diff --git a/MIBS/liebert/LIEBERT-GP-FLEXIBLE-COND-MIB b/MIBS/liebert/LIEBERT-GP-FLEXIBLE-COND-MIB
new file mode 100644
index 0000000..43b1dbb
--- /dev/null
+++ b/MIBS/liebert/LIEBERT-GP-FLEXIBLE-COND-MIB
@@ -0,0 +1,5534 @@
+LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB DEFINITIONS ::= BEGIN
+
+IMPORTS
+ MODULE-IDENTITY,
+ OBJECT-IDENTITY
+ FROM SNMPv2-SMI
+ liebertFlexibleConditionsModuleReg
+ FROM LIEBERT-GP-REGISTRATION-MIB
+ lgpFlexConditions
+ FROM LIEBERT-GP-CONDITIONS-MIB
+ ;
+
+-- =============================================================================
+-- Module Identification and Registration
+-- =============================================================================
+
+liebertGlobalProductsFlexibleConditionsModule MODULE-IDENTITY
+ LAST-UPDATED "201810020000Z"
+ ORGANIZATION "Liebert Corporation"
+ CONTACT-INFO
+ "Contact: Technical Support
+
+ Postal:
+ Liebert Corporation
+ 1050 Dearborn Drive
+ P.O. Box 29186
+ Columbus OH, 43229
+ US
+
+ Tel: +1 (800) 222-5877
+
+ E-mail: liebert.monitoring@vertivco.com
+ Web: www.vertivco.com"
+
+ DESCRIPTION
+ "The MIB module used to register Liebert SNMP OIDs.
+
+ Copyright 2000-2018 Liebert Corporation. All rights reserved.
+ Reproduction of this document is authorized on the condition
+ that the forgoing copyright notice is included.
+
+ This Specification is supplied 'AS IS' and Liebert Corporation
+ makes no warranty, either express or implied, as to the use,
+ operation, condition, or performance of the Specification."
+
+ REVISION "201810020000Z"
+ DESCRIPTION
+ "Compiled From GDD Version: 6825.1"
+
+
+ ::= { liebertFlexibleConditionsModuleReg 1 }
+
+-- =============================================================================
+-- lgpFlexConditions - Liebert Conditions Registrations
+-- =============================================================================
+
+lgpFlexConditionsWellKnown OBJECT IDENTIFIER
+ -- STATUS current
+ -- DESCRIPTION
+ -- "Liebert well known conditions are defined by OIDs that
+ -- reside in this sub-tree."
+ ::= { lgpFlexConditions 1 }
+
+-- =============================================================================
+-- lgpFlexConditionsWellKnown - Liebert "well-known" Conditions
+-- =============================================================================
+
+lgpCondId4122SystemInputPowerProblem OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The input is not qualified to provide power to the system."
+ ::= { lgpFlexConditionsWellKnown 4122 }
+
+lgpCondId4132BypassOverloadPhaseA OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "An overload exists on output phase A while operating on the bypass."
+ ::= { lgpFlexConditionsWellKnown 4132 }
+
+lgpCondId4133BypassOverloadPhaseB OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "An overload exists on output phase B while operating on the bypass."
+ ::= { lgpFlexConditionsWellKnown 4133 }
+
+lgpCondId4134BypassOverloadPhaseC OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "An overload exists on output phase C while operating on the bypass."
+ ::= { lgpFlexConditionsWellKnown 4134 }
+
+lgpCondId4135BypassNotAvailable OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A problem associated with the bypass has been detected."
+ ::= { lgpFlexConditionsWellKnown 4135 }
+
+lgpCondId4137BypassAutoRetransferPrimed OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Automatic retransfer from bypass to inverter is possible."
+ ::= { lgpFlexConditionsWellKnown 4137 }
+
+lgpCondId4138BypassAutoRetransferFailed OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "After performing a recoverable transfer to bypass, an attempt to
+ auto retransfer from bypass to inverter failed."
+ ::= { lgpFlexConditionsWellKnown 4138 }
+
+lgpCondId4139BypassExcessAutoRetransfers OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The number of auto retransfers, from bypass to inverter, has
+ exceeded the maximum for a specified time interval."
+ ::= { lgpFlexConditionsWellKnown 4139 }
+
+lgpCondId4140BypassRestartInhibitExternal OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Restart of the bypass is inhibited by the state of an external
+ signal."
+ ::= { lgpFlexConditionsWellKnown 4140 }
+
+lgpCondId4141BypassBreakerClosed OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The bypass breaker is closed."
+ ::= { lgpFlexConditionsWellKnown 4141 }
+
+lgpCondId4142BypassStaticSwitchOverload OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Bypass off due to static switch overload."
+ ::= { lgpFlexConditionsWellKnown 4142 }
+
+lgpCondId4143BypassStaticSwitchUnavailable OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The static bypass is unavailable to support the critical load."
+ ::= { lgpFlexConditionsWellKnown 4143 }
+
+lgpCondId4144BypassExcessivePulseParallel OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has performed too many pulse parallel operations within
+ a specified time interval."
+ ::= { lgpFlexConditionsWellKnown 4144 }
+
+lgpCondId4145BypassAutoTransferFailed OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "An automatic transfer to static bypass failed."
+ ::= { lgpFlexConditionsWellKnown 4145 }
+
+lgpCondId4146SystemInputPhsRotationError OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The power conductors on the input line are not wired to the UPS in
+ the sequence preferred for the rectifier (A-B-C)."
+ ::= { lgpFlexConditionsWellKnown 4146 }
+
+lgpCondId4147SystemInputCurrentLimit OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The RMS input current has reached the input current limit
+ threshold."
+ ::= { lgpFlexConditionsWellKnown 4147 }
+
+lgpCondId4162BatteryLow OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The calculated battery time remaining has reached the low battery
+ threshold."
+ ::= { lgpFlexConditionsWellKnown 4162 }
+
+lgpCondId4163OutputOffEndofDischarge OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Output turned off due to battery reaching end-of-discharge."
+ ::= { lgpFlexConditionsWellKnown 4163 }
+
+lgpCondId4164BatteryChargingError OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The battery is not charging properly."
+ ::= { lgpFlexConditionsWellKnown 4164 }
+
+lgpCondId4165BatteryChargingReducedExtrnl OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Using a reduced battery charging algorithm due to an external
+ signal."
+ ::= { lgpFlexConditionsWellKnown 4165 }
+
+lgpCondId4166BatteryCapacityLow OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Battery capacity is low."
+ ::= { lgpFlexConditionsWellKnown 4166 }
+
+lgpCondId4167OutputOff OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Output is off."
+ ::= { lgpFlexConditionsWellKnown 4167 }
+
+lgpCondId4168BatteryDischarging OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The battery is discharging."
+ ::= { lgpFlexConditionsWellKnown 4168 }
+
+lgpCondId4169BatteryTemperatureImbalance OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Excessive temperature differences between battery sensors detected."
+ ::= { lgpFlexConditionsWellKnown 4169 }
+
+lgpCondId4170BatteryEqualize OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The rectifier output voltage is increased to equalize the battery
+ voltage level."
+ ::= { lgpFlexConditionsWellKnown 4170 }
+
+lgpCondId4171BatteryManualTestInProgress OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Manual battery test is in progress."
+ ::= { lgpFlexConditionsWellKnown 4171 }
+
+lgpCondId4172BatteryAutoTestInProgress OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Automatic battery test is in progress."
+ ::= { lgpFlexConditionsWellKnown 4172 }
+
+lgpCondId4173MainBatteryDisconnectOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Main battery disconnect is open."
+ ::= { lgpFlexConditionsWellKnown 4173 }
+
+lgpCondId4174BatteryTemperatureSensorFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A battery temperature sensor fault has been detected."
+ ::= { lgpFlexConditionsWellKnown 4174 }
+
+lgpCondId4175BypassFrequencyError OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The bypass frequency is outside the inverter synchronization
+ limits."
+ ::= { lgpFlexConditionsWellKnown 4175 }
+
+lgpCondId4176BatteryCircuitBreaker1Open OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Battery circuit breaker 1 is open."
+ ::= { lgpFlexConditionsWellKnown 4176 }
+
+lgpCondId4177BatteryBreaker1OpenFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Battery circuit breaker 1 failed to open."
+ ::= { lgpFlexConditionsWellKnown 4177 }
+
+lgpCondId4178BatteryBreaker1CloseFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Battery circuit breaker 1 failed to close."
+ ::= { lgpFlexConditionsWellKnown 4178 }
+
+lgpCondId4179BatteryCircuitBreaker2Open OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Battery circuit breaker 2 is open."
+ ::= { lgpFlexConditionsWellKnown 4179 }
+
+lgpCondId4180BatteryBreaker2OpenFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Battery circuit breaker 2 failed to open."
+ ::= { lgpFlexConditionsWellKnown 4180 }
+
+lgpCondId4181BatteryBreaker2CloseFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Battery circuit breaker 2 failed to close."
+ ::= { lgpFlexConditionsWellKnown 4181 }
+
+lgpCondId4182BatteryCircuitBreaker3Open OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Battery circuit breaker 3 is open."
+ ::= { lgpFlexConditionsWellKnown 4182 }
+
+lgpCondId4183BatteryBreaker3OpenFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Battery circuit breaker 3 failed to open."
+ ::= { lgpFlexConditionsWellKnown 4183 }
+
+lgpCondId4184BatteryBreaker3CloseFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Battery circuit breaker 3 failed to close."
+ ::= { lgpFlexConditionsWellKnown 4184 }
+
+lgpCondId4185BatteryCircuitBreaker4Open OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Battery circuit breaker 4 is open."
+ ::= { lgpFlexConditionsWellKnown 4185 }
+
+lgpCondId4186BatteryBreaker4OpenFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Battery circuit breaker 4 failed to open."
+ ::= { lgpFlexConditionsWellKnown 4186 }
+
+lgpCondId4187BatteryBreaker4CloseFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Battery circuit breaker 4 failed to close."
+ ::= { lgpFlexConditionsWellKnown 4187 }
+
+lgpCondId4188BatteryCircuitBreaker5Open OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Battery circuit breaker 5 is open."
+ ::= { lgpFlexConditionsWellKnown 4188 }
+
+lgpCondId4189BatteryBreaker5OpenFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Battery circuit breaker 5 failed to open."
+ ::= { lgpFlexConditionsWellKnown 4189 }
+
+lgpCondId4190BatteryBreaker5CloseFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Battery circuit breaker 5 failed to close."
+ ::= { lgpFlexConditionsWellKnown 4190 }
+
+lgpCondId4191BatteryCircuitBreaker6Open OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Battery circuit breaker 6 is open."
+ ::= { lgpFlexConditionsWellKnown 4191 }
+
+lgpCondId4192BatteryBreaker6OpenFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Battery circuit breaker 6 failed to open."
+ ::= { lgpFlexConditionsWellKnown 4192 }
+
+lgpCondId4193BatteryBreaker6CloseFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Battery circuit breaker 6 failed to close."
+ ::= { lgpFlexConditionsWellKnown 4193 }
+
+lgpCondId4194BatteryCircuitBreaker7Open OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Battery circuit breaker 7 is open."
+ ::= { lgpFlexConditionsWellKnown 4194 }
+
+lgpCondId4195BatteryBreaker7OpenFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Battery circuit breaker 7 failed to open."
+ ::= { lgpFlexConditionsWellKnown 4195 }
+
+lgpCondId4196BatteryBreaker7CloseFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Battery circuit breaker 7 failed to close."
+ ::= { lgpFlexConditionsWellKnown 4196 }
+
+lgpCondId4197BatteryCircuitBreaker8Open OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Battery circuit breaker 8 is open."
+ ::= { lgpFlexConditionsWellKnown 4197 }
+
+lgpCondId4198BatteryBreaker8OpenFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Battery circuit breaker 8 failed to open."
+ ::= { lgpFlexConditionsWellKnown 4198 }
+
+lgpCondId4199BatteryBreaker8CloseFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Battery circuit breaker 8 failed to close."
+ ::= { lgpFlexConditionsWellKnown 4199 }
+
+lgpCondId4200BatteryChargingInhibited OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Battery charging is inhibited due to an external inhibit signal."
+ ::= { lgpFlexConditionsWellKnown 4200 }
+
+lgpCondId4213SystemShutdownEPO OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "System shutdown due to Emergency Power Off (EPO)."
+ ::= { lgpFlexConditionsWellKnown 4213 }
+
+lgpCondId4214SystemShutdownREPO OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "System shutdown due to Remote Emergency Power Off (REPO)."
+ ::= { lgpFlexConditionsWellKnown 4214 }
+
+lgpCondId4215SystemOutputOff OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system output is off."
+ ::= { lgpFlexConditionsWellKnown 4215 }
+
+lgpCondId4216BypassBackfeedDetected OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system detected a voltage on the bypass when none was expected."
+ ::= { lgpFlexConditionsWellKnown 4216 }
+
+lgpCondId4217BypassManualXfrInhibited OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Manual transfer from inverter to bypass is inhibited - bypass not
+ qualified."
+ ::= { lgpFlexConditionsWellKnown 4217 }
+
+lgpCondId4218BypassManualRexfrInhibited OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Manual transfer from bypass to inverter is inhibited - inverter
+ output not qualified."
+ ::= { lgpFlexConditionsWellKnown 4218 }
+
+lgpCondId4219BatteryOverTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A battery temperature sensor is reporting a value above a
+ threshold."
+ ::= { lgpFlexConditionsWellKnown 4219 }
+
+lgpCondId4220BatteryExternalMonitor1 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "External battery monitor 1 - battery maintenance required."
+ ::= { lgpFlexConditionsWellKnown 4220 }
+
+lgpCondId4221BatteryExternalMonitor2 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "External battery monitor 2 - battery maintenance required."
+ ::= { lgpFlexConditionsWellKnown 4221 }
+
+lgpCondId4222BatteryGroundFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Battery system ground fault amperage exceeds the threshold."
+ ::= { lgpFlexConditionsWellKnown 4222 }
+
+lgpCondId4229EmergencyPowerOffLatched OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "System output is off - 'Emergency Power Off (EPO) - latched'
+ requires manual reset."
+ ::= { lgpFlexConditionsWellKnown 4229 }
+
+lgpCondId4230SystemOutputLowPowerFactor OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system output power factor is low, resulting in reduced output
+ capacity."
+ ::= { lgpFlexConditionsWellKnown 4230 }
+
+lgpCondId4231OutputCurrentExceedsThreshold OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Output current for one or more phases exceeds a threshold."
+ ::= { lgpFlexConditionsWellKnown 4231 }
+
+lgpCondId4233InverterFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Inverter failure - inverter output is off."
+ ::= { lgpFlexConditionsWellKnown 4233 }
+
+lgpCondId4234InverterOverloadPhaseA OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Inverter is operating with an overload on phase A."
+ ::= { lgpFlexConditionsWellKnown 4234 }
+
+lgpCondId4235InverterOverloadPhaseB OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Inverter is operating with an overload on phase B."
+ ::= { lgpFlexConditionsWellKnown 4235 }
+
+lgpCondId4236InverterOverloadPhaseC OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Inverter is operating with an overload on phase C."
+ ::= { lgpFlexConditionsWellKnown 4236 }
+
+lgpCondId4237InverterInhibitExternal OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Restart of the inverter is inhibited by an external signal."
+ ::= { lgpFlexConditionsWellKnown 4237 }
+
+lgpCondId4238InverterOutBreakerOpenFail OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Inverter output breaker failed to open."
+ ::= { lgpFlexConditionsWellKnown 4238 }
+
+lgpCondId4239InverterOutBreakerCloseFail OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Inverter output breaker failed to close."
+ ::= { lgpFlexConditionsWellKnown 4239 }
+
+lgpCondId4270InputContact01 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The external input contact 1."
+ ::= { lgpFlexConditionsWellKnown 4270 }
+
+lgpCondId4271InputContact02 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The external input contact 2."
+ ::= { lgpFlexConditionsWellKnown 4271 }
+
+lgpCondId4272InputContact03 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The external input contact 3."
+ ::= { lgpFlexConditionsWellKnown 4272 }
+
+lgpCondId4273InputContact04 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The external input contact 4."
+ ::= { lgpFlexConditionsWellKnown 4273 }
+
+lgpCondId4274InputContact05 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The external input contact 5."
+ ::= { lgpFlexConditionsWellKnown 4274 }
+
+lgpCondId4275InputContact06 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The external input contact 6."
+ ::= { lgpFlexConditionsWellKnown 4275 }
+
+lgpCondId4276InputContact07 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The external input contact 7."
+ ::= { lgpFlexConditionsWellKnown 4276 }
+
+lgpCondId4277InputContact08 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The external input contact 8."
+ ::= { lgpFlexConditionsWellKnown 4277 }
+
+lgpCondId4278InputContact09 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The external input contact 9."
+ ::= { lgpFlexConditionsWellKnown 4278 }
+
+lgpCondId4279InputContact10 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The external input contact 10."
+ ::= { lgpFlexConditionsWellKnown 4279 }
+
+lgpCondId4280InputContact11 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The external input contact 11."
+ ::= { lgpFlexConditionsWellKnown 4280 }
+
+lgpCondId4281InputContact12 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The external input contact 12."
+ ::= { lgpFlexConditionsWellKnown 4281 }
+
+lgpCondId4282InputContact13 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The external input contact 13."
+ ::= { lgpFlexConditionsWellKnown 4282 }
+
+lgpCondId4283InputContact14 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The external input contact 14."
+ ::= { lgpFlexConditionsWellKnown 4283 }
+
+lgpCondId4284InputContact15 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The external input contact 15."
+ ::= { lgpFlexConditionsWellKnown 4284 }
+
+lgpCondId4285InputContact16 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The external input contact 16."
+ ::= { lgpFlexConditionsWellKnown 4285 }
+
+lgpCondId4286OutputAmpOverUserLimitPhsA OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The phase A output has exceeded the user amperage threshold."
+ ::= { lgpFlexConditionsWellKnown 4286 }
+
+lgpCondId4287OutputAmpOverUserLimitPhsB OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The phase B output has exceeded the user amperage threshold."
+ ::= { lgpFlexConditionsWellKnown 4287 }
+
+lgpCondId4288OutputAmpOverUserLimitPhsC OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The phase C output has exceeded the user amperage threshold."
+ ::= { lgpFlexConditionsWellKnown 4288 }
+
+lgpCondId4289InverterTransferInhibitExt OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Transfer of critical bus source to inverter is inhibited by an
+ external signal."
+ ::= { lgpFlexConditionsWellKnown 4289 }
+
+lgpCondId4290InverterShutdownOverload OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The inverter has shutdown due to a sustained overload."
+ ::= { lgpFlexConditionsWellKnown 4290 }
+
+lgpCondId4294InletAirOverTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The inlet air exceeds the maximum temperature threshold."
