diff --git a/MIBS/liebert/LIEBERT-GP-POWER-MIB b/MIBS/liebert/LIEBERT-GP-POWER-MIB new file mode 100644 index 0000000..3730c64 --- /dev/null +++ b/MIBS/liebert/LIEBERT-GP-POWER-MIB @@ -0,0 +1,3300 @@ +LIEBERT-GP-POWER-MIB DEFINITIONS ::= BEGIN
+
+IMPORTS
+ MODULE-IDENTITY,
+ OBJECT-IDENTITY,
+ OBJECT-TYPE,
+ Integer32,
+ Unsigned32
+ FROM SNMPv2-SMI
+ lgpPower,
+ liebertPowerModuleReg
+ FROM LIEBERT-GP-REGISTRATION-MIB
+ ;
+
+-- =============================================================================
+-- Module Identification and Registration
+-- =============================================================================
+
+liebertGlobalProductsPowerModule MODULE-IDENTITY
+ LAST-UPDATED "201307100000Z"
+ ORGANIZATION "Liebert Corporation"
+ CONTACT-INFO
+ "Contact: Technical Support
+
+ Postal:
+ Liebert Corporation
+ 1050 Dearborn Drive
+ P.O. Box 29186
+ Columbus OH, 43229
+ US
+
+ Tel: +1 (800) 222-5877
+
+ E-mail: liebert.monitoring@vertivco.com
+ Web: www.vertivco.com
+
+ Author: Gregory M. Hoge"
+
+ DESCRIPTION
+ "The MIB module used to register Liebert POWER related SNMP OIDs.
+
+ Copyright 2000-2008 Liebert Corporation. All rights reserved.
+ Reproduction of this document is authorized on the condition
+ that the forgoing copyright notice is included.
+
+ This Specification is supplied 'AS IS' and Liebert Corporation
+ makes no warranty, either express or implied, as to the use,
+ operation, condition, or performance of the Specification."
+
+ REVISION "201307100000Z"
+ DESCRIPTION
+ "Added support for GXT4 economic operation mode and outlet control."
+
+ REVISION "200811170000Z"
+ DESCRIPTION
+ "Added support for NXL unit."
+
+ REVISION "200807020000Z"
+ DESCRIPTION
+ "Replaced INTEGER with Integer32 (SMIv2).
+ Minor spelling fixes and formatting."
+
+ REVISION "200801100000Z"
+ DESCRIPTION
+ "Modified contact email address and removed redundant
+ lgpPwrMeasurementPointNumLines."
+
+ REVISION "200602220000Z"
+ DESCRIPTION
+ "Added support for Liebert DS Unit."
+
+ ::= { liebertPowerModuleReg 1 }
+
+-- =============================================================================
+-- lgpPower - Liebert Power Registrations
+-- =============================================================================
+
+lgpPwrBattery OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This sub-tree is used to register Liebert Power Battery object
+ identifiers."
+ REFERENCE
+ "The registrations for the objects in this sub-tree are
+ defined below in the sub-section titled Liebert Power Battery Group."
+ ::= { lgpPower 1 }
+
+lgpPwrMeasurements OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This sub-tree registers Liebert Power Measurement object
+ identifiers. The sub-tree contains tables and well known power
+ measurement points."
+ REFERENCE
+ "The registrations for the objects in this sub-tree are defined
+ below in the sub-section titled Liebert Power Measurement Group."
+ ::= { lgpPower 2 }
+
+lgpPwrStatus OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This sub-tree registers Liebert Power Status object
+ identifiers. This is the location of power related status information
+ that does not fit into a more specific category such as the
+ lgpPwrConversion sub-tree."
+ REFERENCE
+ "The registrations for the objects in this sub-tree are defined
+ below in the sub-section titled Liebert Power Status Group"
+ ::= { lgpPower 3 }
+
+lgpPwrSettings OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This sub-tree registers Liebert Power Static Switch object
+ identifiers."
+ REFERENCE
+ "The registrations for the objects in this sub-tree are defined
+ below in the sub-section titled Liebert Power Settings Group."
+ ::= { lgpPower 4 }
+
+lgpPwrConversion OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This sub-tree is used to register Liebert Power Conversion object
+ identifiers."
+ REFERENCE
+ "The registrations for the objects in this sub-tree are
+ defined below in the sub-section titled Liebert Power Conversion Group."
+ ::= { lgpPower 5 }
+
+lgpPwrControl OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This sub-tree is used to register Liebert Power Control object
+ identifiers."
+ REFERENCE
+ "The registrations for the objects in this sub-tree are
+ defined below in the sub-section titled Liebert Power Control Group."
+ ::= { lgpPower 6 }
+
+lgpPwrTopology OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This sub-tree is used to register Liebert Power Topology object
+ identifiers."
+ REFERENCE
+ "The registrations for the objects in this sub-tree are
+ defined below in the sub-section titled Liebert Power Topology Group."
+ ::= { lgpPower 7 }
+
+lgpPwrStatistic OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This sub-tree is used to register Liebert Power Statistic object
+ identifiers."
+ REFERENCE
+ "The registrations for the objects in this sub-tree are
+ defined below in the sub-section titled Liebert Power Statistic Group."
+ ::= { lgpPower 8 }
+
+lgpPwrConfig OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This sub-tree is used to register Liebert Power Configuration
+ Object identifiers."
+ REFERENCE
+ "The registrations for the objects in this sub-tree are
+ defined below in the sub-section titled Liebert Power Configuration
+ Group."
+ ::= { lgpPower 9 }
+
+-- =============================================================================
+-- lgpPwrBattery - Liebert Power Battery Group
+-- =============================================================================
+
+lgpPwrNumberInstalledBatteryModules OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of battery modules installed in the device."
+ ::= { lgpPwrBattery 1 }
+
+lgpPwrNumberFailedBatteryModules OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of battery modules in the device that have failed."
+ ::= { lgpPwrBattery 2 }
+
+lgpPwrNumberRedundantBatteryModules OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of redundant battery modules in the device."
+ ::= { lgpPwrBattery 3 }
+
+lgpPwrNumberActiveBatteryModules OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of active battery modules in the device."
+ ::= { lgpPwrBattery 4 }
+
+lgpPwrConfigLowBatteryWarningTime OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "minutes"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The value of the device's estimated minutes of remaining battery
+ at which a lgpEventLowBatteryWarning notification will be sent."
+ ::= { lgpPwrBattery 5 }
+
+lgpPwrNumberBatteryModuleWarnings OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of battery modules in the device that have a warning."
+ ::= { lgpPwrBattery 6 }
+
+lgpPwrBatteryCount OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Count"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of batteries installed."
+ ::= { lgpPwrBattery 7 }
+
+lgpPwrBatteryTestResult OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ unknown(1),
+ passed(2),
+ failed(3),
+ inProgress(4),
+ systemFailure(5),
+ inhibited(6)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The outcome of the previous battery test."
+ ::= { lgpPwrBattery 8 }
+
+lgpPwrNominalBatteryCapacity OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "minutes"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The nominal battery capacity of the system (in minutes) at full load."
+ ::= { lgpPwrBattery 9 }
+
+lgpPwrBatteryFloatVoltage OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Volt"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The battery float voltage of the system."
+ ::= { lgpPwrBattery 10 }
+
+lgpPwrBatteryEndOfDischargeVoltage OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The battery voltage threshold at which the batteries are considered
+ completely discharged."
+ ::= { lgpPwrBattery 11 }
+
+lgpPwrAutomaticBatteryTestInterval OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "hours"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The automatic battery test interval."
+ ::= { lgpPwrBattery 12 }
+
+lgpPwrAutomaticBatteryTestCountdown OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "minutes"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The time remaining before the next battery test."
+ ::= { lgpPwrBattery 13 }
+
+lgpPwrBatteryChargeStatus OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ fullycharged(1),
+ notfullycharged(2),
+ charging(3),
+ discharging(4)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present state of the system's battery charge.
+ A value of 'charging' indicates the batteries are currently charging.
+ A value of 'discharging' indicates the batteries are currently
+ discharging. A value of 'fullycharged' indicates the batteries are
+ charged to their full capacity. A value of 'notfullycharged' indicates
+ the battery charge is neither fully charged, charging or discharging."
+ ::= { lgpPwrBattery 14 }
+
+lgpPwrBatteryLifeEnhancer OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ on(1),
+ off(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The state of the battery life enhancer. When 'on', it will
+ preserve battery life."
+ ::= { lgpPwrBattery 15 }
+
+lgpPwrBatteryCharger OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ on(1),
+ off(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The state of the battery charger."
+ ::= { lgpPwrBattery 16 }
+
+lgpPwrBatteryChargeMode OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ float(1),
+ equalize(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The mode of the battery charger: 'float' charging or 'equalize'
+ charging."
+ ::= { lgpPwrBattery 17 }
+
+lgpPwrBatteryTimeRemaining OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "minutes"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "An estimate of the time to battery charge depletion under the present
+ load conditions if the utility power is off and remains off, or if it
+ were to be lost and remain off.
+
+ NOTE: A UPS is expected to provide a battery time remaining value
+ when not operating on battery. However, if the system is not capable of
+ providing this information, then this point will return 65535 to
+ indicate that the value is unavailable."
+ ::= { lgpPwrBattery 18 }
+
+lgpPwrBatteryCapacity OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "percent"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present percentage of battery capacity."
+ ::= { lgpPwrBattery 19 }
+
+lgpPwrBatteryCabinet OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This sub-tree contains items related to battery cabinets."
+ ::= { lgpPwrBattery 20 }
+
+ lgpPwrBatteryCabinetCount OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Count"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The number of battery cabinets installed with this device.
+ Note some devices may not permit writing a value to this object."
+ ::= { lgpPwrBatteryCabinet 1 }
+
+ lgpPwrBatteryCabinetType OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ notSpecified(1),
+ internal(2),
+ external(3),
+ lrt(4)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The type of battery cabinet(s) installed on this device.
+ Enumeration definitions:
+ notSpecified - The type has not been specified in the
+ device's configuration.
+ internal - Battery cabinets are internal to the device.
+ external - Device has external battery cabinets installed.
+ lrt - Long Run Time cabinets.
+ Note some devices may not permit writing a value to this object."
+ ::= { lgpPwrBatteryCabinet 2 }
+
+ lgpPwrBatteryCabinetRatedCapacity OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "0.1 Amp-hour"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Battery cabinet rated capacity (tenths of Amp-hours).
