mibs/MIBS/riedo/NETTRACK-E3METER-SNMP-MIB

1079 lines
26 KiB
Plaintext
Raw Normal View History

2023-12-05 12:25:34 +01:00
NETTRACK-E3METER-SNMP-MIB DEFINITIONS ::= BEGIN
IMPORTS
MODULE-IDENTITY,
OBJECT-TYPE,
Integer32,
enterprises
FROM SNMPv2-SMI
TEXTUAL-CONVENTION,
TruthValue
FROM SNMPv2-TC
;
nettrack OBJECT IDENTIFIER
::= { enterprises 21695 }
public OBJECT IDENTIFIER
::= { nettrack 1 }
e3Mib
MODULE-IDENTITY
LAST-UPDATED "201810090000Z"
ORGANIZATION "net-track GmbH"
CONTACT-INFO "net-track GmbH
Duensstrasse 1
3186 Duedingen
Switzerland
www.net-track.ch"
DESCRIPTION "Management Information for E3METER IPM products
www.e3meter.com"
REVISION "201810090000Z"
DESCRIPTION "Added RCM traps."
REVISION "201810080000Z"
DESCRIPTION "Added RCM-related stuff."
REVISION "201604180000Z"
DESCRIPTION "Added e3IpmAlarmTable."
REVISION "201602030000Z"
DESCRIPTION "Added traps."
REVISION "201204120000Z"
DESCRIPTION "Added import of TEXTUAL-CONVENTION."
REVISION "201111020000Z"
DESCRIPTION "Added channel type and channel groups."
REVISION "201108190000Z"
DESCRIPTION "Added e3IpmChannelName."
REVISION "201101260000Z"
DESCRIPTION "Corrected some syntax errors for very picky parsers."
REVISION "201012060000Z"
DESCRIPTION "Added sensor data."
REVISION "201010200000Z"
DESCRIPTION "Initial version of this MIB module."
::= { public 10 }
e3Ipm OBJECT IDENTIFIER
::= { e3Mib 7 }
-- ===========================================================================
-- Textual conventions
--
Watts ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Watts"
SYNTAX INTEGER
VoltAmpereReactives ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Volt-ampere reactives"
SYNTAX Integer32
VoltAmperes ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Volt-amperes"
SYNTAX Integer32
WattHours ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Watt hours"
SYNTAX Integer32
VoltAmpereReactiveHours ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Volt-ampere reactive hours"
SYNTAX Integer32
VoltAmpereHours ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Volt-ampere hours"
SYNTAX Integer32
MilliAmperes ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Milli-amperes"
SYNTAX Integer32
MilliVolts ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Milli-volts"
SYNTAX Integer32
MilliHertz ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Milli-hertz"
SYNTAX Integer32
DeciDegreesCelsius ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Deci-degrees celsius"
SYNTAX Integer32
Permil ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Per mil"
SYNTAX INTEGER
-- ===========================================================================
-- Agent information
--
e3IpmInfo OBJECT IDENTIFIER
::= { e3Ipm 1 }
e3IpmInfoSerial OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Serial number."
::= { e3IpmInfo 1 }
e3IpmInfoModel OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Model number."
::= { e3IpmInfo 2 }
e3IpmInfoHWVersion OBJECT-TYPE
SYNTAX INTEGER {
rev-a (0),
rev-b (1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Hardware revision."
::= { e3IpmInfo 3 }
e3IpmInfoFWVersion OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Integer representation of the firmware revision
(major.minor) represented as a 16 bit integer."
::= { e3IpmInfo 4 }
e3IpmInfoMeters OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of power meters in this IPS."
::= { e3IpmInfo 5 }
-- ===========================================================================
-- IPM meters
--
e3IpmMeterTable OBJECT-TYPE
SYNTAX SEQUENCE OF E3IpmMeterEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The e3IpmMeterTable holds information related to the
powermeters of all IPS nodes."
