WebGraph-Thermo-Hygrometer-MIB DEFINITIONS ::= BEGIN
|
|||
|
----------------------------------------------------------------
|
|||
|
-- Revison: 1.26
|
|||
|
----------------------------------------------------------------
|
|||
|
-- 03.08.2006 wtWebGraphThermHygroSensorNo korrigiert
|
|||
|
--
|
|||
|
----------------------------------------------------------------
|
|||
|
-- Revison: 1.25
|
|||
|
----------------------------------------------------------------
|
|||
|
-- 28.06.2006 New: Community String Trap
|
|||
|
--
|
|||
|
----------------------------------------------------------------
|
|||
|
-- Revison: 1.24
|
|||
|
----------------------------------------------------------------
|
|||
|
-- 26.07.2005 #57606, WebGraph Thermo-Hygrometer
|
|||
|
-- CRON Zeitfunktion
|
|||
|
----------------------------------------------------------------
|
|||
|
-- Revison: 1.23
|
|||
|
----------------------------------------------------------------
|
|||
|
-- 14.07.2005 #57606, WebGraph Thermo-Hygrometer
|
|||
|
-- FTP Funktionen
|
|||
|
----------------------------------------------------------------
|
|||
|
-- Revison: 1.22
|
|||
|
----------------------------------------------------------------
|
|||
|
-- 17.05.2005 #57606, WebGraph Thermo-Hygrometer
|
|||
|
-- Trap NMS annotations
|
|||
|
----------------------------------------------------------------
|
|||
|
-- Revison: 1.21
|
|||
|
----------------------------------------------------------------
|
|||
|
-- 19.04.2005 #57606, WebGraph Thermo-Hygrometer
|
|||
|
-- Mail Authentication
|
|||
|
----------------------------------------------------------------
|
|||
|
-- Revison: 1.20
|
|||
|
----------------------------------------------------------------
|
|||
|
-- 05.11.2004 #57606, WebGraph Themo-Hygrometer
|
|||
|
-- Neu: Syslog
|
|||
|
--
|
|||
|
----------------------------------------------------------------
|
|||
|
-- Revison: 1.19
|
|||
|
----------------------------------------------------------------
|
|||
|
-- 08.09.2004 #57606 WebGraph Thermo-Hygrometer
|
|||
|
-- Neu:
|
|||
|
-- wtWebGraphThermHygroAlarmRHMin
|
|||
|
-- wtWebGraphThermHygroAlarmRHMax
|
|||
|
-- wtWebGraphThermHygroAlarmRHHysteresis
|
|||
|
-- wtWebGraphThermHygroPortSensorSelect
|
|||
|
-- wtWebGraphThermHygroAlarmDeltaTemp
|
|||
|
-- wtWebGraphThermHygroAlarmAHMin
|
|||
|
-- wtWebGraphThermHygroAlarmAHMax
|
|||
|
----------------------------------------------------------------
|
|||
|
-- Revison: 1.18
|
|||
|
----------------------------------------------------------------
|
|||
|
-- 21.07.2004 #57601/3/4, Webio Digital
|
|||
|
-- Neu:
|
|||
|
-- Diagnosis
|
|||
|
----------------------------------------------------------------
|
|||
|
-- Revison: 1.17
|
|||
|
----------------------------------------------------------------
|
|||
|
-- 28.06.2004 #57630/1/2, Webio Digital
|
|||
|
-- Neu: Puls Mode
|
|||
|
----------------------------------------------------------------
|
|||
|
-- Revison: 1.16
|
|||
|
----------------------------------------------------------------
|
|||
|
-- 16.04.2004 neu: #57632, Webio Digital EA24x24
|
|||
|
--
|
|||
|
-- #57630/1, Webio Digital EA12x12
|
|||
|
-- Neu:
|
|||
|
-- wtWebioEA12x12InputCounterClear
|
|||
|
----------------------------------------------------------------
|
|||
|
-- Revison: 1.15
|
|||
|
----------------------------------------------------------------
|
|||
|
-- 27.02.2004 #57630/1, Webio Digital EA12x12
|
|||
|
-- Neu:
|
|||
|
-- L<>nge erweitert auf 32 Bit:
|
|||
|
-- wtWebioEA12x12InputValue
|
|||
|
-- wtWebioEA12x12OutputValue
|
|||
|
-- wtWebioEA12x12LoadControlView
|
|||
|
-- wtWebioEA12x12LCShutDownView
|
|||
|
-- wtWebioEA12x12SetOutput
|
|||
|
-- wtWebioEA12x12AlarmInputTrigger
|
|||
|
-- wtWebioEA12x12AlarmOutputTrigger
|
|||
|
-- wtWebioEA12x12PortOutputSafetyState
|
|||
|
----------------------------------------------------------------
|
|||
|
-- Revison: 1.14
|
|||
|
----------------------------------------------------------------
|
|||
|
-- 16.02.2004 #57630/1, Webio Digital EA12x12
|
|||
|
-- Neu:
|
|||
|
-- Texte: Location, Contact
|
|||
|
-- SNMP: ColdStart, WarmStart, ComunityString Read/RW
|
|||
|
-- Alarm: ColdStart / WarmStart trigger
|
|||
|
--
|
|||
|
-- #57601, 1xWebThermometer
|
|||
|
-- #57603, 2xWebThermometer
|
|||
|
-- #57604, 8xWebThermometer
|
|||
|
-- Neu:
|
|||
|
-- Alarm Hysterese
|
|||
|
-- Alarm Clear Traps und Mails
|
|||
|
----------------------------------------------------------------
|
|||
|
-- Revison: 1.13
|
|||
|
----------------------------------------------------------------
|
|||
|
-- 05.02.2004 #57601, 1xWebThermometer
|
|||
|
-- #57603, 2xWebThermometer
|
|||
|
-- #57604, 8xWebThermometer
|
|||
|
-- Neu:
|
|||
|
-- Texte: Location, Contact
|
|||
|
-- SNMP: ColdStart, WarmStart, ComunityString Read/RW
|
|||
|
-- Alarm: ColdStart / WarmStart trigger
|
|||
|
----------------------------------------------------------------
|
|||
|
-- Revison: 1.12
|
|||
|
----------------------------------------------------------------
|
|||
|
-- 05.11.2003 #57601, 1xWebThermometer
|
|||
|
-- #57603, 2xWebThermometer
|
|||
|
-- #57604, 8xWebThermometer
|
|||
|
-- Neu:
|
|||
|
-- Mail Option: CSV attachment
|
|||
|
-- Offsetkalibrierung
|
|||
|
-- Alarm: Tcp Client mode
|
|||
|
----------------------------------------------------------------
|
|||
|
-- Revison: 1.11
|
|||
|
----------------------------------------------------------------
|
|||
|
-- 28.10.2003 #57630/1, Webio Digital EA12x12
|
|||
|
-- Neue Feature:
|
|||
|
-- Alarm : TCP Client mode
|
|||
|
-- INPUTS: Pulsfilter
|
|||
|
----------------------------------------------------------------
|
|||
|
-- Revison: 1.10
|
|||
|
----------------------------------------------------------------
|
|||
|
-- 04.07.2003 #57630, Webio Digital EA12x12
|
|||
|
-- Neuer Men<65>baum, neue Bin<69>rmodi
|
|||
|
--
|
|||
|
----------------------------------------------------------------
|
|||
|
-- Revison: 1.09
|
|||
|
----------------------------------------------------------------
|
|||
|
-- 24.03.2003 Trap Enterprise (Type 1, 2) korrigiert
|
|||
|
--
|
|||
|
----------------------------------------------------------------
|
|||
|
-- Revison: 1.08
|
|||
|
----------------------------------------------------------------
|
|||
|
-- 04.03.2003 Abgleich der Sprachversionen DE/US
|
|||
|
--
|
|||
|
----------------------------------------------------------------
|
|||
|
-- Revison: 1.07
|
|||
|
----------------------------------------------------------------
|
|||
|
-- 25.02.2003 Korrektur US: wtWebioEA12x12LoadControl
|
|||
|
----------------------------------------------------------------
|
|||
|
-- Revison: 1.06
|
|||
|
----------------------------------------------------------------
|
|||
|
-- 24.02.2003 Neu:
|
|||
|
-- #57630, Webio EA12x12, LoadControl Group
|
|||
|
-- Korrektur: Trap variable Namen
|
|||
|
----------------------------------------------------------------
|
|||
|
-- Revison: 1.05
|
|||
|
----------------------------------------------------------------
|
|||
|
-- 21.01.2003 Neu:
|
|||
|
-- #57630, Webio EA12x12
|
|||
|
----------------------------------------------------------------
|
|||
|
-- Revison: 1.04
|
|||
|
----------------------------------------------------------------
|
|||
|
-- 02.01.2003 Neu:
|
|||
|
-- #57601, 1xWebThermometer
|
|||
|
-- #57603, 2xWebThermometer, 8 Alarme
|
|||
|
----------------------------------------------------------------
|
|||
|
-- Revison: 1.03
|
|||
|
----------------------------------------------------------------
|
|||
|
-- 21.11.2002 Neu:
|
|||
|
-- #57604, 2xWebThermometer, BOOTP, StartupSite
|
|||
|
-- #57603, 8xWebThermometer, BOOTP, StartupSite
|
|||
|
----------------------------------------------------------------
|
|||
|
-- Revison: 1.02
|
|||
|
----------------------------------------------------------------
|
|||
|
-- 26.07.2002 Neu:
|
|||
|
-- #57604, 2xWebThermometer
|
|||
|
-- #57603, 8xWebThermometer
|
|||
|
--
|
|||
|
|
|||
|
IMPORTS
|
|||
|
|
|||
|
OBJECT-TYPE FROM RFC-1212
|
|||
|
TRAP-TYPE FROM RFC-1215
|
|||
|
DisplayString, PhysAddress FROM RFC1213-MIB
|
|||
|
enterprises, TimeTicks, IpAddress, NetworkAddress FROM RFC1155-SMI;
|
|||
|
|
|||
|
|
|||
|
-- IpAddress ::=
|
|||
|
-- [APPLICATION 0]
|
|||
|
-- IMPLICIT OCTET STRING (SIZE (4))
|
|||
|
-- Counter ::=
|
|||
|
-- [APPLICATION 1]
|
|||
|
-- IMPLICIT INTEGER (0..4294967295)
|
|||
|
-- Gauge ::=
|
|||
|
-- [APPLICATION 2]
|
|||
|
-- IMPLICIT INTEGER (0..4294967295)
|
|||
|
-- TimeTicks ::=
|
|||
|
-- [APPLICATION 3]
|
|||
|
-- IMPLICIT INTEGER (0..4294967295)
|
|||
|
|
|||
|
|
|||
|
-- DisplayString ::= OCTET STRING
|
|||
|
-- PhysAddress ::= OCTET STRING
|
|||
|
|
|||
|
-- internet OBJECT IDENTIFIER ::= { iso org(3) dod(6) 1 }
|
|||
|
-- privat OBJECT IDENTIFIER ::= { internet 4 }
|
|||
|
-- enterprises OBJECT IDENTIFIER ::= { privat 1 }
|
|||
|
|
|||
|
|
|||
|
|
|||
|
-- Wiesemann & Theis Com-Server MIB
|
|||
|
|
|||
|
wut OBJECT IDENTIFIER ::= { enterprises 5040 }
|
|||
|
wtComServer OBJECT IDENTIFIER ::= { wut 1 }
|
|||
|
wtWebio OBJECT IDENTIFIER ::= { wtComServer 2 }
|
|||
|
|
|||
|
|
|||
|
-- wtWebGraph Tree
|
|||
|
|
|||
|
wtWebGraphThermHygro OBJECT IDENTIFIER ::= { wtWebio 9 }
|
|||
|
|
|||
|
-- wtWebGraphThermHygro Tree
|
|||
|
|
|||
|
wtWebGraphThermHygroTemp OBJECT IDENTIFIER ::= { wtWebGraphThermHygro 1 }
|
|||
|
wtWebGraphThermHygroSessCntrl OBJECT IDENTIFIER ::= { wtWebGraphThermHygro 2 }
|
|||
|
wtWebGraphThermHygroConfig OBJECT IDENTIFIER ::= { wtWebGraphThermHygro 3 }
|
|||
|
wtWebGraphThermHygroDiag OBJECT IDENTIFIER ::= { wtWebGraphThermHygro 4 }
|
|||
|
|
|||
|
-- wtWebGraphThermHygroConfig Tree
|
|||
|
|
|||
|
wtWebGraphThermHygroDevice OBJECT IDENTIFIER ::= { wtWebGraphThermHygroConfig 1 }
|
|||
|
wtWebGraphThermHygroPorts OBJECT IDENTIFIER ::= { wtWebGraphThermHygroConfig 2 }
|
|||
|
wtWebGraphThermHygroManufact OBJECT IDENTIFIER ::= { wtWebGraphThermHygroConfig 3 }
|
|||
|
|
|||
|
-- wtWebGraphThermHygroDevice Tree
|
|||
|
|
|||
|
wtWebGraphThermHygroText OBJECT IDENTIFIER ::= { wtWebGraphThermHygroDevice 1 }
|
|||
|
wtWebGraphThermHygroTimeDate OBJECT IDENTIFIER ::= { wtWebGraphThermHygroDevice 2 }
|
|||
|
wtWebGraphThermHygroBasic OBJECT IDENTIFIER ::= { wtWebGraphThermHygroDevice 3 }
|
|||
|
wtWebGraphThermHygroDatalogger OBJECT IDENTIFIER ::= { wtWebGraphThermHygroDevice 4 }
|
|||
|
wtWebGraphThermHygroAlarm OBJECT IDENTIFIER ::= { wtWebGraphThermHygroDevice 5 }
|
|||
|
|
|||
|
-- wtWebGraphThermHygroTimeDate Tree
|
|||
|
|
|||
|
wtWebGraphThermHygroTimeZone OBJECT IDENTIFIER ::= { wtWebGraphThermHygroTimeDate 1 }
|
|||
|
wtWebGraphThermHygroTimeServer OBJECT IDENTIFIER ::= { wtWebGraphThermHygroTimeDate 2 }
|
|||
|
wtWebGraphThermHygroDeviceClock OBJECT IDENTIFIER ::= { wtWebGraphThermHygroTimeDate 3 }
|
|||
|
|
|||
|
-- wtWebGraphThermHygroBasic Tree
|
|||
|
|
|||
|
wtWebGraphThermHygroNetwork OBJECT IDENTIFIER ::= { wtWebGraphThermHygroBasic 1 }
|
|||
|
wtWebGraphThermHygroHTTP OBJECT IDENTIFIER ::= { wtWebGraphThermHygroBasic 2 }
|
|||
|
wtWebGraphThermHygroMail OBJECT IDENTIFIER ::= { wtWebGraphThermHygroBasic 3 }
|
|||
|
wtWebGraphThermHygroSNMP OBJECT IDENTIFIER ::= { wtWebGraphThermHygroBasic 4 }
|
|||
|
wtWebGraphThermHygroUDP OBJECT IDENTIFIER ::= { wtWebGraphThermHygroBasic 5 }
|
|||
|
wtWebGraphThermHygroSyslog OBJECT IDENTIFIER ::= { wtWebGraphThermHygroBasic 6 }
|
|||
|
wtWebGraphThermHygroFTP OBJECT IDENTIFIER ::= { wtWebGraphThermHygroBasic 7 }
|
|||
|
|
|||
|
|
|||
|
|
|||
|
-- wtWebGraphThermHygroTemp Group
|
|||
|
------------------------
|
|||
|
|
|||
|
wtWebGraphThermHygroSensors OBJECT-TYPE
|
|||
|
SYNTAX INTEGER (1..2)
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Anzahl der Sensoren"
|
|||
|
::= { wtWebGraphThermHygroTemp 1 }
|
|||
|
|
|||
|
-- Interface Table
|
|||
|
|
|||
|
wtWebGraphThermHygroSensorTable OBJECT-TYPE
|
|||
|
SYNTAX SEQUENCE OF WtWebGraphThermHygroSensorEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Liste der Sensoren."
