NETTRACK-E3METER-SNMP-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
MODULE-IDENTITY,
|
|
OBJECT-TYPE,
|
|
Integer32,
|
|
enterprises
|
|
FROM SNMPv2-SMI
|
|
TEXTUAL-CONVENTION,
|
|
TruthValue
|
|
FROM SNMPv2-TC
|
|
;
|
|
|
|
nettrack OBJECT IDENTIFIER
|
|
::= { enterprises 21695 }
|
|
|
|
public OBJECT IDENTIFIER
|
|
::= { nettrack 1 }
|
|
|
|
e3Mib
|
|
MODULE-IDENTITY
|
|
LAST-UPDATED "201810090000Z"
|
|
ORGANIZATION "net-track GmbH"
|
|
CONTACT-INFO "net-track GmbH
|
|
Duensstrasse 1
|
|
3186 Duedingen
|
|
Switzerland
|
|
www.net-track.ch"
|
|
DESCRIPTION "Management Information for E3METER IPM products
|
|
www.e3meter.com"
|
|
REVISION "201810090000Z"
|
|
DESCRIPTION "Added RCM traps."
|
|
REVISION "201810080000Z"
|
|
DESCRIPTION "Added RCM-related stuff."
|
|
REVISION "201604180000Z"
|
|
DESCRIPTION "Added e3IpmAlarmTable."
|
|
REVISION "201602030000Z"
|
|
DESCRIPTION "Added traps."
|
|
REVISION "201204120000Z"
|
|
DESCRIPTION "Added import of TEXTUAL-CONVENTION."
|
|
REVISION "201111020000Z"
|
|
DESCRIPTION "Added channel type and channel groups."
|
|
REVISION "201108190000Z"
|
|
DESCRIPTION "Added e3IpmChannelName."
|
|
REVISION "201101260000Z"
|
|
DESCRIPTION "Corrected some syntax errors for very picky parsers."
|
|
REVISION "201012060000Z"
|
|
DESCRIPTION "Added sensor data."
|
|
REVISION "201010200000Z"
|
|
DESCRIPTION "Initial version of this MIB module."
|
|
::= { public 10 }
|
|
|
|
e3Ipm OBJECT IDENTIFIER
|
|
::= { e3Mib 7 }
|
|
|
|
-- ===========================================================================
|
|
-- Textual conventions
|
|
--
|
|
|
|
Watts ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Watts"
|
|
SYNTAX INTEGER
|
|
|
|
VoltAmpereReactives ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Volt-ampere reactives"
|
|
SYNTAX Integer32
|
|
|
|
VoltAmperes ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Volt-amperes"
|
|
SYNTAX Integer32
|
|
|
|
WattHours ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Watt hours"
|
|
SYNTAX Integer32
|
|
|
|
VoltAmpereReactiveHours ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Volt-ampere reactive hours"
|
|
SYNTAX Integer32
|
|
|
|
VoltAmpereHours ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Volt-ampere hours"
|
|
SYNTAX Integer32
|
|
|
|
MilliAmperes ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Milli-amperes"
|
|
SYNTAX Integer32
|
|
|
|
MilliVolts ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Milli-volts"
|
|
SYNTAX Integer32
|
|
|
|
MilliHertz ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Milli-hertz"
|
|
SYNTAX Integer32
|
|
|
|
DeciDegreesCelsius ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Deci-degrees celsius"
|
|
SYNTAX Integer32
|
|
|
|
Permil ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Per mil"
|
|
SYNTAX INTEGER
|
|
|
|
-- ===========================================================================
|
|
-- Agent information
|
|
--
|
|
|
|
e3IpmInfo OBJECT IDENTIFIER
|
|
::= { e3Ipm 1 }
|
|
|
|
e3IpmInfoSerial OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Serial number."
|
|
::= { e3IpmInfo 1 }
|
|
|
|
e3IpmInfoModel OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Model number."
|
|
::= { e3IpmInfo 2 }
|
|
|
|
e3IpmInfoHWVersion OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
rev-a (0),
|
|
rev-b (1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Hardware revision."
