commit98a672123c7872f6b9b75a9a2b6bb3aea504de6a (patch)
tree9b13bd7f563c3198047bd359195327cf28b3caf0 /MIBS/orvaldi
downloadmibs-main.tar.gz
mibs-main.zip
Initial commitHEADmain
Diffstat (limited to 'MIBS/orvaldi')
-rw-r--r--MIBS/orvaldi/companyMIB2762
1 files changed, 2762 insertions, 0 deletions
diff --git a/MIBS/orvaldi/companyMIB b/MIBS/orvaldi/companyMIB
new file mode 100644
index 0000000..1ec1838
--- /dev/null
+++ b/MIBS/orvaldi/companyMIB
@@ -0,0 +1,2762 @@
+-- company power MIB
+
+--
+-- { iso org(3) dod(6) internet(1) private(4) enterprises(1) company(2111)
+-- products(1) ups(1)
+--
+-- ==============================================================================================
+
+
+companyMIB DEFINITIONS ::= BEGIN
+
+IMPORTS
+ enterprises
+ FROM RFC1155-SMI
+ MODULE-IDENTITY, OBJECT-TYPE, OBJECT-IDENTITY
+ FROM SNMPv2-SMI
+ DisplayString
+ FROM SNMPv2-TC
+ TRAP-TYPE
+ FROM RFC-1215
+ PositiveInteger, NonNegativeInteger
+ FROM UPS-MIB;
+
+
+ companyMIB MODULE-IDENTITY
+ LAST-UPDATED "201005060000Z"
+ ORGANIZATION "company Power Technology"
+ CONTACT-INFO " "
+
+ DESCRIPTION
+ "The MIB module to describe UPS"
+
+
+
+ ::= { enterprises 21111 }
+
+
+
+products OBJECT IDENTIFIER ::= { companyMIB 1 }
+ups OBJECT IDENTIFIER ::= { products 1 }
+inverter OBJECT IDENTIFIER ::= { products 2 }
+charger OBJECT IDENTIFIER ::= { products 3 }
+ATS OBJECT IDENTIFIER ::= { products 4 }
+
+upsIdent OBJECT IDENTIFIER ::= { ups 1 }
+upsRating OBJECT IDENTIFIER ::= { ups 2 }
+upsBattery OBJECT IDENTIFIER ::= { ups 3 }
+upsInput OBJECT IDENTIFIER ::= { ups 4 }
+upsOutput OBJECT IDENTIFIER ::= { ups 5 }
+upsBypass OBJECT IDENTIFIER ::= { ups 6 }
+upsTest OBJECT IDENTIFIER ::= { ups 7 }
+upsControl OBJECT IDENTIFIER ::= { ups 8 }
+agentConfig OBJECT IDENTIFIER ::= { ups 9 }
+commConfig OBJECT IDENTIFIER ::= { ups 10 }
+upsConfig OBJECT IDENTIFIER ::= { ups 11 }
+upsTraps OBJECT IDENTIFIER ::= { ups 12 }
+extend OBJECT IDENTIFIER ::= { ups 13 }
+
+solarIdent OBJECT IDENTIFIER ::= { inverter 1 }
+solarRating OBJECT IDENTIFIER ::= { inverter 2 }
+solarBattery OBJECT IDENTIFIER ::= { inverter 3 }
+solarGrid OBJECT IDENTIFIER ::= { inverter 4 }
+solarACOutput OBJECT IDENTIFIER ::= { inverter 5 }
+solarPV OBJECT IDENTIFIER ::= { inverter 6 }
+solarEnergy OBJECT IDENTIFIER ::= { inverter 7 }
+solarTest OBJECT IDENTIFIER ::= { inverter 8 }
+solarDefValue OBJECT IDENTIFIER ::= { inverter 9 }
+solarFaultInfo OBJECT IDENTIFIER ::= { inverter 10 }
+solarControl OBJECT IDENTIFIER ::= { inverter 11 }
+solarAgentConfig OBJECT IDENTIFIER ::= { inverter 12 }
+solarCommConfig OBJECT IDENTIFIER ::= { inverter 13 }
+solarConfig OBJECT IDENTIFIER ::= { inverter 14 }
+solarTraps OBJECT IDENTIFIER ::= { inverter 15 }
+solarExtend OBJECT IDENTIFIER ::= { inverter 16 }
+
+
+ATSIdent OBJECT IDENTIFIER ::= { ATS 1 }
+ATSRating OBJECT IDENTIFIER ::= { ATS 2 }
+ATSInformation OBJECT IDENTIFIER ::= { ATS 3 }
+ATSControl OBJECT IDENTIFIER ::= { ATS 4 }
+ATSAgentConfig OBJECT IDENTIFIER ::= { ATS 5 }
+ATSCommConfig OBJECT IDENTIFIER ::= { ATS 6 }
+ATSConfig OBJECT IDENTIFIER ::= { ATS 7 }
+ATSTraps OBJECT IDENTIFIER ::= { ATS 8 }
+ATSExtend OBJECT IDENTIFIER ::= { ATS 9 }
+
+---=======================================================
+---upsIdent
+--- prefix =upsId
+---========================================================
+
+upsIdManufacturer OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..31))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the UPS manufacturer."
+ ::= { upsIdent 1 }
+
+upsIdProtocol OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(-1),
+ pmv(99),
+ p00(0),
+ p01(1),
+ p02(2),
+ p03(3),
+ p04(4),
+ p05(5),
+ p06(6),
+ p07(7),
+ p08(8),
+ p09(9),
+ p10(10),
+ sec(80)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The UPS Protocol id."
+ ::= { upsIdent 2 }
+
+upsIdModelName OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..15))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The UPS Model designation."
+ ::= { upsIdent 3 }
+
+upsIdSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString (SIZE(0..31))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The UPS serial no."
+ ::= { upsIdent 4 }
+
+upsIdName OBJECT-TYPE
+ SYNTAX DisplayString (SIZE(0..31))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A string identifying the UPS. This object should be
+ set by the administrator."
+ ::= { upsIdent 5 }
+
+upsIdFWVersion OBJECT-TYPE
+ SYNTAX DisplayString (SIZE(0..31))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Main CPU firmware version."
+ ::= { upsIdent 6 }
+
+
+upsIdUPSType OBJECT-TYPE
+ SYNTAX INTEGER {
+ standy(0),
+ line-interactive(1),
+ on-line(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "UPS type."