+ This assumes that each cabinet is of the same type and capacity.
+ This is not a sum of the rating for all attached cabinets.
+ Note some devices may not permit writing a value to this object."
+ ::= { lgpPwrBatteryCabinet 3 }
+
+ lgpPwrBatteryLeadAcidCellCount OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Count"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Battery cell count - lead-acid. The number of cells that comprise
+ the lead acid battery string."
+ ::= { lgpPwrBatteryCabinet 4 }
+
+ lgpPwrBatteryNiCadCellCount OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Count"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Battery cell count - nickel-cadmium. The number of cells that
+ comprise the nickel-cadmium battery string."
+ ::= { lgpPwrBatteryCabinet 5 }
+
+lgpPwrBatteryAmpHoursConsumed OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Amp-hour"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The cumulative battery Amp-hours withdrawn over the life of the
+ battery. This value persists across reboots. Typically, this value is
+ reset back to zero when the batteries are replaced."
+ ::= { lgpPwrBattery 21 }
+
+lgpPwrBatteryAmpHoursDischargeConsumed OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Amp-hour"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The battery Amp-hours withdrawn during the current/latest
+ discharge. This value does not persist across reboots."
+ ::= { lgpPwrBattery 22 }
+
+lgpPwrBatteryLastDischargeTime OBJECT-TYPE
+ SYNTAX Unsigned32
+ UNITS "seconds"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The date and time of the last battery discharge. Typically this is the
+ time when the discharge starts. This value persists across reboots.
+ The date and time are determined in seconds since the epoch on
+ January 1, 1970."
+ ::= { lgpPwrBattery 23 }
+
+lgpPwrBatteryLastCommissionTime OBJECT-TYPE
+ SYNTAX Unsigned32
+ UNITS "seconds"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The date and time when the battery system was put into service.
+ This information persists across system reboot events. It is the
+ responsibility of Service to reset this date/time when the batteries
+ are replaced. The date and time are determined in seconds since the
+ epoch on January 1, 1970."
+ ::= { lgpPwrBattery 24 }
+
+lgpPwrBatteryPresentDischargeTime OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "seconds"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The total time spent on battery during the current or last discharge.
+
+ NOTE: While not discharging, some systems may display zero instead of
+ the last discharge."
+ ::= { lgpPwrBattery 25 }
+
+lgpPwrBatteryCapacityStatus OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ unknown(1),
+ batteryNormal(2),
+ batteryLow(3),
+ batteryDepleted(4)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The indication of the capacity remaining in the UPS
+ system's batteries.
+
+ NOTE: In a single-module system, this point is intended to have the same
+ behavior as the RFC1628 point upsBatteryStatus."
+ ::= { lgpPwrBattery 26 }
+
+lgpPwrBatteryCircuitBreakerState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ unknown(0),
+ open(1),
+ closed(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The state of the Battery Circuit Breaker."
+ ::= { lgpPwrBattery 27 }
+
+-- =============================================================================
+-- lgpPwrMeasurements - Liebert Power Measurement Group
+-- =============================================================================
+
+-- -----------------------------------------------------------------------------
+-- Well Known Power Measurement Points
+-- -----------------------------------------------------------------------------
+
+lgpPwrWellKnownMeasurementPoints OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This sub-tree registers well known Liebert Power Measurement
+ Points. The object identifier names usually imply locations
+ where the measurement is taken -- such as 'input', 'output'
+ and 'bypass'."
+ REFERENCE
+ "These well known measurement identifiers are referenced in the
+ 'lgpPwrMeasurementPointId' column in the
+ 'lgpPwrMeasurementPointTable'."
+ ::= { lgpPwrMeasurements 1 }
+
+ lgpPwrSource1Input OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This sub-tree is used to register a source 1 input as a
+ well known measurement point. It is intended that no sub-trees
+ be created below this node.
+
+ Power input to the managed device from power source 1.
+ Many power systems contain more than one input source and
+ many of them have more than one measurement point per input
+ source. This identifier represents one input source for the
+ system but does not necessarily represent the 'first' one.
+ The input sources' numbering with respect to
+ 'lgpPwrSource1Input' etc. may depend on the physical wiring
+ of the system when it was installed."
+ ::= { lgpPwrWellKnownMeasurementPoints 1 }
+
+ lgpPwrSource2Input OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This sub-tree is used to register a source 2 input as a
+ well known measurement point. It is intended that no sub-trees
+ be created below this node.
+
+ Power input to the managed device from power source 2.
+ Many power systems contain more than one input source and
+ many of them have more than one measurement point per input
+ source. This identifier represents one input source for the
+ system but does not necessarily represent the 'first' one.
+ The input sources' numbering with respect to
+ 'lgpPwrSource2Input' etc. may depend on the physical wiring
+ of the system when it was installed."
+ ::= { lgpPwrWellKnownMeasurementPoints 2 }
+
+ lgpPwrSourcePdu1Input OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This sub-tree is used to register a source PDU 1 input as a
+ well known measurement point. It is intended that no sub-trees
+ be created below this node.
+
+ Power input to the managed device from power distribution
+ unit 1. Many power systems contain more than one input source
+ and many of them have more than one measurement point per input
+ source. This identifier represents one input source for the
+ system but does not necessarily represent the 'first' one.
+ The input sources' numbering with respect to
+ 'lgpPwrSourcePdu1Input' etc. may depend on the physical wiring
+ of the system when it was installed."
+ ::= { lgpPwrWellKnownMeasurementPoints 3 }
+
+ lgpPwrSourcePdu2Input OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This sub-tree is used to register a source PDU 2 input as a
+ well known measurement point. It is intended that no sub-trees
+ be created below this node.
+
+ Power input to the managed device from power distribution
+ unit 1. Many power systems contain more than one input source
+ and many of them have more than one measurement point per input
+ source. This identifier represents one input source for the
+ system but does not necessarily represent the 'first' one.
+ The input sources' numbering with respect to
+ 'lgpPwrSourcePdu2Input' etc. may depend on the physical wiring
+ of the system when it was installed."
+ ::= { lgpPwrWellKnownMeasurementPoints 4 }
+
+ lgpPwrOutputToLoad OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This sub-tree is used to register the output to the critical
+ load as a well known measurement point. It is intended that
+ no sub-trees be created below this node."
+ ::= { lgpPwrWellKnownMeasurementPoints 5 }
+
+ lgpPwrMeasBattery OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This sub-tree is used to register a battery as a well known
+ measurement point. It is intended that no sub-trees be created
+ below this node."
+ ::= { lgpPwrWellKnownMeasurementPoints 6 }
+
+ lgpPwrMeasBypass OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This sub-tree is used to register a bypass as a well known
+ measurement point. It is intended that no sub-trees be created
+ below this node."
+ ::= { lgpPwrWellKnownMeasurementPoints 7 }
+
+ lgpPwrMeasDcBus OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This sub-tree is used to register a DC bus as a well known
+ measurement point. It is intended that no sub-trees be created
+ below this node."
+ ::= { lgpPwrWellKnownMeasurementPoints 8 }
+
+ lgpPwrMeasSystemOutput OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This sub-tree is used to register the output of a
+ multi-module system as a well known measurement point.
+ It is intended that no sub-trees be created below this node.
+
+ This identifier represents the power related data of the
+ system."
+ ::= { lgpPwrWellKnownMeasurementPoints 9 }
+
+ lgpPwrMeasBatteryCabinet OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This sub-tree is used to register the voltage between the
+ most negative and the most postive terminals of a battery
+ cabinet. To determine the cabinet being described in a
+ multi-cabinet system, this point implements an additional
+ two indexes. The first index describes the module the cabinet
+ is located in. The second index describes the cabinet
+ number. In an SMS(Single-Module System) the first index is
+ always 1.
+
+ Example: lgpPwrMeasBatteryCabinet.2.4
+
+ 'lgpPwrMeasBatteryCabinet' = Point is a battery cabinet.
+ '.2' = Cabinet is in the second module.
+ '.4' = Cabinet number 4"
+ ::= { lgpPwrWellKnownMeasurementPoints 10 }
+
+-- -----------------------------------------------------------------------------
+-- AC Power Measurement Point Table
+-- -----------------------------------------------------------------------------
+
+lgpPwrMeasurementPointTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF LgpPwrMeasurementPointEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "This table contains a list of AC power measurement point entries.
+ The table contains zero, one, or many rows, depending upon the number
+ of power related measurement points available. The NMS cannot
+ create or delete rows from the table. The rows are created by the
+ agent based upon the capabilities of the managed device. Each row
+ in the table represents a series of measurements on a given point
+ or location within the system. Measurement points/locations are
+ identified by the object identifier 'lgpPwrMeasurementPointId' in the
+ 'LgpPwrMeasurementPointEntry' object. The actual measurement being
+ taken at that identified point is identified by the other
+ corresponding columns in the LgpPwrMeasurementPointEntry for the
+ particular row of the table."
+ REFERENCE
+ "The measurement points represented by 'lgpPwrMeasurementPointId'
+ can be found in the sub-tree lgpPwrWellKnownMeasurementPoints.
+ Additional measurement detail on a 'per line' basis is available in
+ the lgpPwrLineMeasurementTable"
+ ::= { lgpPwrMeasurements 2 }
+
+ lgpPwrMeasurementPointEntry OBJECT-TYPE
+ SYNTAX LgpPwrMeasurementPointEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "This entry defines the measurements to be populated in the
+ various columns of the 'lgpPwrMeasurementPointTable'."
+ INDEX { lgpPwrMeasurementPointIndex }
+ ::= { lgpPwrMeasurementPointTable 1 }
+
+ LgpPwrMeasurementPointEntry ::= SEQUENCE
+ {
+ lgpPwrMeasurementPointIndex Unsigned32,
+ lgpPwrMeasurementPointId OBJECT IDENTIFIER,
+ lgpPwrMeasurementPointNumLines Integer32,
+ lgpPwrMeasurementPointNomVolts Integer32,
+ lgpPwrMeasurementPointNomFrequency Integer32,
+ lgpPwrMeasurementPointFrequency Integer32,
+ lgpPwrMeasurementPointApparentPower Integer32,
+ lgpPwrMeasurementPointTruePower Integer32,
+ lgpPwrMeasurementPointPowerFactor Integer32,
+ lgpPwrMeasurementPointWattHours Integer32,
+ lgpPwrMeasurementPointVAPercent Integer32,
+ lgpPwrMeasurementPointNeutralCurrent Integer32,
+ lgpPwrMeasurementPointGroundCurrent Integer32,
+ lgpPwrMeasurementPointNomCurrent Integer32,
+ lgpPwrMeasurementPointNomPowerFactor Integer32,
+ lgpPwrMeasurementPointNomVA Integer32,
+ lgpPwrMeasurementPointNomW Integer32,
+ lgpPwrMeasurementPointPowerFactorTag INTEGER
+ }
+
+ lgpPwrMeasurementPointIndex OBJECT-TYPE
+ SYNTAX Unsigned32
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "This is the index that indicates the row of the
+ 'lgpPwrMeasurementPointTable' for a power measurement point."