+ ::= { lgpFlexConditionsWellKnown 4294 }
+
+lgpCondId4295RectifierFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Rectifier failure - rectifier is off."
+ ::= { lgpFlexConditionsWellKnown 4295 }
+
+lgpCondId4296RectifierOperationInhibitExt OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The operation of the rectifier is inhibited by an external signal."
+ ::= { lgpFlexConditionsWellKnown 4296 }
+
+lgpCondId4297UPSOutputonInverter OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The output power is supplied by the inverter."
+ ::= { lgpFlexConditionsWellKnown 4297 }
+
+lgpCondId4298UPSOutputonBypass OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The output power is supplied by the bypass."
+ ::= { lgpFlexConditionsWellKnown 4298 }
+
+lgpCondId4299OutputLoadonMaintBypass OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The output power is supplied by the maintenance bypass."
+ ::= { lgpFlexConditionsWellKnown 4299 }
+
+lgpCondId4300InternalCommunicationsFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The control has detected a communication failure of a component on
+ the internal communication bus."
+ ::= { lgpFlexConditionsWellKnown 4300 }
+
+lgpCondId4308DCBusGroundFaultPositive OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A ground fault has been detected on the positive DC Bus link."
+ ::= { lgpFlexConditionsWellKnown 4308 }
+
+lgpCondId4309DCBusGroundFaultNegative OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A ground fault has been detected on the negative DC Bus link."
+ ::= { lgpFlexConditionsWellKnown 4309 }
+
+lgpCondId4310EquipmentOverTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Equipment over temperature summary event."
+ ::= { lgpFlexConditionsWellKnown 4310 }
+
+lgpCondId4311SystemFanFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "System fan failure - one or more fans have failed."
+ ::= { lgpFlexConditionsWellKnown 4311 }
+
+lgpCondId4313PasswordChanged OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Password changed."
+ ::= { lgpFlexConditionsWellKnown 4313 }
+
+lgpCondId4314PowerSupplyFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Power supply failure."
+ ::= { lgpFlexConditionsWellKnown 4314 }
+
+lgpCondId4315OnGenerator OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A generator is supplying the power to the system."
+ ::= { lgpFlexConditionsWellKnown 4315 }
+
+lgpCondId4316AutoRestartInProgress OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Auto restart is in progress."
+ ::= { lgpFlexConditionsWellKnown 4316 }
+
+lgpCondId4317AutoRestartInhibitedExt OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Auto restart inhibited due to an external signal."
+ ::= { lgpFlexConditionsWellKnown 4317 }
+
+lgpCondId4320InitiatedTransfertoBypass OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "User initiated manual transfer to bypass."
+ ::= { lgpFlexConditionsWellKnown 4320 }
+
+lgpCondId4321InitiatedTransfertoInverter OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "User initiated manual transfer to inverter."
+ ::= { lgpFlexConditionsWellKnown 4321 }
+
+lgpCondId4322BatteryTestPassed OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Battery test passed."
+ ::= { lgpFlexConditionsWellKnown 4322 }
+
+lgpCondId4323BatteryTestFailed OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Battery test failed."
+ ::= { lgpFlexConditionsWellKnown 4323 }
+
+lgpCondId4324BatteryTestManuallyStopped OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The battery test was manually stopped prior to completion."
+ ::= { lgpFlexConditionsWellKnown 4324 }
+
+lgpCondId4325BackfeedBreakerOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The backfeed breaker is in the open position."
+ ::= { lgpFlexConditionsWellKnown 4325 }
+
+lgpCondId4341VelocityAuthenticationFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Notification of a message rejected by Velocity due to an
+ authentication failure."
+ ::= { lgpFlexConditionsWellKnown 4341 }
+
+lgpCondId4360ReceptacleOverCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a receptacle over current condition."
+ ::= { lgpFlexConditionsWellKnown 4360 }
+
+lgpCondId4361ReceptacleUnderCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a receptacle under current condition."
+ ::= { lgpFlexConditionsWellKnown 4361 }
+
+lgpCondId4382SystemInputCurrentImbalance OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "System Input Currents are Imbalanced."
+ ::= { lgpFlexConditionsWellKnown 4382 }
+
+lgpCondId4383BypassStaticSwitchOffExtrnl OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Bypass static switch is off due to the state of an external signal."
+ ::= { lgpFlexConditionsWellKnown 4383 }
+
+lgpCondId4384BatteryEoDDisconnect OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Battery disconnect due to end-of-discharge."
+ ::= { lgpFlexConditionsWellKnown 4384 }
+
+lgpCondId4389SystemOutputFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A fault has been detected in the system output."
+ ::= { lgpFlexConditionsWellKnown 4389 }
+
+lgpCondId4390InverterOffExternal OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Inverter is off (operation is inhibited) due to external signal
+ state."
+ ::= { lgpFlexConditionsWellKnown 4390 }
+
+lgpCondId4391InverterStaticSwitchSCRShort OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a short across one or more inverter static
+ switch Silicon Controlled Rectifiers (SCR)."
+ ::= { lgpFlexConditionsWellKnown 4391 }
+
+lgpCondId4392TemperatureSensorError OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "One or more temperature sensors cannot provide a valid temperature
+ reading (i.e. sensor failure, wiring failure, sense circuit
+ failure, etc)."
+ ::= { lgpFlexConditionsWellKnown 4392 }
+
+lgpCondId4406BranchOverCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a module over current condition."
+ ::= { lgpFlexConditionsWellKnown 4406 }
+
+lgpCondId4407BranchUnderCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a module under current condition."
+ ::= { lgpFlexConditionsWellKnown 4407 }
+
+lgpCondId4416BranchOverCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a module over current condition."
+ ::= { lgpFlexConditionsWellKnown 4416 }
+
+lgpCondId4417BranchUnderCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a module under current condition."
+ ::= { lgpFlexConditionsWellKnown 4417 }
+
+lgpCondId4421BranchFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "One or more conditions indicate a Branch Receptacle Module failure
+ , service is required."
+ ::= { lgpFlexConditionsWellKnown 4421 }
+
+lgpCondId4436PDUOverCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a module over current condition."
+ ::= { lgpFlexConditionsWellKnown 4436 }
+
+lgpCondId4437PDUUnderCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a module under current condition."
+ ::= { lgpFlexConditionsWellKnown 4437 }
+
+lgpCondId4438SystemInternalTemperatureRise OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Excessive temperature rise internal to the system (i.e. difference
+ between the output versus input temperature is too large)."
+ ::= { lgpFlexConditionsWellKnown 4438 }
+
+lgpCondId4439AutomaticRestartFailed OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Automatic restart failed."
+ ::= { lgpFlexConditionsWellKnown 4439 }
+
+lgpCondId4440FuseFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A summary event indicating one or more fuse failures."
+ ::= { lgpFlexConditionsWellKnown 4440 }
+
+lgpCondId4441SystemControllerError OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "System controller internal error."
+ ::= { lgpFlexConditionsWellKnown 4441 }
+
+lgpCondId4442SystemBreakersOpenFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "One or more breakers in the system failed to open."
+ ::= { lgpFlexConditionsWellKnown 4442 }
+
+lgpCondId4448PDUOverCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a module over current condition."
+ ::= { lgpFlexConditionsWellKnown 4448 }
+
+lgpCondId4449PDUUnderCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a module under current condition."
+ ::= { lgpFlexConditionsWellKnown 4449 }
+
+lgpCondId4468PDUOverCurrentL1 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a module over current condition on line 1."
+ ::= { lgpFlexConditionsWellKnown 4468 }
+
+lgpCondId4469PDUOverCurrentL2 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a module over current condition on line 2."
+ ::= { lgpFlexConditionsWellKnown 4469 }
+
+lgpCondId4470PDUOverCurrentL3 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a module over current condition on line 3."
+ ::= { lgpFlexConditionsWellKnown 4470 }
+
+lgpCondId4471PDUUnderCurrentL1 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a module under current condition on line 1."
+ ::= { lgpFlexConditionsWellKnown 4471 }
+
+lgpCondId4472PDUUnderCurrentL2 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a module under current condition on line 2."
+ ::= { lgpFlexConditionsWellKnown 4472 }
+
+lgpCondId4473PDUUnderCurrentL3 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a module under current condition on line 3."
+ ::= { lgpFlexConditionsWellKnown 4473 }
+
+lgpCondId4492ReceptaclePowerStateOn OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The receptacle power state changed to the ON state."
+ ::= { lgpFlexConditionsWellKnown 4492 }
+
+lgpCondId4493ReceptaclePowerStateOff OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The receptacle power state changed to the OFF state."
+ ::= { lgpFlexConditionsWellKnown 4493 }
+
+lgpCondId4494BranchBreakerOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The Branch Receptacle Module's input breaker is open."
+ ::= { lgpFlexConditionsWellKnown 4494 }
+
+lgpCondId4495DeviceConfigurationChange OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Device Configuration Change."
+ ::= { lgpFlexConditionsWellKnown 4495 }
+
+lgpCondId4496BasicDisplayModuleRemoved OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Basic Display Module Removed."
+ ::= { lgpFlexConditionsWellKnown 4496 }
+
+lgpCondId4497BasicDisplayModuleDiscovered OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Basic Display Module Discovered."
+ ::= { lgpFlexConditionsWellKnown 4497 }
+
+lgpCondId4500PDUOverCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a power module over current condition."
+ ::= { lgpFlexConditionsWellKnown 4500 }
+
+lgpCondId4501PDUUnderCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a power module under current condition."
+ ::= { lgpFlexConditionsWellKnown 4501 }
+
+lgpCondId4502PDUFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "One or more conditions indicate a power module failure, service is
+ required."
+ ::= { lgpFlexConditionsWellKnown 4502 }
+
+lgpCondId4503PDUCommunicationFail OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Internal communications failure with the Power Module."
+ ::= { lgpFlexConditionsWellKnown 4503 }
+
+lgpCondId4504BranchRemoved OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Branch Receptacle Module Removed."
+ ::= { lgpFlexConditionsWellKnown 4504 }
+
+lgpCondId4505BranchDiscovered OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Branch Receptacle Module Discovered."
+ ::= { lgpFlexConditionsWellKnown 4505 }
+
+lgpCondId4506BranchOverCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a Branch Receptacle Module over current
+ condition."
+ ::= { lgpFlexConditionsWellKnown 4506 }
+
+lgpCondId4507BranchCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a Branch Receptacle Module under current
+ condition."
+ ::= { lgpFlexConditionsWellKnown 4507 }
+
+lgpCondId4508ReceptacleLoadRemoved OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The receptacle's load stopped drawing power."
+ ::= { lgpFlexConditionsWellKnown 4508 }
+
+lgpCondId4509ReceptacleLoadAdded OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The receptacle's load started to draw power."
+ ::= { lgpFlexConditionsWellKnown 4509 }
+
+lgpCondId4523ModuleRemoved OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Module Removed."
+ ::= { lgpFlexConditionsWellKnown 4523 }
+
+lgpCondId4524ModuleAdded OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Module Added."
+ ::= { lgpFlexConditionsWellKnown 4524 }
+
+lgpCondId4550FirmwareUpdateRequired OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Module compatibility error requires a system firmware update to
+ resolve."
+ ::= { lgpFlexConditionsWellKnown 4550 }
+
+lgpCondId4551GenericTestEvent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A generic test event designed to evaluate system handling of
+ events."
+ ::= { lgpFlexConditionsWellKnown 4551 }
+
+lgpCondId4580OverTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "An over temperature condition was detected."
+ ::= { lgpFlexConditionsWellKnown 4580 }
+
+lgpCondId4581UnderTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "An under temperature condition was detected."
+ ::= { lgpFlexConditionsWellKnown 4581 }
+
+lgpCondId4588OverRelativeHumidity OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "An over relative humidity condition was detected."
+ ::= { lgpFlexConditionsWellKnown 4588 }
+
+lgpCondId4589UnderRelativeHumidity OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "An under relative humidity condition was detected."
+ ::= { lgpFlexConditionsWellKnown 4589 }
+
+lgpCondId4601ExternalAirSensorAOverTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "[Ext Air Sensor A Temperature] has exceeded [External Air Over
+ Temp Threshold]."
+ ::= { lgpFlexConditionsWellKnown 4601 }
+
+lgpCondId4604ExternalAirSensorBOverTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "[Ext Air Sensor B Temperature] has exceeded [External Air Over
+ Temp Threshold]."
+ ::= { lgpFlexConditionsWellKnown 4604 }
+
+lgpCondId4608ExtAirSensorAUnderTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "[Ext Air Sensor A Temperature] has dropped below [Ext Air Under
+ Temp Threshold]."
+ ::= { lgpFlexConditionsWellKnown 4608 }
+
+lgpCondId4611ExtAirSensorBUnderTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "[Ext Air Sensor B Temperature] has dropped below [Ext Air Under
+ Temp Threshold]."
+ ::= { lgpFlexConditionsWellKnown 4611 }
+
+lgpCondId4615ExtDewPointOverTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "At least one dew point temperature reading ([Ext Air Sensor A Dew
+ Point Temp], [Ext Air Sensor B Dew Point Temp]...) has exceeded
+ [Ext Dew Point Over Temp Threshold]."
+ ::= { lgpFlexConditionsWellKnown 4615 }
+
+lgpCondId4618ExternalAirSensorAIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The external air sensor A is disconnected or the signal is out of
+ range."
+ ::= { lgpFlexConditionsWellKnown 4618 }
+
+lgpCondId4621ExternalAirSensorBIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The external air sensor B is disconnected or the signal is out of
+ range."
+ ::= { lgpFlexConditionsWellKnown 4621 }
+
+lgpCondId4626SupplyChilledWaterOverTemp OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "[Supply Fluid Temperature] has exceeded [High Supply Fluid
+ Temperature Threshold]."
+ ::= { lgpFlexConditionsWellKnown 4626 }
+
+lgpCondId4629SupplyChilledWaterTempSensorIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The supply chilled water temperature sensor is disconnected or the
+ signal is out of range."
+ ::= { lgpFlexConditionsWellKnown 4629 }
+
+lgpCondId4634SupplyRefrigerantOverTemp OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Event that is activated when [Supply Refrigerant Temperature]
+ exceeds [Supply Refrig Over Temp Threshold]. The event is
+ deactivated when the temperature drops below the threshold."
+ ::= { lgpFlexConditionsWellKnown 4634 }
+
+lgpCondId4637SupplyRefrigerantUnderTemp OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "[Supply Refrigerant Temperature] has dropped below a specified
+ threshold."
+ ::= { lgpFlexConditionsWellKnown 4637 }
+
+lgpCondId4640SupplyRefrigerantTempSensorIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The supply refrigeramt temperature sensor is disconnected or the
+ signal is out of range."
+ ::= { lgpFlexConditionsWellKnown 4640 }
+
+lgpCondId4645SupplyFluidOverTemp OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "[Supply Fluid Temperature] has exceeded [Supply Fluid Over Temp
+ Threshold]."
+ ::= { lgpFlexConditionsWellKnown 4645 }
+
+lgpCondId4648SupplyFluidUnderTemp OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "[Supply Fluid Temperature] has dropped below a specified threshold."
+ ::= { lgpFlexConditionsWellKnown 4648 }
+
+lgpCondId4651SupplyFluidTempSensorIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The supply fluid temperature sensor is disconnected or the signal
+ is out of range."
+ ::= { lgpFlexConditionsWellKnown 4651 }
+
+lgpCondId4656Pump1LossofFlow OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Loss of flow is detected in pump 1. The loss of flow condition
+ occurs when no differential pressure is detected across the pump."
+ ::= { lgpFlexConditionsWellKnown 4656 }
+
+lgpCondId4659Pump2LossofFlow OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Loss of flow is detected in pump 2. The loss of flow condition
+ occurs when no differential pressure is detected across the pump."
+ ::= { lgpFlexConditionsWellKnown 4659 }
+
+lgpCondId4662PumpShortCycle OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Pumps have short cycled. A short cycle is defined as turning on
+ and off a number of times over a set time period."
+ ::= { lgpFlexConditionsWellKnown 4662 }
+
+lgpCondId4669Compressor1AHighHeadPressure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Compressor 1A high head pressure."
+ ::= { lgpFlexConditionsWellKnown 4669 }
+
+lgpCondId4672Compressor1BHighHeadPressure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Compressor 1B high head pressure."
+ ::= { lgpFlexConditionsWellKnown 4672 }
+
+lgpCondId4675Compressor2AHighHeadPressure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Compressor 2A high head pressure."
+ ::= { lgpFlexConditionsWellKnown 4675 }
+
+lgpCondId4678Compressor2BHighHeadPressure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Compressor 2B high head pressure."
+ ::= { lgpFlexConditionsWellKnown 4678 }
+
+lgpCondId4681Compressor1AShortCycle OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Compressor 1A short cycle. A short cycle is defined as turning on
+ and off a number of times over a set time period."
+ ::= { lgpFlexConditionsWellKnown 4681 }
+
+lgpCondId4684Compressor1BShortCycle OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Compressor 1B short cycle. A short cycle is defined as turning on
+ and off a number of times over a set time period."
+ ::= { lgpFlexConditionsWellKnown 4684 }
+
+lgpCondId4687Compressor2AShortCycle OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Compressor 2A short cycle. A short cycle is defined as turning on
+ and off a number of times over a set time period."
+ ::= { lgpFlexConditionsWellKnown 4687 }
+
+lgpCondId4690Compressor2BShortCycle OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Compressor 2B short cycle. A short cycle is defined as turning on
+ and off a number of times over a set time period."
+ ::= { lgpFlexConditionsWellKnown 4690 }
+
+lgpCondId4693Tandem1LowSuctionPressure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "'Tandem compressors' 1 low suction pressure."
+ ::= { lgpFlexConditionsWellKnown 4693 }
+
+lgpCondId4696Tandem2LowSuctionPressure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "'Tandem compressors' 2 low suction pressure."
+ ::= { lgpFlexConditionsWellKnown 4696 }
+
+lgpCondId4703ChilledWaterControlValvePosition OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Chilled water valve out of position. Chilled water control valve
+ position does not match expected value."
+ ::= { lgpFlexConditionsWellKnown 4703 }
+
+lgpCondId4711SystemCondensationDetected OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "System condensation detected."
+ ::= { lgpFlexConditionsWellKnown 4711 }
+
+lgpCondId4714ShutdownLossOfPower OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "System lost power. This event becomes active when the unit is
+ powered on following an unexpected loss of power."
+ ::= { lgpFlexConditionsWellKnown 4714 }
+
+lgpCondId4720SmokeDetected OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Smoke detected."
+ ::= { lgpFlexConditionsWellKnown 4720 }
+
+lgpCondId4723WaterUnderFloor OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Water under the floor is detected."
+ ::= { lgpFlexConditionsWellKnown 4723 }
+
+lgpCondId4726ServiceRequired OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Unit requires servicing."