+ ::= { upsIdent 7 }
+--===========================================================================
+--upsRating
+--prefix =upsRat
+--the rating info of ups
+--==========================================================================
+upsRatinVoltage OBJECT-TYPE
+ SYNTAX NonNegativeInteger
+ UNITS "0.1 Volt DC"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The rating input voltage of UPS"
+ ::= { upsRating 1 }
+
+upsRatoutVoltage OBJECT-TYPE
+ SYNTAX NonNegativeInteger
+ UNITS "0.1 Volt DC"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The rating output voltage of UPS"
+ ::= { upsRating 2 }
+
+upsRatoutFrequency OBJECT-TYPE
+ SYNTAX NonNegativeInteger
+ UNITS "0.1 HZ"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The rating output frequency of UPS"
+ ::= { upsRating 3 }
+
+upsRatoutCurrent OBJECT-TYPE
+ SYNTAX NonNegativeInteger
+ UNITS "0.1 Amp DC"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The rating output current of UPS"
+ ::= { upsRating 4 }
+
+upsRatoutApparentPower OBJECT-TYPE
+ SYNTAX NonNegativeInteger
+ UNITS "0.1 VA"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The rating output apparent power of UPS"
+ ::= { upsRating 5 }
+
+upsRatoutTruePower OBJECT-TYPE
+ SYNTAX NonNegativeInteger
+ UNITS "0.1 Wt"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The rating output true power of UPS"
+ ::= { upsRating 6 }
+
+upsRatBatVoltage OBJECT-TYPE
+ SYNTAX NonNegativeInteger
+ UNITS "0.1 vol"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The rating battery voltage of UPS"
+ ::= { upsRating 7 }
+
+
+
+-- ===========================================================================
+-- upsBattery
+-- prefix = upsBat
+-- The Battery group.
+-- est=estimated
+-- ===========================================================================
+
+upsBatStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(1),
+ batteryNormal(2),
+ batteryLow(3),
+ batteryDepleted(4),
+ batteryDischarging(5),
+ batteryFailure(6),
+ batteryReplace(7),
+ batterysilence(8)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The indication of the status in the UPS system's batteries."
+ ::= { upsBattery 1 }
+
+
+
+upsBatSecondsOnBattery OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "seconds"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "If the unit is on battery power, the elapsed time
+ since the UPS last switched to battery power, or the
+ time since the network management subsystem was last
+ restarted, whichever is less. -1 shall be returned
+ if the unit is not on battery power."
+ ::= { upsBattery 2 }
+
+upsBatEstMinutesRemaining OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "minutes"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "An estimate of the time to battery charge depletion
+ under the present load conditions if the utility power
+ is off and remains off, or if it were to be lost and
+ remain off."
+ ::= { upsBattery 3 }
+
+upsBatEstChargeRemaining OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ UNITS "percent"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "An estimate of the battery charge remaining expressed
+ as a percent of full charge."
+ ::= { upsBattery 4 }
+
+upsBatPBatVoltage OBJECT-TYPE
+ SYNTAX NonNegativeInteger
+ UNITS "0.1 Volt DC"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The magnitude of the present Positive battery voltage."
+ ::= { upsBattery 5 }
+
+
+upsBatNBatVoltage OBJECT-TYPE
+ SYNTAX NonNegativeInteger
+ UNITS "0.1 Volt DC"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The magnitude of the present negative battery voltage."
+ ::= { upsBattery 6 }
+
+upsBatPBatCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "0.1 Amp DC"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The positive battery present current."
+ ::= { upsBattery 7 }
+
+upsBatNBatCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "0.1 Amp DC"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present negative battery current."
+ ::= { upsBattery 8 }
+
+upsBatPBatChargCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "0.1 Amp DC"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The Positive battery charging current."
+ ::= { upsBattery 9 }
+
+upsBatNBatchargCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "0.1 Amp DC"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present negative battery charging current."
+ ::= { upsBattery 10 }
+
+upsBatPBatDischargCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "0.1 Amp DC"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present positive battery discharging current."
+ ::= { upsBattery 11 }
+
+upsBatNBatDischargCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "0.1 Amp DC"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present negative battery discharging current."
+ ::= { upsBattery 12 }
+
+upsBatTemperature OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "degrees 0.1 Centigrade"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The ambient temperature at or near the UPS Battery
+ casing."
+ ::= { upsBattery 13 }
+
+upsBatNumberInSeries OBJECT-TYPE
+ SYNTAX PositiveInteger
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of battery in series."
+ ::= { upsBattery 14 }
+
+
+upsBatNumberInParallel OBJECT-TYPE
+ SYNTAX PositiveInteger
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of battery in Parallel."
+ ::= { upsBattery 15 }
+
+upsBatPBatDischargCurrent2 OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "0.1 Amp DC"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present positive battery pipe2 discharging current."
+ ::= { upsBattery 16 }
+
+-- ===========================================================================
+-- upsInput
+-- prefix = upsIn
+-- Input group.
+-- ===========================================================================
+
+upsInLineBads OBJECT-TYPE
+ SYNTAX NonNegativeInteger
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "A count of the number of times the input entered an
+ out-of-tolerance condition as defined by the
+ manufacturer. This count is incremented by one each
+ time the input transitions from zero out-of-tolerance
+ lines to one or more input lines out-of-tolerance."
+ ::= { upsInput 1 }
+
+
+upsInTtlApparentPower OBJECT-TYPE
+ SYNTAX NonNegativeInteger
+ UNITS "0.1VA"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Total input apparent power ."
+ ::= { upsInput 2 }
+
+upsInTtlTruePower OBJECT-TYPE
+ SYNTAX NonNegativeInteger
+ UNITS "0.1WT"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Total input active(true) power ."
+ ::= { upsInput 3 }
+
+
+
+upsInNumLines OBJECT-TYPE
+ SYNTAX NonNegativeInteger
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of input lines utilized in this device.
+ This variable indicates the number of rows in the
+ input table."
+ ::= { upsInput 4 }
+
+
+upsInTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsInEntry
+ ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A list of input table entries. The number of entries
+ is given by the value of upsInputNumLines."
+ ::= { upsInput 5 }
+
+
+upsInTtlVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "0.1 Volts"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The input utility line tatol voltage ."
+ ::= { upsInput 6 }
+
+upsInTtlCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "0.1 A"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The input utility line tatol current."
+ ::= { upsInput 7 }
+
+upsInEntry OBJECT-TYPE
+ SYNTAX UpsInEntry
+ ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular input line."
+ INDEX { upsInLineIndex }
+ ::= { upsInTable 1 }
+
+UpsInEntry ::=
+ SEQUENCE {
+ upsInLineIndex PositiveInteger,
+ upsInFrequency NonNegativeInteger,
+ upsInVoltage NonNegativeInteger,
+ upsInCurrent NonNegativeInteger,
+ upsInApparentPower NonNegativeInteger,
+ upsInTruePower NonNegativeInteger,
+ upsInPowerFactor NonNegativeInteger,
+ upsInLineVoltage NonNegativeInteger
+ }
+
+upsInLineIndex OBJECT-TYPE
+ SYNTAX INTEGER (0..10)
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of output lines"
+ ::= { upsInEntry 1 }
+
+upsInFrequency OBJECT-TYPE
+ SYNTAX NonNegativeInteger
+ UNITS "0.1 Hertz"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present input frequency."
+ ::= { upsInEntry 2 }
+
+upsInVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "0.1 Volts"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The input utility line voltage ."
+ ::= { upsInEntry 3 }
+
+upsInCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "0.1Amp"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The magnitude of the present input current "
+ ::= { upsInEntry 4 }
+
+
+
+upsInApparentPower OBJECT-TYPE
+ SYNTAX NonNegativeInteger
+ UNITS "0.1VA"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The magnitude of the present input Apparent power."
