
+ wirelessSensorPodConfigMinRssiThresh INTEGER,
+ wirelessSensorPodConfigLocation DisplayString
+ }
+
+wirelessSensorPodConfigIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the entry."
+ ::= { wirelessSensorPodConfigEntry 1 }
+
+wirelessSensorPodConfigPortIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The sensor pod port index."
+ ::= { wirelessSensorPodConfigEntry 2 }
+
+wirelessSensorPodConfigName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The user defined name of the sensor pod."
+ ::= { wirelessSensorPodConfigEntry 3 }
+
+wirelessSensorPodConfigAlarmGeneration OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled (0),
+ enabled (1)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable alarm generation for this sensor."
+ ::= { wirelessSensorPodConfigEntry 4 }
+
+wirelessSensorPodConfigDryContactNormalState OBJECT-TYPE
+ SYNTAX INTEGER {
+ normallyOpen (0),
+ normallyClosed (1)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The normal state of the dry contact. If the normal state is closed,
+ the normallyClosed (1) value will be returned. If the normal state is open,
+ the normallyOpen (0) value will be returned. Setting this variable will change
+ the normal state of the dry contact."
+ ::= { wirelessSensorPodConfigEntry 5 }
+
+
+wirelessSensorPodConfigHighTempThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Values are displayed in tenths of degrees in the scale
+ shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
+ ::= { wirelessSensorPodConfigEntry 6 }
+
+wirelessSensorPodConfigLowTempThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Values are displayed in tenths of degrees in the scale
+ shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
+ ::= { wirelessSensorPodConfigEntry 7 }
+
+wirelessSensorPodConfigHighHumidityThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Values are represented in whole number percentage."
+ ::= { wirelessSensorPodConfigEntry 8 }
+
+wirelessSensorPodConfigLowHumidityThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Values are represented in whole number percentage."
+ ::= { wirelessSensorPodConfigEntry 9 }
+
+wirelessSensorPodConfigMaxTempThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Values are displayed in tenths of degrees in the scale
+ shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
+ ::= { wirelessSensorPodConfigEntry 10 }
+
+wirelessSensorPodConfigMinTempThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Values are represented in whole number degrees.
+ Units are displayed in the scale shown in
+ the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
+ ::= { wirelessSensorPodConfigEntry 11 }
+
+wirelessSensorPodConfigMaxHumidityThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Values are represented in whole number percentage."
+ ::= { wirelessSensorPodConfigEntry 12 }
+
+wirelessSensorPodConfigMinHumidityThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Values are represented in whole number percentage."
+ ::= { wirelessSensorPodConfigEntry 13 }
+
+wirelessSensorPodConfigLowBatteryThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Values are displayed in tenths of Volts DC."
+ ::= { wirelessSensorPodConfigEntry 14 }
+
+wirelessSensorPodConfigMinBatteryThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Values are displayed in tenths of Volts DC."
+ ::= { wirelessSensorPodConfigEntry 15 }
+
+wirelessSensorPodConfigLowRssiThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Values are represented in whole number percentage."
+ ::= { wirelessSensorPodConfigEntry 16 }
+
+wirelessSensorPodConfigMinRssiThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Values are represented in whole number percentage."
+ ::= { wirelessSensorPodConfigEntry 17 }
+
+wirelessSensorPodConfigLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A user-defined string identifying the location of the
+ wireless pod sensor. Maximum text input is 20 characters."
+ ::= { wirelessSensorPodConfigEntry 18 }
+
+-- Integrated Environmental Monitor (IEM)
+
+iemIdentHardwareRevision OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The hardware revision of the Integrated Environmental
+ Monitor."
+ ::= { iemIdent 1 }
+
+iemConfigProbesNumProbes OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of temperature and humidity probes available."
+ ::= { iemConfig 1 }
+
+iemConfigProbesTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF IemConfigProbesEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of probes supported by the Environmental Monitor
+ and their configurations."
+ ::= { iemConfig 2 }
+
+iemConfigProbesEntry OBJECT-TYPE
+ SYNTAX IemConfigProbesEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The Environmental Monitor probe configurations."
+ INDEX { iemConfigProbeNumber }
+ ::= { iemConfigProbesTable 1 }
+
+IemConfigProbesEntry ::=
+ SEQUENCE {
+ iemConfigProbeNumber
+ INTEGER,
+ iemConfigProbeName
+ DisplayString,
+ iemConfigProbeHighTempThreshold
+ INTEGER,
+ iemConfigProbeLowTempThreshold
+ INTEGER,
+ iemConfigProbeTempUnits
+ INTEGER,
+ iemConfigProbeHighHumidThreshold
+ INTEGER,
+ iemConfigProbeLowHumidThreshold
+ INTEGER,
+ iemConfigProbeHighTempEnable
+ INTEGER,
+ iemConfigProbeLowTempEnable
+ INTEGER,
+ iemConfigProbeHighHumidEnable
+ INTEGER,
+ iemConfigProbeLowHumidEnable
+ INTEGER,
+ iemConfigProbeMaxTempThreshold
+ INTEGER,
+ iemConfigProbeMinTempThreshold
+ INTEGER,
+ iemConfigProbeMaxHumidThreshold
+ INTEGER,
+ iemConfigProbeMinHumidThreshold
+ INTEGER,
+ iemConfigProbeMaxTempEnable
+ INTEGER,
+ iemConfigProbeMinTempEnable
+ INTEGER,
+ iemConfigProbeMaxHumidEnable
+ INTEGER,
+ iemConfigProbeMinHumidEnable
+ INTEGER,
+ iemConfigProbeTempHysteresis
+ INTEGER,
+ iemConfigProbeHumidHysteresis
+ INTEGER,
+ iemConfigProbeLocation
+ DisplayString
+ }
+
+iemConfigProbeNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to a Environmental Monitor probe entry."
+ ::= { iemConfigProbesEntry 1 }
+
+iemConfigProbeName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A descriptive name for the probe set by the user,
+ possibly denoting its location or purpose."
+ ::= { iemConfigProbesEntry 2 }
+
+iemConfigProbeHighTempThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The high temperature alarm threshold for the probe.
+ Units are displayed in the scale selected in the
+ 'iemConfigProbeTempUnits' OID (Celsius or Fahrenheit)."
+ ::= { iemConfigProbesEntry 3 }
+
+iemConfigProbeLowTempThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The low temperature alarm threshold for the probe.
+ Units are displayed in the scale selected in the
+ 'iemConfigProbeTempUnits' OID (Celsius or Fahrenheit)."
+ ::= { iemConfigProbesEntry 4 }
+
+iemConfigProbeTempUnits OBJECT-TYPE
+ SYNTAX INTEGER {
+ celsius(1),
+ fahrenheit(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature scale used to display the temperature
+ thresholds of the probe, Celsius(1) or Fahrenheit(2).
+ This setting is based on the system preferences
+ configuration in the agent."
+ ::= { iemConfigProbesEntry 5 }
+
+iemConfigProbeHighHumidThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The high humidity alarm threshold for the probe in
+ percent relative humidity."
+ ::= { iemConfigProbesEntry 6 }
+
+iemConfigProbeLowHumidThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The low humidity alarm threshold for the probe in
+ percent relative humidity."
+ ::= { iemConfigProbesEntry 7 }
+
+iemConfigProbeHighTempEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(1),
+ enabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The high temperature alarm enable/disable for the
+ probe. No alarm will be generated if this value
+ is set to disabled(1). The alarm will be
+ generated if this value is set to enabled(2) and
+ the threshold has been violated."
+ ::= { iemConfigProbesEntry 8 }
+
+iemConfigProbeLowTempEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(1),
+ enabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The low temperature alarm enable/disable for the
+ probe. No alarm will be generated if this value
+ is set to disabled(1). The alarm will be
+ generated if this value is set to enabled(2) and
+ the threshold has been violated."
+ ::= { iemConfigProbesEntry 9 }
+
+iemConfigProbeHighHumidEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(1),
+ enabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The high humidity alarm enable/disable for the
+ probe. No alarm will be generated if this value
+ is set to disabled(1). The alarm will be
+ generated if this value is set to enabled(2) and
+ the threshold has been violated."
+ ::= { iemConfigProbesEntry 10 }
+
+iemConfigProbeLowHumidEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(1),
+ enabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The low humidity alarm enable/disable for the
+ probe. No alarm will be generated if this value
+ is set to disabled(1). The alarm will be
+ generated if this value is set to enabled(2) and
+ the threshold has been violated."
+ ::= { iemConfigProbesEntry 11 }
+
+iemConfigProbeMaxTempThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The maximun temperature alarm threshold for the probe.
+ Units are displayed in the scale selected in the
+ 'iemConfigProbeTempUnits' OID (Celsius or Fahrenheit)."
+ ::= { iemConfigProbesEntry 12 }
+
+iemConfigProbeMinTempThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The minimun temperature alarm threshold for the probe.
+ Units are displayed in the scale selected in the
+ 'iemConfigProbeTempUnits' OID (Celsius or Fahrenheit)."
+ ::= { iemConfigProbesEntry 13 }
+
+iemConfigProbeMaxHumidThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum humidity alarm threshold for the probe in
+ percent relative humidity."
+ ::= { iemConfigProbesEntry 14 }
+
+iemConfigProbeMinHumidThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum humidity alarm threshold for the probe in
+ percent relative humidity."
+ ::= { iemConfigProbesEntry 15 }
+
+iemConfigProbeMaxTempEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(1),
+ enabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum temperature alarm enable/disable for the
+ probe. No alarm will be generated if this value
+ is set to disabled(1). The alarm will be
+ generated if this value is set to enabled(2) and
+ the threshold has been violated."
+ ::= { iemConfigProbesEntry 16 }
+
+iemConfigProbeMinTempEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(1),
+ enabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The low temperature alarm enable/disable for the
+ probe. No alarm will be generated if this value
+ is set to disabled(1). The alarm will be
+ generated if this value is set to enabled(2) and
+ the threshold has been violated."
+ ::= { iemConfigProbesEntry 17 }
+
+iemConfigProbeMaxHumidEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(1),
+ enabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum humidity alarm enable/disable for the
+ probe. No alarm will be generated if this value
+ is set to disabled(1). The alarm will be
+ generated if this value is set to enabled(2) and
+ the threshold has been violated."
+ ::= { iemConfigProbesEntry 18 }
+
+iemConfigProbeMinHumidEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(1),
+ enabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum humidity alarm enable/disable for the
+ probe. No alarm will be generated if this value
+ is set to disabled(1). The alarm will be
+ generated if this value is set to enabled(2) and
+ the threshold has been violated."
+ ::= { iemConfigProbesEntry 19 }
+
+iemConfigProbeTempHysteresis OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The number of degrees beyond the temperature thresholds
+ at which an active temperature alarm will be cleared.
+ This configuration setting applies to all temperature
+ thresholds.
+ Units are displayed in the scale selected in
+ the 'emConfigProbeTempUnits' OID (Celsius or Fahrenheit)."
+ ::= { iemConfigProbesEntry 20 }
+
+iemConfigProbeHumidHysteresis OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The number of percent RH points beyond the humidity
+ thresholds at which an active humidity alarm will be
+ cleared. This configuration setting applies to all
+ humidity thresholds.
+ Units are displayed in the scale selected in
+ the 'emConfigProbeTempUnits' OID (Celsius or Fahrenheit)."
+ ::= { iemConfigProbesEntry 21 }
+
+iemConfigProbeLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A string describing the location of the probe."
+ ::= { iemConfigProbesEntry 22 }
+
+iemConfigContactsNumContacts OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of contacts available on the Environmental
+ Monitor."
+ ::= { iemConfig 3 }
+
+iemConfigContactsTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF IemConfigContactsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of contacts supported by the Environmental Monitor
+ and their configurations."
+ ::= { iemConfig 4 }
+
+iemConfigContactsEntry OBJECT-TYPE
+ SYNTAX IemConfigContactsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The Environmental Monitor contact configurations."
+ INDEX { iemConfigContactNumber }
+ ::= { iemConfigContactsTable 1 }
+
+IemConfigContactsEntry ::=
+ SEQUENCE {
+ iemConfigContactNumber
+ INTEGER,
+ iemConfigContactName
+ DisplayString,
+ iemConfigContactEnable
+ INTEGER,
+ iemConfigContactSeverity
+ INTEGER,
+ iemConfigContactNormalState
+ INTEGER,
+ iemConfigContactLocation
+ DisplayString
+ }
+
+iemConfigContactNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of an Environmental Monitor contact."
+ ::= { iemConfigContactsEntry 1 }
+
+iemConfigContactName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A descriptive name for the Environmental Monitor contact
+ set by the user, possibly denoting its location or purpose."
+ ::= { iemConfigContactsEntry 2 }
+
+iemConfigContactEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(1),
+ enabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "An Environmental Monitor contact alarm enable/disable."
+ ::= { iemConfigContactsEntry 3 }
+
+iemConfigContactSeverity OBJECT-TYPE
+ SYNTAX INTEGER {
+ critical(1),
+ warning(2),
+ informational(3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The severtity of the alarm that will be triggered when
+ the input contact is activated. The alarms can be
+ critical(1), warning(2) or informational(3).
+ NOTE: informational(3) is deprecated (and no longer valid) for this OID."
+ ::= { iemConfigContactsEntry 4 }
+
+iemConfigContactNormalState OBJECT-TYPE
+ SYNTAX INTEGER {
+ open(1),
+ closed(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The contact state that will be considered normal, i.e.
+ will not trigger an alarm. The states are open(1) or
+ closed(2)."
+ ::= { iemConfigContactsEntry 5 }
+
+iemConfigContactLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A descriptive label for the contact denoting its
+ location or purpose."
+ ::= { iemConfigContactsEntry 6 }
+
+iemConfigConfigRelaysNumRelays OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of output relays supported by the Environmental
+ Monitor."
+ ::= { iemConfig 5 }
+
+
+iemConfigRelaysTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF IemConfigRelaysEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of output relays supported by the Environmental Monitor
+ and their configurations."
+ ::= { iemConfig 6 }
+
+iemConfigRelaysEntry OBJECT-TYPE
+ SYNTAX IemConfigRelaysEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The Environmental Monitor output relay configurations."
+ INDEX { iemConfigRelayNumber }
+ ::= { iemConfigRelaysTable 1 }
+
+IemConfigRelaysEntry ::=
+ SEQUENCE {
+ iemConfigRelayNumber
+ INTEGER,
+ iemConfigRelayName
+ DisplayString,
+ iemConfigRelayNormalState
+ INTEGER,
+ iemConfigRelayFaultCondition
+ INTEGER
+ }
+
+iemConfigRelayNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of an Environmental Monitor output relay."
+ ::= { iemConfigRelaysEntry 1 }
+
+iemConfigRelayName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A descriptive name of an Environmental Monitor output relay,
+ set by the user, describing its location or purpose."
+ ::= { iemConfigRelaysEntry 2 }
+
+iemConfigRelayNormalState OBJECT-TYPE
+ SYNTAX INTEGER {
+ open(1),
+ closed(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The normal state (non-fault state) of an Environmental
+ Monitor output relay, either open(1) or closed(2)."
+ ::= { iemConfigRelaysEntry 3 }
+
+iemConfigRelayFaultCondition OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The fault condition used to activate the output relay."
+ ::= { iemConfigRelaysEntry 4 }
+
+iemStatusProbesNumProbes OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of available probes on the Environmental
+ Monitor."
+ ::= { iemStatus 1 }
+
+iemStatusProbesTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF IemStatusProbesEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of probes supported by the Environmental Monitor
+ and their status."
+ ::= { iemStatus 2 }
+
+iemStatusProbesEntry OBJECT-TYPE
+ SYNTAX IemStatusProbesEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the probe."
+ INDEX { iemStatusProbeNumber }
+ ::= { iemStatusProbesTable 1 }
+
+IemStatusProbesEntry ::=
+ SEQUENCE {
+ iemStatusProbeNumber
+ INTEGER,
+ iemStatusProbeName
+ DisplayString,
+ iemStatusProbeStatus
+ INTEGER,
+ iemStatusProbeCurrentTemp
+ INTEGER,
+ iemStatusProbeTempUnits
+ INTEGER,
+ iemStatusProbeCurrentHumid
+ INTEGER,
+ iemStatusProbeHighTempViolation
+ INTEGER,
+ iemStatusProbeLowTempViolation
+ INTEGER,
+ iemStatusProbeHighHumidViolation
+ INTEGER,
+ iemStatusProbeLowHumidViolation
+ INTEGER,
+ iemStatusProbeMaxTempViolation
+ INTEGER,
+ iemStatusProbeMinTempViolation
+ INTEGER,
+ iemStatusProbeMaxHumidViolation
+ INTEGER,
+ iemStatusProbeMinHumidViolation
+ INTEGER,
+ iemStatusProbeLocation
+ DisplayString
+ }
+
+iemStatusProbeNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of the probe."
+ ::= { iemStatusProbesEntry 1 }
+
+iemStatusProbeName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A descriptive name for the probe set by the user."
+ ::= { iemStatusProbesEntry 2 }
+
+iemStatusProbeStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ disconnected(1),
+ connected(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The connected status of the probe, either
+ disconnected(1) or connected(2)."
+ ::= { iemStatusProbesEntry 3 }
+
+iemStatusProbeCurrentTemp OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current temperature reading from the probe displayed
+ in the units shown in the 'iemStatusProbeTempUnits' OID
+ (Celsius or Fahrenheit)."
+ ::= { iemStatusProbesEntry 4 }
+
+iemStatusProbeTempUnits OBJECT-TYPE
+ SYNTAX INTEGER {
+ celsius(1),
+ fahrenheit(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature scale used to display the temperature
+ thresholds of the probe, Celsius(1) or Fahrenheit(2).
+ This setting is based on the system preferences
+ configuration in the agent."
+ ::= { iemStatusProbesEntry 5 }
+
+iemStatusProbeCurrentHumid OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current humidity reading from the probe in percent
+ relative humidity."
+ ::= { iemStatusProbesEntry 6 }
+
+iemStatusProbeHighTempViolation OBJECT-TYPE
+ SYNTAX INTEGER {
+ noViolation(1),
+ highTempViolation(2),
+ disabled(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The high temperature violation status of the probe
+ temperature reading. This OID will show a highTempViolation(2)
+ if the current temperature reading shown in the
+ 'iemStatusProbeCurrentTemp' OID is greater than or equal to
+ the high temperature threshold value, the
+ 'iemConfigProbeHighTempThreshold' OID, and the value of the
+ 'iemConfigProbeHighTempEnable' OID is enabled. Otherwise it will show
+ noViolation(1). If the 'iemConfigProbeHighTempEnable' OID is disabled,
+ this OID will show disabled(3)."
+ ::= { iemStatusProbesEntry 7 }
+
+iemStatusProbeLowTempViolation OBJECT-TYPE
+ SYNTAX INTEGER {
+ noViolation(1),
+ lowTempViolation(2),
+ disabled(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The high temperature violation status of the probe
+ temperature reading. This OID will show a lowTempViolation(2)
+ if the current temperature reading shown in the
+ 'iemStatusProbeCurrentTemp' OID is less than or equal to
+ the low temperature threshold value, the
+ 'iemConfigProbeLowTempThreshold' OID, and the value of the
+ 'iemPConfigrobeLowTempEnable' OID is enabled. Otherwise it will show
+ noViolation(1). If the 'iemConfigProbeLowTempEnable' OID is disabled,
+ this OID will show disabled(3)."
+ ::= { iemStatusProbesEntry 8 }
+
+iemStatusProbeHighHumidViolation OBJECT-TYPE
+ SYNTAX INTEGER {
+ noViolation(1),
+ highHumidViolation(2),
+ disabled(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The high humidity violation status of the probe humidity
+ reading. This OID will show a highTempViolation(2)
+ if the current humidity reading shown in the
+ 'iemStatusProbeCurrentHumid' OID is greater than or equal to
+ the high humidity threshold value, the
+ 'iemConfigProbeHighHumidThreshold' OID, and the value of the
+ 'iemConfigProbeHighHumidEnable' OID is enabled. Otherwise it will
+ show noViolation(1). If the 'iemConfigProbeHighHumidEnable' OID is
+ disabled, this OID will show disabled(3)."
+ ::= { iemStatusProbesEntry 9 }
+
+iemStatusProbeLowHumidViolation OBJECT-TYPE
+ SYNTAX INTEGER {
+ noViolation(1),
+ lowHumidViolation(2),
+ disabled(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The low humidity violation status of the probe humidity
+ reading. This OID will show a lowTempViolation(2)
+ if the current humidity reading shown in the
+ 'iemStatusProbeCurrentHumid' OID is less than or equal to
+ the low humidity threshold value, the
+ 'iemConfigProbeLowHumidThreshold' OID, and the value of the
+ 'iemConfigProbeLowHumidEnable' OID is enabled. Otherwise it will
+ show noViolation(1). If the 'iemConfigProbeLowHumidEnable' OID is
+ disabled, this OID will show disabled(3)."
+ ::= { iemStatusProbesEntry 10 }
+
+iemStatusProbeMaxTempViolation OBJECT-TYPE
+ SYNTAX INTEGER {
+ noViolation(1),
+ maxTempViolation(2),
+ disabled(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The max temperature violation status of the probe
+ temperature reading. This OID will show a maxTempViolation(2)
+ if the current temperature reading shown in the
+ 'iemStatusProbeCurrentTemp' OID is greater than or equal to
+ the maximun temperature threshold value, the
+ 'iemConfigProbeMaxTempThreshold' OID, and the value of the
+ 'iemConfigProbeMaxTempEnable' OID is enabled. Otherwise it will show
+ noViolation(1). If the 'iemConfigProbeMaxTempEnable' OID is disabled,
+ this OID will show disabled(3)."
+ ::= { iemStatusProbesEntry 11 }
+
+iemStatusProbeMinTempViolation OBJECT-TYPE
+ SYNTAX INTEGER {
+ noViolation(1),
+ minTempViolation(2),
+ disabled(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum temperature violation status of the probe
+ temperature reading. This OID will show a minTempViolation(2)
+ if the current temperature reading shown in the
+ 'iemStatusProbeCurrentTemp' OID is less than or equal to
+ the minimum temperature threshold value, the
+ 'iemConfigProbeMinTempThreshold' OID, and the value of the
+ 'iemConfigProbeMinTempEnable' OID is enabled. Otherwise it will show
+ noViolation(1). If the 'iemConfigProbeMinTempEnable' OID is disabled,
+ this OID will show disabled(3)."
+ ::= { iemStatusProbesEntry 12 }
+
+iemStatusProbeMaxHumidViolation OBJECT-TYPE
+ SYNTAX INTEGER {
+ noViolation(1),
+ maxHumidViolation(2),
+ disabled(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum humidity violation status of the probe humidity
+ reading. This OID will show a maxTempViolation(2)
+ if the current humidity reading shown in the
+ 'iemStatusProbeCurrentHumid' OID is greater than or equal to
+ the maximum humidity threshold value, the
+ 'iemConfigProbeMaxHumidThreshold' OID, and the value of the
+ 'iemConfigProbeMaxHumidEnable' OID is enabled. Otherwise it will
+ show noViolation(1). If the 'iemConfigProbeMaxHumidEnable' OID is
+ disabled, this OID will show disabled(3)"
+ ::= { iemStatusProbesEntry 13 }
+
+iemStatusProbeMinHumidViolation OBJECT-TYPE
+ SYNTAX INTEGER {
+ noViolation(1),
+ minHumidViolation(2),
+ disabled(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum humidity violation status of the probe humidity
+ reading. This OID will show a minTempViolation(2)
+ if the current humidity reading shown in the
+ 'iemStatusProbeCurrentHumid' OID is less than or equal to
+ the minimum humidity threshold value, the
+ 'iemConfigProbeMinHumidThreshold' OID, and the value of the
+ 'iemConfigProbeMinHumidEnable' OID is enabled. Otherwise it will
+ show noViolation(1). If the 'iemConfigProbeMinHumidEnable' OID is
+ disabled, this OID will show disabled(3)."
+ ::= { iemStatusProbesEntry 14 }
+
+iemStatusProbeLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A descriptive location for the probe set by the user."
+ ::= { iemStatusProbesEntry 15 }
+
+iemStatusContactsNumContacts OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of contacts supported on the
+ Environmental Monitor."
+ ::= { iemStatus 3 }
+
+iemStatusContactsTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF IemStatusContactsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of contacts supported by the Environmental Monitor
+ and their status."
+ ::= { iemStatus 4 }
+
+iemStatusContactsEntry OBJECT-TYPE
+ SYNTAX IemStatusContactsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the contact."
+ INDEX { iemStatusContactNumber }
+ ::= { iemStatusContactsTable 1 }
+
+IemStatusContactsEntry ::=
+ SEQUENCE {
+ iemStatusContactNumber
+ INTEGER,
+ iemStatusContactName
+ DisplayString,
+ iemStatusContactStatus
+ INTEGER
+ }
+
+iemStatusContactNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of the Environmental Monitor contact."
+ ::= { iemStatusContactsEntry 1 }
+
+iemStatusContactName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A descriptive name for the Environmental Monitor contact
+ set by the user, denoting its location or purpose."
+ ::= { iemStatusContactsEntry 2 }
+
+iemStatusContactStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ noFault(1),
+ fault(2),
+ disabled(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the Environmental Monitor contact. The status
+ will show noFault(1) if the contact is in the normal state
+ and the 'iemConfigContactEnable' OID is enabled. The status will
+ show a fault(2) if the contact is faulted and the
+ 'iemConfigContactEnable' OID is enabled. If the
+ 'iemConfigContactEnable' OID is disabled, the status will show
+ disabled(3)."
+ ::= { iemStatusContactsEntry 3 }
+
+iemStatusRelaysNumRelays OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of output relays supported on the
+ Environmental Monitor."
+ ::= { iemStatus 6 }
+
+iemStatusRelaysTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF IemStatusRelaysEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of output relays supported by the
+ Environmental Monitor and their status."
+ ::= { iemStatus 7 }
+
+iemStatusRelaysEntry OBJECT-TYPE
+ SYNTAX IemStatusRelaysEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the relay."
+ INDEX { iemStatusRelayNumber }
+ ::= { iemStatusRelaysTable 1 }
+
+IemStatusRelaysEntry ::=
+ SEQUENCE {
+ iemStatusRelayNumber
+ INTEGER,
+ iemStatusRelayName
+ DisplayString,
+ iemStatusRelayStatus
+ INTEGER
+ }
+
+iemStatusRelayNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of the output relay."
+ ::= { iemStatusRelaysEntry 1 }
+
+iemStatusRelayName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A descriptive name for the output relay set by the
+ user, denoting its location or purpose."
+ ::= { iemStatusRelaysEntry 2 }
+
+iemStatusRelayStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ faultState(1),
+ normalState(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the output relay, either faultState(1) or
+ normalState(2)."
+ ::= { iemStatusRelaysEntry 3 }
+
+-- Environmental Management System (EMS)
+
+-- EMS IDENT
+
+emsIdentEMSName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the
+ device. "
+ ::= { emsIdent 1 }
+
+emsIdentProductNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the model number of
+ the device. This value is set at the factory."
+ ::= { emsIdent 2 }
+
+emsIdentFirmwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The firmware revision of the device."
+ ::= { emsIdent 3 }
+
+emsIdentHardwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The hardware revision of the device.
+ This value is set at the factory."
+ ::= { emsIdent 4 }
+
+emsIdentDateOfManufacture OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The date when the device was manufactured in mm/dd/yyyy format.
+ This value is set at the factory. "
+ ::= { emsIdent 5 }
+
+emsIdentSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the serial number of
+ the device. This value is set at the factory."
+ ::= { emsIdent 6 }
+
+-- EMS CONTROL
+
+-- EMS OUTPUT RELAY CONTROL STATUS TABLE
+
+emsOutputRelayControlTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF EmsOutputRelayControlEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for control of individual output relays. The number of
+ entries is contained in the emsStatusOutputRelayCount OID."
+ ::= { emsOutputRelayControl 1 }
+
+emsOutputRelayControlEntry OBJECT-TYPE
+ SYNTAX EmsOutputRelayControlEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The output relays to control."
+ INDEX { emsOutputRelayControlOutputRelayIndex }
+ ::= { emsOutputRelayControlTable 1 }
+
+EmsOutputRelayControlEntry ::=
+ SEQUENCE {
+ emsOutputRelayControlOutputRelayIndex INTEGER,
+ emsOutputRelayControlOutputRelayName DisplayString,
+ emsOutputRelayControlOutputRelayCommand INTEGER
+ }
+
+emsOutputRelayControlOutputRelayIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the output relay entry."
+ ::= { emsOutputRelayControlEntry 1 }
+
+emsOutputRelayControlOutputRelayName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the output relay.
+ This OID is provided for informational purposes only."
+ ::= { emsOutputRelayControlEntry 2 }
+
+emsOutputRelayControlOutputRelayCommand OBJECT-TYPE
+ SYNTAX INTEGER {
+ immediateCloseEMS (1),
+ immediateOpenEMS (2)
+ }
+
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this variable will return the output relay state. If
+ the output relay is closed, the immediateCloseEMS (1) value will be returned.
+ If the output relay is open, the immediateOpenEMS (2) value will be
+ returned.
+
+ Setting this variable to immediateCloseEMS (1) will immediately close the relay.
+
+ Setting this variable to immediateOpenEMS (2) will immediately open the relay."
+ ::= { emsOutputRelayControlEntry 3 }
+
+-- EMS OUTLET CONTROL TABLE
+
+emsOutletControlTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF EmsOutletControlEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for control of individual outlet switches. The number of
+ entries is contained in the emsStatusOutletCount OID."
+ ::= { emsOutletControl 1 }
+
+emsOutletControlEntry OBJECT-TYPE
+ SYNTAX EmsOutletControlEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The outlets to control."
+ INDEX { emsOutletControlOutletIndex }
+ ::= { emsOutletControlTable 1 }
+
+EmsOutletControlEntry ::=
+ SEQUENCE {
+ emsOutletControlOutletIndex INTEGER,
+ emsOutletControlOutletName DisplayString,
+ emsOutletControlOutletCommand INTEGER
+ }
+
+emsOutletControlOutletIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the outlet entry."
+ ::= { emsOutletControlEntry 1 }
+
+emsOutletControlOutletName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the outlet.
+ This OID is provided for informational purposes only."
+ ::= { emsOutletControlEntry 2 }
+
+emsOutletControlOutletCommand OBJECT-TYPE
+ SYNTAX INTEGER {
+ immediateOnEMS (1),
+ immediateOffEMS (2)
+ }
+
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this variable will return the outlet state. If
+ the outlet is on, the immediateOnEMS (1) value will be returned.
+ If the outlet is off, the immediateOffEMS (2) value will be
+ returned.
+
+ Setting this variable to immediateOnEMS (1) will immediately turn the outlet on.
+
+ Setting this variable to immediateOffEMS (2) will immediately turn the outlet off."
+ ::= { emsOutletControlEntry 3 }
+
+-- EMS SENSOR CONTROL TABLE
+
+emsSensorControlTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF EMSSensorControlEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for control/reset of individual sensors. The number of
+ entries is contained in the emsStatusSensorCount OID."
+ ::= { emsSensorControl 1 }
+
+emsSensorControlEntry OBJECT-TYPE
+ SYNTAX EMSSensorControlEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The sensors to control/reset."
+ INDEX { emsSensorControlSensorIndex }
+ ::= { emsSensorControlTable 1 }
+
+EMSSensorControlEntry ::=
+ SEQUENCE {
+ emsSensorControlSensorIndex INTEGER,
+ emsSensorControlSensorSystemName DisplayString,
+ emsSensorControlSensorUserName DisplayString,
+ emsSensorControlSensorCommand INTEGER
+ }
+
+emsSensorControlSensorIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the sensor entry."
+ ::= { emsSensorControlEntry 1 }
+
+emsSensorControlSensorSystemName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The system name of the sensor. This describes the hardware system
+ intent of this sensor."
+ ::= { emsSensorControlEntry 2 }
+
+emsSensorControlSensorUserName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the sensor as given by the system user."
+ ::= { emsSensorControlEntry 3 }
+
+emsSensorControlSensorCommand OBJECT-TYPE
+ SYNTAX INTEGER {
+ noCommandEMS (1),
+ resetCommandEMS (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this variable will return noCommandEMS(1).
+
+ Setting this variable to resetCommandEMS(2) will issue a reset command to the
+ sensor. Some sensors cannot be manually reset and will not be affected
+ by this command."
+ ::= { emsSensorControlEntry 4 }
+
+-- EMS ALARM DEVICE CONTROL TABLE
+
+emsAlarmDeviceControlTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF EmsAlarmDeviceControlEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for control of individual alarm devices.
+ Note: Some alarm devices are not controllable. The number of
+ entries is contained in the emsStatusAlarmDeviceCount OID."
+ ::= { emsAlarmDeviceControl 1 }
+
+emsAlarmDeviceControlEntry OBJECT-TYPE
+ SYNTAX EmsAlarmDeviceControlEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The alarm devices to control."
+ INDEX { emsAlarmDeviceControlDeviceIndex }
+ ::= { emsAlarmDeviceControlTable 1 }
+
+EmsAlarmDeviceControlEntry ::=
+ SEQUENCE {
+ emsAlarmDeviceControlDeviceIndex INTEGER,
+ emsAlarmDeviceControlDeviceName DisplayString,
+ emsAlarmDeviceControlDeviceCommand INTEGER
+ }
+
+emsAlarmDeviceControlDeviceIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the alarm device entry."
+ ::= { emsAlarmDeviceControlEntry 1 }
+
+emsAlarmDeviceControlDeviceName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the alarm device.
+ This OID is provided for informational purposes only."
+ ::= { emsAlarmDeviceControlEntry 2 }
+
+emsAlarmDeviceControlDeviceCommand OBJECT-TYPE
+ SYNTAX INTEGER {
+ alarmDeviceOnEMS (1),
+ alarmDeviceOffEMS (2),
+ alarmDeviceNotInstalledEMS (3)
+ }
+
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this variable will return the device state. If
+ the device is active, the alarmDeviceOnEMS (1) value will be returned.
+ If the device is inactive, the alarmDeviceOffEMS (2) value will be
+ returned. If the device is not installed, the
+ alarmDeviceNotInstalledEMS (3) value will be returned.
+
+ Actions resulting from setting this variable are device-dependent.
+
+ Setting this variable to alarmDeviceOnEMS (1) will turn that device (ex. Beacon) on.
+ Setting this variable to alarmDeviceOffEMS (2) will turn that device off."
+
+ ::= { emsAlarmDeviceControlEntry 3 }
+
+
+-- EMS CONFIG
+
+emsConfigName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the device."
+ ::= { emsConfig 1 }
+
+emsConfigCheckLogLight OBJECT-TYPE
+ SYNTAX INTEGER {
+ lightDisabled (1),
+ lightOnInformational (2),
+ lightOnWarning (3),
+ lightOnSevere (4)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The setting of this OID determines the level of event that will
+ trigger the check-log light on the EMS. This is not available on the EMU2.
+
+ lightDisabled (1) disables the check-log light.
+ lightOnInformational (2) lights check-log for any event of
+ informational severity or above.
+ lightOnWarning (3) lights check-log for any event of
+ warning severity or above.
+ lightOnSevere (4) lights check-log for any event of severe severity."
+
+ ::= { emsConfig 2 }
+
+-- EMS PROBE CONFIG TABLE
+
+emsProbeConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF EMSProbeConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for configuration of individual probes. The number of
+ entries is contained in the emsStatusProbeCount OID."
+ ::= { emsProbeConfig 1 }
+
+emsProbeConfigEntry OBJECT-TYPE
+ SYNTAX EMSProbeConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The probes to configure."
+ INDEX { emsProbeConfigProbeIndex }
+ ::= { emsProbeConfigTable 1 }
+
+EMSProbeConfigEntry ::=
+ SEQUENCE {
+ emsProbeConfigProbeIndex INTEGER,
+ emsProbeConfigProbeName DisplayString,
+ emsProbeConfigProbeHighTempThresh INTEGER,
+ emsProbeConfigProbeLowTempThresh INTEGER,
+ emsProbeConfigProbeHighHumidityThresh INTEGER,
+ emsProbeConfigProbeLowHumidityThresh INTEGER,
+ emsProbeConfigProbeMaxTempThresh INTEGER,
+ emsProbeConfigProbeMinTempThresh INTEGER,
+ emsProbeConfigProbeDeltaTemp INTEGER,
+ emsProbeConfigProbeMaxHumidityThresh INTEGER,
+ emsProbeConfigProbeMinHumidityThresh INTEGER,
+ emsProbeConfigProbeDeltaHumidity INTEGER,
+ emsProbeConfigProbeSTIncTempVariance INTEGER,
+ emsProbeConfigProbeSTIncTempTime INTEGER,
+ emsProbeConfigProbeSTDecTempVariance INTEGER,
+ emsProbeConfigProbeSTDecTempTime INTEGER,
+ emsProbeConfigProbeLTIncTempVariance INTEGER,
+ emsProbeConfigProbeLTIncTempTime INTEGER,
+ emsProbeConfigProbeLTDecTempVariance INTEGER,
+ emsProbeConfigProbeLTDecTempTime INTEGER,
+ emsProbeConfigProbeMaxVoltThresh INTEGER,
+ emsProbeConfigProbeMinVoltThresh INTEGER
+ }
+
+emsProbeConfigProbeIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the probe entry."
+ ::= { emsProbeConfigEntry 1 }
+
+emsProbeConfigProbeName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the probe."
+ ::= { emsProbeConfigEntry 2 }
+
+emsProbeConfigProbeHighTempThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Probe high temperature threshold.
+
+ Values are represented in whole number degrees.
+ Units are displayed in the scale shown in
+ the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
+ ::= { emsProbeConfigEntry 3 }
+
+emsProbeConfigProbeLowTempThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Probe low temperature threshold.
+
+ Values are represented in whole number degrees.
+ Units are displayed in the scale shown in
+ the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
+ ::= { emsProbeConfigEntry 4 }
+
+emsProbeConfigProbeHighHumidityThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Probe high humidity threshold.
+
+ Values are represented in whole number percentage."
+ ::= { emsProbeConfigEntry 5 }
+
+emsProbeConfigProbeLowHumidityThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Probe low humidity threshold.
+
+ Values are represented in whole number percentage."
+ ::= { emsProbeConfigEntry 6 }
+
+emsProbeConfigProbeMaxTempThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Probe maximum temperature threshold.
+
+ Values are represented in whole number degrees.
+ Units are displayed in the scale shown in
+ the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
+ ::= { emsProbeConfigEntry 7 }
+
+emsProbeConfigProbeMinTempThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Probe minimum temperature threshold.
+
+ Values are represented in whole number degrees.
+ Units are displayed in the scale shown in
+ the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
+ ::= { emsProbeConfigEntry 8 }
+
+emsProbeConfigProbeDeltaTemp OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Probe delta temperature.
+
+ Values are represented in whole number degrees.
+ Units are displayed in the scale shown in
+ the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
+ ::= { emsProbeConfigEntry 9 }
+
+emsProbeConfigProbeMaxHumidityThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Probe maximum humidity threshold.
+
+ Values are represented in whole number percentage."
+ ::= { emsProbeConfigEntry 10 }
+
+emsProbeConfigProbeMinHumidityThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Probe minimum humidity threshold.
+
+ Values are represented in whole number percentage."
+ ::= { emsProbeConfigEntry 11 }
+
+emsProbeConfigProbeDeltaHumidity OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Probe delta humidity.
+
+ Values are represented in whole number percentage."
+ ::= { emsProbeConfigEntry 12 }
+
+emsProbeConfigProbeSTIncTempVariance OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Probe short-term increasing temperature variance used for rate of change alarms.
+
+ Values are represented in whole number degrees.
+ Units are displayed in the scale shown in
+ the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
+ ::= { emsProbeConfigEntry 13 }
+
+emsProbeConfigProbeSTIncTempTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Probe short-term increasing temperature time used for rate of change alarms.
+
+ Values are represented in whole number minutes."
+ ::= { emsProbeConfigEntry 14 }
+
+emsProbeConfigProbeSTDecTempVariance OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Probe short-term decreasing temperature variance used for rate of change alarms.
+
+ Values are represented in whole number degrees.
+ Units are displayed in the scale shown in
+ the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
+ ::= { emsProbeConfigEntry 15 }
+
+emsProbeConfigProbeSTDecTempTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Probe short-term decreasing temperature time used for rate of change alarms.
+
+ Values are represented in whole number minutes."
+ ::= { emsProbeConfigEntry 16 }
+
+emsProbeConfigProbeLTIncTempVariance OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Probe long-term increasing temperature variance used for rate of change alarms.
+
+ Values are represented in whole number degrees.
+ Units are displayed in the scale shown in
+ the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
+ ::= { emsProbeConfigEntry 17 }
+
+emsProbeConfigProbeLTIncTempTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Probe long-term increasing temperature time used for rate of change alarms.
+
+ Values are represented in whole number hours."
+ ::= { emsProbeConfigEntry 18 }
+
+emsProbeConfigProbeLTDecTempVariance OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Probe long-term decreasing temperature variance used for rate of change alarms.
+
+ Values are represented in whole number degrees.
+ Units are displayed in the scale shown in
+ the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
+ ::= { emsProbeConfigEntry 19 }
+
+emsProbeConfigProbeLTDecTempTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Probe long-term decreasing temperature time used for rate of change alarms.
+
+ Values are represented in whole number hours."
+ ::= { emsProbeConfigEntry 20 }
+
+emsProbeConfigProbeMaxVoltThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Probe maximum voltage threshold in Volts."
+ ::= { emsProbeConfigEntry 21 }
+
+emsProbeConfigProbeMinVoltThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Probe minimum voltage threshold in Volts."
+ ::= { emsProbeConfigEntry 22 }
+
+
+-- EMS INPUT CONTACT CONFIG STATUS TABLE
+
+emsInputContactConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF EMSInputContactConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for configuration of individual input contacts. The number of
+ entries is contained in the emsStatusInputContactCount OID."
+ ::= { emsInputContactConfig 1 }
+
+emsInputContactConfigEntry OBJECT-TYPE
+ SYNTAX EMSInputContactConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The input contacts to configure."
+ INDEX { emsInputContactConfigInputContactIndex }
+ ::= { emsInputContactConfigTable 1 }
+
+EMSInputContactConfigEntry ::=
+ SEQUENCE {
+ emsInputContactConfigInputContactIndex INTEGER,
+ emsInputContactConfigInputContactName DisplayString,
+ emsInputContactConfigInputContactNormalState INTEGER
+ }
+
+emsInputContactConfigInputContactIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the input contact entry."
+ ::= { emsInputContactConfigEntry 1 }
+
+emsInputContactConfigInputContactName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the input contact."
+ ::= { emsInputContactConfigEntry 2 }
+
+emsInputContactConfigInputContactNormalState OBJECT-TYPE
+ SYNTAX INTEGER {
+ normallyClosedEMS (1),
+ normallyOpenEMS (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this variable will return the normal state of the input contact. If
+ the normal state is closed, the normallyClosedEMS (1) value will be returned.
+ If the normal state is closed, the normallyOpenEMS (2) value will be
+ returned.
+
+ Setting this variable will change the normal state of the input contact"
+ ::= { emsInputContactConfigEntry 3 }
+
+-- EMS OUTPUT RELAY CONFIG STATUS TABLE
+
+emsOutputRelayConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF EMSOutputRelayConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for configuration of individual output relays. The number of
+ entries is contained in the emsStatusOutputRelayCount OID."
+ ::= { emsOutputRelayConfig 1 }
+
+emsOutputRelayConfigEntry OBJECT-TYPE
+ SYNTAX EMSOutputRelayConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The output relays to configure."
+ INDEX { emsOutputRelayConfigOutputRelayIndex }
+ ::= { emsOutputRelayConfigTable 1 }
+
+EMSOutputRelayConfigEntry ::=
+ SEQUENCE {
+ emsOutputRelayConfigOutputRelayIndex INTEGER,
+ emsOutputRelayConfigOutputRelayName DisplayString,
+ emsOutputRelayConfigOutputRelayNormalState INTEGER
+ }
+
+emsOutputRelayConfigOutputRelayIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the output relay entry."
+ ::= { emsOutputRelayConfigEntry 1 }
+
+emsOutputRelayConfigOutputRelayName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the output relay."
+ ::= { emsOutputRelayConfigEntry 2 }
+
+emsOutputRelayConfigOutputRelayNormalState OBJECT-TYPE
+ SYNTAX INTEGER {
+ normallyClosedEMS (1),
+ normallyOpenEMS (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this variable will return the normal state of the output relay. If
+ the normal state is closed, the normallyClosedEMS (1) value will be returned.
+ If the normal state is closed, the normallyOpenEMS (2) value will be
+ returned.
+
+ Setting this variable will change the normal state of the output relay"
+ ::= { emsOutputRelayConfigEntry 3 }
+
+-- EMS OUTLET CONFIG TABLE
+
+emsOutletConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF EMSOutletConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for configuration of individual outlets. The number of
+ entries is contained in the emsStatusOutletCount OID."
+ ::= { emsOutletConfig 1 }
+
+emsOutletConfigEntry OBJECT-TYPE
+ SYNTAX EMSOutletConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The outlets to configure."
+ INDEX { emsOutletConfigOutletIndex }
+ ::= { emsOutletConfigTable 1 }
+
+EMSOutletConfigEntry ::=
+ SEQUENCE {
+ emsOutletConfigOutletIndex INTEGER,
+ emsOutletConfigOutletName DisplayString,
+ emsOutletConfigOutletNormalState INTEGER
+ }
+
+emsOutletConfigOutletIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the outlet entry."
+ ::= { emsOutletConfigEntry 1 }
+
+emsOutletConfigOutletName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the outlet."
+ ::= { emsOutletConfigEntry 2 }
+
+emsOutletConfigOutletNormalState OBJECT-TYPE
+ SYNTAX INTEGER {
+ normallyOnEMS (1),
+ normallyOffEMS (2)
+ }
+
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this variable will return the normal state of the outlet. If
+ the normal state is on, the normallyOnEMS (1) value will be returned.
+ If the normal state is off, the normallyOffEMS (2) value will be
+ returned.
+
+ Setting this variable will change the normal state of the outlet"
+ ::= { emsOutletConfigEntry 3 }
+
+-- EMS SENSOR CONFIG TABLE
+
+emsSensorConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF EMSSensorConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for configuration of individual sensors. The number of
+ entries is contained in the emsStatusSensorCount OID."
+ ::= { emsSensorConfig 1 }
+
+emsSensorConfigEntry OBJECT-TYPE
+ SYNTAX EMSSensorConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The sensors to configure."
+ INDEX { emsSensorConfigSensorIndex }
+ ::= { emsSensorConfigTable 1 }
+
+EMSSensorConfigEntry ::=
+ SEQUENCE {
+ emsSensorConfigSensorIndex INTEGER,
+ emsSensorConfigSensorSystemName DisplayString,
+ emsSensorConfigSensorUserName DisplayString,
+ emsSensorConfigSensorNormalState INTEGER,
+ emsSensorConfigSensorAlarmDelay INTEGER
+ }
+
+emsSensorConfigSensorIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the sensor entry."
+ ::= { emsSensorConfigEntry 1 }
+
+emsSensorConfigSensorSystemName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The system name of the sensor. This describes the hardware system
+ intent of this sensor."
+ ::= { emsSensorConfigEntry 2 }
+
+emsSensorConfigSensorUserName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the sensor as given by the system user."
+ ::= { emsSensorConfigEntry 3 }
+
+emsSensorConfigSensorNormalState OBJECT-TYPE
+ SYNTAX INTEGER {
+ normallyClosedEMS (1),
+ normallyOpenEMS (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this variable will return the normal state of the sensor. If
+ the normal state is closed, the normallyClosedEMS (1) value will be returned.
+ If the normal state is closed, the normallyOpenEMS (2) value will be
+ returned.
+
+ Setting this variable will change the normal state of the sensor. Note:
+ Only the AUX sensor in the EMS has a configurable Normal State"
+ ::= { emsSensorConfigEntry 4 }
+
+emsSensorConfigSensorAlarmDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The delay (in seconds) after a sensor detects an alarm condition before the
+ condition is reported."
+ ::= { emsSensorConfigEntry 5 }
+
+-- EMS STATUS
+--- EMS MASTER status
+
+emsStatusEMSName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the
+ device. "
+ ::= { emsStatus 1 }
+
+emsStatusCommStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ noComm(1),
+ comm(2),
+ commLost(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The communication status between the agent
+ and the device.
+
+ noComm(1), Communication has never been established.
+ comm(2), Communication has been established.
+ commLost(3), Communication was established, but was lost."
+ ::= { emsStatus 2 }
+
+emsStatusProbeCount OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The total number of T/H probes (both local and remote) that
+ is supported by this device."
+ ::= { emsStatus 3 }
+
+emsStatusInputContactCount OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The total number of Input Contacts that
+ is supported by this device."
+ ::= { emsStatus 4 }
+
+emsStatusOutputRelayCount OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The total number of Output Relays that
+ is supported by this device."
+ ::= { emsStatus 5 }
+
+emsStatusOutletCount OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The total number of AC Outlets that
+ is supported by this device."
+ ::= { emsStatus 6 }
+
+emsStatusSensorCount OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The total number of Sensors that
+ is supported by this device."
+ ::= { emsStatus 7 }
+
+emsStatusAlinkAruDeviceCount OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The total number of remote Aru's supported by this device."
+ ::= { emsStatus 8 }
+
+emsStatusAlinkProbeDeviceCount OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The total number of remote T/H probes supported by this device."
+ ::= { emsStatus 9 }
+
+emsStatusAlarmDeviceCount OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of alarm devices supported by this device."
+ ::= { emsStatus 10 }
+
+emsStatusSysTempUnits OBJECT-TYPE
+ SYNTAX INTEGER {
+ celsius(1),
+ fahrenheit(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature scale used to display the temperature
+ in the system, Celsius(1) or Fahrenheit(2).
+ This setting is based on the system preferences
+ configuration in the agent."
+ ::= { emsStatus 11 }
+
+emsStatusCheckLogLight OBJECT-TYPE
+ SYNTAX INTEGER {
+ lightOff (1),
+ lightOn (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the check-log light on the device.
+ For the EMU2, this will always indicate lightOff(1).
+
+ lightOff (1) indicates the light is off (no new log entries).
+ lightOn (2) indicates the light is on (new log entries present)."
+
+ ::= { emsStatus 12 }
+
+emsStatusHardwareStatus OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the EMS hardware. This integer should be interpreted
+ as a bit map, with each bit representing the presence or absence of
+ a specific hardware error condition.
+
+ 0 indicates there are no error conditions detected in the EMS hardware.
+ 1 indicates a Current Limit error condition related to the Alink port.
+ 2 indicates incorrect hardware is plugged into an EMS port.
+ 3 indicates that both of these error conditions are present."
+
+ ::= { emsStatus 13 }
+
+-- EMS PROBE STATUS TABLE
+
+emsProbeStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF EMSProbeStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for access of individual probes. The number of
+ entries is contained in the emsStatusProbeCount OID."
+ ::= { emsProbeStatus 1 }
+
+emsProbeStatusEntry OBJECT-TYPE
+ SYNTAX EMSProbeStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The probes to access."
+ INDEX { emsProbeStatusProbeIndex }
+ ::= { emsProbeStatusTable 1 }
+
+EMSProbeStatusEntry ::=
+ SEQUENCE {
+ emsProbeStatusProbeIndex INTEGER,
+ emsProbeStatusProbeName DisplayString,
+ emsProbeStatusProbeTemperature INTEGER,
+ emsProbeStatusProbeHighTempThresh INTEGER,
+ emsProbeStatusProbeLowTempThresh INTEGER,
+ emsProbeStatusProbeHumidity INTEGER,
+ emsProbeStatusProbeHighHumidityThresh INTEGER,
+ emsProbeStatusProbeLowHumidityThresh INTEGER,
+ emsProbeStatusProbeSerialNumber DisplayString,
+ emsProbeStatusProbeCommStatus INTEGER,
+ emsProbeStatusProbeAlarmStatus INTEGER,
+ emsProbeStatusProbeMaxTempThresh INTEGER,
+ emsProbeStatusProbeMinTempThresh INTEGER,
+ emsProbeStatusProbeMaxHumidityThresh INTEGER,
+ emsProbeStatusProbeMinHumidityThresh INTEGER,
+ emsProbeStatusProbeVoltage INTEGER,
+ emsProbeStatusProbeMaxVoltThresh INTEGER,
+ emsProbeStatusProbeMinVoltThresh INTEGER
+
+ }
+
+emsProbeStatusProbeIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the probe entry."
+ ::= { emsProbeStatusEntry 1 }
+
+emsProbeStatusProbeName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the probe."
+ ::= { emsProbeStatusEntry 2 }
+
+emsProbeStatusProbeTemperature OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Probe temperature reading.
+
+ Values are represented in whole number degrees.
+ Units are displayed in the scale shown in
+ the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
+ ::= { emsProbeStatusEntry 3 }
+
+emsProbeStatusProbeHighTempThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Probe high temperature threshold.
+
+ Values are represented in whole number degrees.
+ Units are displayed in the scale shown in
+ the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
+ ::= { emsProbeStatusEntry 4 }
+
+emsProbeStatusProbeLowTempThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Probe low temperature threshold.
+
+ Values are represented in whole number degrees.
+ Units are displayed in the scale shown in
+ the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
+ ::= { emsProbeStatusEntry 5 }
+
+emsProbeStatusProbeHumidity OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Probe humidity reading.
+
+ Values are represented in whole number percentage."
+ ::= { emsProbeStatusEntry 6 }
+
+emsProbeStatusProbeHighHumidityThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Probe high humidity threshold.
+
+ Values are represented in whole number percentage."
+ ::= { emsProbeStatusEntry 7 }
+
+emsProbeStatusProbeLowHumidityThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Probe low humidity threshold.
+
+ Values are represented in whole number percentage."
+ ::= { emsProbeStatusEntry 8 }
+
+emsProbeStatusProbeSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A label indicating the type (Local[L] or Remote[R]) and Number
+ of the probe. For example, the first local probe would be L1 and
+ the third remote probe would be R3."
+ ::= { emsProbeStatusEntry 9 }
+
+emsProbeStatusProbeCommStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ commsNeverDiscovered(1),
+ commsEstablished(2),
+ commsLost(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ " The state of communications to the probe.
+ commNeverDiscovered(1) indicates there has never been communications with this device.
+ commsEstablished(2) indicates communication is normal and active with this device.
+ commsLost(3) indicates communication had been established, but is no longer."
+ ::= { emsProbeStatusEntry 10 }
+
+emsProbeStatusProbeAlarmStatus OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The alarm status of the probe. This integer should be interpreted
+ as a bit map, with each bit representing the presence or absence of
+ the specific alarm conditions listed below. The bit will be '1' if
+ the condition is present, and '0' if the condition is not present.
+
+ Bit Hex. Value Description
+ 1 0x0001 Maximum temperature exceeded.
+ 2 0x0002 High temperature exceeded.
+ 3 0x0004 Low temperature exceeded.
+ 4 0x0008 Minimum temperature exceeded.
+ 5 0x0010 Short-term increasing temperature rate exceeded.
+ 6 0x0020 Short-term decreasing temperature rate exceeded.
+ 7 0x0040 Long-term increasing temperature rate exceeded.
+ 8 0x0080 Long-term decreasing temperature rate exceeded.
+ 9 0x0100 Maximum humidity exceeded.
+ 10 0x0200 High humidity exceeded.
+ 11 0x0400 Low humidity exceeded.
+ 12 0x0800 Minimum humidity exceeded.
+ 13 0x1000 Maximum voltage exceeded.
+ 14 0x2000 Minimum voltage exceeded."
+
+ ::= { emsProbeStatusEntry 11 }
+
+emsProbeStatusProbeMaxTempThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Probe maximum temperature threshold.
+
+ Values are represented in whole number degrees.
+ Units are displayed in the scale shown in
+ the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
+ ::= { emsProbeStatusEntry 12 }
+
+emsProbeStatusProbeMinTempThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Probe minimum temperature threshold.
+
+ Values are represented in whole number degrees.
+ Units are displayed in the scale shown in
+ the emsStatusSysTempUnits OID (Celsius or Fahrenheit)."
+ ::= { emsProbeStatusEntry 13 }
+
+emsProbeStatusProbeMaxHumidityThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Probe maximum humidity threshold.
+
+ Values are represented in whole number percentage."
+ ::= { emsProbeStatusEntry 14 }
+
+emsProbeStatusProbeMinHumidityThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Probe minimum humidity threshold.
+
+ Values are represented in whole number percentage."
+ ::= { emsProbeStatusEntry 15 }
+
+emsProbeStatusProbeVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Probe voltage reading.
+
+ Values are displayed in tenths of Volts DC."
+ ::= { emsProbeStatusEntry 16 }
+
+emsProbeStatusProbeMaxVoltThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Probe maximum voltage threshold in Volts."
+ ::= { emsProbeStatusEntry 17 }
+
+emsProbeStatusProbeMinVoltThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Probe minimum voltage threshold in Volts."
+ ::= { emsProbeStatusEntry 18 }
+
+-- EMS INPUT CONTACT STATUS TABLE
+
+emsInputContactStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF EMSInputContactStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for access of individual input contacts. The number of
+ entries is contained in the emsStatusInputContactCount OID."
+ ::= { emsInputContactStatus 1 }
+
+emsInputContactStatusEntry OBJECT-TYPE
+ SYNTAX EMSInputContactStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The input contacts to access."
+ INDEX { emsInputContactStatusInputContactIndex }
+ ::= { emsInputContactStatusTable 1 }
+
+EMSInputContactStatusEntry ::=
+ SEQUENCE {
+ emsInputContactStatusInputContactIndex INTEGER,
+ emsInputContactStatusInputContactName DisplayString,
+ emsInputContactStatusInputContactState INTEGER,
+ emsInputContactStatusInputContactNormalState INTEGER
+ }
+
+emsInputContactStatusInputContactIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the input contact entry."
+ ::= { emsInputContactStatusEntry 1 }
+
+emsInputContactStatusInputContactName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the input contact."
+ ::= { emsInputContactStatusEntry 2 }
+
+emsInputContactStatusInputContactState OBJECT-TYPE
+ SYNTAX INTEGER {
+ contactClosedEMS (1),
+ contactOpenEMS (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this variable will return the state of the input contact. If
+ the input contact is closed, the contactClosedEMS (1) value will be returned.
+ If the input contact state is open, the contactOpenEMS (2) value will be
+ returned. "
+
+ ::= { emsInputContactStatusEntry 3 }
+
+emsInputContactStatusInputContactNormalState OBJECT-TYPE
+ SYNTAX INTEGER {
+ normallyClosedEMS (1),
+ normallyOpenEMS (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this variable will return the normal state of the input contact. If
+ the normal state is closed, the normallyClosedEMS (1) value will be returned.
+ If the normal state is open, the normallyOpenEMS (2) value will be
+ returned. "
+
+ ::= { emsInputContactStatusEntry 4 }
+
+
+-- EMS OUTPUT RELAY STATUS TABLE
+
+emsOutputRelayStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF EMSOutputRelayStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for access of individual output relays. The number of
+ entries is contained in the emsStatusOutputRelayCount OID."
+ ::= { emsOutputRelayStatus 1 }
+
+emsOutputRelayStatusEntry OBJECT-TYPE
+ SYNTAX EMSOutputRelayStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The output relays to access."
+ INDEX { emsOutputRelayStatusOutputRelayIndex }
+ ::= { emsOutputRelayStatusTable 1 }
+
+EMSOutputRelayStatusEntry ::=
+ SEQUENCE {
+ emsOutputRelayStatusOutputRelayIndex INTEGER,
+ emsOutputRelayStatusOutputRelayName DisplayString,
+ emsOutputRelayStatusOutputRelayState INTEGER,
+ emsOutputRelayStatusOutputRelayNormalState INTEGER
+ }
+
+emsOutputRelayStatusOutputRelayIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the output relay entry."
+ ::= { emsOutputRelayStatusEntry 1 }
+
+emsOutputRelayStatusOutputRelayName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the output relay."
+ ::= { emsOutputRelayStatusEntry 2 }
+
+emsOutputRelayStatusOutputRelayState OBJECT-TYPE
+ SYNTAX INTEGER {
+ relayClosedEMS (1),
+ relayOpenEMS (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this variable will return the state of the output relay. If
+ the output relay is closed, the relayClosedEMS (1) value will be returned.
+ If the output relay is open, the relayOpenEMS (2) value will be
+ returned. "
+
+ ::= { emsOutputRelayStatusEntry 3 }
+
+emsOutputRelayStatusOutputRelayNormalState OBJECT-TYPE
+ SYNTAX INTEGER {
+ normallyClosedEMS (1),
+ normallyOpenEMS (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this variable will return the normal state of the output relay. If
+ the normal state is closed, the normallyClosedEMS (1) value will be returned.
+ If the normal state is open, the normallyOpenEMS (2) value will be
+ returned. "
+
+ ::= { emsOutputRelayStatusEntry 4 }
+
+-- EMS OUTLET STATUS TABLE
+
+emsOutletStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF EMSOutletStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for access of individual outlets. The number of
+ entries is contained in the emsStatusOutletCount OID."
+ ::= { emsOutletStatus 1 }
+
+emsOutletStatusEntry OBJECT-TYPE
+ SYNTAX EMSOutletStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The outlets to access."
+ INDEX { emsOutletStatusOutletIndex }
+ ::= { emsOutletStatusTable 1 }
+
+EMSOutletStatusEntry ::=
+ SEQUENCE {
+ emsOutletStatusOutletIndex INTEGER,
+ emsOutletStatusOutletName DisplayString,
+ emsOutletStatusOutletState INTEGER,
+ emsOutletStatusOutletNormalState INTEGER
+ }
+
+emsOutletStatusOutletIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the outlet entry."
+ ::= { emsOutletStatusEntry 1 }
+
+emsOutletStatusOutletName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the outlet."
+ ::= { emsOutletStatusEntry 2 }
+
+emsOutletStatusOutletState OBJECT-TYPE
+ SYNTAX INTEGER {
+ outletOnEMS (1),
+ outletOffEMS (2)
+ }
+
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this variable will return the state of the outlet. If
+ the outlet is on, the outletOnEMS (1) value will be returned.
+ If the outlet is off, the outletOffEMS (2) value will be
+ returned. "
+
+ ::= { emsOutletStatusEntry 3 }
+
+emsOutletStatusOutletNormalState OBJECT-TYPE
+ SYNTAX INTEGER {
+ normallyOnEMS (1),
+ normallyOffEMS (2)
+ }
+
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this variable will return the normal state of the outlet. If
+ the normal state is on, the normallyOnEMS (1) value will be returned.
+ If the normal state is off, the normallyOffEMS (2) value will be
+ returned. "
+
+ ::= { emsOutletStatusEntry 4 }
+
+-- EMS ALARM DEVICE STATUS TABLE
+
+emsAlarmDeviceStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF EMSAlarmDeviceStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for access of individual alarm devices. The number of
+ entries is contained in the emsStatusAlarmDeviceCount OID."
+ ::= { emsAlarmDeviceStatus 1 }
+
+emsAlarmDeviceStatusEntry OBJECT-TYPE
+ SYNTAX EMSAlarmDeviceStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The alarm devices to access."
+ INDEX { emsAlarmDeviceStatusDeviceIndex }
+ ::= { emsAlarmDeviceStatusTable 1 }
+
+EMSAlarmDeviceStatusEntry ::=
+ SEQUENCE {
+ emsAlarmDeviceStatusDeviceIndex INTEGER,
+ emsAlarmDeviceStatusDeviceName DisplayString,
+ emsAlarmDeviceStatusDeviceState INTEGER
+ }
+
+emsAlarmDeviceStatusDeviceIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the alarm device entry."
+ ::= { emsAlarmDeviceStatusEntry 1 }
+
+emsAlarmDeviceStatusDeviceName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the alarm device.
+ This OID is provided for informational purposes only."
+ ::= { emsAlarmDeviceStatusEntry 2 }
+
+emsAlarmDeviceStatusDeviceState OBJECT-TYPE
+ SYNTAX INTEGER {
+ alarmDeviceOnEMS (1),
+ alarmDeviceOffEMS (2),
+ alarmDeviceNotInstalledEMS (3)
+ }
+
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this variable will return the device state. If
+ the device is active, the alarmDeviceOnEMS (1) value will be returned.
+ If the device is inactive, the alarmDeviceOffEMS (2) value will be
+ returned. If the device is not installed, the
+ alarmDeviceNotInstalledEMS (3) value will be returned."
+
+ ::= { emsAlarmDeviceStatusEntry 3 }
+
+
+-- EMS SENSOR STATUS TABLE
+
+emsSensorStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF EMSSensorStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for access of individual sensors. The number of
+ entries is contained in the emsStatusSensorCount OID."
+ ::= { emsSensorStatus 1 }
+
+emsSensorStatusEntry OBJECT-TYPE
+ SYNTAX EMSSensorStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The sensors to access."
+ INDEX { emsSensorStatusSensorIndex }
+ ::= { emsSensorStatusTable 1 }
+
+EMSSensorStatusEntry ::=
+ SEQUENCE {
+ emsSensorStatusSensorIndex INTEGER,
+ emsSensorStatusSensorSystemName DisplayString,
+ emsSensorStatusSensorName DisplayString,
+ emsSensorStatusSensorState INTEGER,
+ emsSensorStatusSensorNormalState INTEGER,
+ emsSensorStatusSensorAlarmDelay INTEGER
+ }
+
+emsSensorStatusSensorIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the sensor entry."
+ ::= { emsSensorStatusEntry 1 }
+
+emsSensorStatusSensorSystemName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The system name of the sensor. This describes the hardware system
+ intent of this sensor."
+ ::= { emsSensorStatusEntry 2 }
+
+emsSensorStatusSensorName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the sensor as given by the system user."
+ ::= { emsSensorStatusEntry 3 }
+
+emsSensorStatusSensorState OBJECT-TYPE
+ SYNTAX INTEGER {
+ sensorFaultedEMS (1),
+ sensorOKEMS (2),
+ sensorNotInstalledEMS (3)
+ }
+
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this variable will return the sensor state. If the sensor is faulted,
+ the sensorFaultedEMS (1) value will be returned.
+ If the sensor is not faulted, the sensorOKEMS (2) value will be
+ returned. If the sensor is not installed, the sensorNotInstalledEMS (3)
+ value will be returned."
+ ::= { emsSensorStatusEntry 4 }
+
+emsSensorStatusSensorNormalState OBJECT-TYPE
+ SYNTAX INTEGER {
+ normallyClosedEMS (1),
+ normallyOpenEMS (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Getting this variable will return the normal state of the sensor. If
+ the normal state is closed, the normallyClosedEMS (1) value will be returned.
+ If the normal state is closed, the normallyOpenEMS (2) value will be
+ returned."
+ ::= { emsSensorStatusEntry 5 }
+
+emsSensorStatusSensorAlarmDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The delay (in seconds) after a sensor detects an alarm condition before the
+ condition is reported."
+ ::= { emsSensorStatusEntry 6 }
+
+-- EMS INPUT STATE SENSOR CONFIG TABLE
+emsSmokeSensorConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF EmsSmokeSensorConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+
+ "Allows for the configuration of individual sensors."
+ ::= { emsInputStateSensorConfig 1 }
+
+emsSmokeSensorConfigEntry OBJECT-TYPE
+ SYNTAX EmsSmokeSensorConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The sensors to configure."
+ INDEX { emsSmokeSensorConfigSensorIndex }
+ ::= { emsSmokeSensorConfigTable 1 }
+
+EmsSmokeSensorConfigEntry ::=
+ SEQUENCE {
+ emsSmokeSensorConfigSensorIndex INTEGER,
+ emsSmokeSensorConfigSensorName DisplayString,
+ emsSmokeSensorConfigSensorLocation DisplayString,
+ emsSmokeSensorConfigSensorSeverity INTEGER
+ }
+
+emsSmokeSensorConfigSensorIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the sensor entry."
+ ::= { emsSmokeSensorConfigEntry 1 }
+
+emsSmokeSensorConfigSensorName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The user defined name of the smoke sensor."
+ ::= { emsSmokeSensorConfigEntry 2 }
+
+emsSmokeSensorConfigSensorLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The user defined location of the smoke sensor."
+ ::= { emsSmokeSensorConfigEntry 3 }
+
+emsSmokeSensorConfigSensorSeverity OBJECT-TYPE
+ SYNTAX INTEGER {
+ critical(1),
+ warning(2),
+ informational(3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The severity of the alarm that will be triggered when
+ the smoke sensor is activated. The alarms can be
+ critical(1), warning(2) or informational(3)."
+ ::= { emsSmokeSensorConfigEntry 4 }
+
+emsVibrationSensorConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF EmsVibrationSensorConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for the configuration of individual sensors."
+ ::= { emsInputStateSensorConfig 2 }
+
+emsVibrationSensorConfigEntry OBJECT-TYPE
+ SYNTAX EmsVibrationSensorConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The sensors to configure."
+ INDEX { emsVibrationSensorConfigSensorIndex }
+ ::= { emsVibrationSensorConfigTable 1 }
+
+EmsVibrationSensorConfigEntry ::=
+ SEQUENCE {
+ emsVibrationSensorConfigSensorIndex INTEGER,
+ emsVibrationSensorConfigSensorName DisplayString,
+ emsVibrationSensorConfigSensorLocation DisplayString,
+ emsVibrationSensorConfigSensorSeverity INTEGER
+ }
+
+emsVibrationSensorConfigSensorIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the sensor entry."
+ ::= { emsVibrationSensorConfigEntry 1 }
+
+emsVibrationSensorConfigSensorName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The user defined name of the vibration sensor."
+ ::= { emsVibrationSensorConfigEntry 2 }
+
+emsVibrationSensorConfigSensorLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The user defined location of the vibration sensor."
+ ::= { emsVibrationSensorConfigEntry 3 }
+
+emsVibrationSensorConfigSensorSeverity OBJECT-TYPE
+ SYNTAX INTEGER {
+ critical(1),
+ warning(2),
+ informational(3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The severity of the alarm that will be triggered when
+ the vibration sensor is activated. The alarms can be
+ critical(1), warning(2) or informational(3)."
+ ::= { emsVibrationSensorConfigEntry 4 }
+
+emsFluidSensorConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF EmsFluidSensorConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for the configuration of individual sensors."
+ ::= { emsInputStateSensorConfig 3 }
+
+emsFluidSensorConfigEntry OBJECT-TYPE
+ SYNTAX EmsFluidSensorConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The sensors to configure."
+ INDEX { emsFluidSensorConfigSensorIndex }
+ ::= { emsFluidSensorConfigTable 1 }
+
+EmsFluidSensorConfigEntry ::=
+ SEQUENCE {
+ emsFluidSensorConfigSensorIndex INTEGER,
+ emsFluidSensorConfigSensorName DisplayString,
+ emsFluidSensorConfigSensorLocation DisplayString,
+ emsFluidSensorConfigSensorSeverity INTEGER
+ }
+
+emsFluidSensorConfigSensorIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the sensor entry."
+ ::= { emsFluidSensorConfigEntry 1 }
+
+emsFluidSensorConfigSensorName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The user defined name of the fluid sensor."
+ ::= { emsFluidSensorConfigEntry 2 }
+
+emsFluidSensorConfigSensorLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The user defined location of the fluid sensor."
+ ::= { emsFluidSensorConfigEntry 3 }
+
+
+emsFluidSensorConfigSensorSeverity OBJECT-TYPE
+ SYNTAX INTEGER {
+ critical(1),
+ warning(2),
+ informational(3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The severity of the alarm that will be triggered when
+ the fluid sensor is activated. The alarms can be
+ critical(1), warning(2) or informational(3)."
+ ::= { emsFluidSensorConfigEntry 4 }
+
+emsDoorSensorConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF EmsDoorSensorConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for the configuration of individual sensors."
+ ::= { emsInputStateSensorConfig 4 }
+
+emsDoorSensorConfigEntry OBJECT-TYPE
+ SYNTAX EmsDoorSensorConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The sensors to configure."
+ INDEX { emsDoorSensorConfigSensorIndex }
+ ::= { emsDoorSensorConfigTable 1 }
+
+EmsDoorSensorConfigEntry ::=
+ SEQUENCE {
+ emsDoorSensorConfigSensorIndex INTEGER,
+ emsDoorSensorConfigSensorName DisplayString,
+ emsDoorSensorConfigSensorLocation DisplayString,
+ emsDoorSensorConfigSensorSeverity INTEGER
+ }
+
+emsDoorSensorConfigSensorIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the sensor entry."
+ ::= { emsDoorSensorConfigEntry 1 }
+
+emsDoorSensorConfigSensorName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The user defined name of the door sensor."
+ ::= { emsDoorSensorConfigEntry 2 }
+
+emsDoorSensorConfigSensorLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The user defined location of the door sensor."
+ ::= { emsDoorSensorConfigEntry 3 }
+
+emsDoorSensorConfigSensorSeverity OBJECT-TYPE
+ SYNTAX INTEGER {
+ critical(1),
+ warning(2),
+ informational(3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The severity of the alarm that will be triggered when
+ the door sensor is activated. The alarms can be
+ critical(1), warning(2) or informational(3)."
+ ::= { emsDoorSensorConfigEntry 4 }
+
+--EMS INPUT STATE SENSOR STATUS TABLE
+
+emsSmokeSensorStatusTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the emsSmokeSensorStatusTable."
+ ::= { emsInputStateSensorStatus 1 }
+
+emsSmokeSensorStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF EmsSmokeSensorStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for the access of individual sensors."
+ ::= { emsInputStateSensorStatus 2 }
+
+emsSmokeSensorStatusEntry OBJECT-TYPE
+ SYNTAX EmsSmokeSensorStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The sensor to access."
+ INDEX { emsSmokeSensorStatusSensorIndex }
+ ::= { emsSmokeSensorStatusTable 1 }
+
+EmsSmokeSensorStatusEntry ::=
+ SEQUENCE {
+ emsSmokeSensorStatusSensorIndex INTEGER,
+ emsSmokeSensorStatusSensorName DisplayString,
+ emsSmokeSensorStatusSensorLocation DisplayString,
+ emsSmokeSensorStatusSensorState INTEGER,
+ emsSmokeSensorStatusSensorSeverity INTEGER,
+ emsSmokeSensorCommStatus INTEGER
+
+ }
+
+emsSmokeSensorStatusSensorIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the sensor entry."
+ ::= { emsSmokeSensorStatusEntry 1 }
+
+emsSmokeSensorStatusSensorName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user defined name of the smoke sensor."
+ ::= { emsSmokeSensorStatusEntry 2 }
+
+emsSmokeSensorStatusSensorLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user defined location of the smoke sensor."
+ ::= { emsSmokeSensorStatusEntry 3 }
+
+emsSmokeSensorStatusSensorState OBJECT-TYPE
+ SYNTAX INTEGER {
+ smokeDetected (1),
+ noSmoke (2),
+ unknown (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The state of the smoke sensor.
+ smokeDetected (1) indicates there is smoke.
+ noSmoke (2) indicates there is no smoke.
+ unknown (3) indicates the state is unknown."
+ ::= { emsSmokeSensorStatusEntry 4 }
+
+emsSmokeSensorStatusSensorSeverity OBJECT-TYPE
+ SYNTAX INTEGER {
+ critical(1),
+ warning(2),
+ informational(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The severity of the alarm that will be triggered when
+ the smoke sensor is activated. The alarms can be
+ critical(1), warning(2) or informational(3)."
+ ::= { emsSmokeSensorStatusEntry 5 }
+
+emsSmokeSensorCommStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ commOK(1),
+ commLost(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The communication status of the smoke sensor."
+ ::= { emsSmokeSensorStatusEntry 6 }
+
+emsVibrationSensorStatusTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the emsVibrationSensorStatusTable."
+ ::= { emsInputStateSensorStatus 3}
+
+emsVibrationSensorStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF EmsVibrationSensorStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for the access of individual sensors."
+ ::= { emsInputStateSensorStatus 4 }
+
+emsVibrationSensorStatusEntry OBJECT-TYPE
+ SYNTAX EmsVibrationSensorStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The sensor to access."
+ INDEX { emsVibrationSensorStatusSensorIndex }
+ ::= { emsVibrationSensorStatusTable 1 }
+
+EmsVibrationSensorStatusEntry ::=
+ SEQUENCE {
+ emsVibrationSensorStatusSensorIndex INTEGER,
+ emsVibrationSensorStatusSensorName DisplayString,
+ emsVibrationSensorStatusSensorLocation DisplayString,
+ emsVibrationSensorStatusSensorState INTEGER,
+ emsVibrationSensorStatusSensorSeverity INTEGER,
+ emsVibrationSensorCommStatus INTEGER
+ }
+
+emsVibrationSensorStatusSensorIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the sensor entry."
+ ::= { emsVibrationSensorStatusEntry 1 }
+
+emsVibrationSensorStatusSensorName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user defined name of the vibration sensor."
+ ::= { emsVibrationSensorStatusEntry 2 }
+
+emsVibrationSensorStatusSensorLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user defined location of the vibration sensor."
+ ::= { emsVibrationSensorStatusEntry 3 }
+
+emsVibrationSensorStatusSensorState OBJECT-TYPE
+ SYNTAX INTEGER {
+ vibrationDetected (1),
+ noVibration (2),
+ unknown (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The state of the vibration sensor.
+ vibrationDetected (1) indicates there is vibration.
+ noVibration (2) indicates there is no vibration.
+ unknown (3) indicates the state is unknown."
+ ::= { emsVibrationSensorStatusEntry 4 }
+
+emsVibrationSensorStatusSensorSeverity OBJECT-TYPE
+ SYNTAX INTEGER {
+ critical(1),
+ warning(2),
+ informational(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The severity of the alarm that will be triggered when
+ the vibration sensor is activated. The alarms can be
+ critical(1), warning(2) or informational(3)."
+ ::= { emsVibrationSensorStatusEntry 5 }
+
+emsVibrationSensorCommStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ commOK(1),
+ commLost(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The communication status of the vibration sensor."
+ ::= { emsVibrationSensorStatusEntry 6 }
+
+emsFluidSensorStatusTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the emsFluidSensorStatusTable."
+ ::= { emsInputStateSensorStatus 5}
+
+emsFluidSensorStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF EmsFluidSensorStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for the access of individual sensors."
+ ::= { emsInputStateSensorStatus 6 }
+
+emsFluidSensorStatusEntry OBJECT-TYPE
+ SYNTAX EmsFluidSensorStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The sensors to access."
+ INDEX { emsFluidSensorStatusSensorIndex }
+ ::= { emsFluidSensorStatusTable 1 }
+
+EmsFluidSensorStatusEntry ::=
+ SEQUENCE {
+ emsFluidSensorStatusSensorIndex INTEGER,
+ emsFluidSensorStatusSensorName DisplayString,
+ emsFluidSensorStatusSensorLocation DisplayString,
+ emsFluidSensorStatusSensorState INTEGER,
+ emsFluidSensorStatusSensorSeverity INTEGER,
+ emsFluidSensorCommStatus INTEGER
+ }
+
+emsFluidSensorStatusSensorIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the sensor entry."
+ ::= { emsFluidSensorStatusEntry 1 }
+
+emsFluidSensorStatusSensorName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user defined name of the fluid sensor."
+ ::= { emsFluidSensorStatusEntry 2 }
+
+emsFluidSensorStatusSensorLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user defined location of the fluid sensor."
+ ::= { emsFluidSensorStatusEntry 3 }
+
+emsFluidSensorStatusSensorState OBJECT-TYPE
+ SYNTAX INTEGER {
+ fluidDetected (1),
+ noFluid (2),
+ unknown (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The state of the fluid sensor.
+ fluidDetected (1) indicates there is fluid leak.
+ noFluid (2) indicates there is no fluid leak.
+ unknown (3) indicates the state is unknown."
+ ::= { emsFluidSensorStatusEntry 4 }
+
+emsFluidSensorStatusSensorSeverity OBJECT-TYPE
+ SYNTAX INTEGER {
+ critical(1),
+ warning(2),
+ informational(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The severity of the alarm that will be triggered when
+ the fluid sensor is activated. The alarms can be
+ critical(1), warning(2) or informational(3)."
+ ::= { emsFluidSensorStatusEntry 5 }
+
+emsFluidSensorCommStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ commOK(1),
+ commLost(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The communication status of the fluid sensor."
+ ::= { emsFluidSensorStatusEntry 6 }
+
+emsDoorSensorStatusTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the emsDoorSensorStatusTable."
+ ::= { emsInputStateSensorStatus 7}
+
+emsDoorSensorStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF EmsDoorSensorStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for the access of individual sensors."
+ ::= { emsInputStateSensorStatus 8}
+
+emsDoorSensorStatusEntry OBJECT-TYPE
+ SYNTAX EmsDoorSensorStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The sensor to access."
+ INDEX { emsDoorSensorStatusSensorIndex }
+ ::= { emsDoorSensorStatusTable 1 }
+
+EmsDoorSensorStatusEntry ::=
+ SEQUENCE {
+ emsDoorSensorStatusSensorIndex INTEGER,
+ emsDoorSensorStatusSensorName DisplayString,
+ emsDoorSensorStatusSensorLocation DisplayString,
+ emsDoorSensorStatusSensorState INTEGER,
+ emsDoorSensorStatusSensorSeverity INTEGER,
+ emsDoorSensorCommStatus INTEGER
+ }
+
+emsDoorSensorStatusSensorIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the sensor entry."
+ ::= { emsDoorSensorStatusEntry 1 }
+
+emsDoorSensorStatusSensorName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user defined name of the door sensor."
+ ::= { emsDoorSensorStatusEntry 2 }
+
+emsDoorSensorStatusSensorLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The user defined location of the door sensor."
+ ::= { emsDoorSensorStatusEntry 3 }
+
+emsDoorSensorStatusSensorState OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2),
+ unknown (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The state of the door sensor.
+ open (1) indicates door open.
+ closed (2) indicates door closed.
+ unknown (3) indicates the state is unknown."
+ ::= { emsDoorSensorStatusEntry 4 }
+
+emsDoorSensorStatusSensorSeverity OBJECT-TYPE
+ SYNTAX INTEGER {
+ critical(1),
+ warning(2),
+ informational(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The severity of the alarm that will be triggered when
+ the door sensor is activated. The alarms can be
+ critical(1), warning(2) or informational(3)."
+ ::= { emsDoorSensorStatusEntry 5 }
+
+emsDoorSensorCommStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ commOK(1),
+ commLost(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The communication status of the door sensor."
+ ::= { emsDoorSensorStatusEntry 6 }
+
+
+
+-- airFM AIR CONDITIONER IDENT
+
+airFMIdentName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the device."
+ ::= { airFMIdent 1 }
+
+airFMIdentTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the airFMIdentTable. "
+ ::= { airFMIdent 2 }
+
+airFMIdentTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AirFMIdentEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting identification information
+ from each module in the system. "
+ ::= { airFMIdent 3 }
+
+airFMIdentEntry OBJECT-TYPE
+ SYNTAX AirFMIdentEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The module to get information from."
+ INDEX { airFMIdentModuleIndex }
+ ::= { airFMIdentTable 1 }
+
+AirFMIdentEntry ::=
+ SEQUENCE {
+ airFMIdentModuleIndex INTEGER,
+ airFMIdentModuleModelNumber DisplayString,
+ airFMIdentModuleDateOfMfg DisplayString,
+ airFMIdentModuleSerialNumber DisplayString,
+ airFMIdentModuleFirmwareRev DisplayString,
+ airFMIdentModuleHardwareRev DisplayString
+ }
+
+airFMIdentModuleIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of the module information."
+ ::= { airFMIdentEntry 1 }
+
+airFMIdentModuleModelNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the
+ model number. "
+ ::= { airFMIdentEntry 2 }
+
+airFMIdentModuleDateOfMfg OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the
+ manufacture date. "
+ ::= { airFMIdentEntry 3 }
+
+airFMIdentModuleSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the
+ unit serial number. "
+ ::= { airFMIdentEntry 4 }
+
+airFMIdentModuleFirmwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the
+ firmware revision. "
+ ::= { airFMIdentEntry 5 }
+
+airFMIdentModuleHardwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the
+ hardware revision. "
+ ::= { airFMIdentEntry 6 }
+
+airFMIdentLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the
+ location of the device. "
+ ::= { airFMIdent 4 }
+
+airFMIdentContact OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the
+ person to contact regarding the device. "
+ ::= { airFMIdent 5 }
+
+
+-- airFM AIR CONDITIONER STATUS
+
+airFMStatusSystemOn OBJECT-TYPE
+ SYNTAX INTEGER {
+ statusOn (1),
+ statusOff (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The operating state of the system.
+ This OID has been deprecated in favor of
+ airFMGroupSysStatus."
+ ::= { airFMStatus 1 }
+
+airFMStatusSystemAverageRetTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The system average return air
+ temperature in tenths of degrees Celsius.
+ This OID has been deprecated in favor of
+ airFMSysAvgReturnTempC."
+ ::= { airFMStatus 2 }
+
+airFMStatusSystemAverageRetTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The system average return air
+ temperature in tenths of degrees Fahrenheit.
+ This OID has been deprecated in favor of
+ airFMSysAvgReturnTempF."
+ ::= { airFMStatus 3 }
+
+airFMStatusSystemAverageRetHum OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The system average return air
+ humidity in tenths of percent RH.
+ This OID has been deprecated in favor of
+ airFMSysAvgReturnHum."
+ ::= { airFMStatus 4 }
+
+airFMStatusSystemActionTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The system action air
+ temperature in tenths of degrees Celsius.
+ This OID has been deprecated in favor of
+ airFMSysCtrlTempC."
+ ::= { airFMStatus 5 }
+
+airFMStatusSystemActionTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The system action air
+ temperature in tenths of degrees Fahrenheit.
+ This OID has been deprecated in favor of
+ airFMSysCtrlTempF."
+ ::= { airFMStatus 6 }
+
+airFMStatusSystemActionHum OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The system action air humidity in tenths of percent RH.
+ This OID has been deprecated in favor of
+ airFMSysCtrlHum."
+ ::= { airFMStatus 7 }
+
+airFMStatusSystemRemoteHighTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The system remote high air
+ temperature in tenths of degrees Celsius.
+ This OID has been deprecated in favor of
+ airFMSysMaxRemoteTempC."
+ ::= { airFMStatus 8 }
+
+airFMStatusSystemRemoteHighTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The system remote high air
+ temperature in tenths of degrees Fahrenheit.
+ This OID has been deprecated in favor of
+ airFMSysMaxRemoteTempF."
+ ::= { airFMStatus 9 }
+
+airFMStatusSystemRemoteAvgTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The system remote average air
+ temperature in tenths of degrees Celsius.
+ This OID has been deprecated in favor of
+ airFMSysAvgRemoteTempC."
+ ::= { airFMStatus 10 }
+
+airFMStatusSystemRemoteAvgTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The system remote average air
+ temperature in tenths of degrees Fahrenheit.
+ This OID has been deprecated in favor of
+ airFMSysAvgRemoteTempF."
+ ::= { airFMStatus 11 }
+
+airFMStatusSystemRemoteAvgHum OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The system remote average air
+ humidity in tenths of percent RH.
+ This OID has been deprecated in favor of
+ airFMSysAvgRemoteHum."
+ ::= { airFMStatus 12 }
+
+airFMStatusSystemRemoteLowTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The system remote low air
+ temperature in tenths of degrees Celsius.
+ This OID has been deprecated in favor of
+ airFMSysMinRemoteTempC."
+ ::= { airFMStatus 13 }
+
+airFMStatusSystemRemoteLowTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The system remote low air
+ temperature in tenths of degrees Fahrenheit.
+ This OID has been deprecated in favor of
+ airFMSysMinRemoteTempF."
+ ::= { airFMStatus 14 }
+
+airFMStatusSystemCoolingEnabled OBJECT-TYPE
+ SYNTAX INTEGER {
+ enabledYes (1),
+ enabledNo (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The state of the system cooling
+ function enable.
+ This OID has been deprecated in favor of
+ airFMSysCoolState."
+ ::= { airFMStatus 15 }
+
+airFMStatusSystemReheatingEnabled OBJECT-TYPE
+ SYNTAX INTEGER {
+ enabledYes (1),
+ enabledNo (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The state of the system reheating
+ function enable.
+ This OID has been deprecated in favor of
+ airFMSysReheatState."
+ ::= { airFMStatus 16 }
+
+airFMStatusSystemHumidifyEnabled OBJECT-TYPE
+ SYNTAX INTEGER {
+ enabledYes (1),
+ enabledNo (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The state of the system humidify
+ function enable.
+ This OID has been deprecated in favor of
+ airFMSysHumState."
+ ::= { airFMStatus 17 }
+
+airFMStatusSystemDehumidifyEnabled OBJECT-TYPE
+ SYNTAX INTEGER {
+ enabledYes (1),
+ enabledNo (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The state of the system dehumidify
+ function enable.
+ This OID has been deprecated in favor of
+ airFMSysDehumState."
+ ::= { airFMStatus 18 }
+
+airFMStatusModuleTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the airFMStatusModuleTable."
+ ::= { airFMStatus 19 }
+
+airFMStatusModuleTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AirFMStatusModuleEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting information from each module
+ in the system."
+ ::= { airFMStatus 20 }
+
+airFMStatusModuleEntry OBJECT-TYPE
+ SYNTAX AirFMStatusModuleEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The module to get status from."
+ INDEX { airFMStatusModuleIndex }
+ ::= { airFMStatusModuleTable 1 }
+
+AirFMStatusModuleEntry ::=
+ SEQUENCE {
+ airFMStatusModuleIndex INTEGER,
+ airFMStatusModuleOutputCapacity INTEGER,
+ airFMStatusModuleSupplyTempC INTEGER,
+ airFMStatusModuleSupplyTempF INTEGER,
+ airFMStatusModuleSupplyHum INTEGER,
+ airFMStatusModuleReturnTempC INTEGER,
+ airFMStatusModuleReturnTempF INTEGER,
+ airFMStatusModuleReturnHum INTEGER
+ }
+
+airFMStatusModuleIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of the module information."
+ ::= { airFMStatusModuleEntry 1 }
+
+airFMStatusModuleOutputCapacity OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The module output capacity in kilowatts.
+ This OID has been deprecated in favor of
+ airFMModOutputCapacity."
+ ::= { airFMStatusModuleEntry 2 }
+
+airFMStatusModuleSupplyTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The module supply air temperature in
+ tenths of degrees Celsius.
+ This OID has been deprecated in favor of
+ airFMModSupplyTempC."
+ ::= { airFMStatusModuleEntry 3 }
+
+airFMStatusModuleSupplyTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The module supply air temperature in
+ tenths of degrees Fahrenheit.
+ This OID has been deprecated in favor of
+ airFMModSupplyTempF."
+ ::= { airFMStatusModuleEntry 4 }
+
+airFMStatusModuleSupplyHum OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The module supply air humidity in tenths of percent RH.
+ This OID has been deprecated in favor of
+ airFMModSupplyHum."
+ ::= { airFMStatusModuleEntry 5 }
+
+airFMStatusModuleReturnTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The module return air temperature in
+ tenths of degrees Celsius.
+ This OID has been deprecated in favor of
+ airFMModReturnTempC."
+ ::= { airFMStatusModuleEntry 6 }
+
+airFMStatusModuleReturnTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The module return air temperature in
+ tenths of degrees Fahrenheit.
+ This OID has been deprecated in favor of
+ airFMModReturnTempF."
+ ::= { airFMStatusModuleEntry 7 }
+
+airFMStatusModuleReturnHum OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The module return air humidity in tenths of percent RH.
+ This OID has been deprecated in favor of
+ airFMModReturnHum."
+ ::= { airFMStatusModuleEntry 8 }
+
+-- airFM AIR CONDITIONER GROUP DATA
+
+airFMGroupSysStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ statusOnLine (1),
+ statusIdle (2),
+ statusLoadShare (3),
+ statusOffLine (4),
+ statusFailed (5),
+ statusDisabled (6),
+ statusUndefined (7)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of this system within the group."
+ ::= { airFMGroup 1 }
+
+airFMGroupSysRuntime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of hours the system has been running."
+ ::= { airFMGroup 2 }
+
+airFMGroupSysRole OBJECT-TYPE
+ SYNTAX INTEGER {
+ rolePrimary (1),
+ roleBackup (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The role of this system within the group."
+ ::= { airFMGroup 3 }
+
+-- airFM Group System Roles
+airFMGroupSysRolesTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the airFMGroupSysRolesTable. "
+ ::= { airFMGroupSysRoles 1 }
+
+airFMGroupSysRolesTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AirFMGroupSysRolesEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting information from each system
+ in the group. "
+ ::= { airFMGroupSysRoles 2 }
+
+airFMGroupSysRolesEntry OBJECT-TYPE
+ SYNTAX AirFMGroupSysRolesEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The system to get status from."
+ INDEX { airFMGroupSysIndex }
+ ::= { airFMGroupSysRolesTable 1 }
+
+AirFMGroupSysRolesEntry ::=
+ SEQUENCE {
+ airFMGroupSysIndex INTEGER,
+ airFMGroupSysRoleStatus INTEGER,
+ airFMGroupSysPresentRole INTEGER,
+ airFMGroupSysManualRoleSetting INTEGER,
+ airFMGroupSysRunHours INTEGER,
+ airFMGroupSysComm INTEGER,
+ airFMGroupSysIPAddress IpAddress
+ }
+
+airFMGroupSysIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of the system information."
+ ::= { airFMGroupSysRolesEntry 1 }
+
+airFMGroupSysRoleStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ reserved1 (1),
+ reserved2 (2),
+ onLine (3),
+ idle (4),
+ loadShare (5),
+ failed (6),
+ offLine (7)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The present mode of the System."
+ ::= { airFMGroupSysRolesEntry 2 }
+
+airFMGroupSysPresentRole OBJECT-TYPE
+ SYNTAX INTEGER {
+ primary (1),
+ backup (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The present role of the System in a Group."
+ ::= { airFMGroupSysRolesEntry 3 }
+
+airFMGroupSysManualRoleSetting OBJECT-TYPE
+ SYNTAX INTEGER {
+ primary (1),
+ backup (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The manual role setting of the System in a Group.
+ Only applies if Role Assignment Method is set
+ to static (Manually Assigned Roles)."
+ ::= { airFMGroupSysRolesEntry 4 }
+
+airFMGroupSysRunHours OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The total number of hours the System has been
+ contributing to environmental control."
+ ::= { airFMGroupSysRolesEntry 5 }
+
+airFMGroupSysComm OBJECT-TYPE
+ SYNTAX INTEGER {
+ commLost (1),
+ commEstablished (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates whether a system is communicating with the
+ other Systems in the Group."
+ ::= { airFMGroupSysRolesEntry 6 }
+
+airFMGroupSysIPAddress OBJECT-TYPE
+ SYNTAX IpAddress
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The IP Address of the System."
+ ::= { airFMGroupSysRolesEntry 7 }
+
+airFMGroupSysRoleAssignment OBJECT-TYPE
+ SYNTAX INTEGER {
+ staticManual (1),
+ dynamicAutomatic (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The method used to assign roles (i.e. Primary, Backup)
+ to the Systems in a Group.
+
+ staticManual: Manually assign Primary or Backup to
+ regulate run hours across the Group.
+ dynamicAutomatic: User indicates the number of Systems
+ that will be assigned a primary role in this Group."
+ ::= { airFMGroupSysRoles 3 }
+
+airFMGroupAutoRoleNumPrimary OBJECT-TYPE
+ SYNTAX INTEGER {
+ one (1),
+ two (2),
+ three (3),
+ four (4)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The number of Systems assigned the 'primary' role in
+ this Group. Only applies if Role Assignment Method
+ is set to dynamic (Automatic Run Hour Balancing)."
+ ::= { airFMGroupSysRoles 4 }
+
+-- airFM Group Config
+airFMGroupCfgName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the group name."
+ ::= { airFMGroupCfg 1 }
+
+airFMGroupCfgNumSystems OBJECT-TYPE
+ SYNTAX INTEGER {
+ one (1),
+ two (2),
+ three (3),
+ four (4)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The number of Systems in this Group."
+ ::= { airFMGroupCfg 2 }
+
+airFMGroupCfgIdleBlower OBJECT-TYPE
+ SYNTAX INTEGER {
+ off (1),
+ minimumSpeed (2),
+ normalSpeed (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Blower behavior for backup Systems and Systems that
+ have entered a failure mode."
+ ::= { airFMGroupCfg 3 }
+
+airFMGroupCfgShutdownSmoke OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "If enabled, all Systems in the Group will shut down
+ if smoke is detected."
+ ::= { airFMGroupCfg 4 }
+
+airFMGroupCfgShutdownFire OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "If enabled, all Systems in the Group will shut down
+ if fire is detected."
+ ::= { airFMGroupCfg 5 }
+
+airFMGroupCfgFailoverCommLoss OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Failover on Comm Loss enables an available backup
+ System to run in place of a System that has lost
+ communication with the Group."
+ ::= { airFMGroupCfg 6 }
+
+airFMGroupCfgDmdFightStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ off (1),
+ on (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Demand Fighting and Setpoint Sharing are
+ automatically enabled when a System is responding to
+ a Load Sharing Request."
+ ::= { airFMGroupCfg 7 }
+
+airFMGroupCfgDmdFightSetting OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Demand Fighting prevents a System from engaging
+ reheat in a Group where any System is cooling."
+ ::= { airFMGroupCfg 8 }
+
+airFMGroupCfgSetpointShareStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ off (1),
+ on (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Demand Fighting and Setpoint Sharing are
+ automatically enabled when a System is responding to
+ Load Sharing Request."
+ ::= { airFMGroupCfg 9 }
+
+airFMGroupCfgSetpointShareSetting OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "All Systems in the Group use the same setpoints."
+ ::= { airFMGroupCfg 10 }
+
+airFMGroupCfgResetFieldServiceDefaults OBJECT-TYPE
+ SYNTAX INTEGER {
+ noOperation (1),
+ reset (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to reset(2) will reset all Group
+ parameters, which can only be edited by a field
+ service engineer, to their factory default values.
+
+ Getting this OID will do nothing and return the
+ noOperation(1) value."
+ ::= { airFMGroupCfg 11 }
+
+-- airFM Group Load Sharing
+airFMGroupLoadShareCoolRequests OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Systems that are cooling may request assistance from
+ other Systems in the Group."
+ ::= { airFMGroupLoadShare 1 }
+
+airFMGroupLoadShareCoolThreshC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Temperature threshold at which a System will generate
+ a load sharing request for cooling. Measured in
+ tenths of degrees Celsius."
+ ::= { airFMGroupLoadShare 2 }
+
+airFMGroupLoadShareCoolThreshF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Temperature threshold at which a System will generate
+ a load sharing request for cooling. Measured in
+ tenths of degrees Fahrenheit."
+ ::= { airFMGroupLoadShare 3 }
+
+airFMGroupLoadShareReheatRequests OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Systems that are reheating may request assistance
+ from other Systems in the Group."
+ ::= { airFMGroupLoadShare 4 }
+
+airFMGroupLoadShareReheatThreshC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Temperature threshold at which a System will generate
+ a load sharing request for reheating. Measured in
+ tenths of degrees Celsius."
+ ::= { airFMGroupLoadShare 5 }
+
+airFMGroupLoadShareReheatThreshF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Temperature threshold at which a System will generate
+ a load sharing request for reheating. Measured in
+ tenths of degrees Fahrenheit."
+ ::= { airFMGroupLoadShare 6 }
+
+airFMGroupLoadShareHumRequests OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Systems that are humidifying may request humidification
+ assistance from other Systems in the Group."
+ ::= { airFMGroupLoadShare 7 }
+
+airFMGroupLoadShareHumThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Humidity threshold at which a System will generate a
+ load sharing request for humidification. Measured in
+ tenths of percent relative humidity."
+ ::= { airFMGroupLoadShare 8 }
+
+airFMGroupLoadShareDehumRequests OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Systems that are dehumidifying may request assistance
+ from other Systems in the Group."
+ ::= { airFMGroupLoadShare 9 }
+
+airFMGroupLoadShareDehumThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Humidity threshold at which a System will generate a
+ load sharing request for dehumidification. Measured in
+ tenths of percent relative humidity."
+ ::= { airFMGroupLoadShare 10 }
+
+-- airFM Group System Failover Events
+airFMGroupFailoverSysAnyMinorAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disable (2),
+ enable (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enabling this OID will cause the system to enter
+ a failure state if any minor system alarm is active.
+ Once in the failure state, environmental control
+ ceases for the system, and the blowers enter the
+ Idle Blower Operation mode.
+ A value of notApplicable indicates that this alarm
+ does not apply to this device due to its configuration."
+ ::= { airFMGroupFailoverSys 1 }
+
+airFMGroupFailoverSysAnyMajorAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disable (2),
+ enable (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enabling this OID will cause the system to enter
+ a failure state if any major system alarm is active.
+ Once in the failure state, environmental control
+ ceases for the system, and the blowers enter the
+ Idle Blower Operation mode.
+ A value of notApplicable indicates that this alarm
+ does not apply to this device due to its configuration."
+ ::= { airFMGroupFailoverSys 2 }
+
+airFMGroupFailoverSysHighEnvTemp OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disable (2),
+ enable (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enabling this OID will cause the system to enter
+ a failure state if the high environmental temperature
+ alarm is active.
+ Once in the failure state, environmental control
+ ceases for the system, and the blowers enter the
+ Idle Blower Operation mode.
+ A value of notApplicable indicates that this alarm
+ does not apply to this device due to its configuration."