+ ::= { lgpFlexConditionsWellKnown 4726 }
+
+lgpCondId4729FanIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "One or more fans are not operating within their operational
+ parameters."
+ ::= { lgpFlexConditionsWellKnown 4729 }
+
+lgpCondId4732ReceptacleLoadDropped OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The receptacle's load is not drawing power."
+ ::= { lgpFlexConditionsWellKnown 4732 }
+
+lgpCondId4740BatteryAutomaticTestInhibited OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Automatic (scheduled) battery tests are inhibited."
+ ::= { lgpFlexConditionsWellKnown 4740 }
+
+lgpCondId4741BatterySelfTest OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Battery self test is in progress."
+ ::= { lgpFlexConditionsWellKnown 4741 }
+
+lgpCondId4742BatteryLowShutdown OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Battery disconnect due to end-of-discharge."
+ ::= { lgpFlexConditionsWellKnown 4742 }
+
+lgpCondId4747EquipmentTemperatureSensorFail OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "One or more temperature sensors report a temperature outside of
+ the range of expected operation."
+ ::= { lgpFlexConditionsWellKnown 4747 }
+
+lgpCondId4749SystemFanFailureRedundant OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Redundant system fan failure."
+ ::= { lgpFlexConditionsWellKnown 4749 }
+
+lgpCondId4750MultipleFanFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Multiple fan failure."
+ ::= { lgpFlexConditionsWellKnown 4750 }
+
+lgpCondId4753MainControllerFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A Main Controller fault has been detected."
+ ::= { lgpFlexConditionsWellKnown 4753 }
+
+lgpCondId4754SystemBreakersCloseFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "One or more breakers in the system failed to close."
+ ::= { lgpFlexConditionsWellKnown 4754 }
+
+lgpCondId4755InputFilterCycleLock OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The input filter disconnect is open due to exceeding the maximum
+ number of cycles."
+ ::= { lgpFlexConditionsWellKnown 4755 }
+
+lgpCondId4756ServiceCodeActive OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Service code is running."
+ ::= { lgpFlexConditionsWellKnown 4756 }
+
+lgpCondId4757LBSActive OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The Load Bus Sync option is active."
+ ::= { lgpFlexConditionsWellKnown 4757 }
+
+lgpCondId4758LBSInhibited OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that conditions to perform Load Bus Sync
+ are not satisfied."
+ ::= { lgpFlexConditionsWellKnown 4758 }
+
+lgpCondId4759LeadingPowerFactor OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The leading output Power Factor has fallen below a specified value."
+ ::= { lgpFlexConditionsWellKnown 4759 }
+
+lgpCondId4760ControlsResetRequired OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A controls reset is required due to one or more critical settings
+ changing."
+ ::= { lgpFlexConditionsWellKnown 4760 }
+
+lgpCondId4823ParallelCommWarning OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Parallel communication bus warning."
+ ::= { lgpFlexConditionsWellKnown 4823 }
+
+lgpCondId4824SystemCommFail OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Failure of a device on the multi-module system communication bus."
+ ::= { lgpFlexConditionsWellKnown 4824 }
+
+lgpCondId4825LossofRedundancy OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The multi-module collection doesn't have enough modules to satisfy
+ the redundancy configuration."
+ ::= { lgpFlexConditionsWellKnown 4825 }
+
+lgpCondId4826BPSSStartupInhibit OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The Bypass Static Switch startup is inhibited."
+ ::= { lgpFlexConditionsWellKnown 4826 }
+
+lgpCondId4827MMSTransferInhibit OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The critical load can not be manually transferred from inverter to
+ bypass."
+ ::= { lgpFlexConditionsWellKnown 4827 }
+
+lgpCondId4828MMSRetransferInhibit OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The critical load can not be manually retransferred from bypass to
+ inverter."
+ ::= { lgpFlexConditionsWellKnown 4828 }
+
+lgpCondId4830MMSLossofSyncPulse OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Multi-module system loss of sync pulse."
+ ::= { lgpFlexConditionsWellKnown 4830 }
+
+lgpCondId4831MMSOverload OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Multi-module system overload."
+ ::= { lgpFlexConditionsWellKnown 4831 }
+
+lgpCondId4834MMSOnBattery OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The multi-module system is on battery."
+ ::= { lgpFlexConditionsWellKnown 4834 }
+
+lgpCondId4835MMSLowBatteryWarning OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Multi-module system low battery warning."
+ ::= { lgpFlexConditionsWellKnown 4835 }
+
+lgpCondId4906LowAmbientTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a low ambient temperature condition."
+ ::= { lgpFlexConditionsWellKnown 4906 }
+
+lgpCondId4907HighAmbientTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a high ambient temperature condition."
+ ::= { lgpFlexConditionsWellKnown 4907 }
+
+lgpCondId4908LowOverallVoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a low battery string overall voltage
+ condition."
+ ::= { lgpFlexConditionsWellKnown 4908 }
+
+lgpCondId4909HighOverallVoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a high battery string overall voltage
+ condition."
+ ::= { lgpFlexConditionsWellKnown 4909 }
+
+lgpCondId4910HighBatteryStringCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a high battery string current condition."
+ ::= { lgpFlexConditionsWellKnown 4910 }
+
+lgpCondId4911LowBatteryStringFloatCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a low battery string float current
+ condition."
+ ::= { lgpFlexConditionsWellKnown 4911 }
+
+lgpCondId4912HighBatteryStringFloatCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a high battery string float current
+ condition."
+ ::= { lgpFlexConditionsWellKnown 4912 }
+
+lgpCondId4913HighBatteryStringRippleCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a high battery string ripple current
+ condition."
+ ::= { lgpFlexConditionsWellKnown 4913 }
+
+lgpCondId4914BatteryStringDischargeDetected OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a battery string discharge condition."
+ ::= { lgpFlexConditionsWellKnown 4914 }
+
+lgpCondId4915MaximumDischargeTimeExceeded OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an excessive discharge time condition."
+ ::= { lgpFlexConditionsWellKnown 4915 }
+
+lgpCondId4916DischargeLowOverallVoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a low battery string overall voltage
+ condition during a discharge."
+ ::= { lgpFlexConditionsWellKnown 4916 }
+
+lgpCondId4917DischargeLowCellVoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a low cell voltage condition during a
+ discharge."
+ ::= { lgpFlexConditionsWellKnown 4917 }
+
+lgpCondId4918DischargeHighBatteryStringCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a high battery string current condition
+ during a discharge."
+ ::= { lgpFlexConditionsWellKnown 4918 }
+
+lgpCondId4919ExcessiveCelltoCellTemperatureDeviation OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an excessive cell to cell temperature
+ deviation condition."
+ ::= { lgpFlexConditionsWellKnown 4919 }
+
+lgpCondId4920ExcessiveCelltoAmbientTemperatureDeviation OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an excessive cell to ambient temperature
+ deviation condition."
+ ::= { lgpFlexConditionsWellKnown 4920 }
+
+lgpCondId4964LowCellVoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a low cell voltage condition."
+ ::= { lgpFlexConditionsWellKnown 4964 }
+
+lgpCondId4965HighCellVoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a high cell voltage condition."
+ ::= { lgpFlexConditionsWellKnown 4965 }
+
+lgpCondId4966LowCellTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a low cell temperature condition."
+ ::= { lgpFlexConditionsWellKnown 4966 }
+
+lgpCondId4967HighCellTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a high cell temperature condition."
+ ::= { lgpFlexConditionsWellKnown 4967 }
+
+lgpCondId4968LowInternalResistance OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a low internal resistance condition."
+ ::= { lgpFlexConditionsWellKnown 4968 }
+
+lgpCondId4969HighInternalResistance OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a high internal resistance condition."
+ ::= { lgpFlexConditionsWellKnown 4969 }
+
+lgpCondId4970HighIntercellResistance OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a high intercell resistance condition."
+ ::= { lgpFlexConditionsWellKnown 4970 }
+
+lgpCondId4978IntertierResistanceHigh OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a high intertier resistance condition."
+ ::= { lgpFlexConditionsWellKnown 4978 }
+
+lgpCondId4980SupplyChilledWaterLossofFlow OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Supply chilled water or glycol flow is too low."
+ ::= { lgpFlexConditionsWellKnown 4980 }
+
+lgpCondId4983SupplyRefrigOverTempBand1 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "[Supply Refrigerant Temperature] is above the upper threshold
+ specified by [Supply Refrig Temp Band 1]."
+ ::= { lgpFlexConditionsWellKnown 4983 }
+
+lgpCondId4986SupplyRefrigUnderTempBand1 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "[Supply Refrigerant Temperature] is below the lower threshold
+ specified by [Supply Refrig Temp Band 1]."
+ ::= { lgpFlexConditionsWellKnown 4986 }
+
+lgpCondId4990SupplyRefrigOverTempBand2 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "[Supply Refrigerant Temperature] is above the upper threshold
+ specified by [Supply Refrig Temp Band 2]."
+ ::= { lgpFlexConditionsWellKnown 4990 }
+
+lgpCondId4993SupplyRefrigUnderTempBand2 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "[Supply Refrigerant Temperature] is below the lower threshold
+ specified by [Supply Refrig Temp Band 2]."
+ ::= { lgpFlexConditionsWellKnown 4993 }
+
+lgpCondId4996Inverter1ShortCycle OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Inverter for pump 1 has short cycled and is temporarily locked out
+ from further operation to protect from thermal overload. A short
+ cycle is defined as powering on and off a number of times over a
+ set time period."
+ ::= { lgpFlexConditionsWellKnown 4996 }
+
+lgpCondId4999Inverter2ShortCycle OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Inverter for pump 2 has short cycled and is temporarily locked out
+ from further operation to protect from thermal overload. A short
+ cycle is defined as powering on and off a number of times over a
+ set time period."
+ ::= { lgpFlexConditionsWellKnown 4999 }
+
+lgpCondId5015SupplyAirOverTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "[Supply Air Temperature] has exceeded [High Supply Air Temperature
+ Threshold]."
+ ::= { lgpFlexConditionsWellKnown 5015 }
+
+lgpCondId5019SupplyAirUnderTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "[Supply Air Temperature] has dropped below [Low Supply Air
+ Temperature Threshold]."
+ ::= { lgpFlexConditionsWellKnown 5019 }
+
+lgpCondId5023ReturnAirOverTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "[Return Air Temperature] has exceeded [High Return Air Temperature
+ Threshold]."
+ ::= { lgpFlexConditionsWellKnown 5023 }
+
+lgpCondId5026SupplyAirSensorIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The air sensor at the outlet of the unit is disconnected or the
+ signal is out of range."
+ ::= { lgpFlexConditionsWellKnown 5026 }
+
+lgpCondId5034HighReturnHumidity OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "[Return Humidity] has exceeded [High Return Humidity Threshold]."
+ ::= { lgpFlexConditionsWellKnown 5034 }
+
+lgpCondId5036LowReturnHumidity OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "[Return Humidity] has dropped below [Low Return Humidity
+ Threshold]."
+ ::= { lgpFlexConditionsWellKnown 5036 }
+
+lgpCondId5037HumidifierHoursExceeded OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Operating hours for the humidifier have exceeded the threshold."
+ ::= { lgpFlexConditionsWellKnown 5037 }
+
+lgpCondId5038DehumidifierHoursExceeded OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Operating hours for the dehumidifier have exceeded the threshold."
+ ::= { lgpFlexConditionsWellKnown 5038 }
+
+lgpCondId5039HumidifierUnderCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The electrical current to the humidifier has dropped below its
+ lower threshold."
+ ::= { lgpFlexConditionsWellKnown 5039 }
+
+lgpCondId5040HumidifierOverCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The electrical current to the humidifier has exceeded its upper
+ threshold."
+ ::= { lgpFlexConditionsWellKnown 5040 }
+
+lgpCondId5041HumidifierLowWater OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The water level in the humidifier has dropped below its threshold."
+ ::= { lgpFlexConditionsWellKnown 5041 }
+
+lgpCondId5042HumidifierCylinderWorn OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Humidifier cylinder is not operating properly and needs to be
+ replaced."
+ ::= { lgpFlexConditionsWellKnown 5042 }
+
+lgpCondId5043HumidifierIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Humidifier issue detected, causing it to be locked out."
+ ::= { lgpFlexConditionsWellKnown 5043 }
+
+lgpCondId5044ExtHumidifierLockout OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The humidifier is shut down and disabled by an external input
+ signal."
+ ::= { lgpFlexConditionsWellKnown 5044 }
+
+lgpCondId5045HumidifierControlBoardNotDetected OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Humidifier control board is required to be connected, but no
+ signal is detected."
+ ::= { lgpFlexConditionsWellKnown 5045 }
+
+lgpCondId5046ReturnHumidityOutOfProportionalBand OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "[Return Humidity] has exceeded the upper limit of
+ [Dehumidification Proportional Band], or has dropped below the
+ lower limit of [Humidification Proportional Band] ], for an
+ extended period of time."
+ ::= { lgpFlexConditionsWellKnown 5046 }
+
+lgpCondId5053LossofAirFlow OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "No air flow through the unit due to failure of all fans."
+ ::= { lgpFlexConditionsWellKnown 5053 }
+
+lgpCondId5054FanHoursExceeded OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Operating hours for the unit blower fan have exceeded the
+ threshold."
+ ::= { lgpFlexConditionsWellKnown 5054 }
+
+lgpCondId5055TopFanIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The top fan is not operating within its normal parameters."
+ ::= { lgpFlexConditionsWellKnown 5055 }
+
+lgpCondId5056BottomFanIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The bottom fan is not operating within its normal parameters."
+ ::= { lgpFlexConditionsWellKnown 5056 }
+
+lgpCondId5060RemoteSensorIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Remote sensor is disconnected or the signal is out of range."
+ ::= { lgpFlexConditionsWellKnown 5060 }
+
+lgpCondId5062Compressor1LowSuctionPressure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Compressor 1 low suction pressure."
+ ::= { lgpFlexConditionsWellKnown 5062 }
+
+lgpCondId5063Compressor1HoursExceeded OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Operating hours for compressor 1 have exceeded the threshold."
+ ::= { lgpFlexConditionsWellKnown 5063 }
+
+lgpCondId5064DigScrollComp1TempSensorIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Digital scroll compressor 1 temperature sensor is disconnected or
+ the signal is out of range."
+ ::= { lgpFlexConditionsWellKnown 5064 }
+
+lgpCondId5065DigScrollComp1OverTemp OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Digital scroll compressor 1 shut off because its head temperature
+ has exceeded the upper threshold."
+ ::= { lgpFlexConditionsWellKnown 5065 }
+
+lgpCondId5066Compressor1LowPressureTransducerIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Compressor 1 low pressure transducer is disconnected or the signal
+ is out of range."
+ ::= { lgpFlexConditionsWellKnown 5066 }
+
+lgpCondId5067ExtCompressorLockout OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The compressor is shut down and disabled by an external input
+ signal."
+ ::= { lgpFlexConditionsWellKnown 5067 }
+
+lgpCondId5068ReheaterOverTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The temperature of the reheater has exceeded its threshold."
+ ::= { lgpFlexConditionsWellKnown 5068 }
+
+lgpCondId5069ElectricReheater1HoursExceeded OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Operating hours for electric reheater 1 have exceeded the
+ threshold."
+ ::= { lgpFlexConditionsWellKnown 5069 }
+
+lgpCondId5070ExtReheatLockout OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The reheater is shut down and disabled by an external input signal."
+ ::= { lgpFlexConditionsWellKnown 5070 }
+
+lgpCondId5071Condenser1Issue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Condenser 1 is not operating within its normal parameters."
+ ::= { lgpFlexConditionsWellKnown 5071 }
+
+lgpCondId5072CondenserVFDIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The condenser fan Variable Frequency Drive is offline."
+ ::= { lgpFlexConditionsWellKnown 5072 }
+
+lgpCondId5073CondenserTVSSIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The condenser Transient Voltage Surge Suppressor or Surge
+ Protection Device has failed."
+ ::= { lgpFlexConditionsWellKnown 5073 }
+
+lgpCondId5104ExtOverTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A temperature has exceeded its threshold, as indicated by an
+ external input signal."
+ ::= { lgpFlexConditionsWellKnown 5104 }
+
+lgpCondId5105ExtLossofFlow OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Loss of flow is detected, as indicated by an external input signal."
+ ::= { lgpFlexConditionsWellKnown 5105 }
+
+lgpCondId5106ExtCondenserPumpHighWater OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "High water is detected in the condensate pump by the auxiliary
+ float, as indicated by an external input signal."
+ ::= { lgpFlexConditionsWellKnown 5106 }
+
+lgpCondId5107ExtStandbyGlycolPumpOn OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The standby glycol pump is on, as indicated by an external input
+ signal."
+ ::= { lgpFlexConditionsWellKnown 5107 }
+
+lgpCondId5108ExternalFireDetected OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Fire detected, as indicated by an external input signal."
+ ::= { lgpFlexConditionsWellKnown 5108 }
+
+lgpCondId5109UnitOn OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Unit was turned on."
+ ::= { lgpFlexConditionsWellKnown 5109 }
+
+lgpCondId5110UnitOff OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Unit was turned off."
+ ::= { lgpFlexConditionsWellKnown 5110 }
+
+lgpCondId5111UnitStandby OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Unit was placed in standby mode."
+ ::= { lgpFlexConditionsWellKnown 5111 }
+
+lgpCondId5112UnitPartialShutdown OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "An event has occurred requiring some system components to be
+ shutdown and disabled."
+ ::= { lgpFlexConditionsWellKnown 5112 }
+
+lgpCondId5113UnitShutdown OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "An event has occurred requiring the unit to be shutdown and
+ disabled to prevent damage to the system."
+ ::= { lgpFlexConditionsWellKnown 5113 }
+
+lgpCondId5114WaterLeakageDetectorSensorIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The water leakage detector sensor is disconnected or the signal is
+ out of range."
+ ::= { lgpFlexConditionsWellKnown 5114 }
+
+lgpCondId5115BMSCommunicationsTimeout OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Building Management System (or external monitoring system) has not
+ communicated with the system within the expected timeframe."
+ ::= { lgpFlexConditionsWellKnown 5115 }
+
+lgpCondId5116MaintenanceDue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The calculated maintenance date has been reached."
+ ::= { lgpFlexConditionsWellKnown 5116 }
+
+lgpCondId5117MaintenanceCompleted OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Maintenance has been completed on the unit."
+ ::= { lgpFlexConditionsWellKnown 5117 }
+
+lgpCondId5118CloggedAirFilter OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Air filter is dirty and needs to be (cleaned or) replaced."
+ ::= { lgpFlexConditionsWellKnown 5118 }
+
+lgpCondId5119RAMBatteryIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "RAM or RAM backup battery is not operating correctly."