+ ::= { lgpPwrMeasurementPointEntry 1 }
+
+ lgpPwrMeasurementPointId OBJECT-TYPE
+ SYNTAX OBJECT IDENTIFIER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "An OID representing a well known measurement point.
+ These object identifiers indicate a point or location of power
+ measurement in a power system. The OID's name usually
+ implies a location of the measurement point such as
+ 'input', 'output', 'bypass' etc."
+ REFERENCE
+ "The object identifiers in this column can be found in the sub-tree
+ 'lgpPwrWellKnownMeasurementPoints'."
+ ::= { lgpPwrMeasurementPointEntry 2 }
+
+ lgpPwrMeasurementPointNumLines OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Count"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of lines on the indicated power measurement point.
+ (i.e. the number of phases on the power source being measured.)"
+ ::= { lgpPwrMeasurementPointEntry 3 }
+
+ lgpPwrMeasurementPointNomVolts OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Volt"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The magnitude of the nominal voltage on the power source being
+ measured."
+ ::= { lgpPwrMeasurementPointEntry 4 }
+
+ lgpPwrMeasurementPointNomFrequency OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Hertz"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The nominal or configured/expected frequency for the power
+ source indicated by 'lgpPwrMeasurementPointId' in the
+ corresponding row in the lgpPwrMeasurementPointTable."
+ ::= { lgpPwrMeasurementPointEntry 5 }
+
+ lgpPwrMeasurementPointFrequency OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Hertz"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present (actual) frequency for the power source indicated
+ by 'lgpPwrMeasurementPointId' in the corresponding row in the
+ lgpPwrMeasurementPointTable."
+ ::= { lgpPwrMeasurementPointEntry 6 }
+
+ lgpPwrMeasurementPointApparentPower OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Volt-Amp"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present apparent AC power for the power source
+ indicated by 'lgpPwrMeasurementPointId' in the corresponding row
+ in the lgpPwrMeasurementPointTable."
+ ::= { lgpPwrMeasurementPointEntry 7 }
+
+ lgpPwrMeasurementPointTruePower OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Watt"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present AC power for the power source indicated by
+ 'lgpPwrMeasurementPointId' in the corresponding row in the
+ lgpPwrMeasurementPointTable."
+ ::= { lgpPwrMeasurementPointEntry 8 }
+
+ lgpPwrMeasurementPointPowerFactor OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS ".01 Power Factor"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present Power Factor for the power source indicated by
+ 'lgpPwrMeasurementPointId' in the corresponding row in the
+ lgpPwrMeasurementPointTable."
+ ::= { lgpPwrMeasurementPointEntry 9 }
+
+ lgpPwrMeasurementPointWattHours OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Watt-Hour"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present number of Watt Hours for the power source indicated by
+ 'lgpPwrMeasurementPointId' in the corresponding row in the
+ lgpPwrMeasurementPointTable."
+ ::= { lgpPwrMeasurementPointEntry 10 }
+
+ lgpPwrMeasurementPointVAPercent OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "0.1 Percent"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The percentage of the rated apparent AC power of the power
+ source indicated by 'lgpPwrMeasurementPointId' in the corresponding
+ row in the lgpPwrMeasurementPointTable."
+ ::= { lgpPwrMeasurementPointEntry 11 }
+
+ lgpPwrMeasurementPointNeutralCurrent OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Amp"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present neutral current of the power point indicated by
+ 'lgpPwrMeasurementPointId' in the corresponding row in the
+ lgpPwrMeasurementPointTable."
+ ::= { lgpPwrMeasurementPointEntry 12 }
+
+ lgpPwrMeasurementPointGroundCurrent OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "0.1 Amp"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present ground current of the power point indicated by
+ 'lgpPwrMeasurementPointId' in the corresponding row in the
+ lgpPwrMeasurementPointTable."
+ ::= { lgpPwrMeasurementPointEntry 13 }
+
+ lgpPwrMeasurementPointNomCurrent OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "0.1 Amp"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The nominal or configured/expected current of the power point
+ indicated by 'lgpPwrMeasurementPointId' in the corresponding row
+ in the lgpPwrMeasurementPointTable."
+ ::= { lgpPwrMeasurementPointEntry 14 }
+
+ lgpPwrMeasurementPointNomPowerFactor OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS ".01 Power Factor"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The nominal or configured/expected power factor of the power point
+ indicated by 'lgpPwrMeasurementPointId' in the corresponding row
+ in the lgpPwrMeasurementPointTable."
+ ::= { lgpPwrMeasurementPointEntry 15 }
+
+ lgpPwrMeasurementPointNomVA OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Volt-Amp"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The nominal or configured/expected apparent AC power for the power
+ source indicated by 'lgpPwrMeasurementPointId' in the corresponding
+ row in the lgpPwrMeasurementPointTable."
+ ::= { lgpPwrMeasurementPointEntry 16 }
+
+ lgpPwrMeasurementPointNomW OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Watt"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The nominal or configured/expected true AC power for the power
+ source indicated by 'lgpPwrMeasurementPointId' in the corresponding
+ row in the lgpPwrMeasurementPointTable."
+ ::= { lgpPwrMeasurementPointEntry 17 }
+
+ lgpPwrMeasurementPointPowerFactorTag OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ leading(1),
+ lagging(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present description of the Power Factor for the power source
+ indicated by 'lgpPwrMeasurementPointId' in the corresponding row
+ in the lgpPwrMeasurementPointTable. If Leading, the load is said
+ to be capacitive and the phase of the current leads the voltage.
+ If Lagging, the load is said to be inductive and the phase of the
+ current lags the voltage."
+ ::= { lgpPwrMeasurementPointEntry 19 }
+
+-- -----------------------------------------------------------------------------
+-- Source Measurement Line/Phase Table
+-- -----------------------------------------------------------------------------
+
+lgpPwrLineMeasurementTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF LgpPwrLineMeasurementEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A list of power measurements for each phase/line for a given
+ power measurement point/location in the 'lgpPwrMeasurementPointTable'.
+ The lgpPwrMeasurementPointIndex in this table corresponds to the
+ index in the lgpPwrMeasurementPointTable.
+
+ This table contains zero, one, or
+ many rows, depending upon the number of power line source objects
+ available. The NMS cannot create or delete rows from the table.
+ The rows are created by the agent based upon the capabilities of
+ the managed device."
+ ::= { lgpPwrMeasurements 3 }
+
+ lgpPwrLineMeasurementEntry OBJECT-TYPE
+ SYNTAX LgpPwrLineMeasurementEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "This entry defines the contents of the columns for the table
+ 'lgpPwrLineMeasurementTable'."
+ REFERENCE
+ "The lgpPwrMeasurementPointIndex can be found in the
+ lgpPwrMeasurementPointTable. This index identifies the measurement
+ point for which the line detail measurement in the table applies."
+ INDEX { lgpPwrMeasurementPtIndex, lgpPwrLineMeasurementIndex }
+ ::= { lgpPwrLineMeasurementTable 1 }
+
+ LgpPwrLineMeasurementEntry ::= SEQUENCE
+ {
+ lgpPwrMeasurementPtIndex Unsigned32,
+ lgpPwrLineMeasurementIndex Unsigned32,
+ lgpPwrMeasurementPoint OBJECT IDENTIFIER,
+ lgpPwrLineMeasurementVoltsLL Integer32,
+ lgpPwrLineMeasurementVoltsLN Integer32,
+ lgpPwrLineMeasurementCurrent Integer32,
+ lgpPwrLineMeasurementCapacity Integer32,
+ lgpPwrLineMeasurementVA Integer32,
+ lgpPwrLineMeasurementTruePower Integer32,
+ lgpPwrLineMeasurementVoltageTHD Integer32,
+ lgpPwrLineMeasurementCurrentTHD Integer32,
+ lgpPwrLineMeasurementKFactorCurrent Integer32,
+ lgpPwrLineMeasurementCrestFactorCurrent Integer32,
+ lgpPwrLineMeasurementPowerFactor Integer32,
+ lgpPwrLineMeasurementPowerFactorTag INTEGER,
+ lgpPwrLineMeasurementMaxVolts Integer32,
+ lgpPwrLineMeasurementMinVolts Integer32,
+ lgpPwrLineMeasurementVAR Integer32,
+ lgpPwrLineMeasurementPercentLoad Integer32,
+ lgpPwrLineMeasurementVolts Integer32,
+ lgpPwrLineMeasurementVACapacity Integer32
+ }
+
+ lgpPwrMeasurementPtIndex OBJECT-TYPE
+ SYNTAX Unsigned32
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "This is the index indicating the row of the table
+ 'lgpPwrMeasurementPointTable' for a power measurement point."
+ ::= { lgpPwrLineMeasurementEntry 1 }
+
+ lgpPwrLineMeasurementIndex OBJECT-TYPE
+ SYNTAX Unsigned32
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "This is the index indicating the row of the table
+ 'lgpPwrLineMeasurementTable' for a power measurement point."
+ ::= { lgpPwrLineMeasurementEntry 2 }
+
+ lgpPwrMeasurementPoint OBJECT-TYPE
+ SYNTAX OBJECT IDENTIFIER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "An OID representing a well known measurement point.
+ These object identifiers indicate a point or location of power
+ measurement in a power system. The OID name usually
+ implies a location of the measurement point such as
+ 'input', 'output', 'bypass', etc."
+ REFERENCE
+ "The object identifiers in this column can be found in the sub-tree
+ 'lgpPwrWellKnownMeasurementPoints' and correspond to the entry in
+ the table lgpPwrMeasurementPointTable."