|
|
::= { e3IpmInfo 3 }
|
|
|
|
e3IpmInfoFWVersion OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Integer representation of the firmware revision
|
|
(major.minor) represented as a 16 bit integer."
|
|
::= { e3IpmInfo 4 }
|
|
|
|
e3IpmInfoMeters OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of power meters in this IPS."
|
|
::= { e3IpmInfo 5 }
|
|
|
|
-- ===========================================================================
|
|
-- IPM meters
|
|
--
|
|
|
|
e3IpmMeterTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF E3IpmMeterEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmMeterTable holds information related to the
|
|
powermeters of all IPS nodes."
|
|
::= { e3Ipm 2 }
|
|
|
|
e3IpmMeterEntry OBJECT-TYPE
|
|
SYNTAX E3IpmMeterEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Holds the information related to one specific powermeter."
|
|
INDEX { e3IpmMeter }
|
|
::= { e3IpmMeterTable 1 }
|
|
|
|
E3IpmMeterEntry ::= SEQUENCE {
|
|
e3IpmMeter Integer32,
|
|
e3IpmEnergyP WattHours,
|
|
e3IpmEnergyQ VoltAmpereReactiveHours,
|
|
e3IpmEnergyS VoltAmpereHours,
|
|
e3IpmPowerP Watts,
|
|
e3IpmPowerQ VoltAmpereReactives,
|
|
e3IpmPowerS VoltAmperes,
|
|
e3IpmUrms MilliVolts,
|
|
e3IpmIrms MilliAmperes,
|
|
e3IpmFrequency MilliHertz,
|
|
e3IpmChannelName OCTET STRING,
|
|
e3IpmChannelType INTEGER
|
|
}
|
|
|
|
e3IpmMeter OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of the powermeter of this IPS."
|
|
::= { e3IpmMeterEntry 1 }
|
|
|
|
e3IpmEnergyP OBJECT-TYPE
|
|
SYNTAX WattHours
|
|
UNITS "Wh"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Active energy in watt hours."
|
|
::= { e3IpmMeterEntry 2 }
|
|
|
|
e3IpmEnergyQ OBJECT-TYPE
|
|
SYNTAX VoltAmpereReactiveHours
|
|
UNITS "varh"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reactive energy in volt-ampere reactives hours."
|
|
::= { e3IpmMeterEntry 3 }
|
|
|
|
e3IpmEnergyS OBJECT-TYPE
|
|
SYNTAX VoltAmpereHours
|
|
UNITS "VAh"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Apparent energy in volt-ampere hours."
|
|
::= { e3IpmMeterEntry 4 }
|
|
|
|
e3IpmPowerP OBJECT-TYPE
|
|
SYNTAX Watts
|
|
UNITS "W"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Active power at a given instant."
|
|
::= { e3IpmMeterEntry 5 }
|
|
|
|
e3IpmPowerQ OBJECT-TYPE
|
|
SYNTAX VoltAmpereReactives
|
|
UNITS "var"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reactive power at a given instant."
|
|
::= { e3IpmMeterEntry 6 }
|
|
|
|
e3IpmPowerS OBJECT-TYPE
|
|
SYNTAX VoltAmperes
|
|
UNITS "VA"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Apparent power at a given instant."
|
|
::= { e3IpmMeterEntry 7 }
|
|
|
|
e3IpmUrms OBJECT-TYPE
|
|
SYNTAX MilliVolts
|
|
UNITS "mV"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"RMS voltage at a given instant."
|
|
::= { e3IpmMeterEntry 8 }
|
|
|
|
e3IpmIrms OBJECT-TYPE
|
|
SYNTAX MilliAmperes
|
|
UNITS "mA"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"RMS current at a given instant."
|
|
::= { e3IpmMeterEntry 9 }
|
|
|
|
e3IpmFrequency OBJECT-TYPE
|
|
SYNTAX MilliHertz
|
|
UNITS "mHz"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Frequency measured a given instant."