+ ::= { lgpFlexConditionsWellKnown 5119 }
+
+lgpCondId5120MasterUnitCommunicationLost OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Communication with master unit has been lost."
+ ::= { lgpFlexConditionsWellKnown 5120 }
+
+lgpCondId5121HighPowerShutdown OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Supply to high power components has been shutdown."
+ ::= { lgpFlexConditionsWellKnown 5121 }
+
+lgpCondId5126DigScrollComp2OverTemp OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Digital scroll compressor 2 shut off because its head temperature
+ has exceeded the upper threshold."
+ ::= { lgpFlexConditionsWellKnown 5126 }
+
+lgpCondId5144OutputOfUf OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The output frequency has exceeded a specified range for a
+ specified period of time."
+ ::= { lgpFlexConditionsWellKnown 5144 }
+
+lgpCondId5145MMSModuleAlarmActive OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Active alarm or fault of any module in a multi-module system."
+ ::= { lgpFlexConditionsWellKnown 5145 }
+
+lgpCondId5146CompressorPumpDownIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Unable to pump down suction-side pressure during compressor
+ shutdown."
+ ::= { lgpFlexConditionsWellKnown 5146 }
+
+lgpCondId5147ReturnAirSensorIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The air sensor at the inlet of the unit is disconnected or the
+ signal is out of range."
+ ::= { lgpFlexConditionsWellKnown 5147 }
+
+lgpCondId5148CompressorHighPressureTransducerIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Compressor high pressure transducer is disconnected or the signal
+ is out of range."
+ ::= { lgpFlexConditionsWellKnown 5148 }
+
+lgpCondId5149BatteryNotQualified OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The UPS battery voltage is not qualified. This event will be
+ detected even in the absence of battery disconnect or when it is
+ open."
+ ::= { lgpFlexConditionsWellKnown 5149 }
+
+lgpCondId5150BatteryTerminalsReversed OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The measured battery voltage is a negative value due to reverse
+ battery terminal connections."
+ ::= { lgpFlexConditionsWellKnown 5150 }
+
+lgpCondId5151BatteryConverterFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Battery converter failure. This is a summary event caused by one
+ or more power sub-modules in a UPS module."
+ ::= { lgpFlexConditionsWellKnown 5151 }
+
+lgpCondId5152InverterSCROpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an open across one or more inverter static
+ switch Silicon Controlled Rectifiers."
+ ::= { lgpFlexConditionsWellKnown 5152 }
+
+lgpCondId5153LoadSharingFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Difference between any phase inverter current of unit and the
+ relevant average output current of parallel system is more than a
+ specific percent of nominal current."
+ ::= { lgpFlexConditionsWellKnown 5153 }
+
+lgpCondId5154DCBusAbnormal OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an abnormal DC Bus Voltage."
+ ::= { lgpFlexConditionsWellKnown 5154 }
+
+lgpCondId5155MainsInputNeutralLost OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Loss of neutral in the input source is detected."
+ ::= { lgpFlexConditionsWellKnown 5155 }
+
+lgpCondId5156LoadImpactTransfer OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "On bypass as result of load impact."
+ ::= { lgpFlexConditionsWellKnown 5156 }
+
+lgpCondId5157UserOperationInvalid OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "User attempted an invalid operation."
+ ::= { lgpFlexConditionsWellKnown 5157 }
+
+lgpCondId5158PowerSubModuleFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "One or more failures detected in power module, inverter or
+ rectifier."
+ ::= { lgpFlexConditionsWellKnown 5158 }
+
+lgpCondId5178OutputOvervoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "One or more of the output phase voltages has exceeded the limit."
+ ::= { lgpFlexConditionsWellKnown 5178 }
+
+lgpCondId5179OutputUndervoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "One or more of the output phase voltages has dropped below the
+ limit."
+ ::= { lgpFlexConditionsWellKnown 5179 }
+
+lgpCondId5180OutputOvercurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "One or more of the phase currents has exceeded the limit."
+ ::= { lgpFlexConditionsWellKnown 5180 }
+
+lgpCondId5181NeutralOvercurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system's neutral current has exceeded the limit."
+ ::= { lgpFlexConditionsWellKnown 5181 }
+
+lgpCondId5182GroundOvercurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "System ground current has exceeded the limit."
+ ::= { lgpFlexConditionsWellKnown 5182 }
+
+lgpCondId5183OutputVoltageTHD OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The Total Harmonic Distortion of the voltage on one or more of the
+ output phases has exceeded the limit."
+ ::= { lgpFlexConditionsWellKnown 5183 }
+
+lgpCondId5184OutputFrequencyError OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The output frequency is outside a specified range."
+ ::= { lgpFlexConditionsWellKnown 5184 }
+
+lgpCondId5185TransformerOvertemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Indicates a unit transformer overtemperature condition."
+ ::= { lgpFlexConditionsWellKnown 5185 }
+
+lgpCondId5212PanelSummaryStatus OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The status for the panel. Detects and annunciates upon occurrence
+ of any branch or panelboard main breaker active event."
+ ::= { lgpFlexConditionsWellKnown 5212 }
+
+lgpCondId5213PanelOvervoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "One or more of the phase voltages of this panel has exceeded the
+ limit."
+ ::= { lgpFlexConditionsWellKnown 5213 }
+
+lgpCondId5214PanelUndervoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "One or more of the phase voltages of this panel is less than the
+ limit."
+ ::= { lgpFlexConditionsWellKnown 5214 }
+
+lgpCondId5215PanelOvercurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "One or more of the phase currents of this panel has exceeded the
+ limit."
+ ::= { lgpFlexConditionsWellKnown 5215 }
+
+lgpCondId5216PanelNeutralOvercurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The Neutral current of this panel has exceeded the limit."
+ ::= { lgpFlexConditionsWellKnown 5216 }
+
+lgpCondId5217PanelGroundOvercurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The Ground current of this panel has exceeded the limit."
+ ::= { lgpFlexConditionsWellKnown 5217 }
+
+lgpCondId5226BranchOvercurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The current in one or more phases of this branch exceeds the limit."
+ ::= { lgpFlexConditionsWellKnown 5226 }
+
+lgpCondId5227BranchUndercurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The current in one or more phases of this branch is less than the
+ limit."
+ ::= { lgpFlexConditionsWellKnown 5227 }
+
+lgpCondId5245SubfeedPhaseOvercurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "One or more of the phase currents in this subfeed has exceeded the
+ limit."
+ ::= { lgpFlexConditionsWellKnown 5245 }
+
+lgpCondId5246SubfeedNeutralOvercurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The Neutral current in this subfeed has exceeded the limit."
+ ::= { lgpFlexConditionsWellKnown 5246 }
+
+lgpCondId5247SubfeedGroundOvercurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The Ground current of this subfeed has exceeded the limit."
+ ::= { lgpFlexConditionsWellKnown 5247 }
+
+lgpCondId5249EventState OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The present state of this digital event input."
+ ::= { lgpFlexConditionsWellKnown 5249 }
+
+lgpCondId5263CompressorNotStopping OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Compressor commanded to stop, but continues to run."
+ ::= { lgpFlexConditionsWellKnown 5263 }
+
+lgpCondId5269CompressorHoursExceeded OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "[Compressor Hours] has exceeded [Compressor Hours Threshold]."
+ ::= { lgpFlexConditionsWellKnown 5269 }
+
+lgpCondId5270CompressorHighHeadPressure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Compressor is shut down due to high head pressure."
+ ::= { lgpFlexConditionsWellKnown 5270 }
+
+lgpCondId5271CompressorLowSuctionPressure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Compressor is shut down due to low suction pressure."
+ ::= { lgpFlexConditionsWellKnown 5271 }
+
+lgpCondId5272CompressorThermalOverload OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Compressor is shut down due to thermal overload."
+ ::= { lgpFlexConditionsWellKnown 5272 }
+
+lgpCondId5273CompressorLowOilPressure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Compressor low oil pressure."
+ ::= { lgpFlexConditionsWellKnown 5273 }
+
+lgpCondId5274CompressorHeadPressureOverThreshold OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Compressor head pressure has exceeded an upper threshold."
+ ::= { lgpFlexConditionsWellKnown 5274 }
+
+lgpCondId5275CompressorLossofDifferentialPressure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Compressor is shut down due to low differential pressure."
+ ::= { lgpFlexConditionsWellKnown 5275 }
+
+lgpCondId5277CondenserFanIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Condenser fan is not operating within its operational parameters."
+ ::= { lgpFlexConditionsWellKnown 5277 }
+
+lgpCondId5278LowCondenserRefrigerantPressure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Refrigerant pressure in condenser coil is too low."
+ ::= { lgpFlexConditionsWellKnown 5278 }
+
+lgpCondId5280LowFluidPressure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "[Fluid Pressure] has dropped below a specified threshold."
+ ::= { lgpFlexConditionsWellKnown 5280 }
+
+lgpCondId5293ReturnFluidOverTemp OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "[Return Fluid Temperature] has exceeded a specified threshold."
+ ::= { lgpFlexConditionsWellKnown 5293 }
+
+lgpCondId5294ReturnFluidUnderTemp OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "[Return Fluid Temperature] has dropped below a specified threshold."
+ ::= { lgpFlexConditionsWellKnown 5294 }
+
+lgpCondId5295ReturnFluidTempSensorIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The return fluid temperature sensor is disconnected or the signal
+ is out of range."
+ ::= { lgpFlexConditionsWellKnown 5295 }
+
+lgpCondId5296TeamworkReturnFluidTempSensorIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The return fluid temperature sensors for all Teamwork units are
+ disconnected or the signals are out of range."
+ ::= { lgpFlexConditionsWellKnown 5296 }
+
+lgpCondId5297AllPumpsLossofFlow OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "System is shut down due to loss of flow in all available pumps."
+ ::= { lgpFlexConditionsWellKnown 5297 }
+
+lgpCondId5300PumpHoursExceeded OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "[Pump Hours] has exceeded [Pump Hours Threshold]."
+ ::= { lgpFlexConditionsWellKnown 5300 }
+
+lgpCondId5306FreeCoolingValveHoursExceeded OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "[Free Cooling Valve Hours] has exceeded [Free Cooling Valve Hours
+ Threshold]."
+ ::= { lgpFlexConditionsWellKnown 5306 }
+
+lgpCondId5308EvaporatorInletTempSensorIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The evaporator inlet temperature sensor is disconnected or the
+ signal is out of range."
+ ::= { lgpFlexConditionsWellKnown 5308 }
+
+lgpCondId5309TeamworkEvaporatorInletTempSensorIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The evaporator inlet temperature sensors for all Teamwork units
+ are disconnected or the signals are out of range."
+ ::= { lgpFlexConditionsWellKnown 5309 }
+
+lgpCondId5310EvaporatorFluidFreezeAutoReset OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Evaporator outlet fluid temperature has dropped below the freeze
+ threshold. Evaporator has been shut down, but will restart when
+ the temperature rises above the threshold."
+ ::= { lgpFlexConditionsWellKnown 5310 }
+
+lgpCondId5311EvaporatorFluidFreezeManualResetRequired OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Evaporator outlet fluid temperature has dropped below the freeze
+ threshold. Evaporator has been shut down and requires a manual
+ reset."
+ ::= { lgpFlexConditionsWellKnown 5311 }
+
+lgpCondId5315SubgroupEventOccurredDuringCommunicationLoss OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "While subgroup unit communication was lost, an event occurred on
+ the subgroup unit. Please check subgroup unit event log."
+ ::= { lgpFlexConditionsWellKnown 5315 }
+
+lgpCondId5335ReturnAirUnderTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "[Return Air Temperature] has dropped below [Low Return Air
+ Temperature Threshold]."
+ ::= { lgpFlexConditionsWellKnown 5335 }
+
+lgpCondId5349ExtAirSensorAHighHumidity OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "[Ext Air Sensor A Humidity] has exceeded [Ext Air Sensor A High
+ Humidity Threshold]."
+ ::= { lgpFlexConditionsWellKnown 5349 }
+
+lgpCondId5351ExtAirSensorALowHumidity OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "[Ext Air Sensor A Humidity] has dropped below [Ext Air Sensor A
+ Low Humidity Threshold]."
+ ::= { lgpFlexConditionsWellKnown 5351 }
+
+lgpCondId5352CompressorShortCycle OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Compressor short cycle. A short cycle is defined as turning on and
+ off a number of times over a set time period."
+ ::= { lgpFlexConditionsWellKnown 5352 }
+
+lgpCondId5354DigScrollCompDischargeTempSensorIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Digital scroll compressor discharge temperature sensor is
+ disconnected or the signal is out of range."
+ ::= { lgpFlexConditionsWellKnown 5354 }
+
+lgpCondId5355DigScrollCompOverTemp OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Digital scroll compressor is shut down due to head temperature
+ exceeding an upper threshold."
+ ::= { lgpFlexConditionsWellKnown 5355 }
+
+lgpCondId5361ExtFreeCoolingLockout OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Free cooling is disabled by an external input signal."
+ ::= { lgpFlexConditionsWellKnown 5361 }
+
+lgpCondId5362FreeCoolingTempSensorIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The free cooling fluid temperature sensor is disconnected or the
+ signal is out of range."
+ ::= { lgpFlexConditionsWellKnown 5362 }
+
+lgpCondId5365HotWaterHotGasValveHoursExceeded OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "[Hot Water / Hot Gas Valve Hours] has exceeded [Hot Water / Hot
+ Gas Valve Hours Threshold]."
+ ::= { lgpFlexConditionsWellKnown 5365 }
+
+lgpCondId5368ElectricReheaterHoursExceeded OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "[Electric Reheater Hours] has exceeded [Electric Reheaters Hours
+ Threshold]."
+ ::= { lgpFlexConditionsWellKnown 5368 }
+
+lgpCondId5376MainFanOverload OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Main fan is shut down due to thermal overload."
+ ::= { lgpFlexConditionsWellKnown 5376 }
+
+lgpCondId5377Condenser OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Condenser is not operating within its operational parameters."
+ ::= { lgpFlexConditionsWellKnown 5377 }
+
+lgpCondId5415ExtLossofAirBlower OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Loss of air blower is detected, as indicated by an external input
+ signal."
+ ::= { lgpFlexConditionsWellKnown 5415 }
+
+lgpCondId5416ExtStandbyUnitOn OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Standby unit is on, as indicated by an external input signal."
+ ::= { lgpFlexConditionsWellKnown 5416 }
+
+lgpCondId5417DigitalOutputBoardNotDetected OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Digital output board is required to be connected, but no signal is
+ detected."
+ ::= { lgpFlexConditionsWellKnown 5417 }
+
+lgpCondId5418UnitCodeMissing OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Unit code has not been entered and saved."
+ ::= { lgpFlexConditionsWellKnown 5418 }
+
+lgpCondId5419UnitCommunicationLost OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Master has lost communication with one or more networked units."
+ ::= { lgpFlexConditionsWellKnown 5419 }
+
+lgpCondId5422OvertemperaturePowerOff OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Power turned off because equipment over temperature limit."
+ ::= { lgpFlexConditionsWellKnown 5422 }
+
+lgpCondId5423TooManySensors OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The number of sensors connected to the PDU exceeds the allowable
+ limit."
+ ::= { lgpFlexConditionsWellKnown 5423 }
+
+lgpCondId5432TransformerOvertemperaturePowerOff OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Output power shutdown due to high transformer temperature."
+ ::= { lgpFlexConditionsWellKnown 5432 }
+
+lgpCondId5433TransformerOvertemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Transformer temperature has exceeded the limit."
+ ::= { lgpFlexConditionsWellKnown 5433 }
+
+lgpCondId5434TransformerTemperatureSensorFail OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Transformer temperature sensor has failed."
+ ::= { lgpFlexConditionsWellKnown 5434 }
+
+lgpCondId5436LowAmbientTemperatureProbeTwo OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a low ambient temperature condition on
+ temperature probe 2."
+ ::= { lgpFlexConditionsWellKnown 5436 }
+
+lgpCondId5437HighAmbientTemperatureProbeTwo OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a high ambient temperature condition on
+ temperature probe 2."
+ ::= { lgpFlexConditionsWellKnown 5437 }
+
+lgpCondId5438ThermalRunawayDetected OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a thermal runaway condition."
+ ::= { lgpFlexConditionsWellKnown 5438 }
+
+lgpCondId5439BatteryStringEqualize OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a battery string equalize condition."
+ ::= { lgpFlexConditionsWellKnown 5439 }
+
+lgpCondId5440BatteryStringOffline OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the battery string is offline."
+ ::= { lgpFlexConditionsWellKnown 5440 }
+
+lgpCondId5442DischargeLowCellVoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a low cell voltage condition during a
+ discharge."
+ ::= { lgpFlexConditionsWellKnown 5442 }
+
+lgpCondId5447MMSPowerSharing OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A module is not sharing power with the other modules in a multi
+ -module system."
+ ::= { lgpFlexConditionsWellKnown 5447 }
+
+lgpCondId5453ModuleInStandbyIntelligentParalleling OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Module is placed into standby operation per Intelligent
+ Paralleling."
+ ::= { lgpFlexConditionsWellKnown 5453 }
+
+lgpCondId5456ECOModeActive OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Conditions for Activation or Automatic Reactivation have been
+ satisfied."
+ ::= { lgpFlexConditionsWellKnown 5456 }
+
+lgpCondId5457ECOModeSuspended OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "ECO Mode session is suspended."
+ ::= { lgpFlexConditionsWellKnown 5457 }
+
+lgpCondId5458ExcessECOSuspends OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Number of automatic suspensions has exceeded the ECO Mode -
+ Maximum Auto Suspensions setting."
+ ::= { lgpFlexConditionsWellKnown 5458 }
+
+lgpCondId5471DoorOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "An open door was detected."
+ ::= { lgpFlexConditionsWellKnown 5471 }
+
+lgpCondId5472DoorSensorDisconnected OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Door sensor disconnect detected."
+ ::= { lgpFlexConditionsWellKnown 5472 }
+
+lgpCondId5479ContactClosureOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "An open circuit was detected."
+ ::= { lgpFlexConditionsWellKnown 5479 }
+
+lgpCondId5480ContactClosureClosed OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A closed circuit was detected."
+ ::= { lgpFlexConditionsWellKnown 5480 }
+
+lgpCondId5492ExtSystemCondensationDetected OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "External system condensation detected."
+ ::= { lgpFlexConditionsWellKnown 5492 }
+
+lgpCondId5495ExtFanIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "One or more fans are not operating within their operational
+ parameters."
+ ::= { lgpFlexConditionsWellKnown 5495 }
+
+lgpCondId5500ExtRemoteShutdown OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Unit is shut down by a remote signal."
+ ::= { lgpFlexConditionsWellKnown 5500 }
+
+lgpCondId5505HotAisleTempOutofRange OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The air temperature in the Hot aisle is either above [Hot Aisle
+ Over Temp Threshold] or below [Hot Aisle Under Temp Threshold]."
