1550 lines
		
	
	
		
			51 KiB
		
	
	
	
		
			Plaintext
		
	
	
	
	
	
			
		
		
	
	
			1550 lines
		
	
	
		
			51 KiB
		
	
	
	
		
			Plaintext
		
	
	
	
	
	
--
 | 
						||
--                      C&C Power DC_SYSTEM MIB
 | 
						||
--         Management Information Base for SNMP Network Management
 | 
						||
--
 | 
						||
--      Copyright 2004 C&C Power, Inc.
 | 
						||
--
 | 
						||
--      C&C Power shall not be liable for technical or
 | 
						||
--      editorial errors or omissions contained herein. The information in
 | 
						||
--      this document is provided "as is" without warranty of any kind and
 | 
						||
--      is subject to change without notice. The warranties for C&C Power products
 | 
						||
--      are set forth in the express limited warranty statements
 | 
						||
--      accompanying such products. Nothing herein should be construed as
 | 
						||
--      constituting an additional warranty.
 | 
						||
--
 | 
						||
--      The C&C Power Enterprise number is 18642.
 | 
						||
--      The ASN.1 prefix to, and including the C&C Power Enterprise is:
 | 
						||
--           1.3.6.1.4.1.18642
 | 
						||
--
 | 
						||
--    MIB Version 1.0
 | 
						||
--    *********************************************************************
 | 
						||
--    Release History
 | 
						||
--       Initial Release Date: August 9, 2004 (Version 1.0)
 | 
						||
--       Author: Jeff Gear
 | 
						||
--    Revision History
 | 
						||
--       Date:
 | 
						||
--       Revision:
 | 
						||
--    *********************************************************************
 | 
						||
 | 
						||
CCPOWER-MIB DEFINITIONS ::= BEGIN
 | 
						||
 | 
						||
   IMPORTS
 | 
						||
     	enterprises    FROM RFC1155-SMI
 | 
						||
      DisplayString  FROM RFC1213-MIB
 | 
						||
      OBJECT-TYPE    FROM RFC-1212
 | 
						||
      TRAP-TYPE      FROM RFC-1215;
 | 
						||
 | 
						||
   ccpower           OBJECT IDENTIFIER ::= { enterprises 18642 }
 | 
						||
   dcSystem          OBJECT IDENTIFIER ::= { ccpower 1 }
 | 
						||
 | 
						||
-- *********************************************************************
 | 
						||
-- readWriteObjects definition
 | 
						||
-- *********************************************************************
 | 
						||
 | 
						||
   readWriteObjects OBJECT IDENTIFIER ::= { dcSystem 1 }
 | 
						||
 | 
						||
-- *********************************************************************
 | 
						||
-- readWriteObjects.settings definition
 | 
						||
-- *********************************************************************
 | 
						||
 | 
						||
	settings OBJECT IDENTIFIER ::= { readWriteObjects 1 }
 | 
						||
 | 
						||
   floatVoltage OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Rectifier DC Output Voltage.
 | 
						||
                  Return value is XXX representing XX.X volts."
 | 
						||
   	::= { settings 1 }
 | 
						||
 | 
						||
   overloadCurrent OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Current which when exceeded will cause an alarm.
 | 
						||
                  Return value is XXXX representing XXXX amps."
 | 
						||
   	::= { settings 2 }
 | 
						||
 | 
						||
   highVoltageAlarm OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Voltage which when exceeded will cause an alarm.
 | 
						||
                  Return value is XXX representing XX.X volts."
 | 
						||
   	::= { settings 3 }
 | 
						||
 | 
						||
   lowVoltageAlarm OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Voltage which when exceeded will cause an alarm.
 | 
						||
                  Return value is XXX representing XX.X volts."
 | 
						||
   	::= { settings 4 }
 | 
						||
 | 
						||
   disconnect1Voltage OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Voltage which when exceeded will cause a specific load to disconnect.
 | 
						||
                  Return value is XXX representing XX.X volts."
 | 
						||
   	::= { settings 5 }
 | 
						||
 | 
						||
   disconnect1Temperature OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Temperature which when exceeded will cause a specific load to disconnect.
 | 
						||
                  Return value is XX representing XX <20>C."
 | 
						||
   	::= { settings 6 }
 | 
						||
 | 
						||
   disconnect1LoadShedSundayOff OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Time on Sunday which when reached will cause a specific load to disconnect.
 | 
						||
                  Return value is XX:XX representing HH:MM."
 | 
						||
   	::= { settings 7 }
 | 
						||
 | 
						||
   disconnect1LoadShedMondayOff OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Time on Monday which when reached will cause a specific load to disconnect.
 | 
						||
                  Return value is XX:XX representing HH:MM."
 | 
						||
   	::= { settings 8 }
 | 
						||
 | 
						||
   disconnect1LoadShedTuesdayOff OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Time on Tuesday which when reached will cause a specific load to disconnect.
 | 
						||
                  Return value is XX:XX representing HH:MM."
 | 
						||
   	::= { settings 9 }
 | 
						||
 | 
						||
   disconnect1LoadShedWednesdayOff OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Time on Wednesday which when reached will cause a specific load to disconnect.
 | 
						||
                  Return value is XX:XX representing HH:MM."
 | 
						||
   	::= { settings 10 }
 | 
						||
 | 
						||
   disconnect1LoadShedThursdayOff OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Time on Thursday which when reached will cause a specific load to disconnect.
 | 
						||
                  Return value is XX:XX representing HH:MM."
 | 
						||
   	::= { settings 11 }
 | 
						||
 | 
						||
   disconnect1LoadShedFridayOff OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Time on Friday which when reached will cause a specific load to disconnect.
 | 
						||
                  Return value is XX:XX representing HH:MM."
 | 
						||
   	::= { settings 12 }
 | 
						||
 | 
						||
   disconnect1LoadShedSaturdayOff OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Time on Saturday which when reached will cause a specific load to disconnect.
 | 
						||
                  Return value is XX:XX representing HH:MM."
 | 
						||
   	::= { settings 13 }
 | 
						||
 | 
						||
   disconnect2Voltage OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Voltage which when exceeded will cause a specific load to disconnect.
 | 
						||
                  Return value is XXX representing XX.X volts."
 | 
						||
   	::= { settings 14 }
 | 
						||
 | 
						||
   disconnect2Temperature OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Temperature which when exceeded will cause a specific load to disconnect.
 | 
						||
                  Return value is XX representing XX <20>C."
 | 
						||
   	::= { settings 15 }
 | 
						||
 | 
						||
   disconnect2LoadShedSundayOff OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Time on Sunday which when reached will cause a specific load to disconnect.
 | 
						||
                  Return value is XX:XX representing HH:MM."
 | 
						||
   	::= { settings 16 }
 | 
						||
 | 
						||
   disconnect2LoadShedMondayOff OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Time on Monday which when reached will cause a specific load to disconnect.