|
|||
|
::= { wtWebGraphThermHygroTemp 2 }
|
|||
|
|
|||
|
wtWebGraphThermHygroSensorEntry OBJECT-TYPE
|
|||
|
SYNTAX WtWebGraphThermHygroSensorEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Nummern der Sensoren."
|
|||
|
INDEX { wtWebGraphThermHygroSensorNo }
|
|||
|
::= { wtWebGraphThermHygroSensorTable 1 }
|
|||
|
|
|||
|
WtWebGraphThermHygroSensorEntry ::= SEQUENCE {
|
|||
|
wtWebGraphThermHygroSensorNo INTEGER
|
|||
|
}
|
|||
|
|
|||
|
wtWebGraphThermHygroSensorNo OBJECT-TYPE
|
|||
|
SYNTAX INTEGER (1..2)
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Nummer des Sensors."
|
|||
|
::= { wtWebGraphThermHygroSensorEntry 1 }
|
|||
|
|
|||
|
|
|||
|
-- wtWebGraphThermHygroTempValue Table
|
|||
|
|
|||
|
wtWebGraphThermHygroTempValueTable OBJECT-TYPE
|
|||
|
SYNTAX SEQUENCE OF WtWebGraphThermHygroTempValueEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Liste Sensormesswerte korrespondiernd zu den Kanalnummern."
|
|||
|
::= { wtWebGraphThermHygroTemp 3 }
|
|||
|
|
|||
|
wtWebGraphThermHygroTempValueEntry OBJECT-TYPE
|
|||
|
SYNTAX WtWebGraphThermHygroTempValueEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Messwerte der Sensoren."
|
|||
|
INDEX { wtWebGraphThermHygroSensorNo }
|
|||
|
::= { wtWebGraphThermHygroTempValueTable 1 }
|
|||
|
|
|||
|
WtWebGraphThermHygroTempValueEntry ::= SEQUENCE{
|
|||
|
wtWebGraphThermHygroTempValue OCTET STRING
|
|||
|
}
|
|||
|
|
|||
|
wtWebGraphThermHygroTempValue OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING (SIZE (5))
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Messwert des Sensors, ASCII, 5 Zeichen lang."
|
|||
|
::= { wtWebGraphThermHygroTempValueEntry 1 }
|
|||
|
|
|||
|
-- wtWebGraphThermHygroBinaryTempValue Table
|
|||
|
|
|||
|
wtWebGraphThermHygroBinaryTempValueTable OBJECT-TYPE
|
|||
|
SYNTAX SEQUENCE OF WtWebGraphThermHygroBinaryTempValueEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Liste bin<69>rer Messwerte korrespondiernd zu den Kanalnummern."
|
|||
|
::= { wtWebGraphThermHygroTemp 4 }
|
|||
|
|
|||
|
wtWebGraphThermHygroBinaryTempValueEntry OBJECT-TYPE
|
|||
|
SYNTAX WtWebGraphThermHygroBinaryTempValueEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Bin<69>re Messwerte der Sensoren."
|
|||
|
INDEX { wtWebGraphThermHygroSensorNo }
|
|||
|
::= { wtWebGraphThermHygroBinaryTempValueTable 1 }
|
|||
|
|
|||
|
WtWebGraphThermHygroBinaryTempValueEntry ::= SEQUENCE{
|
|||
|
wtWebGraphThermHygroBinaryTempValue INTEGER
|
|||
|
}
|
|||
|
|
|||
|
wtWebGraphThermHygroBinaryTempValue OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Bin<69>rer Messwert des Sensors in 1/10 Grad Celcius oder 1/10 Prozent,
|
|||
|
vorzeichenbehaftete Zahl, der Wert 0x4FFF6 zeigt einen
|
|||
|
ung<6E>ltigen Messwert an."
|
|||
|
::= { wtWebGraphThermHygroBinaryTempValueEntry 1 }
|
|||
|
|
|||
|
-- wtWebGraphThermHygroSessCntrl Group
|
|||
|
--------------------------------
|
|||
|
|
|||
|
wtWebGraphThermHygroSessCntrlPassword OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Durch Eintrag diese Passworts wird eine Session er<65>ffnet, die durch Schreiben einer 1
|
|||
|
in wtWebGraphThermHygroSessCntrlLogout beendet wird. Gelesen liefert diese Variable einen String der
|
|||
|
L<>nge Null."
|
|||
|
::= { wtWebGraphThermHygroSessCntrl 1 }
|
|||
|
|
|||
|
wtWebGraphThermHygroSessCntrlConfigMode OBJECT-TYPE
|
|||
|
SYNTAX INTEGER {
|
|||
|
wtWebGraphThermHygroSessCntrl-NoSession(0),
|
|||
|
wtWebGraphThermHygroSessCntrl-Session(1)
|
|||
|
}
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Wenn sich das Ger<65>t im SNMP-Konfigurationsmodus befindet, wird der Wert
|
|||
|
1 zur<75>ckgeliefert, ansonsten 0. Ist der ausgelesene Wert 0
|
|||
|
obwohl das Passwort geschrieben wurde, befindet sich das Ger<65>t bereits
|
|||
|
im Configmodus und die Variablen k<>nnen nur gelesen werden."
|
|||
|
::= { wtWebGraphThermHygroSessCntrl 2 }
|
|||
|
|
|||
|
wtWebGraphThermHygroSessCntrlLogout OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Wenn sich das Ger<65>t im Konfigurationsmodus befindet und die Session wurde
|
|||
|
von diesem SNMP Manager er<65>ffnet, kann durch Schreiben einer 1 in diese
|
|||
|
Variable die Session beendet werden und alle Parameter werden gespeichert.
|
|||
|
Durch Schreiben einer 2 werden alle Eingaben wieder verworfen.
|
|||
|
Gelesen liefert diese Variable den Wert 0."
|
|||
|
::= { wtWebGraphThermHygroSessCntrl 3 }
|
|||
|
|
|||
|
wtWebGraphThermHygroSessCntrlAdminPassword OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Dieses Passwort sch<63>tzt den Zugang der Variablen mit Administratorrechten. Es kann nur vom
|
|||
|
Administrator ver<65>ndert werden. Wurde kein Passwort vergeben so ist public das g<>ltige Passwort.
|
|||
|
Gelesen liefert diese Variable einen Null-Pointer."
|
|||
|
::= { wtWebGraphThermHygroSessCntrl 4 }
|
|||
|
|
|||
|
wtWebGraphThermHygroSessCntrlConfigPassword OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Dieses Passwort sch<63>tzt den Zugang der Variablen mit Configuratorrechten. Es kann vom
|
|||
|
Administrator und vom Configurator ver<65>ndert werden. Wurde kein Passwort vergeben so ist
|
|||
|
public das g<>ltige Passwort.Gelesen liefert diese Variable einen Null-Pointer."
|
|||
|
::= { wtWebGraphThermHygroSessCntrl 5 }
|
|||
|
|
|||
|
|
|||
|
-- wtWebGraphThermHygroText Group
|
|||
|
------------------------
|
|||
|
|
|||
|
wtWebGraphThermHygroDeviceName OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Name des Webio's, der userdefinierbar ist."
|
|||
|
::= { wtWebGraphThermHygroText 1 }
|
|||
|
|
|||
|
wtWebGraphThermHygroDeviceText OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Beschreibung des Webio's, die userdefinierbar ist."
|
|||
|
::= { wtWebGraphThermHygroText 2 }
|
|||
|
|
|||
|
wtWebGraphThermHygroDeviceLocation OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Aufstellort des Webio's, die userdefinierbar ist."
|
|||
|
::= { wtWebGraphThermHygroText 3 }
|
|||
|
|
|||
|
wtWebGraphThermHygroDeviceContact OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Kontaktadresse im Servicefall des Webio's, die userdefinierbar ist."
|
|||
|
::= { wtWebGraphThermHygroText 4 }
|
|||
|
|
|||
|
-- wtWebGraphThermHygroTimeZone Group
|
|||
|
----------------------------
|
|||
|
|
|||
|
wtWebGraphThermHygroTzOffsetHrs OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Offset Stunden der Zeitzone (Winterzeit) in Bezug auf UTC."
|
|||
|
::= { wtWebGraphThermHygroTimeZone 1 }
|
|||
|
|
|||
|
wtWebGraphThermHygroTzOffsetMin OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Offset Minuten der Zeitzone (Winterzeit) in Bezug auf UTC."
|
|||
|
::= { wtWebGraphThermHygroTimeZone 2 }
|
|||
|
|
|||
|
wtWebGraphThermHygroTzEnable OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING (SIZE(4))
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Bin<69>r kodierte Bedingung:
|
|||
|
Octet 1: ungenutzt
|
|||
|
Octet 2: ungenutzt
|
|||
|
Octet 3: ungenutzt
|
|||
|
Octet 4:
|
|||
|
Bit 1-7: ungenutzt
|
|||
|
Bit 0 : Apply Timezone"
|
|||
|
::= { wtWebGraphThermHygroTimeZone 3 }
|
|||
|
|
|||
|
wtWebGraphThermHygroStTzOffsetHrs OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Offset Stunden der Zeitzone (Sommerzeit) in Bezug auf UTC."