|
|
::= { e3IpmMeterEntry 10 }
|
|
|
|
e3IpmChannelName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(0..15))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Channel name."
|
|
::= { e3IpmMeterEntry 11 }
|
|
|
|
e3IpmChannelType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
live-wire (0),
|
|
neutral-wire (1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Channel type: For neutral wire channels, only I_rms will
|
|
contain meaningful values."
|
|
::= { e3IpmMeterEntry 12 }
|
|
|
|
-- ===========================================================================
|
|
-- IPM sensors
|
|
--
|
|
|
|
e3IpmSensorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF E3IpmSensorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmSensorTable holds information related to the
|
|
sensor of this IPM."
|
|
::= { e3Ipm 3 }
|
|
|
|
e3IpmSensorEntry OBJECT-TYPE
|
|
SYNTAX E3IpmSensorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Holds the information related to one specific sensor."
|
|
INDEX { e3IpmSensor }
|
|
::= { e3IpmSensorTable 1 }
|
|
|
|
E3IpmSensorEntry ::= SEQUENCE {
|
|
e3IpmSensor Integer32,
|
|
e3IpmSensorType INTEGER,
|
|
e3IpmSensorVersion OCTET STRING,
|
|
e3IpmSensorTemperatureCelsius DeciDegreesCelsius,
|
|
e3IpmSensorHumidity Permil
|
|
}
|
|
|
|
e3IpmSensor OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sensor port number."
|
|
::= { e3IpmSensorEntry 1 }
|
|
|
|
e3IpmSensorType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none (0),
|
|
temp (1),
|
|
temp-humidity (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sensor type."
|
|
::= { e3IpmSensorEntry 2 }
|
|
|
|
e3IpmSensorVersion OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(0..15))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sensor version."
|
|
::= { e3IpmSensorEntry 3 }
|
|
|
|
e3IpmSensorTemperatureCelsius OBJECT-TYPE
|
|
SYNTAX DeciDegreesCelsius
|
|
UNITS "deg-C/10"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature in tenth degrees."
|
|
::= { e3IpmSensorEntry 4 }
|
|
|
|
e3IpmSensorHumidity OBJECT-TYPE
|
|
SYNTAX Permil
|
|
UNITS "/1000"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Relative humidity in per mil."
|
|
::= { e3IpmSensorEntry 5 }
|
|
|
|
-- ===========================================================================
|
|
-- IPM predefined channel groups
|
|
--
|
|
|
|
e3IpmPGroupTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF E3IpmPGroupEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmPGroupTable holds information related to predefined
|
|
channel groups."
|
|
::= { e3Ipm 4 }
|
|
|
|
e3IpmPGroupEntry OBJECT-TYPE
|
|
SYNTAX E3IpmPGroupEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Holds the information related to one specific group."
|
|
INDEX { e3IpmPGroup }
|
|
::= { e3IpmPGroupTable 1 }
|
|
|
|
E3IpmPGroupEntry ::= SEQUENCE {
|
|
e3IpmPGroup Integer32,
|
|
e3IpmPGName OCTET STRING,
|
|
e3IpmPGMembers Integer32,
|
|
e3IpmPGEnergyP WattHours,
|
|
e3IpmPGEnergyQ VoltAmpereReactiveHours,
|
|
e3IpmPGEnergyS VoltAmpereHours,
|
|
e3IpmPGPowerP Watts,
|
|
e3IpmPGPowerQ VoltAmpereReactives,
|
|
e3IpmPGPowerS VoltAmperes,
|
|
e3IpmPGIrms MilliAmperes
|
|
}
|
|
|
|
e3IpmPGroup OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Predefined channel group number."
|
|
::= { e3IpmPGroupEntry 1 }
|
|
|
|
e3IpmPGName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(0..15))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Channel group name."
|
|
::= { e3IpmPGroupEntry 2 }
|
|
|
|
e3IpmPGMembers OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A bit set specifying the channels which are
|
|
members of this channel group. If bit 0 is set,
|
|
this means that channel CH1 is member of this
|
|
group. Bit 1 stands for CH2 and so on."