+ ::= { upsInEntry 5 }
+
+
+upsInTruePower OBJECT-TYPE
+ SYNTAX NonNegativeInteger
+ UNITS "0.1Watts"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The magnitude of the present input true power."
+ ::= { upsInEntry 6 }
+
+
+
+upsInPowerFactor OBJECT-TYPE
+ SYNTAX NonNegativeInteger
+ UNITS "0.01"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Input true power/apparent power factor "
+ ::= { upsInEntry 7 }
+
+upsInLineVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "0.1 Volts"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The input utility line voltage .
+ if upsInLineIndex =1, upsInLineVoltage = Line voltage of RS phase;
+ if upsInLineIndex =2, upsInLineVoltage = Line voltage of ST phase;
+ if upsInLineIndex =3, upsInLineVoltage = Line voltage of TR phase."
+ ::= { upsInEntry 8 }
+
+-- ===========================================================================
+-- upsOutput
+-- prefix= upsOut
+-- Output group
+-- ===========================================================================
+
+upsOutSource OBJECT-TYPE
+ SYNTAX INTEGER {
+ other(1),
+ none(2),
+ normal(3),
+ bypass(4),
+ battery(5),
+ booster(6),
+ reducer(7),
+ batterytest(8),
+ fault(9),
+ HE-ECOmode(10),
+ convertermode(11)
+ }
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present source of output power. The enumeration
+ none(2) indicates that there is no source of output
+ power (and therefore no output power), for example,
+ the system has opened the output breaker.==UPS standby mode"
+ ::= { upsOutput 1 }
+
+upsOutFrequency OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "0.1 Hertz"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The current output frequency of the UPS system "
+ ::= { upsOutput 2 }
+
+
+upsOutTtlApparentPower OBJECT-TYPE
+ SYNTAX NonNegativeInteger
+ UNITS "0.1VA"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Total output apparent power ."
+ ::= { upsOutput 3 }
+
+upsOutTtlTruePower OBJECT-TYPE
+ SYNTAX NonNegativeInteger
+ UNITS "0.1Watts"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Total output active(true) power ."
+ ::= { upsOutput 4 }
+
+
+upsOutTtlPercentLoad OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ UNITS "percent"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The percentage of the UPS power capacity presently
+ being used on this output line, i.e., the greater of
+ the percent load of true power capacity and the
+ percent load of VA."
+ ::= { upsOutput 5 }
+
+
+
+
+upsOutNumLines OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of output lines utilized in this device.
+ This variable indicates the number of rows in the
+ output table."
+ ::= { upsOutput 6 }
+
+upsOutTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsOutEntry
+ ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A list of output table entries. The number of
+ entries is given by the value of upsOutputNumLines."
+ ::= { upsOutput 7 }
+
+
+upsOutTtlVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "0.1vot"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Total output voltage ."
+ ::= { upsOutput 8 }
+
+upsOutTtlCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "0.1A"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Total output current."
+ ::= { upsOutput 9 }
+
+upsOutStatus OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (4..4))
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ " For HVDC device.
+ char status[4];
+ status[0]status[1]:00, no output1; 01, line output1; 02, bat output1
+ status[2]status[3]:00, no output2; 01, line output2; 02, bat output2
+ "
+ ::= { upsOutput 10 }
+
+
+
+upsOutSource2 OBJECT-TYPE
+ SYNTAX INTEGER {
+ other(1),
+ none(2),
+ normal(3),
+ bypass(4),
+ battery(5),
+ booster(6),
+ reducer(7),
+ batterytest(8),
+ fault(9),
+ HE-ECOmode(10),
+ convertermode(11)
+ }
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "For HVDC(protocol:P12) machine. The present source of output power. The enumeration
+ none(2) indicates that there is no source of output
+ power (and therefore no output power), for example,
+ the system has opened the output breaker.==UPS standby mode"
+ ::= { upsOutput 11 }
+
+
+upsOutEntry OBJECT-TYPE
+ SYNTAX UpsOutEntry
+ ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular output line."
+ INDEX { upsOutLineIndex }
+ ::= { upsOutTable 1 }
+
+UpsOutEntry ::=
+ SEQUENCE {
+ upsOutLineIndex PositiveInteger,
+ upsOutVoltage NonNegativeInteger,
+ upsOutCurrent NonNegativeInteger,
+ upsOutApparentPower NonNegativeInteger,
+ upsOutTruePower NonNegativeInteger,
+ upsOutPowerFactor NonNegativeInteger,
+ upsOutPercentLoad INTEGER,
+ upsOutLineVoltage NonNegativeInteger
+ }
+
+upsOutLineIndex OBJECT-TYPE
+ SYNTAX INTEGER (0..10)
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The output line identifier."
+ ::= { upsOutEntry 1 }
+
+upsOutVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "0.1 Volts"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The output voltage of the UPS system."
+ ::= { upsOutEntry 2 }
+
+upsOutCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "0.1 Amp"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The output current of the UPS system"
+ ::= { upsOutEntry 3 }
+
+upsOutApparentPower OBJECT-TYPE
+ SYNTAX NonNegativeInteger
+ UNITS "0.1VA"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present output apparent power."
+ ::= { upsOutEntry 4 }
+
+upsOutTruePower OBJECT-TYPE
+ SYNTAX NonNegativeInteger
+ UNITS "0.1Watts"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present output true power."
+ ::= { upsOutEntry 5 }
+
+upsOutPowerFactor OBJECT-TYPE
+ SYNTAX NonNegativeInteger
+ UNITS "0.01"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Output true power/apparent power factor "
+ ::= { upsOutEntry 6 }
+
+upsOutPercentLoad OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ UNITS "percent"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The percentage of the UPS power capacity presently
+ being used on this output line, i.e., the greater of
+ the percent load of true power capacity and the
+ percent load of VA."
+ ::= { upsOutEntry 7 }
+
+upsOutLineVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "0.1 Volts"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The output line voltage of the UPS system.
+ if upsOutLineIndex =1, upsOutLineVoltage = Line voltage of RS phase;
+ if upsOutLineIndex =2, upsOutLineVoltage = Line voltage of ST phase;
+ if upsOutLineIndex =3, upsOutLineVoltage = Line voltage of TR phase."
+ ::= { upsOutEntry 8 }
+
+upsOutFrequency OBJECT-TYPE
+ SYNTAX NonNegativeInteger
+ UNITS "0.1Hertz"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present output frequency."
+ ::= { upsOutEntry 9 }
+
+-- ===========================================================================
+-- upsBypass
+-- prefix =upsBy
+-- ===========================================================================
+
+upsByFrequency OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "0.1 Hertz"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present bypass frequency."
+ ::= { upsBypass 1 }
+
+
+
+upsByNumLines OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of bypass lines utilized in this device.
+ This entry indicates the number of rows in the bypass
+ table."
+ ::= { upsBypass 2 }
+
+
+upsByTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UpsByEntry
+ ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A list of bypass table entries. The number of
+ entries is given by the value of upsBypassNumLines."
+ ::= { upsBypass 3 }
+
+upsByEntry OBJECT-TYPE
+ SYNTAX UpsByEntry
+ ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular bypass input."