+ ::= { lgpPwrLineMeasurementEntry 3 }
+
+ lgpPwrLineMeasurementVoltsLL OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Volt"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present Line-to-Line voltage measurement for the indicated
+ source. The line being measured is given by the
+ lgpPwrLineMeasurementIndex [1 = AB, 2 = BC, 3 = CA]."
+ ::= { lgpPwrLineMeasurementEntry 4 }
+
+ lgpPwrLineMeasurementVoltsLN OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Volt"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present Line-to-neutral voltage measurement for the indicated
+ source. The line being measured is given by the
+ lgpPwrLineMeasurementIndex where [1 = A, 2 = B, 3 = C]."
+ ::= { lgpPwrLineMeasurementEntry 5 }
+
+ lgpPwrLineMeasurementCurrent OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Amp"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present current measurement for the indicated source. The line
+ being measured is given by the 'lgpPwrLineMeasurementIndex' where
+ [1 = A, 2 = B, 3 = C]."
+ ::= { lgpPwrLineMeasurementEntry 6 }
+
+ lgpPwrLineMeasurementCapacity OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "percent"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The percentage of the power capacity presently being used on this
+ line."
+ ::= { lgpPwrLineMeasurementEntry 7 }
+
+ lgpPwrLineMeasurementVA OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Volt-Amp"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present apparent AC line power."
+ ::= { lgpPwrLineMeasurementEntry 8 }
+
+ lgpPwrLineMeasurementTruePower OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Watt"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present AC line power measured in watts."
+ ::= { lgpPwrLineMeasurementEntry 9 }
+
+ lgpPwrLineMeasurementVoltageTHD OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "0.1 Percent"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present total harmonic distortion on the AC line voltage."
+ ::= { lgpPwrLineMeasurementEntry 10 }
+
+ lgpPwrLineMeasurementCurrentTHD OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "0.1 Percent"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present total harmonic distortion on the AC line current."
+ ::= { lgpPwrLineMeasurementEntry 11 }
+
+ lgpPwrLineMeasurementKFactorCurrent OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "0.1 K Factor"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present line K Factor."
+ ::= { lgpPwrLineMeasurementEntry 12 }
+
+ lgpPwrLineMeasurementCrestFactorCurrent OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "0.1 Crest Factor"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present crest factor of the line current."
+ ::= { lgpPwrLineMeasurementEntry 13 }
+
+ lgpPwrLineMeasurementPowerFactor OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "0.01 Power Factor"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present Power Factor for the line."
+ ::= { lgpPwrLineMeasurementEntry 14 }
+
+ lgpPwrLineMeasurementPowerFactorTag OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ leading(1),
+ lagging(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present description of the Power Factor for the line. If
+ Leading, the load is said to be capacitive and the phase of the
+ current leads the voltage. If Lagging, the load is said to be
+ inductive and the phase of the current lags the voltage."
+ ::= { lgpPwrLineMeasurementEntry 15 }
+
+ lgpPwrLineMeasurementMaxVolts OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Volt"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The maximum voltage measurement recorded for the indicated source
+ since the command 'lgpPwrStatisticsReset' was executed."
+ ::= { lgpPwrLineMeasurementEntry 16 }
+
+ lgpPwrLineMeasurementMinVolts OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Volt"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The minimum voltage measurement recorded for the
+ indicated source since the command 'lgpPwrStatisticsReset' was
+ executed."
+ ::= { lgpPwrLineMeasurementEntry 17 }
+
+ lgpPwrLineMeasurementVAR OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Volt-Amp-Reactive"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present reactive AC line power of the power source indicated by
+ 'lgpPwrMeasurementPoint'."
+ ::= { lgpPwrLineMeasurementEntry 18 }
+
+ lgpPwrLineMeasurementPercentLoad OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "percent"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present percent load of the AC line power."
+ ::= { lgpPwrLineMeasurementEntry 19 }
+
+ lgpPwrLineMeasurementVolts OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Volt"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present voltage measurement for the indicated source."
+ ::= { lgpPwrLineMeasurementEntry 20 }
+
+ lgpPwrLineMeasurementVACapacity OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "percent"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The percentage of the apparent power capacity presently being
+ used on this line."
+ ::= { lgpPwrLineMeasurementEntry 21 }
+
+-- -----------------------------------------------------------------------------
+-- DC Power Measurement Point Table
+-- -----------------------------------------------------------------------------
+
+lgpPwrDcMeasurementPointTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF LgpPwrDcMeasurementPointEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "This table contains a list of DC power measurement point entries.
+ The table contains zero, one, or many rows, depending upon the number
+ of power related measurement points available. The NMS cannot
+ create or delete rows from the table. The rows are created by the
+ agent based upon the capabilities of the managed device. Each row
+ in the table represents a series of measurements on a given point
+ or location within the system. Measurement points/locations are
+ identified by the object identifier 'lgpPwrDcMeasurementPointId' in the
+ 'LgpPwrDcMeasurementPointEntry' object. The actual measurement being
+ taken at that identified point is identified by the other
+ corresponding columns in the LgpPwrDcMeasurementPointEntry for the
+ particular row of the table."
+ REFERENCE
+ "The measurement points represented by 'lgpPwrDcMeasurementPointId'
+ can be found in the sub-tree lgpPwrWellKnownMeasurementPoints.
+ Additional measurement detail on a 'per line' basis is available in
+ the lgpPwrLineMeasurementTable"
+ ::= { lgpPwrMeasurements 4 }
+
+ lgpPwrDcMeasurementPointEntry OBJECT-TYPE
+ SYNTAX LgpPwrDcMeasurementPointEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "This entry defines the measurements to be populated in the
+ various columns of the 'lgpPwrDcMeasurementPointTable'."
+ INDEX { lgpPwrDcMeasurementPointIndex }
+ ::= { lgpPwrDcMeasurementPointTable 1 }
+
+ LgpPwrDcMeasurementPointEntry ::= SEQUENCE
+ {
+ lgpPwrDcMeasurementPointIndex Unsigned32,
+ lgpPwrDcMeasurementPointId OBJECT IDENTIFIER,
+ lgpPwrDcMeasurementPointSubID Integer32,
+ lgpPwrDcMeasurementPointVolts Integer32,
+ lgpPwrDcMeasurementPointCurrent Integer32,
+ lgpPwrDcMeasurementPointNomVolts Integer32,
+ lgpPwrDcMeasurementPointTruePower Integer32
+ }
+
+ lgpPwrDcMeasurementPointIndex OBJECT-TYPE
+ SYNTAX Unsigned32
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "This is the index that indicates the row of the
+ 'lgpPwrMeasurementPointTable' for a power measurement point."
+ ::= { lgpPwrDcMeasurementPointEntry 1 }
+
+ lgpPwrDcMeasurementPointId OBJECT-TYPE
+ SYNTAX OBJECT IDENTIFIER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "An OID representing a well known measurement point.
+ These object identifiers indicate a point or location of power
+ measurement in a power system. The OID's name usually
+ implies a location of the measurement point such as
+ 'input', 'output', 'bypass' etc."
+ REFERENCE
+ "The object identifiers in this column can be found in the sub-tree
+ 'lgpPwrWellKnownMeasurementPoints'."
+ ::= { lgpPwrDcMeasurementPointEntry 2 }
+
+ lgpPwrDcMeasurementPointSubID OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Count"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The identifier used to differentiate between identical thresholds
+ for a given point index and point ID in the DC measurements table."
+ ::= { lgpPwrDcMeasurementPointEntry 3 }
+
+ lgpPwrDcMeasurementPointVolts OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Volt"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present DC voltage for the power source indicated by
+ 'lgpPwrDcMeasurementPointId' in the corresponding row in the
+ lgpPwrDcMeasurementPointTable."
+ ::= { lgpPwrDcMeasurementPointEntry 4 }
+
+ lgpPwrDcMeasurementPointCurrent OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Amp"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present DC current for the power source indicated by
+ 'lgpPwrDcMeasurementPointId' in the corresponding row in the
+ lgpPwrDcMeasurementPointTable."
+ ::= { lgpPwrDcMeasurementPointEntry 5 }
+
+ lgpPwrDcMeasurementPointNomVolts OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Volt"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The nominal(configured/expected) DC voltage for the power source
+ indicated by 'lgpPwrDcMeasurementPointId' in the
+ corresponding row in the lgpPwrDcMeasurementPointTable."
+ ::= { lgpPwrDcMeasurementPointEntry 6 }
+
+ lgpPwrDcMeasurementPointTruePower OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Watt"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present DC power for the power source indicated by
+ 'lgpPwrDcMeasurementPointId' in the corresponding row in the
+ lgpPwrDcMeasurementPointTable."
+ ::= { lgpPwrDcMeasurementPointEntry 7 }
+
+-- -----------------------------------------------------------------------------
+-- Well Known Power Measurement Types
+-- -----------------------------------------------------------------------------
+
+lgpPwrWellKnownMeasurementTypes OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This sub-tree registers well known Liebert Power Measurement
+ Types. The object identifier names usually encompass units of
+ measure, lines of reference, and device location. The OID's
+ name usually implies a measurement type such as 'voltsAC',
+ 'current', 'voltsDc', 'VoltsLL', etc."
+ ::= { lgpPwrMeasurements 5 }
+
+ lgpPwrVoltsAc OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This identifier represents an AC voltage."
+ ::= { lgpPwrWellKnownMeasurementTypes 1 }
+
+ lgpPwrVoltsDc OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This identifier represents a DC voltage."
+ ::= { lgpPwrWellKnownMeasurementTypes 2 }
+
+ lgpPwrAmpsNeutral OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This identifier represents a current measurement in Amps on the
+ neutral line."
+ ::= { lgpPwrWellKnownMeasurementTypes 3 }
+
+-- -----------------------------------------------------------------------------
+-- lgpPwrControl - Liebert Control Group
+-- -----------------------------------------------------------------------------
+
+lgpPwrWellKnownControlPoints OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This sub-tree registers well known Liebert Power Control
+ Points. The object identifier names usually imply locations
+ where control of a device is available -- such 'output' or
+ 'load circuits'."
+ REFERENCE
+ "These well known control identifiers are referenced in the
+ 'lgpPwrLoadCircuitId' column in the
+ 'lgpPwrLoadCircuitTable'."
+ ::= { lgpPwrControl 1 }
+
+ lgpPwrLoadCircuit OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The managed device's controllable load circuit.
+ Many power systems contain more than one load circuit.
+ This identifier represents one load circuit for the
+ system but does not necessarily represent the 'first' one.