+ ::= { airFMGroupFailoverSys 3 }
+
+airFMGroupFailoverSysLowEnvTemp OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disable (2),
+ enable (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enabling this OID will cause the system to enter
+ a failure state if the low environmental temperature
+ alarm is active.
+ Once in the failure state, environmental control
+ ceases for the system, and the blowers enter the
+ Idle Blower Operation mode.
+ A value of notApplicable indicates that this alarm
+ does not apply to this device due to its configuration."
+ ::= { airFMGroupFailoverSys 4 }
+
+airFMGroupFailoverSysHighEnvHum OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disable (2),
+ enable (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enabling this OID will cause the system to enter
+ a failure state if the high environmental humidity
+ alarm is active.
+ Once in the failure state, environmental control
+ ceases for the system, and the blowers enter the
+ Idle Blower Operation mode.
+ A value of notApplicable indicates that this alarm
+ does not apply to this device due to its configuration."
+ ::= { airFMGroupFailoverSys 5 }
+
+airFMGroupFailoverSysLowEnvHum OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disable (2),
+ enable (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enabling this OID will cause the system to enter
+ a failure state if the low environmental humidity
+ alarm is active.
+ Once in the failure state, environmental control
+ ceases for the system, and the blowers enter the
+ Idle Blower Operation mode.
+ A value of notApplicable indicates that this alarm
+ does not apply to this device due to its configuration."
+ ::= { airFMGroupFailoverSys 6 }
+
+airFMGroupFailoverSysFireAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disable (2),
+ enable (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enabling this OID will cause the system to enter
+ a failure state if the fire alarm is active.
+ Once in the failure state, environmental control
+ ceases for the system, and the blowers enter the
+ Idle Blower Operation mode.
+ A value of notApplicable indicates that this alarm
+ does not apply to this device due to its configuration."
+ ::= { airFMGroupFailoverSys 7 }
+
+airFMGroupFailoverSysSmokeAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disable (2),
+ enable (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enabling this OID will cause the system to enter
+ a failure state if the smoke alarm is active.
+ Once in the failure state, environmental control
+ ceases for the system, and the blowers enter the
+ Idle Blower Operation mode.
+ A value of notApplicable indicates that this alarm
+ does not apply to this device due to its configuration."
+ ::= { airFMGroupFailoverSys 8 }
+
+airFMGroupFailoverSysCommLost OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disable (2),
+ enable (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enabling this OID will cause the system to enter
+ a failure state if the system has lost comm.
+ Once in the failure state, environmental control
+ ceases for the system, and the blowers enter the
+ Idle Blower Operation mode.
+ A value of notApplicable indicates that this alarm
+ does not apply to this device due to its configuration."
+ ::= { airFMGroupFailoverSys 9 }
+
+airFMGroupFailoverSysSupplySensorFail OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disable (2),
+ enable (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enabling this OID will cause the system to enter
+ a failure state if the supply sensor has failed.
+ Once in the failure state, environmental control
+ ceases for the system, and the blowers enter the
+ Idle Blower Operation mode.
+ A value of notApplicable indicates that this alarm
+ does not apply to this device due to its configuration."
+ ::= { airFMGroupFailoverSys 10 }
+
+airFMGroupFailoverSysReturnSensorFail OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disable (2),
+ enable (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enabling this OID will cause the system to enter
+ a failure state if the return sensor has failed.
+ Once in the failure state, environmental control
+ ceases for the system, and the blowers enter the
+ Idle Blower Operation mode.
+ A value of notApplicable indicates that this alarm
+ does not apply to this device due to its configuration."
+ ::= { airFMGroupFailoverSys 11 }
+
+airFMGroupFailoverSysPrimarySensorFail OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disable (2),
+ enable (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enabling this OID will cause the system to enter
+ a failure state if the primary sensor has failed.
+ Once in the failure state, environmental control
+ ceases for the system, and the blowers enter the
+ Idle Blower Operation mode.
+ A value of notApplicable indicates that this alarm
+ does not apply to this device due to its configuration."
+ ::= { airFMGroupFailoverSys 12 }
+
+airFMGroupFailoverSysSecondarySensorFail OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disable (2),
+ enable (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enabling this OID will cause the system to enter
+ a failure state if the secondary sensor has failed.
+ Once in the failure state, environmental control
+ ceases for the system, and the blowers enter the
+ Idle Blower Operation mode.
+ A value of notApplicable indicates that this alarm
+ does not apply to this device due to its configuration."
+ ::= { airFMGroupFailoverSys 13 }
+
+airFMGroupFailoverSysNoSensorsAvailable OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disable (2),
+ enable (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enabling this OID will cause the system to enter
+ a failure state if no sensors are available.
+ Once in the failure state, environmental control
+ ceases for the system, and the blowers enter the
+ Idle Blower Operation mode.
+ A value of notApplicable indicates that this alarm
+ does not apply to this device due to its configuration."
+ ::= { airFMGroupFailoverSys 14 }
+
+-- airFM Group Module Failover Events
+airFMGroupFailoverModMaintRequired OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disable (2),
+ enable (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enabling this OID will cause the system to enter
+ a failure state if maintenance is required on a
+ module.
+ Once in the failure state, environmental control
+ ceases for the system, and the blowers enter the
+ Idle Blower Operation mode.
+ A value of notApplicable indicates that this alarm
+ does not apply to this device due to its configuration."
+ ::= { airFMGroupFailoverMod 1 }
+
+airFMGroupFailoverModCoolFail OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disable (2),
+ enable (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enabling this OID will cause the system to enter
+ a failure state if cooling has failed on a module.
+ Once in the failure state, environmental control
+ ceases for the system, and the blowers enter the
+ Idle Blower Operation mode.
+ A value of notApplicable indicates that this alarm
+ does not apply to this device due to its configuration."
+ ::= { airFMGroupFailoverMod 2 }
+
+
+airFMGroupFailoverModHumFail OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disable (2),
+ enable (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enabling this OID will cause the system to enter
+ a failure state if the humidifier has failed on a
+ module.
+ Once in the failure state, environmental control
+ ceases for the system, and the blowers enter the
+ Idle Blower Operation mode.
+ A value of notApplicable indicates that this alarm
+ does not apply to this device due to its configuration."
+ ::= { airFMGroupFailoverMod 3 }
+
+airFMGroupFailoverModBlwrCntrl1Fail OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disable (2),
+ enable (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enabling this OID will cause the system to enter
+ a failure state if blower controller 1 has failed on
+ a module.
+ Once in the failure state, environmental control
+ ceases for the system, and the blowers enter the
+ Idle Blower Operation mode.
+ A value of notApplicable indicates that this alarm
+ does not apply to this device due to its configuration."
+ ::= { airFMGroupFailoverMod 4 }
+
+airFMGroupFailoverModBlwrCntrl2Fail OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disable (2),
+ enable (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enabling this OID will cause the system to enter
+ a failure state if blower controller 2 has failed on
+ a module.
+ Once in the failure state, environmental control
+ ceases for the system, and the blowers enter the
+ Idle Blower Operation mode.
+ A value of notApplicable indicates that this alarm
+ does not apply to this device due to its configuration."
+ ::= { airFMGroupFailoverMod 5 }
+
+airFMGroupFailoverModHighFilterDP OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disable (2),
+ enable (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enabling this OID will cause the system to enter
+ a failure state if a high filter differential
+ pressure is present on a module.
+ Once in the failure state, environmental control
+ ceases for the system, and the blowers enter the
+ Idle Blower Operation mode.
+ A value of notApplicable indicates that this alarm
+ does not apply to this device due to its configuration."
+ ::= { airFMGroupFailoverMod 6 }
+
+airFMGroupFailoverModHighSupplyTemp OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disable (2),
+ enable (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enabling this OID will cause the system to enter
+ a failure state if a high supply temperature is
+ active on a module.
+ Once in the failure state, environmental control
+ ceases for the system, and the blowers enter the
+ Idle Blower Operation mode.
+ A value of notApplicable indicates that this alarm
+ does not apply to this device due to its configuration."
+ ::= { airFMGroupFailoverMod 7 }
+
+airFMGroupFailoverModLowSupplyTemp OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disable (2),
+ enable (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enabling this OID will cause the system to enter
+ a failure state if a low supply temperature is active
+ on a module.
+ Once in the failure state, environmental control
+ ceases for the system, and the blowers enter the
+ Idle Blower Operation mode.
+ A value of notApplicable indicates that this alarm
+ does not apply to this device due to its configuration."
+ ::= { airFMGroupFailoverMod 8 }
+
+airFMGroupFailoverModLossOrLowAirFlow OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disable (2),
+ enable (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enabling this OID will cause the system to enter
+ a failure state if there is a loss of air flow or low
+ air flow on a module.
+ Once in the failure state, environmental control
+ ceases for the system, and the blowers enter the
+ Idle Blower Operation mode.
+ A value of notApplicable indicates that this alarm
+ does not apply to this device due to its configuration."
+ ::= { airFMGroupFailoverMod 9 }
+
+airFMGroupFailoverModHumReplaceCylinder OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disable (2),
+ enable (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enabling this OID will cause the system to enter
+ a failure state if a humidifier needs its cylinder
+ replaced on a module.
+ Once in the failure state, environmental control
+ ceases for the system, and the blowers enter the
+ Idle Blower Operation mode.
+ A value of notApplicable indicates that this alarm
+ does not apply to this device due to its configuration."
+ ::= { airFMGroupFailoverMod 10 }
+
+airFMGroupFailoverModAirBlockInterlockOpen OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disable (2),
+ enable (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enabling this OID will cause the system to enter
+ a failure state if the air block interlock is open
+ on a module.
+ Once in the failure state, environmental control
+ ceases for the system, and the blowers enter the
+ Idle Blower Operation mode.
+ A value of notApplicable indicates that this alarm
+ does not apply to this device due to its configuration."
+ ::= { airFMGroupFailoverMod 11 }
+
+airFMGroupFailoverModWaterDetected OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disable (2),
+ enable (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enabling this OID will cause the system to enter
+ a failure state if water is detected by a module.
+ Once in the failure state, environmental control
+ ceases for the system, and the blowers enter the
+ Idle Blower Operation mode.
+ A value of notApplicable indicates that this alarm
+ does not apply to this device due to its configuration."
+ ::= { airFMGroupFailoverMod 12 }
+
+airFMGroupFailoverModCondensatePumpFail OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disable (2),
+ enable (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enabling this OID will cause the system to enter
+ a failure state if the condensate pump has failed in
+ a module.
+ Once in the failure state, environmental control
+ ceases for the system, and the blowers enter the
+ Idle Blower Operation mode.
+ A value of notApplicable indicates that this alarm
+ does not apply to this device due to its configuration."
+ ::= { airFMGroupFailoverMod 13 }
+
+-- airFM System Status
+
+airFMSysNumber OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ one (2),
+ two (3),
+ three (4),
+ four (5)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of the system within the group.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysStatus 1 }
+
+airFMSysPresentStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ reserved1 (2),
+ reserved2 (3),
+ onLine (4),
+ idle (5),
+ loadShare (6),
+ failed (7),
+ offLine (8)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The present mode of the System.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysStatus 2 }
+
+airFMSysPresentRole OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ primary (2),
+ backup (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The present role of the System in the Group.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysStatus 3 }
+
+airFMSysRunHours OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The total number of hours the System has been
+ contributing to environmental control.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysStatus 4 }
+
+airFMSysCoilFluidTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature of the coolant at the fluid coil
+ inlet. Measured in degrees Celsius.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysStatus 5 }
+
+airFMSysCoilFluidTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature of the coolant at the fluid coil
+ inlet. Measured in degrees Fahrenheit.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysStatus 6 }
+
+airFMSysHotWaterTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The hot water temperature. Measured in degrees
+ Celsius.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysStatus 7 }
+
+airFMSysHotWaterTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The hot water temperature. Measured in degrees
+ Fahrenheit.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysStatus 8 }
+
+airFMSysAvgReturnTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The average return temperature calculated from all
+ present modules. Measured in tenths of degrees
+ Celsius.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysStatus 9 }
+
+airFMSysAvgReturnTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The average return temperature calculated from all
+ present modules. Measured in tenths of degrees
+ Fahrenheit.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysStatus 10 }
+
+airFMSysAvgReturnHum OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The average return humidity calculated from all
+ present modules. Measured in tenths of percent RH.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysStatus 11 }
+
+airFMSysAvgRemoteTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The average temperature calculated from all
+ operational remote sensors. Measured in tenths of
+ degrees Celsius.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysStatus 12 }
+
+airFMSysAvgRemoteTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The average temperature calculated from all
+ operational remote sensors. Measured in tenths of
+ degrees Fahrenheit.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysStatus 13 }
+
+airFMSysAvgRemoteHum OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The average return humidity calculated from all
+ present modules. Measured in tenths of percent RH.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysStatus 14 }
+
+airFMSysMaxRemoteTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum temperature reading from all operational
+ remote sensors. Measured in tenths of degrees
+ Celsius.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysStatus 15 }
+
+airFMSysMaxRemoteTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum temperature reading from all operational
+ remote sensors. Measured in tenths of degrees
+ Fahrenheit.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysStatus 16 }
+
+airFMSysMinRemoteTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum temperature reading from all operational
+ remote sensors. Measured in tenths of degrees
+ Celsius.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysStatus 17 }
+
+airFMSysMinRemoteTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum temperature reading from all operational
+ remote sensors. Measured in tenths of degrees
+ Fahrenheit.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysStatus 18 }
+
+airFMSysTempCtrlMethod OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ avgReturn (2),
+ avgRemote (3),
+ maxRemote (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The method of environment temperature control
+ selected to regulate the temperature.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysStatus 19 }
+
+airFMSysActualTempCtrlMethod OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ avgReturn (2),
+ avgRemote (3),
+ maxRemote (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The actual method of environment temperature control
+ being used to regulate the temperature.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysStatus 20 }
+
+airFMSysHumCtrlMethod OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ avgReturnRH (2),
+ avgReturnDewPt (3),
+ avgRemoteRH (4),
+ avgRemoteDewPt (5)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The method of environment humidity control selected
+ to regulate the humidity.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysStatus 21 }
+
+airFMSysActualHumCtrlMethod OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ avgReturnRH (2),
+ avgReturnDewPt (3),
+ avgRemoteRH (4),
+ avgRemoteDewPt (5)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The actual method of environment humidity control
+ being used to regulate the humidity.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysStatus 22 }
+
+airFMSysCtrlTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The system environmental control air temperature from
+ the sensor denoted by airFMSysActualTempCtrl.
+ Measured in tenths of degrees Celsius.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysStatus 23 }
+
+airFMSysCtrlTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The system environmental control air temperature from
+ the sensor denoted by airFMSysActualTempCtrl.
+ Measured in tenths of degrees Fahrenheit.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysStatus 24 }
+
+airFMSysCtrlHum OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The system environmental control air humidity from
+ the sensor denoted by airFMSysActualHumCtrl.
+ Measured in percent relative humidity.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysStatus 25 }
+
+-- airFM System Demands and Actuals
+
+airFMSysDXCoolingDmd OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The direct expansion cooling output demanded by the
+ System. Measured in percent.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysDemands 1 }
+
+airFMSysDXDehumDmd OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The direct expansion dehumidification output demanded
+ by the System. Measured in percent.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysDemands 2 }
+
+airFMSysDXActualCoolDehum OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The direct expansion cooling or dehumidification
+ output measured by the System. Measured in percent.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysDemands 3 }
+
+airFMSysCoilFluidCoolDmd OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The fluid coil cooling output demanded by the System.
+ Measured in percent.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysDemands 4 }
+
+airFMSysCoilFluidDehumDmd OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The fluid coil dehumidification output demanded by
+ the System. Measured in percent.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysDemands 5 }
+
+airFMSysCoilFluidActualCoolDehum OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The fluid coil cooling or dehumidification output
+ measured by the System. Measured in percent.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysDemands 6 }
+
+airFMSysElectricReheatDmd OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The electric reheating output demanded by the System.
+ Measured in percent.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysDemands 7 }
+
+airFMSysActualElectricReheat OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The electric reheating output of the System.
+ Measured in percent.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysDemands 8 }
+
+airFMSysSteamHotGasReheatDmd OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ off (2),
+ on (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The steam, hot water, or hot gas reheating output
+ demanded by the System.
+ A value of notApplicable indicates that this OID
+ does not apply to this device due to its configuration."
+ ::= { airFMSysDemands 9 }
+
+airFMSysActualSteamHotGasReheat OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ off (2),
+ on (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The steam, hot water, or hot gas reheating output of
+ the System.
+ A value of notApplicable indicates that this OID
+ does not apply to this device due to its configuration."
+ ::= { airFMSysDemands 10 }
+
+airFMSysSteamElectrodeHumDmd OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The steam electrode humidification output demanded by
+ the System. Measured in percent.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysDemands 11 }
+
+airFMSysActualSteamElectrodeHum OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The average steam electrode humidification output
+ measured for the Modules in the System. Measured in
+ percent.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysDemands 12 }
+
+airFMSysSteamHumDmd OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ off (2),
+ on (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The steam humidification output demanded by the System.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysDemands 13 }
+
+airFMSysActualSteamHum OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ off (2),
+ on (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The steam humidification output for the System.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysDemands 14 }
+
+-- airFM System Physical Setup
+
+airFMSysNumModules OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ one (2),
+ two (3),
+ three (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of Modules in this System.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysSetup 1 }
+
+airFMSysNumPCIOMs OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ one (2),
+ two (3),
+ three (4),
+ four (5)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of Programmable Customer Input/Output
+ Modules (PCIOMs) installed in the Main Module of this
+ System. Each PCIOM adds four input contacts and four
+ output relays to the System.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysSetup 2 }
+
+airFMSysMainsVlt OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The mains voltage for the Modules in this System.
+ A value of N/A indicates that this OID does not apply
+ to this device due to its configuration."
+ ::= { airFMSysSetup 3 }
+
+airFMSysUPSVlt OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The UPS voltage for the Modules in this System.
+ A value of N/A indicates that this OID does not apply
+ to this device due to its configuration."
+ ::= { airFMSysSetup 4 }
+
+airFMSysCoilCfg OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ dx (2),
+ econ (3),
+ multicool (4),
+ chilledWater (5)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The type of cooling coils installed in the Modules in
+ this System: DX coil, DX and MultiCool (chilled water)
+ coils, DX and Economizer coils, or only a Chilled
+ Liquid coil.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysSetup 5 }
+
+airFMSysRefrigType OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ r22 (2),
+ r407C (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The type of refrigerant used by each compressor in
+ the system.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysSetup 6 }
+
+airFMSysHeatRejection OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ airCooled (2),
+ waterCooled (3),
+ glycolCooled (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The method the Modules in this System use to transfer
+ heat away from the refrigerant.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysSetup 7 }
+
+airFMSysDischAirPtrn OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ upFlow (2),
+ downFlow (3),
+ horizFlow (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The discharge air pattern for the Modules in this
+ System.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysSetup 8 }
+
+airFMSysAirFltr OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ standard (2),
+ highEfficiency (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The type of air filters (standard or high efficiency)
+ installed in the Modules of this System.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysSetup 9 }
+
+airFMSysFlowSwitch OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ none (2),
+ dxEcon (3),
+ multiCoolChillWater (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The location of the optional flow switch.
+ None: No flow switch is installed in this System.
+ DX: Coolant input to the heat exchanger (condenser).
+ MultiCool: Chilled water input to the MultiCool coil.
+
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysSetup 10 }
+
+airFMSysCoilFluidVlvAct OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ none (2),
+ springAnalog (3),
+ floatingControl (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The type of valve actuator installed on the coil
+ fluid valve. The coil fluid valve controls the flow
+ of coolant into a fluid cooling coil, such as a
+ MultiCool or Economizer coil.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysSetup 11 }
+
+airFMSysCoilFluidVlvType OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ twoWay (2),
+ threeWay (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The type of coil fluid valve installed for the
+ Modules in this System.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysSetup 12 }
+
+airFMSysCndsrFluidVlvAct OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ none (2),
+ floatingControl (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The type of valve actuator installed on the Condenser
+ fluid valve. The Condenser fluid valve controls the
+ flow of coolant into the heat exchanger (condenser)
+ to regulate head pressure.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysSetup 13 }
+
+airFMSysCndsrFluidVlvType OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ twoWay (2),
+ threeWay (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The type of Condenser fluid valve installed for the
+ Modules in this System.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysSetup 14 }
+
+airFMSysHotWaterVlvAct OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ none (2),
+ springAnalog (3),
+ floatingControl (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The type of valve actuator installed on the hot water
+ valve.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysSetup 15 }
+
+airFMSysNumRemoteSensors OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of remote sensors detected by the system."
+ ::= { airFMSysSetup 16 }
+
+-- airFM System Configuration
+
+airFMSysPrimaryControlSensor OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ return (2),
+ remote (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Selects whether return or remote sensors will control
+ the system.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysConfig 1 }
+
+airFMSysRemoteSensorData OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ average (2),
+ maximum (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Selects whether average temperature or max temperature
+ will be used when remote sensors are selected for
+ control of the system.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysConfig 2 }
+
+airFMSysFastStartup OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Minimizes the time for the cooling process to begin
+ after other delay constraints have been met.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysConfig 3 }
+
+airFMSysStartupDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Set the delay that begins when power is applied and
+ ends when the System starts. This allows you to
+ create a staged restart among your Systems after a
+ power loss. Measured in seconds.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysConfig 4 }
+
+airFMSysModeDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Set the delay between starting the blowers and
+ engaging the modes. It allows the sensors to read
+ room conditions accurately and allows the controller
+ to check for major alarms before engaging a mode.
+ Measured in seconds.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysConfig 5 }
+
+airFMSysCommLossShutdownDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Set the delay between an Expansion Module losing
+ communication with the Main Module and the Expansion
+ Module shutting down. A value of -1 will keep
+ the Expansion Module running after a communication
+ loss. Measured in hours.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysConfig 6 }
+
+airFMSysResetSysFailure OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ noOperation (2),
+ reset (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to reset(2) will allows the system
+ to return from any failure condition, if the
+ failure(s) have cleared.
+ Getting this OID will do nothing and return the noOperation(1) value.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysConfig 7 }
+
+airFMSysResetUserDflts OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ noOperation (2),
+ reset (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to reset(2) will reset all system
+ parameters that can be edited by the user to their
+ factory default values.
+ Getting this OID will do nothing and return the noOperation(1) value.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysConfig 8 }
+
+airFMSysResetFldSrvcDflts OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ noOperation (2),
+ reset (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to reset(2) will reset all system
+ parameters that can only be edited by the field
+ service engineer to their factory default values.
+ Getting this OID will do nothing and return the noOperation(1) value.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysConfig 9 }
+
+airFMSysResetRunHours OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ noOperation (2),
+ reset (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting this OID to reset(2) will reset the system Run Hours.
+ Getting this OID will do nothing and return the noOperation(1) value.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysConfig 10 }
+
+-- airFM System Cooling
+
+airFMSysCompMinOnTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Set the minimum time the compressor continues to
+ operate after it is started. The delay protects the
+ compressor from damage. Caution: Reducing this delay
+ shortens compressor life. Measured in seconds.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysCooling 1 }
+
+airFMSysCompMinOffTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Set the minimum time the compressor will remain off
+ after it ceases operation. The delay protects the
+ compressor from damage. Caution: Reducing this delay
+ shortens compressor life. Measured in seconds.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysCooling 2 }
+
+airFMSysCompRotPeriod OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Set how often to perform compressor runtime
+ balancing. Measured in hours.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysCooling 3 }
+
+airFMSysEconIsolVlvOpenDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Set the delay between opening the Economizer Isolator
+ output relay and engaging the compressors. Measured
+ in seconds.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysCooling 4 }
+
+airFMSysEconIsolVlvCloseDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Set the delay between disengaging the compressor and
+ closing the Economizer Isolator output relay.
+ Measured in seconds.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysCooling 5 }
+
+airFMSysCndsrFluidVlvCloseDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Set the time the condenser valve remains open after
+ the compressors disengage. Measured in seconds.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysCooling 6 }
+
+airFMSysInterstageDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The DX interstage delay allows the first compressor's
+ cooling to take effect before engaging the second
+ compressor. This prevents the second compressor from
+ cycling on and off excessively. Measured in seconds.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysCooling 7 }
+
+airFMSysCoolState OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Set the mode to enabled or disabled. Disabled modes
+ will not operate, and you cannot make changes to
+ their settings while they are disabled.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysCooling 8 }
+
+airFMSysCoolEssFunction OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ yes (2),
+ no (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Set the priority of the mode for alarms and events
+ with the nonessential stop behavior. Nonessential
+ modes are disabled during nonessential stop alarms
+ and events.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysCooling 9 }
+
+airFMSysCoolSetpointC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The target value for the selected control sensor air
+ for this mode. It must be at least 1.0 C above the
+ reheat setpoint if a heater is installed. Measured
+ in tenths of degrees Celsius.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysCooling 10 }
+
+airFMSysCoolSetpointF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The target value for the selected control sensor air
+ for this mode. It must be at least 1.0 C above the
+ reheat setpoint if a heater is installed. Measured
+ in tenths of degrees Fahrenheit.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysCooling 11 }
+
+airFMSysCoolDeadbandC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature range that controls output when the
+ selected control sensor temperature is above the
+ setpoint. At the top of this range, the cool mode
+ outputs at 100%. The deadband does not apply to PID-
+ controlled modes. Measured in tenths of degrees
+ Celsius.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysCooling 12 }
+
+airFMSysCoolDeadbandF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature range that controls output when the
+ selected control sensor temperature is above the
+ setpoint. At the top of this range, the cool mode
+ outputs at 100%. The deadband does not apply to PID-
+ controlled modes. Measured in tenths of degrees
+ Fahrenheit.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysCooling 13 }
+
+airFMSysCoolEconIsolFunction OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Set the Economizer Automatic Coolant Isolation valve
+ to enabled or disabled. This valve anticipates a
+ cooling demand and opens the coil fluid valve.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysCooling 14 }
+
+airFMSysSuctPresCompensation OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Set the Suction Pressure Compensation to enabled or
+ disabled. This function attempts to keep the suction
+ pressure from exceeding 95 psi.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysCooling 15 }
+
+airFMSysCoilFluidActivThreshC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum coolant temperature required to use the
+ optional MultiCool or Economizer coil. Measured in
+ tenths of degrees Celsius.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysCooling 16 }
+
+airFMSysCoilFluidActivThreshF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum coolant temperature required to use the
+ optional MultiCool or Economizer coil. Measured in
+ tenths of degrees Fahrenheit.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysCooling 17 }
+
+airFMSysCoilFluidActivDeadbandC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The controller will disengage the MultiCool or
+ Economizer coil when the coolant temperature reaches
+ the coil fluid temperature activation threshold plus
+ the deadband. Measured in tenths of degrees Celsius.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysCooling 18 }
+
+airFMSysCoilFluidActivDeadbandF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The controller will disengage the MultiCool or
+ Economizer coil when the coolant temperature reaches
+ the coil fluid temperature activation threshold plus
+ the deadband. Measured in tenths of degrees
+ Fahrenheit.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysCooling 19 }
+
+airFMSysCoolPIDMethod OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ p (2),
+ pi (3),
+ pid (4)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Set the multipliers that the PID algorithm will use
+ to calculate the cool output. Proportional,
+ Proportional + Integral, or Proportional + Integral
+ + Derivative.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysCooling 20 }
+
+airFMSysCoolPIDGainP OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Set the proportional multiplier to correct for
+ differences between the selected control sensor
+ actual temperature and the setpoint. Measured in
+ %/C.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysCooling 21 }
+
+airFMSysCoolPIDResetRateI OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Set the integral multiplier to correct for the
+ proportional offset. Measured in %/(C * min).
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysCooling 22 }
+
+airFMSysCoolPIDDerivativeD OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Set the derivative multiplier to counteract overshoot
+ and droop during changes in the room load. Measured
+ in %/(C / min).
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysCooling 23 }
+
+-- airFM System Humidify Function
+
+airFMSysHumState OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Set the mode to enabled or disabled. Disabled modes
+ will not operate, and you cannot make changes to their
+ settings while they are disabled.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysHumidify 1 }
+
+airFMSysHumEssFunction OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ yes (2),
+ no (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Set the priority of the mode for alarms and events
+ with the nonessential stop behavior. Nonessential
+ modes are disabled during nonessential stop alarms
+ and events.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysHumidify 2 }
+
+airFMSysHumSetpoint OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The target value for the selected control sensor air
+ for this mode. It must be at least 1.0 % RH below
+ the dehumidification setpoint. Measured in tenths of
+ percent relative humidity.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysHumidify 3 }
+
+airFMSysHumDeadband OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The humidity range that controls output when the
+ selected control sensor humidity is below the
+ setpoint. At the top of this range, the
+ humidification mode outputs at 100%. The deadband
+ does not apply to PID-controlled modes. Measured in
+ tenths of percent relative humidity.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysHumidify 4 }
+
+airFMSysHumCtrlSetting OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ relativeHum (2),
+ dewPoint (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Set the method to control the humidity in the room.
+ The two methods are Relative Humidity (RH) or Dew
+ Point of the selected control sensor air. The dew
+ point method helps correct for hot spots near the
+ selected control sensors.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysHumidify 5 }
+
+airFMSysActualHumCtrl OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ relativeHum (2),
+ dewPoint (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The humidity control method the system is using.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysHumidify 6 }
+
+airFMSysHumSensBand OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The percentage of relative humidity below the
+ setpoint at which the humidifier will output at 100%
+ of capacity. Measured in percent relative humidity.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysHumidify 7 }
+
+-- airFM System Dehumidify Function
+
+airFMSysDehumState OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Set the mode to enabled or disabled. Disabled modes
+ will not operate, and you cannot make changes to their
+ settings while they are disabled.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysDehumidify 1 }
+
+airFMSysDehumEssFunction OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ yes (2),
+ no (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Set the priority of the mode for alarms and events
+ with the nonessential stop behavior. Nonessential
+ modes are disabled during nonessential stop alarms
+ and events.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysDehumidify 2 }
+
+airFMSysDehumSetpoint OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The target value for the selected control sensor air
+ for this mode. It must be at least 1.0 % RH above
+ the humidification setpoint if a humidifier is
+ installed. Measured in tenths of percent relative
+ humidity.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysDehumidify 3 }
+
+airFMSysDehumDeadband OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The humidity range above the setpoint at which the
+ dehumidification mode will output at 100%. The
+ deadband does not apply to PID controlled modes.
+ Measured in tenths of percent relative humidity.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysDehumidify 4 }
+
+airFMSysDehumCapacity OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ half (2),
+ full (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Set the dehumidification mode to use either half of
+ the cooling coil or the full coil when dehumidifying
+ the room.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysDehumidify 5 }
+
+airFMSysDehumPIDMethod OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ p (2),
+ pi (3),
+ pid (4)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Set the multipliers that the PID algorithm will use
+ to calculate the output. Proportional,
+ Proportional + Integral, or Proportional + Integral
+ + Derivative.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysDehumidify 6 }
+
+airFMSysDehumPIDGainP OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Set the proportional multiplier to correct for
+ differences between the selected control sensor
+ actual humidity and the setpoint. Measured in %/%RH.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysDehumidify 7 }
+
+airFMSysDehumPIDResetRateI OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Set the integral multiplier to correct for the
+ proportional offset. Measured in %/(%RH * min).
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysDehumidify 8 }
+
+airFMSysDehumPIDDerivativeD OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Set the derivative multiplier to counteract overshoot
+ and droop during changes in the room humidity.
+ Measure in %/(%RH / min).
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysDehumidify 9 }
+
+-- airFM System Reheat Function
+
+airFMSysReheatState OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Set the mode to enabled or disabled. Disabled modes
+ will not operate, and you cannot make changes to their
+ settings while they are disabled.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysReheat 1 }
+
+airFMSysReheatEssFunction OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ yes (2),
+ no (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Set the priority of the mode for alarms and events
+ with the nonessential stop behavior. Nonessential
+ modes are disabled during nonessential stop alarms
+ and events.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysReheat 2 }
+
+airFMSysReheatSetpointC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The target value for the selected control sensor air
+ for this mode. It must be at least 1.0 C below the
+ cooling setpoint. Measured in tenths of degrees
+ Celsius.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysReheat 3 }
+
+airFMSysReheatSetpointF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The target value for the selected control sensor air
+ for this mode. It must be at least 1.0 C below the
+ cooling setpoint. Measured in tenths of degrees
+ Fahrenheit.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysReheat 4 }
+
+airFMSysReheatDeadbandC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature range that controls output when the
+ selected control sensor temperature is below the
+ setpoint. At the bottom of this range, the reheat
+ mode outputs at 100%. The deadband does not apply to
+ PID-controlled modes. Measured in tenths of degrees
+ Celsius.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysReheat 5 }
+
+airFMSysReheatDeadbandF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature range that controls output when the
+ selected control sensor temperature is below the
+ setpoint. At the bottom of this range, the reheat
+ mode outputs at 100%. The deadband does not apply to
+ PID-controlled modes. Measured in tenths of degrees
+ Fahrenheit.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysReheat 6 }
+
+airFMSysReheatPIDMethod OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ p (2),
+ pi (3),
+ pid (4)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Set the multipliers that the PID algorithm will use
+ to calculate the output. Proportional,
+ Proportional + Integral, or Proportional + Integral
+ + Derivative.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysReheat 7 }
+
+airFMSysReheatPIDGainP OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Set the proportional multiplier to correct for
+ differences between the selected control sensor
+ actual temperature and the setpoint. Measured in
+ %/C.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysReheat 8 }
+
+airFMSysReheatPIDResetRateI OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Set the integral multiplier to correct for the
+ proportional offset. Measured in %/(C * min).
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysReheat 9 }
+
+airFMSysReheatPIDDerivativeD OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Set the derivative multiplier to counteract overshoot
+ and droop during changes in the room load. Measured
+ in %/(C / min).
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysReheat 10 }
+
+-- airFM System Thresholds
+
+airFMSysHighSplyTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The high temperature threshold for air blown into the
+ room (supply). If the supply temperature exceeds the
+ threshold, an alarm will occur. Measured in tenths
+ of degrees Celsius.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysThresholds 1 }
+
+airFMSysHighSplyTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The high temperature threshold for air blown into the
+ room (supply). If the supply temperature exceeds the
+ threshold, an alarm will occur. Measured in tenths
+ of degrees Fahrenheit.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysThresholds 2 }
+
+airFMSysLowSplyTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The low temperature threshold for air blown into the
+ room (supply). If the supply temperature drops below
+ the threshold, an alarm will occur. Measured in
+ tenths of degrees Celsius.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysThresholds 3 }
+
+airFMSysLowSplyTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The low temperature threshold for air blown into the
+ room (supply). If the supply temperature drops below
+ the threshold, an alarm will occur. Measured in
+ tenths of degrees Fahrenheit.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysThresholds 4 }
+
+airFMSysHighCoilFluidTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The high temperature threshold for coolant at the
+ inlet to the fluid coil. If the fluid coil coolant
+ temperature exceeds the threshold, an alarm will
+ occur. Measured in tenths of degrees Celsius.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysThresholds 5 }
+
+airFMSysHighCoilFluidTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The high temperature threshold for coolant at the
+ inlet to the fluid coil. If the fluid coil coolant
+ temperature exceeds the threshold, an alarm will
+ occur. Measured in tenths of degrees Fahrenheit.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysThresholds 6 }
+
+airFMSysLowCoilFluidTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The low temperature threshold for coolant at the
+ inlet to the fluid coil. If the fluid coil coolant
+ temperature drops below the threshold, an alarm will
+ occur. Measured in tenths of degrees Celsius.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysThresholds 7 }
+
+airFMSysLowCoilFluidTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The low temperature threshold for coolant at the
+ inlet to the fluid coil. If the fluid coil coolant
+ temperature drops below the threshold, an alarm will
+ occur. Measured in tenths of degrees Fahrenheit.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysThresholds 8 }
+
+airFMSysHighCtrlTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The high temperature threshold for air monitored by
+ the System. If the temperature exceeds the threshold,
+ an alarm will occur. Measured in tenths of degrees
+ Celsius.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysThresholds 9 }
+
+airFMSysHighCtrlTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The high temperature threshold for air monitored by
+ the System. If the temperature exceeds the threshold,
+ an alarm will occur. Measured in tenths of degrees
+ Fahrenheit.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysThresholds 10 }
+
+airFMSysLowCtrlTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The low temperature threshold for air monitored by
+ the System. If the temperature drops below the
+ threshold, an alarm will occur. Measured in tenths
+ of degrees Celsius.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysThresholds 11 }
+
+airFMSysLowCtrlTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The low temperature threshold for air monitored by
+ the System. If the temperature drops below the
+ threshold, an alarm will occur. Measured in tenths
+ of degrees Fahrenheit.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysThresholds 12 }
+
+airFMSysHighCtrlHum OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The high humidity threshold for air monitored by the
+ System. If the humidity exceeds the threshold, an
+ alarm will occur. Measured in tenths of percent
+ relative humidity.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysThresholds 13 }
+
+airFMSysLowCtrlHum OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The low humidity threshold for air monitored by the
+ System. If the humidity drops below the threshold,
+ an alarm will occur. Measured in tenths of percent
+ relative humidity.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysThresholds 14 }
+
+airFMSysTempAlarmDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The amount of time the blower must be on before a
+ temperature alarm can be issued. Measured in
+ seconds.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysThresholds 15 }
+
+airFMSysHumAlarmDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The amount of time the blower must be on before a
+ humidity alarm can be issued. Measured in seconds.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysThresholds 16 }
+
+-- airFM System Input Contacts
+
+airFMSysInputTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the airFMSysInputTable. "
+ ::= { airFMSysInputs 1 }
+
+airFMSysInputTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AirFMSysInputEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting information from each input
+ contact."
+ ::= { airFMSysInputs 2 }
+
+airFMSysInputEntry OBJECT-TYPE
+ SYNTAX AirFMSysInputEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The input contact to obtain status from."
+ INDEX { airFMSysInputIndex }
+ ::= { airFMSysInputTable 1 }
+
+AirFMSysInputEntry ::=
+ SEQUENCE {
+ airFMSysInputIndex INTEGER,
+ airFMSysInputName DisplayString,
+ airFMSysInputStatus INTEGER,
+ airFMSysInputNormalState INTEGER,
+ airFMSysInputDelay INTEGER,
+ airFMSysInputAlarmAction INTEGER
+ }
+
+airFMSysInputIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number designator of the Input Contact."
+ ::= { airFMSysInputEntry 1 }
+
+airFMSysInputName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The configurable name for the Input Contact. Maximum
+ text input is 13 characters."
+ ::= { airFMSysInputEntry 2 }
+
+airFMSysInputStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The state of this contact: Open or Closed. A
+ violation will occur when this relay is not in its
+ normal state."
+ ::= { airFMSysInputEntry 3 }
+
+airFMSysInputNormalState OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Set the normal state of this contact (the state when
+ no alarm/event exists)."
+ ::= { airFMSysInputEntry 4 }
+
+airFMSysInputDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Set the delay between this contact exiting its normal
+ state and an alarm being triggered. Measured in
+ seconds."
+ ::= { airFMSysInputEntry 5 }
+
+airFMSysInputAlarmAction OBJECT-TYPE
+ SYNTAX INTEGER {
+ statusOnly (1),
+ minor (2),
+ major (3),
+ remoteRunStop (4),
+ nonessStop (5),
+ immShutdown (6)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Sets the behavior for this contact when it exits its
+ normal state."
+ ::= { airFMSysInputEntry 6 }
+
+-- airFM System Output Relays
+
+airFMSysOutputTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the airFMSysOutputTable. "
+ ::= { airFMSysOutputs 1 }
+
+airFMSysOutputTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AirFMSysOutputEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting information from each output relay. "
+ ::= { airFMSysOutputs 2 }
+
+airFMSysOutputEntry OBJECT-TYPE
+ SYNTAX AirFMSysOutputEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The output relay to obtain status from."
+ INDEX { airFMSysOutputIndex }
+ ::= { airFMSysOutputTable 1 }
+
+AirFMSysOutputEntry ::=
+ SEQUENCE {
+ airFMSysOutputIndex INTEGER,
+ airFMSysOutputStatus INTEGER,
+ airFMSysOutputNormalState INTEGER
+ }
+
+airFMSysOutputIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number designator of the output relay."
+ ::= { airFMSysOutputEntry 1 }
+
+airFMSysOutputStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The state of this relay: Open or Closed. A violation
+ will occur when this relay is not in its normal state."
+ ::= { airFMSysOutputEntry 2 }
+
+airFMSysOutputNormalState OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Set the normal state of this relay (the state when no
+ alarm/event exists)."
+ ::= { airFMSysOutputEntry 3 }
+
+-- airFM System Output Alarm Mapping
+
+airFMSysAlarmMapSysTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the airFMSysAlarmMapSysTable. "
+ ::= { airFMSysAlarmMapSys 1 }
+
+airFMSysAlarmMapSysTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AirFMSysAlarmMapSysEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting alarm map information."
+ ::= { airFMSysAlarmMapSys 2 }
+
+airFMSysAlarmMapSysEntry OBJECT-TYPE
+ SYNTAX AirFMSysAlarmMapSysEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The system alarm map type to reference."
+ INDEX { airFMSysAlarmMapSysOutputIndex }
+ ::= { airFMSysAlarmMapSysTable 1 }
+
+AirFMSysAlarmMapSysEntry ::=
+ SEQUENCE {
+ airFMSysAlarmMapSysOutputIndex INTEGER,
+ airFMSysAlarmMapSysAnyAlarm INTEGER,
+ airFMSysAlarmMapSystemOn INTEGER,
+ airFMSysAlarmMapSystemOffline INTEGER,
+ airFMSysAlarmMapSysHighEnvTemp INTEGER,
+ airFMSysAlarmMapSysLowEnvTemp INTEGER,
+ airFMSysAlarmMapSysHighEnvHum INTEGER,
+ airFMSysAlarmMapSysLowEnvHum INTEGER,
+ airFMSysAlarmMapSysFireDet INTEGER,
+ airFMSysAlarmMapSysSmokeDet INTEGER,
+ airFMSysAlarmMapSysEconIsol INTEGER,
+ airFMSysAlarmMapSysSupplySensFail INTEGER,
+ airFMSysAlarmMapSysReturnSensFail INTEGER,
+ airFMSysAlarmMapSysRemSensRemoved INTEGER,
+ airFMSysAlarmMapSysPrimSensFail INTEGER,
+ airFMSysAlarmMapSysSecSensFail INTEGER,
+ airFMSysAlarmMapSysSecSensActive INTEGER
+ }
+
+airFMSysAlarmMapSysOutputIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of the output relay."
+ ::= { airFMSysAlarmMapSysEntry 1 }
+
+airFMSysAlarmMapSysAnyAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "System alarm map setting for Any Alarm.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapSysEntry 2 }
+
+airFMSysAlarmMapSystemOn OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "System alarm map setting for System On.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapSysEntry 3 }
+
+airFMSysAlarmMapSystemOffline OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "System alarm map setting for System Offline.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapSysEntry 4 }
+
+airFMSysAlarmMapSysHighEnvTemp OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "System alarm map setting for High Environmental
+ Temperature.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapSysEntry 5 }
+
+airFMSysAlarmMapSysLowEnvTemp OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "System alarm map setting for Low Environmental
+ Temperature.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapSysEntry 6 }
+
+airFMSysAlarmMapSysHighEnvHum OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "System alarm map setting for High Environmental
+ Humidity.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapSysEntry 7 }
+
+airFMSysAlarmMapSysLowEnvHum OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "System alarm map setting for Low Environmental
+ Humidity.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapSysEntry 8 }
+
+airFMSysAlarmMapSysFireDet OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "System alarm map setting for Fire Detected.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapSysEntry 9 }
+
+airFMSysAlarmMapSysSmokeDet OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "System alarm map setting for Smoke Detected.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapSysEntry 10 }
+
+airFMSysAlarmMapSysEconIsol OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "System alarm map setting for Econ Isolator.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapSysEntry 11 }
+
+airFMSysAlarmMapSysSupplySensFail OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "System alarm map setting for Supply Sensor Failure.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapSysEntry 12 }
+
+airFMSysAlarmMapSysReturnSensFail OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "System alarm map setting for Return Sensor Failure.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapSysEntry 13 }
+
+airFMSysAlarmMapSysRemSensRemoved OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "System alarm map setting for Remote Sensor Removed.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapSysEntry 14 }
+
+airFMSysAlarmMapSysPrimSensFail OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "System alarm map setting for Primary Sensor Failure.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapSysEntry 15 }
+
+airFMSysAlarmMapSysSecSensFail OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "System alarm map setting for Secondary Sensor Failure.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapSysEntry 16 }
+
+airFMSysAlarmMapSysSecSensActive OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "System alarm map setting for Secondary Sensor Active.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapSysEntry 17 }
+
+-- airFM Main Module Output Alarm Mapping
+
+airFMSysAlarmMapMainModTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the airFMSysAlarmMapMainModTable. "
+ ::= { airFMSysAlarmMapMainMod 1 }
+
+airFMSysAlarmMapMainModTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AirFMSysAlarmMapMainModEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting alarm map information."
+ ::= { airFMSysAlarmMapMainMod 2 }
+
+airFMSysAlarmMapMainModEntry OBJECT-TYPE
+ SYNTAX AirFMSysAlarmMapMainModEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The main module alarm map type to reference."
+ INDEX { airFMSysAlarmMapMainModOutputIndex }
+ ::= { airFMSysAlarmMapMainModTable 1 }
+
+AirFMSysAlarmMapMainModEntry ::=
+ SEQUENCE {
+ airFMSysAlarmMapMainModOutputIndex INTEGER,
+ airFMSysAlarmMapMainModAnyAlarm INTEGER,
+ airFMSysAlarmMapMainModMaintReq INTEGER,
+ airFMSysAlarmMapMainModCoolFail INTEGER,
+ airFMSysAlarmMapMainModHighSupplyTemp INTEGER,
+ airFMSysAlarmMapMainModLowSupplyTemp INTEGER,
+ airFMSysAlarmMapMainModHumFail INTEGER,
+ airFMSysAlarmMapMainModHumReplCyl INTEGER,
+ airFMSysAlarmMapMainModCondPumpFail INTEGER,
+ airFMSysAlarmMapMainModBlwrCntl1Fail INTEGER,
+ airFMSysAlarmMapMainModBlwrCntl2Fail INTEGER,
+ airFMSysAlarmMapMainModHighFltrDP INTEGER,
+ airFMSysAlarmMapMainModLowAirFlow INTEGER,
+ airFMSysAlarmMapMainModAirBlckIntOpen INTEGER,
+ airFMSysAlarmMapMainModWaterDetected INTEGER
+ }
+
+airFMSysAlarmMapMainModOutputIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of the output relay."
+ ::= { airFMSysAlarmMapMainModEntry 1 }
+
+airFMSysAlarmMapMainModAnyAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Main Module alarm map setting for Any Alarm.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapMainModEntry 2 }
+
+airFMSysAlarmMapMainModMaintReq OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Main Module alarm map setting for Module Maintenance
+ Required.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapMainModEntry 3 }
+
+airFMSysAlarmMapMainModCoolFail OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Main Module alarm map setting for Module Cooling
+ Failure.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapMainModEntry 4 }
+
+airFMSysAlarmMapMainModHighSupplyTemp OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Main Module alarm map setting for High Supply
+ Temperature.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapMainModEntry 5 }
+
+airFMSysAlarmMapMainModLowSupplyTemp OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Main Module alarm map setting for Low Supply
+ Temperature.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapMainModEntry 6 }
+
+airFMSysAlarmMapMainModHumFail OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Main Module alarm map setting for Humidifier Failure.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapMainModEntry 7 }
+
+airFMSysAlarmMapMainModHumReplCyl OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Main Module alarm map setting for Humidifier Replace
+ Cylinder.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapMainModEntry 8 }
+
+airFMSysAlarmMapMainModCondPumpFail OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Main Module alarm map setting for Condensate Pump
+ Failure.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapMainModEntry 9 }
+
+airFMSysAlarmMapMainModBlwrCntl1Fail OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Main Module alarm map setting for Blower Controller 1
+ Failure.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapMainModEntry 10 }
+
+airFMSysAlarmMapMainModBlwrCntl2Fail OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Main Module alarm map setting for Blower Controller 2
+ Failure.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapMainModEntry 11 }
+
+airFMSysAlarmMapMainModHighFltrDP OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Main Module alarm map setting for High Filter
+ Differential Pressure.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapMainModEntry 12 }
+
+airFMSysAlarmMapMainModLowAirFlow OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Main Module alarm map setting for Low Air Flow.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapMainModEntry 13 }
+
+airFMSysAlarmMapMainModAirBlckIntOpen OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Main Module alarm map setting for Air Block Interlock
+ Open.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapMainModEntry 14 }
+
+airFMSysAlarmMapMainModWaterDetected OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Main Module alarm map setting for Water Detected.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapMainModEntry 15 }
+
+-- airFM Exp Module 1 Output Alarm Mapping
+
+airFMSysAlarmMapExpMod1TableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the airFMSysAlarmMapExpMod1Table. "
+ ::= { airFMSysAlarmMapExpMod1 1 }
+
+airFMSysAlarmMapExpMod1Table OBJECT-TYPE
+ SYNTAX SEQUENCE OF AirFMSysAlarmMapExpMod1Entry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting alarm map information."
+ ::= { airFMSysAlarmMapExpMod1 2 }
+
+airFMSysAlarmMapExpMod1Entry OBJECT-TYPE
+ SYNTAX AirFMSysAlarmMapExpMod1Entry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The expansion module 1 alarm map type to reference."
+ INDEX { airFMSysAlarmMapExpMod1OutputIndex }
+ ::= { airFMSysAlarmMapExpMod1Table 1 }
+
+AirFMSysAlarmMapExpMod1Entry ::=
+ SEQUENCE {
+ airFMSysAlarmMapExpMod1OutputIndex INTEGER,
+ airFMSysAlarmMapExpMod1AnyAlarm INTEGER,
+ airFMSysAlarmMapExpMod1MaintReq INTEGER,
+ airFMSysAlarmMapExpMod1CoolFail INTEGER,
+ airFMSysAlarmMapExpMod1HighSupplyTemp INTEGER,
+ airFMSysAlarmMapExpMod1LowSupplyTemp INTEGER,
+ airFMSysAlarmMapExpMod1HumFail INTEGER,
+ airFMSysAlarmMapExpMod1HumReplCyl INTEGER,
+ airFMSysAlarmMapExpMod1CondPumpFail INTEGER,
+ airFMSysAlarmMapExpMod1BlwrCntl1Fail INTEGER,
+ airFMSysAlarmMapExpMod1BlwrCntl2Fail INTEGER,
+ airFMSysAlarmMapExpMod1HighFltrDP INTEGER,
+ airFMSysAlarmMapExpMod1LowAirFlow INTEGER,
+ airFMSysAlarmMapExpMod1AirBlckIntOpen INTEGER,
+ airFMSysAlarmMapExpMod1WaterDetected INTEGER
+ }
+
+airFMSysAlarmMapExpMod1OutputIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of the output relay."
+ ::= { airFMSysAlarmMapExpMod1Entry 1 }
+
+airFMSysAlarmMapExpMod1AnyAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Exp Module 1 alarm map setting for Any Alarm.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapExpMod1Entry 2 }
+
+airFMSysAlarmMapExpMod1MaintReq OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Exp Module 1 alarm map setting for Module Maintenance
+ Required.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapExpMod1Entry 3 }
+
+airFMSysAlarmMapExpMod1CoolFail OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Exp Module 1 alarm map setting for Module Cooling
+ Failure.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapExpMod1Entry 4 }
+
+airFMSysAlarmMapExpMod1HighSupplyTemp OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Exp Module 1 alarm map setting for High Supply
+ Temperature.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapExpMod1Entry 5 }
+
+airFMSysAlarmMapExpMod1LowSupplyTemp OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Exp Module 1 alarm map setting for Low Supply
+ Temperature.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapExpMod1Entry 6 }
+
+airFMSysAlarmMapExpMod1HumFail OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Exp Module 1 alarm map setting for Humidifier Failure.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapExpMod1Entry 7 }
+
+airFMSysAlarmMapExpMod1HumReplCyl OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Exp Module 1 alarm map setting for Humidifier Replace
+ Cylinder.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapExpMod1Entry 8 }
+
+airFMSysAlarmMapExpMod1CondPumpFail OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Exp Module 1 alarm map setting for Condensate Pump
+ Failure.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapExpMod1Entry 9 }
+
+airFMSysAlarmMapExpMod1BlwrCntl1Fail OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Exp Module 1 alarm map setting for Blower Controller 1
+ Failure.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapExpMod1Entry 10 }
+
+airFMSysAlarmMapExpMod1BlwrCntl2Fail OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Exp Module 1 alarm map setting for Blower Controller 2
+ Failure.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapExpMod1Entry 11 }
+
+airFMSysAlarmMapExpMod1HighFltrDP OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Exp Module 1 alarm map setting for High Filter
+ Differential Pressure.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapExpMod1Entry 12 }
+
+airFMSysAlarmMapExpMod1LowAirFlow OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Exp Module 1 alarm map setting for Low Air Flow.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapExpMod1Entry 13 }
+
+airFMSysAlarmMapExpMod1AirBlckIntOpen OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Exp Module 1 alarm map setting for Air Block Interlock
+ Open.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapExpMod1Entry 14 }
+
+airFMSysAlarmMapExpMod1WaterDetected OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Exp Module 1 alarm map setting for Water Detected.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapExpMod1Entry 15 }
+
+-- airFM Expansion Module 2 Output Alarm Mapping
+
+airFMSysAlarmMapExpMod2TableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the
+ airFMSysAlarmMapExpMod2Table."
+ ::= { airFMSysAlarmMapExpMod2 1 }
+
+airFMSysAlarmMapExpMod2Table OBJECT-TYPE
+ SYNTAX SEQUENCE OF AirFMSysAlarmMapExpMod2Entry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting alarm map information."
+ ::= { airFMSysAlarmMapExpMod2 2 }
+
+airFMSysAlarmMapExpMod2Entry OBJECT-TYPE
+ SYNTAX AirFMSysAlarmMapExpMod2Entry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The expansion module 2 alarm map type to reference."
+ INDEX { airFMSysAlarmMapExpMod2OutputIndex }
+ ::= { airFMSysAlarmMapExpMod2Table 1 }
+
+AirFMSysAlarmMapExpMod2Entry ::=
+ SEQUENCE {
+ airFMSysAlarmMapExpMod2OutputIndex INTEGER,
+ airFMSysAlarmMapExpMod2AnyAlarm INTEGER,
+ airFMSysAlarmMapExpMod2MaintReq INTEGER,
+ airFMSysAlarmMapExpMod2CoolFail INTEGER,
+ airFMSysAlarmMapExpMod2HighSupplyTemp INTEGER,
+ airFMSysAlarmMapExpMod2LowSupplyTemp INTEGER,
+ airFMSysAlarmMapExpMod2HumFail INTEGER,
+ airFMSysAlarmMapExpMod2HumReplCyl INTEGER,
+ airFMSysAlarmMapExpMod2CondPumpFail INTEGER,
+ airFMSysAlarmMapExpMod2BlwrCntl1Fail INTEGER,
+ airFMSysAlarmMapExpMod2BlwrCntl2Fail INTEGER,
+ airFMSysAlarmMapExpMod2HighFltrDP INTEGER,
+ airFMSysAlarmMapExpMod2LowAirFlow INTEGER,
+ airFMSysAlarmMapExpMod2AirBlckIntOpen INTEGER,
+ airFMSysAlarmMapExpMod2WaterDetected INTEGER
+ }
+
+airFMSysAlarmMapExpMod2OutputIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of the output relay."
+ ::= { airFMSysAlarmMapExpMod2Entry 1 }
+
+airFMSysAlarmMapExpMod2AnyAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Exp Module 2 alarm map setting for Any Alarm.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapExpMod2Entry 2 }
+
+airFMSysAlarmMapExpMod2MaintReq OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Exp Module 2 alarm map setting for Module Maintenance
+ Required.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapExpMod2Entry 3 }
+
+airFMSysAlarmMapExpMod2CoolFail OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Exp Module 2 alarm map setting for Module Cooling
+ Failure.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapExpMod2Entry 4 }
+
+airFMSysAlarmMapExpMod2HighSupplyTemp OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Exp Module 2 alarm map setting for High Supply
+ Temperature.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapExpMod2Entry 5 }
+
+airFMSysAlarmMapExpMod2LowSupplyTemp OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Exp Module 2 alarm map setting for Low Supply
+ Temperature.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapExpMod2Entry 6 }
+
+airFMSysAlarmMapExpMod2HumFail OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Exp Module 2 alarm map setting for Humidifier Failure.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapExpMod2Entry 7 }
+
+airFMSysAlarmMapExpMod2HumReplCyl OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Exp Module 2 alarm map setting for Humidifier Replace
+ Cylinder.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapExpMod2Entry 8 }
+
+airFMSysAlarmMapExpMod2CondPumpFail OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Exp Module 2 alarm map setting for Condensate Pump
+ Failure.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapExpMod2Entry 9 }
+
+airFMSysAlarmMapExpMod2BlwrCntl1Fail OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Exp Module 2 alarm map setting for Blower Controller 1
+ Failure.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapExpMod2Entry 10 }
+
+airFMSysAlarmMapExpMod2BlwrCntl2Fail OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Exp Module 2 alarm map setting for Blower Controller 2
+ Failure.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapExpMod2Entry 11 }
+
+airFMSysAlarmMapExpMod2HighFltrDP OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Exp Module 2 alarm map setting for High Filter
+ Differential Pressure.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapExpMod2Entry 12 }
+
+airFMSysAlarmMapExpMod2LowAirFlow OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Exp Module 2 alarm map setting for Low Air Flow.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapExpMod2Entry 13 }
+
+airFMSysAlarmMapExpMod2AirBlckIntOpen OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Exp Module 2 alarm map setting for Air Block Interlock
+ Open.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapExpMod2Entry 14 }
+
+airFMSysAlarmMapExpMod2WaterDetected OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Exp Module 2 alarm map setting for Water Detected.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapExpMod2Entry 15 }
+
+-- airFM Input Alarm Mapping
+
+airFMSysAlarmMapInputTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the airFMSysAlarmMapInputTable. "
+ ::= { airFMSysAlarmMapInput 1 }
+
+airFMSysAlarmMapInputTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AirFMSysAlarmMapInputEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting alarm map information."
+ ::= { airFMSysAlarmMapInput 2 }
+
+airFMSysAlarmMapInputEntry OBJECT-TYPE
+ SYNTAX AirFMSysAlarmMapInputEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The input contact alarm map type to reference."
+ INDEX { airFMSysAlarmMapInputOutputIndex }
+ ::= { airFMSysAlarmMapInputTable 1 }
+
+AirFMSysAlarmMapInputEntry ::=
+ SEQUENCE {
+ airFMSysAlarmMapInputOutputIndex INTEGER,
+ airFMSysAlarmMapInput1 INTEGER,
+ airFMSysAlarmMapInput2 INTEGER,
+ airFMSysAlarmMapInput3 INTEGER,
+ airFMSysAlarmMapInput4 INTEGER,
+ airFMSysAlarmMapInput5 INTEGER,
+ airFMSysAlarmMapInput6 INTEGER,
+ airFMSysAlarmMapInput7 INTEGER,
+ airFMSysAlarmMapInput8 INTEGER,
+ airFMSysAlarmMapInput9 INTEGER,
+ airFMSysAlarmMapInput10 INTEGER,
+ airFMSysAlarmMapInput11 INTEGER,
+ airFMSysAlarmMapInput12 INTEGER,
+ airFMSysAlarmMapInput13 INTEGER,
+ airFMSysAlarmMapInput14 INTEGER,
+ airFMSysAlarmMapInput15 INTEGER,
+ airFMSysAlarmMapInput16 INTEGER
+ }
+
+airFMSysAlarmMapInputOutputIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of the output relay."
+ ::= { airFMSysAlarmMapInputEntry 1 }
+
+airFMSysAlarmMapInput1 OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Input contact 1 alarm map setting.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapInputEntry 2 }
+
+airFMSysAlarmMapInput2 OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Input contact 2 alarm map setting.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapInputEntry 3 }
+
+airFMSysAlarmMapInput3 OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Input contact 3 alarm map setting.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapInputEntry 4 }
+
+airFMSysAlarmMapInput4 OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Input contact 4 alarm map setting.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapInputEntry 5 }
+
+airFMSysAlarmMapInput5 OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Input contact 5 alarm map setting.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapInputEntry 6 }
+
+airFMSysAlarmMapInput6 OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Input contact 6 alarm map setting.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapInputEntry 7 }
+
+airFMSysAlarmMapInput7 OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Input contact 7 alarm map setting.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapInputEntry 8 }
+
+airFMSysAlarmMapInput8 OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Input contact 8 alarm map setting.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapInputEntry 9 }
+
+airFMSysAlarmMapInput9 OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Input contact 9 alarm map setting.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapInputEntry 10 }
+
+airFMSysAlarmMapInput10 OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Input contact 10 alarm map setting.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapInputEntry 11 }
+
+airFMSysAlarmMapInput11 OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Input contact 11 alarm map setting.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapInputEntry 12 }
+
+airFMSysAlarmMapInput12 OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Input contact 12 alarm map setting.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapInputEntry 13 }
+
+airFMSysAlarmMapInput13 OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Input contact 13 alarm map setting.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapInputEntry 14 }
+
+airFMSysAlarmMapInput14 OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Input contact 14 alarm map setting.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapInputEntry 15 }
+
+airFMSysAlarmMapInput15 OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Input contact 15 alarm map setting.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapInputEntry 16 }
+
+airFMSysAlarmMapInput16 OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Input contact 16 alarm map setting.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapInputEntry 17 }
+
+-- airFM Output Alarm Mapping
+
+airFMSysAlarmMapOutputTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the
+ airFMSysAlarmMapOutputTable. "
+ ::= { airFMSysAlarmMapOutput 1 }
+
+airFMSysAlarmMapOutputTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AirFMSysAlarmMapOutputEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting alarm map information."
+ ::= { airFMSysAlarmMapOutput 2 }
+
+airFMSysAlarmMapOutputEntry OBJECT-TYPE
+ SYNTAX AirFMSysAlarmMapOutputEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The input contact alarm map type to reference."
+ INDEX { airFMSysAlarmMapOutputIndex }
+ ::= { airFMSysAlarmMapOutputTable 1 }
+
+AirFMSysAlarmMapOutputEntry ::=
+ SEQUENCE {
+ airFMSysAlarmMapOutputIndex INTEGER,
+ airFMSysAlarmMapOutput1 INTEGER,
+ airFMSysAlarmMapOutput2 INTEGER,
+ airFMSysAlarmMapOutput3 INTEGER,
+ airFMSysAlarmMapOutput4 INTEGER,
+ airFMSysAlarmMapOutput5 INTEGER,
+ airFMSysAlarmMapOutput6 INTEGER,
+ airFMSysAlarmMapOutput7 INTEGER,
+ airFMSysAlarmMapOutput8 INTEGER,
+ airFMSysAlarmMapOutput9 INTEGER,
+ airFMSysAlarmMapOutput10 INTEGER,
+ airFMSysAlarmMapOutput11 INTEGER,
+ airFMSysAlarmMapOutput12 INTEGER,
+ airFMSysAlarmMapOutput13 INTEGER,
+ airFMSysAlarmMapOutput14 INTEGER,
+ airFMSysAlarmMapOutput15 INTEGER,
+ airFMSysAlarmMapOutput16 INTEGER
+ }
+
+airFMSysAlarmMapOutputIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of the output relay."
+ ::= { airFMSysAlarmMapOutputEntry 1 }
+
+airFMSysAlarmMapOutput1 OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Output relay 1 alarm map setting.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapOutputEntry 2 }
+
+airFMSysAlarmMapOutput2 OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Output relay 2 alarm map setting.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapOutputEntry 3 }
+
+airFMSysAlarmMapOutput3 OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Output relay 3 alarm map setting.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapOutputEntry 4 }
+
+airFMSysAlarmMapOutput4 OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Output relay 4 alarm map setting.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapOutputEntry 5 }
+
+airFMSysAlarmMapOutput5 OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Output relay 5 alarm map setting.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapOutputEntry 6 }
+
+airFMSysAlarmMapOutput6 OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Output relay 6 alarm map setting.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapOutputEntry 7 }
+
+airFMSysAlarmMapOutput7 OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Output relay 7 alarm map setting.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapOutputEntry 8 }
+
+airFMSysAlarmMapOutput8 OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Output relay 8 alarm map setting.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapOutputEntry 9 }
+
+airFMSysAlarmMapOutput9 OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Output relay 9 alarm map setting.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapOutputEntry 10 }
+
+airFMSysAlarmMapOutput10 OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Output relay 10 alarm map setting.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapOutputEntry 11 }
+
+airFMSysAlarmMapOutput11 OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Output relay 11 alarm map setting.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapOutputEntry 12 }
+
+airFMSysAlarmMapOutput12 OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Output relay 12 alarm map setting.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapOutputEntry 13 }
+
+airFMSysAlarmMapOutput13 OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Output relay 13 alarm map setting.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapOutputEntry 14 }
+
+airFMSysAlarmMapOutput14 OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Output relay 14 alarm map setting.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapOutputEntry 15 }
+
+airFMSysAlarmMapOutput15 OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Output relay 15 alarm map setting.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapOutputEntry 16 }
+
+airFMSysAlarmMapOutput16 OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ disabled (2),
+ enabled (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Output relay 16 alarm map setting.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMSysAlarmMapOutputEntry 17 }
+
+-- airFM Module Identification Table
+
+airFMModIdentTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the airFMModIdentTable. "
+ ::= { airFMModIdent 1 }
+
+airFMModIdentTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AirFMModIdentEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting information from each module in
+ the system. "
+ ::= { airFMModIdent 2 }
+
+airFMModIdentEntry OBJECT-TYPE
+ SYNTAX AirFMModIdentEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The module to get information from."
+ INDEX { airFMModIdentModuleIndex }
+ ::= { airFMModIdentTable 1 }
+
+AirFMModIdentEntry ::=
+ SEQUENCE {
+ airFMModIdentModuleIndex INTEGER,
+ airFMModModelNumber DisplayString,
+ airFMModSerialNumber DisplayString,
+ airFMModManufactureDate DisplayString,
+ airFMModFirmwareRev DisplayString,
+ airFMModHardwareRev DisplayString
+ }
+
+airFMModIdentModuleIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of the module."
+ ::= { airFMModIdentEntry 1 }
+
+airFMModModelNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Model number of the Module."
+ ::= { airFMModIdentEntry 2 }
+
+airFMModSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unique identification number for this Module."
+ ::= { airFMModIdentEntry 3 }
+
+airFMModManufactureDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Date the Module was manufactured."
+ ::= { airFMModIdentEntry 4 }
+
+airFMModFirmwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Revision number of the firmware installed on this
+ Module."
+ ::= { airFMModIdentEntry 5 }
+
+airFMModHardwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Revision number of the hardware installed on this
+ Module."
+ ::= { airFMModIdentEntry 6 }
+
+-- airFM Module Status Table
+
+airFMModStatusTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the airFMModStatusTable. "
+ ::= { airFMModStatus 1 }
+
+airFMModStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AirFMModStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting information from each module in
+ the system. "
+ ::= { airFMModStatus 2 }
+
+airFMModStatusEntry OBJECT-TYPE
+ SYNTAX AirFMModStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The module to get information from."
+ INDEX { airFMModStatusModuleIndex }
+ ::= { airFMModStatusTable 1 }
+
+AirFMModStatusEntry ::=
+ SEQUENCE {
+ airFMModStatusModuleIndex INTEGER,
+ airFMModSupplyTempC INTEGER,
+ airFMModSupplyTempF INTEGER,
+ airFMModSupplyHum INTEGER,
+ airFMModReturnTempC INTEGER,
+ airFMModReturnTempF INTEGER,
+ airFMModReturnHum INTEGER,
+ airFMModFilterDiffPresPa INTEGER,
+ airFMModFilterDiffPresInWC INTEGER,
+ airFMModCoilDiffPresPa INTEGER,
+ airFMModCoilDiffPresInWC INTEGER
+ }
+
+airFMModStatusModuleIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of the module."
+ ::= { airFMModStatusEntry 1 }
+
+airFMModSupplyTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature measured at the supply sensor.
+ Measured in tenths of degrees Celsius.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModStatusEntry 2 }
+
+airFMModSupplyTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature measured at the supply sensor.
+ Measured in tenths of degrees Fahrenheit.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModStatusEntry 3 }
+
+airFMModSupplyHum OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The humidity measured at the supply sensor.
+ Measured in tenths of percent relative humidity.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModStatusEntry 4 }
+
+airFMModReturnTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature measured at the return sensor.
+ Measured in tenths of degrees Celsius.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModStatusEntry 5 }
+
+airFMModReturnTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature measured at the return sensor.
+ Measured in tenths of degrees Fahrenheit.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModStatusEntry 6 }
+
+airFMModReturnHum OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The humidity measured at the return sensor.
+ Measured in tenths of percent relative humidity.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModStatusEntry 7 }
+
+airFMModFilterDiffPresPa OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The difference in pressure on either side of the air
+ filters. A high differential pressure indicates a
+ clogged filter. Measured in Pascals.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModStatusEntry 8 }
+
+airFMModFilterDiffPresInWC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The difference in pressure on either side of the air
+ filters. A high differential pressure indicates a
+ clogged filter. Measured in hundredths of inches
+ water column.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModStatusEntry 9 }
+
+airFMModCoilDiffPresPa OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The difference in pressure on either side of the
+ cooling/dehumidification coils. Measured in Pascals.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModStatusEntry 10 }
+
+airFMModCoilDiffPresInWC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The difference in pressure on either side of the
+ cooling/dehumidification coils. Measured in
+ hundredths of inches water column.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModStatusEntry 11 }
+
+-- airFM Module Properties Table
+
+airFMModPropTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the airFMModPropTable. "
+ ::= { airFMModProperties 1 }
+
+airFMModPropTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AirFMModPropEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting information from each module in
+ the system. "
+ ::= { airFMModProperties 2 }
+
+airFMModPropEntry OBJECT-TYPE
+ SYNTAX AirFMModPropEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The module to get information from."
+ INDEX { airFMModPropModuleIndex }
+ ::= { airFMModPropTable 1 }
+
+AirFMModPropEntry ::=
+ SEQUENCE {
+ airFMModPropModuleIndex INTEGER,
+ airFMModOutputCapacity INTEGER,
+ airFMModCapacityCtrl INTEGER,
+ airFMModHeaterType INTEGER,
+ airFMModElectricHeaterType INTEGER,
+ airFMModHumidifierType INTEGER,
+ airFMModBlwrFreqSetting INTEGER,
+ airFMModNomCoilDiffPresPa INTEGER,
+ airFMModNomCoilDiffPresInWC INTEGER,
+ airFMModCondPump INTEGER,
+ airFMModFireDetector INTEGER,
+ airFMModSmokeDetector INTEGER,
+ airFMModWaterDetector INTEGER
+ }
+
+airFMModPropModuleIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of the module."
+ ::= { airFMModPropEntry 1 }
+
+airFMModOutputCapacity OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ kw45 (2),
+ kw35 (3),
+ kw40 (4),
+ kw50 (5),
+ kw80 (6)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The cooling capacity (in Kilowatts) of the displayed
+ Module.
+ A value of notApplicable indicates that this OID
+ does not apply to this device due to its configuration."
+ ::= { airFMModPropEntry 2 }
+
+airFMModCapacityCtrl OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ tandem (2),
+ hotGasBypass (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The method used to load and unload the compressors.
+ Tandem compressor Modules use two stages (one
+ compressor each). Single compressor Modules use hot
+ gas bypass.
+ A value of notApplicable indicates that this OID
+ does not apply to this device due to its configuration."
+ ::= { airFMModPropEntry 3 }
+
+airFMModHeaterType OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ none (2),
+ electricSCR (3),
+ steam (4),
+ hotWaterOnOff (5),
+ hotGasReheat (6),
+ hotGasAndElectric (7),
+ hotWaterProp (8)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The type of reheating device installed in this Module.
+ A value of notApplicable indicates that this OID
+ does not apply to this device due to its configuration."
+ ::= { airFMModPropEntry 4 }
+
+airFMModElectricHeaterType OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ kw10 (2),
+ kw15 (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The type/capacity of the electric heater, if installed.
+ A value of notApplicable indicates that this OID
+ does not apply to this device due to its configuration."
+ ::= { airFMModPropEntry 5 }
+
+airFMModHumidifierType OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ none (2),
+ steamElectrode (3),
+ liveSteam (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The type of equipment installed in the Module to run
+ the humidification mode.
+ A value of notApplicable indicates that this OID
+ does not apply to this device due to its configuration."
+ ::= { airFMModPropEntry 6 }
+
+airFMModBlwrFreqSetting OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Frequency of the blower in tenths of hertz.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModPropEntry 7 }
+
+airFMModNomCoilDiffPresPa OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The difference in pressure on either side of the
+ cooling/dehumidification coils. Measured in Pascals.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModPropEntry 8 }
+
+airFMModNomCoilDiffPresInWC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The difference in pressure on either side of the
+ cooling/dehumidification coils. Measured in
+ hundredths of inches water column.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModPropEntry 9 }
+
+airFMModCondPump OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ notPresent (2),
+ present (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the presence of a condensate pump in the
+ Modules of this System.
+ A value of notApplicable indicates that this OID
+ does not apply to this device due to its configuration."
+ ::= { airFMModPropEntry 10 }
+
+airFMModFireDetector OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ notPresent (2),
+ present (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the presence of a fire detector for each
+ of the Modules in this System.
+ A value of notApplicable indicates that this OID
+ does not apply to this device due to its configuration."
+ ::= { airFMModPropEntry 11 }
+
+airFMModSmokeDetector OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ notPresent (2),
+ present (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the presence of a smoke detector for each
+ of the Modules in this System.
+ A value of notApplicable indicates that this OID
+ does not apply to this device due to its configuration."
+ ::= { airFMModPropEntry 12 }
+
+airFMModWaterDetector OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ notPresent (2),
+ present (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the presence of a water leak detector for
+ each of the Modules in this System.
+ A value of notApplicable indicates that this OID
+ does not apply to this device due to its configuration."
+ ::= { airFMModPropEntry 13 }
+
+-- airFM Module Cooling Table
+
+airFMModCoolTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the airFMModCoolTable. "
+ ::= { airFMModCooling 1 }
+
+airFMModCoolTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AirFMModCoolEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting information from each module in
+ the system. "
+ ::= { airFMModCooling 2 }
+
+airFMModCoolEntry OBJECT-TYPE
+ SYNTAX AirFMModCoolEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The module to get information from."
+ INDEX { airFMModCoolModuleIndex }
+ ::= { airFMModCoolTable 1 }
+
+AirFMModCoolEntry ::=
+ SEQUENCE {
+ airFMModCoolModuleIndex INTEGER,
+ airFMModComp1 INTEGER,
+ airFMModComp2 INTEGER,
+ airFMModSuctPresKPa INTEGER,
+ airFMModSuctPresPSI INTEGER,
+ airFMModDischPresKPa INTEGER,
+ airFMModDischPresPSI INTEGER,
+ airFMModCondFluidVlvPos INTEGER,
+ airFMModCoilFluidVlvPos INTEGER
+ }
+
+airFMModCoolModuleIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of the module."
+ ::= { airFMModCoolEntry 1 }
+
+airFMModComp1 OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ on (2),
+ off (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of compressor 1 of the tandem compressor
+ unit (on or off).
+ A value of notApplicable indicates that this OID
+ does not apply to this device due to its configuration."
+ ::= { airFMModCoolEntry 2 }
+
+airFMModComp2 OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ on (2),
+ off (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of compressor 2 of the tandem compressor
+ unit (on or off).
+ A value of notApplicable indicates that this OID
+ does not apply to this device due to its configuration."
+ ::= { airFMModCoolEntry 3 }
+
+airFMModSuctPresKPa OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The refrigerant pressure measured at the suction
+ inlet of the compressor. Measured in kiloPascals.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModCoolEntry 4 }
+
+airFMModSuctPresPSI OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The refrigerant pressure measured at the suction
+ inlet of the compressor. Measured in pounds per
+ square inch.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModCoolEntry 5 }
+
+airFMModDischPresKPa OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The refrigerant pressure measured at the discharge
+ outlet of the compressor. Measured in kiloPascals.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModCoolEntry 6 }
+
+airFMModDischPresPSI OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The refrigerant pressure measured at the discharge
+ outlet of the compressor. Measured in pounds per
+ square inch.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModCoolEntry 7 }
+
+airFMModCondFluidVlvPos OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The position of the condenser fluid valve. The valve
+ regulates the flow of liquid coolant into the heat
+ exchanger (condenser). 100% indicates the valve is
+ completely open, and 0% indicates that the valve is
+ closed. Measured in percent.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModCoolEntry 8 }
+
+airFMModCoilFluidVlvPos OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The position of the coil fluid valve. The valve
+ regulates the flow of liquid coolant in the fluid
+ cooling coil (MultiCool, Economizer, or Chilled
+ Water). 100% indicates the valve is completely open,
+ and 0% indicates that the valve is closed. Measured
+ in percent.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModCoolEntry 9 }
+
+
+-- airFM Module Humidity Control Table
+
+airFMModHumTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the airFMModHumTable. "
+ ::= { airFMModHumidity 1 }
+
+airFMModHumTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AirFMModHumEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting information from each module in
+ the system. "
+ ::= { airFMModHumidity 2 }
+
+airFMModHumEntry OBJECT-TYPE
+ SYNTAX AirFMModHumEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The module to get information from."
+ INDEX { airFMModHumModuleIndex }
+ ::= { airFMModHumTable 1 }
+
+AirFMModHumEntry ::=
+ SEQUENCE {
+ airFMModHumModuleIndex INTEGER,
+ airFMModHumidifier INTEGER,
+ airFMModElectrodeCurrent INTEGER,
+ airFMModHumActualOutput INTEGER,
+ airFMModWaterConductivity INTEGER,
+ airFMModHotWaterVlvPos INTEGER,
+ airFMModStmElectHumMode INTEGER
+ }
+
+airFMModHumModuleIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of the module."
+ ::= { airFMModHumEntry 1 }
+
+airFMModHumidifier OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ none (2),
+ steamElectrode (3),
+ liveSteam (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The type of equipment installed in the Module to run
+ the humidification mode.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModHumEntry 2 }
+
+airFMModElectrodeCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current drawn by the electrodes of the steam
+ cylinder humidifier. Measured in tenths of amps.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModHumEntry 3 }
+
+airFMModHumActualOutput OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The humidification output of an individual Module.
+ Measured in percent.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModHumEntry 4 }
+
+airFMModWaterConductivity OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The conductivity of the water in the humidifier
+ cylinder. Measured in microSiemens per centimeter.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModHumEntry 5 }
+
+airFMModHotWaterVlvPos OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The position of the hot water valve. 100% indicates
+ the valve is completely open, and 0% indicates that
+ the valve is closed. Measured in percent.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModHumEntry 6 }
+
+airFMModStmElectHumMode OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ off (2),
+ auto (3),
+ drain (4)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Set the humidifier function mode.
+ Off: Remove power from electrodes.
+ Auto: Humidifier controlled by Module controller.
+ Drain: Remove power from electrodes and drain the cylinder.
+
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModHumEntry 7 }
+
+-- airFM Module Blower 1 Table
+
+airFMModBlwr1TableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the airFMModBlwr1Table. "
+ ::= { airFMModBlower1 1 }
+
+airFMModBlwr1Table OBJECT-TYPE
+ SYNTAX SEQUENCE OF AirFMModBlwr1Entry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting information from each module in
+ the system. "
+ ::= { airFMModBlower1 2 }
+
+airFMModBlwr1Entry OBJECT-TYPE
+ SYNTAX AirFMModBlwr1Entry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The module to get information from."
+ INDEX { airFMModBlwr1ModuleIndex }
+ ::= { airFMModBlwr1Table 1 }
+
+AirFMModBlwr1Entry ::=
+ SEQUENCE {
+ airFMModBlwr1ModuleIndex INTEGER,
+ airFMModBlwr1CtrlType INTEGER,
+ airFMModBlwr1CmdFreq INTEGER,
+ airFMModBlwr1ActFreq INTEGER,
+ airFMModBlwr1Poles INTEGER,
+ airFMModBlwr1RatedHorsePower INTEGER,
+ airFMModBlwr1RatedCurrent INTEGER,
+ airFMModBlwr1ActTorq INTEGER,
+ airFMModBlwr1Current INTEGER,
+ airFMModBlwr1Vlt INTEGER,
+ airFMModBlwr1DCLinkVlt INTEGER,
+ airFMModBlwr1AccTime INTEGER,
+ airFMModBlwr1DecTime INTEGER,
+ airFMModBlwr1CapLife INTEGER,
+ airFMModBlwr1CtrlCoolFanLife INTEGER,
+ airFMModBlwr1ElOvMode INTEGER,
+ airFMModBlwr1ElOvSetting INTEGER,
+ airFMModBlwr1ElOvTimeConst INTEGER,
+ airFMModBlwr1FanPower INTEGER,
+ airFMModBlwr1HeatsinkTempC INTEGER,
+ airFMModBlwr1HeatsinkTempF INTEGER,
+ airFMModBlwr1ChokeTempC INTEGER,
+ airFMModBlwr1ChokeTempF INTEGER,
+ airFMModBlwr1InverterTempC INTEGER,
+ airFMModBlwr1InverterTempF INTEGER
+ }
+
+airFMModBlwr1ModuleIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of the module."
+ ::= { airFMModBlwr1Entry 1 }
+
+airFMModBlwr1CtrlType OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ fujiVFD (2),
+ ecController (3),
+ danfossVFD (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The type of blower controller.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr1Entry 2 }
+
+airFMModBlwr1CmdFreq OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The requested operating frequency for the blower.
+ Measured in tenths of hertz.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr1Entry 3 }
+
+airFMModBlwr1ActFreq OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The frequency at which the blower controller is
+ operating. Measured in tenths of hertz.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr1Entry 4 }
+
+airFMModBlwr1Poles OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of poles of the blower motor that the
+ blower controller is controlling.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr1Entry 5 }
+
+airFMModBlwr1RatedHorsePower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The power rating of the blower motor. Measured in
+ hundredths of horsepower.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr1Entry 6 }
+
+airFMModBlwr1RatedCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current rating of the blower motor. Measured in
+ hundredths of amps.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr1Entry 7 }
+
+airFMModBlwr1ActTorq OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The actual torque of the blower motor. Measured in
+ hundredths of percent.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr1Entry 8 }
+
+airFMModBlwr1Current OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The percent of rated current drawn by the blower
+ motor. Measured in hundredths of percent.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr1Entry 9 }
+
+airFMModBlwr1Vlt OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The voltage supplied to the blower motor. Measured
+ in tenths of volts RMS.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr1Entry 10 }
+
+airFMModBlwr1DCLinkVlt OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The voltage of the blower controller's DC bus.
+ Measured in volts DC.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr1Entry 11 }
+
+airFMModBlwr1AccTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The time to accelerate the blower to the specified
+ frequency. Measured in tenths of seconds.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr1Entry 12 }
+
+airFMModBlwr1DecTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The time to decelerate the blower frequency to zero.
+ Measured in tenths of seconds.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr1Entry 13 }
+
+airFMModBlwr1CapLife OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The remaining life of the main circuit capacitor.
+ Measured in tenths of percent.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr1Entry 14 }
+
+airFMModBlwr1CtrlCoolFanLife OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The total operation time of the blower controller
+ cooling fan. Measured in hours.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr1Entry 15 }
+
+airFMModBlwr1ElOvMode OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ inactive (2),
+ active (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Enables or disables the electronic overload relay.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr1Entry 16 }
+
+airFMModBlwr1ElOvSetting OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The electronic overload relay is activated when the
+ current exceeds this threshold. Measured in
+ hundredths of amps.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr1Entry 17 }
+
+airFMModBlwr1ElOvTimeConst OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The delay between the current exceeding the overload
+ threshold and the activation of the electronic
+ overload relay. Measured in tenths of minutes.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr1Entry 18 }
+
+airFMModBlwr1FanPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The actual power of the blower motor. Measured in
+ tenths of percent.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr1Entry 19 }
+
+airFMModBlwr1HeatsinkTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature of the heatsink on the blower
+ controller. Measured in degrees Celsius.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr1Entry 20 }
+
+airFMModBlwr1HeatsinkTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature of the heatsink on the blower
+ controller. Measured in degrees Fahrenheit.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr1Entry 21 }
+
+airFMModBlwr1ChokeTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature of the choke on the blower
+ controller. Measured in degrees Celsius.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr1Entry 22 }
+
+airFMModBlwr1ChokeTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature of the choke on the blower
+ controller. Measured in degrees Fahrenheit.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr1Entry 23 }
+
+airFMModBlwr1InverterTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature of the inverter on the blower
+ controller. Measured in degrees Celsius.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr1Entry 24 }
+
+airFMModBlwr1InverterTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature of the inverter on the blower
+ controller. Measured in degrees Fahrenheit.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr1Entry 25 }
+
+
+-- airFM Module Blower 2 Table
+
+airFMModBlwr2TableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the airFMModBlwr2Table. "
+ ::= { airFMModBlower2 1 }
+
+airFMModBlwr2Table OBJECT-TYPE
+ SYNTAX SEQUENCE OF AirFMModBlwr2Entry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting information from each module in
+ the system. "
+ ::= { airFMModBlower2 2 }
+
+airFMModBlwr2Entry OBJECT-TYPE
+ SYNTAX AirFMModBlwr2Entry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The module to get information from."
+ INDEX { airFMModBlwr2ModuleIndex }
+ ::= { airFMModBlwr2Table 1 }
+
+AirFMModBlwr2Entry ::=
+ SEQUENCE {
+ airFMModBlwr2ModuleIndex INTEGER,
+ airFMModBlwr2CtrlType INTEGER,
+ airFMModBlwr2CmdFreq INTEGER,
+ airFMModBlwr2ActFreq INTEGER,
+ airFMModBlwr2Poles INTEGER,
+ airFMModBlwr2RatedHorsePower INTEGER,
+ airFMModBlwr2RatedCurrent INTEGER,
+ airFMModBlwr2ActTorq INTEGER,
+ airFMModBlwr2Current INTEGER,
+ airFMModBlwr2Vlt INTEGER,
+ airFMModBlwr2DCLinkVlt INTEGER,
+ airFMModBlwr2AccTime INTEGER,
+ airFMModBlwr2DecTime INTEGER,
+ airFMModBlwr2CapLife INTEGER,
+ airFMModBlwr2CtrlCoolFanLife INTEGER,
+ airFMModBlwr2ElOvMode INTEGER,
+ airFMModBlwr2ElOvSetting INTEGER,
+ airFMModBlwr2ElOvTimeConst INTEGER,
+ airFMModBlwr2FanPower INTEGER,
+ airFMModBlwr2HeatsinkTempC INTEGER,
+ airFMModBlwr2HeatsinkTempF INTEGER,
+ airFMModBlwr2ChokeTempC INTEGER,
+ airFMModBlwr2ChokeTempF INTEGER,
+ airFMModBlwr2InverterTempC INTEGER,
+ airFMModBlwr2InverterTempF INTEGER
+ }
+
+airFMModBlwr2ModuleIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of the module."
+ ::= { airFMModBlwr2Entry 1 }
+
+airFMModBlwr2CtrlType OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ fujiVFD (2),
+ ecController (3),
+ danfossVFD (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The type of blower controller.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr2Entry 2 }
+
+airFMModBlwr2CmdFreq OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The requested operating frequency for the blower.
+ Measured in tenths of hertz.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr2Entry 3 }
+
+airFMModBlwr2ActFreq OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The frequency at which the blower controller is
+ operating. Measured in tenths of hertz.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr2Entry 4 }
+
+airFMModBlwr2Poles OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of poles of the blower motor that the
+ blower controller is controlling.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr2Entry 5 }
+
+airFMModBlwr2RatedHorsePower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The power rating of the blower motor. Measured in
+ hundredths of horsepower.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr2Entry 6 }
+
+airFMModBlwr2RatedCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current rating of the blower motor. Measured in
+ hundredths of amps.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr2Entry 7 }
+
+airFMModBlwr2ActTorq OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The actual torque of the blower motor. Measured in
+ hundredths of percent.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr2Entry 8 }
+
+airFMModBlwr2Current OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The percent of rated current drawn by the blower
+ motor. Measured in hundredths of percent.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr2Entry 9 }
+
+airFMModBlwr2Vlt OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The voltage supplied to the blower motor. Measured
+ in tenths of volts RMS.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr2Entry 10 }
+
+airFMModBlwr2DCLinkVlt OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The voltage of the blower controller's DC bus.
+ Measured in volts DC.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr2Entry 11 }
+
+airFMModBlwr2AccTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The time to accelerate the blower to the specified
+ frequency. Measured in tenths of seconds.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr2Entry 12 }
+
+airFMModBlwr2DecTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The time to decelerate the blower frequency to zero.
+ Measured in tenths of seconds.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr2Entry 13 }
+
+airFMModBlwr2CapLife OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The remaining life of the main circuit capacitor.
+ Measured in tenths of percent.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr2Entry 14 }
+
+airFMModBlwr2CtrlCoolFanLife OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The total operation time of the blower controller
+ cooling fan. Measured in hours.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr2Entry 15 }
+
+airFMModBlwr2ElOvMode OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ inactive (2),
+ active (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Enables or disables the electronic overload relay.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr2Entry 16 }
+
+airFMModBlwr2ElOvSetting OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The electronic overload relay is activated when the
+ current exceeds this threshold. Measured in
+ hundredths of amps.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr2Entry 17 }
+
+airFMModBlwr2ElOvTimeConst OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The delay between the current exceeding the overload
+ threshold and the activation of the electronic
+ overload relay. Measured in tenths of minutes.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr2Entry 18 }
+
+airFMModBlwr2FanPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The actual power of the blower motor. Measured in
+ tenths of percent.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr2Entry 19 }
+
+airFMModBlwr2HeatsinkTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature of the heatsink on the blower
+ controller. Measured in degrees Celsius.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr2Entry 20 }
+
+airFMModBlwr2HeatsinkTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature of the heatsink on the blower
+ controller. Measured in degrees Fahrenheit.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr2Entry 21 }
+
+airFMModBlwr2ChokeTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature of the choke on the blower
+ controller. Measured in degrees Celsius.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr2Entry 22 }
+
+airFMModBlwr2ChokeTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature of the choke on the blower
+ controller. Measured in degrees Fahrenheit.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr2Entry 23 }
+
+airFMModBlwr2InverterTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature of the inverter on the blower
+ controller. Measured in degrees Celsius.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr2Entry 24 }
+
+airFMModBlwr2InverterTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature of the inverter on the blower
+ controller. Measured in degrees Fahrenheit.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModBlwr2Entry 25 }
+
+-- airFM Module Run Hours Table
+
+airFMModRHTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the airFMModRHTable. "
+ ::= { airFMModRunHours 1 }
+
+airFMModRHTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AirFMModRHEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting information from each module in
+ the system. "
+ ::= { airFMModRunHours 2 }
+
+airFMModRHEntry OBJECT-TYPE
+ SYNTAX AirFMModRHEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The module to get information from."
+ INDEX { airFMModRHModuleIndex }
+ ::= { airFMModRHTable 1 }
+
+AirFMModRHEntry ::=
+ SEQUENCE {
+ airFMModRHModuleIndex INTEGER,
+ airFMModRHComp1 INTEGER,
+ airFMModRHComp2 INTEGER,
+ airFMModRHHeater INTEGER,
+ airFMModRHHum INTEGER,
+ airFMModRHBlwr1 INTEGER,
+ airFMModRHBlwr2 INTEGER,
+ airFMModRHBlwrCtrl1 INTEGER,
+ airFMModRHBlwrCtrl2 INTEGER,
+ airFMModRHComp1Reset INTEGER,
+ airFMModRHComp2Reset INTEGER,
+ airFMModRHHeaterReset INTEGER,
+ airFMModRHHumReset INTEGER,
+ airFMModRHBlwr1Reset INTEGER,
+ airFMModRHBlwr2Reset INTEGER
+ }
+
+airFMModRHModuleIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of the module."
+ ::= { airFMModRHEntry 1 }
+
+airFMModRHComp1 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Compressor 1 run hours.
+ A value of -2147483648 indicates that this OID
+ does not apply to this device due to its configuration."
+ ::= { airFMModRHEntry 2 }
+
+airFMModRHComp2 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Compressor 2 run hours.
+ A value of -2147483648 indicates that this OID
+ does not apply to this device due to its configuration."
+ ::= { airFMModRHEntry 3 }
+
+airFMModRHHeater OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Heater run hours.
+ A value of -2147483648 indicates that this OID
+ does not apply to this device due to its configuration."
+ ::= { airFMModRHEntry 4 }
+
+airFMModRHHum OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Humidifier run hours
+ A value of -2147483648 indicates that this OID
+ does not apply to this device due to its configuration."
+ ::= { airFMModRHEntry 5 }
+
+airFMModRHBlwr1 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Blower 1 run hours.
+ A value of -2147483648 indicates that this OID
+ does not apply to this device due to its configuration."
+ ::= { airFMModRHEntry 6 }
+
+airFMModRHBlwr2 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Blower 2 run hours.
+ A value of -2147483648 indicates that this OID
+ does not apply to this device due to its configuration."
+ ::= { airFMModRHEntry 7 }
+
+airFMModRHBlwrCtrl1 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Blower Controller 1 run hours.
+ A value of -2147483648 indicates that this OID
+ does not apply to this device due to its configuration."
+ ::= { airFMModRHEntry 8 }
+
+airFMModRHBlwrCtrl2 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Blower Controller 2 run hours.
+ A value of -2147483648 indicates that this OID
+ does not apply to this device due to its configuration."
+ ::= { airFMModRHEntry 9 }
+
+airFMModRHComp1Reset OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ noOperation (2),
+ reset (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Reset the compressor 1 run hours.
+ Getting this OID will do nothing and return the
+ noOperation value.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModRHEntry 10 }
+
+airFMModRHComp2Reset OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ noOperation (2),
+ reset (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Reset the compressor 2 run hours.
+ Getting this OID will do nothing and return the
+ noOperation value.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModRHEntry 11 }
+
+airFMModRHHeaterReset OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ noOperation (2),
+ reset (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Reset the heater run hours.
+ Getting this OID will do nothing and return the
+ noOperation value.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModRHEntry 12 }
+
+airFMModRHHumReset OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ noOperation (2),
+ reset (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Reset the humidifier run hours.
+ Getting this OID will do nothing and return the
+ noOperation value.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModRHEntry 13 }
+
+airFMModRHBlwr1Reset OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ noOperation (2),
+ reset (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Reset the blower 1 run hours.
+ Getting this OID will do nothing and return the
+ noOperation value.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModRHEntry 14 }
+
+airFMModRHBlwr2Reset OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ noOperation (2),
+ reset (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Reset the blower 2 run hours.
+ Getting this OID will do nothing and return the
+ noOperation value.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModRHEntry 15 }
+
+-- airFM Module Service Intervals
+
+airFMModServIntComp1 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The interval at which to generate a maintenance alarm
+ for compressor 1. Values stored in increments of 100
+ hours.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModServIntervals 1 }
+
+airFMModServIntComp2 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The interval at which to generate a maintenance alarm
+ for compressor 2. Values stored in increments of 100
+ hours.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModServIntervals 2 }
+
+airFMModServIntHeater OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The interval at which to generate a maintenance alarm
+ for the reheat components. Values stored in
+ increments of 100 hours.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModServIntervals 3 }
+
+airFMModServIntHum OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The interval at which to generate a maintenance alarm
+ for the humidifier. Values stored in increments of
+ 100 hours.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModServIntervals 4 }
+
+airFMModServIntBlwr1 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The interval at which to generate a maintenance alarm
+ for blower 1. Values stored in increments of 100
+ hours.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModServIntervals 5 }
+
+airFMModServIntBlwr2 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The interval at which to generate a maintenance alarm
+ for blower 2. Values stored in increments of 100
+ hours.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModServIntervals 6 }
+
+airFMModServIntBlwrCtrl1 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The interval at which to generate a maintenance alarm
+ for blower controller 1. Values stored in increments
+ of 100 hours.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModServIntervals 7 }
+
+airFMModServIntBlwrCtrl2 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The interval at which to generate a maintenance alarm
+ for blower controller 2. Values stored in increments
+ of 100 hours.
+ A value of -2147483648 indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModServIntervals 8 }
+
+-- airFM Module Service Intervals Reset Table
+
+airFMModServIntResetTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the airFMModServIntTable. "
+ ::= { airFMModServIntResets 1 }
+
+airFMModServIntResetTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AirFMModServIntResetEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting information from each module in
+ the system. "
+ ::= { airFMModServIntResets 2 }
+
+airFMModServIntResetEntry OBJECT-TYPE
+ SYNTAX AirFMModServIntResetEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The module to get information from."
+ INDEX { airFMModServIntResetModuleIndex }
+ ::= { airFMModServIntResetTable 1 }
+
+AirFMModServIntResetEntry ::=
+ SEQUENCE {
+ airFMModServIntResetModuleIndex INTEGER,
+ airFMModServIntComp1Reset INTEGER,
+ airFMModServIntComp2Reset INTEGER,
+ airFMModServIntHeaterReset INTEGER,
+ airFMModServIntHumReset INTEGER,
+ airFMModServIntBlwr1Reset INTEGER,
+ airFMModServIntBlwr2Reset INTEGER,
+ airFMModServIntBlwrCtrl1Reset INTEGER,
+ airFMModServIntBlwrCtrl2Reset INTEGER
+ }
+
+airFMModServIntResetModuleIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of the module."
+ ::= { airFMModServIntResetEntry 1 }
+
+airFMModServIntComp1Reset OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ noOperation (2),
+ reset (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Reset the compressor 1 service interval maintenance
+ alarm.
+ Getting this OID will do nothing and return the
+ noOperation value.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModServIntResetEntry 2 }
+
+airFMModServIntComp2Reset OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ noOperation (2),
+ reset (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Reset the compressor 2 service interval maintenance
+ alarm.
+ Getting this OID will do nothing and return the
+ noOperation value.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModServIntResetEntry 3 }
+
+airFMModServIntHeaterReset OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ noOperation (2),
+ reset (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Reset the heater service interval maintenance alarm.
+ Getting this OID will do nothing and return the
+ noOperation value.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModServIntResetEntry 4 }
+
+airFMModServIntHumReset OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ noOperation (2),
+ reset (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Reset the humidifier service interval maintenance
+ alarm.
+ Getting this OID will do nothing and return the
+ noOperation value.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModServIntResetEntry 5 }
+
+airFMModServIntBlwr1Reset OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ noOperation (2),
+ reset (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Reset the blower 1 service interval maintenance
+ alarm.
+ Getting this OID will do nothing and return the
+ noOperation value.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModServIntResetEntry 6 }
+
+airFMModServIntBlwr2Reset OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ noOperation (2),
+ reset (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Reset the blower 2 service interval maintenance
+ alarm.
+ Getting this OID will do nothing and return the
+ noOperation value.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModServIntResetEntry 7 }
+
+airFMModServIntBlwrCtrl1Reset OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ noOperation (2),
+ reset (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Reset the blower controller 1 service interval
+ maintenance alarm.
+ Getting this OID will do nothing and return the
+ noOperation value.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModServIntResetEntry 8 }
+
+airFMModServIntBlwrCtrl2Reset OBJECT-TYPE
+ SYNTAX INTEGER {
+ notApplicable (1),
+ noOperation (2),
+ reset (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Reset the blower controller 2 service interval
+ maintenance alarm.
+ Getting this OID will do nothing and return the
+ noOperation value.
+ A value of notApplicable indicates that this OID does
+ not apply to this device due to its configuration."
+ ::= { airFMModServIntResetEntry 9 }
+
+-- airFM Alarms Table
+
+airFMAlarmClearActiveGroupAlarms OBJECT-TYPE
+ SYNTAX INTEGER {
+ noOperation (1),
+ clearAlarms (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Clear active group alarms. If alarm conditions are
+ still present, new alarms will be generated for those
+ conditions.
+ Getting this OID will do nothing and return the
+ noOperation value."
+ ::= { airFMAlarms 1 }
+
+airFMAlarmClearActiveSysModAlarms OBJECT-TYPE
+ SYNTAX INTEGER {
+ noOperation (1),
+ clearAlarms (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Clear active system and module alarms. If alarm
+ conditions are still present, new alarms will be
+ generated for those conditions.
+ Getting this OID will do nothing and return the
+ noOperation value."
+ ::= { airFMAlarms 2 }
+
+airFMAlarmConditionsTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of active alarm conditions in the
+ airFMAlarmConditionTable."
+ ::= { airFMAlarms 3 }
+
+airFMAlarmConditionsTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AirFMAlarmConditionsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Table of active alarm conditions for the device."
+ ::= { airFMAlarms 4 }
+
+airFMAlarmConditionsEntry OBJECT-TYPE
+ SYNTAX AirFMAlarmConditionsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "Alarm condition specification"
+ INDEX { airFMAlarmConditionsIndex }
+ ::= { airFMAlarmConditionsTable 1 }
+
+AirFMAlarmConditionsEntry ::= SEQUENCE {
+ airFMAlarmConditionsIndex INTEGER,
+ airFMAlarmSeverity INTEGER,
+ airFMAlarmType INTEGER,
+ airFMEventCode INTEGER,
+ airFMAlarmDate DisplayString,
+ airFMAlarmTime DisplayString,
+ airFMAlarmDescription DisplayString
+ }
+
+airFMAlarmConditionsIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Alarm condition index."