+ INDEX { upsByLineIndex }
+ ::= { upsByTable 1 }
+
+UpsByEntry ::=
+ SEQUENCE {
+ upsByLineIndex PositiveInteger,
+ upsByVoltage NonNegativeInteger,
+ upsByCurrent NonNegativeInteger,
+ upsByPower NonNegativeInteger,
+ upsByLineVoltage INTEGER
+ }
+
+upsByLineIndex OBJECT-TYPE
+ SYNTAX INTEGER (0..65535)
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The bypass line identifier."
+ ::= { upsByEntry 1 }
+
+upsByVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "0.1 Volts"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present bypass voltage."
+ ::= { upsByEntry 2 }
+
+upsByCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "0.1 RMS Amp"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present bypass current."
+ ::= { upsByEntry 3 }
+
+upsByPower OBJECT-TYPE
+ SYNTAX NonNegativeInteger
+ UNITS "0.1Watts"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present true power conveyed by the bypass."
+ ::= { upsByEntry 4 }
+
+upsByLineVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "0.1 Volts"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present bypass line voltage.
+ if upsByLineIndex=1,upsByLineVoltage=Line voltage of RS phase;
+ if upsByLineIndex=2,upsByLineVoltage=Line voltage of ST phase;
+ if upsByLineIndex=3,upsByLineVoltage=Line voltage of TR phase."
+ ::= { upsByEntry 5 }
+
+-- ===========================================================================
+-- upsTest
+-- prefix=upsTst
+-- ===========================================================================
+
+
+upsTstBatteryTest OBJECT-TYPE
+ SYNTAX INTEGER {
+ none(1),
+ battTest10sec(2),
+ battTestUntilLow(3),
+ battTestWithTime(4),
+ battTestCancelTest(5),
+ battTestClearInfo(6)
+
+ }
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "This object specify the battery test type and initiate
+ battery test. If battTestWithTime selected, the test
+ time is refer to upsTestBatteryTestTime."
+ ::= { upsTest 1 }
+
+upsTstBatteryTestResult OBJECT-TYPE
+ SYNTAX INTEGER {
+ donePassed(1),
+ doneWarning(2),
+ doneError(3),
+ aborted(4),
+ inProgress(5),
+ noTestsInitiated(6)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The results of the current or last UPS diagnostics
+ test performed. The values for donePassed(1),
+ doneWarning(2), and doneError(3) indicate that the
+ test completed either successfully, with a warning, or
+ with an error, respectively. The value aborted(4) is
+ returned for tests which are aborted by setting the
+ value of upsTestId to upsTestAbortTestInProgress.
+ Tests which have not yet concluded are indicated by
+ inProgress(5). The value noTestsInitiated(6)
+ indicates that no previous test results are available,
+ such as is the case when no tests have been run since
+ the last reinitialization of the network management
+ subsystem and the system has no provision for non-
+ volatile storage of test results."
+ ::= { upsTest 2 }
+
+
+
+upsTstBatteryTestStartTime OBJECT-TYPE
+ SYNTAX DisplayString (SIZE(19..19))
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The value of the time the test in progress was initiated,
+ or, if no test is in progress, the time the previous test
+ was initiated. If the value of upsTestBatteryTestResult
+ is noTestsInitiated(6), upsTestStartTime has the value
+ 01/01/1970 00:00:00. format is (MM/DD/YYYY hh:mm:ss)"
+ ::= { upsTest 3 }
+
+
+upsTstBatterySettingTime OBJECT-TYPE
+ SYNTAX INTEGER (12..5940)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The object specify the test time for battery test, the unit is seconds"
+ ::= { upsTest 4 }
+
+ --below 1 minute 0.2-1.0 ,larger than 1 minutes ,1,2,3..99;
+
+-- ===========================================================================
+-- upsControl
+-- prefix=upsCtl
+-- ===========================================================================
+
+
+upsCtlShutdownDelay OBJECT-TYPE
+ SYNTAX INTEGER (-2..2147483648)
+ UNITS "seconds"
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The delay in seconds the UPS remains on after being told
+ to turn off. if value=-2 cancel shutdown, if value=-1 donothing,
+ value=0 shutdown ups immediately"
+ ::= { upsControl 1 }
+
+
+upsCtlSleepTime OBJECT-TYPE
+ SYNTAX INTEGER (-1..2147483648)
+ UNITS "minutes"
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The time in minutes for the UPS to go to sleep when
+ instructed. When in sleep mode, the UPS will not provide
+ output power regardless of the input line state. Once the
+ specified time has elapsed, output power will be restored.
+
+ This is a configuration setting. The UPS will not go to
+ sleep until told to do so by the manager from a management
+ station.
+
+ Any input value is allowed, however the UPS only recognizes
+ 0 - 9999 minutes in one minute increments.
+
+ If the provided value is higher than the highest acceptable
+ value, the highest acceptable value is used."
+ ::= { upsControl 2 }
+
+upsCtlStartupAfterDelay OBJECT-TYPE
+ SYNTAX INTEGER (-1..2147483648)
+ UNITS "seconds"
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Setting this object will start the output after the
+ indicated number of seconds, including starting the
+ UPS, if necessary. -1 mean not startup.
+ must set upsCtlStartupAfterDelay before upsCtlShutdownDelay ,
+ the value must larger than 59 if the value not equal -1 "
+
+ ::= { upsControl 3 }
+
+
+
+upsCtlbuzzer OBJECT-TYPE
+ SYNTAX INTEGER {
+ on(1),
+ off(2)
+ }
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Setting this object to 'on' or 'off' to enable or disable buzzer"
+
+ ::= { upsControl 4 }
+
+
+
+upsCtlRemoteControlUPS OBJECT-TYPE
+ SYNTAX INTEGER {
+ on(1),
+ off(2)
+ }
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Setting this object to turn 'on' or 'off' UPS "
+
+ ::= { upsControl 5 }
+
+upsCtloutletPoweron OBJECT-TYPE
+ SYNTAX INTEGER (1..2)
+ ACCESS write-only
+ STATUS current
+ DESCRIPTION
+ "Setting this object to 1 means 1st outlet,2 means 2nd outlet , immediately process"
+
+ ::= { upsControl 6 }
+
+
+
+upsCtloutletPoweroff OBJECT-TYPE
+ SYNTAX INTEGER (1..2)
+ ACCESS write-only
+ STATUS current
+ DESCRIPTION
+ "Setting this object to 1 means 1st outlet,
+ 2 means 2nd outlet , immediately process"
+
+ ::= { upsControl 7 }
+
+
+upsCtlOutlet1Powerofftime OBJECT-TYPE
+ SYNTAX INTEGER (-1..999)
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "setting this object to -1 means this control not effect,
+ 0 means immediately process,
+ >0 means wait times unit is minutes
+ use in battery mode"
+ ::= { upsControl 8 }
+
+upsCtlOutlet2Powerofftime OBJECT-TYPE
+ SYNTAX INTEGER (-1..999)
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "setting this object to -1 means this control not effect,
+ 0 means immediately process ,
+ >0 means wait times unit is minutes .use in battery mode"
+ ::= { upsControl 9 }
+
+upsCtlResetConfigure OBJECT-TYPE
+ SYNTAX INTEGER {
+ none(0),
+ reset(1)
+ }
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " reset all configure para to default."