+ ::= { lgpFlexConditionsWellKnown 5505 }
+
+lgpCondId5508ColdAisleTempOutofRange OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The air temperature in the cold aisle is either above [Cold Aisle
+ Over Temp Threshold] or below [Cold Aisle Under Temp Threshold]."
+ ::= { lgpFlexConditionsWellKnown 5508 }
+
+lgpCondId5512RemoteShutdown OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Unit is shut down by a remote signal."
+ ::= { lgpFlexConditionsWellKnown 5512 }
+
+lgpCondId5513CompressorCapacityReduced OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Compressor capacity has been reduced."
+ ::= { lgpFlexConditionsWellKnown 5513 }
+
+lgpCondId5514CompressorLowPressureTransducerIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Compressor low pressure transducer is disconnected or the signal
+ is out of range."
+ ::= { lgpFlexConditionsWellKnown 5514 }
+
+lgpCondId5524PDUNeutralOverCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a neutral over current condition."
+ ::= { lgpFlexConditionsWellKnown 5524 }
+
+lgpCondId5531CondenserCommunicationLost OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Communication with condenser unit has been lost."
+ ::= { lgpFlexConditionsWellKnown 5531 }
+
+lgpCondId5535CondenserOutsideAirTempSensorIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Condenser outside air temperature sensor is disconnected or the
+ signal is out of range."
+ ::= { lgpFlexConditionsWellKnown 5535 }
+
+lgpCondId5536CondenserOutsideAirTempOutofOperatingRange OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "[Condenser Outside Air Temperature] is either above an upper
+ threshold or below a lower threshold."
+ ::= { lgpFlexConditionsWellKnown 5536 }
+
+lgpCondId5537CondenserControlBoardIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The condenser control board is reporting an issue."
+ ::= { lgpFlexConditionsWellKnown 5537 }
+
+lgpCondId5539CondenserRefrigerantPressureOverThreshold OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Condenser refrigerant pressure has exceeded a threshold."
+ ::= { lgpFlexConditionsWellKnown 5539 }
+
+lgpCondId5540CondenserRefrigerantPressureUnderThreshold OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Condenser refrigerant pressure has dropped below a threshold."
+ ::= { lgpFlexConditionsWellKnown 5540 }
+
+lgpCondId5541CondenserRefrigerantPressureSensorIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Condenser refrigerant pressure sensor is disconnected or the
+ signal is out of range."
+ ::= { lgpFlexConditionsWellKnown 5541 }
+
+lgpCondId5542CondenserSupplyRefrigerantOverTemp OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Condenser supply refrigerant temperature has exceeded a threshold."
+ ::= { lgpFlexConditionsWellKnown 5542 }
+
+lgpCondId5543CondenserSupplyRefrigerantUnderTemp OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Condenser supply refrigerant temperature has dropped below a
+ specified threshold."
+ ::= { lgpFlexConditionsWellKnown 5543 }
+
+lgpCondId5544CondenserSupplyRefrigerantTempSensorIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Condenser supply refrigerant temperature sensor is disconnected or
+ the signal is out of range."
+ ::= { lgpFlexConditionsWellKnown 5544 }
+
+lgpCondId5545CondenserMaxFanSpeedOverride OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Fan speed exceeding the maximum set point in order to alleviate a
+ high temperature or pressure condition."
+ ::= { lgpFlexConditionsWellKnown 5545 }
+
+lgpCondId5559EvaporatorReturnFluidOverTemp OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "[Evaporator Return Fluid Temperature] has exceeded a threshold.
+ The event is deactivated when the temperature drops below the
+ threshold."
+ ::= { lgpFlexConditionsWellKnown 5559 }
+
+lgpCondId5560EvaporatorReturnFluidUnderTemp OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "[Evaporator Return Fluid Temperature] has dropped below a
+ threshold. The event is deactivated when the temperature rises
+ above the threshold."
+ ::= { lgpFlexConditionsWellKnown 5560 }
+
+lgpCondId5561LBSActiveMaster OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This UPS system has been selected as the functional Master Load
+ Bus Synchronization (LBS) system."
+ ::= { lgpFlexConditionsWellKnown 5561 }
+
+lgpCondId5562LBSActiveSlave OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This UPS system is synchronized to the output bus of the UPS
+ system that has been selected as the Master Load Bus
+ Synchronization (LBS) system."
+ ::= { lgpFlexConditionsWellKnown 5562 }
+
+lgpCondId5563DCBusLowFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The DC Bus voltage has reached a critical low level."
+ ::= { lgpFlexConditionsWellKnown 5563 }
+
+lgpCondId5564FanContactorOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The fan contactor is open."
+ ::= { lgpFlexConditionsWellKnown 5564 }
+
+lgpCondId5565FanContactorOpenFail OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The fan contactor failed to open."
+ ::= { lgpFlexConditionsWellKnown 5565 }
+
+lgpCondId5566FanContactorCloseFail OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The fan contactor failed to close."
+ ::= { lgpFlexConditionsWellKnown 5566 }
+
+lgpCondId5567IPInhibit OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The intelligent paralleling operation is inhibited."
+ ::= { lgpFlexConditionsWellKnown 5567 }
+
+lgpCondId5568InputUndervoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "One or more of the input phase voltages has dropped below the
+ limit."
+ ::= { lgpFlexConditionsWellKnown 5568 }
+
+lgpCondId5569InputOvervoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "One or more of the input phase voltages has exceeded the limit."
+ ::= { lgpFlexConditionsWellKnown 5569 }
+
+lgpCondId5573AmbientAirSensorIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Ambient air sensor is disconnected or the signal is out of range."
+ ::= { lgpFlexConditionsWellKnown 5573 }
+
+lgpCondId5577ExtDewPointUnderTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "At least one dew point temperature reading ([Ext Air Sensor A Dew
+ Point Temp], [Ext Air Sensor B Dew Point Temp]...) has dropped
+ below [Ext Dew Point Under Temp Threshold]."
+ ::= { lgpFlexConditionsWellKnown 5577 }
+
+lgpCondId5578DewPointOverTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Dew point temperature reading has exceeded the upper threshold."
+ ::= { lgpFlexConditionsWellKnown 5578 }
+
+lgpCondId5579DewPointUnderTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Dew point temperature reading has dropped below the lower
+ threshold."
+ ::= { lgpFlexConditionsWellKnown 5579 }
+
+lgpCondId5588UnspecifiedGeneralEvent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "One or more unspecified events active. See local unit display for
+ further details."
+ ::= { lgpFlexConditionsWellKnown 5588 }
+
+lgpCondId5593RemoteSensorAverageOverTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "[Remote Sensor Average Temperature] has exceeded [Remote Sensor
+ Over Temp Threshold]."
+ ::= { lgpFlexConditionsWellKnown 5593 }
+
+lgpCondId5594RemoteSensorAverageUnderTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "[Remote Sensor Average Temperature] has dropped below [Remote
+ Sensor Under Temp Threshold]."
+ ::= { lgpFlexConditionsWellKnown 5594 }
+
+lgpCondId5595RemoteSensorSystemAverageOverTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "[Remote Sensor System Average Temperature] has exceeded [Remote
+ Sensor Over Temp Threshold]."
+ ::= { lgpFlexConditionsWellKnown 5595 }
+
+lgpCondId5596RemoteSensorSystemAverageUnderTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "[Remote Sensor System Average Temperature] has dropped below
+ [Remote Sensor Under Temp Threshold]."
+ ::= { lgpFlexConditionsWellKnown 5596 }
+
+lgpCondId5597RemoteSensorOverTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "[Remote Sensor Temperature] has exceeded [Remote Sensor Over Temp
+ Threshold]."
+ ::= { lgpFlexConditionsWellKnown 5597 }
+
+lgpCondId5598RemoteSensorUnderTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "[Remote Sensor Temperature] has dropped below [Remote Sensor Under
+ Temp Threshold]."
+ ::= { lgpFlexConditionsWellKnown 5598 }
+
+lgpCondId5600AirEconomizerEmergencyOverride OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Indoor room temperature has exceeded its upper threshold and the
+ outdoor air damper has been opened for emergency cooling."
+ ::= { lgpFlexConditionsWellKnown 5600 }
+
+lgpCondId5601AirEconomizerReducedAirflow OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Air economizer filter is dirty and needs to be cleaned or replaced."
+ ::= { lgpFlexConditionsWellKnown 5601 }
+
+lgpCondId5604CompressorSuperheatOverThreshold OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Compressor discharge refrigerant superheat temperature has
+ exceeded an upper threshold."
+ ::= { lgpFlexConditionsWellKnown 5604 }
+
+lgpCondId5609ThermalRunawayCelltoAmbientTemperatureEvent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The delta temperature between a cell temperature and the ambient
+ temperature has exceeded the thermal runaway cell to ambient
+ temperature threshold."
+ ::= { lgpFlexConditionsWellKnown 5609 }
+
+lgpCondId5610ThermalRunawayCelltoCellTemperatureEvent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The delta temperature between two cells has exceeded the thermal
+ runaway cell to cell temperature threshold."
+ ::= { lgpFlexConditionsWellKnown 5610 }
+
+lgpCondId5611ThermalRunawayChargerCurrentLevelOneEvent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The Battery-String charger current has exceeded the thermal
+ runaway charger current level one threshold."
+ ::= { lgpFlexConditionsWellKnown 5611 }
+
+lgpCondId5612ThermalRunawayChargerCurrentLevelTwoEvent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The Battery-String charger current has exceeded the thermal
+ runaway charger current level two threshold."
+ ::= { lgpFlexConditionsWellKnown 5612 }
+
+lgpCondId5617TemperatureControlSensorIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The air sensor selected for cooling control is disconnected or the
+ signal is out of range."
+ ::= { lgpFlexConditionsWellKnown 5617 }
+
+lgpCondId5621EEVSuperheatBelowThreshold OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Electronic expansion valve refrigerant low superheat event."
+ ::= { lgpFlexConditionsWellKnown 5621 }
+
+lgpCondId5622EEVDischargeTempAboveThreshold OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Electronic expansion valve refrigerant high discharge temperature
+ event."
+ ::= { lgpFlexConditionsWellKnown 5622 }
+
+lgpCondId5623EEVBatteryIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Electronic expansion valve battery cannot be recharged and needs
+ to be replaced."
+ ::= { lgpFlexConditionsWellKnown 5623 }
+
+lgpCondId5624EEVPowerIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Electronic expansion valve lost power and is running on battery
+ backup."
+ ::= { lgpFlexConditionsWellKnown 5624 }
+
+lgpCondId5625EEVUnspecifiedGeneralEvent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "One or more unspecified electronic expansion valve events active.
+ See local unit display for further details."
+ ::= { lgpFlexConditionsWellKnown 5625 }
+
+lgpCondId5629StaticPressureSensorIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The static pressure sensor is disconnected or the signal is out of
+ range."
+ ::= { lgpFlexConditionsWellKnown 5629 }
+
+lgpCondId5630HighStaticPressure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "High static pressure event."
+ ::= { lgpFlexConditionsWellKnown 5630 }
+
+lgpCondId5631LowStaticPressure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Low static pressure event."
+ ::= { lgpFlexConditionsWellKnown 5631 }
+
+lgpCondId5636PumpUnspecifiedGeneralEvent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "One or more unspecified pump events active. See local unit display
+ for further details."
+ ::= { lgpFlexConditionsWellKnown 5636 }
+
+lgpCondId5637CondenserUnitUnspecifiedGeneralEvent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "One or more unspecified condenser unit events active. See local
+ unit display for further details."
+ ::= { lgpFlexConditionsWellKnown 5637 }
+
+lgpCondId5638CondenserCircuitUnspecifiedGeneralEvent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "One or more unspecified condenser circuit events active. See local
+ unit display for further details."
+ ::= { lgpFlexConditionsWellKnown 5638 }
+
+lgpCondId5642SFAReservedEvent1 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 5642 }
+
+lgpCondId5643SFAReservedEvent2 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 5643 }
+
+lgpCondId5644SFAReservedEvent3 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 5644 }
+
+lgpCondId5645SFAReservedEvent4 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 5645 }
+
+lgpCondId5646SFAReservedEvent5 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 5646 }
+
+lgpCondId5647SFAReservedEvent6 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 5647 }
+
+lgpCondId5648SFAReservedEvent7 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 5648 }
+
+lgpCondId5649SFAReservedEvent8 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 5649 }
+
+lgpCondId5650SFAReservedEvent9 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 5650 }
+
+lgpCondId5651SFAReservedEvent10 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 5651 }
+
+lgpCondId5652SFAReservedEvent11 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 5652 }
+
+lgpCondId5653SFAReservedEvent12 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 5653 }
+
+lgpCondId5654SFAReservedEvent13 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 5654 }
+
+lgpCondId5655SFAReservedEvent14 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 5655 }
+
+lgpCondId5656SFAReservedEvent15 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 5656 }
+
+lgpCondId5657SFAReservedEvent16 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 5657 }
+
+lgpCondId5658SFAReservedEvent17 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 5658 }
+
+lgpCondId5659SFAReservedEvent18 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 5659 }
+
+lgpCondId5660SFAReservedEvent19 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 5660 }
+
+lgpCondId5661SFAReservedEvent20 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 5661 }
+
+lgpCondId5662SFAReservedEvent21 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 5662 }
+
+lgpCondId5663SFAReservedEvent22 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 5663 }
+
+lgpCondId5664SFAReservedEvent23 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 5664 }
+
+lgpCondId5665SFAReservedEvent24 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 5665 }
+
+lgpCondId5666SFAReservedEvent25 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 5666 }
+
+lgpCondId5768OutletAirOvertemperatureLimit OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The difference between the outlet air temperature and inlet air
+ temperature exceeds a specified maximum temperature."
+ ::= { lgpFlexConditionsWellKnown 5768 }
+
+lgpCondId5769EMOShutdown OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "An Emergency Module Off command has been detected."
+ ::= { lgpFlexConditionsWellKnown 5769 }
+
+lgpCondId5770TopOutletFanFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Top outlet fan fault - one or more top outlet fans have failed."
+ ::= { lgpFlexConditionsWellKnown 5770 }
+
+lgpCondId5771MMSOverCapacity OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The multi-module system load is larger than the apparent power
+ limit setting."
+ ::= { lgpFlexConditionsWellKnown 5771 }
+
+lgpCondId5773CompressorCapacityNormal OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Compressor has returned to normal load capacity."
+ ::= { lgpFlexConditionsWellKnown 5773 }
+
+lgpCondId5774CompressorContactorIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Compressor contactor is not closing during compressor startup or
+ is not opening during compressor shutdown."
+ ::= { lgpFlexConditionsWellKnown 5774 }
+
+lgpCondId5775UnitShutdownUnspecifiedGeneralEvent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "One or more unspecified unit shutdown events active. See local
+ unit display for further details."
+ ::= { lgpFlexConditionsWellKnown 5775 }
+
+lgpCondId5776PDULowVoltageLN OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a module under voltage condition (LN)."
+ ::= { lgpFlexConditionsWellKnown 5776 }
+
+lgpCondId5777PDULowVoltageLL OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a module under voltage condition (LL)."
+ ::= { lgpFlexConditionsWellKnown 5777 }
+
+lgpCondId5778PDULowVoltageL1L2 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a line-to-line under voltage condition (L1
+ -L2)."
+ ::= { lgpFlexConditionsWellKnown 5778 }
+
+lgpCondId5779PDULowVoltageL2L3 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a line-to-line under voltage condition (L2
+ -L3)."
+ ::= { lgpFlexConditionsWellKnown 5779 }
+
+lgpCondId5780PDULowVoltageL3L1 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a line-to-line under voltage condition (L3
+ -L1)."
+ ::= { lgpFlexConditionsWellKnown 5780 }
+
+lgpCondId5781PDULowVoltageL1N OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a line to neutral under voltage condition
+ (L1-N)."
+ ::= { lgpFlexConditionsWellKnown 5781 }
+
+lgpCondId5782PDULowVoltageL2N OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a line to neutral under voltage condition
+ (L2-N)."
+ ::= { lgpFlexConditionsWellKnown 5782 }
+
+lgpCondId5783PDULowVoltageL3N OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a line to neutral under voltage condition
+ (L3-N)."
+ ::= { lgpFlexConditionsWellKnown 5783 }
+
+lgpCondId5784BranchLowVoltageLN OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a module under voltage condition (LN)."
+ ::= { lgpFlexConditionsWellKnown 5784 }
+
+lgpCondId5785BranchLowVoltageLL OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a module under voltage condition (LL)."
+ ::= { lgpFlexConditionsWellKnown 5785 }
+
+lgpCondId5786BranchLowVoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a module under voltage condition."
+ ::= { lgpFlexConditionsWellKnown 5786 }
+
+lgpCondId5788ContTieActive OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Continuous Power Tie Active."
+ ::= { lgpFlexConditionsWellKnown 5788 }
+
+lgpCondId5792UserkWhReset OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The user kWh accumulator was reset to zero by the operator."
+ ::= { lgpFlexConditionsWellKnown 5792 }
+
+lgpCondId5796PeakkWReset OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The Peak kW was reset."
+ ::= { lgpFlexConditionsWellKnown 5796 }
+
+lgpCondId5798BypassOverload OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Bypass overloaded, reduce load immediately."
+ ::= { lgpFlexConditionsWellKnown 5798 }
+
+lgpCondId5801LowBatteryShutdownImminent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "If active and guaranteed shutdown is enabled, a low battery
+ reserve condition exists that will shutdown the UPS."
+ ::= { lgpFlexConditionsWellKnown 5801 }
+
+lgpCondId5806OutputOverload OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "An overload exists on the output."
+ ::= { lgpFlexConditionsWellKnown 5806 }
+
+lgpCondId5807OutputOffPending OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Output off pending - shutdown imminent."
+ ::= { lgpFlexConditionsWellKnown 5807 }
+
+lgpCondId5808SystemShutdownOutputShort OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Shutdown was due to a short on the output."
+ ::= { lgpFlexConditionsWellKnown 5808 }
+
+lgpCondId5809SystemShutdownLowBattery OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Shutdown was due to a low battery condition."
+ ::= { lgpFlexConditionsWellKnown 5809 }
+
+lgpCondId5810SystemShutdownRemoteShutdown OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Shutdown was due to a remote communications shutdown command."
+ ::= { lgpFlexConditionsWellKnown 5810 }
+
+lgpCondId5811SystemShutdownHardwareFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Shutdown was due to an externally applied hardware control signal."
+ ::= { lgpFlexConditionsWellKnown 5811 }
+
+lgpCondId5817LossofRedundancy OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has an insufficient number of power modules to provide
+ redundancy."
+ ::= { lgpFlexConditionsWellKnown 5817 }
+
+lgpCondId5818PowerModuleFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "One or more conditions indicate a power module failure, service is
+ required."