+ ::= { airFMAlarmConditionsEntry 1 }
+
+airFMAlarmSeverity OBJECT-TYPE
+ SYNTAX INTEGER {
+ informational (1),
+ warningMinor (2),
+ criticalMajor (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Severity of the alarm."
+ ::= { airFMAlarmConditionsEntry 2 }
+
+airFMAlarmType OBJECT-TYPE
+ SYNTAX INTEGER {
+ group (1),
+ system (2),
+ mainMod (3),
+ expMod1 (4),
+ expMod2 (5)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Type of alarm."
+ ::= { airFMAlarmConditionsEntry 3 }
+
+airFMEventCode OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "APC event code for the alarm."
+ ::= { airFMAlarmConditionsEntry 4 }
+
+airFMAlarmDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Date the alarm was recorded."
+ ::= { airFMAlarmConditionsEntry 5 }
+
+airFMAlarmTime OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Time the alarm was recorded."
+ ::= { airFMAlarmConditionsEntry 6 }
+
+airFMAlarmDescription OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..64))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Description of the alarm."
+ ::= { airFMAlarmConditionsEntry 7 }
+
+-- airPA Portable Air Conditioner Ident
+
+airPAIdentName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the device name."
+ ::= { airPAIdent 1 }
+
+airPAModelNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the device model number."
+ ::= { airPAIdent 2 }
+
+airPADateOfManufacture OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying when the device was produced."
+ ::= { airPAIdent 3 }
+
+airPASerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the device serial number."
+ ::= { airPAIdent 4 }
+
+airPAFirmwareRevision OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the device firmware revision."
+ ::= { airPAIdent 5 }
+
+airPAHardwareRevision OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the device hardware revision."
+ ::= { airPAIdent 6 }
+
+-- airPA Portable Air Conditioner Status
+
+airPASystemPower OBJECT-TYPE
+ SYNTAX INTEGER {
+ powerON (1),
+ powerOFF (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the unit's system power setting.
+
+ ON(1) The system power is turned on.
+ OFF(2) The system power is turned off. "
+ ::= { airPAStatus 1 }
+
+airPAOperatingMode OBJECT-TYPE
+ SYNTAX INTEGER {
+ modeOFF (1),
+ modeVENTING (2),
+ modeCOOLING (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current operating mode of the unit.
+
+ OFF(1) The system is off.
+ VENTING(2) The system's venting function is active.
+ COOLING(3) The system's cooling function is active. "
+ ::= { airPAStatus 2 }
+
+airPASetpointTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature setpoint in Fahrenheit to which the unit is controlling. "
+ ::= { airPAStatus 3 }
+
+airPASetpointTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature setpoint in Celsius to which the unity is controlling. "
+ ::= { airPAStatus 4 }
+
+airPABlowerSpeed OBJECT-TYPE
+ SYNTAX INTEGER {
+ speedLOW (1),
+ speedHIGH (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit's blower speed setting.
+
+ LOW(1) The blower speed is low.
+ HIGH(2) The blower speed is high. "
+ ::= { airPAStatus 5 }
+
+airPACompressor OBJECT-TYPE
+ SYNTAX INTEGER {
+ statusON (1),
+ statusOFF (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit's compressor status.
+
+ ON(1) The compressor is turned on.
+ OFF(2) The compressor is turned off. "
+ ::= { airPAStatus 6 }
+
+airPACondenserFan OBJECT-TYPE
+ SYNTAX INTEGER {
+ statusON (1),
+ statusOFF (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit's condenser fan status.
+
+ ON(1) The condenser fan is turned on.
+ OFF(2) The condenser fan is turned off. "
+ ::= { airPAStatus 7 }
+
+airPACondensatePump OBJECT-TYPE
+ SYNTAX INTEGER {
+ statusON (1),
+ statusOFF (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit's condensate pump status.
+
+ ON(1) The condensate pump is turned on.
+ OFF(2) The condensate pump is turned off. "
+ ::= { airPAStatus 8 }
+
+airPASupplyTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The supply temperature in degrees Fahrenheit. "
+ ::= { airPAStatus 9 }
+
+airPASupplyTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The supply temperature in degrees Celsius. "
+ ::= { airPAStatus 10 }
+
+airPAReturnTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The return temperature in degrees Fahrenheit. "
+ ::= { airPAStatus 11 }
+
+airPAReturnTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The return temperature in degrees Celsius. "
+ ::= { airPAStatus 12 }
+
+airPARemoteTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The remote temperature in degrees Fahrenheit. "
+ ::= { airPAStatus 13 }
+
+airPARemoteTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The remote temperature in degrees Celsius. "
+ ::= { airPAStatus 14 }
+
+airPARemoteHumidity OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The remote humidity. "
+ ::= { airPAStatus 15 }
+
+-- air InRow Air Conditioners
+-- airIR AIR CONDITIONER Alarm Status - shared across all IR products
+
+airIRAlarmConditionsTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of active alarm conditions in the airIRAlarmConditionTable."
+ ::= { airIRAlarms 1 }
+
+airIRAlarmConditionsTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AirIRAlarmConditionsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Table of active alarm conditions for the device."
+ ::= { airIRAlarms 2 }
+
+airIRAlarmConditionsEntry OBJECT-TYPE
+ SYNTAX AirIRAlarmConditionsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "Alarm condition specification"
+ INDEX { airIRAlarmConditionsIndex }
+ ::= { airIRAlarmConditionsTable 1 }
+
+AirIRAlarmConditionsEntry ::= SEQUENCE {
+ airIRAlarmConditionsIndex INTEGER,
+ airIREventCode INTEGER,
+ airIRAlarmDescription DisplayString
+ }
+
+airIRAlarmConditionsIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Alarm condition index."
+ ::= { airIRAlarmConditionsEntry 1 }
+
+airIREventCode OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Code for the alarm."
+ ::= { airIRAlarmConditionsEntry 2 }
+
+airIRAlarmDescription OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..64))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Description of the alarm."
+ ::= { airIRAlarmConditionsEntry 3 }
+
+-- airIRRC AIR CONDITIONER Group Status
+
+airIRRCGroupStatusCoolOutput OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Group coolant output in tenths of kW."
+ ::= { airIRRCGroupStatus 1 }
+
+airIRRCGroupStatusCoolDemand OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Group coolant demand in tenths of kW."
+ ::= { airIRRCGroupStatus 2 }
+
+airIRRCGroupStatusAirFlowUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Group air flow in cubic feet per minute."
+ ::= { airIRRCGroupStatus 3 }
+
+airIRRCGroupStatusAirFlowMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Group air flow in liters per second."
+ ::= { airIRRCGroupStatus 4 }
+
+airIRRCGroupStatusMaxRackInletTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Group maximum rack inlet temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRRCGroupStatus 5 }
+
+airIRRCGroupStatusMaxRackInletTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Group maximum rack inlet temperature in tenths of
+ degrees Celsius."
+ ::= { airIRRCGroupStatus 6 }
+
+airIRRCGroupStatusMinRackInletTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Group minimum rack inlet temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRRCGroupStatus 7 }
+
+airIRRCGroupStatusMinRackInletTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Group minimum rack inlet temperature in tenths of
+ degrees Celsius."
+ ::= { airIRRCGroupStatus 8 }
+
+airIRRCGroupStatusActiveFlowControlStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ under (1),
+ okay (2),
+ over (3),
+ notApplicable (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Status of the active flow control
+ system."
+ ::= { airIRRCGroupStatus 9 }
+
+
+-- airIRRC AIR CONDITIONER Group Setpoints
+
+airIRRCGroupSetpointsCoolUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Group cooling setpoint in tenths of
+ degrees Fahrenheit."
+ ::= { airIRRCGroupSetpoints 1 }
+
+airIRRCGroupSetpointsCoolMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Group cooling setpoint in tenths of
+ degrees Celsius."
+ ::= { airIRRCGroupSetpoints 2 }
+
+airIRRCGroupSetpointsSupplyAirUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Group supply air setpoint in tenths of
+ degrees Fahrenheit."
+ ::= { airIRRCGroupSetpoints 3 }
+
+airIRRCGroupSetpointsSupplyAirMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Group supply air setpoint in tenths of
+ degrees Celsius."
+ ::= { airIRRCGroupSetpoints 4 }
+
+airIRRCGroupSetpointsFanSpeedPreference OBJECT-TYPE
+ SYNTAX INTEGER {
+ low (1),
+ med-low (2),
+ med (3),
+ med-high (4),
+ high (5)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The preferred fan speed setting."
+ ::= { airIRRCGroupSetpoints 5 }
+
+airIRRCGroupSetpointsFanSpeedControl OBJECT-TYPE
+ SYNTAX INTEGER {
+ automatic (1),
+ manual (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The fan speed control setting.
+ Automatic(1) - controller manages fan speed.
+ Manual(2) - fan speed is fixed and set by the fan speed preference.
+ See airIRRCGroupSetpointsFanSpeedPreference."
+ ::= { airIRRCGroupSetpoints 6 }
+
+airIRRCGroupSetpointsActiveFlowControlBias OBJECT-TYPE
+ SYNTAX INTEGER {
+ positive (1),
+ slightlyPositive (2),
+ zero (3),
+ slightlyNegative (4),
+ negative (5)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The active flow control bias setting."
+ ::= { airIRRCGroupSetpoints 7 }
+
+-- airIRRC AIR CONDITIONER Group Config
+
+airIRRCGroupConfigNumberofCoolingUnits OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The number of cooling units present in the group."
+ ::= { airIRRCGroupConfig 1 }
+
+airIRRCGroupConfigConfigurationType OBJECT-TYPE
+ SYNTAX INTEGER {
+ racs (1),
+ hacs (2),
+ in-row (3),
+ cacs (4)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The group configuration type."
+ ::= { airIRRCGroupConfig 2 }
+
+airIRRCGroupConfigPctGlycol OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The glycol mixture in percent."
+ ::= { airIRRCGroupConfig 3 }
+
+airIRRCGroupConfigCoolGainP OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The gain component of the PID in hundredths."
+ ::= { airIRRCGroupConfig 4 }
+
+airIRRCGroupConfigCoolResetRateI OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The integral component of the PID in hundredths."
+ ::= { airIRRCGroupConfig 5 }
+
+airIRRCGroupConfigCoolDerivativeD OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The derivative component of the PID in hundredths."
+ ::= { airIRRCGroupConfig 6 }
+
+airIRRCGroupConfigMaxFanSpeed OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum desired fan speed setting in percent."
+ ::= { airIRRCGroupConfig 7 }
+
+airIRRCGroupConfigNumberOfActiveFlowControllers OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The number of active flow controllers
+ present in the group."
+ ::= { airIRRCGroupConfig 8 }
+
+airIRRCGroupConfigActiveFlowControllerLampTest OBJECT-TYPE
+ SYNTAX INTEGER {
+ off (1),
+ on (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Turns off/on the active flow
+ controller lamp test."
+ ::= { airIRRCGroupConfig 9 }
+
+airIRRCGroupConfigAltitudeUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The group altitude of the units above sea level in feet."
+ ::= { airIRRCGroupConfig 10 }
+
+airIRRCGroupConfigAltitudeMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The group altitude of the units above sea level in meters."
+ ::= { airIRRCGroupConfig 11 }
+
+-- airIRRC AIR CONDITIONER UNIT Status
+
+airIRRCUnitStatusOperateMode OBJECT-TYPE
+ SYNTAX INTEGER {
+ standby (1),
+ on (2),
+ idle (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The cooling unit operating mode."
+ ::= { airIRRCUnitStatus 1 }
+
+airIRRCUnitStatusCoolOutput OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit cooling output in tenths of kW."
+ ::= { airIRRCUnitStatus 2 }
+
+airIRRCUnitStatusCoolDemand OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit cooling demand in tenths of kW."
+ ::= { airIRRCUnitStatus 3 }
+
+airIRRCUnitStatusAirFlowUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit air flow in cubic feet per minute."
+ ::= { airIRRCUnitStatus 4 }
+
+airIRRCUnitStatusAirFlowMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit air flow in hundredths of
+ liters per second."
+ ::= { airIRRCUnitStatus 5 }
+
+airIRRCUnitStatusRackInletTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit rack inlet temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRRCUnitStatus 6 }
+
+airIRRCUnitStatusRackInletTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit rack inlet temperature in tenths of
+ degrees Celsius."
+ ::= { airIRRCUnitStatus 7 }
+
+airIRRCUnitStatusSupplyAirTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit supply air temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRRCUnitStatus 8 }
+
+airIRRCUnitStatusSupplyAirTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit supply air temperature in tenths of
+ degrees Celsius."
+ ::= { airIRRCUnitStatus 9 }
+
+airIRRCUnitStatusReturnAirTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit return air temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRRCUnitStatus 10 }
+
+airIRRCUnitStatusReturnAirTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit return air temperature in tenths of
+ degrees Celsius."
+ ::= { airIRRCUnitStatus 11 }
+
+airIRRCUnitStatusContainmtDPUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit containment differential pressure in
+ hundredths of inches of water."
+ ::= { airIRRCUnitStatus 12 }
+
+airIRRCUnitStatusContainmtDPMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit containment differential pressure in Pa."
+ ::= { airIRRCUnitStatus 13 }
+
+airIRRCUnitStatusFilterDPUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit air filter differential pressure in
+ hundredths of inches of water."
+ ::= { airIRRCUnitStatus 14 }
+
+airIRRCUnitStatusFilterDPMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit air filter differential pressure in Pa."
+ ::= { airIRRCUnitStatus 15 }
+
+airIRRCUnitStatusFanSpeed OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit average fan speed in tenths of percent."
+ ::= { airIRRCUnitStatus 16 }
+
+airIRRCUnitStatusInputState OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The state of the input contact."
+ ::= { airIRRCUnitStatus 17 }
+
+airIRRCUnitStatusOutputState OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The state of the output relay."
+ ::= { airIRRCUnitStatus 18 }
+
+airIRRCUnitStatusActivePowerSource OBJECT-TYPE
+ SYNTAX INTEGER {
+ sourceA (1),
+ sourceB (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The power source that is powering the unit."
+ ::= { airIRRCUnitStatus 19 }
+
+airIRRCUnitStatusFluidValvePosition OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The fluid valve position in percent open."
+ ::= { airIRRCUnitStatus 20 }
+
+airIRRCUnitStatusFluidFlowUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The fluid flow in tenths of gallons per minute."
+ ::= { airIRRCUnitStatus 21 }
+
+airIRRCUnitStatusFluidFlowMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The fluid flow in hundredths of liters per second."
+ ::= { airIRRCUnitStatus 22 }
+
+airIRRCUnitStatusEnteringFluidTemperatureUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature of the entering fluid in
+ tenths of degrees Fahrenheit."
+ ::= { airIRRCUnitStatus 23 }
+
+airIRRCUnitStatusEnteringFluidTemperatureMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature of the entering fluid in
+ tenths of degrees Celsius."
+ ::= { airIRRCUnitStatus 24 }
+
+airIRRCUnitStatusLeavingFluidTemperatureUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature of the Leaving fluid in
+ tenths of degrees Fahrenheit."
+ ::= { airIRRCUnitStatus 25 }
+
+airIRRCUnitStatusLeavingFluidTemperatureMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature of the Leaving fluid in
+ tenths of degrees Celsius."
+ ::= { airIRRCUnitStatus 26 }
+
+airIRRCUnitStatusLeakSensor OBJECT-TYPE
+ SYNTAX INTEGER {
+ no-leak (1),
+ leak (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The state (no-leak/leak) of the leak sensor."
+ ::= { airIRRCUnitStatus 27 }
+
+-- airIRRC AIR CONDITIONER UNIT Ident
+
+airIRRCUnitIdentID OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The unit identification number."
+ ::= { airIRRCUnitIdent 1 }
+
+airIRRCUnitIdentName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the
+ unit name."
+ ::= { airIRRCUnitIdent 2 }
+
+airIRRCUnitIdentLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the
+ unit location."
+ ::= { airIRRCUnitIdent 3 }
+
+airIRRCUnitIdentModelNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the
+ unit model number."
+ ::= { airIRRCUnitIdent 4 }
+
+airIRRCUnitIdentSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the
+ unit serial number."
+ ::= { airIRRCUnitIdent 5 }
+
+airIRRCUnitIdentFirmwareRevision OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the
+ unit firmware version."
+ ::= { airIRRCUnitIdent 6 }
+
+airIRRCUnitIdentHardwareRevision OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the
+ unit controller hardware revision."
+ ::= { airIRRCUnitIdent 7 }
+
+airIRRCUnitIdentManufactureDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the
+ unit manufacture date."
+ ::= { airIRRCUnitIdent 8 }
+
+
+-- airIRRC AIR CONDITIONER UNIT Runhours
+
+airIRRCUnitRunHoursAirFilter OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit air filter run hours."
+ ::= { airIRRCUnitRunHours 1 }
+
+airIRRCUnitRunHoursFan1 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit fan 1 run hours."
+ ::= { airIRRCUnitRunHours 2 }
+
+airIRRCUnitRunHoursFan2 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit fan 2 run hours."
+ ::= { airIRRCUnitRunHours 3 }
+
+airIRRCUnitRunHoursFan3 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit fan 3 run hours."
+ ::= { airIRRCUnitRunHours 4 }
+
+airIRRCUnitRunHoursFan4 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit fan 4 run hours."
+ ::= { airIRRCUnitRunHours 5 }
+
+airIRRCUnitRunHoursFan5 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit fan 5 run hours."
+ ::= { airIRRCUnitRunHours 6 }
+
+airIRRCUnitRunHoursFan6 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit fan 6 run hours."
+ ::= { airIRRCUnitRunHours 7 }
+
+airIRRCUnitRunHoursFan7 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit fan 7 run hours."
+ ::= { airIRRCUnitRunHours 8}
+
+airIRRCUnitRunHoursFan8 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit fan 8 run hours."
+ ::= { airIRRCUnitRunHours 9 }
+
+airIRRCUnitRunHoursFanPowerSupplyLeft OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit fan left power supply run hours."
+ ::= { airIRRCUnitRunHours 10 }
+
+airIRRCUnitRunHoursFanPowerSupplyRight OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit fan right power supply run hours."
+ ::= { airIRRCUnitRunHours 11 }
+
+airIRRCUnitRunHoursCondensatePump OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit condensate pump run hours."
+ ::= { airIRRCUnitRunHours 12 }
+
+airIRRCUnitRunHoursFanPowerSupplyFeedALeft OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit fan, DC power feed A, left power supply run hours.
+ This is only valid for a DC input unit."
+ ::= { airIRRCUnitRunHours 13 }
+
+airIRRCUnitRunHoursFanPowerSupplyFeedARight OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit fan, DC power feed A, right power supply run hours.
+ This is only valid for a DC input unit."
+ ::= { airIRRCUnitRunHours 14 }
+
+airIRRCUnitRunHoursFanPowerSupplyFeedBLeft OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit fan, DC power feed B, left power supply run hours.
+ This is only valid for a DC input unit."
+ ::= { airIRRCUnitRunHours 15 }
+
+airIRRCUnitRunHoursFanPowerSupplyFeedBRight OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit fan, DC power feed B, right power supply run hours.
+ This is only valid for a DC input unit."
+ ::= { airIRRCUnitRunHours 16 }
+
+-- airIRRC AIR CONDITIONER UNIT Service Intervals
+
+airIRRCUnitServiceIntervalsAirFilter OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Air filter service interval in weeks."
+ ::= { airIRRCUnitServiceIntervals 1 }
+
+airIRRCUnitServiceIntervalsAirFilterAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ enable (1),
+ disable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The air filter service interval alarm enable/disable."
+ ::= { airIRRCUnitServiceIntervals 2 }
+
+
+-- airIRRC AIR CONDITIONER UNIT Thresholds
+
+airIRRCUnitThresholdsRackInletHighTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unit rack inlet air high temperature threshold in
+ tenths of degrees Fahrenheit."
+ ::= { airIRRCUnitThresholds 1 }
+
+airIRRCUnitThresholdsRackInletHighTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unit rack inlet air high temperature threshold in
+ tenths of degrees Celsius."
+ ::= { airIRRCUnitThresholds 2 }
+
+airIRRCUnitThresholdsSupplyAirHighTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unit supply air high temperature threshold in
+ tenths of degrees Fahrenheit."
+ ::= { airIRRCUnitThresholds 3 }
+
+airIRRCUnitThresholdsSupplyAirHighTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unit supply air high temperature threshold in
+ tenths of degrees Celsius."
+ ::= { airIRRCUnitThresholds 4 }
+
+airIRRCUnitThresholdsReturnAirHighTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unit return air high temperature threshold in
+ tenths of degrees Fahrenheit."
+ ::= { airIRRCUnitThresholds 5 }
+
+airIRRCUnitThresholdsReturnAirHighTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unit return air high temperature threshold in
+ tenths of degrees Celsius."
+ ::= { airIRRCUnitThresholds 6 }
+
+airIRRCUnitThresholdsEnteringFluidHighTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unit entering fluid high temperature threshold in
+ tenths of degrees Fahrenheit."
+ ::= { airIRRCUnitThresholds 7 }
+
+airIRRCUnitThresholdsEnteringFluidHighTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unit incoming fluid high temperature threshold in
+ tenths of degrees Celsius."
+ ::= { airIRRCUnitThresholds 8 }
+
+
+-- airIRRC AIR CONDITIONER UNIT Config
+
+airIRRCUnitConfigCoolCapacity OBJECT-TYPE
+ SYNTAX INTEGER {
+ automatic (1),
+ maximum (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The cooling capacity options setting."
+ ::= { airIRRCUnitConfig 1 }
+
+airIRRCUnitConfigStartupDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The startup delay in seconds."
+ ::= { airIRRCUnitConfig 2 }
+
+airIRRCUnitConfigIdleOnLeakDetect OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The idle on leak options setting."
+ ::= { airIRRCUnitConfig 3 }
+
+airIRRCUnitConfigPowerSource OBJECT-TYPE
+ SYNTAX INTEGER {
+ sourceA (1),
+ sourceB (2),
+ sourceAandB (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The configured power source of the unit."
+ ::= { airIRRCUnitConfig 4 }
+
+airIRRCUnitConfigInputNormalState OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The normal state of the input contact."
+ ::= { airIRRCUnitConfig 5 }
+
+airIRRCUnitConfigOutputNormalState OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The normal state of the output relay."
+ ::= { airIRRCUnitConfig 6 }
+
+airIRRCUnitConfigOutputSource OBJECT-TYPE
+ SYNTAX INTEGER {
+ anyAlarm (1),
+ criticalAlarm (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The source of output relay change."
+ ::= { airIRRCUnitConfig 7 }
+
+airIRRCUnitConfigIdleOnCoolFail OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The idle on cool fail options setting.
+ If yes, the system will go into idle mode
+ when a cooling failure is detected.
+ If no, the system will not go into idle mode
+ when a cooling failure is detected. "
+ ::= { airIRRCUnitConfig 8 }
+
+
+-- airIRRP100 AIR CONDITIONER Group Status
+
+airIRRP100GroupStatusAirFlowUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Group air flow in cubic feet per minute."
+ ::= { airIRRP100GroupStatus 1 }
+
+airIRRP100GroupStatusAirFlowMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Group air flow in liters per second."
+ ::= { airIRRP100GroupStatus 2 }
+
+airIRRP100GroupStatusMaxRackInletTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Group maximum rack inlet temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRRP100GroupStatus 3 }
+
+airIRRP100GroupStatusMaxRackInletTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Group maximum rack inlet temperature in tenths of
+ degrees Celsius."
+ ::= { airIRRP100GroupStatus 4 }
+
+airIRRP100GroupStatusMinRackInletTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Group minimum rack inlet temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRRP100GroupStatus 5 }
+
+airIRRP100GroupStatusMinRackInletTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Group minimum rack inlet temperature in tenths of
+ degrees Celsius."
+ ::= { airIRRP100GroupStatus 6 }
+
+airIRRP100GroupStatusCoolDemand OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Group coolant demand in tenths of kiloWatts."
+ ::= { airIRRP100GroupStatus 7 }
+
+airIRRP100GroupStatusCoolOutput OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Group coolant output in tenths of kiloWatts."
+ ::= { airIRRP100GroupStatus 8 }
+
+airIRRP100GroupStatusHumidifyDemand OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The amount of humidification the group is demanding
+ from the humidifiers in percent."
+ ::= { airIRRP100GroupStatus 9 }
+
+airIRRP100GroupStatusHumidifyOutput OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The actual amount of humidification the group is
+ supplying in percent."
+ ::= { airIRRP100GroupStatus 10 }
+
+airIRRP100GroupStatusDehumidifyDemand OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The amount of dehumidification the group is demanding
+ from the electric heaters in percent."
+ ::= { airIRRP100GroupStatus 11 }
+
+airIRRP100GroupStatusDehumidifyOutput OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The actual amount of dehumidification the group is
+ supplying in percent."
+ ::= { airIRRP100GroupStatus 12 }
+
+airIRRP100GroupStatusReheatDemand OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The amount of heating the group is demanding
+ from the electric heaters in percent."
+ ::= { airIRRP100GroupStatus 13 }
+
+airIRRP100GroupStatusReheatOutput OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The actual amount of heating the group is
+ supplying in percent."
+ ::= { airIRRP100GroupStatus 14 }
+
+airIRRP100GroupStatusActiveFlowControlStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ under (1),
+ okay (2),
+ over (3),
+ notApplicable (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Status of the active flow control
+ system."
+ ::= { airIRRP100GroupStatus 15 }
+
+airIRRP100GroupStatusDewPointTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Group average dew point temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRRP100GroupStatus 16 }
+
+airIRRP100GroupStatusDewPointTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Group average dew point temperature in tenths of
+ degrees Celsius."
+ ::= { airIRRP100GroupStatus 17 }
+
+
+-- airIRRP100 AIR CONDITIONER Group Setpoints
+
+airIRRP100GroupSetpointsCoolUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Group cooling setpoint in tenths of
+ degrees Fahrenheit."
+ ::= { airIRRP100GroupSetpoints 1 }
+
+airIRRP100GroupSetpointsCoolMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Group cooling setpoint in tenths of
+ degrees Celsius."
+ ::= { airIRRP100GroupSetpoints 2 }
+
+airIRRP100GroupSetpointsSupplyAirUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Group supply air setpoint in tenths of
+ degrees Fahrenheit."
+ ::= { airIRRP100GroupSetpoints 3 }
+
+airIRRP100GroupSetpointsSupplyAirMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Group supply air setpoint in tenths of
+ degrees Celsius."
+ ::= { airIRRP100GroupSetpoints 4 }
+
+airIRRP100GroupSetpointsHumidify OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Group humidify setpoint in tenths of
+ percent relative humidity."
+ ::= { airIRRP100GroupSetpoints 5 }
+
+airIRRP100GroupSetpointsDehumidify OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Group dehumidify setpoint in tenths of
+ percent relative humidity."
+ ::= { airIRRP100GroupSetpoints 6 }
+
+airIRRP100GroupSetpointsDehumidifyDeadband OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Group dehumidify deadband in percent relative humidity."
+ ::= { airIRRP100GroupSetpoints 7 }
+
+airIRRP100GroupSetpointsReheatUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Group supply air setpoint in tenths of
+ degrees Fahrenheit."
+ ::= { airIRRP100GroupSetpoints 8 }
+
+airIRRP100GroupSetpointsReheatMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Group supply air setpoint in tenths of
+ degrees Celsius."
+ ::= { airIRRP100GroupSetpoints 9 }
+
+airIRRP100GroupSetpointsFanSpeedPreference OBJECT-TYPE
+ SYNTAX INTEGER {
+ low (1),
+ med-low (2),
+ med (3),
+ med-high (4),
+ high (5)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The preferred fan speed setting."
+ ::= { airIRRP100GroupSetpoints 10 }
+
+airIRRP100GroupSetpointsFanSpeedControl OBJECT-TYPE
+ SYNTAX INTEGER {
+ automatic (1),
+ manual (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The fan speed control setting."
+ ::= { airIRRP100GroupSetpoints 11 }
+
+airIRRP100GroupSetpointsActiveFlowControlBias OBJECT-TYPE
+ SYNTAX INTEGER {
+ positive (1),
+ slightlyPositive (2),
+ zero (3),
+ slightlyNegative (4),
+ negative (5)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The active flow control bias setting."
+ ::= { airIRRP100GroupSetpoints 12 }
+
+-- airIRRP100 AIR CONDITIONER Group Config
+
+airIRRP100GroupConfigNumberofCoolingUnits OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The number of cooling units present in the group."
+ ::= { airIRRP100GroupConfig 1 }
+
+airIRRP100GroupConfigConfigurationType OBJECT-TYPE
+ SYNTAX INTEGER {
+ racs (1),
+ hacs (2),
+ in-row (3),
+ cacs (4)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The group configuration type."
+ ::= { airIRRP100GroupConfig 2 }
+
+airIRRP100GroupConfigCoolGainP OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The gain component of the cool PID in hundredths."
+ ::= { airIRRP100GroupConfig 3 }
+
+airIRRP100GroupConfigCoolResetRateI OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The integral component of the cool PID in hundredths."
+ ::= { airIRRP100GroupConfig 4 }
+
+airIRRP100GroupConfigCoolDerivativeD OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The derivative component of the cool PID in hundredths."
+ ::= { airIRRP100GroupConfig 5 }
+
+airIRRP100GroupConfigHumidifySensitivityBand OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The percent relative humidity below the setpoint that
+ will cause the humidifier to run at 100% capacity."
+ ::= { airIRRP100GroupConfig 6 }
+
+airIRRP100GroupConfigReheatGainP OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The gain component of the reheat PID in hundredths."
+ ::= { airIRRP100GroupConfig 7 }
+
+airIRRP100GroupConfigReheatResetRateI OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The integral component of the reheat PID in hundredths."
+ ::= { airIRRP100GroupConfig 8 }
+
+airIRRP100GroupConfigReheatDerivativeD OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The derivative component of the reheat PID in hundredths."
+ ::= { airIRRP100GroupConfig 9 }
+
+airIRRP100GroupConfigNumberofBackupUnits OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The number of backup units."
+ ::= { airIRRP100GroupConfig 10 }
+
+airIRRP100GroupConfigRuntimeBalancingEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable runtime balancing feature."
+ ::= { airIRRP100GroupConfig 11 }
+
+airIRRP100GroupConfigLoadAssistEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable load assist feature."
+ ::= { airIRRP100GroupConfig 12 }
+
+airIRRP100GroupConfigFullRPBackups OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The number of full featured RPs that can be used as backup units."
+ ::= { airIRRP100GroupConfig 13 }
+
+airIRRP100GroupConfigMaxFanSpeed OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum desired fan speed setting in percent."
+ ::= { airIRRP100GroupConfig 14 }
+
+airIRRP100GroupConfigNumberOfActiveFlowControllers OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The number of active flow controllers
+ present in the group."
+ ::= { airIRRP100GroupConfig 15 }
+
+airIRRP100GroupConfigActiveFlowControllerLampTest OBJECT-TYPE
+ SYNTAX INTEGER {
+ off (1),
+ on (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Turns off/on the active flow
+ controller lamp test."
+ ::= { airIRRP100GroupConfig 16 }
+
+airIRRP100GroupConfigAltitudeUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The group altitude of the units above sea level in feet."
+ ::= { airIRRP100GroupConfig 17 }
+
+airIRRP100GroupConfigAltitudeMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The group altitude of the units above sea level in meters."
+ ::= { airIRRP100GroupConfig 18 }
+
+-- airIRRP100 AIR CONDITIONER UNIT Status
+
+airIRRP100UnitStatusOperateMode OBJECT-TYPE
+ SYNTAX INTEGER {
+ standby (1),
+ on (2),
+ idle (3),
+ prestart (4),
+ service (5),
+ backup (6),
+ assist (7)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The cooling unit operating mode."
+ ::= { airIRRP100UnitStatus 1 }
+
+airIRRP100UnitStatusRackInletTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit rack inlet temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRRP100UnitStatus 2 }
+
+airIRRP100UnitStatusRackInletTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit rack inlet temperature in tenths of
+ degrees Celsius."
+ ::= { airIRRP100UnitStatus 3 }
+
+airIRRP100UnitStatusSupplyAirTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit supply air temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRRP100UnitStatus 4 }
+
+airIRRP100UnitStatusSupplyAirTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit supply air temperature in tenths of
+ degrees Celsius."
+ ::= { airIRRP100UnitStatus 5 }
+
+airIRRP100UnitStatusReturnAirTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit return air temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRRP100UnitStatus 6 }
+
+airIRRP100UnitStatusReturnAirTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit return air temperature in tenths of
+ degrees Celsius."
+ ::= { airIRRP100UnitStatus 7 }
+
+airIRRP100UnitStatusSupplyHumidity OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The relative humidity of the supply air in
+ tenths of percent."
+ ::= { airIRRP100UnitStatus 8 }
+
+airIRRP100UnitStatusReturnHumidity OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The relative humidity of the return air in
+ tenths of percent."
+ ::= { airIRRP100UnitStatus 9 }
+
+airIRRP100UnitStatusAirFlowUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit air flow in cubic feet per minute."
+ ::= { airIRRP100UnitStatus 10 }
+
+airIRRP100UnitStatusAirFlowMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit air flow in hundredths of
+ liters per second."
+ ::= { airIRRP100UnitStatus 11 }
+
+airIRRP100UnitStatusFanSpeed OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit average fan speed in tenths of percent."
+ ::= { airIRRP100UnitStatus 12 }
+
+airIRRP100UnitStatusCoolDemand OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit cooling demand in tenths of kiloWatts."
+ ::= { airIRRP100UnitStatus 13 }
+
+airIRRP100UnitStatusCoolOutput OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit cooling output in tenths of kiloWatts."
+ ::= { airIRRP100UnitStatus 14 }
+
+airIRRP100UnitStatusHumidifyDemand OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The amount of humidification the unit is demanding
+ from the humidifier in percent."
+ ::= { airIRRP100UnitStatus 15 }
+
+airIRRP100UnitStatusHumidifyOutput OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The actual humidification output of the unit
+ in percent."
+ ::= { airIRRP100UnitStatus 16 }
+
+airIRRP100UnitStatusDehumidifyDemand OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The amount of dehumidification the unit is
+ demanding in percent."
+ ::= { airIRRP100UnitStatus 17 }
+
+airIRRP100UnitStatusDehumidifyOutput OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The actual dehumidification output of the unit
+ in percent."
+ ::= { airIRRP100UnitStatus 18 }
+
+airIRRP100UnitStatusReheatDemand OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The amount of heating the unit is demanding
+ from the electric heater in percent."
+ ::= { airIRRP100UnitStatus 19 }
+
+airIRRP100UnitStatusReheatOutput OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The actual heating output of the unit
+ in percent."
+ ::= { airIRRP100UnitStatus 20 }
+
+airIRRP100UnitStatusInputState OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The state of the input contact."
+ ::= { airIRRP100UnitStatus 21 }
+
+airIRRP100UnitStatusOutputState OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The state of the output relay."
+ ::= { airIRRP100UnitStatus 22 }
+
+airIRRP100UnitStatusRackInletTemperature1US OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit rack inlet temperature sensor in tenths of
+ degrees Fahrenheit."
+ ::= { airIRRP100UnitStatus 23 }
+
+airIRRP100UnitStatusRackInletTemperature1Metric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit rack inlet temperature sensor in tenths of
+ degrees Celsius."
+ ::= { airIRRP100UnitStatus 24 }
+
+airIRRP100UnitStatusRackInletTemperature2US OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit rack inlet temperature sensor in tenths of
+ degrees Fahrenheit."
+ ::= { airIRRP100UnitStatus 25 }
+
+airIRRP100UnitStatusRackInletTemperature2Metric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit rack inlet temperature sensor in tenths of
+ degrees Celsius."
+ ::= { airIRRP100UnitStatus 26 }
+
+airIRRP100UnitStatusRackInletTemperature3US OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit rack inlet temperature sensor in tenths of
+ degrees Fahrenheit."
+ ::= { airIRRP100UnitStatus 27 }
+
+airIRRP100UnitStatusRackInletTemperature3Metric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit rack inlet temperature sensor in tenths of
+ degrees Celsius."
+ ::= { airIRRP100UnitStatus 28 }
+
+airIRRP100UnitStatusFilterDPUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit air filter differential pressure in
+ hundredths of inches of water."
+ ::= { airIRRP100UnitStatus 29 }
+
+airIRRP100UnitStatusFilterDPMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit air filter differential pressure in Pa."
+ ::= { airIRRP100UnitStatus 30 }
+
+airIRRP100UnitStatusContainmtDPUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit containment differential pressure in
+ hundredths of inches of water."
+ ::= { airIRRP100UnitStatus 31 }
+
+airIRRP100UnitStatusContainmtDPMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit containment differential pressure in Pa."
+ ::= { airIRRP100UnitStatus 32 }
+
+airIRRP100UnitStatusHumidifierCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The humidifier current of the unit
+ in tenths of amperes."
+ ::= { airIRRP100UnitStatus 33 }
+
+airIRRP100UnitStatusHumidifierWaterConductivity OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The water conductivity in the humidifier of the unit
+ in microSiemens/cm."
+ ::= { airIRRP100UnitStatus 34 }
+
+airIRRP100UnitStatusCompressorDriveSpeed OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The compressor drive speed in hundredths of Hertz."
+ ::= { airIRRP100UnitStatus 35 }
+
+airIRRP100UnitStatusCompressorDrivePower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The compressor drive power consumption in
+ tenths of kiloWatts."
+ ::= { airIRRP100UnitStatus 36 }
+
+airIRRP100UnitStatusCompressorDriveVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The compressor drive voltage consumption in
+ tenths of volts."
+ ::= { airIRRP100UnitStatus 37 }
+
+airIRRP100UnitStatusCompressorDriveCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The compressor drive voltage consumption in
+ tenths of amperes."
+ ::= { airIRRP100UnitStatus 38 }
+
+airIRRP100UnitStatusCompressorDriveDCLinkVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The compressor drive DC link voltage in
+ tenths of volts."
+ ::= { airIRRP100UnitStatus 39 }
+
+airIRRP100UnitStatusCompressorDriveHeatSinkTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature of the compressor drive heatsink
+ in tenths of degrees Fahrenheit."
+ ::= { airIRRP100UnitStatus 40 }
+
+airIRRP100UnitStatusCompressorDriveHeatSinkTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature of the compressor drive heatsink
+ in tenths of degrees Celsius."
+ ::= { airIRRP100UnitStatus 41 }
+
+airIRRP100UnitStatusCompressorDriveControlCardTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature of the compressor drive control card
+ in tenths of degrees Fahrenheit."
+ ::= { airIRRP100UnitStatus 42 }
+
+airIRRP100UnitStatusCompressorDriveControlCardTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature of the compressor drive control card
+ in tenths of degrees Celsius."
+ ::= { airIRRP100UnitStatus 43 }
+
+airIRRP100UnitStatusCompressorDriveWarningStatus OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The four byte warning status of the compressor drive
+ in hexadecimal."
+ ::= { airIRRP100UnitStatus 44 }
+
+airIRRP100UnitStatusCompressorDriveAlarmStatus OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The four byte alarm status of the compressor drive
+ in hexadecimal."
+ ::= { airIRRP100UnitStatus 45 }
+
+airIRRP100UnitStatusSuctionPressureUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit suction pressure in pounds per square inch (PSI)."
+ ::= { airIRRP100UnitStatus 46 }
+
+airIRRP100UnitStatusSuctionPressureMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit suction pressure in kiloPascals (kPa)."
+ ::= { airIRRP100UnitStatus 47 }
+
+airIRRP100UnitStatusDischargePressureUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit discharge pressure in pounds per square inch (PSI)."
+ ::= { airIRRP100UnitStatus 48 }
+
+airIRRP100UnitStatusDischargePressureMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit discharge pressure in kiloPascals (kPa)."
+ ::= { airIRRP100UnitStatus 49 }
+
+airIRRP100UnitStatusLeakSensor OBJECT-TYPE
+ SYNTAX INTEGER {
+ no-leak (1),
+ leak (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The state (no-leak/leak) of the leak sensor."
+ ::= { airIRRP100UnitStatus 50 }
+
+-- airIRRP100 AIR CONDITIONER UNIT Ident
+
+airIRRP100UnitIdentID OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The unit identification number."
+ ::= { airIRRP100UnitIdent 1 }
+
+airIRRP100UnitIdentName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the
+ unit name."
+ ::= { airIRRP100UnitIdent 2 }
+
+airIRRP100UnitIdentLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the
+ unit location."
+ ::= { airIRRP100UnitIdent 3 }
+
+airIRRP100UnitIdentModelNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the
+ unit model number."
+ ::= { airIRRP100UnitIdent 4 }
+
+airIRRP100UnitIdentSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the
+ unit serial number."
+ ::= { airIRRP100UnitIdent 5 }
+
+airIRRP100UnitIdentFirmwareRevision OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the
+ unit firmware version."
+ ::= { airIRRP100UnitIdent 6 }
+
+airIRRP100UnitIdentHardwareRevision OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the
+ unit controller hardware revision."
+ ::= { airIRRP100UnitIdent 7 }
+
+airIRRP100UnitIdentManufactureDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the
+ unit manufacture date."
+ ::= { airIRRP100UnitIdent 8 }
+
+
+-- airIRRP100 AIR CONDITIONER UNIT Runhours
+
+airIRRP100UnitRunHoursAirFilter OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit air filter run hours."
+ ::= { airIRRP100UnitRunHours 1 }
+
+airIRRP100UnitRunHoursCondensatePump OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit condensate pump run hours."
+ ::= { airIRRP100UnitRunHours 2 }
+
+airIRRP100UnitRunHoursHumidifier OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit fan right power supply run hours."
+ ::= { airIRRP100UnitRunHours 3 }
+
+airIRRP100UnitRunHoursFan1 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit fan 1 run hours."
+ ::= { airIRRP100UnitRunHours 4 }
+
+airIRRP100UnitRunHoursHeater1 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit heater 1 run hours."
+ ::= { airIRRP100UnitRunHours 5 }
+
+airIRRP100UnitRunHoursFan2 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit fan 2 run hours."
+ ::= { airIRRP100UnitRunHours 6 }
+
+airIRRP100UnitRunHoursHeater2 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit Heater 2 run hours."
+ ::= { airIRRP100UnitRunHours 7 }
+
+airIRRP100UnitRunHoursCompressor OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit compressor run hours."
+ ::= { airIRRP100UnitRunHours 8 }
+
+airIRRP100UnitRunHoursSystem OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Total system run hours."
+ ::= { airIRRP100UnitRunHours 9 }
+
+
+-- airIRRP100 AIR CONDITIONER UNIT Service Intervals
+
+airIRRP100UnitServiceIntervalAirFilter OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Air filter service interval in weeks."
+ ::= { airIRRP100UnitServiceIntervals 1 }
+
+airIRRP100UnitServiceIntervalAirFilterAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ enable (1),
+ disable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The air filter service interval alarm enable/disable."
+ ::= { airIRRP100UnitServiceIntervals 2 }
+
+airIRRP100UnitServiceIntervalHumidifier OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Humidifier service interval in weeks."
+ ::= { airIRRP100UnitServiceIntervals 3 }
+
+airIRRP100UnitServiceIntervalHumidifierAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ enable (1),
+ disable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The humidifier service interval alarm enable/disable."
+ ::= { airIRRP100UnitServiceIntervals 4 }
+
+airIRRP100UnitServiceIntervalHeater OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Heater service interval in weeks."
+ ::= { airIRRP100UnitServiceIntervals 5 }
+
+airIRRP100UnitServiceIntervalHeaterAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ enable (1),
+ disable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The heater service interval alarm enable/disable."
+ ::= { airIRRP100UnitServiceIntervals 6 }
+
+airIRRP100UnitServiceIntervalCompressor OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Compressor service interval in weeks."
+ ::= { airIRRP100UnitServiceIntervals 7 }
+
+airIRRP100UnitServiceIntervalCompressorAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ enable (1),
+ disable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The compressor service interval alarm enable/disable."
+ ::= { airIRRP100UnitServiceIntervals 8 }
+
+airIRRP100UnitServiceIntervalCondensatePump OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Condensate pump service interval in weeks."
+ ::= { airIRRP100UnitServiceIntervals 9 }
+
+airIRRP100UnitServiceIntervalCondensatePumpAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ enable (1),
+ disable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The condensate pump service interval alarm enable/disable."
+ ::= { airIRRP100UnitServiceIntervals 10 }
+
+airIRRP100UnitServiceIntervalFans OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Fans service interval in weeks."
+ ::= { airIRRP100UnitServiceIntervals 11 }
+
+airIRRP100UnitServiceIntervalFansAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ enable (1),
+ disable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The fans service interval alarm enable/disable."
+ ::= { airIRRP100UnitServiceIntervals 12 }
+
+
+
+-- airIRRP100 AIR CONDITIONER UNIT Thresholds
+
+airIRRP100UnitThresholdsRackInletHighTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unit rack inlet air high temperature threshold in
+ tenths of degrees Fahrenheit."
+ ::= { airIRRP100UnitThresholds 1 }
+
+airIRRP100UnitThresholdsRackInletHighTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unit rack inlet air high temperature threshold in
+ tenths of degrees Celsius."
+ ::= { airIRRP100UnitThresholds 2 }
+
+airIRRP100UnitThresholdsSupplyAirHighTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unit supply air high temperature threshold in
+ tenths of degrees Fahrenheit."
+ ::= { airIRRP100UnitThresholds 3 }
+
+airIRRP100UnitThresholdsSupplyAirHighTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unit supply air high temperature threshold in
+ tenths of degrees Celsius."
+ ::= { airIRRP100UnitThresholds 4 }
+
+airIRRP100UnitThresholdsReturnAirHighTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unit return air high temperature threshold in
+ tenths of degrees Fahrenheit."
+ ::= { airIRRP100UnitThresholds 5 }
+
+airIRRP100UnitThresholdsReturnAirHighTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unit return air high temperature threshold in
+ tenths of degrees Celsius."
+ ::= { airIRRP100UnitThresholds 6 }
+
+airIRRP100UnitThresholdsSupplyHumidityHigh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unit supply humidity high threshold in
+ tenths of percent relative humidity."
+ ::= { airIRRP100UnitThresholds 7 }
+
+airIRRP100UnitThresholdsSupplyHumidityLow OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unit supply humidity low threshold in
+ tenths of percent relative humidity."
+ ::= { airIRRP100UnitThresholds 8 }
+
+
+-- airIRRP100 AIR CONDITIONER UNIT Config
+
+airIRRP100UnitConfigStartupDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The startup delay in seconds."
+ ::= { airIRRP100UnitConfig 1 }
+
+airIRRP100UnitConfigCoolCapacity OBJECT-TYPE
+ SYNTAX INTEGER {
+ automatic (1),
+ maximum (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The cooling capacity options setting."
+ ::= { airIRRP100UnitConfig 2 }
+
+airIRRP100UnitConfigIdleOnLeakDetect OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The idle on leak options setting."
+ ::= { airIRRP100UnitConfig 3 }
+
+airIRRP100UnitConfigInputNormalState OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The normal state of the input contact."
+ ::= { airIRRP100UnitConfig 4 }
+
+airIRRP100UnitConfigOutputNormalState OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The normal state of the output relay."
+ ::= { airIRRP100UnitConfig 5 }
+
+airIRRP100UnitConfigOutputSource OBJECT-TYPE
+ SYNTAX INTEGER {
+ anyAlarm (1),
+ criticalAlarm (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The source of output relay change."
+ ::= { airIRRP100UnitConfig 6 }
+
+airIRRP100UnitConfigHumidifyEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ enable (1),
+ disable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable/disable humidification."
+ ::= { airIRRP100UnitConfig 7 }
+
+airIRRP100UnitConfigHumidifierControl OBJECT-TYPE
+ SYNTAX INTEGER {
+ auto (1),
+ drainOff (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The humidifier drain control."
+ ::= { airIRRP100UnitConfig 8 }
+
+airIRRP100UnitConfigDehumidifyEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ enable (1),
+ disable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable/disable dehumidification."
+ ::= { airIRRP100UnitConfig 9 }
+
+airIRRP100UnitConfigReheatEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ enable (1),
+ disable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable/disable reheat."
+ ::= { airIRRP100UnitConfig 10 }
+
+airIRRP100UnitConfigHeatAssistEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ enable (1),
+ disable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable/disable heat assist."
+ ::= { airIRRP100UnitConfig 11 }
+
+airIRRP100UnitConfigPowerSourceConfig OBJECT-TYPE
+ SYNTAX INTEGER {
+ single (1),
+ dual (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Configure the input power source: (1) single feed or (2) dual feed."
+ ::= { airIRRP100UnitConfig 12 }
+
+airIRRP100UnitConfigUnitRoleOverride OBJECT-TYPE
+ SYNTAX INTEGER {
+ automatic (1),
+ forcedOn (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "When this OID value is (1) automatic, the system determines
+ which units are used as primary units and which units are used as backups.
+ When this OID value is (2) forcedOn, the connected unit is set as a primary
+ unit."
+ ::= { airIRRP100UnitConfig 13 }
+
+airIRRP100UnitConfigSecondaryPowerFeedCapability OBJECT-TYPE
+ SYNTAX INTEGER {
+ full (1),
+ reduced (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Available on chilled water units. When the power source config setting
+ is set to dual, setting this value to reduced (2) will inhibit the heater
+ and humdifier when the unit is being powered from the secondary
+ input."
+ ::= { airIRRP100UnitConfig 14 }
+
+airIRRP100UnitConfigIdleOnCoolFail OBJECT-TYPE
+ SYNTAX INTEGER {
+ enable (1),
+ disable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "When this OID value is (1) enable, the unit idles if it detects that it is blowing warm
+ air into the cold aisle. The unit will attempt to restart at 5 minute intervals."
+ ::= { airIRRP100UnitConfig 15 }
+
+-- airIRRP500 AIR CONDITIONER Group Status
+
+airIRRP500GroupStatusAirFlowUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Group air flow in cubic feet per minute."
+ ::= { airIRRP500GroupStatus 1 }
+
+airIRRP500GroupStatusAirFlowMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Group air flow in liters per second."
+ ::= { airIRRP500GroupStatus 2 }
+
+airIRRP500GroupStatusMaxRackInletTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Group maximum rack inlet temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRRP500GroupStatus 3 }
+
+airIRRP500GroupStatusMaxRackInletTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Group maximum rack inlet temperature in tenths of
+ degrees Celsius."
+ ::= { airIRRP500GroupStatus 4 }
+
+airIRRP500GroupStatusMinRackInletTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Group minimum rack inlet temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRRP500GroupStatus 5 }
+
+airIRRP500GroupStatusMinRackInletTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Group minimum rack inlet temperature in tenths of
+ degrees Celsius."
+ ::= { airIRRP500GroupStatus 6 }
+
+airIRRP500GroupStatusCoolDemand OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Group coolant demand in tenths of kiloWatts."
+ ::= { airIRRP500GroupStatus 7 }
+
+airIRRP500GroupStatusCoolOutput OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Group coolant output in tenths of kiloWatts."
+ ::= { airIRRP500GroupStatus 8 }
+
+airIRRP500GroupStatusHumidifyDemand OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The amount of humidification the group is demanding
+ from the humidifiers in percent."
+ ::= { airIRRP500GroupStatus 9 }
+
+airIRRP500GroupStatusHumidifyOutput OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The actual amount of humidification the group is
+ supplying in percent."
+ ::= { airIRRP500GroupStatus 10 }
+
+airIRRP500GroupStatusDehumidifyDemand OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The amount of dehumidification the group is demanding
+ from the electric heaters in percent."
+ ::= { airIRRP500GroupStatus 11 }
+
+airIRRP500GroupStatusDehumidifyOutput OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The actual amount of dehumidification the group is
+ supplying in percent."
+ ::= { airIRRP500GroupStatus 12 }
+
+airIRRP500GroupStatusReheatDemand OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The amount of heating the group is demanding
+ from the electric heaters in percent."
+ ::= { airIRRP500GroupStatus 13 }
+
+airIRRP500GroupStatusReheatOutput OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The actual amount of heating the group is
+ supplying in percent."
+ ::= { airIRRP500GroupStatus 14 }
+
+
+airIRRP500GroupStatusActiveFlowControlStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ under (1),
+ okay (2),
+ over (3),
+ notApplicable (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Status of the active flow control
+ system."
+ ::= { airIRRP500GroupStatus 15 }
+
+airIRRP500GroupStatusDewPointTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Group average dew point temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRRP500GroupStatus 16 }
+
+airIRRP500GroupStatusDewPointTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Group average dew point temperature in tenths of
+ degrees Celsius."
+ ::= { airIRRP500GroupStatus 17 }
+
+
+-- airIRRP500 AIR CONDITIONER Group Setpoints
+
+airIRRP500GroupSetpointsCoolUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Group cooling setpoint in tenths of
+ degrees Fahrenheit."
+ ::= { airIRRP500GroupSetpoints 1 }
+
+airIRRP500GroupSetpointsCoolMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Group cooling setpoint in tenths of
+ degrees Celsius."
+ ::= { airIRRP500GroupSetpoints 2 }
+
+airIRRP500GroupSetpointsSupplyAirUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Group supply air setpoint in tenths of
+ degrees Fahrenheit."
+ ::= { airIRRP500GroupSetpoints 3 }
+
+airIRRP500GroupSetpointsSupplyAirMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Group supply air setpoint in tenths of
+ degrees Celsius."
+ ::= { airIRRP500GroupSetpoints 4 }
+
+airIRRP500GroupSetpointsHumidify OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Group humidify setpoint in tenths of
+ percent relative humidity."
+ ::= { airIRRP500GroupSetpoints 5 }
+
+airIRRP500GroupSetpointsDehumidify OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Group dehumidify setpoint in tenths of
+ percent relative humidity."
+ ::= { airIRRP500GroupSetpoints 6 }
+
+airIRRP500GroupSetpointsDehumidifyDeadband OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Group dehumidify deadband in
+ percent relative humidity."
+ ::= { airIRRP500GroupSetpoints 7 }
+
+airIRRP500GroupSetpointsReheatUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Group supply air setpoint in tenths of
+ degrees Fahrenheit."
+ ::= { airIRRP500GroupSetpoints 8 }
+
+airIRRP500GroupSetpointsReheatMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Group supply air setpoint in tenths of
+ degrees Celsius."
+ ::= { airIRRP500GroupSetpoints 9 }
+
+airIRRP500GroupSetpointsFanSpeedPreference OBJECT-TYPE
+ SYNTAX INTEGER {
+ low (1),
+ med-low (2),
+ med (3),
+ med-high (4),
+ high (5)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The preferred fan speed setting."
+ ::= { airIRRP500GroupSetpoints 10 }
+
+airIRRP500GroupSetpointsFanSpeedControl OBJECT-TYPE
+ SYNTAX INTEGER {
+ automatic (1),
+ manual (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The fan speed control setting."
+ ::= { airIRRP500GroupSetpoints 11 }
+
+airIRRP500GroupSetpointsActiveFlowControlBias OBJECT-TYPE
+ SYNTAX INTEGER {
+ positive (1),
+ slightlyPositive (2),
+ zero (3),
+ slightlyNegative (4),
+ negative (5)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The active flow control bias setting."
+ ::= { airIRRP500GroupSetpoints 12 }
+
+-- airIRRP500 AIR CONDITIONER Group Config
+
+airIRRP500GroupConfigNumberofCoolingUnits OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The number of cooling units."
+ ::= { airIRRP500GroupConfig 1 }
+
+airIRRP500GroupConfigConfigurationType OBJECT-TYPE
+ SYNTAX INTEGER {
+ racs (1),
+ hacs (2),
+ in-row (3),
+ cacs (4)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The group configuration type."
+ ::= { airIRRP500GroupConfig 2 }
+
+airIRRP500GroupConfigPercentGlycol OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The glycol mixture in percent."
+ ::= { airIRRP500GroupConfig 3 }
+
+airIRRP500GroupConfigCoolGainP OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The gain component of the cool PID in hundredths."
+ ::= { airIRRP500GroupConfig 4 }
+
+airIRRP500GroupConfigCoolResetRateI OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The integral component of the cool PID in hundredths."
+ ::= { airIRRP500GroupConfig 5 }
+
+airIRRP500GroupConfigCoolDerivativeD OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The derivative component of the cool PID in hundredths."
+ ::= { airIRRP500GroupConfig 6 }
+
+airIRRP500GroupConfigHumidifySensitivityBand OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The percent relative humidity below the setpoint that
+ will cause the humidifier to run at 100% capacity."
+ ::= { airIRRP500GroupConfig 7 }
+
+airIRRP500GroupConfigReheatGainP OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The gain component of the reheat PID in hundredths."
+ ::= { airIRRP500GroupConfig 8 }
+
+airIRRP500GroupConfigReheatResetRateI OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The integral component of the reheat PID in hundredths."
+ ::= { airIRRP500GroupConfig 9 }
+
+airIRRP500GroupConfigReheatDerivativeD OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The derivative component of the reheat PID in hundredths."
+ ::= { airIRRP500GroupConfig 10 }
+
+airIRRP500GroupConfigMaxFanSpeed OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum desired fan speed setting in percent."
+ ::= { airIRRP500GroupConfig 11 }
+
+airIRRP500GroupConfigNumberofBackupUnits OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The number of backup units."
+ ::= { airIRRP500GroupConfig 12 }
+
+airIRRP500GroupConfigRuntimeBalancingEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable runtime balancing feature."
+ ::= { airIRRP500GroupConfig 13 }
+
+airIRRP500GroupConfigLoadAssistEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable load assist feature."
+ ::= { airIRRP500GroupConfig 14 }
+
+airIRRP500GroupConfigFullRPBackups OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The number of full featured RPs that can be used as backup units."
+ ::= { airIRRP500GroupConfig 15 }
+
+airIRRP500GroupConfigNumberOfActiveFlowControllers OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The number of active flow controllers
+ present in the group."
+ ::= { airIRRP500GroupConfig 16 }
+
+airIRRP500GroupConfigActiveFlowControllerLampTest OBJECT-TYPE
+ SYNTAX INTEGER {
+ off (1),
+ on (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Turns off/on the active flow
+ controller lamp test."
+ ::= { airIRRP500GroupConfig 17 }
+
+airIRRP500GroupConfigAltitudeUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The group altitude of the units above sea level in feet."
+ ::= { airIRRP500GroupConfig 18 }
+
+airIRRP500GroupConfigAltitudeMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The group altitude of the units above sea level in meters."
+ ::= { airIRRP500GroupConfig 19 }
+
+-- airIRRP500 AIR CONDITIONER UNIT Status
+
+airIRRP500UnitStatusOperateMode OBJECT-TYPE
+ SYNTAX INTEGER {
+ standby (1),
+ on (2),
+ idle (3),
+ prestart (4),
+ backup (5),
+ assist (6)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The cooling unit operating mode."
+ ::= { airIRRP500UnitStatus 1 }
+
+airIRRP500UnitStatusMaximumRackInletTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum unit rack inlet temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRRP500UnitStatus 2 }
+
+airIRRP500UnitStatusMaximumRackInletTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum unit rack inlet temperature in tenths of
+ degrees Celsius."
+ ::= { airIRRP500UnitStatus 3 }
+
+airIRRP500UnitStatusSupplyAirTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit supply air temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRRP500UnitStatus 4 }
+
+airIRRP500UnitStatusSupplyAirTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit supply air temperature in tenths of
+ degrees Celsius."
+ ::= { airIRRP500UnitStatus 5 }
+
+airIRRP500UnitStatusReturnAirTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit return air temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRRP500UnitStatus 6 }
+
+airIRRP500UnitStatusReturnAirTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit return air temperature in tenths of
+ degrees Celsius."
+ ::= { airIRRP500UnitStatus 7 }
+
+airIRRP500UnitStatusSupplyHumidity OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The relative humidity of the supply air in
+ tenths of percent."
+ ::= { airIRRP500UnitStatus 8 }
+
+airIRRP500UnitStatusReturnHumidity OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The relative humidity of the return air in
+ tenths of percent."
+ ::= { airIRRP500UnitStatus 9 }
+
+airIRRP500UnitStatusAirFlowUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit air flow in cubic feet per minute."
+ ::= { airIRRP500UnitStatus 10 }
+
+airIRRP500UnitStatusAirFlowMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit air flow in hundredths of
+ liters per second."
+ ::= { airIRRP500UnitStatus 11 }
+
+airIRRP500UnitStatusFanSpeed OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit average fan speed in tenths of percent."
+ ::= { airIRRP500UnitStatus 12 }
+
+airIRRP500UnitStatusCoolDemand OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit cooling demand in tenths of kiloWatts."
+ ::= { airIRRP500UnitStatus 13 }
+
+airIRRP500UnitStatusCoolOutput OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit cooling output in tenths of kiloWatts."
+ ::= { airIRRP500UnitStatus 14 }
+
+airIRRP500UnitStatusHumidifyDemand OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The amount of humidification the unit is demanding
+ from the humidifier in percent."
+ ::= { airIRRP500UnitStatus 15 }
+
+airIRRP500UnitStatusHumidifyOutput OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The actual humidification output of the unit
+ in percent."
+ ::= { airIRRP500UnitStatus 16 }
+
+airIRRP500UnitStatusDehumidifyDemand OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The amount of dehumidification the unit is
+ demanding in percent."
+ ::= { airIRRP500UnitStatus 17 }
+
+airIRRP500UnitStatusDehumidifyOutput OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The actual dehumidification output of the unit
+ in percent."
+ ::= { airIRRP500UnitStatus 18 }
+
+airIRRP500UnitStatusReheatDemand OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The amount of heating the unit is demanding
+ from the electric heater in percent."
+ ::= { airIRRP500UnitStatus 19 }
+
+airIRRP500UnitStatusReheatOutput OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The actual heating output of the unit
+ in percent."
+ ::= { airIRRP500UnitStatus 20 }
+
+airIRRP500UnitStatusInputState OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The state of the input contact."
+ ::= { airIRRP500UnitStatus 21 }
+
+airIRRP500UnitStatusOutputState OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The state of the output relay."
+ ::= { airIRRP500UnitStatus 22 }
+
+airIRRP500UnitStatusRackInletTemperature1US OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit rack inlet temperature sensor in tenths of
+ degrees Fahrenheit."
+ ::= { airIRRP500UnitStatus 23 }
+
+airIRRP500UnitStatusRackInletTemperature1Metric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit rack inlet temperature sensor in tenths of
+ degrees Celsius."
+ ::= { airIRRP500UnitStatus 24 }
+
+airIRRP500UnitStatusRackInletTemperature2US OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit rack inlet temperature sensor in tenths of
+ degrees Fahrenheit."
+ ::= { airIRRP500UnitStatus 25 }
+
+airIRRP500UnitStatusRackInletTemperature2Metric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit rack inlet temperature sensor in tenths of
+ degrees Celsius."
+ ::= { airIRRP500UnitStatus 26 }
+
+airIRRP500UnitStatusRackInletTemperature3US OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit rack inlet temperature sensor in tenths of
+ degrees Fahrenheit."
+ ::= { airIRRP500UnitStatus 27 }
+
+airIRRP500UnitStatusRackInletTemperature3Metric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit rack inlet temperature sensor in tenths of
+ degrees Celsius."
+ ::= { airIRRP500UnitStatus 28 }
+
+airIRRP500UnitStatusContainmtDPUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit containment differential pressure in
+ hundredths of inches of water."
+ ::= { airIRRP500UnitStatus 29 }
+
+airIRRP500UnitStatusContainmtDPMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit containment differential pressure in Pa."
+ ::= { airIRRP500UnitStatus 30 }
+
+airIRRP500UnitStatusFilterDPUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit air filter differential pressure in
+ hundredths of inches of water."
+ ::= { airIRRP500UnitStatus 31 }
+
+airIRRP500UnitStatusFilterDPMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit air filter differential pressure in Pa."
+ ::= { airIRRP500UnitStatus 32 }
+
+airIRRP500UnitStatusHumidifierCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The humidifier current of the unit
+ in tenths of amperes."
+ ::= { airIRRP500UnitStatus 33 }
+
+airIRRP500UnitStatusHumidifierWaterConductivity OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The water conductivity in the humidifier of the unit
+ in microSiemens/cm."
+ ::= { airIRRP500UnitStatus 34 }
+
+airIRRP500UnitStatusActivePowerSource OBJECT-TYPE
+ SYNTAX INTEGER {
+ sourceA (1),
+ sourceB (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The power source that is powering the unit."
+ ::= { airIRRP500UnitStatus 35 }
+
+airIRRP500UnitStatusFluidValvePosition OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The fluid valve position in percent open."
+ ::= { airIRRP500UnitStatus 36 }
+
+airIRRP500UnitStatusFluidFlowUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The fluid flow in tenths of gallons per minute."
+ ::= { airIRRP500UnitStatus 37 }
+
+airIRRP500UnitStatusFluidFlowMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The fluid flow in hundredths of liters per second."
+ ::= { airIRRP500UnitStatus 38 }
+
+airIRRP500UnitStatusEnteringFluidTemperatureUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature of the entering fluid in
+ tenths of degrees Fahrenheit."
+ ::= { airIRRP500UnitStatus 39 }
+
+airIRRP500UnitStatusEnteringFluidTemperatureMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature of the entering fluid in
+ tenths of degrees Celsius."
+ ::= { airIRRP500UnitStatus 40 }
+
+airIRRP500UnitStatusLeavingFluidTemperatureUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature of the Leaving fluid in
+ tenths of degrees Fahrenheit."
+ ::= { airIRRP500UnitStatus 41 }
+
+airIRRP500UnitStatusLeavingFluidTemperatureMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature of the Leaving fluid in
+ tenths of degrees Celsius."
+ ::= { airIRRP500UnitStatus 42 }
+
+airIRRP500UnitStatusLeakSensor OBJECT-TYPE
+ SYNTAX INTEGER {
+ no-leak (1),
+ leak (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The state (no-leak/leak) of the leak sensor."
+ ::= { airIRRP500UnitStatus 43 }
+
+
+-- airIRRP500 AIR CONDITIONER UNIT Ident
+
+airIRRP500UnitIdentID OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The unit identification number."
+ ::= { airIRRP500UnitIdent 1 }
+
+airIRRP500UnitIdentName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the
+ unit name."
+ ::= { airIRRP500UnitIdent 2 }
+
+airIRRP500UnitIdentLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the
+ unit location."
+ ::= { airIRRP500UnitIdent 3 }
+
+airIRRP500UnitIdentModelNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the
+ unit model number."
+ ::= { airIRRP500UnitIdent 4 }
+
+airIRRP500UnitIdentSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the
+ unit serial number."
+ ::= { airIRRP500UnitIdent 5 }
+
+airIRRP500UnitIdentFirmwareRevision OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the
+ unit firmware version."
+ ::= { airIRRP500UnitIdent 6 }
+
+airIRRP500UnitIdentHardwareRevision OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the
+ unit controller hardware revision."
+ ::= { airIRRP500UnitIdent 7 }
+
+airIRRP500UnitIdentManufactureDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the
+ unit manufacture date."
+ ::= { airIRRP500UnitIdent 8 }
+
+
+-- airIRRP500 AIR CONDITIONER UNIT Runhours
+
+airIRRP500UnitRunHoursAirFilter OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit air filter run hours in hours."
+ ::= { airIRRP500UnitRunHours 1 }
+
+airIRRP500UnitRunHoursCondensatePump OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit condensate pump run hours in hours."
+ ::= { airIRRP500UnitRunHours 2 }
+
+airIRRP500UnitRunHoursHumidifier OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit fan right power supply run hours in hours."
+ ::= { airIRRP500UnitRunHours 3 }
+
+airIRRP500UnitRunHoursFan1 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit fan 1 run hours in hours."
+ ::= { airIRRP500UnitRunHours 4 }
+
+airIRRP500UnitRunHoursHeater1 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit heater 1 run hours in hours."
+ ::= { airIRRP500UnitRunHours 5 }
+
+airIRRP500UnitRunHoursFan2 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit fan 2 run hours in hours."
+ ::= { airIRRP500UnitRunHours 6 }
+
+airIRRP500UnitRunHoursHeater2 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit Heater 2 run hours in hours."
+ ::= { airIRRP500UnitRunHours 7 }
+
+airIRRP500UnitRunHoursFan3 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit fan 3 run hours in hours."
+ ::= { airIRRP500UnitRunHours 8 }
+
+airIRRP500UnitRunHoursHeater3 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit heater 3 run hours in hours."
+ ::= { airIRRP500UnitRunHours 9 }
+
+airIRRP500UnitRunHoursSystem OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Total system run hours."
+ ::= { airIRRP500UnitRunHours 10 }
+
+
+-- airIRRP500 AIR CONDITIONER UNIT Service Intervals
+
+airIRRP500UnitServiceIntervalAirFilter OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Air filter service interval in weeks."
+ ::= { airIRRP500UnitServiceIntervals 1 }
+
+airIRRP500UnitServiceIntervalAirFilterAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ enable (1),
+ disable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The air filter service interval alarm enable/disable."
+ ::= { airIRRP500UnitServiceIntervals 2 }
+
+airIRRP500UnitServiceIntervalHumidifier OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Humidifier service interval in weeks."
+ ::= { airIRRP500UnitServiceIntervals 3 }
+
+airIRRP500UnitServiceIntervalHumidifierAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ enable (1),
+ disable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The humidifier service interval alarm enable/disable."
+ ::= { airIRRP500UnitServiceIntervals 4 }
+
+airIRRP500UnitServiceIntervalHeater OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Heater service interval in weeks."
+ ::= { airIRRP500UnitServiceIntervals 5 }
+
+airIRRP500UnitServiceIntervalHeaterAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ enable (1),
+ disable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The heater service interval alarm enable/disable."
+ ::= { airIRRP500UnitServiceIntervals 6 }
+
+airIRRP500UnitServiceIntervalCondensatePump OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Condensate pump service interval in weeks."
+ ::= { airIRRP500UnitServiceIntervals 7 }
+
+airIRRP500UnitServiceIntervalCondensatePumpAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ enable (1),
+ disable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The condensate pump service interval alarm enable/disable."
+ ::= { airIRRP500UnitServiceIntervals 8 }
+
+airIRRP500UnitServiceIntervalFans OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Fans service interval in weeks."
+ ::= { airIRRP500UnitServiceIntervals 9 }
+
+airIRRP500UnitServiceIntervalFansAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ enable (1),
+ disable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The fans service interval alarm enable/disable."
+ ::= { airIRRP500UnitServiceIntervals 10 }
+
+
+-- airIRRP500 AIR CONDITIONER UNIT Thresholds
+
+airIRRP500UnitThresholdsRackInletHighTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unit rack inlet air high temperature threshold in
+ tenths of degrees Fahrenheit."
+ ::= { airIRRP500UnitThresholds 1 }
+
+airIRRP500UnitThresholdsRackInletHighTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unit rack inlet air high temperature threshold in
+ tenths of degrees Celsius."
+ ::= { airIRRP500UnitThresholds 2 }
+
+airIRRP500UnitThresholdsSupplyAirHighTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unit supply air temperature high threshold in
+ tenths of degrees Fahrenheit."
+ ::= { airIRRP500UnitThresholds 3 }
+
+airIRRP500UnitThresholdsSupplyAirHighTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unit supply air high temperature high threshold in
+ tenths of degrees Celsius."
+ ::= { airIRRP500UnitThresholds 4 }
+
+airIRRP500UnitThresholdsReturnAirHighTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unit return air high temperature threshold in
+ tenths of degrees Fahrenheit."
+ ::= { airIRRP500UnitThresholds 5 }
+
+airIRRP500UnitThresholdsReturnAirHighTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unit return air high temperature threshold in
+ tenths of degrees Celsius."
+ ::= { airIRRP500UnitThresholds 6 }
+
+airIRRP500UnitThresholdsReturnHumidityHigh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unit return humidity high threshold in
+ tenths of percent relative humidity."
+ ::= { airIRRP500UnitThresholds 7 }
+
+airIRRP500UnitThresholdsReturnHumidityLow OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unit return humidity low threshold in
+ tenths of percent relative humidity."
+ ::= { airIRRP500UnitThresholds 8 }
+
+airIRRP500UnitThresholdsEnteringFluidHighTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Entering fluid high temperature threshold in
+ tenths of degrees Fahrenheit."
+ ::= { airIRRP500UnitThresholds 9 }
+
+airIRRP500UnitThresholdsEnteringFluidHighTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Entering fluid high temperature threshold in
+ tenths of degrees Celsius."
+ ::= { airIRRP500UnitThresholds 10 }
+
+
+-- airIRRP500 AIR CONDITIONER UNIT Config
+
+airIRRP500UnitConfigStartupDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The startup delay in seconds."
+ ::= { airIRRP500UnitConfig 1 }
+
+airIRRP500UnitConfigCoolCapacity OBJECT-TYPE
+ SYNTAX INTEGER {
+ automatic (1),
+ maximum (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The cooling capacity options setting."
+ ::= { airIRRP500UnitConfig 2 }
+
+airIRRP500UnitConfigIdleOnLeakDetect OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The idle on leak options setting."
+ ::= { airIRRP500UnitConfig 3 }
+
+airIRRP500UnitConfigInputNormalState OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The normal state of the input contact."
+ ::= { airIRRP500UnitConfig 4 }
+
+airIRRP500UnitConfigOutputNormalState OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The normal state of the output relay."
+ ::= { airIRRP500UnitConfig 5 }
+
+airIRRP500UnitConfigOutputSource OBJECT-TYPE
+ SYNTAX INTEGER {
+ anyAlarm (1),
+ criticalAlarm (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The source of output relay change."
+ ::= { airIRRP500UnitConfig 6 }
+
+airIRRP500UnitConfigHumidifyEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ enable (1),
+ disable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable/disable humidification."
+ ::= { airIRRP500UnitConfig 7 }
+
+airIRRP500UnitConfigHumidifierControl OBJECT-TYPE
+ SYNTAX INTEGER {
+ auto (1),
+ drainOff (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The humidifier drain control."
+ ::= { airIRRP500UnitConfig 8 }
+
+airIRRP500UnitConfigDehumidifyEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ enable (1),
+ disable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable/disable dehumidification."
+ ::= { airIRRP500UnitConfig 9 }
+
+airIRRP500UnitConfigReheatEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ enable (1),
+ disable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable/disable reheat."
+ ::= { airIRRP500UnitConfig 10 }
+
+airIRRP500UnitConfigHeatAssistEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ enable (1),
+ disable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable/disable heat assist."
+ ::= { airIRRP500UnitConfig 11 }
+
+airIRRP500UnitConfigPowerSourceConfig OBJECT-TYPE
+ SYNTAX INTEGER {
+ single (1),
+ dual (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Configure the input power source: (1) single feed or (2) dual feed."
+ ::= { airIRRP500UnitConfig 12 }
+
+airIRRP500UnitConfigUnitRoleOverride OBJECT-TYPE
+ SYNTAX INTEGER {
+ automatic (1),
+ forcedOn (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "When this OID value is (1) automatic, the system determines
+ which units are used as primary units and which units are used as backups.
+ When this OID value is (2) forcedOn, the connected unit is set as a primary
+ unit."
+ ::= { airIRRP500UnitConfig 13 }
+
+airIRRP500UnitConfigSecondaryPowerFeedCapability OBJECT-TYPE
+ SYNTAX INTEGER {
+ full (1),
+ reduced (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Available on chilled water units. When the power source config setting
+ is set to dual, setting this value to reduced (2) will inhibit the heater
+ and humdifier when the unit is being powered from the secondary
+ input."
+ ::= { airIRRP500UnitConfig 14 }
+
+airIRRP500UnitConfigIdleOnCoolFail OBJECT-TYPE
+ SYNTAX INTEGER {
+ enable (1),
+ disable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "When this OID value is (1) enable, the unit idles if it detects that it is blowing warm
+ air into the cold aisle. The unit will attempt to restart at 5 minute intervals."
+ ::= { airIRRP500UnitConfig 15 }
+
+-- airIRSC AIR CONDITIONER Defines
+
+AirIRSCConfigType ::= INTEGER {
+ racs (1),
+ spot (2),
+ in-row (3)
+ }
+
+AirIRSCCapacityControlType ::= INTEGER {
+ discrete (1),
+ proportional (2)
+ }
+
+AirIRSCFanSpeedPreference ::= INTEGER {
+ low (1),
+ med-low (2),
+ med (3),
+ med-high (4),
+ high (5)
+ }
+
+AirIRSCFanSpeedControl ::= INTEGER {
+ automatic (1),
+ manual (2)
+ }
+
+-- airIRSC AIR CONDITIONER UNIT Status
+
+airIRSCUnitStatusOperateMode OBJECT-TYPE
+ SYNTAX INTEGER {
+ standby (1),
+ on (2),
+ idle (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The cooling unit operating mode."
+ ::= { airIRSCUnitStatus 1 }
+
+airIRSCUnitStatusCoolOutput OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit cooling output in tenths of kW."
+ ::= { airIRSCUnitStatus 2 }
+
+airIRSCUnitStatusCoolDemand OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit cooling demand in tenths of kW."
+ ::= { airIRSCUnitStatus 3 }
+
+airIRSCUnitStatusAirFlowUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit air flow in cubic feet per minute."
+ ::= { airIRSCUnitStatus 4 }
+
+airIRSCUnitStatusAirFlowMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit air flow in liters per second."
+ ::= { airIRSCUnitStatus 5 }
+
+airIRSCUnitStatusRackInletTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit rack inlet temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRSCUnitStatus 6 }
+
+airIRSCUnitStatusRackInletTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit rack inlet temperature in tenths of
+ degrees Celsius."
+ ::= { airIRSCUnitStatus 7 }
+
+airIRSCUnitStatusSupplyAirTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit supply air temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRSCUnitStatus 8 }
+
+airIRSCUnitStatusSupplyAirTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit supply air temperature in tenths of
+ degrees Celsius."
+ ::= { airIRSCUnitStatus 9 }
+
+airIRSCUnitStatusReturnAirTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit return air temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRSCUnitStatus 10 }
+
+airIRSCUnitStatusReturnAirTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit return air temperature in tenths of
+ degrees Celsius."
+ ::= { airIRSCUnitStatus 11 }
+
+airIRSCUnitStatusSuctionTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit suction temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRSCUnitStatus 12 }
+
+airIRSCUnitStatusSuctionTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit suction temperature in tenths of
+ degrees Celsius."
+ ::= { airIRSCUnitStatus 13 }
+
+airIRSCUnitStatusSuperheatTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit superheat temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRSCUnitStatus 14 }
+
+airIRSCUnitStatusSuperheatTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit superheat temperature in tenths of
+ degrees Celsius."
+ ::= { airIRSCUnitStatus 15 }
+
+airIRSCUnitStatusContainmtDPUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit containment differential pressure in
+ hundredths of inches of water."
+ ::= { airIRSCUnitStatus 16 }
+
+airIRSCUnitStatusContainmtDPMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit containment differential pressure in Pa."
+ ::= { airIRSCUnitStatus 17 }
+
+airIRSCUnitStatusFilterDPUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit air filter differential pressure in
+ hundredths of inches of water."
+ ::= { airIRSCUnitStatus 18 }
+
+airIRSCUnitStatusFilterDPMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit air filter differential pressure in Pa."
+ ::= { airIRSCUnitStatus 19 }
+
+airIRSCUnitStatusSuctionPressureUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit suction pressure in pounds per square inch (PSI)."
+ ::= { airIRSCUnitStatus 20 }
+
+airIRSCUnitStatusSuctionPressureMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit suction pressure in kiloPascals (kPa)."
+ ::= { airIRSCUnitStatus 21 }
+
+airIRSCUnitStatusDischargePressureUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit discharge pressure in pounds per square inch (PSI)."
+ ::= { airIRSCUnitStatus 22 }
+
+airIRSCUnitStatusDischargePressureMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit discharge pressure in kiloPascals (kPa)."
+ ::= { airIRSCUnitStatus 23 }
+
+airIRSCUnitStatusEvaporatorFanSpeed OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit average evaporator fan speed in tenths of percent."
+ ::= { airIRSCUnitStatus 24 }
+
+airIRSCUnitStatusCondenserFanSpeed OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit average condenser fan speed in tenths of percent."
+ ::= { airIRSCUnitStatus 25 }
+
+airIRSCUnitStatusInputState OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The state of the input contact."
+ ::= { airIRSCUnitStatus 26 }
+
+airIRSCUnitStatusOutputState OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The state of the output relay."
+ ::= { airIRSCUnitStatus 27 }
+
+airIRSCUnitStatusCondOutletTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit condenser outlet air temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRSCUnitStatus 28 }
+
+airIRSCUnitStatusCondOutletTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit condenser outlet air temperature in tenths of
+ degrees Celsius."
+ ::= { airIRSCUnitStatus 29 }
+
+airIRSCUnitStatusCondInletTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit condenser inlet air temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRSCUnitStatus 30 }
+
+airIRSCUnitStatusCondInletTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit condenser inlet air temperature in tenths of
+ degrees Celsius."
+ ::= { airIRSCUnitStatus 31 }
+
+airIRSCUnitStatusCompressor OBJECT-TYPE
+ SYNTAX INTEGER {
+ off (1),
+ on (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The state (off/on) of the compressor."
+ ::= { airIRSCUnitStatus 32 }
+
+airIRSCUnitStatusLeakSensor OBJECT-TYPE
+ SYNTAX INTEGER {
+ no-leak (1),
+ leak (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The state (no-leak/leak) of the leak sensor."
+ ::= { airIRSCUnitStatus 33 }
+
+-- airIRSC AIR CONDITIONER UNIT Ident
+
+airIRSCUnitIdentName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the
+ unit name."
+ ::= { airIRSCUnitIdent 1 }
+
+airIRSCUnitIdentLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the
+ unit location."
+ ::= { airIRSCUnitIdent 2 }
+
+airIRSCUnitIdentModelNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the
+ unit model number."
+ ::= { airIRSCUnitIdent 3 }
+
+airIRSCUnitIdentSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the
+ unit serial number."
+ ::= { airIRSCUnitIdent 4 }
+
+airIRSCUnitIdentFirmwareRevision OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the
+ unit firmware version."
+ ::= { airIRSCUnitIdent 5 }
+
+airIRSCUnitIdentHardwareRevision OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the
+ unit controller hardware revision."
+ ::= { airIRSCUnitIdent 6 }
+
+airIRSCUnitIdentManufactureDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the
+ unit manufacture date."
+ ::= { airIRSCUnitIdent 7 }
+
+
+-- airIRSC AIR CONDITIONER UNIT Runhours
+
+airIRSCUnitRunHoursAirFilter OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit air filter run hours."
+ ::= { airIRSCUnitRunHours 1 }
+
+airIRSCUnitRunHoursEvaporatorFan1 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit evaporator fan 1 run hours."
+ ::= { airIRSCUnitRunHours 2 }
+
+airIRSCUnitRunHoursEvaporatorFan2 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit evaporator fan 2 run hours."
+ ::= { airIRSCUnitRunHours 3 }
+
+airIRSCUnitRunHoursEvaporatorFan3 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit evaporator fan 3 run hours."
+ ::= { airIRSCUnitRunHours 4 }
+
+airIRSCUnitRunHoursCondenserFan1 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit condenser fan 1 run hours."
+ ::= { airIRSCUnitRunHours 5 }
+
+airIRSCUnitRunHoursCondenserFan2 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit condenser fan 2 run hours."
+ ::= { airIRSCUnitRunHours 6 }
+
+airIRSCUnitRunHoursCondenserFan3 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit condenser fan 3 run hours."
+ ::= { airIRSCUnitRunHours 7 }
+
+airIRSCUnitRunHoursFanPowerSupplyLeft OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit fan left power supply run hours."
+ ::= { airIRSCUnitRunHours 8 }
+
+airIRSCUnitRunHoursFanPowerSupplyRight OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit fan right power supply run hours."
+ ::= { airIRSCUnitRunHours 9 }
+
+airIRSCUnitRunHoursCondensatePump OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit condensate pump run hours."
+ ::= { airIRSCUnitRunHours 10 }
+
+airIRSCUnitRunHoursCompressor OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit compressor run hours."
+ ::= { airIRSCUnitRunHours 11 }
+
+
+-- airIRSC AIR CONDITIONER UNIT Service Intervals
+
+airIRSCUnitServiceIntervalsAirFilter OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Air filter service interval in weeks."
+ ::= { airIRSCUnitServiceIntervals 1 }
+
+airIRSCUnitServiceIntervalsAirFilterAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ enable (1),
+ disable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The air filter service interval alarm enable/disable."
+ ::= { airIRSCUnitServiceIntervals 2 }
+
+
+-- airIRSC AIR CONDITIONER UNIT Thresholds
+
+airIRSCUnitThresholdsRackInletHighTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unit rack inlet air high temperature threshold in
+ tenths of degrees Fahrenheit."
+ ::= { airIRSCUnitThresholds 1 }
+
+airIRSCUnitThresholdsRackInletHighTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unit rack inlet air high temperature threshold in
+ tenths of degrees Celsius."
+ ::= { airIRSCUnitThresholds 2 }
+
+airIRSCUnitThresholdsSupplyAirHighTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unit supply air high temperature threshold in
+ tenths of degrees Fahrenheit."
+ ::= { airIRSCUnitThresholds 3 }
+
+airIRSCUnitThresholdsSupplyAirHighTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unit supply air high temperature threshold in
+ tenths of degrees Celsius."
+ ::= { airIRSCUnitThresholds 4 }
+
+airIRSCUnitThresholdsReturnAirHighTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unit return air high temperature threshold in
+ tenths of degrees Fahrenheit."
+ ::= { airIRSCUnitThresholds 5 }
+
+airIRSCUnitThresholdsReturnAirHighTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unit return air high temperature threshold in
+ tenths of degrees Celsius."
+ ::= { airIRSCUnitThresholds 6 }
+
+-- airIRSC AIR CONDITIONER UNIT Setpoints
+
+airIRSCUnitSetptsCoolSetpointUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unit cooling setpoint in tenths of
+ degrees Fahrenheit."
+ ::= { airIRSCUnitSetpoints 1 }
+
+airIRSCUnitSetptsCoolSetpointMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unit cooling setpoint in tenths of
+ degrees Celsius."
+ ::= { airIRSCUnitSetpoints 2 }
+
+airIRSCUnitSetptsCoolDeadbandUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unit cooling deadband in tenths of
+ degrees Fahrenheit."
+ ::= { airIRSCUnitSetpoints 3 }
+
+airIRSCUnitSetptsCoolDeadbandMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unit cooling deadband in tenths of
+ degrees Celsius."
+ ::= { airIRSCUnitSetpoints 4 }
+
+airIRSCUnitSetptsFanSpeedPreference OBJECT-TYPE
+ SYNTAX AirIRSCFanSpeedPreference
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The preferred fan speed setting."
+ ::= { airIRSCUnitSetpoints 5 }
+
+airIRSCUnitSetptsSupplyAirSetpointUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unit supply air setpoint in tenths of
+ degrees Fahrenheit."
+ ::= { airIRSCUnitSetpoints 6 }
+
+airIRSCUnitSetptsSupplyAirSetpointMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unit supply air setpoint in tenths of
+ degrees Celsius."
+ ::= { airIRSCUnitSetpoints 7 }
+
+-- airIRSC AIR CONDITIONER UNIT Config
+
+airIRSCUnitConfigConfigurationType OBJECT-TYPE
+ SYNTAX AirIRSCConfigType
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The unit configuration type."
+ ::= { airIRSCUnitConfig 1 }
+
+airIRSCUnitConfigCapacityControlType OBJECT-TYPE
+ SYNTAX AirIRSCCapacityControlType
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The unit capacity control."
+ ::= { airIRSCUnitConfig 2 }
+
+airIRSCUnitConfigStartupDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The startup delay in seconds."
+ ::= { airIRSCUnitConfig 3 }
+
+airIRSCUnitConfigIdleOnLeakDetect OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The idle on leak options setting."
+ ::= { airIRSCUnitConfig 4 }
+
+airIRSCUnitConfigInputNormalState OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The normal state of the input contact."
+ ::= { airIRSCUnitConfig 5 }
+
+airIRSCUnitConfigOutputNormalState OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The normal state of the output relay."
+ ::= { airIRSCUnitConfig 6 }
+
+airIRSCUnitConfigOutputSource OBJECT-TYPE
+ SYNTAX INTEGER {
+ anyAlarm (1),
+ criticalAlarm (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The source of output relay change."
+ ::= { airIRSCUnitConfig 7 }
+
+airIRSCUnitConfigAltitudeUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The altitude of the unit above sea level in feet."
+ ::= { airIRSCUnitConfig 8 }
+
+airIRSCUnitConfigAltitudeMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The altitude of the unit above sea level in meters."
+ ::= { airIRSCUnitConfig 9 }
+
+airIRSCUnitConfigOpControl OBJECT-TYPE
+ SYNTAX INTEGER {
+ standby (1),
+ on (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The unit operational control."
+ ::= { airIRSCUnitConfig 10 }
+
+
+-- airIRSC AIR CONDITIONER GROUP Status
+
+airIRSCGroupStatusCoolOutput OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group cooling output in tenths of kW."
+ ::= { airIRSCGroupStatus 1 }
+
+airIRSCGroupStatusCoolDemand OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group cooling demand in tenths of kW."
+ ::= { airIRSCGroupStatus 2 }
+
+airIRSCGroupStatusAirFlowUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group air flow in cubic feet per minute."
+ ::= { airIRSCGroupStatus 3 }
+
+airIRSCGroupStatusAirFlowMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group air flow in liters per second."
+ ::= { airIRSCGroupStatus 4 }
+
+airIRSCGroupStatusMaxRackInletTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group maximum rack inlet temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRSCGroupStatus 5 }
+
+airIRSCGroupStatusMaxRackInletTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group maximum rack inlet temperature in tenths of
+ degrees Celsius."
+ ::= { airIRSCGroupStatus 6 }
+
+airIRSCGroupStatusMinRackInletTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group minimum rack inlet temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRSCGroupStatus 7 }
+
+airIRSCGroupStatusMinRackInletTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group minimum rack inlet temperature in tenths of
+ degrees Celsius."
+ ::= { airIRSCGroupStatus 8 }
+
+airIRSCGroupStatusMaxReturnAirTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group maximum return air temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRSCGroupStatus 9 }
+
+airIRSCGroupStatusMaxReturnAirTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group maximum return air temperature in tenths of
+ degrees Celsius."
+ ::= { airIRSCGroupStatus 10 }
+
+airIRSCGroupStatusMinReturnAirTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group minimum return air temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRSCGroupStatus 11 }
+
+airIRSCGroupStatusMinReturnAirTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group minimum return air temperature in tenths of
+ degrees Celsius."
+ ::= { airIRSCGroupStatus 12 }
+
+airIRSCGroupStatusActiveFlowControlStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ under (1),
+ okay (2),
+ over (3),
+ notApplicable (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Status of the active flow control
+ system."
+ ::= { airIRSCGroupStatus 13 }
+
+
+-- airIRSC AIR CONDITIONER GROUP Setpoint
+
+airIRSCGroupSetptsCoolSetpointUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Group cooling setpoint in tenths of
+ degrees Fahrenheit."
+ ::= { airIRSCGroupSetpoints 1 }
+
+airIRSCGroupSetptsCoolSetpointMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Group cooling setpoint in tenths of
+ degrees Celsius."
+ ::= { airIRSCGroupSetpoints 2 }
+
+airIRSCGroupSetptsCoolDeadbandUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Group cooling deadband in tenths of
+ degrees Fahrenheit."
+ ::= { airIRSCGroupSetpoints 3 }
+
+airIRSCGroupSetptsCoolDeadbandMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Group cooling deadband in tenths of
+ degrees Celsius."
+ ::= { airIRSCGroupSetpoints 4 }
+
+airIRSCGroupSetptsFanSpeedPreference OBJECT-TYPE
+ SYNTAX AirIRSCFanSpeedPreference
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The group preferred fan speed setting."
+ ::= { airIRSCGroupSetpoints 5 }
+
+airIRSCGroupSetptsSupplyAirSetpointUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Group supply air setpoint in tenths of
+ degrees Fahrenheit."
+ ::= { airIRSCGroupSetpoints 6 }
+
+airIRSCGroupSetptsSupplyAirSetpointMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Group supply air setpoint in tenths of
+ degrees Celsius."
+ ::= { airIRSCGroupSetpoints 7 }
+
+airIRSCGroupSetpointsActiveFlowControlBias OBJECT-TYPE
+ SYNTAX INTEGER {
+ positive (1),
+ slightlyPositive (2),
+ zero (3),
+ slightlyNegative (4),
+ negative (5)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The active flow control bias setting."
+ ::= { airIRSCGroupSetpoints 8 }
+
+-- airIRSC AIR CONDITIONER GROUP Config
+
+airIRSCGroupConfigNumberofCoolingUnits OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The number of cooling units."
+ ::= { airIRSCGroupConfig 1 }
+
+airIRSCGroupConfigConfigurationType OBJECT-TYPE
+ SYNTAX AirIRSCConfigType
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The group configuration type."
+ ::= { airIRSCGroupConfig 2 }
+
+airIRSCGroupConfigCapacityControlType OBJECT-TYPE
+ SYNTAX AirIRSCCapacityControlType
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The group capacity control."
+ ::= { airIRSCGroupConfig 3 }
+
+airIRSCGroupConfigAltitudeUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The group altitude of the units above sea level in feet."
+ ::= { airIRSCGroupConfig 4 }
+
+airIRSCGroupConfigAltitudeMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The group altitude of the units above sea level in meters."
+ ::= { airIRSCGroupConfig 5 }
+
+airIRSCGroupConfigFanSpeedControl OBJECT-TYPE
+ SYNTAX AirIRSCFanSpeedControl
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The group fan speed control."
+ ::= { airIRSCGroupConfig 6 }
+
+airIRSCGroupConfigNumberOfActiveFlowControllers OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The number of active flow controllers
+ present in the group."
+ ::= { airIRSCGroupConfig 7 }
+
+airIRSCGroupConfigActiveFlowControllerLampTest OBJECT-TYPE
+ SYNTAX INTEGER {
+ off (1),
+ on (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Turns off/on the active flow
+ controller lamp test."
+ ::= { airIRSCGroupConfig 8 }
+
+-- ******************************************************************
+-- airIRG2 Ident
+-- ******************************************************************
+
+airIRG2IdentName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the unit name."
+ ::= { airIRG2Ident 1 }
+
+airIRG2IdentLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the unit location."
+ ::= { airIRG2Ident 2 }
+
+airIRG2IdentModelNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the unit model number."
+ ::= { airIRG2Ident 3 }
+
+airIRG2IdentSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the unit serial number."
+ ::= { airIRG2Ident 4 }
+
+airIRG2IdentFirmwareRevision OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the unit firmware version."
+ ::= { airIRG2Ident 5 }
+
+airIRG2IdentHardwareRevision OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the unit controller hardware revision."
+ ::= { airIRG2Ident 6 }
+
+airIRG2IdentManufactureDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the unit manufacture date."
+ ::= { airIRG2Ident 7 }
+
+airIRG2IdentUnitSysOID OBJECT-TYPE
+ SYNTAX OBJECT IDENTIFIER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID contains an OID path to the device's top level unit data."
+ ::= { airIRG2Ident 8 }
+
+airIRG2IdentGroupSysOID OBJECT-TYPE
+ SYNTAX OBJECT IDENTIFIER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID contains an OID path to the device's top level group data."
+ ::= { airIRG2Ident 9 }
+
+-- ******************************************************************
+-- airIRG2 GROUP Status
+-- ******************************************************************
+
+airIRG2GroupStatusCoolOutput OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group cooling output in tenths of kilowatts (kW)."
+ ::= { airIRG2GroupStatus 1 }
+
+airIRG2GroupStatusCoolDemand OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group cooling demand in tenths of kilowatts (kW)."
+ ::= { airIRG2GroupStatus 2 }
+
+airIRG2GroupStatusAirFlowUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group air flow in cubic feet per minute."
+ ::= { airIRG2GroupStatus 3 }
+
+airIRG2GroupStatusAirFlowMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group air flow in hundredths of
+ liters per second."
+ ::= { airIRG2GroupStatus 4 }
+
+airIRG2GroupStatusMaxRackInletTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group maximum rack inlet temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRG2GroupStatus 5 }
+
+airIRG2GroupStatusMaxRackInletTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group maximum rack inlet temperature in tenths of
+ degrees Celsius."
+ ::= { airIRG2GroupStatus 6 }
+
+airIRG2GroupStatusMinRackInletTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group minimum rack inlet temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRG2GroupStatus 7 }
+
+airIRG2GroupStatusMinRackInletTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group minimum rack inlet temperature in tenths of
+ degrees Celsius."
+ ::= { airIRG2GroupStatus 8 }
+
+airIRG2GroupStatusMaxReturnAirTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group maximum return air temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRG2GroupStatus 9 }
+
+airIRG2GroupStatusMaxReturnAirTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group maximum return air temperature in tenths of
+ degrees Celsius."
+ ::= { airIRG2GroupStatus 10 }
+
+airIRG2GroupStatusMinReturnAirTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group minimum return air temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRG2GroupStatus 11 }
+
+airIRG2GroupStatusMinReturnAirTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group minimum return air temperature in tenths of
+ degrees Celsius."
+ ::= { airIRG2GroupStatus 12 }
+
+airIRG2GroupStatusActiveFlowControlStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ under (1),
+ okay (2),
+ over (3),
+ notApplicable (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Status of the active flow control
+ system."
+ ::= { airIRG2GroupStatus 13 }
+
+
+-- ******************************************************************
+-- airIRG2 GROUP Setpoint
+-- ******************************************************************
+
+airIRG2GroupSetptsCoolSetpointUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Group cooling setpoint in tenths of
+ degrees Fahrenheit."
+ ::= { airIRG2GroupSetpoints 1 }
+
+airIRG2GroupSetptsCoolSetpointMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Group cooling setpoint in tenths of
+ degrees Celsius."
+ ::= { airIRG2GroupSetpoints 2 }
+
+airIRG2GroupSetptsCoolDeadbandUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Group cooling deadband in tenths of
+ degrees Fahrenheit."
+ ::= { airIRG2GroupSetpoints 3 }
+
+airIRG2GroupSetptsCoolDeadbandMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Group cooling deadband in tenths of
+ degrees Celsius."
+ ::= { airIRG2GroupSetpoints 4 }
+
+airIRG2GroupSetptsFanSpeedPreference OBJECT-TYPE
+ SYNTAX INTEGER {
+ low (1),
+ med-low (2),
+ med (3),
+ med-high (4),
+ high (5)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The group preferred fan speed setting."
+ ::= { airIRG2GroupSetpoints 5 }
+
+airIRG2GroupSetptsSupplyAirSetpointUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Group supply air setpoint in tenths of
+ degrees Fahrenheit."
+ ::= { airIRG2GroupSetpoints 6 }
+
+airIRG2GroupSetptsSupplyAirSetpointMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Group supply air setpoint in tenths of
+ degrees Celsius."
+ ::= { airIRG2GroupSetpoints 7 }
+
+airIRG2GroupSetpointsActiveFlowControlBias OBJECT-TYPE
+ SYNTAX INTEGER {
+ positive (1),
+ slightlyPositive (2),
+ zero (3),
+ slightlyNegative (4),
+ negative (5)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The active flow control bias setting."
+ ::= { airIRG2GroupSetpoints 8 }
+
+-- ******************************************************************
+-- airIRG2 GROUP Config
+-- ******************************************************************
+airIRG2GroupConfigNumberofCoolingUnits OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The number of cooling units."
+ ::= { airIRG2GroupConfig 1 }
+
+airIRG2GroupConfigConfigurationType OBJECT-TYPE
+ SYNTAX INTEGER {
+ racs (1),
+ spot (2),
+ in-row (3),
+ hacs (4),
+ cacs (5)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The group configuration type."
+ ::= { airIRG2GroupConfig 2 }
+
+airIRG2GroupConfigCapacityControlType OBJECT-TYPE
+ SYNTAX INTEGER {
+ discrete (1),
+ proportional (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The group capacity control."
+ ::= { airIRG2GroupConfig 3 }
+
+airIRG2GroupConfigFanSpeedControl OBJECT-TYPE
+ SYNTAX INTEGER {
+ automatic (1),
+ manual (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The group fan speed control."
+ ::= { airIRG2GroupConfig 4 }
+
+airIRG2GroupConfigCoolGainP OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The gain component of the PID in hundredths."
+ ::= { airIRG2GroupConfig 5 }
+
+airIRG2GroupConfigCoolResetRateI OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The integral component of the PID in hundredths."
+ ::= { airIRG2GroupConfig 6 }
+
+airIRG2GroupConfigCoolDerivativeD OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The derivative component of the PID in hundredths."
+ ::= { airIRG2GroupConfig 7 }
+
+airIRG2GroupConfigCoolPIDReset OBJECT-TYPE
+ SYNTAX INTEGER {
+ readBack (1),
+ reset (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Will reset the PID coefficients back to the factory defaults."
+ ::= { airIRG2GroupConfig 8 }
+
+airIRG2GroupConfigNumberofBackupUnits OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The number of backup units."
+ ::= { airIRG2GroupConfig 9 }
+
+airIRG2GroupConfigRuntimeBalancingEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable runtime balancing feature."
+ ::= { airIRG2GroupConfig 10 }
+
+airIRG2GroupConfigLoadAssistEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable load assist feature."
+ ::= { airIRG2GroupConfig 11 }
+
+airIRG2GroupConfigNumberOfActiveFlowControllers OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The number of active flow controllers
+ present in the group."
+ ::= { airIRG2GroupConfig 12 }
+
+airIRG2GroupConfigActiveFlowControllerLampTest OBJECT-TYPE
+ SYNTAX INTEGER {
+ off (1),
+ on (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Turns off/on the active flow
+ controller lamp test."