 | 
						||
                  Return value is XX:XX representing HH:MM."
 | 
						||
   	::= { settings 17 }
 | 
						||
 | 
						||
   disconnect2LoadShedTuesdayOff OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Time on Tuesday which when reached will cause a specific load to disconnect.
 | 
						||
                  Return value is XX:XX representing HH:MM."
 | 
						||
   	::= { settings 18 }
 | 
						||
 | 
						||
   disconnect2LoadShedWednesdayOff OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Time on Wednesday which when reached will cause a specific load to disconnect.
 | 
						||
                  Return value is XX:XX representing HH:MM."
 | 
						||
   	::= { settings 19 }
 | 
						||
 | 
						||
   disconnect2LoadShedThursdayOff OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Time on Thursday which when reached will cause a specific load to disconnect.
 | 
						||
                  Return value is XX:XX representing HH:MM."
 | 
						||
   	::= { settings 20 }
 | 
						||
 | 
						||
   disconnect2LoadShedFridayOff OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Time on Friday which when reached will cause a specific load to disconnect.
 | 
						||
                  Return value is XX:XX representing HH:MM."
 | 
						||
   	::= { settings 21 }
 | 
						||
 | 
						||
   disconnect2LoadShedSaturdayOff OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Time on Saturday which when reached will cause a specific load to disconnect.
 | 
						||
                  Return value is XX:XX representing HH:MM."
 | 
						||
   	::= { settings 22 }
 | 
						||
 | 
						||
   disconnect3Voltage OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Voltage which when exceeded will cause a specific load to disconnect.
 | 
						||
                  Return value is XXX representing XX.X volts."
 | 
						||
   	::= { settings 23 }
 | 
						||
 | 
						||
   disconnect3Temperature OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Temperature which when exceeded will cause a specific load to disconnect.
 | 
						||
                  Return value is XX representing XX <20>C."
 | 
						||
   	::= { settings 24 }
 | 
						||
 | 
						||
   disconnect3LoadShedSundayOff OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Time on Sunday which when reached will cause a specific load to disconnect.
 | 
						||
                  Return value is XX:XX representing HH:MM."
 | 
						||
   	::= { settings 25 }
 | 
						||
 | 
						||
   disconnect3LoadShedMondayOff OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Time on Monday which when reached will cause a specific load to disconnect.
 | 
						||
                  Return value is XX:XX representing HH:MM."
 | 
						||
   	::= { settings 26 }
 | 
						||
 | 
						||
   disconnect3LoadShedTuesdayOff OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Time on Tuesday which when reached will cause a specific load to disconnect.
 | 
						||
                  Return value is XX:XX representing HH:MM."
 | 
						||
   	::= { settings 27 }
 | 
						||
 | 
						||
   disconnect3LoadShedWednesdayOff OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Time on Wednesday which when reached will cause a specific load to disconnect.
 | 
						||
                  Return value is XX:XX representing HH:MM."
 | 
						||
   	::= { settings 28 }
 | 
						||
 | 
						||
   disconnect3LoadShedThursdayOff OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Time on Thursday which when reached will cause a specific load to disconnect.
 | 
						||
                  Return value is XX:XX representing HH:MM."
 | 
						||
   	::= { settings 29 }
 | 
						||
 | 
						||
   disconnect3LoadShedFridayOff OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Time on Friday which when reached will cause a specific load to disconnect.
 | 
						||
                  Return value is XX:XX representing HH:MM."
 | 
						||
   	::= { settings 30 }
 | 
						||
 | 
						||
   disconnect3LoadShedSaturdayOff OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Time on Saturday which when reached will cause a specific load to disconnect.
 | 
						||
                  Return value is XX:XX representing HH:MM."
 | 
						||
   	::= { settings 31 }
 | 
						||
 | 
						||
   reconnect1Voltage OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Voltage which when reached will cause a specific load to reconnect.
 | 
						||
                  Return value is XXX representing XX.X volts."
 | 
						||
   	::= { settings 32 }
 | 
						||
 | 
						||
   reconnect1LoadShedSundayOn OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Time which when reached will cause a specific load to reconnect.
 | 
						||
                  Return value is XX:XX representing HH:MM."
 | 
						||
   	::= { settings 33 }
 | 
						||
 | 
						||
   reconnect1LoadShedMondayOn OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Time on Monday which when reached will cause a specific load to reconnect.
 | 
						||
                  Return value is XX:XX representing HH:MM."
 | 
						||
   	::= { settings 34 }
 | 
						||
 | 
						||
   reconnect1LoadShedTuesdayOn OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Time on Tuesday which when reached will cause a specific load to reconnect.
 | 
						||
                  Return value is XX:XX representing HH:MM."
 | 
						||
   	::= { settings 35 }
 | 
						||
 | 
						||
   reconnect1LoadShedWednesdayOn OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Time on Wednesday which when reached will cause a specific load to reconnect.
 | 
						||
                  Return value is XX:XX representing HH:MM."
 | 
						||
   	::= { settings 36 }
 | 
						||
 | 
						||
   reconnect1LoadShedThursdayOn OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Time on Thursday which when reached will cause a specific load to reconnect.
 | 
						||
                  Return value is XX:XX representing HH:MM."
 | 
						||
   	::= { settings 37 }
 | 
						||
 | 
						||
   reconnect1LoadShedFridayOn OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Time on Friday which when reached will cause a specific load to reconnect.
 | 
						||
                  Return value is XX:XX representing HH:MM."
 | 
						||
   	::= { settings 38 }
 | 
						||
 | 
						||
   reconnect1LoadShedSaturdayOn OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Time on Saturday which when reached will cause a specific load to reconnect.
 | 
						||
                  Return value is XX:XX representing HH:MM."
 | 
						||
   	::= { settings 39 }
 | 
						||
 | 
						||
   reconnect2Voltage OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Voltage which when reached will cause a specific load to reconnect.
 | 
						||
                  Return value is XXX representing XX.X volts."
 | 
						||
   	::= { settings 40 }
 | 
						||
 | 
						||
   reconnect2LoadShedSundayOn OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Time on Sunday which when reached will cause a specific load to reconnect.
 | 
						||
                  Return value is XX:XX representing HH:MM."
 | 
						||
   	::= { settings 41 }
 | 
						||
 | 
						||
   reconnect2LoadShedMondayOn OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Time on Monday which when reached will cause a specific load to reconnect.