::= { e3Ipm 2 }
e3IpmMeterEntry OBJECT-TYPE
SYNTAX E3IpmMeterEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Holds the information related to one specific powermeter."
INDEX { e3IpmMeter }
::= { e3IpmMeterTable 1 }
E3IpmMeterEntry ::= SEQUENCE {
e3IpmMeter Integer32,
e3IpmEnergyP WattHours,
e3IpmEnergyQ VoltAmpereReactiveHours,
e3IpmEnergyS VoltAmpereHours,
e3IpmPowerP Watts,
e3IpmPowerQ VoltAmpereReactives,
e3IpmPowerS VoltAmperes,
e3IpmUrms MilliVolts,
e3IpmIrms MilliAmperes,
e3IpmFrequency MilliHertz,
e3IpmChannelName OCTET STRING,
e3IpmChannelType INTEGER
}
e3IpmMeter OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of the powermeter of this IPS."
::= { e3IpmMeterEntry 1 }
e3IpmEnergyP OBJECT-TYPE
SYNTAX WattHours
UNITS "Wh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Active energy in watt hours."
::= { e3IpmMeterEntry 2 }
e3IpmEnergyQ OBJECT-TYPE
SYNTAX VoltAmpereReactiveHours
UNITS "varh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Reactive energy in volt-ampere reactives hours."
::= { e3IpmMeterEntry 3 }
e3IpmEnergyS OBJECT-TYPE
SYNTAX VoltAmpereHours
UNITS "VAh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Apparent energy in volt-ampere hours."
::= { e3IpmMeterEntry 4 }
e3IpmPowerP OBJECT-TYPE
SYNTAX Watts
UNITS "W"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Active power at a given instant."
::= { e3IpmMeterEntry 5 }
e3IpmPowerQ OBJECT-TYPE
SYNTAX VoltAmpereReactives
UNITS "var"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Reactive power at a given instant."
::= { e3IpmMeterEntry 6 }
e3IpmPowerS OBJECT-TYPE
SYNTAX VoltAmperes
UNITS "VA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Apparent power at a given instant."
::= { e3IpmMeterEntry 7 }
e3IpmUrms OBJECT-TYPE
SYNTAX MilliVolts
UNITS "mV"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"RMS voltage at a given instant."
::= { e3IpmMeterEntry 8 }
e3IpmIrms OBJECT-TYPE
SYNTAX MilliAmperes
UNITS "mA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"RMS current at a given instant."
::= { e3IpmMeterEntry 9 }
e3IpmFrequency OBJECT-TYPE
SYNTAX MilliHertz
UNITS "mHz"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Frequency measured a given instant."
::= { e3IpmMeterEntry 10 }
e3IpmChannelName OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(0..15))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Channel name."
::= { e3IpmMeterEntry 11 }
e3IpmChannelType OBJECT-TYPE
SYNTAX INTEGER {
live-wire (0),
neutral-wire (1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Channel type: For neutral wire channels, only I_rms will
contain meaningful values."
::= { e3IpmMeterEntry 12 }
-- ===========================================================================
-- IPM sensors
--
e3IpmSensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF E3IpmSensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The e3IpmSensorTable holds information related to the
sensor of this IPM."
::= { e3Ipm 3 }
e3IpmSensorEntry OBJECT-TYPE
SYNTAX E3IpmSensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Holds the information related to one specific sensor."
INDEX { e3IpmSensor }
::= { e3IpmSensorTable 1 }
E3IpmSensorEntry ::= SEQUENCE {
e3IpmSensor Integer32,
e3IpmSensorType INTEGER,
e3IpmSensorVersion OCTET STRING,
e3IpmSensorTemperatureCelsius DeciDegreesCelsius,
e3IpmSensorHumidity Permil
}
e3IpmSensor OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Sensor port number."
::= { e3IpmSensorEntry 1 }
e3IpmSensorType OBJECT-TYPE
SYNTAX INTEGER {
none (0),
temp (1),
temp-humidity (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Sensor type."
