+-- MIB table for T3610
+--
+-- v3.0 for firmware 1-5-7-2, 2016-04-11
+-----------------------------------------------------------------------
+T3610-MIB DEFINITIONS ::= BEGIN
+
+
+IMPORTS
+ enterprises
+ FROM RFC1155-SMI
+ OBJECT-TYPE
+ FROM RFC-1212
+ TRAP-TYPE
+ FROM RFC-1215;
+
+ DisplayString ::= OCTET STRING
+
+
+comet OBJECT IDENTIFIER ::= { enterprises 22626 }
+products OBJECT IDENTIFIER ::= { comet 1 }
+t3610 OBJECT IDENTIFIER ::= { products 2 }
+values OBJECT IDENTIFIER ::= { t3610 1 }
+global OBJECT IDENTIFIER ::= { t3610 2 }
+valuesInt OBJECT IDENTIFIER ::= { t3610 3 }
+settings OBJECT IDENTIFIER ::= { t3610 4 }
+traps OBJECT IDENTIFIER ::= { t3610 5 }
+tables OBJECT IDENTIFIER ::= { t3610 6 }
+
+
+-----------------------------------------------------------------------
+-- Measured values - String
+-----------------------------------------------------------------------
+temp OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..8))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Temperature"
+::= { values 1 }
+
+hum OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..8))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Relative humidity"
+::= { values 2 }
+
+compVal OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..8))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Computed value"
+::= { values 3 }
+
+tempAlarm OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..8))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Alarm on Temperature; none, high, low"
+::= { values 5 }
+
+humAlarm OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..8))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Alarm on Relative humidity; none, high, low"
+::= { values 6 }
+
+compValAlarm OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..8))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Alarm on Computed value; none, high, low"
+::= { values 7 }
+
+tempUnit OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..8))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Temperature Unit"
+::= { values 9 }
+
+humUnit OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..8))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Relative humidity Unit"
+::= { values 10 }
+
+compValUnit OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..8))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Computed value Unit"
+::= { values 11 }
+
+tempMin OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..8))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Minimal temperature"
+::= { values 13 }
+
+humMin OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..8))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Minimal relative humidity"
+::= { values 14 }
+
+compValMin OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..8))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Minimal computed value"
+::= { values 15 }
+
+tempMax OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..8))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Maximal temperature"
+::= { values 17 }
+
+humMax OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..8))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Maximal relative humidity"
+::= { values 18 }
+
+compValMax OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..8))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Maximal computed value"
+::= { values 19 }
+
+
+-----------------------------------------------------------------------
+-- Device informations
+-----------------------------------------------------------------------
+sensorName OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..68))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Device name"
+::= { global 1 }
+
+serialNumber OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..16))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Serial number"
+::= { global 2 }
+
+deviceType OBJECT-TYPE
+ SYNTAX INTEGER (0..65534)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Device type"
+::= { global 3 }
+
+
+-----------------------------------------------------------------------
+-- Measured values - Integer
+-----------------------------------------------------------------------
+tempInt OBJECT-TYPE