 | 
						||
                  Return value is XX:XX representing HH:MM."
 | 
						||
   	::= { settings 42 }
 | 
						||
 | 
						||
   reconnect2LoadShedTuesdayOn OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Time on Tuesday which when reached will cause a specific load to reconnect.
 | 
						||
                  Return value is XX:XX representing HH:MM."
 | 
						||
   	::= { settings 43 }
 | 
						||
 | 
						||
   reconnect2LoadShedWednesdayOn OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Time on Wednesday which when reached will cause a specific load to reconnect.
 | 
						||
                  Return value is XX:XX representing HH:MM."
 | 
						||
   	::= { settings 44 }
 | 
						||
 | 
						||
   reconnect2LoadShedThursdayOn OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Time on Thursday which when reached will cause a specific load to reconnect.
 | 
						||
                  Return value is XX:XX representing HH:MM."
 | 
						||
   	::= { settings 45 }
 | 
						||
 | 
						||
   reconnect2LoadShedFridayOn OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Time on Friday which when reached will cause a specific load to reconnect.
 | 
						||
                  Return value is XX:XX representing HH:MM."
 | 
						||
   	::= { settings 46 }
 | 
						||
 | 
						||
   reconnect2LoadShedSaturdayOn OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Time on Saturday which when reached will cause a specific load to reconnect.
 | 
						||
                  Return value is XX:XX representing HH:MM."
 | 
						||
   	::= { settings 47 }
 | 
						||
 | 
						||
   reconnect3Voltage OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Voltage which when reached will cause a specific load to reconnect.
 | 
						||
                  Return value is XXX representing XX.X volts."
 | 
						||
   	::= { settings 48 }
 | 
						||
 | 
						||
   reconnect3LoadShedSundayOn OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Time on Sunday which when reached will cause a specific load to reconnect.
 | 
						||
                  Return value is XX:XX representing HH:MM."
 | 
						||
   	::= { settings 49 }
 | 
						||
 | 
						||
   reconnect3LoadShedMondayOn OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Time on Monday which when reached will cause a specific load to reconnect.
 | 
						||
                  Return value is XX:XX representing HH:MM."
 | 
						||
   	::= { settings 50 }
 | 
						||
 | 
						||
   reconnect3LoadShedTuesdayOn OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Time on Tuesday which when reached will cause a specific load to reconnect.
 | 
						||
                  Return value is XX:XX representing HH:MM."
 | 
						||
   	::= { settings 51 }
 | 
						||
 | 
						||
   reconnect3LoadShedWednesdayOn OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Time on Wednesday which when reached will cause a specific load to reconnect.
 | 
						||
                  Return value is XX:XX representing HH:MM."
 | 
						||
   	::= { settings 52 }
 | 
						||
 | 
						||
   reconnect3LoadShedThursdayOn OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Time on Thursday which when reached will cause a specific load to reconnect.
 | 
						||
                  Return value is XX:XX representing HH:MM."
 | 
						||
   	::= { settings 53 }
 | 
						||
 | 
						||
   reconnect3LoadShedFridayOn OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Time on Friday which when reached will cause a specific load to reconnect.
 | 
						||
                  Return value is XX:XX representing HH:MM."
 | 
						||
   	::= { settings 54 }
 | 
						||
 | 
						||
   reconnect3LoadShedSaturdayOn OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Time on Saturday which when reached will cause a specific load to reconnect.
 | 
						||
                  Return value is XX:XX representing HH:MM."
 | 
						||
   	::= { settings 55 }
 | 
						||
 | 
						||
   equalizeTime OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Number of hours the equalize voltage is to be applied.
 | 
						||
                  Return value is XXX representing XX.X hours."
 | 
						||
   	::= { settings 56 }
 | 
						||
 | 
						||
   equalizeVoltage OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Equalize voltage to be applied.
 | 
						||
                  Return value is XXX representing XX.X volts."
 | 
						||
   	::= { settings 57 }
 | 
						||
 | 
						||
   batteryResistancePercentChange OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Resistance percentange change that when reached will cause an alarm.
 | 
						||
                  Return value is XXX representing XXX %."
 | 
						||
   	::= { settings 58 }
 | 
						||
 | 
						||
   batteryResistanceTestInterval OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Battery resistance test interval.
 | 
						||
                  Return value is XX representing XX weeks."
 | 
						||
   	::= { settings 59 }
 | 
						||
 | 
						||
   loadShedTimeControl OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER {
 | 
						||
			enabled(1),
 | 
						||
         disabled(2)
 | 
						||
      }
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Load shed time control enabled/disabled status.
 | 
						||
                  Return value: 1 = time control enabled, 2 = time control disabled."
 | 
						||
   	::= { settings 60 }
 | 
						||
 | 
						||
   batteryFloatCurrent OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER
 | 
						||
   	ACCESS		read-write
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Battery float current.
 | 
						||
                  Return value is XXX representing XXX amps."
 | 
						||
   	::= { settings 61 }
 | 
						||
 | 
						||
-- *********************************************************************
 | 
						||
-- readOnlyObjects definition
 | 
						||
-- *********************************************************************
 | 
						||
 | 
						||
   readOnlyObjects OBJECT IDENTIFIER ::= { dcSystem 2 }
 | 
						||
 | 
						||
-- *********************************************************************
 | 
						||
-- readOnlyObjects.rectifiers definition
 | 
						||
-- *********************************************************************
 | 
						||
 | 
						||
	rectifiers OBJECT IDENTIFIER ::= { readOnlyObjects 1 }
 | 
						||
 | 
						||
   rectifierFloatVoltage OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Rectifier float voltage.
 | 
						||
                  Return value is XXX representing XX.X volts. Valid ranges are 24.0 to 57.0 volts."
 | 
						||
   	::= { rectifiers 1 }
 | 
						||
 | 
						||
   rectifierLoadCurrent OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Rectifier DC load current.
 | 
						||
                  Return value is XXXX representing XXXX amps. Valid ranges are 0000 to 5000 amps."
 | 
						||
   	::= { rectifiers 2}
 | 
						||
 | 
						||
-- *********************************************************************
 | 
						||
-- readOnlyObjects.batteries definition
 | 
						||
-- *********************************************************************
 | 
						||
 | 
						||
	batteries OBJECT IDENTIFIER ::= { readOnlyObjects 2 }
 | 
						||
 | 
						||
   batteryCurrent OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Battery current.