+ The load circuits' numbering with respect to
+ 'lgpPwrLoadCircuit1' etc. may depend on the physical wiring
+ of the system when it was installed."
+ ::= { lgpPwrWellKnownControlPoints 1 }
+
+-- -----------------------------------------------------------------------------
+-- Load Circuit Table
+-- -----------------------------------------------------------------------------
+lgpPwrLoadCircuitTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF LgpPwrLoadCircuitEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A list of load circuits that can be controlled(opened or closed).
+ The NMS cannot create or delete rows from the table.
+ The rows are created by the agent based upon the capabilities of
+ the managed device."
+ ::= { lgpPwrControl 2 }
+
+ lgpPwrLoadCircuitEntry OBJECT-TYPE
+ SYNTAX LgpPwrLoadCircuitEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "This entry defines the contents of the columns for the table
+ 'lgpPwrLoadCircuitTable'."
+ INDEX { lgpPwrLoadCircuitIndex }
+ ::= { lgpPwrLoadCircuitTable 1 }
+
+ LgpPwrLoadCircuitEntry ::= SEQUENCE
+ {
+ lgpPwrLoadCircuitIndex Unsigned32,
+ lgpPwrLoadCircuitId OBJECT IDENTIFIER,
+ lgpPwrLoadCircuitSubID Unsigned32,
+ lgpPwrLoadCircuitState INTEGER,
+ lgpPwrLoadCircuitStateAndControl INTEGER
+
+ }
+
+ lgpPwrLoadCircuitIndex OBJECT-TYPE
+ SYNTAX Unsigned32
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "This is the index indicating the row of the table
+ 'lgpPwrLoadCircuitTable'."
+ ::= { lgpPwrLoadCircuitEntry 1 }
+
+ lgpPwrLoadCircuitId OBJECT-TYPE
+ SYNTAX OBJECT IDENTIFIER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "An OID representing a well known load circuit identifier.
+ These load circuit identifiers indicate the name or type of load
+ circuit reference in the table."
+ REFERENCE
+ "The object identifiers in this column can be found in the sub-tree
+ 'lgpPwrWellKnownMeasurementPoints'."
+ ::= { lgpPwrLoadCircuitEntry 2 }
+
+ lgpPwrLoadCircuitSubID OBJECT-TYPE
+ SYNTAX Unsigned32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "This is a sub identifier for the 'lgpPwrLoadCircuitId'.
+ It indicates the hardware identifier of the load control circuit."
+ ::= { lgpPwrLoadCircuitEntry 3 }
+
+ lgpPwrLoadCircuitState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ on(1),
+ off(2),
+ default(3)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "This identifier indicates the state of the load circuit.
+ When read, only a closed or open response will be returned.
+ When written to, the state of the circuit will transition to
+ desired state."
+ ::= { lgpPwrLoadCircuitEntry 4 }
+
+ lgpPwrLoadCircuitStateAndControl OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ off(0),
+ on(1),
+ reboot(2)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "This identifier indicates the state of the load circuit.
+ When read, only a closed or open response will be returned.
+ When written to, the state of the circuit will transition to
+ desired state."
+ ::= { lgpPwrLoadCircuitEntry 5 }
+
+lgpPwrAlarmSilence OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Audible Alarm Silence Command. This command turns off the device's
+ audible alarm. It will not affect the status of the alarm(s) that
+ caused the audible alarm. This command should be sent with a
+ parameter of 1. This variable doesn't return a value when read."
+ ::= { lgpPwrControl 3 }
+
+lgpPwrBatteryTest OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ start(1),
+ abort(2)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Battery Test Command. This command will initiate a battery test if
+ one is not already in progress, or abort the current test if it is in
+ progress."
+ ::= { lgpPwrControl 4 }
+
+lgpPwrUpsAbortCommand OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "UPS Abort command. This command will abort the pending command on the
+ device. There is no guarantee a client using the abort command will
+ cancel a command sent moments before from the same client.
+ Another client could initiate a command and change what command is
+ actually pending on the device. This command should be sent with a
+ parameter of 1. This variable doesn't return a value when read."
+ ::= { lgpPwrControl 5 }
+
+lgpPwrTransferToBypass OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Transfer to Bypass Command. This command will initiate a transfer of
+ the load to the bypass of the system. This command should be sent with a
+ parameter of 1. This variable doesn't return a value when read."
+ ::= { lgpPwrControl 6 }
+
+lgpPwrTransferToInverter OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Transfer to Inverter Command. This command will initiate a transfer
+ of the load to the inverter of the system. This command should be sent
+ with a parameter of 1. This variable doesn't return a value when read."
+ ::= { lgpPwrControl 7 }
+
+lgpPwrOutputOnDelay OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "seconds"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Output On Delay Command. This command will turn on the output of the
+ device after a user specified delay. The number of seconds to delay
+ is subject to the precision of the device and should be kept to 10
+ second intervals."
+ ::= { lgpPwrControl 8 }
+
+lgpPwrOutputOffDelayWithRestart OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "seconds"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Output Off Delay with Restart Command. This command will turn off the
+ output of the device after a user specified delay. The number
+ of seconds to delay is subject to the precision of the device and
+ should be kept to 10 second intervals. The device will then
+ turn the output on again after a specified amount of time. "
+ ::= { lgpPwrControl 9 }
+
+lgpPwrOutputOffDelayWithoutRestart OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "seconds"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Output Off Delay without Restart Command. This command will turn off
+ the output of the device after a specified delay. The number of seconds
+ to delay is subject to the precision of the device and should be kept
+ to 10 second intervals. The device will NOT automatically turn the
+ output on following this command."
+ ::= { lgpPwrControl 10 }
+
+-- =============================================================================
+-- lgpPwrStatus - Liebert Power Status Group
+-- =============================================================================
+
+lgpPwrTransferCount OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Count"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Number of times that the output load has been transferred between the
+ available input sources."
+ ::= { lgpPwrStatus 1 }
+
+lgpPwrAutoTransferTimer OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "seconds"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The required wait time between output load auto transfer attempts
+ between available input sources."
+ ::= { lgpPwrStatus 2 }
+
+lgpPwrAutoReTransferEnabled OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ no (0),
+ yes (1)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The ability to retransfer the output load automatically to the well
+ known measurement source from the 'lgpPwrWellKnownMeasurements'
+ sub-tree that is the preferred input source of the system"
+ ::= { lgpPwrStatus 3 }
+
+lgpPwrSyncPhaseAngle OBJECT-TYPE
+ SYNTAX Integer32(-3600..3600)
+ UNITS "0.1 Degrees"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The phase angle difference of source 1 in relation to source 2."
+ ::= { lgpPwrStatus 4 }
+
+lgpPwrParallelSystemOutputToLoadSource OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ unknown (0),
+ utility (1),
+ battery (2),
+ bypass (3),
+ none (4)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The source supporting the parallel system's load."
+ ::= { lgpPwrStatus 5 }
+
+lgpPwrDcToDcConverter OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ on(1),
+ off(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The state of the DC to DC converter."
+ ::= { lgpPwrStatus 6 }
+
+lgpPwrOutputToLoadOnInverter OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ yes(1),
+ no(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present source of output power is the Inverter."
+ ::= { lgpPwrStatus 7 }
+
+lgpPwrBatteryChargeCompensating OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ yes(1),
+ no(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The system is adjusting the battery charging algorithm to accommodate
+ for the battery temperature."
+ ::= { lgpPwrStatus 8 }
+
+lgpPwrInverterReady OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ yes(1),
+ no(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The ability of the inverter to support the output load of the system."
+ ::= { lgpPwrStatus 9 }
+
+lgpPwrOutputToLoadOnBypass OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ yes(1),
+ no(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present source of output power is the Bypass."
+ ::= { lgpPwrStatus 10 }
+
+lgpPwrBoost OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ on(1),
+ off(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present state of the boost circuitry"
+ ::= { lgpPwrStatus 11 }
+
+lgpPwrBuck OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ on(1),
+ off(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present state of the buck circuitry"
+ ::= { lgpPwrStatus 12 }
+
+lgpPwrShutdownOverTemperature OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ yes(1),
+ no(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The system has previously shutdown due to an over temperature
+ condition."
+ ::= { lgpPwrStatus 13 }
+
+lgpPwrShutdownOverload OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ yes(1),
+ no(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The system has previously shutdown due to an over load condition."
+ ::= { lgpPwrStatus 14 }
+
+lgpPwrShutdownDcBusOverload OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ yes(1),
+ no(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The system has previously shutdown due to a DC bus over load
+ condition."
+ ::= { lgpPwrStatus 15 }
+
+lgpPwrShutdownOutputShort OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ yes(1),
+ no(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The system has previously shutdown due to an output short condition."
+ ::= { lgpPwrStatus 16 }
+
+lgpPwrShutdownLineSwap OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ yes(1),
+ no(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The system has previously shutdown due to a condition where the line
+ and neutral were reversed."
+ ::= { lgpPwrStatus 17 }
+
+lgpPwrShutdownLowBattery OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ yes(1),
+ no(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The system has previously shutdown due to a low battery condition."
+ ::= { lgpPwrStatus 18 }
+
+lgpPwrShutdownRemote OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ yes(1),
+ no(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The system has previously shutdown due to a remote shutdown command."
+ ::= { lgpPwrStatus 19 }
+
+lgpPwrShutdownInputUnderVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ yes(1),
+ no(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The system has previously shutdown due to an under voltage condition
+ during startup."
+ ::= { lgpPwrStatus 20 }
+
+lgpPwrShutdownPowerFactorCorrectionFailure OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ yes(1),
+ no(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The system has previously shutdown due to a power factor correction
+ startup failure."
+ ::= { lgpPwrStatus 21 }
+
+lgpPwrShutdownHardware OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ yes(1),
+ no(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The system has previously shutdown due external shutdown signal."
+ ::= { lgpPwrStatus 22 }
+
+lgpPwrRedundantSubModule OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ yes(1),
+ no(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The system has a redundant battery module installed."
+ ::= { lgpPwrStatus 23 }
+
+lgpPwrBypassReady OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ yes(1),
+ no(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The ability of the bypass to support the output load of the system.
+ If Yes, the bypass is available to transfer to."
+ ::= { lgpPwrStatus 24 }
+
+lgpPwrGeneratorStatus OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ connected(1),
+ disconnected(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The state of the system generator."