|
|||
|
::= { wtWebGraphThermHygroTimeZone 4 }
|
|||
|
|
|||
|
wtWebGraphThermHygroStTzOffsetMin OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Offset Minuten der Zeitzone (Sommerzeit) in Bezug auf UTC."
|
|||
|
::= { wtWebGraphThermHygroTimeZone 5 }
|
|||
|
|
|||
|
wtWebGraphThermHygroStTzEnable OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING (SIZE(4))
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Bin<69>r kodierte Bedingung:
|
|||
|
Octet 1: ungenutzt
|
|||
|
Octet 2: ungenutzt
|
|||
|
Octet 3: ungenutzt
|
|||
|
Octet 4:
|
|||
|
Bit 1-7: ungenutzt
|
|||
|
Bit 0 : Apply Summertime"
|
|||
|
::= { wtWebGraphThermHygroTimeZone 6 }
|
|||
|
|
|||
|
wtWebGraphThermHygroStTzStartMonth OBJECT-TYPE
|
|||
|
SYNTAX INTEGER {
|
|||
|
wtWebGraphThermHygroStartMonth-January(1),
|
|||
|
wtWebGraphThermHygroStartMonth-February(2),
|
|||
|
wtWebGraphThermHygroStartMonth-March(3),
|
|||
|
wtWebGraphThermHygroStartMonth-April(4),
|
|||
|
wtWebGraphThermHygroStartMonth-May(5),
|
|||
|
wtWebGraphThermHygroStartMonth-June(6),
|
|||
|
wtWebGraphThermHygroStartMonth-July(7),
|
|||
|
wtWebGraphThermHygroStartMonth-August(8),
|
|||
|
wtWebGraphThermHygroStartMonth-September(9),
|
|||
|
wtWebGraphThermHygroStartMonth-October(10),
|
|||
|
wtWebGraphThermHygroStartMonth-November(11),
|
|||
|
wtWebGraphThermHygroStartMonth-December(12)
|
|||
|
}
|
|||
|
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Monat, in dem von Winterzeit auf Sommerzeit umgestellt wird."
|
|||
|
::= { wtWebGraphThermHygroTimeZone 7 }
|
|||
|
|
|||
|
wtWebGraphThermHygroStTzStartMode OBJECT-TYPE
|
|||
|
SYNTAX INTEGER {
|
|||
|
wtWebGraphThermHygroStartMode-first(1),
|
|||
|
wtWebGraphThermHygroStartMode-second(2),
|
|||
|
wtWebGraphThermHygroStartMode-third(3),
|
|||
|
wtWebGraphThermHygroStartMode-fourth(4),
|
|||
|
wtWebGraphThermHygroStartMode-last(5)
|
|||
|
}
|
|||
|
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Modus des Wochentages, bei dem von Winterzeit auf Sommerzeit umgestellt wird."
|
|||
|
::= { wtWebGraphThermHygroTimeZone 8 }
|
|||
|
|
|||
|
wtWebGraphThermHygroStTzStartWday OBJECT-TYPE
|
|||
|
SYNTAX INTEGER {
|
|||
|
wtWebGraphThermHygroStartWday-Sunday(1),
|
|||
|
wtWebGraphThermHygroStartWday-Monday(2),
|
|||
|
wtWebGraphThermHygroStartWday-Tuesday(3),
|
|||
|
wtWebGraphThermHygroStartWday-Thursday(4),
|
|||
|
wtWebGraphThermHygroStartWday-Wednesday(5),
|
|||
|
wtWebGraphThermHygroStartWday-Friday(6),
|
|||
|
wtWebGraphThermHygroStartWday-Saturday(7)
|
|||
|
}
|
|||
|
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Wochentag, bei dem von Winterzeit auf Sommerzeit umgestellt wird"
|
|||
|
::= { wtWebGraphThermHygroTimeZone 9 }
|
|||
|
|
|||
|
wtWebGraphThermHygroStTzStartHrs OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Stunde, in der die Zeitzone von Winter auf Sommerzeit in Bezug auf UTC
|
|||
|
umgestellt wird."
|
|||
|
::= { wtWebGraphThermHygroTimeZone 10 }
|
|||
|
|
|||
|
wtWebGraphThermHygroStTzStartMin OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Minute, in der die Zeitzone von Winter auf Sommerzeit in Bezug auf UTC
|
|||
|
umgestellt wird."
|
|||
|
::= { wtWebGraphThermHygroTimeZone 11 }
|
|||
|
|
|||
|
wtWebGraphThermHygroStTzStopMonth OBJECT-TYPE
|
|||
|
SYNTAX INTEGER {
|
|||
|
wtWebGraphThermHygroStopMonth-January(1),
|
|||
|
wtWebGraphThermHygroStopMonth-February(2),
|
|||
|
wtWebGraphThermHygroStopMonth-March(3),
|
|||
|
wtWebGraphThermHygroStopMonth-April(4),
|
|||
|
wtWebGraphThermHygroStopMonth-May(5),
|
|||
|
wtWebGraphThermHygroStopMonth-June(6),
|
|||
|
wtWebGraphThermHygroStopMonth-July(7),
|
|||
|
wtWebGraphThermHygroStopMonth-August(8),
|
|||
|
wtWebGraphThermHygroStopMonth-September(9),
|
|||
|
wtWebGraphThermHygroStopMonth-October(10),
|
|||
|
wtWebGraphThermHygroStopMonth-November(11),
|
|||
|
wtWebGraphThermHygroStopMonth-December(12)
|
|||
|
}
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Monat, bei dem von Sommerzeit auf Winterzeit umgestellt wird."
|
|||
|
::= { wtWebGraphThermHygroTimeZone 12 }
|
|||
|
|
|||
|
wtWebGraphThermHygroStTzStopMode OBJECT-TYPE
|
|||
|
SYNTAX INTEGER {
|
|||
|
wtWebGraphThermHygroStopMode-first(1),
|
|||
|
wtWebGraphThermHygroStopMode-second(2),
|
|||
|
wtWebGraphThermHygroStopMode-third(3),
|
|||
|
wtWebGraphThermHygroStopMode-fourth(4),
|
|||
|
wtWebGraphThermHygroStopMode-last(5)
|
|||
|
}
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Modus des Wochentages, bei dem von Sommerzeit auf Winterzeit umgestellt wird."
|
|||
|
::= { wtWebGraphThermHygroTimeZone 13 }
|
|||
|
|
|||
|
wtWebGraphThermHygroStTzStopWday OBJECT-TYPE
|
|||
|
SYNTAX INTEGER {
|
|||
|
wtWebGraphThermHygroStopWday-Sunday(1),
|
|||
|
wtWebGraphThermHygroStopWday-Monday(2),
|
|||
|
wtWebGraphThermHygroStopWday-Tuesday(3),
|
|||
|
wtWebGraphThermHygroStopWday-Thursday(4),
|
|||
|
wtWebGraphThermHygroStopWday-Wednesday(5),
|
|||
|
wtWebGraphThermHygroStopWday-Friday(6),
|
|||
|
wtWebGraphThermHygroStopWday-Saturday(7)
|
|||
|
}
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Wochentage, bei dem von Sommerzeit auf Winterzeit umgestellt wird."
|
|||
|
::= { wtWebGraphThermHygroTimeZone 14 }
|
|||
|
|
|||
|
wtWebGraphThermHygroStTzStopHrs OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Stunde, in der die Zeitzone von Sommer auf Winterzeit in Bezug auf UTC
|
|||
|
umgestellt wird."
|
|||
|
::= { wtWebGraphThermHygroTimeZone 15 }
|
|||
|
|
|||
|
wtWebGraphThermHygroStTzStopMin OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Minute, in der die Zeitzone von Sommer auf Winterzeit in Bezug auf UTC
|
|||
|
umgestellt wird."
|
|||
|
::= { wtWebGraphThermHygroTimeZone 16 }
|
|||
|
|
|||
|
-- wtWebGraphThermHygroTimeServer Group
|
|||
|
----------------------------
|
|||
|
|
|||
|
wtWebGraphThermHygroTimeServer1 OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"IP-Adresse oder Name des 1. Time Servers in ASCII"
|
|||
|
::= { wtWebGraphThermHygroTimeServer 1 }
|
|||
|
|
|||
|
wtWebGraphThermHygroTimeServer2 OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"IP-Adresse oder Name des 2. Time Servers in ASCII"
|
|||
|
::= { wtWebGraphThermHygroTimeServer 2 }
|
|||
|
|
|||
|
wtWebGraphThermHygroTsEnable OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING (SIZE(4))
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Bin<69>r kodierte Bedingung:
|
|||
|
Octet 1: ungenutzt
|
|||
|
Octet 2: ungenutzt
|
|||
|
Octet 3: ungenutzt
|
|||
|
Octet 4:
|
|||
|
Bit 1-7: ungenutzt
|
|||
|
Bit 0 : Apply Time Server"
|
|||
|
::= { wtWebGraphThermHygroTimeServer 3 }
|
|||
|
|
|||
|
wtWebGraphThermHygroTsSyncTime OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Die Abfrage der Timeserver erfolgt zu dieser vollen Stunde (0-23)."
|
|||
|
::= { wtWebGraphThermHygroTimeServer 4 }
|
|||
|
|
|||
|
-- wtWebGraphThermHygroDeviceClock Group
|
|||
|
----------------------------
|
|||
|
|
|||
|
wtWebGraphThermHygroClockHrs OBJECT-TYPE
|
|||
|
SYNTAX INTEGER (0..23)
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Uhrzeit Stunde, unter Ber<65>cksichtigung der Zeitzoneneinstellungen."
|
|||
|
::= { wtWebGraphThermHygroDeviceClock 1 }
|
|||
|
|
|||
|
wtWebGraphThermHygroClockMin OBJECT-TYPE
|
|||
|
SYNTAX INTEGER (0..59)
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Uhrzeit Minute, unter Ber<65>cksichtigung der Zeitzoneneinstellungen."
|
|||
|
::= { wtWebGraphThermHygroDeviceClock 2 }
|
|||
|
|
|||
|
wtWebGraphThermHygroClockDay OBJECT-TYPE
|
|||
|
SYNTAX INTEGER (1..31)
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Datum: Tag des Monats, unter Ber<65>cksichtigung der Zeitzoneneinstellungen."
|
|||
|
::= { wtWebGraphThermHygroDeviceClock 3 }
|
|||
|
|
|||
|
wtWebGraphThermHygroClockMonth OBJECT-TYPE
|
|||
|
SYNTAX INTEGER {
|
|||
|
wtWebGraphThermHygroClockMonth-January(1),
|
|||
|
wtWebGraphThermHygroClockMonth-February(2),
|
|||
|
wtWebGraphThermHygroClockMonth-March(3),
|
|||
|
wtWebGraphThermHygroClockMonth-April(4),
|
|||
|
wtWebGraphThermHygroClockMonth-May(5),
|
|||
|
wtWebGraphThermHygroClockMonth-June(6),
|
|||
|
wtWebGraphThermHygroClockMonth-July(7),
|
|||
|
wtWebGraphThermHygroClockMonth-August(8),
|
|||
|
wtWebGraphThermHygroClockMonth-September(9),
|
|||
|
wtWebGraphThermHygroClockMonth-October(10),
|
|||
|
wtWebGraphThermHygroClockMonth-November(11),
|
|||
|
wtWebGraphThermHygroClockMonth-December(12)
|
|||
|
}
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Datum: Monat, unter Ber<65>cksichtigung der Zeitzoneneinstellungen."
|
|||
|
::= { wtWebGraphThermHygroDeviceClock 4 }
|
|||
|
|
|||
|
wtWebGraphThermHygroClockYear OBJECT-TYPE
|
|||
|
SYNTAX INTEGER (0..65535)
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Datum: Jahr, unter Ber<65>cksichtigung der Zeitzoneneinstellungen."