+ ::= { airIRG2GroupConfig 13 }
+
+airIRG2GroupConfigAltitudeUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The group altitude of the units above sea level in feet."
+ ::= { airIRG2GroupConfig 14 }
+
+airIRG2GroupConfigAltitudeMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The group altitude of the units above sea level in meters."
+ ::= { airIRG2GroupConfig 15 }
+
+-- ***************************************
+-- airIRG2 Alarm Status
+-- ***************************************
+
+airIRG2AlarmsTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of active alarms in the airIRG2AlarmsTable."
+ ::= { airIRG2Alarms 1 }
+
+AirIRG2AlarmsEntry ::= SEQUENCE {
+ airIRG2AlarmsIndex INTEGER,
+ airIRG2AlarmsEventCode INTEGER,
+ airIRG2AlarmsDescription DisplayString
+ }
+
+airIRG2AlarmsTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AirIRG2AlarmsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Table of active alarms for the device."
+ ::= { airIRG2Alarms 2 }
+
+airIRG2AlarmsEntry OBJECT-TYPE
+ SYNTAX AirIRG2AlarmsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Alarms specification"
+ INDEX { airIRG2AlarmsIndex }
+ ::= { airIRG2AlarmsTable 1 }
+
+airIRG2AlarmsIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Alarm index."
+ ::= { airIRG2AlarmsEntry 1 }
+
+airIRG2AlarmsEventCode OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Code for the alarm."
+ ::= { airIRG2AlarmsEntry 2 }
+
+airIRG2AlarmsDescription OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..64))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Description of the alarm."
+ ::= { airIRG2AlarmsEntry 3 }
+
+-- ***************************************
+-- airIRG2RDType2 AIR CONDITIONER Defines
+-- ***************************************
+
+AirIRG2RDType2IOState ::= INTEGER {
+ open (1),
+ closed (2)
+}
+
+-- ******************************************************************
+-- airIRG2RDT2 Status
+-- ******************************************************************
+
+airIRG2RDT2StatusOperateMode OBJECT-TYPE
+ SYNTAX INTEGER {
+ standby (1),
+ on (2),
+ idle (3),
+ reserved (4),
+ service (5)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The cooling unit operating mode."
+ ::= { airIRG2RDT2Status 1 }
+
+airIRG2RDT2StatusCoolOutput OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit cooling output in tenths of kilowatts (kW)."
+ ::= { airIRG2RDT2Status 2 }
+
+airIRG2RDT2StatusCoolDemand OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit cooling demand in tenths of kilowatts (kW)."
+ ::= { airIRG2RDT2Status 3 }
+
+airIRG2RDT2StatusAirFlowUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit air flow in cubic feet per minute."
+ ::= { airIRG2RDT2Status 4 }
+
+airIRG2RDT2StatusAirFlowMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit air flow in liters per second."
+ ::= { airIRG2RDT2Status 5 }
+
+airIRG2RDT2StatusRackInletTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit rack inlet temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRG2RDT2Status 6 }
+
+airIRG2RDT2StatusRackInletTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit rack inlet temperature in tenths of
+ degrees Celsius."
+ ::= { airIRG2RDT2Status 7 }
+
+airIRG2RDT2StatusSupplyAirTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit supply air temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRG2RDT2Status 8 }
+
+airIRG2RDT2StatusSupplyAirTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit supply air temperature in tenths of
+ degrees Celsius."
+ ::= { airIRG2RDT2Status 9 }
+
+airIRG2RDT2StatusReturnAirTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit return air temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRG2RDT2Status 10 }
+
+airIRG2RDT2StatusReturnAirTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit return air temperature in tenths of
+ degrees Celsius."
+ ::= { airIRG2RDT2Status 11 }
+
+airIRG2RDT2StatusSuctionTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit suction temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRG2RDT2Status 12 }
+
+airIRG2RDT2StatusSuctionTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit suction temperature in tenths of
+ degrees Celsius."
+ ::= { airIRG2RDT2Status 13 }
+
+airIRG2RDT2StatusSuperheatTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit superheat temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRG2RDT2Status 14 }
+
+airIRG2RDT2StatusSuperheatTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit superheat temperature in tenths of
+ degrees Celsius."
+ ::= { airIRG2RDT2Status 15 }
+
+airIRG2RDT2StatusFilterDPUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit air filter differential pressure in
+ hundredths of inches of water."
+ ::= { airIRG2RDT2Status 16 }
+
+airIRG2RDT2StatusFilterDPMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit air filter differential pressure in pascals (Pa)."
+ ::= { airIRG2RDT2Status 17 }
+
+airIRG2RDT2StatusSuctionPressureUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit suction pressure in pounds per square inch (PSI)."
+ ::= { airIRG2RDT2Status 18 }
+
+airIRG2RDT2StatusSuctionPressureMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit suction pressure in kiloPascals (kPa)."
+ ::= { airIRG2RDT2Status 19 }
+
+airIRG2RDT2StatusDischargePressureUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit discharge pressure in pounds per square inch (PSI)."
+ ::= { airIRG2RDT2Status 20 }
+
+airIRG2RDT2StatusDischargePressureMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit discharge pressure in kiloPascals (kPa)."
+ ::= { airIRG2RDT2Status 21 }
+
+airIRG2RDT2StatusEvaporatorFanSpeed OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The unit average evaporator fan speed in tenths of percent."
+ ::= { airIRG2RDT2Status 22 }
+
+airIRG2RDT2StatusInputState OBJECT-TYPE
+ SYNTAX AirIRG2RDType2IOState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The state of the input contact."
+ ::= { airIRG2RDT2Status 23 }
+
+airIRG2RDT2StatusOutputState OBJECT-TYPE
+ SYNTAX AirIRG2RDType2IOState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The state of the output relay."
+ ::= { airIRG2RDT2Status 24 }
+
+airIRG2RDT2StatusOHEInputState OBJECT-TYPE
+ SYNTAX AirIRG2RDType2IOState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The state of the outside heat exchanger(OHE) input contact."
+ ::= { airIRG2RDT2Status 25 }
+
+airIRG2RDT2StatusOHEOutputState OBJECT-TYPE
+ SYNTAX AirIRG2RDType2IOState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The state of the outside heat exchanger(OHE) output relay."
+ ::= { airIRG2RDT2Status 26 }
+
+airIRG2RDT2StatusCompressor OBJECT-TYPE
+ SYNTAX INTEGER {
+ off (1),
+ on (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The state (off/on) of the compressor."
+ ::= { airIRG2RDT2Status 27 }
+
+airIRG2RDT2StatusFluidValvePos OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The position of the fluid valve in percent. This OID is only valid
+ when airIRG2RDT2ConfigUnitType indicates fluidCooled(1)."
+ ::= { airIRG2RDT2Status 28 }
+
+airIRG2RDT2StatusHotGasBypassValvePos OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The position of the hot gas bypass valve in hundredths of percent."
+ ::= { airIRG2RDT2Status 29 }
+
+airIRG2RDT2StatusLeakSensor OBJECT-TYPE
+ SYNTAX INTEGER {
+ no-leak (1),
+ leak (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The state (no-leak/leak) of the leak sensor."
+ ::= { airIRG2RDT2Status 30 }
+
+-- ******************************************************************
+-- airIRG2RDT2 Runhours
+-- ******************************************************************
+
+airIRG2RDT2RunHoursAirFilter OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit air filter run hours."
+ ::= { airIRG2RDT2RunHours 1 }
+
+airIRG2RDT2RunHoursCondensatePump OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit condensate pump run hours."
+ ::= { airIRG2RDT2RunHours 2 }
+
+airIRG2RDT2RunHoursCompressor OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit compressor run hours."
+ ::= { airIRG2RDT2RunHours 3 }
+
+-- *******************************
+-- Run Hour Fan Power supply table
+-- *******************************
+airIRG2RDT2RunHoursFanPSTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the run hour fan power supply table
+ (airIRG2RDT2RunHoursFanPSTable)."
+ ::= { airIRG2RDT2RunHours 4 }
+
+AirIRG2RDT2RunHoursFanPSEntry ::=
+ SEQUENCE {
+ airIRG2RDT2RunHoursFanPSIndex INTEGER,
+ airIRG2RDT2RunHoursFanPSPosition INTEGER,
+ airIRG2RDT2RunHoursFanPSHours INTEGER
+ }
+
+airIRG2RDT2RunHoursFanPSTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AirIRG2RDT2RunHoursFanPSEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting run hour information from each power supply."
+ ::= { airIRG2RDT2RunHours 5 }
+
+airIRG2RDT2RunHoursFanPSEntry OBJECT-TYPE
+ SYNTAX AirIRG2RDT2RunHoursFanPSEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The run hours fan power supply table entry."
+ INDEX { airIRG2RDT2RunHoursFanPSIndex }
+ ::= { airIRG2RDT2RunHoursFanPSTable 1 }
+
+airIRG2RDT2RunHoursFanPSIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index of run hours fan power supply table."
+ ::= { airIRG2RDT2RunHoursFanPSEntry 1 }
+
+airIRG2RDT2RunHoursFanPSHours OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Fan power supply run time in hours."
+ ::= { airIRG2RDT2RunHoursFanPSEntry 2 }
+
+airIRG2RDT2RunHoursFanPSPosition OBJECT-TYPE
+ SYNTAX INTEGER {
+ upper (1),
+ lower (2),
+ left (3),
+ right (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Position of fan power supply within the unit."
+ ::= { airIRG2RDT2RunHoursFanPSEntry 3 }
+
+-- *****************************
+-- Run Hour Evaporator Fan table
+-- *****************************
+airIRG2RDT2RunHoursEvapFanTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the run hour evaporator fan table
+ (airIRG2RDT2RunHoursEvapFanTable)."
+ ::= { airIRG2RDT2RunHours 6 }
+
+AirIRG2RDT2RunHoursEvapFanEntry ::=
+ SEQUENCE {
+ airIRG2RDT2RunHoursEvapFanIndex INTEGER,
+ airIRG2RDT2RunHoursEvapFanHours INTEGER
+ }
+
+airIRG2RDT2RunHoursEvapFanTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AirIRG2RDT2RunHoursEvapFanEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting information from each evaporator fan run
+ hour in the system. "
+ ::= { airIRG2RDT2RunHours 7 }
+
+airIRG2RDT2RunHoursEvapFanEntry OBJECT-TYPE
+ SYNTAX AirIRG2RDT2RunHoursEvapFanEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting information from each evaporator fan run
+ hour in the system. "
+ INDEX { airIRG2RDT2RunHoursEvapFanIndex }
+ ::= { airIRG2RDT2RunHoursEvapFanTable 1 }
+
+airIRG2RDT2RunHoursEvapFanIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index of run hours evaporator fan table."
+ ::= { airIRG2RDT2RunHoursEvapFanEntry 1 }
+
+airIRG2RDT2RunHoursEvapFanHours OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Evaporator fan run time in hours."
+ ::= { airIRG2RDT2RunHoursEvapFanEntry 2 }
+
+airIRG2RDT2RunHoursUnit OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit run time in hours."
+ ::= { airIRG2RDT2RunHours 8 }
+
+-- ******************************************************************
+-- airIRG2RDT2 Service Intervals
+-- ******************************************************************
+
+airIRG2RDT2ServiceIntervalsAirFilter OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Air filter service interval in weeks."
+ ::= { airIRG2RDT2ServiceIntervals 1 }
+
+airIRG2RDT2ServiceIntervalsAirFilterAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ enable (1),
+ disable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The air filter service interval alarm enable/disable."
+ ::= { airIRG2RDT2ServiceIntervals 2 }
+
+-- ******************************************************************
+-- airIRG2RDT2 Thresholds
+-- ******************************************************************
+
+airIRG2RDT2ThresholdsRackInletHighTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unit rack inlet air high temperature threshold in
+ tenths of degrees Fahrenheit."
+ ::= { airIRG2RDT2Thresholds 1 }
+
+airIRG2RDT2ThresholdsRackInletHighTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unit rack inlet air high temperature threshold in
+ tenths of degrees Celsius."
+ ::= { airIRG2RDT2Thresholds 2 }
+
+airIRG2RDT2ThresholdsSupplyAirHighTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unit supply air high temperature threshold in
+ tenths of degrees Fahrenheit."
+ ::= { airIRG2RDT2Thresholds 3 }
+
+airIRG2RDT2ThresholdsSupplyAirHighTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unit supply air high temperature threshold in
+ tenths of degrees Celsius."
+ ::= { airIRG2RDT2Thresholds 4 }
+
+airIRG2RDT2ThresholdsReturnAirHighTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unit return air high temperature threshold in
+ tenths of degrees Fahrenheit."
+ ::= { airIRG2RDT2Thresholds 5 }
+
+airIRG2RDT2ThresholdsReturnAirHighTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unit return air high temperature threshold in
+ tenths of degrees Celsius."
+ ::= { airIRG2RDT2Thresholds 6 }
+
+-- ******************************************************************
+-- airIRG2RDT2 Setpoints
+-- ******************************************************************
+
+-- There are no setpoint OIDs. This is just a placeholder in case
+-- we add some unit setpoints.
+
+-- ******************************************************************
+-- airIRG2RDT2 Config
+-- ******************************************************************
+
+airIRG2RDT2ConfigUnitType OBJECT-TYPE
+ SYNTAX INTEGER {
+ fluidCooled (1),
+ airCooled (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The type of the unit."
+ ::= { airIRG2RDT2Config 1 }
+
+airIRG2RDT2ConfigStartupDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The startup delay in seconds."
+ ::= { airIRG2RDT2Config 2 }
+
+airIRG2RDT2ConfigIdleOnLeakDetect OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The idle on leak options setting."
+ ::= { airIRG2RDT2Config 3 }
+
+airIRG2RDT2ConfigInputNormalState OBJECT-TYPE
+ SYNTAX AirIRG2RDType2IOState
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The normal state of the input contact."
+ ::= { airIRG2RDT2Config 4 }
+
+airIRG2RDT2ConfigOutputNormalState OBJECT-TYPE
+ SYNTAX AirIRG2RDType2IOState
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The normal state of the output relay."
+ ::= { airIRG2RDT2Config 5 }
+
+airIRG2RDT2ConfigOutputSource OBJECT-TYPE
+ SYNTAX INTEGER {
+ anyAlarm (1),
+ criticalAlarm (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The source of output relay change."
+ ::= { airIRG2RDT2Config 6 }
+
+airIRG2RDT2ConfigOHEInputNormalState OBJECT-TYPE
+ SYNTAX AirIRG2RDType2IOState
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The normal state of the outside heat exchanger(OHE) input relay."
+ ::= { airIRG2RDT2Config 7 }
+
+airIRG2RDT2ConfigUnitRoleOverride OBJECT-TYPE
+ SYNTAX INTEGER {
+ automatic (1),
+ forcedOn (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "When this OID value is (1) automatic, the system determines
+ which units are used as primary units and which units are used as backups.
+ When this OID value is (2) forcedOn, the connected unit is set as a primary
+ unit."
+ ::= { airIRG2RDT2Config 8 }
+
+airIRG2RDT2ConfigUnitIdleOnCoolFail OBJECT-TYPE
+ SYNTAX INTEGER {
+ no (1),
+ yes (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "When this OID value is (2) yes, the unit idles if it detects that it is blowing warm
+ air into the cold aisle. The unit will attempt to restart at 5 minute intervals."
+ ::= { airIRG2RDT2Config 9 }
+
+-- Beginning of AC InRoom
+
+-- common InRoom values
+AirIRmAlarmState ::= INTEGER { ok (1), alarm (2) }
+AirIRmControlState ::= INTEGER { off (1), on (2) }
+AirIRmStopState ::= INTEGER { maybeOn (1), unitOff (2) }
+AirIRmActivityState ::= INTEGER { inactive (1), active (2) }
+
+
+-- ***************************************
+-- InRoom Ident
+-- ***************************************
+
+airIRmIdentName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the unit name."
+ ::= { airIRmIdent 1 }
+
+airIRmIdentLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the unit location."
+ ::= { airIRmIdent 2 }
+
+airIRmIdentModelNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the unit model number."
+ ::= { airIRmIdent 3 }
+
+airIRmIdentSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the unit serial number."
+ ::= { airIRmIdent 4 }
+
+airIRmIdentFirmwareRevision OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the unit firmware version."
+ ::= { airIRmIdent 5 }
+
+airIRmIdentHardwareRevision OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the unit controller hardware revision."
+ ::= { airIRmIdent 6 }
+
+airIRmIdentManufactureDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the unit manufacture date."
+ ::= { airIRmIdent 7 }
+
+airIRmIdentSysOID OBJECT-TYPE
+ SYNTAX OBJECT IDENTIFIER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID contains an OID path to the device's top level data."
+ ::= { airIRmIdent 8 }
+
+-- ***************************************
+-- InRoom Alarm Status
+-- ***************************************
+
+airIRmAlarmsTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of active alarms in the airIRG2AlarmsTable."
+ ::= { airIRmAlarms 1 }
+
+AirIRmAlarmsEntry ::= SEQUENCE {
+ airIRmAlarmsIndex INTEGER,
+ airIRmAlarmsEventCode INTEGER,
+ airIRmAlarmsDescription DisplayString
+ }
+
+airIRmAlarmsTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AirIRmAlarmsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Table of active alarms for the device."
+ ::= { airIRmAlarms 2 }
+
+airIRmAlarmsEntry OBJECT-TYPE
+ SYNTAX AirIRmAlarmsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Alarms specification"
+ INDEX { airIRmAlarmsIndex }
+ ::= { airIRmAlarmsTable 1 }
+
+airIRmAlarmsIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Alarm index."
+ ::= { airIRmAlarmsEntry 1 }
+
+airIRmAlarmsEventCode OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Code for the alarm."
+ ::= { airIRmAlarmsEntry 2 }
+
+airIRmAlarmsDescription OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..64))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Description of the alarm."
+ ::= { airIRmAlarmsEntry 3 }
+
+
+-- airIRmPmCommon1
+
+airIRmPmUnitType OBJECT-TYPE
+ SYNTAX INTEGER {
+ mc (1),
+ dx (2),
+ cw (3),
+ ch (4),
+ ecoCool (5),
+ msc (6),
+ ge1 (7),
+ ge2 (8),
+ dualFluid (9),
+ cw2 (10),
+ unknown (256) }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit type (1)."
+ ::= { airIRmPmCommon1 1 }
+
+airIRmPmSwVersion OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Software version (3)."
+ ::= { airIRmPmCommon1 3 }
+
+airIRmPmBusAddress OBJECT-TYPE
+ SYNTAX INTEGER (0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Bus addresss of unit (5)."
+ ::= { airIRmPmCommon1 5 }
+
+airIRmPmControllerType OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ c4000 (2),
+ c1001 (3),
+ c1002 (4),
+ c5000 (5),
+ c6000 (6),
+ c1010 (7),
+ c7000IOC (8),
+ c7000AT (9),
+ c7000PT (10),
+ c5MSC (11),
+ c7000PT2 (12) }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Controller type (7)."
+ ::= { airIRmPmCommon1 7 }
+
+airIRmPmGeneralError OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "General Error (8)"
+ ::= { airIRmPmCommon1 8 }
+
+airIRmPmErrorOnBus OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Error On Bus (9)"
+ ::= { airIRmPmCommon1 9 }
+
+-- airIRmPmCommon2
+
+airIRmPmPCStop OBJECT-TYPE
+ SYNTAX AirIRmStopState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "PC-STOP (1000)"
+ ::= { airIRmPmCommon2 1 }
+
+airIRmPmRemoteStop OBJECT-TYPE
+ SYNTAX AirIRmStopState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Remote Stop (1001)"
+ ::= { airIRmPmCommon2 2 }
+
+airIRmPmLocalStop OBJECT-TYPE
+ SYNTAX AirIRmStopState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Local Stop (1002)"
+ ::= { airIRmPmCommon2 3}
+
+airIRmPmTimerStop OBJECT-TYPE
+ SYNTAX AirIRmStopState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Timer Stop (1003)"
+ ::= { airIRmPmCommon2 4}
+
+airIRmPmSeqStop OBJECT-TYPE
+ SYNTAX AirIRmStopState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Seq. Stop (1004)"
+ ::= { airIRmPmCommon2 5}
+
+airIRmPmRemoteUPS OBJECT-TYPE
+ SYNTAX INTEGER {
+ off (1),
+ on (2) }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Remote UPS (1006)"
+ ::= { airIRmPmCommon2 7}
+
+airIRmPmLocalUPS OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Local UPS (1007)"
+ ::= { airIRmPmCommon2 8}
+
+airIRmPmCommonAlarm OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Common alarm (1010)."
+ ::= { airIRmPmCommon2 11 }
+
+airIRmPmResetAllAlarms OBJECT-TYPE
+ SYNTAX INTEGER {
+ doNothing (1),
+ reset (2) }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Reset all alarms control (1011)."
+ ::= { airIRmPmCommon2 12 }
+
+airIRmPmUnitOnOff OBJECT-TYPE
+ SYNTAX AirIRmControlState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit running state (1013)."
+ ::= { airIRmPmCommon2 14 }
+
+airIRmPmMaintenance OBJECT-TYPE
+ SYNTAX INTEGER {
+ notNecessary (1),
+ necessary (2) }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Maintenance necessary state (1014)."
+ ::= { airIRmPmCommon2 15 }
+
+airIRmPmUnitTemperatureScale OBJECT-TYPE
+ SYNTAX INTEGER {
+ celsius (1),
+ fahrenheit (2) }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Current Unit Temperature Scale (1022)."
+ ::= { airIRmPmCommon2 23 }
+
+airIRmPmUnitWinterMode OBJECT-TYPE
+ SYNTAX INTEGER {
+ summer (1),
+ winter (2) }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Winter or summer configuration mode (1023)."
+ ::= { airIRmPmCommon2 24 }
+
+airIRmPmDayNightMode OBJECT-TYPE
+ SYNTAX INTEGER {
+ day (1),
+ night (2) }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Day or night configuration mode (1024)."
+ ::= { airIRmPmCommon2 25 }
+
+
+-- airIRmPmCommon3
+
+airIRmPmLastMaintenanceYear OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Last maintenance year (1160)."
+ ::= { airIRmPmCommon3 1 }
+
+airIRmPmLastMaintenanceMonth OBJECT-TYPE
+ SYNTAX INTEGER (1..12)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Last maintenance month (1161)."
+ ::= { airIRmPmCommon3 2 }
+
+airIRmPmLastMaintenanceDay OBJECT-TYPE
+ SYNTAX INTEGER (1..31)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Last maintenance day (1162)."
+ ::= { airIRmPmCommon3 3 }
+
+airIRmPmUnitMaintenanceInterval OBJECT-TYPE
+ SYNTAX INTEGER (1..255)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit maintenance interval in months (1163)."
+ ::= { airIRmPmCommon3 4 }
+
+airIRmPmRuntimeUnit OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Runtime unit in hours (1164)."
+ ::= { airIRmPmCommon3 5 }
+
+airIRmPmStoptimeUnit OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit stoptime in hours (1165)"
+ ::= { airIRmPmCommon3 6 }
+
+airIRmPmRuntimeCooling OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Cooling runtime in hours (1166)"
+ ::= { airIRmPmCommon3 7 }
+
+airIRmPmRuntimeHeating OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Heating runtime in hours (1167)"
+ ::= { airIRmPmCommon3 8 }
+
+airIRmPmRuntimeHumidification OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Humidification runtime in hours (1168)"
+ ::= { airIRmPmCommon3 9 }
+
+airIRmPmRuntimeDehumidification OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Dehumidification runtime in hours (1169)"
+ ::= { airIRmPmCommon3 10 }
+
+airIRmPmUnitTemperature OBJECT IDENTIFIER ::= { airIRmPmCommon3 11 }
+airIRmPmUnitTemperatureC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit temperature in tenths of degrees Celsius (1170)."
+ ::= { airIRmPmUnitTemperature 1 }
+airIRmPmUnitTemperatureF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit temperature in tenths of degrees Fahrenheit (1170)."
+ ::= { airIRmPmUnitTemperature 2 }
+
+airIRmPmUnitHumidity OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit humidity in tenths of %RH (1171)."
+ ::= { airIRmPmCommon3 12 }
+
+airIRmPmSetpointTemperatureDay OBJECT IDENTIFIER ::= { airIRmPmCommon3 14 }
+airIRmPmSetpointTemperatureDayC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setpoint daytime temperature in tenths
+ of degrees Celsius (1173)."
+ ::= { airIRmPmSetpointTemperatureDay 1 }
+airIRmPmSetpointTemperatureDayF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setpoint daytime temperature in tenths
+ of degrees Fahrenheit (1173)."
+ ::= { airIRmPmSetpointTemperatureDay 2 }
+
+airIRmPmSetpointTemperatureNight OBJECT IDENTIFIER ::= { airIRmPmCommon3 15 }
+airIRmPmSetpointTemperatureNightC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setpoint nighttime temperature in tenths
+ of degrees Celsius (1174)."
+ ::= { airIRmPmSetpointTemperatureNight 1 }
+airIRmPmSetpointTemperatureNightF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setpoint nighttime temperature in tenths
+ of degrees Fahrenheit (1174)."
+ ::= { airIRmPmSetpointTemperatureNight 2 }
+
+airIRmPmSetpointHumidity OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setpoint humidity in tenths of %RH (1176)."
+ ::= { airIRmPmCommon3 17 }
+
+airIRmPmUnitControlType OBJECT-TYPE
+ SYNTAX INTEGER {
+ room (1),
+ supply (2),
+ room-SupplyLimit (3),
+ supply-RoomLimit (4) }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Current unit control type (1183)."
+ ::= { airIRmPmCommon3 24 }
+
+airIRmPmWinterModeStartTemp OBJECT IDENTIFIER ::= { airIRmPmCommon3 29 }
+airIRmPmWinterModeStartTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Winter mode start temperature in tenths of degrees Celsius (1188)."
+ ::= { airIRmPmWinterModeStartTemp 1 }
+airIRmPmWinterModeStartTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Winter mode start temperature in tenths of degrees Fahrenheit (1188)."
+ ::= { airIRmPmWinterModeStartTemp 2 }
+
+airIRmPmWinterModeHysteresis OBJECT IDENTIFIER ::= { airIRmPmCommon3 30 }
+airIRmPmWinterModeHysteresisK OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Winter mode hysteresis in tenths of Kelvins (1189)"
+ ::= { airIRmPmWinterModeHysteresis 1 }
+airIRmPmWinterModeHysteresisF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Winter mode hysteresis in tenths of degrees Fahrenheit (1189)"
+ ::= { airIRmPmWinterModeHysteresis 2 }
+
+airIRmPmWaterTemperature OBJECT IDENTIFIER ::= { airIRmPmCommon3 32 }
+airIRmPmWaterTemperatureC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Water temperature in tenths of degrees Celsius (1191)."
+ ::= { airIRmPmWaterTemperature 1 }
+airIRmPmWaterTemperatureF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Water temperature in tenths of degrees Fahrenheit (1191)."
+ ::= { airIRmPmWaterTemperature 2 }
+
+airIRmPmReturnAirTemperature OBJECT IDENTIFIER ::= { airIRmPmCommon3 33 }
+airIRmPmReturnAirTemperatureC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Return air temperature in tenths of degrees Celsius (1192)."
+ ::= { airIRmPmReturnAirTemperature 1 }
+airIRmPmReturnAirTemperatureF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Return air temperature in tenths of degrees Fahrenheit (1192)."
+ ::= { airIRmPmReturnAirTemperature 2 }
+
+airIRmPmSupplyAirTemperature OBJECT IDENTIFIER ::= { airIRmPmCommon3 34 }
+airIRmPmSupplyAirTemperatureC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Supply air temperature in tenths of degrees Celsius (1193)."
+ ::= { airIRmPmSupplyAirTemperature 1 }
+airIRmPmSupplyAirTemperatureF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Supply air temperature in tenths of degrees Fahrenheit (1193)."
+ ::= { airIRmPmSupplyAirTemperature 2 }
+
+airIRmPmReturnAirHumidity OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Return air humidity in tenths of %RH (1194)."
+ ::= { airIRmPmCommon3 35 }
+
+airIRmPmSupplyAirHumidity OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Supply air humidity in tenths of %RH (1195)."
+ ::= { airIRmPmCommon3 36 }
+
+airIRmPmOutsideAirTemperature OBJECT IDENTIFIER ::= { airIRmPmCommon3 37 }
+airIRmPmOutsideAirTemperatureC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Outside air temperature in tenths of degrees Celsius (1196)"
+ ::= { airIRmPmOutsideAirTemperature 1 }
+airIRmPmOutsideAirTemperatureF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Outside air temperature in tenths of degrees Fahrenheit (1196)"
+ ::= { airIRmPmOutsideAirTemperature 2 }
+
+airIRmPmOutsideAirHumidity OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Outside air humidity in tenths of percent relative humidity (1197)"
+ ::= { airIRmPmCommon3 38 }
+
+airIRmPmCoolingPriority OBJECT-TYPE
+ SYNTAX INTEGER {
+ ge (1),
+ cw (2),
+ dx (3) }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Cooling priority (1198)."
+ ::= { airIRmPmCommon3 39 }
+
+airIRmPmWaterTemperature2 OBJECT IDENTIFIER ::= { airIRmPmCommon3 43 }
+airIRmPmWaterTemperature2C OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Water temperature 2 in tenths of degrees Celsius (1202)."
+ ::= { airIRmPmWaterTemperature2 1 }
+airIRmPmWaterTemperature2F OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Water temperature 2 in tenths of degrees Fahrenheit (1202)."
+ ::= { airIRmPmWaterTemperature2 2 }
+
+airIRmPmRuntimeFreeCooling OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Freecooling runtime in hours (1203)"
+ ::= { airIRmPmCommon3 44 }
+
+airIRmPmRuntimeMixedModeFreeCooling OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Mixed mode freecooling runtime in hours (1203)"
+ ::= { airIRmPmCommon3 45 }
+
+-- airIRmPmCommon4
+
+airIRmPmNumberOfCompressors OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Number of compressors (1761)"
+ ::= { airIRmPmCommon4 4 }
+
+airIRmPmNumberOfSuctionValves OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Number of suction valves (1762)"
+ ::= { airIRmPmCommon4 5 }
+
+airIRmPmNumberOfDryCoolers OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Number of drycoolers (1763)"
+ ::= { airIRmPmCommon4 6 }
+
+airIRmPmNumberOfPumps OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Number of pumps (1764)"
+ ::= { airIRmPmCommon4 7 }
+
+airIRmPmNumberOfElectricHeaters OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Number of electric heaters (1765)"
+ ::= { airIRmPmCommon4 8 }
+
+airIRmPmNumberOfHumidifiers OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Number of humidifiers (1766)"
+ ::= { airIRmPmCommon4 9 }
+
+airIRmPmNumberOfFans OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Number of fans (1767)"
+ ::= { airIRmPmCommon4 10 }
+
+airIRmPmNumberOfLouvers OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Number of louvers (1768)"
+ ::= { airIRmPmCommon4 11 }
+
+airIRmPmNumberOfSensors OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Number of sensors (1769)"
+ ::= { airIRmPmCommon4 12 }
+
+airIRmPmNumberOfExternalAlarmInputs OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Number of external alarm inputs (1770)"
+ ::= { airIRmPmCommon4 13 }
+
+airIRmPmNumberOfGECWValves OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Number of GE/CW valves (1771)"
+ ::= { airIRmPmCommon4 14 }
+
+airIRmPmNumberOfHotGasReheat OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Number of hot gas reheaters (1772)"
+ ::= { airIRmPmCommon4 15 }
+
+airIRmPmNumberOfPWWReheat OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Number of PWW reheaters (1773)"
+ ::= { airIRmPmCommon4 16 }
+
+airIRmPmNumberOfDehumidifiers OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Number of dehumidifiers (1774)"
+ ::= { airIRmPmCommon4 17 }
+
+-- airIRmPmCommon5
+
+airIRmPmUnitEvaporationTemperature1 OBJECT IDENTIFIER ::= { airIRmPmCommon5 1 }
+airIRmPmUnitEvaporationTemperature1C OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit evaporation temperature 1 in tenths
+ of degrees Celsius (2232)"
+ ::= { airIRmPmUnitEvaporationTemperature1 1 }
+airIRmPmUnitEvaporationTemperature1F OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit evaporation temperature 1 in tenths
+ of degrees Fahrenheit (2232)"
+ ::= { airIRmPmUnitEvaporationTemperature1 2 }
+
+airIRmPmUnitEvaporationPressure1 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit evaporation pressure 1 in tenths
+ of Bars (2233)"
+ ::= { airIRmPmCommon5 2 }
+
+airIRmPmUnitCondensationTemperature1 OBJECT IDENTIFIER ::= { airIRmPmCommon5 3 }
+airIRmPmUnitCondensationTemperature1C OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit condensation temperature 1 in tenths
+ of degrees Celsius (2234)"
+ ::= { airIRmPmUnitCondensationTemperature1 1 }
+airIRmPmUnitCondensationTemperature1F OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit condensation temperature 1 in tenths
+ of degrees Fahrenheit (2234)"
+ ::= { airIRmPmUnitCondensationTemperature1 2 }
+
+airIRmPmUnitCondensationPressure1 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit condensation pressure 1 in tenths
+ of Bars (2235)"
+ ::= { airIRmPmCommon5 4 }
+
+airIRmPmMaxLimitReturnAirTemperature OBJECT IDENTIFIER ::= { airIRmPmCommon5 8 }
+airIRmPmMaxLimitReturnAirTemperatureC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Maximum limit return air temperature in tenths
+ of degrees Celsius (2239)."
+ ::= { airIRmPmMaxLimitReturnAirTemperature 1 }
+airIRmPmMaxLimitReturnAirTemperatureF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Maximum limit return air temperature in tenths
+ of degrees Fahrenheit (2239)."
+ ::= { airIRmPmMaxLimitReturnAirTemperature 2 }
+
+airIRmPmMinLimitReturnAirTemperature OBJECT IDENTIFIER ::= { airIRmPmCommon5 9 }
+airIRmPmMinLimitReturnAirTemperatureC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Minimum limit return air temperature in tenths
+ of degrees Celsius (2240)."
+ ::= { airIRmPmMinLimitReturnAirTemperature 1 }
+airIRmPmMinLimitReturnAirTemperatureF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Minimum limit return air temperature in tenths
+ of degrees Fahrenheit (2240)."
+ ::= { airIRmPmMinLimitReturnAirTemperature 2 }
+
+airIRmPmMaxLimitSupplyAirTemperature OBJECT IDENTIFIER ::= { airIRmPmCommon5 10 }
+airIRmPmMaxLimitSupplyAirTemperatureC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Maximum limit supply air temperature in tenths
+ of degrees Celsius (2241)."
+ ::= { airIRmPmMaxLimitSupplyAirTemperature 1 }
+airIRmPmMaxLimitSupplyAirTemperatureF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Maximum limit supply air temperature in tenths
+ of degrees Fahrenheit (2241)."
+ ::= { airIRmPmMaxLimitSupplyAirTemperature 2 }
+
+airIRmPmMinLimitSupplyAirTemperature OBJECT IDENTIFIER ::= { airIRmPmCommon5 11 }
+airIRmPmMinLimitSupplyAirTemperatureC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Minimum limit supply air temperature in tenths
+ of degrees Celsius (2242)."
+ ::= { airIRmPmMinLimitSupplyAirTemperature 1 }
+airIRmPmMinLimitSupplyAirTemperatureF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Minimum limit supply air temperature in tenths
+ of degrees Fahrenheit (2242)."
+ ::= { airIRmPmMinLimitSupplyAirTemperature 2 }
+
+airIRmPmMaxLimitWaterTemperature OBJECT IDENTIFIER ::= { airIRmPmCommon5 12 }
+airIRmPmMaxLimitWaterTemperatureC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Maximum limit water temperature in tenths of degrees Celsius (2243)."
+ ::= { airIRmPmMaxLimitWaterTemperature 1 }
+airIRmPmMaxLimitWaterTemperatureF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Maximum limit water temperature in tenths
+ of degrees Fahrenheit (2243)."
+ ::= { airIRmPmMaxLimitWaterTemperature 2 }
+
+airIRmPmMinLimitWaterTemperature OBJECT IDENTIFIER ::= { airIRmPmCommon5 13 }
+airIRmPmMinLimitWaterTemperatureC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Minimum limit water temperature in tenths
+ of degrees Celsius (2244)."
+ ::= { airIRmPmMinLimitWaterTemperature 1 }
+airIRmPmMinLimitWaterTemperatureF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Minimum limit water temperature in tenths
+ of degrees Fahrenheit (2244)."
+ ::= { airIRmPmMinLimitWaterTemperature 2 }
+
+airIRmPmMaxLimitReturnAirHumidity OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Maximum limit return air humidity in tenths of %RH (2245)."
+ ::= { airIRmPmCommon5 14 }
+
+airIRmPmMinLimitReturnAirHumidity OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Minimum limit return air humidity in tenths of %RH (2246)."
+ ::= { airIRmPmCommon5 15 }
+
+airIRmPmMaxLimitSupplyAirHumidity OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Maximum limit supply air humidity in tenths of %RH (2247)."
+ ::= { airIRmPmCommon5 16 }
+
+airIRmPmMinLimitSupplyAirHumidity OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Minimum limit supply air humidity in tenths of %RH (2248)."
+ ::= { airIRmPmCommon5 17 }
+
+airIRmPmLowPressureWinterDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Winter mode low pressure delay in seconds (2249)"
+ ::= { airIRmPmCommon5 18 }
+
+airIRmPmUnitCondensationPressure2 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit condensation pressure 2 in tenths of Bars (2250)"
+ ::= { airIRmPmCommon5 19 }
+
+airIRmPmUnitOverloadSwitch OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit overload switch setting in tenths of Kelvins (2251)"
+ ::= { airIRmPmCommon5 20 }
+
+airIRmPmUnitCondensationTemperature2 OBJECT IDENTIFIER ::= { airIRmPmCommon5 41 }
+airIRmPmUnitCondensationTemperature2C OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit condensation temperature 2 in tenths
+ of degrees Celsius (2272)"
+ ::= { airIRmPmUnitCondensationTemperature2 1 }
+airIRmPmUnitCondensationTemperature2F OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit condensation temperature 2 in tenths
+ of degrees Fahrenheit (2272)"
+ ::= { airIRmPmUnitCondensationTemperature2 2 }
+
+airIRmPmUnitEvaporationPressure2 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit evaporation pressure 2 in tenths
+ of Bars (2273)"
+ ::= { airIRmPmCommon5 42 }
+
+airIRmPmUnitEvaporationTemperature2 OBJECT IDENTIFIER ::= { airIRmPmCommon5 43 }
+airIRmPmUnitEvaporationTemperature2C OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit evaporation temperature 2 in tenths
+ of degrees Celsius (2274)"
+ ::= { airIRmPmUnitEvaporationTemperature2 1 }
+airIRmPmUnitEvaporationTemperature2F OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Unit evaporation temperature 2 in tenths
+ of degrees Fahrenheit (2274)"
+ ::= { airIRmPmUnitEvaporationTemperature2 2 }
+
+-- airIRmPmCompressor1
+
+airIRmPmCmp1ManOperationActive OBJECT-TYPE
+ SYNTAX INTEGER {
+ automatic (1),
+ manual (2) }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Compressor 1 manual operation active (4401)"
+ ::= { airIRmPmCompressor1 2 }
+
+airIRmPmCmp1ManOperationState OBJECT-TYPE
+ SYNTAX AirIRmControlState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Compressor 1 manual operation state (4402)"
+ ::= { airIRmPmCompressor1 3 }
+
+airIRmPmCmp1Running OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Compressor 1 running (4403)"
+ ::= { airIRmPmCompressor1 4 }
+
+airIRmPmCmp1StartTempSummer OBJECT IDENTIFIER ::= { airIRmPmCompressor1 17 }
+airIRmPmCmp1StartTempSummerK OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Compressor 1 summer mode start temperature
+ in tenths of Kelvins (4416)"
+ ::= { airIRmPmCmp1StartTempSummer 1 }
+airIRmPmCmp1StartTempSummerF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Compressor 1 summer mode start temperature
+ in tenths of degrees Fahrenheit (4416)"
+ ::= { airIRmPmCmp1StartTempSummer 2 }
+
+airIRmPmCmp1HysteresisSummer OBJECT IDENTIFIER ::= { airIRmPmCompressor1 18 }
+airIRmPmCmp1HysteresisSummerK OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Compressor 1 summer mode hysteresis setting
+ in tenths of Kelvins (4417)"
+ ::= { airIRmPmCmp1HysteresisSummer 1 }
+airIRmPmCmp1HysteresisSummerF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Compressor 1 summer mode hysteresis setting
+ in tenths of Fahrenheit (4417)"
+ ::= { airIRmPmCmp1HysteresisSummer 2 }
+
+airIRmPmCmp1StartTempWinter OBJECT IDENTIFIER ::= { airIRmPmCompressor1 19 }
+airIRmPmCmp1StartTempWinterK OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Compressor 1 winter mode start temperature
+ in tenths of Kelvins (4418)"
+ ::= { airIRmPmCmp1StartTempWinter 1 }
+airIRmPmCmp1StartTempWinterF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Compressor 1 winter mode start temperature
+ in tenths of degrees Fahrenheit (4418)"
+ ::= { airIRmPmCmp1StartTempWinter 2 }
+
+airIRmPmCmp1HysteresisWinter OBJECT IDENTIFIER ::= { airIRmPmCompressor1 20 }
+airIRmPmCmp1HysteresisWinterK OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Compressor 1 Winter mode hysteresis setting
+ in tenths of Kelvins (4419)"
+ ::= { airIRmPmCmp1HysteresisWinter 1 }
+airIRmPmCmp1HysteresisWinterF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Compressor 1 Winter mode hysteresis setting
+ in tenths of Fahrenheit (4419)"
+ ::= { airIRmPmCmp1HysteresisWinter 2 }
+
+airIRmPmCmp1Runtime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Compressor 1 runtime in hours (4428)"
+ ::= { airIRmPmCompressor1 29 }
+
+-- airIRmPmCompressor2
+
+airIRmPmCmp2ManOperationActive OBJECT-TYPE
+ SYNTAX INTEGER {
+ automatic (1),
+ manual (2) }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Compressor 2 manual operation active (4501)"
+ ::= { airIRmPmCompressor2 2 }
+
+airIRmPmCmp2ManOperationState OBJECT-TYPE
+ SYNTAX AirIRmControlState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Compressor 2 manual operation state (4502)"
+ ::= { airIRmPmCompressor2 3 }
+
+airIRmPmCmp2Running OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Compressor 2 running (4503)"
+ ::= { airIRmPmCompressor2 4 }
+
+airIRmPmCmp2StartTempSummer OBJECT IDENTIFIER ::= { airIRmPmCompressor2 17 }
+airIRmPmCmp2StartTempSummerK OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Compressor 2 summer mode start temperature
+ in tenths of Kelvins (4516)"
+ ::= { airIRmPmCmp2StartTempSummer 1 }
+airIRmPmCmp2StartTempSummerF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Compressor 2 summer mode start temperature
+ in tenths of degrees Fahrenheit (4516)"
+ ::= { airIRmPmCmp2StartTempSummer 2 }
+
+airIRmPmCmp2HysteresisSummer OBJECT IDENTIFIER ::= { airIRmPmCompressor2 18 }
+airIRmPmCmp2HysteresisSummerK OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Compressor 2 summer mode hysteresis setting
+ in tenths of Kelvins (4517)"
+ ::= { airIRmPmCmp2HysteresisSummer 1 }
+airIRmPmCmp2HysteresisSummerF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Compressor 2 summer mode hysteresis setting
+ in tenths of Fahrenheit (4517)"
+ ::= { airIRmPmCmp2HysteresisSummer 2 }
+
+airIRmPmCmp2StartTempWinter OBJECT IDENTIFIER ::= { airIRmPmCompressor2 19 }
+airIRmPmCmp2StartTempWinterK OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Compressor 2 winter mode start temperature
+ in tenths of Kelvins (4518)"
+ ::= { airIRmPmCmp2StartTempWinter 1 }
+airIRmPmCmp2StartTempWinterF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Compressor 2 winter mode start temperature
+ in tenths of degrees Fahrenheit (4518)"
+ ::= { airIRmPmCmp2StartTempWinter 2 }
+
+airIRmPmCmp2HysteresisWinter OBJECT IDENTIFIER ::= { airIRmPmCompressor2 20 }
+airIRmPmCmp2HysteresisWinterK OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Compressor 2 Winter mode hysteresis setting
+ in tenths of Kelvins (4519)"
+ ::= { airIRmPmCmp2HysteresisWinter 1 }
+airIRmPmCmp2HysteresisWinterF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Compressor 2 Winter mode hysteresis setting
+ in tenths of Fahrenheit (4519)"
+ ::= { airIRmPmCmp2HysteresisWinter 2 }
+
+airIRmPmCmp2Runtime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Compressor 2 runtime in hours (4528)"
+ ::= { airIRmPmCompressor2 29 }
+
+-- airIRmPmSuctionValve1
+-- Empty
+
+-- airIRmPmSuctionValve2
+-- Empty
+
+-- airIRmPmEheating1
+
+airIRmPmEheating1ManOpEnable OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Electric heater #1 manual operation enable (4801)"
+ ::= { airIRmPmEheating1 2 }
+
+airIRmPmEheating1Running OBJECT-TYPE
+ SYNTAX AirIRmControlState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Electric heater #1 running state (4803)"
+ ::= { airIRmPmEheating1 4 }
+
+airIRmPmEheating1ManOpRunning OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Electric heater #1 running in manual operation mode (4804)"
+ ::= { airIRmPmEheating1 5 }
+
+airIRmPmEheating1Type OBJECT-TYPE
+ SYNTAX INTEGER {
+ direct (1),
+ pwm (2) }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Electric heater #1 type (4808)"
+ ::= { airIRmPmEheating1 9 }
+
+airIRmPmEheating1StartTemperature OBJECT IDENTIFIER ::= { airIRmPmEheating1 10 }
+airIRmPmEheating1StartTemperatureK OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Electric heater #1 start temperature in tenths of Kelvins (4809)"
+ ::= { airIRmPmEheating1StartTemperature 1 }
+airIRmPmEheating1StartTemperatureF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Electric heater #1 start temperature in tenths of degrees Fahrenheit (4809)"
+ ::= { airIRmPmEheating1StartTemperature 2 }
+
+airIRmPmEheating1Hysteresis OBJECT IDENTIFIER ::= { airIRmPmEheating1 11 }
+airIRmPmEheating1HysteresisK OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Electric heater #1 hysteresis in tenths of Kelvins (4810)"
+ ::= { airIRmPmEheating1Hysteresis 1 }
+airIRmPmEheating1HysteresisF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Electric heater #1 hysteresis in tenths of degrees Fahrenheit (4810)"
+ ::= { airIRmPmEheating1Hysteresis 2 }
+
+airIRmPmEheating1Runtime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Electric heater #1 runtime in hours (4816)"
+ ::= { airIRmPmEheating1 17 }
+
+-- airIRmPmEheating2
+
+airIRmPmEheating2ManOpEnable OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Electric heater #2 manual operation enable (4901)"
+ ::= { airIRmPmEheating2 2 }
+
+airIRmPmEheating2Running OBJECT-TYPE
+ SYNTAX AirIRmControlState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Electric heater #2 running state (4903)"
+ ::= { airIRmPmEheating2 4 }
+
+airIRmPmEheating2ManOpRunning OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Electric heater #2 running in manual operation mode (4904)"
+ ::= { airIRmPmEheating2 5 }
+
+airIRmPmEheating2Type OBJECT-TYPE
+ SYNTAX INTEGER {
+ direct (1),
+ pwm (2) }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Electric heater #2 type (4908)"
+ ::= { airIRmPmEheating2 9 }
+
+airIRmPmEheating2StartTemperature OBJECT IDENTIFIER ::= { airIRmPmEheating2 10 }
+airIRmPmEheating2StartTemperatureK OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Electric heater #2 start temperature in tenths of Kelvins (4909)"
+ ::= { airIRmPmEheating2StartTemperature 1 }
+airIRmPmEheating2StartTemperatureF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Electric heater #2 start temperature in tenths of degrees Fahrenheit (4909)"
+ ::= { airIRmPmEheating2StartTemperature 2 }
+
+airIRmPmEheating2Hysteresis OBJECT IDENTIFIER ::= { airIRmPmEheating2 11 }
+airIRmPmEheating2HysteresisK OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Electric heater #2 hysteresis in tenths of Kelvins (4910)"
+ ::= { airIRmPmEheating2Hysteresis 1 }
+airIRmPmEheating2HysteresisF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Electric heater #2 hysteresis in tenths of degrees Fahrenheit (4910)"
+ ::= { airIRmPmEheating2Hysteresis 2 }
+
+airIRmPmEheating2Runtime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Electric heater #2 runtime in hours (4916)"
+ ::= { airIRmPmEheating2 17 }
+
+-- airIRmPmEheating3
+
+airIRmPmEheating3ManOpEnable OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Electric heater #3 manual operation enable (5001)"
+ ::= { airIRmPmEheating3 2 }
+
+airIRmPmEheating3Running OBJECT-TYPE
+ SYNTAX AirIRmControlState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Electric heater #3 running state (5003)"
+ ::= { airIRmPmEheating3 4 }
+
+airIRmPmEheating3ManOpRunning OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Electric heater #3 running in manual operation mode (5004)"
+ ::= { airIRmPmEheating3 5 }
+
+airIRmPmEheating3Type OBJECT-TYPE
+ SYNTAX INTEGER {
+ direct (1),
+ pwm (2) }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Electric heater #3 type (5008)"
+ ::= { airIRmPmEheating3 9 }
+
+airIRmPmEheating3StartTemperature OBJECT IDENTIFIER ::= { airIRmPmEheating3 10 }
+airIRmPmEheating3StartTemperatureK OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Electric heater #3 start temperature in tenths of Kelvins (5009)"
+ ::= { airIRmPmEheating3StartTemperature 1 }
+airIRmPmEheating3StartTemperatureF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Electric heater #3 start temperature in tenths of degrees Fahrenheit (5009)"
+ ::= { airIRmPmEheating3StartTemperature 2 }
+
+airIRmPmEheating3Hysteresis OBJECT IDENTIFIER ::= { airIRmPmEheating3 11 }
+airIRmPmEheating3HysteresisK OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Electric heater #3 hysteresis in tenths of Kelvins (5010)"
+ ::= { airIRmPmEheating3Hysteresis 1 }
+airIRmPmEheating3HysteresisF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Electric heater #3 hysteresis in tenths of degrees Fahrenheit (5010)"
+ ::= { airIRmPmEheating3Hysteresis 2 }
+
+airIRmPmEheating3Runtime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Electric heater #3 runtime in hours (5016)"
+ ::= { airIRmPmEheating3 17 }
+
+-- airIRmPmEheating4
+
+airIRmPmEheating4ManOpEnable OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Electric heater #4 manual operation enable (5101)"
+ ::= { airIRmPmEheating4 2 }
+
+airIRmPmEheating4Running OBJECT-TYPE
+ SYNTAX AirIRmControlState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Electric heater #4 running state (5103)"
+ ::= { airIRmPmEheating4 4 }
+
+airIRmPmEheating4ManOpRunning OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Electric heater #4 running in manual operation mode (5104)"
+ ::= { airIRmPmEheating4 5 }
+
+airIRmPmEheating4Type OBJECT-TYPE
+ SYNTAX INTEGER {
+ direct (1),
+ pwm (2) }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Electric heater #4 type (5108)"
+ ::= { airIRmPmEheating4 9 }
+
+airIRmPmEheating4StartTemperature OBJECT IDENTIFIER ::= { airIRmPmEheating4 10 }
+airIRmPmEheating4StartTemperatureK OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Electric heater #4 start temperature in tenths of Kelvins (5109)"
+ ::= { airIRmPmEheating4StartTemperature 1 }
+airIRmPmEheating4StartTemperatureF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Electric heater #4 start temperature in tenths of degrees Fahrenheit (5109)"
+ ::= { airIRmPmEheating4StartTemperature 2 }
+
+airIRmPmEheating4Hysteresis OBJECT IDENTIFIER ::= { airIRmPmEheating4 11 }
+airIRmPmEheating4HysteresisK OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Electric heater #4 hysteresis in tenths of Kelvins (5110)"
+ ::= { airIRmPmEheating4Hysteresis 1 }
+airIRmPmEheating4HysteresisF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Electric heater #4 hysteresis in tenths of degrees Fahrenheit (5110)"
+ ::= { airIRmPmEheating4Hysteresis 2 }
+
+airIRmPmEheating4Runtime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Electric heater #4 runtime in hours (5116)"
+ ::= { airIRmPmEheating4 17 }
+
+-- airIRmPmGECWvalve
+
+airIRmPmGECWvalveManOpEnable OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "GE/CW valve manual operation enable (5201)"
+ ::= { airIRmPmGECWvalve 2 }
+
+airIRmPmGECWvalveStartTemperature OBJECT IDENTIFIER ::= { airIRmPmGECWvalve 9 }
+airIRmPmGECWvalveStartTemperatureK OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "GE/CW valve start temperature in tenths of Kelvins (5208)"
+ ::= { airIRmPmGECWvalveStartTemperature 1 }
+airIRmPmGECWvalveStartTemperatureF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "GE/CW valve start temperature in tenths of degrees Fahrenheit (5208)"
+ ::= { airIRmPmGECWvalveStartTemperature 2 }
+
+airIRmPmGECWvalveLinearRange OBJECT IDENTIFIER ::= { airIRmPmGECWvalve 10 }
+airIRmPmGECWvalveLinearRangeK OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "GE/CW valve linear range in tenths of Kelvins (5209)"
+ ::= { airIRmPmGECWvalveLinearRange 1 }
+airIRmPmGECWvalveLinearRangeF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "GE/CW valve linear range in tenths of degrees Fahrenheit (5209)"
+ ::= { airIRmPmGECWvalveLinearRange 2 }
+
+airIRmPmGECWvalveGEOffTemp OBJECT IDENTIFIER ::= { airIRmPmGECWvalve 12 }
+airIRmPmGECWvalveGEOffTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "GE/CW valve GE off temperature in tenths of degrees Celsius (5211)"
+ ::= { airIRmPmGECWvalveGEOffTemp 1 }
+airIRmPmGECWvalveGEOffTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "GE/CW valve GE off temperature in tenths of degrees Fahrenheit (5211)"
+ ::= { airIRmPmGECWvalveGEOffTemp 2 }
+
+airIRmPmGECWvalveOpeningGrade OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "GE/CW valve opening grade in percent (5214)"
+ ::= { airIRmPmGECWvalve 15 }
+
+airIRmPmGECWvalveManOpOpeningGrade OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "GE/CW valve manual operation opening grade in percent (5215)"
+ ::= { airIRmPmGECWvalve 16 }
+
+-- airIRmPmGvalve
+
+airIRmPmGvalveManOperationEnable OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "G-valve manual operation enable (5301)"
+ ::= { airIRmPmGvalve 2 }
+
+airIRmPmGvalvePreOpeningTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "G-valve pre-opening time in seconds (5310)"
+ ::= { airIRmPmGvalve 11 }
+
+airIRmPmGvalvePreOpeningGrade OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "G-valve pre-opening grade in percent (5311)"
+ ::= { airIRmPmGvalve 12 }
+
+airIRmPmGvalveOpeningGrade OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "G-valve opening grade in percent (5312)"
+ ::= { airIRmPmGvalve 13 }
+
+airIRmPmGvalveManOpOpeningGrade OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "G-valve manual operation opening grade in percent (5313)"
+ ::= { airIRmPmGvalve 14 }
+
+-- airIRmPmDrycooler1
+
+airIRmPmDrycooler1ManOpEnable OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler 1 manual operation enable setting (5401)"
+ ::= { airIRmPmDrycooler1 2 }
+
+airIRmPmDrycooler1Running OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler 1 running (5402)"
+ ::= { airIRmPmDrycooler1 3 }
+
+airIRmPmDrycooler1ManOpRunning OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler 1 manual operation running (5404)"
+ ::= { airIRmPmDrycooler1 5 }
+
+airIRmPmDrycooler1WinterStartTemp OBJECT IDENTIFIER ::= { airIRmPmDrycooler1 9 }
+airIRmPmDrycooler1WinterStartTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler 1 winter mode start temperature
+ in tenths of degrees Celsius (5408)"
+ ::= { airIRmPmDrycooler1WinterStartTemp 1 }
+airIRmPmDrycooler1WinterStartTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler 1 winter mode start temperature
+ in tenths of degrees Fahrenheit (5408)"
+ ::= { airIRmPmDrycooler1WinterStartTemp 2 }
+
+airIRmPmDrycooler1SummerStartTemp OBJECT IDENTIFIER ::= { airIRmPmDrycooler1 10 }
+airIRmPmDrycooler1SummerStartTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler 1 summer mode start temperature
+ in tenths of degrees Celsius (5409)"
+ ::= { airIRmPmDrycooler1SummerStartTemp 1 }
+airIRmPmDrycooler1SummerStartTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler 1 summer mode start temperature
+ in tenths of degrees Fahrenheit (5409)"
+ ::= { airIRmPmDrycooler1SummerStartTemp 2 }
+
+airIRmPmDrycooler1Hysteresis OBJECT IDENTIFIER ::= { airIRmPmDrycooler1 11 }
+airIRmPmDrycooler1HysteresisK OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler 1 hysteresis in tenths of Kelvins (5410)"
+ ::= { airIRmPmDrycooler1Hysteresis 1 }
+airIRmPmDrycooler1HysteresisF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler 1 hysteresis in tenths of degrees Fahrenheit (5410)"
+ ::= { airIRmPmDrycooler1Hysteresis 2 }
+
+airIRmPmDrycooler1Runtime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler 1 runtime in hours (5415)"
+ ::= { airIRmPmDrycooler1 16 }
+
+-- airIRmPmDrycooler2
+
+airIRmPmDrycooler2ManOpEnable OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler 2 manual operation enable setting (5501)"
+ ::= { airIRmPmDrycooler2 2 }
+
+airIRmPmDrycooler2Running OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler 2 running (5502)"
+ ::= { airIRmPmDrycooler2 3 }
+
+airIRmPmDrycooler2ManOpRunning OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler 2 manual operation running (5504)"
+ ::= { airIRmPmDrycooler2 5 }
+
+airIRmPmDrycooler2WinterStartTemp OBJECT IDENTIFIER ::= { airIRmPmDrycooler2 9 }
+airIRmPmDrycooler2WinterStartTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler 2 winter mode start temperature
+ in tenths of degrees Celsius (5508)"
+ ::= { airIRmPmDrycooler2WinterStartTemp 1 }
+airIRmPmDrycooler2WinterStartTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler 2 winter mode start temperature
+ in tenths of degrees Fahrenheit (5508)"
+ ::= { airIRmPmDrycooler2WinterStartTemp 2 }
+
+airIRmPmDrycooler2SummerStartTemp OBJECT IDENTIFIER ::= { airIRmPmDrycooler2 10 }
+airIRmPmDrycooler2SummerStartTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler 2 summer mode start temperature
+ in tenths of degrees Celsius (5509)"
+ ::= { airIRmPmDrycooler2SummerStartTemp 1 }
+airIRmPmDrycooler2SummerStartTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler 2 summer mode start temperature
+ in tenths of degrees Fahrenheit (5509)"
+ ::= { airIRmPmDrycooler2SummerStartTemp 2 }
+
+airIRmPmDrycooler2Hysteresis OBJECT IDENTIFIER ::= { airIRmPmDrycooler2 11 }
+airIRmPmDrycooler2HysteresisK OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler 2 hysteresis in tenths of Kelvins (5510)"
+ ::= { airIRmPmDrycooler2Hysteresis 1 }
+airIRmPmDrycooler2HysteresisF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler 2 hysteresis in tenths of degrees Fahrenheit (5510)"
+ ::= { airIRmPmDrycooler2Hysteresis 2 }
+
+airIRmPmDrycooler2Runtime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler 2 runtime in hours (5515)"
+ ::= { airIRmPmDrycooler2 16 }
+
+-- airIRmPmDrycooler3
+
+airIRmPmDrycooler3ManOpEnable OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler 3 manual operation enable setting (5601)"
+ ::= { airIRmPmDrycooler3 2 }
+
+airIRmPmDrycooler3Running OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler 3 running (5602)"
+ ::= { airIRmPmDrycooler3 3 }
+
+airIRmPmDrycooler3ManOpRunning OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler 3 manual operation running (5604)"
+ ::= { airIRmPmDrycooler3 5 }
+
+airIRmPmDrycooler3WinterStartTemp OBJECT IDENTIFIER ::= { airIRmPmDrycooler3 9 }
+airIRmPmDrycooler3WinterStartTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler 3 winter mode start temperature
+ in tenths of degrees Celsius (5608)"
+ ::= { airIRmPmDrycooler3WinterStartTemp 1 }
+airIRmPmDrycooler3WinterStartTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler 3 winter mode start temperature
+ in tenths of degrees Fahrenheit (5608)"
+ ::= { airIRmPmDrycooler3WinterStartTemp 2 }
+
+airIRmPmDrycooler3SummerStartTemp OBJECT IDENTIFIER ::= { airIRmPmDrycooler3 10 }
+airIRmPmDrycooler3SummerStartTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler 3 summer mode start temperature
+ in tenths of degrees Celsius (5609)"
+ ::= { airIRmPmDrycooler3SummerStartTemp 1 }
+airIRmPmDrycooler3SummerStartTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler 3 summer mode start temperature
+ in tenths of degrees Fahrenheit (5609)"
+ ::= { airIRmPmDrycooler3SummerStartTemp 2 }
+
+airIRmPmDrycooler3Hysteresis OBJECT IDENTIFIER ::= { airIRmPmDrycooler3 11 }
+airIRmPmDrycooler3HysteresisK OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler 3 hysteresis in tenths of Kelvins (5610)"
+ ::= { airIRmPmDrycooler3Hysteresis 1 }
+airIRmPmDrycooler3HysteresisF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler 3 hysteresis in tenths of degrees Fahrenheit (5610)"
+ ::= { airIRmPmDrycooler3Hysteresis 2 }
+
+airIRmPmDrycooler3Runtime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler 3 runtime in hours (5615)"
+ ::= { airIRmPmDrycooler3 16 }
+
+-- airIRmPmDrycooler4
+
+airIRmPmDrycooler4ManOpEnable OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler 4 manual operation enable setting (5701)"
+ ::= { airIRmPmDrycooler4 2 }
+
+airIRmPmDrycooler4Running OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler 4 running (5702)"
+ ::= { airIRmPmDrycooler4 3 }
+
+airIRmPmDrycooler4ManOpRunning OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler 4 manual operation running (5704)"
+ ::= { airIRmPmDrycooler4 5 }
+
+airIRmPmDrycooler4WinterStartTemp OBJECT IDENTIFIER ::= { airIRmPmDrycooler4 9 }
+airIRmPmDrycooler4WinterStartTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler 4 winter mode start temperature
+ in tenths of degrees Celsius (5708)"
+ ::= { airIRmPmDrycooler4WinterStartTemp 1 }
+airIRmPmDrycooler4WinterStartTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler 4 winter mode start temperature
+ in tenths of degrees Fahrenheit (5708)"
+ ::= { airIRmPmDrycooler4WinterStartTemp 2 }
+
+airIRmPmDrycooler4SummerStartTemp OBJECT IDENTIFIER ::= { airIRmPmDrycooler4 10 }
+airIRmPmDrycooler4SummerStartTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler 4 summer mode start temperature
+ in tenths of degrees Celsius (5709)"
+ ::= { airIRmPmDrycooler4SummerStartTemp 1 }
+airIRmPmDrycooler4SummerStartTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler 4 summer mode start temperature
+ in tenths of degrees Fahrenheit (5709)"
+ ::= { airIRmPmDrycooler4SummerStartTemp 2 }
+
+airIRmPmDrycooler4Hysteresis OBJECT IDENTIFIER ::= { airIRmPmDrycooler4 11 }
+airIRmPmDrycooler4HysteresisK OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler 4 hysteresis in tenths of Kelvins (5710)"
+ ::= { airIRmPmDrycooler4Hysteresis 1 }
+airIRmPmDrycooler4HysteresisF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler 4 hysteresis in tenths of degrees Fahrenheit (5710)"
+ ::= { airIRmPmDrycooler4Hysteresis 2 }
+
+airIRmPmDrycooler4Runtime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler 4 runtime in hours (5715)"
+ ::= { airIRmPmDrycooler4 16 }
+
+-- airIRmPmPump1
+
+airIRmPmPump1ManOpEnable OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 1 manual operation enable state (5801)"
+ ::= { airIRmPmPump1 2 }
+
+airIRmPmPump1Running OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 1 running (5802)"
+ ::= { airIRmPmPump1 3 }
+
+airIRmPmPump1ManOpRunning OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 1 manual operation running (5805)"
+ ::= { airIRmPmPump1 6 }
+
+airIRmPmPump1StartTemperature OBJECT IDENTIFIER ::= { airIRmPmPump1 10 }
+airIRmPmPump1StartTemperatureK OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 1 starting temperature in tenths of Kelvins (5809)"
+ ::= { airIRmPmPump1StartTemperature 1 }
+airIRmPmPump1StartTemperatureF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 1 starting temperature in tenths of degrees Fahrenheit (5809)"
+ ::= { airIRmPmPump1StartTemperature 2 }
+
+airIRmPmPump1Hysteresis OBJECT IDENTIFIER ::= { airIRmPmPump1 11 }
+airIRmPmPump1HysteresisK OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 1 hysteresis in tenths of Kelvins (5810)"
+ ::= { airIRmPmPump1Hysteresis 1 }
+airIRmPmPump1HysteresisF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 1 hysteresis in tenths of degrees Fahrenheit (5810)"
+ ::= { airIRmPmPump1Hysteresis 2 }
+
+airIRmPmPump1LinearRange OBJECT IDENTIFIER ::= { airIRmPmPump1 12 }
+airIRmPmPump1LinearRangeK OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 1 linear range in tenths of Kelvins (5811)"
+ ::= { airIRmPmPump1LinearRange 1 }
+airIRmPmPump1LinearRangeF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 1 linear range in tenths of degrees Fahrenheit (5811)"
+ ::= { airIRmPmPump1LinearRange 2 }
+
+airIRmPmPump1PressureSetpoint OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 1 pressure setpoint in tenths of Bars (5812)"
+ ::= { airIRmPmPump1 13 }
+
+airIRmPmPump1Runtime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 1 runtime in hours (5820)"
+ ::= { airIRmPmPump1 21 }
+
+airIRmPmPump1Speed OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 1 speed in percent (5821)"
+ ::= { airIRmPmPump1 22 }
+
+airIRmPmPump1ControlCycle OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 1 control cycle length in seconds (5827)"
+ ::= { airIRmPmPump1 28 }
+
+airIRmPmPump1MaxAdjust OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 1 maximum adjustment in percent (5828)"
+ ::= { airIRmPmPump1 29 }
+
+airIRmPmPump1ControlFactor OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 1 control factor setting (5829)"
+ ::= { airIRmPmPump1 30 }
+
+-- airIRmPmPump2
+
+airIRmPmPump2ManOpEnable OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 2 manual operation enable state (5901)"
+ ::= { airIRmPmPump2 2 }
+
+airIRmPmPump2Running OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 2 running (5902)"
+ ::= { airIRmPmPump2 3 }
+
+airIRmPmPump2ManOpRunning OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 2 manual operation running (5905)"
+ ::= { airIRmPmPump2 6 }
+
+airIRmPmPump2StartTemperature OBJECT IDENTIFIER ::= { airIRmPmPump2 10 }
+airIRmPmPump2StartTemperatureK OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 2 starting temperature in tenths of Kelvins (5909)"
+ ::= { airIRmPmPump2StartTemperature 1 }
+airIRmPmPump2StartTemperatureF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 2 starting temperature in tenths of degrees Fahrenheit (5909)"
+ ::= { airIRmPmPump2StartTemperature 2 }
+
+airIRmPmPump2Hysteresis OBJECT IDENTIFIER ::= { airIRmPmPump2 11 }
+airIRmPmPump2HysteresisK OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 2 hysteresis in tenths of Kelvins (5910)"
+ ::= { airIRmPmPump2Hysteresis 1 }
+airIRmPmPump2HysteresisF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 2 hysteresis in tenths of degrees Fahrenheit (5910)"
+ ::= { airIRmPmPump2Hysteresis 2 }
+
+airIRmPmPump2LinearRange OBJECT IDENTIFIER ::= { airIRmPmPump2 12 }
+airIRmPmPump2LinearRangeK OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 2 linear range in tenths of Kelvins (5911)"
+ ::= { airIRmPmPump2LinearRange 1 }
+airIRmPmPump2LinearRangeF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 2 linear range in tenths of degrees Fahrenheit (5911)"
+ ::= { airIRmPmPump2LinearRange 2 }
+
+airIRmPmPump2PressureSetpoint OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 2 pressure setpoint in tenths of Bars (5912)"
+ ::= { airIRmPmPump2 13 }
+
+airIRmPmPump2Runtime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 2 runtime in hours (5920)"
+ ::= { airIRmPmPump2 21 }
+
+airIRmPmPump2Speed OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 2 speed in percent (5921)"
+ ::= { airIRmPmPump2 22 }
+
+airIRmPmPump2ControlCycle OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 2 control cycle length in seconds (5927)"
+ ::= { airIRmPmPump2 28 }
+
+airIRmPmPump2MaxAdjust OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 2 maximum adjustment in percent (5928)"
+ ::= { airIRmPmPump2 29 }
+
+airIRmPmPump2ControlFactor OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 2 control factor setting (5929)"
+ ::= { airIRmPmPump2 30 }
+
+-- airIRmPmPump3
+
+airIRmPmPump3ManOpEnable OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 3 manual operation enable state (6001)"
+ ::= { airIRmPmPump3 2 }
+
+airIRmPmPump3Running OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 3 running (6002)"
+ ::= { airIRmPmPump3 3 }
+
+airIRmPmPump3ManOpRunning OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 3 manual operation running (6005)"
+ ::= { airIRmPmPump3 6 }
+
+airIRmPmPump3StartTemperature OBJECT IDENTIFIER ::= { airIRmPmPump3 10 }
+airIRmPmPump3StartTemperatureK OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 3 starting temperature in tenths of Kelvins (6009)"
+ ::= { airIRmPmPump3StartTemperature 1 }
+airIRmPmPump3StartTemperatureF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 3 starting temperature in tenths of degrees Fahrenheit (6009)"
+ ::= { airIRmPmPump3StartTemperature 2 }
+
+airIRmPmPump3Hysteresis OBJECT IDENTIFIER ::= { airIRmPmPump3 11 }
+airIRmPmPump3HysteresisK OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 3 hysteresis in tenths of Kelvins (6010)"
+ ::= { airIRmPmPump3Hysteresis 1 }
+airIRmPmPump3HysteresisF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 3 hysteresis in tenths of degrees Fahrenheit (6010)"
+ ::= { airIRmPmPump3Hysteresis 2 }
+
+airIRmPmPump3LinearRange OBJECT IDENTIFIER ::= { airIRmPmPump3 12 }
+airIRmPmPump3LinearRangeK OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 3 linear range in tenths of Kelvins (6011)"
+ ::= { airIRmPmPump3LinearRange 1 }
+airIRmPmPump3LinearRangeF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 3 linear range in tenths of degrees Fahrenheit (6011)"
+ ::= { airIRmPmPump3LinearRange 2 }
+
+airIRmPmPump3PressureSetpoint OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 3 pressure setpoint in tenths of Bars (6012)"
+ ::= { airIRmPmPump3 13 }
+
+airIRmPmPump3Runtime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 3 runtime in hours (6020)"
+ ::= { airIRmPmPump3 21 }
+
+airIRmPmPump3Speed OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 3 speed in percent (6021)"
+ ::= { airIRmPmPump3 22 }
+
+airIRmPmPump3ControlCycle OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 3 control cycle length in seconds (6027)"
+ ::= { airIRmPmPump3 28 }
+
+airIRmPmPump3MaxAdjust OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 3 maximum adjustment in percent (6028)"
+ ::= { airIRmPmPump3 29 }
+
+airIRmPmPump3ControlFactor OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 3 control factor setting (6029)"
+ ::= { airIRmPmPump3 30 }
+
+-- airIRmPmPump4
+
+airIRmPmPump4ManOpEnable OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 4 manual operation enable state (6101)"
+ ::= { airIRmPmPump4 2 }
+
+airIRmPmPump4Running OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 4 running (6102)"
+ ::= { airIRmPmPump4 3 }
+
+airIRmPmPump4ManOpRunning OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 4 manual operation running (6105)"
+ ::= { airIRmPmPump4 6 }
+
+airIRmPmPump4StartTemperature OBJECT IDENTIFIER ::= { airIRmPmPump4 10 }
+airIRmPmPump4StartTemperatureK OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 4 starting temperature in tenths of Kelvins (6109)"
+ ::= { airIRmPmPump4StartTemperature 1 }
+airIRmPmPump4StartTemperatureF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 4 starting temperature in tenths of degrees Fahrenheit (6109)"
+ ::= { airIRmPmPump4StartTemperature 2 }
+
+airIRmPmPump4Hysteresis OBJECT IDENTIFIER ::= { airIRmPmPump4 11 }
+airIRmPmPump4HysteresisK OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 4 hysteresis in tenths of Kelvins (6110)"
+ ::= { airIRmPmPump4Hysteresis 1 }
+airIRmPmPump4HysteresisF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 4 hysteresis in tenths of degrees Fahrenheit (6110)"
+ ::= { airIRmPmPump4Hysteresis 2 }
+
+airIRmPmPump4LinearRange OBJECT IDENTIFIER ::= { airIRmPmPump4 12 }
+airIRmPmPump4LinearRangeK OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 4 linear range in tenths of Kelvins (6111)"
+ ::= { airIRmPmPump4LinearRange 1 }
+airIRmPmPump4LinearRangeF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 4 linear range in tenths of degrees Fahrenheit (6111)"
+ ::= { airIRmPmPump4LinearRange 2 }
+
+airIRmPmPump4PressureSetpoint OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 4 pressure setpoint in tenths of Bars (6112)"
+ ::= { airIRmPmPump4 13 }
+
+airIRmPmPump4Runtime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 4 runtime in hours (6120)"
+ ::= { airIRmPmPump4 21 }
+
+airIRmPmPump4Speed OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 4 speed in percent (6121)"
+ ::= { airIRmPmPump4 22 }
+
+airIRmPmPump4ControlCycle OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 4 control cycle length in seconds (6127)"
+ ::= { airIRmPmPump4 28 }
+
+airIRmPmPump4MaxAdjust OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 4 maximum adjustment in percent (6128)"
+ ::= { airIRmPmPump4 29 }
+
+airIRmPmPump4ControlFactor OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Pump 4 control factor setting (6129)"
+ ::= { airIRmPmPump4 30 }
+
+-- airIRmPmHotgasHeating
+
+airIRmPmHotgasHeatRunning OBJECT-TYPE
+ SYNTAX AirIRmControlState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Hotgas heat running state. (6202)"
+ ::= { airIRmPmHotgasHeating 3 }
+
+-- airIRmPmPWWHeating
+
+airIRmPmPWWHeatingManOpEnable OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "PWW-heating manual operation enable (6301)"
+ ::= { airIRmPmPWWHeating 2 }
+
+airIRmPmPWWHeatingRunning OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "PWW-heating running (6302)"
+ ::= { airIRmPmPWWHeating 3 }
+
+airIRmPmPWWHeatingManOpRunning OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "PWW-heating manual operation running (6303)"
+ ::= { airIRmPmPWWHeating 4 }
+
+airIRmPmPWWHeatingType OBJECT-TYPE
+ SYNTAX INTEGER {
+ direct (1),
+ undefined (2) }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "PWW-heating type (6308)"
+ ::= { airIRmPmPWWHeating 9 }
+
+airIRmPmPWWHeatingStartTemp OBJECT IDENTIFIER ::= { airIRmPmPWWHeating 10 }
+airIRmPmPWWHeatingStartTempK OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "PWW-heating starting temperature in Kelvins (6309)"
+ ::= { airIRmPmPWWHeatingStartTemp 1 }
+airIRmPmPWWHeatingStartTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "PWW-heating starting temperature in degrees Fahrenheit (6309)"
+ ::= { airIRmPmPWWHeatingStartTemp 2 }
+
+airIRmPmPWWHeatingHysteresis OBJECT IDENTIFIER ::= { airIRmPmPWWHeating 12 }
+airIRmPmPWWHeatingHysteresisK OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "PWW-heating hysteresis in Kelvins (6311)"
+ ::= { airIRmPmPWWHeatingHysteresis 1 }
+airIRmPmPWWHeatingHysteresisF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "PWW-heating hysteresis in degrees Fahrenheit (6311)"
+ ::= { airIRmPmPWWHeatingHysteresis 2 }
+
+airIRmPmPWWHeatingLinearRange OBJECT IDENTIFIER ::= { airIRmPmPWWHeating 13 }
+airIRmPmPWWHeatingLinearRangeK OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "PWW-heating linear range in Kelvins (6312)"
+ ::= { airIRmPmPWWHeatingLinearRange 1 }
+airIRmPmPWWHeatingLinearRangeF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "PWW-heating linear range in degrees Fahrenheit (6312)"
+ ::= { airIRmPmPWWHeatingLinearRange 2 }
+
+airIRmPmPWWHeatingCurrentValue OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "PWW-heating current value in percent (6315)"
+ ::= { airIRmPmPWWHeating 16 }
+
+airIRmPmPWWHeatingManOpValue OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "PWW-heating manual operation value in percent (6316)"
+ ::= { airIRmPmPWWHeating 17 }
+
+-- airIRmPmHumidifier1
+
+airIRmPmHumidifier1ManOpEnable OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Humidifier #1 manual operation enable (6401)"
+ ::= { airIRmPmHumidifier1 2 }
+
+airIRmPmHumidifier1Running OBJECT-TYPE
+ SYNTAX AirIRmControlState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Humidifier #1 running state (6402)"
+ ::= { airIRmPmHumidifier1 3 }
+
+airIRmPmHumidifier1ManOpRunning OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Humidifier #1 manual operation running state (6404)"
+ ::= { airIRmPmHumidifier1 5 }
+
+airIRmPmHumidifier1Type OBJECT-TYPE
+ SYNTAX INTEGER {
+ direct (1),
+ proportional (2) }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Humidifier #1 type (6416)"
+ ::= { airIRmPmHumidifier1 17 }
+
+airIRmPmHumidifier1StartHumidity OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Humidifier #1 start humidity in tenths
+ of percent relative humidity (6417)"
+ ::= { airIRmPmHumidifier1 18 }
+
+airIRmPmHumidifier1Hysteresis OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Humidifier #1 hysteresis in tenths
+ of percent relative humidity (6419)"
+ ::= { airIRmPmHumidifier1 20 }
+
+airIRmPmHumidifier1LinearRange OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Humidifier #1 linear range in tenths
+ of percent relative humidity per Kelvin (6420)"
+ ::= { airIRmPmHumidifier1 21 }
+
+airIRmPmHumidifier1Runtime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Humidifier #1 runtime in hours (6426)"
+ ::= { airIRmPmHumidifier1 27 }
+
+airIRmPmHumidifier1CurrentValue OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Humidifier #1 current value in percent (6427)"
+ ::= { airIRmPmHumidifier1 28 }
+
+airIRmPmHumidifier1ManOpValue OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Humidifier #1 manual operation value in percent (6428)"
+ ::= { airIRmPmHumidifier1 29 }
+
+-- airIRmPmHumidifier2
+
+airIRmPmHumidifier2ManOpEnable OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Humidifier #2 manual operation enable (6501)"
+ ::= { airIRmPmHumidifier2 2 }
+
+airIRmPmHumidifier2Running OBJECT-TYPE
+ SYNTAX AirIRmControlState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Humidifier #2 running state (6502)"
+ ::= { airIRmPmHumidifier2 3 }
+
+airIRmPmHumidifier2ManOpRunning OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Humidifier #2 manual operation running state (6504)"
+ ::= { airIRmPmHumidifier2 5 }
+
+airIRmPmHumidifier2Type OBJECT-TYPE
+ SYNTAX INTEGER {
+ direct (1),
+ proportional (2) }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Humidifier #2 type (6516)"
+ ::= { airIRmPmHumidifier2 17 }
+
+airIRmPmHumidifier2StartHumidity OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Humidifier #2 start humidity in tenths
+ of percent relative humidity (6517)"
+ ::= { airIRmPmHumidifier2 18 }
+
+airIRmPmHumidifier2Hysteresis OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Humidifier #2 hysteresis in tenths
+ of percent relative humidity (6519)"
+ ::= { airIRmPmHumidifier2 20 }
+
+airIRmPmHumidifier2LinearRange OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Humidifier #2 linear range in tenths
+ of percent relative humidity per Kelvin (6520)"
+ ::= { airIRmPmHumidifier2 21 }
+
+airIRmPmHumidifier2Runtime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Humidifier #2 runtime in hours (6526)"
+ ::= { airIRmPmHumidifier2 27 }
+
+airIRmPmHumidifier2CurrentValue OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Humidifier #2 current value in percent (6527)"
+ ::= { airIRmPmHumidifier2 28 }
+
+airIRmPmHumidifier2ManOpValue OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Humidifier #2 manual operation value in percent (6528)"
+ ::= { airIRmPmHumidifier2 29 }
+
+-- airIRmPmDehumidification
+
+airIRmPmDehumidificManOpEnable OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Dehumidifier manual operation enable setting (6801)"
+ ::= { airIRmPmDehumidification 2 }
+
+airIRmPmDehumidificRunning OBJECT-TYPE
+ SYNTAX AirIRmControlState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Dehumidifier running state (6802)"
+ ::= { airIRmPmDehumidification 3 }
+
+airIRmPmDehumidificManOpRunning OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Dehumidifier manual operation running (6804)"
+ ::= { airIRmPmDehumidification 5 }
+
+airIRmPmDehumidificStartHumidity OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Dehumidifier start humidity in tenths of percent relative humidity (6809)"
+ ::= { airIRmPmDehumidification 10 }
+
+airIRmPmDehumidificHysteresis OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Dehumidifier hysteresis in tenths of percent relative humidity (6811)"
+ ::= { airIRmPmDehumidification 12 }
+
+airIRmPmDehumidificMinWaterTemp OBJECT IDENTIFIER ::= { airIRmPmDehumidification 18 }
+airIRmPmDehumidificMinWaterTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Dehumidifier minimum water temperature in tenths of
+ degrees Celsius (6817)"
+ ::= { airIRmPmDehumidificMinWaterTemp 1 }
+airIRmPmDehumidificMinWaterTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Dehumidifier minimum water temperature in tenths of
+ degrees Fahrenheit (6817)"
+ ::= { airIRmPmDehumidificMinWaterTemp 2 }
+
+airIRmPmDehumidificMaxWaterTemp OBJECT IDENTIFIER ::= { airIRmPmDehumidification 19 }
+airIRmPmDehumidificMaxWaterTempC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Dehumidifier maximum water temperature in tenths of
+ degrees Celsius (6818)"
+ ::= { airIRmPmDehumidificMaxWaterTemp 1 }
+airIRmPmDehumidificMaxWaterTempF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Dehumidifier maximum water temperature in tenths of
+ degrees Fahrenheit (6818)"
+ ::= { airIRmPmDehumidificMaxWaterTemp 2 }
+
+airIRmPmDehumidificRuntime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Dehumidifier runtime in hours (6820)"
+ ::= { airIRmPmDehumidification 21 }
+
+-- airIRmPmFan1
+
+airIRmPmFan1ManOpEnable OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Fan 1 manual operation enable (6901)"
+ ::= { airIRmPmFan1 2 }
+
+airIRmPmFan1Running OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Fan 1 running (6902)"
+ ::= { airIRmPmFan1 3 }
+
+airIRmPmFan1ManOpRunning OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Fan 1 manual operation running (6905)"
+ ::= { airIRmPmFan1 6 }
+
+airIRmPmFan1Type OBJECT-TYPE
+ SYNTAX INTEGER {
+ direct (1),
+ proportional (2) }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Fan 1 type (6908)"
+ ::= { airIRmPmFan1 9 }
+
+airIRmPmFan1Runtime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Fan 1 runtime in hours (6931)"
+ ::= { airIRmPmFan1 32 }
+
+airIRmPmFan1Speed OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Fan 1 speed in percent (6932)"
+ ::= { airIRmPmFan1 33 }
+
+airIRmPmFan1ManOpSpeed OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Fan 1 manual operation speed in percent (6933)"
+ ::= { airIRmPmFan1 34 }
+
+-- airIRmPmFan2
+
+airIRmPmFan2ManOpEnable OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Fan 1 manual operation enable (7001)"
+ ::= { airIRmPmFan2 2 }
+
+airIRmPmFan2Running OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Fan 1 running (7002)"
+ ::= { airIRmPmFan2 3 }
+
+airIRmPmFan2ManOpRunning OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Fan 1 manual operation running (7005)"
+ ::= { airIRmPmFan2 6 }
+
+airIRmPmFan2Type OBJECT-TYPE
+ SYNTAX INTEGER {
+ direct (1),
+ proportional (2) }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Fan 2 type (7008)"
+ ::= { airIRmPmFan2 9 }
+
+airIRmPmFan2Runtime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Fan 1 runtime in hours (7031)"
+ ::= { airIRmPmFan2 32 }
+
+airIRmPmFan2Speed OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Fan 1 speed in percent (7032)"
+ ::= { airIRmPmFan2 33 }
+
+airIRmPmFan2ManOpSpeed OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Fan 1 manual operation speed in percent (7033)"
+ ::= { airIRmPmFan2 34 }
+
+-- airIRmPmFan3
+
+airIRmPmFan3ManOpEnable OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Fan 1 manual operation enable (7101)"
+ ::= { airIRmPmFan3 2 }
+
+airIRmPmFan3Running OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Fan 1 running (7102)"
+ ::= { airIRmPmFan3 3 }
+
+airIRmPmFan3ManOpRunning OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Fan 1 manual operation running (7105)"
+ ::= { airIRmPmFan3 6 }
+
+airIRmPmFan3Type OBJECT-TYPE
+ SYNTAX INTEGER {
+ direct (1),
+ proportional (2) }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Fan 3 type (7108)"
+ ::= { airIRmPmFan3 9 }
+
+airIRmPmFan3Runtime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Fan 1 runtime in hours (7131)"
+ ::= { airIRmPmFan3 32 }
+
+airIRmPmFan3Speed OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Fan 1 speed in percent (7132)"
+ ::= { airIRmPmFan3 33 }
+
+airIRmPmFan3ManOpSpeed OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Fan 1 manual operation speed in percent (7133)"
+ ::= { airIRmPmFan3 34 }
+
+-- airIRmPmLouver1
+
+airIRmPmLouver1ManOpEnable OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Louver 1 manual operation enable (7201)"
+ ::= { airIRmPmLouver1 2 }
+
+airIRmPmLouver1Position OBJECT-TYPE
+ SYNTAX INTEGER {
+ closed (1),
+ open (2) }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Louver 1 position (7202)"
+ ::= { airIRmPmLouver1 3 }
+
+airIRmPmLouver1ManOpPosition OBJECT-TYPE
+ SYNTAX INTEGER {
+ closed (1),
+ open (2) }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Louver 1 manual operation position setting (7203)"
+ ::= { airIRmPmLouver1 4 }
+
+-- airIRmPmLouver2
+
+airIRmPmLouver2ManOpEnable OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Louver 2 manual operation enable (7301)"
+ ::= { airIRmPmLouver2 2 }
+
+airIRmPmLouver2Position OBJECT-TYPE
+ SYNTAX INTEGER {
+ closed (1),
+ open (2) }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Louver 2 position (7302)"
+ ::= { airIRmPmLouver2 3 }
+
+airIRmPmLouver2ManOpPosition OBJECT-TYPE
+ SYNTAX INTEGER {
+ closed (1),
+ open (2) }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Louver 2 manual operation position setting (7303)"
+ ::= { airIRmPmLouver2 4 }
+
+-- airIRmPmLouver3
+
+airIRmPmLouver3ManOpEnable OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Louver 3 manual operation enable (7401)"
+ ::= { airIRmPmLouver3 2 }
+
+airIRmPmLouver3Position OBJECT-TYPE
+ SYNTAX INTEGER {
+ closed (1),
+ open (2) }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Louver 3 position (7402)"
+ ::= { airIRmPmLouver3 3 }
+
+airIRmPmLouver3ManOpPosition OBJECT-TYPE
+ SYNTAX INTEGER {
+ closed (1),
+ open (2) }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Louver 3 manual operation position setting (7403)"
+ ::= { airIRmPmLouver3 4 }
+
+-- airIRmPmAuxAlarm1
+-- Empty
+
+-- airIRmPmAuxAlarm2
+-- Empty
+
+-- airIRmPmAuxAlarm3
+-- Empty
+
+-- airIRmPmAuxAlarm4
+-- Empty
+
+-- airIRmPmAuxAlarm5
+-- Empty
+
+
+-- airIRmPmAlarmBits
+
+airIRmPmFan1Failure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Fan #1 failure (8500)."
+ ::= { airIRmPmAlarmBits 1 }
+
+airIRmPmFan2Failure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Fan #2 failure (8501)."
+ ::= { airIRmPmAlarmBits 2 }
+
+airIRmPmFan3Failure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Fan #3 failure (8502)."
+ ::= { airIRmPmAlarmBits 3 }
+
+airIRmPmCompressor1Failure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Compressor #1 failure (8503)."
+ ::= { airIRmPmAlarmBits 4 }
+
+airIRmPmCompressor2Failure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Compressor #2 failure (8504)."
+ ::= { airIRmPmAlarmBits 5 }
+
+airIRmPmWaterDetector OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Water detector alarm (8505)."
+ ::= { airIRmPmAlarmBits 6 }
+
+airIRmPmPhaseFailure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Phase failure (8506)."
+ ::= { airIRmPmAlarmBits 7 }
+
+airIRmPmFireSmokeDetector OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Fire/smoke detector (8507)."
+ ::= { airIRmPmAlarmBits 8 }
+
+airIRmPmReturnAirTemperatureTooHigh OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Return air temperature too high (8508)."
+ ::= { airIRmPmAlarmBits 9 }
+
+airIRmPmReturnAirHumidityTooHigh OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Return air humidity too high (8509)."
+ ::= { airIRmPmAlarmBits 10 }
+
+airIRmPmSupplyAirTemperatureTooHigh OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Supply air temperature too high (8510)."
+ ::= { airIRmPmAlarmBits 11 }
+
+airIRmPmSupplyAirHumidityTooHigh OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Supply air humidity too high (8511)."
+ ::= { airIRmPmAlarmBits 12 }
+
+airIRmPmWaterTemperatureTooHigh OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Water temperature too high (8512)."
+ ::= { airIRmPmAlarmBits 13 }
+
+airIRmPmReturnAirTemperatureTooLow OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Return air temperature too low (8513)."
+ ::= { airIRmPmAlarmBits 14 }
+
+airIRmPmReturnAirHumidityTooLow OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Return air humidity too low (8514)."
+ ::= { airIRmPmAlarmBits 15 }
+
+airIRmPmSupplyAirTemperatureTooLow OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Supply air temperature too low (8515)."
+ ::= { airIRmPmAlarmBits 16 }
+
+airIRmPmSupplyAirHumidityTooLow OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Supply air humidity too low (8516)."
+ ::= { airIRmPmAlarmBits 17 }
+
+airIRmPmWaterTemperatureTooLow OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Water temperature too low (8517)."
+ ::= { airIRmPmAlarmBits 18 }
+
+airIRmPmSensor1Failure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor #1 failure (8518)."
+ ::= { airIRmPmAlarmBits 19 }
+
+airIRmPmSensor2Failure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor #2 failure (8519)."
+ ::= { airIRmPmAlarmBits 20 }
+
+airIRmPmSensor3Failure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor #3 failure (8520)."
+ ::= { airIRmPmAlarmBits 21 }
+
+airIRmPmSensor4Failure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor #4 failure (8521)."
+ ::= { airIRmPmAlarmBits 22 }
+
+airIRmPmSensor5Failure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor #5 failure (8522)."
+ ::= { airIRmPmAlarmBits 23 }
+
+airIRmPmSensor6Failure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor #6 failure (8523)."
+ ::= { airIRmPmAlarmBits 24 }
+
+airIRmPmSensor7Failure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor #7 failure (8524)."
+ ::= { airIRmPmAlarmBits 25 }
+
+airIRmPmSensor8Failure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor #8 failure (8525)."
+ ::= { airIRmPmAlarmBits 26 }
+
+airIRmPmSensor9Failure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor #9 failure (8526)."
+ ::= { airIRmPmAlarmBits 27 }
+
+airIRmPmSensor10Failure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor #10 failure (8527)."
+ ::= { airIRmPmAlarmBits 28 }
+
+airIRmPmSensor11Failure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor #11 failure (8528)."
+ ::= { airIRmPmAlarmBits 29 }
+
+airIRmPmSensor12Failure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor #12 failure (8529)."
+ ::= { airIRmPmAlarmBits 30 }
+
+airIRmPmSensor13Failure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor #13 failure (8530)."
+ ::= { airIRmPmAlarmBits 31 }
+
+airIRmPmSensor14Failure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor #14 failure (8531)."
+ ::= { airIRmPmAlarmBits 32 }
+
+airIRmPmSensor15Failure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor #15 failure (8532)."
+ ::= { airIRmPmAlarmBits 33 }
+
+airIRmPmSensor16Failure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor #16 failure (8533)."
+ ::= { airIRmPmAlarmBits 34 }
+
+airIRmPmSensor17Failure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor #17 failure (8534)."
+ ::= { airIRmPmAlarmBits 35 }
+
+airIRmPmSensor18Failure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor #18 failure (8535)."
+ ::= { airIRmPmAlarmBits 36 }
+
+airIRmPmSensor19Failure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor #19 failure (8536)."
+ ::= { airIRmPmAlarmBits 37 }
+
+airIRmPmSensor20Failure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor #20 failure (8537)."
+ ::= { airIRmPmAlarmBits 38 }
+
+airIRmPmSensor21Failure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor #21 failure (8538)."
+ ::= { airIRmPmAlarmBits 39 }
+
+airIRmPmSensor1Defect OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor #1 defect (8539)."
+ ::= { airIRmPmAlarmBits 40 }
+
+airIRmPmSensor2Defect OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor #2 defect (8540)."
+ ::= { airIRmPmAlarmBits 41 }
+
+airIRmPmSensor3Defect OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor #3 defect (8541)."
+ ::= { airIRmPmAlarmBits 42 }
+
+airIRmPmSensor4Defect OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor #4 defect (8542)."
+ ::= { airIRmPmAlarmBits 43 }
+
+airIRmPmSensor5Defect OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor #5 defect (8543)."
+ ::= { airIRmPmAlarmBits 44 }
+
+airIRmPmSensor6Defect OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor #6 defect (8544)."
+ ::= { airIRmPmAlarmBits 45 }
+
+airIRmPmSensor7Defect OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor #7 defect (8545)."
+ ::= { airIRmPmAlarmBits 46 }
+
+airIRmPmSensor8Defect OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor #8 defect (8546)."
+ ::= { airIRmPmAlarmBits 47 }
+
+airIRmPmSensor9Defect OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor #9 defect (8547)."
+ ::= { airIRmPmAlarmBits 48 }
+
+airIRmPmSensor10Defect OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor #10 defect (8548)."
+ ::= { airIRmPmAlarmBits 49 }
+
+airIRmPmSensor11Defect OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor #11 defect (8549)."
+ ::= { airIRmPmAlarmBits 50 }
+
+airIRmPmSensor12Defect OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor #12 defect (8550)."
+ ::= { airIRmPmAlarmBits 51 }
+
+airIRmPmSensor13Defect OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor #13 defect (8551)."
+ ::= { airIRmPmAlarmBits 52 }
+
+airIRmPmSensor14Defect OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor #14 defect (8552)."
+ ::= { airIRmPmAlarmBits 53 }
+
+airIRmPmSensor15Defect OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor #15 defect (8553)."
+ ::= { airIRmPmAlarmBits 54 }
+
+airIRmPmSensor16Defect OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor #16 defect (8554)."
+ ::= { airIRmPmAlarmBits 55 }
+
+airIRmPmSensor17Defect OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor #17 defect (8555)."
+ ::= { airIRmPmAlarmBits 56 }
+
+airIRmPmSensor18Defect OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor #18 defect (8556)"
+ ::= { airIRmPmAlarmBits 57 }
+
+airIRmPmSensor19Defect OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor #19 defect (8557)."
+ ::= { airIRmPmAlarmBits 58 }
+
+airIRmPmSensor20Defect OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor #20 defect (8558)."
+ ::= { airIRmPmAlarmBits 59 }
+
+airIRmPmSensor21Defect OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Sensor #21 defect (8559)."
+ ::= { airIRmPmAlarmBits 60 }
+
+airIRmPmCompressor1Alarm OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Compressor #1 alarm (8560)."
+ ::= { airIRmPmAlarmBits 61 }
+
+airIRmPmCompressor2Alarm OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Compressor #2 alarm (8561)."
+ ::= { airIRmPmAlarmBits 62 }
+
+airIRmPmCompressor1LowPressure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Compressor #1 low pressure (8562)."
+ ::= { airIRmPmAlarmBits 63 }
+
+airIRmPmCompressor2LowPressure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Compressor #2 low pressure (8563)."
+ ::= { airIRmPmAlarmBits 64 }
+
+airIRmPmReheat1Failure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Reheat #1 failure (8564)."
+ ::= { airIRmPmAlarmBits 65 }
+
+airIRmPmReheat2Failure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Reheat #2 failure (8565)."
+ ::= { airIRmPmAlarmBits 66 }
+
+airIRmPmReheat3Failure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Reheat #3 failure (8566)."
+ ::= { airIRmPmAlarmBits 67 }
+
+airIRmPmReheat4Failure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Reheat #4 failure (8567)."
+ ::= { airIRmPmAlarmBits 68 }
+
+airIRmPmDrycooler1Failure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler #1 failure (8568)."
+ ::= { airIRmPmAlarmBits 69 }
+
+airIRmPmDrycooler2Failure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler #2 failure (8569)."
+ ::= { airIRmPmAlarmBits 70 }
+
+airIRmPmDrycooler3Failure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler #3 failure (8570)."
+ ::= { airIRmPmAlarmBits 71 }
+
+airIRmPmDrycooler4Failure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Drycooler #4 failure (8571)."
+ ::= { airIRmPmAlarmBits 72 }
+
+airIRmPmPump1Failure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Pump #1 failure (8572)."
+ ::= { airIRmPmAlarmBits 73 }
+
+airIRmPmPump2Failure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Pump #2 failure (8573)."
+ ::= { airIRmPmAlarmBits 74 }
+
+airIRmPmPump3Failure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Pump #3 failure (8574)."
+ ::= { airIRmPmAlarmBits 75 }
+
+airIRmPmPump4Failure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Pump #4 failure (8575)."
+ ::= { airIRmPmAlarmBits 76 }
+
+airIRmPmHumidifier1Failure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Humidifier #1 failure (8576)."
+ ::= { airIRmPmAlarmBits 77 }
+
+airIRmPmHumidifier2Failure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Humidifier #2 failure (8577)."
+ ::= { airIRmPmAlarmBits 78 }
+
+airIRmPmHumidifier3Failure OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Humidifier #3 failure (8578)."
+ ::= { airIRmPmAlarmBits 79 }
+
+airIRmPmHumidifier1Alarm5us OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Humidifier #1 5us alarm (8579)."
+ ::= { airIRmPmAlarmBits 80 }
+
+airIRmPmHumidifier2Alarm5us OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Humidifier #2 5us alarm (8580)."
+ ::= { airIRmPmAlarmBits 81 }
+
+airIRmPmHumidifier3Alarm5us OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Humidifier #3 5us alarm (8581)."
+ ::= { airIRmPmAlarmBits 82 }
+
+airIRmPmHumidifier1Alarm20us OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Humidifier #1 20us alarm (8582)."
+ ::= { airIRmPmAlarmBits 83 }
+
+airIRmPmHumidifier2Alarm20us OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Humidifier #2 20us alarm (8583)."
+ ::= { airIRmPmAlarmBits 84 }
+
+airIRmPmHumidifier3Alarm20us OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Humidifier #3 20us alarm (8584)."
+ ::= { airIRmPmAlarmBits 85 }
+
+airIRmPmFan1Alarm OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Fan #1 alarm (8585)."
+ ::= { airIRmPmAlarmBits 86 }
+
+airIRmPmFan2Alarm OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Fan #2 alarm (8586)."
+ ::= { airIRmPmAlarmBits 87 }
+
+airIRmPmFan3Alarm OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Fan #3 alarm (8587)."
+ ::= { airIRmPmAlarmBits 88 }
+
+airIRmPmFilter1Clogged OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Filter #1 clogged (8588)."
+ ::= { airIRmPmAlarmBits 89 }
+
+airIRmPmFilter2Clogged OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Filter #2 clogged (8589)."
+ ::= { airIRmPmAlarmBits 90 }
+
+airIRmPmFilter3Clogged OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Filter #3 clogged (8590)."
+ ::= { airIRmPmAlarmBits 91 }
+
+airIRmPmAuxiliaryAlarm1 OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Auxiliary #1 alarm (8591)."
+ ::= { airIRmPmAlarmBits 92 }
+
+airIRmPmAuxiliaryAlarm2 OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Auxiliary #2 alarm (8592)."
+ ::= { airIRmPmAlarmBits 93 }
+
+airIRmPmAuxiliaryAlarm3 OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Auxiliary #3 alarm (8593)."