|
|
::= { e3IpmPGroupEntry 3 }
|
|
|
|
e3IpmPGEnergyP OBJECT-TYPE
|
|
SYNTAX WattHours
|
|
UNITS "Wh"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Channel group active energy in watt hours."
|
|
::= { e3IpmPGroupEntry 4 }
|
|
|
|
e3IpmPGEnergyQ OBJECT-TYPE
|
|
SYNTAX VoltAmpereReactiveHours
|
|
UNITS "varh"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Channel group reactive energy in volt-ampere reactives hours."
|
|
::= { e3IpmPGroupEntry 5 }
|
|
|
|
e3IpmPGEnergyS OBJECT-TYPE
|
|
SYNTAX VoltAmpereHours
|
|
UNITS "VAh"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Channel group apparent energy in volt-ampere hours."
|
|
::= { e3IpmPGroupEntry 6 }
|
|
|
|
e3IpmPGPowerP OBJECT-TYPE
|
|
SYNTAX Watts
|
|
UNITS "W"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Channel group active power at a given instant."
|
|
::= { e3IpmPGroupEntry 7 }
|
|
|
|
e3IpmPGPowerQ OBJECT-TYPE
|
|
SYNTAX VoltAmpereReactives
|
|
UNITS "var"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Channel group reactive power at a given instant."
|
|
::= { e3IpmPGroupEntry 8 }
|
|
|
|
e3IpmPGPowerS OBJECT-TYPE
|
|
SYNTAX VoltAmperes
|
|
UNITS "VA"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Channel group apparent power at a given instant."
|
|
::= { e3IpmPGroupEntry 9 }
|
|
|
|
e3IpmPGIrms OBJECT-TYPE
|
|
SYNTAX MilliAmperes
|
|
UNITS "mA"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Channel group RMS current at a given instant."
|
|
::= { e3IpmPGroupEntry 10 }
|
|
|
|
-- ===========================================================================
|
|
-- IPM user defined channel groups
|
|
--
|
|
|
|
e3IpmUGroupTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF E3IpmUGroupEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmUGroupTable holds information related to user
|
|
defined channel groups."
|
|
::= { e3Ipm 5 }
|
|
|
|
e3IpmUGroupEntry OBJECT-TYPE
|
|
SYNTAX E3IpmUGroupEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Holds the information related to one specific group."
|
|
INDEX { e3IpmUGroup }
|
|
::= { e3IpmUGroupTable 1 }
|
|
|
|
E3IpmUGroupEntry ::= SEQUENCE {
|
|
e3IpmUGroup Integer32,
|
|
e3IpmUGName OCTET STRING,
|
|
e3IpmUGMembers Integer32,
|
|
e3IpmUGEnergyP WattHours,
|
|
e3IpmUGEnergyQ VoltAmpereReactiveHours,
|
|
e3IpmUGEnergyS VoltAmpereHours,
|
|
e3IpmUGPowerP Watts,
|
|
e3IpmUGPowerQ VoltAmpereReactives,
|
|
e3IpmUGPowerS VoltAmperes,
|
|
e3IpmUGIrms MilliAmperes
|
|
}
|
|
|
|
e3IpmUGroup OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User defined channel group number."
|
|
::= { e3IpmUGroupEntry 1 }
|
|
|
|
e3IpmUGName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(0..15))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Channel group name."
|
|
::= { e3IpmUGroupEntry 2 }
|
|
|
|
e3IpmUGMembers OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A bit set specifying the channels which are
|
|
members of this channel group. If bit 0 is set,
|
|
this means that channel CH1 is member of this
|
|
group. Bit 1 stands for CH2 and so on. If no
|
|
members are configured, the group is inactive."
|
|
::= { e3IpmUGroupEntry 3 }
|
|
|
|
e3IpmUGEnergyP OBJECT-TYPE
|
|
SYNTAX WattHours
|
|
UNITS "Wh"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Channel group active energy in watt hours."