+ ::= { lgpFlexConditionsWellKnown 5818 }
+
+lgpCondId5819PowerModuleWarning OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "One or more power modules is reporting a warning condition."
+ ::= { lgpFlexConditionsWellKnown 5819 }
+
+lgpCondId5838PowerModuleFanFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The Power Module has detected a fan fault."
+ ::= { lgpFlexConditionsWellKnown 5838 }
+
+lgpCondId5839PowerModuleOverTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The Power Module has detected an over temperature condition."
+ ::= { lgpFlexConditionsWellKnown 5839 }
+
+lgpCondId5840PowerModuleShutdownOverTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Power Module has shutdown due to over temperature."
+ ::= { lgpFlexConditionsWellKnown 5840 }
+
+lgpCondId5842ChargerModuleFanFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The Charger Module has detected a fan fault."
+ ::= { lgpFlexConditionsWellKnown 5842 }
+
+lgpCondId5847BatteryModuleTemperatureSensorFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A Battery Module temperature sensor fault has been detected."
+ ::= { lgpFlexConditionsWellKnown 5847 }
+
+lgpCondId5848BatteryModuleOverTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The Battery Module has detected an over temperature condition."
+ ::= { lgpFlexConditionsWellKnown 5848 }
+
+lgpCondId5849ReplaceBatteryModule OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The Battery Module needs to be replaced."
+ ::= { lgpFlexConditionsWellKnown 5849 }
+
+lgpCondId5850SystemShutdownTransformerOverTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "System shutdown due to transformer over temperature."
+ ::= { lgpFlexConditionsWellKnown 5850 }
+
+lgpCondId5851MaximumLoadAlarm OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Maximum load alarm indicating load setting has been exceeded."
+ ::= { lgpFlexConditionsWellKnown 5851 }
+
+lgpCondId5856BatteryModuleFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "One or more battery modules are reporting a fault condition."
+ ::= { lgpFlexConditionsWellKnown 5856 }
+
+lgpCondId5857BatteryModuleWarning OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "One or more battery modules are reporting a warning condition."
+ ::= { lgpFlexConditionsWellKnown 5857 }
+
+lgpCondId5862CheckAirFilter OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Please check air filter, it may need to be cleaned or replaced."
+ ::= { lgpFlexConditionsWellKnown 5862 }
+
+lgpCondId5863TransformerFanFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The transformer fan has failed."
+ ::= { lgpFlexConditionsWellKnown 5863 }
+
+lgpCondId5865NoLoadWarning OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Indicates the UPS has output voltage but the output current is
+ below a set threshold [No Load Warning Current Threshold] for a
+ set period of time [No Load Warning Delay]."
+ ::= { lgpFlexConditionsWellKnown 5865 }
+
+lgpCondId5871BatteryOverTemperatureLimit OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A battery temperature sensor is reporting a value above a
+ predetermined limit."
+ ::= { lgpFlexConditionsWellKnown 5871 }
+
+lgpCondId5873UnexpectedMainBatteryDisconnectClosure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The main battery disconnect has closed unexpectedly."
+ ::= { lgpFlexConditionsWellKnown 5873 }
+
+lgpCondId5874BatteryOverVoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that the battery voltage has exceeded a
+ predetermined limit."
+ ::= { lgpFlexConditionsWellKnown 5874 }
+
+lgpCondId5875BatteryFuseFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "One or more battery fuse faults has occurred."
+ ::= { lgpFlexConditionsWellKnown 5875 }
+
+lgpCondId5878MainBatteryDisconnectForcedToUnlock OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The main battery disconnect is forced to the unlocked state."
+ ::= { lgpFlexConditionsWellKnown 5878 }
+
+lgpCondId5879VdcBackfeed OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The voltage between battery and DC bus measurements is out of
+ tolerance."
+ ::= { lgpFlexConditionsWellKnown 5879 }
+
+lgpCondId5880RectifierConfigurationChangeRequest OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This event indicates that the battery is not configured and PFC is
+ not enabled."
+ ::= { lgpFlexConditionsWellKnown 5880 }
+
+lgpCondId5881RegenerationActive OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Regeneration operation is active."
+ ::= { lgpFlexConditionsWellKnown 5881 }
+
+lgpCondId5882RegenerationOperationTerminated OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Regeneration operation is not active."
+ ::= { lgpFlexConditionsWellKnown 5882 }
+
+lgpCondId5883RegenerationOperationFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Regeneration operation has been terminated due to bypass source
+ instability or unit misoperation."
+ ::= { lgpFlexConditionsWellKnown 5883 }
+
+lgpCondId5884ProgramInputContact01 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "When the signal from [Program Input Contact 01] is active the
+ function assigned to this contact is executed."
+ ::= { lgpFlexConditionsWellKnown 5884 }
+
+lgpCondId5885ProgramInputContact02 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "When the signal from [Program Input Contact 02] is active the
+ function assigned to this contact is executed."
+ ::= { lgpFlexConditionsWellKnown 5885 }
+
+lgpCondId5886ProgramInputContact03 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "When the signal from [Program Input Contact 03] is active the
+ function assigned to this contact is executed."
+ ::= { lgpFlexConditionsWellKnown 5886 }
+
+lgpCondId5887ProgramInputContact04 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "When the signal from [Program Input Contact 04] is active the
+ function assigned to this contact is executed."
+ ::= { lgpFlexConditionsWellKnown 5887 }
+
+lgpCondId5888ProgramInputContact05 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "When the signal from [Program Input Contact 05] is active the
+ function assigned to this contact is executed."
+ ::= { lgpFlexConditionsWellKnown 5888 }
+
+lgpCondId5889ProgramInputContact06 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "When the signal from [Program Input Contact 06] is active the
+ function assigned to this contact is executed."
+ ::= { lgpFlexConditionsWellKnown 5889 }
+
+lgpCondId5890ProgramInputContact07 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "When the signal from [Program Input Contact 07] is active the
+ function assigned to this contact is executed."
+ ::= { lgpFlexConditionsWellKnown 5890 }
+
+lgpCondId5891ProgramInputContact08 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "When the signal from [Program Input Contact 08] is active the
+ function assigned to this contact is executed."
+ ::= { lgpFlexConditionsWellKnown 5891 }
+
+lgpCondId5892ProgramInputContact09 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "When the signal from [Program Input Contact 09] is active the
+ function assigned to this contact is executed."
+ ::= { lgpFlexConditionsWellKnown 5892 }
+
+lgpCondId5893ProgramInputContact10 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "When the signal from [Program Input Contact 10] is active the
+ function assigned to this contact is executed."
+ ::= { lgpFlexConditionsWellKnown 5893 }
+
+lgpCondId5894ProgramInputContact11 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "When the signal from [Program Input Contact 11] is active the
+ function assigned to this contact is executed."
+ ::= { lgpFlexConditionsWellKnown 5894 }
+
+lgpCondId5895ProgramInputContact12 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "When the signal from [Program Input Contact 12] is active the
+ function assigned to this contact is executed."
+ ::= { lgpFlexConditionsWellKnown 5895 }
+
+lgpCondId5896GroundFaultDetected OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a ground fault on a Battery-String."
+ ::= { lgpFlexConditionsWellKnown 5896 }
+
+lgpCondId5902ReturnHumiditySensorIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The humidity sensor at the inlet of the unit is disconnected or
+ the signal is out of range."
+ ::= { lgpFlexConditionsWellKnown 5902 }
+
+lgpCondId5903CompressorLowDifferentialPressureLockout OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Compressor exceeded maximum startup attempts due to low
+ differential pressure. Compressor is shutdown and has been
+ disabled."
+ ::= { lgpFlexConditionsWellKnown 5903 }
+
+lgpCondId5906AirflowSensorIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Airflow sensor is disconnected or the signal is out of range."
+ ::= { lgpFlexConditionsWellKnown 5906 }
+
+lgpCondId5907ExtAirDamperPositionIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Air damper position does not match expected value, as indicated by
+ an external input signal."
+ ::= { lgpFlexConditionsWellKnown 5907 }
+
+lgpCondId5908ExtPowerSourceAFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Unit main power source A failure, as indicated by an external
+ input signal."
+ ::= { lgpFlexConditionsWellKnown 5908 }
+
+lgpCondId5909ExtPowerSourceBFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Unit main power source B failure, as indicated by an external
+ input signal."
+ ::= { lgpFlexConditionsWellKnown 5909 }
+
+lgpCondId5910StaticPressureSensorOutofRange OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Static pressure sensor signal is out of its configured range."
+ ::= { lgpFlexConditionsWellKnown 5910 }
+
+lgpCondId5911FluidTemperatureSensorIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The fluid temperature sensor is disconnected or the signal is out
+ of range."
+ ::= { lgpFlexConditionsWellKnown 5911 }
+
+lgpCondId5912FluidFlowSensorIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The fluid flow sensor is disconnected or the signal is out of
+ range."
+ ::= { lgpFlexConditionsWellKnown 5912 }
+
+lgpCondId5914OverDifferentialPressure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "An over differential pressure condition was detected."
+ ::= { lgpFlexConditionsWellKnown 5914 }
+
+lgpCondId5915UnderDifferentialPressure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "An under differential pressure condition was detected."
+ ::= { lgpFlexConditionsWellKnown 5915 }
+
+lgpCondId5924MixedModeLockout OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Mixed mode has been entered too many times over a rolling time
+ period and has been temporarily disabled. Mixed mode is defined
+ as the use of a compressor on one refrigeration circuit and the
+ use of a refrigerant pump on the other circuit."
+ ::= { lgpFlexConditionsWellKnown 5924 }
+
+lgpCondId5928UnbalancedLoadCondition OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a line-to-line unbalanced load condition."
+ ::= { lgpFlexConditionsWellKnown 5928 }
+
+lgpCondId5939BranchOverCurrentProtection OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The Branch Receptacle Module's over current protection is
+ triggered."
+ ::= { lgpFlexConditionsWellKnown 5939 }
+
+lgpCondId5948BranchLowVoltageLL OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a module under voltage condition (LL)."
+ ::= { lgpFlexConditionsWellKnown 5948 }
+
+lgpCondId5957BypassInputVoltageFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the bypass voltage is unqualified."
+ ::= { lgpFlexConditionsWellKnown 5957 }
+
+lgpCondId5958BatteryTemperatureOutofRange OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Battery temperature is outside of acceptable range."
+ ::= { lgpFlexConditionsWellKnown 5958 }
+
+lgpCondId5960InverterOverload OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Inverter in overload fault."
+ ::= { lgpFlexConditionsWellKnown 5960 }
+
+lgpCondId5966AuxAirTempDeviceCommunicationLost OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Communication with external auxiliary device providing an air
+ temperature value has been lost."
+ ::= { lgpFlexConditionsWellKnown 5966 }
+
+lgpCondId5967ModbusPowerMeterCommunicationLost OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Communication with Modbus power meter has been lost."
+ ::= { lgpFlexConditionsWellKnown 5967 }
+
+lgpCondId5968InverterDesaturation OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Inverter Desaturation."
+ ::= { lgpFlexConditionsWellKnown 5968 }
+
+lgpCondId5969GenericDICFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The control board reports a fault - Service required."
+ ::= { lgpFlexConditionsWellKnown 5969 }
+
+lgpCondId5970GroundFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "An AC phase to ground fault or three phase fault to ground exists
+ on the output of the UPS."
+ ::= { lgpFlexConditionsWellKnown 5970 }
+
+lgpCondId5973InputBreakerOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The main input breaker is open."
+ ::= { lgpFlexConditionsWellKnown 5973 }
+
+lgpCondId5974NeutralBreakerOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The neutral breaker is open."
+ ::= { lgpFlexConditionsWellKnown 5974 }
+
+lgpCondId5975OutputBreakerOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The output breaker is open."
+ ::= { lgpFlexConditionsWellKnown 5975 }
+
+lgpCondId5976MaintenanceBypassBreakerClosed OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The maintenance bypass breaker is closed."
+ ::= { lgpFlexConditionsWellKnown 5976 }
+
+lgpCondId5977BatteryBreakerOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The battery circuit is open."
+ ::= { lgpFlexConditionsWellKnown 5977 }
+
+lgpCondId5978RectifierIsolationBreakerRFBOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The rectifier isolation breaker (RFB) indicates that it is in the
+ open position."
+ ::= { lgpFlexConditionsWellKnown 5978 }
+
+lgpCondId5982BypassBreakerSBBOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The bypass circuit breaker (SBB) indicates that it is in the open
+ position."
+ ::= { lgpFlexConditionsWellKnown 5982 }
+
+lgpCondId5983BypassIsolationBreakerBIBOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The bypass isolation breaker (BIB) indicates that it is in the
+ open position."
+ ::= { lgpFlexConditionsWellKnown 5983 }
+
+lgpCondId5984BypassUndervoltageWarning OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The voltage on one or more bypass phases is less than a specified
+ percentage of the nominal voltage."
+ ::= { lgpFlexConditionsWellKnown 5984 }
+
+lgpCondId5985BypassStaticSwitchBPSSOn OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The Bypass Static Switch has been turned on."
+ ::= { lgpFlexConditionsWellKnown 5985 }
+
+lgpCondId5998BattOvtempWarning OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A battery temperature sensor is reporting a value above the
+ setpoint."
+ ::= { lgpFlexConditionsWellKnown 5998 }
+
+lgpCondId6009InverterOutputBreakerOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The inverter output breaker indicates that it is in the open
+ position."
+ ::= { lgpFlexConditionsWellKnown 6009 }
+
+lgpCondId6011EquipmentOverTempWarning OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Equipment over temperature warning is a summary event based on the
+ detection of at least one measured temperature exceeding a
+ threshold."
+ ::= { lgpFlexConditionsWellKnown 6011 }
+
+lgpCondId6012EquipmentOvertemperatureLimit OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The equipment air temperature has exceeded its maximum set point."
+ ::= { lgpFlexConditionsWellKnown 6012 }
+
+lgpCondId6045RectifierInputBreakerOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The rectifier isolation breaker indicates that it is in the open
+ position."
+ ::= { lgpFlexConditionsWellKnown 6045 }
+
+lgpCondId6046LoadonUPS OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The output is being supplied power from the inverter."
+ ::= { lgpFlexConditionsWellKnown 6046 }
+
+lgpCondId6047Core2CoreFuseFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Core-2-core fuse failure."
+ ::= { lgpFlexConditionsWellKnown 6047 }
+
+lgpCondId6052SystemOutputBreakerOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system output breaker is open."
+ ::= { lgpFlexConditionsWellKnown 6052 }
+
+lgpCondId6059InverterRelayFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The inverter relay has malfunctioned."
+ ::= { lgpFlexConditionsWellKnown 6059 }
+
+lgpCondId6060TransfertoBypassSystemOverload OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The UPS System has transferred to bypass because the active power
+ modules cannot support the critical load."
+ ::= { lgpFlexConditionsWellKnown 6060 }
+
+lgpCondId6061InputSourceBackfeed OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The battery is backfeeding the input source."
+ ::= { lgpFlexConditionsWellKnown 6061 }
+
+lgpCondId6062LossofSynchronization OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The inverter and bypass are no longer synchronized. ."
+ ::= { lgpFlexConditionsWellKnown 6062 }
+
+lgpCondId6063BatteryConverterCurrentLimit OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The battery converter has reached is maximum current limit. ."
+ ::= { lgpFlexConditionsWellKnown 6063 }
+
+lgpCondId6064LBSCableFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Load Bus Sync communications is abnormal. A problem with the LBS
+ cable may exist."
+ ::= { lgpFlexConditionsWellKnown 6064 }
+
+lgpCondId6065BatteryChargeEqualizationTimeout OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The battery equalizing is time out."
+ ::= { lgpFlexConditionsWellKnown 6065 }
+
+lgpCondId6066ParallelCableFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The UPS parallel system communications is abnormal. A problem with
+ the parallel cable may exist."
+ ::= { lgpFlexConditionsWellKnown 6066 }
+
+lgpCondId6067BatteryFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A short circuit exists in the battery system."
+ ::= { lgpFlexConditionsWellKnown 6067 }
+
+lgpCondId6068BatteryRoomAlarm OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The ambient temperature of the battery room is abnormal."
+ ::= { lgpFlexConditionsWellKnown 6068 }
+
+lgpCondId6080UPSCCommunicationFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The UPSC has failed to communicate in a designated time period."
+ ::= { lgpFlexConditionsWellKnown 6080 }
+
+lgpCondId6092Compressor1BThermalOverload OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Fixed compressor 1B is shut down due to thermal overload."
+ ::= { lgpFlexConditionsWellKnown 6092 }
+
+lgpCondId6093Compressor2BThermalOverload OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Fixed compressor 2B is shut down due to thermal overload."
+ ::= { lgpFlexConditionsWellKnown 6093 }
+
+lgpCondId6094Compressor1BHoursExceeded OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Fixed compressor 1B run hours have exceeded the threshold."
+ ::= { lgpFlexConditionsWellKnown 6094 }
+
+lgpCondId6095Compressor2BHoursExceeded OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Fixed compressor 2B run hours have exceeded the threshold."
+ ::= { lgpFlexConditionsWellKnown 6095 }
+
+lgpCondId6100CondenserRemoteShutdown OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Condenser is shut down by a remote signal."
+ ::= { lgpFlexConditionsWellKnown 6100 }
+
+lgpCondId6105ExternalCondenserTVSSIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The condenser Transient Voltage Surge Suppressor or Surge
+ Protection Device has failed, as indicated by an external input
+ signal."
+ ::= { lgpFlexConditionsWellKnown 6105 }
+
+lgpCondId6106ExternalCondenserVFDIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The condenser fan Variable Frequency Drive is offline, as
+ indicated by an external input signal."
+ ::= { lgpFlexConditionsWellKnown 6106 }
+
+lgpCondId6107ExternalCondenserIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Condenser is not operating within its operational parameters, as
+ indicated by an external input signal."
+ ::= { lgpFlexConditionsWellKnown 6107 }
+
+lgpCondId6119Slotsnotavailable OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The number of sensors exceeds the number of allocated slots and
+ cannot be displayed."
+ ::= { lgpFlexConditionsWellKnown 6119 }
+
+lgpCondId6180BatteryUnderVoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Battery voltage is too low."
+ ::= { lgpFlexConditionsWellKnown 6180 }
+
+lgpCondId6182ReplaceBattery OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The battery is due for replacement."
+ ::= { lgpFlexConditionsWellKnown 6182 }
+
+lgpCondId6186InputFrequencyDeviation OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The input frequency is outside of the normal range."
+ ::= { lgpFlexConditionsWellKnown 6186 }
+
+lgpCondId6187ShutdownPending OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Shutdown is pending."
+ ::= { lgpFlexConditionsWellKnown 6187 }
+
+lgpCondId6194SystemRebootCommandIssued OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reboot command issued to the system."