::= { e3IpmSensorEntry 2 }
e3IpmSensorVersion OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(0..15))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Sensor version."
::= { e3IpmSensorEntry 3 }
e3IpmSensorTemperatureCelsius OBJECT-TYPE
SYNTAX DeciDegreesCelsius
UNITS "deg-C/10"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Temperature in tenth degrees."
::= { e3IpmSensorEntry 4 }
e3IpmSensorHumidity OBJECT-TYPE
SYNTAX Permil
UNITS "/1000"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Relative humidity in per mil."
::= { e3IpmSensorEntry 5 }
-- ===========================================================================
-- IPM predefined channel groups
--
e3IpmPGroupTable OBJECT-TYPE
SYNTAX SEQUENCE OF E3IpmPGroupEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The e3IpmPGroupTable holds information related to predefined
channel groups."
::= { e3Ipm 4 }
e3IpmPGroupEntry OBJECT-TYPE
SYNTAX E3IpmPGroupEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Holds the information related to one specific group."
INDEX { e3IpmPGroup }
::= { e3IpmPGroupTable 1 }
E3IpmPGroupEntry ::= SEQUENCE {
e3IpmPGroup Integer32,
e3IpmPGName OCTET STRING,
e3IpmPGMembers Integer32,
e3IpmPGEnergyP WattHours,
e3IpmPGEnergyQ VoltAmpereReactiveHours,
e3IpmPGEnergyS VoltAmpereHours,
e3IpmPGPowerP Watts,
e3IpmPGPowerQ VoltAmpereReactives,
e3IpmPGPowerS VoltAmperes,
e3IpmPGIrms MilliAmperes
}
e3IpmPGroup OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Predefined channel group number."
::= { e3IpmPGroupEntry 1 }
e3IpmPGName OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(0..15))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Channel group name."
::= { e3IpmPGroupEntry 2 }
e3IpmPGMembers OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A bit set specifying the channels which are
members of this channel group. If bit 0 is set,
this means that channel CH1 is member of this
group. Bit 1 stands for CH2 and so on."
::= { e3IpmPGroupEntry 3 }
e3IpmPGEnergyP OBJECT-TYPE
SYNTAX WattHours
UNITS "Wh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Channel group active energy in watt hours."
::= { e3IpmPGroupEntry 4 }
e3IpmPGEnergyQ OBJECT-TYPE
SYNTAX VoltAmpereReactiveHours
UNITS "varh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Channel group reactive energy in volt-ampere reactives hours."
::= { e3IpmPGroupEntry 5 }
e3IpmPGEnergyS OBJECT-TYPE
SYNTAX VoltAmpereHours
UNITS "VAh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Channel group apparent energy in volt-ampere hours."
::= { e3IpmPGroupEntry 6 }
e3IpmPGPowerP OBJECT-TYPE
SYNTAX Watts
UNITS "W"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Channel group active power at a given instant."
::= { e3IpmPGroupEntry 7 }
e3IpmPGPowerQ OBJECT-TYPE
SYNTAX VoltAmpereReactives
UNITS "var"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Channel group reactive power at a given instant."
::= { e3IpmPGroupEntry 8 }
e3IpmPGPowerS OBJECT-TYPE
SYNTAX VoltAmperes
UNITS "VA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Channel group apparent power at a given instant."
::= { e3IpmPGroupEntry 9 }
e3IpmPGIrms OBJECT-TYPE
SYNTAX MilliAmperes
UNITS "mA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Channel group RMS current at a given instant."
::= { e3IpmPGroupEntry 10 }
-- ===========================================================================
-- IPM user defined channel groups
--
e3IpmUGroupTable OBJECT-TYPE
SYNTAX SEQUENCE OF E3IpmUGroupEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The e3IpmUGroupTable holds information related to user
defined channel groups."
::= { e3Ipm 5 }
e3IpmUGroupEntry OBJECT-TYPE
SYNTAX E3IpmUGroupEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Holds the information related to one specific group."