+ ::= { upsControl 10 }
+
+
+--===========================================================================
+--
+-- agentConfig
+-- prefix=agent
+-- ===========================================================================
+
+
+agentConfigDatetime OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (19..19))
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The datetime in agent, format is (MM/DD/YYYY hh:mm:ss)"
+ ::= { agentConfig 1 }
+
+
+
+
+---======================================================================
+-- commConfig
+-- prefix =comm
+---======================================================================
+
+commBaudRate OBJECT-TYPE
+ SYNTAX INTEGER {
+ B1200(1),
+ B2400(2),
+ B4800(3),
+ B9600(4),
+ B19200(5)
+ }
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The UPS communicate baudrate"
+ ::= { commConfig 1 }
+
+
+
+commDatabits OBJECT-TYPE
+ SYNTAX INTEGER (8..9)
+
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The UPS communicate data bits"
+ ::= { commConfig 2 }
+
+
+commStopbits OBJECT-TYPE
+ SYNTAX INTEGER (1..2)
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The UPS communicate stop bits "
+
+ ::= { commConfig 3 }
+
+commParity OBJECT-TYPE
+ SYNTAX INTEGER {
+ none(0),
+ odd(1),
+ even(2)
+ }
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The UPS communicate Parity "
+ ::= { commConfig 4 }
+
+commTimeout OBJECT-TYPE
+ SYNTAX INTEGER (100..1000)
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The UPS communicate timeout"
+ ::= { commConfig 5 }
+
+
+--===========================================================================
+--
+-- upsConfig
+--prefix=upsCfg
+-- ===========================================================================
+
+upsCfgAlarmbypass OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable(0),
+ enable(1),
+ notsupport(2)
+
+ }
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Setting this object enable /disable alarm bypass mode"
+
+ ::= { upsConfig 1 }
+
+upsCfgAlarmbattery OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable(0),
+ enable(1),
+ notsupport(2)
+ }
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Setting this object enable/disable alarm battery mode"
+
+ ::= { upsConfig 2 }
+
+upsCfgAutoReboot OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable(0),
+ enable(1),
+ notsupport(2)
+ }
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Setting this object enable/disable auto reboot"
+ ::= { upsConfig 3 }
+
+
+upsCfgBypasswhenupsoff OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable(0),
+ enable(1),
+ notsupport(2)
+ }
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Setting this object start/stop bypass when ups off"
+ ::= { upsConfig 4 }
+
+
+upsCfgBatterDDP OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable(0),
+ enable(1),
+ notsupport(2)
+ }
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Setting this object to enable/disable battery deep-discharge protection"
+ ::= { upsConfig 5 }
+
+
+
+
+upsCfgConvertermode OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable(0),
+ enable(1),
+ notsupport(2)
+ }
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Setting this object to enable/disable converter mode "
+
+ ::= { upsConfig 6 }
+
+
+upsCfgECOmode OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable(0),
+ enable(1),
+ notsupport(2)
+ }
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Setting this object to enable/disable ECO mode"
+ ::= { upsConfig 7 }
+
+
+
+upsCfgAdvanceECOmode OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable(0),
+ enable(1),
+ notsupport(2)
+ }
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Setting this object to enable/disable advance ECO mode"
+ ::= { upsConfig 8 }
+
+
+upsCfgGreenPowerFunction OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable(0),
+ enable(1),
+ notsupport(2)
+ }
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Setting this object to enable/disable green power function"
+ ::= { upsConfig 9 }
+
+
+
+
+upsCfgBatteryOSC OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable(0),
+ enable(1),
+ notsupport(2)
+ }
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Setting this object to enable/disable battery open status check"
+ ::= { upsConfig 10 }
+
+
+upsCfgAllowShort3times OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable(0),
+ enable(1),
+ notsupport(2)
+ }
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Setting this object to enable/disable short 3 times"
+ ::= { upsConfig 11 }
+
+
+
+upsCfgColdstart OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable(0),
+ enable(1),
+ notsupport(2)
+
+ }
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Setting this object to cold start ups"
+ ::= { upsConfig 12 }
+
+
+upsCfgBypassNotAllowed OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable(0),
+ enable(1),
+ notsupport(2)
+
+ }
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Setting this object to enable/disable bypass mode"
+ ::= { upsConfig 13 }
+
+
+upsCfgBatterylowprotect OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable(0),
+ enable(1),
+ notsupport(2)
+
+ }
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Setting this object to enable/disable battery low protect"
+ ::= { upsConfig 14 }
+
+
+
+upsCfgP1progoutletcontrol OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable(0),
+ enable(1),
+ notsupport(2)
+ }
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Setting this object to enable/disable p1 programmable outlet control (battery mode)"
+ ::= { upsConfig 15 }
+
+
+
+upsCfgP2progoutletcontrol OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable(0),
+ enable(1),
+ notsupport(2)
+ }
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Setting this object to enable/disable p2 programmable outlet control (battery mode)"
+ ::= { upsConfig 16 }
+
+
+upsCfgInverterShortClear OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable(0),
+ enable(1),
+ notsupport(2)
+ }
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Setting this object to enable/disable Inverter short clear function"
+ ::= { upsConfig 17 }
+
+
+
+
+upsCfgSitefaildetection OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable(0),
+ enable(1),
+ notsupport(2)
+ }
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Setting this object to enable/disable site fail detection"
+ ::= { upsConfig 18 }
+
+
+
+upsCfgBatNumInParallel OBJECT-TYPE
+ SYNTAX INTEGER (1..99)
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Battery numbers in parallel (battery numbers setting)"
+ ::= { upsConfig 19 }
+
+
+upsCfgBatNumInSeries OBJECT-TYPE
+ SYNTAX INTEGER (1..20)
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Battery numbers in series (battery numbers setting)"
+ ::= { upsConfig 20 }
+
+
+
+upsCfgBypassmaxvoltage OBJECT-TYPE
+ SYNTAX INTEGER (1760..2760)
+ UNITS "0.1 Volts"
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Bypass mode max voltage"
+
+ ::= { upsConfig 21 }
+
+
+upsCfgBypassminvoltage OBJECT-TYPE
+ SYNTAX INTEGER (1760..2640)
+ UNITS "0.1 Volts"
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Bypass mode min voltage"
+ ::= { upsConfig 22 }
+
+
+upsCfgBypassmaxfrequency OBJECT-TYPE
+ SYNTAX INTEGER (510..700) -- ( 510..600 ,610..700)
+ UNITS "0.1 Hertz"
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Bypass mode max frequency ,for 50 HZ (510..600) for 60HZ (610..700)"
+ ::= { upsConfig 23 }
+
+
+
+upsCfgBypassminfrequency OBJECT-TYPE
+ SYNTAX INTEGER (400..590) --(400..490,500..590)
+ UNITS "0.1 Hertz"
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Bypass mode min frequency, for 50HZ (400..490) for 60Hz (500..590)"
+ ::= { upsConfig 24 }
+
+
+