|
|
::= { e3IpmUGroupEntry 4 }
|
|
|
|
e3IpmUGEnergyQ OBJECT-TYPE
|
|
SYNTAX VoltAmpereReactiveHours
|
|
UNITS "varh"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Channel group reactive energy in volt-ampere reactives hours."
|
|
::= { e3IpmUGroupEntry 5 }
|
|
|
|
e3IpmUGEnergyS OBJECT-TYPE
|
|
SYNTAX VoltAmpereHours
|
|
UNITS "VAh"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Channel group apparent energy in volt-ampere hours."
|
|
::= { e3IpmUGroupEntry 6 }
|
|
|
|
e3IpmUGPowerP OBJECT-TYPE
|
|
SYNTAX Watts
|
|
UNITS "W"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Channel group active power at a given instant."
|
|
::= { e3IpmUGroupEntry 7 }
|
|
|
|
e3IpmUGPowerQ OBJECT-TYPE
|
|
SYNTAX VoltAmpereReactives
|
|
UNITS "var"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Channel group reactive power at a given instant."
|
|
::= { e3IpmUGroupEntry 8 }
|
|
|
|
e3IpmUGPowerS OBJECT-TYPE
|
|
SYNTAX VoltAmperes
|
|
UNITS "VA"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Channel group apparent power at a given instant."
|
|
::= { e3IpmUGroupEntry 9 }
|
|
|
|
e3IpmUGIrms OBJECT-TYPE
|
|
SYNTAX MilliAmperes
|
|
UNITS "mA"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Channel group RMS current at a given instant."
|
|
::= { e3IpmUGroupEntry 10 }
|
|
|
|
-- ===========================================================================
|
|
-- IPM Alarm Settings
|
|
--
|
|
|
|
e3IpmAlarmTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF E3IpmAlarmTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Holds alarm settings."
|
|
::= { e3Ipm 6 }
|
|
|
|
e3IpmAlarmTableEntry OBJECT-TYPE
|
|
SYNTAX E3IpmAlarmTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Holds alarm settings for one specific measured value."
|
|
INDEX { e3IpmAlarmIndex }
|
|
::= { e3IpmAlarmTable 1 }
|
|
|
|
E3IpmAlarmTableEntry ::= SEQUENCE {
|
|
e3IpmAlarmIndex INTEGER,
|
|
e3IpmAlarmState INTEGER,
|
|
e3IpmAlarmCritLowSet TruthValue,
|
|
e3IpmAlarmCritLow Integer32,
|
|
e3IpmAlarmWarnLowSet TruthValue,
|
|
e3IpmAlarmWarnLow Integer32,
|
|
e3IpmAlarmWarnHighSet TruthValue,
|
|
e3IpmAlarmWarnHigh Integer32,
|
|
e3IpmAlarmCritHighSet TruthValue,
|
|
e3IpmAlarmCritHigh Integer32
|
|
}
|
|
|
|
e3IpmAlarmIndex OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
current-l1 (0),
|
|
current-l2 (1),
|
|
current-l3 (2),
|
|
current-n (3),
|
|
temp-int (4),
|
|
temp-ext1 (5),
|
|
temp-ext2 (6),
|
|
rh-ext1 (7),
|
|
rh-ext2 (8)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Defines the alarm described by the current entry. There
|
|
are alarms for the current of all phases, for the
|
|
temperature and the relative humidity."
|
|
::= { e3IpmAlarmTableEntry 1 }
|
|
|
|
e3IpmAlarmState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
critical-low (0),
|
|
warn-low (1),
|
|
normal (2),
|
|
warn-high (3),
|
|
critical-high (4),
|
|
unknown (5)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Shows this alarm entries' state. If no alarm settings
|
|
are defined, the state is unknown."
|
|
::= { e3IpmAlarmTableEntry 2 }
|
|
|
|
e3IpmAlarmCritLowSet OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"True if a 'critical low' alarm level for the current
|
|
entry is defined, false otherwise."
|
|
::= { e3IpmAlarmTableEntry 3 }
|
|
|
|
e3IpmAlarmCritLow OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The 'critical low' alarm level for the current entry
|
|
in hundredths of the relevant unit (i.e. amperes, degrees
|
|
celsius and %RH). If no alarm level is configured, this
|
|
reads 0."