INDEX { e3IpmUGroup }
::= { e3IpmUGroupTable 1 }
E3IpmUGroupEntry ::= SEQUENCE {
e3IpmUGroup Integer32,
e3IpmUGName OCTET STRING,
e3IpmUGMembers Integer32,
e3IpmUGEnergyP WattHours,
e3IpmUGEnergyQ VoltAmpereReactiveHours,
e3IpmUGEnergyS VoltAmpereHours,
e3IpmUGPowerP Watts,
e3IpmUGPowerQ VoltAmpereReactives,
e3IpmUGPowerS VoltAmperes,
e3IpmUGIrms MilliAmperes
}
e3IpmUGroup OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"User defined channel group number."
::= { e3IpmUGroupEntry 1 }
e3IpmUGName OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(0..15))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Channel group name."
::= { e3IpmUGroupEntry 2 }
e3IpmUGMembers OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A bit set specifying the channels which are
members of this channel group. If bit 0 is set,
this means that channel CH1 is member of this
group. Bit 1 stands for CH2 and so on. If no
members are configured, the group is inactive."
::= { e3IpmUGroupEntry 3 }
e3IpmUGEnergyP OBJECT-TYPE
SYNTAX WattHours
UNITS "Wh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Channel group active energy in watt hours."
::= { e3IpmUGroupEntry 4 }
e3IpmUGEnergyQ OBJECT-TYPE
SYNTAX VoltAmpereReactiveHours
UNITS "varh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Channel group reactive energy in volt-ampere reactives hours."
::= { e3IpmUGroupEntry 5 }
e3IpmUGEnergyS OBJECT-TYPE
SYNTAX VoltAmpereHours
UNITS "VAh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Channel group apparent energy in volt-ampere hours."
::= { e3IpmUGroupEntry 6 }
e3IpmUGPowerP OBJECT-TYPE
SYNTAX Watts
UNITS "W"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Channel group active power at a given instant."
::= { e3IpmUGroupEntry 7 }
e3IpmUGPowerQ OBJECT-TYPE
SYNTAX VoltAmpereReactives
UNITS "var"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Channel group reactive power at a given instant."
::= { e3IpmUGroupEntry 8 }
e3IpmUGPowerS OBJECT-TYPE
SYNTAX VoltAmperes
UNITS "VA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Channel group apparent power at a given instant."
::= { e3IpmUGroupEntry 9 }
e3IpmUGIrms OBJECT-TYPE
SYNTAX MilliAmperes
UNITS "mA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Channel group RMS current at a given instant."
::= { e3IpmUGroupEntry 10 }
-- ===========================================================================
-- IPM Alarm Settings
--
e3IpmAlarmTable OBJECT-TYPE
SYNTAX SEQUENCE OF E3IpmAlarmTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Holds alarm settings."
::= { e3Ipm 6 }
e3IpmAlarmTableEntry OBJECT-TYPE
SYNTAX E3IpmAlarmTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Holds alarm settings for one specific measured value."
INDEX { e3IpmAlarmIndex }
::= { e3IpmAlarmTable 1 }
E3IpmAlarmTableEntry ::= SEQUENCE {
e3IpmAlarmIndex INTEGER,
e3IpmAlarmState INTEGER,
e3IpmAlarmCritLowSet TruthValue,
e3IpmAlarmCritLow Integer32,
e3IpmAlarmWarnLowSet TruthValue,
e3IpmAlarmWarnLow Integer32,
e3IpmAlarmWarnHighSet TruthValue,
e3IpmAlarmWarnHigh Integer32,
e3IpmAlarmCritHighSet TruthValue,
e3IpmAlarmCritHigh Integer32
}
e3IpmAlarmIndex OBJECT-TYPE
SYNTAX INTEGER {
current-l1 (0),
current-l2 (1),
current-l3 (2),
current-n (3),
temp-int (4),
temp-ext1 (5),
temp-ext2 (6),
rh-ext1 (7),
rh-ext2 (8)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Defines the alarm described by the current entry. There
are alarms for the current of all phases, for the
temperature and the relative humidity."