|
|||
|
::= { wtWebGraphThermHygroDeviceClock 5 }
|
|||
|
|
|||
|
|
|||
|
-- wtWebGraphThermHygroNetwork Group
|
|||
|
------------------------
|
|||
|
|
|||
|
wtWebGraphThermHygroIpAddress OBJECT-TYPE
|
|||
|
SYNTAX IpAddress
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"IP-Adresse des Webio's"
|
|||
|
::= { wtWebGraphThermHygroNetwork 1 }
|
|||
|
|
|||
|
wtWebGraphThermHygroSubnetMask OBJECT-TYPE
|
|||
|
SYNTAX IpAddress
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Subnetmask des Webio's"
|
|||
|
::= { wtWebGraphThermHygroNetwork 2 }
|
|||
|
|
|||
|
wtWebGraphThermHygroGateway OBJECT-TYPE
|
|||
|
SYNTAX IpAddress
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Gateway des Webio's"
|
|||
|
::= { wtWebGraphThermHygroNetwork 3 }
|
|||
|
|
|||
|
wtWebGraphThermHygroDnsServer1 OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"IP-Adresse des 1. DNS Servers in ASCII"
|
|||
|
::= { wtWebGraphThermHygroNetwork 4 }
|
|||
|
|
|||
|
wtWebGraphThermHygroDnsServer2 OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"IP-Adresse des 2. DNS Servers in ASCII"
|
|||
|
::= { wtWebGraphThermHygroNetwork 5 }
|
|||
|
|
|||
|
wtWebGraphThermHygroAddConfig OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Zusatzkonfiguration (1=EIN):
|
|||
|
Octet 1: ungenutzt
|
|||
|
Octet 2: ungenutzt
|
|||
|
Octet 3: ungenutzt
|
|||
|
Octet 4:
|
|||
|
Bit 0: BOOTP disable
|
|||
|
"
|
|||
|
::= { wtWebGraphThermHygroNetwork 6 }
|
|||
|
|
|||
|
-- wtWebGraphThermHygroHTTP Group
|
|||
|
--------------------------------
|
|||
|
|
|||
|
wtWebGraphThermHygroStartup OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Legt die Startseite fest, nur eine Auswahl zul<75>ssig:
|
|||
|
Octet 1: ungenutzt
|
|||
|
Octet 2: ungenutzt
|
|||
|
Octet 3: ungenutzt
|
|||
|
Octet 4:
|
|||
|
Bit 2: user.htm
|
|||
|
Bit 1: home.htm
|
|||
|
Bit 0: index.htm"
|
|||
|
::= { wtWebGraphThermHygroHTTP 1 }
|
|||
|
|
|||
|
wtWebGraphThermHygroGetHeaderEnable OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Wenn freigeschaltet, wird eine Erkennungssequenz nach
|
|||
|
jeder GET-Anfrage der Antwort vorangestellt:
|
|||
|
Octet 1: ungenutzt
|
|||
|
Octet 2: ungenutzt
|
|||
|
Octet 3: ungenutzt
|
|||
|
Octet 4:
|
|||
|
Bit 1-7: ungenutzt
|
|||
|
Bit 0 : GET Header enable"
|
|||
|
::= { wtWebGraphThermHygroHTTP 2 }
|
|||
|
|
|||
|
wtWebGraphThermHygroHttpPort OBJECT-TYPE
|
|||
|
SYNTAX INTEGER (1..65535)
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"HTTP Port, an den die TCP-Anfragen gesendet werden k<>nnen (Default: 80)."
|
|||
|
::= { wtWebGraphThermHygroHTTP 3 }
|
|||
|
|
|||
|
-- wtWebGraphThermHygroMail Group
|
|||
|
--------------------------------
|
|||
|
|
|||
|
wtWebGraphThermHygroMailAdName OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Ger<65>tename f<>r die Mail-Administration."
|
|||
|
::= { wtWebGraphThermHygroMail 1 }
|
|||
|
|
|||
|
wtWebGraphThermHygroMailReply OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Reply-Adresse f<>r den Mailserver."
|
|||
|
::= { wtWebGraphThermHygroMail 2 }
|
|||
|
|
|||
|
wtWebGraphThermHygroMailServer OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Name oder Ip-Adresse des Mailservers."
|
|||
|
::= { wtWebGraphThermHygroMail 3 }
|
|||
|
|
|||
|
wtWebGraphThermHygroMailEnable OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Erlaubt das versenden von Mails:
|
|||
|
Octet 1: ungenutzt
|
|||
|
Octet 2: ungenutzt
|
|||
|
Octet 3: ungenutzt
|
|||
|
Octet 4:
|
|||
|
Bit 1-7: ungenutzt
|
|||
|
Bit 0 : Mail enable"
|
|||
|
::= { wtWebGraphThermHygroMail 4 }
|
|||
|
|
|||
|
wtWebGraphThermHygroMailAuthentication OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING (SIZE (4))
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Auswahl des Authenticationmodi:
|
|||
|
die OCTETS werden bitweise interpretiert, es darf nur ein Bit gesetzt sein.
|
|||
|
Bit 0 entspricht dem LSB.
|
|||
|
OCTET 1: ungenutzt
|
|||
|
OCTET 2: ungenutzt
|
|||
|
OCTET 3: ungenutzt
|
|||
|
OCTET 4: Bit 3-7: ungenutzt
|
|||
|
Bit 2 : POP3 vor SMTP
|
|||
|
Bit 1 : ESMTP, Authentifizierung
|
|||
|
Bit 0 : SMTP, keine Authentifizierung"
|
|||
|
::= { wtWebGraphThermHygroMail 5 }
|
|||
|
|
|||
|
wtWebGraphThermHygroMailAuthUser OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Name des Postfaches / Postfachusers."
|
|||
|
::= { wtWebGraphThermHygroMail 6 }
|
|||
|
|
|||
|
wtWebGraphThermHygroMailAuthPassword OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Passwort zur Identifizierung des Users."
|
|||
|
::= { wtWebGraphThermHygroMail 7 }
|
|||
|
|
|||
|
wtWebGraphThermHygroMailPop3Server OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Name oder Ip-Adresse des POP3 Servers."
|
|||
|
::= { wtWebGraphThermHygroMail 8 }
|
|||
|
|
|||
|
-- wtWebGraphThermHygroSNMP Group
|
|||
|
--------------------------------
|
|||
|
|
|||
|
wtWebGraphThermHygroSnmpCommunityStringRead OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Community string read only"
|
|||
|
::= { wtWebGraphThermHygroSNMP 1 }
|
|||
|
|
|||
|
wtWebGraphThermHygroSnmpCommunityStringReadWrite OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Community string read / write"
|
|||
|
::= { wtWebGraphThermHygroSNMP 2 }
|
|||
|
|
|||
|
wtWebGraphThermHygroSystemTrapManagerIP OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Name oder IP-Adresse des SNMP-Managers, der den System Trap entgegen nimmt."
|
|||
|
::= { wtWebGraphThermHygroSNMP 3 }
|
|||
|
|
|||
|
wtWebGraphThermHygroSystemTrapEnable OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING (SIZE(4))
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Bin<69>r kodierte Triggerbedingungen:
|
|||
|
Octet 1: ungenutzt
|
|||
|
Octet 2: ungenutzt
|
|||
|
Octet 3: ungenutzt
|
|||
|
Octet 4:
|
|||
|
Bit 0: ColdStart
|
|||
|
Bit 1: WarmStart
|
|||
|
Bit 2-7: ungenutzt"
|
|||
|
::= { wtWebGraphThermHygroSNMP 4 }
|
|||
|
|
|||
|
wtWebGraphThermHygroSnmpEnable OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Bit 0 schaltet SNMP frei:
|
|||
|
Octet 1: ungenutzt
|
|||
|
Octet 2: ungenutzt
|
|||
|
Octet 3: ungenutzt
|
|||
|
Octet 4:
|
|||
|
Bit 1-7: ungenutzt
|
|||
|
Bit 0 : SNMP enable"
|
|||
|
::= { wtWebGraphThermHygroSNMP 5 }
|
|||
|
|
|||
|
wtWebGraphThermHygroSnmpCommunityStringTrap OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Community string der Traps."
|
|||
|
::= { wtWebGraphThermHygroSNMP 6 }
|
|||
|
|
|||
|
|
|||
|
-- wtWebGraphThermHygroUDP Group
|
|||
|
--------------------------------
|
|||
|
|
|||
|
wtWebGraphThermHygroUdpPort OBJECT-TYPE
|
|||
|
SYNTAX INTEGER (1..65535)
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Udp Port, an den die Udp-Anfragen GET Single gesendet werden k<>nnen"
|
|||
|
::= { wtWebGraphThermHygroUDP 1 }
|
|||
|
|
|||
|
wtWebGraphThermHygroUdpEnable OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Schaltet UDP frei:
|
|||
|
Octet 1: ungenutzt
|
|||
|
Octet 2: ungenutzt
|
|||
|
Octet 3: ungenutzt
|
|||
|
Octet 4:
|
|||
|
Bit 1-7: ungenutzt
|
|||
|
Bit 0 : UDP enable"
|
|||
|
::= { wtWebGraphThermHygroUDP 2 }
|
|||
|
|
|||
|
-- wtWebGraphThermHygroSyslog Group
|
|||
|
--------------------------------
|
|||
|
|
|||
|
wtWebGraphThermHygroSyslogServerIP OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Name oder IP-Adresse des Syslog-Servers, der die Syslog-Nachricht entgegen nimmt."
|
|||
|
::= { wtWebGraphThermHygroSyslog 1 }
|
|||
|
|
|||
|
wtWebGraphThermHygroSyslogServerPort OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Portnummer des Syslog-Servers, default ist 514."
|
|||
|
::= { wtWebGraphThermHygroSyslog 2 }
|
|||
|
|
|||
|
wtWebGraphThermHygroSyslogSystemMessagesEnable OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING (SIZE(4))
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Bin<69>r kodierte Triggerbedingungen:
|
|||
|
Octet 1: ungenutzt
|
|||
|
Octet 2: ungenutzt
|
|||
|
Octet 3: ungenutzt
|
|||
|
Octet 4:
|
|||
|
Bit 0: ColdStart
|
|||
|
Bit 1: WarmStart
|
|||
|
Bit 2: Diag Messages
|
|||
|
Bit 3-7: ungenutzt"
|
|||
|
::= { wtWebGraphThermHygroSyslog 3 }
|
|||
|
|
|||
|
wtWebGraphThermHygroSyslogEnable OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Bit 0 schaltet Syslog frei:
|
|||
|
Octet 1: ungenutzt
|
|||
|
Octet 2: ungenutzt
|
|||
|
Octet 3: ungenutzt
|
|||
|
Octet 4:
|
|||
|
Bit 1-7: ungenutzt
|
|||
|
Bit 0 : Syslog enable"
|
|||
|
::= { wtWebGraphThermHygroSyslog 4 }
|
|||
|
|
|||
|
-- wtWebGraphThermHygroFTP Group
|
|||
|
--------------------------------
|
|||
|
|
|||
|
wtWebGraphThermHygroFTPServerIP OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Name oder IP-Adresse des FTP-Servers, der die FTP-Nachricht entgegen nimmt."
|
|||
|
::= { wtWebGraphThermHygroFTP 1 }
|
|||
|
|
|||
|
wtWebGraphThermHygroFTPServerControlPort OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Portnummer des Kontrollports des FTP-Servers, default ist 21."
|
|||
|
::= { wtWebGraphThermHygroFTP 2 }
|
|||
|
|
|||
|
wtWebGraphThermHygroFTPUserName OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"FTP Loggin: Name des Anwenders."
|
|||
|
::= { wtWebGraphThermHygroFTP 3 }
|
|||
|
|
|||
|
wtWebGraphThermHygroFTPPassword OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"FTP Loggin: Passwort des Anwenders."
|
|||
|
::= { wtWebGraphThermHygroFTP 4 }
|
|||
|
|
|||
|
wtWebGraphThermHygroFTPAccount OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"FTP Loggin: Account-Name des Anwenderkontos."