+ ::= { lgpFlexConditionsWellKnown 6194 }
+
+lgpCondId6203SensorAdded OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Sensor Added."
+ ::= { lgpFlexConditionsWellKnown 6203 }
+
+lgpCondId6204SensorRemoved OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Sensor Removed."
+ ::= { lgpFlexConditionsWellKnown 6204 }
+
+lgpCondId6205WaterLeakDetected OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Water leak detected."
+ ::= { lgpFlexConditionsWellKnown 6205 }
+
+lgpCondId6210FirmwareUpdateInProgress OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Firmware update has started and is in progress."
+ ::= { lgpFlexConditionsWellKnown 6210 }
+
+lgpCondId6211FirmwareUpdateCompletedSuccessfully OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Firmware update has completed successfully."
+ ::= { lgpFlexConditionsWellKnown 6211 }
+
+lgpCondId6212FirmwareUpdateCompletedUnsuccessfully OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Firmware update has completed, but was not successful."
+ ::= { lgpFlexConditionsWellKnown 6212 }
+
+lgpCondId6216PrechargeCircuitFailed OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "DC Bus precharge/discharge didn't reach specified level within a
+ specified time."
+ ::= { lgpFlexConditionsWellKnown 6216 }
+
+lgpCondId6217MemoryCardRemoved OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The memory card on the control board has been removed."
+ ::= { lgpFlexConditionsWellKnown 6217 }
+
+lgpCondId6218AutoCalibrationActive OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system is automatically calibrating ADC channels."
+ ::= { lgpFlexConditionsWellKnown 6218 }
+
+lgpCondId6219AutoCalibrationFailed OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "ADC channel calibration has failed."
+ ::= { lgpFlexConditionsWellKnown 6219 }
+
+lgpCondId6220ModuleOutputBreakerOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The module output breaker is open."
+ ::= { lgpFlexConditionsWellKnown 6220 }
+
+lgpCondId6221NeutralVoltageFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Voltage observed on neutral line."
+ ::= { lgpFlexConditionsWellKnown 6221 }
+
+lgpCondId6222BranchLoadLoss OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Loss of load on branch detected. Branch circuit breaker might be
+ open."
+ ::= { lgpFlexConditionsWellKnown 6222 }
+
+lgpCondId6225RemoteSensorLowHumidity OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Remote sensor humidity has dropped below a lower threshold. The
+ event is deactivated when the humidity rises above the threshold."
+ ::= { lgpFlexConditionsWellKnown 6225 }
+
+lgpCondId6226RemoteSensorHighHumidity OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Remote sensor humidity has exceeded an upper threshold. The event
+ is deactivated when the humidity drops below the threshold."
+ ::= { lgpFlexConditionsWellKnown 6226 }
+
+lgpCondId6227RemoteSensorAverageLowHumidity OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The average humidity of multiple remote sensors on the cooling
+ unit has dropped below a lower threshold. The event is
+ deactivated when the humidity rises above the threshold."
+ ::= { lgpFlexConditionsWellKnown 6227 }
+
+lgpCondId6228RemoteSensorAverageHighHumidity OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The average humidity of multiple remote sensors on the cooling
+ unit has exceeded an upper threshold. The event is deactivated
+ when the humidity drops below the threshold."
+ ::= { lgpFlexConditionsWellKnown 6228 }
+
+lgpCondId6229RemoteSensorSystemAverageLowHumidity OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The average humidity of multiple remote sensors on interconnected
+ cooling units in a single system has dropped below a lower
+ threshold. The event is deactivated when the humidity rises
+ above the threshold."
+ ::= { lgpFlexConditionsWellKnown 6229 }
+
+lgpCondId6230RemoteSensorSystemAverageHighHumidity OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The average humidity of multiple remote sensors on interconnected
+ cooling units in a single system has exceeded an upper threshold.
+ The event is deactivated when the humidity drops below the
+ threshold."
+ ::= { lgpFlexConditionsWellKnown 6230 }
+
+lgpCondId6231LowCompressorSuperheat OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Compressor suction superheat has dropped below a lower threshold."
+ ::= { lgpFlexConditionsWellKnown 6231 }
+
+lgpCondId6232SECUnspecifiedGeneralEvent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "One or more unspecified events active for the Superheat and
+ Envelope Controller. See local unit display for further details."
+ ::= { lgpFlexConditionsWellKnown 6232 }
+
+lgpCondId6233SECCommunicationLost OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Communication with the Superheat and Envelope Controller has been
+ lost. The event is deactivated when communication is re
+ -established."
+ ::= { lgpFlexConditionsWellKnown 6233 }
+
+lgpCondId6236PowerSourceAIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "No power is detected at power source input 'A'."
+ ::= { lgpFlexConditionsWellKnown 6236 }
+
+lgpCondId6237PowerSourceBIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "No power is detected at power source input 'B'."
+ ::= { lgpFlexConditionsWellKnown 6237 }
+
+lgpCondId6239FluidValveHoursExceeded OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Operating hours for the fluid valve have exceeded the threshold."
+ ::= { lgpFlexConditionsWellKnown 6239 }
+
+lgpCondId6253BoosterFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Booster failure - boost is off."
+ ::= { lgpFlexConditionsWellKnown 6253 }
+
+lgpCondId6254ChargerFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Charger Failure - Charger is off."
+ ::= { lgpFlexConditionsWellKnown 6254 }
+
+lgpCondId6274UnitTopReturnAirSensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Return air sensor at the top of the unit is disconnected or the
+ signal is out of range."
+ ::= { lgpFlexConditionsWellKnown 6274 }
+
+lgpCondId6275UnitMiddleReturnAirSensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Return air sensor in the middle of the unit is disconnected or the
+ signal is out of range."
+ ::= { lgpFlexConditionsWellKnown 6275 }
+
+lgpCondId6276UnitBottomReturnAirSensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Return air sensor at the bottom of the unit is disconnected or the
+ signal is out of range."
+ ::= { lgpFlexConditionsWellKnown 6276 }
+
+lgpCondId6277UnitTopSupplyAirSensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Supply air sensor at the top of the unit is disconnected or the
+ signal is out of range."
+ ::= { lgpFlexConditionsWellKnown 6277 }
+
+lgpCondId6278UnitMiddleFirstSupplyAirSensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "First supply air sensor in the middle of the unit is disconnected
+ or the signal is out of range."
+ ::= { lgpFlexConditionsWellKnown 6278 }
+
+lgpCondId6279UnitBottomSupplyAirSensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Supply air sensor at the bottom of the unit is disconnected or the
+ signal is out of range."
+ ::= { lgpFlexConditionsWellKnown 6279 }
+
+lgpCondId6284UnitMiddleSecondSupplyAirSensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Second supply air sensor in the middle of the unit is disconnected
+ or the signal is out of range."
+ ::= { lgpFlexConditionsWellKnown 6284 }
+
+lgpCondId6293ChilledWaterControlActive OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Chilled water inlet temperature control function is enabled due to
+ 'bad' water."
+ ::= { lgpFlexConditionsWellKnown 6293 }
+
+lgpCondId6294ChilledWaterFlowTransducerFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Chilled water flow transducer is disconnected or the signal is out
+ of range."
+ ::= { lgpFlexConditionsWellKnown 6294 }
+
+lgpCondId6295ChilledWaterInletTemperatureSensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Chilled water inlet temperature sensor is disconnected or the
+ signal is out of range. The sensor is mandatory for the chilled
+ water flow function."
+ ::= { lgpFlexConditionsWellKnown 6295 }
+
+lgpCondId6296ChilledWaterHighInletTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Chilled water inlet temperature has exceeded an upper threshold."
+ ::= { lgpFlexConditionsWellKnown 6296 }
+
+lgpCondId6297Modbus010VModuleCommunicationFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Modbus 0-10V module for managing the second Chilled Water circuit
+ valve is disconnected or the signal is out of range."
+ ::= { lgpFlexConditionsWellKnown 6297 }
+
+lgpCondId6299RackDoorsOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Rack doors opened due to supply air temperature exceeding the
+ [Rack Door Open High Supply Air Temperature Threshold]."
+ ::= { lgpFlexConditionsWellKnown 6299 }
+
+lgpCondId6303TeamStaticPressureSensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The team static pressure sensor is disconnected or the signal is
+ out of range."
+ ::= { lgpFlexConditionsWellKnown 6303 }
+
+lgpCondId6304HeatingLockout OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Heating is shut down and disabled."
+ ::= { lgpFlexConditionsWellKnown 6304 }
+
+lgpCondId6305FreeCoolingStoppedHighRoomTemp OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Free cooling is temporarily disabled due to room temperature
+ exceeding a preset delta above the the set point."
+ ::= { lgpFlexConditionsWellKnown 6305 }
+
+lgpCondId6306ColdAisleTemperatureHumidityTeamSensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Cold aisle team sensor measuring air temperature and humidity is
+ disconnected or the signal is out of range."
+ ::= { lgpFlexConditionsWellKnown 6306 }
+
+lgpCondId6309ColdAisleAirSensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Cold aisle sensor measuring air temperature and humidity is
+ disconnected or the signal is out of range."
+ ::= { lgpFlexConditionsWellKnown 6309 }
+
+lgpCondId6310ChilledWaterInletTemperatureControlActive OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Chilled water inlet temperature control is active."
+ ::= { lgpFlexConditionsWellKnown 6310 }
+
+lgpCondId6313ChilledWaterInletTemperatureSensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Chilled water inlet temperature sensor is disconnected or the
+ signal is out of range."
+ ::= { lgpFlexConditionsWellKnown 6313 }
+
+lgpCondId6314ChilledWaterOutletTemperatureSensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Chilled water outlet temperature sensor is disconnected or the
+ signal is out of range."
+ ::= { lgpFlexConditionsWellKnown 6314 }
+
+lgpCondId6315ChilledWaterFlowMeterSensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Chilled water flow meter sensor is disconnected or the signal is
+ out of range."
+ ::= { lgpFlexConditionsWellKnown 6315 }
+
+lgpCondId6333Bypassoutofsync OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Bypass and Inverter inputs are not in sync."
+ ::= { lgpFlexConditionsWellKnown 6333 }
+
+lgpCondId6348SystemOutputoffasrequested OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The UPS has shutdown as requested, i.e., the output is off."
+ ::= { lgpFlexConditionsWellKnown 6348 }
+
+lgpCondId6349SystemOffasrequested OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The entire UPS has shutdown as commanded."
+ ::= { lgpFlexConditionsWellKnown 6349 }
+
+lgpCondId6350GeneralFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A general fault in the UPS has been detected."
+ ::= { lgpFlexConditionsWellKnown 6350 }
+
+lgpCondId6351UPSAwaitingPower OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The UPS output is off and the UPS is awaiting the return of input
+ power."
+ ::= { lgpFlexConditionsWellKnown 6351 }
+
+lgpCondId6352AutonomyCalibration OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Calibration test occurred."
+ ::= { lgpFlexConditionsWellKnown 6352 }
+
+lgpCondId6353GeneralWarning OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A warning in the UPS has been detected."
+ ::= { lgpFlexConditionsWellKnown 6353 }
+
+lgpCondId6354BatteryCharging OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The UPS battery is charging (battery charge percentage lower than
+ 98)."
+ ::= { lgpFlexConditionsWellKnown 6354 }
+
+lgpCondId6355BackfeedRelayFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Bypass SCR is wrongly on or commutated."
+ ::= { lgpFlexConditionsWellKnown 6355 }
+
+lgpCondId6356BatteryCircuitOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Battery Circuit Open."
+ ::= { lgpFlexConditionsWellKnown 6356 }
+
+lgpCondId6357SystemRestartPending OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A request for UPS restart has been received."
+ ::= { lgpFlexConditionsWellKnown 6357 }
+
+lgpCondId6358PipeTemperatureSensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Air temperature sensor located in the pipe is not sending a valid
+ value."
+ ::= { lgpFlexConditionsWellKnown 6358 }
+
+lgpCondId6362SFAReservedEvent26 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 6362 }
+
+lgpCondId6363SFAReservedEvent27 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 6363 }
+
+lgpCondId6364SFAReservedEvent28 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 6364 }
+
+lgpCondId6365SFAReservedEvent29 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 6365 }
+
+lgpCondId6366SFAReservedEvent30 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 6366 }
+
+lgpCondId6367SFAReservedEvent31 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 6367 }
+
+lgpCondId6368SFAReservedEvent32 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 6368 }
+
+lgpCondId6369SFAReservedEvent33 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 6369 }
+
+lgpCondId6370SFAReservedEvent34 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 6370 }
+
+lgpCondId6371SFAReservedEvent35 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 6371 }
+
+lgpCondId6372SFAReservedEvent36 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 6372 }
+
+lgpCondId6373SFAReservedEvent37 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 6373 }
+
+lgpCondId6374SFAReservedEvent38 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 6374 }
+
+lgpCondId6375SFAReservedEvent39 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 6375 }
+
+lgpCondId6376SFAReservedEvent40 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 6376 }
+
+lgpCondId6377SFAReservedEvent41 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 6377 }
+
+lgpCondId6378SFAReservedEvent42 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 6378 }
+
+lgpCondId6379SFAReservedEvent43 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 6379 }
+
+lgpCondId6380SFAReservedEvent44 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 6380 }
+
+lgpCondId6381SFAReservedEvent45 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 6381 }
+
+lgpCondId6382SFAReservedEvent46 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 6382 }
+
+lgpCondId6383SFAReservedEvent47 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 6383 }
+
+lgpCondId6384SFAReservedEvent48 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 6384 }
+
+lgpCondId6385SFAReservedEvent49 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 6385 }
+
+lgpCondId6386SFAReservedEvent50 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Reserved event for SFA use."
+ ::= { lgpFlexConditionsWellKnown 6386 }
+
+lgpCondId6438PowerModuleInputCurrentAbnormal OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Input current of the power module is abnormal."
+ ::= { lgpFlexConditionsWellKnown 6438 }
+
+lgpCondId6439PowerModuleBalancerofDCBusFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Balancer of DC Bus in the power module has failed."
+ ::= { lgpFlexConditionsWellKnown 6439 }
+
+lgpCondId6440PowerModuleFuseFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A summary event indicating one or more fuse failures in the power
+ module."
+ ::= { lgpFlexConditionsWellKnown 6440 }
+
+lgpCondId6441PowerModulePowerSupplyFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Power module power supply failure."
+ ::= { lgpFlexConditionsWellKnown 6441 }
+
+lgpCondId6450PDUPoweredOn OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The PDU was powered on."
+ ::= { lgpFlexConditionsWellKnown 6450 }
+
+lgpCondId6453InputWiringFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The neutral/ground conductors on the input wiring are not properly
+ bonded, or the line/neutral conductors have been swapped."
+ ::= { lgpFlexConditionsWellKnown 6453 }
+
+lgpCondId6454DCtoDCConverterFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A failure has occurred in the battery discharge circuit."
+ ::= { lgpFlexConditionsWellKnown 6454 }
+
+lgpCondId6455LeakSensorCableFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A fault is detected in the 'Leak Sensor' cable."
+ ::= { lgpFlexConditionsWellKnown 6455 }
+
+lgpCondId6518StandbyUnitActivatedDuetoChillerFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "External chiller unit has failed for this unit, so the standby
+ cooling unit has been activated."
+ ::= { lgpFlexConditionsWellKnown 6518 }
+
+lgpCondId6522PDUResidualOverCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a PDU residual over current condition."
+ ::= { lgpFlexConditionsWellKnown 6522 }
+
+lgpCondId6527PDUOverCurrentProtection OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The PDU over current protection is triggered."
+ ::= { lgpFlexConditionsWellKnown 6527 }
+
+lgpCondId6528PowerModuleLeverUnlocked OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The power module is inactive because the lever is in the unlocked
+ position."
+ ::= { lgpFlexConditionsWellKnown 6528 }
+
+lgpCondId6529HardwareMismatch OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The assigned system model settings do not match the actual
+ installed hardware. The module count is wrong, or a module of the
+ wrong type is installed."
+ ::= { lgpFlexConditionsWellKnown 6529 }
+
+lgpCondId6530SupplyNTCAirSensorIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The supply NTC air sensor is disconnected or the signal is out of
+ range."
+ ::= { lgpFlexConditionsWellKnown 6530 }
+
+lgpCondId6531ExternalAirSensorCIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The external air sensor C is disconnected or the signal is out of
+ range."
+ ::= { lgpFlexConditionsWellKnown 6531 }
+
+lgpCondId6532ExternalAirSensorDIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The external air sensor D is disconnected or the signal is out of
+ range."
+ ::= { lgpFlexConditionsWellKnown 6532 }
+
+lgpCondId6533ExternalAirSensorEIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The external air sensor E is disconnected or the signal is out of
+ range."
+ ::= { lgpFlexConditionsWellKnown 6533 }
+
+lgpCondId6534PumpThermalOverload OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Pump is shut down due to thermal overload."
+ ::= { lgpFlexConditionsWellKnown 6534 }
+
+lgpCondId6535XDModuleCommunicationLost OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Communication with XD Module has been lost."
+ ::= { lgpFlexConditionsWellKnown 6535 }
+
+lgpCondId6536MMSCapacityExceeded OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The critical load is larger than the redundant rating of a 1+N
+ redundant multi-module system."
+ ::= { lgpFlexConditionsWellKnown 6536 }
+
+lgpCondId6538TSAControlInputIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The analog input used to set the air temperature set point for
+ cooling control is disconnected or the signal is out of range."
+ ::= { lgpFlexConditionsWellKnown 6538 }
+
+lgpCondId6539ChilledWaterValveHoursExceeded OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "[Chilled Water Valve Hours] has exceeded [Chilled Water Valve
+ Operating Hours Threshold]."
+ ::= { lgpFlexConditionsWellKnown 6539 }
+
+lgpCondId6540FSAControlInputIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The analog input used to set the air temperature set point for fan
+ speed control is disconnected or the signal is out of range."
+ ::= { lgpFlexConditionsWellKnown 6540 }
+
+lgpCondId6541AutoTuneLicenseExpiring OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "License for the AutoTune feature has not been refreshed in 30 days
+ and will be expiring soon."
+ ::= { lgpFlexConditionsWellKnown 6541 }
+
+lgpCondId6542AutoTuneLicenseExpired OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "License for the AutoTune feature has expired."
+ ::= { lgpFlexConditionsWellKnown 6542 }
+
+lgpCondId6543UnitInStandbyDueToCoolingLoss OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Unit forced into standby because it is unable to provide any
+ cooling."
+ ::= { lgpFlexConditionsWellKnown 6543 }
+
+lgpCondId6544ControlUnitsRemoteShutdownMismatch OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The remote shutdown status of the primary control unit does not
+ match the remote shutdown status of the secondary control unit."