|
|
::= { e3IpmAlarmTableEntry 4 }
|
|
|
|
e3IpmAlarmWarnLowSet OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"True if a 'warn low' alarm level for the current
|
|
entry is defined, false otherwise."
|
|
::= { e3IpmAlarmTableEntry 5 }
|
|
|
|
e3IpmAlarmWarnLow OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The 'warn low' alarm level for the current entry
|
|
in hundredths of the relevant unit (i.e. amperes, degrees
|
|
celsius and %RH). If no alarm level is configured, this
|
|
reads 0."
|
|
::= { e3IpmAlarmTableEntry 6 }
|
|
|
|
e3IpmAlarmWarnHighSet OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"True if a 'warn high' alarm level for the current
|
|
entry is defined, false otherwise."
|
|
::= { e3IpmAlarmTableEntry 7 }
|
|
|
|
e3IpmAlarmWarnHigh OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The 'warn high' alarm level for the current entry
|
|
in hundredths of the relevant unit (i.e. amperes, degrees
|
|
celsius and %RH). If no alarm level is configured, this
|
|
reads 0."
|
|
::= { e3IpmAlarmTableEntry 8 }
|
|
|
|
e3IpmAlarmCritHighSet OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"True if a 'critical high' alarm level for the current
|
|
entry is defined, false otherwise."
|
|
::= { e3IpmAlarmTableEntry 9 }
|
|
|
|
e3IpmAlarmCritHigh OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The 'critical high' alarm level for the current entry
|
|
in hundredths of the relevant unit (i.e. amperes, degrees
|
|
celsius and %RH). If no alarm level is configured, this
|
|
reads 0."
|
|
::= { e3IpmAlarmTableEntry 10 }
|
|
|
|
-- ===========================================================================
|
|
-- IPM RCM Data
|
|
--
|
|
|
|
e3IpmRcmTable OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table holding all residual current monitoring (RCM)
|
|
data of this IPS."
|
|
::= { e3Ipm 7 }
|
|
|
|
e3IpmRcmTableEntry OBJECT-TYPE
|
|
SYNTAX E3IpmRcmTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One entry in the RCM table."
|
|
INDEX { e3IpmRcmChannel }
|
|
::= { e3IpmRcmTable 1 }
|
|
|
|
E3IpmRcmTableEntry ::= SEQUENCE {
|
|
e3IpmRcmChannel Integer32,
|
|
e3IpmRcmAcLimit MilliAmperes,
|
|
e3IpmRcmDcLimit MilliAmperes,
|
|
e3IpmRcmStatus Integer32,
|
|
e3IpmRcmAc MilliAmperes,
|
|
e3IpmRcmDc MilliAmperes
|
|
}
|
|
|
|
e3IpmRcmChannel OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
total(0)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"RCM channel: 0 (total) is the total of all phases in this IPS."
|
|
::= { e3IpmRcmTableEntry 1 }
|
|
|
|
e3IpmRcmAcLimit OBJECT-TYPE
|
|
SYNTAX MilliAmperes
|
|
UNITS "mA"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The factory configured AC RCM limit. Any measurement
|
|
higher than this limit is considered a critical problem."
|
|
::= { e3IpmRcmTableEntry 2 }
|
|
|
|
e3IpmRcmDcLimit OBJECT-TYPE
|
|
SYNTAX MilliAmperes
|
|
UNITS "mA"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The factory configured DC RCM limit. Any measurement
|
|
higher than this limit is considered a critical problem."
|
|
::= { e3IpmRcmTableEntry 3 }
|
|
|
|
e3IpmRcmStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknown(0),
|
|
valid(1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Status of the RcmAc/RcmDc data. If the residual
|
|
current cannot be measured, 0 (unknown) is signalled
|
|
here, otherwise 1 (valid)."