|
|||
|
::= { wtWebGraphThermHygroFTP 5 }
|
|||
|
|
|||
|
wtWebGraphThermHygroFTPOption OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Bit 0 schaltet den FTP Server in den Passiv-Modus,
|
|||
|
der Client kontrolliert die Datenverbindung allein:
|
|||
|
Octet 1: ungenutzt
|
|||
|
Octet 2: ungenutzt
|
|||
|
Octet 3: ungenutzt
|
|||
|
Octet 4:
|
|||
|
Bit 1-7: ungenutzt
|
|||
|
Bit 0 : PASV enable"
|
|||
|
::= { wtWebGraphThermHygroFTP 6 }
|
|||
|
|
|||
|
wtWebGraphThermHygroFTPEnable OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Bit 0 schaltet FTP frei:
|
|||
|
Octet 1: ungenutzt
|
|||
|
Octet 2: ungenutzt
|
|||
|
Octet 3: ungenutzt
|
|||
|
Octet 4:
|
|||
|
Bit 1-7: ungenutzt
|
|||
|
Bit 0 : FTP enable"
|
|||
|
::= { wtWebGraphThermHygroFTP 7 }
|
|||
|
|
|||
|
|
|||
|
-- wtWebGraphThermHygroDatalogger Group
|
|||
|
--------------------------------
|
|||
|
|
|||
|
wtWebGraphThermHygroLoggerTimebase OBJECT-TYPE
|
|||
|
SYNTAX INTEGER {
|
|||
|
wtWebGraphThermHygroDatalogger-1Min(1),
|
|||
|
wtWebGraphThermHygroDatalogger-5Min(2),
|
|||
|
wtWebGraphThermHygroDatalogger-15Min(3),
|
|||
|
wtWebGraphThermHygroDatalogger-60Min(4)
|
|||
|
}
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Zeitbasis des Dataloggers"
|
|||
|
::= { wtWebGraphThermHygroDatalogger 1 }
|
|||
|
|
|||
|
wtWebGraphThermHygroLoggerSensorSel OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING (SIZE(4))
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Bin<69>r kodierte Triggerbedingungen:
|
|||
|
Octet 1: ungenutzt
|
|||
|
Octet 2: ungenutzt
|
|||
|
Octet 3: ungenutzt
|
|||
|
Octet 4:
|
|||
|
Bit 0 : Sensor 1
|
|||
|
Bit 1 : Sensor 2
|
|||
|
Bit 2-7: ungenutzt"
|
|||
|
::= { wtWebGraphThermHygroDatalogger 2 }
|
|||
|
|
|||
|
wtWebGraphThermHygroDisplaySensorSel OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING (SIZE(4))
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Die hier ausgew<65>hlten Sensoren werden grafisch angezeigt:
|
|||
|
Octet 1: ungenutzt
|
|||
|
Octet 2: ungenutzt
|
|||
|
Octet 3: ungenutzt
|
|||
|
Octet 4:
|
|||
|
Bit 0: Sensor 1
|
|||
|
Bit 1: Sensor 2
|
|||
|
Bit 2-7: ungenutzt"
|
|||
|
::= { wtWebGraphThermHygroDatalogger 3 }
|
|||
|
|
|||
|
-- Graph Sensor Color Table
|
|||
|
|
|||
|
wtWebGraphThermHygroSensorColorTable OBJECT-TYPE
|
|||
|
SYNTAX SEQUENCE OF WtWebGraphThermHygroSensorColorEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Liste der Sensorfarben in der grafischen Darstellung."
|
|||
|
::= { wtWebGraphThermHygroDatalogger 4 }
|
|||
|
|
|||
|
wtWebGraphThermHygroSensorColorEntry OBJECT-TYPE
|
|||
|
SYNTAX WtWebGraphThermHygroSensorColorEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Nummern der Sensoren."
|
|||
|
INDEX { wtWebGraphThermHygroSensorNo }
|
|||
|
::= { wtWebGraphThermHygroSensorColorTable 1 }
|
|||
|
|
|||
|
WtWebGraphThermHygroSensorColorEntry ::= SEQUENCE {
|
|||
|
wtWebGraphThermHygroSensorColor OCTET STRING
|
|||
|
}
|
|||
|
|
|||
|
wtWebGraphThermHygroSensorColor OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING (SIZE(3))
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Farbe des Sensors in der grafischen Darstellung."
|
|||
|
::= { wtWebGraphThermHygroSensorColorEntry 1 }
|
|||
|
|
|||
|
wtWebGraphThermHygroAutoScaleEnable OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Bit 0 schaltet Vertical Auto Scale frei:
|
|||
|
Octet 1: ungenutzt
|
|||
|
Octet 2: ungenutzt
|
|||
|
Octet 3: ungenutzt
|
|||
|
Octet 4:
|
|||
|
Bit 1-7: ungenutzt
|
|||
|
Bit 0 : Auto Scale enable"
|
|||
|
::= { wtWebGraphThermHygroDatalogger 5 }
|
|||
|
|
|||
|
wtWebGraphThermHygroVerticalUpperLimit OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Definiert die maximal sichtbare Temperatur f<>r die grafische Darstellung.
|
|||
|
Temperatur in Grad mit maximal 2 Nachkommastellen."
|
|||
|
::= { wtWebGraphThermHygroDatalogger 6 }
|
|||
|
|
|||
|
wtWebGraphThermHygroVerticalLowerLimit OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Definiert die Minal sichtbare Temperatur f<>r die grafische Darstellung.
|
|||
|
Temperatur in Grad mit maximal 2 Nachkommastellen."
|
|||
|
::= { wtWebGraphThermHygroDatalogger 7 }
|
|||
|
|
|||
|
wtWebGraphThermHygroHorizontalZoom OBJECT-TYPE
|
|||
|
SYNTAX INTEGER {
|
|||
|
wtWebGraphThermHygroZoom-25Min(1),
|
|||
|
wtWebGraphThermHygroZoom-75Min(2),
|
|||
|
wtWebGraphThermHygroZoom-5Std(3),
|
|||
|
wtWebGraphThermHygroZoom-30Std(4),
|
|||
|
wtWebGraphThermHygroZoom-5Tage(5),
|
|||
|
wtWebGraphThermHygroZoom-25Tage(6)
|
|||
|
}
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Definiert den default Zoom."
|
|||
|
::= { wtWebGraphThermHygroDatalogger 8 }
|
|||
|
|
|||
|
-- wtWebGraphThermHygroAlarm Group
|
|||
|
----------------------------
|
|||
|
|
|||
|
wtWebGraphThermHygroAlarmCount OBJECT-TYPE
|
|||
|
SYNTAX INTEGER (1..8)
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Anzahl der unabh<62>ngigen Alarme."
|
|||
|
::= { wtWebGraphThermHygroAlarm 1 }
|
|||
|
|
|||
|
-- Alarm Interface Table
|
|||
|
|
|||
|
wtWebGraphThermHygroAlarmIfTable OBJECT-TYPE
|
|||
|
SYNTAX SEQUENCE OF WtWebGraphThermHygroAlarmIfEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Liste der Alarmindizes."
|
|||
|
::= { wtWebGraphThermHygroAlarm 2 }
|
|||
|
|
|||
|
wtWebGraphThermHygroAlarmIfEntry OBJECT-TYPE
|
|||
|
SYNTAX WtWebGraphThermHygroAlarmIfEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Nummern der Alarme."
|
|||
|
INDEX { wtWebGraphThermHygroAlarmNo }
|
|||
|
::= { wtWebGraphThermHygroAlarmIfTable 1 }
|
|||
|
|
|||
|
WtWebGraphThermHygroAlarmIfEntry ::= SEQUENCE {
|
|||
|
wtWebGraphThermHygroAlarmNo INTEGER
|
|||
|
}
|
|||
|
|
|||
|
wtWebGraphThermHygroAlarmNo OBJECT-TYPE
|
|||
|
SYNTAX INTEGER (1..8)
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Nummer des Alarms."
|
|||
|
::= { wtWebGraphThermHygroAlarmIfEntry 1 }
|
|||
|
|
|||
|
-- Alarm Table
|
|||
|
|
|||
|
wtWebGraphThermHygroAlarmTable OBJECT-TYPE
|
|||
|
SYNTAX SEQUENCE OF WtWebGraphThermHygroAlarmEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Liste der Einstellungen abh<62>ngig von der Alarmnummer."
|
|||
|
::= { wtWebGraphThermHygroAlarm 3 }
|
|||
|
|
|||
|
wtWebGraphThermHygroAlarmEntry OBJECT-TYPE
|
|||
|
SYNTAX WtWebGraphThermHygroAlarmEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Alarm-Parameter der einzelnen Alarme."
|
|||
|
INDEX { wtWebGraphThermHygroAlarmNo }
|
|||
|
::= { wtWebGraphThermHygroAlarmTable 1 }
|
|||
|
|
|||
|
WtWebGraphThermHygroAlarmEntry ::= SEQUENCE {
|
|||
|
wtWebGraphThermHygroAlarmTrigger OCTET STRING,
|
|||
|
wtWebGraphThermHygroAlarmMin OCTET STRING,
|
|||
|
wtWebGraphThermHygroAlarmMax OCTET STRING,
|
|||
|
wtWebGraphThermHygroAlarmHysteresis OCTET STRING,
|
|||
|
wtWebGraphThermHygroAlarmDelay OCTET STRING,
|
|||
|
wtWebGraphThermHygroAlarmInterval OCTET STRING,
|
|||
|
wtWebGraphThermHygroAlarmEnable OCTET STRING,
|
|||
|
wtWebGraphThermHygroAlarmEMailAddr OCTET STRING,
|
|||
|
wtWebGraphThermHygroAlarmMailSubject OCTET STRING,
|
|||
|
wtWebGraphThermHygroAlarmMailText OCTET STRING,
|
|||
|
wtWebGraphThermHygroAlarmManagerIP OCTET STRING,
|
|||
|
wtWebGraphThermHygroAlarmTrapText OCTET STRING,
|
|||
|
wtWebGraphThermHygroAlarmMailOptions OCTET STRING,
|
|||
|
wtWebGraphThermHygroAlarmTcpIpAddr OCTET STRING,
|
|||
|
wtWebGraphThermHygroAlarmTcpPort INTEGER,
|
|||
|
wtWebGraphThermHygroAlarmTcpText OCTET STRING,
|
|||
|
wtWebGraphThermHygroAlarmClearMailSubject OCTET STRING,
|
|||
|
wtWebGraphThermHygroAlarmClearMailText OCTET STRING,
|
|||
|
wtWebGraphThermHygroAlarmClearTrapText OCTET STRING,
|
|||
|
wtWebGraphThermHygroAlarmClearTcpText OCTET STRING,
|
|||
|
wtWebGraphThermHygroAlarmDeltaTemp OCTET STRING,
|
|||
|
wtWebGraphThermHygroAlarmRHMin OCTET STRING,
|
|||
|
wtWebGraphThermHygroAlarmRHMax OCTET STRING,
|
|||
|
wtWebGraphThermHygroAlarmRHHysteresis OCTET STRING,
|
|||
|
wtWebGraphThermHygroAlarmAHMin OCTET STRING,
|
|||
|
wtWebGraphThermHygroAlarmAHMax OCTET STRING,
|
|||
|
wtWebGraphThermHygroAlarmSyslogIpAddr OCTET STRING,
|
|||
|
wtWebGraphThermHygroAlarmSyslogPort INTEGER,
|
|||
|
wtWebGraphThermHygroAlarmSyslogText OCTET STRING,
|
|||
|
wtWebGraphThermHygroAlarmSyslogClearText OCTET STRING,
|
|||
|
wtWebGraphThermHygroAlarmFtpDataPort OCTET STRING,
|
|||
|
wtWebGraphThermHygroAlarmFtpFileName OCTET STRING,
|
|||
|
wtWebGraphThermHygroAlarmFtpText OCTET STRING,
|
|||
|
wtWebGraphThermHygroAlarmFtpClearText OCTET STRING,
|
|||
|
wtWebGraphThermHygroAlarmFtpOption OCTET STRING,
|
|||
|
wtWebGraphThermHygroAlarmTimerCron OCTET STRING
|
|||
|
|
|||
|
}
|
|||
|
|
|||
|
wtWebGraphThermHygroAlarmTrigger OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING (SIZE(4))
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Bin<69>r kodierte Triggerbedingungen:
|
|||
|
Octet 1: ungenutzt
|
|||
|
Octet 2: ungenutzt
|
|||
|
Octet 3:
|
|||
|
Bit 0: Timer
|
|||
|
Bit 1: ColdStart
|
|||
|
Bit 2: WarmStart
|
|||
|
Bit 3: Sensor lost
|
|||
|
Bit 4-7 ungenutzt
|
|||
|
Octet 4:
|
|||
|
Bit 0: Sensor 1
|
|||
|
Bit 1: Sensor 2
|
|||
|
Bit 2-7: ungenutzt"
|
|||
|
::= { wtWebGraphThermHygroAlarmEntry 1 }
|
|||
|
|
|||
|
wtWebGraphThermHygroAlarmMin OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Minimum Temperatur in Grad mit maximal 2 Nachkommastellen."