+ ::= { airIRmPmAlarmBits 94 }
+
+airIRmPmAuxiliaryAlarm4 OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Auxiliary #4 alarm (8594)."
+ ::= { airIRmPmAlarmBits 95 }
+
+airIRmPmAuxiliaryAlarm5 OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Auxiliary #5 alarm (8595)."
+ ::= { airIRmPmAlarmBits 96 }
+
+airIRmPmAuxiliaryAlarm6 OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Auxiliary #6 alarm (8596)."
+ ::= { airIRmPmAlarmBits 97 }
+
+airIRmPmAuxiliaryAlarm7 OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Auxiliary #7 alarm (8597)."
+ ::= { airIRmPmAlarmBits 98 }
+
+airIRmPmAuxiliaryAlarm8 OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Auxiliary #8 alarm (8598)."
+ ::= { airIRmPmAlarmBits 99 }
+
+airIRmPmAuxiliaryAlarm9 OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Auxiliary #9 alarm (8599)."
+ ::= { airIRmPmAlarmBits 100 }
+
+airIRmPmAuxiliaryAlarm10 OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Auxiliary #10 alarm (8600)."
+ ::= { airIRmPmAlarmBits 101 }
+
+airIRmPmHotGasHeatingAlarm OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Hot gas heating alarm (8601)."
+ ::= { airIRmPmAlarmBits 102 }
+
+airIRmPmEEV1PressureSensorError OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "EEV1 pressure sensor error (8602)."
+ ::= { airIRmPmAlarmBits 103 }
+
+airIRmPmEEV1TemperatureSensorError OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "EEV1 temperature sensor error (8603)."
+ ::= { airIRmPmAlarmBits 104 }
+
+airIRmPmEEV1StepperMotorError OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "EEV1 stepper motor error (8604)."
+ ::= { airIRmPmAlarmBits 105 }
+
+airIRmPmEEV2PressureSensorError OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "EEV2 pressure sensor error (8605)."
+ ::= { airIRmPmAlarmBits 106 }
+
+airIRmPmEEV2TemperatureSensorError OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "EEV2 temperature sensor error (8606)."
+ ::= { airIRmPmAlarmBits 107 }
+
+airIRmPmEEV2StepperMotorError OBJECT-TYPE
+ SYNTAX AirIRmAlarmState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "EEV2 stepper motor error (8607)."
+ ::= { airIRmPmAlarmBits 108 }
+
+-- airIRmPmMyZone
+
+airIRmPmMyZoneNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "My zone number (11700)."
+ ::= { airIRmPmMyZone 1 }
+
+airIRmPmMyZoneRoomTemperature OBJECT IDENTIFIER ::= { airIRmPmMyZone 2 }
+airIRmPmMyZoneRoomTemperatureC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "My zone room temperature in tenths of degrees Celsius (11701)."
+ ::= { airIRmPmMyZoneRoomTemperature 1 }
+airIRmPmMyZoneRoomTemperatureF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "My zone room temperature in tenths of degrees Fahrenheit (11701)."
+ ::= { airIRmPmMyZoneRoomTemperature 2 }
+
+airIRmPmMyZoneRoomHumidity OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "My zone room humidity in tenths of %RH (11702)."
+ ::= { airIRmPmMyZone 3 }
+
+airIRmPmMyZoneSupplyTemperature OBJECT IDENTIFIER ::= { airIRmPmMyZone 4 }
+airIRmPmMyZoneSupplyTemperatureC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "My zone supply temperature in tenths of degrees Celsius (11703)."
+ ::= { airIRmPmMyZoneSupplyTemperature 1 }
+airIRmPmMyZoneSupplyTemperatureF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "My zone supply temperature in tenths
+ of degrees Fahrenheit (11703)."
+ ::= { airIRmPmMyZoneSupplyTemperature 2 }
+
+airIRmPmMyZoneSupplyHumidity OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "My zone supply humidity in tenths of %RH (11704)."
+ ::= { airIRmPmMyZone 5 }
+
+airIRmPmMyZoneSequencingTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "My zone sequencing time in minutes (11705)."
+ ::= { airIRmPmMyZone 6 }
+
+airIRmPmMyZoneNumberOfErrorUnits OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Number of error units in my zone (11706)."
+ ::= { airIRmPmMyZone 7 }
+
+airIRmPmMyZoneEmergencyTemperature OBJECT IDENTIFIER ::= { airIRmPmMyZone 8 }
+airIRmPmMyZoneEmergencyTemperatureC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "My zone emergency temperature in tenths of degrees Celsius (11707)."
+ ::= { airIRmPmMyZoneEmergencyTemperature 1 }
+airIRmPmMyZoneEmergencyTemperatureF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "My zone emergency temperature in tenths
+ of degrees Fahrenheit (11707)."
+ ::= { airIRmPmMyZoneEmergencyTemperature 2 }
+
+airIRmPmMyZoneCWEnergySaveMode OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "My zone CW energy save mode (11708)."
+ ::= { airIRmPmMyZone 9 }
+
+-- airIRmPmGlobalZoneData
+
+airIRmPmGlobalZoneDataEmergencyOpMode OBJECT-TYPE
+ SYNTAX AirIRmActivityState
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Emergency operation mode (11800)."
+ ::= { airIRmPmGlobalZoneData 1 }
+
+-- End of AC InRoom
+
+-- Begining of airIRGen3
+
+-- ******************************************************************
+--airIRG3 Ident Group
+-- ******************************************************************
+
+airIRG3IdentTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The ident table size."
+ ::= { airIRG3Ident 1 }
+
+AirIRG3IdentEntry ::= SEQUENCE {
+ airIRG3IdentIndex INTEGER,
+ airIRG3IdentName DisplayString,
+ airIRG3IdentLocation DisplayString,
+ airIRG3IdentModelNumber DisplayString,
+ airIRG3IdentSerialNumber DisplayString,
+ airIRG3IdentFirmwareRevision DisplayString,
+ airIRG3IdentHardwareRevision DisplayString,
+ airIRG3IdentManufactureDate DisplayString,
+ airIRG3IdentRDUSysOID OBJECT IDENTIFIER,
+ airIRG3IdentCMSysOID OBJECT IDENTIFIER,
+ airIRG3IdentGroupSysOID OBJECT IDENTIFIER
+ }
+
+airIRG3IdentTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AirIRG3IdentEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows to get ident information of current RDU and its assigned CM's."
+ ::= { airIRG3Ident 2 }
+
+airIRG3IdentEntry OBJECT-TYPE
+ SYNTAX AirIRG3IdentEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The ident table entry."
+ INDEX { airIRG3IdentIndex}
+ ::= { airIRG3IdentTable 1 }
+
+airIRG3IdentIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index of ident table."
+ ::= { airIRG3IdentEntry 1 }
+
+airIRG3IdentName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the unit name."
+ ::= { airIRG3IdentEntry 2 }
+
+airIRG3IdentLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the unit location."
+ ::= { airIRG3IdentEntry 3 }
+
+airIRG3IdentModelNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the unit model number."
+ ::= { airIRG3IdentEntry 4 }
+
+airIRG3IdentSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the unit serial number."
+ ::= { airIRG3IdentEntry 5 }
+
+airIRG3IdentFirmwareRevision OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the unit firmware version."
+ ::= { airIRG3IdentEntry 6 }
+
+airIRG3IdentHardwareRevision OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the unit controller hardware revision."
+ ::= { airIRG3IdentEntry 7 }
+
+airIRG3IdentManufactureDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the unit manufacture date."
+ ::= { airIRG3IdentEntry 8 }
+
+airIRG3IdentRDUSysOID OBJECT-TYPE
+ SYNTAX OBJECT IDENTIFIER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID contains an OID path to the RDU data."
+ ::= { airIRG3IdentEntry 9 }
+
+airIRG3IdentCMSysOID OBJECT-TYPE
+ SYNTAX OBJECT IDENTIFIER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID contains an OID path to the cooling module data."
+ ::= { airIRG3IdentEntry 10 }
+
+airIRG3IdentGroupSysOID OBJECT-TYPE
+ SYNTAX OBJECT IDENTIFIER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID contains an OID path to the group data."
+ ::= { airIRG3IdentEntry 11 }
+
+
+
+-- ******************************************************************
+-- airIRG3 Group Status
+-- ******************************************************************
+
+airIRG3GroupTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group table size."
+ ::= { airIRG3Group 1 }
+
+
+AirIRG3GroupStatusEntry ::= SEQUENCE {
+ airIRG3GroupStatusIndex INTEGER,
+ airIRG3GroupStatusCoolOutput INTEGER,
+ airIRG3GroupStatusCoolDemand INTEGER,
+ airIRG3GroupStatusAirFlowUS INTEGER,
+ airIRG3GroupStatusAirFlowMetric INTEGER,
+ airIRG3GroupStatusMaxRackInletTempUS INTEGER,
+ airIRG3GroupStatusMaxRackInletTempMetric INTEGER,
+ airIRG3GroupStatusMinRackInletTempUS INTEGER,
+ airIRG3GroupStatusMinRackInletTempMetric INTEGER,
+ airIRG3GroupStatusMaxReturnAirTempUS INTEGER,
+ airIRG3GroupStatusMaxReturnAirTempMetric INTEGER,
+ airIRG3GroupStatusMinReturnAirTempUS INTEGER,
+ airIRG3GroupStatusMinReturnAirTempMetric INTEGER,
+ airIRG3GroupStatusAvgSupplyTempUS INTEGER,
+ airIRG3GroupStatusAvgSupplyTempMetric INTEGER,
+ airIRG3GroupStatusAvgReturnTempUS INTEGER,
+ airIRG3GroupStatusAvgReturnTempMetric INTEGER,
+ airIRG3GroupStatusAvgFanSpeed INTEGER,
+ airIRG3GroupStatusAvgAirFlowUS INTEGER,
+ airIRG3GroupStatusAvgAirFlowMetric INTEGER,
+ airIRG3GroupStatusTotalAirFlowUS INTEGER,
+ airIRG3GroupStatusTotalAirFlowMetric INTEGER
+ }
+
+airIRG3GroupStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AirIRG3GroupStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows to get group status information."
+ ::= { airIRG3Group 2 }
+
+airIRG3GroupStatusEntry OBJECT-TYPE
+ SYNTAX AirIRG3GroupStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The group staus table entry."
+ INDEX { airIRG3GroupStatusIndex}
+ ::= { airIRG3GroupStatusTable 1 }
+
+airIRG3GroupStatusIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index of group status table."
+ ::= { airIRG3GroupStatusEntry 1 }
+
+airIRG3GroupStatusCoolOutput OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group cooling output in tenths of kilowatts (kW).
+ Returns (-1) if not supported."
+ ::= { airIRG3GroupStatusEntry 2 }
+
+airIRG3GroupStatusCoolDemand OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group cooling demand in tenths of kilowatts (kW).
+ Returns (-1) if not supported."
+ ::= { airIRG3GroupStatusEntry 3 }
+
+airIRG3GroupStatusAirFlowUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group air flow in cubic feet per minute (CFM).
+ Returns (-1) if not supported."
+ ::= { airIRG3GroupStatusEntry 4 }
+
+airIRG3GroupStatusAirFlowMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group air flow in liters per second (L/s).
+ Returns (-1) if not supported."
+ ::= { airIRG3GroupStatusEntry 5 }
+
+airIRG3GroupStatusMaxRackInletTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group maximum rack inlet temperature in tenths of
+ degrees Fahrenheit. Returns (-1) if not supported."
+ ::= { airIRG3GroupStatusEntry 6 }
+
+airIRG3GroupStatusMaxRackInletTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group maximum rack inlet temperature in tenths of
+ degrees Celsius. Returns (-1) if not supported."
+ ::= { airIRG3GroupStatusEntry 7 }
+
+airIRG3GroupStatusMinRackInletTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group minimum rack inlet temperature in tenths of
+ degrees Fahrenheit. Returns (-1) if not supported."
+ ::= { airIRG3GroupStatusEntry 8 }
+
+airIRG3GroupStatusMinRackInletTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group minimum rack inlet temperature in tenths of
+ degrees Celsius. Returns (-1) if not supported."
+ ::= { airIRG3GroupStatusEntry 9 }
+
+airIRG3GroupStatusMaxReturnAirTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group maximum return air temperature in tenths of
+ degrees Fahrenheit. Returns (-1) if not supported."
+ ::= { airIRG3GroupStatusEntry 10 }
+
+airIRG3GroupStatusMaxReturnAirTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group maximum return air temperature in tenths of
+ degrees Celsius. Returns (-1) if not supported."
+ ::= { airIRG3GroupStatusEntry 11 }
+
+airIRG3GroupStatusMinReturnAirTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group minimum return air temperature in tenths of
+ degrees Fahrenheit. Returns (-1) if not supported."
+ ::= { airIRG3GroupStatusEntry 12 }
+
+airIRG3GroupStatusMinReturnAirTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group minimum return air temperature in tenths of
+ degrees Celsius. Returns (-1) if not supported."
+ ::= { airIRG3GroupStatusEntry 13 }
+
+airIRG3GroupStatusAvgSupplyTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group average supply air temperature in tenths of
+ degrees Fahrenheit. Returns (-1) if not supported."
+ ::= { airIRG3GroupStatusEntry 14 }
+
+airIRG3GroupStatusAvgSupplyTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group average supply air temperature in tenths of
+ degrees Celsius. Returns (-1) if not supported."
+ ::= { airIRG3GroupStatusEntry 15 }
+
+airIRG3GroupStatusAvgReturnTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group average return air temperature in tenths of
+ degrees Fahrenheit. Returns (-1) if not supported."
+ ::= { airIRG3GroupStatusEntry 16 }
+
+airIRG3GroupStatusAvgReturnTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group average return air temperature in tenths of
+ degrees Celsius. Returns (-1) if not supported."
+ ::= { airIRG3GroupStatusEntry 17 }
+
+airIRG3GroupStatusAvgFanSpeed OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group average fan speed in revolutions per minute (RPM).
+ Returns (-1) if not supported."
+ ::= { airIRG3GroupStatusEntry 18 }
+
+airIRG3GroupStatusAvgAirFlowUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group average air flow in cubic feet per minute (CFM).
+ Returns (-1) if not supported."
+ ::= { airIRG3GroupStatusEntry 19 }
+
+airIRG3GroupStatusAvgAirFlowMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group average air flow in liters per second (L/s).
+ Returns (-1) if not supported."
+ ::= { airIRG3GroupStatusEntry 20 }
+
+airIRG3GroupStatusTotalAirFlowUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group total air flow in cubic feet per minute (CFM).
+ Returns (-1) if not supported."
+ ::= { airIRG3GroupStatusEntry 21 }
+
+airIRG3GroupStatusTotalAirFlowMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The group total air flow in liters per second (L/s).
+ Returns (-1) if not supported."
+ ::= { airIRG3GroupStatusEntry 22 }
+
+
+
+-- ******************************************************************
+--airIRG3 Group Setpoints
+-- ******************************************************************
+
+AirIRG3GroupSetpointsEntry ::= SEQUENCE {
+ airIRG3GroupSetpointsIndex INTEGER,
+ airIRG3GroupSetpointsCoolSetpointUS INTEGER,
+ airIRG3GroupSetpointsCoolSetpointMetric INTEGER,
+ airIRG3GroupSetpointsCoolDeadbandUS INTEGER,
+ airIRG3GroupSetpointsCoolDeadbandMetric INTEGER,
+ airIRG3GroupSetpointsFanSpeedPreference INTEGER,
+ airIRG3GroupSetpointsSupplyAirSetpointUS INTEGER,
+ airIRG3GroupSetpointsSupplyAirSetpointMetric INTEGER,
+ airIRG3GroupSetpointsAirFlowControl INTEGER,
+ airIRG3GroupSetpointsLightingOnTime INTEGER
+ }
+
+airIRG3GroupSetpointsTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AirIRG3GroupSetpointsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows to access the group setpoints."
+ ::= { airIRG3Group 3 }
+
+airIRG3GroupSetpointsEntry OBJECT-TYPE
+ SYNTAX AirIRG3GroupSetpointsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The group setpoints table entry."
+ INDEX { airIRG3GroupSetpointsIndex}
+ ::= { airIRG3GroupSetpointsTable 1 }
+
+airIRG3GroupSetpointsIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index of group setpoints table."
+ ::= { airIRG3GroupSetpointsEntry 1 }
+
+airIRG3GroupSetpointsCoolSetpointUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Group cooling setpoint in tenths of
+ degrees Fahrenheit."
+ ::= { airIRG3GroupSetpointsEntry 2 }
+
+airIRG3GroupSetpointsCoolSetpointMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Group cooling setpoint in tenths of
+ degrees Celsius."
+ ::= { airIRG3GroupSetpointsEntry 3 }
+
+airIRG3GroupSetpointsCoolDeadbandUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Group cooling deadband in tenths of
+ degrees Fahrenheit. Returns (-1) if not supported."
+ ::= { airIRG3GroupSetpointsEntry 4 }
+
+airIRG3GroupSetpointsCoolDeadbandMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Group cooling deadband in tenths of
+ degrees Celsius. Returns (-1) if not supported."
+ ::= { airIRG3GroupSetpointsEntry 5 }
+
+airIRG3GroupSetpointsFanSpeedPreference OBJECT-TYPE
+ SYNTAX INTEGER {
+ low (1),
+ med-low (2),
+ med (3),
+ med-high (4),
+ high (5)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The group preferred fan speed setting."
+ ::= { airIRG3GroupSetpointsEntry 6 }
+
+airIRG3GroupSetpointsSupplyAirSetpointUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Group supply air setpoint in tenths of
+ degrees Fahrenheit."
+ ::= { airIRG3GroupSetpointsEntry 7 }
+
+airIRG3GroupSetpointsSupplyAirSetpointMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Group supply air setpoint in tenths of
+ degrees Celsius."
+ ::= { airIRG3GroupSetpointsEntry 8 }
+
+airIRG3GroupSetpointsAirFlowControl OBJECT-TYPE
+ SYNTAX INTEGER {
+ automatic (1),
+ manual (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The group air flow control."
+ ::= { airIRG3GroupSetpointsEntry 9 }
+
+airIRG3GroupSetpointsLightingOnTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The group lighting on time in minutes."
+ ::= { airIRG3GroupSetpointsEntry 10 }
+
+
+-- ******************************************************************
+--airIRG3 Group Config
+-- ******************************************************************
+
+AirIRG3GroupConfigEntry ::= SEQUENCE {
+ airIRG3GroupConfigIndex INTEGER,
+ airIRG3GroupConfigNumberofCoolingUnits INTEGER,
+ airIRG3GroupConfigConfigurationType INTEGER,
+ airIRG3GroupConfigCapacityControlType INTEGER,
+ airIRG3GroupConfigFanSpeedControl INTEGER,
+ airIRG3GroupConfigCoolGainP INTEGER,
+ airIRG3GroupConfigCoolResetRateI INTEGER,
+ airIRG3GroupConfigCoolDerivativeD INTEGER,
+ airIRG3GroupConfigCoolPIDReset INTEGER,
+ airIRG3GroupConfigNumberofBackupUnits INTEGER,
+ airIRG3GroupConfigRuntimeBalancingEnable INTEGER,
+ airIRG3GroupConfigLoadAssistEnable INTEGER
+ }
+
+airIRG3GroupConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AirIRG3GroupConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows to access group configuration table."
+ ::= { airIRG3Group 4 }
+
+airIRG3GroupConfigEntry OBJECT-TYPE
+ SYNTAX AirIRG3GroupConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The group config table entry."
+ INDEX { airIRG3GroupConfigIndex}
+ ::= { airIRG3GroupConfigTable 1 }
+
+airIRG3GroupConfigIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index of group config table."
+ ::= { airIRG3GroupConfigEntry 1 }
+
+airIRG3GroupConfigNumberofCoolingUnits OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The number of cooling units."
+ ::= { airIRG3GroupConfigEntry 2 }
+
+airIRG3GroupConfigConfigurationType OBJECT-TYPE
+ SYNTAX INTEGER {
+ racs (1),
+ spot (2),
+ in-row (3),
+ hacs (4)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The group configuration type.
+ The spot configuration type is not supported.
+ Returns (-1) if not supported."
+ ::= { airIRG3GroupConfigEntry 3 }
+
+airIRG3GroupConfigCapacityControlType OBJECT-TYPE
+ SYNTAX INTEGER {
+ discrete (1),
+ proportional (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The group capacity control. Returns (-1) if not supported."
+ ::= { airIRG3GroupConfigEntry 4 }
+
+airIRG3GroupConfigFanSpeedControl OBJECT-TYPE
+ SYNTAX INTEGER {
+ automatic (1),
+ manual (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The group fan speed control."
+ ::= { airIRG3GroupConfigEntry 5 }
+
+airIRG3GroupConfigCoolGainP OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The gain component of the PID in hundredths."
+ ::= { airIRG3GroupConfigEntry 6 }
+
+airIRG3GroupConfigCoolResetRateI OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The integral component of the PID in hundredths."
+ ::= { airIRG3GroupConfigEntry 7 }
+
+airIRG3GroupConfigCoolDerivativeD OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The derivative component of the PID in hundredths."
+ ::= { airIRG3GroupConfigEntry 8 }
+
+airIRG3GroupConfigCoolPIDReset OBJECT-TYPE
+ SYNTAX INTEGER {
+ readBack (1),
+ reset (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Will reset the PID coefficients back to the factory defaults.
+ Readback is not supported, returns -1."
+ ::= { airIRG3GroupConfigEntry 9 }
+
+airIRG3GroupConfigNumberofBackupUnits OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The number of backup units."
+ ::= { airIRG3GroupConfigEntry 10 }
+
+airIRG3GroupConfigRuntimeBalancingEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable runtime balancing feature."
+ ::= { airIRG3GroupConfigEntry 11 }
+
+airIRG3GroupConfigLoadAssistEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable load assist feature."
+ ::= { airIRG3GroupConfigEntry 12 }
+
+
+-- ***************************************
+-- airIRG3 Alarm Status
+-- ***************************************
+
+airIRG3AlarmsTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of active alarms in the airIRG3AlarmsTable."
+ ::= { airIRG3Alarms 1 }
+
+AirIRG3AlarmsEntry ::= SEQUENCE {
+ airIRG3AlarmsIndex INTEGER,
+ airIRG3AlarmsEventCode INTEGER,
+ airIRG3AlarmsDescription DisplayString
+ }
+
+airIRG3AlarmsTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AirIRG3AlarmsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Table of active alarms for the device."
+ ::= { airIRG3Alarms 2 }
+
+airIRG3AlarmsEntry OBJECT-TYPE
+ SYNTAX AirIRG3AlarmsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Alarms specification"
+ INDEX { airIRG3AlarmsIndex }
+ ::= { airIRG3AlarmsTable 1 }
+
+airIRG3AlarmsIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Alarm index."
+ ::= { airIRG3AlarmsEntry 1 }
+
+airIRG3AlarmsEventCode OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Event Code for the alarm. Returns (-1) if not supported."
+ ::= { airIRG3AlarmsEntry 2 }
+
+airIRG3AlarmsDescription OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..64))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Description of the alarm. Returns (-1) if not supported."
+ ::= { airIRG3AlarmsEntry 3 }
+
+-- ***************************************
+-- airIRG3 RDU Status
+-- ***************************************
+
+airIRG3RDUTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU table size."
+ ::= { airIRG3RDU 1 }
+
+
+AirIRG3RDUStatusEntry ::= SEQUENCE {
+ airIRG3RDUStatusDeviceIndex INTEGER,
+ airIRG3RDUID DisplayString,
+ airIRG3RDUStatusOnReadyStandby INTEGER,
+ airIRG3RDUStatusOperatingMode INTEGER,
+ airIRG3RDUStatusLeadPump INTEGER,
+ airIRG3RDUStatusStartupDelay INTEGER,
+ airIRG3RDUStatusPumpChangeOverInterval INTEGER,
+ airIRG3RDUStatusStopOnLeakDetect INTEGER,
+ airIRG3RDUStatusPowerSource INTEGER,
+ airIRG3RDUStatusTotalRDUOutputPower INTEGER,
+ airIRG3RDUStatusInletWaterTempUS INTEGER,
+ airIRG3RDUStatusInletWaterTempMetric INTEGER,
+ airIRG3RDUStatusOutletWaterTempUS INTEGER,
+ airIRG3RDUStatusOutletWaterTempMetric INTEGER,
+ airIRG3RDUStatusCondenserSaturationTempUS INTEGER,
+ airIRG3RDUStatusCondenserSaturationTempMetric INTEGER,
+ airIRG3RDUStatusDewPointTempUS INTEGER,
+ airIRG3RDUStatusDewPointTempMetric INTEGER,
+ airIRG3RDUStatusPumpOutletTempUS INTEGER,
+ airIRG3RDUStatusPumpOutletTempMetric INTEGER,
+ airIRG3RDUStatusSubcoolerOutletTempUS INTEGER,
+ airIRG3RDUStatusSubcoolerOutletTempMetric INTEGER,
+ airIRG3RDUStatusCondenserOutletTempUS INTEGER,
+ airIRG3RDUStatusCondenserOutletTempMetric INTEGER,
+ airIRG3RDUStatusCondenserInletTempUS INTEGER,
+ airIRG3RDUStatusCondenserInletTempMetric INTEGER,
+ airIRG3RDUStatusCondenserOutletPressureUS INTEGER,
+ airIRG3RDUStatusCondenserOutletPressureMetric INTEGER,
+ airIRG3RDUStatusPump1HeadPressureUS INTEGER,
+ airIRG3RDUStatusPump1HeadPressureMetric INTEGER,
+ airIRG3RDUStatusPump2HeadPressureUS INTEGER,
+ airIRG3RDUStatusPump2HeadPressureMetric INTEGER,
+ airIRG3RDUStatusPump1Speed INTEGER,
+ airIRG3RDUStatusPump2Speed INTEGER,
+ airIRG3RDUStatusCWValvePosition INTEGER,
+ airIRG3RDUStatusReceiverLiquidLevel INTEGER,
+ airIRG3RDUStatusDCPowerSupply1Current INTEGER,
+ airIRG3RDUStatusDCPowerSupply2Current INTEGER,
+ airIRG3RDUStatusTotalDCPowerSupplyCurrent INTEGER,
+ airIRG3RDUStatusInputState INTEGER,
+ airIRG3RDUStatusOutputState INTEGER,
+ airIRG3RDUStatusByPassValvePosition INTEGER,
+ airIRG3RDUStatusRefrigerantLeakDetector INTEGER
+ }
+
+airIRG3RDUStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AirIRG3RDUStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows to access RDU status table."
+ ::= { airIRG3RDU 2 }
+
+airIRG3RDUStatusEntry OBJECT-TYPE
+ SYNTAX AirIRG3RDUStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU status table entry."
+ INDEX { airIRG3RDUStatusDeviceIndex}
+ ::= { airIRG3RDUStatusTable 1 }
+
+airIRG3RDUStatusDeviceIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index of RDU status table."
+ ::= { airIRG3RDUStatusEntry 1 }
+
+
+airIRG3RDUID OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current RDU ID (1 to F).
+ Configured RDU only shall display ID, else return -1. "
+ ::= { airIRG3RDUStatusEntry 2 }
+
+
+airIRG3RDUStatusOnReadyStandby OBJECT-TYPE
+ SYNTAX INTEGER {
+ standby (1),
+ ready (2),
+ on (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU current status."
+ ::= { airIRG3RDUStatusEntry 3 }
+
+
+airIRG3RDUStatusOperatingMode OBJECT-TYPE
+ SYNTAX INTEGER {
+ standby (1),
+ ready (2),
+ on (3),
+ stop (4),
+ maintenancemode (5)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU actual operating mode."
+ ::= { airIRG3RDUStatusEntry 4 }
+
+
+airIRG3RDUStatusLeadPump OBJECT-TYPE
+ SYNTAX INTEGER {
+ pump1 (1),
+ pump2 (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU lead pump."
+ ::= { airIRG3RDUStatusEntry 5 }
+
+
+airIRG3RDUStatusStartupDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU start up delay in seconds."
+ ::= { airIRG3RDUStatusEntry 6 }
+
+
+airIRG3RDUStatusPumpChangeOverInterval OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU pump change over interval in days."
+ ::= { airIRG3RDUStatusEntry 7 }
+
+
+airIRG3RDUStatusStopOnLeakDetect OBJECT-TYPE
+ SYNTAX INTEGER {
+ no (1),
+ yes (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU status of stop on leak detect."
+ ::= { airIRG3RDUStatusEntry 8 }
+
+
+airIRG3RDUStatusPowerSource OBJECT-TYPE
+ SYNTAX INTEGER {
+ singleFeed (1),
+ dualFeed (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU power source status."
+ ::= { airIRG3RDUStatusEntry 9 }
+
+
+airIRG3RDUStatusTotalRDUOutputPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU output power in tenths of kilowatts (kW)."
+ ::= { airIRG3RDUStatusEntry 10 }
+
+
+airIRG3RDUStatusInletWaterTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU inlet water temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRG3RDUStatusEntry 11 }
+
+
+airIRG3RDUStatusInletWaterTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU inlet water temperature in tenths of
+ degrees Celsius."
+ ::= { airIRG3RDUStatusEntry 12 }
+
+
+airIRG3RDUStatusOutletWaterTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU outlet water temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRG3RDUStatusEntry 13 }
+
+
+airIRG3RDUStatusOutletWaterTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU outlet water temperature in tenths of
+ degrees Celsius."
+ ::= { airIRG3RDUStatusEntry 14 }
+
+
+airIRG3RDUStatusCondenserSaturationTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU condenser saturation temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRG3RDUStatusEntry 15 }
+
+
+airIRG3RDUStatusCondenserSaturationTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU condenser saturation temperature in tenths of
+ degrees Celsius."
+ ::= { airIRG3RDUStatusEntry 16 }
+
+
+airIRG3RDUStatusDewPointTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU dew point temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRG3RDUStatusEntry 17 }
+
+
+airIRG3RDUStatusDewPointTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU dew point temperature in tenths of
+ degrees Celsius."
+ ::= { airIRG3RDUStatusEntry 18 }
+
+
+airIRG3RDUStatusPumpOutletTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU pump outlet temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRG3RDUStatusEntry 19 }
+
+
+airIRG3RDUStatusPumpOutletTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU pump outlet temperature in tenths of
+ degrees Celsius."
+ ::= { airIRG3RDUStatusEntry 20 }
+
+
+airIRG3RDUStatusSubcoolerOutletTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU sub cooler outlet temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRG3RDUStatusEntry 21 }
+
+
+airIRG3RDUStatusSubcoolerOutletTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU sub cooler outlet temperature in tenths of
+ degrees Celsius."
+ ::= { airIRG3RDUStatusEntry 22 }
+
+
+airIRG3RDUStatusCondenserOutletTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU condenser outlet temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRG3RDUStatusEntry 23 }
+
+
+airIRG3RDUStatusCondenserOutletTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU condenser outlet temperature in tenths of
+ degrees Celsius."
+ ::= { airIRG3RDUStatusEntry 24 }
+
+
+airIRG3RDUStatusCondenserInletTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU condenser inlet temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRG3RDUStatusEntry 25 }
+
+
+airIRG3RDUStatusCondenserInletTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU condenser inlet temperature in tenths of
+ degrees Celsius."
+ ::= { airIRG3RDUStatusEntry 26 }
+
+
+airIRG3RDUStatusCondenserOutletPressureUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU condenser outlet pressure in
+ pounds per square inch (PSI)."
+ ::= { airIRG3RDUStatusEntry 27 }
+
+airIRG3RDUStatusCondenserOutletPressureMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU condenser outlet pressure in kiloPascals (KPa)."
+ ::= { airIRG3RDUStatusEntry 28 }
+
+
+airIRG3RDUStatusPump1HeadPressureUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU Pump 1 head pressure in pounds per square inch (PSI)."
+ ::= { airIRG3RDUStatusEntry 29 }
+
+airIRG3RDUStatusPump1HeadPressureMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU Pump 1 head pressure in kiloPascals (KPa)."
+ ::= { airIRG3RDUStatusEntry 30 }
+
+airIRG3RDUStatusPump2HeadPressureUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU Pump 2 head pressure in pounds per square inch (PSI)."
+ ::= { airIRG3RDUStatusEntry 31 }
+
+airIRG3RDUStatusPump2HeadPressureMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU Pump 2 head pressure in kiloPascals (KPa)."
+ ::= { airIRG3RDUStatusEntry 32 }
+
+airIRG3RDUStatusPump1Speed OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU Pump 1 speed in revolutions per minute (RPM)."
+ ::= { airIRG3RDUStatusEntry 33 }
+
+
+airIRG3RDUStatusPump2Speed OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU Pump 2 speed in revolutions per minute (RPM)."
+ ::= { airIRG3RDUStatusEntry 34 }
+
+
+airIRG3RDUStatusCWValvePosition OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU CW Valve position in % open"
+ ::= { airIRG3RDUStatusEntry 35 }
+
+
+airIRG3RDUStatusReceiverLiquidLevel OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU receiver liquid level in % Full"
+ ::= { airIRG3RDUStatusEntry 36 }
+
+
+airIRG3RDUStatusDCPowerSupply1Current OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU DC Power Supply 1 Current in Amps"
+ ::= { airIRG3RDUStatusEntry 37 }
+
+
+airIRG3RDUStatusDCPowerSupply2Current OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU DC Power Supply 2 Current in Amps"
+ ::= { airIRG3RDUStatusEntry 38 }
+
+
+airIRG3RDUStatusTotalDCPowerSupplyCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU Total DC Power Supply Current in Amps"
+ ::= { airIRG3RDUStatusEntry 39 }
+
+
+airIRG3RDUStatusInputState OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU Input state."
+ ::= { airIRG3RDUStatusEntry 40 }
+
+
+airIRG3RDUStatusOutputState OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU Output state"
+ ::= { airIRG3RDUStatusEntry 41 }
+
+airIRG3RDUStatusByPassValvePosition OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU By Pass Valve position in % open"
+ ::= { airIRG3RDUStatusEntry 42 }
+
+airIRG3RDUStatusRefrigerantLeakDetector OBJECT-TYPE
+ SYNTAX INTEGER {
+ suspended (1),
+ calibrating (2),
+ operating (3),
+ disabled (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU refrigerant leak detector status."
+ ::= { airIRG3RDUStatusEntry 43 }
+
+
+-- ***************************************
+-- airIRG3 RDU Run Hours
+-- ***************************************
+
+AirIRG3RDURunHoursEntry ::= SEQUENCE {
+ airIRG3RDURunHoursDeviceIndex INTEGER,
+ airIRG3RDURunHoursRDUID DisplayString,
+ airIRG3RDURunHoursPump1 INTEGER,
+ airIRG3RDURunHoursPump2 INTEGER,
+ airIRG3RDURunHoursPowerSupply1 INTEGER,
+ airIRG3RDURunHoursPowerSupply2 INTEGER
+ }
+
+airIRG3RDURunHoursTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AirIRG3RDURunHoursEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows to access RDU run hours table."
+ ::= { airIRG3RDU 3 }
+
+airIRG3RDURunHoursEntry OBJECT-TYPE
+ SYNTAX AirIRG3RDURunHoursEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU run hours table entry."
+ INDEX { airIRG3RDURunHoursDeviceIndex}
+ ::= { airIRG3RDURunHoursTable 1 }
+
+airIRG3RDURunHoursDeviceIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index of RDU run hours table."
+ ::= { airIRG3RDURunHoursEntry 1 }
+
+airIRG3RDURunHoursRDUID OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current RDU ID (1 to F).
+ Configured RDU only shall display ID, else return -1. "
+ ::= { airIRG3RDURunHoursEntry 2 }
+
+airIRG3RDURunHoursPump1 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU run hours of Pump 1."
+ ::= { airIRG3RDURunHoursEntry 3 }
+
+airIRG3RDURunHoursPump2 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU run hours of Pump 2."
+ ::= { airIRG3RDURunHoursEntry 4 }
+
+airIRG3RDURunHoursPowerSupply1 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU run hours of power supply 1."
+ ::= { airIRG3RDURunHoursEntry 5 }
+
+airIRG3RDURunHoursPowerSupply2 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU run hours of power supply 2."
+ ::= { airIRG3RDURunHoursEntry 6 }
+
+
+-- ***************************************
+-- airIRG3 RDU Service Intervals
+-- ***************************************
+
+AirIRG3RDUServiceIntervalsEntry ::= SEQUENCE {
+ airIRG3RDUServiceIntervalsDeviceIndex INTEGER,
+ airIRG3RDUServiceIntervalsRDUID DisplayString,
+ airIRG3RDUServiceIntervalsAirFilterInterval INTEGER,
+ airIRG3RDUServiceIntervalsAirFilterAlarm INTEGER
+ }
+
+airIRG3RDUServiceIntervalsTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AirIRG3RDUServiceIntervalsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows to access RDU service intervals table."
+ ::= { airIRG3RDU 4 }
+
+airIRG3RDUServiceIntervalsEntry OBJECT-TYPE
+ SYNTAX AirIRG3RDUServiceIntervalsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The service interval table entry."
+ INDEX { airIRG3RDUServiceIntervalsDeviceIndex}
+ ::= { airIRG3RDUServiceIntervalsTable 1 }
+
+airIRG3RDUServiceIntervalsDeviceIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index of service interval table."
+ ::= { airIRG3RDUServiceIntervalsEntry 1 }
+
+airIRG3RDUServiceIntervalsRDUID OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current RDU ID (1 to F).
+ Configured RDU only shall display ID, else return -1. "
+ ::= { airIRG3RDUServiceIntervalsEntry 2 }
+
+airIRG3RDUServiceIntervalsAirFilterInterval OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU service interval for air filter in hours.
+ Returns -1 if not supported."
+ ::= { airIRG3RDUServiceIntervalsEntry 3 }
+
+
+airIRG3RDUServiceIntervalsAirFilterAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ enable (1),
+ disable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU service interval air filter alarm status.
+ Returns -1 if not supported."
+ ::= { airIRG3RDUServiceIntervalsEntry 4 }
+
+
+
+-- *******************************************
+-- airIRG3 RDU Thresholds
+-- Currently there are no thresholds for RDU
+-- *******************************************
+
+AirIRG3RDUThresholdsEntry ::= SEQUENCE {
+ airIRG3RDUThresholdsDeviceIndex INTEGER,
+ airIRG3RDUThresholdsRDUID DisplayString,
+ airIRG3RDUThresholdsEnteringFluidTempHighUS INTEGER,
+ airIRG3RDUThresholdsEnteringFluidTempHighMetric INTEGER
+ }
+
+airIRG3RDUThresholdsTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AirIRG3RDUThresholdsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows to access RDU thresholds table."
+ ::= { airIRG3RDU 5 }
+
+airIRG3RDUThresholdsEntry OBJECT-TYPE
+ SYNTAX AirIRG3RDUThresholdsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU thresholds table entry."
+ INDEX { airIRG3RDUThresholdsDeviceIndex}
+ ::= { airIRG3RDUThresholdsTable 1 }
+
+airIRG3RDUThresholdsDeviceIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index of RDU thresholds table."
+ ::= { airIRG3RDUThresholdsEntry 1 }
+
+airIRG3RDUThresholdsRDUID OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current RDU ID (1 to F).
+ Configured RDU only shall display ID, else return -1. "
+ ::= { airIRG3RDUThresholdsEntry 2 }
+
+airIRG3RDUThresholdsEnteringFluidTempHighUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU threshold for entering fluid temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRG3RDUThresholdsEntry 3 }
+
+
+airIRG3RDUThresholdsEnteringFluidTempHighMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU threshold for entering fluid temperature in tenths of
+ degrees Celsius."
+ ::= { airIRG3RDUThresholdsEntry 4 }
+
+
+-- ***************************************
+-- airIRG3 RDU Setpoints
+-- ***************************************
+
+AirIRG3RDUSetpointsEntry ::= SEQUENCE {
+ airIRG3RDUSetpointsDeviceIndex INTEGER
+ }
+
+airIRG3RDUSetpointsTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AirIRG3RDUSetpointsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows to access RDU set points table."
+ ::= { airIRG3RDU 6 }
+
+airIRG3RDUSetpointsEntry OBJECT-TYPE
+ SYNTAX AirIRG3RDUSetpointsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU set points table entry."
+ INDEX { airIRG3RDUSetpointsDeviceIndex}
+ ::= { airIRG3RDUSetpointsTable 1 }
+
+airIRG3RDUSetpointsDeviceIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index of RDU set points table."
+ ::= { airIRG3RDUSetpointsEntry 1 }
+
+
+
+-- ***************************************
+-- airIRG3 RDU Config
+-- ***************************************
+
+AirIRG3RDUConfigEntry ::= SEQUENCE {
+ airIRG3RDUConfigDeviceIndex INTEGER,
+ airIRG3RDUConfigRDUID DisplayString,
+ airIRG3RDUConfigStopOnLeakDetect INTEGER,
+ airIRG3RDUConfigStartupDelay INTEGER,
+ airIRG3RDUConfigPumpChangeOverInterval INTEGER,
+ airIRG3RDUConfigPowerSource INTEGER,
+ airIRG3RDUConfigOutputSource INTEGER,
+ airIRG3RDUConfigInputNormalState INTEGER,
+ airIRG3RDUConfigOutputNormalState INTEGER,
+ airIRG3RDUConfigByPassValveEnabled INTEGER,
+ airIRG3RDUConfigRefrigerantLeakDetectorEnabled INTEGER,
+ airIRG3RDUConfigCalibrateRefrigerantLeakDetector INTEGER,
+ airIRG3RDUConfigOnReadyStandby INTEGER
+ }
+
+airIRG3RDUConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AirIRG3RDUConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows to access RDU configuration table."
+ ::= { airIRG3RDU 7 }
+
+airIRG3RDUConfigEntry OBJECT-TYPE
+ SYNTAX AirIRG3RDUConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU configuration table entry."
+ INDEX { airIRG3RDUConfigDeviceIndex}
+ ::= { airIRG3RDUConfigTable 1 }
+
+airIRG3RDUConfigDeviceIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index of RDU configuration table."
+ ::= { airIRG3RDUConfigEntry 1 }
+
+airIRG3RDUConfigRDUID OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current RDU ID (1 to F).
+ Configured RDU only shall display ID, else return -1. "
+ ::= { airIRG3RDUConfigEntry 2 }
+
+airIRG3RDUConfigStopOnLeakDetect OBJECT-TYPE
+ SYNTAX INTEGER {
+ no (1),
+ yes (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU stop on leak detect set."
+ ::= { airIRG3RDUConfigEntry 3 }
+
+
+airIRG3RDUConfigStartupDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU start up delay in seconds."
+ ::= { airIRG3RDUConfigEntry 4 }
+
+
+airIRG3RDUConfigPumpChangeOverInterval OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU pump change over interval in days."
+ ::= { airIRG3RDUConfigEntry 5 }
+
+
+airIRG3RDUConfigPowerSource OBJECT-TYPE
+ SYNTAX INTEGER {
+ singleFeed (1),
+ dualFeed (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU power source."
+ ::= { airIRG3RDUConfigEntry 6 }
+
+
+airIRG3RDUConfigOutputSource OBJECT-TYPE
+ SYNTAX INTEGER {
+ anyalarm (1),
+ onlycriticalalarms (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU output source."
+ ::= { airIRG3RDUConfigEntry 7 }
+
+
+airIRG3RDUConfigInputNormalState OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU Input Normal State."
+ ::= { airIRG3RDUConfigEntry 8 }
+
+
+airIRG3RDUConfigOutputNormalState OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU Output Normal State."
+ ::= { airIRG3RDUConfigEntry 9 }
+
+
+airIRG3RDUConfigByPassValveEnabled OBJECT-TYPE
+ SYNTAX INTEGER {
+ no (1),
+ yes (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU By Pass Valve Enabled State."
+ ::= { airIRG3RDUConfigEntry 10 }
+
+airIRG3RDUConfigRefrigerantLeakDetectorEnabled OBJECT-TYPE
+ SYNTAX INTEGER {
+ no (1),
+ yes (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The RDU Refrigerant Leak Detector Enabled State."
+ ::= { airIRG3RDUConfigEntry 11 }
+
+airIRG3RDUConfigCalibrateRefrigerantLeakDetector OBJECT-TYPE
+ SYNTAX INTEGER {
+ no (1),
+ yes (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "This parameter allows to calibrate the RDU Refrigerant Leak Detector and is write only.
+ The read returns -1. Only 'yes' is supported."
+ ::= { airIRG3RDUConfigEntry 12 }
+
+airIRG3RDUConfigOnReadyStandby OBJECT-TYPE
+ SYNTAX INTEGER {
+ standby (1),
+ ready (2),
+ on (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "This parameter allows to configure RDU on/standby parameter.
+ Ready is currently not supported. If unsupported returns -1. "
+ ::= { airIRG3RDUConfigEntry 13 }
+
+
+-- ***************************************
+-- airIRG3 CMStatus
+-- ***************************************
+
+airIRG3CMTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The cooling module table size."
+ ::= { airIRG3CM 1 }
+
+
+AirIRG3CMStatusEntry ::= SEQUENCE {
+ airIRG3CMStatusDeviceIndex INTEGER,
+ airIRG3CMStatusCMID DisplayString,
+ airIRG3CMStatusOperatingMode INTEGER,
+ airIRG3CMStatusUnitType INTEGER,
+ airIRG3CMStatusRackInletTempUS INTEGER,
+ airIRG3CMStatusRackInletTempMetric INTEGER,
+ airIRG3CMStatusReturnAirTempUS INTEGER,
+ airIRG3CMStatusReturnAirTempMetric INTEGER,
+ airIRG3CMStatusLiquidTempUS INTEGER,
+ airIRG3CMStatusLiquidTempMetric INTEGER,
+ airIRG3CMStatusVaporTempUS INTEGER,
+ airIRG3CMStatusVaporTempMetric INTEGER,
+ airIRG3CMStatusEvaporatorTempUS INTEGER,
+ airIRG3CMStatusEvaporatorTempMetric INTEGER,
+ airIRG3CMStatusLiquidInletPressureUS INTEGER,
+ airIRG3CMStatusLiquidInletPressureMetric INTEGER,
+ airIRG3CMStatusVaporOutletPressureUS INTEGER,
+ airIRG3CMStatusVaporOutletPressureMetric INTEGER,
+ airIRG3CMStatusExpansionValvePosition INTEGER,
+ airIRG3CMStatusEPRValvePosition INTEGER,
+ airIRG3CMStatusLocalDisplayOnOffEnabled INTEGER,
+ airIRG3CMStatusAverageFanSpeed INTEGER
+ }
+
+airIRG3CMStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AirIRG3CMStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows to access CM status table."
+ ::= { airIRG3CM 2 }
+
+airIRG3CMStatusEntry OBJECT-TYPE
+ SYNTAX AirIRG3CMStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The CM status table entry."
+ INDEX { airIRG3CMStatusDeviceIndex}
+ ::= { airIRG3CMStatusTable 1 }
+
+airIRG3CMStatusDeviceIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index of CM status table."
+ ::= { airIRG3CMStatusEntry 1 }
+
+airIRG3CMStatusCMID OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The CM ID (RDU Number - Group Number - CM Unit Number)."
+ ::= { airIRG3CMStatusEntry 2 }
+
+airIRG3CMStatusOperatingMode OBJECT-TYPE
+ SYNTAX INTEGER {
+ standBy (1),
+ on (2),
+ idle (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current operating mode of the CM."
+ ::= { airIRG3CMStatusEntry 3 }
+
+
+airIRG3CMStatusUnitType OBJECT-TYPE
+ SYNTAX INTEGER{
+ unconfigured (1),
+ oa (2),
+ ra (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current CM unit type."
+ ::= { airIRG3CMStatusEntry 4 }
+
+
+airIRG3CMStatusRackInletTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The CM rack inlet temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRG3CMStatusEntry 5 }
+
+
+airIRG3CMStatusRackInletTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The CM rack inlet temperature in tenths of
+ degrees Celsius."
+ ::= { airIRG3CMStatusEntry 6 }
+
+
+airIRG3CMStatusReturnAirTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The CM return air temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRG3CMStatusEntry 7 }
+
+
+airIRG3CMStatusReturnAirTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The CM return air temperature in tenths of
+ degrees Celsius."
+ ::= { airIRG3CMStatusEntry 8 }
+
+
+airIRG3CMStatusLiquidTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The CM liquid temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRG3CMStatusEntry 9 }
+
+
+airIRG3CMStatusLiquidTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The CM liquid temperature in tenths of
+ degrees Celsius."
+ ::= { airIRG3CMStatusEntry 10 }
+
+
+airIRG3CMStatusVaporTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The CM vapor temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRG3CMStatusEntry 11 }
+
+
+airIRG3CMStatusVaporTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The CM vapor temperature in tenths of
+ degrees Celsius."
+ ::= { airIRG3CMStatusEntry 12 }
+
+
+airIRG3CMStatusEvaporatorTempUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The CM saturation temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRG3CMStatusEntry 13 }
+
+
+airIRG3CMStatusEvaporatorTempMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The CM saturation temperature in tenths of
+ degrees Celsius."
+ ::= { airIRG3CMStatusEntry 14 }
+
+airIRG3CMStatusLiquidInletPressureUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The CM Liquid Inlet pressure in pounds per square inch (PSI)."
+ ::= { airIRG3CMStatusEntry 15 }
+
+airIRG3CMStatusLiquidInletPressureMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The CM Liquid Inlet pressure in kiloPascals (kPa)."
+ ::= { airIRG3CMStatusEntry 16 }
+
+airIRG3CMStatusVaporOutletPressureUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The CM Vapor Outlet pressure in pounds per square inch (PSI)."
+ ::= { airIRG3CMStatusEntry 17 }
+
+airIRG3CMStatusVaporOutletPressureMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The CM Vapor Outlet pressure in kiloPascals (kPa)."
+ ::= { airIRG3CMStatusEntry 18 }
+
+airIRG3CMStatusExpansionValvePosition OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The CM expansion valve position in % open"
+ ::= { airIRG3CMStatusEntry 19 }
+
+
+airIRG3CMStatusEPRValvePosition OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The CM Evaporator Pressure Regulator Valve Position
+ in tenths of percent open"
+ ::= { airIRG3CMStatusEntry 20 }
+
+
+airIRG3CMStatusLocalDisplayOnOffEnabled OBJECT-TYPE
+ SYNTAX INTEGER {
+ no (1),
+ yes (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of the on/off control on the CM local display."
+ ::= { airIRG3CMStatusEntry 21 }
+
+
+airIRG3CMStatusAverageFanSpeed OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The CM Average Fan Speed."
+ ::= { airIRG3CMStatusEntry 22 }
+
+
+-- ***************************************
+-- airIRG3 CM Run Hours
+-- ***************************************
+
+AirIRG3CMRunHoursEntry ::= SEQUENCE {
+ airIRG3CMRunHoursDeviceIndex INTEGER,
+ airIRG3CMRunHoursCMID DisplayString,
+ airIRG3CMRunHoursFan1 INTEGER,
+ airIRG3CMRunHoursFan2 INTEGER,
+ airIRG3CMRunHoursFan3 INTEGER,
+ airIRG3CMRunHoursFan4 INTEGER,
+ airIRG3CMRunHoursFan5 INTEGER,
+ airIRG3CMRunHoursAirFilter INTEGER
+ }
+
+airIRG3CMRunHoursTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AirIRG3CMRunHoursEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows to access CM run hours table."
+ ::= { airIRG3CM 3 }
+
+airIRG3CMRunHoursEntry OBJECT-TYPE
+ SYNTAX AirIRG3CMRunHoursEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The CM run hours table entry."
+ INDEX { airIRG3CMRunHoursDeviceIndex}
+ ::= { airIRG3CMRunHoursTable 1 }
+
+airIRG3CMRunHoursDeviceIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index of CM run hours table."
+ ::= { airIRG3CMRunHoursEntry 1 }
+
+airIRG3CMRunHoursCMID OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The CM ID (RDU Number - Group Number - CM Unit Number)."
+ ::= { airIRG3CMRunHoursEntry 2 }
+
+airIRG3CMRunHoursFan1 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The CM run hours for Fan1.
+ Returns (-1) if not appilcable."
+ ::= { airIRG3CMRunHoursEntry 3 }
+
+airIRG3CMRunHoursFan2 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The CM run hours for Fan2.
+ Returns (-1) if not appilcable."
+ ::= { airIRG3CMRunHoursEntry 4 }
+
+airIRG3CMRunHoursFan3 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The CM run hours for Fan3.
+ Returns (-1) if not appilcable."
+ ::= { airIRG3CMRunHoursEntry 5 }
+
+airIRG3CMRunHoursFan4 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The CM run hours for Fan4.
+ Returns (-1) if not appilcable."
+ ::= { airIRG3CMRunHoursEntry 6 }
+
+airIRG3CMRunHoursFan5 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The CM run hours for Fan5.
+ Returns (-1) if not appilcable."
+ ::= { airIRG3CMRunHoursEntry 7 }
+
+airIRG3CMRunHoursAirFilter OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The CM run hours for air filter."
+ ::= { airIRG3CMRunHoursEntry 8 }
+
+
+
+-- ***************************************
+-- airIRG3 CM Service Intervals
+-- ***************************************
+
+AirIRG3CMServiceIntervalsEntry ::= SEQUENCE {
+ airIRG3CMServiceIntervalsDeviceIndex INTEGER,
+ airIRG3CMServiceIntervalsCMID DisplayString,
+ airIRG3CMServiceIntervalsAirFilterInterval INTEGER,
+ airIRG3CMServiceIntervalsAirFilterAlarm INTEGER
+ }
+
+airIRG3CMServiceIntervalsTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AirIRG3CMServiceIntervalsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows to access CM service intervals table."
+ ::= { airIRG3CM 4 }
+
+airIRG3CMServiceIntervalsEntry OBJECT-TYPE
+ SYNTAX AirIRG3CMServiceIntervalsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The CM service interval table entry."
+ INDEX { airIRG3CMServiceIntervalsDeviceIndex}
+ ::= { airIRG3CMServiceIntervalsTable 1 }
+
+airIRG3CMServiceIntervalsDeviceIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index of CM service intervals table."
+ ::= { airIRG3CMServiceIntervalsEntry 1 }
+
+airIRG3CMServiceIntervalsCMID OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The CM ID (RDU Number - Group Number - CM Unit Number)."
+ ::= { airIRG3CMServiceIntervalsEntry 2 }
+
+airIRG3CMServiceIntervalsAirFilterInterval OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The CM service interval for air filter in weeks.
+ Supported only for RA. Returns -1 if not supported."
+ ::= { airIRG3CMServiceIntervalsEntry 3 }
+
+airIRG3CMServiceIntervalsAirFilterAlarm OBJECT-TYPE
+ SYNTAX INTEGER{
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The CM service interval air filter alarm status.
+ Supported only for RA. Returns -1 if not supported."
+ ::= { airIRG3CMServiceIntervalsEntry 4 }
+
+
+-- ***************************************
+-- airIRG3 CM Thresholds
+-- ***************************************
+
+AirIRG3CMThresholdsEntry ::= SEQUENCE {
+ airIRG3CMThresholdsDeviceIndex INTEGER,
+ airIRG3CMThresholdsCMID DisplayString,
+ airIRG3CMThresholdsRackInletTempHighUS INTEGER,
+ airIRG3CMThresholdsRackInletTempHighMetric INTEGER,
+ airIRG3CMThresholdsSupplyAirTempHighUS INTEGER,
+ airIRG3CMThresholdsSupplyAirTempHighMetric INTEGER,
+ airIRG3CMThresholdsReturnAirTempHighUS INTEGER,
+ airIRG3CMThresholdsReturnAirTempHighMetric INTEGER
+ }
+
+airIRG3CMThresholdsTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AirIRG3CMThresholdsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows to access CM thresholds table."
+ ::= { airIRG3CM 5 }
+
+airIRG3CMThresholdsEntry OBJECT-TYPE
+ SYNTAX AirIRG3CMThresholdsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The CM thresholds table entry."
+ INDEX { airIRG3CMThresholdsDeviceIndex}
+ ::= { airIRG3CMThresholdsTable 1 }
+
+airIRG3CMThresholdsDeviceIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index for CM thresholds table."
+ ::= { airIRG3CMThresholdsEntry 1 }
+
+airIRG3CMThresholdsCMID OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The CM ID (RDU Number - Group Number - CM Unit Number)."
+ ::= { airIRG3CMThresholdsEntry 2 }
+
+airIRG3CMThresholdsRackInletTempHighUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The CM high threshold for rack inlet temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRG3CMThresholdsEntry 3 }
+
+
+airIRG3CMThresholdsRackInletTempHighMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The CM high threshold for rack inlet temperature in tenths of
+ degrees Celsius."
+ ::= { airIRG3CMThresholdsEntry 4 }
+
+
+airIRG3CMThresholdsSupplyAirTempHighUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The CM high threshold for supply air temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRG3CMThresholdsEntry 5 }
+
+
+airIRG3CMThresholdsSupplyAirTempHighMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The CM high threshold for supply air temperature in tenths of
+ degrees Celsius."
+ ::= { airIRG3CMThresholdsEntry 6 }
+
+
+airIRG3CMThresholdsReturnAirTempHighUS OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The CM high threshold for return air temperature in tenths of
+ degrees Fahrenheit."
+ ::= { airIRG3CMThresholdsEntry 7 }
+
+
+airIRG3CMThresholdsReturnAirTempHighMetric OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The CM high threshold for return air temperature in tenths of
+ degrees Celsius."
+ ::= { airIRG3CMThresholdsEntry 8 }
+
+
+-- ***************************************
+-- airIRG3 CM Setpoints
+-- ***************************************
+
+AirIRG3CMSetpointsEntry ::= SEQUENCE {
+ airIRG3CMSetpointsDeviceIndex INTEGER
+ }
+
+airIRG3CMSetpointsTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AirIRG3CMSetpointsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows to access CM set points table."
+ ::= { airIRG3CM 6 }
+
+airIRG3CMSetpointsEntry OBJECT-TYPE
+ SYNTAX AirIRG3CMSetpointsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The CM set points table entry."
+ INDEX { airIRG3CMSetpointsDeviceIndex}
+ ::= { airIRG3CMSetpointsTable 1 }
+
+airIRG3CMSetpointsDeviceIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index of CM set points table."
+ ::= { airIRG3CMSetpointsEntry 1 }
+
+
+
+-- ***************************************
+-- airIRG3 CM Config
+-- ***************************************
+
+AirIRG3CMConfigEntry ::= SEQUENCE {
+ airIRG3CMConfigDeviceIndex INTEGER,
+ airIRG3CMConfigCMID DisplayString,
+ airIRG3CMConfigStopOnCoolFail INTEGER,
+ airIRG3CMConfigStartupDelay INTEGER,
+ airIRG3CMConfigRemoteOnStandby INTEGER,
+ airIRG3CMConfigPowerSource INTEGER
+ }
+
+airIRG3CMConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AirIRG3CMConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows to access CM configuration table."
+ ::= { airIRG3CM 7 }
+
+airIRG3CMConfigEntry OBJECT-TYPE
+ SYNTAX AirIRG3CMConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The CM configuration table entry."
+ INDEX { airIRG3CMConfigDeviceIndex}
+ ::= { airIRG3CMConfigTable 1 }
+
+airIRG3CMConfigDeviceIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index of CM configuration table."
+ ::= { airIRG3CMConfigEntry 1 }
+
+airIRG3CMConfigCMID OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The CM ID (RDU Number - Group Number - CM Unit Number)."
+ ::= { airIRG3CMConfigEntry 2 }
+
+airIRG3CMConfigStopOnCoolFail OBJECT-TYPE
+ SYNTAX INTEGER{
+ no (1),
+ yes (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable/Disable Stop On cool fail. When enabled, stops the unit
+ if it detects that it is blowing warm air into the cold aisle."
+ ::= { airIRG3CMConfigEntry 3 }
+
+
+airIRG3CMConfigStartupDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The CM start up delay in seconds."
+ ::= { airIRG3CMConfigEntry 4 }
+
+
+airIRG3CMConfigRemoteOnStandby OBJECT-TYPE
+ SYNTAX INTEGER{
+ standBy (1),
+ on (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The CM configuration for operating mode."
+ ::= { airIRG3CMConfigEntry 5 }
+
+
+airIRG3CMConfigPowerSource OBJECT-TYPE
+ SYNTAX INTEGER{
+ singleFeed (1),
+ dualFeed (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The CM power source."
+ ::= { airIRG3CMConfigEntry 6 }
+
+
+-- End of airIRGen3
+
+
+-- RACK AIR REMOVAL UNIT IDENT
+
+rARUIdentTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RARUIdentEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for query of the individual devices.
+ The number of entries is contained in the
+ rARUStatusAruDeviceCount OID."
+ ::= { rARUIdent 1 }
+
+rARUIdentEntry OBJECT-TYPE
+ SYNTAX RARUIdentEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The device to query."
+ INDEX { rARUIdentAruIndex}
+ ::= { rARUIdentTable 1 }
+
+RARUIdentEntry ::=
+ SEQUENCE {
+ rARUIdentAruIndex INTEGER,
+ rARUIdentName DisplayString
+ }
+
+rARUIdentAruIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the ARU entry."
+ ::= { rARUIdentEntry 1 }
+
+rARUIdentName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the device. "
+ ::= { rARUIdentEntry 2 }
+
+-- RACK AIR REMOVAL UNIT CONFIGURATION
+
+rARUConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RARUConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for configuration of the individual ARU devices accessible from this IP address.
+ The number of entries is contained in the rARUStatusAruDeviceCount OID."
+ ::= { rARUConfig 1 }
+
+rARUConfigEntry OBJECT-TYPE
+ SYNTAX RARUConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The ARUs to configure."
+ INDEX { rARUConfigAruIndex }
+ ::= { rARUConfigTable 1 }
+
+RARUConfigEntry ::=
+ SEQUENCE {
+ rARUConfigAruIndex INTEGER,
+ rARUConfigAruName DisplayString,
+ rARUConfigAruRemoteSetpoint INTEGER,
+ rARUConfigAruTempOvrdEnableDisable INTEGER,
+ rARUConfigAruTempOvrdSetpoint INTEGER,
+ rARUConfigAruMasterControl INTEGER
+ }
+
+rARUConfigAruIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the ARU entry."
+ ::= { rARUConfigEntry 1 }
+
+rARUConfigAruName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the ARU."
+ ::= { rARUConfigEntry 2 }
+
+rARUConfigAruRemoteSetpoint OBJECT-TYPE
+ SYNTAX INTEGER {
+ aruOff (1),
+ aru85F-29C (2),
+ aru90F-32C (3),
+ aru95F-35C (4),
+ aru100F-38C (5),
+ aru7kW-1200cfm (6),
+ aru5kW-800cfm (7),
+ aru3kW-500cfm (8),
+ aru2kW-300cfm (9),
+ aru400cfm (10),
+ aru600cfm (11),
+ aru700cfm (12),
+ aru900cfm (13),
+ aru1000cfm (14),
+ aru1400cfm (15),
+ aru1600cfm (16),
+ aru1800cfm (17),
+ aru2000cfm (18)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "This OID defines the desired base airflow of the ARU, and sets the
+ speed of the ARU fans when the temperature override is inactive.
+
+ Values specified in cfm (cubic feet per minute) can be converted
+ to metric values using the conversion factor:
+
+ 1 cfm = 1.70 m^3/hr (cubic meters per hour).
+
+ Values (1) through (9) are for support of legacy (1st generation) ARUs.
+ Writing these values to a 2nd generation ARU will result in the following:
+ A value greater than (9) will be ignored by a 1st generation ARU.
+
+ aruOff (1) - Ignored
+ aru85F-29C (2) - 1200 cfm
+ aru90F-32C (3) - 800 cfm
+ aru95F-35C (4) - 500 cfm
+ aru100F-38C (5) - 400 cfm
+ aru7kW (6) - 1200 cfm
+ aru5kW (7) - 800 cfm
+ aru3kW (8) - 500 cfm
+ aru2kW (9) - 400 cfm
+
+ NOTE: -1 will be returned if the ARU is not communicating."
+ ::= { rARUConfigEntry 3 }
+
+rARUConfigAruTempOvrdEnableDisable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(1),
+ enabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "This OID is used to enable/disable the remote temperature override setting of the ARU.
+
+ If this OID is set to 1, the remote setting for temperature override is disabled.
+ If this OID is set to 2, the remote setting for temperature override is enabled."
+ ::= { rARUConfigEntry 4 }
+
+rARUConfigAruTempOvrdSetpoint OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "This OID is the Temperature Override setpoint of the ARU.
+
+ NOTE: -1 will be returned if the ARU is not communicating.
+
+ Values are represented in whole number degrees using the
+ units specified in the rARUStatusSysTempUnits OID (Celsius or Fahrenheit)."
+ ::= { rARUConfigEntry 5 }
+
+rARUConfigAruMasterControl OBJECT-TYPE
+ SYNTAX INTEGER {
+ aruOn (1),
+ aruOff (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "This is the master on/off control for the ARU."
+ ::= { rARUConfigEntry 6 }
+
+-- RACK AIR REMOVAL UNIT STATUS
+
+rARUStatusAruDeviceCount OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The total number of ARUs accessible from this IP."
+ ::= { rARUStatus 1 }
+
+rARUStatusSysTempUnits OBJECT-TYPE
+ SYNTAX INTEGER {
+ celsius(1),
+ fahrenheit(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature scale used to display the temperature
+ in the system, Celsius(1) or Fahrenheit(2).
+ This setting is based on the system preferences
+ configuration in the agent."
+ ::= { rARUStatus 2 }
+
+rARUStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RARUStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for query of the individual ARUs accessible from this IP address.
+ The number of entries is contained in the rARUStatusAruDeviceCount OID."
+ ::= { rARUStatus 3 }
+
+rARUStatusEntry OBJECT-TYPE
+ SYNTAX RARUStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The ARUs to access."
+ INDEX { rARUStatusAruIndex }
+ ::= { rARUStatusTable 1 }
+
+RARUStatusEntry ::=
+ SEQUENCE {
+ rARUStatusAruIndex INTEGER,
+ rARUStatusAruName DisplayString,
+ rARUStatusAruRemoteSetpoint INTEGER,
+ rARUStatusAruManualSetpoint INTEGER,
+ rARUStatusAruTemp1 INTEGER,
+ rARUStatusAruTemp2 INTEGER,
+ rARUStatusAruTemp3 INTEGER,
+ rARUStatusAruTempOvrdEnableDisable INTEGER,
+ rARUStatusAruTempOvrdSetpoint INTEGER,
+ rARUStatusAruAlarmState DisplayString,
+ rARUStatusAruCommStatus INTEGER,
+ rARUStatusAruTempOvrdStatus INTEGER,
+ rARUStatusAruMasterControl INTEGER,
+ rARUStatusAruTotalAirflow INTEGER
+ }
+
+rARUStatusAruIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the ARU entry."
+ ::= { rARUStatusEntry 1 }
+
+rARUStatusAruName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the ARU."
+ ::= { rARUStatusEntry 2 }
+
+rARUStatusAruRemoteSetpoint OBJECT-TYPE
+ SYNTAX INTEGER {
+ aruOff (1),
+ aru85F-29C (2),
+ aru90F-32C (3),
+ aru95F-35C (4),
+ aru100F-38C (5),
+ aru7kW-1200cfm (6),
+ aru5kW-800cfm (7),
+ aru3kW-500cfm (8),
+ aru2kW-300cfm (9),
+ aru400cfm (10),
+ aru600cfm (11),
+ aru700cfm (12),
+ aru900cfm (13),
+ aru1000cfm (14),
+ aru1400cfm (15),
+ aru1600cfm (16),
+ aru1800cfm (17),
+ aru2000cfm (18)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID defines the desired base airflow of the ARU, or the
+ speed of the ARU fans when the temperature override is inactive.
+
+ See also the rARUConfigAruRemoteSetpoint OID.
+
+ NOTE: -1 will be returned if the ARU is not communicating."
+ ::= { rARUStatusEntry 3 }
+
+rARUStatusAruManualSetpoint OBJECT-TYPE
+ SYNTAX INTEGER {
+ aruOff (1),
+ aru85F-29C (2),
+ aru90F-32C (3),
+ aru95F-35C (4),
+ aru100F-38C (5),
+ aru7kW (6),
+ aru5kW (7),
+ aru3kW (8),
+ aru2kW (9),
+ aruRem (10)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Manual operating setpoint of the ARU, which is set on the
+ panel of the ARU. If the ARU doesn't have a manual ,
+ the OID will always return a value of aruRem (10).
+
+ NOTE: -1 will be returned if the ARU is not communicating.
+
+ Values are represented in whole number degrees or kW.
+ If the manual setpoint is set to Remote, or if the ARU doesn't
+ have a manual switch, this OID will return aruRem."
+ ::= { rARUStatusEntry 4 }
+
+rARUStatusAruTemp1 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "ARU temperature probe #1 reading.
+ The summary exhaust temperature on 2nd generation ARUs.
+
+ NOTE: -1 will be returned if the ARU is not communicating.
+
+ Values are represented in whole number degrees.
+ Units are displayed in the scale shown in
+ the rARUStatusSysTempUnits OID (Celsius or Fahrenheit)."
+ ::= { rARUStatusEntry 5 }
+
+rARUStatusAruTemp2 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "ARU temperature probe #2 reading.
+ The exhaust temperature in the upper plenum on 2nd generation ARUs.
+
+ NOTE: -1 will be returned if the ARU is not communicating.
+
+ Values are represented in whole number degrees.
+ Units are displayed in the scale shown in
+ the rARUStatusSysTempUnits OID (Celsius or Fahrenheit)."
+ ::= { rARUStatusEntry 6 }
+
+rARUStatusAruTemp3 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "ARU temperature probe #3 reading.
+ The exhaust temperature in the lower plenum on 2nd generation ARUs.
+
+ NOTE: -1 will be returned if the ARU is not communicating.
+
+ Values are represented in whole number degrees.
+ Units are displayed in the scale shown in
+ the rARUStatusSysTempUnits OID (Celsius or Fahrenheit)."
+ ::= { rARUStatusEntry 7 }
+
+rARUStatusAruTempOvrdEnableDisable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(1),
+ enabled(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This OID indicates whether the ARU remote temperature override is enabled or disabled.
+ If this OID is a 1, the remote setting for temperature override is disabled.
+ If this OID is a 2, the remote setting for temperature override is enabled."
+ ::= { rARUStatusEntry 8 }
+
+rARUStatusAruTempOvrdSetpoint OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "ARU remote temperature override setpoint setting.
+
+ NOTE: -1 will be returned if the ARU is not communicating.
+
+ Values are represented in whole number degrees.
+ Units are displayed in the scale shown in
+ the rARUStatusSysTempUnits OID (Celsius or Fahrenheit)."
+ ::= { rARUStatusEntry 9 }
+
+rARUStatusAruAlarmState OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An ASCII string containing the 8 flags representing
+ the current alarm state of the ARU. If the state of
+ the ARU is unknown, this variable is set to 'UNKNOWN'.
+
+ The flags are numbered 1 to 8, read from left to
+ right. The flags are defined as follows:
+
+ Flag 1: Fan Fail 1
+ Flag 2: Fan Fail 2
+ Flag 3: Fan Fail 3
+ Flag 4: Smoke (if ARU is equipped with smoke detector)
+
+ Flag 5: High Temp (Out of Thermal Control)
+ Flag 6: Over Temp (Exhaust Temp. Exceeds Override Setpoint)
+ Flag 7: Fan Fail 4 (Gen 2 ARU only)
+ Flag 8: Reserved"
+ ::= { rARUStatusEntry 10 }
+
+rARUStatusAruCommStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ commsNeverDiscovered(1),
+ commsEstablished(2),
+ commsLost(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The state of communications to the device.
+ commNeverDiscovered(1) indicates there has never been communications with this device.
+ commsEstablished(2) indicates communication is normal and active with this device.
+ commsLost(3) indicates communication had been established, but is no device."
+ ::= { rARUStatusEntry 11 }
+
+rARUStatusAruTempOvrdStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ inactive (1),
+ active (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Specifies whether the ARU is increasing airflow because
+ exhaust air temperature has exceeded the setting specified in the
+ rARUConfigAruTempOvrdSetpoint OID."
+ ::= { rARUStatusEntry 12 }
+
+rARUStatusAruMasterControl OBJECT-TYPE
+ SYNTAX INTEGER {
+ aruOn (1),
+ aruOff (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This is the master on/off control for the ARU."
+ ::= { rARUStatusEntry 13 }
+
+rARUStatusAruTotalAirflow OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The total airflow provided by the aru. Specified in cfm (cubic feet per minute).
+ Can be converted to metric values using the conversion factor:
+ 1 cfm = 1.70 m^3/hr (cubic meters per hour)."
+ ::= { rARUStatusEntry 14 }
+
+-- RACK AIR REMOVAL UNIT FAN STATUS
+
+rARUFanStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RARUFanStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for query of the individual devices.
+ The number of entries is contained in the
+ rARUStatusAruDeviceCount OID."
+ ::= { rARUFanStatus 1 }
+
+rARUFanStatusEntry OBJECT-TYPE
+ SYNTAX RARUFanStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The device to query."
+ INDEX { rARUFanStatusAruIndex, rARUFanStatusFanIndex}
+ ::= { rARUFanStatusTable 1 }
+
+RARUFanStatusEntry ::=
+ SEQUENCE {
+ rARUFanStatusAruIndex INTEGER,
+ rARUFanStatusNominalFanSpeed INTEGER,
+ rARUFanStatusSelectedFanLevel INTEGER,
+ rARUFanStatusReplacementThreshold INTEGER,
+ rARUFanStatusFanIndex INTEGER,
+ rARUFanStatusFanOperatingStatus INTEGER,
+ rARUFanStatusFanRpmSpeed INTEGER,
+ rARUFanStatusFanFlowRate INTEGER,
+ rARUFanStatusFanInServiceDate DisplayString,
+ rARUFanStatusFanRunhourCounter INTEGER,
+ rARUFanStatusFanRunhourReset INTEGER
+ }
+
+rARUFanStatusAruIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the ARU entry."
+ ::= { rARUFanStatusEntry 1 }
+
+rARUFanStatusNominalFanSpeed OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The nominal rotational speed (RPM) of the fans when they are
+ operating at the 100% level."
+ ::= { rARUFanStatusEntry 2 }
+
+rARUFanStatusSelectedFanLevel OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The currently selected ARU speed level,
+ specified in percent of full capacity."
+ ::= { rARUFanStatusEntry 3 }
+
+rARUFanStatusReplacementThreshold OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled (1),
+ khr20 (2),
+ khr25 (3),
+ khr30 (4),
+ khr35 (5),
+ khr40 (6),
+ khr50 (7)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Threshold above which a run hour alarm will exist, indicating
+ that it might be time to proactively replace a fan."
+ ::= { rARUFanStatusEntry 4 }
+
+rARUFanStatusFanIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to an individual fan table entry."
+ ::= { rARUFanStatusEntry 5 }
+
+rARUFanStatusFanOperatingStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown (1),
+ off (2),
+ onOk (3),
+ onDegraded (4),
+ offFailed (5)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current operating state of the fan."
+ ::= { rARUFanStatusEntry 6 }
+
+rARUFanStatusFanRpmSpeed OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current rotational speed of the fan,
+ specified in rotations per minute (RPM)."
+ ::= { rARUFanStatusEntry 7 }
+
+rARUFanStatusFanFlowRate OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The flow rate provided by the fan, based on its measured rotational speed.
+ Specified in cfm (cubic feet per minute). Can be converted to metric values
+ using the conversion factor: 1 cfm = 1.70 m^3/hr (cubic meters per hour)."
+ ::= { rARUFanStatusEntry 8 }
+
+rARUFanStatusFanInServiceDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The installation/replacement date of the fan."
+ ::= { rARUFanStatusEntry 9 }
+
+rARUFanStatusFanRunhourCounter OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The total time for which the fan has been running.
+ Specified in 10ths of hours."
+ ::= { rARUFanStatusEntry 10 }
+
+rARUFanStatusFanRunhourReset OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Writing yes to this This OID will reset a fan's total run hour counter,
+ which is shown in the rARUFanStatusFanRunhourCounter OID."
+ ::= { rARUFanStatusEntry 11 }
+
+-- RACK AIR REMOVAL UNIT INPUT POWER STATUS
+
+rARUPowerStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RARUPowerStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for query of the individual ARUs accessible from this IP address.
+ The number of entries is contained in the rARUStatusAruDeviceCount OID."
+ ::= { rARUPower 1 }
+
+rARUPowerStatusEntry OBJECT-TYPE
+ SYNTAX RARUPowerStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The device to query."
+ INDEX { rARUPowerStatusAruIndex}
+ ::= { rARUPowerStatusTable 1 }
+
+RARUPowerStatusEntry ::=
+ SEQUENCE {
+ rARUPowerStatusAruIndex INTEGER,
+ rARUPowerStatusPrimaryAcPresent INTEGER,
+ rARUPowerStatusAuxiliaryAcPresent INTEGER,
+ rARUPowerStatusRedundantAcConfig INTEGER
+ }
+
+rARUPowerStatusAruIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the ARU entry."
+ ::= { rARUPowerStatusEntry 1 }
+
+rARUPowerStatusPrimaryAcPresent OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates whether or not line voltage is present on AC input 1."
+ ::= { rARUPowerStatusEntry 2 }
+
+rARUPowerStatusAuxiliaryAcPresent OBJECT-TYPE
+ SYNTAX INTEGER {
+ yes (1),
+ no (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates whether or not line voltage is present on AC input 2."
+ ::= { rARUPowerStatusEntry 3 }
+
+rARUPowerStatusRedundantAcConfig OBJECT-TYPE
+ SYNTAX INTEGER {
+ singleCord (1),
+ dualCord (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates whether or not a dual cord is in use.
+ When this setting is set to dualCord (2), aruRedundantPowerLostAlarm
+ traps will be generated when either primary or auxiliary input
+ voltage is not present. When this setting is set to singleCord (1),
+ aruRedundantPowerLostAlarm traps will not be generated."
+ ::= { rARUPowerStatusEntry 4 }
+
+-- RACK AIR REMOVAL UNIT SENSOR STATUS
+
+rARUSensorsStatusTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the rARUSensorsStatusTable."
+ ::= { rARUSensors 1 }
+
+rARUSensorsStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RARUSensorsStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting environmental sensor status information."
+ ::= { rARUSensors 2 }
+
+rARUSensorsStatusEntry OBJECT-TYPE
+ SYNTAX RARUSensorsStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The unit to get data from."
+ INDEX { rARUSensorsStatusAruIndex, rARUSensorsStatusSensorNumber }
+ ::= { rARUSensorsStatusTable 1 }
+
+RARUSensorsStatusEntry ::=
+ SEQUENCE {
+ rARUSensorsStatusAruIndex INTEGER,
+ rARUSensorsStatusSensorNumber INTEGER,
+ rARUSensorsTemperature INTEGER
+ }
+
+rARUSensorsStatusAruIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the ARU entry."
+ ::= { rARUSensorsStatusEntry 1 }
+
+rARUSensorsStatusSensorNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of the sensor on the device."
+ ::= { rARUSensorsStatusEntry 2 }
+
+rARUSensorsTemperature OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The sensor's current temperature reading. The temperature scale
+ is based on the system preferences configuration."
+ ::= { rARUSensorsStatusEntry 3 }
+
+
+-- RACK AIR REMOVAL UNIT CONFIG STATUS
+
+rARUSensorsConfigTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the rARUSensorsConfigTable."
+ ::= { rARUSensors 3 }
+
+rARUSensorsConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF RARUSensorsConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting configuration information from
+ environmental sensors attached to the device."
+ ::= { rARUSensors 4 }
+
+rARUSensorsConfigEntry OBJECT-TYPE
+ SYNTAX RARUSensorsConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The unit to get data from."
+ INDEX { rARUSensorsConfigAruIndex, rARUSensorsConfigSensorNumber }
+ ::= { rARUSensorsConfigTable 1 }
+
+RARUSensorsConfigEntry ::=
+ SEQUENCE {
+ rARUSensorsConfigAruIndex INTEGER,
+ rARUSensorsConfigSensorNumber INTEGER,
+ rARUSensorsName DisplayString,
+ rARUSensorsLocation DisplayString,
+ rARUSensorsTempMaxThresh INTEGER,
+ rARUSensorsTempHighThresh INTEGER,
+ rARUSensorsTempLowThresh INTEGER,
+ rARUSensorsTempMinThresh INTEGER,
+ rARUSensorsTempThreshHysteresis INTEGER,
+ rARUSensorsTempShortDecRateThreshValue INTEGER,
+ rARUSensorsTempShortDecRateThreshTime INTEGER,
+ rARUSensorsTempShortIncRateThreshValue INTEGER,
+ rARUSensorsTempShortIncRateThreshTime INTEGER,
+ rARUSensorsTempLongDecRateThreshValue INTEGER,
+ rARUSensorsTempLongDecRateThreshTime INTEGER,
+ rARUSensorsTempLongIncRateThreshValue INTEGER,
+ rARUSensorsTempLongIncRateThreshTime INTEGER
+ }
+
+rARUSensorsConfigAruIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to the ARU entry."
+ ::= { rARUSensorsConfigEntry 1 }
+
+rARUSensorsConfigSensorNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of the sensor on the device."
+ ::= { rARUSensorsConfigEntry 2 }
+
+rARUSensorsName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A descriptive name for the sensor."
+ ::= { rARUSensorsConfigEntry 3 }
+
+rARUSensorsLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The location of the sensor."
+ ::= { rARUSensorsConfigEntry 4 }
+
+rARUSensorsTempMaxThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature at which a maximum temperature threshold
+ violation alarm will be generated for this sensor.
+ The temperature scale is based on the system preferences
+ configuration."
+ ::= { rARUSensorsConfigEntry 5 }
+
+rARUSensorsTempHighThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature at which a high temperature threshold
+ violation alarm will be generated for this sensor.
+ The temperature scale is based on the system preferences
+ configuration."
+ ::= { rARUSensorsConfigEntry 6 }
+
+rARUSensorsTempLowThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature at which a low temperature threshold
+ violation alarm will be generated for this sensor.
+ The temperature scale is based on the system preferences
+ configuration."
+ ::= { rARUSensorsConfigEntry 7 }
+
+rARUSensorsTempMinThresh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature at which a min temperature threshold
+ violation alarm will be generated for this sensor.
+ The temperature scale is based on the system preferences
+ configuration."
+ ::= { rARUSensorsConfigEntry 8 }
+
+rARUSensorsTempThreshHysteresis OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The change in temperature required to cause a
+ temperature alarm to change from an active to an
+ inactive state. The temperature scale is based on
+ the system preferences configuration."
+ ::= { rARUSensorsConfigEntry 9 }
+
+rARUSensorsTempShortDecRateThreshValue OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The value of the temperature short-term decreasing rate
+ time that will cause an alarm to be generated.
+ The temperature scale is based on the system preferences
+ configuration."
+ ::= { rARUSensorsConfigEntry 10 }
+
+rARUSensorsTempShortDecRateThreshTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The time over which the temperature may not decrease
+ beyond the value specified by the temperature short-term
+ decreasing rate threshold value."
+ ::= { rARUSensorsConfigEntry 11 }
+
+rARUSensorsTempShortIncRateThreshValue OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The value of the temperature short-term increasing rate
+ time that will cause an alarm to be generated.
+ The temperature scale is based on the system preferences
+ configuration."
+ ::= { rARUSensorsConfigEntry 12 }
+
+rARUSensorsTempShortIncRateThreshTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The time over which the temperature may not increase
+ beyond the value specified by the temperature short-term
+ increasing rate threshold value."
+ ::= { rARUSensorsConfigEntry 13 }
+
+rARUSensorsTempLongDecRateThreshValue OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The value of the temperature long-term decreasing rate
+ time that will cause an alarm to be generated.
+ The temperature scale is based on the system preferences
+ configuration."
+ ::= { rARUSensorsConfigEntry 14 }
+
+rARUSensorsTempLongDecRateThreshTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The time over which the temperature may not decrease
+ beyond the value specified by the temperature long-term
+ decreasing rate threshold value."
+ ::= { rARUSensorsConfigEntry 15 }
+
+rARUSensorsTempLongIncRateThreshValue OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The value of the temperature long-term increasing rate
+ time that will cause an alarm to be generated.
+ The temperature scale is based on the system preferences
+ configuration."
+ ::= { rARUSensorsConfigEntry 16 }
+
+rARUSensorsTempLongIncRateThreshTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The time over which the temperature may not increase
+ beyond the value specified by the temperature long-term
+ increasing rate threshold value."
+ ::= { rARUSensorsConfigEntry 17 }
+
+-- MODULAR DISTRIBUTION SYSTEM
+
+-- Modular Information
+
+isxModularDistInfoTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the isxModularDistInfoTable."
+ ::= { isxModularDistInfo 1 }
+
+isxModularDistInfoTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF IsxModularDistInfoEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting information about the modular
+ distribution metering equipment."
+ ::= { isxModularDistInfo 2 }
+
+isxModularDistInfoEntry OBJECT-TYPE
+ SYNTAX IsxModularDistInfoEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information about an individual metering segment."
+ INDEX { isxModularDistInfoSegmentIndex }
+ ::= { isxModularDistInfoTable 1 }
+
+IsxModularDistInfoEntry ::=
+ SEQUENCE {
+ isxModularDistInfoSegmentIndex INTEGER,
+ isxModularDistInfoMeterModelNumber DisplayString,
+ isxModularDistInfoMeterSerialNumber DisplayString,
+ isxModularDistInfoMeterDateOfManufacture DisplayString,
+ isxModularDistInfoMeterFirmwareRev DisplayString,
+ isxModularDistInfoMeterHardwareRev DisplayString
+ }
+
+isxModularDistInfoSegmentIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of the metering segment."
+ ::= { isxModularDistInfoEntry 1 }
+
+isxModularDistInfoMeterModelNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The model number of the metering board for this segment."
+ ::= { isxModularDistInfoEntry 2 }
+
+isxModularDistInfoMeterSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The serial number of the metering board for this segment."
+ ::= { isxModularDistInfoEntry 3 }
+
+isxModularDistInfoMeterDateOfManufacture OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The date of manufacture for the metering board for this segment,
+ in the format mm/dd/yyyy."
+ ::= { isxModularDistInfoEntry 4 }
+
+isxModularDistInfoMeterFirmwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The firmware revision number of the metering board for this segment."
+ ::= { isxModularDistInfoEntry 5 }
+
+isxModularDistInfoMeterHardwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The hardware revision number of the metering board for this segment."
+ ::= { isxModularDistInfoEntry 6 }
+
+-- Distribution Modules
+
+isxModularDistModuleInfoTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the isxModularDistModuleInfoTable."
+ ::= { isxModularDistModules 1 }
+
+isxModularDistModuleInfoTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF IsxModularDistModuleInfoEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting basic information about the distribution modules
+ installed in the system."
+ ::= { isxModularDistModules 2 }
+
+isxModularDistModuleInfoEntry OBJECT-TYPE
+ SYNTAX IsxModularDistModuleInfoEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information about a specific distribution module."
+ INDEX { isxModularDistModuleInfoModIndex }
+ ::= { isxModularDistModuleInfoTable 1 }
+
+IsxModularDistModuleInfoEntry ::=
+ SEQUENCE {
+ isxModularDistModuleInfoModIndex INTEGER,
+ isxModularDistModuleInfoAlarmStatus INTEGER,
+ isxModularDistModuleInfoModelNumber DisplayString,
+ isxModularDistModuleInfoSerialNumber DisplayString,
+ isxModularDistModuleInfoDateOfManufacture DisplayString,
+ isxModularDistModuleInfoNumCables INTEGER
+ }
+
+isxModularDistModuleInfoModIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of the distribution module."
+ ::= { isxModularDistModuleInfoEntry 1 }
+
+isxModularDistModuleInfoAlarmStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ warning (2),
+ critical (3),
+ notPresent (4),
+ unknown (5)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The status of this module. This reflects the indicator lamp(s) on the front of the module.
+ A value of notPresent indicates that the module is not installed.
+ A value of unknown indicates that there is no communication with the
+ metering segment for this module."
+ ::= { isxModularDistModuleInfoEntry 2 }
+
+isxModularDistModuleInfoModelNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The model number of the distribution module."
+ ::= { isxModularDistModuleInfoEntry 3 }
+
+isxModularDistModuleInfoSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The serial number of the distribution module."
+ ::= { isxModularDistModuleInfoEntry 4 }
+
+isxModularDistModuleInfoDateOfManufacture OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The date that the distribution module was manufactured."
+ ::= { isxModularDistModuleInfoEntry 5 }
+
+isxModularDistModuleInfoNumCables OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of cables provided by this distribution module."
+ ::= { isxModularDistModuleInfoEntry 6 }
+
+isxModularDistModuleBreakerTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the isxModularDistModuleBreakerTable."
+ ::= { isxModularDistModules 3 }
+
+isxModularDistModuleBreakerTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF IsxModularDistModuleBreakerEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting operational information about the distribution modules."
+ ::= { isxModularDistModules 4 }
+
+isxModularDistModuleBreakerEntry OBJECT-TYPE
+ SYNTAX IsxModularDistModuleBreakerEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information about a specific distribution modules and circuit breakers."
+ INDEX { isxModularDistModuleBreakerModIndex, isxModularDistModuleBreakerPhaseIndex}
+ ::= { isxModularDistModuleBreakerTable 1 }
+
+IsxModularDistModuleBreakerEntry ::=
+ SEQUENCE {
+ isxModularDistModuleBreakerModIndex INTEGER,
+ isxModularDistModuleBreakerPhaseIndex INTEGER,
+ isxModularDistModuleBreakerAlarmStatus INTEGER,
+ isxModularDistModuleBreakerRating INTEGER,
+ isxModularDistModuleBreakerPhysicalGroup INTEGER,
+ isxModularDistModuleBreakerCableNum INTEGER,
+ isxModularDistModuleBreakerPosition INTEGER,
+ isxModularDistModuleBreakerPositionAlarms INTEGER,
+ isxModularDistModuleBreakerCurrent INTEGER,
+ isxModularDistModuleBreakerPercent INTEGER,
+ isxModularDistModuleBreakerPower INTEGER
+ }
+
+isxModularDistModuleBreakerModIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The distribution module number."
+ ::= { isxModularDistModuleBreakerEntry 1 }
+
+isxModularDistModuleBreakerPhaseIndex OBJECT-TYPE
+ SYNTAX INTEGER{
+ phaseL1(1),
+ phaseL2(2),
+ phaseL3(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to an individual breaker in the distribution module. The index also corresponds
+ to the system phase to which the breaker is attached."
+ ::= { isxModularDistModuleBreakerEntry 2 }
+
+isxModularDistModuleBreakerAlarmStatus OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This is a bit map representing the active alarms for this breaker:
+
+ b0 - Minimum current threshold exceeded (critical)
+ b1 - Low current threshold exceeded (warning)
+ b2 - High current threshold exceeded (warning)
+ b3 - Maximum current threshold exceeded (critical)
+ b4 - Breaker is open (critical)
+
+ If a bit is set, the corresponding alarm is active."
+ ::= { isxModularDistModuleBreakerEntry 3 }
+
+isxModularDistModuleBreakerRating OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current rating of the breaker."
+ ::= { isxModularDistModuleBreakerEntry 4 }
+
+isxModularDistModuleBreakerPhysicalGroup OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Numeric value used to indicate that a breaker is a part of a multi-pole breaker.
+ Breakers within a distribution module, with equivalent physical group numbers,
+ may have their handles physically tied together.
+ A value of 1 indicates breakers that are physically tied together as part of a
+ multi-pole breaker.
+ A value of 0 indicates a single-handle breaker that is not physically tied to
+ another breaker."
+ ::= { isxModularDistModuleBreakerEntry 5 }
+
+isxModularDistModuleBreakerCableNum OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Numeric value used to indicate the distribution cable to which
+ this breaker is connected. These distribution cables are described
+ in the table isxModularDistModuleOutputTable,
+ and indexed by the OID isxModularDistModuleOutputCordIndex."
+ ::= { isxModularDistModuleBreakerEntry 6 }
+
+isxModularDistModuleBreakerPosition OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The physical status of this breaker pole, either closed or open (including tripped)."
+ ::= { isxModularDistModuleBreakerEntry 7 }
+
+isxModularDistModuleBreakerPositionAlarms OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled (1),
+ enabled (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable breaker position alarms for this circuit breaker."
+ ::= { isxModularDistModuleBreakerEntry 8 }
+
+isxModularDistModuleBreakerCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current flowing though this breaker. Measured in tenths of amps."
+ ::= { isxModularDistModuleBreakerEntry 9 }
+
+isxModularDistModuleBreakerPercent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The loading on this breaker as a percentage of the breaker's current rating.
+ Expressed in tenths of percent."
+ ::= { isxModularDistModuleBreakerEntry 10 }
+
+isxModularDistModuleBreakerPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The power being supplied through this breaker. Measured in tenths of kW."
+ ::= { isxModularDistModuleBreakerEntry 11 }
+
+isxModularDistModuleOutputsTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the isxModularDistModuleOutputTable."
+ ::= { isxModularDistModules 5 }
+
+isxModularDistModuleOutputTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF IsxModularDistModuleOutputEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting and setting information related to the
+ load equipment being fed by the distribution modules in the ISX
+ Modular Distribution System."
+ ::= { isxModularDistModules 6 }
+
+isxModularDistModuleOutputEntry OBJECT-TYPE
+ SYNTAX IsxModularDistModuleOutputEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information about a specific distribution module
+ and its output distribution cables."
+ INDEX { isxModularDistModuleOutputModIndex, isxModularDistModuleOutputCordIndex }
+ ::= { isxModularDistModuleOutputTable 1 }
+
+IsxModularDistModuleOutputEntry ::=
+ SEQUENCE {
+ isxModularDistModuleOutputModIndex INTEGER,
+ isxModularDistModuleOutputNumCables INTEGER,
+ isxModularDistModuleOutputCordIndex INTEGER,
+ isxModularDistModuleOutputName DisplayString,
+ isxModularDistModuleOutputLocation DisplayString,
+ isxModularDistModuleOutputStatus INTEGER,
+ isxModularDistModuleOutputAlarmGeneration INTEGER,
+ isxModularDistModuleOutputBreakerMap INTEGER,
+ isxModularDistModuleOutputThresholdMin INTEGER,
+ isxModularDistModuleOutputThresholdLow INTEGER,
+ isxModularDistModuleOutputThresholdHigh INTEGER,
+ isxModularDistModuleOutputThresholdMax INTEGER,
+ isxModularDistModuleOutputAlarmMinEnable INTEGER,
+ isxModularDistModuleOutputAlarmLowEnable INTEGER,
+ isxModularDistModuleOutputAlarmHighEnable INTEGER,
+ isxModularDistModuleOutputAlarmMaxEnable INTEGER,
+ isxModularDistModuleOutputCableLength INTEGER,
+ isxModularDistModuleOutputConnectorType DisplayString,
+ isxModularDistModuleOutputAvailableVoltages INTEGER,
+ isxModularDistModuleOutputTotalPower INTEGER,
+ isxModularDistModuleOutputKwhUsage INTEGER,
+ isxModularDistModuleOutputKwhReset INTEGER,
+ isxModularDistModuleOutputKwhResetDate DisplayString
+ }
+
+isxModularDistModuleOutputModIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of the distribution module supplying power to the load equipment."
+ ::= { isxModularDistModuleOutputEntry 1 }
+
+isxModularDistModuleOutputNumCables OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of distribution cables provided by this module."
+ ::= { isxModularDistModuleOutputEntry 2 }
+
+isxModularDistModuleOutputCordIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of an individual distribution cable supplied by this module."
+ ::= { isxModularDistModuleOutputEntry 3 }
+
+isxModularDistModuleOutputName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A string describing the load equipment being supplied by this distribution cable."
+ ::= { isxModularDistModuleOutputEntry 4 }
+
+isxModularDistModuleOutputLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A string describing the location of equipment being supplied by distribution cable."
+ ::= { isxModularDistModuleOutputEntry 5 }
+
+isxModularDistModuleOutputStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ warning (2),
+ critical (3),
+ notPresent (4),
+ unknown (6)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This reflects the worse case severity for alarms associated with this distribution cable.
+ A value of notPresent indicates that the cable does not exist for this module.
+ A value of unknown indicates that the there is no communication with the
+ metering segment for this distribution cable's module."
+ ::= { isxModularDistModuleOutputEntry 6 }
+
+isxModularDistModuleOutputAlarmGeneration OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled (1),
+ enabled (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable all alarm generation related to this distribution cable."
+ ::= { isxModularDistModuleOutputEntry 7 }
+
+isxModularDistModuleOutputBreakerMap OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This is a bit map representing the breaker poles within the
+ module that are associated with this distribution cable.
+ The following 3 bits are used to indicate the indices of
+ the breakers feeding the cable:
+
+ b0 - Module breaker L1
+ b1 - Module breaker L2
+ b2 - Module breaker L3
+
+ If a bit is set, the breaker is used to feed this distribution cable.
+ These breakers are described in the table isxModularDistModuleBreakerTable,
+ and indexed by the OID isxModularDistModuleBreakerPhaseIndex."
+ ::= { isxModularDistModuleOutputEntry 8 }
+
+isxModularDistModuleOutputThresholdMin OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "When the current drops below this value a critical alarm will exist."
+ ::= { isxModularDistModuleOutputEntry 9 }
+
+isxModularDistModuleOutputThresholdLow OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "When the current drops below this value a warning alarm will exist."
+ ::= { isxModularDistModuleOutputEntry 10 }
+
+isxModularDistModuleOutputThresholdHigh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "When the current exceeds this value a warning alarm will exist."
+ ::= { isxModularDistModuleOutputEntry 11 }
+
+isxModularDistModuleOutputThresholdMax OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "When the current exceeds this value a critical alarm will exist."
+ ::= { isxModularDistModuleOutputEntry 12 }
+
+isxModularDistModuleOutputAlarmMinEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled (1),
+ enabled (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable minimum current alarm generation for this distribution cable."
+ ::= { isxModularDistModuleOutputEntry 13 }
+
+isxModularDistModuleOutputAlarmLowEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled (1),
+ enabled (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable low current alarm generation for this distribution cable."
+ ::= { isxModularDistModuleOutputEntry 14 }
+
+isxModularDistModuleOutputAlarmHighEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled (1),
+ enabled (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable high current alarm generation for this distribution cable."
+ ::= { isxModularDistModuleOutputEntry 15 }
+
+isxModularDistModuleOutputAlarmMaxEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled (1),
+ enabled (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable maximum current alarm generation for this distribution cable."
+ ::= { isxModularDistModuleOutputEntry 16 }
+
+isxModularDistModuleOutputCableLength OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The length of this distribution cable. Specified in tenths of meters."
+ ::= { isxModularDistModuleOutputEntry 17 }
+
+isxModularDistModuleOutputConnectorType OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A string describing the connector on the end of this distribution cable."
+ ::= { isxModularDistModuleOutputEntry 18 }
+
+isxModularDistModuleOutputAvailableVoltages OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This is a bit map representing the voltages that are available at the connector.
+ 6 bits are used to indicate the following:
+
+ b0 - L1
+ b1 - L2
+ b2 - L3
+ b3 - L1-2
+ b4 - L2-3
+ b5 - L3-1"
+ ::= { isxModularDistModuleOutputEntry 19 }
+
+isxModularDistModuleOutputTotalPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The total power being consumed by the load equipment supplied by this distribution cable.
+ Measured in tenths of kW."
+ ::= { isxModularDistModuleOutputEntry 20 }
+
+isxModularDistModuleOutputKwhUsage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The total energy consumed by the load equipment fed by this distribution cable.
+ This is the total since the date specified in the isxModularDistModuleOutputKwhResetDate
+ OID, and may be cleared using the isxModularDistModuleOutputKwhReset OID.
+ Measured in tenths of kWh."
+ ::= { isxModularDistModuleOutputEntry 21 }
+
+isxModularDistModuleOutputKwhReset OBJECT-TYPE
+ SYNTAX INTEGER {
+ no (1),
+ yes (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Writing yes to this OID will reset the total kWh usage shown
+ in the isxModularDistModuleOutputKwhUsage OID."
+ ::= { isxModularDistModuleOutputEntry 22 }
+
+isxModularDistModuleOutputKwhResetDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The date that the kWh usage was reset, in the format mm/dd/yyyy. Example: 01/01/2000."
+ ::= { isxModularDistModuleOutputEntry 23 }
+
+-- Distribution Subfeeds
+
+isxModularDistSubFeedInfoTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the isxModularDistSubFeedInfoTable."
+ ::= { isxModularDistSubFeeds 1 }
+
+isxModularDistSubFeedInfoTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF IsxModularDistSubFeedInfoEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting information about distribution subfeed breakers."
+ ::= { isxModularDistSubFeeds 2 }
+
+isxModularDistSubFeedInfoEntry OBJECT-TYPE
+ SYNTAX IsxModularDistSubFeedInfoEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information about a specific distribution subfeed."