+ SYNTAX INTEGER (-5000..20000)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Temperature (value*10)"
+::= { valuesInt 1 }
+
+humInt OBJECT-TYPE
+ SYNTAX INTEGER (-5000..20000)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Relative humidity (value*10)"
+::= { valuesInt 2 }
+
+compValInt OBJECT-TYPE
+ SYNTAX INTEGER (-5000..20000)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Computed value (value*10)"
+::= { valuesInt 3 }
+
+tempAlarmInt OBJECT-TYPE
+ SYNTAX INTEGER (0..2)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Alarm on Temperature; 0 - No, 1 - High, 2 - Low"
+::= { valuesInt 5 }
+
+humAlarmInt OBJECT-TYPE
+ SYNTAX INTEGER (0..2)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Alarm on Relative humidity; 0 - No, 1 - High, 2 - Low"
+::= { valuesInt 6 }
+
+compValAlarmInt OBJECT-TYPE
+ SYNTAX INTEGER (0..2)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Alarm on Computed value; 0 - No, 1 - High, 2 - Low"
+::= { valuesInt 7 }
+
+
+-----------------------------------------------------------------------
+-- Alarm settings
+-----------------------------------------------------------------------
+tempLowInt OBJECT-TYPE
+ SYNTAX INTEGER (-5000..20000)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Temperature Limit Low (value*10)"
+::= { settings 1 }
+
+tempHighInt OBJECT-TYPE
+ SYNTAX INTEGER (-5000..20000)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Temperature Limit High (value*10)"
+::= { settings 2 }
+
+humLowInt OBJECT-TYPE
+ SYNTAX INTEGER (-5000..20000)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Humidity Limit Low (value*10)"
+::= { settings 3 }
+
+humHighInt OBJECT-TYPE
+ SYNTAX INTEGER (-5000..20000)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Humidity Limit High (value*10)"
+::= { settings 4 }
+
+compValLowInt OBJECT-TYPE
+ SYNTAX INTEGER (-5000..20000)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Computed value Limit Low (value*10)"
+::= { settings 5 }
+
+compValHighInt OBJECT-TYPE
+ SYNTAX INTEGER (-5000..20000)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Computed value Limit High (value*10)"
+::= { settings 6 }
+
+tempDelayInt OBJECT-TYPE
+ SYNTAX INTEGER (0..4500)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Temperature alaram delay [sec]"
+::= { settings 7 }
+
+humDelayInt OBJECT-TYPE
+ SYNTAX INTEGER (0..4500)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Humidity alaram delay [sec]"
+::= { settings 8 }
+
+compValDelayInt OBJECT-TYPE
+ SYNTAX INTEGER (0..4500)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Computed value alaram delay [sec]"
+::= { settings 9 }
+
+tempHystInt OBJECT-TYPE
+ SYNTAX INTEGER (0..10000)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Temperature hysteresis (value*10)"
+::= { settings 10 }
+
+humHystInt OBJECT-TYPE
+ SYNTAX INTEGER (0..10000)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Humidity hysteresis (value*10)"
+::= { settings 11 }
+
+compValHystInt OBJECT-TYPE
+ SYNTAX INTEGER (0..10000)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Computed value hysteresis (value*10)"
+::= { settings 12 }
+
+
+-----------------------------------------------------------------------
+-- Trap message
+-----------------------------------------------------------------------
+messageString OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Message giving more detailed information on alarms"
+::= { traps 1 }
+
+
+-----------------------------------------------------------------------
+-- Tables
+-----------------------------------------------------------------------
+historyTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF HistoryEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "Table of the history values"
+::= { tables 1 }
+
+historyEntry OBJECT-TYPE
+ SYNTAX HistoryEntry
+ ACCESS not-accessible
+ STATUS optional
+ DESCRIPTION "History values entries"
+ INDEX { histTemp }
+::= { historyTable 1 }
+
+HistoryEntry ::=
+ SEQUENCE {
+ histTemp
+ INTEGER,
+ histHum
+ INTEGER,
+ histCompVal
+ INTEGER
+ }
+
+histTemp OBJECT-TYPE
+ SYNTAX INTEGER(-5000..20000)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Temperature reading"
+::= { historyEntry 1 }
+
+histHum OBJECT-TYPE
+ SYNTAX INTEGER(-5000..20000)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Humidity reading"