|
|||
|
::= { wtWebGraphThermHygroAlarmEntry 2 }
|
|||
|
|
|||
|
wtWebGraphThermHygroAlarmMax OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Maximum Temperatur in Grad mit maximal 2 Nachkommastellen."
|
|||
|
::= { wtWebGraphThermHygroAlarmEntry 3 }
|
|||
|
|
|||
|
wtWebGraphThermHygroAlarmHysteresis OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Bei <20>berschreiten der Temperatur Min+Hyst. und Unterschreiten der Temperatur Max-Hyst.
|
|||
|
wird der Alarm gel<65>scht: pos. Temperaturdifferenz in Grad mit maximal 2 Nachkommastellen."
|
|||
|
::= { wtWebGraphThermHygroAlarmEntry 4 }
|
|||
|
|
|||
|
wtWebGraphThermHygroAlarmDelay OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Der Alarm wird erst ausgel<65>st, wenn f<>r die Dauer dieser Zeit
|
|||
|
die Alarmbedingungen erf<72>llt sind (Zeit in Minuten)."
|
|||
|
::= { wtWebGraphThermHygroAlarmEntry 5 }
|
|||
|
|
|||
|
wtWebGraphThermHygroAlarmInterval OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Sendeintervall von Alarmmeldungen."
|
|||
|
::= { wtWebGraphThermHygroAlarmEntry 6 }
|
|||
|
|
|||
|
wtWebGraphThermHygroAlarmEnable OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING (SIZE(4))
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Bin<69>r kodierte Alarmfreischaltung:
|
|||
|
Octet 1: ungenutzt
|
|||
|
Octet 2: ungenutzt
|
|||
|
Octet 3: ungenutzt
|
|||
|
Octet 4:
|
|||
|
Bit 0: Mail Enable
|
|||
|
Bit 1: SNMP Trap enable
|
|||
|
Bit 2: TCP Client enable"
|
|||
|
::= { wtWebGraphThermHygroAlarmEntry 7 }
|
|||
|
|
|||
|
wtWebGraphThermHygroAlarmEMailAddr OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"E-Mail Adresse, an die die Alarmmail gesendet werden soll."
|
|||
|
::= { wtWebGraphThermHygroAlarmEntry 8 }
|
|||
|
|
|||
|
wtWebGraphThermHygroAlarmMailSubject OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Betreffzeile der Alarmmail."
|
|||
|
::= { wtWebGraphThermHygroAlarmEntry 9 }
|
|||
|
|
|||
|
wtWebGraphThermHygroAlarmMailText OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Text der Alarmmail: <Tn> liefert die aktuelle Temperatur; n = 1..8.
|
|||
|
<Z> liefert die aktuelle Zeit."
|
|||
|
::= { wtWebGraphThermHygroAlarmEntry 10 }
|
|||
|
|
|||
|
wtWebGraphThermHygroAlarmManagerIP OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Name oder IP-Adresse des SNMP-Managers, der den Trap entgegen nimmt."
|
|||
|
::= { wtWebGraphThermHygroAlarmEntry 11 }
|
|||
|
|
|||
|
wtWebGraphThermHygroAlarmTrapText OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Dieser Text wird im Trapbody gesendet."
|
|||
|
::= { wtWebGraphThermHygroAlarmEntry 12 }
|
|||
|
|
|||
|
wtWebGraphThermHygroAlarmMailOptions OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING (SIZE(4))
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Bin<69>r kodierte Optionen:
|
|||
|
Octet 1: ungenutzt
|
|||
|
Octet 2: ungenutzt
|
|||
|
Octet 3: ungenutzt
|
|||
|
Octet 4:
|
|||
|
Bit 0 : Attach Thermo.csv Enable
|
|||
|
Bit 1 : CSV-Data_since_last_report
|
|||
|
Bit 2-7: ungenutzt"
|
|||
|
::= { wtWebGraphThermHygroAlarmEntry 13 }
|
|||
|
|
|||
|
wtWebGraphThermHygroAlarmTcpIpAddr OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"IP-Adresse des Ger<65>tes, dass eine TCP-Nachricht empfangen soll."
|
|||
|
::= { wtWebGraphThermHygroAlarmEntry 14 }
|
|||
|
|
|||
|
wtWebGraphThermHygroAlarmTcpPort OBJECT-TYPE
|
|||
|
SYNTAX INTEGER (1..65535)
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Portnummer des Ger<65>tes, dass eine TCP-Nachricht empfangen soll."
|
|||
|
::= { wtWebGraphThermHygroAlarmEntry 15 }
|
|||
|
|
|||
|
wtWebGraphThermHygroAlarmTcpText OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Dieser Text wird im TCP Trapbody gesendet."
|
|||
|
::= { wtWebGraphThermHygroAlarmEntry 16 }
|
|||
|
|
|||
|
wtWebGraphThermHygroAlarmClearMailSubject OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Betreffzeile der Alarm Clear Mail."
|
|||
|
::= { wtWebGraphThermHygroAlarmEntry 17 }
|
|||
|
|
|||
|
wtWebGraphThermHygroAlarmClearMailText OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Text der Alarm Clear Mail: <Tn> liefert die aktuelle Temperatur; n = 1..8.
|
|||
|
<Z> liefert die aktuelle Zeit."
|
|||
|
::= { wtWebGraphThermHygroAlarmEntry 18 }
|
|||
|
|
|||
|
wtWebGraphThermHygroAlarmClearTrapText OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Dieser Text wird im Trapbody gesendet."
|
|||
|
::= { wtWebGraphThermHygroAlarmEntry 19 }
|
|||
|
|
|||
|
wtWebGraphThermHygroAlarmClearTcpText OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Dieser Text wird im TCP Trapbody gesendet."
|
|||
|
::= { wtWebGraphThermHygroAlarmEntry 20 }
|
|||
|
|
|||
|
wtWebGraphThermHygroAlarmDeltaTemp OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Maximale Temperatur<75>nderung in Grad/min mit maximal 2 Nachkommastellen.
|
|||
|
Es wird ein Mittelwert einer Periode von 5 Minuten verglichen."
|
|||
|
::= { wtWebGraphThermHygroAlarmEntry 21 }
|
|||
|
|
|||
|
wtWebGraphThermHygroAlarmRHMin OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Minimum rel. Feuchte in Prozent mit maximal 2 Nachkommastellen."
|
|||
|
::= { wtWebGraphThermHygroAlarmEntry 22 }
|
|||
|
|
|||
|
wtWebGraphThermHygroAlarmRHMax OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Maximum rel.Feuchte in Prozent mit maximal 2 Nachkommastellen."
|
|||
|
::= { wtWebGraphThermHygroAlarmEntry 23 }
|
|||
|
|
|||
|
wtWebGraphThermHygroAlarmRHHysteresis OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Hysterese rel. Feuchte in Prozent mit maximal 2 Nachkommastellen."
|
|||
|
::= { wtWebGraphThermHygroAlarmEntry 24 }
|
|||
|
|
|||
|
wtWebGraphThermHygroAlarmAHMin OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Minimum abs. Feuchte in g/(m*m*m) mit maximal 2 Nachkommastellen."
|
|||
|
::= { wtWebGraphThermHygroAlarmEntry 25 }
|
|||
|
|
|||
|
wtWebGraphThermHygroAlarmAHMax OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Maximum abs. Feuchte in g/(m*m*m) mit maximal 2 Nachkommastellen."
|
|||
|
::= { wtWebGraphThermHygroAlarmEntry 26 }
|
|||
|
|
|||
|
wtWebGraphThermHygroAlarmSyslogIpAddr OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"IP-Adresse des Ger<65>tes, dass eine Syslog-Nachricht empfangen soll."
|
|||
|
::= { wtWebGraphThermHygroAlarmEntry 27 }
|
|||
|
|
|||
|
wtWebGraphThermHygroAlarmSyslogPort OBJECT-TYPE
|
|||
|
SYNTAX INTEGER (1..65535)
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Portnummer des Ger<65>tes, dass eine Syslog-Nachricht empfangen soll, default Port ist 514."
|
|||
|
::= { wtWebGraphThermHygroAlarmEntry 28 }
|
|||
|
|
|||
|
wtWebGraphThermHygroAlarmSyslogText OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Jede Syslog-Nachricht beginnt mit einem Priorit<69>tsschl<68>ssel, einem Zeitstempel und der Host Ip-Nummer gem<65><6D> RFC3164.
|
|||
|
Dieser Text wird im darauf folgenden Syslog-Nachrichtenteil gesendet."
|
|||
|
::= { wtWebGraphThermHygroAlarmEntry 29 }
|
|||
|
|
|||
|
wtWebGraphThermHygroAlarmSyslogClearText OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Jede Syslog-Nachricht beginnt mit einem Priorit<69>tsschl<68>ssel, einem Zeitstempel und der Host Ip-Nummer gem<65><6D> RFC3164.
|
|||
|
Dieser Text wird im darauf folgenden Syslog-Nachrichtenteil gesendet."
|
|||
|
::= { wtWebGraphThermHygroAlarmEntry 30 }
|
|||
|
|
|||
|
wtWebGraphThermHygroAlarmFtpDataPort OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Lokaler Datenport: 1..65535 oder AUTO: der n<>chste ungenutzte Port wird automatisch zugewiesen."
|
|||
|
::= { wtWebGraphThermHygroAlarmEntry 31 }
|
|||
|
|
|||
|
wtWebGraphThermHygroAlarmFtpFileName OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Der File Name kann auch Pfadinformationen enthalten."
|
|||
|
::= { wtWebGraphThermHygroAlarmEntry 32 }
|
|||
|
|
|||
|
wtWebGraphThermHygroAlarmFtpText OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Dieser Text wird in die angegebene Datei geschrieben."
|
|||
|
::= { wtWebGraphThermHygroAlarmEntry 33 }
|
|||
|
|
|||
|
wtWebGraphThermHygroAlarmFtpClearText OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Dieser Text wird in die angegebene Datei geschrieben."
|
|||
|
::= { wtWebGraphThermHygroAlarmEntry 34 }
|
|||
|
|
|||
|
wtWebGraphThermHygroAlarmFtpOptions OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING (SIZE(4))
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Bin<69>r kodierte Optionen, nur eine Option darf eingeschaltet sein:
|
|||
|
STORE = Datei ersetzen
|
|||
|
APPEND = Nachrichten ans Dateiende anh<6E>ngen
|
|||
|
|
|||
|
Octet 1: ungenutzt
|
|||
|
Octet 2: ungenutzt
|
|||
|
Octet 3: ungenutzt
|
|||
|
Octet 4:
|
|||
|
Bit 0 : STORE
|
|||
|
Bit 1 : APPEND
|
|||
|
Bit 2-7: ungenutzt"
|
|||
|
::= { wtWebGraphThermHygroAlarmEntry 35 }
|
|||
|
|
|||
|
wtWebGraphThermHygroAlarmTimerCron OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Diser Eintrag enth<74>lt 5 Leerzeichen- oder Tab-getrente Felder zur Definition von zeitgesteuerten
|
|||
|
Ausgabe von Alarmnachrichten. Jedes der 5 Felder muss mit der aktuelle Zeit <20>bereinstimmen, um
|
|||
|
das Senden einer Nachricht auszul<75>sen, Wochentag und Monatstag werden getrennt ausgewertet.
|
|||
|
Feld m<>glicher Zahlenbereich
|
|||
|
1: Minuten 0-59
|
|||
|
2. Stunden 0-23, 0 ist Mitternacht
|
|||
|
3: Monatstag 1-31
|
|||
|
4: Monat 1-12
|
|||
|
5: Wochentag 0-6, 0 ist Sonntag
|
|||
|
|
|||
|
F<>r jedes Feld kann nun angegeben werden:
|
|||
|
- eine ganze Zahl aus dem angegebenen Zahlenbereich
|
|||
|
- ein Teil-Zahlenbereich (wie z.B. 1-5) innerhalb des angegebenen Zahlenbereichs
|
|||
|
- eine mit Komma getrennte Liste von ganzen Zahlen oder Tei-Zahlenbereichen (wie z.B. 2,4-6,8,10)
|
|||
|
- ein Stern * (deckt den gesamten erlaubten Bereich ab)
|
|||
|
- ein / gibt die Schrittweite bei Teil-Zahlenbereichen an (z.B. 0-59/2 jede zweite Minute)."