::= { e3IpmAlarmTableEntry 1 }
e3IpmAlarmState OBJECT-TYPE
SYNTAX INTEGER {
critical-low (0),
warn-low (1),
normal (2),
warn-high (3),
critical-high (4),
unknown (5)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Shows this alarm entries' state. If no alarm settings
are defined, the state is unknown."
::= { e3IpmAlarmTableEntry 2 }
e3IpmAlarmCritLowSet OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"True if a 'critical low' alarm level for the current
entry is defined, false otherwise."
::= { e3IpmAlarmTableEntry 3 }
e3IpmAlarmCritLow OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The 'critical low' alarm level for the current entry
in hundredths of the relevant unit (i.e. amperes, degrees
celsius and %RH). If no alarm level is configured, this
reads 0."
::= { e3IpmAlarmTableEntry 4 }
e3IpmAlarmWarnLowSet OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"True if a 'warn low' alarm level for the current
entry is defined, false otherwise."
::= { e3IpmAlarmTableEntry 5 }
e3IpmAlarmWarnLow OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The 'warn low' alarm level for the current entry
in hundredths of the relevant unit (i.e. amperes, degrees
celsius and %RH). If no alarm level is configured, this
reads 0."
::= { e3IpmAlarmTableEntry 6 }
e3IpmAlarmWarnHighSet OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"True if a 'warn high' alarm level for the current
entry is defined, false otherwise."
::= { e3IpmAlarmTableEntry 7 }
e3IpmAlarmWarnHigh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The 'warn high' alarm level for the current entry
in hundredths of the relevant unit (i.e. amperes, degrees
celsius and %RH). If no alarm level is configured, this
reads 0."
::= { e3IpmAlarmTableEntry 8 }
e3IpmAlarmCritHighSet OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"True if a 'critical high' alarm level for the current
entry is defined, false otherwise."
::= { e3IpmAlarmTableEntry 9 }
e3IpmAlarmCritHigh OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The 'critical high' alarm level for the current entry
in hundredths of the relevant unit (i.e. amperes, degrees
celsius and %RH). If no alarm level is configured, this
reads 0."
::= { e3IpmAlarmTableEntry 10 }
-- ===========================================================================
-- IPM RCM Data
--
e3IpmRcmTable OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Table holding all residual current monitoring (RCM)
data of this IPS."
::= { e3Ipm 7 }
e3IpmRcmTableEntry OBJECT-TYPE
SYNTAX E3IpmRcmTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"One entry in the RCM table."
INDEX { e3IpmRcmChannel }
::= { e3IpmRcmTable 1 }
E3IpmRcmTableEntry ::= SEQUENCE {
e3IpmRcmChannel Integer32,
e3IpmRcmAcLimit MilliAmperes,
e3IpmRcmDcLimit MilliAmperes,
e3IpmRcmStatus Integer32,
e3IpmRcmAc MilliAmperes,
e3IpmRcmDc MilliAmperes
}
e3IpmRcmChannel OBJECT-TYPE
SYNTAX INTEGER {
total(0)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"RCM channel: 0 (total) is the total of all phases in this IPS."
::= { e3IpmRcmTableEntry 1 }
e3IpmRcmAcLimit OBJECT-TYPE
SYNTAX MilliAmperes
UNITS "mA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The factory configured AC RCM limit. Any measurement
higher than this limit is considered a critical problem."
::= { e3IpmRcmTableEntry 2 }
e3IpmRcmDcLimit OBJECT-TYPE
SYNTAX MilliAmperes
UNITS "mA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The factory configured DC RCM limit. Any measurement
higher than this limit is considered a critical problem."
::= { e3IpmRcmTableEntry 3 }
e3IpmRcmStatus OBJECT-TYPE
SYNTAX INTEGER {
unknown(0),
valid(1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status of the RcmAc/RcmDc data. If the residual
current cannot be measured, 0 (unknown) is signalled
here, otherwise 1 (valid)."