 | 
						||
                  Return value is XXXX representing XXXX amps. Valid ranges are 0000 to 1000 amps."
 | 
						||
   	::= { batteries 1 }
 | 
						||
 | 
						||
   batteryTemperature OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Battery temperature.
 | 
						||
                  Return value is XX representing XX <20>C. Valid ranges are -40 to 99 <20>C."
 | 
						||
   	::= { batteries 2 }
 | 
						||
 | 
						||
   batteryResistanceReference OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Initial battery resistance.
 | 
						||
                  Return value is XXXXX representing X.XXXX ohms. Valid ranges are 0.0000 to 5.0000 ohms."
 | 
						||
   	::= { batteries 3 }
 | 
						||
 | 
						||
   batteryResistanceReading OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Last battery resistance reading.
 | 
						||
                   Return value is XXXXX representing X.XXXX ohms. Valid ranges are 0.0000 to 5.0000 ohms."
 | 
						||
   	::= { batteries 4 }
 | 
						||
 | 
						||
   batteryResistanceChange OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Percent change from last battery resistance reading.
 | 
						||
                  Return value is XXX representing XXX %. Valid ranges are 001 to 999 %."
 | 
						||
   	::= { batteries 5 }
 | 
						||
 | 
						||
   batteryCycles1 OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Number of discharge/recharge cycles less than 1 minute.
 | 
						||
                  Return value is XXX representing XXX cycles. Valid ranges are 000 to 255 cycles."
 | 
						||
   	::= { batteries 6 }
 | 
						||
 | 
						||
   batteryCycles1to5 OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Number of discharge/recharge cycles from 1 to 5 minutes.
 | 
						||
                  Return value is XXX representing XXX cycles. Valid ranges are 000 to 255 cycles."
 | 
						||
   	::= { batteries 7 }
 | 
						||
 | 
						||
   batteryCycles5to15 OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Number of discharge/recharge cycles from 5 to 15 minutes.
 | 
						||
                  Return value is XXX representing XXX cycles. Valid ranges are 000 to 255 cycles."
 | 
						||
   	::= { batteries 8 }
 | 
						||
 | 
						||
   batteryCycles15 OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Number of discharge/recharge cycles greater than 15 minutes.
 | 
						||
                  Return value is XXX representing XXX cycles. Valid ranges are 000 to 255 cycles."
 | 
						||
   	::= { batteries 9 }
 | 
						||
 | 
						||
   batteryCycles15LastCycleDate OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Last cycle date of batteryCycles15.
 | 
						||
                  Return value is MM-DD-YY, HH-MM."
 | 
						||
   	::= { batteries 10 }
 | 
						||
 | 
						||
   batteryCycles15LastDuration OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Duration of batteryCycles15 last cycle.
 | 
						||
                  Return value is XXXX representing XXXX minutes."
 | 
						||
   	::= { batteries 11 }
 | 
						||
 | 
						||
   batteryTestFault OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER {
 | 
						||
			abort1(1),
 | 
						||
         abort2(2),
 | 
						||
         abort3(3),
 | 
						||
         none(4)
 | 
						||
      }
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Battery failure has occured during battery restistance test.
 | 
						||
                  Return value: 1 = Abort 1, 2 = Abort 2, 3 = Abort 3, 4 = None."
 | 
						||
   	::= { batteries 12 }
 | 
						||
 | 
						||
-- *********************************************************************
 | 
						||
-- readOnlyObjects.factorySettings definition
 | 
						||
-- *********************************************************************
 | 
						||
 | 
						||
	factorySettings OBJECT IDENTIFIER ::= { readOnlyObjects 3 }
 | 
						||
 | 
						||
   floatVoltagePresets OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Float voltage factory setting range.
 | 
						||
                  Return value is XX.X volts min, XX.X volts max."
 | 
						||
   	::= { factorySettings 1 }
 | 
						||
 | 
						||
   highVoltageAlarmPresets OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"High voltage alarm factory setting range.
 | 
						||
                  Return value is XX.X volts min, XX.X volts max."
 | 
						||
   	::= { factorySettings 2 }
 | 
						||
 | 
						||
   lowVoltageAlarmPresets OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Low voltage alarm factory setting range.
 | 
						||
                  Return value is XX.X volts min, XX.X volts max."
 | 
						||
   	::= { factorySettings 3 }
 | 
						||
 | 
						||
   disconnect1VoltagePresets OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Disconnect voltage 1 factory setting range.
 | 
						||
                   Return value is XX.X volts min, XX.X volts max."
 | 
						||
   	::= { factorySettings 4 }
 | 
						||
 | 
						||
   disconnect1TemperaturePreset OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Disconnect temperature 1 factory setting.
 | 
						||
                  Return value is XX <20>C."
 | 
						||
   	::= { factorySettings 5 }
 | 
						||
 | 
						||
   disconnect1LoadShedSundayPresets OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Disconnect 1 load shed Sunday time settings.
 | 
						||
                  Return value is XX:Xx off, XX:XX on."
 | 
						||
   	::= { factorySettings 6 }
 | 
						||
 | 
						||
   disconnect1LoadShedMondayPresets OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Disconnect 1 load shed Monday time settings.
 | 
						||
                  Return value is XX:Xx off, XX:XX on."
 | 
						||
   	::= { factorySettings 7 }
 | 
						||
 | 
						||
   disconnect1LoadShedTuesdayPresets OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Disconnect 1 load shed Tuesday time settings.
 | 
						||
                  Return value is XX:Xx off, XX:XX on."
 | 
						||
   	::= { factorySettings 8 }
 | 
						||
 | 
						||
   disconnect1LoadShedWednesdayPresets OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Disconnect 1 load shed Wednesday time settings.
 | 
						||
                  Return value is XX:Xx off, XX:XX on."
 | 
						||
   	::= { factorySettings 9 }
 | 
						||
 | 
						||
   disconnect1LoadShedThursdayPresets OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Disconnect 1 load shed Thursday time settings.
 | 
						||
                  Return value is XX:Xx off, XX:XX on."
 | 
						||
   	::= { factorySettings 10 }
 | 
						||
 | 
						||
   disconnect1LoadShedFridayPresets OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Disconnect 1 load shed Friday time settings.
 | 
						||
                  Return value is XX:Xx off, XX:XX on."
 | 
						||
   	::= { factorySettings 11 }
 | 
						||
 | 
						||
   disconnect1LoadShedSaturdayPresets OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Disconnect 1 load shed Saturday time settings.
 | 
						||
                  Return value is XX:Xx off, XX:XX on."
 | 
						||
   	::= { factorySettings 12 }
 | 
						||
 | 
						||
   reconnectVoltage1Presets OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Reconnect voltage 1 factory setting range.
 | 
						||
                  Return value is XX.X volts min, XX.X volts max."
 | 
						||