+::= { historyEntry 2 }
+
+histCompVal OBJECT-TYPE
+ SYNTAX INTEGER (-5000..20000)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Computed value reading"
+::= { historyEntry 3 }
+
+
+-----------------------------------------------------------------------
+-- Traps definition
+-----------------------------------------------------------------------
+
+trapTest TRAP-TYPE
+ ENTERPRISE comet
+ VARIABLES { sensorName, messageString }
+ DESCRIPTION
+ "Testing trap, testing trap by TSensor software"
+ ::= 0
+
+trapNTPError TRAP-TYPE
+ ENTERPRISE comet
+ VARIABLES { sensorName, messageString }
+ DESCRIPTION
+ "Error on time synchronisation via NTP"
+ ::= 1
+
+trapEmailErrLogin TRAP-TYPE
+ ENTERPRISE comet
+ VARIABLES { sensorName, messageString }
+ DESCRIPTION
+ "SMTP error - unknown server"
+ ::= 2
+
+trapEmailErrAuth TRAP-TYPE
+ ENTERPRISE comet
+ VARIABLES { sensorName, messageString }
+ DESCRIPTION
+ "SMTP error - authentication error"
+ ::= 3
+
+trapEmailErrSome TRAP-TYPE
+ ENTERPRISE comet
+ VARIABLES { sensorName, messageString }
+ DESCRIPTION
+ "SMTP error - error during communication with server, unexpected return code"
+ ::= 4
+
+trapEmailErrSocket TRAP-TYPE
+ ENTERPRISE comet
+ VARIABLES { sensorName, messageString }
+ DESCRIPTION
+ "SMTP error - socket error, server is not available"
+ ::= 5
+
+trapEmailErrDNS TRAP-TYPE
+ ENTERPRISE comet
+ VARIABLES { sensorName, messageString }
+ DESCRIPTION
+ "SMTP error - DNS error"
+ ::= 6
+
+trapSOAPErrFile TRAP-TYPE
+ ENTERPRISE comet
+ VARIABLES { sensorName, messageString }
+ DESCRIPTION
+ "SOAP error - file SOAP not found"
+ ::= 7
+
+trapSOAPErrDNS TRAP-TYPE
+ ENTERPRISE comet
+ VARIABLES { sensorName, messageString }
+ DESCRIPTION
+ "SOAP error - DNS error"
+ ::= 8
+
+trapSOAPErrSocket TRAP-TYPE
+ ENTERPRISE comet
+ VARIABLES { sensorName, messageString }
+ DESCRIPTION
+ "SOAP error - socket error, server is not available"
+ ::= 9
+
+trapSOAPErrDelivery TRAP-TYPE
+ ENTERPRISE comet
+ VARIABLES { sensorName, messageString }
+ DESCRIPTION
+ "SOAP error - delivery error, wrong return code from server"
+ ::= 10
+
+trapTempHighAlarm TRAP-TYPE
+ ENTERPRISE comet
+ VARIABLES { sensorName, messageString, temp, tempAlarmInt }
+ DESCRIPTION
+ "Trap for high alarm on temperature"
+ ::= 11
+
+trapHumHighAlarm TRAP-TYPE
+ ENTERPRISE comet
+ VARIABLES { sensorName, messageString, hum, humAlarmInt }
+ DESCRIPTION
+ "Trap for high alarm on relative humidity"
+ ::= 12
+
+trapCompValHighAlarm TRAP-TYPE
+ ENTERPRISE comet
+ VARIABLES { sensorName, messageString, compVal, compValAlarmInt }
+ DESCRIPTION
+ "Trap for high alarm on computed value"
+ ::= 13
+
+trapTempLowAlarm TRAP-TYPE
+ ENTERPRISE comet
+ VARIABLES { sensorName, messageString, temp, tempAlarmInt }
+ DESCRIPTION
+ "Trap for low alarm on temperature"
+ ::= 21
+
+trapHumLowAlarm TRAP-TYPE
+ ENTERPRISE comet
+ VARIABLES { sensorName, messageString, hum, humAlarmInt }
+ DESCRIPTION
+ "Trap for low alarm on relative humidity"
+ ::= 22
+
+trapCompValLowAlarm TRAP-TYPE
+ ENTERPRISE comet
+ VARIABLES { sensorName, messageString, compVal, compValAlarmInt }
+ DESCRIPTION
+ "Trap for low alarm on computed value"
+ ::= 23
+
+trapTempClrAlarm TRAP-TYPE
+ ENTERPRISE comet
+ VARIABLES { sensorName, messageString, temp, tempAlarmInt }
+ DESCRIPTION
+ "Trap for clearing alarm on temperature"
+ ::= 31
+
+trapHumClrAlarm TRAP-TYPE
+ ENTERPRISE comet
+ VARIABLES { sensorName, messageString, hum, humAlarmInt }
+ DESCRIPTION
+ "Trap for clearing alarm on relative humidity"
+ ::= 32
+
+trapCompValClrAlarm TRAP-TYPE
+ ENTERPRISE comet
+ VARIABLES { sensorName, messageString, compVal, compValAlarmInt }
+ DESCRIPTION
+ "Trap for clearing alarm on computed value"
+ ::= 33
+
+trapTempError TRAP-TYPE
+ ENTERPRISE comet
+ VARIABLES { sensorName, messageString, temp, tempAlarmInt }
+ DESCRIPTION
+ "Trap for error on temperature"
+ ::= 41
+
+trapHumError TRAP-TYPE
+ ENTERPRISE comet
+ VARIABLES { sensorName, messageString, hum, humAlarmInt }
+ DESCRIPTION
+ "Trap for error on relative humidity"
+ ::= 42
+
+trapCompValError TRAP-TYPE
+ ENTERPRISE comet
+ VARIABLES { sensorName, messageString, compVal, compValAlarmInt }
+ DESCRIPTION
+ "Trap for error on computed value"
+ ::= 43
+
+
+END