+ ::= { lgpPwrStatus 25 }
+
+lgpPwrRotaryBreakerStatus OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ unknown(1),
+ closed(2),
+ test(3),
+ normal(4),
+ bypass(5),
+ maintenance(6)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The state of the system rotary breaker."
+ ::= { lgpPwrStatus 26 }
+
+lgpPwrPowerFactorCorrection OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ on(1),
+ off(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The state of the power factor correction circuitry of the system."
+ ::= { lgpPwrStatus 27 }
+
+lgpPwrBypassSyncDiff OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "0.1 Degrees"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The phase angle difference between the inverter output and bypass
+ source. A positive value means the inverter leads the bypass source.
+ A negative value means the inverter lags the bypass source."
+ ::= { lgpPwrStatus 28 }
+
+lgpPwrBypassOverloadShutdownTime OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "seconds"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The calculated time remaining before bypass static switch shutdown due
+ to the present overload condition. If the bypass is not in an overload
+ condition, this object returns -1."
+ ::= { lgpPwrStatus 29 }
+
+lgpPwrInverterOverloadShutdownTime OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "seconds"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The calculated time remaining before inverter shutdown. The calculated
+ time of inverter operation remaining for the present overload event.
+
+ Note: If the inverter is not experiencing an overload event this point
+ will return 65535 indicating this value is unavailable."
+ ::= { lgpPwrStatus 30 }
+
+lgpPwrStateOutputSource OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ none(1),
+ inverter(2),
+ bypass(3),
+ maintenanceBypass(4)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The UPS's output power source (inverter, bypass, or none).
+ NOTE: It is possible that the load still has power from the
+ Maintenance Bypass."
+ ::= { lgpPwrStatus 31 }
+
+lgpPwrStateInputSource OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ none(1),
+ utility(2),
+ generator(3)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The system input power source (none, utility, generator)."
+ ::= { lgpPwrStatus 32 }
+
+lgpPwrStateInputQualification OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ fail(1),
+ marginalLow(2),
+ normal(3),
+ marginalHigh(4)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The current state of the system input. The unit may or may not operate
+ normally under 'marginalLow' and 'marginalHigh' states."
+ ::= { lgpPwrStatus 33 }
+
+lgpPwrStateBypassStaticSwitchState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ on(1),
+ off(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The current state of the bypass static switch."
+ ::= { lgpPwrStatus 34 }
+
+lgpPwrStateBypassQualification OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ fail(1),
+ marginalLow(2),
+ normal(3),
+ marginalHigh(4)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The current operational state of the bypass static switch. The unit may
+ or may not operate normally under 'marginalLow' and 'marginalHigh'
+ states."
+ ::= { lgpPwrStatus 35 }
+
+lgpPwrStateDCBusQualification OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ fail(1),
+ marginalLow(2),
+ normal(3),
+ marginalHigh(4)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The current operational state of the DC bus. The unit may or may not
+ operate normally under 'marginalLow' and 'marginalHigh' states."
+ ::= { lgpPwrStatus 36 }
+
+lgpPwrStateOutQualification OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ fail(1),
+ marginalLow(2),
+ normal(3),
+ marginalHigh(4)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The current operational state of the output. The unit may or may not
+ operate normally under 'marginalLow' and 'marginalHigh' states."
+ ::= { lgpPwrStatus 37 }
+
+lgpPwrStateInverterQualification OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ fail(1),
+ marginalLow(2),
+ normal(3),
+ marginalHigh(4)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The current operational state of the inverter. The unit may or may not
+ operate normally under 'marginalLow' and 'marginalHigh' states."
+ ::= { lgpPwrStatus 38 }
+
+lgpPwrStateInverterState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ on(1),
+ off(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The current state of the inverter."
+ ::= { lgpPwrStatus 39 }
+
+lgpPwrStateRectifierState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ on(1),
+ off(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The current state of the rectifier."
+ ::= { lgpPwrStatus 40 }
+
+lgpPwrStateModuleGroup OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This group contains UPS module information."
+ ::= { lgpPwrStatus 41 }
+
+ lgpPwrStateUpsModuleCount OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Count"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Number of UPS modules in the system. In a single module system, this
+ value is one."
+ ::= { lgpPwrStateModuleGroup 1 }
+
+ lgpPwrStateUpsModuleRedundantCount OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Count"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Number of redundant UPS modules in the system. In a single module
+ system, the value is zero. This value is dependent upon the present
+ load and the number of modules (i.e. the value may change during normal
+ operation based upon a load change). This value represents the number
+ of extra modules above the minimum needed to support the load."
+ ::= { lgpPwrStateModuleGroup 2 }
+
+lgpPwrStateBackfeedBrkrState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ open(1),
+ closed(2),
+ notInstalled(3)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The state of the Static Bypass Switch Line Disconnect Breaker."
+ ::= { lgpPwrStatus 42 }
+
+lgpPwrStateLoadDisconnectState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ open(1),
+ closed(2),
+ notInstalled(3)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The state of the Static Bypass Switch Load Disconnect Breaker."
+ ::= { lgpPwrStatus 43 }
+
+lgpPwrStateInputBrkrState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ open(1),
+ closed(2),
+ notInstalled(3)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The state of the Input Disconnect Breaker."
+ ::= { lgpPwrStatus 44 }
+
+lgpPwrStateTrapFilterBrkrState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ open(1),
+ closed(2),
+ notInstalled(3)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The state of the Trap Filter Disconnect Breaker."
+ ::= { lgpPwrStatus 45 }
+
+lgpPwrStateInvOutputBrkrState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ open(1),
+ closed(2),
+ notInstalled(3)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The state of the Inverter Output Disconnect Breaker."
+ ::= { lgpPwrStatus 46 }
+
+lgpPwrStateIntBypassBrkrState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ open(1),
+ closed(2),
+ notInstalled(3)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The state of the Internal Bypass Breaker."
+ ::= { lgpPwrStatus 47 }
+
+lgpPwrStateBypassIsolBrkrState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ open(1),
+ closed(2),
+ notInstalled(3)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The state of the Bypass Isolation Breaker."
+ ::= { lgpPwrStatus 48 }
+
+lgpPwrStateRectifierIsolBrkrState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ open(1),
+ closed(2),
+ notInstalled(3)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The state of the Rectifier Isolation Breaker."
+ ::= { lgpPwrStatus 49 }
+
+lgpPwrStateMaintBypassBrkrState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ open(1),
+ closed(2),
+ notInstalled(3)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The state of the Maintenance Bypass Breaker."
+ ::= { lgpPwrStatus 50 }
+
+lgpPwrStateMaintIsolBrkrState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ open(1),
+ closed(2),
+ notInstalled(3)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The state of the Maintenance Isolation Breaker."
+ ::= { lgpPwrStatus 51 }
+
+lgpPwrStateOutStaticSwState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ off(1),
+ on(2),
+ notInstalled(3)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The state of the Output Series Static Switch."
+ ::= { lgpPwrStatus 52 }
+
+lgpPwrStateModuleOutBrkrState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ open(1),
+ closed(2),
+ notInstalled(3)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The state of the Module Output Breaker."
+ ::= { lgpPwrStatus 53 }
+
+lgpPwrBypassReXfrRemainTime OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "seconds"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The time remaining before an inverter overload or inverter fault can
+ be cleared and auto retransfer from the bypass to the inverter can take
+ place.
+
+ Note: If an inverter overload or fault is not taking place, this point
+ will return 65535."
+ ::= { lgpPwrStatus 54 }
+
+lgpPwrStateUpsOutputSource OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ other(1),
+ none(2),
+ normal(3),
+ bypass(4),
+ battery(5),
+ booster(6),
+ reducer(7)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present source of output power. The enumeration
+ none(2) indicates that there is no source of output
+ power (and therefore no output power), for example,
+ the system has opened the output breaker.
+
+ NOTE: In a single-module system, this point is intended to have the same
+ behavior as the RFC1628 point upsOutputSource."
+ ::= { lgpPwrStatus 55 }
+
+lgpPwrStateLoadBusSynchronization OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ unknown(0),
+ active(1),
+ abnormal(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The state of the Load Bus Synchronizer (LBS)."
+ ::= { lgpPwrStatus 56 }
+
+lgpPwrStateCircuitBrkrStateGroup OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This group contains Static Switch circuit breaker state information."
+ ::= { lgpPwrStatus 57 }
+
+ lgpPwrStateSource1InputBrkrState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ open(1),
+ closed(2),
+ notInstalled(3)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The states of Source 1 Input Breaker."
+ ::= { lgpPwrStateCircuitBrkrStateGroup 1 }
+
+ lgpPwrStateSource2InputBrkrState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ open(1),
+ closed(2),
+ notInstalled(3)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The states of Source 2 Input Breaker."
+ ::= { lgpPwrStateCircuitBrkrStateGroup 2 }
+
+ lgpPwrStateSource1BypassBrkrState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ open(1),
+ closed(2),
+ notInstalled(3)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The states of Source 1 Bypass Breaker."
+ ::= { lgpPwrStateCircuitBrkrStateGroup 3 }
+
+ lgpPwrStateSource2BypassBrkrState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ open(1),
+ closed(2),
+ notInstalled(3)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The states of Source 2 Bypass Breaker."
+ ::= { lgpPwrStateCircuitBrkrStateGroup 4 }
+
+ lgpPwrStateOutputBrkrState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ open(1),
+ closed(2),
+ notInstalled(3)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The states of Output Breaker."
+ ::= { lgpPwrStateCircuitBrkrStateGroup 5 }
+
+ lgpPwrStateAuxOutputBrkrState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ open(1),
+ closed(2),
+ notInstalled(3)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The states of Auxiliary Output Breaker."
+ ::= { lgpPwrStateCircuitBrkrStateGroup 6 }
+
+ lgpPwrStateSource1PduInputBrkrState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ open(1),
+ closed(2),
+ notInstalled(3)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The states of Source 1 PDU Input Breaker."
+ ::= { lgpPwrStateCircuitBrkrStateGroup 7 }
+
+ lgpPwrStateSource2PduInputBrkrState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ open(1),
+ closed(2),
+ notInstalled(3)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The states of Source 2 PDU Input Breaker."
+ ::= { lgpPwrStateCircuitBrkrStateGroup 8 }
+
+lgpPwrEconomicOperation OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ off(0),
+ on(1)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present state of ECO mode operation,
+ on(1) if system is on bypass due to ECO mode operation,
+ off(0) any other time."