+ ::= { lgpFlexConditionsWellKnown 6544 }
+
+lgpCondId6545SecondaryControlUnitCommunicationLost OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The primary control unit has lost Ethernet communications with the
+ secondary control unit."
+ ::= { lgpFlexConditionsWellKnown 6545 }
+
+lgpCondId6546ControlUnitsUnitCodeMismatch OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Unit codes for the primary and secondary control units do not
+ match."
+ ::= { lgpFlexConditionsWellKnown 6546 }
+
+lgpCondId6547SSAControlInputIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The analog input used to set the static pressure set point for fan
+ speed control is disconnected or the signal is out of range."
+ ::= { lgpFlexConditionsWellKnown 6547 }
+
+lgpCondId6574SubfeedPhaseUndercurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Subfeed breaker phase current has dropped below the threshold."
+ ::= { lgpFlexConditionsWellKnown 6574 }
+
+lgpCondId6587TransferCountCleared OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A system event indicating the transfer count has been cleared."
+ ::= { lgpFlexConditionsWellKnown 6587 }
+
+lgpCondId6588EnergyCounterCleared OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A system event indicating the energy counter (e.g. KWH) has been
+ cleared."
+ ::= { lgpFlexConditionsWellKnown 6588 }
+
+lgpCondId6589HistoryLogsFull OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The history logs are full."
+ ::= { lgpFlexConditionsWellKnown 6589 }
+
+lgpCondId6590HistoryLogsCleared OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "History logs have been cleared."
+ ::= { lgpFlexConditionsWellKnown 6590 }
+
+lgpCondId6591EventLogCleared OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "All past alarms and faults have been cleared."
+ ::= { lgpFlexConditionsWellKnown 6591 }
+
+lgpCondId6592SystemDateChanged OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system date has been updated."
+ ::= { lgpFlexConditionsWellKnown 6592 }
+
+lgpCondId6593SystemTimeChanged OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system time has been updated."
+ ::= { lgpFlexConditionsWellKnown 6593 }
+
+lgpCondId6594AccessPasswordChanged OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The access password has been changed."
+ ::= { lgpFlexConditionsWellKnown 6594 }
+
+lgpCondId6595ConfigModified OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A setpoint has been updated."
+ ::= { lgpFlexConditionsWellKnown 6595 }
+
+lgpCondId6612SCRShort OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The SCR is in a short condition."
+ ::= { lgpFlexConditionsWellKnown 6612 }
+
+lgpCondId6613SCROpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The SCR is in an open condition."
+ ::= { lgpFlexConditionsWellKnown 6613 }
+
+lgpCondId6614ACPowerSupplyFail OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A failure of the AC Power Supply has been detected."
+ ::= { lgpFlexConditionsWellKnown 6614 }
+
+lgpCondId6615DCPowerSupplyFail OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A failure of the DC Power Supply has been detected."
+ ::= { lgpFlexConditionsWellKnown 6615 }
+
+lgpCondId6616VoltageSensorFail OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A voltage sensor failure has been detected."
+ ::= { lgpFlexConditionsWellKnown 6616 }
+
+lgpCondId6617SCRSensorFail OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The SCR sensor module failed."
+ ::= { lgpFlexConditionsWellKnown 6617 }
+
+lgpCondId6618CurrentSensorFail OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The current sensor module failed."
+ ::= { lgpFlexConditionsWellKnown 6618 }
+
+lgpCondId6619GateDriveFail OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The Gate Drive module failed."
+ ::= { lgpFlexConditionsWellKnown 6619 }
+
+lgpCondId6620SurgeFail OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The surge module failed for the input source."
+ ::= { lgpFlexConditionsWellKnown 6620 }
+
+lgpCondId6621FastUnderVoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Fast under voltage detected."
+ ::= { lgpFlexConditionsWellKnown 6621 }
+
+lgpCondId6622SlowUnderVoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Slow under voltage detected."
+ ::= { lgpFlexConditionsWellKnown 6622 }
+
+lgpCondId6623OverVoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Over voltage detected."
+ ::= { lgpFlexConditionsWellKnown 6623 }
+
+lgpCondId6624OverUnderFrequencyFail OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "An over or under frequency condition has been detected."
+ ::= { lgpFlexConditionsWellKnown 6624 }
+
+lgpCondId6625GeneralSourceFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A non-specific failure has been detected in the source."
+ ::= { lgpFlexConditionsWellKnown 6625 }
+
+lgpCondId6626OverCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "An over current has been detected."
+ ::= { lgpFlexConditionsWellKnown 6626 }
+
+lgpCondId6627PeakCurrentOffLimit OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The peak current has exceeded the setpoint defined by I-PK Xfer
+ Lockout."
+ ::= { lgpFlexConditionsWellKnown 6627 }
+
+lgpCondId6628SyncFail OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A phase rotation/out of synchronization failure has been detected."
+ ::= { lgpFlexConditionsWellKnown 6628 }
+
+lgpCondId6629InputOverVoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Input over voltage."
+ ::= { lgpFlexConditionsWellKnown 6629 }
+
+lgpCondId6630InputUnderVoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Input under voltage."
+ ::= { lgpFlexConditionsWellKnown 6630 }
+
+lgpCondId6631InputOverUnderFrequency OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Input over/under frequency."
+ ::= { lgpFlexConditionsWellKnown 6631 }
+
+lgpCondId6635VoltageSenseFail OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Output voltage sense failure."
+ ::= { lgpFlexConditionsWellKnown 6635 }
+
+lgpCondId6636LoadonAlternateSource OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The load is on the alternate source."
+ ::= { lgpFlexConditionsWellKnown 6636 }
+
+lgpCondId6637UnderVoltageFail OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Output under voltage failure."
+ ::= { lgpFlexConditionsWellKnown 6637 }
+
+lgpCondId6638OutputOverCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Output is over current."
+ ::= { lgpFlexConditionsWellKnown 6638 }
+
+lgpCondId6639GroundOverCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Ground is over current."
+ ::= { lgpFlexConditionsWellKnown 6639 }
+
+lgpCondId6640NeutralOverCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Neutral is over current."
+ ::= { lgpFlexConditionsWellKnown 6640 }
+
+lgpCondId6641LoadVoltageTHD OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Load voltage THD has exceeded the set limit."
+ ::= { lgpFlexConditionsWellKnown 6641 }
+
+lgpCondId6662ControlLogicFail OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A control logic module has failed."
+ ::= { lgpFlexConditionsWellKnown 6662 }
+
+lgpCondId6663PowerSupplyLogicFail OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A power supply module has failed."
+ ::= { lgpFlexConditionsWellKnown 6663 }
+
+lgpCondId6664ExternalCommsFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "External communications failure."
+ ::= { lgpFlexConditionsWellKnown 6664 }
+
+lgpCondId6665HeatSinkOverTemp OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system heat sink temperature has exceeded design limits."
+ ::= { lgpFlexConditionsWellKnown 6665 }
+
+lgpCondId6666AutomaticTransferInhibited OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Automatic transfer is inhibited."
+ ::= { lgpFlexConditionsWellKnown 6666 }
+
+lgpCondId6667InputSourceTransferInhibited OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Input source transfer is inhibited."
+ ::= { lgpFlexConditionsWellKnown 6667 }
+
+lgpCondId6676CB1ShuntTrip OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "CB1 Shunt Trip event."
+ ::= { lgpFlexConditionsWellKnown 6676 }
+
+lgpCondId6677CB2ShuntTrip OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "CB2 Shunt Trip event."
+ ::= { lgpFlexConditionsWellKnown 6677 }
+
+lgpCondId6678CB6NeutralOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "CB6 neutral open event."
+ ::= { lgpFlexConditionsWellKnown 6678 }
+
+lgpCondId6679ContactorNeutralFail OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Contactor Neutral Fail event."
+ ::= { lgpFlexConditionsWellKnown 6679 }
+
+lgpCondId6680CB1BreakerOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "CB1 Breaker open event. Normal state is breaker closed. Latched
+ state is breaker open."
+ ::= { lgpFlexConditionsWellKnown 6680 }
+
+lgpCondId6681CB2BreakerOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "CB2 Breaker open event. Normal state is breaker closed. Latched
+ state is breaker open."
+ ::= { lgpFlexConditionsWellKnown 6681 }
+
+lgpCondId6682CB4BreakerClosed OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "CB4 breaker closed event. Normal state is breaker open. Latched
+ state is breaker closed."
+ ::= { lgpFlexConditionsWellKnown 6682 }
+
+lgpCondId6683CB5BreakerClosed OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "CB5 breaker closed event. Normal state is breaker open. Latched
+ state is breaker closed."
+ ::= { lgpFlexConditionsWellKnown 6683 }
+
+lgpCondId6684CB3BreakerOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "CB3 breaker open event. Normal state is breaker closed. Latched
+ state is breaker open."
+ ::= { lgpFlexConditionsWellKnown 6684 }
+
+lgpCondId6685CB3ABreakerOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "CB3A breaker open event. Normal state is breaker closed. Latched
+ state is breaker open."
+ ::= { lgpFlexConditionsWellKnown 6685 }
+
+lgpCondId6686CB6BreakerOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "CB6 breaker open event. Normal state is breaker closed. Latched
+ state is breaker open."
+ ::= { lgpFlexConditionsWellKnown 6686 }
+
+lgpCondId6687CB7BreakerOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "CB7 breaker open event. Normal state is breaker closed. Latched
+ state is breaker open."
+ ::= { lgpFlexConditionsWellKnown 6687 }
+
+lgpCondId6691GroupIndependentOn OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The group standby/cascade state for this unit has been overridden.
+ The unit has been forced on."
+ ::= { lgpFlexConditionsWellKnown 6691 }
+
+lgpCondId6692GroupIndependentOff OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The group standby/cascade state for this unit has been overridden.
+ The unit has been forced off."
+ ::= { lgpFlexConditionsWellKnown 6692 }
+
+lgpCondId6693BranchResidualOverCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a branch residual over current condition."
+ ::= { lgpFlexConditionsWellKnown 6693 }
+
+lgpCondId6694ReceptacleResidualOverCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a receptacle residual over current
+ condition."
+ ::= { lgpFlexConditionsWellKnown 6694 }
+
+lgpCondId6728BuckOn OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The input voltage is currently being bucked (lowered) by the
+ inverter."
+ ::= { lgpFlexConditionsWellKnown 6728 }
+
+lgpCondId6729BoostOn OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The input voltage is currently being boosted (raised) by the
+ inverter."
+ ::= { lgpFlexConditionsWellKnown 6729 }
+
+lgpCondId6739Compressor1HighPressure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Compressor 1 High Pressure."
+ ::= { lgpFlexConditionsWellKnown 6739 }
+
+lgpCondId6740Compressor2HighPressure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Compressor 2 High Pressure."
+ ::= { lgpFlexConditionsWellKnown 6740 }
+
+lgpCondId6741Compressor1ThermalOverload OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Compressor 1 Thermal Overload."
+ ::= { lgpFlexConditionsWellKnown 6741 }
+
+lgpCondId6742Compressor2ThermalOverload OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Compressor 2 Thermal Overload."
+ ::= { lgpFlexConditionsWellKnown 6742 }
+
+lgpCondId6758CompressorFreezeProtection OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Compressor has entered the freeze protection phase."
+ ::= { lgpFlexConditionsWellKnown 6758 }
+
+lgpCondId6773FanTemperatureCompensationLimitReached OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Unit is configured for fan temperature compensation, and the fan
+ control set point cannot be reduced any further due to high
+ remote air temperature sensor readings."
+ ::= { lgpFlexConditionsWellKnown 6773 }
+
+lgpCondId6774ModbusECFanCommunicationLost OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Communication with Modbus EC fan has been lost."
+ ::= { lgpFlexConditionsWellKnown 6774 }
+
+lgpCondId6785AnalogTemperatureControlIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Analog input used for creating the control temperature (instead of
+ reading a sensor) is disconnected or the signal is out of range."
+ ::= { lgpFlexConditionsWellKnown 6785 }
+
+lgpCondId6786SubgroupFirmwareUpdateRequired OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Mismatch of subgroup firmware. Both the primary and secondary
+ control boards must be running the same firmware version."
+ ::= { lgpFlexConditionsWellKnown 6786 }
+
+lgpCondId6787SubgroupSecondaryControlUnitIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Subgroup secondary control unit is reporting an unspecified issue."
+ ::= { lgpFlexConditionsWellKnown 6787 }
+
+lgpCondId6788EEVCommunicationLost OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Communication with Electronic Expansion Valve unit has been lost."
+ ::= { lgpFlexConditionsWellKnown 6788 }
+
+lgpCondId6789EEVMotorIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Electronic Expansion Valve stepper motor issue."
+ ::= { lgpFlexConditionsWellKnown 6789 }
+
+lgpCondId6790EEVFeedbackIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Electronic Expansion Valve feedback error."
+ ::= { lgpFlexConditionsWellKnown 6790 }
+
+lgpCondId6791EEVPressureSensorIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Electronic Expansion Valve refrigerant pressure sensor is
+ disconnected or the signal is out of range."
+ ::= { lgpFlexConditionsWellKnown 6791 }
+
+lgpCondId6792EEVCoilTemperatureSensorIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Electronic Expansion Valve coil temperature sensor is disconnected
+ or the signal is out of range."
+ ::= { lgpFlexConditionsWellKnown 6792 }
+
+lgpCondId6793EEVDischargeTemperatureSensorIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Electronic Expansion Valve discharge temperature sensor is
+ disconnected or the signal is out of range."
+ ::= { lgpFlexConditionsWellKnown 6793 }
+
+lgpCondId6794EEVSumpTemperatureSensorIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Electronic Expansion Valve sump temperature sensor is disconnected
+ or the signal is out of range."
+ ::= { lgpFlexConditionsWellKnown 6794 }
+
+lgpCondId6795EEVBatteryTestIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Electronic Expansion Valve battery state cannot be determined."
+ ::= { lgpFlexConditionsWellKnown 6795 }
+
+lgpCondId6796EEVBatteryPersistentIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Electronic Expansion Valve has continuously detected a 'bad'
+ battery condition for an extended period of time."
+ ::= { lgpFlexConditionsWellKnown 6796 }
+
+lgpCondId6798PumpCycleLockOut OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Pump is locked out due to multiple pump-to-compressor transitions
+ at cold ambient air temperature."
+ ::= { lgpFlexConditionsWellKnown 6798 }
+
+lgpCondId6799PumpBoardFirmwareUpdateRequired OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Mismatch of pump board firmware. All pump boards must be running
+ the same firmware version."
+ ::= { lgpFlexConditionsWellKnown 6799 }
+
+lgpCondId6800PumpControlBoardIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Pump is shut down due to a pump control board issue. Control
+ board must be rebooted."
+ ::= { lgpFlexConditionsWellKnown 6800 }
+
+lgpCondId6801PumpInvalidDataShutdown OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Pump is shut down due to invalid data."
+ ::= { lgpFlexConditionsWellKnown 6801 }
+
+lgpCondId6802PumpInputPressureSensorIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Pump input refrigerant pressure sensor is disconnected or the
+ signal is out of range."
+ ::= { lgpFlexConditionsWellKnown 6802 }
+
+lgpCondId6803PumpInputTemperatureSensorIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Pump input refrigerant temperature sensor is disconnected or the
+ signal is out of range."
+ ::= { lgpFlexConditionsWellKnown 6803 }
+
+lgpCondId6804PumpOutputPressureSensorIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Pump output refrigerant pressure sensor is disconnected or the
+ signal is out of range."
+ ::= { lgpFlexConditionsWellKnown 6804 }
+
+lgpCondId6805PumpOutputTemperatureSensorIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Pump output refrigerant temperature sensor is disconnected or the
+ signal is out of range."
+ ::= { lgpFlexConditionsWellKnown 6805 }
+
+lgpCondId6806PumpCommunicationLost OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Communication with pump unit has been lost."
+ ::= { lgpFlexConditionsWellKnown 6806 }
+
+lgpCondId6807PumpRemoteShutdown OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Pump is shut down by a remote signal."
+ ::= { lgpFlexConditionsWellKnown 6807 }
+
+lgpCondId6808PumpUSBEthernetPortIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Pump control board USB or Ethernet interface has failed."
+ ::= { lgpFlexConditionsWellKnown 6808 }
+
+lgpCondId6809PumpStartupFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Multiple attempts to start the pump have failed."
+ ::= { lgpFlexConditionsWellKnown 6809 }
+
+lgpCondId6810PumpInverterFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Pump inverter is reporting a failure."
+ ::= { lgpFlexConditionsWellKnown 6810 }
+
+lgpCondId6811PumpTVSSIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Pump Transient Voltage Surge Suppressor or Surge Protection Device
+ has failed."
+ ::= { lgpFlexConditionsWellKnown 6811 }
+
+lgpCondId6812PumpHighSuperheat OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Pump inlet refrigerant superheat temperature is too high, or the
+ pump has been running too long with the condenser fan off."
+ ::= { lgpFlexConditionsWellKnown 6812 }
+
+lgpCondId6813CondenserHighAmbientAirTempDelta OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The difference between condenser measured ambient air temperatures
+ has been too large for an extended period of time."
+ ::= { lgpFlexConditionsWellKnown 6813 }
+
+lgpCondId6814CondenserLeeTempOptionMismatch OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Lee-Temp option configured at a condenser unit does not match Lee
+ -Temp option configured at the control unit."
+ ::= { lgpFlexConditionsWellKnown 6814 }
+
+lgpCondId6815CondenserBoardFirmwareUpdateRequired OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Mismatch of condenser board firmware. All condenser boards must
+ be running the same firmware version."
+ ::= { lgpFlexConditionsWellKnown 6815 }
+
+lgpCondId6816CondenserToPumpHighRefrigerantTempDelta OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Temperature delta between the condenser output refrigerant and
+ pump inlet refrigerant is too large."
+ ::= { lgpFlexConditionsWellKnown 6816 }
+
+lgpCondId6817CondenserRefrigerantTypeMismatch OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Refrigerant type configured at condenser unit does not match
+ refrigerant type configured at the control unit."
+ ::= { lgpFlexConditionsWellKnown 6817 }
+
+lgpCondId6818ExternalSupplyFluidHighTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Supply fluid temperature has exceeded a threshold, as indicated by
+ an external input signal."
+ ::= { lgpFlexConditionsWellKnown 6818 }
+
+lgpCondId6819ExternalSupplyFluidTempSensorIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Supply fluid temperature sensor is disconnected or the signal is
+ out of range, as indicated by an external input signal."
+ ::= { lgpFlexConditionsWellKnown 6819 }
+
+lgpCondId6822AuditLogUpdate OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Audit log has been updated."
+ ::= { lgpFlexConditionsWellKnown 6822 }
+
+lgpCondId6824ExternalSupplyFluidFlowIssue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Supply fluid flow issue, as indicated by an external input signal."
+ ::= { lgpFlexConditionsWellKnown 6824 }
+
+END