+ INDEX { isxModularDistSubFeedInfoSubIndex }
+ ::= { isxModularDistSubFeedInfoTable 1 }
+
+IsxModularDistSubFeedInfoEntry ::=
+ SEQUENCE {
+ isxModularDistSubFeedInfoSubIndex INTEGER,
+ isxModularDistSubFeedInfoName DisplayString,
+ isxModularDistSubFeedInfoLocation DisplayString,
+ isxModularDistSubFeedInfoBreakerRating INTEGER,
+ isxModularDistSubFeedInfoBreakerPosition INTEGER,
+ isxModularDistSubFeedInfoAlarmStatus INTEGER,
+ isxModularDistSubFeedInfoAlarmGeneration INTEGER,
+ isxModularDistSubFeedInfoThresholdMin INTEGER,
+ isxModularDistSubFeedInfoThresholdLow INTEGER,
+ isxModularDistSubFeedInfoThresholdHigh INTEGER,
+ isxModularDistSubFeedInfoThresholdMax INTEGER,
+ isxModularDistSubFeedInfoAlarmMinEnable INTEGER,
+ isxModularDistSubFeedInfoAlarmLowEnable INTEGER,
+ isxModularDistSubFeedInfoAlarmHighEnable INTEGER,
+ isxModularDistSubFeedInfoAlarmMaxEnable INTEGER,
+ isxModularDistSubFeedInfoBreakerAlarmEnable INTEGER,
+ isxModularDistSubFeedInfoTotalPower INTEGER,
+ isxModularDistSubFeedInfoKwhUsage INTEGER,
+ isxModularDistSubFeedInfoKwhReset INTEGER,
+ isxModularDistSubFeedInfoKwhResetDate DisplayString
+ }
+
+isxModularDistSubFeedInfoSubIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of an individual subfeed."
+ ::= { isxModularDistSubFeedInfoEntry 1 }
+
+isxModularDistSubFeedInfoName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A string describing the load equipment being supplied by this subfeed."
+ ::= { isxModularDistSubFeedInfoEntry 2 }
+
+isxModularDistSubFeedInfoLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A string describing the location of the equipment being supplied by this subfeed."
+ ::= { isxModularDistSubFeedInfoEntry 3 }
+
+isxModularDistSubFeedInfoBreakerRating OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current rating of this subfeed breaker."
+ ::= { isxModularDistSubFeedInfoEntry 4 }
+
+isxModularDistSubFeedInfoBreakerPosition OBJECT-TYPE
+ SYNTAX INTEGER {
+ open (1),
+ closed (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The operational status of this breaker, either closed or open (including tripped)."
+ ::= { isxModularDistSubFeedInfoEntry 5 }
+
+isxModularDistSubFeedInfoAlarmStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ warning (2),
+ critical (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The worst case alarm status for this subfeed."
+ ::= { isxModularDistSubFeedInfoEntry 6 }
+
+isxModularDistSubFeedInfoAlarmGeneration OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled (1),
+ enabled (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable all alarm generation related to this subfeed."
+ ::= { isxModularDistSubFeedInfoEntry 7 }
+
+isxModularDistSubFeedInfoThresholdMin OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "When the current drops below this value a critical alarm will exist."
+ ::= { isxModularDistSubFeedInfoEntry 8 }
+
+isxModularDistSubFeedInfoThresholdLow OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "When the current drops below this value a warning alarm will exist."
+ ::= { isxModularDistSubFeedInfoEntry 9 }
+
+isxModularDistSubFeedInfoThresholdHigh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "When the current exceeds this value a warning alarm will exist."
+ ::= { isxModularDistSubFeedInfoEntry 10 }
+
+isxModularDistSubFeedInfoThresholdMax OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "When the current exceeds this value a critical alarm will exist."
+ ::= { isxModularDistSubFeedInfoEntry 11 }
+
+isxModularDistSubFeedInfoAlarmMinEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled (1),
+ enabled (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable minimum current alarm generation for this subfeed."
+ ::= { isxModularDistSubFeedInfoEntry 12 }
+
+isxModularDistSubFeedInfoAlarmLowEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled (1),
+ enabled (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable low current alarm generation for this subfeed."
+ ::= { isxModularDistSubFeedInfoEntry 13 }
+
+isxModularDistSubFeedInfoAlarmHighEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled (1),
+ enabled (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable high current alarm generation for this subfeed."
+ ::= { isxModularDistSubFeedInfoEntry 14 }
+
+isxModularDistSubFeedInfoAlarmMaxEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled (1),
+ enabled (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable maximum current alarm generation for this subfeed."
+ ::= { isxModularDistSubFeedInfoEntry 15 }
+
+isxModularDistSubFeedInfoBreakerAlarmEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled (1),
+ enabled (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable breaker position alarms for this subfeed."
+ ::= { isxModularDistSubFeedInfoEntry 16 }
+
+isxModularDistSubFeedInfoTotalPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The total power being supplied by this subfeed. Measured in tenths of kW."
+ ::= { isxModularDistSubFeedInfoEntry 17 }
+
+isxModularDistSubFeedInfoKwhUsage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The total energy consumed by the load equipment fed by this subfeed.
+ This is the total since the date specified in the isxModularDistSubFeedInfoKwhResetDate
+ OID, and may be cleared using the isxModularDistSubFeedInfoKwhReset OID.
+ Measured in tenths of kWh."
+ ::= { isxModularDistSubFeedInfoEntry 18 }
+
+isxModularDistSubFeedInfoKwhReset OBJECT-TYPE
+ SYNTAX INTEGER {
+ no (1),
+ yes (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Writing yes to this OID will reset the total kWh usage shown
+ in the isxModularDistSubFeedInfoKwhUsage OID."
+ ::= { isxModularDistSubFeedInfoEntry 19 }
+
+isxModularDistSubFeedInfoKwhResetDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The date that the kWh usage was reset, in the format mm/dd/yyyy. Example: 01/01/2000."
+ ::= { isxModularDistSubFeedInfoEntry 20 }
+
+isxModularDistSubFeedLoadingTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the isxModularDistSubFeedLoadingTable."
+ ::= { isxModularDistSubFeeds 3 }
+
+isxModularDistSubFeedLoadingTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF IsxModularDistSubFeedLoadingEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting subfeed phase loading information."
+ ::= { isxModularDistSubFeeds 4 }
+
+isxModularDistSubFeedLoadingEntry OBJECT-TYPE
+ SYNTAX IsxModularDistSubFeedLoadingEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing data for an individual subfeed."
+ INDEX { isxModularDistSubFeedLoadingSubIndex, isxModularDistSubFeedLoadingPhaseIndex }
+ ::= { isxModularDistSubFeedLoadingTable 1 }
+
+IsxModularDistSubFeedLoadingEntry ::= SEQUENCE {
+ isxModularDistSubFeedLoadingSubIndex INTEGER,
+ isxModularDistSubFeedLoadingPhaseIndex INTEGER,
+ isxModularDistSubFeedLoadingAlarmStatus INTEGER,
+ isxModularDistSubFeedLoadingCurrent INTEGER,
+ isxModularDistSubFeedLoadingPercent INTEGER,
+ isxModularDistSubFeedLoadingPower INTEGER
+ }
+
+isxModularDistSubFeedLoadingSubIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index of an individual subfeed."
+ ::= { isxModularDistSubFeedLoadingEntry 1 }
+
+isxModularDistSubFeedLoadingPhaseIndex OBJECT-TYPE
+ SYNTAX INTEGER{
+ phase1(1),
+ phase2(2),
+ phase3(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Description of each input phase entry in the table."
+ ::= { isxModularDistSubFeedLoadingEntry 2 }
+
+isxModularDistSubFeedLoadingAlarmStatus OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This is a bit map representing the active alarms for this subfeed:
+
+ b0 - Minimum current threshold exceeded (critical)
+ b1 - Low current threshold exceeded (warning)
+ b2 - High current threshold exceeded (warning)
+ b3 - Maximum current threshold exceeded (critical)
+ b4 - Breaker is open (critical)
+
+ If a bit is set, the corresponding alarm is active."
+ ::= { isxModularDistSubFeedLoadingEntry 3 }
+
+isxModularDistSubFeedLoadingCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current flowing though this subfeed phase. Measured in tenths of amps."
+ ::= { isxModularDistSubFeedLoadingEntry 4 }
+
+isxModularDistSubFeedLoadingPercent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The loading on this subfeed phase as a percentage of the subfeed's current rating.
+ Expressed in tenths of percent."
+ ::= { isxModularDistSubFeedLoadingEntry 5 }
+
+isxModularDistSubFeedLoadingPower OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The power being supplied by this subfeed phase. Measured in tenths of kW."
+ ::= { isxModularDistSubFeedLoadingEntry 6 }
+
+-- Distribution System Output Voltage
+
+isxModularDistSysOutputVoltageNominalLineToNeutral OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The nominal line-to-neutral voltage available at the distribution panel."
+ ::= { isxModularDistSysVoltage 1 }
+
+isxModularDistSysOutputVoltageNominalLineToLine OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The nominal line-to-line voltage available at the distribution panel."
+ ::= { isxModularDistSysVoltage 2 }
+
+isxModularDistSysOutputNominalFrequency OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The nominal system output frequency. Measured in tenths of Hertz."
+ ::= { isxModularDistSysVoltage 3 }
+
+isxModularDistSysOutputFrequency OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The system output frequency in tenths of Hertz.
+ -1 if not available."
+ ::= { isxModularDistSysVoltage 4 }
+
+isxModularDistSysOutputVoltageMonitoring OBJECT-TYPE
+ SYNTAX INTEGER {
+ notPresent (1),
+ present (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates whether or not output voltage alarm generation is present."
+ ::= { isxModularDistSysVoltage 5 }
+
+isxModularDistSysOutputVoltageThresholdMin OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "When the line-to-neutral voltage of any phase drops below this value a critical alarm will exist.
+ Specified as a percent of the nominal voltage, isxModularDistSysOutputVoltageNominalLineToNeutral.
+ This value is returned as a positive number which represents a negative percentage.
+ A value of -1 indicates that the threshold is not available in the device."
+ ::= { isxModularDistSysVoltage 6 }
+
+isxModularDistSysOutputVoltageThresholdLow OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "When the line-to-neutral voltage of any phase drops below this value a warning alarm will exist.
+ Specified as a percent of the nominal voltage, isxModularDistSysOutputVoltageNominalLineToNeutral.
+ This value is returned as a positive number which represents a negative percentage.
+ A value of -1 indicates that the threshold is not available in the device."
+ ::= { isxModularDistSysVoltage 7 }
+
+isxModularDistSysOutputVoltageThresholdHigh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "When the line-to-neutral voltage of any phase exceeds this value a warning alarm will exist.
+ Specified as a percent of the nominal voltage, isxModularDistSysOutputVoltageNominalLineToNeutral.
+ A value of -1 indicates that the threshold is not available in the device."
+ ::= { isxModularDistSysVoltage 8 }
+
+isxModularDistSysOutputVoltageThresholdMax OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "When the line-to-neutral voltage of any phase exceeds this value a critical alarm will exist.
+ Specified as a percent of the nominal voltage, isxModularDistSysOutputVoltageNominalLineToNeutral.
+ A value of -1 indicates that the threshold is not available in the device."
+ ::= { isxModularDistSysVoltage 9 }
+
+isxModularDistSysOutputVoltageAlarmMinEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled (1),
+ enabled (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable minimum voltage alarm generation for the distribution panel."
+ ::= { isxModularDistSysVoltage 10 }
+
+isxModularDistSysOutputVoltageAlarmLowEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled (1),
+ enabled (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable low voltage alarm generation for the distribution panel."
+ ::= { isxModularDistSysVoltage 11 }
+
+isxModularDistSysOutputVoltageAlarmHighEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled (1),
+ enabled (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable high voltage alarm generation for the distribution panel."
+ ::= { isxModularDistSysVoltage 12 }
+
+isxModularDistSysOutputVoltageAlarmMaxEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled (1),
+ enabled (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable maximum voltage alarm generation for the distribution panel."
+ ::= { isxModularDistSysVoltage 13 }
+
+isxModularDistSysOutputVoltageFrequencyTolerance OBJECT-TYPE
+ SYNTAX INTEGER{
+ freqToleranceOff (1),
+ freqTolerancePointTwo (2),
+ freqTolerancePointFive (3),
+ freqToleranceOne (4),
+ freqToleranceOnePointFive (5),
+ freqToleranceTwo (6),
+ freqToleranceThree (7),
+ freqToleranceFour (8),
+ freqToleranceFive (9),
+ freqToleranceNine (10),
+ freqToleranceNotAvailable (11)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The circuit panel output frequency tolerance in Hertz.
+ When the system output frequency deviates from the nominal by more than this range,
+ a critical alarm will be generated."
+ ::= { isxModularDistSysVoltage 14 }
+
+isxModularDistSysVoltageTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF IsxModularDistSysVoltageEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting the system output voltage information."
+ ::= { isxModularDistSysVoltage 15 }
+
+isxModularDistSysVoltageEntry OBJECT-TYPE
+ SYNTAX IsxModularDistSysVoltageEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing data for an individual system output phase."
+ INDEX { isxModularDistSysVoltagePhaseIndex }
+ ::= { isxModularDistSysVoltageTable 1 }
+
+IsxModularDistSysVoltageEntry ::=
+ SEQUENCE {
+ isxModularDistSysVoltagePhaseIndex INTEGER,
+ isxModularDistSysVoltageAlarmStatus INTEGER,
+ isxModularDistSysVoltageLtoN INTEGER,
+ isxModularDistSysVoltageLtoL INTEGER
+ }
+
+isxModularDistSysVoltagePhaseIndex OBJECT-TYPE
+ SYNTAX INTEGER{
+ phase1(1),
+ phase2(2),
+ phase3(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Description of each phase entry in the table."
+ ::= { isxModularDistSysVoltageEntry 1 }
+
+isxModularDistSysVoltageAlarmStatus OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This is a bit map representing the active alarms for this output phase:
+
+ b0 - Minimum voltage threshold exceeded (critical)
+ b1 - Low voltage threshold exceeded (warning)
+ b2 - High voltage threshold exceeded (warning)
+ b3 - Maximum voltage threshold exceeded (critical)
+
+ If a bit is set, the corresponding alarm is active."
+ ::= { isxModularDistSysVoltageEntry 2 }
+
+isxModularDistSysVoltageLtoN OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Line-to-neutral system output voltage available at the distribution panel.
+ Measured in tenths of Volts."
+ ::= { isxModularDistSysVoltageEntry 3 }
+
+isxModularDistSysVoltageLtoL OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Line-to-line system output voltage available at the distribution panel.
+ Measured in tenths of Volts."
+ ::= { isxModularDistSysVoltageEntry 4 }
+
+
+-- Distribution System Total Output Current
+
+isxModularDistSysCurrentRating OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The 100 percent current rating of the distribution panel."
+ ::= { isxModularDistSysCurrent 1 }
+
+isxModularDistSysCurrentMonitoring OBJECT-TYPE
+ SYNTAX INTEGER {
+ notPresent (1),
+ present (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates whether or not total output current measurements and alarm generation are present."
+ ::= { isxModularDistSysCurrent 2 }
+
+isxModularDistSysCurrentThresholdMin OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "When total system current in any phase drops below this value a critical alarm will exist.
+ Specified as a percent of the panel rating, isxModularDistSysCurrentRating.
+ A value of -1 indicates that the threshold is not available in the device."
+ ::= { isxModularDistSysCurrent 3 }
+
+isxModularDistSysCurrentThresholdLow OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "When total system current in any phase drops below this value a warning alarm will exist.
+ Specified as a percent of the panel rating, isxModularDistSysCurrentRating.
+ A value of -1 indicates that the threshold is not available in the device."
+ ::= { isxModularDistSysCurrent 4 }
+
+isxModularDistSysCurrentThresholdHigh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "When total system current in any phase exceeds this value a warning alarm will exist.
+ Specified as a percent of the panel rating, isxModularDistSysCurrentRating.
+ A value of -1 indicates that the threshold is not available in the device."
+ ::= { isxModularDistSysCurrent 5 }
+
+isxModularDistSysCurrentThresholdMax OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "When total system current in any phase exceeds this value a critical alarm will exist.
+ Specified as a percent of the panel rating, isxModularDistSysCurrentRating.
+ A value of -1 indicates that the threshold is not available in the device."
+ ::= { isxModularDistSysCurrent 6 }
+
+isxModularDistSysCurrentAlarmMinEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled (1),
+ enabled (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable minimum total output current alarm generation."
+ ::= { isxModularDistSysCurrent 7 }
+
+isxModularDistSysCurrentAlarmLowEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled (1),
+ enabled (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable low total output current alarm generation."
+ ::= { isxModularDistSysCurrent 8 }
+
+isxModularDistSysCurrentAlarmHighEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled (1),
+ enabled (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable high total output current alarm generation."
+ ::= { isxModularDistSysCurrent 9 }
+
+isxModularDistSysCurrentAlarmMaxEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled (1),
+ enabled (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable maximum total output current alarm generation."
+ ::= { isxModularDistSysCurrent 10 }
+
+isxModularDistSysCurrentTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF IsxModularDistSysCurrentEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting the total system phase current information."
+ ::= { isxModularDistSysCurrent 11 }
+
+isxModularDistSysCurrentEntry OBJECT-TYPE
+ SYNTAX IsxModularDistSysCurrentEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing data for an individual system output phase."
+ INDEX { isxModularDistSysCurrentPhaseIndex }
+ ::= { isxModularDistSysCurrentTable 1 }
+
+IsxModularDistSysCurrentEntry ::=
+ SEQUENCE {
+ isxModularDistSysCurrentPhaseIndex INTEGER,
+ isxModularDistSysCurrentAlarmStatus INTEGER,
+ isxModularDistSysCurrentAmps INTEGER,
+ isxModularDistSysCurrentPercent INTEGER
+ }
+
+isxModularDistSysCurrentPhaseIndex OBJECT-TYPE
+ SYNTAX INTEGER{
+ phase1(1),
+ phase2(2),
+ phase3(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Description of each phase entry in the table."
+ ::= { isxModularDistSysCurrentEntry 1 }
+
+isxModularDistSysCurrentAlarmStatus OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "This is a bit map representing the active alarms for this output phase:
+
+ b0 - Minimum current threshold exceeded (critical)
+ b1 - Low current threshold exceeded (warning)
+ b2 - High current threshold exceeded (warning)
+ b3 - Maximum current threshold exceeded (critical)
+
+ If a bit is set, the corresponding alarm is active."
+ ::= { isxModularDistSysCurrentEntry 2 }
+
+isxModularDistSysCurrentAmps OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current flowing though this system output phase. Measured in tenths of amps."
+ ::= { isxModularDistSysCurrentEntry 3 }
+
+isxModularDistSysCurrentPercent OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The loading on this system output phase as a percentage of the panel current rating.
+ Expressed in tenths of percent."
+ ::= { isxModularDistSysCurrentEntry 4 }
+
+-- Distribution System Total Output Power
+
+isxModularDistSysPowerTotal OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The total system power being supplied. Measured in tenths of kW."
+ ::= { isxModularDistSysPower 1 }
+
+isxModularDistSysPowerKwhUsage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The total system energy consumed by the load equipment.
+ This is the total since the date specified in the isxModularDistSysOutputKwhResetDate
+ OID, and may be cleared using the isxModularDistSysOutputKwhReset OID.
+ Measured in tenths of kWh."
+ ::= { isxModularDistSysPower 2 }
+
+isxModularDistSysPowerKwhReset OBJECT-TYPE
+ SYNTAX INTEGER {
+ no (1),
+ yes (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Writing yes to this OID will reset the total kWh usage shown
+ in the isxModularDistSysPowerKwhUsage OID."
+ ::= { isxModularDistSysPower 3 }
+
+isxModularDistSysPowerKwhResetDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The date that the kWh usage was reset, in the format mm/dd/yyyy. Example: 01/01/2000."
+ ::= { isxModularDistSysPower 4 }
+
+isxModularDistSysPowerTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF IsxModularDistSysPowerEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting the total system phase power loading information."
+ ::= { isxModularDistSysPower 5 }
+
+isxModularDistSysPowerEntry OBJECT-TYPE
+ SYNTAX IsxModularDistSysPowerEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing data for an individual system output phase."
+ INDEX { isxModularDistSysPowerPhaseIndex }
+ ::= { isxModularDistSysPowerTable 1 }
+
+IsxModularDistSysPowerEntry ::=
+ SEQUENCE {
+ isxModularDistSysPowerPhaseIndex INTEGER,
+ isxModularDistSysPowerKw INTEGER,
+ isxModularDistSysPowerKwhPhaseUsage INTEGER
+ }
+
+isxModularDistSysPowerPhaseIndex OBJECT-TYPE
+ SYNTAX INTEGER{
+ phase1(1),
+ phase2(2),
+ phase3(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Description of each phase entry in the table."
+ ::= { isxModularDistSysPowerEntry 1 }
+
+isxModularDistSysPowerKw OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The power being supplied by this system output phase. Measured in tenths of kW."
+ ::= { isxModularDistSysPowerEntry 2 }
+
+isxModularDistSysPowerKwhPhaseUsage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The energy consumed by the load equipment on this system output phase.
+ This is the total since the date specified in the isxModularDistSysPowerKwhResetDate
+ OID, and may be cleared using the isxModularDistSysPowerKwhReset OID.
+ Measured in tenths of kWh."
+ ::= { isxModularDistSysPowerEntry 3 }
+
+-- the isxModularPduIdent group
+
+isxModularPduIdentModelNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the model number of the PDU.
+ This value is set at the factory."
+ ::= { isxModularPduIdent 1 }
+
+isxModularPduIdentSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the serial number of the PDU.
+ This value is set at the factory."
+ ::= { isxModularPduIdent 2 }
+
+isxModularPduIdentDateOfManufacture OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The date when the PDU was manufactured in mm/dd/yyyy format.
+ This value is set at the factory."
+ ::= { isxModularPduIdent 3 }
+
+isxModularPduIdentMonitorCardSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A character string identifying the serial number of the PDU monitor card.
+ This value is set at the factory."
+ ::= { isxModularPduIdent 4 }
+
+isxModularPduIdentMonitorCardHardwareRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The hardware revision of the PDU monitor card.
+ This value is set at the factory."
+ ::= { isxModularPduIdent 5 }
+
+isxModularPduIdentMonitorCardFirmwareAppRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An ID string identifying the application firmware revision of the
+ PDU monitor card."
+ ::= { isxModularPduIdent 6 }
+
+isxModularPduIdentMonitorCardFirmwareAppOSRev OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An ID string identifying the application operating system firmware revision of the
+ PDU monitor card."
+ ::= { isxModularPduIdent 7 }
+
+-- the isxModularPduDevice group
+
+isxModularPduDeviceTransformerPresent OBJECT-TYPE
+ SYNTAX INTEGER {
+ notPresent (1),
+ isoXfmrPresent (2),
+ autoXfmrPresent (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates the type of transformer present in this PDU."
+ ::= { isxModularPduDevice 1 }
+
+isxModularPduDeviceServiceType OBJECT-TYPE
+ SYNTAX INTEGER {
+ threeWire (1),
+ fourWire (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The type of utility input to the PDU. Either 3 wires (delta), or 4 wires (wye)."
+ ::= { isxModularPduDevice 2 }
+
+isxModularPduDeviceFansPresent OBJECT-TYPE
+ SYNTAX INTEGER {
+ notPresent (1),
+ present (2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates whether or not cooling fans are installed in the PDU."
+ ::= { isxModularPduDevice 3 }
+
+isxModularPduDeviceNominalMainInputVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The nominal main input voltage to the system. Measured in Volts,
+ line-to-line for a 3-wire (delta) service or line-to-neutral for a
+ 4-wire (wye) service. -1 if main input voltage is not being measured."
+ ::= { isxModularPduDevice 4 }
+
+isxModularPduAlarmStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ warning (2),
+ critical (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The overall status (worst case) of this PDU."
+ ::= { isxModularPduStatus 1 }
+
+isxModularPduTransformerTempStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ overtemp (2),
+ noTransformerPresent (3),
+ unknown (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates if the PDU isolation transformer is over temperature."
+ ::= { isxModularPduStatus 2 }
+
+isxModularPduFanStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal (1),
+ failed (2),
+ noCoolingFansPresent (3),
+ unknown (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates if one or more of the PDU's cooling fans have failed."
+ ::= { isxModularPduStatus 3 }
+
+
+-- Universal Input / Output (uio)
+
+-- uio Sensor Status Table
+
+uioSensorStatusTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the uioSensorStatusTable."
+ ::= { uioSensor 1 }
+
+uioSensorStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UIOSensorStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting sensor status information."
+ ::= { uioSensor 2 }
+
+uioSensorStatusEntry OBJECT-TYPE
+ SYNTAX UIOSensorStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The unit from which to get data."
+ INDEX { uioSensorStatusPortID, uioSensorStatusSensorID }
+ ::= { uioSensorStatusTable 1 }
+
+UIOSensorStatusEntry ::=
+ SEQUENCE {
+ uioSensorStatusPortID INTEGER,
+ uioSensorStatusSensorID INTEGER,
+ uioSensorStatusSensorName DisplayString,
+ uioSensorStatusSensorLocation DisplayString,
+ uioSensorStatusTemperatureDegF INTEGER,
+ uioSensorStatusTemperatureDegC INTEGER,
+ uioSensorStatusHumidity INTEGER,
+ uioSensorStatusViolationStatus INTEGER,
+ uioSensorStatusAlarmStatus INTEGER,
+ uioSensorStatusCommStatus INTEGER
+ }
+
+uioSensorStatusPortID OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The ID of the port to which the sensor is attached."
+ ::= { uioSensorStatusEntry 1 }
+
+uioSensorStatusSensorID OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The ID of the sensor."
+ ::= { uioSensorStatusEntry 2 }
+
+uioSensorStatusSensorName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The sensor name."
+ ::= { uioSensorStatusEntry 3 }
+
+uioSensorStatusSensorLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The location of the sensor."
+ ::= { uioSensorStatusEntry 4 }
+
+uioSensorStatusTemperatureDegF OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The sensor's current temperature reading in degrees Fahrenheit.
+ -1 indicates an invalid reading due to lost communications."
+ ::= { uioSensorStatusEntry 5 }
+
+uioSensorStatusTemperatureDegC OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The sensor's current temperature reading in degrees Celsius.
+ -1 indicates an invalid reading due to lost communications."
+ ::= { uioSensorStatusEntry 6 }
+
+uioSensorStatusHumidity OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The sensor's current humidity reading in percent relative
+ humidity. -1 indicates an invalid reading due to either a
+ sensor that doesn't read humidity or lost communications."
+ ::= { uioSensorStatusEntry 7 }
+
+uioSensorStatusViolationStatus OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The violation status of the sensor. This integer should be interpreted
+ as a bit map, with each bit representing the presence or absence of
+ the specific alarm conditions listed below. The bit will be '1' if
+ the condition is present, and '0' if the condition is not present.
+
+ Bit Hex. Value Description
+ 1 0x0001 Maximum temperature exceeded.
+ 2 0x0002 High temperature exceeded.
+ 3 0x0004 Low temperature exceeded.
+ 4 0x0008 Minimum temperature exceeded.
+ 5 0x0010 Short-term increasing temperature rate exceeded (Not used).
+ 6 0x0020 Short-term decreasing temperature rate exceeded (Not used).
+ 7 0x0040 Long-term increasing temperature rate exceeded (Not used).
+ 8 0x0080 Long-term decreasing temperature rate exceeded (Not used).
+ 9 0x0100 Maximum humidity exceeded.
+ 10 0x0200 High humidity exceeded.
+ 11 0x0400 Low humidity exceeded.
+ 12 0x0800 Minimum humidity exceeded."
+ ::= { uioSensorStatusEntry 8 }
+
+uioSensorStatusAlarmStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ uioNormal (1),
+ uioWarning (2),
+ uioCritical (3),
+ sensorStatusNotApplicable (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The alarm status of the sensor."
+ ::= { uioSensorStatusEntry 9 }
+
+uioSensorStatusCommStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ notInstalled (1),
+ commsOK (2),
+ commsLost (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The communications status of the sensor."
+ ::= { uioSensorStatusEntry 10 }
+
+
+-- uio Sensor Config Table
+
+uioSensorConfigTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the uioSensorConfigTable."
+ ::= { uioSensor 3 }
+
+uioSensorConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UIOSensorConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for configuring the sensor."
+ ::= { uioSensor 4 }
+
+uioSensorConfigEntry OBJECT-TYPE
+ SYNTAX UIOSensorConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The sensor from which to get configuration."
+ INDEX { uioSensorConfigPortID, uioSensorConfigSensorID }
+ ::= { uioSensorConfigTable 1 }
+
+UIOSensorConfigEntry ::=
+ SEQUENCE {
+ uioSensorConfigPortID INTEGER,
+ uioSensorConfigSensorID INTEGER,
+ uioSensorConfigSensorName DisplayString,
+ uioSensorConfigSensorLocation DisplayString,
+ uioSensorConfigMinTemperatureThreshold INTEGER,
+ uioSensorConfigLowTemperatureThreshold INTEGER,
+ uioSensorConfigHighTemperatureThreshold INTEGER,
+ uioSensorConfigMaxTemperatureThreshold INTEGER,
+ uioSensorConfigTemperatureHysteresis INTEGER,
+ uioSensorConfigMinTemperatureEnable INTEGER,
+ uioSensorConfigLowTemperatureEnable INTEGER,
+ uioSensorConfigHighTemperatureEnable INTEGER,
+ uioSensorConfigMaxTemperatureEnable INTEGER,
+ uioSensorConfigMinHumidityThreshold INTEGER,
+ uioSensorConfigLowHumidityThreshold INTEGER,
+ uioSensorConfigHighHumidityThreshold INTEGER,
+ uioSensorConfigMaxHumidityThreshold INTEGER,
+ uioSensorConfigHumidityHysteresis INTEGER,
+ uioSensorConfigMinHumidityEnable INTEGER,
+ uioSensorConfigLowHumidityEnable INTEGER,
+ uioSensorConfigHighHumidityEnable INTEGER,
+ uioSensorConfigMaxHumidityEnable INTEGER
+ }
+
+uioSensorConfigPortID OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The ID of the port to which the sensor is attached."
+ ::= { uioSensorConfigEntry 1 }
+
+uioSensorConfigSensorID OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The ID of the sensor."
+ ::= { uioSensorConfigEntry 2 }
+
+uioSensorConfigSensorName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The sensor name."
+ ::= { uioSensorConfigEntry 3 }
+
+uioSensorConfigSensorLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The location of the sensor."
+ ::= { uioSensorConfigEntry 4 }
+
+uioSensorConfigMinTemperatureThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum (critical) temperature alarm threshold for the
+ probe in degrees C. Must be lower than the low threshold to
+ ensure proper sensor alarm behavior."
+ ::= { uioSensorConfigEntry 5 }
+
+uioSensorConfigLowTemperatureThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The low (warning) temperature alarm threshold for the probe
+ in degrees C. Must be higher than the minimum threshold and
+ lower than the high threshold to ensure proper sensor alarm
+ behavior."
+ ::= { uioSensorConfigEntry 6 }
+
+uioSensorConfigHighTemperatureThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The high (warning) temperature alarm threshold for the probe
+ in degrees C. Must be lower than the maximum threshold and
+ higher than the low threshold to ensure proper sensor alarm
+ behavior."
+ ::= { uioSensorConfigEntry 7 }
+
+uioSensorConfigMaxTemperatureThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum (critical) temperature alarm threshold for the
+ probe in degrees C. Must be higher than the high threshold
+ to ensure proper sensor alarm behavior."
+ ::= { uioSensorConfigEntry 8 }
+
+uioSensorConfigTemperatureHysteresis OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The number of degrees C beyond the temperature thresholds at
+ which an active temperature alarm will be cleared. This value
+ applies to all temperature thresholds."
+ ::= { uioSensorConfigEntry 9 }
+
+uioSensorConfigMinTemperatureEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(1),
+ enabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum temperature alarm enable/disable for the sensor.
+ 1 - disabled
+ 2 - enabled"
+ ::= { uioSensorConfigEntry 10 }
+
+uioSensorConfigLowTemperatureEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(1),
+ enabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The low temperature alarm enable/disable for the sensor.
+ 1 - disabled
+ 2 - enabled"
+ ::= { uioSensorConfigEntry 11 }
+
+uioSensorConfigHighTemperatureEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(1),
+ enabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The high temperature alarm enable/disable for the sensor.
+ 1 - disabled
+ 2 - enabled"
+ ::= { uioSensorConfigEntry 12 }
+
+uioSensorConfigMaxTemperatureEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(1),
+ enabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum temperature alarm enable/disable for the sensor.
+ 1 - disabled
+ 2 - enabled"
+ ::= { uioSensorConfigEntry 13 }
+
+uioSensorConfigMinHumidityThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum (critical) humidity alarm threshold for the
+ probe in percent relative humidity. Must be lower than the
+ low threshold to ensure proper sensor alarm behavior. -1 if
+ the sensor doesn't read humidity."
+ ::= { uioSensorConfigEntry 14 }
+
+uioSensorConfigLowHumidityThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The low (warning) humidity alarm threshold for the probe in
+ percent relative humidity. Must be higher than the minimum
+ threshold and lower than the high threshold to ensure proper
+ sensor alarm behavior. -1 if the sensor doesn't read
+ humidity."
+ ::= { uioSensorConfigEntry 15 }
+
+uioSensorConfigHighHumidityThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The high (warning) humidity alarm threshold for the probe in
+ percent relative humidity. Must be lower than the maximum
+ threshold and higher than the low threshold to ensure proper
+ sensor alarm behavior. -1 if the sensor doesn't read
+ humidity."
+ ::= { uioSensorConfigEntry 16 }
+
+uioSensorConfigMaxHumidityThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum (critical) humidity alarm threshold for the
+ probe in percent relative humidity. Must be higher than the
+ high threshold to ensure proper sensor alarm behavior. -1 if
+ the sensor doesn't read humidity."
+ ::= { uioSensorConfigEntry 17 }
+
+uioSensorConfigHumidityHysteresis OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The number of percent relative humidity beyond the humidity
+ thresholds at which an active humidity alarm will be cleared.
+ This value applies to all humidity thresholds. -1 if the
+ sensor doesn't read humidity."
+ ::= { uioSensorConfigEntry 18 }
+
+uioSensorConfigMinHumidityEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(1),
+ enabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum humidity alarm enable/disable for the sensor.
+ 1 - disabled (always set if the sensor doesn't read humidity)
+ 2 - enabled"
+ ::= { uioSensorConfigEntry 19 }
+
+uioSensorConfigLowHumidityEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(1),
+ enabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The low humidity alarm enable/disable for the sensor.
+ 1 - disabled (always set if the sensor doesn't read humidity)
+ 2 - enabled"
+ ::= { uioSensorConfigEntry 20 }
+
+uioSensorConfigHighHumidityEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(1),
+ enabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The high humidity alarm enable/disable for the sensor.
+ 1 - disabled (always set if the sensor doesn't read humidity)
+ 2 - enabled"
+ ::= { uioSensorConfigEntry 21 }
+
+uioSensorConfigMaxHumidityEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(1),
+ enabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum humidity alarm enable/disable for the sensor.
+ 1 - disabled (always set if the sensor doesn't read humidity)
+ 2 - enabled"
+ ::= { uioSensorConfigEntry 22 }
+
+
+-- uio Input Contact Status Table
+
+uioInputContactStatusTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the uioInputContactStatusTable."
+ ::= { uioInputContact 1 }
+
+uioInputContactStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UIOInputContactStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting input contact status information."
+ ::= { uioInputContact 2 }
+
+uioInputContactStatusEntry OBJECT-TYPE
+ SYNTAX UIOInputContactStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The input contact from which to get data."
+ INDEX { uioInputContactStatusPortID, uioInputContactStatusContactID }
+ ::= { uioInputContactStatusTable 1 }
+
+UIOInputContactStatusEntry ::=
+ SEQUENCE {
+ uioInputContactStatusPortID INTEGER,
+ uioInputContactStatusContactID INTEGER,
+ uioInputContactStatusContactName DisplayString,
+ uioInputContactStatusContactLocation DisplayString,
+ uioInputContactStatusCurrentState INTEGER,
+ uioInputContactStatusAlarmStatus INTEGER,
+ uioInputContactStatusCommStatus INTEGER
+ }
+
+uioInputContactStatusPortID OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The ID of the port to which the input contact is attached."
+ ::= { uioInputContactStatusEntry 1 }
+
+uioInputContactStatusContactID OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The ID of the input contact on the module."
+ ::= { uioInputContactStatusEntry 2 }
+
+uioInputContactStatusContactName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The input contact name."
+ ::= { uioInputContactStatusEntry 3 }
+
+uioInputContactStatusContactLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The location of the input contact."
+ ::= { uioInputContactStatusEntry 4 }
+
+uioInputContactStatusCurrentState OBJECT-TYPE
+ SYNTAX INTEGER {
+ uioInputClosed (1),
+ uioInputOpen (2),
+ uioInputDisabled (3),
+ inputStateNotApplicable (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current state of the input contact. "
+ ::= { uioInputContactStatusEntry 5 }
+
+uioInputContactStatusAlarmStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ uioNormal (1),
+ uioWarning (2),
+ uioCritical (3),
+ inputStatusNotApplicable (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The alarm status of the input contact."
+ ::= { uioInputContactStatusEntry 6 }
+
+uioInputContactStatusCommStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ notInstalled (1),
+ commsOK (2),
+ commsLost (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The communications status of the input contact."
+ ::= { uioInputContactStatusEntry 7 }
+
+
+-- uio Input Contact Config Table
+
+uioInputContactConfigTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the uioInputContactConfigTable."
+ ::= { uioInputContact 3 }
+
+uioInputContactConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UIOInputContactConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for configuring the input contacts."
+ ::= { uioInputContact 4 }
+
+uioInputContactConfigEntry OBJECT-TYPE
+ SYNTAX UIOInputContactConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The input contact from which to get configuration."
+ INDEX { uioInputContactConfigPortID, uioInputContactConfigContactID }
+ ::= { uioInputContactConfigTable 1 }
+
+UIOInputContactConfigEntry ::=
+ SEQUENCE {
+ uioInputContactConfigPortID INTEGER,
+ uioInputContactConfigContactID INTEGER,
+ uioInputContactConfigContactName DisplayString,
+ uioInputContactConfigContactLocation DisplayString,
+ uioInputContactConfigEnable INTEGER,
+ uioInputContactConfigNormalState INTEGER,
+ uioInputContactConfigSeverity INTEGER
+ }
+
+uioInputContactConfigPortID OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The ID of the port to which the input contact is attached."
+ ::= { uioInputContactConfigEntry 1 }
+
+uioInputContactConfigContactID OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The ID of the input contact on the module."
+ ::= { uioInputContactConfigEntry 2 }
+
+uioInputContactConfigContactName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The input contact name."
+ ::= { uioInputContactConfigEntry 3 }
+
+uioInputContactConfigContactLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The location of the input contact."
+ ::= { uioInputContactConfigEntry 4 }
+
+uioInputContactConfigEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ uioInputContactDisabled (1),
+ uioInputContactEnabled (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable this input contact.
+ 1 - disabled
+ 2 - enabled"
+ ::= { uioInputContactConfigEntry 5 }
+
+uioInputContactConfigNormalState OBJECT-TYPE
+ SYNTAX INTEGER {
+ uioInputNormallyOpen (1),
+ uioInputNormallyClosed (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The normal (non-alarm) state of the input contact.
+ 1 - normally open
+ 2 - normally closed"
+ ::= { uioInputContactConfigEntry 6 }
+
+uioInputContactConfigSeverity OBJECT-TYPE
+ SYNTAX INTEGER {
+ uioInputCriticalSeverity (1),
+ uioInputWarningSeverity (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The severity of the alarm that this input contact will
+ generate in the abnormal state.
+ 1 - critical severity
+ 2 - warning severity"
+ ::= { uioInputContactConfigEntry 7 }
+
+
+-- uio Output Relay Status Table
+
+uioOutputRelayStatusTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the uioOutputRelayStatusTable."
+ ::= { uioOutputRelay 1 }
+
+uioOutputRelayStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UIOOutputRelayStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for getting output relay status information."
+ ::= { uioOutputRelay 2 }
+
+uioOutputRelayStatusEntry OBJECT-TYPE
+ SYNTAX UIOOutputRelayStatusEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The unit from which to get data."
+ INDEX { uioOutputRelayStatusPortID, uioOutputRelayStatusRelayID }
+ ::= { uioOutputRelayStatusTable 1 }
+
+UIOOutputRelayStatusEntry ::=
+ SEQUENCE {
+ uioOutputRelayStatusPortID INTEGER,
+ uioOutputRelayStatusRelayID INTEGER,
+ uioOutputRelayStatusRelayName DisplayString,
+ uioOutputRelayStatusRelayLocation DisplayString,
+ uioOutputRelayStatusCurrentState INTEGER,
+ uioOutputRelayStatusAlarmStatus INTEGER,
+ uioOutputRelayStatusCommStatus INTEGER
+ }
+
+uioOutputRelayStatusPortID OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The ID of the port to which the output relay is attached."
+ ::= { uioOutputRelayStatusEntry 1 }
+
+uioOutputRelayStatusRelayID OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The ID of the output relay on the module."
+ ::= { uioOutputRelayStatusEntry 2 }
+
+uioOutputRelayStatusRelayName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The output relay name."
+ ::= { uioOutputRelayStatusEntry 3 }
+
+uioOutputRelayStatusRelayLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The location of the output relay."
+ ::= { uioOutputRelayStatusEntry 4 }
+
+uioOutputRelayStatusCurrentState OBJECT-TYPE
+ SYNTAX INTEGER {
+ uioOutputClosed (1),
+ uioOutputOpen (2),
+ outputStateNotApplicable (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current state of the output relay."
+ ::= { uioOutputRelayStatusEntry 5 }
+
+uioOutputRelayStatusAlarmStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ uioNormal (1),
+ uioWarning (2),
+ uioCritical (3),
+ inputStatusNotApplicable (4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The alarm status of the output relay."
+ ::= { uioOutputRelayStatusEntry 6 }
+
+uioOutputRelayStatusCommStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ notInstalled (1),
+ commsOK (2),
+ commsLost (3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The communications status of the output relay."
+ ::= { uioOutputRelayStatusEntry 7 }
+
+
+-- uio Output Relay Config Table
+
+uioOutputRelayConfigTableSize OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of entries in the uioOutputRelayConfigTable."
+ ::= { uioOutputRelay 3 }
+
+uioOutputRelayConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UIOOutputRelayConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Allows for configuring the output relay."
+ ::= { uioOutputRelay 4 }
+
+uioOutputRelayConfigEntry OBJECT-TYPE
+ SYNTAX UIOOutputRelayConfigEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The unit from which to get configuration."
+ INDEX { uioOutputRelayConfigPortID, uioOutputRelayConfigRelayID }
+ ::= { uioOutputRelayConfigTable 1 }
+
+UIOOutputRelayConfigEntry ::=
+ SEQUENCE {
+ uioOutputRelayConfigPortID INTEGER,
+ uioOutputRelayConfigRelayID INTEGER,
+ uioOutputRelayConfigRelayName DisplayString,
+ uioOutputRelayConfigRelayLocation DisplayString,
+ uioOutputRelayConfigNormalState INTEGER,
+ uioOutputRelayConfigControlState INTEGER,
+ uioOutputRelayConfigDelay TimeTicks,
+ uioOutputRelayConfigHold TimeTicks
+ }
+
+uioOutputRelayConfigPortID OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The ID of the port to which the output relay is attached."
+ ::= { uioOutputRelayConfigEntry 1 }
+
+uioOutputRelayConfigRelayID OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The ID of the output relay on the module."
+ ::= { uioOutputRelayConfigEntry 2 }
+
+uioOutputRelayConfigRelayName OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The output relay name."
+ ::= { uioOutputRelayConfigEntry 3 }
+
+uioOutputRelayConfigRelayLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The location of the output relay."
+ ::= { uioOutputRelayConfigEntry 4 }
+
+uioOutputRelayConfigNormalState OBJECT-TYPE
+ SYNTAX INTEGER {
+ uioOutputNormallyOpen (1),
+ uioOutputNormallyClosed (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The normal state of the output relay.
+ 1 - normally open
+ 2 - normally closed"
+ ::= { uioOutputRelayConfigEntry 5 }
+
+uioOutputRelayConfigControlState OBJECT-TYPE
+ SYNTAX INTEGER {
+ uioOutputClose (1),
+ uioOutputOpen (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Close or open the output relay for testing purposes. Always
+ returns 1 when read.
+ 1 - close output relay
+ 2 - open output relay"
+ ::= { uioOutputRelayConfigEntry 6 }
+
+uioOutputRelayConfigDelay OBJECT-TYPE
+ SYNTAX TimeTicks
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The time a selected alarm condition must exist before the
+ output relay is activated. Valid values are whole seconds
+ from 0 to 65535."
+ ::= { uioOutputRelayConfigEntry 7 }
+
+uioOutputRelayConfigHold OBJECT-TYPE
+ SYNTAX TimeTicks
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum time the output relay remains activated after the
+ alarm occurs. Valid values are whole seconds from 0 to 65535."
+ ::= { uioOutputRelayConfigEntry 8 }
+
+
+-- Traps
+-- Annotations are provided for Novell's NMS product
+--
+-- Each trap has at least one variable (mtrapargsString) which always appears
+-- as the last variable in the list. This variable contains either a static
+-- or dynamically-constructed string which provides an enhanced description of
+-- the trap's purpose and any pertinent information about the trap.
+
+communicationLost TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Communication to the UPS has been lost. Steps
+ to reestablish communication are in progress."
+ --#TYPE "APC UPS: Communication lost"
+ --#SUMMARY "Communication lost between the agent and the UPS."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 1
+
+upsOverload TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The UPS has sensed a load greater than 100 percent
+ of its rated capacity."
+ --#TYPE "APC UPS: Overload"
+ --#SUMMARY "The UPS has sensed a load greater than 100 percent of its rated capacity."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 2
+
+upsDiagnosticsFailed TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The UPS failed its internal diagnostic self-test."
+ --#TYPE "APC UPS: Failed self-test"
+ --#SUMMARY "The UPS has failed its internal self-test."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 3
+
+upsDischarged TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The UPS batteries are discharged; if utility power fails
+ an immediate low battery condition will exist. Sufficient runtime
+ for necessary action cannot be guaranteed."
+ --#TYPE "APC UPS: batteries are discharged"
+ --#SUMMARY "The UPS batteries are discharged."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 4
+
+upsOnBattery TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: The UPS has switched to battery backup power."
+ --#TYPE "APC UPS: On battery"
+ --#SUMMARY "The UPS has switched to battery backup power."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 5
+
+smartBoostOn TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: The UPS has enabled SmartBoost(TM)."
+ --#TYPE "APC UPS: SmartBoost(TM)"
+ --#SUMMARY "The UPS has enabled SmartBoost(TM); low incoming line voltage."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 6
+
+lowBattery TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The UPS batteries are low and will soon be exhausted.
+ If utility power is not restored the UPS will put itself
+ to 'sleep' and immediately cut power to the load."
+ --#TYPE "APC UPS: Low battery"
+ --#SUMMARY "The UPS system's batteries are low and will soon be exhausted."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 7
+
+communicationEstablished TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Communication with the UPS has been established."
+ --#TYPE "APC UPS: Communication established"
+ --#SUMMARY "UPS communication has been established."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 8
+
+powerRestored TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Utility power has been restored."
+ --#TYPE "APC UPS: Utility power restored"
+ --#SUMMARY "Returned from battery backup power; utility power restored."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 9
+
+upsDiagnosticsPassed TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The UPS passed its internal self-test."
+ --#TYPE "APC UPS: Passed self-test"
+ --#SUMMARY "The UPS passed internal self-test."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 10
+
+returnFromLowBattery TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The UPS has returned from a low battery
+ condition."
+ --#TYPE "APC UPS: Returned from Low-Battery condition"
+ --#SUMMARY "The UPS has returned from a Low-Battery condition."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 11
+
+upsTurnedOff TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: The UPS has been turned 'off' by the management station."
+ --#TYPE "APC UPS: Turned off"
+ --#SUMMARY "The UPS has been switched off by a management station."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE NONOPERATIONAL
+ ::= 12
+
+upsSleeping TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: The UPS is entering 'sleep' mode. Power
+ to the load will be cut off."
+ --#TYPE "APC UPS: Entered sleep mode"
+ --#SUMMARY "The UPS entered sleep mode. Power to the load will be cut off."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE NONOPERATIONAL
+ ::= 13
+
+upsWokeUp TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATION: The UPS has returned from 'sleep' mode. Power
+ to the load has been restored."
+ --#TYPE "APC UPS: Wake up"
+ --#SUMMARY "The UPS has returned from sleep mode. Power to the load has been restored."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 14
+
+upsRebootStarted TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: The UPS has started its reboot sequence.
+ The UPS will reboot itself at this time."
+ --#TYPE "APC UPS: Starting reboot"
+ --#SUMMARY "The UPS has started its reboot sequence."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE NONOPERATIONAL
+ ::= 15
+
+upsDipSwitchChanged TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: The dip switch settings on the UPS have been
+ changed, possibly altering UPS performance."
+ --#TYPE "APC UPS: DIP switch altered"
+ --#SUMMARY "The DIP switch settings on the UPS have been changed."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 16
+
+upsBatteryNeedsReplacement TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The batteries of the UPS need immediate replacement."
+ --#TYPE "APC UPS: UPS batteries need replacement"
+ --#SUMMARY "The UPS batteries require immediate replacement."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 17
+
+
+-- the Environmental Monitor traps
+
+contactFault TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: One of the contacts on the Environmental Monitor has
+ changed from its default position. The first variable is
+ the contact number that is faulted."
+ --#TYPE "APC Environment: Contact fault"
+ --#SUMMARY "An Environment contact closure has faulted."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 18
+
+contactFaultResolved TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A fault on one of the Environmental Monitor contacts
+ has been resolved. The first variable is
+ the contact number that has been resolved."
+ --#TYPE "APC Environment: Contact fault cleared."
+ --#SUMMARY "A Environment contact closure has returned to it's default state."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 19
+
+-- the Matrix-UPS traps
+
+hardwareFailureBypass TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "SEVERE: UPS on bypass due to internal fault"
+ --#TYPE "APC UPS: On bypass due to internal fault"
+ --#SUMMARY "The UPS is on bypass due to an internal fault."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 20
+
+softwareBypass TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: UPS on bypass - user set via software or panel"
+ --#TYPE "APC UPS: On bypass by user via software or panel"
+ --#SUMMARY "UPS put on bypass by user via software or front UPS panel."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 21
+
+switchedBypass TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: UPS on bypass - initiated by user"
+ --#TYPE "APC UPS: On bypass initiated by user"
+ --#SUMMARY "UPS put on bypass by user."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 22
+
+returnFromBypass TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: UPS has returned from bypass"
+ --#TYPE "APC UPS: UPS has returned from bypass"
+ --#SUMMARY "The UPS has returned from bypass mode."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 23
+
+bypassPowerSupplyFailure TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Base module bypass power supply needs repair"
+ --#TYPE "APC UPS: Base module bypass power supply needs repair"
+ --#SUMMARY "The base module bypass power supply needs repair."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE NONOPERATIONAL
+ ::= 24
+
+baseFanFailure TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Base module fan needs repair"
+ --#TYPE "APC UPS: Base module fan needs repair"
+ --#SUMMARY "The base module fan needs repair."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE NONOPERATIONAL
+ ::= 25
+
+batteryPackCommLost TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Check installation of external battery packs signal cable"
+ --#TYPE "APC UPS: Communication lost with battery packs"
+ --#SUMMARY "Communication lost with external battery packs, check battery signal cable."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 26
+
+batteryPackCommEstablished TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: UPS is communicating with the external battery packs."
+ --#TYPE "APC UPS: Communication established with battery packs"
+ --#SUMMARY "Communication established with external battery packs."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 27
+
+calibrationStart TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A battery calibration test has been initiated on the UPS."
+ --#TYPE "APC UPS: Calibration initiated"
+ --#SUMMARY "A battery run time calibration test has been initiated."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 28
+
+-- Misc. Traps
+
+restartAgent TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Agent restarting as commanded by manager."
+ --#TYPE "APC SNMP Agent: Agent restarting"
+ --#SUMMARY "Agent restarting as commanded by manager."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 29
+
+upsTurnedOn TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A UPS is turned on."
+ --#TYPE "APC UPS: A UPS is turned on."
+ --#SUMMARY " A UPS is turned on."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 30
+
+smartAvrReducing TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: The UPS is reducing the line voltage via SmartTrim(TM)."
+ --#TYPE "APC UPS: SmartTrim(TM) reducing"
+ --#SUMMARY "The UPS has enabled SmartTrim(TM) voltage reduction."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 31
+
+codeAuthenticationDone TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mconfigTFTPServerIP, newCodeAuthentViaTFTP }
+ DESCRIPTION
+ "INFORMATIONAL: Authentication on agent code image is done."
+ --#TYPE "APC CODE: Authentication on agent code image is done."
+ --#SUMMARY "Authentication on agent code image is done."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 32
+
+upsOverloadCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The overload condition has been cleared."
+ --#TYPE "APC UPS: Overload cleared."
+ --#SUMMARY "The overload condition has been cleared. ."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 33
+
+smartBoostOff TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The UPS has returned from SmartBoost(TM)."
+ --#TYPE "APC UPS: SmartBoost(TM) off."
+ --#SUMMARY "The UPS has returned from SmartBoost(TM)."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 34
+
+smartAvrReducingOff TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The UPS has returned from SmartTrim(TM)."
+ --#TYPE "APC UPS: SmartTrim(TM) reducing off"
+ --#SUMMARY "The UPS has returned from SmartTrim(TM) voltage reduction."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 35
+
+upsBatteryReplaced TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A bad battery fault has been cleared."
+ --#TYPE "APC UPS: Bad battery replaced"
+ --#SUMMARY "The UPS has returned from a bad battery fault."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 36
+
+calibrationEnd TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The UPS has finished calibrating."
+ --#TYPE "APC UPS: Calibration end"
+ --#SUMMARY "The UPS has finished calibrating"
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 37
+
+dischargeCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A UPS discharge condition has been cleared."
+ --#TYPE "APC UPS: Discharge cleared."
+ --#SUMMARY "The UPS discharge condition has been cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 38
+
+gracefulShutdown TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A graceful shutdown has been initiated."
+ --#TYPE "APC UPS: A graceful shutdown has been initiated."
+ --#SUMMARY "A graceful shutdown has been initiated."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 39
+
+
+outletOn TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { sPDUOutletControlIndex }
+ DESCRIPTION
+ "WARNING: The specified PDU outlet has turned on.
+ If sPDUOutletControlIndex equals zero, then all outlets have
+ turned on."
+ --#TYPE "APC PDU: Outlet has been turned on."
+ --#SUMMARY "Outlet has been turned on"
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 41
+
+
+outletOff TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { sPDUOutletControlIndex }
+ DESCRIPTION
+ "WARNING: The specified PDU outlet has turned off.
+ If sPDUOutletControlIndex equals zero, then all outlets
+ have turned off."
+ --#TYPE "APC PDU: Outlet has turned off."
+ --#SUMMARY "Outlet has turned off."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 42
+
+outletReboot TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { sPDUOutletControlIndex }
+ DESCRIPTION
+ "WARNING: The specified PDU outlet has rebooted.
+ If sPDUOutletControlIndex equals zero, then all outlets
+ have rebooted."
+ --#TYPE "APC PDU: Outlet has rebooted."
+ --#SUMMARY "Outlet has rebooted."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 43
+
+configChangeSNMP TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: The SNMP configuration has been changed."
+ --#TYPE "APC: The SNMP configuration has been changed."
+ --#SUMMARY "The SNMP configuration has been changed."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 44
+
+
+configChangeOutlet TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { sPDUOutletConfigIndex }
+ DESCRIPTION
+ "WARNING: The specified PDU outlet has changed configuration.
+ If sPDUOutletConfigIndex equals zero, then the Master outlet
+ has changed configuration."
+ --#TYPE "APC PDU: Outlet configuration has been changed."
+ --#SUMMARY "Outlet configuration has been changed."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 45
+
+accessViolationConsole TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: Someone has attempted to login via the console with the incorrect password."
+ --#TYPE "APC: Access violation via the console."
+ --#SUMMARY "Three unsuccessful logins have been attempted via the console."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 46
+
+accessViolationHTTP TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: Someone has attempted to login via HTTP with the incorrect password."
+ --#TYPE "APC: Access violation via HTTP."
+ --#SUMMARY "An unsuccessful attempt to login via HTTP."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 47
+
+passwordChange TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: The password for the device has been changed."
+ --#TYPE "APC: Password change for the device."
+ --#SUMMARY "Someone has changed the password on the device."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 48
+
+badVoltage TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: The output voltage is not within acceptable range."
+ --#TYPE "APC UPS: Bad output voltage."
+ --#SUMMARY "The output voltage is not within acceptable range."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 49
+
+badVoltageCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The output voltage has returned to an acceptable level."
+ --#TYPE "APC UPS: The bad voltage output condition has been cleared."
+ --#SUMMARY "The output voltage has returned to an acceptable level."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 50
+
+chargerFailure TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: The battery charger has failed."
+ --#TYPE "APC UPS: The battery charger has failed."
+ --#SUMMARY "The battery charger has failed."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 51
+
+chargerFailureCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The battery charger failure condition has been cleared."
+ --#TYPE "APC UPS: The battery charger failure condition cleared"
+ --#SUMMARY "The battery charger failure condition has been cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 52
+
+batteryOverTemperature TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: The battery temperature threshold has been violated."
+ --#TYPE "APC UPS: The battery temperature threshold has been violated."
+ --#SUMMARY "The battery temperature threshold has been violated."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 53
+
+batteryOverTemperatureCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The battery over temperature has been cleared."
+ --#TYPE "APC UPS: The battery over temperature has been cleared."
+ --#SUMMARY "The battery over temperature has been cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 54
+
+ smartRelayFault TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: SmartBoost(TM) or SmartTrim(TM) relay fault."
+ --#TYPE "APC UPS: SmartBoost(TM) or SmartTrim(TM) relay fault."
+ --#SUMMARY "SmartBoost(TM) or SmartTrim(TM) relay fault."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 55
+
+smartRelayFaultCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: SmartBoost(TM) or SmartTrim(TM) relay fault has been cleared."
+ --#TYPE "APC UPS: SmartBoost(TM) or SmartTrim(TM) relay fault cleared."
+ --#SUMMARY "SmartBoost(TM) or SmartTrim(TM) relay fault has been cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 56
+
+humidityThresholdViolation1 TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Probe 1 humidity threshold violated. The
+ first variable is the current humidity."
+ --#TYPE "APC Environmental Monitor: Probe 1 humidity threshold violation"
+ --#SUMMARY "A humidity threshold has been violated on probe 1."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 57
+
+humidityThresholdViolationCleared1 TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: An Environmental Monitor humidity threshold violation has been cleared on probe 1."
+ --#TYPE "APC Environmental Monitor: Probe 1 humidity violation cleared"
+ --#SUMMARY "A humidity threshold violation has been cleared on probe 1."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 58
+
+temperatureThresholdViolation1 TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: An Environmental Monitor temperature threshold has been violated on probe 1.
+ The first variable is the current temperature."
+ --#TYPE "APC Environmental Monitor: Probe 1 temperature violation"
+ --#SUMMARY "A temperature threshold has been violated on probe 1."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 59
+
+temperatureThresholdViolationCleared1 TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: An Environmental Monitor temperature threshold violation has been cleared on probe 1."
+ --#TYPE "APC Environmental Monitor: Probe 1 temperature violation cleared"
+ --#SUMMARY "A temperature threshold violation has been cleared on probe 1."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 60
+
+humidityThresholdViolation2 TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: An Environmental Monitor humidity threshold has been violated on probe 2.
+ The first variable is the current humidity."
+ --#TYPE "APC Environmental Monitor: Probe 2 humidity violation"
+ --#SUMMARY "A humidity threshold has been violated on probe 2."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 61
+
+humidityThresholdViolationCleared2 TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: An Environmental Monitor humidity threshold violation has been cleared on probe 2."
+ --#TYPE "APC Environmental Monitor: Probe 2 humidity violation cleared"
+ --#SUMMARY "A humidity threshold violation has been cleared on probe 2."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 62
+
+temperatureThresholdViolation2 TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: An Environmental Monitor temperature threshold has been violated on probe 2.
+ The first variable is the current temperature."
+ --#TYPE "APC Environmental Monitor: Probe 2 temperature violation"
+ --#SUMMARY "A temperature threshold has been violated on probe 2."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 63
+
+temperatureThresholdViolationCleared2 TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: An Environmental Monitor temperature threshold violation has been cleared on probe 2."
+ --#TYPE "APC Environmental Monitor: Probe 2 temperature violation cleared"
+ --#SUMMARY "A temperature threshold violation has been cleared on probe 2."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 64
+
+mupsCommunicationEstablished TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Communication with the Environmental Monitor has been established."
+ --#TYPE "APC Environmental Monitor: Communication established"
+ --#SUMMARY "Communication established between the agent and the Environmental Monitor."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 65
+
+mupsCommunicationLost TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Communication to the Environmental Monitor has been lost. Steps
+ to reestablish communication are in progress."
+ --#TYPE "APC Environmental Monitor: Communication failure"
+ --#SUMMARY "Communication lost between the agent and the Environmental Monitor."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 66
+
+batteryIncrease TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The number of batteries has increased."
+ --#TYPE "APC UPS: The number of batteries has increased."
+ --#SUMMARY "The number of batteries has increased."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 67
+
+batteryDecrease TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The number of batteries has decreased."
+ --#TYPE "APC UPS: The number of batteries has decreased."
+ --#SUMMARY "The number of batteries has decreased."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 68
+
+powerModuleIncrease TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The number of power modules has increased."
+ --#TYPE "APC UPS: The number of power modules has increased."
+ --#SUMMARY "The number of power modules has increased."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 69
+
+powerModuleDecrease TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The number of power modules has decreased."
+ --#TYPE "APC UPS: The number of power modules has decreased."
+ --#SUMMARY "The number of power modules has decreased."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 70
+
+intelligenceModuleInserted TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: An intelligence module has been inserted."
+ --#TYPE "APC UPS: An intelligence module has been inserted."
+ --#SUMMARY "An intelligence module has been inserted."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 71
+
+intelligenceModuleRemoved TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: An intelligence module has been removed."
+ --#TYPE "APC UPS: An intelligence module has been removed."
+ --#SUMMARY "An intelligence module has been removed."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 72
+
+rintelligenceModuleInserted TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A redundant intelligence module has been inserted."
+ --#TYPE "APC UPS: A redundant intelligence module has been inserted."
+ --#SUMMARY "A redundant intelligence module has been inserted."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 73
+
+rintelligenceModuleRemoved TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A redundant intelligence module has been removed."
+ --#TYPE "APC UPS: A redundant intelligence module has been removed."
+ --#SUMMARY "A redundant intelligence module has been removed."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 74
+
+extBatteryFrameIncease TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: An external battery frame has been added."
+ --#TYPE "APC UPS: An external battery frame has been added."
+ --#SUMMARY "An external battery frame has been added."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 75
+
+extBatteryFrameDecrease TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: An external battery frame has been removed."
+ --#TYPE "APC UPS: An external battery frame has been removed."
+ --#SUMMARY "An external battery frame has been removed."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 76
+
+abnormalCondition TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: An abnormal condition has been detected.
+ The first variable is the fault condition."
+ --#TYPE "APC: An abnormal condition has been detected."
+ --#SUMMARY "An abnormal condition has been detected."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 77
+
+abnormalConditionCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: An abnormal condition has been cleared.
+ The first variable is the fault condition."
+ --#TYPE "APC: An abnormal condition has been cleared."
+ --#SUMMARY "An abnormal condition has been cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 78
+
+deviceStatusChange TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString}
+ DESCRIPTION
+ "INFORMATIONAL: The status of the device being monitored has changed."
+ --#TYPE "APC : The status of the device being monitored has changed."
+ --#SUMMARY "The status of the device being monitored has changed."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 79
+
+noBatteries TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: The UPS has no batteries attached."
+ --#TYPE "APC UPS: No batteries attached."
+ --#SUMMARY "The UPS has no batteries attached."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 80
+
+noBatteriesCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The UPS's batteries have been attached."
+ --#TYPE "APC UPS: The no batteries attached condition has been cleared."
+ --#SUMMARY "The UPS's batteries have been attached."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 81
+
+userAdded TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A new user has been added."
+ --#TYPE "APC: A new user has been added."
+ --#SUMMARY "A new user has been added."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 82
+
+userDeleted TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A user has been deleted."
+ --#TYPE "APC: A user has been deleted."
+ --#SUMMARY "A user has been deleted."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 83
+
+userModified TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A user has been modified."
+ --#TYPE "APC: A user has been modified."
+ --#SUMMARY "A user has been modified."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 84
+
+-- MasterSwitch Vm Traps
+
+msvmCommunicationEstablished TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { sPDUMasterControlVMIndex, sPDUMasterControlVMName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Communications with the MasterSwitch VM has been established."
+ --#TYPE "APC: Communications established with the MasterSwitch VM."
+ --#SUMMARY "Communications with the MasterSwitch VM has been established."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 85
+
+msvmCommunicationLost TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { sPDUMasterControlVMIndex, sPDUMasterControlVMName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Communications with the MasterSwitch VM has been lost."
+ --#TYPE "APC: Communications lost with the MasterSwitch VM."
+ --#SUMMARY "Communications with the MasterSwitch VM has been lost."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 86
+
+msvmOverload TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { sPDUMasterControlVMIndex, sPDUMasterControlVMName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The MasterSwitch VM in an overload condition."
+ --#TYPE "APC: The MasterSwitch VM is near or at an overload condition."
+ --#SUMMARY "The MasterSwitch VM is near or at an overload condition."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 87
+
+msvmOverloadCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { sPDUMasterControlVMIndex, sPDUMasterControlVMName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The overload condition on the MasterSwitch VM has been cleared."
+ --#TYPE "APC: The overload condition cleared on the MasterSwitch VM."
+ --#SUMMARY "The overload condition on the MasterSwitch VM has been cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 88
+
+msvmOutletOn TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { sPDUMasterControlVMIndex, sPDUMasterControlVMName,
+ sPDUOutletControlVMOutletIndex, sPDUOutletControlVMOutletName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: An outlet on the MasterSwitch VM has turned on."
+ --#TYPE "APC: An outlet on the MasterSwitch VM has turned on."
+ --#SUMMARY "An outlet on the MasterSwitch VM has turned on."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 89
+
+msvmOutletOff TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { sPDUMasterControlVMIndex, sPDUMasterControlVMName,
+ sPDUOutletControlVMOutletIndex, sPDUOutletControlVMOutletName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: An outlet on the MasterSwitch VM has turned off."
+ --#TYPE "APC: An outlet on the MasterSwitch VM has turned off."
+ --#SUMMARY "An outlet on the MasterSwitch VM has turned off."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 90
+
+msvmDeviceConfigChange TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { sPDUMasterControlVMIndex, sPDUMasterControlVMName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A device configuration change has been made on a MasterSwitch VM."
+ --#TYPE "APC: A device configuration change on a MasterSwitch VM."
+ --#SUMMARY "A device configuration change has been made on a MasterSwitch VM."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 91
+
+msvmOutletConfigChange TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { sPDUMasterControlVMIndex, sPDUMasterControlVMName,
+ sPDUOutletControlVMOutletIndex, sPDUOutletControlVMOutletName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: An outlet configuration change has been made on a MasterSwitch VM."
+ --#TYPE "APC: An outlet configuration change on a MasterSwitch VM."
+ --#SUMMARY "An outlet configuration change has been made on a MasterSwitch VM."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 92
+
+msvmLowLoad TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { sPDUMasterControlVMIndex, sPDUMasterControlVMName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The MasterSwitch VM has violated the low load threshold."
+ --#TYPE "APC: The MasterSwitch VM has violated the low load threshold."
+ --#SUMMARY "The MasterSwitch VM has violated the low load threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 93
+
+msvmLowLoadCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { sPDUMasterControlVMIndex, sPDUMasterControlVMName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The low load condition on the MasterSwitch VM has been cleared."
+ --#TYPE "APC: The low load condition cleared on the MasterSwitch VM."
+ --#SUMMARY "The low load condition on the MasterSwitch VM has been cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 94
+
+msvmNearOverload TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { sPDUMasterControlVMIndex, sPDUMasterControlVMName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The MasterSwitch VM is approaching an overload condition."
+ --#TYPE "APC: The MasterSwitch VM is near or at an overload condition."
+ --#SUMMARY "The MasterSwitch VM is near or at an overload condition."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 95
+
+msvmNearOverloadCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { sPDUMasterControlVMIndex, sPDUMasterControlVMName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The near overload condition on the MasterSwitch VM has been cleared."
+ --#TYPE "APC: The overload condition cleared on the MasterSwitch VM."
+ --#SUMMARY "The overload condition on the MasterSwitch VM has been cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 96
+
+msvmPowerSupplyStatusChange TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { sPDUMasterControlVMIndex, sPDUMasterControlVMName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "WARNING: The power supply status of the MasterSwitch VM has changed."
+ --#TYPE "APC: The power supply status changed on MasterSwitch VM"
+ --#SUMMARY "The power supply status of the MasterSwitch VM has changed."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 97
+
+-- MasterSwitch plus (MSP) Traps
+
+mspCommunicationEstablished TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { sPDUMasterControlMSPIndex, sPDUMasterControlMSPName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Communications with the MasterSwitch plus has been established."
+ --#TYPE "APC: Communications established with the MasterSwitch plus."
+ --#SUMMARY "Communications with the MasterSwitch plus has been established."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 98
+
+mspCommunicationLost TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { sPDUMasterControlMSPIndex, sPDUMasterControlMSPName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Communications with the MasterSwitch plus has been lost."
+ --#TYPE "APC: Communications lost with the MasterSwitch plus."
+ --#SUMMARY "Communications with the MasterSwitch plus has been lost."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 99
+
+mspOutletOn TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { sPDUMasterControlMSPIndex, sPDUMasterControlMSPName,
+ sPDUOutletControlMSPOutletIndex, sPDUOutletControlMSPOutletName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: An outlet on the MasterSwitch plus has turned on."
+ --#TYPE "APC: An outlet on the MasterSwitch plus has turned on."
+ --#SUMMARY "An outlet on the MasterSwitch plus has turned on."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 100
+
+mspOutletOff TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { sPDUMasterControlMSPIndex, sPDUMasterControlMSPName,
+ sPDUOutletControlMSPOutletIndex, sPDUOutletControlMSPOutletName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: An outlet on the MasterSwitch plus has turned off."
+ --#TYPE "APC: An outlet on the MasterSwitch plus has turned off."
+ --#SUMMARY "An outlet on the MasterSwitch plus has turned off."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 101
+
+mspDeviceConfigChange TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { sPDUMasterControlMSPIndex, sPDUMasterControlMSPName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A device configuration change has been made on a MasterSwitch plus."
+ --#TYPE "APC: A device configuration change on a MasterSwitch plus."
+ --#SUMMARY "A device configuration change has been made on a MasterSwitch plus."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 102
+
+mspOutletConfigChange TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { sPDUMasterControlMSPIndex, sPDUMasterControlMSPName, sPDUOutletControlMSPOutletIndex, sPDUOutletControlMSPOutletName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: An outlet configuration change has been made on a MasterSwitch plus."
+ --#TYPE "APC: An outlet configuration change on a MasterSwitch plus."
+ --#SUMMARY "An outlet configuration change has been made on a MasterSwitch plus."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 103
+
+rsSourceSwitched TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsInteger02, mtrapargsString03, mtrapargsInteger, mtrapargsString02, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The Redundant Switch has switched source.
+ The first variable is an integer representing the current source: 0=A, 1=B.
+ The second variable is the 32-character name of the current source.
+ The third variable is an integer representing the transfer cause:
+ 0=No Transfers Recorded, 1=Due to user action or preferred switching,
+ 3=Due to line notch or spike, 5=Due to low line voltage,
+ 7=Transfer due to high line voltage,
+ 9=Transfer due to frequency out of range.
+ The fourth variable is a character string listing the transfer cause."
+ --#TYPE "APC Redundant Switch: The Redundant Switch has switched source"
+ --#SUMMARY "The Redundant Switch has switched source."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 104
+
+rsLostRedundancy TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsInteger, mtrapargsString02, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The Redundant Switch has lost redundancy.
+ The first variable is an integer representing the source which is no longer available: 0=A, 1=B.
+ The second variable is the 32-character name of the source which is no longer available."
+ --#TYPE "APC Redundant Switch: The Redundant Switch has lost redundancy"
+ --#SUMMARY "The Redundant Switch has lost redundancy."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 105
+
+rsRedundancyRestored TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsInteger, mtrapargsString02, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Redundancy has been restored to the Redundant Switch .
+ The first variable is an integer representing the source which has been restored: 0=A, 1=B.
+ The second variable is the 32-character name of the source which has been restored."
+ --#TYPE "APC Redundant Switch: Redundancy has been restored."
+ --#SUMMARY "Redundancy has been restored to the Redundant Switch ."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 106
+
+rsConfigChange TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A configuration change has been made on a Redundant Switch."
+ --#TYPE "APC: A configuration change on a Redundant Switch."
+ --#SUMMARY "A configuration change has been made on a Redundant Switch."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 107
+
+rsCommunicationEstablished TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Communications with the Redundant Switch has been established."
+ --#TYPE "APC: Communications established with the Redundant Switch."
+ --#SUMMARY "Communications with the Redundant Switch has been established."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 108
+
+rsCommunicationLost TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Communications with the Redundant Switch has been lost."
+ --#TYPE "APC: Communications lost with the Redundant Switch."
+ --#SUMMARY "Communications with the Redundant Switch has been lost."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 109
+
+dcCommunicationEstablished TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Communications with the DC power plant has been established."
+ --#TYPE "APC: Communications established with the DC power plant."
+ --#SUMMARY "Communications with the DC power plant has been established."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 110
+
+dcCommunicationLost TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Communications with the DC power plant has been lost."
+ --#TYPE "APC: Communications lost with the DC power plant."
+ --#SUMMARY "Communications with the DC power plant has been lost."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 111
+
+dcPINChanged TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The active PIN on the DC controller has been changed."
+ --#TYPE "APC: The active PIN on the DC controller has been changed."
+ --#SUMMARY "The active PIN on the DC controller has been changed."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 112
+
+dcMajorAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "SEVERE: A Major alarm is active in the DC power plant."
+ --#TYPE "APC: A Major alarm is active in the DC power plant."
+ --#SUMMARY "A Major alarm is active in the DC power plant."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 113
+
+dcMajorAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A Major alarm is no longer active in the DC power plant."
+ --#TYPE "APC: A Major alarm is no longer active in the DC power plant."
+ --#SUMMARY "A Major alarm is no longer active in the DC power plant."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 114
+
+dcMinorAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: A Minor alarm is active in the DC power plant."
+ --#TYPE "APC: A Minor alarm is active in the DC power plant."
+ --#SUMMARY "A Minor alarm is active in the DC power plant."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 115
+
+dcMinorAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A Minor alarm is no longer active in the DC power plant."
+ --#TYPE "APC: A Minor alarm is no longer active in the DC power plant."
+ --#SUMMARY "A Minor alarm is no longer active in the DC power plant."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 116
+
+dcOutputRelayOn TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { dm3StatusOutRlyIndex, dm3StatusOutRlyName, mtrapargsString }
+ DESCRIPTION
+ "WARNING: An output relay for the powerplant has been activated (state changed to on).
+ The first variable is an integer representing the output relay number that has gone on.
+ The second variable is the 16-character name of the output relay."
+ --#TYPE "APC: An output relay has gone on."
+ --#SUMMARY "An output relay has gone on in the DC power plant."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 117
+
+dcOutputRelayOff TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { dm3StatusOutRlyIndex, dm3StatusOutRlyName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: An output relay for the powerplant has been deactivated (state changed to off).
+ The first variable is an integer representing the output relay number that has gone off.
+ The second variable is the 16-character name of the output relay."
+ --#TYPE "APC: An output relay has gone off."
+ --#SUMMARY "An output relay has gone off in the DC power plant."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 118
+
+dcInputRelayOn TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { dm3StatusInRlyIndex, dm3StatusInRlyName, mtrapargsString }
+ DESCRIPTION
+ "WARNING: An input relay for the powerplant has been activated (state changed to on).
+ The first variable is an integer representing the input relay number that has gone on.
+ The second variable is the 16-character name of the input relay."
+ --#TYPE "APC: An input relay has gone on."
+ --#SUMMARY "An input relay has gone on in the DC power plant."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 119
+
+dcInputRelayOff TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { dm3StatusInRlyIndex, dm3StatusInRlyName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: An input relay for the powerplant has been deactivated (state changed to off).
+ The first variable is an integer representing the input relay number that has gone off.
+ The second variable is the 16-character name of the input relay."
+ --#TYPE "APC: An input relay has gone off."
+ --#SUMMARY "An input relay has gone off in the DC power plant."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 120
+
+logicPowerSuppliesIncreased TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The number of system power supplies has increased."
+ --#TYPE "APC UPS: The number of system power supplies has increased."
+ --#SUMMARY "The number of system power supplies has increased."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 121
+
+logicPowerSuppliesDecreased TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The number of system power supplies has decreased."
+ --#TYPE "APC UPS: The number of system power supplies has decreased."
+ --#SUMMARY "The number of system power supplies has decreased."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 122
+
+externalSwitchGearClosed TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: External Switch Gear closed."
+ --#TYPE "APC UPS: External Switch Gear closed."
+ --#SUMMARY "External Switch Gear closed."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 123
+
+externalSwitchGearOpened TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: External Switch Gear opened."
+ --#TYPE "APC UPS: External Switch Gear opened."
+ --#SUMMARY "External Switch Gear opened."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 124
+
+generalDeviceEvent TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: APC Device event."
+ --#TYPE "APC Device event"
+ --#SUMMARY "APC Device event."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 125
+
+atsSourceSwitched TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsInteger, mtrapargsString02, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The Automatic Transfer Switch has switched source.
+ The first variable is an integer representing the current source: 0=A, 1=B.
+ The second variable is the 32-character name of the current source."
+ --#TYPE "APC Automatic Transfer Switch: The ATS has switched source"
+ --#SUMMARY "The Automatic Transfer Switch has switched source."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 126
+
+atsLostRedundancy TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsInteger, mtrapargsString02, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The Automatic Transfer Switch has lost redundancy.
+ The first variable is an integer representing the source which is no longer available: 0=A, 1=B.
+ The second variable is the 32-character name of the source which is no longer available."
+ --#TYPE "APC Automatic Transfer Switch: The ATS has lost redundancy. "
+ --#SUMMARY "The Automatic Transfer Switch has lost redundancy."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 127
+
+atsRedundancyRestored TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsInteger, mtrapargsString02, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Redundancy has been restored to the Automatic Transfer Switch .
+ The first variable is an integer representing the source which has been restored: 0=A, 1=B.
+ The second variable is the 32-character name of the source which has been restored."
+ --#TYPE "APC Automatic Transfer Switch: Redundancy has been restored."
+ --#SUMMARY "Redundancy has been restored to the Automatic Transfer Switch ."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 128
+
+atsConfigChange TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A configuration change has been made on the Automatic Transfer Switch.
+ The first variable is an integer representing the configuration setting which changed:
+ 0=Transfer Voltage Range, 1=Sensitivity, 2=Preferred Source
+ 3=Front Panel Lockout, 4=Current Limit, 5=Reset XA Processor,
+ 6=Reset to defaults, 7=Product Name, 8=Nominal Voltage, 9=Nominal Line Frequency,
+ 10=Narrow VRMS, 11=Medium VRMS, 12=Wide VRMS,13=Frequency Deviation,
+ 14=ColdStart ATS, 15=Events Count Cleared, 16=Phase or Bank Threshold. "
+ --#TYPE "APC Automatic Transfer Switch: ATS configuration changed."
+ --#SUMMARY "A configuration change has been made on a Automatic Transfer Switch."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 129
+
+atsCommunicationEstablished TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Communications with the Automatic Transfer Switch has been established."
+ --#TYPE "APC Automatic Transfer Switch: Communications established."
+ --#SUMMARY "Communications with the Automatic Transfer Switch has been established."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 130
+
+atsCommunicationLost TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Communications with the Automatic Transfer Switch has been lost."
+ --#TYPE "APC Automatic Transfer Switch: Communications lost."
+ --#SUMMARY "Communications with the Automatic Transfer Switch has been lost."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 131
+
+atsOverCurrent TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Output Current has exceeded threshold. This is same as atsOverload Trap
+ for phase or total in case banked units"
+
+ --#TYPE "APC Automatic Transfer Switch: Output Current exceeded threshold"
+ --#SUMMARY "Output Current has exceeded Threshold. "
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 132
+
+atsOverCurrentCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Output Current has returned below threshold.This is same as atsOverloadCleared Trap
+ for phase or total in case banked units"
+ --#TYPE "APC Automatic Transfer Switch: Output Current below threshold."
+ --#SUMMARY "Output Current has returned below threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 133
+
+atsPowerSupplyFailure TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The Automatic Transfer Switch Power Supply has failed.
+ The first variable is an integer representing the Power Supply which
+ has failed: 0 = Source A 24V,
+ 1 = 12V,
+ 2 = 5V,
+ 3 = Source B 24V."
+ --#TYPE "APC Automatic Transfer Switch: The ATS Power Supply has failed."
+ --#SUMMARY "The Automatic Transfer Switch Power Supply has failed."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 134
+
+atsPowerSupplyFailureCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The Automatic Transfer Power Supply Failure Cleared.
+ The first variable is an integer representing the Power Supply which
+ has cleared: 0 = Source A 24V,
+ 1 = 12V,
+ 2 = 5V,
+ 3 = Source B 24V."
+ --#TYPE "APC Automatic Transfer Switch: Power Supply Failure Cleared."
+ --#SUMMARY "The Automatic Transfer Switch Power Supply Failure Cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 135
+
+dcMainsFailAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: A Mains Fail alarm is active in the DC power plant."
+ --#TYPE "APC: A Mains Fail alarm is active in the DC power plant."
+ --#SUMMARY "A Mains Fail alarm is active in the DC power plant."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 136
+
+dcMainsFailAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Mains Fail alarm is no longer active in the DC power plant."
+ --#TYPE "APC: Mains Fail alarm is no longer active in the DC power plant."
+ --#SUMMARY "Mains Fail alarm is no longer active in the DC power plant."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 137
+
+dcFanFailAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: A Fan Fail alarm is active in the DC power plant."
+ --#TYPE "APC: A Fan Fail alarm is active in the DC power plant."
+ --#SUMMARY "A Fan Fail alarm is active in the DC power plant."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 138
+
+dcFanFailAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A Fan Fail alarm is no longer active in the DC power plant."
+ --#TYPE "APC: A Fan Fail alarm is no longer active in the DC power plant."
+ --#SUMMARY "A Fan Fail alarm is no longer active in the DC power plant."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 139
+
+dcRectifierOvertempAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: Rect. Overtemp alarm is active in the power plant."
+ --#TYPE "APC: Rect. Overtemp alarm is active in the power plant."
+ --#SUMMARY "Rect. Overtemp alarm is active in the power plant."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 140
+
+dcRectifierOvertempAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Rect. Overtemp alarm is no longer active in the power plant."
+ --#TYPE "APC: Rect. Overtmp alarm is no longer active in the power plant."
+ --#SUMMARY "Rect. Overtemp alarm is no longer active in the power plant."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 141
+
+dcCurrentLimitAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: A Current Limit alarm is active in the power plant."
+ --#TYPE "APC: A Current Limit alarm is active in the power plant."
+ --#SUMMARY "A Current Limit alarm is active in the power plant."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 142
+
+dcCurrentLimitAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Current Limit alarm is no longer active in the power plant."
+ --#TYPE "APC: Current Limit alarm is no longer active in the power plant."
+ --#SUMMARY "Current Limit alarm is no longer active in the power plant."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 143
+
+dcRectifierFailAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: A Rect. Fail alarm is active in the power plant."
+ --#TYPE "APC: A Rect. Fail alarm is active in the power plant."
+ --#SUMMARY "A Rect. Fail alarm is active in the power plant."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 144
+
+dcRectifierFailAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Rect. Fail alarm is no longer active in the power plant."
+ --#TYPE "APC: Rect. Fail alarm is no longer active in the power plant."
+ --#SUMMARY "Rect. Fail alarm is no longer active in the power plant."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 145
+
+dcMultRectFailAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: Multiple Rect. Fail alarm is active in the powerplant."
+ --#TYPE "APC: Multiple Rect. Fail alarm is active in the powerplant."
+ --#SUMMARY "Multiple Rect. Fail alarm is active in the powerplant."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 146
+
+dcMultRectFailAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Multiple Rect Fail alarm is no longer active in the powerplant."
+ --#TYPE "APC: Multiple Rect Fail alarm is no longer active in powerplant."
+ --#SUMMARY "Multiple Rect Fail alarm is no longer active in the powerplant."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 147
+
+dcBatteryBreakerAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: Batt. Breaker alarm is active in the power plant."
+ --#TYPE "APC: Batt. Breaker alarm is active in the power plant."
+ --#SUMMARY "Batt. Breaker alarm is active in the power plant."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 148
+
+dcBatteryBreakerAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Batt. Breaker alarm is no longer active in the power plant."
+ --#TYPE "APC: Batt. Breaker alarm is no longer active in the power plant."
+ --#SUMMARY "Batt. Breaker alarm is no longer active in the power plant."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 149
+
+dcRectifierOVPAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: A Rect. OVP alarm is active in the power plant."
+ --#TYPE "APC: A Rect. OVP alarm is active in the power plant."
+ --#SUMMARY "A Rect. OVP alarm is active in the power plant."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 150
+
+dcRectifierOVPAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A Rect. OVP alarm is no longer active in the power plant."
+ --#TYPE "APC: A Rect. OVP alarm is no longer active in the power plant."
+ --#SUMMARY "A Rect. OVP alarm is no longer active in the power plant."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 151
+
+dcLVDImminentAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: A LVD Imminent alarm is active in the powerplant."
+ --#TYPE "APC: A LVD Imminent alarm is active in the powerplant."
+ --#SUMMARY "A LVD Imminent alarm is active in the powerplant."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 152
+
+dcLVDImminentAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A LVD Imminent alarm is no longer active in the powerplant."
+ --#TYPE "APC: A LVD Imminent alarm is no longer active in the powerplant."
+ --#SUMMARY "A LVD Imminent alarm is no longer active in the powerplant."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 153
+
+dcFuseCBAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: A Fuse/CB alarm is active in the DC power plant."
+ --#TYPE "APC: A Fuse/CB alarm is active in the DC power plant."
+ --#SUMMARY "A Fuse/CB alarm is active in the DC power plant."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 154
+
+dcFuseCBAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A Fuse/CB alarm is no longer active in the DC power plant."
+ --#TYPE "APC: A Fuse/CB alarm is no longer active in the DC power plant."
+ --#SUMMARY "A Fuse/CB alarm is no longer active in the DC power plant."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 155
+
+dcBatteryTestFail TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: A Battery Test failed in the DC power plant."
+ --#TYPE "APC: A Battery Test failed in the DC power plant."
+ --#SUMMARY "A Battery Test failed in the DC power plant."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 156
+
+dcTemperatureAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: A Temperature is active in the power plant."
+ --#TYPE "APC: A Temperature alarm is active in the power plant."
+ --#SUMMARY "A Temperature alarm is active in the power plant."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 157
+
+dcTemperatureAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A Temperature alarm is no longer active in the power plant."
+ --#TYPE "APC: A Temperature alarm is no longer active in the power plant."
+ --#SUMMARY "A Temperature alarm is no longer active in the power plant."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 158
+
+dcHumidityAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: A Humidity alarm is active in the DC power plant."
+ --#TYPE "APC: A Humidity alarm is active in the DC power plant."
+ --#SUMMARY "A Humidity alarm is active in the DC power plant."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 159
+
+dcHumidityAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A Humidity alarm is no longer active in the DC power plant."
+ --#TYPE "APC: A Humidity alarm is no longer active in the DC power plant."
+ --#SUMMARY "A Humidity alarm is no longer active in the DC power plant."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 160
+
+dcBBCommunicationEstablished TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Power plant bridging board communications established."
+ --#TYPE "APC: Power plant bridging board communications established."
+ --#SUMMARY "Power plant bridging board communications established."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 161
+
+dcBBCommunicationLost TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Power plant bridging board communications lost."
+ --#TYPE "APC: Power plant bridging board communications lost."
+ --#SUMMARY "Power plant bridging board communications lost."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 162
+
+iemHighTempThresholdViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { iemStatusProbeCurrentTemp, iemStatusProbeTempUnits, iemStatusProbeNumber,
+ iemStatusProbeName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: High temperature threshold violated on Integrated
+ Environmental Monitor probe. The first variable is the
+ current temperature. The second variable is the temperature
+ scale. The third variable is the probe number. The fourth
+ variable is the probe name."
+ --#TYPE "APC IEM: High temperature threshold violation."
+ --#SUMMARY "High temperature threshold violation."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 163
+
+iemHighTempThresholdViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { iemStatusProbeNumber, iemStatusProbeName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: High temperature threshold violated on Integrated
+ Environmental Monitor probe has been cleared. The first variable
+ is the probe number. The second variable is the probe name."
+ --#TYPE "APC IEM: High temperature threshold violation cleared."
+ --#SUMMARY "High temperature threshold violation has been cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 164
+
+iemLowTempThresholdViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { iemStatusProbeCurrentTemp, iemStatusProbeTempUnits, iemStatusProbeNumber,
+ iemStatusProbeName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Low temperature threshold violated on integrated
+ probe. The first variable is the current temperature. The
+ second variable is the temperature scale. The third
+ variable is the probe number. The fourth variable is the
+ probe name."
+ --#TYPE "APC IEM: Low temperature threshold violation."
+ --#SUMMARY "Low temperature threshold violation."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 165
+
+iemLowTempThresholdViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { iemStatusProbeNumber, iemStatusProbeName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Low temperature threshold violated on integrated
+ probe has been cleared. The first variable is the probe number.
+ The second variable is the probe name."
+ --#TYPE "APC IEM: Low temperature threshold violation cleared."
+ --#SUMMARY "Low temperature threshold violation has been cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 166
+
+iemHighHumidThresholdViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { iemStatusProbeCurrentHumid, iemStatusProbeNumber, iemStatusProbeName,
+ mtrapargsString }
+ DESCRIPTION
+ "SEVERE: High humidity threshold violated on integrated
+ probe. The first variable is the current humidity. The
+ second variable is the probe number. The third variable
+ is the probe name."
+ --#TYPE "APC IEM: High humidity threshold violation."
+ --#SUMMARY "High humidity threshold violation."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 167
+
+iemHighHumidThresholdViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { iemStatusProbeNumber, iemStatusProbeName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: High humidity threshold violated on integrated
+ probe cleared. The first variable is the probe number. The second
+ variable is the probe name."
+ --#TYPE "APC IEM: High humidity threshold violation cleared."
+ --#SUMMARY "High humidity threshold violation has been cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 168
+
+iemLowHumidThresholdViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { iemStatusProbeCurrentHumid, iemStatusProbeNumber, iemStatusProbeName,
+ mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Low humidity threshold violated on integrated
+ probe. The first variable is the current humidity. The
+ second variable is the probe number. The third variable
+ is the probe name."
+ --#TYPE "APC IEM: Low humidity threshold violation."
+ --#SUMMARY "Low humidity threshold violation."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 169
+
+iemLowHumidThresholdViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { iemStatusProbeNumber, iemStatusProbeName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Low humidity threshold violated on integrated
+ probe cleared. The first variable is the probe number. The second
+ variable is the probe name."
+ --#TYPE "APC IEM: Low humidity threshold violation cleared."
+ --#SUMMARY "Low humidity threshold violation has been cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 170
+
+iemProbeDisconnected TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: The temperature/humidity probe on the Integrated
+ Environmental Monitor has been disconnected. This trap is
+ generated when a probe that has been in communication with
+ the Environmental Monitor has been disconnected or can no
+ longer communicate."
+ --#TYPE "APC IEM: Probe disconnected."
+ --#SUMMARY "Probe has been disconnected."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 171
+
+iemProbeConnected TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The temperature/humidity probe on the Integrated
+ Environmental Monitor has been connected. This trap is generated
+ when the Environmental Monitor establishes communication with a
+ probe that had previously not been connected."
+ --#TYPE "APC IEM: Probe Connected."
+ --#SUMMARY "Probe has been connected."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 172
+
+iemContactFault TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { iemStatusContactNumber, iemStatusContactName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: There is a contact fault on the Integrated
+ Environmental Monitor. The first argument is the number
+ of the contact. The second argument is the name of the
+ contact."
+ --#TYPE "APC IEM: Contact fault."
+ --#SUMMARY "Contact fault."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 173
+
+iemContactFaultCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { iemStatusContactNumber, iemStatusContactName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The contact fault on the Integrated
+ Environmental Monitor has been cleared. The first
+ argument is the number of the contact. The second
+ argument is the name of the contact."
+ --#TYPE "APC IEM: Contact fault."
+ --#SUMMARY "Contact fault cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 174
+
+iemRelayFault TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { iemStatusRelayNumber, iemStatusRelayName, mtrapargsString02, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The output relay on the Integrated Environmental
+ Monitor has switched to the fault state. The first
+ argument is the number of the output relay. The second
+ argument is the name of the output relay. The third
+ argument is the event that caused the fault."
+ --#TYPE "APC IEM: Output relay fault."
+ --#SUMMARY "Output relay has faulted."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 175
+
+iemRelayFaultCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { iemStatusRelayNumber, iemStatusRelayName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The fault condition on the output relay on the
+ Integrated Environmental Monitor has cleared. The first
+ argument is the number of the output relay. The second
+ argument is the name of the output relay."
+ --#TYPE "APC IEM: Output relay fault condition cleared."
+ --#SUMMARY "Output relay fault cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 176
+
+bmBatManCommEstab TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Serial Communications Established with Battery Manager."
+ --#TYPE "BatMan : Communications Established."
+ --#SUMMARY "Communications Established."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 177
+
+bmBatManCommLost TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Serial Communications Lost with Battery Manager."
+ --#TYPE "BatMan : Communications Lost."
+ --#SUMMARY "Communications Lost."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 178
+
+bmBatManKneeAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Battery Voltage Knee Threshold Alarm Detected."
+ --#TYPE "BatMan : Knee Alarm Detected."
+ --#SUMMARY "Knee Alarm Detected."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 179
+
+bmBatManKneeAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Battery Voltage Knee Threshold Alarm Cleared."
+ --#TYPE "BatMan : Knee Alarm Cleared."
+ --#SUMMARY "Knee Alarm Cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 180
+
+bmBatManChargerAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "WARNING: Charger Alarm Detected."
+ --#TYPE "BatMan : Charger Alarm Detected."
+ --#SUMMARY "Charger Alarm Detected."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 181
+
+bmBatManChargerAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Charger Alarm Cleared."
+ --#TYPE "BatMan : Charger Alarm Cleared."
+ --#SUMMARY "Charger Alarm Cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 182
+
+bmBatManBatteryAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "WARNING: Battery Alarm Detected."
+ --#TYPE "BatMan : Battery Alarm Detected."
+ --#SUMMARY "Battery Alarm Detected."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 183
+
+bmBatManBatteryAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Battery Alarm Cleared."
+ --#TYPE "BatMan : Battery Alarm Cleared."
+ --#SUMMARY "Battery Alarm Cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 184
+
+bmBatManEnvironmentAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "WARNING: Environment Alarm Detected."
+ --#TYPE "BatMan : Environment Alarm Detected."
+ --#SUMMARY "Environment Alarm Detected."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 185
+
+bmBatManEnvironmentAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Environment Alarm Cleared."
+ --#TYPE "BatMan : Environment Alarm Cleared."
+ --#SUMMARY "Environment Alarm Cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 186
+
+bmBatManMaintenanceAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Maintenance Alarm Detected."
+ --#TYPE "BatMan : Maintenance Due Alarm Detected."
+ --#SUMMARY "Maintenance Due Alarm Detected."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 187
+
+bmBatManMaintenanceAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Maintenance Alarm Cleared."
+ --#TYPE "BatMan : Maintenance Due Alarm Cleared."
+ --#SUMMARY "Maintenance Due Alarm Cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 188
+
+pduCommunicationEstablished TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Communication Established.
+ The first argument is the serial number.
+ The second argument is the device name."
+ --#TYPE "APC PDU: Communication Established."
+ --#SUMMARY "Communication Established."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 189
+
+pduCommunicationLost TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Communication Lost.
+ The first argument is the serial number.
+ The second argument is the device name."
+ --#TYPE "APC PDU: Communication Lost."
+ --#SUMMARY "Communication Lost."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 190
+
+pduUtilityLineUndervoltage TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Utility Line Undervoltage.
+ The first argument is the serial number.
+ The second argument is the device name.
+ The third argument is the phase number."
+ --#TYPE "APC PDU: Utility Line Undervoltage."
+ --#SUMMARY "Utility Line Undervoltage."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 191
+
+pduUtilityLineUndervoltageCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Utility Line Undervoltage Cleared.
+ The first argument is the serial number.
+ The second argument is the device name.
+ The third argument is the phase number."
+ --#TYPE "APC PDU: Utility Line Undervoltage Cleared."
+ --#SUMMARY "Utility Line Undervoltage Cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 192
+
+pduUtilityLineOvervoltage TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Utility Line Overvoltage.
+ The first argument is the serial number.
+ The second argument is the device name.
+ The third argument is the phase number."
+ --#TYPE "APC PDU: Utility Line Overvoltage."
+ --#SUMMARY "Utility Line Overvoltage."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 193
+
+pduUtilityLineOvervoltageCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Utility Line Overvoltage Cleared.
+ The first argument is the serial number.
+ The second argument is the device name.
+ The third argument is the phase number."
+ --#TYPE "APC PDU: Utility Line Overvoltage Cleared."
+ --#SUMMARY "Utility Line Overvoltage Cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 194
+
+pduGroundOvercurrent TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Ground Overcurrent.
+ The first argument is the serial number.
+ The second argument is the device name."
+ --#TYPE "APC PDU: Ground Overcurrent."
+ --#SUMMARY "Ground Overcurrent."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 195
+
+pduGroundOvercurrentCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Ground Overcurrent Cleared.
+ The first argument is the serial number.
+ The second argument is the device name."
+ --#TYPE "APC PDU: Ground Overcurrent Cleared."
+ --#SUMMARY "Ground Overcurrent Cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 196
+
+pduCircuitPanelInputUndervoltage TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Circuit Panel Input Undervoltage.
+ The first argument is the serial number.
+ The second argument is the device name.
+ The third argument is the phase number."
+ --#TYPE "APC PDU: Circuit Panel Input Undervoltage."
+ --#SUMMARY "Circuit Panel Input Undervoltage."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 197
+
+pduCircuitPanelInputUndervoltageCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Circuit Panel Input Undervoltage Cleared.
+ The first argument is the serial number.
+ The second argument is the device name.
+ The third argument is the phase number."
+ --#TYPE "APC PDU: Circuit Panel Input Undervoltage Cleared."
+ --#SUMMARY "Circuit Panel Input Undervoltage Cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 198
+
+pduCircuitPanelInputOvervoltage TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Circuit Panel Input Overvoltage.
+ The first argument is the serial number.
+ The second argument is the device name.
+ The third argument is the phase number."
+ --#TYPE "APC PDU: Circuit Panel Input Overvoltage."
+ --#SUMMARY "Circuit Panel Input Overvoltage."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 199
+
+pduCircuitPanelInputOvervoltageCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Circuit Panel Input Overvoltage Cleared.
+ The first argument is the serial number.
+ The second argument is the device name.
+ The third argument is the phase number."
+ --#TYPE "APC PDU: Circuit Panel Input Overvoltage Cleared."
+ --#SUMMARY "Circuit Panel Input Overvoltage Cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 200
+
+pduCircuitPanelInputUndercurrent TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Circuit Panel Input Undercurrent.
+ The first argument is the serial number.
+ The second argument is the device name.
+ The third argument is the phase number."
+ --#TYPE "APC PDU: Circuit Panel Input Undercurrent."
+ --#SUMMARY "Circuit Panel Input Undercurrent."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 201
+
+pduCircuitPanelInputUndercurrentCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Circuit Panel Input Undercurrent Cleared.
+ The first argument is the serial number.
+ The second argument is the device name.
+ The third argument is the phase number."
+ --#TYPE "APC PDU: Circuit Panel Input Undercurrent Cleared."
+ --#SUMMARY "Circuit Panel Input Undercurrent Cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 202
+
+pduCircuitPanelInputOvercurrent TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Circuit Panel Input Overcurrent.
+ The first argument is the serial number.
+ The second argument is the device name.
+ The third argument is the phase number."
+ --#TYPE "APC PDU: Circuit Panel Input Overcurrent."
+ --#SUMMARY "Circuit Panel Input Overcurrent."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 203
+
+pduCircuitPanelInputOvercurrentCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Circuit Panel Input Overcurrent Cleared.
+ The first argument is the serial number.
+ The second argument is the device name.
+ The third argument is the phase number."
+ --#TYPE "APC PDU: Circuit Panel Input Overcurrent Cleared."
+ --#SUMMARY "Circuit Panel Input Overcurrent Cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 204
+
+pduCircuitPanelFrequencyOutOfRange TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Circuit Panel Input Frequency Out Of Range.
+ The first argument is the serial number.
+ The second argument is the device name."
+ --#TYPE "APC PDU: Circuit Panel Input Frequency Out Of Range."
+ --#SUMMARY "Circuit Panel Input Frequency Out Of Range."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 205
+
+pduCircuitPanelFrequencyOutofRangeCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Circuit Panel Input Frequency No Longer Out Of Range.
+ The first argument is the serial number.
+ The second argument is the device name."
+ --#TYPE "APC PDU: Circuit Panel Input Frequency No Longer Out Of Range."
+ --#SUMMARY "Circuit Panel Input Frequency No Longer Out Of Range."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 206
+
+pduCircuitPanelNeutralOvercurrent TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Circuit Panel Input Neutral Overcurrent.
+ The first argument is the serial number.
+ The second argument is the device name."
+ --#TYPE "APC PDU: Circuit Panel Input Neutral Overcurrent."