+ ::= { lgpPwrStatus 58 }
+
+-- =============================================================================
+-- lgpPwrSettings - Liebert Power Settings Group
+-- =============================================================================
+
+lgpPwrPreferredSource OBJECT-TYPE
+ SYNTAX OBJECT IDENTIFIER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The well known measurement source from the
+ 'lgpPwrWellKnownMeasurements' sub-tree that is the preferred
+ input source of the system."
+ ::= { lgpPwrSettings 1 }
+
+lgpPwrLoadOnSource OBJECT-TYPE
+ SYNTAX OBJECT IDENTIFIER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The well known measurement source from the
+ 'lgpPwrWellKnownMeasurements' sub-tree that is currently
+ powering the output (load)."
+ ::= { lgpPwrSettings 2 }
+
+lgpPwrNominalVoltageDeviation OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Volt"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The nominal voltage deviation between the well known
+ measurement source lgpPwrSource1Input and lgpPwrSource2Input."
+ ::= { lgpPwrSettings 3 }
+
+lgpPwrNominalVoltageDeviationPercent OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "percent"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The percentage of the nominal voltage deviation between the well known
+ measurement source lgpPwrSource1Input and lgpPwrSource2Input."
+ ::= { lgpPwrSettings 4 }
+
+lgpPwrPhaseDifferenceLimit OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "0.1 Degrees"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The maximum phase difference (between the well known
+ input sources ) in which a transfer to an available input source is
+ permitted."
+ ::= { lgpPwrSettings 5 }
+
+lgpPwrFrequencyDeviationLimit OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "0.1 Hertz"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The maximum frequency deviation (between the well known
+ input sources ) in which a transfer to an available input source is
+ permitted."
+ ::= { lgpPwrSettings 6 }
+
+-- -----------------------------------------------------------------------------
+-- Thresholds Table
+-- -----------------------------------------------------------------------------
+
+lgpPwrThresholdTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF LgpPwrThresholdEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A list of power thresholds for a given power measurement at a
+ point/location in the system.
+ The lgpPwrThresholdType in this table corresponds to the
+ type of measurement the high and low thresholds applies to.
+
+ This table contains zero, one, or many rows, depending upon the number
+ of 'lgpPwrThresholdPoint' and 'lgpPwrThresholdSubID' available in the
+ table.
+ The NMS cannot create or delete rows from the table.
+ The rows are created by the agent based upon the capabilities of
+ the managed device."
+ ::= { lgpPwrSettings 7 }
+
+ lgpPwrThresholdEntry OBJECT-TYPE
+ SYNTAX LgpPwrThresholdEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "This entry defines the contents of the columns for the table
+ 'lgpPwrThresholdTable'."
+ REFERENCE
+ "The lgpPwrThresholdType in this table corresponds to the
+ type of measurement the high and low thresholds applies to."
+ INDEX { lgpPwrThresholdIndex }
+ ::= { lgpPwrThresholdTable 1 }
+
+ LgpPwrThresholdEntry ::= SEQUENCE
+ {
+ lgpPwrThresholdIndex Unsigned32,
+ lgpPwrThresholdPoint OBJECT IDENTIFIER,
+ lgpPwrThresholdSubID Unsigned32,
+ lgpPwrThresholdType OBJECT IDENTIFIER,
+ lgpPwrThresholdHighWarning Integer32,
+ lgpPwrThresholdHighFailure Integer32,
+ lgpPwrThresholdLowWarning Integer32,
+ lgpPwrThresholdLowFailure Integer32
+ }
+
+ lgpPwrThresholdIndex OBJECT-TYPE
+ SYNTAX Unsigned32
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "This is the index indicating the row of the table
+ 'lgpPwrLineMeasurementTable' for a power measurement point."
+ ::= { lgpPwrThresholdEntry 1 }
+
+ lgpPwrThresholdPoint OBJECT-TYPE
+ SYNTAX OBJECT IDENTIFIER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "An OID representing a well known measurement point.
+ These object identifiers indicate a point or location of power
+ measurement in a power system. The OID's name usually
+ implies a location of the measurement point such as
+ 'input', 'output', 'bypass' etc."
+ REFERENCE
+ "The object identifiers in this column can be found in the sub-tree
+ 'lgpPwrWellKnownMeasurementPoints' and correspond to the
+ entry in the table 'lgpPwrThresholdTable'."
+ ::= { lgpPwrThresholdEntry 2 }
+
+ lgpPwrThresholdSubID OBJECT-TYPE
+ SYNTAX Unsigned32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "This is a sub identifier for the 'lgpPwrThresholdPoint'.
+ It indicates the instance number of the well known threshold point."
+ ::= { lgpPwrThresholdEntry 3 }
+
+ lgpPwrThresholdType OBJECT-TYPE
+ SYNTAX OBJECT IDENTIFIER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "An OID representing a well known measurement type.
+ These object identifiers indicate the type of measurement referenced
+ by the row of the table. These object identifiers can encompass
+ units of measure, lines of reference, and device location.
+ The OID's name usually implies a measurement type such as
+ 'voltsAc', 'current', 'voltsDc', 'VoltsLL', etc."
+ REFERENCE
+ "The object identifiers in this column can be found in the sub-tree
+ 'lgpPwrWellKnownThresholdTypes' and correspond to the
+ entry in the table lgpPwrThresholdTable."
+ ::= { lgpPwrThresholdEntry 4 }
+
+ lgpPwrThresholdHighWarning OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The high warning threshold of a type of measurement designated by
+ the 'lgpPwrThresholdType' at a location designated by the
+ 'lgpPwrThresholdPoint'. If multiple thresholds are available at a
+ single 'lgpPwrThresholdPoint', of the same 'lgpPwrThresholdType',
+ then the 'lgpPwrThresholdSubID' will differentiate between them.
+ When this threshold is met, the agent will send a notification."
+ ::= { lgpPwrThresholdEntry 5 }
+
+ lgpPwrThresholdHighFailure OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The high failure threshold of a type of measurement designated by
+ the 'lgpPwrThresholdType' at a location designated by the
+ 'lgpPwrThresholdPoint'. If multiple thresholds are available at a
+ single 'lgpPwrThresholdPoint', of the same 'lgpPwrThresholdType',
+ then the 'lgpPwrThresholdSubID' will differentiate between them.
+ When this threshold is met, the agent will send a notification."
+ ::= { lgpPwrThresholdEntry 6 }
+
+ lgpPwrThresholdLowWarning OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The low warning threshold of a type of measurement designated by
+ the 'lgpPwrThresholdType' at a location designated by the
+ 'lgpPwrThresholdPoint'. If multiple thresholds are available at a
+ single 'lgpPwrThresholdPoint', of the same 'lgpPwrThresholdType',
+ then the 'lgpPwrThresholdSubID' will differentiate between them.
+ When this threshold is met, the agent will send a notification."
+ ::= { lgpPwrThresholdEntry 7 }
+
+ lgpPwrThresholdLowFailure OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The low failure threshold of a type of measurement designated by
+ the 'lgpPwrThresholdType' at a location designated by the
+ 'lgpPwrThresholdPoint'. If multiple thresholds are available at a
+ single 'lgpPwrThresholdPoint', of the same 'lgpPwrThresholdType',
+ then the 'lgpPwrThresholdSubID' will differentiate between them.
+ When this threshold is met, the agent will send a notification."
+ ::= { lgpPwrThresholdEntry 8 }
+
+lgpPwrUpsAutoRestart OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ on(1),
+ off(2)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The device will automatically restart when utility power is restored
+ following a battery discharge."
+ ::= { lgpPwrSettings 8 }
+
+lgpPwrUpsAutoRestartDelay OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "seconds"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The device will automatically delay a certain number of seconds and
+ then restart after utility power is restored following a battery
+ discharge. The number of seconds to delay is subject to the precision
+ of the device and should be kept to 10 second intervals."
+ ::= { lgpPwrSettings 9 }
+
+lgpPwrAutoRestartBatteryChargeThreshold OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "percent"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The battery charge percentage required before the device can
+ automatically restart."
+ ::= { lgpPwrSettings 10 }
+
+lgpPwrParallelModuleCount OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Count"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The number of modules in the parallel system."
+ ::= { lgpPwrSettings 11 }
+
+lgpPwrParallelRedundancyCount OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Count"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The number of redundant modules in the parallel system."
+ ::= { lgpPwrSettings 12 }
+
+lgpPwrLoadBusSyncMode OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ master(1),
+ slave(2),
+ none(3)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The configuration of Load Bus Synchronization (LBS) between
+ independent systems."
+ ::= { lgpPwrSettings 13 }
+
+lgpPwrEconomicOperationMode OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ on(1),
+ off(2)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The configuration of the economic operation mode of the system."
+ ::= { lgpPwrSettings 14 }
+
+lgpPwrAutomaticBatteryTest OBJECT-TYPE
+ SYNTAX INTEGER {
+ on(1),
+ off(2)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Automatic battery test option. If enabled, the battery will be tested
+ on a fixed interval. If disabled, the battery test must be initiated
+ by a battery test command. The interval at which a battery test is
+ performed is defined by 'lgpPwrAutomaticBatteryTestInterval'."
+ ::= { lgpPwrSettings 15 }
+
+lgpPwrMinimumRedundantPowerModule OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Count"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The minimum number of redundant power modules that must be present
+ before sending a loss of power redundancy alarm. If 0, there is no
+ redundant power functionality."
+ ::= { lgpPwrSettings 16 }
+
+lgpPwrMinimumRedundantBatteryModule OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Count"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The minimum number of redundant battery modules that must be present
+ before sending an alarm. If 0, the redundant battery module alarm is
+ disabled."
+ ::= { lgpPwrSettings 17 }
+
+lgpPwrOutputToLoadUserOverloadLimit OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Volt-Amp"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "This is the user specified maximum load the device can support
+ without sending an alarm."
+ ::= { lgpPwrSettings 18 }
+
+lgpPwrNoLoadWarningLimit OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Amp"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The minimum current draw on the output in which the device considers
+ there to be a load present on the output. The condition
+ lgpConditionWarningNoLoadDetected will be triggered if the output
+ current falls below this value. If this value is '-1' then the
+ lgpConditionNoLoadDetectedWarning condition is 'disabled'."