+upsCfgECOmaxvoltage OBJECT-TYPE
+ SYNTAX INTEGER (10..3000)
+ UNITS "0.1 Volts"
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "ECO mode max voltage"
+
+ ::= { upsConfig 25 }
+
+upsCfgECOminvoltage OBJECT-TYPE
+ SYNTAX INTEGER (10..3000)
+ UNITS "0.1 Volts"
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "ECO mode min voltage"
+ ::= { upsConfig 26 }
+
+
+upsCfgFreeRunMaxFrequency OBJECT-TYPE
+ SYNTAX INTEGER (400..700)
+ UNITS "0.1 Hertz "
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Free run mode max frequency"
+ ::= { upsConfig 27 }
+
+
+
+upsCfgFreeRunMinFrequency OBJECT-TYPE
+ SYNTAX INTEGER (400..700)
+ UNITS "0.1 Hertz "
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Free run mode min frequency"
+ ::= { upsConfig 28 }
+
+
+
+
+upsCfgEPOStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable(0),
+ enable(1)
+ }
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Get EPO status,configured by mamual"
+ ::= { upsConfig 29 }
+
+
+
+upsCfgQSK1Status OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable(0),
+ enable(1)
+ }
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Get QSK 1 status"
+ ::= { upsConfig 30 }
+
+upsCfgQSK2Status OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable(0),
+ enable(1)
+ }
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Get QSK 2 status"
+ ::= { upsConfig 31 }
+
+upsCfgQSKT1Delaytime OBJECT-TYPE
+ SYNTAX INTEGER (0..999)
+ UNITS "minutes "
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Get QSKT 1 time delay"
+ ::= { upsConfig 32 }
+
+upsCfgQSKT2Delaytime OBJECT-TYPE
+ SYNTAX INTEGER (0..999)
+ UNITS "minutes "
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Get QSKT 2 time delay"
+ ::= { upsConfig 33 }
+
+upsCfgConstantPhaseAngle OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable(0),
+ enable(1)
+ }
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "setting this object to Enable/disable Constant Phase Angle function"
+ ::= { upsConfig 34 }
+
+---PE/PD q
+
+upsCfgInPhaseAngle OBJECT-TYPE
+ SYNTAX INTEGER {
+ Angle000(0),
+ Angle120(120),
+ Angle180(180),
+ Angle240(240)
+ }
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Get input phase angle"
+ ::= { upsConfig 35 }
+
+---QPD
+
+upsCfgOutPhaseAngle OBJECT-TYPE
+ SYNTAX INTEGER {
+ Angle000(0),
+ Angle120(120),
+ Angle180(180),
+ Angle240(240)
+ }
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Set output phase angle"
+ ::= { upsConfig 36 }
+
+---QPD PPD<NNN>
+
+upsCfgLimiRunOnBatMode OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable(0),
+ enable(1),
+ notsupport(2)
+ }
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Enable/disable limited runtime on battery mode"
+ ::= { upsConfig 37 }
+
+
+upsCfgChargingCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "0.1 Amp DC"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Set charging current to battery ."
+ ::= { upsConfig 38 }
+
+upsCfgBatSeftCheckVolt OBJECT-TYPE
+ SYNTAX INTEGER (2400..2800)
+ UNITS "0.1 Volts"
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "BatTest until battery voltage lower than <nnn>"
+ ::= { upsConfig 39 }
+
+upsCfgOverChargVolt OBJECT-TYPE
+ SYNTAX INTEGER (130..143)
+ UNITS "0.1 Volts"
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "set over charging voltage to per battery"
+ ::= { upsConfig 40 }
+
+upsCfgBattUnderVolt OBJECT-TYPE
+ SYNTAX INTEGER (2000..2400)
+ UNITS "0.1 Volts"
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "set battery under voltage of setting value.value is a number ranging from 200V to 240V"
+ ::= { upsConfig 41 }
+
+upsCfgBattLowVolt OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "0.1 Volts"
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "set battery low voltage of setting value.it is 10 to 40V high than battery under voltage.
+ it is 10 to 40V high than battery under voltage.default 20.
+ it means that the battery low point is battery under add 20.
+ for example, if the battery under voltage is 210V, the battry low point voltage is 230V.
+ "
+ ::= { upsConfig 42 }
+
+upsCfgIn1VoltHLoss OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "0.1 Volts"
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "set input1 voltage high loss point."
+ ::= { upsConfig 43 }
+
+upsCfgIn1VoltLLoss OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "0.1 Volts"
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "set input1 voltage low loss point."
+ ::= { upsConfig 44 }
+
+upsCfgIn2VoltHLoss OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "0.1 Volts"
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "set input2 voltage high loss point."
+ ::= { upsConfig 45 }
+
+upsCfgIn2VoltLLoss OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "0.1 Volts"
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "set input2 voltage low loss point."
+ ::= { upsConfig 46 }
+
+upsCfgBatteryTurnOn OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable(0),
+ enable(1),
+ notsupport(2)
+ }
+ ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Enable/disable battery turn on."
+ ::= { upsConfig 47 }
+
+-- ===========================================================================
+-- upsTraps
+-- prefix = upsTraps
+-- Traps group
+-- ===========================================================================
+
+ -- This section defines the well-known notifications sent by
+ -- UPS agents.
+
+ -- this traps use one share trap-node for send traps ,the trap-node vlaue between 1 and 127.
+ -- the share trap-node name is trapleafnodev1v2;
+
+-- if failure or warning occur ,traps send immediately , if question not resolved,agent will resend every 4 seconds.
+-- info only send once
+
+trapleafnodev103 OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (16..16))
+ ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "The share trap-node for send all traps,snmpcard V1-03 and later use this trap-node
+ char trap[16];
+ trap[0]: trap[0]=1,fault trap ; trap[0]=0,warn trap"
+ ::= { upsTraps 998 }
+
+trapleafnodev1v2 OBJECT-TYPE
+ SYNTAX INTEGER (0..255)
+ ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "The share trap-node for send all traps"
+ ::= { upsTraps 999 }
+
+
+cmpACFailure TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "AC failure"
+ ::= 1
+
+cmpFanFailure TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Fan failure"
+ ::= 2
+
+cmpUPSFailure TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "UPS failure"
+ ::= 3
+
+cmpChargerFailure TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Charger failure"
+ ::= 4
+
+cmpOverloadFailure TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Overload failure"
+ ::= 5
+
+cmpOvertempFailure TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Over temperature fault."
+ ::= 6
+
+cmpInvertershortcircuited TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Inverter short-circuited"
+ ::= 7
+
+cmpbatteryfusebeingoc TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Battery fuse being open-dcircuited failure"
+ ::= 8
+
+
+
+cmpLowbattery TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "The UPS has returned from a low battery
+ condition."
+ ::= 9
+
+cmpSysgotoshutdown TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "System is going to shutdown"
+ ::= 10
+
+
+cmpSitefault TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Site fault"
+ ::= 11
+
+
+cmpPhasesequenceincorrect TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Phase sequence incorrect"
+ ::= 12
+
+cmpPhasesequenceincorrectbypass TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Phase sequence incorrect in bypass"
+ ::= 13
+
+cmpFanalarm TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Fan alarm."