|
|
::= { e3IpmRcmTableEntry 4 }
|
|
|
|
e3IpmRcmAc OBJECT-TYPE
|
|
SYNTAX MilliAmperes
|
|
UNITS "mA"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The latest AC RCM measurement."
|
|
::= { e3IpmRcmTableEntry 5 }
|
|
|
|
e3IpmRcmDc OBJECT-TYPE
|
|
SYNTAX MilliAmperes
|
|
UNITS "mA"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The latest DC RCM measurement."
|
|
::= { e3IpmRcmTableEntry 6 }
|
|
|
|
-- ===========================================================================
|
|
-- IPM Traps
|
|
--
|
|
|
|
e3IpmTraps OBJECT IDENTIFIER
|
|
::= { e3Mib 8 }
|
|
|
|
-- Current
|
|
|
|
e3IpmCurrentCritLow NOTIFICATION-TYPE
|
|
OBJECTS { e3IpmInfoSerial, e3IpmMeter, e3IpmIrms }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmCurrentCritLow is triggered when the current
|
|
on the given channel is less than or equal to the configured
|
|
critical low threshold."
|
|
::= { e3IpmTraps 1 }
|
|
|
|
e3IpmCurrentWarnLow NOTIFICATION-TYPE
|
|
OBJECTS { e3IpmInfoSerial, e3IpmMeter, e3IpmIrms }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmCurrentWarnLow is triggered when the current
|
|
on the given channel is less than or equal to the configured
|
|
warn low threshold."
|
|
::= { e3IpmTraps 2 }
|
|
|
|
e3IpmCurrentNormal NOTIFICATION-TYPE
|
|
OBJECTS { e3IpmInfoSerial, e3IpmMeter, e3IpmIrms }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmCurrentNormal is triggered when the current
|
|
on the given channel is not outside any configured
|
|
limits."
|
|
::= { e3IpmTraps 3 }
|
|
|
|
e3IpmCurrentWarnHigh NOTIFICATION-TYPE
|
|
OBJECTS { e3IpmInfoSerial, e3IpmMeter, e3IpmIrms }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmCurrentWarnHigh is triggered when the current
|
|
on the given channel is greater than or equal to the
|
|
configured warn high threshold."
|
|
::= { e3IpmTraps 4 }
|
|
|
|
e3IpmCurrentCritHigh NOTIFICATION-TYPE
|
|
OBJECTS { e3IpmInfoSerial, e3IpmMeter, e3IpmIrms }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmCurrentCritHigh is triggered when the current
|
|
on the given channel is greater than or equal to the
|
|
configured critical high threshold."
|
|
::= { e3IpmTraps 5 }
|
|
|
|
-- Temperature
|
|
|
|
e3IpmTempCritLow NOTIFICATION-TYPE
|
|
OBJECTS { e3IpmInfoSerial, e3IpmSensor, e3IpmSensorTemperatureCelsius }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmTempCritLow is triggered when the temperature
|
|
on the given sensor is less than or equal to the configured
|
|
critical low threshold."
|
|
::= { e3IpmTraps 6 }
|
|
|
|
e3IpmTempWarnLow NOTIFICATION-TYPE
|
|
OBJECTS { e3IpmInfoSerial, e3IpmSensor, e3IpmSensorTemperatureCelsius }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmTempWarnLow is triggered when the temperature
|
|
on the given sensor is less than or equal to the configured
|
|
warn low threshold."
|
|
::= { e3IpmTraps 7 }
|
|
|
|
e3IpmTempNormal NOTIFICATION-TYPE
|
|
OBJECTS { e3IpmInfoSerial, e3IpmSensor, e3IpmSensorTemperatureCelsius }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmTempNormal is triggered when the temperature
|
|
on the given sensor is not outside any configured
|
|
limits."
|
|
::= { e3IpmTraps 8 }
|
|
|
|
e3IpmTempWarnHigh NOTIFICATION-TYPE
|
|
OBJECTS { e3IpmInfoSerial, e3IpmSensor, e3IpmSensorTemperatureCelsius }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmTempWarnHigh is triggered when the temperature
|
|
on the given sensor is greater than or equal to the
|
|
configured warn high threshold."