   	::= { factorySettings 13 }
 | 
						||
 | 
						||
   disconnect2VoltagePresets OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Disconnect voltage 2 factory setting range.
 | 
						||
                  Return value is XX.X volts min, XX.X volts max."
 | 
						||
   	::= { factorySettings 14 }
 | 
						||
 | 
						||
   disconnect2TemperaturePreset OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Disconnect temperature 2 factory setting.
 | 
						||
                  Return value is XX <20>C."
 | 
						||
   	::= { factorySettings 15 }
 | 
						||
 | 
						||
   disconnect2LoadShedSundayPresets OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Disconnect 2 load shed Sunday time settings.
 | 
						||
                  Return value is XX:Xx off, XX:XX on."
 | 
						||
   	::= { factorySettings 16 }
 | 
						||
 | 
						||
   disconnect2LoadShedMondayPresets OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Disconnect 2 load shed Monday time settings.
 | 
						||
                  Return value is XX:Xx off, XX:XX on."
 | 
						||
   	::= { factorySettings 17 }
 | 
						||
 | 
						||
   disconnect2LoadShedTuesdayPresets OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Disconnect 2 load shed Tuesday time settings.
 | 
						||
                  Return value is XX:Xx off, XX:XX on."
 | 
						||
   	::= { factorySettings 18 }
 | 
						||
 | 
						||
   disconnect2LoadShedWednesdayPresets OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Disconnect 2 load shed Wednesday time settings.
 | 
						||
                  Return value is XX:Xx off, XX:XX on."
 | 
						||
   	::= { factorySettings 19 }
 | 
						||
 | 
						||
   disconnect2LoadShedThursdayPresets OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Disconnect 2 load shed Thursday time settings.
 | 
						||
                  Return value is XX:Xx off, XX:XX on."
 | 
						||
   	::= { factorySettings 20 }
 | 
						||
 | 
						||
   disconnect2LoadShedFridayPresets OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Disconnect 2 load shed Friday time settings.
 | 
						||
                  Return value is XX:Xx off, XX:XX on."
 | 
						||
   	::= { factorySettings 21 }
 | 
						||
 | 
						||
   disconnect2LoadShedSaturdayPresets OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Disconnect 2 load shed Saturday time settings.
 | 
						||
                  Return value is XX:Xx off, XX:XX on."
 | 
						||
   	::= { factorySettings 22 }
 | 
						||
 | 
						||
   reconnect2VoltagePresets OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Reconnect voltage 2 factory setting range.
 | 
						||
                  Return value is XX.X volts min, XX.X volts max."
 | 
						||
   	::= { factorySettings 23 }
 | 
						||
 | 
						||
   disconnect3VoltagePresets OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Disconnect voltage 3 factory setting range.
 | 
						||
                  Return value is XX.X volts min, XX.X volts max."
 | 
						||
   	::= { factorySettings 24 }
 | 
						||
 | 
						||
   disconnect3TemperaturePreset OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Disconnect temperature 3 factory setting.
 | 
						||
                  Return value is XX <20>C."
 | 
						||
   	::= { factorySettings 25 }
 | 
						||
 | 
						||
   disconnect3LoadShedSundayPresets OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Disconnect 3 load shed Sunday time settings.
 | 
						||
                  Return value is XX:Xx off, XX:XX on."
 | 
						||
   	::= { factorySettings 26 }
 | 
						||
 | 
						||
   disconnect3LoadShedMondayPresets OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Disconnect 3 load shed Monday time settings.
 | 
						||
                  Return value is XX:Xx off, XX:XX on."
 | 
						||
   	::= { factorySettings 27 }
 | 
						||
 | 
						||
   disconnect3LoadShedTuesdayPresets OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Disconnect 3 load shed Tuesday time settings.
 | 
						||
                  Return value is XX:Xx off, XX:XX on."
 | 
						||
   	::= { factorySettings 28 }
 | 
						||
 | 
						||
   disconnect3LoadShedWednesdayPresets OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Disconnect 3 load shed Wednesday time settings.
 | 
						||
                  Return value is XX:Xx off, XX:XX on."
 | 
						||
   	::= { factorySettings 29 }
 | 
						||
 | 
						||
   disconnect3LoadShedThursdayPresets OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Disconnect 3 load shed Thursday time settings.
 | 
						||
                  Return value is XX:Xx off, XX:XX on."
 | 
						||
   	::= { factorySettings 30 }
 | 
						||
 | 
						||
   disconnect3LoadShedFridayPresets OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Disconnect 3 load shed Friday time settings.
 | 
						||
                  Return value is XX:Xx off, XX:XX on."
 | 
						||
   	::= { factorySettings 31 }
 | 
						||
 | 
						||
   disconnect3LoadShedSaturdayPresets OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Disconnect 3 load shed Saturday time settings.
 | 
						||
                  Return value is XX:Xx off, XX:XX on."
 | 
						||
   	::= { factorySettings 32 }
 | 
						||
 | 
						||
   reconnect3VoltagePresets OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Reconnect voltage 3 factory setting range.
 | 
						||
                  Return value is XX.X volts min, XX.X volts max."
 | 
						||
   	::= { factorySettings 33 }
 | 
						||
 | 
						||
   overloadCurrentPresets OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Overload current factory setting range.
 | 
						||
                  Return value is XXXX amps min, XXXX amps max."
 | 
						||
   	::= { factorySettings 34 }
 | 
						||
 | 
						||
   maximumCurrentPreset OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Maximum current factory setting.
 | 
						||
                  Return value is XXXX amps."
 | 
						||
   	::= { factorySettings 35 }
 | 
						||
 | 
						||
   batteryFloatCurrentPresets OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Battery float current factory settings.
 | 
						||
                  Return value is XXX amps min, XXX amps max."
 | 
						||
   	::= { factorySettings 36 }
 | 
						||
 | 
						||
   equalizeTimePresets OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Equalize time factory setting range.
 | 
						||
                  Return value is 00.0 hours min, XX.X hours max."
 | 
						||
   	::= { factorySettings 37 }
 | 
						||
 | 
						||
   equalizeVoltagePresets OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Equalize voltage factory setting range.
 | 
						||
                  Return value is XX.X volts min, XX.X volts max."
 | 
						||
   	::= { factorySettings 38 }
 | 
						||
 | 
						||
   batteryResistancePresets OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Battery resistance percent change factory setting range.
 | 
						||
                  Return value is XXX % min, XXX % max."
 | 
						||
   	::= { factorySettings 39 }
 | 
						||
 | 
						||
   batteryTestIntervalPresets OBJECT-TYPE
 | 
						||
   	SYNTAX		DisplayString
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Battery resistance test interval factory setting range.
 | 
						||
                  Return value is XX weeks min, XX weeks max."
 | 
						||
   	::= { factorySettings 40 }
 | 