::= { e3IpmRcmTableEntry 4 }
e3IpmRcmAc OBJECT-TYPE
SYNTAX MilliAmperes
UNITS "mA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The latest AC RCM measurement."
::= { e3IpmRcmTableEntry 5 }
e3IpmRcmDc OBJECT-TYPE
SYNTAX MilliAmperes
UNITS "mA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The latest DC RCM measurement."
::= { e3IpmRcmTableEntry 6 }
-- ===========================================================================
-- IPM Traps
--
e3IpmTraps OBJECT IDENTIFIER
::= { e3Mib 8 }
-- Current
e3IpmCurrentCritLow NOTIFICATION-TYPE
OBJECTS { e3IpmInfoSerial, e3IpmMeter, e3IpmIrms }
STATUS current
DESCRIPTION
"The e3IpmCurrentCritLow is triggered when the current
on the given channel is less than or equal to the configured
critical low threshold."
::= { e3IpmTraps 1 }
e3IpmCurrentWarnLow NOTIFICATION-TYPE
OBJECTS { e3IpmInfoSerial, e3IpmMeter, e3IpmIrms }
STATUS current
DESCRIPTION
"The e3IpmCurrentWarnLow is triggered when the current
on the given channel is less than or equal to the configured
warn low threshold."
::= { e3IpmTraps 2 }
e3IpmCurrentNormal NOTIFICATION-TYPE
OBJECTS { e3IpmInfoSerial, e3IpmMeter, e3IpmIrms }
STATUS current
DESCRIPTION
"The e3IpmCurrentNormal is triggered when the current
on the given channel is not outside any configured
limits."
::= { e3IpmTraps 3 }
e3IpmCurrentWarnHigh NOTIFICATION-TYPE
OBJECTS { e3IpmInfoSerial, e3IpmMeter, e3IpmIrms }
STATUS current
DESCRIPTION
"The e3IpmCurrentWarnHigh is triggered when the current
on the given channel is greater than or equal to the
configured warn high threshold."
::= { e3IpmTraps 4 }
e3IpmCurrentCritHigh NOTIFICATION-TYPE
OBJECTS { e3IpmInfoSerial, e3IpmMeter, e3IpmIrms }
STATUS current
DESCRIPTION
"The e3IpmCurrentCritHigh is triggered when the current
on the given channel is greater than or equal to the
configured critical high threshold."
::= { e3IpmTraps 5 }
-- Temperature
e3IpmTempCritLow NOTIFICATION-TYPE
OBJECTS { e3IpmInfoSerial, e3IpmSensor, e3IpmSensorTemperatureCelsius }
STATUS current
DESCRIPTION
"The e3IpmTempCritLow is triggered when the temperature
on the given sensor is less than or equal to the configured
critical low threshold."
::= { e3IpmTraps 6 }
e3IpmTempWarnLow NOTIFICATION-TYPE
OBJECTS { e3IpmInfoSerial, e3IpmSensor, e3IpmSensorTemperatureCelsius }
STATUS current
DESCRIPTION
"The e3IpmTempWarnLow is triggered when the temperature
on the given sensor is less than or equal to the configured
warn low threshold."
::= { e3IpmTraps 7 }
e3IpmTempNormal NOTIFICATION-TYPE
OBJECTS { e3IpmInfoSerial, e3IpmSensor, e3IpmSensorTemperatureCelsius }
STATUS current
DESCRIPTION
"The e3IpmTempNormal is triggered when the temperature
on the given sensor is not outside any configured
limits."
::= { e3IpmTraps 8 }
e3IpmTempWarnHigh NOTIFICATION-TYPE
OBJECTS { e3IpmInfoSerial, e3IpmSensor, e3IpmSensorTemperatureCelsius }
STATUS current
DESCRIPTION
"The e3IpmTempWarnHigh is triggered when the temperature
on the given sensor is greater than or equal to the
configured warn high threshold."