|
|||
|
::= { wtWebGraphThermHygroAlarmEntry 36 }
|
|||
|
|
|||
|
-- wtWebGraphThermHygroPorts Group
|
|||
|
----------------------------
|
|||
|
|
|||
|
-- Table
|
|||
|
|
|||
|
wtWebGraphThermHygroPortTable OBJECT-TYPE
|
|||
|
SYNTAX SEQUENCE OF WtWebGraphThermHygroPortEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Liste der Einstellungen abh<62>ngig von der Sensornummer."
|
|||
|
::= { wtWebGraphThermHygroPorts 1 }
|
|||
|
|
|||
|
wtWebGraphThermHygroPortEntry OBJECT-TYPE
|
|||
|
SYNTAX WtWebGraphThermHygroPortEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Sensor-Parameter der einzelnen Sensoren."
|
|||
|
INDEX { wtWebGraphThermHygroSensorNo }
|
|||
|
::= { wtWebGraphThermHygroPortTable 1 }
|
|||
|
|
|||
|
WtWebGraphThermHygroPortEntry ::= SEQUENCE {
|
|||
|
wtWebGraphThermHygroPortName OCTET STRING,
|
|||
|
wtWebGraphThermHygroPortText OCTET STRING,
|
|||
|
wtWebGraphThermHygroPortOffset1 OCTET STRING,
|
|||
|
wtWebGraphThermHygroPortTemperature1 OCTET STRING,
|
|||
|
wtWebGraphThermHygroPortOffset2 OCTET STRING,
|
|||
|
wtWebGraphThermHygroPortTemperature2 OCTET STRING,
|
|||
|
wtWebGraphThermHygroPortComment OCTET STRING,
|
|||
|
wtWebGraphThermHygroPortSensorSelect OCTET STRING
|
|||
|
}
|
|||
|
|
|||
|
wtWebGraphThermHygroPortName OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Name des Sensors."
|
|||
|
::= { wtWebGraphThermHygroPortEntry 1 }
|
|||
|
|
|||
|
wtWebGraphThermHygroPortText OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Beschreibung des Sensors."
|
|||
|
::= { wtWebGraphThermHygroPortEntry 2 }
|
|||
|
|
|||
|
wtWebGraphThermHygroPortOffset1 OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Offset-Kalibrierung: Offset in Grad mit max. 2 Nachkommastellen bei Temperatur 1."
|
|||
|
::= { wtWebGraphThermHygroPortEntry 3 }
|
|||
|
|
|||
|
wtWebGraphThermHygroPortTemperature1 OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Offset-Kalibrierung: Referenztemperatur 1 in Grad mit max. 2 Nachkommastellen."
|
|||
|
::= { wtWebGraphThermHygroPortEntry 4 }
|
|||
|
|
|||
|
wtWebGraphThermHygroPortOffset2 OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Offset-Kalibrierung: Offset in Grad mit max. 2 Nachkommastellen bei Temperatur 2."
|
|||
|
::= { wtWebGraphThermHygroPortEntry 5 }
|
|||
|
|
|||
|
wtWebGraphThermHygroPortTemperature2 OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Offset-Kalibrierung: Referenztemperatur 2 in Grad mit max. 2 Nachkommastellen."
|
|||
|
::= { wtWebGraphThermHygroPortEntry 6 }
|
|||
|
|
|||
|
wtWebGraphThermHygroPortComment OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Offset-Kalibrierung: Angaben zu Datum, Referenzger<65>t, Operator."
|
|||
|
::= { wtWebGraphThermHygroPortEntry 7 }
|
|||
|
|
|||
|
wtWebGraphThermHygroPortSensorSelect OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING (SIZE(4))
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Bin<69>r kodierte Optionen f<>r Sensor 1:
|
|||
|
Octet 1: ungenutzt
|
|||
|
Octet 2: ungenutzt
|
|||
|
Octet 3: ungenutzt
|
|||
|
Octet 4:
|
|||
|
Bit 0 : PT100
|
|||
|
Bit 1 : PT1000 (default)
|
|||
|
Bit 2-7: ungenutzt
|
|||
|
|
|||
|
Bin<69>r kodierte Optionen f<>r Sensor 2:
|
|||
|
Octet 1: ungenutzt
|
|||
|
Octet 2: ungenutzt
|
|||
|
Octet 3: ungenutzt
|
|||
|
Octet 4:
|
|||
|
Bit 0 : W&T Sensor rel. Feuchte (default)
|
|||
|
Bit 1 : Skalar 0-2.5V
|
|||
|
Bit 2 : Disconnect
|
|||
|
Bit 3-7: ungenutzt"
|
|||
|
::= { wtWebGraphThermHygroPortEntry 8 }
|
|||
|
|
|||
|
-- wtWebGraphThermHygroManufact Group
|
|||
|
----------------------------
|
|||
|
|
|||
|
wtWebGraphThermHygroMfName OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Hersteller Firmenname"
|
|||
|
::= { wtWebGraphThermHygroManufact 1 }
|
|||
|
|
|||
|
wtWebGraphThermHygroMfAddr OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Adresse des Herstellers."
|
|||
|
::= { wtWebGraphThermHygroManufact 2 }
|
|||
|
|
|||
|
wtWebGraphThermHygroMfHotline OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Hotline des Herstellers."
|
|||
|
::= { wtWebGraphThermHygroManufact 3 }
|
|||
|
|
|||
|
wtWebGraphThermHygroMfInternet OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Internet-Adresse des Herstellers."
|
|||
|
::= { wtWebGraphThermHygroManufact 4 }
|
|||
|
|
|||
|
wtWebGraphThermHygroMfDeviceTyp OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Ger<65>tebezeichnung (Typ) des Herstellers."
|
|||
|
::= { wtWebGraphThermHygroManufact 5 }
|
|||
|
|
|||
|
wtWebGraphThermHygroMfOrderNo OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Bestellnummer des Ger<65>tes des Herstellers."
|
|||
|
::= { wtWebGraphThermHygroManufact 6 }
|
|||
|
|
|||
|
-- wtWebGraphThermHygroDiag Group
|
|||
|
----------------------------
|
|||
|
|
|||
|
wtWebGraphThermHygroDiagErrorCount OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Anzahl der Eintr<74>ge im Fehlerspeicher."
|
|||
|
::= { wtWebGraphThermHygroDiag 1 }
|
|||
|
|
|||
|
wtWebGraphThermHygroDiagBinaryError OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Bitweise kodierte Fehlerursachen."
|
|||
|
::= { wtWebGraphThermHygroDiag 2 }
|
|||
|
|
|||
|
wtWebGraphThermHygroDiagErrorIndex OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
ACCESS read-write
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Der Wert dieser Variable wird als Index f<>r die Ausgabe
|
|||
|
eines Fehlertextes (wtWebGraphThermHygroDiagErrorMessage) verwendet.
|
|||
|
Die Fehler im Speicher sind von 1 bis wtWebGraphThermHygroDiagErrorCount durchnummeriert.
|
|||
|
Nach dem Schreiben einens g<>ltigen Wertes in diese Variable kann der dazugeh<65>rige Text
|
|||
|
in wtWebGraphThermHygroDiagErrorMessage ausgelesen werden."
|
|||
|
::= { wtWebGraphThermHygroDiag 3 }
|
|||
|
|
|||
|
wtWebGraphThermHygroDiagErrorMessage OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Abh<62>ngig vom Wert wtWebGraphThermHygroDiagErrorIndex wird ein Fehlertext angezeigt."
|
|||
|
::= { wtWebGraphThermHygroDiag 4 }
|
|||
|
|
|||
|
wtWebGraphThermHygroDiagErrorClear OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
ACCESS write-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION
|
|||
|
"Durch Schreiben eine 1 in diese Variable, wird der Fehlerspeicher gel<65>scht."
|
|||
|
::= { wtWebGraphThermHygroDiag 5 }
|
|||
|
|
|||
|
-- TRAP DEFINITIONS
|
|||
|
|
|||
|
-- Diese SNMP-Traps werden gesendet, wenn die Alarmtriggerbedingungen zutreffen
|
|||
|
|
|||
|
wtWebGraphThermHygroAlert1 TRAP-TYPE
|
|||
|
ENTERPRISE wtWebGraphThermHygro
|
|||
|
VARIABLES { wtWebGraphThermHygroAlarmTrapText }
|
|||
|
DESCRIPTION
|
|||
|
"Dieser SNMP-Trap wird generiert, wenn der Alarm 1 ausgel<65>st wurde,
|
|||
|
das SNMP-Trap-Enable gesetzt ist und
|
|||
|
SNMP in Enable freigegeben ist."
|
|||
|
-- NMS trap annotation
|
|||
|
--#TYPE "Thermo-Hygrometer Alarm 1"
|
|||
|
--#SUMMARY "Alarm 1: %s"
|
|||
|
--#ARGUMENTS {0}
|
|||
|
--#SEVERITY INFORMATIONAL
|
|||
|
--#TIMEINDEX 99
|
|||
|
--#STATE OPERATIONAL
|
|||
|
::= 31
|
|||
|
|
|||
|
wtWebGraphThermHygroAlert2 TRAP-TYPE
|
|||
|
ENTERPRISE wtWebGraphThermHygro
|
|||
|
VARIABLES { wtWebGraphThermHygroAlarmTrapText }
|
|||
|
DESCRIPTION
|
|||
|
"Dieser SNMP-Trap wird generiert, wenn der Alarm 2 ausgel<65>st wurde,
|
|||
|
das SNMP-Trap-Enable gesetzt ist und
|
|||
|
SNMP in Enable freigegeben ist."
|
|||
|
-- NMS trap annotation
|
|||
|
--#TYPE "Thermo-Hygrometer Alarm 2"
|
|||
|
--#SUMMARY "Alarm 2: %s"
|
|||
|
--#ARGUMENTS {0}
|
|||
|
--#SEVERITY INFORMATIONAL
|
|||
|
--#TIMEINDEX 99
|
|||
|
--#STATE OPERATIONAL
|
|||
|
::= 32
|
|||
|
|
|||
|
wtWebGraphThermHygroAlert3 TRAP-TYPE
|
|||
|
ENTERPRISE wtWebGraphThermHygro
|
|||
|
VARIABLES { wtWebGraphThermHygroAlarmTrapText }
|
|||
|
DESCRIPTION
|
|||
|
"Dieser SNMP-Trap wird generiert, wenn der Alarm 3 ausgel<65>st wurde,
|
|||
|
das SNMP-Trap-Enable gesetzt ist und
|
|||
|
SNMP in Enable freigegeben ist."
|
|||
|
-- NMS trap annotation
|
|||
|
--#TYPE "Thermo-Hygrometer Alarm 3"
|
|||
|
--#SUMMARY "Alarm 3: %s"
|
|||
|
--#ARGUMENTS {0}
|
|||
|
--#SEVERITY INFORMATIONAL
|
|||
|
--#TIMEINDEX 99
|
|||
|
--#STATE OPERATIONAL
|
|||
|
::= 33
|
|||
|
|
|||
|
wtWebGraphThermHygroAlert4 TRAP-TYPE
|
|||
|
ENTERPRISE wtWebGraphThermHygro
|
|||
|
VARIABLES { wtWebGraphThermHygroAlarmTrapText }
|
|||
|
DESCRIPTION
|
|||
|
"Dieser SNMP-Trap wird generiert, wenn der Alarm 4 ausgel<65>st wurde,
|
|||
|
das SNMP-Trap-Enable gesetzt ist und
|
|||
|
SNMP in Enable freigegeben ist."
|
|||
|
-- NMS trap annotation
|
|||
|
--#TYPE "Thermo-Hygrometer Alarm 4"
|
|||
|
--#SUMMARY "Alarm 4: %s"
|
|||
|
--#ARGUMENTS {0}
|
|||
|
--#SEVERITY INFORMATIONAL
|
|||
|
--#TIMEINDEX 99
|
|||
|
--#STATE OPERATIONAL
|
|||
|
::= 34
|
|||
|
|
|||
|
wtWebGraphThermHygroAlert5 TRAP-TYPE
|
|||
|
ENTERPRISE wtWebGraphThermHygro
|
|||
|
VARIABLES { wtWebGraphThermHygroAlarmTrapText }
|
|||
|
DESCRIPTION
|
|||
|
"Dieser SNMP-Trap wird generiert, wenn der Alarm 5 ausgel<65>st wurde,
|
|||
|
das SNMP-Trap-Enable gesetzt ist und
|
|||
|
SNMP in Enable freigegeben ist."