+ ::= 14
+
+
+cmpEPOenabled TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "EPO enabled"
+ ::= 15
+
+cmpUnabletotrunonUPS TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Unalbe to turn on UPS"
+ ::= 16
+
+cmpOvertemperaturealarm TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Over temperature alarm"
+ ::= 17
+
+cmpInputfrequnstablebypass TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Input frequency unstable in bypass"
+ ::= 18
+
+
+cmpChargeralarm TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Charger alarm"
+ ::= 19
+
+
+cmpL1inputfusenotwork TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "L1 input fuse not working"
+ ::= 20
+
+cmpNeutralnotConnected TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Neutral not connected"
+ ::= 21
+
+cmpL2inputfusenotwork TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "L2 input fuse not working"
+ ::= 22
+
+cmpL3inputfusenotwork TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "L3 input fuse not working"
+ ::= 23
+
+
+cmpPositivePFCabnormalL1 TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Positive PFC abnormal in L1"
+ ::= 24
+
+
+cmpNegativePFCabnormalL1 TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Negative PFC abnormal in L1"
+ ::= 25
+
+
+cmpPositivePFCabnormalL2 TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Positive PFC abnormal in L2"
+ ::= 26
+
+cmpNegativePFCabnormalL2 TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Negative PFC abnormal in L2"
+ ::= 27
+
+cmpPositivePFCabnormalL3 TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Positive PFC abnormal in L3"
+ ::= 28
+
+cmpNegativePFCabnormalL3 TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Negative PFC abnormal in L3"
+ ::= 29
+
+
+cmpBusvoltagenotwds TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Bus voltage not within default setting"
+ ::= 30
+
+
+cmpBusvoltageovermaxvalue TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Bus voltage over maxinum value"
+ ::= 31
+
+cmpBusvoltagebelowminvalue TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Bus voltage below mininum value"
+ ::= 32
+
+cmpBusvoltagediffoutofrange TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Bus voltage differences out fo acceptable range"
+ ::= 33
+
+cmpBusvoltageofsloperatetoofast TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Bus voltage of slope rate drops too fast"
+ ::= 34
+
+cmpOvercurrentinPFCII TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "WARNING:Over current in PFC input inductor."
+ ::= 35
+
+cmpInvertervoloutofrange TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Inverter voltage not within default setting."
+ ::= 36
+
+cmpInvertervolovermaxvalue TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Inverter voltage over maximum value."
+ ::= 37
+
+cmpInvertervolbelowminvalue TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Inverter voltage below minimum value."
+ ::= 38
+
+
+cmpBatteryoppositelyconnected TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Battery oppositely connected."
+ ::= 39
+
+cmpL2phaseshortcicuited TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "L2Phase inverter short-cicuited."
+ ::= 40
+
+cmpL3phaseshortcicuited TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "L3Phase inverter short-cicuited."
+ ::= 41
+
+cmpL1L2invertershortcicuited TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "L1L2Inverter short-cicuited."
+ ::= 42
+
+cmpL2L3invertershortcicuited TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "L2L3Inverter short-cicuited."
+ ::= 43
+
+cmpL3L1invertershortcicuited TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "L3L1Inverter short-cicuited."
+ ::= 44
+
+
+cmpL1negativepoweroutofrange TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "L1 inverter negative powere out of acceptable range."
+ ::= 45
+
+cmpL2negativepoweroutofrange TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "L2 inverter negative powere out of acceptable range."
+ ::= 46
+
+cmpL3negativepoweroutofrange TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "L3 inverter negative powere out of acceptable range."
+ ::= 47
+
+cmpBatterySCRshortcircuited TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Battery SCR short-circuited."
+ ::= 48
+
+cmpLineSCRshortcircuited TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Line SCR short-circuited."
+ ::= 49
+
+cmpInverterrelayopenfault TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Inverter relay open fault."
+ ::= 50
+
+cmpInverterrelayshortcircuited TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Inverter relay short-circuited."
+ ::= 51
+
+cmpInoutwiresoppositelyconnected TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Input and output wires oppositely connected."
+ ::= 52
+
+cmpabnormalcanbuscommunication TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Abnormal in CAN-bus communication."
+ ::= 53
+
+cmpcommfailurebcupsboard TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Communication failure between cpus in control board.Or DSP and MCU communication error"
+ ::= 54
+
+cmpabnormalsyncsignalcircuit TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Abnomal in synchronous signal circuit."
+ ::= 55
+
+cmpabnormalsyncpulsesignalcircuit TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Abnomal in synchronous pulse signal circuit."
+ ::= 56
+
+
+cmpcurrent3punbalancedetected TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Warning for a three-phase input current unbalance detected."
+ ::= 57
+
+cmpbatteryselftestfailure TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Battery self-test failure."
+ ::= 58
+
+cmpintercurrentunbalance TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Inverter inter-current unbalance."
+ ::= 59
+
+cmpbatterydisconnected TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Battery disconnected."
+ ::= 60
+
+cmpabnormalhostsignalcircuit TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Abnormal in host signal circuit."
+ ::= 61
+
+cmpbatteryovercharged TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Bettery overcharged."
+ ::= 62
+
+cmpbatteryvoltoohigh TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Bettery voltage is too high."
+ ::= 63
+
+cmpbatteryvoltoolow TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Bettery voltage is too low."
+ ::= 64
+
+cmpfemaleconnectornotconnwell TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Female connector of parallel cable not connected well."
+ ::= 65
+
+cmpmaleconnectornotconnwell TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Male connector of parallel cable not connected well."