::= { e3IpmTraps 9 }
e3IpmTempCritHigh NOTIFICATION-TYPE
OBJECTS { e3IpmInfoSerial, e3IpmSensor, e3IpmSensorTemperatureCelsius }
STATUS current
DESCRIPTION
"The e3IpmTempCritHigh is triggered when the temperature
on the given sensor is greater than or equal to the
configured critical high threshold."
::= { e3IpmTraps 10 }
-- Relative Humidity
e3IpmRHCritLow NOTIFICATION-TYPE
OBJECTS { e3IpmInfoSerial, e3IpmSensor, e3IpmSensorHumidity }
STATUS current
DESCRIPTION
"The e3IpmRHCritLow is triggered when the relative humidity
on the given sensor is less than or equal to the configured
critical low threshold."
::= { e3IpmTraps 11 }
e3IpmRHWarnLow NOTIFICATION-TYPE
OBJECTS { e3IpmInfoSerial, e3IpmSensor, e3IpmSensorHumidity }
STATUS current
DESCRIPTION
"The e3IpmRHWarnLow is triggered when the relative humidity
on the given sensor is less than or equal to the configured
warn low threshold."
::= { e3IpmTraps 12 }
e3IpmRHNormal NOTIFICATION-TYPE
OBJECTS { e3IpmInfoSerial, e3IpmSensor, e3IpmSensorHumidity }
STATUS current
DESCRIPTION
"The e3IpmRHNormal is triggered when the relative humidity
on the given sensor is not outside any configured
limits."
::= { e3IpmTraps 13 }
e3IpmRHWarnHigh NOTIFICATION-TYPE
OBJECTS { e3IpmInfoSerial, e3IpmSensor, e3IpmSensorHumidity }
STATUS current
DESCRIPTION
"The e3IpmRHWarnHigh is triggered when the relative humidity
on the given sensor is greater than or equal to the
configured warn high threshold."
::= { e3IpmTraps 14 }
e3IpmRHCritHigh NOTIFICATION-TYPE
OBJECTS { e3IpmInfoSerial, e3IpmSensor, e3IpmSensorHumidity }
STATUS current
DESCRIPTION
"The e3IpmRHCritHigh is triggered when the relative humidity
on the given sensor is greater than or equal to the
configured critical high threshold."
::= { e3IpmTraps 15 }
-- RCM Alarms
e3IpmRcmAcNormal NOTIFICATION-TYPE
OBJECTS { e3IpmInfoSerial, e3IpmRcmChannel, e3IpmRcmAc }
STATUS current
DESCRIPTION
"The e3IpmRcmAcNormal is triggered when the AC part of
the residual current falls below the
factory-configured limit."
::= { e3IpmTraps 16 }
e3IpmRcmAcCritHigh NOTIFICATION-TYPE
OBJECTS { e3IpmInfoSerial, e3IpmRcmChannel, e3IpmRcmAc }
STATUS current
DESCRIPTION
"The e3IpmRcmAcCritHigh is triggered when the AC part
of the residual current is greater than the
factory-configured limit."
::= { e3IpmTraps 17 }
e3IpmRcmDcNormal NOTIFICATION-TYPE
OBJECTS { e3IpmInfoSerial, e3IpmRcmChannel, e3IpmRcmDc }
STATUS current
DESCRIPTION
"The e3IpmRcmDcNormal is triggered when the DC part of
the residual current falls below the
factory-configured limit."
::= { e3IpmTraps 18 }
e3IpmRcmDcCritHigh NOTIFICATION-TYPE
OBJECTS { e3IpmInfoSerial, e3IpmRcmChannel, e3IpmRcmDc }
STATUS current
DESCRIPTION
"The e3IpmRcmDcCritHigh is triggered when the DC part
of the residual current is greater than the
factory-configured limit."
::= { e3IpmTraps 19 }
END