						||
 | 
						||
-- *********************************************************************
 | 
						||
-- readOnlyObjects.alarmStatus definition
 | 
						||
-- *********************************************************************
 | 
						||
 | 
						||
	alarmStatus OBJECT IDENTIFIER ::= { readOnlyObjects 4 }
 | 
						||
 | 
						||
   highVoltageAlarmStatus OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER {
 | 
						||
			inactive(1),
 | 
						||
         active(2)
 | 
						||
      }
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"High voltage alarm status.
 | 
						||
                  Return value 1 = alarm inactive, 2 = alarm active."
 | 
						||
   	::= { alarmStatus 1 }
 | 
						||
 | 
						||
   lowVoltageAlarmStatus OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER {
 | 
						||
			inactive(1),
 | 
						||
         active(2)
 | 
						||
      }
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Low voltage alarm status.
 | 
						||
                  Return value 1 = alarm inactive, 2 = alarm active."
 | 
						||
   	::= { alarmStatus 2 }
 | 
						||
 | 
						||
   overloadAlarmStatus OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER {
 | 
						||
			inactive(1),
 | 
						||
         active(2)
 | 
						||
      }
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Overload alarm status.
 | 
						||
                  Return value 1 = alarm inactive, 2 = alarm active."
 | 
						||
   	::= { alarmStatus 3 }
 | 
						||
 | 
						||
   breakerAlarmStatus OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER {
 | 
						||
			inactive(1),
 | 
						||
         active(2)
 | 
						||
      }
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Breaker alarm status.
 | 
						||
                  Return value 1 = alarm inactive, 2 = alarm active."
 | 
						||
   	::= { alarmStatus 4 }
 | 
						||
 | 
						||
   acFailureAlarmStatus OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER {
 | 
						||
			inactive(1),
 | 
						||
         active(2)
 | 
						||
      }
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"AC failure alarm status.
 | 
						||
                  Return value 1 = alarm inactive, 2 = alarm active."
 | 
						||
   	::= { alarmStatus 5 }
 | 
						||
 | 
						||
   fanFailureAlarmStatus OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER {
 | 
						||
			inactive(1),
 | 
						||
         active(2)
 | 
						||
      }
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Fan failure alarm status.
 | 
						||
                  Return value 1 = alarm inactive, 2 = alarm active."
 | 
						||
   	::= { alarmStatus 6 }
 | 
						||
 | 
						||
   rectifierFailureAlarmStatus OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER {
 | 
						||
			inactive(1),
 | 
						||
         active(2)
 | 
						||
      }
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Rectifier failure alarm status.
 | 
						||
                  Return value 1 = alarm inactive, 2 = alarm active."
 | 
						||
   	::= { alarmStatus 7 }
 | 
						||
 | 
						||
   majorAlarmStatus OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER {
 | 
						||
			inactive(1),
 | 
						||
         active(2)
 | 
						||
      }
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Major alarm status.
 | 
						||
                  Return value 1 = alarm inactive, 2 = alarm active."
 | 
						||
   	::= { alarmStatus 8 }
 | 
						||
 | 
						||
   lowVoltageDisconnect1TemperatureAlarmStatus OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER {
 | 
						||
			inactive(1),
 | 
						||
         active(2)
 | 
						||
      }
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Low voltage disconnect 1 high temperature alarm status.
 | 
						||
                  Return value 1 = alarm inactive, 2 = alarm active."
 | 
						||
   	::= { alarmStatus 9 }
 | 
						||
 | 
						||
   lowVoltageDisconnect2TemperatureAlarmStatus OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER {
 | 
						||
			inactive(1),
 | 
						||
         active(2)
 | 
						||
      }
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Low voltage disconnect 2 high temperature alarm status.
 | 
						||
                  Return value 1 = alarm inactive, 2 = alarm active."
 | 
						||
   	::= { alarmStatus 10 }
 | 
						||
 | 
						||
   lowVoltageDisconnect3TemperatureAlarmStatus OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER {
 | 
						||
			inactive(1),
 | 
						||
         active(2)
 | 
						||
      }
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Low voltage disconnect 3 high temperature alarm status.
 | 
						||
                   Return value 1 = alarm inactive, 2 = alarm active."
 | 
						||
   	::= { alarmStatus 11 }
 | 
						||
 | 
						||
   lowVoltageDisconnect1VoltageAlarmStatus OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER {
 | 
						||
			inactive(1),
 | 
						||
         active(2)
 | 
						||
      }
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Low voltage disconnect 1 low voltage alarm status.
 | 
						||
                  Return value 1 = alarm inactive, 2 = alarm active."
 | 
						||
   	::= { alarmStatus 12 }
 | 
						||
 | 
						||
   lowVoltageDisconnect2VoltageAlarmStatus OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER {
 | 
						||
			inactive(1),
 | 
						||
         active(2)
 | 
						||
      }
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Low voltage disconnect 2 low voltage alarm status.
 | 
						||
                  Return value 1 = alarm inactive, 2 = alarm active."
 | 
						||
   	::= { alarmStatus 13 }
 | 
						||
 | 
						||
   lowVoltageDisconnect3VoltageAlarmStatus OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER {
 | 
						||
			inactive(1),
 | 
						||
         active(2)
 | 
						||
      }
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Low voltage disconnect 3 low voltage alarm status.
 | 
						||
                   Return value 1 = alarm inactive, 2 = alarm active."
 | 
						||
   	::= { alarmStatus 14 }
 | 
						||
 | 
						||
   batteryResistanceAlarmStatus OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER {
 | 
						||
			inactive(1),
 | 
						||
         active(2)
 | 
						||
      }
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Battery resistance alarm status.
 | 
						||
                  Return value 1 = alarm inactive, 2 = alarm active."
 | 
						||
   	::= { alarmStatus 15 }
 | 
						||
 | 
						||
   batteryCurrentAlarmStatus OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER {
 | 
						||
			inactive(1),
 | 
						||
         active(2)
 | 
						||
      }
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Battery resistance alarm status.
 | 
						||
                  Return value 1 = alarm inactive, 2 = alarm active."
 | 
						||
   	::= { alarmStatus 16 }
 | 
						||
 | 
						||
   batteryTestAbortCondition1AlarmStatus OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER {
 | 
						||
			inactive(1),
 | 
						||
         active(2)
 | 
						||
      }
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Battery test abort condition 1 alarm status.
 | 
						||
                  Return value 1 = alarm inactive, 2 = alarm active."
 | 
						||
   	::= { alarmStatus 17 }
 | 
						||
 | 
						||
   batteryTestAbortCondition2AlarmStatus OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER {
 | 
						||
			inactive(1),
 | 
						||
         active(2)
 | 
						||
      }
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Battery test abort condition 2 alarm status.
 | 
						||
                  Return value 1 = alarm inactive, 2 = alarm active."
 | 
						||
   	::= { alarmStatus 18 }
 | 
						||
 | 
						||
   batteryTestAbortCondition3AlarmStatus OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER {
 | 
						||
			inactive(1),
 | 
						||
         active(2)
 | 
						||
      }
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Battery test abort condition 3 alarm status.
 | 
						||
                  Return value 1 = alarm inactive, 2 = alarm active."
 | 
						||
   	::= { alarmStatus 19 }
 | 
						||
 | 
						||
   batteryDisconnectAlarmStatus OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER {
 | 
						||
			inactive(1),
 | 
						||
         active(2)
 | 
						||
      }
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Battery disconnect alarm status.
 | 
						||
                  Return value 1 = alarm inactive, 2 = alarm active."
 | 
						||
   	::= { alarmStatus 20 }
 | 
						||
 | 
						||
   fuseAlarmStatus OBJECT-TYPE
 | 
						||
   	SYNTAX		INTEGER {
 | 
						||
			inactive(1),
 | 
						||
         active(2)
 | 
						||
      }
 | 
						||
   	ACCESS		read-only
 | 
						||
   	STATUS		mandatory
 | 
						||
   	DESCRIPTION	"Fuse alarm status.
 | 
						||
                  Return value 1 = alarm inactive, 2 = alarm active."
 | 
						||
   	::= { alarmStatus 21 }
 | 
						||
 | 
						||
-- *********************************************************************
 | 
						||
-- readOnlyObjects.digitalSensorAlarms definition
 | 
						||
-- *********************************************************************
 | 
						||
 | 
						||
	digitalSensorAlarms OBJECT IDENTIFIER ::= { readOnlyObjects 5 }
 | 
						||
 | 
						||
   breakerTrap TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
      --#SEVERITY CRITICAL
 | 
						||
   	DESCRIPTION "Breaker has tripped."
 | 
						||
   	::= 0
 | 
						||
 | 
						||
   fuseTrap TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
      --#SEVERITY CRITICAL
 | 
						||
   	DESCRIPTION "Fuse has opened."
 | 
						||
   	::= 1
 | 
						||
 | 
						||
   batteryDisconnectTrap TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
      --#SEVERITY CRITICAL
 | 
						||
   	DESCRIPTION "Battery disconnect has operated."
 | 
						||
   	::= 2
 | 
						||
 | 
						||
   programmableTrap TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
   	DESCRIPTION "Programmable alarm has occurred."
 | 
						||
      --#SEVERITY CRITICAL
 | 
						||
   	::= 3
 | 
						||
 | 
						||
-- *********************************************************************
 | 
						||
-- readOnlyObjects.SystemAlarms definition
 | 
						||
-- *********************************************************************
 | 
						||
 | 
						||
	systemAlarms OBJECT IDENTIFIER ::= { readOnlyObjects 6 }
 | 
						||
 | 
						||
   highVoltageTrap TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
   	DESCRIPTION "Float voltage has exceeded preset value.
 | 
						||
                  Return value: High voltage alarm XX.X volts."
 | 
						||
      --#SEVERITY WARNING
 | 
						||
   	::= 4
 | 
						||
 | 
						||
   lowVoltageTrap TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
   	DESCRIPTION "Float voltage is below preset value.
 | 
						||
                  Return value: Low voltage alarm XX.X volts."
 | 
						||
      --#SEVERITY WARNING
 | 
						||
   	::= 5
 | 
						||
 | 
						||
   loadOverCurrentTrap TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
   	DESCRIPTION "Load current has exceeded preset value.
 | 
						||
                  Return value: Load over current alarm XXXX amps."
 | 
						||
      --#SEVERITY WARNING
 | 
						||
   	::= 6
 | 
						||
 | 
						||
   batteryFloatCurrentTrap TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
   	DESCRIPTION "Battery float current has exceeded preset value.
 | 
						||
                  Return value: Battery float current alarm XXXX amps."
 | 
						||
      --#SEVERITY CRITICAL
 | 
						||
   	::= 7
 | 
						||
 | 
						||
   loadDisconnect1VoltageTrap TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
   	DESCRIPTION "Load disconnect 1 voltage has dropped below preset value.
 | 
						||
                  Return value: Load disconnect 1 voltage XX.X volts."
 | 
						||
      --#SEVERITY CRITICAL
 | 
						||
   	::= 8
 | 
						||
 | 
						||
   loadDisconnect2VoltageTrap TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
   	DESCRIPTION "Load disconnect 2 voltage has dropped below preset value.
 | 
						||
                  Return value: Load disconnect 2 voltage XX.X volts."
 | 
						||
      --#SEVERITY CRITICAL
 | 
						||
   	::= 9
 | 
						||
 | 
						||
   loadDisconnect3VoltageTrap TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
   	DESCRIPTION "Load disconnect 3 voltage has dropped below preset value.
 | 
						||
                  Return value: Load disconnect 3 voltage XX.X volts."
 | 
						||
      --#SEVERITY CRITICAL
 | 
						||
   	::= 10
 | 
						||
 | 
						||
   loadDisconnect1TemperatureTrap TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
   	DESCRIPTION "Load disconnect 1 temperature has exceeded preset value.
 | 
						||
                  Return value: Load disconnect 1 temperature alarm XX <20>C."
 | 
						||
      --#SEVERITY CRITICAL
 | 
						||
   	::= 11
 | 
						||
 | 
						||
   loadDisconnect2TemperatureTrap TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
   	DESCRIPTION "Load disconnect 2 temperature has exceeded preset value.
 | 
						||
                  Return value: Load disconnect 2 temperature alarm XX <20>C."
 | 
						||
      --#SEVERITY CRITICAL
 | 
						||
   	::= 12
 | 
						||
 | 
						||
   loadDisconnect3TemperatureTrap TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
   	DESCRIPTION "Load disconnect 3 temperature has exceeded preset value.
 | 
						||
                  Return value: Load disconnect 3 temperature alarm XX <20>C."
 | 
						||
      --#SEVERITY CRITICAL
 | 
						||
   	::= 13
 | 
						||
 | 
						||
   rectifierFailureTrap TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
   	DESCRIPTION "Rectifier failure.
 | 
						||
                  Return value: Rectifier failure."
 | 
						||
      --#SEVERITY WARNING
 | 
						||
   	::= 14
 | 
						||
 | 
						||
   fanFailureTrap TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
   	DESCRIPTION "Rectifier fan has failed.
 | 
						||
                  Return value: Fan failure."
 | 
						||
      --#SEVERITY CRITICAL
 | 
						||
   	::= 15
 | 
						||
 | 
						||
   acFailureTrap TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
   	DESCRIPTION "Rectifier has lost AC input power.
 | 
						||
                  Return value: AC failure."
 | 
						||
      --#SEVERITY CRITICAL
 | 
						||
   	::= 16
 | 
						||
 | 
						||
   majorFailureTrap TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
   	DESCRIPTION "Multiple failures of AC, rectififers, fans or a programmed alarm.
 | 
						||
                  Return value: Multiple AC, fan, rectifier or optional alarm failures has occurred."
 | 