+ --#SUMMARY "Circuit Panel Input Neutral Overcurrent."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 207
+
+pduCircuitPanelNeutralOvercurrentCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Circuit Panel Input Neutral Overcurrent Cleared.
+ The first argument is the serial number.
+ The second argument is the device name."
+ --#TYPE "APC PDU: Circuit Panel Input Neutral Overcurrent Cleared."
+ --#SUMMARY "Circuit Panel Input Neutral Overcurrent Cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 208
+
+pduSystemOff TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: PDU System Off.
+ The first argument is the serial number.
+ The second argument is the device name."
+ --#TYPE "APC PDU: System Off."
+ --#SUMMARY "PDU System Off."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 209
+
+pduOnBatteryMode TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: PDU is in On Battery Mode.
+ The first argument is the serial number.
+ The second argument is the device name."
+ --#TYPE "APC PDU: On Battery Mode."
+ --#SUMMARY "PDU is in On Battery Mode."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 210
+
+pduMaintenanceBypassMode TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: PDU is in Maintenance Bypass Mode.
+ The first argument is the serial number.
+ The second argument is the device name."
+ --#TYPE "APC PDU: Maintenance Bypass Mode."
+ --#SUMMARY "PDU is in Maintenance Bypass Mode."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 211
+
+pduAtypicalBypassMode TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsString }
+ DESCRIPTION
+ "WARNING: PDU is in Atypical Bypass Mode.
+ The first argument is the serial number.
+ The second argument is the device name."
+ --#TYPE "APC PDU: Atypical Bypass Mode."
+ --#SUMMARY "PDU is in Atypical Bypass Mode."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 212
+
+pduNoPanelFeedMode TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: PDU is in No Panel Feed Mode.
+ The first argument is the serial number.
+ The second argument is the device name."
+ --#TYPE "APC PDU: No Panel Feed Mode."
+ --#SUMMARY "PDU is in No Panel Feed Mode."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 213
+
+pduUpsOperationMode TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: PDU is in Ups Operation Mode.
+ The first argument is the serial number.
+ The second argument is the device name."
+ --#TYPE "APC PDU: Ups Operation Mode."
+ --#SUMMARY "PDU is in Ups Operation Mode."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 214
+
+pduForcedBypassMode TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsString }
+ DESCRIPTION
+ "WARNING: PDU is in Forced Bypass Mode.
+ The first argument is the serial number.
+ The second argument is the device name."
+ --#TYPE "APC PDU: Forced Bypass Mode."
+ --#SUMMARY "PDU is in Forced Bypass Mode."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 215
+
+pduInputTransformerOverTemperature TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Input Transformer Over Temperature.
+ The first argument is the serial number.
+ The second argument is the device name."
+ --#TYPE "APC PDU: Input Transformer Over Temperature."
+ --#SUMMARY "Input Transformer Over Temperature."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 216
+
+pduInputTransformerOverTemperatureCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Input Transformer Over Temperature Cleared.
+ The first argument is the serial number.
+ The second argument is the device name."
+ --#TYPE "APC PDU: Input Transformer Over Temperature Cleared."
+ --#SUMMARY "Input Transformer Over Temperature Cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 217
+
+pduUPSInputVoltageLost TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: UPS Input Voltage phase-N Lost.
+ The first argument is the serial number.
+ The second argument is the device name.
+ The third argument is the phase number."
+ --#TYPE "APC PDU: UPS Input Voltage phase-N Lost."
+ --#SUMMARY "UPS Input Voltage phase-N Lost."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 218
+
+pduUPSInputVoltageRestored TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: UPS Input Voltage phase-N Restored.
+ The first argument is the serial number.
+ The second argument is the device name.
+ The third argument is the phase number."
+ --#TYPE "APC PDU: UPS Input Voltage phase-N Restored."
+ --#SUMMARY "UPS Input Voltage phase-N Restored."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 219
+
+pduContactFault TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: A contact closure in the PDU is in an abnormal position.
+ The first argument is the serial number.
+ The second argument is the device name.
+ The third argument is the number of the contact."
+ --#TYPE "APC PDU: Contact Abnormal."
+ --#SUMMARY "Contact Abnormal."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 220
+
+pduContactFaultCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A contact closure in the PDU is in a normal position.
+ The first argument is the serial number.
+ The second argument is the device name.
+ The third argument is the number of the contact."
+ --#TYPE "APC PDU: Contact Normal."
+ --#SUMMARY "Contact Normal."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 221
+
+rPDUBankPhaseLowLoad TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
+ rPDULoadStatusBankNumber, rPDULoadStatusPhaseNumber, mtrapargsString }
+ DESCRIPTION
+ "WARNING: A bank or phase on the Rack PDU has violated the low load threshold.
+ The first argument is the serial number.
+ The second argument is the device name.
+ The third argument is the bank number (0 if this is phase data).
+ The fourth argument is the phase number (0 if this is bank data)."
+ --#TYPE "APC Rack PDU: Violation of bank or phase low load threshold."
+ --#SUMMARY "A bank or phase on the Rack PDU has violated the low load threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 222
+
+rPDUBankPhaseLowLoadCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
+ rPDULoadStatusBankNumber, rPDULoadStatusPhaseNumber, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The bank or phase low load condition on a Rack PDU has been
+ cleared.
+ The first argument is the serial number.
+ The second argument is the device name.
+ The third argument is the bank number (0 if this is phase data).
+ The fourth argument is the phase number (0 if this is bank data)."
+ --#TYPE "APC Rack PDU: Bank or phase low load condition cleared."
+ --#SUMMARY "The bank or phase low load condition on a Rack PDU has been cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 223
+
+rPDUBankPhaseNearOverload TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
+ rPDULoadStatusBankNumber, rPDULoadStatusPhaseNumber, mtrapargsString }
+ DESCRIPTION
+ "WARNING: A bank or phase of the Rack PDU is near an overload condition.
+ The first argument is the serial number.
+ The second argument is the device name.
+ The third argument is the bank number (0 if this is phase data).
+ The fourth argument is the phase number (0 if this is bank data)."
+ --#TYPE "APC Rack PDU: Bank or phase near an overload condition."
+ --#SUMMARY "A bank or phase of the Rack PDU is near an overload condition."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 224
+
+rPDUBankPhaseNearOverloadCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
+ rPDULoadStatusBankNumber, rPDULoadStatusPhaseNumber, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The bank or phase near overload condition on a Rack PDU has
+ been cleared.
+ The first argument is the serial number.
+ The second argument is the device name.
+ The third argument is the bank number (0 if this is phase data).
+ The fourth argument is the phase number (0 if this is bank data)."
+ --#TYPE "APC Rack PDU: Bank or phase near overload condition has cleared."
+ --#SUMMARY "Rack PDU bank or phase near overload condition has cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 225
+
+rPDUBankPhaseOverload TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
+ rPDULoadStatusBankNumber, rPDULoadStatusPhaseNumber, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: A bank or phase of the Rack PDU is in an overload condition.
+ The first argument is the serial number.
+ The second argument is the device name.
+ The third argument is the phase number.
+ The third argument is the bank number (0 if this is phase data).
+ The fourth argument is the phase number (0 if this is bank data)."
+ --#TYPE "APC Rack PDU: Bank or phase overload condition."
+ --#SUMMARY "A bank or phase of the Rack PDU is in an overload condition."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 226
+
+rPDUBankPhaseOverloadCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
+ rPDULoadStatusBankNumber, rPDULoadStatusPhaseNumber, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The bank or phase overload condition on a Rack PDU has been
+ cleared.
+ The first argument is the serial number.
+ The second argument is the device name.
+ The third argument is the bank number (0 if this is phase data).
+ The fourth argument is the phase number (0 if this is bank data)."
+ --#TYPE "APC Rack PDU: Bank or phase overload condition has cleared."
+ --#SUMMARY "The bank or phase overload condition on a Rack PDU has cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 227
+
+aruDeviceConfigChange TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
+ rARUStatusAruIndex, rARUStatusAruName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Remote ARU Device Configuration change.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the ARU number.
+ The fourth argument is the ARU name."
+ --#TYPE "APC ARU: ARU Device configuration change."
+ --#SUMMARY "ARU device configuration change."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 228
+
+rmPDUCommunicationLost TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString03, mtrapargsString02, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Communication Lost.
+ The first argument is the serial number.
+ The second argument is the device name."
+ --#TYPE "APC RM PDU: Communication Lost."
+ --#SUMMARY "Communication Lost."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 229
+
+emsCommunicationEstablished TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Communication Established.
+ The first argument is the serial number.
+ The second argument is the device name."
+ --#TYPE "APC EMS: Communication Established."
+ --#SUMMARY "Communication Established."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 230
+
+emsCommunicationLost TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Communication Lost.
+ The first argument is the serial number.
+ The second argument is the device name."
+ --#TYPE "APC EMS: Communication Lost."
+ --#SUMMARY "Communication Lost."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 231
+
+emsProbeConnected TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
+ emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A probe has been connected to the EMS.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the probe number.
+ The fourth argument is the probe name."
+ --#TYPE "APC EMS: Probe Connected."
+ --#SUMMARY "Probe Connected."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 232
+
+emsProbeDisconnected TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
+ emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: A probe has been disconnected from the EMS.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the probe number.
+ The fourth argument is the probe name."
+ --#TYPE "APC EMS: Probe Disconnected."
+ --#SUMMARY "Probe Disconnected."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 233
+
+emsSensorConnected TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
+ emsSensorStatusSensorIndex, emsSensorStatusSensorName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A sensor has been connected to the EMS.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the sensor number.
+ The fourth argument is the sensor name."
+ --#TYPE "APC EMS: Sensor Connected."
+ --#SUMMARY "Sensor Connected."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 234
+
+emsSensorDisconnected TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
+ emsSensorStatusSensorIndex, emsSensorStatusSensorName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: A sensor has been disconnected from the EMS.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the sensor number.
+ The fourth argument is the sensor name."
+ --#TYPE "APC EMS: Sensor Disconnected."
+ --#SUMMARY "Sensor Disconnected."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 235
+
+emsSensorFault TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
+ emsSensorStatusSensorIndex, emsSensorStatusSensorName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: A EMS sensor is in the fault condition.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the sensor number.
+ The fourth argument is the sensor name."
+ --#TYPE "APC EMS: Sensor Fault."
+ --#SUMMARY "Sensor Fault."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 236
+
+emsSensorFaultCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
+ emsSensorStatusSensorIndex, emsSensorStatusSensorName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A EMS sensor fault condition has cleared.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the sensor number.
+ The fourth argument is the sensor name."
+ --#TYPE "APC EMS: Sensor Fault Cleared."
+ --#SUMMARY "Sensor Fault Cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 237
+
+emsBeaconConnected TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A beacon has been connected to the EMS.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC EMS: Beacon Connected."
+ --#SUMMARY "Beacon Connected."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 238
+
+emsBeaconDisconnected TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: A beacon has been disconnected from the EMS.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC EMS: Beacon Disconnected."
+ --#SUMMARY "Beacon Disconnected."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 239
+
+emsBeaconOn TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A EMS beacon has gone on.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC EMS: Beacon On."
+ --#SUMMARY "Beacon On."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 240
+
+emsBeaconOff TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A EMS beacon has gone off.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC EMS: Beacon Off."
+ --#SUMMARY "Beacon Off."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 241
+
+emsMajorAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: A Major Alarm is present in the EMS.
+ The first argument is the EMS serial number.
+ The second argument is the EMS name."
+ --#TYPE "APC EMS: Major Alarm."
+ --#SUMMARY "Major Alarm."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 242
+
+emsMajorAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A Major Alarm condition has been cleared in the EMS.
+ The first argument is the EMS serial number.
+ The second argument is the EMS name."
+ --#TYPE "APC EMS: Major Alarm Cleared."
+ --#SUMMARY "Major Alarm Cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 243
+
+emsMinorAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: A Minor Alarm is present in the EMS.
+ The first argument is the EMS serial number.
+ The second argument is the EMS name."
+ --#TYPE "APC EMS: Minor Alarm."
+ --#SUMMARY "Minor Alarm."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 244
+
+emsMinorAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A Minor Alarm condition has been cleared in the EMS.
+ The first argument is the EMS serial number.
+ The second argument is the EMS name."
+ --#TYPE "APC EMS: Minor Alarm Cleared."
+ --#SUMMARY "Minor Alarm Cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 245
+
+emsOutletStateAbnormal TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsOutletStatusOutletIndex, emsOutletStatusOutletName,
+ emsOutletStatusOutletState, emsOutletStatusOutletNormalState, mtrapargsString }
+ DESCRIPTION
+ "WARNING: An outlet on the EMS has changed to its abnormal state.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the outlet number.
+ The fourth argument is the outlet name.
+ The fifth argument is the current outlet state (1=ON, 2=OFF).
+ The sixth argument is the configured normal outlet state (1=ON, 2=OFF)."
+ --#TYPE "APC EMS: Outlet has changed to its abnormal state."
+ --#SUMMARY "Outlet has changed to its abnormal state."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 246
+
+emsOutletStateNormal TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsOutletStatusOutletIndex, emsOutletStatusOutletName,
+ emsOutletStatusOutletState, emsOutletStatusOutletNormalState, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: An outlet on the EMS has changed to its normal state.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the outlet number.
+ The fourth argument is the outlet name.
+ The fifth argument is the current outlet state (1=ON, 2=OFF).
+ The sixth argument is the configured normal outlet state (1=ON, 2=OFF)."
+ --#TYPE "APC EMS: Outlet has changed to its normal state."
+ --#SUMMARY "Outlet has changed to its normal state."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 247
+
+emsInputContactStateAbnormal TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsInputContactStatusInputContactIndex,
+ emsInputContactStatusInputContactName, emsInputContactStatusInputContactState,
+ emsInputContactStatusInputContactNormalState, mtrapargsString }
+ DESCRIPTION
+ "WARNING: An input contact on the EMS has changed to its abnormal state.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the input contact number.
+ The fourth argument is the input contact name.
+ The fifth argument is the input contact state (1=CLOSED, 2=OPEN).
+ The sixth argument is the configured normal input contact state (1=CLOSED, 2=OPEN)."
+ --#TYPE "APC EMS: Input contact has changed to its abnormal state."
+ --#SUMMARY "Input contact has changed to its abnormal state."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 248
+
+emsInputContactStateNormal TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsInputContactStatusInputContactIndex,
+ emsInputContactStatusInputContactName, emsInputContactStatusInputContactState,
+ emsInputContactStatusInputContactNormalState, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: An input contact on the EMS has changed to its normal state.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the input contact number.
+ The fourth argument is the input contact name.
+ The fifth argument is the input contact state (1=CLOSED, 2=OPEN).
+ The sixth argument is the configured normal input contact state (1=CLOSED, 2=OPEN)."
+ --#TYPE "APC EMS: Input contact has changed to its normal state."
+ --#SUMMARY "Input contact has changed to its normal state."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 249
+
+emsOutputRelayStateAbnormal TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsOutputRelayStatusOutputRelayIndex,
+ emsOutputRelayStatusOutputRelayName, emsOutputRelayStatusOutputRelayState,
+ emsOutputRelayStatusOutputRelayNormalState, mtrapargsString }
+ DESCRIPTION
+ "WARNING: An output relay on the EMS has changed to its abnormal state.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the output relay number.
+ The fourth argument is the output relay name.
+ The fifth argument is the current output relay state (1=CLOSED, 2=OPEN).
+ The sixth argument is the configured normal output relay state (1=CLOSED, 2=OPEN)."
+ --#TYPE "APC EMS: Output Relay has changed to its abnormal state."
+ --#SUMMARY "Output Relay has changed to its abnormal state."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 250
+
+emsOutputRelayStateNormal TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsOutputRelayStatusOutputRelayIndex,
+ emsOutputRelayStatusOutputRelayName, emsOutputRelayStatusOutputRelayState,
+ emsOutputRelayStatusOutputRelayNormalState, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: An output relay on the EMS has changed to its normal state.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the output relay number.
+ The fourth argument is the output relay name.
+ The fifth argument is the current output relay state (1=CLOSED, 2=OPEN).
+ The sixth argument is the configured normal output relay state (1=CLOSED, 2=OPEN)."
+ --#TYPE "APC EMS: Output Relay has changed to its normal state."
+ --#SUMMARY "Output Relay has changed to its normal state."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 251
+
+emsDeviceConfigChange TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A device configuration change has been made on the EMS.
+ The first argument is the EMS serial number.
+ The second argument is the EMS name."
+ --#TYPE "APC: A device configuration change on a EMS."
+ --#SUMMARY "A device configuration change has been made on a EMS."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 252
+
+envHighTempThresholdViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeTemperature, emsStatusSysTempUnits,
+ emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: High temperature threshold violated on the probe.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the current temperature.
+ The fourth argument is the temperature scale.
+ The fifth argument is the probe number.
+ The sixth argument is the probe name."
+ --#TYPE "APC ENV: High temperature threshold violation."
+ --#SUMMARY "High temperature threshold violation."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 253
+
+envHighTempThresholdViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeTemperature, emsStatusSysTempUnits,
+ emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: High temperature threshold violation cleared on the probe.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the current temperature.
+ The fourth argument is the temperature scale.
+ The fifth argument is the probe number.
+ The sixth argument is the probe name."
+ --#TYPE "APC ENV: High temperature threshold violation cleared."
+ --#SUMMARY "High temperature threshold violation cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 254
+
+envLowTempThresholdViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeTemperature, emsStatusSysTempUnits,
+ emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Low temperature threshold violated on the probe.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the current temperature.
+ The fourth argument is the temperature scale.
+ The fifth argument is the probe number.
+ The sixth argument is the probe name."
+ --#TYPE "APC ENV: Low temperature threshold violation."
+ --#SUMMARY "Low temperature threshold violation."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 255
+
+envLowTempThresholdViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeTemperature, emsStatusSysTempUnits,
+ emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Low temperature threshold violation cleared on the probe.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the current temperature.
+ The fourth argument is the temperature scale.
+ The fifth argument is the probe number.
+ The sixth argument is the probe name."
+ --#TYPE "APC ENV: Low temperature threshold violation cleared."
+ --#SUMMARY "Low temperature threshold violation cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 256
+
+envHighHumidityThresholdViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeHumidity,
+ emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: High humidity threshold violated on the probe.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the current humidity
+ The fourth argument is the probe number.
+ The fifth argument is the probe name."
+ --#TYPE "APC ENV: High humidity threshold violation."
+ --#SUMMARY "High humidity threshold violation."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 257
+
+envHighHumidityThresholdViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeHumidity,
+ emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: High humidity threshold violation cleared on the probe.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the current humidity.
+ The fourth argument is the probe number.
+ The fifth argument is the probe name."
+ --#TYPE "APC ENV: High humidity threshold violation cleared."
+ --#SUMMARY "High humidity threshold violation cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 258
+
+envLowHumidityThresholdViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeHumidity,
+ emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Low humidity threshold violated on the probe.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the current humidity
+ The fourth argument is the probe number.
+ The fifth argument is the probe name."
+ --#TYPE "APC ENV: Low humidity threshold violation."
+ --#SUMMARY "Low humidity threshold violation."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 259
+
+envLowHumidityThresholdViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeHumidity,
+ emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Low humidity threshold violation cleared on the probe.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the current humidity.
+ The fourth argument is the probe number.
+ The fifth argument is the probe name."
+ --#TYPE "APC ENV: Low humidity threshold violation cleared."
+ --#SUMMARY "Low humidity threshold violation cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 260
+
+
+-- Switched and Metered Rack PDU Traps
+
+rPDUCommunicationEstablished TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { rPDUIdentSerialNumber, rPDUIdentName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Communication with a Rack PDU has been established.
+ The first argument is the serial number.
+ The second argument is the device name."
+ --#TYPE "APC Rack PDU: Communication established."
+ --#SUMMARY "Communication with a Rack PDU established."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 266
+
+rPDUCommunicationLost TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { rPDUIdentSerialNumber, rPDUIdentName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Communication with a Rack PDU has been lost.
+ The first argument is the serial number.
+ The second argument is the device name."
+ --#TYPE "APC Rack PDU: Communication lost."
+ --#SUMMARY "Communication with a Rack PDU has been lost."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 267
+
+rPDUOutletOn TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
+ rPDUOutletControlIndex, rPDUOutletControlOutletName,
+ mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: An outlet on a Switched Rack PDU has turned on.
+ The first argument is the serial number.
+ The second argument is the device name.
+ The third argument is the outlet index number.
+ The fourth argument is the outlet name."
+ --#TYPE "APC Switched Rack PDU: An outlet has turned on."
+ --#SUMMARY "An outlet on a Switched Rack PDU has turned on."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 268
+
+rPDUOutletOff TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
+ rPDUOutletControlIndex, rPDUOutletControlOutletName,
+ mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: An outlet on a Switched Rack PDU has turned off.
+ The first argument is the serial number.
+ The second argument is the device name.
+ The third argument is the outlet index number.
+ The fourth argument is the outlet name."
+ --#TYPE "APC Switched Rack PDU: An outlet has turned off."
+ --#SUMMARY "An outlet on a Switched Rack PDU has turned off."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 269
+
+rPDUDeviceConfigChange TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { rPDUIdentSerialNumber, rPDUIdentName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A device configuration change has been made on a
+ Rack PDU.
+ The first argument is the serial number.
+ The second argument is the device name."
+ --#TYPE "APC Rack PDU: Device configuration change made."
+ --#SUMMARY "Device configuration change has been made on a Rack PDU."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 270
+
+rPDUOutletConfigChange TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
+ rPDUOutletControlIndex, rPDUOutletControlOutletName,
+ mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: An outlet configuration change has been made on a
+ Switched Rack PDU.
+ The first argument is the serial number.
+ The second argument is the device name.
+ The third argument is the outlet index number.
+ The fourth argument is the outlet name."
+ --#TYPE "APC Switched Rack PDU: Outlet configuration change made."
+ --#SUMMARY "Outlet configuration change has been made on a Switched Rack PDU."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 271
+
+rPDULowLoad TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
+ rPDULoadStatusPhaseNumber, mtrapargsString }
+ DESCRIPTION
+ "WARNING: A Rack PDU has violated the low load threshold.
+ The first argument is the serial number.
+ The second argument is the device name.
+ The third argument is the phase number."
+ --#TYPE "APC Rack PDU: Violation of low load threshold."
+ --#SUMMARY "A Rack PDU has violated the low load threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 272
+
+rPDULowLoadCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
+ rPDULoadStatusPhaseNumber, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The low load condition on a Rack PDU has been
+ cleared.
+ The first argument is the serial number.
+ The second argument is the device name.
+ The third argument is the phase number."
+ --#TYPE "APC Rack PDU: Low load condition cleared."
+ --#SUMMARY "The low load condition on a Rack PDU has been cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 273
+
+rPDUNearOverload TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
+ rPDULoadStatusPhaseNumber, mtrapargsString }
+ DESCRIPTION
+ "WARNING: A Rack PDU is near an overload condition.
+ The first argument is the serial number.
+ The second argument is the device name.
+ The third argument is the phase number."
+ --#TYPE "APC Rack PDU: Near an overload condition."
+ --#SUMMARY "A Rack PDU is near an overload condition."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 274
+
+rPDUNearOverloadCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
+ rPDULoadStatusPhaseNumber, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The near overload condition on a Rack PDU has
+ been cleared.
+ The first argument is the serial number.
+ The second argument is the device name.
+ The third argument is the phase number."
+ --#TYPE "APC Rack PDU: Near overload condition has cleared."
+ --#SUMMARY "Rack PDU near overload condition has cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 275
+
+rPDUOverload TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
+ rPDULoadStatusPhaseNumber, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: A Rack PDU is in an overload condition.
+ The first argument is the serial number.
+ The second argument is the device name.
+ The third argument is the phase number."
+ --#TYPE "APC Rack PDU: Overload condition."
+ --#SUMMARY "A Rack PDU is in an overload condition."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 276
+
+rPDUOverloadCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
+ rPDULoadStatusPhaseNumber, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The overload condition on a Rack PDU has been
+ cleared.
+ The first argument is the serial number.
+ The second argument is the device name.
+ The third argument is the phase number."
+ --#TYPE "APC Rack PDU: Overload condition has cleared."
+ --#SUMMARY "The overload condition on a Rack PDU has cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 277
+
+rPDUPowerSupply1Fail TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { rPDUIdentSerialNumber, rPDUIdentName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Power Supply 1 on Rack PDU is in FAIL state.
+ The first argument is the serial number.
+ The second argument is the device name."
+ --#TYPE "APC Rack PDU: Power Supply 1 is in FAIL state."
+ --#SUMMARY "Power Supply 1 on Rack PDU is in FAIL state."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 278
+
+rPDUPowerSupply1Ok TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { rPDUIdentSerialNumber, rPDUIdentName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Power Supply 1 on Rack PDU is operating normally.
+ The first argument is the serial number.
+ The second argument is the device name."
+ --#TYPE "APC Rack PDU: Power Supply 1 is operating normally."
+ --#SUMMARY "Power Supply 1 on Rack PDU is operating normally."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 279
+
+rPDUPowerSupply2Fail TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { rPDUIdentSerialNumber, rPDUIdentName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Power Supply 2 on Rack PDU is in FAIL state.
+ The first argument is the serial number.
+ The second argument is the device name."
+ --#TYPE "APC Rack PDU: Power Supply 2 is in FAIL state."
+ --#SUMMARY "Power Supply 2 on Rack PDU is in FAIL state."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 280
+
+rPDUPowerSupply2Ok TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { rPDUIdentSerialNumber, rPDUIdentName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Power Supply 2 on Rack PDU is operating normally.
+ The first argument is the serial number.
+ The second argument is the device name."
+ --#TYPE "APC Rack PDU: Power Supply 2 is operating normally."
+ --#SUMMARY "Power Supply 2 on Rack PDU is operating normally."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 281
+
+rPDUPhaseConfigChange TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
+ rPDULoadPhaseConfigIndex, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A phase configuration change has been made on a
+ Rack PDU.
+ The first argument is the serial number.
+ The second argument is the device name.
+ The third argument is the phase index number."
+ --#TYPE "APC Rack PDU: Phase configuration change made."
+ --#SUMMARY "Phase configuration change has been made on a Rack PDU."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 282
+
+rPDUCancelPendingCommand TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
+ rPDUOutletControlIndex, rPDUOutletControlOutletName,
+ mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A cancel pending command has been made on a
+ Switched Rack PDU.
+ The first argument is the serial number.
+ The second argument is the device name.
+ The third argument is the outlet index number (0 indicates all outlets).
+ The fourth argument is the outlet name (or device name if all outlets)."
+ --#TYPE "APC Switched Rack PDU: Cancel Pending Command made."
+ --#SUMMARY "A Cancel Pending Command has been made on a Switched Rack PDU."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 283
+
+aruAlinkCommunicationEstablished TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
+ rARUStatusAruIndex, rARUStatusAruName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Remote ARU Communication Established.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the ARU number.
+ The fourth argument is the ARU name."
+ --#TYPE "APC ARU: Communication Established."
+ --#SUMMARY "Communication Established."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 284
+
+aruAlinkCommunicationLost TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
+ rARUStatusAruIndex, rARUStatusAruName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Remote ARU Communication Lost.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the ARU number.
+ The fourth argument is the ARU name."
+ --#TYPE "APC ARU: Communication Lost."
+ --#SUMMARY "Communication Lost."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 285
+
+aruFanFail TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
+ rARUStatusAruIndex, rARUStatusAruName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Remote ARU Fan Fail.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the ARU number.
+ The fourth argument is the ARU name."
+ --#TYPE "APC ARU: Fan Failure."
+ --#SUMMARY "Fan Fail."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 286
+
+aruFanFailCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
+ rARUStatusAruIndex, rARUStatusAruName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Remote ARU Fan Fail Cleared.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the ARU number.
+ The fourth argument is the ARU name."
+ --#TYPE "APC ARU: Fan Fail Cleared."
+ --#SUMMARY "Fan Fail Cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 287
+
+aruSmokeAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
+ rARUStatusAruIndex, rARUStatusAruName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Remote ARU Smoke Alarm.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the ARU number.
+ The fourth argument is the ARU name."
+ --#TYPE "APC ARU: Smoke Alarm."
+ --#SUMMARY "Smoke Alarm."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 288
+
+aruSmokeAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
+ rARUStatusAruIndex, rARUStatusAruName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Remote ARU Smoke Alarm Cleared.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the ARU number.
+ The fourth argument is the ARU name."
+ --#TYPE "APC ARU: Smoke Alarm Cleared."
+ --#SUMMARY "Smoke Alarm Cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 289
+
+aruHighTemperatureAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
+ rARUStatusAruIndex, rARUStatusAruName, mtrapargsString }
+ DESCRIPTION
+ "WARNING: ARU Exhaust temperature has exceeded the override
+ threshold and the ARU has increased fan speed to
+ maintain a safe environment in the rack.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the ARU number.
+ The fourth argument is the ARU name."
+ --#TYPE "APC ARU: High Temperature Alarm."
+ --#SUMMARY "High Temperature Alarm."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 290
+
+aruHighTemperatureAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
+ rARUStatusAruIndex, rARUStatusAruName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: ARU temperature override state has been cleared.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the ARU number.
+ The fourth argument is the ARU name."
+ --#TYPE "APC ARU: High Temperature Alarm Cleared."
+ --#SUMMARY "High Temperature Alarm Cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 291
+
+aruExhaustTemperatureAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
+ rARUStatusAruIndex, rARUStatusAruName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: ARU Extreme Exhaust Temperature Alarm.
+ The ARU is unable to control the temperature within the rack
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the ARU number.
+ The fourth argument is the ARU name."
+ --#TYPE "APC ARU: Exhaust Temperature Alarm."
+ --#SUMMARY "Exhaust Temperature Alarm."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 292
+
+aruExhaustTemperatureAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
+ rARUStatusAruIndex, rARUStatusAruName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Remote ARU Exhaust Temperature Alarm Cleared.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the ARU number.
+ The fourth argument is the ARU name."
+ --#TYPE "APC ARU: Exhaust Temperature Alarm Cleared."
+ --#SUMMARY "Exhaust Temperature Alarm Cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 293
+
+envAlinkCommunicationEstablished TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
+ emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Remote Probe Communication Established.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the probe number.
+ The fourth argument is the probe name."
+ --#TYPE "APC ENV: Communication Established."
+ --#SUMMARY "Communication Established."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 294
+
+envAlinkCommunicationLost TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
+ emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Remote Probe Communication Lost.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the probe number.
+ The fourth argument is the probe name."
+ --#TYPE "APC ENV: Communication Lost."
+ --#SUMMARY "Communication Lost."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 295
+
+emsAlinkPowerOverload TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Alink Power Overload.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC EMS: Alink Power Overload."
+ --#SUMMARY "Alink Power Overload."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 296
+
+emsAlinkPowerOverloadCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Alink Power Overload Cleared.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC EMS: Alink Power Overload Cleared."
+ --#SUMMARY "Alink Power Overload Cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 297
+
+upsOutletGroupTurnedOn TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { upsOutletGroupControlIndex, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The specified Outlet Group turned on."
+ --#TYPE "APC UPS: Outlet Group turned on."
+ --#SUMMARY "Outlet Group turned on"
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 298
+
+upsOutletGroupTurnedOff TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { upsOutletGroupControlIndex, mtrapargsString }
+ DESCRIPTION
+ "WARNING: The specified Outlet Group turned off."
+ --#TYPE "APC UPS: Outlet Group turned off."
+ --#SUMMARY "Outlet Group turned off."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 299
+
+smwCriticalCondition TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsGauge, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: A Symmetra MW UPS critical condition has been detected.
+ The first variable is the fault condition."
+ --#TYPE "APC Symmetra MW UPS: A critical condition has been detected."
+ --#SUMMARY "A critical condition has been detected."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 300
+
+smwCriticalConditionCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsGauge, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A Symmetra MW UPS critical condition has been cleared.
+ The first variable is the fault condition."
+ --#TYPE "APC Symmetra MW UPS: A critical condition has been cleared."
+ --#SUMMARY "A critical condition has been cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 301
+
+smwWarningCondition TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsGauge, mtrapargsString }
+ DESCRIPTION
+ "WARNING: A Symmetra MW UPS warning condition has been detected.
+ The first variable is the fault condition."
+ --#TYPE "APC Symmetra MW UPS: A warning condition has been detected."
+ --#SUMMARY "A warning condition has been detected."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 302
+
+smwWarningConditionCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsGauge, mtrapargsString }
+ DESCRIPTION
+ "WARNING: A Symmetra MW UPS warning condition has been cleared.
+ The first variable is the fault condition."
+ --#TYPE "APC Symmetra MW UPS: A warning condition has been cleared."
+ --#SUMMARY "A warning condition has been cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 303
+
+smwInformationalCondition TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsGauge, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A Symmetra MW UPS informational condition has been detected.
+ The first variable is the fault condition."
+ --#TYPE "APC Symmetra MW UPS: Informational condition detected."
+ --#SUMMARY "An informational condition has been detected."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 304
+
+smwInformationalConditionCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsGauge, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A Symmetra MW UPS informational condition has been cleared.
+ The first variable is the fault condition."
+ --#TYPE "APC Symmetra MW UPS: Informational condition cleared."
+ --#SUMMARY "An informational condition has been cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 305
+
+airCriticalCondition TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: An Air critical condition was detected.
+ The first variable is the error condition text message.
+ The second variable is the error number."
+ --#TYPE "APC Air: A critical condition was detected. "
+ --#SUMMARY "A critical condition was detected. "
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 306
+
+airCriticalConditionCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: An Air critical condition was cleared.
+ The first variable is the error condition text message.
+ The second variable is the error number."
+ --#TYPE "APC Air: A critical condition was cleared. "
+ --#SUMMARY "A critical condition was cleared. "
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 307
+
+airWarningCondition TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "WARNING: An Air warning condition was detected.
+ The first variable is the error condition text message.
+ The second variable is the error number."
+ --#TYPE "APC Air: A warning condition was detected. "
+ --#SUMMARY "A warning condition was detected. "
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 308
+
+airWarningConditionCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "WARNING: An Air warning condition was cleared.
+ The first variable is the error condition text message.
+ The second variable is the error number."
+ --#TYPE "APC Air: A warning condition was cleared. "
+ --#SUMMARY "A warning condition was cleared. "
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 309
+
+airInformationalCondition TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: An Air informational condition was detected.
+ The first variable is the error condition text message.
+ The second variable is the error number."
+ --#TYPE "APC Air: Informational condition detected. "
+ --#SUMMARY "An informational condition was detected. "
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 310
+
+airInformationalConditionCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: An Air informational condition was cleared.
+ The first variable is the error condition text message.
+ The second variable is the error number."
+ --#TYPE "APC Air: Informational condition was cleared. "
+ --#SUMMARY "An informational condition was cleared. "
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 311
+
+-- xPDU Traps (part 1)
+
+xPDUInputVoltageLowAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
+ mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Three-phase input voltage to the device is outside the specified limits.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N, 4=unused, 5=L1-L2, 6=L2-L3, 7=L3-L1).
+ The fourth argument is the measured voltage in tenths of Volts.
+ The fifth argument is the threshold, in tenths of Volts, from which the alarm was generated."
+ --#TYPE "APC XPDU: Main input low voltage alarm."
+ --#SUMMARY "Input voltage is below threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 312
+
+xPDUInputVoltageLowAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
+ mtrapargsInteger02, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Three-phase input voltage to the device is back within the specified limits.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N, 4=unused, 5=L1-L2, 6=L2-L3, 7=L3-L1).
+ The fourth argument is the measured voltage in tenths of Volts."
+ --#TYPE "APC XPDU: Main input low voltage alarm cleared."
+ --#SUMMARY "Main input low voltage cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 313
+
+
+xPDUInputVoltageHighAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
+ mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Three-phase input voltage to the device is outside the specified limits.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N, 4=unused, 5=L1-L2, 6=L2-L3, 7=L3-L1).
+ The fourth argument is the measured voltage in tenths of Volts.
+ The fifth argument is the threshold, in tenths of Volts, above which the alarm was generated."
+ --#TYPE "APC XPDU: Main input high voltage alarm."
+ --#SUMMARY "Main input voltage is above threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 314
+
+xPDUInputVoltageHighAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
+ mtrapargsInteger02, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Three-phase input voltage to the device is back within the specified limits.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N, 4=unused, 5=L1-L2, 6=L2-L3, 7=L3-L1).
+ The fourth argument is the measured voltage in tenths of Volts."
+ --#TYPE "APC XPDU: Main input high voltage alarm cleared."
+ --#SUMMARY "Main input high voltage alarm cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 315
+
+xPDUBypassVoltageLowAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
+ mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Three-phase bypass input voltage to the device is outside the specified limits.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N).
+ The fourth argument is the measured voltage in tenths of Volts.
+ The fifth argument is the threshold, in tenths of Volts, from which the alarm was generated."
+ --#TYPE "APC XPDU: Bypass input low voltage alarm."
+ --#SUMMARY "Bypass input voltage is below threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 316
+
+xPDUBypassVoltageLowAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
+ mtrapargsInteger02, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Three-phase bypass input voltage to the device is back within the specified limits.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N).
+ The fourth argument is the measured voltage in tenths of Volts."
+ --#TYPE "APC XPDU: Bypass input low voltage alarm cleared."
+ --#SUMMARY "Bypass input low voltage alarm cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 317
+
+xPDUBypassVoltageHighAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
+ mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Three-phase bypass input voltage to the device is outside the specified limits.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N).
+ The fourth argument is the measured voltage in tenths of Volts.
+ The fifth argument is the threshold, in tenths of Volts, above which the alarm was generated."
+ --#TYPE "APC XPDU: Bypass input high voltage alarm."
+ --#SUMMARY "Bypass input voltage is above threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 318
+
+xPDUBypassVoltageHighAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
+ mtrapargsInteger02, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Three-phase bypass input voltage to the device is back within the specified limits.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N).
+ The fourth argument is the measured voltage in tenths of Volts."
+ --#TYPE "APC XPDU: Bypass input high voltage alarm cleared."
+ --#SUMMARY "Bypass input voltage alarm cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 319
+
+xPDUOutputVoltageLowAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
+ mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The three-phase output voltage of the device is outside the specified limits.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N).
+ The fourth argument is the measured voltage in tenths of Volts.
+ The fifth argument is the threshold, in tenths of Volts, from which the alarm was generated."
+ --#TYPE "APC XPDU: Output low voltage alarm."
+ --#SUMMARY "Output voltage is below threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 320
+
+xPDUOutputVoltageLowAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
+ mtrapargsInteger02, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The three-phase output voltage of the device is back within the specified limits.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N).
+ The fourth argument is the measured voltage in tenths of Volts."
+ --#TYPE "APC XPDU: Output low voltage alarm cleared."
+ --#SUMMARY "Output low voltage alarm cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 321
+
+xPDUOutputVoltageHighAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
+ mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The three-phase output voltage of the device is outside the specified limits.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N).
+ The fourth argument is the measured voltage in tenths of Volts.
+ The fifth argument is the threshold, in tenths of Volts, above which the alarm was generated."
+ --#TYPE "APC XPDU: Output high voltage alarm."
+ --#SUMMARY "Output voltage is above threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 322
+
+xPDUOutputVoltageHighAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
+ mtrapargsInteger02, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The three-phase output voltage of the device is back within the specified limits.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N).
+ The fourth argument is the measured voltage in tenths of Volts."
+ --#TYPE "APC XPDU: Output high voltage alarm cleared."
+ --#SUMMARY "Output high voltage alarm cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 323
+
+xPDUOutputCurrentLowAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
+ mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The three-phase output load current of the device is outside the specified limits.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the phase (1=L1, 2=L2, 3=L3).
+ The fourth argument is the measured current in tenths of Amps.
+ The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated."
+ --#TYPE "APC XPDU: Output low current alarm."
+ --#SUMMARY "Output current is below threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 324
+
+xPDUOutputCurrentLowAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
+ mtrapargsInteger02, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The three-phase output load current of the device is back within the specified limits.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the phase (1=L1, 2=L2, 3=L3).
+ The fourth argument is the measured current in tenths of Amps."
+ --#TYPE "APC XPDU: Output low current alarm cleared."
+ --#SUMMARY "Output low current alarm cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 325
+
+xPDUOutputCurrentHighAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
+ mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The three-phase load current of the device is outside the specified limits.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the phase (1=L1, 2=L2, 3=L3).
+ The fourth argument is the measured current in tenths of Amps.
+ The fifth argument is the threshold, in tenths of Amps, above which the alarm was generated."
+ --#TYPE "APC XPDU: Output high current alarm."
+ --#SUMMARY "Output current is above threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 326
+
+xPDUOutputCurrentHighAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
+ mtrapargsInteger02, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The three-phase output current of the device is back within the specified limits.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the phase (1=L1, 2=L2, 3=L3).
+ The fourth argument is the measured current in tenths of Amps."
+ --#TYPE "APC XPDU: Output high current alarm cleared."
+ --#SUMMARY "Output high current alarm cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 327
+
+xPDUOutputFrequencyAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The devices output frequency is outside the specified limits.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the frequency deviation from the nominal in tenths of Hertz."
+ --#TYPE "APC XPDU: Output frequency out-of-range alarm."
+ --#SUMMARY "Output frequency is out-of-range."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 328
+
+xPDUOutputFrequencyAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The devices output frequency is back within the specified limits.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XPDU: Output frequency back in range."
+ --#SUMMARY "Output frequency in range."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 329
+
+xPDUSystemGroundCurrentAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger, mtrapargsInteger02, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The earth ground current of the device is over the specified limits.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the measured current in tenths of Amps.
+ The fourth argument is the threshold, in tenths of Amps, above which the alarm was generated."
+ --#TYPE "APC XPDU: Earth ground high current alarm."
+ --#SUMMARY "Earth ground current is above threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 330
+
+xPDUSystemGroundCurrentAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The earth ground current of the device is back within the specified limits.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the measured current in tenths of Amps."
+ --#TYPE "APC XPDU: Earth ground high current alarm cleared."
+ --#SUMMARY "Earth ground high current alarm cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 331
+
+xPDUInputContactStateAbnormal TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
+ mtrapargsString02, mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: A user input contact on the device has changed to its abnormal state.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the input contact number.
+ The fourth argument is the input contact name.
+ The fifth argument is the input contact state (1=OPEN, 2=CLOSED).
+ The sixth argument is the configured normal input contact state (1=OPEN, 2=CLOSED)."
+ --#TYPE "APC XPDU: Input contact has changed to its abnormal state."
+ --#SUMMARY "Input contact has changed to its abnormal state."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 332
+
+xPDUInputContactStateNormal TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
+ mtrapargsString02, mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A user input contact on the device has changed to its normal state.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the input contact number.
+ The fourth argument is the input contact name.
+ The fifth argument is the input contact state (1=CLOSED, 2=OPEN).
+ The sixth argument is the configured normal input contact state (1=OPEN, 2=CLOSED)."
+ --#TYPE "APC XPDU: Input contact has changed to its normal state."
+ --#SUMMARY "Input contact has changed to its normal state."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 333
+
+xPDUOutputNeutralCurrentHighAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
+ mtrapargsInteger02, mtrapargsString }
+ DESCRIPTION
+ "WARNING: The three-phase neutral current of the device is outside the specified limits.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the measured current in tenths of Amps.
+ The fourth argument is the threshold, in tenths of Amps, above which the alarm was generated."
+ --#TYPE "APC XPDU: Output high neutral current alarm."
+ --#SUMMARY "Output neutral current is above threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 334
+
+xPDUOutputNeutralCurrentHighAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
+ mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The output neutral current of the device is back within the specified limits.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the measured current in tenths of Amps."
+ --#TYPE "APC XPDU: Output neutral high current alarm cleared."
+ --#SUMMARY "Output neutral high current alarm cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 335
+
+xPDUCoolingFanAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The device's internal cooling fans have failed.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XPDU: Cooling fan failure alarm."
+ --#SUMMARY "Cooling fan failure."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 336
+
+xPDUCoolingFanAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The device's cooling fans are now functioning properly.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XPDU: Cooling fan alarm cleared."
+ --#SUMMARY "Cooling fan alarm cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 337
+
+xPDUTransformerTempAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The device's isolation transformer is over temperature.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XPDU: Isolation transformer over temperature alarm."
+ --#SUMMARY "Transformer temp alarm."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 338
+
+xPDUTransformerTempAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The device's isolation transformer is no longer over temperature.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XPDU: Isolation transformer over temperature alarm cleared."
+ --#SUMMARY "Transformer temp alarm cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 339
+
+xPDUBranchCurrentLowAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
+ mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "WARNING: The current in a branch circuit is outside the limits specified for that
+ branch circuit.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the panel position of the branch circuit (1-based index).
+ The fourth argument is the measured current in tenths of Amps.
+ The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated."
+ --#TYPE "APC XPDU: Branch circuit low current alarm."
+ --#SUMMARY "Branch circuit current is below threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 340
+
+xPDUBranchCurrentLowAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
+ mtrapargsInteger02, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The current in a branch circuit is back within the limits
+ specified for that branch circuit.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the panel position of the branch circuit (1-based index).
+ The fourth argument is the measured current in tenths of Amps."
+ --#TYPE "APC XPDU: Branch circuit low current alarm cleared."
+ --#SUMMARY "Branch circuit low current alarm cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 341
+
+xPDUBranchCurrentHighAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
+ mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "WARNING: The current in a branch circuit is outside the limits specified for that
+ branch circuit.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the panel position of the branch circuit (1-based index).
+ The fourth argument is the measured current in tenths of Amps.
+ The fifth argument is the threshold, in tenths of Amps, above which the alarm was generated."
+ --#TYPE "APC XPDU: Branch circuit high current alarm."
+ --#SUMMARY "Branch circuit current is above threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 342
+
+xPDUBranchCurrentHighAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
+ mtrapargsInteger02, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The current in a branch circuit is back within the limits
+ specified for that branch circuit.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the panel position of the branch circuit (1-based index).
+ The fourth argument is the measured current in tenths of Amps."
+ --#TYPE "APC XPDU: Branch circuit high current alarm cleared."
+ --#SUMMARY "Branch circuit high current alarm cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 343
+
+
+xPDUInternalCommError TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: There is an internal communication error in the device.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XPDU: Internal communication error."
+ --#SUMMARY "Internal communication error."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 344
+
+emsHardwareStateAbnormal TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The device's hardware is improperly configured and operating outside
+ normal bounds for the hardware. This can be caused by improper devices being
+ connected to the EMS ports or Alink Current limit detection."
+ --#TYPE "APC EMS: Hardware is in an abnormal state."
+ --#SUMMARY "Hardware is in an abnormal state."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 345
+
+emsHardwareStateNormal TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The device's hardware is in its normal operational state.
+ The first argument is the host device serial number."
+ --#TYPE "APC EMS: Hardware is in a normal state."
+ --#SUMMARY "Hardware is in its normal state."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 346
+
+ceSevereCondition TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: A Custom Event severe condition was detected.
+ The first variable is the custom event text message.
+ The second variable is the custom event number."
+ --#TYPE "APC Custom Event: A severe condition was detected. "
+ --#SUMMARY "A severe condition was detected. "
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 347
+
+ceSevereConditionCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A Custom Event severe condition was cleared.
+ The first variable is the custom event text message.
+ The second variable is the custom event number."
+ --#TYPE "APC Custom Event: A severe condition was cleared. "
+ --#SUMMARY "A severe condition was cleared. "
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 348
+
+ceWarningCondition TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "WARNING: A Custom Event warning condition was detected.
+ The first variable is the custom event text message.
+ The second variable is the custom event number."
+ --#TYPE "APC Custom Event: A warning condition was detected. "
+ --#SUMMARY "A warning condition was detected. "
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 349
+
+ceWarningConditionCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A Custom Event warning condition was cleared.
+ The first variable is the custom event text message.
+ The second variable is the custom event number."
+ --#TYPE "APC Custom Event: A warning condition was cleared. "
+ --#SUMMARY "A warning condition was cleared. "
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 350
+
+ceInformationalCondition TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A Custom Event informational condition was detected.
+ The first variable is the custom event text message.
+ The second variable is the custom event number."
+ --#TYPE "APC Custom Event: Informational condition detected. "
+ --#SUMMARY "An informational condition was detected. "
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 351
+
+ceInformationalConditionCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A Custom Event informational condition was cleared.
+ The first variable is the custom event text message.
+ The second variable is the custom event number."
+ --#TYPE "APC Custom Event: Informational condition was cleared. "
+ --#SUMMARY "An informational condition was cleared. "
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 352
+
+upsInternalOverTemperature TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: The internal over temperature condition exists."
+ --#TYPE "APC UPS: The internal over temperature condition exists."
+ --#SUMMARY "The internal over temperature condition exists."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 353
+
+upsInternalOverTemperatureCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The internal over temperature condition cleared."
+ --#TYPE "APC UPS: The internal over temperature condition cleared."
+ --#SUMMARY "The internal over temperature condition cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 354
+
+upsMpuReset TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The MPU has been reset."
+ --#TYPE "APC UPS: The MPU has been reset."
+ --#SUMMARY "The MPU has been reset."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 355
+
+upsOutputSwitchClosed TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The Output Switch is closed."
+ --#TYPE "APC UPS: The Output Switch is closed."
+ --#SUMMARY "The Output Switch is closed."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 356
+
+upsOutputSwitchOpened TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The Output Switch is open."
+ --#TYPE "APC UPS: The Output Switch is open."
+ --#SUMMARY "The Output Switch is open."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 357
+
+upsCalibrationStackChanged TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A calibration value in the stack was changed."
+ --#TYPE "APC UPS: A calibration value in the stack was changed."
+ --#SUMMARY "A calibration value in the stack was changed."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 358
+
+
+-- Upgraded EMS now has more env traps
+
+envMaxTempThresholdViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeTemperature, emsStatusSysTempUnits,
+ emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Max temperature threshold violated on the probe.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the current temperature.
+ The fourth argument is the temperature scale.
+ The fifth argument is the probe number.
+ The sixth argument is the probe name."
+ --#TYPE "APC ENV: Max temperature threshold violation."
+ --#SUMMARY "Max temperature threshold violation."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 359
+
+envMaxTempThresholdViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeTemperature, emsStatusSysTempUnits,
+ emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Max temperature threshold violation cleared on the probe.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the current temperature.
+ The fourth argument is the temperature scale.
+ The fifth argument is the probe number.
+ The sixth argument is the probe name."
+ --#TYPE "APC ENV: Max temperature threshold violation cleared."
+ --#SUMMARY "Max temperature threshold violation cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 360
+
+envMinTempThresholdViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeTemperature, emsStatusSysTempUnits,
+ emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Min temperature threshold violated on the probe.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the current temperature.
+ The fourth argument is the temperature scale.
+ The fifth argument is the probe number.
+ The sixth argument is the probe name."
+ --#TYPE "APC ENV: Min temperature threshold violation."
+ --#SUMMARY "Min temperature threshold violation."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 361
+
+envMinTempThresholdViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeTemperature, emsStatusSysTempUnits,
+ emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Min temperature threshold violation cleared on the probe.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the current temperature.
+ The fourth argument is the temperature scale.
+ The fifth argument is the probe number.
+ The sixth argument is the probe name."
+ --#TYPE "APC ENV: Min temperature threshold violation cleared."
+ --#SUMMARY "Min temperature threshold violation cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 362
+
+envMaxHumidityThresholdViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeHumidity,
+ emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Max humidity threshold violated on the probe.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the current humidity
+ The fourth argument is the probe number.
+ The fifth argument is the probe name."
+ --#TYPE "APC ENV: Max humidity threshold violation."
+ --#SUMMARY "Max humidity threshold violation."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 363
+
+envMaxHumidityThresholdViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeHumidity,
+ emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Max humidity threshold violation cleared on the probe.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the current humidity.
+ The fourth argument is the probe number.
+ The fifth argument is the probe name."
+ --#TYPE "APC ENV: Max humidity threshold violation cleared."
+ --#SUMMARY "Max humidity threshold violation cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 364
+
+envMinHumidityThresholdViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeHumidity,
+ emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Min humidity threshold violated on the probe.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the current humidity
+ The fourth argument is the probe number.
+ The fifth argument is the probe name."
+ --#TYPE "APC ENV: Min humidity threshold violation."
+ --#SUMMARY "Min humidity threshold violation."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 365
+
+envMinHumidityThresholdViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeHumidity,
+ emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Min humidity threshold violation cleared on the probe.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the current humidity.
+ The fourth argument is the probe number.
+ The fifth argument is the probe name."
+ --#TYPE "APC ENV: Min humidity threshold violation cleared."
+ --#SUMMARY "Min humidity threshold violation cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 366
+
+envSTIncTempRateViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeTemperature, emsStatusSysTempUnits,
+ emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Short-term increasing temperature rate violated on the probe.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the current temperature.
+ The fourth argument is the temperature scale.
+ The fifth argument is the probe number.
+ The sixth argument is the probe name."
+ --#TYPE "APC ENV: Short-term inc. temp rate violation."
+ --#SUMMARY "Short-term inc. temp rate violation."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 367
+
+envSTIncTempRateViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeTemperature, emsStatusSysTempUnits,
+ emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Short-term increasing temperature rate cleared on the probe.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the current temperature.
+ The fourth argument is the temperature scale.
+ The fifth argument is the probe number.
+ The sixth argument is the probe name."
+ --#TYPE "APC ENV: Short-term inc. temp rate violation cleared."
+ --#SUMMARY "Short-term inc. temp rate violation cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 368
+
+envSTDecTempRateViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeTemperature, emsStatusSysTempUnits,
+ emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Short-term decreasing temperature rate violated on the probe.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the current temperature.
+ The fourth argument is the temperature scale.
+ The fifth argument is the probe number.
+ The sixth argument is the probe name."
+ --#TYPE "APC ENV: Short-term dec. temp rate violation."
+ --#SUMMARY "Short-term dec. temp rate violation."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 369
+
+envSTDecTempRateViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeTemperature, emsStatusSysTempUnits,
+ emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Short-term decreasing temperature rate cleared on the probe.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the current temperature.
+ The fourth argument is the temperature scale.
+ The fifth argument is the probe number.
+ The sixth argument is the probe name."
+ --#TYPE "APC ENV: Short-term dec. temp rate violation cleared."
+ --#SUMMARY "Short-term dec. temp rate violation cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 370
+
+envLTIncTempRateViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeTemperature, emsStatusSysTempUnits,
+ emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Long-term increasing temperature rate violated on the probe.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the current temperature.
+ The fourth argument is the temperature scale.
+ The fifth argument is the probe number.
+ The sixth argument is the probe name."
+ --#TYPE "APC ENV: Long-term inc. temp rate violation."
+ --#SUMMARY "Long-term inc. temp rate violation."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 371
+
+envLTIncTempRateViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeTemperature, emsStatusSysTempUnits,
+ emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Long-term increasing temperature rate cleared on the probe.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the current temperature.
+ The fourth argument is the temperature scale.
+ The fifth argument is the probe number.
+ The sixth argument is the probe name."
+ --#TYPE "APC ENV: Long-term inc. temp rate violation cleared."
+ --#SUMMARY "Long-term inc. temp rate violation cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 372
+
+envLTDecTempRateViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeTemperature, emsStatusSysTempUnits,
+ emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Long-term decreasing temperature rate violated on the probe.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the current temperature.
+ The fourth argument is the temperature scale.
+ The fifth argument is the probe number.
+ The sixth argument is the probe name."
+ --#TYPE "APC ENV: Long-term dec. temp rate violation."
+ --#SUMMARY "Long-term dec. temp rate violation."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 373
+
+envLTDecTempRateViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName, emsProbeStatusProbeTemperature, emsStatusSysTempUnits,
+ emsProbeStatusProbeIndex, emsProbeStatusProbeName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Long-term decreasing temperature rate cleared on the probe.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the current temperature.
+ The fourth argument is the temperature scale.
+ The fifth argument is the probe number.
+ The sixth argument is the probe name."
+ --#TYPE "APC ENV: Long-term dec. temp rate violation cleared."
+ --#SUMMARY "Long-term dec. temp rate violation cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 374
+
+-- Battery Management System Traps
+
+bmsCriticalCondition TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: A Battery Management System critical condition was detected.
+ The first variable is the error condition text message.
+ The second variable is the error number."
+ --#TYPE "APC BMS: A critical condition was detected. "
+ --#SUMMARY "A critical condition was detected. "
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 375
+
+bmsCriticalConditionCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A Battery Management System critical condition was cleared.
+ The first variable is the error condition text message.
+ The second variable is the error number."
+ --#TYPE "APC BMS: A critical condition was cleared. "
+ --#SUMMARY "A critical condition was cleared. "
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 376
+
+bmsWarningCondition TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "WARNING: A Battery Management System warning condition was detected.
+ The first variable is the error condition text message.
+ The second variable is the error number."
+ --#TYPE "APC BMS: A warning condition was detected. "
+ --#SUMMARY "A warning condition was detected. "
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 377
+
+bmsWarningConditionCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "WARNING: A Battery Management System warning condition was cleared.
+ The first variable is the error condition text message.
+ The second variable is the error number."
+ --#TYPE "APC BMS: A warning condition was cleared. "
+ --#SUMMARY "A warning condition was cleared. "
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 378
+
+bmsInformationalCondition TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A Battery Management System informational condition was detected.
+ The first variable is the error condition text message.
+ The second variable is the error number."
+ --#TYPE "APC BMS: Informational condition detected. "
+ --#SUMMARY "An informational condition was detected. "
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 379
+
+bmsInformationalConditionCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A Battery Management System informational condition was cleared.
+ The first variable is the error condition text message.
+ The second variable is the error number."
+ --#TYPE "APC BMS: Informational condition was cleared. "
+ --#SUMMARY "An informational condition was cleared. "
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 380
+
+-- xATS Traps
+
+xATSOutputVoltageLowAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger,
+ mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The device three-phase output voltage of the device is outside the specified limits.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N, 4=unused, 5=L1-L2, 6=L2-L3, 7=L3-L1).
+ The fourth argument is the measured voltage in tenths of Volts.
+ The fifth argument is the threshold, in tenths of Volts, from which the alarm was generated."
+ --#TYPE "APC XATS: Output low voltage alarm."
+ --#SUMMARY "Output voltage is below threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 381
+
+xATSOutputVoltageLowAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger,
+ mtrapargsInteger02, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The devices three-phase output voltage is back within the specified limits.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N, 4=unused, 5=L1-L2, 6=L2-L3, 7=L3-L1).
+ The fourth argument is the measured voltage in tenths of Volts."
+ --#TYPE "APC XATS: Output low voltage alarm cleared."
+ --#SUMMARY "Output low voltage alarm cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 382
+
+xATSOutputVoltageHighAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger,
+ mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The device three-phase output voltage of the device is outside the specified limits.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N, 4=unused, 5=L1-L2, 6=L2-L3, 7=L3-L1).
+ The fourth argument is the measured voltage in tenths of Volts.
+ The fifth argument is the threshold, in tenths of Volts, above which the alarm is generated."
+ --#TYPE "APC XATS: Output high voltage alarm."
+ --#SUMMARY "Output voltage is above threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 383
+
+xATSOutputVoltageHighAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger,
+ mtrapargsInteger02, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The devices three-phase output voltage is back within the specified limits.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N, 4=unused, 5=L1-L2, 6=L2-L3, 7=L3-L1).
+ The fourth argument is the measured voltage in tenths of Volts."
+ --#TYPE "APC XATS: Output high voltage alarm cleared."
+ --#SUMMARY "Output high voltage alarm cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 384
+
+xATSOutputCurrentLowAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger,
+ mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The three-phase load current of the device is outside the specified limits.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the phase (1=L1, 2=L2, 3=L3).
+ The fourth argument is the measured current in Amps.
+ The fifth argument is the threshold, in Amps, from which the alarm was generated."
+ --#TYPE "APC XATS: Output low current alarm."
+ --#SUMMARY "Output current is below threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 385
+
+xATSOutputCurrentLowAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger,
+ mtrapargsInteger02, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The three-phase load current of the device is back within the specified limits.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the phase (1=L1, 2=L2, 3=L3).
+ The fourth argument is the measured current in Amps."
+ --#TYPE "APC XATS: Output low current alarm cleared."
+ --#SUMMARY "Output low current alarm cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 386
+
+xATSOutputCurrentHighAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger,
+ mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The three-phase output load current of the device is outside the specified limits.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the phase (1=L1, 2=L2, 3=L3).
+ The fourth argument is the measured current in Amps.
+ The fifth argument is the threshold, in Amps, from which the alarm was generated."
+ --#TYPE "APC XATS: Output high current alarm."
+ --#SUMMARY "Output current is above threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 387
+
+xATSOutputCurrentHighAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger,
+ mtrapargsInteger02, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The three-phase output load current of the device is back within the specified limits.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the phase (1=L1, 2=L2, 3=L3).
+ The fourth argument is the measured current in Amps."
+ --#TYPE "APC XATS: Output high current alarm cleared."
+ --#SUMMARY "Output high current alarm cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 388
+
+
+xATSOutputFrequencyAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger,
+ mtrapargsInteger02, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The devices output frequency is outside the specified limits.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the frequency deviation from the nominal in tenths of Hertz.
+ The fourth argument is the frequency deviation threshold in tenths of Hertz,
+ from which the alarm was generated."
+ --#TYPE "APC XATS: Output frequency out-of-range alarm."
+ --#SUMMARY "Output frequency is out-of-range."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 389
+
+xATSOutputFrequencyAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The devices output frequency is back within the specified limits.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XATS: Output frequency back in range."
+ --#SUMMARY "Output frequency in range."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 390
+
+xATSInternalCommError TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: There is an internal communication error in the device.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XATS: Internal communication error."
+ --#SUMMARY "Internal communication error."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 391
+
+xATSInternalCommErrorCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Internal communication has been restored.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XATS: Internal Communication error cleared."
+ --#SUMMARY "ATS Communication error cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 392
+
+xATSDataCommMismatchError TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: A data incompatibility exists within the device. This
+ is typically the result of mismatches between firmware revisions
+ of the transfer switch controller and the Network Management interface.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XATS: Data mismatch error."
+ --#SUMMARY "ATS data mismatch error."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 393
+
+xATSDataCommMismatchErrorCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The internal data incompatibility has been resolved.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XATS: data mismatch error cleared."
+ --#SUMMARY "ATS data mismatch error cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 394
+
+xATSGenCommLost TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "WARNING: The XATS cannot communicate with the generator.
+ This will make unavailable all the xATSGenerator OIDs.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XATS: No communication with generator."
+ --#SUMMARY "ATS/Generator communication lost."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 395
+
+xATSGenCommEstablished TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The XATS has established communication with the generator.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XATS: Communication with generator established."
+ --#SUMMARY "ATS/generator communication established."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 396
+
+xATSNeutralPosition TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger,
+ mtrapargsString }
+ DESCRIPTION
+ "WARNING: XATS has transferred to neutral position.
+ In this position neither Source 1 nor Source 2 is selected,
+ and the XATS will have no output voltage.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the mode in which the switch is operating
+ (1=Auto, 2=Not-in-Auto, Abnormal Condition 3=Not-in-Auto, manual)."
+ --#TYPE "APC XATS: Transferred to the neutral (no output power) position."
+ --#SUMMARY "Transferred to neutral."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 397
+
+xATSSwitchTransferEvent TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger,
+ mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: XATS has transferred from one source to the other.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the mode in which the switch is operating.
+ (1=Auto, 2=Not-in-Auto, Abnormal Condition 3=Not-in-Auto, manual).
+ The fourth argument is the input source selected (1=Source 1, 2=Source 2).
+ The fifth argument is type of transfer that took place. (1=Closed, 2=Open, 3=Unknown)"
+ --#TYPE "APC XATS: Transferred from Source-X to Source-Y."
+ --#SUMMARY "Source-to-Source transfer."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 398
+
+xATSInternalATSFault TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: An internal XATS fault has been detected.
+ The XATS may have forced itself to not-in-auto mode (abnormal condition),
+ as indicated by the xATSSwitchStatusAutoSwitchOperationalMode OID.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument indicates the detected fault.
+
+ 1=Cannot Close S1
+ 2=Cannot Close S2
+ 3=Cannot Open S1
+ 4=Cannot Open S2
+ 5=Cannot Trip Open S1
+ 6=Cannot Trip Open S2
+ 7=Start Contact Failure
+ 8=Voltage Sensing Failure"
+
+ --#TYPE "APC XATS: Internal fault detected."
+ --#SUMMARY "ATS internal fault detected."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 399
+
+xATSInternalATSFaultCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The detected internal XATS fault has been cleared.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument indicates the detected fault.
+
+ 1=Cannot Close S1
+ 2=Cannot Close S2
+ 3=Cannot Open S1
+ 4=Cannot Open S2
+ 5=Cannot Trip Open S1
+ 6=Cannot Trip Open S2
+ 7=Start Contact Failure
+ 8=Voltage Sensing Failure"
+
+ --#TYPE "APC XATS: Internal fault cleared."
+ --#SUMMARY "ATS internal fault cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 400
+
+xATSEngineStartAsserted TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The XATS has asserted the Engine Start contact.
+ This should result in the generator producing output voltage.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument indicates the reason that the start signal was asserted
+ 1=Unknown, 2=S1 Low Voltage, 3=S1 High Voltage, 4=S1 Line Imbalance,
+ 5=S1 Freq Range, 6=S1 Bad Rotation."
+ --#TYPE "APC XATS: Engine Start signal asserted."
+ --#SUMMARY "Engine Start asserted."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 401
+
+xATSEngineStopAsserted TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The XATS has de-asserted the Engine Start contact.
+ This should result in the generator shutting down, and producing no output voltage.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XATS: Engine Stop signal asserted."
+ --#SUMMARY "Engine Stop asserted."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 402
+
+xATSStartFailure TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The generator failed to start. After assertion of the
+ Engine Start signal, the quality of Source 2 was not seen as good.
+ This alarm can be cleared using the xATSSwitchStatusClearLatchedAlarms OID.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument indicates the line quality at S2
+ 1=Unknown, 2=S2 Low Voltage, 3=S2 High Voltage, 4=S2 Line Imbalance,
+ 4=S2 Freq Range, 5=S2 Bad Rotation."
+ --#TYPE "APC XATS: Generator failed to start alarm."
+ --#SUMMARY "Generator failed to start."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 403
+
+xATSStopFailure TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "WARNING: The generator failed to stop. After de-assertion of the
+ Engine Start signal, the quality of Source 2 continued to be seen as good.
+ This alarm can be cleared using the xATSSwitchStatusClearLatchedAlarms OID.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XATS: Generator failed to stop alarm."
+ --#SUMMARY "Generator failed to stop."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 404
+
+xATSNotInAutomaticMode TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Automatic Transfer Switch is not in automatic mode.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The xATSSwitchStatusAutoSwitchStatus OID and the
+ xATSSwitchStatusAutoSwitchOperationalMode OID
+ can provide more information about the state of the XATS."
+ --#TYPE "APC XATS: XATS is not-in-automatic mode."
+ --#SUMMARY "ATS not in auto."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 405
+
+xATSNotInAutomaticModeCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Automatic Transfer Switch is in automatic mode.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XATS: XATS in auto mode."
+ --#SUMMARY "ATS in auto mode."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 406
+
+xATSEpoTripped TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The device's Emergency Power Off (EPO) circuit is tripped.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XATS: Emergency Power Off (EPO) tripped."
+ --#SUMMARY "EPO tripped."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 407
+
+xATSEpoReset TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The device's Emergency Power Off (EPO) circuit has been
+ reset to the armed position.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XATS: Emergency Power Off (EPO) reset."
+ --#SUMMARY "EPO armed."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 408
+
+xATSEpoTestMode TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "WARNING: The device's Emergency Power Off (EPO) circuit has been
+ switched back to the test position.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XATS: Emergency Power Off (EPO) in test mode."
+ --#SUMMARY "EPO disabled."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 409
+
+xATSEpoArmed TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The device's Emergency Power Off (EPO) circuit has been
+ switched back to the armed position.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XATS: Emergency Power Off (EPO) enabled."
+ --#SUMMARY "EPO armed."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 410
+
+xATSTestInitiated TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A scheduled test has been initiated.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the type of test initiated (1=scheduled, 2=manual)."
+ --#TYPE "APC XATS: Test initiated."
+ --#SUMMARY "Test initiated."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 411
+
+xATSTestCanceled TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The scheduled test has been canceled
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the type of test initiated (1=scheduled, 2=manual)."
+ --#TYPE "APC XATS: Test canceled."
+ --#SUMMARY "Test canceled."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 412
+
+xATSTestFailed TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The initiated test has failed.
+ This alarm can be cleared using the xATSSwitchStatusClearLatchedAlarms OID.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XATS: Initiated test failed."
+ --#SUMMARY "Initiated test failed."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 413
+
+xATSTestPassed TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The initiated test has passed
+ switched back to the armed position.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XATS: Initiated test passed."
+ --#SUMMARY "Initiated test passed."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 414
+
+xATSInputContactStateAbnormal TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger,
+ mtrapargsString02, mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: A user input contact on the device has changed to its abnormal state.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the input contact number.
+ The fourth argument is the input contact name.
+ The fifth argument is the input contact state (1=OPEN, 2=CLOSED).
+ The sixth argument is the configured normal input contact state (1=OPEN, 2=CLOSED)."
+ --#TYPE "APC XATS: Input contact has changed to its abnormal state."
+ --#SUMMARY "Input contact has changed to its abnormal state."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 415
+
+xATSInputContactStateNormal TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger,
+ mtrapargsString02, mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A user input contact on the device has changed to its normal state.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the input contact number.
+ The fourth argument is the input contact name.
+ The fifth argument is the input contact state (1=OPEN, 2=CLOSED).
+ The sixth argument is the configured normal input contact state (1=OPEN, 2=CLOSED)."
+ --#TYPE "APC XATS: Input contact has changed to its normal state."
+ --#SUMMARY "Input contact has changed to its normal state."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 416
+
+xATSRemoteStartContactMismatch TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The state of the generator's Remote Start input
+ and the ATS's Engine Start output do not match.
+ This indicates something wrong in the Engine Start wiring,
+ which must be corrected. This condition will prevent the
+ generator from being started when needed.
+
+ (See also: xATSGeneratorStatusRemoteStart
+ and xATSSwitchStatusEngineStartSignal OIDs)
+
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XATS: Generator/ATS start contact mismatch."
+ --#SUMMARY "Generator/ATS start contact mismatch."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 417
+
+xATSRemoteStartContactMismatchCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Mismatch in the state of the generator's
+ Remote Start input and the ATS's Engine Start output as been resolved.
+ This indicates something wrong in the Engine Start wiring,
+ which must be corrected. This condition will prevent the
+ generator from being started when needed.
+
+ (See also: xATSGeneratorStatusRemoteStart
+ and xATSSwitchStatusEngineStartSignal OIDs)
+
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XATS: Generator/ATS start contact mismatch cleared."
+ --#SUMMARY "Generator/ATS start contact mismatch cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 418
+
+xATSDoorOpenAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "WARNING: The XATS exterior panel door is open.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XATS: Panel door is open alarm."
+ --#SUMMARY "Panel door open alarm."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 419
+
+xATSDoorOpenAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The external door to the device is closed.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XATS: Panel door open alarm cleared."
+ --#SUMMARY "Panel door open alarm cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 420
+
+xATSDCBackupAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "WARNING: The XATS's DC backup has been lost. The XATS will lose power
+ on Source 1 failure, causing the Engine Start signal to be asserted.
+ The XATS will then restart from Source 2.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XATS: DC backup failure."
+ --#SUMMARY "ATS DC backup failure."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 421
+
+xATSDCBackupAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: DC backup alarm has been cleared in the device.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XATS: DC backup alarm cleared."
+ --#SUMMARY "DC backup alarm cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 422
+
+-- xATS Generator Traps
+
+xATSGeneratorLowCoolantLevelAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Low coolant level has been detected in the generator.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: Generator low coolant level alarm."
+ --#SUMMARY "Generator low coolant level alarm."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 423
+
+xATSGeneratorLowCoolantLevelAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The detected low coolant level has been cleared in the generator.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: Generator low coolant level alarm cleared."
+ --#SUMMARY "Generator low coolant level alarm cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 424
+
+xATSGeneratorVeryLowCoolantLevelAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Very low coolant level has been detected in the generator.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: Generator very low coolant level alarm."
+ --#SUMMARY "Generator very low coolant level alarm."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 425
+
+xATSGeneratorVeryLowCoolantLevelAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The detected Very low coolant level has been cleared in the generator.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: Generator very low coolant level alarm cleared."
+ --#SUMMARY "Generator very low coolant level alarm cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 426
+
+xATSGeneratorHighCoolantTempAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: High coolant temperature has been detected in the generator.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: Generator high coolant temperature alarm."
+ --#SUMMARY "Generator high coolant temperature alarm."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 427
+
+xATSGeneratorHighCoolantTempAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The detected high coolant temperature has been cleared in the generator.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: Generator high coolant temperature alarm cleared."
+ --#SUMMARY "Generator high coolant temperature alarm cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 428
+
+xATSGeneratorVeryHighCoolantTempAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Very high coolant temperature has been detected in the generator.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: Generator very high coolant temperature alarm."
+ --#SUMMARY "Generator very high coolant temperature alarm."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 429
+
+xATSGeneratorVeryHighCoolantTempAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The Very high coolant temperature condition has been cleared in the generator.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: Generator very high coolant temperature alarm cleared."
+ --#SUMMARY "Generator very high coolant temperature alarm cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 430
+
+xATSGeneratorLowCoolantTempAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "WARNING: Low coolant temperature has been detected in the generator.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: Generator low coolant temperature alarm."
+ --#SUMMARY "Generator low coolant temperature alarm."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 431
+
+xATSGeneratorLowCoolantTempAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The low coolant temperature condition has been cleared in the generator.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: Generator low coolant temperature alarm cleared."
+ --#SUMMARY "Generator low coolant temperature alarm cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 432
+
+xATSGeneratorLowOilLevelAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Low oil level has been detected in the generator.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: Generator low oil level alarm."
+ --#SUMMARY "Generator low oil level alarm."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 433
+
+xATSGeneratorLowOilLevelAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Low oil level alarm has been cleared in the generator.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: Generator low oil level alarm cleared."
+ --#SUMMARY "Generator low oil level alarm cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 434
+
+xATSGeneratorLowBatteryVoltDuringCrankAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The generator's battery voltage has been detected
+ as low while cranking the engine.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: Low batt. voltage while cranking alarm."
+ --#SUMMARY "Generator low battery volts while cranking alarm."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 435
+
+xATSGeneratorLowBatteryVoltDuringCrankAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The generator's low battery voltage while
+ cranking condition has been cleared.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "XGEN: Generator low batt. voltage while cranking alarm cleared."
+ --#SUMMARY "Generator low battery volts while cranking alarm cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 436
+
+xATSGeneratorVeryLowBatteryVoltDuringCrankAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The generator's battery voltage has been detected
+ as very low while cranking the engine.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "XGEN: Generator v.low battery voltage while cranking alarm."
+ --#SUMMARY "Generator v.low battery volts while cranking alarm."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 437
+
+xATSGeneratorVeryLowBatteryVoltDuringCrankAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The generator's high battery voltage while
+ cranking condition has been cleared.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "XGEN: Generator v.low batt volt, while cranking alarm cleared."
+ --#SUMMARY "Generator v.low battery volts while cranking alarm cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 438
+
+xATSGeneratorEStop TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsInteger02, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The generator's emergency stop input has been activated.
+ After the emergency stop signal has been removed, the E-Stop condition
+ must be cleared before the generator can be started again.
+ E-Stop conditions can only be cleared via the generator front panel.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code.
+ The fourth argument is the type of E-Stop (1=LOCAL, 2=REMOTE)."
+ --#TYPE "APC XGEN: Generator emergency stop engaged."
+ --#SUMMARY "Generator emergency stop engaged."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE NONOPERATIONAL
+ ::= 439
+
+xATSGeneratorEStopCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsInteger02, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The generator's emergency stop condition has been cleared.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code.
+ The fourth argument is the type of E-Stop (1=LOCAL, 2=REMOTE)."
+ --#TYPE "APC XGEN: Generator emergency stop condition cleared."
+ --#SUMMARY "Generator emergency stop condition cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 440
+
+xATSGeneratorHighBatteryVolt TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "WARNING: The generator's battery voltage has been detected as high.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: Generator high battery voltage."
+ --#SUMMARY "Generator high battery volts."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 441
+
+xATSGeneratorHighBatteryVoltCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The detected high battery voltage has been cleared, on the generator.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: Generator high battery voltage condition cleared."
+ --#SUMMARY "Generator high battery volts condition cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 442
+
+xATSGeneratorLowBatteryVolt TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The generator's battery voltage has been detected as low.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: Generator low battery voltage."
+ --#SUMMARY "Generator low battery volts."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 443
+
+xATSGeneratorLowBatteryVoltCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The detected low battery voltage has been cleared, on the generator.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: Generator low battery voltage condition cleared."
+ --#SUMMARY "Generator low battery volts condition cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 444
+
+xATSGeneratorControlSwitchNotAuto TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The control switch on the generator is not in auto position.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: Generator not-in-automatic mode."
+ --#SUMMARY "Generator not-in-auto."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 445
+
+xATSGeneratorControlSwitchNotAutoCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The control switch on the generator is in auto position.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: Generator automatic mode restored."
+ --#SUMMARY "Generator not-in-auto cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 446
+
+xATSGeneratorLowOilPressure TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The generator's oil pressure has been detected as low.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: Generator low oil pressure."
+ --#SUMMARY "Generator low oil pressure."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 447
+
+xATSGeneratorLowOilPressureCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The detected low oil pressure has been cleared, on the generator.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: Generator low oil pressure condition cleared."
+ --#SUMMARY "Generator low oil pressure condition cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 448
+
+xATSGeneratorVeryLowOilPressure TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The generator's oil pressure has been detected as very low.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: Generator v.low oil pressure."
+ --#SUMMARY "Generator v.low oil pressure."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 449
+
+xATSGeneratorVeryLowOilPressureCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The detected v.low oil pressure has been cleared, on the generator.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: Generator v.low oil pressure condition cleared."
+ --#SUMMARY "Generator v.low oil pressure condition cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 450
+
+xATSGeneratorOverload TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The generator is overloaded.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: Generator is in overload event."
+ --#SUMMARY "Generator on overload event."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 451
+
+xATSGeneratorOverloadCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The generator is running within loading limits.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: Generator is in overload event cleared."
+ --#SUMMARY "Generator on overload event cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 452
+
+xATSGeneratorLowACVEvent TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The generator AC voltage is outside the acceptable bounds.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: State of the Generator AC voltage."
+ --#SUMMARY " State of the Generator AC voltage."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 453
+
+xATSGeneratorLowACVEventCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The generator AC voltage is within normal bounds.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: State of the Generator AC voltage cleared."
+ --#SUMMARY "State of the Generator AC voltage cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 454
+
+xATSGeneratorHighACVEvent TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The generator AC voltage is outside the acceptable bounds.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: State of the Generator AC voltage."
+ --#SUMMARY " State of the Generator AC voltage."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 455
+
+xATSGeneratorHighACVEventCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The generator AC voltage is within normal bounds.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: State of the Generator AC voltage cleared."
+ --#SUMMARY "State of the Generator AC voltage cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 456
+
+xATSGeneratorOverspeed TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The generator is running over the acceptable RPM.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: Generator overspeed condition."
+ --#SUMMARY "Generator overspeed condition."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 457
+
+xATSGeneratorOverspeedCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The generator overspeed shutdown has been cleared.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: Generator overspeed condition cleared."
+ --#SUMMARY "Generator overspeed condition cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 458
+
+xATSGeneratorEngineCold TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The generator engine is cold, may not start.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: Generator engine is cold, may not start."
+ --#SUMMARY "Generator engine is cold."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 459
+
+xATSGeneratorEngineColdCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The engine is not cold to start.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: Engine is cold to start condition cleared."
+ --#SUMMARY "Engine is cold to start condition cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 460
+
+xATSGeneratorOutputBreakerOpen TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The generators output breaker has been detected as open.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: Generator output breaker open alarm."
+ --#SUMMARY "Generator output breaker open."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE NONOPERATIONAL
+ ::= 461
+
+xATSGeneratorOutputBreakerOpenCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The engine is not cold to start.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: Generator output breaker open alarm cleared."
+ --#SUMMARY "Generator output breaker open cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 462
+
+xATSGeneratorLowFuelLevelAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "WARNING: The tank fuel level is below the limits specified
+ in the xATSGeneratorFuelSystemLowFuelLevelThreshold OID.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the measured fuel level in percent of full."
+ --#TYPE "APC XGEN: Low fuel level alarm."
+ --#SUMMARY "Generator low fuel level alarm."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 463
+
+xATSGeneratorLowFuelLevelAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The tank fuel level is back above the specified limit.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XGEN: Low fuel level alarm cleared."
+ --#SUMMARY "Generator low fuel level alarm cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 464
+
+xATSGeneratorVeryLowFuelLevelAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The tank fuel level is below the low threshold limits.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the measured tank fuel level in percent of full."
+ --#TYPE "APC XGEN: Very Low fuel level alarm."
+ --#SUMMARY "Generator very low fuel level alarm."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 465
+
+xATSGeneratorVeryLowFuelLevelAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The detected low tank level has been cleared in the device.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XGEN: Very low fuel level alarm cleared."
+ --#SUMMARY "Generator very low fuel level alarm cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 466
+
+xATSGeneratorLowRunTimeAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "WARNING: The estimated runtime is below the limits specified.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the estimated runtime in hours."
+ --#TYPE "APC XGEN: Low run time alarm."
+ --#SUMMARY "Generator low run time alarm."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 467
+
+xATSGeneratorLowRunTimeAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The detected low runtime has been cleared in the device.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XGEN: Low run time alarm cleared."
+ --#SUMMARY "Generator low run time alarm."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 468
+
+xATSGeneratorVeryLowRunTimeAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The estimated runtime is below the limits specified
+ in the xATSGeneratorFuelSystemVeryLowRunTimeThreshold OID.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the estimated runtime in hours."
+ --#TYPE "APC XGEN: Very low run time alarm."
+ --#SUMMARY "Generator very low run time alarm."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 469
+
+xATSGeneratorVeryLowRunTimeAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The detected low runtime has been cleared in the device.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XGEN: Very low run time alarm cleared."
+ --#SUMMARY "Generator very low run time alarm."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 470
+
+xATSGeneratorServiceDueAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "WARNING: The generator is due for scheduled service.
+ Generation of this alarm is based on calendar days since
+ and/or actual generator run-hours since last service.
+ This alarm is cleared using the xATSGeneratorServiceResetRecord OID.
+
+ (See also: xATSGeneratorServiceCalendarIntervalThreshold
+ and xATSGeneratorServiceRunHoursThreshold OIDs)
+
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XATS: Generator scheduled maintenance is due."
+ --#SUMMARY "Generator maintenance due."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 471
+
+xATSGeneratorServiceDueAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The generator's service registers have been reset.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XATS: Generator service due alarm is cleared."
+ --#SUMMARY "Generator service alarm is cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 472
+
+xATSGeneratorShutdown TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The generator is shutdown.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: Generator shutdown."
+ --#SUMMARY "Generator shutdown"
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 473
+
+xATSGeneratorShutdownCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The generator shutdown alarm is cleared.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: Generator shutdown is cleared."
+ --#SUMMARY "Generator shutdown is cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 474
+
+xATSGeneratorBatteryCharger TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The generator battery charger is nonfunctional.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: Generator batt. charger is nonfunctional."
+ --#SUMMARY "Generator battery charger is nonfunctional"
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 475
+
+xATSGeneratorBatteryChargerCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Fault in the generator battery charger is cleared.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: Fault in the generator battery charger is cleared."
+ --#SUMMARY "Fault in the generator battery charger is cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 476
+
+xATSGeneratorGenericEvent TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "WARNING: Any generic generator event.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: Generator generic event."
+ --#SUMMARY "Generator generic event."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 477
+
+xATSGeneratorGenericEventCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Generated generic generator event is cleared.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: Generic generator event is cleared."
+ --#SUMMARY "Generic generator event is cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 478
+
+-- xPDU Traps (part 2)
+
+xPDUInternalCommErrorCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Internal communication has been restored.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XPDU: Internal Communication error cleared."
+ --#SUMMARY "Communication error cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 479
+
+
+xPDUSystemStateAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName,
+ mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The PDU's breakers (Q1, Q2 & Q3) are in a configuration that might lead
+ to system unavailability. it may signify a temporary condition, when the breakers
+ are placed in an atypical manner as the user transitions to (UPS OPERATION or MAINTENANCE BYPASS)
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the type of state change (1=NO UPS INPUT, 2=NO PANEL FEED, 3=ATYPICAL BYPASS MODE).
+ note: The NO_PANEL_FEED alarm is applicable only for PDUs with system bypass."
+ --#TYPE "APC XPDU: System state change alarm."
+ --#SUMMARY "PDU state change alarm."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 480
+
+xPDUSystemStateAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName,
+ mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The PDU's breakers (Q1, Q2 & Q3) are set in a configuration
+ that is a non-alarm state.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the type of state change (1=NO UPS INPUT, 2=NO PANEL FEED, 3=ATYPICAL BYPASS MODE).
+ note: The NO_PANEL_FEED alarm is applicable only for PDUs with system bypass."
+ --#TYPE "APC XPDU: Normal system state change."
+ --#SUMMARY "PDU normal state change."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 481
+
+xPDUEpoTestMode TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "WARNING: The device's Emergency Power Off (EPO) circuit has been
+ switched back to the test position.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XPDU: Emergency Power Off (EPO) in test mode."
+ --#SUMMARY "EPO disabled."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 482
+
+xPDUEpoArmed TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The device's Emergency Power Off (EPO) circuit has been
+ switched back to the armed position.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XPDU: Emergency Power Off (EPO) enabled."
+ --#SUMMARY "EPO armed."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 483
+
+xPDUFuseBlownAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName,
+ mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: One or more fuses in this PDU have been detected as open.
+ These fuses are in the feed to the UPS associated with this PDU.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the phase (1=L1, 2=L2, 3=L3)."
+ --#TYPE "APC XPDU: Check fuse alarm."
+ --#SUMMARY "Fuse detected opened."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 484
+
+xPDUFuseBlownAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName,
+ mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A previous check fuse alarm in this PDU has cleared.
+ These fuses are in the feed to the UPS associated with this PDU.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the phase (1=L1, 2=L2, 3=L3)."
+ --#TYPE "APC XPDU: Check fuse alarm cleared."
+ --#SUMMARY "Fuse alarm cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 485
+
+xPDUBreakerPositionAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName,
+ mtrapargsInteger, mtrapargsInteger02, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: A PDU breaker is in a state that compromises system availability.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the breaker (1=MAIN INPUT, 2=BYPASS INPUT, 3=CROSS TIE, 4=OUTPUT).
+ note: The OUTPUT breaker position alarm is applicable only for PDUs with no system bypass.
+ The fourth argument is the breaker position (1=OPEN, 2=CLOSED)."
+ --#TYPE "APC XPDU: Breaker position alarm."
+ --#SUMMARY "Breaker position alarm."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 486
+
+xPDUBreakerPositionAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName,
+ mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A PDU breaker is no longer in a state that compromises system availability.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the breaker (1=MAIN INPUT, 2=BYPASS INPUT, 3=CROSS TIE, 4=OUTPUT).
+ note: The OUTPUT breaker position alarm cleared is applicable only for PDUs with no system bypass."
+ --#TYPE "APC XPDU: Breaker position alarm cleared."
+ --#SUMMARY "Breaker alarm cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 487
+
+xPDUBreakerChangeEvent TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
+ mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A system breaker or switch within the device has changed state.
+ They are generated when any of the Q1, Q2 or Q3 breakers have changed states.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the breaker that has changed
+ (1=UPS FEED (Q1), 2=UPS OUTPUT(Q2), 3=MAINTENANCE BYPASS (Q3).
+ The fourth argument is the state of the breaker that has changed (1=OPEN, 2=CLOSED).
+ The fifth argument is a 8-bit field representing the state of all breakers in the system,
+ when any of one of the Q1, Q2 or Q3 breakers have changed state.
+
+ The bit map is represented in the following manner (b7, b6 ... b0)
+ b0 - UPS FEED (Q1)
+ b1 - MAINTENANCE BYPASS (Q3)
+ b2 - UPS OUTPUT (Q2)
+ b3 - MAIN INPUT
+ b4 - BYPASS INPUT
+ b5 - CROSS-TIE OUTPUT
+
+ Example: value of 60 (0x3C) indicates that the CROSS_TIE, BYPASS and MAIN INPUT, and Q2 breakers
+ are CLOSED and Q3, Q1 breakers are OPEN."
+ --#TYPE "APC XPDU: Breaker/switch change event."
+ --#SUMMARY "Breaker/switch change event."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 488
+
+xPDUDataCommMismatchError TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: A data incompatibility exists within the device. This
+ is typically the result of mismatches between firmware revisions
+ of the transfer switch controller and the Network Management interface.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XPDU: Data mismatch error."
+ --#SUMMARY "XPDU data mismatch error."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 489
+
+xPDUDataCommMismatchErrorCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The internal data incompatibility has been resolved.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XPDU: data mismatch error cleared."
+ --#SUMMARY "XPDU data mismatch error cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 490
+
+xPDUSystemInMaintenanceBypassMode TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "WARNING: The PDU state has changed to maintenance bypass mode.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XPDU: System state changed to maintenance bypass."
+ --#SUMMARY "PDU state changed to maintenance bypass."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 491
+
+xPDUSystemInUPSOperationalMode TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The PDU state has changed to UPS operational mode.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XPDU: System state changed to UPS operational."
+ --#SUMMARY "PDU state changed to UPS operational."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 492
+
+xATSGeneratorFuelTankRuptureAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "WARNING: Detected a rupture in the inner wall of the generator fuel tank.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: Generator inner wall rupture alarm."
+ --#SUMMARY "Generator inner wall rupture alarm."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 493
+
+xATSGeneratorFuelTankRuptureAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The rupture in the inner wall of the generator is not detected.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: Generator inner wall rupture alarm cleared."
+ --#SUMMARY "Generator inner wall rupture alarm cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 494
+
+xATSGeneratorGroundFaultAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Generator ground fault alarm.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: Generator ground fault alarm."
+ --#SUMMARY "Generator ground fault alarm."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 495
+
+xATSGeneratorGroundFaultAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Generator ground fault alarm cleared.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the OEM's fault/event code."
+ --#TYPE "APC XGEN: Generator ground fault alarm cleared."
+ --#SUMMARY "Generator ground fault alarm cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 496
+
+xATSOutputLoadPoweredByGeneratorAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "WARNING: The system load on the output of the ATS is being powered by source 2 (generator).
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument indicates if the load is powered by the generator,
+ when 'load testing' the generator (1 = LIVE, 2 = TEST)."
+ --#TYPE "APC XATS: System load powered by generator alarm."
+ --#SUMMARY "System load powered by generator."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 497
+
+xATSOutputLoadPoweredByGeneratorAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The system load on the output of the ATS is no longer being powered by source 2 (generator).
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XATS: System load powered by generator alarm cleared."
+ --#SUMMARY "System load powered by generator alarm cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 498
+
+xAPCControllerFirmwareUpdateTransferStart TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString05, mtrapargsString04, mtrapargsString02, mtrapargsString03,
+ mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Start controller firmware transfer in the device.
+ The first argument is the host device serial number.
+ The second argument is the host model name that initiated the transfer.
+ The third argument is the name of the file that is transferred.
+ The fourth argument is the updated revision of the file, if available
+ The fifth argument is the reason for the update, if available
+ (1=User request, 2=Automatic upgrade by NMC, 3=Unknown)."
+ --#TYPE "APC: Start update transfer."
+ --#SUMMARY "Start update transfer."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 499
+
+xAPCControllerFirmwareUpdateTransferComplete TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString05, mtrapargsString04, mtrapargsString02,
+ mtrapargsString03, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Transfer of controller firmware was completed in the device.
+ The first argument is the host device serial number.
+ The second argument is the host device model name that completed the transfer.
+ The third argument is the name of the file that was transferred.
+ The fourth argument is the revision of the file that was transferred, if available."
+ --#TYPE "APC : Update transfer complete."
+ --#SUMMARY "Update transfer complete."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 500
+
+
+xAPCControllerFirmwareUpdateTransferFailed TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString05, mtrapargsString04, mtrapargsString02,
+ mtrapargsString03, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Transfer of controller firmware failed.
+ The first argument is the host device serial number.
+ The second argument is the host device model name that failed to transfer.
+ The third argument is the name of the file that failed the transfer, if available.
+ The fourth argument is the reason for failure."
+ --#TYPE "APC: Update transfer failed."
+ --#SUMMARY "Update transfer failed."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 501
+
+upsPfcInputRelayFailure TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: The PFC (Power Factor Correction) input relay failure exists."
+ --#TYPE "APC UPS: The PFC input relay failure exists."
+ --#SUMMARY "The PFC (Power Factor Correction) input relay failure exists."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 502
+
+upsPfcInputRelayFailureCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The PFC (Power Factor Correction) input relay failure cleared."
+ --#TYPE "APC UPS: The PFC input relay failure cleared."
+ --#SUMMARY "The PFC (Power Factor Correction) input relay failure cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 503
+
+upsInverterOverTemperature TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: The inverter over temperature condition exists."
+ --#TYPE "APC UPS: The inverter over temperature condition exists."
+ --#SUMMARY "The inverter over temperature condition exists."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 504
+
+upsInverterOverTemperatureCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The inverter over temperature condition cleared."
+ --#TYPE "APC UPS: The inverter over temperature condition cleared."
+ --#SUMMARY "The inverter over temperature condition cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 505
+
+upsBatteryOverVoltage TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: The battery over voltage condition exists."
+ --#TYPE "APC UPS: The battery over voltage condition exists."
+ --#SUMMARY "The battery over voltage condition exists."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 506
+
+upsBatteryOverVoltageCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The battery over voltage condition cleared."
+ --#TYPE "APC UPS: The battery over voltage condition cleared."
+ --#SUMMARY "The battery over voltage condition cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 507
+
+upsEepromFault TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: The EEPROM fault exists."
+ --#TYPE "APC UPS: The EEPROM fault exists."
+ --#SUMMARY "The EEPROM fault exists."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 508
+
+upsEepromFaultCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The EEPROM fault cleared."
+ --#TYPE "APC UPS: The EEPROM fault cleared."
+ --#SUMMARY "The EEPROM fault cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 509
+
+-- rARU Traps (part 2)
+
+aruFanRuntimeAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
+ rARUStatusAruIndex, rARUStatusAruName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "WARNING: The total running hours for a fan has exceeded
+ the run hour threshold.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the ARU number.
+ The fourth argument is the ARU name.
+ The fifth argument indicates which fan in the ARU."
+ --#TYPE "APC ARU: Fan Runhour Warning."
+ --#SUMMARY "Fan Runhour Alarm."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 510
+
+aruFanRuntimeAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
+ rARUStatusAruIndex, rARUStatusAruName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The total running hours for a fan is no longer
+ above the fan runhour threshold.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the ARU number.
+ The fourth argument is the ARU name.
+ The fifth argument indicates which fan in the ARU."
+ --#TYPE "APC ARU: Fan Runhour Alarm Cleared."
+ --#SUMMARY "Fan Runhour Alarm Cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 511
+
+
+aruFanPoorPerformanceAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
+ rARUStatusAruIndex, rARUStatusAruName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "WARNING: Poor fan performance has been detected in the ARU,
+ indicating that the fan may be close to failing.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the ARU number.
+ The fourth argument is the ARU name.
+ The fifth argument indicates which fan in the ARU."
+ --#TYPE "APC ARU: Poor Fan Performance Warning."
+ --#SUMMARY "Fan Health Alarm."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 512
+
+aruFanPoorPerformanceAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
+ rARUStatusAruIndex, rARUStatusAruName, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Fan performance is no longer degraded.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the ARU number.
+ The fourth argument is the ARU name.
+ The fifth argument indicates which fan in the ARU."
+ --#TYPE "APC ARU: Poor Fan Performance Warning Cleared."
+ --#SUMMARY "Fan Health Alarm Cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 513
+
+aruRedundantPowerLostAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
+ rARUStatusAruIndex, rARUStatusAruName, mtrapargsString }
+ DESCRIPTION
+ "WARNING: One of the redundant line cords on the ARU is no longer receiving AC power.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the ARU number.
+ The fourth argument is the ARU name."
+ --#TYPE "APC ARU: Redundant AC Input is not Present."
+ --#SUMMARY "AC Redundancy Lost."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 514
+
+aruRedundantPowerLostAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { emsIdentSerialNumber, emsIdentEMSName,
+ rARUStatusAruIndex, rARUStatusAruName, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Line-cord redundancy has been restored to the ARU.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the ARU number.
+ The fourth argument is the ARU name."
+ --#TYPE "APC ARU: Redundant AC Input is Present."
+ --#SUMMARY "AC Redundancy Restored."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 515
+
+apcDeviceConfigChange TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A device configuration change has been made on the device.
+ The first argument is the device serial number.
+ The second argument is the device name.
+ The third argument is a secondary device id number."
+ --#TYPE "APC: A device configuration change on a device."
+ --#SUMMARY "A device configuration change has been made on a device."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 516
+
+apcEnvSensorConnected TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
+ mtrapargsInteger, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A sensor has been connected to the host device.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is the sensor number.
+ The fifth argument is the sensor name."
+ --#TYPE "APC ENV: Sensor Connected."
+ --#SUMMARY "Sensor Connected."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 517
+
+apcEnvSensorDisconnected TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
+ mtrapargsInteger, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: A sensor has been disconnected from the device.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is the sensor number.
+ The fifth argument is the sensor name."
+ --#TYPE "APC ENV: Sensor Disconnected."
+ --#SUMMARY "Sensor Disconnected."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 518
+
+apcEnvMaxTempThresholdViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
+ mtrapargsInteger, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Max temperature threshold violated on the sensor.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is the sensor number.
+ The fifth argument is the sensor name."
+ --#TYPE "APC ENV: Max temperature threshold violation."
+ --#SUMMARY "Max temperature threshold violation."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 519
+
+apcEnvMaxTempThresholdViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
+ mtrapargsInteger, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Max temperature threshold violation cleared on the sensor.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is the sensor number.
+ The fifth argument is the sensor name."
+ --#TYPE "APC ENV: Max temperature threshold violation cleared."
+ --#SUMMARY "Max temperature threshold violation cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 520
+
+apcEnvHighTempThresholdViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
+ mtrapargsInteger, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "WARNING: High temperature threshold violated on the sensor.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is the sensor number.
+ The fifth argument is the sensor name."
+ --#TYPE "APC ENV: High temperature threshold violation."
+ --#SUMMARY "High temperature threshold violation."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 521
+
+apcEnvHighTempThresholdViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
+ mtrapargsInteger, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: High temperature threshold violation cleared on the sensor.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is the sensor number.
+ The fifth argument is the sensor name."
+ --#TYPE "APC ENV: High temperature threshold violation cleared."
+ --#SUMMARY "High temperature threshold violation cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 522
+
+apcEnvLowTempThresholdViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
+ mtrapargsInteger, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "WARNING: Low temperature threshold violated on the sensor.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is the sensor number.
+ The fifth argument is the sensor name."
+ --#TYPE "APC ENV: Low temperature threshold violation."
+ --#SUMMARY "Low temperature threshold violation."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 523
+
+apcEnvLowTempThresholdViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
+ mtrapargsInteger, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Low temperature threshold violation cleared on the sensor.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is the sensor number.
+ The fifth argument is the sensor name."
+ --#TYPE "APC ENV: Low temperature threshold violation cleared."
+ --#SUMMARY "Low temperature threshold violation cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 524
+
+apcEnvMinTempThresholdViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
+ mtrapargsInteger, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Min temperature threshold violated on the sensor.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is the sensor number.
+ The fifth argument is the sensor name."
+ --#TYPE "APC ENV: Min temperature threshold violation."
+ --#SUMMARY "Min temperature threshold violation."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 525
+
+apcEnvMinTempThresholdViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
+ mtrapargsInteger, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Min temperature threshold violation cleared on the sensor.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The sixth argument is the sensor number.
+ The seventh argument is the sensor name."
+ --#TYPE "APC ENV: Min temperature threshold violation cleared."
+ --#SUMMARY "Min temperature threshold violation cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 526
+
+apcEnvSTIncTempRateViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
+ mtrapargsInteger, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Short-term increasing temperature rate violated on the sensor.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is the sensor number.
+ The fifth argument is the sensor name."
+ --#TYPE "APC ENV: Short-term inc. temp rate violation."
+ --#SUMMARY "Short-term inc. temp rate violation."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 527
+
+apcEnvSTIncTempRateViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
+ mtrapargsInteger, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Short-term increasing temperature rate cleared on the sensor.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is the sensor number.
+ The fifth argument is the sensor name."
+ --#TYPE "APC ENV: Short-term inc. temp rate violation cleared."
+ --#SUMMARY "Short-term inc. temp rate violation cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 528
+
+apcEnvSTDecTempRateViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
+ mtrapargsInteger, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Short-term decreasing temperature rate violated on the sensor.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is the sensor number.
+ The fifth argument is the sensor name."
+ --#TYPE "APC ENV: Short-term dec. temp rate violation."
+ --#SUMMARY "Short-term dec. temp rate violation."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 529
+
+apcEnvSTDecTempRateViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
+ mtrapargsInteger, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Short-term decreasing temperature rate cleared on the sensor.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is the sensor number.
+ The fifth argument is the sensor name."
+ --#TYPE "APC ENV: Short-term dec. temp rate violation cleared."
+ --#SUMMARY "Short-term dec. temp rate violation cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 530
+
+apcEnvLTIncTempRateViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
+ mtrapargsInteger, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Long-term increasing temperature rate violated on the sensor.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is the sensor number.
+ The fifth argument is the sensor name."