+ ::= { lgpPwrSettings 19 }
+
+lgpPwrNoLoadWarningDelay OBJECT-TYPE
+ SYNTAX Integer32(0..10000)
+ UNITS "minutes"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The amount of time to delay before annunciation of the condition
+ lgpConditionNoLoadDetectedWarning after the output current load
+ falls below the threshold lgpPwrOutputNoLoadWarningLimit."
+ ::= { lgpPwrSettings 20 }
+
+lgpPwrEconomicOperationModeControl OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ disabled(0),
+ mode1(1),
+ mode2(2)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The configuration of the economic operation mode of the system.
+ Note that this supersedes lgpPwrEconomicOperationMode in newer devices."
+ ::= { lgpPwrSettings 21 }
+
+-- =============================================================================
+-- lgpPwrStatistic - Liebert Power Statistic Group
+-- =============================================================================
+lgpPwrBrownOutCount OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Count"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of occurrences where the input line voltage has fallen below
+ a pre-determined threshold for a specified amount of time. This number
+ resets when the command 'lgpPwrStatisticsReset' is executed."
+ ::= { lgpPwrStatistic 1 }
+
+lgpPwrBlackOutCount OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Count"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of occurrences where there is a total loss of electric power.
+ This number resets when the command 'lgpPwrStatisticsReset' is
+ executed."
+ ::= { lgpPwrStatistic 2 }
+
+lgpPwrTransientCount OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Count"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of occurrences where the input line voltage spikes above a
+ pre-determined threshold for a specified amount of time. This number
+ resets when the command 'lgpPwrStatisticsReset' is executed."
+ ::= { lgpPwrStatistic 3 }
+
+lgpPwrBatteryDischargeCount OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Count"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of battery discharges since the last reset."
+ ::= { lgpPwrStatistic 4 }
+
+lgpPwrBatteryDischargeTime OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "minutes"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The total accumulated time spent on battery since the last reset."
+ ::= { lgpPwrStatistic 5 }
+
+lgpPwrBatteryAmpHours OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Amp-hour"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The total accumulated Amp-hours removed from the battery since last
+ reset."
+ ::= { lgpPwrStatistic 6 }
+
+lgpPwrBatteryWattHours OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Watt-Hour"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The total accumulated Watt-Hours removed from the battery since last
+ reset. This command should be sent with a parameter of 1. This
+ variable doesn't return a value when read."
+ ::= { lgpPwrStatistic 7 }
+
+lgpPwrBatteryStatisticsReset OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Battery statistics clear command. The command to reset all battery
+ statistics stored by the device. This command should be sent with a
+ parameter of 1. This variable doesn't return a value when read."
+ ::= { lgpPwrStatistic 8 }
+
+lgpPwrStatisticsReset OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Reset Power Statistics Command. This command will reset the power
+ statistics stored in the system. This command should be sent with a
+ parameter of 1. This variable doesn't return a value when read."
+ ::= { lgpPwrStatistic 9 }
+
+-- =============================================================================
+-- lgpPwrConversion - Liebert Power Conversion Group
+-- =============================================================================
+
+lgpPwrNumberInstalledPowerModules OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Count"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of power modules installed in the device."
+ ::= { lgpPwrConversion 1 }
+
+lgpPwrNumberFailedPowerModules OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Count"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of power modules in the device that have failed."
+ ::= { lgpPwrConversion 2 }
+
+lgpPwrNumberRedundantPowerModules OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Count"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of redundant power modules installed in the device."
+ ::= { lgpPwrConversion 3 }
+
+lgpPwrNumberActivePowerModules OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Count"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of active power modules in the device."
+ ::= { lgpPwrConversion 4 }
+
+lgpPwrNumberPowerModuleWarnings OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Count"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of power modules in the device that have a warning."
+ ::= { lgpPwrConversion 6 }
+
+lgpPwrUpsInverterStandby OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ on(1),
+ off(2)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The output to the load is supported by the bypass and the inverter is
+ on standby."
+ ::= { lgpPwrConversion 7 }
+
+-- =============================================================================
+-- lgpPwrTopology - Liebert Power Topology Group
+-- =============================================================================
+
+lgpPwrUpsTopOffline OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ yes(1),
+ no(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The UPS has an offline topology. Under normal operating conditions,
+ AC power from the utility passes straight through the UPS
+ to the critical load. The inverter is used to convert the DC power
+ from the battery to create AC power to support the load when the
+ utility fails. Normally the inverter is operating in the stand-by mode,
+ keeping the batteries charged. Should the utility power go out of
+ specification, the inverter will power the load by drawing energy from
+ the battery."
+ ::= { lgpPwrTopology 1 }
+
+lgpPwrUpsTopLineInteractive OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ yes(1),
+ no(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The UPS has a line-interactive topology. This topology
+ resembles the offline product, but inserts a transformer or inductor
+ in series between the utility power source and the load. This inline
+ inductor enables the UPS inverter to interact with incoming power
+ and provide a measure of power conditioning to the load. This
+ buck-and-boost circuitry helps with high and low input voltage
+ conditions."
+ ::= { lgpPwrTopology 2 }
+
+lgpPwrUPSTopDualInput OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ yes(1),
+ no(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The system has separate input sources for the bypass and inverter."
+ ::= { lgpPwrTopology 3 }
+
+lgpPwrTopFrequencyConverter OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ yes(1),
+ no(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The system has a frequency converter."
+ ::= { lgpPwrTopology 4 }
+
+lgpPwrTopVoltageConverter OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ yes(1),
+ no(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The system has a voltage converter."
+ ::= { lgpPwrTopology 5 }
+
+lgpPwrTopMaximumFrameCapacity OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Volt-Amp"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The maximum device system capacity."
+ ::= { lgpPwrTopology 6 }
+
+lgpPwrTopRedundantControlModules OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ yes(1),
+ no(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The device has a redundant control module installed."
+ ::= { lgpPwrTopology 7 }
+
+lgpPwrInputIsolationTransformerInstalled OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ notInstalled(1),
+ installed(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Indicates whether the input isolation transformer is installed."
+ ::= { lgpPwrTopology 8 }
+
+lgpPwrStateStaticSwitchType OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ notApplicable(1),
+ continuousDuty(2),
+ momentaryDuty(3)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Static switch type (N/A, continous duty, or momentary duty)."
+ ::= { lgpPwrTopology 9 }
+
+lgpPwrStateModuleType OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ singleModuleSystem(1),
+ module1plus1(2),
+ module1plusN(3),
+ moduleNplus1(4),
+ systemControlCabinet(5),
+ mainStaticSwitch(6)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "UPS module type.
+ SMS -- Single Module System
+ 1 + 1 -- Redundant system for capacity
+ 1 + N -- Distributed multi-module system
+ N + 1 -- A multi-module system with one bypass for the system
+ SCC -- System Control Cabinet used in an N+1 system to
+ provide a single bypass for the system.
+ MSS -- Main Static Switch"
+ ::= { lgpPwrTopology 10 }
+
+lgpPwrStateBypassInputConfig OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ singlePhase2WireL1WithReturn(1),
+ twoPhase2WireL1L2(2),
+ twoPhase3WireL1L2WithNeutral(3),
+ threePhase3WireL1L2L3(4),
+ threePhase4WireL1L2L3WithNeutral(5)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Bypass input wire physical wiring configuration.
+ singlePhase2WireL1WithReturn
+ Single phase input with 2 wires (Line 1, and Return).
+ twoPhase2WireL1L2
+ Two phase input with 2 wires (Line 1, and Line 2).
+ twoPhase3WireL1L2WithNeutral
+ Two phase input with 3 wires (Line 1, Line 2, and Neutral)
+ threePhase3WireL1L2L3
+ Three phase input with 3 wires (Line 1, Line 2, and Line 3)
+ threePhase4WireL1L2L3WithNeutral
+ Three phase input with 4 wires (Line 1, Line 2, Line 3, and
+ Neutral)."
+ ::= { lgpPwrTopology 11 }
+
+lgpPwrStateOutputConfig OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ singlePhase2WireL1WithReturn(1),
+ twoPhase2WireL1L2(2),
+ twoPhase3WireL1L2WithNeutral(3),
+ threePhase3WireL1L2L3(4),
+ threePhase4WireL1L2L3WithNeutral(5)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Output wire physical wiring configuration.
+ singlePhase2WireL1WithReturn
+ Single phase output with 2 wires (Line 1, and Return).
+ twoPhase2WireL1L2
+ Two phase output with 2 wires (Line 1, and Line 2).
+ twoPhase3WireL1L2WithNeutral
+ Two phase output with 3 wires (Line 1, Line 2, and Neutral)
+ threePhase3WireL1L2L3
+ Three phase output with 3 wires (Line 1, Line 2, and Line 3)
+ threePhase4WireL1L2L3WithNeutral
+ Three phase output with 4 wires (Line 1, Line 2, Line 3, and
+ Neutral)."
+ ::= { lgpPwrTopology 12 }
+
+lgpPwrRectifierPassiveFilterInstalled OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ notInstalled(1),
+ installed(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Indicates whether the rectifier passive filter is installed."
+ ::= { lgpPwrTopology 13 }
+
+lgpPwrRectifierTrapInstalled OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ notInstalled(1),
+ installed(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Indicates whether the rectifier input passive filter is installed."
+ ::= { lgpPwrTopology 14 }
+
+lgpPwrRectifierActiveFilterInstalled OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ notInstalled(1),
+ installed(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Indicates whether the rectifier active filter is installed."
+ ::= { lgpPwrTopology 15 }
+
+-- =============================================================================
+-- lgpPwrConfig - Liebert Power Config Group
+-- =============================================================================
+
+lgpPwrSysCapacity OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Volt-Amp"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The current device system capacity."
+ ::= { lgpPwrConfig 1 }
+
+lgpPwrUPSModuleMode OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ single(1),
+ parallel(2),
+ hotmaster(3),
+ hotslave(4)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The module mode of the UPS."
+ ::= { lgpPwrConfig 2 }
+
+lgpPwrMaxRatedCurrent OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "Amp"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "System output maximum amperage rating. The maximum rated amperage for
+ the system. This value is based upon the model type and is typically
+ limited by the wiring, breakers, power devices, etc."
+ ::= { lgpPwrConfig 3 }
+
+lgpPwrRectifierPulseCount OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ sixPulse(1),
+ twelvePulse(2),
+ eighteenPulse(3),
+ twentyFourPulse(4)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Rectifier pulse count per waveform cycle (6-, 12-, 18-, or 24-pulse)."
+ ::= { lgpPwrConfig 4 }
+END
|