						||
      --#SEVERITY CRITICAL
 | 
						||
   	::= 17
 | 
						||
 | 
						||
   batteryResistanceTrap TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
   	DESCRIPTION "Battery resistance has increased by a programmed percentage.
 | 
						||
                  Return value: Battery resistance alarm X.XXXX ohms, XXX %."
 | 
						||
      --#SEVERITY WARNING
 | 
						||
   	::= 18
 | 
						||
 | 
						||
   batteryTestAbort1Trap TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
   	DESCRIPTION "Battery failure abort 1 has occured during battery resistance test.
 | 
						||
                  Return value: Battery test failure: Abort 1."
 | 
						||
      --#SEVERITY CRITICAL
 | 
						||
   	::= 19
 | 
						||
 | 
						||
   batteryTestAbort2Trap TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
   	DESCRIPTION "Battery failure abort 2 has occured during battery resistance test.
 | 
						||
                  Return value: Battery test failure: Abort 2."
 | 
						||
      --#SEVERITY CRITICAL
 | 
						||
   	::= 20
 | 
						||
 | 
						||
   batteryTestAbort3Trap TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
   	DESCRIPTION "Battery failure abort 3 has occured during battery resistance test.
 | 
						||
                  Return value: Battery test failure: Abort 3."
 | 
						||
      --#SEVERITY CRITICAL
 | 
						||
   	::= 21
 | 
						||
 | 
						||
-- *********************************************************************
 | 
						||
-- readOnlyObjects.digitalSensorAlarmClears definition
 | 
						||
-- *********************************************************************
 | 
						||
 | 
						||
	digitalSensorAlarmClears OBJECT IDENTIFIER ::= { readOnlyObjects 7 }
 | 
						||
 | 
						||
   breakerTrapClear TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
   	DESCRIPTION "Breaker alarm has been cleared."
 | 
						||
      --#SEVERITY INFORMATIONAL
 | 
						||
   	::= 100
 | 
						||
 | 
						||
   fuseTrapClear TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
   	DESCRIPTION "Fuse alarm has been cleared."
 | 
						||
      --#SEVERITY INFORMATIONAL
 | 
						||
   	::= 101
 | 
						||
 | 
						||
   batteryDisconnectTrapClear TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
   	DESCRIPTION "Battery disconnect alarm has been cleared."
 | 
						||
      --#SEVERITY INFORMATIONAL
 | 
						||
   	::= 102
 | 
						||
 | 
						||
   programmableTrapClear TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
   	DESCRIPTION "Programmable alarm has been cleared."
 | 
						||
      --#SEVERITY INFORMATIONAL
 | 
						||
   	::= 103
 | 
						||
 | 
						||
-- *********************************************************************
 | 
						||
-- readOnlyObjects.SystemAlarmClears definition
 | 
						||
-- *********************************************************************
 | 
						||
 | 
						||
	systemAlarmClears OBJECT IDENTIFIER ::= { readOnlyObjects 8 }
 | 
						||
 | 
						||
   highVoltageTrapClear TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
   	DESCRIPTION "High voltage alarm has been cleared."
 | 
						||
      --#SEVERITY INFORMATIONAL
 | 
						||
   	::= 104
 | 
						||
 | 
						||
   lowVoltageTrapClear TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
   	DESCRIPTION "Low voltage alarm has been cleared."
 | 
						||
      --#SEVERITY INFORMATIONAL
 | 
						||
      ::= 105
 | 
						||
 | 
						||
   loadOverCurrentTrapClear TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
   	DESCRIPTION "Load over current alarm has been cleared."
 | 
						||
      --#SEVERITY INFORMATIONAL
 | 
						||
   	::= 106
 | 
						||
 | 
						||
   batteryFloatCurrentTrapClear TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
   	DESCRIPTION "Battery float current alarm has been cleared."
 | 
						||
      --#SEVERITY INFORMATIONAL
 | 
						||
   	::= 107
 | 
						||
 | 
						||
   loadDisconnect1VoltageTrapClear TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
   	DESCRIPTION "Load disconnect 1 voltage alarm has been cleared."
 | 
						||
      --#SEVERITY INFORMATIONAL
 | 
						||
   	::= 108
 | 
						||
 | 
						||
   loadDisconnect2VoltageTrapClear TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
   	DESCRIPTION "Load disconnect 2 voltage alarm has been cleared."
 | 
						||
      --#SEVERITY INFORMATIONAL
 | 
						||
   	::= 109
 | 
						||
 | 
						||
   loadDisconnect3VoltageTrapClear TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
   	DESCRIPTION "Load disconnect 3 voltage alarm has been cleared."
 | 
						||
      --#SEVERITY INFORMATIONAL
 | 
						||
   	::= 110
 | 
						||
 | 
						||
   loadDisconnect1TemperatureTrapClear TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
   	DESCRIPTION "Load disconnect 1 temperature alarm has been cleared."
 | 
						||
      --#SEVERITY INFORMATIONAL
 | 
						||
   	::= 111
 | 
						||
 | 
						||
   loadDisconnect2TemperatureTrapClear TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
   	DESCRIPTION "Load disconnect 2 temperature alarm has been cleared."
 | 
						||
      --#SEVERITY INFORMATIONAL
 | 
						||
   	::= 112
 | 
						||
 | 
						||
   loadDisconnect3TemperatureTrapClear TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
   	DESCRIPTION "Load disconnect 3 temperature alarm has been cleared."
 | 
						||
      --#SEVERITY INFORMATIONAL
 | 
						||
   	::= 113
 | 
						||
 | 
						||
   rectifierFailureTrapClear TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
   	DESCRIPTION "Rectififer failure alarm has been cleared."
 | 
						||
      --#SEVERITY INFORMATIONAL
 | 
						||
   	::= 114
 | 
						||
 | 
						||
   fanFailureTrapClear TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
   	DESCRIPTION "Fan failure alarm has been cleared."
 | 
						||
      --#SEVERITY INFORMATIONAL
 | 
						||
   	::= 115
 | 
						||
 | 
						||
   acFailureTrapClear TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
   	DESCRIPTION "AC failure alarm been cleared."
 | 
						||
      --#SEVERITY INFORMATIONAL
 | 
						||
   	::= 116
 | 
						||
 | 
						||
   majorFailureTrapClear TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
   	DESCRIPTION "Major failure alarm has been cleared."
 | 
						||
      --#SEVERITY INFORMATIONAL
 | 
						||
   	::= 117
 | 
						||
 | 
						||
   batteryResistanceTrapClear TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
   	DESCRIPTION "Battery resistance alarm has been cleared."
 | 
						||
      --#SEVERITY INFORMATIONAL
 | 
						||
   	::= 118
 | 
						||
 | 
						||
   batteryTestAbort1TrapClear TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
   	DESCRIPTION "Battery test abort 1 alarm has been cleared."
 | 
						||
      --#SEVERITY INFORMATIONAL
 | 
						||
   	::= 119
 | 
						||
 | 
						||
   batteryTestAbort2TrapClear TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
   	DESCRIPTION "Battery test abort 2 alarm has been cleared."
 | 
						||
      --#SEVERITY INFORMATIONAL
 | 
						||
   	::= 120
 | 
						||
 | 
						||
   batteryTestAbort3TrapClear TRAP-TYPE
 | 
						||
   	ENTERPRISE ccpower
 | 
						||
   	DESCRIPTION "Battery test abort 3 alarm has been cleared."
 | 
						||
      --#SEVERITY INFORMATIONAL
 | 
						||
   	::= 121
 | 
						||
 | 
						||
END
 | 
						||
 | 
						||
 |