+ --#TYPE "APC ENV: Long-term inc. temp rate violation."
+ --#SUMMARY "Long-term inc. temp rate violation."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 531
+
+apcEnvLTIncTempRateViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
+ mtrapargsInteger, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Long-term increasing temperature rate cleared on the sensor.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is the sensor number.
+ The fifth argument is the sensor name."
+ --#TYPE "APC ENV: Long-term inc. temp rate violation cleared."
+ --#SUMMARY "Long-term inc. temp rate violation cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 532
+
+apcEnvLTDecTempRateViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
+ mtrapargsInteger, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Long-term decreasing temperature rate violated on the sensor.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is the sensor number.
+ The fifth argument is the sensor name."
+ --#TYPE "APC ENV: Long-term dec. temp rate violation."
+ --#SUMMARY "Long-term dec. temp rate violation."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 533
+
+apcEnvLTDecTempRateViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
+ mtrapargsInteger, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Long-term decreasing temperature rate cleared on the sensor.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is the sensor number.
+ The fifth argument is the sensor name."
+ --#TYPE "APC ENV: Long-term dec. temp rate violation cleared."
+ --#SUMMARY "Long-term dec. temp rate violation cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 534
+
+apcEnvMaxHumidityThresholdViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
+ mtrapargsInteger, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Max humidity threshold violated on the sensor.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is the sensor number.
+ The fifth argument is the sensor name."
+ --#TYPE "APC ENV: Max humidity threshold violation."
+ --#SUMMARY "Max humidity threshold violation."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 535
+
+apcEnvMaxHumidityThresholdViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
+ mtrapargsInteger, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Max humidity threshold violation cleared on the sensor.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is the sensor number.
+ The fifth argument is the sensor name."
+ --#TYPE "APC ENV: Max humidity threshold violation cleared."
+ --#SUMMARY "Max humidity threshold violation cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 536
+
+apcEnvHighHumidityThresholdViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
+ mtrapargsInteger, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "WARNING: High humidity threshold violated on the sensor.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is the sensor number.
+ The fifth argument is the sensor name."
+ --#TYPE "APC ENV: High humidity threshold violation."
+ --#SUMMARY "High humidity threshold violation."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 537
+
+apcEnvHighHumidityThresholdViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
+ mtrapargsInteger, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: High humidity threshold violation cleared on the sensor.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is the sensor number.
+ The fifth argument is the sensor name."
+ --#TYPE "APC ENV: High humidity threshold violation cleared."
+ --#SUMMARY "High humidity threshold violation cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 538
+
+apcEnvLowHumidityThresholdViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
+ mtrapargsInteger, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "WARNING: Low humidity threshold violated on the sensor.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is the sensor number.
+ The fifth argument is the sensor name."
+ --#TYPE "APC ENV: Low humidity threshold violation."
+ --#SUMMARY "Low humidity threshold violation."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 539
+
+apcEnvLowHumidityThresholdViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
+ mtrapargsInteger, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Low humidity threshold violation cleared on the sensor.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is the sensor number.
+ The fifth argument is the sensor name."
+ --#TYPE "APC ENV: Low humidity threshold violation cleared."
+ --#SUMMARY "Low humidity threshold violation cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 540
+
+apcEnvMinHumidityThresholdViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
+ mtrapargsInteger, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Min humidity threshold violated on the sensor.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is the sensor number.
+ The fifth argument is the sensor name."
+ --#TYPE "APC ENV: Min humidity threshold violation."
+ --#SUMMARY "Min humidity threshold violation."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 541
+
+apcEnvMinHumidityThresholdViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
+ mtrapargsInteger, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Min humidity threshold violation cleared on the sensor.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is the sensor number.
+ The fifth argument is the sensor name."
+ --#TYPE "APC ENV: Min humidity threshold violation cleared."
+ --#SUMMARY "Min humidity threshold violation cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 542
+
+apcBeaconConnected TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A beacon has been connected to the device.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number."
+ --#TYPE "APC: Beacon Connected."
+ --#SUMMARY "Beacon Connected."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 543
+
+apcBeaconDisconnected TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: A beacon has been disconnected from the device.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number. "
+ --#TYPE "APC: Beacon Disconnected."
+ --#SUMMARY "Beacon Disconnected."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 544
+
+apcBeaconOn TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A beacon has gone on (activated).
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number. "
+ --#TYPE "APC: Beacon On."
+ --#SUMMARY "Beacon On."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 545
+
+apcBeaconOff TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A beacon has gone off (deactivated).
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number. "
+ --#TYPE "APC: Beacon Off."
+ --#SUMMARY "Beacon Off."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 546
+
+apcOutletStateAbnormal TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04, mtrapargsInteger, mtrapargsString04,
+ mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "WARNING: An outlet on the device has changed to its abnormal state.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is the outlet number.
+ The fifth argument is the outlet name.
+ The sixth argument is the current outlet state (1=ON, 2=OFF).
+ The seventh argument is the configured normal outlet state (1=ON, 2=OFF)."
+ --#TYPE "APC: Outlet has changed to its abnormal state."
+ --#SUMMARY "Outlet has changed to its abnormal state."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 547
+
+apcOutletStateNormal TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04, mtrapargsInteger, mtrapargsString04,
+ mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: An outlet on the device has changed to its normal state.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is the outlet number.
+ The fifth argument is the outlet name.
+ The sixth argument is the current outlet state (1=ON, 2=OFF).
+ The seventh argument is the configured normal outlet state (1=ON, 2=OFF)."
+ --#TYPE "APC: Outlet has changed to its normal state."
+ --#SUMMARY "Outlet has changed to its normal state."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 548
+
+apcOutputRelayStateAbnormal TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04, mtrapargsInteger,
+ mtrapargsString04, mtrapargsInteger02,
+ mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "WARNING: An output relay on the device has changed to its abnormal state.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is the output relay number.
+ The fifth argument is the output relay name.
+ The sixth argument is the current output relay state (1=CLOSED, 2=OPEN).
+ The seventh argument is the configured normal output relay state (1=CLOSED, 2=OPEN)."
+ --#TYPE "APC: Output Relay has changed to its abnormal state."
+ --#SUMMARY "Output Relay has changed to its abnormal state."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 549
+
+apcOutputRelayStateNormal TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04, mtrapargsInteger,
+ mtrapargsString04, mtrapargsInteger02,
+ mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: An output relay on the device has changed to its normal state.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is the output relay number.
+ The fifth argument is the output relay name.
+ The sixth argument is the current output relay state (1=CLOSED, 2=OPEN).
+ The seventh argument is the configured normal output relay state (1=CLOSED, 2=OPEN)."
+ --#TYPE "APC: Output Relay has changed to its normal state."
+ --#SUMMARY "Output Relay has changed to its normal state."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 550
+
+apcHardwareStateAbnormal TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
+ mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+
+ "SEVERE: The device's hardware is improperly configured and operating outside
+ normal bounds for the hardware. This can be caused by improper devices being
+ connected to device ports or Alink Current limit detection.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is a hardware specific state code."
+
+ --#TYPE "APC: Hardware is in an abnormal state."
+ --#SUMMARY "Hardware is in an abnormal state."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 551
+
+apcHardwareStateNormal TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03,
+ mtrapargsInteger04, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The device's hardware is in its normal operational state.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number."
+ --#TYPE "APC EMS: Hardware is in a normal state."
+ --#SUMMARY "Hardware is in its normal state."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 552
+
+apcCriticalDiscreteInputContactStateAbnormal TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04, mtrapargsInteger,
+ mtrapargsString04, mtrapargsInteger02,
+ mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: A discrete input contact on the device has changed to its abnormal state.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is the input contact number.
+ The fifth argument is the input contact name.
+ The sixth argument is the input contact state (1=CLOSED, 2=OPEN).
+ The seventh argument is the configured normal input contact state (1=CLOSED, 2=OPEN)."
+ --#TYPE "APC: Discrete input contact has changed to its abnormal state."
+ --#SUMMARY "Discrete input contact has changed to its abnormal state."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 553
+
+apcCriticalDiscreteInputContactStateNormal TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04, mtrapargsInteger,
+ mtrapargsString04, mtrapargsInteger02,
+ mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A discrete input contact on the device has changed to its normal state.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is the input contact number.
+ The fifth argument is the input contact name.
+ The sixth argument is the input contact state (1=CLOSED, 2=OPEN).
+ The seventh argument is the configured normal input contact state (1=CLOSED, 2=OPEN)."
+ --#TYPE "APC: Discrete input contact has changed to its normal state."
+ --#SUMMARY "Discrete input contact has changed to its normal state."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 554
+
+apcWarningDiscreteInputContactStateAbnormal TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04, mtrapargsInteger,
+ mtrapargsString04, mtrapargsInteger02,
+ mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "WARNING: A discrete input contact on the device has changed to its abnormal state.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is the input contact number.
+ The fifth argument is the input contact name.
+ The sixth argument is the input contact state (1=CLOSED, 2=OPEN).
+ The seventh argument is the configured normal input contact state (1=CLOSED, 2=OPEN)."
+ --#TYPE "APC: Discrete input contact has changed to its abnormal state."
+ --#SUMMARY "Discrete input contact has changed to its abnormal state."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 555
+
+apcWarningDiscreteInputContactStateNormal TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04, mtrapargsInteger,
+ mtrapargsString04, mtrapargsInteger02,
+ mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A discrete input contact on the device has changed to its normal state.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is the input contact number.
+ The fifth argument is the input contact name.
+ The sixth argument is the input contact state (1=CLOSED, 2=OPEN).
+ The seventh argument is the configured normal input contact state (1=CLOSED, 2=OPEN)."
+ --#TYPE "APC: Discrete input contact has changed to its normal state."
+ --#SUMMARY "Discrete input contact has changed to its normal state."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 556
+
+apcInformationalDiscreteInputContactStateAbnormal TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04, mtrapargsInteger,
+ mtrapargsString04, mtrapargsInteger02,
+ mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A discrete input contact on the device has changed to its abnormal state.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is the input contact number.
+ The fifth argument is the input contact name.
+ The sixth argument is the input contact state (1=CLOSED, 2=OPEN).
+ The seventh argument is the configured normal input contact state (1=CLOSED, 2=OPEN)."
+ --#TYPE "APC: Discrete input contact has changed to its abnormal state."
+ --#SUMMARY "Discrete input contact has changed to its abnormal state."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 557
+
+apcInformationalDiscreteInputContactStateNormal TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04, mtrapargsInteger,
+ mtrapargsString04, mtrapargsInteger02,
+ mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A discrete input contact on the device has changed to its normal state.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is the input contact number.
+ The fifth argument is the input contact name.
+ The sixth argument is the input contact state (1=CLOSED, 2=OPEN).
+ The seventh argument is the configured normal input contact state (1=CLOSED, 2=OPEN)."
+ --#TYPE "APC: Discrete input contact has changed to its normal state."
+ --#SUMMARY "Discrete input contact has changed to its normal state."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 558
+
+apcAnalogInputMaxThresholdViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
+ mtrapargsInteger, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Maximum threshold violated on an analog input.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is the input number.
+ The fifth argument is the input name."
+ --#TYPE "APC: Maximum threshold violation on analog input."
+ --#SUMMARY "Max threshold violation on input."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 559
+
+apcAnalogInputMaxThresholdViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
+ mtrapargsInteger, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Maximum threshold violation cleared on the analog input.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is the input number.
+ The fifth argument is the input name."
+ --#TYPE "APC: Max threshold violation cleared."
+ --#SUMMARY "Max threshold violation cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 560
+
+apcAnalogInputHighThresholdViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
+ mtrapargsInteger, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "WARNING: High threshold violated on an analog input.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is the input number.
+ The fifth argument is the input name."
+ --#TYPE "APC: High threshold violation on analog input."
+ --#SUMMARY "High threshold violation on input."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 561
+
+apcAnalogInputHighThresholdViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
+ mtrapargsInteger, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: High threshold violation cleared on the analog input.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is the input number.
+ The fifth argument is the input name."
+ --#TYPE "APC: High threshold violation cleared."
+ --#SUMMARY "High threshold violation cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 562
+
+apcAnalogInputLowThresholdViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
+ mtrapargsInteger, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "WARNING: Low threshold violated on an analog input.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is the input number.
+ The fifth argument is the input name."
+ --#TYPE "APC: Low threshold violation on analog input."
+ --#SUMMARY "Low threshold violation on input."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 563
+
+apcAnalogInputLowThresholdViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
+ mtrapargsInteger, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Low threshold violation cleared on the analog input.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is the input number.
+ The fifth argument is the input name."
+ --#TYPE "APC: Low threshold violation cleared."
+ --#SUMMARY "Low threshold violation cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 564
+
+apcAnalogInputMinThresholdViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
+ mtrapargsInteger, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Minimum threshold violated on an analog input.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is the input number.
+ The fifth argument is the input name."
+ --#TYPE "APC: Min threshold violation on analog input."
+ --#SUMMARY "Min threshold violation on input."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 565
+
+apcAnalogInputMinThresholdViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04,
+ mtrapargsInteger, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Minimum threshold violation cleared on the analog input.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is a secondary device id number.
+ The fourth argument is the input number.
+ The fifth argument is the input name."
+ --#TYPE "APC: Min threshold violation cleared."
+ --#SUMMARY "Min threshold violation cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 566
+
+apcDeviceClearLostComms TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Lost communications reset command has been issued.
+ The first argument is the device serial number.
+ The second argument is the device name.
+ The third argument is a secondary device id number."
+ --#TYPE "APC: Lost communications reset command has been issued."
+ --#SUMMARY "Lost communications reset command has been issued."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+
+ ::= 567
+
+apcDeviceConnected TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03,
+ mtrapargsInteger, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A device has been connected to the host.
+ The first argument is the host serial number.
+ The second argument is the host name.
+ The third argument is the device number.
+ The fourth argument is the device name."
+ --#TYPE "APC: Device Connected."
+ --#SUMMARY "Device Connected."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 568
+
+apcDeviceDisconnected TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03,
+ mtrapargsInteger, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: A device has been disconnected from the host.
+ The first argument is the host serial number.
+ The second argument is the host name.
+ The third argument is the device number.
+ The fourth argument is the device name."
+ --#TYPE "APC: Device Disconnected."
+ --#SUMMARY "Device Disconnected."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 569
+
+apcUnregisteredUserAccessDenied TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsString04,
+ mtrapargsInteger, mtrapargsString05, mtrapargsString}
+ DESCRIPTION
+ "INFORMATIONAL: An unregistered user has tried to access the device.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the host device location.
+ The fourth argumant is the door identifier.
+ The fifth argument is the unregistered user's RFID."
+ --#TYPE "APC: Unregistered user."
+ --#SUMMARY "Unregistered user."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 570
+
+
+apcRegisteredUserAccessDenied TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsString04,
+ mtrapargsInteger, mtrapargsString05, mtrapargsString}
+ DESCRIPTION
+ "INFORMATIONAL: A registered user has been denied access to the device.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the host device location.
+ The fourth argumant is the door identifier.
+ The fifth argument is the user name."
+ --#TYPE "APC: Access denied."
+ --#SUMMARY "Access denied."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 571
+
+apcRegisteredUserConfigChange TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03,
+ mtrapargsString04, mtrapargsString05, mtrapargsString}
+ DESCRIPTION
+ "INFORMATIONAL: Registered user configuration change.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the host device location.
+ The fourth argument is the user name."
+ --#TYPE "APC: Registered user configuration change."
+ --#SUMMARY "Registered user configuration change."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 572
+
+apcDoorUnlocked TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsString04,
+ mtrapargsInteger, mtrapargsString05, mtrapargsInteger02, mtrapargsString}
+ DESCRIPTION
+ "INFORMATIONAL: A door has been unlocked.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the host device location.
+ The fourth argument is the door identifier.
+ The fifth argument is the door access user.
+ The sixth argument is the door access type."
+ --#TYPE "APC: Door unlocked."
+ --#SUMMARY "Door unlocked."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 573
+
+apcDoorLocked TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsString04,
+ mtrapargsInteger, mtrapargsString05, mtrapargsInteger02, mtrapargsString}
+ DESCRIPTION
+ "INFORMATIONAL: A door has been locked.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the host device location.
+ The fourth argument is the door identifier.
+ The fifth argument is the door access user.
+ The sixth argument is the door access type."
+ --#TYPE "APC: Door locked."
+ --#SUMMARY "Door locked."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 574
+
+apcHandleOpened TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03,
+ mtrapargsString04, mtrapargsInteger, mtrapargsString}
+ DESCRIPTION
+ "INFORMATIONAL: A door handle has been opened.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the host device location.
+ The fourth argument is the door identifier, (1=front, 2=rear)."
+ --#TYPE "APC: Door handle opened."
+ --#SUMMARY "Door handle opened."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 575
+
+apcHandleClosed TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03,
+ mtrapargsString04, mtrapargsInteger, mtrapargsString}
+ DESCRIPTION
+ "INFORMATIONAL: A door handle has been closed.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the host device location.
+ The fourth argument is the door identifier, (1=front, 2=rear)."
+ --#TYPE "APC: Door handle closed."
+ --#SUMMARY "Door handle closed."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 576
+
+
+apcDoorOpened TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03,
+ mtrapargsString04, mtrapargsInteger, mtrapargsString}
+ DESCRIPTION
+ "INFORMATIONAL: A door has been opened.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the host device location.
+ The fourth argument is the door identifier, (1=front, 2=rear)."
+ --#TYPE "APC: Door opened."
+ --#SUMMARY "Door opened."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 577
+
+apcDoorClosed TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03,
+ mtrapargsString04, mtrapargsInteger, mtrapargsString}
+ DESCRIPTION
+ "INFORMATIONAL: A door has been closed.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the host device location.
+ The fourth argument is the door identifier, (1=front, 2=rear)."
+ --#TYPE "APC: Door closed."
+ --#SUMMARY "Door closed."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 578
+
+ -- trap number 579 available
+
+
+apcKeyOverrideUnlocked TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03,
+ mtrapargsString04, mtrapargsInteger, mtrapargsString}
+ DESCRIPTION
+ "SEVERE: Key override unlock has occurred.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the host device location.
+ The fourth argument is the door identifier, (1=front, 2=rear)."
+ --#TYPE "APC: Key override unlock has occurred."
+ --#SUMMARY "Key override unlock has occurred."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 580
+
+
+apcKeyOverrideLocked TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03,
+ mtrapargsString04, mtrapargsInteger, mtrapargsString}
+ DESCRIPTION
+ "INFORMATIONAL: Key override lock has occurred.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the host device location.
+ The fourth argument is the door identifier, (1=front, 2=rear)."
+ --#TYPE "APC: Key override lock has occurred."
+ --#SUMMARY "Key override lock has occurred."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 581
+
+apcForcedEntry TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03,
+ mtrapargsString04, mtrapargsInteger, mtrapargsString}
+ DESCRIPTION
+ "SEVERE: A forced entry condition has occurred.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the host device location.
+ The fourth argument is the door identifier, (1=front, 2=rear)."
+ --#TYPE "APC: A forced entry condition has occurred."
+ --#SUMMARY "A forced entry has occurred."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 582
+
+apcForcedEntryCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03,
+ mtrapargsString04, mtrapargsInteger, mtrapargsString}
+ DESCRIPTION
+ "INFORMATIONAL: A forced entry condition has been cleared.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the host device location.
+ The fourth argument is the door identifier, (1=front, 2=rear)."
+ --#TYPE "APC: A forced entry condition has been cleared."
+ --#SUMMARY "A forced entry has been cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 583
+
+
+apcRelockTimeout TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03,
+ mtrapargsString04, mtrapargsInteger, mtrapargsString}
+ DESCRIPTION
+ "SEVERE: A relock timout has occurred.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the host device location.
+ The fourth argument is the door identifier, (1=front, 2=rear)."
+ --#TYPE "APC: Relock timout."
+ --#SUMMARY "Relock timeout."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 584
+
+apcRelockTimeoutCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03,
+ mtrapargsString04, mtrapargsInteger, mtrapargsString}
+ DESCRIPTION
+ "INFORMATIONAL: A relock timout has been cleared.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the host device location.
+ The fourth argument is the door identifier, (1=front, 2=rear)."
+ --#TYPE "APC: relock timout has been cleared."
+ --#SUMMARY "Relock timout has been cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 585
+
+apcDoorSenseDisconnected TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03,
+ mtrapargsString04, mtrapargsInteger, mtrapargsString}
+ DESCRIPTION
+ "SEVERE: A door sensor was disconnected.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the host device location.
+ The fourth argument is the door identifier, (1=front, 2=rear)."
+ --#TYPE "APC: A door sensor was disconnected."
+ --#SUMMARY "A door sensor was disconnected."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 586
+
+apcDoorSenseConnected TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03,
+ mtrapargsString04, mtrapargsInteger, mtrapargsString}
+ DESCRIPTION
+ "INFORMATIONAL: A forced entry condition has been cleared.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the host device location.
+ The fourth argument is the door identifier, (1=front, 2=rear)."
+ --#TYPE "APC: A door sensor was connected."
+ --#SUMMARY "A door sensor was connected."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 587
+
+
+apcDoorLostComms TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03,
+ mtrapargsString04, mtrapargsInteger, mtrapargsString}
+ DESCRIPTION
+ "SEVERE: Communications have been lost with the door.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the host device location.
+ The fourth argument is the door identifier, (1=front, 2=rear)."
+ --#TYPE "APC: A door has lost communications."
+ --#SUMMARY "A door has lost communications."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 588
+
+apcDoorEstablishedComms TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03,
+ mtrapargsString04, mtrapargsInteger, mtrapargsString}
+ DESCRIPTION
+ "INFORMATIONAL: Communications have been established with the door.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the host device location.
+ The fourth argument is the door identifier, (1=front, 2=rear)."
+ --#TYPE "APC: A door has established communications."
+ --#SUMMARY "A door has established communications."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 589
+
+
+
+apcRegisteredUserAccessChange TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03,
+ mtrapargsString04, mtrapargsString05, mtrapargsString}
+ DESCRIPTION
+ "INFORMATIONAL: Registered user access changed.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the host device location.
+ The fourth argument is the user name."
+ --#TYPE "APC: Registered user access change."
+ --#SUMMARY "Registered user access change."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 590
+
+
+apcUnregisteredUserStatusChange TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03,
+ mtrapargsString04, mtrapargsString05, mtrapargsString}
+ DESCRIPTION
+ "INFORMATIONAL: Unregistered user status changed.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the host device location.
+ The fourth argument is the user name."
+ --#TYPE "APC: Unregistered user status change."
+ --#SUMMARY "Unregistered user status change."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 591
+
+apcDeviceClearUserConfigs TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger04, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: User configurations reset command has been issued.
+ The first argument is the device serial number.
+ The second argument is the device name.
+ The third argument is a secondary device id number."
+ --#TYPE "APC: User configurations reset command has been issued."
+ --#SUMMARY "User configurations reset command has been issued."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 592
+
+-- Add more events starting at 600 for UPS Devices
+
+upsBatteryTempSensorFault TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: The battery temperature sensor fault exists."
+ --#TYPE "APC UPS: The battery temperature sensor fault exists."
+ --#SUMMARY "The battery temperature sensor fault exists."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 600
+
+upsBatteryTempSensorFaultCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The battery temperature sensor fault cleared."
+ --#TYPE "APC UPS: The battery temperature sensor fault cleared."
+ --#SUMMARY "The battery temperature sensor fault cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 601
+
+upsBatterySoftBusStartFault TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: A battery bus soft start fault exists."
+ --#TYPE "APC UPS: A battery bus soft start fault exists."
+ --#SUMMARY "A battery bus soft start fault exists."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 602
+
+upsBatterySoftBusStartFaultCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A battery bus soft start fault exists cleared."
+ --#TYPE "APC UPS: A battery bus soft start fault exists cleared."
+ --#SUMMARY "A battery bus soft start fault exists cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 603
+
+apcOutputShortCircuit TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: An output short circuit condition exists."
+ --#TYPE "APC Device: An output short circuit condition exists."
+ --#SUMMARY "An output short circuit condition exists."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 604
+
+apcOutputShortCircuitCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: An output short circuit condition cleared."
+ --#TYPE "APC Device: An output short circuit condition cleared."
+ --#SUMMARY "An output short circuit condition cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 605
+
+apcOutputRelayFault TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: An output relay (or its driver) fault exists."
+ --#TYPE "APC Device: An output relay (or its driver) fault exists."
+ --#SUMMARY "An output relay (or its driver) fault exists."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 606
+
+apcOutputRelayFaultCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: An output relay (or its driver) fault cleared."
+ --#TYPE "APC Device: An output relay (or its driver) fault cleared."
+ --#SUMMARY "An output relay (or its driver) fault cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 607
+
+upsPfcFault TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: A PFC fault exists."
+ --#TYPE "APC UPS: A PFC fault exists."
+ --#SUMMARY "A PFC fault exists."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 608
+
+upsPfcFaultCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The PFC fault cleared."
+ --#TYPE "APC UPS: The PFC fault cleared."
+ --#SUMMARY "The PFC fault cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 609
+
+apcDcBusOverVoltage TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: The DC bus voltage is too high."
+ --#TYPE "APC Devcie: DC bus voltage is too high."
+ --#SUMMARY "The DC bus voltage is too high."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 610
+
+apcDcBusOverVoltageCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The DC bus voltage is too high cleared."
+ --#TYPE "APC Device: The DC bus voltage is too high cleared."
+ --#SUMMARY "The DC bus voltage is too high cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 611
+
+upsInverterFault TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: The inverter fault exists."
+ --#TYPE "APC UPS: The inverter fault exists."
+ --#SUMMARY "The inverter fault exists."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 612
+
+upsInverterFaultCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The inverter fault cleared."
+ --#TYPE "APC UPS: The inverter fault cleared."
+ --#SUMMARY "The inverter fault cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 613
+
+apcAdConverterFault TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: The A/D converter fault exists."
+ --#TYPE "APC Device: The A/D converter fault exists."
+ --#SUMMARY "The A/D converter fault exists."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 614
+
+apcAdConverterFaultCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The A/D converter fault cleared."
+ --#TYPE "APC Device: The A/D converter fault cleared."
+ --#SUMMARY "The A/D converter fault cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 615
+
+apcLogicPowerSupplyFault TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: A logic power supply fault exists."
+ --#TYPE "APC Device: A logic power supply fault exists."
+ --#SUMMARY "A logic power supply fault exists."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 616
+
+apcLogicPowerSupplyFaultCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A logic power supply fault cleared."
+ --#TYPE "APC Device: A logic power supply fault cleared."
+ --#SUMMARY "A logic power supply fault cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 617
+
+apcTransformerDCImbalanceFault TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: The DC component of the transformer's current is too high."
+ --#TYPE "APC Device: The DC component of the tformer's curr is too high."
+ --#SUMMARY "The DC component of the transformer's current is too high."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 618
+
+apcTransformerDCImbalanceFaultCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: The DC component of the transformer's current is normal."
+ --#TYPE "APC Device: The DC component of the tformer's curr is normal."
+ --#SUMMARY "The DC component of the transformer's current is normal."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 619
+
+upsBackfeedRelayFault TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: The backfeed relay (or its driver) has a fault."
+ --#TYPE "UPS Device: The backfeed relay (or its driver) has a fault."
+ --#SUMMARY "The backfeed relay (or its driver) has a fault."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 620
+
+upsBackfeedRelayFaultCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: The backfeed relay (or its driver) has a fault cleared."
+ --#TYPE "UPS Device: The bfeed rly (or its drver) has a flt cleared."
+ --#SUMMARY "The backfeed relay (or its driver) has a fault cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 621
+
+upsBypassRelayFault TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: A bypass relay (or its driver) has a fault."
+ --#TYPE "APC Device: A bypass relay (or its driver) has a fault."
+ --#SUMMARY "A bypass relay (or its driver) has a fault."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 622
+
+upsBypassRelayFaultCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: A bypass relay (or its driver) has a fault cleared."
+ --#TYPE "APC Device: A bypass relay (or its driver) has a fault cleared."
+ --#SUMMARY "A bypass relay (or its driver) has a fault cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 623
+
+
+xPDUBranchCurrentMinAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
+ mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The current in a branch circuit is outside the limits specified for that
+ branch circuit.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the panel position of the branch circuit (1-based index).
+ The fourth argument is the measured current in tenths of Amps.
+ The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated."
+ --#TYPE "APC XPDU: Branch circuit minimum current alarm."
+ --#SUMMARY "Branch circuit current is below threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 626
+
+xPDUBranchCurrentMinAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
+ mtrapargsInteger02, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The current in a branch circuit is back within the limits
+ specified for that branch circuit.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the panel position of the branch circuit (1-based index).
+ The fourth argument is the measured current in tenths of Amps."
+ --#TYPE "APC XPDU: Branch circuit minimum current alarm cleared."
+ --#SUMMARY "Branch circuit low current alarm cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 627
+
+xPDUBranchCurrentMaxAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
+ mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The current in a branch circuit is outside the limits specified for that
+ branch circuit.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the panel position of the branch circuit (1-based index).
+ The fourth argument is the measured current in tenths of Amps.
+ The fifth argument is the threshold, in tenths of Amps, above which the alarm was generated."
+ --#TYPE "APC XPDU: Branch circuit maximum current alarm."
+ --#SUMMARY "Branch circuit current is above threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 628
+
+xPDUBranchCurrentMaxAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xPDUIdentSerialNumber, xPDUIdentProductName, mtrapargsInteger,
+ mtrapargsInteger02, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The current in a branch circuit is back within the limits
+ specified for that branch circuit.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the panel position of the branch circuit (1-based index).
+ The fourth argument is the measured current in tenths of Amps."
+ --#TYPE "APC XPDU: Branch circuit maximum current alarm cleared."
+ --#SUMMARY "Branch circuit high current alarm cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 629
+
+
+rPDUOutletLowLoad TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
+ rPDUOutletStatusIndex, mtrapargsString }
+ DESCRIPTION
+ "WARNING: A Rack PDU has violated the outlet low load threshold.
+ The first argument is the serial number.
+ The second argument is the device name.
+ The third argument is the outlet number."
+ --#TYPE "APC Rack PDU: Violation of outlet low load threshold."
+ --#SUMMARY "A Rack PDU has violated the outlet low load threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 630
+
+rPDUOutletLowLoadCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
+ rPDUOutletStatusIndex, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The outlet low load condition on a Rack PDU has been
+ cleared.
+ The first argument is the serial number.
+ The second argument is the device name.
+ The third argument is the outlet number."
+ --#TYPE "APC Rack PDU: Low load condition cleared."
+ --#SUMMARY "The low load condition on a Rack PDU has been cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 631
+
+rPDUOutletNearOverload TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
+ rPDUOutletStatusIndex, mtrapargsString }
+ DESCRIPTION
+ "WARNING: A Rack PDU is near an outlet overload condition.
+ The first argument is the serial number.
+ The second argument is the device name.
+ The third argument is the outlet number."
+ --#TYPE "APC Rack PDU: Near an overload condition."
+ --#SUMMARY "A Rack PDU is near an outlet overload condition."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 632
+
+rPDUOutletNearOverloadCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
+ rPDUOutletStatusIndex, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The outlet near overload condition on a Rack PDU has
+ been cleared.
+ The first argument is the serial number.
+ The second argument is the device name.
+ The third argument is the outlet number."
+ --#TYPE "APC Rack PDU: Outlet Near overload condition has cleared."
+ --#SUMMARY "Rack PDU outlet near overload condition has cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 633
+
+rPDUOutletOverload TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
+ rPDUOutletStatusIndex, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: A Rack PDU is in an overload condition.
+ The first argument is the serial number.
+ The second argument is the device name.
+ The third argument is the outlet number."
+ --#TYPE "APC Rack PDU: Outlet Overload condition."
+ --#SUMMARY "A Rack PDU is in an outlet overload condition."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 634
+
+rPDUOutletOverloadCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { rPDUIdentSerialNumber, rPDUIdentName,
+ rPDUOutletStatusIndex, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The outlet overload condition on a Rack PDU has been
+ cleared.
+ The first argument is the serial number.
+ The second argument is the device name.
+ The third argument is the outlet number."
+ --#TYPE "APC Rack PDU: Overload condition has cleared."
+ --#SUMMARY "The outlet overload condition on a Rack PDU has cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 635
+
+apcTestTrap TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsInteger02, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Trap used to test SNMP trap functionality.
+ The first argument is a place holder for test variables."
+ --#TYPE "APC: Test trap."
+ --#SUMMARY "Test Trap."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 636
+
+baseFanFailureCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Base module fan has been repaired"
+ --#TYPE "APC UPS: Base module fan has been repaired"
+ --#SUMMARY "The base module fan has been repaired."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 637
+
+
+
+atsLowLoad TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { atsIdentSerialNumber, atsConfigProductName,
+ atsOutputPhaseIndex, atsOutputBank, mtrapargsString }
+ DESCRIPTION
+ "WARNING: ATS has violated the bank or phase low load threshold.
+ The first argument is the serial number.
+ The second argument is the product name.
+ The third argument is the phase number
+ The fourth argument is the bank number. -1 is returned if bank does not exist."
+ --#TYPE "APC ATS: Violation of bank or phase low load threshold."
+ --#SUMMARY "ATS has violated the bank or phase low load threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 638
+
+atsLowLoadCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { atsIdentSerialNumber, atsConfigProductName,
+ atsOutputPhaseIndex, atsOutputBank, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The bank or phase low load condition on an ATS has been
+ cleared.
+ The first argument is the serial number.
+ The second argument is the product name.
+ The third argument is the phase number
+ The fourth argument is the bank number. -1 is returned if bank does not exist."
+ --#TYPE "APC ATS: Low load condition cleared."
+ --#SUMMARY "The low load condition on an ATS has been cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 639
+
+atsNearOverload TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { atsIdentSerialNumber, atsConfigProductName,
+ atsOutputPhaseIndex, atsOutputBank, mtrapargsString }
+ DESCRIPTION
+ "WARNING: ATS has violated the bank or phase near overload threshold.
+ The first argument is the serial number.
+ The second argument is the product name.
+ The third argument is the phase number
+ The fourth argument is the bank number. -1 is returned if bank does not exist."
+ --#TYPE "APC ATS: Near an overload condition."
+ --#SUMMARY "ATS is near a bank or phase overload condition."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 640
+
+atsNearOverloadCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { atsIdentSerialNumber, atsConfigProductName,
+ atsOutputPhaseIndex, atsOutputBank, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The bank or phase near overload condition on an ATS has
+ been cleared.
+ The first argument is the serial number.
+ The second argument is the product name.
+ The third argument is the phase number
+ The fourth argument is the bank number. -1 is returned if bank does not exist."
+ --#TYPE "APC ATS: Bank or phase near overload condition has cleared."
+ --#SUMMARY "ATS bank or phase near overload condition has cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 641
+
+atsOverload TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { atsIdentSerialNumber, atsConfigProductName,
+ atsOutputPhaseIndex, atsOutputBank, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: ATS is in an overload condition.
+ The first argument is the serial number.
+ The second argument is the product name.
+ The third argument is the phase number.
+ The fourth argument is the bank number. -1 is returned if bank does not exist."
+ --#TYPE "APC ATS: Bank or Phase Overload condition."
+ --#SUMMARY "ATS is in overload condition."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 642
+
+atsOverloadCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { atsIdentSerialNumber, atsConfigProductName,
+ atsOutputPhaseIndex, atsOutputBank, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The bank or phase overload condition on an ATS has been
+ cleared.
+ The first argument is the serial number.
+ The second argument is the product name.
+ The third argument is the phase number.
+ The fourth argument is the bank number. -1 is returned if bank does not exist."
+ --#TYPE "APC ATS: Overload condition has cleared."
+ --#SUMMARY "The bank or phase overload condition on an ATS has cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 643
+
+atsRMSOverVoltage TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { atsIdentSerialNumber, atsConfigProductName,
+ mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Overvoltage condition violated.
+ The first argument is the serial number.
+ The second argument is the product name.
+ The third argument is an integer representing the source: 0=A, 1=B."
+ --#TYPE "APC ATS: Overvoltage condition violated."
+ --#SUMMARY "Overvoltage condition violated."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 644
+
+atsRMSOverVoltageCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { atsIdentSerialNumber, atsConfigProductName,
+ mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Overvoltage condition cleared.
+ The first argument is the serial number.
+ The second argument is the product name.
+ The third argument is an integer representing the source: 0=A, 1=B."
+ --#TYPE "APC ATS: Overvoltage condition cleared."
+ --#SUMMARY "Overvoltage condition cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 645
+
+atsRMSUnderVoltage TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { atsIdentSerialNumber, atsConfigProductName,
+ mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Undervoltage condition violated.
+ The first argument is the serial number.
+ The second argument is the product name.
+ The third argument is an integer representing the source: 0=A, 1=B."
+ --#TYPE "APC ATS: Undervoltage condition violated."
+ --#SUMMARY "Undervoltage condition violated."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 646
+
+atsRMSUnderVoltageCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { atsIdentSerialNumber, atsConfigProductName,
+ mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Undervoltage condition cleared.
+ The first argument is the serial number.
+ The second argument is the product name.
+ The third argument is an integer representing the source: 0=A, 1=B."
+ --#TYPE "APC ATS: Undervoltage condition cleared."
+ --#SUMMARY "Undervoltage condition cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 647
+
+atsRMSOverFrequency TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { atsIdentSerialNumber, atsConfigProductName,
+ mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: OverFrequency condition violated.
+ The first argument is the serial number.
+ The second argument is the product name.
+ The third argument is an integer representing the source: 0=A, 1=B."
+ --#TYPE "APC ATS: OverFrequency condition violated."
+ --#SUMMARY "OverFrequency condition violated."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 648
+
+atsRMSOverFrequencyCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { atsIdentSerialNumber, atsConfigProductName,
+ mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: OverFrequency condition cleared.
+ The first argument is the serial number.
+ The second argument is the product name.
+ The third argument is an integer representing the source: 0=A, 1=B."
+ --#TYPE "APC ATS: OverFrequency condition cleared."
+ --#SUMMARY "OverFrequency condition cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 649
+
+atsRMSUnderFrequency TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { atsIdentSerialNumber, atsConfigProductName,
+ mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: UnderFrequency condition violated.
+ The first argument is the serial number.
+ The second argument is the product name.
+ The third argument is an integer representing the source: 0=A, 1=B."
+ --#TYPE "APC ATS: UnderFrequency condition violated."
+ --#SUMMARY "UnderFrequency condition violated."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 650
+
+atsRMSUnderFrequencyCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { atsIdentSerialNumber, atsConfigProductName,
+ mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: UnderFrequency condition cleared.
+ The first argument is the serial number.
+ The second argument is the product name.
+ The third argument is an integer representing the source: 0=A, 1=B."
+ --#TYPE "APC ATS: UnderFrequency condition cleared."
+ --#SUMMARY "UnderFrequency condition cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 651
+
+
+
+-- MODULAR POWER DISTRIBUTION SYSTEM
+
+isxModularDistributionCommLost TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Communication with a metering segment of the modular
+ distribution system has been lost.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the segment number.
+ The fourth argument describes the modules served by this metering segment."
+ --#TYPE "APC MDS: Com lost in modular distribution system."
+ --#SUMMARY "Modular distribution communication lost."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 652
+
+isxModularDistributionCommEstablished TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Communication with a metering segment of the modular
+ distribution system has been restored.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the segment number.
+ The fourth argument describes the modules served by this metering segment."
+ --#TYPE "APC MDS: Com restored in modular distribution system."
+ --#SUMMARY "Modular distribution communication restored."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 653
+
+isxModularDistributionModuleInserted TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A distribution module has been inserted into the system.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the module location number."
+ --#TYPE "APC MDS: Distribution module inserted."
+ --#SUMMARY "Distribution module inserted."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 654
+
+isxModularDistributionModuleRemoved TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A distribution module has been removed from the system.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the module location number."
+ --#TYPE "APC MDS: Distribution module removed."
+ --#SUMMARY "Distribution module removed."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 655
+
+isxModularBreakerOpenAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger03,
+ mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: A distribution module breaker is open and in an alarm condition.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the module number.
+ The fourth argument is the module breaker(s) (1=L1, 2=L2, 3=L3, 4=L12, 5=L23, 6=L123).
+ The fifth argument is the load name associated with the circuit/cable fed by this breaker."
+ --#TYPE "APC MDS: Distribution breaker open alarm."
+ --#SUMMARY "Distribution breaker open alarm."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 656
+
+isxModularBreakerOpenAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger03,
+ mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: An alarm caused by a distribution breaker being open has been cleared.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the module number.
+ The fourth argument is the breaker(s) (1=L1, 2=L2, 3=L3, 4=L12, 5=L23, 6=L123).
+ The fifth argument is the load name associated with the circuit/cable fed by this breaker."
+ --#TYPE "APC MDS: Distribution breaker open alarm cleared."
+ --#SUMMARY "Distribution breaker open alarm cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 657
+
+isxModularMinCurrentThresholdViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger03,
+ mtrapargsInteger02, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The current in a distribution module is below the minimum/critical
+ limit specified for the circuit/cable.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the module number.
+ The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
+ The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated.
+ The sixth argument is the load name associated with the circuit/cable fed by this breaker."
+ --#TYPE "APC MDS: Distribution minimum current alarm."
+ --#SUMMARY "Distribution current is below the critical threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 658
+
+isxModularMinCurrentThresholdViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger03,
+ mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The current in a distribution module is no longer below the minimum/critical
+ limit specified for the circuit/cable.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the module number.
+ The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
+ The fifth argument is the load name associated with the circuit/cable fed by this breaker."
+ --#TYPE "APC MDS: Distribution minimum current alarm cleared."
+ --#SUMMARY "Distribution current no longer below the critical threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 659
+
+isxModularLowCurrentThresholdViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger03,
+ mtrapargsInteger02, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "WARNING: The current in a distribution module is below the low/warning
+ limit specified for the circuit/cable.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the module number.
+ The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
+ The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated.
+ The sixth argument is the load name associated with the circuit/cable fed by this breaker."
+ --#TYPE "APC MDS: Distribution low current alarm."
+ --#SUMMARY "Distribution current is below the warning threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 660
+
+isxModularLowCurrentThresholdViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger03,
+ mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The current in a distribution module is no longer below the low/warning
+ limit specified for the circuit/cable.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the module number.
+ The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
+ The fifth argument is the load name associated with the circuit/cable fed by this breaker."
+ --#TYPE "APC MDS: Distribution low current alarm cleared."
+ --#SUMMARY "Distribution current no longer below the warning threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 661
+
+isxModularHighCurrentThresholdViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger03,
+ mtrapargsInteger02, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "WARNING: The current in a distribution module is above the high/warning
+ limit specified for the circuit/cable.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the module number.
+ The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
+ The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated.
+ The sixth argument is the load name associated with the circuit/cable fed by this breaker."
+ --#TYPE "APC MDS: Distribution high current alarm."
+ --#SUMMARY "Distribution current is above the warning threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 662
+
+isxModularHighCurrentThresholdViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger03,
+ mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The current in a distribution module is no longer above the high/warning
+ limit specified for the circuit/cable.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the module number.
+ The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
+ The fifth argument is the load name associated with the circuit/cable fed by this breaker."
+ --#TYPE "APC MDS: Distribution high current alarm cleared."
+ --#SUMMARY "Distribution current no longer above the warning threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 663
+
+isxModularMaxCurrentThresholdViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger03,
+ mtrapargsInteger02, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The current in a distribution module is above the maximum/critical
+ limit specified for the circuit/cable.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the module number.
+ The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
+ The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated.
+ The sixth argument is the load name associated with the circuit/cable fed by this breaker."
+ --#TYPE "APC MDS: Distribution maximum current alarm."
+ --#SUMMARY "Distribution current is above the critical threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 664
+
+isxModularMaxCurrentThresholdViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger03,
+ mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The current in a distribution module is no longer above the maximum/critical
+ limit specified for the circuit/cable.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the module number.
+ The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
+ The fifth argument is the load name associated with the circuit/cable fed by this breaker."
+ --#TYPE "APC MDS: Distribution maximum current alarm cleared."
+ --#SUMMARY "Distribution current no longer above the critical threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 665
+
+isxModularSubfeedBreakerOpenAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger,
+ mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: A distribution subfeed breaker is open and in an alarm condition.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the subfeed number.
+ The fourth argument is the load name associated with the subfeed."
+ --#TYPE "APC MDS: Distribution subfeed breaker open alarm."
+ --#SUMMARY "Distribution subfeed breaker open alarm."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 666
+
+isxModularSubfeedBreakerOpenAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger,
+ mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: An alarm caused by a distribution subfeed breaker being open has been cleared.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the subfeed number.
+ The fourth argument is the load name associated with the subfeed."
+ --#TYPE "APC MDS: Distribution subfeed breaker open alarm cleared."
+ --#SUMMARY "Distribution subfeed breaker open alarm cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 667
+
+isxModularSubfeedMinCurrentThresholdViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger03,
+ mtrapargsInteger02, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The current in a distribution subfeed is below the minimum/critical limit specified.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the subfeed number.
+ The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
+ The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated.
+ The sixth argument is the load name associated with the subfeed."
+ --#TYPE "APC MDS: Distribution subfeed minimum current alarm."
+ --#SUMMARY "Distribution subfeed current is below the critical threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 668
+
+isxModularSubfeedMinCurrentThresholdViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger03,
+ mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The current in a distribution subfeed is no longer below the minimum/critical limit specified.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the subfeed number.
+ The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
+ The fifth argument is the load name associated with the subfeed."
+ --#TYPE "APC MDS: Distribution subfeed minimum current alarm cleared."
+ --#SUMMARY "Distribution subfeed current no longer below the critical threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 669
+
+isxModularSubfeedLowCurrentThresholdViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger03,
+ mtrapargsInteger02, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "WARNING: The current in a distribution subfeed is below the low/warning limit specified.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the subfeed number.
+ The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
+ The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated.
+ The sixth argument is the load name associated with the subfeed."
+ --#TYPE "APC MDS: Distribution subfeed low current alarm."
+ --#SUMMARY "Distribution subfeed current is below the warning threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 670
+
+isxModularSubfeedLowCurrentThresholdViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger03,
+ mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The current in a distribution subfeed is no longer below the low/warning limit specified.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the subfeed number.
+ The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
+ The fifth argument is the load name associated with the subfeed."
+ --#TYPE "APC MDS: Distribution subfeed low current alarm cleared."
+ --#SUMMARY "Distribution subfeed current is no longer below the warning threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 671
+
+isxModularSubfeedHighCurrentThresholdViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger03,
+ mtrapargsInteger02, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "WARNING: The current in a distribution subfeed is above the high/warning limit specified.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the subfeed number.
+ The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
+ The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated.
+ The sixth argument is the load name associated with the subfeed."
+ --#TYPE "APC MDS: Distribution subfeed high current alarm."
+ --#SUMMARY "Distribution subfeed current is above the warning threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 672
+
+isxModularSubfeedHighCurrentThresholdViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger03,
+ mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The current in a distribution subfeed is no longer above the high/warning limit specified.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the subfeed number.
+ The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
+ The fifth argument is the load name associated with the subfeed."
+ --#TYPE "APC MDS: Distribution subfeed high current alarm cleared."
+ --#SUMMARY "Distribution subfeed current no longer above the warning threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 673
+
+isxModularSubfeedMaxCurrentThresholdViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger03,
+ mtrapargsInteger02, mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The current in a distribution subfeed is above the maximum/critical limit specified.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the subfeed number.
+ The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
+ The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated.
+ The sixth argument is the load name associated with the subfeed."
+ --#TYPE "APC MDS: Distribution subfeed maximum current alarm."
+ --#SUMMARY "Distribution subfeed current is above the critical threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 674
+
+isxModularSubfeedMaxCurrentThresholdViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger03,
+ mtrapargsString04, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The current in a distribution subfeed is no longer above the maximum/critical limit specified.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the subfeed number.
+ The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
+ The fifth argument is the load name associated with the subfeed."
+ --#TYPE "APC MDS: Distribution subfeed maximum current alarm cleared."
+ --#SUMMARY "Distribution subfeed current no longer above the critical threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 675
+
+isxModularTotalOutputCurrentMinThresholdViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger,
+ mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The total output current of the distribution is below the minimum/critical limit specified.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the phase index (1=L1, 2=L2, 3=L3).
+ The fourth argument is the threshold, in tenths of Amps, from which the alarm was generated."
+ --#TYPE "APC MDS: Total distribution output minimum current alarm."
+ --#SUMMARY "Distribution total current is below the critical threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 676
+
+isxModularTotalOutputCurrentMinThresholdViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger,
+ mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The total output current of the distribution is no longer below the minimum/critical limit specified.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the phase index (1=L1, 2=L2, 3=L3)."
+ --#TYPE "APC MDS: Total output minimum current alarm cleared."
+ --#SUMMARY "Distribution total current no longer below the critical threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 677
+
+isxModularTotalOutputCurrentLowThresholdViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger,
+ mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "WARNING: The total output current of the distribution is below the low/warning limit specified.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the phase index (1=L1, 2=L2, 3=L3).
+ The fourth argument is the threshold, in tenths of Amps, from which the alarm was generated."
+ --#TYPE "APC MDS: Total output low current alarm."
+ --#SUMMARY "Distribution total current is below the warning threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 678
+
+isxModularTotalOutputCurrentLowThresholdViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger,
+ mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The total output current of the distribution is no longer below the low/warning limit specified.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the phase index (1=L1, 2=L2, 3=L3)."
+ --#TYPE "APC MDS: Total output low current alarm cleared."
+ --#SUMMARY "Distribution total current no longer below the warning threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 679
+
+isxModularTotalOutputCurrentHighThresholdViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger,
+ mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "WARNING: The total output current of the distribution is above the high/warning limit specified.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the phase index (1=L1, 2=L2, 3=L3).
+ The fourth argument is the threshold, in tenths of Amps, from which the alarm was generated."
+ --#TYPE "APC MDS: Total output high current alarm."
+ --#SUMMARY "Distribution total current is above the warning threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 680
+
+isxModularTotalOutputCurrentHighThresholdViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger,
+ mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The total output current of the distribution is no longer above the high/warning limit specified.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the phase index (1=L1, 2=L2, 3=L3)."
+ --#TYPE "APC MDS: Total output high current alarm cleared."
+ --#SUMMARY "Distribution total current no longer above the warning threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 681
+
+isxModularTotalOutputCurrentMaxThresholdViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger,
+ mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The total output current of the distribution is above the maximum/critical limit specified.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the phase index (1=L1, 2=L2, 3=L3).
+ The fourth argument is the threshold, in tenths of Amps, from which the alarm was generated."
+ --#TYPE "APC MDS: Total output maximum current alarm."
+ --#SUMMARY "Distribution total current is above the critical threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 682
+
+isxModularTotalOutputCurrentMaxThresholdViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger,
+ mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The total output current of the distribution is no longer above the maximum/critical limit specified.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the phase index (1=L1, 2=L2, 3=L3)."
+ --#TYPE "APC MDS: Total output maximum current alarm cleared."
+ --#SUMMARY "Distribution total current no longer above the critical threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 683
+
+isxModularOutputVoltageMinThresholdViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger,
+ mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The distribution output voltage is below the minimum/critical limit specified.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the phase index (1=L1, 2=L2, 3=L3).
+ The fourth argument is the threshold, in tenths of Volts, from which the alarm was generated."
+ --#TYPE "APC MDS: Distribution minimum output voltage alarm."
+ --#SUMMARY "Distribution output voltage is below the critical threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 684
+
+isxModularOutputVoltageMinThresholdViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger,
+ mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The distribution output voltage is no longer below the minimum/critical limit specified.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the phase index (1=L1, 2=L2, 3=L3)."
+ --#TYPE "APC MDS: Distribution minimum output voltage alarm cleared."
+ --#SUMMARY "Distribution output voltage no longer below the critical threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 685
+
+isxModularOutputVoltageLowThresholdViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger,
+ mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "WARNING: The distribution output voltage is below the low/warning limit specified.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the phase index (1=L1, 2=L2, 3=L3).
+ The fourth argument is the threshold, in tenths of Volts, from which the alarm was generated."
+ --#TYPE "APC MDS: Distribution low output voltage alarm."
+ --#SUMMARY "Distribution output voltage is below the warning threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 686
+
+isxModularOutputVoltageLowThresholdViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger,
+ mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The distribution output voltage is no longer below the low/warning limit specified.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the phase index (1=L1, 2=L2, 3=L3)."
+ --#TYPE "APC MDS: Distribution low output voltage alarm cleared."
+ --#SUMMARY "Distribution output voltage no longer below the warning threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 687
+
+isxModularOutputVoltageHighThresholdViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger,
+ mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "WARNING: The distribution output voltage is above the high/warning limit specified.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the phase index (1=L1, 2=L2, 3=L3).
+ The fourth argument is the threshold, in tenths of Volts, from which the alarm was generated."
+ --#TYPE "APC MDS: Distribution high output voltage alarm."
+ --#SUMMARY "Distribution output voltage is above the warning threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 688
+
+isxModularOutputVoltageHighThresholdViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger,
+ mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The distribution output voltage is no longer above the high/warning limit specified.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the phase index (1=L1, 2=L2, 3=L3)."
+ --#TYPE "APC MDS: Distribution high output voltage alarm cleared."
+ --#SUMMARY "Distribution output voltage no longer above the warning threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 689
+
+isxModularOutputVoltageMaxThresholdViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger,
+ mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The distribution output voltage is above the maximum/critical limit specified.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the phase index (1=L1, 2=L2, 3=L3).
+ The fourth argument is the threshold, in tenths of Volts, from which the alarm was generated."
+ --#TYPE "APC MDS: Distribution maximum output voltage alarm."
+ --#SUMMARY "Distribution output voltage is above the critical threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 690
+
+isxModularOutputVoltageMaxThresholdViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger,
+ mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The distribution output voltage is no longer above the maximum/critical limit specified.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the phase index (1=L1, 2=L2, 3=L3)."
+ --#TYPE "APC MDS: Distribution maximum output voltage alarm cleared."
+ --#SUMMARY "Distribution output voltage no longer above the critical threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 691
+
+apcDoorClosedImproperly TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03,
+ mtrapargsString04, mtrapargsInteger, mtrapargsString}
+ DESCRIPTION
+ "SEVERE: A door has been closed improperly.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the host device location.
+ The fourth argument is the door identifier, (1=front, 2=rear)."
+ --#TYPE "APC: Door closed improperly."
+ --#SUMMARY "Door closed improperly."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 692
+
+apcDoorClosedImproperlyCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03,
+ mtrapargsString04, mtrapargsInteger, mtrapargsString}
+ DESCRIPTION
+ "INFORMATIONAL: A door is no longer closed improperly.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the host device location.
+ The fourth argument is the door identifier, (1=front, 2=rear)."
+ --#TYPE "APC: Door no longer closed improperly."
+ --#SUMMARY "Door no longer closed improperly."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 693
+
+apcUserScheduleViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03,
+ mtrapargsString04, mtrapargsInteger, mtrapargsString}
+ DESCRIPTION
+ "SEVERE: A user has had a door opened past the scheduled access period.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the host device location.
+ The fourth argument is the door identifier, (1=front, 2=rear)."
+ --#TYPE "APC: User schedule violated."
+ --#SUMMARY "User schedule violated."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 694
+
+apcUserScheduleViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03,
+ mtrapargsString04, mtrapargsInteger, mtrapargsString}
+ DESCRIPTION
+ "INFORMATIONAL: User schedule violation has been cleared.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the host device location.
+ The fourth argument is the door identifier, (1=front, 2=rear)."
+ --#TYPE "APC: User schedule violation cleared."
+ --#SUMMARY "User schedule violation cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 695
+
+isxModularOutputFrequencyThresholdViolation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The distribution output frequency is outside of the operating range specified.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the threshold, in tenths of Hertz, from which the alarm was generated."
+ --#TYPE "APC MDS: Distribution output frequency out of range."
+ --#SUMMARY "Distribution output frequency out of range."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 696
+
+isxModularOutputFrequencyViolationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The distribution output frequency is no longer out of range.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC MDS: Distribution output frequency no longer out of range."
+ --#SUMMARY "Distribution output frequency no longer out of range."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 697
+
+atsSourceStatusFail TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { atsIdentSerialNumber, atsConfigProductName,
+ mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: ATS Source failed.
+ The first argument is the serial number.
+ The second argument is the product name.
+ The third argument is an integer representing the source: 0=A, 1=B."
+ --#TYPE "APC ATS: ATS Source failed."
+ --#SUMMARY "ATS Source failed."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 698
+
+atsSourceStatusOk TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { atsIdentSerialNumber, atsConfigProductName,
+ mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: ATS Source OK.
+ The first argument is the serial number.
+ The second argument is the product name.
+ The third argument is an integer representing the source: 0=A, 1=B."
+ --#TYPE "APC ATS: ATS Source OK."
+ --#SUMMARY "ATS Source OK."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 699
+
+atsHardwareStatusFail TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { atsIdentSerialNumber, atsConfigProductName,
+ mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: ATS display board hardware failed.
+ The first argument is the serial number.
+ The second argument is the product name.
+ The third argument is an integer representing the failed hardware:
+ 0= Phase LEDs/Push-button hardware failure
+ 1= Seven-segment display hardware failure."
+ --#TYPE "APC ATS: ATS display board hardware failed."
+ --#SUMMARY "ATS display board hardware failed."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 700
+
+atsHardwareStatusOk TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { atsIdentSerialNumber, atsConfigProductName,
+ mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: ATS display board hardware ok.
+ The first argument is the serial number.
+ The second argument is the product name.
+ The third argument is an integer representing the hardware:
+ 0= Phase LEDs/Push-button hardware failure
+ 1= Seven-segment display hardware failure."
+ --#TYPE "APC ATS: ATS display board hardware ok."
+ --#SUMMARY "ATS display board hardware ok."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 701
+
+atsControllerRestart TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: ATS Controller restarted."
+ --#TYPE "APC ATS: ATS Controller restarted."
+ --#SUMMARY "ATS Controller restarted."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 702
+
+
+
+inputWarningError TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "WARNING: Input warning error has been detected.
+ The first variable is the fault condition."
+ --#TYPE "APC UPS: Input warning error has been detected."
+ --#SUMMARY "UPS Input warning error has been detected."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 703
+
+inputOK TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Input warning error has been cleared.
+ The first variable is the fault condition."
+ --#TYPE "APC UPS: Input warning error has been cleared."
+ --#SUMMARY "UPS Input warning error has been cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 704
+
+bypassWarningError TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "WARNING: Bypass warning error has been detected.
+ The first variable is the fault condition."
+ --#TYPE "APC UPS: Bypass warning error has been detected."
+ --#SUMMARY "UPS Bypass warning error has been detected."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 705
+
+bypassOK TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Bypass warning error has been cleared.
+ The first variable is the fault condition."
+ --#TYPE "APC UPS: Bypass warning error has been cleared."
+ --#SUMMARY "UPS Bypass warning error has been cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 706
+
+communicationWarningError TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "WARNING: Communication warning error has been detected.
+ The first variable is the fault condition."
+ --#TYPE "APC UPS: Communication warning error has been detected."
+ --#SUMMARY "UPS Communication warning error has been detected."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 707
+
+communicationOK TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Communication warning error has been cleared.
+ The first variable is the fault condition."
+ --#TYPE "APC UPS: Communication warning error has been cleared."
+ --#SUMMARY "UPS Communication warning error has been cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 708
+
+powerModuleSevereError TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Power module severe error has been detected.
+ The first variable is the fault condition."
+ --#TYPE "APC UPS: Power module severe error has been detected."
+ --#SUMMARY "UPS Power module severe error has been detected."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 709
+
+powerModuleOK TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Power module severe error has been cleared.
+ The first variable is the fault condition."
+ --#TYPE "APC UPS: Power module severe error has been cleared."
+ --#SUMMARY "UPS Power module severe error has been cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 710
+
+outputVoltageWaveformError TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Output voltage waveform error has been detected."
+ --#TYPE "APC UPS: Output voltage waveform error has been detected."
+ --#SUMMARY "UPS output voltage waveform error has been detected."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 711
+
+outputVoltageWaveformOK TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Output voltage waveform is OK."
+ --#TYPE "APC UPS: Output voltage waveform is OK"
+ --#SUMMARY "UPS output voltage waveform is OK."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 712
+
+bypassStaticSwitchOverload TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Overload on bypass static switch has been detected."
+ --#TYPE "APC UPS: Overload on bypass static switch has been detected."
+ --#SUMMARY "Overload on bypass static switch has been detected."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 713
+
+noOverloadOnBypassStaticSwitch TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Overload on static bypass switch no longer present."
+ --#TYPE "APC UPS: Overload on static bypass switch no longer present."
+ --#SUMMARY "Overload on static bypass switch no longer present."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 714
+
+batteryVoltageCollapse TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Battery voltage collapse has been detected."
+ --#TYPE "APC UPS: Battery voltage collapse has been detected."
+ --#SUMMARY "Battery voltage collapse has been detected."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 715
+
+batteryVoltageOK TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Battery voltage OK."
+ --#TYPE "APC UPS: Battery voltage OK."
+ --#SUMMARY "Battery voltage OK."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 716
+
+overloadOnInstallation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Overload on installation has been detected."
+ --#TYPE "APC UPS: Overload on installation has been detected."
+ --#SUMMARY "Overload on installation has been detected."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 717
+
+noOverloadOnInstallation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Overload on installation no longer present."
+ --#TYPE "APC UPS: Overload on installation no longer present."
+ --#SUMMARY "Overload on installation no longer present."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 718
+
+bypassStaticSwitchError TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Bypass static switch error, module has critical error."
+ --#TYPE "APC UPS: Bypass static switch error, module has critical error."
+ --#SUMMARY "Bypass static switch error, module has critical error."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 719
+
+bypassStaticSwitchOK TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Bypass static switch OK."
+ --#TYPE "APC UPS: Bypass static switch OK."
+ --#SUMMARY "Bypass static switch OK."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 720
+
+forcedBypassSwitchActivated TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Forced bypass switch has been activated."
+ --#TYPE "APC UPS: Forced bypass switch has been activated."
+ --#SUMMARY "Forced bypass switch has been activated."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 721
+
+forcedBypassSwitchReleased TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Forced bypass switch has been released."
+ --#TYPE "APC UPS: Forced bypass switch has been released."
+ --#SUMMARY "Forced bypass switch has been released."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 722
+
+epoActivated TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Emergency Power Off (EPO) switch has been activated."
+ --#TYPE "APC Emergency Power Off (EPO) switch has been activated."
+ --#SUMMARY "Emergency Power Off (EPO) switch has been activated."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 723
+
+
+xATSS1BadPhaseRotation TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The device's source 1 phase rotation is bad.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XATS: S1 bad phase rotation alarm."
+ --#SUMMARY "Phase rotation on source 1 is bad."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 724
+
+xATSS1BadPhaseRotationCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString}
+ DESCRIPTION
+ "INFORMATIONAL: The device's source 1 phase rotation is back to normal.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XATS: S1 phase rotation back to normal."
+ --#SUMMARY "S1 phase rotation back to normal."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 725
+
+xATSS1BadPhaseBalance TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsInteger,
+ mtrapargsString}
+ DESCRIPTION
+ "SEVERE: The device's source 1 phase balance is out of bounds.
+ The first argument is the host device serial number.
+ The second argument is the host device name.
+ The third argument is the minimum phase balance as a percentage."
+ --#TYPE "APC XATS: S1 phase imbalance exceeds threshold alarm."
+ --#SUMMARY "Phase imbalance on source 1 exceeds threshold."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 726
+
+xATSS1BadPhaseBalanceCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { xATSIdentSerialNumber, xATSIdentProductName, mtrapargsString}
+ DESCRIPTION
+ "INFORMATIONAL: The device's source 1 phase balance is back to normal.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC XATS: S1 phase balance back to normal."
+ --#SUMMARY "S1 phase balance back to normal."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 727
+
+isxModularTransformerOverheating TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The distribution transformer temperature is too hot.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC MDS: Transformer overheating."
+ --#SUMMARY "Distribution transformer temperature is too hot."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 728
+
+isxModularTransformerOverheatingCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The distribution transformer temperature has returned to normal.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC MDS: Transformer temperature has returned to normal."
+ --#SUMMARY "Distribution transformer temperature has returned to normal."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 729
+
+apcInternalCommunicationFault TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "SEVERE: An internal UPS communication fault exists."
+ --#TYPE "APC Device: An internal UPS communication fault exists."
+ --#SUMMARY "An internal UPS communication fault exists."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 730
+
+apcInternalCommunicationFaultCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: An internal UPS communication fault no longer exists."
+ --#TYPE "APC Device:An internal UPS communication fault no longer exists."
+ --#SUMMARY "An internal UPS communication fault no longer exists."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 731
+
+upsOutletGroupCommand TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { upsOutletGroupControlIndex, mtrapargsString }
+ DESCRIPTION
+ "WARNING: The specified Outlet Group command has been issued."
+ --#TYPE "APC UPS: Outlet Group command issued."
+ --#SUMMARY "Outlet Group command issued."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 732
+
+onbatterycommunicationLost TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Communication to the UPS when the UPS is on Battery. Steps
+ to reestablish communication are in progress."
+ --#TYPE "APC UPS: Communication lost"
+ --#SUMMARY "Communication lost between the agent and the UPS when UPS is on Battery."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 733
+
+upsCriticalCondition TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: A UPS critical condition was detected.
+ The first variable is the error condition text message.
+ The second variable is the error number."
+ --#TYPE "UPS: A critical condition has been detected."
+ --#SUMMARY "A critical condition has been detected."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 734
+
+upsCriticalConditionCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A UPS critical condition has been cleared.
+ The first variable is the fault condition."
+ --#TYPE "UPS: A critical condition has been cleared."
+ --#SUMMARY "A critical condition has been cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 735
+
+upsWarningCondition TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "WARNING: A UPS warning condition has been detected.
+ The first variable is the fault condition."
+ --#TYPE "UPS: A warning condition has been detected."
+ --#SUMMARY "A warning condition has been detected."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 736
+
+upsWarningConditionCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "WARNING: A UPS warning condition has been cleared.
+ The first variable is the fault condition."
+ --#TYPE "UPS: A warning condition has been cleared."
+ --#SUMMARY "A warning condition has been cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 737
+
+upsInformationalCondition TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A UPS informational condition has been detected.
+ The first variable is the fault condition."
+ --#TYPE "UPS: Informational condition detected."
+ --#SUMMARY "An informational condition has been detected."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 738
+
+upsInformationalConditionCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsInteger, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A UPS informational condition has been cleared.
+ The first variable is the fault condition."
+ --#TYPE "UPS: Informational condition cleared."
+ --#SUMMARY "An informational condition has been cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 739
+
+isxcInformationalAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02,
+ mtrapargsOctetString,
+ mtrapargsInteger,
+ mtrapargsString03,
+ mtrapargsOctetString02,
+ mtrapargsString04,
+ mtrapargsOctetString03,
+ mtrapargsString05,
+ mtrapargsString06,
+ mtrapargsString07,
+ mtrapargsOctetString04,
+ mtrapargsOctetString05,
+ mtrapargsString08,
+ mtrapargsOctetString06,
+ mtrapargsOctetString07,
+ mtrapargsInteger02,
+ mtrapargsInteger03,
+ mtrapargsOctetString08,
+ mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: An ISXC Alarm exists.
+ The first argument is the unique ISXC alarm ID.
+ The second argument is the ISXC alarm label as a UTF8 string.
+ The third argument is the ISXC alarm code.
+ The fourth argument is the unique ISXC device ID.
+ The fifth argument is the ISXC device label as a UTF8 string.
+ The sixth argument is the ISXC parent host.
+ The seventh argument is the ISXC device type as a UTF8 string.
+ The eighth argument is the device serial number.
+ The ninth argument is the device model number.
+ The tenth argument is the device host.
+ The eleventh argument is the device location as a UTF8 string.
+ The twelfth argument is the device contact as a UTF8 string.
+ The thirteenth argument is the unique ISXC sensor ID.
+ The fourteenth argument is the ISXC sensor label as a UTF8 string.
+ The fifteenth argument is the sensor value as a UTF8 string.
+ The sixteenth argument is the ISXC alarm start time.
+ The seventeenth argument is the ISXC alarm resolution time.
+ The eighteenth argument is the description as a UTF8 string."
+ --#TYPE "APC ISXC: An ISXC Informational Alarm exists."
+ --#SUMMARY "An ISXC Informational Alarm exists."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 740
+
+isxcInformationalAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02,
+ mtrapargsOctetString,
+ mtrapargsInteger,
+ mtrapargsString03,
+ mtrapargsOctetString02,
+ mtrapargsString04,
+ mtrapargsOctetString03,
+ mtrapargsString05,
+ mtrapargsString06,
+ mtrapargsString07,
+ mtrapargsOctetString04,
+ mtrapargsOctetString05,
+ mtrapargsString08,
+ mtrapargsOctetString06,
+ mtrapargsOctetString07,
+ mtrapargsInteger02,
+ mtrapargsInteger03,
+ mtrapargsOctetString08,
+ mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: An ISXC Alarm has been cleared.
+ The first argument is the unique ISXC alarm ID.
+ The second argument is the ISXC alarm label as a UTF8 string.
+ The third argument is the ISXC alarm code.
+ The fourth argument is the unique ISXC device ID.
+ The fifth argument is the ISXC device label as a UTF8 string.
+ The sixth argument is the ISXC parent host.
+ The seventh argument is the ISXC device type as a UTF8 string.
+ The eighth argument is the device serial number.
+ The ninth argument is the device model number.
+ The tenth argument is the device host.
+ The eleventh argument is the device location as a UTF8 string.
+ The twelfth argument is the device contact as a UTF8 string.
+ The thirteenth argument is the unique ISXC sensor ID.
+ The fourteenth argument is the ISXC sensor label as a UTF8 string.
+ The fifteenth argument is the sensor value as a UTF8 string.
+ The sixteenth argument is the ISXC alarm start time.
+ The seventeenth argument is the ISXC alarm resolution time.
+ The eighteenth argument is the description as a UTF8 string."
+ --#TYPE "APC ISXC: An ISXC Informational Alarm has been cleared."
+ --#SUMMARY "An ISXC Informational Alarm has been cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 741
+
+isxcWarningAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02,
+ mtrapargsOctetString,
+ mtrapargsInteger,
+ mtrapargsString03,
+ mtrapargsOctetString02,
+ mtrapargsString04,
+ mtrapargsOctetString03,
+ mtrapargsString05,
+ mtrapargsString06,
+ mtrapargsString07,
+ mtrapargsOctetString04,
+ mtrapargsOctetString05,
+ mtrapargsString08,
+ mtrapargsOctetString06,
+ mtrapargsOctetString07,
+ mtrapargsInteger02,
+ mtrapargsInteger03,
+ mtrapargsOctetString08,
+ mtrapargsString }
+ DESCRIPTION
+ "WARNING: An ISXC Alarm exists.
+ The first argument is the unique ISXC alarm ID.
+ The second argument is the ISXC alarm label as a UTF8 string.
+ The third argument is the ISXC alarm code.
+ The fourth argument is the unique ISXC device ID.
+ The fifth argument is the ISXC device label as a UTF8 string.
+ The sixth argument is the ISXC parent host.
+ The seventh argument is the ISXC device type as a UTF8 string.
+ The eighth argument is the device serial number.
+ The ninth argument is the device model number.
+ The tenth argument is the device host.
+ The eleventh argument is the device location as a UTF8 string.
+ The twelfth argument is the device contact as a UTF8 string.
+ The thirteenth argument is the unique ISXC sensor ID.
+ The fourteenth argument is the ISXC sensor label as a UTF8 string.
+ The fifteenth argument is the sensor value as a UTF8 string.
+ The sixteenth argument is the ISXC alarm start time.
+ The seventeenth argument is the ISXC alarm resolution time.
+ The eighteenth argument is the description as a UTF8 string."
+ --#TYPE "APC ISXC: An ISXC Warning Alarm exists."
+ --#SUMMARY "An ISXC Warning Alarm exists."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 742
+
+isxcWarningAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02,
+ mtrapargsOctetString,
+ mtrapargsInteger,
+ mtrapargsString03,
+ mtrapargsOctetString02,
+ mtrapargsString04,
+ mtrapargsOctetString03,
+ mtrapargsString05,
+ mtrapargsString06,
+ mtrapargsString07,
+ mtrapargsOctetString04,
+ mtrapargsOctetString05,
+ mtrapargsString08,
+ mtrapargsOctetString06,
+ mtrapargsOctetString07,
+ mtrapargsInteger02,
+ mtrapargsInteger03,
+ mtrapargsOctetString08,
+ mtrapargsString }
+ DESCRIPTION
+ "WARNING: An ISXC Alarm has been cleared.
+ The first argument is the unique ISXC alarm ID.
+ The second argument is the ISXC alarm label as a UTF8 string.
+ The third argument is the ISXC alarm code.
+ The fourth argument is the unique ISXC device ID.
+ The fifth argument is the ISXC device label as a UTF8 string.
+ The sixth argument is the ISXC parent host.
+ The seventh argument is the ISXC device type as a UTF8 string.
+ The eighth argument is the device serial number.
+ The ninth argument is the device model number.
+ The tenth argument is the device host.
+ The eleventh argument is the device location as a UTF8 string.
+ The twelfth argument is the device contact as a UTF8 string.
+ The thirteenth argument is the unique ISXC sensor ID.
+ The fourteenth argument is the ISXC sensor label as a UTF8 string.
+ The fifteenth argument is the sensor value as a UTF8 string.
+ The sixteenth argument is the ISXC alarm start time.
+ The seventeenth argument is the ISXC alarm resolution time.
+ The eighteenth argument is the description as a UTF8 string."
+ --#TYPE "APC ISXC: An ISXC Warning Alarm has been cleared."
+ --#SUMMARY "An ISXC Warning Alarm has been cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 743
+
+isxcErrorAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02,
+ mtrapargsOctetString,
+ mtrapargsInteger,
+ mtrapargsString03,
+ mtrapargsOctetString02,
+ mtrapargsString04,
+ mtrapargsOctetString03,
+ mtrapargsString05,
+ mtrapargsString06,
+ mtrapargsString07,
+ mtrapargsOctetString04,
+ mtrapargsOctetString05,
+ mtrapargsString08,
+ mtrapargsOctetString06,
+ mtrapargsOctetString07,
+ mtrapargsInteger02,
+ mtrapargsInteger03,
+ mtrapargsOctetString08,
+ mtrapargsString }
+ DESCRIPTION
+ "ERROR: An ISXC Alarm exists.
+ The first argument is the unique ISXC alarm ID.
+ The second argument is the ISXC alarm label as a UTF8 string.
+ The third argument is the ISXC alarm code.
+ The fourth argument is the unique ISXC device ID.
+ The fifth argument is the ISXC device label as a UTF8 string.
+ The sixth argument is the ISXC parent host.
+ The seventh argument is the ISXC device type as a UTF8 string.
+ The eighth argument is the device serial number.
+ The ninth argument is the device model number.
+ The tenth argument is the device host.
+ The eleventh argument is the device location as a UTF8 string.
+ The twelfth argument is the device contact as a UTF8 string.
+ The thirteenth argument is the unique ISXC sensor ID.
+ The fourteenth argument is the ISXC sensor label as a UTF8 string.
+ The fifteenth argument is the sensor value as a UTF8 string.
+ The sixteenth argument is the ISXC alarm start time.
+ The seventeenth argument is the ISXC alarm resolution time.
+ The eighteenth argument is the description as a UTF8 string."
+ --#TYPE "APC ISXC: An ISXC Error Alarm exists."
+ --#SUMMARY "An ISXC Error Alarm exists."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 744
+
+isxcErrorAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02,
+ mtrapargsOctetString,
+ mtrapargsInteger,
+ mtrapargsString03,
+ mtrapargsOctetString02,
+ mtrapargsString04,
+ mtrapargsOctetString03,
+ mtrapargsString05,
+ mtrapargsString06,
+ mtrapargsString07,
+ mtrapargsOctetString04,
+ mtrapargsOctetString05,
+ mtrapargsString08,
+ mtrapargsOctetString06,
+ mtrapargsOctetString07,
+ mtrapargsInteger02,
+ mtrapargsInteger03,
+ mtrapargsOctetString08,
+ mtrapargsString }
+ DESCRIPTION
+ "ERROR: An ISXC Alarm has been cleared.
+ The first argument is the unique ISXC alarm ID.
+ The second argument is the ISXC alarm label as a UTF8 string.
+ The third argument is the ISXC alarm code.
+ The fourth argument is the unique ISXC device ID.
+ The fifth argument is the ISXC device label as a UTF8 string.
+ The sixth argument is the ISXC parent host.
+ The seventh argument is the ISXC device type as a UTF8 string.
+ The eighth argument is the device serial number.
+ The ninth argument is the device model number.
+ The tenth argument is the device host.
+ The eleventh argument is the device location as a UTF8 string.
+ The twelfth argument is the device contact as a UTF8 string.
+ The thirteenth argument is the unique ISXC sensor ID.
+ The fourteenth argument is the ISXC sensor label as a UTF8 string.
+ The fifteenth argument is the sensor value as a UTF8 string.
+ The sixteenth argument is the ISXC alarm start time.
+ The seventeenth argument is the ISXC alarm resolution time.
+ The eighteenth argument is the description as a UTF8 string."
+ --#TYPE "APC ISXC: An ISXC Error Alarm has been cleared."
+ --#SUMMARY "An ISXC Error Alarm has been cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 745
+
+isxcCriticalAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02,
+ mtrapargsOctetString,
+ mtrapargsInteger,
+ mtrapargsString03,
+ mtrapargsOctetString02,
+ mtrapargsString04,
+ mtrapargsOctetString03,
+ mtrapargsString05,
+ mtrapargsString06,
+ mtrapargsString07,
+ mtrapargsOctetString04,
+ mtrapargsOctetString05,
+ mtrapargsString08,
+ mtrapargsOctetString06,
+ mtrapargsOctetString07,
+ mtrapargsInteger02,
+ mtrapargsInteger03,
+ mtrapargsOctetString08,
+ mtrapargsString }
+ DESCRIPTION
+ "CRITICAL: An ISXC Alarm exists.
+ The first argument is the unique ISXC alarm ID.
+ The second argument is the ISXC alarm label as a UTF8 string.
+ The third argument is the ISXC alarm code.
+ The fourth argument is the unique ISXC device ID.
+ The fifth argument is the ISXC device label as a UTF8 string.
+ The sixth argument is the ISXC parent host.
+ The seventh argument is the ISXC device type as a UTF8 string.
+ The eighth argument is the device serial number.
+ The ninth argument is the device model number.
+ The tenth argument is the device host.
+ The eleventh argument is the device location as a UTF8 string.
+ The twelfth argument is the device contact as a UTF8 string.
+ The thirteenth argument is the unique ISXC sensor ID.
+ The fourteenth argument is the ISXC sensor label as a UTF8 string.
+ The fifteenth argument is the sensor value as a UTF8 string.
+ The sixteenth argument is the ISXC alarm start time.
+ The seventeenth argument is the ISXC alarm resolution time.
+ The eighteenth argument is the description as a UTF8 string."
+ --#TYPE "APC ISXC: An ISXC Critical Alarm exists."
+ --#SUMMARY "An ISXC Critical Alarm exists."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 746
+
+isxcCriticalAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02,
+ mtrapargsOctetString,
+ mtrapargsInteger,
+ mtrapargsString03,
+ mtrapargsOctetString02,
+ mtrapargsString04,
+ mtrapargsOctetString03,
+ mtrapargsString05,
+ mtrapargsString06,
+ mtrapargsString07,
+ mtrapargsOctetString04,
+ mtrapargsOctetString05,
+ mtrapargsString08,
+ mtrapargsOctetString06,
+ mtrapargsOctetString07,
+ mtrapargsInteger02,
+ mtrapargsInteger03,
+ mtrapargsOctetString08,
+ mtrapargsString }
+ DESCRIPTION
+ "CRITICAL: An ISXC Alarm has been cleared.
+ The first argument is the unique ISXC alarm ID.
+ The second argument is the ISXC alarm label as a UTF8 string.
+ The third argument is the ISXC alarm code.
+ The fourth argument is the unique ISXC device ID.
+ The fifth argument is the ISXC device label as a UTF8 string.
+ The sixth argument is the ISXC parent host.
+ The seventh argument is the ISXC device type as a UTF8 string.
+ The eighth argument is the device serial number.
+ The ninth argument is the device model number.
+ The tenth argument is the device host.
+ The eleventh argument is the device location as a UTF8 string.
+ The twelfth argument is the device contact as a UTF8 string.
+ The thirteenth argument is the unique ISXC sensor ID.
+ The fourteenth argument is the ISXC sensor label as a UTF8 string.
+ The fifteenth argument is the sensor value as a UTF8 string.
+ The sixteenth argument is the ISXC alarm start time.
+ The seventeenth argument is the ISXC alarm resolution time.
+ The eighteenth argument is the description as a UTF8 string."
+ --#TYPE "APC ISXC: An ISXC Critical Alarm has been cleared."
+ --#SUMMARY "An ISXC Critical Alarm has been cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 747
+
+isxcFailureAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02,
+ mtrapargsOctetString,
+ mtrapargsInteger,
+ mtrapargsString03,
+ mtrapargsOctetString02,
+ mtrapargsString04,
+ mtrapargsOctetString03,
+ mtrapargsString05,
+ mtrapargsString06,
+ mtrapargsString07,
+ mtrapargsOctetString04,
+ mtrapargsOctetString05,
+ mtrapargsString08,
+ mtrapargsOctetString06,
+ mtrapargsOctetString07,
+ mtrapargsInteger02,
+ mtrapargsInteger03,
+ mtrapargsOctetString08,
+ mtrapargsString }
+ DESCRIPTION
+ "FAILURE: An ISXC Alarm exists.
+ The first argument is the unique ISXC alarm ID.
+ The second argument is the ISXC alarm label as a UTF8 string.
+ The third argument is the ISXC alarm code.
+ The fourth argument is the unique ISXC device ID.
+ The fifth argument is the ISXC device label as a UTF8 string.
+ The sixth argument is the ISXC parent host.
+ The seventh argument is the ISXC device type as a UTF8 string.
+ The eighth argument is the device serial number.
+ The ninth argument is the device model number.
+ The tenth argument is the device host.
+ The eleventh argument is the device location as a UTF8 string.
+ The twelfth argument is the device contact as a UTF8 string.
+ The thirteenth argument is the unique ISXC sensor ID.
+ The fourteenth argument is the ISXC sensor label as a UTF8 string.
+ The fifteenth argument is the sensor value as a UTF8 string.
+ The sixteenth argument is the ISXC alarm start time.
+ The seventeenth argument is the ISXC alarm resolution time.
+ The eighteenth argument is the description as a UTF8 string."
+ --#TYPE "APC ISXC: An ISXC Failure Alarm exists."
+ --#SUMMARY "An ISXC Failure Alarm exists."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 748
+
+isxcFailureAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02,
+ mtrapargsOctetString,
+ mtrapargsInteger,
+ mtrapargsString03,
+ mtrapargsOctetString02,
+ mtrapargsString04,
+ mtrapargsOctetString03,
+ mtrapargsString05,
+ mtrapargsString06,
+ mtrapargsString07,
+ mtrapargsOctetString04,
+ mtrapargsOctetString05,
+ mtrapargsString08,
+ mtrapargsOctetString06,
+ mtrapargsOctetString07,
+ mtrapargsInteger02,
+ mtrapargsInteger03,
+ mtrapargsOctetString08,
+ mtrapargsString }
+ DESCRIPTION
+ "FAILURE: An ISXC Alarm has been cleared.
+ The first argument is the unique ISXC alarm ID.
+ The second argument is the ISXC alarm label as a UTF8 string.
+ The third argument is the ISXC alarm code.
+ The fourth argument is the unique ISXC device ID.
+ The fifth argument is the ISXC device label as a UTF8 string.
+ The sixth argument is the ISXC parent host.
+ The seventh argument is the ISXC device type as a UTF8 string.
+ The eighth argument is the device serial number.
+ The ninth argument is the device model number.
+ The tenth argument is the device host.
+ The eleventh argument is the device location as a UTF8 string.
+ The twelfth argument is the device contact as a UTF8 string.
+ The thirteenth argument is the unique ISXC sensor ID.
+ The fourteenth argument is the ISXC sensor label as a UTF8 string.
+ The fifteenth argument is the sensor value as a UTF8 string.
+ The sixteenth argument is the ISXC alarm start time.
+ The seventeenth argument is the ISXC alarm resolution time.
+ The eighteenth argument is the description as a UTF8 string."
+ --#TYPE "APC ISXC: An ISXC Failure Alarm has been cleared."
+ --#SUMMARY "An ISXC Failure Alarm has been cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 749
+
+-- rPDU2g Trap Section
+
+rpduCriticalCondition TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: A RPDU critical condition has been detected.
+ The first variable is the serial number.
+ The second variable is the device name.
+ The third variable is the error number.
+ The fourth variable is the device number.
+ The fifth variable is the instance number.
+ The sixth variable is the trap text message."
+ --#TYPE "RPDU: A critical condition has been detected."
+ --#SUMMARY "A critical condition has been detected."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 750
+
+rpduCriticalConditionCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A RPDU critical condition has been cleared.
+ The first variable is the serial number.
+ The second variable is the device name.
+ The third variable is the error number.
+ The fourth variable is the device number.
+ The fifth variable is the instance number.
+ The sixth variable is the trap text message."
+ --#TYPE "RPDU: A critical condition has been cleared."
+ --#SUMMARY "A critical condition has been cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 751
+
+rpduWarningCondition TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "WARNING: A RPDU warning condition has been detected.
+ The first variable is the serial number.
+ The second variable is the device name.
+ The third variable is the error number.
+ The fourth variable is the device number.
+ The fifth variable is the instance number.
+ The sixth variable is the trap text message."
+ --#TYPE "RPDU: A warning condition has been detected."
+ --#SUMMARY "A warning condition has been detected."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 752
+
+rpduWarningConditionCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "WARNING: A RPDU warning condition has been cleared.
+ The first variable is the serial number.
+ The second variable is the device name.
+ The third variable is the error number.
+ The fourth variable is the device number.
+ The fifth variable is the instance number.
+ The sixth variable is the trap text message."
+ --#TYPE "RPDU: A warning condition has been cleared."
+ --#SUMMARY "A warning condition has been cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 753
+
+rpduInformationalCondition TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A RPDU informational condition has been detected.
+ The first variable is the serial number.
+ The second variable is the device name.
+ The third variable is the error number.
+ The fourth variable is the device number.
+ The fifth variable is the instance number.
+ The sixth variable is the trap text message."
+ --#TYPE "RPDU: Informational condition detected."
+ --#SUMMARY "An informational condition has been detected."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 754
+
+rpduInformationalConditionCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger02, mtrapargsInteger03, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A RPDU informational condition has been cleared.
+ The first variable is the serial number.
+ The second variable is the device name.
+ The third variable is the error number.
+ The fourth variable is the device number.
+ The fifth variable is the instance number.
+ The sixth variable is the trap text message."
+ --#TYPE "RPDU: Informational condition cleared."
+ --#SUMMARY "An informational condition has been cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 755
+
+isxModularCoolingFanAlarm TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The device's internal cooling fans have failed.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC MDS: Cooling fan failure."
+ --#SUMMARY "Cooling fan failure."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 756
+
+isxModularCoolingFanAlarmCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The device's internal cooling fans are now functioning properly.
+ The first argument is the host device serial number.
+ The second argument is the host device name."
+ --#TYPE "APC MDS: Cooling fan alarm cleared."
+ --#SUMMARY "Cooling fan alarm cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 757
+
+upsFirmwareUpdateStarted TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: Updating UPS firmware."
+ --#TYPE "APC UPS: Updating firmware"
+ --#SUMMARY "The UPS has started a firmware update."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 758
+
+upsFirmwareUpdateFinished TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Finished updating UPS firmware."
+ --#TYPE "APC UPS: Finished firmware update"
+ --#SUMMARY "The UPS has finished the firmware update."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 759
+
+upsFirmwareUpdateSucceeded TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: UPS firmware update succeeded."
+ --#TYPE "APC UPS: Firmware update succeeded"
+ --#SUMMARY "The UPS has successfully completed a firmware update."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 760
+
+upsFirmwareUpdateFailed TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: UPS firmware update failed."
+ --#TYPE "APC UPS: Firmware update failed"
+ --#SUMMARY "The UPS failed to complete a firmware update."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 761
+
+upsHasNoValidFirmware TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "SEVERE: UPS has no valid firmware."
+ --#TYPE "APC UPS: No firmware"
+ --#SUMMARY "The UPS does not have a valid firmware."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE NONOPERATIONAL
+ ::= 762
+
+upsHasNoValidFirmwareCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: UPS now has a valid firmware."
+ --#TYPE "APC UPS: Now has valid firmware"
+ --#SUMMARY "The UPS now has a valid firmware."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 763
+
+
+upsLocalDisplayButtonFault TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: A local display button fault exists."
+ --#TYPE "APC UPS: A local display button fault exists."
+ --#SUMMARY "The UPS has detected a local display button error. The button may be stuck in the closed position."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 767
+
+upsLocalDisplayButtonFaultCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A local display button fault no longer exists."
+ --#TYPE "APC UPS: A local display button fault no longer exists."
+ --#SUMMARY "The UPS no longer detects a local display button error."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 768
+
+upsNeedsFactorySetupFault TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "SEVERE: UPS needs factory setup."
+ --#TYPE "APC UPS: needs factory setup."
+ --#SUMMARY "The UPS is missing factory configuration information. The UPS needs to be set up by the factory."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE NONOPERATIONAL
+ ::= 769
+
+upsNeedsFactorySetupFaultCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: UPS no longer needs factory setup."
+ --#TYPE "APC UPS: no longer needs factory setup."
+ --#SUMMARY "The UPS now has the required factory configuration information."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 770
+
+upsEPOActive TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Emergency Power Off (EPO) active."
+ --#TYPE "APC UPS: Emergency Power Off (EPO) active."
+ --#SUMMARY "The EPO contact on the UPS was activated causing the UPS to turn off."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE NONOPERATIONAL
+ ::= 771
+
+upsEPOActiveCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Emergency Power Off (EPO) now inactive."
+ --#TYPE "APC UPS: Emergency Power Off (EPO) now inactive."
+ --#SUMMARY "The EPO contact on the UPS is no longer activated. The UPS may be turned on."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 772
+
+upsFirmwareMismatch TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "SEVERE: A firmware mismatch error exists."
+ --#TYPE "APC UPS: A firmware mismatch error exists."
+ --#SUMMARY "Parts of the system are running firmware versions not designed to work together. This may be due to an incomplete firmware update."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE NONOPERATIONAL
+ ::= 773
+
+upsFirmwareMismatchCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A firmware mismatch error no longer exists."
+ --#TYPE "APC UPS: A firmware mismatch error no longer exists."
+ --#SUMMARY "The firmware versions on the system are now compatible."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 774
+
+upsOscillatorFailed TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "SEVERE: An oscillator error exists."
+ --#TYPE "APC UPS: An oscillator error exists."
+ --#SUMMARY "One or more system clocks no longer keeps time due to a failed oscillator. Depending on the failure, this may result in a loss of time keeping, or render parts of the system inoperable."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE NONOPERATIONAL
+ ::= 775
+
+upsOscillatorFailedCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: An oscillator error no longer exists."
+ --#TYPE "APC UPS: An oscillator error no longer exists."
+ --#SUMMARY "The oscillator error no longer exists."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 776
+
+upsOnBatteryDueToFault TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "SEVERE: The UPS is on battery due to an error.
+
+ Symmetra UPSes: Intelligence module has reported being in self-test for
+ too long. When this happens, the UPS is not usually in self-test, but the
+ batteries are draining slowly. If left uncorrected, the batteries will
+ become depleted and the UPS will not be able to turn on. If UPS has at
+ least N+1 redundancy, check power modules one by one to determine which
+ keeps the UPS in self-test. Once identified, replace the module."
+ --#TYPE "APC UPS: The UPS is on battery due to an error."
+ --#SUMMARY "The UPS is on battery due to an error."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 777
+
+upsOnBatteryDueToFaultCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: The UPS is no longer on battery due to an error."
+ --#TYPE "APC UPS: The UPS is no longer on battery due to an error."
+ --#SUMMARY "The UPS is no longer on battery due to an error."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 778
+
+
+pcnsCriticalEventActive TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "SEVERE: PowerChute Network Shutdown has begun a safe shutdown of the host."
+ --#TYPE "APC CODE: PowerChute Network Shutdown has begun a safe shutdown of the host."
+ --#SUMMARY "Safe Shutdown of host initiated."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 779
+
+pcnsCriticalEventResolved TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: PowerChute Network Shutdown critical event resolved. Safe shutdown will continue."
+ --#TYPE "APC CODE: PowerChute Network Shutdown critical event resolved. Safe shutdown will continue."
+ --#SUMMARY "Critical event resolved."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 780
+
+pcnsNetworkComsLost TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "SEVERE: PowerChute cannot communicate with NMC"
+ --#TYPE "APC CODE: PowerChute cannot communicate with NMC"
+ --#SUMMARY "PowerChute cannot communicate with NMC"
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 781
+
+pcnsNetworkComsLostResolved TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: PowerChute can communicate with NMC again."
+ --#TYPE "APC CODE: PowerChute can communicate with NMC again."
+ --#SUMMARY "PowerChute can communicate with NMC again."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 782
+
+pcnsNMCComsLost TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "SEVERE: NMC cannot communicate with UPS."
+ --#TYPE "APC CODE: NMC cannot communicate with UPS."
+ --#SUMMARY "NMC cannot communicate with UPS."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 783
+
+pcnsNMCComsLostResolved TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: NMC can communicate with UPS again."
+ --#TYPE "APC CODE: NMC can communicate with UPS again."
+ --#SUMMARY "NMC can communicate with UPS again."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 784
+
+pcnsTest TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: PowerChute has sent a test trap."
+ --#TYPE "APC CODE: PowerChute has sent a test trap."
+ --#SUMMARY "PowerChute has sent a test trap."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 785
+
+pcnsUpdateAvailable TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: PowerChute has detected that a newer version is available."
+ --#TYPE "APC CODE: PowerChute has detected that a newer version is available."
+ --#SUMMARY "PowerChute has detected that a newer version is available."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 786
+
+temporaryBypass TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: UPS on temporary bypass"
+ --#TYPE "APC UPS: On temporary bypass"
+ --#SUMMARY "The UPS is on temporary bypass."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 787
+
+
+
+
+pcbeCriticalEventActive TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "SEVERE: PowerChute Business Edition has begun a safe shutdown of the host."
+ --#TYPE "APC CODE: PowerChute Business Edition has begun a safe shutdown of the host."
+ --#SUMMARY "Safe shutdown of host initiated."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 790
+
+pcbeCriticalEventResolved TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: PowerChute Business Edition critical event resolved. Safe shutdown will continue."
+ --#TYPE "APC CODE: PowerChute Business Edition critical event resolved. Safe shutdown will continue."
+ --#SUMMARY "Critical event resolved."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 791
+
+pcbeComsLost TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "SEVERE: PowerChute cannot communicate with UPS"
+ --#TYPE "APC CODE: PowerChute cannot communicate with UPS"
+ --#SUMMARY "PowerChute cannot communicate with UPS"
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 792
+
+pcbeComsLostResolved TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: PowerChute can communicate with UPS again."
+ --#TYPE "APC CODE: PowerChute can communicate with UPS again."
+ --#SUMMARY "PowerChute can communicate with UPS again."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 793
+
+pcbeTest TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: PowerChute has sent a test trap."
+ --#TYPE "APC CODE: PowerChute has sent a test trap."
+ --#SUMMARY "PowerChute has sent a test trap."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 794
+
+pcbeUpdateAvailable TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: PowerChute has detected that a newer version is available."
+ --#TYPE "APC CODE: PowerChute has detected that a newer version is available."
+ --#SUMMARY "PowerChute has detected that a newer version is available."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 795
+-- pMM Trap Section
+
+pmmCriticalCondition TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger02, mtrapargsString }
+ DESCRIPTION
+ "SEVERE: A PMM critical condition has been detected.
+ The first variable is the serial number.
+ The second variable is the device name.
+ The third variable is the event ID.
+ The fourth variable is the instance number.
+ The fifth variable is the trap text message."
+ --#TYPE "PMM: A critical condition has been detected."
+ --#SUMMARY "A critical condition has been detected."
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 796
+
+pmmCriticalConditionCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger02, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A PMM critical condition has been cleared.
+ The first variable is the serial number.
+ The second variable is the device name.
+ The third variable is the event ID.
+ The fourth variable is the instance number.
+ The fifth variable is the trap text message."
+ --#TYPE "PMM: A critical condition has been cleared."
+ --#SUMMARY "A critical condition has been cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 797
+
+pmmWarningCondition TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger02, mtrapargsString }
+ DESCRIPTION
+ "WARNING: A PMM warning condition has been detected.
+ The first variable is the serial number.
+ The second variable is the device name.
+ The third variable is the event ID.
+ The fourth variable is the instance number.
+ The fifth variable is the trap text message."
+ --#TYPE "PMM: A warning condition has been detected."
+ --#SUMMARY "A warning condition has been detected."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 798
+
+pmmWarningConditionCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger02, mtrapargsString }
+ DESCRIPTION
+ "WARNING: A PMM warning condition has been cleared.
+ The first variable is the serial number.
+ The second variable is the device name.
+ The third variable is the event ID.
+ The fourth variable is the instance number.
+ The fifth variable is the trap text message."
+ --#TYPE "PMM: A warning condition has been cleared."
+ --#SUMMARY "A warning condition has been cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 799
+
+pmmInformationalCondition TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger02, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A PMM informational condition has been detected.
+ The first variable is the serial number.
+ The second variable is the device name.
+ The third variable is the event ID.
+ The fourth variable is the instance number.
+ The fifth variable is the trap text message."
+ --#TYPE "PMM: Informational condition detected."
+ --#SUMMARY "An informational condition has been detected."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 800
+
+pmmInformationalConditionCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger02, mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A PMM informational condition has been cleared.
+ The first variable is the serial number.
+ The second variable is the device name.
+ The third variable is the event ID.
+ The fourth variable is the instance number.
+ The fifth variable is the trap text message."
+ --#TYPE "PMM: Informational condition cleared."
+ --#SUMMARY "An informational condition has been cleared."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 801
+
+upsInputContactOutputRelayFault TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "SEVERE: A fault exists in the UPS input contact / output relay hardware."
+ --#TYPE "APC UPS: Input contact / output relay fault."
+ --#SUMMARY "Input contact / output relay fault."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 802
+
+upsInputContactOutputRelayFaultCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Fault no longer exists in the UPS input contact / output relay hardware."
+ --#TYPE "APC UPS: Input contact / output relay fault cleared."
+ --#SUMMARY "Input contact / output relay fault cleared."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 803
+
+upsAirFilterWarning TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: Air filter requires service."
+ --#TYPE "APC UPS: Air filter requires service."
+ --#SUMMARY "Air filter requires service."
+ --#ARGUMENTS { }
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 804
+
+upsAirFilterWarningCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Air filter no longer requires service."
+ --#TYPE "APC UPS: Air filter no longer requires service."
+ --#SUMMARY "Air filter no longer requires service."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 805
+
+upsBatteryPackIncompatible TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "SEVERE: Incompatible battery pack."
+ --#TYPE "APC UPS: Incompatible battery pack."
+ --#SUMMARY "Incompatible battery pack."
+ --#ARGUMENTS { }
+ --#SEVERITY SEVERE
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE DEGRADED
+ ::= 806
+
+upsBatteryPackIncompatibleCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: Incompatible battery pack no longer present."
+ --#TYPE "APC UPS: Incompatible battery pack no longer present."
+ --#SUMMARY "Incompatible battery pack no longer present."
+ --#ARGUMENTS { }
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 807
+
+upsInputContactAbnormal TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: UPS input contact is in the abnormal state."
+ --#TYPE "APC UPS: Input contact in abnormal state."
+ --#SUMMARY "UPS input contact in abnormal state."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 808
+
+upsInputContactAbnormalCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: UPS input contact has returned to its normal
+ state."
+ --#TYPE "APC UPS: Input contact has returned to the normal state."
+ --#SUMMARY "UPS input contact has returned to the normal state."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 809
+
+upsOutputRelayAbnormal TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "WARNING: A UPS output relay has switched to the abnormal state."
+ --#TYPE "APC UPS: Output relay in abnormal state."
+ --#SUMMARY "UPS output relay in abnormal state."
+ --#SEVERITY WARNING
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 810
+
+upsOutputRelayAbnormalCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A UPS output relay has returned to its normal
+ state."
+ --#TYPE "APC UPS: Output relay back in normal state."
+ --#SUMMARY "UPS output relay back in normal state."
+ --#SEVERITY INFORMATIONAL
+ --#TIMEINDEX 1
+ --#HELP ""
+ --#HELPTAG 0
+ --#STATE OPERATIONAL
+ ::= 811
+
+ePDUCriticalCondition TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "SEVERE: A EPDU critical condition has been detected."
+ ::= 812
+
+ePDUCriticalConditionCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "INFORMATIONAL: A EPDU critical condition has been cleared."
+ ::= 813
+
+ePDUWarningCondition TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "SEVERE: A Easy PDU warning condition has been detected."
+ ::= 814
+
+ePDUWarningConditionCleared TRAP-TYPE
+ ENTERPRISE apc
+ VARIABLES { mtrapargsString }
+ DESCRIPTION
+ "SEVERE: A Easy PDU warning condition has been cleared."
+ ::= 815
+
+
+END
|