|
|||
|
-- NMS trap annotation
|
|||
|
--#TYPE "Thermo-Hygrometer Alarm 5"
|
|||
|
--#SUMMARY "Alarm 5: %s"
|
|||
|
--#ARGUMENTS {0}
|
|||
|
--#SEVERITY INFORMATIONAL
|
|||
|
--#TIMEINDEX 99
|
|||
|
--#STATE OPERATIONAL
|
|||
|
::= 35
|
|||
|
|
|||
|
wtWebGraphThermHygroAlert6 TRAP-TYPE
|
|||
|
ENTERPRISE wtWebGraphThermHygro
|
|||
|
VARIABLES { wtWebGraphThermHygroAlarmTrapText }
|
|||
|
DESCRIPTION
|
|||
|
"Dieser SNMP-Trap wird generiert, wenn der Alarm 6 ausgel<65>st wurde,
|
|||
|
das SNMP-Trap-Enable gesetzt ist und
|
|||
|
SNMP in Enable freigegeben ist."
|
|||
|
-- NMS trap annotation
|
|||
|
--#TYPE "Thermo-Hygrometer Alarm 6"
|
|||
|
--#SUMMARY "Alarm 6: %s"
|
|||
|
--#ARGUMENTS {0}
|
|||
|
--#SEVERITY INFORMATIONAL
|
|||
|
--#TIMEINDEX 99
|
|||
|
--#STATE OPERATIONAL
|
|||
|
::= 36
|
|||
|
|
|||
|
wtWebGraphThermHygroAlert7 TRAP-TYPE
|
|||
|
ENTERPRISE wtWebGraphThermHygro
|
|||
|
VARIABLES { wtWebGraphThermHygroAlarmTrapText }
|
|||
|
DESCRIPTION
|
|||
|
"Dieser SNMP-Trap wird generiert, wenn der Alarm 7 ausgel<65>st wurde,
|
|||
|
das SNMP-Trap-Enable gesetzt ist und
|
|||
|
SNMP in Enable freigegeben ist."
|
|||
|
-- NMS trap annotation
|
|||
|
--#TYPE "Thermo-Hygrometer Alarm 7"
|
|||
|
--#SUMMARY "Alarm 7: %s"
|
|||
|
--#ARGUMENTS {0}
|
|||
|
--#SEVERITY INFORMATIONAL
|
|||
|
--#TIMEINDEX 99
|
|||
|
--#STATE OPERATIONAL
|
|||
|
::= 37
|
|||
|
|
|||
|
wtWebGraphThermHygroAlert8 TRAP-TYPE
|
|||
|
ENTERPRISE wtWebGraphThermHygro
|
|||
|
VARIABLES { wtWebGraphThermHygroAlarmTrapText }
|
|||
|
DESCRIPTION
|
|||
|
"Dieser SNMP-Trap wird generiert, wenn der Alarm 8 ausgel<65>st wurde,
|
|||
|
das SNMP-Trap-Enable gesetzt ist und
|
|||
|
SNMP in Enable freigegeben ist."
|
|||
|
-- NMS trap annotation
|
|||
|
--#TYPE "Thermo-Hygrometer Alarm 8"
|
|||
|
--#SUMMARY "Alarm 8: %s"
|
|||
|
--#ARGUMENTS {0}
|
|||
|
--#SEVERITY INFORMATIONAL
|
|||
|
--#TIMEINDEX 99
|
|||
|
--#STATE OPERATIONAL
|
|||
|
::= 38
|
|||
|
|
|||
|
wtWebGraphThermHygroAlert9 TRAP-TYPE
|
|||
|
ENTERPRISE wtWebGraphThermHygro
|
|||
|
VARIABLES { wtWebGraphThermHygroAlarmClearTrapText }
|
|||
|
DESCRIPTION
|
|||
|
"Dieser SNMP-Trap wird generiert, wenn der Alarm 1 gel<65>scht wurde,
|
|||
|
das SNMP-Trap-Enable gesetzt ist und
|
|||
|
SNMP in Enable freigegeben ist."
|
|||
|
-- NMS trap annotation
|
|||
|
--#TYPE "Thermo-Hygrometer Release Alarm 1"
|
|||
|
--#SUMMARY "Release Alarm 1: %s"
|
|||
|
--#ARGUMENTS {0}
|
|||
|
--#SEVERITY INFORMATIONAL
|
|||
|
--#TIMEINDEX 99
|
|||
|
--#STATE OPERATIONAL
|
|||
|
::= 91
|
|||
|
|
|||
|
wtWebGraphThermHygroAlert10 TRAP-TYPE
|
|||
|
ENTERPRISE wtWebGraphThermHygro
|
|||
|
VARIABLES { wtWebGraphThermHygroAlarmClearTrapText }
|
|||
|
DESCRIPTION
|
|||
|
"Dieser SNMP-Trap wird generiert, wenn der Alarm 2 gel<65>scht wurde,
|
|||
|
das SNMP-Trap-Enable gesetzt ist und
|
|||
|
SNMP in Enable freigegeben ist."
|
|||
|
-- NMS trap annotation
|
|||
|
--#TYPE "Thermo-Hygrometer Release Alarm 2"
|
|||
|
--#SUMMARY "Release Alarm 2: %s"
|
|||
|
--#ARGUMENTS {0}
|
|||
|
--#SEVERITY INFORMATIONAL
|
|||
|
--#TIMEINDEX 99
|
|||
|
--#STATE OPERATIONAL
|
|||
|
::= 92
|
|||
|
|
|||
|
wtWebGraphThermHygroAlert11 TRAP-TYPE
|
|||
|
ENTERPRISE wtWebGraphThermHygro
|
|||
|
VARIABLES { wtWebGraphThermHygroAlarmClearTrapText }
|
|||
|
DESCRIPTION
|
|||
|
"Dieser SNMP-Trap wird generiert, wenn der Alarm 3 gel<65>scht wurde,
|
|||
|
das SNMP-Trap-Enable gesetzt ist und
|
|||
|
SNMP in Enable freigegeben ist."
|
|||
|
-- NMS trap annotation
|
|||
|
--#TYPE "Thermo-Hygrometer Release Alarm 3"
|
|||
|
--#SUMMARY "Release Alarm 3: %s"
|
|||
|
--#ARGUMENTS {0}
|
|||
|
--#SEVERITY INFORMATIONAL
|
|||
|
--#TIMEINDEX 99
|
|||
|
--#STATE OPERATIONAL
|
|||
|
::= 93
|
|||
|
|
|||
|
wtWebGraphThermHygroAlert12 TRAP-TYPE
|
|||
|
ENTERPRISE wtWebGraphThermHygro
|
|||
|
VARIABLES { wtWebGraphThermHygroAlarmClearTrapText }
|
|||
|
DESCRIPTION
|
|||
|
"Dieser SNMP-Trap wird generiert, wenn der Alarm 4 gel<65>scht wurde,
|
|||
|
das SNMP-Trap-Enable gesetzt ist und
|
|||
|
SNMP in Enable freigegeben ist."
|
|||
|
-- NMS trap annotation
|
|||
|
--#TYPE "Thermo-Hygrometer Release Alarm 4"
|
|||
|
--#SUMMARY "Release Alarm 4: %s"
|
|||
|
--#ARGUMENTS {0}
|
|||
|
--#SEVERITY INFORMATIONAL
|
|||
|
--#TIMEINDEX 99
|
|||
|
--#STATE OPERATIONAL
|
|||
|
::= 94
|
|||
|
|
|||
|
wtWebGraphThermHygroAlert13 TRAP-TYPE
|
|||
|
ENTERPRISE wtWebGraphThermHygro
|
|||
|
VARIABLES { wtWebGraphThermHygroAlarmClearTrapText }
|
|||
|
DESCRIPTION
|
|||
|
"Dieser SNMP-Trap wird generiert, wenn der Alarm 5 gel<65>scht wurde,
|
|||
|
das SNMP-Trap-Enable gesetzt ist und
|
|||
|
SNMP in Enable freigegeben ist."
|
|||
|
-- NMS trap annotation
|
|||
|
--#TYPE "Thermo-Hygrometer Release Alarm 5"
|
|||
|
--#SUMMARY "Release Alarm 5: %s"
|
|||
|
--#ARGUMENTS {0}
|
|||
|
--#SEVERITY INFORMATIONAL
|
|||
|
--#TIMEINDEX 99
|
|||
|
--#STATE OPERATIONAL
|
|||
|
::= 95
|
|||
|
|
|||
|
wtWebGraphThermHygroAlert14 TRAP-TYPE
|
|||
|
ENTERPRISE wtWebGraphThermHygro
|
|||
|
VARIABLES { wtWebGraphThermHygroAlarmClearTrapText }
|
|||
|
DESCRIPTION
|
|||
|
"Dieser SNMP-Trap wird generiert, wenn der Alarm 6 gel<65>scht wurde,
|
|||
|
das SNMP-Trap-Enable gesetzt ist und
|
|||
|
SNMP in Enable freigegeben ist."
|
|||
|
-- NMS trap annotation
|
|||
|
--#TYPE "Thermo-Hygrometer Release Alarm 6"
|
|||
|
--#SUMMARY "Release Alarm 6: %s"
|
|||
|
--#ARGUMENTS {0}
|
|||
|
--#SEVERITY INFORMATIONAL
|
|||
|
--#TIMEINDEX 99
|
|||
|
--#STATE OPERATIONAL
|
|||
|
::= 96
|
|||
|
|
|||
|
wtWebGraphThermHygroAlert15 TRAP-TYPE
|
|||
|
ENTERPRISE wtWebGraphThermHygro
|
|||
|
VARIABLES { wtWebGraphThermHygroAlarmClearTrapText }
|
|||
|
DESCRIPTION
|
|||
|
"Dieser SNMP-Trap wird generiert, wenn der Alarm 7 gel<65>scht wurde,
|
|||
|
das SNMP-Trap-Enable gesetzt ist und
|
|||
|
SNMP in Enable freigegeben ist."
|
|||
|
-- NMS trap annotation
|
|||
|
--#TYPE "Thermo-Hygrometer Release Alarm 7"
|
|||
|
--#SUMMARY "Release Alarm 7: %s"
|
|||
|
--#ARGUMENTS {0}
|
|||
|
--#SEVERITY INFORMATIONAL
|
|||
|
--#TIMEINDEX 99
|
|||
|
--#STATE OPERATIONAL
|
|||
|
::= 97
|
|||
|
|
|||
|
wtWebGraphThermHygroAlert16 TRAP-TYPE
|
|||
|
ENTERPRISE wtWebGraphThermHygro
|
|||
|
VARIABLES { wtWebGraphThermHygroAlarmClearTrapText }
|
|||
|
DESCRIPTION
|
|||
|
"Dieser SNMP-Trap wird generiert, wenn der Alarm 8 gel<65>scht wurde,
|
|||
|
das SNMP-Trap-Enable gesetzt ist und
|
|||
|
SNMP in Enable freigegeben ist."
|
|||
|
-- NMS trap annotation
|
|||
|
--#TYPE "Thermo-Hygrometer Release Alarm 8"
|
|||
|
--#SUMMARY "Release Alarm 8: %s"
|
|||
|
--#ARGUMENTS {0}
|
|||
|
--#SEVERITY INFORMATIONAL
|
|||
|
--#TIMEINDEX 99
|
|||
|
--#STATE OPERATIONAL
|
|||
|
::= 98
|
|||
|
|
|||
|
wtWebGraphThermHygroAlertDiag TRAP-TYPE
|
|||
|
ENTERPRISE wtWebGraphThermHygro
|
|||
|
VARIABLES {
|
|||
|
wtWebGraphThermHygroDiagErrorIndex,
|
|||
|
wtWebGraphThermHygroDiagErrorMessage
|
|||
|
}
|
|||
|
DESCRIPTION
|
|||
|
"Dieser SNMP-Trap wird generiert, wenn eine Diagnose/Error-Message ausgel<65>st wurde,
|
|||
|
das SNMP-Trap-Enable gesetzt ist und
|
|||
|
SNMP in Enable freigegeben ist."
|
|||
|
-- NMS trap annotation
|
|||
|
--#TYPE "Thermo-Hygrometer Diagnose Error"
|
|||
|
--#SUMMARY "Diagnose error index: %d, Message: %s."
|
|||
|
--#ARGUMENTS {0,1}
|
|||
|
--#SEVERITY MAJOR
|
|||
|
--#TIMEINDEX 99
|
|||
|
--#STATE DEGRADED
|
|||
|
::= 110
|
|||
|
|
|||
|
END
|