+ ::= 66
+
+
+cmplockingbypassA3COW30M TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Locking inbypass mode after 3 consecutive overloads within 30 minutes"
+
+ ::= 67
+
+
+cmpparallelcabledisconnected TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Parallel cable disconnected"
+
+ ::= 68
+
+cmpsyncpulsecircuitfault TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Synchronous pulse signal circuit fault"
+
+ ::= 69
+
+
+cmpsyncsignalcircuitfalt TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Synchronous signal circuit fault"
+
+ ::= 70
+
+cmphostsignalcircuitfault TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Host signal circuit fault"
+
+ ::= 71
+
+cmpcanbuscommunicationfault TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Can-bus communication fault"
+
+ ::= 72
+
+cmplowlosspointforvolinACmode TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Low loss point for voltage in ac mode not consistent in parallel systems"
+
+ ::= 73
+
+cmphighlosspointforvolinACmode TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "High loss point for voltage in ac mode not consistent in parallel systems"
+
+ ::= 74
+
+cmplowlosspointforfreqinACmode TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Low loss point for frequency in ac mode not consistent in parallel systems"
+
+ ::= 75
+
+cmphighlosspointforfreqinACmode TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "High loss point for frequency in ac mode not consistent in parallel systems"
+
+ ::= 76
+
+cmplowlosspointforvolinbypassmode TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Low loss point for voltage in bypass mode not consistent in parallel systems"
+
+ ::= 77
+
+
+cmphighlosspointforvolinbypassmode TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "High loss point for voltage in bypass mode not consistent in parallel systems"
+
+ ::= 78
+
+
+cmplowlosspointforfreqinbypassmode TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Low loss point for frequency in bypass mode not consistent in parallel systems"
+
+ ::= 79
+
+cmphighlosspointforfreqinbypassmode TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "High loss point for frequency in bypass mode not consistent in parallel systems"
+
+ ::= 80
+
+cmploadunbalanced TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Load unbalanced"
+
+ ::= 81
+
+
+cmpoverloadalarm TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Overload alarm"
+
+ ::= 82
+
+
+cmpparallelnotconnectedwell TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Parallel cable not connected well"
+
+ ::= 83
+
+cmpcommunicationlost TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Communication lost"
+ ::= 84
+
+
+cmpbatteryconnnotsonsistent TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Battery connection not consistent in parallel systems"
+ ::= 85
+
+
+cmpconverternotconsisstent TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Converter setting not consistent in parallel systems"
+ ::= 86
+
+cmpbypassnotallownotconsistent TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Bypass not allowed setting not consistent in parallel systems"
+ ::= 87
+
+
+cmpACconnnotconsistent TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "AC connection not consistent in parallel systems"
+ ::= 88
+
+cmpinput3pcurrentunbalance TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Warning for three-phase ac input current unbalance"
+ ::= 89
+
+cmpbypassconnnotconsistent TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Bypass connection not consistent in parallel systems"
+ ::= 90
+
+cmpbatteryprotectionnotconsistent TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Battery protection setting not consistent in parallel systems"
+ ::= 91
+
+cmpbatterydetectionnotconsistent TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Battery detection setting not consistent in parallel systems"
+ ::= 92
+
+
+
+cmpupsmodeltypesnotconsistent TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "UPS model types not consistent in parallel systems"
+ ::= 93
+
+cmpbypassnotconsistent TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Bypass setting not consistent in parallel systems"
+ ::= 94
+
+
+cmpcapacitynotconsistent TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Capacity of upss not consistent in parallel systems"
+ ::= 95
+
+cmpautorestartnotconsistent TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Auto restart setting not consistent in parallel systems"
+ ::= 96
+
+
+cmpBatteryReplace TRAP-TYPE ENTERPRISE upsTraps
+ DESCRIPTION
+ "Battery need to be replace"
+ ::= 97
+
+
+cmpACNormal TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "AC normal"
+ ::= 100
+
+cmpOutputBadAlarm TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Output bad alarm"
+ ::= 103
+
+
+cmpBypassBadAlarm TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Bypass bad alarm"
+ ::= 104
+
+
+cmpOutputOffAlarm TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Output off alarm"
+ ::= 105
+
+
+cmpUPSShutAlarm TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "UPS shutdown alarm"
+ ::= 106
+
+cmpSystemOffAlarm TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "System off alarm"
+ ::= 107
+
+cmpFuseFailureAlarm TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Fuse failure alarm"
+ ::= 108
+
+cmpGenFailureAlarm TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "General failure alarm"
+ ::= 109
+
+cmpAwaitPowerAlarm TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Awaiting power alarm"
+ ::= 110
+
+cmpShutPendingAlarm TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Shutdown pending alarm"
+ ::= 111
+
+cmpBatDepleted TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Battery depleted"
+ ::= 112
+
+
+cmpUnknowStatus TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Battery unknow status"
+ ::= 113
+
+cmpOutputOn TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Output on"
+ ::= 114
+
+cmpTurntobypass TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Ups turn to bypass mode"
+ ::= 115
+
+cmpTurntobattery TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Ups turn to battery mode"
+ ::= 116
+
+cmpOutBooster TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Turn to booster"
+ ::= 117
+
+
+cmpOutReducer TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Turn to reducer"
+ ::= 118
+
+cmpOutBattest TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Turn to battery test mode"
+ ::= 119
+
+
+cmpOtherSource TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Other source"
+ ::= 120
+
+cmpBatfailure TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Battery failure"
+ ::= 121
+
+
+cmpBatTestDonePassed TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Battery test passed"
+ ::= 122
+
+cmpBatTestDoneWarning TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Battery test done warning "
+ ::= 123
+
+
+cmpBatTestDoneAborted TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Battery test done Aborted"
+ ::= 124
+
+cmpBatteryNormal TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Battery normal"
+ ::= 125
+
+cmpBatteryDischarging TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Battery Discharging "
+ ::= 126
+
+cmpP1cutoffprealarm TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "P1 cut off pre-alarm "
+ ::= 127
+
+cmpInputPhaseError TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Warning for input phase error for LV 6-10K UPS"
+ ::= 128
+cmpMaintainSwitchOpenalarm TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "Warning for maintain switch open"
+ ::= 129
+
+cmpEMDChAbnormal1 TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "EMD Channels 1 Abnormal"
+ ::= 130
+cmpEMDChAbnormal2 TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "EMD Channels 2 Abnormal"
+ ::= 131
+cmpEMDChAbnormal3 TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "EMD Channels 3 Abnormal"
+ ::= 132
+cmpEMDChAbnormal4 TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "EMD Channels 4 Abnormal"
+ ::= 133
+cmpEMDChAbnormal5 TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "EMD Channels 5 Abnormal: smoke alarm"
+ ::= 134
+cmpEMDChAbnormal6 TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "EMD Channels 6 Abnormal"
+ ::= 135
+cmpEMDChAbnormal7 TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "EMD Channels 7 Abnormal"
+ ::= 136
+cmpEMDChAbnormal8 TRAP-TYPE
+ ENTERPRISE upsTraps
+ DESCRIPTION
+ "EMD Channels 8 Abnormal"
+ ::= 137
+--===============================================================================
+--extend
+--===============================================================================
+
+extendWorkTemperature OBJECT-TYPE
+ SYNTAX INTEGER (-2200..2200)
+ UNITS "degrees 0.1 Centigrade"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The temperature of work environment"
+ ::= { extend 1 }
+
+extendWorkhumidity OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ UNITS "percent"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The humidity of work environment"
+ ::= { extend 2 }
+
+
+extendSmokeScope OBJECT-TYPE
+ SYNTAX INTEGER (0..1000000)
+ UNITS "%/FOOT"
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The smokeScope of work environment"
+ ::= { extend 3 }
+
+
+extendEMDAlarm1 OBJECT-TYPE
+ SYNTAX INTEGER {
+ on(1),
+ off(0)
+ }
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Environment detector alarm 1"
+ ::= { extend 4 }
+
+extendEMDAlarm2 OBJECT-TYPE
+ SYNTAX INTEGER {
+ on(1),
+ off(0)
+ }
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Environment detector alarm 2"
+ ::= { extend 5 }
+
+
+extendEMDAlarm3 OBJECT-TYPE
+ SYNTAX INTEGER {
+ on(1),
+ off(0)
+ }
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Environment detector alarm 3"
+ ::= { extend 6 }
+
+extendEMDAlarm4 OBJECT-TYPE
+ SYNTAX INTEGER {
+ on(1),
+ off(0)
+ }
+ ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Environment detector alarm 4"
+ ::= { extend 7 }
+
+END