|
|
::= { e3IpmTraps 9 }
|
|
|
|
e3IpmTempCritHigh NOTIFICATION-TYPE
|
|
OBJECTS { e3IpmInfoSerial, e3IpmSensor, e3IpmSensorTemperatureCelsius }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmTempCritHigh is triggered when the temperature
|
|
on the given sensor is greater than or equal to the
|
|
configured critical high threshold."
|
|
::= { e3IpmTraps 10 }
|
|
|
|
-- Relative Humidity
|
|
|
|
e3IpmRHCritLow NOTIFICATION-TYPE
|
|
OBJECTS { e3IpmInfoSerial, e3IpmSensor, e3IpmSensorHumidity }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmRHCritLow is triggered when the relative humidity
|
|
on the given sensor is less than or equal to the configured
|
|
critical low threshold."
|
|
::= { e3IpmTraps 11 }
|
|
|
|
e3IpmRHWarnLow NOTIFICATION-TYPE
|
|
OBJECTS { e3IpmInfoSerial, e3IpmSensor, e3IpmSensorHumidity }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmRHWarnLow is triggered when the relative humidity
|
|
on the given sensor is less than or equal to the configured
|
|
warn low threshold."
|
|
::= { e3IpmTraps 12 }
|
|
|
|
e3IpmRHNormal NOTIFICATION-TYPE
|
|
OBJECTS { e3IpmInfoSerial, e3IpmSensor, e3IpmSensorHumidity }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmRHNormal is triggered when the relative humidity
|
|
on the given sensor is not outside any configured
|
|
limits."
|
|
::= { e3IpmTraps 13 }
|
|
|
|
e3IpmRHWarnHigh NOTIFICATION-TYPE
|
|
OBJECTS { e3IpmInfoSerial, e3IpmSensor, e3IpmSensorHumidity }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmRHWarnHigh is triggered when the relative humidity
|
|
on the given sensor is greater than or equal to the
|
|
configured warn high threshold."
|
|
::= { e3IpmTraps 14 }
|
|
|
|
e3IpmRHCritHigh NOTIFICATION-TYPE
|
|
OBJECTS { e3IpmInfoSerial, e3IpmSensor, e3IpmSensorHumidity }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmRHCritHigh is triggered when the relative humidity
|
|
on the given sensor is greater than or equal to the
|
|
configured critical high threshold."
|
|
::= { e3IpmTraps 15 }
|
|
|
|
-- RCM Alarms
|
|
|
|
e3IpmRcmAcNormal NOTIFICATION-TYPE
|
|
OBJECTS { e3IpmInfoSerial, e3IpmRcmChannel, e3IpmRcmAc }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmRcmAcNormal is triggered when the AC part of
|
|
the residual current falls below the
|
|
factory-configured limit."
|
|
::= { e3IpmTraps 16 }
|
|
|
|
e3IpmRcmAcCritHigh NOTIFICATION-TYPE
|
|
OBJECTS { e3IpmInfoSerial, e3IpmRcmChannel, e3IpmRcmAc }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmRcmAcCritHigh is triggered when the AC part
|
|
of the residual current is greater than the
|
|
factory-configured limit."
|
|
::= { e3IpmTraps 17 }
|
|
|
|
e3IpmRcmDcNormal NOTIFICATION-TYPE
|
|
OBJECTS { e3IpmInfoSerial, e3IpmRcmChannel, e3IpmRcmDc }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmRcmDcNormal is triggered when the DC part of
|
|
the residual current falls below the
|
|
factory-configured limit."
|
|
::= { e3IpmTraps 18 }
|
|
|
|
e3IpmRcmDcCritHigh NOTIFICATION-TYPE
|
|
OBJECTS { e3IpmInfoSerial, e3IpmRcmChannel, e3IpmRcmDc }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmRcmDcCritHigh is triggered when the DC part
|
|
of the residual current is greater than the
|
|
factory-configured limit."
|
|
::= { e3IpmTraps 19 }
|
|
|
|
END
|